Table of Contents

Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:04

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2020-06-03 20:04:38


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 31637.07 683.01 683.01
Net Site Energy 31637.07 683.01 683.01
Total Source Energy 93084.77 2009.59 2009.59
Net Source Energy 93084.77 2009.59 2009.59


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 2782.93 0.00 0.00 0.00 0.00
Cooling 2486.74 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4294.36 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 882.57 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.29 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2044.08 0.00 0.00 0.00 0.00 0.00
Fans 2290.71 0.00 0.00 0.00 0.00 0.00
Pumps 279.21 0.00 0.00 0.00 0.00 0.00
Heat Rejection 715.94 0.00 0.00 0.00 0.00 987.87
Humidification 16.91 0.00 0.00 0.00 0.00 6.29
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 630.35 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 28223.80 3413.27 0.00 0.00 0.00 3274.33
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 2782.93 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 245.67 0.00 0.00 0.00 0.00 0.00
  Other 2241.07 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 4294.36 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 882.57 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.86 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.73 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1895.08 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 61.27 0.00 0.00 0.00 0.00 0.00
Fans General 2290.71 0.00 0.00 0.00 0.00 0.00
Pumps General 279.21 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 19.04 0.00 0.00 0.00 0.00 0.00
  Other 696.90 0.00 0.00 0.00 0.00 987.87
Humidification General 16.91 0.00 0.00 0.00 0.00 6.29
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 630.35 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 111.76 0.00 0.00 0.00 0.00 0.00
HVAC 124.99 73.69 0.00 0.00 0.00 0.07
Other 372.57 0.00 0.00 0.00 0.00 0.00
Total 609.32 73.69 0.00 0.00 0.00 0.07


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 111.76 0.00 0.00 0.00 0.00 0.00
HVAC 124.99 73.69 0.00 0.00 0.00 0.07
Other 372.57 0.00 0.00 0.00 0.00 0.00
Total 609.32 73.69 0.00 0.00 0.00 0.07


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 28223.802 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 28223.802 100.00
     
Total On-Site and Utility Electric Sources 28223.802 100.00
Total Electricity End Uses 28223.802 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 3274.33 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 3274.33 100.00
Total Water End Uses 3274.33 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 3.83
Time Setpoint Not Met During Occupied Cooling 46.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 1342.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Meter |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Meter |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

| Meter |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

| Meter |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | DUMMY BOILER |

DXReportMonthly

| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SHWSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |

PlantLoopDemandReportMonthly

| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

General

Value
Program Version and Build EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:04
RunPeriod RUNPERIOD 1
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.6875 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.6875 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.6875 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.6875 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.6875 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.6875 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.6875 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.6875 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.6875 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.6875 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.6875 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.6875 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.6875 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.6875 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.6875 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.6875 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.6875   215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 9.6875   215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.6875   215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.6875   484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.6875 19.08 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.6875 19.08 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 14-AUG-15:00 30-DEC-07:10 - - - 21-JUL-15:00
Heating 0.00 1347538.30 0.00 0.00 0.00 0.00
Cooling 322783.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting 373325.05 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 92996.58 0.00 0.00 0.00 0.00 0.00
Fans 131984.60 0.00 0.00 0.00 0.00 0.00
Pumps 50246.68 0.00 0.00 0.00 0.00 0.00
Heat Rejection 79510.01 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 8146.58 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1844850.50 1355684.88 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 1347538.30 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 170355.60 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 373325.05 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5498.40 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 85555.38 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 1942.80 0.00 0.00 0.00 0.00 0.00
Fans General 131984.60 0.00 0.00 0.00 0.00 0.00
Pumps General 50246.68 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 30261.73 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 8146.58 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 3016.69 0.00 0.00 0.00
Cooling 7875.50 0.00 0.00 0.00 0.00
Interior Lighting 13600.23 0.00 0.00 0.00 0.00
Exterior Lighting 2795.10 0.00 0.00 0.00 0.00
Interior Equipment 48180.48 0.00 0.00 0.00 0.00
Exterior Equipment 6473.60 0.00 0.00 0.00 0.00
Fans 7254.69 0.00 0.00 0.00 0.00
Pumps 884.25 0.00 0.00 0.00 0.00
Heat Rejection 2267.39 0.00 0.00 0.00 0.00
Humidification 53.54 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 683.29 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 89384.78 3699.99 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 65.13 0.00 0.00 0.00
Cooling 170.02 0.00 0.00 0.00 0.00
Interior Lighting 293.61 0.00 0.00 0.00 0.00
Exterior Lighting 60.34 0.00 0.00 0.00 0.00
Interior Equipment 1040.16 0.00 0.00 0.00 0.00
Exterior Equipment 139.76 0.00 0.00 0.00 0.00
Fans 156.62 0.00 0.00 0.00 0.00
Pumps 19.09 0.00 0.00 0.00 0.00
Heat Rejection 48.95 0.00 0.00 0.00 0.00
Humidification 1.16 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.75 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1929.71 79.88 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 65.13 0.00 0.00 0.00
Cooling 170.02 0.00 0.00 0.00 0.00
Interior Lighting 293.61 0.00 0.00 0.00 0.00
Exterior Lighting 60.34 0.00 0.00 0.00 0.00
Interior Equipment 1040.16 0.00 0.00 0.00 0.00
Exterior Equipment 139.76 0.00 0.00 0.00 0.00
Fans 156.62 0.00 0.00 0.00 0.00
Pumps 19.09 0.00 0.00 0.00 0.00
Heat Rejection 48.95 0.00 0.00 0.00 0.00
Humidification 1.16 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.75 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1929.71 79.88 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.80
DATACENTER BOT DIRECT AIR 0.494742
DATACENTER MID DIRECT AIR 4.73
DATACENTER TOP DIRECT AIR 0.480420
DATACENTER BASEMENT DIRECT AIR 21.48
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.99 0.317799 0.300000 1.80 0.847465 0.500000 0.001199 0.000395 1.80 12.80 0.008000
CORE_MID VAV BOX COMPONENT 56.21 0.338372 0.300000 16.86 0.902325 0.500000 0.001126 0.006958 16.86 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.42 0.350883 0.300000 1.63 0.935688 0.500000 0.001086 0.001516 2.06 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.804415 0.296887 0.300000 0.241325 0.791699 0.500000 0.001283 0.000100 0.241325 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.12 0.137088 0.300000 0.336803 0.365567 0.500000 0.002779 0.000115 0.336803 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.44 0.165935 0.300000 0.431782 0.442493 0.500000 0.002296 0.000187 0.431782 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.35 0.114263 0.300000 0.404080 0.304702 0.500000 0.003334 0.000094 0.404080 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 7.22 0.330658 0.300000 2.17 0.881754 0.500000 0.001152 0.002772 3.78 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 11.48 0.134114 0.300000 3.44 0.357638 0.500000 0.002841 0.002077 3.44 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 14.46 0.165115 0.300000 4.34 0.440307 0.500000 0.002307 0.002929 4.34 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.89 0.129433 0.300000 3.57 0.345153 0.500000 0.002944 0.001921 3.57 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.817852 0.292009 0.300000 0.245356 0.778692 0.500000 0.001305 0.000409 0.558400 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.13 0.136477 0.300000 0.338309 0.363939 0.500000 0.002792 0.000272 0.370966 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.54 0.154918 0.300000 0.462487 0.413116 0.500000 0.002459 0.000413 0.562869 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.26 0.122580 0.300000 0.376664 0.326880 0.500000 0.003108 0.000260 0.376664 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 17886.58 0.000395 311.32
CORE_MID VAV BOX REHEAT COIL 314945.10 0.006958 5869.85
CORE_TOP VAV BOX REHEAT COIL 68631.55 0.001516 1433.26
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4506.00 0.000100 83.98
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5185.50 0.000115 94.73
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 8468.98 0.000187 158.82
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4275.63 0.000094 74.92
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 125476.25 0.002772 2618.68
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 94021.39 0.002077 1865.66
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 132555.83 0.002929 2701.81
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 86962.61 0.001921 1686.89
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 18533.00 0.000409 386.67
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 12311.28 0.000272 256.86
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 18680.96 0.000413 389.76
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11782.18 0.000260 241.68
CAV_BAS_HEATC 283742.84 0.006269 5242.17
VAV_BOT WITH REHEAT_HEATC 56389.63 0.001246 811.43
VAV_MID WITH REHEAT_HEATC 535140.61 0.011823 7673.54
VAV_TOP WITH REHEAT_HEATC 55727.30 0.001231 799.09
DATACENTER_EXTRAWATERHEATC 1030312.18 0.022763 19167.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
CAV_BAS 5.80 5.80 5.80 5.80 5.80 5.80 1.00 1.00 5.80
VAV_BOT WITH REHEAT 5.35 3.21 10.70 3.21 9.42 9.42 0.300000 0.340646 9.42
VAV_MID WITH REHEAT 50.63 30.38 101.26 30.38 87.14 87.14 0.300000 0.348644 87.14
VAV_TOP WITH REHEAT 5.08 3.05 10.16 3.90 9.07 9.07 0.300000 0.429738 9.07
AIRLOOP DATACENTER BASEMENT 21.48 21.48 21.48 21.48 21.48 21.48 1.00 1.00 21.48
AIRLOOP DATACENTER BOT 0.494742 0.494742 0.494742 0.494742 0.494742 0.494742 1.00 1.00 0.494742
AIRLOOP DATACENTER MID 4.73 4.73 4.73 4.73 4.73 4.73 1.00 1.00 4.73
AIRLOOP DATACENTER TOP 0.480420 0.480420 0.480420 0.480420 0.480420 0.480420 1.00 1.00 0.480420
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
CAV_BAS_OA_CONTROLLER 5.80 1.20
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.42 2.71
VAV_MID WITH REHEAT_OA_CONTROLLER 87.14 28.43
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.07 3.01
AIRLOOP DATACENTER BASEMENT OA CONTROLLER 21.48 0.338372
AIRLOOP DATACENTER BOT OA CONTROLLER 0.494742  
AIRLOOP DATACENTER MID OA CONTROLLER 4.73  
AIRLOOP DATACENTER TOP OA CONTROLLER 0.480420  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Inlet Air Humidity Ratio Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio
CAV_BAS_COOLC 96017.04 0.004085 5.80 0.008835 24.07 6.67 11.28 0.008367
VAV_BOT WITH REHEAT_COOLC 164371.26 0.006993 9.42 0.008712 24.74 6.67 11.28 0.008367
VAV_MID WITH REHEAT_COOLC 1533547.29 0.065241 87.14 0.008713 24.86 6.67 11.28 0.008367
VAV_TOP WITH REHEAT_COOLC 158410.05 0.006739 9.07 0.008693 24.80 6.67 11.28 0.008367
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
CAV_BAS_COOLC_CONTROLLER 0.004085 0.000117
CAV_BAS_HEATC_CONTROLLER 0.006269  
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.006993 0.000068
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.001246  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.065241 0.000007
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.011823  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.006739 0.000071
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.001231  
DATACENTER_BAS_HEATC_CONTROLLER 0.022763 0.000021
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.42
VAV_MID WITH REHEAT FAN 87.14
VAV_TOP WITH REHEAT FAN 9.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT 21.48 422590.74 304636.26 0.010349
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT 0.494742 9432.84 6910.17 0.000231
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID 4.73 90063.21 65986.74 0.002206
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP 0.480420 9158.08 6709.51 0.000224
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.48 21.48 21.48 21.48 422590.74 422590.74 17945.27 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.494742 0.494742 0.494742 0.494742 9432.84 9432.84 829.00 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.73 4.73 4.73 4.73 90063.21 90063.21 8289.97 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.480420 0.480420 0.480420 0.480420 9158.08 9158.08 829.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
DATACENTER BASEMENT SUPPLY FAN 21.48
DATACENTER BOT SUPPLY FAN 0.494742
DATACENTER MID SUPPLY FAN 4.73
DATACENTER TOP SUPPLY FAN 0.480420
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT 21.48 422590.74 0.010349
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT 0.494742 9432.84 0.000231
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID 4.73 90063.21 0.002206
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP 0.480420 9158.08 0.000224
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT 17945.27  
DATACENTER_EXTRAELECHEATC 422590.74 10000000.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT 829.00  
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID 8289.97  
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP 829.00  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER BASEMENT HUMIDIFIER 0.000144 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP SECONDARY 0.083057 19892.93
HEATSYS1 PUMP 0.063752 16287.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.083057 9.97
SHWSYS1 0.000440 0.052800
HEATSYS1 0.063752 7.65
COOLSYS1_SUPPLY 0.083057 9.97
SINGLE WATER PLANT LOOP 0.013010 1.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.083057 0.083057 348633.15 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SHWSYS1 PUMP 0.000440 56.21
COOLSYS1 PUMP 0.083057 6630.98
PLANT CIRC PUMP 0.013010 3318.24
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2885535.39 1442767.70 0.063752
DUMMY BOILER 535906.76 93894.07 0.013010
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.083057 0.041787 983354.55 989339.96 0.050403
COOLSYS1 CHILLER2 0.083057 0.041787 983354.55 989339.96 0.050403
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013010 139666.47 60475.04 69833.23 7879.72 21530.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.100805 12.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.100805 25753.32
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 40.25 940233.75 8.05 117529.22
TOWERWATERSYS COOLTOWER 2 40.25 940233.75 8.05 117529.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 48
WSHPPLANT OPERATION SCHEME 0.040682
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Version

Version ID
1 9.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.30 6.70 4.10 4.20 4.20 5.90 9.00 10.00 13.30 15.00 15.70 13.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 William R Fairchild WA USA TMY3 WMO#=727885 48.12 -123.50 -8.00 91.00 100237 1.1914


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.23 11.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance

Adjust Zone Mixing

Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}
Infiltration Zones {MixingSourceZonesOnly
AllZones}
1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.688 4.842 0.000 0.000 0.000 0.000 14.529 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.758 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.688 8.070 0.000 0.000 0.000 0.000 17.757 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 0.0 N/A 0.000 9.688 215.299 0.000 0.000 0.000 0.000 224.987 No
21 DATACENTER_MID_ZN_6 36.20 0.0 N/A 0.000 9.688 215.299 0.000 0.000 0.000 0.000 224.987 No
22 DATACENTER_TOP_ZN_6 36.20 0.0 N/A 0.000 9.688 215.299 0.000 0.000 0.000 0.000 224.987 No
23 DATACENTER_BASEMENT_ZN_6 783.68 0.0 N/A 0.000 9.688 484.423 0.000 0.000 0.000 0.000 494.111 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation
1 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
2 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
3 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
4 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
5 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
6 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
7 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
8 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
9 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
10 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
11 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
12 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
13 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
14 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
15 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
16 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS BLDG_LIGHT_SCH BASEMENT 2779.43 149.6 26925.749 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 26925.749
2 CORE_BOTTOM_LIGHTS BLDG_LIGHT_SCH CORE_BOTTOM 2496.12 134.4 24181.215 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 24181.215
3 CORE_MID_LIGHTS BLDG_LIGHT_SCH CORE_MID 2496.12 134.4 24181.215 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 24181.215
4 CORE_TOP_LIGHTS BLDG_LIGHT_SCH CORE_TOP 2496.12 134.4 24181.215 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 24181.215
5 PERIMETER_BOT_ZN_3_LIGHTS BLDG_LIGHT_SCH PERIMETER_BOT_ZN_3 313.41 16.9 3036.193 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3036.193
6 PERIMETER_BOT_ZN_2_LIGHTS BLDG_LIGHT_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1956.638 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1956.638
7 PERIMETER_BOT_ZN_1_LIGHTS BLDG_LIGHT_SCH PERIMETER_BOT_ZN_1 313.42 16.9 3036.259 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3036.259
8 PERIMETER_BOT_ZN_4_LIGHTS BLDG_LIGHT_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1956.638 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1956.638
9 PERIMETER_MID_ZN_3_LIGHTS BLDG_LIGHT_SCH PERIMETER_MID_ZN_3 313.41 16.9 3036.193 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3036.193
10 PERIMETER_MID_ZN_2_LIGHTS BLDG_LIGHT_SCH PERIMETER_MID_ZN_2 201.98 10.9 1956.638 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1956.638
11 PERIMETER_MID_ZN_1_LIGHTS BLDG_LIGHT_SCH PERIMETER_MID_ZN_1 313.42 16.9 3036.259 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3036.259
12 PERIMETER_MID_ZN_4_LIGHTS BLDG_LIGHT_SCH PERIMETER_MID_ZN_4 201.98 10.9 1956.638 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1956.638
13 PERIMETER_TOP_ZN_3_LIGHTS BLDG_LIGHT_SCH PERIMETER_TOP_ZN_3 313.41 16.9 3036.193 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3036.193
14 PERIMETER_TOP_ZN_2_LIGHTS BLDG_LIGHT_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1956.638 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1956.638
15 PERIMETER_TOP_ZN_1_LIGHTS BLDG_LIGHT_SCH PERIMETER_TOP_ZN_1 313.42 16.9 3036.259 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3036.259
16 PERIMETER_TOP_ZN_4_LIGHTS BLDG_LIGHT_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1956.638 9.688 179.982 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1956.638
17 DATACENTER_BASEMENT_LIGHTS BLDG_LIGHT_SCH DATACENTER_BASEMENT_ZN_6 783.68 0.0 7591.909 9.688 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7591.909
18 DATACENTER_BOT_LIGHTS BLDG_LIGHT_SCH DATACENTER_BOT_ZN_6 36.20 0.0 350.715 9.688 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 350.715
19 DATACENTER_MID_LIGHTS BLDG_LIGHT_SCH DATACENTER_MID_ZN_6 36.20 0.0 350.715 9.688 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 350.715
20 DATACENTER_TOP_LIGHTS BLDG_LIGHT_SCH DATACENTER_TOP_ZN_6 36.20 0.0 350.715 9.688 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 350.715


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 0.0 379632.522 484.423 N/A 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 0.0 7794.422 215.299 N/A 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 0.0 7794.422 215.299 N/A 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 0.0 7794.422 215.299 N/A 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.092 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL 20 3 9 0.167 0.4744 0.900 0.900 0.700 0.700 MediumRough
10 BASEMENT_WALL_EAST_CFACTOR 30 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
11 BASEMENT_WALL_SOUTH_CFACTOR 31 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
12 BASEMENT_WALL_NORTH_CFACTOR 32 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 33 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 34 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 35 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4781
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION 0.0000 0.000 0.000 0.000 1.941
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
19 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
20 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
21 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
22 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
23 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
24 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.0917746 2.0917746 2.0917746  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.31219756E-14 -0.25237900E-15 -0.17078023E-09 -0.40080417E-16
51 8 0.24827770E-07 0.64895754E-13 0.40814970E-03 -0.28230026E-09
52 7 -0.13145170E-01 0.32788080E-08 -0.24386180E-01 0.14946539E-03
53 6 0.42990022 0.11289000E-05 0.49294528 -0.50371474E-02
54 5 -5.4301032 0.41776872E-04 -4.6011904 0.66154067E-01
55 4 34.062169 0.33899226E-03 22.064921 -0.43618800
56 3 -113.47938 0.73347792E-03 -56.858567 1.5477483
57 2 199.36357 0.40991987E-03 79.008039 -2.9361691
58 1 -171.98885 0.43498902E-04 -55.585984 2.7600347
59 0 57.057407 0.24596459E-06 15.505383  
60 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
61 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
62 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
63 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
64 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
65 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
66 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
67 0 0.43108349 0.21254961E-04 60.838472  
68 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
69 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
70 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
71 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
72 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
73 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
74 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
75 0 0.43108349 0.21254961E-04 60.838472  
76 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
77 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
78 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
79 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
80 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
81 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
82 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
83 0 0.43108349 0.21254961E-04 60.838472  
84 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
85 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
86 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
87 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
88 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
89 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
90 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
91 0 0.43108349 0.21254961E-04 60.838472  
92 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
93 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
94 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
95 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
96 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
97 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
98 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
99 0 0.43108349 0.21254961E-04 60.838472  
100 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
101 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
102 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
103 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
104 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
105 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
106 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
107 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.38_SHGC_0.4 29 1 VerySmooth 2.159 0.394 0.315 0.401


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.45900E-002 0.31435 0.47939 0.47939 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11893 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Calculation Method Value {days} Allowable Number Figures in Shadow Overlap {} Polygon Clipping Algorithm Sky Diffuse Modeling Algorithm External Shading Calculation Method Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 AverageOverDaysInFrequency 30 15000 SutherlandHodgman SimpleSkyDiffuseModeling InternalCalculation No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SHWSYS1 WATER HEATER 1.1356 87921.3 0.000 0.0000


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.119 3.783E-004 5.690E-004 0.496 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.831E-002 3.877E-004 5.690E-004 0.509 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.119 3.783E-004 5.690E-004 0.496 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.831E-002 3.877E-004 5.690E-004 0.509 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.642E-004 5.690E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.609E-002 3.767E-004 5.690E-004 0.494 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.642E-004 5.690E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.609E-002 3.767E-004 5.690E-004 0.494 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.642E-004 5.690E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.609E-002 3.767E-004 5.690E-004 0.494 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.642E-004 5.690E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.609E-002 3.767E-004 5.690E-004 0.494 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.744E-005 5.690E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.744E-005 5.690E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.741E-005 4.376E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 79643.03171 79643.03171 5.79632 5.79632 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.38408E-003 2779.42662 149.60210 1.20008 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20008 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   -4.30000 2.65759E-003 2779.42662 149.60210 1.20008 0.00000
3 CORE_BOTTOM Cooling 82245.44136 82245.44136 5.98505 5.98505 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.38408E-003 2496.12046 134.35320 1.07776 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07776 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   -4.30000 2.65759E-003 2496.12046 134.35320 1.07776 0.00000
5 CORE_MID Cooling 772651.04092 772651.04092 56.21164 56.21164 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.38408E-003 2496.12046 134.35320 10.77757 0.00000
6 CORE_MID Heating 146954.03731 146954.03731 6.21188 10.77757 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 2496.12046 134.35320 10.77757 0.00000
7 CORE_TOP Cooling 73815.42616 73815.42616 5.42074 5.42074 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 26.40000 8.38408E-003 2496.12046 134.35320 1.07776 0.00000
8 CORE_TOP Heating 48094.93815 48094.93815 2.06153 2.06153 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 2496.12046 134.35320 1.07776 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 10954.04073 10954.04073 0.80442 0.80442 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.38408E-003 313.41284 16.86939 0.13532 0.00000
10 PERIMETER_BOT_ZN_3 Heating 2107.60232 2107.60232 8.98209E-002 0.13532 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41284 16.86939 0.13532 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 15288.16253 15288.16253 1.12268 1.12268 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 20.24233 8.38408E-003 201.97515 10.87127 8.72074E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 1837.33507 1837.33507 7.80563E-002 8.72074E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72074E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 19599.29096 19599.29096 1.43927 1.43927 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 26.02083 8.38408E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 4173.95566 4173.95566 0.17830 0.17830 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 18341.92864 18341.92864 1.34693 1.34693 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.97433 8.38408E-003 201.97515 10.87127 8.72074E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 268.10883 268.10883 1.15752E-002 8.72074E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72074E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 99257.82060 99257.82060 7.22259 7.22259 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.38408E-003 313.41284 16.86939 1.35323 0.00000
18 PERIMETER_MID_ZN_3 Heating 87882.15805 87882.15805 3.77708 3.77708 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41284 16.86939 1.35323 0.00000
19 PERIMETER_MID_ZN_2 Cooling 156270.24373 156270.24373 11.47566 11.47566 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 21.10683 8.38408E-003 201.97515 10.87127 0.87207 0.00000
20 PERIMETER_MID_ZN_2 Heating 59752.69482 59752.69482 2.56877 2.56877 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 0.87207 0.00000
21 PERIMETER_MID_ZN_1 Cooling 196966.12451 196966.12451 14.46419 14.46419 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 26.09667 8.38408E-003 313.41969 16.86975 1.35326 0.00000
22 PERIMETER_MID_ZN_1 Heating 89364.75085 89364.75085 3.84113 3.84113 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41969 16.86975 1.35326 0.00000
23 PERIMETER_MID_ZN_4 Cooling 161922.86007 161922.86007 11.89076 11.89076 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 24.82267 8.38408E-003 201.97515 10.87127 0.87207 0.00000
24 PERIMETER_MID_ZN_4 Heating 51466.11299 51466.11299 2.21082 2.21082 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 0.87207 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 11137.02865 11137.02865 0.81785 0.81785 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.40000 8.38408E-003 313.41284 16.86939 0.13532 0.00000
26 PERIMETER_TOP_ZN_3 Heating 12971.97880 12971.97880 0.55840 0.55840 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41284 16.86939 0.13532 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15356.45311 15356.45311 1.12770 1.12770 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 21.10683 8.38408E-003 201.97515 10.87127 8.72074E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 8616.81620 8616.81620 0.37097 0.37097 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72074E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 20993.08672 20993.08672 1.54162 1.54162 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.38408E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 13075.40704 13075.40704 0.56287 0.56287 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 17097.47958 17097.47958 1.25555 1.25555 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 24.82267 8.38408E-003 201.97515 10.87127 8.72074E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 8031.33251 8031.33251 0.34567 0.34567 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72074E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8542.54715 8542.54715 0.49474 0.49474 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 23.30600 8.38409E-003 36.20274 0.00000 1.56314E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56314E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   -4.30000 2.65759E-003 36.20274 0.00000 1.56314E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 81586.77862 81586.77862 4.72510 4.72510 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 23.30600 8.38409E-003 36.20274 0.00000 0.15631 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15631 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   -4.30000 2.65759E-003 36.20274 0.00000 0.15631 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8295.26515 8295.26515 0.48042 0.48042 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 23.30600 8.38409E-003 36.20274 0.00000 1.56314E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56314E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   -4.30000 2.65759E-003 36.20274 0.00000 1.56314E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370877.45234 370877.45234 21.47938 21.47938 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 06:00:00 17.48200 8.38408E-003 783.67941 0.00000 0.33837 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33837 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   -4.30000 2.65759E-003 783.67941 0.00000 0.33837 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 CAV_BAS Cooling Sensible 72058.37 5.79632 5.79632 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 CAV_BAS Heating Sensible 63645.36 1.20008 1.20008 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 VAV_BOT WITH REHEAT Cooling Sensible 125684.87 9.42182 9.42182 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_BOT WITH REHEAT Heating Sensible 32054.10 1.56580 1.56580 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 VAV_MID WITH REHEAT Cooling Sensible 1140608.11 87.13612 87.13612 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_MID WITH REHEAT Heating Sensible 474433.34 23.17537 23.17537 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00
7 VAV_TOP WITH REHEAT Cooling Sensible 130235.67 9.07399 9.07399 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
8 VAV_TOP WITH REHEAT Heating Sensible 61705.79 3.89944 3.89944 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 10:00:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 364348.60 21.47938 21.47938 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 17945.27 0.33837 0.33837 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8341.32 0.49474 0.49474 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 829.00 1.56314E-002 1.56314E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 79633.91 4.72510 4.72510 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 8289.97 0.15631 0.15631 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8097.87 0.48042 0.48042 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 829.00 1.56314E-002 1.56314E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:Uncontrolled BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.79632
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.98505
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31780
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.79551
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84746
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.19887E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.95182E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.79551
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17886.58116
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.95182E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 311.32055
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 56.21164
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33837
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.86349
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90232
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12598E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.95833E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.86349
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 314945.09698
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.95833E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5869.84580
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.42074
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35088
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.62622
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.93569
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08583E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.51633E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.06153
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 68631.55038
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.51633E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1433.26417
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80442
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29689
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24132
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79170
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.28332E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.95545E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24132
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4505.99628
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.95545E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 83.97903
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12268
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13709
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33680
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36557
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.77924E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.14567E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33680
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5185.49926
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.14567E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 94.72982
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.43927
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16594
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.43178
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44249
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.29608E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.87112E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43178
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8468.97540
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.87112E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 158.81634
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.34693
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11426
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40408
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30470
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.33440E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.44649E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.40408
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4275.63231
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.44649E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 74.92103
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.22259
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33066
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.16678
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88175
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.15225E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.77224E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.77708
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 125476.24604
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.77224E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2618.68153
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.47566
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13411
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.44270
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35764
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.84086E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.07729E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.44270
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 94021.39029
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.07729E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1865.66132
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.46419
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16512
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.33926
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44031
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.30748E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.92866E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.33926
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 132555.82816
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.92866E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2701.81389
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.89076
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12943
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.56723
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34515
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.94362E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.92133E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.56723
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 86962.61249
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.92133E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1686.88929
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.81785
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29201
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24536
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.77869
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.30475E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.09464E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55840
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18532.99923
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.09464E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 386.67374
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12770
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13648
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33831
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36394
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.79167E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.72003E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37097
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12311.27785
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.72003E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 256.85775
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.54162
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15492
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.46249
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41312
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.45936E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.12733E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.56287
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18680.96333
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.12733E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 389.75861
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.25555
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12258
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37666
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32688
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.10817E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.60313E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37666
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11782.17675
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.60313E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 241.67769
212 AirTerminal:SingleDuct:Uncontrolled DATACENTER BOT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49474
213 AirTerminal:SingleDuct:Uncontrolled DATACENTER MID DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.72510
214 AirTerminal:SingleDuct:Uncontrolled DATACENTER TOP DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48042
215 AirTerminal:SingleDuct:Uncontrolled DATACENTER BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.47938
216 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.79632
217 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.79632
218 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.79632
219 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.79632
220 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.79632
221 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.79632
222 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
223 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
224 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.34917
225 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.20950
226 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.69834
227 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.20950
228 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.42182
229 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.42182
230 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34065
232 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 50.63242
233 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 30.37945
234 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 101.26484
235 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 30.37945
236 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 87.13612
237 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 87.13612
238 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34864
240 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.08173
241 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.04904
242 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.16346
243 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.89944
244 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.07399
245 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.07399
246 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
247 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.42974
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.47938
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.47938
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.47938
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.47938
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.47938
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.47938
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49474
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49474
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49474
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49474
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49474
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49474
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.72510
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.72510
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.72510
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.72510
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.72510
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.72510
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48042
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48042
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48042
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.48042
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.48042
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.48042
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.79632
281 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.42182
282 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 87.13612
283 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.07399
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.47938
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49474
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.72510
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.48042
288 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.79632
289 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20008
290 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Coil Load [W] 96017.04188
291 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Water Flow Rate [m3/s] 4.08479E-003
292 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Air Flow Rate [m3/s] 5.79632
293 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Inlet Air Humidity Ratio 8.83457E-003
294 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Inlet Air Temperature [C] 24.06796
295 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Inlet Water Temperature [C] 6.67000
296 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Outlet Air Temperature [C] 11.28028
297 Coil:Cooling:Water CAV_BAS_COOLC Design Size Design Outlet Air Humidity Ratio 8.36692E-003
298 Coil:Heating:Water CAV_BAS_HEATC Design Size Rated Capacity [W] 283742.83722
299 Coil:Heating:Water CAV_BAS_HEATC Design Size Maximum Water Flow Rate [m3/s] 6.26895E-003
300 Coil:Heating:Water CAV_BAS_HEATC Design Size U-Factor Times Area Value [W/K] 5242.16983
301 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.79632
302 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.08479E-003
303 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.16577E-004
304 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.26895E-003
305 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.42182
306 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.71265
307 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Coil Load [W] 164371.25883
308 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Water Flow Rate [m3/s] 6.99273E-003
309 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Air Flow Rate [m3/s] 9.42182
310 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Inlet Air Humidity Ratio 8.71224E-003
311 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Inlet Air Temperature [C] 24.73956
312 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Inlet Water Temperature [C] 6.67000
313 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Outlet Air Temperature [C] 11.27994
314 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC Design Size Design Outlet Air Humidity Ratio 8.36692E-003
315 Coil:Heating:Water VAV_BOT WITH REHEAT_HEATC Design Size Rated Capacity [W] 56389.62856
316 Coil:Heating:Water VAV_BOT WITH REHEAT_HEATC Design Size Maximum Water Flow Rate [m3/s] 1.24586E-003
317 Coil:Heating:Water VAV_BOT WITH REHEAT_HEATC Design Size U-Factor Times Area Value [W/K] 811.43042
318 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.42182
319 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.99273E-003
320 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.80979E-005
321 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.24586E-003
322 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 87.13612
323 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 28.42906
324 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Coil Load [W] 1533547.28592
325 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Water Flow Rate [m3/s] 6.52406E-002
326 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Air Flow Rate [m3/s] 87.13612
327 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Inlet Air Humidity Ratio 8.71335E-003
328 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Inlet Air Temperature [C] 24.86309
329 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Inlet Water Temperature [C] 6.67000
330 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Outlet Air Temperature [C] 11.27994
331 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC Design Size Design Outlet Air Humidity Ratio 8.36692E-003
332 Coil:Heating:Water VAV_MID WITH REHEAT_HEATC Design Size Rated Capacity [W] 535140.61416
333 Coil:Heating:Water VAV_MID WITH REHEAT_HEATC Design Size Maximum Water Flow Rate [m3/s] 1.18233E-002
334 Coil:Heating:Water VAV_MID WITH REHEAT_HEATC Design Size U-Factor Times Area Value [W/K] 7673.54224
335 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 87.13612
336 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.52406E-002
337 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.29898E-006
338 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.18233E-002
339 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.07399
340 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 3.01498
341 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Coil Load [W] 158410.04590
342 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Water Flow Rate [m3/s] 6.73913E-003
343 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Air Flow Rate [m3/s] 9.07399
344 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Inlet Air Humidity Ratio 8.69303E-003
345 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Inlet Air Temperature [C] 24.79719
346 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Inlet Water Temperature [C] 6.67000
347 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Outlet Air Temperature [C] 11.27989
348 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC Design Size Design Outlet Air Humidity Ratio 8.36692E-003
349 Coil:Heating:Water VAV_TOP WITH REHEAT_HEATC Design Size Rated Capacity [W] 55727.30215
350 Coil:Heating:Water VAV_TOP WITH REHEAT_HEATC Design Size Maximum Water Flow Rate [m3/s] 1.23123E-003
351 Coil:Heating:Water VAV_TOP WITH REHEAT_HEATC Design Size U-Factor Times Area Value [W/K] 799.09055
352 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.07399
353 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.73913E-003
354 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.06605E-005
355 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.23123E-003
356 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.47938
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33837
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Air Flow Rate [m3/s] 21.47938
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Total Cooling Capacity [W] 422590.73731
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Sensible Cooling Capacity [W] 304636.25905
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Water Flow Rate [m3/s] 1.03492E-002
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.47938
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.47938
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.47938
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.47938
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 422590.73731
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 422590.73731
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 17945.26944
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
370 Fan:OnOff DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.47938
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Air Flow Rate [m3/s] 21.47938
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Heating Capacity [W] 422590.73731
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT Design Size Rated Water Flow Rate [m3/s] 1.03492E-002
374 Coil:Heating:Electric HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT Design Size Nominal Capacity [W] 17945.26944
375 Humidifier:Steam:Electric DATACENTER BASEMENT HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.44059E-004
376 Humidifier:Steam:Electric DATACENTER BASEMENT HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
377 Humidifier:Steam:Electric DATACENTER BASEMENT HUMIDIFIER Design Size Rated Power [W] 96450.69782
378 Humidifier:Steam:Electric DATACENTER BASEMENT HUMIDIFIER User-Specified Rated Power [W] 100000.00000
379 Coil:Heating:Electric DATACENTER_EXTRAELECHEATC Design Size Nominal Capacity [W] 422590.73731
380 Coil:Heating:Electric DATACENTER_EXTRAELECHEATC User-Specified Nominal Capacity [W] 10000000.00000
381 Coil:Heating:Water DATACENTER_EXTRAWATERHEATC Design Size Rated Capacity [W] 1030312.17778
382 Coil:Heating:Water DATACENTER_EXTRAWATERHEATC Design Size Maximum Water Flow Rate [m3/s] 2.27635E-002
383 Coil:Heating:Water DATACENTER_EXTRAWATERHEATC Design Size U-Factor Times Area Value [W/K] 19167.73258
384 Controller:WaterCoil DATACENTER_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.27635E-002
385 Controller:WaterCoil DATACENTER_BAS_HEATC_CONTROLLER Controller Convergence Tolerance 2.09190E-005
386 Controller:OutdoorAir AIRLOOP DATACENTER BOT OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49474
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT Design Size Rated Air Flow Rate [m3/s] 0.49474
388 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT Design Size Rated Total Cooling Capacity [W] 9432.84014
389 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT Design Size Rated Sensible Cooling Capacity [W] 6910.17062
390 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT Design Size Rated Water Flow Rate [m3/s] 2.31010E-004
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49474
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49474
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49474
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49474
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9432.84014
396 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9432.84014
397 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 828.99711
398 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
399 Fan:OnOff DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49474
400 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT Design Size Rated Air Flow Rate [m3/s] 0.49474
401 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT Design Size Rated Heating Capacity [W] 9432.84014
402 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT Design Size Rated Water Flow Rate [m3/s] 2.31010E-004
403 Coil:Heating:Electric HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT Design Size Nominal Capacity [W] 828.99711
404 Controller:OutdoorAir AIRLOOP DATACENTER MID OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.72510
405 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID Design Size Rated Air Flow Rate [m3/s] 4.72510
406 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID Design Size Rated Total Cooling Capacity [W] 90063.21347
407 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID Design Size Rated Sensible Cooling Capacity [W] 65986.73617
408 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID Design Size Rated Water Flow Rate [m3/s] 2.20564E-003
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.72510
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.72510
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.72510
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.72510
413 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 90063.21347
414 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 90063.21347
415 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 8289.97105
416 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
417 Fan:OnOff DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.72510
418 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID Design Size Rated Air Flow Rate [m3/s] 4.72510
419 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID Design Size Rated Heating Capacity [W] 90063.21347
420 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID Design Size Rated Water Flow Rate [m3/s] 2.20564E-003
421 Coil:Heating:Electric HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID Design Size Nominal Capacity [W] 8289.97105
422 Controller:OutdoorAir AIRLOOP DATACENTER TOP OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48042
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP Design Size Rated Air Flow Rate [m3/s] 0.48042
424 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP Design Size Rated Total Cooling Capacity [W] 9158.08390
425 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP Design Size Rated Sensible Cooling Capacity [W] 6709.51007
426 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP Design Size Rated Water Flow Rate [m3/s] 2.24281E-004
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48042
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48042
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48042
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48042
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9158.08390
432 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9158.08390
433 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 828.99711
434 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
435 Fan:OnOff DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48042
436 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP Design Size Rated Air Flow Rate [m3/s] 0.48042
437 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP Design Size Rated Heating Capacity [W] 9158.08390
438 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP Design Size Rated Water Flow Rate [m3/s] 2.24281E-004
439 Coil:Heating:Electric HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP Design Size Nominal Capacity [W] 828.99711
440 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 8.30573E-002
441 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 19892.93374
442 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 8.30573E-002
443 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 9.96688
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 8.30573E-002
445 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 8.30573E-002
446 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 348633.14867
447 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
448 PlantLoop SHWSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
449 PlantLoop SHWSYS1 Plant Loop Volume [m3] 5.28000E-002
450 Pump:ConstantSpeed SHWSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
451 Pump:ConstantSpeed SHWSYS1 PUMP Design Power Consumption [W] 56.20535
452 WaterHeater:Mixed SHWSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
453 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 6.37524E-002
454 PlantLoop HEATSYS1 Plant Loop Volume [m3] 7.65029
455 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 6.37524E-002
456 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 16287.91518
457 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2885535.38577
458 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1442767.69500
459 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 6.37524E-002
460 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 8.30573E-002
461 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 9.96688
462 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 8.30573E-002
463 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 6630.97791
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 8.30573E-002
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.17874E-002
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 983354.54977
467 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 989339.96000
468 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.04027E-002
469 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 8.30573E-002
470 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.17874E-002
471 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 983354.54977
472 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 989339.96000
473 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.04027E-002
474 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.30102E-002
475 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.56122
476 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.30102E-002
477 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3318.23957
478 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.30102E-002
479 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
480 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 60475.03514
481 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
482 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
483 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21530.40190
484 Boiler:HotWater DUMMY BOILER Design Size Nominal Capacity [W] 535906.75838
485 Boiler:HotWater DUMMY BOILER User-Specified Nominal Capacity [W] 93894.07000
486 Boiler:HotWater DUMMY BOILER Design Size Design Water Flow Rate [m3/s] 1.30102E-002
487 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.10081
488 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 12.09664
489 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.10081
490 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 25753.31533
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 40.25044
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 940233.74535
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 8.05009
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 117529.21817
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 40.25044
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 940233.74535
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 8.05009
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 117529.21817
499 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 48 4.06820E-002
500 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 48 4.06820E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 16969.30
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 299021.98
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 65117.49
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4278.18
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4924.39
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 8040.43
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4056.24
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 119051.85
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 89230.90
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 125780.02
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 82547.45
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 17584.12
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11680.95
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 17724.51
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11179.61
16 Coil:Heating:Water CAV_BAS_HEATC 225480.90
17 Coil:Heating:Water VAV_BOT WITH REHEAT_HEATC 43171.76
18 Coil:Heating:Water VAV_MID WITH REHEAT_HEATC 407633.84
19 Coil:Heating:Water VAV_TOP WITH REHEAT_HEATC 42449.28
20 Coil:Heating:Water DATACENTER_EXTRAWATERHEATC 827153.50


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water CAV_BAS_COOLC 144243.03 101223.73 43019.31 0.70 18994.51 192.65
2 Coil:Cooling:Water VAV_BOT WITH REHEAT_COOLC 241688.73 167782.71 73906.02 0.69 32089.32 325.47
3 Coil:Cooling:Water VAV_MID WITH REHEAT_COOLC 2241549.90 1554270.63 687279.27 0.69 296503.44 3007.30
4 Coil:Cooling:Water VAV_TOP WITH REHEAT_COOLC 232753.54 161576.97 71176.57 0.69 30874.04 313.14


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.94 23.67
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.94 23.67


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.092 2.092   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_0.4 N/A 2.159 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.474 0.443   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1
2 VETERANS DAY Holiday InputFile 11/11 1
3 CHRISTMAS Holiday InputFile 12/25 1
4 INDEPENDENCE DAY Holiday InputFile 07/04 1
5 MLK DAY Holiday InputFile 01/16 1
6 PRESIDENTS DAY Holiday InputFile 02/20 1
7 MEMORIAL DAY Holiday InputFile 05/29 1
8 LABOR DAY Holiday InputFile 09/04 1
9 COLUMBUS DAY Holiday InputFile 10/09 1
10 THANKSGIVING Holiday InputFile 11/23 1


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Environment:WarmupDays

NumberofWarmupDays
1 25


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.3692205972 0.4643055168 Pass Pass 1.4206684242 2.2073232240 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.3285279057E-002 0.1033741983 Pass Fail 7.0853287918E-003 8.3884147626E-002 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 3.6940028631E-003 3.6232064349E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 4.6460363780E-002 2.2654792299E-002 Pass Pass 0.3705841899 0.5417537795 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.5457799144E-002 5.7275695069E-002 Pass Fail 7.0534659025E-003 8.3691899378E-002 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 5.8845200120E-002 0.1334766769 Pass Fail 7.0212667363E-003 8.3498213245E-002 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 8.4954050904E-002 0.1436708367 Pass Pass 7.1736285645E-003 8.4409124974E-002 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 5.7050751449E-002 0.1434677196 Pass Fail 6.9446805720E-003 8.2722291290E-002 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.2973360552E-002 2.0216198535E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 4.4566273036E-002 5.6960350870E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 7.7258346580E-002 8.9349470145E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 3.7670922785E-002 4.1027084805E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1709870373 0.1737369400 Pass Pass 2.2894377664 8.2956730560 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1256542968 0.1385537106 Pass Pass 3.1340168794 12.8022262503 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1041543017 0.1260872617 Pass Pass 1.3083744590 6.4265378793 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 4.7830333975E-002 5.4338914685E-002 Pass Pass 10.0576533287 71.2257061916 Pass Fail
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.6479264633E-003 1.7639889925E-002 Pass Pass 7.1819199773E-003 7.5702008848E-002 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.7807005124E-003 9.6291805425E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.8371725596E-002 6.3885159457E-002 Pass Pass 0.3314480496 0.4619502708 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 2.6867397196E-014 2.7126928863E-014 Pass Pass 2.6831011800E-003 2.9995375941E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 1.5419764231E-014 1.4125252783E-014 Pass Pass 9.2765211222E-003 9.9493363577E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 2.1168018740E-002 2.0335743677E-002 Pass Pass 8.0602638815E-003 9.7287997046E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 9.3234062446E-014 7.4454391738E-014 Pass Pass 4.0463112962E-005 2.6734443445E-005 Pass Pass



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL 0.30 0.443 0.474 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL 0.30 0.443 0.474 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL 0.30 0.443 0.474 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL 0.30 0.443 0.474 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL 0.30 0.443 0.474 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL 0.30 0.443 0.474 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL 0.30 0.443 0.474 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL 0.30 0.443 0.474 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL 0.30 0.443 0.474 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL 0.30 0.443 0.474 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL 0.30 0.443 0.474 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL 0.30 0.443 0.474 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL 0.30 0.443 0.474 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL 0.30 0.443 0.474 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL 0.30 0.443 0.474 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL 0.30 0.443 0.474 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL 0.30 0.443 0.474 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL 0.30 0.443 0.474 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL 0.30 0.443 0.474 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL 0.30 0.443 0.474 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL 0.30 0.443 0.474 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL 0.30 0.443 0.474 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL 0.30 0.443 0.474 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL 0.30 0.443 0.474 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.221 0.228 3563.11 3563.11 180.00 0.00  
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00   0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00   0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00   0.419 139.09 139.09 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00   0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00   0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00   0.419 118.87 118.87 270.00 90.00 W


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.38_SHGC_0.4 19.32 0.00 0.00 19.32 19.32 2.159 0.394 0.401     No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.38_SHGC_0.4 19.32 0.00 0.00 19.32 19.32 2.159 0.394 0.401     No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.38_SHGC_0.4 19.32 0.00 0.00 19.32 19.32 2.159 0.394 0.401     No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.38_SHGC_0.4 17.38 0.00 0.00 17.38 17.38 2.159 0.394 0.401     No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.38_SHGC_0.4 19.32 0.00 0.00 19.32 19.32 2.159 0.394 0.401     No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.38_SHGC_0.4 19.32 0.00 0.00 19.32 19.32 2.159 0.394 0.401     No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.38_SHGC_0.4 19.32 0.00 0.00 19.32 19.32 2.159 0.394 0.401     No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.38_SHGC_0.4 86.92 0.00 0.00 86.92 869.21 2.159 0.394 0.401     No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.38_SHGC_0.4 57.95 0.00 0.00 57.95 579.48 2.159 0.394 0.401     No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.38_SHGC_0.4 86.92 0.00 0.00 86.92 869.21 2.159 0.394 0.401     No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.38_SHGC_0.4 57.95 0.00 0.00 57.95 579.48 2.159 0.394 0.401     No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.38_SHGC_0.4 86.92 0.00 0.00 86.92 86.92 2.159 0.394 0.401     No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.38_SHGC_0.4 57.95 0.00 0.00 57.95 57.95 2.159 0.394 0.401     No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.38_SHGC_0.4 86.92 0.00 0.00 86.92 86.92 2.159 0.394 0.401     No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.38_SHGC_0.4 57.95 0.00 0.00 57.95 57.95 2.159 0.394 0.401     No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average           3476.85 2.159 0.394 0.401              
North Total or Average           1043.06 2.159 0.394 0.401              
Non-North Total or Average           2433.80 2.159 0.394 0.401              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.593 2.092 1.95 PERIMETER_BOT_ZN_4_WALL_WEST



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT 9.6875 2779.43 26925.75 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 257.68
CORE_BOTTOM_LIGHTS CORE_BOTTOM 9.6875 2496.12 24181.22 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 231.41
CORE_MID_LIGHTS CORE_MID 9.6875 24961.20 241812.15 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 2314.14
CORE_TOP_LIGHTS CORE_TOP 9.6875 2496.12 24181.22 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 231.41
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 9.6875 313.41 3036.19 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 29.06
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 9.6875 201.98 1956.64 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 18.73
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 9.6875 313.42 3036.26 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 29.06
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 9.6875 201.98 1956.64 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 18.73
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 9.6875 3134.13 30361.93 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 290.56
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 9.6875 2019.75 19566.38 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 187.25
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 9.6875 3134.20 30362.59 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 290.57
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 9.6875 2019.75 19566.38 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 187.25
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 9.6875 313.41 3036.19 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 29.06
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 9.6875 201.98 1956.64 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 18.73
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 9.6875 313.42 3036.26 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 29.06
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 9.6875 201.98 1956.64 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 18.73
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 9.6875 783.68 7591.91 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 72.65
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 9.6875 36.20 350.71 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 3.36
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 9.6875 362.03 3507.15 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 33.56
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 9.6875 36.20 350.71 LightsWired BLDG_LIGHT_SCH 52.33 168.00 50.98 0.0000 Y 3.36
Interior Lighting Total   9.6875 46320.38 448729.56               1321.34


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 56280.71 AstronomicalClock -   83.54 83.54 882.57
Exterior Lighting Total 56280.71           882.57



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 1947855.81      
HEATSYS1 BOILER Boiler:HotWater 1442767.70 0.81    
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 989339.96 5.17 6.94 23.67
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 989339.96 5.17 6.94 23.67
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00      
DUMMY BOILER Boiler:HotWater 93894.07 0.80    
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 940233.75      
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 940233.75      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CAV_BAS_COOLC Coil:Cooling:Water 96017.04 144243.03 101223.73 43019.31 0.70 - 18994.51 192.65
VAV_BOT WITH REHEAT_COOLC Coil:Cooling:Water 164371.26 241688.73 167782.71 73906.02 0.69 - 32089.32 325.47
VAV_MID WITH REHEAT_COOLC Coil:Cooling:Water 1533547.29 2241549.90 1554270.63 687279.27 0.69 - 296503.44 3007.30
VAV_TOP WITH REHEAT_COOLC Coil:Cooling:Water 158410.05 232753.54 161576.97 71176.57 0.69 - 30874.04 313.14
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT Coil:Cooling:WaterToAirHeatPump:EquationFit   422590.74 304636.26 117954.48 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT Coil:Cooling:WaterToAirHeatPump:EquationFit   9432.84 6910.17 2522.67 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID Coil:Cooling:WaterToAirHeatPump:EquationFit   90063.21 65986.74 24076.48 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP Coil:Cooling:WaterToAirHeatPump:EquationFit   9158.08 6709.51 2448.57 0.73 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 17886.58 16969.30 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 314945.10 299021.98 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 68631.55 65117.49 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 4506.00 4278.18 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 5185.50 4924.39 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 8468.98 8040.43 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 4275.63 4056.24 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 125476.25 119051.85 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 94021.39 89230.90 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 132555.83 125780.02 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 86962.61 82547.45 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 18533.00 17584.12 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 12311.28 11680.95 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 18680.96 17724.51 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11782.18 11179.61 -
CAV_BAS_HEATC Coil:Heating:Water 283742.84 225480.90 -
VAV_BOT WITH REHEAT_HEATC Coil:Heating:Water 56389.63 43171.76 -
VAV_MID WITH REHEAT_HEATC Coil:Heating:Water 535140.61 407633.84 -
VAV_TOP WITH REHEAT_HEATC Coil:Heating:Water 55727.30 42449.28 -
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT Coil:Heating:WaterToAirHeatPump:EquationFit   422590.74 0.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT Coil:Heating:WaterToAirHeatPump:EquationFit   9432.84 0.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID Coil:Heating:WaterToAirHeatPump:EquationFit   90063.21 0.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP Coil:Heating:WaterToAirHeatPump:EquationFit   9158.08 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT Coil:Heating:Electric   17945.27 1.00
DATACENTER_EXTRAELECHEATC Coil:Heating:Electric   10000000.00 1.00
DATACENTER_EXTRAWATERHEATC Coil:Heating:Water 1030312.18 827153.50 -
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT Coil:Heating:Electric   829.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID Coil:Heating:Electric   8289.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP Coil:Heating:Electric   829.00 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
CAV_BAS FAN Fan:ConstantVolume 0.60 1110.54 5.80 10717.69 1849.05 1.00 1.14 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.42 21516.87 2283.73 1.00 1.11 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 87.14 198995.17 2283.73 1.00 1.07 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.07 20722.52 2283.73 1.00 1.12 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00
DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.48 35612.23 1657.97 1.00 1.13 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 554.16 1120.11 1.00 1.61 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.73 5292.62 1120.11 1.00 1.16 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 538.12 1120.11 1.00 1.62 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 168135.01 0.083057 19892.93 239508.57 0.90 General
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 179352.00 0.063752 16287.92 255487.18 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 56045.00 0.083057 6630.98 79836.19 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013010 3318.24 255050.01 0.90 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 179344.01 0.100805 25753.32 255475.80 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 79643.03 79643.03 28.65 5.796 5.796 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00894 19.67 0.00838 1.200 0.00
CORE_BOTTOM 82245.44 82245.44 32.95 5.985 5.985 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00888 19.67 0.00838 1.078 0.00
CORE_MID 772651.04 772651.04 309.54 56.212 56.212 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00890 19.67 0.00838 10.778 0.00
CORE_TOP 73815.43 73815.43 29.57 5.421 5.421 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00891 26.40 0.00838 1.078 0.00
PERIMETER_BOT_ZN_3 10954.04 10954.04 34.95 0.804 0.804 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00885 26.17 0.00838 0.135 0.00
PERIMETER_BOT_ZN_2 15288.16 15288.16 75.69 1.123 1.123 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 24.00 24.00 0.00866 20.24 0.00838 0.087 0.00
PERIMETER_BOT_ZN_1 19599.29 19599.29 62.53 1.439 1.439 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00869 26.02 0.00838 0.135 0.00
PERIMETER_BOT_ZN_4 18341.93 18341.93 90.81 1.347 1.347 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00863 24.97 0.00838 0.087 0.00
PERIMETER_MID_ZN_3 99257.82 99257.82 316.70 7.223 7.223 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00889 19.67 0.00838 1.353 0.00
PERIMETER_MID_ZN_2 156270.24 156270.24 773.71 11.476 11.476 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 24.00 24.00 0.00866 21.11 0.00838 0.872 0.00
PERIMETER_MID_ZN_1 196966.12 196966.12 628.44 14.464 14.464 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00869 26.10 0.00838 1.353 0.00
PERIMETER_MID_ZN_4 161922.86 161922.86 801.70 11.891 11.891 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 24.00 24.00 0.00865 24.82 0.00838 0.872 0.00
PERIMETER_TOP_ZN_3 11137.03 11137.03 35.53 0.818 0.818 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00884 26.40 0.00838 0.135 0.00
PERIMETER_TOP_ZN_2 15356.45 15356.45 76.03 1.128 1.128 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 24.00 24.00 0.00866 21.11 0.00838 0.087 0.00
PERIMETER_TOP_ZN_1 20993.09 20993.09 66.98 1.542 1.542 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00868 26.17 0.00838 0.135 0.00
PERIMETER_TOP_ZN_4 17097.48 17097.48 84.65 1.256 1.256 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 24.00 24.00 0.00864 24.82 0.00838 0.087 0.00
DATACENTER_BOT_ZN_6 8542.55 8542.55 235.96 0.495 0.495 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00850 23.31 0.00838 0.016 0.00
DATACENTER_MID_ZN_6 81586.78 81586.78 2253.61 4.725 4.725 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00850 23.31 0.00838 0.156 0.00
DATACENTER_TOP_ZN_6 8295.27 8295.27 229.13 0.480 0.480 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00850 23.31 0.00838 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370877.45 370877.45 473.25 21.479 21.479 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 06:00:00 27.00 27.00 0.00850 17.48 0.00838 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   0.00 21.00 0.00800 -4.30 0.00266 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   0.00 21.00 0.00800 -4.30 0.00266 1.078 0.00
CORE_MID 146954.04 146954.04 58.87 6.212 10.778 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -4.30 0.00266 10.778 0.00
CORE_TOP 48094.94 48094.94 19.27 2.062 2.062 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -4.30 0.00266 1.078 0.00
PERIMETER_BOT_ZN_3 2107.60 2107.60 6.72 0.090 0.135 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00677 -4.30 0.00266 0.135 0.00
PERIMETER_BOT_ZN_2 1837.34 1837.34 9.10 0.078 0.087 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00692 -4.30 0.00266 0.087 0.00
PERIMETER_BOT_ZN_1 4173.96 4173.96 13.32 0.178 0.178 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00727 -4.30 0.00266 0.135 0.00
PERIMETER_BOT_ZN_4 268.11 268.11 1.33 0.012 0.087 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00559 -4.30 0.00266 0.087 0.00
PERIMETER_MID_ZN_3 87882.16 87882.16 280.40 3.777 3.777 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00761 -4.30 0.00266 1.353 0.00
PERIMETER_MID_ZN_2 59752.69 59752.69 295.84 2.569 2.569 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -4.30 0.00266 0.872 0.00
PERIMETER_MID_ZN_1 89364.75 89364.75 285.13 3.841 3.841 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 -4.30 0.00266 1.353 0.00
PERIMETER_MID_ZN_4 51466.11 51466.11 254.81 2.211 2.211 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00748 -4.30 0.00266 0.872 0.00
PERIMETER_TOP_ZN_3 12971.98 12971.98 41.39 0.558 0.558 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00787 -4.30 0.00266 0.135 0.00
PERIMETER_TOP_ZN_2 8616.82 8616.82 42.66 0.371 0.371 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00788 -4.30 0.00266 0.087 0.00
PERIMETER_TOP_ZN_1 13075.41 13075.41 41.72 0.563 0.563 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00788 -4.30 0.00266 0.135 0.00
PERIMETER_TOP_ZN_4 8031.33 8031.33 39.76 0.346 0.346 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 -4.30 0.00266 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   0.00 18.00 0.00800 -4.30 0.00266 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   0.00 18.00 0.00800 -4.30 0.00266 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   0.00 18.00 0.00800 -4.30 0.00266 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB   0.00 18.00 0.00800 -4.30 0.00266 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CAV_BAS 5.80 5.80 1.20 1.20 5.7963 5.7963 5.7963 1.0000 1.0000
VAV_BOT WITH REHEAT 9.42 9.42 1.57 1.57 9.4218 3.2095 9.4218 0.3406 0.3000
VAV_MID WITH REHEAT 87.14 87.14 23.18 23.18 87.1361 30.3795 87.1361 0.3486 0.3000
VAV_TOP WITH REHEAT 9.07 9.07 3.90 3.90 9.0740 3.8994 9.0740 0.4297 0.3000
AIRLOOP DATACENTER BASEMENT 21.48 21.48 0.34 0.34 21.4794 21.4794 21.4794 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.49 0.49 0.02 0.02 0.4947 0.4947 0.4947 1.0000 1.0000
AIRLOOP DATACENTER MID 4.73 4.73 0.16 0.16 4.7251 4.7251 4.7251 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.48 0.48 0.02 0.02 0.4804 0.4804 0.4804 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 17886.581 17886.581 1.795514 0.00039518 311.321 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 16969.30 17886.58 1.795514 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00800000 51.1678 0.00 0.00 17958.53 17958.53
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 314945.097 314945.097 16.863493 0.00695833 5869.846 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 299021.98 314945.10 16.863493 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00800000 51.1678 146954.04 0.00 316459.39 316459.39
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 68631.550 68631.550 2.061533 0.00151633 1433.264 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 65117.49 68631.55 2.061533 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00800000 51.1678 48094.94 0.00 68944.92 68944.92
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 4505.996 4505.996 0.241325 0.00009955 83.979 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4278.18 4506.00 0.241325 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00676836 43.3773 2107.60 0.00 4527.66 4527.66
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 5185.499 5185.499 0.336803 0.00011457 94.730 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4924.39 5185.50 0.336803 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00692299 44.3579 1837.34 0.00 5211.08 5211.08
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 8468.975 8468.975 0.431782 0.00018711 158.816 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8040.43 8468.98 0.431782 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00726552 46.5274 4173.96 0.00 8509.53 8509.53
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 4275.632 4275.632 0.404080 0.00009446 74.921 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4056.24 4275.63 0.404080 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00558910 35.8858 268.11 0.00 4292.79 4292.79
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 125476.246 125476.246 3.777082 0.00277224 2618.682 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 119051.85 125476.25 3.777082 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00760590 48.6812 87882.16 0.00 126049.12 126049.12
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 94021.390 94021.390 3.442697 0.00207729 1865.661 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 89230.90 94021.39 3.442697 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00764628 48.9363 59752.69 0.00 94458.08 94458.08
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 132555.828 132555.828 4.339258 0.00292866 2701.814 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 125780.02 132555.83 4.339258 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00762322 48.7906 89364.75 0.00 133161.48 133161.48
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 86962.612 86962.612 3.567228 0.00192133 1686.889 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 82547.45 86962.61 3.567228 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00748463 47.9149 51466.11 0.00 87375.48 87375.48
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 18532.999 18532.999 0.558400 0.00040946 386.674 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17584.12 18533.00 0.558400 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00787298 50.3672 12971.98 0.00 18617.61 18617.61
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 12311.278 12311.278 0.370966 0.00027200 256.858 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11680.95 12311.28 0.370966 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00788129 50.4197 8616.82 0.00 12367.48 12367.48
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 18680.963 18680.963 0.562869 0.00041273 389.759 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17724.51 18680.96 0.562869 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00787543 50.3827 13075.41 0.00 18766.25 18766.25
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11782.177 11782.177 0.376664 0.00026031 241.678 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11179.61 11782.18 0.376664 12.80 11.50 0.00800000 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00783825 50.1482 8031.33 0.00 11835.96 11835.96
CAV_BAS_COOLC Coil:Cooling:Water AirLoopHVAC CAV_BAS 96017.042 -999.000 5.796322 0.00408479 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 96017.04 88033.99 5.796322 24.07 16.57 0.00883457 11.28 11.28 0.00836692 24.31 0.00838408 16.27 20.7042 24.00 0.00893830 47.5752 78557.44 0.00 110045.21 93347.50
CAV_BAS_HEATC Coil:Heating:Water AirLoopHVAC CAV_BAS 283742.837 283742.837 5.796322 0.00626895 5242.170 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 225480.90 283742.84 5.796322 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 20.7042 21.00 0.00800000 51.1678 0.00 0.00 237872.78 237872.78
VAV_BOT WITH REHEAT_COOLC Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 164371.259 -999.000 9.421817 0.00699273 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 164371.26 154532.16 9.421817 24.74 16.70 0.00871224 11.28 12.00 0.00836692 26.40 0.00838408 17.00 28.7912 24.00 0.00879854 46.8411 119738.58 0.00 187244.80 161351.03
VAV_BOT WITH REHEAT_HEATC Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 56389.629 56389.629 2.826545 0.00124586 811.430 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 43171.76 56389.63 2.826545 -4.30 -4.30 0.00265759 12.80 11.50 0.00800000 -4.30 0.00265759 -4.30 95.9705 21.00 0.00761566 48.7401 8387.00 0.00 45649.70 45649.70
VAV_MID WITH REHEAT_COOLC Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1533547.286 -999.000 87.136118 0.06524065 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 1533547.29 1442248.83 87.136118 24.86 16.75 0.00871335 11.28 12.00 0.00836692 26.40 0.00838408 17.00 32.6260 24.00 0.00881527 46.9290 1075515.97 0.00 1745117.56 1505081.96
VAV_MID WITH REHEAT_HEATC Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 535140.614 535140.614 26.140835 0.01182328 7673.542 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 407633.84 535140.61 26.140835 -4.30 -4.30 0.00265759 12.80 11.50 0.00800000 -4.30 0.00265759 -4.30 108.7534 21.00 0.00778495 49.8114 435419.75 0.00 431025.83 431025.83
VAV_TOP WITH REHEAT_COOLC Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 158410.046 -999.000 9.073990 0.00673913 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 158410.05 149461.08 9.073990 24.80 16.71 0.00869303 11.28 12.00 0.00836692 26.40 0.00838408 17.00 33.2266 24.00 0.00880976 46.9000 123478.11 0.00 180438.99 156002.31
VAV_TOP WITH REHEAT_HEATC Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 55727.302 55727.302 2.722197 0.00123123 799.091 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 10:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 42449.28 55727.30 2.722197 -4.29 -4.29 0.00266032 12.80 11.50 0.00800000 -4.30 0.00265759 -4.30 110.7554 21.00 0.00793820 50.7784 69628.68 0.00 44885.22 44885.22
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 422590.737 304636.259 21.479376 0.01034922 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 06:00:00 454715.71 454715.71 -999.0 28.41 17.77 0.00849817 12.80 12.00 0.00849817 26.40 0.00838408 17.00 -999.0000 27.00 0.00850000 37.8820 370318.00 0.00 -999.00 -999.00
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9432.840 6910.171 0.494742 0.00023101 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 10203.19 10203.19 -999.0 27.84 17.58 0.00849634 12.80 12.00 0.00849634 23.31 0.00838409 15.92 -999.0000 27.00 0.00850000 37.8820 8542.55 0.00 -999.00 -999.00
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90063.213 65986.736 4.725100 0.00220564 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 97423.73 97423.73 -999.0 27.83 17.58 0.00849617 12.80 12.00 0.00849617 23.31 0.00838409 15.92 -999.0000 27.00 0.00850000 37.8820 81586.78 0.00 -999.00 -999.00
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9158.084 6709.510 0.480420 0.00022428 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 9906.34 9906.34 -999.0 27.84 17.58 0.00849623 12.80 12.00 0.00849623 23.31 0.00838409 15.92 -999.0000 27.00 0.00850000 37.8820 8295.27 0.00 -999.00 -999.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 422590.737 422590.737 21.479376 0.01034922 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 422590.74 422590.74 21.479376 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 1.5753 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9432.840 9432.840 0.494742 0.00023101 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9432.84 9432.84 0.494742 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 3.1595 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90063.213 90063.213 4.725100 0.00220564 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 90063.21 90063.21 4.725100 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 3.3082 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9158.084 9158.084 0.480420 0.00022428 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9158.08 9158.08 0.480420 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 3.2537 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 17945.269 17945.269 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 17945.27 17945.27 21.479376 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 1.5753 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
DATACENTER_EXTRAELECHEATC Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 10000000.000 10000000.000 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10000000.00 1155979.49 21.479376 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 1.5753 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
DATACENTER_EXTRAWATERHEATC Coil:Heating:Water AirLoopHVAC AIRLOOP DATACENTER BASEMENT 1030312.178 1030312.178 21.479376 0.02276349 19167.733 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 827153.50 1030312.18 21.479376 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 1.5753 18.00 0.00800000 61.6621 0.00 0.00 0.00 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 828.997 828.997 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 829.00 829.00 0.494742 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 3.1595 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 8289.971 8289.971 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8289.97 8289.97 4.725100 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 3.3082 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 828.997 828.997 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 829.00 829.00 0.480420 -4.30 -4.30 0.00265759 40.00 21.02 0.00800000 -4.30 0.00265759 -4.30 3.2537 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 17886.581 17886.581 1.795514 0.00039518 311.321 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.5765 0.619870 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 16969.30 17886.58 1.0000 2.13912481 1.795514 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.39514184 60.00 49.00 11.00 0.000 16969.30 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.1678 0.00 0.00 17958.53 17958.53 2.13912481 12.80 11.59 0.00800000 33059.8 21.03 14.85 0.00800000 41455.1
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 314945.097 314945.097 16.863493 0.00695833 5869.846 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 10.1583 10.914616 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 299021.98 314945.10 1.0000 20.09069374 16.863493 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 6.95761725 60.00 49.00 11.00 0.000 299021.98 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.62 0.00800000 21.00 0.00800000 51.1678 146954.04 0.00 316459.39 316459.39 20.09069374 12.80 11.59 0.00800000 33059.8 28.25 17.42 0.00800000 48811.4
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 68631.550 68631.550 2.061533 0.00151633 1433.264 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 2.2122 2.378469 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 65117.49 68631.55 1.0000 2.45605219 2.061533 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 1.51617556 60.00 49.00 11.00 0.000 65117.49 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 51.1678 48094.94 0.00 68944.92 68944.92 2.45605219 12.80 11.59 0.00800000 33059.8 40.33 21.25 0.00800000 61131.3
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 4505.996 4505.996 0.241325 0.00009955 83.979 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.1453 0.156158 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4278.18 4506.00 1.0000 0.28750733 0.241325 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.09954433 60.00 49.00 11.00 0.000 4278.18 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.88 0.00676836 21.00 0.00676836 43.3773 2107.60 0.00 4527.66 4527.66 0.28750733 12.80 11.59 0.00800000 33059.8 28.24 17.42 0.00800000 48807.8
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 5185.499 5185.499 0.336803 0.00011457 94.730 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.1673 0.179707 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4924.39 5185.50 1.0000 0.40125730 0.336803 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.11455558 60.00 49.00 11.00 0.000 4924.39 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.83 0.00692299 21.00 0.00692299 44.3579 1837.34 0.00 5211.08 5211.08 0.40125730 12.80 11.59 0.00800000 33059.8 25.54 16.48 0.00800000 46046.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 8468.975 8468.975 0.431782 0.00018711 158.816 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.2731 0.293498 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8040.43 8468.98 1.0000 0.51441291 0.431782 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.18709258 60.00 49.00 11.00 0.000 8040.43 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.87 0.00726552 21.00 0.00726552 46.5274 4173.96 0.00 8509.53 8509.53 0.51441291 12.80 11.59 0.00800000 33059.8 29.02 17.69 0.00800000 49602.1
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 4275.632 4275.632 0.404080 0.00009446 74.921 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.1378 0.148175 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4056.24 4275.63 1.0000 0.48140910 0.404080 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.09445523 60.00 49.00 11.00 0.000 4056.24 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.98 0.00558910 21.00 0.00558910 35.8858 268.11 0.00 4292.79 4292.79 0.48140910 12.80 11.59 0.00800000 33059.8 21.54 15.04 0.00800000 41977.0
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 125476.246 125476.246 3.777082 0.00277224 2618.682 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 4.0444 4.348456 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 119051.85 125476.25 1.0000 4.49991002 3.777082 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 2.77196153 60.00 49.00 11.00 0.000 119051.85 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.91 0.00760590 21.00 0.00760590 48.6812 87882.16 0.00 126049.12 126049.12 4.49991002 12.80 11.59 0.00800000 33059.8 40.27 21.23 0.00800000 61071.3
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 94021.390 94021.390 3.442697 0.00207729 1865.661 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 3.0313 3.258369 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 89230.90 94021.39 1.0000 4.10153312 3.442697 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 2.07707583 60.00 49.00 11.00 0.000 89230.90 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.91 0.00764628 21.00 0.00764628 48.9363 59752.69 0.00 94458.08 94458.08 4.10153312 12.80 11.59 0.00800000 33059.8 35.38 19.75 0.00800000 56089.8
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 132555.828 132555.828 4.339258 0.00292866 2701.814 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 4.2730 4.593804 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 125780.02 132555.83 1.0000 5.16967061 4.339258 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 2.92836029 60.00 49.00 11.00 0.000 125780.02 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.91 0.00762322 21.00 0.00762322 48.7906 89364.75 0.00 133161.48 133161.48 5.16967061 12.80 11.59 0.00800000 33059.8 38.06 20.57 0.00800000 58818.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 86962.612 86962.612 3.567228 0.00192133 1686.889 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 2.8043 3.013743 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 82547.45 86962.61 1.0000 4.24989501 3.567228 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 1.92113666 60.00 49.00 11.00 0.000 82547.45 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.91 0.00748463 21.00 0.00748463 47.9149 51466.11 0.00 87375.48 87375.48 4.24989501 12.80 11.59 0.00800000 33059.8 32.96 18.98 0.00800000 53619.3
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 18532.999 18532.999 0.558400 0.00040946 386.674 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.5974 0.642272 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17584.12 18533.00 1.0000 0.66526162 0.558400 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.40942220 60.00 49.00 11.00 0.000 17584.12 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00787298 21.00 0.00787298 50.3672 12971.98 0.00 18617.61 18617.61 0.66526162 12.80 11.59 0.00800000 33059.8 40.24 21.22 0.00800000 61045.2
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 12311.278 12311.278 0.370966 0.00027200 256.858 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.3968 0.426655 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11680.95 12311.28 1.0000 0.44195817 0.370966 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.27197489 60.00 49.00 11.00 0.000 11680.95 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00788129 21.00 0.00788129 50.4197 8616.82 0.00 12367.48 12367.48 0.44195817 12.80 11.59 0.00800000 33059.8 40.24 21.22 0.00800000 61043.2
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 18680.963 18680.963 0.562869 0.00041273 389.759 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.6021 0.647400 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17724.51 18680.96 1.0000 0.67058588 0.562869 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.41269095 60.00 49.00 11.00 0.000 17724.51 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00787543 21.00 0.00787543 50.3827 13075.41 0.00 18766.25 18766.25 0.67058588 12.80 11.59 0.00800000 33059.8 40.24 21.22 0.00800000 61044.7
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11782.177 11782.177 0.376664 0.00026031 241.678 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 0.3798 0.408319 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11179.61 11782.18 1.0000 0.44874697 0.376664 12.80 11.50 0.00800000 33059.8 40.00 21.02 0.00800000 60796.0 0.26028624 60.00 49.00 11.00 0.000 11179.61 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00783825 21.00 0.00783825 50.1482 8031.33 0.00 11835.96 11835.96 0.44874697 12.80 11.59 0.00800000 33059.8 38.67 20.75 0.00800000 59435.4
CAV_BAS_COOLC Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 96017.042 -999.000 5.796322 0.00408479 -999.000 -999.0000 1.00000 1.00000 1021.2630 1004.8586 1.1914 CAV_BAS FAN Fan:ConstantVolume 5.796322 6.90557541   4197.9300 999.8980 83.04882375 12.27 6.67 5.60 1952345.63 4.9180 4.918035 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 96017.04 88033.99 1.0000 6.90557541 5.796322 24.07 16.57 0.00883457 46674.4 11.28 11.28 0.00836692 32771.1 4.08437023 6.67 10.65 5.60 10717.694 85299.35 24.31 0.00838408 16.27 1.20008137 20.7042 24.00 0.00896510 24.00 0.00893830 47.5752 78557.44 0.00 110045.21 93347.50 6.90557541 24.07 16.68 0.00883457 46674.4 10.83 10.62 0.00787545 30738.7
CAV_BAS_HEATC Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 283742.837 283742.837 5.796322 0.00626895 5242.170 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 CAV_BAS FAN Fan:ConstantVolume 5.796322 6.90557541   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 7.6600 9.833282 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 225480.90 283742.84 1.0000 6.90557541 5.796322 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 6.26831177 60.00 49.00 11.00 0.000 225480.90 -4.30 0.00265759 -4.30 1.20008137 20.7042 0.00 0.00000000 21.00 0.00800000 51.1678 0.00 0.00 237872.78 237872.78 6.90557541 12.80 2.72 0.00055023 14251.1 47.05 17.54 0.00055023 48697.6
VAV_BOT WITH REHEAT_COOLC Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 164371.259 -999.000 9.421817 0.00699273 -999.000 -999.0000 1.00000 1.00000 1021.0356 1004.8586 1.1914 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.421817 11.22488944   4197.9300 999.8980 83.04882375 12.27 6.67 5.60 1952345.63 8.4192 8.419168 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 164371.26 154532.16 1.0000 11.22488944 9.421817 24.74 16.70 0.00871224 47048.8 11.28 12.00 0.00836692 34322.2 6.99202000 6.67 10.65 5.60 21516.866 142854.39 26.40 0.00838408 17.00 2.71265000 28.7912 24.00 0.00885864 24.00 0.00879854 46.8411 119738.58 0.00 187244.80 161351.03 11.22488944 24.74 16.81 0.00871224 47048.8 10.66 10.47 0.00779711 30367.6
VAV_BOT WITH REHEAT_HEATC Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 56389.629 56389.629 2.826545 0.00124586 811.430 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.421817 11.22488944   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 1.4666 1.954217 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 43171.76 56389.63 1.0000 3.36746683 2.826545 -4.30 -4.30 0.00265759 2304.4 12.80 11.50 0.00800000 33059.8 1.24573285 60.00 49.00 11.00 0.000 43171.76 -4.30 0.00265759 -4.30 2.71265000 95.9705 6.51 0.00210916 21.00 0.00761566 48.7401 8387.00 0.00 45649.70 45649.70 3.36746683 12.80 5.49 0.00263549 19515.9 26.23 11.68 0.00263549 33072.0
VAV_MID WITH REHEAT_COOLC Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1533547.286 -999.000 87.136118 0.06524065 -999.000 -999.0000 1.00000 1.00000 1021.0377 1004.8586 1.1914 VAV_MID WITH REHEAT FAN Fan:VariableVolume 87.136118 103.81153158   4197.9300 999.8980 83.04882375 12.27 6.67 5.60 1952345.63 78.5490 78.548965 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 1533547.29 1442248.83 1.0000 103.81153158 87.136118 24.86 16.75 0.00871335 47177.7 11.28 12.00 0.00836692 34322.2 65.23399143 6.67 10.65 5.60 198995.175 1334552.11 26.40 0.00838408 17.00 28.42906000 32.6260 24.00 0.00889852 24.00 0.00881527 46.9290 1075515.97 0.00 1745117.56 1505081.96 103.81153158 24.86 16.86 0.00871335 47177.7 10.66 10.47 0.00779608 30367.3
VAV_MID WITH REHEAT_HEATC Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 535140.614 535140.614 26.140835 0.01182328 7673.542 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV_MID WITH REHEAT FAN Fan:VariableVolume 87.136118 103.81153158   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 13.8481 18.545626 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 407633.84 535140.61 1.0000 31.14345947 26.140835 -4.30 -4.30 0.00265759 2304.4 12.80 11.50 0.00800000 33059.8 11.82207187 60.00 49.00 11.00 0.000 407633.84 -4.30 0.00265759 -4.30 28.42906000 108.7534 20.77 0.00778495 21.00 0.00778495 49.8114 435419.75 0.00 431025.83 431025.83 31.14345947 12.80 5.51 0.00265759 19571.7 26.51 11.82 0.00265759 33411.7
VAV_TOP WITH REHEAT_COOLC Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 158410.046 -999.000 9.073990 0.00673913 -999.000 -999.0000 1.00000 1.00000 1020.9999 1004.8586 1.1914 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.073990 10.81049809   4197.9300 999.8980 83.04882375 12.27 6.67 5.60 1952345.63 8.1138 8.113832 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 158410.05 149461.08 1.0000 10.81049809 9.073990 24.80 16.71 0.00869303 47058.7 11.28 12.00 0.00836692 34322.2 6.73844209 6.67 10.65 5.60 20722.524 137687.52 26.40 0.00838408 17.00 3.01498000 33.2266 24.00 0.00884692 24.00 0.00880976 46.9000 123478.11 0.00 180438.99 156002.31 10.81049809 24.80 16.82 0.00869303 47058.7 10.66 10.47 0.00779629 30367.6
VAV_TOP WITH REHEAT_HEATC Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 55727.302 55727.302 2.722197 0.00123123 799.091 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.073990 10.81049809   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 1.4421 1.931264 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 10:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 42449.28 55727.30 1.0000 3.24314943 2.722197 -4.29 -4.29 0.00266032 2324.3 12.80 11.50 0.00800000 33059.8 1.23110105 60.00 49.00 11.00 0.000 42449.28 -4.30 0.00265759 -4.30 3.01498000 110.7554 21.00 0.00796714 21.00 0.00793820 50.7784 69628.68 0.00 44885.22 44885.22 3.24314943 12.80 5.51 0.00265759 19571.7 26.51 11.82 0.00265759 33411.7
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 422590.737 304636.259 21.479376 0.01034922 -999.000 -999.0000 -999.00000 -999.00000 1020.6377 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 06:00:00 454715.71 454715.71 0.9294 -999.0 -999.0 28.41 17.77 0.00849817 50245.3 12.80 12.00 0.00849817 34317.6 -999.0 -999.00 -999.00 -999.00 0.000 454715.71 26.40 0.00838408 17.00 0.33837161 -999.0000 27.00 0.00850000 27.00 0.00850000 37.8820 370318.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9432.840 6910.171 0.494742 0.00023101 -999.000 -999.0000 -999.00000 -999.00000 1020.6343 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 10203.19 10203.19 0.9245 -999.0 -999.0 27.84 17.58 0.00849634 49662.2 12.80 12.00 0.00849634 34312.9 -999.0 -999.00 -999.00 -999.00 0.000 10203.19 23.31 0.00838409 15.92 0.01563137 -999.0000 27.00 0.00850000 27.00 0.00850000 37.8820 8542.55 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 90063.213 65986.736 4.725100 0.00220564 -999.000 -999.0000 -999.00000 -999.00000 1020.6339 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 97423.73 97423.73 0.9244 -999.0 -999.0 27.83 17.58 0.00849617 49656.2 12.80 12.00 0.00849617 34312.5 -999.0 -999.00 -999.00 -999.00 0.000 97423.73 23.31 0.00838409 15.92 0.15631366 -999.0000 27.00 0.00850000 27.00 0.00850000 37.8820 81586.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9158.084 6709.510 0.480420 0.00022428 -999.000 -999.0000 -999.00000 -999.00000 1020.6341 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 9906.34 9906.34 0.9245 -999.0 -999.0 27.84 17.58 0.00849623 49658.4 12.80 12.00 0.00849623 34312.7 -999.0 -999.00 -999.00 -999.00 0.000 9906.34 23.31 0.00838409 15.92 0.01563137 -999.0000 27.00 0.00850000 27.00 0.00850000 37.8820 8295.27 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 422590.737 422590.737 21.479376 0.01034922 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 422590.74 422590.74 1.0000 25.58992685 21.479376 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 422590.74 -4.30 0.00265759 -4.30 0.33837161 1.5753 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9432.840 9432.840 0.494742 0.00023101 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9432.84 9432.84 1.0000 0.58942153 0.494742 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9432.84 -4.30 0.00265759 -4.30 0.01563137 3.1595 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 90063.213 90063.213 4.725100 0.00220564 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 90063.21 90063.21 1.0000 5.62935191 4.725100 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 90063.21 -4.30 0.00265759 -4.30 0.15631366 3.3082 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9158.084 9158.084 0.480420 0.00022428 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9158.08 9158.08 1.0000 0.57235949 0.480420 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9158.08 -4.30 0.00265759 -4.30 0.01563137 3.2537 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 17945.269 17945.269 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.479376 25.58992685   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 17945.27 17945.27 1.0000 25.58992685 21.479376 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 17945.27 -4.30 0.00265759 -4.30 0.33837161 1.5753 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
DATACENTER_EXTRAELECHEATC Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A No No unknown No 10000000.000 10000000.000 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.479376 25.58992685   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10000000.00 1155979.49 1.0000 25.58992685 21.479376 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10000000.00 -4.30 0.00265759 -4.30 0.33837161 1.5753 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
DATACENTER_EXTRAWATERHEATC Coil:Heating:Water AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes Yes Yes No 1030312.178 1030312.178 21.479376 0.02276349 19167.733 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.479376 25.58992685   4197.9300 999.8980 63.74587501 71.00 82.00 11.00 2943607.93 28.1000 35.706101 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 827153.50 1030312.18 1.0000 25.58992685 21.479376 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 22.76116648 60.00 49.00 11.00 0.000 827153.50 -4.30 0.00265759 -4.30 0.33837161 1.5753 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 0.00 0.00 25.58992685 16.60 4.09 0.00004187 16786.3 16.60 4.09 0.00004187 16786.3
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 828.997 828.997 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 DATACENTER BOT SUPPLY FAN Fan:OnOff 0.494742 0.58942153   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 829.00 829.00 1.0000 0.58942153 0.494742 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 829.00 -4.30 0.00265759 -4.30 0.01563137 3.1595 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8289.971 8289.971 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 DATACENTER MID SUPPLY FAN Fan:OnOff 4.725100 5.62935191   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8289.97 8289.97 1.0000 5.62935191 4.725100 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8289.97 -4.30 0.00265759 -4.30 0.15631366 3.3082 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 828.997 828.997 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 DATACENTER TOP SUPPLY FAN Fan:OnOff 0.480420 0.57235949   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 829.00 829.00 1.0000 0.57235949 0.480420 -4.30 -4.30 0.00265759 2304.4 40.00 21.02 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 829.00 -4.30 0.00265759 -4.30 0.01563137 3.2537 0.00 0.00000000 18.00 0.00800000 61.6621 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 5.80 -      
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 2.71 9.42 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 28.43 87.14 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 3.01 9.07 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2631.17 97.33 4.50
CORE_BOTTOM 2691.83 208.83 12.00
CORE_MID 1514.33 1526.17 13.17
CORE_TOP 1266.17 3568.50 266.83
PERIMETER_BOT_ZN_3 1331.00 2579.83 0.00
PERIMETER_BOT_ZN_2 1264.83 3813.17 27.33
PERIMETER_BOT_ZN_1 1561.33 3184.83 20.33
PERIMETER_BOT_ZN_4 2745.33 1761.33 54.17
PERIMETER_MID_ZN_3 886.67 4211.50 224.50
PERIMETER_MID_ZN_2 963.33 3864.00 246.50
PERIMETER_MID_ZN_1 1289.33 3917.67 127.83
PERIMETER_MID_ZN_4 994.17 4521.17 166.50
PERIMETER_TOP_ZN_3 1756.17 4709.00 1150.00
PERIMETER_TOP_ZN_2 2047.00 4541.33 1112.00
PERIMETER_TOP_ZN_1 1776.00 4452.50 835.50
PERIMETER_TOP_ZN_4 1576.00 4825.33 859.83
DATACENTER_BOT_ZN_6 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 4336.17 5342.17 1342.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 140.67 0.00 9.33
CORE_BOTTOM 0.00 2.83 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 1.50 0.00 0.17 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 0.00 5.83 0.00 5.83
PERIMETER_BOT_ZN_1 0.00 4.33 0.00 4.33
PERIMETER_BOT_ZN_4 0.00 27.00 0.00 14.17
PERIMETER_MID_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 0.00 3.33 0.00 3.33
PERIMETER_MID_ZN_1 0.00 4.83 0.00 4.83
PERIMETER_MID_ZN_4 0.00 9.00 0.00 4.33
PERIMETER_TOP_ZN_3 19.50 0.00 3.83 0.00
PERIMETER_TOP_ZN_2 11.17 1.67 0.00 1.67
PERIMETER_TOP_ZN_1 8.33 2.00 0.00 2.00
PERIMETER_TOP_ZN_4 6.17 9.50 0.00 4.67
DATACENTER_BOT_ZN_6 0.00 4.33 0.00 0.00
DATACENTER_MID_ZN_6 0.00 3.33 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 2.83 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 12.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 20.50 212.50 3.83 46.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 1.447 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 1.081 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.887 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.814 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.956 0.026 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 1.582 0.027 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 1.470 0.026 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 2.080 0.027 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.763 0.059 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 1.576 0.064 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 1.490 0.059 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 1.728 0.061 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.866 0.073 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 1.762 0.075 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 1.640 0.073 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 1.961 0.075 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 0
Defaulted Fields 0
Fields with Defaults 0
Autosized Fields 0
Autosizable Fields 0
Autocalculated Fields 0
Autocalculatable Fields 0



