Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:00
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 20:00:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32287.10 | 697.04 | 697.04 |
Net Site Energy | 32287.10 | 697.04 | 697.04 |
Total Source Energy | 98117.35 | 2118.23 | 2118.23 |
Net Source Energy | 98117.35 | 2118.23 | 2118.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1393.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3757.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 883.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2044.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2220.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 647.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1192.56 | 0.00 | 0.00 | 0.00 | 0.00 | 5951.13 |
Humidification | 25.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
Heat Recovery | 22.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 592.14 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30301.55 | 1985.54 | 0.00 | 0.00 | 0.00 | 8240.82 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 1393.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1260.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2496.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 883.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2220.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 647.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 245.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 946.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5951.13 | |
Humidification | General | 25.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
Heat Recovery | General | 22.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 592.14 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 169.33 | 42.87 | 0.00 | 0.00 | 0.00 | 0.18 |
Other | 373.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 654.17 | 42.87 | 0.00 | 0.00 | 0.00 | 0.18 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 169.33 | 42.87 | 0.00 | 0.00 | 0.00 | 0.18 |
Other | 373.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 654.17 | 42.87 | 0.00 | 0.00 | 0.00 | 0.18 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30301.555 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30301.555 | 100.00 |
Total On-Site and Utility Electric Sources | 30301.555 | 100.00 |
Total Electricity End Uses | 30301.555 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 794.83 | 26.56 |
Air to Air Heat Recovery for Heating | 2198.05 | 73.44 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2992.88 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8240.82 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8240.82 | 100.00 |
Total Water End Uses | 8240.82 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 31.33 |
Time Setpoint Not Met During Occupied Cooling | 234.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2483.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:00 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.6875 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.6875 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:09 | 02-JAN-07:10 | - | - | - | 24-AUG-16:00 |
Heating | 0.00 | 2550782.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 519650.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 92996.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147862.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 75484.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95698.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2110.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2101131.46 | 2558928.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 2550782.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 350944.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 147862.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 75484.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 46449.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2110.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1510.45 | 0.00 | 0.00 | 0.00 |
Cooling | 11899.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13600.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2798.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6473.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7031.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2052.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3776.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 81.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 71.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 641.88 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 95965.02 | 2152.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 32.61 | 0.00 | 0.00 | 0.00 |
Cooling | 256.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.86 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2071.77 | 46.47 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 32.61 | 0.00 | 0.00 | 0.00 |
Cooling | 256.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.86 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2071.77 | 46.47 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.78 |
DATACENTER BOT DIRECT AIR | 0.469785 |
DATACENTER MID DIRECT AIR | 4.48 |
DATACENTER TOP DIRECT AIR | 0.457733 |
DATACENTER BASEMENT DIRECT AIR | 21.27 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.98 | 0.317869 | 0.300000 | 1.80 | 0.847651 | 0.500000 | 0.001199 | 0.000399 | 1.80 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.35 | 0.337521 | 0.300000 | 16.91 | 0.900055 | 0.500000 | 0.001129 | 0.009030 | 16.91 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.74 | 0.331499 | 0.300000 | 1.72 | 0.883997 | 0.500000 | 0.001149 | 0.001939 | 2.61 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.937017 | 0.254873 | 0.300000 | 0.281105 | 0.679662 | 0.500000 | 0.001495 | 0.000208 | 0.281105 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.07 | 0.144003 | 0.300000 | 0.320628 | 0.384009 | 0.500000 | 0.002646 | 0.000175 | 0.320628 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.06 | 0.224537 | 0.300000 | 0.319091 | 0.598764 | 0.500000 | 0.001697 | 0.000267 | 0.359843 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.31 | 0.117613 | 0.300000 | 0.392572 | 0.313635 | 0.500000 | 0.003239 | 0.000158 | 0.392572 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.81 | 0.271219 | 0.300000 | 2.64 | 0.723249 | 0.500000 | 0.001405 | 0.004216 | 5.69 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.14 | 0.138160 | 0.300000 | 3.34 | 0.368428 | 0.500000 | 0.002758 | 0.002784 | 3.76 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.03 | 0.238118 | 0.300000 | 3.01 | 0.634983 | 0.500000 | 0.001600 | 0.004200 | 5.67 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.42 | 0.134819 | 0.300000 | 3.42 | 0.359517 | 0.500000 | 0.002826 | 0.002653 | 3.58 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.994510 | 0.240139 | 0.300000 | 0.298353 | 0.640371 | 0.500000 | 0.001587 | 0.000554 | 0.747766 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.13 | 0.135759 | 0.300000 | 0.340100 | 0.362023 | 0.500000 | 0.002806 | 0.000363 | 0.490257 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.13 | 0.210572 | 0.300000 | 0.340253 | 0.561525 | 0.500000 | 0.001809 | 0.000551 | 0.744258 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.125049 | 0.300000 | 0.369226 | 0.333465 | 0.500000 | 0.003047 | 0.000353 | 0.476980 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18066.12 | 0.000399 | 314.45 |
CORE_MID VAV BOX REHEAT COIL | 408702.12 | 0.009030 | 7901.33 |
CORE_TOP VAV BOX REHEAT COIL | 87760.99 | 0.001939 | 1832.02 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9435.15 | 0.000208 | 196.92 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7924.75 | 0.000175 | 153.82 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12077.08 | 0.000267 | 252.05 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7140.22 | 0.000158 | 132.52 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 190837.07 | 0.004216 | 3981.37 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 125997.55 | 0.002784 | 2628.60 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 190103.44 | 0.004200 | 3966.07 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 120080.61 | 0.002653 | 2505.23 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25053.49 | 0.000554 | 522.60 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16425.23 | 0.000363 | 342.61 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24936.15 | 0.000551 | 520.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15981.02 | 0.000353 | 333.35 |
CAV_BAS_HEATC | 295027.98 | 0.006518 | 5394.63 |
VAV_BOT WITH REHEAT_HEATC | 78412.18 | 0.001732 | 1081.69 |
VAV_MID WITH REHEAT_HEATC | 773810.97 | 0.017096 | 10578.63 |
VAV_TOP WITH REHEAT_HEATC | 81119.11 | 0.001792 | 1110.04 |
DATACENTER_EXTRAWATERHEATC | 1033354.38 | 0.022831 | 19208.91 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.78 | 5.78 | 5.78 | 5.78 | 5.78 | 5.78 | 1.00 | 1.00 | 5.78 |
VAV_BOT WITH REHEAT | 5.18 | 3.11 | 10.36 | 3.11 | 9.72 | 9.72 | 0.300000 | 0.319922 | 9.72 |
VAV_MID WITH REHEAT | 48.87 | 29.32 | 97.74 | 29.48 | 90.75 | 90.75 | 0.300000 | 0.324861 | 90.75 |
VAV_TOP WITH REHEAT | 5.12 | 3.07 | 10.23 | 5.07 | 9.57 | 9.57 | 0.300000 | 0.530003 | 9.57 |
AIRLOOP DATACENTER BASEMENT | 21.27 | 21.27 | 21.27 | 21.27 | 21.27 | 21.27 | 1.00 | 1.00 | 21.27 |
AIRLOOP DATACENTER BOT | 0.469785 | 0.469785 | 0.469785 | 0.469785 | 0.469785 | 0.469785 | 1.00 | 1.00 | 0.469785 |
AIRLOOP DATACENTER MID | 4.48 | 4.48 | 4.48 | 4.48 | 4.48 | 4.48 | 1.00 | 1.00 | 4.48 |
AIRLOOP DATACENTER TOP | 0.457733 | 0.457733 | 0.457733 | 0.457733 | 0.457733 | 0.457733 | 1.00 | 1.00 | 0.457733 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.78 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.72 | 2.74 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 90.75 | 28.72 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.57 | 2.86 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.27 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.469785 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.48 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.457733 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 121077.90 | 0.005151 | 5.78 | 0.010007 | 24.59 | 6.67 | 11.30 | 0.008281 |
VAV_BOT WITH REHEAT_COOLC | 243930.05 | 0.010377 | 9.72 | 0.010471 | 26.46 | 6.67 | 11.30 | 0.008281 |
VAV_MID WITH REHEAT_COOLC | 2415272.12 | 0.102751 | 90.75 | 0.010789 | 26.89 | 6.67 | 11.30 | 0.008281 |
VAV_TOP WITH REHEAT_COOLC | 238488.76 | 0.010146 | 9.57 | 0.010435 | 26.40 | 6.67 | 11.30 | 0.008281 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.78 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.005151 | 0.000092 |
CAV_BAS_HEATC_CONTROLLER | 0.006518 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010377 | 0.000046 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001732 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.102751 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.017096 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010146 | 0.000047 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001792 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022831 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.72 |
VAV_MID WITH REHEAT FAN | 90.75 |
VAV_TOP WITH REHEAT FAN | 9.57 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 28.72 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.27 | 428255.44 | 309426.71 | 0.010488 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.469785 | 9352.23 | 6793.97 | 0.000229 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.48 | 89292.21 | 64815.87 | 0.002187 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.457733 | 9122.39 | 6623.04 | 0.000223 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.27 | 21.27 | 21.27 | 21.27 | 428255.44 | 428255.44 | 20748.52 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.469785 | 0.469785 | 0.469785 | 0.469785 | 9352.23 | 9352.23 | 958.50 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.48 | 4.48 | 4.48 | 4.48 | 89292.21 | 89292.21 | 9584.96 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.457733 | 0.457733 | 0.457733 | 0.457733 | 9122.39 | 9122.39 | 958.50 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.27 |
DATACENTER BOT SUPPLY FAN | 0.469785 |
DATACENTER MID SUPPLY FAN | 4.48 |
DATACENTER TOP SUPPLY FAN | 0.457733 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.27 | 428255.44 | 0.010488 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.469785 | 9352.23 | 0.000229 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.48 | 89292.21 | 0.002187 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.457733 | 9122.39 | 0.000223 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 20748.52 | |
DATACENTER_EXTRAELECHEATC | 428255.44 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 958.50 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 9584.96 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 958.50 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000172 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.128425 | 30758.98 |
HEATSYS1 PUMP | 0.077820 | 19881.94 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.128425 | 15.41 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.077820 | 9.34 |
COOLSYS1_SUPPLY | 0.128425 | 15.41 |
SINGLE WATER PLANT LOOP | 0.013127 | 1.58 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.128425 | 0.128425 | 539065.86 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 PUMP | 0.128425 | 10252.99 |
PLANT CIRC PUMP | 0.013127 | 3348.08 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3522245.59 | 1761122.79 | 0.077820 |
DUMMY BOILER | 540726.07 | 93894.07 | 0.013127 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.128425 | 0.064485 | 1519508.53 | 1526701.81 | 0.075840 |
COOLSYS1 CHILLER2 | 0.128425 | 0.064485 | 1519508.53 | 1526701.81 | 0.075840 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013127 | 139666.47 | 59963.22 | 69833.23 | 7879.72 | 21481.95 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.151679 | 18.20 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.151679 | 38750.35 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 61.15 | 1449097.60 | 12.23 | 181137.20 |
TOWERWATERSYS COOLTOWER 2 | 61.15 | 1449097.60 | 12.23 | 181137.20 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.062778 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.688 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.529 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 9.688 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 26925.749 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26925.749 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 7591.909 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7591.909 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
51 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
52 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
53 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
54 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
55 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
56 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
57 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
58 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
59 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 80198.60981 | 80198.60981 | 5.77741 | 5.77741 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 83071.91391 | 83071.91391 | 5.98373 | 5.98373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 782549.56340 | 782549.56340 | 56.35341 | 56.35341 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 238559.44949 | 238559.44949 | 10.05220 | 10.77757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 79666.51315 | 79666.51315 | 5.73771 | 5.73771 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 61465.73460 | 61465.73460 | 2.61280 | 2.61280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12998.89361 | 12998.89361 | 0.93702 | 0.93702 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6613.46109 | 6613.46109 | 0.28078 | 0.28078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14808.06110 | 14808.06110 | 1.06876 | 1.06876 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4704.99994 | 4704.99994 | 0.19991 | 0.19991 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14632.41620 | 14632.41620 | 1.06364 | 1.06364 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.40969E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 8461.47580 | 8461.47580 | 0.35984 | 0.35984 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18002.11060 | 18002.11060 | 1.30857 | 1.30857 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3205.73124 | 3205.73124 | 0.13578 | 0.13578 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 122174.14225 | 122174.14225 | 8.80547 | 8.80547 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 133596.90386 | 133596.90386 | 5.69282 | 5.69282 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 153245.05260 | 153245.05260 | 11.13960 | 11.13960 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.40969E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 88203.12914 | 88203.12914 | 3.75882 | 3.75882 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 137975.39276 | 137975.39276 | 10.02970 | 10.02970 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.40969E-002 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 133084.09786 | 133084.09786 | 5.67088 | 5.67088 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 157043.03246 | 157043.03246 | 11.41569 | 11.41569 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 84066.84045 | 84066.84045 | 3.58195 | 3.58195 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13681.04327 | 13681.04327 | 0.99451 | 0.99451 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17533.84555 | 17533.84555 | 0.74777 | 0.74777 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15595.49940 | 15595.49940 | 1.13367 | 1.13367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11495.18183 | 11495.18183 | 0.49026 | 0.49026 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15602.42546 | 15602.42546 | 1.13418 | 1.13418 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 17451.81210 | 17451.81210 | 0.74426 | 0.74426 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16931.10057 | 16931.10057 | 1.23075 | 1.23075 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11184.61118 | 11184.61118 | 0.47698 | 0.47698 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8194.84013 | 8194.84013 | 0.46978 | 0.46978 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.40969E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78128.48903 | 78128.48903 | 4.47886 | 4.47886 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.40969E-002 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7984.61496 | 7984.61496 | 0.45773 | 0.45773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.40969E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371023.55237 | 371023.55237 | 21.26962 | 21.26962 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 24.93433 | 1.40969E-002 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 82406.03 | 5.77741 | 5.77741 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 73587.49 | 1.20008 | 1.20008 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 147378.70 | 9.71649 | 9.71649 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 58380.54 | 2.05407 | 2.05407 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1360188.35 | 90.75289 | 90.75289 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 815812.62 | 29.48204 | 29.48204 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 156919.70 | 9.56986 | 9.56986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 81148.03 | 5.07206 | 5.07206 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366800.12 | 21.26962 | 21.26962 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20748.52 | 0.33837 | 0.33837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8116.97 | 0.46978 | 0.46978 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.50 | 1.56314E-002 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77408.88 | 4.47886 | 4.47886 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9584.96 | 0.15631 | 0.15631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7913.50 | 0.45773 | 0.45773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.50 | 1.56314E-002 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.77741 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.98373 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31787 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79512 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84765 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19861E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.99149E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79512 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18066.12064 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.99149E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.44548 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.35341 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33752 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.90602 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90005 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12882E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.02977E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.90602 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 408702.12224 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.02977E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7901.32501 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.73771 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33150 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72131 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88400 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14933E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93897E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.61280 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 87760.98730 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93897E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1832.02287 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93702 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25487 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28111 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67966 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49486E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08458E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28111 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9435.14584 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08458E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 196.91665 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06876 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32063 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38401 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64577E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75088E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32063 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7924.74838 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75088E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.82428 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06364 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22454 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31909 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59876 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69683E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.66828E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35984 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12077.08419 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66828E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.04998 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30857 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11761 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39257 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31363 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23944E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57754E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39257 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7140.21524 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57754E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 132.51743 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.80547 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27122 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.64164 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72325 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40477E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21631E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.69282 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 190837.07008 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21631E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3981.36647 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.13960 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13816 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.34188 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36843 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.75767E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78376E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.75882 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 125997.55202 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78376E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2628.59740 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.02970 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23812 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.00891 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63498 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60004E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.20010E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.67088 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 190103.44046 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20010E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3966.07182 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.41569 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13482 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.42471 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35952 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82601E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65303E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.58195 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120080.60575 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65303E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2505.22989 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99451 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24014 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29835 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64037 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58658E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.53526E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74777 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25053.48770 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.53526E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 522.59740 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13367 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13576 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34010 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36202 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80645E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.62895E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49026 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16425.22866 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.62895E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 342.61473 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13418 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21057 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34025 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56152 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80936E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.50934E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74426 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24936.14531 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.50934E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 520.15102 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23075 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12505 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36923 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33347 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04680E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53081E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47698 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15981.02106 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53081E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 333.35284 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46978 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.47886 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45773 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.26962 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.77741 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.77741 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.77741 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.77741 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.77741 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.77741 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.18086 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.10852 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.36172 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.10852 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.71649 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.71649 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31992 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.87194 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.32316 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 97.74387 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.48204 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 90.75289 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 90.75289 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32486 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.11541 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.06925 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.23082 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.07206 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.56986 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.56986 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.26962 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.26962 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.26962 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.26962 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.26962 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.26962 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46978 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46978 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46978 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46978 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46978 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46978 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.47886 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.47886 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.47886 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.47886 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.47886 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.47886 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45773 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45773 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45773 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45773 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45773 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45773 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.77741 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.71649 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 90.75289 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.56986 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.26962 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46978 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.47886 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45773 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.77741 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 121077.90364 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 5.15093E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.77741 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.00075E-002 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.59345 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.29892 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 295027.98343 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.51828E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 5394.62859 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.77741 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.15093E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.24474E-005 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.51828E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.71649 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.73720 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 243930.04630 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.03773E-002 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.71649 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.04711E-002 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.46219 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.30018 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 78412.18187 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.73242E-003 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 1081.69332 |
318 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.71649 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03773E-002 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.58875E-005 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73242E-003 |
322 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 90.75289 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 28.71625 |
324 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 28.71625 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2415272.11757 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 0.10275 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 90.75289 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.07886E-002 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.88576 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.30104 |
332 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
333 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 773810.96813 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.70964E-002 |
335 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 10578.62543 |
336 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 90.75289 |
337 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10275 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.63440E-006 |
339 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.70964E-002 |
340 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.56986 |
341 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.85707 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 238488.76201 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.01459E-002 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.56986 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.04349E-002 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.40322 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.30008 |
349 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
350 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 81119.10923 |
351 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.79223E-003 |
352 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 1110.03929 |
353 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.56986 |
354 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.01459E-002 |
355 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.69344E-005 |
356 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.79223E-003 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.26962 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.26962 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 428255.43502 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 309426.71113 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04879E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.26962 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.26962 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.26962 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.26962 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 428255.43502 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 428255.43502 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20748.52325 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.26962 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.26962 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 428255.43502 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04879E-002 |
375 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 20748.52325 |
376 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.72456E-004 |
377 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 428255.43502 |
381 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
382 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1033354.37700 |
383 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.28307E-002 |
384 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19208.91138 |
385 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.28307E-002 |
386 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.08575E-005 |
387 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46978 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46978 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9352.22925 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6793.97061 |
391 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.29035E-004 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46978 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46978 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46978 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46978 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9352.22925 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9352.22925 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.49582 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
400 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46978 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46978 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9352.22925 |
403 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.29035E-004 |
404 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 958.49582 |
405 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.47886 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.47886 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 89292.20786 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 64815.86518 |
409 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.18676E-003 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.47886 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.47886 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.47886 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.47886 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89292.20786 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89292.20786 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9584.95818 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
418 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.47886 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.47886 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 89292.20786 |
421 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.18676E-003 |
422 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 9584.95818 |
423 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45773 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45773 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 9122.39330 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6623.04142 |
427 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.23407E-004 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45773 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45773 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45773 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45773 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9122.39330 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9122.39330 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.49582 |
435 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
436 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45773 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45773 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 9122.39330 |
439 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.23407E-004 |
440 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 958.49582 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12843 |
442 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 30758.98411 |
443 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12843 |
444 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.41105 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12843 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12843 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 539065.86241 |
448 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
449 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
450 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
451 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
452 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
453 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
454 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.78197E-002 |
455 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 9.33837 |
456 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.78197E-002 |
457 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 19881.93864 |
458 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3522245.59453 |
459 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1761122.79500 |
460 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.78197E-002 |
461 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12843 |
462 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.41105 |
463 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12843 |
464 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 10252.99470 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12843 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.44850E-002 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1519508.52708 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1526701.81000 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.58396E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12843 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.44850E-002 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1519508.52708 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1526701.81000 |
474 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.58396E-002 |
475 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31272E-002 |
476 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.57526 |
477 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31272E-002 |
478 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3348.07991 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31272E-002 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59963.21547 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
484 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21481.95023 |
485 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 540726.07247 |
486 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
487 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31272E-002 |
488 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15168 |
489 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.20149 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15168 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 38750.34600 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 61.15459 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1449097.59867 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.23092 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 181137.19983 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 61.15459 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1449097.59867 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.23092 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 181137.19983 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 6.27780E-002 |
501 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 6.27780E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17139.46 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 387950.73 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 83265.60 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8951.86 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7522.27 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11458.47 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6779.87 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 181062.14 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 119543.80 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 180366.09 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 113929.91 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23770.23 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15583.91 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23658.89 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15162.46 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 230759.49 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 56385.87 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 548872.81 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 57624.06 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 828547.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 158212.86 | 107857.69 | 50355.16 | 0.68 | 20054.00 | 203.40 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 283942.02 | 189387.55 | 94554.48 | 0.67 | 35646.73 | 361.55 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2699158.07 | 1790043.75 | 909114.32 | 0.66 | 337409.03 | 3422.19 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 279043.47 | 186256.19 | 92787.28 | 0.67 | 35060.33 | 355.60 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.89 | 23.50 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.89 | 23.50 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.5300068495E-002 | 9.2870603305E-002 | Pass | Pass | 9.2412661060E-002 | 0.5698192431 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.3249959948E-003 | 3.2373442937E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.4710744992E-002 | 1.8663252698E-002 | Pass | Pass | 0.4850208122 | 0.4921731697 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.4611866089E-002 | 8.0361397724E-002 | Pass | Pass | 5.8766155738 | 55.9845405455 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8324010789E-002 | 2.1662989208E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1059634950E-002 | 6.0404331079E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.5352843662E-002 | 9.4768803724E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.8733703516E-002 | 3.4154791503E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5404522911 | 0.4875573245 | Pass | Pass | 0.7750297540 | 0.6692004703 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4916306828 | 0.5161789811 | Pass | Pass | 0.8549806910 | 0.8768190131 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3742713259 | 0.4351737533 | Pass | Pass | 0.8897778837 | 1.8265232579 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4597138143 | 0.4750380268 | Pass | Pass | 0.8813907986 | 1.1359957780 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7466989162 | 0.6347944574 | Pass | Pass | 0.7234036490 | 0.6213786542 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6943928058 | 0.6946571511 | Pass | Pass | 0.7912813693 | 0.8305312480 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5463148391 | 0.6032614470 | Pass | Pass | 3.5187465885 | 32.5946469514 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6693404939 | 0.6664727432 | Pass | Pass | 0.8145055582 | 0.8869981235 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0750259608E-002 | 7.6084513542E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6047912928E-002 | 4.6014225305E-002 | Pass | Pass | 0.4836138486 | 0.4820875506 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1736212674 | 0.1276084267 | Pass | Pass | 0.4888706052 | 0.4904378321 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.9557990653E-015 | 7.6170613716E-015 | Pass | Pass | 7.6887941739E-003 | 5.9114503870E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.9250997811E-003 | 8.3704369701E-003 | Pass | Pass | 3.9711760710E-003 | 4.8250745380E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5943894297E-002 | 1.2021047922E-002 | Pass | Pass | 6.0449562250E-003 | 6.8416453315E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.8027656754E-014 | 4.4803884320E-014 | Pass | Pass | 5.1085528500E-005 | 3.0058947018E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 1043.06 | 2.159 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 9.6875 | 2779.43 | 26925.75 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 257.68 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
CORE_MID_LIGHTS | CORE_MID | 9.6875 | 24961.20 | 241812.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 2314.14 |
CORE_TOP_LIGHTS | CORE_TOP | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 9.6875 | 3134.13 | 30361.93 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 9.6875 | 3134.20 | 30362.59 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 9.6875 | 783.68 | 7591.91 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 72.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 9.6875 | 362.03 | 3507.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 33.56 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
Interior Lighting Total | 9.6875 | 46320.38 | 448729.56 | 1321.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 56280.71 | AstronomicalClock | - | 83.64 | 83.64 | 883.65 | |
Exterior Lighting Total | 56280.71 | 883.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3011826.55 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1761122.79 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1526701.81 | 6.11 | 6.89 | 23.50 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1526701.81 | 6.11 | 6.89 | 23.50 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1449097.60 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1449097.60 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 121077.90 | 158212.86 | 107857.69 | 50355.16 | 0.68 | - | 20054.00 | 203.40 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 243930.05 | 283942.02 | 189387.55 | 94554.48 | 0.67 | - | 35646.73 | 361.55 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2415272.12 | 2699158.07 | 1790043.75 | 909114.32 | 0.66 | - | 337409.03 | 3422.19 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 238488.76 | 279043.47 | 186256.19 | 92787.28 | 0.67 | - | 35060.33 | 355.60 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 428255.44 | 309426.71 | 118828.72 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9352.23 | 6793.97 | 2558.26 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89292.21 | 64815.87 | 24476.34 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9122.39 | 6623.04 | 2499.35 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18066.12 | 17139.46 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 408702.12 | 387950.73 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 87760.99 | 83265.60 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9435.15 | 8951.86 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7924.75 | 7522.27 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12077.08 | 11458.47 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7140.22 | 6779.87 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 190837.07 | 181062.14 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 125997.55 | 119543.80 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 190103.44 | 180366.09 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 120080.61 | 113929.91 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 25053.49 | 23770.23 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16425.23 | 15583.91 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24936.15 | 23658.89 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15981.02 | 15162.46 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 295027.98 | 230759.49 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 78412.18 | 56385.87 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 773810.97 | 548872.81 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 81119.11 | 57624.06 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 428255.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9352.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 89292.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 9122.39 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 20748.52 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1033354.38 | 828547.06 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 958.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 9584.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 958.50 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 5.78 | 10682.72 | 1849.05 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.72 | 22071.92 | 2271.59 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 90.75 | 207254.89 | 2283.73 | 1.00 | 1.07 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.57 | 21738.83 | 2271.59 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.27 | 35264.46 | 1657.97 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 526.21 | 1120.11 | 1.00 | 1.63 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.48 | 5016.81 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 512.71 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.128425 | 30758.98 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.077820 | 19881.94 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.128425 | 10252.99 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013127 | 3348.08 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.151679 | 38750.35 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 80198.61 | 80198.61 | 28.85 | 5.777 | 5.777 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 26.62 | 0.01410 | 1.200 | 0.00 |
CORE_BOTTOM | 83071.91 | 83071.91 | 33.28 | 5.984 | 5.984 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 26.62 | 0.01410 | 1.078 | 0.00 |
CORE_MID | 782549.56 | 782549.56 | 313.51 | 56.353 | 56.353 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 26.62 | 0.01410 | 10.778 | 0.00 |
CORE_TOP | 79666.51 | 79666.51 | 31.92 | 5.738 | 5.738 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 26.62 | 0.01410 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12998.89 | 12998.89 | 41.48 | 0.937 | 0.937 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 26.62 | 0.01410 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14808.06 | 14808.06 | 73.32 | 1.069 | 1.069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00869 | 26.62 | 0.01410 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14632.42 | 14632.42 | 46.69 | 1.064 | 1.064 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00880 | 31.73 | 0.01410 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18002.11 | 18002.11 | 89.13 | 1.309 | 1.309 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00866 | 31.26 | 0.01410 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 122174.14 | 122174.14 | 389.82 | 8.805 | 8.805 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 26.62 | 0.01410 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 153245.05 | 153245.05 | 758.73 | 11.140 | 11.140 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00872 | 27.80 | 0.01410 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 137975.39 | 137975.39 | 440.23 | 10.030 | 10.030 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00887 | 31.79 | 0.01410 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 157043.03 | 157043.03 | 777.54 | 11.416 | 11.416 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00871 | 31.16 | 0.01410 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13681.04 | 13681.04 | 43.65 | 0.995 | 0.995 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00890 | 32.10 | 0.01410 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15595.50 | 15595.50 | 77.21 | 1.134 | 1.134 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00873 | 28.03 | 0.01410 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15602.43 | 15602.43 | 49.78 | 1.134 | 1.134 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00885 | 31.92 | 0.01410 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16931.10 | 16931.10 | 83.83 | 1.231 | 1.231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00871 | 31.16 | 0.01410 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8194.84 | 8194.84 | 226.36 | 0.470 | 0.470 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 29.58 | 0.01410 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78128.49 | 78128.49 | 2158.08 | 4.479 | 4.479 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 29.58 | 0.01410 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7984.61 | 7984.61 | 220.55 | 0.458 | 0.458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00850 | 29.77 | 0.01410 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371023.55 | 371023.55 | 473.44 | 21.270 | 21.270 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 24.93 | 0.01410 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 | |
CORE_MID | 238559.45 | 238559.45 | 95.57 | 10.052 | 10.778 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 61465.73 | 61465.73 | 24.62 | 2.613 | 2.613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6613.46 | 6613.46 | 21.10 | 0.281 | 0.281 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00677 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4705.00 | 4705.00 | 23.29 | 0.200 | 0.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00698 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 8461.48 | 8461.48 | 27.00 | 0.360 | 0.360 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00726 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3205.73 | 3205.73 | 15.87 | 0.136 | 0.136 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00596 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 133596.90 | 133596.90 | 426.26 | 5.693 | 5.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 88203.13 | 88203.13 | 436.70 | 3.759 | 3.759 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 133084.10 | 133084.10 | 424.62 | 5.671 | 5.671 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 84066.84 | 84066.84 | 416.22 | 3.582 | 3.582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17533.85 | 17533.85 | 55.94 | 0.748 | 0.748 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11495.18 | 11495.18 | 56.91 | 0.490 | 0.490 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17451.81 | 17451.81 | 55.68 | 0.744 | 0.744 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11184.61 | 11184.61 | 55.38 | 0.477 | 0.477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.78 | 5.78 | 1.20 | 1.20 | 5.7774 | 5.7774 | 5.7774 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.72 | 9.72 | 2.05 | 2.05 | 9.7165 | 3.1085 | 9.7165 | 0.3199 | 0.3000 |
VAV_MID WITH REHEAT | 90.75 | 90.75 | 29.48 | 29.48 | 90.7529 | 29.4820 | 90.7529 | 0.3249 | 0.3000 |
