Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:57
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2020-06-03 19:57:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33977.91 | 733.54 | 733.54 |
Net Site Energy | 33977.91 | 733.54 | 733.54 |
Total Source Energy | 104158.26 | 2248.65 | 2248.65 |
Net Source Energy | 104158.26 | 2248.65 | 2248.65 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1077.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4113.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 884.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2044.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2804.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 577.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1191.97 | 0.00 | 0.00 | 0.00 | 0.00 | 6245.93 |
Humidification | 1197.53 | 0.00 | 0.00 | 0.00 | 0.00 | 445.48 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 578.45 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32321.75 | 1656.16 | 0.00 | 0.00 | 0.00 | 8971.58 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 1077.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1074.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 3038.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 884.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2804.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 577.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 105.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1086.81 | 0.00 | 0.00 | 0.00 | 0.00 | 6245.93 | |
Humidification | General | 1197.53 | 0.00 | 0.00 | 0.00 | 0.00 | 445.48 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 578.45 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 213.42 | 35.75 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 697.79 | 35.75 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 213.42 | 35.75 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 697.79 | 35.75 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32321.750 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32321.750 | 100.00 |
Total On-Site and Utility Electric Sources | 32321.750 | 100.00 |
Total Electricity End Uses | 32321.750 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8971.58 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8971.58 | 100.00 |
Total Water End Uses | 8971.58 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.50 |
Time Setpoint Not Met During Occupied Cooling | 694.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2065.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:57 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.6875 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.6875 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:00 | 22-DEC-07:10 | - | - | - | 28-JUN-15:00 |
Heating | 0.00 | 1226334.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 435306.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 92996.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186178.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 57764.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 84388.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 34190.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2058154.05 | 1234480.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 1226334.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 233336.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 186178.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 57764.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 35139.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 34190.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1168.24 | 0.00 | 0.00 | 0.00 |
Cooling | 13028.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13600.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2800.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6473.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8882.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1829.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3774.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3792.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 627.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 102362.98 | 1795.28 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.22 | 0.00 | 0.00 | 0.00 |
Cooling | 281.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 81.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.54 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2209.89 | 38.76 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.22 | 0.00 | 0.00 | 0.00 |
Cooling | 281.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 81.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.54 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2209.89 | 38.76 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 7.07 |
DATACENTER BOT DIRECT AIR | 0.578104 |
DATACENTER MID DIRECT AIR | 5.52 |
DATACENTER TOP DIRECT AIR | 0.565227 |
DATACENTER BASEMENT DIRECT AIR | 25.93 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.28 | 0.261264 | 0.300000 | 2.18 | 0.696703 | 0.500000 | 0.001458 | 0.000400 | 2.18 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 68.48 | 0.277755 | 0.300000 | 20.54 | 0.740680 | 0.500000 | 0.001372 | 0.007877 | 20.54 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.04 | 0.270364 | 0.300000 | 2.11 | 0.720970 | 0.500000 | 0.001409 | 0.001747 | 2.86 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.15 | 0.208012 | 0.300000 | 0.344432 | 0.554700 | 0.500000 | 0.001832 | 0.000151 | 0.344432 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.34 | 0.114754 | 0.300000 | 0.402353 | 0.306010 | 0.500000 | 0.003320 | 0.000142 | 0.402353 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.23 | 0.193608 | 0.300000 | 0.370066 | 0.516288 | 0.500000 | 0.001968 | 0.000205 | 0.370066 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.67 | 0.092010 | 0.300000 | 0.501811 | 0.300000 | 0.500000 | 0.004141 | 0.000127 | 0.501811 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.54 | 0.226560 | 0.300000 | 3.16 | 0.604159 | 0.500000 | 0.001682 | 0.003548 | 5.82 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.95 | 0.110347 | 0.300000 | 4.18 | 0.300000 | 0.500000 | 0.003453 | 0.002427 | 4.18 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.48 | 0.208087 | 0.300000 | 3.44 | 0.554898 | 0.500000 | 0.001831 | 0.003546 | 5.82 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.75 | 0.104319 | 0.300000 | 4.43 | 0.300000 | 0.500000 | 0.003652 | 0.002341 | 4.43 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.24 | 0.192345 | 0.300000 | 0.372488 | 0.512919 | 0.500000 | 0.001981 | 0.000479 | 0.785856 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.41 | 0.109401 | 0.300000 | 0.422040 | 0.300000 | 0.500000 | 0.003483 | 0.000317 | 0.519785 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.34 | 0.178857 | 0.300000 | 0.400587 | 0.476951 | 0.500000 | 0.002130 | 0.000478 | 0.784161 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.60 | 0.096485 | 0.300000 | 0.478536 | 0.300000 | 0.500000 | 0.003949 | 0.000302 | 0.495968 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18087.08 | 0.000400 | 314.81 |
CORE_MID VAV BOX REHEAT COIL | 356536.56 | 0.007877 | 6743.46 |
CORE_TOP VAV BOX REHEAT COIL | 79083.63 | 0.001747 | 1650.68 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6832.06 | 0.000151 | 132.01 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6417.32 | 0.000142 | 120.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9256.51 | 0.000205 | 187.93 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5758.01 | 0.000127 | 104.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 160571.47 | 0.003548 | 3350.01 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 109842.40 | 0.002427 | 2258.99 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 160486.05 | 0.003546 | 3348.23 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 105968.74 | 0.002341 | 2128.47 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21666.51 | 0.000479 | 451.95 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14330.11 | 0.000317 | 298.91 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21619.86 | 0.000478 | 450.98 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13674.49 | 0.000302 | 285.24 |
CAV_BAS_HEATC | 290913.37 | 0.006427 | 5356.30 |
VAV_BOT WITH REHEAT_HEATC | 53863.87 | 0.001190 | 783.27 |
VAV_MID WITH REHEAT_HEATC | 445148.00 | 0.009835 | 6568.20 |
VAV_TOP WITH REHEAT_HEATC | 45331.23 | 0.001002 | 674.18 |
DATACENTER_EXTRAWATERHEATC | 1034979.96 | 0.022867 | 19249.32 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 7.07 | 7.07 | 7.07 | 7.07 | 7.07 | 7.07 | 1.00 | 1.00 | 7.07 |
VAV_BOT WITH REHEAT | 6.34 | 3.80 | 12.68 | 3.80 | 11.72 | 11.72 | 0.300000 | 0.324374 | 11.72 |
VAV_MID WITH REHEAT | 59.60 | 35.76 | 119.20 | 35.76 | 109.08 | 109.08 | 0.300000 | 0.327833 | 109.08 |
VAV_TOP WITH REHEAT | 6.31 | 3.78 | 12.61 | 5.45 | 11.86 | 11.86 | 0.300000 | 0.459217 | 11.86 |
AIRLOOP DATACENTER BASEMENT | 25.93 | 25.93 | 25.93 | 25.93 | 25.93 | 25.93 | 1.00 | 1.00 | 25.93 |
AIRLOOP DATACENTER BOT | 0.578104 | 0.578104 | 0.578104 | 0.578104 | 0.578104 | 0.578104 | 1.00 | 1.00 | 0.578104 |
AIRLOOP DATACENTER MID | 5.52 | 5.52 | 5.52 | 5.52 | 5.52 | 5.52 | 1.00 | 1.00 | 5.52 |
AIRLOOP DATACENTER TOP | 0.565227 | 0.565227 | 0.565227 | 0.565227 | 0.565227 | 0.565227 | 1.00 | 1.00 | 0.565227 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 7.07 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.72 | 2.39 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 109.08 | 24.76 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.86 | 2.47 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 25.93 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.578104 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 5.52 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.565227 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 107608.27 | 0.004578 | 7.07 | 0.007127 | 25.76 | 6.67 | 10.98 | 0.007127 |
VAV_BOT WITH REHEAT_COOLC | 187037.90 | 0.007957 | 11.72 | 0.006974 | 26.37 | 6.67 | 10.98 | 0.006974 |
VAV_MID WITH REHEAT_COOLC | 1781763.50 | 0.075800 | 109.08 | 0.006942 | 26.75 | 6.67 | 10.98 | 0.006942 |
VAV_TOP WITH REHEAT_COOLC | 187927.44 | 0.007995 | 11.86 | 0.006967 | 26.26 | 6.67 | 10.98 | 0.006967 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 7.07 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.004578 | 0.000104 |
CAV_BAS_HEATC_CONTROLLER | 0.006427 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007957 | 0.000060 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001190 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.075800 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009835 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007995 | 0.000060 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001002 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022867 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.72 |
VAV_MID WITH REHEAT FAN | 109.08 |
VAV_TOP WITH REHEAT FAN | 11.86 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 25.93 | 473991.07 | 250951.86 | 0.011608 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.578104 | 10261.57 | 5487.74 | 0.000251 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 5.52 | 97922.74 | 52355.95 | 0.002398 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.565227 | 10034.32 | 5365.64 | 0.000246 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.93 | 25.93 | 25.93 | 25.93 | 473991.07 | 473991.07 | 16130.54 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.578104 | 0.578104 | 0.578104 | 0.578104 | 10261.57 | 10261.57 | 745.16 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.52 | 5.52 | 5.52 | 5.52 | 97922.74 | 97922.74 | 7451.64 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.565227 | 0.565227 | 0.565227 | 0.565227 | 10034.32 | 10034.32 | 745.16 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 25.93 |
DATACENTER BOT SUPPLY FAN | 0.578104 |
DATACENTER MID SUPPLY FAN | 5.52 |
DATACENTER TOP SUPPLY FAN | 0.565227 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 25.93 | 473991.07 | 0.011608 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.578104 | 10261.57 | 0.000251 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 5.52 | 97922.74 | 0.002398 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.565227 | 10034.32 | 0.000246 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 16130.54 | |
DATACENTER_EXTRAELECHEATC | 473991.07 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 745.16 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 7451.64 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 745.16 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000140 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.096330 | 23071.89 |
HEATSYS1 PUMP | 0.065406 | 16710.32 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.096330 | 11.56 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.065406 | 7.85 |
COOLSYS1_SUPPLY | 0.096330 | 11.56 |
SINGLE WATER PLANT LOOP | 0.014503 | 1.74 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.096330 | 0.096330 | 404345.91 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 PUMP | 0.096330 | 7690.63 |
PLANT CIRC PUMP | 0.014503 | 3699.04 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2960367.24 | 1480183.62 | 0.065406 |
DUMMY BOILER | 597406.57 | 93894.07 | 0.014503 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.096330 | 0.048524 | 1143403.95 | 1148827.18 | 0.057068 |
COOLSYS1 CHILLER2 | 0.096330 | 0.048524 | 1143403.95 | 1148827.18 | 0.057068 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014503 | 139666.47 | 55270.72 | 69833.23 | 7879.72 | 20989.95 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.114137 | 13.70 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.114137 | 29159.23 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 56.22 | 1091800.85 | 11.24 | 136475.11 |
TOWERWATERSYS COOLTOWER 2 | 56.22 | 1091800.85 | 11.24 | 136475.11 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.047240 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.688 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.529 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 9.688 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 26925.749 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26925.749 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 7591.909 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7591.909 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
51 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
52 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
53 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
54 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
55 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
56 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
57 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
58 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
59 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 80490.67658 | 80490.67658 | 7.07074 | 7.07074 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.65324E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 82887.29740 | 82887.29740 | 7.28017 | 7.28017 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.65324E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 779823.21497 | 779823.21497 | 68.47920 | 68.47920 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.65324E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 186404.70039 | 186404.70039 | 9.73280 | 10.77757 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 79420.97148 | 79420.97148 | 7.03513 | 7.03513 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.65324E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 55378.82296 | 55378.82296 | 2.86240 | 2.86240 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12961.45794 | 12961.45794 | 1.14811 | 1.14811 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.65324E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3986.44651 | 3986.44651 | 0.20520 | 0.20520 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15141.25224 | 15141.25224 | 1.34118 | 1.34118 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 26.39250 | 5.65324E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3091.50356 | 3091.50356 | 0.15935 | 0.15935 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13926.10193 | 13926.10193 | 1.23355 | 1.23355 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.65324E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6195.38253 | 6195.38253 | 0.31998 | 0.31998 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18884.07444 | 18884.07444 | 1.67270 | 1.67270 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1619.12705 | 1619.12705 | 8.31288E-002 | 8.72074E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 119004.08367 | 119004.08367 | 10.54118 | 10.54118 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.65324E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 112386.56721 | 112386.56721 | 5.82062 | 5.82062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 157460.43847 | 157460.43847 | 13.94743 | 13.94743 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.65324E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 75203.28456 | 75203.28456 | 3.89537 | 3.89537 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 129571.73502 | 129571.73502 | 11.47723 | 11.47723 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.65324E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 112326.88189 | 112326.88189 | 5.81752 | 5.81752 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 166557.92375 | 166557.92375 | 14.75327 | 14.75327 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.98500 | 5.65324E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 69331.40644 | 69331.40644 | 3.59020 | 3.59020 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14017.34418 | 14017.34418 | 1.24163 | 1.24163 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15160.25630 | 15160.25630 | 0.78586 | 0.78586 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15882.19891 | 15882.19891 | 1.40680 | 1.40680 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.65324E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10026.71640 | 10026.71640 | 0.51978 | 0.51978 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15074.76825 | 15074.76825 | 1.33529 | 1.33529 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15127.64573 | 15127.64573 | 0.78416 | 0.78416 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18008.26899 | 18008.26899 | 1.59512 | 1.59512 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9568.34764 | 9568.34764 | 0.49597 | 0.49597 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8275.49741 | 8275.49741 | 0.57810 | 0.57810 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.65325E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90000 | 2.34317E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78948.22501 | 78948.22501 | 5.51512 | 5.51512 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.65324E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90000 | 2.34317E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8091.16399 | 8091.16399 | 0.56523 | 0.56523 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.65325E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90000 | 2.34317E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371212.41122 | 371212.41122 | 25.93192 | 25.93192 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 22.02750 | 5.65325E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90000 | 2.34317E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 82323.72 | 7.07074 | 7.07074 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 57209.18 | 1.20008 | 1.20008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 147411.08 | 11.72324 | 11.72324 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 38101.51 | 1.84949 | 1.84949 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1352671.35 | 109.07829 | 109.07829 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 510045.61 | 29.90128 | 29.90128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 21:10:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 158160.37 | 11.86406 | 11.86406 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 50193.57 | 5.44817 | 5.44817 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368600.87 | 25.93192 | 25.93192 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16130.54 | 0.33837 | 0.33837 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8224.46 | 0.57810 | 0.57810 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.16 | 1.56314E-002 | 1.56314E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78474.75 | 5.51512 | 5.51512 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7451.64 | 0.15631 | 0.15631 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8042.47 | 0.56523 | 0.56523 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.16 | 1.56314E-002 | 1.56314E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.07074 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.28017 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26126 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.18405 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69670 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45830E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.99612E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.18405 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18087.07834 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.99612E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.81025 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 68.47920 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27775 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 20.54376 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74068 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37171E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.87724E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.54376 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 356536.55847 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.87724E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6743.45781 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.03513 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27036 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.11054 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72097 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40921E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74726E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.86240 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 79083.62570 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74726E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1650.68163 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14811 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20801 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34443 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55470 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83162E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50946E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34443 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6832.06254 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50946E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 132.01464 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34118 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11475 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40235 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30601 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32015E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41783E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40235 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6417.32393 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41783E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 120.00205 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23355 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19361 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37007 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51629 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96789E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04511E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37007 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9256.51185 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04511E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 187.93061 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.67270 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.20097E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50181 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.14087E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27216E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50181 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5758.00735 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27216E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 104.26210 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.54118 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22656 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.16236 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60416 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68168E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.54763E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.82062 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160571.47155 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.54763E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3350.01391 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.94743 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11035 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.18423 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45276E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.42683E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.18423 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 109842.40348 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.42683E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2258.98756 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.47723 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20809 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.44317 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55490 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83097E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.54574E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.81752 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160486.04580 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.54574E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3348.23314 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.75327 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10432 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.42598 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65225E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.34125E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.42598 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105968.74022 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34125E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2128.47032 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24163 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19234 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37249 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51292 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98082E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.78695E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78586 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21666.51119 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.78695E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 451.95052 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40680 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10940 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42204 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48261E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16606E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51978 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14330.11063 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16606E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.91345 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33529 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17886 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40059 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47695 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13020E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.77664E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78416 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21619.86053 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.77664E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 450.97798 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59512 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.64849E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47854 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.94881E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.02121E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49597 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13674.49396 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02121E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 285.24406 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57810 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.51512 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56523 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.93192 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.07074 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.07074 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.07074 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 7.07074 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.07074 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.07074 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.33786 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.80271 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.67571 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.80271 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.72324 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.72324 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32437 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.59915 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 35.75949 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 119.19831 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 35.75949 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 109.07829 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 109.07829 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32783 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.30698 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.78419 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.61397 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.44817 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.86406 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.86406 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45922 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.93192 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.93192 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.93192 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.93192 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.93192 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.93192 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57810 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57810 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57810 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57810 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57810 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.57810 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.51512 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.51512 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.51512 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.51512 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.51512 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.51512 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56523 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56523 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56523 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56523 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56523 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.56523 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.07074 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.72324 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 109.07829 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.86406 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.93192 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.57810 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.51512 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.56523 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.07074 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 107608.26753 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.57790E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 7.07074 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 7.12740E-003 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 25.75526 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.97805 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 7.12740E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 290913.36834 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.42738E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 5356.29778 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 7.07074 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.57790E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.04019E-004 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.42738E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.72324 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.39275 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 187037.90177 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.95702E-003 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 11.72324 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 6.97358E-003 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.37370 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.97753 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 6.97358E-003 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 53863.87059 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.19006E-003 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 783.26921 |
318 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.72324 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.95702E-003 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.98453E-005 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.19006E-003 |
322 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 109.07829 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 24.76162 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 1781763.50070 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.58003E-002 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 109.07829 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 6.94195E-003 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.75175 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.97743 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 6.94195E-003 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 445148.00300 |
333 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 9.83500E-003 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 6568.20193 |
335 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 109.07829 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.58003E-002 |
337 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.28217E-006 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.83500E-003 |
339 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.86406 |
340 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.46531 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 187927.44343 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.99487E-003 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 11.86406 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 6.96665E-003 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.26040 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.97751 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 6.96665E-003 |
349 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 45331.23319 |
350 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.00154E-003 |
351 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 674.17945 |
352 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.86406 |
353 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.99487E-003 |
354 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.95620E-005 |
355 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.00154E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.93192 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 25.93192 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 473991.07040 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 250951.85812 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.16080E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.93192 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.93192 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.93192 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.93192 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 473991.07040 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 473991.07040 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16130.54010 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.93192 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 25.93192 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 473991.07040 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.16080E-002 |
374 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 16130.54010 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.40257E-004 |
376 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 473991.07040 |
380 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
381 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1034979.95926 |
382 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.28666E-002 |
383 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19249.32131 |
384 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.28666E-002 |
385 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.08247E-005 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57810 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.57810 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 10261.56738 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 5487.74144 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.51305E-004 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57810 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57810 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57810 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57810 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10261.56738 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10261.56738 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.16413 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
399 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57810 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.57810 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 10261.56738 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.51305E-004 |
403 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 745.16413 |
404 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.51512 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 5.51512 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 97922.73634 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 52355.94580 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.39812E-003 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.51512 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.51512 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.51512 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.51512 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 97922.73634 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 97922.73634 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7451.64128 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.51512 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 5.51512 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 97922.73634 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.39812E-003 |
421 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 7451.64128 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56523 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.56523 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 10034.31850 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 5365.64388 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.45740E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56523 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56523 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56523 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56523 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10034.31850 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10034.31850 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.16413 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56523 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.56523 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 10034.31850 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.45740E-004 |
439 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 745.16413 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.63301E-002 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 23071.89229 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.63301E-002 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.55962 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.63301E-002 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.63301E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 404345.91311 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
448 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
449 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
450 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
451 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
452 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
453 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.54057E-002 |
454 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 7.84868 |
455 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.54057E-002 |
456 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 16710.31682 |
457 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2960367.23991 |
458 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1480183.62000 |
459 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.54057E-002 |
460 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.63301E-002 |
461 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.55962 |
462 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.63301E-002 |
463 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 7690.63076 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.63301E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.85239E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1143403.95195 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1148827.18000 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.70685E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.63301E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.85239E-002 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1143403.95195 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1148827.18000 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.70685E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.45032E-002 |
475 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.74038 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.45032E-002 |
477 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3699.03547 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.45032E-002 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55270.72147 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20989.94904 |
484 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 597406.56652 |
485 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
486 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.45032E-002 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11414 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.69643 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11414 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29159.23098 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 56.22262 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1091800.84879 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.24452 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 136475.10610 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 56.22262 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1091800.84879 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.24452 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 136475.10610 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.72400E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.72400E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17163.01 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 338561.00 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 75069.66 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6487.24 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6094.08 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8787.11 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5469.28 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 152421.58 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 104269.34 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 152340.49 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 100603.83 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20566.82 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13602.78 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20522.54 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12980.44 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 230098.18 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 41867.38 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 353134.76 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 36347.63 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 831064.52 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 167486.10 | 104003.12 | 63482.99 | 0.62 | 22077.33 | 223.92 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 291965.55 | 178223.89 | 113741.66 | 0.61 | 41365.07 | 419.55 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2740024.96 | 1666939.53 | 1073085.43 | 0.61 | 384510.58 | 3899.92 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 294689.42 | 180076.04 | 114613.38 | 0.61 | 41876.71 | 424.74 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.89 | 23.50 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.89 | 23.50 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 25 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2293659812 | 0.2676988599 | Pass | Pass | 1.1457692398 | 3.1413497800 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1191252730 | 0.1985080252 | Pass | Pass | 0.1609412501 | 0.3651107120 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.4247494886E-002 | 0.1371694706 | Pass | Pass | 0.1329035177 | 0.3375157501 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.2735896689E-002 | 7.2223737227E-002 | Pass | Pass | 0.1752671486 | 0.3779603185 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1100300690 | 0.1816546260 | Pass | Pass | 0.1608282428 | 0.3635471829 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2282169164 | 0.3507940767 | Fail | Pass | 0.1640612343 | 0.3683559544 | Pass | Fail |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2687704089 | 0.4701638059 | Pass | Pass | 0.1799882321 | 0.3961550113 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2298908110 | 0.4067490809 | Pass | Pass | 0.1617905892 | 0.3594987946 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.8352283513E-002 | 9.3339303337E-002 | Pass | Pass | 0.1323636625 | 0.3327545890 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1779528895 | 0.2538310997 | Pass | Pass | 0.1375934317 | 0.3438514148 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3019286300 | 0.5030218197 | Pass | Pass | 0.1868858474 | 0.4805053207 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1591771230 | 0.2599030965 | Pass | Pass | 0.1324447497 | 0.3299734218 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.4495679620E-002 | 0.1152838365 | Pass | Pass | 0.3251762362 | 1.4354965720 | Fail | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1308994360 | 0.1591233817 | Pass | Pass | 0.2688162451 | 0.9227999189 | Fail | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2339307541 | 0.2486175832 | Pass | Pass | 0.1797282121 | 0.3830025113 | Pass | Fail |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1469293094 | 0.1947828620 | Fail | Pass | 0.1794122287 | 0.3787514770 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3690143892E-002 | 2.5334295658E-002 | Pass | Pass | 0.2085766573 | 0.4653536562 | Fail | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.1872989522E-002 | 2.5760166603E-002 | Pass | Pass | 0.6292083835 | 3.4045480922 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1029243055 | 7.9177060556E-002 | Pass | Pass | 0.1790350994 | 0.3755581217 | Pass | Fail |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.6381957519E-014 | 1.5954892566E-014 | Pass | Pass | 6.7541824638E-003 | 9.3286941860E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.3652786745E-015 | 7.5582191831E-015 | Pass | Pass | 3.0483843981E-002 | 2.3873196652E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.5303100765E-002 | 3.9017837283E-002 | Pass | Pass | 9.1154093491E-002 | 0.2729324009 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1538274502 | 1.4579828388 | Pass | Pass | 1.5325673885 | 6.3691156564 | Pass | Fail |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 1043.06 | 2.159 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 9.6875 | 2779.43 | 26925.75 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 257.68 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
CORE_MID_LIGHTS | CORE_MID | 9.6875 | 24961.20 | 241812.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 2314.14 |
CORE_TOP_LIGHTS | CORE_TOP | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 9.6875 | 3134.13 | 30361.93 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 9.6875 | 3134.20 | 30362.59 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 9.6875 | 783.68 | 7591.91 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 72.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 9.6875 | 362.03 | 3507.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 33.56 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
Interior Lighting Total | 9.6875 | 46320.38 | 448729.56 | 1321.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 56280.71 | AstronomicalClock | - | 83.71 | 83.71 | 884.33 | |
Exterior Lighting Total | 56280.71 | 884.33 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2259129.81 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1480183.62 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1148827.18 | 6.11 | 6.89 | 23.50 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1148827.18 | 6.11 | 6.89 | 23.50 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1091800.85 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1091800.85 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 107608.27 | 167486.10 | 104003.12 | 63482.99 | 0.62 | - | 22077.33 | 223.92 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 187037.90 | 291965.55 | 178223.89 | 113741.66 | 0.61 | - | 41365.07 | 419.55 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 1781763.50 | 2740024.96 | 1666939.53 | 1073085.43 | 0.61 | - | 384510.58 | 3899.92 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 187927.44 | 294689.42 | 180076.04 | 114613.38 | 0.61 | - | 41876.71 | 424.74 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 473991.07 | 250951.86 | 223039.21 | 0.53 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10261.57 | 5487.74 | 4773.83 | 0.53 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 97922.74 | 52355.95 | 45566.79 | 0.53 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10034.32 | 5365.64 | 4668.67 | 0.53 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18087.08 | 17163.01 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 356536.56 | 338561.00 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 79083.63 | 75069.66 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6832.06 | 6487.24 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6417.32 | 6094.08 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9256.51 | 8787.11 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5758.01 | 5469.28 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 160571.47 | 152421.58 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 109842.40 | 104269.34 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 160486.05 | 152340.49 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 105968.74 | 100603.83 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21666.51 | 20566.82 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14330.11 | 13602.78 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21619.86 | 20522.54 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13674.49 | 12980.44 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 290913.37 | 230098.18 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 53863.87 | 41867.38 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 445148.00 | 353134.76 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 45331.23 | 36347.63 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 473991.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 10261.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 97922.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 10034.32 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 16130.54 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1034979.96 | 831064.52 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 745.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 7451.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 745.16 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 7.07 | 12989.81 | 1837.12 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.72 | 26630.44 | 2271.59 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 109.08 | 247781.50 | 2271.59 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.86 | 26950.31 | 2271.59 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.93 | 42768.14 | 1649.25 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 647.54 | 1120.11 | 1.00 | 1.54 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.52 | 6177.52 | 1120.11 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 633.12 | 1120.11 | 1.00 | 1.55 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.096330 | 23071.89 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.065406 | 16710.32 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.096330 | 7690.63 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014503 | 3699.04 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.114137 | 29159.23 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 80490.68 | 80490.68 | 28.96 | 7.071 | 7.071 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 25.11 | 0.00565 | 1.200 | 0.00 |