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
Electricity:Building 19507.65 254949.54 01-JAN-06:10 1167329.12 03-APR-07:10
Electricity:Zone:BASEMENT 682.08 14702.05 01-JAN-06:10 35858.69 02-JAN-08:10
InteriorLights:Electricity 4294.36 20740.28 01-JAN-06:10 373325.05 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 257.68 1244.51 01-JAN-06:10 22401.15 02-JAN-08:10
LightsWired:InteriorLights:Electricity 4294.36 20740.28 01-JAN-06:10 373325.05 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 552.69 7160.52 01-JAN-06:10 38246.39 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 231.42 1117.66 01-JAN-06:10 20117.80 02-JAN-08:10
Electricity:Zone:CORE_MID 5526.92 71604.96 01-JAN-06:10 382463.24 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2314.15 11176.56 01-JAN-06:10 201178.04 02-JAN-08:10
Electricity:Zone:CORE_TOP 552.69 7160.50 01-JAN-06:10 38246.32 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 231.42 1117.66 01-JAN-06:10 20117.80 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 69.40 899.11 01-JAN-06:10 4802.31 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 29.06 140.33 01-JAN-06:10 2525.99 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 44.72 579.42 01-JAN-06:10 3094.79 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 18.73 90.44 01-JAN-06:10 1627.84 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 69.40 899.12 01-JAN-06:10 4802.40 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 29.06 140.34 01-JAN-06:10 2526.05 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 44.72 579.41 01-JAN-06:10 3094.78 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 18.73 90.44 01-JAN-06:10 1627.84 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 693.98 8991.05 01-JAN-06:10 48023.09 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 290.56 1403.33 01-JAN-06:10 25259.91 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 447.23 5794.18 01-JAN-06:10 30947.91 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 187.25 904.36 01-JAN-06:10 16278.45 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 693.99 8991.20 01-JAN-06:10 48023.99 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 290.57 1403.36 01-JAN-06:10 25260.46 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 447.22 5794.15 01-JAN-06:10 30947.81 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 187.25 904.36 01-JAN-06:10 16278.45 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 69.40 899.11 01-JAN-06:10 4802.31 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 29.06 140.33 01-JAN-06:10 2525.99 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 44.72 579.42 01-JAN-06:10 3094.79 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 18.73 90.44 01-JAN-06:10 1627.84 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 69.40 899.12 01-JAN-06:10 4802.40 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 29.06 140.34 01-JAN-06:10 2526.05 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 44.72 579.41 01-JAN-06:10 3094.78 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 18.73 90.44 01-JAN-06:10 1627.84 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7567.51 95259.03 01-JAN-06:10 385948.69 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 72.65 350.90 01-JAN-06:10 6316.16 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.24 1964.82 01-JAN-06:10 8086.20 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.36 16.21 01-JAN-06:10 291.78 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1572.37 19648.16 01-JAN-06:10 80862.03 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 33.56 162.10 01-JAN-06:10 2917.81 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.24 1964.82 01-JAN-06:10 8086.20 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.36 16.21 01-JAN-06:10 291.78 02-JAN-08:10
InteriorEquipment:Electricity 15213.29 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity 5871.86 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.28 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.77 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.41 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.42 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.97 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 01-APR-00:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 01-APR-00:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 01-APR-00:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 01-APR-00:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 01-APR-00:10
Electricity:HVAC 4636.42 69160.35 07-JAN-20:10 289910.89 14-AUG-16:00
ExteriorEquipment:Electricity 2044.08 15778.61 01-JAN-00:10 129663.18 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 87.73 1613.62 01-JAN-00:10 5498.40 03-APR-07:20
ElectricityPurchased:Facility 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
ElectricityPurchased:Plant 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
Cogeneration:ElectricityPurchased 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
ElectricityNet:Plant 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
Cogeneration:ElectricityNet 28223.80 376843.08 08-JAN-10:10 1844850.50 14-AUG-16:00
Fans:Electricity 2290.71 41997.14 04-JAN-03:30 169201.87 12-APR-15:00
General:Fans:Electricity 2290.71 41997.14 04-JAN-03:30 169201.87 12-APR-15:00
ExteriorLights:Electricity 882.57 0.00 01-JAN-08:20 56280.71 01-JAN-00:10
General:ExteriorLights:Electricity 882.57 0.00 01-JAN-08:20 56280.71 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 1895.08 12222.20 01-JAN-00:10 122221.98 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 61.27 1942.80 01-JAN-00:10 1942.80 01-JAN-00:10
Cooling:Electricity 2486.74 25544.43 07-JAN-20:10 322783.49 14-AUG-16:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 16.91 0.00 01-JAN-00:10 33362.21 03-FEB-05:20
Electricity:Plant 1240.82 5370.56 12-JAN-23:00 345548.31 13-JUN-16:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:Electricity 245.67 0.00 01-JAN-00:10 215417.80 13-JUN-16:00
HeatRejection:Electricity 715.94 1967.61 10-JAN-21:50 79510.01 22-MAY-14:40
General:HeatRejection:Electricity 19.04 0.00 01-JAN-00:10 30261.73 22-MAY-14:40
Pumps:Electricity 279.21 3318.24 01-JAN-01:00 51331.74 25-SEP-14:00
General:Pumps:Electricity 279.21 3318.24 01-JAN-01:00 51331.74 25-SEP-14:00
WIRED_LTG_ELECTRICITY 120.67 0.00 01-JAN-00:10 10490.43 02-JAN-08:20
WIRED_INT_EQUIP 5871.86 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 3413.27 8146.58 03-JAN-22:50 1355684.88 30-DEC-07:10
Gas:Plant 3413.27 8146.58 03-JAN-22:50 1355684.88 30-DEC-07:10
WaterSystems:Gas 630.35 8146.58 03-JAN-22:50 79903.97 16-FEB-12:20
Water Heater:WaterSystems:Gas 630.35 8146.58 03-JAN-22:50 79903.97 16-FEB-12:20
Heating:Gas 2782.93 0.00 01-JAN-00:10 1347538.30 30-DEC-07:10
Boiler:Heating:Gas 2782.93 0.00 01-JAN-00:10 1347538.30 30-DEC-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 13166.21 90235.18 06-JAN-23:20 1821005.98 14-AUG-16:00
PlantLoopCoolingDemand:HVAC 13166.21 90235.18 06-JAN-23:20 1821005.98 14-AUG-16:00
CoolingCoils:PlantLoopCoolingDemand 13166.21 90235.18 06-JAN-23:20 1821005.98 14-AUG-16:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 3274.33 0.00 01-JAN-00:10 0.00 21-JUL-16:00
Water:Plant 3268.04 0.00 01-JAN-00:10 0.00 21-JUL-16:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MainsWater:Facility 3274.33 0.00 01-JAN-00:10 0.00 21-JUL-16:00
MainsWater:Plant 3268.04 0.00 01-JAN-00:10 0.00 21-JUL-16:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:HVAC 6.29 0.00 01-JAN-00:10 0.00 03-FEB-05:20
Humidifier:Water 6.29 0.00 01-JAN-00:10 0.00 03-FEB-05:20
MainsWater:HVAC 6.29 0.00 01-JAN-00:10 0.00 03-FEB-05:20
Humidifier:MainsWater 6.29 0.00 01-JAN-00:10 0.00 03-FEB-05:20
HeatRejection:Water 987.87 0.00 01-JAN-00:10 0.00 21-JUL-16:00
HeatRejection:MainsWater 987.87 0.00 01-JAN-00:10 0.00 21-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 2580.34 0.00 01-JAN-00:10 924140.15 10-JAN-08:00
PlantLoopHeatingDemand:Plant 444.01 0.00 01-JAN-00:10 51529.83 17-FEB-12:30
WaterSystems:PlantLoopHeatingDemand 444.01 0.00 01-JAN-00:10 51529.83 17-FEB-12:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Facility 39508.49 152829.68 06-JAN-23:20 7417281.80 13-JUN-16:00
EnergyTransfer:Building 18859.83 66624.69 26-JAN-22:30 1513710.85 28-APR-15:20
EnergyTransfer:Zone:BASEMENT 751.53 0.00 01-JAN-00:10 84201.03 19-APR-03:50
Heating:EnergyTransfer 60.08 0.00 04-JAN-22:10 227943.01 26-DEC-06:10
Heating:EnergyTransfer:Zone:BASEMENT 7.12 0.00 01-JAN-00:10 64251.46 12-JAN-05:00
Cooling:EnergyTransfer 18799.74 66624.69 26-JAN-22:30 1513710.85 28-APR-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 744.42 0.00 01-JAN-00:10 80989.69 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 663.56 0.00 01-JAN-00:10 54701.92 24-APR-09:30
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 663.56 0.00 01-JAN-00:10 54701.92 24-APR-09:30
EnergyTransfer:Zone:CORE_MID 4777.15 0.00 01-JAN-00:10 442580.92 05-JUL-13:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 4777.15 0.00 01-JAN-00:10 442580.92 05-JUL-13:10
EnergyTransfer:Zone:CORE_TOP 376.14 0.00 01-JAN-00:10 58858.52 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_TOP 2.45 0.00 01-JAN-00:10 58858.52 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_TOP 373.69 0.00 01-JAN-00:10 52136.81 13-JUN-15:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 69.75 0.00 01-JAN-00:10 8768.42 10-JUL-15:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 69.75 0.00 01-JAN-00:10 8768.42 10-JUL-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.60 0.00 01-JAN-00:10 11445.10 13-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 57.86 30-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.60 0.00 01-JAN-00:10 11445.10 13-JUN-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 103.62 0.00 01-JAN-00:10 17772.21 11-SEP-12:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 345.57 11-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 103.62 0.00 01-JAN-00:10 17772.21 11-SEP-12:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.13 0.00 01-JAN-00:10 15357.12 28-APR-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.13 0.00 01-JAN-00:10 15357.12 28-APR-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 460.45 0.00 01-JAN-00:10 76872.12 13-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1.86 0.00 01-JAN-00:10 41651.45 26-DEC-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 458.59 0.00 01-JAN-00:10 76872.12 13-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 564.13 0.00 01-JAN-00:10 117991.93 13-JUN-08:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.70 0.00 01-JAN-00:10 31080.00 18-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 562.43 0.00 01-JAN-00:10 117991.93 13-JUN-08:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 874.42 0.00 01-JAN-00:10 187618.11 11-SEP-13:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.95 0.00 01-JAN-00:10 39024.73 28-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 873.47 0.00 01-JAN-00:10 187618.11 11-SEP-13:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 601.02 0.00 01-JAN-00:10 133266.72 13-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.70 0.00 01-JAN-00:10 22647.20 10-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 600.31 0.00 01-JAN-00:10 133266.72 13-JUN-17:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 44.88 0.00 01-JAN-00:10 10507.05 02-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 5.52 0.00 01-JAN-00:10 10507.05 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 39.36 0.00 01-JAN-00:10 8802.08 13-JUN-15:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 50.55 0.00 01-JAN-00:10 11792.58 13-JUN-08:50
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.56 0.00 01-JAN-00:10 9569.44 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 46.99 0.00 01-JAN-00:10 11792.58 13-JUN-08:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 78.89 0.00 01-JAN-00:10 19000.11 11-SEP-13:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.03 0.00 01-JAN-00:10 13343.65 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 74.86 0.00 01-JAN-00:10 19000.11 11-SEP-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 54.54 0.00 01-JAN-00:10 14078.04 13-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 2.01 0.00 01-JAN-00:10 8010.59 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 52.53 0.00 01-JAN-00:10 14078.04 13-JUN-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 72.63 0.00 01-JAN-00:10 7963.73 02-JAN-06:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.82 0.00 01-JAN-00:10 2983.37 03-JUL-03:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 71.81 0.00 01-JAN-00:10 7963.73 02-JAN-06:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 453.01 0.00 01-JAN-00:10 50593.96 14-SEP-05:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 5.07 0.00 01-JAN-00:10 22513.83 07-MAY-15:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 447.94 0.00 01-JAN-00:10 50593.96 14-SEP-05:10
EnergyTransfer:Zone:TOPFLOOR_PLENUM 66.98 0.00 01-JAN-00:10 17446.92 02-JAN-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 23.22 0.00 01-JAN-00:10 17446.92 02-JAN-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 43.76 0.00 01-JAN-00:10 16928.66 13-JUN-14:30
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.43 922.05 14-JAN-18:20 8022.30 13-AUG-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.43 922.05 14-JAN-18:20 8022.30 13-AUG-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1213.68 3754.64 11-JAN-06:20 76070.37 27-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1213.68 3754.64 11-JAN-06:20 76070.37 27-APR-17:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 108.63 0.37 05-JAN-00:40 7677.97 27-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.53 0.00 02-JAN-12:50 566.45 08-JAN-17:40
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 108.10 0.00 01-JAN-00:10 7677.97 27-APR-17:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7167.09 57816.31 21-JAN-03:50 375979.32 02-DEC-19:30
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.54 0.00 01-JAN-00:10 12594.12 21-JAN-04:20
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.55 57816.31 21-JAN-03:50 375979.32 02-DEC-19:30
EnergyTransfer:Plant 7462.11 0.00 01-JAN-00:10 4455568.98 13-JUN-16:00
WaterSystems:EnergyTransfer 444.01 0.00 01-JAN-00:10 51529.83 17-FEB-12:30
WaterUse:WaterSystems:EnergyTransfer 444.01 0.00 01-JAN-00:10 51529.83 17-FEB-12:30
EnergyTransfer:HVAC 13186.55 73803.35 06-JAN-23:20 1677801.84 21-JUL-16:00
HeatingCoils:EnergyTransfer 2136.33 0.00 01-JAN-00:10 906822.80 10-JAN-08:00
PlantLoopHeatingDemand:HVAC 2136.33 0.00 01-JAN-00:10 906822.80 10-JAN-08:00
HeatingCoils:PlantLoopHeatingDemand 2136.33 0.00 01-JAN-00:10 906822.80 10-JAN-08:00
CoolingCoils:EnergyTransfer 11050.22 73803.35 06-JAN-23:20 1677801.84 21-JUL-16:00
LoopToLoop:EnergyTransfer 1666.88 -1.66 20-FEB-14:10 1398707.09 13-JUN-16:00
Boilers:EnergyTransfer 2109.38 0.00 01-JAN-00:10 1086355.14 30-DEC-07:10
Chillers:EnergyTransfer 1498.09 0.00 01-JAN-00:10 1402450.95 13-JUN-16:00
HeatRejection:EnergyTransfer 1743.76 0.00 01-JAN-00:10 1617868.74 13-JUN-16:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 7.116 -744.421 0.000 0.000 92.682 257.680 424.397 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -37.454
CORE_BOTTOM 0.000 0.000 0.000 -663.564 0.000 0.000 83.363 231.415 321.278 0.000 0.000 0.000 27.508 0.000 0.000 0.000 0.000 -0.001
CORE_MID 0.000 0.000 0.000 -4777.149 0.000 0.000 836.468 2314.151 3212.773 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1586.243
CORE_TOP 0.000 0.000 2.452 -373.689 0.000 0.000 85.968 231.415 321.277 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -267.423
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -69.752 0.000 0.000 10.575 29.056 40.341 12.970 0.000 0.002 38.005 0.000 -56.598 0.000 -4.600 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -69.603 0.000 0.000 7.062 18.725 25.998 35.229 0.000 0.001 19.601 0.000 -34.099 0.000 -2.914 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -103.618 0.000 0.000 10.821 29.057 40.342 66.308 0.000 0.002 13.406 0.000 -51.846 0.000 -4.472 -0.002
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -99.128 0.000 0.000 6.856 18.725 25.997 33.475 0.000 0.001 56.654 0.000 -39.343 0.000 -3.238 0.000
PERIMETER_MID_ZN_3 0.000 0.000 1.860 -458.593 0.000 0.000 109.446 290.565 403.414 135.267 0.000 0.039 132.142 0.000 -519.350 0.000 -94.789 0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.704 -562.430 0.000 0.000 53.924 187.251 259.975 354.762 0.000 0.032 88.168 0.000 -320.889 0.000 -62.497 -0.001
PERIMETER_MID_ZN_1 0.000 0.000 0.949 -873.470 0.000 0.000 110.765 290.571 403.420 664.911 0.000 0.045 2.979 0.000 -503.386 0.000 -96.784 -0.011
PERIMETER_MID_ZN_4 0.000 0.000 0.703 -600.313 0.000 0.000 73.852 187.251 259.973 346.334 0.000 0.027 138.584 0.000 -342.088 0.000 -64.323 0.000
PERIMETER_TOP_ZN_3 0.000 0.000 5.522 -39.357 0.000 0.000 11.421 29.056 40.341 14.142 0.000 0.005 0.000 0.000 -47.029 0.000 -10.821 -3.278
PERIMETER_TOP_ZN_2 0.000 0.000 3.564 -46.991 0.000 0.000 7.442 18.725 25.998 35.933 0.000 0.004 0.000 0.000 -29.727 0.000 -7.252 -7.694
PERIMETER_TOP_ZN_1 0.000 0.000 4.028 -74.863 0.000 0.000 11.437 29.057 40.342 67.459 0.000 0.005 0.002 0.000 -46.442 0.000 -11.144 -19.881
PERIMETER_TOP_ZN_4 0.000 0.000 2.010 -52.527 0.000 0.000 7.577 18.725 25.997 34.979 0.000 0.003 2.674 0.000 -31.931 0.000 -7.508 -0.002
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -138.431 0.000 0.000 0.000 3.356 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -18.806
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1213.676 0.000 0.000 0.000 33.564 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -358.694
DATACENTER_TOP_ZN_6 0.000 0.000 0.533 -108.101 0.000 0.000 0.000 3.356 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -49.669
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.541 -7166.549 0.000 0.000 0.000 72.655 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -401.504
GROUNDFLOOR_PLENUM 0.818 -71.809 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 80.257 0.000 0.000 0.000 -9.268 0.000
MIDFLOOR_PLENUM 5.069 -447.940 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.049 603.052 0.000 0.000 0.000 -160.230 0.000
TOPFLOOR_PLENUM 23.216 -43.764 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 37.328 0.000 0.000 0.000 -16.782 -0.000
Total Facility 29.103 -563.513 30.980 -18236.224 0.000 0.000 1519.658 4294.357 15213.288 1801.769 0.000 0.220 1240.360 0.000 -2022.728 0.000 -556.622 -2750.662


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 04-SEP-07:30 0.00 0.00 0.00 -126403.24 0.00 0.00 399.52 1244.51 13457.54 0.00 0.00 0.00 111301.66 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 13-JUN-03:02 0.00 0.00 0.00 -86180.95 0.00 0.00 0.00 1209.06 8057.15 0.00 0.00 0.00 76914.73 0.00 -0.00 0.00 0.00 0.00
CORE_MID 22-JUL-05:02 0.00 0.00 0.00 -753161.26 0.00 0.00 8376.71 22353.12 80571.20 0.00 0.00 0.00 641860.23 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 22-JUL-05:02 0.00 0.00 0.00 -70644.77 0.00 0.00 853.20 2235.31 8057.12 0.00 0.00 0.00 59499.14 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 10-JUL-05:03 0.00 0.00 0.00 -9205.62 0.00 0.00 109.45 280.67 1011.70 1125.02 0.00 0.00 6724.49 0.00 -0.00 0.00 -45.70 0.00
PERIMETER_BOT_ZN_2 20-AUG-08:52 0.00 0.00 0.00 -18263.18 0.00 0.00 24.58 90.44 488.98 13571.65 0.00 0.00 4220.84 0.00 -0.00 0.00 -133.31 0.00
PERIMETER_BOT_ZN_1 24-SEP-14:02 0.00 0.00 0.00 -24635.52 0.00 0.00 40.36 140.34 758.78 14485.75 0.00 0.00 9339.67 0.00 -0.00 0.00 -129.39 0.00
PERIMETER_BOT_ZN_4 09-JUL-18:21 0.00 0.00 0.00 -25707.45 0.00 0.00 0.00 97.83 488.98 11447.51 0.00 0.00 13760.86 0.00 -0.00 0.00 -87.74 0.00
PERIMETER_MID_ZN_3 18-JUL-05:01 0.00 0.00 0.00 -81864.22 0.00 0.00 1148.78 2806.66 10116.97 0.00 0.00 0.00 79454.55 0.00 -11057.03 0.00 -605.71 0.00
PERIMETER_MID_ZN_2 23-JUL-09:42 0.00 0.00 0.00 -203694.11 0.00 0.00 231.77 904.36 4889.82 101215.71 0.00 0.00 98168.48 0.00 -0.00 0.00 -1716.04 0.00
PERIMETER_MID_ZN_1 10-SEP-13:32 0.00 0.00 0.00 -259938.30 0.00 0.00 368.71 1403.36 7587.84 179367.36 0.00 0.00 76065.38 0.00 -0.00 0.00 -4854.34 0.00
PERIMETER_MID_ZN_4 23-JUL-17:21 0.00 0.00 0.00 -207171.82 0.00 0.00 0.00 978.32 4889.79 115875.43 0.00 0.00 87963.49 0.00 -0.00 0.00 -2535.21 0.00
PERIMETER_TOP_ZN_3 13-JUN-15:50 0.00 0.00 0.00 -8801.96 0.00 0.00 1114.39 2525.99 2276.32 3334.33 0.00 47.78 0.00 0.00 -0.00 0.00 0.00 -496.85
PERIMETER_TOP_ZN_2 23-JUL-09:42 0.00 0.00 0.00 -20096.35 0.00 0.00 23.09 90.44 488.98 10097.48 0.00 0.00 9614.32 0.00 -0.00 0.00 -217.96 0.00
PERIMETER_TOP_ZN_1 30-APR-13:12 0.00 0.00 0.00 -27445.25 0.00 0.00 36.92 140.34 758.78 18249.09 0.00 0.00 8552.67 0.00 -0.00 0.00 -292.55 0.00
PERIMETER_TOP_ZN_4 09-JUL-17:11 0.00 0.00 0.00 -24079.48 0.00 0.00 0.00 97.83 488.98 15985.75 0.00 0.00 7864.98 0.00 -0.00 0.00 -358.06 0.00
DATACENTER_BOT_ZN_6 13-AUG-18:23 0.00 0.00 0.00 -8027.71 0.00 0.00 0.00 17.54 7794.42 0.00 0.00 0.00 215.76 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 27-APR-17:50 0.00 0.00 0.00 -76070.37 0.00 0.00 0.00 972.60 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2846.45
DATACENTER_TOP_ZN_6 27-APR-17:50 0.00 0.00 0.00 -7677.97 0.00 0.00 0.00 97.26 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -213.71
DATACENTER_BASEMENT_ZN_6 18-JUN-21:21 0.00 0.00 0.00 -413709.44 0.00 0.00 0.00 379.60 189816.26 0.00 0.00 0.00 223513.59 0.00 -0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 02-JAN-06:13 0.00 -9335.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9335.04 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 07-JUL-05:13 0.00 -64425.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64425.74 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 13-JUN-14:30 0.00 -16928.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16957.80 0.00 -0.00 0.00 -29.61 0.00
Total Facility 22-JUL-05:01 0.00 19290.63 0.00 -1584984.41 0.00 0.00 15626.46 41480.56 504945.49 24324.02 0.00 0.00 1010659.54 0.00 -25695.59 0.00 -5646.70 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 20-JAN-04:45 0.00 0.00 139609.47 0.00 0.00 0.00 0.00 1346.29 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -154413.30
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 02-JAN-04:01 0.00 0.00 72845.60 -0.00 0.00 0.00 0.00 1209.06 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -82111.78
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 30-DEC-06:01 0.00 0.00 578.62 -0.00 0.00 0.00 91.89 180.87 651.98 0.00 0.00 0.00 1006.48 0.00 -2439.63 0.00 -70.20 0.00
PERIMETER_BOT_ZN_1 11-DEC-06:01 0.00 0.00 3455.75 -0.00 0.00 0.00 140.75 280.67 1011.71 0.00 0.00 0.00 0.00 0.00 -2812.39 0.00 0.00 -2076.50
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 26-DEC-05:01 0.00 0.00 90942.72 -0.00 0.00 0.00 0.00 3036.19 10116.97 0.00 0.00 0.00 0.00 0.00 -29227.59 0.00 -12597.74 -62270.56
PERIMETER_MID_ZN_2 26-DEC-05:01 0.00 0.00 93060.21 -0.00 0.00 0.00 0.00 1956.64 6519.76 0.00 0.00 0.00 0.00 0.00 -19413.24 0.00 -8452.86 -73670.51
PERIMETER_MID_ZN_1 28-DEC-06:01 0.00 0.00 132858.33 -0.00 0.00 0.00 1483.77 2806.72 10117.12 0.00 0.00 0.00 0.00 0.00 -33924.07 0.00 -3768.51 -109573.37
PERIMETER_MID_ZN_4 11-JAN-06:01 0.00 0.00 80424.34 -0.00 0.00 0.00 946.66 1808.72 6519.72 0.00 0.00 0.00 0.00 0.00 -24941.78 0.00 -1645.35 -63112.31
PERIMETER_TOP_ZN_3 01-JAN-18:15 0.00 0.00 12144.97 -0.00 0.00 0.00 0.00 151.81 758.77 0.00 0.00 0.00 0.00 0.00 -2066.42 0.00 -1028.75 -9960.39
PERIMETER_TOP_ZN_2 04-DEC-04:01 0.00 0.00 14784.33 -0.00 0.00 0.00 0.00 97.83 651.98 0.00 0.00 0.00 0.00 0.00 -1625.98 0.00 -727.78 -13180.38
PERIMETER_TOP_ZN_1 26-DEC-04:01 0.00 0.00 20971.28 -0.00 0.00 0.00 0.00 151.81 1011.71 0.00 0.00 0.00 0.00 0.00 -2971.98 0.00 -1866.13 -17296.69
PERIMETER_TOP_ZN_4 26-DEC-04:01 0.00 0.00 14410.58 -0.00 0.00 0.00 0.00 97.83 651.97 0.00 0.00 0.00 0.00 0.00 -2023.53 0.00 -1250.48 -11886.38
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 14-JAN-04:42 0.00 0.00 610.87 0.00 0.00 0.00 0.00 17.54 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2577.01
DATACENTER_BASEMENT_ZN_6 21-JAN-04:41 0.00 0.00 57558.09 0.00 0.00 0.00 0.00 379.60 94908.13 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -152845.82
GROUNDFLOOR_PLENUM 11-DEC-04:01 12316.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -412.04 -11904.75
MIDFLOOR_PLENUM 03-JUL-04:01 79454.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -18650.77 -60803.61
TOPFLOOR_PLENUM 27-APR-05:01 22365.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -22365.98
Total Facility 28-NOV-06:01 -987477.47 1046653.40 491588.85 -1046653.40 0.00 0.00 17483.24 41480.56 504945.49 0.00 0.00 0.00 89685.64 0.00 -136113.63 0.00 -21592.67 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CAV_BAS 5.7963 0.0000 149.6021 1.0000 1.2001 5.7963 0.2070 1.0000 1.2001 0.2070    
VAV_BOT WITH REHEAT 10.6983 0.0000 0.0000 1.0000 0.0000 9.4218 0.0000 1.0000 0.0000 0.0000    
VAV_MID WITH REHEAT 101.2648 0.0000 0.0000 1.0000 0.0000 87.1361 0.0000 1.0000 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.1635 0.0000 0.0000 1.0000 0.0000 9.0740 0.0000 1.0000 0.0000 0.0000    
AIRLOOP DATACENTER BASEMENT 21.4794 0.0000 0.0000 1.0000 0.3384 21.4794 0.0158 1.0000 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4947 0.0000 0.0000 1.0000 0.0156 0.4947 0.0316 1.0000 0.0156 0.0316    
AIRLOOP DATACENTER MID 4.7251 0.0000 0.0000 1.0000 0.1563 4.7251 0.0331 1.0000 0.1563 0.0331    
AIRLOOP DATACENTER TOP 0.4804 0.0000 0.0000 1.0000 0.0156 0.4804 0.0325 1.0000 0.0156 0.0325    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CAV_BAS 5.7963 0.0000 149.6021 1.0000 1.2001 5.7963 1.0000 1.0000 1.2001 0.2070    
VAV_BOT WITH REHEAT 5.3492 0.0000 0.0000 1.0000 0.0000 3.2095 0.0000 1.0000 0.0000 0.0000    
VAV_MID WITH REHEAT 50.6324 0.0000 0.0000 1.0000 0.0000 30.3795 0.0000 1.0000 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.0817 0.0000 0.0000 1.0000 0.0000 3.0490 0.0000 1.0000 0.0000 0.0000    
AIRLOOP DATACENTER BASEMENT 21.4794 0.0000 0.0000 1.0000 0.3384 21.4794 1.0000 1.0000 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4947 0.0000 0.0000 1.0000 0.0156 0.4947 1.0000 1.0000 0.0156 0.0316    
AIRLOOP DATACENTER MID 4.7251 0.0000 0.0000 1.0000 0.1563 4.7251 1.0000 1.0000 0.1563 0.0331    
AIRLOOP DATACENTER TOP 0.4804 0.0000 0.0000 1.0000 0.0156 0.4804 1.0000 1.0000 0.0156 0.0325    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2001 1.0000 1.2001 1.000 1.2001
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 0.0000 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 0.0000 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 0.0000 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 0.0000 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2001 1.2001 1.2001
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT   0.00 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT   0.00 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID   0.00 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP   0.00 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS   5.7963 5.7963 5.7963 1.2001 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9850 5.9850 1.7955 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 56.2116 56.2116 16.8635 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4207 5.4207 1.6262 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8044 0.8044 0.2413 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1227 1.1227 0.3368 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4393 1.4393 0.4318 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3469 1.3469 0.4041 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.2226 7.2226 2.1668 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.4757 11.4757 3.4427 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.4642 14.4642 4.3393 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.8908 11.8908 3.5672 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8179 0.8179 0.2454 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1277 1.1277 0.3383 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5416 1.5416 0.4625 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2555 1.2555 0.3767 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT   0.4947 0.4947 0.4947 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID   4.7251 4.7251 4.7251 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP   0.4804 0.4804 0.4804 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT   21.4794 21.4794 21.4794 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
CAV_BAS 5.7963 5.7963 5.7963 5.7963 1.2001 1.0000
VAV_BOT WITH REHEAT 10.6983 9.4218 10.6983 3.2095 0.0000 1.0000
VAV_MID WITH REHEAT 101.2648 87.1361 101.2648 30.3795 0.0000 1.0000
VAV_TOP WITH REHEAT 10.1635 9.0740 10.1635 3.0490 0.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.4794 21.4794 21.4794 21.4794 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4947 0.4947 0.4947 0.4947 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7251 4.7251 4.7251 4.7251 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4804 0.4804 0.4804 0.4804 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS   5.7963 5.7963 5.7963 1.2001 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9925 2.9925 1.7955 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 28.1058 28.1058 16.8635 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7104 2.7104 1.6262 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4022 0.4022 0.2413 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5613 0.5613 0.3368 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7196 0.7196 0.4318 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6735 0.6735 0.4041 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.6113 3.6113 2.1668 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7378 5.7378 3.4427 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.2321 7.2321 4.3393 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9454 5.9454 3.5672 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4089 0.4089 0.2454 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5638 0.5638 0.3383 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7708 0.7708 0.4625 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6278 0.6278 0.3767 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT   0.4947 0.4947 0.4947 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID   4.7251 4.7251 4.7251 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP   0.4804 0.4804 0.4804 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT   21.4794 21.4794 21.4794 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
CAV_BAS 5.7963 5.7963 5.7963 5.7963 1.2001 1.0000
VAV_BOT WITH REHEAT 5.3492 3.2095 3.2095 3.2095 0.0000 1.0000
VAV_MID WITH REHEAT 50.6324 30.3795 30.3795 30.3795 0.0000 1.0000
VAV_TOP WITH REHEAT 5.0817 3.0490 3.0490 3.0490 0.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.4794 21.4794 21.4794 21.4794 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4947 0.4947 0.4947 0.4947 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7251 4.7251 4.7251 4.7251 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4804 0.4804 0.4804 0.4804 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2020-06-03 20:04:38

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 0.00
DATACENTER_MID_ZN_6 36.20 36.20 0.00 0.00
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 0.00
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 0.00
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 3.83
Number of hours cooling loads not met 46.83
Number of hours not met 50.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Fuel Use [GJ] Additional Fuel Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- Boiler 0.00 0.00 2782.93 1347538.30 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 245.67 215417.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- Other 2241.07 107365.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 4294.36 373325.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 882.57 56280.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.86 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.73 5498.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1895.08 122221.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 61.27 1942.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2290.71 169201.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 279.21 51331.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 19.04 30261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Other 696.90 49248.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 16.91 33362.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 630.35 79903.97 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.29 28223.80
Natural Gas 0.00 3413.27
Additional 0.00 0.00
Total 15213.29 31637.07


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 92.71
Space Heating 0.00
Space Cooling 53.69
Fans (All) 49.45
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 609.32
Subtotal 609.32


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 60.08
Service Water Heating 13.61
Miscellaneous (All) 73.69
Subtotal 73.69


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 13.57
Space Heating 8.80
Space Cooling 7.86
Fans (All) 7.24
Service Water Heating 1.99
Receptacle Equipment 48.09
Miscellaneous 12.45


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
BLDG_LIGHT_SCH 2728. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2154. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM BASEMENT DUALSPSCHED January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM BASEMENT DUALSPSCHED July 24.00 365 26.70 365
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.541867E+12
February 0.000 0.426788E+12
March 0.000 0.380277E+12
April 0.000 0.137394E+12
May 0.000 0.118719E+12
June 0.000 0.342097E+11
July 0.000 0.966199E+10
August 0.000 0.533967E+10
September 0.000 0.381036E+11
October 0.000 0.172272E+12
November 0.000 0.338832E+12
December 0.000 0.579462E+12
     
Annual Sum or Average   0.278293E+13
Minimum of Months 0.000 0.533967E+10
Maximum of Months 0.000 0.579462E+12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.576809E+11 123752.79 01-JAN-07:02 5.83 4.96 0.566695E+10 7499.18 10-JAN-10:20 -2.7 -3.2
February 0.524639E+11 118201.91 20-FEB-22:31 5.67 4.42 0.513964E+10 7499.13 17-FEB-10:09 3.50 2.57
March 0.631670E+11 122014.43 21-MAR-03:50 1.47 0.99 0.613411E+10 7499.12 28-MAR-13:20 10.33 6.94
April 0.618543E+11 125028.43 30-APR-22:08 13.35 9.95 0.545300E+10 7499.31 25-APR-13:20 13.33 9.07
May 0.623499E+11 125865.24 29-MAY-14:18 12.00 7.60 0.590264E+10 7499.07 16-MAY-13:20 9.67 8.29
June 0.637647E+11 125118.97 11-JUN-22:23 9.00 9.00 0.588334E+10 7499.35 08-JUN-13:20 14.00 10.26
July 0.651388E+11 125977.17 04-JUL-20:20 11.00 9.74 0.547514E+10 7499.11 10-JUL-13:20 23.00 16.22
August 0.703974E+11 124687.77 20-AUG-23:08 13.00 11.29 0.613870E+10 7499.42 08-AUG-13:09 17.83 16.42
September 0.616518E+11 126409.28 04-SEP-07:30 11.00 8.62 0.545274E+10 7499.32 06-SEP-09:20 13.67 11.59
October 0.635036E+11 122369.93 09-OCT-20:52 11.00 11.00 0.567161E+10 7499.32 17-OCT-09:20 11.67 11.31
November 0.620039E+11 122119.09 12-NOV-21:22 6.50 6.24 0.561594E+10 7499.13 07-NOV-14:20 11.00 10.83
December 0.604423E+11 122342.25 05-DEC-04:50 7.00 6.47 0.547134E+10 7499.12 20-DEC-10:20 8.33 7.61
                     
Annual Sum or Average 0.744419E+12         0.680052E+11        
Minimum of Months 0.524639E+11 118201.91   1.47 0.99 0.513964E+10 7499.07   -2.7 -3.2
Maximum of Months 0.703974E+11 126409.28   13.35 11.29 0.613870E+10 7499.42   23.00 16.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.451242E+11 78383.32 02-JAN-04:01 1.17 0.70 0.507893E+10 6734.79 10-JAN-10:50 -2.2 -2.3
February 0.439457E+11 72968.82 13-FEB-04:02 -1.8 -1.8 0.460802E+10 6734.79 17-FEB-10:09 3.50 2.57
March 0.561295E+11 75231.91 06-MAR-04:02 3.80 3.41 0.550436E+10 6734.79 29-MAR-09:09 7.17 6.35
April 0.604615E+11 77483.57 25-APR-03:02 6.00 3.44 0.488674E+10 6735.08 14-APR-13:00 13.00 8.44
May 0.546548E+11 77394.35 30-MAY-03:02 8.00 7.45 0.529010E+10 6734.75 05-MAY-13:00 8.00 6.97
June 0.595561E+11 86197.25 13-JUN-03:02 15.50 10.97 0.527257E+10 6734.99 08-JUN-13:09 13.50 10.04
July 0.631294E+11 84155.66 19-JUL-03:02 14.00 13.33 0.489982E+10 6734.83 03-JUL-09:09 14.00 10.69
August 0.713920E+11 84128.41 22-AUG-03:02 14.00 11.12 0.549905E+10 6734.88 08-AUG-09:00 18.00 14.97
September 0.538127E+11 81615.86 01-SEP-03:02 12.92 12.36 0.487968E+10 6735.01 06-SEP-09:09 13.33 11.44
October 0.526194E+11 77410.32 10-OCT-02:61 10.17 10.17 0.508417E+10 6734.99 17-OCT-09:09 12.33 11.88
November 0.518062E+11 77093.73 15-NOV-04:02 11.83 9.30 0.503552E+10 6734.76 07-NOV-14:09 11.00 10.91
December 0.509311E+11 78447.93 26-DEC-04:01 2.00 0.67 0.490680E+10 6734.85 04-DEC-14:00 9.00 4.92
                     
Annual Sum or Average 0.663563E+12         0.609458E+11        
Minimum of Months 0.439457E+11 72968.82   -1.8 -1.8 0.460802E+10 6734.75   -2.2 -2.3
Maximum of Months 0.713920E+11 86197.25   15.50 13.33 0.550436E+10 6735.08   18.00 14.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.336767E+11 63314.24 26-JAN-06:01 5.00 4.51 0.503769E+10 6734.79 20-JAN-10:20 4.67 4.23
February 0.311480E+11 62337.50 10-FEB-06:01 5.00 4.51 0.457486E+10 6734.78 17-FEB-10:39 5.00 3.80
March 0.387895E+11 64041.43 30-MAR-05:01 5.00 4.51 0.547744E+10 6734.76 29-MAR-09:09 7.17 6.35
April 0.416087E+11 65661.75 24-APR-04:02 7.00 5.87 0.487568E+10 6735.01 14-APR-13:00 13.00 8.44
May 0.437340E+11 64699.55 31-MAY-05:01 7.67 7.59 0.528049E+10 6734.73 05-MAY-13:00 8.00 6.97
June 0.465927E+11 71751.47 13-JUN-05:02 14.50 12.19 0.526514E+10 6734.95 08-JUN-13:09 13.50 10.04
July 0.457576E+11 75325.51 22-JUL-05:02 16.33 11.77 0.488981E+10 6734.79 03-JUL-09:09 14.00 10.69
August 0.501249E+11 72197.67 09-AUG-05:01 15.17 13.25 0.548869E+10 6734.83 08-AUG-09:00 18.00 14.97
September 0.434974E+11 68372.77 16-SEP-05:02 14.00 13.42 0.486993E+10 6734.95 06-SEP-09:09 13.33 11.44
October 0.383809E+11 66829.79 10-OCT-04:02 10.17 10.17 0.506207E+10 6734.94 17-OCT-09:09 12.33 11.88
November 0.339789E+11 64226.08 09-NOV-06:01 9.00 9.00 0.500016E+10 6734.74 10-NOV-10:30 11.00 9.41
December 0.304254E+11 60709.09 22-DEC-06:02 3.00 2.55 0.483970E+10 6734.78 20-DEC-10:09 8.17 7.53
                     
Annual Sum or Average 0.477715E+12         0.606616E+11        
Minimum of Months 0.304254E+11 60709.09   3.00 2.55 0.457486E+10 6734.73   4.67 3.80
Maximum of Months 0.501249E+11 75325.51   16.33 13.42 0.548869E+10 6735.01   18.00 14.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.200820E+11 30904.71 19-JAN-16:30 7.00 6.74 0.454330E+10 6734.57 19-JAN-14:00 9.00 7.43
February 0.196304E+11 30377.47 09-FEB-16:50 6.33 4.78 0.424849E+10 6734.64 16-FEB-14:39 6.00 4.14
March 0.256817E+11 34617.97 31-MAR-16:00 9.00 4.94 0.523350E+10 6734.68 28-MAR-13:09 10.17 6.98
April 0.336192E+11 57113.86 21-APR-05:02 8.00 6.97 0.479839E+10 6735.00 14-APR-13:00 13.00 8.44
May 0.374091E+11 57579.34 23-MAY-05:02 9.67 9.01 0.522129E+10 6734.71 05-MAY-13:00 8.00 6.97
June 0.436124E+11 69152.38 13-JUN-05:02 14.50 12.19 0.523862E+10 6734.90 08-JUN-13:09 13.50 10.04
July 0.440322E+11 70655.31 22-JUL-05:02 16.33 11.77 0.486711E+10 6734.71 03-JUL-09:09 14.00 10.69
August 0.465808E+11 68780.31 15-AUG-05:02 14.50 11.06 0.546233E+10 6734.78 15-AUG-09:09 16.00 13.59
September 0.366048E+11 63495.33 01-SEP-05:02 14.00 13.43 0.481554E+10 6734.83 06-SEP-09:09 13.33 11.44
October 0.261911E+11 38862.39 05-OCT-16:00 16.00 9.11 0.487588E+10 6734.74 12-OCT-09:30 9.00 9.00
November 0.213794E+11 33246.49 10-NOV-16:20 9.67 7.82 0.467683E+10 6734.73 10-NOV-10:30 11.00 9.41
December 0.188683E+11 24670.23 21-DEC-17:00 6.00 5.49 0.435968E+10 6734.52 21-DEC-14:09 8.00 6.97
                     
Annual Sum or Average 0.373691E+12         0.583410E+11        
Minimum of Months 0.188683E+11 24670.23   6.00 4.78 0.424849E+10 6734.52   6.00 4.14
Maximum of Months 0.465808E+11 70655.31   16.33 13.43 0.546233E+10 6735.00   16.00 13.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.354730E+10 4479.76 17-JAN-13:40 11.47 7.69 0.610567E+09 845.62 18-JAN-10:00 10.00 9.41
February 0.359021E+10 4875.16 21-FEB-14:10 9.00 7.84 0.563062E+09 845.62 24-FEB-10:20 5.33 3.96
March 0.506970E+10 6157.15 20-MAR-12:40 10.20 6.55 0.681237E+09 845.63 28-MAR-13:09 10.17 6.98
April 0.663016E+10 7864.62 18-APR-05:01 8.83 7.35 0.609711E+09 845.67 14-APR-13:00 13.00 8.44
May 0.624398E+10 7476.86 22-MAY-15:00 24.00 16.06 0.659449E+09 845.63 16-MAY-13:09 9.83 8.37
June 0.775685E+10 9084.83 26-JUN-05:03 14.33 11.95 0.660504E+09 845.66 08-JUN-13:09 13.50 10.04
July 0.849990E+10 9205.85 10-JUL-05:03 14.50 12.63 0.614208E+09 845.64 03-JUL-09:09 14.00 10.69
August 0.922100E+10 8970.83 15-AUG-05:01 14.50 11.06 0.689173E+09 845.64 08-AUG-09:00 18.00 14.97
September 0.620234E+10 8363.49 02-SEP-05:01 13.00 11.97 0.608109E+09 845.65 06-SEP-09:09 13.33 11.44
October 0.498026E+10 8499.72 10-OCT-05:03 11.00 11.00 0.629443E+09 845.65 17-OCT-09:09 12.33 11.88
November 0.424875E+10 5072.29 13-NOV-11:40 10.33 8.92 0.620143E+09 845.63 07-NOV-14:09 11.00 10.91
December 0.376163E+10 4133.35 21-DEC-14:30 8.00 6.97 0.598768E+09 845.63 04-DEC-14:00 9.00 4.92
                     
Annual Sum or Average 0.697521E+11         0.754437E+10        
Minimum of Months 0.354730E+10 4133.35   8.00 6.55 0.563062E+09 845.62   5.33 3.96
Maximum of Months 0.922100E+10 9205.85   24.00 16.06 0.689173E+09 845.67   18.00 14.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.382031E+10 3870.19 20-JAN-09:55 4.00 3.60 0.356818E+09 544.95 20-JAN-10:20 4.67 4.23
February 0.371822E+10 5206.59 17-FEB-09:45 2.67 1.90 0.332460E+09 544.96 17-FEB-10:39 5.00 3.80
March 0.460689E+10 4436.13 31-MAR-09:30 7.00 4.33 0.405379E+09 544.95 08-MAR-10:39 7.00 3.96
April 0.677330E+10 12134.36 30-APR-08:43 17.90 12.07 0.387044E+09 544.98 14-APR-13:00 13.00 8.44
May 0.669133E+10 16292.71 21-MAY-07:32 12.23 9.52 0.418839E+09 544.96 05-MAY-13:00 8.00 6.97
June 0.745611E+10 12491.64 25-JUN-07:12 15.00 12.16 0.419718E+09 544.98 08-JUN-13:09 13.50 10.04
July 0.809691E+10 18075.63 16-JUL-07:52 16.00 13.58 0.390529E+09 544.97 03-JUL-09:09 14.00 10.69
August 0.885576E+10 18263.46 20-AUG-08:52 17.00 13.49 0.435046E+09 544.97 23-AUG-09:09 16.17 12.08
September 0.682937E+10 16817.52 04-SEP-09:02 14.08 10.76 0.386208E+09 544.99 06-SEP-09:09 13.33 11.44
October 0.488818E+10 7479.20 03-OCT-09:00 12.00 9.30 0.381670E+09 544.95 23-OCT-09:09 9.33 8.10
November 0.409418E+10 4837.53 13-NOV-09:30 8.00 7.21 0.361040E+09 544.95 13-NOV-10:09 8.17 7.54
December 0.377211E+10 3344.90 26-DEC-09:45 2.83 0.79 0.339651E+09 534.64 26-DEC-10:09 3.17 0.99
                     
Annual Sum or Average 0.696027E+11         0.461440E+10        
Minimum of Months 0.371822E+10 3344.90   2.67 0.79 0.332460E+09 534.64   3.17 0.99
Maximum of Months 0.885576E+10 18263.46   17.90 13.58 0.435046E+09 544.99   16.17 12.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.618084E+10 14593.14 20-JAN-12:00 8.00 6.07 0.579614E+09 845.65 20-JAN-10:00 6.00 5.49
February 0.642556E+10 19586.60 19-FEB-13:53 6.00 4.14 0.537492E+09 860.99 17-FEB-14:09 6.00 3.05
March 0.679240E+10 11286.91 28-MAR-12:10 11.67 7.17 0.648869E+09 845.66 28-MAR-13:09 10.17 6.98
April 0.102122E+11 19999.47 30-APR-12:43 22.00 13.20 0.599631E+09 846.75 13-APR-13:09 10.18 5.68
May 0.839078E+10 11911.46 22-MAY-12:50 21.83 14.73 0.644320E+09 845.65 09-MAY-13:09 12.00 8.86
June 0.939963E+10 11084.74 26-JUN-12:50 21.67 16.65 0.650690E+09 845.69 08-JUN-13:09 13.50 10.04
July 0.108122E+11 13478.63 31-JUL-12:40 18.00 12.00 0.606325E+09 845.65 03-JUL-09:09 14.00 10.69
August 0.131443E+11 18006.64 20-AUG-13:42 23.00 14.80 0.681224E+09 845.65 21-AUG-13:00 21.00 15.00
September 0.112632E+11 24635.21 24-SEP-14:02 21.17 15.43 0.599504E+09 845.68 28-SEP-13:00 16.00 13.03
October 0.854039E+10 20584.09 01-OCT-13:32 12.67 9.46 0.606854E+09 874.30 03-OCT-13:09 13.17 9.31
November 0.660420E+10 14757.05 03-NOV-12:40 9.00 5.47 0.587790E+09 846.66 03-NOV-13:09 9.00 5.41
December 0.585218E+10 14776.99 18-DEC-13:20 8.00 5.38 0.556495E+09 845.73 18-DEC-14:09 8.00 5.66
                     
Annual Sum or Average 0.103618E+12         0.729881E+10        
Minimum of Months 0.585218E+10 11084.74   6.00 4.14 0.537492E+09 845.65   6.00 3.05
Maximum of Months 0.131443E+11 24635.21   23.00 16.65 0.681224E+09 874.30   21.00 15.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.502434E+10 6892.65 30-JAN-16:40 7.37 6.68 0.370748E+09 544.95 19-JAN-14:00 9.00 7.43
February 0.544504E+10 14684.75 20-FEB-15:01 9.00 4.87 0.355888E+09 544.95 21-FEB-14:09 9.00 7.84
March 0.722099E+10 12232.65 24-MAR-03:01 3.90 3.15 0.439058E+09 544.96 28-MAR-13:09 10.17 6.98
April 0.104219E+11 23789.16 30-APR-16:42 24.00 12.65 0.395334E+09 544.99 14-APR-13:00 13.00 8.44
May 0.823958E+10 20029.63 28-MAY-16:12 12.67 7.93 0.419473E+09 544.96 05-MAY-13:00 8.00 6.97
June 0.102826E+11 25486.48 25-JUN-17:21 21.50 17.04 0.425138E+09 544.99 08-JUN-13:09 13.50 10.04
July 0.119867E+11 25707.42 09-JUL-18:21 21.00 15.01 0.396509E+09 544.96 03-JUL-09:09 14.00 10.69
August 0.134149E+11 23856.00 20-AUG-16:22 23.00 14.80 0.445506E+09 544.97 08-AUG-09:00 18.00 14.97
September 0.808728E+10 17068.35 01-SEP-03:01 12.92 12.36 0.383500E+09 544.97 28-SEP-13:00 16.00 13.03
October 0.672246E+10 10742.40 03-OCT-15:40 14.00 8.95 0.401286E+09 544.96 11-OCT-13:09 16.00 10.52
November 0.619096E+10 15027.27 09-NOV-04:01 10.83 10.30 0.398923E+09 544.96 07-NOV-14:09 11.00 10.91
December 0.609149E+10 11241.43 11-DEC-04:01 3.00 3.00 0.389570E+09 544.96 04-DEC-14:00 9.00 4.92
                     
Annual Sum or Average 0.991282E+11         0.482093E+10        
Minimum of Months 0.502434E+10 6892.65   3.00 3.00 0.355888E+09 544.95   8.00 4.92
Maximum of Months 0.134149E+11 25707.42   24.00 17.04 0.445506E+09 544.99   18.00 14.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.225261E+10 2568.64 19-JAN-15:30 8.50 7.45 0.552637E+09 845.60 19-JAN-14:00 9.00 7.43
February 0.217479E+10 2236.28 07-FEB-15:00 11.00 9.86 0.512819E+09 841.86 22-FEB-14:00 9.00 6.98
March 0.298902E+10 3841.67 30-MAR-13:50 12.83 7.47 0.642633E+09 845.63 28-MAR-13:09 10.17 6.98
April 0.407762E+10 6213.87 28-APR-15:10 20.08 13.46 0.595724E+09 845.66 14-APR-13:00 13.00 8.44
May 0.448555E+10 6425.94 31-MAY-16:00 21.00 15.00 0.647949E+09 845.62 05-MAY-13:00 8.00 6.97
June 0.570576E+10 7687.21 13-JUN-16:00 26.50 17.68 0.655379E+09 845.65 08-JUN-13:09 13.50 10.04
July 0.594435E+10 8186.48 18-JUL-05:01 16.00 14.13 0.608902E+09 845.63 03-JUL-09:09 14.00 10.69
August 0.616017E+10 6785.99 14-AUG-16:00 26.00 15.84 0.682726E+09 845.63 23-AUG-09:09 16.17 12.08
September 0.463165E+10 6355.59 13-SEP-15:30 23.00 16.21 0.598316E+09 845.64 19-SEP-13:00 14.00 14.00
October 0.313754E+10 4559.14 11-OCT-15:00 17.00 11.02 0.601889E+09 845.61 11-OCT-13:09 16.00 10.52
November 0.240807E+10 3001.22 08-NOV-15:00 12.00 12.00 0.564860E+09 845.61 08-NOV-14:00 12.00 12.00
December 0.189222E+10 2049.00 20-DEC-14:40 9.00 7.93 0.510972E+09 798.39 20-DEC-14:50 9.00 7.93
                     
Annual Sum or Average 0.458593E+11         0.717481E+10        
Minimum of Months 0.189222E+10 2049.00   8.50 7.45 0.510972E+09 798.39   8.00 6.97
Maximum of Months 0.616017E+10 8186.48   26.50 17.68 0.682726E+09 845.66   16.17 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255348E+10 3239.84 20-JAN-10:00 4.00 3.60 0.235393E+09 489.72 20-JAN-09:00 4.00 3.60
February 0.257368E+10 3481.09 17-FEB-09:55 3.00 2.16 0.220211E+09 518.99 17-FEB-09:00 3.00 2.16
March 0.353007E+10 3359.52 30-MAR-14:20 12.67 7.08 0.269254E+09 497.87 30-MAR-10:39 9.67 6.88
April 0.564194E+10 11927.76 30-APR-08:43 17.90 12.07 0.277658E+09 521.26 28-APR-07:30 13.65 12.84
May 0.595080E+10 11483.08 23-MAY-08:40 18.33 14.51 0.297970E+09 521.21 22-MAY-14:09 23.17 15.80
June 0.672046E+10 11799.19 13-JUN-08:40 21.40 15.96 0.301268E+09 521.24 09-JUN-07:10 12.17 10.98
July 0.695923E+10 20371.96 23-JUL-09:42 20.83 15.93 0.282665E+09 521.22 31-JUL-08:09 14.83 10.70
August 0.753428E+10 10784.09 18-AUG-08:40 19.00 15.27 0.312460E+09 521.22 29-AUG-10:09 18.00 14.38
September 0.614201E+10 11612.64 04-SEP-09:21 14.25 10.91 0.276422E+09 521.24 21-SEP-08:09 13.00 11.30
October 0.393222E+10 6221.70 04-OCT-09:00 12.00 9.30 0.258744E+09 521.20 02-OCT-10:30 12.50 9.90
November 0.278535E+10 3196.48 13-NOV-09:40 8.00 7.29 0.236766E+09 487.18 13-NOV-09:50 8.00 7.37
December 0.191919E+10 2810.87 06-DEC-09:50 3.67 2.86 0.220514E+09 444.92 06-DEC-09:00 4.00 3.11
                     
Annual Sum or Average 0.562427E+11         0.318932E+10        
Minimum of Months 0.191919E+10 2810.87   3.00 2.16 0.220211E+09 444.92   3.00 2.16
Maximum of Months 0.753428E+10 20371.96   21.40 15.96 0.312460E+09 521.26   23.17 15.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.535993E+10 19699.82 15-JAN-13:13 9.67 6.80 0.560263E+09 845.65 10-JAN-10:00 -2.0 -2.0
February 0.552169E+10 15469.57 17-FEB-13:40 6.00 3.24 0.517685E+09 880.65 17-FEB-14:09 6.00 3.05
March 0.550404E+10 10012.05 28-MAR-12:10 11.67 7.17 0.615561E+09 845.66 28-MAR-13:09 10.17 6.98
April 0.843865E+10 20729.70 30-APR-13:23 22.50 12.91 0.584082E+09 845.69 14-APR-13:00 13.00 8.44
May 0.741370E+10 11717.30 22-MAY-13:10 22.17 14.94 0.625201E+09 845.65 05-MAY-13:50 8.33 6.95
June 0.802600E+10 10618.62 13-JUN-13:10 24.18 17.10 0.634450E+09 845.69 08-JUN-13:09 13.50 10.04
July 0.873773E+10 12750.17 31-JUL-13:10 18.17 12.07 0.593270E+09 845.65 27-JUL-13:09 15.17 13.17
August 0.107600E+11 16416.76 30-AUG-13:00 21.00 15.44 0.666037E+09 845.65 21-AUG-13:00 21.00 15.00
September 0.107632E+11 25997.83 10-SEP-13:32 21.00 15.80 0.590604E+09 857.81 29-SEP-13:30 16.00 9.45
October 0.768954E+10 21177.03 01-OCT-13:23 12.50 9.55 0.584623E+09 890.07 03-OCT-13:20 13.33 9.33
November 0.524364E+10 14348.36 03-NOV-12:40 9.00 5.47 0.555248E+09 845.64 17-NOV-14:09 8.00 6.01
December 0.388909E+10 13587.95 18-DEC-13:30 8.00 5.45 0.516191E+09 845.64 26-DEC-14:00 6.00 3.37
                     
Annual Sum or Average 0.873472E+11         0.704322E+10        
Minimum of Months 0.388909E+10 10012.05   6.00 3.24 0.516191E+09 845.64   -2.0 -2.0
Maximum of Months 0.107632E+11 25997.83   24.18 17.10 0.666037E+09 890.07   21.00 15.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288720E+10 4120.14 19-JAN-16:00 8.00 7.45 0.325875E+09 521.19 19-JAN-16:10 7.67 7.22
February 0.305104E+10 6680.95 27-FEB-16:30 8.00 6.72 0.305678E+09 533.64 27-FEB-14:00 8.00 6.96
March 0.397473E+10 6774.81 23-MAR-17:00 10.00 6.64 0.372972E+09 535.75 10-MAR-14:00 9.00 4.93
April 0.567402E+10 20261.01 30-APR-17:22 24.00 12.83 0.361461E+09 544.93 28-APR-13:00 20.00 12.74
May 0.614391E+10 20590.05 21-MAY-18:02 19.83 13.21 0.391023E+09 544.91 01-MAY-13:00 12.00 8.01
June 0.723930E+10 18617.54 25-JUN-17:42 21.83 18.98 0.402355E+09 544.93 14-JUN-13:50 13.83 12.77
July 0.760566E+10 20717.56 23-JUL-17:21 21.00 16.53 0.377135E+09 544.95 27-JUL-13:09 15.17 13.17
August 0.771795E+10 18703.77 20-AUG-17:02 21.17 14.67 0.416982E+09 544.93 03-AUG-13:00 19.00 14.77
September 0.607058E+10 11659.17 12-SEP-16:00 21.00 15.98 0.356656E+09 544.02 01-SEP-13:00 18.00 13.90
October 0.422041E+10 8363.12 03-OCT-16:00 14.00 8.95 0.349270E+09 530.21 10-OCT-13:00 13.00 11.87
November 0.315022E+10 4106.54 10-NOV-15:40 11.33 8.40 0.328815E+09 535.35 15-NOV-14:00 12.00 8.89
December 0.229647E+10 3180.13 21-DEC-14:50 8.00 6.97 0.303377E+09 492.73 21-DEC-14:00 8.00 6.97
                     