VAV_TOP WITH REHEAT | 9.57 | 9.57 | 5.07 | 5.07 | 9.5699 | 5.0721 | 9.5699 | 0.5300 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.27 | 21.27 | 0.34 | 0.34 | 21.2696 | 21.2696 | 21.2696 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4698 | 0.4698 | 0.4698 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.48 | 4.48 | 0.16 | 0.16 | 4.4789 | 4.4789 | 4.4789 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4577 | 0.4577 | 0.4577 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18066.121 | 18066.121 | 1.795119 | 0.00039915 | 314.445 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17139.46 | 18066.12 | 1.795119 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 18138.79 | 18138.79 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 408702.122 | 408702.122 | 16.906024 | 0.00902977 | 7901.325 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 387950.73 | 408702.12 | 16.906024 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 238559.45 | 0.00 | 410642.01 | 410642.01 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 87760.987 | 87760.987 | 2.612798 | 0.00193897 | 1832.023 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 83265.60 | 87760.99 | 2.612798 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 61465.73 | 0.00 | 88161.68 | 88161.68 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9435.146 | 9435.146 | 0.281105 | 0.00020846 | 196.917 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8951.86 | 9435.15 | 0.281105 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00676819 | 43.8269 | 6613.46 | 0.00 | 9478.22 | 9478.22 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7924.748 | 7924.748 | 0.320628 | 0.00017509 | 153.824 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7522.27 | 7924.75 | 0.320628 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00697916 | 45.1772 | 4705.00 | 0.00 | 7962.38 | 7962.38 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12077.084 | 12077.084 | 0.359843 | 0.00026683 | 252.050 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11458.47 | 12077.08 | 0.359843 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00726098 | 46.9790 | 8461.48 | 0.00 | 12132.22 | 12132.22 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7140.215 | 7140.215 | 0.392572 | 0.00015775 | 132.517 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6779.87 | 7140.22 | 0.392572 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00595993 | 38.6441 | 3205.73 | 0.00 | 7175.17 | 7175.17 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 190837.070 | 190837.070 | 5.692815 | 0.00421631 | 3981.366 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181062.14 | 190837.07 | 5.692815 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760521 | 49.1775 | 133596.90 | 0.00 | 191708.31 | 191708.31 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 125997.552 | 125997.552 | 3.758817 | 0.00278376 | 2628.597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 119543.80 | 125997.55 | 3.758817 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760887 | 49.2009 | 88203.13 | 0.00 | 126572.78 | 126572.78 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 190103.440 | 190103.440 | 5.670879 | 0.00420010 | 3966.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180366.09 | 190103.44 | 5.670879 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760294 | 49.1630 | 133084.10 | 0.00 | 190971.33 | 190971.33 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 120080.606 | 120080.606 | 3.581951 | 0.00265303 | 2505.230 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113929.91 | 120080.61 | 3.581951 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00757875 | 49.0087 | 84066.84 | 0.00 | 120628.82 | 120628.82 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 25053.488 | 25053.488 | 0.747766 | 0.00055353 | 522.597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23770.23 | 25053.49 | 0.747766 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767534 | 49.6253 | 17533.85 | 0.00 | 25167.86 | 25167.86 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16425.229 | 16425.229 | 0.490257 | 0.00036290 | 342.615 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15583.91 | 16425.23 | 0.490257 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767193 | 49.6036 | 11495.18 | 0.00 | 16500.21 | 16500.21 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24936.145 | 24936.145 | 0.744258 | 0.00055093 | 520.151 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23658.89 | 24936.15 | 0.744258 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767349 | 49.6135 | 17451.81 | 0.00 | 25049.99 | 25049.99 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15981.021 | 15981.021 | 0.476980 | 0.00035308 | 333.353 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15162.46 | 15981.02 | 0.476980 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766019 | 49.5288 | 11184.61 | 0.00 | 16053.98 | 16053.98 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 121077.904 | -999.000 | 5.777406 | 0.00515093 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 121077.90 | 91597.43 | 5.777406 | 24.59 | 17.83 | 0.01000745 | 11.30 | 11.30 | 0.00828082 | 26.62 | 0.01409688 | 21.55 | 20.7720 | 24.00 | 0.00893529 | 48.0473 | 80198.61 | 0.00 | 135768.41 | 98524.05 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 295027.983 | 295027.983 | 5.777406 | 0.00651828 | 5394.629 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 230759.49 | 295027.98 | 5.777406 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.7720 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 243402.26 | 243402.26 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 243930.046 | -999.000 | 9.716494 | 0.01037735 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 243930.05 | 179523.14 | 9.716494 | 26.46 | 18.82 | 0.01047111 | 11.30 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 28.1707 | 24.00 | 0.00881994 | 47.4354 | 122701.91 | 0.00 | 268631.06 | 190197.62 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 78412.182 | 78412.182 | 2.914948 | 0.00173242 | 1081.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56385.87 | 78412.18 | 2.914948 | -10.70 | -10.70 | 0.00150390 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 93.9022 | 21.00 | 0.00746794 | 48.2995 | 22985.67 | 0.00 | 59598.95 | 59598.95 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2415272.118 | -999.000 | 90.752886 | 0.10275126 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2415272.12 | 1725448.39 | 90.752886 | 26.89 | 19.20 | 0.01078856 | 11.30 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 31.6422 | 24.00 | 0.00885776 | 47.6362 | 1100944.06 | 0.00 | 2646135.87 | 1826387.22 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 773810.968 | 773810.968 | 27.225866 | 0.01709641 | 10578.625 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 548872.81 | 773810.97 | 27.225866 | -10.66 | -10.66 | 0.00151202 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 105.4741 | 21.00 | 0.00774635 | 50.0771 | 637891.59 | 0.00 | 580105.85 | 580105.85 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 238488.762 | -999.000 | 9.569862 | 0.01014586 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 238488.76 | 176112.55 | 9.569862 | 26.40 | 18.77 | 0.01043487 | 11.30 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 29.8549 | 24.00 | 0.00884871 | 47.5883 | 131210.31 | 0.00 | 262815.45 | 186609.43 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 81119.109 | 81119.109 | 2.870959 | 0.00179223 | 1110.039 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57624.06 | 81119.11 | 2.870959 | -10.61 | -10.61 | 0.00151608 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 99.5162 | 21.00 | 0.00784056 | 50.6778 | 73594.17 | 0.00 | 60903.70 | 60903.70 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 428255.435 | 309426.711 | 21.269620 | 0.01048795 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 458205.66 | 452231.27 | -999.0 | 28.48 | 17.98 | 0.00858918 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 370441.23 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9352.229 | 6793.971 | 0.469785 | 0.00022904 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 10025.65 | 9749.42 | -999.0 | 28.03 | 17.91 | 0.00868623 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01409688 | 22.40 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 8194.84 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89292.208 | 64815.865 | 4.478862 | 0.00218676 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 95698.84 | 92937.58 | -999.0 | 28.04 | 17.92 | 0.00869533 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01409688 | 22.40 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 78128.49 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9122.393 | 6623.041 | 0.457733 | 0.00022341 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9777.44 | 9501.29 | -999.0 | 28.04 | 17.92 | 0.00869113 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01409688 | 22.45 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 7984.61 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 428255.435 | 428255.435 | 21.269620 | 0.01048795 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 428255.44 | 428255.44 | 21.269620 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5909 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9352.229 | 9352.229 | 0.469785 | 0.00022904 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9352.23 | 9352.23 | 0.469785 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3273 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89292.208 | 89292.208 | 4.478862 | 0.00218676 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 89292.21 | 89292.21 | 4.478862 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4900 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9122.393 | 9122.393 | 0.457733 | 0.00022341 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9122.39 | 9122.39 | 0.457733 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4150 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20748.523 | 20748.523 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20748.52 | 20748.52 | 21.269620 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5909 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 1323504.47 | 21.269620 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5909 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1033354.377 | 1033354.377 | 21.269620 | 0.02283070 | 19208.911 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 828547.06 | 1033354.38 | 21.269620 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5909 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 0.469785 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3273 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9584.958 | 9584.958 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9584.96 | 9584.96 | 4.478862 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4900 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 0.457733 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4150 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18066.121 | 18066.121 | 1.795119 | 0.00039915 | 314.445 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.4770 | 0.512915 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17139.46 | 18066.12 | 1.0000 | 2.16059663 | 1.795119 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.39910814 | 60.00 | 49.00 | 11.00 | 0.000 | 17139.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 18138.79 | 18138.79 | 2.16059663 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 408702.122 | 408702.122 | 16.906024 | 0.00902977 | 7901.325 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 10.7970 | 11.603453 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 387950.73 | 408702.12 | 1.0000 | 20.34800530 | 16.906024 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 9.02885285 | 60.00 | 49.00 | 11.00 | 0.000 | 387950.73 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 238559.45 | 0.00 | 410642.01 | 410642.01 | 20.34800530 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 32.59 | 18.86 | 0.00800000 | 53240.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 87760.987 | 87760.987 | 2.612798 | 0.00193897 | 1832.023 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 2.3174 | 2.491620 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 83265.60 | 87760.99 | 1.0000 | 3.14475008 | 2.612798 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.93877398 | 60.00 | 49.00 | 11.00 | 0.000 | 83265.60 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 61465.73 | 0.00 | 88161.68 | 88161.68 | 3.14475008 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.29 | 21.24 | 0.00800000 | 61094.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9435.146 | 9435.146 | 0.281105 | 0.00020846 | 196.917 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.2491 | 0.267873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8951.86 | 9435.15 | 1.0000 | 0.33833667 | 0.281105 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.20843675 | 60.00 | 49.00 | 11.00 | 0.000 | 8951.86 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00676819 | 21.00 | 0.00676819 | 43.8269 | 6613.46 | 0.00 | 9478.22 | 9478.22 | 0.33833667 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61074.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7924.748 | 7924.748 | 0.320628 | 0.00017509 | 153.824 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.2094 | 0.224991 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7522.27 | 7924.75 | 1.0000 | 0.38590659 | 0.320628 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.17506977 | 60.00 | 49.00 | 11.00 | 0.000 | 7522.27 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00697916 | 21.00 | 0.00697916 | 45.1772 | 4705.00 | 0.00 | 7962.38 | 7962.38 | 0.38590659 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 33.03 | 19.01 | 0.00800000 | 53692.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12077.084 | 12077.084 | 0.359843 | 0.00026683 | 252.050 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.3189 | 0.342880 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11458.47 | 12077.08 | 1.0000 | 0.43310496 | 0.359843 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26680120 | 60.00 | 49.00 | 11.00 | 0.000 | 11458.47 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00726098 | 21.00 | 0.00726098 | 46.9790 | 8461.48 | 0.00 | 12132.22 | 12132.22 | 0.43310496 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61072.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7140.215 | 7140.215 | 0.392572 | 0.00015775 | 132.517 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.1887 | 0.202718 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6779.87 | 7140.22 | 1.0000 | 0.47249709 | 0.392572 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.15773824 | 60.00 | 49.00 | 11.00 | 0.000 | 6779.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00595993 | 21.00 | 0.00595993 | 38.6441 | 3205.73 | 0.00 | 7175.17 | 7175.17 | 0.47249709 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 27.69 | 17.23 | 0.00800000 | 48245.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 190837.070 | 190837.070 | 5.692815 | 0.00421631 | 3981.366 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 5.0391 | 5.418051 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181062.14 | 190837.07 | 1.0000 | 6.85184377 | 5.692815 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 4.21588177 | 60.00 | 49.00 | 11.00 | 0.000 | 181062.14 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00760521 | 21.00 | 0.00760521 | 49.1775 | 133596.90 | 0.00 | 191708.31 | 191708.31 | 6.85184377 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61038.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 125997.552 | 125997.552 | 3.758817 | 0.00278376 | 2628.597 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 3.3270 | 3.577194 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 119543.80 | 125997.55 | 1.0000 | 4.52409277 | 3.758817 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.78347798 | 60.00 | 49.00 | 11.00 | 0.000 | 119543.80 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00760887 | 21.00 | 0.00760887 | 49.2009 | 88203.13 | 0.00 | 126572.78 | 126572.78 | 4.52409277 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61037.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 190103.440 | 190103.440 | 5.670879 | 0.00420010 | 3966.072 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 5.0197 | 5.397223 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180366.09 | 190103.44 | 1.0000 | 6.82544180 | 5.670879 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 4.19967477 | 60.00 | 49.00 | 11.00 | 0.000 | 180366.09 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00760294 | 21.00 | 0.00760294 | 49.1630 | 133084.10 | 0.00 | 190971.33 | 190971.33 | 6.82544180 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120080.606 | 120080.606 | 3.581951 | 0.00265303 | 2505.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 3.1708 | 3.409206 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113929.91 | 120080.61 | 1.0000 | 4.31121834 | 3.581951 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.65276362 | 60.00 | 49.00 | 11.00 | 0.000 | 113929.91 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00757875 | 21.00 | 0.00757875 | 49.0087 | 84066.84 | 0.00 | 120628.82 | 120628.82 | 4.31121834 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61040.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25053.488 | 25053.488 | 0.747766 | 0.00055353 | 522.597 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.6615 | 0.711293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23770.23 | 25053.49 | 1.0000 | 0.90000764 | 0.747766 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.55346973 | 60.00 | 49.00 | 11.00 | 0.000 | 23770.23 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00767534 | 21.00 | 0.00767534 | 49.6253 | 17533.85 | 0.00 | 25167.86 | 25167.86 | 0.90000764 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61023.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16425.229 | 16425.229 | 0.490257 | 0.00036290 | 342.615 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.4337 | 0.466328 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15583.91 | 16425.23 | 1.0000 | 0.59007084 | 0.490257 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.36285834 | 60.00 | 49.00 | 11.00 | 0.000 | 15583.91 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00767193 | 21.00 | 0.00767193 | 49.6036 | 11495.18 | 0.00 | 16500.21 | 16500.21 | 0.59007084 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61022.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24936.145 | 24936.145 | 0.744258 | 0.00055093 | 520.151 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.6584 | 0.707962 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23658.89 | 24936.15 | 1.0000 | 0.89578487 | 0.744258 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.55087746 | 60.00 | 49.00 | 11.00 | 0.000 | 23658.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00767349 | 21.00 | 0.00767349 | 49.6135 | 17451.81 | 0.00 | 25049.99 | 25049.99 | 0.89578487 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61024.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15981.021 | 15981.021 | 0.476980 | 0.00035308 | 333.353 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 0.4220 | 0.453717 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15162.46 | 15981.02 | 1.0000 | 0.57409080 | 0.476980 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.35304511 | 60.00 | 49.00 | 11.00 | 0.000 | 15162.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766019 | 21.00 | 0.00766019 | 49.5288 | 11184.61 | 0.00 | 16053.98 | 16053.98 | 0.57409080 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61024.0 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 121077.904 | -999.000 | 5.777406 | 0.00515093 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4434 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.777406 | 6.95365717 | 4197.9300 | 999.8980 | 128.41230378 | 12.27 | 6.67 | 5.60 | 3018768.83 | 4.0108 | 4.010837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 121077.90 | 91597.43 | 1.0000 | 6.95365717 | 5.777406 | 24.59 | 17.83 | 0.01000745 | 50198.0 | 11.30 | 11.30 | 0.00828082 | 32790.1 | 5.15040847 | 6.67 | 10.65 | 5.60 | 10682.719 | 110395.19 | 26.62 | 0.01409688 | 21.55 | 1.20008137 | 20.7720 | 24.06 | 0.00893529 | 24.00 | 0.00893529 | 48.0473 | 80198.61 | 0.00 | 135768.41 | 98524.05 | 6.95365717 | 24.59 | 17.84 | 0.01000745 | 50198.0 | 10.75 | 10.60 | 0.00788280 | 30673.3 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 295027.983 | 295027.983 | 5.777406 | 0.00651828 | 5394.629 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.777406 | 6.95365717 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 6.4222 | 8.376133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 230759.49 | 295027.98 | 1.0000 | 6.95365717 | 5.777406 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 6.51761786 | 60.00 | 49.00 | 11.00 | 0.000 | 230759.49 | -10.70 | 0.00150390 | -10.70 | 1.20008137 | 20.7720 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 243402.26 | 243402.26 | 6.95365717 | 12.80 | 2.39 | 0.00031239 | 13650.7 | 47.61 | 17.53 | 0.00031239 | 48654.1 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 243930.046 | -999.000 | 9.716494 | 0.01037735 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3053 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.716494 | 11.69472327 | 4197.9300 | 999.8980 | 128.41230378 | 12.27 | 6.67 | 5.60 | 3018768.83 | 8.0804 | 8.080448 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 243930.05 | 179523.14 | 1.0000 | 11.69472327 | 9.716494 | 26.46 | 18.82 | 0.01047111 | 53293.0 | 11.30 | 12.09 | 0.00828082 | 34322.2 | 10.37628947 | 6.67 | 10.65 | 5.60 | 22071.922 | 221858.12 | 32.03 | 0.01409687 | 23.08 | 2.73720000 | 28.1707 | 24.00 | 0.00886576 | 24.00 | 0.00881994 | 47.4354 | 122701.91 | 0.00 | 268631.06 | 190197.62 | 11.69472327 | 26.46 | 18.83 | 0.01047111 | 53293.0 | 10.58 | 10.45 | 0.00781036 | 30322.7 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 78412.182 | 78412.182 | 2.914948 | 0.00173242 | 1081.693 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.716494 | 11.69472327 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 1.5693 | 2.226199 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56385.87 | 78412.18 | 1.0000 | 3.50841698 | 2.914948 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.73224462 | 60.00 | 49.00 | 11.00 | 0.000 | 56385.87 | -10.70 | 0.00150390 | -10.70 | 2.73720000 | 93.9022 | 9.94 | 0.00327039 | 21.00 | 0.00746794 | 48.2995 | 22985.67 | 0.00 | 59598.95 | 59598.95 | 3.50841698 | 12.80 | 4.16 | 0.00161162 | 16930.9 | 29.66 | 12.04 | 0.00161162 | 33918.3 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2415272.118 | -999.000 | 90.752886 | 0.10275126 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8954 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.752886 | 109.22971865 | 4197.9300 | 999.8980 | 128.41230378 | 12.27 | 6.67 | 5.60 | 3018768.83 | 80.0085 | 80.008515 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2415272.12 | 1725448.39 | 1.0000 | 109.22971865 | 90.752886 | 26.89 | 19.20 | 0.01078856 | 54536.6 | 11.30 | 12.09 | 0.00828082 | 34322.2 | 102.74077758 | 6.67 | 10.65 | 5.60 | 207254.891 | 2208017.23 | 32.03 | 0.01409687 | 23.08 | 28.71625000 | 31.6422 | 24.00 | 0.00893037 | 24.00 | 0.00885776 | 47.6362 | 1100944.06 | 0.00 | 2646135.87 | 1826387.22 | 109.22971865 | 26.89 | 19.21 | 0.01078856 | 54536.6 | 10.57 | 10.44 | 0.00781116 | 30311.2 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 773810.968 | 773810.968 | 27.225866 | 0.01709641 | 10578.625 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.752886 | 109.22971865 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 15.2756 | 21.969251 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 548872.81 | 773810.97 | 1.0000 | 32.76891559 | 27.225866 | -10.66 | -10.66 | 0.00151202 | -6959.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 17.09466378 | 60.00 | 49.00 | 11.00 | 0.000 | 548872.81 | -10.70 | 0.00150390 | -10.70 | 28.71625000 | 105.4741 | 20.68 | 0.00772636 | 21.00 | 0.00774635 | 50.0771 | 637891.59 | 0.00 | 580105.85 | 580105.85 | 32.76891559 | 12.80 | 4.02 | 0.00150390 | 16658.9 | 30.37 | 12.23 | 0.00150390 | 34361.8 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 238488.762 | -999.000 | 9.569862 | 0.01014586 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2379 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.569862 | 11.51823785 | 4197.9300 | 999.8980 | 128.41230378 | 12.27 | 6.67 | 5.60 | 3018768.83 | 7.9002 | 7.900200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 238488.76 | 176112.55 | 1.0000 | 11.51823785 | 9.569862 | 26.40 | 18.77 | 0.01043487 | 53140.2 | 11.30 | 12.09 | 0.00828082 | 34322.2 | 10.14482827 | 6.67 | 10.65 | 5.60 | 21738.834 | 216749.93 | 32.03 | 0.01409687 | 23.08 | 2.85707000 | 29.8549 | 24.00 | 0.00886880 | 24.00 | 0.00884871 | 47.5883 | 131210.31 | 0.00 | 262815.45 | 186609.43 | 11.51823785 | 26.40 | 18.78 | 0.01043487 | 53140.2 | 10.59 | 10.45 | 0.00781007 | 30322.8 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 81119.109 | 81119.109 | 2.870959 | 0.00179223 | 1110.039 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.569862 | 11.51823785 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 1.6037 | 2.303051 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57624.06 | 81119.11 | 1.0000 | 3.45547136 | 2.870959 | -10.61 | -10.61 | 0.00151608 | -6898.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.79204477 | 60.00 | 49.00 | 11.00 | 0.000 | 57624.06 | -10.70 | 0.00150390 | -10.70 | 2.85707000 | 99.5162 | 17.82 | 0.00533183 | 21.00 | 0.00784056 | 50.6778 | 73594.17 | 0.00 | 60903.70 | 60903.70 | 3.45547136 | 12.80 | 4.04 | 0.00152242 | 16705.6 | 30.29 | 12.21 | 0.00152242 | 34330.9 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 428255.435 | 309426.711 | 21.269620 | 0.01048795 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8069 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 458205.66 | 452231.27 | 0.9346 | -999.0 | -999.0 | 28.48 | 17.98 | 0.00858918 | 50556.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 458205.66 | 32.10 | 0.01409687 | 23.10 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 370441.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9352.229 | 6793.971 | 0.469785 | 0.00022904 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9873 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 10025.65 | 9749.42 | 0.9328 | -999.0 | -999.0 | 28.03 | 17.91 | 0.00868623 | 50344.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10025.65 | 29.58 | 0.01409688 | 22.40 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 8194.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89292.208 | 64815.865 | 4.478862 | 0.00218676 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0042 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 95698.84 | 92937.58 | 0.9331 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00869533 | 50372.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95698.84 | 29.58 | 0.01409688 | 22.40 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 78128.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9122.393 | 6623.041 | 0.457733 | 0.00022341 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9964 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9777.44 | 9501.29 | 0.9330 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00869113 | 50365.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9777.44 | 29.77 | 0.01409688 | 22.45 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 7984.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 428255.435 | 428255.435 | 21.269620 | 0.01048795 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 428255.44 | 428255.44 | 1.0000 | 25.60000751 | 21.269620 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 428255.44 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5909 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9352.229 | 9352.229 | 0.469785 | 0.00022904 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9352.23 | 9352.23 | 1.0000 | 0.56543033 | 0.469785 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9352.23 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.3273 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89292.208 | 89292.208 | 4.478862 | 0.00218676 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 89292.21 | 89292.21 | 1.0000 | 5.39073569 | 4.478862 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89292.21 | -10.70 | 0.00150390 | -10.70 | 0.15631366 | 3.4900 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9122.393 | 9122.393 | 0.457733 | 0.00022341 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9122.39 | 9122.39 | 1.0000 | 0.55092514 | 0.457733 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9122.39 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.4150 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20748.523 | 20748.523 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.269620 | 25.60000751 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20748.52 | 20748.52 | 1.0000 | 25.60000751 | 21.269620 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20748.52 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5909 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.269620 | 25.60000751 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 1323504.47 | 1.0000 | 25.60000751 | 21.269620 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5909 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1033354.377 | 1033354.377 | 21.269620 | 0.02283070 | 19208.911 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.269620 | 25.60000751 | 4197.9300 | 999.8980 | 77.81177404 | 71.00 | 82.00 | 11.00 | 3593132.19 | 23.0592 | 29.337942 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 828547.06 | 1033354.38 | 1.0000 | 25.60000751 | 21.269620 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 22.82837330 | 60.00 | 49.00 | 11.00 | 0.000 | 828547.06 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5909 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60000751 | 16.60 | 4.06 | 0.00002393 | 16740.9 | 16.60 | 4.06 | 0.00002393 | 16740.9 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.469785 | 0.56543033 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 1.0000 | 0.56543033 | 0.469785 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.50 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.3273 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9584.958 | 9584.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.478862 | 5.39073569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9584.96 | 9584.96 | 1.0000 | 5.39073569 | 4.478862 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9584.96 | -10.70 | 0.00150390 | -10.70 | 0.15631366 | 3.4900 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.457733 | 0.55092514 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 1.0000 | 0.55092514 | 0.457733 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.50 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.4150 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.78 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.74 | 9.72 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 28.72 | 90.75 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.86 | 9.57 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3149.33 | 1261.67 | 583.67 |
CORE_BOTTOM | 3010.00 | 861.17 | 12.00 |
CORE_MID | 2187.33 | 2343.17 | 38.17 |
CORE_TOP | 2430.67 | 3155.17 | 532.83 |
PERIMETER_BOT_ZN_3 | 2387.33 | 2782.17 | 134.17 |
PERIMETER_BOT_ZN_2 | 1917.67 | 3383.00 | 182.67 |
PERIMETER_BOT_ZN_1 | 2699.33 | 2379.83 | 188.67 |
PERIMETER_BOT_ZN_4 | 3000.17 | 1931.33 | 129.83 |
PERIMETER_MID_ZN_3 | 2749.33 | 3635.00 | 1055.50 |
PERIMETER_MID_ZN_2 | 2013.67 | 3480.00 | 882.33 |
PERIMETER_MID_ZN_1 | 2765.00 | 2906.67 | 590.50 |
PERIMETER_MID_ZN_4 | 2367.17 | 3807.67 | 822.83 |
PERIMETER_TOP_ZN_3 | 3351.67 | 3942.67 | 1825.00 |
PERIMETER_TOP_ZN_2 | 3106.17 | 4059.50 | 1626.17 |
PERIMETER_TOP_ZN_1 | 3073.50 | 3364.83 | 1228.50 |
PERIMETER_TOP_ZN_4 | 2894.50 | 4075.83 | 1487.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5088.17 | 4893.83 | 2483.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 138.67 | 0.00 | 10.83 |
CORE_BOTTOM | 0.00 | 1.17 | 0.00 | 0.00 |
CORE_MID | 2.00 | 1.50 | 1.17 | 1.50 |
CORE_TOP | 5.67 | 0.00 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 7.50 | 0.00 | 7.50 |
PERIMETER_BOT_ZN_1 | 0.33 | 105.67 | 0.00 | 105.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 45.67 | 0.00 | 18.50 |
PERIMETER_MID_ZN_3 | 27.33 | 0.00 | 7.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18.50 | 7.67 | 2.33 | 7.67 |
PERIMETER_MID_ZN_1 | 16.00 | 158.67 | 2.83 | 158.67 |
PERIMETER_MID_ZN_4 | 15.50 | 10.00 | 2.67 | 7.17 |
PERIMETER_TOP_ZN_3 | 110.83 | 0.00 | 31.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 77.83 | 8.50 | 13.17 | 8.50 |
PERIMETER_TOP_ZN_1 | 69.17 | 45.83 | 11.83 | 45.67 |
PERIMETER_TOP_ZN_4 | 53.50 | 11.17 | 9.17 | 8.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 805.33 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 771.33 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 670.50 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 132.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 118.33 | 1171.67 | 31.33 | 234.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 1.242 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.912 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.798 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.748 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.909 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 1.379 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 1.199 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 1.844 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.878 | 0.128 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 1.504 | 0.141 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 1.230 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 1.655 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.958 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 1.610 | 0.165 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 1.273 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 1.759 | 0.165 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
Electricity:Building | 19507.65 | 254949.54 | 01-JAN-06:10 | 1167329.12 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 682.08 | 14702.05 | 01-JAN-06:10 | 35858.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 257.68 | 1244.51 | 01-JAN-06:10 | 22401.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 552.69 | 7160.52 | 01-JAN-06:10 | 38246.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5526.92 | 71604.96 | 01-JAN-06:10 | 382463.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2314.15 | 11176.56 | 01-JAN-06:10 | 201178.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 552.69 | 7160.50 | 01-JAN-06:10 | 38246.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 693.98 | 8991.05 | 01-JAN-06:10 | 48023.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 290.56 | 1403.33 | 01-JAN-06:10 | 25259.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 447.23 | 5794.18 | 01-JAN-06:10 | 30947.91 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 693.99 | 8991.20 | 01-JAN-06:10 | 48023.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 290.57 | 1403.36 | 01-JAN-06:10 | 25260.46 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 447.22 | 5794.15 | 01-JAN-06:10 | 30947.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7567.51 | 95259.03 | 01-JAN-06:10 | 385948.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 72.65 | 350.90 | 01-JAN-06:10 | 6316.16 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1572.37 | 19648.16 | 01-JAN-06:10 | 80862.03 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 33.56 | 162.10 | 01-JAN-06:10 | 2917.81 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4852.62 | 65235.65 | 11-JAN-22:40 | 398087.13 | 25-AUG-14:40 |
ExteriorEquipment:Electricity | 2044.08 | 15778.61 | 01-JAN-00:10 | 129663.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.73 | 1613.62 | 01-JAN-00:10 | 5498.40 | 03-APR-07:20 |
ElectricityPurchased:Facility | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
ElectricityPurchased:Plant | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
Cogeneration:ElectricityPurchased | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
ElectricityNet:Plant | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
Cogeneration:ElectricityNet | 30301.55 | 371640.29 | 08-JAN-15:50 | 2101131.46 | 02-AUG-15:10 |
Fans:Electricity | 2220.34 | 41320.19 | 01-JAN-06:00 | 236609.16 | 25-AUG-14:40 |
General:Fans:Electricity | 2220.34 | 41320.19 | 01-JAN-06:00 | 236609.16 | 25-AUG-14:40 |
ExteriorLights:Electricity | 883.65 | 0.00 | 01-JAN-07:30 | 56280.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 883.65 | 0.00 | 01-JAN-07:30 | 56280.71 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.27 | 1942.80 | 01-JAN-00:10 | 1942.80 | 01-JAN-00:10 |
HeatRecovery:Electricity | 22.55 | 0.00 | 01-JAN-00:10 | 2110.37 | 02-JAN-07:10 |
Cooling:Electricity | 3757.20 | 21964.19 | 11-JAN-22:40 | 522552.78 | 02-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 25.58 | 0.00 | 01-JAN-00:10 | 38049.99 | 09-JAN-20:30 |
Electricity:Plant | 3101.29 | 4777.94 | 05-JAN-01:00 | 524863.39 | 02-AUG-15:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 1260.78 | 0.00 | 01-JAN-00:10 | 353658.84 | 02-AUG-15:00 |
HeatRejection:Electricity | 1192.56 | 1417.79 | 14-JAN-21:10 | 95698.22 | 18-JUN-14:10 |
General:HeatRejection:Electricity | 245.98 | 0.00 | 01-JAN-00:10 | 46449.95 | 18-JUN-14:10 |
Pumps:Electricity | 647.95 | 3348.08 | 02-JAN-04:40 | 78337.73 | 25-AUG-14:40 |
General:Pumps:Electricity | 647.95 | 3348.08 | 02-JAN-04:40 | 78337.73 | 25-AUG-14:40 |
WIRED_LTG_ELECTRICITY | 120.67 | 0.00 | 01-JAN-00:10 | 10490.43 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1985.54 | 8146.58 | 05-JAN-02:10 | 2558928.86 | 02-JAN-07:10 |
Gas:Plant | 1985.54 | 8146.58 | 05-JAN-02:10 | 2558928.86 | 02-JAN-07:10 |
WaterSystems:Gas | 592.14 | 8146.58 | 02-JAN-06:00 | 83901.37 | 10-FEB-12:20 |
Water Heater:WaterSystems:Gas | 592.14 | 8146.58 | 02-JAN-06:00 | 83901.37 | 10-FEB-12:20 |
Heating:Gas | 1393.40 | 0.00 | 01-JAN-00:40 | 2550782.28 | 02-JAN-07:10 |
Boiler:Heating:Gas | 1393.40 | 0.00 | 01-JAN-00:40 | 2550782.28 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 19970.78 | 72222.97 | 05-JAN-03:00 | 2741275.93 | 02-AUG-15:00 |
PlantLoopCoolingDemand:HVAC | 19970.78 | 72222.97 | 05-JAN-03:00 | 2741275.93 | 02-AUG-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 19970.78 | 72222.97 | 05-JAN-03:00 | 2741275.93 | 02-AUG-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8240.82 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
Water:Plant | 8231.30 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 8240.82 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
MainsWater:Plant | 8231.30 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 9.52 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-20:30 |
Humidifier:Water | 9.52 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-20:30 |
MainsWater:HVAC | 9.52 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-20:30 |
Humidifier:MainsWater | 9.52 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-20:30 |
HeatRejection:Water | 5951.13 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
HeatRejection:MainsWater | 5951.13 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 1395.28 | 0.00 | 01-JAN-00:40 | 2191886.79 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 413.25 | 0.00 | 01-JAN-00:10 | 52103.25 | 08-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 413.25 | 0.00 | 01-JAN-00:10 | 52103.25 | 08-FEB-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 68056.66 | 151590.44 | 11-JAN-22:40 | 11600683.88 | 02-AUG-15:00 |
EnergyTransfer:Building | 19684.70 | 63834.82 | 28-JAN-01:00 | 1653765.87 | 18-AUG-15:50 |
EnergyTransfer:Zone:BASEMENT | 763.03 | 0.00 | 01-JAN-00:10 | 86120.25 | 29-MAR-03:50 |
Heating:EnergyTransfer | 294.75 | 0.00 | 12-JAN-22:10 | 1183901.96 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 7.72 | 0.00 | 01-JAN-00:10 | 69023.00 | 25-JUN-18:40 |
Cooling:EnergyTransfer | 19389.95 | 63829.71 | 28-JAN-01:00 | 1653765.87 | 18-AUG-15:50 |
Cooling:EnergyTransfer:Zone:BASEMENT | 755.31 | 0.00 | 01-JAN-00:10 | 83013.12 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 683.55 | 0.00 | 01-JAN-00:10 | 54689.31 | 14-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 683.55 | 0.00 | 01-JAN-00:10 | 54689.31 | 14-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4892.40 | 0.00 | 01-JAN-00:40 | 501287.39 | 11-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.47 | 0.00 | 01-JAN-00:10 | 401688.90 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4885.93 | 0.00 | 01-JAN-00:40 | 501287.39 | 11-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 449.02 | 0.00 | 01-JAN-00:40 | 73703.20 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 7.32 | 0.00 | 01-JAN-00:40 | 73703.20 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 441.70 | 0.00 | 01-JAN-00:20 | 56608.36 | 19-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.94 | 0.00 | 01-JAN-00:10 | 10743.50 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.05 | 0.00 | 01-JAN-00:10 | 3868.51 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.89 | 0.00 | 01-JAN-00:10 | 10743.50 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 77.02 | 0.00 | 01-JAN-00:10 | 12521.85 | 26-JUN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.05 | 0.00 | 01-JAN-00:10 | 3035.71 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 76.97 | 0.00 | 01-JAN-00:10 | 12521.85 | 26-JUN-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.42 | 0.00 | 01-JAN-00:10 | 16202.80 | 04-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.21 | 0.00 | 01-JAN-00:10 | 7905.22 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.20 | 0.00 | 01-JAN-00:10 | 16202.80 | 04-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 111.35 | 0.00 | 01-JAN-00:10 | 17262.21 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1753.23 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 111.34 | 0.00 | 01-JAN-00:10 | 17262.21 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 640.67 | 0.00 | 01-JAN-00:40 | 127017.51 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 47.80 | 0.00 | 01-JAN-00:40 | 127017.51 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 592.86 | 0.00 | 01-JAN-00:10 | 101151.09 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 648.83 | 0.00 | 01-JAN-00:40 | 133833.56 | 14-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.53 | 0.00 | 01-JAN-00:40 | 120392.71 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 620.30 | 0.00 | 01-JAN-00:10 | 133833.56 | 14-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 929.53 | 0.00 | 01-JAN-00:40 | 161155.82 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 28.13 | 0.00 | 01-JAN-00:40 | 130808.54 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 901.40 | 0.00 | 01-JAN-00:10 | 161155.82 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 693.66 | 0.00 | 01-JAN-00:40 | 149671.26 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 22.64 | 0.00 | 01-JAN-00:40 | 114115.22 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 671.03 | 0.00 | 01-JAN-00:10 | 149671.26 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.69 | 0.00 | 01-JAN-00:40 | 15258.69 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 17.20 | 0.00 | 01-JAN-00:40 | 15258.69 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.49 | 0.00 | 01-JAN-00:10 | 11789.99 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.06 | 0.00 | 01-JAN-00:40 | 14870.51 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.80 | 0.00 | 01-JAN-00:40 | 14870.51 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.25 | 0.00 | 01-JAN-00:10 | 13635.13 | 14-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.09 | 0.00 | 01-JAN-00:40 | 17563.76 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 11.39 | 0.00 | 01-JAN-00:40 | 16969.63 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.70 | 0.00 | 01-JAN-00:10 | 17563.76 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 72.05 | 0.00 | 01-JAN-00:40 | 15685.74 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.59 | 0.00 | 01-JAN-00:40 | 15295.90 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.45 | 0.00 | 01-JAN-00:10 | 15685.74 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 70.52 | 0.00 | 01-JAN-00:10 | 7972.04 | 14-AUG-14:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.06 | 0.00 | 01-JAN-00:10 | 3374.42 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 69.46 | 0.00 | 01-JAN-00:10 | 7972.04 | 14-AUG-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 506.49 | 0.00 | 01-JAN-00:40 | 160947.49 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 60.37 | 0.00 | 01-JAN-00:40 | 160947.49 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 446.12 | 0.00 | 01-JAN-00:10 | 72343.70 | 25-AUG-14:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 103.07 | 0.00 | 01-JAN-00:40 | 29519.33 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.11 | 0.00 | 01-JAN-00:40 | 29519.33 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.96 | 0.00 | 01-JAN-00:10 | 22659.55 | 19-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.18 | 559.98 | 01-JAN-00:40 | 7631.49 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.18 | 559.98 | 01-JAN-00:40 | 7631.49 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1191.30 | 1.66 | 10-JAN-07:20 | 72519.09 | 12-APR-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.99 | 0.00 | 03-JAN-11:10 | 5294.06 | 02-JAN-23:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1188.32 | 0.00 | 01-JAN-00:10 | 72519.09 | 12-APR-17:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.84 | 1.23 | 09-JAN-13:10 | 7361.97 | 12-APR-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.84 | 0.00 | 02-JAN-16:20 | 567.89 | 16-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.01 | 0.00 | 01-JAN-00:10 | 7361.97 | 12-APR-17:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.00 | 56393.05 | 28-JAN-01:00 | 376565.51 | 04-DEC-22:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.47 | 0.00 | 01-JAN-00:10 | 9465.41 | 28-JAN-01:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.53 | 56393.05 | 28-JAN-01:00 | 376565.51 | 04-DEC-22:40 |
EnergyTransfer:Plant | 26795.48 | 0.00 | 01-JAN-00:40 | 7386266.66 | 25-AUG-14:40 |
WaterSystems:EnergyTransfer | 413.25 | 0.00 | 01-JAN-00:10 | 52103.25 | 08-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 413.25 | 0.00 | 01-JAN-00:10 | 52103.25 | 08-FEB-13:00 |
EnergyTransfer:HVAC | 21576.48 | 65457.24 | 05-JAN-03:00 | 3218958.04 | 02-AUG-15:00 |
HeatingCoils:EnergyTransfer | 982.02 | 0.00 | 01-JAN-00:40 | 2174668.28 | 02-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 982.02 | 0.00 | 01-JAN-00:40 | 2174668.28 | 02-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 982.02 | 0.00 | 01-JAN-00:40 | 2174668.28 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 17601.58 | 58969.29 | 05-JAN-03:00 | 2572382.00 | 02-AUG-15:00 |
HeatRecoveryForHeating:EnergyTransfer | 2198.05 | 0.00 | 01-JAN-00:10 | 847202.67 | 06-FEB-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 794.83 | 0.00 | 01-JAN-00:10 | 689907.89 | 08-JUL-12:00 |
LoopToLoop:EnergyTransfer | 8699.33 | -0.19 | 04-JAN-07:10 | 2371036.02 | 25-AUG-14:40 |
Boilers:EnergyTransfer | 967.52 | 0.00 | 01-JAN-00:40 | 2113347.35 | 02-JAN-07:10 |
Chillers:EnergyTransfer | 7727.30 | 0.00 | 01-JAN-00:10 | 2304095.88 | 25-AUG-14:40 |
HeatRejection:EnergyTransfer | 8988.08 | 0.00 | 01-JAN-00:10 | 2621198.36 | 25-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 7.718 | -755.317 | 0.000 | 0.000 | 92.686 | 257.680 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -27.164 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -683.548 | 0.000 | 0.000 | 83.418 | 231.415 | 321.278 | 0.000 | 0.000 | 0.000 | 47.436 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 6.472 | -4885.914 | 0.000 | 0.000 | 840.740 | 2314.151 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1488.221 |
CORE_TOP | 0.000 | 0.000 | 7.322 | -441.694 | 0.000 | 0.000 | 86.535 | 231.415 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -204.855 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.046 | -84.892 | 0.000 | 0.000 | 10.711 | 29.056 | 40.341 | 21.510 | 0.000 | 0.135 | 40.643 | 0.000 | -48.447 | 0.000 | -9.103 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.050 | -76.970 | 0.000 | 0.000 | 7.052 | 18.725 | 25.998 | 41.475 | 0.000 | 0.115 | 18.198 | 0.000 | -28.832 | 0.000 | -5.810 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.215 | -110.199 | 0.000 | 0.000 | 10.665 | 29.057 | 40.342 | 80.071 | 0.000 | 0.131 | 1.888 | 0.000 | -43.137 | 0.000 | -9.033 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.005 | -111.339 | 0.000 | 0.000 | 6.893 | 18.725 | 25.997 | 41.526 | 0.000 | 0.085 | 57.844 | 0.000 | -33.290 | 0.000 | -6.446 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 47.805 | -592.853 | 0.000 | 0.000 | 111.830 | 290.565 | 403.414 | 221.961 | 0.000 | 2.820 | 129.089 | 0.000 | -433.692 | 0.000 | -180.938 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 28.528 | -620.295 | 0.000 | 0.000 | 53.756 | 187.251 | 259.975 | 417.331 | 0.000 | 2.107 | 58.593 | 0.000 | -266.988 | 0.000 | -120.257 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 28.127 | -901.388 | 0.000 | 0.000 | 108.201 | 290.571 | 403.420 | 801.341 | 0.000 | 2.648 | 0.024 | 0.000 | -414.656 | 0.000 | -191.534 | -126.731 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 22.635 | -671.020 | 0.000 | 0.000 | 73.319 | 187.251 | 259.973 | 427.364 | 0.000 | 1.956 | 107.367 | 0.000 | -284.618 | 0.000 | -124.227 | -0.021 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 17.199 | -57.487 | 0.000 | 0.000 | 11.439 | 29.056 | 40.341 | 22.528 | 0.000 | 0.328 | 0.000 | 0.000 | -40.091 | 0.000 | -20.847 | -2.465 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.804 | -58.251 | 0.000 | 0.000 | 7.386 | 18.725 | 25.998 | 41.993 | 0.000 | 0.239 | 0.001 | 0.000 | -24.983 | 0.000 | -13.971 | -6.940 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 11.391 | -85.700 | 0.000 | 0.000 | 11.095 | 29.057 | 40.342 | 80.798 | 0.000 | 0.314 | 0.001 | 0.000 | -38.453 | 0.000 | -21.996 | -26.848 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 7.592 | -64.452 | 0.000 | 0.000 | 7.458 | 18.725 | 25.997 | 42.937 | 0.000 | 0.239 | 2.754 | 0.000 | -26.756 | 0.000 | -14.494 | -0.002 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -136.179 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.058 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.987 | -1188.318 | 0.000 | 0.000 | 0.000 | 33.564 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -387.038 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.839 | -109.006 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.070 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.467 | -7170.533 | 0.000 | 0.000 | 0.000 | 72.655 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -397.446 |
GROUNDFLOOR_PLENUM | 1.061 | -69.456 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.201 | 86.911 | 0.000 | 0.000 | 0.000 | -18.718 | 0.000 |
MIDFLOOR_PLENUM | 60.374 | -446.115 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.623 | 697.597 | 0.000 | 0.000 | 0.000 | -315.478 | -0.026 |
TOPFLOOR_PLENUM | 34.115 | -68.955 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.260 | 66.982 | 0.000 | 0.000 | 0.000 | -32.403 | -0.003 |
Total Facility | 95.550 | -584.526 | 199.204 | -18805.357 | 0.000 | 0.000 | 1523.182 | 4294.357 | 15213.288 | 2240.834 | 0.000 | 15.199 | 1315.328 | 0.000 | -1683.943 | 0.000 | -1085.254 | -2737.894 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-DEC-15:00 | 0.00 | 0.00 | 0.00 | -126848.03 | 0.00 | 0.00 | 402.74 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 111743.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 06-SEP-03:02 | 0.00 | 0.00 | 0.00 | -101284.09 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.15 | 0.00 | 0.00 | 0.00 | 92017.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 | -937546.36 | 0.00 | 0.00 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 844884.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-03:03 | 0.00 | 0.00 | 0.00 | -97050.06 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.12 | 0.00 | 0.00 | 0.00 | 87783.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 14-SEP-03:01 | 0.00 | 0.00 | 0.00 | -13505.56 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.70 | 0.00 | 0.00 | 0.00 | 13036.73 | 0.00 | -602.54 | 0.00 | -92.13 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-08:52 | 0.00 | 0.00 | 0.00 | -19541.41 | 0.00 | 0.00 | 22.98 | 90.44 | 488.98 | 13723.12 | 0.00 | 0.00 | 5252.83 | 0.00 | -0.00 | 0.00 | -36.94 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-11:43 | 0.00 | 0.00 | 0.00 | -18950.76 | 0.00 | 0.00 | 39.22 | 140.34 | 758.78 | 18149.50 | 0.00 | 0.00 | 82.39 | 0.00 | -0.00 | 0.00 | -219.46 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-16:41 | 0.00 | 0.00 | 0.00 | -24240.95 | 0.00 | 0.00 | 19.85 | 90.44 | 488.98 | 11904.96 | 0.00 | 0.00 | 11800.88 | 0.00 | -0.00 | 0.00 | -64.16 | 0.00 |
PERIMETER_MID_ZN_3 | 10-JUL-03:58 | 0.00 | 0.00 | 0.00 | -132506.29 | 0.00 | 0.00 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 295.95 | 121159.26 | 0.00 | -583.98 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:42 | 0.00 | 0.00 | 0.00 | -209713.70 | 0.00 | 0.00 | 219.50 | 904.36 | 4889.82 | 136397.35 | 0.00 | 0.00 | 68397.88 | 0.00 | -0.00 | 0.00 | -1095.20 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:52 | 0.00 | 0.00 | 0.00 | -189101.85 | 0.00 | 0.00 | 366.11 | 1403.36 | 7587.84 | 174631.03 | 0.00 | 0.00 | 6415.93 | 0.00 | -0.00 | 0.00 | -1302.42 | 0.00 |
PERIMETER_MID_ZN_4 | 18-JUN-17:41 | 0.00 | 0.00 | 0.00 | -206328.93 | 0.00 | 0.00 | 0.00 | 978.32 | 4889.79 | 82109.24 | 0.00 | 0.00 | 121196.06 | 0.00 | -0.00 | 0.00 | -2844.47 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-03:01 | 0.00 | 0.00 | 0.00 | -14567.63 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.70 | 0.00 | 0.00 | 0.00 | 14554.81 | 0.00 | -883.38 | 0.00 | -267.31 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-08:51 | 0.00 | 0.00 | 0.00 | -20621.65 | 0.00 | 0.00 | 21.98 | 90.44 | 488.98 | 13033.59 | 0.00 | 0.00 | 7086.25 | 0.00 | -0.00 | 0.00 | -99.58 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:41 | 0.00 | 0.00 | 0.00 | -20848.50 | 0.00 | 0.00 | 35.32 | 140.34 | 758.78 | 16017.00 | 0.00 | 0.00 | 4055.14 | 0.00 | -0.00 | 0.00 | -158.08 | 0.00 |
PERIMETER_TOP_ZN_4 | 18-JUN-17:41 | 0.00 | 0.00 | 0.00 | -22370.80 | 0.00 | 0.00 | 0.00 | 97.83 | 488.98 | 8147.57 | 0.00 | 0.00 | 14006.17 | 0.00 | -0.00 | 0.00 | -369.76 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:47 | 0.00 | 0.00 | 0.00 | -7637.15 | 0.00 | 0.00 | 0.00 | 17.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -174.81 |
DATACENTER_MID_ZN_6 | 12-APR-17:20 | 0.00 | 0.00 | 0.00 | -72519.09 | 0.00 | 0.00 | 0.00 | 972.60 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6397.73 |
DATACENTER_TOP_ZN_6 | 12-APR-17:20 | 0.00 | 0.00 | 0.00 | -7361.97 | 0.00 | 0.00 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -529.71 |
DATACENTER_BASEMENT_ZN_6 | 18-MAR-17:22 | 0.00 | 0.00 | 0.00 | -415454.76 | 0.00 | 0.00 | 0.00 | 350.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 130379.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-SEP-05:01 | 0.00 | -9870.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9899.55 | 0.00 | -0.00 | 0.00 | -29.16 | 0.00 |
MIDFLOOR_PLENUM | 12-JUL-05:01 | 0.00 | -97806.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98080.99 | 0.00 | -0.00 | 0.00 | -274.75 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:50 | 0.00 | -22658.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.37 | 22404.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-AUG-03:01 | 0.00 | 88709.73 | 0.00 | -2073059.88 | 0.00 | 0.00 | 0.00 | 22436.48 | 623236.89 | 0.00 | 0.00 | 0.00 | 1370042.88 | 0.00 | -26595.39 | 0.00 | -4770.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-JUL-13:40 | 0.00 | 0.00 | 151984.97 | 0.00 | 0.00 | 0.00 | 400.25 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -167087.27 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 464324.54 | -0.00 | 0.00 | 0.00 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -556986.35 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 84420.91 | -0.00 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -93687.09 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 9699.20 | -0.00 | 0.00 | 0.00 | 0.00 | 303.62 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5638.64 | 0.00 | -2203.57 | -3172.31 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 7422.99 | -0.00 | 0.00 | 0.00 | 0.00 | 195.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3623.05 | 0.00 | -1447.59 | -3199.99 |
PERIMETER_BOT_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 12608.30 | -0.00 | 0.00 | 0.00 | 0.00 | 303.63 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5235.24 | 0.00 | -2126.25 | -6562.14 |
PERIMETER_BOT_ZN_4 | 14-JAN-06:01 | 0.00 | 0.00 | 5502.37 | -0.00 | 0.00 | 0.00 | 94.15 | 180.87 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3122.14 | 0.00 | -376.37 | -2930.85 |
PERIMETER_MID_ZN_3 | 06-FEB-04:11 | 0.00 | 0.00 | 137098.91 | -0.00 | 0.00 | 0.00 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49384.82 | 0.00 | -39499.24 | -59849.92 |
PERIMETER_MID_ZN_2 | 06-FEB-04:11 | 0.00 | 0.00 | 156359.40 | -0.00 | 0.00 | 0.00 | 0.00 | 978.32 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31983.67 | 0.00 | -26725.27 | -105148.53 |
PERIMETER_MID_ZN_1 | 01-JAN-07:22 | 0.00 | 0.00 | 154021.18 | -0.00 | 0.00 | 0.00 | 891.41 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19450.70 | 0.00 | -25864.35 | -118588.75 |
PERIMETER_MID_ZN_4 | 02-JAN-00:41 | 0.00 | 0.00 | 153450.01 | -0.00 | 0.00 | 0.00 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29398.14 | 0.00 | -26398.21 | -105151.69 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:11 | 0.00 | 0.00 | 16402.69 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4631.66 | 0.00 | -4658.32 | -8276.22 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:11 | 0.00 | 0.00 | 18408.90 | -0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2997.68 | 0.00 | -3148.05 | -13012.97 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:11 | 0.00 | 0.00 | 18485.57 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4542.03 | 0.00 | -4713.72 | -10393.34 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:11 | 0.00 | 0.00 | 19251.72 | -0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3159.04 | 0.00 | -3205.64 | -13636.85 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-23:20 | 0.00 | 0.00 | 5294.06 | 0.00 | 0.00 | 0.00 | 0.00 | 162.10 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24942.21 |
DATACENTER_TOP_ZN_6 | 16-JAN-17:50 | 0.00 | 0.00 | 567.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2532.70 |
DATACENTER_BASEMENT_ZN_6 | 13-JAN-22:32 | 0.00 | 0.00 | 43602.49 | 0.00 | 0.00 | 0.00 | 0.00 | 701.80 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -139212.41 |
GROUNDFLOOR_PLENUM | 26-DEC-04:01 | 13701.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -922.69 | -12778.86 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 166882.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6572.24 | -160310.12 |
TOPFLOOR_PLENUM | 06-FEB-05:10 | 31427.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7774.36 | -23653.01 |
Total Facility | 02-JAN-04:01 | -156089.29 | 203199.98 | 1210298.80 | -203199.98 | 0.00 | 0.00 | 0.00 | 22436.48 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -177637.59 | 0.00 | -78214.48 | -1089156.61 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.7774 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.7774 | 0.2077 | 1.0000 | 1.2001 | 0.2077 | ||
VAV_BOT WITH REHEAT | 10.3617 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.7165 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 97.7439 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 90.7529 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2308 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.5699 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.2696 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.2696 | 0.0159 | 1.0000 | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4698 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4698 | 0.0333 | 1.0000 | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4789 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4789 | 0.0349 | 1.0000 | 0.1563 | 0.0349 | ||
AIRLOOP DATACENTER TOP | 0.4577 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4577 | 0.0341 | 1.0000 | 0.0156 | 0.0341 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.7774 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.7774 | 1.0000 | 1.0000 | 1.2001 | 0.2077 | ||
VAV_BOT WITH REHEAT | 5.1809 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.1085 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.8719 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 29.3232 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1154 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.0692 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.2696 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.2696 | 1.0000 | 1.0000 | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4698 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4698 | 1.0000 | 1.0000 | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4789 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4789 | 1.0000 | 1.0000 | 0.1563 | 0.0349 | ||
AIRLOOP DATACENTER TOP | 0.4577 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4577 | 1.0000 | 1.0000 | 0.0156 | 0.0341 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.7774 | 5.7774 | 5.7774 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9837 | 5.9837 | 1.7951 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.3534 | 56.3534 | 16.9060 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7377 | 5.7377 | 1.7213 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9370 | 0.9370 | 0.2811 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0688 | 1.0688 | 0.3206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0636 | 1.0636 | 0.3191 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3086 | 1.3086 | 0.3926 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8055 | 8.8055 | 2.6416 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1396 | 11.1396 | 3.3419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0297 | 10.0297 | 3.0089 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4157 | 11.4157 | 3.4247 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9945 | 0.9945 | 0.2984 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1337 | 1.1337 | 0.3401 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1342 | 1.1342 | 0.3403 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2308 | 1.2308 | 0.3692 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4698 | 0.4698 | 0.4698 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4789 | 4.4789 | 4.4789 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4577 | 0.4577 | 0.4577 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.2696 | 21.2696 | 21.2696 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.7774 | 5.7774 | 5.7774 | 5.7774 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 10.3617 | 9.7165 | 10.3617 | 3.1085 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 97.7439 | 90.7529 | 97.7439 | 29.3232 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2308 | 9.5699 | 10.2308 | 3.0692 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2696 | 21.2696 | 21.2696 | 21.2696 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4698 | 0.4698 | 0.4698 | 0.4698 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4789 | 4.4789 | 4.4789 | 4.4789 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4577 | 0.4577 | 0.4577 | 0.4577 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.7774 | 5.7774 | 5.7774 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9919 | 2.9919 | 1.7951 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1767 | 28.1767 | 16.9060 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8689 | 2.8689 | 1.7213 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4685 | 0.4685 | 0.2811 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5344 | 0.5344 | 0.3206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5318 | 0.5318 | 0.3191 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6543 | 0.6543 | 0.3926 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4027 | 4.4027 | 2.6416 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5698 | 5.5698 | 3.3419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0149 | 5.0149 | 3.0089 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7078 | 5.7078 | 3.4247 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4973 | 0.4973 | 0.2984 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5668 | 0.5668 | 0.3401 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5671 | 0.5671 | 0.3403 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6154 | 0.6154 | 0.3692 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4698 | 0.4698 | 0.4698 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4789 | 4.4789 | 4.4789 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4577 | 0.4577 | 0.4577 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.2696 | 21.2696 | 21.2696 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.7774 | 5.7774 | 5.7774 | 5.7774 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 5.1809 | 3.1085 | 3.1085 | 3.1085 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.8719 | 29.3232 | 29.3232 | 29.3232 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1154 | 3.0692 | 3.0692 | 3.0692 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2696 | 21.2696 | 21.2696 | 21.2696 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4698 | 0.4698 | 0.4698 | 0.4698 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4789 | 4.4789 | 4.4789 | 4.4789 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4577 | 0.4577 | 0.4577 | 0.4577 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 20:00:28
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 31.33 |
Number of hours cooling loads not met | 234.67 |
Number of hours not met | 266.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 1393.40 | 2550782.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1260.78 | 353658.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2496.42 | 168893.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 4294.36 | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 883.65 | 56280.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.73 | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.27 | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2220.34 | 236609.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 647.95 | 78337.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 245.98 | 46449.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 946.57 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 25.58 | 38049.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 22.55 | 2110.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 592.14 | 83901.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 30301.55 |
Natural Gas | 0.00 | 1985.54 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 32287.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 92.71 |
Space Heating | 0.00 |
Space Cooling | 81.11 |
Fans (All) | 47.93 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 654.17 |
Subtotal | 654.17 |
Natural Gas [MJ/m2] | |
Space Heating | 30.08 |
Service Water Heating | 12.78 |
Miscellaneous (All) | 42.87 |
Subtotal | 42.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.30 |
Space Heating | 4.32 |
Space Cooling | 11.64 |
Fans (All) | 6.88 |
Service Water Heating | 1.83 |
Receptacle Equipment | 47.12 |
Miscellaneous | 14.92 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2728. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.405982E+12 |
February | 0.000 | 0.324517E+12 |
March | 0.000 | 0.174730E+12 |
April | 0.000 | 0.564149E+11 |
May | 0.000 | 0.460604E+10 |
June | 0.000 | 0.151333E+10 |
July | 0.000 | 0.153087E+10 |
August | 0.000 | 0.128476E+10 |
September | 0.000 | 0.159071E+10 |
October | 0.000 | 0.197334E+11 |
November | 0.000 | 0.134232E+12 |
December | 0.000 | 0.267265E+12 |
Annual Sum or Average | 0.139340E+13 | |
Minimum of Months | 0.000 | 0.128476E+10 |
Maximum of Months | 0.000 | 0.405982E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538618E+11 | 124893.86 | 02-JAN-02:46 | -11.7 | -13.2 | 0.566028E+10 | 7499.16 | 20-JAN-14:30 | 7.50 | 3.79 |
February | 0.500476E+11 | 125704.38 | 20-FEB-15:53 | 7.20 | 4.43 | 0.513594E+10 | 7499.13 | 28-FEB-10:20 | 7.03 | 6.58 |
March | 0.622150E+11 | 122538.98 | 21-MAR-03:50 | 6.02 | 5.83 | 0.613348E+10 | 7499.16 | 09-MAR-14:20 | 3.13 | 3.00 |
April | 0.590785E+11 | 124695.18 | 24-APR-03:01 | 7.88 | 7.53 | 0.545090E+10 | 7499.17 | 07-APR-13:00 | 26.10 | 15.93 |
May | 0.618854E+11 | 119870.14 | 01-MAY-02:61 | 8.43 | 5.63 | 0.590227E+10 | 7499.55 | 25-MAY-09:20 | 16.87 | 13.21 |
June | 0.647880E+11 | 119917.48 | 04-JUN-18:53 | 18.90 | 13.67 | 0.588426E+10 | 7499.29 | 23-JUN-09:00 | 30.00 | 18.37 |
July | 0.662903E+11 | 108677.05 | 16-JUL-22:47 | 25.37 | 20.12 | 0.547634E+10 | 7499.22 | 12-JUL-09:09 | 27.30 | 18.59 |
August | 0.732181E+11 | 111413.38 | 20-AUG-09:52 | 23.90 | 15.36 | 0.614006E+10 | 7499.18 | 09-AUG-09:20 | 26.10 | 17.24 |
September | 0.662644E+11 | 121284.36 | 10-SEP-18:47 | 20.78 | 11.47 | 0.545470E+10 | 7499.25 | 01-SEP-13:39 | 30.93 | 17.67 |
October | 0.702046E+11 | 126110.59 | 29-OCT-17:00 | 12.20 | 7.38 | 0.567395E+10 | 7499.50 | 16-OCT-09:20 | 17.07 | 14.17 |
November | 0.654184E+11 | 126505.84 | 11-NOV-15:20 | 13.13 | 10.80 | 0.561731E+10 | 7499.13 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.620407E+11 | 126867.90 | 25-DEC-15:00 | 10.00 | 8.28 | 0.547226E+10 | 7499.16 | 06-DEC-14:09 | 3.40 | -0.5 |
Annual Sum or Average | 0.755313E+12 | 0.680018E+11 | ||||||||
Minimum of Months | 0.500476E+11 | 108677.05 | -11.7 | -13.2 | 0.513594E+10 | 7499.13 | 3.13 | -0.5 | ||
Maximum of Months | 0.732181E+11 | 126867.90 | 25.37 | 20.12 | 0.614006E+10 | 7499.55 | 30.93 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391142E+11 | 68069.77 | 26-JAN-06:01 | -1.0 | -3.1 | 0.506276E+10 | 6734.94 | 03-JAN-10:00 | 12.00 | 11.46 |
February | 0.390809E+11 | 74732.33 | 21-FEB-04:02 | 1.78 | 1.01 | 0.460108E+10 | 6734.82 | 28-FEB-10:09 | 7.12 | 6.62 |
March | 0.551653E+11 | 76063.27 | 28-MAR-03:02 | 10.00 | 7.99 | 0.550200E+10 | 6734.88 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.581051E+11 | 82034.21 | 27-APR-03:02 | 13.22 | 11.36 | 0.488426E+10 | 6734.82 | 05-APR-09:09 | 11.28 | 8.50 |
May | 0.572053E+11 | 95911.96 | 30-MAY-03:03 | 18.22 | 15.07 | 0.528536E+10 | 6735.07 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.649105E+11 | 93862.05 | 28-JUN-03:02 | 18.98 | 18.21 | 0.526925E+10 | 6734.70 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.715314E+11 | 89620.47 | 01-JUL-03:01 | 20.00 | 19.64 | 0.489209E+10 | 6734.46 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.801656E+11 | 89010.54 | 24-AUG-05:02 | 21.10 | 18.14 | 0.549258E+10 | 6734.75 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.573144E+11 | 101292.09 | 06-SEP-03:02 | 21.60 | 19.31 | 0.488123E+10 | 6734.96 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.582388E+11 | 93779.48 | 06-OCT-03:02 | 19.40 | 17.99 | 0.508003E+10 | 6735.14 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.517511E+11 | 79450.13 | 06-NOV-04:01 | 5.00 | 2.82 | 0.503605E+10 | 6734.90 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.509663E+11 | 76483.03 | 26-DEC-04:02 | 5.60 | 4.99 | 0.490335E+10 | 6734.81 | 06-DEC-14:00 | 3.90 | -0.3 |
Annual Sum or Average | 0.683549E+12 | 0.608900E+11 | ||||||||
Minimum of Months | 0.390809E+11 | 68069.77 | -1.0 | -3.1 | 0.460108E+10 | 6734.46 | 3.90 | -0.3 | ||
Maximum of Months | 0.801656E+11 | 101292.09 | 21.60 | 19.64 | 0.550200E+10 | 6735.14 | 25.68 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251805E+11 | 62911.20 | 30-JAN-11:47 | 0.92 | -2.2 | 0.479856E+10 | 6900.76 | 26-JAN-10:20 | 2.57 | -0.6 |
February | 0.258377E+11 | 63256.30 | 21-FEB-13:10 | 3.90 | 2.68 | 0.447524E+10 | 6973.81 | 22-FEB-10:39 | 1.67 | -2.2 |
March | 0.361643E+11 | 65186.48 | 08-MAR-17:15 | 2.03 | 1.70 | 0.545586E+10 | 6931.85 | 08-MAR-13:20 | 2.20 | 1.78 |
April | 0.377871E+11 | 70018.54 | 28-APR-04:03 | 14.22 | 11.80 | 0.485739E+10 | 6753.25 | 03-APR-09:00 | 7.80 | 2.86 |
May | 0.470511E+11 | 79358.96 | 30-MAY-03:01 | 18.22 | 15.07 | 0.527255E+10 | 6735.02 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.519224E+11 | 85666.37 | 30-JUN-03:01 | 21.60 | 19.30 | 0.526237E+10 | 6734.71 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.528500E+11 | 91502.78 | 24-JUL-03:03 | 22.02 | 21.19 | 0.488706E+10 | 6734.46 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.575275E+11 | 93762.22 | 07-AUG-03:02 | 18.80 | 17.42 | 0.549347E+10 | 6734.74 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.475252E+11 | 85537.64 | 14-SEP-03:01 | 22.20 | 21.85 | 0.486967E+10 | 6734.93 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.438330E+11 | 81050.49 | 06-OCT-04:02 | 19.40 | 18.28 | 0.506287E+10 | 6735.06 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.329883E+11 | 72197.33 | 10-NOV-06:01 | 14.60 | 14.60 | 0.498039E+10 | 6913.43 | 24-NOV-14:30 | 1.95 | -1.5 |
December | 0.299255E+11 | 65252.69 | 12-DEC-16:30 | 4.45 | 3.10 | 0.481905E+10 | 7005.03 | 13-DEC-10:00 | 3.20 | 0.03 |
Annual Sum or Average | 0.488593E+12 | 0.602345E+11 | ||||||||
Minimum of Months | 0.251805E+11 | 62911.20 | 0.92 | -2.2 | 0.447524E+10 | 6734.46 | 1.67 | -2.2 | ||
Maximum of Months | 0.575275E+11 | 93762.22 | 22.20 | 21.85 | 0.549347E+10 | 7005.03 | 26.20 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184976E+11 | 25122.66 | 20-JAN-16:50 | 5.87 | 3.29 | 0.432031E+10 | 6734.79 | 20-JAN-14:30 | 7.50 | 3.79 |
February | 0.178823E+11 | 26622.79 | 24-FEB-17:00 | 6.70 | 1.40 | 0.396601E+10 | 6734.73 | 02-FEB-14:09 | 5.50 | -0.7 |
March | 0.272322E+11 | 38677.41 | 03-MAR-15:00 | 15.00 | 8.37 | 0.514301E+10 | 6734.74 | 10-MAR-14:39 | 6.30 | 3.00 |
April | 0.320478E+11 | 70005.20 | 07-APR-05:02 | 14.82 | 12.60 | 0.473057E+10 | 6734.72 | 05-APR-09:39 | 11.83 | 9.10 |
May | 0.448468E+11 | 82909.88 | 30-MAY-03:01 | 18.22 | 15.07 | 0.523400E+10 | 6735.00 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.550548E+11 | 96480.95 | 20-JUN-03:02 | 22.02 | 19.38 | 0.525681E+10 | 6734.64 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.583476E+11 | 97061.65 | 24-JUL-03:03 | 22.02 | 21.19 | 0.489075E+10 | 6734.45 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.619847E+11 | 95870.68 | 18-AUG-03:02 | 25.50 | 18.50 | 0.549084E+10 | 6734.76 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.461584E+11 | 90237.14 | 05-SEP-04:02 | 20.52 | 17.92 | 0.484267E+10 | 6734.89 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.366441E+11 | 80494.72 | 06-OCT-05:01 | 19.40 | 18.22 | 0.496387E+10 | 6734.96 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.232696E+11 | 37640.20 | 03-NOV-15:50 | 15.37 | 10.38 | 0.463481E+10 | 6734.78 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.197317E+11 | 23665.69 | 20-DEC-17:00 | 6.70 | 3.51 | 0.429969E+10 | 6734.62 | 21-DEC-14:39 | 3.30 | -1.4 |