CORE_BOTTOM | 82887.30 | 82887.30 | 33.21 | 7.280 | 7.280 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 25.11 | 0.00565 | 1.078 | 0.00 |
CORE_MID | 779823.21 | 779823.21 | 312.41 | 68.479 | 68.479 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 25.11 | 0.00565 | 10.778 | 0.00 |
CORE_TOP | 79420.97 | 79420.97 | 31.82 | 7.035 | 7.035 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00738 | 35.10 | 0.00565 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12961.46 | 12961.46 | 41.36 | 1.148 | 1.148 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00728 | 35.10 | 0.00565 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15141.25 | 15141.25 | 74.97 | 1.341 | 1.341 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.00 | 24.00 | 0.00716 | 26.39 | 0.00565 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13926.10 | 13926.10 | 44.43 | 1.234 | 1.234 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00727 | 35.10 | 0.00565 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18884.07 | 18884.07 | 93.50 | 1.673 | 1.673 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00713 | 33.21 | 0.00565 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 119004.08 | 119004.08 | 379.70 | 10.541 | 10.541 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00730 | 35.10 | 0.00565 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 157460.44 | 157460.44 | 779.60 | 13.947 | 13.947 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00714 | 27.68 | 0.00565 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 129571.74 | 129571.74 | 413.41 | 11.477 | 11.477 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00727 | 35.10 | 0.00565 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 166557.92 | 166557.92 | 824.65 | 14.753 | 14.753 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00714 | 32.98 | 0.00565 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14017.34 | 14017.34 | 44.72 | 1.242 | 1.242 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00725 | 35.10 | 0.00565 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15882.20 | 15882.20 | 78.63 | 1.407 | 1.407 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00714 | 28.44 | 0.00565 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15074.77 | 15074.77 | 48.10 | 1.335 | 1.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00723 | 35.10 | 0.00565 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18008.27 | 18008.27 | 89.16 | 1.595 | 1.595 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00712 | 33.21 | 0.00565 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8275.50 | 8275.50 | 228.59 | 0.578 | 0.578 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00700 | 30.51 | 0.00565 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78948.23 | 78948.23 | 2180.73 | 5.515 | 5.515 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00700 | 30.17 | 0.00565 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8091.16 | 8091.16 | 223.50 | 0.565 | 0.565 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00700 | 30.51 | 0.00565 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371212.41 | 371212.41 | 473.68 | 25.932 | 25.932 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 27.00 | 27.00 | 0.00700 | 22.03 | 0.00565 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 | |
CORE_MID | 186404.70 | 186404.70 | 74.68 | 9.733 | 10.778 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 55378.82 | 55378.82 | 22.19 | 2.862 | 2.862 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3986.45 | 3986.45 | 12.72 | 0.205 | 0.205 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00683 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3091.50 | 3091.50 | 15.31 | 0.159 | 0.159 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00709 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6195.38 | 6195.38 | 19.77 | 0.320 | 0.320 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1619.13 | 1619.13 | 8.02 | 0.083 | 0.087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00590 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 112386.57 | 112386.57 | 358.59 | 5.821 | 5.821 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 75203.28 | 75203.28 | 372.34 | 3.895 | 3.895 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 112326.88 | 112326.88 | 358.39 | 5.818 | 5.818 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 69331.41 | 69331.41 | 343.27 | 3.590 | 3.590 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15160.26 | 15160.26 | 48.37 | 0.786 | 0.786 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10026.72 | 10026.72 | 49.64 | 0.520 | 0.520 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15127.65 | 15127.65 | 48.27 | 0.784 | 0.784 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9568.35 | 9568.35 | 47.37 | 0.496 | 0.496 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -7.90 | 0.00234 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -7.90 | 0.00234 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -7.90 | 0.00234 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 7.07 | 7.07 | 1.20 | 1.20 | 7.0707 | 7.0707 | 7.0707 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 11.72 | 11.72 | 1.85 | 1.85 | 11.7232 | 3.8027 | 11.7232 | 0.3244 | 0.3000 |
VAV_MID WITH REHEAT | 109.08 | 109.08 | 29.90 | 29.90 | 109.0783 | 35.7595 | 109.0783 | 0.3278 | 0.3000 |
VAV_TOP WITH REHEAT | 11.86 | 11.86 | 5.45 | 5.45 | 11.8641 | 5.4482 | 11.8641 | 0.4592 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 25.93 | 25.93 | 0.34 | 0.34 | 25.9319 | 25.9319 | 25.9319 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.58 | 0.58 | 0.02 | 0.02 | 0.5781 | 0.5781 | 0.5781 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.52 | 5.52 | 0.16 | 0.16 | 5.5151 | 5.5151 | 5.5151 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.57 | 0.57 | 0.02 | 0.02 | 0.5652 | 0.5652 | 0.5652 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18087.078 | 18087.078 | 2.184050 | 0.00039961 | 314.810 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17163.01 | 18087.08 | 2.184050 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 18159.84 | 18159.84 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 356536.558 | 356536.558 | 20.543759 | 0.00787724 | 6743.458 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 338561.00 | 356536.56 | 20.543759 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 186404.70 | 0.00 | 358236.64 | 358236.64 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 79083.626 | 79083.626 | 2.862402 | 0.00174726 | 1650.682 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 75069.66 | 79083.63 | 2.862402 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 55378.82 | 0.00 | 79444.70 | 79444.70 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6832.063 | 6832.063 | 0.344432 | 0.00015095 | 132.015 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6487.24 | 6832.06 | 0.344432 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00682559 | 36.3644 | 3986.45 | 0.00 | 6864.49 | 6864.49 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6417.324 | 6417.324 | 0.402353 | 0.00014178 | 120.002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6094.08 | 6417.32 | 0.402353 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00709433 | 37.7798 | 3091.50 | 0.00 | 6448.11 | 6448.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9256.512 | 9256.512 | 0.370066 | 0.00020451 | 187.931 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8787.11 | 9256.51 | 0.370066 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00745698 | 39.6870 | 6195.38 | 0.00 | 9298.84 | 9298.84 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5758.007 | 5758.007 | 0.501811 | 0.00012722 | 104.262 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5469.28 | 5758.01 | 0.501811 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00590425 | 31.5019 | 1619.13 | 0.00 | 5786.66 | 5786.66 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 160571.472 | 160571.472 | 5.820622 | 0.00354763 | 3350.014 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 152421.58 | 160571.47 | 5.820622 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00783652 | 41.6800 | 112386.57 | 0.00 | 161304.54 | 161304.54 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 109842.403 | 109842.403 | 4.184229 | 0.00242683 | 2258.988 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 104269.34 | 109842.40 | 4.184229 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00784654 | 41.7325 | 75203.28 | 0.00 | 110343.70 | 110343.70 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 160486.046 | 160486.046 | 5.817517 | 0.00354574 | 3348.233 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 152340.49 | 160486.05 | 5.817517 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00783620 | 41.6783 | 112326.88 | 0.00 | 161218.73 | 161218.73 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 105968.740 | 105968.740 | 4.425980 | 0.00234125 | 2128.470 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 100603.83 | 105968.74 | 4.425980 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00780874 | 41.5343 | 69331.41 | 0.00 | 106460.83 | 106460.83 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21666.511 | 21666.511 | 0.785856 | 0.00047870 | 451.951 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20566.82 | 21666.51 | 0.785856 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788599 | 41.9395 | 15160.26 | 0.00 | 21765.42 | 21765.42 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14330.111 | 14330.111 | 0.519785 | 0.00031661 | 298.913 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13602.78 | 14330.11 | 0.519785 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788595 | 41.9393 | 10026.72 | 0.00 | 14395.53 | 14395.53 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21619.861 | 21619.861 | 0.784161 | 0.00047766 | 450.978 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20522.54 | 21619.86 | 0.784161 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788567 | 41.9378 | 15127.65 | 0.00 | 21718.56 | 21718.56 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13674.494 | 13674.494 | 0.495968 | 0.00030212 | 285.244 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12980.44 | 13674.49 | 0.495968 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00787845 | 41.9000 | 9568.35 | 0.00 | 13736.92 | 13736.92 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 107608.268 | -999.000 | 7.070743 | 0.00457790 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 107608.27 | 107608.27 | 7.070743 | 25.76 | 13.82 | 0.00712740 | 10.98 | 8.11 | 0.00712740 | 33.34 | 0.00565324 | 15.14 | 16.9725 | 24.00 | 0.00742917 | 32.9516 | 72081.04 | 0.00 | 109763.06 | 109763.06 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 290913.368 | 290913.368 | 7.070743 | 0.00642738 | 5356.298 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 230098.18 | 290913.37 | 7.070743 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 16.9725 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 242564.99 | 242564.99 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 187037.902 | -999.000 | 11.723244 | 0.00795702 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 187037.90 | 187037.90 | 11.723244 | 26.37 | 13.90 | 0.00697358 | 10.98 | 8.84 | 0.00697358 | 34.83 | 0.00565324 | 15.62 | 20.4103 | 24.00 | 0.00730004 | 32.3851 | 123191.00 | 0.00 | 192903.79 | 192903.79 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53863.871 | 53863.871 | 3.516973 | 0.00119006 | 783.269 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41867.38 | 53863.87 | 3.516973 | -7.90 | -7.90 | 0.00234317 | 12.80 | 9.85 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 68.0344 | 21.00 | 0.00759890 | 40.4316 | 14892.46 | 0.00 | 44264.46 | 44264.46 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1781763.501 | -999.000 | 109.078289 | 0.07580034 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1781763.50 | 1781763.50 | 109.078289 | 26.75 | 14.01 | 0.00694195 | 10.98 | 8.80 | 0.00694195 | 34.83 | 0.00565324 | 15.62 | 22.7008 | 24.00 | 0.00731558 | 32.4532 | 1099792.30 | 0.00 | 1831823.50 | 1831823.50 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 445148.003 | 445148.003 | 32.723487 | 0.00983500 | 6568.202 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 21:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353134.76 | 445148.00 | 32.723487 | -7.89 | -7.89 | 0.00234502 | 12.80 | 9.85 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 75.6693 | 21.00 | 0.00789335 | 41.9779 | 368571.59 | 0.00 | 373435.89 | 373435.89 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 187927.443 | -999.000 | 11.864056 | 0.00799487 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 187927.44 | 187927.44 | 11.864056 | 26.26 | 13.86 | 0.00696665 | 10.98 | 8.83 | 0.00696665 | 34.83 | 0.00565324 | 15.62 | 20.7797 | 24.00 | 0.00729364 | 32.3569 | 133616.59 | 0.00 | 193690.83 | 193690.83 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 45331.233 | 45331.233 | 3.559217 | 0.00100154 | 674.179 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36347.63 | 45331.23 | 3.559217 | -6.71 | -6.89 | 0.00249171 | 12.80 | 9.85 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 69.2655 | 21.00 | 0.00794515 | 42.2494 | 51564.64 | 0.00 | 38437.26 | 38437.26 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 473991.070 | 250951.858 | 25.931922 | 0.01160801 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 556330.59 | 556330.59 | -999.0 | 28.80 | 14.72 | 0.00698240 | 12.80 | 8.84 | 0.00698240 | 35.10 | 0.00565324 | 15.70 | -999.0000 | 27.00 | 0.00700000 | 25.9964 | 370604.35 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10261.567 | 5487.741 | 0.578104 | 0.00025131 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 12115.92 | 12115.92 | -999.0 | 28.25 | 14.53 | 0.00696359 | 12.80 | 8.83 | 0.00696359 | 30.51 | 0.00565325 | 14.20 | -999.0000 | 27.00 | 0.00700000 | 25.9964 | 8275.50 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97922.736 | 52355.946 | 5.515115 | 0.00239812 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 115617.93 | 115617.93 | -999.0 | 28.25 | 14.53 | 0.00696182 | 12.80 | 8.82 | 0.00696182 | 30.51 | 0.00565325 | 14.20 | -999.0000 | 27.00 | 0.00700000 | 25.9964 | 78936.43 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10034.319 | 5365.644 | 0.565227 | 0.00024574 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 11847.59 | 11847.59 | -999.0 | 28.25 | 14.53 | 0.00696276 | 12.80 | 8.82 | 0.00696276 | 30.51 | 0.00565325 | 14.20 | -999.0000 | 27.00 | 0.00700000 | 25.9964 | 8091.16 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 473991.070 | 473991.070 | 25.931922 | 0.01160801 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 473991.07 | 473991.07 | 25.931922 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3048 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10261.567 | 10261.567 | 0.578104 | 0.00025131 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10261.57 | 10261.57 | 0.578104 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7039 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97922.736 | 97922.736 | 5.515115 | 0.00239812 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 97922.74 | 97922.74 | 5.515115 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8343 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10034.319 | 10034.319 | 0.565227 | 0.00024574 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10034.32 | 10034.32 | 0.565227 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7655 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16130.540 | 16130.540 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16130.54 | 16130.54 | 25.931922 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3048 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1254475.27 | 25.931922 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3048 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1034979.959 | 1034979.959 | 25.931922 | 0.02286662 | 19249.321 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 831064.52 | 1034979.96 | 25.931922 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3048 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.164 | 745.164 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.16 | 745.16 | 0.578104 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7039 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7451.641 | 7451.641 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7451.64 | 7451.64 | 5.515115 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8343 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.164 | 745.164 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.16 | 745.16 | 0.565227 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7655 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18087.078 | 18087.078 | 2.184050 | 0.00039961 | 314.810 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.5683 | 0.610974 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17163.01 | 18087.08 | 1.0000 | 2.16310304 | 2.184050 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.39957113 | 60.00 | 49.00 | 11.00 | 0.000 | 17163.01 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 18159.84 | 18159.84 | 2.16310304 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 356536.558 | 356536.558 | 20.543759 | 0.00787724 | 6743.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 11.2108 | 12.043660 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 338561.00 | 356536.56 | 1.0000 | 20.34672114 | 20.543759 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 7.87643603 | 60.00 | 49.00 | 11.00 | 0.000 | 338561.00 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.03 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 186404.70 | 0.00 | 358236.64 | 358236.64 | 20.34672114 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 30.07 | 18.04 | 0.00800000 | 50666.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 79083.626 | 79083.626 | 2.862402 | 0.00174726 | 1650.682 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 2.4858 | 2.671413 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 75069.66 | 79083.63 | 1.0000 | 2.83494824 | 2.862402 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 1.74707784 | 60.00 | 49.00 | 11.00 | 0.000 | 75069.66 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 55378.82 | 0.00 | 79444.70 | 79444.70 | 2.83494824 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.28 | 21.23 | 0.00800000 | 61083.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6832.063 | 6832.063 | 0.344432 | 0.00015095 | 132.015 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.2148 | 0.230784 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6487.24 | 6832.06 | 1.0000 | 0.34112883 | 0.344432 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.15093068 | 60.00 | 49.00 | 11.00 | 0.000 | 6487.24 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.87 | 0.00682559 | 21.00 | 0.00682559 | 36.3644 | 3986.45 | 0.00 | 6864.49 | 6864.49 | 0.34112883 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 32.53 | 18.84 | 0.00800000 | 53182.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6417.324 | 6417.324 | 0.402353 | 0.00014178 | 120.002 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.2018 | 0.216775 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6094.08 | 6417.32 | 1.0000 | 0.39849419 | 0.402353 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.14176847 | 60.00 | 49.00 | 11.00 | 0.000 | 6094.08 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.86 | 0.00709433 | 21.00 | 0.00709433 | 37.7798 | 3091.50 | 0.00 | 6448.11 | 6448.11 | 0.39849419 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.67 | 17.57 | 0.00800000 | 49241.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9256.512 | 9256.512 | 0.370066 | 0.00020451 | 187.931 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.2910 | 0.312681 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8787.11 | 9256.51 | 1.0000 | 0.36651655 | 0.370066 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.20449046 | 60.00 | 49.00 | 11.00 | 0.000 | 8787.11 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00745698 | 21.00 | 0.00745698 | 39.6870 | 6195.38 | 0.00 | 9298.84 | 9298.84 | 0.36651655 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 37.68 | 20.46 | 0.00800000 | 58430.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5758.007 | 5758.007 | 0.501811 | 0.00012722 | 104.262 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.1811 | 0.194503 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5469.28 | 5758.01 | 1.0000 | 0.49699844 | 0.501811 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.12720316 | 60.00 | 49.00 | 11.00 | 0.000 | 5469.28 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.88 | 0.00590425 | 21.00 | 0.00590425 | 31.5019 | 1619.13 | 0.00 | 5786.66 | 5786.66 | 0.49699844 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 24.22 | 16.02 | 0.00800000 | 44703.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160571.472 | 160571.472 | 5.820622 | 0.00354763 | 3350.014 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 5.0472 | 5.424039 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 152421.58 | 160571.47 | 1.0000 | 5.76479553 | 5.820622 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 3.54726856 | 60.00 | 49.00 | 11.00 | 0.000 | 152421.58 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00783652 | 21.00 | 0.00783652 | 41.6800 | 112386.57 | 0.00 | 161304.54 | 161304.54 | 5.76479553 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61040.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 109842.403 | 109842.403 | 4.184229 | 0.00242683 | 2258.988 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 3.4527 | 3.710432 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 104269.34 | 109842.40 | 1.0000 | 4.14409803 | 4.184229 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 2.42658612 | 60.00 | 49.00 | 11.00 | 0.000 | 104269.34 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784654 | 21.00 | 0.00784654 | 41.7325 | 75203.28 | 0.00 | 110343.70 | 110343.70 | 4.14409803 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 38.91 | 20.83 | 0.00800000 | 59686.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160486.046 | 160486.046 | 5.817517 | 0.00354574 | 3348.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 5.0445 | 5.421153 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 152340.49 | 160486.05 | 1.0000 | 5.76172019 | 5.817517 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 3.54538138 | 60.00 | 49.00 | 11.00 | 0.000 | 152340.49 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00783620 | 21.00 | 0.00783620 | 41.6783 | 112326.88 | 0.00 | 161218.73 | 161218.73 | 5.76172019 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61040.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105968.740 | 105968.740 | 4.425980 | 0.00234125 | 2128.470 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 3.3313 | 3.579581 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 100603.83 | 105968.74 | 1.0000 | 4.38352978 | 4.425980 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 2.34101100 | 60.00 | 49.00 | 11.00 | 0.000 | 100603.83 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00780874 | 21.00 | 0.00780874 | 41.5343 | 69331.41 | 0.00 | 106460.83 | 106460.83 | 4.38352978 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 36.62 | 20.13 | 0.00800000 | 57346.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21666.511 | 21666.511 | 0.785856 | 0.00047870 | 451.951 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.6810 | 0.731886 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20566.82 | 21666.51 | 1.0000 | 0.77831882 | 0.785856 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.47864626 | 60.00 | 49.00 | 11.00 | 0.000 | 20566.82 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788599 | 21.00 | 0.00788599 | 41.9395 | 15160.26 | 0.00 | 21765.42 | 21765.42 | 0.77831882 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61024.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14330.111 | 14330.111 | 0.519785 | 0.00031661 | 298.913 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.4504 | 0.484065 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13602.78 | 14330.11 | 1.0000 | 0.51479930 | 0.519785 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.31657399 | 60.00 | 49.00 | 11.00 | 0.000 | 13602.78 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788595 | 21.00 | 0.00788595 | 41.9393 | 10026.72 | 0.00 | 14395.53 | 14395.53 | 0.51479930 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61023.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21619.861 | 21619.861 | 0.784161 | 0.00047766 | 450.978 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.6796 | 0.730310 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20522.54 | 21619.86 | 1.0000 | 0.77663976 | 0.784161 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.47761567 | 60.00 | 49.00 | 11.00 | 0.000 | 20522.54 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788567 | 21.00 | 0.00788567 | 41.9378 | 15127.65 | 0.00 | 21718.56 | 21718.56 | 0.77663976 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61024.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13674.494 | 13674.494 | 0.495968 | 0.00030212 | 285.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 0.4298 | 0.461919 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12980.44 | 13674.49 | 1.0000 | 0.49121133 | 0.495968 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 0.30209042 | 60.00 | 49.00 | 11.00 | 0.000 | 12980.44 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787845 | 21.00 | 0.00787845 | 41.9000 | 9568.35 | 0.00 | 13736.92 | 13736.92 | 0.49121133 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.2 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 107608.268 | -999.000 | 7.070743 | 0.00457790 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0895 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 7.070743 | 7.00292652 | 4197.9300 | 999.8980 | 96.32030861 | 12.27 | 6.67 | 5.60 | 2264337.11 | 4.7523 | 4.752308 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 107608.27 | 107608.27 | 1.0000 | 7.00292652 | 7.070743 | 25.76 | 13.82 | 0.00712740 | 44046.4 | 10.98 | 8.11 | 0.00712740 | 28680.6 | 4.57743747 | 6.67 | 10.65 | 5.60 | 12989.814 | 94618.45 | 33.34 | 0.00565324 | 15.14 | 1.20008137 | 16.9725 | 24.00 | 0.00746861 | 24.00 | 0.00742917 | 32.9516 | 72081.04 | 0.00 | 109763.06 | 109763.06 | 7.00292652 | 25.76 | 15.80 | 0.00712740 | 44046.4 | 10.36 | 9.61 | 0.00712740 | 28372.5 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 290913.368 | 290913.368 | 7.070743 | 0.00642738 | 5356.298 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 7.070743 | 7.00292652 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 7.6193 | 9.826935 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 230098.18 | 290913.37 | 1.0000 | 7.00292652 | 7.070743 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 6.42671974 | 60.00 | 49.00 | 11.00 | 0.000 | 230098.18 | -7.90 | 0.00234317 | -7.90 | 1.20008137 | 16.9725 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 242564.99 | 242564.99 | 7.00292652 | 12.80 | 2.51 | 0.00039769 | 13866.0 | 47.25 | 17.48 | 0.00039769 | 48503.7 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 187037.902 | -999.000 | 11.723244 | 0.00795702 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8035 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.723244 | 11.61080471 | 4197.9300 | 999.8980 | 96.32030861 | 12.27 | 6.67 | 5.60 | 2264337.11 | 8.2602 | 8.260161 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 187037.90 | 187037.90 | 1.0000 | 11.61080471 | 11.723244 | 26.37 | 13.90 | 0.00697358 | 44283.8 | 10.98 | 8.84 | 0.00697358 | 30468.4 | 7.95621302 | 6.67 | 10.65 | 5.60 | 26630.441 | 160407.46 | 34.83 | 0.00565324 | 15.62 | 2.39275000 | 20.4103 | 24.00 | 0.00734441 | 24.00 | 0.00730004 | 32.3851 | 123191.00 | 0.00 | 192903.79 | 192903.79 | 11.61080471 | 26.37 | 15.89 | 0.00697358 | 44283.8 | 10.05 | 9.30 | 0.00697358 | 27669.6 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53863.871 | 53863.871 | 3.516973 | 0.00119006 | 783.269 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.723244 | 11.61080471 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 1.3864 | 1.819500 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41867.38 | 53863.87 | 1.0000 | 3.48324141 | 3.516973 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 1.18993500 | 60.00 | 49.00 | 11.00 | 0.000 | 41867.38 | -7.90 | 0.00234317 | -7.90 | 2.39275000 | 68.0344 | 8.71 | 0.00293705 | 21.00 | 0.00759890 | 40.4316 | 14892.46 | 0.00 | 44264.46 | 44264.46 | 3.48324141 | 12.80 | 5.36 | 0.00253301 | 19257.1 | 25.39 | 11.22 | 0.00253301 | 31965.0 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1781763.501 | -999.000 | 109.078289 | 0.07580034 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7447 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 109.078289 | 108.03210722 | 4197.9300 | 999.8980 | 96.32030861 | 12.27 | 6.67 | 5.60 | 2264337.11 | 78.6881 | 78.688084 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1781763.50 | 1781763.50 | 1.0000 | 108.03210722 | 109.078289 | 26.75 | 14.01 | 0.00694195 | 44587.9 | 10.98 | 8.80 | 0.00694195 | 30388.5 | 75.79260581 | 6.67 | 10.65 | 5.60 | 247781.502 | 1533982.00 | 34.83 | 0.00565324 | 15.62 | 24.76162000 | 22.7008 | 24.00 | 0.00738115 | 24.00 | 0.00731558 | 32.4532 | 1099792.30 | 0.00 | 1831823.50 | 1831823.50 | 108.03210722 | 26.75 | 16.00 | 0.00694195 | 44587.9 | 10.09 | 9.29 | 0.00694195 | 27631.6 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 445148.003 | 445148.003 | 32.723487 | 0.00983500 | 6568.202 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 109.078289 | 108.03210722 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 11.6934 | 15.036918 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 21:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353134.76 | 445148.00 | 1.0000 | 32.40963217 | 32.723487 | -7.89 | -7.89 | 0.00234502 | -2097.8 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 9.83399791 | 60.00 | 49.00 | 11.00 | 0.000 | 353134.76 | -7.90 | 0.00234317 | -7.90 | 24.76162000 | 75.6693 | 21.00 | 0.00766610 | 21.00 | 0.00789335 | 41.9779 | 368571.59 | 0.00 | 373435.89 | 373435.89 | 32.40963217 | 12.80 | 6.73 | 0.00363828 | 22047.6 | 24.19 | 11.87 | 0.00363828 | 33570.0 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 187927.443 | -999.000 | 11.864056 | 0.00799487 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7907 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.864056 | 11.75026674 | 4197.9300 | 999.8980 | 96.32030861 | 12.27 | 6.67 | 5.60 | 2264337.11 | 8.2994 | 8.299446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 187927.44 | 187927.44 | 1.0000 | 11.75026674 | 11.864056 | 26.26 | 13.86 | 0.00696665 | 44150.8 | 10.98 | 8.83 | 0.00696665 | 30450.9 | 7.99405232 | 6.67 | 10.65 | 5.60 | 26950.310 | 160977.13 | 34.83 | 0.00565324 | 15.62 | 2.46531000 | 20.7797 | 24.00 | 0.00731328 | 24.00 | 0.00729364 | 32.3569 | 133616.59 | 0.00 | 193690.83 | 193690.83 | 11.75026674 | 26.26 | 15.84 | 0.00696665 | 44150.8 | 10.06 | 9.30 | 0.00696665 | 27666.8 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 45331.233 | 45331.233 | 3.559217 | 0.00100154 | 674.179 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.864056 | 11.75026674 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 1.2036 | 1.531271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36347.63 | 45331.23 | 1.0000 | 3.52508002 | 3.559217 | -6.71 | -6.89 | 0.00249171 | -546.4 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 1.00143604 | 60.00 | 49.00 | 11.00 | 0.000 | 36347.63 | -7.90 | 0.00234317 | -7.90 | 2.46531000 | 69.2655 | 17.81 | 0.00556454 | 21.00 | 0.00794515 | 42.2494 | 51564.64 | 0.00 | 38437.26 | 38437.26 | 3.52508002 | 12.80 | 6.36 | 0.00333324 | 21277.5 | 23.58 | 11.30 | 0.00333324 | 32181.4 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 473991.070 | 250951.858 | 25.931922 | 0.01160801 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8199 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 556330.59 | 556330.59 | 0.8520 | -999.0 | -999.0 | 28.80 | 14.72 | 0.00698240 | 46776.2 | 12.80 | 8.84 | 0.00698240 | 30490.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 556330.59 | 35.10 | 0.00565324 | 15.70 | 0.33837161 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 370604.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10261.567 | 5487.741 | 0.578104 | 0.00025131 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.7850 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 12115.92 | 12115.92 | 0.8469 | -999.0 | -999.0 | 28.25 | 14.53 | 0.00696359 | 46163.6 | 12.80 | 8.83 | 0.00696359 | 30443.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12115.92 | 30.51 | 0.00565325 | 14.20 | 0.01563137 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 8275.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 97922.736 | 52355.946 | 5.515115 | 0.00239812 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.7817 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 115617.93 | 115617.93 | 0.8470 | -999.0 | -999.0 | 28.25 | 14.53 | 0.00696182 | 46163.8 | 12.80 | 8.82 | 0.00696182 | 30438.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 115617.93 | 30.51 | 0.00565325 | 14.20 | 0.15631366 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 78936.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10034.319 | 5365.644 | 0.565227 | 0.00024574 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.7834 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 11847.59 | 11847.59 | 0.8469 | -999.0 | -999.0 | 28.25 | 14.53 | 0.00696276 | 46163.7 | 12.80 | 8.82 | 0.00696276 | 30441.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11847.59 | 30.51 | 0.00565325 | 14.20 | 0.01563137 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 8091.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 473991.070 | 473991.070 | 25.931922 | 0.01160801 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 473991.07 | 473991.07 | 1.0000 | 25.68320582 | 25.931922 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 473991.07 | -7.90 | 0.00234317 | -7.90 | 0.33837161 | 1.3048 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10261.567 | 10261.567 | 0.578104 | 0.00025131 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10261.57 | 10261.57 | 1.0000 | 0.57255980 | 0.578104 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10261.57 | -7.90 | 0.00234317 | -7.90 | 0.01563137 | 2.7039 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97922.736 | 97922.736 | 5.515115 | 0.00239812 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 97922.74 | 97922.74 | 1.0000 | 5.46221907 | 5.515115 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97922.74 | -7.90 | 0.00234317 | -7.90 | 0.15631366 | 2.8343 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10034.319 | 10034.319 | 0.565227 | 0.00024574 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10034.32 | 10034.32 | 1.0000 | 0.55980626 | 0.565227 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10034.32 | -7.90 | 0.00234317 | -7.90 | 0.01563137 | 2.7655 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16130.540 | 16130.540 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.931922 | 25.68320582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16130.54 | 16130.54 | 1.0000 | 25.68320582 | 25.931922 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16130.54 | -7.90 | 0.00234317 | -7.90 | 0.33837161 | 1.3048 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.931922 | 25.68320582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1254475.27 | 1.0000 | 25.68320582 | 25.931922 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -7.90 | 0.00234317 | -7.90 | 0.33837161 | 1.3048 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1034979.959 | 1034979.959 | 25.931922 | 0.02286662 | 19249.321 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.931922 | 25.68320582 | 4197.9300 | 999.8980 | 65.39902473 | 71.00 | 82.00 | 11.00 | 3019945.81 | 27.5192 | 34.961202 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 831064.52 | 1034979.96 | 1.0000 | 25.68320582 | 25.931922 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | 22.86428489 | 60.00 | 49.00 | 11.00 | 0.000 | 831064.52 | -7.90 | 0.00234317 | -7.90 | 0.33837161 | 1.3048 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68320582 | 16.60 | 4.07 | 0.00003057 | 16757.8 | 16.60 | 4.07 | 0.00003057 | 16757.8 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.164 | 745.164 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.578104 | 0.57255980 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.16 | 745.16 | 1.0000 | 0.57255980 | 0.578104 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.16 | -7.90 | 0.00234317 | -7.90 | 0.01563137 | 2.7039 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7451.641 | 7451.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.515115 | 5.46221907 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7451.64 | 7451.64 | 1.0000 | 5.46221907 | 5.515115 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7451.64 | -7.90 | 0.00234317 | -7.90 | 0.15631366 | 2.8343 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.164 | 745.164 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.565227 | 0.55980626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.16 | 745.16 | 1.0000 | 0.55980626 | 0.565227 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.16 | -7.90 | 0.00234317 | -7.90 | 0.01563137 | 2.7655 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 51.2608 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 7.07 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.39 | 11.72 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 24.76 | 109.08 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.47 | 11.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2544.50 | 1106.83 | 249.33 |
CORE_BOTTOM | 2202.83 | 942.33 | 1.17 |
CORE_MID | 1573.83 | 2458.33 | 4.83 |
CORE_TOP | 1909.33 | 3263.67 | 324.50 |
PERIMETER_BOT_ZN_3 | 1788.83 | 2999.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 1893.83 | 3090.00 | 98.00 |
PERIMETER_BOT_ZN_1 | 2596.17 | 1992.67 | 121.67 |
PERIMETER_BOT_ZN_4 | 2717.33 | 1819.67 | 123.83 |
PERIMETER_MID_ZN_3 | 2052.83 | 3661.67 | 587.17 |
PERIMETER_MID_ZN_2 | 1771.50 | 3102.33 | 449.83 |
PERIMETER_MID_ZN_1 | 2540.50 | 2453.00 | 369.83 |
PERIMETER_MID_ZN_4 | 1873.50 | 3643.00 | 368.00 |
PERIMETER_TOP_ZN_3 | 2780.83 | 3904.00 | 1420.17 |
PERIMETER_TOP_ZN_2 | 2729.50 | 3585.50 | 1063.00 |
PERIMETER_TOP_ZN_1 | 2618.50 | 2808.50 | 639.17 |
PERIMETER_TOP_ZN_4 | 2386.00 | 3904.33 | 956.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4771.83 | 4863.00 | 2065.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 157.50 | 0.00 | 11.83 |
CORE_BOTTOM | 0.00 | 3.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 24.17 | 0.00 | 24.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 447.50 | 0.00 | 447.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 62.50 | 0.00 | 27.67 |
PERIMETER_MID_ZN_3 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 1.33 | 22.33 | 0.00 | 22.33 |
PERIMETER_MID_ZN_1 | 0.67 | 558.50 | 0.00 | 558.50 |
PERIMETER_MID_ZN_4 | 0.67 | 21.00 | 0.00 | 12.50 |
PERIMETER_TOP_ZN_3 | 29.83 | 1.83 | 3.50 | 1.33 |
PERIMETER_TOP_ZN_2 | 24.33 | 25.50 | 0.33 | 25.33 |
PERIMETER_TOP_ZN_1 | 16.67 | 287.50 | 0.67 | 287.17 |
PERIMETER_TOP_ZN_4 | 15.00 | 22.00 | 0.00 | 13.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 402.33 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 345.83 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 285.33 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 981.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 30.83 | 1808.67 | 3.50 | 694.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.662 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.145 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.923 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.861 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 1.138 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.930 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.609 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.448 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.960 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.874 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.498 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.973 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 1.069 | 0.124 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.969 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.558 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 2.089 | 0.129 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
Electricity:Building | 19507.65 | 254949.54 | 01-JAN-06:10 | 1167329.12 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 682.08 | 14702.05 | 01-JAN-06:10 | 35858.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 257.68 | 1244.51 | 01-JAN-06:10 | 22401.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 552.69 | 7160.52 | 01-JAN-06:10 | 38246.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5526.92 | 71604.96 | 01-JAN-06:10 | 382463.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2314.15 | 11176.56 | 01-JAN-06:10 | 201178.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 552.69 | 7160.50 | 01-JAN-06:10 | 38246.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 693.98 | 8991.05 | 01-JAN-06:10 | 48023.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 290.56 | 1403.33 | 01-JAN-06:10 | 25259.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 447.23 | 5794.18 | 01-JAN-06:10 | 30947.91 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 693.99 | 8991.20 | 01-JAN-06:10 | 48023.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 290.57 | 1403.36 | 01-JAN-06:10 | 25260.46 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 447.22 | 5794.15 | 01-JAN-06:10 | 30947.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7567.51 | 95259.03 | 01-JAN-06:10 | 385948.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 72.65 | 350.90 | 01-JAN-06:10 | 6316.16 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1572.37 | 19648.16 | 01-JAN-06:10 | 80862.03 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 33.56 | 162.10 | 01-JAN-06:10 | 2917.81 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 7128.99 | 87305.92 | 29-JAN-01:50 | 427837.62 | 18-AUG-16:00 |
ExteriorEquipment:Electricity | 2044.08 | 15778.61 | 01-JAN-00:10 | 129663.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.73 | 1613.62 | 01-JAN-00:10 | 5498.40 | 03-APR-07:20 |
ElectricityPurchased:Facility | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
ElectricityPurchased:Plant | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
Cogeneration:ElectricityPurchased | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
ElectricityNet:Plant | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
Cogeneration:ElectricityNet | 32321.75 | 401064.62 | 01-JAN-10:10 | 2058154.05 | 18-AUG-16:00 |
Fans:Electricity | 2804.78 | 50226.32 | 01-JAN-00:10 | 192745.45 | 01-NOV-15:40 |
General:Fans:Electricity | 2804.78 | 50226.32 | 01-JAN-00:10 | 192745.45 | 01-NOV-15:40 |
ExteriorLights:Electricity | 884.33 | 0.00 | 01-JAN-07:20 | 56280.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 884.33 | 0.00 | 01-JAN-07:20 | 56280.71 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.27 | 1942.80 | 01-JAN-00:10 | 1942.80 | 01-JAN-00:10 |
Cooling:Electricity | 4113.87 | 28138.89 | 18-JAN-07:10 | 441774.51 | 01-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1197.53 | 0.00 | 01-JAN-20:50 | 81319.63 | 09-FEB-05:00 |
Electricity:Plant | 2844.45 | 5759.17 | 15-JAN-08:20 | 412696.96 | 23-AUG-16:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 1074.94 | 0.00 | 01-JAN-00:10 | 270106.59 | 23-AUG-16:00 |
HeatRejection:Electricity | 1191.97 | 2003.92 | 15-JAN-08:20 | 84388.24 | 06-JUN-12:50 |
General:HeatRejection:Electricity | 105.15 | 0.00 | 01-JAN-00:10 | 35139.97 | 06-JUN-12:50 |
Pumps:Electricity | 577.54 | 3699.04 | 01-JAN-00:10 | 60000.40 | 29-JUN-14:20 |
General:Pumps:Electricity | 577.54 | 3699.04 | 01-JAN-00:10 | 60000.40 | 29-JUN-14:20 |
WIRED_LTG_ELECTRICITY | 120.67 | 0.00 | 01-JAN-00:10 | 10490.43 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1656.16 | 8146.58 | 05-JAN-03:20 | 1234480.64 | 22-DEC-07:10 |
Gas:Plant | 1656.16 | 8146.58 | 05-JAN-03:20 | 1234480.64 | 22-DEC-07:10 |
WaterSystems:Gas | 578.45 | 8146.58 | 02-JAN-04:10 | 79190.88 | 31-JAN-12:30 |
Water Heater:WaterSystems:Gas | 578.45 | 8146.58 | 02-JAN-04:10 | 79190.88 | 31-JAN-12:30 |
Heating:Gas | 1077.71 | 0.00 | 01-JAN-00:10 | 1226334.06 | 22-DEC-07:10 |
Boiler:Heating:Gas | 1077.71 | 0.00 | 01-JAN-00:10 | 1226334.06 | 22-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 21144.08 | 108455.00 | 01-JAN-20:50 | 2510197.64 | 23-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 21144.08 | 108455.00 | 01-JAN-20:50 | 2510197.64 | 23-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 21144.08 | 108455.00 | 01-JAN-20:50 | 2510197.64 | 23-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8971.58 | 0.00 | 23-JAN-03:20 | 0.00 | 28-JUN-16:00 |
Water:Plant | 8526.10 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 8971.58 | 0.00 | 23-JAN-03:20 | 0.00 | 28-JUN-16:00 |
MainsWater:Plant | 8526.10 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 445.48 | 0.00 | 01-JAN-20:50 | 0.00 | 09-FEB-05:00 |
Humidifier:Water | 445.48 | 0.00 | 01-JAN-20:50 | 0.00 | 09-FEB-05:00 |
MainsWater:HVAC | 445.48 | 0.00 | 01-JAN-20:50 | 0.00 | 09-FEB-05:00 |
Humidifier:MainsWater | 445.48 | 0.00 | 01-JAN-20:50 | 0.00 | 09-FEB-05:00 |
HeatRejection:Water | 6245.93 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:00 |
HeatRejection:MainsWater | 6245.93 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 1208.21 | 0.00 | 01-JAN-00:10 | 807559.77 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 402.19 | 0.00 | 01-JAN-00:10 | 50684.60 | 06-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 402.19 | 0.00 | 01-JAN-00:10 | 50684.60 | 06-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 63798.19 | 161152.93 | 01-JAN-20:50 | 9687994.96 | 23-AUG-16:00 |
EnergyTransfer:Building | 21009.73 | 69106.22 | 18-JAN-23:30 | 1655589.83 | 18-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 789.51 | 0.00 | 01-JAN-00:10 | 85888.89 | 18-JAN-04:50 |
Heating:EnergyTransfer | 85.45 | 0.00 | 01-JAN-16:30 | 388458.35 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 7.15 | 0.00 | 01-JAN-00:10 | 64159.73 | 09-JUL-19:00 |
Cooling:EnergyTransfer | 20924.27 | 68728.97 | 18-JAN-23:30 | 1655589.83 | 18-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 782.36 | 0.00 | 01-JAN-00:10 | 78534.41 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 722.09 | 0.00 | 01-JAN-00:10 | 55928.18 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 722.09 | 0.00 | 01-JAN-00:10 | 55928.18 | 21-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 5327.25 | 0.00 | 01-JAN-00:10 | 460011.85 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5327.25 | 0.00 | 01-JAN-00:10 | 460011.85 | 18-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 487.64 | 0.00 | 01-JAN-00:10 | 57048.94 | 28-JUN-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.20 | 0.00 | 01-JAN-00:10 | 50641.76 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 485.44 | 0.00 | 01-JAN-00:10 | 57048.94 | 28-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 92.25 | 0.00 | 01-JAN-00:10 | 10855.56 | 07-AUG-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 92.25 | 0.00 | 01-JAN-00:10 | 10855.56 | 07-AUG-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 93.85 | 0.00 | 01-JAN-00:10 | 13665.81 | 05-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 491.86 | 15-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 93.85 | 0.00 | 01-JAN-00:10 | 13665.81 | 05-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 128.55 | 0.00 | 01-JAN-00:10 | 16366.53 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 2355.37 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 128.54 | 0.00 | 01-JAN-00:10 | 16366.53 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 128.39 | 0.00 | 01-JAN-00:10 | 18414.55 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 128.39 | 0.00 | 01-JAN-00:10 | 18414.55 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 676.07 | 0.00 | 01-JAN-00:10 | 104640.83 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 8.39 | 0.00 | 01-JAN-00:10 | 83767.46 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 667.68 | 0.00 | 01-JAN-00:10 | 104640.83 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 825.90 | 0.00 | 01-JAN-00:10 | 142416.92 | 28-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 4.77 | 0.00 | 01-JAN-00:10 | 59025.11 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 821.13 | 0.00 | 01-JAN-00:10 | 142416.92 | 28-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1116.22 | 0.00 | 01-JAN-00:10 | 164254.45 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.06 | 0.00 | 01-JAN-00:10 | 76570.39 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1114.16 | 0.00 | 01-JAN-00:10 | 164254.45 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 838.89 | 0.00 | 01-JAN-00:10 | 159900.15 | 21-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.46 | 0.00 | 01-JAN-00:10 | 54492.50 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 836.42 | 0.00 | 01-JAN-00:10 | 159900.15 | 21-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.11 | 0.00 | 01-JAN-00:10 | 13601.62 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.51 | 0.00 | 01-JAN-00:10 | 13601.62 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.60 | 0.00 | 01-JAN-00:10 | 12026.31 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 81.50 | 0.00 | 01-JAN-00:10 | 14545.00 | 05-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.71 | 0.00 | 01-JAN-00:10 | 12050.68 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 77.79 | 0.00 | 01-JAN-00:10 | 14545.00 | 05-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 111.48 | 0.00 | 01-JAN-00:10 | 17805.06 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.61 | 0.00 | 01-JAN-00:10 | 14369.57 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.88 | 0.00 | 01-JAN-00:10 | 17805.06 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 83.81 | 0.00 | 01-JAN-00:10 | 16921.21 | 21-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.64 | 0.00 | 01-JAN-00:10 | 10657.54 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 81.16 | 0.00 | 01-JAN-00:10 | 16921.21 | 21-JUL-16:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 81.26 | 0.00 | 01-JAN-00:10 | 8328.74 | 05-SEP-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.89 | 0.00 | 01-JAN-00:10 | 2722.03 | 17-DEC-09:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.37 | 0.00 | 01-JAN-00:10 | 8328.74 | 05-SEP-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 548.18 | 0.00 | 01-JAN-00:10 | 69684.99 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.52 | 0.00 | 01-JAN-00:10 | 35382.62 | 26-DEC-14:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 532.66 | 0.00 | 01-JAN-00:10 | 69684.99 | 29-JUN-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 114.93 | 0.00 | 01-JAN-00:10 | 23692.64 | 28-JUN-14:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.30 | 0.00 | 01-JAN-00:10 | 20456.37 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 93.63 | 0.00 | 01-JAN-00:10 | 23692.64 | 28-JUN-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.26 | 878.83 | 21-JAN-08:00 | 8204.90 | 15-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.26 | 878.83 | 21-JAN-08:00 | 8204.90 | 15-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1249.79 | 5.31 | 17-JAN-01:40 | 76542.23 | 07-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.03 | 0.00 | 01-JAN-00:10 | 2858.91 | 17-JAN-03:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1249.76 | 0.00 | 17-JAN-02:40 | 76542.23 | 07-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.78 | 0.20 | 28-JAN-10:40 | 7686.03 | 05-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.64 | 0.00 | 01-JAN-16:20 | 664.35 | 18-JAN-01:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.14 | 0.00 | 01-JAN-00:10 | 7686.03 | 05-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7182.02 | 60803.48 | 12-JAN-06:00 | 367644.68 | 31-AUG-06:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 2.56 | 0.00 | 01-JAN-00:30 | 13725.74 | 16-JAN-03:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7179.46 | 60803.48 | 12-JAN-06:00 | 367644.68 | 31-AUG-06:10 |
EnergyTransfer:Plant | 23735.70 | 0.00 | 01-JAN-00:10 | 5810253.60 | 23-AUG-16:00 |
WaterSystems:EnergyTransfer | 402.19 | 0.00 | 01-JAN-00:10 | 50684.60 | 06-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 402.19 | 0.00 | 01-JAN-00:10 | 50684.60 | 06-FEB-12:10 |
EnergyTransfer:HVAC | 19052.76 | 87953.65 | 01-JAN-20:50 | 2342611.65 | 23-AUG-16:00 |
HeatingCoils:EnergyTransfer | 806.02 | 0.00 | 01-JAN-00:10 | 790364.61 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 806.02 | 0.00 | 01-JAN-00:10 | 790364.61 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 806.02 | 0.00 | 01-JAN-00:10 | 790364.61 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 18246.74 | 87953.65 | 01-JAN-20:50 | 2342611.65 | 23-AUG-16:00 |
LoopToLoop:EnergyTransfer | 7694.34 | 0.00 | 01-JAN-00:10 | 1835113.80 | 23-AUG-16:00 |
Boilers:EnergyTransfer | 795.20 | 0.00 | 01-JAN-00:10 | 987287.05 | 22-DEC-07:10 |
Chillers:EnergyTransfer | 6884.52 | 0.00 | 01-JAN-00:10 | 1837934.91 | 23-AUG-16:00 |
HeatRejection:EnergyTransfer | 7959.45 | 0.00 | 01-JAN-00:10 | 2108041.50 | 23-AUG-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 7.145 | -782.357 | 0.000 | 0.000 | 92.655 | 257.680 | 424.397 | 0.000 | 0.000 | 0.000 | 0.480 | 0.000 | 0.000 | 0.000 | 0.000 | -0.014 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -722.086 | 0.000 | 0.000 | 83.428 | 231.415 | 321.278 | 0.000 | 0.000 | 0.000 | 85.964 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5327.194 | 0.000 | 0.000 | 836.730 | 2314.151 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1036.460 |