Annual Sum or Average 0.600315E+11         0.429160E+10        
Minimum of Months 0.229647E+10 3180.13   8.00 6.64 0.303377E+09 492.73   7.67 4.93
Maximum of Months 0.771795E+10 20717.56   24.00 18.98 0.416982E+09 544.95   20.00 14.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120268E+10 2298.32 19-JAN-15:50 8.17 7.45 0.490110E+09 785.38 19-JAN-14:00 9.00 7.43
February 0.136247E+10 2208.38 09-FEB-16:30 7.00 5.14 0.454062E+09 759.05 09-FEB-14:00 8.00 6.07
March 0.228828E+10 2674.09 30-MAR-14:00 13.00 7.35 0.574488E+09 832.21 30-MAR-13:00 13.00 7.35
April 0.357975E+10 6746.40 28-APR-15:30 20.05 13.00 0.565816E+09 845.65 14-APR-13:00 13.00 8.44
May 0.410567E+10 7294.61 22-MAY-15:30 23.50 15.66 0.622035E+09 845.62 05-MAY-13:00 8.00 6.97
June 0.558495E+10 8802.08 13-JUN-15:50 26.42 17.70 0.643798E+09 845.65 08-JUN-13:09 13.50 10.04
July 0.596325E+10 8469.00 10-JUL-15:00 23.00 16.68 0.600624E+09 845.62 27-JUL-13:09 15.17 13.17
August 0.603175E+10 7619.82 14-AUG-16:00 26.00 15.84 0.669843E+09 845.62 15-AUG-09:20 16.00 13.59
September 0.423959E+10 6777.74 13-SEP-15:30 23.00 16.21 0.574616E+09 845.64 19-SEP-13:00 14.00 14.00
October 0.246881E+10 3803.47 06-OCT-15:50 17.00 9.19 0.542968E+09 845.59 11-OCT-13:00 16.00 10.21
November 0.160592E+10 2503.15 10-NOV-15:00 12.00 8.41 0.499840E+09 805.70 10-NOV-14:00 12.00 8.41
December 0.924442E+09 2127.14 29-DEC-17:00 -2.0 -2.7 0.460666E+09 721.37 21-DEC-14:00 8.00 6.97
                     
Annual Sum or Average 0.393576E+11         0.669887E+10        
Minimum of Months 0.924442E+09 2127.14   -2.0 -2.7 0.454062E+09 721.37   8.00 6.07
Maximum of Months 0.603175E+10 8802.08   26.42 17.70 0.669843E+09 845.65   16.00 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.126738E+10 2727.69 20-JAN-10:10 4.33 3.91 0.305446E+09 460.86 20-JAN-10:20 4.67 4.23
February 0.152902E+10 2928.82 24-FEB-10:10 5.17 3.81 0.283392E+09 484.23 24-FEB-10:20 5.33 3.96
March 0.246579E+10 3237.65 30-MAR-14:00 13.00 7.35 0.347686E+09 487.56 10-MAR-14:00 9.00 4.93
April 0.495820E+10 18214.35 30-APR-09:12 18.67 12.22 0.373014E+09 544.98 14-APR-13:00 13.00 8.44
May 0.540203E+10 11123.74 23-MAY-09:00 19.00 14.77 0.400078E+09 544.96 05-MAY-13:00 8.00 6.97
June 0.647428E+10 11792.58 13-JUN-08:50 21.50 15.95 0.409054E+09 544.98 08-JUN-13:09 13.50 10.04
July 0.674244E+10 20098.81 23-JUL-09:42 20.83 15.93 0.384433E+09 544.97 03-JUL-09:09 14.00 10.69
August 0.721910E+10 15447.46 20-AUG-08:52 17.00 13.49 0.425784E+09 544.97 23-AUG-09:09 16.17 12.08
September 0.546089E+10 9397.91 12-SEP-09:10 17.83 14.41 0.374290E+09 544.98 06-SEP-09:09 13.33 11.44
October 0.293704E+10 4662.08 04-OCT-09:30 12.50 9.56 0.335660E+09 544.95 04-OCT-09:30 12.50 9.56
November 0.162804E+10 2997.76 10-NOV-15:00 12.00 8.41 0.306003E+09 467.06 10-NOV-14:00 12.00 8.41
December 0.906935E+09 2416.60 21-DEC-14:50 8.00 6.97 0.290402E+09 425.16 21-DEC-14:00 8.00 6.97
                     
Annual Sum or Average 0.469912E+11         0.423524E+10        
Minimum of Months 0.906935E+09 2416.60   4.33 3.81 0.283392E+09 425.16   4.67 3.96
Maximum of Months 0.721910E+10 20098.81   21.50 15.95 0.425784E+09 544.98   16.17 12.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.334826E+10 11817.25 20-JAN-12:00 8.00 6.07 0.514780E+09 845.64 20-JAN-10:00 6.00 5.49
February 0.383912E+10 14947.14 17-FEB-13:40 6.00 3.24 0.481975E+09 845.64 27-FEB-14:09 8.83 7.77
March 0.408927E+10 7905.14 10-MAR-14:30 8.50 4.87 0.567662E+09 845.65 28-MAR-13:09 10.17 6.98
April 0.756747E+10 27442.29 30-APR-13:12 22.33 12.96 0.560623E+09 845.69 14-APR-13:00 13.00 8.44
May 0.685806E+10 12344.42 22-MAY-13:10 22.17 14.94 0.598783E+09 845.65 05-MAY-13:00 8.00 6.97
June 0.790878E+10 11621.12 13-JUN-13:10 24.18 17.10 0.616668E+09 845.68 08-JUN-13:09 13.50 10.04
July 0.872721E+10 12931.89 31-JUL-13:10 18.17 12.07 0.579822E+09 845.65 27-JUL-13:09 15.17 13.17
August 0.105658E+11 16472.41 30-AUG-13:00 21.00 15.44 0.648963E+09 845.65 21-AUG-13:00 21.00 15.00
September 0.995159E+10 27062.05 10-SEP-13:22 21.00 15.71 0.572875E+09 845.68 28-SEP-13:00 16.00 13.03
October 0.615480E+10 17604.00 03-OCT-14:00 14.00 9.39 0.547902E+09 855.83 03-OCT-13:20 13.33 9.33
November 0.361554E+10 12452.84 03-NOV-12:40 9.00 5.47 0.511548E+09 845.64 03-NOV-13:50 9.00 5.65
December 0.223699E+10 9770.53 18-DEC-13:30 8.00 5.45 0.480915E+09 845.64 26-DEC-14:00 6.00 3.37
                     
Annual Sum or Average 0.748629E+11         0.668251E+10        
Minimum of Months 0.223699E+10 7905.14   6.00 3.24 0.480915E+09 845.64   6.00 3.37
Maximum of Months 0.105658E+11 27442.29   24.18 17.10 0.648963E+09 855.83   21.00 15.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.166640E+10 3791.64 10-JAN-16:00 -3.0 -5.6 0.308584E+09 508.49 19-JAN-16:10 7.67 7.22
February 0.206226E+10 5477.77 27-FEB-16:40 8.00 6.80 0.288565E+09 521.18 27-FEB-16:00 8.00 6.96
March 0.302281E+10 6168.73 23-MAR-17:00 10.00 6.64 0.349122E+09 521.18 10-MAR-16:00 7.00 3.91
April 0.524645E+10 21964.14 30-APR-17:11 24.00 12.74 0.344481E+09 544.89 21-APR-13:00 14.00 9.38
May 0.579226E+10 21707.40 21-MAY-18:02 19.83 13.21 0.375271E+09 544.91 23-MAY-13:00 19.00 14.76
June 0.718046E+10 22914.80 25-JUN-16:52 21.00 13.99 0.390772E+09 544.93 21-JUN-13:00 22.00 15.84
July 0.760754E+10 24078.86 09-JUL-17:11 21.00 15.01 0.368115E+09 544.95 10-JUL-13:50 21.50 15.64
August 0.763902E+10 21688.86 20-AUG-16:31 22.67 14.80 0.404551E+09 544.92 14-AUG-13:00 24.00 16.56
September 0.567335E+10 11947.35 12-SEP-16:00 21.00 15.98 0.342317E+09 538.45 13-SEP-13:00 23.00 16.21
October 0.334247E+10 8021.05 03-OCT-16:00 14.00 8.95 0.327194E+09 521.20 11-OCT-15:39 14.33 10.65
November 0.209467E+10 3832.43 10-NOV-15:40 11.33 8.40 0.308969E+09 507.64 15-NOV-14:00 12.00 8.89
December 0.119986E+10 3077.24 21-DEC-15:00 8.00 6.97 0.292082E+09 463.76 21-DEC-14:00 8.00 6.97
                     
Annual Sum or Average 0.525276E+11         0.410002E+10        
Minimum of Months 0.119986E+10 3077.24   -3.0 -5.6 0.288565E+09 463.76   7.00 3.91
Maximum of Months 0.763902E+10 24078.86   24.00 15.98 0.404551E+09 544.95   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.437801E+10 9335.52 02-JAN-06:13 1.33 0.92 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.408771E+10 5983.58 21-FEB-06:15 4.60 4.37 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.553344E+10 7332.90 20-MAR-05:13 5.00 4.51 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.698147E+10 8131.79 24-APR-05:15 7.00 4.99 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.607099E+10 7800.15 01-MAY-05:13 4.67 3.90 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.710323E+10 9212.12 26-JUN-05:13 14.67 12.17 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.761800E+10 8620.11 05-JUL-05:15 7.67 6.97 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.835494E+10 9183.27 28-AUG-05:13 9.33 8.59 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.639281E+10 7967.94 05-SEP-05:15 6.67 5.99 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.566036E+10 8499.70 10-OCT-05:15 11.00 11.00 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.505331E+10 8357.80 13-NOV-06:15 4.33 3.86 0.00 0.00 01-NOV-00:10 6.57 4.28
December 0.457469E+10 6875.81 26-DEC-06:05 1.92 0.28 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.718090E+11         0.00        
Minimum of Months 0.408771E+10 5983.58   1.33 0.28 0.00 0.00   1.92 1.45
Maximum of Months 0.835494E+10 9335.52   14.67 12.17 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243319E+10 5093.11 10-JAN-06:01 -4.0 -4.8 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.223043E+10 4884.83 25-FEB-06:08 1.00 1.00 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.315969E+10 5028.35 27-MAR-05:10 0.83 0.07 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.424514E+10 6163.67 29-APR-05:13 6.33 5.81 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.416399E+10 5264.80 06-MAY-05:10 2.17 1.67 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.500761E+10 5833.77 15-JUN-05:13 12.00 10.35 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.519484E+10 6442.61 07-JUL-05:13 13.67 11.76 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.559677E+10 6218.22 05-AUG-05:13 10.00 9.27 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.475359E+10 5737.05 28-SEP-05:13 7.67 6.33 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.358523E+10 5514.28 10-OCT-05:10 11.00 11.00 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.258662E+10 4907.19 13-NOV-06:10 4.17 3.69 0.00 0.00 01-NOV-00:10 6.57 4.28
December 0.183704E+10 5317.05 30-DEC-06:01 -1.0 -2.4 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.447942E+11         0.00        
Minimum of Months 0.183704E+10 4884.83   -4.0 -4.8 0.00 0.00   1.92 1.45
Maximum of Months 0.559677E+10 6442.61   13.67 11.76 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 87964785.58 1866.70 19-JAN-15:00 9.00 7.43 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.201543E+09 2556.27 09-FEB-15:00 8.00 6.07 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.830644E+09 4463.92 25-MAR-12:40 13.33 10.43 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.504627E+10 14372.57 28-APR-14:40 20.07 13.37 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.571112E+10 15301.15 22-MAY-14:40 23.67 15.96 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.792181E+10 16928.66 13-JUN-14:30 25.55 17.63 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.871545E+10 16772.65 21-JUL-14:40 27.00 15.93 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.830966E+10 14724.56 14-AUG-15:00 25.00 16.00 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.529207E+10 12742.89 12-SEP-13:10 20.17 16.23 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.147816E+10 7044.12 04-OCT-13:30 14.00 10.27 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.167243E+09 3003.70 10-NOV-14:00 12.00 8.90 0.00 0.00 01-NOV-00:10 6.57 4.28
December 2695133.99 280.42 06-DEC-12:50 7.17 5.22 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.437646E+11         0.00        
Minimum of Months 2695133.99 280.42   7.17 5.22 0.00 0.00   1.92 1.45
Maximum of Months 0.871545E+10 16928.66   27.00 17.63 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.354169E+10 1915.99 19-JAN-16:20 7.33 6.98 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.803444E+10 4085.89 27-FEB-17:00 8.00 6.96 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.141806E+11 5932.90 23-MAR-17:30 9.00 6.39 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.189333E+11 7979.34 27-APR-17:50 18.00 10.52 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.424413E+10 2241.13 21-MAY-18:34 19.33 13.21 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.920565E+10 4170.65 11-JUN-18:45 13.17 11.94 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.146289E+11 6252.48 09-JUL-18:48 21.00 15.01 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.196200E+11 8027.71 13-AUG-18:23 17.50 13.93 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.408413E+10 2174.25 12-SEP-17:20 18.33 15.24 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.916660E+10 4047.63 03-OCT-16:40 13.33 8.61 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.137039E+11 5701.71 03-NOV-16:00 8.00 4.83 0.00 0.00 01-NOV-00:10 6.57 4.28
December 0.190875E+11 7519.13 25-DEC-15:00 6.30 4.49 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.138431E+12         0.00        
Minimum of Months 0.354169E+10 1915.99   6.30 4.49 0.00 0.00   1.92 1.45
Maximum of Months 0.196200E+11 8027.71   21.00 15.24 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.212152E+10 1708.37 19-JAN-16:30 7.00 6.74 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.651785E+10 3738.93 27-FEB-17:00 8.00 6.96 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.124044E+11 5564.21 23-MAR-17:30 9.00 6.39 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.174899E+11 7607.04 27-APR-17:50 18.00 10.52 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.341734E+10 2108.29 21-MAY-18:25 19.50 13.21 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.832679E+10 3895.29 11-JUN-18:50 13.17 11.94 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.135460E+11 5844.05 09-JUL-18:48 21.00 15.01 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.183591E+11 7469.02 04-AUG-18:10 16.83 13.41 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.327153E+10 2052.67 12-SEP-17:20 18.33 15.24 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.772000E+10 3785.32 03-OCT-16:50 13.17 8.53 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.117453E+11 5293.81 03-NOV-16:00 8.00 4.83 0.00 0.00 01-NOV-00:10 6.57 4.28
December 0.164478E+11 6847.31 21-DEC-15:20 7.67 6.81 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.121368E+12         0.00        
Minimum of Months 0.212152E+10 1708.37   7.00 4.83 0.00 0.00   1.92 1.45
Maximum of Months 0.183591E+11 7607.04   21.00 15.24 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.599120E+09 1621.25 19-JAN-16:30 7.00 6.74 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.472770E+10 3560.44 17-FEB-17:00 5.00 2.85 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.109231E+11 5514.88 23-MAR-17:30 9.00 6.39 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.167029E+11 7677.97 27-APR-17:50 18.00 10.52 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.272335E+10 2186.85 21-MAY-18:27 19.50 13.21 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.797289E+10 4056.92 11-JUN-18:40 13.33 12.00 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.132428E+11 6004.24 09-JUL-18:42 21.00 15.01 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.180248E+11 7569.31 13-AUG-18:10 17.83 13.91 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.261471E+10 2105.45 12-SEP-17:20 18.33 15.24 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.631329E+10 3768.57 03-OCT-16:50 13.17 8.53 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.999951E+10 5206.35 10-NOV-16:20 9.67 7.82 0.00 0.00 01-NOV-00:10 6.57 4.28
December 0.142573E+11 6661.51 21-DEC-15:20 7.67 6.81 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.108101E+12         0.00        
Minimum of Months 0.599120E+09 1621.25   5.00 2.85 0.00 0.00   1.92 1.45
Maximum of Months 0.180248E+11 7677.97   21.00 15.24 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.238330E+12 336712.94 21-JAN-04:13 1.93 1.46 0.00 0.00 01-JAN-00:10 1.92 1.45
February 0.435914E+12 365576.64 07-FEB-04:05 6.00 6.00 0.00 0.00 01-FEB-00:10 7.00 5.79
March 0.728591E+12 395605.94 02-MAR-04:02 4.27 3.68 0.00 0.00 01-MAR-00:10 3.80 3.71
April 0.944728E+12 389920.83 26-APR-03:44 5.93 4.54 0.00 0.00 01-APR-00:10 4.23 1.83
May 0.240191E+12 338211.41 11-MAY-22:13 9.00 7.42 0.00 0.00 01-MAY-00:10 10.47 8.15
June 0.469319E+12 413682.84 18-JUN-21:21 9.50 9.21 0.00 0.00 01-JUN-00:10 9.27 7.38
July 0.731062E+12 395846.04 31-JUL-03:22 9.00 6.35 0.00 0.00 01-JUL-00:10 11.00 9.95
August 0.977581E+12 392327.77 03-AUG-03:42 9.33 9.16 0.00 0.00 01-AUG-00:10 11.43 9.82
September 0.233560E+12 318739.20 19-SEP-21:18 9.33 8.76 0.00 0.00 01-SEP-00:10 12.43 10.95
October 0.485038E+12 378622.76 14-OCT-19:27 6.50 5.98 0.00 0.00 01-OCT-00:10 7.57 5.82
November 0.706846E+12 391092.63 14-NOV-02:37 8.00 8.00 0.00 0.00 01-NOV-00:10 6.57 4.28
December 0.975392E+12 387238.34 12-DEC-05:23 3.50 3.07 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.716655E+13         0.00        
Minimum of Months 0.233560E+12 318739.20   1.93 1.46 0.00 0.00   1.92 1.45
Maximum of Months 0.977581E+12 413682.84   9.50 9.21 0.00 0.00   12.43 10.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.601962E+09 139612.42 20-JAN-04:45 1.05
February 0.146032E+09 139386.12 07-FEB-04:45 6.00
March 0.573063E+09 131985.33 01-MAR-04:47 3.85
April 0.551056E+09 133748.05 30-APR-18:00 24.00
May 0.855117E+09 131423.28 03-MAY-03:47 4.17
June 0.412886E+09 139161.72 25-JUN-17:50 21.83
July 0.103626E+10 136218.59 23-JUL-15:30 21.50
August 0.621463E+09 138503.14 20-AUG-15:20 23.33
September 0.503856E+09 128393.39 04-SEP-11:30 15.50
October 0.472838E+09 119410.74 09-OCT-07:30 11.50
November 0.542647E+09 131257.42 30-NOV-04:47 3.17
December 0.799030E+09 131749.68 15-DEC-04:47 2.67
         
Annual Sum or Average 0.711621E+10      
Minimum of Months 0.146032E+09 119410.74   1.05
Maximum of Months 0.103626E+10 139612.42   24.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.918560E+09 72845.64 02-JAN-04:01 1.17
February 0.293378E+09 65090.40 21-FEB-05:01 5.48
March 63750794.97 62451.34 06-MAR-06:01 4.00
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 10542351.51 37097.67 23-OCT-05:03 3.17
November 0.283707E+09 65940.85 20-NOV-05:01 0.67
December 0.882030E+09 69129.52 26-DEC-05:01 1.98
         
Annual Sum or Average 0.245197E+10      
Minimum of Months 0.00 0.00   0.67
Maximum of Months 0.918560E+09 72845.64   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 34716.98 578.62 30-DEC-06:01 -1.0
         
Annual Sum or Average 34716.98      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 34716.98 578.62   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 27203.68 317.38 20-NOV-06:01 -0.7
December 305334.53 3455.74 11-DEC-06:01 3.17
         
Annual Sum or Average 332538.21      
Minimum of Months 0.00 0.00   -0.7
Maximum of Months 305334.53 3455.74   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 45561052.68 8691.83 11-JAN-06:01 -2.9
February 8032470.31 8457.58 13-FEB-06:01 -1.0
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 25167364.77 8593.06 20-NOV-06:01 -0.7
December 0.107217E+09 9094.23 26-DEC-05:01 1.98
         
Annual Sum or Average 0.185978E+09      
Minimum of Months 0.00 0.00   -2.9
Maximum of Months 0.107217E+09 9094.23   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 39147208.16 9263.45 11-JAN-06:01 -2.9
February 7974054.71 8603.42 17-FEB-06:01 -3.1
March 946875.77 3280.74 04-MAR-06:03 3.00
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 15719.32 87.14 30-OCT-05:10 7.00
November 21561356.89 9016.86 28-NOV-06:01 1.00
December 0.100730E+09 9305.90 26-DEC-05:01 1.98
         
Annual Sum or Average 0.170375E+09      
Minimum of Months 0.00 0.00   -3.1
Maximum of Months 0.100730E+09 9305.90   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 15053887.57 12953.50 11-JAN-06:01 -2.9
February 760134.14 6660.53 17-FEB-06:01 -3.1
March 152541.64 863.80 04-MAR-06:03 3.00
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 8960956.19 12755.45 27-NOV-06:01 4.00
December 69923416.25 13285.75 28-DEC-06:01 1.00
         
Annual Sum or Average 94850935.79      
Minimum of Months 0.00 0.00   -3.1
Maximum of Months 69923416.25 13285.75   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17636761.70 8042.36 11-JAN-06:01 -2.9
February 1387347.01 7431.07 13-FEB-06:01 -1.0
March 16084.20 162.56 16-MAR-05:06 1.08
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 9259669.77 7800.24 28-NOV-06:01 1.00
December 41973614.60 7968.04 28-DEC-06:01 1.00
         
Annual Sum or Average 70273477.28      
Minimum of Months 0.00 0.00   -2.9
Maximum of Months 41973614.60 8042.36   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.144481E+10 12144.95 01-JAN-18:15 2.80
February 0.849768E+09 11309.31 13-FEB-04:01 -1.8
March 0.385623E+09 10737.91 06-MAR-05:01 3.83
April 26153487.81 9522.66 01-APR-05:01 2.17
May 19250221.25 9592.34 05-MAY-05:02 6.00
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 892467.38 5994.26 18-SEP-05:02 12.00
October 0.187039E+09 10441.15 30-OCT-04:01 7.00
November 0.766890E+09 11716.28 20-NOV-04:01 1.83
December 0.184125E+10 12080.90 04-DEC-04:01 1.33
         
Annual Sum or Average 0.552167E+10      
Minimum of Months 0.00 0.00   -1.8
Maximum of Months 0.184125E+10 12144.95   12.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.884651E+09 14617.29 02-JAN-04:01 1.17
February 0.521761E+09 13538.99 13-FEB-04:01 -1.8
March 0.267668E+09 12951.95 06-MAR-05:01 3.83
April 11199508.43 11379.31 01-APR-05:01 2.17
May 9179843.09 11372.81 02-MAY-05:01 4.17
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 58104.13 632.83 21-SEP-05:03 5.83
October 0.134359E+09 12383.42 30-OCT-04:01 7.00
November 0.499395E+09 14172.82 20-NOV-04:01 1.83
December 0.123550E+10 14784.07 04-DEC-04:01 1.33
         
Annual Sum or Average 0.356377E+10      
Minimum of Months 0.00 0.00   -1.8
Maximum of Months 0.123550E+10 14784.07   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.928768E+09 20931.91 02-JAN-04:01 1.17
February 0.574626E+09 18834.49 27-FEB-05:01 6.00
March 0.339408E+09 18693.23 06-MAR-05:01 3.83
April 13182809.20 16494.24 11-APR-05:01 5.83
May 27706755.84 16655.04 16-MAY-05:01 6.33
June 580631.34 8216.09 08-JUN-05:01 6.17
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 13229.18 220.49 07-SEP-05:03 8.83
October 0.123994E+09 17536.53 30-OCT-04:01 7.00
November 0.552332E+09 19939.19 27-NOV-04:02 4.83
December 0.146770E+10 20971.21 26-DEC-04:01 2.00
         
Annual Sum or Average 0.402832E+10      
Minimum of Months 0.00 0.00   1.17
Maximum of Months 0.146770E+10 20971.21   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.546382E+09 14365.09 02-JAN-04:01 1.17
February 0.292075E+09 12686.42 13-FEB-05:01 -1.0
March 0.123031E+09 11762.84 06-MAR-05:01 3.83
April 480493.20 1194.72 24-APR-05:03 7.00
May 7977328.30 10786.47 16-MAY-05:01 6.33
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 31939.20 309.65 07-SEP-05:01 8.83
October 45887233.66 11121.60 28-OCT-05:01 7.00
November 0.283814E+09 12865.88 20-NOV-05:01 0.67
December 0.710500E+09 14410.54 26-DEC-04:01 2.00
         
Annual Sum or Average 0.201018E+10      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 0.710500E+09 14410.54   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 41703202.36 8968.11 17-JAN-04:02 5.92
February 53017273.78 9911.13 27-FEB-04:02 6.00
March 58072188.91 10580.43 06-MAR-04:01 3.80
April 90570163.36 11009.07 07-APR-03:01 5.75
May 63335269.71 9716.45 01-MAY-03:01 6.17
June 66644369.11 9832.33 12-JUN-03:01 8.83
July 97409624.78 10974.04 28-JUL-03:01 13.17
August 92354884.71 10881.23 18-AUG-03:01 14.00
September 52788206.28 10629.09 01-SEP-03:01 12.92
October 57919349.56 9855.07 30-OCT-03:02 7.00
November 72486129.23 11094.07 09-NOV-04:01 10.83
December 71353742.20 12314.76 11-DEC-04:01 3.00
         
Annual Sum or Average 0.817654E+09      
Minimum of Months 41703202.36 8968.11   3.00
Maximum of Months 97409624.78 12314.76   14.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 31439258.26 6839.67 18-JAN-06:01 6.17
February 28835487.33 7389.37 08-FEB-06:01 6.00
March 18020754.06 7304.15 07-MAR-06:01 4.00
April 28174615.70 6404.34 03-APR-04:01 4.42
May 50221246.04 6581.17 30-MAY-04:03 8.00
June 42057955.63 7287.53 19-JUN-04:01 11.00
July 45949192.44 7944.57 03-JUL-04:01 9.00
August 43972639.23 6208.58 22-AUG-04:03 13.83
September 47537662.33 6832.77 18-SEP-05:02 12.00
October 26874541.98 6915.48 31-OCT-05:01 7.00
November 35535139.74 7167.13 02-NOV-05:01 8.00
December 0.108295E+09 7520.54 20-DEC-06:01 4.33
         
Annual Sum or Average 0.506913E+09      
Minimum of Months 18020754.06 6208.58   4.00
Maximum of Months 0.108295E+09 7944.57   13.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.468170E+10 20631.00 02-JAN-05:31 1.00
February 0.308870E+10 14853.40 13-FEB-06:02 -1.0
March 0.230298E+10 10804.67 06-MAR-06:02 4.00
April 0.926207E+09 22365.86 27-APR-05:01 4.00
May 0.643782E+09 20390.26 25-MAY-05:01 7.17
June 0.224267E+09 20867.45 01-JUN-05:01 6.50
July 0.174160E+09 19673.79 05-JUL-05:03 7.33
August 0.264421E+09 19197.39 23-AUG-05:01 9.33
September 0.602243E+09 19760.42 27-SEP-05:01 8.83
October 0.173174E+10 9585.69 13-OCT-05:01 10.83
November 0.308632E+10 15468.71 20-NOV-06:03 -0.7
December 0.548906E+10 19708.84 26-DEC-05:12 1.97
         
Annual Sum or Average 0.232156E+11      
Minimum of Months 0.174160E+09 9585.69   -1.0
Maximum of Months 0.548906E+10 22365.86   10.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.532948E+09 610.87 14-JAN-04:42 4.45
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:05 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 313821.92 383.26 17-SEP-07:05 10.33
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.533262E+09      
Minimum of Months 0.00 0.00   3.80
Maximum of Months 0.532948E+09 610.87   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.245518E+09 57555.01 21-JAN-04:41 1.98
February 16011020.32 28076.99 03-FEB-05:31 3.33
March 995027.40 16583.79 02-MAR-04:01 4.27
April 0.00 0.00 01-APR-00:10 4.23
May 0.219650E+09 50753.24 11-MAY-22:11 9.00
June 9404232.38 11877.02 18-JUN-21:26 9.50
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 26221733.04 40365.70 19-SEP-21:19 9.33
October 22693229.63 10656.41 14-OCT-19:29 6.50
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.540493E+09      
Minimum of Months 0.00 0.00   1.98
Maximum of Months 0.245518E+09 57555.01   11.43



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.215029E+11 22401.15 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.195042E+11 22401.15 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.231659E+11 22401.15 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.207025E+11 22401.15 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.223344E+11 22401.15 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.222225E+11 22401.15 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.208144E+11 22401.15 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.231659E+11 22401.15 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.207025E+11 22401.15 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.215029E+11 22401.15 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.212480E+11 22401.15 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.208144E+11 22401.15 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.257680E+12     0.424397E+12    
Minimum of Months 0.195042E+11 22401.15   0.325565E+11 13457.54  
Maximum of Months 0.231659E+11 22401.15   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.193111E+11 20117.80 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.175161E+11 20117.80 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.208046E+11 20117.80 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.185923E+11 20117.80 03-APR-07:10 0.261233E+11 18128.59 03-APR-07:10
May 0.200579E+11 20117.80 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.199573E+11 20117.80 01-JUN-07:10 0.270334E+11 18128.59 01-JUN-07:10
July 0.186928E+11 20117.80 03-JUL-07:10 0.266454E+11 18128.59 03-JUL-07:10
August 0.208046E+11 20117.80 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.185923E+11 20117.80 01-SEP-07:10 0.261233E+11 18128.59 01-SEP-07:10
October 0.193111E+11 20117.80 02-OCT-07:10 0.270551E+11 18128.59 02-OCT-07:10
November 0.190822E+11 20117.80 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.186928E+11 20117.80 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.231415E+12     0.321278E+12    
Minimum of Months 0.175161E+11 20117.80   0.244881E+11 18128.59  
Maximum of Months 0.208046E+11 20117.80   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.193111E+11 20117.80 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.175161E+11 20117.80 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.208046E+11 20117.80 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.185923E+11 20117.80 03-APR-07:10 0.261232E+11 18128.52 03-APR-07:10
May 0.200579E+11 20117.80 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.199573E+11 20117.80 01-JUN-07:10 0.270332E+11 18128.52 01-JUN-07:10
July 0.186928E+11 20117.80 03-JUL-07:10 0.266453E+11 18128.52 03-JUL-07:10
August 0.208046E+11 20117.80 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.185923E+11 20117.80 01-SEP-07:10 0.261232E+11 18128.52 01-SEP-07:10
October 0.193111E+11 20117.80 02-OCT-07:10 0.270550E+11 18128.52 02-OCT-07:10
November 0.190822E+11 20117.80 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.186928E+11 20117.80 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.231415E+12     0.321277E+12    
Minimum of Months 0.175161E+11 20117.80   0.244880E+11 18128.52  
Maximum of Months 0.208046E+11 20117.80   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.193111E+11 20117.80 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.175161E+11 20117.80 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.208046E+11 20117.80 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.185923E+11 20117.80 03-APR-07:10 0.261232E+11 18128.52 03-APR-07:10
May 0.200579E+11 20117.80 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.199573E+11 20117.80 01-JUN-07:10 0.270332E+11 18128.52 01-JUN-07:10
July 0.186928E+11 20117.80 03-JUL-07:10 0.266453E+11 18128.52 03-JUL-07:10
August 0.208046E+11 20117.80 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.185923E+11 20117.80 01-SEP-07:10 0.261232E+11 18128.52 01-SEP-07:10
October 0.193111E+11 20117.80 02-OCT-07:10 0.270550E+11 18128.52 02-OCT-07:10
November 0.190822E+11 20117.80 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.186928E+11 20117.80 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.231415E+12     0.321277E+12    
Minimum of Months 0.175161E+11 20117.80   0.244880E+11 18128.52  
Maximum of Months 0.208046E+11 20117.80   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242470E+10 2525.99 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.219932E+10 2525.99 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.261222E+10 2525.99 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.233445E+10 2525.99 03-APR-07:10 0.328017E+10 2276.32 03-APR-07:10
May 0.251846E+10 2525.99 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.250584E+10 2525.99 01-JUN-07:10 0.339445E+10 2276.32 01-JUN-07:10
July 0.234707E+10 2525.99 03-JUL-07:10 0.334573E+10 2276.32 03-JUL-07:10
August 0.261222E+10 2525.99 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.233445E+10 2525.99 01-SEP-07:10 0.328017E+10 2276.32 01-SEP-07:10
October 0.242470E+10 2525.99 02-OCT-07:10 0.339718E+10 2276.32 02-OCT-07:10
November 0.239596E+10 2525.99 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.234707E+10 2525.99 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.290565E+11     0.403414E+11    
Minimum of Months 0.219932E+10 2525.99   0.307485E+10 2276.32  
Maximum of Months 0.261222E+10 2525.99   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.156257E+10 1627.84 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.141733E+10 1627.84 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.168342E+10 1627.84 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.150441E+10 1627.84 03-APR-07:10 0.211387E+10 1466.95 03-APR-07:10
May 0.162299E+10 1627.84 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.161486E+10 1627.84 01-JUN-07:10 0.218751E+10 1466.95 01-JUN-07:10
July 0.151254E+10 1627.84 03-JUL-07:10 0.215612E+10 1466.95 03-JUL-07:10
August 0.168342E+10 1627.84 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.150441E+10 1627.84 01-SEP-07:10 0.211387E+10 1466.95 01-SEP-07:10
October 0.156257E+10 1627.84 02-OCT-07:10 0.218927E+10 1466.95 02-OCT-07:10
November 0.154405E+10 1627.84 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.151254E+10 1627.84 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.187251E+11     0.259975E+11    
Minimum of Months 0.141733E+10 1627.84   0.198155E+10 1466.95  
Maximum of Months 0.168342E+10 1627.84   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242476E+10 2526.05 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.219937E+10 2526.05 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.261228E+10 2526.05 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.233450E+10 2526.05 03-APR-07:10 0.328022E+10 2276.35 03-APR-07:10
May 0.251852E+10 2526.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.250590E+10 2526.05 01-JUN-07:10 0.339450E+10 2276.35 01-JUN-07:10
July 0.234712E+10 2526.05 03-JUL-07:10 0.334578E+10 2276.35 03-JUL-07:10
August 0.261228E+10 2526.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.233450E+10 2526.05 01-SEP-07:10 0.328022E+10 2276.35 01-SEP-07:10
October 0.242476E+10 2526.05 02-OCT-07:10 0.339723E+10 2276.35 02-OCT-07:10
November 0.239601E+10 2526.05 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.234712E+10 2526.05 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.290571E+11     0.403420E+11    
Minimum of Months 0.219937E+10 2526.05   0.307490E+10 2276.35  
Maximum of Months 0.261228E+10 2526.05   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.156257E+10 1627.84 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.141733E+10 1627.84 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.168342E+10 1627.84 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.150441E+10 1627.84 03-APR-07:10 0.211386E+10 1466.94 03-APR-07:10
May 0.162299E+10 1627.84 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.161486E+10 1627.84 01-JUN-07:10 0.218750E+10 1466.94 01-JUN-07:10
July 0.151254E+10 1627.84 03-JUL-07:10 0.215610E+10 1466.94 03-JUL-07:10
August 0.168342E+10 1627.84 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.150441E+10 1627.84 01-SEP-07:10 0.211386E+10 1466.94 01-SEP-07:10
October 0.156257E+10 1627.84 02-OCT-07:10 0.218926E+10 1466.94 02-OCT-07:10
November 0.154405E+10 1627.84 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.151254E+10 1627.84 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.187251E+11     0.259973E+11    
Minimum of Months 0.141733E+10 1627.84   0.198154E+10 1466.94  
Maximum of Months 0.168342E+10 1627.84   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242470E+10 2525.99 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.219932E+10 2525.99 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.261222E+10 2525.99 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.233445E+10 2525.99 03-APR-07:10 0.328017E+10 2276.32 03-APR-07:10
May 0.251846E+10 2525.99 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.250584E+10 2525.99 01-JUN-07:10 0.339445E+10 2276.32 01-JUN-07:10
July 0.234707E+10 2525.99 03-JUL-07:10 0.334573E+10 2276.32 03-JUL-07:10
August 0.261222E+10 2525.99 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.233445E+10 2525.99 01-SEP-07:10 0.328017E+10 2276.32 01-SEP-07:10
October 0.242470E+10 2525.99 02-OCT-07:10 0.339718E+10 2276.32 02-OCT-07:10
November 0.239596E+10 2525.99 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.234707E+10 2525.99 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.290565E+11     0.403414E+11    
Minimum of Months 0.219932E+10 2525.99   0.307485E+10 2276.32  
Maximum of Months 0.261222E+10 2525.99   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.156257E+10 1627.84 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.141733E+10 1627.84 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.168342E+10 1627.84 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.150441E+10 1627.84 03-APR-07:10 0.211387E+10 1466.95 03-APR-07:10
May 0.162299E+10 1627.84 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.161486E+10 1627.84 01-JUN-07:10 0.218751E+10 1466.95 01-JUN-07:10
July 0.151254E+10 1627.84 03-JUL-07:10 0.215612E+10 1466.95 03-JUL-07:10
August 0.168342E+10 1627.84 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.150441E+10 1627.84 01-SEP-07:10 0.211387E+10 1466.95 01-SEP-07:10
October 0.156257E+10 1627.84 02-OCT-07:10 0.218927E+10 1466.95 02-OCT-07:10
November 0.154405E+10 1627.84 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.151254E+10 1627.84 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.187251E+11     0.259975E+11    
Minimum of Months 0.141733E+10 1627.84   0.198155E+10 1466.95  
Maximum of Months 0.168342E+10 1627.84   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242476E+10 2526.05 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.219937E+10 2526.05 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.261228E+10 2526.05 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.233450E+10 2526.05 03-APR-07:10 0.328022E+10 2276.35 03-APR-07:10
May 0.251852E+10 2526.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.250590E+10 2526.05 01-JUN-07:10 0.339450E+10 2276.35 01-JUN-07:10
July 0.234712E+10 2526.05 03-JUL-07:10 0.334578E+10 2276.35 03-JUL-07:10
August 0.261228E+10 2526.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.233450E+10 2526.05 01-SEP-07:10 0.328022E+10 2276.35 01-SEP-07:10
October 0.242476E+10 2526.05 02-OCT-07:10 0.339723E+10 2276.35 02-OCT-07:10
November 0.239601E+10 2526.05 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.234712E+10 2526.05 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.290571E+11     0.403420E+11    
Minimum of Months 0.219937E+10 2526.05   0.307490E+10 2276.35  
Maximum of Months 0.261228E+10 2526.05   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.156257E+10 1627.84 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.141733E+10 1627.84 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.168342E+10 1627.84 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.150441E+10 1627.84 03-APR-07:10 0.211386E+10 1466.94 03-APR-07:10
May 0.162299E+10 1627.84 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.161486E+10 1627.84 01-JUN-07:10 0.218750E+10 1466.94 01-JUN-07:10
July 0.151254E+10 1627.84 03-JUL-07:10 0.215610E+10 1466.94 03-JUL-07:10
August 0.168342E+10 1627.84 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.150441E+10 1627.84 01-SEP-07:10 0.211386E+10 1466.94 01-SEP-07:10
October 0.156257E+10 1627.84 02-OCT-07:10 0.218926E+10 1466.94 02-OCT-07:10
November 0.154405E+10 1627.84 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.151254E+10 1627.84 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.187251E+11     0.259973E+11    
Minimum of Months 0.141733E+10 1627.84   0.198154E+10 1466.94  
Maximum of Months 0.168342E+10 1627.84   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242470E+10 2525.99 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.219932E+10 2525.99 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.261222E+10 2525.99 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.233445E+10 2525.99 03-APR-07:10 0.328017E+10 2276.32 03-APR-07:10
May 0.251846E+10 2525.99 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.250584E+10 2525.99 01-JUN-07:10 0.339445E+10 2276.32 01-JUN-07:10
July 0.234707E+10 2525.99 03-JUL-07:10 0.334573E+10 2276.32 03-JUL-07:10
August 0.261222E+10 2525.99 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.233445E+10 2525.99 01-SEP-07:10 0.328017E+10 2276.32 01-SEP-07:10
October 0.242470E+10 2525.99 02-OCT-07:10 0.339718E+10 2276.32 02-OCT-07:10
November 0.239596E+10 2525.99 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.234707E+10 2525.99 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.290565E+11     0.403414E+11    
Minimum of Months 0.219932E+10 2525.99   0.307485E+10 2276.32  
Maximum of Months 0.261222E+10 2525.99   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.156257E+10 1627.84 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.141733E+10 1627.84 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.168342E+10 1627.84 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.150441E+10 1627.84 03-APR-07:10 0.211387E+10 1466.95 03-APR-07:10
May 0.162299E+10 1627.84 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.161486E+10 1627.84 01-JUN-07:10 0.218751E+10 1466.95 01-JUN-07:10
July 0.151254E+10 1627.84 03-JUL-07:10 0.215612E+10 1466.95 03-JUL-07:10
August 0.168342E+10 1627.84 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.150441E+10 1627.84 01-SEP-07:10 0.211387E+10 1466.95 01-SEP-07:10
October 0.156257E+10 1627.84 02-OCT-07:10 0.218927E+10 1466.95 02-OCT-07:10
November 0.154405E+10 1627.84 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.151254E+10 1627.84 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.187251E+11     0.259975E+11    
Minimum of Months 0.141733E+10 1627.84   0.198155E+10 1466.95  
Maximum of Months 0.168342E+10 1627.84   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242476E+10 2526.05 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.219937E+10 2526.05 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.261228E+10 2526.05 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.233450E+10 2526.05 03-APR-07:10 0.328022E+10 2276.35 03-APR-07:10
May 0.251852E+10 2526.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.250590E+10 2526.05 01-JUN-07:10 0.339450E+10 2276.35 01-JUN-07:10
July 0.234712E+10 2526.05 03-JUL-07:10 0.334578E+10 2276.35 03-JUL-07:10
August 0.261228E+10 2526.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.233450E+10 2526.05 01-SEP-07:10 0.328022E+10 2276.35 01-SEP-07:10
October 0.242476E+10 2526.05 02-OCT-07:10 0.339723E+10 2276.35 02-OCT-07:10
November 0.239601E+10 2526.05 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.234712E+10 2526.05 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.290571E+11     0.403420E+11    
Minimum of Months 0.219937E+10 2526.05   0.307490E+10 2276.35  
Maximum of Months 0.261228E+10 2526.05   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.156257E+10 1627.84 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.141733E+10 1627.84 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.168342E+10 1627.84 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.150441E+10 1627.84 03-APR-07:10 0.211386E+10 1466.94 03-APR-07:10
May 0.162299E+10 1627.84 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.161486E+10 1627.84 01-JUN-07:10 0.218750E+10 1466.94 01-JUN-07:10
July 0.151254E+10 1627.84 03-JUL-07:10 0.215610E+10 1466.94 03-JUL-07:10
August 0.168342E+10 1627.84 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.150441E+10 1627.84 01-SEP-07:10 0.211386E+10 1466.94 01-SEP-07:10
October 0.156257E+10 1627.84 02-OCT-07:10 0.218926E+10 1466.94 02-OCT-07:10
November 0.154405E+10 1627.84 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.151254E+10 1627.84 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.187251E+11     0.259973E+11    
Minimum of Months 0.141733E+10 1627.84   0.198154E+10 1466.94  
Maximum of Months 0.168342E+10 1627.84   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.606290E+10 6316.16 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.549934E+10 6316.16 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.653179E+10 6316.16 01-MAR-08:09 0.762606E+12 284724.39 01-MAR-00:10
April 0.583722E+10 6316.16 03-APR-07:10 0.984007E+12 379632.52 01-APR-00:10
May 0.629734E+10 6316.16 01-MAY-07:10 0.254202E+12 94908.13 01-MAY-00:10
June 0.626579E+10 6316.16 01-JUN-07:10 0.492004E+12 189816.26 01-JUN-00:10
July 0.586877E+10 6316.16 03-JUL-07:10 0.762606E+12 284724.39 01-JUL-00:10
August 0.653179E+10 6316.16 01-AUG-07:10 0.101681E+13 379632.52 01-AUG-00:10
September 0.583722E+10 6316.16 01-SEP-07:10 0.246002E+12 94908.13 01-SEP-00:10
October 0.606290E+10 6316.16 02-OCT-07:10 0.508404E+12 189816.26 01-OCT-00:10
November 0.599102E+10 6316.16 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.586877E+10 6316.16 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.726548E+11     0.749486E+13    
Minimum of Months 0.549934E+10 6316.16   0.246002E+12 94908.13  
Maximum of Months 0.653179E+10 6316.16   0.101681E+13 379632.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.280081E+09 291.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.254047E+09 291.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.301742E+09 291.78 01-MAR-08:09 0.156574E+11 5845.82 01-MAR-00:10
April 0.269655E+09 291.78 03-APR-07:10 0.202031E+11 7794.42 01-APR-00:10
May 0.290911E+09 291.78 01-MAY-07:10 0.521915E+10 1948.61 01-MAY-00:10
June 0.289453E+09 291.78 01-JUN-07:10 0.101016E+11 3897.21 01-JUN-00:10
July 0.271113E+09 291.78 03-JUL-07:10 0.156574E+11 5845.82 01-JUL-00:10
August 0.301742E+09 291.78 01-AUG-07:10 0.208766E+11 7794.42 01-AUG-00:10
September 0.269655E+09 291.78 01-SEP-07:10 0.505079E+10 1948.61 01-SEP-00:10
October 0.280081E+09 291.78 02-OCT-07:10 0.104383E+11 3897.21 01-OCT-00:10
November 0.276760E+09 291.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.271113E+09 291.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.335635E+10     0.153881E+12    
Minimum of Months 0.254047E+09 291.78   0.505079E+10 1948.61  
Maximum of Months 0.301742E+09 291.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.280081E+09 291.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.254047E+09 291.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.301742E+09 291.78 01-MAR-08:09 0.156574E+11 5845.82 01-MAR-00:10
April 0.269655E+09 291.78 03-APR-07:10 0.202031E+11 7794.42 01-APR-00:10
May 0.290911E+09 291.78 01-MAY-07:10 0.521915E+10 1948.61 01-MAY-00:10
June 0.289453E+09 291.78 01-JUN-07:10 0.101016E+11 3897.21 01-JUN-00:10
July 0.271113E+09 291.78 03-JUL-07:10 0.156574E+11 5845.82 01-JUL-00:10
August 0.301742E+09 291.78 01-AUG-07:10 0.208766E+11 7794.42 01-AUG-00:10
September 0.269655E+09 291.78 01-SEP-07:10 0.505079E+10 1948.61 01-SEP-00:10
October 0.280081E+09 291.78 02-OCT-07:10 0.104383E+11 3897.21 01-OCT-00:10
November 0.276760E+09 291.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.271113E+09 291.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.335635E+10     0.153881E+12    
Minimum of Months 0.254047E+09 291.78   0.505079E+10 1948.61  
Maximum of Months 0.301742E+09 291.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.280081E+09 291.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.254047E+09 291.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.301742E+09 291.78 01-MAR-08:09 0.156574E+11 5845.82 01-MAR-00:10
April 0.269655E+09 291.78 03-APR-07:10 0.202031E+11 7794.42 01-APR-00:10
May 0.290911E+09 291.78 01-MAY-07:10 0.521915E+10 1948.61 01-MAY-00:10
June 0.289453E+09 291.78 01-JUN-07:10 0.101016E+11 3897.21 01-JUN-00:10
July 0.271113E+09 291.78 03-JUL-07:10 0.156574E+11 5845.82 01-JUL-00:10
August 0.301742E+09 291.78 01-AUG-07:10 0.208766E+11 7794.42 01-AUG-00:10
September 0.269655E+09 291.78 01-SEP-07:10 0.505079E+10 1948.61 01-SEP-00:10
October 0.280081E+09 291.78 02-OCT-07:10 0.104383E+11 3897.21 01-OCT-00:10
November 0.276760E+09 291.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.271113E+09 291.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.335635E+10     0.153881E+12    
Minimum of Months 0.254047E+09 291.78   0.505079E+10 1948.61  
Maximum of Months 0.301742E+09 291.78   0.208766E+11 7794.42  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.215029E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.195042E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.231659E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.207025E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.223344E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.222225E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.208144E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.231659E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.207025E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.215029E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.212480E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.208144E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.257680E+12 0.424397E+12            
Minimum of Months 0.121482E+11 0.195042E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.231659E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.193111E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.175161E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.208046E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.185923E+11 0.261233E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.200579E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.199573E+11 0.270334E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.186928E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.208046E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.185923E+11 0.261233E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.193111E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.190822E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.186928E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.231415E+12 0.321278E+12            
Minimum of Months 0.109099E+11 0.175161E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.208046E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.193111E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.175161E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.208046E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.185923E+11 0.261232E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.200579E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.199573E+11 0.270332E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.186928E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.208046E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.185923E+11 0.261232E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.193111E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.190822E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.186928E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.231415E+12 0.321277E+12            
Minimum of Months 0.109099E+11 0.175161E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.208046E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.193111E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.175161E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.208046E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.185923E+11 0.261232E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.200579E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.199573E+11 0.270332E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.186928E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.208046E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.185923E+11 0.261232E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.193111E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.190822E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.186928E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.231415E+12 0.321277E+12            
Minimum of Months 0.109099E+11 0.175161E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.208046E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.242470E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.244702E+09
February 0.136985E+10 0.219932E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.342461E+09
March 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.200945E+09
April 0.145243E+10 0.233445E+10 0.328017E+10 0.00 0.00 0.00 0.00 0.00 0.247323E+09
May 0.157338E+10 0.251846E+10 0.346000E+10 0.00 0.00 0.00 0.00 4.01 0.589195E+09
June 0.156900E+10 0.250584E+10 0.339445E+10 0.00 0.00 0.00 0.00 259173.77 0.450731E+09
July 0.145680E+10 0.234707E+10 0.334573E+10 0.00 0.00 0.00 0.00 1348542.60 0.432515E+09
August 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 168087.64 0.310965E+09
September 0.145243E+10 0.233445E+10 0.328017E+10 0.00 0.00 0.00 0.00 0.00 0.331486E+09
October 0.150991E+10 0.242470E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.365874E+09
November 0.149516E+10 0.239596E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.455716E+09
December 0.145680E+10 0.234707E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.627594E+09
                   
Annual Sum or Average 0.181194E+11 0.290565E+11 0.403414E+11         1775808.02 0.459951E+10
Minimum of Months 0.136985E+10 0.219932E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.200945E+09
Maximum of Months 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 1348542.60 0.627594E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.156257E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.157688E+09
February 0.882782E+09 0.141733E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.218972E+09
March 0.105485E+10 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.127354E+09
April 0.936002E+09 0.150441E+10 0.211387E+10 0.00 0.00 0.00 0.00 35029.54 0.157271E+09
May 0.101394E+10 0.162299E+10 0.222976E+10 0.00 0.00 0.00 0.00 2.63 0.381854E+09
June 0.101113E+10 0.161486E+10 0.218751E+10 0.00 0.00 0.00 0.00 200283.39 0.286575E+09
July 0.938820E+09 0.151254E+10 0.215612E+10 0.00 0.00 0.00 0.00 1091472.83 0.269370E+09
August 0.105485E+10 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 130194.86 0.188216E+09
September 0.936002E+09 0.150441E+10 0.211387E+10 0.00 0.00 0.00 0.00 0.00 0.214059E+09
October 0.973041E+09 0.156257E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.232492E+09
November 0.963541E+09 0.154405E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.287111E+09
December 0.938820E+09 0.151254E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.393476E+09
                   
Annual Sum or Average 0.116768E+11 0.187251E+11 0.259975E+11         1456983.25 0.291444E+10
Minimum of Months 0.882782E+09 0.141733E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.127354E+09
Maximum of Months 0.105485E+10 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 1091472.83 0.393476E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.242476E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.238965E+09
February 0.136988E+10 0.219937E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.334645E+09
March 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.193991E+09
April 0.145246E+10 0.233450E+10 0.328022E+10 0.00 0.00 0.00 0.00 0.00 0.243850E+09
May 0.157341E+10 0.251852E+10 0.346006E+10 0.00 0.00 0.00 0.00 3.91 0.575596E+09
June 0.156904E+10 0.250590E+10 0.339450E+10 0.00 0.00 0.00 0.00 266243.36 0.437352E+09
July 0.145684E+10 0.234712E+10 0.334578E+10 0.00 0.00 0.00 0.00 1532528.86 0.416082E+09
August 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 168516.02 0.301766E+09
September 0.145246E+10 0.233450E+10 0.328022E+10 0.00 0.00 0.00 0.00 0.00 0.331710E+09
October 0.150994E+10 0.242476E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.360129E+09
November 0.149520E+10 0.239601E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.441122E+09
December 0.145684E+10 0.234712E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.596749E+09
                   
Annual Sum or Average 0.181198E+11 0.290571E+11 0.403420E+11         1967292.15 0.447196E+10
Minimum of Months 0.136988E+10 0.219937E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.193991E+09
Maximum of Months 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 1532528.86 0.596749E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.156257E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.164594E+09
February 0.882782E+09 0.141733E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.236428E+09
March 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.139658E+09
April 0.936002E+09 0.150441E+10 0.211386E+10 0.00 0.00 0.00 0.00 0.00 0.177160E+09
May 0.101394E+10 0.162299E+10 0.222974E+10 0.00 0.00 0.00 0.00 2.74 0.406859E+09
June 0.101113E+10 0.161486E+10 0.218750E+10 0.00 0.00 0.00 0.00 171158.95 0.319670E+09
July 0.938820E+09 0.151254E+10 0.215610E+10 0.00 0.00 0.00 0.00 735217.52 0.314421E+09
August 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 111016.45 0.227644E+09
September 0.936002E+09 0.150441E+10 0.211386E+10 0.00 0.00 0.00 0.00 0.00 0.227874E+09
October 0.973041E+09 0.156257E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.255271E+09
November 0.963541E+09 0.154405E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.320850E+09
December 0.938820E+09 0.151254E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.447137E+09
                   
Annual Sum or Average 0.116768E+11 0.187251E+11 0.259973E+11         1017395.65 0.323757E+10
Minimum of Months 0.882782E+09 0.141733E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.139658E+09
Maximum of Months 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 735217.52 0.447137E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.242470E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.496976E+09
February 0.136985E+10 0.219932E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.699329E+09
March 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.418819E+09
April 0.145243E+10 0.233445E+10 0.328017E+10 0.00 0.00 0.00 0.00 10705.12 0.517507E+09
May 0.157338E+10 0.251846E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.124932E+10
June 0.156900E+10 0.250584E+10 0.339445E+10 0.00 0.00 0.00 0.00 546274.32 0.960825E+09
July 0.145680E+10 0.234707E+10 0.334573E+10 0.00 0.00 0.00 0.00 2998576.74 0.909293E+09
August 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 357415.03 0.658393E+09
September 0.145243E+10 0.233445E+10 0.328017E+10 0.00 0.00 0.00 0.00 0.00 0.694510E+09
October 0.150991E+10 0.242470E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.749839E+09
November 0.149516E+10 0.239596E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.905663E+09
December 0.145680E+10 0.234707E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.121848E+10
                   
Annual Sum or Average 0.181194E+11 0.290565E+11 0.403414E+11         3912971.21 0.947895E+10
Minimum of Months 0.136985E+10 0.219932E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.418819E+09
Maximum of Months 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 2998576.74 0.124932E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.156257E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.328140E+09
February 0.649041E+09 0.141733E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.460950E+09
March 0.773965E+09 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.270675E+09
April 0.688021E+09 0.150441E+10 0.211387E+10 0.00 0.00 0.00 0.00 124250.57 0.347844E+09
May 0.744847E+09 0.162299E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.830768E+09
June 0.742030E+09 0.161486E+10 0.218751E+10 0.00 0.00 0.00 0.00 430795.39 0.630872E+09
July 0.690839E+09 0.151254E+10 0.215612E+10 0.00 0.00 0.00 0.00 2397770.01 0.603769E+09
August 0.773965E+09 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 297016.73 0.430290E+09
September 0.688021E+09 0.150441E+10 0.211387E+10 0.00 0.00 0.00 0.00 0.00 0.464274E+09
October 0.715730E+09 0.156257E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.489214E+09
November 0.708685E+09 0.154405E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.591675E+09
December 0.690839E+09 0.151254E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.801258E+09
                   
Annual Sum or Average 0.858171E+10 0.187251E+11 0.259975E+11         3249832.69 0.624973E+10
Minimum of Months 0.649041E+09 0.141733E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.270675E+09
Maximum of Months 0.773965E+09 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 2397770.01 0.830768E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.242476E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.524580E+09
February 0.136988E+10 0.219937E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.730134E+09
March 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.419006E+09
April 0.145246E+10 0.233450E+10 0.328022E+10 0.00 0.00 0.00 0.00 22.93 0.536213E+09
May 0.157341E+10 0.251852E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.125213E+10
June 0.156904E+10 0.250590E+10 0.339450E+10 0.00 0.00 0.00 0.00 583072.36 0.946225E+09
July 0.145684E+10 0.234712E+10 0.334578E+10 0.00 0.00 0.00 0.00 3543107.12 0.903811E+09
August 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 367518.29 0.670130E+09
September 0.145246E+10 0.233450E+10 0.328022E+10 0.00 0.00 0.00 0.00 0.00 0.731263E+09
October 0.150994E+10 0.242476E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.782118E+09
November 0.149520E+10 0.239601E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.936200E+09
December 0.145684E+10 0.234712E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.124657E+10
                   
Annual Sum or Average 0.181198E+11 0.290571E+11 0.403420E+11         4493720.70 0.967838E+10
Minimum of Months 0.136988E+10 0.219937E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.419006E+09
Maximum of Months 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 3543107.12 0.125213E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.156257E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.332308E+09
February 0.882782E+09 0.141733E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.470490E+09
March 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.274002E+09
April 0.936002E+09 0.150441E+10 0.211386E+10 0.00 0.00 0.00 0.00 478.71 0.353242E+09
May 0.101394E+10 0.162299E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.856501E+09
June 0.101113E+10 0.161486E+10 0.218750E+10 0.00 0.00 0.00 0.00 379212.31 0.661719E+09
July 0.938820E+09 0.151254E+10 0.215610E+10 0.00 0.00 0.00 0.00 2023093.93 0.638842E+09
August 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 271090.65 0.457445E+09
September 0.936002E+09 0.150441E+10 0.211386E+10 0.00 0.00 0.00 0.00 0.00 0.467572E+09
October 0.973041E+09 0.156257E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.500448E+09
November 0.963541E+09 0.154405E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.602672E+09
December 0.938820E+09 0.151254E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.817088E+09
                   
Annual Sum or Average 0.116768E+11 0.187251E+11 0.259973E+11         2673875.60 0.643233E+10
Minimum of Months 0.882782E+09 0.141733E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.274002E+09
Maximum of Months 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 2023093.93 0.856501E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.242470E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.536574E+09
February 0.136985E+10 0.219932E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.768758E+09
March 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.472145E+09
April 0.145243E+10 0.233445E+10 0.328017E+10 0.00 0.00 0.00 0.00 502.81 0.600150E+09
May 0.157338E+10 0.251846E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.146434E+10
June 0.156900E+10 0.250584E+10 0.339445E+10 0.00 0.00 0.00 0.00 629421.39 0.114937E+10
July 0.145680E+10 0.234707E+10 0.334573E+10 0.00 0.00 0.00 0.00 3499113.91 0.108851E+10
August 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 416477.40 0.785336E+09
September 0.145243E+10 0.233445E+10 0.328017E+10 0.00 0.00 0.00 0.00 0.00 0.799096E+09
October 0.150991E+10 0.242470E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.828598E+09
November 0.149516E+10 0.239596E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.992095E+09
December 0.145680E+10 0.234707E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.133652E+10
                   
Annual Sum or Average 0.181194E+11 0.290565E+11 0.403414E+11         4545515.51 0.108215E+11
Minimum of Months 0.136985E+10 0.219932E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.472145E+09
Maximum of Months 0.163685E+10 0.261222E+10 0.352283E+10 0.00 0.00 0.00 0.00 3499113.91 0.146434E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.156257E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.357979E+09
February 0.882782E+09 0.141733E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.514819E+09
March 0.105485E+10 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.311121E+09
April 0.936002E+09 0.150441E+10 0.211387E+10 0.00 0.00 0.00 0.00 57472.76 0.409384E+09
May 0.101394E+10 0.162299E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.986845E+09
June 0.101113E+10 0.161486E+10 0.218751E+10 0.00 0.00 0.00 0.00 448778.16 0.762974E+09
July 0.938820E+09 0.151254E+10 0.215612E+10 0.00 0.00 0.00 0.00 2684705.35 0.735444E+09
August 0.105485E+10 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 310963.01 0.523791E+09
September 0.936002E+09 0.150441E+10 0.211387E+10 0.00 0.00 0.00 0.00 0.00 0.549032E+09
October 0.973041E+09 0.156257E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.552153E+09
November 0.963541E+09 0.154405E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.659673E+09
December 0.938820E+09 0.151254E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.888573E+09
                   
Annual Sum or Average 0.116768E+11 0.187251E+11 0.259975E+11         3501919.27 0.725179E+10
Minimum of Months 0.882782E+09 0.141733E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.311121E+09
Maximum of Months 0.105485E+10 0.168342E+10 0.227025E+10 0.00 0.00 0.00 0.00 2684705.35 0.986845E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.242476E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.568447E+09
February 0.136988E+10 0.219937E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.816047E+09
March 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.478657E+09
April 0.145246E+10 0.233450E+10 0.328022E+10 0.00 0.00 0.00 0.00 0.00 0.628093E+09
May 0.157341E+10 0.251852E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.147424E+10
June 0.156904E+10 0.250590E+10 0.339450E+10 0.00 0.00 0.00 0.00 654165.49 0.113234E+10
July 0.145684E+10 0.234712E+10 0.334578E+10 0.00 0.00 0.00 0.00 4267645.55 0.108572E+10
August 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 424671.43 0.802870E+09
September 0.145246E+10 0.233450E+10 0.328022E+10 0.00 0.00 0.00 0.00 0.00 0.856583E+09
October 0.150994E+10 0.242476E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.885016E+09
November 0.149520E+10 0.239601E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.103991E+10
December 0.145684E+10 0.234712E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.137558E+10
                   
Annual Sum or Average 0.181198E+11 0.290571E+11 0.403420E+11         5346482.47 0.111435E+11
Minimum of Months 0.136988E+10 0.219937E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.478657E+09
Maximum of Months 0.163688E+10 0.261228E+10 0.352288E+10 0.00 0.00 0.00 0.00 4267645.55 0.147424E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.156257E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.369441E+09
February 0.882782E+09 0.141733E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.536035E+09
March 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.317927E+09
April 0.936002E+09 0.150441E+10 0.211386E+10 0.00 0.00 0.00 0.00 0.00 0.416313E+09
May 0.101394E+10 0.162299E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.101826E+10
June 0.101113E+10 0.161486E+10 0.218750E+10 0.00 0.00 0.00 0.00 442740.64 0.795959E+09
July 0.938820E+09 0.151254E+10 0.215610E+10 0.00 0.00 0.00 0.00 2452093.11 0.771160E+09
August 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 294768.40 0.550046E+09
September 0.936002E+09 0.150441E+10 0.211386E+10 0.00 0.00 0.00 0.00 0.00 0.551040E+09
October 0.973041E+09 0.156257E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.573283E+09
November 0.963541E+09 0.154405E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.684370E+09
December 0.938820E+09 0.151254E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.924105E+09
                   
Annual Sum or Average 0.116768E+11 0.187251E+11 0.259973E+11         3189602.16 0.750794E+10
Minimum of Months 0.882782E+09 0.141733E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.317927E+09
Maximum of Months 0.105485E+10 0.168342E+10 0.227023E+10 0.00 0.00 0.00 0.00 2452093.11 0.101826E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.606290E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.549934E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.653179E+10 0.762606E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.583722E+10 0.984007E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.629734E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.626579E+10 0.492004E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.586877E+10 0.762606E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.653179E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.583722E+10 0.246002E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.606290E+10 0.508404E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.599102E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.586877E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.726548E+11 0.749486E+13            
Minimum of Months 0.00 0.549934E+10 0.246002E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.653179E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.280081E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.254047E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.301742E+09 0.156574E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.269655E+09 0.202031E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.290911E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.289453E+09 0.101016E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.271113E+09 0.156574E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.301742E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.269655E+09 0.505079E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.280081E+09 0.104383E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.276760E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.271113E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.335635E+10 0.153881E+12            
Minimum of Months 0.00 0.254047E+09 0.505079E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.301742E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.280081E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.254047E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.301742E+09 0.156574E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.269655E+09 0.202031E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.290911E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.289453E+09 0.101016E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.271113E+09 0.156574E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.301742E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.269655E+09 0.505079E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.280081E+09 0.104383E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.276760E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.271113E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.335635E+10 0.153881E+12            
Minimum of Months 0.00 0.254047E+09 0.505079E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.301742E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.280081E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.254047E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.301742E+09 0.156574E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.269655E+09 0.202031E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.290911E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.289453E+09 0.101016E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.271113E+09 0.156574E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.301742E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.269655E+09 0.505079E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.280081E+09 0.104383E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.276760E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.271113E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.335635E+10 0.153881E+12            
Minimum of Months 0.00 0.254047E+09 0.505079E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.301742E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.495421E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.691360E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.400016E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.495256E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118273E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 264342.17 0.899611E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2074045.57 0.866245E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 187209.14 0.633953E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.675017E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.738451E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.923784E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.126640E+10
                   
Annual Sum or Average               2525596.89 0.926824E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.400016E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2074045.57 0.126640E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.852493E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.119616E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.693158E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.861726E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.207659E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 503211.64 0.157609E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4001313.53 0.150251E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 376244.82 0.110293E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118046E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.127862E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157625E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.212603E+10
                   
Annual Sum or Average               4880769.99 0.160230E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.693158E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4001313.53 0.212603E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.816104E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118334E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.726271E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.950682E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.227840E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63754.36 0.178085E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2201264.54 0.170963E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133715.90 0.122917E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.125365E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.128580E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.152903E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.203896E+10
                   
Annual Sum or Average               2398734.80 0.167819E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.726271E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2201264.54 0.227840E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 22401.15 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 22401.15 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 22401.15 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 22401.15 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 22401.15 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 22401.15 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 22401.15 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 22401.15 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 22401.15 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 22401.15 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 22401.15 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 22401.15 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 17832.21   22401.15   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   22401.15   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20117.80 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20117.80 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20117.80 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20117.80 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20117.80 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20117.80 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20117.80 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20117.80 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20117.80 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20117.80 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20117.80 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20117.80 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 16014.58   20117.80   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20117.80   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20117.80 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20117.80 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20117.80 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20117.80 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20117.80 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20117.80 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20117.80 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20117.80 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20117.80 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20117.80 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20117.80 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20117.80 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 16014.58   20117.80   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20117.80   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 20117.80 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 20117.80 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 20117.80 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 20117.80 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 20117.80 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 20117.80 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 20117.80 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 20117.80 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 20117.80 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 20117.80 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 20117.80 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 20117.80 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 16014.58   20117.80   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   20117.80   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2525.99 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 810.95 08-JAN-08:00
February 2010.79 01-FEB-10:09 2525.99 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 724.72 08-FEB-22:10
March 2010.79 01-MAR-10:09 2525.99 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 749.31 27-MAR-22:00
April 2010.79 03-APR-09:09 2525.99 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 814.22 23-APR-21:51
May 2010.79 01-MAY-09:09 2525.99 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.01 22-MAY-15:00 1170.41 04-MAY-23:00
June 2010.79 01-JUN-09:09 2525.99 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 18.82 13-JUN-15:30 800.51 05-JUN-22:00
July 2010.79 03-JUL-09:09 2525.99 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 76.78 22-JUL-19:10 723.87 30-JUL-18:40
August 2010.79 01-AUG-09:09 2525.99 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 14.26 14-AUG-16:50 545.79 22-AUG-21:10
September 2010.79 01-SEP-09:09 2525.99 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 722.16 06-SEP-04:00
October 2010.79 02-OCT-09:09 2525.99 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 923.23 20-OCT-22:00
November 2010.79 01-NOV-09:09 2525.99 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 976.93 25-NOV-05:00
December 2010.79 01-DEC-10:09 2525.99 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1435.07 02-DEC-18:10
                             
Annual Sum or Average                            
Minimum of Months 2010.79   2525.99   2276.32   0.00 0.00 0.00 0.00 0.00   545.79  
Maximum of Months 2010.79   2525.99   2276.32   0.00 0.00 0.00 0.00 76.78   1435.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1627.84 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 527.34 08-JAN-08:00
February 1295.83 01-FEB-10:09 1627.84 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 455.21 14-FEB-23:00
March 1295.83 01-MAR-10:09 1627.84 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 473.41 27-MAR-22:00
April 1295.83 03-APR-09:09 1627.84 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 9.15 30-APR-18:50 516.89 23-APR-21:51
May 1295.83 01-MAY-09:09 1627.84 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 22-MAY-15:00 749.04 04-MAY-23:00
June 1295.83 01-JUN-09:09 1627.84 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 12.43 13-JUN-15:30 557.25 18-JUN-11:00
July 1295.83 03-JUL-09:09 1627.84 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 75.44 22-JUL-19:10 461.86 11-JUL-02:00
August 1295.83 01-AUG-09:09 1627.84 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 11.25 14-AUG-18:00 322.99 18-AUG-03:00
September 1295.83 01-SEP-09:09 1627.84 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 463.92 06-SEP-04:00
October 1295.83 02-OCT-09:09 1627.84 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 575.89 20-OCT-22:00
November 1295.83 01-NOV-09:09 1627.84 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 608.53 25-NOV-05:00
December 1295.83 01-DEC-10:09 1627.84 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 881.50 02-DEC-18:10
                             
Annual Sum or Average                            
Minimum of Months 1295.83   1627.84   1466.95   0.00 0.00 0.00 0.00 0.00   322.99  
Maximum of Months 1295.83   1627.84   1466.95   0.00 0.00 0.00 0.00 75.44   881.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2526.05 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 781.01 08-JAN-08:00
February 2010.83 01-FEB-10:09 2526.05 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 704.69 05-FEB-13:53
March 2010.83 01-MAR-10:09 2526.05 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 716.80 27-MAR-22:00
April 2010.83 03-APR-09:09 2526.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 777.57 23-APR-21:51
May 2010.83 01-MAY-09:09 2526.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.01 22-MAY-15:00 1138.30 04-MAY-23:00
June 2010.83 01-JUN-09:09 2526.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 18.82 13-JUN-15:30 784.44 05-JUN-22:00
July 2010.83 03-JUL-09:09 2526.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 100.17 22-JUL-19:10 715.81 30-JUL-18:40
August 2010.83 01-AUG-09:09 2526.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 14.26 14-AUG-16:50 529.96 22-AUG-21:10
September 2010.83 01-SEP-09:09 2526.05 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 698.50 06-SEP-04:00
October 2010.83 02-OCT-09:09 2526.05 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 897.97 20-OCT-22:00
November 2010.83 01-NOV-09:09 2526.05 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 912.48 25-NOV-05:00
December 2010.83 01-DEC-10:09 2526.05 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1363.44 02-DEC-18:10
                             
Annual Sum or Average                            
Minimum of Months 2010.83   2526.05   2276.35   0.00 0.00 0.00 0.00 0.00   529.96  
Maximum of Months 2010.83   2526.05   2276.35   0.00 0.00 0.00 0.00 100.17   1363.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1627.84 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 555.36 08-JAN-08:00
February 1295.83 01-FEB-10:09 1627.84 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 502.43 14-FEB-23:00
March 1295.83 01-MAR-10:09 1627.84 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 528.25 27-MAR-22:00
April 1295.83 03-APR-09:09 1627.84 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 602.05 23-APR-21:51
May 1295.83 01-MAY-09:09 1627.84 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 22-MAY-15:00 803.44 04-MAY-23:00
June 1295.83 01-JUN-09:09 1627.84 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 12.43 13-JUN-15:30 601.12 18-JUN-16:00
July 1295.83 03-JUL-09:09 1627.84 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 45.33 22-JUL-19:10 623.17 30-JUL-18:40
August 1295.83 01-AUG-09:09 1627.84 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 9.42 14-AUG-16:50 411.08 18-AUG-03:00
September 1295.83 01-SEP-09:09 1627.84 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 492.20 06-SEP-04:00
October 1295.83 02-OCT-09:09 1627.84 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 652.76 20-OCT-22:00
November 1295.83 01-NOV-09:09 1627.84 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 695.76 25-NOV-05:00
December 1295.83 01-DEC-10:09 1627.84 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1011.48 02-DEC-18:10
                             