Annual Sum or Average | 0.441698E+12 | 0.577733E+11 | ||||||||
Minimum of Months | 0.178823E+11 | 23665.69 | 5.87 | 1.40 | 0.396601E+10 | 6734.45 | 3.30 | -1.4 | ||
Maximum of Months | 0.619847E+11 | 97061.65 | 25.50 | 21.19 | 0.549084E+10 | 6735.00 | 25.68 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310747E+10 | 3021.36 | 20-JAN-14:40 | 7.60 | 3.85 | 0.562739E+09 | 845.63 | 20-JAN-14:30 | 7.50 | 3.79 |
February | 0.300632E+10 | 3463.36 | 24-FEB-14:10 | 9.22 | 3.10 | 0.515184E+09 | 845.62 | 21-FEB-14:50 | 3.90 | 2.91 |
March | 0.496945E+10 | 6971.68 | 27-MAR-13:30 | 20.85 | 16.75 | 0.667072E+09 | 845.64 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.649772E+10 | 7912.58 | 26-APR-13:50 | 18.30 | 12.82 | 0.604413E+09 | 845.64 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.787517E+10 | 12222.09 | 30-MAY-03:01 | 18.22 | 15.07 | 0.660217E+09 | 845.67 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.104776E+11 | 12865.96 | 26-JUN-03:01 | 21.02 | 16.53 | 0.661253E+09 | 845.63 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.122877E+11 | 13365.09 | 07-JUL-05:02 | 25.68 | 21.68 | 0.614840E+09 | 845.60 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.132185E+11 | 13224.68 | 18-AUG-05:02 | 25.00 | 18.88 | 0.689577E+09 | 845.64 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.816024E+10 | 13508.88 | 14-SEP-03:01 | 22.20 | 21.85 | 0.609961E+09 | 845.65 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.684979E+10 | 10144.67 | 23-OCT-05:03 | 13.22 | 10.94 | 0.630542E+09 | 845.67 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.456991E+10 | 5933.69 | 03-NOV-13:40 | 17.60 | 10.63 | 0.612374E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.387291E+10 | 4643.92 | 26-DEC-13:30 | 9.45 | 5.01 | 0.580620E+09 | 845.62 | 05-DEC-14:30 | 4.70 | 3.36 |
Annual Sum or Average | 0.848928E+11 | 0.740879E+10 | ||||||||
Minimum of Months | 0.300632E+10 | 3021.36 | 7.60 | 3.10 | 0.515184E+09 | 845.60 | 3.90 | 2.91 | ||
Maximum of Months | 0.132185E+11 | 13508.88 | 25.68 | 21.85 | 0.689577E+09 | 845.67 | 25.68 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301930E+10 | 4099.42 | 19-JAN-09:25 | 6.10 | 3.62 | 0.344560E+09 | 544.94 | 19-JAN-10:09 | 7.80 | 4.24 |
February | 0.301578E+10 | 5391.65 | 22-FEB-09:05 | 0.10 | -3.1 | 0.318862E+09 | 544.95 | 22-FEB-10:30 | 1.40 | -2.4 |
March | 0.490339E+10 | 8502.27 | 29-MAR-08:40 | 5.20 | 2.68 | 0.412157E+09 | 544.95 | 01-MAR-10:50 | 13.90 | 7.29 |
April | 0.602555E+10 | 10381.48 | 06-APR-08:20 | 14.60 | 12.54 | 0.378214E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.55 |
May | 0.755697E+10 | 18550.55 | 29-MAY-08:22 | 25.00 | 16.72 | 0.417547E+09 | 545.00 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.891825E+10 | 12521.85 | 26-JUN-08:00 | 23.90 | 18.06 | 0.420113E+09 | 544.97 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.103444E+11 | 19543.49 | 02-JUL-08:52 | 25.60 | 21.65 | 0.391470E+09 | 544.95 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.114938E+11 | 13908.88 | 20-AUG-09:22 | 22.80 | 15.07 | 0.440537E+09 | 544.96 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.752292E+10 | 18491.53 | 04-SEP-08:12 | 23.17 | 18.66 | 0.385477E+09 | 544.98 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.636480E+10 | 9357.91 | 09-OCT-08:41 | 10.32 | 6.05 | 0.399466E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.416705E+10 | 5938.31 | 02-NOV-08:50 | 10.82 | 5.70 | 0.373284E+09 | 544.95 | 06-NOV-10:09 | 9.18 | 5.16 |
December | 0.363856E+10 | 4371.01 | 20-DEC-09:20 | 6.83 | 4.41 | 0.343615E+09 | 544.94 | 26-DEC-10:09 | 8.40 | 5.01 |
Annual Sum or Average | 0.769708E+11 | 0.462530E+10 | ||||||||
Minimum of Months | 0.301578E+10 | 4099.42 | 0.10 | -3.1 | 0.318862E+09 | 544.94 | 1.40 | -2.4 | ||
Maximum of Months | 0.114938E+11 | 19543.49 | 25.60 | 21.65 | 0.440537E+09 | 545.00 | 25.68 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481049E+10 | 12066.16 | 17-JAN-13:30 | 10.55 | 5.36 | 0.577367E+09 | 902.24 | 19-JAN-14:09 | 9.32 | 3.66 |
February | 0.507866E+10 | 12018.34 | 22-FEB-13:20 | 4.27 | -0.9 | 0.537121E+09 | 913.91 | 22-FEB-14:09 | 4.90 | -0.5 |
March | 0.763611E+10 | 13646.47 | 01-MAR-13:20 | 13.90 | 6.50 | 0.665587E+09 | 937.66 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.780821E+10 | 13828.87 | 07-APR-12:30 | 26.15 | 15.88 | 0.597532E+09 | 845.66 | 10-APR-13:09 | 20.10 | 10.08 |
May | 0.848295E+10 | 13842.54 | 30-MAY-03:01 | 18.22 | 15.07 | 0.656691E+09 | 845.69 | 15-MAY-13:50 | 18.27 | 11.31 |
June | 0.110616E+11 | 14134.93 | 26-JUN-03:01 | 21.02 | 16.53 | 0.659874E+09 | 845.64 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.132799E+11 | 17239.53 | 30-JUL-14:12 | 26.67 | 23.47 | 0.614442E+09 | 845.62 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.157121E+11 | 18175.17 | 27-AUG-12:32 | 27.97 | 22.64 | 0.690395E+09 | 896.41 | 30-AUG-13:09 | 27.48 | 15.57 |
September | 0.112709E+11 | 18949.05 | 10-SEP-11:43 | 22.70 | 13.56 | 0.613154E+09 | 944.42 | 28-SEP-13:09 | 22.98 | 13.53 |
October | 0.116757E+11 | 18583.77 | 15-OCT-14:41 | 20.68 | 12.93 | 0.642687E+09 | 978.42 | 30-OCT-13:20 | 15.77 | 9.68 |
November | 0.715623E+10 | 14757.84 | 02-NOV-13:20 | 15.77 | 8.35 | 0.617701E+09 | 974.06 | 02-NOV-13:09 | 15.68 | 8.27 |
December | 0.622738E+10 | 16411.62 | 17-DEC-12:02 | 12.20 | 4.55 | 0.582130E+09 | 926.23 | 21-DEC-14:09 | 3.30 | -1.3 |
Annual Sum or Average | 0.110200E+12 | 0.745468E+10 | ||||||||
Minimum of Months | 0.481049E+10 | 12018.34 | 4.27 | -0.9 | 0.537121E+09 | 845.62 | 3.30 | -1.3 | ||
Maximum of Months | 0.157121E+11 | 18949.05 | 27.97 | 23.47 | 0.690395E+09 | 978.42 | 27.48 | 16.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427314E+10 | 6620.15 | 20-JAN-15:50 | 7.30 | 3.82 | 0.352495E+09 | 544.94 | 27-JAN-14:00 | 5.60 | 2.71 |
February | 0.460504E+10 | 8999.17 | 24-FEB-15:30 | 8.05 | 2.02 | 0.334869E+09 | 544.95 | 02-FEB-14:09 | 5.50 | -0.7 |
March | 0.780541E+10 | 18801.60 | 26-MAR-16:42 | 10.78 | 9.70 | 0.435624E+09 | 544.97 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.982416E+10 | 21750.16 | 09-APR-16:22 | 16.65 | 13.96 | 0.393989E+09 | 544.97 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.920350E+10 | 19939.06 | 14-MAY-16:22 | 13.30 | 9.03 | 0.420512E+09 | 544.99 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.122854E+11 | 23255.31 | 18-JUN-16:02 | 25.50 | 22.07 | 0.425430E+09 | 544.96 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.147427E+11 | 24241.21 | 04-JUL-16:41 | 25.18 | 18.18 | 0.396431E+09 | 544.94 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.178121E+11 | 23973.92 | 20-AUG-16:01 | 25.50 | 16.87 | 0.445267E+09 | 544.98 | 08-AUG-13:30 | 26.40 | 17.03 |
September | 0.942448E+10 | 22346.95 | 03-SEP-16:41 | 24.50 | 16.30 | 0.387727E+09 | 544.97 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.892765E+10 | 21276.00 | 15-OCT-16:01 | 19.22 | 12.10 | 0.406613E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.630228E+10 | 15210.88 | 04-NOV-03:01 | 10.10 | 9.12 | 0.398329E+09 | 544.98 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.613432E+10 | 10725.17 | 25-DEC-14:14 | 10.00 | 8.63 | 0.387005E+09 | 544.96 | 29-DEC-14:00 | 3.90 | 3.16 |
Annual Sum or Average | 0.111340E+12 | 0.478429E+10 | ||||||||
Minimum of Months | 0.427314E+10 | 6620.15 | 7.30 | 2.02 | 0.334869E+09 | 544.94 | 3.90 | -0.7 | ||
Maximum of Months | 0.178121E+11 | 24241.21 | 25.50 | 22.07 | 0.445267E+09 | 544.99 | 26.40 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120379E+10 | 4347.23 | 19-JAN-09:35 | 6.67 | 3.81 | 0.485331E+09 | 755.89 | 20-JAN-14:30 | 7.50 | 3.79 |
February | 0.121325E+10 | 5456.92 | 21-FEB-14:33 | 3.90 | 2.86 | 0.445239E+09 | 767.12 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.282610E+10 | 4254.62 | 27-MAR-16:00 | 22.20 | 16.33 | 0.590294E+09 | 845.60 | 28-MAR-13:09 | 13.80 | 8.63 |
April | 0.387629E+10 | 6380.39 | 07-APR-14:00 | 26.10 | 15.93 | 0.569348E+09 | 845.63 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.631156E+10 | 10274.87 | 30-MAY-05:03 | 18.17 | 14.30 | 0.650854E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.856944E+10 | 12828.50 | 22-JUN-05:02 | 22.88 | 15.42 | 0.659230E+09 | 845.63 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.957840E+10 | 13252.66 | 10-JUL-03:58 | 26.10 | 21.50 | 0.614589E+09 | 845.60 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.990353E+10 | 13162.28 | 05-AUG-03:01 | 25.60 | 23.68 | 0.689105E+09 | 845.64 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.674078E+10 | 12720.79 | 02-SEP-05:02 | 22.12 | 16.29 | 0.603681E+09 | 845.65 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.490163E+10 | 6541.21 | 05-OCT-14:00 | 23.30 | 18.85 | 0.608934E+09 | 845.61 | 19-OCT-13:00 | 15.60 | 10.52 |
November | 0.255275E+10 | 4432.53 | 13-NOV-08:20 | 6.30 | 5.16 | 0.539586E+09 | 845.63 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.160862E+10 | 5139.43 | 12-DEC-16:30 | 4.45 | 3.10 | 0.480184E+09 | 764.21 | 20-DEC-14:30 | 9.15 | 5.46 |
Annual Sum or Average | 0.592861E+11 | 0.693637E+10 | ||||||||
Minimum of Months | 0.120379E+10 | 4254.62 | 3.90 | 2.86 | 0.445239E+09 | 755.89 | 7.50 | 2.25 | ||
Maximum of Months | 0.990353E+10 | 13252.66 | 26.10 | 23.68 | 0.689105E+09 | 845.66 | 26.60 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127812E+10 | 6006.95 | 19-JAN-09:35 | 6.67 | 3.81 | 0.225175E+09 | 471.25 | 27-JAN-09:50 | 4.22 | 1.39 |
February | 0.154222E+10 | 4582.62 | 02-FEB-09:50 | 4.82 | 0.65 | 0.208410E+09 | 502.12 | 22-FEB-09:50 | 0.50 | -3.0 |
March | 0.343921E+10 | 11360.35 | 14-MAR-09:43 | 2.52 | -2.2 | 0.275905E+09 | 529.14 | 24-MAR-08:00 | 7.20 | 3.82 |
April | 0.457404E+10 | 10163.69 | 28-APR-08:40 | 15.53 | 8.73 | 0.263810E+09 | 534.25 | 12-APR-08:09 | 5.78 | 0.37 |
May | 0.701989E+10 | 20970.51 | 29-MAY-08:42 | 25.73 | 16.71 | 0.297867E+09 | 521.24 | 30-MAY-14:30 | 28.85 | 17.06 |
June | 0.817276E+10 | 20026.75 | 25-JUN-08:52 | 25.60 | 23.63 | 0.303582E+09 | 521.23 | 22-JUN-14:09 | 30.10 | 17.74 |
July | 0.898911E+10 | 20845.76 | 09-JUL-09:12 | 28.87 | 25.20 | 0.287292E+09 | 521.20 | 11-JUL-14:50 | 28.40 | 17.61 |
August | 0.993491E+10 | 17687.01 | 20-AUG-09:12 | 22.43 | 14.97 | 0.323204E+09 | 522.81 | 22-AUG-15:09 | 29.90 | 17.44 |
September | 0.701313E+10 | 19970.69 | 04-SEP-07:52 | 22.80 | 18.70 | 0.275660E+09 | 521.23 | 19-SEP-10:20 | 20.00 | 15.46 |
October | 0.548597E+10 | 9885.63 | 15-OCT-09:11 | 17.57 | 12.45 | 0.280202E+09 | 521.22 | 16-OCT-08:00 | 16.70 | 14.03 |
November | 0.282897E+10 | 5095.80 | 06-NOV-08:07 | 6.38 | 3.39 | 0.243188E+09 | 521.18 | 02-NOV-08:00 | 11.10 | 5.84 |
December | 0.175193E+10 | 4455.95 | 01-DEC-09:55 | 5.60 | 1.49 | 0.221816E+09 | 497.94 | 20-DEC-09:39 | 7.57 | 4.72 |
Annual Sum or Average | 0.620303E+11 | 0.320611E+10 | ||||||||
Minimum of Months | 0.127812E+10 | 4455.95 | 2.52 | -2.2 | 0.208410E+09 | 471.25 | 0.50 | -3.0 | ||
Maximum of Months | 0.993491E+10 | 20970.51 | 28.87 | 25.20 | 0.323204E+09 | 534.25 | 30.10 | 17.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354597E+10 | 13745.40 | 30-JAN-11:47 | 0.92 | -2.2 | 0.547098E+09 | 957.23 | 30-JAN-11:39 | 0.73 | -2.3 |
February | 0.397180E+10 | 15187.77 | 22-FEB-13:05 | 4.08 | -1.0 | 0.515027E+09 | 959.05 | 02-FEB-14:09 | 5.50 | -0.7 |
March | 0.604294E+10 | 14577.89 | 22-MAR-13:30 | 1.70 | -3.3 | 0.639704E+09 | 969.19 | 01-MAR-14:09 | 13.62 | 5.83 |
April | 0.571018E+10 | 13339.36 | 07-APR-12:30 | 26.15 | 15.88 | 0.577141E+09 | 847.82 | 07-APR-13:39 | 26.30 | 16.08 |
May | 0.729867E+10 | 11726.70 | 30-MAY-05:03 | 18.17 | 14.30 | 0.648672E+09 | 845.69 | 15-MAY-13:50 | 18.27 | 11.31 |
June | 0.926937E+10 | 13824.46 | 20-JUN-03:01 | 22.02 | 19.38 | 0.657811E+09 | 845.65 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.105517E+11 | 17221.62 | 30-JUL-14:02 | 26.93 | 23.74 | 0.614048E+09 | 845.62 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.125903E+11 | 16441.01 | 30-AUG-13:30 | 28.05 | 15.53 | 0.691645E+09 | 954.08 | 30-AUG-13:00 | 28.90 | 15.44 |
September | 0.104650E+11 | 18909.69 | 04-SEP-11:52 | 26.10 | 17.77 | 0.614205E+09 | 1004.67 | 28-SEP-13:30 | 23.35 | 13.51 |
October | 0.106863E+11 | 18907.37 | 22-OCT-12:32 | 21.83 | 16.68 | 0.644177E+09 | 1025.08 | 30-OCT-13:39 | 15.93 | 9.65 |
November | 0.570474E+10 | 14612.68 | 02-NOV-13:30 | 15.85 | 8.44 | 0.597552E+09 | 1018.50 | 02-NOV-13:20 | 15.77 | 8.35 |
December | 0.430307E+10 | 15520.36 | 17-DEC-12:53 | 12.20 | 4.93 | 0.552553E+09 | 944.07 | 15-DEC-14:09 | 3.98 | 0.24 |
Annual Sum or Average | 0.901401E+11 | 0.729963E+10 | ||||||||
Minimum of Months | 0.354597E+10 | 11726.70 | 0.92 | -3.3 | 0.515027E+09 | 845.62 | 0.73 | -2.3 | ||
Maximum of Months | 0.125903E+11 | 18909.69 | 28.05 | 23.74 | 0.691645E+09 | 1025.08 | 28.90 | 16.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153107E+10 | 4878.66 | 19-JAN-09:45 | 7.23 | 3.98 | 0.311892E+09 | 521.18 | 20-JAN-16:30 | 6.40 | 3.50 |
February | 0.174581E+10 | 6997.28 | 02-FEB-17:25 | 2.25 | -3.1 | 0.288036E+09 | 531.91 | 17-FEB-14:00 | 6.10 | 1.73 |
March | 0.396020E+10 | 9476.36 | 22-MAR-16:50 | 1.70 | -3.4 | 0.371371E+09 | 544.93 | 07-MAR-14:50 | 10.00 | 5.03 |
April | 0.507597E+10 | 18260.53 | 09-APR-16:11 | 16.83 | 14.02 | 0.350537E+09 | 544.95 | 26-APR-13:00 | 18.30 | 12.91 |
May | 0.710382E+10 | 14033.63 | 27-MAY-17:08 | 21.60 | 11.96 | 0.397715E+09 | 544.99 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.886664E+10 | 20635.21 | 18-JUN-17:41 | 23.58 | 21.53 | 0.414184E+09 | 544.95 | 09-JUN-13:00 | 21.10 | 14.09 |
July | 0.950714E+10 | 20498.26 | 04-JUL-16:31 | 25.37 | 18.14 | 0.390596E+09 | 544.94 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.109407E+11 | 20033.78 | 13-AUG-15:52 | 30.00 | 20.44 | 0.440047E+09 | 544.97 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.733127E+10 | 20394.91 | 10-SEP-16:41 | 22.88 | 12.70 | 0.370797E+09 | 544.95 | 15-SEP-13:00 | 22.80 | 15.48 |
October | 0.601806E+10 | 11180.15 | 04-OCT-15:30 | 23.35 | 19.11 | 0.372664E+09 | 544.92 | 13-OCT-13:00 | 21.70 | 17.44 |
November | 0.298284E+10 | 6310.26 | 03-NOV-15:40 | 15.73 | 10.51 | 0.331386E+09 | 544.89 | 06-NOV-14:00 | 13.30 | 7.70 |
December | 0.203947E+10 | 5371.33 | 28-DEC-14:45 | 2.98 | -0.8 | 0.305673E+09 | 514.38 | 08-DEC-15:00 | 6.10 | 1.86 |
Annual Sum or Average | 0.671030E+11 | 0.434490E+10 | ||||||||
Minimum of Months | 0.153107E+10 | 4878.66 | 1.70 | -3.4 | 0.288036E+09 | 514.38 | 6.10 | 1.73 | ||
Maximum of Months | 0.109407E+11 | 20635.21 | 30.00 | 21.53 | 0.440047E+09 | 544.99 | 26.20 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612409E+09 | 2367.21 | 20-JAN-16:00 | 7.20 | 3.79 | 0.467762E+09 | 695.87 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.591317E+09 | 2404.69 | 17-FEB-16:10 | 6.02 | 1.70 | 0.426599E+09 | 703.95 | 17-FEB-14:00 | 6.10 | 1.73 |
March | 0.215091E+10 | 3964.93 | 27-MAR-16:00 | 22.20 | 16.33 | 0.547167E+09 | 845.59 | 28-MAR-13:00 | 13.30 | 8.40 |
April | 0.352536E+10 | 7272.42 | 07-APR-15:20 | 25.60 | 15.99 | 0.536396E+09 | 845.63 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.637362E+10 | 10560.09 | 31-MAY-05:01 | 16.38 | 14.98 | 0.632918E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.913307E+10 | 13662.24 | 20-JUN-03:01 | 22.02 | 19.38 | 0.656058E+09 | 845.63 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.104877E+11 | 14576.77 | 24-JUL-03:01 | 22.02 | 21.19 | 0.613611E+09 | 845.60 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.106671E+11 | 14434.64 | 18-AUG-05:02 | 25.00 | 18.88 | 0.686757E+09 | 845.64 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.685470E+10 | 13588.74 | 02-SEP-05:02 | 22.12 | 16.29 | 0.592228E+09 | 845.64 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.450582E+10 | 6966.52 | 04-OCT-14:00 | 24.40 | 18.94 | 0.575929E+09 | 845.59 | 16-OCT-13:20 | 19.07 | 15.96 |
November | 0.188471E+10 | 3640.15 | 03-NOV-14:00 | 17.80 | 10.65 | 0.494442E+09 | 813.31 | 03-NOV-13:00 | 17.80 | 10.65 |
December | 0.701645E+09 | 2330.61 | 20-DEC-14:20 | 9.43 | 5.61 | 0.450888E+09 | 695.48 | 20-DEC-14:30 | 9.15 | 5.46 |
Annual Sum or Average | 0.574884E+11 | 0.668075E+10 | ||||||||
Minimum of Months | 0.591317E+09 | 2330.61 | 6.02 | 1.70 | 0.426599E+09 | 695.48 | 6.10 | 1.73 | ||
Maximum of Months | 0.106671E+11 | 14576.77 | 25.60 | 21.19 | 0.686757E+09 | 845.66 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.699053E+09 | 2631.36 | 19-JAN-09:40 | 6.67 | 3.81 | 0.301064E+09 | 442.23 | 19-JAN-10:09 | 7.80 | 4.24 |
February | 0.860998E+09 | 2739.90 | 17-FEB-09:50 | 4.13 | 0.26 | 0.275165E+09 | 457.04 | 17-FEB-10:09 | 4.68 | 0.59 |
March | 0.265774E+10 | 5520.12 | 29-MAR-09:25 | 6.15 | 3.18 | 0.361297E+09 | 544.95 | 29-MAR-09:09 | 5.78 | 3.04 |
April | 0.400067E+10 | 9442.24 | 28-APR-08:50 | 15.82 | 8.78 | 0.352280E+09 | 544.97 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.686169E+10 | 20623.01 | 29-MAY-08:51 | 26.10 | 16.70 | 0.402204E+09 | 545.00 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.848880E+10 | 20538.80 | 25-JUN-08:52 | 25.60 | 23.63 | 0.414092E+09 | 544.96 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.956869E+10 | 20517.66 | 09-JUL-10:02 | 29.90 | 25.41 | 0.391346E+09 | 544.95 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.104075E+11 | 17234.18 | 13-AUG-09:12 | 28.17 | 19.19 | 0.441126E+09 | 544.97 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.692156E+10 | 20209.46 | 04-SEP-09:21 | 24.75 | 18.33 | 0.373821E+09 | 544.98 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.488501E+10 | 7703.89 | 05-OCT-09:10 | 19.08 | 16.87 | 0.373948E+09 | 544.98 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.204117E+10 | 3912.25 | 03-NOV-14:00 | 17.80 | 10.65 | 0.314347E+09 | 510.54 | 03-NOV-09:39 | 13.13 | 8.28 |
December | 0.858702E+09 | 2661.65 | 20-DEC-09:30 | 7.20 | 4.57 | 0.290249E+09 | 439.60 | 20-DEC-10:09 | 8.40 | 5.02 |
Annual Sum or Average | 0.582516E+11 | 0.429094E+10 | ||||||||
Minimum of Months | 0.699053E+09 | 2631.36 | 4.13 | 0.26 | 0.275165E+09 | 439.60 | 4.68 | 0.59 | ||
Maximum of Months | 0.104075E+11 | 20623.01 | 29.90 | 25.41 | 0.441126E+09 | 545.00 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255778E+10 | 11938.82 | 19-JAN-13:40 | 9.40 | 3.84 | 0.520866E+09 | 864.49 | 19-JAN-14:09 | 9.32 | 3.66 |
February | 0.295805E+10 | 12128.48 | 02-FEB-14:10 | 5.50 | -0.7 | 0.481790E+09 | 878.14 | 02-FEB-14:20 | 5.40 | -0.8 |
March | 0.507590E+10 | 14161.70 | 01-MAR-13:40 | 13.90 | 6.18 | 0.600708E+09 | 914.08 | 01-MAR-14:09 | 13.62 | 5.83 |
April | 0.517405E+10 | 14057.75 | 07-APR-12:40 | 26.33 | 16.04 | 0.549938E+09 | 845.66 | 10-APR-13:09 | 20.10 | 10.08 |
May | 0.738240E+10 | 17019.85 | 29-MAY-14:58 | 25.60 | 17.02 | 0.629367E+09 | 845.69 | 15-MAY-13:50 | 18.27 | 11.31 |
June | 0.987116E+10 | 15607.98 | 20-JUN-03:01 | 22.02 | 19.38 | 0.653076E+09 | 845.65 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.115001E+11 | 16561.52 | 24-JUL-03:01 | 22.02 | 21.19 | 0.612529E+09 | 845.62 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.133930E+11 | 19405.44 | 13-AUG-15:52 | 30.00 | 20.44 | 0.687812E+09 | 902.34 | 30-AUG-13:20 | 27.77 | 15.55 |
September | 0.105210E+11 | 20848.70 | 04-SEP-12:41 | 26.10 | 18.21 | 0.601349E+09 | 964.76 | 28-SEP-13:39 | 23.53 | 13.50 |
October | 0.984824E+10 | 20295.96 | 15-OCT-12:32 | 20.40 | 13.09 | 0.615901E+09 | 954.07 | 04-OCT-13:30 | 24.70 | 18.74 |
November | 0.449727E+10 | 15344.53 | 02-NOV-13:30 | 15.85 | 8.44 | 0.558464E+09 | 945.87 | 02-NOV-13:30 | 15.85 | 8.44 |
December | 0.292291E+10 | 11827.07 | 15-DEC-13:30 | 3.35 | -0.3 | 0.513227E+09 | 855.31 | 21-DEC-14:09 | 3.30 | -1.3 |
Annual Sum or Average | 0.857019E+11 | 0.702503E+10 | ||||||||
Minimum of Months | 0.255778E+10 | 11827.07 | 3.35 | -0.7 | 0.481790E+09 | 845.62 | 3.30 | -1.3 | ||
Maximum of Months | 0.133930E+11 | 20848.70 | 30.00 | 21.19 | 0.687812E+09 | 964.76 | 29.15 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985304E+09 | 3597.52 | 20-JAN-16:00 | 7.20 | 3.79 | 0.305161E+09 | 501.67 | 20-JAN-16:10 | 6.93 | 3.70 |
February | 0.113559E+10 | 4651.18 | 22-FEB-16:30 | 3.85 | -0.4 | 0.281073E+09 | 521.19 | 22-FEB-16:00 | 3.30 | -0.4 |
March | 0.325325E+10 | 9010.58 | 29-MAR-16:00 | 7.20 | 4.87 | 0.354853E+09 | 544.92 | 03-MAR-14:00 | 15.00 | 8.37 |
April | 0.465853E+10 | 19476.34 | 09-APR-16:51 | 16.10 | 13.79 | 0.335061E+09 | 544.95 | 26-APR-13:00 | 18.30 | 12.91 |
May | 0.714423E+10 | 14572.42 | 27-MAY-17:08 | 21.60 | 11.96 | 0.385250E+09 | 544.99 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.929629E+10 | 22373.78 | 18-JUN-17:41 | 23.58 | 21.53 | 0.408038E+09 | 544.96 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.101597E+11 | 21814.98 | 02-JUL-16:42 | 24.50 | 20.60 | 0.387682E+09 | 544.93 | 12-JUL-13:09 | 28.80 | 18.60 |
August | 0.114399E+11 | 21774.23 | 13-AUG-15:52 | 30.00 | 20.44 | 0.435406E+09 | 544.97 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.739963E+10 | 21188.59 | 10-SEP-16:12 | 23.13 | 12.79 | 0.361179E+09 | 544.95 | 15-SEP-13:00 | 22.80 | 15.48 |
October | 0.555562E+10 | 11449.35 | 04-OCT-15:30 | 23.35 | 19.11 | 0.356344E+09 | 544.92 | 04-OCT-13:00 | 24.40 | 18.94 |
November | 0.228091E+10 | 5890.83 | 03-NOV-15:40 | 15.73 | 10.51 | 0.313926E+09 | 521.19 | 03-NOV-15:20 | 16.47 | 10.75 |
December | 0.114435E+10 | 3480.32 | 08-DEC-15:50 | 6.20 | 1.94 | 0.295010E+09 | 489.78 | 08-DEC-15:00 | 6.10 | 1.86 |
Annual Sum or Average | 0.644533E+11 | 0.421898E+10 | ||||||||
Minimum of Months | 0.985304E+09 | 3480.32 | 3.85 | -0.4 | 0.281073E+09 | 489.78 | 3.30 | -0.4 | ||
Maximum of Months | 0.114399E+11 | 22373.78 | 30.00 | 21.53 | 0.435406E+09 | 544.99 | 29.15 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182699E+10 | 4308.42 | 21-JAN-06:10 | -0.5 | -0.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.203472E+10 | 5214.26 | 21-FEB-06:06 | 2.30 | 1.56 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.424965E+10 | 5366.83 | 28-MAR-05:02 | 9.50 | 7.48 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.557571E+10 | 8636.02 | 10-APR-05:13 | 15.20 | 13.75 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.642047E+10 | 9320.20 | 31-MAY-05:01 | 16.38 | 14.98 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.814963E+10 | 9374.40 | 20-JUN-05:01 | 20.78 | 18.12 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.907300E+10 | 8682.32 | 17-JUL-05:13 | 21.87 | 19.48 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.102698E+11 | 9602.68 | 22-AUG-05:01 | 25.00 | 18.09 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.725449E+10 | 9870.63 | 06-SEP-05:01 | 21.52 | 18.83 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.664192E+10 | 8644.71 | 16-OCT-05:13 | 8.90 | 8.42 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.440929E+10 | 7586.17 | 13-NOV-06:15 | 5.77 | 4.70 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.355036E+10 | 5025.73 | 18-DEC-06:07 | 0.60 | -1.2 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.694561E+11 | 0.00 | ||||||||
Minimum of Months | 0.182699E+10 | 4308.42 | -0.5 | -1.2 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.102698E+11 | 9870.63 | 25.00 | 19.48 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513775E+09 | 5824.30 | 14-JAN-05:01 | -7.3 | -7.9 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.705413E+09 | 7811.22 | 06-FEB-04:11 | -13.3 | -14.6 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.160126E+10 | 5141.58 | 17-MAR-04:01 | -1.6 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.285475E+10 | 5228.42 | 10-APR-05:13 | 15.20 | 13.75 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.459920E+10 | 7777.52 | 31-MAY-05:01 | 16.38 | 14.98 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.641076E+10 | 9544.63 | 20-JUN-05:01 | 20.78 | 18.12 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.720753E+10 | 9780.78 | 12-JUL-05:01 | 21.97 | 18.13 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.806793E+10 | 9222.93 | 17-AUG-05:01 | 25.10 | 24.25 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.569277E+10 | 8955.12 | 06-SEP-05:01 | 21.52 | 18.83 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.420908E+10 | 5449.73 | 13-OCT-05:13 | 14.63 | 14.63 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.176848E+10 | 5862.29 | 24-NOV-05:01 | -4.0 | -5.9 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.981035E+09 | 5390.47 | 02-DEC-05:01 | 1.10 | -2.2 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.446120E+11 | 0.00 | ||||||||
Minimum of Months | 0.513775E+09 | 5141.58 | -13.3 | -14.6 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.806793E+10 | 9780.78 | 25.10 | 24.25 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13369907.25 | 1289.46 | 19-JAN-13:10 | 9.40 | 4.08 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.119989E+09 | 2532.81 | 17-FEB-13:00 | 6.70 | 1.54 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.164085E+10 | 8470.06 | 28-MAR-13:10 | 13.80 | 8.63 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.382901E+10 | 15125.47 | 07-APR-13:10 | 26.60 | 16.30 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.794434E+10 | 20096.42 | 30-MAY-13:10 | 29.90 | 17.80 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.121308E+11 | 22659.55 | 19-JUN-13:50 | 34.50 | 23.72 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.143195E+11 | 21171.47 | 10-JUL-13:50 | 32.70 | 20.80 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.152272E+11 | 20938.80 | 18-AUG-13:10 | 33.30 | 20.32 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.829696E+10 | 18251.13 | 01-SEP-14:15 | 30.93 | 17.36 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.472404E+10 | 12788.76 | 04-OCT-14:00 | 24.40 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.701066E+09 | 5675.28 | 03-NOV-13:50 | 17.70 | 10.64 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 8568844.41 | 1584.69 | 17-DEC-13:20 | 12.20 | 5.04 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.689556E+11 | 0.00 | ||||||||
Minimum of Months | 8568844.41 | 1289.46 | 6.70 | 1.54 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.152272E+11 | 22659.55 | 34.50 | 23.72 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291388E+10 | 1965.57 | 20-JAN-16:20 | 6.67 | 3.60 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.758070E+10 | 4066.35 | 14-FEB-17:00 | 0.00 | -3.8 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.141696E+11 | 6048.80 | 29-MAR-17:10 | 5.92 | 4.23 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.186788E+11 | 7637.15 | 23-APR-17:47 | 12.38 | 8.82 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.432042E+10 | 2096.48 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.927318E+10 | 4090.54 | 18-JUN-17:52 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.146192E+11 | 6059.44 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.181944E+11 | 7285.73 | 08-AUG-04:12 | 15.40 | 12.61 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.428147E+10 | 3807.39 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.944160E+10 | 4123.85 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.136745E+11 | 5847.76 | 06-NOV-16:10 | 13.03 | 7.65 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.190310E+11 | 7532.98 | 18-DEC-15:50 | 5.68 | 2.50 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.136179E+12 | 0.00 | ||||||||
Minimum of Months | 0.291388E+10 | 1965.57 | 0.00 | -3.8 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.190310E+11 | 7637.15 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102177E+10 | 1704.74 | 20-JAN-16:30 | 6.40 | 3.50 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.554683E+10 | 3684.57 | 22-FEB-17:00 | 3.30 | -0.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.122124E+11 | 5689.16 | 29-MAR-17:20 | 5.73 | 4.14 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.170062E+11 | 7251.91 | 12-APR-17:20 | 12.03 | 3.26 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.357930E+10 | 2000.86 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.862257E+10 | 3912.58 | 18-JUN-17:56 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.138915E+11 | 5805.17 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.173633E+11 | 6966.19 | 20-AUG-02:55 | 15.60 | 13.01 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.360902E+10 | 3675.16 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.822341E+10 | 3889.92 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.115258E+11 | 5458.05 | 03-NOV-16:00 | 15.00 | 10.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.162296E+11 | 7114.77 | 08-DEC-16:10 | 5.92 | 1.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.118832E+12 | 0.00 | ||||||||
Minimum of Months | 0.102177E+10 | 1704.74 | 3.30 | -0.4 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.173633E+11 | 7251.91 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375620E+09 | 1594.81 | 20-JAN-16:40 | 6.13 | 3.40 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.368933E+10 | 3572.13 | 02-FEB-16:50 | 3.07 | -2.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.107958E+11 | 5679.32 | 29-MAR-17:10 | 5.92 | 4.23 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.161432E+11 | 7361.97 | 12-APR-17:20 | 12.03 | 3.26 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.321053E+10 | 2091.99 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.858920E+10 | 4161.49 | 18-JUN-17:54 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.139779E+11 | 5899.98 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.176289E+11 | 6980.29 | 20-AUG-01:12 | 16.83 | 13.77 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.331690E+10 | 3092.24 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.735061E+10 | 3952.75 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.986240E+10 | 5436.15 | 03-NOV-16:00 | 15.00 | 10.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.140652E+11 | 6976.72 | 08-DEC-16:10 | 5.92 | 1.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.109006E+12 | 0.00 | ||||||||
Minimum of Months | 0.375620E+09 | 1594.81 | 3.07 | -2.5 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.176289E+11 | 7361.97 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237164E+12 | 333247.07 | 09-JAN-20:31 | 0.77 | -2.2 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.434496E+12 | 370289.05 | 27-FEB-23:30 | 0.00 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.728404E+12 | 415447.79 | 18-MAR-17:22 | 2.20 | 0.92 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.943390E+12 | 396037.10 | 05-APR-03:43 | 6.20 | 2.77 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.239638E+12 | 327913.85 | 01-MAY-01:25 | 9.05 | 6.33 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.469555E+12 | 183075.46 | 20-JUN-16:00 | 25.60 | 17.02 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.731395E+12 | 275282.78 | 06-JUL-16:00 | 28.30 | 24.26 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.978209E+12 | 369652.74 | 16-AUG-21:13 | 26.50 | 25.09 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.235438E+12 | 105708.13 | 01-SEP-00:05 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.487757E+12 | 355778.70 | 28-OCT-19:46 | 7.30 | 2.64 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.708573E+12 | 411760.58 | 08-NOV-04:22 | 6.10 | 5.59 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.976515E+12 | 400727.70 | 25-DEC-02:43 | 6.02 | 5.74 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.717053E+13 | 0.00 | ||||||||
Minimum of Months | 0.235438E+12 | 105708.13 | 0.00 | -2.2 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.978209E+12 | 415447.79 | 28.30 | 25.09 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252062E+09 | 142385.17 | 31-JAN-04:47 | -7.7 |
February | 0.512773E+09 | 142862.99 | 03-FEB-04:07 | -7.2 |
March | 0.432421E+09 | 142426.53 | 31-MAR-03:44 | 5.60 |
April | 0.394434E+09 | 140355.75 | 22-APR-03:48 | 5.78 |
May | 0.602499E+09 | 141441.21 | 05-MAY-03:16 | 13.70 |
June | 0.497919E+09 | 150214.80 | 25-JUN-16:56 | 25.60 |
July | 0.947227E+09 | 152050.71 | 09-JUL-13:40 | 31.70 |
August | 0.515111E+09 | 145433.10 | 13-AUG-14:10 | 31.52 |
September | 0.712234E+09 | 139375.75 | 04-SEP-20:46 | 22.88 |
October | 0.125488E+10 | 136511.70 | 22-OCT-10:00 | 19.40 |
November | 0.896747E+09 | 132502.71 | 11-NOV-15:18 | 13.13 |
December | 0.701033E+09 | 135599.80 | 21-DEC-04:47 | 0.18 |
Annual Sum or Average | 0.771934E+10 | |||
Minimum of Months | 0.252062E+09 | 132502.71 | -7.7 | |
Maximum of Months | 0.125488E+10 | 152050.71 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513016E+09 | 46432.53 | 02-JAN-04:01 | -11.8 |
February | 12601340.87 | 33726.86 | 06-FEB-06:01 | -12.9 |
March | 9062257.17 | 12989.45 | 13-MAR-10:10 | 2.38 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 16759278.20 | 17831.85 | 24-NOV-17:17 | 1.33 |
December | 95720764.07 | 26169.52 | 18-DEC-17:37 | 3.30 |
Annual Sum or Average | 0.647160E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.513016E+09 | 46432.53 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325865E+10 | 84421.03 | 02-JAN-04:01 | -11.8 |
February | 0.214345E+10 | 82537.34 | 06-FEB-04:11 | -13.3 |
March | 0.319521E+09 | 73922.42 | 20-MAR-04:01 | -0.8 |
April | 47577140.34 | 69152.42 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.723067E+09 | 75849.65 | 24-NOV-05:01 | -4.0 |
December | 0.829339E+09 | 76385.84 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.732160E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.325865E+10 | 84421.03 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15156504.07 | 9516.96 | 14-JAN-06:01 | -7.8 |
February | 30702026.24 | 9699.05 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 45858530.30 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 30702026.24 | 9699.05 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22330203.84 | 7138.17 | 14-JAN-06:01 | -7.8 |
February | 26293328.77 | 7422.79 | 06-FEB-05:01 | -13.2 |
March | 427800.50 | 3647.10 | 22-MAR-05:01 | -2.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 274635.57 | 3077.27 | 22-NOV-06:01 | -2.2 |
December | 1060339.06 | 3478.16 | 28-DEC-06:01 | 1.02 |
Annual Sum or Average | 50386307.74 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 26293328.77 | 7422.79 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115583E+09 | 12305.98 | 02-JAN-05:02 | -12.1 |
February | 94642824.72 | 12608.08 | 06-FEB-05:01 | -13.2 |
March | 1249155.14 | 8327.70 | 13-MAR-05:03 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 1826264.35 | 11178.40 | 24-NOV-06:01 | -4.4 |
December | 1589441.94 | 11158.20 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.214891E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.115583E+09 | 12608.08 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3254757.23 | 5502.33 | 14-JAN-06:01 | -7.8 |
February | 1605271.17 | 5154.55 | 06-FEB-06:01 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 4860028.40 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 3254757.23 | 5502.33 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227290E+10 | 13671.08 | 01-JAN-08:62 | -3.2 |
February | 0.144885E+10 | 13710.43 | 06-FEB-04:11 | -13.3 |
March | 0.208260E+09 | 11664.96 | 13-MAR-04:01 | -0.1 |
April | 13314312.56 | 10657.44 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 101019.58 | 1683.66 | 28-OCT-05:01 | 3.90 |
November | 0.245869E+09 | 11942.49 | 24-NOV-04:07 | -3.4 |
December | 0.591197E+09 | 12271.87 | 31-DEC-22:22 | -7.5 |
Annual Sum or Average | 0.478050E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.227290E+10 | 13710.43 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139669E+10 | 15603.32 | 02-JAN-00:41 | -11.0 |
February | 0.763903E+09 | 15636.52 | 06-FEB-04:11 | -13.3 |
March | 0.134344E+09 | 13083.91 | 13-MAR-04:01 | -0.1 |
April | 11376061.26 | 12088.53 | 22-APR-05:01 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 233735.93 | 1780.87 | 28-OCT-05:01 | 3.90 |
November | 0.147326E+09 | 13285.94 | 24-NOV-05:01 | -4.0 |
December | 0.398911E+09 | 12904.18 | 02-DEC-05:01 | 1.10 |
Annual Sum or Average | 0.285278E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.139669E+10 | 15636.52 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148528E+10 | 15402.04 | 01-JAN-07:22 | -3.9 |
February | 0.737200E+09 | 15167.92 | 06-FEB-04:11 | -13.3 |
March | 0.122981E+09 | 12913.21 | 13-MAR-04:01 | -0.1 |
April | 7607480.37 | 11932.50 | 22-APR-05:01 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.123150E+09 | 12831.50 | 22-NOV-05:01 | -2.2 |
December | 0.336494E+09 | 12850.67 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.281272E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.148528E+10 | 15402.04 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114831E+10 | 15344.92 | 02-JAN-00:41 | -11.0 |
February | 0.668934E+09 | 15231.60 | 06-FEB-04:11 | -13.3 |
March | 77894053.68 | 12526.45 | 13-MAR-04:01 | -0.1 |
April | 2631125.12 | 11631.03 | 22-APR-05:01 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 62512.62 | 238.10 | 07-OCT-08:57 | 10.60 |
November | 0.109272E+09 | 12816.41 | 24-NOV-05:01 | -4.0 |
December | 0.256392E+09 | 12448.03 | 02-DEC-05:01 | 1.10 |
Annual Sum or Average | 0.226350E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.114831E+10 | 15344.92 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562504E+10 | 15794.49 | 01-JAN-08:62 | -3.2 |
February | 0.483087E+10 | 16403.03 | 06-FEB-04:11 | -13.3 |
March | 0.135737E+10 | 14770.28 | 13-MAR-02:61 | 0.60 |
April | 0.336058E+09 | 14031.01 | 03-APR-03:01 | 3.22 |
May | 6338427.99 | 11750.39 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.106306E+09 | 12379.76 | 10-OCT-04:01 | 10.50 |
November | 0.160896E+10 | 14969.74 | 23-NOV-23:33 | -3.1 |
December | 0.332751E+10 | 15735.17 | 31-DEC-21:02 | -6.8 |
Annual Sum or Average | 0.171985E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.562504E+10 | 16403.03 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335683E+10 | 17640.45 | 02-JAN-00:41 | -11.0 |
February | 0.260938E+10 | 18409.53 | 06-FEB-04:11 | -13.3 |
March | 0.736698E+09 | 16177.67 | 13-MAR-03:01 | 0.50 |
April | 0.196597E+09 | 15625.24 | 03-APR-03:01 | 3.22 |
May | 3389533.07 | 10317.94 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 54596658.67 | 13481.84 | 18-OCT-05:01 | 6.02 |
November | 0.908483E+09 | 16675.06 | 24-NOV-04:11 | -3.5 |
December | 0.193845E+10 | 17535.61 | 31-DEC-21:02 | -6.8 |
Annual Sum or Average | 0.980443E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.335683E+10 | 18409.53 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396574E+10 | 17787.28 | 01-JAN-07:22 | -3.9 |
February | 0.298534E+10 | 18486.08 | 06-FEB-04:11 | -13.3 |
March | 0.981275E+09 | 16391.06 | 13-MAR-03:01 | 0.50 |
April | 0.277571E+09 | 15553.75 | 03-APR-03:01 | 3.22 |
May | 6771242.47 | 13340.52 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 28403802.06 | 13501.89 | 18-OCT-05:01 | 6.02 |
November | 0.976214E+09 | 16712.67 | 24-NOV-04:11 | -3.5 |
December | 0.216998E+10 | 17542.56 | 31-DEC-21:02 | -6.8 |
Annual Sum or Average | 0.113913E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.396574E+10 | 18486.08 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280044E+10 | 18626.99 | 02-JAN-00:41 | -11.0 |
February | 0.214360E+10 | 19252.39 | 06-FEB-04:11 | -13.3 |
March | 0.511929E+09 | 17001.59 | 13-MAR-03:01 | 0.50 |
April | 0.110238E+09 | 15442.75 | 03-APR-04:01 | 2.80 |
May | 254920.47 | 1660.05 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 23664117.73 | 14028.05 | 18-OCT-05:01 | 6.02 |
November | 0.663256E+09 | 17370.84 | 24-NOV-04:11 | -3.5 |
December | 0.133871E+10 | 18234.03 | 31-DEC-21:02 | -6.8 |
Annual Sum or Average | 0.759209E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.280044E+10 | 19252.39 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156936E+09 | 13613.59 | 03-JAN-06:01 | 4.27 |
February | 0.128660E+09 | 11645.00 | 10-FEB-05:21 | -3.6 |
March | 88534169.76 | 12652.90 | 13-MAR-03:01 | 0.50 |
April | 0.111728E+09 | 13334.86 | 24-APR-03:01 | 7.88 |
May | 55228309.88 | 10562.90 | 01-MAY-03:02 | 7.45 |
June | 65315211.11 | 9729.64 | 12-JUN-03:02 | 18.90 |
July | 88365106.39 | 8891.92 | 01-JUL-03:01 | 20.00 |
August | 69840569.13 | 6998.19 | 26-AUG-03:01 | 16.60 |
September | 45252945.65 | 10042.35 | 14-SEP-03:01 | 22.20 |
October | 70901246.21 | 10973.91 | 23-OCT-03:02 | 14.13 |
November | 75409464.45 | 12544.70 | 27-NOV-04:02 | 6.60 |
December | 0.104927E+09 | 13700.65 | 26-DEC-04:01 | 5.60 |
Annual Sum or Average | 0.106110E+10 | |||
Minimum of Months | 45252945.65 | 6998.19 | -3.6 | |
Maximum of Months | 0.156936E+09 | 13700.65 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297837E+10 | 16688.24 | 02-JAN-06:12 | -11.7 |
February | 0.132206E+10 | 8929.53 | 22-FEB-10:20 | 1.13 |
March | 0.415729E+09 | 8987.32 | 21-MAR-05:01 | 6.02 |
April | 98612469.89 | 8278.09 | 04-APR-05:01 | 3.80 |
May | 49899384.67 | 7945.08 | 03-MAY-04:03 | 11.70 |
June | 30786304.83 | 8089.67 | 12-JUN-03:02 | 18.90 |
July | 35508100.24 | 8578.59 | 07-JUL-03:01 | 26.10 |
August | 28757362.17 | 7923.54 | 07-AUG-03:01 | 18.80 |
September | 36148056.04 | 7437.11 | 01-SEP-03:01 | 22.45 |
October | 45086804.08 | 7271.15 | 10-OCT-05:02 | 9.72 |
November | 0.361860E+09 | 10680.81 | 24-NOV-15:00 | 2.20 |
December | 0.634428E+09 | 13455.23 | 11-DEC-12:23 | 1.70 |
Annual Sum or Average | 0.603724E+10 | |||
Minimum of Months | 28757362.17 | 7271.15 | -11.7 | |
Maximum of Months | 0.297837E+10 | 16688.24 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.968878E+10 | 29220.76 | 02-JAN-05:33 | -11.9 |
February | 0.798220E+10 | 31427.37 | 06-FEB-05:10 | -13.2 |
March | 0.329689E+10 | 17803.09 | 20-MAR-05:13 | -1.3 |
April | 0.134098E+10 | 19600.86 | 26-APR-05:01 | 8.68 |
May | 0.207517E+09 | 19671.14 | 17-MAY-05:01 | 10.28 |
June | 68746664.49 | 17376.52 | 03-JUN-05:01 | 13.48 |
July | 42767688.08 | 12226.03 | 05-JUL-03:02 | 20.10 |
August | 64837967.06 | 14557.25 | 08-AUG-04:02 | 15.50 |
September | 0.134513E+09 | 18490.65 | 29-SEP-05:01 | 11.78 |
October | 0.776095E+09 | 19855.62 | 17-OCT-05:01 | 10.10 |
November | 0.376582E+10 | 21439.37 | 24-NOV-05:13 | -4.1 |
December | 0.674583E+10 | 19996.12 | 11-DEC-06:13 | 1.70 |
Annual Sum or Average | 0.341150E+11 | |||
Minimum of Months | 42767688.08 | 12226.03 | -13.2 | |
Maximum of Months | 0.968878E+10 | 31427.37 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298667E+09 | 529.41 | 02-JAN-23:20 | -4.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.298667E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 0.298667E+09 | 529.41 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.788907E+09 | 567.89 | 16-JAN-17:50 | 3.98 |
February | 50015449.38 | 524.05 | 05-FEB-23:50 | -13.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.838923E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.788907E+09 | 567.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363622E+09 | 43603.37 | 13-JAN-22:32 | -3.2 |
February | 47570421.84 | 29932.45 | 09-FEB-02:21 | -8.3 |
March | 602707.78 | 5507.07 | 18-MAR-17:21 | 2.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 48777417.45 | 42442.87 | 16-MAY-03:05 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 6192260.31 | 23822.93 | 28-OCT-19:41 | 7.30 |
November | 719350.86 | 5612.48 | 21-NOV-22:21 | -0.3 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.467485E+09 | |||
Minimum of Months | 0.00 | 0.00 | -8.3 | |
Maximum of Months | 0.363622E+09 | 43603.37 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.215029E+11 | 22401.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.195042E+11 | 22401.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.231659E+11 | 22401.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.207025E+11 | 22401.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.223344E+11 | 22401.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.222225E+11 | 22401.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.208144E+11 | 22401.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.231659E+11 | 22401.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.207025E+11 | 22401.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.215029E+11 | 22401.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.212480E+11 | 22401.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.208144E+11 | 22401.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.257680E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.195042E+11 | 22401.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.231659E+11 | 22401.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.606290E+10 | 6316.16 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.549934E+10 | 6316.16 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.653179E+10 | 6316.16 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.583722E+10 | 6316.16 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.629734E+10 | 6316.16 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.626579E+10 | 6316.16 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.586877E+10 | 6316.16 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.653179E+10 | 6316.16 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.583722E+10 | 6316.16 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.606290E+10 | 6316.16 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.599102E+10 | 6316.16 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.586877E+10 | 6316.16 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.549934E+10 | 6316.16 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.653179E+10 | 6316.16 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.223344E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.222225E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.212480E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.257680E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160547E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139148E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115827E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522874.53 | 0.770278E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3236707.23 | 0.428442E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19234887.38 | 0.209058E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48284739.35 | 56378728.07 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56493671.95 | 75327004.72 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6630762.06 | 0.231879E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99053.89 | 0.599186E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117095E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140621E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.134503E+09 | 0.910295E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56378728.07 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56493671.95 | 0.160547E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104519E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910757E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742190E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393896.17 | 0.487387E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2117673.71 | 0.274667E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15606268.65 | 0.121308E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43508930.08 | 22421835.76 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47601547.95 | 34550698.72 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5492542.73 | 0.145404E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65431.69 | 0.382583E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748589E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894458E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 0.114786E+09 | 0.580950E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22421835.76 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47601547.95 | 0.104519E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157242E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139872E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114615E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522860.66 | 0.754712E+09 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2938425.50 | 0.420674E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19094009.65 | 0.204304E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47883729.97 | 54624433.07 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54738632.43 | 76230804.86 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5844778.90 | 0.240622E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43430.73 | 0.623349E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115709E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138414E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 0.131066E+09 | 0.903306E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54624433.07 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54738632.43 | 0.157242E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108754E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962519E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823740E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 345306.29 | 0.564412E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2618324.05 | 0.300034E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12218286.97 | 0.157173E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30286509.70 | 50499972.31 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34225557.09 | 64023905.52 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4811338.17 | 0.166092E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65440.62 | 0.430314E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831942E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100721E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 84570762.89 | 0.644551E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50499972.31 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34225557.09 | 0.108754E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313999E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278058E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230038E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1162969.18 | 0.153832E+10 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8085391.99 | 0.896060E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41166701.78 | 0.454574E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100267E+09 | 0.155535E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115396E+09 | 0.204420E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15711962.25 | 0.475720E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172965.70 | 0.119464E+10 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225404E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269959E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.281962E+09 | 0.180938E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155535E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115396E+09 | 0.313999E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208918E+10 |
February | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187327E+10 |
March | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153305E+10 |
April | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 875143.77 | 0.103611E+10 |
May | 0.744847E+09 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4307751.10 | 0.588787E+09 |
June | 0.742030E+09 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31524709.81 | 0.283598E+09 |
July | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77395454.95 | 91814987.64 |
August | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84255096.30 | 0.129549E+09 |
September | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12163627.74 | 0.309655E+09 |
October | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134271.90 | 0.791651E+09 |
November | 0.708685E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149990E+10 |
December | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179919E+10 |
Annual Sum or Average | 0.858171E+10 | 0.187251E+11 | 0.259975E+11 | 0.210656E+09 | 0.120257E+11 | ||||
Minimum of Months | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91814987.64 |
Maximum of Months | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84255096.30 | 0.208918E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325978E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297443E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241962E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104960.66 | 0.159354E+10 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6546875.00 | 0.907314E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40144215.84 | 0.454570E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96818808.65 | 0.158674E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108188E+09 | 0.218818E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11950751.43 | 0.531004E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64141.11 | 0.135283E+10 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240717E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287569E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 0.264817E+09 | 0.191534E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158674E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108188E+09 | 0.325978E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213060E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189869E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158877E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982644.63 | 0.106938E+10 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6466750.31 | 0.614197E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28124216.20 | 0.323508E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70991865.42 | 0.123702E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76687230.37 | 0.160339E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12056611.74 | 0.326680E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245716.44 | 0.828012E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151850E+10 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184029E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 0.195555E+09 | 0.124227E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123702E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76687230.37 | 0.213060E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369035E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327310E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262684E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1408891.92 | 0.174784E+10 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9193454.62 | 0.105269E+10 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47036874.08 | 0.558811E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115460E+09 | 0.200204E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136366E+09 | 0.251949E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18663268.77 | 0.551769E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160795.75 | 0.133869E+10 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249562E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305939E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.328289E+09 | 0.208472E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200204E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136366E+09 | 0.369035E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246353E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220021E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176512E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 951150.69 | 0.119820E+10 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4681875.66 | 0.703335E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35043357.87 | 0.355393E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87470411.89 | 0.121410E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97127905.32 | 0.163222E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13538095.74 | 0.368264E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107380.29 | 0.907435E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167543E+10 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204897E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 0.238920E+09 | 0.139705E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121410E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97127905.32 | 0.246353E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379338E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343324E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276866E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307901.96 | 0.181945E+10 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7689318.24 | 0.106543E+10 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46844609.07 | 0.557185E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113984E+09 | 0.203418E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129639E+09 | 0.268616E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14768019.32 | 0.621265E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70801.36 | 0.155396E+10 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267195E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323907E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 0.314303E+09 | 0.219956E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203418E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129639E+09 | 0.379338E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250715E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224337E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184704E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1200862.60 | 0.124351E+10 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7801294.75 | 0.728444E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34598719.80 | 0.395550E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86915756.52 | 0.155229E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93368632.86 | 0.194767E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14938086.00 | 0.384859E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 345843.26 | 0.957042E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172044E+10 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211664E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 0.239169E+09 | 0.144940E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155229E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93368632.86 | 0.250715E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.606290E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.549934E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.653179E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.583722E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.629734E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.626579E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.586877E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.583722E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.606290E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.599102E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.586877E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.549934E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331555E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287630E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235737E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594230.59 | 0.156861E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5031811.69 | 0.870297E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28855062.81 | 0.431516E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74453209.67 | 0.128087E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84031910.55 | 0.176519E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7944752.76 | 0.476983E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4743.25 | 0.123786E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238992E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288860E+10 |
Annual Sum or Average | 0.200916E+09 | 0.187176E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128087E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84031910.55 | 0.331555E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539977E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487522E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401124E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190447.21 | 0.266374E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10955749.09 | 0.151091E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53216282.94 | 0.752025E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134747E+09 | 0.233762E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147512E+09 | 0.331866E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14640606.02 | 0.820178E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13691.55 | 0.212361E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400772E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481777E+10 |
Annual Sum or Average | 0.362276E+09 | 0.315478E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233762E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147512E+09 | 0.539977E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548277E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493329E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415756E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103818.08 | 0.280156E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2742624.24 | 0.169877E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34865758.95 | 0.901722E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89771736.84 | 0.311993E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122516E+09 | 0.383656E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10138655.50 | 0.893934E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219464E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394044E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470223E+10 |
Annual Sum or Average | 0.260139E+09 | 0.324026E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311993E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122516E+09 | 0.548277E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22401.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22401.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22401.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22401.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22401.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22401.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22401.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22401.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22401.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22401.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22401.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22401.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2675.30 | 31-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2664.76 | 06-FEB-00:52 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2081.98 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 07-APR-13:00 | 1601.14 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.01 | 29-MAY-12:00 | 964.82 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.47 | 19-JUN-21:02 | 546.10 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.47 | 09-JUL-13:50 | 225.02 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.71 | 12-AUG-18:52 | 322.60 | 20-AUG-06:10 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 14-SEP-14:00 | 504.52 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 25-OCT-11:00 | 1414.90 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2217.52 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2869.19 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.02 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 310.71 | 2869.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1749.49 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1841.58 | 05-FEB-08:40 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1478.63 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 07-APR-13:00 | 1009.34 | 11-APR-03:49 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.97 | 29-MAY-11:52 | 618.74 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.14 | 25-JUN-19:10 | 346.16 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.39 | 09-JUL-13:50 | 130.46 | 11-JUL-05:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.21 | 12-AUG-18:52 | 206.88 | 20-AUG-06:20 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 14-SEP-14:00 | 324.10 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 25-OCT-11:00 | 1015.82 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1433.75 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1861.81 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.46 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 244.21 | 1861.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2672.85 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2601.49 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2185.11 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 | 07-APR-13:00 | 1577.06 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.85 | 29-MAY-11:54 | 948.26 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.05 | 19-JUN-21:02 | 542.82 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.76 | 09-JUL-13:50 | 219.58 | 11-JUL-05:00 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.82 | 12-AUG-18:52 | 319.51 | 20-AUG-06:10 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.90 | 14-SEP-14:00 | 494.03 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 25-OCT-11:00 | 1416.06 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2186.31 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2788.66 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.58 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 311.82 | 2788.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1816.43 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1835.38 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1531.37 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 07-APR-13:00 | 1165.14 | 11-APR-03:49 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.78 | 29-MAY-11:52 | 682.63 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.57 | 19-JUN-21:02 | 419.83 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.79 | 09-JUL-13:50 | 220.91 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.31 | 12-AUG-18:52 | 253.99 | 20-AUG-06:10 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 | 04-SEP-13:00 | 366.13 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 25-OCT-11:00 | 1007.60 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1564.87 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2055.28 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.91 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 187.31 | 2055.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5263.77 | 31-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5374.56 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4097.09 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 07-APR-13:00 | 3225.99 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.58 | 29-MAY-11:52 | 1946.85 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.64 | 19-JUN-21:02 | 1136.38 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.59 | 09-JUL-14:00 | 492.96 | 11-JUL-04:47 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.98 | 04-AUG-21:02 | 758.65 | 20-AUG-05:55 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.44 | 14-SEP-14:00 | 998.79 | 23-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 25-OCT-11:00 | 2675.08 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4260.53 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5341.22 | 31-DEC-22:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.96 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 639.98 | 5374.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3510.91 | 31-JAN-00:53 |
February | 1239.33 | 01-FEB-08:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3604.80 | 06-FEB-00:53 |
March | 1239.33 | 01-MAR-08:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2789.22 | 12-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.69 | 07-APR-17:00 | 2131.65 | 11-APR-03:53 |
May | 1239.33 | 01-MAY-07:10 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.34 | 29-MAY-12:10 | 1292.14 | 03-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.31 | 25-JUN-19:20 | 733.43 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.48 | 09-JUL-14:00 | 312.08 | 11-JUL-04:47 |