CORE_TOP | 0.000 | 0.000 | 2.200 | -485.435 | 0.000 | 0.000 | 85.442 | 231.415 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -154.899 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -92.251 | 0.000 | 0.000 | 10.621 | 29.056 | 40.341 | 25.285 | 0.000 | 0.220 | 38.410 | 0.000 | -46.594 | 0.000 | -5.090 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.002 | -93.846 | 0.000 | 0.000 | 6.919 | 18.725 | 25.998 | 66.808 | 0.000 | 0.167 | 6.132 | 0.000 | -27.640 | 0.000 | -3.265 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.009 | -128.541 | 0.000 | 0.000 | 10.417 | 29.057 | 40.342 | 110.367 | 0.000 | 0.217 | 0.001 | 0.000 | -42.957 | 0.000 | -5.196 | -13.714 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -128.384 | 0.000 | 0.000 | 6.858 | 18.725 | 25.997 | 60.472 | 0.000 | 0.134 | 52.441 | 0.000 | -32.613 | 0.000 | -3.630 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 8.386 | -667.672 | 0.000 | 0.000 | 109.719 | 290.565 | 403.414 | 262.260 | 0.000 | 4.923 | 123.114 | 0.000 | -429.874 | 0.000 | -104.835 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 4.771 | -821.121 | 0.000 | 0.000 | 52.146 | 187.251 | 259.975 | 669.285 | 0.000 | 3.473 | 0.000 | 0.000 | -264.392 | 0.000 | -70.824 | -20.564 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.064 | -1114.134 | 0.000 | 0.000 | 104.060 | 290.571 | 403.420 | 1102.023 | 0.000 | 4.732 | 0.041 | 0.000 | -424.137 | 0.000 | -114.628 | -253.970 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.461 | -836.403 | 0.000 | 0.000 | 72.279 | 187.251 | 259.973 | 618.267 | 0.000 | 3.202 | 57.112 | 0.000 | -290.976 | 0.000 | -73.166 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.513 | -66.598 | 0.000 | 0.000 | 11.280 | 29.056 | 40.341 | 26.684 | 0.000 | 0.585 | 2.984 | 0.000 | -39.850 | 0.000 | -11.997 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.706 | -77.792 | 0.000 | 0.000 | 7.179 | 18.725 | 25.998 | 67.256 | 0.000 | 0.402 | 0.000 | 0.000 | -24.960 | 0.000 | -8.244 | -12.268 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 3.608 | -107.873 | 0.000 | 0.000 | 10.735 | 29.057 | 40.342 | 111.048 | 0.000 | 0.566 | 0.002 | 0.000 | -39.746 | 0.000 | -13.217 | -34.521 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 2.644 | -81.162 | 0.000 | 0.000 | 7.361 | 18.725 | 25.997 | 62.015 | 0.000 | 0.391 | 0.106 | 0.000 | -27.527 | 0.000 | -8.549 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.259 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.978 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.033 | -1249.755 | 0.000 | 0.000 | 0.000 | 33.564 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -322.647 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.641 | -116.138 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -41.739 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 2.556 | -7179.477 | 0.000 | 0.000 | 0.000 | 72.655 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -390.591 |
GROUNDFLOOR_PLENUM | 0.891 | -80.371 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.365 | 89.608 | 0.000 | 0.000 | 0.000 | -10.493 | 0.000 |
MIDFLOOR_PLENUM | 15.523 | -532.650 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.751 | 692.018 | 0.000 | 0.000 | 0.000 | -181.642 | 0.000 |
TOPFLOOR_PLENUM | 21.302 | -93.622 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.536 | 90.615 | 0.000 | 0.000 | 0.000 | -18.831 | -0.002 |
Total Facility | 37.716 | -706.642 | 47.738 | -20217.477 | 0.000 | 0.000 | 1507.828 | 4294.357 | 15213.288 | 3181.770 | 0.000 | 26.664 | 1239.028 | 0.000 | -1691.266 | 0.000 | -633.608 | -2299.369 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-FEB-17:00 | 0.00 | 0.00 | 0.00 | -127740.48 | 0.00 | 0.00 | 399.63 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 112638.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-03:03 | 0.00 | 0.00 | 0.00 | -96463.33 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.15 | 0.00 | 0.00 | 0.00 | 87197.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-JUL-03:01 | 0.00 | 0.00 | 0.00 | -850503.02 | 0.00 | 0.00 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 757841.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 | -89267.85 | 0.00 | 0.00 | 836.07 | 2235.31 | 8057.12 | 0.00 | 0.00 | 0.00 | 78139.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 20-AUG-15:51 | 0.00 | 0.00 | 0.00 | -15638.38 | 0.00 | 0.00 | 45.05 | 140.33 | 758.77 | 4014.53 | 0.00 | 152.09 | 10527.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 03-SEP-08:21 | 0.00 | 0.00 | 0.00 | -21134.19 | 0.00 | 0.00 | 20.83 | 90.44 | 488.98 | 16379.70 | 0.00 | 0.00 | 4178.38 | 0.00 | -0.00 | 0.00 | -24.14 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-11:31 | 0.00 | 0.00 | 0.00 | -19980.50 | 0.00 | 0.00 | 33.36 | 140.34 | 758.78 | 23330.47 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -35.18 | -4247.27 |
PERIMETER_BOT_ZN_4 | 20-AUG-15:51 | 0.00 | 0.00 | 0.00 | -29466.32 | 0.00 | 0.00 | 14.05 | 90.44 | 488.98 | 17544.39 | 0.00 | 54.61 | 11273.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 | -124104.18 | 0.00 | 0.00 | 1078.50 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 119292.74 | 0.00 | -8924.80 | 0.00 | -265.89 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-08:41 | 0.00 | 0.00 | 0.00 | -226461.68 | 0.00 | 0.00 | 197.52 | 904.36 | 4889.82 | 156056.12 | 0.00 | 0.00 | 64917.14 | 0.00 | -0.00 | 0.00 | -503.28 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-13:42 | 0.00 | 0.00 | 0.00 | -177721.57 | 0.00 | 0.00 | 364.51 | 1403.36 | 7587.84 | 121083.20 | 0.00 | 2056.41 | 45226.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:11 | 0.00 | 0.00 | 0.00 | -253620.67 | 0.00 | 0.00 | 0.00 | 978.32 | 4889.79 | 175055.84 | 0.00 | 1955.93 | 70740.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -17391.80 | 0.00 | 0.00 | 0.00 | 151.81 | 758.77 | 3584.32 | 0.00 | 1182.03 | 11714.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-07:21 | 0.00 | 0.00 | 0.00 | -21693.60 | 0.00 | 0.00 | 21.59 | 90.44 | 488.98 | 18396.42 | 0.00 | 0.00 | 2696.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-11:21 | 0.00 | 0.00 | 0.00 | -21515.92 | 0.00 | 0.00 | 33.50 | 140.34 | 758.78 | 23303.56 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -109.63 | -2610.63 |
PERIMETER_TOP_ZN_4 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 | -27101.25 | 0.00 | 0.00 | 0.00 | 97.83 | 488.98 | 18660.93 | 0.00 | 0.00 | 7913.02 | 0.00 | -0.00 | 0.00 | -59.52 | 0.00 |
DATACENTER_BOT_ZN_6 | 15-APR-18:00 | 0.00 | 0.00 | 0.00 | -8204.90 | 0.00 | 0.00 | 0.00 | 16.21 | 7794.42 | 0.00 | 0.00 | 0.00 | 394.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 07-APR-17:50 | 0.00 | 0.00 | 0.00 | -76542.23 | 0.00 | 0.00 | 0.00 | 972.60 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2374.59 |
DATACENTER_TOP_ZN_6 | 05-APR-18:00 | 0.00 | 0.00 | 0.00 | -7686.03 | 0.00 | 0.00 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -205.65 |
DATACENTER_BASEMENT_ZN_6 | 18-MAR-04:32 | 0.00 | 0.00 | 0.00 | -398451.37 | 0.00 | 0.00 | 0.00 | 379.60 | 284724.39 | 0.00 | 0.00 | 0.00 | 113347.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-SEP-05:13 | 0.00 | -11657.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11723.15 | 0.00 | -0.00 | 0.00 | -66.03 | 0.00 |
MIDFLOOR_PLENUM | 17-AUG-05:01 | 0.00 | -93635.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94266.76 | 0.00 | -0.00 | 0.00 | -631.65 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:30 | 0.00 | -23686.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.35 | 23455.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-03:01 | 0.00 | 86740.07 | 0.00 | -1964231.50 | 0.00 | 0.00 | 0.00 | 22436.48 | 623236.89 | 0.00 | 0.00 | 0.00 | 1265448.99 | 0.00 | -33630.92 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JUL-15:28 | 0.00 | 0.00 | 147980.08 | 0.00 | 0.00 | 0.00 | 399.52 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -163081.66 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JAN-05:01 | 0.00 | 0.00 | 77014.77 | -0.00 | 0.00 | 0.00 | 0.00 | 2418.12 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -87490.01 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 22-DEC-06:01 | 0.00 | 0.00 | 4818.58 | -0.00 | 0.00 | 0.00 | 92.96 | 180.87 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3038.92 | 0.00 | -114.14 | -2591.33 |
PERIMETER_BOT_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 8818.13 | -0.00 | 0.00 | 0.00 | 144.40 | 280.67 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4184.00 | 0.00 | -237.22 | -5833.69 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JAN-04:01 | 0.00 | 0.00 | 117978.43 | -0.00 | 0.00 | 0.00 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35980.63 | 0.00 | -27744.08 | -65888.79 |
PERIMETER_MID_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 119162.01 | -0.00 | 0.00 | 0.00 | 0.00 | 1956.64 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24268.45 | 0.00 | -17149.57 | -86220.39 |
PERIMETER_MID_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 124719.54 | -0.00 | 0.00 | 0.00 | 0.00 | 3036.26 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35610.44 | 0.00 | -25540.65 | -76721.83 |
PERIMETER_MID_ZN_4 | 17-JAN-05:01 | 0.00 | 0.00 | 112427.94 | -0.00 | 0.00 | 0.00 | 0.00 | 1956.64 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23732.90 | 0.00 | -17151.91 | -80019.49 |
PERIMETER_TOP_ZN_3 | 17-JAN-01:41 | 0.00 | 0.00 | 15870.97 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3063.67 | 0.00 | -2764.46 | -11206.35 |
PERIMETER_TOP_ZN_2 | 17-JAN-01:41 | 0.00 | 0.00 | 16913.17 | -0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2048.65 | 0.00 | -1878.94 | -13735.39 |
PERIMETER_TOP_ZN_1 | 17-JAN-01:41 | 0.00 | 0.00 | 16822.66 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3140.43 | 0.00 | -2812.72 | -12033.03 |
PERIMETER_TOP_ZN_4 | 17-JAN-01:41 | 0.00 | 0.00 | 17240.57 | -0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2039.65 | 0.00 | -1931.70 | -14019.03 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-05:08 | 0.00 | 0.00 | 5897.51 | 0.00 | 0.00 | 0.00 | 0.00 | 350.71 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25734.28 |
DATACENTER_TOP_ZN_6 | 03-JAN-01:42 | 0.00 | 0.00 | 671.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2638.04 |
DATACENTER_BASEMENT_ZN_6 | 16-JAN-01:41 | 0.00 | 0.00 | 94901.59 | 0.00 | 0.00 | 0.00 | 0.00 | 379.60 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -190189.32 |
GROUNDFLOOR_PLENUM | 14-DEC-04:01 | 12954.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4482.46 | -8472.38 |
MIDFLOOR_PLENUM | 14-MAR-05:01 | 89231.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12393.23 | -76838.63 |
TOPFLOOR_PLENUM | 06-FEB-06:01 | 23694.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -829.45 | -22865.09 |
Total Facility | 17-JAN-05:01 | -407585.40 | 367536.09 | 611035.47 | -367536.09 | 0.00 | 0.00 | 0.00 | 44872.96 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -144100.48 | 0.00 | -150951.38 | -221633.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 7.0707 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 7.0707 | 0.1697 | 1.0000 | 1.2001 | 0.1697 | ||
VAV_BOT WITH REHEAT | 12.6757 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 11.7232 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 119.1983 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 109.0783 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.6140 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 11.8641 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 25.9319 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 25.9319 | 0.0130 | 1.0000 | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.5781 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.5781 | 0.0270 | 1.0000 | 0.0156 | 0.0270 | ||
AIRLOOP DATACENTER MID | 5.5151 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 5.5151 | 0.0283 | 1.0000 | 0.1563 | 0.0283 | ||
AIRLOOP DATACENTER TOP | 0.5652 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.5652 | 0.0277 | 1.0000 | 0.0156 | 0.0277 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 7.0707 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 7.0707 | 1.0000 | 1.0000 | 1.2001 | 0.1697 | ||
VAV_BOT WITH REHEAT | 6.3379 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.8027 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.5992 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 35.7595 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.3070 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.7842 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 25.9319 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 25.9319 | 1.0000 | 1.0000 | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.5781 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.5781 | 1.0000 | 1.0000 | 0.0156 | 0.0270 | ||
AIRLOOP DATACENTER MID | 5.5151 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 5.5151 | 1.0000 | 1.0000 | 0.1563 | 0.0283 | ||
AIRLOOP DATACENTER TOP | 0.5652 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.5652 | 1.0000 | 1.0000 | 0.0156 | 0.0277 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 7.0707 | 7.0707 | 7.0707 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2802 | 7.2802 | 2.1841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 68.4792 | 68.4792 | 20.5438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0351 | 7.0351 | 2.1105 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1481 | 1.1481 | 0.3444 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3412 | 1.3412 | 0.4024 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2336 | 1.2336 | 0.3701 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6727 | 1.6727 | 0.5018 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5412 | 10.5412 | 3.1624 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.9474 | 13.9474 | 4.1842 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4772 | 11.4772 | 3.4432 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.7533 | 14.7533 | 4.4260 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2416 | 1.2416 | 0.3725 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4068 | 1.4068 | 0.4220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3353 | 1.3353 | 0.4006 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5951 | 1.5951 | 0.4785 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.5781 | 0.5781 | 0.5781 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 5.5151 | 5.5151 | 5.5151 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.5652 | 0.5652 | 0.5652 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 25.9319 | 25.9319 | 25.9319 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 7.0707 | 7.0707 | 7.0707 | 7.0707 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 12.6757 | 11.7232 | 12.6757 | 3.8027 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 119.1983 | 109.0783 | 119.1983 | 35.7595 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.6140 | 11.8641 | 12.6140 | 3.7842 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.9319 | 25.9319 | 25.9319 | 25.9319 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5781 | 0.5781 | 0.5781 | 0.5781 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5151 | 5.5151 | 5.5151 | 5.5151 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5652 | 0.5652 | 0.5652 | 0.5652 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 7.0707 | 7.0707 | 7.0707 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6401 | 3.6401 | 2.1841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 34.2396 | 34.2396 | 20.5438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5176 | 3.5176 | 2.1105 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5741 | 0.5741 | 0.3444 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6706 | 0.6706 | 0.4024 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6168 | 0.6168 | 0.3701 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8364 | 0.8364 | 0.5018 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2706 | 5.2706 | 3.1624 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9737 | 6.9737 | 4.1842 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7386 | 5.7386 | 3.4432 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3766 | 7.3766 | 4.4260 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6208 | 0.6208 | 0.3725 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7034 | 0.7034 | 0.4220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6676 | 0.6676 | 0.4006 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7976 | 0.7976 | 0.4785 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.5781 | 0.5781 | 0.5781 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 5.5151 | 5.5151 | 5.5151 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.5652 | 0.5652 | 0.5652 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 25.9319 | 25.9319 | 25.9319 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 7.0707 | 7.0707 | 7.0707 | 7.0707 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 6.3379 | 3.8027 | 3.8027 | 3.8027 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.5992 | 35.7595 | 35.7595 | 35.7595 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.3070 | 3.7842 | 3.7842 | 3.7842 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.9319 | 25.9319 | 25.9319 | 25.9319 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5781 | 0.5781 | 0.5781 | 0.5781 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5151 | 5.5151 | 5.5151 | 5.5151 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5652 | 0.5652 | 0.5652 | 0.5652 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 3.50 |
Number of hours cooling loads not met | 694.50 |
Number of hours not met | 698.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 1077.71 | 1226334.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1074.94 | 270106.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 3038.94 | 171667.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 4294.36 | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 884.33 | 56280.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.73 | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.27 | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2804.78 | 192745.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 577.54 | 60000.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 105.15 | 35139.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 1086.81 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 1197.53 | 81319.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 578.45 | 79190.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 32321.75 |
Natural Gas | 0.00 | 1656.16 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 33977.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 92.71 |
Space Heating | 0.00 |
Space Cooling | 88.81 |
Fans (All) | 60.55 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 697.79 |
Subtotal | 697.79 |
Natural Gas [MJ/m2] | |
Space Heating | 23.27 |
Service Water Heating | 12.49 |
Miscellaneous (All) | 35.75 |
Subtotal | 35.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.64 |
Space Heating | 3.17 |
Space Cooling | 12.11 |
Fans (All) | 8.25 |
Service Water Heating | 1.70 |
Receptacle Equipment | 44.77 |
Miscellaneous | 17.35 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2728. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.322578E+12 |
February | 0.000 | 0.208575E+12 |
March | 0.000 | 0.826318E+11 |
April | 0.000 | 0.166747E+11 |
May | 0.000 | 0.506842E+10 |
June | 0.000 | 0.822430E+09 |
July | 0.000 | 0.821671E+09 |
August | 0.000 | 0.532023E+09 |
September | 0.000 | 0.119823E+10 |
October | 0.000 | 0.437031E+11 |
November | 0.000 | 0.108552E+12 |
December | 0.000 | 0.286550E+12 |
Annual Sum or Average | 0.107771E+13 | |
Minimum of Months | 0.000 | 0.532023E+09 |
Maximum of Months | 0.000 | 0.322578E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.596394E+11 | 127185.00 | 16-JAN-23:10 | -2.2 | -3.9 | 0.566886E+10 | 7499.20 | 27-JAN-10:39 | 5.00 | -0.9 |
February | 0.539643E+11 | 127745.83 | 20-FEB-17:00 | 10.60 | 4.23 | 0.514170E+10 | 7499.06 | 01-FEB-10:00 | 1.70 | -1.3 |
March | 0.637569E+11 | 124828.89 | 19-MAR-21:38 | 9.60 | 3.92 | 0.613587E+10 | 7499.00 | 10-MAR-10:09 | 6.97 | 1.33 |
April | 0.613264E+11 | 126158.71 | 02-APR-22:42 | 13.40 | 4.96 | 0.545379E+10 | 7499.01 | 26-APR-13:20 | 24.80 | 9.87 |
May | 0.639889E+11 | 118051.64 | 01-MAY-03:11 | 11.70 | 8.06 | 0.590459E+10 | 7499.28 | 11-MAY-09:20 | 12.93 | 6.32 |
June | 0.658384E+11 | 117669.67 | 19-JUN-03:01 | 14.13 | 6.19 | 0.588552E+10 | 7499.12 | 30-JUN-13:00 | 26.70 | 17.70 |
July | 0.674837E+11 | 110020.26 | 30-JUL-23:00 | 23.30 | 16.37 | 0.547733E+10 | 7499.02 | 31-JUL-09:30 | 24.75 | 17.32 |
August | 0.749546E+11 | 111868.06 | 27-AUG-20:32 | 20.97 | 14.53 | 0.614057E+10 | 7500.47 | 28-AUG-13:00 | 23.30 | 17.98 |
September | 0.678325E+11 | 119559.40 | 17-SEP-20:32 | 17.20 | 11.31 | 0.545611E+10 | 7499.08 | 27-SEP-09:20 | 19.23 | 11.07 |
October | 0.707570E+11 | 125900.16 | 09-OCT-05:27 | 7.20 | 3.34 | 0.567487E+10 | 7499.09 | 24-OCT-13:50 | 8.87 | 4.53 |
November | 0.678030E+11 | 126551.19 | 11-NOV-16:50 | 9.08 | 3.78 | 0.561831E+10 | 7498.94 | 28-NOV-10:20 | 3.13 | -1.0 |
December | 0.650173E+11 | 126192.14 | 17-DEC-16:50 | 10.28 | 2.99 | 0.547525E+10 | 7498.99 | 20-DEC-14:20 | 7.00 | 0.31 |
Annual Sum or Average | 0.782362E+12 | 0.680328E+11 | ||||||||
Minimum of Months | 0.539643E+11 | 110020.26 | -2.2 | -3.9 | 0.514170E+10 | 7498.94 | 1.70 | -1.3 | ||
Maximum of Months | 0.749546E+11 | 127745.83 | 23.30 | 16.37 | 0.614057E+10 | 7500.47 | 26.70 | 17.98 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456675E+11 | 73173.14 | 02-JAN-04:02 | -1.8 | -3.5 | 0.507189E+10 | 6734.84 | 27-JAN-10:39 | 5.00 | -0.9 |
February | 0.448910E+11 | 72244.62 | 21-FEB-04:02 | 2.70 | 0.06 | 0.460484E+10 | 6734.76 | 15-FEB-10:09 | 11.38 | 5.31 |
March | 0.591848E+11 | 75172.40 | 20-MAR-03:02 | 11.32 | 5.04 | 0.549886E+10 | 6734.70 | 10-MAR-10:09 | 6.97 | 1.33 |
April | 0.641224E+11 | 77013.48 | 04-APR-03:02 | 5.40 | -1.2 | 0.488199E+10 | 6734.72 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.589205E+11 | 88043.67 | 30-MAY-03:03 | 14.82 | 11.25 | 0.528413E+10 | 6735.02 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.664351E+11 | 92134.74 | 08-JUN-03:02 | 18.90 | 11.94 | 0.526593E+10 | 6735.04 | 30-JUN-13:00 | 26.70 | 17.70 |
July | 0.718502E+11 | 88974.84 | 10-JUL-05:02 | 20.10 | 15.67 | 0.489048E+10 | 6734.65 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.823475E+11 | 85136.84 | 04-AUG-05:02 | 18.22 | 14.00 | 0.549131E+10 | 6735.43 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.586527E+11 | 96466.99 | 05-SEP-03:03 | 17.80 | 15.21 | 0.488081E+10 | 6734.77 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.594422E+11 | 91889.51 | 11-OCT-03:02 | 17.70 | 13.78 | 0.507721E+10 | 6734.83 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.559296E+11 | 77007.44 | 08-NOV-04:02 | 12.12 | 4.55 | 0.502895E+10 | 6734.69 | 27-NOV-10:20 | 1.47 | -2.8 |
December | 0.546487E+11 | 75240.48 | 26-DEC-04:01 | 0.32 | -0.8 | 0.490391E+10 | 6734.74 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.722092E+12 | 0.608803E+11 | ||||||||
Minimum of Months | 0.448910E+11 | 72244.62 | -1.8 | -3.5 | 0.460484E+10 | 6734.65 | 1.47 | -2.8 | ||
Maximum of Months | 0.823475E+11 | 96466.99 | 20.10 | 15.67 | 0.549886E+10 | 6735.43 | 26.70 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339710E+11 | 61782.73 | 06-JAN-06:02 | -1.2 | -3.3 | 0.502083E+10 | 6734.84 | 27-JAN-10:39 | 5.00 | -0.9 |
February | 0.325962E+11 | 62243.89 | 14-FEB-06:01 | -0.9 | -3.4 | 0.456985E+10 | 6734.71 | 01-FEB-10:00 | 1.70 | -1.3 |
March | 0.423843E+11 | 63553.29 | 21-MAR-05:02 | 10.60 | 4.70 | 0.547829E+10 | 6734.70 | 10-MAR-10:09 | 6.97 | 1.33 |
April | 0.436768E+11 | 68874.07 | 13-APR-04:02 | 13.62 | 3.62 | 0.487017E+10 | 6734.65 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.492474E+11 | 78134.57 | 22-MAY-03:01 | 18.22 | 12.60 | 0.527334E+10 | 6734.98 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.531373E+11 | 83236.23 | 07-JUN-03:01 | 20.50 | 11.93 | 0.525810E+10 | 6735.09 | 30-JUN-13:00 | 26.70 | 17.70 |
July | 0.535297E+11 | 85046.55 | 26-JUL-03:01 | 22.12 | 15.59 | 0.488412E+10 | 6734.63 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.567960E+11 | 84759.75 | 15-AUG-03:01 | 21.02 | 16.59 | 0.548853E+10 | 6735.31 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.488439E+11 | 82826.86 | 01-SEP-03:01 | 19.90 | 14.27 | 0.487067E+10 | 6734.75 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.455166E+11 | 78000.55 | 07-OCT-04:02 | 18.80 | 11.89 | 0.506177E+10 | 6734.78 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.387772E+11 | 64454.05 | 09-NOV-06:02 | 12.20 | 7.73 | 0.500694E+10 | 6734.69 | 27-NOV-10:20 | 1.47 | -2.8 |
December | 0.342485E+11 | 62933.35 | 01-DEC-06:01 | 3.90 | -0.2 | 0.485286E+10 | 6734.73 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.532725E+12 | 0.606355E+11 | ||||||||
Minimum of Months | 0.325962E+11 | 61782.73 | -1.2 | -3.4 | 0.456985E+10 | 6734.63 | 1.47 | -2.8 | ||
Maximum of Months | 0.567960E+11 | 85046.55 | 22.12 | 16.59 | 0.548853E+10 | 6735.31 | 30.18 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225998E+11 | 32356.97 | 05-JAN-16:40 | 14.23 | 5.97 | 0.455971E+10 | 6734.58 | 06-JAN-14:50 | 10.68 | 3.59 |
February | 0.233443E+11 | 41196.19 | 15-FEB-16:20 | 17.03 | 6.25 | 0.427516E+10 | 6734.62 | 15-FEB-10:09 | 11.38 | 5.31 |
March | 0.336917E+11 | 42418.63 | 08-MAR-16:20 | 22.60 | 8.75 | 0.531578E+10 | 6734.68 | 10-MAR-10:20 | 7.23 | 1.52 |
April | 0.400667E+11 | 65450.35 | 28-APR-05:02 | 11.93 | 4.33 | 0.481501E+10 | 6734.65 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.489924E+11 | 79682.56 | 19-MAY-05:02 | 16.78 | 9.40 | 0.524869E+10 | 6734.91 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.574014E+11 | 87195.59 | 24-JUN-05:02 | 19.90 | 14.57 | 0.525044E+10 | 6735.06 | 30-JUN-13:00 | 26.70 | 17.70 |
July | 0.601652E+11 | 89274.93 | 25-JUL-05:02 | 21.20 | 15.33 | 0.488631E+10 | 6734.63 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.620551E+11 | 87583.72 | 15-AUG-03:01 | 21.02 | 16.59 | 0.548637E+10 | 6735.35 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.489720E+11 | 82464.04 | 05-SEP-03:01 | 17.80 | 15.21 | 0.485058E+10 | 6734.69 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.386296E+11 | 79622.73 | 07-OCT-05:02 | 18.12 | 11.60 | 0.496740E+10 | 6734.69 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.276148E+11 | 55547.07 | 01-NOV-05:01 | 7.70 | 5.59 | 0.478335E+10 | 6734.59 | 02-NOV-09:09 | 9.40 | 6.71 |
December | 0.219110E+11 | 31635.52 | 29-DEC-16:30 | 10.85 | 3.42 | 0.442805E+10 | 6734.62 | 20-DEC-14:00 | 7.00 | 0.44 |
Annual Sum or Average | 0.485444E+12 | 0.588668E+11 | ||||||||
Minimum of Months | 0.219110E+11 | 31635.52 | 7.70 | 3.42 | 0.427516E+10 | 6734.58 | 7.00 | 0.44 | ||
Maximum of Months | 0.620551E+11 | 89274.93 | 22.60 | 16.59 | 0.548637E+10 | 6735.35 | 30.18 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388591E+10 | 4128.77 | 24-JAN-14:40 | 15.37 | 4.69 | 0.594070E+09 | 845.61 | 12-JAN-14:00 | 7.20 | 2.88 |
February | 0.401421E+10 | 5514.98 | 14-FEB-16:30 | 21.65 | 7.52 | 0.552192E+09 | 845.62 | 15-FEB-10:09 | 11.38 | 5.31 |
March | 0.621687E+10 | 7238.15 | 27-MAR-14:30 | 18.05 | 6.94 | 0.677280E+09 | 845.63 | 02-MAR-14:09 | 7.88 | 3.37 |
April | 0.813340E+10 | 8792.33 | 14-APR-14:00 | 23.30 | 10.23 | 0.608530E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.830804E+10 | 10349.67 | 19-MAY-05:01 | 16.78 | 9.40 | 0.660358E+09 | 845.65 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.110118E+11 | 11887.17 | 29-JUN-05:01 | 24.40 | 16.06 | 0.660924E+09 | 845.68 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.124399E+11 | 11905.72 | 10-JUL-05:01 | 20.10 | 15.67 | 0.614461E+09 | 845.62 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.134287E+11 | 15638.37 | 20-AUG-15:51 | 35.00 | 15.94 | 0.689401E+09 | 845.75 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.851726E+10 | 12275.36 | 05-SEP-03:01 | 17.80 | 15.21 | 0.610471E+09 | 845.63 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.689751E+10 | 10091.03 | 11-OCT-05:01 | 17.80 | 13.87 | 0.628066E+09 | 845.64 | 24-OCT-13:39 | 10.53 | 5.30 |
November | 0.515822E+10 | 5875.47 | 08-NOV-13:50 | 15.92 | 6.93 | 0.616709E+09 | 845.62 | 27-NOV-14:30 | 6.40 | 1.19 |
December | 0.424021E+10 | 4896.58 | 01-DEC-14:10 | 11.78 | 4.39 | 0.586278E+09 | 845.61 | 20-DEC-14:20 | 7.00 | 0.31 |
Annual Sum or Average | 0.922519E+11 | 0.749874E+10 | ||||||||
Minimum of Months | 0.388591E+10 | 4128.77 | 11.78 | 4.39 | 0.552192E+09 | 845.61 | 6.40 | 0.31 | ||
Maximum of Months | 0.134287E+11 | 15638.37 | 35.00 | 16.06 | 0.689401E+09 | 845.75 | 28.08 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423509E+10 | 10541.53 | 01-JAN-09:38 | 4.07 | -0.3 | 0.370671E+09 | 544.96 | 27-JAN-10:39 | 5.00 | -0.9 |
February | 0.434278E+10 | 9306.47 | 14-FEB-09:05 | 7.25 | 1.88 | 0.347100E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.31 |
March | 0.653235E+10 | 12397.90 | 26-MAR-08:32 | 9.67 | 3.25 | 0.429768E+09 | 544.95 | 21-MAR-09:09 | 14.40 | 6.66 |
April | 0.880454E+10 | 17165.65 | 30-APR-08:12 | 15.20 | 5.05 | 0.390370E+09 | 545.33 | 24-APR-09:09 | 11.57 | 5.56 |
May | 0.903445E+10 | 19261.83 | 14-MAY-08:51 | 21.10 | 9.76 | 0.423273E+09 | 544.96 | 01-MAY-13:09 | 11.93 | 5.54 |
June | 0.111418E+11 | 20963.48 | 25-JUN-07:41 | 23.35 | 15.06 | 0.423801E+09 | 544.99 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.118364E+11 | 20974.45 | 30-JUL-07:51 | 23.90 | 15.83 | 0.393664E+09 | 544.97 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.123222E+11 | 20266.90 | 20-AUG-08:31 | 25.53 | 15.18 | 0.440992E+09 | 545.03 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.881269E+10 | 21134.21 | 03-SEP-08:21 | 24.45 | 14.42 | 0.390063E+09 | 544.97 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.726884E+10 | 18564.99 | 01-OCT-09:32 | 20.00 | 12.08 | 0.398947E+09 | 544.97 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.522031E+10 | 9738.75 | 12-NOV-08:06 | 1.38 | -0.5 | 0.387527E+09 | 544.95 | 28-NOV-10:20 | 3.13 | -1.0 |
December | 0.429514E+10 | 6462.34 | 29-DEC-09:05 | 1.38 | -0.9 | 0.361946E+09 | 544.95 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.938466E+11 | 0.475812E+10 | ||||||||
Minimum of Months | 0.423509E+10 | 6462.34 | 1.38 | -0.9 | 0.347100E+09 | 544.95 | 2.38 | -1.0 | ||
Maximum of Months | 0.123222E+11 | 21134.21 | 25.53 | 15.83 | 0.440992E+09 | 545.33 | 28.08 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871093E+10 | 16994.79 | 01-JAN-14:11 | 15.77 | 5.68 | 0.637396E+09 | 1050.12 | 26-JAN-14:09 | 10.10 | 1.47 |
February | 0.853449E+10 | 16772.01 | 12-FEB-14:32 | 17.93 | 6.14 | 0.581746E+09 | 1002.19 | 10-FEB-14:09 | 13.90 | 5.02 |
March | 0.932412E+10 | 15892.42 | 12-MAR-13:42 | 17.62 | 5.91 | 0.680071E+09 | 899.44 | 24-MAR-13:20 | 17.57 | 6.05 |
April | 0.952280E+10 | 11436.45 | 27-APR-13:10 | 23.07 | 9.44 | 0.607188E+09 | 845.66 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.864104E+10 | 10952.26 | 19-MAY-05:01 | 16.78 | 9.40 | 0.658165E+09 | 845.67 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.111336E+11 | 12604.25 | 29-JUN-05:01 | 24.40 | 16.06 | 0.659321E+09 | 845.70 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.129695E+11 | 12663.15 | 10-JUL-05:01 | 20.10 | 15.67 | 0.614027E+09 | 845.64 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.149080E+11 | 17600.32 | 20-AUG-15:51 | 35.00 | 15.94 | 0.689393E+09 | 857.40 | 31-AUG-13:09 | 29.50 | 15.71 |
September | 0.117298E+11 | 18664.08 | 03-SEP-13:42 | 32.52 | 16.74 | 0.614418E+09 | 973.51 | 28-SEP-13:30 | 29.45 | 15.24 |
October | 0.122657E+11 | 19982.72 | 01-OCT-11:31 | 25.03 | 14.21 | 0.653705E+09 | 1023.10 | 30-OCT-13:20 | 18.90 | 7.06 |
November | 0.106116E+11 | 16229.82 | 05-NOV-12:32 | 11.13 | 2.82 | 0.664612E+09 | 1067.40 | 01-NOV-13:20 | 12.93 | 7.55 |
December | 0.101916E+11 | 16590.82 | 24-DEC-14:22 | 12.75 | 3.62 | 0.642839E+09 | 1069.63 | 29-DEC-14:09 | 10.68 | 3.51 |
Annual Sum or Average | 0.128543E+12 | 0.770288E+10 | ||||||||
Minimum of Months | 0.853449E+10 | 10952.26 | 11.13 | 2.82 | 0.581746E+09 | 845.64 | 10.10 | 1.47 | ||
Maximum of Months | 0.149080E+11 | 19982.72 | 35.00 | 16.74 | 0.689393E+09 | 1069.63 | 29.50 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573265E+10 | 9885.86 | 26-JAN-16:30 | 10.30 | 1.37 | 0.368199E+09 | 544.94 | 06-JAN-14:50 | 10.68 | 3.59 |
February | 0.644618E+10 | 13422.87 | 15-FEB-16:30 | 16.95 | 6.15 | 0.352183E+09 | 544.95 | 15-FEB-10:09 | 11.38 | 5.31 |
March | 0.935379E+10 | 23313.90 | 12-MAR-16:22 | 20.00 | 6.20 | 0.438680E+09 | 544.96 | 02-MAR-14:09 | 7.88 | 3.37 |
April | 0.127165E+11 | 25494.57 | 16-APR-17:01 | 20.40 | 8.02 | 0.395276E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.103710E+11 | 23953.42 | 29-MAY-16:32 | 26.47 | 13.20 | 0.419437E+09 | 544.97 | 09-MAY-13:30 | 25.00 | 9.07 |
June | 0.135683E+11 | 28691.83 | 25-JUN-16:31 | 34.07 | 14.55 | 0.424338E+09 | 545.00 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.155508E+11 | 28023.51 | 02-JUL-17:31 | 31.50 | 16.62 | 0.395497E+09 | 544.96 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.188264E+11 | 29466.69 | 20-AUG-15:51 | 35.00 | 15.94 | 0.445256E+09 | 545.07 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.105434E+11 | 24290.49 | 04-SEP-17:21 | 26.15 | 15.89 | 0.387958E+09 | 544.96 | 19-SEP-13:09 | 25.18 | 14.08 |
October | 0.973770E+10 | 24017.38 | 01-OCT-15:31 | 28.70 | 13.10 | 0.403357E+09 | 544.97 | 24-OCT-13:39 | 10.53 | 5.30 |
November | 0.796736E+10 | 17258.82 | 12-NOV-14:42 | 9.32 | 2.56 | 0.399852E+09 | 544.95 | 21-NOV-14:09 | 15.18 | 5.76 |
December | 0.757274E+10 | 19600.54 | 31-DEC-15:32 | 10.37 | 1.70 | 0.388285E+09 | 544.95 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.128387E+12 | 0.481832E+10 | ||||||||
Minimum of Months | 0.573265E+10 | 9885.86 | 9.32 | 1.37 | 0.352183E+09 | 544.94 | 2.38 | 0.81 | ||
Maximum of Months | 0.188264E+11 | 29466.69 | 35.00 | 16.62 | 0.445256E+09 | 545.07 | 28.08 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237392E+10 | 2997.20 | 05-JAN-16:00 | 16.10 | 6.82 | 0.525894E+09 | 802.27 | 13-JAN-14:00 | 12.20 | 3.69 |
February | 0.248443E+10 | 3965.45 | 15-FEB-15:50 | 17.20 | 6.50 | 0.495709E+09 | 845.60 | 15-FEB-14:39 | 16.83 | 6.51 |
March | 0.398523E+10 | 4972.80 | 27-MAR-14:50 | 18.22 | 6.99 | 0.637807E+09 | 845.62 | 28-MAR-13:09 | 16.42 | 7.52 |
April | 0.523448E+10 | 7594.85 | 14-APR-14:30 | 23.60 | 10.42 | 0.593685E+09 | 845.62 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.677237E+10 | 9604.31 | 19-MAY-05:01 | 16.78 | 9.40 | 0.654048E+09 | 845.65 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.910855E+10 | 12056.69 | 27-JUN-05:02 | 19.60 | 12.21 | 0.658730E+09 | 845.69 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.978471E+10 | 12411.53 | 25-JUL-05:02 | 21.20 | 15.33 | 0.614010E+09 | 845.62 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.962373E+10 | 11823.30 | 07-AUG-05:02 | 18.90 | 13.66 | 0.688145E+09 | 845.73 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.702814E+10 | 9814.11 | 12-SEP-05:01 | 17.62 | 13.36 | 0.605871E+09 | 845.62 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.500433E+10 | 7415.15 | 02-OCT-13:50 | 26.52 | 15.41 | 0.604868E+09 | 845.63 | 24-OCT-13:39 | 10.53 | 5.30 |
November | 0.316656E+10 | 4074.26 | 03-NOV-14:00 | 12.20 | 2.39 | 0.567331E+09 | 845.60 | 01-NOV-13:00 | 12.20 | 7.25 |
December | 0.220205E+10 | 2846.00 | 01-DEC-16:00 | 12.80 | 4.90 | 0.501330E+09 | 832.20 | 01-DEC-14:00 | 12.20 | 4.60 |
Annual Sum or Average | 0.667685E+11 | 0.714743E+10 | ||||||||
Minimum of Months | 0.220205E+10 | 2846.00 | 12.20 | 2.39 | 0.495709E+09 | 802.27 | 10.53 | 3.69 | ||
Maximum of Months | 0.978471E+10 | 12411.53 | 26.52 | 15.41 | 0.688145E+09 | 845.73 | 30.18 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300128E+10 | 4820.99 | 27-JAN-09:30 | 1.70 | -2.9 | 0.247513E+09 | 521.19 | 03-JAN-09:39 | 5.40 | 1.20 |
February | 0.334235E+10 | 7877.59 | 14-FEB-09:20 | 7.80 | 2.16 | 0.234382E+09 | 521.19 | 14-FEB-08:50 | 6.13 | 1.23 |
March | 0.550334E+10 | 15633.74 | 26-MAR-09:02 | 11.23 | 4.18 | 0.298530E+09 | 521.20 | 10-MAR-11:09 | 8.58 | 2.30 |
April | 0.748620E+10 | 17797.64 | 30-APR-08:52 | 15.60 | 4.80 | 0.284304E+09 | 521.22 | 17-APR-14:09 | 24.60 | 9.73 |
May | 0.867970E+10 | 21164.25 | 29-MAY-08:51 | 18.30 | 12.77 | 0.307100E+09 | 521.29 | 23-MAY-14:30 | 18.05 | 13.92 |
June | 0.106699E+11 | 22609.04 | 18-JUN-08:31 | 24.67 | 11.79 | 0.309475E+09 | 521.26 | 30-JUN-14:09 | 27.35 | 17.45 |
July | 0.108355E+11 | 22642.99 | 30-JUL-08:41 | 25.32 | 16.67 | 0.289823E+09 | 521.23 | 05-JUL-07:10 | 24.60 | 15.15 |
August | 0.107868E+11 | 22069.39 | 13-AUG-09:01 | 22.48 | 17.93 | 0.323393E+09 | 521.22 | 31-AUG-10:39 | 25.37 | 15.24 |
September | 0.837811E+10 | 22006.09 | 03-SEP-09:01 | 25.97 | 15.08 | 0.283576E+09 | 521.23 | 12-SEP-10:20 | 24.97 | 15.34 |
October | 0.642887E+10 | 12404.98 | 01-OCT-09:02 | 18.35 | 11.46 | 0.283581E+09 | 521.22 | 06-OCT-10:09 | 21.57 | 12.31 |
November | 0.412109E+10 | 8275.33 | 01-NOV-08:50 | 9.63 | 6.29 | 0.266109E+09 | 521.19 | 01-NOV-10:20 | 12.97 | 7.66 |
December | 0.287982E+10 | 4559.60 | 29-DEC-09:20 | 1.67 | -0.8 | 0.239355E+09 | 521.19 | 29-DEC-09:20 | 1.67 | -0.8 |
Annual Sum or Average | 0.821130E+11 | 0.336714E+10 | ||||||||
Minimum of Months | 0.287982E+10 | 4559.60 | 1.67 | -2.9 | 0.234382E+09 | 521.19 | 1.67 | -0.8 | ||
Maximum of Months | 0.108355E+11 | 22642.99 | 25.97 | 17.93 | 0.323393E+09 | 521.29 | 27.35 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.842947E+10 | 16246.00 | 01-JAN-14:11 | 15.77 | 5.68 | 0.644186E+09 | 1161.23 | 26-JAN-14:20 | 10.20 | 1.52 |
February | 0.798956E+10 | 16757.77 | 19-FEB-14:12 | 16.47 | 6.87 | 0.585175E+09 | 1082.68 | 10-FEB-14:09 | 13.90 | 5.02 |
March | 0.800640E+10 | 15973.08 | 26-MAR-14:41 | 20.50 | 7.68 | 0.668589E+09 | 934.01 | 10-MAR-14:09 | 12.88 | 3.10 |
April | 0.716828E+10 | 10989.61 | 27-APR-13:30 | 23.60 | 9.33 | 0.598439E+09 | 845.66 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.743590E+10 | 10469.27 | 19-MAY-05:01 | 16.78 | 9.40 | 0.653169E+09 | 845.67 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.931505E+10 | 12919.63 | 28-JUN-05:02 | 19.37 | 11.61 | 0.657031E+09 | 845.71 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.103073E+11 | 13332.92 | 12-JUL-05:02 | 20.60 | 15.75 | 0.613466E+09 | 845.64 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.113060E+11 | 13465.49 | 31-AUG-13:00 | 29.40 | 15.80 | 0.688826E+09 | 876.59 | 31-AUG-13:09 | 29.50 | 15.71 |
September | 0.109514E+11 | 17772.11 | 03-SEP-13:42 | 32.52 | 16.74 | 0.617509E+09 | 1050.24 | 28-SEP-13:39 | 29.63 | 15.07 |
October | 0.115126E+11 | 17712.32 | 01-OCT-13:42 | 28.12 | 13.70 | 0.663795E+09 | 1108.33 | 30-OCT-13:39 | 18.90 | 7.06 |
November | 0.983263E+10 | 15343.21 | 23-NOV-12:32 | 13.33 | 4.23 | 0.676614E+09 | 1155.26 | 01-NOV-13:39 | 12.57 | 7.40 |
December | 0.916126E+10 | 14848.48 | 31-DEC-14:23 | 10.55 | 1.88 | 0.646923E+09 | 1152.11 | 29-DEC-14:09 | 10.68 | 3.51 |
Annual Sum or Average | 0.111416E+12 | 0.771372E+10 | ||||||||
Minimum of Months | 0.716828E+10 | 10469.27 | 10.55 | 1.88 | 0.585175E+09 | 845.64 | 10.20 | 1.52 | ||
Maximum of Months | 0.115126E+11 | 17772.11 | 32.52 | 16.74 | 0.688826E+09 | 1161.23 | 30.18 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341920E+10 | 8306.57 | 26-JAN-16:30 | 10.30 | 1.37 | 0.334587E+09 | 544.83 | 26-JAN-14:00 | 10.60 | 1.70 |
February | 0.391001E+10 | 11478.83 | 15-FEB-16:30 | 16.95 | 6.15 | 0.312904E+09 | 544.92 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.574809E+10 | 11977.10 | 07-MAR-16:30 | 21.15 | 8.76 | 0.387327E+09 | 544.92 | 07-MAR-14:00 | 20.60 | 8.69 |
April | 0.725624E+10 | 21132.68 | 16-APR-17:12 | 20.20 | 7.93 | 0.365988E+09 | 544.94 | 14-APR-13:00 | 23.30 | 10.23 |
May | 0.838002E+10 | 21442.81 | 29-MAY-16:51 | 26.10 | 13.32 | 0.398640E+09 | 544.94 | 09-MAY-13:00 | 25.60 | 9.52 |
June | 0.101950E+11 | 25365.94 | 25-JUN-17:11 | 33.13 | 14.88 | 0.410972E+09 | 545.00 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.105017E+11 | 23496.64 | 04-JUL-17:01 | 35.73 | 14.59 | 0.387209E+09 | 544.95 | 21-JUL-09:30 | 30.55 | 16.73 |
August | 0.108156E+11 | 22830.67 | 20-AUG-17:21 | 34.40 | 15.43 | 0.432776E+09 | 545.03 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.846330E+10 | 21235.82 | 04-SEP-17:21 | 26.15 | 15.89 | 0.371903E+09 | 544.95 | 22-SEP-13:09 | 27.98 | 16.20 |
October | 0.692120E+10 | 20418.50 | 15-OCT-16:21 | 20.60 | 7.78 | 0.368896E+09 | 544.94 | 02-OCT-13:39 | 26.33 | 15.34 |
November | 0.464345E+10 | 10093.85 | 02-NOV-16:00 | 16.70 | 9.77 | 0.352745E+09 | 544.94 | 20-NOV-14:39 | 14.80 | 4.88 |
December | 0.338864E+10 | 7096.51 | 29-DEC-16:00 | 11.70 | 3.86 | 0.324994E+09 | 544.93 | 20-DEC-14:00 | 7.00 | 0.44 |
Annual Sum or Average | 0.836424E+11 | 0.444894E+10 | ||||||||
Minimum of Months | 0.338864E+10 | 7096.51 | 10.30 | 1.37 | 0.312904E+09 | 544.83 | 7.00 | 0.44 | ||
Maximum of Months | 0.108156E+11 | 25365.94 | 35.73 | 15.89 | 0.432776E+09 | 545.03 | 30.55 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146326E+10 | 3273.18 | 05-JAN-16:00 | 16.10 | 6.82 | 0.485808E+09 | 742.77 | 05-JAN-14:00 | 16.10 | 6.82 |
February | 0.186528E+10 | 4019.58 | 14-FEB-16:50 | 21.28 | 7.31 | 0.455675E+09 | 830.25 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.358563E+10 | 4688.47 | 08-MAR-16:00 | 22.80 | 9.01 | 0.591525E+09 | 845.60 | 17-MAR-13:00 | 16.10 | 5.39 |
April | 0.520167E+10 | 8259.95 | 28-APR-15:30 | 25.00 | 10.38 | 0.570428E+09 | 845.62 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.710651E+10 | 9256.29 | 19-MAY-15:30 | 30.00 | 12.63 | 0.640327E+09 | 845.63 | 23-MAY-13:30 | 23.05 | 13.67 |
June | 0.993173E+10 | 13779.26 | 29-JUN-03:01 | 23.07 | 14.68 | 0.654067E+09 | 845.68 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.109309E+11 | 17390.18 | 04-JUL-17:01 | 35.73 | 14.59 | 0.612154E+09 | 845.62 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.105644E+11 | 13802.35 | 22-AUG-03:01 | 21.20 | 15.84 | 0.684649E+09 | 845.74 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.739594E+10 | 9251.43 | 01-SEP-15:10 | 28.80 | 16.51 | 0.595004E+09 | 845.64 | 13-SEP-13:39 | 26.67 | 14.53 |
October | 0.476573E+10 | 8057.66 | 02-OCT-13:50 | 26.52 | 15.41 | 0.570527E+09 | 845.63 | 02-OCT-13:39 | 26.33 | 15.34 |
November | 0.255575E+10 | 3776.80 | 09-NOV-14:00 | 19.40 | 9.79 | 0.516533E+09 | 832.22 | 03-NOV-13:00 | 12.20 | 2.39 |
December | 0.123259E+10 | 3015.03 | 01-DEC-16:00 | 12.80 | 4.90 | 0.462437E+09 | 760.57 | 01-DEC-14:00 | 12.20 | 4.60 |
Annual Sum or Average | 0.665994E+11 | 0.683913E+10 | ||||||||
Minimum of Months | 0.123259E+10 | 3015.03 | 12.80 | 4.90 | 0.455675E+09 | 742.77 | 12.20 | 2.39 | ||
Maximum of Months | 0.109309E+11 | 17390.18 | 35.73 | 16.51 | 0.684649E+09 | 845.74 | 28.08 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201457E+10 | 3513.37 | 05-JAN-15:40 | 16.10 | 6.82 | 0.317723E+09 | 505.79 | 27-JAN-10:09 | 3.35 | -1.8 |
February | 0.251525E+10 | 5550.45 | 14-FEB-09:40 | 8.90 | 2.70 | 0.304746E+09 | 544.95 | 10-FEB-10:09 | 6.15 | 1.44 |
March | 0.464530E+10 | 7801.02 | 24-MAR-09:20 | 8.33 | 2.38 | 0.399418E+09 | 544.95 | 10-MAR-10:20 | 7.23 | 1.52 |
April | 0.702432E+10 | 19056.88 | 30-APR-09:22 | 16.15 | 4.98 | 0.386360E+09 | 544.96 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.861966E+10 | 21107.21 | 29-MAY-08:51 | 18.30 | 12.77 | 0.418062E+09 | 544.96 | 15-MAY-13:09 | 26.88 | 10.23 |
June | 0.110409E+11 | 21699.84 | 18-JUN-07:21 | 21.95 | 11.18 | 0.422261E+09 | 545.00 | 30-JUN-13:39 | 29.47 | 17.81 |
July | 0.114790E+11 | 21527.51 | 04-JUL-09:01 | 26.97 | 18.47 | 0.394225E+09 | 544.98 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.112910E+11 | 21428.78 | 20-AUG-08:41 | 25.82 | 15.33 | 0.441399E+09 | 545.03 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.835805E+10 | 20418.54 | 03-SEP-09:12 | 26.33 | 15.28 | 0.386085E+09 | 544.97 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.573067E+10 | 18801.37 | 01-OCT-08:42 | 17.43 | 11.05 | 0.381977E+09 | 544.97 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.318408E+10 | 7042.99 | 01-NOV-09:00 | 10.00 | 6.45 | 0.343525E+09 | 544.94 | 01-NOV-09:09 | 10.47 | 6.67 |
December | 0.189057E+10 | 3226.50 | 29-DEC-09:30 | 1.95 | -0.6 | 0.302202E+09 | 494.33 | 29-DEC-10:09 | 3.27 | 0.10 |
Annual Sum or Average | 0.777934E+11 | 0.449798E+10 | ||||||||
Minimum of Months | 0.189057E+10 | 3226.50 | 1.95 | -0.6 | 0.302202E+09 | 494.33 | 3.27 | -1.8 | ||
Maximum of Months | 0.114790E+11 | 21699.84 | 26.97 | 18.47 | 0.441399E+09 | 545.03 | 29.47 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.688917E+10 | 17392.93 | 01-JAN-14:11 | 15.77 | 5.68 | 0.593723E+09 | 1054.79 | 26-JAN-14:20 | 10.20 | 1.52 |
February | 0.688578E+10 | 18214.72 | 19-FEB-14:12 | 16.47 | 6.87 | 0.543513E+09 | 1000.34 | 10-FEB-14:20 | 13.90 | 4.99 |
March | 0.703577E+10 | 18374.56 | 26-MAR-14:32 | 20.40 | 7.65 | 0.634716E+09 | 875.47 | 10-MAR-14:09 | 12.88 | 3.10 |
April | 0.699444E+10 | 11871.13 | 27-APR-13:30 | 23.60 | 9.33 | 0.579091E+09 | 845.66 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.775546E+10 | 10699.59 | 19-MAY-05:01 | 16.78 | 9.40 | 0.639236E+09 | 845.65 | 01-MAY-13:09 | 11.93 | 5.54 |
June | 0.101494E+11 | 14773.54 | 29-JUN-03:01 | 23.07 | 14.68 | 0.651206E+09 | 845.70 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.114566E+11 | 18542.40 | 04-JUL-17:01 | 35.73 | 14.59 | 0.611185E+09 | 845.64 | 03-JUL-09:09 | 25.87 | 15.96 |
August | 0.122379E+11 | 18636.71 | 13-AUG-15:51 | 30.00 | 17.17 | 0.684942E+09 | 851.90 | 31-AUG-13:09 | 29.50 | 15.71 |
September | 0.112610E+11 | 20101.92 | 03-SEP-13:51 | 32.80 | 16.73 | 0.605303E+09 | 1001.49 | 28-SEP-13:39 | 29.63 | 15.07 |
October | 0.110378E+11 | 21517.71 | 01-OCT-11:21 | 24.75 | 14.07 | 0.626970E+09 | 1020.33 | 31-OCT-13:20 | 20.93 | 8.51 |
November | 0.852050E+10 | 17081.73 | 19-NOV-14:01 | 13.58 | 3.40 | 0.625434E+09 | 1075.02 | 01-NOV-13:39 | 12.57 | 7.40 |
December | 0.765152E+10 | 17927.89 | 31-DEC-14:01 | 10.18 | 1.68 | 0.589712E+09 | 1049.32 | 29-DEC-14:09 | 10.68 | 3.51 |
Annual Sum or Average | 0.107875E+12 | 0.738503E+10 | ||||||||
Minimum of Months | 0.688578E+10 | 10699.59 | 10.18 | 1.68 | 0.543513E+09 | 845.64 | 10.20 | 1.52 | ||
Maximum of Months | 0.122379E+11 | 21517.71 | 35.73 | 17.17 | 0.684942E+09 | 1075.02 | 29.63 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247420E+10 | 7667.27 | 26-JAN-16:30 | 10.30 | 1.37 | 0.322664E+09 | 527.04 | 26-JAN-14:00 | 10.60 | 1.70 |
February | 0.316424E+10 | 11386.25 | 15-FEB-16:30 | 16.95 | 6.15 | 0.300753E+09 | 544.91 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.511734E+10 | 12086.84 | 07-MAR-16:30 | 21.15 | 8.76 | 0.369037E+09 | 544.89 | 08-MAR-14:00 | 22.20 | 9.07 |
April | 0.708117E+10 | 22601.17 | 16-APR-17:12 | 20.20 | 7.93 | 0.353346E+09 | 544.94 | 14-APR-13:00 | 23.30 | 10.23 |
May | 0.858381E+10 | 23071.66 | 29-MAY-16:21 | 26.65 | 13.14 | 0.388165E+09 | 544.95 | 15-MAY-13:09 | 26.88 | 10.23 |
June | 0.107395E+11 | 27101.13 | 11-JUN-17:01 | 28.22 | 13.05 | 0.405200E+09 | 544.99 | 30-JUN-13:50 | 28.08 | 17.81 |
July | 0.112799E+11 | 25374.64 | 04-JUL-17:01 | 35.73 | 14.59 | 0.383099E+09 | 544.95 | 05-JUL-09:00 | 29.40 | 16.78 |
August | 0.114428E+11 | 26504.90 | 13-AUG-16:31 | 30.73 | 17.19 | 0.426976E+09 | 545.03 | 28-AUG-13:30 | 23.30 | 16.29 |
September | 0.864592E+10 | 22889.35 | 04-SEP-17:21 | 26.15 | 15.89 | 0.363684E+09 | 544.96 | 13-SEP-13:39 | 26.67 | 14.53 |
October | 0.646906E+10 | 22421.20 | 01-OCT-15:21 | 28.60 | 13.04 | 0.354392E+09 | 544.95 | 02-OCT-13:50 | 26.52 | 15.41 |
November | 0.380328E+10 | 9819.75 | 02-NOV-16:00 | 16.70 | 9.77 | 0.335202E+09 | 544.91 | 24-NOV-14:00 | 15.60 | 5.14 |
December | 0.236327E+10 | 6463.86 | 29-DEC-16:00 | 11.70 | 3.86 | 0.313139E+09 | 533.13 | 20-DEC-14:00 | 7.00 | 0.44 |
Annual Sum or Average | 0.811645E+11 | 0.431566E+10 | ||||||||
Minimum of Months | 0.236327E+10 | 6463.86 | 10.30 | 1.37 | 0.300753E+09 | 527.04 | 7.00 | 0.44 | ||
Maximum of Months | 0.114428E+11 | 27101.13 | 35.73 | 17.19 | 0.426976E+09 | 545.03 | 29.40 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352668E+10 | 6089.58 | 03-JAN-06:12 | -1.7 | -2.9 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.371122E+10 | 5866.09 | 21-FEB-06:10 | 3.40 | 0.80 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.570847E+10 | 5732.71 | 20-MAR-05:15 | 8.13 | 4.31 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.700767E+10 | 7463.11 | 18-APR-05:13 | 7.03 | 0.68 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.707460E+10 | 9897.28 | 30-MAY-05:13 | 14.43 | 10.89 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.867633E+10 | 9529.55 | 05-JUN-05:13 | 15.00 | 12.60 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.955768E+10 | 8385.73 | 10-JUL-05:13 | 20.20 | 15.69 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.105493E+11 | 8401.15 | 22-AUG-05:01 | 21.52 | 15.20 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.777732E+10 | 11657.24 | 05-SEP-05:13 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.691843E+10 | 10288.46 | 10-OCT-05:13 | 13.90 | 11.13 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.540802E+10 | 6692.43 | 24-NOV-06:15 | 2.97 | -1.9 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.445585E+10 | 6154.46 | 26-DEC-06:15 | -1.0 | -1.9 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.803715E+11 | 0.00 | ||||||||
Minimum of Months | 0.352668E+10 | 5732.71 | -1.7 | -2.9 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.105493E+11 | 11657.24 | 21.52 | 15.69 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149779E+10 | 6460.77 | 17-JAN-05:01 | -3.3 | -4.9 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.169121E+10 | 6363.57 | 06-FEB-05:01 | -4.4 | -6.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.309851E+10 | 4838.47 | 18-MAR-05:06 | 1.02 | 0.29 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.430590E+10 | 6407.89 | 29-APR-05:13 | 10.37 | 2.73 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.534486E+10 | 6317.76 | 23-MAY-05:01 | 14.40 | 9.65 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.689375E+10 | 8489.02 | 29-JUN-05:01 | 24.40 | 16.06 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.759214E+10 | 9004.94 | 14-JUL-05:01 | 17.67 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.774949E+10 | 9363.27 | 17-AUG-05:01 | 20.60 | 14.37 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.611817E+10 | 7910.96 | 30-SEP-05:01 | 16.42 | 11.13 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.460688E+10 | 6191.97 | 06-OCT-05:13 | 12.80 | 7.63 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.274875E+10 | 4908.01 | 24-NOV-06:08 | 2.88 | -1.9 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.161808E+10 | 5632.65 | 23-DEC-06:01 | -5.5 | -7.8 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.532655E+11 | 0.00 | ||||||||
Minimum of Months | 0.149779E+10 | 4838.47 | -5.5 | -7.8 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.774949E+10 | 9363.27 | 24.40 | 16.06 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.894980E+09 | 4546.42 | 05-JAN-14:30 | 16.10 | 6.82 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.187693E+10 | 8999.62 | 15-FEB-15:20 | 17.20 | 6.59 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.434288E+10 | 11888.08 | 08-MAR-14:00 | 22.80 | 9.65 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.796437E+10 | 17052.81 | 28-APR-14:00 | 24.40 | 10.25 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.106321E+11 | 19557.25 | 30-MAY-14:30 | 27.20 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.151714E+11 | 23692.64 | 28-JUN-14:30 | 38.05 | 14.18 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.168966E+11 | 23475.40 | 21-JUL-14:30 | 37.80 | 15.26 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.161598E+11 | 22983.90 | 07-AUG-14:00 | 33.30 | 15.88 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.110644E+11 | 18817.64 | 01-SEP-14:20 | 28.90 | 16.78 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.619621E+10 | 15192.26 | 05-OCT-14:30 | 26.70 | 12.34 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.192551E+10 | 8012.28 | 02-NOV-14:40 | 16.67 | 9.17 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.500151E+09 | 3965.10 | 31-DEC-14:47 | 10.92 | 2.09 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.936253E+11 | 0.00 | ||||||||
Minimum of Months | 0.500151E+09 | 3965.10 | 10.92 | 2.09 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.168966E+11 | 23692.64 | 38.05 | 16.78 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343975E+10 | 2363.51 | 26-JAN-17:00 | 10.00 | 1.18 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.803966E+10 | 4381.93 | 15-FEB-17:00 | 16.70 | 5.82 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.143007E+11 | 6306.79 | 24-MAR-17:40 | 16.83 | 5.25 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.189477E+11 | 8204.90 | 15-APR-17:55 | 7.20 | 4.15 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.441628E+10 | 2422.61 | 20-MAY-18:16 | 25.77 | 10.29 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.930816E+10 | 4639.13 | 11-JUN-18:45 | 25.47 | 12.10 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.146336E+11 | 6581.36 | 04-JUL-18:51 | 32.20 | 13.40 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.192688E+11 | 7519.33 | 10-AUG-19:00 | 19.40 | 15.66 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.437851E+10 | 2419.53 | 02-SEP-17:50 | 30.18 | 15.03 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.945472E+10 | 4458.68 | 15-OCT-16:52 | 20.60 | 7.78 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.138159E+11 | 6244.46 | 06-NOV-16:40 | 14.40 | 4.26 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.192548E+11 | 8046.34 | 31-DEC-16:33 | 9.27 | 1.18 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.139259E+12 | 0.00 | ||||||||
Minimum of Months | 0.343975E+10 | 2363.51 | 7.20 | 1.18 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.192688E+11 | 8204.90 | 32.20 | 15.66 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206190E+10 | 2203.86 | 26-JAN-17:00 | 10.00 | 1.18 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.667279E+10 | 4122.60 | 15-FEB-17:10 | 16.05 | 5.51 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.128197E+11 | 5977.76 | 24-MAR-17:40 | 16.83 | 5.25 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.176320E+11 | 7654.22 | 07-APR-17:50 | 11.28 | 2.25 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.376495E+10 | 2310.53 | 20-MAY-18:17 | 25.77 | 10.29 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.865878E+10 | 4333.15 | 18-JUN-18:23 | 29.15 | 10.39 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.138811E+11 | 6254.94 | 04-JUL-18:34 | 32.77 | 13.49 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.182385E+11 | 7144.06 | 10-AUG-19:00 | 19.40 | 15.66 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.376199E+10 | 2283.10 | 28-SEP-17:00 | 28.30 | 13.86 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.834803E+10 | 4202.17 | 04-OCT-17:00 | 26.10 | 12.20 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.122164E+11 | 5874.90 | 02-NOV-16:40 | 16.30 | 9.63 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.169194E+11 | 7499.35 | 29-DEC-16:50 | 10.28 | 3.12 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.124976E+12 | 0.00 | ||||||||
Minimum of Months | 0.206190E+10 | 2203.86 | 10.00 | 1.18 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.182385E+11 | 7654.22 | 32.77 | 15.66 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.826409E+09 | 2129.92 | 26-JAN-17:00 | 10.00 | 1.18 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.515709E+10 | 4141.53 | 15-FEB-17:00 | 16.70 | 5.82 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.117629E+11 | 6021.21 | 24-MAR-17:40 | 16.83 | 5.25 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.171336E+11 | 7686.03 | 05-APR-18:00 | 15.60 | 3.48 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.351827E+10 | 2478.31 | 20-MAY-18:10 | 26.23 | 10.60 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.863714E+10 | 4627.64 | 18-JUN-18:23 | 29.15 | 10.39 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.139841E+11 | 6510.21 | 04-JUL-19:11 | 31.27 | 13.29 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.183653E+11 | 7226.68 | 28-AUG-18:50 | 21.05 | 14.65 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.358046E+10 | 2392.95 | 02-SEP-17:48 | 30.18 | 15.03 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.758987E+10 | 4281.78 | 04-OCT-17:00 | 26.10 | 12.20 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.107342E+11 | 5870.06 | 02-NOV-16:40 | 16.30 | 9.63 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.148491E+11 | 7418.42 | 29-DEC-16:50 | 10.28 | 3.12 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.116138E+12 | 0.00 | ||||||||