Annual Sum or Average                            
Minimum of Months 1295.83   1627.84   1466.94   0.00 0.00 0.00 0.00 0.00   411.08  
Maximum of Months 1295.83   1627.84   1466.94   0.00 0.00 0.00 0.00 45.33   1011.48  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2525.99 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1612.52 08-JAN-08:00
February 2010.79 01-FEB-10:09 2525.99 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1516.75 08-FEB-22:10
March 2010.79 01-MAR-10:09 2525.99 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1530.38 27-MAR-21:13
April 2010.79 03-APR-09:09 2525.99 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 5.84 30-APR-18:50 1574.33 23-APR-21:51
May 2010.79 01-MAY-09:09 2525.99 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 2425.03 04-MAY-23:00
June 2010.79 01-JUN-09:09 2525.99 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 40.47 13-JUN-15:40 1689.46 05-JUN-21:13
July 2010.79 03-JUL-09:09 2525.99 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 176.79 22-JUL-19:10 1470.45 11-JUL-02:00
August 2010.79 01-AUG-09:09 2525.99 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 30.95 14-AUG-16:50 1131.49 22-AUG-21:10
September 2010.79 01-SEP-09:09 2525.99 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1477.26 06-SEP-04:00
October 2010.79 02-OCT-09:09 2525.99 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1864.36 20-OCT-22:00
November 2010.79 01-NOV-09:09 2525.99 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1872.59 25-NOV-05:00
December 2010.79 01-DEC-10:09 2525.99 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2839.17 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 2010.79   2525.99   2276.32   0.00 0.00 0.00 0.00 0.00   1131.49  
Maximum of Months 2010.79   2525.99   2276.32   0.00 0.00 0.00 0.00 176.79   2839.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1627.84 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1072.35 08-JAN-08:00
February 1239.33 01-FEB-08:09 1627.84 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 971.02 08-FEB-22:03
March 1239.33 01-MAR-08:09 1627.84 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 978.90 27-MAR-21:20
April 1239.33 03-APR-07:10 1627.84 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 27.69 30-APR-18:50 1049.35 23-APR-21:51
May 1239.33 01-MAY-07:10 1627.84 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 1551.17 04-MAY-23:00
June 1239.33 01-JUN-07:10 1627.84 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 26.98 13-JUN-15:40 1240.53 18-JUN-11:00
July 1239.33 03-JUL-07:10 1627.84 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 175.27 22-JUL-19:10 974.89 11-JUL-02:00
August 1239.33 01-AUG-07:10 1627.84 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 26.38 14-AUG-18:00 695.84 22-AUG-01:55
September 1239.33 01-SEP-07:10 1627.84 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 984.10 06-SEP-04:00
October 1239.33 02-OCT-07:10 1627.84 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1172.98 20-OCT-22:00
November 1239.33 01-NOV-07:10 1627.84 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1206.31 25-NOV-05:00
December 1239.33 01-DEC-08:09 1627.84 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1815.51 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 1239.33   1627.84   1466.95   0.00 0.00 0.00 0.00 0.00   695.84  
Maximum of Months 1239.33   1627.84   1466.95   0.00 0.00 0.00 0.00 175.27   1815.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2526.05 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1700.95 01-JAN-14:51
February 2010.83 01-FEB-10:09 2526.05 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1584.93 05-FEB-14:00
March 2010.83 01-MAR-10:09 2526.05 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1484.59 27-MAR-22:00
April 2010.83 03-APR-09:09 2526.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.19 30-APR-18:50 1593.48 16-APR-12:00
May 2010.83 01-MAY-09:09 2526.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 2370.71 04-MAY-23:00
June 2010.83 01-JUN-09:09 2526.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 40.47 13-JUN-15:40 1719.75 18-JUN-15:52
July 2010.83 03-JUL-09:09 2526.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 233.76 22-JUL-19:10 1551.36 30-JUL-19:00
August 2010.83 01-AUG-09:09 2526.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 31.80 14-AUG-18:00 1106.81 22-AUG-21:10
September 2010.83 01-SEP-09:09 2526.05 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1493.09 06-SEP-04:00
October 2010.83 02-OCT-09:09 2526.05 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1853.01 01-OCT-24:00
November 2010.83 01-NOV-09:09 2526.05 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1832.38 25-NOV-05:00
December 2010.83 01-DEC-10:09 2526.05 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2808.73 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 2010.83   2526.05   2276.35   0.00 0.00 0.00 0.00 0.00   1106.81  
Maximum of Months 2010.83   2526.05   2276.35   0.00 0.00 0.00 0.00 233.76   2808.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1627.84 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1089.63 08-JAN-08:00
February 1295.83 01-FEB-10:09 1627.84 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 990.83 08-FEB-22:10
March 1295.83 01-MAR-10:09 1627.84 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 994.82 27-MAR-22:00
April 1295.83 03-APR-09:09 1627.84 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 2.79 30-APR-13:30 1068.71 23-APR-21:51
May 1295.83 01-MAY-09:09 1627.84 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 1591.71 04-MAY-23:00
June 1295.83 01-JUN-09:09 1627.84 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 26.98 13-JUN-15:40 1299.63 18-JUN-16:00
July 1295.83 03-JUL-09:09 1627.84 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 95.10 22-JUL-19:10 1318.26 30-JUL-19:00
August 1295.83 01-AUG-09:09 1627.84 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 30.42 20-AUG-13:00 779.86 22-AUG-21:10
September 1295.83 01-SEP-09:09 1627.84 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 988.90 06-SEP-04:00
October 1295.83 02-OCT-09:09 1627.84 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1222.10 20-OCT-22:00
November 1295.83 01-NOV-09:09 1627.84 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1234.76 25-NOV-05:00
December 1295.83 01-DEC-10:09 1627.84 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1852.63 02-DEC-18:10
                             
Annual Sum or Average                            
Minimum of Months 1295.83   1627.84   1466.94   0.00 0.00 0.00 0.00 0.00   779.86  
Maximum of Months 1295.83   1627.84   1466.94   0.00 0.00 0.00 0.00 95.10   1852.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2525.99 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1663.01 10-JAN-05:52
February 2010.79 01-FEB-10:09 2525.99 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1805.67 08-FEB-22:03
March 2010.79 01-MAR-10:09 2525.99 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1793.21 27-MAR-21:03
April 2010.79 03-APR-09:09 2525.99 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 1.94 30-APR-19:00 1714.30 23-APR-21:51
May 2010.79 01-MAY-09:09 2525.99 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 2795.83 04-MAY-23:00
June 2010.79 01-JUN-09:09 2525.99 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 47.78 13-JUN-15:50 2036.20 05-JUN-21:10
July 2010.79 03-JUL-09:09 2525.99 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 199.92 22-JUL-19:10 1789.26 30-JUL-19:00
August 2010.79 01-AUG-09:09 2525.99 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 36.89 14-AUG-16:50 1349.96 22-AUG-21:10
September 2010.79 01-SEP-09:09 2525.99 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1643.60 06-SEP-04:00
October 2010.79 02-OCT-09:09 2525.99 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2101.28 20-OCT-22:00
November 2010.79 01-NOV-09:09 2525.99 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2131.00 25-NOV-05:10
December 2010.79 01-DEC-10:09 2525.99 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3266.72 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 2010.79   2525.99   2276.32   0.00 0.00 0.00 0.00 0.00   1349.96  
Maximum of Months 2010.79   2525.99   2276.32   0.00 0.00 0.00 0.00 199.92   3266.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1627.84 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1108.19 10-JAN-05:52
February 1295.83 01-FEB-10:09 1627.84 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1200.30 08-FEB-22:03
March 1295.83 01-MAR-10:09 1627.84 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1193.14 27-MAR-21:03
April 1295.83 03-APR-09:09 1627.84 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 22.81 30-APR-18:40 1144.60 23-APR-21:51
May 1295.83 01-MAY-09:09 1627.84 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 1804.52 04-MAY-23:00
June 1295.83 01-JUN-09:09 1627.84 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 31.86 13-JUN-15:50 1468.67 18-JUN-11:00
July 1295.83 03-JUL-09:09 1627.84 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 194.47 22-JUL-19:10 1209.67 30-JUL-19:00
August 1295.83 01-AUG-09:09 1627.84 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 28.84 14-AUG-18:00 821.78 22-AUG-21:10
September 1295.83 01-SEP-09:09 1627.84 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1101.74 06-SEP-04:00
October 1295.83 02-OCT-09:09 1627.84 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1362.44 20-OCT-22:00
November 1295.83 01-NOV-09:09 1627.84 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1438.88 25-NOV-05:05
December 1295.83 01-DEC-10:09 1627.84 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2120.75 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 1295.83   1627.84   1466.95   0.00 0.00 0.00 0.00 0.00   821.78  
Maximum of Months 1295.83   1627.84   1466.95   0.00 0.00 0.00 0.00 194.47   2120.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2526.05 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1726.33 08-JAN-08:00
February 2010.83 01-FEB-10:09 2526.05 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1808.87 08-FEB-22:03
March 2010.83 01-MAR-10:09 2526.05 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1791.26 27-MAR-21:03
April 2010.83 03-APR-09:09 2526.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1799.01 16-APR-12:00
May 2010.83 01-MAY-09:09 2526.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 2733.52 04-MAY-23:00
June 2010.83 01-JUN-09:09 2526.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 47.78 13-JUN-15:50 2115.02 18-JUN-15:52
July 2010.83 03-JUL-09:09 2526.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 273.66 22-JUL-19:10 1908.30 30-JUL-19:00
August 2010.83 01-AUG-09:09 2526.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 37.15 14-AUG-18:00 1322.01 22-AUG-21:10
September 2010.83 01-SEP-09:09 2526.05 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1667.30 06-SEP-04:00
October 2010.83 02-OCT-09:09 2526.05 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2116.46 20-OCT-22:00
November 2010.83 01-NOV-09:09 2526.05 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2158.86 25-NOV-05:05
December 2010.83 01-DEC-10:09 2526.05 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3257.81 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 2010.83   2526.05   2276.35   0.00 0.00 0.00 0.00 0.00   1322.01  
Maximum of Months 2010.83   2526.05   2276.35   0.00 0.00 0.00 0.00 273.66   3257.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1627.84 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1158.25 08-JAN-08:00
February 1295.83 01-FEB-10:09 1627.84 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1207.52 08-FEB-22:03
March 1295.83 01-MAR-10:09 1627.84 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1198.14 27-MAR-21:03
April 1295.83 03-APR-09:09 1627.84 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1189.83 23-APR-21:51
May 1295.83 01-MAY-09:09 1627.84 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 1848.07 04-MAY-23:00
June 1295.83 01-JUN-09:09 1627.84 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 31.86 13-JUN-15:40 1618.61 18-JUN-16:20
July 1295.83 03-JUL-09:09 1627.84 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 117.20 22-JUL-19:10 1622.90 30-JUL-19:00
August 1295.83 01-AUG-09:09 1627.84 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 24.60 14-AUG-16:50 934.19 22-AUG-21:10
September 1295.83 01-SEP-09:09 1627.84 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1112.79 06-SEP-04:00
October 1295.83 02-OCT-09:09 1627.84 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1418.66 20-OCT-22:00
November 1295.83 01-NOV-09:09 1627.84 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1420.68 25-NOV-05:08
December 1295.83 01-DEC-10:09 1627.84 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2181.36 02-DEC-18:03
                             
Annual Sum or Average                            
Minimum of Months 1295.83   1627.84   1466.94   0.00 0.00 0.00 0.00 0.00   934.19  
Maximum of Months 1295.83   1627.84   1466.94   0.00 0.00 0.00 0.00 117.20   2181.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 6316.16 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 6316.16 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 6316.16 01-MAR-08:09 284724.39 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 6316.16 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 6316.16 01-MAY-07:10 94908.13 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 6316.16 01-JUN-07:10 189816.26 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 6316.16 03-JUL-07:10 284724.39 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 6316.16 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 6316.16 01-SEP-07:10 94908.13 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 6316.16 02-OCT-07:10 189816.26 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 6316.16 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 6316.16 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 6316.16   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 6316.16   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 291.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 291.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 291.78 01-MAR-08:09 5845.82 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 291.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 291.78 01-MAY-07:10 1948.61 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 291.78 01-JUN-07:10 3897.21 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 291.78 03-JUL-07:10 5845.82 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 291.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 291.78 01-SEP-07:10 1948.61 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 291.78 02-OCT-07:10 3897.21 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 291.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 291.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 291.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 291.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 291.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 291.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 291.78 01-MAR-08:09 5845.82 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 291.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 291.78 01-MAY-07:10 1948.61 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 291.78 01-JUN-07:10 3897.21 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 291.78 03-JUL-07:10 5845.82 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 291.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 291.78 01-SEP-07:10 1948.61 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 291.78 02-OCT-07:10 3897.21 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 291.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 291.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 291.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 291.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 291.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 291.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 291.78 01-MAR-08:09 5845.82 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 291.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 291.78 01-MAY-07:10 1948.61 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 291.78 01-JUN-07:10 3897.21 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 291.78 03-JUL-07:10 5845.82 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 291.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 291.78 01-SEP-07:10 1948.61 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 291.78 02-OCT-07:10 3897.21 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 291.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 291.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 291.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 291.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1677.15 08-JAN-08:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1480.00 08-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1498.34 27-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1620.95 23-APR-21:51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 2396.34 04-MAY-23:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.03 13-JUN-16:00 1596.88 05-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.58 22-JUL-18:52 1462.03 30-JUL-18:51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.47 14-AUG-17:00 1084.61 22-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1484.92 06-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1855.04 20-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2008.19 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2962.53 02-DEC-18:10
                       
Annual Sum or Average                      
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1084.61  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.58   2962.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2896.60 08-JAN-08:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2587.20 08-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2569.16 27-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2747.92 23-APR-21:51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 4201.54 04-MAY-23:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.21 13-JUN-16:00 2788.24 05-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.54 22-JUL-18:52 2446.11 30-JUL-19:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37.68 14-AUG-18:00 1895.40 22-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2583.98 06-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3205.14 20-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3376.56 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5009.41 02-DEC-18:03
                       
Annual Sum or Average                      
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1895.40  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.54   5009.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2528.83 08-JAN-08:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2761.92 08-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2721.83 27-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2685.97 23-APR-21:51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 4355.43 04-MAY-23:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.67 13-JUN-17:00 3500.13 18-JUN-15:52
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 213.46 22-JUL-18:52 3017.82 30-JUL-18:51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.61 14-AUG-18:00 2025.11 22-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2493.08 06-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3229.65 20-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3194.80 25-NOV-05:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5219.16 02-DEC-18:03
                       
Annual Sum or Average                      
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2025.11  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 213.46   5219.16  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 123752.79 01-JAN-07:02 5385.68 7467.05 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
February 118201.91 20-FEB-22:31 0.00 13462.87 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
March 122014.43 21-MAR-03:50 0.00 4038.86 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
April 125028.43 30-APR-22:08 0.00 5385.15 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
May 125865.24 29-MAY-14:18 3590.45 4978.03 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 125118.97 11-JUN-22:23 0.00 4038.86 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
July 125977.17 04-JUL-20:20 0.00 4038.86 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
August 124687.77 20-AUG-23:08 0.00 5385.15 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
September 126409.28 04-SEP-07:30 2692.84 3733.52 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
October 122369.93 09-OCT-20:52 0.00 6731.44 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 122119.09 12-NOV-21:22 0.00 6731.44 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
December 122342.25 05-DEC-04:50 0.00 4038.86 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 118201.91   0.00 3733.52 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 126409.28   5385.68 13462.87 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 78383.32 02-JAN-04:01 0.00 9672.49 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
February 72968.82 13-FEB-04:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
March 75231.91 06-MAR-04:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
April 77483.57 25-APR-03:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
May 77394.35 30-MAY-03:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
June 86197.25 13-JUN-03:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
July 84155.66 19-JUL-03:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
August 84128.41 22-AUG-03:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
September 81615.86 01-SEP-03:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
October 77410.32 10-OCT-02:61 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
November 77093.73 15-NOV-04:02 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
December 78447.93 26-DEC-04:01 0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 72968.82   0.00 9672.49 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86197.25   0.00 12090.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 63314.24 26-JAN-06:01 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
February 62337.50 10-FEB-06:01 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
March 64041.43 30-MAR-05:01 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
April 65661.75 24-APR-04:02 0.00 24181.22 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
May 64699.55 31-MAY-05:01 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
June 71751.47 13-JUN-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
July 75325.51 22-JUL-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
August 72197.67 09-AUG-05:01 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
September 68372.77 16-SEP-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
October 66829.79 10-OCT-04:02 0.00 24181.22 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
November 64226.08 09-NOV-06:01 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
December 60709.09 22-DEC-06:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 60709.09   0.00 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 75325.51   16122.38 24181.22 80571.20 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 30904.71 19-JAN-16:30 15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 30377.47 09-FEB-16:50 15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 34617.97 31-MAR-16:00 15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
April 57113.86 21-APR-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
May 57579.34 23-MAY-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
June 69152.38 13-JUN-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
July 70655.31 22-JUL-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
August 68780.31 15-AUG-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
September 63495.33 01-SEP-05:02 16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00
October 38862.39 05-OCT-16:00 15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
November 33246.49 10-NOV-16:20 15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
December 24670.23 21-DEC-17:00 15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 24670.23   15316.26 20117.80 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 70655.31   16122.38 22353.12 80571.20 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4479.76 17-JAN-13:40 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 56.69
February 4875.16 21-FEB-14:10 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 43.01
March 6157.15 20-MAR-12:40 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 82.95
April 7864.62 18-APR-05:01 2024.33 2806.66 10116.97 0.00 0.00 0.00 0.00 0.00 0.00
May 7476.86 22-MAY-15:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.01 0.00
June 9084.83 26-JUN-05:03 809.73 1122.66 4046.79 0.00 0.00 0.00 0.00 0.00 78.38
July 9205.85 10-JUL-05:03 809.73 1122.66 4046.79 0.00 0.00 0.00 0.00 0.00 45.70
August 8970.83 15-AUG-05:01 2024.33 2806.66 10116.97 0.00 0.00 0.00 0.00 0.00 6.47
September 8363.49 02-SEP-05:01 2024.33 2806.66 10116.97 0.00 0.00 0.00 0.00 0.00 0.00
October 8499.72 10-OCT-05:03 809.73 1122.66 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
November 5072.29 13-NOV-11:40 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 68.92
December 4133.35 21-DEC-14:30 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 73.42
                       
Annual Sum or Average                      
Minimum of Months 4133.35   809.73 1122.66 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9205.85   2024.33 2806.66 10116.97 0.00 0.00 0.00 0.00 0.01 82.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3870.19 20-JAN-09:55 2478.65 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
February 5206.59 17-FEB-09:45 2478.65 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
March 4436.13 31-MAR-09:30 1295.83 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 83.75
April 12134.36 30-APR-08:43 260.91 361.74 1955.93 0.00 0.00 0.00 0.00 0.00 164.54
May 16292.71 21-MAY-07:32 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 161.58
June 12491.64 25-JUN-07:12 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 29.35
July 18075.63 16-JUL-07:52 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 118.90
August 18263.46 20-AUG-08:52 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 133.31
September 16817.52 04-SEP-09:02 260.91 361.74 1955.93 0.00 0.00 0.00 0.00 0.00 139.11
October 7479.20 03-OCT-09:00 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 39.72
November 4837.53 13-NOV-09:30 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 42.39
December 3344.90 26-DEC-09:45 2478.65 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 59.84
                       
Annual Sum or Average                      
Minimum of Months 3344.90   260.91 361.74 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18263.46   2478.65 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 164.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14593.14 20-JAN-12:00 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
February 19586.60 19-FEB-13:53 404.87 561.34 3035.14 0.00 0.00 0.00 0.00 0.00 0.00
March 11286.91 28-MAR-12:10 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 101.02
April 19999.47 30-APR-12:43 404.87 561.34 3035.14 0.00 0.00 0.00 0.00 0.00 92.27
May 11911.46 22-MAY-12:50 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 9.40
June 11084.74 26-JUN-12:50 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 18.37
July 13478.63 31-JUL-12:40 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 44.59
August 18006.64 20-AUG-13:42 506.09 701.68 3793.92 0.00 0.00 0.00 0.00 0.00 87.52
September 24635.21 24-SEP-14:02 506.09 701.68 3793.92 0.00 0.00 0.00 0.00 0.00 129.39
October 20584.09 01-OCT-13:32 404.87 561.34 3035.14 0.00 0.00 0.00 0.00 0.00 280.91
November 14757.05 03-NOV-12:40 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 131.71
December 14776.99 18-DEC-13:20 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 63.57
                       
Annual Sum or Average                      
Minimum of Months 11084.74   404.87 561.34 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24635.21   1923.15 2526.05 3793.92 0.00 0.00 0.00 0.00 0.00 280.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6892.65 30-JAN-16:40 2478.65 3255.69 2933.87 0.00 0.00 0.00 0.00 0.00 0.00
February 14684.75 20-FEB-15:01 652.28 904.36 4889.79 0.00 0.00 0.00 0.00 0.00 193.99
March 12232.65 24-MAR-03:01 0.00 978.32 6519.72 0.00 0.00 0.00 0.00 0.00 0.00
April 23789.16 30-APR-16:42 391.37 542.61 2933.87 0.00 0.00 0.00 0.00 0.00 21.01
May 20029.63 28-MAY-16:12 326.14 452.18 2444.89 0.00 0.00 0.00 0.00 0.00 441.51
June 25486.48 25-JUN-17:21 0.00 684.82 3422.85 0.00 0.00 0.00 0.00 0.00 35.68
July 25707.42 09-JUL-18:21 0.00 684.82 3422.85 0.00 0.00 0.00 0.00 0.00 87.74
August 23856.00 20-AUG-16:22 391.37 542.61 2933.87 0.00 0.00 0.00 0.00 0.00 51.07
September 17068.35 01-SEP-03:01 0.00 978.32 6519.72 0.00 0.00 0.00 0.00 0.00 314.47
October 10742.40 03-OCT-15:40 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 37.04
November 15027.27 09-NOV-04:01 0.00 978.32 6519.72 0.00 0.00 0.00 0.00 0.00 131.49
December 11241.43 11-DEC-04:01 0.00 978.32 6519.72 0.00 0.00 0.00 0.00 0.00 147.07
                       
Annual Sum or Average                      
Minimum of Months 6892.65   0.00 452.18 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25707.42   2478.65 3255.69 6519.72 0.00 0.00 0.00 0.00 0.00 441.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2568.64 19-JAN-15:30 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
February 2236.28 07-FEB-15:00 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 118.14
March 3841.67 30-MAR-13:50 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 127.12
April 6213.87 28-APR-15:10 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 35.35
May 6425.94 31-MAY-16:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 19.46
June 7687.21 13-JUN-16:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 40.20 0.00
July 8186.48 18-JUL-05:01 2024.33 2806.66 10116.97 0.00 0.00 0.00 0.00 0.00 60.57
August 6785.99 14-AUG-16:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 28.07 0.00
September 6355.59 13-SEP-15:30 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 15.39
October 4559.14 11-OCT-15:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 45.10
November 3001.22 08-NOV-15:00 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
December 2049.00 20-DEC-14:40 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 63.01
                       
Annual Sum or Average                      
Minimum of Months 2049.00   1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8186.48   2024.33 2806.66 10116.97 0.00 0.00 0.00 0.00 40.20 127.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3239.84 20-JAN-10:00 2478.65 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
February 3481.09 17-FEB-09:55 2478.65 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
March 3359.52 30-MAR-14:20 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 67.49
April 11927.76 30-APR-08:43 260.91 361.74 1955.93 0.00 0.00 0.00 0.00 0.00 379.18
May 11483.08 23-MAY-08:40 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 55.80
June 11799.19 13-JUN-08:40 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 29.95
July 20371.96 23-JUL-09:42 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 171.60
August 10784.09 18-AUG-08:40 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 44.60
September 11612.64 04-SEP-09:21 652.28 904.36 4889.82 0.00 0.00 0.00 0.00 0.00 323.38
October 6221.70 04-OCT-09:00 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 73.76
November 3196.48 13-NOV-09:40 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 84.63
December 2810.87 06-DEC-09:50 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 2810.87   260.91 361.74 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20371.96   2478.65 3255.69 4889.82 0.00 0.00 0.00 0.00 0.00 379.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19699.82 15-JAN-13:13 404.87 561.34 3035.14 0.00 0.00 0.00 0.00 0.00 215.34
February 15469.57 17-FEB-13:40 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 241.75
March 10012.05 28-MAR-12:10 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 230.07
April 20729.70 30-APR-13:23 404.87 561.34 3035.14 0.00 0.00 0.00 0.00 0.00 191.56
May 11717.30 22-MAY-13:10 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 17.65
June 10618.62 13-JUN-13:10 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.88 0.00
July 12750.17 31-JUL-13:10 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 101.74
August 16416.76 30-AUG-13:00 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 47.03
September 25997.83 10-SEP-13:32 506.09 701.68 3793.92 0.00 0.00 0.00 0.00 0.00 485.43
October 21177.03 01-OCT-13:23 404.87 561.34 3035.14 0.00 0.00 0.00 0.00 0.00 661.63
November 14348.36 03-NOV-12:40 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 297.60
December 13587.95 18-DEC-13:30 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 162.80
                       
Annual Sum or Average                      
Minimum of Months 10012.05   404.87 561.34 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25997.83   2010.83 2526.05 3793.92 0.00 0.00 0.00 0.00 0.88 661.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4120.14 19-JAN-16:00 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
February 6680.95 27-FEB-16:30 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
March 6774.81 23-MAR-17:00 391.37 904.36 814.96 0.00 0.00 0.00 0.00 0.00 106.17
April 20261.01 30-APR-17:22 0.00 586.99 2933.87 0.00 0.00 0.00 0.00 0.00 50.93
May 20590.05 21-MAY-18:02 0.00 489.16 2444.89 0.00 0.00 0.00 0.00 0.00 263.40
June 18617.54 25-JUN-17:42 0.00 489.16 2444.89 0.00 0.00 0.00 0.00 0.00 20.14
July 20717.56 23-JUL-17:21 0.00 978.32 4889.79 0.00 0.00 0.00 0.00 0.00 253.52
August 18703.77 20-AUG-17:02 0.00 586.99 2933.87 0.00 0.00 0.00 0.00 0.00 178.66
September 11659.17 12-SEP-16:00 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 31.21
October 8363.12 03-OCT-16:00 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 75.61
November 4106.54 10-NOV-15:40 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 90.10
December 3180.13 21-DEC-14:50 1295.83 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 111.34
                       
Annual Sum or Average                      
Minimum of Months 3180.13   0.00 489.16 814.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20717.56   1295.83 1627.84 4889.79 0.00 0.00 0.00 0.00 0.00 263.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2298.32 19-JAN-15:50 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
February 2208.38 09-FEB-16:30 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 159.60
March 2674.09 30-MAR-14:00 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 154.88
April 6746.40 28-APR-15:30 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 45.43
May 7294.61 22-MAY-15:30 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 10.50
June 8802.08 13-JUN-15:50 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 47.78 0.00
July 8469.00 10-JUL-15:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 25.79
August 7619.82 14-AUG-16:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 32.84 0.00
September 6777.74 13-SEP-15:30 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 20.99
October 3803.47 06-OCT-15:50 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 120.83
November 2503.15 10-NOV-15:00 2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 132.61
December 2127.14 29-DEC-17:00 1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 274.81
                       
Annual Sum or Average                      
Minimum of Months 2127.14   1923.11 2525.99 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8802.08   2010.79 2525.99 2276.32 0.00 0.00 0.00 0.00 47.78 274.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2727.69 20-JAN-10:10 2591.66 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
February 2928.82 24-FEB-10:10 2591.66 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 16.27
March 3237.65 30-MAR-14:00 1295.83 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 93.10
April 18214.35 30-APR-09:12 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 453.83
May 11123.74 23-MAY-09:00 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 65.48
June 11792.58 13-JUN-08:50 1239.33 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 36.98
July 20098.81 23-JUL-09:42 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 217.96
August 15447.46 20-AUG-08:52 326.14 452.18 2444.91 0.00 0.00 0.00 0.00 0.00 365.79
September 9397.91 12-SEP-09:10 1295.83 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 46.97
October 4662.08 04-OCT-09:30 1295.83 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 44.26
November 2997.76 10-NOV-15:00 1295.83 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 80.13
December 2416.60 21-DEC-14:50 1295.83 1627.84 1466.95 0.00 0.00 0.00 0.00 0.00 125.92
                       
Annual Sum or Average                      
Minimum of Months 2416.60   326.14 452.18 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20098.81   2591.66 3255.69 2933.89 0.00 0.00 0.00 0.00 0.00 453.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11817.25 20-JAN-12:00 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
February 14947.14 17-FEB-13:40 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 294.44
March 7905.14 10-MAR-14:30 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 152.22
April 27442.29 30-APR-13:12 506.09 701.68 3793.92 0.00 0.00 0.00 0.00 0.00 292.55
May 12344.42 22-MAY-13:10 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 23.15
June 11621.12 13-JUN-13:10 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 0.48
July 12931.89 31-JUL-13:10 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 128.64
August 16472.41 30-AUG-13:00 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 60.44
September 27062.05 10-SEP-13:22 506.09 701.68 3793.92 0.00 0.00 0.00 0.00 0.00 559.53
October 17604.00 03-OCT-14:00 2010.83 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 170.44
November 12452.84 03-NOV-12:40 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 372.16
December 9770.53 18-DEC-13:30 1923.15 2526.05 2276.35 0.00 0.00 0.00 0.00 0.00 203.50
                       
Annual Sum or Average                      
Minimum of Months 7905.14   506.09 701.68 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27442.29   2010.83 2526.05 3793.92 0.00 0.00 0.00 0.00 0.00 559.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3791.64 10-JAN-16:00 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 377.37
February 5477.77 27-FEB-16:40 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
March 6168.73 23-MAR-17:00 391.37 904.36 814.96 0.00 0.00 0.00 0.00 0.00 132.84
April 21964.14 30-APR-17:11 0.00 782.66 3911.83 0.00 0.00 0.00 0.00 0.00 73.09
May 21707.40 21-MAY-18:02 0.00 489.16 2444.89 0.00 0.00 0.00 0.00 0.00 330.52
June 22914.80 25-JUN-16:52 391.37 542.61 2933.87 0.00 0.00 0.00 0.00 0.00 208.18
July 24078.86 09-JUL-17:11 0.00 684.82 3422.85 0.00 0.00 0.00 0.00 0.00 358.06
August 21688.86 20-AUG-16:31 652.28 904.36 4889.79 0.00 0.00 0.00 0.00 0.00 156.40
September 11947.35 12-SEP-16:00 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 40.10
October 8021.05 03-OCT-16:00 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 94.89
November 3832.43 10-NOV-15:40 1239.33 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 109.90
December 3077.24 21-DEC-15:00 1295.83 1627.84 1466.94 0.00 0.00 0.00 0.00 0.00 138.13
                       
Annual Sum or Average                      
Minimum of Months 3077.24   0.00 489.16 814.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24078.86   1295.83 1627.84 4889.79 0.00 0.00 0.00 0.00 0.00 377.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9335.52 02-JAN-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 5983.58 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.53
March 7332.90 20-MAR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.42
April 8131.79 24-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.12
May 7800.15 01-MAY-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 339.29
June 9212.12 26-JUN-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.37
July 8620.11 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 212.83
August 9183.27 28-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.00
September 7967.94 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 188.16
October 8499.70 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 8357.80 13-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.60
December 6875.81 26-DEC-06:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 354.34
                       
Annual Sum or Average                      
Minimum of Months 5983.58   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9335.52   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 354.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5093.11 10-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 546.96
February 4884.83 25-FEB-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.48
March 5028.35 27-MAR-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 6163.67 29-APR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 5264.80 06-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 534.16
June 5833.77 15-JUN-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.05
July 6442.61 07-JUL-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 6218.22 05-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.22
September 5737.05 28-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.04
October 5514.28 10-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 4907.19 13-NOV-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.71
December 5317.05 30-DEC-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 395.45
                       
Annual Sum or Average                      
Minimum of Months 4884.83   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6442.61   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 546.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1866.70 19-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 2556.27 09-FEB-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 201.90
March 4463.92 25-MAR-12:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.17
April 14372.57 28-APR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.31
May 15301.15 22-MAY-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.05
June 16928.66 13-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.61
July 16772.65 21-JUL-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.10 0.00
August 14724.56 14-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.66
September 12742.89 12-SEP-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.04
October 7044.12 04-OCT-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 256.91
November 3003.70 10-NOV-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 212.61
December 280.42 06-DEC-12:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.94
                       
Annual Sum or Average                      
Minimum of Months 280.42   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16928.66   0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.10 256.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1915.99 19-JAN-16:20 0.00 291.78 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4085.89 27-FEB-17:00 0.00 291.78 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5932.90 23-MAR-17:30 0.00 97.26 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7979.34 27-APR-17:50 0.00 97.26 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 2241.13 21-MAY-18:34 0.00 87.68 9743.03 0.00 0.00 0.00 0.00 0.00 0.00
June 4170.65 11-JUN-18:45 0.00 35.07 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
July 6252.48 09-JUL-18:48 0.00 87.68 29229.08 0.00 0.00 0.00 0.00 0.00 0.00
August 8027.71 13-AUG-18:23 0.00 70.14 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 2174.25 12-SEP-17:20 0.00 97.26 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 4047.63 03-OCT-16:40 0.00 162.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5701.71 03-NOV-16:00 0.00 291.78 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7519.13 25-DEC-15:00 0.00 64.84 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1915.99   0.00 35.07 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8027.71   0.00 291.78 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1708.37 19-JAN-16:30 0.00 291.78 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3738.93 27-FEB-17:00 0.00 291.78 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5564.21 23-MAR-17:30 0.00 97.26 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7607.04 27-APR-17:50 0.00 97.26 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 2108.29 21-MAY-18:25 0.00 70.14 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
June 3895.29 11-JUN-18:50 0.00 35.07 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
July 5844.05 09-JUL-18:48 0.00 87.68 29229.08 0.00 0.00 0.00 0.00 0.00 0.00
August 7469.02 04-AUG-18:10 0.00 97.26 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2052.67 12-SEP-17:20 0.00 97.26 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 3785.32 03-OCT-16:50 0.00 162.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5293.81 03-NOV-16:00 0.00 291.78 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6847.31 21-DEC-15:20 0.00 291.78 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1708.37   0.00 35.07 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7607.04   0.00 291.78 29229.08 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1621.25 19-JAN-16:30 0.00 291.78 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3560.44 17-FEB-17:00 0.00 291.78 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5514.88 23-MAR-17:30 0.00 97.26 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7677.97 27-APR-17:50 0.00 97.26 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 2186.85 21-MAY-18:27 0.00 70.14 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
June 4056.92 11-JUN-18:40 0.00 70.14 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
July 6004.24 09-JUL-18:42 0.00 87.68 29229.08 0.00 0.00 0.00 0.00 0.00 0.00
August 7569.31 13-AUG-18:10 0.00 175.36 77944.22 0.00 0.00 0.00 0.00 0.00 0.00
September 2105.45 12-SEP-17:20 0.00 97.26 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 3768.57 03-OCT-16:50 0.00 162.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5206.35 10-NOV-16:20 0.00 291.78 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6661.51 21-DEC-15:20 0.00 291.78 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1621.25   0.00 70.14 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7677.97   0.00 291.78 77944.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 336712.94 21-JAN-04:13 0.00 3795.95 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
February 365576.64 07-FEB-04:05 0.00 3795.95 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
March 395605.94 02-MAR-04:02 0.00 3795.95 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
April 389920.83 26-APR-03:44 0.00 3795.95 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
May 338211.41 11-MAY-22:13 0.00 3508.98 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
June 413682.84 18-JUN-21:21 0.00 3795.95 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
July 395846.04 31-JUL-03:22 0.00 3795.95 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
August 392327.77 03-AUG-03:42 0.00 3795.95 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
September 318739.20 19-SEP-21:18 0.00 7017.96 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
October 378622.76 14-OCT-19:27 0.00 3795.95 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
November 391092.63 14-NOV-02:37 0.00 3795.95 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
December 387238.34 12-DEC-05:23 0.00 7591.91 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 318739.20   0.00 3508.98 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 413682.84   0.00 7591.91 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP}
January 0.174107E+13 1128065.43 02-JAN-08:09 0.596966E+12 1120868.38 10-JAN-07:00
February 0.192031E+13 1233093.01 09-FEB-16:10 0.477029E+12 997111.56 17-FEB-07:19
March 0.256629E+13 1393827.68 23-MAR-15:00 0.438410E+12 821751.40 08-MAR-07:10
April 0.286750E+13 1781068.05 28-APR-15:09 0.189692E+12 821972.58 08-APR-06:10
May 0.178138E+13 1358987.40 22-MAY-15:39 0.173092E+12 572131.66 15-MAY-01:49
June 0.220363E+13 1593345.24 13-JUN-15:00 0.864996E+11 408579.36 07-JUN-20:00
July 0.266862E+13 1727890.14 21-JUL-15:00 0.592723E+11 396764.85 02-JUL-18:49
August 0.316876E+13 1844850.50 14-AUG-15:00 0.582332E+11 276636.89 27-AUG-21:40
September 0.178913E+13 1367812.06 12-SEP-15:39 0.870145E+11 610461.89 04-SEP-06:10
October 0.215743E+13 1355825.88 06-OCT-15:20 0.223919E+12 645442.06 28-OCT-06:00
November 0.246531E+13 1427375.70 10-NOV-16:40 0.390736E+12 1106679.36 29-NOV-07:10
December 0.289438E+13 1560954.59 29-DEC-08:09 0.632407E+12 1355684.88 30-DEC-07:10
             
Annual Sum or Average 0.282238E+14     0.341327E+13    
Minimum of Months 0.174107E+13 1128065.43   0.582332E+11 276636.89  
Maximum of Months 0.316876E+13 1844850.50   0.632407E+12 1355684.88  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.358355E+12 0.964764E+11 0.811612E+12 0.173544E+12 0.181736E+12 0.144273E+11 0.00 0.901954E+11 0.119956E+11 0.272858E+10 0.00 0.00 0.00
February 0.325045E+12 0.793896E+11 0.102011E+13 0.156760E+12 0.167383E+12 0.120055E+11 0.00 0.140338E+12 0.172027E+11 0.207365E+10 0.00 0.00 0.00
March 0.386070E+12 0.772622E+11 0.146224E+13 0.173828E+12 0.191230E+12 0.124156E+11 0.00 0.217507E+12 0.428204E+11 0.291144E+10 0.00 0.00 0.00
April 0.345016E+12 0.640249E+11 0.170426E+13 0.167919E+12 0.201586E+12 0.170492E+11 0.00 0.282840E+12 0.824874E+11 0.231058E+10 0.00 0.00 0.00
May 0.372213E+12 0.567310E+11 0.820095E+12 0.173686E+12 0.202561E+12 0.187046E+11 0.00 0.107898E+12 0.284320E+11 0.105874E+10 0.00 0.00 0.00
June 0.370347E+12 0.498760E+11 0.110647E+13 0.168186E+12 0.199145E+12 0.312974E+11 0.00 0.196198E+12 0.819300E+11 0.181563E+09 0.00 0.00 0.00
July 0.346881E+12 0.537593E+11 0.143833E+13 0.173418E+12 0.199089E+12 0.450513E+11 0.00 0.292420E+12 0.119628E+12 43978590.82 0.00 0.00 0.00
August 0.386070E+12 0.619651E+11 0.177907E+13 0.173828E+12 0.205518E+12 0.520457E+11 0.00 0.377702E+12 0.132499E+12 56060621.32 0.00 0.00 0.00
September 0.345016E+12 0.701032E+11 0.784429E+12 0.167919E+12 0.193075E+12 0.360882E+11 0.00 0.135545E+12 0.567676E+11 0.185084E+09 0.00 0.00 0.00
October 0.358355E+12 0.834755E+11 0.112844E+13 0.173544E+12 0.191760E+12 0.145240E+11 0.00 0.162468E+12 0.439940E+11 0.868674E+09 0.00 0.00 0.00
November 0.354107E+12 0.904318E+11 0.140306E+13 0.168027E+12 0.179686E+12 0.117613E+11 0.00 0.210109E+12 0.465596E+11 0.156696E+10 0.00 0.00 0.00
December 0.346881E+12 0.990766E+11 0.175516E+13 0.173418E+12 0.177943E+12 0.138362E+11 0.00 0.273520E+12 0.516248E+11 0.292118E+10 0.00 0.00 0.00
                           
Annual Sum or Average 0.429436E+13 0.882572E+12 0.152133E+14 0.204408E+13 0.229071E+13 0.279206E+12 0.00 0.248674E+13 0.715941E+12 0.169065E+11      
Minimum of Months 0.325045E+12 0.498760E+11 0.784429E+12 0.156760E+12 0.167383E+12 0.117613E+11 0.00 0.901954E+11 0.119956E+11 43978590.82 0.00 0.00 0.00
Maximum of Months 0.386070E+12 0.990766E+11 0.177907E+13 0.173828E+12 0.205518E+12 0.520457E+11 0.00 0.377702E+12 0.132499E+12 0.292118E+10 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

INTERIOREQUIPMENT:GAS [] EXTERIOREQUIPMENT:GAS [] HEATING:GAS [J] COOLING:GAS [] WATERSYSTEMS:GAS [J] COGENERATION:GAS [] HUMIDIFIER:GAS []
January 0.00 0.00 0.541867E+12 0.00 0.550992E+11 0.00 0.00
February 0.00 0.00 0.426788E+12 0.00 0.502410E+11 0.00 0.00
March 0.00 0.00 0.380277E+12 0.00 0.581328E+11 0.00 0.00
April 0.00 0.00 0.137394E+12 0.00 0.522984E+11 0.00 0.00
May 0.00 0.00 0.118719E+12 0.00 0.543727E+11 0.00 0.00
June 0.00 0.00 0.342097E+11 0.00 0.522900E+11 0.00 0.00
July 0.00 0.00 0.966199E+10 0.00 0.496103E+11 0.00 0.00
August 0.00 0.00 0.533967E+10 0.00 0.528935E+11 0.00 0.00
September 0.00 0.00 0.381036E+11 0.00 0.489109E+11 0.00 0.00
October 0.00 0.00 0.172272E+12 0.00 0.516469E+11 0.00 0.00
November 0.00 0.00 0.338832E+12 0.00 0.519043E+11 0.00 0.00
December 0.00 0.00 0.579462E+12 0.00 0.529451E+11 0.00 0.00
               
Annual Sum or Average     0.278293E+13   0.630345E+12    
Minimum of Months 0.00 0.00 0.533967E+10 0.00 0.489109E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.579462E+12 0.00 0.581328E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum}[W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum}[W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum}[W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum}[W] HEATING:ELECTRICITY {TIMESTAMP}
January 373325.05 02-JAN-08:09 56280.71 01-JAN-00:10 439129.89 02-JAN-08:09 129663.18 02-JAN-08:20 139450.19 20-JAN-11:00 26640.87 09-JAN-06:10 0.00 01-JAN-00:10
February 373325.05 01-FEB-08:09 56280.71 01-FEB-00:10 557421.28 01-FEB-08:09 129663.18 01-FEB-08:20 140939.00 17-FEB-15:20 25537.67 13-FEB-06:10 0.00 01-FEB-00:10
March 373325.05 01-MAR-08:09 56280.71 01-MAR-00:10 675712.68 01-MAR-08:09 129663.18 01-MAR-08:20 136460.86 23-MAR-15:00 23715.25 08-MAR-06:10 0.00 01-MAR-00:10
April 373325.05 03-APR-07:10 56280.71 01-APR-00:10 794004.08 03-APR-07:10 129663.18 03-APR-07:19 169201.87 12-APR-14:00 51178.91 28-APR-14:39 0.00 01-APR-00:10
May 373325.05 01-MAY-07:10 56280.71 01-MAY-00:10 439129.89 01-MAY-07:10 129663.18 01-MAY-07:19 157251.67 01-MAY-15:00 50535.50 22-MAY-15:00 0.00 01-MAY-00:10
June 373325.05 01-JUN-07:10 56280.71 01-JUN-00:10 557421.28 01-JUN-07:10 129663.18 01-JUN-07:19 154306.86 06-JUN-15:00 50895.43 20-JUN-14:00 0.00 01-JUN-00:10
July 373325.05 03-JUL-07:10 56280.71 01-JUL-00:10 675712.68 03-JUL-07:10 129663.18 03-JUL-07:19 142414.62 20-JUL-15:00 51221.11 06-JUL-14:00 0.00 01-JUL-00:10
August 373325.05 01-AUG-07:10 56280.71 01-AUG-00:10 794004.08 01-AUG-07:10 129663.18 01-AUG-07:19 144483.92 29-AUG-15:30 51037.33 14-AUG-16:40 0.00 01-AUG-00:10
September 373325.05 01-SEP-07:10 56280.71 01-SEP-00:10 439129.89 01-SEP-07:10 129663.18 01-SEP-07:19 148954.66 29-SEP-15:39 51331.74 25-SEP-13:00 0.00 01-SEP-00:10
October 373325.05 02-OCT-07:10 56280.71 01-OCT-00:10 557421.28 02-OCT-07:10 129663.18 02-OCT-07:19 155610.73 03-OCT-14:00 29779.04 06-OCT-15:20 0.00 01-OCT-00:10
November 373325.05 01-NOV-07:10 56280.71 01-NOV-00:10 675712.68 01-NOV-07:10 129663.18 01-NOV-07:19 139910.95 03-NOV-13:09 28434.44 24-NOV-11:00 0.00 01-NOV-00:10
December 373325.05 01-DEC-08:09 56280.71 01-DEC-00:10 794004.08 01-DEC-08:09 129663.18 01-DEC-08:20 124180.94 21-DEC-14:09 26256.72 26-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 373325.05   56280.71   439129.89   129663.18   124180.94   23715.25   0.00  
Maximum of Months 373325.05   56280.71   794004.08   129663.18   169201.87   51331.74   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING:ELECTRICITY {Maximum}[W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum}[W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum}[W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 93661.73 04-JAN-01:39 17199.83 29-JAN-05:00 22649.59 06-JAN-22:30 0.00 0.00 0.00
February 100140.12 18-FEB-18:19 19936.70 04-FEB-18:19 33362.21 03-FEB-05:19 0.00 0.00 0.00
March 103632.56 04-MAR-19:30 44634.08 25-MAR-12:00 18854.33 15-MAR-03:39 0.00 0.00 0.00
April 288974.14 28-APR-14:39 59751.18 28-APR-14:39 8046.99 08-APR-16:19 0.00 0.00 0.00
May 207614.95 22-MAY-14:30 79510.01 22-MAY-14:39 21092.62 16-MAY-21:40 0.00 0.00 0.00
June 300775.65 13-JUN-15:00 79510.01 12-JUN-12:20 33333.33 07-JUN-21:19 0.00 0.00 0.00
July 318134.13 21-JUL-15:00 79510.01 10-JUL-09:30 12157.14 03-JUL-21:10 0.00 0.00 0.00
August 322783.49 14-AUG-15:00 79510.01 14-AUG-09:00 2897.05 24-AUG-15:00 0.00 0.00 0.00
September 203936.80 12-SEP-15:39 79510.01 11-SEP-13:50 19363.77 20-SEP-21:19 0.00 0.00 0.00
October 117604.87 06-OCT-15:30 50987.51 11-OCT-14:00 33334.82 27-OCT-21:19 0.00 0.00 0.00
November 119871.82 24-NOV-11:00 49935.35 24-NOV-11:00 20180.25 01-NOV-21:30 0.00 0.00 0.00
December 108149.27 12-DEC-05:00 46231.08 23-DEC-10:00 8939.80 30-DEC-17:19 0.00 0.00 0.00
                   
Annual Sum or Average                  
Minimum of Months 93661.73   17199.83   2897.05   0.00 0.00 0.00
Maximum of Months 322783.49   79510.01   33362.21   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1128065.43 02-JAN-08:09 373325.05 439129.89 56280.71 129457.66 82110.18 10192.98 0.00 31536.62 3404.15
February 1233093.01 09-FEB-16:10 373325.05 557421.28 0.00 92996.58 132987.96 4604.63 0.00 59984.63 9661.48
March 1393827.68 23-MAR-15:00 373325.05 675712.68 0.00 92996.58 136460.86 3374.44 0.00 82683.52 27145.55
April 1781068.05 28-APR-15:09 373325.05 794004.08 0.00 92996.58 139448.10 50924.14 0.00 271901.87 58468.23
May 1358987.40 22-MAY-15:39 373325.05 439129.89 0.00 92996.58 123726.64 50453.71 0.00 205562.45 73793.09
June 1593345.24 13-JUN-15:00 373325.05 557421.28 0.00 92996.58 138696.17 50620.51 0.00 300775.65 79510.01
July 1727890.14 21-JUL-15:00 373325.05 675712.68 0.00 92996.58 137186.71 51024.98 0.00 318134.13 79510.01
August 1844850.50 14-AUG-15:00 373325.05 794004.08 0.00 92996.58 131984.60 50246.68 0.00 322783.49 79510.01
September 1367812.06 12-SEP-15:39 373325.05 439129.89 0.00 92996.58 131757.04 50212.09 0.00 203936.80 76454.61
October 1355825.88 06-OCT-15:20 373325.05 557421.28 0.00 92996.58 131602.41 29779.04 0.00 117481.54 50362.73
November 1427375.70 10-NOV-16:40 373325.05 675712.68 56280.71 92996.58 119494.60 3990.37 0.00 82814.60 21896.65
December 1560954.59 29-DEC-08:09 373325.05 794004.08 56280.71 129457.66 80141.24 9284.53 0.00 101200.74 14431.58
                       
Annual Sum or Average                      
Minimum of Months 1128065.43   373325.05 439129.89 0.00 92996.58 80141.24 3374.44 0.00 31536.62 3404.15
Maximum of Months 1844850.50   373325.05 794004.08 56280.71 129457.66 139448.10 51024.98 0.00 322783.49 79510.01



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

INTERIOREQUIPMENT:GAS [] EXTERIOREQUIPMENT:GAS [] HEATING:GAS {Maximum}[W] HEATING:GAS {TIMESTAMP} COOLING:GAS [] WATERSYSTEMS:GAS {Maximum}[W] WATERSYSTEMS:GAS {TIMESTAMP} COGENERATION:GAS []
January 0.00 0.00 1112721.80 10-JAN-07:00 0.00 79838.04 31-JAN-12:20 0.00
February 0.00 0.00 988964.98 17-FEB-07:19 0.00 79903.97 16-FEB-12:20 0.00
March 0.00 0.00 813604.82 08-MAR-07:10 0.00 79836.28 01-MAR-12:20 0.00
April 0.00 0.00 813826.00 08-APR-06:10 0.00 79147.52 04-APR-11:30 0.00
May 0.00 0.00 563985.08 15-MAY-01:49 0.00 78172.92 01-MAY-11:20 0.00
June 0.00 0.00 400432.78 07-JUN-20:00 0.00 76824.05 01-JUN-11:39 0.00
July 0.00 0.00 388618.27 02-JUL-18:49 0.00 75564.91 03-JUL-11:30 0.00
August 0.00 0.00 268490.31 27-AUG-21:40 0.00 74878.47 31-AUG-11:39 0.00
September 0.00 0.00 602315.31 04-SEP-06:10 0.00 75564.61 29-SEP-11:00 0.00
October 0.00 0.00 637295.48 28-OCT-06:00 0.00 76830.73 31-OCT-11:39 0.00
November 0.00 0.00 1098532.78 29-NOV-07:10 0.00 78139.67 30-NOV-12:50 0.00
December 0.00 0.00 1347538.30 30-DEC-07:10 0.00 79178.46 29-DEC-12:30 0.00
                 
Annual Sum or Average                
Minimum of Months 0.00 0.00 268490.31   0.00 74878.47   0.00
Maximum of Months 0.00 0.00 1347538.30   0.00 79903.97   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 9.33 26.43 0.50 28.16
February 0.00 0.00 0.00 0.00 7.33 26.10 0.17 27.27
March 0.00 0.00 0.00 0.00 13.00 26.20 0.00 0.00
April 0.00 0.00 0.00 0.00 12.50 26.25 0.50 27.54
May 0.00 0.00 0.00 0.00 13.33 26.54 1.83 28.09
June 0.00 0.00 0.00 0.00 11.17 26.08 0.00 0.00
July 0.00 0.00 0.00 0.00 14.50 26.54 1.00 27.40
August 0.00 0.00 0.00 0.00 12.83 26.25 1.00 27.43
September 0.00 0.00 0.00 0.00 11.33 26.22 1.33 27.83
October 0.00 0.00 0.00 0.00 10.83 26.19 0.83 28.49
November 0.00 0.00 0.00 0.00 11.50 26.31 1.00 28.45
December 0.00 0.00 0.00 0.00 13.00 26.40 1.17 28.08
                 
Annual Sum or Average 0.00   0.00   140.67 26.30 9.33 27.94
Minimum of Months 0.00 0.00 0.00 0.00 7.33 26.08 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 14.50 26.54 1.83 28.49



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 25.68 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 25.59 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 25.61 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.33 25.65 0.00 0.00
November 0.00 0.00 0.00 0.00 0.33 25.62 0.00 0.00
December 0.00 0.00 0.00 0.00 0.33 25.60 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 25.63 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 25.68 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 19.28 0.17 20.41 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 19.39 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.50 19.33 0.17 20.41 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 19.39 0.17 20.41 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.66 0.83 27.66
May 0.00 0.00 0.00 0.00 1.00 27.54 1.00 27.54
June 0.00 0.00 0.00 0.00 0.67 27.32 0.67 27.32
July 0.00 0.00 0.00 0.00 1.83 27.71 1.83 27.71
August 0.00 0.00 0.00 0.00 0.67 27.71 0.67 27.71
September 0.00 0.00 0.00 0.00 0.67 27.62 0.67 27.62
October 0.00 0.00 0.00 0.00 0.17 27.29 0.17 27.29
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.83 27.61 5.83 27.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 27.71 1.83 27.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 27.44 0.33 27.44
February 0.00 0.00 0.00 0.00 0.33 27.41 0.33 27.41
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.90 0.83 27.90
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.33 27.61 1.33 27.61
October 0.00 0.00 0.00 0.00 0.67 27.35 0.67 27.35
November 0.00 0.00 0.00 0.00 0.67 27.67 0.67 27.67
December 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
                 
Annual Sum or Average 0.00   0.00   4.33 27.59 4.33 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 27.90 1.33 27.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 27.43 0.17 27.43
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.50 27.91 2.17 27.88
May 0.00 0.00 0.00 0.00 2.50 27.86 1.67 27.87
June 0.00 0.00 0.00 0.00 3.83 27.91 2.17 27.76
July 0.00 0.00 0.00 0.00 7.50 28.13 3.50 28.17
August 0.00 0.00 0.00 0.00 8.50 27.90 3.50 28.31
September 0.00 0.00 0.00 0.00 0.50 27.31 0.50 27.31
October 0.00 0.00 0.00 0.00 0.33 27.29 0.33 27.29
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
                 
Annual Sum or Average 0.00   0.00   27.00 27.94 14.17 27.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.50 28.13 3.50 28.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.81 0.67 27.81
May 0.00 0.00 0.00 0.00 0.50 27.46 0.50 27.46
June 0.00 0.00 0.00 0.00 0.17 27.42 0.17 27.42
July 0.00 0.00 0.00 0.00 1.50 27.94 1.50 27.94
August 0.00 0.00 0.00 0.00 0.50 27.67 0.50 27.67
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.33 27.78 3.33 27.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 27.94 1.50 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 27.46 0.17 27.46
February 0.00 0.00 0.00 0.00 0.33 27.67 0.33 27.67
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.82 1.00 27.82
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.83 27.78 1.83 27.78
October 0.00 0.00 0.00 0.00 0.83 27.06 0.83 27.06
November 0.00 0.00 0.00 0.00 0.67 27.60 0.67 27.60
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.83 27.62 4.83 27.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 27.82 1.83 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 28.09 0.33 28.03
May 0.00 0.00 0.00 0.00 1.50 27.84 0.83 27.71
June 0.00 0.00 0.00 0.00 1.50 28.17 0.67 28.03
July 0.00 0.00 0.00 0.00 3.83 27.88 1.67 27.79
August 0.00 0.00 0.00 0.00 1.33 27.85 0.83 27.82
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   9.00 27.93 4.33 27.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.83 28.17 1.67 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.83 18.74 1.33 20.05 0.00 0.00 0.00 0.00
February 2.33 19.04 0.17 20.41 0.00 0.00 0.00 0.00
March 0.33 19.26 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.83 18.97 0.50 20.33 0.00 0.00 0.00 0.00
December 8.17 18.90 1.83 20.19 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 19.50 18.89 3.83 20.17 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.17 19.26 1.83 20.41 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.83 18.55 0.00 0.00 0.00 0.00 0.00 0.00
February 1.67 18.87 0.00 0.00 0.00 0.00 0.00 0.00
March 0.50 19.33 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.41 0.50 27.41
May 0.00 0.00 0.00 0.00 0.17 27.34 0.17 27.34
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 28.00 1.00 28.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.67 18.48 0.00 0.00 0.00 0.00 0.00 0.00
December 4.50 18.48 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 11.17 18.59 0.00   1.67 27.76 1.67 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 19.33 0.00 0.00 1.00 28.00 1.00 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 18.52 0.00 0.00 0.00 0.00 0.00 0.00
February 1.33 19.03 0.00 0.00 0.00 0.00 0.00 0.00
March 0.17 19.24 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.94 0.83 27.94
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.17 27.60 1.17 27.60
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.17 18.91 0.00 0.00 0.00 0.00 0.00 0.00
December 3.50 18.48 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.33 18.65 0.00   2.00 27.74 2.00 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 19.24 0.00 0.00 1.17 27.94 1.17 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.83 18.61 0.00 0.00 0.00 0.00 0.00 0.00
February 1.00 19.07 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 28.25 0.33 28.09
May 0.00 0.00 0.00 0.00 1.17 27.94 0.67 27.72
June 0.00 0.00 0.00 0.00 2.00 28.10 1.00 28.04
July 0.00 0.00 0.00 0.00 3.83 28.01 1.67 27.88
August 0.00 0.00 0.00 0.00 1.67 27.78 1.00 27.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.00 18.98 0.00 0.00 0.00 0.00 0.00 0.00
December 2.33 18.54 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 6.17 18.72 0.00   9.50 28.00 4.67 27.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.07 0.00 0.00 3.83 28.25 1.67 28.09



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.50 28.06 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.83 27.72 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.33 27.92 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.50 28.06 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 27.81 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.67 27.70 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.33 27.76 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 27.81 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 27.83 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.17 27.69 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 27.78 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 27.83 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.50 28.28 0.00 0.00
February 0.00 0.00 0.00 0.00 1.00 28.77 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 28.25 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.50 28.46 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 28.26 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 27.63 0.00 0.00
August 0.00 0.00 0.00 0.00 1.17 27.69 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 28.23 0.00 0.00
October 0.00 0.00 0.00 0.00 1.83 28.64 0.00 0.00
November 0.00 0.00 0.00 0.00 1.83 27.87 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.00 28.28 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.50 28.77 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 40.17 24.03 112.67 26.12 0.33 26.84
February 14.17 24.03 95.00 26.23 0.00 0.00
March 17.00 24.03 89.50 26.19 0.00 0.00
April 0.00 0.00 105.67 26.38 0.00 0.00
May 1.67 26.01 192.33 25.26 1.17 26.82
June 0.00 0.00 330.17 24.69 0.00 0.00
July 0.00 0.00 428.33 24.71 0.00 0.00
August 0.17 26.61 434.33 24.56 0.17 26.61
September 0.17 26.80 326.17 24.79 0.17 26.80
October 1.17 26.12 223.50 25.29 0.83 26.85
November 2.00 25.48 184.17 25.51 1.00 26.83
December 20.83 24.13 109.33 26.39 0.83 26.82
             
Annual Sum or Average 97.33 24.15 2631.17 25.14 4.50 26.82
Minimum of Months 0.00 0.00 89.50 24.56 0.00 0.00
Maximum of Months 40.17 26.80 434.33 26.39 1.17 26.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 99.33 24.32 100.67 25.60 12.00 27.01
February 41.33 23.98 94.50 25.58 0.00 0.00
March 19.67 24.02 83.00 26.07 0.00 0.00
April 0.00 0.00 116.00 25.50 0.00 0.00
May 6.67 23.85 190.17 24.87 0.00 0.00
June 0.00 0.00 360.50 24.41 0.00 0.00
July 0.00 0.00 434.83 24.39 0.00 0.00
August 0.00 0.00 459.83 24.30 0.00 0.00
September 0.33 24.03 325.50 24.41 0.00 0.00
October 3.17 23.84 229.33 24.96 0.00 0.00
November 10.17 24.02 190.33 25.17 0.00 0.00
December 28.17 24.00 107.17 26.02 0.00 0.00
             
Annual Sum or Average 208.83 24.14 2691.83 24.77 12.00 27.01
Minimum of Months 0.00 0.00 83.00 24.30 0.00 0.00
Maximum of Months 99.33 24.32 459.83 26.07 12.00 27.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 279.83 23.80 13.83 24.65 13.17 24.68
February 212.33 23.80 0.17 24.10 0.00 0.00
March 198.33 23.82 22.00 24.98 0.00 0.00
April 85.17 23.80 59.17 25.40 0.00 0.00
May 59.17 23.76 125.50 24.78 0.00 0.00
June 15.17 23.46 274.00 24.38 0.00 0.00
July 20.83 23.43 318.50 24.38 0.00 0.00
August 15.50 23.43 323.83 24.26 0.00 0.00
September 30.83 23.50 219.33 24.38 0.00 0.00
October 81.33 23.68 109.00 24.71 0.00 0.00
November 180.50 23.80 49.00 24.70 0.00 0.00
December 347.17 23.68 0.00 0.00 0.00 0.00
             
Annual Sum or Average 1526.17 23.75 1514.33 24.47 13.17 24.68
Minimum of Months 15.17 23.43 0.00 0.00 0.00 0.00
Maximum of Months 347.17 23.82 323.83 25.40 13.17 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 474.67 22.10 76.33 20.08 76.33 20.08
February 425.17 22.42 44.67 20.27 44.67 20.27
March 457.83 22.98 10.17 20.81 10.17 20.81
April 271.00 23.44 4.17 24.20 0.00 0.00
May 215.67 23.43 64.33 24.17 0.00 0.00
June 89.33 23.46 236.33 24.24 0.00 0.00
July 82.00 23.42 285.00 24.28 0.00 0.00
August 79.00 23.45 271.00 24.16 0.00 0.00
September 187.00 23.28 125.00 24.10 0.00 0.00
October 362.83 22.95 11.00 24.00 0.00 0.00
November 431.50 22.59 32.33 20.91 29.83 20.65
December 492.50 22.02 105.83 20.21 105.83 20.21
             
Annual Sum or Average 3568.50 22.72 1266.17 23.37 266.83 20.25
Minimum of Months 79.00 22.02 4.17 20.08 0.00 0.00
Maximum of Months 492.50 23.46 285.00 24.28 105.83 20.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 424.67 23.11 0.00 0.00 0.00 0.00
February 360.33 23.26 0.00 0.00 0.00 0.00
March 327.00 23.54 14.83 25.12 0.00 0.00
April 152.83 23.75 24.00 24.78 0.00 0.00
May 166.00 23.62 83.67 24.46 0.00 0.00
June 23.67 23.70 276.00 24.27 0.00 0.00
July 3.50 23.74 368.17 24.31 0.00 0.00
August 6.67 23.76 364.83 24.20 0.00 0.00
September 113.17 23.52 148.00 24.18 0.00 0.00
October 246.00 23.47 42.50 24.69 0.00 0.00
November 315.17 23.43 9.00 24.32 0.00 0.00
December 440.83 23.36 0.00 0.00 0.00 0.00
             
Annual Sum or Average 2579.83 23.40 1331.00 24.30 0.00  
Minimum of Months 3.50 23.11 0.00 0.00 0.00 0.00
Maximum of Months 440.83 23.76 368.17 25.12 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 480.50 22.25 7.67 23.87 3.00 21.02
February 424.67 22.39 2.00 26.35 0.00 0.00
March 470.67 22.62 5.67 25.31 0.00 0.00
April 235.50 23.01 72.50 24.35 2.33 26.67
May 218.00 22.96 148.83 24.61 1.83 26.49
June 157.00 22.96 239.67 24.26 3.00 26.08
July 133.17 23.01 282.83 24.30 7.67 26.48
August 164.67 22.85 251.67 24.12 4.50 26.21
September 204.17 22.78 200.50 24.29 4.17 26.27
October 361.83 22.62 51.00 24.63 0.00 0.00
November 466.00 22.50 1.67 25.66 0.00 0.00
December 497.00 22.15 0.83 20.50 0.83 20.50
             
Annual Sum or Average 3813.17 22.56 1264.83 24.31 27.33 25.59
Minimum of Months 133.17 22.15 0.83 20.50 0.00 0.00
Maximum of Months 497.00 23.01 282.83 26.35 7.67 26.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 398.50 22.31 51.50 24.54 4.50 21.42
February 331.17 22.48 51.50 24.65 0.33 26.19
March 391.50 22.76 5.67 24.40 0.00 0.00
April 203.17 23.23 100.33 24.34 2.67 26.86
May 255.33 23.02 105.67 24.43 0.00 0.00
June 139.00 23.06 223.50 24.17 0.00 0.00
July 110.33 23.05 280.17 24.23 0.17 25.43
August 98.17 23.12 311.50 24.21 2.50 25.89
September 170.67 23.08 237.83 24.34 7.17 26.44
October 286.00 22.84 119.50 24.38 0.83 26.12
November 375.67 22.74 47.00 24.81 1.50 26.80
December 425.33 22.26 27.17 24.76 0.67 20.67
             
Annual Sum or Average 3184.83 22.71 1561.33 24.32 20.33 25.13
Minimum of Months 98.17 22.26 5.67 24.17 0.00 0.00
Maximum of Months 425.33 23.23 311.50 24.81 7.17 26.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 420.67 22.63 21.00 25.02 0.00 0.00
February 262.67 22.97 55.33 24.84 0.00 0.00
March 169.83 23.20 97.67 25.49 0.00 0.00
April 15.33 24.55 303.33 24.77 4.83 26.91
May 144.33 23.12 222.67 24.60 4.83 26.60
June 20.17 24.55 406.50 24.42 8.50 26.36
July 19.67 26.15 472.33 24.49 17.00 26.61
August 16.50 26.69 505.00 24.41 16.50 26.69
September 139.67 22.94 235.00 24.36 2.50 25.68
October 166.83 22.98 185.50 24.81 0.00 0.00
November 177.50 23.13 150.67 24.98 0.00 0.00
December 208.17 23.17 90.33 25.66 0.00 0.00
             
Annual Sum or Average 1761.33 23.06 2745.33 24.63 54.17 26.58
Minimum of Months 15.33 22.63 21.00 24.36 0.00 0.00
Maximum of Months 420.67 26.69 505.00 25.66 17.00 26.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.67 21.97 60.50 20.70 60.50 20.70
February 453.17 22.09 24.33 20.44 24.33 20.44
March 502.17 22.75 0.00 0.00 0.00 0.00
April 359.17 23.21 0.67 24.00 0.00 0.00
May 301.67 23.13 33.00 24.00 0.00 0.00
June 150.00 23.38 156.83 24.13 0.00 0.00
July 132.83 23.35 213.83 24.14 0.00 0.00
August 145.33 23.33 184.50 24.01 0.00 0.00
September 277.67 23.11 70.17 24.01 0.00 0.00
October 420.17 22.73 3.17 24.00 0.00 0.00
November 471.67 22.22 29.67 20.53 29.67 20.53
December 497.00 21.49 110.00 20.42 110.00 20.42
             
Annual Sum or Average 4211.50 22.53 886.67 23.18 224.50 20.51
Minimum of Months 132.83 21.49 0.00 0.00 0.00 0.00
Maximum of Months 502.17 23.38 213.83 24.14 110.00 20.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 21.33 59.17 20.70 59.17 20.70
February 384.67 21.48 17.67 20.40 17.67 20.40
March 431.83 21.78 3.17 20.68 3.17 20.68
April 265.83 22.62 43.50 24.53 2.50 26.73
May 262.17 22.50 96.17 24.68 0.83 26.25
June 211.50 22.65 144.50 24.45 1.83 25.93
July 188.17 22.83 184.33 24.64 7.67 26.56
August 220.67 22.68 154.50 24.29 4.33 26.24
September 239.83 22.40 106.67 24.48 1.50 25.84
October 393.33 21.98 5.83 24.96 0.00 0.00
November 417.00 21.45 23.83 20.52 23.83 20.52
December 422.00 20.96 124.00 20.47 124.00 20.47
             
Annual Sum or Average 3864.00 21.89 963.33 23.57 246.50 20.97
Minimum of Months 188.17 20.96 3.17 20.40 0.00 0.00
Maximum of Months 431.83 22.83 184.33 24.96 124.00 26.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.50 21.91 65.00 23.54 22.50 21.00
February 351.67 21.96 56.33 24.21 8.17 20.70
March 455.17 22.22 1.00 20.54 1.00 20.54
April 272.83 22.81 86.67 24.58 2.67 26.79
May 327.17 22.64 78.33 24.45 0.00 0.00
June 248.50 22.80 150.00 24.19 0.00 0.00
July 209.50 22.76 195.00 24.28 0.00 0.00
August 200.67 22.86 219.33 24.20 2.50 26.13
September 218.00 22.83 215.83 24.36 8.00 26.62
October 347.67 22.41 95.00 24.35 2.33 26.63
November 410.33 22.01 45.33 23.99 11.33 21.32
December 461.67 21.51 81.50 21.10 69.33 20.49
             
Annual Sum or Average 3917.67 22.28 1289.33 24.05 127.83 21.40
Minimum of Months 200.67 21.51 1.00 20.54 0.00 0.00
Maximum of Months 461.67 22.86 219.33 24.58 69.33 26.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.00 21.47 42.83 20.81 42.83 20.81
February 431.67 21.62 15.67 21.28 12.67 20.52
March 500.00 21.96 3.00 23.00 0.83 20.40
April 356.33 22.72 57.33 24.27 1.17 26.64
May 341.83 22.61 92.00 24.40 2.33 26.49
June 218.67 22.79 182.67 24.29 4.17 26.58
July 178.50 22.77 232.50 24.34 7.83 26.55
August 215.17 22.72 171.50 24.20 5.83 26.43
September 338.33 22.45 90.33 24.25 0.50 25.59
October 461.50 22.09 18.00 24.13 0.00 0.00
November 483.17 21.62 18.67 20.54 18.67 20.54
December 497.00 21.12 69.67 20.52 69.67 20.52
             
Annual Sum or Average 4521.17 22.01 994.17 23.75 166.50 21.38
Minimum of Months 178.50 21.12 3.00 20.52 0.00 0.00
Maximum of Months 500.00 22.79 232.50 24.40 69.67 26.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.67 279.33 20.00 279.33 20.00
February 454.00 20.83 198.33 19.86 198.33 19.86
March 514.00 21.60 111.83 20.43 111.83 20.43
April 397.50 22.44 25.00 20.64 23.50 20.42
May 369.67 22.49 45.17 23.47 6.83 20.47
June 222.00 22.90 145.00 24.09 0.00 0.00
July 194.83 22.88 197.67 24.11 0.00 0.00
August 237.50 22.95 165.17 24.00 0.00 0.00
September 342.00 22.46 61.33 23.82 2.83 20.05
October 489.50 21.70 57.50 19.97 57.50 19.97
November 489.00 21.01 162.00 19.92 162.00 19.92
December 497.00 20.36 307.83 19.80 307.83 19.80
             
Annual Sum or Average 4709.00 21.63 1756.17 21.38 1150.00 19.96
Minimum of Months 194.83 20.36 25.00 19.80 0.00 0.00
Maximum of Months 514.00 22.95 307.83 24.11 307.83 20.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.56 279.50 20.10 279.50 20.10
February 454.00 20.76 184.83 20.02 184.83 20.02
March 514.00 21.21 113.33 20.56 113.33 20.56
April 325.50 22.30 51.67 23.64 9.50 20.83
May 334.17 22.30 97.83 24.27 2.33 20.30
June 239.00 22.44 190.33 24.26 1.83 25.92
July 198.67 22.63 250.00 24.41 7.50 26.55
August 234.67 22.47 220.50 24.19 1.50 25.85
September 269.33 22.08 149.50 24.20 2.17 20.05
October 484.00 21.43 47.33 20.08 47.33 20.08
November 489.00 20.79 151.33 19.98 151.33 19.98
December 497.00 20.29 310.83 19.84 310.83 19.84
             
Annual Sum or Average 4541.33 21.37 2047.00 22.01 1112.00 20.11
Minimum of Months 198.67 20.29 47.33 19.84 1.50 19.84
Maximum of Months 514.00 22.63 310.83 24.41 310.83 26.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 464.33 21.03 203.67 20.43 193.83 20.21
February 401.67 21.22 142.00 20.76 120.83 20.14
March 496.67 21.49 89.33 20.52 89.33 20.52
April 320.67 22.25 85.00 23.69 17.17 21.53
May 371.67 22.13 78.17 23.94 7.33 20.64
June 293.00 22.41 134.50 24.15 0.00 0.00
July 249.67 22.41 178.50 24.25 0.50 25.66
August 260.17 22.54 199.17 24.20 3.67 26.20
September 257.50 22.23 194.00 24.24 9.83 23.73
October 401.83 21.65 92.83 22.96 29.67 20.26
November 452.33 21.19 121.33 20.74 105.83 20.15
December 483.00 20.69 257.50 20.03 257.50 20.03
             
Annual Sum or Average 4452.50 21.64 1776.00 22.37 835.50 20.27
Minimum of Months 249.67 20.69 78.17 20.03 0.00 0.00
Maximum of Months 496.67 22.54 257.50 24.25 257.50 26.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.00 20.74 217.83 20.15 217.83 20.15
February 442.50 20.96 128.83 20.10 128.33 20.09
March 505.83 21.32 71.17 20.62 69.83 20.56
April 389.17 22.20 61.50 23.73 9.50 21.39
May 375.83 22.14 87.33 24.33 3.00 24.60
June 267.83 22.45 159.33 24.24 3.83 26.75
July 223.33 22.49 201.00 24.30 9.50 26.49
August 285.00 22.47 147.17 24.15 6.00 26.35
September 373.00 22.02 77.17 24.19 1.67 21.78
October 476.67 21.43 42.00 21.53 27.67 20.19
November 488.17 20.97 120.50 20.15 120.50 20.15
December 497.00 20.50 262.17 20.02 262.17 20.02
             