August | 1239.33 | 01-AUG-07:10 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.67 | 12-AUG-19:10 | 528.61 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.71 | 04-SEP-14:00 | 687.75 | 10-SEP-08:00 |
October | 1239.33 | 02-OCT-07:10 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 25-OCT-11:00 | 1980.68 | 08-OCT-08:00 |
November | 1239.33 | 01-NOV-07:10 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2842.47 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3561.02 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.08 | |||||
Maximum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 500.67 | 3604.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5558.36 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5395.05 | 06-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4277.50 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 07-APR-13:00 | 3293.38 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.31 | 29-MAY-11:42 | 1980.53 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.80 | 19-JUN-21:02 | 1135.54 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.68 | 09-JUL-14:00 | 495.13 | 11-JUL-04:47 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.05 | 04-AUG-21:02 | 784.23 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.06 | 14-SEP-14:00 | 1090.10 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 | 25-OCT-11:00 | 2860.91 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4419.15 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5437.56 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.13 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 638.05 | 5558.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3555.85 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3602.35 | 06-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2752.68 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.53 | 07-APR-13:00 | 2238.60 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.68 | 29-MAY-12:10 | 1357.89 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.29 | 19-JUN-21:02 | 823.59 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.43 | 09-JUL-14:00 | 464.43 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.19 | 12-AUG-19:10 | 565.50 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.31 | 04-SEP-13:20 | 712.19 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 25-OCT-11:00 | 1829.70 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2875.35 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3560.85 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.43 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 454.43 | 3602.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6321.23 | 14-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6697.90 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5068.13 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.96 | 07-APR-13:00 | 3650.24 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 455.52 | 29-MAY-11:52 | 2199.64 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.61 | 19-JUN-21:02 | 1356.59 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.85 | 09-JUL-13:50 | 609.46 | 23-JUL-17:53 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.70 | 04-AUG-21:02 | 880.73 | 20-AUG-05:55 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.61 | 14-SEP-14:00 | 1146.46 | 23-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-OCT-11:00 | 3021.42 | 17-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4955.86 | 22-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6663.54 | 31-DEC-22:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.46 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 780.70 | 6697.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4326.15 | 14-JAN-05:53 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4465.62 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3381.03 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 | 07-APR-13:00 | 2417.69 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.86 | 29-MAY-12:20 | 1467.07 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.34 | 25-JUN-19:00 | 882.06 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.31 | 09-JUL-14:10 | 388.54 | 11-JUL-04:50 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.11 | 04-AUG-21:02 | 616.24 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.41 | 14-SEP-14:00 | 787.81 | 10-SEP-08:10 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 25-OCT-11:00 | 2055.26 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3305.19 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4442.29 | 31-DEC-22:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.54 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 568.11 | 4465.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6469.60 | 14-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6698.37 | 06-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5097.23 | 21-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.95 | 07-APR-13:00 | 3731.53 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.32 | 29-MAY-11:52 | 2241.93 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.65 | 19-JUN-21:02 | 1353.83 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.72 | 09-JUL-14:10 | 622.16 | 23-JUL-17:53 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.42 | 04-AUG-21:02 | 911.48 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.57 | 14-SEP-14:00 | 1243.33 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 | 25-OCT-11:00 | 3239.14 | 17-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4974.53 | 22-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6663.72 | 31-DEC-22:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.16 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 778.42 | 6698.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4326.20 | 14-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4465.57 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3403.87 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.42 | 08-APR-10:00 | 2551.20 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.06 | 29-MAY-11:42 | 1551.89 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.53 | 19-JUN-21:02 | 1024.43 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.43 | 09-JUL-13:42 | 613.96 | 02-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.84 | 04-AUG-21:02 | 656.99 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.35 | 04-SEP-12:50 | 819.43 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.05 | 25-OCT-11:00 | 2092.31 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3310.41 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4442.47 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.96 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 533.84 | 4465.57 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 6316.16 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6316.16 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 6316.16 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 6316.16 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 6316.16 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 6316.16 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 6316.16 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 6316.16 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 6316.16 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 6316.16 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 6316.16 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 6316.16 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 6316.16 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 6316.16 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5618.90 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5615.41 | 06-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4182.40 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 | 07-APR-13:00 | 3357.04 | 11-APR-03:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.76 | 29-MAY-12:00 | 1995.10 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.37 | 19-JUN-21:02 | 1081.62 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.47 | 09-JUL-14:00 | 450.57 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.75 | 12-AUG-18:52 | 704.27 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.07 | 14-SEP-14:00 | 966.50 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 25-OCT-11:00 | 2910.74 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4654.30 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6007.07 | 31-DEC-21:55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.75 | 6007.07 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9591.87 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9438.74 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6960.30 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 | 07-APR-13:00 | 5800.53 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.75 | 29-MAY-11:52 | 3461.23 | 03-MAY-04:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.69 | 19-JUN-21:02 | 1898.67 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.95 | 09-JUL-14:00 | 821.41 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.56 | 12-AUG-18:52 | 1271.82 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.60 | 14-SEP-14:00 | 1703.73 | 23-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 25-OCT-11:00 | 4953.29 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7900.57 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9668.63 | 31-DEC-21:55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 821.41 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.56 | 9668.63 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9461.80 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9087.67 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7718.14 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 | 08-APR-10:00 | 5785.61 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.89 | 29-MAY-11:52 | 3503.56 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.22 | 19-JUN-21:02 | 1923.57 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.17 | 07-JUL-22:00 | 960.90 | 02-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.57 | 04-AUG-21:02 | 1254.70 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.90 | 14-SEP-14:00 | 1751.90 | 23-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4792.64 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7565.65 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9184.69 | 31-DEC-22:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.57 | 9461.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 124893.86 | 02-JAN-02:46 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 125704.38 | 20-FEB-15:53 | 2692.84 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 122538.98 | 21-MAR-03:50 | 0.00 | 4038.86 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 124695.18 | 24-APR-03:01 | 0.00 | 10770.30 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 119870.14 | 01-MAY-02:61 | 0.00 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 119917.48 | 04-JUN-18:53 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 108677.05 | 16-JUL-22:47 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111413.38 | 20-AUG-09:52 | 4488.06 | 6222.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 121284.36 | 10-SEP-18:47 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 126110.59 | 29-OCT-17:00 | 2692.84 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 126505.84 | 11-NOV-15:20 | 3590.45 | 4978.03 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 126867.90 | 25-DEC-15:00 | 3590.45 | 4978.03 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 108677.05 | 0.00 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 126867.90 | 4488.06 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 68069.77 | 26-JAN-06:01 | 16122.38 | 22353.12 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74732.33 | 21-FEB-04:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76063.27 | 28-MAR-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82034.21 | 27-APR-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95911.96 | 30-MAY-03:03 | 0.00 | 8463.43 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93862.05 | 28-JUN-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89620.47 | 01-JUL-03:01 | 0.00 | 12090.61 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89010.54 | 24-AUG-05:02 | 16122.38 | 22353.12 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 101292.09 | 06-SEP-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93779.48 | 06-OCT-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79450.13 | 06-NOV-04:01 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76483.03 | 26-DEC-04:02 | 0.00 | 9672.49 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 68069.77 | 0.00 | 8463.43 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101292.09 | 16122.38 | 22353.12 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 62911.20 | 30-JAN-11:47 | 45948.79 | 60353.41 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63256.30 | 21-FEB-13:10 | 45948.79 | 60353.41 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65186.48 | 08-MAR-17:15 | 9673.43 | 22353.12 | 20142.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70018.54 | 28-APR-04:03 | 0.00 | 9672.49 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79358.96 | 30-MAY-03:01 | 0.00 | 8463.43 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85666.37 | 30-JUN-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 91502.78 | 24-JUL-03:03 | 0.00 | 8463.43 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93762.22 | 07-AUG-03:02 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85537.64 | 14-SEP-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81050.49 | 06-OCT-04:02 | 0.00 | 12090.61 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72197.33 | 10-NOV-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 65252.69 | 12-DEC-16:30 | 45948.79 | 60353.41 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62911.20 | 0.00 | 8463.43 | 20142.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93762.22 | 45948.79 | 60353.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25122.66 | 20-JAN-16:50 | 30632.53 | 40235.61 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26622.79 | 24-FEB-17:00 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38677.41 | 03-MAR-15:00 | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70005.20 | 07-APR-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82909.88 | 30-MAY-03:01 | 0.00 | 8463.43 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96480.95 | 20-JUN-03:02 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97061.65 | 24-JUL-03:03 | 0.00 | 8463.43 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 95870.68 | 18-AUG-03:02 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90237.14 | 05-SEP-04:02 | 0.00 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80494.72 | 06-OCT-05:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37640.20 | 03-NOV-15:50 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23665.69 | 20-DEC-17:00 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 23665.69 | 0.00 | 8463.43 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97061.65 | 30632.53 | 40235.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3021.36 | 20-JAN-14:40 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 |
February | 3463.36 | 24-FEB-14:10 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.45 |
March | 6971.68 | 27-MAR-13:30 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 |
April | 7912.58 | 26-APR-13:50 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.16 |
May | 12222.09 | 30-MAY-03:01 | 0.00 | 1062.67 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.04 |
June | 12865.96 | 26-JUN-03:01 | 0.00 | 1062.67 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.48 |
July | 13365.09 | 07-JUL-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 | 0.00 |
August | 13224.68 | 18-AUG-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 0.00 |
September | 13508.88 | 14-SEP-03:01 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.13 |
October | 10144.67 | 23-OCT-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.42 |
November | 5933.69 | 03-NOV-13:40 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 |
December | 4643.92 | 26-DEC-13:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3021.36 | 0.00 | 1062.67 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13508.88 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 277.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4099.42 | 19-JAN-09:25 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.26 |
February | 5391.65 | 22-FEB-09:05 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.72 |
March | 8502.27 | 29-MAR-08:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
April | 10381.48 | 06-APR-08:20 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 |
May | 18550.55 | 29-MAY-08:22 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 |
June | 12521.85 | 26-JUN-08:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 19543.49 | 02-JUL-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 |
August | 13908.88 | 20-AUG-09:22 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.94 |
September | 18491.53 | 04-SEP-08:12 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 |
October | 9357.91 | 09-OCT-08:41 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5938.31 | 02-NOV-08:50 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.78 |
December | 4371.01 | 20-DEC-09:20 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4099.42 | 326.14 | 452.18 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19543.49 | 2478.65 | 3255.69 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12066.16 | 17-JAN-13:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.23 |
February | 12018.34 | 22-FEB-13:20 | 3846.30 | 5052.09 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.60 |
March | 13646.47 | 01-MAR-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.13 |
April | 13828.87 | 07-APR-12:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
May | 13842.54 | 30-MAY-03:01 | 0.00 | 1062.69 | 7081.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.73 |
June | 14134.93 | 26-JUN-03:01 | 0.00 | 1062.69 | 7081.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.69 |
July | 17239.53 | 30-JUL-14:12 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
August | 18175.17 | 27-AUG-12:32 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 0.00 |
September | 18949.05 | 10-SEP-11:43 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.46 |
October | 18583.77 | 15-OCT-14:41 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.68 |
November | 14757.84 | 02-NOV-13:20 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.59 |
December | 16411.62 | 17-DEC-12:02 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12018.34 | 0.00 | 561.34 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18949.05 | 3846.30 | 5052.09 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 528.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6620.15 | 20-JAN-15:50 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 |
February | 8999.17 | 24-FEB-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 |
March | 18801.60 | 26-MAR-16:42 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.41 |
April | 21750.16 | 09-APR-16:22 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
May | 19939.06 | 14-MAY-16:22 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.11 |
June | 23255.31 | 18-JUN-16:02 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.39 |
July | 24241.21 | 04-JUL-16:41 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.16 |
August | 23973.92 | 20-AUG-16:01 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 |
September | 22346.95 | 03-SEP-16:41 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 |
October | 21276.00 | 15-OCT-16:01 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.38 |
November | 15210.88 | 04-NOV-03:01 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 |
December | 10725.17 | 25-DEC-14:14 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6620.15 | 0.00 | 452.18 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 | |
Maximum of Months | 24241.21 | 1239.33 | 1627.84 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4347.23 | 19-JAN-09:35 | 3846.22 | 5051.98 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.67 |
February | 5456.92 | 21-FEB-14:33 | 6032.37 | 7577.97 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.01 |
March | 4254.62 | 27-MAR-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 |
April | 6380.39 | 07-APR-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 0.00 |
May | 10274.87 | 30-MAY-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.34 |
June | 12828.50 | 22-JUN-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.69 |
July | 13252.66 | 10-JUL-03:58 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 0.00 |
August | 13162.28 | 05-AUG-03:01 | 0.00 | 1518.10 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 |
September | 12720.79 | 02-SEP-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 |
October | 6541.21 | 05-OCT-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
November | 4432.53 | 13-NOV-08:20 | 3846.22 | 5051.98 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.94 |
December | 5139.43 | 12-DEC-16:30 | 5769.33 | 7577.97 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4254.62 | 0.00 | 1122.66 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13252.66 | 6032.37 | 7577.97 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 395.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6006.95 | 19-JAN-09:35 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.51 |
February | 4582.62 | 02-FEB-09:50 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.99 |
March | 11360.35 | 14-MAR-09:43 | 0.00 | 4883.53 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.23 |
April | 10163.69 | 28-APR-08:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 |
May | 20970.51 | 29-MAY-08:42 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.52 |
June | 20026.75 | 25-JUN-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.88 |
July | 20845.76 | 09-JUL-09:12 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 0.00 |
August | 17687.01 | 20-AUG-09:12 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.94 |
September | 19970.69 | 04-SEP-07:52 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9885.63 | 15-OCT-09:11 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.08 |
November | 5095.80 | 06-NOV-08:07 | 3717.98 | 4883.53 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.72 |
December | 4455.95 | 01-DEC-09:55 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4455.95 | 0.00 | 452.18 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20970.51 | 3717.98 | 4883.53 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 742.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13745.40 | 30-JAN-11:47 | 5769.46 | 7578.14 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.81 |
February | 15187.77 | 22-FEB-13:05 | 3846.30 | 5052.09 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.45 |
March | 14577.89 | 22-MAR-13:30 | 4021.67 | 5052.09 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.62 |
April | 13339.36 | 07-APR-12:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 | 0.00 |
May | 11726.70 | 30-MAY-05:03 | 809.75 | 1122.69 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.51 |
June | 13824.46 | 20-JUN-03:01 | 0.00 | 1518.13 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.32 |
July | 17221.62 | 30-JUL-14:02 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 | 0.00 |
August | 16441.01 | 30-AUG-13:30 | 4021.67 | 5052.09 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 32.60 | 0.00 |
September | 18909.69 | 04-SEP-11:52 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.24 |
October | 18907.37 | 22-OCT-12:32 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.95 |
November | 14612.68 | 02-NOV-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.03 |
December | 15520.36 | 17-DEC-12:53 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 977.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11726.70 | 0.00 | 561.34 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18909.69 | 5769.46 | 7578.14 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 | 977.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4878.66 | 19-JAN-09:45 | 2478.65 | 3255.69 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.49 |
February | 6997.28 | 02-FEB-17:25 | 782.73 | 1808.72 | 1629.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.38 |
March | 9476.36 | 22-MAR-16:50 | 782.73 | 1808.72 | 1629.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.96 |
April | 18260.53 | 09-APR-16:11 | 521.82 | 723.49 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.83 |
May | 14033.63 | 27-MAY-17:08 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.80 |
June | 20635.21 | 18-JUN-17:41 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.45 |
July | 20498.26 | 04-JUL-16:31 | 521.82 | 723.49 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.56 |
August | 20033.78 | 13-AUG-15:52 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 122.74 | 0.00 |
September | 20394.91 | 10-SEP-16:41 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.04 |
October | 11180.15 | 04-OCT-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 |
November | 6310.26 | 03-NOV-15:40 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 |
December | 5371.33 | 28-DEC-14:45 | 2591.66 | 3255.69 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.05 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4878.66 | 0.00 | 452.18 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20635.21 | 2591.66 | 3255.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 122.74 | 522.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2367.21 | 20-JAN-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.50 |
February | 2404.69 | 17-FEB-16:10 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.70 |
March | 3964.93 | 27-MAR-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 |
April | 7272.42 | 07-APR-15:20 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 0.00 |
May | 10560.09 | 31-MAY-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13662.24 | 20-JUN-03:01 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.10 |
July | 14576.77 | 24-JUL-03:01 | 0.00 | 1062.67 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.31 |
August | 14434.64 | 18-AUG-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 0.00 |
September | 13588.74 | 02-SEP-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 |
October | 6966.52 | 04-OCT-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
November | 3640.15 | 03-NOV-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 |
December | 2330.61 | 20-DEC-14:20 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2330.61 | 0.00 | 1062.67 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14576.77 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 368.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2631.36 | 19-JAN-09:40 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.22 |
February | 2739.90 | 17-FEB-09:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.34 |
March | 5520.12 | 29-MAR-09:25 | 2591.66 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.05 |
April | 9442.24 | 28-APR-08:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.06 |
May | 20623.01 | 29-MAY-08:51 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.58 |
June | 20538.80 | 25-JUN-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.89 |
July | 20517.66 | 09-JUL-10:02 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 110.26 | 0.00 |
August | 17234.18 | 13-AUG-09:12 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 71.72 | 0.00 |
September | 20209.46 | 04-SEP-09:21 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.75 |
October | 7703.89 | 05-OCT-09:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.24 |
November | 3912.25 | 03-NOV-14:00 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.62 |
December | 2661.65 | 20-DEC-09:30 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2631.36 | 326.14 | 452.18 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20623.01 | 2591.66 | 3255.69 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 110.26 | 350.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11938.82 | 19-JAN-13:40 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.88 |
February | 12128.48 | 02-FEB-14:10 | 6032.50 | 7578.14 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.50 |
March | 14161.70 | 01-MAR-13:40 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.99 |
April | 14057.75 | 07-APR-12:40 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 | 0.00 |
May | 17019.85 | 29-MAY-14:58 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.16 |
June | 15607.98 | 20-JUN-03:01 | 0.00 | 1518.13 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.87 |
July | 16561.52 | 24-JUL-03:01 | 0.00 | 1062.69 | 7081.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.34 |
August | 19405.44 | 13-AUG-15:52 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 243.60 | 0.00 |
September | 20848.70 | 04-SEP-12:41 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.08 |
October | 20295.96 | 15-OCT-12:32 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1317.87 |
November | 15344.53 | 02-NOV-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.87 |
December | 11827.07 | 15-DEC-13:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 817.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11827.07 | 0.00 | 701.68 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20848.70 | 6032.50 | 7578.14 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 243.60 | 1317.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3597.52 | 20-JAN-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.28 |
February | 4651.18 | 22-FEB-16:30 | 2478.65 | 3255.69 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.72 |
March | 9010.58 | 29-MAR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.06 |
April | 19476.34 | 09-APR-16:51 | 456.59 | 633.05 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.15 |
May | 14572.42 | 27-MAY-17:08 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.11 |
June | 22373.78 | 18-JUN-17:41 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.76 |
July | 21814.98 | 02-JUL-16:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.99 |
August | 21774.23 | 13-AUG-15:52 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 | 0.00 |
September | 21188.59 | 10-SEP-16:12 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.43 |
October | 11449.35 | 04-OCT-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
November | 5890.83 | 03-NOV-15:40 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.70 |
December | 3480.32 | 08-DEC-15:50 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.22 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3480.32 | 0.00 | 452.18 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22373.78 | 2478.65 | 3255.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 | 663.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4308.42 | 21-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.39 |
February | 5214.26 | 21-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.33 |
March | 5366.83 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.72 |
April | 8636.02 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.26 |
May | 9320.20 | 31-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9374.40 | 20-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.75 |
July | 8682.32 | 17-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.11 |
August | 9602.68 | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
September | 9870.63 | 06-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
October | 8644.71 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.62 |
November | 7586.17 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.92 |
December | 5025.73 | 18-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4308.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9870.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5824.30 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7084.26 |
February | 7811.22 | 06-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7133.51 |
March | 5141.58 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4152.87 |
April | 5228.42 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.21 |
May | 7777.52 | 31-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9544.63 | 20-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.45 |
July | 9780.78 | 12-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
August | 9222.93 | 17-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
September | 8955.12 | 06-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 |
October | 5449.73 | 13-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 |
November | 5862.29 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2688.65 |
December | 5390.47 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5613.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5141.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7133.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1289.46 | 19-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.93 |
February | 2532.81 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.04 |
March | 8470.06 | 28-MAR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.01 |
April | 15125.47 | 07-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 | 0.00 |
May | 20096.42 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.93 | 0.00 |
June | 22659.55 | 19-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.37 | 0.00 |
July | 21171.47 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.84 | 0.00 |
August | 20938.80 | 18-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.22 | 0.00 |
September | 18251.13 | 01-SEP-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.66 | 0.00 |
October | 12788.76 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 |
November | 5675.28 | 03-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.40 |
December | 1584.69 | 17-DEC-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1289.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22659.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.84 | 1169.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1965.57 | 20-JAN-16:20 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4066.35 | 14-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6048.80 | 29-MAR-17:10 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7637.15 | 23-APR-17:47 | 0.00 | 52.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2096.48 | 30-MAY-18:00 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4090.54 | 18-JUN-17:52 | 0.00 | 87.68 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6059.44 | 12-JUL-18:20 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7285.73 | 08-AUG-04:12 | 0.00 | 140.29 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3807.39 | 01-SEP-00:03 | 0.00 | 70.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4123.85 | 04-OCT-16:30 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5847.76 | 06-NOV-16:10 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7532.98 | 18-DEC-15:50 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1965.57 | 0.00 | 52.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7637.15 | 0.00 | 291.78 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1704.74 | 20-JAN-16:30 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3684.57 | 22-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5689.16 | 29-MAR-17:20 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7251.91 | 12-APR-17:20 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2000.86 | 30-MAY-18:00 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3912.58 | 18-JUN-17:56 | 0.00 | 87.68 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5805.17 | 12-JUL-18:20 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6966.19 | 20-AUG-02:55 | 0.00 | 35.07 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3675.16 | 01-SEP-00:03 | 0.00 | 70.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3889.92 | 04-OCT-16:30 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5458.05 | 03-NOV-16:00 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7114.77 | 08-DEC-16:10 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1704.74 | 0.00 | 35.07 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7251.91 | 0.00 | 291.78 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1594.81 | 20-JAN-16:40 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3572.13 | 02-FEB-16:50 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5679.32 | 29-MAR-17:10 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7361.97 | 12-APR-17:20 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2091.99 | 30-MAY-18:00 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4161.49 | 18-JUN-17:54 | 0.00 | 87.68 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5899.98 | 12-JUL-18:20 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6980.29 | 20-AUG-01:12 | 0.00 | 105.21 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3092.24 | 01-SEP-00:03 | 0.00 | 70.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3952.75 | 04-OCT-16:30 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5436.15 | 03-NOV-16:00 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6976.72 | 08-DEC-16:10 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1594.81 | 0.00 | 70.14 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7361.97 | 0.00 | 291.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 333247.07 | 09-JAN-20:31 | 0.00 | 14035.92 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 370289.05 | 27-FEB-23:30 | 0.00 | 3508.98 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 415447.79 | 18-MAR-17:22 | 0.00 | 3508.98 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 396037.10 | 05-APR-03:43 | 0.00 | 3795.95 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 327913.85 | 01-MAY-01:25 | 0.00 | 3795.95 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 183075.46 | 20-JUN-16:00 | 0.00 | 6316.16 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 275282.78 | 06-JUL-16:00 | 0.00 | 6316.16 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369652.74 | 16-AUG-21:13 | 0.00 | 4210.78 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105708.13 | 01-SEP-00:05 | 0.00 | 1518.38 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 355778.70 | 28-OCT-19:46 | 0.00 | 3795.95 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 411760.58 | 08-NOV-04:22 | 0.00 | 3795.95 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 400727.70 | 25-DEC-02:43 | 0.00 | 3795.95 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 105708.13 | 0.00 | 1518.38 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 415447.79 | 0.00 | 14035.92 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.172647E+13 | 1114475.96 | 12-JAN-16:00 | 0.461415E+12 | 2558928.86 | 02-JAN-07:10 |
February | 0.191083E+13 | 1308052.46 | 02-FEB-16:40 | 0.375156E+12 | 2176157.03 | 06-FEB-07:10 |
March | 0.257885E+13 | 1582674.02 | 27-MAR-15:00 | 0.232510E+12 | 1341528.45 | 23-MAR-06:10 |
April | 0.289985E+13 | 1922741.54 | 07-APR-15:20 | 0.106893E+12 | 803790.26 | 01-APR-06:10 |
May | 0.196659E+13 | 1510647.28 | 31-MAY-15:50 | 0.551011E+11 | 433203.71 | 29-MAY-02:39 |
June | 0.260162E+13 | 1727332.95 | 19-JUN-15:09 | 0.480617E+11 | 222544.67 | 25-JUN-18:40 |
July | 0.318387E+13 | 1923084.31 | 20-JUL-15:20 | 0.447578E+11 | 107523.19 | 16-JUL-16:00 |
August | 0.364496E+13 | 2101131.46 | 02-AUG-15:09 | 0.469103E+11 | 172893.74 | 27-AUG-14:20 |
September | 0.206751E+13 | 1559794.79 | 07-SEP-15:09 | 0.447600E+11 | 228557.77 | 03-SEP-21:00 |
October | 0.234501E+13 | 1648677.91 | 04-OCT-15:20 | 0.669834E+11 | 330809.98 | 28-OCT-06:10 |
November | 0.248541E+13 | 1509849.83 | 10-NOV-08:20 | 0.183595E+12 | 1504681.77 | 24-NOV-07:10 |
December | 0.289058E+13 | 1597636.27 | 27-DEC-16:30 | 0.319402E+12 | 1696187.20 | 22-DEC-07:10 |
Annual Sum or Average | 0.303016E+14 | 0.198554E+13 | ||||
Minimum of Months | 0.172647E+13 | 1114475.96 | 0.447578E+11 | 107523.19 | ||
Maximum of Months | 0.364496E+13 | 2101131.46 | 0.461415E+12 | 2558928.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.358355E+12 | 0.914449E+11 | 0.811612E+12 | 0.173544E+12 | 0.170847E+12 | 0.161813E+11 | 0.00 | 0.870920E+11 | 0.100137E+11 | 0.472670E+10 | 0.265806E+10 | 0.00 | 0.00 |
February | 0.325045E+12 | 0.766881E+11 | 0.102011E+13 | 0.156760E+12 | 0.157170E+12 | 0.129149E+11 | 0.00 | 0.140554E+12 | 0.138872E+11 | 0.527421E+10 | 0.242573E+10 | 0.00 | 0.00 |
March | 0.386070E+12 | 0.767894E+11 | 0.146224E+13 | 0.173828E+12 | 0.186799E+12 | 0.158699E+11 | 0.00 | 0.225166E+12 | 0.460075E+11 | 0.385272E+10 | 0.222457E+10 | 0.00 | 0.00 |
April | 0.345016E+12 | 0.661861E+11 | 0.170426E+13 | 0.167919E+12 | 0.179645E+12 | 0.290868E+11 | 0.00 | 0.308843E+12 | 0.956746E+11 | 0.190670E+10 | 0.131350E+10 | 0.00 | 0.00 |
May | 0.372213E+12 | 0.611884E+11 | 0.820095E+12 | 0.173686E+12 | 0.189220E+12 | 0.619186E+11 | 0.00 | 0.196122E+12 | 0.909546E+11 | 0.734227E+09 | 0.462805E+09 | 0.00 | 0.00 |
June | 0.370347E+12 | 0.554140E+11 | 0.110647E+13 | 0.168186E+12 | 0.191830E+12 | 0.102298E+12 | 0.00 | 0.429114E+12 | 0.175879E+12 | 67070753.58 | 0.200886E+10 | 0.00 | 0.00 |
July | 0.346881E+12 | 0.589597E+11 | 0.143833E+13 | 0.173418E+12 | 0.200695E+12 | 0.121782E+12 | 0.00 | 0.630455E+12 | 0.210713E+12 | 0.00 | 0.263754E+10 | 0.00 | 0.00 |
August | 0.386070E+12 | 0.651055E+11 | 0.177907E+13 | 0.173828E+12 | 0.214349E+12 | 0.123283E+12 | 0.00 | 0.702909E+12 | 0.197971E+12 | 50529375.67 | 0.231782E+10 | 0.00 | 0.00 |
September | 0.345016E+12 | 0.707448E+11 | 0.784429E+12 | 0.167919E+12 | 0.186451E+12 | 0.838199E+11 | 0.00 | 0.284891E+12 | 0.142913E+12 | 0.110843E+09 | 0.121684E+10 | 0.00 | 0.00 |
October | 0.358355E+12 | 0.815507E+11 | 0.112844E+13 | 0.173544E+12 | 0.191596E+12 | 0.522875E+11 | 0.00 | 0.254207E+12 | 0.102746E+12 | 0.130897E+10 | 0.973515E+09 | 0.00 | 0.00 |
November | 0.354107E+12 | 0.863459E+11 | 0.140306E+13 | 0.168027E+12 | 0.175167E+12 | 0.167080E+11 | 0.00 | 0.220519E+12 | 0.569699E+11 | 0.273160E+10 | 0.177185E+10 | 0.00 | 0.00 |
December | 0.346881E+12 | 0.932346E+11 | 0.175516E+13 | 0.173418E+12 | 0.176569E+12 | 0.117993E+11 | 0.00 | 0.277332E+12 | 0.488278E+11 | 0.481669E+10 | 0.253922E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.429436E+13 | 0.883652E+12 | 0.152133E+14 | 0.204408E+13 | 0.222034E+13 | 0.647949E+12 | 0.00 | 0.375720E+13 | 0.119256E+13 | 0.255803E+11 | 0.225503E+11 | ||
Minimum of Months | 0.325045E+12 | 0.554140E+11 | 0.784429E+12 | 0.156760E+12 | 0.157170E+12 | 0.117993E+11 | 0.00 | 0.870920E+11 | 0.100137E+11 | 0.00 | 0.462805E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386070E+12 | 0.932346E+11 | 0.177907E+13 | 0.173828E+12 | 0.214349E+12 | 0.123283E+12 | 0.00 | 0.702909E+12 | 0.210713E+12 | 0.527421E+10 | 0.265806E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.405982E+12 | 0.00 | 0.554326E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.324517E+12 | 0.00 | 0.506387E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.174730E+12 | 0.00 | 0.577796E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.564149E+11 | 0.00 | 0.504776E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.460604E+10 | 0.00 | 0.504951E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151333E+10 | 0.00 | 0.465484E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.153087E+10 | 0.00 | 0.432270E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.128476E+10 | 0.00 | 0.456256E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.159071E+10 | 0.00 | 0.431693E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.197334E+11 | 0.00 | 0.472499E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.134232E+12 | 0.00 | 0.493624E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.267265E+12 | 0.00 | 0.521366E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.139340E+13 | 0.592143E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.128476E+10 | 0.00 | 0.431693E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.405982E+12 | 0.00 | 0.577796E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 373325.05 | 02-JAN-08:09 | 56280.71 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 129663.18 | 02-JAN-08:20 | 187683.11 | 30-JAN-11:20 | 44101.45 | 04-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 373325.05 | 01-FEB-08:09 | 56280.71 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 129663.18 | 01-FEB-08:20 | 200462.30 | 02-FEB-16:40 | 41799.98 | 06-FEB-05:10 | 0.00 | 01-FEB-00:10 |
March | 373325.05 | 01-MAR-08:09 | 56280.71 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 129663.18 | 01-MAR-08:20 | 171911.31 | 22-MAR-15:30 | 68260.80 | 27-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 373325.05 | 03-APR-07:10 | 56280.71 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 129663.18 | 03-APR-07:19 | 150077.49 | 12-APR-07:00 | 75043.32 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 373325.05 | 01-MAY-07:10 | 56280.71 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 129663.18 | 01-MAY-07:19 | 159524.06 | 30-MAY-13:00 | 75500.61 | 30-MAY-10:00 | 0.00 | 01-MAY-00:10 |
June | 373325.05 | 01-JUN-07:10 | 56280.71 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 129663.18 | 01-JUN-07:19 | 163880.44 | 01-JUN-15:09 | 75489.03 | 01-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 373325.05 | 03-JUL-07:10 | 56280.71 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 129663.18 | 03-JUL-07:19 | 160364.57 | 11-JUL-15:39 | 75373.57 | 26-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 373325.05 | 01-AUG-07:10 | 56280.71 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 129663.18 | 01-AUG-07:19 | 236609.16 | 25-AUG-14:39 | 78337.73 | 25-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 373325.05 | 01-SEP-07:10 | 56280.71 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 129663.18 | 01-SEP-07:19 | 182781.74 | 01-SEP-13:00 | 76412.51 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 373325.05 | 02-OCT-07:10 | 56280.71 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 129663.18 | 02-OCT-07:19 | 153647.42 | 27-OCT-16:49 | 74487.32 | 24-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 373325.05 | 01-NOV-07:10 | 56280.71 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 129663.18 | 01-NOV-07:19 | 188254.75 | 24-NOV-13:00 | 42063.07 | 10-NOV-09:00 | 0.00 | 01-NOV-00:10 |
December | 373325.05 | 01-DEC-08:09 | 56280.71 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 129663.18 | 01-DEC-08:20 | 188554.75 | 21-DEC-10:50 | 35161.34 | 30-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 373325.05 | 56280.71 | 439129.89 | 129663.18 | 150077.49 | 35161.34 | 0.00 | |||||||
Maximum of Months | 373325.05 | 56280.71 | 794004.08 | 129663.18 | 236609.16 | 78337.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 95022.51 | 19-JAN-23:19 | 13959.64 | 24-JAN-12:09 | 38049.99 | 09-JAN-20:30 | 2110.37 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 99383.13 | 26-FEB-07:49 | 15761.59 | 20-FEB-11:00 | 35857.00 | 26-FEB-07:49 | 2110.37 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 217907.16 | 27-MAR-15:00 | 72473.24 | 27-MAR-12:50 | 22776.12 | 21-MAR-21:49 | 2110.37 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 378733.76 | 07-APR-13:00 | 88854.36 | 07-APR-15:20 | 8049.42 | 01-APR-17:19 | 2110.37 | 01-APR-06:10 | 0.00 | 0.00 |
May | 313758.42 | 30-MAY-10:00 | 95698.22 | 19-MAY-11:39 | 19444.49 | 01-MAY-21:19 | 2110.37 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 401309.15 | 19-JUN-12:20 | 95698.22 | 18-JUN-14:09 | 1988.65 | 02-JUN-19:00 | 2110.37 | 01-JUN-09:39 | 0.00 | 0.00 |
July | 468791.44 | 20-JUL-14:50 | 95698.22 | 06-JUL-07:10 | 0.00 | 01-JUL-00:10 | 2110.37 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 522552.78 | 02-AUG-14:00 | 95698.22 | 03-AUG-03:30 | 3913.60 | 30-AUG-15:09 | 2110.37 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 350925.40 | 14-SEP-10:20 | 95698.22 | 01-SEP-05:49 | 2669.98 | 28-SEP-17:00 | 2110.37 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 338005.75 | 04-OCT-13:30 | 95698.22 | 03-OCT-10:00 | 33333.33 | 28-OCT-17:19 | 2110.37 | 02-OCT-06:10 | 0.00 | 0.00 |
November | 166879.32 | 03-NOV-13:00 | 54979.04 | 10-NOV-09:00 | 19222.32 | 07-NOV-22:19 | 2110.37 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 120249.72 | 05-DEC-11:50 | 43417.42 | 17-DEC-14:00 | 11205.20 | 30-DEC-17:30 | 2110.37 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||
Minimum of Months | 95022.51 | 13959.64 | 0.00 | 2110.37 | 0.00 | 0.00 | ||||
Maximum of Months | 522552.78 | 95698.22 | 38049.99 | 2110.37 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1114475.96 | 12-JAN-16:00 | 373325.05 | 439129.89 | 56280.71 | 92996.58 | 99500.74 | 6793.57 | 0.00 | 36737.48 | 4903.86 |
February | 1308052.46 | 02-FEB-16:40 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 200462.30 | 4679.30 | 0.00 | 67088.94 | 5783.97 |
March | 1582674.02 | 27-MAR-15:00 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 98130.03 | 68260.80 | 0.00 | 217907.16 | 56341.72 |
April | 1922741.54 | 07-APR-15:20 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 122247.46 | 74685.77 | 0.00 | 376628.24 | 88854.36 |
May | 1510647.28 | 31-MAY-15:50 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 131156.70 | 73958.57 | 0.00 | 302271.90 | 95698.22 |
June | 1727332.95 | 19-JUN-15:09 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 139174.03 | 74443.33 | 0.00 | 392164.09 | 95698.22 |
July | 1923084.31 | 20-JUL-15:20 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 139923.85 | 75192.69 | 0.00 | 468124.88 | 95698.22 |
August | 2101131.46 | 02-AUG-15:09 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 147862.27 | 75484.42 | 0.00 | 519650.47 | 95698.22 |
September | 1559794.79 | 07-SEP-15:09 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 139831.85 | 74637.45 | 0.00 | 342065.39 | 95698.22 |
October | 1648677.91 | 04-OCT-15:20 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 133152.90 | 73479.68 | 0.00 | 320493.82 | 95698.22 |
November | 1509849.83 | 10-NOV-08:20 | 373325.05 | 675712.68 | 0.00 | 129663.18 | 85353.15 | 40176.41 | 0.00 | 151478.88 | 54140.48 |
December | 1597636.27 | 27-DEC-16:30 | 373325.05 | 794004.08 | 56280.71 | 92996.58 | 152547.57 | 4595.07 | 0.00 | 104080.43 | 14826.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1114475.96 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 85353.15 | 4595.07 | 0.00 | 36737.48 | 4903.86 | |
Maximum of Months | 2101131.46 | 373325.05 | 794004.08 | 56280.71 | 129663.18 | 200462.30 | 75484.42 | 0.00 | 519650.47 | 95698.22 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 2550782.28 | 02-JAN-07:10 | 0.00 | 82697.21 | 12-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 2168010.45 | 06-FEB-07:10 | 0.00 | 83901.37 | 10-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 1333381.87 | 23-MAR-06:10 | 0.00 | 82561.59 | 10-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 795643.68 | 01-APR-06:10 | 0.00 | 78067.01 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 425057.13 | 29-MAY-02:39 | 0.00 | 75198.18 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 214398.09 | 25-JUN-18:40 | 0.00 | 71184.65 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 99376.61 | 16-JUL-16:00 | 0.00 | 67032.23 | 05-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 164747.16 | 27-AUG-14:20 | 0.00 | 65584.40 | 29-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 220411.19 | 03-SEP-21:00 | 0.00 | 68594.43 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 322663.40 | 28-OCT-06:10 | 0.00 | 72738.09 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 1496535.19 | 24-NOV-07:10 | 0.00 | 79092.17 | 28-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 1688040.62 | 22-DEC-07:10 | 0.00 | 81946.58 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 99376.61 | 0.00 | 65584.40 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2550782.28 | 0.00 | 83901.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.94 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.32 | 0.67 | 27.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.15 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.12 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.45 | 1.33 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.22 | 0.33 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.45 | 2.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.09 | 1.33 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.41 | 1.33 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 26.70 | 1.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.51 | 1.50 | 28.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.35 | 0.67 | 27.80 |
Annual Sum or Average | 0.00 | 0.00 | 138.67 | 26.34 | 10.83 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.94 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 26.70 | 2.00 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 25.60 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.49 | 1.17 | 20.00 | 0.17 | 24.59 | 0.17 | 24.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.75 | 1.33 | 24.75 |
Annual Sum or Average | 2.00 | 19.49 | 1.17 | 20.00 | 1.50 | 24.74 | 1.50 | 24.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.49 | 1.17 | 20.00 | 1.33 | 24.75 | 1.33 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.90 | 0.67 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 18.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 18.72 | 0.67 | 20.08 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.44 | 0.67 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.87 | 2.00 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.91 | 1.50 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.49 | 0.33 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.94 | 2.00 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 27.80 | 7.50 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.94 | 2.00 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.34 | 0.00 | 0.00 | 4.33 | 24.78 | 4.33 | 24.78 |
February | 0.17 | 19.17 | 0.00 | 0.00 | 8.67 | 24.88 | 8.67 | 24.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 24.80 | 17.67 | 24.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.58 | 2.50 | 25.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 25.66 | 11.67 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 25.20 | 36.17 | 25.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 25.05 | 12.50 | 25.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 25.36 | 12.17 | 25.36 |
Annual Sum or Average | 0.33 | 19.26 | 0.00 | 105.67 | 25.15 | 105.67 | 25.15 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.34 | 0.00 | 0.00 | 36.17 | 25.66 | 36.17 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.50 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.82 | 3.67 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.57 | 1.33 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.71 | 3.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.59 | 4.67 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.00 | 2.67 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.80 | 1.83 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.67 | 27.49 | 18.50 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.82 | 4.67 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.67 | 16.94 | 5.83 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.33 | 17.75 | 1.17 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 17.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.33 | 17.31 | 7.00 | 17.55 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 19.17 | 5.83 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 16.18 | 2.33 | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.17 | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.97 | 1.50 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.77 | 0.67 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.98 | 2.33 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.74 | 0.83 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.77 | 2.17 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 18.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.50 | 16.80 | 2.33 | 15.12 | 7.67 | 27.86 | 7.67 | 27.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.00 | 19.24 | 2.33 | 15.12 | 2.33 | 27.98 | 2.33 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 16.85 | 2.67 | 17.69 | 7.33 | 24.96 | 7.33 | 24.96 |
February | 3.83 | 17.95 | 0.17 | 20.44 | 13.83 | 24.93 | 13.83 | 24.93 |
March | 0.17 | 19.17 | 0.00 | 0.00 | 22.83 | 24.92 | 22.83 | 24.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.21 | 7.50 | 25.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 25.42 | 26.17 | 25.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 25.27 | 55.17 | 25.27 |
November | 0.17 | 19.17 | 0.00 | 0.00 | 14.17 | 25.18 | 14.17 | 25.18 |
December | 0.33 | 19.20 | 0.00 | 0.00 | 11.67 | 25.27 | 11.67 | 25.27 |
Annual Sum or Average | 16.00 | 17.21 | 2.83 | 17.85 | 158.67 | 25.19 | 158.67 | 25.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.50 | 19.20 | 2.67 | 20.44 | 55.17 | 25.42 | 55.17 | 25.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 16.11 | 2.67 | 15.11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.00 | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.96 | 0.33 | 28.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.33 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.87 | 2.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.82 | 2.33 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.96 | 1.17 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.72 | 1.00 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.50 | 16.55 | 2.67 | 15.11 | 10.00 | 27.84 | 7.17 | 27.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 19.24 | 2.67 | 15.11 | 3.50 | 27.96 | 2.33 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.67 | 16.49 | 12.00 | 16.74 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36.50 | 16.67 | 13.17 | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5.67 | 18.69 | 0.50 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.83 | 17.64 | 1.33 | 19.60 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15.50 | 17.17 | 4.00 | 15.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 110.83 | 16.86 | 31.00 | 16.98 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.67 | 18.93 | 13.17 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.83 | 15.57 | 6.50 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22.33 | 16.01 | 4.00 | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.33 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.86 | 1.50 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.74 | 0.67 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.67 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.77 | 1.17 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.67 | 1.50 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.17 | 16.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.50 | 16.66 | 2.67 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.83 | 16.18 | 13.17 | 14.84 | 8.50 | 27.78 | 8.50 | 27.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.83 | 18.95 | 6.50 | 14.93 | 3.67 | 27.86 | 3.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.67 | 16.38 | 5.83 | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21.50 | 16.83 | 4.67 | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.67 | 18.64 | 0.00 | 0.00 | 4.17 | 24.72 | 4.17 | 24.72 |
April | 0.67 | 19.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.45 | 1.67 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.89 | 4.33 | 25.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 25.69 | 13.67 | 25.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 25.10 | 18.83 | 25.10 |
November | 4.17 | 18.38 | 0.17 | 20.40 | 3.00 | 25.02 | 3.00 | 25.02 |
December | 10.50 | 17.40 | 1.17 | 16.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.17 | 16.94 | 11.83 | 17.19 | 45.83 | 25.40 | 45.67 | 25.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.67 | 19.02 | 5.83 | 20.40 | 18.83 | 27.45 | 18.83 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.83 | 15.76 | 4.50 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16.17 | 16.19 | 3.33 | 14.69 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.67 | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 19.28 | 0.00 | 0.00 | 0.50 | 27.92 | 0.33 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.02 | 2.00 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.04 | 2.83 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.22 | 1.17 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.75 | 1.33 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.50 | 18.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.67 | 17.38 | 1.33 | 14.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.50 | 16.53 | 9.17 | 14.76 | 11.17 | 28.00 | 8.00 | 28.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.83 | 19.28 | 4.50 | 14.90 | 4.17 | 28.22 | 2.83 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 28.20 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 714.67 | 29.04 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 805.33 | 28.94 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 714.67 | 29.04 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 28.11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 710.67 | 29.02 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 771.33 | 28.95 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 710.67 | 29.02 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 28.14 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 631.50 | 28.96 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 670.50 | 28.91 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 631.50 | 28.96 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.39 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 29.37 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 125.67 | 28.07 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.41 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.78 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.72 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 132.00 | 28.08 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 125.67 | 29.37 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 182.00 | 23.97 | 91.67 | 25.60 | 0.00 | 0.00 |
February | 230.50 | 23.99 | 68.83 | 26.33 | 0.00 | 0.00 |
March | 90.00 | 24.01 | 107.17 | 25.64 | 0.00 | 0.00 |
April | 28.50 | 24.01 | 166.33 | 25.39 | 0.00 | 0.00 |
May | 25.67 | 24.02 | 285.67 | 24.86 | 22.17 | 24.02 |
June | 148.00 | 24.88 | 442.33 | 24.53 | 148.00 | 24.88 |
July | 227.50 | 25.27 | 497.00 | 24.63 | 227.50 | 25.27 |
August | 109.33 | 25.14 | 479.50 | 24.53 | 109.33 | 25.14 |
September | 55.83 | 25.04 | 404.50 | 24.67 | 55.83 | 25.04 |
October | 35.00 | 24.40 | 350.33 | 24.86 | 19.67 | 24.68 |
November | 26.50 | 24.13 | 157.00 | 25.79 | 1.00 | 26.82 |
December | 102.83 | 24.03 | 99.00 | 26.48 | 0.17 | 26.84 |
Annual Sum or Average | 1261.67 | 24.49 | 3149.33 | 24.91 | 583.67 | 25.06 |
Minimum of Months | 25.67 | 23.97 | 68.83 | 24.53 | 0.00 | 0.00 |
Maximum of Months | 230.50 | 25.27 | 497.00 | 26.48 | 227.50 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.17 | 24.05 | 56.00 | 24.73 | 12.00 | 24.97 |
February | 242.00 | 23.98 | 18.17 | 25.89 | 0.00 | 0.00 |
March | 85.67 | 24.01 | 106.00 | 25.29 | 0.00 | 0.00 |
April | 15.83 | 24.01 | 187.83 | 24.80 | 0.00 | 0.00 |
May | 14.83 | 23.72 | 286.67 | 24.46 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 434.33 | 24.29 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 492.67 | 24.23 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 490.67 | 24.18 | 0.00 | 0.00 |
September | 5.00 | 23.79 | 393.83 | 24.37 | 0.00 | 0.00 |
October | 29.67 | 24.02 | 325.67 | 24.53 | 0.00 | 0.00 |
November | 45.67 | 24.00 | 142.33 | 25.47 | 0.00 | 0.00 |
December | 130.33 | 24.01 | 75.83 | 25.96 | 0.00 | 0.00 |
Annual Sum or Average | 861.17 | 24.01 | 3010.00 | 24.50 | 12.00 | 24.97 |
Minimum of Months | 0.00 | 0.00 | 18.17 | 24.18 | 0.00 | 0.00 |
Maximum of Months | 292.17 | 24.05 | 492.67 | 25.96 | 12.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.50 | 22.95 | 36.00 | 19.56 | 36.00 | 19.56 |
February | 435.50 | 23.48 | 2.17 | 21.02 | 2.17 | 21.02 |
March | 322.67 | 23.76 | 14.33 | 24.11 | 0.00 | 0.00 |
April | 182.50 | 23.76 | 74.00 | 24.62 | 0.00 | 0.00 |
May | 60.33 | 23.66 | 205.17 | 24.34 | 0.00 | 0.00 |
June | 18.33 | 23.45 | 384.33 | 24.27 | 0.00 | 0.00 |
July | 6.50 | 23.35 | 427.17 | 24.25 | 0.00 | 0.00 |
August | 3.17 | 23.49 | 430.83 | 24.26 | 0.00 | 0.00 |
September | 32.33 | 23.58 | 319.83 | 24.29 | 0.00 | 0.00 |
October | 98.67 | 23.85 | 229.00 | 24.29 | 0.00 | 0.00 |
November | 253.00 | 23.66 | 64.50 | 24.77 | 0.00 | 0.00 |
December | 459.67 | 23.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2343.17 | 23.50 | 2187.33 | 24.22 | 38.17 | 19.64 |
Minimum of Months | 3.17 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 470.50 | 23.85 | 430.83 | 24.77 | 36.00 | 21.02 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.45 | 166.50 | 19.66 | 166.50 | 19.66 |
February | 454.00 | 21.76 | 137.50 | 20.22 | 137.50 | 20.22 |
March | 469.67 | 22.77 | 31.33 | 21.05 | 28.00 | 20.70 |
April | 306.67 | 22.99 | 55.33 | 23.76 | 8.17 | 20.60 |
May | 146.50 | 23.45 | 174.50 | 24.20 | 0.00 | 0.00 |
June | 14.50 | 23.56 | 367.67 | 24.28 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 450.83 | 24.30 | 0.00 | 0.00 |
August | 1.67 | 23.40 | 431.50 | 24.29 | 0.00 | 0.00 |
September | 82.67 | 23.31 | 266.67 | 24.21 | 0.00 | 0.00 |
October | 247.67 | 23.11 | 148.67 | 24.05 | 2.83 | 21.27 |
November | 432.83 | 22.50 | 72.50 | 20.92 | 62.17 | 20.41 |
December | 497.00 | 21.85 | 127.67 | 20.08 | 127.67 | 20.08 |
Annual Sum or Average | 3155.17 | 22.33 | 2430.67 | 23.34 | 532.83 | 20.07 |
Minimum of Months | 0.00 | 0.00 | 31.33 | 19.66 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.56 | 450.83 | 24.30 | 166.50 | 21.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.50 | 22.13 | 78.17 | 20.83 | 78.17 | 20.83 |
February | 454.00 | 22.33 | 54.33 | 20.84 | 54.33 | 20.84 |
March | 428.50 | 23.17 | 12.83 | 24.08 | 0.00 | 0.00 |
April | 243.50 | 23.44 | 82.33 | 24.26 | 0.00 | 0.00 |
May | 90.83 | 23.57 | 213.00 | 24.29 | 0.00 | 0.00 |
June | 3.50 | 23.82 | 432.17 | 24.26 | 0.17 | 25.20 |
July | 0.00 | 0.00 | 496.33 | 24.31 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 478.33 | 24.20 | 0.00 | 0.00 |
September | 63.00 | 23.56 | 324.50 | 24.27 | 1.50 | 25.98 |
October | 171.00 | 23.48 | 189.67 | 24.19 | 0.00 | 0.00 |
November | 348.83 | 23.14 | 25.67 | 24.32 | 0.00 | 0.00 |
December | 484.50 | 22.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2782.17 | 22.86 | 2387.33 | 24.07 | 134.17 | 20.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 494.50 | 23.82 | 496.33 | 24.32 | 78.17 | 25.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.17 | 21.70 | 88.50 | 20.81 | 88.50 | 20.81 |
February | 442.67 | 21.91 | 52.00 | 21.10 | 49.50 | 20.85 |
March | 421.50 | 22.43 | 15.83 | 24.15 | 1.33 | 21.00 |
April | 288.83 | 22.63 | 89.50 | 24.38 | 1.83 | 26.34 |
May | 183.00 | 22.96 | 222.50 | 24.42 | 7.17 | 26.60 |
June | 98.83 | 22.90 | 321.83 | 24.21 | 3.83 | 26.23 |
July | 68.33 | 23.18 | 351.50 | 24.19 | 7.17 | 26.48 |
August | 79.17 | 23.00 | 347.50 | 24.04 | 3.17 | 26.11 |
September | 157.50 | 22.90 | 250.50 | 24.38 | 10.17 | 26.53 |
October | 245.50 | 22.79 | 158.83 | 24.23 | 1.33 | 26.34 |
November | 408.50 | 22.49 | 11.83 | 24.45 | 1.67 | 20.92 |
December | 489.00 | 22.06 | 7.33 | 20.98 | 7.00 | 20.75 |
Annual Sum or Average | 3383.00 | 22.34 | 1917.67 | 23.98 | 182.67 | 21.89 |
Minimum of Months | 68.33 | 21.70 | 7.33 | 20.81 | 1.33 | 20.75 |
Maximum of Months | 500.17 | 23.18 | 351.50 | 24.45 | 88.50 | 26.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 432.17 | 21.91 | 105.17 | 21.18 | 88.50 | 20.45 |
February | 361.50 | 22.29 | 75.00 | 22.20 | 51.83 | 20.77 |
March | 347.33 | 22.81 | 59.00 | 24.46 | 0.67 | 21.04 |