Minimum of Months | 0.826409E+09 | 2129.92 | 10.00 | 1.18 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.183653E+11 | 7686.03 | 31.27 | 15.03 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241798E+12 | 308073.89 | 29-JAN-10:11 | 6.67 | 1.67 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.437796E+12 | 351650.04 | 25-FEB-20:07 | 4.22 | 0.04 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.730597E+12 | 398205.51 | 18-MAR-04:32 | 1.10 | 0.28 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.942903E+12 | 370760.21 | 06-APR-03:02 | 2.70 | -1.5 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.241025E+12 | 306492.70 | 12-MAY-05:02 | 9.60 | 2.78 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.470039E+12 | 327158.84 | 09-JUN-03:03 | 8.72 | 6.37 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.731973E+12 | 275464.79 | 05-JUL-16:00 | 32.80 | 16.74 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.968896E+12 | 367690.88 | 31-AUG-06:05 | 13.63 | 11.20 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.236262E+12 | 152677.00 | 01-SEP-00:02 | 21.88 | 14.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.488779E+12 | 352727.35 | 23-OCT-03:43 | 7.88 | 6.67 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.711393E+12 | 376211.21 | 22-NOV-00:46 | 6.88 | 2.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.978001E+12 | 384701.14 | 01-DEC-00:05 | 5.13 | 1.83 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.717946E+13 | 0.00 | ||||||||
Minimum of Months | 0.236262E+12 | 152677.00 | 1.10 | -1.5 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.978001E+12 | 398205.51 | 32.80 | 16.74 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585241E+09 | 144299.46 | 19-JAN-04:24 | -2.8 |
February | 0.369442E+09 | 136902.68 | 20-FEB-21:38 | 5.20 |
March | 0.298119E+09 | 144451.03 | 04-MAR-04:45 | -1.1 |
April | 0.421621E+09 | 135662.96 | 02-APR-19:44 | 17.38 |
May | 0.436884E+09 | 132473.20 | 14-MAY-19:57 | 22.80 |
June | 0.604651E+09 | 142587.72 | 25-JUN-14:27 | 34.15 |
July | 0.825699E+09 | 148010.12 | 02-JUL-15:28 | 31.95 |
August | 0.588600E+09 | 146969.11 | 20-AUG-09:19 | 26.83 |
September | 0.951855E+09 | 147233.46 | 03-SEP-09:17 | 26.33 |
October | 0.707307E+09 | 137283.33 | 01-OCT-12:49 | 26.93 |
November | 0.622797E+09 | 136666.93 | 19-NOV-20:27 | 8.60 |
December | 0.733025E+09 | 129633.20 | 24-DEC-17:47 | 8.68 |
Annual Sum or Average | 0.714524E+10 | |||
Minimum of Months | 0.298119E+09 | 129633.20 | -2.8 | |
Maximum of Months | 0.951855E+09 | 148010.12 | 34.15 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.977203E+09 | 77014.98 | 17-JAN-05:01 | -3.3 |
February | 0.353010E+09 | 76661.87 | 06-FEB-05:11 | -4.4 |
March | 11329702.46 | 67404.38 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.159239E+09 | 72064.33 | 27-NOV-05:01 | -4.0 |
December | 0.699309E+09 | 76915.42 | 26-DEC-05:11 | -0.9 |
Annual Sum or Average | 0.220009E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.977203E+09 | 77014.98 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11703.71 | 195.06 | 21-JAN-06:04 | -6.5 |
February | 75044.95 | 1243.65 | 04-FEB-06:01 | -6.7 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 2385679.27 | 4818.57 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 2472427.94 | |||
Minimum of Months | 0.00 | 0.00 | -6.7 | |
Maximum of Months | 2385679.27 | 4818.57 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5271470.55 | 8789.41 | 17-JAN-06:01 | -3.4 |
February | 3090956.88 | 8818.07 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 161430.85 | 2690.51 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 8523858.29 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 5271470.55 | 8818.07 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329369E+09 | 11797.79 | 17-JAN-04:01 | -3.3 |
February | 0.179015E+09 | 11767.35 | 06-FEB-04:01 | -4.4 |
March | 14284750.74 | 10326.41 | 06-MAR-06:01 | -2.9 |
April | 168590.12 | 2809.84 | 08-APR-05:01 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 367475.33 | 4704.15 | 26-OCT-05:01 | -2.5 |
November | 40878370.24 | 10795.49 | 27-NOV-05:01 | -4.0 |
December | 0.274479E+09 | 10923.13 | 14-DEC-05:01 | -2.9 |
Annual Sum or Average | 0.838563E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.329369E+09 | 11797.79 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192851E+09 | 11916.09 | 17-JAN-05:01 | -3.3 |
February | 96027778.09 | 11828.91 | 06-FEB-05:21 | -4.4 |
March | 6093389.90 | 10908.64 | 04-MAR-06:01 | -1.7 |
April | 138685.01 | 2311.42 | 08-APR-05:01 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 2261001.27 | 9116.78 | 26-OCT-05:01 | -2.5 |
November | 18560255.39 | 10956.18 | 28-NOV-06:01 | -2.1 |
December | 0.161140E+09 | 11052.37 | 14-DEC-05:01 | -2.9 |
Annual Sum or Average | 0.477072E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.192851E+09 | 11916.09 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97068989.94 | 12471.87 | 17-JAN-05:01 | -3.3 |
February | 52564757.77 | 12320.09 | 06-FEB-05:01 | -4.4 |
March | 3550180.04 | 11231.09 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 73537.09 | 1225.62 | 26-OCT-05:01 | -2.5 |
November | 2667093.90 | 9354.40 | 27-NOV-06:03 | -4.4 |
December | 50476180.97 | 11279.68 | 09-DEC-06:01 | -4.2 |
Annual Sum or Average | 0.206401E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 97068989.94 | 12471.87 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101432E+09 | 11242.69 | 17-JAN-05:01 | -3.3 |
February | 60098949.41 | 11071.58 | 06-FEB-05:01 | -4.4 |
March | 3454940.62 | 10200.37 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 312745.91 | 3723.78 | 26-OCT-05:01 | -2.5 |
November | 7720720.29 | 9863.60 | 25-NOV-06:01 | 1.10 |
December | 73124424.76 | 10019.74 | 08-DEC-06:01 | -3.2 |
Annual Sum or Average | 0.246144E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.101432E+09 | 11242.69 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234348E+10 | 15871.10 | 17-JAN-01:41 | -3.2 |
February | 0.148346E+10 | 15506.29 | 06-FEB-03:13 | -4.8 |
March | 0.467853E+09 | 13604.26 | 04-MAR-05:01 | -1.2 |
April | 44725948.99 | 12182.80 | 08-APR-05:01 | 2.62 |
May | 3055414.71 | 11848.91 | 06-MAY-05:01 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.144515E+09 | 12981.79 | 26-OCT-04:02 | -2.8 |
November | 0.788761E+09 | 14909.75 | 27-NOV-04:11 | -3.9 |
December | 0.223716E+10 | 15201.15 | 25-DEC-19:16 | 1.67 |
Annual Sum or Average | 0.751301E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.8 | |
Maximum of Months | 0.234348E+10 | 15871.10 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122447E+10 | 16913.39 | 17-JAN-01:41 | -3.2 |
February | 0.729293E+09 | 16438.72 | 06-FEB-03:51 | -4.4 |
March | 0.195736E+09 | 14455.06 | 04-MAR-05:01 | -1.2 |
April | 15982367.04 | 12785.11 | 08-APR-05:01 | 2.62 |
May | 1412853.65 | 7232.81 | 06-MAY-05:01 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 75723762.40 | 13704.01 | 26-OCT-04:02 | -2.8 |
November | 0.334881E+09 | 15719.57 | 27-NOV-04:11 | -3.9 |
December | 0.112867E+10 | 15614.74 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.370617E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.122447E+10 | 16913.39 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120502E+10 | 16822.80 | 17-JAN-01:41 | -3.2 |
February | 0.767897E+09 | 16415.02 | 06-FEB-03:51 | -4.4 |
March | 0.247106E+09 | 14392.95 | 04-MAR-05:01 | -1.2 |
April | 29126260.41 | 13034.79 | 08-APR-05:01 | 2.62 |
May | 2024616.99 | 11938.19 | 05-MAY-05:01 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 77074948.46 | 13847.57 | 26-OCT-04:02 | -2.8 |
November | 0.238391E+09 | 14804.34 | 27-NOV-04:11 | -3.9 |
December | 0.104172E+10 | 15839.26 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.360836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.120502E+10 | 16822.80 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.920768E+09 | 17240.81 | 17-JAN-01:41 | -3.2 |
February | 0.536544E+09 | 16405.42 | 06-FEB-04:01 | -4.4 |
March | 0.130354E+09 | 14380.29 | 04-MAR-05:01 | -1.2 |
April | 5379327.87 | 12921.49 | 08-APR-05:01 | 2.62 |
May | 701184.95 | 7635.24 | 05-MAY-05:01 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 43298859.32 | 13320.13 | 26-OCT-04:02 | -2.8 |
November | 0.224300E+09 | 14734.04 | 27-NOV-04:11 | -3.9 |
December | 0.782307E+09 | 15783.39 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.264365E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.920768E+09 | 17240.81 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58489647.41 | 10797.23 | 17-JAN-05:01 | -3.3 |
February | 53405938.41 | 10788.39 | 06-FEB-05:01 | -4.4 |
March | 72792590.70 | 11403.86 | 20-MAR-03:02 | 11.32 |
April | 0.114106E+09 | 11444.43 | 03-APR-03:02 | 9.22 |
May | 56543856.99 | 10723.60 | 01-MAY-03:02 | 11.85 |
June | 70650803.71 | 10814.24 | 05-JUN-03:01 | 15.00 |
July | 92258034.21 | 6853.34 | 01-JUL-03:01 | 19.13 |
August | 74606135.81 | 8132.89 | 20-AUG-15:51 | 35.00 |
September | 44432116.75 | 9437.30 | 04-SEP-08:61 | 19.50 |
October | 66870399.60 | 10462.86 | 16-OCT-03:02 | 13.80 |
November | 85691028.60 | 10933.17 | 09-NOV-04:01 | 12.80 |
December | 0.100984E+09 | 12954.39 | 14-DEC-04:01 | -1.4 |
Annual Sum or Average | 0.890830E+09 | |||
Minimum of Months | 44432116.75 | 6853.34 | -4.4 | |
Maximum of Months | 0.114106E+09 | 12954.39 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505988E+09 | 6992.84 | 01-JAN-10:20 | 6.10 |
February | 0.226952E+09 | 7081.40 | 15-FEB-05:01 | 7.70 |
March | 36351728.17 | 8923.05 | 14-MAR-05:01 | 6.02 |
April | 40661649.40 | 6906.22 | 24-APR-04:01 | 6.10 |
May | 43824517.28 | 6876.18 | 18-MAY-04:03 | 12.20 |
June | 38462761.84 | 7160.07 | 22-JUN-03:01 | 19.82 |
July | 34042432.55 | 7469.31 | 19-JUL-03:01 | 20.82 |
August | 28258396.80 | 7771.39 | 22-AUG-03:01 | 21.20 |
September | 29724544.12 | 6295.36 | 12-SEP-03:01 | 18.30 |
October | 42273368.95 | 6710.77 | 16-OCT-05:02 | 13.12 |
November | 0.118069E+09 | 7464.61 | 29-NOV-06:01 | 3.72 |
December | 0.407728E+09 | 6584.21 | 01-DEC-06:01 | 3.90 |
Annual Sum or Average | 0.155234E+10 | |||
Minimum of Months | 28258396.80 | 6295.36 | 3.72 | |
Maximum of Months | 0.505988E+09 | 8923.05 | 21.20 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526314E+10 | 23620.87 | 17-JAN-05:12 | -3.3 |
February | 0.362569E+10 | 23694.53 | 06-FEB-06:01 | -4.6 |
March | 0.203386E+10 | 12287.29 | 06-MAR-06:01 | -2.9 |
April | 0.775148E+09 | 22536.07 | 19-APR-05:01 | 4.08 |
May | 0.350089E+09 | 22156.77 | 02-MAY-05:01 | 6.20 |
June | 0.134112E+09 | 21486.07 | 09-JUN-05:01 | 7.98 |
July | 73530886.58 | 13717.47 | 08-JUL-05:01 | 16.88 |
August | 77872235.49 | 14140.55 | 31-AUG-04:02 | 15.32 |
September | 0.161264E+09 | 18051.75 | 27-SEP-05:01 | 11.60 |
October | 0.116526E+10 | 22453.83 | 12-OCT-05:01 | 6.70 |
November | 0.246942E+10 | 19057.49 | 01-NOV-05:01 | 7.70 |
December | 0.517253E+10 | 19423.94 | 26-DEC-06:03 | -0.8 |
Annual Sum or Average | 0.213019E+11 | |||
Minimum of Months | 73530886.58 | 12287.29 | -4.6 | |
Maximum of Months | 0.526314E+10 | 23694.53 | 16.88 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3289528.04 | 589.75 | 17-JAN-05:08 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 3289528.04 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 3289528.04 | 589.75 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.636398E+09 | 671.90 | 03-JAN-01:42 | 1.20 |
February | 4133481.92 | 609.40 | 06-FEB-04:05 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.640531E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.636398E+09 | 671.90 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226040E+10 | 94859.57 | 16-JAN-01:41 | 1.52 |
February | 47159920.11 | 34138.83 | 26-FEB-08:51 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.00 |
May | 0.195555E+09 | 65210.47 | 02-MAY-03:31 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.88 |
October | 52445727.43 | 32651.23 | 15-OCT-03:21 | 6.95 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.255556E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.52 | |
Maximum of Months | 0.226040E+10 | 94859.57 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.215029E+11 | 22401.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.195042E+11 | 22401.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.231659E+11 | 22401.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.207025E+11 | 22401.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.223344E+11 | 22401.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.222225E+11 | 22401.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.208144E+11 | 22401.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.231659E+11 | 22401.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.207025E+11 | 22401.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.215029E+11 | 22401.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.212480E+11 | 22401.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.208144E+11 | 22401.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.257680E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.195042E+11 | 22401.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.231659E+11 | 22401.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.606290E+10 | 6316.16 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.549934E+10 | 6316.16 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.653179E+10 | 6316.16 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.583722E+10 | 6316.16 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.629734E+10 | 6316.16 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.626579E+10 | 6316.16 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.586877E+10 | 6316.16 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.653179E+10 | 6316.16 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.583722E+10 | 6316.16 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.606290E+10 | 6316.16 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.599102E+10 | 6316.16 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.586877E+10 | 6316.16 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.549934E+10 | 6316.16 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.653179E+10 | 6316.16 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.223344E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.222225E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.212480E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.257680E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746197E+09 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690472E+09 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671603E+09 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1295593.61 | 0.468913E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12873301.77 | 0.318683E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59040064.71 | 0.162241E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85485447.28 | 78200621.50 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43586707.31 | 0.103181E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14593862.00 | 0.189343E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3450673.39 | 0.362201E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598996E+09 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699503E+09 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.220326E+09 | 0.508953E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78200621.50 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85485447.28 | 0.746197E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491019E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450019E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433499E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1366102.28 | 0.298175E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9799391.72 | 0.209226E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43365854.51 | 99295358.24 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63282894.42 | 41126439.41 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35106075.89 | 50861091.75 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11385818.35 | 0.120053E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2833692.39 | 0.233586E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388248E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450080E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 0.167140E+09 | 0.326519E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41126439.41 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63282894.42 | 0.491019E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766779E+09 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708789E+09 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676942E+09 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1222156.81 | 0.468182E+09 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12792620.83 | 0.314847E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60116729.21 | 0.158444E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85405899.71 | 77405405.65 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42334358.57 | 0.104131E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12534724.30 | 0.197190E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2343080.07 | 0.378938E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625562E+09 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718766E+09 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 0.216750E+09 | 0.519598E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77405405.65 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85405899.71 | 0.766779E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506758E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480512E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479653E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724006.44 | 0.349986E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7572575.54 | 0.226670E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35969849.74 | 0.118854E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52794305.42 | 59423734.40 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25397442.95 | 82412613.29 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9701682.92 | 0.136343E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2117826.19 | 0.259351E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426330E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503793E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 0.134278E+09 | 0.363009E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59423734.40 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52794305.42 | 0.506758E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150206E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140385E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137717E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221799.33 | 0.976216E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30789997.01 | 0.672975E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131146E+09 | 0.359640E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187471E+09 | 0.202724E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96836949.88 | 0.266490E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34463758.78 | 0.395588E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8339818.13 | 0.741924E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120561E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137925E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.492269E+09 | 0.104835E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202724E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187471E+09 | 0.150206E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101641E+10 |
February | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945361E+09 |
March | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925225E+09 |
April | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3134449.23 | 0.679301E+09 |
May | 0.744847E+09 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21610814.13 | 0.458932E+09 |
June | 0.742030E+09 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92300788.94 | 0.236728E+09 |
July | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128900E+09 | 0.136783E+09 |
August | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68193195.45 | 0.176440E+09 |
September | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26299634.54 | 0.261692E+09 |
October | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6852125.94 | 0.500826E+09 |
November | 0.708685E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814362E+09 |
December | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930335E+09 |
Annual Sum or Average | 0.858171E+10 | 0.187251E+11 | 0.259975E+11 | 0.347291E+09 | 0.708240E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136783E+09 |
Maximum of Months | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128900E+09 | 0.101641E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168546E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155700E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146951E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2492196.85 | 0.102086E+10 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28991175.78 | 0.679512E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133396E+09 | 0.356548E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186708E+09 | 0.204302E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91727603.92 | 0.277728E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25878044.43 | 0.436093E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3964677.80 | 0.840996E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137316E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156168E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 0.473157E+09 | 0.114628E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204302E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186708E+09 | 0.168546E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103712E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971853E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952407E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1740157.39 | 0.703201E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18769573.48 | 0.469746E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83013177.54 | 0.255209E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124619E+09 | 0.145322E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62736105.98 | 0.192615E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23617772.57 | 0.278862E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5702184.16 | 0.518080E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834244E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957960E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 0.320197E+09 | 0.731662E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145322E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124619E+09 | 0.103712E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167931E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159702E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157504E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3940790.45 | 0.113741E+10 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36287731.53 | 0.801318E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156967E+09 | 0.434356E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222029E+09 | 0.253482E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113905E+09 | 0.328044E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41601632.06 | 0.472674E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10555839.72 | 0.847388E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134021E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153031E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.585286E+09 | 0.119966E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253482E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222029E+09 | 0.167931E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114545E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108594E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107984E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3113511.04 | 0.812371E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24241493.56 | 0.558640E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107958E+09 | 0.292460E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150299E+09 | 0.174969E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78460921.28 | 0.223212E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29724839.14 | 0.320910E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7932501.51 | 0.589197E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921295E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103998E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 0.401730E+09 | 0.824426E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174969E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150299E+09 | 0.114545E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189716E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177968E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169984E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2868223.10 | 0.119581E+10 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34416247.59 | 0.809567E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160262E+09 | 0.430272E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222164E+09 | 0.255059E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108862E+09 | 0.341790E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31903948.62 | 0.523315E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5735226.03 | 0.976498E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155807E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175028E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 0.566211E+09 | 0.132173E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255059E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222164E+09 | 0.189716E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118566E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112855E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111559E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1939661.14 | 0.835096E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23421466.20 | 0.562998E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101429E+09 | 0.309374E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151932E+09 | 0.179869E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76112162.27 | 0.236328E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28896111.05 | 0.337151E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7286028.76 | 0.609507E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956927E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109223E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 0.391016E+09 | 0.854927E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179869E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151932E+09 | 0.118566E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.606290E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.549934E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.653179E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.583722E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.629734E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.626579E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.586877E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.583722E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.606290E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.599102E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.586877E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.549934E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154173E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141822E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137233E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690342.89 | 0.965624E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19303730.83 | 0.647138E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100106E+09 | 0.334339E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148515E+09 | 0.172032E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70919417.43 | 0.236565E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21388806.73 | 0.384784E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3888267.86 | 0.746875E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123671E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143678E+10 |
Annual Sum or Average | 0.364811E+09 | 0.104931E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172032E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148515E+09 | 0.154173E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265168E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245537E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237521E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1636637.02 | 0.167065E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38392642.11 | 0.112996E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183613E+09 | 0.588896E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272218E+09 | 0.313564E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130768E+09 | 0.434760E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40811538.78 | 0.666440E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7656875.92 | 0.129379E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213525E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244865E+10 |
Annual Sum or Average | 0.675097E+09 | 0.181642E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313564E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272218E+09 | 0.265168E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260906E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250210E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249619E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27935.40 | 0.183846E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16917392.39 | 0.125832E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157466E+09 | 0.649205E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229134E+09 | 0.361443E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104157E+09 | 0.493266E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25389960.60 | 0.734549E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3148015.89 | 0.134523E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214750E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239596E+10 |
Annual Sum or Average | 0.536240E+09 | 0.188313E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361443E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229134E+09 | 0.260906E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22401.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22401.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22401.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22401.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22401.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22401.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22401.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22401.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22401.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22401.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22401.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22401.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2135.93 | 16-JAN-17:51 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1617.51 | 05-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1439.11 | 14-MAR-02:52 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 29-APR-17:10 | 1555.32 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.77 | 14-MAY-17:10 | 958.95 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.45 | 18-JUN-16:00 | 741.90 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.99 | 04-JUL-14:51 | 341.22 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.28 | 05-AUG-17:01 | 374.32 | 10-AUG-21:30 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.01 | 03-SEP-14:50 | 545.87 | 18-SEP-00:55 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.05 | 01-OCT-16:20 | 881.99 | 11-OCT-22:51 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1618.87 | 26-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2285.97 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.22 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 556.99 | 2285.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1415.05 | 16-JAN-17:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1062.75 | 05-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 933.73 | 14-MAR-02:52 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.34 | 29-APR-17:10 | 1001.71 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 14-MAY-17:10 | 616.37 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.74 | 18-JUN-16:00 | 475.43 | 10-JUN-01:20 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.62 | 04-JUL-15:10 | 209.23 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.54 | 05-AUG-17:10 | 298.86 | 27-AUG-08:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.33 | 03-SEP-15:10 | 363.00 | 18-SEP-00:55 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.83 | 01-OCT-16:20 | 568.80 | 11-OCT-22:51 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1049.08 | 26-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1472.86 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.23 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 410.62 | 1472.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2097.52 | 16-JAN-17:51 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1651.44 | 05-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1441.03 | 14-MAR-02:52 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 29-APR-16:00 | 1556.18 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.59 | 14-MAY-17:10 | 944.12 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.58 | 18-JUN-16:00 | 724.24 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.50 | 04-JUL-14:51 | 348.29 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.14 | 05-AUG-17:01 | 379.55 | 10-AUG-21:30 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.38 | 03-SEP-15:10 | 566.75 | 18-SEP-00:55 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.62 | 01-OCT-16:20 | 902.20 | 11-OCT-22:51 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1615.98 | 03-NOV-23:52 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2305.06 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.29 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 550.50 | 2305.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1452.83 | 16-JAN-17:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1152.06 | 05-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1050.22 | 14-MAR-02:52 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 29-APR-16:00 | 1150.84 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.11 | 14-MAY-17:10 | 682.83 | 18-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.68 | 18-JUN-14:00 | 571.94 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.20 | 04-JUL-15:05 | 266.94 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.65 | 20-AUG-17:00 | 342.69 | 22-AUG-21:30 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | 03-SEP-15:10 | 404.90 | 18-SEP-00:55 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 01-OCT-16:20 | 635.94 | 11-OCT-22:51 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1159.88 | 03-NOV-23:52 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1654.35 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.94 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 332.20 | 1654.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4029.21 | 16-JAN-17:51 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3171.38 | 05-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2775.83 | 14-MAR-02:52 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.15 | 01-APR-17:01 | 3179.96 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.70 | 14-MAY-17:10 | 1993.83 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1025.77 | 18-JUN-16:00 | 1502.83 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.31 | 04-JUL-14:51 | 804.64 | 15-JUL-18:52 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.07 | 05-AUG-17:01 | 781.73 | 08-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.22 | 03-SEP-14:50 | 1081.92 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.41 | 01-OCT-16:30 | 1845.06 | 11-OCT-22:51 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3201.01 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4389.76 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.73 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.31 | 4389.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2727.40 | 16-JAN-17:51 |
February | 1239.33 | 01-FEB-08:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2143.68 | 05-FEB-00:51 |
March | 1239.33 | 01-MAR-08:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1871.71 | 14-MAR-02:52 |
April | 1239.33 | 03-APR-07:10 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.60 | 29-APR-17:50 | 2135.46 | 23-APR-09:00 |
May | 1239.33 | 01-MAY-07:10 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.68 | 14-MAY-17:10 | 1287.10 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.25 | 18-JUN-16:00 | 986.92 | 10-JUN-01:30 |
July | 1239.33 | 03-JUL-07:10 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.22 | 04-JUL-15:10 | 558.90 | 15-JUL-18:52 |
August | 1239.33 | 01-AUG-07:10 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.42 | 05-AUG-17:01 | 659.04 | 27-AUG-08:10 |
September | 1239.33 | 01-SEP-07:10 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.35 | 03-SEP-15:10 | 730.89 | 18-SEP-00:55 |
October | 1239.33 | 02-OCT-07:10 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.51 | 01-OCT-16:30 | 1211.57 | 11-OCT-22:51 |
November | 1239.33 | 01-NOV-07:10 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2086.02 | 03-NOV-23:52 |
December | 1239.33 | 01-DEC-08:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2934.68 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.90 | |||||
Maximum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 886.22 | 2934.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4413.59 | 16-JAN-17:51 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3505.88 | 05-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2943.18 | 14-MAR-02:52 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.03 | 29-APR-17:01 | 3248.62 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.74 | 14-MAY-17:10 | 1984.16 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.95 | 18-JUN-16:00 | 1491.05 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.34 | 04-JUL-14:51 | 821.80 | 15-JUL-18:52 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 700.33 | 05-AUG-17:01 | 808.41 | 08-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.97 | 03-SEP-15:10 | 1183.22 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.26 | 01-OCT-15:48 | 1936.83 | 11-OCT-22:51 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3408.49 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4743.08 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.41 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.34 | 4743.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2821.88 | 16-JAN-17:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2254.08 | 05-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1901.73 | 14-MAR-02:52 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 29-APR-14:40 | 2328.70 | 15-APR-17:08 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.08 | 14-MAY-13:00 | 1350.74 | 18-MAY-03:01 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 657.39 | 18-JUN-13:20 | 1091.57 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.85 | 04-JUL-14:51 | 585.76 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.73 | 06-AUG-14:20 | 605.27 | 08-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.41 | 03-SEP-15:10 | 819.21 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.87 | 01-OCT-16:10 | 1264.39 | 11-OCT-22:51 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2184.35 | 03-NOV-23:52 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3010.49 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.76 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 778.85 | 3010.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4426.85 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3458.94 | 05-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3212.87 | 14-MAR-04:53 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.07 | 01-APR-17:01 | 3733.44 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 603.72 | 14-MAY-16:52 | 2323.16 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201.03 | 18-JUN-16:10 | 1741.12 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.06 | 04-JUL-15:07 | 1048.41 | 15-JUL-18:52 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 839.79 | 05-AUG-17:01 | 965.97 | 08-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.48 | 03-SEP-15:00 | 1263.53 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.51 | 01-OCT-16:10 | 2195.65 | 11-OCT-22:51 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3783.07 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4969.27 | 14-DEC-04:07 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.97 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.06 | 4969.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2951.28 | 16-JAN-17:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2342.63 | 05-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2142.02 | 14-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.86 | 01-APR-17:50 | 2568.77 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.95 | 14-MAY-16:52 | 1509.70 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 949.97 | 18-JUN-16:10 | 1158.74 | 04-JUN-17:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.61 | 04-JUL-15:10 | 729.49 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.36 | 05-AUG-17:01 | 792.46 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.61 | 03-SEP-14:40 | 877.55 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.97 | 01-OCT-16:10 | 1450.84 | 11-OCT-22:51 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2522.43 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3318.88 | 14-DEC-04:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.49 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.61 | 3318.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4489.26 | 16-JAN-17:51 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3858.41 | 05-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3326.00 | 14-MAR-02:52 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 | 01-APR-17:50 | 3830.06 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 613.75 | 14-MAY-16:52 | 2311.95 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1234.84 | 18-JUN-16:10 | 1727.42 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1438.90 | 04-JUL-15:07 | 1067.60 | 15-JUL-18:52 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 808.44 | 05-AUG-17:01 | 997.80 | 08-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.00 | 03-SEP-14:40 | 1460.76 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.00 | 01-OCT-16:07 | 2305.53 | 11-OCT-22:51 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4021.50 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5237.52 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.80 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1438.90 | 5237.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2951.52 | 16-JAN-17:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2521.44 | 05-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2165.63 | 14-MAR-02:52 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.18 | 29-APR-14:50 | 2811.50 | 15-APR-17:10 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 455.80 | 21-MAY-17:00 | 1581.20 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 797.00 | 18-JUN-13:30 | 1275.65 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 927.81 | 04-JUL-15:05 | 756.80 | 15-JUL-18:52 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.75 | 06-AUG-14:20 | 739.88 | 08-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.16 | 03-SEP-16:40 | 1016.16 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.02 | 01-OCT-16:07 | 1508.94 | 11-OCT-22:51 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2562.27 | 03-NOV-21:10 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3382.04 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.88 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 927.81 | 3382.04 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 6316.16 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6316.16 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 6316.16 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 6316.16 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 6316.16 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 6316.16 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 6316.16 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 6316.16 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 6316.16 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 6316.16 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 6316.16 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 6316.16 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 6316.16 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 6316.16 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4408.92 | 16-JAN-17:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3413.78 | 05-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2936.01 | 14-MAR-02:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 | 29-APR-16:00 | 3151.51 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.16 | 14-MAY-16:52 | 1926.05 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.75 | 18-JUN-16:00 | 1495.12 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.26 | 04-JUL-14:51 | 666.51 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.93 | 05-AUG-17:01 | 709.08 | 28-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.59 | 03-SEP-14:50 | 1071.71 | 18-SEP-00:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.09 | 01-OCT-16:00 | 1759.98 | 11-OCT-22:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3399.54 | 26-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4763.12 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.26 | 4763.12 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 7423.39 | 16-JAN-17:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5877.27 | 05-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4966.23 | 14-MAR-02:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | 29-APR-16:00 | 5493.63 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.75 | 14-MAY-16:52 | 3376.47 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1545.82 | 18-JUN-16:00 | 2587.53 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1989.97 | 04-JUL-14:51 | 1214.02 | 15-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.54 | 05-AUG-17:01 | 1245.41 | 10-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.76 | 03-SEP-14:50 | 1814.71 | 07-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.52 | 01-OCT-16:10 | 3070.96 | 11-OCT-22:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5779.07 | 26-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 8145.52 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.02 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1989.97 | 8145.52 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6969.78 | 16-JAN-17:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5541.86 | 05-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4987.82 | 14-MAR-02:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 29-APR-15:50 | 5818.05 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.22 | 14-MAY-17:00 | 3512.38 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.08 | 18-JUN-16:10 | 2779.46 | 04-JUN-16:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.57 | 04-JUL-16:51 | 1659.17 | 15-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.51 | 20-AUG-17:00 | 1386.22 | 08-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.31 | 03-SEP-15:00 | 1952.42 | 17-SEP-20:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.09 | 01-OCT-15:52 | 3308.34 | 11-OCT-22:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6032.49 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7892.10 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1386.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.57 | 7892.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 127185.00 | 16-JAN-23:10 | 0.00 | 4038.86 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 127745.83 | 20-FEB-17:00 | 3590.45 | 4978.03 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 124828.89 | 19-MAR-21:38 | 0.00 | 12116.59 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 126158.71 | 02-APR-22:42 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 118051.64 | 01-MAY-03:11 | 0.00 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 117669.67 | 19-JUN-03:01 | 0.00 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 110020.26 | 30-JUL-23:00 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111868.06 | 27-AUG-20:32 | 0.00 | 8077.72 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119559.40 | 17-SEP-20:32 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 125900.16 | 09-OCT-05:27 | 8078.51 | 11200.57 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 126551.19 | 11-NOV-16:50 | 2692.84 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 126192.14 | 17-DEC-16:50 | 2692.84 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 110020.26 | 0.00 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127745.83 | 8078.51 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 73173.14 | 02-JAN-04:02 | 0.00 | 10881.55 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72244.62 | 21-FEB-04:02 | 0.00 | 6045.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75172.40 | 20-MAR-03:02 | 0.00 | 6045.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77013.48 | 04-APR-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88043.67 | 30-MAY-03:03 | 0.00 | 8463.43 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92134.74 | 08-JUN-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88974.84 | 10-JUL-05:02 | 16122.38 | 22353.12 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85136.84 | 04-AUG-05:02 | 16122.38 | 22353.12 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96466.99 | 05-SEP-03:03 | 0.00 | 9672.49 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91889.51 | 11-OCT-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77007.44 | 08-NOV-04:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75240.48 | 26-DEC-04:01 | 0.00 | 8463.43 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 72244.62 | 0.00 | 6045.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96466.99 | 16122.38 | 22353.12 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 61782.73 | 06-JAN-06:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62243.89 | 14-FEB-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63553.29 | 21-MAR-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68874.07 | 13-APR-04:02 | 0.00 | 14508.73 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78134.57 | 22-MAY-03:01 | 0.00 | 8463.43 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83236.23 | 07-JUN-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85046.55 | 26-JUL-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84759.75 | 15-AUG-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82826.86 | 01-SEP-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78000.55 | 07-OCT-04:02 | 0.00 | 7254.36 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64454.05 | 09-NOV-06:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 62933.35 | 01-DEC-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 61782.73 | 0.00 | 7254.36 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85046.55 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32356.97 | 05-JAN-16:40 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41196.19 | 15-FEB-16:20 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42418.63 | 08-MAR-16:20 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65450.35 | 28-APR-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79682.56 | 19-MAY-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87195.59 | 24-JUN-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89274.93 | 25-JUL-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87583.72 | 15-AUG-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82464.04 | 05-SEP-03:01 | 0.00 | 9672.49 | 64456.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79622.73 | 07-OCT-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55547.07 | 01-NOV-05:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31635.52 | 29-DEC-16:30 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 31635.52 | 0.00 | 9672.49 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89274.93 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4128.77 | 24-JAN-14:40 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.16 |
February | 5514.98 | 14-FEB-16:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
March | 7238.15 | 27-MAR-14:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.30 |
April | 8792.33 | 14-APR-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
May | 10349.67 | 19-MAY-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11887.17 | 29-JUN-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 11905.72 | 10-JUL-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 |
August | 15638.37 | 20-AUG-15:51 | 1012.16 | 1403.33 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 152.09 | 0.00 |
September | 12275.36 | 05-SEP-03:01 | 0.00 | 1214.48 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.51 |
October | 10091.03 | 11-OCT-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 |
November | 5875.47 | 08-NOV-13:50 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.81 |
December | 4896.58 | 01-DEC-14:10 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.22 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4128.77 | 0.00 | 1214.48 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15638.37 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 152.09 | 162.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10541.53 | 01-JAN-09:38 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.15 |
February | 9306.47 | 14-FEB-09:05 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 |
March | 12397.90 | 26-MAR-08:32 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.81 |
April | 17165.65 | 30-APR-08:12 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.15 |
May | 19261.83 | 14-MAY-08:51 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.39 |
June | 20963.48 | 25-JUN-07:41 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.39 |
July | 20974.45 | 30-JUL-07:51 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.54 |
August | 20266.90 | 20-AUG-08:31 | 587.05 | 813.92 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 |
September | 21134.21 | 03-SEP-08:21 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 |
October | 18564.99 | 01-OCT-09:32 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.55 |
November | 9738.75 | 12-NOV-08:06 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.20 |
December | 6462.34 | 29-DEC-09:05 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6462.34 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | |
Maximum of Months | 21134.21 | 2478.65 | 3255.69 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16994.79 | 01-JAN-14:11 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.43 |
February | 16772.01 | 12-FEB-14:32 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.85 |
March | 15892.42 | 12-MAR-13:42 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.74 |
April | 11436.45 | 27-APR-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 |
May | 10952.26 | 19-MAY-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12604.25 | 29-JUN-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 |
July | 12663.15 | 10-JUL-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
August | 17600.32 | 20-AUG-15:51 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 143.37 | 0.00 |
September | 18664.08 | 03-SEP-13:42 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 100.82 | 0.00 |