Annual Sum or Average 4825.33 21.49 1576.00 22.07 859.83 20.31
Minimum of Months 223.33 20.50 42.00 20.02 1.67 20.02
Maximum of Months 505.83 22.49 262.17 24.33 262.17 26.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.51703 27.25782 0.40598 9.02415
February 454.00000 24.49401 28.04391 0.40681 8.89804
March 514.00000 24.41038 27.48707 0.39182 8.64326
April 485.00000 24.53605 27.75155 0.42600 9.36258
May 508.00000 24.48966 33.72559 -0.3974 9.20960
June 496.00000 24.45808 41.87343 -0.3403 8.34903
July 497.00000 24.60837 43.46345 -0.2813 7.82956
August 514.00000 24.47070 44.33950 -0.3074 7.97755
September 485.00000 24.53217 40.83248 -0.3257 8.39652
October 502.00000 24.57951 34.64099 0.48342 10.52240
November 489.00000 24.58432 31.14724 0.45916 10.03360
December 497.00000 24.55242 26.28356 0.41265 9.12551
           
Annual Sum or Average 5943.00000 24.51898 33.95328 0.10808 8.94515
Minimum of Months 454.00000 24.41038 26.28356 -0.3974 7.82956
Maximum of Months 514.00000 24.60837 44.33950 0.48342 10.52240



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.37008 29.61757 0.38600 8.73523
February 454.00000 24.36610 29.31789 0.39025 8.45533
March 514.00000 24.35217 28.66283 0.39684 8.66214
April 485.00000 24.37294 28.75755 0.42029 9.00679
May 508.00000 24.33509 35.26084 -0.4216 9.28012
June 496.00000 24.29115 42.80764 -0.3607 8.17807
July 497.00000 24.34171 44.72585 -0.3238 7.65734
August 514.00000 24.26427 45.05771 -0.3336 7.67516
September 485.00000 24.26372 42.43624 -0.3838 8.51258
October 502.00000 24.44543 35.93889 0.46587 9.97585
November 489.00000 24.46765 32.43605 0.44606 9.62291
December 497.00000 24.45700 27.70324 0.40551 8.90271
           
Annual Sum or Average 5943.00000 24.36034 35.27589 0.08760 8.72161
Minimum of Months 454.00000 24.26372 27.70324 -0.4216 7.65734
Maximum of Months 514.00000 24.46765 45.05771 0.46587 9.97585



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.97608 31.45811 0.27251 6.97759
February 454.00000 23.99712 30.40739 0.27257 6.71493
March 514.00000 24.07160 29.83459 0.29632 6.98539
April 485.00000 24.21445 29.89133 0.34667 7.68541
May 508.00000 24.20730 35.98981 -0.4976 10.52751
June 496.00000 24.19049 43.59262 -0.4332 9.24053
July 497.00000 24.21061 45.70353 -0.4146 8.96650
August 514.00000 24.13166 46.18374 -0.4260 9.06331
September 485.00000 24.12998 43.33926 -0.4598 9.74745
October 502.00000 24.18060 36.98018 0.37409 8.11571
November 489.00000 24.07152 33.83741 0.31506 7.29670
December 497.00000 23.80482 29.45399 0.20744 6.15307
           
Annual Sum or Average 5943.00000 24.09950 36.43880 -0.0151 8.13447
Minimum of Months 454.00000 23.80482 29.45399 -0.4976 6.15307
Maximum of Months 514.00000 24.21445 46.18374 0.37409 10.52751



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.19057 33.10594 -0.2032 8.38920
February 454.00000 22.51082 33.62655 -0.1147 7.21865
March 514.00000 23.08071 32.14851 0.02634 6.13103
April 485.00000 23.71936 31.19694 0.21361 6.49199
May 508.00000 23.81943 37.08950 -0.6439 14.58265
June 496.00000 24.02774 44.22978 -0.4916 10.54480
July 497.00000 24.05781 46.32885 -0.4644 10.06894
August 514.00000 23.98929 46.84210 -0.4800 10.18679
September 485.00000 23.76184 45.10033 -0.6008 13.33158
October 502.00000 23.23014 39.80731 0.12070 6.29465
November 489.00000 22.74440 37.00991 -0.0355 6.64933
December 497.00000 22.02262 32.93708 -0.2501 8.46461
           
Annual Sum or Average 5943.00000 23.26863 38.32184 -0.2453 9.04446
Minimum of Months 454.00000 22.02262 31.19694 -0.6439 6.13103
Maximum of Months 514.00000 24.05781 46.84210 0.21361 14.58265



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.25252 29.81544 0.07422 5.86526
February 454.00000 23.40555 30.19126 0.12095 5.84189
March 514.00000 23.74838 29.14234 0.20899 6.29441
April 485.00000 24.03739 28.70876 0.30708 7.17173
May 508.00000 23.97039 35.05901 -0.5738 12.46501
June 496.00000 24.13855 42.25373 -0.4305 9.23274
July 497.00000 24.22376 44.09346 -0.3778 8.27934
August 514.00000 24.13584 44.56593 -0.4030 8.61784
September 485.00000 23.92851 42.23404 -0.5338 11.42647
October 502.00000 23.82187 36.54375 0.27999 7.00914
November 489.00000 23.66833 33.21149 0.20900 6.37321
December 497.00000 23.42448 28.59999 0.11091 5.71167
           
Annual Sum or Average 5943.00000 23.81593 35.41130 -0.0862 7.87176
Minimum of Months 454.00000 23.25252 28.59999 -0.5738 5.71167
Maximum of Months 514.00000 24.22376 44.56593 0.30708 12.46501



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.35447 30.20509 -0.0980 6.24765
February 454.00000 22.50877 30.85741 -0.0493 6.03584
March 514.00000 22.75428 30.18970 0.01143 5.88985
April 485.00000 23.54664 29.11615 0.25150 7.26448
May 508.00000 23.68557 35.18477 -0.5835 14.42316
June 496.00000 23.71969 43.01599 -0.4903 11.82179
July 497.00000 23.80636 45.01303 -0.4357 10.86856
August 514.00000 23.59287 45.73040 -0.4967 11.98340
September 485.00000 23.54259 42.68218 -0.5641 14.05451
October 502.00000 23.05698 37.68060 0.14305 6.42756
November 489.00000 22.57972 34.54005 -0.0091 5.79030
December 497.00000 22.13463 29.73710 -0.1530 6.19218
           
Annual Sum or Average 5943.00000 23.11083 36.20793 -0.2082 8.94010
Minimum of Months 454.00000 22.13463 29.11615 -0.5835 5.79030
Maximum of Months 514.00000 23.80636 45.73040 0.25150 14.42316



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.72757 29.71913 -0.0090 6.96283
February 454.00000 22.95657 30.10957 0.06204 6.86227
March 514.00000 23.05645 29.79490 0.07368 6.08004
April 485.00000 23.75408 28.76499 0.29252 7.71073
May 508.00000 23.57652 35.52770 -0.6591 15.92094
June 496.00000 23.76466 43.00825 -0.5203 11.74107
July 497.00000 23.86303 44.86997 -0.4539 10.39583
August 514.00000 23.88603 44.91726 -0.4158 9.92440
September 485.00000 23.77020 42.00658 -0.4793 12.24946
October 502.00000 23.42213 36.86100 0.23825 7.45802
November 489.00000 23.08344 33.68478 0.10880 6.65616
December 497.00000 22.55491 29.17744 -0.0600 6.67856
           
Annual Sum or Average 5943.00000 23.37015 35.75178 -0.1545 9.07184
Minimum of Months 454.00000 22.55491 28.76499 -0.6591 6.08004
Maximum of Months 514.00000 23.88603 44.91726 0.29252 15.92094



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.91767 29.04351 0.05505 6.12112
February 454.00000 23.53827 28.86562 0.22311 6.88672
March 514.00000 24.01340 27.75462 0.34695 8.30167
April 485.00000 24.43621 27.37203 0.51952 11.36038
May 508.00000 23.95399 34.48709 -0.4564 11.25696
June 496.00000 24.24839 41.47471 -0.2444 7.59543
July 497.00000 24.43476 43.11939 -0.1364 6.84236
August 514.00000 24.38461 43.35425 -0.1350 6.61234
September 485.00000 23.75029 41.97392 -0.4638 11.17242
October 502.00000 23.93205 35.61522 0.37724 8.84520
November 489.00000 23.98187 31.66348 0.35103 8.41109
December 497.00000 23.97543 26.59653 0.30909 7.75432
           
Annual Sum or Average 5943.00000 23.96682 34.32098 0.06035 8.42795
Minimum of Months 454.00000 22.91767 26.59653 -0.4638 6.12112
Maximum of Months 514.00000 24.43621 43.35425 0.51952 11.36038



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.97277 31.70220 -0.2412 7.59336
February 454.00000 22.08997 32.51614 -0.2020 7.17204
March 514.00000 22.77004 31.39081 -0.0411 6.01537
April 485.00000 23.40564 30.37487 0.13285 6.04665
May 508.00000 23.47705 36.35263 -0.7603 18.42537
June 496.00000 23.83768 43.30547 -0.5623 12.28400
July 497.00000 23.87724 45.23563 -0.5308 11.53600
August 514.00000 23.78681 45.97295 -0.5600 12.12414
September 485.00000 23.47945 43.52660 -0.7087 16.61867
October 502.00000 22.93127 39.05265 0.05447 6.02903
November 489.00000 22.27863 36.03719 -0.1345 6.79564
December 497.00000 21.48204 31.51812 -0.3640 8.86252
           
Annual Sum or Average 5943.00000 22.95605 37.28822 -0.3280 9.98233
Minimum of Months 454.00000 21.48204 30.37487 -0.7603 6.01537
Maximum of Months 514.00000 23.87724 45.97295 0.13285 18.42537



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 21.31753 30.73998 -0.3750 8.53889
February 385.00000 21.46961 31.43464 -0.3228 7.84394
March 433.00000 21.77416 31.11249 -0.2392 6.87717
April 410.00000 23.14469 29.60377 0.13499 6.88672
May 430.00000 23.20101 35.73199 -0.7625 20.60279
June 418.00000 23.40123 43.46405 -0.6166 15.86990
July 422.00000 23.63549 45.13693 -0.5231 14.02000
August 433.00000 23.33734 46.12502 -0.6068 15.43422
September 410.00000 23.12137 43.26366 -0.7278 19.44526
October 427.00000 22.13092 39.06050 -0.0923 6.28220
November 417.00000 21.43680 35.77952 -0.3054 7.54183
December 422.00000 20.94678 30.55160 -0.4790 10.21651
           
Annual Sum or Average 5034.00000 22.41392 36.87326 -0.4110 11.65495
Minimum of Months 385.00000 20.94678 29.60377 -0.7625 6.28220
Maximum of Months 433.00000 23.63549 46.12502 0.13499 20.60279



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.34419 29.77819 -0.1079 7.64366
February 454.00000 22.50104 30.46655 -0.0521 7.60708
March 514.00000 22.42121 30.69500 -0.0834 6.41888
April 485.00000 23.40809 29.44982 0.19947 7.43247
May 508.00000 23.17488 36.32786 -0.7963 20.96275
June 496.00000 23.39035 44.03738 -0.6571 15.80559
July 497.00000 23.53020 45.85553 -0.5845 14.19412
August 514.00000 23.57444 45.93964 -0.5354 13.14955
September 485.00000 23.55866 42.42933 -0.5509 14.91791
October 502.00000 22.95845 37.83728 0.12757 7.29289
November 489.00000 22.38776 34.71564 -0.0640 7.08664
December 497.00000 21.70362 29.96801 -0.2818 8.54265
           
Annual Sum or Average 5943.00000 22.91457 36.51081 -0.2851 10.95475
Minimum of Months 454.00000 21.70362 29.44982 -0.7963 6.41888
Maximum of Months 514.00000 23.57444 45.93964 0.19947 20.96275



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.48485 30.98962 -0.3207 7.92763
February 454.00000 21.73003 31.64185 -0.2422 7.32212
March 514.00000 22.00899 31.12735 -0.1695 6.42719
April 485.00000 23.08450 29.94327 0.13000 6.71514
May 508.00000 23.09592 36.32233 -0.7807 20.99375
June 496.00000 23.47072 43.64120 -0.5685 14.25523
July 497.00000 23.58613 45.55330 -0.5077 13.10862
August 514.00000 23.38029 46.42773 -0.5747 14.09777
September 485.00000 22.89493 44.14654 -0.7915 20.82648
October 502.00000 22.24264 39.32137 -0.0522 6.09834
November 489.00000 21.64715 35.87890 -0.2412 7.02819
December 497.00000 21.11830 30.70811 -0.4228 9.13299
           
Annual Sum or Average 5943.00000 22.48435 37.18709 -0.3802 11.18948
Minimum of Months 454.00000 21.11830 29.94327 -0.7915 6.09834
Maximum of Months 514.00000 23.58613 46.42773 0.13000 20.99375



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.67028 33.12570 -0.6001 15.05839
February 454.00000 20.81982 33.83557 -0.5411 13.55998
March 514.00000 21.59578 32.59701 -0.3421 9.01122
April 485.00000 22.70854 31.50084 -0.0370 6.85608
May 508.00000 22.88178 37.49159 -0.9600 27.07140
June 496.00000 23.51501 44.11262 -0.6647 16.01452
July 497.00000 23.58524 45.93969 -0.6203 14.82615
August 514.00000 23.48003 46.81331 -0.6586 15.60605
September 485.00000 22.88957 44.96571 -0.9085 24.86452
October 502.00000 21.74911 41.44300 -0.2392 7.99376
November 489.00000 21.00964 37.71675 -0.4679 11.73951
December 497.00000 20.36797 32.64813 -0.6823 17.22271
           
Annual Sum or Average 5943.00000 22.11621 38.55380 -0.5609 14.99757
Minimum of Months 454.00000 20.36797 31.50084 -0.9600 6.85608
Maximum of Months 514.00000 23.58524 46.81331 -0.0370 27.07140



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.55611 32.14573 -0.6146 14.68802
February 454.00000 20.74889 32.81680 -0.5398 12.63093
March 514.00000 21.20493 32.01924 -0.4101 9.37974
April 485.00000 22.84850 30.26744 0.06024 7.22146
May 508.00000 22.92137 36.60223 -0.8558 24.22368
June 496.00000 23.28978 44.11032 -0.6430 17.01098
July 497.00000 23.55691 45.66243 -0.5352 14.46628
August 514.00000 23.30871 46.61160 -0.6070 15.83076
September 485.00000 22.95343 44.05572 -0.7902 22.00827
October 502.00000 21.50896 40.93794 -0.2619 7.94810
November 489.00000 20.78179 37.12099 -0.5065 11.68005
December 497.00000 20.29053 31.70733 -0.6953 17.23233
           
Annual Sum or Average 5943.00000 22.00587 37.88110 -0.5342 14.54505
Minimum of Months 454.00000 20.29053 30.26744 -0.8558 7.22146
Maximum of Months 514.00000 23.55691 46.61160 0.06024 24.22368



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.26100 30.97918 -0.4202 11.82204
February 454.00000 21.54223 31.47122 -0.3266 10.63196
March 514.00000 21.56143 31.54501 -0.3211 8.81617
April 485.00000 22.85926 30.26540 0.05987 7.72387
May 508.00000 22.64221 37.28214 -0.9782 28.78012
June 496.00000 23.04493 44.86211 -0.7652 20.12664
July 497.00000 23.23216 46.56691 -0.6752 17.86373
August 514.00000 23.26977 46.75616 -0.6327 16.82688
September 485.00000 23.12506 43.49048 -0.7063 20.94776
October 502.00000 22.12467 39.56734 -0.0956 8.06300
November 489.00000 21.42242 36.01257 -0.3347 9.97471
December 497.00000 20.78241 30.94849 -0.5599 14.27024
           
Annual Sum or Average 5943.00000 22.24276 37.53103 -0.4821 14.69743
Minimum of Months 454.00000 20.78241 30.26540 -0.9782 7.72387
Maximum of Months 514.00000 23.26977 46.75616 0.05987 28.78012



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.74287 31.65338 -0.5528 13.03718
February 454.00000 21.02119 32.20193 -0.4557 11.11945
March 514.00000 21.35733 31.60538 -0.3572 8.64266
April 485.00000 22.54955 30.69624 -0.0027 7.17316
May 508.00000 22.63471 37.13909 -0.9379 27.84150
June 496.00000 23.14430 44.41958 -0.6694 18.07071
July 497.00000 23.31013 46.20814 -0.5909 16.24098
August 514.00000 23.07571 47.23449 -0.6703 17.62211
September 485.00000 22.47024 45.16162 -0.9400 27.26095
October 502.00000 21.55019 40.69964 -0.2402 7.48508
November 489.00000 20.96720 36.61354 -0.4455 10.33973
December 497.00000 20.50390 31.15674 -0.6264 14.60358
           
Annual Sum or Average 5943.00000 21.95094 37.94528 -0.5421 14.98291
Minimum of Months 454.00000 20.50390 30.69624 -0.9400 7.17316
Maximum of Months 514.00000 23.31013 47.23449 -0.0027 27.84150



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

CHILLER ELECTRIC ENERGY [J] CHILLER ELECTRIC POWER {Maximum}[W] CHILLER ELECTRIC POWER {TIMESTAMP} CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum}[W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 51251234.65 1934.76 30-JAN-06:20 7.41 0.159271E+09 0.00 0.210522E+09 0.03 3.15 10-JAN-07:00 0.00 0.00
February 28174049.71 1934.37 17-FEB-06:07 4.08 87712773.91 0.00 0.115887E+09 0.02 3.16 13-FEB-06:30 0.00 0.00
March 67872318.47 1990.00 18-MAR-05:02 9.80 0.210672E+09 0.00 0.278544E+09 0.04 3.14 07-MAR-06:50 0.00 0.00
April 0.995060E+10 79234.38 28-APR-14:40 89.82 0.577757E+11 0.00 0.677263E+11 0.59 7.15 28-APR-14:40 0.00 0.00
May 0.119552E+11 81175.87 22-MAY-14:30 92.63 0.687509E+11 0.00 0.807061E+11 0.60 7.14 22-MAY-15:40 0.00 0.00
June 0.323156E+11 107708.90 13-JUN-16:00 234.65 0.189765E+12 0.00 0.222081E+12 1.60 7.15 12-JUN-11:30 0.00 0.00
July 0.542581E+11 95665.49 21-JUL-16:00 380.63 0.326865E+12 0.00 0.381123E+12 2.64 7.15 24-JUL-16:40 0.00 0.00
August 0.696090E+11 85177.80 14-AUG-16:00 438.95 0.434207E+12 0.00 0.503816E+12 3.29 7.15 10-AUG-13:40 0.00 0.00
September 0.394036E+11 87276.31 22-SEP-12:40 290.89 0.233407E+12 0.00 0.272810E+12 2.04 7.16 22-SEP-15:50 0.00 0.00
October 0.437811E+10 53854.53 06-OCT-15:30 54.89 0.215851E+11 0.00 0.259632E+11 0.30 6.74 06-OCT-15:30 0.00 0.00
November 0.201135E+09 35517.85 24-NOV-12:00 9.03 0.677585E+09 0.00 0.878721E+09 0.04 4.68 24-NOV-12:00 0.00 0.00
December 59962474.55 1935.07 15-DEC-06:02 8.66 0.186077E+09 0.00 0.246039E+09 0.04 3.15 26-DEC-06:30 0.00 0.00
                         
Annual Sum or Average 0.222279E+12     1621.43 0.133368E+13   0.155596E+13 0.94        
Minimum of Months 28174049.71 1934.37   4.08 87712773.91 0.00 0.115887E+09 0.02 3.14   0.00 0.00
Maximum of Months 0.696090E+11 107708.90   438.95 0.434207E+12 0.00 0.503816E+12 3.29 7.16   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

CHILLER ELECTRIC ENERGY [J] CHILLER ELECTRIC POWER {Maximum}[W] CHILLER ELECTRIC POWER {TIMESTAMP} CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum}[W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 94112298.75 79234.38 28-APR-14:40 0.35 0.669710E+09 0.00 0.763822E+09 0.00 7.15 28-APR-14:40 0.00 0.00
May 0.844427E+09 81175.87 22-MAY-14:30 3.17 0.599180E+10 0.00 0.683623E+10 0.03 7.14 22-MAY-15:40 0.00 0.00
June 0.623968E+10 107708.90 13-JUN-16:00 21.55 0.430574E+11 0.00 0.492971E+11 0.21 7.15 25-JUN-15:53 0.00 0.00
July 0.571764E+10 95665.49 21-JUL-16:00 20.87 0.404109E+11 0.00 0.461286E+11 0.20 7.14 10-JUL-10:30 0.00 0.00
August 0.649556E+10 85177.80 14-AUG-16:00 23.83 0.459056E+11 0.00 0.524012E+11 0.23 7.14 14-AUG-16:40 0.00 0.00
September 0.400026E+10 80716.72 12-SEP-15:40 15.00 0.283726E+11 0.00 0.323729E+11 0.15 7.12 12-SEP-15:40 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.233917E+11     84.77 0.164408E+12   0.187800E+12 0.07        
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.649556E+10 107708.90   23.83 0.459056E+11 0.00 0.524012E+11 0.23 7.15   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING TOWER FAN ELECTRIC ENERGY [J] COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.119956E+11 744.00 26072.02 25-JAN-22:20 533212.79 21-JAN-03:51 21.73 18.33 13.86
February 0.172027E+11 672.00 22054.87 07-FEB-05:42 576487.17 04-FEB-21:01 24.52 18.33 13.86
March 0.428204E+11 744.00 44634.08 25-MAR-13:00 593035.78 22-MAR-21:20 27.34 18.33 13.86
April 0.821728E+11 720.00 49248.27 15-APR-13:40 661240.44 30-APR-19:12 30.69 18.74 13.86
May 0.277136E+11 744.00 49248.27 11-MAY-15:00 538490.61 11-MAY-21:51 22.04 18.45 13.86
June 0.782669E+11 720.00 49248.27 01-JUN-12:00 582791.35 05-JUN-21:17 25.43 19.00 13.86
July 0.114347E+12 744.00 49248.27 01-JUL-12:50 597328.75 03-JUL-21:12 29.32 20.04 13.86
August 0.126448E+12 744.00 49248.27 01-AUG-06:20 644832.63 20-AUG-17:11 33.17 21.05 13.86
September 0.538013E+11 720.00 49248.27 01-SEP-09:50 535200.41 20-SEP-21:20 22.40 18.78 13.86
October 0.439493E+11 744.00 49248.27 05-OCT-14:00 580351.19 21-OCT-20:51 24.65 18.35 13.86
November 0.465583E+11 720.00 49248.27 24-NOV-11:30 592394.06 01-NOV-21:30 27.33 18.33 13.86
December 0.516248E+11 744.00 46231.08 23-DEC-11:00 610363.33 12-DEC-22:43 30.04 18.33 13.86
                   
Annual Sum or Average 0.696901E+12 8760.00         26.57 18.84 13.86
Minimum of Months 0.119956E+11 672.00 22054.87   533212.79   21.73 18.33 13.86
Maximum of Months 0.126448E+12 744.00 49248.27   661240.44   33.17 21.05 13.86



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING TOWER FAN ELECTRIC ENERGY [J] COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 140156.53 12-JAN-05:20 21.03 21.03 0.05
February 0.00 0.00 0.00 01-FEB-00:10 140334.50 17-FEB-06:15 21.04 21.04 0.02
March 0.00 0.00 0.00 01-MAR-00:10 140166.18 08-MAR-06:40 21.02 21.01 0.10
April 0.308321E+09 57.53 5251.45 28-APR-14:40 650482.41 28-APR-14:40 21.23 21.06 3.86
May 0.594065E+09 69.17 15130.87 22-MAY-14:40 685461.72 22-MAY-14:40 21.27 21.08 4.48
June 0.256474E+10 177.70 15130.87 12-JUN-12:20 823642.45 13-JUN-16:00 21.70 21.17 12.07
July 0.425225E+10 306.68 15130.87 10-JUL-09:30 768328.21 21-JUL-16:00 22.03 21.16 19.28
August 0.497021E+10 380.79 15130.87 08-AUG-13:00 703711.97 14-AUG-16:00 22.32 21.17 22.88
September 0.238653E+10 225.08 15130.87 11-SEP-13:50 684838.39 11-SEP-13:50 21.84 21.20 14.96
October 44730277.69 26.07 1739.24 11-OCT-15:00 428192.78 06-OCT-15:30 21.20 21.14 2.18
November 1228920.51 1.00 687.08 24-NOV-12:00 203846.68 24-NOV-12:00 20.97 20.97 0.14
December 0.00 0.00 0.00 01-DEC-00:10 139708.13 15-DEC-06:02 21.00 21.00 0.06
                   
Annual Sum or Average 0.151221E+11 1244.02         21.39 21.09 6.71
Minimum of Months 0.00 0.00 0.00   139708.13   20.97 20.97 0.02
Maximum of Months 0.497021E+10 380.79 15130.87   823642.45   22.32 21.20 22.88



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING TOWER FAN ELECTRIC ENERGY [J] COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.03 21.03 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.04 21.04 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.02 21.02 0.00
April 6326437.22 0.37 5251.45 28-APR-14:40 650482.41 28-APR-14:40 21.23 21.22 0.02
May 0.124270E+09 3.17 15130.87 22-MAY-14:40 685461.72 22-MAY-14:40 21.27 21.25 0.17
June 0.109836E+10 21.78 15130.87 12-JUN-12:20 823642.45 13-JUN-16:00 21.70 21.58 1.23
July 0.102862E+10 20.87 15130.87 10-JUL-09:30 768328.21 21-JUL-16:00 22.03 21.93 1.14
August 0.108065E+10 23.83 15130.87 14-AUG-10:00 703711.97 14-AUG-16:00 22.32 22.20 1.30
September 0.579759E+09 15.00 15130.87 11-SEP-13:50 684838.39 11-SEP-13:50 21.84 21.77 0.85
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 21.20 21.20 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.97 20.97 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.00 21.00 0.00
                   
Annual Sum or Average 0.391798E+10 85.01         21.39 21.35 0.39
Minimum of Months 0.00 0.00 0.00   0.00   20.97 20.97 0.00
Maximum of Months 0.109836E+10 23.83 15130.87   823642.45   22.32 22.20 1.30



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum}[W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRIC POWER [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum}[] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.419920E+12 0.00 416.54 923581.36 10-JAN-21:17 0.00 66.25 74.31 2.55 0.00 0.11 0.64 10-JAN-21:17
February 0.326101E+12 0.00 368.81 793948.01 17-FEB-07:20 0.00 65.15 73.83 2.02 0.00 0.09 0.55 17-FEB-07:20
March 0.285781E+12 0.00 416.89 730253.67 26-MAR-23:40 0.00 61.89 72.96 1.34 0.00 0.07 0.51 26-MAR-23:40
April 0.101979E+12 0.00 222.16 1696838.90 30-APR-19:16 0.00 57.67 65.02 0.42 0.00 0.03 1.18 30-APR-19:16
May 0.855547E+11 0.00 233.51 1044547.33 24-MAY-03:47 0.00 62.70 67.05 0.60 0.00 0.02 0.72 24-MAY-03:47
June 0.228974E+11 0.00 102.55 849894.18 10-JUN-03:47 0.00 54.08 57.89 0.09 0.00 0.01 0.59 10-JUN-03:47
July 0.669685E+10 0.00 47.78 784887.45 02-JUL-16:30 0.00 60.35 61.83 0.03 0.00 0.00 0.54 02-JUL-16:30
August 0.366118E+10 0.00 30.73 791457.16 06-AUG-15:30 0.00 59.98 60.98 0.02 0.00 0.00 0.55 06-AUG-15:30
September 0.262519E+11 0.00 129.48 969902.25 04-SEP-06:10 0.00 55.85 60.08 0.14 0.00 0.01 0.67 04-SEP-06:10
October 0.126427E+12 0.00 309.01 609486.41 09-OCT-07:30 0.00 60.00 68.10 0.58 0.00 0.03 0.42 09-OCT-07:30
November 0.255078E+12 0.00 377.15 883434.54 29-NOV-07:10 0.00 61.09 71.73 1.23 0.00 0.07 0.61 29-NOV-07:10
December 0.449031E+12 0.00 414.76 1086355.14 30-DEC-07:10 0.00 62.42 74.15 2.19 0.00 0.12 0.75 30-DEC-07:10
                           
Annual Sum or Average 0.210938E+13   3069.37       60.62 67.32 0.93 0.00 0.05    
Minimum of Months 0.366118E+10 0.00 30.73 609486.41   0.00 54.08 57.89 0.02 0.00 0.00 0.42  
Maximum of Months 0.449031E+12 0.00 416.89 1696838.90   0.00 66.25 74.31 2.55 0.00 0.12 1.18  



Table of Contents

Report: BoilerReportMonthly

For: DUMMY BOILER

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum}[W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRIC POWER [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.73 21.73 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 24.52 24.52 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 27.34 27.34 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 30.69 30.69 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 22.04 22.04 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 25.43 25.43 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 29.32 29.32 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:10 0.00 33.17 33.17 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 22.40 22.40 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 24.65 24.65 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 27.33 27.33 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.04 30.04 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00   0.00       26.57 26.57 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.73 21.73 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 33.17 33.17 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRIC POWER [] COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 531036.36 0.00 0.05 531036.36 0.00 0.00 0.00 0.00 3728.45 20-FEB-15:01 3728.45 20-FEB-15:01 0.00 0.00 0.00
March 2423267.48 0.00 0.16 1314127.70 0.00 0.00 0.00 0.00 8108.83 18-MAR-05:02 3690.37 18-MAR-05:02 0.00 0.00 0.00
April 0.929681E+09 0.00 22.22 0.929681E+09 0.00 0.00 0.00 0.00 93594.14 30-APR-18:51 93594.14 30-APR-18:51 0.00 0.00 0.00
May 0.265793E+10 0.00 35.83 0.265576E+10 0.00 0.00 0.00 0.00 61883.62 22-MAY-15:00 61883.62 22-MAY-15:00 0.00 0.00 0.00
June 0.914233E+10 0.00 97.33 0.897537E+10 0.00 0.00 0.00 0.00 141711.65 25-JUN-17:52 65285.46 25-JUN-17:50 0.00 0.00 0.00
July 0.152393E+11 0.00 192.38 0.148857E+11 0.00 0.00 0.00 0.00 94429.55 23-JUL-16:21 72546.08 09-JUL-16:00 0.00 0.00 0.00
August 0.196218E+11 0.00 266.14 0.194052E+11 0.00 0.00 0.00 0.00 83134.36 13-AUG-15:50 76348.18 20-AUG-14:30 0.00 0.00 0.00
September 0.960111E+10 0.00 136.99 0.951649E+10 0.00 0.00 0.00 0.00 76368.93 10-SEP-19:01 62051.19 24-SEP-17:41 0.00 0.00 0.00
October 0.415902E+09 0.00 14.27 0.302909E+09 0.00 0.00 0.00 0.00 55872.47 08-OCT-16:11 29621.78 08-OCT-16:11 0.00 0.00 0.00
November 41798667.35 0.00 1.64 36866379.97 0.00 0.00 0.00 0.00 29989.42 09-NOV-04:01 23097.66 15-NOV-04:01 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.576528E+11   767.01 0.567098E+11                      
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.196218E+11 0.00 266.14 0.194052E+11 0.00 0.00 0.00 0.00 141711.65   93594.14   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRIC POWER [] COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 1128.38 0.00 0.89 1128.38 0.00 0.00 0.00 0.00 0.82 30-JAN-05:50 0.82 30-JAN-05:50 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00
March 3778.63 0.00 2.35 3778.63 0.00 0.00 0.00 0.00 0.95 20-MAR-03:47 0.95 20-MAR-03:47 0.00 0.00 0.00
April 0.578384E+10 0.00 67.72 0.575537E+10 0.00 0.00 0.00 0.00 66601.65 28-APR-15:00 66601.65 28-APR-15:00 0.00 0.00 0.00
May 0.693479E+10 0.00 80.81 0.693479E+10 0.00 0.00 0.00 0.00 87858.94 22-MAY-15:00 87858.94 22-MAY-15:00 0.00 0.00 0.00
June 0.224723E+11 0.00 214.52 0.208127E+11 0.00 0.00 0.00 0.00 119168.19 26-JUN-15:50 107524.92 13-JUN-16:00 0.00 0.00 0.00
July 0.381863E+11 0.00 353.53 0.364073E+11 0.00 0.00 0.00 0.00 113213.48 21-JUL-16:00 113213.48 21-JUL-16:00 0.00 0.00 0.00
August 0.508987E+11 0.00 418.64 0.478204E+11 0.00 0.00 0.00 0.00 114685.42 14-AUG-13:00 111597.06 14-AUG-16:00 0.00 0.00 0.00
September 0.246417E+11 0.00 259.17 0.238689E+11 0.00 0.00 0.00 0.00 94284.12 12-SEP-14:00 82171.15 13-SEP-14:40 0.00 0.00 0.00
October 0.193770E+10 0.00 41.87 0.193770E+10 0.00 0.00 0.00 0.00 33623.71 11-OCT-15:00 33623.71 11-OCT-15:00 0.00 0.00 0.00
November 59234398.59 0.00 2.17 59234398.59 0.00 0.00 0.00 0.00 19514.27 24-NOV-12:00 19514.27 24-NOV-12:00 0.00 0.00 0.00
December 27.44 0.00 0.02 27.44 0.00 0.00 0.00 0.00 0.46 30-DEC-06:09 0.46 30-DEC-06:09 0.00 0.00 0.00
                               
Annual Sum or Average 0.150915E+12   1441.69 0.143596E+12                      
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.508987E+11 0.00 418.64 0.478204E+11 0.00 0.00 0.00 0.00 119168.19   113213.48   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRIC POWER [] COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 23905.69 0.00 6.36 23905.69 0.00 0.00 0.00 0.00 3.77 30-JAN-06:02 3.77 30-JAN-06:02 0.00 0.00 0.00
February 7086.85 0.00 4.03 7086.85 0.00 0.00 0.00 0.00 2.97 19-FEB-15:48 2.97 19-FEB-15:48 0.00 0.00 0.00
March 31410.90 0.00 7.57 31410.90 0.00 0.00 0.00 0.00 5.85 20-MAR-05:04 5.85 20-MAR-05:04 0.00 0.00 0.00
April 0.473147E+11 0.00 80.15 0.471164E+11 0.00 0.00 0.00 0.00 568225.99 28-APR-15:00 568225.99 28-APR-15:00 0.00 0.00 0.00
May 0.599592E+11 0.00 86.64 0.599592E+11 0.00 0.00 0.00 0.00 766470.07 22-MAY-15:00 766470.07 22-MAY-15:00 0.00 0.00 0.00
June 0.185581E+12 0.00 209.94 0.172204E+12 0.00 0.00 0.00 0.00 1075449.70 13-JUN-16:00 969740.23 13-JUN-16:00 0.00 0.00 0.00
July 0.301755E+12 0.00 333.36 0.289105E+12 0.00 0.00 0.00 0.00 1011179.15 21-JUL-16:00 1011179.15 21-JUL-16:00 0.00 0.00 0.00
August 0.397839E+12 0.00 393.47 0.375437E+12 0.00 0.00 0.00 0.00 907213.91 14-AUG-16:00 907213.91 14-AUG-16:00 0.00 0.00 0.00
September 0.216078E+12 0.00 268.95 0.209623E+12 0.00 0.00 0.00 0.00 853718.53 12-SEP-14:00 764822.90 13-SEP-14:50 0.00 0.00 0.00
October 0.161656E+11 0.00 51.00 0.161656E+11 0.00 0.00 0.00 0.00 282792.18 06-OCT-15:00 282792.18 06-OCT-15:00 0.00 0.00 0.00
November 0.355713E+09 0.00 8.22 0.355713E+09 0.00 0.00 0.00 0.00 129120.95 24-NOV-12:00 129120.95 24-NOV-12:00 0.00 0.00 0.00
December 22770.01 0.00 8.64 22770.01 0.00 0.00 0.00 0.00 1.71 15-DEC-06:01 1.71 15-DEC-06:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.122505E+13   1458.32 0.116997E+13                      
Minimum of Months 7086.85 0.00 4.03 7086.85 0.00 0.00 0.00 0.00 1.71   1.71   0.00 0.00 0.00
Maximum of Months 0.397839E+12 0.00 393.47 0.375437E+12 0.00 0.00 0.00 0.00 1075449.70   1011179.15   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRIC POWER [] COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 399.61 0.00 0.33 399.61 0.00 0.00 0.00 0.00 0.34 01-JAN-22:11 0.34 01-JAN-22:11 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00
March 159.16 0.00 0.17 159.16 0.00 0.00 0.00 0.00 0.27 27-MAR-06:00 0.27 27-MAR-06:00 0.00 0.00 0.00
April 0.477986E+10 0.00 60.73 0.476760E+10 0.00 0.00 0.00 0.00 62144.91 28-APR-15:20 62144.91 28-APR-15:20 0.00 0.00 0.00
May 0.644877E+10 0.00 78.00 0.644877E+10 0.00 0.00 0.00 0.00 89051.33 22-MAY-15:00 89051.33 22-MAY-15:00 0.00 0.00 0.00
June 0.203720E+11 0.00 197.48 0.187756E+11 0.00 0.00 0.00 0.00 133990.31 13-JUN-15:10 119155.62 13-JUN-16:00 0.00 0.00 0.00
July 0.321775E+11 0.00 313.34 0.307076E+11 0.00 0.00 0.00 0.00 121459.54 21-JUL-16:00 121459.54 21-JUL-16:00 0.00 0.00 0.00
August 0.401524E+11 0.00 378.89 0.378882E+11 0.00 0.00 0.00 0.00 108314.19 14-AUG-16:00 108314.19 14-AUG-16:00 0.00 0.00 0.00
September 0.204930E+11 0.00 237.75 0.198651E+11 0.00 0.00 0.00 0.00 91653.12 12-SEP-14:00 82143.54 13-SEP-15:00 0.00 0.00 0.00
October 0.133845E+10 0.00 37.83 0.133845E+10 0.00 0.00 0.00 0.00 25663.22 07-OCT-15:00 25663.22 07-OCT-15:00 0.00 0.00 0.00
November 24264352.54 0.00 1.50 24264352.54 0.00 0.00 0.00 0.00 9106.80 24-NOV-12:00 9106.80 24-NOV-12:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.125786E+12   1306.03 0.119816E+12                      
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.401524E+11 0.00 378.89 0.378882E+11 0.00 0.00 0.00 0.00 133990.31   121459.54   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum}[W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRIC POWER {Maximum}[W] COOLING COIL ELECTRIC POWER {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.312016E+12 0.791783E+11 738.04 0.311981E+12 34316143.14 0.00 1.00 03-JAN-22:20 0.01 14-JAN-18:30 425385.92 06-JAN-22:42 425385.92 06-JAN-22:42 19092.45 06-JAN-23:10 90480.16 06-JAN-22:42 0.00
February 0.493281E+12 0.117595E+12 670.17 0.493251E+12 29962248.16 0.00 1.00 03-FEB-05:17 0.02 25-FEB-18:15 435908.28 16-FEB-23:10 435908.28 16-FEB-23:10 25518.13 04-FEB-18:40 90660.61 16-FEB-23:10 0.00
March 0.782533E+12 0.178959E+12 743.87 0.782526E+12 6403541.51 0.00 1.00 01-MAR-22:40 0.04 02-MAR-00:32 423883.87 15-MAR-03:40 423883.87 15-MAR-03:40 6082.63 13-MAR-22:30 90454.40 15-MAR-03:40 0.00
April 0.989840E+12 0.221693E+12 720.00 0.989840E+12 0.00 0.00 1.00 03-APR-21:10 0.76 26-APR-03:43 417385.79 30-APR-03:53 417385.79 30-APR-03:53 0.00 01-APR-00:10 117191.02 30-APR-18:33 0.00
May 0.316290E+12 0.801573E+11 738.34 0.316210E+12 79841528.11 0.00 1.00 01-MAY-03:25 0.01 03-MAY-00:38 426074.82 17-MAY-22:37 424311.21 17-MAY-23:16 25988.12 17-MAY-23:45 90491.97 17-MAY-22:37 0.00
June 0.534345E+12 0.128874E+12 718.56 0.533675E+12 0.669405E+09 0.00 1.00 05-JUN-21:13 0.01 06-JUN-03:21 437270.47 05-JUN-21:17 437270.47 05-JUN-21:17 24213.45 18-JUN-22:30 90683.97 05-JUN-21:17 0.00
July 0.789996E+12 0.188427E+12 743.97 0.788864E+12 0.113228E+10 0.00 1.00 03-JUL-21:08 0.02 31-JUL-03:14 431832.68 31-JUL-02:36 431832.68 31-JUL-02:36 21637.01 31-JUL-03:13 106719.96 22-JUL-18:00 0.00
August 0.102625E+13 0.243669E+12 744.00 0.102542E+13 0.826352E+09 0.00 1.00 03-AUG-03:40 0.82 20-AUG-05:30 426162.57 20-AUG-03:23 426162.57 20-AUG-03:23 6847.89 20-AUG-03:35 124826.41 14-AUG-17:20 0.00
September 0.308065E+12 0.775674E+11 719.28 0.307480E+12 0.585130E+09 0.00 1.00 19-SEP-21:07 0.03 20-SEP-21:23 423014.51 19-SEP-21:13 423014.51 19-SEP-21:13 20636.62 19-SEP-23:35 90439.49 19-SEP-21:13 0.00
October 0.551497E+12 0.131518E+12 740.92 0.551374E+12 0.122986E+09 0.00 1.00 02-OCT-21:17 0.04 06-OCT-22:12 438950.62 13-OCT-21:17 438950.62 13-OCT-21:17 28030.69 21-OCT-18:30 90712.79 13-OCT-21:17 0.00
November 0.760182E+12 0.173351E+12 719.91 0.760105E+12 77232822.11 0.00 1.00 01-NOV-21:10 0.06 21-NOV-22:40 430128.13 14-NOV-02:37 430128.13 14-NOV-02:37 21478.72 23-NOV-16:55 90561.48 14-NOV-02:37 0.00
December 0.101957E+13 0.225223E+12 744.00 0.101957E+13 0.00 0.00 1.00 02-DEC-18:40 0.80 12-DEC-05:25 416617.99 02-DEC-19:20 416617.99 02-DEC-19:20 0.00 01-DEC-00:10 90329.79 02-DEC-19:20 0.00
                                       
Annual Sum or Average 0.788386E+13 0.184621E+13 8741.04 0.788030E+13 0.356390E+10                            
Minimum of Months 0.308065E+12 0.775674E+11 670.17 0.307480E+12 0.00 0.00 1.00   0.01   416617.99   416617.99   0.00   90329.79   0.00
Maximum of Months 0.102625E+13 0.243669E+12 744.00 0.102542E+13 0.113228E+10 0.00 1.00   0.82   438950.62   438950.62   28030.69   124826.41   0.00



Table of Contents

Report: DXReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum}[W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRIC POWER {Maximum}[W] COOLING COIL ELECTRIC POWER {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.486237E+10 0.128443E+10 744.00 0.486237E+10 0.00 0.00 0.32 19-JAN-16:20 0.20 14-JAN-18:17 2389.75 19-JAN-16:20 2389.75 19-JAN-16:20 0.00 01-JAN-00:05 616.75 19-JAN-16:20 0.00
February 0.906990E+10 0.225062E+10 672.00 0.906990E+10 0.00 0.00 0.57 27-FEB-17:00 0.44 25-FEB-18:12 4489.01 27-FEB-17:00 4489.01 27-FEB-17:00 0.00 01-FEB-00:10 1094.97 27-FEB-17:00 0.00
March 0.151550E+11 0.359184E+10 744.00 0.151550E+11 0.00 0.00 0.76 23-MAR-17:30 0.66 04-MAR-18:13 6275.91 23-MAR-17:30 6275.91 23-MAR-17:30 0.00 01-MAR-00:10 1469.17 23-MAR-17:30 0.00
April 0.197063E+11 0.456241E+10 720.00 0.197063E+11 0.00 0.00 1.00 27-APR-17:40 0.86 01-APR-07:00 8244.26 27-APR-18:00 8244.26 27-APR-18:00 0.00 01-APR-00:10 2506.93 30-APR-18:22 0.00
May 0.554193E+10 0.145487E+10 744.00 0.554193E+10 0.00 0.00 0.37 21-MAY-18:23 0.24 06-MAY-07:00 2704.31 21-MAY-18:34 2704.31 21-MAY-18:34 0.00 01-MAY-00:05 764.02 21-MAY-18:02 0.00
June 0.102956E+11 0.260351E+10 720.00 0.102956E+11 0.00 0.00 0.59 12-JUN-18:30 0.47 01-JUN-06:00 4571.01 11-JUN-18:45 4571.01 11-JUN-18:45 0.00 01-JUN-00:10 1493.13 13-JUN-17:00 0.00
July 0.155887E+11 0.391516E+10 744.00 0.155887E+11 0.00 0.00 0.87 22-JUL-18:35 0.67 01-JUL-07:00 6585.09 09-JUL-18:50 6585.09 09-JUL-18:50 0.00 01-JUL-00:10 2377.70 22-JUL-18:35 0.00
August 0.204171E+11 0.511352E+10 744.00 0.204171E+11 0.00 0.00 1.00 13-AUG-17:42 0.88 12-AUG-06:40 8312.84 20-AUG-17:52 8312.84 20-AUG-17:52 0.00 01-AUG-00:10 2666.72 14-AUG-17:40 0.00
September 0.534083E+10 0.142203E+10 720.00 0.534083E+10 0.00 0.00 0.36 12-SEP-17:10 0.23 16-SEP-17:20 2639.60 12-SEP-17:20 2639.60 12-SEP-17:20 0.00 01-SEP-00:10 800.06 13-SEP-17:00 0.00
October 0.103042E+11 0.255114E+10 744.00 0.103042E+11 0.00 0.00 0.56 03-OCT-16:40 0.45 28-OCT-17:13 4452.00 03-OCT-16:40 4452.00 03-OCT-16:40 0.00 01-OCT-00:10 1096.49 06-OCT-16:00 0.00
November 0.146475E+11 0.346950E+10 720.00 0.146475E+11 0.00 0.00 0.73 03-NOV-16:00 0.66 29-NOV-08:00 6052.24 03-NOV-16:00 6052.24 03-NOV-16:00 0.00 01-NOV-00:10 1430.55 24-NOV-12:00 0.00
December 0.199021E+11 0.455759E+10 744.00 0.199021E+11 0.00 0.00 0.92 25-DEC-14:58 0.85 30-DEC-18:13 7810.50 25-DEC-14:58 7810.50 25-DEC-14:58 0.00 01-DEC-00:10 1776.36 25-DEC-14:58 0.00
                                       
Annual Sum or Average 0.150832E+12 0.367766E+11 8760.00 0.150832E+12 0.00                            
Minimum of Months 0.486237E+10 0.128443E+10 672.00 0.486237E+10 0.00 0.00 0.32   0.20   2389.75   2389.75   0.00   616.75   0.00
Maximum of Months 0.204171E+11 0.511352E+10 744.00 0.204171E+11 0.00 0.00 1.00   0.88   8312.84   8312.84   0.00   2666.72   0.00



Table of Contents

Report: DXReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum}[W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRIC POWER {Maximum}[W] COOLING COIL ELECTRIC POWER {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.342389E+11 0.927059E+10 744.00 0.342389E+11 0.00 0.00 0.30 19-JAN-16:30 0.13 11-JAN-06:15 21647.99 19-JAN-16:30 21647.99 19-JAN-16:30 0.00 01-JAN-00:05 5611.86 19-JAN-16:30 0.00
February 0.754440E+11 0.189657E+11 672.00 0.754440E+11 0.00 0.00 0.55 27-FEB-17:00 0.37 26-FEB-07:50 41292.60 27-FEB-17:00 41292.60 27-FEB-17:00 0.00 01-FEB-00:10 10112.44 27-FEB-17:00 0.00
March 0.133721E+12 0.319878E+11 744.00 0.133721E+12 0.00 0.00 0.75 23-MAR-17:30 0.59 04-MAR-18:20 58951.23 23-MAR-17:30 58951.23 23-MAR-17:30 0.00 01-MAR-00:10 13829.09 23-MAR-17:30 0.00
April 0.182476E+12 0.424345E+11 720.00 0.182476E+12 0.00 0.00 1.00 27-APR-17:50 0.83 01-APR-07:00 78678.39 27-APR-17:50 78678.39 27-APR-17:50 0.00 01-APR-00:10 23930.16 30-APR-18:32 0.00
May 0.467753E+11 0.124039E+11 744.00 0.467753E+11 0.00 0.00 0.36 21-MAY-18:23 0.19 05-MAY-06:00 25517.01 21-MAY-18:27 25517.01 21-MAY-18:27 0.00 01-MAY-00:05 7215.37 21-MAY-18:12 0.00
June 0.938293E+11 0.238480E+11 720.00 0.938293E+11 0.00 0.00 0.59 13-JUN-18:30 0.44 08-JUN-06:30 42805.30 11-JUN-18:50 42805.30 11-JUN-18:50 0.00 01-JUN-00:10 14186.22 13-JUN-17:00 0.00
July 0.144765E+12 0.365000E+11 744.00 0.144765E+12 0.00 0.00 0.86 22-JUL-18:35 0.64 01-JUL-07:00 61658.58 09-JUL-18:46 61658.58 09-JUL-18:46 0.00 01-JUL-00:10 22408.40 22-JUL-18:35 0.00
August 0.191328E+12 0.480579E+11 744.00 0.191328E+12 0.00 0.00 1.00 14-AUG-15:10 0.85 12-AUG-06:50 77379.34 04-AUG-18:10 77379.34 04-AUG-18:10 0.00 01-AUG-00:10 25460.80 14-AUG-17:40 0.00
September 0.449223E+11 0.120921E+11 720.00 0.449223E+11 0.00 0.00 0.35 12-SEP-17:10 0.18 16-SEP-17:13 24978.90 12-SEP-17:20 24978.90 12-SEP-17:20 0.00 01-SEP-00:10 7557.65 13-SEP-17:00 0.00
October 0.884013E+11 0.221138E+11 744.00 0.884013E+11 0.00 0.00 0.55 03-OCT-16:50 0.39 28-OCT-17:25 41741.34 03-OCT-16:50 41741.34 03-OCT-16:50 0.00 01-OCT-00:10 10277.24 06-OCT-16:00 0.00
November 0.126901E+12 0.304022E+11 720.00 0.126901E+12 0.00 0.00 0.72 10-NOV-16:20 0.58 19-NOV-08:70 56335.29 03-NOV-16:00 56335.29 03-NOV-16:00 0.00 01-NOV-00:10 13238.51 03-NOV-16:00 0.00
December 0.172839E+12 0.400923E+11 744.00 0.172839E+12 0.00 0.00 0.88 21-DEC-15:20 0.76 31-DEC-06:40 71364.61 21-DEC-15:20 71364.61 21-DEC-15:20 0.00 01-DEC-00:10 16292.22 21-DEC-15:20 0.00
                                       
Annual Sum or Average 0.133564E+13 0.328169E+12 8760.00 0.133564E+13 0.00                            
Minimum of Months 0.342389E+11 0.927059E+10 672.00 0.342389E+11 0.00 0.00 0.30   0.13   21647.99   21647.99   0.00   5611.86   0.00
Maximum of Months 0.191328E+12 0.480579E+11 744.00 0.191328E+12 0.00 0.00 1.00   0.85   78678.39   78678.39   0.00   25460.80   0.00



Table of Contents

Report: DXReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum}[W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRIC POWER {Maximum}[W] COOLING COIL ELECTRIC POWER {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.145725E+10 0.410863E+09 501.39 0.145725E+10 0.00 0.00 0.29 19-JAN-16:30 0.00 01-JAN-00:05 2089.09 19-JAN-16:30 2089.09 19-JAN-16:30 0.00 01-JAN-00:05 543.94 19-JAN-16:30 0.00
February 0.583326E+10 0.149882E+10 672.00 0.583326E+10 0.00 0.00 0.52 24-FEB-17:00 0.15 20-FEB-08:25 3965.15 17-FEB-17:00 3965.15 17-FEB-17:00 0.00 01-FEB-00:10 973.84 24-FEB-17:00 0.00
March 0.119619E+11 0.290117E+10 744.00 0.119619E+11 0.00 0.00 0.74 23-MAR-17:30 0.44 06-MAR-04:55 5855.97 23-MAR-17:30 5855.97 23-MAR-17:30 0.00 01-MAR-00:10 1377.78 23-MAR-17:30 0.00
April 0.175084E+11 0.410546E+10 720.00 0.175084E+11 0.00 0.00 1.00 30-APR-16:42 0.72 09-APR-06:50 7948.65 27-APR-17:50 7948.65 27-APR-17:50 0.00 01-APR-00:10 2433.38 30-APR-18:22 0.00
May 0.402909E+10 0.108200E+10 744.00 0.402909E+10 0.00 0.00 0.37 21-MAY-18:12 0.09 05-MAY-05:15 2636.27 21-MAY-18:27 2636.27 21-MAY-18:27 0.00 01-MAY-00:05 745.99 21-MAY-18:12 0.00
June 0.906278E+10 0.231722E+10 720.00 0.906278E+10 0.00 0.00 0.60 13-JUN-18:30 0.37 08-JUN-06:00 4445.47 11-JUN-18:40 4445.47 11-JUN-18:40 0.00 01-JUN-00:10 1457.23 13-JUN-17:00 0.00
July 0.142062E+11 0.360190E+10 744.00 0.142062E+11 0.00 0.00 0.87 22-JUL-18:35 0.58 09-JUL-05:10 6329.40 09-JUL-18:44 6329.40 09-JUL-18:44 0.00 01-JUL-00:10 2309.12 22-JUL-18:35 0.00
August 0.188323E+11 0.475695E+10 744.00 0.188323E+11 0.00 0.00 1.00 14-AUG-15:10 0.80 27-AUG-06:08 7843.53 13-AUG-18:03 7843.53 13-AUG-18:03 0.00 01-AUG-00:10 2588.91 14-AUG-17:40 0.00
September 0.387875E+10 0.105932E+10 719.83 0.387875E+10 0.00 0.00 0.36 12-SEP-17:10 0.00 17-SEP-06:45 2557.52 12-SEP-17:20 2557.52 12-SEP-17:20 0.00 01-SEP-00:10 774.69 13-SEP-17:00 0.00
October 0.750218E+10 0.190649E+10 744.00 0.750218E+10 0.00 0.00 0.54 03-OCT-16:50 0.26 23-OCT-05:20 4166.51 03-OCT-16:50 4166.51 03-OCT-16:50 0.00 01-OCT-00:10 1027.61 06-OCT-16:00 0.00
November 0.110234E+11 0.268506E+10 720.00 0.110234E+11 0.00 0.00 0.70 10-NOV-16:20 0.39 27-NOV-04:02 5557.48 10-NOV-16:20 5557.48 10-NOV-16:20 0.00 01-NOV-00:10 1314.48 10-NOV-16:20 0.00
December 0.151876E+11 0.358649E+10 744.00 0.151876E+11 0.00 0.00 0.85 21-DEC-15:20 0.53 26-DEC-04:07 6965.28 21-DEC-15:20 6965.28 21-DEC-15:20 0.00 01-DEC-00:10 1599.22 21-DEC-15:20 0.00
                                       
Annual Sum or Average 0.120483E+12 0.299117E+11 8517.23 0.120483E+12 0.00                            
Minimum of Months 0.145725E+10 0.410863E+09 501.39 0.145725E+10 0.00 0.00 0.29   0.00   2089.09   2089.09   0.00   543.94   0.00
Maximum of Months 0.188323E+11 0.475695E+10 744.00 0.188323E+11 0.00 0.00 1.00   0.80   7948.65   7948.65   0.00   2588.91   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.40 0.00 73.40 0.38 533.48 0.00 0.00 744.00
February 114.61 0.00 114.61 2.13 501.71 0.00 0.00 672.00
March 158.61 0.00 158.61 20.29 416.36 0.00 0.00 744.00
April 258.22 1.14 257.08 108.13 321.49 0.00 0.00 720.00
May 322.83 15.54 307.28 130.73 254.59 0.00 0.00 744.00
June 356.86 22.34 334.52 202.97 192.74 0.00 0.00 720.00
July 338.50 19.26 319.24 211.23 178.32 0.00 0.00 744.00
August 266.09 4.15 261.94 172.40 202.45 0.00 0.00 744.00
September 202.55 0.04 202.50 107.76 267.19 0.00 0.00 720.00
October 129.79 0.00 129.79 25.47 380.08 0.00 0.00 744.00
November 77.98 0.00 77.98 0.78 483.87 0.00 0.00 720.00
December 53.11 0.00 53.11 0.00 583.37 0.00 0.00 744.00
                 
Annual Sum or Average 196.41 5.24 191.17 82.26 358.94 0.00 0.00 8760.00
Minimum of Months 53.11 0.00 53.11 0.00 178.32 0.00 0.00 672.00
Maximum of Months 356.86 22.34 334.52 211.23 583.37 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.40 0.00 73.40 0.38 533.48 0.00 0.00 744.00
February 114.61 0.00 114.61 2.13 501.71 0.00 0.00 672.00
March 158.60 0.00 158.60 20.28 416.36 0.00 0.00 744.00
April 258.22 1.14 257.08 108.13 321.49 0.00 0.00 720.00
May 322.82 15.54 307.28 130.72 254.59 0.00 0.00 744.00
June 356.86 22.34 334.52 202.96 192.74 0.00 0.00 720.00
July 338.50 19.26 319.23 211.23 178.32 0.00 0.00 744.00
August 266.09 4.15 261.94 172.39 202.45 0.00 0.00 744.00
September 202.54 0.04 202.50 107.75 267.19 0.00 0.00 720.00
October 129.79 0.00 129.79 25.47 380.08 0.00 0.00 744.00
November 77.98 0.00 77.98 0.78 483.87 0.00 0.00 720.00
December 53.11 0.00 53.11 0.00 583.37 0.00 0.00 744.00
                 
Annual Sum or Average 196.41 5.24 191.17 82.26 358.94 0.00 0.00 8760.00
Minimum of Months 53.11 0.00 53.11 0.00 178.32 0.00 0.00 672.00
Maximum of Months 356.86 22.34 334.52 211.23 583.37 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.40 0.00 73.40 0.38 533.48 0.00 0.00 744.00
February 114.61 0.00 114.61 2.13 501.71 0.00 0.00 672.00
March 158.60 0.00 158.60 20.28 416.36 0.00 0.00 744.00
April 258.22 1.14 257.08 108.13 321.49 0.00 0.00 720.00
May 322.83 15.54 307.28 130.72 254.59 0.00 0.00 744.00
June 356.86 22.34 334.52 202.96 192.74 0.00 0.00 720.00
July 338.50 19.26 319.24 211.23 178.32 0.00 0.00 744.00
August 266.09 4.15 261.94 172.39 202.45 0.00 0.00 744.00
September 202.54 0.04 202.50 107.76 267.19 0.00 0.00 720.00
October 129.79 0.00 129.79 25.47 380.08 0.00 0.00 744.00
November 77.98 0.00 77.98 0.78 483.87 0.00 0.00 720.00
December 53.11 0.00 53.11 0.00 583.37 0.00 0.00 744.00
                 
Annual Sum or Average 196.41 5.24 191.17 82.26 358.94 0.00 0.00 8760.00
Minimum of Months 53.11 0.00 53.11 0.00 178.32 0.00 0.00 672.00
Maximum of Months 356.86 22.34 334.52 211.23 583.37 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.40 0.00 73.40 0.38 533.48 0.00 0.00 744.00
February 114.61 0.00 114.61 2.13 501.71 0.00 0.00 672.00
March 158.60 0.00 158.60 20.28 416.36 0.00 0.00 744.00
April 258.22 1.14 257.08 108.13 321.49 0.00 0.00 720.00
May 322.82 15.54 307.28 130.72 254.59 0.00 0.00 744.00
June 356.86 22.34 334.52 202.96 192.74 0.00 0.00 720.00
July 338.50 19.26 319.23 211.23 178.32 0.00 0.00 744.00
August 266.09 4.15 261.94 172.39 202.45 0.00 0.00 744.00
September 202.54 0.04 202.50 107.75 267.19 0.00 0.00 720.00
October 129.79 0.00 129.79 25.47 380.08 0.00 0.00 744.00
November 77.98 0.00 77.98 0.78 483.87 0.00 0.00 720.00
December 53.11 0.00 53.11 0.00 583.37 0.00 0.00 744.00
                 
Annual Sum or Average 196.41 5.24 191.17 82.26 358.94 0.00 0.00 8760.00
Minimum of Months 53.11 0.00 53.11 0.00 178.32 0.00 0.00 672.00
Maximum of Months 356.86 22.34 334.52 211.23 583.37 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.39 0.00 73.39 0.38 533.46 0.00 0.00 744.00
February 114.61 0.00 114.61 2.13 501.69 0.00 0.00 672.00
March 158.60 0.00 158.60 20.28 416.35 0.00 0.00 744.00
April 258.21 1.14 257.07 108.13 321.48 0.00 0.00 720.00
May 322.81 15.54 307.27 130.72 254.58 0.00 0.00 744.00
June 356.84 22.34 334.50 202.96 192.73 0.00 0.00 720.00
July 338.48 19.26 319.22 211.22 178.31 0.00 0.00 744.00
August 266.08 4.15 261.93 172.39 202.44 0.00 0.00 744.00
September 202.53 0.04 202.49 107.75 267.18 0.00 0.00 720.00
October 129.78 0.00 129.78 25.47 380.07 0.00 0.00 744.00
November 77.98 0.00 77.98 0.78 483.85 0.00 0.00 720.00
December 53.10 0.00 53.10 0.00 583.35 0.00 0.00 744.00
                 
Annual Sum or Average 196.40 5.24 191.16 82.25 358.93 0.00 0.00 8760.00
Minimum of Months 53.10 0.00 53.10 0.00 178.31 0.00 0.00 672.00
Maximum of Months 356.84 22.34 334.50 211.22 583.35 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 166.71 66.98 99.73 58.01 531.60 0.00 0.00 744.00
February 248.57 91.82 156.75 113.40 498.25 0.00 0.00 672.00
March 259.76 51.19 208.57 102.70 411.63 0.00 0.00 744.00
April 697.55 327.82 369.73 607.48 315.50 0.00 0.00 720.00
May 733.27 319.71 413.56 620.33 270.92 0.00 0.00 744.00
June 725.80 289.81 435.99 659.01 207.79 0.00 0.00 720.00
July 740.91 314.83 426.08 706.94 188.74 0.00 0.00 744.00
August 701.93 335.37 366.56 693.21 200.93 0.00 0.00 744.00
September 632.21 336.22 295.99 600.99 267.54 0.00 0.00 720.00
October 305.13 126.45 178.68 205.33 383.68 0.00 0.00 744.00
November 159.09 54.23 104.86 57.78 479.16 0.00 0.00 720.00
December 117.91 43.84 74.06 32.23 577.15 0.00 0.00 744.00
                 
Annual Sum or Average 458.07 196.78 261.29 372.37 360.42 0.00 0.00 8760.00
Minimum of Months 117.91 43.84 74.06 32.23 188.74 0.00 0.00 672.00
Maximum of Months 740.91 336.22 435.99 706.94 577.15 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 166.71 66.98 99.73 58.01 531.60 0.00 0.00 744.00
February 248.57 91.82 156.75 113.40 498.25 0.00 0.00 672.00
March 259.76 51.19 208.57 102.70 411.63 0.00 0.00 744.00
April 697.55 327.82 369.73 607.48 315.50 0.00 0.00 720.00
May 733.27 319.71 413.56 620.33 270.92 0.00 0.00 744.00
June 725.80 289.81 435.99 659.01 207.79 0.00 0.00 720.00
July 740.91 314.83 426.08 706.94 188.74 0.00 0.00 744.00
August 701.93 335.37 366.56 693.21 200.93 0.00 0.00 744.00
September 632.21 336.22 295.99 600.99 267.54 0.00 0.00 720.00
October 305.13 126.45 178.68 205.33 383.68 0.00 0.00 744.00
November 159.09 54.23 104.86 57.78 479.16 0.00 0.00 720.00
December 117.91 43.84 74.06 32.23 577.15 0.00 0.00 744.00
                 
Annual Sum or Average 458.07 196.78 261.29 372.37 360.42 0.00 0.00 8760.00
Minimum of Months 117.91 43.84 74.06 32.23 188.74 0.00 0.00 672.00
Maximum of Months 740.91 336.22 435.99 706.94 577.15 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 166.71 66.98 99.73 58.01 531.59 0.00 0.00 744.00
February 248.57 91.82 156.74 113.40 498.24 0.00 0.00 672.00
March 259.76 51.19 208.57 102.69 411.62 0.00 0.00 744.00
April 697.53 327.81 369.72 607.47 315.49 0.00 0.00 720.00
May 733.26 319.70 413.56 620.32 270.92 0.00 0.00 744.00
June 725.79 289.81 435.98 659.00 207.78 0.00 0.00 720.00
July 740.89 314.82 426.07 706.93 188.73 0.00 0.00 744.00
August 701.92 335.36 366.56 693.20 200.92 0.00 0.00 744.00
September 632.20 336.21 295.98 600.97 267.53 0.00 0.00 720.00
October 305.13 126.45 178.68 205.32 383.67 0.00 0.00 744.00
November 159.08 54.23 104.86 57.78 479.15 0.00 0.00 720.00
December 117.90 43.84 74.06 32.23 577.14 0.00 0.00 744.00
                 
Annual Sum or Average 458.06 196.77 261.29 372.36 360.42 0.00 0.00 8760.00
Minimum of Months 117.90 43.84 74.06 32.23 188.73 0.00 0.00 672.00
Maximum of Months 740.89 336.21 435.98 706.93 577.14 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.58 269.63 146.95 371.94 439.05 0.00 0.00 744.00
February 508.95 310.57 198.37 448.74 433.51 0.00 0.00 672.00
March 314.71 91.68 223.04 190.64 374.64 0.00 0.00 744.00
April 653.46 295.39 358.07 553.20 312.62 0.00 0.00 720.00
May 540.34 175.86 364.48 363.83 267.81 0.00 0.00 744.00
June 497.77 120.43 377.34 345.03 205.26 0.00 0.00 720.00
July 539.32 168.84 370.48 412.68 189.06 0.00 0.00 744.00
August 632.04 284.31 347.74 569.58 203.23 0.00 0.00 744.00
September 747.20 437.83 309.37 743.01 260.01 0.00 0.00 720.00
October 513.29 300.04 213.25 485.11 349.27 0.00 0.00 744.00
November 363.75 221.24 142.51 323.70 418.42 0.00 0.00 720.00
December 288.27 184.66 103.61 250.70 499.12 0.00 0.00 744.00
                 
Annual Sum or Average 500.54 237.45 263.09 420.53 328.81 0.00 0.00 8760.00
Minimum of Months 288.27 91.68 103.61 190.64 189.06 0.00 0.00 672.00
Maximum of Months 747.20 437.83 377.34 743.01 499.12 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.58 269.63 146.95 371.93 439.05 0.00 0.00 744.00
February 508.94 310.57 198.37 448.74 433.51 0.00 0.00 672.00
March 314.71 91.68 223.04 190.64 374.64 0.00 0.00 744.00
April 653.46 295.39 358.07 553.20 312.62 0.00 0.00 720.00
May 540.34 175.86 364.48 363.83 267.81 0.00 0.00 744.00
June 497.77 120.43 377.33 345.03 205.26 0.00 0.00 720.00
July 539.32 168.84 370.48 412.68 189.06 0.00 0.00 744.00
August 632.04 284.30 347.74 569.58 203.23 0.00 0.00 744.00
September 747.19 437.83 309.37 743.01 260.01 0.00 0.00 720.00
October 513.28 300.04 213.25 485.11 349.27 0.00 0.00 744.00
November 363.75 221.24 142.51 323.70 418.42 0.00 0.00 720.00
December 288.27 184.66 103.61 250.70 499.12 0.00 0.00 744.00
                 
Annual Sum or Average 500.54 237.45 263.09 420.52 328.81 0.00 0.00 8760.00
Minimum of Months 288.27 91.68 103.61 190.64 189.06 0.00 0.00 672.00
Maximum of Months 747.19 437.83 377.33 743.01 499.12 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.58 269.63 146.95 371.94 439.05 0.00 0.00 744.00
February 508.95 310.57 198.37 448.74 433.51 0.00 0.00 672.00
March 314.71 91.68 223.04 190.64 374.64 0.00 0.00 744.00
April 653.46 295.39 358.07 553.20 312.62 0.00 0.00 720.00
May 540.34 175.86 364.48 363.83 267.81 0.00 0.00 744.00
June 497.77 120.43 377.34 345.03 205.26 0.00 0.00 720.00
July 539.32 168.84 370.48 412.68 189.06 0.00 0.00 744.00
August 632.04 284.31 347.74 569.58 203.23 0.00 0.00 744.00
September 747.20 437.83 309.37 743.01 260.01 0.00 0.00 720.00
October 513.29 300.04 213.25 485.11 349.27 0.00 0.00 744.00
November 363.75 221.24 142.51 323.70 418.42 0.00 0.00 720.00
December 288.27 184.66 103.61 250.70 499.12 0.00 0.00 744.00
                 
Annual Sum or Average 500.54 237.45 263.09 420.53 328.81 0.00 0.00 8760.00
Minimum of Months 288.27 91.68 103.61 190.64 189.06 0.00 0.00 672.00
Maximum of Months 747.20 437.83 377.34 743.01 499.12 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.58 269.63 146.95 371.93 439.05 0.00 0.00 744.00
February 508.94 310.57 198.37 448.74 433.51 0.00 0.00 672.00
March 314.71 91.68 223.04 190.64 374.64 0.00 0.00 744.00
April 653.46 295.39 358.07 553.20 312.62 0.00 0.00 720.00
May 540.34 175.86 364.48 363.83 267.81 0.00 0.00 744.00
June 497.77 120.43 377.33 345.03 205.26 0.00 0.00 720.00
July 539.32 168.84 370.48 412.68 189.06 0.00 0.00 744.00
August 632.04 284.30 347.74 569.58 203.23 0.00 0.00 744.00
September 747.19 437.83 309.37 743.01 260.01 0.00 0.00 720.00
October 513.28 300.04 213.25 485.11 349.27 0.00 0.00 744.00
November 363.75 221.24 142.51 323.70 418.42 0.00 0.00 720.00
December 288.27 184.66 103.61 250.70 499.12 0.00 0.00 744.00
                 
Annual Sum or Average 500.54 237.45 263.09 420.52 328.81 0.00 0.00 8760.00
Minimum of Months 288.27 91.68 103.61 190.64 189.06 0.00 0.00 672.00
Maximum of Months 747.19 437.83 377.33 743.01 499.12 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.57 269.62 146.95 371.92 439.04 0.00 0.00 744.00
February 508.92 310.56 198.36 448.72 433.49 0.00 0.00 672.00
March 314.70 91.67 223.03 190.63 374.63 0.00 0.00 744.00
April 653.43 295.38 358.05 553.18 312.61 0.00 0.00 720.00
May 540.32 175.85 364.46 363.82 267.80 0.00 0.00 744.00
June 497.75 120.43 377.32 345.02 205.25 0.00 0.00 720.00
July 539.30 168.83 370.47 412.66 189.05 0.00 0.00 744.00
August 632.02 284.29 347.72 569.55 203.22 0.00 0.00 744.00
September 747.16 437.81 309.35 742.98 260.00 0.00 0.00 720.00
October 513.26 300.03 213.24 485.09 349.26 0.00 0.00 744.00
November 363.73 221.23 142.50 323.69 418.40 0.00 0.00 720.00
December 288.26 184.65 103.61 250.69 499.10 0.00 0.00 744.00
                 
Annual Sum or Average 500.52 237.44 263.08 420.51 328.80 0.00 0.00 8760.00
Minimum of Months 288.26 91.67 103.61 190.63 189.05 0.00 0.00 672.00
Maximum of Months 747.16 437.81 377.32 742.98 499.10 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 162.12 53.58 108.54 59.82 567.15 0.00 0.00 744.00
February 287.02 121.20 165.82 160.83 554.72 0.00 0.00 672.00
March 259.52 49.65 209.87 97.67 472.84 0.00 0.00 744.00
April 612.37 243.26 369.11 495.67 382.51 0.00 0.00 720.00
May 718.33 292.04 426.28 597.25 304.73 0.00 0.00 744.00
June 775.69 319.25 456.44 707.57 245.79 0.00 0.00 720.00
July 790.02 348.26 441.76 754.34 233.25 0.00 0.00 744.00
August 663.63 287.32 376.31 633.31 255.72 0.00 0.00 744.00
September 532.44 238.77 293.68 484.21 306.34 0.00 0.00 720.00
October 284.04 102.15 181.89 180.75 435.63 0.00 0.00 744.00
November 153.71 44.87 108.84 54.64 554.88 0.00 0.00 720.00
December 87.00 18.36 68.64 11.78 684.48 0.00 0.00 744.00
                 