April | 246.83 | 23.05 | 98.33 | 24.35 | 0.00 | 0.00 |
May | 130.83 | 23.30 | 206.67 | 24.28 | 0.17 | 26.06 |
June | 10.33 | 23.65 | 388.00 | 24.27 | 0.50 | 26.43 |
July | 2.83 | 25.97 | 483.33 | 24.31 | 2.83 | 25.97 |
August | 5.17 | 26.51 | 477.83 | 24.25 | 5.17 | 26.51 |
September | 61.67 | 24.05 | 365.50 | 24.44 | 14.00 | 26.75 |
October | 116.67 | 23.72 | 301.33 | 24.57 | 12.33 | 26.61 |
November | 285.17 | 22.85 | 95.17 | 24.44 | 3.67 | 20.86 |
December | 379.33 | 22.50 | 44.00 | 24.57 | 9.00 | 21.72 |
Annual Sum or Average | 2379.83 | 22.67 | 2699.33 | 24.17 | 188.67 | 21.75 |
Minimum of Months | 2.83 | 21.91 | 44.00 | 21.18 | 0.00 | 0.00 |
Maximum of Months | 432.17 | 26.51 | 483.33 | 24.57 | 88.50 | 26.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.33 | 22.06 | 23.00 | 21.36 | 20.67 | 20.85 |
February | 401.83 | 22.54 | 12.33 | 24.09 | 4.67 | 21.00 |
March | 208.83 | 23.22 | 129.17 | 24.67 | 1.50 | 26.45 |
April | 60.83 | 23.93 | 275.33 | 24.71 | 10.83 | 26.64 |
May | 89.00 | 23.13 | 301.00 | 24.43 | 3.67 | 26.09 |
June | 20.67 | 26.40 | 466.17 | 24.34 | 20.67 | 26.40 |
July | 34.00 | 26.24 | 497.00 | 24.41 | 34.00 | 26.24 |
August | 22.33 | 26.11 | 514.00 | 24.35 | 22.33 | 26.11 |
September | 73.17 | 23.33 | 318.50 | 24.39 | 8.67 | 26.59 |
October | 77.83 | 23.33 | 299.83 | 24.39 | 2.00 | 25.98 |
November | 192.17 | 23.14 | 121.33 | 24.98 | 0.83 | 26.53 |
December | 268.33 | 23.22 | 42.50 | 25.67 | 0.00 | 0.00 |
Annual Sum or Average | 1931.33 | 22.93 | 3000.17 | 24.44 | 129.83 | 25.25 |
Minimum of Months | 20.67 | 22.06 | 12.33 | 21.36 | 0.00 | 0.00 |
Maximum of Months | 482.33 | 26.40 | 514.00 | 25.67 | 34.00 | 26.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 297.00 | 19.88 | 297.00 | 19.88 |
February | 454.00 | 20.72 | 275.00 | 20.17 | 275.00 | 20.17 |
March | 502.50 | 21.76 | 82.00 | 20.45 | 79.17 | 20.32 |
April | 391.33 | 22.46 | 35.00 | 22.95 | 11.17 | 20.26 |
May | 229.17 | 23.19 | 128.50 | 24.14 | 0.00 | 0.00 |
June | 47.33 | 24.18 | 367.17 | 24.24 | 16.83 | 25.43 |
July | 29.33 | 25.74 | 477.67 | 24.34 | 29.33 | 25.74 |
August | 27.50 | 25.17 | 435.00 | 24.29 | 19.00 | 25.96 |
September | 142.17 | 23.22 | 235.17 | 24.14 | 7.17 | 24.81 |
October | 340.83 | 22.68 | 100.17 | 23.85 | 4.17 | 20.28 |
November | 471.83 | 21.69 | 92.00 | 20.07 | 92.00 | 20.07 |
December | 497.00 | 20.90 | 224.67 | 20.16 | 224.67 | 20.16 |
Annual Sum or Average | 3635.00 | 21.73 | 2749.33 | 22.76 | 1055.50 | 20.46 |
Minimum of Months | 27.50 | 20.52 | 35.00 | 19.88 | 0.00 | 0.00 |
Maximum of Months | 502.50 | 25.74 | 477.67 | 24.34 | 297.00 | 25.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.32 | 251.67 | 19.71 | 251.67 | 19.71 |
February | 385.00 | 20.72 | 195.33 | 20.06 | 195.33 | 20.06 |
March | 416.00 | 21.50 | 61.67 | 20.42 | 59.83 | 20.27 |
April | 314.00 | 22.02 | 58.17 | 24.47 | 4.83 | 20.70 |
May | 243.00 | 22.58 | 128.67 | 24.65 | 6.33 | 26.59 |
June | 138.67 | 22.94 | 223.00 | 24.39 | 15.17 | 25.87 |
July | 103.00 | 23.85 | 291.00 | 24.51 | 35.33 | 26.13 |
August | 90.67 | 23.50 | 299.00 | 24.37 | 20.33 | 26.10 |
September | 212.33 | 22.64 | 156.67 | 24.48 | 14.83 | 25.77 |
October | 314.00 | 22.26 | 72.50 | 24.03 | 2.67 | 21.88 |
November | 414.33 | 21.39 | 81.00 | 20.11 | 81.00 | 20.11 |
December | 422.00 | 20.75 | 195.00 | 20.15 | 195.00 | 20.15 |
Annual Sum or Average | 3480.00 | 21.60 | 2013.67 | 22.71 | 882.33 | 20.63 |
Minimum of Months | 90.67 | 20.32 | 58.17 | 19.71 | 2.67 | 19.71 |
Maximum of Months | 427.00 | 23.85 | 299.00 | 24.65 | 251.67 | 26.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 442.50 | 21.03 | 193.00 | 20.12 | 176.67 | 19.66 |
February | 377.17 | 21.61 | 138.33 | 21.21 | 111.50 | 20.19 |
March | 390.83 | 22.08 | 86.00 | 23.03 | 34.00 | 20.55 |
April | 327.50 | 22.47 | 76.83 | 24.03 | 9.50 | 21.35 |
May | 212.17 | 23.07 | 153.17 | 24.25 | 0.00 | 0.00 |
June | 57.17 | 23.87 | 352.83 | 24.27 | 14.83 | 25.55 |
July | 33.50 | 25.66 | 457.67 | 24.37 | 31.67 | 25.80 |
August | 31.67 | 25.55 | 459.50 | 24.37 | 24.50 | 26.21 |
September | 99.00 | 23.81 | 333.50 | 24.46 | 23.83 | 26.30 |
October | 174.83 | 23.43 | 275.67 | 24.67 | 21.67 | 26.23 |
November | 347.50 | 22.16 | 103.50 | 23.00 | 36.17 | 20.31 |
December | 412.83 | 21.67 | 135.00 | 21.46 | 106.17 | 20.37 |
Annual Sum or Average | 2906.67 | 22.18 | 2765.00 | 23.69 | 590.50 | 21.27 |
Minimum of Months | 31.67 | 21.03 | 76.83 | 20.12 | 0.00 | 0.00 |
Maximum of Months | 442.50 | 25.66 | 459.50 | 24.67 | 176.67 | 26.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.00 | 20.62 | 248.50 | 19.92 | 248.50 | 19.92 |
February | 444.83 | 20.87 | 199.17 | 20.17 | 199.17 | 20.17 |
March | 455.17 | 21.64 | 58.17 | 21.57 | 42.33 | 20.57 |
April | 371.00 | 22.16 | 70.00 | 24.09 | 9.00 | 21.96 |
May | 271.83 | 22.64 | 140.67 | 24.33 | 2.17 | 25.82 |
June | 109.33 | 23.31 | 324.50 | 24.35 | 19.33 | 26.09 |
July | 78.50 | 24.23 | 389.50 | 24.41 | 34.33 | 26.27 |
August | 49.17 | 24.53 | 423.17 | 24.37 | 23.00 | 26.52 |
September | 225.33 | 22.65 | 183.00 | 24.29 | 10.50 | 25.69 |
October | 328.83 | 22.36 | 96.33 | 24.06 | 2.17 | 20.58 |
November | 475.67 | 21.47 | 72.17 | 20.27 | 70.33 | 20.17 |
December | 497.00 | 21.00 | 162.00 | 20.26 | 162.00 | 20.26 |
Annual Sum or Average | 3807.67 | 21.69 | 2367.17 | 23.05 | 822.83 | 20.81 |
Minimum of Months | 49.17 | 20.62 | 58.17 | 19.92 | 2.17 | 19.92 |
Maximum of Months | 501.00 | 24.53 | 423.17 | 24.41 | 248.50 | 26.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 393.67 | 19.70 | 393.67 | 19.70 |
February | 454.00 | 20.16 | 383.50 | 19.94 | 383.50 | 19.94 |
March | 510.67 | 21.01 | 206.83 | 20.04 | 206.83 | 20.04 |
April | 415.67 | 21.75 | 93.00 | 21.07 | 69.33 | 20.02 |
May | 284.83 | 22.71 | 112.33 | 24.14 | 0.33 | 20.99 |
June | 81.50 | 23.54 | 347.33 | 24.23 | 16.33 | 25.25 |
July | 43.50 | 25.38 | 453.00 | 24.36 | 38.00 | 25.70 |
August | 56.00 | 24.04 | 413.50 | 24.29 | 18.67 | 25.92 |
September | 208.83 | 22.79 | 194.50 | 24.09 | 8.00 | 24.02 |
October | 399.67 | 21.95 | 123.00 | 22.09 | 59.33 | 20.06 |
November | 489.00 | 20.80 | 213.00 | 19.74 | 213.00 | 19.74 |
December | 497.00 | 20.12 | 418.00 | 19.92 | 418.00 | 19.92 |
Annual Sum or Average | 3942.67 | 21.18 | 3351.67 | 21.97 | 1825.00 | 20.13 |
Minimum of Months | 43.50 | 20.01 | 93.00 | 19.70 | 0.33 | 19.70 |
Maximum of Months | 510.67 | 25.38 | 453.00 | 24.36 | 418.00 | 25.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 380.17 | 19.68 | 380.17 | 19.68 |
February | 454.00 | 20.27 | 353.17 | 20.00 | 353.17 | 20.00 |
March | 505.83 | 21.11 | 148.50 | 19.77 | 148.50 | 19.77 |
April | 372.00 | 21.67 | 114.83 | 22.53 | 51.67 | 20.22 |
May | 274.33 | 22.29 | 173.17 | 24.43 | 6.50 | 26.29 |
June | 144.33 | 22.97 | 293.50 | 24.27 | 18.17 | 25.91 |
July | 106.83 | 24.02 | 380.33 | 24.39 | 43.83 | 26.08 |
August | 88.33 | 23.51 | 387.50 | 24.28 | 22.00 | 26.13 |
September | 242.83 | 22.39 | 195.50 | 24.31 | 13.00 | 25.12 |
October | 383.00 | 21.89 | 117.50 | 23.13 | 27.17 | 20.17 |
November | 489.00 | 20.77 | 185.00 | 19.70 | 185.00 | 19.70 |
December | 497.00 | 20.18 | 377.00 | 19.90 | 377.00 | 19.90 |
Annual Sum or Average | 4059.50 | 21.20 | 3106.17 | 22.13 | 1626.17 | 20.24 |
Minimum of Months | 88.33 | 20.02 | 114.83 | 19.68 | 6.50 | 19.68 |
Maximum of Months | 505.83 | 24.02 | 387.50 | 24.43 | 380.17 | 26.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.50 | 20.51 | 276.00 | 19.51 | 273.83 | 19.48 |
February | 408.50 | 20.87 | 239.83 | 19.96 | 237.50 | 19.91 |
March | 418.83 | 21.32 | 170.67 | 20.80 | 138.00 | 20.00 |
April | 357.33 | 21.78 | 121.50 | 22.26 | 61.00 | 20.28 |
May | 267.67 | 22.58 | 134.00 | 24.25 | 0.83 | 23.97 |
June | 97.17 | 23.31 | 330.83 | 24.25 | 14.67 | 25.34 |
July | 57.00 | 25.21 | 435.33 | 24.38 | 43.33 | 25.90 |
August | 57.50 | 24.49 | 432.00 | 24.36 | 26.50 | 26.25 |
September | 154.50 | 23.18 | 283.33 | 24.38 | 23.33 | 25.96 |
October | 226.67 | 22.46 | 230.67 | 24.15 | 28.83 | 22.35 |
November | 401.00 | 21.33 | 160.00 | 20.66 | 127.67 | 19.78 |
December | 446.17 | 20.80 | 259.33 | 19.99 | 253.00 | 19.83 |
Annual Sum or Average | 3364.83 | 21.57 | 3073.50 | 22.71 | 1228.50 | 20.40 |
Minimum of Months | 57.00 | 20.51 | 121.50 | 19.51 | 0.83 | 19.48 |
Maximum of Months | 472.50 | 25.21 | 435.33 | 24.38 | 273.83 | 26.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.19 | 340.00 | 19.70 | 340.00 | 19.70 |
February | 449.67 | 20.44 | 311.67 | 20.01 | 311.67 | 20.01 |
March | 472.50 | 21.15 | 154.67 | 20.52 | 142.50 | 20.21 |
April | 392.83 | 21.66 | 100.50 | 22.58 | 44.83 | 20.38 |
May | 311.83 | 22.28 | 129.50 | 24.33 | 3.17 | 25.84 |
June | 141.17 | 22.99 | 300.67 | 24.31 | 20.00 | 25.99 |
July | 100.17 | 23.95 | 376.17 | 24.39 | 39.33 | 26.20 |
August | 79.67 | 23.72 | 398.00 | 24.35 | 23.83 | 26.45 |
September | 271.67 | 22.36 | 158.00 | 24.23 | 11.50 | 25.26 |
October | 376.17 | 21.85 | 104.50 | 22.96 | 30.67 | 20.24 |
November | 481.17 | 20.83 | 176.67 | 19.91 | 175.67 | 19.89 |
December | 497.00 | 20.42 | 344.17 | 20.06 | 344.17 | 20.06 |
Annual Sum or Average | 4075.83 | 21.29 | 2894.50 | 22.23 | 1487.33 | 20.37 |
Minimum of Months | 79.67 | 20.19 | 100.50 | 19.70 | 3.17 | 19.70 |
Maximum of Months | 502.00 | 23.95 | 398.00 | 24.39 | 344.17 | 26.45 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45221 | 20.34143 | 0.33371 | 7.82634 |
February | 454.00000 | 24.45501 | 16.81779 | 0.31260 | 7.51670 |
March | 514.00000 | 24.40362 | 24.55637 | 0.36810 | 8.29316 |
April | 485.00000 | 24.50579 | 30.88217 | 0.43645 | 9.62986 |
May | 508.00000 | 24.48858 | 40.64489 | -0.3508 | 8.55047 |
June | 496.00000 | 24.47203 | 55.78261 | -0.2346 | 7.27872 |
July | 497.00000 | 24.62427 | 61.45395 | -0.1433 | 6.98101 |
August | 514.00000 | 24.48675 | 55.62555 | -0.2140 | 7.16015 |
September | 485.00000 | 24.55909 | 49.22180 | -0.2454 | 7.56667 |
October | 502.00000 | 24.61117 | 40.31047 | 0.54321 | 12.03932 |
November | 489.00000 | 24.60190 | 26.73531 | 0.43859 | 9.75638 |
December | 497.00000 | 24.56611 | 19.39381 | 0.37012 | 8.50410 |
Annual Sum or Average | 5943.00000 | 24.51872 | 36.97074 | 0.13237 | 8.42829 |
Minimum of Months | 454.00000 | 24.40362 | 16.81779 | -0.3508 | 6.98101 |
Maximum of Months | 514.00000 | 24.62427 | 61.45395 | 0.54321 | 12.03932 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17910 | 22.68497 | 0.27462 | 6.92344 |
February | 454.00000 | 24.27535 | 17.55483 | 0.27184 | 6.79348 |
March | 514.00000 | 24.31658 | 25.54160 | 0.36379 | 8.11226 |
April | 485.00000 | 24.33323 | 32.14005 | 0.42816 | 9.20883 |
May | 508.00000 | 24.26419 | 40.55348 | -0.3968 | 8.80479 |
June | 496.00000 | 24.24436 | 46.84839 | -0.3367 | 7.73003 |
July | 497.00000 | 24.22202 | 48.70304 | -0.3223 | 7.37432 |
August | 514.00000 | 24.17267 | 47.23971 | -0.3333 | 7.46883 |
September | 485.00000 | 24.29135 | 45.06876 | -0.3456 | 8.03408 |
October | 502.00000 | 24.37824 | 38.16490 | 0.48224 | 10.33912 |
November | 489.00000 | 24.47714 | 28.35691 | 0.41954 | 9.29333 |
December | 497.00000 | 24.39930 | 20.33740 | 0.34072 | 7.77258 |
Annual Sum or Average | 5943.00000 | 24.29559 | 34.55999 | 0.06812 | 8.16101 |
Minimum of Months | 454.00000 | 24.17267 | 17.55483 | -0.3968 | 6.79348 |
Maximum of Months | 514.00000 | 24.47714 | 48.70304 | 0.48224 | 10.33912 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.00575 | 25.16151 | -0.0367 | 7.62719 |
February | 454.00000 | 23.49130 | 20.98110 | 0.06329 | 5.66396 |
March | 514.00000 | 23.91407 | 27.67076 | 0.23469 | 6.44617 |
April | 485.00000 | 24.05540 | 33.77533 | 0.32398 | 7.50546 |
May | 508.00000 | 24.11638 | 41.18074 | -0.4770 | 10.16753 |
June | 496.00000 | 24.16874 | 47.44744 | -0.3944 | 8.64480 |
July | 497.00000 | 24.17350 | 49.34552 | -0.3748 | 8.30039 |
August | 514.00000 | 24.19685 | 47.72022 | -0.3698 | 8.25444 |
September | 485.00000 | 24.14818 | 45.81633 | -0.4220 | 9.15748 |
October | 502.00000 | 24.15144 | 39.24413 | 0.40002 | 8.73730 |
November | 489.00000 | 23.95316 | 30.98415 | 0.26227 | 7.01510 |
December | 497.00000 | 23.63847 | 23.44101 | 0.12326 | 5.66340 |
Annual Sum or Average | 5943.00000 | 23.92061 | 36.17531 | -0.0573 | 7.78182 |
Minimum of Months | 454.00000 | 23.00575 | 20.98110 | -0.4770 | 5.66340 |
Maximum of Months | 514.00000 | 24.19685 | 49.34552 | 0.40002 | 10.16753 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.44198 | 24.81310 | -0.4452 | 13.17772 |
February | 454.00000 | 21.74391 | 20.04157 | -0.3968 | 10.95066 |
March | 514.00000 | 22.86249 | 28.85113 | -0.0433 | 6.65769 |
April | 485.00000 | 23.38871 | 35.07834 | 0.15270 | 6.94213 |
May | 508.00000 | 23.92273 | 41.99814 | -0.5411 | 11.82972 |
June | 496.00000 | 24.16633 | 47.31342 | -0.3793 | 8.44444 |
July | 497.00000 | 24.24984 | 48.88718 | -0.3266 | 7.64450 |
August | 514.00000 | 24.21593 | 47.44150 | -0.3446 | 7.94690 |
September | 485.00000 | 23.97000 | 46.38959 | -0.4808 | 10.50484 |
October | 502.00000 | 23.57196 | 40.83880 | 0.25040 | 7.63586 |
November | 489.00000 | 22.65780 | 32.70672 | -0.0779 | 7.54655 |
December | 497.00000 | 21.83704 | 24.13468 | -0.3462 | 9.91664 |
Annual Sum or Average | 5943.00000 | 23.18023 | 36.66001 | -0.2477 | 9.08710 |
Minimum of Months | 454.00000 | 21.44198 | 20.04157 | -0.5411 | 6.65769 |
Maximum of Months | 514.00000 | 24.24984 | 48.88718 | 0.25040 | 13.17772 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.14984 | 22.23605 | -0.2301 | 7.57252 |
February | 454.00000 | 22.32309 | 17.77049 | -0.2140 | 7.25961 |
March | 514.00000 | 23.30382 | 26.25264 | 0.09168 | 5.99741 |
April | 485.00000 | 23.76460 | 32.34360 | 0.26698 | 7.10011 |
May | 508.00000 | 24.03304 | 40.16044 | -0.4814 | 10.44019 |
June | 496.00000 | 24.21970 | 46.73595 | -0.3216 | 7.58691 |
July | 497.00000 | 24.30331 | 48.74748 | -0.2557 | 6.83931 |
August | 514.00000 | 24.17974 | 46.86340 | -0.3051 | 7.23685 |
September | 485.00000 | 24.08689 | 45.24909 | -0.4156 | 9.25455 |
October | 502.00000 | 23.85063 | 38.35840 | 0.33567 | 8.06703 |
November | 489.00000 | 23.41117 | 29.07382 | 0.13364 | 6.37083 |
December | 497.00000 | 22.93857 | 21.31547 | -0.0419 | 5.80281 |
Annual Sum or Average | 5943.00000 | 23.55552 | 34.71668 | -0.1199 | 7.46198 |
Minimum of Months | 454.00000 | 22.14984 | 17.77049 | -0.4814 | 5.80281 |
Maximum of Months | 514.00000 | 24.30331 | 48.74748 | 0.33567 | 10.44019 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.70231 | 22.14584 | -0.3104 | 8.09746 |
February | 454.00000 | 21.97717 | 17.43875 | -0.2662 | 7.67894 |
March | 514.00000 | 22.70971 | 26.61143 | -0.0052 | 6.30908 |
April | 485.00000 | 23.22011 | 33.08646 | 0.18466 | 7.33749 |
May | 508.00000 | 23.71591 | 40.65499 | -0.5082 | 12.71936 |
June | 496.00000 | 23.80410 | 47.46607 | -0.3986 | 9.71251 |
July | 497.00000 | 23.86307 | 49.45980 | -0.3428 | 8.91437 |
August | 514.00000 | 23.75282 | 47.64261 | -0.3734 | 9.13110 |
September | 485.00000 | 23.69311 | 45.89461 | -0.4726 | 11.95753 |
October | 502.00000 | 23.43724 | 38.99256 | 0.28513 | 7.98130 |
November | 489.00000 | 22.74157 | 29.65525 | 0.00963 | 6.34226 |
December | 497.00000 | 22.08645 | 21.56969 | -0.2101 | 6.81637 |
Annual Sum or Average | 5943.00000 | 23.06653 | 35.18089 | -0.2009 | 8.59002 |
Minimum of Months | 454.00000 | 21.70231 | 17.43875 | -0.5082 | 6.30908 |
Maximum of Months | 514.00000 | 23.86307 | 49.45980 | 0.28513 | 12.71936 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.23104 | 21.91421 | -0.1910 | 8.60774 |
February | 454.00000 | 22.72457 | 17.02983 | -0.0927 | 7.91684 |
March | 514.00000 | 23.24728 | 25.91755 | 0.11508 | 6.93536 |
April | 485.00000 | 23.57892 | 32.50961 | 0.24225 | 7.45191 |
May | 508.00000 | 23.91462 | 40.40996 | -0.5085 | 11.40437 |
June | 496.00000 | 24.15080 | 46.81041 | -0.3347 | 7.92038 |
July | 497.00000 | 24.28201 | 48.62960 | -0.2476 | 6.91377 |
August | 514.00000 | 24.20825 | 46.55460 | -0.2539 | 6.94200 |
September | 485.00000 | 24.21042 | 44.64147 | -0.3129 | 8.67660 |
October | 502.00000 | 24.20331 | 37.17137 | 0.48385 | 11.38914 |
November | 489.00000 | 23.44193 | 28.63863 | 0.17790 | 7.56635 |
December | 497.00000 | 22.94887 | 20.88405 | -0.0057 | 7.27647 |
Annual Sum or Average | 5943.00000 | 23.60109 | 34.38672 | -0.0781 | 8.25549 |
Minimum of Months | 454.00000 | 22.23104 | 17.02983 | -0.5085 | 6.91377 |
Maximum of Months | 514.00000 | 24.28201 | 48.62960 | 0.48385 | 11.40437 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15030 | 21.31472 | -0.1812 | 6.98425 |
February | 454.00000 | 22.75185 | 16.42383 | -0.0536 | 6.44318 |
March | 514.00000 | 23.86396 | 24.54638 | 0.31177 | 7.97301 |
April | 485.00000 | 24.30203 | 30.71997 | 0.50133 | 11.27502 |
May | 508.00000 | 23.98131 | 39.88295 | -0.3788 | 9.54687 |
June | 496.00000 | 24.28229 | 45.74825 | -0.1584 | 6.90619 |
July | 497.00000 | 24.40080 | 47.47935 | -0.0677 | 6.39883 |
August | 514.00000 | 24.34088 | 45.62107 | -0.0413 | 5.96941 |
September | 485.00000 | 23.95059 | 44.95014 | -0.3380 | 9.24384 |
October | 502.00000 | 24.09564 | 37.27556 | 0.48348 | 10.87945 |
November | 489.00000 | 23.88457 | 27.48620 | 0.31057 | 8.15718 |
December | 497.00000 | 23.77816 | 19.34279 | 0.22273 | 6.82660 |
Annual Sum or Average | 5943.00000 | 23.82225 | 33.52479 | 0.05108 | 8.05115 |
Minimum of Months | 454.00000 | 22.15030 | 16.42383 | -0.3788 | 5.96941 |
Maximum of Months | 514.00000 | 24.40080 | 47.47935 | 0.50133 | 11.27502 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51845 | 26.04839 | -0.6522 | 16.70682 |
February | 454.00000 | 20.72008 | 20.61835 | -0.6202 | 15.25663 |
March | 514.00000 | 21.80318 | 29.06325 | -0.2733 | 8.26056 |
April | 485.00000 | 22.74545 | 34.79308 | 0.00728 | 6.80963 |
May | 508.00000 | 23.65336 | 41.38345 | -0.6284 | 14.38570 |
June | 496.00000 | 24.10259 | 48.66200 | -0.3771 | 8.64274 |
July | 497.00000 | 24.31024 | 51.52402 | -0.2677 | 7.26629 |
August | 514.00000 | 24.19908 | 48.71697 | -0.3267 | 7.89808 |
September | 485.00000 | 23.77707 | 46.90284 | -0.5362 | 12.03161 |
October | 502.00000 | 23.07597 | 40.50148 | 0.13932 | 7.12696 |
November | 489.00000 | 21.76152 | 32.45732 | -0.2667 | 8.74693 |
December | 497.00000 | 20.89659 | 24.71061 | -0.5406 | 12.45978 |
Annual Sum or Average | 5943.00000 | 22.64511 | 37.23535 | -0.3605 | 10.43420 |
Minimum of Months | 454.00000 | 20.51845 | 20.61835 | -0.6522 | 6.80963 |
Maximum of Months | 514.00000 | 24.31024 | 51.52402 | 0.13932 | 16.70682 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.31776 | 24.99318 | -0.6862 | 17.48443 |
February | 385.00000 | 20.71140 | 19.35552 | -0.5991 | 14.41423 |
March | 433.00000 | 21.59120 | 28.35369 | -0.2878 | 8.47590 |
April | 410.00000 | 22.56071 | 34.24413 | 0.00833 | 7.62102 |
May | 430.00000 | 23.30146 | 41.61532 | -0.6592 | 17.81598 |
June | 418.00000 | 23.69072 | 49.01609 | -0.4463 | 11.62879 |
July | 422.00000 | 24.00655 | 51.36621 | -0.3034 | 9.45734 |
August | 433.00000 | 23.93298 | 48.63949 | -0.3319 | 9.23216 |
September | 410.00000 | 23.33708 | 47.36528 | -0.6036 | 15.97849 |
October | 427.00000 | 22.69633 | 40.21553 | 0.09688 | 7.07879 |
November | 417.00000 | 21.38950 | 32.08664 | -0.3257 | 8.88981 |
December | 422.00000 | 20.74820 | 23.68896 | -0.5613 | 12.71672 |
Annual Sum or Average | 5034.00000 | 22.36775 | 36.85551 | -0.3904 | 11.71386 |
Minimum of Months | 385.00000 | 20.31776 | 19.35552 | -0.6862 | 7.07879 |
Maximum of Months | 433.00000 | 24.00655 | 51.36621 | 0.09688 | 17.81598 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.41681 | 24.69134 | -0.3920 | 13.23523 |
February | 454.00000 | 22.10115 | 18.96512 | -0.2405 | 10.44390 |
March | 514.00000 | 22.60280 | 27.38058 | -0.0398 | 7.85540 |
April | 485.00000 | 23.01047 | 33.85878 | 0.09667 | 7.44947 |
May | 508.00000 | 23.66302 | 41.22097 | -0.6048 | 14.11419 |
June | 496.00000 | 24.06294 | 48.56973 | -0.3770 | 8.86699 |
July | 497.00000 | 24.30336 | 51.19281 | -0.2527 | 7.33821 |
August | 514.00000 | 24.29019 | 48.04397 | -0.2477 | 7.30543 |
September | 485.00000 | 24.13034 | 45.50608 | -0.3448 | 9.77045 |
October | 502.00000 | 24.04554 | 37.72379 | 0.44397 | 11.40011 |
November | 489.00000 | 22.74905 | 30.35961 | 0.01343 | 8.14710 |
December | 497.00000 | 22.15171 | 22.86684 | -0.2024 | 9.57496 |
Annual Sum or Average | 5943.00000 | 23.21905 | 35.98975 | -0.1792 | 9.62655 |
Minimum of Months | 454.00000 | 21.41681 | 18.96512 | -0.6048 | 7.30543 |
Maximum of Months | 514.00000 | 24.30336 | 51.19281 | 0.44397 | 14.11419 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.62918 | 25.21258 | -0.5991 | 15.00201 |
February | 454.00000 | 20.93122 | 19.69317 | -0.5371 | 13.25030 |
March | 514.00000 | 21.90460 | 28.10095 | -0.1977 | 7.75669 |
April | 485.00000 | 22.61307 | 34.29047 | 0.03799 | 7.40947 |
May | 508.00000 | 23.29504 | 41.75325 | -0.6497 | 16.51555 |
June | 496.00000 | 23.87502 | 48.31770 | -0.3561 | 9.82476 |
July | 497.00000 | 24.08494 | 50.81000 | -0.2525 | 8.46468 |
August | 514.00000 | 24.14330 | 47.89970 | -0.2225 | 7.73677 |
September | 485.00000 | 23.34265 | 47.25171 | -0.5831 | 14.80742 |
October | 502.00000 | 22.87211 | 40.22484 | 0.15689 | 7.37250 |
November | 489.00000 | 21.52813 | 32.10257 | -0.2860 | 8.35458 |
December | 497.00000 | 20.99359 | 23.77988 | -0.4904 | 11.13146 |
Annual Sum or Average | 5943.00000 | 22.53151 | 36.74039 | -0.3301 | 10.61318 |
Minimum of Months | 454.00000 | 20.62918 | 19.69317 | -0.6497 | 7.37250 |
Maximum of Months | 514.00000 | 24.14330 | 50.81000 | 0.15689 | 16.51555 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02212 | 23.94078 | -0.8378 | 22.96890 |
February | 454.00000 | 20.16176 | 18.72421 | -0.8272 | 22.08373 |
March | 514.00000 | 21.03227 | 29.09167 | -0.4886 | 12.49753 |
April | 485.00000 | 22.06006 | 35.62895 | -0.1647 | 8.66992 |
May | 508.00000 | 23.27925 | 42.38222 | -0.7421 | 18.93698 |
June | 496.00000 | 23.99554 | 49.01738 | -0.3940 | 9.33987 |
July | 497.00000 | 24.27701 | 51.75176 | -0.2538 | 7.39745 |
August | 514.00000 | 24.12801 | 48.90431 | -0.3302 | 8.32050 |
September | 485.00000 | 23.46034 | 47.87219 | -0.6317 | 15.36535 |
October | 502.00000 | 22.33590 | 42.00939 | -0.0383 | 8.32665 |
November | 489.00000 | 20.80253 | 33.12155 | -0.5294 | 14.07777 |
December | 497.00000 | 20.12266 | 23.88826 | -0.7939 | 20.71273 |
Annual Sum or Average | 5943.00000 | 22.15609 | 37.32594 | -0.5005 | 13.99988 |
Minimum of Months | 454.00000 | 20.02212 | 18.72421 | -0.8378 | 7.39745 |
Maximum of Months | 514.00000 | 24.27701 | 51.75176 | -0.0383 | 22.96890 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03593 | 23.23993 | -0.8161 | 22.22141 |
February | 454.00000 | 20.27599 | 17.96524 | -0.7676 | 19.83847 |
March | 514.00000 | 21.15632 | 28.37329 | -0.4225 | 11.43631 |
April | 485.00000 | 22.23812 | 34.71485 | -0.0809 | 8.64340 |
May | 508.00000 | 23.14252 | 42.34926 | -0.6986 | 19.63775 |
June | 496.00000 | 23.69247 | 49.09808 | -0.4186 | 11.08270 |
July | 497.00000 | 24.02940 | 51.28810 | -0.2608 | 8.85270 |
August | 514.00000 | 23.95664 | 48.48099 | -0.2907 | 8.68065 |
September | 485.00000 | 23.22119 | 47.88384 | -0.6287 | 16.99467 |
October | 502.00000 | 22.35448 | 41.42802 | 0.01318 | 7.94249 |
November | 489.00000 | 20.77402 | 32.56641 | -0.5090 | 13.20780 |
December | 497.00000 | 20.18450 | 23.13011 | -0.7609 | 19.45868 |
Annual Sum or Average | 5943.00000 | 22.10361 | 36.84333 | -0.4680 | 13.95354 |
Minimum of Months | 454.00000 | 20.03593 | 17.96524 | -0.8161 | 7.94249 |
Maximum of Months | 514.00000 | 24.02940 | 51.28810 | 0.01318 | 22.22141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72354 | 22.99911 | -0.6133 | 18.59375 |
February | 454.00000 | 21.20031 | 17.50752 | -0.5112 | 15.77128 |
March | 514.00000 | 21.82209 | 27.61783 | -0.2547 | 10.67333 |
April | 485.00000 | 22.37878 | 34.70689 | -0.0639 | 8.82557 |
May | 508.00000 | 23.27264 | 42.26567 | -0.7229 | 18.81604 |
June | 496.00000 | 23.93190 | 48.98895 | -0.4010 | 9.77915 |
July | 497.00000 | 24.24925 | 51.49198 | -0.2452 | 7.63925 |
August | 514.00000 | 24.19595 | 48.30386 | -0.2587 | 7.82129 |
September | 485.00000 | 23.82143 | 46.46306 | -0.4391 | 12.39214 |
October | 502.00000 | 23.43602 | 39.01660 | 0.29159 | 10.40713 |
November | 489.00000 | 21.80643 | 31.14728 | -0.2430 | 10.94792 |
December | 497.00000 | 21.16688 | 22.42957 | -0.4929 | 15.20865 |
Annual Sum or Average | 5943.00000 | 22.67900 | 36.21252 | -0.3287 | 12.22167 |
Minimum of Months | 454.00000 | 20.72354 | 17.50752 | -0.7229 | 7.63925 |
Maximum of Months | 514.00000 | 24.24925 | 51.49198 | 0.29159 | 18.81604 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19950 | 22.93094 | -0.7611 | 20.39879 |
February | 454.00000 | 20.48074 | 17.71169 | -0.7064 | 18.42546 |
March | 514.00000 | 21.36748 | 27.81746 | -0.3573 | 10.44074 |
April | 485.00000 | 22.11654 | 34.84067 | -0.0912 | 8.59741 |
May | 508.00000 | 22.95048 | 42.70683 | -0.7523 | 20.75870 |
June | 496.00000 | 23.70765 | 48.85031 | -0.3907 | 11.01015 |
July | 497.00000 | 23.99496 | 51.25918 | -0.2566 | 8.99321 |
August | 514.00000 | 24.01355 | 48.26495 | -0.2462 | 8.53690 |
September | 485.00000 | 23.04187 | 48.20325 | -0.6727 | 18.15429 |
October | 502.00000 | 22.34347 | 41.37623 | 0.02600 | 7.94366 |
November | 489.00000 | 20.87050 | 32.26528 | -0.4776 | 12.22496 |
December | 497.00000 | 20.42612 | 22.64614 | -0.6868 | 16.87444 |
Annual Sum or Average | 5943.00000 | 22.14089 | 36.70528 | -0.4457 | 13.48861 |
Minimum of Months | 454.00000 | 20.19950 | 17.71169 | -0.7611 | 7.94366 |
Maximum of Months | 514.00000 | 24.01355 | 51.25918 | 0.02600 | 20.75870 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.280259E+09 | 16791.08 | 24-JAN-06:03 | 21.68 | 0.777909E+09 | 0.00 | 0.105817E+10 | 0.08 | 2.78 | 19-JAN-20:40 | 0.00 | 0.00 |
February | 0.191479E+09 | 6730.47 | 22-FEB-10:35 | 14.86 | 0.531574E+09 | 0.00 | 0.723052E+09 | 0.06 | 2.78 | 22-FEB-10:50 | 0.00 | 0.00 |
March | 0.481616E+10 | 111825.49 | 27-MAR-13:40 | 47.26 | 0.213057E+11 | 0.00 | 0.261219E+11 | 0.21 | 6.88 | 27-MAR-13:40 | 0.00 | 0.00 |
April | 0.275211E+11 | 123282.94 | 07-APR-13:40 | 155.89 | 0.141592E+12 | 0.00 | 0.169113E+12 | 0.90 | 7.03 | 07-APR-13:40 | 0.00 | 0.00 |
May | 0.904039E+11 | 131505.88 | 30-MAY-10:30 | 382.03 | 0.486562E+12 | 0.00 | 0.576966E+12 | 2.42 | 7.02 | 30-MAY-11:00 | 0.00 | 0.00 |
June | 0.175272E+12 | 204305.89 | 27-JUN-05:02 | 528.96 | 0.109680E+13 | 0.00 | 0.127207E+13 | 4.24 | 7.26 | 30-JUN-05:02 | 0.00 | 0.00 |
July | 0.213196E+12 | 214723.37 | 22-JUL-05:02 | 614.72 | 0.131007E+13 | 0.00 | 0.152326E+13 | 4.59 | 7.26 | 19-JUL-05:02 | 0.00 | 0.00 |
August | 0.213241E+12 | 192766.34 | 04-AUG-05:02 | 640.50 | 0.131431E+13 | 0.00 | 0.152755E+13 | 4.75 | 7.27 | 25-AUG-14:40 | 0.00 | 0.00 |
September | 0.140323E+12 | 221950.54 | 14-SEP-05:02 | 449.97 | 0.848713E+12 | 0.00 | 0.989036E+12 | 3.49 | 7.14 | 02-SEP-05:03 | 0.00 | 0.00 |
October | 0.755550E+11 | 136525.78 | 06-OCT-05:02 | 286.93 | 0.438452E+12 | 0.00 | 0.514007E+12 | 1.97 | 7.10 | 06-OCT-05:02 | 0.00 | 0.00 |
November | 0.711222E+10 | 74087.21 | 10-NOV-10:00 | 59.38 | 0.254038E+11 | 0.00 | 0.325160E+11 | 0.26 | 5.76 | 10-NOV-10:00 | 0.00 | 0.00 |
December | 0.227188E+09 | 16934.75 | 07-DEC-11:40 | 10.75 | 0.630558E+09 | 0.00 | 0.857746E+09 | 0.04 | 2.78 | 21-DEC-14:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.948140E+12 | 3212.93 | 0.568514E+13 | 0.663328E+13 | 1.93 | |||||||
Minimum of Months | 0.191479E+09 | 6730.47 | 10.75 | 0.531574E+09 | 0.00 | 0.723052E+09 | 0.04 | 2.78 | 0.00 | 0.00 | ||
Maximum of Months | 0.213241E+12 | 221950.54 | 640.50 | 0.131431E+13 | 0.00 | 0.152755E+13 | 4.75 | 7.27 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.268927E+09 | 112549.98 | 07-APR-14:30 | 0.67 | 0.185009E+10 | 0.00 | 0.211901E+10 | 0.01 | 6.89 | 07-APR-14:30 | 0.00 | 0.00 |
May | 0.533104E+10 | 129988.20 | 31-MAY-13:10 | 12.33 | 0.362647E+11 | 0.00 | 0.415957E+11 | 0.11 | 7.02 | 30-MAY-11:00 | 0.00 | 0.00 |
June | 0.609848E+11 | 204305.89 | 27-JUN-05:02 | 136.37 | 0.404456E+12 | 0.00 | 0.465441E+12 | 1.26 | 7.26 | 30-JUN-05:02 | 0.00 | 0.00 |
July | 0.103444E+12 | 214723.37 | 22-JUL-05:02 | 218.72 | 0.667314E+12 | 0.00 | 0.770759E+12 | 1.90 | 7.26 | 19-JUL-05:02 | 0.00 | 0.00 |
August | 0.943487E+11 | 192766.34 | 04-AUG-05:02 | 197.37 | 0.610758E+12 | 0.00 | 0.705107E+12 | 1.72 | 7.27 | 25-AUG-14:40 | 0.00 | 0.00 |
September | 0.381647E+11 | 221950.54 | 14-SEP-05:02 | 85.52 | 0.253248E+12 | 0.00 | 0.291413E+12 | 0.79 | 7.14 | 02-SEP-05:03 | 0.00 | 0.00 |
October | 0.100999E+11 | 136525.78 | 06-OCT-05:02 | 23.57 | 0.682610E+11 | 0.00 | 0.783609E+11 | 0.21 | 7.10 | 06-OCT-05:02 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.312642E+12 | 674.56 | 0.204215E+13 | 0.235480E+13 | 0.50 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.103444E+12 | 221950.54 | 218.72 | 0.667314E+12 | 0.00 | 0.770759E+12 | 1.90 | 7.27 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.100137E+11 | 744.00 | 17564.62 | 21-JAN-18:17 | 537440.79 | 28-JAN-01:01 | 21.60 | 18.33 | 13.89 |
February | 0.138872E+11 | 672.00 | 17232.54 | 16-FEB-13:10 | 570515.20 | 26-FEB-07:51 | 24.43 | 18.33 | 13.86 |
March | 0.457367E+11 | 744.00 | 49248.27 | 02-MAR-15:40 | 604791.18 | 18-MAR-18:03 | 27.39 | 18.40 | 13.91 |
April | 0.943038E+11 | 720.00 | 49248.27 | 05-APR-10:50 | 634626.15 | 07-APR-17:20 | 31.25 | 19.39 | 13.97 |
May | 0.824869E+11 | 744.00 | 49248.27 | 01-MAY-10:50 | 540391.81 | 01-MAY-21:17 | 23.27 | 19.63 | 13.97 |
June | 0.126885E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 382916.46 | 19-JUN-12:20 | 31.19 | 24.53 | 13.98 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 531358.61 | 07-JUL-12:20 | 39.04 | 29.20 | 13.98 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 664167.13 | 04-AUG-21:02 | 42.75 | 30.15 | 13.98 |
September | 0.113345E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 434768.36 | 01-SEP-00:03 | 25.80 | 22.05 | 13.98 |
October | 0.904277E+11 | 744.00 | 49248.27 | 02-OCT-08:20 | 587526.16 | 28-OCT-19:00 | 25.98 | 19.55 | 13.96 |
November | 0.568475E+11 | 720.00 | 49248.27 | 02-NOV-11:40 | 602341.19 | 14-NOV-22:13 | 27.38 | 18.40 | 13.94 |
December | 0.488278E+11 | 744.00 | 43423.40 | 17-DEC-15:00 | 616872.44 | 29-DEC-22:12 | 29.97 | 18.33 | 13.96 |
Annual Sum or Average | 0.946575E+12 | 8760.00 | 29.21 | 21.39 | 13.95 | ||||
Minimum of Months | 0.100137E+11 | 672.00 | 17232.54 | 382916.46 | 21.60 | 18.33 | 13.86 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 664167.13 | 42.75 | 30.15 | 13.98 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 216383.01 | 30-JAN-05:36 | 20.99 | 20.99 | 0.27 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 217210.66 | 17-FEB-06:30 | 20.97 | 20.96 | 0.20 |
March | 0.270791E+09 | 16.25 | 23224.97 | 27-MAR-12:50 | 860891.73 | 27-MAR-15:50 | 21.04 | 21.00 | 2.28 |
April | 0.132439E+10 | 98.97 | 20280.30 | 07-APR-15:40 | 929296.86 | 07-APR-15:40 | 21.33 | 21.06 | 11.34 |
May | 0.729720E+10 | 328.60 | 23224.97 | 18-MAY-09:20 | 1013019.03 | 30-MAY-14:00 | 22.20 | 21.35 | 30.59 |
June | 0.333656E+11 | 515.65 | 23224.97 | 01-JUN-07:40 | 1151865.77 | 27-JUN-16:00 | 24.68 | 22.75 | 44.35 |
July | 0.494576E+11 | 614.72 | 23224.97 | 01-JUL-03:01 | 1232797.34 | 26-JUL-16:00 | 26.43 | 24.19 | 47.77 |
August | 0.427552E+11 | 624.94 | 23224.97 | 01-AUG-00:20 | 1262017.14 | 02-AUG-15:10 | 25.57 | 23.33 | 51.24 |
September | 0.201872E+11 | 431.66 | 23224.97 | 01-SEP-02:32 | 1142001.82 | 01-SEP-14:00 | 23.94 | 22.44 | 38.06 |
October | 0.102032E+11 | 245.13 | 23224.97 | 02-OCT-14:40 | 1019207.50 | 24-OCT-13:20 | 22.22 | 21.45 | 22.92 |
November | 0.122379E+09 | 29.72 | 5730.77 | 10-NOV-10:00 | 507220.55 | 10-NOV-10:10 | 21.11 | 21.05 | 3.52 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 217038.44 | 28-DEC-18:00 | 21.00 | 21.00 | 0.11 |
Annual Sum or Average | 0.164984E+12 | 2905.63 | 22.63 | 21.80 | 21.19 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 216383.01 | 20.97 | 20.96 | 0.11 | ||
Maximum of Months | 0.494576E+11 | 624.94 | 23224.97 | 1262017.14 | 26.43 | 24.19 | 51.24 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 20.99 | 20.99 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.97 | 20.97 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.04 | 21.04 | 0.00 |
April | 46354738.51 | 0.67 | 19803.05 | 07-APR-15:20 | 928989.66 | 07-APR-14:30 | 21.33 | 21.32 | 0.06 |
May | 0.117054E+10 | 14.00 | 23224.97 | 19-MAY-11:40 | 1013019.03 | 30-MAY-14:00 | 22.20 | 22.13 | 1.15 |
June | 0.156279E+11 | 186.93 | 23224.97 | 01-JUN-09:50 | 1151865.77 | 27-JUN-16:00 | 24.68 | 23.76 | 14.87 |
July | 0.293492E+11 | 351.03 | 23224.97 | 01-JUL-05:03 | 1232797.34 | 26-JUL-16:00 | 26.43 | 24.74 | 25.53 |
August | 0.233089E+11 | 279.96 | 23224.97 | 01-AUG-04:30 | 1262017.14 | 02-AUG-15:10 | 25.57 | 24.18 | 21.06 |
September | 0.938138E+10 | 112.21 | 23224.97 | 01-SEP-03:25 | 1142001.82 | 01-SEP-14:00 | 23.94 | 23.38 | 8.99 |
October | 0.211533E+10 | 25.30 | 23224.97 | 03-OCT-11:00 | 1019207.50 | 24-OCT-13:20 | 22.22 | 22.10 | 2.13 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.11 | 21.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.00 | 21.00 | 0.00 |
Annual Sum or Average | 0.809996E+11 | 970.09 | 22.63 | 22.23 | 6.20 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 20.97 | 0.00 | ||
Maximum of Months | 0.293492E+11 | 351.03 | 23224.97 | 1262017.14 | 26.43 | 24.74 | 25.53 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.293690E+12 | 0.00 | 514.77 | 2113347.35 | 02-JAN-07:10 | 0.00 | 70.97 | 78.30 | 2.33 | 0.00 | 0.06 | 1.20 | 02-JAN-07:10 |
February | 0.229423E+12 | 0.00 | 450.71 | 1761532.69 | 06-FEB-07:10 | 0.00 | 68.97 | 77.53 | 1.65 | 0.00 | 0.05 | 1.00 | 06-FEB-07:10 |
March | 0.115224E+12 | 0.00 | 392.47 | 1072211.99 | 23-MAR-06:10 | 0.00 | 64.04 | 73.29 | 0.59 | 0.00 | 0.02 | 0.61 | 23-MAR-06:10 |
April | 0.362318E+11 | 0.00 | 239.51 | 1106690.05 | 22-APR-05:01 | 0.00 | 56.23 | 64.66 | 0.13 | 0.00 | 0.01 | 0.63 | 22-APR-05:01 |
May | 0.314695E+10 | 0.00 | 57.76 | 676122.80 | 29-MAY-02:40 | 0.00 | 59.27 | 60.69 | 0.03 | 0.00 | 0.00 | 0.38 | 29-MAY-02:40 |
June | 0.111024E+10 | 0.00 | 7.80 | 470807.56 | 04-JUN-16:47 | 0.00 | 69.11 | 69.26 | 0.01 | 0.00 | 0.00 | 0.27 | 04-JUN-16:47 |
July | 0.113900E+10 | 0.00 | 3.11 | 331261.15 | 16-JUL-14:20 | 0.00 | 72.19 | 72.23 | 0.01 | 0.00 | 0.00 | 0.19 | 16-JUL-14:20 |
August | 0.924064E+09 | 0.00 | 8.10 | 576882.89 | 27-AUG-11:58 | 0.00 | 70.35 | 70.52 | 0.01 | 0.00 | 0.00 | 0.33 | 27-AUG-11:58 |
September | 0.117423E+10 | 0.00 | 21.95 | 439716.09 | 03-SEP-11:58 | 0.00 | 69.74 | 70.12 | 0.01 | 0.00 | 0.00 | 0.25 | 03-SEP-11:58 |
October | 0.126593E+11 | 0.00 | 114.02 | 429785.48 | 01-OCT-19:10 | 0.00 | 69.13 | 70.76 | 0.13 | 0.00 | 0.00 | 0.24 | 01-OCT-19:10 |
November | 0.892825E+11 | 0.00 | 345.30 | 1205171.77 | 24-NOV-07:10 | 0.00 | 64.59 | 72.71 | 0.49 | 0.00 | 0.02 | 0.68 | 24-NOV-07:10 |
December | 0.183514E+12 | 0.00 | 451.39 | 1361304.33 | 22-DEC-07:10 | 0.00 | 58.26 | 72.26 | 0.73 | 0.00 | 0.04 | 0.77 | 22-DEC-07:10 |
Annual Sum or Average | 0.967520E+12 | 2606.90 | 66.06 | 70.99 | 0.50 | 0.00 | 0.02 | ||||||
Minimum of Months | 0.924064E+09 | 0.00 | 3.11 | 331261.15 | 0.00 | 56.23 | 60.69 | 0.01 | 0.00 | 0.00 | 0.19 | ||
Maximum of Months | 0.293690E+12 | 0.00 | 514.77 | 2113347.35 | 0.00 | 72.19 | 78.30 | 2.33 | 0.00 | 0.06 | 1.20 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 21.60 | 21.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.43 | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.39 | 27.39 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.25 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 23.27 | 23.27 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.19 | 31.19 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 39.04 | 39.04 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 42.75 | 42.75 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.98 | 25.98 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.38 | 27.38 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.97 | 29.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.21 | 29.21 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 21.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 | 42.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 14116267.72 | 0.00 | 1.67 | 6294599.66 | 0.00 | 0.00 | 0.00 | 0.00 | 42058.00 | 24-JAN-06:03 | 18487.81 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 1781617.06 | 0.00 | 1.45 | 1781617.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7168.51 | 20-FEB-12:50 | 7168.51 | 20-FEB-12:50 | 0.00 | 0.00 | 0.00 |
March | 0.757143E+09 | 0.00 | 8.95 | 0.756630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48580.86 | 27-MAR-16:00 | 48580.86 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.658952E+10 | 0.00 | 74.32 | 0.647639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82084.04 | 28-APR-03:01 | 72779.41 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.195188E+11 | 0.00 | 196.86 | 0.181441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125652.60 | 29-MAY-11:38 | 120434.51 | 29-MAY-10:18 | 0.00 | 0.00 | 0.00 |
June | 0.761823E+11 | 0.00 | 409.41 | 0.639890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186427.39 | 25-JUN-14:41 | 120044.80 | 11-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.108800E+12 | 0.00 | 454.31 | 0.877088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191044.73 | 23-JUL-15:12 | 122363.15 | 16-JUL-14:23 | 0.00 | 0.00 | 0.00 |
August | 0.106681E+12 | 0.00 | 465.40 | 0.905074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169689.77 | 04-AUG-03:01 | 136157.48 | 13-AUG-13:21 | 0.00 | 0.00 | 0.00 |
September | 0.572638E+11 | 0.00 | 354.68 | 0.502838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168049.46 | 01-SEP-03:01 | 119585.61 | 04-SEP-20:49 | 0.00 | 0.00 | 0.00 |
October | 0.228056E+11 | 0.00 | 192.73 | 0.189145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130351.28 | 06-OCT-05:04 | 81806.53 | 15-OCT-13:16 | 0.00 | 0.00 | 0.00 |
November | 0.326551E+09 | 0.00 | 11.27 | 0.293426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87135.81 | 10-NOV-06:02 | 35359.56 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 7664040.20 | 0.00 | 0.53 | 6048446.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17074.86 | 25-DEC-09:01 | 10682.26 | 25-DEC-14:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398948E+12 | 2171.59 | 0.337088E+12 | ||||||||||||
Minimum of Months | 1781617.06 | 0.00 | 0.53 | 1781617.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7168.51 | 7168.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108800E+12 | 0.00 | 465.40 | 0.905074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191044.73 | 136157.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2077.36 | 0.00 | 1.91 | 2077.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 04-JAN-06:01 | 1.02 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 423.07 | 0.00 | 0.56 | 423.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 03-FEB-05:01 | 0.68 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 |
March | 0.221884E+10 | 0.00 | 34.34 | 0.188115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94693.26 | 27-MAR-13:00 | 74686.45 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.153905E+11 | 0.00 | 146.62 | 0.152204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109914.97 | 07-APR-13:50 | 109914.97 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.485121E+11 | 0.00 | 364.46 | 0.402846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141783.04 | 31-MAY-14:00 | 139520.90 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.152055E+12 | 0.00 | 500.23 | 0.106820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 197598.82 | 19-JUN-09:10 | 152676.53 | 21-JUN-05:01 | 0.00 | 0.00 | 0.00 |
July | 0.220324E+12 | 0.00 | 569.15 | 0.146134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 212503.55 | 20-JUL-15:00 | 161085.08 | 17-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.218849E+12 | 0.00 | 613.23 | 0.161393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225456.55 | 04-AUG-14:00 | 157611.24 | 02-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.103347E+12 | 0.00 | 428.35 | 0.774277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213306.03 | 14-SEP-03:01 | 163915.32 | 06-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.522698E+11 | 0.00 | 274.67 | 0.362241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152689.96 | 06-OCT-03:02 | 111046.33 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 |
November | 0.236913E+10 | 0.00 | 47.92 | 0.205026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48847.98 | 10-NOV-10:00 | 39778.52 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 188.31 | 0.00 | 0.16 | 188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 08-DEC-06:02 | 0.63 | 08-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815336E+12 | 2981.59 | 0.587435E+12 | ||||||||||||
Minimum of Months | 188.31 | 0.00 | 0.16 | 188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.220324E+12 | 0.00 | 613.23 | 0.161393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225456.55 | 163915.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.138969E+09 | 0.00 | 16.08 | 0.138969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26708.92 | 19-JAN-14:40 | 26708.92 | 19-JAN-14:40 | 0.00 | 0.00 | 0.00 |
February | 63702036.43 | 0.00 | 12.70 | 63702036.43 | 0.00 | 0.00 | 0.00 | 0.00 | 37088.82 | 22-FEB-10:35 | 37088.82 | 22-FEB-10:35 | 0.00 | 0.00 | 0.00 |
March | 0.157964E+11 | 0.00 | 40.94 | 0.136649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 659038.63 | 27-MAR-13:00 | 552588.26 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.109549E+12 | 0.00 | 118.12 | 0.109047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 951806.43 | 07-APR-13:40 | 951806.43 | 07-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.416648E+12 | 0.00 | 349.71 | 0.345962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1311045.42 | 30-MAY-14:00 | 1311045.42 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.123742E+13 | 0.00 | 448.99 | 0.840539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2037279.76 | 27-JUN-05:02 | 1488775.75 | 20-JUN-03:01 | 0.00 | 0.00 | 0.00 |
July | 0.155889E+13 | 0.00 | 459.81 | 0.105476E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2650257.98 | 24-JUL-03:01 | 1512067.05 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.148874E+13 | 0.00 | 480.26 | 0.114424E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2145779.13 | 04-AUG-03:01 | 1712997.22 | 25-AUG-14:40 | 0.00 | 0.00 | 0.00 |
September | 0.883572E+12 | 0.00 | 409.06 | 0.658379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2206526.77 | 14-SEP-05:02 | 1596338.80 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.432943E+12 | 0.00 | 261.41 | 0.289810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1351821.05 | 06-OCT-04:02 | 894251.35 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.184076E+11 | 0.00 | 50.47 | 0.160704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 345681.43 | 10-NOV-10:00 | 309790.84 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.298781E+09 | 0.00 | 9.86 | 0.298781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76643.38 | 07-DEC-11:40 | 76643.38 | 07-DEC-11:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.616246E+13 | 2657.39 | 0.447297E+13 | ||||||||||||
Minimum of Months | 63702036.43 | 0.00 | 9.86 | 63702036.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26708.92 | 26708.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.155889E+13 | 0.00 | 480.26 | 0.114424E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2650257.98 | 1712997.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4616457.29 | 0.00 | 2.21 | 4616457.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2302.38 | 15-JAN-10:40 | 2302.38 | 15-JAN-10:40 | 0.00 | 0.00 | 0.00 |
February | 29503.08 | 0.00 | 0.67 | 29503.08 | 0.00 | 0.00 | 0.00 | 0.00 | 479.11 | 07-FEB-05:03 | 479.11 | 07-FEB-05:03 | 0.00 | 0.00 | 0.00 |
March | 0.138299E+10 | 0.00 | 28.42 | 0.121927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53400.93 | 27-MAR-16:00 | 49243.54 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.112690E+11 | 0.00 | 111.42 | 0.112286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104672.39 | 07-APR-15:30 | 104672.39 | 07-APR-15:30 | 0.00 | 0.00 | 0.00 |
May | 0.443378E+11 | 0.00 | 349.48 | 0.370194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160318.46 | 31-MAY-14:00 | 149518.76 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.141447E+12 | 0.00 | 443.07 | 0.954095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218201.29 | 19-JUN-14:00 | 161083.96 | 19-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.204368E+12 | 0.00 | 461.28 | 0.125876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290910.59 | 24-JUL-03:01 | 161059.69 | 24-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.193844E+12 | 0.00 | 476.26 | 0.134312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243930.87 | 04-AUG-14:00 | 164130.82 | 05-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.952751E+11 | 0.00 | 397.61 | 0.692112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209057.46 | 14-SEP-04:02 | 164991.06 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 |
October | 0.421936E+11 | 0.00 | 253.53 | 0.281582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149148.71 | 06-OCT-05:03 | 102408.34 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 |
November | 0.162109E+10 | 0.00 | 41.98 | 0.142601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29326.68 | 03-NOV-14:00 | 29326.68 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 235.58 | 0.00 | 0.26 | 235.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 30-DEC-05:01 | 0.34 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735744E+12 | 2566.17 | 0.503865E+12 | ||||||||||||
Minimum of Months | 235.58 | 0.00 | 0.26 | 235.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.204368E+12 | 0.00 | 476.26 | 0.134312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290910.59 | 164991.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.308903E+12 | 0.792605E+11 | 732.08 | 0.308847E+12 | 56056750.90 | 0.00 | 1.00 | 02-JAN-22:10 | 0.01 | 18-JAN-22:22 | 432632.41 | 09-JAN-20:31 | 432632.41 | 09-JAN-20:31 | 23988.25 | 28-JAN-22:00 | 91719.50 | 09-JAN-20:31 | 0.00 |
February | 0.490143E+12 | 0.118576E+12 | 665.93 | 0.489984E+12 | 0.158500E+09 | 0.00 | 1.00 | 03-FEB-22:30 | 0.01 | 27-FEB-23:17 | 438202.29 | 07-FEB-23:17 | 438202.29 | 07-FEB-23:17 | 16288.81 | 26-FEB-06:10 | 91815.02 | 07-FEB-23:17 | 0.00 |
March | 0.781043E+12 | 0.179120E+12 | 743.80 | 0.780929E+12 | 0.113920E+09 | 0.00 | 1.00 | 04-MAR-18:10 | 0.01 | 25-MAR-19:10 | 436538.33 | 25-MAR-18:07 | 436538.33 | 25-MAR-18:07 | 27032.52 | 25-MAR-19:05 | 91786.48 | 25-MAR-18:07 | 0.00 |
April | 0.987969E+12 | 0.225832E+12 | 720.00 | 0.987953E+12 | 15577700.22 | 0.00 | 1.00 | 01-APR-16:10 | 0.73 | 05-APR-05:03 | 425751.94 | 17-APR-21:25 | 425751.94 | 17-APR-21:25 | 1503.43 | 27-APR-21:00 | 125644.98 | 07-APR-13:00 | 0.00 |
May | 0.317574E+12 | 0.829131E+11 | 742.93 | 0.316198E+12 | 0.137637E+10 | 0.00 | 1.00 | 01-MAY-01:21 | 0.03 | 16-MAY-04:02 | 424849.14 | 16-MAY-03:04 | 424849.14 | 16-MAY-03:04 | 8829.10 | 16-MAY-04:40 | 91586.02 | 16-MAY-03:04 | 0.00 |
June | 0.542031E+12 | 0.154118E+12 | 720.00 | 0.536480E+12 | 0.555102E+10 | 0.00 | 0.63 | 19-JUN-12:00 | 0.52 | 01-JUN-06:05 | 219690.99 | 15-JUN-12:50 | 212337.64 | 19-JUN-12:00 | 10608.39 | 15-JUN-13:50 | 91903.38 | 19-JUN-12:00 | 0.00 |
July | 0.800713E+12 | 0.248461E+12 | 744.00 | 0.792066E+12 | 0.864666E+10 | 0.00 | 0.84 | 07-JUL-12:00 | 0.73 | 01-JUL-00:10 | 309488.17 | 20-JUL-15:00 | 299893.34 | 10-JUL-15:00 | 11415.89 | 20-JUL-15:00 | 119114.88 | 07-JUL-12:00 | 0.00 |
August | 0.103361E+13 | 0.317592E+12 | 744.00 | 0.102793E+13 | 0.568008E+10 | 0.00 | 1.00 | 01-AUG-08:50 | 0.92 | 08-AUG-05:00 | 397804.07 | 18-AUG-19:00 | 389118.85 | 03-AUG-21:02 | 11969.38 | 16-AUG-20:00 | 144461.36 | 24-AUG-16:00 | 0.00 |
September | 0.314418E+12 | 0.874456E+11 | 720.00 | 0.310995E+12 | 0.342337E+10 | 0.00 | 0.38 | 01-SEP-00:03 | 0.31 | 23-SEP-06:20 | 136660.61 | 01-SEP-00:10 | 135259.05 | 01-SEP-00:10 | 8911.20 | 22-SEP-18:20 | 48181.05 | 01-SEP-14:00 | 0.00 |
October | 0.557095E+12 | 0.136879E+12 | 743.20 | 0.554442E+12 | 0.265234E+10 | 0.00 | 1.00 | 18-OCT-21:10 | 0.06 | 28-OCT-17:40 | 442121.60 | 28-OCT-19:00 | 442121.60 | 28-OCT-19:00 | 12268.51 | 28-OCT-20:20 | 91882.24 | 28-OCT-19:00 | 0.00 |
November | 0.761210E+12 | 0.174257E+12 | 719.49 | 0.761088E+12 | 0.121985E+09 | 0.00 | 1.00 | 07-NOV-22:17 | 0.01 | 08-NOV-02:48 | 436289.53 | 26-NOV-08:44 | 436289.53 | 26-NOV-08:44 | 19880.82 | 08-NOV-05:35 | 91782.22 | 26-NOV-08:44 | 0.00 |
December | 0.101956E+13 | 0.225509E+12 | 744.00 | 0.101956E+13 | 0.00 | 0.00 | 1.00 | 01-DEC-22:10 | 0.66 | 25-DEC-02:42 | 424087.94 | 09-DEC-19:55 | 424087.94 | 09-DEC-19:55 | 0.00 | 01-DEC-00:10 | 91572.96 | 09-DEC-19:55 | 0.00 |
Annual Sum or Average | 0.791427E+13 | 0.202996E+13 | 8739.42 | 0.788648E+13 | 0.277959E+11 | ||||||||||||||
Minimum of Months | 0.308903E+12 | 0.792605E+11 | 665.93 | 0.308847E+12 | 0.00 | 0.00 | 0.38 | 0.01 | 136660.61 | 135259.05 | 0.00 | 48181.05 | 0.00 | ||||||
Maximum of Months | 0.103361E+13 | 0.317592E+12 | 744.00 | 0.102793E+13 | 0.864666E+10 | 0.00 | 1.00 | 0.92 | 442121.60 | 442121.60 | 27032.52 | 144461.36 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.420505E+10 | 0.121879E+10 | 744.00 | 0.420505E+10 | 0.00 | 0.00 | 0.36 | 20-JAN-16:20 | 0.17 | 02-JAN-06:17 | 2423.64 | 20-JAN-16:20 | 2423.64 | 20-JAN-16:20 | 0.00 | 01-JAN-00:01 | 678.28 | 20-JAN-16:20 | 0.00 |
February | 0.861158E+10 | 0.232582E+10 | 672.00 | 0.861158E+10 | 0.00 | 0.00 | 0.62 | 14-FEB-17:00 | 0.43 | 06-FEB-06:25 | 4466.96 | 14-FEB-17:00 | 4466.96 | 14-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1174.64 | 14-FEB-17:00 | 0.00 |
March | 0.151530E+11 | 0.388837E+10 | 744.00 | 0.151530E+11 | 0.00 | 0.00 | 0.90 | 27-MAR-17:00 | 0.71 | 01-MAR-00:10 | 6395.20 | 29-MAR-17:10 | 6395.20 | 29-MAR-17:10 | 0.00 | 01-MAR-00:10 | 2027.00 | 27-MAR-17:00 | 0.00 |
April | 0.194835E+11 | 0.497477E+10 | 720.00 | 0.194835E+11 | 0.00 | 0.00 | 1.00 | 02-APR-16:35 | 0.94 | 01-APR-07:00 | 7886.74 | 23-APR-18:02 | 7886.74 | 23-APR-18:02 | 0.00 | 01-APR-00:10 | 2617.77 | 07-APR-13:00 | 0.00 |
May | 0.557312E+10 | 0.166383E+10 | 744.00 | 0.557312E+10 | 0.00 | 0.00 | 0.40 | 30-MAY-17:50 | 0.26 | 04-MAY-21:15 | 2550.97 | 30-MAY-18:00 | 2550.97 | 30-MAY-18:00 | 0.00 | 01-MAY-00:01 | 995.79 | 30-MAY-16:00 | 0.00 |
June | 0.103462E+11 | 0.342779E+10 | 720.00 | 0.103462E+11 | 0.00 | 0.00 | 0.70 | 19-JUN-12:00 | 0.53 | 03-JUN-07:00 | 4490.50 | 18-JUN-17:58 | 4490.50 | 18-JUN-17:58 | 0.00 | 01-JUN-00:10 | 2125.24 | 19-JUN-12:00 | 0.00 |
July | 0.155902E+11 | 0.569714E+10 | 744.00 | 0.155902E+11 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.80 | 02-JUL-05:00 | 6405.55 | 12-JUL-18:20 | 6405.55 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 2810.34 | 07-JUL-12:00 | 0.00 |
August | 0.189418E+11 | 0.674614E+10 | 744.00 | 0.189418E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-00:05 | 0.99 | 08-AUG-05:00 | 7604.30 | 08-AUG-04:12 | 7604.30 | 08-AUG-04:12 | 0.00 | 01-AUG-00:05 | 3007.52 | 24-AUG-16:00 | 0.00 |
September | 0.549116E+10 | 0.178248E+10 | 720.00 | 0.549116E+10 | 0.00 | 0.00 | 0.72 | 01-SEP-00:03 | 0.26 | 23-SEP-17:20 | 4888.73 | 01-SEP-00:03 | 4888.73 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 1709.50 | 01-SEP-00:03 | 0.00 |
October | 0.105543E+11 | 0.295312E+10 | 744.00 | 0.105543E+11 | 0.00 | 0.00 | 0.67 | 04-OCT-16:20 | 0.50 | 28-OCT-06:55 | 4522.90 | 04-OCT-16:30 | 4522.90 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 1528.03 | 02-OCT-16:40 | 0.00 |
November | 0.146272E+11 | 0.375905E+10 | 720.00 | 0.146272E+11 | 0.00 | 0.00 | 0.83 | 03-NOV-16:00 | 0.71 | 25-NOV-18:13 | 6199.66 | 06-NOV-16:10 | 6199.66 | 06-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1681.86 | 03-NOV-14:00 | 0.00 |
December | 0.198809E+11 | 0.490990E+10 | 744.00 | 0.198809E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-15:30 | 0.93 | 30-DEC-18:20 | 7808.03 | 21-DEC-16:20 | 7808.03 | 21-DEC-16:20 | 0.00 | 01-DEC-00:10 | 1900.25 | 21-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.148458E+12 | 0.433472E+11 | 8760.00 | 0.148458E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.420505E+10 | 0.121879E+10 | 672.00 | 0.420505E+10 | 0.00 | 0.00 | 0.36 | 0.17 | 2423.64 | 2423.64 | 0.00 | 678.28 | 0.00 | ||||||
Maximum of Months | 0.198809E+11 | 0.674614E+10 | 744.00 | 0.198809E+11 | 0.00 | 0.00 | 1.00 | 0.99 | 7886.74 | 7886.74 | 0.00 | 3007.52 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.200872E+11 | 0.604555E+10 | 600.91 | 0.200872E+11 | 0.00 | 0.00 | 0.33 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 21460.79 | 20-JAN-16:30 | 21460.79 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 6045.24 | 20-JAN-16:30 | 0.00 |
February | 0.657562E+11 | 0.181226E+11 | 672.00 | 0.657562E+11 | 0.00 | 0.00 | 0.59 | 22-FEB-17:00 | 0.20 | 06-FEB-04:27 | 40717.68 | 22-FEB-17:00 | 40717.68 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 10787.74 | 22-FEB-17:00 | 0.00 |
March | 0.131854E+12 | 0.342247E+11 | 744.00 | 0.131854E+12 | 0.00 | 0.00 | 0.88 | 27-MAR-17:10 | 0.61 | 13-MAR-04:14 | 60215.44 | 29-MAR-17:20 | 60215.44 | 29-MAR-17:20 | 0.00 | 01-MAR-00:10 | 18955.41 | 27-MAR-17:00 | 0.00 |
April | 0.177989E+12 | 0.458220E+11 | 720.00 | 0.177989E+12 | 0.00 | 0.00 | 1.00 | 03-APR-16:50 | 0.85 | 02-APR-06:50 | 74976.13 | 12-APR-18:00 | 74976.13 | 12-APR-18:00 | 0.00 | 01-APR-00:10 | 24987.16 | 07-APR-13:00 | 0.00 |
May | 0.478838E+11 | 0.144490E+11 | 744.00 | 0.478838E+11 | 0.00 | 0.00 | 0.40 | 30-MAY-17:50 | 0.21 | 04-MAY-07:00 | 24341.04 | 30-MAY-18:00 | 24341.04 | 30-MAY-18:00 | 0.00 | 01-MAY-00:01 | 9383.40 | 30-MAY-16:00 | 0.00 |
June | 0.965156E+11 | 0.320903E+11 | 720.00 | 0.965156E+11 | 0.00 | 0.00 | 0.70 | 19-JUN-18:00 | 0.50 | 03-JUN-07:00 | 42935.45 | 18-JUN-17:56 | 42935.45 | 18-JUN-17:56 | 0.00 | 01-JUN-00:10 | 20208.36 | 19-JUN-12:00 | 0.00 |
July | 0.148186E+12 | 0.541841E+11 | 744.00 | 0.148186E+12 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.78 | 15-JUL-07:30 | 61343.79 | 12-JUL-18:20 | 61343.79 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 26831.66 | 07-JUL-12:00 | 0.00 |
August | 0.180772E+12 | 0.644083E+11 | 744.00 | 0.180772E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-00:05 | 0.99 | 08-AUG-05:00 | 72676.71 | 08-AUG-04:22 | 72676.71 | 08-AUG-04:22 | 0.00 | 01-AUG-00:05 | 28714.17 | 24-AUG-16:00 | 0.00 |
September | 0.477526E+11 | 0.156737E+11 | 720.00 | 0.477526E+11 | 0.00 | 0.00 | 0.72 | 01-SEP-00:03 | 0.21 | 23-SEP-17:20 | 47412.40 | 01-SEP-00:03 | 47412.40 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 16533.15 | 01-SEP-00:03 | 0.00 |
October | 0.930548E+11 | 0.262897E+11 | 744.00 | 0.930548E+11 | 0.00 | 0.00 | 0.66 | 04-OCT-16:30 | 0.44 | 08-OCT-07:10 | 42715.00 | 04-OCT-16:30 | 42715.00 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 14337.04 | 02-OCT-16:40 | 0.00 |
November | 0.124754E+12 | 0.325061E+11 | 720.00 | 0.124754E+12 | 0.00 | 0.00 | 0.82 | 03-NOV-16:00 | 0.57 | 24-NOV-05:02 | 57967.49 | 03-NOV-16:00 | 57967.49 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 15693.96 | 03-NOV-14:10 | 0.00 |
December | 0.170928E+12 | 0.428485E+11 | 744.00 | 0.170928E+12 | 0.00 | 0.00 | 1.00 | 08-DEC-16:00 | 0.72 | 31-DEC-24:00 | 73992.88 | 08-DEC-16:25 | 73992.88 | 08-DEC-16:25 | 0.00 | 01-DEC-00:10 | 18133.86 | 08-DEC-16:25 | 0.00 |
Annual Sum or Average | 0.130553E+13 | 0.386665E+12 | 8616.91 | 0.130553E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.200872E+11 | 0.604555E+10 | 600.91 | 0.200872E+11 | 0.00 | 0.00 | 0.33 | 0.00 | 21460.79 | 21460.79 | 0.00 | 6045.24 | 0.00 | ||||||
Maximum of Months | 0.180772E+12 | 0.644083E+11 | 744.00 | 0.180772E+12 | 0.00 | 0.00 | 1.00 | 0.99 | 74976.13 | 74976.13 | 0.00 | 28714.17 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.931420E+09 | 0.286917E+09 | 353.44 | 0.931420E+09 | 0.00 | 0.00 | 0.31 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 2049.88 | 20-JAN-16:40 | 2049.88 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 580.73 | 20-JAN-16:40 | 0.00 |
February | 0.474589E+10 | 0.133822E+10 | 648.31 | 0.474589E+10 | 0.00 | 0.00 | 0.57 | 02-FEB-16:50 | 0.00 | 05-FEB-05:55 | 3973.13 | 02-FEB-16:50 | 3973.13 | 02-FEB-16:50 | 0.00 | 01-FEB-00:10 | 1059.83 | 02-FEB-16:50 | 0.00 |
March | 0.118363E+11 | 0.311643E+10 | 744.00 | 0.118363E+11 | 0.00 | 0.00 | 0.86 | 27-MAR-17:00 | 0.40 | 13-MAR-03:20 | 6022.70 | 29-MAR-17:10 | 6022.70 | 29-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1899.51 | 27-MAR-17:00 | 0.00 |
April | 0.169896E+11 | 0.442404E+10 | 720.00 | 0.169896E+11 | 0.00 | 0.00 | 1.00 | 03-APR-17:20 | 0.69 | 02-APR-07:00 | 7626.32 | 12-APR-17:50 | 7626.32 | 12-APR-17:50 | 0.00 | 01-APR-00:10 | 2552.71 | 07-APR-13:00 | 0.00 |
May | 0.445842E+10 | 0.136137E+10 | 744.00 | 0.445842E+10 | 0.00 | 0.00 | 0.40 | 30-MAY-17:50 | 0.10 | 01-MAY-06:00 | 2533.47 | 30-MAY-18:00 | 2533.47 | 30-MAY-18:00 | 0.00 | 01-MAY-00:01 | 988.89 | 30-MAY-16:00 | 0.00 |
June | 0.964692E+10 | 0.322104E+10 | 720.00 | 0.964692E+10 | 0.00 | 0.00 | 0.70 | 19-JUN-12:00 | 0.45 | 03-JUN-07:00 | 4546.37 | 18-JUN-17:54 | 4546.37 | 18-JUN-17:54 | 0.00 | 01-JUN-00:10 | 2082.86 | 19-JUN-12:00 | 0.00 |
July | 0.149313E+11 | 0.547274E+10 | 744.00 | 0.149313E+11 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.75 | 15-JUL-08:00 | 6237.32 | 12-JUL-18:20 | 6237.32 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 2739.25 | 10-JUL-15:00 | 0.00 |
August | 0.183767E+11 | 0.657309E+10 | 744.00 | 0.183767E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-00:05 | 0.95 | 08-AUG-05:00 | 7296.08 | 20-AUG-01:12 | 7296.08 | 20-AUG-01:12 | 0.00 | 01-AUG-00:05 | 2933.64 | 24-AUG-16:00 | 0.00 |
September | 0.451890E+10 | 0.150122E+10 | 720.00 | 0.451890E+10 | 0.00 | 0.00 | 0.62 | 01-SEP-00:03 | 0.12 | 24-SEP-06:35 | 4017.49 | 01-SEP-00:03 | 4017.49 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 1440.03 | 01-SEP-00:03 | 0.00 |
October | 0.848528E+10 | 0.243040E+10 | 744.00 | 0.848528E+10 | 0.00 | 0.00 | 0.66 | 04-OCT-16:20 | 0.28 | 29-OCT-07:25 | 4343.34 | 04-OCT-16:30 | 4343.34 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 1458.23 | 04-OCT-16:10 | 0.00 |
November | 0.108853E+11 | 0.288468E+10 | 720.00 | 0.108853E+11 | 0.00 | 0.00 | 0.80 | 03-NOV-16:00 | 0.33 | 24-NOV-04:27 | 5786.18 | 03-NOV-16:00 | 5786.18 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 1570.41 | 03-NOV-15:00 | 0.00 |
December | 0.150163E+11 | 0.383733E+10 | 744.00 | 0.150163E+11 | 0.00 | 0.00 | 0.97 | 08-DEC-16:10 | 0.52 | 31-DEC-24:00 | 7284.61 | 08-DEC-16:10 | 7284.61 | 08-DEC-16:10 | 0.00 | 01-DEC-00:10 | 1796.13 | 08-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.120822E+12 | 0.364475E+11 | 8345.75 | 0.120822E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.931420E+09 | 0.286917E+09 | 353.44 | 0.931420E+09 | 0.00 | 0.00 | 0.31 | 0.00 | 2049.88 | 2049.88 | 0.00 | 580.73 | 0.00 | ||||||
Maximum of Months | 0.183767E+11 | 0.657309E+10 | 744.00 | 0.183767E+11 | 0.00 | 0.00 | 1.00 | 0.95 | 7626.32 | 7626.32 | 0.00 | 2933.64 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.48 | 597.34 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.46 | 613.38 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.28 | 419.86 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 97.98 | 296.26 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 212.99 | 168.58 | 0.00 | 0.00 | 744.00 |
June | 321.52 | 17.24 | 304.28 | 309.83 | 87.23 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.52 | 356.72 | 45.01 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.04 | 317.64 | 62.25 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.27 | 137.80 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.31 | 263.69 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.65 | 437.83 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 578.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.42 | 307.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 45.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.52 | 17.24 | 304.28 | 356.72 | 613.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.48 | 597.34 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.46 | 613.38 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.28 | 419.86 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 97.98 | 296.26 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 212.99 | 168.58 | 0.00 | 0.00 | 744.00 |
June | 321.51 | 17.24 | 304.27 | 309.83 | 87.23 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.51 | 356.72 | 45.01 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.03 | 317.64 | 62.25 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.27 | 137.80 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.31 | 263.69 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.65 | 437.83 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 578.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.42 | 307.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 45.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.51 | 17.24 | 304.27 | 356.72 | 613.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.48 | 597.34 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.46 | 613.38 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.28 | 419.86 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 97.98 | 296.26 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 212.99 | 168.58 | 0.00 | 0.00 | 744.00 |
June | 321.51 | 17.24 | 304.28 | 309.83 | 87.23 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.51 | 356.72 | 45.01 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.04 | 317.64 | 62.25 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.27 | 137.80 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.31 | 263.69 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.65 | 437.83 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 578.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.42 | 307.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 45.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.51 | 17.24 | 304.28 | 356.72 | 613.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.48 | 597.34 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.46 | 613.38 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.28 | 419.86 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 97.98 | 296.26 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 212.99 | 168.58 | 0.00 | 0.00 | 744.00 |
June | 321.51 | 17.24 | 304.27 | 309.83 | 87.23 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.51 | 356.72 | 45.01 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.03 | 317.64 | 62.25 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.27 | 137.80 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.31 | 263.69 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.65 | 437.83 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 578.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.42 | 307.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 45.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.51 | 17.24 | 304.27 | 356.72 | 613.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.26 | 0.00 | 100.26 | 0.48 | 597.32 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.46 | 613.35 | 0.00 | 0.00 | 672.00 |
March | 190.27 | 0.00 | 190.27 | 36.28 | 419.84 | 0.00 | 0.00 | 744.00 |
April | 228.53 | 0.64 | 227.89 | 97.98 | 296.25 | 0.00 | 0.00 | 720.00 |
May | 303.17 | 10.07 | 293.10 | 212.98 | 168.58 | 0.00 | 0.00 | 744.00 |
June | 321.50 | 17.24 | 304.26 | 309.82 | 87.23 | 0.00 | 0.00 | 720.00 |
July | 310.71 | 11.20 | 299.50 | 356.71 | 45.01 | 0.00 | 0.00 | 744.00 |
August | 275.28 | 3.25 | 272.02 | 317.62 | 62.24 | 0.00 | 0.00 | 744.00 |
September | 207.53 | 0.04 | 207.49 | 178.26 | 137.80 | 0.00 | 0.00 | 720.00 |
October | 179.60 | 0.00 | 179.60 | 95.31 | 263.68 | 0.00 | 0.00 | 744.00 |
November | 125.97 | 0.00 | 125.97 | 16.64 | 437.81 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 578.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.02 | 3.56 | 202.46 | 136.41 | 307.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 45.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.50 | 17.24 | 304.26 | 356.71 | 613.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.75 | 93.33 | 139.42 | 95.87 | 599.89 | 0.00 | 0.00 | 744.00 |
February | 360.91 | 168.36 | 192.54 | 186.43 | 593.36 | 0.00 | 0.00 | 672.00 |
March | 460.40 | 195.81 | 264.59 | 319.31 | 424.89 | 0.00 | 0.00 | 744.00 |
April | 552.54 | 242.05 | 310.50 | 458.52 | 295.08 | 0.00 | 0.00 | 720.00 |
May | 670.02 | 267.74 | 402.28 | 653.59 | 180.47 | 0.00 | 0.00 | 744.00 |
June | 620.96 | 224.74 | 396.22 | 681.39 | 90.10 | 0.00 | 0.00 | 720.00 |
July | 623.69 | 225.03 | 398.65 | 752.89 | 39.69 | 0.00 | 0.00 | 744.00 |
August | 702.34 | 316.68 | 385.66 | 848.09 | 56.09 | 0.00 | 0.00 | 744.00 |
September | 523.86 | 235.06 | 288.80 | 548.69 | 138.79 | 0.00 | 0.00 | 720.00 |
October | 474.89 | 215.25 | 259.65 | 423.99 | 268.67 | 0.00 | 0.00 | 744.00 |
November | 293.70 | 112.80 | 180.90 | 167.56 | 429.71 | 0.00 | 0.00 | 720.00 |
December | 228.82 | 107.46 | 121.36 | 103.23 | 559.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.50 | 200.59 | 278.91 | 438.39 | 304.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 228.82 | 93.33 | 121.36 | 95.87 | 39.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 702.34 | 316.68 | 402.28 | 848.09 | 599.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.75 | 93.33 | 139.42 | 95.87 | 599.89 | 0.00 | 0.00 | 744.00 |
February | 360.91 | 168.36 | 192.54 | 186.43 | 593.36 | 0.00 | 0.00 | 672.00 |
March | 460.40 | 195.81 | 264.59 | 319.31 | 424.89 | 0.00 | 0.00 | 744.00 |
April | 552.54 | 242.05 | 310.50 | 458.52 | 295.08 | 0.00 | 0.00 | 720.00 |
May | 670.02 | 267.74 | 402.28 | 653.59 | 180.47 | 0.00 | 0.00 | 744.00 |
June | 620.96 | 224.74 | 396.22 | 681.39 | 90.10 | 0.00 | 0.00 | 720.00 |
July | 623.69 | 225.03 | 398.65 | 752.89 | 39.69 | 0.00 | 0.00 | 744.00 |
August | 702.34 | 316.68 | 385.66 | 848.09 | 56.09 | 0.00 | 0.00 | 744.00 |
September | 523.86 | 235.06 | 288.80 | 548.69 | 138.79 | 0.00 | 0.00 | 720.00 |
October | 474.89 | 215.25 | 259.65 | 423.99 | 268.67 | 0.00 | 0.00 | 744.00 |
November | 293.70 | 112.80 | 180.90 | 167.56 | 429.71 | 0.00 | 0.00 | 720.00 |
December | 228.82 | 107.46 | 121.36 | 103.23 | 559.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.50 | 200.59 | 278.91 | 438.39 | 304.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 228.82 | 93.33 | 121.36 | 95.87 | 39.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 702.34 | 316.68 | 402.28 | 848.09 | 599.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.74 | 93.33 | 139.42 | 95.87 | 599.88 | 0.00 | 0.00 | 744.00 |
February | 360.90 | 168.36 | 192.54 | 186.43 | 593.35 | 0.00 | 0.00 | 672.00 |
March | 460.39 | 195.80 | 264.58 | 319.31 | 424.88 | 0.00 | 0.00 | 744.00 |
April | 552.53 | 242.04 | 310.49 | 458.52 | 295.07 | 0.00 | 0.00 | 720.00 |
May | 670.01 | 267.74 | 402.27 | 653.58 | 180.46 | 0.00 | 0.00 | 744.00 |
June | 620.95 | 224.74 | 396.21 | 681.38 | 90.10 | 0.00 | 0.00 | 720.00 |
July | 623.67 | 225.03 | 398.64 | 752.87 | 39.69 | 0.00 | 0.00 | 744.00 |
August | 702.32 | 316.67 | 385.65 | 848.08 | 56.09 | 0.00 | 0.00 | 744.00 |
September | 523.85 | 235.05 | 288.80 | 548.68 | 138.79 | 0.00 | 0.00 | 720.00 |
October | 474.88 | 215.24 | 259.64 | 423.98 | 268.67 | 0.00 | 0.00 | 744.00 |
November | 293.69 | 112.79 | 180.90 | 167.56 | 429.70 | 0.00 | 0.00 | 720.00 |
December | 228.82 | 107.46 | 121.36 | 103.23 | 559.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.49 | 200.58 | 278.91 | 438.38 | 304.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 228.82 | 93.33 | 121.36 | 95.87 | 39.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 702.32 | 316.67 | 402.27 | 848.08 | 599.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.08 | 500.29 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.72 | 508.99 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.47 | 386.26 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.60 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.62 | 174.47 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.13 | 333.69 | 363.97 | 91.56 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.35 | 45.55 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.18 | 64.55 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 613.01 | 137.34 | 0.00 | 0.00 | 720.00 |
October | 819.94 | 514.30 | 305.63 | 856.09 | 253.72 | 0.00 | 0.00 | 744.00 |