October | 19982.72 | 01-OCT-11:31 | 708.53 | 982.35 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
November | 16229.82 | 05-NOV-12:32 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.89 |
December | 16590.82 | 24-DEC-14:22 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10952.26 | 506.09 | 701.68 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19982.72 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 143.37 | 760.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9885.86 | 26-JAN-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.60 |
February | 13422.87 | 15-FEB-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.16 |
March | 23313.90 | 12-MAR-16:22 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.96 |
April | 25494.57 | 16-APR-17:01 | 0.00 | 782.66 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 |
May | 23953.42 | 29-MAY-16:32 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 |
June | 28691.83 | 25-JUN-16:31 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 99.94 | 0.00 |
July | 28023.51 | 02-JUL-17:31 | 0.00 | 880.49 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 50.68 | 0.00 |
August | 29466.69 | 20-AUG-15:51 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 | 0.00 |
September | 24290.49 | 04-SEP-17:21 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 |
October | 24017.38 | 01-OCT-15:31 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 | 0.00 |
November | 17258.82 | 12-NOV-14:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.61 |
December | 19600.54 | 31-DEC-15:32 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9885.86 | 0.00 | 542.61 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29466.69 | 1239.33 | 1627.84 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 99.94 | 132.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2997.20 | 05-JAN-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.40 |
February | 3965.45 | 15-FEB-15:50 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.35 |
March | 4972.80 | 27-MAR-14:50 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.18 |
April | 7594.85 | 14-APR-14:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
May | 9604.31 | 19-MAY-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12056.69 | 27-JUN-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.65 |
July | 12411.53 | 25-JUL-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 |
August | 11823.30 | 07-AUG-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 |
September | 9814.11 | 12-SEP-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 |
October | 7415.15 | 02-OCT-13:50 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 0.00 |
November | 4074.26 | 03-NOV-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.88 |
December | 2846.00 | 01-DEC-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2846.00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12411.53 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 175.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4820.99 | 27-JAN-09:30 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7877.59 | 14-FEB-09:20 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 |
March | 15633.74 | 26-MAR-09:02 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.79 |
April | 17797.64 | 30-APR-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.12 |
May | 21164.25 | 29-MAY-08:51 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.37 |
June | 22609.04 | 18-JUN-08:31 | 521.82 | 723.49 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.17 |
July | 22642.99 | 30-JUL-08:41 | 521.82 | 723.49 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 |
August | 22069.39 | 13-AUG-09:01 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.12 |
September | 22006.09 | 03-SEP-09:01 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 |
October | 12404.98 | 01-OCT-09:02 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.62 |
November | 8275.33 | 01-NOV-08:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 |
December | 4559.60 | 29-DEC-09:20 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4559.60 | 260.91 | 361.74 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22642.99 | 1239.33 | 1627.84 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16246.00 | 01-JAN-14:11 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.92 |
February | 16757.77 | 19-FEB-14:12 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.17 |
March | 15973.08 | 26-MAR-14:41 | 708.53 | 982.35 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.99 |
April | 10989.61 | 27-APR-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 |
May | 10469.27 | 19-MAY-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12919.63 | 28-JUN-05:02 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.14 |
July | 13332.92 | 12-JUL-05:02 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 |
August | 13465.49 | 31-AUG-13:00 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 34.91 | 0.00 |
September | 17772.11 | 03-SEP-13:42 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 205.64 | 0.00 |
October | 17712.32 | 01-OCT-13:42 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
November | 15343.21 | 23-NOV-12:32 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.92 |
December | 14848.48 | 31-DEC-14:23 | 303.66 | 421.01 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10469.27 | 303.66 | 421.01 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17772.11 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 205.64 | 1008.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8306.57 | 26-JAN-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.44 |
February | 11478.83 | 15-FEB-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
March | 11977.10 | 07-MAR-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 |
April | 21132.68 | 16-APR-17:12 | 0.00 | 586.99 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.48 |
May | 21442.81 | 29-MAY-16:51 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.03 |
June | 25365.94 | 25-JUN-17:11 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 195.59 | 0.00 |
July | 23496.64 | 04-JUL-17:01 | 0.00 | 782.66 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 524.68 | 0.00 |
August | 22830.67 | 20-AUG-17:21 | 0.00 | 782.66 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 240.38 | 0.00 |
September | 21235.82 | 04-SEP-17:21 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 |
October | 20418.50 | 15-OCT-16:21 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.26 |
November | 10093.85 | 02-NOV-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.47 |
December | 7096.51 | 29-DEC-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7096.51 | 0.00 | 586.99 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25365.94 | 1239.33 | 1627.84 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 524.68 | 115.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3273.18 | 05-JAN-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 |
February | 4019.58 | 14-FEB-16:50 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.22 |
March | 4688.47 | 08-MAR-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 |
April | 8259.95 | 28-APR-15:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 0.00 |
May | 9256.29 | 19-MAY-15:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 212.42 | 0.00 |
June | 13779.26 | 29-JUN-03:01 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.11 |
July | 17390.18 | 04-JUL-17:01 | 0.00 | 1214.48 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.03 | 0.00 |
August | 13802.35 | 22-AUG-03:01 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9251.43 | 01-SEP-15:10 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 64.63 | 0.00 |
October | 8057.66 | 02-OCT-13:50 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 0.00 |
November | 3776.80 | 09-NOV-14:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.64 |
December | 3015.03 | 01-DEC-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3015.03 | 0.00 | 1214.48 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17390.18 | 2010.79 | 2525.99 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.03 | 192.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3513.37 | 05-JAN-15:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.42 |
February | 5550.45 | 14-FEB-09:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.01 |
March | 7801.02 | 24-MAR-09:20 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.71 |
April | 19056.88 | 30-APR-09:22 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.72 |
May | 21107.21 | 29-MAY-08:51 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.57 |
June | 21699.84 | 18-JUN-07:21 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21527.51 | 04-JUL-09:01 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
August | 21428.78 | 20-AUG-08:41 | 456.59 | 633.05 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 |
September | 20418.54 | 03-SEP-09:12 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 |
October | 18801.37 | 01-OCT-08:42 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.01 |
November | 7042.99 | 01-NOV-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.58 |
December | 3226.50 | 29-DEC-09:30 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3226.50 | 391.37 | 542.61 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21699.84 | 1295.83 | 1627.84 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17392.93 | 01-JAN-14:11 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785.42 |
February | 18214.72 | 19-FEB-14:12 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.31 |
March | 18374.56 | 26-MAR-14:32 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.54 |
April | 11871.13 | 27-APR-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
May | 10699.59 | 19-MAY-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14773.54 | 29-JUN-03:01 | 0.00 | 1518.13 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.11 |
July | 18542.40 | 04-JUL-17:01 | 0.00 | 1214.50 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.67 | 0.00 |
August | 18636.71 | 13-AUG-15:51 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 106.19 | 0.00 |
September | 20101.92 | 03-SEP-13:51 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 290.92 | 0.00 |
October | 21517.71 | 01-OCT-11:21 | 708.53 | 982.35 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.63 |
November | 17081.73 | 19-NOV-14:01 | 708.53 | 982.35 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.50 |
December | 17927.89 | 31-DEC-14:01 | 708.53 | 982.35 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10699.59 | 0.00 | 842.02 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21517.71 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.67 | 1167.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7667.27 | 26-JAN-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 |
February | 11386.25 | 15-FEB-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 |
March | 12086.84 | 07-MAR-16:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 |
April | 22601.17 | 16-APR-17:12 | 0.00 | 586.99 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.47 |
May | 23071.66 | 29-MAY-16:21 | 521.82 | 723.49 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 |
June | 27101.13 | 11-JUN-17:01 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.52 |
July | 25374.64 | 04-JUL-17:01 | 0.00 | 782.66 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 614.64 | 0.00 |
August | 26504.90 | 13-AUG-16:31 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | 0.00 |
September | 22889.35 | 04-SEP-17:21 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 |
October | 22421.20 | 01-OCT-15:21 | 456.59 | 633.05 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 47.29 | 0.00 |
November | 9819.75 | 02-NOV-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 |
December | 6463.86 | 29-DEC-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6463.86 | 0.00 | 586.99 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27101.13 | 1239.33 | 1627.84 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 614.64 | 142.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6089.58 | 03-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.08 |
February | 5866.09 | 21-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 |
March | 5732.71 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.50 |
April | 7463.11 | 18-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.36 |
May | 9897.28 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.77 |
June | 9529.55 | 05-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 |
July | 8385.73 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 |
August | 8401.15 | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 |
September | 11657.24 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 |
October | 10288.46 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.61 |
November | 6692.43 | 24-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.94 |
December | 6154.46 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5732.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | |
Maximum of Months | 11657.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6460.77 | 17-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.25 |
February | 6363.57 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4158.59 |
March | 4838.47 | 18-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6407.89 | 29-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.88 |
May | 6317.76 | 23-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.92 |
June | 8489.02 | 29-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.75 |
July | 9004.94 | 14-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 |
August | 9363.27 | 17-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.16 |
September | 7910.96 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 |
October | 6191.97 | 06-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.55 |
November | 4908.01 | 24-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.83 |
December | 5632.65 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4838.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9363.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4546.42 | 05-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.21 |
February | 8999.62 | 15-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.61 |
March | 11888.08 | 08-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 |
April | 17052.81 | 28-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.72 |
May | 19557.25 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 0.00 |
June | 23692.64 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.35 | 0.00 |
July | 23475.40 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 0.00 |
August | 22983.90 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18817.64 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.78 | 0.00 |
October | 15192.26 | 05-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
November | 8012.28 | 02-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.50 |
December | 3965.10 | 31-DEC-14:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3965.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23692.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 260.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2363.51 | 26-JAN-17:00 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4381.93 | 15-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6306.79 | 24-MAR-17:40 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8204.90 | 15-APR-17:55 | 0.00 | 32.42 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2422.61 | 20-MAY-18:16 | 0.00 | 122.75 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4639.13 | 11-JUN-18:45 | 0.00 | 35.07 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6581.36 | 04-JUL-18:51 | 0.00 | 140.29 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7519.33 | 10-AUG-19:00 | 0.00 | 194.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2419.53 | 02-SEP-17:50 | 0.00 | 81.05 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4458.68 | 15-OCT-16:52 | 0.00 | 81.05 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6244.46 | 06-NOV-16:40 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8046.34 | 31-DEC-16:33 | 0.00 | 48.63 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2363.51 | 0.00 | 32.42 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8204.90 | 0.00 | 291.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2203.86 | 26-JAN-17:00 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4122.60 | 15-FEB-17:10 | 0.00 | 324.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5977.76 | 24-MAR-17:40 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7654.22 | 07-APR-17:50 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2310.53 | 20-MAY-18:17 | 0.00 | 122.75 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4333.15 | 18-JUN-18:23 | 0.00 | 157.82 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6254.94 | 04-JUL-18:34 | 0.00 | 175.36 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7144.06 | 10-AUG-19:00 | 0.00 | 194.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2283.10 | 28-SEP-17:00 | 0.00 | 162.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4202.17 | 04-OCT-17:00 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5874.90 | 02-NOV-16:40 | 0.00 | 162.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7499.35 | 29-DEC-16:50 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2203.86 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7654.22 | 0.00 | 324.20 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2129.92 | 26-JAN-17:00 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4141.53 | 15-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6021.21 | 24-MAR-17:40 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7686.03 | 05-APR-18:00 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2478.31 | 20-MAY-18:10 | 0.00 | 17.54 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4627.64 | 18-JUN-18:23 | 0.00 | 157.82 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6510.21 | 04-JUL-19:11 | 0.00 | 175.36 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7226.68 | 28-AUG-18:50 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2392.95 | 02-SEP-17:48 | 0.00 | 81.05 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4281.78 | 04-OCT-17:00 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5870.06 | 02-NOV-16:40 | 0.00 | 162.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7418.42 | 29-DEC-16:50 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2129.92 | 0.00 | 17.54 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7686.03 | 0.00 | 291.78 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 308073.89 | 29-JAN-10:11 | 0.00 | 3508.98 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 351650.04 | 25-FEB-20:07 | 0.00 | 3795.95 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 398205.51 | 18-MAR-04:32 | 0.00 | 3795.95 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 370760.21 | 06-APR-03:02 | 0.00 | 3795.95 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 306492.70 | 12-MAY-05:02 | 0.00 | 7017.96 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 327158.84 | 09-JUN-03:03 | 0.00 | 3795.95 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 275464.79 | 05-JUL-16:00 | 0.00 | 6316.16 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367690.88 | 31-AUG-06:05 | 0.00 | 4210.78 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 152677.00 | 01-SEP-00:02 | 0.00 | 2277.57 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 352727.35 | 23-OCT-03:43 | 0.00 | 3795.95 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 376211.21 | 22-NOV-00:46 | 0.00 | 3795.95 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 384701.14 | 01-DEC-00:05 | 0.00 | 759.19 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 152677.00 | 0.00 | 759.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 398205.51 | 0.00 | 7017.96 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.187490E+13 | 1236495.96 | 05-JAN-16:10 | 0.376729E+12 | 923319.76 | 17-JAN-07:19 |
February | 0.210727E+13 | 1466633.92 | 13-FEB-16:19 | 0.258035E+12 | 1071895.15 | 06-FEB-07:10 |
March | 0.286497E+13 | 1625818.33 | 07-MAR-16:19 | 0.138828E+12 | 614657.87 | 04-MAR-07:10 |
April | 0.324155E+13 | 1925327.41 | 13-APR-15:00 | 0.657615E+11 | 975643.08 | 25-APR-00:30 |
May | 0.211134E+13 | 1466507.54 | 19-MAY-15:00 | 0.541681E+11 | 172281.00 | 06-MAY-06:00 |
June | 0.265804E+13 | 1749231.76 | 28-JUN-15:00 | 0.461402E+11 | 148746.64 | 04-JUN-22:30 |
July | 0.321223E+13 | 1903657.44 | 21-JUL-15:00 | 0.430355E+11 | 165465.74 | 09-JUL-18:00 |
August | 0.373020E+13 | 2058154.05 | 18-AUG-15:00 | 0.451587E+11 | 167489.98 | 27-AUG-20:30 |
September | 0.213001E+13 | 1495655.07 | 05-SEP-15:09 | 0.435348E+11 | 169877.59 | 10-SEP-19:30 |
October | 0.249734E+13 | 1629832.90 | 06-OCT-15:30 | 0.900621E+11 | 613683.22 | 26-OCT-06:00 |
November | 0.271941E+13 | 1611129.17 | 22-NOV-16:00 | 0.157047E+12 | 943682.64 | 27-NOV-07:10 |
December | 0.317450E+13 | 1718216.09 | 29-DEC-16:00 | 0.337659E+12 | 1234480.64 | 22-DEC-07:10 |
Annual Sum or Average | 0.323218E+14 | 0.165616E+13 | ||||
Minimum of Months | 0.187490E+13 | 1236495.96 | 0.430355E+11 | 148746.64 | ||
Maximum of Months | 0.373020E+13 | 2058154.05 | 0.376729E+12 | 1234480.64 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.358355E+12 | 0.881356E+11 | 0.811612E+12 | 0.173544E+12 | 0.221354E+12 | 0.173727E+11 | 0.00 | 0.124183E+12 | 0.174296E+11 | 0.629156E+11 | 0.00 | 0.00 | 0.00 |
February | 0.325045E+12 | 0.750672E+11 | 0.102011E+13 | 0.156760E+12 | 0.204440E+12 | 0.175478E+11 | 0.00 | 0.182738E+12 | 0.350487E+11 | 0.905186E+11 | 0.00 | 0.00 | 0.00 |
March | 0.386070E+12 | 0.765530E+11 | 0.146224E+13 | 0.173828E+12 | 0.233187E+12 | 0.262485E+11 | 0.00 | 0.292511E+12 | 0.832434E+11 | 0.131082E+12 | 0.00 | 0.00 | 0.00 |
April | 0.345016E+12 | 0.673680E+11 | 0.170426E+13 | 0.167919E+12 | 0.229384E+12 | 0.421984E+11 | 0.00 | 0.417537E+12 | 0.116658E+12 | 0.151208E+12 | 0.00 | 0.00 | 0.00 |
May | 0.372213E+12 | 0.638899E+11 | 0.820095E+12 | 0.173686E+12 | 0.236710E+12 | 0.547627E+11 | 0.00 | 0.232324E+12 | 0.104299E+12 | 0.533560E+11 | 0.00 | 0.00 | 0.00 |
June | 0.370347E+12 | 0.587908E+11 | 0.110647E+13 | 0.168186E+12 | 0.242592E+12 | 0.788688E+11 | 0.00 | 0.428106E+12 | 0.140602E+12 | 0.640743E+11 | 0.00 | 0.00 | 0.00 |
July | 0.346881E+12 | 0.623365E+11 | 0.143833E+13 | 0.173418E+12 | 0.249036E+12 | 0.942439E+11 | 0.00 | 0.609034E+12 | 0.168516E+12 | 0.704329E+11 | 0.00 | 0.00 | 0.00 |
August | 0.386070E+12 | 0.670303E+11 | 0.177907E+13 | 0.173828E+12 | 0.257096E+12 | 0.974481E+11 | 0.00 | 0.679335E+12 | 0.164170E+12 | 0.126149E+12 | 0.00 | 0.00 | 0.00 |
September | 0.345016E+12 | 0.712514E+11 | 0.784429E+12 | 0.167919E+12 | 0.233168E+12 | 0.690761E+11 | 0.00 | 0.281504E+12 | 0.131316E+12 | 0.463298E+11 | 0.00 | 0.00 | 0.00 |
October | 0.358355E+12 | 0.804364E+11 | 0.112844E+13 | 0.173544E+12 | 0.239798E+12 | 0.453097E+11 | 0.00 | 0.282311E+12 | 0.980857E+11 | 0.910518E+11 | 0.00 | 0.00 | 0.00 |
November | 0.354107E+12 | 0.837119E+11 | 0.140306E+13 | 0.168027E+12 | 0.230234E+12 | 0.171020E+11 | 0.00 | 0.261271E+12 | 0.703833E+11 | 0.131515E+12 | 0.00 | 0.00 | 0.00 |
December | 0.346881E+12 | 0.897565E+11 | 0.175516E+13 | 0.173418E+12 | 0.227784E+12 | 0.173626E+11 | 0.00 | 0.323018E+12 | 0.622155E+11 | 0.178901E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429436E+13 | 0.884327E+12 | 0.152133E+14 | 0.204408E+13 | 0.280478E+13 | 0.577541E+12 | 0.00 | 0.411387E+13 | 0.119197E+13 | 0.119753E+13 | |||
Minimum of Months | 0.325045E+12 | 0.587908E+11 | 0.784429E+12 | 0.156760E+12 | 0.204440E+12 | 0.171020E+11 | 0.00 | 0.124183E+12 | 0.174296E+11 | 0.463298E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386070E+12 | 0.897565E+11 | 0.177907E+13 | 0.173828E+12 | 0.257096E+12 | 0.974481E+11 | 0.00 | 0.679335E+12 | 0.168516E+12 | 0.178901E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.322578E+12 | 0.00 | 0.541511E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.208575E+12 | 0.00 | 0.494599E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.826318E+11 | 0.00 | 0.561964E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.166747E+11 | 0.00 | 0.490868E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.506842E+10 | 0.00 | 0.490997E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.822430E+09 | 0.00 | 0.453178E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.821671E+09 | 0.00 | 0.422138E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.532023E+09 | 0.00 | 0.446267E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.119823E+10 | 0.00 | 0.423366E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.437031E+11 | 0.00 | 0.463590E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.108552E+12 | 0.00 | 0.484951E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.286550E+12 | 0.00 | 0.511088E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.107771E+13 | 0.578452E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.532023E+09 | 0.00 | 0.422138E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.322578E+12 | 0.00 | 0.561964E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 373325.05 | 02-JAN-08:09 | 56280.71 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 129663.18 | 02-JAN-08:20 | 173429.10 | 26-JAN-16:40 | 31792.26 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 373325.05 | 01-FEB-08:09 | 56280.71 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 129663.18 | 01-FEB-08:20 | 173083.17 | 24-FEB-16:30 | 51740.27 | 13-FEB-16:19 | 0.00 | 01-FEB-00:10 |
March | 373325.05 | 01-MAR-08:09 | 56280.71 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 129663.18 | 01-MAR-08:20 | 161770.27 | 10-MAR-15:39 | 51744.33 | 07-MAR-15:50 | 0.00 | 01-MAR-00:10 |
April | 373325.05 | 03-APR-07:10 | 56280.71 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 129663.18 | 03-APR-07:19 | 170197.38 | 19-APR-15:00 | 54553.41 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 373325.05 | 01-MAY-07:10 | 56280.71 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 129663.18 | 01-MAY-07:19 | 172339.24 | 01-MAY-15:00 | 58613.42 | 23-MAY-10:39 | 0.00 | 01-MAY-00:10 |
June | 373325.05 | 01-JUN-07:10 | 56280.71 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 129663.18 | 01-JUN-07:19 | 191349.54 | 28-JUN-15:00 | 60000.40 | 29-JUN-14:20 | 0.00 | 01-JUN-00:10 |
July | 373325.05 | 03-JUL-07:10 | 56280.71 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 129663.18 | 03-JUL-07:19 | 187653.81 | 21-JUL-15:00 | 59483.33 | 21-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 373325.05 | 01-AUG-07:10 | 56280.71 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 129663.18 | 01-AUG-07:19 | 186178.72 | 18-AUG-15:00 | 59712.77 | 16-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 373325.05 | 01-SEP-07:10 | 56280.71 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 129663.18 | 01-SEP-07:19 | 170847.78 | 13-SEP-15:09 | 59084.45 | 13-SEP-10:20 | 0.00 | 01-SEP-00:10 |
October | 373325.05 | 02-OCT-07:10 | 56280.71 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 129663.18 | 02-OCT-07:19 | 177512.44 | 12-OCT-15:20 | 58735.60 | 04-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 373325.05 | 01-NOV-07:10 | 56280.71 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 129663.18 | 01-NOV-07:19 | 192745.45 | 01-NOV-15:39 | 34123.20 | 09-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 373325.05 | 01-DEC-08:09 | 56280.71 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 129663.18 | 01-DEC-08:20 | 168909.75 | 29-DEC-16:30 | 28251.26 | 22-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 373325.05 | 56280.71 | 439129.89 | 129663.18 | 161770.27 | 28251.26 | 0.00 | |||||||
Maximum of Months | 373325.05 | 56280.71 | 794004.08 | 129663.18 | 192745.45 | 60000.40 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 99850.98 | 31-JAN-22:19 | 49295.20 | 05-JAN-15:00 | 81089.76 | 21-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 178194.03 | 13-FEB-16:19 | 50831.91 | 14-FEB-15:00 | 81319.63 | 09-FEB-04:00 | 0.00 | 0.00 | 0.00 |
March | 214997.52 | 13-MAR-14:00 | 51618.95 | 16-MAR-12:00 | 71461.32 | 12-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 354969.43 | 17-APR-15:30 | 56754.19 | 14-APR-15:00 | 71053.18 | 08-APR-09:00 | 0.00 | 0.00 | 0.00 |
May | 265063.90 | 19-MAY-15:00 | 75760.48 | 22-MAY-12:30 | 56122.83 | 12-MAY-04:49 | 0.00 | 0.00 | 0.00 |
June | 388042.46 | 28-JUN-15:00 | 84388.24 | 06-JUN-12:50 | 79213.72 | 09-JUN-02:09 | 0.00 | 0.00 | 0.00 |
July | 429708.56 | 21-JUL-15:30 | 84388.24 | 01-JUL-10:39 | 44984.78 | 08-JUL-03:30 | 0.00 | 0.00 | 0.00 |
August | 441774.51 | 01-AUG-15:00 | 84388.24 | 01-AUG-12:20 | 66849.66 | 25-AUG-20:19 | 0.00 | 0.00 | 0.00 |
September | 316404.29 | 05-SEP-13:09 | 84388.24 | 01-SEP-11:20 | 23445.05 | 27-SEP-07:00 | 0.00 | 0.00 | 0.00 |
October | 300623.52 | 06-OCT-15:00 | 84388.24 | 11-OCT-10:00 | 80489.82 | 13-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 190221.22 | 09-NOV-13:00 | 51174.45 | 09-NOV-13:00 | 73254.72 | 20-NOV-23:19 | 0.00 | 0.00 | 0.00 |
December | 128884.36 | 24-DEC-15:30 | 49248.27 | 01-DEC-12:50 | 72967.84 | 23-DEC-10:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 99850.98 | 49248.27 | 23445.05 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 441774.51 | 84388.24 | 81319.63 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1236495.96 | 05-JAN-16:10 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 140620.86 | 30040.47 | 0.00 | 92889.87 | 43385.79 |
February | 1466633.92 | 13-FEB-16:19 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 132383.40 | 51740.27 | 0.00 | 178194.03 | 49318.08 |
March | 1625818.33 | 07-MAR-16:19 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 130785.37 | 51613.24 | 0.00 | 213897.00 | 49926.10 |
April | 1925327.41 | 13-APR-15:00 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 161363.03 | 53831.13 | 0.00 | 351300.55 | 55604.28 |
May | 1466507.54 | 19-MAY-15:00 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 167027.21 | 54632.14 | 0.00 | 265063.90 | 60898.20 |
June | 1749231.76 | 28-JUN-15:00 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 191349.54 | 56230.39 | 0.00 | 388042.46 | 84388.24 |
July | 1903657.44 | 21-JUL-15:00 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 187653.81 | 56049.83 | 0.00 | 429078.40 | 84388.24 |
August | 2058154.05 | 18-AUG-15:00 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 186178.72 | 57764.64 | 0.00 | 435306.07 | 84388.24 |
September | 1495655.07 | 05-SEP-15:09 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 151503.40 | 57442.20 | 0.00 | 285275.91 | 84388.24 |
October | 1629832.90 | 06-OCT-15:30 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 170780.12 | 54621.44 | 0.00 | 300396.73 | 60547.49 |
November | 1611129.17 | 22-NOV-16:00 | 373325.05 | 675712.68 | 56280.71 | 92996.58 | 144992.44 | 27845.78 | 0.00 | 139307.43 | 49254.65 |
December | 1718216.09 | 29-DEC-16:00 | 373325.05 | 794004.08 | 56280.71 | 92996.58 | 162464.06 | 3755.24 | 0.00 | 123131.42 | 44135.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1236495.96 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 130785.37 | 3755.24 | 0.00 | 92889.87 | 43385.79 | |
Maximum of Months | 2058154.05 | 373325.05 | 794004.08 | 56280.71 | 92996.58 | 191349.54 | 57764.64 | 0.00 | 435306.07 | 84388.24 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 915173.18 | 17-JAN-07:19 | 0.00 | 79190.88 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 1063748.57 | 06-FEB-07:10 | 0.00 | 79183.54 | 07-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 606511.29 | 04-MAR-07:10 | 0.00 | 78738.48 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 967496.50 | 25-APR-00:30 | 0.00 | 76596.49 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 164134.42 | 06-MAY-06:00 | 0.00 | 73197.60 | 04-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 140600.06 | 04-JUN-22:30 | 0.00 | 69388.57 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 157319.16 | 09-JUL-18:00 | 0.00 | 65390.88 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 159343.40 | 27-AUG-20:30 | 0.00 | 64255.05 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 161731.01 | 10-SEP-19:30 | 0.00 | 66946.52 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 605536.64 | 26-OCT-06:00 | 0.00 | 71629.71 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 935536.06 | 27-NOV-07:10 | 0.00 | 75107.46 | 28-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 1226334.06 | 22-DEC-07:10 | 0.00 | 77836.93 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 140600.06 | 0.00 | 64255.05 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1226334.06 | 0.00 | 79190.88 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.27 | 0.67 | 27.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.16 | 0.83 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.95 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.19 | 0.33 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.20 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.13 | 0.33 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.37 | 1.83 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 26.19 | 1.50 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 26.51 | 2.50 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 26.43 | 1.33 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 26.49 | 1.50 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.56 | 1.00 | 28.42 |
Annual Sum or Average | 0.00 | 0.00 | 157.50 | 26.31 | 11.83 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.95 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 26.56 | 2.50 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.65 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 25.61 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.65 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 18.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 18.79 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.84 | 1.17 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.77 | 2.83 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.13 | 4.33 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.43 | 2.83 | 28.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.31 | 6.00 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.19 | 3.33 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.02 | 2.00 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.87 | 1.67 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.17 | 28.13 | 24.17 | 28.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.43 | 6.00 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 | 25.63 | 73.83 | 25.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 60.83 | 25.32 | 60.83 | 25.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.25 | 8.33 | 25.25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.78 | 10.67 | 25.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 77.00 | 25.35 | 77.00 | 25.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 102.67 | 25.71 | 102.67 | 25.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 | 25.64 | 114.17 | 25.64 |
Annual Sum or Average | 0.00 | 0.00 | 447.50 | 25.56 | 447.50 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 | 25.78 | 114.17 | 25.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.08 | 2.83 | 28.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.94 | 3.67 | 28.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.29 | 2.17 | 28.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.20 | 3.50 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.18 | 4.17 | 28.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.23 | 4.17 | 28.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.94 | 2.33 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.23 | 2.17 | 28.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.50 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 62.50 | 27.84 | 27.67 | 28.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 28.29 | 4.17 | 28.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 19.02 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 19.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.33 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.30 | 1.00 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.09 | 4.17 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.56 | 3.00 | 28.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.43 | 7.50 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.34 | 4.50 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.33 | 1.33 | 28.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.04 | 0.50 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 19.03 | 0.00 | 22.33 | 28.33 | 22.33 | 28.33 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.39 | 0.00 | 0.00 | 7.50 | 28.56 | 7.50 | 28.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.83 | 0.00 | 0.00 | 95.00 | 26.06 | 95.00 | 26.06 |
February | 0.33 | 19.00 | 0.00 | 0.00 | 83.67 | 25.62 | 83.67 | 25.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 25.02 | 21.00 | 25.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 25.99 | 14.00 | 25.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 106.33 | 25.64 | 106.33 | 25.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 116.00 | 26.14 | 116.00 | 26.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 122.50 | 26.04 | 122.50 | 26.04 |
Annual Sum or Average | 0.67 | 18.91 | 0.00 | 558.50 | 25.89 | 558.50 | 25.89 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.00 | 0.00 | 0.00 | 122.50 | 26.14 | 122.50 | 26.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.33 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.08 | 1.67 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.25 | 1.83 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.79 | 1.83 | 28.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.76 | 2.33 | 28.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.59 | 1.50 | 28.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.88 | 1.50 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.58 | 1.50 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.88 | 0.00 | 21.00 | 28.40 | 12.50 | 28.33 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.93 | 0.00 | 0.00 | 4.83 | 28.79 | 2.33 | 28.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 17.65 | 1.33 | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.50 | 17.57 | 1.50 | 17.78 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.49 | 1.33 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 18.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.17 | 18.29 | 0.67 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.83 | 17.86 | 3.50 | 18.67 | 1.83 | 27.49 | 1.33 | 27.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.33 | 19.33 | 1.50 | 19.52 | 1.83 | 27.49 | 1.33 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 17.26 | 0.17 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.17 | 17.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.09 | 0.83 | 28.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.06 | 3.00 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.32 | 3.50 | 28.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.29 | 10.17 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.12 | 6.17 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.10 | 1.33 | 28.10 |
October | 0.17 | 19.25 | 0.00 | 0.00 | 0.33 | 27.68 | 0.33 | 27.68 |
November | 1.67 | 18.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 18.04 | 0.17 | 15.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.33 | 17.67 | 0.33 | 15.01 | 25.50 | 28.20 | 25.33 | 28.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 19.25 | 0.17 | 15.04 | 10.33 | 28.32 | 10.17 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 17.94 | 0.33 | 20.31 | 49.00 | 25.45 | 49.00 | 25.45 |
February | 3.67 | 17.96 | 0.17 | 20.17 | 34.33 | 25.37 | 34.33 | 25.37 |
March | 0.50 | 19.07 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 1.50 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.41 | 1.50 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.87 | 10.67 | 25.87 |
October | 0.17 | 19.38 | 0.00 | 0.00 | 60.17 | 25.38 | 60.17 | 25.38 |
November | 1.00 | 18.79 | 0.00 | 0.00 | 68.83 | 25.52 | 68.83 | 25.52 |
December | 5.17 | 18.67 | 0.17 | 20.44 | 61.00 | 25.38 | 61.00 | 25.38 |
Annual Sum or Average | 16.67 | 18.27 | 0.67 | 20.31 | 287.50 | 25.47 | 287.17 | 25.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.38 | 0.33 | 20.44 | 68.83 | 27.56 | 68.83 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 17.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.18 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.06 | 1.50 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.35 | 1.83 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.94 | 2.33 | 28.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.72 | 3.33 | 28.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.67 | 1.83 | 28.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.91 | 1.50 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.51 | 1.00 | 27.51 |
November | 1.17 | 18.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.83 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.00 | 18.34 | 0.00 | 22.00 | 28.51 | 13.50 | 28.43 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 19.18 | 0.00 | 0.00 | 5.50 | 28.94 | 3.33 | 28.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 | 28.05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 345.83 | 28.74 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 402.33 | 28.65 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 345.83 | 28.74 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 28.01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 299.33 | 28.62 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 345.83 | 28.54 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 299.33 | 28.62 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.60 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.96 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 253.83 | 28.74 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 285.33 | 28.65 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 253.83 | 28.74 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.39 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.21 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.36 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 215.50 | 28.18 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.43 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.18 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 29.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.30 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.23 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.84 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 981.83 | 29.18 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 29.50 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.83 | 24.02 | 88.67 | 26.48 | 0.00 | 0.00 |
February | 123.67 | 24.02 | 80.33 | 26.42 | 0.00 | 0.00 |
March | 118.67 | 24.02 | 74.67 | 26.36 | 0.00 | 0.00 |
April | 135.33 | 24.02 | 85.00 | 26.60 | 0.00 | 0.00 |
May | 82.50 | 24.03 | 156.33 | 25.51 | 0.67 | 24.00 |
June | 4.50 | 24.08 | 298.00 | 24.80 | 0.00 | 0.00 |
July | 134.83 | 24.43 | 474.83 | 24.66 | 134.83 | 24.43 |
August | 94.50 | 24.20 | 497.00 | 24.51 | 94.50 | 24.20 |
September | 18.67 | 24.56 | 383.50 | 24.72 | 18.67 | 24.56 |
October | 40.67 | 24.03 | 200.33 | 25.49 | 0.00 | 0.00 |
November | 46.00 | 24.04 | 107.17 | 26.62 | 0.00 | 0.00 |
December | 147.67 | 24.03 | 98.67 | 26.67 | 0.67 | 26.83 |
Annual Sum or Average | 1106.83 | 24.10 | 2544.50 | 25.17 | 249.33 | 24.35 |
Minimum of Months | 4.50 | 24.02 | 74.67 | 24.51 | 0.00 | 0.00 |
Maximum of Months | 159.83 | 24.56 | 497.00 | 26.67 | 134.83 | 26.83 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 209.00 | 23.99 | 19.17 | 25.94 | 0.00 | 0.00 |
February | 144.50 | 24.01 | 35.50 | 25.92 | 0.00 | 0.00 |
March | 123.00 | 24.02 | 46.33 | 26.06 | 0.00 | 0.00 |
April | 91.50 | 24.01 | 43.83 | 25.93 | 0.00 | 0.00 |
May | 87.67 | 23.96 | 131.50 | 24.77 | 0.33 | 24.00 |
June | 8.50 | 23.84 | 278.00 | 24.30 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 470.67 | 24.20 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 497.67 | 24.15 | 0.00 | 0.00 |
September | 1.50 | 23.91 | 370.00 | 24.39 | 0.83 | 24.00 |
October | 54.17 | 23.98 | 175.50 | 24.79 | 0.00 | 0.00 |
November | 74.83 | 24.03 | 70.33 | 25.78 | 0.00 | 0.00 |
December | 147.67 | 24.02 | 64.33 | 26.27 | 0.00 | 0.00 |
Annual Sum or Average | 942.33 | 24.00 | 2202.83 | 24.54 | 1.17 | 24.00 |
Minimum of Months | 0.00 | 0.00 | 19.17 | 24.15 | 0.00 | 0.00 |
Maximum of Months | 209.00 | 24.03 | 497.67 | 26.27 | 0.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.17 | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 325.17 | 23.83 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 276.83 | 23.86 | 2.00 | 25.03 | 0.00 | 0.00 |
April | 250.33 | 23.89 | 4.17 | 25.52 | 0.00 | 0.00 |
May | 160.83 | 23.85 | 80.83 | 24.43 | 0.50 | 24.00 |
June | 58.33 | 23.65 | 217.33 | 24.30 | 0.00 | 0.00 |
July | 3.83 | 23.58 | 426.33 | 24.16 | 0.00 | 0.00 |
August | 3.50 | 23.65 | 441.00 | 24.18 | 1.00 | 24.00 |
September | 26.17 | 23.58 | 302.17 | 24.29 | 3.33 | 24.00 |
October | 173.33 | 23.84 | 96.50 | 24.46 | 0.00 | 0.00 |
November | 297.00 | 23.90 | 3.50 | 25.30 | 0.00 | 0.00 |
December | 443.83 | 23.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2458.33 | 23.83 | 1573.83 | 24.25 | 4.83 | 24.00 |
Minimum of Months | 3.50 | 23.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.83 | 23.90 | 441.00 | 25.52 | 3.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 22.20 | 112.00 | 20.30 | 112.00 | 20.30 |
February | 442.00 | 22.66 | 42.67 | 20.52 | 42.67 | 20.52 |
March | 436.00 | 23.24 | 8.00 | 20.91 | 8.00 | 20.91 |
April | 326.17 | 23.64 | 0.83 | 25.41 | 0.00 | 0.00 |
May | 185.83 | 23.67 | 79.17 | 24.27 | 1.00 | 24.00 |
June | 57.67 | 23.62 | 243.33 | 24.26 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 461.33 | 24.21 | 0.00 | 0.00 |
August | 3.00 | 23.92 | 467.17 | 24.19 | 2.50 | 24.00 |
September | 61.00 | 23.55 | 269.83 | 24.20 | 5.00 | 23.92 |
October | 303.00 | 23.34 | 72.50 | 24.15 | 0.83 | 24.00 |
November | 452.33 | 22.95 | 27.50 | 20.90 | 27.50 | 20.90 |
December | 497.00 | 22.27 | 125.00 | 20.58 | 125.00 | 20.58 |
Annual Sum or Average | 3263.67 | 22.90 | 1909.33 | 23.60 | 324.50 | 20.61 |
Minimum of Months | 0.00 | 0.00 | 0.83 | 20.30 | 0.00 | 0.00 |
Maximum of Months | 499.67 | 23.92 | 467.17 | 25.41 | 125.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.76 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 430.83 | 23.07 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 392.00 | 23.42 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 254.83 | 23.78 | 2.17 | 24.87 | 0.00 | 0.00 |
May | 154.50 | 23.67 | 109.00 | 24.42 | 0.00 | 0.00 |
June | 16.83 | 23.74 | 299.67 | 24.29 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 477.33 | 24.28 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 489.67 | 24.17 | 0.00 | 0.00 |
September | 43.00 | 23.52 | 314.67 | 24.30 | 0.00 | 0.00 |
October | 263.33 | 23.49 | 96.33 | 24.27 | 0.00 | 0.00 |
November | 446.00 | 23.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 495.67 | 23.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2999.00 | 23.26 | 1788.83 | 24.26 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.78 | 489.67 | 24.87 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.67 | 22.34 | 9.50 | 25.09 | 1.83 | 21.00 |
February | 398.50 | 22.58 | 14.67 | 24.31 | 3.67 | 21.03 |
March | 332.83 | 22.79 | 40.17 | 24.74 | 1.17 | 26.40 |
April | 221.67 | 23.14 | 86.83 | 24.69 | 4.33 | 26.78 |
May | 175.83 | 23.33 | 183.17 | 24.61 | 14.00 | 26.77 |
June | 83.50 | 23.59 | 314.67 | 24.29 | 11.17 | 26.91 |
July | 63.33 | 24.52 | 397.00 | 24.29 | 27.83 | 26.69 |
August | 85.67 | 23.44 | 380.67 | 24.11 | 14.17 | 26.73 |
September | 120.17 | 23.03 | 308.17 | 24.29 | 9.50 | 26.63 |
October | 266.50 | 22.89 | 132.50 | 24.48 | 3.83 | 26.55 |
November | 404.00 | 22.83 | 16.33 | 25.38 | 0.00 | 0.00 |
December | 470.33 | 22.43 | 10.17 | 22.83 | 6.50 | 21.01 |
Annual Sum or Average | 3090.00 | 22.79 | 1893.83 | 24.33 | 98.00 | 26.03 |
Minimum of Months | 63.33 | 22.34 | 9.50 | 22.83 | 0.00 | 0.00 |
Maximum of Months | 470.33 | 24.52 | 397.00 | 25.38 | 27.83 | 26.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 307.33 | 22.87 | 132.67 | 25.46 | 15.50 | 24.49 |
February | 248.67 | 23.06 | 120.33 | 25.13 | 9.00 | 23.75 |
March | 275.17 | 23.32 | 57.83 | 24.87 | 1.00 | 26.47 |
April | 214.83 | 23.63 | 13.33 | 25.44 | 0.00 | 0.00 |
May | 170.00 | 23.51 | 107.50 | 24.40 | 0.00 | 0.00 |
June | 46.67 | 23.52 | 279.00 | 24.25 | 0.00 | 0.00 |
July | 1.83 | 25.86 | 472.00 | 24.26 | 1.83 | 25.86 |
August | 3.17 | 25.94 | 492.67 | 24.19 | 3.17 | 25.94 |
September | 45.67 | 24.45 | 372.33 | 24.47 | 16.33 | 26.28 |
October | 156.00 | 23.91 | 236.17 | 25.01 | 26.00 | 26.62 |
November | 233.50 | 23.72 | 158.00 | 25.75 | 25.67 | 26.61 |
December | 289.83 | 23.36 | 154.33 | 25.70 | 23.17 | 26.69 |
Annual Sum or Average | 1992.67 | 23.40 | 2596.17 | 24.65 | 121.67 | 26.07 |
Minimum of Months | 1.83 | 22.87 | 13.33 | 24.19 | 0.00 | 0.00 |
Maximum of Months | 307.33 | 25.94 | 492.67 | 25.75 | 26.00 | 26.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 431.17 | 22.45 | 13.17 | 24.97 | 0.00 | 0.00 |
February | 306.00 | 22.99 | 54.67 | 24.59 | 0.00 | 0.00 |
March | 171.17 | 23.30 | 106.33 | 24.97 | 4.17 | 26.93 |
April | 40.83 | 24.85 | 205.33 | 25.01 | 15.00 | 27.02 |
May | 135.00 | 23.30 | 217.33 | 24.59 | 6.83 | 26.83 |
June | 23.17 | 25.36 | 389.00 | 24.37 | 14.17 | 26.70 |
July | 27.83 | 26.46 | 495.50 | 24.31 | 27.83 | 26.46 |
August | 33.00 | 25.91 | 514.00 | 24.33 | 33.00 | 25.91 |
September | 64.50 | 23.62 | 343.00 | 24.39 | 12.00 | 26.39 |
October | 148.67 | 23.37 | 211.00 | 24.60 | 8.00 | 26.72 |
November | 202.50 | 23.28 | 96.83 | 24.76 | 1.83 | 26.10 |
December | 235.83 | 23.32 | 71.17 | 25.19 | 1.00 | 26.21 |
Annual Sum or Average | 1819.67 | 23.22 | 2717.33 | 24.50 | 123.83 | 26.45 |
Minimum of Months | 23.17 | 22.45 | 13.17 | 24.31 | 0.00 | 0.00 |
Maximum of Months | 431.17 | 26.46 | 514.00 | 25.19 | 33.00 | 27.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.38 | 189.67 | 20.43 | 189.67 | 20.43 |
February | 454.00 | 21.80 | 87.33 | 20.51 | 87.33 | 20.51 |
March | 505.50 | 22.60 | 20.83 | 20.77 | 20.83 | 20.77 |
April | 401.83 | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 250.83 | 23.44 | 51.17 | 24.24 | 0.00 | 0.00 |
June | 70.00 | 23.42 | 241.50 | 24.30 | 0.00 | 0.00 |
July | 7.50 | 24.68 | 466.33 | 24.27 | 7.50 | 24.68 |
August | 8.50 | 23.72 | 444.67 | 24.19 | 3.33 | 24.50 |
September | 111.67 | 23.31 | 227.17 | 24.15 | 2.33 | 24.00 |
October | 379.83 | 22.81 | 50.00 | 23.89 | 2.00 | 21.00 |
November | 473.00 | 22.17 | 52.17 | 20.53 | 52.17 | 20.53 |
December | 497.00 | 21.31 | 222.00 | 20.56 | 222.00 | 20.56 |
Annual Sum or Average | 3661.67 | 22.29 | 2052.83 | 23.19 | 587.17 | 20.61 |
Minimum of Months | 7.50 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 505.50 | 24.68 | 466.33 | 24.30 | 222.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.50 | 21.40 | 119.17 | 20.62 | 119.17 | 20.62 |
February | 368.33 | 21.67 | 53.83 | 20.77 | 51.50 | 20.52 |
March | 366.00 | 22.21 | 25.50 | 24.14 | 5.50 | 21.08 |
April | 226.83 | 22.78 | 74.00 | 25.17 | 2.67 | 27.05 |
May | 209.33 | 23.08 | 130.83 | 24.83 | 13.50 | 26.75 |
June | 98.67 | 23.34 | 245.17 | 24.49 | 12.33 | 26.88 |
July | 81.33 | 24.66 | 330.50 | 24.56 | 40.00 | 26.60 |
August | 85.50 | 23.68 | 320.00 | 24.38 | 22.17 | 26.61 |
September | 153.33 | 22.76 | 207.67 | 24.31 | 7.33 | 26.63 |
October | 288.00 | 22.37 | 85.33 | 24.50 | 4.00 | 24.49 |
November | 381.17 | 21.94 | 29.33 | 21.90 | 21.50 | 20.61 |
December | 419.33 | 21.34 | 150.17 | 20.62 | 150.17 | 20.62 |
Annual Sum or Average | 3102.33 | 22.17 | 1771.50 | 23.76 | 449.83 | 21.96 |
Minimum of Months | 81.33 | 21.34 | 25.50 | 20.62 | 2.67 | 20.52 |
Maximum of Months | 424.50 | 24.66 | 330.50 | 25.17 | 150.17 | 27.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 349.67 | 23.01 | 177.00 | 24.88 | 88.83 | 24.17 |
February | 274.33 | 22.92 | 141.67 | 25.06 | 40.67 | 24.34 |
March | 317.83 | 22.87 | 63.67 | 24.74 | 6.17 | 22.07 |
April | 293.67 | 23.28 | 13.83 | 26.06 | 0.00 | 0.00 |
May | 229.17 | 23.35 | 67.83 | 24.31 | 0.00 | 0.00 |
June | 89.17 | 23.30 | 233.33 | 24.30 | 0.00 | 0.00 |
July | 7.50 | 24.59 | 458.00 | 24.27 | 7.50 | 24.59 |
August | 6.83 | 24.05 | 452.00 | 24.26 | 3.50 | 24.87 |
September | 73.00 | 24.28 | 337.83 | 24.49 | 23.50 | 26.31 |
October | 195.33 | 23.88 | 236.50 | 25.25 | 46.83 | 26.40 |
November | 288.00 | 23.78 | 169.00 | 25.97 | 67.00 | 26.46 |
December | 328.50 | 23.18 | 189.83 | 25.14 | 85.83 | 24.56 |
Annual Sum or Average | 2453.00 | 23.29 | 2540.50 | 24.68 | 369.83 | 25.09 |
Minimum of Months | 6.83 | 22.87 | 13.83 | 24.26 | 0.00 | 0.00 |
Maximum of Months | 349.67 | 24.59 | 458.00 | 26.06 | 88.83 | 26.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.17 | 21.39 | 122.50 | 20.58 | 122.50 | 20.58 |
February | 399.83 | 21.70 | 51.67 | 21.31 | 41.17 | 20.63 |
March | 438.67 | 22.18 | 40.00 | 24.02 | 6.50 | 21.18 |
April | 332.33 | 22.80 | 72.17 | 24.76 | 2.67 | 26.58 |
May | 296.67 | 22.84 | 109.50 | 24.54 | 6.33 | 26.87 |
June | 140.00 | 22.93 | 265.83 | 24.41 | 9.17 | 27.04 |
July | 66.00 | 23.48 | 372.00 | 24.24 | 16.50 | 26.17 |
August | 63.67 | 23.17 | 386.33 | 24.19 | 9.00 | 26.47 |
September | 185.33 | 22.71 | 212.17 | 24.31 | 7.50 | 26.46 |
October | 355.00 | 22.41 | 89.67 | 24.25 | 3.50 | 23.12 |
November | 429.50 | 21.94 | 23.50 | 21.78 | 15.00 | 20.27 |
December | 464.83 | 21.43 | 128.17 | 20.73 | 128.17 | 20.73 |
Annual Sum or Average | 3643.00 | 22.13 | 1873.50 | 23.70 | 368.00 | 21.49 |
Minimum of Months | 63.67 | 21.39 | 23.50 | 20.58 | 2.67 | 20.27 |
Maximum of Months | 471.17 | 23.48 | 386.33 | 24.76 | 128.17 | 27.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.45 | 351.00 | 19.94 | 351.00 | 19.94 |
February | 454.00 | 20.90 | 236.00 | 20.14 | 236.00 | 20.14 |
March | 511.00 | 21.82 | 127.17 | 20.49 | 127.17 | 20.49 |
April | 403.33 | 22.62 | 38.00 | 20.71 | 38.00 | 20.71 |
May | 283.17 | 22.97 | 65.17 | 23.86 | 7.33 | 20.89 |
June | 99.83 | 23.04 | 244.00 | 24.28 | 0.17 | 26.07 |
July | 20.17 | 23.95 | 433.33 | 24.29 | 10.17 | 24.76 |
August | 44.33 | 23.11 | 411.50 | 24.20 | 4.50 | 24.30 |
September | 185.00 | 22.96 | 189.00 | 24.10 | 3.33 | 23.71 |
October | 417.67 | 22.11 | 102.00 | 22.06 | 58.83 | 20.64 |
November | 486.50 | 21.17 | 209.00 | 20.12 | 209.00 | 20.12 |
December | 497.00 | 20.37 | 374.67 | 20.01 | 374.67 | 20.01 |
Annual Sum or Average | 3904.00 | 21.58 | 2780.83 | 22.15 | 1420.17 | 20.18 |
Minimum of Months | 20.17 | 20.37 | 38.00 | 19.94 | 0.17 | 19.94 |
Maximum of Months | 511.00 | 23.95 | 433.33 | 24.29 | 374.67 | 26.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.73 | 279.83 | 20.10 | 279.83 | 20.10 |
February | 450.00 | 21.21 | 150.17 | 20.09 | 150.17 | 20.09 |
March | 435.00 | 21.93 | 70.33 | 21.22 | 61.50 | 20.62 |
April | 241.00 | 22.56 | 82.83 | 24.33 | 13.17 | 21.64 |
May | 209.83 | 22.91 | 169.50 | 24.57 | 14.67 | 25.83 |
June | 91.33 | 23.35 | 331.17 | 24.36 | 14.17 | 26.65 |
July | 87.67 | 24.84 | 419.67 | 24.47 | 49.50 | 26.52 |
August | 85.50 | 23.79 | 410.83 | 24.32 | 26.83 | 26.45 |
September | 163.83 | 22.66 | 271.50 | 24.19 | 7.83 | 26.14 |
October | 343.33 | 22.16 | 128.50 | 23.47 | 32.17 | 20.90 |
November | 479.00 | 21.48 | 128.67 | 20.38 | 126.67 | 20.32 |
December | 497.00 | 20.59 | 286.50 | 20.00 | 286.50 | 20.00 |
Annual Sum or Average | 3585.50 | 21.73 | 2729.50 | 22.93 | 1063.00 | 20.84 |
Minimum of Months | 85.50 | 20.59 | 70.33 | 20.00 | 7.83 | 20.00 |
Maximum of Months | 502.00 | 24.84 | 419.67 | 24.57 | 286.50 | 26.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 352.17 | 21.59 | 229.00 | 22.28 | 143.33 | 20.38 |