Annual Sum or Average 444.30 176.63 267.67 353.83 415.85 0.00 0.00 8760.00
Minimum of Months 87.00 18.36 68.64 11.78 233.25 0.00 0.00 672.00
Maximum of Months 790.02 348.26 456.44 754.34 684.48 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 162.12 53.58 108.54 59.82 567.15 0.00 0.00 744.00
February 287.02 121.20 165.82 160.83 554.72 0.00 0.00 672.00
March 259.52 49.65 209.87 97.67 472.84 0.00 0.00 744.00
April 612.37 243.26 369.11 495.67 382.51 0.00 0.00 720.00
May 718.33 292.04 426.28 597.25 304.73 0.00 0.00 744.00
June 775.69 319.25 456.44 707.57 245.79 0.00 0.00 720.00
July 790.02 348.26 441.76 754.34 233.25 0.00 0.00 744.00
August 663.63 287.32 376.31 633.31 255.72 0.00 0.00 744.00
September 532.44 238.77 293.68 484.21 306.34 0.00 0.00 720.00
October 284.04 102.15 181.89 180.75 435.63 0.00 0.00 744.00
November 153.71 44.87 108.84 54.64 554.88 0.00 0.00 720.00
December 87.00 18.36 68.64 11.78 684.48 0.00 0.00 744.00
                 
Annual Sum or Average 444.30 176.63 267.67 353.83 415.85 0.00 0.00 8760.00
Minimum of Months 87.00 18.36 68.64 11.78 233.25 0.00 0.00 672.00
Maximum of Months 790.02 348.26 456.44 754.34 684.48 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 162.12 53.58 108.54 59.82 567.14 0.00 0.00 744.00
February 287.02 121.20 165.82 160.82 554.71 0.00 0.00 672.00
March 259.52 49.65 209.87 97.67 472.84 0.00 0.00 744.00
April 612.36 243.25 369.11 495.66 382.50 0.00 0.00 720.00
May 718.32 292.04 426.28 597.23 304.73 0.00 0.00 744.00
June 775.68 319.25 456.43 707.56 245.79 0.00 0.00 720.00
July 790.00 348.25 441.75 754.32 233.25 0.00 0.00 744.00
August 663.62 287.31 376.31 633.30 255.72 0.00 0.00 744.00
September 532.43 238.76 293.67 484.21 306.33 0.00 0.00 720.00
October 284.03 102.14 181.89 180.75 435.62 0.00 0.00 744.00
November 153.71 44.87 108.84 54.64 554.87 0.00 0.00 720.00
December 87.00 18.35 68.64 11.78 684.47 0.00 0.00 744.00
                 
Annual Sum or Average 444.29 176.63 267.66 353.83 415.85 0.00 0.00 8760.00
Minimum of Months 87.00 18.35 68.64 11.78 233.25 0.00 0.00 672.00
Maximum of Months 790.00 348.25 456.43 754.32 684.47 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 366.99 0.00 366.99 4.02 2445.24 0.00 0.00 744.00
February 573.07 0.00 573.07 20.04 2286.55 0.00 0.00 672.00
March 793.03 0.00 793.03 118.79 1911.43 0.00 0.00 744.00
April 1291.11 5.71 1285.40 567.56 1502.69 0.00 0.00 720.00
May 1614.15 77.72 1536.42 676.27 1205.58 0.00 0.00 744.00
June 1784.31 111.70 1672.61 1036.07 917.65 0.00 0.00 720.00
July 1692.51 96.32 1596.20 1089.73 840.04 0.00 0.00 744.00
August 1330.46 20.75 1309.71 891.22 952.31 0.00 0.00 744.00
September 1012.73 0.22 1012.51 561.92 1262.94 0.00 0.00 720.00
October 648.95 0.00 648.95 148.23 1747.59 0.00 0.00 744.00
November 389.92 0.00 389.92 8.51 2164.42 0.00 0.00 720.00
December 265.54 0.00 265.54 0.00 2563.78 0.00 0.00 744.00
                 
Annual Sum or Average 982.05 26.21 955.84 428.93 1646.85 0.00 0.00 8760.00
Minimum of Months 265.54 0.00 265.54 0.00 840.04 0.00 0.00 672.00
Maximum of Months 1784.31 111.70 1672.61 1089.73 2563.78 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 500.14 200.94 299.20 186.00 1485.36 0.00 0.00 744.00
February 745.71 275.47 470.23 355.88 1396.09 0.00 0.00 672.00
March 779.28 153.58 625.71 329.30 1155.45 0.00 0.00 744.00
April 2092.62 983.45 1109.18 1823.97 918.48 0.00 0.00 720.00
May 2199.80 959.12 1240.68 1864.18 779.92 0.00 0.00 744.00
June 2177.39 869.43 1307.95 1977.74 602.13 0.00 0.00 720.00
July 2222.70 944.47 1278.23 2117.75 551.91 0.00 0.00 744.00
August 2105.77 1006.10 1099.68 2078.53 595.24 0.00 0.00 744.00
September 1896.61 1008.65 887.96 1807.59 770.87 0.00 0.00 720.00
October 915.39 379.36 536.03 632.48 1074.33 0.00 0.00 744.00
November 477.26 162.68 314.58 185.86 1317.61 0.00 0.00 720.00
December 353.71 131.53 222.19 107.40 1584.76 0.00 0.00 744.00
                 
Annual Sum or Average 1374.18 590.32 783.86 1124.94 1017.53 0.00 0.00 8760.00
Minimum of Months 353.71 131.53 222.19 107.40 551.91 0.00 0.00 672.00
Maximum of Months 2222.70 1008.65 1307.95 2117.75 1584.76 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2082.97 1348.19 734.78 1856.41 2161.97 0.00 0.00 744.00
February 2544.77 1552.90 991.87 2241.18 2125.87 0.00 0.00 672.00
March 1573.60 458.39 1115.21 965.75 1802.33 0.00 0.00 744.00
April 3267.35 1476.98 1790.37 2767.19 1526.03 0.00 0.00 720.00
May 2701.73 879.32 1822.41 1827.30 1307.07 0.00 0.00 744.00
June 2488.89 602.18 1886.70 1741.09 992.82 0.00 0.00 720.00
July 2696.64 844.20 1852.44 2081.62 913.48 0.00 0.00 744.00
August 3160.27 1421.56 1738.71 2858.75 993.66 0.00 0.00 744.00
September 3736.05 2189.19 1546.85 3705.69 1282.41 0.00 0.00 720.00
October 2566.48 1500.24 1066.25 2424.12 1700.35 0.00 0.00 744.00
November 1818.79 1106.24 712.54 1623.70 2006.43 0.00 0.00 720.00
December 1441.37 923.30 518.07 1266.37 2374.95 0.00 0.00 744.00
                 
Annual Sum or Average 2502.74 1187.26 1315.48 2108.42 1596.23 0.00 0.00 8760.00
Minimum of Months 1441.37 458.39 518.07 965.75 913.48 0.00 0.00 672.00
Maximum of Months 3736.05 2189.19 1886.70 3705.69 2374.95 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 486.35 160.73 325.62 195.03 1529.87 0.00 0.00 744.00
February 861.06 363.59 497.47 510.15 1458.22 0.00 0.00 672.00
March 778.56 148.95 629.61 336.39 1199.65 0.00 0.00 744.00
April 1837.10 729.77 1107.33 1547.30 1001.93 0.00 0.00 720.00
May 2154.97 876.13 1278.84 1824.41 849.75 0.00 0.00 744.00
June 2327.05 957.74 1369.31 2161.79 668.78 0.00 0.00 720.00
July 2370.03 1044.76 1325.27 2315.99 622.00 0.00 0.00 744.00
August 1990.88 861.95 1128.93 1960.84 672.07 0.00 0.00 744.00
September 1597.31 716.29 881.02 1487.09 843.91 0.00 0.00 720.00
October 852.11 306.43 545.68 580.94 1131.86 0.00 0.00 744.00
November 461.13 134.62 326.51 187.83 1383.64 0.00 0.00 720.00
December 260.99 55.07 205.93 45.91 1677.26 0.00 0.00 744.00
                 
Annual Sum or Average 1332.87 529.88 802.99 1098.22 1084.75 0.00 0.00 8760.00
Minimum of Months 260.99 55.07 205.93 45.91 622.00 0.00 0.00 672.00
Maximum of Months 2370.03 1044.76 1369.31 2315.99 1677.26 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 366.99 0.00 366.99 12.69 2144.84 0.00 0.00 744.00
February 573.07 0.00 573.07 44.62 2025.12 0.00 0.00 672.00
March 793.03 0.00 793.03 157.53 1715.38 0.00 0.00 744.00
April 1291.11 5.71 1285.40 596.59 1401.24 0.00 0.00 720.00
May 1614.15 77.72 1536.42 706.50 1128.76 0.00 0.00 744.00
June 1784.31 111.70 1672.61 1048.10 880.53 0.00 0.00 720.00
July 1692.51 96.32 1596.20 1099.00 807.46 0.00 0.00 744.00
August 1330.46 20.75 1309.71 898.35 909.99 0.00 0.00 744.00
September 1012.73 0.22 1012.51 586.91 1180.44 0.00 0.00 720.00
October 648.95 0.00 648.95 186.53 1554.67 0.00 0.00 744.00
November 389.92 0.00 389.92 19.40 1901.36 0.00 0.00 720.00
December 265.54 0.00 265.54 0.84 2277.98 0.00 0.00 744.00
                 
Annual Sum or Average 982.05 26.21 955.84 448.45 1491.29 0.00 0.00 8760.00
Minimum of Months 265.54 0.00 265.54 0.84 807.46 0.00 0.00 672.00
Maximum of Months 1784.31 111.70 1672.61 1099.00 2277.98 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 500.14 200.94 299.20 205.09 1332.50 0.00 0.00 744.00
February 745.71 275.47 470.23 383.79 1268.13 0.00 0.00 672.00
March 779.28 153.58 625.71 356.86 1064.50 0.00 0.00 744.00
April 2092.62 983.45 1109.18 1841.26 872.73 0.00 0.00 720.00
May 2199.80 959.12 1240.68 1880.22 745.20 0.00 0.00 744.00
June 2177.39 869.43 1307.95 1979.89 585.53 0.00 0.00 720.00
July 2222.70 944.47 1278.23 2116.61 538.80 0.00 0.00 744.00
August 2105.77 1006.10 1099.68 2078.28 579.48 0.00 0.00 744.00
September 1896.61 1008.65 887.96 1818.47 737.01 0.00 0.00 720.00
October 915.39 379.36 536.03 658.61 980.61 0.00 0.00 744.00
November 477.26 162.68 314.58 201.94 1190.75 0.00 0.00 720.00
December 353.71 131.53 222.19 120.29 1435.55 0.00 0.00 744.00
                 
Annual Sum or Average 1374.18 590.32 783.86 1139.42 942.64 0.00 0.00 8760.00
Minimum of Months 353.71 131.53 222.19 120.29 538.80 0.00 0.00 672.00
Maximum of Months 2222.70 1008.65 1307.95 2116.61 1435.55 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2082.97 1348.19 734.78 1912.54 1934.32 0.00 0.00 744.00
February 2544.77 1552.90 991.87 2293.62 1930.64 0.00 0.00 672.00
March 1573.60 458.39 1115.21 1010.86 1649.04 0.00 0.00 744.00
April 3267.35 1476.98 1790.37 2792.92 1440.48 0.00 0.00 720.00
May 2701.73 879.32 1822.41 1854.89 1235.66 0.00 0.00 744.00
June 2488.89 602.18 1886.70 1754.42 955.95 0.00 0.00 720.00
July 2696.64 844.20 1852.44 2091.15 881.48 0.00 0.00 744.00
August 3160.27 1421.56 1738.71 2867.08 955.75 0.00 0.00 744.00
September 3736.05 2189.19 1546.85 3723.86 1214.73 0.00 0.00 720.00
October 2566.48 1500.24 1066.25 2460.70 1547.14 0.00 0.00 744.00
November 1818.79 1106.24 712.54 1661.14 1805.39 0.00 0.00 720.00
December 1441.37 923.30 518.07 1305.41 2150.38 0.00 0.00 744.00
                 
Annual Sum or Average 2502.74 1187.26 1315.48 2139.10 1472.66 0.00 0.00 8760.00
Minimum of Months 1441.37 458.39 518.07 1010.86 881.48 0.00 0.00 672.00
Maximum of Months 3736.05 2189.19 1886.70 3723.86 2150.38 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 486.35 160.73 325.62 208.70 1394.86 0.00 0.00 744.00
February 861.06 363.59 497.47 528.27 1344.39 0.00 0.00 672.00
March 778.56 148.95 629.61 356.25 1113.47 0.00 0.00 744.00
April 1837.10 729.77 1107.33 1562.32 951.08 0.00 0.00 720.00
May 2154.97 876.13 1278.84 1836.94 809.11 0.00 0.00 744.00
June 2327.05 957.74 1369.31 2165.34 645.49 0.00 0.00 720.00
July 2370.03 1044.76 1325.27 2317.32 601.58 0.00 0.00 744.00
August 1990.88 861.95 1128.93 1963.91 647.86 0.00 0.00 744.00
September 1597.31 716.29 881.02 1497.68 802.63 0.00 0.00 720.00
October 852.11 306.43 545.68 599.72 1044.29 0.00 0.00 744.00
November 461.13 134.62 326.51 198.09 1268.92 0.00 0.00 720.00
December 260.99 55.07 205.93 51.38 1546.35 0.00 0.00 744.00
                 
Annual Sum or Average 1332.87 529.88 802.99 1109.19 1012.52 0.00 0.00 8760.00
Minimum of Months 260.99 55.07 205.93 51.38 601.58 0.00 0.00 672.00
Maximum of Months 2370.03 1044.76 1369.31 2317.32 1546.35 0.00 0.00 744.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196590E+09 0.00 0.196590E+09 1019389.48 0.142887E+10
February 0.277276E+09 0.00 0.277276E+09 5152485.67 0.121374E+10
March 0.424812E+09 0.00 0.424812E+09 54333584.09 0.111518E+10
April 0.669311E+09 2958567.24 0.666352E+09 0.280278E+09 0.833301E+09
May 0.864666E+09 41635168.62 0.823031E+09 0.350141E+09 0.681883E+09
June 0.924985E+09 57902793.67 0.867082E+09 0.526092E+09 0.499581E+09
July 0.906646E+09 51594728.13 0.855051E+09 0.565771E+09 0.477607E+09
August 0.712699E+09 11113958.37 0.701585E+09 0.461748E+09 0.542238E+09
September 0.524998E+09 111816.23 0.524886E+09 0.279307E+09 0.692563E+09
October 0.347631E+09 0.00 0.347631E+09 68221126.12 0.101801E+10
November 0.202137E+09 0.00 0.202137E+09 2029712.97 0.125419E+10
December 0.142243E+09 0.00 0.142243E+09 0.00 0.156251E+10
           
Annual Sum or Average 0.619399E+10 0.165317E+09 0.602868E+10 0.259409E+10 0.113197E+11
Minimum of Months 0.142243E+09 0.00 0.142243E+09 0.00 0.477607E+09
Maximum of Months 0.924985E+09 57902793.67 0.867082E+09 0.565771E+09 0.156251E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196587E+09 0.00 0.196587E+09 1019189.72 0.142887E+10
February 0.277272E+09 0.00 0.277272E+09 5151835.78 0.121374E+10
March 0.424804E+09 0.00 0.424804E+09 54329685.41 0.111518E+10
April 0.669301E+09 2958502.20 0.666343E+09 0.280270E+09 0.833302E+09
May 0.864653E+09 41634253.32 0.823019E+09 0.350130E+09 0.681884E+09
June 0.924971E+09 57901520.74 0.867070E+09 0.526079E+09 0.499581E+09
July 0.906633E+09 51593593.88 0.855039E+09 0.565759E+09 0.477607E+09
August 0.712689E+09 11113714.04 0.701575E+09 0.461740E+09 0.542237E+09
September 0.524991E+09 111813.78 0.524879E+09 0.279301E+09 0.692562E+09
October 0.347626E+09 0.00 0.347626E+09 68218010.65 0.101801E+10
November 0.202133E+09 0.00 0.202133E+09 2029359.37 0.125419E+10
December 0.142241E+09 0.00 0.142241E+09 0.00 0.156251E+10
           
Annual Sum or Average 0.619390E+10 0.165313E+09 0.602859E+10 0.259403E+10 0.113197E+11
Minimum of Months 0.142241E+09 0.00 0.142241E+09 0.00 0.477607E+09
Maximum of Months 0.924971E+09 57901520.74 0.867070E+09 0.565759E+09 0.156251E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196588E+09 0.00 0.196588E+09 1019256.30 0.142887E+10
February 0.277273E+09 0.00 0.277273E+09 5152052.41 0.121374E+10
March 0.424807E+09 0.00 0.424807E+09 54330984.97 0.111518E+10
April 0.669305E+09 2958523.88 0.666346E+09 0.280273E+09 0.833302E+09
May 0.864658E+09 41634558.42 0.823023E+09 0.350134E+09 0.681883E+09
June 0.924976E+09 57901945.05 0.867074E+09 0.526083E+09 0.499581E+09
July 0.906637E+09 51593971.97 0.855043E+09 0.565763E+09 0.477607E+09
August 0.712692E+09 11113795.49 0.701579E+09 0.461743E+09 0.542238E+09
September 0.524993E+09 111814.60 0.524881E+09 0.279303E+09 0.692562E+09
October 0.347627E+09 0.00 0.347627E+09 68219049.14 0.101801E+10
November 0.202134E+09 0.00 0.202134E+09 2029477.24 0.125419E+10
December 0.142241E+09 0.00 0.142241E+09 0.00 0.156251E+10
           
Annual Sum or Average 0.619393E+10 0.165315E+09 0.602862E+10 0.259405E+10 0.113197E+11
Minimum of Months 0.142241E+09 0.00 0.142241E+09 0.00 0.477607E+09
Maximum of Months 0.924976E+09 57901945.05 0.867074E+09 0.565763E+09 0.156251E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196587E+09 0.00 0.196587E+09 1019189.72 0.142887E+10
February 0.277272E+09 0.00 0.277272E+09 5151835.78 0.121374E+10
March 0.424804E+09 0.00 0.424804E+09 54329685.41 0.111518E+10
April 0.669301E+09 2958502.20 0.666343E+09 0.280270E+09 0.833302E+09
May 0.864653E+09 41634253.32 0.823019E+09 0.350130E+09 0.681884E+09
June 0.924971E+09 57901520.74 0.867070E+09 0.526079E+09 0.499581E+09
July 0.906633E+09 51593593.88 0.855039E+09 0.565759E+09 0.477607E+09
August 0.712689E+09 11113714.04 0.701575E+09 0.461740E+09 0.542237E+09
September 0.524991E+09 111813.78 0.524879E+09 0.279301E+09 0.692562E+09
October 0.347626E+09 0.00 0.347626E+09 68218010.65 0.101801E+10
November 0.202133E+09 0.00 0.202133E+09 2029359.37 0.125419E+10
December 0.142241E+09 0.00 0.142241E+09 0.00 0.156251E+10
           
Annual Sum or Average 0.619390E+10 0.165313E+09 0.602859E+10 0.259403E+10 0.113197E+11
Minimum of Months 0.142241E+09 0.00 0.142241E+09 0.00 0.477607E+09
Maximum of Months 0.924971E+09 57901520.74 0.867070E+09 0.565759E+09 0.156251E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.196580E+09 0.00 0.196580E+09 1019181.93 0.142881E+10
February 0.277261E+09 0.00 0.277261E+09 5151736.45 0.121369E+10
March 0.424788E+09 0.00 0.424788E+09 54328145.44 0.111514E+10
April 0.669276E+09 2958393.80 0.666318E+09 0.280260E+09 0.833268E+09
May 0.864621E+09 41632727.82 0.822988E+09 0.350118E+09 0.681856E+09
June 0.924936E+09 57899399.20 0.867037E+09 0.526060E+09 0.499561E+09
July 0.906598E+09 51591703.47 0.855006E+09 0.565738E+09 0.477588E+09
August 0.712662E+09 11113306.83 0.701549E+09 0.461722E+09 0.542216E+09
September 0.524971E+09 111809.68 0.524859E+09 0.279291E+09 0.692534E+09
October 0.347613E+09 0.00 0.347613E+09 68215780.39 0.101797E+10
November 0.202126E+09 0.00 0.202126E+09 2029336.51 0.125414E+10
December 0.142235E+09 0.00 0.142235E+09 0.00 0.156245E+10
           
Annual Sum or Average 0.619367E+10 0.165307E+09 0.602836E+10 0.259393E+10 0.113192E+11
Minimum of Months 0.142235E+09 0.00 0.142235E+09 0.00 0.477588E+09
Maximum of Months 0.924936E+09 57899399.20 0.867037E+09 0.565738E+09 0.156245E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.446525E+09 0.179401E+09 0.267124E+09 0.155376E+09 0.142384E+10
February 0.601343E+09 0.222143E+09 0.379200E+09 0.274333E+09 0.120537E+10
March 0.695753E+09 0.137115E+09 0.558638E+09 0.275059E+09 0.110250E+10
April 0.180804E+10 0.849706E+09 0.958337E+09 0.157459E+10 0.817775E+09
May 0.196400E+10 0.856312E+09 0.110769E+10 0.166150E+10 0.725640E+09
June 0.188128E+10 0.751199E+09 0.113008E+10 0.170816E+10 0.538582E+09
July 0.198444E+10 0.843229E+09 0.114121E+10 0.189347E+10 0.505515E+09
August 0.188005E+10 0.898252E+09 0.981800E+09 0.185670E+10 0.538159E+09
September 0.163868E+10 0.871479E+09 0.767206E+09 0.155776E+10 0.693463E+09
October 0.817268E+09 0.338693E+09 0.478575E+09 0.549951E+09 0.102765E+10
November 0.412355E+09 0.140557E+09 0.271799E+09 0.149765E+09 0.124197E+10
December 0.315799E+09 0.117429E+09 0.198371E+09 86317784.78 0.154583E+10
           
Annual Sum or Average 0.144456E+11 0.620551E+10 0.824004E+10 0.117430E+11 0.113663E+11
Minimum of Months 0.315799E+09 0.117429E+09 0.198371E+09 86317784.78 0.505515E+09
Maximum of Months 0.198444E+10 0.898252E+09 0.114121E+10 0.189347E+10 0.154583E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.446525E+09 0.179401E+09 0.267124E+09 0.155376E+09 0.142384E+10
February 0.601343E+09 0.222143E+09 0.379200E+09 0.274333E+09 0.120537E+10
March 0.695753E+09 0.137115E+09 0.558638E+09 0.275059E+09 0.110250E+10
April 0.180804E+10 0.849706E+09 0.958337E+09 0.157459E+10 0.817775E+09
May 0.196400E+10 0.856312E+09 0.110769E+10 0.166150E+10 0.725640E+09
June 0.188128E+10 0.751199E+09 0.113008E+10 0.170816E+10 0.538582E+09
July 0.198444E+10 0.843229E+09 0.114121E+10 0.189347E+10 0.505515E+09
August 0.188005E+10 0.898252E+09 0.981800E+09 0.185670E+10 0.538159E+09
September 0.163868E+10 0.871479E+09 0.767206E+09 0.155776E+10 0.693463E+09
October 0.817268E+09 0.338693E+09 0.478575E+09 0.549951E+09 0.102765E+10
November 0.412355E+09 0.140557E+09 0.271799E+09 0.149765E+09 0.124197E+10
December 0.315799E+09 0.117429E+09 0.198371E+09 86317784.78 0.154583E+10
           
Annual Sum or Average 0.144456E+11 0.620551E+10 0.824004E+10 0.117430E+11 0.113663E+11
Minimum of Months 0.315799E+09 0.117429E+09 0.198371E+09 86317784.78 0.505515E+09
Maximum of Months 0.198444E+10 0.898252E+09 0.114121E+10 0.189347E+10 0.154583E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.446517E+09 0.179398E+09 0.267119E+09 0.155373E+09 0.142382E+10
February 0.601332E+09 0.222139E+09 0.379193E+09 0.274328E+09 0.120535E+10
March 0.695740E+09 0.137112E+09 0.558627E+09 0.275054E+09 0.110248E+10
April 0.180801E+10 0.849691E+09 0.958320E+09 0.157456E+10 0.817761E+09
May 0.196397E+10 0.856296E+09 0.110767E+10 0.166147E+10 0.725627E+09
June 0.188125E+10 0.751186E+09 0.113006E+10 0.170813E+10 0.538572E+09
July 0.198441E+10 0.843214E+09 0.114119E+10 0.189343E+10 0.505506E+09
August 0.188002E+10 0.898236E+09 0.981782E+09 0.185667E+10 0.538149E+09
September 0.163865E+10 0.871463E+09 0.767192E+09 0.155773E+10 0.693450E+09
October 0.817253E+09 0.338687E+09 0.478566E+09 0.549941E+09 0.102763E+10
November 0.412348E+09 0.140554E+09 0.271794E+09 0.149762E+09 0.124195E+10
December 0.315794E+09 0.117427E+09 0.198367E+09 86316207.56 0.154580E+10
           
Annual Sum or Average 0.144453E+11 0.620540E+10 0.823989E+10 0.117428E+11 0.113661E+11
Minimum of Months 0.315794E+09 0.117427E+09 0.198367E+09 86316207.56 0.505506E+09
Maximum of Months 0.198441E+10 0.898236E+09 0.114119E+10 0.189343E+10 0.154580E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111578E+10 0.722182E+09 0.393599E+09 0.996200E+09 0.117596E+10
February 0.123124E+10 0.751340E+09 0.479900E+09 0.108560E+10 0.104874E+10
March 0.842930E+09 0.245545E+09 0.597385E+09 0.510618E+09 0.100344E+10
April 0.169377E+10 0.765650E+09 0.928117E+09 0.143390E+10 0.810316E+09
May 0.144724E+10 0.471026E+09 0.976217E+09 0.974494E+09 0.717307E+09
June 0.129022E+10 0.312166E+09 0.978056E+09 0.894323E+09 0.532027E+09
July 0.144452E+10 0.452211E+09 0.992304E+09 0.110532E+10 0.506382E+09
August 0.169287E+10 0.761487E+09 0.931380E+09 0.152556E+10 0.544333E+09
September 0.193673E+10 0.113485E+10 0.801879E+09 0.192589E+10 0.673943E+09
October 0.137479E+10 0.803630E+09 0.571159E+09 0.129932E+10 0.935490E+09
November 0.942841E+09 0.573464E+09 0.369376E+09 0.839030E+09 0.108454E+10
December 0.772099E+09 0.494585E+09 0.277514E+09 0.671486E+09 0.133683E+10
           
Annual Sum or Average 0.157850E+11 0.748814E+10 0.829689E+10 0.132617E+11 0.103693E+11
Minimum of Months 0.772099E+09 0.245545E+09 0.277514E+09 0.510618E+09 0.506382E+09
Maximum of Months 0.193673E+10 0.113485E+10 0.992304E+09 0.192589E+10 0.133683E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111577E+10 0.722177E+09 0.393596E+09 0.996190E+09 0.117596E+10
February 0.123123E+10 0.751335E+09 0.479897E+09 0.108559E+10 0.104874E+10
March 0.842925E+09 0.245544E+09 0.597381E+09 0.510612E+09 0.100344E+10
April 0.169376E+10 0.765645E+09 0.928112E+09 0.143389E+10 0.810316E+09
May 0.144723E+10 0.471022E+09 0.976212E+09 0.974486E+09 0.717307E+09
June 0.129021E+10 0.312163E+09 0.978051E+09 0.894316E+09 0.532027E+09
July 0.144451E+10 0.452208E+09 0.992299E+09 0.110531E+10 0.506382E+09
August 0.169286E+10 0.761482E+09 0.931376E+09 0.152555E+10 0.544333E+09
September 0.193672E+10 0.113485E+10 0.801875E+09 0.192588E+10 0.673943E+09
October 0.137478E+10 0.803624E+09 0.571155E+09 0.129931E+10 0.935490E+09
November 0.942834E+09 0.573460E+09 0.369374E+09 0.839022E+09 0.108454E+10
December 0.772094E+09 0.494582E+09 0.277512E+09 0.671480E+09 0.133683E+10
           
Annual Sum or Average 0.157849E+11 0.748809E+10 0.829684E+10 0.132616E+11 0.103693E+11
Minimum of Months 0.772094E+09 0.245544E+09 0.277512E+09 0.510612E+09 0.506382E+09
Maximum of Months 0.193672E+10 0.113485E+10 0.992299E+09 0.192588E+10 0.133683E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111578E+10 0.722182E+09 0.393599E+09 0.996200E+09 0.117596E+10
February 0.123124E+10 0.751340E+09 0.479900E+09 0.108560E+10 0.104874E+10
March 0.842930E+09 0.245545E+09 0.597385E+09 0.510618E+09 0.100344E+10
April 0.169377E+10 0.765650E+09 0.928117E+09 0.143390E+10 0.810316E+09
May 0.144724E+10 0.471026E+09 0.976217E+09 0.974494E+09 0.717307E+09
June 0.129022E+10 0.312166E+09 0.978056E+09 0.894323E+09 0.532027E+09
July 0.144452E+10 0.452211E+09 0.992304E+09 0.110532E+10 0.506382E+09
August 0.169287E+10 0.761487E+09 0.931380E+09 0.152556E+10 0.544333E+09
September 0.193673E+10 0.113485E+10 0.801879E+09 0.192589E+10 0.673943E+09
October 0.137479E+10 0.803630E+09 0.571159E+09 0.129932E+10 0.935490E+09
November 0.942841E+09 0.573464E+09 0.369376E+09 0.839030E+09 0.108454E+10
December 0.772099E+09 0.494585E+09 0.277514E+09 0.671486E+09 0.133683E+10
           
Annual Sum or Average 0.157850E+11 0.748814E+10 0.829689E+10 0.132617E+11 0.103693E+11
Minimum of Months 0.772099E+09 0.245545E+09 0.277514E+09 0.510618E+09 0.506382E+09
Maximum of Months 0.193673E+10 0.113485E+10 0.992304E+09 0.192589E+10 0.133683E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111577E+10 0.722177E+09 0.393596E+09 0.996190E+09 0.117596E+10
February 0.123123E+10 0.751335E+09 0.479897E+09 0.108559E+10 0.104874E+10
March 0.842925E+09 0.245544E+09 0.597381E+09 0.510612E+09 0.100344E+10
April 0.169376E+10 0.765645E+09 0.928112E+09 0.143389E+10 0.810316E+09
May 0.144723E+10 0.471022E+09 0.976212E+09 0.974486E+09 0.717307E+09
June 0.129021E+10 0.312163E+09 0.978051E+09 0.894316E+09 0.532027E+09
July 0.144451E+10 0.452208E+09 0.992299E+09 0.110531E+10 0.506382E+09
August 0.169286E+10 0.761482E+09 0.931376E+09 0.152555E+10 0.544333E+09
September 0.193672E+10 0.113485E+10 0.801875E+09 0.192588E+10 0.673943E+09
October 0.137478E+10 0.803624E+09 0.571155E+09 0.129931E+10 0.935490E+09
November 0.942834E+09 0.573460E+09 0.369374E+09 0.839022E+09 0.108454E+10
December 0.772094E+09 0.494582E+09 0.277512E+09 0.671480E+09 0.133683E+10
           
Annual Sum or Average 0.157849E+11 0.748809E+10 0.829684E+10 0.132616E+11 0.103693E+11
Minimum of Months 0.772094E+09 0.245544E+09 0.277512E+09 0.510612E+09 0.506382E+09
Maximum of Months 0.193672E+10 0.113485E+10 0.992299E+09 0.192588E+10 0.133683E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111573E+10 0.722150E+09 0.393582E+09 0.996155E+09 0.117591E+10
February 0.123119E+10 0.751307E+09 0.479879E+09 0.108555E+10 0.104870E+10
March 0.842894E+09 0.245535E+09 0.597359E+09 0.510595E+09 0.100340E+10
April 0.169369E+10 0.765617E+09 0.928077E+09 0.143384E+10 0.810283E+09
May 0.144718E+10 0.471005E+09 0.976175E+09 0.974451E+09 0.717278E+09
June 0.129017E+10 0.312152E+09 0.978014E+09 0.894283E+09 0.532006E+09
July 0.144445E+10 0.452191E+09 0.992261E+09 0.110527E+10 0.506362E+09
August 0.169279E+10 0.761454E+09 0.931341E+09 0.152549E+10 0.544311E+09
September 0.193665E+10 0.113480E+10 0.801845E+09 0.192581E+10 0.673916E+09
October 0.137473E+10 0.803594E+09 0.571134E+09 0.129927E+10 0.935453E+09
November 0.942800E+09 0.573439E+09 0.369360E+09 0.838992E+09 0.108450E+10
December 0.772065E+09 0.494563E+09 0.277502E+09 0.671456E+09 0.133678E+10
           
Annual Sum or Average 0.157843E+11 0.748781E+10 0.829653E+10 0.132612E+11 0.103689E+11
Minimum of Months 0.772065E+09 0.245535E+09 0.277502E+09 0.510595E+09 0.506362E+09
Maximum of Months 0.193665E+10 0.113480E+10 0.992261E+09 0.192581E+10 0.133678E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.434219E+09 0.143498E+09 0.290721E+09 0.160232E+09 0.151907E+10
February 0.694364E+09 0.293201E+09 0.401163E+09 0.389070E+09 0.134199E+10
March 0.695109E+09 0.132987E+09 0.562121E+09 0.261598E+09 0.126647E+10
April 0.158727E+10 0.630527E+09 0.956743E+09 0.128479E+10 0.991462E+09
May 0.192397E+10 0.782213E+09 0.114176E+10 0.159966E+10 0.816196E+09
June 0.201059E+10 0.827500E+09 0.118309E+10 0.183402E+10 0.637094E+09
July 0.211598E+10 0.932768E+09 0.118321E+10 0.202041E+10 0.624741E+09
August 0.177747E+10 0.769556E+09 0.100792E+10 0.169627E+10 0.684933E+09
September 0.138009E+10 0.618882E+09 0.761210E+09 0.125508E+10 0.794031E+09
October 0.760772E+09 0.273585E+09 0.487187E+09 0.484126E+09 0.116678E+10
November 0.398423E+09 0.116313E+09 0.282110E+09 0.141636E+09 0.143825E+10
December 0.233018E+09 49162664.67 0.183855E+09 31561910.86 0.183332E+10
           
Annual Sum or Average 0.140113E+11 0.557019E+10 0.844109E+10 0.111585E+11 0.131143E+11
Minimum of Months 0.233018E+09 49162664.67 0.183855E+09 31561910.86 0.624741E+09
Maximum of Months 0.211598E+10 0.932768E+09 0.118321E+10 0.202041E+10 0.183332E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.434219E+09 0.143498E+09 0.290721E+09 0.160232E+09 0.151907E+10
February 0.694364E+09 0.293201E+09 0.401163E+09 0.389070E+09 0.134199E+10
March 0.695109E+09 0.132987E+09 0.562121E+09 0.261598E+09 0.126647E+10
April 0.158727E+10 0.630527E+09 0.956743E+09 0.128479E+10 0.991462E+09
May 0.192397E+10 0.782213E+09 0.114176E+10 0.159966E+10 0.816196E+09
June 0.201059E+10 0.827500E+09 0.118309E+10 0.183402E+10 0.637094E+09
July 0.211598E+10 0.932768E+09 0.118321E+10 0.202041E+10 0.624741E+09
August 0.177747E+10 0.769556E+09 0.100792E+10 0.169627E+10 0.684933E+09
September 0.138009E+10 0.618882E+09 0.761210E+09 0.125508E+10 0.794031E+09
October 0.760772E+09 0.273585E+09 0.487187E+09 0.484126E+09 0.116678E+10
November 0.398423E+09 0.116313E+09 0.282110E+09 0.141636E+09 0.143825E+10
December 0.233018E+09 49162664.67 0.183855E+09 31561910.86 0.183332E+10
           
Annual Sum or Average 0.140113E+11 0.557019E+10 0.844109E+10 0.111585E+11 0.131143E+11
Minimum of Months 0.233018E+09 49162664.67 0.183855E+09 31561910.86 0.624741E+09
Maximum of Months 0.211598E+10 0.932768E+09 0.118321E+10 0.202041E+10 0.183332E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.434211E+09 0.143496E+09 0.290715E+09 0.160229E+09 0.151904E+10
February 0.694351E+09 0.293195E+09 0.401156E+09 0.389063E+09 0.134196E+10
March 0.695096E+09 0.132985E+09 0.562111E+09 0.261593E+09 0.126644E+10
April 0.158724E+10 0.630516E+09 0.956726E+09 0.128476E+10 0.991444E+09
May 0.192394E+10 0.782199E+09 0.114174E+10 0.159963E+10 0.816181E+09
June 0.201056E+10 0.827485E+09 0.118307E+10 0.183399E+10 0.637082E+09
July 0.211594E+10 0.932751E+09 0.118319E+10 0.202038E+10 0.624729E+09
August 0.177744E+10 0.769542E+09 0.100790E+10 0.169623E+10 0.684921E+09
September 0.138007E+10 0.618871E+09 0.761196E+09 0.125506E+10 0.794016E+09
October 0.760758E+09 0.273580E+09 0.487178E+09 0.484117E+09 0.116676E+10
November 0.398415E+09 0.116311E+09 0.282104E+09 0.141633E+09 0.143823E+10
December 0.233013E+09 49161766.36 0.183852E+09 31561334.15 0.183329E+10
           
Annual Sum or Average 0.140110E+11 0.557009E+10 0.844094E+10 0.111583E+11 0.131141E+11
Minimum of Months 0.233013E+09 49161766.36 0.183852E+09 31561334.15 0.624729E+09
Maximum of Months 0.211594E+10 0.932751E+09 0.118319E+10 0.202038E+10 0.183329E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.982953E+09 0.00 0.982953E+09 10780230.39 0.654932E+10
February 0.138638E+10 0.00 0.138638E+10 48472160.76 0.553161E+10
March 0.212406E+10 0.00 0.212406E+10 0.318179E+09 0.511957E+10
April 0.334655E+10 14792930.49 0.333176E+10 0.147112E+10 0.389496E+10
May 0.432333E+10 0.208177E+09 0.411515E+10 0.181132E+10 0.322903E+10
June 0.462493E+10 0.289516E+09 0.433541E+10 0.268550E+10 0.237855E+10
July 0.453323E+10 0.257975E+09 0.427525E+10 0.291872E+10 0.224996E+10
August 0.356349E+10 55570145.98 0.350792E+10 0.238706E+10 0.255066E+10
September 0.262499E+10 559084.73 0.262443E+10 0.145649E+10 0.327355E+10
October 0.173816E+10 0.00 0.173816E+10 0.397022E+09 0.468075E+10
November 0.101068E+10 0.00 0.101068E+10 22055594.27 0.561018E+10
December 0.711216E+09 0.00 0.711216E+09 0.00 0.686683E+10
           
Annual Sum or Average 0.309700E+11 0.826590E+09 0.301434E+11 0.135267E+11 0.519350E+11
Minimum of Months 0.711216E+09 0.00 0.711216E+09 0.00 0.224996E+10
Maximum of Months 0.462493E+10 0.289516E+09 0.433541E+10 0.291872E+10 0.686683E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133956E+10 0.538197E+09 0.801364E+09 0.498194E+09 0.397840E+10
February 0.180401E+10 0.666422E+09 0.113759E+10 0.860942E+09 0.337743E+10
March 0.208724E+10 0.411340E+09 0.167590E+10 0.881984E+09 0.309477E+10
April 0.542408E+10 0.254909E+10 0.287498E+10 0.472773E+10 0.238069E+10
May 0.589194E+10 0.256891E+10 0.332304E+10 0.499303E+10 0.208894E+10
June 0.564379E+10 0.225358E+10 0.339021E+10 0.512631E+10 0.156072E+10
July 0.595327E+10 0.252966E+10 0.342361E+10 0.567217E+10 0.147823E+10
August 0.564010E+10 0.269473E+10 0.294537E+10 0.556712E+10 0.159430E+10
September 0.491600E+10 0.261441E+10 0.230159E+10 0.468526E+10 0.199810E+10
October 0.245178E+10 0.101607E+10 0.143571E+10 0.169405E+10 0.287748E+10
November 0.123705E+10 0.421665E+09 0.815388E+09 0.481761E+09 0.341524E+10
December 0.947389E+09 0.352283E+09 0.595106E+09 0.287648E+09 0.424462E+10
           
Annual Sum or Average 0.433362E+11 0.186164E+11 0.247199E+11 0.354762E+11 0.320889E+11
Minimum of Months 0.947389E+09 0.352283E+09 0.595106E+09 0.287648E+09 0.147823E+10
Maximum of Months 0.595327E+10 0.269473E+10 0.342361E+10 0.567217E+10 0.424462E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.557901E+10 0.361099E+10 0.196803E+10 0.497221E+10 0.579061E+10
February 0.615632E+10 0.375678E+10 0.239954E+10 0.542186E+10 0.514290E+10
March 0.421472E+10 0.122775E+10 0.298697E+10 0.258666E+10 0.482735E+10
April 0.846897E+10 0.382833E+10 0.464064E+10 0.717256E+10 0.395547E+10
May 0.723632E+10 0.235518E+10 0.488114E+10 0.489424E+10 0.350087E+10
June 0.645120E+10 0.156086E+10 0.489034E+10 0.451289E+10 0.257339E+10
July 0.722268E+10 0.226110E+10 0.496157E+10 0.557541E+10 0.244667E+10
August 0.846447E+10 0.380752E+10 0.465696E+10 0.765687E+10 0.266141E+10
September 0.968383E+10 0.567439E+10 0.400945E+10 0.960516E+10 0.332401E+10
October 0.687407E+10 0.401823E+10 0.285584E+10 0.649275E+10 0.455422E+10
November 0.471429E+10 0.286738E+10 0.184691E+10 0.420864E+10 0.520066E+10
December 0.386057E+10 0.247298E+10 0.138759E+10 0.339186E+10 0.636106E+10
           
Annual Sum or Average 0.789265E+11 0.374415E+11 0.414850E+11 0.664911E+11 0.503386E+11
Minimum of Months 0.386057E+10 0.122775E+10 0.138759E+10 0.258666E+10 0.244667E+10
Maximum of Months 0.968383E+10 0.567439E+10 0.496157E+10 0.960516E+10 0.636106E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.130264E+10 0.430491E+09 0.872153E+09 0.522374E+09 0.409762E+10
February 0.208307E+10 0.879593E+09 0.120348E+10 0.123416E+10 0.352773E+10
March 0.208530E+10 0.398957E+09 0.168635E+10 0.900979E+09 0.321316E+10
April 0.476176E+10 0.189156E+10 0.287020E+10 0.401059E+10 0.259699E+10
May 0.577186E+10 0.234662E+10 0.342524E+10 0.488650E+10 0.227598E+10
June 0.603172E+10 0.248247E+10 0.354925E+10 0.560336E+10 0.173347E+10
July 0.634788E+10 0.279828E+10 0.354960E+10 0.620315E+10 0.166597E+10
August 0.533237E+10 0.230865E+10 0.302372E+10 0.525192E+10 0.180006E+10
September 0.414023E+10 0.185663E+10 0.228361E+10 0.385453E+10 0.218742E+10
October 0.228229E+10 0.820747E+09 0.146155E+10 0.155598E+10 0.303158E+10
November 0.119526E+10 0.348936E+09 0.846320E+09 0.486844E+09 0.358640E+10
December 0.699046E+09 0.147486E+09 0.551559E+09 0.122960E+09 0.449238E+10
           
Annual Sum or Average 0.420334E+11 0.167104E+11 0.253230E+11 0.346334E+11 0.342088E+11
Minimum of Months 0.699046E+09 0.147486E+09 0.551559E+09 0.122960E+09 0.166597E+10
Maximum of Months 0.634788E+10 0.279828E+10 0.354960E+10 0.620315E+10 0.449238E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.982953E+09 0.00 0.982953E+09 33977139.41 0.574474E+10
February 0.138638E+10 0.00 0.138638E+10 0.107955E+09 0.489916E+10
March 0.212406E+10 0.00 0.212406E+10 0.421922E+09 0.459448E+10
April 0.334655E+10 14792930.49 0.333176E+10 0.154637E+10 0.363202E+10
May 0.432333E+10 0.208177E+09 0.411515E+10 0.189229E+10 0.302328E+10
June 0.462493E+10 0.289516E+09 0.433541E+10 0.271666E+10 0.228232E+10
July 0.453323E+10 0.257975E+09 0.427525E+10 0.294356E+10 0.216271E+10
August 0.356349E+10 55570145.98 0.350792E+10 0.240613E+10 0.243731E+10
September 0.262499E+10 559084.73 0.262443E+10 0.152126E+10 0.305971E+10
October 0.173816E+10 0.00 0.173816E+10 0.499595E+09 0.416402E+10
November 0.101068E+10 0.00 0.101068E+10 50272382.69 0.492833E+10
December 0.711216E+09 0.00 0.711216E+09 2254208.28 0.610133E+10
           
Annual Sum or Average 0.309700E+11 0.826590E+09 0.301434E+11 0.141423E+11 0.470294E+11
Minimum of Months 0.711216E+09 0.00 0.711216E+09 2254208.28 0.216271E+10
Maximum of Months 0.462493E+10 0.289516E+09 0.433541E+10 0.294356E+10 0.610133E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133956E+10 0.538197E+09 0.801364E+09 0.549311E+09 0.356897E+10
February 0.180401E+10 0.666422E+09 0.113759E+10 0.928471E+09 0.306787E+10
March 0.208724E+10 0.411340E+09 0.167590E+10 0.955802E+09 0.285117E+10
April 0.542408E+10 0.254909E+10 0.287498E+10 0.477254E+10 0.226211E+10
May 0.589194E+10 0.256891E+10 0.332304E+10 0.503599E+10 0.199595E+10
June 0.564379E+10 0.225358E+10 0.339021E+10 0.513189E+10 0.151769E+10
July 0.595327E+10 0.252966E+10 0.342361E+10 0.566912E+10 0.144312E+10
August 0.564010E+10 0.269473E+10 0.294537E+10 0.556648E+10 0.155208E+10
September 0.491600E+10 0.261441E+10 0.230159E+10 0.471347E+10 0.191034E+10
October 0.245178E+10 0.101607E+10 0.143571E+10 0.176403E+10 0.262647E+10
November 0.123705E+10 0.421665E+09 0.815388E+09 0.523424E+09 0.308643E+10
December 0.947389E+09 0.352283E+09 0.595106E+09 0.322187E+09 0.384496E+10
           
Annual Sum or Average 0.433362E+11 0.186164E+11 0.247199E+11 0.359327E+11 0.297272E+11
Minimum of Months 0.947389E+09 0.352283E+09 0.595106E+09 0.322187E+09 0.144312E+10
Maximum of Months 0.595327E+10 0.269473E+10 0.342361E+10 0.566912E+10 0.384496E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.557901E+10 0.361099E+10 0.196803E+10 0.512254E+10 0.518088E+10
February 0.615632E+10 0.375678E+10 0.239954E+10 0.554872E+10 0.467060E+10
March 0.421472E+10 0.122775E+10 0.298697E+10 0.270748E+10 0.441678E+10
April 0.846897E+10 0.382833E+10 0.464064E+10 0.723924E+10 0.373372E+10
May 0.723632E+10 0.235518E+10 0.488114E+10 0.496813E+10 0.330960E+10
June 0.645120E+10 0.156086E+10 0.489034E+10 0.454747E+10 0.247782E+10
July 0.722268E+10 0.226110E+10 0.496157E+10 0.560094E+10 0.236096E+10
August 0.846447E+10 0.380752E+10 0.465696E+10 0.767918E+10 0.255988E+10
September 0.968383E+10 0.567439E+10 0.400945E+10 0.965225E+10 0.314857E+10
October 0.687407E+10 0.401823E+10 0.285584E+10 0.659075E+10 0.414387E+10
November 0.471429E+10 0.286738E+10 0.184691E+10 0.430568E+10 0.467956E+10
December 0.386057E+10 0.247298E+10 0.138759E+10 0.349640E+10 0.575959E+10
           
Annual Sum or Average 0.789265E+11 0.374415E+11 0.414850E+11 0.674588E+11 0.464418E+11
Minimum of Months 0.386057E+10 0.122775E+10 0.138759E+10 0.270748E+10 0.236096E+10
Maximum of Months 0.968383E+10 0.567439E+10 0.496157E+10 0.965225E+10 0.575959E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.130264E+10 0.430491E+09 0.872153E+09 0.558976E+09 0.373600E+10
February 0.208307E+10 0.879593E+09 0.120348E+10 0.127800E+10 0.325236E+10
March 0.208530E+10 0.398957E+09 0.168635E+10 0.954176E+09 0.298232E+10
April 0.476176E+10 0.189156E+10 0.287020E+10 0.404952E+10 0.246519E+10
May 0.577186E+10 0.234662E+10 0.342524E+10 0.492005E+10 0.216712E+10
June 0.603172E+10 0.248247E+10 0.354925E+10 0.561257E+10 0.167311E+10
July 0.634788E+10 0.279828E+10 0.354960E+10 0.620670E+10 0.161126E+10
August 0.533237E+10 0.230865E+10 0.302372E+10 0.526013E+10 0.173524E+10
September 0.414023E+10 0.185663E+10 0.228361E+10 0.388199E+10 0.208042E+10
October 0.228229E+10 0.820747E+09 0.146155E+10 0.160629E+10 0.279701E+10
November 0.119526E+10 0.348936E+09 0.846320E+09 0.513462E+09 0.328904E+10
December 0.699046E+09 0.147486E+09 0.551559E+09 0.137621E+09 0.414175E+10
           
Annual Sum or Average 0.420334E+11 0.167104E+11 0.253230E+11 0.349795E+11 0.319308E+11
Minimum of Months 0.699046E+09 0.147486E+09 0.551559E+09 0.137621E+09 0.161126E+10
Maximum of Months 0.634788E+10 0.279828E+10 0.354960E+10 0.620670E+10 0.414175E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.90 2667.37 366.98 0.00 366.98 0.00 0.00
February 10.65 2508.53 573.06 0.00 573.06 0.00 0.00
March 101.42 2081.79 793.02 0.00 793.02 0.00 0.00
April 540.64 1607.44 1291.09 5.71 1285.38 0.00 0.00
May 653.62 1272.92 1614.12 77.72 1536.39 0.00 0.00
June 1014.81 963.69 1784.27 111.69 1672.58 0.00 0.00
July 1056.15 891.58 1692.48 96.31 1596.17 0.00 0.00
August 861.97 1012.23 1330.43 20.75 1309.69 0.00 0.00
September 538.77 1335.95 1012.71 0.22 1012.49 0.00 0.00
October 127.35 1900.39 648.94 0.00 648.94 0.00 0.00
November 3.91 2419.33 389.92 0.00 389.92 0.00 0.00
December 0.00 2916.85 265.53 0.00 265.53 0.00 0.00
               
Annual Sum or Average 411.28 1794.71 982.03 26.21 955.82 0.00 0.00
Minimum of Months 0.00 891.58 265.53 0.00 265.53 0.00 0.00
Maximum of Months 1056.15 2916.85 1784.27 111.69 1672.58 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 174.03 1594.80 500.14 200.94 299.20 0.00 0.00
February 340.19 1494.75 745.71 275.47 470.24 0.00 0.00
March 308.08 1234.87 779.29 153.58 625.71 0.00 0.00
April 1822.43 946.49 2092.63 983.45 1109.18 0.00 0.00
May 1860.99 812.76 2199.81 959.12 1240.68 0.00 0.00
June 1977.03 623.35 2177.40 869.44 1307.96 0.00 0.00
July 2120.81 566.21 2222.71 944.47 1278.23 0.00 0.00
August 2079.62 602.77 2105.78 1006.10 1099.68 0.00 0.00
September 1802.95 802.61 1896.61 1008.65 887.96 0.00 0.00
October 615.98 1151.03 915.39 379.36 536.03 0.00 0.00
November 173.34 1437.46 477.26 162.68 314.58 0.00 0.00
December 96.68 1731.43 353.72 131.53 222.19 0.00 0.00
               
Annual Sum or Average 1117.10 1081.26 1374.19 590.32 783.86 0.00 0.00
Minimum of Months 96.68 566.21 353.72 131.53 222.19 0.00 0.00
Maximum of Months 2120.81 1731.43 2222.71 1008.65 1307.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1859.67 2195.25 2082.90 1348.14 734.76 0.00 0.00
February 2243.69 2167.52 2544.70 1552.85 991.85 0.00 0.00
March 953.20 1873.20 1573.55 458.38 1115.18 0.00 0.00
April 2765.98 1563.10 3267.26 1476.93 1790.33 0.00 0.00
May 1819.15 1339.05 2701.66 879.29 1822.37 0.00 0.00
June 1725.14 1026.28 2488.83 602.16 1886.66 0.00 0.00
July 2063.37 945.30 2696.57 844.17 1852.40 0.00 0.00
August 2847.86 1016.15 3160.19 1421.52 1738.67 0.00 0.00
September 3715.03 1300.03 3735.94 2189.12 1546.82 0.00 0.00
October 2425.53 1746.35 2566.41 1500.19 1066.22 0.00 0.00
November 1618.48 2092.08 1818.73 1106.21 712.52 0.00 0.00
December 1253.51 2495.56 1441.33 923.27 518.05 0.00 0.00
               
Annual Sum or Average 2102.61 1644.03 2502.67 1187.22 1315.45 0.00 0.00
Minimum of Months 953.20 945.30 1441.33 458.38 518.05 0.00 0.00
Maximum of Months 3715.03 2495.56 3735.94 2189.12 1886.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 179.47 1701.45 486.35 160.73 325.63 0.00 0.00
February 482.47 1664.16 861.06 363.59 497.47 0.00 0.00
March 293.01 1418.53 778.57 148.95 629.61 0.00 0.00
April 1487.01 1147.52 1837.11 729.77 1107.34 0.00 0.00
May 1791.73 914.19 2154.97 876.13 1278.85 0.00 0.00
June 2122.70 737.37 2327.06 957.75 1369.31 0.00 0.00
July 2262.99 699.75 2370.04 1044.76 1325.27 0.00 0.00
August 1899.93 767.17 1990.89 861.95 1128.93 0.00 0.00
September 1452.63 919.01 1597.32 716.29 881.02 0.00 0.00
October 542.25 1306.87 852.11 306.43 545.68 0.00 0.00
November 163.93 1664.63 461.13 134.62 326.51 0.00 0.00
December 35.35 2053.44 260.99 55.07 205.93 0.00 0.00
               
Annual Sum or Average 1061.49 1247.55 1332.88 529.89 802.99 0.00 0.00
Minimum of Months 35.35 699.75 260.99 55.07 205.93 0.00 0.00
Maximum of Months 2262.99 2053.44 2370.04 1044.76 1369.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4.02 2445.24 366.99 0.00 366.99 0.00 0.00
February 20.04 2286.55 573.07 0.00 573.07 0.00 0.00
March 118.79 1911.43 793.03 0.00 793.03 0.00 0.00
April 567.56 1502.69 1291.11 5.71 1285.40 0.00 0.00
May 676.27 1205.58 1614.15 77.72 1536.42 0.00 0.00
June 1036.07 917.65 1784.31 111.70 1672.61 0.00 0.00
July 1089.73 840.04 1692.51 96.32 1596.20 0.00 0.00
August 891.22 952.31 1330.46 20.75 1309.71 0.00 0.00
September 561.92 1262.94 1012.73 0.22 1012.51 0.00 0.00
October 148.23 1747.59 648.95 0.00 648.95 0.00 0.00
November 8.51 2164.42 389.92 0.00 389.92 0.00 0.00
December 0.00 2563.78 265.54 0.00 265.54 0.00 0.00
               
Annual Sum or Average 428.93 1646.85 982.05 26.21 955.84 0.00 0.00
Minimum of Months 0.00 840.04 265.54 0.00 265.54 0.00 0.00
Maximum of Months 1089.73 2563.78 1784.31 111.70 1672.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 186.00 1485.36 500.14 200.94 299.20 0.00 0.00
February 355.88 1396.09 745.71 275.47 470.23 0.00 0.00
March 329.30 1155.45 779.28 153.58 625.71 0.00 0.00
April 1823.97 918.48 2092.62 983.45 1109.18 0.00 0.00
May 1864.18 779.92 2199.80 959.12 1240.68 0.00 0.00
June 1977.74 602.13 2177.39 869.43 1307.95 0.00 0.00
July 2117.75 551.91 2222.70 944.47 1278.23 0.00 0.00
August 2078.53 595.24 2105.77 1006.10 1099.68 0.00 0.00
September 1807.59 770.87 1896.61 1008.65 887.96 0.00 0.00
October 632.48 1074.33 915.39 379.36 536.03 0.00 0.00
November 185.86 1317.61 477.26 162.68 314.58 0.00 0.00
December 107.40 1584.76 353.71 131.53 222.19 0.00 0.00
               
Annual Sum or Average 1124.94 1017.53 1374.18 590.32 783.86 0.00 0.00
Minimum of Months 107.40 551.91 353.71 131.53 222.19 0.00 0.00
Maximum of Months 2117.75 1584.76 2222.70 1008.65 1307.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1856.41 2161.97 2082.97 1348.19 734.78 0.00 0.00
February 2241.18 2125.87 2544.77 1552.90 991.87 0.00 0.00
March 965.75 1802.33 1573.60 458.39 1115.21 0.00 0.00
April 2767.19 1526.03 3267.35 1476.98 1790.37 0.00 0.00
May 1827.30 1307.07 2701.73 879.32 1822.41 0.00 0.00
June 1741.09 992.82 2488.89 602.18 1886.70 0.00 0.00
July 2081.62 913.48 2696.64 844.20 1852.44 0.00 0.00
August 2858.75 993.66 3160.27 1421.56 1738.71 0.00 0.00
September 3705.69 1282.41 3736.05 2189.19 1546.85 0.00 0.00
October 2424.12 1700.35 2566.48 1500.24 1066.25 0.00 0.00
November 1623.70 2006.43 1818.79 1106.24 712.54 0.00 0.00
December 1266.37 2374.95 1441.37 923.30 518.07 0.00 0.00
               
Annual Sum or Average 2108.42 1596.23 2502.74 1187.26 1315.48 0.00 0.00
Minimum of Months 965.75 913.48 1441.37 458.39 518.07 0.00 0.00
Maximum of Months 3705.69 2374.95 3736.05 2189.19 1886.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 195.03 1529.87 486.35 160.73 325.62 0.00 0.00
February 510.15 1458.22 861.06 363.59 497.47 0.00 0.00
March 336.39 1199.65 778.56 148.95 629.61 0.00 0.00
April 1547.30 1001.93 1837.10 729.77 1107.33 0.00 0.00
May 1824.41 849.75 2154.97 876.13 1278.84 0.00 0.00
June 2161.79 668.78 2327.05 957.74 1369.31 0.00 0.00
July 2315.99 622.00 2370.03 1044.76 1325.27 0.00 0.00
August 1960.84 672.07 1990.88 861.95 1128.93 0.00 0.00
September 1487.09 843.91 1597.31 716.29 881.02 0.00 0.00
October 580.94 1131.86 852.11 306.43 545.68 0.00 0.00
November 187.83 1383.64 461.13 134.62 326.51 0.00 0.00
December 45.91 1677.26 260.99 55.07 205.93 0.00 0.00
               
Annual Sum or Average 1098.22 1084.75 1332.87 529.88 802.99 0.00 0.00
Minimum of Months 45.91 622.00 260.99 55.07 205.93 0.00 0.00
Maximum of Months 2315.99 1677.26 2370.03 1044.76 1369.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.69 2144.84 366.99 0.00 366.99 0.00 0.00
February 44.62 2025.12 573.07 0.00 573.07 0.00 0.00
March 157.53 1715.38 793.03 0.00 793.03 0.00 0.00
April 596.59 1401.24 1291.11 5.71 1285.40 0.00 0.00
May 706.50 1128.76 1614.15 77.72 1536.42 0.00 0.00
June 1048.10 880.53 1784.31 111.70 1672.61 0.00 0.00
July 1099.00 807.46 1692.51 96.32 1596.20 0.00 0.00
August 898.35 909.99 1330.46 20.75 1309.71 0.00 0.00
September 586.91 1180.44 1012.73 0.22 1012.51 0.00 0.00
October 186.53 1554.67 648.95 0.00 648.95 0.00 0.00
November 19.40 1901.36 389.92 0.00 389.92 0.00 0.00
December 0.84 2277.98 265.54 0.00 265.54 0.00 0.00
               
Annual Sum or Average 448.45 1491.29 982.05 26.21 955.84 0.00 0.00
Minimum of Months 0.84 807.46 265.54 0.00 265.54 0.00 0.00
Maximum of Months 1099.00 2277.98 1784.31 111.70 1672.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 205.09 1332.50 500.14 200.94 299.20 0.00 0.00
February 383.79 1268.13 745.71 275.47 470.23 0.00 0.00
March 356.86 1064.50 779.28 153.58 625.71 0.00 0.00
April 1841.26 872.73 2092.62 983.45 1109.18 0.00 0.00
May 1880.22 745.20 2199.80 959.12 1240.68 0.00 0.00
June 1979.89 585.53 2177.39 869.43 1307.95 0.00 0.00
July 2116.61 538.80 2222.70 944.47 1278.23 0.00 0.00
August 2078.28 579.48 2105.77 1006.10 1099.68 0.00 0.00
September 1818.47 737.01 1896.61 1008.65 887.96 0.00 0.00
October 658.61 980.61 915.39 379.36 536.03 0.00 0.00
November 201.94 1190.75 477.26 162.68 314.58 0.00 0.00
December 120.29 1435.55 353.71 131.53 222.19 0.00 0.00
               
Annual Sum or Average 1139.42 942.64 1374.18 590.32 783.86 0.00 0.00
Minimum of Months 120.29 538.80 353.71 131.53 222.19 0.00 0.00
Maximum of Months 2116.61 1435.55 2222.70 1008.65 1307.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1912.54 1934.32 2082.97 1348.19 734.78 0.00 0.00
February 2293.62 1930.64 2544.77 1552.90 991.87 0.00 0.00
March 1010.86 1649.04 1573.60 458.39 1115.21 0.00 0.00
April 2792.92 1440.48 3267.35 1476.98 1790.37 0.00 0.00
May 1854.89 1235.66 2701.73 879.32 1822.41 0.00 0.00
June 1754.42 955.95 2488.89 602.18 1886.70 0.00 0.00
July 2091.15 881.48 2696.64 844.20 1852.44 0.00 0.00
August 2867.08 955.75 3160.27 1421.56 1738.71 0.00 0.00
September 3723.86 1214.73 3736.05 2189.19 1546.85 0.00 0.00
October 2460.70 1547.14 2566.48 1500.24 1066.25 0.00 0.00
November 1661.14 1805.39 1818.79 1106.24 712.54 0.00 0.00
December 1305.41 2150.38 1441.37 923.30 518.07 0.00 0.00
               
Annual Sum or Average 2139.10 1472.66 2502.74 1187.26 1315.48 0.00 0.00
Minimum of Months 1010.86 881.48 1441.37 458.39 518.07 0.00 0.00
Maximum of Months 3723.86 2150.38 3736.05 2189.19 1886.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 208.70 1394.86 486.35 160.73 325.62 0.00 0.00
February 528.27 1344.39 861.06 363.59 497.47 0.00 0.00
March 356.25 1113.47 778.56 148.95 629.61 0.00 0.00
April 1562.32 951.08 1837.10 729.77 1107.33 0.00 0.00
May 1836.94 809.11 2154.97 876.13 1278.84 0.00 0.00
June 2165.34 645.49 2327.05 957.74 1369.31 0.00 0.00
July 2317.32 601.58 2370.03 1044.76 1325.27 0.00 0.00
August 1963.91 647.86 1990.88 861.95 1128.93 0.00 0.00
September 1497.68 802.63 1597.31 716.29 881.02 0.00 0.00
October 599.72 1044.29 852.11 306.43 545.68 0.00 0.00
November 198.09 1268.92 461.13 134.62 326.51 0.00 0.00
December 51.38 1546.35 260.99 55.07 205.93 0.00 0.00
               
Annual Sum or Average 1109.19 1012.52 1332.87 529.88 802.99 0.00 0.00
Minimum of Months 51.38 601.58 260.99 55.07 205.93 0.00 0.00
Maximum of Months 2317.32 1546.35 2370.03 1044.76 1369.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 5096207.15 0.714428E+10 0.982933E+09 0.00 0.982933E+09 0.00 0.00
February 25759946.09 0.606864E+10 0.138635E+10 0.00 0.138635E+10 0.00 0.00
March 0.271652E+09 0.557587E+10 0.212402E+10 0.00 0.212402E+10 0.00 0.00
April 0.140135E+10 0.416647E+10 0.334649E+10 14792489.34 0.333170E+10 0.00 0.00
May 0.175065E+10 0.340939E+10 0.432325E+10 0.208171E+09 0.411508E+10 0.00 0.00
June 0.263039E+10 0.249789E+10 0.462484E+10 0.289507E+09 0.433533E+10 0.00 0.00
July 0.282879E+10 0.238802E+10 0.453315E+10 0.257968E+09 0.427518E+10 0.00 0.00
August 0.230869E+10 0.271117E+10 0.356343E+10 55568488.77 0.350786E+10 0.00 0.00
September 0.139650E+10 0.346278E+10 0.262494E+10 559068.06 0.262438E+10 0.00 0.00
October 0.341092E+09 0.509002E+10 0.173812E+10 0.00 0.173812E+10 0.00 0.00
November 10147245.47 0.627091E+10 0.101066E+10 0.00 0.101066E+10 0.00 0.00
December 0.00 0.781249E+10 0.711201E+09 0.00 0.711201E+09 0.00 0.00
               
Annual Sum or Average 0.129701E+11 0.565979E+11 0.309694E+11 0.826566E+09 0.301428E+11 0.00 0.00
Minimum of Months 0.00 0.238802E+10 0.711201E+09 0.00 0.711201E+09 0.00 0.00
Maximum of Months 0.282879E+10 0.781249E+10 0.462484E+10 0.289507E+09 0.433533E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.466125E+09 0.427151E+10 0.133957E+10 0.538200E+09 0.801368E+09 0.00 0.00
February 0.822994E+09 0.361610E+10 0.180402E+10 0.666425E+09 0.113759E+10 0.00 0.00
March 0.825173E+09 0.330748E+10 0.208724E+10 0.411342E+09 0.167590E+10 0.00 0.00
April 0.472373E+10 0.245331E+10 0.542410E+10 0.254910E+10 0.287499E+10 0.00 0.00
May 0.498447E+10 0.217691E+10 0.589197E+10 0.256892E+10 0.332305E+10 0.00 0.00
June 0.512446E+10 0.161573E+10 0.564381E+10 0.225358E+10 0.339022E+10 0.00 0.00
July 0.568037E+10 0.151654E+10 0.595330E+10 0.252967E+10 0.342362E+10 0.00 0.00
August 0.557007E+10 0.161447E+10 0.564012E+10 0.269474E+10 0.294538E+10 0.00 0.00
September 0.467324E+10 0.208038E+10 0.491602E+10 0.261442E+10 0.230160E+10 0.00 0.00
October 0.164984E+10 0.308292E+10 0.245179E+10 0.101607E+10 0.143572E+10 0.00 0.00
November 0.449292E+09 0.372589E+10 0.123706E+10 0.421667E+09 0.815391E+09 0.00 0.00
December 0.258952E+09 0.463746E+10 0.947392E+09 0.352284E+09 0.595108E+09 0.00 0.00
               
Annual Sum or Average 0.352287E+11 0.340987E+11 0.433364E+11 0.186164E+11 0.247200E+11 0.00 0.00
Minimum of Months 0.258952E+09 0.151654E+10 0.947392E+09 0.352284E+09 0.595108E+09 0.00 0.00
Maximum of Months 0.568037E+10 0.463746E+10 0.595330E+10 0.269474E+10 0.342362E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.498093E+10 0.587975E+10 0.557884E+10 0.361087E+10 0.196797E+10 0.00 0.00
February 0.542793E+10 0.524366E+10 0.615613E+10 0.375666E+10 0.239947E+10 0.00 0.00
March 0.255305E+10 0.501718E+10 0.421460E+10 0.122771E+10 0.298689E+10 0.00 0.00
April 0.716943E+10 0.405155E+10 0.846874E+10 0.382821E+10 0.464053E+10 0.00 0.00
May 0.487241E+10 0.358651E+10 0.723614E+10 0.235510E+10 0.488103E+10 0.00 0.00
June 0.447156E+10 0.266011E+10 0.645104E+10 0.156081E+10 0.489023E+10 0.00 0.00
July 0.552652E+10 0.253189E+10 0.722250E+10 0.226103E+10 0.496147E+10 0.00 0.00
August 0.762772E+10 0.272164E+10 0.846425E+10 0.380739E+10 0.465685E+10 0.00 0.00
September 0.962935E+10 0.336969E+10 0.968355E+10 0.567420E+10 0.400935E+10 0.00 0.00
October 0.649654E+10 0.467741E+10 0.687386E+10 0.401810E+10 0.285576E+10 0.00 0.00
November 0.419510E+10 0.542266E+10 0.471415E+10 0.286729E+10 0.184686E+10 0.00 0.00
December 0.335739E+10 0.668410E+10 0.386045E+10 0.247290E+10 0.138756E+10 0.00 0.00
               
Annual Sum or Average 0.663079E+11 0.518461E+11 0.789243E+11 0.374403E+11 0.414840E+11 0.00 0.00
Minimum of Months 0.255305E+10 0.253189E+10 0.386045E+10 0.122771E+10 0.138756E+10 0.00 0.00
Maximum of Months 0.962935E+10 0.668410E+10 0.968355E+10 0.567420E+10 0.496147E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.480693E+09 0.455717E+10 0.130265E+10 0.430493E+09 0.872157E+09 0.00 0.00
February 0.116720E+10 0.402594E+10 0.208308E+10 0.879596E+09 0.120348E+10 0.00 0.00
March 0.784789E+09 0.379938E+10 0.208531E+10 0.398959E+09 0.168635E+10 0.00 0.00
April 0.385434E+10 0.297437E+10 0.476178E+10 0.189157E+10 0.287021E+10 0.00 0.00
May 0.479896E+10 0.244857E+10 0.577188E+10 0.234663E+10 0.342526E+10 0.00 0.00
June 0.550203E+10 0.191127E+10 0.603175E+10 0.248248E+10 0.354926E+10 0.00 0.00
July 0.606120E+10 0.187421E+10 0.634790E+10 0.279829E+10 0.354962E+10 0.00 0.00
August 0.508877E+10 0.205479E+10 0.533239E+10 0.230865E+10 0.302373E+10 0.00 0.00
September 0.376523E+10 0.238208E+10 0.414025E+10 0.185664E+10 0.228362E+10 0.00 0.00
October 0.145237E+10 0.350032E+10 0.228230E+10 0.820751E+09 0.146155E+10 0.00 0.00
November 0.424904E+09 0.431473E+10 0.119526E+10 0.348937E+09 0.846324E+09 0.00 0.00
December 94685155.86 0.549993E+10 0.699049E+09 0.147487E+09 0.551562E+09 0.00 0.00
               
Annual Sum or Average 0.334752E+11 0.393428E+11 0.420336E+11 0.167105E+11 0.253231E+11 0.00 0.00
Minimum of Months 94685155.86 0.187421E+10 0.699049E+09 0.147487E+09 0.551562E+09 0.00 0.00
Maximum of Months 0.606120E+10 0.549993E+10 0.634790E+10 0.279829E+10 0.354962E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 10780230.39 0.654932E+10 0.982953E+09 0.00 0.982953E+09 0.00 0.00
February 48472160.76 0.553161E+10 0.138638E+10 0.00 0.138638E+10 0.00 0.00
March 0.318179E+09 0.511957E+10 0.212406E+10 0.00 0.212406E+10 0.00 0.00
April 0.147112E+10 0.389496E+10 0.334655E+10 14792930.49 0.333176E+10 0.00 0.00
May 0.181132E+10 0.322903E+10 0.432333E+10 0.208177E+09 0.411515E+10 0.00 0.00
June 0.268550E+10 0.237855E+10 0.462493E+10 0.289516E+09 0.433541E+10 0.00 0.00
July 0.291872E+10 0.224996E+10 0.453323E+10 0.257975E+09 0.427525E+10 0.00 0.00
August 0.238706E+10 0.255066E+10 0.356349E+10 55570145.98 0.350792E+10 0.00 0.00
September 0.145649E+10 0.327355E+10 0.262499E+10 559084.73 0.262443E+10 0.00 0.00
October 0.397022E+09 0.468075E+10 0.173816E+10 0.00 0.173816E+10 0.00 0.00
November 22055594.27 0.561018E+10 0.101068E+10 0.00 0.101068E+10 0.00 0.00
December 0.00 0.686683E+10 0.711216E+09 0.00 0.711216E+09 0.00 0.00
               