November | 568.36 | 341.35 | 227.00 | 529.75 | 378.76 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.05 | 163.07 | 522.02 | 471.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.81 | 273.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.13 | 163.07 | 312.62 | 45.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.94 | 514.30 | 346.86 | 856.09 | 508.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.08 | 500.29 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.72 | 508.99 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.47 | 386.26 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.60 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.62 | 174.47 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.12 | 333.69 | 363.96 | 91.56 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.35 | 45.55 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.17 | 64.55 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 613.01 | 137.34 | 0.00 | 0.00 | 720.00 |
October | 819.93 | 514.30 | 305.63 | 856.08 | 253.72 | 0.00 | 0.00 | 744.00 |
November | 568.35 | 341.35 | 227.00 | 529.74 | 378.76 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.04 | 163.07 | 522.01 | 471.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.81 | 273.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.12 | 163.07 | 312.62 | 45.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.93 | 514.30 | 346.86 | 856.08 | 508.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.08 | 500.29 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.72 | 508.99 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.47 | 386.26 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.60 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.62 | 174.47 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.13 | 333.69 | 363.97 | 91.56 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.35 | 45.55 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.18 | 64.55 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 613.01 | 137.34 | 0.00 | 0.00 | 720.00 |
October | 819.94 | 514.30 | 305.63 | 856.09 | 253.72 | 0.00 | 0.00 | 744.00 |
November | 568.36 | 341.35 | 227.00 | 529.75 | 378.76 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.05 | 163.07 | 522.02 | 471.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.81 | 273.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.13 | 163.07 | 312.62 | 45.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.94 | 514.30 | 346.86 | 856.09 | 508.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.08 | 500.29 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.72 | 508.99 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.47 | 386.26 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.60 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.62 | 174.47 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.12 | 333.69 | 363.96 | 91.56 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.35 | 45.55 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.17 | 64.55 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 613.01 | 137.34 | 0.00 | 0.00 | 720.00 |
October | 819.93 | 514.30 | 305.63 | 856.08 | 253.72 | 0.00 | 0.00 | 744.00 |
November | 568.35 | 341.35 | 227.00 | 529.74 | 378.76 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.04 | 163.07 | 522.01 | 471.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.81 | 273.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.12 | 163.07 | 312.62 | 45.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.93 | 514.30 | 346.86 | 856.08 | 508.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.69 | 339.65 | 179.05 | 454.06 | 500.27 | 0.00 | 0.00 | 744.00 |
February | 684.41 | 453.12 | 231.29 | 590.70 | 508.97 | 0.00 | 0.00 | 672.00 |
March | 617.42 | 342.77 | 274.65 | 510.45 | 386.25 | 0.00 | 0.00 | 744.00 |
April | 478.86 | 189.31 | 289.55 | 340.59 | 286.19 | 0.00 | 0.00 | 720.00 |
May | 419.65 | 87.48 | 332.17 | 312.60 | 174.46 | 0.00 | 0.00 | 744.00 |
June | 393.80 | 60.12 | 333.68 | 363.95 | 91.56 | 0.00 | 0.00 | 720.00 |
July | 412.80 | 71.64 | 341.16 | 435.33 | 45.55 | 0.00 | 0.00 | 744.00 |
August | 551.27 | 204.42 | 346.84 | 567.15 | 64.55 | 0.00 | 0.00 | 744.00 |
September | 598.30 | 309.51 | 288.80 | 612.99 | 137.33 | 0.00 | 0.00 | 720.00 |
October | 819.90 | 514.28 | 305.62 | 856.05 | 253.71 | 0.00 | 0.00 | 744.00 |
November | 568.33 | 341.34 | 226.99 | 529.72 | 378.74 | 0.00 | 0.00 | 720.00 |
December | 562.10 | 399.03 | 163.07 | 521.99 | 471.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.50 | 275.16 | 276.34 | 507.79 | 273.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.80 | 60.12 | 163.07 | 312.60 | 45.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.90 | 514.28 | 346.84 | 856.05 | 508.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 229.77 | 94.13 | 135.64 | 97.93 | 639.41 | 0.00 | 0.00 | 744.00 |
February | 338.80 | 148.80 | 190.00 | 167.64 | 660.71 | 0.00 | 0.00 | 672.00 |
March | 500.31 | 231.00 | 269.31 | 352.92 | 474.74 | 0.00 | 0.00 | 744.00 |
April | 546.80 | 233.97 | 312.83 | 442.58 | 359.16 | 0.00 | 0.00 | 720.00 |
May | 636.88 | 241.82 | 395.06 | 611.93 | 205.05 | 0.00 | 0.00 | 744.00 |
June | 697.04 | 281.09 | 415.95 | 763.00 | 116.96 | 0.00 | 0.00 | 720.00 |
July | 652.83 | 245.80 | 407.03 | 768.22 | 66.54 | 0.00 | 0.00 | 744.00 |
August | 722.26 | 334.35 | 387.91 | 852.85 | 91.73 | 0.00 | 0.00 | 744.00 |
September | 512.79 | 224.11 | 288.68 | 536.95 | 164.03 | 0.00 | 0.00 | 720.00 |
October | 508.36 | 247.20 | 261.16 | 461.19 | 310.04 | 0.00 | 0.00 | 744.00 |
November | 238.73 | 69.00 | 169.73 | 103.02 | 500.66 | 0.00 | 0.00 | 720.00 |
December | 212.37 | 91.91 | 120.46 | 85.59 | 654.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 484.09 | 204.07 | 280.03 | 438.93 | 351.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 212.37 | 69.00 | 120.46 | 85.59 | 66.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 722.26 | 334.35 | 415.95 | 852.85 | 660.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 229.77 | 94.13 | 135.64 | 97.93 | 639.41 | 0.00 | 0.00 | 744.00 |
February | 338.80 | 148.80 | 190.00 | 167.64 | 660.71 | 0.00 | 0.00 | 672.00 |
March | 500.31 | 231.00 | 269.31 | 352.92 | 474.74 | 0.00 | 0.00 | 744.00 |
April | 546.80 | 233.97 | 312.83 | 442.58 | 359.16 | 0.00 | 0.00 | 720.00 |
May | 636.88 | 241.82 | 395.06 | 611.93 | 205.05 | 0.00 | 0.00 | 744.00 |
June | 697.04 | 281.09 | 415.95 | 763.00 | 116.96 | 0.00 | 0.00 | 720.00 |
July | 652.83 | 245.80 | 407.03 | 768.22 | 66.54 | 0.00 | 0.00 | 744.00 |
August | 722.26 | 334.35 | 387.91 | 852.85 | 91.73 | 0.00 | 0.00 | 744.00 |
September | 512.79 | 224.11 | 288.68 | 536.95 | 164.03 | 0.00 | 0.00 | 720.00 |
October | 508.36 | 247.20 | 261.16 | 461.19 | 310.04 | 0.00 | 0.00 | 744.00 |
November | 238.73 | 69.00 | 169.73 | 103.02 | 500.66 | 0.00 | 0.00 | 720.00 |
December | 212.37 | 91.91 | 120.46 | 85.59 | 654.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 484.09 | 204.07 | 280.03 | 438.93 | 351.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 212.37 | 69.00 | 120.46 | 85.59 | 66.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 722.26 | 334.35 | 415.95 | 852.85 | 660.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 229.77 | 94.13 | 135.64 | 97.93 | 639.40 | 0.00 | 0.00 | 744.00 |
February | 338.79 | 148.80 | 189.99 | 167.64 | 660.70 | 0.00 | 0.00 | 672.00 |
March | 500.31 | 231.00 | 269.31 | 352.91 | 474.73 | 0.00 | 0.00 | 744.00 |
April | 546.79 | 233.97 | 312.82 | 442.57 | 359.16 | 0.00 | 0.00 | 720.00 |
May | 636.87 | 241.82 | 395.05 | 611.92 | 205.04 | 0.00 | 0.00 | 744.00 |
June | 697.03 | 281.08 | 415.94 | 762.98 | 116.96 | 0.00 | 0.00 | 720.00 |
July | 652.82 | 245.80 | 407.02 | 768.20 | 66.54 | 0.00 | 0.00 | 744.00 |
August | 722.25 | 334.35 | 387.90 | 852.83 | 91.73 | 0.00 | 0.00 | 744.00 |
September | 512.78 | 224.10 | 288.68 | 536.94 | 164.03 | 0.00 | 0.00 | 720.00 |
October | 508.35 | 247.20 | 261.15 | 461.18 | 310.03 | 0.00 | 0.00 | 744.00 |
November | 238.72 | 69.00 | 169.73 | 103.02 | 500.65 | 0.00 | 0.00 | 720.00 |
December | 212.36 | 91.91 | 120.46 | 85.59 | 654.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 484.08 | 204.06 | 280.02 | 438.92 | 351.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 212.36 | 69.00 | 120.46 | 85.59 | 66.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 722.25 | 334.35 | 415.94 | 852.83 | 660.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.34 | 0.00 | 501.34 | 10.48 | 2643.37 | 0.00 | 0.00 | 744.00 |
February | 686.07 | 0.00 | 686.07 | 31.48 | 2764.00 | 0.00 | 0.00 | 672.00 |
March | 951.40 | 0.00 | 951.40 | 219.67 | 1870.98 | 0.00 | 0.00 | 744.00 |
April | 1142.71 | 3.20 | 1139.51 | 534.39 | 1325.08 | 0.00 | 0.00 | 720.00 |
May | 1515.92 | 50.36 | 1465.57 | 1089.14 | 791.61 | 0.00 | 0.00 | 744.00 |
June | 1607.59 | 86.19 | 1521.40 | 1565.77 | 414.74 | 0.00 | 0.00 | 720.00 |
July | 1553.61 | 56.03 | 1497.58 | 1795.97 | 225.91 | 0.00 | 0.00 | 744.00 |
August | 1376.45 | 16.27 | 1360.19 | 1605.89 | 311.67 | 0.00 | 0.00 | 744.00 |
September | 1037.70 | 0.19 | 1037.51 | 912.72 | 636.69 | 0.00 | 0.00 | 720.00 |
October | 898.06 | 0.00 | 898.06 | 511.46 | 1195.54 | 0.00 | 0.00 | 744.00 |
November | 629.90 | 0.00 | 629.90 | 107.34 | 1906.01 | 0.00 | 0.00 | 720.00 |
December | 437.30 | 0.00 | 437.30 | 6.45 | 2512.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1030.15 | 17.78 | 1012.37 | 703.83 | 1375.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 437.30 | 0.00 | 437.30 | 6.45 | 225.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1607.59 | 86.19 | 1521.40 | 1795.97 | 2764.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.24 | 279.98 | 418.26 | 307.21 | 1622.83 | 0.00 | 0.00 | 744.00 |
February | 1082.71 | 505.09 | 577.62 | 581.87 | 1642.44 | 0.00 | 0.00 | 672.00 |
March | 1381.18 | 587.42 | 793.76 | 974.92 | 1178.89 | 0.00 | 0.00 | 744.00 |
April | 1657.61 | 726.13 | 931.48 | 1386.14 | 830.35 | 0.00 | 0.00 | 720.00 |
May | 2010.04 | 803.22 | 1206.82 | 1963.36 | 514.22 | 0.00 | 0.00 | 744.00 |
June | 1862.87 | 674.23 | 1188.64 | 2040.30 | 266.99 | 0.00 | 0.00 | 720.00 |
July | 1871.04 | 675.10 | 1195.94 | 2244.81 | 139.56 | 0.00 | 0.00 | 744.00 |
August | 2106.99 | 950.02 | 1156.97 | 2526.78 | 194.76 | 0.00 | 0.00 | 744.00 |
September | 1571.56 | 705.17 | 866.39 | 1651.65 | 390.92 | 0.00 | 0.00 | 720.00 |
October | 1424.67 | 645.73 | 778.94 | 1286.50 | 749.79 | 0.00 | 0.00 | 744.00 |
November | 881.08 | 338.38 | 542.70 | 528.21 | 1161.73 | 0.00 | 0.00 | 720.00 |
December | 686.47 | 322.38 | 364.09 | 326.75 | 1520.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1438.48 | 601.75 | 836.73 | 1323.35 | 846.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 686.47 | 279.98 | 364.09 | 307.21 | 139.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2106.99 | 950.02 | 1206.82 | 2526.78 | 1642.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2593.62 | 1698.34 | 895.28 | 2277.87 | 2376.03 | 0.00 | 0.00 | 744.00 |
February | 3422.28 | 2265.77 | 1156.51 | 2946.38 | 2463.25 | 0.00 | 0.00 | 672.00 |
March | 3087.27 | 1713.95 | 1373.31 | 2549.54 | 1848.50 | 0.00 | 0.00 | 744.00 |
April | 2394.45 | 946.63 | 1447.82 | 1718.62 | 1358.08 | 0.00 | 0.00 | 720.00 |
May | 2098.37 | 437.43 | 1660.93 | 1571.84 | 844.80 | 0.00 | 0.00 | 744.00 |
June | 1969.12 | 300.63 | 1668.49 | 1829.80 | 444.52 | 0.00 | 0.00 | 720.00 |
July | 2064.13 | 358.24 | 1705.89 | 2187.32 | 234.39 | 0.00 | 0.00 | 744.00 |
August | 2756.49 | 1022.17 | 1734.32 | 2844.08 | 335.55 | 0.00 | 0.00 | 744.00 |
September | 2991.70 | 1547.63 | 1444.07 | 3056.60 | 671.18 | 0.00 | 0.00 | 720.00 |
October | 4099.76 | 2571.57 | 1528.19 | 4256.93 | 1242.88 | 0.00 | 0.00 | 744.00 |
November | 2841.85 | 1706.81 | 1135.04 | 2650.55 | 1800.98 | 0.00 | 0.00 | 720.00 |
December | 2810.67 | 1995.28 | 815.39 | 2612.83 | 2237.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2757.69 | 1375.89 | 1381.80 | 2541.04 | 1314.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1969.12 | 300.63 | 815.39 | 1571.84 | 234.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4099.76 | 2571.57 | 1734.32 | 4256.93 | 2463.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 689.32 | 282.39 | 406.93 | 312.56 | 1690.70 | 0.00 | 0.00 | 744.00 |
February | 1016.39 | 446.40 | 569.99 | 533.22 | 1745.69 | 0.00 | 0.00 | 672.00 |
March | 1500.93 | 692.99 | 807.93 | 1107.89 | 1207.48 | 0.00 | 0.00 | 744.00 |
April | 1640.38 | 701.91 | 938.47 | 1390.96 | 891.19 | 0.00 | 0.00 | 720.00 |
May | 1910.62 | 725.46 | 1185.16 | 1867.48 | 558.07 | 0.00 | 0.00 | 744.00 |
June | 2091.09 | 843.26 | 1247.84 | 2320.24 | 309.29 | 0.00 | 0.00 | 720.00 |
July | 1958.47 | 737.40 | 1221.08 | 2344.46 | 173.11 | 0.00 | 0.00 | 744.00 |
August | 2166.76 | 1003.05 | 1163.71 | 2600.26 | 244.42 | 0.00 | 0.00 | 744.00 |
September | 1538.35 | 672.31 | 866.04 | 1641.40 | 432.73 | 0.00 | 0.00 | 720.00 |
October | 1525.07 | 741.61 | 783.46 | 1428.95 | 805.67 | 0.00 | 0.00 | 744.00 |
November | 716.17 | 206.99 | 509.19 | 354.62 | 1226.43 | 0.00 | 0.00 | 720.00 |
December | 637.09 | 275.72 | 361.38 | 289.61 | 1602.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1452.26 | 612.19 | 840.07 | 1355.16 | 902.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 637.09 | 206.99 | 361.38 | 289.61 | 173.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2166.76 | 1003.05 | 1247.84 | 2600.26 | 1745.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.34 | 0.00 | 501.34 | 17.10 | 2474.53 | 0.00 | 0.00 | 744.00 |
February | 686.07 | 0.00 | 686.07 | 43.94 | 2573.58 | 0.00 | 0.00 | 672.00 |
March | 951.40 | 0.00 | 951.40 | 248.01 | 1712.76 | 0.00 | 0.00 | 744.00 |
April | 1142.71 | 3.20 | 1139.51 | 565.28 | 1217.14 | 0.00 | 0.00 | 720.00 |
May | 1515.92 | 50.36 | 1465.57 | 1102.02 | 751.50 | 0.00 | 0.00 | 744.00 |
June | 1607.59 | 86.19 | 1521.40 | 1555.38 | 407.96 | 0.00 | 0.00 | 720.00 |
July | 1553.61 | 56.03 | 1497.58 | 1776.03 | 229.65 | 0.00 | 0.00 | 744.00 |
August | 1376.45 | 16.27 | 1360.19 | 1592.67 | 308.21 | 0.00 | 0.00 | 744.00 |
September | 1037.70 | 0.19 | 1037.51 | 920.54 | 599.64 | 0.00 | 0.00 | 720.00 |
October | 898.06 | 0.00 | 898.06 | 545.11 | 1090.52 | 0.00 | 0.00 | 744.00 |
November | 629.90 | 0.00 | 629.90 | 136.50 | 1704.78 | 0.00 | 0.00 | 720.00 |
December | 437.30 | 0.00 | 437.30 | 15.01 | 2273.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1030.15 | 17.78 | 1012.37 | 714.34 | 1271.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 437.30 | 0.00 | 437.30 | 15.01 | 229.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1607.59 | 86.19 | 1521.40 | 1776.03 | 2573.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.24 | 279.98 | 418.26 | 318.54 | 1526.02 | 0.00 | 0.00 | 744.00 |
February | 1082.71 | 505.09 | 577.62 | 603.81 | 1535.63 | 0.00 | 0.00 | 672.00 |
March | 1381.18 | 587.42 | 793.76 | 996.68 | 1094.09 | 0.00 | 0.00 | 744.00 |
April | 1657.61 | 726.13 | 931.48 | 1403.67 | 778.56 | 0.00 | 0.00 | 720.00 |
May | 2010.04 | 803.22 | 1206.82 | 1965.06 | 496.13 | 0.00 | 0.00 | 744.00 |
June | 1862.87 | 674.23 | 1188.64 | 2029.03 | 266.91 | 0.00 | 0.00 | 720.00 |
July | 1871.04 | 675.10 | 1195.94 | 2228.31 | 144.46 | 0.00 | 0.00 | 744.00 |
August | 2106.99 | 950.02 | 1156.97 | 2514.03 | 196.00 | 0.00 | 0.00 | 744.00 |
September | 1571.56 | 705.17 | 866.39 | 1652.45 | 375.49 | 0.00 | 0.00 | 720.00 |
October | 1424.67 | 645.73 | 778.94 | 1305.56 | 697.84 | 0.00 | 0.00 | 744.00 |
November | 881.08 | 338.38 | 542.70 | 556.29 | 1057.05 | 0.00 | 0.00 | 720.00 |
December | 686.47 | 322.38 | 364.09 | 345.39 | 1388.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1438.48 | 601.75 | 836.73 | 1331.59 | 792.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 686.47 | 279.98 | 364.09 | 318.54 | 144.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2106.99 | 950.02 | 1206.82 | 2514.03 | 1535.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2593.62 | 1698.34 | 895.28 | 2307.35 | 2213.66 | 0.00 | 0.00 | 744.00 |
February | 3422.28 | 2265.77 | 1156.51 | 2993.45 | 2277.56 | 0.00 | 0.00 | 672.00 |
March | 3087.27 | 1713.95 | 1373.31 | 2581.47 | 1698.49 | 0.00 | 0.00 | 744.00 |
April | 2394.45 | 946.63 | 1447.82 | 1749.95 | 1257.91 | 0.00 | 0.00 | 720.00 |
May | 2098.37 | 437.43 | 1660.93 | 1585.33 | 803.85 | 0.00 | 0.00 | 744.00 |
June | 1969.12 | 300.63 | 1668.49 | 1822.03 | 437.44 | 0.00 | 0.00 | 720.00 |
July | 2064.13 | 358.24 | 1705.89 | 2171.28 | 237.66 | 0.00 | 0.00 | 744.00 |
August | 2756.49 | 1022.17 | 1734.32 | 2835.04 | 331.64 | 0.00 | 0.00 | 744.00 |
September | 2991.70 | 1547.63 | 1444.07 | 3064.58 | 637.20 | 0.00 | 0.00 | 720.00 |
October | 4099.76 | 2571.57 | 1528.19 | 4285.40 | 1152.92 | 0.00 | 0.00 | 744.00 |
November | 2841.85 | 1706.81 | 1135.04 | 2699.78 | 1628.69 | 0.00 | 0.00 | 720.00 |
December | 2810.67 | 1995.28 | 815.39 | 2661.67 | 2027.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2757.69 | 1375.89 | 1381.80 | 2562.08 | 1219.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1969.12 | 300.63 | 815.39 | 1585.33 | 237.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4099.76 | 2571.57 | 1734.32 | 4285.40 | 2277.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 689.32 | 282.39 | 406.93 | 320.17 | 1596.42 | 0.00 | 0.00 | 744.00 |
February | 1016.39 | 446.40 | 569.99 | 543.08 | 1647.40 | 0.00 | 0.00 | 672.00 |
March | 1500.93 | 692.99 | 807.93 | 1122.12 | 1128.14 | 0.00 | 0.00 | 744.00 |
April | 1640.38 | 701.91 | 938.47 | 1404.60 | 835.59 | 0.00 | 0.00 | 720.00 |
May | 1910.62 | 725.46 | 1185.16 | 1872.39 | 534.52 | 0.00 | 0.00 | 744.00 |
June | 2091.09 | 843.26 | 1247.84 | 2314.74 | 303.62 | 0.00 | 0.00 | 720.00 |
July | 1958.47 | 737.40 | 1221.08 | 2334.12 | 172.95 | 0.00 | 0.00 | 744.00 |
August | 2166.76 | 1003.05 | 1163.71 | 2594.35 | 239.58 | 0.00 | 0.00 | 744.00 |
September | 1538.35 | 672.31 | 866.04 | 1645.70 | 412.47 | 0.00 | 0.00 | 720.00 |
October | 1525.07 | 741.61 | 783.46 | 1443.73 | 752.63 | 0.00 | 0.00 | 744.00 |
November | 716.17 | 206.99 | 509.19 | 372.66 | 1127.77 | 0.00 | 0.00 | 720.00 |
December | 637.09 | 275.72 | 361.38 | 300.70 | 1484.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1452.26 | 612.19 | 840.07 | 1361.51 | 848.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 637.09 | 206.99 | 361.38 | 300.70 | 172.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2166.76 | 1003.05 | 1247.84 | 2594.35 | 1647.40 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268559E+09 | 0.00 | 0.268559E+09 | 1289779.39 | 0.159992E+10 |
February | 0.331947E+09 | 0.00 | 0.331947E+09 | 8371807.27 | 0.148388E+10 |
March | 0.509647E+09 | 0.00 | 0.509647E+09 | 97166237.42 | 0.112454E+10 |
April | 0.592383E+09 | 1658662.77 | 0.590724E+09 | 0.253970E+09 | 0.767912E+09 |
May | 0.812050E+09 | 26974361.52 | 0.785076E+09 | 0.570481E+09 | 0.451535E+09 |
June | 0.833375E+09 | 44682914.63 | 0.788692E+09 | 0.803084E+09 | 0.226104E+09 |
July | 0.832237E+09 | 30011298.19 | 0.802225E+09 | 0.955452E+09 | 0.120562E+09 |
August | 0.737338E+09 | 8712936.52 | 0.728625E+09 | 0.850767E+09 | 0.166724E+09 |
September | 0.537942E+09 | 96941.75 | 0.537845E+09 | 0.462080E+09 | 0.357186E+09 |
October | 0.481072E+09 | 0.00 | 0.481072E+09 | 0.255284E+09 | 0.706264E+09 |
November | 0.326541E+09 | 0.00 | 0.326541E+09 | 43147216.25 | 0.113485E+10 |
December | 0.234255E+09 | 0.00 | 0.234255E+09 | 1064124.51 | 0.155001E+10 |
Annual Sum or Average | 0.649735E+10 | 0.112137E+09 | 0.638521E+10 | 0.430216E+10 | 0.968948E+10 |
Minimum of Months | 0.234255E+09 | 0.00 | 0.234255E+09 | 1064124.51 | 0.120562E+09 |
Maximum of Months | 0.833375E+09 | 44682914.63 | 0.802225E+09 | 0.955452E+09 | 0.159992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268555E+09 | 0.00 | 0.268555E+09 | 1289549.46 | 0.159992E+10 |
February | 0.331942E+09 | 0.00 | 0.331942E+09 | 8371037.75 | 0.148388E+10 |
March | 0.509640E+09 | 0.00 | 0.509640E+09 | 97162271.99 | 0.112455E+10 |
April | 0.592375E+09 | 1658626.30 | 0.590716E+09 | 0.253964E+09 | 0.767912E+09 |
May | 0.812038E+09 | 26973768.52 | 0.785064E+09 | 0.570470E+09 | 0.451535E+09 |
June | 0.833363E+09 | 44681932.32 | 0.788681E+09 | 0.803072E+09 | 0.226103E+09 |
July | 0.832225E+09 | 30010638.43 | 0.802214E+09 | 0.955439E+09 | 0.120561E+09 |
August | 0.737328E+09 | 8712744.97 | 0.728615E+09 | 0.850758E+09 | 0.166723E+09 |
September | 0.537935E+09 | 96939.62 | 0.537838E+09 | 0.462073E+09 | 0.357185E+09 |
October | 0.481065E+09 | 0.00 | 0.481065E+09 | 0.255278E+09 | 0.706262E+09 |
November | 0.326536E+09 | 0.00 | 0.326536E+09 | 43145224.64 | 0.113485E+10 |
December | 0.234252E+09 | 0.00 | 0.234252E+09 | 1063975.54 | 0.155001E+10 |
Annual Sum or Average | 0.649725E+10 | 0.112135E+09 | 0.638512E+10 | 0.430209E+10 | 0.968948E+10 |
Minimum of Months | 0.234252E+09 | 0.00 | 0.234252E+09 | 1063975.54 | 0.120561E+09 |
Maximum of Months | 0.833363E+09 | 44681932.32 | 0.802214E+09 | 0.955439E+09 | 0.159992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268557E+09 | 0.00 | 0.268557E+09 | 1289626.10 | 0.159992E+10 |
February | 0.331944E+09 | 0.00 | 0.331944E+09 | 8371294.25 | 0.148388E+10 |
March | 0.509643E+09 | 0.00 | 0.509643E+09 | 97163593.80 | 0.112455E+10 |
April | 0.592377E+09 | 1658638.46 | 0.590719E+09 | 0.253966E+09 | 0.767912E+09 |
May | 0.812042E+09 | 26973966.19 | 0.785068E+09 | 0.570474E+09 | 0.451535E+09 |
June | 0.833367E+09 | 44682259.76 | 0.788684E+09 | 0.803076E+09 | 0.226103E+09 |
July | 0.832229E+09 | 30010858.35 | 0.802218E+09 | 0.955444E+09 | 0.120561E+09 |
August | 0.737331E+09 | 8712808.82 | 0.728619E+09 | 0.850761E+09 | 0.166723E+09 |
September | 0.537937E+09 | 96940.33 | 0.537840E+09 | 0.462075E+09 | 0.357186E+09 |
October | 0.481068E+09 | 0.00 | 0.481068E+09 | 0.255280E+09 | 0.706263E+09 |
November | 0.326537E+09 | 0.00 | 0.326537E+09 | 43145888.51 | 0.113485E+10 |
December | 0.234253E+09 | 0.00 | 0.234253E+09 | 1064025.19 | 0.155001E+10 |
Annual Sum or Average | 0.649728E+10 | 0.112135E+09 | 0.638515E+10 | 0.430211E+10 | 0.968948E+10 |
Minimum of Months | 0.234253E+09 | 0.00 | 0.234253E+09 | 1064025.19 | 0.120561E+09 |
Maximum of Months | 0.833367E+09 | 44682259.76 | 0.802218E+09 | 0.955444E+09 | 0.159992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268555E+09 | 0.00 | 0.268555E+09 | 1289549.46 | 0.159992E+10 |
February | 0.331942E+09 | 0.00 | 0.331942E+09 | 8371037.75 | 0.148388E+10 |
March | 0.509640E+09 | 0.00 | 0.509640E+09 | 97162271.99 | 0.112455E+10 |
April | 0.592375E+09 | 1658626.30 | 0.590716E+09 | 0.253964E+09 | 0.767912E+09 |
May | 0.812038E+09 | 26973768.52 | 0.785064E+09 | 0.570470E+09 | 0.451535E+09 |
June | 0.833363E+09 | 44681932.32 | 0.788681E+09 | 0.803072E+09 | 0.226103E+09 |
July | 0.832225E+09 | 30010638.43 | 0.802214E+09 | 0.955439E+09 | 0.120561E+09 |
August | 0.737328E+09 | 8712744.97 | 0.728615E+09 | 0.850758E+09 | 0.166723E+09 |
September | 0.537935E+09 | 96939.62 | 0.537838E+09 | 0.462073E+09 | 0.357185E+09 |
October | 0.481065E+09 | 0.00 | 0.481065E+09 | 0.255278E+09 | 0.706262E+09 |
November | 0.326536E+09 | 0.00 | 0.326536E+09 | 43145224.64 | 0.113485E+10 |
December | 0.234252E+09 | 0.00 | 0.234252E+09 | 1063975.54 | 0.155001E+10 |
Annual Sum or Average | 0.649725E+10 | 0.112135E+09 | 0.638512E+10 | 0.430209E+10 | 0.968948E+10 |
Minimum of Months | 0.234252E+09 | 0.00 | 0.234252E+09 | 1063975.54 | 0.120561E+09 |
Maximum of Months | 0.833363E+09 | 44681932.32 | 0.802214E+09 | 0.955439E+09 | 0.159992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268545E+09 | 0.00 | 0.268545E+09 | 1289535.81 | 0.159985E+10 |
February | 0.331929E+09 | 0.00 | 0.331929E+09 | 8370828.60 | 0.148382E+10 |
March | 0.509621E+09 | 0.00 | 0.509621E+09 | 97159016.80 | 0.112450E+10 |
April | 0.592352E+09 | 1658565.53 | 0.590694E+09 | 0.253955E+09 | 0.767881E+09 |
May | 0.812007E+09 | 26972780.19 | 0.785035E+09 | 0.570449E+09 | 0.451517E+09 |
June | 0.833331E+09 | 44680295.16 | 0.788651E+09 | 0.803042E+09 | 0.226094E+09 |
July | 0.832193E+09 | 30009538.83 | 0.802184E+09 | 0.955403E+09 | 0.120556E+09 |
August | 0.737300E+09 | 8712425.73 | 0.728588E+09 | 0.850725E+09 | 0.166716E+09 |
September | 0.537914E+09 | 96936.07 | 0.537817E+09 | 0.462056E+09 | 0.357171E+09 |
October | 0.481047E+09 | 0.00 | 0.481047E+09 | 0.255269E+09 | 0.706234E+09 |
November | 0.326523E+09 | 0.00 | 0.326523E+09 | 43143817.61 | 0.113480E+10 |
December | 0.234243E+09 | 0.00 | 0.234243E+09 | 1063957.48 | 0.154994E+10 |
Annual Sum or Average | 0.649701E+10 | 0.112131E+09 | 0.638488E+10 | 0.430193E+10 | 0.968909E+10 |
Minimum of Months | 0.234243E+09 | 0.00 | 0.234243E+09 | 1063957.48 | 0.120556E+09 |
Maximum of Months | 0.833331E+09 | 44680295.16 | 0.802184E+09 | 0.955403E+09 | 0.159985E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623391E+09 | 0.249968E+09 | 0.373423E+09 | 0.256775E+09 | 0.160675E+10 |
February | 0.873106E+09 | 0.407308E+09 | 0.465798E+09 | 0.451016E+09 | 0.143545E+10 |
March | 0.123313E+10 | 0.524454E+09 | 0.708677E+09 | 0.855252E+09 | 0.113801E+10 |
April | 0.143219E+10 | 0.627383E+09 | 0.804805E+09 | 0.118850E+10 | 0.764846E+09 |
May | 0.179458E+10 | 0.717120E+09 | 0.107746E+10 | 0.175058E+10 | 0.483362E+09 |
June | 0.160954E+10 | 0.582537E+09 | 0.102700E+10 | 0.176616E+10 | 0.233544E+09 |
July | 0.167048E+10 | 0.602734E+09 | 0.106774E+10 | 0.201654E+10 | 0.106302E+09 |
August | 0.188114E+10 | 0.848184E+09 | 0.103295E+10 | 0.227153E+10 | 0.150229E+09 |
September | 0.135784E+10 | 0.609273E+09 | 0.748572E+09 | 0.142220E+10 | 0.359750E+09 |
October | 0.127195E+10 | 0.576514E+09 | 0.695440E+09 | 0.113561E+10 | 0.719609E+09 |
November | 0.761261E+09 | 0.292365E+09 | 0.468896E+09 | 0.434321E+09 | 0.111382E+10 |
December | 0.612885E+09 | 0.287822E+09 | 0.325062E+09 | 0.276490E+09 | 0.149896E+10 |
Annual Sum or Average | 0.151215E+11 | 0.632566E+10 | 0.879583E+10 | 0.138250E+11 | 0.961063E+10 |
Minimum of Months | 0.612885E+09 | 0.249968E+09 | 0.325062E+09 | 0.256775E+09 | 0.106302E+09 |
Maximum of Months | 0.188114E+10 | 0.848184E+09 | 0.107746E+10 | 0.227153E+10 | 0.160675E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623391E+09 | 0.249968E+09 | 0.373423E+09 | 0.256775E+09 | 0.160675E+10 |
February | 0.873106E+09 | 0.407308E+09 | 0.465798E+09 | 0.451016E+09 | 0.143545E+10 |
March | 0.123313E+10 | 0.524454E+09 | 0.708677E+09 | 0.855252E+09 | 0.113801E+10 |
April | 0.143219E+10 | 0.627383E+09 | 0.804805E+09 | 0.118850E+10 | 0.764846E+09 |
May | 0.179458E+10 | 0.717120E+09 | 0.107746E+10 | 0.175058E+10 | 0.483362E+09 |
June | 0.160954E+10 | 0.582537E+09 | 0.102700E+10 | 0.176616E+10 | 0.233544E+09 |
July | 0.167048E+10 | 0.602734E+09 | 0.106774E+10 | 0.201654E+10 | 0.106302E+09 |
August | 0.188114E+10 | 0.848184E+09 | 0.103295E+10 | 0.227153E+10 | 0.150229E+09 |
September | 0.135784E+10 | 0.609273E+09 | 0.748572E+09 | 0.142220E+10 | 0.359750E+09 |
October | 0.127195E+10 | 0.576514E+09 | 0.695440E+09 | 0.113561E+10 | 0.719609E+09 |
November | 0.761261E+09 | 0.292365E+09 | 0.468896E+09 | 0.434321E+09 | 0.111382E+10 |
December | 0.612885E+09 | 0.287822E+09 | 0.325062E+09 | 0.276490E+09 | 0.149896E+10 |
Annual Sum or Average | 0.151215E+11 | 0.632566E+10 | 0.879583E+10 | 0.138250E+11 | 0.961063E+10 |
Minimum of Months | 0.612885E+09 | 0.249968E+09 | 0.325062E+09 | 0.256775E+09 | 0.106302E+09 |
Maximum of Months | 0.188114E+10 | 0.848184E+09 | 0.107746E+10 | 0.227153E+10 | 0.160675E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623380E+09 | 0.249964E+09 | 0.373416E+09 | 0.256770E+09 | 0.160672E+10 |
February | 0.873090E+09 | 0.407301E+09 | 0.465790E+09 | 0.451008E+09 | 0.143543E+10 |
March | 0.123311E+10 | 0.524444E+09 | 0.708664E+09 | 0.855236E+09 | 0.113799E+10 |
April | 0.143216E+10 | 0.627372E+09 | 0.804790E+09 | 0.118847E+10 | 0.764832E+09 |
May | 0.179455E+10 | 0.717107E+09 | 0.107744E+10 | 0.175055E+10 | 0.483353E+09 |
June | 0.160951E+10 | 0.582527E+09 | 0.102698E+10 | 0.176613E+10 | 0.233540E+09 |
July | 0.167045E+10 | 0.602723E+09 | 0.106773E+10 | 0.201650E+10 | 0.106300E+09 |
August | 0.188110E+10 | 0.848168E+09 | 0.103294E+10 | 0.227149E+10 | 0.150226E+09 |
September | 0.135782E+10 | 0.609261E+09 | 0.748558E+09 | 0.142217E+10 | 0.359744E+09 |
October | 0.127193E+10 | 0.576504E+09 | 0.695428E+09 | 0.113559E+10 | 0.719596E+09 |
November | 0.761247E+09 | 0.292359E+09 | 0.468888E+09 | 0.434313E+09 | 0.111379E+10 |
December | 0.612873E+09 | 0.287817E+09 | 0.325056E+09 | 0.276485E+09 | 0.149893E+10 |
Annual Sum or Average | 0.151212E+11 | 0.632555E+10 | 0.879567E+10 | 0.138247E+11 | 0.961045E+10 |
Minimum of Months | 0.612873E+09 | 0.249964E+09 | 0.325056E+09 | 0.256770E+09 | 0.106300E+09 |
Maximum of Months | 0.188110E+10 | 0.848168E+09 | 0.107744E+10 | 0.227149E+10 | 0.160672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138933E+10 | 0.909750E+09 | 0.479576E+09 | 0.121621E+10 | 0.133998E+10 |
February | 0.165580E+10 | 0.109624E+10 | 0.559559E+09 | 0.142908E+10 | 0.123136E+10 |
March | 0.165376E+10 | 0.918111E+09 | 0.735648E+09 | 0.136725E+10 | 0.103457E+10 |
April | 0.124127E+10 | 0.490723E+09 | 0.750543E+09 | 0.882840E+09 | 0.741824E+09 |
May | 0.112404E+10 | 0.234319E+09 | 0.889719E+09 | 0.837315E+09 | 0.467305E+09 |
June | 0.102078E+10 | 0.155844E+09 | 0.864935E+09 | 0.943399E+09 | 0.237332E+09 |
July | 0.110570E+10 | 0.191900E+09 | 0.913799E+09 | 0.116604E+10 | 0.122005E+09 |
August | 0.147657E+10 | 0.547544E+09 | 0.929029E+09 | 0.151912E+10 | 0.172888E+09 |
September | 0.155087E+10 | 0.802273E+09 | 0.748597E+09 | 0.158893E+10 | 0.355983E+09 |
October | 0.219612E+10 | 0.137751E+10 | 0.818608E+09 | 0.229295E+10 | 0.679563E+09 |
November | 0.147318E+10 | 0.884792E+09 | 0.588393E+09 | 0.137311E+10 | 0.981743E+09 |
December | 0.150559E+10 | 0.106881E+10 | 0.436779E+09 | 0.139817E+10 | 0.126295E+10 |
Annual Sum or Average | 0.173930E+11 | 0.867782E+10 | 0.871518E+10 | 0.160144E+11 | 0.862750E+10 |
Minimum of Months | 0.102078E+10 | 0.155844E+09 | 0.436779E+09 | 0.837315E+09 | 0.122005E+09 |
Maximum of Months | 0.219612E+10 | 0.137751E+10 | 0.929029E+09 | 0.229295E+10 | 0.133998E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138932E+10 | 0.909744E+09 | 0.479573E+09 | 0.121620E+10 | 0.133998E+10 |
February | 0.165579E+10 | 0.109624E+10 | 0.559556E+09 | 0.142906E+10 | 0.123136E+10 |
March | 0.165375E+10 | 0.918104E+09 | 0.735644E+09 | 0.136724E+10 | 0.103457E+10 |
April | 0.124126E+10 | 0.490719E+09 | 0.750539E+09 | 0.882833E+09 | 0.741824E+09 |
May | 0.112403E+10 | 0.234318E+09 | 0.889714E+09 | 0.837310E+09 | 0.467305E+09 |
June | 0.102077E+10 | 0.155843E+09 | 0.864931E+09 | 0.943394E+09 | 0.237332E+09 |
July | 0.110569E+10 | 0.191899E+09 | 0.913795E+09 | 0.116604E+10 | 0.122004E+09 |
August | 0.147656E+10 | 0.547540E+09 | 0.929024E+09 | 0.151912E+10 | 0.172887E+09 |
September | 0.155086E+10 | 0.802267E+09 | 0.748593E+09 | 0.158892E+10 | 0.355982E+09 |
October | 0.219611E+10 | 0.137750E+10 | 0.818604E+09 | 0.229293E+10 | 0.679563E+09 |
November | 0.147317E+10 | 0.884785E+09 | 0.588389E+09 | 0.137310E+10 | 0.981743E+09 |
December | 0.150558E+10 | 0.106880E+10 | 0.436777E+09 | 0.139816E+10 | 0.126295E+10 |
Annual Sum or Average | 0.173929E+11 | 0.867776E+10 | 0.871514E+10 | 0.160143E+11 | 0.862749E+10 |
Minimum of Months | 0.102077E+10 | 0.155843E+09 | 0.436777E+09 | 0.837310E+09 | 0.122004E+09 |
Maximum of Months | 0.219611E+10 | 0.137750E+10 | 0.929024E+09 | 0.229293E+10 | 0.133998E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138933E+10 | 0.909750E+09 | 0.479576E+09 | 0.121621E+10 | 0.133998E+10 |
February | 0.165580E+10 | 0.109624E+10 | 0.559559E+09 | 0.142908E+10 | 0.123136E+10 |
March | 0.165376E+10 | 0.918111E+09 | 0.735648E+09 | 0.136725E+10 | 0.103457E+10 |
April | 0.124127E+10 | 0.490723E+09 | 0.750543E+09 | 0.882840E+09 | 0.741824E+09 |
May | 0.112404E+10 | 0.234319E+09 | 0.889719E+09 | 0.837315E+09 | 0.467305E+09 |
June | 0.102078E+10 | 0.155844E+09 | 0.864935E+09 | 0.943399E+09 | 0.237332E+09 |
July | 0.110570E+10 | 0.191900E+09 | 0.913799E+09 | 0.116604E+10 | 0.122005E+09 |
August | 0.147657E+10 | 0.547544E+09 | 0.929029E+09 | 0.151912E+10 | 0.172888E+09 |
September | 0.155087E+10 | 0.802273E+09 | 0.748597E+09 | 0.158893E+10 | 0.355983E+09 |
October | 0.219612E+10 | 0.137751E+10 | 0.818608E+09 | 0.229295E+10 | 0.679563E+09 |
November | 0.147318E+10 | 0.884792E+09 | 0.588393E+09 | 0.137311E+10 | 0.981743E+09 |
December | 0.150559E+10 | 0.106881E+10 | 0.436779E+09 | 0.139817E+10 | 0.126295E+10 |
Annual Sum or Average | 0.173930E+11 | 0.867782E+10 | 0.871518E+10 | 0.160144E+11 | 0.862750E+10 |
Minimum of Months | 0.102078E+10 | 0.155844E+09 | 0.436779E+09 | 0.837315E+09 | 0.122005E+09 |
Maximum of Months | 0.219612E+10 | 0.137751E+10 | 0.929029E+09 | 0.229295E+10 | 0.133998E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138932E+10 | 0.909744E+09 | 0.479573E+09 | 0.121620E+10 | 0.133998E+10 |
February | 0.165579E+10 | 0.109624E+10 | 0.559556E+09 | 0.142906E+10 | 0.123136E+10 |
March | 0.165375E+10 | 0.918104E+09 | 0.735644E+09 | 0.136724E+10 | 0.103457E+10 |
April | 0.124126E+10 | 0.490719E+09 | 0.750539E+09 | 0.882833E+09 | 0.741824E+09 |
May | 0.112403E+10 | 0.234318E+09 | 0.889714E+09 | 0.837310E+09 | 0.467305E+09 |
June | 0.102077E+10 | 0.155843E+09 | 0.864931E+09 | 0.943394E+09 | 0.237332E+09 |
July | 0.110569E+10 | 0.191899E+09 | 0.913795E+09 | 0.116604E+10 | 0.122004E+09 |
August | 0.147656E+10 | 0.547540E+09 | 0.929024E+09 | 0.151912E+10 | 0.172887E+09 |
September | 0.155086E+10 | 0.802267E+09 | 0.748593E+09 | 0.158892E+10 | 0.355982E+09 |
October | 0.219611E+10 | 0.137750E+10 | 0.818604E+09 | 0.229293E+10 | 0.679563E+09 |
November | 0.147317E+10 | 0.884785E+09 | 0.588389E+09 | 0.137310E+10 | 0.981743E+09 |
December | 0.150558E+10 | 0.106880E+10 | 0.436777E+09 | 0.139816E+10 | 0.126295E+10 |
Annual Sum or Average | 0.173929E+11 | 0.867776E+10 | 0.871514E+10 | 0.160143E+11 | 0.862749E+10 |
Minimum of Months | 0.102077E+10 | 0.155843E+09 | 0.436777E+09 | 0.837310E+09 | 0.122004E+09 |
Maximum of Months | 0.219611E+10 | 0.137750E+10 | 0.929024E+09 | 0.229293E+10 | 0.133998E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138927E+10 | 0.909710E+09 | 0.479555E+09 | 0.121616E+10 | 0.133993E+10 |
February | 0.165573E+10 | 0.109620E+10 | 0.559535E+09 | 0.142901E+10 | 0.123131E+10 |
March | 0.165369E+10 | 0.918071E+09 | 0.735616E+09 | 0.136719E+10 | 0.103452E+10 |
April | 0.124121E+10 | 0.490701E+09 | 0.750510E+09 | 0.882801E+09 | 0.741794E+09 |
May | 0.112399E+10 | 0.234309E+09 | 0.889681E+09 | 0.837279E+09 | 0.467286E+09 |
June | 0.102074E+10 | 0.155838E+09 | 0.864898E+09 | 0.943358E+09 | 0.237323E+09 |
July | 0.110565E+10 | 0.191892E+09 | 0.913760E+09 | 0.116599E+10 | 0.122000E+09 |
August | 0.147651E+10 | 0.547520E+09 | 0.928989E+09 | 0.151906E+10 | 0.172881E+09 |
September | 0.155080E+10 | 0.802238E+09 | 0.748565E+09 | 0.158887E+10 | 0.355968E+09 |
October | 0.219602E+10 | 0.137745E+10 | 0.818573E+09 | 0.229285E+10 | 0.679536E+09 |
November | 0.147312E+10 | 0.884753E+09 | 0.588368E+09 | 0.137305E+10 | 0.981704E+09 |
December | 0.150552E+10 | 0.106876E+10 | 0.436760E+09 | 0.139811E+10 | 0.126289E+10 |
Annual Sum or Average | 0.173923E+11 | 0.867744E+10 | 0.871481E+10 | 0.160137E+11 | 0.862715E+10 |
Minimum of Months | 0.102074E+10 | 0.155838E+09 | 0.436760E+09 | 0.837279E+09 | 0.122000E+09 |
Maximum of Months | 0.219602E+10 | 0.137745E+10 | 0.928989E+09 | 0.229285E+10 | 0.133993E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.615427E+09 | 0.252119E+09 | 0.363308E+09 | 0.262300E+09 | 0.171260E+10 |
February | 0.819626E+09 | 0.359984E+09 | 0.459642E+09 | 0.405550E+09 | 0.159840E+10 |
March | 0.134004E+10 | 0.618712E+09 | 0.721330E+09 | 0.945263E+09 | 0.127155E+10 |
April | 0.141730E+10 | 0.606454E+09 | 0.810849E+09 | 0.114717E+10 | 0.930953E+09 |
May | 0.170582E+10 | 0.647694E+09 | 0.105812E+10 | 0.163900E+10 | 0.549198E+09 |
June | 0.180672E+10 | 0.728583E+09 | 0.107814E+10 | 0.197769E+10 | 0.303165E+09 |
July | 0.174854E+10 | 0.658353E+09 | 0.109019E+10 | 0.205759E+10 | 0.178223E+09 |
August | 0.193451E+10 | 0.895535E+09 | 0.103897E+10 | 0.228426E+10 | 0.245697E+09 |
September | 0.132915E+10 | 0.580885E+09 | 0.748265E+09 | 0.139177E+10 | 0.425176E+09 |
October | 0.136159E+10 | 0.662112E+09 | 0.699481E+09 | 0.123525E+10 | 0.830400E+09 |
November | 0.618780E+09 | 0.178839E+09 | 0.439942E+09 | 0.267035E+09 | 0.129772E+10 |
December | 0.568802E+09 | 0.246163E+09 | 0.322639E+09 | 0.229235E+09 | 0.175359E+10 |
Annual Sum or Average | 0.152663E+11 | 0.643543E+10 | 0.883088E+10 | 0.138421E+11 | 0.110967E+11 |
Minimum of Months | 0.568802E+09 | 0.178839E+09 | 0.322639E+09 | 0.229235E+09 | 0.178223E+09 |
Maximum of Months | 0.193451E+10 | 0.895535E+09 | 0.109019E+10 | 0.228426E+10 | 0.175359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.615427E+09 | 0.252119E+09 | 0.363308E+09 | 0.262300E+09 | 0.171260E+10 |
February | 0.819626E+09 | 0.359984E+09 | 0.459642E+09 | 0.405550E+09 | 0.159840E+10 |
March | 0.134004E+10 | 0.618712E+09 | 0.721330E+09 | 0.945263E+09 | 0.127155E+10 |
April | 0.141730E+10 | 0.606454E+09 | 0.810849E+09 | 0.114717E+10 | 0.930953E+09 |
May | 0.170582E+10 | 0.647694E+09 | 0.105812E+10 | 0.163900E+10 | 0.549198E+09 |
June | 0.180672E+10 | 0.728583E+09 | 0.107814E+10 | 0.197769E+10 | 0.303165E+09 |
July | 0.174854E+10 | 0.658353E+09 | 0.109019E+10 | 0.205759E+10 | 0.178223E+09 |
August | 0.193451E+10 | 0.895535E+09 | 0.103897E+10 | 0.228426E+10 | 0.245697E+09 |
September | 0.132915E+10 | 0.580885E+09 | 0.748265E+09 | 0.139177E+10 | 0.425176E+09 |
October | 0.136159E+10 | 0.662112E+09 | 0.699481E+09 | 0.123525E+10 | 0.830400E+09 |
November | 0.618780E+09 | 0.178839E+09 | 0.439942E+09 | 0.267035E+09 | 0.129772E+10 |
December | 0.568802E+09 | 0.246163E+09 | 0.322639E+09 | 0.229235E+09 | 0.175359E+10 |
Annual Sum or Average | 0.152663E+11 | 0.643543E+10 | 0.883088E+10 | 0.138421E+11 | 0.110967E+11 |
Minimum of Months | 0.568802E+09 | 0.178839E+09 | 0.322639E+09 | 0.229235E+09 | 0.178223E+09 |
Maximum of Months | 0.193451E+10 | 0.895535E+09 | 0.109019E+10 | 0.228426E+10 | 0.175359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.615416E+09 | 0.252114E+09 | 0.363302E+09 | 0.262295E+09 | 0.171256E+10 |
February | 0.819611E+09 | 0.359977E+09 | 0.459633E+09 | 0.405543E+09 | 0.159837E+10 |
March | 0.134002E+10 | 0.618701E+09 | 0.721317E+09 | 0.945246E+09 | 0.127152E+10 |
April | 0.141728E+10 | 0.606443E+09 | 0.810835E+09 | 0.114715E+10 | 0.930936E+09 |
May | 0.170579E+10 | 0.647682E+09 | 0.105810E+10 | 0.163897E+10 | 0.549188E+09 |
June | 0.180669E+10 | 0.728569E+09 | 0.107812E+10 | 0.197765E+10 | 0.303160E+09 |
July | 0.174851E+10 | 0.658341E+09 | 0.109017E+10 | 0.205755E+10 | 0.178220E+09 |
August | 0.193447E+10 | 0.895518E+09 | 0.103895E+10 | 0.228422E+10 | 0.245692E+09 |
September | 0.132912E+10 | 0.580874E+09 | 0.748251E+09 | 0.139175E+10 | 0.425168E+09 |
October | 0.136157E+10 | 0.662100E+09 | 0.699468E+09 | 0.123523E+10 | 0.830385E+09 |
November | 0.618769E+09 | 0.178835E+09 | 0.439934E+09 | 0.267031E+09 | 0.129770E+10 |
December | 0.568791E+09 | 0.246158E+09 | 0.322633E+09 | 0.229231E+09 | 0.175356E+10 |
Annual Sum or Average | 0.152660E+11 | 0.643531E+10 | 0.883072E+10 | 0.138419E+11 | 0.110965E+11 |
Minimum of Months | 0.568791E+09 | 0.178835E+09 | 0.322633E+09 | 0.229231E+09 | 0.178220E+09 |
Maximum of Months | 0.193447E+10 | 0.895518E+09 | 0.109017E+10 | 0.228422E+10 | 0.175356E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134280E+10 | 0.00 | 0.134280E+10 | 28072076.67 | 0.708001E+10 |
February | 0.165973E+10 | 0.00 | 0.165973E+10 | 76150945.77 | 0.668666E+10 |
March | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.588365E+09 | 0.501122E+10 |
April | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.138513E+10 | 0.343460E+10 |
May | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.291716E+10 | 0.212024E+10 |
June | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.405849E+10 | 0.107501E+10 |
July | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.481034E+10 | 0.605068E+09 |
August | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.430121E+10 | 0.834765E+09 |
September | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.236576E+10 | 0.165030E+10 |
October | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.136989E+10 | 0.320213E+10 |
November | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.278220E+09 | 0.494038E+10 |
December | 0.117128E+10 | 0.00 | 0.117128E+10 | 17270851.31 | 0.672877E+10 |
Annual Sum or Average | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.221961E+11 | 0.433692E+11 |
Minimum of Months | 0.117128E+10 | 0.00 | 0.117128E+10 | 17270851.31 | 0.605068E+09 |
Maximum of Months | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.481034E+10 | 0.708001E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.822836E+09 | 0.434659E+10 |
February | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.140767E+10 | 0.397340E+10 |
March | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.261121E+10 | 0.315754E+10 |
April | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.359287E+10 | 0.215226E+10 |
May | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.525866E+10 | 0.137728E+10 |
June | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.528846E+10 | 0.692036E+09 |
July | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.601250E+10 | 0.373808E+09 |
August | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.676773E+10 | 0.521647E+09 |
September | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.428109E+10 | 0.101328E+10 |
October | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.344575E+10 | 0.200823E+10 |
November | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.136912E+10 | 0.301119E+10 |
December | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.875158E+09 | 0.407156E+10 |
Annual Sum or Average | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.417331E+11 | 0.266988E+11 |
Minimum of Months | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.822836E+09 | 0.373808E+09 |
Maximum of Months | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.676773E+10 | 0.434659E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.610104E+10 | 0.636395E+10 |
February | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.712787E+10 | 0.595910E+10 |
March | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.682869E+10 | 0.495101E+10 |
April | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.445465E+10 | 0.352014E+10 |
May | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.421003E+10 | 0.226271E+10 |
June | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.474285E+10 | 0.115218E+10 |
July | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.585851E+10 | 0.627791E+09 |
August | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.761758E+10 | 0.898743E+09 |
September | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.792271E+10 | 0.173970E+10 |
October | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.114018E+11 | 0.332892E+10 |
November | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.687023E+10 | 0.466815E+10 |
December | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.699822E+10 | 0.599322E+10 |
Annual Sum or Average | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.801341E+11 | 0.414656E+11 |
Minimum of Months | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.421003E+10 | 0.627791E+09 |
Maximum of Months | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.114018E+11 | 0.636395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.837170E+09 | 0.452836E+10 |
February | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.128997E+10 | 0.422317E+10 |
March | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.296737E+10 | 0.323411E+10 |
April | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.360538E+10 | 0.230997E+10 |
May | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.500185E+10 | 0.149474E+10 |
June | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.601405E+10 | 0.801672E+09 |
July | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.627941E+10 | 0.463662E+09 |
August | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.696453E+10 | 0.654658E+09 |
September | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.425450E+10 | 0.112163E+10 |
October | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.382730E+10 | 0.215791E+10 |
November | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.919164E+09 | 0.317891E+10 |
December | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.775690E+09 | 0.429298E+10 |
Annual Sum or Average | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.427364E+11 | 0.284618E+11 |
Minimum of Months | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.775690E+09 | 0.463662E+09 |
Maximum of Months | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.696453E+10 | 0.452836E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134280E+10 | 0.00 | 0.134280E+10 | 45804592.35 | 0.662778E+10 |
February | 0.165973E+10 | 0.00 | 0.165973E+10 | 0.106288E+09 | 0.622600E+10 |
March | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.664262E+09 | 0.458745E+10 |
April | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.146520E+10 | 0.315483E+10 |
May | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.295166E+10 | 0.201282E+10 |
June | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.403155E+10 | 0.105744E+10 |
July | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.475693E+10 | 0.615102E+09 |
August | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.426582E+10 | 0.825500E+09 |
September | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.238604E+10 | 0.155428E+10 |
October | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.146001E+10 | 0.292085E+10 |
November | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.353803E+09 | 0.441879E+10 |
December | 0.117128E+10 | 0.00 | 0.117128E+10 | 40206244.91 | 0.609024E+10 |
Annual Sum or Average | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.225276E+11 | 0.400911E+11 |
Minimum of Months | 0.117128E+10 | 0.00 | 0.117128E+10 | 40206244.91 | 0.615102E+09 |
Maximum of Months | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.475693E+10 | 0.662778E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.853190E+09 | 0.408728E+10 |
February | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.146073E+10 | 0.371499E+10 |
March | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.266951E+10 | 0.293042E+10 |
April | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.363832E+10 | 0.201803E+10 |
May | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.526322E+10 | 0.132883E+10 |
June | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.525925E+10 | 0.691825E+09 |
July | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.596831E+10 | 0.386932E+09 |
August | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.673359E+10 | 0.524957E+09 |
September | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.428315E+10 | 0.973275E+09 |
October | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.349682E+10 | 0.186910E+10 |
November | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.144189E+10 | 0.273988E+10 |
December | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.925104E+09 | 0.371794E+10 |
Annual Sum or Average | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.419931E+11 | 0.249835E+11 |
Minimum of Months | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.853190E+09 | 0.386932E+09 |
Maximum of Months | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.673359E+10 | 0.408728E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.617999E+10 | 0.592907E+10 |
February | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.724176E+10 | 0.550988E+10 |
March | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.691422E+10 | 0.454923E+10 |
April | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.453587E+10 | 0.326051E+10 |
May | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.424614E+10 | 0.215302E+10 |
June | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.472270E+10 | 0.113384E+10 |
July | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.581556E+10 | 0.636552E+09 |
August | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.759337E+10 | 0.888255E+09 |
September | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.794339E+10 | 0.165162E+10 |
October | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.114780E+11 | 0.308799E+10 |
November | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.699782E+10 | 0.422157E+10 |
December | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.712902E+10 | 0.543130E+10 |
Annual Sum or Average | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.807979E+11 | 0.384528E+11 |
Minimum of Months | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.424614E+10 | 0.636552E+09 |
Maximum of Months | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.114780E+11 | 0.592907E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.857546E+09 | 0.427585E+10 |
February | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.131383E+10 | 0.398539E+10 |
March | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.300548E+10 | 0.302161E+10 |
April | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.364071E+10 | 0.216585E+10 |
May | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.501501E+10 | 0.143167E+10 |
June | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.599979E+10 | 0.786992E+09 |
July | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.625172E+10 | 0.463227E+09 |
August | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.694871E+10 | 0.641693E+09 |
September | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.426566E+10 | 0.106913E+10 |
October | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.386690E+10 | 0.201583E+10 |
November | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.965944E+09 | 0.292318E+10 |
December | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.805408E+09 | 0.397540E+10 |
Annual Sum or Average | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.429367E+11 | 0.267558E+11 |
Minimum of Months | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.805408E+09 | 0.463227E+09 |
Maximum of Months | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.694871E+10 | 0.427585E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.41 | 2986.68 | 501.33 | 0.00 | 501.33 | 0.00 | 0.00 |
February | 17.30 | 3066.86 | 686.05 | 0.00 | 686.05 | 0.00 | 0.00 |
March | 181.38 | 2099.27 | 951.39 | 0.00 | 951.39 | 0.00 | 0.00 |
April | 489.90 | 1481.30 | 1142.69 | 3.20 | 1139.49 | 0.00 | 0.00 |
May | 1064.94 | 842.91 | 1515.90 | 50.35 | 1465.54 | 0.00 | 0.00 |
June | 1549.13 | 436.15 | 1607.56 | 86.19 | 1521.37 | 0.00 | 0.00 |
July | 1783.59 | 225.06 | 1553.58 | 56.02 | 1497.56 | 0.00 | 0.00 |
August | 1588.18 | 311.23 | 1376.43 | 16.26 | 1360.16 | 0.00 | 0.00 |
September | 891.34 | 689.01 | 1037.68 | 0.19 | 1037.49 | 0.00 | 0.00 |
October | 476.55 | 1318.43 | 898.04 | 0.00 | 898.04 | 0.00 | 0.00 |
November | 83.23 | 2189.11 | 629.89 | 0.00 | 629.89 | 0.00 | 0.00 |
December | 1.99 | 2893.51 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Annual Sum or Average | 682.09 | 1536.24 | 1030.13 | 17.78 | 1012.35 | 0.00 | 0.00 |
Minimum of Months | 1.99 | 225.06 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Maximum of Months | 1783.59 | 3066.86 | 1607.56 | 86.19 | 1521.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.60 | 1799.66 | 698.24 | 279.98 | 418.26 | 0.00 | 0.00 |
February | 559.29 | 1780.06 | 1082.71 | 505.09 | 577.62 | 0.00 | 0.00 |
March | 957.94 | 1274.65 | 1381.19 | 587.42 | 793.76 | 0.00 | 0.00 |
April | 1375.57 | 885.23 | 1657.61 | 726.13 | 931.48 | 0.00 | 0.00 |
May | 1960.76 | 541.40 | 2010.05 | 803.22 | 1206.83 | 0.00 | 0.00 |
June | 2044.16 | 270.30 | 1862.88 | 674.23 | 1188.65 | 0.00 | 0.00 |
July | 2258.65 | 119.07 | 1871.04 | 675.10 | 1195.94 | 0.00 | 0.00 |
August | 2544.26 | 168.27 | 2107.00 | 950.02 | 1156.98 | 0.00 | 0.00 |
September | 1646.05 | 416.38 | 1571.57 | 705.17 | 866.40 | 0.00 | 0.00 |
October | 1271.96 | 806.01 | 1424.67 | 645.73 | 778.94 | 0.00 | 0.00 |
November | 502.68 | 1289.13 | 881.08 | 338.38 | 542.70 | 0.00 | 0.00 |
December | 309.69 | 1678.93 | 686.47 | 322.38 | 364.09 | 0.00 | 0.00 |
Annual Sum or Average | 1315.15 | 914.25 | 1438.49 | 601.75 | 836.74 | 0.00 | 0.00 |
Minimum of Months | 287.60 | 119.07 | 686.47 | 279.98 | 364.09 | 0.00 | 0.00 |
Maximum of Months | 2544.26 | 1799.66 | 2107.00 | 950.02 | 1206.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2270.38 | 2501.44 | 2593.54 | 1698.29 | 895.26 | 0.00 | 0.00 |
February | 2953.57 | 2544.95 | 3422.18 | 2265.69 | 1156.48 | 0.00 | 0.00 |
March | 2552.34 | 1931.30 | 3087.18 | 1713.90 | 1373.28 | 0.00 | 0.00 |
April | 1702.99 | 1430.98 | 2394.39 | 946.60 | 1447.79 | 0.00 | 0.00 |
May | 1563.07 | 872.35 | 2098.32 | 437.42 | 1660.90 | 0.00 | 0.00 |
June | 1819.81 | 457.81 | 1969.07 | 300.62 | 1668.45 | 0.00 | 0.00 |
July | 2176.73 | 227.75 | 2064.08 | 358.23 | 1705.85 | 0.00 | 0.00 |
August | 2835.85 | 322.74 | 2756.42 | 1022.14 | 1734.28 | 0.00 | 0.00 |
September | 3065.04 | 686.69 | 2991.61 | 1547.58 | 1444.04 | 0.00 | 0.00 |
October | 4280.40 | 1268.59 | 4099.64 | 2571.49 | 1528.15 | 0.00 | 0.00 |
November | 2648.71 | 1893.78 | 2841.76 | 1706.75 | 1135.00 | 0.00 | 0.00 |
December | 2610.06 | 2357.63 | 2810.58 | 1995.22 | 815.36 | 0.00 | 0.00 |
Annual Sum or Average | 2539.04 | 1367.87 | 2757.61 | 1375.84 | 1381.77 | 0.00 | 0.00 |
Minimum of Months | 1563.07 | 227.75 | 1969.07 | 300.62 | 815.36 | 0.00 | 0.00 |
Maximum of Months | 4280.40 | 2544.95 | 4099.64 | 2571.49 | 1734.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.79 | 1918.22 | 689.32 | 282.39 | 406.93 | 0.00 | 0.00 |
February | 502.91 | 1982.13 | 1016.39 | 446.41 | 569.99 | 0.00 | 0.00 |
March | 1058.76 | 1424.21 | 1500.93 | 693.00 | 807.94 | 0.00 | 0.00 |
April | 1327.74 | 1077.48 | 1640.39 | 701.91 | 938.48 | 0.00 | 0.00 |
May | 1835.79 | 615.14 | 1910.63 | 725.46 | 1185.17 | 0.00 | 0.00 |
June | 2288.98 | 350.88 | 2091.10 | 843.26 | 1247.84 | 0.00 | 0.00 |
July | 2304.63 | 199.62 | 1958.48 | 737.40 | 1221.08 | 0.00 | 0.00 |
August | 2558.52 | 275.20 | 2166.77 | 1003.06 | 1163.71 | 0.00 | 0.00 |
September | 1610.84 | 492.10 | 1538.36 | 672.32 | 866.04 | 0.00 | 0.00 |
October | 1383.56 | 930.10 | 1525.07 | 741.61 | 783.46 | 0.00 | 0.00 |
November | 309.07 | 1501.98 | 716.18 | 206.99 | 509.19 | 0.00 | 0.00 |
December | 256.76 | 1964.13 | 637.09 | 275.72 | 361.38 | 0.00 | 0.00 |
Annual Sum or Average | 1316.78 | 1055.61 | 1452.27 | 612.19 | 840.07 | 0.00 | 0.00 |
Minimum of Months | 256.76 | 199.62 | 637.09 | 206.99 | 361.38 | 0.00 | 0.00 |
Maximum of Months | 2558.52 | 1982.13 | 2166.77 | 1003.06 | 1247.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.48 | 2643.37 | 501.34 | 0.00 | 501.34 | 0.00 | 0.00 |
February | 31.48 | 2764.00 | 686.07 | 0.00 | 686.07 | 0.00 | 0.00 |
March | 219.67 | 1870.98 | 951.40 | 0.00 | 951.40 | 0.00 | 0.00 |
April | 534.39 | 1325.08 | 1142.71 | 3.20 | 1139.51 | 0.00 | 0.00 |
May | 1089.14 | 791.61 | 1515.92 | 50.36 | 1465.57 | 0.00 | 0.00 |
June | 1565.77 | 414.74 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
July | 1795.97 | 225.91 | 1553.61 | 56.03 | 1497.58 | 0.00 | 0.00 |
August | 1605.89 | 311.67 | 1376.45 | 16.27 | 1360.19 | 0.00 | 0.00 |
September | 912.72 | 636.69 | 1037.70 | 0.19 | 1037.51 | 0.00 | 0.00 |
October | 511.46 | 1195.54 | 898.06 | 0.00 | 898.06 | 0.00 | 0.00 |
November | 107.34 | 1906.01 | 629.90 | 0.00 | 629.90 | 0.00 | 0.00 |
December | 6.45 | 2512.23 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Annual Sum or Average | 703.83 | 1375.23 | 1030.15 | 17.78 | 1012.37 | 0.00 | 0.00 |
Minimum of Months | 6.45 | 225.91 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Maximum of Months | 1795.97 | 2764.00 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.21 | 1622.83 | 698.24 | 279.98 | 418.26 | 0.00 | 0.00 |
February | 581.87 | 1642.44 | 1082.71 | 505.09 | 577.62 | 0.00 | 0.00 |
March | 974.92 | 1178.89 | 1381.18 | 587.42 | 793.76 | 0.00 | 0.00 |
April | 1386.14 | 830.35 | 1657.61 | 726.13 | 931.48 | 0.00 | 0.00 |
May | 1963.36 | 514.22 | 2010.04 | 803.22 | 1206.82 | 0.00 | 0.00 |
June | 2040.30 | 266.99 | 1862.87 | 674.23 | 1188.64 | 0.00 | 0.00 |
July | 2244.81 | 139.56 | 1871.04 | 675.10 | 1195.94 | 0.00 | 0.00 |
August | 2526.78 | 194.76 | 2106.99 | 950.02 | 1156.97 | 0.00 | 0.00 |
September | 1651.65 | 390.92 | 1571.56 | 705.17 | 866.39 | 0.00 | 0.00 |
October | 1286.50 | 749.79 | 1424.67 | 645.73 | 778.94 | 0.00 | 0.00 |
November | 528.21 | 1161.73 | 881.08 | 338.38 | 542.70 | 0.00 | 0.00 |
December | 326.75 | 1520.15 | 686.47 | 322.38 | 364.09 | 0.00 | 0.00 |
Annual Sum or Average | 1323.35 | 846.61 | 1438.48 | 601.75 | 836.73 | 0.00 | 0.00 |
Minimum of Months | 307.21 | 139.56 | 686.47 | 279.98 | 364.09 | 0.00 | 0.00 |
Maximum of Months | 2526.78 | 1642.44 | 2106.99 | 950.02 | 1206.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2277.87 | 2376.03 | 2593.62 | 1698.34 | 895.28 | 0.00 | 0.00 |
February | 2946.38 | 2463.25 | 3422.28 | 2265.77 | 1156.51 | 0.00 | 0.00 |
March | 2549.54 | 1848.50 | 3087.27 | 1713.95 | 1373.31 | 0.00 | 0.00 |
April | 1718.62 | 1358.08 | 2394.45 | 946.63 | 1447.82 | 0.00 | 0.00 |
May | 1571.84 | 844.80 | 2098.37 | 437.43 | 1660.93 | 0.00 | 0.00 |
June | 1829.80 | 444.52 | 1969.12 | 300.63 | 1668.49 | 0.00 | 0.00 |
July | 2187.32 | 234.39 | 2064.13 | 358.24 | 1705.89 | 0.00 | 0.00 |
August | 2844.08 | 335.55 | 2756.49 | 1022.17 | 1734.32 | 0.00 | 0.00 |
September | 3056.60 | 671.18 | 2991.70 | 1547.63 | 1444.07 | 0.00 | 0.00 |
October | 4256.93 | 1242.88 | 4099.76 | 2571.57 | 1528.19 | 0.00 | 0.00 |
November | 2650.55 | 1800.98 | 2841.85 | 1706.81 | 1135.04 | 0.00 | 0.00 |
December | 2612.83 | 2237.61 | 2810.67 | 1995.28 | 815.39 | 0.00 | 0.00 |
Annual Sum or Average | 2541.04 | 1314.87 | 2757.69 | 1375.89 | 1381.80 | 0.00 | 0.00 |
Minimum of Months | 1571.84 | 234.39 | 1969.12 | 300.63 | 815.39 | 0.00 | 0.00 |
Maximum of Months | 4256.93 | 2463.25 | 4099.76 | 2571.57 | 1734.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 312.56 | 1690.70 | 689.32 | 282.39 | 406.93 | 0.00 | 0.00 |
February | 533.22 | 1745.69 | 1016.39 | 446.40 | 569.99 | 0.00 | 0.00 |
March | 1107.89 | 1207.48 | 1500.93 | 692.99 | 807.93 | 0.00 | 0.00 |
April | 1390.96 | 891.19 | 1640.38 | 701.91 | 938.47 | 0.00 | 0.00 |
May | 1867.48 | 558.07 | 1910.62 | 725.46 | 1185.16 | 0.00 | 0.00 |
June | 2320.24 | 309.29 | 2091.09 | 843.26 | 1247.84 | 0.00 | 0.00 |
July | 2344.46 | 173.11 | 1958.47 | 737.40 | 1221.08 | 0.00 | 0.00 |
August | 2600.26 | 244.42 | 2166.76 | 1003.05 | 1163.71 | 0.00 | 0.00 |
September | 1641.40 | 432.73 | 1538.35 | 672.31 | 866.04 | 0.00 | 0.00 |
October | 1428.95 | 805.67 | 1525.07 | 741.61 | 783.46 | 0.00 | 0.00 |
November | 354.62 | 1226.43 | 716.17 | 206.99 | 509.19 | 0.00 | 0.00 |
December | 289.61 | 1602.82 | 637.09 | 275.72 | 361.38 | 0.00 | 0.00 |
Annual Sum or Average | 1355.16 | 902.52 | 1452.26 | 612.19 | 840.07 | 0.00 | 0.00 |
Minimum of Months | 289.61 | 173.11 | 637.09 | 206.99 | 361.38 | 0.00 | 0.00 |
Maximum of Months | 2600.26 | 1745.69 | 2166.76 | 1003.05 | 1247.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.10 | 2474.53 | 501.34 | 0.00 | 501.34 | 0.00 | 0.00 |
February | 43.94 | 2573.58 | 686.07 | 0.00 | 686.07 | 0.00 | 0.00 |
March | 248.01 | 1712.76 | 951.40 | 0.00 | 951.40 | 0.00 | 0.00 |
April | 565.28 | 1217.14 | 1142.71 | 3.20 | 1139.51 | 0.00 | 0.00 |
May | 1102.02 | 751.50 | 1515.92 | 50.36 | 1465.57 | 0.00 | 0.00 |
June | 1555.38 | 407.96 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
July | 1776.03 | 229.65 | 1553.61 | 56.03 | 1497.58 | 0.00 | 0.00 |
August | 1592.67 | 308.21 | 1376.45 | 16.27 | 1360.19 | 0.00 | 0.00 |
September | 920.54 | 599.64 | 1037.70 | 0.19 | 1037.51 | 0.00 | 0.00 |
October | 545.11 | 1090.52 | 898.06 | 0.00 | 898.06 | 0.00 | 0.00 |
November | 136.50 | 1704.78 | 629.90 | 0.00 | 629.90 | 0.00 | 0.00 |
December | 15.01 | 2273.84 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Annual Sum or Average | 714.34 | 1271.28 | 1030.15 | 17.78 | 1012.37 | 0.00 | 0.00 |
Minimum of Months | 15.01 | 229.65 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Maximum of Months | 1776.03 | 2573.58 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.54 | 1526.02 | 698.24 | 279.98 | 418.26 | 0.00 | 0.00 |
February | 603.81 | 1535.63 | 1082.71 | 505.09 | 577.62 | 0.00 | 0.00 |
March | 996.68 | 1094.09 | 1381.18 | 587.42 | 793.76 | 0.00 | 0.00 |
April | 1403.67 | 778.56 | 1657.61 | 726.13 | 931.48 | 0.00 | 0.00 |
May | 1965.06 | 496.13 | 2010.04 | 803.22 | 1206.82 | 0.00 | 0.00 |
June | 2029.03 | 266.91 | 1862.87 | 674.23 | 1188.64 | 0.00 | 0.00 |
July | 2228.31 | 144.46 | 1871.04 | 675.10 | 1195.94 | 0.00 | 0.00 |
August | 2514.03 | 196.00 | 2106.99 | 950.02 | 1156.97 | 0.00 | 0.00 |
September | 1652.45 | 375.49 | 1571.56 | 705.17 | 866.39 | 0.00 | 0.00 |
October | 1305.56 | 697.84 | 1424.67 | 645.73 | 778.94 | 0.00 | 0.00 |
November | 556.29 | 1057.05 | 881.08 | 338.38 | 542.70 | 0.00 | 0.00 |
December | 345.39 | 1388.12 | 686.47 | 322.38 | 364.09 | 0.00 | 0.00 |
Annual Sum or Average | 1331.59 | 792.22 | 1438.48 | 601.75 | 836.73 | 0.00 | 0.00 |
Minimum of Months | 318.54 | 144.46 | 686.47 | 279.98 | 364.09 | 0.00 | 0.00 |
Maximum of Months | 2514.03 | 1535.63 | 2106.99 | 950.02 | 1206.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2307.35 | 2213.66 | 2593.62 | 1698.34 | 895.28 | 0.00 | 0.00 |
February | 2993.45 | 2277.56 | 3422.28 | 2265.77 | 1156.51 | 0.00 | 0.00 |
March | 2581.47 | 1698.49 | 3087.27 | 1713.95 | 1373.31 | 0.00 | 0.00 |
April | 1749.95 | 1257.91 | 2394.45 | 946.63 | 1447.82 | 0.00 | 0.00 |
May | 1585.33 | 803.85 | 2098.37 | 437.43 | 1660.93 | 0.00 | 0.00 |
June | 1822.03 | 437.44 | 1969.12 | 300.63 | 1668.49 | 0.00 | 0.00 |
July | 2171.28 | 237.66 | 2064.13 | 358.24 | 1705.89 | 0.00 | 0.00 |
August | 2835.04 | 331.64 | 2756.49 | 1022.17 | 1734.32 | 0.00 | 0.00 |
September | 3064.58 | 637.20 | 2991.70 | 1547.63 | 1444.07 | 0.00 | 0.00 |
October | 4285.40 | 1152.92 | 4099.76 | 2571.57 | 1528.19 | 0.00 | 0.00 |
November | 2699.78 | 1628.69 | 2841.85 | 1706.81 | 1135.04 | 0.00 | 0.00 |
December | 2661.67 | 2027.81 | 2810.67 | 1995.28 | 815.39 | 0.00 | 0.00 |
Annual Sum or Average | 2562.08 | 1219.33 | 2757.69 | 1375.89 | 1381.80 | 0.00 | 0.00 |
Minimum of Months | 1585.33 | 237.66 | 1969.12 | 300.63 | 815.39 | 0.00 | 0.00 |
Maximum of Months | 4285.40 | 2277.56 | 4099.76 | 2571.57 | 1734.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.17 | 1596.42 | 689.32 | 282.39 | 406.93 | 0.00 | 0.00 |
February | 543.08 | 1647.40 | 1016.39 | 446.40 | 569.99 | 0.00 | 0.00 |
March | 1122.12 | 1128.14 | 1500.93 | 692.99 | 807.93 | 0.00 | 0.00 |
April | 1404.60 | 835.59 | 1640.38 | 701.91 | 938.47 | 0.00 | 0.00 |
May | 1872.39 | 534.52 | 1910.62 | 725.46 | 1185.16 | 0.00 | 0.00 |
June | 2314.74 | 303.62 | 2091.09 | 843.26 | 1247.84 | 0.00 | 0.00 |
July | 2334.12 | 172.95 | 1958.47 | 737.40 | 1221.08 | 0.00 | 0.00 |
August | 2594.35 | 239.58 | 2166.76 | 1003.05 | 1163.71 | 0.00 | 0.00 |
September | 1645.70 | 412.47 | 1538.35 | 672.31 | 866.04 | 0.00 | 0.00 |
October | 1443.73 | 752.63 | 1525.07 | 741.61 | 783.46 | 0.00 | 0.00 |
November | 372.66 | 1127.77 | 716.17 | 206.99 | 509.19 | 0.00 | 0.00 |
December | 300.70 | 1484.25 | 637.09 | 275.72 | 361.38 | 0.00 | 0.00 |
Annual Sum or Average | 1361.51 | 848.42 | 1452.26 | 612.19 | 840.07 | 0.00 | 0.00 |
Minimum of Months | 300.70 | 172.95 | 637.09 | 206.99 | 361.38 | 0.00 | 0.00 |
Maximum of Months | 2594.35 | 1647.40 | 2166.76 | 1003.05 | 1247.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6448040.22 | 0.799953E+10 | 0.134277E+10 | 0.00 | 0.134277E+10 | 0.00 | 0.00 |
February | 41856005.62 | 0.741934E+10 | 0.165970E+10 | 0.00 | 0.165970E+10 | 0.00 | 0.00 |
March | 0.485813E+09 | 0.562268E+10 | 0.254819E+10 | 0.00 | 0.254819E+10 | 0.00 | 0.00 |
April | 0.126982E+10 | 0.383953E+10 | 0.296186E+10 | 8293119.36 | 0.295357E+10 | 0.00 | 0.00 |
May | 0.285234E+10 | 0.225766E+10 | 0.406018E+10 | 0.134869E+09 | 0.392531E+10 | 0.00 | 0.00 |
June | 0.401535E+10 | 0.113051E+10 | 0.416680E+10 | 0.223409E+09 | 0.394339E+10 | 0.00 | 0.00 |
July | 0.477718E+10 | 0.602799E+09 | 0.416111E+10 | 0.150053E+09 | 0.401106E+10 | 0.00 | 0.00 |
August | 0.425377E+10 | 0.833609E+09 | 0.368663E+10 | 43563661.02 | 0.364306E+10 | 0.00 | 0.00 |
September | 0.231036E+10 | 0.178591E+10 | 0.268966E+10 | 484697.40 | 0.268918E+10 | 0.00 | 0.00 |
October | 0.127639E+10 | 0.353129E+10 | 0.240532E+10 | 0.00 | 0.240532E+10 | 0.00 | 0.00 |
November | 0.215727E+09 | 0.567418E+10 | 0.163267E+10 | 0.00 | 0.163267E+10 | 0.00 | 0.00 |
December | 5320058.26 | 0.774997E+10 | 0.117125E+10 | 0.00 | 0.117125E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215104E+11 | 0.484470E+11 | 0.324861E+11 | 0.560672E+09 | 0.319255E+11 | 0.00 | 0.00 |
Minimum of Months | 5320058.26 | 0.602799E+09 | 0.117125E+10 | 0.00 | 0.117125E+10 | 0.00 | 0.00 |
Maximum of Months | 0.477718E+10 | 0.799953E+10 | 0.416680E+10 | 0.223409E+09 | 0.401106E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770320E+09 | 0.482021E+10 | 0.187016E+10 | 0.749900E+09 | 0.112026E+10 | 0.00 | 0.00 |
February | 0.135304E+10 | 0.430633E+10 | 0.261930E+10 | 0.122192E+10 | 0.139739E+10 | 0.00 | 0.00 |
March | 0.256574E+10 | 0.341402E+10 | 0.369937E+10 | 0.157335E+10 | 0.212602E+10 | 0.00 | 0.00 |
April | 0.356547E+10 | 0.229452E+10 | 0.429654E+10 | 0.188214E+10 | 0.241440E+10 | 0.00 | 0.00 |
May | 0.525171E+10 | 0.145008E+10 | 0.538371E+10 | 0.215135E+10 | 0.323236E+10 | 0.00 | 0.00 |
June | 0.529845E+10 | 0.700629E+09 | 0.482858E+10 | 0.174760E+10 | 0.308098E+10 | 0.00 | 0.00 |
July | 0.604957E+10 | 0.318904E+09 | 0.501140E+10 | 0.180819E+10 | 0.320321E+10 | 0.00 | 0.00 |
August | 0.681455E+10 | 0.450684E+09 | 0.564338E+10 | 0.254454E+10 | 0.309884E+10 | 0.00 | 0.00 |
September | 0.426656E+10 | 0.107924E+10 | 0.407351E+10 | 0.182781E+10 | 0.224570E+10 | 0.00 | 0.00 |
October | 0.340682E+10 | 0.215881E+10 | 0.381584E+10 | 0.172953E+10 | 0.208631E+10 | 0.00 | 0.00 |
November | 0.130295E+10 | 0.334143E+10 | 0.228377E+10 | 0.877089E+09 | 0.140668E+10 | 0.00 | 0.00 |
December | 0.829464E+09 | 0.449684E+10 | 0.183864E+10 | 0.863462E+09 | 0.975181E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.414747E+11 | 0.288317E+11 | 0.453642E+11 | 0.189769E+11 | 0.263873E+11 | 0.00 | 0.00 |
Minimum of Months | 0.770320E+09 | 0.318904E+09 | 0.183864E+10 | 0.749900E+09 | 0.975181E+09 | 0.00 | 0.00 |
Maximum of Months | 0.681455E+10 | 0.482021E+10 | 0.564338E+10 | 0.254454E+10 | 0.323236E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.608100E+10 | 0.669986E+10 | 0.694655E+10 | 0.454870E+10 | 0.239785E+10 | 0.00 | 0.00 |
February | 0.714529E+10 | 0.615675E+10 | 0.827893E+10 | 0.548116E+10 | 0.279777E+10 | 0.00 | 0.00 |
March | 0.683618E+10 | 0.517279E+10 | 0.826870E+10 | 0.459050E+10 | 0.367820E+10 | 0.00 | 0.00 |
April | 0.441415E+10 | 0.370909E+10 | 0.620626E+10 | 0.245359E+10 | 0.375267E+10 | 0.00 | 0.00 |
May | 0.418653E+10 | 0.233650E+10 | 0.562013E+10 | 0.117158E+10 | 0.444855E+10 | 0.00 | 0.00 |
June | 0.471694E+10 | 0.118665E+10 | 0.510384E+10 | 0.779213E+09 | 0.432463E+10 | 0.00 | 0.00 |
July | 0.583016E+10 | 0.610018E+09 | 0.552844E+10 | 0.959489E+09 | 0.456895E+10 | 0.00 | 0.00 |
August | 0.759553E+10 | 0.864432E+09 | 0.738278E+10 | 0.273769E+10 | 0.464509E+10 | 0.00 | 0.00 |
September | 0.794458E+10 | 0.177990E+10 | 0.775426E+10 | 0.401132E+10 | 0.374294E+10 | 0.00 | 0.00 |
October | 0.114646E+11 | 0.339779E+10 | 0.109805E+11 | 0.688748E+10 | 0.409300E+10 | 0.00 | 0.00 |
November | 0.686546E+10 | 0.490868E+10 | 0.736584E+10 | 0.442391E+10 | 0.294193E+10 | 0.00 | 0.00 |
December | 0.699078E+10 | 0.631468E+10 | 0.752786E+10 | 0.534399E+10 | 0.218387E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.800712E+11 | 0.431371E+11 | 0.869641E+11 | 0.433886E+11 | 0.435755E+11 | 0.00 | 0.00 |
Minimum of Months | 0.418653E+10 | 0.610018E+09 | 0.510384E+10 | 0.779213E+09 | 0.218387E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114646E+11 | 0.669986E+10 | 0.109805E+11 | 0.688748E+10 | 0.464509E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.786896E+09 | 0.513776E+10 | 0.184627E+10 | 0.756352E+09 | 0.108992E+10 | 0.00 | 0.00 |
February | 0.121664E+10 | 0.479517E+10 | 0.245886E+10 | 0.107994E+10 | 0.137892E+10 | 0.00 | 0.00 |
March | 0.283577E+10 | 0.381462E+10 | 0.402010E+10 | 0.185612E+10 | 0.216398E+10 | 0.00 | 0.00 |
April | 0.344149E+10 | 0.279284E+10 | 0.425188E+10 | 0.181935E+10 | 0.243253E+10 | 0.00 | 0.00 |
May | 0.491697E+10 | 0.164759E+10 | 0.511742E+10 | 0.194307E+10 | 0.317435E+10 | 0.00 | 0.00 |
June | 0.593303E+10 | 0.909490E+09 | 0.542014E+10 | 0.218573E+10 | 0.323441E+10 | 0.00 | 0.00 |
July | 0.617273E+10 | 0.534667E+09 | 0.524560E+10 | 0.197505E+10 | 0.327055E+10 | 0.00 | 0.00 |