February | 295.17 | 21.74 | 169.83 | 22.43 | 97.17 | 20.36 |
March | 361.50 | 22.18 | 106.33 | 22.11 | 67.67 | 20.61 |
April | 320.00 | 22.69 | 38.00 | 21.86 | 29.50 | 20.80 |
May | 274.17 | 22.93 | 77.17 | 24.02 | 6.83 | 20.92 |
June | 121.33 | 22.93 | 234.33 | 24.27 | 0.00 | 0.00 |
July | 33.83 | 23.70 | 424.17 | 24.30 | 11.83 | 24.95 |
August | 45.50 | 23.42 | 424.17 | 24.26 | 8.83 | 25.47 |
September | 129.83 | 23.44 | 299.17 | 24.40 | 22.00 | 25.95 |
October | 240.67 | 22.93 | 218.17 | 24.50 | 52.17 | 23.82 |
November | 300.17 | 22.29 | 174.83 | 23.84 | 66.50 | 21.22 |
December | 334.17 | 21.62 | 223.33 | 22.30 | 133.33 | 20.24 |
Annual Sum or Average | 2808.50 | 22.33 | 2618.50 | 23.68 | 639.17 | 21.11 |
Minimum of Months | 33.83 | 21.59 | 38.00 | 21.86 | 0.00 | 0.00 |
Maximum of Months | 361.50 | 23.70 | 424.17 | 24.50 | 143.33 | 25.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.00 | 20.83 | 254.00 | 20.12 | 254.00 | 20.12 |
February | 411.17 | 21.16 | 155.00 | 20.47 | 147.00 | 20.28 |
March | 448.67 | 21.67 | 106.33 | 21.88 | 73.50 | 20.71 |
April | 345.33 | 22.35 | 86.50 | 24.15 | 14.17 | 21.95 |
May | 323.50 | 22.52 | 109.00 | 24.35 | 8.67 | 25.17 |
June | 164.67 | 22.69 | 256.83 | 24.39 | 11.00 | 26.98 |
July | 100.00 | 23.09 | 367.17 | 24.21 | 19.17 | 26.06 |
August | 101.50 | 22.79 | 365.50 | 24.17 | 9.83 | 26.34 |
September | 224.17 | 22.42 | 192.33 | 24.21 | 6.83 | 26.35 |
October | 375.00 | 21.94 | 107.83 | 23.32 | 32.50 | 21.07 |
November | 444.83 | 21.32 | 120.17 | 20.40 | 114.83 | 20.24 |
December | 480.50 | 20.87 | 265.33 | 20.23 | 265.33 | 20.23 |
Annual Sum or Average | 3904.33 | 21.68 | 2386.00 | 22.77 | 956.83 | 20.65 |
Minimum of Months | 100.00 | 20.83 | 86.50 | 20.12 | 6.83 | 20.12 |
Maximum of Months | 485.00 | 23.09 | 367.17 | 24.39 | 265.33 | 26.98 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54026 | 13.93243 | 0.31862 | 7.63142 |
February | 454.00000 | 24.51842 | 15.09626 | 0.32275 | 7.64566 |
March | 514.00000 | 24.43202 | 15.20201 | 0.31026 | 7.35331 |
April | 485.00000 | 24.54478 | 13.64221 | 0.32563 | 7.74815 |
May | 508.00000 | 24.51809 | 21.22981 | -0.4737 | 10.84104 |
June | 496.00000 | 24.48489 | 31.89824 | -0.3988 | 9.28891 |
July | 497.00000 | 24.63306 | 45.93867 | -0.2503 | 7.58953 |
August | 514.00000 | 24.48995 | 45.48034 | -0.2825 | 7.63628 |
September | 485.00000 | 24.57547 | 37.45754 | -0.3208 | 8.51285 |
October | 502.00000 | 24.62191 | 22.50173 | 0.41899 | 9.45013 |
November | 489.00000 | 24.61437 | 15.55446 | 0.36511 | 8.44161 |
December | 497.00000 | 24.60574 | 12.04579 | 0.33195 | 7.95835 |
Annual Sum or Average | 5943.00000 | 24.54784 | 24.25516 | 0.05286 | 8.34715 |
Minimum of Months | 454.00000 | 24.43202 | 12.04579 | -0.4737 | 7.35331 |
Maximum of Months | 514.00000 | 24.63306 | 45.93867 | 0.41899 | 10.84104 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.25412 | 15.27647 | 0.26069 | 6.59492 |
February | 454.00000 | 24.30702 | 16.25392 | 0.28944 | 6.95618 |
March | 514.00000 | 24.26467 | 16.16667 | 0.29755 | 7.04097 |
April | 485.00000 | 24.29576 | 14.35247 | 0.30510 | 7.14827 |
May | 508.00000 | 24.24339 | 22.58914 | -0.5227 | 11.23737 |
June | 496.00000 | 24.18810 | 32.48281 | -0.4516 | 9.58800 |
July | 497.00000 | 24.19309 | 44.49663 | -0.3579 | 7.89878 |
August | 514.00000 | 24.14945 | 44.17804 | -0.3567 | 7.79093 |
September | 485.00000 | 24.28481 | 38.20193 | -0.3911 | 8.76931 |
October | 502.00000 | 24.33210 | 23.38622 | 0.37001 | 8.23670 |
November | 489.00000 | 24.35529 | 16.42075 | 0.32105 | 7.40581 |
December | 497.00000 | 24.40786 | 13.03585 | 0.30171 | 7.23842 |
Annual Sum or Average | 5943.00000 | 24.27216 | 24.81981 | 0.00261 | 8.00203 |
Minimum of Months | 454.00000 | 24.14945 | 13.03585 | -0.5227 | 6.59492 |
Maximum of Months | 514.00000 | 24.40786 | 44.49663 | 0.37001 | 11.23737 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.80642 | 16.13067 | 0.12786 | 5.63997 |
February | 454.00000 | 23.94634 | 17.14881 | 0.17447 | 5.85550 |
March | 514.00000 | 24.04515 | 16.95454 | 0.21202 | 6.11701 |
April | 485.00000 | 24.14336 | 15.03601 | 0.23183 | 6.29065 |
May | 508.00000 | 24.10146 | 23.00092 | -0.5983 | 12.93924 |
June | 496.00000 | 24.09497 | 32.66976 | -0.5178 | 11.01703 |
July | 497.00000 | 24.11373 | 44.52215 | -0.4245 | 9.08395 |
August | 514.00000 | 24.12625 | 44.48778 | -0.4181 | 8.94474 |
September | 485.00000 | 24.14257 | 38.66938 | -0.4682 | 10.01555 |
October | 502.00000 | 24.12518 | 24.02888 | 0.29282 | 7.09794 |
November | 489.00000 | 24.08088 | 17.39559 | 0.22000 | 6.19889 |
December | 497.00000 | 23.88234 | 14.30878 | 0.13593 | 5.62412 |
Annual Sum or Average | 5943.00000 | 24.05121 | 25.44308 | -0.0886 | 7.92223 |
Minimum of Months | 454.00000 | 23.80642 | 14.30878 | -0.5983 | 5.62412 |
Maximum of Months | 514.00000 | 24.14336 | 44.52215 | 0.29282 | 12.93924 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.18821 | 18.25324 | -0.2851 | 9.14651 |
February | 454.00000 | 22.67521 | 19.00225 | -0.1511 | 7.41710 |
March | 514.00000 | 23.34044 | 18.10504 | 0.02689 | 6.07222 |
April | 485.00000 | 23.80888 | 15.35356 | 0.14780 | 5.93660 |
May | 508.00000 | 23.98363 | 22.83187 | -0.6339 | 14.14374 |
June | 496.00000 | 24.08681 | 32.58806 | -0.4981 | 10.63469 |
July | 497.00000 | 24.18854 | 44.30212 | -0.3702 | 8.15830 |
August | 514.00000 | 24.16098 | 44.29671 | -0.3834 | 8.35734 |
September | 485.00000 | 24.03332 | 38.57613 | -0.4991 | 10.68443 |
October | 502.00000 | 23.63393 | 24.86531 | 0.16251 | 6.47066 |
November | 489.00000 | 23.01130 | 19.32341 | -0.0595 | 6.60787 |
December | 497.00000 | 22.24939 | 16.31884 | -0.2832 | 8.82931 |
Annual Sum or Average | 5943.00000 | 23.45270 | 26.22294 | -0.2367 | 8.55108 |
Minimum of Months | 454.00000 | 22.18821 | 15.35356 | -0.6339 | 5.93660 |
Maximum of Months | 514.00000 | 24.18854 | 44.30212 | 0.16251 | 14.14374 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.75120 | 16.10517 | -0.1246 | 6.13757 |
February | 454.00000 | 23.10447 | 16.97724 | -0.0269 | 5.82355 |
March | 514.00000 | 23.56350 | 16.36018 | 0.10064 | 5.70678 |
April | 485.00000 | 23.95123 | 14.04609 | 0.20556 | 6.13314 |
May | 508.00000 | 24.04205 | 22.16229 | -0.5942 | 13.17860 |
June | 496.00000 | 24.18249 | 31.57049 | -0.4308 | 9.30460 |
July | 497.00000 | 24.26027 | 43.50274 | -0.3019 | 7.32837 |
August | 514.00000 | 24.15580 | 43.33749 | -0.3344 | 7.62808 |
September | 485.00000 | 24.13148 | 37.66219 | -0.4456 | 9.79547 |
October | 502.00000 | 23.79106 | 23.41260 | 0.21550 | 6.66374 |
November | 489.00000 | 23.45013 | 16.89561 | 0.06505 | 5.57089 |
December | 497.00000 | 23.09449 | 13.74312 | -0.0559 | 5.70657 |
Annual Sum or Average | 5943.00000 | 23.71055 | 24.72476 | -0.1455 | 7.43092 |
Minimum of Months | 454.00000 | 22.75120 | 13.74312 | -0.5942 | 5.57089 |
Maximum of Months | 514.00000 | 24.26027 | 43.50274 | 0.21550 | 13.17860 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48380 | 15.63984 | -0.1445 | 6.73605 |
February | 454.00000 | 22.78218 | 16.71012 | -0.0535 | 6.41869 |
March | 514.00000 | 23.25916 | 16.26348 | 0.08920 | 6.47891 |
April | 485.00000 | 23.70749 | 13.87880 | 0.22853 | 7.34374 |
May | 508.00000 | 23.91127 | 21.88304 | -0.5244 | 13.64578 |
June | 496.00000 | 23.99250 | 31.74214 | -0.3776 | 9.83966 |
July | 497.00000 | 24.04681 | 43.87259 | -0.2708 | 8.90419 |
August | 514.00000 | 23.81137 | 44.05863 | -0.3535 | 9.62148 |
September | 485.00000 | 23.82337 | 38.02488 | -0.4406 | 11.26181 |
October | 502.00000 | 23.49673 | 23.44243 | 0.21239 | 7.65621 |
November | 489.00000 | 23.06284 | 16.82926 | 0.02369 | 6.18324 |
December | 497.00000 | 22.51803 | 13.55700 | -0.1490 | 6.63985 |
Annual Sum or Average | 5943.00000 | 23.41237 | 24.73788 | -0.1480 | 8.41323 |
Minimum of Months | 454.00000 | 22.48380 | 13.55700 | -0.5244 | 6.18324 |
Maximum of Months | 514.00000 | 24.04681 | 44.05863 | 0.22853 | 13.64578 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67308 | 14.66526 | 0.15801 | 9.24652 |
February | 454.00000 | 23.79186 | 15.69289 | 0.20371 | 8.54752 |
March | 514.00000 | 23.74158 | 15.85282 | 0.18502 | 6.87857 |
April | 485.00000 | 23.93659 | 13.91667 | 0.22093 | 6.49479 |
May | 508.00000 | 23.96162 | 22.23480 | -0.6150 | 13.95517 |
June | 496.00000 | 24.09737 | 31.72328 | -0.4577 | 9.97904 |
July | 497.00000 | 24.23706 | 43.54117 | -0.3016 | 7.43073 |
August | 514.00000 | 24.17087 | 43.22051 | -0.3054 | 7.43557 |
September | 485.00000 | 24.29681 | 37.02956 | -0.3275 | 8.69176 |
October | 502.00000 | 24.34525 | 22.28250 | 0.41839 | 10.70240 |
November | 489.00000 | 24.31404 | 15.59092 | 0.34606 | 10.11097 |
December | 497.00000 | 24.03051 | 12.40650 | 0.24777 | 9.83219 |
Annual Sum or Average | 5943.00000 | 24.05018 | 24.09641 | -0.0216 | 9.11672 |
Minimum of Months | 454.00000 | 23.67308 | 12.40650 | -0.6150 | 6.49479 |
Maximum of Months | 514.00000 | 24.34525 | 43.54117 | 0.41839 | 13.95517 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.69521 | 15.23148 | -0.0645 | 6.29172 |
February | 454.00000 | 23.41350 | 15.88743 | 0.13618 | 6.55121 |
March | 514.00000 | 23.98251 | 15.39561 | 0.30395 | 7.81323 |
April | 485.00000 | 24.41627 | 13.18921 | 0.45367 | 10.16582 |
May | 508.00000 | 23.96496 | 21.91799 | -0.4763 | 11.75564 |
June | 496.00000 | 24.18477 | 31.35668 | -0.2638 | 8.11030 |
July | 497.00000 | 24.29061 | 43.13903 | -0.1140 | 6.69394 |
August | 514.00000 | 24.32548 | 42.53417 | -0.0498 | 6.15939 |
September | 485.00000 | 24.01854 | 37.54445 | -0.3342 | 9.34266 |
October | 502.00000 | 23.99435 | 22.66235 | 0.37000 | 9.13690 |
November | 489.00000 | 23.90516 | 15.74726 | 0.26917 | 7.29404 |
December | 497.00000 | 23.93135 | 12.25657 | 0.23558 | 7.02179 |
Annual Sum or Average | 5943.00000 | 23.92981 | 23.98395 | 0.03753 | 8.03315 |
Minimum of Months | 454.00000 | 22.69521 | 12.25657 | -0.4763 | 6.15939 |
Maximum of Months | 514.00000 | 24.41627 | 43.13903 | 0.45367 | 11.75564 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37329 | 17.23046 | -0.4668 | 10.92171 |
February | 454.00000 | 21.78626 | 18.47481 | -0.3515 | 9.04185 |
March | 514.00000 | 22.61035 | 17.76895 | -0.1413 | 6.73989 |
April | 485.00000 | 23.36127 | 14.94380 | 0.04199 | 5.89221 |
May | 508.00000 | 23.75450 | 22.71452 | -0.7130 | 16.81558 |
June | 496.00000 | 24.07034 | 31.64372 | -0.4986 | 10.86384 |
July | 497.00000 | 24.24013 | 43.50513 | -0.3435 | 7.84463 |
August | 514.00000 | 24.11980 | 43.54511 | -0.3943 | 8.59409 |
September | 485.00000 | 23.88651 | 38.30636 | -0.5526 | 12.12681 |
October | 502.00000 | 23.08889 | 24.57710 | 0.03294 | 6.45580 |
November | 489.00000 | 22.22048 | 18.46143 | -0.2400 | 7.70331 |
December | 497.00000 | 21.30382 | 15.41125 | -0.4948 | 11.24946 |
Annual Sum or Average | 5943.00000 | 22.99390 | 25.62007 | -0.3439 | 9.53001 |
Minimum of Months | 454.00000 | 21.30382 | 14.94380 | -0.7130 | 5.89221 |
Maximum of Months | 514.00000 | 24.24013 | 43.54511 | 0.04199 | 16.81558 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.39452 | 15.92374 | -0.4290 | 10.06123 |
February | 385.00000 | 21.76208 | 17.18373 | -0.3136 | 8.76742 |
March | 433.00000 | 22.52133 | 16.63863 | -0.0998 | 7.03863 |
April | 410.00000 | 23.51463 | 13.83248 | 0.16126 | 7.50564 |
May | 430.00000 | 23.69277 | 22.04455 | -0.6112 | 16.92327 |
June | 418.00000 | 23.99319 | 31.06101 | -0.3994 | 11.04088 |
July | 422.00000 | 24.20999 | 42.78514 | -0.2404 | 9.42955 |
August | 433.00000 | 23.98265 | 43.06696 | -0.3270 | 9.90686 |
September | 410.00000 | 23.59106 | 38.03042 | -0.5416 | 14.09814 |
October | 427.00000 | 22.97470 | 23.56173 | 0.07130 | 7.49584 |
November | 417.00000 | 22.12456 | 17.39178 | -0.2116 | 7.50340 |
December | 422.00000 | 21.33384 | 14.15821 | -0.4552 | 10.47621 |
Annual Sum or Average | 5034.00000 | 22.93129 | 24.69954 | -0.2832 | 10.02950 |
Minimum of Months | 385.00000 | 21.33384 | 13.83248 | -0.6112 | 7.03863 |
Maximum of Months | 433.00000 | 24.20999 | 43.06696 | 0.16126 | 16.92327 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.58266 | 14.66623 | 0.13777 | 11.13113 |
February | 454.00000 | 23.64234 | 15.95494 | 0.16897 | 9.88652 |
March | 514.00000 | 23.41426 | 16.36935 | 0.10222 | 7.16794 |
April | 485.00000 | 23.63949 | 14.36869 | 0.13485 | 6.33289 |
May | 508.00000 | 23.76253 | 22.59938 | -0.6970 | 16.46860 |
June | 496.00000 | 24.00539 | 31.74518 | -0.5161 | 11.43729 |
July | 497.00000 | 24.22626 | 43.49699 | -0.3381 | 7.89806 |
August | 514.00000 | 24.18167 | 43.24716 | -0.3428 | 8.04667 |
September | 485.00000 | 24.25743 | 37.08119 | -0.3516 | 9.48230 |
October | 502.00000 | 24.33032 | 22.35936 | 0.41088 | 11.57497 |
November | 489.00000 | 24.22086 | 15.82335 | 0.32292 | 11.50584 |
December | 497.00000 | 23.79481 | 12.80291 | 0.18916 | 11.52901 |
Annual Sum or Average | 5943.00000 | 23.92205 | 24.29265 | -0.0678 | 10.21339 |
Minimum of Months | 454.00000 | 23.41426 | 12.80291 | -0.6970 | 6.33289 |
Maximum of Months | 514.00000 | 24.33032 | 43.49699 | 0.41088 | 16.46860 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.53290 | 16.20631 | -0.3795 | 9.67081 |
February | 454.00000 | 21.96589 | 17.43208 | -0.2466 | 8.27298 |
March | 514.00000 | 22.47021 | 17.09352 | -0.1001 | 6.97961 |
April | 485.00000 | 23.28906 | 14.37344 | 0.11395 | 7.07428 |
May | 508.00000 | 23.37667 | 22.82626 | -0.7126 | 18.62005 |
June | 496.00000 | 23.76315 | 32.13336 | -0.4746 | 12.53055 |
July | 497.00000 | 23.89408 | 44.21493 | -0.3372 | 9.44698 |
August | 514.00000 | 23.86070 | 43.96834 | -0.3495 | 9.44635 |
September | 485.00000 | 23.49399 | 38.75851 | -0.5552 | 14.08368 |
October | 502.00000 | 22.89140 | 24.20709 | 0.07129 | 7.23940 |
November | 489.00000 | 22.19526 | 17.59328 | -0.1800 | 7.35963 |
December | 497.00000 | 21.58486 | 14.30128 | -0.3776 | 9.58937 |
Annual Sum or Average | 5943.00000 | 22.86653 | 25.33670 | -0.2949 | 10.04265 |
Minimum of Months | 454.00000 | 21.53290 | 14.30128 | -0.7126 | 6.97961 |
Maximum of Months | 514.00000 | 23.89408 | 44.21493 | 0.11395 | 18.62005 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44676 | 17.90048 | -0.7317 | 18.98115 |
February | 454.00000 | 20.89810 | 19.17563 | -0.5931 | 14.69907 |
March | 514.00000 | 21.81950 | 18.36569 | -0.3393 | 9.52171 |
April | 485.00000 | 22.84315 | 15.20539 | -0.0760 | 6.90010 |
May | 508.00000 | 23.45186 | 22.82724 | -0.7997 | 20.62130 |
June | 496.00000 | 23.93391 | 31.97569 | -0.5188 | 11.95085 |
July | 497.00000 | 24.17653 | 43.82335 | -0.3342 | 8.10637 |
August | 514.00000 | 24.02517 | 43.84218 | -0.4006 | 9.12954 |
September | 485.00000 | 23.60730 | 38.61051 | -0.6307 | 14.85583 |
October | 502.00000 | 22.40633 | 25.19552 | -0.1316 | 7.88861 |
November | 489.00000 | 21.18237 | 19.33765 | -0.5061 | 12.92243 |
December | 497.00000 | 20.37392 | 15.99588 | -0.7644 | 19.70031 |
Annual Sum or Average | 5943.00000 | 22.44273 | 26.09085 | -0.4851 | 12.92993 |
Minimum of Months | 454.00000 | 20.37392 | 15.20539 | -0.7997 | 6.90010 |
Maximum of Months | 514.00000 | 24.17653 | 43.84218 | -0.0760 | 20.62130 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72679 | 17.03847 | -0.6289 | 15.34139 |
February | 454.00000 | 21.22227 | 18.26967 | -0.4711 | 12.12714 |
March | 514.00000 | 22.25735 | 17.36291 | -0.1784 | 8.05258 |
April | 485.00000 | 23.39853 | 14.09263 | 0.13885 | 7.54898 |
May | 508.00000 | 23.65728 | 21.95054 | -0.6071 | 16.74645 |
June | 496.00000 | 24.00507 | 31.57276 | -0.3590 | 10.19709 |
July | 497.00000 | 24.22330 | 43.37396 | -0.1907 | 8.69561 |
August | 514.00000 | 24.01570 | 43.50374 | -0.2761 | 9.11113 |
September | 485.00000 | 23.57454 | 38.21525 | -0.5245 | 13.79603 |
October | 502.00000 | 22.78755 | 24.20095 | 0.01961 | 7.90282 |
November | 489.00000 | 21.52437 | 18.41967 | -0.3801 | 10.03949 |
December | 497.00000 | 20.59069 | 15.24899 | -0.6723 | 16.60945 |
Annual Sum or Average | 5943.00000 | 22.67672 | 25.34161 | -0.3436 | 11.34102 |
Minimum of Months | 454.00000 | 20.59069 | 14.09263 | -0.6723 | 7.54898 |
Maximum of Months | 514.00000 | 24.22330 | 43.50374 | 0.13885 | 16.74645 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.54684 | 15.55228 | -0.1468 | 12.41995 |
February | 454.00000 | 22.71229 | 16.86783 | -0.0788 | 10.97101 |
March | 514.00000 | 22.76484 | 17.04818 | -0.0665 | 8.33585 |
April | 485.00000 | 23.16898 | 14.66060 | 0.02668 | 6.97235 |
May | 508.00000 | 23.46065 | 22.72759 | -0.7836 | 20.26482 |
June | 496.00000 | 23.85574 | 32.10886 | -0.5401 | 12.71448 |
July | 497.00000 | 24.15280 | 43.85203 | -0.3320 | 8.27566 |
August | 514.00000 | 24.08295 | 43.57817 | -0.3510 | 8.64942 |
September | 485.00000 | 23.99228 | 37.39853 | -0.4272 | 11.53743 |
October | 502.00000 | 23.71124 | 22.98887 | 0.25842 | 10.54005 |
November | 489.00000 | 23.26016 | 16.80651 | 0.07366 | 10.51671 |
December | 497.00000 | 22.64318 | 13.70712 | -0.1202 | 12.65390 |
Annual Sum or Average | 5943.00000 | 23.36668 | 24.85498 | -0.2092 | 11.16608 |
Minimum of Months | 454.00000 | 22.54684 | 13.70712 | -0.7836 | 6.97235 |
Maximum of Months | 514.00000 | 24.15280 | 43.85203 | 0.25842 | 20.26482 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.92761 | 16.76844 | -0.5674 | 14.77496 |
February | 454.00000 | 21.41251 | 17.99409 | -0.4103 | 11.68004 |
March | 514.00000 | 21.98141 | 17.57116 | -0.2317 | 8.62483 |
April | 485.00000 | 22.90246 | 14.58438 | 0.02476 | 7.59508 |
May | 508.00000 | 23.09564 | 22.94450 | -0.7925 | 22.19388 |
June | 496.00000 | 23.60664 | 32.52269 | -0.5017 | 14.03225 |
July | 497.00000 | 23.79292 | 44.67709 | -0.3413 | 10.20854 |
August | 514.00000 | 23.72594 | 44.39016 | -0.3698 | 10.46717 |
September | 485.00000 | 23.24541 | 39.03706 | -0.6240 | 16.70437 |
October | 502.00000 | 22.47068 | 24.63882 | -0.0369 | 7.98554 |
November | 489.00000 | 21.55184 | 18.30302 | -0.3582 | 10.31929 |
December | 497.00000 | 20.96360 | 14.80772 | -0.5711 | 14.64726 |
Annual Sum or Average | 5943.00000 | 22.48138 | 25.76333 | -0.3987 | 12.44506 |
Minimum of Months | 454.00000 | 20.92761 | 14.58438 | -0.7925 | 7.59508 |
Maximum of Months | 514.00000 | 23.79292 | 44.67709 | 0.02476 | 22.19388 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.307367E+10 | 48719.95 | 05-JAN-16:00 | 49.16 | 0.981881E+10 | 0.00 | 0.128925E+11 | 0.19 | 5.04 | 05-JAN-16:00 | 0.00 | 0.00 |
February | 0.658058E+10 | 89182.03 | 13-FEB-16:20 | 74.82 | 0.334422E+11 | 0.00 | 0.400228E+11 | 0.40 | 6.99 | 13-FEB-16:20 | 0.00 | 0.00 |
March | 0.257664E+11 | 89243.23 | 13-MAR-15:00 | 164.09 | 0.130860E+12 | 0.00 | 0.156626E+12 | 0.97 | 6.99 | 13-MAR-15:00 | 0.00 | 0.00 |
April | 0.576451E+11 | 90884.45 | 27-APR-16:00 | 304.15 | 0.340119E+12 | 0.00 | 0.397764E+12 | 2.14 | 7.00 | 27-APR-16:00 | 0.00 | 0.00 |
May | 0.874967E+11 | 102929.56 | 23-MAY-09:30 | 380.89 | 0.538230E+12 | 0.00 | 0.625727E+12 | 2.90 | 7.15 | 23-MAY-09:30 | 0.00 | 0.00 |
June | 0.130891E+12 | 124639.49 | 28-JUN-16:00 | 522.54 | 0.842626E+12 | 0.00 | 0.973518E+12 | 4.28 | 7.25 | 28-JUN-16:00 | 0.00 | 0.00 |
July | 0.156909E+12 | 126132.37 | 31-JUL-15:00 | 609.44 | 0.101654E+13 | 0.00 | 0.117345E+13 | 4.82 | 7.26 | 12-JUL-05:02 | 0.00 | 0.00 |
August | 0.155756E+12 | 137726.27 | 14-AUG-05:02 | 655.10 | 0.990199E+12 | 0.00 | 0.114595E+13 | 4.95 | 7.28 | 15-AUG-05:02 | 0.00 | 0.00 |
September | 0.111543E+12 | 129698.78 | 05-SEP-13:10 | 451.80 | 0.704488E+12 | 0.00 | 0.816031E+12 | 3.69 | 7.13 | 02-SEP-16:02 | 0.00 | 0.00 |
October | 0.616187E+11 | 99779.45 | 04-OCT-14:40 | 308.65 | 0.365085E+12 | 0.00 | 0.426703E+12 | 2.15 | 7.12 | 04-OCT-14:40 | 0.00 | 0.00 |
November | 0.754690E+10 | 72305.63 | 09-NOV-14:00 | 75.82 | 0.297003E+11 | 0.00 | 0.372472E+11 | 0.35 | 6.56 | 09-NOV-14:00 | 0.00 | 0.00 |
December | 0.615142E+09 | 13343.23 | 17-DEC-16:50 | 67.81 | 0.170820E+10 | 0.00 | 0.232334E+10 | 0.25 | 2.78 | 12-DEC-10:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.805442E+12 | 3664.26 | 0.500282E+13 | 0.580826E+13 | 2.27 | |||||||
Minimum of Months | 0.615142E+09 | 13343.23 | 49.16 | 0.170820E+10 | 0.00 | 0.232334E+10 | 0.19 | 2.78 | 0.00 | 0.00 | ||
Maximum of Months | 0.156909E+12 | 137726.27 | 655.10 | 0.101654E+13 | 0.00 | 0.117345E+13 | 4.95 | 7.28 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.648601E+10 | 90884.45 | 27-APR-16:00 | 20.83 | 0.448921E+11 | 0.00 | 0.513781E+11 | 0.20 | 7.00 | 27-APR-16:00 | 0.00 | 0.00 |
May | 0.140484E+11 | 98822.38 | 19-MAY-16:00 | 44.56 | 0.975132E+11 | 0.00 | 0.111562E+12 | 0.42 | 7.10 | 19-MAY-16:00 | 0.00 | 0.00 |
June | 0.543648E+11 | 124639.49 | 28-JUN-16:00 | 159.43 | 0.381897E+12 | 0.00 | 0.436262E+12 | 1.55 | 7.25 | 28-JUN-16:00 | 0.00 | 0.00 |
July | 0.754484E+11 | 126132.37 | 31-JUL-15:00 | 214.90 | 0.525384E+12 | 0.00 | 0.600832E+12 | 2.01 | 7.26 | 12-JUL-05:02 | 0.00 | 0.00 |
August | 0.696856E+11 | 137726.27 | 14-AUG-05:02 | 202.68 | 0.486591E+12 | 0.00 | 0.556277E+12 | 1.90 | 7.28 | 15-AUG-05:02 | 0.00 | 0.00 |
September | 0.371853E+11 | 129698.78 | 05-SEP-13:10 | 112.20 | 0.259952E+12 | 0.00 | 0.297137E+12 | 1.09 | 7.13 | 02-SEP-16:02 | 0.00 | 0.00 |
October | 0.122777E+11 | 99779.45 | 04-OCT-14:40 | 38.44 | 0.854672E+11 | 0.00 | 0.977449E+11 | 0.36 | 7.12 | 04-OCT-14:40 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.269496E+12 | 793.05 | 0.188170E+13 | 0.215119E+13 | 0.63 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.754484E+11 | 137726.27 | 214.90 | 0.525384E+12 | 0.00 | 0.600832E+12 | 2.01 | 7.28 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.174287E+11 | 744.00 | 49248.27 | 05-JAN-16:00 | 556131.00 | 13-JAN-23:05 | 22.15 | 18.33 | 15.45 |
February | 0.350142E+11 | 672.00 | 49248.27 | 10-FEB-15:40 | 632177.64 | 25-FEB-19:01 | 25.19 | 18.48 | 15.45 |
March | 0.831117E+11 | 744.00 | 49248.27 | 01-MAR-13:30 | 646494.36 | 30-MAR-21:42 | 28.71 | 19.20 | 15.45 |
April | 0.115556E+12 | 720.00 | 49248.27 | 01-APR-08:00 | 707816.73 | 01-APR-18:12 | 34.74 | 22.32 | 15.45 |
May | 0.100956E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 589518.52 | 12-MAY-05:02 | 25.66 | 21.67 | 15.45 |
June | 0.124614E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 631700.29 | 09-JUN-02:11 | 34.26 | 27.32 | 15.45 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 584009.24 | 04-JUL-18:11 | 41.20 | 31.29 | 15.45 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:01 | 738128.61 | 03-AUG-18:55 | 44.04 | 31.36 | 15.45 |
September | 0.119005E+12 | 720.00 | 49248.27 | 01-SEP-00:02 | 577411.55 | 01-SEP-00:02 | 27.16 | 23.11 | 15.45 |
October | 0.947429E+11 | 744.00 | 49248.27 | 01-OCT-00:10 | 633938.49 | 19-OCT-02:21 | 27.49 | 20.67 | 15.45 |
November | 0.703558E+11 | 720.00 | 49248.27 | 01-NOV-10:30 | 653543.94 | 11-NOV-18:11 | 28.06 | 18.53 | 15.45 |
December | 0.622155E+11 | 744.00 | 49248.27 | 01-DEC-12:50 | 681845.94 | 24-DEC-16:12 | 30.56 | 18.34 | 15.45 |
Annual Sum or Average | 0.108681E+13 | 8760.00 | 30.81 | 22.58 | 15.45 | ||||
Minimum of Months | 0.174287E+11 | 672.00 | 49248.27 | 556131.00 | 22.15 | 18.33 | 15.45 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 738128.61 | 44.04 | 31.36 | 15.45 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 903257.35 | 12.08 | 46.93 | 05-JAN-16:00 | 307056.79 | 05-JAN-16:00 | 21.09 | 21.06 | 1.55 |
February | 34505767.55 | 25.47 | 1583.64 | 14-FEB-16:00 | 662695.05 | 14-FEB-13:30 | 21.15 | 21.06 | 2.72 |
March | 0.131711E+09 | 116.91 | 2370.68 | 16-MAR-13:00 | 667285.27 | 13-MAR-15:40 | 21.36 | 21.05 | 8.94 |
April | 0.877395E+09 | 226.74 | 3752.96 | 14-APR-16:00 | 747040.15 | 27-APR-14:10 | 21.88 | 21.08 | 17.48 |
May | 0.264836E+10 | 348.26 | 13256.10 | 22-MAY-12:30 | 813424.88 | 19-MAY-16:00 | 22.80 | 21.61 | 23.59 |
June | 0.100274E+11 | 482.62 | 17569.99 | 06-JUN-12:50 | 1042087.77 | 28-JUN-16:00 | 23.27 | 21.32 | 33.76 |
July | 0.235102E+11 | 601.72 | 17569.99 | 01-JUL-03:07 | 1009695.60 | 21-JUL-16:00 | 23.86 | 21.57 | 38.69 |
August | 0.203894E+11 | 624.36 | 17569.99 | 01-AUG-12:20 | 1084561.93 | 23-AUG-16:00 | 23.56 | 21.33 | 41.46 |
September | 0.831365E+10 | 433.85 | 17569.99 | 01-SEP-11:20 | 1048350.48 | 05-SEP-13:10 | 23.33 | 21.70 | 29.39 |
October | 0.234696E+10 | 250.09 | 17569.99 | 11-OCT-11:00 | 811562.98 | 04-OCT-14:40 | 22.19 | 21.36 | 17.94 |
November | 27501376.56 | 35.38 | 1926.18 | 09-NOV-14:00 | 556857.55 | 09-NOV-14:10 | 21.11 | 21.03 | 3.37 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 163483.78 | 06-DEC-11:20 | 21.03 | 21.02 | 0.40 |
Annual Sum or Average | 0.683079E+11 | 3157.47 | 22.23 | 21.27 | 18.37 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 163483.78 | 21.03 | 21.02 | 0.40 | ||
Maximum of Months | 0.235102E+11 | 624.36 | 17569.99 | 1084561.93 | 23.86 | 21.70 | 41.46 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.09 | 21.09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.15 | 21.15 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 21.36 | 21.36 | 0.00 |
April | 0.224426E+09 | 20.83 | 3752.96 | 14-APR-16:00 | 747040.15 | 27-APR-14:10 | 21.88 | 21.77 | 1.37 |
May | 0.694509E+09 | 44.54 | 13256.10 | 22-MAY-12:30 | 813424.88 | 19-MAY-16:00 | 22.80 | 22.59 | 2.83 |
June | 0.596046E+10 | 159.33 | 17569.99 | 06-JUN-12:50 | 1042087.77 | 28-JUN-16:00 | 23.27 | 22.40 | 10.45 |
July | 0.130997E+11 | 217.42 | 17569.99 | 01-JUL-05:02 | 1009695.60 | 21-JUL-16:00 | 23.86 | 22.69 | 13.80 |
August | 0.118744E+11 | 203.63 | 17569.99 | 01-AUG-12:20 | 1084561.93 | 23-AUG-16:00 | 23.56 | 22.48 | 12.93 |
September | 0.399771E+10 | 112.22 | 17569.99 | 01-SEP-11:20 | 1048350.48 | 05-SEP-13:10 | 23.33 | 22.74 | 7.36 |
October | 0.995870E+09 | 38.44 | 17569.99 | 11-OCT-11:00 | 811562.98 | 04-OCT-14:40 | 22.19 | 22.00 | 2.44 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.11 | 21.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.368470E+11 | 796.42 | 22.23 | 21.87 | 4.29 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 21.03 | 0.00 | ||
Maximum of Months | 0.130997E+11 | 217.42 | 17569.99 | 1084561.93 | 23.86 | 22.74 | 13.80 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.243033E+12 | 0.00 | 366.81 | 851765.70 | 14-JAN-04:46 | 0.00 | 69.70 | 75.69 | 1.59 | 0.00 | 0.06 | 0.58 | 14-JAN-04:46 |
February | 0.153772E+12 | 0.00 | 293.49 | 854698.62 | 06-FEB-07:10 | 0.00 | 68.25 | 74.36 | 0.97 | 0.00 | 0.04 | 0.58 | 06-FEB-07:10 |
March | 0.574017E+11 | 0.00 | 204.24 | 823375.06 | 03-MAR-04:50 | 0.00 | 64.77 | 69.58 | 0.28 | 0.00 | 0.01 | 0.56 | 03-MAR-04:50 |
April | 0.117476E+11 | 0.00 | 75.18 | 790698.70 | 09-APR-19:10 | 0.00 | 59.47 | 62.00 | 0.06 | 0.00 | 0.00 | 0.53 | 09-APR-19:10 |
May | 0.323599E+10 | 0.00 | 21.35 | 249721.03 | 14-MAY-19:57 | 0.00 | 76.32 | 76.46 | 0.06 | 0.00 | 0.00 | 0.17 | 14-MAY-19:57 |
June | 0.574872E+09 | 0.00 | 4.52 | 224401.79 | 25-JUN-21:00 | 0.00 | 74.86 | 74.90 | 0.01 | 0.00 | 0.00 | 0.15 | 25-JUN-21:00 |
July | 0.624182E+09 | 0.00 | 0.73 | 241912.01 | 23-JUL-14:10 | 0.00 | 73.13 | 73.14 | 0.01 | 0.00 | 0.00 | 0.16 | 23-JUL-14:10 |
August | 0.404777E+09 | 0.00 | 0.47 | 242617.38 | 27-AUG-20:30 | 0.00 | 73.04 | 73.05 | 0.00 | 0.00 | 0.00 | 0.16 | 27-AUG-20:30 |
September | 0.912898E+09 | 0.00 | 3.90 | 249225.27 | 10-SEP-13:27 | 0.00 | 72.90 | 72.95 | 0.01 | 0.00 | 0.00 | 0.17 | 10-SEP-13:27 |
October | 0.306187E+11 | 0.00 | 106.79 | 482652.45 | 26-OCT-06:55 | 0.00 | 72.19 | 73.82 | 0.20 | 0.00 | 0.01 | 0.33 | 26-OCT-06:55 |
November | 0.766307E+11 | 0.00 | 240.14 | 749795.10 | 27-NOV-07:10 | 0.00 | 63.59 | 69.48 | 0.38 | 0.00 | 0.02 | 0.51 | 27-NOV-07:10 |
December | 0.216243E+12 | 0.00 | 382.27 | 1218004.26 | 09-DEC-06:01 | 0.00 | 57.80 | 70.12 | 0.96 | 0.00 | 0.05 | 0.82 | 09-DEC-06:01 |
Annual Sum or Average | 0.795200E+12 | 1699.87 | 68.85 | 72.13 | 0.37 | 0.00 | 0.02 | ||||||
Minimum of Months | 0.404777E+09 | 0.00 | 0.47 | 224401.79 | 0.00 | 57.80 | 62.00 | 0.00 | 0.00 | 0.00 | 0.15 | ||
Maximum of Months | 0.243033E+12 | 0.00 | 382.27 | 1218004.26 | 0.00 | 76.32 | 76.46 | 1.59 | 0.00 | 0.06 | 0.82 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 22.15 | 22.15 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.19 | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 28.71 | 28.71 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 34.74 | 34.74 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 25.66 | 25.66 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 34.26 | 34.26 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 41.20 | 41.20 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 44.04 | 44.04 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 27.16 | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 27.49 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.06 | 28.06 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 30.56 | 30.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 30.81 | 30.81 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 | 22.15 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 44.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 52060397.90 | 0.00 | 8.58 | 52060397.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18990.85 | 01-JAN-16:11 | 18990.85 | 01-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.158369E+10 | 0.00 | 17.44 | 0.158369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48708.54 | 13-FEB-16:00 | 48708.54 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.440033E+10 | 0.00 | 74.44 | 0.440033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50481.63 | 08-MAR-16:00 | 50481.63 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.217785E+11 | 0.00 | 183.35 | 0.217785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87812.19 | 30-APR-15:20 | 87812.19 | 30-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.379821E+11 | 0.00 | 268.19 | 0.379727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102469.53 | 21-MAY-18:51 | 102469.53 | 21-MAY-18:51 | 0.00 | 0.00 | 0.00 |
June | 0.693520E+11 | 0.00 | 382.72 | 0.692764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125054.18 | 18-JUN-14:37 | 125054.18 | 18-JUN-14:37 | 0.00 | 0.00 | 0.00 |
July | 0.843753E+11 | 0.00 | 436.16 | 0.833701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162823.43 | 02-JUL-13:33 | 126178.31 | 04-JUL-13:22 | 0.00 | 0.00 | 0.00 |
August | 0.842442E+11 | 0.00 | 452.63 | 0.831939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135657.16 | 13-AUG-13:10 | 112378.05 | 27-AUG-13:10 | 0.00 | 0.00 | 0.00 |
September | 0.570464E+11 | 0.00 | 358.69 | 0.563343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120411.00 | 10-SEP-14:10 | 120411.00 | 10-SEP-14:10 | 0.00 | 0.00 | 0.00 |
October | 0.262491E+11 | 0.00 | 203.86 | 0.262238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119702.94 | 01-OCT-12:51 | 119702.94 | 01-OCT-12:51 | 0.00 | 0.00 | 0.00 |
November | 0.881340E+09 | 0.00 | 31.28 | 0.881340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46864.58 | 19-NOV-15:20 | 46864.58 | 19-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 5225176.89 | 0.00 | 0.22 | 5225176.89 | 0.00 | 0.00 | 0.00 | 0.00 | 14993.56 | 17-DEC-16:50 | 14993.56 | 17-DEC-16:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387950E+12 | 2417.56 | 0.385072E+12 | ||||||||||||
Minimum of Months | 5225176.89 | 0.00 | 0.22 | 5225176.89 | 0.00 | 0.00 | 0.00 | 0.00 | 14993.56 | 14993.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.843753E+11 | 0.00 | 452.63 | 0.833701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162823.43 | 126178.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.926173E+09 | 0.00 | 24.58 | 0.926173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22778.61 | 05-JAN-15:50 | 22778.61 | 05-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.352250E+10 | 0.00 | 36.42 | 0.352250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78083.97 | 14-FEB-16:00 | 78083.97 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.134655E+11 | 0.00 | 150.03 | 0.134655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80124.08 | 08-MAR-16:00 | 80124.08 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.423849E+11 | 0.00 | 291.02 | 0.423849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109282.56 | 13-APR-16:00 | 109282.56 | 13-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.618696E+11 | 0.00 | 357.92 | 0.618416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112924.34 | 19-MAY-16:00 | 112924.34 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.116980E+12 | 0.00 | 497.05 | 0.116915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 148021.13 | 29-JUN-05:02 | 147733.73 | 29-JUN-05:01 | 0.00 | 0.00 | 0.00 |
July | 0.155100E+12 | 0.00 | 574.37 | 0.143542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160475.67 | 01-JUL-03:01 | 142041.81 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.159368E+12 | 0.00 | 628.65 | 0.148759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 170079.13 | 23-AUG-16:00 | 141976.25 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.891706E+11 | 0.00 | 436.11 | 0.866697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158743.94 | 05-SEP-13:10 | 117016.89 | 29-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.438498E+11 | 0.00 | 276.53 | 0.436231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116767.05 | 10-OCT-15:20 | 116767.05 | 10-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.294962E+10 | 0.00 | 56.13 | 0.294962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46171.78 | 09-NOV-14:00 | 46171.78 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 867.66 | 0.00 | 0.64 | 867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 16-DEC-12:50 | 0.50 | 16-DEC-12:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689586E+12 | 3329.45 | 0.664599E+12 | ||||||||||||
Minimum of Months | 867.66 | 0.00 | 0.64 | 867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 0.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159368E+12 | 0.00 | 628.65 | 0.148759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 170079.13 | 147733.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.687477E+10 | 0.00 | 47.85 | 0.687477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192091.67 | 05-JAN-16:00 | 192091.67 | 05-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.292179E+11 | 0.00 | 71.48 | 0.292179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 659382.96 | 14-FEB-16:00 | 659382.96 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.105873E+12 | 0.00 | 153.44 | 0.105873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 671574.50 | 08-MAR-16:00 | 671574.50 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.320719E+12 | 0.00 | 252.01 | 0.320719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 932244.47 | 13-APR-16:00 | 932244.47 | 13-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.545706E+12 | 0.00 | 352.09 | 0.545459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1079388.48 | 19-MAY-16:00 | 1079388.48 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.100464E+13 | 0.00 | 449.54 | 0.100411E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1399314.97 | 28-JUN-16:00 | 1399314.97 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.124016E+13 | 0.00 | 472.19 | 0.115784E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1471887.53 | 12-JUL-05:02 | 1346244.60 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.117639E+13 | 0.00 | 488.68 | 0.110669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1515432.30 | 15-AUG-05:02 | 1267909.82 | 01-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.785453E+12 | 0.00 | 419.34 | 0.765329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1350535.74 | 05-SEP-13:00 | 1095569.83 | 29-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.368172E+12 | 0.00 | 281.30 | 0.366586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1050866.09 | 06-OCT-15:30 | 1050866.09 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.215537E+11 | 0.00 | 72.32 | 0.215537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 363108.16 | 09-NOV-14:00 | 363108.16 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 166676.89 | 0.00 | 67.31 | 166676.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 27-DEC-06:01 | 3.24 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560475E+13 | 3127.56 | 0.543025E+13 | ||||||||||||
Minimum of Months | 166676.89 | 0.00 | 47.85 | 166676.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 3.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124016E+13 | 0.00 | 488.68 | 0.115784E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1515432.30 | 1399314.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.540561E+09 | 0.00 | 22.56 | 0.540561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17029.96 | 05-JAN-16:00 | 17029.96 | 05-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.265461E+10 | 0.00 | 34.42 | 0.265461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65926.41 | 14-FEB-16:00 | 65926.41 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.101270E+11 | 0.00 | 138.18 | 0.101270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69798.98 | 08-MAR-16:00 | 69798.98 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.342721E+11 | 0.00 | 244.04 | 0.342721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111084.46 | 13-APR-16:00 | 111084.46 | 13-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.607123E+11 | 0.00 | 347.13 | 0.606924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132312.79 | 19-MAY-16:00 | 132312.79 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.115226E+12 | 0.00 | 442.85 | 0.115179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171439.50 | 28-JUN-16:00 | 171439.50 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.143330E+12 | 0.00 | 472.37 | 0.134397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 165919.04 | 21-JUL-15:40 | 165919.04 | 21-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.133814E+12 | 0.00 | 483.87 | 0.126364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 159884.83 | 23-AUG-16:00 | 154782.35 | 01-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.856652E+11 | 0.00 | 405.81 | 0.836621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155424.02 | 05-SEP-13:30 | 131629.83 | 12-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.380558E+11 | 0.00 | 253.58 | 0.379187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122327.05 | 06-OCT-15:20 | 122327.05 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.180108E+10 | 0.00 | 52.37 | 0.180108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32383.64 | 09-NOV-14:00 | 32383.64 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 184.13 | 0.00 | 0.18 | 184.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 26-DEC-05:11 | 0.79 | 26-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626198E+12 | 2897.36 | 0.607609E+12 | ||||||||||||
Minimum of Months | 184.13 | 0.00 | 0.18 | 184.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143330E+12 | 0.00 | 483.87 | 0.134397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171439.50 | 171439.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.397198E+12 | 0.108700E+12 | 687.40 | 0.344870E+12 | 0.523276E+11 | 0.00 | 1.00 | 01-JAN-00:04 | 0.01 | 26-JAN-06:01 | 464815.98 | 22-JAN-08:63 | 415567.97 | 23-JAN-05:13 | 96257.06 | 03-JAN-23:15 | 101274.27 | 22-JAN-08:63 | 0.00 |
February | 0.606432E+12 | 0.150405E+12 | 650.23 | 0.528540E+12 | 0.778924E+11 | 0.00 | 1.00 | 01-FEB-02:02 | 0.01 | 12-FEB-22:30 | 472969.30 | 05-FEB-08:40 | 458420.54 | 05-FEB-17:40 | 100185.17 | 07-FEB-01:13 | 101414.10 | 05-FEB-08:40 | 0.00 |
March | 0.928024E+12 | 0.221921E+12 | 743.81 | 0.815444E+12 | 0.112579E+12 | 0.00 | 1.00 | 01-MAR-02:21 | 0.05 | 10-MAR-04:01 | 460974.86 | 06-MAR-23:41 | 425160.56 | 01-MAR-03:07 | 79756.81 | 23-MAR-22:10 | 105536.10 | 08-MAR-16:00 | 0.00 |
April | 0.114307E+13 | 0.289602E+12 | 720.00 | 0.101280E+13 | 0.130275E+12 | 0.00 | 1.00 | 01-APR-00:05 | 0.93 | 01-APR-03:42 | 456944.90 | 29-APR-02:42 | 399851.33 | 19-APR-03:05 | 60244.17 | 08-APR-08:30 | 142550.52 | 13-APR-17:00 | 0.00 |
May | 0.385715E+12 | 0.110379E+12 | 739.45 | 0.341576E+12 | 0.441389E+11 | 0.00 | 1.00 | 01-MAY-23:31 | 0.01 | 03-MAY-04:52 | 463042.79 | 02-MAY-02:53 | 411200.97 | 02-MAY-02:53 | 84419.43 | 07-MAY-06:23 | 101243.86 | 02-MAY-02:53 | 0.00 |
June | 0.616526E+12 | 0.199112E+12 | 719.71 | 0.560559E+12 | 0.559671E+11 | 0.00 | 1.00 | 09-JUN-01:55 | 0.04 | 09-JUN-02:20 | 470615.07 | 09-JUN-02:10 | 447258.40 | 09-JUN-02:10 | 93577.86 | 09-JUN-04:37 | 110546.60 | 28-JUN-16:00 | 0.00 |
July | 0.881356E+12 | 0.305911E+12 | 744.00 | 0.816236E+12 | 0.651200E+11 | 0.00 | 0.88 | 21-JUL-15:00 | 0.80 | 01-JUL-04:21 | 345842.07 | 08-JUL-03:30 | 308436.03 | 20-JUL-15:40 | 40531.57 | 08-JUL-03:30 | 150505.03 | 22-JUL-15:00 | 0.00 |
August | 0.114552E+13 | 0.367671E+12 | 744.00 | 0.103320E+13 | 0.112316E+12 | 0.00 | 1.00 | 01-AUG-00:01 | 1.00 | 01-AUG-00:01 | 455110.14 | 31-AUG-06:00 | 396220.79 | 31-AUG-06:00 | 65756.86 | 25-AUG-20:20 | 167934.96 | 20-AUG-16:00 | 0.00 |
September | 0.375311E+12 | 0.111611E+12 | 720.00 | 0.333701E+12 | 0.416094E+11 | 0.00 | 0.61 | 01-SEP-00:02 | 0.36 | 09-SEP-06:05 | 244889.21 | 01-SEP-00:02 | 218580.24 | 01-SEP-00:02 | 26308.98 | 01-SEP-00:02 | 78398.41 | 01-SEP-00:02 | 0.00 |
October | 0.662036E+12 | 0.174253E+12 | 733.46 | 0.583226E+12 | 0.788099E+11 | 0.00 | 1.00 | 08-OCT-04:47 | 0.01 | 12-OCT-03:03 | 471669.66 | 26-OCT-03:40 | 454194.62 | 22-OCT-23:00 | 97030.91 | 09-OCT-06:37 | 101391.81 | 26-OCT-03:40 | 0.00 |
November | 0.908108E+12 | 0.212091E+12 | 719.68 | 0.794563E+12 | 0.113546E+12 | 0.00 | 1.00 | 01-NOV-03:53 | 0.06 | 26-NOV-20:15 | 466850.03 | 20-NOV-23:20 | 428107.82 | 13-NOV-03:30 | 79181.38 | 21-NOV-00:40 | 101309.16 | 20-NOV-23:20 | 0.00 |
December | 0.120439E+13 | 0.268628E+12 | 744.00 | 0.104895E+13 | 0.155446E+12 | 0.00 | 1.00 | 01-DEC-00:05 | 0.92 | 01-DEC-04:02 | 458965.16 | 01-DEC-00:20 | 413574.09 | 01-DEC-00:05 | 63462.96 | 01-DEC-01:30 | 106374.86 | 24-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.925369E+13 | 0.252028E+13 | 8665.76 | 0.821366E+13 | 0.104003E+13 | ||||||||||||||
Minimum of Months | 0.375311E+12 | 0.108700E+12 | 650.23 | 0.333701E+12 | 0.416094E+11 | 0.00 | 0.61 | 0.01 | 244889.21 | 218580.24 | 26308.98 | 78398.41 | 0.00 | ||||||
Maximum of Months | 0.120439E+13 | 0.367671E+12 | 744.00 | 0.104895E+13 | 0.155446E+12 | 0.00 | 1.00 | 1.00 | 472969.30 | 458420.54 | 100185.17 | 167934.96 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.501206E+10 | 0.142353E+10 | 744.00 | 0.501206E+10 | 0.00 | 0.00 | 0.38 | 26-JAN-17:00 | 0.21 | 21-JAN-08:00 | 2916.74 | 26-JAN-17:00 | 2916.74 | 26-JAN-17:00 | 0.00 | 01-JAN-00:01 | 799.81 | 26-JAN-17:00 | 0.00 |
February | 0.930531E+10 | 0.249676E+10 | 672.00 | 0.930531E+10 | 0.00 | 0.00 | 0.63 | 14-FEB-17:00 | 0.44 | 06-FEB-07:50 | 4871.94 | 15-FEB-17:00 | 4871.94 | 15-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1558.68 | 14-FEB-17:00 | 0.00 |
March | 0.155328E+11 | 0.409390E+10 | 744.00 | 0.155328E+11 | 0.00 | 0.00 | 0.85 | 12-MAR-17:22 | 0.66 | 04-MAR-08:00 | 6736.51 | 24-MAR-17:40 | 6736.51 | 24-MAR-17:40 | 0.00 | 01-MAR-00:03 | 2220.47 | 08-MAR-17:00 | 0.00 |
April | 0.199730E+11 | 0.564897E+10 | 720.00 | 0.199730E+11 | 0.00 | 0.00 | 1.00 | 01-APR-15:00 | 0.88 | 01-APR-06:55 | 8575.17 | 15-APR-17:55 | 8575.17 | 15-APR-17:55 | 0.00 | 01-APR-00:05 | 2946.17 | 13-APR-17:00 | 0.00 |
May | 0.595800E+10 | 0.189545E+10 | 744.00 | 0.595800E+10 | 0.00 | 0.00 | 0.43 | 20-MAY-18:10 | 0.25 | 05-MAY-06:35 | 2973.99 | 20-MAY-18:11 | 2973.99 | 20-MAY-18:11 | 0.00 | 01-MAY-00:03 | 1185.15 | 15-MAY-18:00 | 0.00 |
June | 0.106425E+11 | 0.386250E+10 | 720.00 | 0.106425E+11 | 0.00 | 0.00 | 0.73 | 18-JUN-18:21 | 0.48 | 09-JUN-06:40 | 5121.08 | 11-JUN-18:45 | 5121.08 | 11-JUN-18:45 | 0.00 | 01-JUN-00:10 | 2451.83 | 28-JUN-16:00 | 0.00 |
July | 0.158553E+11 | 0.617578E+10 | 744.00 | 0.158553E+11 | 0.00 | 0.00 | 1.00 | 04-JUL-18:10 | 0.73 | 01-JUL-07:00 | 7016.62 | 04-JUL-18:51 | 7016.62 | 04-JUL-18:51 | 0.00 | 01-JUL-00:05 | 3376.12 | 21-JUL-18:10 | 0.00 |
August | 0.202861E+11 | 0.751730E+10 | 744.00 | 0.202861E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-07:50 | 0.91 | 31-AUG-06:00 | 7994.23 | 10-AUG-19:00 | 7994.23 | 10-AUG-19:00 | 0.00 | 01-AUG-00:01 | 3470.34 | 20-AUG-16:00 | 0.00 |
September | 0.586722E+10 | 0.195686E+10 | 720.00 | 0.586722E+10 | 0.00 | 0.00 | 0.45 | 02-SEP-17:31 | 0.26 | 09-SEP-06:55 | 2971.00 | 02-SEP-17:44 | 2971.00 | 02-SEP-17:44 | 0.00 | 01-SEP-00:02 | 1302.00 | 02-SEP-17:31 | 0.00 |
October | 0.108386E+11 | 0.314327E+10 | 744.00 | 0.108386E+11 | 0.00 | 0.00 | 0.68 | 04-OCT-17:00 | 0.46 | 26-OCT-07:00 | 4946.28 | 15-OCT-17:00 | 4946.28 | 15-OCT-17:00 | 0.00 | 01-OCT-00:10 | 1913.89 | 06-OCT-16:50 | 0.00 |
November | 0.150090E+11 | 0.385178E+10 | 720.00 | 0.150090E+11 | 0.00 | 0.00 | 0.82 | 02-NOV-16:40 | 0.67 | 27-NOV-07:40 | 6676.13 | 06-NOV-16:40 | 6676.13 | 06-NOV-16:40 | 0.00 | 01-NOV-00:10 | 1889.52 | 02-NOV-16:30 | 0.00 |
December | 0.203318E+11 | 0.500171E+10 | 744.00 | 0.203318E+11 | 0.00 | 0.00 | 0.98 | 31-DEC-16:37 | 0.86 | 23-DEC-08:00 | 8421.58 | 31-DEC-16:37 | 8421.58 | 31-DEC-16:37 | 0.00 | 01-DEC-00:05 | 2050.33 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.154612E+12 | 0.470678E+11 | 8760.00 | 0.154612E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.501206E+10 | 0.142353E+10 | 672.00 | 0.501206E+10 | 0.00 | 0.00 | 0.38 | 0.21 | 2916.74 | 2916.74 | 0.00 | 799.81 | 0.00 | ||||||
Maximum of Months | 0.203318E+11 | 0.751730E+10 | 744.00 | 0.203318E+11 | 0.00 | 0.00 | 1.00 | 0.91 | 8575.17 | 8575.17 | 0.00 | 3470.34 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.359701E+11 | 0.104431E+11 | 742.67 | 0.359701E+11 | 0.00 | 0.00 | 0.38 | 26-JAN-17:00 | 0.00 | 17-JAN-01:43 | 27332.41 | 26-JAN-17:00 | 27332.41 | 26-JAN-17:00 | 0.00 | 01-JAN-00:01 | 7507.11 | 26-JAN-17:00 | 0.00 |
February | 0.791145E+11 | 0.214655E+11 | 672.00 | 0.791145E+11 | 0.00 | 0.00 | 0.62 | 14-FEB-17:00 | 0.32 | 06-FEB-05:17 | 45918.81 | 15-FEB-17:05 | 45918.81 | 15-FEB-17:05 | 0.00 | 01-FEB-00:10 | 14662.84 | 14-FEB-17:00 | 0.00 |
March | 0.140210E+12 | 0.372245E+11 | 744.00 | 0.140210E+12 | 0.00 | 0.00 | 0.84 | 07-MAR-17:30 | 0.61 | 05-MAR-07:10 | 63889.35 | 24-MAR-17:40 | 63889.35 | 24-MAR-17:40 | 0.00 | 01-MAR-00:03 | 20957.06 | 08-MAR-17:00 | 0.00 |
April | 0.186257E+12 | 0.529351E+11 | 720.00 | 0.186257E+12 | 0.00 | 0.00 | 1.00 | 01-APR-16:12 | 0.83 | 08-APR-06:55 | 80128.87 | 07-APR-17:50 | 80128.87 | 07-APR-17:50 | 0.00 | 01-APR-00:05 | 28113.27 | 13-APR-17:00 | 0.00 |
May | 0.524979E+11 | 0.168608E+11 | 744.00 | 0.524979E+11 | 0.00 | 0.00 | 0.43 | 20-MAY-18:10 | 0.21 | 05-MAY-06:00 | 28365.63 | 20-MAY-18:11 | 28365.63 | 20-MAY-18:11 | 0.00 | 01-MAY-00:03 | 11340.08 | 15-MAY-18:00 | 0.00 |
June | 0.993864E+11 | 0.362223E+11 | 720.00 | 0.993864E+11 | 0.00 | 0.00 | 0.72 | 18-JUN-18:21 | 0.45 | 09-JUN-06:50 | 47958.30 | 18-JUN-18:28 | 47958.30 | 18-JUN-18:28 | 0.00 | 01-JUN-00:10 | 23339.21 | 28-JUN-16:00 | 0.00 |
July | 0.150491E+12 | 0.586494E+11 | 744.00 | 0.150491E+12 | 0.00 | 0.00 | 1.00 | 04-JUL-18:11 | 0.71 | 08-JUL-04:52 | 66583.72 | 04-JUL-18:34 | 66583.72 | 04-JUL-18:34 | 0.00 | 01-JUL-00:05 | 32370.65 | 21-JUL-18:10 | 0.00 |
August | 0.192240E+12 | 0.714635E+11 | 744.00 | 0.192240E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-07:50 | 0.89 | 31-AUG-06:00 | 76128.29 | 10-AUG-18:55 | 76128.29 | 10-AUG-18:55 | 0.00 | 01-AUG-00:01 | 33105.38 | 20-AUG-16:00 | 0.00 |
September | 0.519522E+11 | 0.174866E+11 | 720.00 | 0.519522E+11 | 0.00 | 0.00 | 0.44 | 02-SEP-17:42 | 0.22 | 09-SEP-07:00 | 28099.94 | 28-SEP-17:00 | 28099.94 | 28-SEP-17:00 | 0.00 | 01-SEP-00:02 | 12229.58 | 02-SEP-17:31 | 0.00 |
October | 0.968932E+11 | 0.283488E+11 | 744.00 | 0.968932E+11 | 0.00 | 0.00 | 0.68 | 04-OCT-17:00 | 0.41 | 26-OCT-06:00 | 46689.60 | 04-OCT-17:00 | 46689.60 | 04-OCT-17:00 | 0.00 | 01-OCT-00:10 | 18155.80 | 06-OCT-16:50 | 0.00 |
November | 0.133848E+12 | 0.346328E+11 | 720.00 | 0.133848E+12 | 0.00 | 0.00 | 0.82 | 02-NOV-16:40 | 0.59 | 27-NOV-06:30 | 62892.97 | 02-NOV-16:40 | 62892.97 | 02-NOV-16:40 | 0.00 | 01-NOV-00:10 | 17876.82 | 02-NOV-16:30 | 0.00 |
December | 0.179922E+12 | 0.447202E+11 | 744.00 | 0.179922E+12 | 0.00 | 0.00 | 0.96 | 29-DEC-16:50 | 0.77 | 26-DEC-06:20 | 78628.66 | 29-DEC-16:50 | 78628.66 | 29-DEC-16:50 | 0.00 | 01-DEC-00:05 | 19296.45 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.139878E+13 | 0.430453E+12 | 8758.67 | 0.139878E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.359701E+11 | 0.104431E+11 | 672.00 | 0.359701E+11 | 0.00 | 0.00 | 0.38 | 0.00 | 27332.41 | 27332.41 | 0.00 | 7507.11 | 0.00 | ||||||
Maximum of Months | 0.192240E+12 | 0.714635E+11 | 744.00 | 0.192240E+12 | 0.00 | 0.00 | 1.00 | 0.89 | 80128.87 | 80128.87 | 0.00 | 33105.38 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.182442E+10 | 0.542472E+09 | 507.03 | 0.182442E+10 | 0.00 | 0.00 | 0.36 | 26-JAN-17:00 | 0.00 | 01-JAN-00:01 | 2676.49 | 26-JAN-17:00 | 2676.49 | 26-JAN-17:00 | 0.00 | 01-JAN-00:01 | 738.09 | 26-JAN-17:00 | 0.00 |
February | 0.647521E+10 | 0.178973E+10 | 670.31 | 0.647521E+10 | 0.00 | 0.00 | 0.61 | 14-FEB-17:00 | 0.00 | 06-FEB-00:45 | 4625.09 | 15-FEB-17:00 | 4625.09 | 15-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1478.49 | 14-FEB-17:00 | 0.00 |
March | 0.130371E+11 | 0.350527E+10 | 744.00 | 0.130371E+11 | 0.00 | 0.00 | 0.83 | 07-MAR-17:30 | 0.45 | 05-MAR-07:33 | 6445.90 | 24-MAR-17:40 | 6445.90 | 24-MAR-17:40 | 0.00 | 01-MAR-00:03 | 2125.85 | 08-MAR-17:00 | 0.00 |
April | 0.181830E+11 | 0.521996E+10 | 720.00 | 0.181830E+11 | 0.00 | 0.00 | 1.00 | 01-APR-16:50 | 0.74 | 08-APR-05:30 | 8074.37 | 05-APR-18:00 | 8074.37 | 05-APR-18:00 | 0.00 | 01-APR-00:05 | 2880.59 | 13-APR-17:00 | 0.00 |
May | 0.505070E+10 | 0.164333E+10 | 744.00 | 0.505070E+10 | 0.00 | 0.00 | 0.44 | 20-MAY-18:10 | 0.13 | 05-MAY-06:00 | 3013.98 | 20-MAY-18:10 | 3013.98 | 20-MAY-18:10 | 0.00 | 01-MAY-00:03 | 1184.86 | 15-MAY-18:00 | 0.00 |
June | 0.995625E+10 | 0.365316E+10 | 720.00 | 0.995625E+10 | 0.00 | 0.00 | 0.74 | 18-JUN-18:21 | 0.39 | 09-JUN-06:00 | 5095.98 | 18-JUN-18:24 | 5095.98 | 18-JUN-18:24 | 0.00 | 01-JUN-00:10 | 2425.83 | 28-JUN-16:00 | 0.00 |
July | 0.151887E+11 | 0.594068E+10 | 744.00 | 0.151887E+11 | 0.00 | 0.00 | 1.00 | 04-JUL-17:31 | 0.68 | 08-JUL-06:25 | 6942.91 | 04-JUL-19:12 | 6942.91 | 04-JUL-19:12 | 0.00 | 01-JUL-00:05 | 3319.38 | 21-JUL-18:00 | 0.00 |
August | 0.193910E+11 | 0.724163E+10 | 744.00 | 0.193910E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-08:40 | 0.86 | 31-AUG-06:00 | 7695.16 | 10-AUG-18:50 | 7695.16 | 10-AUG-18:50 | 0.00 | 01-AUG-00:01 | 3393.27 | 20-AUG-16:00 | 0.00 |
September | 0.505795E+10 | 0.172210E+10 | 720.00 | 0.505795E+10 | 0.00 | 0.00 | 0.45 | 02-SEP-17:42 | 0.17 | 09-SEP-07:00 | 2931.28 | 02-SEP-17:46 | 2931.28 | 02-SEP-17:46 | 0.00 | 01-SEP-00:02 | 1283.17 | 02-SEP-17:31 | 0.00 |
October | 0.899477E+10 | 0.267014E+10 | 744.00 | 0.899477E+10 | 0.00 | 0.00 | 0.68 | 04-OCT-17:00 | 0.28 | 26-OCT-05:15 | 4760.96 | 04-OCT-17:00 | 4760.96 | 04-OCT-17:00 | 0.00 | 01-OCT-00:10 | 1854.33 | 06-OCT-16:50 | 0.00 |
November | 0.119877E+11 | 0.314863E+10 | 720.00 | 0.119877E+11 | 0.00 | 0.00 | 0.80 | 02-NOV-16:40 | 0.39 | 27-NOV-04:55 | 6299.49 | 02-NOV-16:40 | 6299.49 | 02-NOV-16:40 | 0.00 | 01-NOV-00:10 | 1796.56 | 02-NOV-16:30 | 0.00 |
December | 0.160266E+11 | 0.405328E+10 | 744.00 | 0.160266E+11 | 0.00 | 0.00 | 0.93 | 29-DEC-16:50 | 0.54 | 26-DEC-04:10 | 7799.35 | 29-DEC-16:50 | 7799.35 | 29-DEC-16:50 | 0.00 | 01-DEC-00:05 | 1916.47 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.131173E+12 | 0.411304E+11 | 8521.34 | 0.131173E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.182442E+10 | 0.542472E+09 | 507.03 | 0.182442E+10 | 0.00 | 0.00 | 0.36 | 0.00 | 2676.49 | 2676.49 | 0.00 | 738.09 | 0.00 | ||||||
Maximum of Months | 0.193910E+11 | 0.724163E+10 | 744.00 | 0.193910E+11 | 0.00 | 0.00 | 1.00 | 0.86 | 8074.37 | 8074.37 | 0.00 | 3393.27 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.52 | 0.00 | 137.52 | 10.28 | 539.42 | 0.00 | 0.00 | 744.00 |
February | 171.87 | 0.00 | 171.87 | 32.93 | 484.88 | 0.00 | 0.00 | 672.00 |
March | 216.80 | 0.00 | 216.80 | 93.39 | 375.89 | 0.00 | 0.00 | 744.00 |
April | 275.01 | 2.32 | 272.69 | 166.92 | 248.48 | 0.00 | 0.00 | 720.00 |
May | 298.91 | 19.20 | 279.70 | 227.61 | 175.16 | 0.00 | 0.00 | 744.00 |
June | 339.61 | 55.49 | 284.13 | 345.59 | 109.91 | 0.00 | 0.00 | 720.00 |
July | 311.73 | 25.87 | 285.86 | 373.34 | 71.06 | 0.00 | 0.00 | 744.00 |
August | 289.21 | 6.43 | 282.78 | 327.57 | 82.34 | 0.00 | 0.00 | 744.00 |
September | 231.31 | 0.06 | 231.26 | 223.97 | 155.14 | 0.00 | 0.00 | 720.00 |
October | 172.61 | 0.00 | 172.61 | 91.90 | 291.67 | 0.00 | 0.00 | 744.00 |
November | 146.59 | 0.00 | 146.59 | 20.81 | 436.24 | 0.00 | 0.00 | 720.00 |
December | 117.05 | 0.00 | 117.05 | 1.40 | 586.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 225.88 | 9.13 | 216.75 | 160.36 | 295.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.05 | 0.00 | 117.05 | 1.40 | 71.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 339.61 | 55.49 | 285.86 | 373.34 | 586.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.52 | 0.00 | 137.52 | 10.28 | 539.42 | 0.00 | 0.00 | 744.00 |
February | 171.87 | 0.00 | 171.87 | 32.93 | 484.88 | 0.00 | 0.00 | 672.00 |
March | 216.79 | 0.00 | 216.79 | 93.38 | 375.89 | 0.00 | 0.00 | 744.00 |
April | 275.01 | 2.32 | 272.69 | 166.92 | 248.48 | 0.00 | 0.00 | 720.00 |
May | 298.90 | 19.20 | 279.70 | 227.60 | 175.16 | 0.00 | 0.00 | 744.00 |
June | 339.61 | 55.49 | 284.12 | 345.59 | 109.91 | 0.00 | 0.00 | 720.00 |
July | 311.73 | 25.87 | 285.86 | 373.34 | 71.06 | 0.00 | 0.00 | 744.00 |
August | 289.21 | 6.43 | 282.78 | 327.57 | 82.34 | 0.00 | 0.00 | 744.00 |
September | 231.31 | 0.06 | 231.25 | 223.97 | 155.14 | 0.00 | 0.00 | 720.00 |
October | 172.61 | 0.00 | 172.61 | 91.90 | 291.67 | 0.00 | 0.00 | 744.00 |
November | 146.58 | 0.00 | 146.58 | 20.81 | 436.24 | 0.00 | 0.00 | 720.00 |
December | 117.05 | 0.00 | 117.05 | 1.40 | 586.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 225.88 | 9.13 | 216.75 | 160.36 | 295.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.05 | 0.00 | 117.05 | 1.40 | 71.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 339.61 | 55.49 | 285.86 | 373.34 | 586.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.52 | 0.00 | 137.52 | 10.28 | 539.42 | 0.00 | 0.00 | 744.00 |
February | 171.87 | 0.00 | 171.87 | 32.93 | 484.88 | 0.00 | 0.00 | 672.00 |
March | 216.80 | 0.00 | 216.80 | 93.38 | 375.89 | 0.00 | 0.00 | 744.00 |
April | 275.01 | 2.32 | 272.69 | 166.92 | 248.48 | 0.00 | 0.00 | 720.00 |
May | 298.90 | 19.20 | 279.70 | 227.60 | 175.16 | 0.00 | 0.00 | 744.00 |
June | 339.61 | 55.49 | 284.12 | 345.59 | 109.91 | 0.00 | 0.00 | 720.00 |
July | 311.73 | 25.87 | 285.86 | 373.34 | 71.06 | 0.00 | 0.00 | 744.00 |
August | 289.21 | 6.43 | 282.78 | 327.57 | 82.34 | 0.00 | 0.00 | 744.00 |
September | 231.31 | 0.06 | 231.25 | 223.97 | 155.14 | 0.00 | 0.00 | 720.00 |
October | 172.61 | 0.00 | 172.61 | 91.90 | 291.67 | 0.00 | 0.00 | 744.00 |
November | 146.58 | 0.00 | 146.58 | 20.81 | 436.24 | 0.00 | 0.00 | 720.00 |
December | 117.05 | 0.00 | 117.05 | 1.40 | 586.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 225.88 | 9.13 | 216.75 | 160.36 | 295.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.05 | 0.00 | 117.05 | 1.40 | 71.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 339.61 | 55.49 | 285.86 | 373.34 | 586.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.52 | 0.00 | 137.52 | 10.28 | 539.42 | 0.00 | 0.00 | 744.00 |
February | 171.87 | 0.00 | 171.87 | 32.93 | 484.88 | 0.00 | 0.00 | 672.00 |
March | 216.79 | 0.00 | 216.79 | 93.38 | 375.89 | 0.00 | 0.00 | 744.00 |
April | 275.01 | 2.32 | 272.69 | 166.92 | 248.48 | 0.00 | 0.00 | 720.00 |
May | 298.90 | 19.20 | 279.70 | 227.60 | 175.16 | 0.00 | 0.00 | 744.00 |
June | 339.61 | 55.49 | 284.12 | 345.59 | 109.91 | 0.00 | 0.00 | 720.00 |
July | 311.73 | 25.87 | 285.86 | 373.34 | 71.06 | 0.00 | 0.00 | 744.00 |
August | 289.21 | 6.43 | 282.78 | 327.57 | 82.34 | 0.00 | 0.00 | 744.00 |
September | 231.31 | 0.06 | 231.25 | 223.97 | 155.14 | 0.00 | 0.00 | 720.00 |
October | 172.61 | 0.00 | 172.61 | 91.90 | 291.67 | 0.00 | 0.00 | 744.00 |
November | 146.58 | 0.00 | 146.58 | 20.81 | 436.24 | 0.00 | 0.00 | 720.00 |