Annual Sum or Average 0.135267E+11 0.519350E+11 0.309700E+11 0.826590E+09 0.301434E+11 0.00 0.00
Minimum of Months 0.00 0.224996E+10 0.711216E+09 0.00 0.711216E+09 0.00 0.00
Maximum of Months 0.291872E+10 0.686683E+10 0.462493E+10 0.289516E+09 0.433541E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.498194E+09 0.397840E+10 0.133956E+10 0.538197E+09 0.801364E+09 0.00 0.00
February 0.860942E+09 0.337743E+10 0.180401E+10 0.666422E+09 0.113759E+10 0.00 0.00
March 0.881984E+09 0.309477E+10 0.208724E+10 0.411340E+09 0.167590E+10 0.00 0.00
April 0.472773E+10 0.238069E+10 0.542408E+10 0.254909E+10 0.287498E+10 0.00 0.00
May 0.499303E+10 0.208894E+10 0.589194E+10 0.256891E+10 0.332304E+10 0.00 0.00
June 0.512631E+10 0.156072E+10 0.564379E+10 0.225358E+10 0.339021E+10 0.00 0.00
July 0.567217E+10 0.147823E+10 0.595327E+10 0.252966E+10 0.342361E+10 0.00 0.00
August 0.556712E+10 0.159430E+10 0.564010E+10 0.269473E+10 0.294537E+10 0.00 0.00
September 0.468526E+10 0.199810E+10 0.491600E+10 0.261441E+10 0.230159E+10 0.00 0.00
October 0.169405E+10 0.287748E+10 0.245178E+10 0.101607E+10 0.143571E+10 0.00 0.00
November 0.481761E+09 0.341524E+10 0.123705E+10 0.421665E+09 0.815388E+09 0.00 0.00
December 0.287648E+09 0.424462E+10 0.947389E+09 0.352283E+09 0.595106E+09 0.00 0.00
               
Annual Sum or Average 0.354762E+11 0.320889E+11 0.433362E+11 0.186164E+11 0.247199E+11 0.00 0.00
Minimum of Months 0.287648E+09 0.147823E+10 0.947389E+09 0.352283E+09 0.595106E+09 0.00 0.00
Maximum of Months 0.567217E+10 0.424462E+10 0.595327E+10 0.269473E+10 0.342361E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.497221E+10 0.579061E+10 0.557901E+10 0.361099E+10 0.196803E+10 0.00 0.00
February 0.542186E+10 0.514290E+10 0.615632E+10 0.375678E+10 0.239954E+10 0.00 0.00
March 0.258666E+10 0.482735E+10 0.421472E+10 0.122775E+10 0.298697E+10 0.00 0.00
April 0.717256E+10 0.395547E+10 0.846897E+10 0.382833E+10 0.464064E+10 0.00 0.00
May 0.489424E+10 0.350087E+10 0.723632E+10 0.235518E+10 0.488114E+10 0.00 0.00
June 0.451289E+10 0.257339E+10 0.645120E+10 0.156086E+10 0.489034E+10 0.00 0.00
July 0.557541E+10 0.244667E+10 0.722268E+10 0.226110E+10 0.496157E+10 0.00 0.00
August 0.765687E+10 0.266141E+10 0.846447E+10 0.380752E+10 0.465696E+10 0.00 0.00
September 0.960516E+10 0.332401E+10 0.968383E+10 0.567439E+10 0.400945E+10 0.00 0.00
October 0.649275E+10 0.455422E+10 0.687407E+10 0.401823E+10 0.285584E+10 0.00 0.00
November 0.420864E+10 0.520066E+10 0.471429E+10 0.286738E+10 0.184691E+10 0.00 0.00
December 0.339186E+10 0.636106E+10 0.386057E+10 0.247298E+10 0.138759E+10 0.00 0.00
               
Annual Sum or Average 0.664911E+11 0.503386E+11 0.789265E+11 0.374415E+11 0.414850E+11 0.00 0.00
Minimum of Months 0.258666E+10 0.244667E+10 0.386057E+10 0.122775E+10 0.138759E+10 0.00 0.00
Maximum of Months 0.960516E+10 0.636106E+10 0.968383E+10 0.567439E+10 0.496157E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.522374E+09 0.409762E+10 0.130264E+10 0.430491E+09 0.872153E+09 0.00 0.00
February 0.123416E+10 0.352773E+10 0.208307E+10 0.879593E+09 0.120348E+10 0.00 0.00
March 0.900979E+09 0.321316E+10 0.208530E+10 0.398957E+09 0.168635E+10 0.00 0.00
April 0.401059E+10 0.259699E+10 0.476176E+10 0.189156E+10 0.287020E+10 0.00 0.00
May 0.488650E+10 0.227598E+10 0.577186E+10 0.234662E+10 0.342524E+10 0.00 0.00
June 0.560336E+10 0.173347E+10 0.603172E+10 0.248247E+10 0.354925E+10 0.00 0.00
July 0.620315E+10 0.166597E+10 0.634788E+10 0.279828E+10 0.354960E+10 0.00 0.00
August 0.525192E+10 0.180006E+10 0.533237E+10 0.230865E+10 0.302372E+10 0.00 0.00
September 0.385453E+10 0.218742E+10 0.414023E+10 0.185663E+10 0.228361E+10 0.00 0.00
October 0.155598E+10 0.303158E+10 0.228229E+10 0.820747E+09 0.146155E+10 0.00 0.00
November 0.486844E+09 0.358640E+10 0.119526E+10 0.348936E+09 0.846320E+09 0.00 0.00
December 0.122960E+09 0.449238E+10 0.699046E+09 0.147486E+09 0.551559E+09 0.00 0.00
               
Annual Sum or Average 0.346334E+11 0.342088E+11 0.420334E+11 0.167104E+11 0.253230E+11 0.00 0.00
Minimum of Months 0.122960E+09 0.166597E+10 0.699046E+09 0.147486E+09 0.551559E+09 0.00 0.00
Maximum of Months 0.620315E+10 0.449238E+10 0.634788E+10 0.279828E+10 0.354960E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 33977139.41 0.574474E+10 0.982953E+09 0.00 0.982953E+09 0.00 0.00
February 0.107955E+09 0.489916E+10 0.138638E+10 0.00 0.138638E+10 0.00 0.00
March 0.421922E+09 0.459448E+10 0.212406E+10 0.00 0.212406E+10 0.00 0.00
April 0.154637E+10 0.363202E+10 0.334655E+10 14792930.49 0.333176E+10 0.00 0.00
May 0.189229E+10 0.302328E+10 0.432333E+10 0.208177E+09 0.411515E+10 0.00 0.00
June 0.271666E+10 0.228232E+10 0.462493E+10 0.289516E+09 0.433541E+10 0.00 0.00
July 0.294356E+10 0.216271E+10 0.453323E+10 0.257975E+09 0.427525E+10 0.00 0.00
August 0.240613E+10 0.243731E+10 0.356349E+10 55570145.98 0.350792E+10 0.00 0.00
September 0.152126E+10 0.305971E+10 0.262499E+10 559084.73 0.262443E+10 0.00 0.00
October 0.499595E+09 0.416402E+10 0.173816E+10 0.00 0.173816E+10 0.00 0.00
November 50272382.69 0.492833E+10 0.101068E+10 0.00 0.101068E+10 0.00 0.00
December 2254208.28 0.610133E+10 0.711216E+09 0.00 0.711216E+09 0.00 0.00
               
Annual Sum or Average 0.141423E+11 0.470294E+11 0.309700E+11 0.826590E+09 0.301434E+11 0.00 0.00
Minimum of Months 2254208.28 0.216271E+10 0.711216E+09 0.00 0.711216E+09 0.00 0.00
Maximum of Months 0.294356E+10 0.610133E+10 0.462493E+10 0.289516E+09 0.433541E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.549311E+09 0.356897E+10 0.133956E+10 0.538197E+09 0.801364E+09 0.00 0.00
February 0.928471E+09 0.306787E+10 0.180401E+10 0.666422E+09 0.113759E+10 0.00 0.00
March 0.955802E+09 0.285117E+10 0.208724E+10 0.411340E+09 0.167590E+10 0.00 0.00
April 0.477254E+10 0.226211E+10 0.542408E+10 0.254909E+10 0.287498E+10 0.00 0.00
May 0.503599E+10 0.199595E+10 0.589194E+10 0.256891E+10 0.332304E+10 0.00 0.00
June 0.513189E+10 0.151769E+10 0.564379E+10 0.225358E+10 0.339021E+10 0.00 0.00
July 0.566912E+10 0.144312E+10 0.595327E+10 0.252966E+10 0.342361E+10 0.00 0.00
August 0.556648E+10 0.155208E+10 0.564010E+10 0.269473E+10 0.294537E+10 0.00 0.00
September 0.471347E+10 0.191034E+10 0.491600E+10 0.261441E+10 0.230159E+10 0.00 0.00
October 0.176403E+10 0.262647E+10 0.245178E+10 0.101607E+10 0.143571E+10 0.00 0.00
November 0.523424E+09 0.308643E+10 0.123705E+10 0.421665E+09 0.815388E+09 0.00 0.00
December 0.322187E+09 0.384496E+10 0.947389E+09 0.352283E+09 0.595106E+09 0.00 0.00
               
Annual Sum or Average 0.359327E+11 0.297272E+11 0.433362E+11 0.186164E+11 0.247199E+11 0.00 0.00
Minimum of Months 0.322187E+09 0.144312E+10 0.947389E+09 0.352283E+09 0.595106E+09 0.00 0.00
Maximum of Months 0.566912E+10 0.384496E+10 0.595327E+10 0.269473E+10 0.342361E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.512254E+10 0.518088E+10 0.557901E+10 0.361099E+10 0.196803E+10 0.00 0.00
February 0.554872E+10 0.467060E+10 0.615632E+10 0.375678E+10 0.239954E+10 0.00 0.00
March 0.270748E+10 0.441678E+10 0.421472E+10 0.122775E+10 0.298697E+10 0.00 0.00
April 0.723924E+10 0.373372E+10 0.846897E+10 0.382833E+10 0.464064E+10 0.00 0.00
May 0.496813E+10 0.330960E+10 0.723632E+10 0.235518E+10 0.488114E+10 0.00 0.00
June 0.454747E+10 0.247782E+10 0.645120E+10 0.156086E+10 0.489034E+10 0.00 0.00
July 0.560094E+10 0.236096E+10 0.722268E+10 0.226110E+10 0.496157E+10 0.00 0.00
August 0.767918E+10 0.255988E+10 0.846447E+10 0.380752E+10 0.465696E+10 0.00 0.00
September 0.965225E+10 0.314857E+10 0.968383E+10 0.567439E+10 0.400945E+10 0.00 0.00
October 0.659075E+10 0.414387E+10 0.687407E+10 0.401823E+10 0.285584E+10 0.00 0.00
November 0.430568E+10 0.467956E+10 0.471429E+10 0.286738E+10 0.184691E+10 0.00 0.00
December 0.349640E+10 0.575959E+10 0.386057E+10 0.247298E+10 0.138759E+10 0.00 0.00
               
Annual Sum or Average 0.674588E+11 0.464418E+11 0.789265E+11 0.374415E+11 0.414850E+11 0.00 0.00
Minimum of Months 0.270748E+10 0.236096E+10 0.386057E+10 0.122775E+10 0.138759E+10 0.00 0.00
Maximum of Months 0.965225E+10 0.575959E+10 0.968383E+10 0.567439E+10 0.496157E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.558976E+09 0.373600E+10 0.130264E+10 0.430491E+09 0.872153E+09 0.00 0.00
February 0.127800E+10 0.325236E+10 0.208307E+10 0.879593E+09 0.120348E+10 0.00 0.00
March 0.954176E+09 0.298232E+10 0.208530E+10 0.398957E+09 0.168635E+10 0.00 0.00
April 0.404952E+10 0.246519E+10 0.476176E+10 0.189156E+10 0.287020E+10 0.00 0.00
May 0.492005E+10 0.216712E+10 0.577186E+10 0.234662E+10 0.342524E+10 0.00 0.00
June 0.561257E+10 0.167311E+10 0.603172E+10 0.248247E+10 0.354925E+10 0.00 0.00
July 0.620670E+10 0.161126E+10 0.634788E+10 0.279828E+10 0.354960E+10 0.00 0.00
August 0.526013E+10 0.173524E+10 0.533237E+10 0.230865E+10 0.302372E+10 0.00 0.00
September 0.388199E+10 0.208042E+10 0.414023E+10 0.185663E+10 0.228361E+10 0.00 0.00
October 0.160629E+10 0.279701E+10 0.228229E+10 0.820747E+09 0.146155E+10 0.00 0.00
November 0.513462E+09 0.328904E+10 0.119526E+10 0.348936E+09 0.846320E+09 0.00 0.00
December 0.137621E+09 0.414175E+10 0.699046E+09 0.147486E+09 0.551559E+09 0.00 0.00
               
Annual Sum or Average 0.349795E+11 0.319308E+11 0.420334E+11 0.167104E+11 0.253230E+11 0.00 0.00
Minimum of Months 0.137621E+09 0.161126E+10 0.699046E+09 0.147486E+09 0.551559E+09 0.00 0.00
Maximum of Months 0.620670E+10 0.414175E+10 0.634788E+10 0.279828E+10 0.354960E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.18 3.24 2.03 1.05 -4.0 28.28 62.93 0.00
February 4.25 3.55 2.74 1.60 -5.0 43.80 86.73 0.02
March 5.90 4.45 2.76 1.18 -2.0 68.95 35.00 0.00
April 8.96 6.23 3.38 1.56 -0.7 96.13 186.12 0.00
May 9.99 8.06 6.28 3.35 -0.9 110.92 199.68 0.02
June 13.31 11.26 9.70 3.33 3.35 121.69 199.28 0.00
July 15.02 12.39 10.49 3.21 4.48 111.91 220.83 0.00
August 15.65 12.74 10.65 2.92 3.94 91.47 211.91 0.00
September 13.43 11.01 9.10 2.64 1.42 68.72 198.32 0.01
October 9.33 8.03 6.81 1.97 -1.0 48.92 91.86 0.04
November 6.66 5.65 4.54 2.05 -2.3 30.27 53.24 0.04
December 4.10 3.14 1.95 2.36 -5.1 20.52 40.74 0.04
                 
Annual Sum or Average 9.26 7.50 5.89 2.27 -0.6 70.25 132.30 0.02
Minimum of Months 4.10 3.14 1.95 1.05 -5.1 20.52 35.00 0.00
Maximum of Months 15.65 12.74 10.65 3.35 4.48 121.69 220.83 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 29-JAN-05:00 9.36 5.00 3.60 8.35 0.00 0.00
February 11.00 07-FEB-14:00 9.86 9.00 2.10 6.35 138.00 225.00
March 14.00 25-MAR-12:00 11.21 9.00 2.60 7.35 287.00 93.00
April 24.00 30-APR-14:00 13.10 4.00 1.50 7.75 167.50 716.00
May 24.00 22-MAY-14:00 16.06 11.00 2.60 9.33 159.00 769.00
June 27.00 13-JUN-16:00 17.51 12.00 3.10 12.41 141.50 652.50
July 30.00 22-JUL-17:00 16.77 8.00 0.00 14.28 122.00 407.00
August 27.00 14-AUG-17:19 14.15 3.33 2.60 10.37 133.00 358.83
September 23.00 11-SEP-16:00 16.21 12.00 2.60 8.74 108.00 325.50
October 19.00 07-OCT-14:00 10.08 1.00 1.50 2.22 131.00 540.50
November 16.00 24-NOV-11:00 12.00 9.00 4.10 9.33 61.50 0.00
December 13.00 23-DEC-10:00 7.62 2.00 7.70 6.75 70.50 0.00
                 
Annual Sum or Average                
Minimum of Months 11.00   7.62 1.00 0.00 2.22 0.00 0.00
Maximum of Months 30.00   17.51 12.00 7.70 14.28 287.00 769.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.0 10-JAN-07:00 -6.9 -9.0 0.00 -20.0 0.00 0.00
February -4.0 17-FEB-06:00 -4.0 -4.0 0.00 -20.5 0.00 0.00
March -1.0 08-MAR-06:00 -1.4 -2.0 0.00 -14.4 17.50 184.50
April 0.00 08-APR-04:00 -0.8 -2.0 0.00 -12.7 0.00 0.00
May 2.00 06-MAY-04:00 1.57 1.00 3.60 -13.7 12.50 117.00
June 6.00 01-JUN-03:00 5.04 4.00 0.00 -9.2 0.00 0.00
July 7.00 05-JUL-04:00 6.47 6.00 3.10 -7.8 28.00 155.00
August 8.00 20-AUG-04:00 7.45 7.00 0.00 -6.6 0.00 0.00
September 5.00 20-SEP-03:00 5.00 5.00 2.60 -10.0 0.00 0.00
October 2.00 07-OCT-03:00 2.00 2.00 0.00 -13.4 0.00 0.00
November -2.0 29-NOV-01:00 -2.0 -2.0 3.10 -10.7 0.00 0.00
December -3.0 29-DEC-20:00 -4.4 -7.0 3.60 -20.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -6.0   -6.9 -9.0 0.00 -20.5 0.00 0.00
Maximum of Months 8.00   7.45 7.00 3.60 -6.6 28.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.44 29-JAN-04:00 13.00 12.00 0.00 9.13 0.00 0.00
February 9.86 07-FEB-14:00 11.00 9.00 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.39 28-APR-07:00 16.00 15.00 0.00 5.54 119.50 626.00
May 16.06 22-MAY-14:00 24.00 11.00 2.60 9.33 159.00 769.00
June 19.93 25-JUN-17:00 22.00 19.00 0.00 15.94 136.50 360.50
July 17.29 22-JUL-09:00 26.00 12.00 4.60 11.46 224.50 619.50
August 17.04 14-AUG-12:00 24.00 13.00 2.60 9.91 205.50 669.50
September 16.53 10-SEP-15:00 21.00 14.00 3.60 8.54 160.50 483.00
October 13.58 17-OCT-14:00 16.00 12.00 0.00 12.03 144.00 44.50
November 12.00 24-NOV-11:00 16.00 9.00 4.10 9.33 61.50 0.00
December 7.93 02-DEC-12:00 9.00 7.00 0.00 2.01 135.50 84.00
                 
Annual Sum or Average                
Minimum of Months 7.93   9.00 7.00 0.00 2.01 0.00 0.00
Maximum of Months 19.93   26.00 19.00 4.60 15.94 224.50 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 29-JAN-04:00 13.00 12.44 0.00 9.13 0.00 0.00
February 9.00 07-FEB-14:00 11.00 9.86 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.00 28-APR-07:00 16.00 15.39 0.00 5.54 119.50 626.00
May 12.00 23-MAY-07:00 17.00 13.94 3.10 5.13 112.00 719.50
June 19.00 25-JUN-17:00 22.00 19.93 0.00 15.94 136.50 360.50
July 14.00 17-JUL-17:00 18.00 15.44 3.60 9.91 120.00 0.00
August 16.00 08-AUG-12:00 18.00 16.70 1.50 11.46 154.00 0.00
September 14.00 10-SEP-15:00 21.00 16.53 3.60 8.54 160.50 483.00
October 13.00 17-OCT-18:00 13.00 13.00 2.60 9.33 0.00 0.00
November 12.00 08-NOV-14:00 12.00 12.00 0.00 8.15 93.00 106.00
December 7.00 02-DEC-11:00 8.00 7.45 3.10 1.16 144.50 146.50
                 
Annual Sum or Average                
Minimum of Months 7.00   8.00 7.45 0.00 1.16 0.00 0.00
Maximum of Months 19.00   22.00 19.93 3.60 15.94 160.50 719.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.33 8.85 0.00
February 18.00 13.00 16.00 10.00 14.79 0.00
March 18.00 13.00 16.00 10.33 17.09 0.00
April 18.00 13.00 16.00 11.26 40.86 0.00
May 18.00 13.00 16.00 12.54 47.73 0.00
June 18.00 13.00 16.00 13.82 50.98 0.00
July 18.00 13.00 16.00 14.77 51.67 0.00
August 18.00 13.00 16.00 15.12 44.67 0.00
September 18.00 13.00 16.00 14.78 34.25 0.00
October 18.00 13.00 16.00 13.84 17.71 0.00
November 18.00 13.00 16.00 12.55 9.34 0.00
December 18.00 13.00 16.00 11.27 6.14 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.57 28.73 0.00
Minimum of Months 18.00 13.00 16.00 10.00 6.14 0.00
Maximum of Months 18.00 13.00 16.00 15.12 51.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SHWSYS1 WATER HEATER

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.246747E+11 -.388459E+11 0.00 0.00 744.00 0.00 -.130137E+10 68.21 0.00 0.00
February 0.227505E+11 -.355274E+11 0.00 0.00 672.00 0.00 -.117000E+10 67.99 0.00 0.00
March 0.274921E+11 -.415137E+11 0.00 0.00 744.00 0.00 -.127013E+10 67.07 0.00 0.00
April 0.231695E+11 -.369571E+11 0.00 0.00 720.00 0.00 -.124671E+10 67.82 0.00 0.00
May 0.241819E+11 -.384073E+11 0.00 0.00 744.00 0.00 -.129044E+10 67.83 0.00 0.00
June 0.232477E+11 -.370450E+11 0.00 0.00 720.00 0.00 -.123753E+10 67.41 0.00 0.00
July 0.200244E+11 -.345149E+11 0.00 0.00 744.00 0.00 -.130919E+10 68.60 0.00 0.00
August 0.231314E+11 -.374609E+11 0.00 0.00 744.00 0.00 -.127447E+10 67.30 0.00 0.00
September 0.202802E+11 -.342613E+11 0.00 0.00 720.00 0.00 -.125517E+10 68.11 0.00 0.00
October 0.217160E+11 -.360877E+11 0.00 0.00 744.00 0.00 -.130653E+10 68.46 0.00 0.00
November 0.226056E+11 -.363991E+11 0.00 0.00 720.00 0.00 -.126442E+10 68.46 0.00 0.00
December 0.229186E+11 -.372193E+11 0.00 0.00 744.00 0.00 -.130026E+10 68.23 0.00 0.00
                     
Annual Sum or Average 0.276193E+12 -.444240E+12     8760.00   -.152262E+11 67.96    
Minimum of Months 0.200244E+11 -.415137E+11 0.00 0.00 672.00 0.00 -.130919E+10 67.07 0.00 0.00
Maximum of Months 0.274921E+11 -.342613E+11 0.00 0.00 744.00 0.00 -.117000E+10 68.60 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 195.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 217.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 215.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 359.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 417.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 410.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 429.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 396.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 337.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 234.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 171.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 131.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3515.67                    
Minimum of Months 131.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 429.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DATACENTER_EXTRAWATERHEATC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.198138E+10 467064.68 21-JAN-03:50 0.00 0.00 0.00 0.00 0.00
February 0.887288E+09 434486.17 04-FEB-18:13 0.00 0.00 0.00 0.00 0.00
March 0.716775E+09 258213.24 11-MAR-00:42 0.00 0.00 0.00 0.00 0.00
April 0.243560E+09 68411.84 30-APR-03:47 0.00 0.00 0.00 0.00 0.00
May 0.172524E+10 467619.59 18-MAY-00:45 0.00 0.00 0.00 0.00 0.00
June 0.288701E+09 442515.58 18-JUN-21:20 0.00 0.00 0.00 0.00 0.00
July 52458219.91 252653.35 31-JUL-02:35 0.00 0.00 0.00 0.00 0.00
August 38651341.52 86613.73 20-AUG-03:18 0.00 0.00 0.00 0.00 0.00
September 0.238439E+09 440545.49 19-SEP-21:13 0.00 0.00 0.00 0.00 0.00
October 0.129186E+10 442780.94 18-OCT-05:17 0.00 0.00 0.00 0.00 0.00
November 0.785444E+09 268992.57 14-NOV-02:36 0.00 0.00 0.00 0.00 0.00
December 0.243681E+09 65881.50 09-DEC-19:55 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.849347E+10              
Minimum of Months 38651341.52 65881.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.198138E+10 467619.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.201606E+10 77225.83 30-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.699122E+09 77224.60 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.257727E+09 77156.39 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.120376E+09 47583.82 23-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.685390E+09 77103.60 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.186167E+10 77229.77 18-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.564034E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.201606E+10 77229.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 55789985.40 2135.48 10-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 6129114.72 1348.50 17-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 3194371.42 424.61 29-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 44181682.16 2496.23 30-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.109295E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 55789985.40 2496.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 71600755.08 2732.72 10-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 5520747.45 1169.22 17-FEB-06:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 4544645.34 2950.58 20-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 28192827.95 6119.11 11-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.109859E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 71600755.08 6119.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2012792.37 804.39 10-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2012792.37              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2012792.37 804.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.233907E+10 109893.19 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.836787E+09 106873.58 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 76963211.88 5557.79 04-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 908055.85 1513.43 23-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 0.921639E+09 110267.47 20-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.448551E+10 109443.93 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.866088E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.448551E+10 110267.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.870292E+10 118879.78 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.577680E+10 116419.81 17-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.315370E+10 52890.68 04-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 56367277.24 14709.12 08-APR-05:09 0.00 0.00 0.00 0.00 0.00
May 26219763.34 8434.49 05-MAY-05:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 1084605.26 1115.85 20-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.155707E+10 23393.50 30-OCT-05:10 0.00 0.00 0.00 0.00 0.00
November 0.554648E+10 117686.57 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.136345E+11 118556.86 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.384551E+11              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.136345E+11 118879.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.426423E+10 166408.02 10-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.236329E+10 91430.87 17-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.127080E+10 34022.74 04-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 8468626.90 2603.79 11-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 68056231.33 17246.36 05-MAY-05:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.368378E+09 18275.57 28-OCT-05:05 0.00 0.00 0.00 0.00 0.00
November 0.234915E+10 164548.92 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.100720E+11 168244.73 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.207644E+11              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.100720E+11 168244.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.705538E+10 109322.66 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.383583E+10 106806.47 13-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.169805E+10 24867.42 16-MAR-05:06 0.00 0.00 0.00 0.00 0.00
April 24047485.98 3975.45 01-APR-06:50 0.00 0.00 0.00 0.00 0.00
May 80066639.22 16237.36 05-MAY-05:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 7003497.67 2641.58 07-SEP-05:50 0.00 0.00 0.00 0.00 0.00
October 0.933565E+09 21669.41 21-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.388179E+10 106831.67 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.107737E+11 109018.51 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.282894E+11              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.107737E+11 109322.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.277126E+10 12392.63 09-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.176945E+10 12177.46 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.916916E+09 12129.84 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.164479E+09 12036.34 24-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 98304386.71 12073.54 15-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 357577.60 411.98 07-JUN-05:09 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 30373110.66 7851.33 18-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.571142E+09 12220.66 20-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.160330E+10 12179.19 13-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.331388E+10 12176.32 12-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112395E+11              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331388E+10 12392.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.294561E+10 14922.44 23-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.200503E+10 14923.39 27-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.137725E+10 14890.96 08-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.175517E+09 14880.88 11-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.114849E+09 14879.09 02-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 5765707.96 2166.59 07-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 1957275.34 1176.97 31-JUL-05:07 0.00 0.00 0.00 0.00 0.00
August 3734019.65 1741.08 23-AUG-05:07 0.00 0.00 0.00 0.00 0.00
September 84738485.92 2842.89 21-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.889270E+09 14943.39 20-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.202326E+10 14911.42 15-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.351693E+10 14915.45 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.131439E+11              
Minimum of Months 1957275.34 1176.97   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.351693E+10 14943.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.288829E+10 21483.30 23-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.197377E+10 21484.82 27-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.154948E+10 21448.91 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.334498E+09 21423.64 11-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.313308E+09 21436.73 15-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 36299511.56 11235.65 08-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 8612325.48 1807.13 01-JUL-05:06 0.00 0.00 0.00 0.00 0.00
August 4338072.84 534.53 12-AUG-06:50 0.00 0.00 0.00 0.00 0.00
September 85253479.11 3245.03 07-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.886056E+09 21435.02 17-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.193540E+10 21468.18 15-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.397296E+10 21472.42 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.139883E+11              
Minimum of Months 4338072.84 534.53   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.397296E+10 21484.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.261866E+10 14835.76 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.168217E+10 14871.92 27-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.115041E+10 14823.35 07-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.219082E+09 3645.96 24-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.197442E+09 14829.98 16-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 12864319.85 1611.51 08-JUN-05:20 0.00 0.00 0.00 0.00 0.00
July 8967493.28 1504.86 01-JUL-05:20 0.00 0.00 0.00 0.00 0.00
August 1360383.14 286.30 12-AUG-06:55 0.00 0.00 0.00 0.00 0.00
September 0.128486E+09 2747.43 07-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.837720E+09 14828.37 14-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.172978E+10 14837.59 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.307589E+10 14865.24 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116628E+11              
Minimum of Months 1360383.14 286.30   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.307589E+10 14871.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS_HEATC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.801118E+09 245925.18 01-JAN-04:20 0.00 0.00 0.00 0.00 0.00
February 14757865.11 245964.42 07-FEB-04:45 0.00 0.00 0.00 0.00 0.00
March 0.811277E+09 246110.65 18-MAR-03:47 0.00 0.00 0.00 0.00 0.00
April 0.652840E+09 246061.29 30-APR-21:17 0.00 0.00 0.00 0.00 0.00
May 0.119749E+10 246083.12 27-MAY-03:47 0.00 0.00 0.00 0.00 0.00
June 0.450890E+09 246189.30 11-JUN-19:10 0.00 0.00 0.00 0.00 0.00
July 0.134650E+10 246194.64 23-JUL-22:30 0.00 0.00 0.00 0.00 0.00
August 0.777435E+09 246203.33 27-AUG-21:40 0.00 0.00 0.00 0.00 0.00
September 0.551136E+09 246134.82 04-SEP-11:30 0.00 0.00 0.00 0.00 0.00
October 0.443178E+09 246210.44 09-OCT-12:10 0.00 0.00 0.00 0.00 0.00
November 0.565681E+09 245965.51 12-NOV-12:40 0.00 0.00 0.00 0.00 0.00
December 0.115528E+10 245983.45 05-DEC-04:47 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.876758E+10              
Minimum of Months 14757865.11 245925.18   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134650E+10 246210.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT_HEATC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.200944E+11 57015.19 10-JAN-19:00 0.00 0.00 0.00 0.00 0.00
February 0.143112E+11 52969.53 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.101405E+11 38000.81 08-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.237718E+10 33178.46 08-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.280866E+10 29452.19 06-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.192225E+09 14819.24 07-JUN-21:00 0.00 0.00 0.00 0.00 0.00
July 4919624.50 4020.79 03-JUL-21:00 0.00 0.00 0.00 0.00 0.00
August 155991.55 261.96 24-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.544819E+09 19990.33 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.400800E+10 29435.62 07-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.814589E+10 41820.49 28-NOV-21:00 0.00 0.00 0.00 0.00 0.00
December 0.148729E+11 48490.29 29-DEC-21:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.775007E+11              
Minimum of Months 155991.55 261.96   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.200944E+11 57015.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT_HEATC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.321582E+12 565653.94 10-JAN-09:10 0.00 0.00 0.00 0.00 0.00
February 0.255070E+12 541988.49 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.228600E+12 512675.61 08-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.846169E+11 482764.62 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.688835E+11 375531.39 06-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.191495E+11 255225.35 07-JUN-21:00 0.00 0.00 0.00 0.00 0.00
July 0.432010E+10 184833.03 03-JUL-21:00 0.00 0.00 0.00 0.00 0.00
August 0.240775E+10 157417.67 24-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.212634E+11 310028.83 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.983052E+11 392714.75 06-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.195757E+12 528875.02 29-NOV-07:30 0.00 0.00 0.00 0.00 0.00
December 0.337019E+12 541986.56 29-DEC-17:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163698E+13              
Minimum of Months 0.240775E+10 157417.67   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.337019E+12 565653.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT_HEATC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.457878E+11 57229.96 11-JAN-14:50 0.00 0.00 0.00 0.00 0.00
February 0.390363E+11 56123.57 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.375690E+11 54465.49 08-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.141431E+11 53183.86 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.116131E+11 41772.04 06-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.322600E+10 29036.84 07-JUN-21:00 0.00 0.00 0.00 0.00 0.00
July 0.950652E+09 21791.24 03-JUL-21:00 0.00 0.00 0.00 0.00 0.00
August 0.559413E+09 22401.47 24-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.363845E+10 35150.77 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.176511E+11 43637.79 06-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.321505E+11 54720.02 29-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.462031E+11 55703.16 29-DEC-21:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.252529E+12              
Minimum of Months 0.559413E+09 21791.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.462031E+11 57229.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DATACENTER_EXTRAELECHEATC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 531036.36 531036.36 3728.45 20-FEB-15:01 3728.45 0.00
March 0.00 0.00 2423267.48 1314127.70 8108.83 18-MAR-05:02 3690.37 0.00
April 0.00 0.00 0.929681E+09 0.929681E+09 93594.14 30-APR-18:51 93594.14 0.00
May 0.00 0.00 0.265793E+10 0.265576E+10 61883.62 22-MAY-15:00 61883.62 0.04
June 0.00 0.00 0.914233E+10 0.897537E+10 141711.65 25-JUN-17:52 63159.86 0.13
July 0.00 0.00 0.152393E+11 0.148857E+11 94429.55 23-JUL-16:21 68199.27 0.23
August 0.00 0.00 0.196218E+11 0.194052E+11 83134.36 13-AUG-15:50 70787.17 0.33
September 0.00 0.00 0.960111E+10 0.951649E+10 76368.93 10-SEP-19:01 41470.89 0.15
October 0.00 0.00 0.415902E+09 0.302909E+09 55872.47 08-OCT-16:11 29621.78 0.00
November 0.00 0.00 41798667.35 36866379.97 29989.42 09-NOV-04:01 16581.95 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average     0.576528E+11 0.567098E+11       0.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.196218E+11 0.194052E+11 141711.65   93594.14 0.33



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1128.38 1128.38 0.82 30-JAN-05:50 0.82 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 3778.63 3778.63 0.95 20-MAR-03:47 0.95 0.00
April 0.00 0.00 0.578384E+10 0.575537E+10 66601.65 28-APR-15:00 66601.65 0.01
May 0.00 0.00 0.693479E+10 0.693479E+10 87858.94 22-MAY-15:00 87858.94 0.08
June 0.00 0.00 0.224723E+11 0.208127E+11 119168.19 26-JUN-15:50 81167.60 0.28
July 0.00 0.00 0.381863E+11 0.364073E+11 113213.48 21-JUL-16:00 113213.48 0.45
August 0.00 0.00 0.508987E+11 0.478204E+11 114685.42 14-AUG-13:00 97461.66 0.52
September 0.00 0.00 0.246417E+11 0.238689E+11 94284.12 12-SEP-14:00 67932.25 0.30
October 0.00 0.00 0.193770E+10 0.193770E+10 33623.71 11-OCT-15:00 33623.71 0.02
November 0.00 0.00 59234398.59 59234398.59 19514.27 24-NOV-12:00 19514.27 0.00
December 0.00 0.00 27.44 27.44 0.46 30-DEC-06:09 0.46 0.00
                 
Annual Sum or Average     0.150915E+12 0.143596E+12       0.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.508987E+11 0.478204E+11 119168.19   113213.48 0.52



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 23905.69 23905.69 3.77 30-JAN-06:02 3.77 0.00
February 0.00 0.00 7086.85 7086.85 2.97 19-FEB-15:48 2.97 0.00
March 0.00 0.00 31410.90 31410.90 5.85 20-MAR-05:04 5.85 0.00
April 0.00 0.00 0.473147E+11 0.471164E+11 568225.99 28-APR-15:00 568225.99 0.01
May 0.00 0.00 0.599592E+11 0.599592E+11 766470.07 22-MAY-15:00 766470.07 0.08
June 0.00 0.00 0.185581E+12 0.172204E+12 1075449.70 13-JUN-16:00 969740.23 0.27
July 0.00 0.00 0.301755E+12 0.289105E+12 1011179.15 21-JUL-16:00 1011179.15 0.42
August 0.00 0.00 0.397839E+12 0.375437E+12 907213.91 14-AUG-16:00 907213.91 0.49
September 0.00 0.00 0.216078E+12 0.209623E+12 853718.53 12-SEP-14:00 616227.17 0.31
October 0.00 0.00 0.161656E+11 0.161656E+11 282792.18 06-OCT-15:00 282792.18 0.02
November 0.00 0.00 0.355713E+09 0.355713E+09 129120.95 24-NOV-12:00 129120.95 0.00
December 0.00 0.00 22770.01 22770.01 1.71 15-DEC-06:01 1.71 0.00
                 
Annual Sum or Average     0.122505E+13 0.116997E+13       0.13
Minimum of Months 0.00 0.00 7086.85 7086.85 1.71   1.71 0.00
Maximum of Months 0.00 0.00 0.397839E+12 0.375437E+12 1075449.70   1011179.15 0.49



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT_COOLC

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 399.61 399.61 0.34 01-JAN-22:11 0.34 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 159.16 159.16 0.27 27-MAR-06:00 0.27 0.00
April 0.00 0.00 0.477986E+10 0.476760E+10 62144.91 28-APR-15:20 62144.91 0.01
May 0.00 0.00 0.644877E+10 0.644877E+10 89051.33 22-MAY-15:00 89051.33 0.08
June 0.00 0.00 0.203720E+11 0.187756E+11 133990.31 13-JUN-15:10 114922.65 0.26
July 0.00 0.00 0.321775E+11 0.307076E+11 121459.54 21-JUL-16:00 121459.54 0.39
August 0.00 0.00 0.401524E+11 0.378882E+11 108314.19 14-AUG-16:00 108314.19 0.47
September 0.00 0.00 0.204930E+11 0.198651E+11 91653.12 12-SEP-14:00 65962.95 0.27
October 0.00 0.00 0.133845E+10 0.133845E+10 25663.22 07-OCT-15:00 25663.22 0.01
November 0.00 0.00 24264352.54 24264352.54 9106.80 24-NOV-12:00 9106.80 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average     0.125786E+12 0.119816E+12       0.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.401524E+11 0.378882E+11 133990.31   121459.54 0.47



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.312016E+12 0.311981E+12 425385.92 06-JAN-22:42 425385.92 0.00
February 0.00 0.00 0.493281E+12 0.493251E+12 435908.28 16-FEB-23:10 435908.28 0.00
March 0.00 0.00 0.782533E+12 0.782526E+12 423883.87 15-MAR-03:40 423883.87 0.00
April 0.00 0.00 0.989840E+12 0.989840E+12 417385.79 30-APR-03:53 417385.79 0.00
May 0.00 0.00 0.316290E+12 0.316210E+12 426074.82 17-MAY-22:37 419282.63 0.00
June 0.00 0.00 0.534345E+12 0.533675E+12 437270.47 05-JUN-21:17 437270.47 0.00
July 0.00 0.00 0.789996E+12 0.788864E+12 431832.68 31-JUL-02:36 431832.68 0.00
August 0.00 0.00 0.102625E+13 0.102542E+13 426162.57 20-AUG-03:23 426162.57 0.00
September 0.00 0.00 0.308065E+12 0.307480E+12 423014.51 19-SEP-21:13 423014.51 0.00
October 0.00 0.00 0.551497E+12 0.551374E+12 438950.62 13-OCT-21:17 438950.62 0.00
November 0.00 0.00 0.760182E+12 0.760105E+12 430128.13 14-NOV-02:37 430128.13 0.00
December 0.00 0.00 0.101957E+13 0.101957E+13 416617.99 02-DEC-19:20 416617.99 0.00
                 
Annual Sum or Average     0.788386E+13 0.788030E+13        
Minimum of Months 0.00 0.00 0.308065E+12 0.307480E+12 416617.99   416617.99 0.00
Maximum of Months 0.00 0.00 0.102625E+13 0.102542E+13 438950.62   438950.62 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.486237E+10 0.486237E+10 2389.75 19-JAN-16:20 2389.75 0.00
February 0.00 0.00 0.906990E+10 0.906990E+10 4489.01 27-FEB-17:00 4489.01 0.00
March 0.00 0.00 0.151550E+11 0.151550E+11 6275.91 23-MAR-17:30 6275.91 0.00
April 0.00 0.00 0.197063E+11 0.197063E+11 8244.26 27-APR-18:00 8244.26 0.00
May 0.00 0.00 0.554193E+10 0.554193E+10 2704.31 21-MAY-18:34 2704.31 0.00
June 0.00 0.00 0.102956E+11 0.102956E+11 4571.01 11-JUN-18:45 4571.01 0.00
July 0.00 0.00 0.155887E+11 0.155887E+11 6585.09 09-JUL-18:50 6585.09 0.00
August 0.00 0.00 0.204171E+11 0.204171E+11 8312.84 20-AUG-17:52 8312.84 0.00
September 0.00 0.00 0.534083E+10 0.534083E+10 2639.60 12-SEP-17:20 2639.60 0.00
October 0.00 0.00 0.103042E+11 0.103042E+11 4452.00 03-OCT-16:40 4452.00 0.00
November 0.00 0.00 0.146475E+11 0.146475E+11 6052.24 03-NOV-16:00 6052.24 0.00
December 0.00 0.00 0.199021E+11 0.199021E+11 7810.50 25-DEC-14:58 7810.50 0.00
                 
Annual Sum or Average     0.150832E+12 0.150832E+12        
Minimum of Months 0.00 0.00 0.486237E+10 0.486237E+10 2389.75   2389.75 0.00
Maximum of Months 0.00 0.00 0.204171E+11 0.204171E+11 8312.84   8312.84 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.342389E+11 0.342389E+11 21647.99 19-JAN-16:30 21647.99 0.00
February 0.00 0.00 0.754440E+11 0.754440E+11 41292.60 27-FEB-17:00 41292.60 0.00
March 0.00 0.00 0.133721E+12 0.133721E+12 58951.23 23-MAR-17:30 58951.23 0.00
April 0.00 0.00 0.182476E+12 0.182476E+12 78678.39 27-APR-17:50 78678.39 0.00
May 0.00 0.00 0.467753E+11 0.467753E+11 25517.01 21-MAY-18:27 25517.01 0.00
June 0.00 0.00 0.938293E+11 0.938293E+11 42805.30 11-JUN-18:50 42805.30 0.00
July 0.00 0.00 0.144765E+12 0.144765E+12 61658.58 09-JUL-18:46 61658.58 0.00
August 0.00 0.00 0.191328E+12 0.191328E+12 77379.34 04-AUG-18:10 77379.34 0.00
September 0.00 0.00 0.449223E+11 0.449223E+11 24978.90 12-SEP-17:20 24978.90 0.00
October 0.00 0.00 0.884013E+11 0.884013E+11 41741.34 03-OCT-16:50 41741.34 0.00
November 0.00 0.00 0.126901E+12 0.126901E+12 56335.29 03-NOV-16:00 56335.29 0.00
December 0.00 0.00 0.172839E+12 0.172839E+12 71364.61 21-DEC-15:20 71364.61 0.00
                 
Annual Sum or Average     0.133564E+13 0.133564E+13        
Minimum of Months 0.00 0.00 0.342389E+11 0.342389E+11 21647.99   21647.99 0.00
Maximum of Months 0.00 0.00 0.191328E+12 0.191328E+12 78678.39   78678.39 0.00



Table of Contents

Report: CoilReportMonthly

For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.145725E+10 0.145725E+10 2089.09 19-JAN-16:30 2089.09 0.00
February 0.00 0.00 0.583326E+10 0.583326E+10 3965.15 17-FEB-17:00 3965.15 0.00
March 0.00 0.00 0.119619E+11 0.119619E+11 5855.97 23-MAR-17:30 5855.97 0.00
April 0.00 0.00 0.175084E+11 0.175084E+11 7948.65 27-APR-17:50 7948.65 0.00
May 0.00 0.00 0.402909E+10 0.402909E+10 2636.27 21-MAY-18:27 2636.27 0.00
June 0.00 0.00 0.906278E+10 0.906278E+10 4445.47 11-JUN-18:40 4445.47 0.00
July 0.00 0.00 0.142062E+11 0.142062E+11 6329.40 09-JUL-18:44 6329.40 0.00
August 0.00 0.00 0.188323E+11 0.188323E+11 7843.53 13-AUG-18:03 7843.53 0.00
September 0.00 0.00 0.387875E+10 0.387875E+10 2557.52 12-SEP-17:20 2557.52 0.00
October 0.00 0.00 0.750218E+10 0.750218E+10 4166.51 03-OCT-16:50 4166.51 0.00
November 0.00 0.00 0.110234E+11 0.110234E+11 5557.48 10-NOV-16:20 5557.48 0.00
December 0.00 0.00 0.151876E+11 0.151876E+11 6965.28 21-DEC-15:20 6965.28 0.00
                 
Annual Sum or Average     0.120483E+12 0.120483E+12        
Minimum of Months 0.00 0.00 0.145725E+10 0.145725E+10 2089.09   2089.09 0.00
Maximum of Months 0.00 0.00 0.188323E+11 0.188323E+11 7948.65   7948.65 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SHWSYS1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 6880.00 37436.27 01-JAN-08:14 13541.82 53224.27 31-JAN-12:50
February 6503.84 37386.81 26-FEB-08:30 13752.49 53331.59 10-FEB-12:50
March 5265.41 37425.88 26-MAR-07:40 14737.46 53221.47 01-MAR-12:50
April 6308.59 37520.60 30-APR-07:16 13312.76 52441.56 03-APR-11:30
May 6203.49 37615.30 29-MAY-07:10 13435.60 51314.32 01-MAY-11:50
June 5576.66 37695.05 25-JUN-07:08 13425.55 49848.64 01-JUN-11:30
July 7196.60 37758.63 30-JUL-07:05 11766.64 48620.28 03-JUL-12:00
August 5533.03 37766.48 13-AUG-07:03 13196.18 47944.00 02-AUG-11:40
September 6521.64 37757.52 03-SEP-07:15 12187.26 48617.19 29-SEP-11:20
October 7097.26 37709.53 01-OCT-07:10 12433.75 49853.02 31-OCT-11:30
November 7144.10 37608.40 05-NOV-07:30 13045.92 51244.28 30-NOV-12:50
December 6975.84 37517.04 03-DEC-08:40 12886.29 52492.49 29-DEC-12:15
             
Annual Sum or Average 6433.80     13140.12    
Minimum of Months 5265.41 37386.81   11766.64 47944.00  
Maximum of Months 7196.60 37766.48   14737.46 53331.59  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.06 325.33 01-JAN-12:40 156780.25 923581.36 10-JAN-21:17
February 0.00 0.00 01-FEB-00:10 134796.88 793948.01 17-FEB-07:20
March 0.00 0.00 01-MAR-00:10 106698.55 730253.67 26-MAR-23:40
April 0.00 0.00 01-APR-00:10 39343.56 1696838.90 30-APR-19:16
May 1.45 816.29 04-MAY-15:00 31942.46 1044547.33 24-MAY-03:47
June 0.00 0.00 01-JUN-00:10 8833.86 849894.18 10-JUN-03:47
July 0.00 0.00 01-JUL-00:10 2500.32 784887.45 02-JUL-16:30
August 0.00 0.00 01-AUG-00:10 1366.93 791457.16 06-AUG-15:30
September 0.00 0.00 01-SEP-00:10 10128.05 969902.25 04-SEP-06:10
October 0.00 0.00 01-OCT-00:10 47202.48 609486.41 09-OCT-07:30
November 0.00 0.00 01-NOV-00:10 98409.55 883434.54 29-NOV-07:10
December 0.00 0.00 01-DEC-00:10 167648.98 1086355.14 30-DEC-07:10
             
Annual Sum or Average 0.13     66887.95    
Minimum of Months 0.00 0.00   1366.93 609486.41  
Maximum of Months 1.45 816.29   167648.98 1696838.90  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 118.19 11861.84 30-JAN-05:30 0.00 0.00 01-JAN-00:05
February 72.06 11861.84 17-FEB-07:00 0.00 0.00 01-FEB-00:10
March 156.34 12289.03 18-MAR-05:02 0.00 0.00 01-MAR-00:10
April 44313.32 1132812.64 28-APR-14:40 0.00 0.00 01-APR-00:10
May 51053.99 1156347.53 22-MAY-14:30 0.00 0.00 01-MAY-00:05
June 145739.66 1402450.95 13-JUN-16:00 0.00 0.00 01-JUN-00:10
July 242794.79 1325289.30 21-JUL-16:00 0.00 0.00 01-JUL-00:10
August 322506.65 1209264.14 14-AUG-16:00 0.00 0.00 01-AUG-00:10
September 179150.39 1246319.84 22-SEP-12:40 0.00 0.00 01-SEP-00:10
October 16018.09 721346.94 06-OCT-15:30 0.00 0.00 01-OCT-00:10
November 519.59 330268.89 24-NOV-12:00 0.00 0.00 01-NOV-00:10
December 138.09 11864.06 26-DEC-07:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 84137.20     0.00    
Minimum of Months 72.06 11861.84   0.00 0.00  
Maximum of Months 322506.65 1402450.95   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 0.00 0.00 01-JAN-00:05
February 0.00 30.08 20-FEB-15:01 0.00 0.00 01-FEB-00:10
March 0.04 479.49 18-MAR-05:02 0.00 0.00 01-MAR-00:10
April 25764.61 1136711.95 28-APR-14:40 0.00 0.00 01-APR-00:10
May 33418.69 1154977.83 22-MAY-14:30 0.00 0.00 01-MAY-00:05
June 104973.45 1398707.09 13-JUN-16:00 0.00 0.00 01-JUN-00:10
July 168596.10 1322217.04 21-JUL-16:00 0.00 0.00 01-JUL-00:10
August 222052.51 1205386.16 14-AUG-16:00 0.00 0.00 01-AUG-00:10
September 121443.61 1147876.78 12-SEP-15:40 0.00 0.00 01-SEP-00:10
October 8214.84 403770.84 06-OCT-15:20 0.00 0.00 01-OCT-00:10
November 197.86 185472.38 24-NOV-12:00 0.00 0.00 01-NOV-00:10
December 0.01 1.16 15-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 57457.90     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 222052.51 1398707.09   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 163906.92 533212.79 21-JAN-03:51 0.00 0.00 01-JAN-00:05
February 298671.46 576487.17 04-FEB-21:01 0.00 0.00 01-FEB-00:10
March 436116.20 593035.78 22-MAR-21:20 0.00 0.00 01-MAR-00:10
April 600214.67 1167260.20 30-APR-18:33 0.00 0.00 01-APR-00:10
May 178849.14 541204.65 22-MAY-15:00 0.00 0.00 01-MAY-00:05
June 343049.11 908487.01 13-JUN-17:00 0.00 0.00 01-JUN-00:10
July 533244.53 1283994.83 22-JUL-18:00 0.00 0.00 01-JUL-00:10
August 722918.74 1324624.67 14-AUG-17:20 0.00 0.00 01-AUG-00:10
September 196093.60 535200.41 20-SEP-21:20 0.00 0.00 01-SEP-00:10
October 304950.73 580351.19 21-OCT-20:51 0.00 0.00 01-OCT-00:10
November 435877.83 592394.06 01-NOV-21:30 0.00 0.00 01-NOV-00:10
December 568159.86 610363.33 12-DEC-22:43 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 399376.40     0.00    
Minimum of Months 163906.92 533212.79   0.00 0.00  
Maximum of Months 722918.74 1324624.67   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 5.47 13400.31 26-JAN-06:30 187.31 75325.14 07-JAN-06:40
February 1.10 5243.09 17-FEB-06:15 139.68 71715.20 02-FEB-06:40
March 7.12 8657.45 27-MAR-06:00 214.28 75189.62 21-MAR-06:00
April 33321.21 1605430.31 28-APR-14:40 545.85 68188.65 19-APR-05:30
May 41564.98 1707213.26 22-MAY-14:40 213.39 68322.51 06-MAY-05:30
June 142079.24 2937597.28 13-JUN-16:00 345.42 69487.37 08-JUN-05:40
July 206584.25 2170635.66 21-JUL-16:00 423.83 49910.38 31-JUL-05:30
August 269067.18 1991817.92 14-AUG-13:10 257.04 45279.15 24-AUG-03:01
September 150715.73 1697530.70 12-SEP-12:10 488.58 56101.53 21-SEP-05:30
October 11429.94 528402.96 06-OCT-15:30 341.62 61206.31 19-OCT-06:00
November 297.09 251553.03 24-NOV-12:00 232.62 73721.96 20-NOV-06:50
December 3.86 9036.46 15-DEC-06:50 188.13 69797.20 18-DEC-06:50
             
Annual Sum or Average 71728.70     298.30    
Minimum of Months 1.10 5243.09   139.68 45279.15  
Maximum of Months 269067.18 2937597.28   545.85 75325.14  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.172486E+11 0.92 10717.69 01-JAN-00:20 1.53
February 0.155917E+11 0.92 10717.69 01-FEB-04:11 1.53
March 0.180025E+11 0.96 10717.69 01-MAR-04:01 1.53
April 0.171288E+11 0.94 10717.69 01-APR-03:01 1.53
May 0.180024E+11 0.96 10717.69 01-MAY-00:10 1.53
June 0.177111E+11 0.97 10717.69 01-JUN-03:01 1.53
July 0.177937E+11 0.94 10717.69 01-JUL-03:01 1.53
August 0.188525E+11 1.00 10717.69 01-AUG-03:01 1.53
September 0.175251E+11 0.96 10717.69 01-SEP-03:01 1.52
October 0.179671E+11 0.96 10717.69 01-OCT-16:51 1.53
November 0.174409E+11 0.96 10717.69 01-NOV-03:01 1.53
December 0.172094E+11 0.92 10717.69 01-DEC-04:01 1.53
           
Annual Sum or Average 0.210474E+12 0.95      
Minimum of Months 0.155917E+11 0.92 10717.69   1.52
Maximum of Months 0.188525E+11 1.00 10717.69   1.53



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.597730E+10 0.39 11231.59 02-JAN-04:01 1.25
February 0.619981E+10 0.42 13573.28 28-FEB-06:01 1.41
March 0.802408E+10 0.47 14253.14 24-MAR-03:01 1.46
April 0.101932E+11 0.56 18410.11 18-APR-05:01 1.71
May 0.778615E+10 0.46 15417.68 01-MAY-03:01 1.53
June 0.805229E+10 0.49 21508.26 26-JUN-05:03 1.88
July 0.822740E+10 0.50 19193.65 10-JUL-05:03 1.75
August 0.916500E+10 0.55 19553.90 07-AUG-05:03 1.77
September 0.688406E+10 0.45 19801.35 02-SEP-05:01 1.78
October 0.739597E+10 0.44 16598.14 10-OCT-05:03 1.59
November 0.729619E+10 0.44 15312.83 09-NOV-04:01 1.52
December 0.709522E+10 0.42 13791.07 20-DEC-04:01 1.43
           
Annual Sum or Average 0.922967E+11 0.47      
Minimum of Months 0.597730E+10 0.39 11231.59   1.25
Maximum of Months 0.101932E+11 0.56 21508.26   1.88



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.428426E+11 0.34 150657.98 11-JAN-06:01 1.59
February 0.410819E+11 0.35 136213.13 13-FEB-06:01 1.49
March 0.492833E+11 0.37 109069.53 01-MAR-06:01 1.29
April 0.607205E+11 0.42 109069.53 01-APR-05:01 1.30
May 0.593413E+11 0.41 112401.87 22-MAY-05:02 1.31
June 0.590630E+11 0.42 150161.17 13-JUN-05:01 1.57
July 0.552376E+11 0.40 158342.18 22-JUL-05:01 1.63
August 0.595277E+11 0.43 136805.12 21-AUG-05:01 1.48
September 0.552781E+11 0.40 109069.53 01-SEP-04:03 1.29
October 0.504492E+11 0.36 109069.53 02-OCT-05:01 1.29
November 0.430532E+11 0.34 150657.98 27-NOV-06:01 1.59
December 0.380751E+11 0.32 150657.98 06-DEC-06:01 1.58
           
Annual Sum or Average 0.613954E+12 0.38      
Minimum of Months 0.380751E+11 0.32 109069.53   1.29
Maximum of Months 0.607205E+11 0.43 158342.18   1.63



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.318255E+10 0.31 4827.86 02-JAN-04:01 0.79
February 0.291001E+10 0.31 4827.86 06-FEB-06:02 0.79
March 0.343498E+10 0.32 4827.86 06-MAR-06:01 0.79
April 0.468734E+10 0.36 9750.85 13-APR-05:01 1.18
May 0.494626E+10 0.37 9750.85 01-MAY-05:01 1.18
June 0.546237E+10 0.39 12257.59 13-JUN-05:01 1.35
July 0.534511E+10 0.37 14567.22 07-JUL-05:01 1.50
August 0.548811E+10 0.39 14223.18 15-AUG-05:01 1.48
September 0.453071E+10 0.35 9750.85 01-SEP-05:01 1.17
October 0.346266E+10 0.31 6760.79 03-OCT-15:00 0.95
November 0.303866E+10 0.30 4827.86 13-NOV-06:02 0.79
December 0.307787E+10 0.31 4827.86 04-DEC-05:01 0.79
           
Annual Sum or Average 0.495666E+11 0.34      
Minimum of Months 0.291001E+10 0.30 4827.86   0.79
Maximum of Months 0.548811E+10 0.39 14567.22   1.50



Table of Contents

Report: FanReportMonthly

For: DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.953838E+11 1.37 35612.23 01-JAN-00:05 1.37
February 0.861531E+11 1.37 35612.23 01-FEB-00:10 1.37
March 0.953838E+11 1.37 35612.23 01-MAR-00:10 1.37
April 0.923069E+11 1.37 35612.23 01-APR-00:10 1.37
May 0.953838E+11 1.37 35612.23 01-MAY-00:10 1.37
June 0.923069E+11 1.37 35612.23 01-JUN-00:10 1.37
July 0.953838E+11 1.37 35612.23 01-JUL-00:10 1.37
August 0.953838E+11 1.37 35612.23 01-AUG-00:20 1.37
September 0.923069E+11 1.37 35612.23 01-SEP-00:10 1.37
October 0.953838E+11 1.37 35612.23 01-OCT-00:20 1.37
November 0.923069E+11 1.37 35612.23 01-NOV-00:10 1.37
December 0.953838E+11 1.37 35612.23 01-DEC-00:10 1.37
           
Annual Sum or Average 0.112307E+13 1.37      
Minimum of Months 0.861531E+11 1.37 35612.23   1.37
Maximum of Months 0.953838E+11 1.37 35612.23   1.37



Table of Contents

Report: FanReportMonthly

For: DATACENTER BOT SUPPLY FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148427E+10 0.93 554.16 01-JAN-00:05 0.93
February 0.134063E+10 0.93 554.16 01-FEB-00:10 0.93
March 0.148427E+10 0.93 554.16 01-MAR-00:10 0.93
April 0.143639E+10 0.93 554.16 01-APR-00:10 0.93
May 0.148427E+10 0.93 554.16 01-MAY-00:05 0.93
June 0.143639E+10 0.93 554.16 01-JUN-00:10 0.93
July 0.148427E+10 0.93 554.16 01-JUL-00:10 0.93
August 0.148427E+10 0.93 554.16 01-AUG-00:10 0.93
September 0.143639E+10 0.93 554.16 01-SEP-00:10 0.93
October 0.148427E+10 0.93 554.16 01-OCT-00:10 0.93
November 0.143639E+10 0.93 554.16 01-NOV-00:10 0.93
December 0.148427E+10 0.93 554.16 01-DEC-00:10 0.93
           
Annual Sum or Average 0.174761E+11 0.93      
Minimum of Months 0.134063E+10 0.93 554.16   0.93
Maximum of Months 0.148427E+10 0.93 554.16   0.93



Table of Contents

Report: FanReportMonthly

For: DATACENTER MID SUPPLY FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.141758E+11 0.93 5292.62 01-JAN-00:05 0.93
February 0.128039E+11 0.93 5292.62 01-FEB-00:10 0.93
March 0.141758E+11 0.93 5292.62 01-MAR-00:10 0.93
April 0.137185E+11 0.93 5292.62 01-APR-00:10 0.93
May 0.141758E+11 0.93 5292.62 01-MAY-00:05 0.93
June 0.137185E+11 0.93 5292.62 01-JUN-00:10 0.93
July 0.141758E+11 0.93 5292.62 01-JUL-00:10 0.93
August 0.141758E+11 0.93 5292.62 01-AUG-00:10 0.93
September 0.137185E+11 0.93 5292.62 01-SEP-00:20 0.93
October 0.141758E+11 0.93 5292.62 01-OCT-00:30 0.93
November 0.137185E+11 0.93 5292.62 01-NOV-00:10 0.93
December 0.141758E+11 0.93 5292.62 01-DEC-00:10 0.93
           
Annual Sum or Average 0.166908E+12 0.93      
Minimum of Months 0.128039E+11 0.93 5292.62   0.93
Maximum of Months 0.141758E+11 0.93 5292.62   0.93



Table of Contents

Report: FanReportMonthly

For: DATACENTER TOP SUPPLY FAN

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144131E+10 0.93 538.12 01-JAN-00:05 0.93
February 0.130183E+10 0.93 538.12 01-FEB-00:10 0.93
March 0.144131E+10 0.93 538.12 01-MAR-00:10 0.93
April 0.139481E+10 0.93 538.12 01-APR-00:10 0.93
May 0.144131E+10 0.93 538.12 01-MAY-00:05 0.93
June 0.139481E+10 0.93 538.12 01-JUN-00:10 0.93
July 0.144131E+10 0.93 538.12 01-JUL-00:10 0.93
August 0.144131E+10 0.93 538.12 01-AUG-00:10 0.93
September 0.139481E+10 0.93 538.12 01-SEP-00:10 0.93
October 0.144131E+10 0.93 538.12 01-OCT-00:10 0.93
November 0.139481E+10 0.93 538.12 01-NOV-00:10 0.93
December 0.144131E+10 0.93 538.12 01-DEC-00:10 0.93
           
Annual Sum or Average 0.169702E+11 0.93      
Minimum of Months 0.130183E+10 0.93 538.12   0.93
Maximum of Months 0.144131E+10 0.93 538.12   0.93



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.490869E+10 0.441782E+10 10022.81 10-JAN-21:33 9020.53 9020.53 70.56 18.66
February 0.359068E+10 0.323161E+10 8944.67 17-FEB-07:10 8050.20 8050.20 69.71 15.31
March 0.272986E+10 0.245687E+10 8016.36 08-MAR-07:10 7214.72 7214.72 70.13 12.92
April 0.860020E+09 0.774018E+09 11007.68 30-APR-19:16 9906.91 9906.91 64.20 22.76
May 0.128213E+10 0.115392E+10 6004.63 04-MAY-03:47 5404.17 5404.17 62.42 8.76
June 0.187214E+09 0.168493E+09 6562.19 18-JUN-21:06 5905.97 5905.97 63.07 9.83
July 58960115.95 53064104.35 5034.41 04-JUL-22:20 4530.97 4530.97 70.68 7.01
August 32267998.82 29041198.94 4580.50 20-AUG-23:05 4122.45 4122.45 69.58 6.27
September 0.286705E+09 0.258035E+09 6004.78 04-SEP-06:10 5404.31 5404.31 55.63 8.79
October 0.122521E+10 0.110269E+10 5100.30 07-OCT-06:30 4590.27 4590.27 66.64 7.14
November 0.240256E+10 0.216230E+10 8669.16 29-NOV-07:10 7802.25 7802.25 67.54 14.58
December 0.423054E+10 0.380748E+10 8750.24 27-DEC-07:10 7875.21 7875.21 65.09 14.82
                 
Annual Sum or Average 0.217948E+11 0.196153E+11            
Minimum of Months 32267998.82 29041198.94 4580.50   4122.45 4122.45 55.63 6.27
Maximum of Months 0.490869E+10 0.441782E+10 11007.68   9906.91 9906.91 70.68 22.76



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 578.36 520.52 0.11 30-JAN-06:02 0.10 0.10 6.70 0.00
February 45575.38 41017.85 312.53 20-FEB-15:01 281.27 281.27 6.70 0.40
March 217425.69 195683.12 684.65 18-MAR-05:02 616.18 616.18 6.71 0.89
April 0.114961E+10 0.103465E+10 15539.61 28-APR-14:40 13985.65 13985.65 7.11 48.02
May 0.175988E+10 0.158389E+10 14895.62 22-MAY-16:00 13406.06 13406.06 6.78 40.41
June 0.490523E+10 0.441471E+10 15260.17 20-JUN-15:00 13734.16 13734.16 6.98 44.37
July 0.816291E+10 0.734662E+10 15588.02 06-JUL-15:00 14029.22 14029.22 6.95 48.70
August 0.108057E+11 0.972514E+10 15396.42 14-AUG-16:40 13856.77 13856.77 6.78 46.08
September 0.589001E+10 0.530101E+10 15697.17 25-SEP-14:00 14127.46 14127.46 7.06 50.28
October 0.461242E+09 0.415118E+09 6968.83 06-OCT-15:20 6271.95 6271.95 7.86 10.90
November 17736740.94 15963066.85 5628.78 24-NOV-12:00 5065.90 5065.90 7.22 8.41
December 540.49 486.44 0.04 15-DEC-06:01 0.04 0.04 7.20 0.00
                 
Annual Sum or Average 0.331526E+11 0.298373E+11            
Minimum of Months 540.49 486.44 0.04   0.04 0.04 6.70 0.00
Maximum of Months 0.108057E+11 0.972514E+10 15697.17   14127.46 14127.46 7.86 50.28



Table of Contents

Report: PumpReportMonthly

For: SHWSYS1 PUMP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871592.27 56.21 01-JAN-06:05 16.86 16.86 73.73 0.44
February 0.101979E+09 30593696.24 56.21 01-FEB-06:02 16.86 16.86 64.94 0.44
March 0.112905E+09 33871592.27 56.21 01-MAR-06:01 16.86 16.86 60.48 0.44
April 0.109263E+09 32778960.26 56.21 01-APR-05:01 16.86 16.86 61.13 0.44
May 0.112905E+09 33871592.27 56.21 01-MAY-05:01 16.86 16.86 79.39 0.44
June 0.109263E+09 32778960.26 56.21 01-JUN-05:01 16.86 16.86 61.66 0.44
July 0.112905E+09 33871592.27 56.21 01-JUL-05:01 16.86 16.86 62.44 0.44
August 0.112905E+09 33871592.27 56.21 01-AUG-05:01 16.86 16.86 61.31 0.44
September 0.109263E+09 32778960.26 56.21 01-SEP-05:01 16.86 16.86 62.71 0.44
October 0.112905E+09 33871592.27 56.21 01-OCT-05:10 16.86 16.86 74.88 0.44
November 0.109263E+09 32778960.26 56.21 01-NOV-05:01 16.86 16.86 61.80 0.44
December 0.112905E+09 33871592.27 56.21 01-DEC-06:01 16.86 16.86 60.88 0.44
                 
Annual Sum or Average 0.132937E+10 0.398811E+09            
Minimum of Months 0.101979E+09 30593696.24 56.21   16.86 16.86 60.48 0.44
Maximum of Months 0.112905E+09 33871592.27 56.21   16.86 16.86 79.39 0.44



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.176981E+09 0.159283E+09 6630.98 01-JAN-22:11 5967.88 5967.88 6.73 83.05
February 97475375.31 87727837.78 6630.98 02-FEB-06:30 5967.88 5967.88 6.73 83.05
March 0.234007E+09 0.210606E+09 6630.98 07-MAR-06:01 5967.88 5967.88 6.73 83.05
April 0.214406E+10 0.192965E+10 6630.98 03-APR-05:08 5967.88 5967.88 6.73 83.05
May 0.221110E+10 0.198999E+10 6630.98 03-MAY-04:03 5967.88 5967.88 6.93 83.05
June 0.560142E+10 0.504128E+10 6630.98 01-JUN-04:03 5967.88 5967.88 6.76 83.05
July 0.908615E+10 0.817754E+10 6630.98 01-JUL-03:01 5967.88 5967.88 6.82 83.05
August 0.104784E+11 0.943059E+10 6630.98 01-AUG-03:01 5967.88 5967.88 6.88 83.05
September 0.694403E+10 0.624962E+10 6630.98 01-SEP-03:01 5967.88 5967.88 6.85 83.05
October 0.131021E+10 0.117919E+10 6630.98 01-OCT-10:53 5967.88 5967.88 6.73 83.05
November 0.215497E+09 0.193948E+09 6630.98 02-NOV-03:01 5967.88 5967.88 6.74 83.05
December 0.206735E+09 0.186061E+09 6630.98 04-DEC-05:07 5967.88 5967.88 6.73 83.05
                 
Annual Sum or Average 0.387061E+11 0.348355E+11            
Minimum of Months 97475375.31 87727837.78 6630.98   5967.88 5967.88 6.73 83.05
Maximum of Months 0.104784E+11 0.943059E+10 6630.98   5967.88 5967.88 6.93 83.05



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.888757E+10 0.799882E+10 3318.24 01-JAN-00:05 2986.42 2986.42 21.76 13.86
February 0.802749E+10 0.722474E+10 3318.24 01-FEB-00:10 2986.42 2986.42 24.16 13.86
March 0.888757E+10 0.799882E+10 3318.24 01-MAR-00:10 2986.42 2986.42 26.98 13.86
April 0.860088E+10 0.774079E+10 3318.24 01-APR-00:10 2986.42 2986.42 29.78 13.86
May 0.888757E+10 0.799882E+10 3318.24 01-MAY-00:05 2986.42 2986.42 24.02 13.86
June 0.860088E+10 0.774079E+10 3318.24 01-JUN-00:10 2986.42 2986.42 24.33 13.86
July 0.888757E+10 0.799882E+10 3318.24 01-JUL-00:10 2986.42 2986.42 27.03 13.86
August 0.888757E+10 0.799882E+10 3318.24 01-AUG-00:10 2986.42 2986.42 29.95 13.86
September 0.860088E+10 0.774079E+10 3318.24 01-SEP-00:10 2986.42 2986.42 23.20 13.86
October 0.888757E+10 0.799882E+10 3318.24 01-OCT-00:10 2986.42 2986.42 24.27 13.86
November 0.860088E+10 0.774079E+10 3318.24 01-NOV-00:10 2986.42 2986.42 26.99 13.86
December 0.888757E+10 0.799882E+10 3318.24 01-DEC-00:10 2986.42 2986.42 29.73 13.86
                 
Annual Sum or Average 0.104644E+12 0.941796E+11            
Minimum of Months 0.802749E+10 0.722474E+10 3318.24   2986.42 2986.42 21.76 13.86
Maximum of Months 0.888757E+10 0.799882E+10 3318.24   2986.42 2986.42 29.95 13.86



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.341121E+09 0.307009E+09 12782.26 26-JAN-06:30 11504.03 11504.03 21.16 50.20
February 0.187876E+09 0.169088E+09 12781.90 17-FEB-06:15 11503.71 11503.71 21.12 50.20
March 0.451041E+09 0.405937E+09 12782.05 27-MAR-06:00 11503.84 11503.84 21.14 50.20
April 0.418538E+10 0.376684E+10 25633.88 28-APR-14:40 23070.49 23070.49 24.93 100.40
May 0.445096E+10 0.400587E+10 25638.87 22-MAY-14:40 23074.98 23074.98 25.17 100.40
June 0.118934E+11 0.107041E+11 25702.00 13-JUN-16:00 23131.80 23131.80 28.10 100.40
July 0.187428E+11 0.168685E+11 25662.61 21-JUL-16:00 23096.35 23096.35 26.27 100.40
August 0.217288E+11 0.195559E+11 25653.44 14-AUG-13:10 23088.10 23088.10 25.85 100.40
September 0.142573E+11 0.128315E+11 25638.37 12-SEP-12:10 23074.53 23074.53 25.15 100.40
October 0.252683E+10 0.227415E+10 12804.84 06-OCT-15:30 11524.36 11524.36 23.62 50.20
November 0.415393E+09 0.373854E+09 12792.69 24-NOV-12:00 11513.42 11513.42 22.30 50.20
December 0.398474E+09 0.358627E+09 12782.07 15-DEC-06:50 11503.86 11503.86 21.14 50.20
                 
Annual Sum or Average 0.795794E+11 0.716215E+11            
Minimum of Months 0.187876E+09 0.169088E+09 12781.90   11503.71 11503.71 21.12 50.20
Maximum of Months 0.217288E+11 0.195559E+11 25702.00   23131.80 23131.80 28.10 100.40



Table of Contents

Report: CondLoopDemandReportMonthly

For: SHWSYS1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 6880.00 37436.27 01-JAN-08:14 80.26 82.22 13541.82 53224.27 31-JAN-12:50
February 6503.84 37386.81 26-FEB-08:30 80.23 82.22 13752.49 53331.59 10-FEB-12:50
March 5265.41 37425.88 26-MAR-07:40 80.25 82.22 14737.46 53221.47 01-MAR-12:50
April 6308.59 37520.60 30-APR-07:16 80.30 82.22 13312.76 52441.56 03-APR-11:30
May 6203.49 37615.30 29-MAY-07:10 80.36 82.22 13435.60 51314.32 01-MAY-11:50
June 5576.66 37695.05 25-JUN-07:08 80.40 82.22 13425.55 49848.64 01-JUN-11:30
July 7196.60 37758.63 30-JUL-07:05 80.43 82.22 11766.64 48620.28 03-JUL-12:00
August 5533.03 37766.48 13-AUG-07:03 80.44 82.22 13196.18 47944.00 02-AUG-11:40
September 6521.64 37757.52 03-SEP-07:15 80.43 82.22 12187.26 48617.19 29-SEP-11:20
October 7097.26 37709.53 01-OCT-07:10 80.41 82.22 12433.75 49853.02 31-OCT-11:30
November 7144.10 37608.40 05-NOV-07:30 80.35 82.22 13045.92 51244.28 30-NOV-12:50
December 6975.84 37517.04 03-DEC-08:40 80.30 82.22 12886.29 52492.49 29-DEC-12:15
                 