August | 0.685275E+10 | 0.737086E+09 | 0.580348E+10 | 0.268659E+10 | 0.311689E+10 | 0.00 | 0.00 |
September | 0.417530E+10 | 0.127552E+10 | 0.398742E+10 | 0.174264E+10 | 0.224478E+10 | 0.00 | 0.00 |
October | 0.370572E+10 | 0.249118E+10 | 0.408475E+10 | 0.198633E+10 | 0.209843E+10 | 0.00 | 0.00 |
November | 0.801101E+09 | 0.389314E+10 | 0.185633E+10 | 0.536513E+09 | 0.131982E+10 | 0.00 | 0.00 |
December | 0.687702E+09 | 0.526074E+10 | 0.170640E+10 | 0.738484E+09 | 0.967911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.415261E+11 | 0.332898E+11 | 0.457987E+11 | 0.193062E+11 | 0.264925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.687702E+09 | 0.534667E+09 | 0.170640E+10 | 0.536513E+09 | 0.967911E+09 | 0.00 | 0.00 |
Maximum of Months | 0.685275E+10 | 0.526074E+10 | 0.580348E+10 | 0.268659E+10 | 0.327055E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 28072076.67 | 0.708001E+10 | 0.134280E+10 | 0.00 | 0.134280E+10 | 0.00 | 0.00 |
February | 76150945.77 | 0.668666E+10 | 0.165973E+10 | 0.00 | 0.165973E+10 | 0.00 | 0.00 |
March | 0.588365E+09 | 0.501122E+10 | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.00 | 0.00 |
April | 0.138513E+10 | 0.343460E+10 | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.00 | 0.00 |
May | 0.291716E+10 | 0.212024E+10 | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.00 | 0.00 |
June | 0.405849E+10 | 0.107501E+10 | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.00 | 0.00 |
July | 0.481034E+10 | 0.605068E+09 | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.00 | 0.00 |
August | 0.430121E+10 | 0.834765E+09 | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.00 | 0.00 |
September | 0.236576E+10 | 0.165030E+10 | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.00 | 0.00 |
October | 0.136989E+10 | 0.320213E+10 | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.00 | 0.00 |
November | 0.278220E+09 | 0.494038E+10 | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.00 | 0.00 |
December | 17270851.31 | 0.672877E+10 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.221961E+11 | 0.433692E+11 | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.00 | 0.00 |
Minimum of Months | 17270851.31 | 0.605068E+09 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Maximum of Months | 0.481034E+10 | 0.708001E+10 | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.822836E+09 | 0.434659E+10 | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.00 | 0.00 |
February | 0.140767E+10 | 0.397340E+10 | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.00 | 0.00 |
March | 0.261121E+10 | 0.315754E+10 | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.00 | 0.00 |
April | 0.359287E+10 | 0.215226E+10 | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.00 | 0.00 |
May | 0.525866E+10 | 0.137728E+10 | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.00 | 0.00 |
June | 0.528846E+10 | 0.692036E+09 | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.00 | 0.00 |
July | 0.601250E+10 | 0.373808E+09 | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.00 | 0.00 |
August | 0.676773E+10 | 0.521647E+09 | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.00 | 0.00 |
September | 0.428109E+10 | 0.101328E+10 | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.00 | 0.00 |
October | 0.344575E+10 | 0.200823E+10 | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.00 | 0.00 |
November | 0.136912E+10 | 0.301119E+10 | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.00 | 0.00 |
December | 0.875158E+09 | 0.407156E+10 | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.417331E+11 | 0.266988E+11 | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.822836E+09 | 0.373808E+09 | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.00 | 0.00 |
Maximum of Months | 0.676773E+10 | 0.434659E+10 | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.610104E+10 | 0.636395E+10 | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.00 | 0.00 |
February | 0.712787E+10 | 0.595910E+10 | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.00 | 0.00 |
March | 0.682869E+10 | 0.495101E+10 | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.00 | 0.00 |
April | 0.445465E+10 | 0.352014E+10 | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.00 | 0.00 |
May | 0.421003E+10 | 0.226271E+10 | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.00 | 0.00 |
June | 0.474285E+10 | 0.115218E+10 | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.00 | 0.00 |
July | 0.585851E+10 | 0.627791E+09 | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.00 | 0.00 |
August | 0.761758E+10 | 0.898743E+09 | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.00 | 0.00 |
September | 0.792271E+10 | 0.173970E+10 | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.00 | 0.00 |
October | 0.114018E+11 | 0.332892E+10 | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.00 | 0.00 |
November | 0.687023E+10 | 0.466815E+10 | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.00 | 0.00 |
December | 0.699822E+10 | 0.599322E+10 | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.801341E+11 | 0.414656E+11 | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.421003E+10 | 0.627791E+09 | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114018E+11 | 0.636395E+10 | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.837170E+09 | 0.452836E+10 | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.00 | 0.00 |
February | 0.128997E+10 | 0.422317E+10 | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.00 | 0.00 |
March | 0.296737E+10 | 0.323411E+10 | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.00 | 0.00 |
April | 0.360538E+10 | 0.230997E+10 | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.00 | 0.00 |
May | 0.500185E+10 | 0.149474E+10 | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.00 | 0.00 |
June | 0.601405E+10 | 0.801672E+09 | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.00 | 0.00 |
July | 0.627941E+10 | 0.463662E+09 | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.00 | 0.00 |
August | 0.696453E+10 | 0.654658E+09 | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.00 | 0.00 |
September | 0.425450E+10 | 0.112163E+10 | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.00 | 0.00 |
October | 0.382730E+10 | 0.215791E+10 | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.00 | 0.00 |
November | 0.919164E+09 | 0.317891E+10 | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.00 | 0.00 |
December | 0.775690E+09 | 0.429298E+10 | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427364E+11 | 0.284618E+11 | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.775690E+09 | 0.463662E+09 | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.00 | 0.00 |
Maximum of Months | 0.696453E+10 | 0.452836E+10 | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 45804592.35 | 0.662778E+10 | 0.134280E+10 | 0.00 | 0.134280E+10 | 0.00 | 0.00 |
February | 0.106288E+09 | 0.622600E+10 | 0.165973E+10 | 0.00 | 0.165973E+10 | 0.00 | 0.00 |
March | 0.664262E+09 | 0.458745E+10 | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.00 | 0.00 |
April | 0.146520E+10 | 0.315483E+10 | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.00 | 0.00 |
May | 0.295166E+10 | 0.201282E+10 | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.00 | 0.00 |
June | 0.403155E+10 | 0.105744E+10 | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.00 | 0.00 |
July | 0.475693E+10 | 0.615102E+09 | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.00 | 0.00 |
August | 0.426582E+10 | 0.825500E+09 | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.00 | 0.00 |
September | 0.238604E+10 | 0.155428E+10 | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.00 | 0.00 |
October | 0.146001E+10 | 0.292085E+10 | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.00 | 0.00 |
November | 0.353803E+09 | 0.441879E+10 | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.00 | 0.00 |
December | 40206244.91 | 0.609024E+10 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.225276E+11 | 0.400911E+11 | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.00 | 0.00 |
Minimum of Months | 40206244.91 | 0.615102E+09 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Maximum of Months | 0.475693E+10 | 0.662778E+10 | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.853190E+09 | 0.408728E+10 | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.00 | 0.00 |
February | 0.146073E+10 | 0.371499E+10 | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.00 | 0.00 |
March | 0.266951E+10 | 0.293042E+10 | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.00 | 0.00 |
April | 0.363832E+10 | 0.201803E+10 | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.00 | 0.00 |
May | 0.526322E+10 | 0.132883E+10 | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.00 | 0.00 |
June | 0.525925E+10 | 0.691825E+09 | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.00 | 0.00 |
July | 0.596831E+10 | 0.386932E+09 | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.00 | 0.00 |
August | 0.673359E+10 | 0.524957E+09 | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.00 | 0.00 |
September | 0.428315E+10 | 0.973275E+09 | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.00 | 0.00 |
October | 0.349682E+10 | 0.186910E+10 | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.00 | 0.00 |
November | 0.144189E+10 | 0.273988E+10 | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.00 | 0.00 |
December | 0.925104E+09 | 0.371794E+10 | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.419931E+11 | 0.249835E+11 | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.853190E+09 | 0.386932E+09 | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.00 | 0.00 |
Maximum of Months | 0.673359E+10 | 0.408728E+10 | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.617999E+10 | 0.592907E+10 | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.00 | 0.00 |
February | 0.724176E+10 | 0.550988E+10 | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.00 | 0.00 |
March | 0.691422E+10 | 0.454923E+10 | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.00 | 0.00 |
April | 0.453587E+10 | 0.326051E+10 | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.00 | 0.00 |
May | 0.424614E+10 | 0.215302E+10 | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.00 | 0.00 |
June | 0.472270E+10 | 0.113384E+10 | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.00 | 0.00 |
July | 0.581556E+10 | 0.636552E+09 | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.00 | 0.00 |
August | 0.759337E+10 | 0.888255E+09 | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.00 | 0.00 |
September | 0.794339E+10 | 0.165162E+10 | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.00 | 0.00 |
October | 0.114780E+11 | 0.308799E+10 | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.00 | 0.00 |
November | 0.699782E+10 | 0.422157E+10 | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.00 | 0.00 |
December | 0.712902E+10 | 0.543130E+10 | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.807979E+11 | 0.384528E+11 | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.424614E+10 | 0.636552E+09 | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114780E+11 | 0.592907E+10 | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.857546E+09 | 0.427585E+10 | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.00 | 0.00 |
February | 0.131383E+10 | 0.398539E+10 | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.00 | 0.00 |
March | 0.300548E+10 | 0.302161E+10 | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.00 | 0.00 |
April | 0.364071E+10 | 0.216585E+10 | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.00 | 0.00 |
May | 0.501501E+10 | 0.143167E+10 | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.00 | 0.00 |
June | 0.599979E+10 | 0.786992E+09 | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.00 | 0.00 |
July | 0.625172E+10 | 0.463227E+09 | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.00 | 0.00 |
August | 0.694871E+10 | 0.641693E+09 | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.00 | 0.00 |
September | 0.426566E+10 | 0.106913E+10 | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.00 | 0.00 |
October | 0.386690E+10 | 0.201583E+10 | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.00 | 0.00 |
November | 0.965944E+09 | 0.292318E+10 | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.00 | 0.00 |
December | 0.805408E+09 | 0.397540E+10 | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.429367E+11 | 0.267558E+11 | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.805408E+09 | 0.463227E+09 | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.00 | 0.00 |
Maximum of Months | 0.694871E+10 | 0.427585E+10 | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.249492E+11 | -.390974E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130445E+10 | 68.23 | 0.00 | 0.00 |
February | 0.231280E+11 | -.358827E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.116852E+10 | 67.88 | 0.00 | 0.00 |
March | 0.272016E+11 | -.412433E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127101E+10 | 67.09 | 0.00 | 0.00 |
April | 0.216263E+11 | -.355179E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125131E+10 | 67.94 | 0.00 | 0.00 |
May | 0.208631E+11 | -.353107E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129932E+10 | 68.12 | 0.00 | 0.00 |
June | 0.183598E+11 | -.324853E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125153E+10 | 67.91 | 0.00 | 0.00 |
July | 0.144444E+11 | -.292954E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132901E+10 | 69.27 | 0.00 | 0.00 |
August | 0.168679E+11 | -.316073E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129768E+10 | 68.09 | 0.00 | 0.00 |
September | 0.152829E+11 | -.295889E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127245E+10 | 68.74 | 0.00 | 0.00 |
October | 0.179176E+11 | -.325412E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131661E+10 | 68.85 | 0.00 | 0.00 |
November | 0.204374E+11 | -.343790E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.126780E+10 | 68.60 | 0.00 | 0.00 |
December | 0.222084E+11 | -.365550E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130244E+10 | 68.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.243287E+12 | -.413504E+12 | 8760.00 | -.153321E+11 | 68.26 | |||||
Minimum of Months | 0.144444E+11 | -.412433E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.132901E+10 | 67.09 | 0.00 | 0.00 |
Maximum of Months | 0.272016E+11 | -.292954E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.116852E+10 | 69.27 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | ||||||||||
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170672E+10 | 495188.50 | 09-JAN-20:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812827E+09 | 437799.46 | 07-FEB-23:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315883E+09 | 284044.92 | 25-MAR-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70884858.62 | 83814.32 | 17-APR-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113217E+09 | 436655.34 | 01-MAY-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350661E+09 | 440384.28 | 28-OCT-18:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.498635E+09 | 279584.43 | 26-NOV-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461385E+09 | 90270.09 | 23-DEC-17:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433021E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170672E+10 | 495188.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112646E+11 | 507257.71 | 02-JAN-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422777E+09 | 506818.70 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116874E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112646E+11 | 507257.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.605915E+10 | 85677.85 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444717E+10 | 85328.78 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745179E+09 | 85344.85 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143659E+09 | 85319.81 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165940E+10 | 85719.86 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231943E+10 | 85693.48 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153740E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.605915E+10 | 85719.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155210E+09 | 11926.38 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135188E+09 | 11920.42 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290398E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155210E+09 | 11926.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.411807E+09 | 9841.86 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318913E+09 | 9838.80 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37556917.60 | 5509.64 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 227137.83 | 1401.71 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26368584.69 | 5071.42 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112434E+09 | 5364.69 | 28-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907306E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.411807E+09 | 9841.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435937E+09 | 14408.52 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310209E+09 | 14409.92 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18395299.81 | 10550.61 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18682440.51 | 14332.04 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34221913.88 | 14339.62 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817446E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435937E+09 | 14409.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158173E+09 | 8870.08 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58955021.06 | 8866.39 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217129E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158173E+09 | 8870.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.364031E+11 | 135486.45 | 13-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264636E+11 | 153986.90 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.581998E+10 | 131051.96 | 24-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761370E+09 | 134648.41 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64711751.77 | 33140.82 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642791E+10 | 133994.38 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154876E+11 | 135429.63 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914284E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.364031E+11 | 153986.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328249E+11 | 150694.31 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221285E+11 | 150363.92 | 16-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.726873E+10 | 150344.39 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.242652E+10 | 149263.51 | 21-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23096667.19 | 7845.48 | 04-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410188E+09 | 38427.42 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793645E+10 | 150463.59 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180028E+11 | 150431.16 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910213E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328249E+11 | 150694.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238263E+11 | 151580.66 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141248E+11 | 149222.67 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375533E+10 | 149047.83 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.780042E+09 | 145595.09 | 21-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328528E+10 | 152677.81 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945707E+10 | 149799.61 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552288E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238263E+11 | 152677.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290873E+11 | 148835.25 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208501E+11 | 148477.89 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.535925E+10 | 148477.80 | 13-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139511E+10 | 147412.53 | 21-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.287697E+09 | 16595.18 | 28-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728472E+10 | 148555.73 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149710E+11 | 148519.61 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792352E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290873E+11 | 148835.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.798841E+10 | 16096.44 | 02-JAN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697774E+10 | 16764.78 | 06-FEB-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266191E+10 | 14876.09 | 20-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.843810E+09 | 14888.30 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37703173.63 | 14850.89 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105277.06 | 74.43 | 30-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307048E+09 | 15082.09 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283597E+10 | 14931.41 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.549590E+10 | 14933.13 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271486E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.798841E+10 | 16764.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595906E+10 | 16965.85 | 24-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.480983E+10 | 16983.02 | 21-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206639E+10 | 16923.90 | 13-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829540E+09 | 16924.87 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62002949.07 | 13176.70 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16364779.88 | 1385.06 | 30-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298233E+09 | 16794.80 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231400E+10 | 16981.37 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430775E+10 | 16977.56 | 04-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206632E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595906E+10 | 16983.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.575460E+10 | 17319.75 | 02-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442833E+10 | 18851.16 | 06-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195175E+10 | 16973.35 | 20-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.809105E+09 | 16973.43 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47419530.66 | 16944.90 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156481E+09 | 16784.55 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180448E+10 | 17019.82 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365800E+10 | 17027.91 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186102E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.575460E+10 | 18851.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.544572E+10 | 17797.63 | 04-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.441508E+10 | 17788.38 | 27-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183318E+10 | 17794.89 | 13-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.699384E+09 | 17766.82 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65627174.95 | 4081.79 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14495125.57 | 656.60 | 27-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.273587E+09 | 17752.45 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213093E+10 | 17806.06 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375690E+10 | 17798.34 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186349E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.544572E+10 | 17806.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288886E+09 | 251368.52 | 03-JAN-04:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711211E+09 | 251512.16 | 16-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574846E+09 | 251714.90 | 21-MAR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.467324E+09 | 251979.39 | 09-APR-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664028E+09 | 251979.00 | 05-MAY-03:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.484875E+09 | 251968.00 | 04-JUN-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.980480E+09 | 248411.30 | 16-JUL-22:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.382750E+09 | 250407.04 | 20-AUG-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.782404E+09 | 251975.65 | 24-SEP-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174272E+10 | 251977.47 | 01-OCT-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114487E+10 | 251914.82 | 11-NOV-15:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905772E+09 | 251894.00 | 25-DEC-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.913017E+10 | |||||||
Minimum of Months | 0.288886E+09 | 248411.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174272E+10 | 251979.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359941E+11 | 78217.68 | 02-JAN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339362E+11 | 77801.28 | 06-FEB-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154521E+11 | 56317.49 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.433983E+10 | 33674.98 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77727811.15 | 7932.85 | 01-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7288493.09 | 2495.14 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100402E+10 | 29487.31 | 28-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.916867E+10 | 52331.21 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194335E+11 | 55103.23 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119414E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359941E+11 | 78217.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396421E+11 | 859694.12 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327253E+11 | 787326.43 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323861E+11 | 682149.76 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.951815E+10 | 437004.27 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975498E+09 | 192649.73 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.598635E+09 | 93033.10 | 01-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147781E+09 | 42109.60 | 11-JUL-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700144E+09 | 127196.81 | 25-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290195E+09 | 118189.81 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370213E+10 | 383118.28 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187157E+11 | 675802.21 | 22-NOV-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399333E+11 | 689033.84 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179335E+12 | |||||||
Minimum of Months | 0.147781E+09 | 42109.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.399333E+11 | 859694.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.554751E+11 | 87616.88 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.548812E+11 | 85190.53 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364771E+11 | 67543.19 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138555E+11 | 43104.08 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798668E+09 | 24384.06 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100377E+09 | 10623.02 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419041E+10 | 37461.09 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.255763E+11 | 65750.03 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471959E+11 | 68222.58 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238551E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.554751E+11 | 87616.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 14116267.72 | 6294599.66 | 42058.00 | 24-JAN-06:03 | 18487.81 | 0.00 |
February | 0.00 | 0.00 | 1781617.06 | 1781617.06 | 7168.51 | 20-FEB-12:50 | 7168.51 | 0.00 |
March | 0.00 | 0.00 | 0.757143E+09 | 0.756630E+09 | 48580.86 | 27-MAR-16:00 | 48580.86 | 0.01 |
April | 0.00 | 0.00 | 0.658952E+10 | 0.647639E+10 | 82084.04 | 28-APR-03:01 | 48793.00 | 0.07 |
May | 0.00 | 0.00 | 0.195188E+11 | 0.181441E+11 | 125652.60 | 29-MAY-11:38 | 120428.97 | 0.15 |
June | 0.00 | 0.00 | 0.761823E+11 | 0.639890E+11 | 186427.39 | 25-JUN-14:41 | 93941.06 | 0.54 |
July | 0.00 | 0.00 | 0.108800E+12 | 0.877088E+11 | 191044.73 | 23-JUL-15:12 | 100558.65 | 0.61 |
August | 0.00 | 0.00 | 0.106681E+12 | 0.905074E+11 | 169689.77 | 04-AUG-03:01 | 100995.26 | 0.59 |
September | 0.00 | 0.00 | 0.572638E+11 | 0.502838E+11 | 168049.46 | 01-SEP-03:01 | 100305.13 | 0.45 |
October | 0.00 | 0.00 | 0.228056E+11 | 0.189145E+11 | 130351.28 | 06-OCT-05:04 | 55789.77 | 0.23 |
November | 0.00 | 0.00 | 0.326551E+09 | 0.293426E+09 | 87135.81 | 10-NOV-06:02 | 35359.56 | 0.00 |
December | 0.00 | 0.00 | 7664040.20 | 6048446.13 | 17074.86 | 25-DEC-09:01 | 9500.75 | 0.00 |
Annual Sum or Average | 0.398948E+12 | 0.337088E+12 | 0.22 | |||||
Minimum of Months | 0.00 | 0.00 | 1781617.06 | 1781617.06 | 7168.51 | 7168.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108800E+12 | 0.905074E+11 | 191044.73 | 120428.97 | 0.61 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2077.36 | 2077.36 | 1.02 | 04-JAN-06:01 | 1.02 | 0.00 |
February | 0.00 | 0.00 | 423.07 | 423.07 | 0.68 | 03-FEB-05:01 | 0.68 | 0.00 |
March | 0.00 | 0.00 | 0.221884E+10 | 0.188115E+10 | 94693.26 | 27-MAR-13:00 | 61922.44 | 0.02 |
April | 0.00 | 0.00 | 0.153905E+11 | 0.152204E+11 | 109914.97 | 07-APR-13:50 | 109914.97 | 0.14 |
May | 0.00 | 0.00 | 0.485121E+11 | 0.402846E+11 | 141783.04 | 31-MAY-14:00 | 105433.35 | 0.30 |
June | 0.00 | 0.00 | 0.152055E+12 | 0.106820E+12 | 197598.82 | 19-JUN-09:10 | 126703.04 | 0.65 |
July | 0.00 | 0.00 | 0.220324E+12 | 0.146134E+12 | 212503.55 | 20-JUL-15:00 | 117813.59 | 0.76 |
August | 0.00 | 0.00 | 0.218849E+12 | 0.161393E+12 | 225456.55 | 04-AUG-14:00 | 133910.92 | 0.79 |
September | 0.00 | 0.00 | 0.103347E+12 | 0.774277E+11 | 213306.03 | 14-SEP-03:01 | 157821.22 | 0.53 |
October | 0.00 | 0.00 | 0.522698E+11 | 0.362241E+11 | 152689.96 | 06-OCT-03:02 | 68204.90 | 0.31 |
November | 0.00 | 0.00 | 0.236913E+10 | 0.205026E+10 | 48847.98 | 10-NOV-10:00 | 20258.73 | 0.04 |
December | 0.00 | 0.00 | 188.31 | 188.31 | 0.63 | 08-DEC-06:02 | 0.63 | 0.00 |
Annual Sum or Average | 0.815336E+12 | 0.587435E+12 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 188.31 | 188.31 | 0.63 | 0.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220324E+12 | 0.161393E+12 | 225456.55 | 157821.22 | 0.79 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138969E+09 | 0.138969E+09 | 26708.92 | 19-JAN-14:40 | 26708.92 | 0.00 |
February | 0.00 | 0.00 | 63702036.43 | 63702036.43 | 37088.82 | 22-FEB-10:35 | 37088.82 | 0.00 |
March | 0.00 | 0.00 | 0.157964E+11 | 0.136649E+11 | 659038.63 | 27-MAR-13:00 | 438377.36 | 0.02 |
April | 0.00 | 0.00 | 0.109549E+12 | 0.109047E+12 | 951806.43 | 07-APR-13:40 | 951806.43 | 0.10 |
May | 0.00 | 0.00 | 0.416648E+12 | 0.345962E+12 | 1311045.42 | 30-MAY-14:00 | 1311045.42 | 0.29 |
June | 0.00 | 0.00 | 0.123742E+13 | 0.840539E+12 | 2037279.76 | 27-JUN-05:02 | 1419973.79 | 0.57 |
July | 0.00 | 0.00 | 0.155889E+13 | 0.105476E+13 | 2650257.98 | 24-JUL-03:01 | 1502874.05 | 0.62 |
August | 0.00 | 0.00 | 0.148874E+13 | 0.114424E+13 | 2145779.13 | 04-AUG-03:01 | 1507316.99 | 0.62 |
September | 0.00 | 0.00 | 0.883572E+12 | 0.658379E+12 | 2206526.77 | 14-SEP-05:02 | 1416352.77 | 0.51 |
October | 0.00 | 0.00 | 0.432943E+12 | 0.289810E+12 | 1351821.05 | 06-OCT-04:02 | 575770.84 | 0.30 |
November | 0.00 | 0.00 | 0.184076E+11 | 0.160704E+11 | 345681.43 | 10-NOV-10:00 | 144001.10 | 0.04 |
December | 0.00 | 0.00 | 0.298781E+09 | 0.298781E+09 | 76643.38 | 07-DEC-11:40 | 76643.38 | 0.00 |
Annual Sum or Average | 0.616246E+13 | 0.447297E+13 | 0.26 | |||||
Minimum of Months | 0.00 | 0.00 | 63702036.43 | 63702036.43 | 26708.92 | 26708.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155889E+13 | 0.114424E+13 | 2650257.98 | 1507316.99 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4616457.29 | 4616457.29 | 2302.38 | 15-JAN-10:40 | 2302.38 | 0.00 |
February | 0.00 | 0.00 | 29503.08 | 29503.08 | 479.11 | 07-FEB-05:03 | 479.11 | 0.00 |
March | 0.00 | 0.00 | 0.138299E+10 | 0.121927E+10 | 53400.93 | 27-MAR-16:00 | 49243.54 | 0.02 |
April | 0.00 | 0.00 | 0.112690E+11 | 0.112286E+11 | 104672.39 | 07-APR-15:30 | 104672.39 | 0.10 |
May | 0.00 | 0.00 | 0.443378E+11 | 0.370194E+11 | 160318.46 | 31-MAY-14:00 | 121146.35 | 0.29 |
June | 0.00 | 0.00 | 0.141447E+12 | 0.954095E+11 | 218201.29 | 19-JUN-14:00 | 161083.96 | 0.57 |
July | 0.00 | 0.00 | 0.204368E+12 | 0.125876E+12 | 290910.59 | 24-JUL-03:01 | 161059.69 | 0.62 |
August | 0.00 | 0.00 | 0.193844E+12 | 0.134312E+12 | 243930.87 | 04-AUG-14:00 | 147088.81 | 0.61 |
September | 0.00 | 0.00 | 0.952751E+11 | 0.692112E+11 | 209057.46 | 14-SEP-04:02 | 125846.16 | 0.49 |
October | 0.00 | 0.00 | 0.421936E+11 | 0.281582E+11 | 149148.71 | 06-OCT-05:03 | 63962.38 | 0.29 |
November | 0.00 | 0.00 | 0.162109E+10 | 0.142601E+10 | 29326.68 | 03-NOV-14:00 | 29326.68 | 0.03 |
December | 0.00 | 0.00 | 235.58 | 235.58 | 0.34 | 30-DEC-05:01 | 0.34 | 0.00 |
Annual Sum or Average | 0.735744E+12 | 0.503865E+12 | 0.25 | |||||
Minimum of Months | 0.00 | 0.00 | 235.58 | 235.58 | 0.34 | 0.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204368E+12 | 0.134312E+12 | 290910.59 | 161083.96 | 0.62 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.308903E+12 | 0.308847E+12 | 432632.41 | 09-JAN-20:31 | 432632.41 | 0.00 |
February | 0.00 | 0.00 | 0.490143E+12 | 0.489984E+12 | 438202.29 | 07-FEB-23:17 | 438202.29 | 0.00 |
March | 0.00 | 0.00 | 0.781043E+12 | 0.780929E+12 | 436538.33 | 25-MAR-18:07 | 436538.33 | 0.00 |
April | 0.00 | 0.00 | 0.987969E+12 | 0.987953E+12 | 425751.94 | 17-APR-21:25 | 425751.94 | 0.00 |
May | 0.00 | 0.00 | 0.317574E+12 | 0.316198E+12 | 424849.14 | 16-MAY-03:04 | 424849.14 | 0.00 |
June | 0.00 | 0.00 | 0.542031E+12 | 0.536480E+12 | 219690.99 | 15-JUN-12:50 | 209398.45 | 0.00 |
July | 0.00 | 0.00 | 0.800713E+12 | 0.792066E+12 | 309488.17 | 20-JUL-15:00 | 298072.28 | 0.00 |
August | 0.00 | 0.00 | 0.103361E+13 | 0.102793E+13 | 397804.07 | 18-AUG-19:00 | 388933.23 | 0.00 |
September | 0.00 | 0.00 | 0.314418E+12 | 0.310995E+12 | 136660.61 | 01-SEP-00:10 | 135259.05 | 0.00 |
October | 0.00 | 0.00 | 0.557095E+12 | 0.554442E+12 | 442121.60 | 28-OCT-19:00 | 442121.60 | 0.00 |
November | 0.00 | 0.00 | 0.761210E+12 | 0.761088E+12 | 436289.53 | 26-NOV-08:44 | 436289.53 | 0.00 |
December | 0.00 | 0.00 | 0.101956E+13 | 0.101956E+13 | 424087.94 | 09-DEC-19:55 | 424087.94 | 0.00 |
Annual Sum or Average | 0.791427E+13 | 0.788648E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.308903E+12 | 0.308847E+12 | 136660.61 | 135259.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103361E+13 | 0.102793E+13 | 442121.60 | 442121.60 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.420505E+10 | 0.420505E+10 | 2423.64 | 20-JAN-16:20 | 2423.64 | 0.00 |
February | 0.00 | 0.00 | 0.861158E+10 | 0.861158E+10 | 4466.96 | 14-FEB-17:00 | 4466.96 | 0.00 |
March | 0.00 | 0.00 | 0.151530E+11 | 0.151530E+11 | 6395.20 | 29-MAR-17:10 | 6395.20 | 0.00 |
April | 0.00 | 0.00 | 0.194835E+11 | 0.194835E+11 | 7886.74 | 23-APR-18:02 | 7886.74 | 0.00 |
May | 0.00 | 0.00 | 0.557312E+10 | 0.557312E+10 | 2550.97 | 30-MAY-18:00 | 2550.97 | 0.00 |
June | 0.00 | 0.00 | 0.103462E+11 | 0.103462E+11 | 4490.50 | 18-JUN-17:58 | 4490.50 | 0.00 |
July | 0.00 | 0.00 | 0.155902E+11 | 0.155902E+11 | 6405.55 | 12-JUL-18:20 | 6405.55 | 0.00 |
August | 0.00 | 0.00 | 0.189418E+11 | 0.189418E+11 | 7604.30 | 08-AUG-04:12 | 7604.30 | 0.00 |
September | 0.00 | 0.00 | 0.549116E+10 | 0.549116E+10 | 4888.73 | 01-SEP-00:03 | 4888.73 | 0.00 |
October | 0.00 | 0.00 | 0.105543E+11 | 0.105543E+11 | 4522.90 | 04-OCT-16:30 | 4522.90 | 0.00 |
November | 0.00 | 0.00 | 0.146272E+11 | 0.146272E+11 | 6199.66 | 06-NOV-16:10 | 6199.66 | 0.00 |
December | 0.00 | 0.00 | 0.198809E+11 | 0.198809E+11 | 7808.03 | 21-DEC-16:20 | 7808.03 | 0.00 |
Annual Sum or Average | 0.148458E+12 | 0.148458E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.420505E+10 | 0.420505E+10 | 2423.64 | 2423.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198809E+11 | 0.198809E+11 | 7886.74 | 7886.74 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200872E+11 | 0.200872E+11 | 21460.79 | 20-JAN-16:30 | 21460.79 | 0.00 |
February | 0.00 | 0.00 | 0.657562E+11 | 0.657562E+11 | 40717.68 | 22-FEB-17:00 | 40717.68 | 0.00 |
March | 0.00 | 0.00 | 0.131854E+12 | 0.131854E+12 | 60215.44 | 29-MAR-17:20 | 60215.44 | 0.00 |
April | 0.00 | 0.00 | 0.177989E+12 | 0.177989E+12 | 74976.13 | 12-APR-18:00 | 74976.13 | 0.00 |
May | 0.00 | 0.00 | 0.478838E+11 | 0.478838E+11 | 24341.04 | 30-MAY-18:00 | 24341.04 | 0.00 |
June | 0.00 | 0.00 | 0.965156E+11 | 0.965156E+11 | 42935.45 | 18-JUN-17:56 | 42935.45 | 0.00 |
July | 0.00 | 0.00 | 0.148186E+12 | 0.148186E+12 | 61343.79 | 12-JUL-18:20 | 61343.79 | 0.00 |
August | 0.00 | 0.00 | 0.180772E+12 | 0.180772E+12 | 72676.71 | 08-AUG-04:22 | 72676.71 | 0.00 |
September | 0.00 | 0.00 | 0.477526E+11 | 0.477526E+11 | 47412.40 | 01-SEP-00:03 | 47412.40 | 0.00 |
October | 0.00 | 0.00 | 0.930548E+11 | 0.930548E+11 | 42715.00 | 04-OCT-16:30 | 42715.00 | 0.00 |
November | 0.00 | 0.00 | 0.124754E+12 | 0.124754E+12 | 57967.49 | 03-NOV-16:00 | 57967.49 | 0.00 |
December | 0.00 | 0.00 | 0.170928E+12 | 0.170928E+12 | 73992.88 | 08-DEC-16:25 | 73992.88 | 0.00 |
Annual Sum or Average | 0.130553E+13 | 0.130553E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.200872E+11 | 0.200872E+11 | 21460.79 | 21460.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180772E+12 | 0.180772E+12 | 74976.13 | 74976.13 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.931420E+09 | 0.931420E+09 | 2049.88 | 20-JAN-16:40 | 2049.88 | 0.00 |
February | 0.00 | 0.00 | 0.474589E+10 | 0.474589E+10 | 3973.13 | 02-FEB-16:50 | 3973.13 | 0.00 |
March | 0.00 | 0.00 | 0.118363E+11 | 0.118363E+11 | 6022.70 | 29-MAR-17:10 | 6022.70 | 0.00 |
April | 0.00 | 0.00 | 0.169896E+11 | 0.169896E+11 | 7626.32 | 12-APR-17:50 | 7626.32 | 0.00 |
May | 0.00 | 0.00 | 0.445842E+10 | 0.445842E+10 | 2533.47 | 30-MAY-18:00 | 2533.47 | 0.00 |
June | 0.00 | 0.00 | 0.964692E+10 | 0.964692E+10 | 4546.37 | 18-JUN-17:54 | 4546.37 | 0.00 |
July | 0.00 | 0.00 | 0.149313E+11 | 0.149313E+11 | 6237.32 | 12-JUL-18:20 | 6237.32 | 0.00 |
August | 0.00 | 0.00 | 0.183767E+11 | 0.183767E+11 | 7296.08 | 20-AUG-01:12 | 7296.08 | 0.00 |
September | 0.00 | 0.00 | 0.451890E+10 | 0.451890E+10 | 4017.49 | 01-SEP-00:03 | 4017.49 | 0.00 |
October | 0.00 | 0.00 | 0.848528E+10 | 0.848528E+10 | 4343.34 | 04-OCT-16:30 | 4343.34 | 0.00 |
November | 0.00 | 0.00 | 0.108853E+11 | 0.108853E+11 | 5786.18 | 03-NOV-16:00 | 5786.18 | 0.00 |
December | 0.00 | 0.00 | 0.150163E+11 | 0.150163E+11 | 7284.61 | 08-DEC-16:10 | 7284.61 | 0.00 |
Annual Sum or Average | 0.120822E+12 | 0.120822E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.931420E+09 | 0.931420E+09 | 2049.88 | 2049.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.183767E+11 | 0.183767E+11 | 7626.32 | 7626.32 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6863.29 | 37443.37 | 01-JAN-08:20 | 13594.07 | 65056.07 | 27-JAN-12:33 |
February | 6471.82 | 37364.45 | 26-FEB-08:30 | 13908.43 | 63147.46 | 28-FEB-12:20 |
March | 5283.18 | 37480.25 | 26-MAR-07:23 | 14617.35 | 65293.01 | 13-MAR-12:23 |
April | 6419.70 | 37727.20 | 30-APR-07:20 | 12703.14 | 53912.38 | 13-APR-11:30 |
May | 6420.38 | 37959.46 | 29-MAY-06:45 | 12167.24 | 48327.92 | 01-MAY-11:30 |
June | 5946.81 | 38145.02 | 25-JUN-06:43 | 11445.08 | 44832.47 | 01-JUN-11:30 |
July | 7747.06 | 38277.19 | 30-JUL-06:40 | 9565.28 | 41931.26 | 03-JUL-11:30 |
August | 6064.94 | 38285.20 | 13-AUG-06:34 | 10642.52 | 40971.19 | 31-AUG-11:20 |
September | 7001.14 | 38246.54 | 03-SEP-06:42 | 10128.27 | 42831.47 | 29-SEP-11:40 |
October | 7371.29 | 38110.10 | 01-OCT-07:00 | 10952.46 | 46138.25 | 31-OCT-11:40 |
November | 7298.60 | 37850.16 | 05-NOV-07:10 | 12236.09 | 56660.58 | 30-NOV-12:35 |
December | 7027.63 | 37628.37 | 03-DEC-08:15 | 12590.87 | 60892.61 | 11-DEC-12:03 |
Annual Sum or Average | 6661.12 | 12035.17 | ||||
Minimum of Months | 5283.18 | 37364.45 | 9565.28 | 40971.19 | ||
Maximum of Months | 7747.06 | 38285.20 | 14617.35 | 65293.01 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 109669.74 | 2195272.22 | 02-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 94834.36 | 1761532.69 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 43019.70 | 1072211.99 | 23-MAR-06:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13978.32 | 1106690.05 | 22-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 1174.94 | 676122.80 | 29-MAY-02:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 428.33 | 470807.56 | 04-JUN-16:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 425.26 | 331261.15 | 16-JUL-14:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 345.01 | 576882.89 | 27-AUG-11:58 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 453.02 | 439716.09 | 03-SEP-11:58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4726.45 | 429785.48 | 01-OCT-19:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 34445.40 | 1205171.77 | 24-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 68516.41 | 1361304.33 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 30681.42 | ||||
Minimum of Months | 0.00 | 0.00 | 345.01 | 331261.15 | ||
Maximum of Months | 0.00 | 0.00 | 109669.74 | 2195272.22 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 578.42 | 92775.01 | 24-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 437.61 | 37191.46 | 22-FEB-10:35 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15846.47 | 1538562.55 | 27-MAR-13:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 108803.79 | 1733861.40 | 07-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 361963.12 | 1830649.45 | 30-MAY-10:30 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 844180.61 | 2872553.07 | 27-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 976323.07 | 2863335.20 | 24-JUL-03:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 979314.19 | 2630199.59 | 02-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 653021.99 | 3096011.70 | 14-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 326273.75 | 1937486.58 | 06-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 19518.92 | 849829.62 | 10-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 467.53 | 93643.58 | 07-DEC-11:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 359621.30 | 0.00 | ||||
Minimum of Months | 437.61 | 37191.46 | 0.00 | 0.00 | ||
Maximum of Months | 979314.19 | 3096011.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22.04 | 52073.42 | 24-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 15.71 | 15572.80 | 22-FEB-10:35 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8522.95 | 1012687.19 | 27-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 64017.43 | 1532211.23 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 226569.37 | 1809128.51 | 30-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 700846.25 | 3208342.39 | 27-JUN-05:01 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 855097.35 | 3602100.66 | 24-JUL-03:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 833428.47 | 3201946.75 | 01-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 500966.93 | 3458665.85 | 14-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 236834.88 | 2131211.96 | 06-OCT-05:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9576.83 | 472739.30 | 10-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102.71 | 59345.79 | 25-DEC-08:11 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 288330.34 | 0.00 | ||||
Minimum of Months | 15.71 | 15572.80 | 0.00 | 0.00 | ||
Maximum of Months | 855097.35 | 3602100.66 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 155597.34 | 537440.79 | 28-JAN-01:01 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 292200.17 | 570515.20 | 26-FEB-07:51 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 439208.08 | 855845.62 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 633080.45 | 1306010.14 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 240166.60 | 861405.56 | 30-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 631192.50 | 1456558.32 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1023130.34 | 1531836.16 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1211264.46 | 1700928.06 | 24-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 364815.86 | 929874.62 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 372452.85 | 811246.32 | 04-OCT-13:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 440178.14 | 624897.09 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 568766.77 | 616872.44 | 29-DEC-22:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 533117.24 | 0.00 | ||||
Minimum of Months | 155597.34 | 537440.79 | 0.00 | 0.00 | ||
Maximum of Months | 1211264.46 | 1700928.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 26.87 | 13967.88 | 20-JAN-06:50 | 835.08 | 126456.40 | 16-JAN-05:30 |
February | 28.66 | 24888.62 | 17-FEB-06:30 | 687.79 | 129704.74 | 13-FEB-04:13 |
March | 11007.61 | 1334579.28 | 27-MAR-13:40 | 945.66 | 121161.51 | 16-MAR-12:10 |
April | 80450.96 | 2235651.16 | 07-APR-14:30 | 725.92 | 134647.51 | 05-APR-05:01 |
May | 319018.47 | 4448876.20 | 31-MAY-13:10 | 547.26 | 74799.46 | 11-MAY-07:50 |
June | 1431239.81 | 7048722.03 | 15-JUN-12:20 | 84.83 | 69959.36 | 02-JUN-06:50 |
July | 2386729.46 | 7951321.56 | 20-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2072301.58 | 8343786.67 | 02-AUG-14:50 | 21.89 | 24562.16 | 20-AUG-03:00 |
September | 954407.01 | 6575631.65 | 07-SEP-14:10 | 77.38 | 54785.00 | 23-SEP-10:00 |
October | 338506.71 | 4048511.70 | 25-OCT-09:30 | 631.06 | 104685.28 | 08-OCT-13:51 |
November | 14668.25 | 610323.38 | 10-NOV-10:10 | 858.88 | 115293.64 | 22-NOV-06:40 |
December | 26.26 | 45821.00 | 08-DEC-08:30 | 549.28 | 117209.29 | 30-DEC-06:30 |
Annual Sum or Average | 639397.01 | 496.18 | ||||
Minimum of Months | 26.26 | 13967.88 | 0.00 | 0.00 | ||
Maximum of Months | 2386729.46 | 8343786.67 | 945.66 | 134647.51 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161148E+11 | 0.86 | 10682.72 | 01-JAN-05:11 | 1.52 |
February | 0.151588E+11 | 0.89 | 10682.72 | 01-FEB-04:40 | 1.52 |
March | 0.177614E+11 | 0.94 | 10682.72 | 01-MAR-04:51 | 1.52 |
April | 0.166404E+11 | 0.91 | 10682.72 | 01-APR-03:01 | 1.52 |
May | 0.179574E+11 | 0.95 | 10682.72 | 01-MAY-00:01 | 1.51 |
June | 0.178878E+11 | 0.97 | 10682.72 | 01-JUN-03:01 | 1.51 |
July | 0.181424E+11 | 0.95 | 10682.72 | 01-JUL-03:01 | 1.50 |
August | 0.191935E+11 | 1.01 | 10682.72 | 01-AUG-03:01 | 1.50 |
September | 0.182148E+11 | 0.99 | 10682.72 | 01-SEP-03:01 | 1.50 |
October | 0.187164E+11 | 0.99 | 10682.72 | 01-OCT-14:11 | 1.51 |
November | 0.177173E+11 | 0.97 | 10682.72 | 01-NOV-03:01 | 1.52 |
December | 0.173669E+11 | 0.92 | 10682.72 | 01-DEC-04:01 | 1.51 |
Annual Sum or Average | 0.210872E+12 | 0.94 | |||
Minimum of Months | 0.151588E+11 | 0.86 | 10682.72 | 1.50 | |
Maximum of Months | 0.191935E+11 | 1.01 | 10682.72 | 1.52 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.466100E+10 | 0.33 | 13790.88 | 14-JAN-06:01 | 1.39 |
February | 0.483520E+10 | 0.36 | 12657.26 | 09-FEB-06:01 | 1.32 |
March | 0.743926E+10 | 0.44 | 13470.63 | 28-MAR-03:01 | 1.36 |
April | 0.762810E+10 | 0.47 | 13972.41 | 05-APR-03:01 | 1.40 |
May | 0.621936E+10 | 0.41 | 22063.09 | 30-MAY-03:01 | 1.85 |
June | 0.681006E+10 | 0.46 | 22063.09 | 05-JUN-05:03 | 1.85 |
July | 0.763691E+10 | 0.50 | 22063.09 | 17-JUL-05:02 | 1.85 |
August | 0.924616E+10 | 0.57 | 21421.60 | 02-AUG-05:01 | 1.81 |
September | 0.606621E+10 | 0.41 | 22063.09 | 06-SEP-03:01 | 1.85 |
October | 0.719825E+10 | 0.43 | 20671.47 | 23-OCT-05:03 | 1.78 |
November | 0.676414E+10 | 0.41 | 13972.41 | 04-NOV-03:01 | 1.39 |
December | 0.671901E+10 | 0.40 | 11890.04 | 26-DEC-04:01 | 1.26 |
Annual Sum or Average | 0.812237E+11 | 0.44 | |||
Minimum of Months | 0.466100E+10 | 0.33 | 11890.04 | 1.26 | |
Maximum of Months | 0.924616E+10 | 0.57 | 22063.09 | 1.85 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355366E+11 | 0.33 | 132738.46 | 13-JAN-06:01 | 1.41 |
February | 0.338140E+11 | 0.33 | 166308.02 | 22-FEB-16:30 | 1.63 |
March | 0.472380E+11 | 0.36 | 166308.02 | 07-MAR-17:05 | 1.63 |
April | 0.444805E+11 | 0.35 | 132738.46 | 21-APR-05:01 | 1.41 |
May | 0.496111E+11 | 0.38 | 193164.44 | 30-MAY-05:03 | 1.78 |
June | 0.541108E+11 | 0.41 | 207171.99 | 17-JUN-05:01 | 1.86 |
July | 0.576295E+11 | 0.41 | 207171.99 | 08-JUL-05:01 | 1.86 |
August | 0.677118E+11 | 0.45 | 207171.99 | 01-AUG-05:01 | 1.86 |
September | 0.501361E+11 | 0.38 | 207171.99 | 02-SEP-05:01 | 1.86 |
October | 0.508104E+11 | 0.37 | 166308.02 | 27-OCT-16:50 | 1.63 |
November | 0.403445E+11 | 0.33 | 132738.46 | 15-NOV-06:01 | 1.41 |
December | 0.384656E+11 | 0.32 | 132738.46 | 21-DEC-06:01 | 1.42 |
Annual Sum or Average | 0.569889E+12 | 0.37 | |||
Minimum of Months | 0.338140E+11 | 0.32 | 132738.46 | 1.41 | |
Maximum of Months | 0.677118E+11 | 0.45 | 207171.99 | 1.86 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386222E+10 | 0.38 | 4589.95 | 02-JAN-04:01 | 0.74 |
February | 0.339992E+10 | 0.36 | 4589.95 | 01-FEB-06:01 | 0.74 |
March | 0.368817E+10 | 0.33 | 7049.03 | 29-MAR-15:10 | 0.93 |
April | 0.379409E+10 | 0.32 | 9761.63 | 07-APR-05:01 | 1.12 |
May | 0.476012E+10 | 0.36 | 21730.14 | 31-MAY-05:01 | 1.85 |
June | 0.591992E+10 | 0.41 | 21730.14 | 15-JUN-05:01 | 1.85 |
July | 0.661448E+10 | 0.42 | 21730.14 | 01-JUL-05:01 | 1.85 |
August | 0.752525E+10 | 0.46 | 21730.14 | 02-AUG-03:01 | 1.85 |
September | 0.493248E+10 | 0.36 | 21730.14 | 01-SEP-05:01 | 1.85 |
October | 0.419893E+10 | 0.32 | 10274.27 | 04-OCT-05:01 | 1.15 |
November | 0.323887E+10 | 0.31 | 4589.95 | 06-NOV-06:01 | 0.74 |
December | 0.334497E+10 | 0.33 | 4589.95 | 02-DEC-06:01 | 0.74 |
Annual Sum or Average | 0.552794E+11 | 0.36 | |||
Minimum of Months | 0.323887E+10 | 0.31 | 4589.95 | 0.74 | |
Maximum of Months | 0.752525E+10 | 0.46 | 21730.14 | 1.85 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.944523E+11 | 1.35 | 35264.46 | 01-JAN-00:01 | 1.35 |
February | 0.853118E+11 | 1.35 | 35264.46 | 01-FEB-00:10 | 1.35 |
March | 0.944523E+11 | 1.35 | 35264.46 | 01-MAR-00:20 | 1.35 |
April | 0.914055E+11 | 1.35 | 35264.46 | 01-APR-00:10 | 1.35 |
May | 0.944523E+11 | 1.35 | 35264.46 | 01-MAY-00:01 | 1.35 |
June | 0.914055E+11 | 1.35 | 35264.46 | 01-JUN-00:10 | 1.35 |
July | 0.944523E+11 | 1.35 | 35264.46 | 01-JUL-00:10 | 1.35 |
August | 0.944523E+11 | 1.35 | 35264.46 | 01-AUG-00:05 | 1.35 |
September | 0.914055E+11 | 1.35 | 35264.46 | 01-SEP-00:03 | 1.35 |
October | 0.944523E+11 | 1.35 | 35264.46 | 01-OCT-00:10 | 1.35 |
November | 0.914055E+11 | 1.35 | 35264.46 | 01-NOV-00:20 | 1.35 |
December | 0.944523E+11 | 1.35 | 35264.46 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111210E+13 | 1.35 | |||
Minimum of Months | 0.853118E+11 | 1.35 | 35264.46 | 1.35 | |
Maximum of Months | 0.944523E+11 | 1.35 | 35264.46 | 1.35 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140940E+10 | 0.93 | 526.21 | 01-JAN-00:01 | 0.93 |
February | 0.127301E+10 | 0.93 | 526.21 | 01-FEB-00:10 | 0.93 |
March | 0.140940E+10 | 0.93 | 526.21 | 01-MAR-00:10 | 0.93 |
April | 0.136393E+10 | 0.93 | 526.21 | 01-APR-00:10 | 0.93 |
May | 0.140940E+10 | 0.93 | 526.21 | 01-MAY-00:01 | 0.93 |
June | 0.136393E+10 | 0.93 | 526.21 | 01-JUN-00:10 | 0.93 |
July | 0.140940E+10 | 0.93 | 526.21 | 01-JUL-00:10 | 0.93 |
August | 0.140940E+10 | 0.93 | 526.21 | 01-AUG-00:05 | 0.93 |
September | 0.136393E+10 | 0.93 | 526.21 | 01-SEP-00:03 | 0.93 |
October | 0.140940E+10 | 0.93 | 526.21 | 01-OCT-00:10 | 0.93 |
November | 0.136393E+10 | 0.93 | 526.21 | 01-NOV-00:10 | 0.93 |
December | 0.140940E+10 | 0.93 | 526.21 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.165945E+11 | 0.93 | |||
Minimum of Months | 0.127301E+10 | 0.93 | 526.21 | 0.93 | |
Maximum of Months | 0.140940E+10 | 0.93 | 526.21 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134370E+11 | 0.93 | 5016.81 | 01-JAN-00:01 | 0.93 |
February | 0.121367E+11 | 0.93 | 5016.81 | 01-FEB-00:10 | 0.93 |
March | 0.134370E+11 | 0.93 | 5016.81 | 01-MAR-00:10 | 0.93 |
April | 0.130036E+11 | 0.93 | 5016.81 | 01-APR-00:10 | 0.93 |
May | 0.134370E+11 | 0.93 | 5016.81 | 01-MAY-00:01 | 0.93 |
June | 0.130036E+11 | 0.93 | 5016.81 | 01-JUN-00:10 | 0.93 |
July | 0.134370E+11 | 0.93 | 5016.81 | 01-JUL-00:10 | 0.93 |
August | 0.134370E+11 | 0.93 | 5016.81 | 01-AUG-00:05 | 0.93 |
September | 0.130036E+11 | 0.93 | 5016.81 | 01-SEP-00:03 | 0.93 |
October | 0.134370E+11 | 0.93 | 5016.81 | 01-OCT-00:20 | 0.93 |
November | 0.130036E+11 | 0.93 | 5016.81 | 01-NOV-00:10 | 0.93 |
December | 0.134370E+11 | 0.93 | 5016.81 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.158210E+12 | 0.93 | |||
Minimum of Months | 0.121367E+11 | 0.93 | 5016.81 | 0.93 | |
Maximum of Months | 0.134370E+11 | 0.93 | 5016.81 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137324E+10 | 0.93 | 512.71 | 01-JAN-00:01 | 0.93 |
February | 0.124035E+10 | 0.93 | 512.71 | 01-FEB-00:10 | 0.93 |
March | 0.137324E+10 | 0.93 | 512.71 | 01-MAR-00:10 | 0.93 |
April | 0.132895E+10 | 0.93 | 512.71 | 01-APR-00:10 | 0.93 |
May | 0.137324E+10 | 0.93 | 512.71 | 01-MAY-00:01 | 0.93 |
June | 0.132895E+10 | 0.93 | 512.71 | 01-JUN-00:20 | 0.93 |
July | 0.137324E+10 | 0.93 | 512.71 | 01-JUL-00:10 | 0.93 |
August | 0.137324E+10 | 0.93 | 512.71 | 01-AUG-00:05 | 0.93 |
September | 0.132895E+10 | 0.93 | 512.71 | 01-SEP-00:03 | 0.93 |
October | 0.137324E+10 | 0.93 | 512.71 | 01-OCT-00:10 | 0.93 |
November | 0.132895E+10 | 0.93 | 512.71 | 01-NOV-00:10 | 0.93 |
December | 0.137324E+10 | 0.93 | 512.71 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.161688E+11 | 0.93 | |||
Minimum of Months | 0.124035E+10 | 0.93 | 512.71 | 0.93 | |
Maximum of Months | 0.137324E+10 | 0.93 | 512.71 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.479403E+10 | 0.431463E+10 | 15329.45 | 02-JAN-07:10 | 13796.51 | 13796.51 | 69.39 | 41.55 |
February | 0.313408E+10 | 0.282067E+10 | 14380.64 | 06-FEB-07:10 | 12942.58 | 12942.58 | 69.29 | 33.07 |
March | 0.126635E+10 | 0.113971E+10 | 10567.68 | 23-MAR-06:10 | 9510.91 | 9510.91 | 67.59 | 17.76 |
April | 0.285315E+09 | 0.256783E+09 | 7733.74 | 21-APR-05:01 | 6960.37 | 6960.37 | 59.67 | 11.48 |
May | 58034240.78 | 52230816.70 | 4878.06 | 29-MAY-23:00 | 4390.26 | 4390.26 | 72.36 | 6.52 |
June | 15163002.02 | 13646701.82 | 4875.27 | 25-JUN-21:57 | 4387.74 | 4387.74 | 71.25 | 6.52 |
July | 20877557.53 | 18789801.77 | 4879.82 | 09-JUL-20:40 | 4391.84 | 4391.84 | 73.06 | 6.52 |
August | 13024957.37 | 11722461.63 | 4880.00 | 13-AUG-14:10 | 4392.00 | 4392.00 | 73.13 | 6.52 |
September | 18034629.79 | 16231166.81 | 4877.78 | 17-SEP-20:50 | 4390.00 | 4390.00 | 72.25 | 6.52 |
October | 0.272056E+09 | 0.244850E+09 | 5842.02 | 09-OCT-08:10 | 5257.82 | 5257.82 | 74.19 | 8.04 |
November | 0.102766E+10 | 0.924898E+09 | 10821.67 | 24-NOV-07:10 | 9739.50 | 9739.50 | 66.41 | 18.46 |
December | 0.156882E+10 | 0.141194E+10 | 10770.62 | 22-DEC-07:10 | 9693.55 | 9693.55 | 64.28 | 18.34 |
Annual Sum or Average | 0.124734E+11 | 0.112261E+11 | ||||||
Minimum of Months | 13024957.37 | 11722461.63 | 4875.27 | 4387.74 | 4387.74 | 59.67 | 6.52 | |
Maximum of Months | 0.479403E+10 | 0.431463E+10 | 15329.45 | 13796.51 | 13796.51 | 74.19 | 41.55 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 5185086.97 | 4666578.27 | 2978.68 | 24-JAN-06:03 | 2680.81 | 2680.81 | 6.81 | 4.01 |
February | 1941480.67 | 1747332.60 | 741.65 | 22-FEB-10:35 | 667.48 | 667.48 | 6.83 | 0.96 |
March | 0.471045E+09 | 0.423940E+09 | 16548.42 | 27-MAR-13:00 | 14893.57 | 14893.57 | 8.18 | 30.51 |
April | 0.336550E+10 | 0.302895E+10 | 22824.27 | 07-APR-14:00 | 20541.85 | 20541.85 | 7.14 | 60.53 |
May | 0.108703E+11 | 0.978330E+10 | 23241.80 | 30-MAY-11:00 | 20917.62 | 20917.62 | 7.13 | 64.60 |
June | 0.266957E+11 | 0.240261E+11 | 26133.63 | 24-JUN-05:02 | 23520.26 | 23520.26 | 7.49 | 100.66 |
July | 0.312310E+11 | 0.281079E+11 | 26986.98 | 20-JUL-05:02 | 24288.29 | 24288.29 | 7.47 | 107.23 |
August | 0.314179E+11 | 0.282761E+11 | 26086.02 | 02-AUG-05:02 | 23477.41 | 23477.41 | 7.73 | 100.23 |
September | 0.205400E+11 | 0.184860E+11 | 27255.97 | 14-SEP-05:02 | 24530.37 | 24530.37 | 7.39 | 108.99 |
October | 0.104772E+11 | 0.942944E+10 | 22958.07 | 06-OCT-05:01 | 20662.26 | 20662.26 | 7.84 | 61.76 |
November | 0.588473E+09 | 0.529626E+09 | 10434.09 | 10-NOV-06:02 | 9390.68 | 9390.68 | 6.97 | 16.19 |
December | 7113212.22 | 6401890.99 | 1706.42 | 04-DEC-16:30 | 1535.78 | 1535.78 | 6.94 | 2.25 |
Annual Sum or Average | 0.135671E+12 | 0.122104E+12 | ||||||
Minimum of Months | 1941480.67 | 1747332.60 | 741.65 | 667.48 | 667.48 | 6.81 | 0.96 | |
Maximum of Months | 0.314179E+11 | 0.282761E+11 | 27255.97 | 24530.37 | 24530.37 | 8.18 | 108.99 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:01 | 16.86 | 16.86 | 79.33 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 62.26 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 66.32 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 64.48 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 77.78 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 62.19 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 63.11 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 62.84 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 63.72 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 75.81 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 62.55 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 61.46 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 61.46 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 79.33 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.800405E+09 | 0.720364E+09 | 10252.99 | 02-JAN-05:10 | 9227.70 | 9227.70 | 6.73 | 128.41 |
February | 0.548477E+09 | 0.493629E+09 | 10252.99 | 01-FEB-09:20 | 9227.70 | 9227.70 | 6.74 | 128.41 |
March | 0.174432E+10 | 0.156989E+10 | 10252.99 | 01-MAR-07:05 | 9227.70 | 9227.70 | 6.73 | 128.41 |
April | 0.575398E+10 | 0.517858E+10 | 10252.99 | 01-APR-04:01 | 9227.70 | 9227.70 | 6.77 | 128.41 |
May | 0.141008E+11 | 0.126908E+11 | 10252.99 | 01-MAY-04:33 | 9227.70 | 9227.70 | 6.94 | 128.41 |
June | 0.195242E+11 | 0.175717E+11 | 10252.99 | 01-JUN-03:01 | 9227.70 | 9227.70 | 8.91 | 128.41 |
July | 0.226899E+11 | 0.204209E+11 | 10252.99 | 01-JUL-03:01 | 9227.70 | 9227.70 | 9.22 | 128.41 |
August | 0.236413E+11 | 0.212771E+11 | 10252.99 | 01-AUG-00:20 | 9227.70 | 9227.70 | 6.94 | 128.41 |
September | 0.166088E+11 | 0.149479E+11 | 10252.99 | 01-SEP-00:03 | 9227.70 | 9227.70 | 6.95 | 128.41 |
October | 0.105908E+11 | 0.953175E+10 | 10252.99 | 01-OCT-14:11 | 9227.70 | 9227.70 | 6.84 | 128.41 |
November | 0.219168E+10 | 0.197251E+10 | 10252.99 | 01-NOV-03:01 | 9227.70 | 9227.70 | 6.73 | 128.41 |
December | 0.398483E+09 | 0.358634E+09 | 10252.99 | 01-DEC-11:10 | 9227.70 | 9227.70 | 6.76 | 128.41 |
Annual Sum or Average | 0.118593E+12 | 0.106734E+12 | ||||||
Minimum of Months | 0.398483E+09 | 0.358634E+09 | 10252.99 | 9227.70 | 9227.70 | 6.73 | 128.41 | |
Maximum of Months | 0.236413E+11 | 0.212771E+11 | 10252.99 | 9227.70 | 9227.70 | 9.22 | 128.41 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-JAN-00:01 | 3013.27 | 3013.27 | 21.36 | 13.98 |
February | 0.809967E+10 | 0.728971E+10 | 3348.08 | 01-FEB-00:10 | 3013.27 | 3013.27 | 24.01 | 13.98 |
March | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-MAR-00:10 | 3013.27 | 3013.27 | 26.78 | 13.98 |
April | 0.867822E+10 | 0.781040E+10 | 3348.08 | 01-APR-00:10 | 3013.27 | 3013.27 | 29.67 | 13.98 |
May | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-MAY-00:01 | 3013.27 | 3013.27 | 27.30 | 13.98 |
June | 0.867822E+10 | 0.781040E+10 | 3348.08 | 01-JUN-00:10 | 3013.27 | 3013.27 | 26.56 | 13.98 |
July | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-JUL-00:10 | 3013.27 | 3013.27 | 32.27 | 13.98 |
August | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-AUG-00:05 | 3013.27 | 3013.27 | 40.23 | 13.98 |
September | 0.867822E+10 | 0.781040E+10 | 3348.08 | 01-SEP-00:03 | 3013.27 | 3013.27 | 35.97 | 13.98 |
October | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-OCT-00:10 | 3013.27 | 3013.27 | 24.30 | 13.98 |
November | 0.867822E+10 | 0.781040E+10 | 3348.08 | 01-NOV-00:10 | 3013.27 | 3013.27 | 26.95 | 13.98 |
December | 0.896750E+10 | 0.807075E+10 | 3348.08 | 01-DEC-00:10 | 3013.27 | 3013.27 | 29.62 | 13.98 |
Annual Sum or Average | 0.105585E+12 | 0.950265E+11 | ||||||
Minimum of Months | 0.809967E+10 | 0.728971E+10 | 3348.08 | 3013.27 | 3013.27 | 21.36 | 13.98 | |
Maximum of Months | 0.896750E+10 | 0.807075E+10 | 3348.08 | 3013.27 | 3013.27 | 40.23 | 13.98 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.150128E+10 | 0.135115E+10 | 19232.86 | 20-JAN-06:50 | 17309.57 | 17309.57 | 21.14 | 75.53 |
February | 0.102875E+10 | 0.925871E+09 | 19233.34 | 17-FEB-06:30 | 17310.00 | 17310.00 | 21.18 | 75.53 |
March | 0.330774E+10 | 0.297697E+10 | 38523.26 | 27-MAR-13:40 | 34670.94 | 34670.94 | 23.21 | 151.06 |
April | 0.108945E+11 | 0.980506E+10 | 38562.74 | 07-APR-14:30 | 34706.47 | 34706.47 | 24.64 | 151.06 |
May | 0.278090E+11 | 0.250281E+11 | 38674.60 | 31-MAY-13:10 | 34807.14 | 34807.14 | 28.15 | 151.06 |
June | 0.472752E+11 | 0.425477E+11 | 38696.10 | 07-JUN-09:30 | 34826.49 | 34826.49 | 29.00 | 151.06 |
July | 0.587603E+11 | 0.528843E+11 | 38696.10 | 03-JUL-09:30 | 34826.49 | 34826.49 | 28.81 | 151.06 |
August | 0.591302E+11 | 0.532172E+11 | 38696.10 | 01-AUG-07:40 | 34826.49 | 34826.49 | 29.14 | 151.06 |
September | 0.378656E+11 | 0.340791E+11 | 38696.10 | 05-SEP-14:00 | 34826.49 | 34826.49 | 28.88 | 151.06 |
October | 0.218670E+11 | 0.196803E+11 | 38654.02 | 25-OCT-09:30 | 34788.62 | 34788.62 | 27.51 | 151.06 |
November | 0.411265E+10 | 0.370139E+10 | 19259.00 | 10-NOV-10:10 | 17333.10 | 17333.10 | 23.03 | 75.53 |
December | 0.744515E+09 | 0.670064E+09 | 19234.25 | 08-DEC-08:30 | 17310.83 | 17310.83 | 21.25 | 75.53 |
Annual Sum or Average | 0.274297E+12 | 0.246867E+12 | ||||||
Minimum of Months | 0.744515E+09 | 0.670064E+09 | 19232.86 | 17309.57 | 17309.57 | 21.14 | 75.53 | |
Maximum of Months | 0.591302E+11 | 0.532172E+11 | 38696.10 | 34826.49 | 34826.49 | 29.14 | 151.06 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6863.29 | 37443.37 | 01-JAN-08:20 | 80.26 | 82.22 | 13594.07 | 65056.07 | 27-JAN-12:33 |
February | 6471.82 | 37364.45 | 26-FEB-08:30 | 80.22 | 82.22 | 13908.43 | 63147.46 | 28-FEB-12:20 |
March | 5283.18 | 37480.25 | 26-MAR-07:23 | 80.28 | 82.22 | 14617.35 | 65293.01 | 13-MAR-12:23 |
April | 6419.70 | 37727.20 | 30-APR-07:20 | 80.42 | 82.22 | 12703.14 | 53912.38 | 13-APR-11:30 |
May | 6420.38 | 37959.46 | 29-MAY-06:45 | 80.54 | 82.22 | 12167.24 | 48327.92 | 01-MAY-11:30 |
June | 5946.81 | 38145.02 | 25-JUN-06:43 | 80.64 | 82.22 | 11445.08 | 44832.47 | 01-JUN-11:30 |
July | 7747.06 | 38277.19 | 30-JUL-06:40 | 80.71 | 82.22 | 9565.28 | 41931.26 | 03-JUL-11:30 |
August | 6064.94 | 38285.20 | 13-AUG-06:34 | 80.72 | 82.22 | 10642.52 | 40971.19 | 31-AUG-11:20 |
September | 7001.14 | 38246.54 | 03-SEP-06:42 | 80.70 | 82.22 | 10128.27 | 42831.47 | 29-SEP-11:40 |
October | 7371.29 | 38110.10 | 01-OCT-07:00 | 80.62 | 82.22 | 10952.46 | 46138.25 | 31-OCT-11:40 |
November | 7298.60 | 37850.16 | 05-NOV-07:10 | 80.48 | 82.22 | 12236.09 | 56660.58 | 30-NOV-12:35 |
December | 7027.63 | 37628.37 | 03-DEC-08:15 | 80.36 | 82.22 | 12590.87 | 60892.61 | 11-DEC-12:03 |
Annual Sum or Average | 6661.12 | 12035.17 | ||||||
Minimum of Months | 5283.18 | 37364.45 | 80.22 | 82.22 | 9565.28 | 40971.19 | ||
Maximum of Months | 7747.06 | 38285.20 | 80.72 | 82.22 | 14617.35 | 65293.01 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 69.98 | 69.98 | 109669.74 | 2195272.22 | 02-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 64.76 | 64.76 | 94834.36 | 1761532.69 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 64.12 | 64.12 | 43019.70 | 1072211.99 | 23-MAR-06:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 66.26 | 66.26 | 13978.32 | 1106690.05 | 22-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 51.72 | 51.72 | 1174.94 | 676122.80 | 29-MAY-02:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 69.24 | 69.24 | 428.33 | 470807.56 | 04-JUN-16:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 71.44 | 71.44 | 425.26 | 331261.15 | 16-JUL-14:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 73.05 | 73.05 | 345.01 | 576882.89 | 27-AUG-11:58 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 65.68 | 65.68 | 453.02 | 439716.09 | 03-SEP-11:58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 64.76 | 64.76 | 4726.45 | 429785.48 | 01-OCT-19:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 72.25 | 72.25 | 34445.40 | 1205171.77 | 24-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.07 | 56.07 | 68516.41 | 1361304.33 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 30681.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.72 | 51.72 | 345.01 | 331261.15 | ||
Maximum of Months | 0.00 | 0.00 | 73.05 | 73.05 | 109669.74 | 2195272.22 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 578.42 | 92775.01 | 24-JAN-06:03 | 6.87 | 6.79 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 437.61 | 37191.46 | 22-FEB-10:35 | 6.77 | 6.73 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15846.47 | 1538562.55 | 27-MAR-13:40 | 9.56 | 8.11 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 108803.79 | 1733861.40 | 07-APR-13:40 | 9.92 | 7.98 | 0.00 | 0.00 | 01-APR-00:10 |
May | 361963.12 | 1830649.45 | 30-MAY-10:30 | 10.10 | 8.04 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 844180.61 | 2872553.07 | 27-JUN-05:02 | 12.04 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 976323.07 | 2863335.20 | 24-JUL-03:03 | 12.02 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 979314.19 | 2630199.59 | 02-AUG-05:02 | 11.59 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 653021.99 | 3096011.70 | 14-SEP-05:02 | 12.46 | 6.78 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 326273.75 | 1937486.58 | 06-OCT-05:02 | 10.30 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 19518.92 | 849829.62 | 10-NOV-10:00 | 8.28 | 7.49 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 467.53 | 93643.58 | 07-DEC-11:40 | 6.87 | 6.79 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 359621.30 | 0.00 | ||||||
Minimum of Months | 437.61 | 37191.46 | 6.77 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 979314.19 | 3096011.70 | 12.46 | 8.11 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22.04 | 52073.42 | 24-JAN-06:03 | 9.80 | 6.78 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 15.71 | 15572.80 | 22-FEB-10:35 | 10.56 | 6.73 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8522.95 | 1012687.19 | 27-MAR-13:00 | 14.63 | 8.10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 64017.43 | 1532211.23 | 07-APR-14:00 | 12.75 | 7.93 | 0.00 | 0.00 | 01-APR-00:10 |
May | 226569.37 | 1809128.51 | 30-MAY-11:00 | 13.39 | 6.84 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 700846.25 | 3208342.39 | 27-JUN-05:01 | 15.06 | 7.33 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 855097.35 | 3602100.66 | 24-JUL-03:01 | 15.86 | 6.73 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 833428.47 | 3201946.75 | 01-AUG-05:02 | 14.44 | 7.19 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 500966.93 | 3458665.85 | 14-SEP-05:02 | 14.28 | 7.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 236834.88 | 2131211.96 | 06-OCT-05:01 | 14.95 | 7.44 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9576.83 | 472739.30 | 10-NOV-10:00 | 14.89 | 7.49 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102.71 | 59345.79 | 25-DEC-08:11 | 14.41 | 6.74 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 288330.34 | 0.00 | ||||||
Minimum of Months | 15.71 | 15572.80 | 9.80 | 6.73 | 0.00 | 0.00 | ||
Maximum of Months | 855097.35 | 3602100.66 | 15.86 | 8.10 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 155597.34 | 537440.79 | 28-JAN-01:01 | 29.31 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 292200.17 | 570515.20 | 26-FEB-07:51 | 29.98 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 439208.08 | 855845.62 | 27-MAR-16:00 | 35.72 | 26.20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 633080.45 | 1306010.14 | 07-APR-13:00 | 44.63 | 32.06 | 0.00 | 0.00 | 01-APR-00:10 |