December | 117.05 | 0.00 | 117.05 | 1.40 | 586.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 225.88 | 9.13 | 216.75 | 160.36 | 295.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.05 | 0.00 | 117.05 | 1.40 | 71.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 339.61 | 55.49 | 285.86 | 373.34 | 586.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.51 | 0.00 | 137.51 | 10.28 | 539.39 | 0.00 | 0.00 | 744.00 |
February | 171.87 | 0.00 | 171.87 | 32.93 | 484.86 | 0.00 | 0.00 | 672.00 |
March | 216.79 | 0.00 | 216.79 | 93.38 | 375.88 | 0.00 | 0.00 | 744.00 |
April | 275.00 | 2.32 | 272.68 | 166.91 | 248.47 | 0.00 | 0.00 | 720.00 |
May | 298.89 | 19.20 | 279.69 | 227.60 | 175.16 | 0.00 | 0.00 | 744.00 |
June | 339.60 | 55.48 | 284.11 | 345.57 | 109.90 | 0.00 | 0.00 | 720.00 |
July | 311.72 | 25.87 | 285.84 | 373.32 | 71.06 | 0.00 | 0.00 | 744.00 |
August | 289.20 | 6.43 | 282.77 | 327.55 | 82.34 | 0.00 | 0.00 | 744.00 |
September | 231.30 | 0.06 | 231.24 | 223.96 | 155.14 | 0.00 | 0.00 | 720.00 |
October | 172.60 | 0.00 | 172.60 | 91.89 | 291.66 | 0.00 | 0.00 | 744.00 |
November | 146.58 | 0.00 | 146.58 | 20.81 | 436.23 | 0.00 | 0.00 | 720.00 |
December | 117.04 | 0.00 | 117.04 | 1.40 | 586.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 225.87 | 9.13 | 216.74 | 160.35 | 295.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 117.04 | 0.00 | 117.04 | 1.40 | 71.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 339.60 | 55.48 | 285.84 | 373.32 | 586.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 423.19 | 236.62 | 186.57 | 264.82 | 530.43 | 0.00 | 0.00 | 744.00 |
February | 514.12 | 277.16 | 236.96 | 372.74 | 480.20 | 0.00 | 0.00 | 672.00 |
March | 678.26 | 385.60 | 292.66 | 604.06 | 371.76 | 0.00 | 0.00 | 744.00 |
April | 926.67 | 527.96 | 398.71 | 936.80 | 246.70 | 0.00 | 0.00 | 720.00 |
May | 884.02 | 503.74 | 380.28 | 944.11 | 188.09 | 0.00 | 0.00 | 744.00 |
June | 952.97 | 586.99 | 365.98 | 1141.11 | 114.16 | 0.00 | 0.00 | 720.00 |
July | 881.87 | 504.23 | 377.64 | 1097.84 | 69.08 | 0.00 | 0.00 | 744.00 |
August | 872.76 | 481.16 | 391.61 | 1051.45 | 75.92 | 0.00 | 0.00 | 744.00 |
September | 726.54 | 406.54 | 320.00 | 815.71 | 157.54 | 0.00 | 0.00 | 720.00 |
October | 631.79 | 400.84 | 230.95 | 608.68 | 286.83 | 0.00 | 0.00 | 744.00 |
November | 493.80 | 290.31 | 203.49 | 370.83 | 428.15 | 0.00 | 0.00 | 720.00 |
December | 400.19 | 243.58 | 156.60 | 247.68 | 568.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 699.53 | 404.23 | 295.30 | 706.16 | 292.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 400.19 | 236.62 | 156.60 | 247.68 | 69.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 952.97 | 586.99 | 398.71 | 1141.11 | 568.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 423.19 | 236.62 | 186.57 | 264.82 | 530.43 | 0.00 | 0.00 | 744.00 |
February | 514.12 | 277.16 | 236.96 | 372.74 | 480.20 | 0.00 | 0.00 | 672.00 |
March | 678.26 | 385.60 | 292.66 | 604.06 | 371.76 | 0.00 | 0.00 | 744.00 |
April | 926.67 | 527.96 | 398.71 | 936.80 | 246.70 | 0.00 | 0.00 | 720.00 |
May | 884.02 | 503.74 | 380.28 | 944.11 | 188.09 | 0.00 | 0.00 | 744.00 |
June | 952.97 | 586.99 | 365.98 | 1141.11 | 114.16 | 0.00 | 0.00 | 720.00 |
July | 881.87 | 504.23 | 377.64 | 1097.84 | 69.08 | 0.00 | 0.00 | 744.00 |
August | 872.76 | 481.16 | 391.61 | 1051.45 | 75.92 | 0.00 | 0.00 | 744.00 |
September | 726.54 | 406.54 | 320.00 | 815.71 | 157.54 | 0.00 | 0.00 | 720.00 |
October | 631.79 | 400.84 | 230.95 | 608.68 | 286.83 | 0.00 | 0.00 | 744.00 |
November | 493.80 | 290.31 | 203.49 | 370.83 | 428.15 | 0.00 | 0.00 | 720.00 |
December | 400.19 | 243.58 | 156.60 | 247.68 | 568.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 699.53 | 404.23 | 295.30 | 706.16 | 292.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 400.19 | 236.62 | 156.60 | 247.68 | 69.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 952.97 | 586.99 | 398.71 | 1141.11 | 568.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 423.19 | 236.62 | 186.57 | 264.82 | 530.42 | 0.00 | 0.00 | 744.00 |
February | 514.11 | 277.16 | 236.95 | 372.73 | 480.19 | 0.00 | 0.00 | 672.00 |
March | 678.24 | 385.59 | 292.66 | 604.05 | 371.76 | 0.00 | 0.00 | 744.00 |
April | 926.66 | 527.95 | 398.70 | 936.79 | 246.70 | 0.00 | 0.00 | 720.00 |
May | 884.01 | 503.73 | 380.28 | 944.10 | 188.09 | 0.00 | 0.00 | 744.00 |
June | 952.95 | 586.98 | 365.97 | 1141.09 | 114.15 | 0.00 | 0.00 | 720.00 |
July | 881.85 | 504.22 | 377.63 | 1097.82 | 69.08 | 0.00 | 0.00 | 744.00 |
August | 872.75 | 481.15 | 391.60 | 1051.43 | 75.92 | 0.00 | 0.00 | 744.00 |
September | 726.52 | 406.53 | 319.99 | 815.70 | 157.54 | 0.00 | 0.00 | 720.00 |
October | 631.78 | 400.84 | 230.94 | 608.67 | 286.83 | 0.00 | 0.00 | 744.00 |
November | 493.79 | 290.31 | 203.49 | 370.83 | 428.14 | 0.00 | 0.00 | 720.00 |
December | 400.18 | 243.58 | 156.60 | 247.67 | 567.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 699.52 | 404.22 | 295.30 | 706.15 | 292.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 400.18 | 236.62 | 156.60 | 247.67 | 69.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 952.95 | 586.98 | 398.70 | 1141.09 | 567.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1017.03 | 791.47 | 225.56 | 1042.35 | 468.31 | 0.00 | 0.00 | 744.00 |
February | 995.57 | 727.40 | 268.17 | 987.07 | 438.92 | 0.00 | 0.00 | 672.00 |
March | 733.22 | 443.30 | 289.92 | 633.18 | 358.05 | 0.00 | 0.00 | 744.00 |
April | 571.64 | 234.57 | 337.07 | 407.65 | 249.74 | 0.00 | 0.00 | 720.00 |
May | 381.15 | 83.71 | 297.44 | 282.97 | 181.05 | 0.00 | 0.00 | 744.00 |
June | 322.31 | 39.49 | 282.82 | 345.35 | 116.97 | 0.00 | 0.00 | 720.00 |
July | 356.71 | 56.77 | 299.94 | 404.40 | 74.27 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 159.43 | 331.28 | 474.79 | 86.35 | 0.00 | 0.00 | 744.00 |
September | 678.63 | 378.39 | 300.24 | 661.33 | 157.43 | 0.00 | 0.00 | 720.00 |
October | 928.97 | 684.29 | 244.68 | 951.61 | 276.32 | 0.00 | 0.00 | 744.00 |
November | 1034.75 | 794.29 | 240.46 | 1068.72 | 384.62 | 0.00 | 0.00 | 720.00 |
December | 1103.32 | 910.17 | 193.15 | 1157.53 | 487.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 716.27 | 440.47 | 275.80 | 699.95 | 272.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 322.31 | 39.49 | 193.15 | 282.97 | 74.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1103.32 | 910.17 | 337.07 | 1157.53 | 487.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1017.02 | 791.47 | 225.56 | 1042.35 | 468.31 | 0.00 | 0.00 | 744.00 |
February | 995.56 | 727.39 | 268.17 | 987.07 | 438.92 | 0.00 | 0.00 | 672.00 |
March | 733.22 | 443.30 | 289.92 | 633.17 | 358.05 | 0.00 | 0.00 | 744.00 |
April | 571.64 | 234.56 | 337.07 | 407.65 | 249.74 | 0.00 | 0.00 | 720.00 |
May | 381.15 | 83.71 | 297.44 | 282.97 | 181.05 | 0.00 | 0.00 | 744.00 |
June | 322.31 | 39.49 | 282.82 | 345.35 | 116.97 | 0.00 | 0.00 | 720.00 |
July | 356.71 | 56.77 | 299.94 | 404.40 | 74.27 | 0.00 | 0.00 | 744.00 |
August | 490.70 | 159.43 | 331.28 | 474.79 | 86.35 | 0.00 | 0.00 | 744.00 |
September | 678.62 | 378.39 | 300.24 | 661.32 | 157.43 | 0.00 | 0.00 | 720.00 |
October | 928.96 | 684.29 | 244.68 | 951.60 | 276.32 | 0.00 | 0.00 | 744.00 |
November | 1034.75 | 794.29 | 240.46 | 1068.71 | 384.62 | 0.00 | 0.00 | 720.00 |
December | 1103.31 | 910.16 | 193.15 | 1157.52 | 487.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 716.27 | 440.47 | 275.80 | 699.94 | 272.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 322.31 | 39.49 | 193.15 | 282.97 | 74.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1103.31 | 910.16 | 337.07 | 1157.52 | 487.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1017.03 | 791.47 | 225.56 | 1042.35 | 468.31 | 0.00 | 0.00 | 744.00 |
February | 995.57 | 727.40 | 268.17 | 987.07 | 438.92 | 0.00 | 0.00 | 672.00 |
March | 733.22 | 443.30 | 289.92 | 633.18 | 358.05 | 0.00 | 0.00 | 744.00 |
April | 571.64 | 234.57 | 337.07 | 407.65 | 249.74 | 0.00 | 0.00 | 720.00 |
May | 381.15 | 83.71 | 297.44 | 282.97 | 181.05 | 0.00 | 0.00 | 744.00 |
June | 322.31 | 39.49 | 282.82 | 345.35 | 116.97 | 0.00 | 0.00 | 720.00 |
July | 356.71 | 56.77 | 299.94 | 404.40 | 74.27 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 159.43 | 331.28 | 474.79 | 86.35 | 0.00 | 0.00 | 744.00 |
September | 678.63 | 378.39 | 300.24 | 661.33 | 157.43 | 0.00 | 0.00 | 720.00 |
October | 928.97 | 684.29 | 244.68 | 951.61 | 276.32 | 0.00 | 0.00 | 744.00 |
November | 1034.75 | 794.29 | 240.46 | 1068.72 | 384.62 | 0.00 | 0.00 | 720.00 |
December | 1103.32 | 910.17 | 193.15 | 1157.53 | 487.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 716.27 | 440.47 | 275.80 | 699.95 | 272.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 322.31 | 39.49 | 193.15 | 282.97 | 74.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1103.32 | 910.17 | 337.07 | 1157.53 | 487.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1017.02 | 791.47 | 225.56 | 1042.35 | 468.31 | 0.00 | 0.00 | 744.00 |
February | 995.56 | 727.39 | 268.17 | 987.07 | 438.92 | 0.00 | 0.00 | 672.00 |
March | 733.22 | 443.30 | 289.92 | 633.17 | 358.05 | 0.00 | 0.00 | 744.00 |
April | 571.64 | 234.56 | 337.07 | 407.65 | 249.74 | 0.00 | 0.00 | 720.00 |
May | 381.15 | 83.71 | 297.44 | 282.97 | 181.05 | 0.00 | 0.00 | 744.00 |
June | 322.31 | 39.49 | 282.82 | 345.35 | 116.97 | 0.00 | 0.00 | 720.00 |
July | 356.71 | 56.77 | 299.94 | 404.40 | 74.27 | 0.00 | 0.00 | 744.00 |
August | 490.70 | 159.43 | 331.28 | 474.79 | 86.35 | 0.00 | 0.00 | 744.00 |
September | 678.62 | 378.39 | 300.24 | 661.32 | 157.43 | 0.00 | 0.00 | 720.00 |
October | 928.96 | 684.29 | 244.68 | 951.60 | 276.32 | 0.00 | 0.00 | 744.00 |
November | 1034.75 | 794.29 | 240.46 | 1068.71 | 384.62 | 0.00 | 0.00 | 720.00 |
December | 1103.31 | 910.16 | 193.15 | 1157.52 | 487.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 716.27 | 440.47 | 275.80 | 699.94 | 272.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 322.31 | 39.49 | 193.15 | 282.97 | 74.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1103.31 | 910.16 | 337.07 | 1157.52 | 487.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1016.99 | 791.44 | 225.55 | 1042.31 | 468.29 | 0.00 | 0.00 | 744.00 |
February | 995.52 | 727.37 | 268.16 | 987.03 | 438.90 | 0.00 | 0.00 | 672.00 |
March | 733.19 | 443.28 | 289.91 | 633.15 | 358.04 | 0.00 | 0.00 | 744.00 |
April | 571.62 | 234.56 | 337.06 | 407.63 | 249.73 | 0.00 | 0.00 | 720.00 |
May | 381.14 | 83.70 | 297.43 | 282.96 | 181.05 | 0.00 | 0.00 | 744.00 |
June | 322.30 | 39.49 | 282.81 | 345.33 | 116.96 | 0.00 | 0.00 | 720.00 |
July | 356.70 | 56.77 | 299.93 | 404.38 | 74.26 | 0.00 | 0.00 | 744.00 |
August | 490.69 | 159.42 | 331.27 | 474.77 | 86.35 | 0.00 | 0.00 | 744.00 |
September | 678.60 | 378.37 | 300.22 | 661.30 | 157.42 | 0.00 | 0.00 | 720.00 |
October | 928.93 | 684.26 | 244.67 | 951.57 | 276.31 | 0.00 | 0.00 | 744.00 |
November | 1034.71 | 794.26 | 240.45 | 1068.68 | 384.60 | 0.00 | 0.00 | 720.00 |
December | 1103.27 | 910.13 | 193.14 | 1157.47 | 487.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 716.24 | 440.45 | 275.79 | 699.92 | 272.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 322.30 | 39.49 | 193.14 | 282.96 | 74.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1103.27 | 910.13 | 337.06 | 1157.47 | 487.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 436.51 | 248.94 | 187.57 | 311.95 | 584.14 | 0.00 | 0.00 | 744.00 |
February | 561.86 | 324.56 | 237.30 | 453.22 | 544.98 | 0.00 | 0.00 | 672.00 |
March | 627.62 | 334.12 | 293.50 | 552.15 | 440.26 | 0.00 | 0.00 | 744.00 |
April | 801.01 | 426.32 | 374.68 | 776.05 | 310.33 | 0.00 | 0.00 | 720.00 |
May | 759.32 | 391.20 | 368.12 | 792.29 | 215.87 | 0.00 | 0.00 | 744.00 |
June | 813.94 | 454.10 | 359.84 | 966.22 | 149.76 | 0.00 | 0.00 | 720.00 |
July | 734.21 | 359.27 | 374.94 | 896.56 | 99.31 | 0.00 | 0.00 | 744.00 |
August | 750.30 | 347.04 | 403.27 | 879.29 | 120.99 | 0.00 | 0.00 | 744.00 |
September | 677.77 | 356.98 | 320.79 | 757.05 | 187.55 | 0.00 | 0.00 | 720.00 |
October | 620.01 | 385.36 | 234.65 | 611.91 | 342.49 | 0.00 | 0.00 | 744.00 |
November | 486.72 | 286.35 | 200.37 | 378.28 | 495.17 | 0.00 | 0.00 | 720.00 |
December | 420.96 | 264.00 | 156.95 | 287.60 | 657.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 640.91 | 348.02 | 292.89 | 639.18 | 344.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 420.96 | 248.94 | 156.95 | 287.60 | 99.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 813.94 | 454.10 | 403.27 | 966.22 | 657.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 436.51 | 248.94 | 187.57 | 311.95 | 584.14 | 0.00 | 0.00 | 744.00 |
February | 561.86 | 324.56 | 237.30 | 453.22 | 544.98 | 0.00 | 0.00 | 672.00 |
March | 627.62 | 334.12 | 293.50 | 552.15 | 440.26 | 0.00 | 0.00 | 744.00 |
April | 801.01 | 426.32 | 374.68 | 776.05 | 310.33 | 0.00 | 0.00 | 720.00 |
May | 759.32 | 391.20 | 368.12 | 792.29 | 215.87 | 0.00 | 0.00 | 744.00 |
June | 813.94 | 454.10 | 359.84 | 966.22 | 149.76 | 0.00 | 0.00 | 720.00 |
July | 734.21 | 359.27 | 374.94 | 896.56 | 99.31 | 0.00 | 0.00 | 744.00 |
August | 750.30 | 347.04 | 403.27 | 879.29 | 120.99 | 0.00 | 0.00 | 744.00 |
September | 677.77 | 356.98 | 320.79 | 757.05 | 187.55 | 0.00 | 0.00 | 720.00 |
October | 620.01 | 385.36 | 234.65 | 611.91 | 342.49 | 0.00 | 0.00 | 744.00 |
November | 486.72 | 286.35 | 200.37 | 378.28 | 495.17 | 0.00 | 0.00 | 720.00 |
December | 420.96 | 264.00 | 156.95 | 287.60 | 657.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 640.91 | 348.02 | 292.89 | 639.18 | 344.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 420.96 | 248.94 | 156.95 | 287.60 | 99.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 813.94 | 454.10 | 403.27 | 966.22 | 657.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 436.50 | 248.94 | 187.56 | 311.95 | 584.13 | 0.00 | 0.00 | 744.00 |
February | 561.85 | 324.56 | 237.30 | 453.21 | 544.97 | 0.00 | 0.00 | 672.00 |
March | 627.61 | 334.11 | 293.49 | 552.14 | 440.25 | 0.00 | 0.00 | 744.00 |
April | 800.99 | 426.31 | 374.68 | 776.03 | 310.33 | 0.00 | 0.00 | 720.00 |
May | 759.30 | 391.19 | 368.11 | 792.28 | 215.87 | 0.00 | 0.00 | 744.00 |
June | 813.92 | 454.09 | 359.84 | 966.20 | 149.76 | 0.00 | 0.00 | 720.00 |
July | 734.20 | 359.27 | 374.93 | 896.55 | 99.31 | 0.00 | 0.00 | 744.00 |
August | 750.29 | 347.03 | 403.26 | 879.27 | 120.99 | 0.00 | 0.00 | 744.00 |
September | 677.76 | 356.98 | 320.78 | 757.04 | 187.55 | 0.00 | 0.00 | 720.00 |
October | 620.00 | 385.35 | 234.65 | 611.90 | 342.48 | 0.00 | 0.00 | 744.00 |
November | 486.71 | 286.35 | 200.36 | 378.27 | 495.16 | 0.00 | 0.00 | 720.00 |
December | 420.95 | 264.00 | 156.95 | 287.59 | 657.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 640.90 | 348.02 | 292.88 | 639.17 | 344.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 420.95 | 248.94 | 156.95 | 287.59 | 99.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 813.92 | 454.09 | 403.26 | 966.20 | 657.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.59 | 0.00 | 687.59 | 81.02 | 2477.45 | 0.00 | 0.00 | 744.00 |
February | 859.37 | 0.00 | 859.37 | 206.88 | 2232.67 | 0.00 | 0.00 | 672.00 |
March | 1083.98 | 0.00 | 1083.98 | 510.12 | 1739.67 | 0.00 | 0.00 | 744.00 |
April | 1375.06 | 11.60 | 1363.46 | 875.08 | 1153.64 | 0.00 | 0.00 | 720.00 |
May | 1494.52 | 96.01 | 1398.51 | 1164.28 | 830.04 | 0.00 | 0.00 | 744.00 |
June | 1698.06 | 277.43 | 1420.63 | 1757.36 | 532.12 | 0.00 | 0.00 | 720.00 |
July | 1558.67 | 129.37 | 1429.29 | 1892.01 | 355.50 | 0.00 | 0.00 | 744.00 |
August | 1446.06 | 32.16 | 1413.90 | 1665.96 | 408.95 | 0.00 | 0.00 | 744.00 |
September | 1156.56 | 0.28 | 1156.28 | 1142.77 | 730.77 | 0.00 | 0.00 | 720.00 |
October | 863.04 | 0.00 | 863.04 | 491.94 | 1346.46 | 0.00 | 0.00 | 744.00 |
November | 732.92 | 0.00 | 732.92 | 131.63 | 1979.76 | 0.00 | 0.00 | 720.00 |
December | 585.24 | 0.00 | 585.24 | 18.66 | 2620.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1129.40 | 45.65 | 1083.75 | 831.62 | 1363.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 585.24 | 0.00 | 585.24 | 18.66 | 355.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1698.06 | 277.43 | 1429.29 | 1892.01 | 2620.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1269.57 | 709.86 | 559.71 | 820.08 | 1494.24 | 0.00 | 0.00 | 744.00 |
February | 1542.34 | 831.47 | 710.87 | 1141.07 | 1360.42 | 0.00 | 0.00 | 672.00 |
March | 2034.75 | 1156.77 | 877.98 | 1822.89 | 1062.88 | 0.00 | 0.00 | 744.00 |
April | 2779.99 | 1583.86 | 1196.12 | 2802.57 | 725.69 | 0.00 | 0.00 | 720.00 |
May | 2652.05 | 1511.21 | 1140.83 | 2826.25 | 544.80 | 0.00 | 0.00 | 744.00 |
June | 2858.88 | 1760.96 | 1097.92 | 3414.45 | 344.24 | 0.00 | 0.00 | 720.00 |
July | 2645.58 | 1512.68 | 1132.90 | 3279.32 | 231.91 | 0.00 | 0.00 | 744.00 |
August | 2618.27 | 1443.46 | 1174.81 | 3138.29 | 260.86 | 0.00 | 0.00 | 744.00 |
September | 2179.58 | 1219.60 | 959.99 | 2446.94 | 453.29 | 0.00 | 0.00 | 720.00 |
October | 1895.35 | 1202.52 | 692.83 | 1833.18 | 818.07 | 0.00 | 0.00 | 744.00 |
November | 1481.39 | 870.92 | 610.46 | 1128.34 | 1206.51 | 0.00 | 0.00 | 720.00 |
December | 1200.55 | 730.74 | 469.80 | 761.19 | 1588.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2098.58 | 1212.67 | 885.90 | 2122.29 | 838.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1200.55 | 709.86 | 469.80 | 761.19 | 231.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2858.88 | 1760.96 | 1196.12 | 3414.45 | 1588.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5085.25 | 3957.45 | 1127.80 | 5171.36 | 2338.27 | 0.00 | 0.00 | 744.00 |
February | 4977.93 | 3637.07 | 1340.86 | 4902.74 | 2177.37 | 0.00 | 0.00 | 672.00 |
March | 3666.17 | 2216.55 | 1449.63 | 3161.32 | 1751.68 | 0.00 | 0.00 | 744.00 |
April | 2858.24 | 1172.86 | 1685.38 | 2056.82 | 1210.25 | 0.00 | 0.00 | 720.00 |
May | 1905.78 | 418.55 | 1487.23 | 1432.61 | 877.43 | 0.00 | 0.00 | 744.00 |
June | 1611.56 | 197.46 | 1414.10 | 1752.22 | 571.64 | 0.00 | 0.00 | 720.00 |
July | 1783.57 | 283.85 | 1499.72 | 2044.75 | 376.38 | 0.00 | 0.00 | 744.00 |
August | 2453.56 | 797.15 | 1656.41 | 2396.30 | 439.70 | 0.00 | 0.00 | 744.00 |
September | 3393.19 | 1891.99 | 1501.20 | 3304.32 | 774.60 | 0.00 | 0.00 | 720.00 |
October | 4644.93 | 3421.54 | 1223.39 | 4731.54 | 1369.29 | 0.00 | 0.00 | 744.00 |
November | 5173.87 | 3971.56 | 1202.31 | 5309.53 | 1904.98 | 0.00 | 0.00 | 720.00 |
December | 5516.69 | 4550.94 | 965.75 | 5756.51 | 2398.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 3581.43 | 2202.41 | 1379.02 | 3494.49 | 1344.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1611.56 | 197.46 | 965.75 | 1432.61 | 376.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 5516.69 | 4550.94 | 1685.38 | 5756.51 | 2398.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1309.51 | 746.81 | 562.69 | 964.45 | 1620.95 | 0.00 | 0.00 | 744.00 |
February | 1685.57 | 973.67 | 711.90 | 1400.24 | 1482.65 | 0.00 | 0.00 | 672.00 |
March | 1882.84 | 1002.35 | 880.49 | 1711.03 | 1172.14 | 0.00 | 0.00 | 744.00 |
April | 2403.00 | 1278.95 | 1124.04 | 2389.08 | 818.26 | 0.00 | 0.00 | 720.00 |
May | 2277.92 | 1173.58 | 1104.34 | 2406.34 | 599.71 | 0.00 | 0.00 | 744.00 |
June | 2441.79 | 1362.28 | 1079.51 | 2936.70 | 413.57 | 0.00 | 0.00 | 720.00 |
July | 2202.62 | 1077.81 | 1124.81 | 2737.45 | 270.17 | 0.00 | 0.00 | 744.00 |
August | 2250.89 | 1041.10 | 1209.79 | 2698.63 | 313.38 | 0.00 | 0.00 | 744.00 |
September | 2033.30 | 1070.94 | 962.36 | 2300.33 | 514.37 | 0.00 | 0.00 | 720.00 |
October | 1860.01 | 1156.06 | 703.95 | 1874.87 | 917.85 | 0.00 | 0.00 | 744.00 |
November | 1460.14 | 859.04 | 601.10 | 1179.87 | 1296.88 | 0.00 | 0.00 | 720.00 |
December | 1262.86 | 792.01 | 470.85 | 904.02 | 1685.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1922.71 | 1044.06 | 878.65 | 1960.51 | 922.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1262.86 | 746.81 | 470.85 | 904.02 | 270.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2441.79 | 1362.28 | 1209.79 | 2936.70 | 1685.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.59 | 0.00 | 687.59 | 116.60 | 2259.46 | 0.00 | 0.00 | 744.00 |
February | 859.37 | 0.00 | 859.37 | 247.81 | 2054.36 | 0.00 | 0.00 | 672.00 |
March | 1083.98 | 0.00 | 1083.98 | 547.76 | 1614.01 | 0.00 | 0.00 | 744.00 |
April | 1375.06 | 11.60 | 1363.46 | 894.99 | 1084.81 | 0.00 | 0.00 | 720.00 |
May | 1494.52 | 96.01 | 1398.51 | 1169.57 | 798.44 | 0.00 | 0.00 | 744.00 |
June | 1698.06 | 277.43 | 1420.63 | 1750.11 | 523.32 | 0.00 | 0.00 | 720.00 |
July | 1558.67 | 129.37 | 1429.29 | 1874.28 | 357.82 | 0.00 | 0.00 | 744.00 |
August | 1446.06 | 32.16 | 1413.90 | 1651.67 | 406.06 | 0.00 | 0.00 | 744.00 |
September | 1156.56 | 0.28 | 1156.28 | 1144.36 | 703.51 | 0.00 | 0.00 | 720.00 |
October | 863.04 | 0.00 | 863.04 | 514.92 | 1244.83 | 0.00 | 0.00 | 744.00 |
November | 732.92 | 0.00 | 732.92 | 167.04 | 1785.65 | 0.00 | 0.00 | 720.00 |
December | 585.24 | 0.00 | 585.24 | 35.34 | 2377.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1129.40 | 45.65 | 1083.75 | 846.16 | 1263.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 585.24 | 0.00 | 585.24 | 35.34 | 357.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1698.06 | 277.43 | 1429.29 | 1874.28 | 2377.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1269.57 | 709.86 | 559.71 | 862.63 | 1382.29 | 0.00 | 0.00 | 744.00 |
February | 1542.34 | 831.47 | 710.87 | 1177.55 | 1269.41 | 0.00 | 0.00 | 672.00 |
March | 2034.75 | 1156.77 | 877.98 | 1843.96 | 1005.00 | 0.00 | 0.00 | 744.00 |
April | 2779.99 | 1583.86 | 1196.12 | 2807.71 | 697.70 | 0.00 | 0.00 | 720.00 |
May | 2652.05 | 1511.21 | 1140.83 | 2820.76 | 533.18 | 0.00 | 0.00 | 744.00 |
June | 2858.88 | 1760.96 | 1097.92 | 3400.77 | 343.16 | 0.00 | 0.00 | 720.00 |
July | 2645.58 | 1512.68 | 1132.90 | 3261.95 | 236.72 | 0.00 | 0.00 | 744.00 |
August | 2618.27 | 1443.46 | 1174.81 | 3123.21 | 263.96 | 0.00 | 0.00 | 744.00 |
September | 2179.58 | 1219.60 | 959.99 | 2441.60 | 446.16 | 0.00 | 0.00 | 720.00 |
October | 1895.35 | 1202.52 | 692.83 | 1844.87 | 777.02 | 0.00 | 0.00 | 744.00 |
November | 1481.39 | 870.92 | 610.46 | 1163.40 | 1114.27 | 0.00 | 0.00 | 720.00 |
December | 1200.55 | 730.74 | 469.80 | 792.55 | 1457.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2098.58 | 1212.67 | 885.90 | 2132.67 | 791.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1200.55 | 709.86 | 469.80 | 792.55 | 236.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2858.88 | 1760.96 | 1196.12 | 3400.77 | 1457.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5085.25 | 3957.45 | 1127.80 | 5244.04 | 2155.29 | 0.00 | 0.00 | 744.00 |
February | 4977.93 | 3637.07 | 1340.86 | 4959.20 | 2017.49 | 0.00 | 0.00 | 672.00 |
March | 3666.17 | 2216.55 | 1449.63 | 3196.70 | 1642.04 | 0.00 | 0.00 | 744.00 |
April | 2858.24 | 1172.86 | 1685.38 | 2078.43 | 1146.03 | 0.00 | 0.00 | 720.00 |
May | 1905.78 | 418.55 | 1487.23 | 1438.74 | 845.58 | 0.00 | 0.00 | 744.00 |
June | 1611.56 | 197.46 | 1414.10 | 1745.02 | 560.40 | 0.00 | 0.00 | 720.00 |
July | 1783.57 | 283.85 | 1499.72 | 2029.37 | 378.33 | 0.00 | 0.00 | 744.00 |
August | 2453.56 | 797.15 | 1656.41 | 2385.08 | 436.63 | 0.00 | 0.00 | 744.00 |
September | 3393.19 | 1891.99 | 1501.20 | 3308.67 | 750.21 | 0.00 | 0.00 | 720.00 |
October | 4644.93 | 3421.54 | 1223.39 | 4762.59 | 1287.29 | 0.00 | 0.00 | 744.00 |
November | 5173.87 | 3971.56 | 1202.31 | 5372.43 | 1756.25 | 0.00 | 0.00 | 720.00 |
December | 5516.69 | 4550.94 | 965.75 | 5823.75 | 2195.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 3581.43 | 2202.41 | 1379.02 | 3521.32 | 1260.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1611.56 | 197.46 | 965.75 | 1438.74 | 378.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 5516.69 | 4550.94 | 1685.38 | 5823.75 | 2195.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1309.51 | 746.81 | 562.69 | 984.01 | 1513.22 | 0.00 | 0.00 | 744.00 |
February | 1685.57 | 973.67 | 711.90 | 1417.45 | 1392.95 | 0.00 | 0.00 | 672.00 |
March | 1882.84 | 1002.35 | 880.49 | 1724.69 | 1109.54 | 0.00 | 0.00 | 744.00 |
April | 2403.00 | 1278.95 | 1124.04 | 2394.86 | 781.33 | 0.00 | 0.00 | 720.00 |
May | 2277.92 | 1173.58 | 1104.34 | 2406.63 | 580.45 | 0.00 | 0.00 | 744.00 |
June | 2441.79 | 1362.28 | 1079.51 | 2930.36 | 405.92 | 0.00 | 0.00 | 720.00 |
July | 2202.62 | 1077.81 | 1124.81 | 2727.89 | 269.46 | 0.00 | 0.00 | 744.00 |
August | 2250.89 | 1041.10 | 1209.79 | 2691.38 | 310.15 | 0.00 | 0.00 | 744.00 |
September | 2033.30 | 1070.94 | 962.36 | 2300.24 | 500.41 | 0.00 | 0.00 | 720.00 |
October | 1860.01 | 1156.06 | 703.95 | 1882.44 | 869.45 | 0.00 | 0.00 | 744.00 |
November | 1460.14 | 859.04 | 601.10 | 1197.65 | 1204.78 | 0.00 | 0.00 | 720.00 |
December | 1262.86 | 792.01 | 470.85 | 917.95 | 1568.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1922.71 | 1044.06 | 878.65 | 1966.48 | 872.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1262.86 | 746.81 | 470.85 | 917.95 | 269.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2441.79 | 1362.28 | 1209.79 | 2930.36 | 1568.02 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368327E+09 | 0.00 | 0.368327E+09 | 27525665.63 | 0.144477E+10 |
February | 0.415797E+09 | 0.00 | 0.415797E+09 | 79663590.61 | 0.117302E+10 |
March | 0.580669E+09 | 0.00 | 0.580669E+09 | 0.250126E+09 | 0.100679E+10 |
April | 0.712833E+09 | 6012290.39 | 0.706821E+09 | 0.432657E+09 | 0.644064E+09 |
May | 0.800589E+09 | 51430801.15 | 0.749158E+09 | 0.609622E+09 | 0.469157E+09 |
June | 0.880278E+09 | 0.143821E+09 | 0.736457E+09 | 0.895766E+09 | 0.284879E+09 |
July | 0.834948E+09 | 69302911.44 | 0.765645E+09 | 0.999950E+09 | 0.190327E+09 |
August | 0.774626E+09 | 17225717.55 | 0.757400E+09 | 0.877364E+09 | 0.220544E+09 |
September | 0.599564E+09 | 147262.61 | 0.599417E+09 | 0.580540E+09 | 0.402132E+09 |
October | 0.462313E+09 | 0.00 | 0.462313E+09 | 0.246144E+09 | 0.781221E+09 |
November | 0.379948E+09 | 0.00 | 0.379948E+09 | 53945925.56 | 0.113074E+10 |
December | 0.313502E+09 | 0.00 | 0.313502E+09 | 3738011.89 | 0.157117E+10 |
Annual Sum or Average | 0.712339E+10 | 0.287940E+09 | 0.683545E+10 | 0.505704E+10 | 0.931882E+10 |
Minimum of Months | 0.313502E+09 | 0.00 | 0.313502E+09 | 3738011.89 | 0.190327E+09 |
Maximum of Months | 0.880278E+09 | 0.143821E+09 | 0.765645E+09 | 0.999950E+09 | 0.157117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368322E+09 | 0.00 | 0.368322E+09 | 27523958.04 | 0.144477E+10 |
February | 0.415792E+09 | 0.00 | 0.415792E+09 | 79660855.02 | 0.117302E+10 |
March | 0.580662E+09 | 0.00 | 0.580662E+09 | 0.250120E+09 | 0.100679E+10 |
April | 0.712825E+09 | 6012158.21 | 0.706812E+09 | 0.432650E+09 | 0.644062E+09 |
May | 0.800579E+09 | 51429670.51 | 0.749149E+09 | 0.609614E+09 | 0.469156E+09 |
June | 0.880266E+09 | 0.143818E+09 | 0.736448E+09 | 0.895757E+09 | 0.284877E+09 |
July | 0.834937E+09 | 69301387.90 | 0.765636E+09 | 0.999941E+09 | 0.190326E+09 |
August | 0.774616E+09 | 17225338.86 | 0.757391E+09 | 0.877355E+09 | 0.220543E+09 |
September | 0.599557E+09 | 147259.37 | 0.599410E+09 | 0.580534E+09 | 0.402130E+09 |
October | 0.462308E+09 | 0.00 | 0.462308E+09 | 0.246140E+09 | 0.781219E+09 |
November | 0.379944E+09 | 0.00 | 0.379944E+09 | 53943604.87 | 0.113074E+10 |
December | 0.313498E+09 | 0.00 | 0.313498E+09 | 3737674.70 | 0.157117E+10 |
Annual Sum or Average | 0.712331E+10 | 0.287934E+09 | 0.683537E+10 | 0.505698E+10 | 0.931881E+10 |
Minimum of Months | 0.313498E+09 | 0.00 | 0.313498E+09 | 3737674.70 | 0.190326E+09 |
Maximum of Months | 0.880266E+09 | 0.143818E+09 | 0.765636E+09 | 0.999941E+09 | 0.157117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368324E+09 | 0.00 | 0.368324E+09 | 27524527.23 | 0.144477E+10 |
February | 0.415794E+09 | 0.00 | 0.415794E+09 | 79661766.88 | 0.117302E+10 |
March | 0.580664E+09 | 0.00 | 0.580664E+09 | 0.250122E+09 | 0.100679E+10 |
April | 0.712827E+09 | 6012202.27 | 0.706815E+09 | 0.432652E+09 | 0.644063E+09 |
May | 0.800582E+09 | 51430047.39 | 0.749152E+09 | 0.609617E+09 | 0.469156E+09 |
June | 0.880270E+09 | 0.143819E+09 | 0.736451E+09 | 0.895760E+09 | 0.284878E+09 |
July | 0.834941E+09 | 69301895.75 | 0.765639E+09 | 0.999944E+09 | 0.190326E+09 |
August | 0.774620E+09 | 17225465.09 | 0.757394E+09 | 0.877358E+09 | 0.220543E+09 |
September | 0.599559E+09 | 147260.45 | 0.599412E+09 | 0.580536E+09 | 0.402130E+09 |
October | 0.462310E+09 | 0.00 | 0.462310E+09 | 0.246141E+09 | 0.781220E+09 |
November | 0.379945E+09 | 0.00 | 0.379945E+09 | 53944378.43 | 0.113074E+10 |
December | 0.313499E+09 | 0.00 | 0.313499E+09 | 3737787.10 | 0.157117E+10 |
Annual Sum or Average | 0.712334E+10 | 0.287936E+09 | 0.683540E+10 | 0.505700E+10 | 0.931881E+10 |
Minimum of Months | 0.313499E+09 | 0.00 | 0.313499E+09 | 3737787.10 | 0.190326E+09 |
Maximum of Months | 0.880270E+09 | 0.143819E+09 | 0.765639E+09 | 0.999944E+09 | 0.157117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368322E+09 | 0.00 | 0.368322E+09 | 27523958.04 | 0.144477E+10 |
February | 0.415792E+09 | 0.00 | 0.415792E+09 | 79660855.02 | 0.117302E+10 |
March | 0.580662E+09 | 0.00 | 0.580662E+09 | 0.250120E+09 | 0.100679E+10 |
April | 0.712825E+09 | 6012158.21 | 0.706812E+09 | 0.432650E+09 | 0.644062E+09 |
May | 0.800579E+09 | 51429670.51 | 0.749149E+09 | 0.609614E+09 | 0.469156E+09 |
June | 0.880266E+09 | 0.143818E+09 | 0.736448E+09 | 0.895757E+09 | 0.284877E+09 |
July | 0.834937E+09 | 69301387.90 | 0.765636E+09 | 0.999941E+09 | 0.190326E+09 |
August | 0.774616E+09 | 17225338.86 | 0.757391E+09 | 0.877355E+09 | 0.220543E+09 |
September | 0.599557E+09 | 147259.37 | 0.599410E+09 | 0.580534E+09 | 0.402130E+09 |
October | 0.462308E+09 | 0.00 | 0.462308E+09 | 0.246140E+09 | 0.781219E+09 |
November | 0.379944E+09 | 0.00 | 0.379944E+09 | 53943604.87 | 0.113074E+10 |
December | 0.313498E+09 | 0.00 | 0.313498E+09 | 3737674.70 | 0.157117E+10 |
Annual Sum or Average | 0.712331E+10 | 0.287934E+09 | 0.683537E+10 | 0.505698E+10 | 0.931881E+10 |
Minimum of Months | 0.313498E+09 | 0.00 | 0.313498E+09 | 3737674.70 | 0.190326E+09 |
Maximum of Months | 0.880266E+09 | 0.143818E+09 | 0.765636E+09 | 0.999941E+09 | 0.157117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368308E+09 | 0.00 | 0.368308E+09 | 27523133.29 | 0.144471E+10 |
February | 0.415776E+09 | 0.00 | 0.415776E+09 | 79658100.25 | 0.117297E+10 |
March | 0.580640E+09 | 0.00 | 0.580640E+09 | 0.250111E+09 | 0.100675E+10 |
April | 0.712797E+09 | 6011937.93 | 0.706785E+09 | 0.432633E+09 | 0.644037E+09 |
May | 0.800548E+09 | 51427786.10 | 0.749120E+09 | 0.609591E+09 | 0.469137E+09 |
June | 0.880233E+09 | 0.143813E+09 | 0.736420E+09 | 0.895722E+09 | 0.284866E+09 |
July | 0.834906E+09 | 69298848.66 | 0.765607E+09 | 0.999902E+09 | 0.190318E+09 |
August | 0.774587E+09 | 17224707.71 | 0.757362E+09 | 0.877322E+09 | 0.220534E+09 |
September | 0.599534E+09 | 147253.97 | 0.599387E+09 | 0.580512E+09 | 0.402114E+09 |
October | 0.462290E+09 | 0.00 | 0.462290E+09 | 0.246131E+09 | 0.781188E+09 |
November | 0.379929E+09 | 0.00 | 0.379929E+09 | 53941817.47 | 0.113070E+10 |
December | 0.313486E+09 | 0.00 | 0.313486E+09 | 3737580.25 | 0.157111E+10 |
Annual Sum or Average | 0.712303E+10 | 0.287923E+09 | 0.683511E+10 | 0.505679E+10 | 0.931843E+10 |
Minimum of Months | 0.313486E+09 | 0.00 | 0.313486E+09 | 3737580.25 | 0.190318E+09 |
Maximum of Months | 0.880233E+09 | 0.143813E+09 | 0.765607E+09 | 0.999902E+09 | 0.157111E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113348E+10 | 0.633766E+09 | 0.499717E+09 | 0.709302E+09 | 0.142069E+10 |
February | 0.124376E+10 | 0.670507E+09 | 0.573250E+09 | 0.901734E+09 | 0.116169E+10 |
March | 0.181664E+10 | 0.103278E+10 | 0.783867E+09 | 0.161792E+10 | 0.995731E+09 |
April | 0.240193E+10 | 0.136847E+10 | 0.103346E+10 | 0.242819E+10 | 0.639448E+09 |
May | 0.236777E+10 | 0.134922E+10 | 0.101855E+10 | 0.252872E+10 | 0.503789E+09 |
June | 0.247010E+10 | 0.152149E+10 | 0.948614E+09 | 0.295777E+10 | 0.295891E+09 |
July | 0.236199E+10 | 0.135053E+10 | 0.101146E+10 | 0.294045E+10 | 0.185022E+09 |
August | 0.233761E+10 | 0.128873E+10 | 0.104888E+10 | 0.281620E+10 | 0.203348E+09 |
September | 0.188318E+10 | 0.105374E+10 | 0.829436E+09 | 0.211433E+10 | 0.408345E+09 |
October | 0.169218E+10 | 0.107362E+10 | 0.618565E+09 | 0.163029E+10 | 0.768256E+09 |
November | 0.127993E+10 | 0.752486E+09 | 0.527446E+09 | 0.961201E+09 | 0.110976E+10 |
December | 0.107186E+10 | 0.652412E+09 | 0.419446E+09 | 0.663383E+09 | 0.152132E+10 |
Annual Sum or Average | 0.220605E+11 | 0.127478E+11 | 0.931270E+10 | 0.222695E+11 | 0.921329E+10 |
Minimum of Months | 0.107186E+10 | 0.633766E+09 | 0.419446E+09 | 0.663383E+09 | 0.185022E+09 |
Maximum of Months | 0.247010E+10 | 0.152149E+10 | 0.104888E+10 | 0.295777E+10 | 0.152132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113348E+10 | 0.633766E+09 | 0.499717E+09 | 0.709302E+09 | 0.142069E+10 |
February | 0.124376E+10 | 0.670507E+09 | 0.573250E+09 | 0.901734E+09 | 0.116169E+10 |
March | 0.181664E+10 | 0.103278E+10 | 0.783867E+09 | 0.161792E+10 | 0.995731E+09 |
April | 0.240193E+10 | 0.136847E+10 | 0.103346E+10 | 0.242819E+10 | 0.639448E+09 |
May | 0.236777E+10 | 0.134922E+10 | 0.101855E+10 | 0.252872E+10 | 0.503789E+09 |
June | 0.247010E+10 | 0.152149E+10 | 0.948614E+09 | 0.295777E+10 | 0.295891E+09 |
July | 0.236199E+10 | 0.135053E+10 | 0.101146E+10 | 0.294045E+10 | 0.185022E+09 |
August | 0.233761E+10 | 0.128873E+10 | 0.104888E+10 | 0.281620E+10 | 0.203348E+09 |
September | 0.188318E+10 | 0.105374E+10 | 0.829436E+09 | 0.211433E+10 | 0.408345E+09 |
October | 0.169218E+10 | 0.107362E+10 | 0.618565E+09 | 0.163029E+10 | 0.768256E+09 |
November | 0.127993E+10 | 0.752486E+09 | 0.527446E+09 | 0.961201E+09 | 0.110976E+10 |
December | 0.107186E+10 | 0.652412E+09 | 0.419446E+09 | 0.663383E+09 | 0.152132E+10 |
Annual Sum or Average | 0.220605E+11 | 0.127478E+11 | 0.931270E+10 | 0.222695E+11 | 0.921329E+10 |
Minimum of Months | 0.107186E+10 | 0.633766E+09 | 0.419446E+09 | 0.663383E+09 | 0.185022E+09 |
Maximum of Months | 0.247010E+10 | 0.152149E+10 | 0.104888E+10 | 0.295777E+10 | 0.152132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113346E+10 | 0.633755E+09 | 0.499708E+09 | 0.709290E+09 | 0.142066E+10 |
February | 0.124374E+10 | 0.670495E+09 | 0.573240E+09 | 0.901717E+09 | 0.116167E+10 |
March | 0.181661E+10 | 0.103276E+10 | 0.783852E+09 | 0.161789E+10 | 0.995713E+09 |
April | 0.240189E+10 | 0.136845E+10 | 0.103344E+10 | 0.242815E+10 | 0.639437E+09 |
May | 0.236773E+10 | 0.134920E+10 | 0.101853E+10 | 0.252867E+10 | 0.503779E+09 |
June | 0.247006E+10 | 0.152146E+10 | 0.948597E+09 | 0.295772E+10 | 0.295885E+09 |
July | 0.236195E+10 | 0.135051E+10 | 0.101144E+10 | 0.294040E+10 | 0.185018E+09 |
August | 0.233757E+10 | 0.128871E+10 | 0.104886E+10 | 0.281615E+10 | 0.203344E+09 |
September | 0.188314E+10 | 0.105372E+10 | 0.829420E+09 | 0.211429E+10 | 0.408337E+09 |
October | 0.169215E+10 | 0.107360E+10 | 0.618554E+09 | 0.163026E+10 | 0.768242E+09 |
November | 0.127991E+10 | 0.752472E+09 | 0.527437E+09 | 0.961184E+09 | 0.110974E+10 |
December | 0.107184E+10 | 0.652400E+09 | 0.419438E+09 | 0.663371E+09 | 0.152129E+10 |
Annual Sum or Average | 0.220601E+11 | 0.127475E+11 | 0.931253E+10 | 0.222691E+11 | 0.921312E+10 |
Minimum of Months | 0.107184E+10 | 0.633755E+09 | 0.419438E+09 | 0.663371E+09 | 0.185018E+09 |
Maximum of Months | 0.247006E+10 | 0.152146E+10 | 0.104886E+10 | 0.295772E+10 | 0.152129E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272402E+10 | 0.211988E+10 | 0.604133E+09 | 0.279184E+10 | 0.125433E+10 |
February | 0.240848E+10 | 0.175972E+10 | 0.648755E+09 | 0.238793E+10 | 0.106182E+10 |
March | 0.196386E+10 | 0.118733E+10 | 0.776529E+09 | 0.169590E+10 | 0.959014E+09 |
April | 0.148169E+10 | 0.607996E+09 | 0.873695E+09 | 0.105663E+10 | 0.647327E+09 |
May | 0.102088E+10 | 0.224204E+09 | 0.796674E+09 | 0.757911E+09 | 0.484934E+09 |
June | 0.835428E+09 | 0.102360E+09 | 0.733069E+09 | 0.895141E+09 | 0.303182E+09 |
July | 0.955417E+09 | 0.152051E+09 | 0.803366E+09 | 0.108314E+10 | 0.198912E+09 |
August | 0.131431E+10 | 0.427008E+09 | 0.887301E+09 | 0.127168E+10 | 0.231284E+09 |
September | 0.175900E+10 | 0.980786E+09 | 0.778215E+09 | 0.171416E+10 | 0.408055E+09 |
October | 0.248815E+10 | 0.183281E+10 | 0.655341E+09 | 0.254879E+10 | 0.740088E+09 |
November | 0.268208E+10 | 0.205881E+10 | 0.623270E+09 | 0.277013E+10 | 0.996930E+09 |
December | 0.295512E+10 | 0.243780E+10 | 0.517327E+09 | 0.310032E+10 | 0.130552E+10 |
Annual Sum or Average | 0.225884E+11 | 0.138908E+11 | 0.869767E+10 | 0.220736E+11 | 0.859140E+10 |
Minimum of Months | 0.835428E+09 | 0.102360E+09 | 0.517327E+09 | 0.757911E+09 | 0.198912E+09 |
Maximum of Months | 0.295512E+10 | 0.243780E+10 | 0.887301E+09 | 0.310032E+10 | 0.130552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272400E+10 | 0.211987E+10 | 0.604130E+09 | 0.279182E+10 | 0.125433E+10 |
February | 0.240846E+10 | 0.175971E+10 | 0.648752E+09 | 0.238791E+10 | 0.106182E+10 |
March | 0.196385E+10 | 0.118733E+10 | 0.776525E+09 | 0.169589E+10 | 0.959014E+09 |
April | 0.148168E+10 | 0.607992E+09 | 0.873691E+09 | 0.105663E+10 | 0.647327E+09 |
May | 0.102087E+10 | 0.224202E+09 | 0.796671E+09 | 0.757907E+09 | 0.484934E+09 |
June | 0.835425E+09 | 0.102359E+09 | 0.733066E+09 | 0.895138E+09 | 0.303182E+09 |
July | 0.955412E+09 | 0.152049E+09 | 0.803363E+09 | 0.108314E+10 | 0.198912E+09 |
August | 0.131430E+10 | 0.427005E+09 | 0.887297E+09 | 0.127167E+10 | 0.231283E+09 |
September | 0.175899E+10 | 0.980778E+09 | 0.778211E+09 | 0.171415E+10 | 0.408055E+09 |
October | 0.248814E+10 | 0.183280E+10 | 0.655338E+09 | 0.254878E+10 | 0.740087E+09 |
November | 0.268206E+10 | 0.205880E+10 | 0.623266E+09 | 0.277011E+10 | 0.996930E+09 |
December | 0.295510E+10 | 0.243778E+10 | 0.517324E+09 | 0.310029E+10 | 0.130552E+10 |
Annual Sum or Average | 0.225883E+11 | 0.138907E+11 | 0.869763E+10 | 0.220734E+11 | 0.859140E+10 |
Minimum of Months | 0.835425E+09 | 0.102359E+09 | 0.517324E+09 | 0.757907E+09 | 0.198912E+09 |
Maximum of Months | 0.295510E+10 | 0.243778E+10 | 0.887297E+09 | 0.310029E+10 | 0.130552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272402E+10 | 0.211988E+10 | 0.604133E+09 | 0.279184E+10 | 0.125433E+10 |
February | 0.240848E+10 | 0.175972E+10 | 0.648755E+09 | 0.238793E+10 | 0.106182E+10 |
March | 0.196386E+10 | 0.118733E+10 | 0.776529E+09 | 0.169590E+10 | 0.959014E+09 |
April | 0.148169E+10 | 0.607996E+09 | 0.873695E+09 | 0.105663E+10 | 0.647327E+09 |
May | 0.102088E+10 | 0.224204E+09 | 0.796674E+09 | 0.757911E+09 | 0.484934E+09 |
June | 0.835428E+09 | 0.102360E+09 | 0.733069E+09 | 0.895141E+09 | 0.303182E+09 |
July | 0.955417E+09 | 0.152051E+09 | 0.803366E+09 | 0.108314E+10 | 0.198912E+09 |
August | 0.131431E+10 | 0.427008E+09 | 0.887301E+09 | 0.127168E+10 | 0.231284E+09 |
September | 0.175900E+10 | 0.980786E+09 | 0.778215E+09 | 0.171416E+10 | 0.408055E+09 |
October | 0.248815E+10 | 0.183281E+10 | 0.655341E+09 | 0.254879E+10 | 0.740088E+09 |
November | 0.268208E+10 | 0.205881E+10 | 0.623270E+09 | 0.277013E+10 | 0.996930E+09 |
December | 0.295512E+10 | 0.243780E+10 | 0.517327E+09 | 0.310032E+10 | 0.130552E+10 |
Annual Sum or Average | 0.225884E+11 | 0.138908E+11 | 0.869767E+10 | 0.220736E+11 | 0.859140E+10 |
Minimum of Months | 0.835428E+09 | 0.102360E+09 | 0.517327E+09 | 0.757911E+09 | 0.198912E+09 |
Maximum of Months | 0.295512E+10 | 0.243780E+10 | 0.887301E+09 | 0.310032E+10 | 0.130552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272400E+10 | 0.211987E+10 | 0.604130E+09 | 0.279182E+10 | 0.125433E+10 |
February | 0.240846E+10 | 0.175971E+10 | 0.648752E+09 | 0.238791E+10 | 0.106182E+10 |
March | 0.196385E+10 | 0.118733E+10 | 0.776525E+09 | 0.169589E+10 | 0.959014E+09 |
April | 0.148168E+10 | 0.607992E+09 | 0.873691E+09 | 0.105663E+10 | 0.647327E+09 |
May | 0.102087E+10 | 0.224202E+09 | 0.796671E+09 | 0.757907E+09 | 0.484934E+09 |
June | 0.835425E+09 | 0.102359E+09 | 0.733066E+09 | 0.895138E+09 | 0.303182E+09 |
July | 0.955412E+09 | 0.152049E+09 | 0.803363E+09 | 0.108314E+10 | 0.198912E+09 |
August | 0.131430E+10 | 0.427005E+09 | 0.887297E+09 | 0.127167E+10 | 0.231283E+09 |
September | 0.175899E+10 | 0.980778E+09 | 0.778211E+09 | 0.171415E+10 | 0.408055E+09 |
October | 0.248814E+10 | 0.183280E+10 | 0.655338E+09 | 0.254878E+10 | 0.740087E+09 |
November | 0.268206E+10 | 0.205880E+10 | 0.623266E+09 | 0.277011E+10 | 0.996930E+09 |
December | 0.295510E+10 | 0.243778E+10 | 0.517324E+09 | 0.310029E+10 | 0.130552E+10 |
Annual Sum or Average | 0.225883E+11 | 0.138907E+11 | 0.869763E+10 | 0.220734E+11 | 0.859140E+10 |
Minimum of Months | 0.835425E+09 | 0.102359E+09 | 0.517324E+09 | 0.757907E+09 | 0.198912E+09 |
Maximum of Months | 0.295510E+10 | 0.243778E+10 | 0.887297E+09 | 0.310029E+10 | 0.130552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272390E+10 | 0.211979E+10 | 0.604107E+09 | 0.279172E+10 | 0.125428E+10 |
February | 0.240837E+10 | 0.175965E+10 | 0.648727E+09 | 0.238783E+10 | 0.106178E+10 |
March | 0.196378E+10 | 0.118728E+10 | 0.776496E+09 | 0.169582E+10 | 0.958976E+09 |
April | 0.148163E+10 | 0.607970E+09 | 0.873658E+09 | 0.105659E+10 | 0.647301E+09 |
May | 0.102083E+10 | 0.224194E+09 | 0.796641E+09 | 0.757879E+09 | 0.484915E+09 |
June | 0.835393E+09 | 0.102355E+09 | 0.733038E+09 | 0.895103E+09 | 0.303170E+09 |
July | 0.955376E+09 | 0.152044E+09 | 0.803332E+09 | 0.108309E+10 | 0.198904E+09 |
August | 0.131425E+10 | 0.426990E+09 | 0.887263E+09 | 0.127162E+10 | 0.231274E+09 |
September | 0.175892E+10 | 0.980743E+09 | 0.778182E+09 | 0.171409E+10 | 0.408039E+09 |
October | 0.248804E+10 | 0.183273E+10 | 0.655313E+09 | 0.254868E+10 | 0.740057E+09 |
November | 0.268196E+10 | 0.205872E+10 | 0.623243E+09 | 0.277001E+10 | 0.996890E+09 |
December | 0.295499E+10 | 0.243769E+10 | 0.517305E+09 | 0.310018E+10 | 0.130547E+10 |
Annual Sum or Average | 0.225875E+11 | 0.138902E+11 | 0.869730E+10 | 0.220726E+11 | 0.859105E+10 |
Minimum of Months | 0.835393E+09 | 0.102355E+09 | 0.517305E+09 | 0.757879E+09 | 0.198904E+09 |
Maximum of Months | 0.295499E+10 | 0.243769E+10 | 0.887263E+09 | 0.310018E+10 | 0.130547E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116914E+10 | 0.666763E+09 | 0.502377E+09 | 0.835530E+09 | 0.156455E+10 |
February | 0.135926E+10 | 0.785179E+09 | 0.574080E+09 | 0.109642E+10 | 0.131841E+10 |
March | 0.168102E+10 | 0.894910E+09 | 0.786108E+09 | 0.147887E+10 | 0.117918E+10 |
April | 0.207621E+10 | 0.110503E+10 | 0.971183E+09 | 0.201152E+10 | 0.804386E+09 |
May | 0.203375E+10 | 0.104779E+10 | 0.985963E+09 | 0.212208E+10 | 0.578184E+09 |
June | 0.210973E+10 | 0.117702E+10 | 0.932710E+09 | 0.250445E+10 | 0.388188E+09 |
July | 0.196652E+10 | 0.962276E+09 | 0.100424E+10 | 0.240136E+10 | 0.266004E+09 |
August | 0.200961E+10 | 0.929507E+09 | 0.108011E+10 | 0.235508E+10 | 0.324068E+09 |
September | 0.175679E+10 | 0.925298E+09 | 0.831487E+09 | 0.196228E+10 | 0.486142E+09 |
October | 0.166064E+10 | 0.103214E+10 | 0.628497E+09 | 0.163895E+10 | 0.917321E+09 |
November | 0.126157E+10 | 0.742221E+09 | 0.519354E+09 | 0.980504E+09 | 0.128348E+10 |
December | 0.112749E+10 | 0.707111E+09 | 0.420383E+09 | 0.770301E+09 | 0.176117E+10 |
Annual Sum or Average | 0.202117E+11 | 0.109752E+11 | 0.923649E+10 | 0.201573E+11 | 0.108711E+11 |
Minimum of Months | 0.112749E+10 | 0.666763E+09 | 0.420383E+09 | 0.770301E+09 | 0.266004E+09 |
Maximum of Months | 0.210973E+10 | 0.117702E+10 | 0.108011E+10 | 0.250445E+10 | 0.176117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116914E+10 | 0.666763E+09 | 0.502377E+09 | 0.835530E+09 | 0.156455E+10 |
February | 0.135926E+10 | 0.785179E+09 | 0.574080E+09 | 0.109642E+10 | 0.131841E+10 |
March | 0.168102E+10 | 0.894910E+09 | 0.786108E+09 | 0.147887E+10 | 0.117918E+10 |
April | 0.207621E+10 | 0.110503E+10 | 0.971183E+09 | 0.201152E+10 | 0.804386E+09 |
May | 0.203375E+10 | 0.104779E+10 | 0.985963E+09 | 0.212208E+10 | 0.578184E+09 |
June | 0.210973E+10 | 0.117702E+10 | 0.932710E+09 | 0.250445E+10 | 0.388188E+09 |
July | 0.196652E+10 | 0.962276E+09 | 0.100424E+10 | 0.240136E+10 | 0.266004E+09 |
August | 0.200961E+10 | 0.929507E+09 | 0.108011E+10 | 0.235508E+10 | 0.324068E+09 |
September | 0.175679E+10 | 0.925298E+09 | 0.831487E+09 | 0.196228E+10 | 0.486142E+09 |
October | 0.166064E+10 | 0.103214E+10 | 0.628497E+09 | 0.163895E+10 | 0.917321E+09 |
November | 0.126157E+10 | 0.742221E+09 | 0.519354E+09 | 0.980504E+09 | 0.128348E+10 |
December | 0.112749E+10 | 0.707111E+09 | 0.420383E+09 | 0.770301E+09 | 0.176117E+10 |
Annual Sum or Average | 0.202117E+11 | 0.109752E+11 | 0.923649E+10 | 0.201573E+11 | 0.108711E+11 |
Minimum of Months | 0.112749E+10 | 0.666763E+09 | 0.420383E+09 | 0.770301E+09 | 0.266004E+09 |
Maximum of Months | 0.210973E+10 | 0.117702E+10 | 0.108011E+10 | 0.250445E+10 | 0.176117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116912E+10 | 0.666750E+09 | 0.502368E+09 | 0.835515E+09 | 0.156452E+10 |
February | 0.135923E+10 | 0.785164E+09 | 0.574069E+09 | 0.109640E+10 | 0.131838E+10 |
March | 0.168099E+10 | 0.894893E+09 | 0.786093E+09 | 0.147884E+10 | 0.117916E+10 |
April | 0.207617E+10 | 0.110501E+10 | 0.971165E+09 | 0.201148E+10 | 0.804371E+09 |
May | 0.203371E+10 | 0.104777E+10 | 0.985945E+09 | 0.212204E+10 | 0.578174E+09 |
June | 0.210969E+10 | 0.117700E+10 | 0.932693E+09 | 0.250440E+10 | 0.388181E+09 |
July | 0.196648E+10 | 0.962259E+09 | 0.100422E+10 | 0.240132E+10 | 0.266000E+09 |
August | 0.200958E+10 | 0.929490E+09 | 0.108009E+10 | 0.235504E+10 | 0.324062E+09 |
September | 0.175675E+10 | 0.925281E+09 | 0.831472E+09 | 0.196224E+10 | 0.486133E+09 |
October | 0.166061E+10 | 0.103212E+10 | 0.628485E+09 | 0.163892E+10 | 0.917304E+09 |
November | 0.126155E+10 | 0.742207E+09 | 0.519344E+09 | 0.980486E+09 | 0.128346E+10 |
December | 0.112747E+10 | 0.707098E+09 | 0.420375E+09 | 0.770287E+09 | 0.176113E+10 |
Annual Sum or Average | 0.202114E+11 | 0.109750E+11 | 0.923632E+10 | 0.201570E+11 | 0.108709E+11 |
Minimum of Months | 0.112747E+10 | 0.666750E+09 | 0.420375E+09 | 0.770287E+09 | 0.266000E+09 |
Maximum of Months | 0.210969E+10 | 0.117700E+10 | 0.108009E+10 | 0.250440E+10 | 0.176113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184163E+10 | 0.00 | 0.184163E+10 | 0.217011E+09 | 0.663561E+10 |
February | 0.207898E+10 | 0.00 | 0.207898E+10 | 0.500494E+09 | 0.540127E+10 |
March | 0.290334E+10 | 0.00 | 0.290334E+10 | 0.136629E+10 | 0.465954E+10 |
April | 0.356416E+10 | 30061643.51 | 0.353410E+10 | 0.226820E+10 | 0.299024E+10 |
May | 0.400294E+10 | 0.257156E+09 | 0.374578E+10 | 0.311842E+10 | 0.222318E+10 |
June | 0.440138E+10 | 0.719110E+09 | 0.368227E+10 | 0.455509E+10 | 0.137925E+10 |
July | 0.417473E+10 | 0.346517E+09 | 0.382822E+10 | 0.506755E+10 | 0.952170E+09 |
August | 0.387312E+10 | 86129136.60 | 0.378699E+10 | 0.446211E+10 | 0.109534E+10 |
September | 0.299781E+10 | 736317.73 | 0.299708E+10 | 0.296207E+10 | 0.189416E+10 |
October | 0.231156E+10 | 0.00 | 0.231156E+10 | 0.131763E+10 | 0.360635E+10 |
November | 0.189974E+10 | 0.00 | 0.189974E+10 | 0.341188E+09 | 0.513154E+10 |
December | 0.156751E+10 | 0.00 | 0.156751E+10 | 49978553.87 | 0.701872E+10 |
Annual Sum or Average | 0.356169E+11 | 0.143971E+10 | 0.341772E+11 | 0.262260E+11 | 0.429874E+11 |
Minimum of Months | 0.156751E+10 | 0.00 | 0.156751E+10 | 49978553.87 | 0.952170E+09 |
Maximum of Months | 0.440138E+10 | 0.719110E+09 | 0.382822E+10 | 0.506755E+10 | 0.701872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340042E+10 | 0.190128E+10 | 0.149914E+10 | 0.219650E+10 | 0.400217E+10 |
February | 0.373124E+10 | 0.201150E+10 | 0.171973E+10 | 0.276047E+10 | 0.329113E+10 |
March | 0.544988E+10 | 0.309830E+10 | 0.235158E+10 | 0.488243E+10 | 0.284683E+10 |
April | 0.720573E+10 | 0.410538E+10 | 0.310035E+10 | 0.726426E+10 | 0.188098E+10 |
May | 0.710324E+10 | 0.404763E+10 | 0.305561E+10 | 0.756984E+10 | 0.145920E+10 |
June | 0.741023E+10 | 0.456441E+10 | 0.284581E+10 | 0.885026E+10 | 0.892269E+09 |
July | 0.708591E+10 | 0.405156E+10 | 0.303435E+10 | 0.878333E+10 | 0.621143E+09 |
August | 0.701277E+10 | 0.386615E+10 | 0.314662E+10 | 0.840558E+10 | 0.698699E+09 |
September | 0.564948E+10 | 0.316120E+10 | 0.248828E+10 | 0.634247E+10 | 0.117492E+10 |
October | 0.507650E+10 | 0.322082E+10 | 0.185568E+10 | 0.490998E+10 | 0.219111E+10 |
November | 0.383976E+10 | 0.225743E+10 | 0.158232E+10 | 0.292466E+10 | 0.312727E+10 |
December | 0.321554E+10 | 0.195722E+10 | 0.125832E+10 | 0.203876E+10 | 0.425347E+10 |
Annual Sum or Average | 0.661807E+11 | 0.382429E+11 | 0.279378E+11 | 0.669285E+11 | 0.264392E+11 |
Minimum of Months | 0.321554E+10 | 0.190128E+10 | 0.125832E+10 | 0.203876E+10 | 0.621143E+09 |
Maximum of Months | 0.741023E+10 | 0.456441E+10 | 0.314662E+10 | 0.885026E+10 | 0.425347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136203E+11 | 0.105996E+11 | 0.302070E+10 | 0.138510E+11 | 0.626283E+10 |
February | 0.120426E+11 | 0.879880E+10 | 0.324381E+10 | 0.118607E+11 | 0.526748E+10 |
March | 0.981948E+10 | 0.593680E+10 | 0.388269E+10 | 0.846727E+10 | 0.469171E+10 |
April | 0.740856E+10 | 0.304005E+10 | 0.436851E+10 | 0.533127E+10 | 0.313697E+10 |
May | 0.510444E+10 | 0.112104E+10 | 0.398340E+10 | 0.383710E+10 | 0.235011E+10 |
June | 0.417717E+10 | 0.511811E+09 | 0.366536E+10 | 0.454175E+10 | 0.148169E+10 |
July | 0.477712E+10 | 0.760269E+09 | 0.401686E+10 | 0.547667E+10 | 0.100810E+10 |
August | 0.657163E+10 | 0.213509E+10 | 0.443654E+10 | 0.641824E+10 | 0.117769E+10 |
September | 0.879514E+10 | 0.490403E+10 | 0.389111E+10 | 0.856481E+10 | 0.200778E+10 |
October | 0.124410E+11 | 0.916425E+10 | 0.327674E+10 | 0.126730E+11 | 0.366750E+10 |
November | 0.134107E+11 | 0.102943E+11 | 0.311639E+10 | 0.137623E+11 | 0.493771E+10 |
December | 0.147759E+11 | 0.121892E+11 | 0.258667E+10 | 0.154182E+11 | 0.642408E+10 |
Annual Sum or Average | 0.112944E+12 | 0.694553E+11 | 0.434888E+11 | 0.110202E+12 | 0.424137E+11 |
Minimum of Months | 0.417717E+10 | 0.511811E+09 | 0.258667E+10 | 0.383710E+10 | 0.100810E+10 |
Maximum of Months | 0.147759E+11 | 0.121892E+11 | 0.443654E+10 | 0.154182E+11 | 0.642408E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350738E+10 | 0.200027E+10 | 0.150712E+10 | 0.258317E+10 | 0.434155E+10 |
February | 0.407773E+10 | 0.235551E+10 | 0.172222E+10 | 0.338747E+10 | 0.358682E+10 |
March | 0.504300E+10 | 0.268470E+10 | 0.235830E+10 | 0.458283E+10 | 0.313945E+10 |
April | 0.622856E+10 | 0.331505E+10 | 0.291352E+10 | 0.619249E+10 | 0.212093E+10 |
May | 0.610119E+10 | 0.314333E+10 | 0.295786E+10 | 0.644513E+10 | 0.160625E+10 |
June | 0.632913E+10 | 0.353103E+10 | 0.279810E+10 | 0.761194E+10 | 0.107197E+10 |
July | 0.589949E+10 | 0.288680E+10 | 0.301269E+10 | 0.733200E+10 | 0.723612E+09 |
August | 0.602878E+10 | 0.278849E+10 | 0.324029E+10 | 0.722801E+10 | 0.839355E+09 |
September | 0.527030E+10 | 0.277587E+10 | 0.249443E+10 | 0.596245E+10 | 0.133326E+10 |
October | 0.498186E+10 | 0.309639E+10 | 0.188547E+10 | 0.502166E+10 | 0.245838E+10 |
November | 0.378469E+10 | 0.222664E+10 | 0.155805E+10 | 0.305822E+10 | 0.336152E+10 |
December | 0.338245E+10 | 0.212131E+10 | 0.126114E+10 | 0.242134E+10 | 0.451453E+10 |
Annual Sum or Average | 0.606346E+11 | 0.329254E+11 | 0.277092E+11 | 0.618267E+11 | 0.290976E+11 |
Minimum of Months | 0.338245E+10 | 0.200027E+10 | 0.126114E+10 | 0.242134E+10 | 0.723612E+09 |
Maximum of Months | 0.632913E+10 | 0.353103E+10 | 0.324029E+10 | 0.761194E+10 | 0.451453E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184163E+10 | 0.00 | 0.184163E+10 | 0.312310E+09 | 0.605173E+10 |
February | 0.207898E+10 | 0.00 | 0.207898E+10 | 0.599499E+09 | 0.496990E+10 |
March | 0.290334E+10 | 0.00 | 0.290334E+10 | 0.146713E+10 | 0.432298E+10 |
April | 0.356416E+10 | 30061643.51 | 0.353410E+10 | 0.231981E+10 | 0.281183E+10 |
May | 0.400294E+10 | 0.257156E+09 | 0.374578E+10 | 0.313257E+10 | 0.213854E+10 |
June | 0.440138E+10 | 0.719110E+09 | 0.368227E+10 | 0.453628E+10 | 0.135645E+10 |
July | 0.417473E+10 | 0.346517E+09 | 0.382822E+10 | 0.502007E+10 | 0.958373E+09 |
August | 0.387312E+10 | 86129136.60 | 0.378699E+10 | 0.442382E+10 | 0.108759E+10 |
September | 0.299781E+10 | 736317.73 | 0.299708E+10 | 0.296619E+10 | 0.182351E+10 |
October | 0.231156E+10 | 0.00 | 0.231156E+10 | 0.137917E+10 | 0.333414E+10 |
November | 0.189974E+10 | 0.00 | 0.189974E+10 | 0.432978E+09 | 0.462841E+10 |
December | 0.156751E+10 | 0.00 | 0.156751E+10 | 94652309.11 | 0.636686E+10 |
Annual Sum or Average | 0.356169E+11 | 0.143971E+10 | 0.341772E+11 | 0.266845E+11 | 0.398503E+11 |
Minimum of Months | 0.156751E+10 | 0.00 | 0.156751E+10 | 94652309.11 | 0.958373E+09 |
Maximum of Months | 0.440138E+10 | 0.719110E+09 | 0.382822E+10 | 0.502007E+10 | 0.636686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340042E+10 | 0.190128E+10 | 0.149914E+10 | 0.231047E+10 | 0.370234E+10 |
February | 0.373124E+10 | 0.201150E+10 | 0.171973E+10 | 0.284873E+10 | 0.307095E+10 |
March | 0.544988E+10 | 0.309830E+10 | 0.235158E+10 | 0.493885E+10 | 0.269179E+10 |
April | 0.720573E+10 | 0.410538E+10 | 0.310035E+10 | 0.727760E+10 | 0.180845E+10 |
May | 0.710324E+10 | 0.404763E+10 | 0.305561E+10 | 0.755512E+10 | 0.142807E+10 |
June | 0.741023E+10 | 0.456441E+10 | 0.284581E+10 | 0.881480E+10 | 0.889471E+09 |
July | 0.708591E+10 | 0.405156E+10 | 0.303435E+10 | 0.873680E+10 | 0.634020E+09 |
August | 0.701277E+10 | 0.386615E+10 | 0.314662E+10 | 0.836521E+10 | 0.706996E+09 |
September | 0.564948E+10 | 0.316120E+10 | 0.248828E+10 | 0.632862E+10 | 0.115645E+10 |
October | 0.507650E+10 | 0.322082E+10 | 0.185568E+10 | 0.494130E+10 | 0.208117E+10 |
November | 0.383976E+10 | 0.225743E+10 | 0.158232E+10 | 0.301553E+10 | 0.288819E+10 |
December | 0.321554E+10 | 0.195722E+10 | 0.125832E+10 | 0.212276E+10 | 0.390258E+10 |
Annual Sum or Average | 0.661807E+11 | 0.382429E+11 | 0.279378E+11 | 0.672558E+11 | 0.249605E+11 |
Minimum of Months | 0.321554E+10 | 0.190128E+10 | 0.125832E+10 | 0.212276E+10 | 0.634020E+09 |
Maximum of Months | 0.741023E+10 | 0.456441E+10 | 0.314662E+10 | 0.881480E+10 | 0.390258E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136203E+11 | 0.105996E+11 | 0.302070E+10 | 0.140456E+11 | 0.577273E+10 |
February | 0.120426E+11 | 0.879880E+10 | 0.324381E+10 | 0.119973E+11 | 0.488071E+10 |
March | 0.981948E+10 | 0.593680E+10 | 0.388269E+10 | 0.856204E+10 | 0.439804E+10 |
April | 0.740856E+10 | 0.304005E+10 | 0.436851E+10 | 0.538730E+10 | 0.297050E+10 |
May | 0.510444E+10 | 0.112104E+10 | 0.398340E+10 | 0.385351E+10 | 0.226480E+10 |
June | 0.417717E+10 | 0.511811E+09 | 0.366536E+10 | 0.452308E+10 | 0.145256E+10 |
July | 0.477712E+10 | 0.760269E+09 | 0.401686E+10 | 0.543546E+10 | 0.101332E+10 |
August | 0.657163E+10 | 0.213509E+10 | 0.443654E+10 | 0.638820E+10 | 0.116948E+10 |
September | 0.879514E+10 | 0.490403E+10 | 0.389111E+10 | 0.857608E+10 | 0.194453E+10 |
October | 0.124410E+11 | 0.916425E+10 | 0.327674E+10 | 0.127561E+11 | 0.344788E+10 |
November | 0.134107E+11 | 0.102943E+11 | 0.311639E+10 | 0.139253E+11 | 0.455219E+10 |
December | 0.147759E+11 | 0.121892E+11 | 0.258667E+10 | 0.155983E+11 | 0.587924E+10 |
Annual Sum or Average | 0.112944E+12 | 0.694553E+11 | 0.434888E+11 | 0.111048E+12 | 0.397460E+11 |
Minimum of Months | 0.417717E+10 | 0.511811E+09 | 0.258667E+10 | 0.385351E+10 | 0.101332E+10 |
Maximum of Months | 0.147759E+11 | 0.121892E+11 | 0.443654E+10 | 0.155983E+11 | 0.587924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350738E+10 | 0.200027E+10 | 0.150712E+10 | 0.263557E+10 | 0.405301E+10 |
February | 0.407773E+10 | 0.235551E+10 | 0.172222E+10 | 0.342910E+10 | 0.336982E+10 |
March | 0.504300E+10 | 0.268470E+10 | 0.235830E+10 | 0.461940E+10 | 0.297180E+10 |
April | 0.622856E+10 | 0.331505E+10 | 0.291352E+10 | 0.620749E+10 | 0.202520E+10 |
May | 0.610119E+10 | 0.314333E+10 | 0.295786E+10 | 0.644591E+10 | 0.155469E+10 |
June | 0.632913E+10 | 0.353103E+10 | 0.279810E+10 | 0.759550E+10 | 0.105214E+10 |
July | 0.589949E+10 | 0.288680E+10 | 0.301269E+10 | 0.730637E+10 | 0.721722E+09 |
August | 0.602878E+10 | 0.278849E+10 | 0.324029E+10 | 0.720858E+10 | 0.830705E+09 |
September | 0.527030E+10 | 0.277587E+10 | 0.249443E+10 | 0.596221E+10 | 0.129706E+10 |
October | 0.498186E+10 | 0.309639E+10 | 0.188547E+10 | 0.504193E+10 | 0.232874E+10 |
November | 0.378469E+10 | 0.222664E+10 | 0.155805E+10 | 0.310430E+10 | 0.312280E+10 |
December | 0.338245E+10 | 0.212131E+10 | 0.126114E+10 | 0.245863E+10 | 0.419978E+10 |
Annual Sum or Average | 0.606346E+11 | 0.329254E+11 | 0.277092E+11 | 0.620150E+11 | 0.275274E+11 |
Minimum of Months | 0.338245E+10 | 0.200027E+10 | 0.126114E+10 | 0.245863E+10 | 0.721722E+09 |
Maximum of Months | 0.632913E+10 | 0.353103E+10 | 0.324029E+10 | 0.759550E+10 | 0.419978E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.38 | 2697.06 | 687.58 | 0.00 | 687.58 | 0.00 | 0.00 |