Annual Sum or Average 6433.80         13140.12    
Minimum of Months 5265.41 37386.81   80.23 82.22 11766.64 47944.00  
Maximum of Months 7196.60 37766.48   80.44 82.22 14737.46 53331.59  



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.06 325.33 01-JAN-12:40 82.03 82.03 156780.25 923581.36 10-JAN-21:17
February 0.00 0.00 01-FEB-00:10 59.15 59.15 134796.88 793948.01 17-FEB-07:20
March 0.00 0.00 01-MAR-00:10 64.72 64.72 106698.55 730253.67 26-MAR-23:40
April 0.00 0.00 01-APR-00:10 62.54 62.54 39343.56 1696838.90 30-APR-19:16
May 1.45 816.29 04-MAY-15:00 82.08 82.08 31942.46 1044547.33 24-MAY-03:47
June 0.00 0.00 01-JUN-00:10 62.47 62.47 8833.86 849894.18 10-JUN-03:47
July 0.00 0.00 01-JUL-00:10 50.04 50.04 2500.32 784887.45 02-JUL-16:30
August 0.00 0.00 01-AUG-00:10 55.12 55.12 1366.93 791457.16 06-AUG-15:30
September 0.00 0.00 01-SEP-00:10 49.61 49.61 10128.05 969902.25 04-SEP-06:10
October 0.00 0.00 01-OCT-00:10 51.51 51.51 47202.48 609486.41 09-OCT-07:30
November 0.00 0.00 01-NOV-00:10 59.97 59.97 98409.55 883434.54 29-NOV-07:10
December 0.00 0.00 01-DEC-00:10 63.87 63.87 167648.98 1086355.14 30-DEC-07:10
                 
Annual Sum or Average 0.13         66887.95    
Minimum of Months 0.00 0.00   49.61 49.61 1366.93 609486.41  
Maximum of Months 1.45 816.29   82.08 82.08 167648.98 1696838.90  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 118.19 11861.84 30-JAN-05:30 6.73 6.72 0.00 0.00 01-JAN-00:05
February 72.06 11861.84 17-FEB-07:00 6.73 6.72 0.00 0.00 01-FEB-00:10
March 156.34 12289.03 18-MAR-05:02 6.74 6.72 0.00 0.00 01-MAR-00:10
April 44313.32 1132812.64 28-APR-14:40 9.95 6.70 0.00 0.00 01-APR-00:10
May 51053.99 1156347.53 22-MAY-14:30 10.02 6.70 0.00 0.00 01-MAY-00:05
June 145739.66 1402450.95 13-JUN-16:00 10.73 6.70 0.00 0.00 01-JUN-00:10
July 242794.79 1325289.30 21-JUL-16:00 10.51 6.70 0.00 0.00 01-JUL-00:10
August 322506.65 1209264.14 14-AUG-16:00 10.17 6.70 0.00 0.00 01-AUG-00:10
September 179150.39 1246319.84 22-SEP-12:40 10.28 8.09 0.00 0.00 01-SEP-00:10
October 16018.09 721346.94 06-OCT-15:30 8.77 7.73 0.00 0.00 01-OCT-00:10
November 519.59 330268.89 24-NOV-12:00 7.65 7.17 0.00 0.00 01-NOV-00:10
December 138.09 11864.06 26-DEC-07:00 6.73 6.72 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 84137.20         0.00    
Minimum of Months 72.06 11861.84   6.73 6.70 0.00 0.00  
Maximum of Months 322506.65 1402450.95   10.73 8.09 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 6.70 6.70 0.00 0.00 01-JAN-00:05
February 0.00 30.08 20-FEB-15:01 6.72 6.72 0.00 0.00 01-FEB-00:10
March 0.04 479.49 18-MAR-05:02 6.83 6.72 0.00 0.00 01-MAR-00:10
April 25764.61 1136711.95 28-APR-14:40 12.35 8.03 0.00 0.00 01-APR-00:10
May 33418.69 1154977.83 22-MAY-14:30 13.98 6.70 0.00 0.00 01-MAY-00:05
June 104973.45 1398707.09 13-JUN-16:00 14.94 6.70 0.00 0.00 01-JUN-00:10
July 168596.10 1322217.04 21-JUL-16:00 13.63 6.70 0.00 0.00 01-JUL-00:10
August 222052.51 1205386.16 14-AUG-16:00 14.33 6.70 0.00 0.00 01-AUG-00:10
September 121443.61 1147876.78 12-SEP-15:40 14.01 6.70 0.00 0.00 01-SEP-00:10
October 8214.84 403770.84 06-OCT-15:20 15.55 7.74 0.00 0.00 01-OCT-00:10
November 197.86 185472.38 24-NOV-12:00 11.97 7.17 0.00 0.00 01-NOV-00:10
December 0.01 1.16 15-DEC-06:02 11.96 6.72 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 57457.90         0.00    
Minimum of Months 0.00 0.00   6.70 6.70 0.00 0.00  
Maximum of Months 222052.51 1398707.09   15.55 8.03 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 163906.92 533212.79 21-JAN-03:51 29.32 18.33 0.00 0.00 01-JAN-00:05
February 298671.46 576487.17 04-FEB-21:01 30.21 18.33 0.00 0.00 01-FEB-00:10
March 436116.20 593035.78 22-MAR-21:20 30.54 18.33 0.00 0.00 01-MAR-00:10
April 600214.67 1167260.20 30-APR-18:33 42.11 29.28 0.00 0.00 01-APR-00:10
May 178849.14 541204.65 22-MAY-15:00 29.49 25.58 0.00 0.00 01-MAY-00:05
June 343049.11 908487.01 13-JUN-17:00 36.93 29.88 0.00 0.00 01-JUN-00:10
July 533244.53 1283994.83 22-JUL-18:00 44.43 34.22 0.00 0.00 01-JUL-00:10
August 722918.74 1324624.67 14-AUG-17:20 45.23 32.34 0.00 0.00 01-AUG-00:10
September 196093.60 535200.41 20-SEP-21:20 29.36 18.33 0.00 0.00 01-SEP-00:10
October 304950.73 580351.19 21-OCT-20:51 30.29 18.33 0.00 0.00 01-OCT-00:10
November 435877.83 592394.06 01-NOV-21:30 30.53 18.33 0.00 0.00 01-NOV-00:10
December 568159.86 610363.33 12-DEC-22:43 30.90 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 399376.40         0.00    
Minimum of Months 163906.92 533212.79   29.32 18.33 0.00 0.00  
Maximum of Months 722918.74 1324624.67   45.23 34.22 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 5.47 13400.31 26-JAN-06:30 21.16 20.63 187.31 75325.14 07-JAN-06:40
February 1.10 5243.09 17-FEB-06:15 21.12 20.46 139.68 71715.20 02-FEB-06:40
March 7.12 8657.45 27-MAR-06:00 21.14 20.49 214.28 75189.62 21-MAR-06:00
April 33321.21 1605430.31 28-APR-14:40 24.93 21.83 545.85 68188.65 19-APR-05:30
May 41564.98 1707213.26 22-MAY-14:40 25.17 21.90 213.39 68322.51 06-MAY-05:30
June 142079.24 2937597.28 13-JUN-16:00 28.10 24.17 345.42 69487.37 08-JUN-05:40
July 206584.25 2170635.66 21-JUL-16:00 26.27 22.61 423.83 49910.38 31-JUL-05:30
August 269067.18 1991817.92 14-AUG-13:10 25.85 22.62 257.04 45279.15 24-AUG-03:01
September 150715.73 1697530.70 12-SEP-12:10 25.15 21.91 488.58 56101.53 21-SEP-05:30
October 11429.94 528402.96 06-OCT-15:30 23.62 21.58 341.62 61206.31 19-OCT-06:00
November 297.09 251553.03 24-NOV-12:00 22.30 21.33 232.62 73721.96 20-NOV-06:50
December 3.86 9036.46 15-DEC-06:50 21.14 20.52 188.13 69797.20 18-DEC-06:50
                 
Annual Sum or Average 71728.70         298.30    
Minimum of Months 1.10 5243.09   21.12 20.46 139.68 45279.15  
Maximum of Months 269067.18 2937597.28   28.10 24.17 545.85 75325.14  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.08 7.48
February 0.08 7.48
March 0.47 7.48
April 0.26 7.48
May 0.61 7.48
June 1.39 7.48
July 0.58 7.48
August 1.18 7.48
September 1.19 7.48
October 0.58 7.48
November 0.65 7.48
December 0.64 7.48
     
Annual Sum or Average 7.74 7.48
Minimum of Months 0.08 7.48
Maximum of Months 1.39 7.48



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.87 11.45
February 1.55 7.47
March 1.81 2.83
April 5.96 3.35
May 2.26 5.65
June 3.62 3.96
July 6.95 2.74
August 12.35 1.96
September 3.21 3.63
October 1.90 4.34
November 2.04 4.37
December 0.87 4.96
     
Annual Sum or Average 43.38 3.46
Minimum of Months 0.87 1.96
Maximum of Months 12.35 11.45



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.45 11.20
February 0.54 12.92
March 1.41 12.37
April 2.71 13.33
May 3.16 11.98
June 1.74 9.81
July 1.76 9.69
August 0.90 9.69
September 3.22 9.73
October 2.78 12.60
November 1.39 11.55
December 0.11 6.72
     
Annual Sum or Average 20.18 11.38
Minimum of Months 0.11 6.72
Maximum of Months 3.22 13.33



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.25 4.48
February 0.06 0.00
March 0.11 0.00
April 0.31 12.21
May 0.71 8.56
June 0.58 6.72
July 0.64 7.45
August 0.31 5.50
September 0.71 8.29
October 0.06 0.00
November 0.17 0.00
December 0.28 0.00
     
Annual Sum or Average 4.17 6.52
Minimum of Months 0.06 0.00
Maximum of Months 0.71 12.21



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.50 0.00
February 0.22 0.21
March 0.33 0.00
April 1.01 0.28
May 0.57 0.37
June 0.98 0.51
July 1.59 0.38
August 1.43 0.22
September 0.60 0.45
October 0.31 0.38
November 0.06 0.00
December 0.00 0.00
     
Annual Sum or Average 7.59 0.31
Minimum of Months 0.00 0.00
Maximum of Months 1.59 0.51



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.47 0.45
February 2.10 0.38
March 2.04 0.13
April 7.75 0.28
May 3.45 0.28
June 5.99 0.23
July 8.70 0.22
August 10.80 0.16
September 5.03 0.28
October 4.01 0.27
November 2.98 0.25
December 1.46 0.37
     
Annual Sum or Average 55.78 0.25
Minimum of Months 1.46 0.13
Maximum of Months 10.80 0.45



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.05 0.37
February 1.54 0.48
March 1.92 0.19
April 6.31 0.38
May 2.97 0.38
June 5.54 0.40
July 8.79 0.38
August 10.89 0.26
September 3.95 0.38
October 2.67 0.28
November 2.21 0.32
December 1.06 0.51
     
Annual Sum or Average 48.91 0.35
Minimum of Months 1.05 0.19
Maximum of Months 10.89 0.51



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 2.45 0.37
February 4.31 0.33
March 4.39 0.15
April 9.21 0.23
May 6.40 0.21
June 7.69 0.24
July 10.77 0.22
August 14.45 0.16
September 7.57 0.25
October 6.22 0.24
November 5.18 0.25
December 5.23 0.29
     
Annual Sum or Average 83.87 0.23
Minimum of Months 2.45 0.15
Maximum of Months 14.45 0.37



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.44 0.00
May 0.08 0.28
June 0.50 0.00
July 0.66 0.19
August 0.54 0.34
September 0.71 0.07
October 0.14 1.01
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 3.07 0.17
Minimum of Months 0.00 0.00
Maximum of Months 0.71 1.01



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.35 0.54
February 0.06 0.54
March 0.06 0.00
April 3.05 0.24
May 2.44 0.26
June 4.08 0.26
July 3.76 0.28
August 3.51 0.38
September 4.29 0.39
October 1.17 0.28
November 0.42 0.54
December 0.06 0.54
     
Annual Sum or Average 23.24 0.31
Minimum of Months 0.06 0.00
Maximum of Months 4.29 0.54



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.32 1.43
February 0.22 0.84
March 0.42 1.01
April 2.12 0.40
May 1.67 0.28
June 3.27 0.39
July 3.22 0.45
August 2.85 0.60
September 3.19 0.54
October 1.30 0.62
November 0.52 1.20
December 0.00 0.00
     
Annual Sum or Average 19.10 0.52
Minimum of Months 0.00 0.00
Maximum of Months 3.27 1.43



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.29 0.54
February 0.00 0.00
March 0.33 0.54
April 3.35 0.29
May 2.99 0.30
June 3.77 0.27
July 3.91 0.28
August 3.94 0.39
September 3.96 0.38
October 1.34 0.40
November 0.44 0.72
December 0.06 0.54
     
Annual Sum or Average 24.37 0.34
Minimum of Months 0.00 0.00
Maximum of Months 3.96 0.72



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.31 1.23
February 0.06 0.84
March 0.04 0.84
April 0.06 0.84
May 0.00 0.00
June 0.26 1.03
July 0.41 0.65
August 0.11 1.27
September 0.18 1.10
October 0.00 0.00
November 0.08 0.84
December 0.18 0.65
     
Annual Sum or Average 1.68 0.93
Minimum of Months 0.00 0.00
Maximum of Months 0.41 1.27



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.17 0.54
February 0.14 0.54
March 0.04 0.54
April 0.51 0.54
May 1.25 0.37
June 2.16 0.46
July 2.37 0.35
August 2.01 0.62
September 1.85 0.56
October 0.22 0.54
November 0.12 0.54
December 0.22 0.54
     
Annual Sum or Average 11.07 0.48
Minimum of Months 0.04 0.35
Maximum of Months 2.37 0.62



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.22 0.84
March 0.04 0.84
April 0.38 0.75
May 0.94 0.55
June 1.53 0.73
July 2.44 0.65
August 1.69 0.94
September 2.01 0.92
October 0.32 0.84
November 0.29 0.84
December 0.14 0.84
     
Annual Sum or Average 10.00 0.78
Minimum of Months 0.00 0.00
Maximum of Months 2.44 0.94



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.06 0.54
March 0.04 0.54
April 0.82 0.57
May 1.67 0.42
June 1.79 0.48
July 2.65 0.46
August 2.75 0.59
September 2.21 0.63
October 0.26 0.54
November 0.18 0.54
December 0.14 0.54
     
Annual Sum or Average 12.58 0.53
Minimum of Months 0.00 0.00
Maximum of Months 2.75 0.63



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 38.99 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 38.99  
Minimum of Months 0.00 0.00
Maximum of Months 38.99 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 2.90 0.00
February 2.42 0.00
March 4.60 0.00
April 0.85 0.00
May 2.70 0.00
June 3.40 0.00
July 0.23 0.00
August 0.48 0.00
September 0.57 0.00
October 5.33 0.00
November 3.06 0.00
December 1.20 0.00
     
Annual Sum or Average 27.71  
Minimum of Months 0.23 0.00
Maximum of Months 5.33 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.801118E+09 0.00 0.00 0.172486E+11 0.00 0.00
February 14757865.11 0.00 531036.36 0.155917E+11 0.00 0.00
March 0.811277E+09 0.00 2423267.48 0.180025E+11 0.00 0.00
April 0.652840E+09 0.00 0.929681E+09 0.171288E+11 0.00 0.00
May 0.119749E+10 0.00 0.265793E+10 0.180024E+11 0.00 0.00
June 0.450890E+09 0.00 0.914233E+10 0.177111E+11 0.00 0.00
July 0.134650E+10 0.00 0.152393E+11 0.177937E+11 0.00 0.00
August 0.777435E+09 0.00 0.196218E+11 0.188525E+11 0.00 0.00
September 0.551136E+09 0.00 0.960111E+10 0.175251E+11 0.00 0.00
October 0.443178E+09 0.00 0.415902E+09 0.179671E+11 0.00 0.00
November 0.565681E+09 0.00 41798667.35 0.174409E+11 0.00 0.00
December 0.115528E+10 0.00 0.00 0.172094E+11 0.00 0.00
             
Annual Sum or Average 0.876758E+10 0.00 0.576528E+11 0.210474E+12 0.00 0.00
Minimum of Months 14757865.11 0.00 0.00 0.155917E+11 0.00 0.00
Maximum of Months 0.134650E+10 0.00 0.196218E+11 0.188525E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.202238E+11 0.00 1128.38 0.597730E+10 0.00 0.00
February 0.143228E+11 0.00 0.00 0.619981E+10 0.00 0.00
March 0.101405E+11 0.00 3778.63 0.802408E+10 0.00 0.00
April 0.237718E+10 0.00 0.578384E+10 0.101932E+11 0.00 0.00
May 0.280866E+10 0.00 0.693479E+10 0.778615E+10 0.00 0.00
June 0.192225E+09 0.00 0.224723E+11 0.805229E+10 0.00 0.00
July 4919624.50 0.00 0.381863E+11 0.822740E+10 0.00 0.00
August 155991.55 0.00 0.508987E+11 0.916500E+10 0.00 0.00
September 0.544819E+09 0.00 0.246417E+11 0.688406E+10 0.00 0.00
October 0.400800E+10 0.00 0.193770E+10 0.739597E+10 0.00 0.00
November 0.815363E+10 0.00 59234398.59 0.729619E+10 0.00 0.00
December 0.149452E+11 0.00 27.44 0.709522E+10 0.00 0.00
             
Annual Sum or Average 0.777219E+11 0.00 0.150915E+12 0.922967E+11 0.00 0.00
Minimum of Months 155991.55 0.00 0.00 0.597730E+10 0.00 0.00
Maximum of Months 0.202238E+11 0.00 0.508987E+11 0.101932E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.343944E+12 0.00 23905.69 0.428426E+11 0.00 0.00
February 0.267882E+12 0.00 7086.85 0.410819E+11 0.00 0.00
March 0.234800E+12 0.00 31410.90 0.492833E+11 0.00 0.00
April 0.847058E+11 0.00 0.473147E+11 0.607205E+11 0.00 0.00
May 0.690578E+11 0.00 0.599592E+11 0.593413E+11 0.00 0.00
June 0.191495E+11 0.00 0.185581E+12 0.590630E+11 0.00 0.00
July 0.432010E+10 0.00 0.301755E+12 0.552376E+11 0.00 0.00
August 0.240775E+10 0.00 0.397839E+12 0.595277E+11 0.00 0.00
September 0.212715E+11 0.00 0.216078E+12 0.552781E+11 0.00 0.00
October 0.101165E+12 0.00 0.161656E+11 0.504492E+11 0.00 0.00
November 0.208457E+12 0.00 0.355713E+09 0.430532E+11 0.00 0.00
December 0.375985E+12 0.00 22770.01 0.380751E+11 0.00 0.00
             
Annual Sum or Average 0.173314E+13 0.00 0.122505E+13 0.613954E+12 0.00 0.00
Minimum of Months 0.240775E+10 0.00 7086.85 0.380751E+11 0.00 0.00
Maximum of Months 0.375985E+12 0.00 0.397839E+12 0.607205E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.590277E+11 0.00 399.61 0.318255E+10 0.00 0.00
February 0.471658E+11 0.00 0.00 0.291001E+10 0.00 0.00
March 0.428208E+11 0.00 159.16 0.343498E+10 0.00 0.00
April 0.150367E+11 0.00 0.477986E+10 0.468734E+10 0.00 0.00
May 0.123370E+11 0.00 0.644877E+10 0.494626E+10 0.00 0.00
June 0.328128E+10 0.00 0.203720E+11 0.546237E+10 0.00 0.00
July 0.970189E+09 0.00 0.321775E+11 0.534511E+10 0.00 0.00
August 0.568845E+09 0.00 0.401524E+11 0.548811E+10 0.00 0.00
September 0.396730E+10 0.00 0.204930E+11 0.453071E+10 0.00 0.00
October 0.209557E+11 0.00 0.133845E+10 0.346266E+10 0.00 0.00
November 0.401277E+11 0.00 24264352.54 0.303866E+10 0.00 0.00
December 0.619445E+11 0.00 0.00 0.307787E+10 0.00 0.00
             
Annual Sum or Average 0.308203E+12 0.00 0.125786E+12 0.495666E+11 0.00 0.00
Minimum of Months 0.568845E+09 0.00 0.00 0.291001E+10 0.00 0.00
Maximum of Months 0.619445E+11 0.00 0.401524E+11 0.548811E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.198138E+10 0.00 0.379907E+12 0.177291E+12 0.00 1.02
February 0.887288E+09 0.00 0.600403E+12 0.205822E+12 0.00 0.77
March 0.716775E+09 0.00 0.953079E+12 0.277254E+12 0.00 1.08
April 0.243560E+09 0.00 0.120904E+13 0.316311E+12 0.00 0.86
May 0.172524E+10 0.00 0.385194E+12 0.176600E+12 0.00 0.39
June 0.288701E+09 0.00 0.651901E+12 0.221362E+12 0.00 0.07
July 52458219.91 0.00 0.969664E+12 0.283855E+12 0.00 0.02
August 38651341.52 0.00 0.126718E+13 0.339108E+12 0.00 0.02
September 0.238439E+09 0.00 0.375296E+12 0.170059E+12 0.00 0.07
October 0.129186E+10 0.00 0.671192E+12 0.227771E+12 0.00 0.32
November 0.785444E+09 0.00 0.925400E+12 0.267225E+12 0.00 0.58
December 0.243681E+09 0.00 0.124203E+13 0.323528E+12 0.00 1.09
             
Annual Sum or Average 0.849347E+10 0.00 0.963028E+13 0.298619E+13 0.00 6.29
Minimum of Months 38651341.52 0.00 0.375296E+12 0.170059E+12 0.00 0.02
Maximum of Months 0.198138E+10 0.00 0.126718E+13 0.339108E+12 0.00 1.09



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.595054E+10 0.276871E+10 0.00 0.00
February 0.00 0.00 0.111024E+11 0.359125E+10 0.00 0.00
March 0.00 0.00 0.185476E+11 0.507611E+10 0.00 0.00
April 0.00 0.00 0.241893E+11 0.599881E+10 0.00 0.00
May 0.00 0.00 0.678796E+10 0.293914E+10 0.00 0.00
June 0.00 0.00 0.126622E+11 0.403990E+10 0.00 0.00
July 0.00 0.00 0.193081E+11 0.539943E+10 0.00 0.00
August 0.00 0.00 0.254594E+11 0.659779E+10 0.00 0.00
September 0.00 0.00 0.655881E+10 0.285842E+10 0.00 0.00
October 0.00 0.00 0.126139E+11 0.403541E+10 0.00 0.00
November 0.00 0.00 0.179237E+11 0.490590E+10 0.00 0.00
December 0.00 0.00 0.243635E+11 0.604186E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.185467E+12 0.542527E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.595054E+10 0.276871E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.254594E+11 0.659779E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.419016E+11 0.234463E+11 0.00 0.00
February 0.00 0.00 0.923501E+11 0.317696E+11 0.00 0.00
March 0.00 0.00 0.163656E+12 0.461635E+11 0.00 0.00
April 0.00 0.00 0.223996E+12 0.561530E+11 0.00 0.00
May 0.00 0.00 0.572962E+11 0.265796E+11 0.00 0.00
June 0.00 0.00 0.115409E+12 0.375664E+11 0.00 0.00
July 0.00 0.00 0.179329E+12 0.506758E+11 0.00 0.00
August 0.00 0.00 0.238594E+12 0.622336E+11 0.00 0.00
September 0.00 0.00 0.551761E+11 0.258105E+11 0.00 0.00
October 0.00 0.00 0.108217E+12 0.362896E+11 0.00 0.00
November 0.00 0.00 0.155286E+12 0.441207E+11 0.00 0.00
December 0.00 0.00 0.211583E+12 0.542681E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.164279E+13 0.495077E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.419016E+11 0.234463E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.238594E+12 0.622336E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.178333E+10 0.185217E+10 0.00 0.00
February 0.00 0.00 0.714033E+10 0.280065E+10 0.00 0.00
March 0.00 0.00 0.146397E+11 0.434248E+10 0.00 0.00
April 0.00 0.00 0.214950E+11 0.550027E+10 0.00 0.00
May 0.00 0.00 0.493630E+10 0.252331E+10 0.00 0.00
June 0.00 0.00 0.111502E+11 0.371203E+10 0.00 0.00
July 0.00 0.00 0.176040E+11 0.504321E+10 0.00 0.00
August 0.00 0.00 0.234911E+11 0.619826E+10 0.00 0.00
September 0.00 0.00 0.476670E+10 0.245413E+10 0.00 0.00
October 0.00 0.00 0.918400E+10 0.334780E+10 0.00 0.00
November 0.00 0.00 0.134891E+11 0.407988E+10 0.00 0.00
December 0.00 0.00 0.185921E+11 0.502780E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.148272E+12 0.468820E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.178333E+10 0.185217E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.234911E+11 0.619826E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.172486E+11 0.00 0.801118E+09 0.00 0.00 0.00 0.00 0.00
February 0.155917E+11 531036.36 14757865.11 0.00 0.00 0.00 0.00 0.00
March 0.180025E+11 2423267.48 0.811277E+09 0.00 0.00 0.00 0.00 0.00
April 0.171288E+11 0.929681E+09 0.652840E+09 0.00 0.00 0.00 0.00 0.00
May 0.180024E+11 0.265793E+10 0.119749E+10 0.00 0.00 0.00 0.00 0.00
June 0.177111E+11 0.914233E+10 0.450890E+09 0.00 0.00 0.00 0.00 0.00
July 0.177937E+11 0.152393E+11 0.134650E+10 0.00 0.00 0.00 0.00 0.00
August 0.188525E+11 0.196218E+11 0.777435E+09 0.00 0.00 0.00 0.00 0.00
September 0.175251E+11 0.960111E+10 0.551136E+09 0.00 0.00 0.00 0.00 0.00
October 0.179671E+11 0.415902E+09 0.443178E+09 0.00 0.00 0.00 0.00 0.00
November 0.174409E+11 41798667.35 0.565681E+09 0.00 0.00 0.00 0.00 0.00
December 0.172094E+11 0.00 0.115528E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.210474E+12 0.576528E+11 0.876758E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155917E+11 0.00 14757865.11 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188525E+11 0.196218E+11 0.134650E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.597730E+10 1128.38 0.202238E+11 0.00 0.00 0.00 0.00 0.00
February 0.619981E+10 0.00 0.143228E+11 0.00 0.00 0.00 0.00 0.00
March 0.802408E+10 3778.63 0.101405E+11 0.00 0.00 0.00 0.00 0.00
April 0.101932E+11 0.578384E+10 0.237718E+10 0.00 0.00 0.00 0.00 0.00
May 0.778615E+10 0.693479E+10 0.280866E+10 0.00 0.00 0.00 0.00 0.00
June 0.805229E+10 0.224723E+11 0.192225E+09 0.00 0.00 0.00 0.00 0.00
July 0.822740E+10 0.381863E+11 4919624.50 0.00 0.00 0.00 0.00 0.00
August 0.916500E+10 0.508987E+11 155991.55 0.00 0.00 0.00 0.00 0.00
September 0.688406E+10 0.246417E+11 0.544819E+09 0.00 0.00 0.00 0.00 0.00
October 0.739597E+10 0.193770E+10 0.400800E+10 0.00 0.00 0.00 0.00 0.00
November 0.729619E+10 59234398.59 0.815363E+10 0.00 0.00 0.00 0.00 0.00
December 0.709522E+10 27.44 0.149452E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.922967E+11 0.150915E+12 0.777219E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.597730E+10 0.00 155991.55 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101932E+11 0.508987E+11 0.202238E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.428426E+11 23905.69 0.343944E+12 0.00 0.00 0.00 0.00 0.00
February 0.410819E+11 7086.85 0.267882E+12 0.00 0.00 0.00 0.00 0.00
March 0.492833E+11 31410.90 0.234800E+12 0.00 0.00 0.00 0.00 0.00
April 0.607205E+11 0.473147E+11 0.847058E+11 0.00 0.00 0.00 0.00 0.00
May 0.593413E+11 0.599592E+11 0.690578E+11 0.00 0.00 0.00 0.00 0.00
June 0.590630E+11 0.185581E+12 0.191495E+11 0.00 0.00 0.00 0.00 0.00
July 0.552376E+11 0.301755E+12 0.432010E+10 0.00 0.00 0.00 0.00 0.00
August 0.595277E+11 0.397839E+12 0.240775E+10 0.00 0.00 0.00 0.00 0.00
September 0.552781E+11 0.216078E+12 0.212715E+11 0.00 0.00 0.00 0.00 0.00
October 0.504492E+11 0.161656E+11 0.101165E+12 0.00 0.00 0.00 0.00 0.00
November 0.430532E+11 0.355713E+09 0.208457E+12 0.00 0.00 0.00 0.00 0.00
December 0.380751E+11 22770.01 0.375985E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.613954E+12 0.122505E+13 0.173314E+13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.380751E+11 7086.85 0.240775E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.607205E+11 0.397839E+12 0.375985E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.318255E+10 399.61 0.590277E+11 0.00 0.00 0.00 0.00 0.00
February 0.291001E+10 0.00 0.471658E+11 0.00 0.00 0.00 0.00 0.00
March 0.343498E+10 159.16 0.428208E+11 0.00 0.00 0.00 0.00 0.00
April 0.468734E+10 0.477986E+10 0.150367E+11 0.00 0.00 0.00 0.00 0.00
May 0.494626E+10 0.644877E+10 0.123370E+11 0.00 0.00 0.00 0.00 0.00
June 0.546237E+10 0.203720E+11 0.328128E+10 0.00 0.00 0.00 0.00 0.00
July 0.534511E+10 0.321775E+11 0.970189E+09 0.00 0.00 0.00 0.00 0.00
August 0.548811E+10 0.401524E+11 0.568845E+09 0.00 0.00 0.00 0.00 0.00
September 0.453071E+10 0.204930E+11 0.396730E+10 0.00 0.00 0.00 0.00 0.00
October 0.346266E+10 0.133845E+10 0.209557E+11 0.00 0.00 0.00 0.00 0.00
November 0.303866E+10 24264352.54 0.401277E+11 0.00 0.00 0.00 0.00 0.00
December 0.307787E+10 0.00 0.619445E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.495666E+11 0.125786E+12 0.308203E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.291001E+10 0.00 0.568845E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.548811E+10 0.401524E+11 0.619445E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.953838E+11 0.324259E+12 0.198138E+10 0.00 0.00 0.271635E+10 0.00 0.00
February 0.861531E+11 0.512783E+12 0.887288E+09 0.00 0.00 0.206436E+10 0.00 0.00
March 0.953838E+11 0.813128E+12 0.716775E+09 0.00 0.00 0.289840E+10 0.00 0.00
April 0.923069E+11 0.102864E+13 0.243560E+09 0.00 0.00 0.230023E+10 0.00 0.00
May 0.953838E+11 0.328813E+12 0.172524E+10 0.00 0.00 0.105400E+10 0.00 0.00
June 0.923069E+11 0.556028E+12 0.288701E+09 0.00 0.00 0.180749E+09 0.00 0.00
July 0.953838E+11 0.822328E+12 52458219.91 0.00 0.00 43781512.49 0.00 0.00
August 0.953838E+11 0.106841E+13 38651341.52 0.00 0.00 55809400.59 0.00 0.00
September 0.923069E+11 0.320594E+12 0.238439E+09 0.00 0.00 0.184255E+09 0.00 0.00
October 0.953838E+11 0.573381E+12 0.129186E+10 0.00 0.00 0.864781E+09 0.00 0.00
November 0.923069E+11 0.790064E+12 0.785444E+09 0.00 0.00 0.155994E+10 0.00 0.00
December 0.953838E+11 0.105952E+13 0.243681E+09 0.00 0.00 0.290809E+10 0.00 0.00
                 
Annual Sum or Average 0.112307E+13 0.819794E+13 0.849347E+10 0.00 0.00 0.168307E+11 0.00 0.00
Minimum of Months 0.861531E+11 0.320594E+12 38651341.52 0.00 0.00 43781512.49 0.00 0.00
Maximum of Months 0.953838E+11 0.106841E+13 0.198138E+10 0.00 0.00 0.290809E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.148427E+10 0.502597E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134063E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148427E+10 0.156649E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143639E+10 0.203697E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148427E+10 0.572840E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143639E+10 0.106420E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148427E+10 0.161132E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148427E+10 0.211043E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143639E+10 0.552053E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148427E+10 0.106509E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143639E+10 0.151403E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148427E+10 0.205717E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.174761E+11 0.155907E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134063E+10 0.502597E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148427E+10 0.211043E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.141758E+11 0.353909E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128039E+11 0.779824E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.141758E+11 0.138220E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137185E+11 0.188617E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141758E+11 0.483491E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137185E+11 0.969864E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141758E+11 0.149636E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141758E+11 0.197767E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137185E+11 0.464338E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.141758E+11 0.913757E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137185E+11 0.131171E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.141758E+11 0.178654E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.166908E+12 0.138058E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128039E+11 0.353909E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141758E+11 0.197767E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.144131E+10 0.150639E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130183E+10 0.602953E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144131E+10 0.123644E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139481E+10 0.180977E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144131E+10 0.416466E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139481E+10 0.936770E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144131E+10 0.146841E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144131E+10 0.194661E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139481E+10 0.400925E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144131E+10 0.775460E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139481E+10 0.113943E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144131E+10 0.156986E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169702E+11 0.124537E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130183E+10 0.150639E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144131E+10 0.194661E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.172486E+11 0.801118E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155917E+11 14757865.11 531036.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.180025E+11 0.811277E+09 2423267.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.171288E+11 0.652840E+09 0.929681E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.180024E+11 0.119749E+10 0.265793E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.177111E+11 0.450890E+09 0.914233E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.177937E+11 0.134650E+10 0.152393E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.188525E+11 0.777435E+09 0.196218E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.175251E+11 0.551136E+09 0.960111E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.179671E+11 0.443178E+09 0.415902E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.174409E+11 0.565681E+09 41798667.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.172094E+11 0.115528E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.210474E+12 0.876758E+10 0.576528E+11 0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.155917E+11 14757865.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188525E+11 0.134650E+10 0.196218E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.597730E+10 0.202238E+11 1128.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.619981E+10 0.143228E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.802408E+10 0.101405E+11 3778.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101932E+11 0.237718E+10 0.578384E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.778615E+10 0.280866E+10 0.693479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.805229E+10 0.192225E+09 0.224723E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.822740E+10 4919624.50 0.381863E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.916500E+10 155991.55 0.508987E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.688406E+10 0.544819E+09 0.246417E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.739597E+10 0.400800E+10 0.193770E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.729619E+10 0.815363E+10 59234398.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.709522E+10 0.149452E+11 27.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.922967E+11 0.777219E+11 0.150915E+12 0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.597730E+10 155991.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101932E+11 0.202238E+11 0.508987E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.428426E+11 0.343944E+12 23905.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.410819E+11 0.267882E+12 7086.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.492833E+11 0.234800E+12 31410.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.607205E+11 0.847058E+11 0.473147E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.593413E+11 0.690578E+11 0.599592E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.590630E+11 0.191495E+11 0.185581E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.552376E+11 0.432010E+10 0.301755E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.595277E+11 0.240775E+10 0.397839E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.552781E+11 0.212715E+11 0.216078E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.504492E+11 0.101165E+12 0.161656E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.430532E+11 0.208457E+12 0.355713E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.380751E+11 0.375985E+12 22770.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.613954E+12 0.173314E+13 0.122505E+13 0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.380751E+11 0.240775E+10 7086.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.607205E+11 0.375985E+12 0.397839E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.318255E+10 0.590277E+11 399.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.291001E+10 0.471658E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.343498E+10 0.428208E+11 159.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.468734E+10 0.150367E+11 0.477986E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.494626E+10 0.123370E+11 0.644877E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.546237E+10 0.328128E+10 0.203720E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.534511E+10 0.970189E+09 0.321775E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.548811E+10 0.568845E+09 0.401524E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453071E+10 0.396730E+10 0.204930E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.346266E+10 0.209557E+11 0.133845E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.303866E+10 0.401277E+11 24264352.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.307787E+10 0.619445E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.495666E+11 0.308203E+12 0.125786E+12 0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.291001E+10 0.568845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.548811E+10 0.619445E+11 0.401524E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.953838E+11 0.198138E+10 0.379907E+12 0.00 0.791783E+11 0.00 0.00 0.00 0.272858E+10 0.00 0.00 0.00
February 0.861531E+11 0.887288E+09 0.600403E+12 0.00 0.117595E+12 0.00 0.00 0.00 0.207365E+10 0.00 0.00 0.00
March 0.953838E+11 0.716775E+09 0.953079E+12 0.00 0.178959E+12 0.00 0.00 0.00 0.291144E+10 0.00 0.00 0.00
April 0.923069E+11 0.243560E+09 0.120904E+13 0.00 0.221693E+12 0.00 0.00 0.00 0.231058E+10 0.00 0.00 0.00
May 0.953838E+11 0.172524E+10 0.385194E+12 0.00 0.801573E+11 0.00 0.00 0.00 0.105874E+10 0.00 0.00 0.00
June 0.923069E+11 0.288701E+09 0.651901E+12 0.00 0.128874E+12 0.00 0.00 0.00 0.181563E+09 0.00 0.00 0.00
July 0.953838E+11 52458219.91 0.969664E+12 0.00 0.188427E+12 0.00 0.00 0.00 43978590.82 0.00 0.00 0.00
August 0.953838E+11 38651341.52 0.126718E+13 0.00 0.243669E+12 0.00 0.00 0.00 56060621.32 0.00 0.00 0.00
September 0.923069E+11 0.238439E+09 0.375296E+12 0.00 0.775674E+11 0.00 0.00 0.00 0.185084E+09 0.00 0.00 0.00
October 0.953838E+11 0.129186E+10 0.671192E+12 0.00 0.131518E+12 0.00 0.00 0.00 0.868674E+09 0.00 0.00 0.00
November 0.923069E+11 0.785444E+09 0.925400E+12 0.00 0.173351E+12 0.00 0.00 0.00 0.156696E+10 0.00 0.00 0.00
December 0.953838E+11 0.243681E+09 0.124203E+13 0.00 0.225223E+12 0.00 0.00 0.00 0.292118E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.112307E+13 0.849347E+10 0.963028E+13 0.00 0.184621E+13 0.00 0.00 0.00 0.169065E+11   0.00 0.00
Minimum of Months 0.861531E+11 38651341.52 0.375296E+12 0.00 0.775674E+11 0.00 0.00 0.00 43978590.82 0.00 0.00 0.00
Maximum of Months 0.953838E+11 0.198138E+10 0.126718E+13 0.00 0.243669E+12 0.00 0.00 0.00 0.292118E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.148427E+10 0.00 0.595054E+10 0.00 0.128443E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134063E+10 0.00 0.111024E+11 0.00 0.225062E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148427E+10 0.00 0.185476E+11 0.00 0.359184E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143639E+10 0.00 0.241893E+11 0.00 0.456241E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148427E+10 0.00 0.678796E+10 0.00 0.145487E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143639E+10 0.00 0.126622E+11 0.00 0.260351E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148427E+10 0.00 0.193081E+11 0.00 0.391516E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148427E+10 0.00 0.254594E+11 0.00 0.511352E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143639E+10 0.00 0.655881E+10 0.00 0.142203E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148427E+10 0.00 0.126139E+11 0.00 0.255114E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143639E+10 0.00 0.179237E+11 0.00 0.346950E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148427E+10 0.00 0.243635E+11 0.00 0.455759E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.174761E+11 0.00 0.185467E+12 0.00 0.367766E+11 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.134063E+10 0.00 0.595054E+10 0.00 0.128443E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148427E+10 0.00 0.254594E+11 0.00 0.511352E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.141758E+11 0.00 0.419016E+11 0.00 0.927059E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128039E+11 0.00 0.923501E+11 0.00 0.189657E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.141758E+11 0.00 0.163656E+12 0.00 0.319878E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137185E+11 0.00 0.223996E+12 0.00 0.424345E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141758E+11 0.00 0.572962E+11 0.00 0.124039E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137185E+11 0.00 0.115409E+12 0.00 0.238480E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141758E+11 0.00 0.179329E+12 0.00 0.365000E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141758E+11 0.00 0.238594E+12 0.00 0.480579E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137185E+11 0.00 0.551761E+11 0.00 0.120921E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.141758E+11 0.00 0.108217E+12 0.00 0.221138E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137185E+11 0.00 0.155286E+12 0.00 0.304022E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.141758E+11 0.00 0.211583E+12 0.00 0.400923E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.166908E+12 0.00 0.164279E+13 0.00 0.328169E+12 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.128039E+11 0.00 0.419016E+11 0.00 0.927059E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141758E+11 0.00 0.238594E+12 0.00 0.480579E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.144131E+10 0.00 0.178333E+10 0.00 0.410863E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130183E+10 0.00 0.714033E+10 0.00 0.149882E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144131E+10 0.00 0.146397E+11 0.00 0.290117E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139481E+10 0.00 0.214950E+11 0.00 0.410546E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144131E+10 0.00 0.493630E+10 0.00 0.108200E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139481E+10 0.00 0.111502E+11 0.00 0.231722E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144131E+10 0.00 0.176040E+11 0.00 0.360190E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144131E+10 0.00 0.234911E+11 0.00 0.475695E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139481E+10 0.00 0.476670E+10 0.00 0.105932E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144131E+10 0.00 0.918400E+10 0.00 0.190649E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139481E+10 0.00 0.134891E+11 0.00 0.268506E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144131E+10 0.00 0.185921E+11 0.00 0.358649E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.169702E+11 0.00 0.148272E+12 0.00 0.299117E+11 0.00 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.130183E+10 0.00 0.178333E+10 0.00 0.410863E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144131E+10 0.00 0.234911E+11 0.00 0.475695E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.578591E+09 0.00 0.00 0.164538E+09 0.00 0.00 0.801242E+11 0.00 0.66
February 0.527193E+09 0.00 0.00 0.145077E+09 0.00 0.00 0.724849E+11 0.00 0.68
March 0.400720E+09 0.00 0.00 0.171904E+09 0.00 0.00 0.871887E+11 0.00 0.79
April 0.391359E+09 0.00 0.00 0.178792E+09 0.00 0.00 0.831428E+11 0.00 1.03
May 0.322344E+09 0.00 0.00 0.176867E+09 0.00 0.00 0.835090E+11 0.00 1.05
June 0.239474E+09 35493486.74 0.00 0.177731E+09 1744788.92 0.00 0.780148E+11 0.00 1.34
July 0.267277E+09 53847293.39 0.00 0.196333E+09 6464321.38 0.00 0.732375E+11 0.00 1.44
August 0.201203E+09 0.00 0.00 0.204363E+09 0.00 0.00 0.756951E+11 0.00 1.68
September 0.408811E+09 0.00 0.00 0.178820E+09 0.00 0.00 0.746394E+11 0.00 1.38
October 0.448032E+09 0.00 0.00 0.184570E+09 0.00 0.00 0.862422E+11 0.00 1.02
November 0.457411E+09 0.00 0.00 0.181204E+09 0.00 0.00 0.844986E+11 0.00 0.83
December 0.625367E+09 0.00 0.00 0.178076E+09 0.00 0.00 0.828819E+11 0.00 0.68
                   
Annual Sum or Average 0.486778E+10 89340780.14 0.00 0.213828E+10 8209110.30 0.00 0.961659E+12 0.00 1.05
Minimum of Months 0.201203E+09 0.00 0.00 0.145077E+09 0.00 0.00 0.724849E+11 0.00 0.66
Maximum of Months 0.625367E+09 53847293.39 0.00 0.204363E+09 6464321.38 0.00 0.871887E+11 0.00 1.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.231940E+10 0.00 0.00 91749618.72 0.00 0.00 0.659255E+11 0.00 0.54
February 0.232372E+10 0.00 0.00 92355901.07 0.00 0.00 0.609025E+11 0.00 0.57
March 0.270490E+10 0.00 0.00 0.114028E+09 0.00 0.00 0.742154E+11 0.00 0.67
April 0.541095E+10 0.00 0.00 0.128654E+09 0.00 0.00 0.689965E+11 0.00 0.86
May 0.434210E+10 0.00 0.00 0.109737E+09 0.00 0.00 0.617881E+11 0.00 0.77
June 0.475968E+10 93658541.43 0.00 0.116543E+09 72022657.57 0.00 0.565772E+11 0.00 0.95
July 0.771721E+10 52242206.01 0.00 0.117714E+09 23695272.89 0.00 0.474258E+11 0.00 0.98
August 0.996587E+10 0.00 0.00 0.132733E+09 0.00 0.00 0.467473E+11 0.00 1.11
September 0.495122E+10 0.00 0.00 0.105668E+09 0.00 0.00 0.473324E+11 0.00 0.87
October 0.312878E+10 0.00 0.00 0.108581E+09 0.00 0.00 0.641333E+11 0.00 0.75
November 0.288091E+10 0.00 0.00 0.107492E+09 0.00 0.00 0.668138E+11 0.00 0.65
December 0.265209E+10 0.00 0.00 0.109039E+09 0.00 0.00 0.695839E+11 0.00 0.57
                   
Annual Sum or Average 0.531568E+11 0.145901E+09 0.00 0.133429E+10 95717930.47 0.00 0.730442E+12 0.00 0.77
Minimum of Months 0.231940E+10 0.00 0.00 91749618.72 0.00 0.00 0.467473E+11 0.00 0.54
Maximum of Months 0.996587E+10 93658541.43 0.00 0.132733E+09 72022657.57 0.00 0.742154E+11 0.00 1.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103468E+12 0.00 0.00 0.546719E+09 0.00 0.00 0.492711E+12 0.00 0.48
February 0.659982E+11 0.00 0.00 0.535753E+09 0.00 0.00 0.458689E+12 0.00 0.48
March 0.326569E+11 0.00 0.00 0.749226E+09 0.00 0.00 0.577230E+12 0.00 0.54
April 0.240371E+11 0.00 0.00 0.850537E+09 0.00 0.00 0.518261E+12 0.00 0.63
May 0.311638E+11 0.00 0.00 0.873654E+09 0.00 0.00 0.514371E+12 0.00 0.65
June 0.268605E+11 0.769719E+09 0.00 0.910091E+09 0.718664E+09 0.00 0.456028E+12 0.00 0.76
July 0.333370E+11 0.386762E+09 0.00 0.866849E+09 0.520223E+09 0.00 0.357903E+12 0.00 0.72
August 0.318536E+11 0.00 0.00 0.991448E+09 0.00 0.00 0.349587E+12 0.00 0.79
September 0.353299E+11 0.00 0.00 0.841578E+09 0.00 0.00 0.385488E+12 0.00 0.72
October 0.282865E+11 0.00 0.00 0.768508E+09 0.00 0.00 0.489367E+12 0.00 0.59
November 0.550461E+11 0.00 0.00 0.620681E+09 0.00 0.00 0.468336E+12 0.00 0.50
December 0.159403E+12 0.00 0.00 0.430786E+09 0.00 0.00 0.396589E+12 0.00 0.46
                   
Annual Sum or Average 0.627441E+12 0.115648E+10 0.00 0.898583E+10 0.123889E+10 0.00 0.546456E+13 0.00 0.61
Minimum of Months 0.240371E+11 0.00 0.00 0.430786E+09 0.00 0.00 0.349587E+12 0.00 0.46
Maximum of Months 0.159403E+12 0.769719E+09 0.00 0.991448E+09 0.718664E+09 0.00 0.577230E+12 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.350107E+11 0.00 0.00 8123181.89 0.00 0.103729E+10 0.114026E+11 0.00 0.43
February 0.274571E+11 0.00 0.00 11542062.47 0.00 0.554456E+09 0.153138E+11 0.00 0.44
March 0.235605E+11 0.00 0.00 21399063.35 0.00 0.137617E+09 0.267010E+11 0.00 0.48
April 0.991394E+10 2107101.64 0.00 43911280.17 0.00 0.00 0.376942E+11 0.00 0.57
May 0.936625E+10 0.00 0.00 51855698.25 0.00 0.00 0.405703E+11 0.00 0.60
June 0.586995E+10 39093951.42 0.00 68975182.97 51603335.38 0.00 0.399769E+11 0.00 0.73
July 0.504860E+10 23993032.69 0.00 71747157.72 16885861.90 0.00 0.331372E+11 0.00 0.70
August 0.531272E+10 0.00 0.00 75062720.32 0.00 0.00 0.303961E+11 0.00 0.74
September 0.815619E+10 0.00 0.00 50240868.56 0.00 0.00 0.275960E+11 0.00 0.63
October 0.163729E+11 0.00 0.00 25408805.21 0.00 9883394.99 0.233692E+11 0.00 0.48
November 0.250616E+11 0.00 0.00 13546843.62 0.00 0.355419E+09 0.160815E+11 0.00 0.44
December 0.351322E+11 0.00 0.00 5639106.20 0.00 0.727341E+09 0.966425E+10 0.00 0.43
                   
Annual Sum or Average 0.206263E+12 65194085.75 0.00 0.447452E+09 68489197.28 0.282201E+10 0.311903E+12 0.00 0.56
Minimum of Months 0.504860E+10 0.00 0.00 5639106.20 0.00 0.00 0.966425E+10 0.00 0.43
Maximum of Months 0.351322E+11 39093951.42 0.00 75062720.32 51603335.38 0.103729E+10 0.405703E+11 0.00 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.394688E+10 0.00 0.00 2428542.96 0.00 0.00 0.214930E+10 0.00 0.38
February 0.305815E+10 0.00 0.00 3349051.43 0.00 0.00 0.264654E+10 0.00 0.41
March 0.259086E+10 0.00 0.00 5613628.66 0.00 0.00 0.468499E+10 0.00 0.51
April 0.153309E+10 0.00 0.00 8860468.93 0.00 0.00 0.669294E+10 0.00 0.78
May 0.144016E+10 0.00 0.00 8325689.52 0.00 0.00 0.615389E+10 0.00 0.72
June 0.867813E+09 16394299.16 0.00 11352217.69 9680146.65 0.00 0.691404E+10 0.00 1.00
July 0.122117E+10 10356595.13 0.00 12149259.00 3184743.86 0.00 0.596252E+10 0.00 1.06
August 0.154787E+10 0.00 0.00 13235099.89 0.00 0.00 0.559916E+10 0.00 1.15
September 0.150010E+10 0.00 0.00 7638737.20 0.00 0.00 0.446557E+10 0.00 0.82
October 0.215775E+10 0.00 0.00 5603743.62 0.00 0.00 0.444514E+10 0.00 0.59
November 0.257965E+10 0.00 0.00 4291667.86 0.00 0.00 0.348958E+10 0.00 0.46
December 0.329223E+10 0.00 0.00 3110466.31 0.00 0.00 0.261279E+10 0.00 0.37
                   
Annual Sum or Average 0.257357E+11 26750894.29 0.00 85958573.08 12864890.51 0.00 0.558165E+11 0.00 0.69
Minimum of Months 0.867813E+09 0.00 0.00 2428542.96 0.00 0.00 0.214930E+10 0.00 0.37
Maximum of Months 0.394688E+10 16394299.16 0.00 13235099.89 9680146.65 0.00 0.691404E+10 0.00 1.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.731369E+10 0.00 0.00 276077.98 0.00 0.00 0.642944E+09 0.00 0.76
February 0.586872E+10 0.00 0.00 773830.98 0.00 0.00 0.118626E+10 0.00 0.77
March 0.555021E+10 0.00 0.00 1245248.85 0.00 0.00 0.229468E+10 0.00 0.83
April 0.332268E+10 0.00 0.00 7322449.72 0.00 0.00 0.554239E+10 0.00 1.28
May 0.296004E+10 0.00 0.00 7434565.29 0.00 0.00 0.558314E+10 0.00 1.25
June 0.269738E+10 11965952.69 0.00 7960762.13 13510019.26 0.00 0.519754E+10 0.00 1.55
July 0.300409E+10 10709423.33 0.00 8219493.87 4444762.30 0.00 0.444154E+10 0.00 1.64
August 0.365649E+10 0.00 0.00 8629362.76 0.00 0.00 0.414326E+10 0.00 1.83
September 0.327168E+10 0.00 0.00 6907213.63 0.00 0.00 0.385244E+10 0.00 1.46
October 0.460355E+10 0.00 0.00 2599812.75 0.00 0.00 0.268636E+10 0.00 0.99
November 0.613628E+10 0.00 0.00 375733.66 0.00 0.00 0.918899E+09 0.00 0.81
December 0.724945E+10 0.00 0.00 83565.33 0.00 222089.60 0.262496E+09 0.00 0.73
                   
Annual Sum or Average 0.556343E+11 22675376.03 0.00 51828116.96 17954781.57 222089.60 0.367519E+11 0.00 1.16
Minimum of Months 0.269738E+10 0.00 0.00 83565.33 0.00 0.00 0.262496E+09 0.00 0.73
Maximum of Months 0.731369E+10 11965952.69 0.00 8629362.76 13510019.26 222089.60 0.558314E+10 0.00 1.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.764180E+10 0.00 0.00 4391584.03 0.00 0.00 0.386731E+10 0.00 0.72
February 0.617405E+10 0.00 0.00 5740186.80 0.00 0.00 0.460465E+10 0.00 0.77
March 0.643031E+10 0.00 0.00 4552941.27 0.00 0.00 0.439152E+10 0.00 0.75
April 0.377571E+10 0.00 0.00 11797953.12 0.00 0.00 0.914321E+10 0.00 1.24
May 0.408532E+10 0.00 0.00 8101011.48 0.00 0.00 0.664695E+10 0.00 1.02
June 0.324291E+10 18504011.30 0.00 9506218.94 17319879.82 0.00 0.657930E+10 0.00 1.25
July 0.371032E+10 11935424.55 0.00 10895271.11 7217949.53 0.00 0.581022E+10 0.00 1.38
August 0.398860E+10 0.00 0.00 14737872.07 0.00 0.00 0.659479E+10 0.00 1.68
September 0.359388E+10 0.00 0.00 13336580.82 0.00 0.00 0.717331E+10 0.00 1.50
October 0.475376E+10 0.00 0.00 8567559.01 0.00 0.00 0.699455E+10 0.00 1.08
November 0.605505E+10 0.00 0.00 4649453.57 0.00 498226.47 0.422560E+10 0.00 0.77
December 0.767183E+10 0.00 0.00 3098617.56 0.00 685103.74 0.278925E+10 0.00 0.66
                   
Annual Sum or Average 0.611235E+11 30439435.84 0.00 99375249.77 24537829.35 1183330.22 0.688207E+11 0.00 1.07
Minimum of Months 0.324291E+10 0.00 0.00 3098617.56 0.00 0.00 0.278925E+10 0.00 0.66
Maximum of Months 0.767183E+10 18504011.30 0.00 14737872.07 17319879.82 685103.74 0.914321E+10 0.00 1.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.735523E+10 0.00 0.00 1357065.45 0.00 0.00 0.224992E+10 0.00 0.93
February 0.457387E+10 0.00 0.00 4255971.81 0.00 0.00 0.439265E+10 0.00 0.99
March 0.224943E+10 0.00 0.00 8209860.58 0.00 0.00 0.824829E+10 0.00 1.12
April 0.138470E+10 0.00 0.00 17807426.62 0.00 0.00 0.111486E+11 0.00 1.85
May 0.243644E+10 0.00 0.00 9913360.57 0.00 0.00 0.771401E+10 0.00 1.50
June 0.123992E+10 44149596.68 0.00 14947967.49 4493143.46 0.00 0.894559E+10 0.00 2.04
July 0.171003E+10 20871854.14 0.00 19837288.30 2381394.64 0.00 0.829520E+10 0.00 2.28
August 0.213913E+10 0.00 0.00 23334837.79 0.00 0.00 0.832808E+10 0.00 2.55
September 0.302419E+10 0.00 0.00 7884378.14 0.00 0.00 0.511259E+10 0.00 1.69
October 0.306688E+10 0.00 0.00 6485914.63 0.00 0.00 0.605927E+10 0.00 1.26
November 0.253088E+10 0.00 0.00 6089916.38 0.00 0.00 0.644327E+10 0.00 1.04
December 0.287334E+10 0.00 0.00 5866053.58 0.00 0.00 0.658149E+10 0.00 0.93
                   
Annual Sum or Average 0.345840E+11 65021450.82 0.00 0.125990E+09 6874538.11 0.00 0.835190E+11 0.00 1.52
Minimum of Months 0.123992E+10 0.00 0.00 1357065.45 0.00 0.00 0.224992E+10 0.00 0.93
Maximum of Months 0.735523E+10 44149596.68 0.00 23334837.79 4493143.46 0.00 0.111486E+11 0.00 2.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.510894E+11 0.00 0.00 2924057.70 0.00 0.220284E+10 0.369138E+10 0.00 0.36
February 0.450346E+11 0.00 0.00 2266538.70 0.00 0.670669E+09 0.400045E+10 0.00 0.36
March 0.412736E+11 0.00 0.00 14360228.72 0.00 0.00 0.149368E+11 0.00 0.40
April 0.221008E+11 0.00 0.00 42435434.25 0.00 0.00 0.338296E+11 0.00 0.53
May 0.211663E+11 0.00 0.00 49684849.30 0.00 0.00 0.367550E+11 0.00 0.56
June 0.112657E+11 0.142121E+09 0.00 73288111.22 92340553.36 0.00 0.461821E+11 0.00 0.76
July 0.114379E+11 0.125991E+09 0.00 75315579.46 27287666.74 0.00 0.376958E+11 0.00 0.75
August 0.123160E+11 0.00 0.00 78259423.45 0.00 0.00 0.337200E+11 0.00 0.78
September 0.203088E+11 0.00 0.00 47654395.52 0.00 0.00 0.254244E+11 0.00 0.64
October 0.302623E+11 0.00 0.00 20697670.19 0.00 0.00 0.179687E+11 0.00 0.44
November 0.411987E+11 0.00 0.00 4873979.95 0.00 0.110642E+10 0.607641E+10 0.00 0.37
December 0.523842E+11 0.00 0.00 0.00 0.00 0.389878E+10 0.00 0.00 0.37
                   
Annual Sum or Average 0.359838E+12 0.268112E+09 0.00 0.411760E+09 0.119628E+09 0.787871E+10 0.260281E+12 0.00 0.53
Minimum of Months 0.112657E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.523842E+11 0.142121E+09 0.00 78259423.45 92340553.36 0.389878E+10 0.461821E+11 0.00 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.859472E+11 0.00 0.00 0.00 0.00 0.453449E+10 0.00 0.00 0.88
February 0.770058E+11 0.00 0.00 715614.55 0.00 0.887534E+09 0.107994E+10 0.00 0.88
March 0.855308E+11 0.00 0.00 216928.70 0.00 67407100.55 0.947115E+09 0.00 0.94
April 0.353057E+11 0.00 0.00 57858597.96 0.00 0.00 0.456796E+11 0.00 1.18
May 0.393306E+11 0.00 0.00 54766831.97 0.00 0.00 0.428276E+11 0.00 1.22
June 0.303415E+11 0.122312E+09 0.00 64404190.03 0.146716E+09 0.00 0.424946E+11 0.00 1.46
July 0.245565E+11 0.160203E+09 0.00 68970385.56 43356180.90 0.00 0.377180E+11 0.00 1.44
August 0.274204E+11 0.00 0.00 72591769.09 0.00 0.00 0.348696E+11 0.00 1.57
September 0.346777E+11 0.00 0.00 53595696.39 0.00 0.00 0.313485E+11 0.00 1.39
October 0.603651E+11 0.00 0.00 11546192.73 0.00 9148184.53 0.122706E+11 0.00 1.00
November 0.745755E+11 0.00 0.00 26935.86 0.00 0.183501E+10 0.149699E+09 0.00 0.89
December 0.785815E+11 0.00 0.00 0.00 0.00 0.108289E+11 0.00 0.00 0.90
                   
Annual Sum or Average 0.653638E+12 0.282515E+09 0.00 0.384693E+09 0.190072E+09 0.181625E+11 0.249385E+12 0.00 1.15
Minimum of Months 0.245565E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.88
Maximum of Months 0.859472E+11 0.160203E+09 0.00 72591769.09 0.146716E+09 0.108289E+11 0.456796E+11 0.00 1.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.895265E+11 0.00 0.00 36658632.93 0.00 0.200961E+10 0.350107E+11 0.00 0.80
February 0.760908E+11 0.00 0.00 47983504.60 0.00 70667963.35 0.389141E+11 0.00 0.84
March 0.862466E+11 0.00 0.00 23899399.66 0.00 16470710.21 0.262040E+11 0.00 0.79
April 0.443536E+11 0.00 0.00 94260961.61 0.00 0.00 0.715829E+11 0.00 1.12
May 0.526823E+11 0.00 0.00 59513912.78 0.00 0.00 0.496634E+11 0.00 0.98
June 0.393367E+11 0.178603E+09 0.00 64524812.23 0.184924E+09 0.00 0.475864E+11 0.00 1.13
July 0.326106E+11 0.170324E+09 0.00 79219279.73 76746744.69 0.00 0.436741E+11 0.00 1.16
August 0.319109E+11 0.00 0.00 0.114683E+09 0.00 0.00 0.507052E+11 0.00 1.40
September 0.374679E+11 0.00 0.00 0.131371E+09 0.00 0.00 0.649629E+11 0.00 1.48
October 0.578061E+11 0.00 0.00 74918516.85 0.00 0.00 0.578032E+11 0.00 1.08
November 0.768494E+11 0.00 0.00 30622148.88 0.00 0.114385E+10 0.269428E+11 0.00 0.80
December 0.952949E+11 0.00 0.00 16092716.49 0.00 0.674527E+10 0.156482E+11 0.00 0.77
                   
Annual Sum or Average 0.720176E+12 0.348927E+09 0.00 0.773748E+09 0.261671E+09 0.998587E+10 0.528698E+12 0.00 1.03
Minimum of Months 0.319109E+11 0.00 0.00 16092716.49 0.00 0.00 0.156482E+11 0.00 0.77
Maximum of Months 0.952949E+11 0.178603E+09 0.00 0.131371E+09 0.184924E+09 0.674527E+10 0.715829E+11 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.898030E+11 0.00 0.00 965488.57 0.00 0.218985E+10 0.177290E+10 0.00 0.92
February 0.762673E+11 0.00 0.00 6435276.02 0.00 0.160048E+09 0.627544E+10 0.00 0.92
March 0.837507E+11 0.00 0.00 4610076.80 0.00 4781731.91 0.656794E+10 0.00 0.98
April 0.424090E+11 0.00 0.00 43000708.92 0.00 0.00 0.401800E+11 0.00 1.22
May 0.431849E+11 0.00 0.00 49849822.84 0.00 0.00 0.418055E+11 0.00 1.27
June 0.276814E+11 0.372660E+09 0.00 66224048.32 60187204.72 0.00 0.481639E+11 0.00 1.55
July 0.218677E+11 0.189229E+09 0.00 82082920.11 55533693.11 0.00 0.433762E+11 0.00 1.55
August 0.256620E+11 0.00 0.00 67420355.94 0.00 0.00 0.366120E+11 0.00 1.60
September 0.425837E+11 0.00 0.00 34238650.22 0.00 0.00 0.235451E+11 0.00 1.41
October 0.661298E+11 0.00 0.00 10244949.46 0.00 0.00 0.100864E+11 0.00 1.06
November 0.757431E+11 0.00 0.00 1394249.44 0.00 0.153299E+10 0.206362E+10 0.00 0.93
December 0.883469E+11 0.00 0.00 0.00 0.00 0.427885E+10 0.00 0.00 0.94
                   
Annual Sum or Average 0.683430E+12 0.561888E+09 0.00 0.366467E+09 0.115721E+09 0.816652E+10 0.260449E+12 0.00 1.20
Minimum of Months 0.218677E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.92
Maximum of Months 0.898030E+11 0.372660E+09 0.00 82082920.11 60187204.72 0.427885E+10 0.481639E+11 0.00 1.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.432538E+10 0.00 0.00 0.00 0.00 0.264964E+10 0.00 0.00 0.50
February 0.455308E+10 0.00 0.00 0.00 0.00 0.164767E+10 0.00 0.00 0.50
March 0.574706E+10 0.00 0.00 92828.79 0.00 0.831401E+09 0.242594E+09 0.00 0.52
April 0.315238E+10 0.00 0.00 2783515.93 241790.44 0.119404E+09 0.249745E+10 0.00 0.55
May 0.302249E+10 0.00 0.00 3623262.74 0.00 49099704.37 0.292381E+10 0.00 0.58
June 0.166726E+10 6837228.88 0.00 6444724.74 7785638.44 0.00 0.417438E+10 0.00 0.77
July 0.136202E+10 3784820.61 0.00 7218267.90 3593643.58 0.00 0.376522E+10 0.00 0.77
August 0.156717E+10 0.00 0.00 6786642.60 0.00 0.00 0.315162E+10 0.00 0.79
September 0.244137E+10 0.00 0.00 3487183.84 0.00 3144953.15 0.202727E+10 0.00 0.63
October 0.417844E+10 0.00 0.00 461372.98 0.00 0.488627E+09 0.553430E+09 0.00 0.50
November 0.448353E+10 0.00 0.00 1349.44 0.00 0.139016E+10 18949937.59 0.00 0.50
December 0.366485E+10 0.00 0.00 0.00 0.00 0.315138E+10 0.00 0.00 0.51
                   
Annual Sum or Average 0.401650E+11 10622049.49 0.00 30899148.97 11621072.46 0.103305E+11 0.193547E+11 0.00 0.59
Minimum of Months 0.136202E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
Maximum of Months 0.574706E+10 6837228.88 0.00 7218267.90 7785638.44 0.315138E+10 0.417438E+10 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.645988E+10 0.00 0.00 0.00 0.00 0.310412E+10 0.00 0.00 1.06
February 0.659480E+10 0.00 0.00 0.00 0.00 0.193942E+10 0.00 0.00 1.06
March 0.826400E+10 0.00 0.00 0.00 0.00 0.113763E+10 0.00 0.00 1.11
April 0.359979E+10 659435.27 0.00 4721511.21 0.00 38367063.96 0.427869E+10 0.00 1.18
May 0.413648E+10 0.00 0.00 4744114.76 0.00 12820774.14 0.395824E+10 0.00 1.22
June 0.285762E+10 5441492.98 0.00 6516009.83 10735244.13 0.00 0.427225E+10 0.00 1.44
July 0.209493E+10 7904287.36 0.00 7230810.61 2211245.03 0.00 0.398298E+10 0.00 1.40
August 0.238353E+10 0.00 0.00 7208248.24 0.00 0.00 0.358607E+10 0.00 1.52
September 0.311124E+10 0.00 0.00 4808430.41 0.00 919986.97 0.287893E+10 0.00 1.30
October 0.572858E+10 0.00 0.00 591754.46 0.00 0.630477E+09 0.818432E+09 0.00 1.07
November 0.641313E+10 0.00 0.00 0.00 0.00 0.168824E+10 0.00 0.00 1.05
December 0.522385E+10 0.00 0.00 0.00 0.00 0.410592E+10 0.00 0.00 1.07
                   
Annual Sum or Average 0.568678E+11 14005215.61 0.00 35820879.52 12946489.16 0.126579E+11 0.237756E+11 0.00 1.21
Minimum of Months 0.209493E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.05
Maximum of Months 0.826400E+10 7904287.36 0.00 7230810.61 10735244.13 0.410592E+10 0.427869E+10 0.00 1.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.860069E+10 0.00 0.00 1623021.61 0.00 0.289175E+10 0.220117E+10 0.00 0.97
February 0.800754E+10 0.00 0.00 2670942.55 0.00 0.179570E+10 0.297220E+10 0.00 1.03
March 0.104507E+11 0.00 0.00 854915.18 0.00 0.134036E+10 0.118506E+10 0.00 0.99
April 0.521991E+10 0.00 0.00 8165383.57 455766.85 0.155058E+09 0.662334E+10 0.00 1.16
May 0.645986E+10 0.00 0.00 4912139.02 0.00 0.115721E+09 0.430449E+10 0.00 1.05
June 0.465355E+10 8171468.93 0.00 5909678.63 14675666.65 463888.93 0.439518E+10 0.00 1.17
July 0.350868E+10 4941611.69 0.00 7703378.43 7073447.68 0.00 0.446488E+10 0.00 1.19
August 0.353019E+10 0.00 0.00 10573988.56 0.00 0.00 0.500757E+10 0.00 1.42
September 0.392719E+10 0.00 0.00 11526061.75 0.00 241981.94 0.611774E+10 0.00 1.44
October 0.665581E+10 0.00 0.00 5340186.61 0.00 0.567524E+09 0.438418E+10 0.00 1.13
November 0.841035E+10 0.00 0.00 1470017.18 0.00 0.151993E+10 0.157343E+10 0.00 0.97
December 0.771443E+10 0.00 0.00 717890.37 0.00 0.427013E+10 0.979990E+09 0.00 0.96
                   
Annual Sum or Average 0.771388E+11 13113080.62 0.00 61467603.47 22204881.18 0.126569E+11 0.442092E+11 0.00 1.12
Minimum of Months 0.350868E+10 0.00 0.00 717890.37 0.00 0.00 0.979990E+09 0.00 0.96
Maximum of Months 0.104507E+11 8171468.93 0.00 11526061.75 14675666.65 0.427013E+10 0.662334E+10 0.00 1.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.809010E+10 0.00 0.00 25257.30 0.00 0.250054E+10 55167120.63 0.00 1.18
February 0.775577E+10 0.00 0.00 344181.36 0.00 0.125617E+10 0.515120E+09 0.00 1.19
March 0.941814E+10 0.00 0.00 263124.49 0.00 0.684361E+09 0.393376E+09 0.00 1.24
April 0.540894E+10 0.00 0.00 3841801.23 371190.82 5623695.39 0.340597E+10 0.00 1.32
May 0.538576E+10 0.00 0.00 4496355.50 0.00 51926924.50 0.360990E+10 0.00 1.36
June 0.337218E+10 21568401.34 0.00 6513440.33 3839260.99 0.00 0.455015E+10 0.00 1.61
July 0.245676E+10 6601703.41 0.00 8133980.60 4488626.70 0.00 0.436749E+10 0.00 1.59
August 0.300043E+10 0.00 0.00 6146757.92 0.00 0.00 0.339380E+10 0.00 1.63
September 0.458635E+10 0.00 0.00 3017611.96 0.00 580326.59 0.197631E+10 0.00 1.43
October 0.704085E+10 0.00 0.00 765844.01 0.00 0.324927E+09 0.724685E+09 0.00 1.21
November 0.764529E+10 0.00 0.00 47353.22 0.00 0.125811E+10 0.114538E+09 0.00 1.17
December 0.698171E+10 0.00 0.00 0.00 0.00 0.340323E+10 0.00 0.00 1.19
                   
Annual Sum or Average 0.711423E+11 28170104.74 0.00 33595707.92 8699078.51 0.948547E+10 0.231065E+11 0.00 1.34
Minimum of Months 0.245676E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.17
Maximum of Months 0.941814E+10 21568401.34 0.00 8133980.60 4488626.70 0.340323E+10 0.455015E+10 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2020-06-03 20:04:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 14780110.78 0.00 0.00 0.213194E+09 0.00 0.00 0.143276E+11 0.00 0.32
February 1324318.56 0.00 0.00 0.408151E+09 0.00 0.00 0.122938E+11 0.00 0.32
March 0.00 0.00 0.00 0.668205E+09 0.00 0.00 0.137617E+11 0.00 0.34
April 0.00 0.00 0.00 0.844671E+09 0.00 0.00 0.996086E+10 0.00 0.32
May 0.00 0.00 0.00 0.212645E+09 0.00 0.00 0.941812E+10 0.00 0.33
June 0.00 10169751.93 0.00 0.412246E+09 0.00 0.00 0.606957E+10 0.00 0.34
July 0.00 2049930.88 0.00 0.594460E+09 0.00 0.00 0.412208E+10 0.00 0.31
August 0.00 0.00 0.00 0.890040E+09 0.00 0.00 0.383545E+10 0.00 0.34
September 0.00 0.00 0.00 0.204614E+09 0.00 0.00 0.575012E+10 0.00 0.32
October 0.00 0.00 0.00 0.414032E+09 0.00 0.00 0.902455E+10 0.00 0.32
November 0.00 0.00 0.00 0.603276E+09 0.00 0.00 0.110412E+11 0.00 0.32
December 0.00 0.00 0.00 0.830804E+09 0.00 0.00 0.135600E+11 0.00 0.31
                   
Annual Sum or Average 16104429.34 12219682.81 0.00 0.629634E+10 0.00 0.00 0.113165E+12 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.204614E+09 0.00 0.00 0.383545E+10 0.00 0.31
Maximum of Months 14780110.78 10169751.93 0.00 0.890040E+09 0.00 0.00 0.143276E+11 0.00 0.34