May | 240166.60 | 861405.56 | 30-MAY-13:00 | 35.83 | 31.72 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 631192.50 | 1456558.32 | 19-JUN-12:00 | 47.58 | 39.96 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1023130.34 | 1531836.16 | 07-JUL-12:00 | 49.05 | 38.45 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1211264.46 | 1700928.06 | 24-AUG-16:00 | 52.34 | 39.46 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 364815.86 | 929874.62 | 01-SEP-14:00 | 37.19 | 32.91 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 372452.85 | 811246.32 | 04-OCT-13:00 | 34.82 | 27.90 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 440178.14 | 624897.09 | 03-NOV-14:00 | 31.08 | 21.71 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 568766.77 | 616872.44 | 29-DEC-22:12 | 30.92 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 533117.24 | 0.00 | ||||||
Minimum of Months | 155597.34 | 537440.79 | 29.31 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1211264.46 | 1700928.06 | 52.34 | 39.96 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 26.87 | 13967.88 | 20-JAN-06:50 | 21.14 | 20.48 | 835.08 | 126456.40 | 16-JAN-05:30 |
February | 28.66 | 24888.62 | 17-FEB-06:30 | 21.18 | 20.49 | 687.79 | 129704.74 | 13-FEB-04:13 |
March | 11007.61 | 1334579.28 | 27-MAR-13:40 | 23.21 | 22.34 | 945.66 | 121161.51 | 16-MAR-12:10 |
April | 80450.96 | 2235651.16 | 07-APR-14:30 | 24.64 | 21.70 | 725.92 | 134647.51 | 05-APR-05:01 |
May | 319018.47 | 4448876.20 | 31-MAY-13:10 | 28.15 | 25.07 | 547.26 | 74799.46 | 11-MAY-07:50 |
June | 1431239.81 | 7048722.03 | 15-JUN-12:20 | 32.26 | 28.84 | 84.83 | 69959.36 | 02-JUN-06:50 |
July | 2386729.46 | 7951321.56 | 20-JUL-15:00 | 33.69 | 29.86 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2072301.58 | 8343786.67 | 02-AUG-14:50 | 34.31 | 30.33 | 21.89 | 24562.16 | 20-AUG-03:00 |
September | 954407.01 | 6575631.65 | 07-SEP-14:10 | 31.51 | 28.02 | 77.38 | 54785.00 | 23-SEP-10:00 |
October | 338506.71 | 4048511.70 | 25-OCT-09:30 | 27.51 | 24.31 | 631.06 | 104685.28 | 08-OCT-13:51 |
November | 14668.25 | 610323.38 | 10-NOV-10:10 | 23.03 | 21.43 | 858.88 | 115293.64 | 22-NOV-06:40 |
December | 26.26 | 45821.00 | 08-DEC-08:30 | 21.25 | 20.63 | 549.28 | 117209.29 | 30-DEC-06:30 |
Annual Sum or Average | 639397.01 | 496.18 | ||||||
Minimum of Months | 26.26 | 13967.88 | 21.14 | 20.48 | 0.00 | 0.00 | ||
Maximum of Months | 2386729.46 | 8343786.67 | 34.31 | 30.33 | 945.66 | 134647.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 4.99 |
February | 0.45 | 7.08 |
March | 0.46 | 7.48 |
April | 0.67 | 7.48 |
May | 1.14 | 7.48 |
June | 1.10 | 7.48 |
July | 0.50 | 7.48 |
August | 0.46 | 7.48 |
September | 0.47 | 7.48 |
October | 0.74 | 7.48 |
November | 1.00 | 7.48 |
December | 1.10 | 7.48 |
Annual Sum or Average | 8.13 | 7.44 |
Minimum of Months | 0.06 | 4.99 |
Maximum of Months | 1.14 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.08 | 13.30 |
February | 1.79 | 12.34 |
March | 1.70 | 6.12 |
April | 6.09 | 3.47 |
May | 3.35 | 3.36 |
June | 7.83 | 2.64 |
July | 14.61 | 1.78 |
August | 13.47 | 1.97 |
September | 3.25 | 1.89 |
October | 2.09 | 3.10 |
November | 1.65 | 4.16 |
December | 1.23 | 4.67 |
Annual Sum or Average | 59.13 | 3.23 |
Minimum of Months | 1.23 | 1.78 |
Maximum of Months | 14.61 | 13.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.61 | 102.19 |
February | 0.15 | 52.80 |
March | 0.86 | 28.02 |
April | 2.17 | 13.93 |
May | 2.63 | 9.69 |
June | 2.07 | 3.80 |
July | 1.76 | 4.83 |
August | 1.95 | 2.22 |
September | 1.64 | 6.72 |
October | 2.08 | 11.38 |
November | 1.39 | 12.09 |
December | 0.76 | 75.21 |
Annual Sum or Average | 18.08 | 15.49 |
Minimum of Months | 0.15 | 2.22 |
Maximum of Months | 2.63 | 102.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.06 | 0.00 |
March | 0.39 | 0.96 |
April | 0.39 | 3.88 |
May | 1.21 | 6.02 |
June | 0.88 | 2.47 |
July | 1.32 | 3.85 |
August | 1.24 | 1.83 |
September | 0.43 | 5.85 |
October | 0.45 | 8.79 |
November | 0.11 | 6.72 |
December | 0.06 | 0.00 |
Annual Sum or Average | 6.53 | 3.97 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.32 | 8.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.06 | 0.00 |
March | 0.46 | 0.46 |
April | 1.82 | 0.41 |
May | 1.93 | 0.29 |
June | 6.78 | 0.28 |
July | 12.17 | 0.27 |
August | 12.44 | 0.28 |
September | 2.73 | 0.17 |
October | 1.53 | 0.17 |
November | 0.35 | 0.30 |
December | 0.11 | 0.42 |
Annual Sum or Average | 40.37 | 0.27 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 12.44 | 0.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 0.62 |
February | 0.71 | 0.56 |
March | 1.93 | 0.49 |
April | 6.96 | 0.24 |
May | 5.75 | 0.21 |
June | 10.81 | 0.21 |
July | 16.19 | 0.18 |
August | 19.84 | 0.17 |
September | 6.03 | 0.12 |
October | 5.85 | 0.40 |
November | 1.74 | 0.26 |
December | 1.08 | 0.49 |
Annual Sum or Average | 77.08 | 0.22 |
Minimum of Months | 0.19 | 0.12 |
Maximum of Months | 19.84 | 0.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.84 |
February | 0.24 | 0.65 |
March | 0.76 | 0.23 |
April | 3.07 | 0.34 |
May | 3.01 | 0.33 |
June | 8.06 | 0.31 |
July | 13.39 | 0.25 |
August | 14.25 | 0.27 |
September | 3.49 | 0.13 |
October | 2.58 | 0.30 |
November | 0.63 | 0.41 |
December | 0.19 | 0.60 |
Annual Sum or Average | 49.73 | 0.28 |
Minimum of Months | 0.06 | 0.13 |
Maximum of Months | 14.25 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.79 | 0.84 |
February | 2.04 | 0.52 |
March | 4.49 | 0.19 |
April | 9.81 | 0.20 |
May | 8.22 | 0.22 |
June | 10.99 | 0.22 |
July | 19.95 | 0.18 |
August | 26.76 | 0.16 |
September | 6.15 | 0.15 |
October | 5.95 | 0.26 |
November | 3.87 | 0.21 |
December | 3.79 | 0.24 |
Annual Sum or Average | 102.80 | 0.20 |
Minimum of Months | 0.79 | 0.15 |
Maximum of Months | 26.76 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 0.75 |
February | 0.40 | 0.98 |
March | 0.24 | 7.19 |
April | 0.71 | 11.49 |
May | 1.69 | 0.36 |
June | 2.01 | 0.32 |
July | 2.41 | 0.60 |
August | 1.45 | 0.28 |
September | 1.70 | 0.30 |
October | 0.91 | 1.76 |
November | 0.19 | 6.87 |
December | 0.51 | 6.71 |
Annual Sum or Average | 12.40 | 1.64 |
Minimum of Months | 0.19 | 0.28 |
Maximum of Months | 2.41 | 11.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 1.81 |
February | 1.34 | 1.26 |
March | 1.38 | 8.52 |
April | 3.04 | 3.94 |
May | 4.79 | 0.33 |
June | 6.09 | 0.22 |
July | 6.76 | 0.28 |
August | 5.97 | 0.15 |
September | 3.44 | 0.24 |
October | 3.26 | 1.00 |
November | 0.33 | 3.13 |
December | 1.93 | 4.54 |
Annual Sum or Average | 38.84 | 1.18 |
Minimum of Months | 0.33 | 0.15 |
Maximum of Months | 6.76 | 8.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.55 | 12.09 |
February | 0.85 | 8.80 |
March | 0.82 | 10.02 |
April | 1.01 | 8.36 |
May | 2.26 | 0.42 |
June | 3.07 | 0.39 |
July | 3.09 | 0.56 |
August | 2.57 | 0.24 |
September | 1.79 | 0.35 |
October | 1.26 | 1.29 |
November | 0.33 | 4.85 |
December | 1.00 | 10.31 |
Annual Sum or Average | 18.61 | 2.66 |
Minimum of Months | 0.33 | 0.24 |
Maximum of Months | 3.09 | 12.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.46 | 7.50 |
February | 0.85 | 2.83 |
March | 0.97 | 7.50 |
April | 3.75 | 5.03 |
May | 5.36 | 0.38 |
June | 6.12 | 0.23 |
July | 6.40 | 0.29 |
August | 5.86 | 0.18 |
September | 3.34 | 0.25 |
October | 3.22 | 0.61 |
November | 0.61 | 4.62 |
December | 1.68 | 5.91 |
Annual Sum or Average | 38.62 | 1.40 |
Minimum of Months | 0.46 | 0.18 |
Maximum of Months | 6.40 | 7.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.77 | 0.64 |
February | 1.09 | 0.61 |
March | 0.51 | 0.94 |
April | 0.26 | 1.03 |
May | 0.87 | 0.69 |
June | 2.38 | 0.31 |
July | 2.15 | 0.37 |
August | 2.39 | 0.27 |
September | 1.05 | 0.52 |
October | 0.09 | 1.37 |
November | 0.09 | 0.32 |
December | 0.84 | 0.84 |
Annual Sum or Average | 12.48 | 0.49 |
Minimum of Months | 0.09 | 0.27 |
Maximum of Months | 2.39 | 1.37 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 0.51 |
February | 0.84 | 0.51 |
March | 0.57 | 0.54 |
April | 0.78 | 1.19 |
May | 2.79 | 0.40 |
June | 4.57 | 0.26 |
July | 5.16 | 0.24 |
August | 5.58 | 0.17 |
September | 3.01 | 0.53 |
October | 1.07 | 0.74 |
November | 0.02 | 0.54 |
December | 0.84 | 0.54 |
Annual Sum or Average | 25.58 | 0.36 |
Minimum of Months | 0.02 | 0.17 |
Maximum of Months | 5.58 | 1.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.25 | 0.43 |
February | 0.62 | 0.58 |
March | 0.20 | 0.75 |
April | 0.30 | 0.88 |
May | 1.34 | 0.66 |
June | 2.89 | 0.30 |
July | 2.85 | 0.36 |
August | 3.16 | 0.19 |
September | 1.19 | 0.50 |
October | 0.42 | 1.07 |
November | 0.00 | 0.00 |
December | 0.62 | 0.84 |
Annual Sum or Average | 13.85 | 0.42 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.16 | 1.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.54 |
February | 0.45 | 0.54 |
March | 0.18 | 0.54 |
April | 1.08 | 0.59 |
May | 3.68 | 0.45 |
June | 4.66 | 0.29 |
July | 5.18 | 0.24 |
August | 5.60 | 0.18 |
September | 2.20 | 0.52 |
October | 1.23 | 0.78 |
November | 0.02 | 0.54 |
December | 0.59 | 0.54 |
Annual Sum or Average | 25.04 | 0.35 |
Minimum of Months | 0.02 | 0.18 |
Maximum of Months | 5.60 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.06 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 10.32 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 10.32 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 10.32 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 22.62 | 0.00 |
February | 1.25 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 23.87 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 22.62 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 6.95 | 0.00 |
February | 8.81 | 0.00 |
March | 1.73 | 0.00 |
April | 0.04 | 0.00 |
May | 0.87 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 1.15 | 0.00 |
November | 3.09 | 0.00 |
December | 3.47 | 0.00 |
Annual Sum or Average | 26.11 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 8.81 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.288886E+09 | 0.00 | 14116267.72 | 0.161148E+11 | 0.00 | 0.00 |
February | 0.711211E+09 | 0.00 | 1781617.06 | 0.151588E+11 | 0.00 | 0.00 |
March | 0.574846E+09 | 0.00 | 0.757143E+09 | 0.177614E+11 | 0.00 | 0.00 |
April | 0.467324E+09 | 0.00 | 0.658952E+10 | 0.166404E+11 | 0.00 | 0.00 |
May | 0.664028E+09 | 0.00 | 0.195188E+11 | 0.179574E+11 | 0.00 | 0.00 |
June | 0.484875E+09 | 0.00 | 0.761823E+11 | 0.178878E+11 | 0.00 | 0.00 |
July | 0.980480E+09 | 0.00 | 0.108800E+12 | 0.181424E+11 | 0.00 | 0.00 |
August | 0.382750E+09 | 0.00 | 0.106681E+12 | 0.191935E+11 | 0.00 | 0.00 |
September | 0.782404E+09 | 0.00 | 0.572638E+11 | 0.182148E+11 | 0.00 | 0.00 |
October | 0.174272E+10 | 0.00 | 0.228056E+11 | 0.187164E+11 | 0.00 | 0.00 |
November | 0.114487E+10 | 0.00 | 0.326551E+09 | 0.177173E+11 | 0.00 | 0.00 |
December | 0.905772E+09 | 0.00 | 7664040.20 | 0.173669E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.913017E+10 | 0.00 | 0.398948E+12 | 0.210872E+12 | 0.00 | 0.00 |
Minimum of Months | 0.288886E+09 | 0.00 | 1781617.06 | 0.151588E+11 | 0.00 | 0.00 |
Maximum of Months | 0.174272E+10 | 0.00 | 0.108800E+12 | 0.191935E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.371553E+11 | 0.00 | 2077.36 | 0.466100E+10 | 0.00 | 0.00 |
February | 0.347595E+11 | 0.00 | 423.07 | 0.483520E+10 | 0.00 | 0.00 |
March | 0.155081E+11 | 0.00 | 0.221884E+10 | 0.743926E+10 | 0.00 | 0.00 |
April | 0.434006E+10 | 0.00 | 0.153905E+11 | 0.762810E+10 | 0.00 | 0.00 |
May | 77727811.15 | 0.00 | 0.485121E+11 | 0.621936E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152055E+12 | 0.681006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220324E+12 | 0.763691E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.218849E+12 | 0.924616E+10 | 0.00 | 0.00 |
September | 7288493.09 | 0.00 | 0.103347E+12 | 0.606621E+10 | 0.00 | 0.00 |
October | 0.100402E+10 | 0.00 | 0.522698E+11 | 0.719825E+10 | 0.00 | 0.00 |
November | 0.921372E+10 | 0.00 | 0.236913E+10 | 0.676414E+10 | 0.00 | 0.00 |
December | 0.195802E+11 | 0.00 | 188.31 | 0.671901E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.121646E+12 | 0.00 | 0.815336E+12 | 0.812237E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 188.31 | 0.466100E+10 | 0.00 | 0.00 |
Maximum of Months | 0.371553E+11 | 0.00 | 0.220324E+12 | 0.924616E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.173048E+12 | 0.00 | 0.138969E+09 | 0.355366E+11 | 0.00 | 0.00 |
February | 0.116715E+12 | 0.00 | 63702036.43 | 0.338140E+11 | 0.00 | 0.00 |
March | 0.545894E+11 | 0.00 | 0.157964E+11 | 0.472380E+11 | 0.00 | 0.00 |
April | 0.148812E+11 | 0.00 | 0.109549E+12 | 0.444805E+11 | 0.00 | 0.00 |
May | 0.998594E+09 | 0.00 | 0.416648E+12 | 0.496111E+11 | 0.00 | 0.00 |
June | 0.598635E+09 | 0.00 | 0.123742E+13 | 0.541108E+11 | 0.00 | 0.00 |
July | 0.147781E+09 | 0.00 | 0.155889E+13 | 0.576295E+11 | 0.00 | 0.00 |
August | 0.700144E+09 | 0.00 | 0.148874E+13 | 0.677118E+11 | 0.00 | 0.00 |
September | 0.290195E+09 | 0.00 | 0.883572E+12 | 0.501361E+11 | 0.00 | 0.00 |
October | 0.446473E+10 | 0.00 | 0.432943E+12 | 0.508104E+11 | 0.00 | 0.00 |
November | 0.436501E+11 | 0.00 | 0.184076E+11 | 0.403445E+11 | 0.00 | 0.00 |
December | 0.978519E+11 | 0.00 | 0.298781E+09 | 0.384656E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.507936E+12 | 0.00 | 0.616246E+13 | 0.569889E+12 | 0.00 | 0.00 |
Minimum of Months | 0.147781E+09 | 0.00 | 63702036.43 | 0.338140E+11 | 0.00 | 0.00 |
Maximum of Months | 0.173048E+12 | 0.00 | 0.155889E+13 | 0.677118E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.866821E+11 | 0.00 | 4616457.29 | 0.386222E+10 | 0.00 | 0.00 |
February | 0.799593E+11 | 0.00 | 29503.08 | 0.339992E+10 | 0.00 | 0.00 |
March | 0.457355E+11 | 0.00 | 0.138299E+10 | 0.368817E+10 | 0.00 | 0.00 |
April | 0.171810E+11 | 0.00 | 0.112690E+11 | 0.379409E+10 | 0.00 | 0.00 |
May | 0.101142E+10 | 0.00 | 0.443378E+11 | 0.476012E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141447E+12 | 0.591992E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204368E+12 | 0.661448E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.193844E+12 | 0.752525E+10 | 0.00 | 0.00 |
September | 0.131342E+09 | 0.00 | 0.952751E+11 | 0.493248E+10 | 0.00 | 0.00 |
October | 0.522576E+10 | 0.00 | 0.421936E+11 | 0.419893E+10 | 0.00 | 0.00 |
November | 0.363211E+11 | 0.00 | 0.162109E+10 | 0.323887E+10 | 0.00 | 0.00 |
December | 0.667339E+11 | 0.00 | 235.58 | 0.334497E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.338981E+12 | 0.00 | 0.735744E+12 | 0.552794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 235.58 | 0.323887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866821E+11 | 0.00 | 0.204368E+12 | 0.752525E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.170672E+10 | 0.00 | 0.376117E+12 | 0.178440E+12 | 0.00 | 1.76 |
February | 0.812827E+09 | 0.00 | 0.597214E+12 | 0.209162E+12 | 0.00 | 1.96 |
March | 0.315883E+09 | 0.00 | 0.951341E+12 | 0.277425E+12 | 0.00 | 1.43 |
April | 70884858.62 | 0.00 | 0.121079E+13 | 0.319144E+12 | 0.00 | 0.71 |
May | 0.113217E+09 | 0.00 | 0.389410E+12 | 0.178100E+12 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.683483E+12 | 0.245591E+12 | 0.00 | 0.02 |
July | 0.00 | 0.00 | 0.103937E+13 | 0.342913E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.135004E+13 | 0.412095E+12 | 0.00 | 0.02 |
September | 0.00 | 0.00 | 0.390511E+12 | 0.178962E+12 | 0.00 | 0.04 |
October | 0.350661E+09 | 0.00 | 0.682110E+12 | 0.232640E+12 | 0.00 | 0.49 |
November | 0.498635E+09 | 0.00 | 0.926983E+12 | 0.268394E+12 | 0.00 | 1.02 |
December | 0.461385E+09 | 0.00 | 0.124185E+13 | 0.324778E+12 | 0.00 | 1.79 |
Annual Sum or Average | 0.433021E+10 | 0.00 | 0.983922E+13 | 0.316764E+13 | 0.00 | 9.52 |
Minimum of Months | 0.00 | 0.00 | 0.376117E+12 | 0.178100E+12 | 0.00 | 0.00 |
Maximum of Months | 0.170672E+10 | 0.00 | 0.135004E+13 | 0.412095E+12 | 0.00 | 1.96 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.523480E+10 | 0.262819E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107237E+11 | 0.359883E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188748E+11 | 0.529776E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.244422E+11 | 0.633870E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.701360E+10 | 0.307323E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135196E+11 | 0.479173E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211479E+11 | 0.710654E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256879E+11 | 0.815554E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.704034E+10 | 0.314642E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132683E+11 | 0.436252E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.182246E+11 | 0.512299E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247605E+11 | 0.631930E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189938E+12 | 0.599417E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.523480E+10 | 0.262819E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256879E+11 | 0.815554E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.250059E+11 | 0.194826E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.818837E+11 | 0.302592E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.164245E+12 | 0.476618E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223390E+12 | 0.588256E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602912E+11 | 0.278860E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126156E+12 | 0.450939E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201012E+12 | 0.676211E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.245180E+12 | 0.778453E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.612779E+11 | 0.286772E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117027E+12 | 0.397267E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.155441E+12 | 0.455097E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.212883E+12 | 0.562856E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167379E+13 | 0.544875E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.250059E+11 | 0.194826E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.245180E+12 | 0.778453E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.115952E+10 | 0.166016E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.590988E+10 | 0.257857E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.147448E+11 | 0.448967E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213347E+11 | 0.575298E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.562090E+10 | 0.273462E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126165E+11 | 0.454999E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202577E+11 | 0.684599E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.249488E+11 | 0.794634E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.580821E+10 | 0.283017E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.106799E+11 | 0.380364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.135639E+11 | 0.421363E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.187021E+11 | 0.521057E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155347E+12 | 0.526163E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.115952E+10 | 0.166016E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.249488E+11 | 0.794634E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161148E+11 | 14116267.72 | 0.288886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151588E+11 | 1781617.06 | 0.711211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177614E+11 | 0.757143E+09 | 0.574846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166404E+11 | 0.658952E+10 | 0.467324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179574E+11 | 0.195188E+11 | 0.664028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178878E+11 | 0.761823E+11 | 0.484875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181424E+11 | 0.108800E+12 | 0.980480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191935E+11 | 0.106681E+12 | 0.382750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182148E+11 | 0.572638E+11 | 0.782404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187164E+11 | 0.228056E+11 | 0.174272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177173E+11 | 0.326551E+09 | 0.114487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173669E+11 | 7664040.20 | 0.905772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210872E+12 | 0.398948E+12 | 0.913017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151588E+11 | 1781617.06 | 0.288886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191935E+11 | 0.108800E+12 | 0.174272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.466100E+10 | 2077.36 | 0.371553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483520E+10 | 423.07 | 0.347595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743926E+10 | 0.221884E+10 | 0.155081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762810E+10 | 0.153905E+11 | 0.434006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.621936E+10 | 0.485121E+11 | 77727811.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.681006E+10 | 0.152055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.763691E+10 | 0.220324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.924616E+10 | 0.218849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606621E+10 | 0.103347E+12 | 7288493.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.719825E+10 | 0.522698E+11 | 0.100402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676414E+10 | 0.236913E+10 | 0.921372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671901E+10 | 188.31 | 0.195802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.812237E+11 | 0.815336E+12 | 0.121646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.466100E+10 | 188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.924616E+10 | 0.220324E+12 | 0.371553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.355366E+11 | 0.138969E+09 | 0.173048E+12 | 0.555729E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338140E+11 | 63702036.43 | 0.116715E+12 | 0.539610E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.472380E+11 | 0.157964E+11 | 0.545894E+11 | 0.306574E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.444805E+11 | 0.109549E+12 | 0.148812E+11 | 0.111608E+12 | 0.183185E+09 | 0.00 | 0.00 | 0.00 |
May | 0.496111E+11 | 0.416648E+12 | 0.998594E+09 | 0.749269E+10 | 0.593403E+10 | 0.00 | 0.00 | 0.00 |
June | 0.541108E+11 | 0.123742E+13 | 0.598635E+09 | 0.00 | 0.856979E+11 | 0.00 | 0.00 | 0.00 |
July | 0.576295E+11 | 0.155889E+13 | 0.147781E+09 | 0.00 | 0.335602E+12 | 0.00 | 0.00 | 0.00 |
August | 0.677118E+11 | 0.148874E+13 | 0.700144E+09 | 0.00 | 0.320458E+12 | 0.00 | 0.00 | 0.00 |
September | 0.501361E+11 | 0.883572E+12 | 0.290195E+09 | 0.105784E+10 | 0.464108E+11 | 0.00 | 0.00 | 0.00 |
October | 0.508104E+11 | 0.432943E+12 | 0.446473E+10 | 0.296395E+11 | 0.546592E+09 | 0.00 | 0.00 | 0.00 |
November | 0.403445E+11 | 0.184076E+11 | 0.436501E+11 | 0.219235E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384656E+11 | 0.298781E+09 | 0.978519E+11 | 0.427102E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569889E+12 | 0.616246E+13 | 0.507936E+12 | 0.219805E+13 | 0.794832E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.338140E+11 | 63702036.43 | 0.147781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.677118E+11 | 0.155889E+13 | 0.173048E+12 | 0.555729E+12 | 0.335602E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.386222E+10 | 4616457.29 | 0.866821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339992E+10 | 29503.08 | 0.799593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368817E+10 | 0.138299E+10 | 0.457355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379409E+10 | 0.112690E+11 | 0.171810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.476012E+10 | 0.443378E+11 | 0.101142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.591992E+10 | 0.141447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.661448E+10 | 0.204368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.752525E+10 | 0.193844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.493248E+10 | 0.952751E+11 | 0.131342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419893E+10 | 0.421936E+11 | 0.522576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323887E+10 | 0.162109E+10 | 0.363211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334497E+10 | 235.58 | 0.667339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552794E+11 | 0.735744E+12 | 0.338981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323887E+10 | 235.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.752525E+10 | 0.204368E+12 | 0.866821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.944523E+11 | 0.320931E+12 | 0.170672E+10 | 0.00 | 0.00 | 0.470552E+10 | 0.00 | 0.00 |
February | 0.853118E+11 | 0.509098E+12 | 0.812827E+09 | 0.00 | 0.00 | 0.525058E+10 | 0.00 | 0.00 |
March | 0.944523E+11 | 0.811556E+12 | 0.315883E+09 | 0.00 | 0.00 | 0.383546E+10 | 0.00 | 0.00 |
April | 0.914055E+11 | 0.102695E+13 | 70884858.62 | 0.00 | 0.00 | 0.189815E+10 | 0.00 | 0.00 |
May | 0.944523E+11 | 0.330310E+12 | 0.113217E+09 | 0.00 | 0.00 | 0.730937E+09 | 0.00 | 0.00 |
June | 0.914055E+11 | 0.564615E+12 | 0.00 | 0.00 | 0.00 | 66770193.87 | 0.00 | 0.00 |
July | 0.944523E+11 | 0.834624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944523E+11 | 0.107810E+13 | 0.00 | 0.00 | 0.00 | 50302941.74 | 0.00 | 0.00 |
September | 0.914055E+11 | 0.327394E+12 | 0.00 | 0.00 | 0.00 | 0.110346E+09 | 0.00 | 0.00 |
October | 0.944523E+11 | 0.579595E+12 | 0.350661E+09 | 0.00 | 0.00 | 0.130310E+10 | 0.00 | 0.00 |
November | 0.914055E+11 | 0.791098E+12 | 0.498635E+09 | 0.00 | 0.00 | 0.271936E+10 | 0.00 | 0.00 |
December | 0.944523E+11 | 0.105925E+13 | 0.461385E+09 | 0.00 | 0.00 | 0.479510E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.111210E+13 | 0.823352E+13 | 0.433021E+10 | 0.00 | 0.00 | 0.254656E+11 | 0.00 | 0.00 |
Minimum of Months | 0.853118E+11 | 0.320931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944523E+11 | 0.107810E+13 | 0.170672E+10 | 0.00 | 0.00 | 0.525058E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140940E+10 | 0.432328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127301E+10 | 0.885370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140940E+10 | 0.155790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136393E+10 | 0.200428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140940E+10 | 0.572982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136393E+10 | 0.106371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140940E+10 | 0.160286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140940E+10 | 0.196001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136393E+10 | 0.564555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140940E+10 | 0.108510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136393E+10 | 0.150384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140940E+10 | 0.204403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165945E+11 | 0.152770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127301E+10 | 0.432328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140940E+10 | 0.204403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134370E+11 | 0.206523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121367E+11 | 0.676050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134370E+11 | 0.135561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130036E+11 | 0.183064E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134370E+11 | 0.492301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130036E+11 | 0.992292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134370E+11 | 0.152353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134370E+11 | 0.187038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130036E+11 | 0.490953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134370E+11 | 0.956712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130036E+11 | 0.128261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134370E+11 | 0.175733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158210E+12 | 0.134349E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121367E+11 | 0.206523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134370E+11 | 0.187038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137324E+10 | 0.957682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124035E+10 | 0.487934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137324E+10 | 0.121691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132895E+10 | 0.174721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137324E+10 | 0.458377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132895E+10 | 0.991815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137324E+10 | 0.153512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137324E+10 | 0.189980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132895E+10 | 0.464596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137324E+10 | 0.872385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132895E+10 | 0.111913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137324E+10 | 0.154385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161688E+11 | 0.124329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124035E+10 | 0.957682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137324E+10 | 0.189980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.161148E+11 | 0.288886E+09 | 14116267.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151588E+11 | 0.711211E+09 | 1781617.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177614E+11 | 0.574846E+09 | 0.757143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166404E+11 | 0.467324E+09 | 0.658952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179574E+11 | 0.664028E+09 | 0.195188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178878E+11 | 0.484875E+09 | 0.761823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181424E+11 | 0.980480E+09 | 0.108800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191935E+11 | 0.382750E+09 | 0.106681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182148E+11 | 0.782404E+09 | 0.572638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187164E+11 | 0.174272E+10 | 0.228056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177173E+11 | 0.114487E+10 | 0.326551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173669E+11 | 0.905772E+09 | 7664040.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210872E+12 | 0.913017E+10 | 0.398948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.151588E+11 | 0.288886E+09 | 1781617.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191935E+11 | 0.174272E+10 | 0.108800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.466100E+10 | 0.371553E+11 | 2077.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483520E+10 | 0.347595E+11 | 423.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743926E+10 | 0.155081E+11 | 0.221884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762810E+10 | 0.434006E+10 | 0.153905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.621936E+10 | 77727811.15 | 0.485121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.681006E+10 | 0.00 | 0.152055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.763691E+10 | 0.00 | 0.220324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.924616E+10 | 0.00 | 0.218849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606621E+10 | 7288493.09 | 0.103347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.719825E+10 | 0.100402E+10 | 0.522698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676414E+10 | 0.921372E+10 | 0.236913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671901E+10 | 0.195802E+11 | 188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.812237E+11 | 0.121646E+12 | 0.815336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.466100E+10 | 0.00 | 188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.924616E+10 | 0.371553E+11 | 0.220324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.355366E+11 | 0.173048E+12 | 0.138969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338140E+11 | 0.116715E+12 | 63702036.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.472380E+11 | 0.545894E+11 | 0.157964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.444805E+11 | 0.148812E+11 | 0.109549E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.496111E+11 | 0.998594E+09 | 0.416648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.541108E+11 | 0.598635E+09 | 0.123742E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.576295E+11 | 0.147781E+09 | 0.155889E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.677118E+11 | 0.700144E+09 | 0.148874E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.501361E+11 | 0.290195E+09 | 0.883572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.508104E+11 | 0.446473E+10 | 0.432943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403445E+11 | 0.436501E+11 | 0.184076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384656E+11 | 0.978519E+11 | 0.298781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569889E+12 | 0.507936E+12 | 0.616246E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.338140E+11 | 0.147781E+09 | 63702036.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.677118E+11 | 0.173048E+12 | 0.155889E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.386222E+10 | 0.866821E+11 | 4616457.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339992E+10 | 0.799593E+11 | 29503.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368817E+10 | 0.457355E+11 | 0.138299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379409E+10 | 0.171810E+11 | 0.112690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.476012E+10 | 0.101142E+10 | 0.443378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.591992E+10 | 0.00 | 0.141447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.661448E+10 | 0.00 | 0.204368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.752525E+10 | 0.00 | 0.193844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.493248E+10 | 0.131342E+09 | 0.952751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419893E+10 | 0.522576E+10 | 0.421936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323887E+10 | 0.363211E+11 | 0.162109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334497E+10 | 0.667339E+11 | 235.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552794E+11 | 0.338981E+12 | 0.735744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.323887E+10 | 0.00 | 235.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.752525E+10 | 0.866821E+11 | 0.204368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.944523E+11 | 0.170672E+10 | 0.376117E+12 | 0.00 | 0.792605E+11 | 0.00 | 0.00 | 0.00 | 0.472670E+10 | 0.00 | 0.00 | 0.00 |
February | 0.853118E+11 | 0.812827E+09 | 0.597214E+12 | 0.00 | 0.118576E+12 | 0.00 | 0.00 | 0.00 | 0.527421E+10 | 0.00 | 0.00 | 0.00 |
March | 0.944523E+11 | 0.315883E+09 | 0.951341E+12 | 0.00 | 0.179120E+12 | 0.00 | 0.00 | 0.00 | 0.385272E+10 | 0.00 | 0.00 | 0.00 |
April | 0.914055E+11 | 70884858.62 | 0.121079E+13 | 0.00 | 0.225832E+12 | 0.00 | 0.00 | 0.00 | 0.190670E+10 | 0.00 | 0.00 | 0.00 |
May | 0.944523E+11 | 0.113217E+09 | 0.389410E+12 | 0.00 | 0.829131E+11 | 0.00 | 0.00 | 0.00 | 0.734227E+09 | 0.00 | 0.00 | 0.00 |
June | 0.914055E+11 | 0.00 | 0.683483E+12 | 0.00 | 0.154118E+12 | 0.00 | 0.00 | 0.00 | 67070753.58 | 0.00 | 0.00 | 0.00 |
July | 0.944523E+11 | 0.00 | 0.103937E+13 | 0.00 | 0.248461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944523E+11 | 0.00 | 0.135004E+13 | 0.00 | 0.317592E+12 | 0.00 | 0.00 | 0.00 | 50529375.67 | 0.00 | 0.00 | 0.00 |
September | 0.914055E+11 | 0.00 | 0.390511E+12 | 0.00 | 0.874456E+11 | 0.00 | 0.00 | 0.00 | 0.110843E+09 | 0.00 | 0.00 | 0.00 |
October | 0.944523E+11 | 0.350661E+09 | 0.682110E+12 | 0.00 | 0.136879E+12 | 0.00 | 0.00 | 0.00 | 0.130897E+10 | 0.00 | 0.00 | 0.00 |
November | 0.914055E+11 | 0.498635E+09 | 0.926983E+12 | 0.00 | 0.174257E+12 | 0.00 | 0.00 | 0.00 | 0.273160E+10 | 0.00 | 0.00 | 0.00 |
December | 0.944523E+11 | 0.461385E+09 | 0.124185E+13 | 0.00 | 0.225509E+12 | 0.00 | 0.00 | 0.00 | 0.481669E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111210E+13 | 0.433021E+10 | 0.983922E+13 | 0.00 | 0.202996E+13 | 0.00 | 0.00 | 0.00 | 0.255803E+11 | 0.00 | 0.00 | |
Minimum of Months | 0.853118E+11 | 0.00 | 0.376117E+12 | 0.00 | 0.792605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944523E+11 | 0.170672E+10 | 0.135004E+13 | 0.00 | 0.317592E+12 | 0.00 | 0.00 | 0.00 | 0.527421E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.140940E+10 | 0.00 | 0.523480E+10 | 0.00 | 0.121879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127301E+10 | 0.00 | 0.107237E+11 | 0.00 | 0.232582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140940E+10 | 0.00 | 0.188748E+11 | 0.00 | 0.388837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136393E+10 | 0.00 | 0.244422E+11 | 0.00 | 0.497477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140940E+10 | 0.00 | 0.701360E+10 | 0.00 | 0.166383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136393E+10 | 0.00 | 0.135196E+11 | 0.00 | 0.342779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140940E+10 | 0.00 | 0.211479E+11 | 0.00 | 0.569714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140940E+10 | 0.00 | 0.256879E+11 | 0.00 | 0.674614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136393E+10 | 0.00 | 0.704034E+10 | 0.00 | 0.178248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140940E+10 | 0.00 | 0.132683E+11 | 0.00 | 0.295312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136393E+10 | 0.00 | 0.182246E+11 | 0.00 | 0.375905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140940E+10 | 0.00 | 0.247605E+11 | 0.00 | 0.490990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165945E+11 | 0.00 | 0.189938E+12 | 0.00 | 0.433472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.127301E+10 | 0.00 | 0.523480E+10 | 0.00 | 0.121879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140940E+10 | 0.00 | 0.256879E+11 | 0.00 | 0.674614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.134370E+11 | 0.00 | 0.250059E+11 | 0.00 | 0.604555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121367E+11 | 0.00 | 0.818837E+11 | 0.00 | 0.181226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134370E+11 | 0.00 | 0.164245E+12 | 0.00 | 0.342247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130036E+11 | 0.00 | 0.223390E+12 | 0.00 | 0.458220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134370E+11 | 0.00 | 0.602912E+11 | 0.00 | 0.144490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130036E+11 | 0.00 | 0.126156E+12 | 0.00 | 0.320903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134370E+11 | 0.00 | 0.201012E+12 | 0.00 | 0.541841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134370E+11 | 0.00 | 0.245180E+12 | 0.00 | 0.644083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130036E+11 | 0.00 | 0.612779E+11 | 0.00 | 0.156737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134370E+11 | 0.00 | 0.117027E+12 | 0.00 | 0.262897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130036E+11 | 0.00 | 0.155441E+12 | 0.00 | 0.325061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134370E+11 | 0.00 | 0.212883E+12 | 0.00 | 0.428485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158210E+12 | 0.00 | 0.167379E+13 | 0.00 | 0.386665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.121367E+11 | 0.00 | 0.250059E+11 | 0.00 | 0.604555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134370E+11 | 0.00 | 0.245180E+12 | 0.00 | 0.644083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.137324E+10 | 0.00 | 0.115952E+10 | 0.00 | 0.286917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124035E+10 | 0.00 | 0.590988E+10 | 0.00 | 0.133822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137324E+10 | 0.00 | 0.147448E+11 | 0.00 | 0.311643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132895E+10 | 0.00 | 0.213347E+11 | 0.00 | 0.442404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137324E+10 | 0.00 | 0.562090E+10 | 0.00 | 0.136137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132895E+10 | 0.00 | 0.126165E+11 | 0.00 | 0.322104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137324E+10 | 0.00 | 0.202577E+11 | 0.00 | 0.547274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137324E+10 | 0.00 | 0.249488E+11 | 0.00 | 0.657309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132895E+10 | 0.00 | 0.580821E+10 | 0.00 | 0.150122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137324E+10 | 0.00 | 0.106799E+11 | 0.00 | 0.243040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132895E+10 | 0.00 | 0.135639E+11 | 0.00 | 0.288468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137324E+10 | 0.00 | 0.187021E+11 | 0.00 | 0.383733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161688E+11 | 0.00 | 0.155347E+12 | 0.00 | 0.364475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124035E+10 | 0.00 | 0.115952E+10 | 0.00 | 0.286917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137324E+10 | 0.00 | 0.249488E+11 | 0.00 | 0.657309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135176E+10 | 0.00 | 0.00 | 0.154368E+09 | 0.00 | 0.00 | 0.743943E+11 | 0.00 | 0.56 |
February | 0.590593E+09 | 0.00 | 0.00 | 0.147614E+09 | 0.00 | 0.00 | 0.698110E+11 | 0.00 | 0.53 |
March | 0.421471E+09 | 0.00 | 0.00 | 0.182532E+09 | 0.00 | 0.00 | 0.849359E+11 | 0.00 | 0.80 |
April | 0.421308E+09 | 17510573.41 | 0.00 | 0.167322E+09 | 0.00 | 0.00 | 0.740677E+11 | 0.00 | 1.06 |
May | 0.211638E+09 | 0.227652E+09 | 0.00 | 0.167365E+09 | 0.00 | 0.00 | 0.660327E+11 | 0.00 | 1.47 |
June | 0.100835E+09 | 0.644317E+10 | 0.00 | 0.103355E+09 | 35549526.05 | 0.00 | 0.183028E+11 | 0.00 | 1.05 |
July | 15328716.69 | 0.202693E+11 | 0.00 | 24614452.22 | 0.119792E+09 | 0.00 | 0.130106E+10 | 0.00 | 0.40 |
August | 44938265.32 | 0.170028E+11 | 0.00 | 80282828.78 | 0.143379E+09 | 0.00 | 0.863376E+10 | 0.00 | 0.78 |
September | 0.216698E+09 | 0.424474E+10 | 0.00 | 0.150669E+09 | 4571871.26 | 0.00 | 0.366576E+11 | 0.00 | 1.29 |
October | 0.357934E+09 | 0.183659E+09 | 0.00 | 0.214308E+09 | 0.00 | 0.00 | 0.719066E+11 | 0.00 | 1.40 |
November | 0.425539E+09 | 0.00 | 0.00 | 0.212115E+09 | 0.00 | 0.00 | 0.883030E+11 | 0.00 | 0.96 |
December | 0.664050E+09 | 0.00 | 0.00 | 0.199801E+09 | 0.00 | 0.00 | 0.842980E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.482210E+10 | 0.483889E+11 | 0.00 | 0.180435E+10 | 0.303291E+09 | 0.00 | 0.678644E+12 | 0.00 | 0.92 |
Minimum of Months | 15328716.69 | 0.00 | 0.00 | 24614452.22 | 0.00 | 0.00 | 0.130106E+10 | 0.00 | 0.40 |
Maximum of Months | 0.135176E+10 | 0.202693E+11 | 0.00 | 0.214308E+09 | 0.143379E+09 | 0.00 | 0.883030E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.413574E+10 | 0.00 | 0.00 | 80942034.17 | 0.00 | 0.00 | 0.647178E+11 | 0.00 | 0.49 |
February | 0.235432E+10 | 0.00 | 0.00 | 83933325.95 | 0.00 | 0.00 | 0.656321E+11 | 0.00 | 0.51 |
March | 0.298345E+10 | 0.00 | 0.00 | 0.126540E+09 | 0.00 | 0.00 | 0.732418E+11 | 0.00 | 0.68 |
April | 0.562100E+10 | 12327295.79 | 0.00 | 0.116631E+09 | 0.00 | 0.00 | 0.590600E+11 | 0.00 | 0.84 |
May | 0.353760E+10 | 0.728163E+09 | 0.00 | 0.100209E+09 | 0.00 | 0.00 | 0.380235E+11 | 0.00 | 0.85 |
June | 0.142769E+10 | 0.173922E+11 | 0.00 | 35252483.13 | 0.212082E+09 | 0.00 | 0.609814E+10 | 0.00 | 0.62 |
July | 0.103004E+09 | 0.393898E+11 | 0.00 | 2578867.08 | 0.552370E+09 | 0.00 | 0.217939E+09 | 0.00 | 0.42 |
August | 0.160713E+10 | 0.307906E+11 | 0.00 | 25546213.67 | 0.416347E+09 | 0.00 | 0.245902E+10 | 0.00 | 0.59 |
September | 0.231086E+10 | 0.103260E+11 | 0.00 | 63040800.73 | 0.102401E+09 | 0.00 | 0.170350E+11 | 0.00 | 0.70 |
October | 0.387901E+10 | 0.150361E+10 | 0.00 | 0.103816E+09 | 0.00 | 0.00 | 0.387611E+11 | 0.00 | 0.80 |
November | 0.260812E+10 | 0.00 | 0.00 | 0.120648E+09 | 0.00 | 0.00 | 0.660335E+11 | 0.00 | 0.70 |
December | 0.298408E+10 | 0.00 | 0.00 | 0.124926E+09 | 0.00 | 0.00 | 0.717267E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.335520E+11 | 0.100143E+12 | 0.00 | 0.984065E+09 | 0.128320E+10 | 0.00 | 0.503007E+12 | 0.00 | 0.65 |
Minimum of Months | 0.103004E+09 | 0.00 | 0.00 | 2578867.08 | 0.00 | 0.00 | 0.217939E+09 | 0.00 | 0.42 |
Maximum of Months | 0.562100E+10 | 0.393898E+11 | 0.00 | 0.126540E+09 | 0.552370E+09 | 0.00 | 0.732418E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141927E+12 | 0.00 | 0.00 | 0.244720E+09 | 0.00 | 0.321760E+10 | 0.161769E+12 | 0.00 | 0.45 |
February | 0.125090E+12 | 0.00 | 0.00 | 0.285366E+09 | 0.00 | 45587020.09 | 0.185508E+12 | 0.00 | 0.47 |
March | 0.646417E+11 | 0.00 | 0.00 | 0.659501E+09 | 0.00 | 0.00 | 0.375017E+12 | 0.00 | 0.55 |
April | 0.387144E+11 | 37923611.44 | 0.00 | 0.705327E+09 | 0.00 | 0.00 | 0.360012E+12 | 0.00 | 0.60 |
May | 0.269872E+11 | 0.428852E+10 | 0.00 | 0.788850E+09 | 0.00 | 0.00 | 0.301684E+12 | 0.00 | 0.71 |
June | 0.867986E+10 | 0.126297E+12 | 0.00 | 0.309738E+09 | 0.405414E+10 | 0.00 | 0.486954E+11 | 0.00 | 0.58 |
July | 0.522270E+09 | 0.210467E+12 | 0.00 | 26791267.64 | 0.530115E+10 | 0.00 | 0.219654E+10 | 0.00 | 0.43 |
August | 0.519310E+10 | 0.135411E+12 | 0.00 | 0.296162E+09 | 0.254666E+10 | 0.00 | 0.233527E+11 | 0.00 | 0.55 |
September | 0.174685E+11 | 0.771499E+11 | 0.00 | 0.501028E+09 | 0.265003E+10 | 0.00 | 0.133939E+12 | 0.00 | 0.61 |
October | 0.272572E+11 | 0.141892E+11 | 0.00 | 0.728266E+09 | 79337709.06 | 0.00 | 0.273997E+12 | 0.00 | 0.64 |
November | 0.514840E+11 | 0.00 | 0.00 | 0.606166E+09 | 0.00 | 0.00 | 0.343365E+12 | 0.00 | 0.54 |
December | 0.110064E+12 | 0.00 | 0.00 | 0.441603E+09 | 0.00 | 0.00 | 0.260665E+12 | 0.00 | 0.48 |
Annual Sum or Average | 0.618029E+12 | 0.567841E+12 | 0.00 | 0.559352E+10 | 0.146313E+11 | 0.326319E+10 | 0.247020E+13 | 0.00 | 0.55 |
Minimum of Months | 0.522270E+09 | 0.00 | 0.00 | 26791267.64 | 0.00 | 0.00 | 0.219654E+10 | 0.00 | 0.43 |
Maximum of Months | 0.141927E+12 | 0.210467E+12 | 0.00 | 0.788850E+09 | 0.530115E+10 | 0.321760E+10 | 0.375017E+12 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427186E+11 | 0.00 | 0.00 | 2721230.06 | 0.00 | 0.337568E+10 | 0.501857E+10 | 0.00 | 0.42 |
February | 0.406454E+11 | 0.00 | 0.00 | 4512903.41 | 0.00 | 0.222545E+10 | 0.697670E+10 | 0.00 | 0.42 |
March | 0.289363E+11 | 0.00 | 0.00 | 21147193.58 | 0.00 | 0.371790E+09 | 0.219688E+11 | 0.00 | 0.49 |
April | 0.135148E+11 | 1027722.72 | 0.00 | 37822237.12 | 0.00 | 0.141557E+09 | 0.266825E+11 | 0.00 | 0.55 |
May | 0.612889E+10 | 0.626570E+09 | 0.00 | 59509814.59 | 0.00 | 0.00 | 0.251374E+11 | 0.00 | 0.68 |
June | 0.886453E+09 | 0.166738E+11 | 0.00 | 28070273.06 | 0.199618E+09 | 0.00 | 0.528818E+10 | 0.00 | 0.58 |
July | 53435665.64 | 0.386621E+11 | 0.00 | 2768713.69 | 0.620287E+09 | 0.00 | 0.226893E+09 | 0.00 | 0.44 |
August | 0.456072E+09 | 0.301060E+11 | 0.00 | 27859773.00 | 0.391952E+09 | 0.00 | 0.242659E+10 | 0.00 | 0.56 |
September | 0.369054E+10 | 0.976342E+10 | 0.00 | 36928782.74 | 0.419896E+09 | 0.00 | 0.100884E+11 | 0.00 | 0.59 |
October | 0.874748E+10 | 0.119231E+10 | 0.00 | 37547318.45 | 75989013.73 | 0.00 | 0.162537E+11 | 0.00 | 0.55 |
November | 0.249807E+11 | 0.00 | 0.00 | 15200367.79 | 0.00 | 0.710054E+09 | 0.147302E+11 | 0.00 | 0.46 |
December | 0.397861E+11 | 0.00 | 0.00 | 4404689.67 | 0.00 | 0.648588E+09 | 0.747807E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.210545E+12 | 0.970252E+11 | 0.00 | 0.278493E+09 | 0.170774E+10 | 0.747312E+10 | 0.142276E+12 | 0.00 | 0.51 |
Minimum of Months | 53435665.64 | 0.00 | 0.00 | 2721230.06 | 0.00 | 0.00 | 0.226893E+09 | 0.00 | 0.42 |
Maximum of Months | 0.427186E+11 | 0.386621E+11 | 0.00 | 59509814.59 | 0.620287E+09 | 0.337568E+10 | 0.266825E+11 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.683605E+10 | 0.00 | 0.00 | 393782.34 | 0.00 | 0.112014E+09 | 0.629074E+09 | 0.00 | 0.42 |
February | 0.614388E+10 | 0.00 | 0.00 | 771507.78 | 0.00 | 0.125779E+09 | 0.774068E+09 | 0.00 | 0.42 |
March | 0.423254E+10 | 0.00 | 0.00 | 4601999.00 | 0.00 | 0.00 | 0.332273E+10 | 0.00 | 0.54 |
April | 0.266962E+10 | 1917576.20 | 0.00 | 7119595.39 | 0.00 | 0.00 | 0.460940E+10 | 0.00 | 0.79 |
May | 0.120119E+10 | 0.127596E+09 | 0.00 | 9050835.66 | 0.00 | 0.00 | 0.425776E+10 | 0.00 | 0.93 |
June | 0.260453E+09 | 0.303536E+10 | 0.00 | 3735527.06 | 33210778.84 | 0.00 | 0.814822E+09 | 0.00 | 0.79 |
July | 16502854.56 | 0.711867E+10 | 0.00 | 327129.67 | 86497834.70 | 0.00 | 32765918.22 | 0.00 | 0.59 |
August | 0.264048E+09 | 0.552985E+10 | 0.00 | 2940799.79 | 65197445.53 | 0.00 | 0.327101E+09 | 0.00 | 0.77 |
September | 0.721488E+09 | 0.159876E+10 | 0.00 | 5156056.19 | 16035430.97 | 0.00 | 0.180317E+10 | 0.00 | 0.78 |
October | 0.176788E+10 | 0.209401E+09 | 0.00 | 6017735.95 | 0.00 | 0.00 | 0.304340E+10 | 0.00 | 0.77 |
November | 0.334307E+10 | 0.00 | 0.00 | 4221317.36 | 0.00 | 0.00 | 0.325203E+10 | 0.00 | 0.55 |
December | 0.486920E+10 | 0.00 | 0.00 | 1816418.51 | 0.00 | 0.00 | 0.189572E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.323259E+11 | 0.176216E+11 | 0.00 | 46152704.69 | 0.200941E+09 | 0.237792E+09 | 0.247620E+11 | 0.00 | 0.65 |
Minimum of Months | 16502854.56 | 0.00 | 0.00 | 327129.67 | 0.00 | 0.00 | 32765918.22 | 0.00 | 0.41 |
Maximum of Months | 0.683605E+10 | 0.711867E+10 | 0.00 | 9050835.66 | 86497834.70 | 0.125779E+09 | 0.460940E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.798560E+10 | 0.00 | 0.00 | 261022.18 | 0.00 | 0.363911E+09 | 0.296923E+09 | 0.00 | 0.75 |
February | 0.746147E+10 | 0.00 | 0.00 | 450196.91 | 0.00 | 0.117130E+09 | 0.466855E+09 | 0.00 | 0.74 |
March | 0.548683E+10 | 0.00 | 0.00 | 3557162.50 | 0.00 | 848621.05 | 0.280270E+10 | 0.00 | 0.89 |
April | 0.405801E+10 | 1330860.08 | 0.00 | 5287987.41 | 0.00 | 0.00 | 0.334632E+10 | 0.00 | 1.21 |
May | 0.220778E+10 | 0.107159E+09 | 0.00 | 7217427.42 | 3001940.39 | 0.00 | 0.350844E+10 | 0.00 | 1.44 |
June | 0.403818E+09 | 0.206620E+10 | 0.00 | 2946519.66 | 0.415482E+09 | 0.00 | 0.800832E+09 | 0.00 | 1.11 |
July | 20526375.63 | 0.503516E+10 | 0.00 | 292517.36 | 0.704601E+09 | 0.00 | 38008548.76 | 0.00 | 0.76 |
August | 0.371776E+09 | 0.422042E+10 | 0.00 | 2209981.79 | 0.288108E+09 | 0.00 | 0.294319E+09 | 0.00 | 1.07 |
September | 0.125794E+10 | 0.104033E+10 | 0.00 | 3987208.67 | 0.383458E+09 | 0.00 | 0.141401E+10 | 0.00 | 1.18 |
October | 0.260917E+10 | 0.139866E+09 | 0.00 | 4633550.89 | 36526338.94 | 0.00 | 0.235675E+10 | 0.00 | 1.18 |
November | 0.485260E+10 | 0.00 | 0.00 | 1687429.50 | 0.00 | 676557.73 | 0.197309E+10 | 0.00 | 0.85 |
December | 0.699097E+10 | 0.00 | 0.00 | 463350.25 | 0.00 | 1545970.10 | 0.576819E+09 | 0.00 | 0.70 |
Annual Sum or Average | 0.437065E+11 | 0.126105E+11 | 0.00 | 32994354.53 | 0.183118E+10 | 0.484112E+09 | 0.178751E+11 | 0.00 | 0.99 |
Minimum of Months | 20526375.63 | 0.00 | 0.00 | 261022.18 | 0.00 | 0.00 | 38008548.76 | 0.00 | 0.70 |
Maximum of Months | 0.798560E+10 | 0.503516E+10 | 0.00 | 7217427.42 | 0.704601E+09 | 0.363911E+09 | 0.350844E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.608403E+10 | 0.00 | 0.00 | 5694550.83 | 0.00 | 0.584625E+09 | 0.400002E+10 | 0.00 | 0.59 |
February | 0.516594E+10 | 0.00 | 0.00 | 6852291.98 | 0.00 | 0.281891E+09 | 0.492225E+10 | 0.00 | 0.62 |
March | 0.436044E+10 | 0.00 | 0.00 | 11037196.45 | 0.00 | 707741.32 | 0.676140E+10 | 0.00 | 0.82 |
April | 0.338338E+10 | 3333099.76 | 0.00 | 8400801.89 | 0.00 | 0.00 | 0.528905E+10 | 0.00 | 0.96 |
May | 0.181292E+10 | 0.139151E+09 | 0.00 | 8859152.78 | 0.00 | 0.00 | 0.408600E+10 | 0.00 | 1.01 |
June | 0.345757E+09 | 0.319621E+10 | 0.00 | 3398746.14 | 37698629.08 | 0.00 | 0.806039E+09 | 0.00 | 0.84 |
July | 18732923.90 | 0.761219E+10 | 0.00 | 313843.21 | 98186489.46 | 0.00 | 32291527.02 | 0.00 | 0.63 |
August | 0.306287E+09 | 0.649347E+10 | 0.00 | 3374978.80 | 74007728.87 | 0.00 | 0.375351E+09 | 0.00 | 0.92 |
September | 0.873733E+09 | 0.206324E+10 | 0.00 | 9245275.64 | 29511505.84 | 0.00 | 0.257247E+10 | 0.00 | 1.08 |
October | 0.147253E+10 | 0.370585E+09 | 0.00 | 15102457.62 | 699897.46 | 0.00 | 0.631560E+10 | 0.00 | 1.25 |
November | 0.327465E+10 | 0.00 | 0.00 | 10361977.13 | 0.00 | 1239638.38 | 0.659712E+10 | 0.00 | 0.84 |
December | 0.498730E+10 | 0.00 | 0.00 | 8729153.52 | 0.00 | 2249864.20 | 0.509848E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.320857E+11 | 0.198782E+11 | 0.00 | 91370425.99 | 0.240104E+09 | 0.870713E+09 | 0.468561E+11 | 0.00 | 0.85 |
Minimum of Months | 18732923.90 | 0.00 | 0.00 | 313843.21 | 0.00 | 0.00 | 32291527.02 | 0.00 | 0.59 |
Maximum of Months | 0.608403E+10 | 0.761219E+10 | 0.00 | 15102457.62 | 98186489.46 | 0.584625E+09 | 0.676140E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.954801E+10 | 0.00 | 0.00 | 782361.00 | 0.00 | 54318440.48 | 0.106908E+10 | 0.00 | 0.92 |
February | 0.766213E+10 | 0.00 | 0.00 | 2210352.81 | 0.00 | 5962623.07 | 0.247732E+10 | 0.00 | 0.93 |
March | 0.284046E+10 | 0.00 | 0.00 | 10380710.46 | 0.00 | 0.00 | 0.849743E+10 | 0.00 | 1.27 |
April | 0.145650E+10 | 2106306.12 | 0.00 | 15669177.71 | 0.00 | 0.00 | 0.916463E+10 | 0.00 | 1.79 |
May | 0.161035E+10 | 0.140536E+09 | 0.00 | 9415626.88 | 0.00 | 0.00 | 0.506912E+10 | 0.00 | 1.72 |
June | 0.326357E+09 | 0.340248E+10 | 0.00 | 4780403.46 | 35530794.09 | 0.00 | 0.103907E+10 | 0.00 | 1.45 |
July | 22169918.39 | 0.818309E+10 | 0.00 | 374106.15 | 70342915.43 | 0.00 | 34587155.92 | 0.00 | 1.06 |
August | 0.329586E+09 | 0.723289E+10 | 0.00 | 4980943.57 | 60074536.42 | 0.00 | 0.460801E+09 | 0.00 | 1.60 |
September | 0.114203E+10 | 0.177618E+10 | 0.00 | 5566674.91 | 51635942.20 | 0.00 | 0.197294E+10 | 0.00 | 1.45 |
October | 0.153591E+10 | 0.272621E+09 | 0.00 | 8890778.57 | 0.00 | 0.00 | 0.481298E+10 | 0.00 | 1.55 |
November | 0.299475E+10 | 0.00 | 0.00 | 7086066.52 | 0.00 | 0.00 | 0.597800E+10 | 0.00 | 1.14 |
December | 0.398105E+10 | 0.00 | 0.00 | 6712781.12 | 0.00 | 0.00 | 0.592241E+10 | 0.00 | 0.93 |
Annual Sum or Average | 0.334493E+11 | 0.210099E+11 | 0.00 | 76849983.16 | 0.217584E+09 | 60281063.55 | 0.464984E+11 | 0.00 | 1.32 |
Minimum of Months | 22169918.39 | 0.00 | 0.00 | 374106.15 | 0.00 | 0.00 | 34587155.92 | 0.00 | 0.92 |
Maximum of Months | 0.954801E+10 | 0.818309E+10 | 0.00 | 15669177.71 | 70342915.43 | 54318440.48 | 0.916463E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170147E+11 | 0.00 | 0.00 | 0.51 |
February | 0.255759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153273E+11 | 0.00 | 0.00 | 0.50 |
March | 0.412581E+11 | 0.00 | 0.00 | 3973231.89 | 0.00 | 0.340597E+10 | 0.408131E+10 | 0.00 | 0.51 |
April | 0.285285E+11 | 5756539.67 | 0.00 | 25072095.23 | 0.00 | 0.307649E+09 | 0.162261E+11 | 0.00 | 0.57 |
May | 0.168925E+11 | 0.771749E+09 | 0.00 | 58074815.57 | 0.00 | 0.00 | 0.256615E+11 | 0.00 | 0.77 |
June | 0.268221E+10 | 0.218437E+11 | 0.00 | 28972104.18 | 0.356168E+09 | 0.00 | 0.567704E+10 | 0.00 | 0.75 |
July | 86298585.92 | 0.382727E+11 | 0.00 | 3345066.35 | 0.568222E+09 | 0.00 | 0.317972E+09 | 0.00 | 0.63 |
August | 0.138336E+10 | 0.247575E+11 | 0.00 | 26227233.01 | 0.417788E+09 | 0.00 | 0.266299E+10 | 0.00 | 0.75 |
September | 0.968376E+10 | 0.113197E+11 | 0.00 | 34447868.68 | 0.862174E+09 | 0.00 | 0.102486E+11 | 0.00 | 0.69 |
October | 0.221468E+11 | 0.170917E+10 | 0.00 | 25645264.66 | 0.252340E+09 | 1808115.19 | 0.119706E+11 | 0.00 | 0.61 |
November | 0.342456E+11 | 0.00 | 0.00 | 4486388.25 | 0.00 | 0.432512E+10 | 0.528744E+10 | 0.00 | 0.50 |
December | 0.340428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105664E+11 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.241638E+12 | 0.986802E+11 | 0.00 | 0.210244E+09 | 0.245669E+10 | 0.509489E+11 | 0.821336E+11 | 0.00 | 0.61 |
Minimum of Months | 86298585.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.412581E+11 | 0.382727E+11 | 0.00 | 58074815.57 | 0.862174E+09 | 0.170147E+11 | 0.256615E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.340425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187953E+11 | 0.00 | 0.00 | 0.99 |
February | 0.365026E+11 | 0.00 | 0.00 | 63883.53 | 0.00 | 0.145383E+11 | 0.150141E+09 | 0.00 | 0.99 |
March | 0.478102E+11 | 0.00 | 0.00 | 11878652.46 | 0.00 | 0.354961E+10 | 0.114188E+11 | 0.00 | 1.01 |
April | 0.355634E+11 | 4917794.27 | 0.00 | 33289546.81 | 0.00 | 0.675354E+09 | 0.221665E+11 | 0.00 | 1.13 |
May | 0.276675E+11 | 0.715733E+09 | 0.00 | 55066804.39 | 58023962.49 | 0.00 | 0.251234E+11 | 0.00 | 1.40 |
June | 0.356448E+10 | 0.143260E+11 | 0.00 | 28632386.51 | 0.668937E+10 | 0.00 | 0.720140E+10 | 0.00 | 1.20 |
July | 0.133384E+09 | 0.283237E+11 | 0.00 | 3404461.98 | 0.898561E+10 | 0.00 | 0.432890E+09 | 0.00 | 0.94 |
August | 0.214576E+10 | 0.211504E+11 | 0.00 | 25244099.23 | 0.388397E+10 | 0.00 | 0.312680E+10 | 0.00 | 1.21 |
September | 0.138527E+11 | 0.625323E+10 | 0.00 | 31478975.24 | 0.655889E+10 | 0.00 | 0.105108E+11 | 0.00 | 1.20 |
October | 0.264573E+11 | 0.139618E+10 | 0.00 | 26981683.95 | 0.590935E+09 | 6663569.47 | 0.160356E+11 | 0.00 | 1.15 |
November | 0.471296E+11 | 0.00 | 0.00 | 2186759.66 | 0.00 | 0.460042E+10 | 0.363365E+10 | 0.00 | 0.97 |
December | 0.441621E+11 | 0.00 | 0.00 | 14809.09 | 0.00 | 0.121537E+11 | 33372724.11 | 0.00 | 0.94 |
Annual Sum or Average | 0.319032E+12 | 0.721702E+11 | 0.00 | 0.218242E+09 | 0.267668E+11 | 0.543194E+11 | 0.998333E+11 | 0.00 | 1.09 |
Minimum of Months | 0.133384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
Maximum of Months | 0.478102E+11 | 0.283237E+11 | 0.00 | 55066804.39 | 0.898561E+10 | 0.187953E+11 | 0.251234E+11 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258679E+11 | 0.00 | 0.00 | 50488281.04 | 0.00 | 0.106357E+11 | 0.244078E+11 | 0.00 | 0.70 |
February | 0.237408E+11 | 0.00 | 0.00 | 60585130.18 | 0.00 | 0.874381E+10 | 0.301087E+11 | 0.00 | 0.73 |
March | 0.307202E+11 | 0.00 | 0.00 | 88569889.75 | 0.00 | 0.266004E+10 | 0.486009E+11 | 0.00 | 0.82 |
April | 0.273985E+11 | 11883871.23 | 0.00 | 57810450.30 | 0.00 | 0.376823E+09 | 0.342059E+11 | 0.00 | 0.80 |
May | 0.190982E+11 | 0.844378E+09 | 0.00 | 68774335.24 | 5701229.69 | 0.00 | 0.303432E+11 | 0.00 | 0.89 |
June | 0.361029E+10 | 0.228448E+11 | 0.00 | 29612219.41 | 0.100241E+10 | 0.00 | 0.566780E+10 | 0.00 | 0.82 |
July | 0.110728E+09 | 0.414090E+11 | 0.00 | 3157892.52 | 0.104080E+10 | 0.00 | 0.321157E+09 | 0.00 | 0.69 |
August | 0.156595E+10 | 0.303882E+11 | 0.00 | 37844767.43 | 0.458776E+09 | 0.00 | 0.336103E+10 | 0.00 | 0.95 |
September | 0.842135E+10 | 0.148700E+11 | 0.00 | 94001845.25 | 0.859187E+09 | 0.00 | 0.219419E+11 | 0.00 | 1.05 |
October | 0.126847E+11 | 0.401508E+10 | 0.00 | 0.146222E+09 | 68589223.64 | 0.00 | 0.540315E+11 | 0.00 | 1.20 |
November | 0.242563E+11 | 0.00 | 0.00 | 80769472.08 | 0.00 | 0.227344E+10 | 0.475119E+11 | 0.00 | 0.82 |
December | 0.270399E+11 | 0.00 | 0.00 | 62311837.91 | 0.00 | 0.696835E+10 | 0.336667E+11 | 0.00 | 0.69 |
Annual Sum or Average | 0.204515E+12 | 0.114383E+12 | 0.00 | 0.780148E+09 | 0.343547E+10 | 0.316582E+11 | 0.334168E+12 | 0.00 | 0.85 |
Minimum of Months | 0.110728E+09 | 0.00 | 0.00 | 3157892.52 | 0.00 | 0.00 | 0.321157E+09 | 0.00 | 0.69 |
Maximum of Months | 0.307202E+11 | 0.414090E+11 | 0.00 | 0.146222E+09 | 0.104080E+10 | 0.106357E+11 | 0.540315E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.358568E+11 | 0.00 | 0.00 | 1019493.25 | 0.00 | 0.169306E+11 | 0.133055E+10 | 0.00 | 1.01 |
February | 0.358565E+11 | 0.00 | 0.00 | 3481806.99 | 0.00 | 0.142196E+11 | 0.288423E+10 | 0.00 | 1.02 |
March | 0.492630E+11 | 0.00 | 0.00 | 20290086.96 | 0.00 | 0.317593E+10 | 0.144814E+11 | 0.00 | 1.08 |
April | 0.396864E+11 | 4526281.89 | 0.00 | 33841526.92 | 162397.29 | 98598204.86 | 0.217399E+11 | 0.00 | 1.21 |
May | 0.274938E+11 | 0.876024E+09 | 0.00 | 46428333.76 | 18661020.37 | 0.00 | 0.249757E+11 | 0.00 | 1.41 |
June | 0.445141E+10 | 0.203187E+11 | 0.00 | 24507701.90 | 0.291533E+10 | 0.00 | 0.539005E+10 | 0.00 | 1.27 |
July | 0.171242E+09 | 0.338749E+11 | 0.00 | 2117858.64 | 0.569301E+10 | 0.00 | 0.232445E+09 | 0.00 | 0.99 |
August | 0.227880E+10 | 0.272135E+11 | 0.00 | 25346513.41 | 0.843137E+09 | 0.00 | 0.235838E+10 | 0.00 | 1.32 |
September | 0.151796E+11 | 0.933843E+10 | 0.00 | 28682899.73 | 0.412627E+10 | 0.00 | 0.936893E+10 | 0.00 | 1.25 |
October | 0.323337E+11 | 0.207325E+10 | 0.00 | 25042555.55 | 0.374402E+09 | 0.00 | 0.126355E+11 | 0.00 | 1.23 |
November | 0.492639E+11 | 0.00 | 0.00 | 4087598.32 | 0.00 | 0.326017E+10 | 0.446986E+10 | 0.00 | 1.00 |
December | 0.468292E+11 | 0.00 | 0.00 | 700276.85 | 0.00 | 0.964794E+10 | 0.124741E+10 | 0.00 | 0.96 |
Annual Sum or Average | 0.338664E+12 | 0.936994E+11 | 0.00 | 0.215547E+09 | 0.139710E+11 | 0.473329E+11 | 0.101114E+12 | 0.00 | 1.15 |
Minimum of Months | 0.171242E+09 | 0.00 | 0.00 | 700276.85 | 0.00 | 0.00 | 0.232445E+09 | 0.00 | 0.96 |
Maximum of Months | 0.492639E+11 | 0.338749E+11 | 0.00 | 46428333.76 | 0.569301E+10 | 0.169306E+11 | 0.249757E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621076E+10 | 0.00 | 0.00 | 0.58 |
February | 0.272560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599469E+10 | 0.00 | 0.00 | 0.58 |
March | 0.578709E+10 | 0.00 | 0.00 | 130152.10 | 0.00 | 0.223472E+10 | 0.192134E+09 | 0.00 | 0.61 |
April | 0.398074E+10 | 148908.01 | 0.00 | 1792794.67 | 0.00 | 0.725832E+09 | 0.118603E+10 | 0.00 | 0.64 |
May | 0.217713E+10 | 0.107195E+09 | 0.00 | 5002110.01 | 2028994.50 | 21528569.00 | 0.235085E+10 | 0.00 | 0.81 |
June | 0.334104E+09 | 0.279789E+10 | 0.00 | 2979424.74 | 0.168253E+09 | 0.00 | 0.630974E+09 | 0.00 | 0.77 |
July | 10071070.96 | 0.702020E+10 | 0.00 | 343654.47 | 0.186963E+09 | 0.00 | 34552422.29 | 0.00 | 0.63 |
August | 0.155587E+09 | 0.544762E+10 | 0.00 | 2856635.15 | 0.150866E+09 | 0.00 | 0.293969E+09 | 0.00 | 0.77 |
September | 0.107548E+10 | 0.133386E+10 | 0.00 | 2917102.00 | 0.290050E+09 | 0.00 | 0.952033E+09 | 0.00 | 0.71 |
October | 0.268775E+10 | 0.126389E+09 | 0.00 | 1558024.71 | 55625684.53 | 0.212273E+09 | 0.694440E+09 | 0.00 | 0.63 |
November | 0.435370E+10 | 0.00 | 0.00 | 30715.49 | 0.00 | 0.222066E+10 | 55459076.50 | 0.00 | 0.59 |
December | 0.337137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489547E+10 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.294229E+11 | 0.168333E+11 | 0.00 | 17610613.35 | 0.853787E+09 | 0.225159E+11 | 0.639044E+10 | 0.00 | 0.66 |
Minimum of Months | 10071070.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.578709E+10 | 0.702020E+10 | 0.00 | 5002110.01 | 0.290050E+09 | 0.621076E+10 | 0.235085E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.446821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558410E+10 | 0.00 | 0.00 | 1.01 |
February | 0.490804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484584E+10 | 0.00 | 0.00 | 1.02 |
March | 0.697425E+10 | 0.00 | 0.00 | 499565.74 | 0.00 | 0.156920E+10 | 0.825437E+09 | 0.00 | 1.08 |
April | 0.412015E+10 | 133172.14 | 0.00 | 2885883.80 | 0.00 | 0.698750E+09 | 0.201748E+10 | 0.00 | 1.14 |
May | 0.258255E+10 | 0.100331E+09 | 0.00 | 5853969.81 | 6485308.63 | 6307333.51 | 0.265040E+10 | 0.00 | 1.40 |
June | 0.312196E+09 | 0.206541E+10 | 0.00 | 3149835.07 | 0.639425E+09 | 0.00 | 0.810888E+09 | 0.00 | 1.18 |
July | 13479950.99 | 0.549325E+10 | 0.00 | 389372.05 | 0.105051E+10 | 0.00 | 46116194.90 | 0.00 | 0.92 |
August | 0.163636E+09 | 0.483305E+10 | 0.00 | 2956396.64 | 0.459016E+09 | 0.00 | 0.367502E+09 | 0.00 | 1.21 |
September | 0.124559E+10 | 0.931070E+09 | 0.00 | 2908127.71 | 0.669419E+09 | 0.00 | 0.103164E+10 | 0.00 | 1.18 |
October | 0.270853E+10 | 0.113601E+09 | 0.00 | 1959618.53 | 73990137.93 | 0.166874E+09 | 0.120343E+10 | 0.00 | 1.11 |
November | 0.552395E+10 | 0.00 | 0.00 | 15129.71 | 0.00 | 0.190314E+10 | 95725514.65 | 0.00 | 1.03 |
December | 0.474732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463997E+10 | 0.00 | 0.00 | 1.01 |
Annual Sum or Average | 0.377679E+11 | 0.135368E+11 | 0.00 | 20617899.06 | 0.289884E+10 | 0.194142E+11 | 0.904862E+10 | 0.00 | 1.11 |
Minimum of Months | 13479950.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
Maximum of Months | 0.697425E+10 | 0.549325E+10 | 0.00 | 5853969.81 | 0.105051E+10 | 0.558410E+10 | 0.265040E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.465067E+10 | 0.00 | 0.00 | 2556565.65 | 0.00 | 0.366596E+10 | 0.297392E+10 | 0.00 | 0.73 |
February | 0.483175E+10 | 0.00 | 0.00 | 3346298.09 | 0.00 | 0.308974E+10 | 0.360252E+10 | 0.00 | 0.77 |
March | 0.543272E+10 | 0.00 | 0.00 | 6096553.57 | 0.00 | 0.142597E+10 | 0.485192E+10 | 0.00 | 0.89 |
April | 0.390776E+10 | 304130.90 | 0.00 | 4881948.79 | 0.00 | 0.698563E+09 | 0.302731E+10 | 0.00 | 0.85 |
May | 0.243527E+10 | 0.117593E+09 | 0.00 | 6047719.19 | 3170548.33 | 28246517.71 | 0.287729E+10 | 0.00 | 0.94 |
June | 0.401999E+09 | 0.289781E+10 | 0.00 | 3096703.79 | 0.293490E+09 | 0.00 | 0.676244E+09 | 0.00 | 0.84 |
July | 11710060.14 | 0.753252E+10 | 0.00 | 343432.46 | 0.344251E+09 | 0.00 | 36254814.33 | 0.00 | 0.69 |
August | 0.168717E+09 | 0.659997E+10 | 0.00 | 4029246.70 | 0.170164E+09 | 0.00 | 0.404061E+09 | 0.00 | 0.96 |
September | 0.928608E+09 | 0.193858E+10 | 0.00 | 8736935.51 | 0.234401E+09 | 0.00 | 0.222947E+10 | 0.00 | 1.06 |
October | 0.175725E+10 | 0.332341E+09 | 0.00 | 10906667.54 | 23197250.21 | 0.105846E+09 | 0.471995E+10 | 0.00 | 1.17 |
November | 0.418058E+10 | 0.00 | 0.00 | 4679050.84 | 0.00 | 0.118724E+10 | 0.373847E+10 | 0.00 | 0.84 |
December | 0.484040E+10 | 0.00 | 0.00 | 2729990.22 | 0.00 | 0.294804E+10 | 0.288858E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.335474E+11 | 0.194191E+11 | 0.00 | 57451112.35 | 0.106867E+10 | 0.131496E+11 | 0.320260E+11 | 0.00 | 0.87 |
Minimum of Months | 11710060.14 | 0.00 | 0.00 | 343432.46 | 0.00 | 0.00 | 36254814.33 | 0.00 | 0.69 |
Maximum of Months | 0.543272E+10 | 0.753252E+10 | 0.00 | 10906667.54 | 0.344251E+09 | 0.366596E+10 | 0.485192E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.506217E+10 | 0.00 | 0.00 | 34035.02 | 0.00 | 0.570702E+10 | 0.137717E+09 | 0.00 | 1.09 |
February | 0.532528E+10 | 0.00 | 0.00 | 240443.47 | 0.00 | 0.495087E+10 | 0.321343E+09 | 0.00 | 1.11 |
March | 0.741214E+10 | 0.00 | 0.00 | 1601648.61 | 0.00 | 0.144261E+10 | 0.159613E+10 | 0.00 | 1.21 |
April | 0.515821E+10 | 110330.19 | 0.00 | 3091417.78 | 0.00 | 0.417975E+09 | 0.211352E+10 | 0.00 | 1.29 |
May | 0.314870E+10 | 0.108834E+09 | 0.00 | 4479737.44 | 4337561.86 | 1152831.72 | 0.241961E+10 | 0.00 | 1.49 |
June | 0.458816E+09 | 0.251663E+10 | 0.00 | 2589040.43 | 0.472945E+09 | 0.00 | 0.643121E+09 | 0.00 | 1.28 |
July | 24183979.93 | 0.604792E+10 | 0.00 | 425429.61 | 0.100677E+10 | 0.00 | 19076642.39 | 0.00 | 0.97 |
August | 0.204954E+09 | 0.562332E+10 | 0.00 | 2714075.95 | 0.291708E+09 | 0.00 | 0.290216E+09 | 0.00 | 1.31 |
September | 0.158358E+10 | 0.117647E+10 | 0.00 | 2658557.16 | 0.581600E+09 | 0.00 | 0.880981E+09 | 0.00 | 1.28 |
October | 0.337102E+10 | 0.156101E+09 | 0.00 | 2237098.99 | 73977024.14 | 0.150313E+09 | 0.106153E+10 | 0.00 | 1.25 |
November | 0.598683E+10 | 0.00 | 0.00 | 231380.26 | 0.00 | 0.193089E+10 | 0.252741E+09 | 0.00 | 1.12 |
December | 0.608540E+10 | 0.00 | 0.00 | 5016.51 | 0.00 | 0.407662E+10 | 25644247.91 | 0.00 | 1.10 |
Annual Sum or Average | 0.438213E+11 | 0.156294E+11 | 0.00 | 20307881.24 | 0.243134E+10 | 0.186774E+11 | 0.976163E+10 | 0.00 | 1.21 |
Minimum of Months | 24183979.93 | 0.00 | 0.00 | 5016.51 | 0.00 | 0.00 | 19076642.39 | 0.00 | 0.97 |
Maximum of Months | 0.741214E+10 | 0.604792E+10 | 0.00 | 4479737.44 | 0.100677E+10 | 0.570702E+10 | 0.241961E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:00:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 96954699.62 | 0.00 | 0.00 | 0.239927E+09 | 0.00 | 0.00 | 0.174283E+11 | 0.00 | 0.32 |
February | 11932938.95 | 0.00 | 0.00 | 0.426421E+09 | 0.00 | 0.00 | 0.173435E+11 | 0.00 | 0.32 |
March | 0.00 | 311353.90 | 0.00 | 0.771964E+09 | 0.00 | 0.00 | 0.148377E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.842525E+09 | 0.00 | 0.00 | 0.899177E+10 | 0.00 | 0.32 |
May | 0.00 | 0.198577E+09 | 0.00 | 0.187478E+09 | 0.00 | 0.00 | 0.488772E+10 | 0.00 | 0.33 |
June | 0.00 | 0.358980E+10 | 0.00 | 0.110310E+09 | 0.00 | 0.00 | 0.768243E+09 | 0.00 | 0.34 |
July | 0.00 | 0.815776E+10 | 0.00 | 10311644.87 | 0.00 | 0.00 | 10932927.06 | 0.00 | 0.31 |
August | 0.00 | 0.607180E+10 | 0.00 | 0.175489E+09 | 0.00 | 0.00 | 0.308390E+09 | 0.00 | 0.35 |
September | 0.00 | 0.201411E+10 | 0.00 | 0.116059E+09 | 0.00 | 0.00 | 0.207945E+10 | 0.00 | 0.32 |
October | 0.00 | 0.357322E+09 | 0.00 | 0.328540E+09 | 0.00 | 0.00 | 0.535497E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.669115E+09 | 0.00 | 0.00 | 0.116293E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.965697E+09 | 0.00 | 0.00 | 0.159741E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.108888E+09 | 0.203897E+11 | 0.00 | 0.484384E+10 | 0.00 | 0.00 | 0.996144E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10311644.87 | 0.00 | 0.00 | 10932927.06 | 0.00 | 0.31 |