February | 164.64 | 2424.38 | 859.35 | 0.00 | 859.35 | 0.00 | 0.00 |
March | 466.92 | 1879.44 | 1083.97 | 0.00 | 1083.97 | 0.00 | 0.00 |
April | 834.58 | 1242.40 | 1375.04 | 11.60 | 1363.44 | 0.00 | 0.00 |
May | 1138.02 | 875.81 | 1494.50 | 96.01 | 1398.49 | 0.00 | 0.00 |
June | 1727.92 | 549.53 | 1698.04 | 277.43 | 1420.61 | 0.00 | 0.00 |
July | 1866.67 | 355.30 | 1558.64 | 129.37 | 1429.27 | 0.00 | 0.00 |
August | 1637.83 | 411.70 | 1446.04 | 32.16 | 1413.88 | 0.00 | 0.00 |
September | 1119.85 | 775.71 | 1156.55 | 0.28 | 1156.26 | 0.00 | 0.00 |
October | 459.49 | 1458.36 | 863.03 | 0.00 | 863.03 | 0.00 | 0.00 |
November | 104.06 | 2181.20 | 732.91 | 0.00 | 732.91 | 0.00 | 0.00 |
December | 6.98 | 2933.02 | 585.23 | 0.00 | 585.23 | 0.00 | 0.00 |
Annual Sum or Average | 801.78 | 1477.48 | 1129.39 | 45.65 | 1083.74 | 0.00 | 0.00 |
Minimum of Months | 6.98 | 355.30 | 585.23 | 0.00 | 585.23 | 0.00 | 0.00 |
Maximum of Months | 1866.67 | 2933.02 | 1698.04 | 277.43 | 1429.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 794.46 | 1591.27 | 1269.58 | 709.86 | 559.72 | 0.00 | 0.00 |
February | 1118.21 | 1440.58 | 1542.35 | 831.48 | 710.87 | 0.00 | 0.00 |
March | 1812.18 | 1115.28 | 2034.76 | 1156.78 | 877.98 | 0.00 | 0.00 |
April | 2810.39 | 740.10 | 2780.00 | 1583.87 | 1196.13 | 0.00 | 0.00 |
May | 2832.33 | 564.28 | 2652.06 | 1511.22 | 1140.84 | 0.00 | 0.00 |
June | 3423.32 | 342.46 | 2858.90 | 1760.97 | 1097.93 | 0.00 | 0.00 |
July | 3293.50 | 207.24 | 2645.59 | 1512.68 | 1132.90 | 0.00 | 0.00 |
August | 3154.33 | 227.76 | 2618.28 | 1443.46 | 1174.82 | 0.00 | 0.00 |
September | 2447.13 | 472.62 | 2179.59 | 1219.60 | 959.99 | 0.00 | 0.00 |
October | 1826.04 | 860.50 | 1895.36 | 1202.52 | 692.83 | 0.00 | 0.00 |
November | 1112.49 | 1284.43 | 1481.39 | 870.93 | 610.47 | 0.00 | 0.00 |
December | 743.03 | 1703.98 | 1200.55 | 730.74 | 469.81 | 0.00 | 0.00 |
Annual Sum or Average | 2118.47 | 876.45 | 2098.58 | 1212.68 | 885.91 | 0.00 | 0.00 |
Minimum of Months | 743.03 | 207.24 | 1200.55 | 709.86 | 469.81 | 0.00 | 0.00 |
Maximum of Months | 3423.32 | 1703.98 | 2858.90 | 1760.97 | 1196.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5211.71 | 2341.54 | 5085.10 | 3957.32 | 1127.78 | 0.00 | 0.00 |
February | 4935.31 | 2194.56 | 4977.78 | 3636.95 | 1340.83 | 0.00 | 0.00 |
March | 3165.84 | 1790.26 | 3666.07 | 2216.47 | 1449.60 | 0.00 | 0.00 |
April | 2038.24 | 1248.69 | 2858.17 | 1172.82 | 1685.35 | 0.00 | 0.00 |
May | 1414.84 | 905.26 | 1905.74 | 418.54 | 1487.21 | 0.00 | 0.00 |
June | 1726.72 | 584.84 | 1611.54 | 197.45 | 1414.08 | 0.00 | 0.00 |
July | 2021.97 | 371.32 | 1783.54 | 283.84 | 1499.70 | 0.00 | 0.00 |
August | 2373.92 | 431.75 | 2453.51 | 797.12 | 1656.38 | 0.00 | 0.00 |
September | 3306.61 | 787.14 | 3393.10 | 1891.93 | 1501.17 | 0.00 | 0.00 |
October | 4758.00 | 1381.57 | 4644.80 | 3421.43 | 1223.37 | 0.00 | 0.00 |
November | 5343.55 | 1923.07 | 5173.71 | 3971.43 | 1202.28 | 0.00 | 0.00 |
December | 5787.56 | 2437.12 | 5516.52 | 4550.79 | 965.73 | 0.00 | 0.00 |
Annual Sum or Average | 3499.70 | 1362.15 | 3581.33 | 2202.34 | 1378.99 | 0.00 | 0.00 |
Minimum of Months | 1414.84 | 371.32 | 1611.54 | 197.45 | 965.73 | 0.00 | 0.00 |
Maximum of Months | 5787.56 | 2437.12 | 5516.52 | 4550.79 | 1685.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 935.85 | 1752.40 | 1309.51 | 746.82 | 562.69 | 0.00 | 0.00 |
February | 1359.64 | 1634.92 | 1685.58 | 973.68 | 711.90 | 0.00 | 0.00 |
March | 1656.43 | 1320.76 | 1882.85 | 1002.36 | 880.49 | 0.00 | 0.00 |
April | 2328.13 | 931.00 | 2403.01 | 1278.96 | 1124.05 | 0.00 | 0.00 |
May | 2376.86 | 647.60 | 2277.93 | 1173.59 | 1104.34 | 0.00 | 0.00 |
June | 2898.65 | 449.29 | 2441.80 | 1362.29 | 1079.52 | 0.00 | 0.00 |
July | 2689.68 | 297.94 | 2202.63 | 1077.81 | 1124.82 | 0.00 | 0.00 |
August | 2637.85 | 362.98 | 2250.90 | 1041.11 | 1209.79 | 0.00 | 0.00 |
September | 2271.14 | 562.66 | 2033.30 | 1070.94 | 962.36 | 0.00 | 0.00 |
October | 1835.73 | 1027.46 | 1860.02 | 1156.06 | 703.96 | 0.00 | 0.00 |
November | 1134.84 | 1485.50 | 1460.15 | 859.05 | 601.10 | 0.00 | 0.00 |
December | 862.79 | 1972.62 | 1262.87 | 792.01 | 470.86 | 0.00 | 0.00 |
Annual Sum or Average | 1917.54 | 1034.15 | 1922.72 | 1044.06 | 878.66 | 0.00 | 0.00 |
Minimum of Months | 862.79 | 297.94 | 1262.87 | 746.82 | 470.86 | 0.00 | 0.00 |
Maximum of Months | 2898.65 | 1972.62 | 2441.80 | 1362.29 | 1209.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.02 | 2477.45 | 687.59 | 0.00 | 687.59 | 0.00 | 0.00 |
February | 206.88 | 2232.67 | 859.37 | 0.00 | 859.37 | 0.00 | 0.00 |
March | 510.12 | 1739.67 | 1083.98 | 0.00 | 1083.98 | 0.00 | 0.00 |
April | 875.08 | 1153.64 | 1375.06 | 11.60 | 1363.46 | 0.00 | 0.00 |
May | 1164.28 | 830.04 | 1494.52 | 96.01 | 1398.51 | 0.00 | 0.00 |
June | 1757.36 | 532.12 | 1698.06 | 277.43 | 1420.63 | 0.00 | 0.00 |
July | 1892.01 | 355.50 | 1558.67 | 129.37 | 1429.29 | 0.00 | 0.00 |
August | 1665.96 | 408.95 | 1446.06 | 32.16 | 1413.90 | 0.00 | 0.00 |
September | 1142.77 | 730.77 | 1156.56 | 0.28 | 1156.28 | 0.00 | 0.00 |
October | 491.94 | 1346.46 | 863.04 | 0.00 | 863.04 | 0.00 | 0.00 |
November | 131.63 | 1979.76 | 732.92 | 0.00 | 732.92 | 0.00 | 0.00 |
December | 18.66 | 2620.49 | 585.24 | 0.00 | 585.24 | 0.00 | 0.00 |
Annual Sum or Average | 831.62 | 1363.12 | 1129.40 | 45.65 | 1083.75 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 355.50 | 585.24 | 0.00 | 585.24 | 0.00 | 0.00 |
Maximum of Months | 1892.01 | 2620.49 | 1698.06 | 277.43 | 1429.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 820.08 | 1494.24 | 1269.57 | 709.86 | 559.71 | 0.00 | 0.00 |
February | 1141.07 | 1360.42 | 1542.34 | 831.47 | 710.87 | 0.00 | 0.00 |
March | 1822.89 | 1062.88 | 2034.75 | 1156.77 | 877.98 | 0.00 | 0.00 |
April | 2802.57 | 725.69 | 2779.99 | 1583.86 | 1196.12 | 0.00 | 0.00 |
May | 2826.25 | 544.80 | 2652.05 | 1511.21 | 1140.83 | 0.00 | 0.00 |
June | 3414.45 | 344.24 | 2858.88 | 1760.96 | 1097.92 | 0.00 | 0.00 |
July | 3279.32 | 231.91 | 2645.58 | 1512.68 | 1132.90 | 0.00 | 0.00 |
August | 3138.29 | 260.86 | 2618.27 | 1443.46 | 1174.81 | 0.00 | 0.00 |
September | 2446.94 | 453.29 | 2179.58 | 1219.60 | 959.99 | 0.00 | 0.00 |
October | 1833.18 | 818.07 | 1895.35 | 1202.52 | 692.83 | 0.00 | 0.00 |
November | 1128.34 | 1206.51 | 1481.39 | 870.92 | 610.46 | 0.00 | 0.00 |
December | 761.19 | 1588.06 | 1200.55 | 730.74 | 469.80 | 0.00 | 0.00 |
Annual Sum or Average | 2122.29 | 838.38 | 2098.58 | 1212.67 | 885.90 | 0.00 | 0.00 |
Minimum of Months | 761.19 | 231.91 | 1200.55 | 709.86 | 469.80 | 0.00 | 0.00 |
Maximum of Months | 3414.45 | 1588.06 | 2858.88 | 1760.96 | 1196.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5171.36 | 2338.27 | 5085.25 | 3957.45 | 1127.80 | 0.00 | 0.00 |
February | 4902.74 | 2177.37 | 4977.93 | 3637.07 | 1340.86 | 0.00 | 0.00 |
March | 3161.32 | 1751.68 | 3666.17 | 2216.55 | 1449.63 | 0.00 | 0.00 |
April | 2056.82 | 1210.25 | 2858.24 | 1172.86 | 1685.38 | 0.00 | 0.00 |
May | 1432.61 | 877.43 | 1905.78 | 418.55 | 1487.23 | 0.00 | 0.00 |
June | 1752.22 | 571.64 | 1611.56 | 197.46 | 1414.10 | 0.00 | 0.00 |
July | 2044.75 | 376.38 | 1783.57 | 283.85 | 1499.72 | 0.00 | 0.00 |
August | 2396.30 | 439.70 | 2453.56 | 797.15 | 1656.41 | 0.00 | 0.00 |
September | 3304.32 | 774.60 | 3393.19 | 1891.99 | 1501.20 | 0.00 | 0.00 |
October | 4731.54 | 1369.29 | 4644.93 | 3421.54 | 1223.39 | 0.00 | 0.00 |
November | 5309.53 | 1904.98 | 5173.87 | 3971.56 | 1202.31 | 0.00 | 0.00 |
December | 5756.51 | 2398.48 | 5516.69 | 4550.94 | 965.75 | 0.00 | 0.00 |
Annual Sum or Average | 3494.49 | 1344.93 | 3581.43 | 2202.41 | 1379.02 | 0.00 | 0.00 |
Minimum of Months | 1432.61 | 376.38 | 1611.56 | 197.46 | 965.75 | 0.00 | 0.00 |
Maximum of Months | 5756.51 | 2398.48 | 5516.69 | 4550.94 | 1685.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 964.45 | 1620.95 | 1309.51 | 746.81 | 562.69 | 0.00 | 0.00 |
February | 1400.24 | 1482.65 | 1685.57 | 973.67 | 711.90 | 0.00 | 0.00 |
March | 1711.03 | 1172.14 | 1882.84 | 1002.35 | 880.49 | 0.00 | 0.00 |
April | 2389.08 | 818.26 | 2403.00 | 1278.95 | 1124.04 | 0.00 | 0.00 |
May | 2406.34 | 599.71 | 2277.92 | 1173.58 | 1104.34 | 0.00 | 0.00 |
June | 2936.70 | 413.57 | 2441.79 | 1362.28 | 1079.51 | 0.00 | 0.00 |
July | 2737.45 | 270.17 | 2202.62 | 1077.81 | 1124.81 | 0.00 | 0.00 |
August | 2698.63 | 313.38 | 2250.89 | 1041.10 | 1209.79 | 0.00 | 0.00 |
September | 2300.33 | 514.37 | 2033.30 | 1070.94 | 962.36 | 0.00 | 0.00 |
October | 1874.87 | 917.85 | 1860.01 | 1156.06 | 703.95 | 0.00 | 0.00 |
November | 1179.87 | 1296.88 | 1460.14 | 859.04 | 601.10 | 0.00 | 0.00 |
December | 904.02 | 1685.53 | 1262.86 | 792.01 | 470.85 | 0.00 | 0.00 |
Annual Sum or Average | 1960.51 | 922.68 | 1922.71 | 1044.06 | 878.65 | 0.00 | 0.00 |
Minimum of Months | 904.02 | 270.17 | 1262.86 | 746.81 | 470.85 | 0.00 | 0.00 |
Maximum of Months | 2936.70 | 1685.53 | 2441.79 | 1362.28 | 1209.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 116.60 | 2259.46 | 687.59 | 0.00 | 687.59 | 0.00 | 0.00 |
February | 247.81 | 2054.36 | 859.37 | 0.00 | 859.37 | 0.00 | 0.00 |
March | 547.76 | 1614.01 | 1083.98 | 0.00 | 1083.98 | 0.00 | 0.00 |
April | 894.99 | 1084.81 | 1375.06 | 11.60 | 1363.46 | 0.00 | 0.00 |
May | 1169.57 | 798.44 | 1494.52 | 96.01 | 1398.51 | 0.00 | 0.00 |
June | 1750.11 | 523.32 | 1698.06 | 277.43 | 1420.63 | 0.00 | 0.00 |
July | 1874.28 | 357.82 | 1558.67 | 129.37 | 1429.29 | 0.00 | 0.00 |
August | 1651.67 | 406.06 | 1446.06 | 32.16 | 1413.90 | 0.00 | 0.00 |
September | 1144.36 | 703.51 | 1156.56 | 0.28 | 1156.28 | 0.00 | 0.00 |
October | 514.92 | 1244.83 | 863.04 | 0.00 | 863.04 | 0.00 | 0.00 |
November | 167.04 | 1785.65 | 732.92 | 0.00 | 732.92 | 0.00 | 0.00 |
December | 35.34 | 2377.11 | 585.24 | 0.00 | 585.24 | 0.00 | 0.00 |
Annual Sum or Average | 846.16 | 1263.64 | 1129.40 | 45.65 | 1083.75 | 0.00 | 0.00 |
Minimum of Months | 35.34 | 357.82 | 585.24 | 0.00 | 585.24 | 0.00 | 0.00 |
Maximum of Months | 1874.28 | 2377.11 | 1698.06 | 277.43 | 1429.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 862.63 | 1382.29 | 1269.57 | 709.86 | 559.71 | 0.00 | 0.00 |
February | 1177.55 | 1269.41 | 1542.34 | 831.47 | 710.87 | 0.00 | 0.00 |
March | 1843.96 | 1005.00 | 2034.75 | 1156.77 | 877.98 | 0.00 | 0.00 |
April | 2807.71 | 697.70 | 2779.99 | 1583.86 | 1196.12 | 0.00 | 0.00 |
May | 2820.76 | 533.18 | 2652.05 | 1511.21 | 1140.83 | 0.00 | 0.00 |
June | 3400.77 | 343.16 | 2858.88 | 1760.96 | 1097.92 | 0.00 | 0.00 |
July | 3261.95 | 236.72 | 2645.58 | 1512.68 | 1132.90 | 0.00 | 0.00 |
August | 3123.21 | 263.96 | 2618.27 | 1443.46 | 1174.81 | 0.00 | 0.00 |
September | 2441.60 | 446.16 | 2179.58 | 1219.60 | 959.99 | 0.00 | 0.00 |
October | 1844.87 | 777.02 | 1895.35 | 1202.52 | 692.83 | 0.00 | 0.00 |
November | 1163.40 | 1114.27 | 1481.39 | 870.92 | 610.46 | 0.00 | 0.00 |
December | 792.55 | 1457.06 | 1200.55 | 730.74 | 469.80 | 0.00 | 0.00 |
Annual Sum or Average | 2132.67 | 791.49 | 2098.58 | 1212.67 | 885.90 | 0.00 | 0.00 |
Minimum of Months | 792.55 | 236.72 | 1200.55 | 709.86 | 469.80 | 0.00 | 0.00 |
Maximum of Months | 3400.77 | 1457.06 | 2858.88 | 1760.96 | 1196.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5244.04 | 2155.29 | 5085.25 | 3957.45 | 1127.80 | 0.00 | 0.00 |
February | 4959.20 | 2017.49 | 4977.93 | 3637.07 | 1340.86 | 0.00 | 0.00 |
March | 3196.70 | 1642.04 | 3666.17 | 2216.55 | 1449.63 | 0.00 | 0.00 |
April | 2078.43 | 1146.03 | 2858.24 | 1172.86 | 1685.38 | 0.00 | 0.00 |
May | 1438.74 | 845.58 | 1905.78 | 418.55 | 1487.23 | 0.00 | 0.00 |
June | 1745.02 | 560.40 | 1611.56 | 197.46 | 1414.10 | 0.00 | 0.00 |
July | 2029.37 | 378.33 | 1783.57 | 283.85 | 1499.72 | 0.00 | 0.00 |
August | 2385.08 | 436.63 | 2453.56 | 797.15 | 1656.41 | 0.00 | 0.00 |
September | 3308.67 | 750.21 | 3393.19 | 1891.99 | 1501.20 | 0.00 | 0.00 |
October | 4762.59 | 1287.29 | 4644.93 | 3421.54 | 1223.39 | 0.00 | 0.00 |
November | 5372.43 | 1756.25 | 5173.87 | 3971.56 | 1202.31 | 0.00 | 0.00 |
December | 5823.75 | 2195.06 | 5516.69 | 4550.94 | 965.75 | 0.00 | 0.00 |
Annual Sum or Average | 3521.32 | 1260.34 | 3581.43 | 2202.41 | 1379.02 | 0.00 | 0.00 |
Minimum of Months | 1438.74 | 378.33 | 1611.56 | 197.46 | 965.75 | 0.00 | 0.00 |
Maximum of Months | 5823.75 | 2195.06 | 5516.69 | 4550.94 | 1685.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 984.01 | 1513.22 | 1309.51 | 746.81 | 562.69 | 0.00 | 0.00 |
February | 1417.45 | 1392.95 | 1685.57 | 973.67 | 711.90 | 0.00 | 0.00 |
March | 1724.69 | 1109.54 | 1882.84 | 1002.35 | 880.49 | 0.00 | 0.00 |
April | 2394.86 | 781.33 | 2403.00 | 1278.95 | 1124.04 | 0.00 | 0.00 |
May | 2406.63 | 580.45 | 2277.92 | 1173.58 | 1104.34 | 0.00 | 0.00 |
June | 2930.36 | 405.92 | 2441.79 | 1362.28 | 1079.51 | 0.00 | 0.00 |
July | 2727.89 | 269.46 | 2202.62 | 1077.81 | 1124.81 | 0.00 | 0.00 |
August | 2691.38 | 310.15 | 2250.89 | 1041.10 | 1209.79 | 0.00 | 0.00 |
September | 2300.24 | 500.41 | 2033.30 | 1070.94 | 962.36 | 0.00 | 0.00 |
October | 1882.44 | 869.45 | 1860.01 | 1156.06 | 703.95 | 0.00 | 0.00 |
November | 1197.65 | 1204.78 | 1460.14 | 859.04 | 601.10 | 0.00 | 0.00 |
December | 917.95 | 1568.02 | 1262.86 | 792.01 | 470.85 | 0.00 | 0.00 |
Annual Sum or Average | 1966.48 | 872.89 | 1922.71 | 1044.06 | 878.65 | 0.00 | 0.00 |
Minimum of Months | 917.95 | 269.46 | 1262.86 | 746.81 | 470.85 | 0.00 | 0.00 |
Maximum of Months | 2930.36 | 1568.02 | 2441.79 | 1362.28 | 1209.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137621E+09 | 0.722380E+10 | 0.184160E+10 | 0.00 | 0.184160E+10 | 0.00 | 0.00 |
February | 0.398305E+09 | 0.586506E+10 | 0.207895E+10 | 0.00 | 0.207895E+10 | 0.00 | 0.00 |
March | 0.125060E+10 | 0.503389E+10 | 0.290330E+10 | 0.00 | 0.290330E+10 | 0.00 | 0.00 |
April | 0.216324E+10 | 0.322029E+10 | 0.356411E+10 | 30060747.01 | 0.353405E+10 | 0.00 | 0.00 |
May | 0.304806E+10 | 0.234576E+10 | 0.400288E+10 | 0.257148E+09 | 0.374573E+10 | 0.00 | 0.00 |
June | 0.447876E+10 | 0.142438E+10 | 0.440131E+10 | 0.719088E+09 | 0.368222E+10 | 0.00 | 0.00 |
July | 0.499968E+10 | 0.951622E+09 | 0.417467E+10 | 0.346506E+09 | 0.382816E+10 | 0.00 | 0.00 |
August | 0.438675E+10 | 0.110271E+10 | 0.387306E+10 | 86126568.07 | 0.378694E+10 | 0.00 | 0.00 |
September | 0.290266E+10 | 0.201063E+10 | 0.299777E+10 | 736295.77 | 0.299703E+10 | 0.00 | 0.00 |
October | 0.123070E+10 | 0.390607E+10 | 0.231153E+10 | 0.00 | 0.231153E+10 | 0.00 | 0.00 |
November | 0.269719E+09 | 0.565366E+10 | 0.189971E+10 | 0.00 | 0.189971E+10 | 0.00 | 0.00 |
December | 18688728.63 | 0.785580E+10 | 0.156748E+10 | 0.00 | 0.156748E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.252848E+11 | 0.465937E+11 | 0.356164E+11 | 0.143967E+10 | 0.341767E+11 | 0.00 | 0.00 |
Minimum of Months | 18688728.63 | 0.951622E+09 | 0.156748E+10 | 0.00 | 0.156748E+10 | 0.00 | 0.00 |
Maximum of Months | 0.499968E+10 | 0.785580E+10 | 0.440131E+10 | 0.719088E+09 | 0.382816E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212789E+10 | 0.426205E+10 | 0.340043E+10 | 0.190129E+10 | 0.149914E+10 | 0.00 | 0.00 |
February | 0.270518E+10 | 0.348505E+10 | 0.373125E+10 | 0.201151E+10 | 0.171974E+10 | 0.00 | 0.00 |
March | 0.485374E+10 | 0.298718E+10 | 0.544990E+10 | 0.309832E+10 | 0.235159E+10 | 0.00 | 0.00 |
April | 0.728454E+10 | 0.191833E+10 | 0.720576E+10 | 0.410539E+10 | 0.310037E+10 | 0.00 | 0.00 |
May | 0.758610E+10 | 0.151136E+10 | 0.710327E+10 | 0.404765E+10 | 0.305562E+10 | 0.00 | 0.00 |
June | 0.887325E+10 | 0.887666E+09 | 0.741026E+10 | 0.456443E+10 | 0.284583E+10 | 0.00 | 0.00 |
July | 0.882130E+10 | 0.555062E+09 | 0.708594E+10 | 0.405157E+10 | 0.303437E+10 | 0.00 | 0.00 |
August | 0.844855E+10 | 0.610041E+09 | 0.701280E+10 | 0.386617E+10 | 0.314663E+10 | 0.00 | 0.00 |
September | 0.634295E+10 | 0.122503E+10 | 0.564950E+10 | 0.316121E+10 | 0.248829E+10 | 0.00 | 0.00 |
October | 0.489085E+10 | 0.230475E+10 | 0.507652E+10 | 0.322084E+10 | 0.185568E+10 | 0.00 | 0.00 |
November | 0.288359E+10 | 0.332925E+10 | 0.383977E+10 | 0.225744E+10 | 0.158233E+10 | 0.00 | 0.00 |
December | 0.199014E+10 | 0.456394E+10 | 0.321555E+10 | 0.195723E+10 | 0.125833E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.668081E+11 | 0.276397E+11 | 0.661810E+11 | 0.382430E+11 | 0.279379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199014E+10 | 0.555062E+09 | 0.321555E+10 | 0.190129E+10 | 0.125833E+10 | 0.00 | 0.00 |
Maximum of Months | 0.887325E+10 | 0.456394E+10 | 0.741026E+10 | 0.456443E+10 | 0.314663E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139590E+11 | 0.627158E+10 | 0.136199E+11 | 0.105993E+11 | 0.302063E+10 | 0.00 | 0.00 |
February | 0.119395E+11 | 0.530908E+10 | 0.120423E+11 | 0.879851E+10 | 0.324374E+10 | 0.00 | 0.00 |
March | 0.847939E+10 | 0.479503E+10 | 0.981921E+10 | 0.593660E+10 | 0.388261E+10 | 0.00 | 0.00 |
April | 0.528311E+10 | 0.323661E+10 | 0.740838E+10 | 0.303995E+10 | 0.436843E+10 | 0.00 | 0.00 |
May | 0.378951E+10 | 0.242465E+10 | 0.510434E+10 | 0.112101E+10 | 0.398333E+10 | 0.00 | 0.00 |
June | 0.447566E+10 | 0.151590E+10 | 0.417710E+10 | 0.511794E+09 | 0.366531E+10 | 0.00 | 0.00 |
July | 0.541564E+10 | 0.994551E+09 | 0.477703E+10 | 0.760244E+09 | 0.401679E+10 | 0.00 | 0.00 |
August | 0.635831E+10 | 0.115641E+10 | 0.657147E+10 | 0.213502E+10 | 0.443646E+10 | 0.00 | 0.00 |
September | 0.857072E+10 | 0.204026E+10 | 0.879491E+10 | 0.490387E+10 | 0.389103E+10 | 0.00 | 0.00 |
October | 0.127438E+11 | 0.370041E+10 | 0.124406E+11 | 0.916395E+10 | 0.327667E+10 | 0.00 | 0.00 |
November | 0.138505E+11 | 0.498461E+10 | 0.134103E+11 | 0.102939E+11 | 0.311632E+10 | 0.00 | 0.00 |
December | 0.155014E+11 | 0.652757E+10 | 0.147754E+11 | 0.121888E+11 | 0.258661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110367E+12 | 0.429567E+11 | 0.112941E+12 | 0.694530E+11 | 0.434879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.378951E+10 | 0.994551E+09 | 0.417710E+10 | 0.511794E+09 | 0.258661E+10 | 0.00 | 0.00 |
Maximum of Months | 0.155014E+11 | 0.652757E+10 | 0.147754E+11 | 0.121888E+11 | 0.443646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250658E+10 | 0.469362E+10 | 0.350740E+10 | 0.200028E+10 | 0.150712E+10 | 0.00 | 0.00 |
February | 0.328925E+10 | 0.395519E+10 | 0.407775E+10 | 0.235552E+10 | 0.172223E+10 | 0.00 | 0.00 |
March | 0.443657E+10 | 0.353753E+10 | 0.504302E+10 | 0.268471E+10 | 0.235831E+10 | 0.00 | 0.00 |
April | 0.603452E+10 | 0.241314E+10 | 0.622859E+10 | 0.331506E+10 | 0.291353E+10 | 0.00 | 0.00 |
May | 0.636619E+10 | 0.173454E+10 | 0.610121E+10 | 0.314334E+10 | 0.295787E+10 | 0.00 | 0.00 |
June | 0.751329E+10 | 0.116456E+10 | 0.632916E+10 | 0.353104E+10 | 0.279811E+10 | 0.00 | 0.00 |
July | 0.720403E+10 | 0.798009E+09 | 0.589952E+10 | 0.288681E+10 | 0.301271E+10 | 0.00 | 0.00 |
August | 0.706521E+10 | 0.972197E+09 | 0.602881E+10 | 0.278850E+10 | 0.324030E+10 | 0.00 | 0.00 |
September | 0.588680E+10 | 0.145842E+10 | 0.527032E+10 | 0.277588E+10 | 0.249445E+10 | 0.00 | 0.00 |
October | 0.491682E+10 | 0.275195E+10 | 0.498188E+10 | 0.309640E+10 | 0.188548E+10 | 0.00 | 0.00 |
November | 0.294149E+10 | 0.385042E+10 | 0.378470E+10 | 0.222665E+10 | 0.155805E+10 | 0.00 | 0.00 |
December | 0.231089E+10 | 0.528347E+10 | 0.338246E+10 | 0.212132E+10 | 0.126114E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.604716E+11 | 0.326130E+11 | 0.606348E+11 | 0.329255E+11 | 0.277093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.231089E+10 | 0.798009E+09 | 0.338246E+10 | 0.200028E+10 | 0.126114E+10 | 0.00 | 0.00 |
Maximum of Months | 0.751329E+10 | 0.528347E+10 | 0.632916E+10 | 0.353104E+10 | 0.324030E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217011E+09 | 0.663561E+10 | 0.184163E+10 | 0.00 | 0.184163E+10 | 0.00 | 0.00 |
February | 0.500494E+09 | 0.540127E+10 | 0.207898E+10 | 0.00 | 0.207898E+10 | 0.00 | 0.00 |
March | 0.136629E+10 | 0.465954E+10 | 0.290334E+10 | 0.00 | 0.290334E+10 | 0.00 | 0.00 |
April | 0.226820E+10 | 0.299024E+10 | 0.356416E+10 | 30061643.51 | 0.353410E+10 | 0.00 | 0.00 |
May | 0.311842E+10 | 0.222318E+10 | 0.400294E+10 | 0.257156E+09 | 0.374578E+10 | 0.00 | 0.00 |
June | 0.455509E+10 | 0.137925E+10 | 0.440138E+10 | 0.719110E+09 | 0.368227E+10 | 0.00 | 0.00 |
July | 0.506755E+10 | 0.952170E+09 | 0.417473E+10 | 0.346517E+09 | 0.382822E+10 | 0.00 | 0.00 |
August | 0.446211E+10 | 0.109534E+10 | 0.387312E+10 | 86129136.60 | 0.378699E+10 | 0.00 | 0.00 |
September | 0.296207E+10 | 0.189416E+10 | 0.299781E+10 | 736317.73 | 0.299708E+10 | 0.00 | 0.00 |
October | 0.131763E+10 | 0.360635E+10 | 0.231156E+10 | 0.00 | 0.231156E+10 | 0.00 | 0.00 |
November | 0.341188E+09 | 0.513154E+10 | 0.189974E+10 | 0.00 | 0.189974E+10 | 0.00 | 0.00 |
December | 49978553.87 | 0.701872E+10 | 0.156751E+10 | 0.00 | 0.156751E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.262260E+11 | 0.429874E+11 | 0.356169E+11 | 0.143971E+10 | 0.341772E+11 | 0.00 | 0.00 |
Minimum of Months | 49978553.87 | 0.952170E+09 | 0.156751E+10 | 0.00 | 0.156751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.506755E+10 | 0.701872E+10 | 0.440138E+10 | 0.719110E+09 | 0.382822E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219650E+10 | 0.400217E+10 | 0.340042E+10 | 0.190128E+10 | 0.149914E+10 | 0.00 | 0.00 |
February | 0.276047E+10 | 0.329113E+10 | 0.373124E+10 | 0.201150E+10 | 0.171973E+10 | 0.00 | 0.00 |
March | 0.488243E+10 | 0.284683E+10 | 0.544988E+10 | 0.309830E+10 | 0.235158E+10 | 0.00 | 0.00 |
April | 0.726426E+10 | 0.188098E+10 | 0.720573E+10 | 0.410538E+10 | 0.310035E+10 | 0.00 | 0.00 |
May | 0.756984E+10 | 0.145920E+10 | 0.710324E+10 | 0.404763E+10 | 0.305561E+10 | 0.00 | 0.00 |
June | 0.885026E+10 | 0.892269E+09 | 0.741023E+10 | 0.456441E+10 | 0.284581E+10 | 0.00 | 0.00 |
July | 0.878333E+10 | 0.621143E+09 | 0.708591E+10 | 0.405156E+10 | 0.303435E+10 | 0.00 | 0.00 |
August | 0.840558E+10 | 0.698699E+09 | 0.701277E+10 | 0.386615E+10 | 0.314662E+10 | 0.00 | 0.00 |
September | 0.634247E+10 | 0.117492E+10 | 0.564948E+10 | 0.316120E+10 | 0.248828E+10 | 0.00 | 0.00 |
October | 0.490998E+10 | 0.219111E+10 | 0.507650E+10 | 0.322082E+10 | 0.185568E+10 | 0.00 | 0.00 |
November | 0.292466E+10 | 0.312727E+10 | 0.383976E+10 | 0.225743E+10 | 0.158232E+10 | 0.00 | 0.00 |
December | 0.203876E+10 | 0.425347E+10 | 0.321554E+10 | 0.195722E+10 | 0.125832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.669285E+11 | 0.264392E+11 | 0.661807E+11 | 0.382429E+11 | 0.279378E+11 | 0.00 | 0.00 |
Minimum of Months | 0.203876E+10 | 0.621143E+09 | 0.321554E+10 | 0.190128E+10 | 0.125832E+10 | 0.00 | 0.00 |
Maximum of Months | 0.885026E+10 | 0.425347E+10 | 0.741023E+10 | 0.456441E+10 | 0.314662E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138510E+11 | 0.626283E+10 | 0.136203E+11 | 0.105996E+11 | 0.302070E+10 | 0.00 | 0.00 |
February | 0.118607E+11 | 0.526748E+10 | 0.120426E+11 | 0.879880E+10 | 0.324381E+10 | 0.00 | 0.00 |
March | 0.846727E+10 | 0.469171E+10 | 0.981948E+10 | 0.593680E+10 | 0.388269E+10 | 0.00 | 0.00 |
April | 0.533127E+10 | 0.313697E+10 | 0.740856E+10 | 0.304005E+10 | 0.436851E+10 | 0.00 | 0.00 |
May | 0.383710E+10 | 0.235011E+10 | 0.510444E+10 | 0.112104E+10 | 0.398340E+10 | 0.00 | 0.00 |
June | 0.454175E+10 | 0.148169E+10 | 0.417717E+10 | 0.511811E+09 | 0.366536E+10 | 0.00 | 0.00 |
July | 0.547667E+10 | 0.100810E+10 | 0.477712E+10 | 0.760269E+09 | 0.401686E+10 | 0.00 | 0.00 |
August | 0.641824E+10 | 0.117769E+10 | 0.657163E+10 | 0.213509E+10 | 0.443654E+10 | 0.00 | 0.00 |
September | 0.856481E+10 | 0.200778E+10 | 0.879514E+10 | 0.490403E+10 | 0.389111E+10 | 0.00 | 0.00 |
October | 0.126730E+11 | 0.366750E+10 | 0.124410E+11 | 0.916425E+10 | 0.327674E+10 | 0.00 | 0.00 |
November | 0.137623E+11 | 0.493771E+10 | 0.134107E+11 | 0.102943E+11 | 0.311639E+10 | 0.00 | 0.00 |
December | 0.154182E+11 | 0.642408E+10 | 0.147759E+11 | 0.121892E+11 | 0.258667E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110202E+12 | 0.424137E+11 | 0.112944E+12 | 0.694553E+11 | 0.434888E+11 | 0.00 | 0.00 |
Minimum of Months | 0.383710E+10 | 0.100810E+10 | 0.417717E+10 | 0.511811E+09 | 0.258667E+10 | 0.00 | 0.00 |
Maximum of Months | 0.154182E+11 | 0.642408E+10 | 0.147759E+11 | 0.121892E+11 | 0.443654E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258317E+10 | 0.434155E+10 | 0.350738E+10 | 0.200027E+10 | 0.150712E+10 | 0.00 | 0.00 |
February | 0.338747E+10 | 0.358682E+10 | 0.407773E+10 | 0.235551E+10 | 0.172222E+10 | 0.00 | 0.00 |
March | 0.458283E+10 | 0.313945E+10 | 0.504300E+10 | 0.268470E+10 | 0.235830E+10 | 0.00 | 0.00 |
April | 0.619249E+10 | 0.212093E+10 | 0.622856E+10 | 0.331505E+10 | 0.291352E+10 | 0.00 | 0.00 |
May | 0.644513E+10 | 0.160625E+10 | 0.610119E+10 | 0.314333E+10 | 0.295786E+10 | 0.00 | 0.00 |
June | 0.761194E+10 | 0.107197E+10 | 0.632913E+10 | 0.353103E+10 | 0.279810E+10 | 0.00 | 0.00 |
July | 0.733200E+10 | 0.723612E+09 | 0.589949E+10 | 0.288680E+10 | 0.301269E+10 | 0.00 | 0.00 |
August | 0.722801E+10 | 0.839355E+09 | 0.602878E+10 | 0.278849E+10 | 0.324029E+10 | 0.00 | 0.00 |
September | 0.596245E+10 | 0.133326E+10 | 0.527030E+10 | 0.277587E+10 | 0.249443E+10 | 0.00 | 0.00 |
October | 0.502166E+10 | 0.245838E+10 | 0.498186E+10 | 0.309639E+10 | 0.188547E+10 | 0.00 | 0.00 |
November | 0.305822E+10 | 0.336152E+10 | 0.378469E+10 | 0.222664E+10 | 0.155805E+10 | 0.00 | 0.00 |
December | 0.242134E+10 | 0.451453E+10 | 0.338245E+10 | 0.212131E+10 | 0.126114E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.618267E+11 | 0.290976E+11 | 0.606346E+11 | 0.329254E+11 | 0.277092E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242134E+10 | 0.723612E+09 | 0.338245E+10 | 0.200027E+10 | 0.126114E+10 | 0.00 | 0.00 |
Maximum of Months | 0.761194E+10 | 0.451453E+10 | 0.632913E+10 | 0.353103E+10 | 0.324029E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.312310E+09 | 0.605173E+10 | 0.184163E+10 | 0.00 | 0.184163E+10 | 0.00 | 0.00 |
February | 0.599499E+09 | 0.496990E+10 | 0.207898E+10 | 0.00 | 0.207898E+10 | 0.00 | 0.00 |
March | 0.146713E+10 | 0.432298E+10 | 0.290334E+10 | 0.00 | 0.290334E+10 | 0.00 | 0.00 |
April | 0.231981E+10 | 0.281183E+10 | 0.356416E+10 | 30061643.51 | 0.353410E+10 | 0.00 | 0.00 |
May | 0.313257E+10 | 0.213854E+10 | 0.400294E+10 | 0.257156E+09 | 0.374578E+10 | 0.00 | 0.00 |
June | 0.453628E+10 | 0.135645E+10 | 0.440138E+10 | 0.719110E+09 | 0.368227E+10 | 0.00 | 0.00 |
July | 0.502007E+10 | 0.958373E+09 | 0.417473E+10 | 0.346517E+09 | 0.382822E+10 | 0.00 | 0.00 |
August | 0.442382E+10 | 0.108759E+10 | 0.387312E+10 | 86129136.60 | 0.378699E+10 | 0.00 | 0.00 |
September | 0.296619E+10 | 0.182351E+10 | 0.299781E+10 | 736317.73 | 0.299708E+10 | 0.00 | 0.00 |
October | 0.137917E+10 | 0.333414E+10 | 0.231156E+10 | 0.00 | 0.231156E+10 | 0.00 | 0.00 |
November | 0.432978E+09 | 0.462841E+10 | 0.189974E+10 | 0.00 | 0.189974E+10 | 0.00 | 0.00 |
December | 94652309.11 | 0.636686E+10 | 0.156751E+10 | 0.00 | 0.156751E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.266845E+11 | 0.398503E+11 | 0.356169E+11 | 0.143971E+10 | 0.341772E+11 | 0.00 | 0.00 |
Minimum of Months | 94652309.11 | 0.958373E+09 | 0.156751E+10 | 0.00 | 0.156751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.502007E+10 | 0.636686E+10 | 0.440138E+10 | 0.719110E+09 | 0.382822E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.231047E+10 | 0.370234E+10 | 0.340042E+10 | 0.190128E+10 | 0.149914E+10 | 0.00 | 0.00 |
February | 0.284873E+10 | 0.307095E+10 | 0.373124E+10 | 0.201150E+10 | 0.171973E+10 | 0.00 | 0.00 |
March | 0.493885E+10 | 0.269179E+10 | 0.544988E+10 | 0.309830E+10 | 0.235158E+10 | 0.00 | 0.00 |
April | 0.727760E+10 | 0.180845E+10 | 0.720573E+10 | 0.410538E+10 | 0.310035E+10 | 0.00 | 0.00 |
May | 0.755512E+10 | 0.142807E+10 | 0.710324E+10 | 0.404763E+10 | 0.305561E+10 | 0.00 | 0.00 |
June | 0.881480E+10 | 0.889471E+09 | 0.741023E+10 | 0.456441E+10 | 0.284581E+10 | 0.00 | 0.00 |
July | 0.873680E+10 | 0.634020E+09 | 0.708591E+10 | 0.405156E+10 | 0.303435E+10 | 0.00 | 0.00 |
August | 0.836521E+10 | 0.706996E+09 | 0.701277E+10 | 0.386615E+10 | 0.314662E+10 | 0.00 | 0.00 |
September | 0.632862E+10 | 0.115645E+10 | 0.564948E+10 | 0.316120E+10 | 0.248828E+10 | 0.00 | 0.00 |
October | 0.494130E+10 | 0.208117E+10 | 0.507650E+10 | 0.322082E+10 | 0.185568E+10 | 0.00 | 0.00 |
November | 0.301553E+10 | 0.288819E+10 | 0.383976E+10 | 0.225743E+10 | 0.158232E+10 | 0.00 | 0.00 |
December | 0.212276E+10 | 0.390258E+10 | 0.321554E+10 | 0.195722E+10 | 0.125832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.672558E+11 | 0.249605E+11 | 0.661807E+11 | 0.382429E+11 | 0.279378E+11 | 0.00 | 0.00 |
Minimum of Months | 0.212276E+10 | 0.634020E+09 | 0.321554E+10 | 0.190128E+10 | 0.125832E+10 | 0.00 | 0.00 |
Maximum of Months | 0.881480E+10 | 0.390258E+10 | 0.741023E+10 | 0.456441E+10 | 0.314662E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140456E+11 | 0.577273E+10 | 0.136203E+11 | 0.105996E+11 | 0.302070E+10 | 0.00 | 0.00 |
February | 0.119973E+11 | 0.488071E+10 | 0.120426E+11 | 0.879880E+10 | 0.324381E+10 | 0.00 | 0.00 |
March | 0.856204E+10 | 0.439804E+10 | 0.981948E+10 | 0.593680E+10 | 0.388269E+10 | 0.00 | 0.00 |
April | 0.538730E+10 | 0.297050E+10 | 0.740856E+10 | 0.304005E+10 | 0.436851E+10 | 0.00 | 0.00 |
May | 0.385351E+10 | 0.226480E+10 | 0.510444E+10 | 0.112104E+10 | 0.398340E+10 | 0.00 | 0.00 |
June | 0.452308E+10 | 0.145256E+10 | 0.417717E+10 | 0.511811E+09 | 0.366536E+10 | 0.00 | 0.00 |
July | 0.543546E+10 | 0.101332E+10 | 0.477712E+10 | 0.760269E+09 | 0.401686E+10 | 0.00 | 0.00 |
August | 0.638820E+10 | 0.116948E+10 | 0.657163E+10 | 0.213509E+10 | 0.443654E+10 | 0.00 | 0.00 |
September | 0.857608E+10 | 0.194453E+10 | 0.879514E+10 | 0.490403E+10 | 0.389111E+10 | 0.00 | 0.00 |
October | 0.127561E+11 | 0.344788E+10 | 0.124410E+11 | 0.916425E+10 | 0.327674E+10 | 0.00 | 0.00 |
November | 0.139253E+11 | 0.455219E+10 | 0.134107E+11 | 0.102943E+11 | 0.311639E+10 | 0.00 | 0.00 |
December | 0.155983E+11 | 0.587924E+10 | 0.147759E+11 | 0.121892E+11 | 0.258667E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.111048E+12 | 0.397460E+11 | 0.112944E+12 | 0.694553E+11 | 0.434888E+11 | 0.00 | 0.00 |
Minimum of Months | 0.385351E+10 | 0.101332E+10 | 0.417717E+10 | 0.511811E+09 | 0.258667E+10 | 0.00 | 0.00 |
Maximum of Months | 0.155983E+11 | 0.587924E+10 | 0.147759E+11 | 0.121892E+11 | 0.443654E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.263557E+10 | 0.405301E+10 | 0.350738E+10 | 0.200027E+10 | 0.150712E+10 | 0.00 | 0.00 |
February | 0.342910E+10 | 0.336982E+10 | 0.407773E+10 | 0.235551E+10 | 0.172222E+10 | 0.00 | 0.00 |
March | 0.461940E+10 | 0.297180E+10 | 0.504300E+10 | 0.268470E+10 | 0.235830E+10 | 0.00 | 0.00 |
April | 0.620749E+10 | 0.202520E+10 | 0.622856E+10 | 0.331505E+10 | 0.291352E+10 | 0.00 | 0.00 |
May | 0.644591E+10 | 0.155469E+10 | 0.610119E+10 | 0.314333E+10 | 0.295786E+10 | 0.00 | 0.00 |
June | 0.759550E+10 | 0.105214E+10 | 0.632913E+10 | 0.353103E+10 | 0.279810E+10 | 0.00 | 0.00 |
July | 0.730637E+10 | 0.721722E+09 | 0.589949E+10 | 0.288680E+10 | 0.301269E+10 | 0.00 | 0.00 |
August | 0.720858E+10 | 0.830705E+09 | 0.602878E+10 | 0.278849E+10 | 0.324029E+10 | 0.00 | 0.00 |
September | 0.596221E+10 | 0.129706E+10 | 0.527030E+10 | 0.277587E+10 | 0.249443E+10 | 0.00 | 0.00 |
October | 0.504193E+10 | 0.232874E+10 | 0.498186E+10 | 0.309639E+10 | 0.188547E+10 | 0.00 | 0.00 |
November | 0.310430E+10 | 0.312280E+10 | 0.378469E+10 | 0.222664E+10 | 0.155805E+10 | 0.00 | 0.00 |
December | 0.245863E+10 | 0.419978E+10 | 0.338245E+10 | 0.212131E+10 | 0.126114E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.620150E+11 | 0.275274E+11 | 0.606346E+11 | 0.329254E+11 | 0.277092E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245863E+10 | 0.721722E+09 | 0.338245E+10 | 0.200027E+10 | 0.126114E+10 | 0.00 | 0.00 |
Maximum of Months | 0.759550E+10 | 0.419978E+10 | 0.632913E+10 | 0.353103E+10 | 0.324029E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.2 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.20 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.66 | -5.5 | 4.72 | -6.1 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.69 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.40 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.39 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.11 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.38 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.86 | 7.70 | 3.48 | 8.21 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.78 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.53 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.11 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.80 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.83 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.65 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.28 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.68 | -1.5 | 8.93 | 13.33 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.11 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.67 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.27 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.73 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.23 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.79 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 3.99 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 3.99 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.73 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.1 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.6 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.2 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -0.7 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.53 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.76 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.7 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.82 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.83 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.65 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.92 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.05 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.75 | 167.00 | 0.00 |
June | 18.16 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.19 | 01-JUL-00:00 | 21.20 | 13.50 | 3.60 | 17.57 | 0.00 | 0.00 |
August | 19.17 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.18 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.15 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.79 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.90 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.90 | 12.80 | -10.0 | 2.10 | -0.1 | 0.00 | 0.00 | |
Maximum of Months | 19.19 | 31.70 | 15.60 | 13.40 | 19.17 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.71 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.78 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.70 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.04 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.58 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.03 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.37 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.04 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.238610E+11 | -.380879E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130210E+10 | 68.27 | 0.00 | 0.00 |
February | 0.220774E+11 | -.348997E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.117117E+10 | 68.07 | 0.00 | 0.00 |
March | 0.258880E+11 | -.400231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127209E+10 | 67.16 | 0.00 | 0.00 |
April | 0.204313E+11 | -.344037E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125329E+10 | 68.05 | 0.00 | 0.00 |
May | 0.196601E+11 | -.341882E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130200E+10 | 68.24 | 0.00 | 0.00 |
June | 0.172851E+11 | -.314794E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125609E+10 | 68.08 | 0.00 | 0.00 |
July | 0.135483E+11 | -.284565E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.133223E+10 | 69.39 | 0.00 | 0.00 |
August | 0.159982E+11 | -.307934E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130148E+10 | 68.23 | 0.00 | 0.00 |
September | 0.145540E+11 | -.289074E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127462E+10 | 68.84 | 0.00 | 0.00 |
October | 0.171384E+11 | -.318138E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131799E+10 | 68.91 | 0.00 | 0.00 |
November | 0.196465E+11 | -.336355E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127203E+10 | 68.77 | 0.00 | 0.00 |
December | 0.213139E+11 | -.357199E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130433E+10 | 68.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.231402E+12 | -.402409E+12 | 8760.00 | -.153594E+11 | 68.37 | |||||
Minimum of Months | 0.135483E+11 | -.400231E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.133223E+10 | 67.16 | 0.00 | 0.00 |
Maximum of Months | 0.258880E+11 | -.284565E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117117E+10 | 69.39 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | ||||||||||
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.719744E+10 | 442985.37 | 15-JAN-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694973E+10 | 389912.59 | 20-FEB-18:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196533E+10 | 219482.56 | 01-MAR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88717814.87 | 13729.62 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689416E+09 | 415488.14 | 12-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177249E+09 | 357651.03 | 09-JUN-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282092E+10 | 374586.11 | 29-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261222E+10 | 213609.43 | 05-NOV-02:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113291E+09 | 15650.64 | 09-DEC-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226143E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.719744E+10 | 442985.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208237E+10 | 85742.96 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.869214E+09 | 85673.65 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77962124.18 | 84935.39 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505314E+09 | 85498.61 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176339E+10 | 85746.76 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529824E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208237E+10 | 85746.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 844288.76 | 324.41 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 300951.15 | 247.05 | 06-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1145239.91 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 844288.76 | 324.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104817E+09 | 2681.99 | 21-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35649102.83 | 3184.89 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 850153.09 | 1071.60 | 04-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1607547.37 | 654.69 | 26-OCT-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2416662.61 | 512.13 | 28-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78078775.86 | 7884.49 | 14-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223420E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104817E+09 | 7884.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 54396092.89 | 11542.52 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23017595.85 | 11534.20 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8580273.04 | 4429.47 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85993961.77 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54396092.89 | 11542.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14171380.61 | 1994.77 | 17-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 188309.49 | 212.40 | 06-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14359690.09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14171380.61 | 1994.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.872715E+10 | 129935.21 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519146E+10 | 129950.14 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.854168E+09 | 133647.57 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33293036.23 | 43586.68 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228808E+09 | 62311.04 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168269E+10 | 129842.60 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831517E+10 | 131394.45 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250327E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.872715E+10 | 133647.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103546E+11 | 138404.33 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552628E+10 | 138315.32 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155759E+10 | 136342.64 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93320768.64 | 43602.20 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1387096.33 | 5374.76 | 05-MAY-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.773322E+09 | 114689.45 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238043E+10 | 136900.11 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952732E+10 | 138302.83 | 04-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302143E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103546E+11 | 138404.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297215E+10 | 140283.12 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173253E+10 | 140216.52 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247640E+09 | 133893.14 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11066261.95 | 4826.11 | 08-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132918E+09 | 28889.55 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140805E+09 | 119871.34 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216024E+10 | 143043.65 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739736E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.297215E+10 | 143043.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.903139E+10 | 132719.78 | 17-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522297E+10 | 132699.20 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167468E+10 | 130810.17 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66101219.97 | 14023.91 | 24-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32807936.69 | 7167.19 | 05-MAY-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592525E+09 | 58598.17 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211676E+10 | 131340.14 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.784936E+10 | 132626.21 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265866E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.903139E+10 | 132719.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.407542E+10 | 15303.94 | 02-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266775E+10 | 15252.11 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106581E+10 | 15288.78 | 21-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194406E+09 | 15182.29 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39302338.77 | 15141.89 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417652E+09 | 15193.21 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163291E+10 | 15301.84 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404506E+10 | 15305.95 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141383E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.407542E+10 | 15305.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285295E+10 | 16373.92 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177441E+10 | 16365.19 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723256E+09 | 16362.72 | 21-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99093986.47 | 16318.24 | 06-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20359317.56 | 9498.46 | 06-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1128687.95 | 792.66 | 02-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 649018.18 | 1649.12 | 09-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353605E+09 | 16324.21 | 26-OCT-04:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110993E+10 | 16370.45 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270219E+10 | 16368.83 | 04-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.963758E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285295E+10 | 16373.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203052E+10 | 16444.62 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134864E+10 | 16393.92 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722549E+09 | 16440.09 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153552E+09 | 16234.48 | 06-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43314751.37 | 15313.46 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1017994.38 | 526.95 | 09-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238743E+09 | 16333.69 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.631195E+09 | 16436.06 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172227E+10 | 16447.31 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689180E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203052E+10 | 16447.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274878E+10 | 17026.93 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176629E+10 | 17023.44 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.904345E+09 | 16986.71 | 29-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155165E+09 | 16972.25 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57525796.66 | 10211.78 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10622632.98 | 2224.69 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3280722.42 | 696.26 | 09-SEP-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.396442E+09 | 16977.43 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112570E+10 | 16982.99 | 10-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257940E+10 | 17019.57 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974755E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274878E+10 | 17026.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737762E+09 | 250565.34 | 12-JAN-04:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399674E+09 | 250734.25 | 17-FEB-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252205E+09 | 250831.69 | 29-MAR-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304373E+09 | 250491.22 | 02-APR-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187979E+09 | 251000.40 | 29-MAY-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.413766E+09 | 251289.20 | 04-JUN-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646216E+09 | 249525.14 | 04-JUL-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413429E+09 | 251194.03 | 27-AUG-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927343E+09 | 251275.48 | 04-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683745E+09 | 251126.46 | 22-OCT-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.765390E+09 | 250593.86 | 11-NOV-16:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.851884E+09 | 250718.74 | 25-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658377E+10 | |||||||
Minimum of Months | 0.187979E+09 | 249525.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.927343E+09 | 251289.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.881746E+10 | 42319.32 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.480217E+10 | 39260.30 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104328E+10 | 23092.34 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61104463.72 | 10751.22 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19567209.61 | 5948.43 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621316E+09 | 24972.08 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121446E+10 | 21245.96 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491110E+10 | 34827.83 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214905E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.881746E+10 | 42319.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163801E+12 | 438661.36 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103423E+12 | 434962.43 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.408226E+11 | 316728.67 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.887811E+10 | 230849.18 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192865E+10 | 129227.49 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202031E+11 | 347394.06 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537809E+11 | 389334.48 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150295E+12 | 439080.02 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543133E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163801E+12 | 439080.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211252E+11 | 44631.75 | 30-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142741E+11 | 45530.44 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619709E+10 | 34631.54 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150043E+10 | 25662.60 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306369E+09 | 14829.44 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7430663.33 | 5087.83 | 09-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359699E+10 | 38094.44 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.826133E+10 | 42691.40 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216554E+11 | 44728.51 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769243E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216554E+11 | 45530.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 52060397.90 | 52060397.90 | 18990.85 | 01-JAN-16:11 | 18990.85 | 0.00 |
February | 0.00 | 0.00 | 0.158369E+10 | 0.158369E+10 | 48708.54 | 13-FEB-16:00 | 48708.54 | 0.00 |
March | 0.00 | 0.00 | 0.440033E+10 | 0.440033E+10 | 50481.63 | 08-MAR-16:00 | 50481.63 | 0.00 |
April | 0.00 | 0.00 | 0.217785E+11 | 0.217785E+11 | 87812.19 | 30-APR-15:20 | 87812.19 | 0.00 |
May | 0.00 | 0.00 | 0.379821E+11 | 0.379727E+11 | 102469.53 | 21-MAY-18:51 | 102469.53 | 0.04 |
June | 0.00 | 0.00 | 0.693520E+11 | 0.692764E+11 | 125054.18 | 18-JUN-14:37 | 125054.18 | 0.22 |
July | 0.00 | 0.00 | 0.843753E+11 | 0.833701E+11 | 162823.43 | 02-JUL-13:33 | 107880.41 | 0.53 |
August | 0.00 | 0.00 | 0.842442E+11 | 0.831939E+11 | 135657.16 | 13-AUG-13:10 | 108619.38 | 0.57 |
September | 0.00 | 0.00 | 0.570464E+11 | 0.563343E+11 | 120411.00 | 10-SEP-14:10 | 120411.00 | 0.33 |
October | 0.00 | 0.00 | 0.262491E+11 | 0.262238E+11 | 119702.94 | 01-OCT-12:51 | 119702.94 | 0.09 |
November | 0.00 | 0.00 | 0.881340E+09 | 0.881340E+09 | 46864.58 | 19-NOV-15:20 | 46864.58 | 0.00 |
December | 0.00 | 0.00 | 5225176.89 | 5225176.89 | 14993.56 | 17-DEC-16:50 | 14993.56 | 0.00 |
Annual Sum or Average | 0.387950E+12 | 0.385072E+12 | 0.15 | |||||
Minimum of Months | 0.00 | 0.00 | 5225176.89 | 5225176.89 | 14993.56 | 14993.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.843753E+11 | 0.833701E+11 | 162823.43 | 125054.18 | 0.57 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.926173E+09 | 0.926173E+09 | 22778.61 | 05-JAN-15:50 | 22778.61 | 0.00 |
February | 0.00 | 0.00 | 0.352250E+10 | 0.352250E+10 | 78083.97 | 14-FEB-16:00 | 78083.97 | 0.00 |
March | 0.00 | 0.00 | 0.134655E+11 | 0.134655E+11 | 80124.08 | 08-MAR-16:00 | 80124.08 | 0.00 |
April | 0.00 | 0.00 | 0.423849E+11 | 0.423849E+11 | 109282.56 | 13-APR-16:00 | 109282.56 | 0.00 |
May | 0.00 | 0.00 | 0.618696E+11 | 0.618416E+11 | 112924.34 | 19-MAY-16:00 | 112924.34 | 0.07 |
June | 0.00 | 0.00 | 0.116980E+12 | 0.116915E+12 | 148021.13 | 29-JUN-05:02 | 128741.56 | 0.25 |
July | 0.00 | 0.00 | 0.155100E+12 | 0.143542E+12 | 160475.67 | 01-JUL-03:01 | 68104.21 | 0.70 |
August | 0.00 | 0.00 | 0.159368E+12 | 0.148759E+12 | 170079.13 | 23-AUG-16:00 | 96718.45 | 0.77 |
September | 0.00 | 0.00 | 0.891706E+11 | 0.866697E+11 | 158743.94 | 05-SEP-13:10 | 98033.94 | 0.38 |
October | 0.00 | 0.00 | 0.438498E+11 | 0.436231E+11 | 116767.05 | 10-OCT-15:20 | 116767.05 | 0.10 |
November | 0.00 | 0.00 | 0.294962E+10 | 0.294962E+10 | 46171.78 | 09-NOV-14:00 | 46171.78 | 0.00 |
December | 0.00 | 0.00 | 867.66 | 867.66 | 0.50 | 16-DEC-12:50 | 0.50 | 0.00 |
Annual Sum or Average | 0.689586E+12 | 0.664599E+12 | 0.19 | |||||
Minimum of Months | 0.00 | 0.00 | 867.66 | 867.66 | 0.50 | 0.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159368E+12 | 0.148759E+12 | 170079.13 | 128741.56 | 0.77 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.687477E+10 | 0.687477E+10 | 192091.67 | 05-JAN-16:00 | 192091.67 | 0.00 |
February | 0.00 | 0.00 | 0.292179E+11 | 0.292179E+11 | 659382.96 | 14-FEB-16:00 | 659382.96 | 0.00 |
March | 0.00 | 0.00 | 0.105873E+12 | 0.105873E+12 | 671574.50 | 08-MAR-16:00 | 671574.50 | 0.00 |
April | 0.00 | 0.00 | 0.320719E+12 | 0.320719E+12 | 932244.47 | 13-APR-16:00 | 932244.47 | 0.00 |
May | 0.00 | 0.00 | 0.545706E+12 | 0.545459E+12 | 1079388.48 | 19-MAY-16:00 | 1079388.48 | 0.07 |
June | 0.00 | 0.00 | 0.100464E+13 | 0.100411E+13 | 1399314.97 | 28-JUN-16:00 | 1399314.97 | 0.22 |
July | 0.00 | 0.00 | 0.124016E+13 | 0.115784E+13 | 1471887.53 | 12-JUL-05:02 | 998456.80 | 0.57 |
August | 0.00 | 0.00 | 0.117639E+13 | 0.110669E+13 | 1515432.30 | 15-AUG-05:02 | 863513.24 | 0.59 |
September | 0.00 | 0.00 | 0.785453E+12 | 0.765329E+12 | 1350535.74 | 05-SEP-13:00 | 828622.33 | 0.36 |
October | 0.00 | 0.00 | 0.368172E+12 | 0.366586E+12 | 1050866.09 | 06-OCT-15:30 | 1050866.09 | 0.09 |
November | 0.00 | 0.00 | 0.215537E+11 | 0.215537E+11 | 363108.16 | 09-NOV-14:00 | 363108.16 | 0.00 |
December | 0.00 | 0.00 | 166676.89 | 166676.89 | 3.24 | 27-DEC-06:01 | 3.24 | 0.00 |
Annual Sum or Average | 0.560475E+13 | 0.543025E+13 | 0.16 | |||||
Minimum of Months | 0.00 | 0.00 | 166676.89 | 166676.89 | 3.24 | 3.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.124016E+13 | 0.115784E+13 | 1515432.30 | 1399314.97 | 0.59 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.540561E+09 | 0.540561E+09 | 17029.96 | 05-JAN-16:00 | 17029.96 | 0.00 |
February | 0.00 | 0.00 | 0.265461E+10 | 0.265461E+10 | 65926.41 | 14-FEB-16:00 | 65926.41 | 0.00 |
March | 0.00 | 0.00 | 0.101270E+11 | 0.101270E+11 | 69798.98 | 08-MAR-16:00 | 69798.98 | 0.00 |
April | 0.00 | 0.00 | 0.342721E+11 | 0.342721E+11 | 111084.46 | 13-APR-16:00 | 111084.46 | 0.00 |
May | 0.00 | 0.00 | 0.607123E+11 | 0.606924E+11 | 132312.79 | 19-MAY-16:00 | 132312.79 | 0.06 |
June | 0.00 | 0.00 | 0.115226E+12 | 0.115179E+12 | 171439.50 | 28-JUN-16:00 | 171439.50 | 0.23 |
July | 0.00 | 0.00 | 0.143330E+12 | 0.134397E+12 | 165919.04 | 21-JUL-15:40 | 165919.04 | 0.58 |
August | 0.00 | 0.00 | 0.133814E+12 | 0.126364E+12 | 159884.83 | 23-AUG-16:00 | 91349.36 | 0.59 |
September | 0.00 | 0.00 | 0.856652E+11 | 0.836621E+11 | 155424.02 | 05-SEP-13:30 | 98658.68 | 0.34 |
October | 0.00 | 0.00 | 0.380558E+11 | 0.379187E+11 | 122327.05 | 06-OCT-15:20 | 122327.05 | 0.08 |
November | 0.00 | 0.00 | 0.180108E+10 | 0.180108E+10 | 32383.64 | 09-NOV-14:00 | 32383.64 | 0.00 |
December | 0.00 | 0.00 | 184.13 | 184.13 | 0.79 | 26-DEC-05:11 | 0.79 | 0.00 |
Annual Sum or Average | 0.626198E+12 | 0.607609E+12 | 0.16 | |||||
Minimum of Months | 0.00 | 0.00 | 184.13 | 184.13 | 0.79 | 0.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143330E+12 | 0.134397E+12 | 171439.50 | 171439.50 | 0.59 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.397198E+12 | 0.344870E+12 | 464815.98 | 22-JAN-08:63 | 409490.71 | 0.00 |
February | 0.00 | 0.00 | 0.606432E+12 | 0.528540E+12 | 472969.30 | 05-FEB-08:40 | 455893.20 | 0.00 |
March | 0.00 | 0.00 | 0.928024E+12 | 0.815444E+12 | 460974.86 | 06-MAR-23:41 | 411634.19 | 0.00 |
April | 0.00 | 0.00 | 0.114307E+13 | 0.101280E+13 | 456944.90 | 29-APR-02:42 | 397648.92 | 0.00 |
May | 0.00 | 0.00 | 0.385715E+12 | 0.341576E+12 | 463042.79 | 02-MAY-02:53 | 411200.97 | 0.00 |
June | 0.00 | 0.00 | 0.616526E+12 | 0.560559E+12 | 470615.07 | 09-JUN-02:10 | 447258.40 | 0.00 |
July | 0.00 | 0.00 | 0.881356E+12 | 0.816236E+12 | 345842.07 | 08-JUL-03:30 | 305310.51 | 0.00 |
August | 0.00 | 0.00 | 0.114552E+13 | 0.103320E+13 | 455110.14 | 31-AUG-06:00 | 396220.79 | 0.00 |
September | 0.00 | 0.00 | 0.375311E+12 | 0.333701E+12 | 244889.21 | 01-SEP-00:02 | 218580.24 | 0.00 |
October | 0.00 | 0.00 | 0.662036E+12 | 0.583226E+12 | 471669.66 | 26-OCT-03:40 | 453453.05 | 0.00 |
November | 0.00 | 0.00 | 0.908108E+12 | 0.794563E+12 | 466850.03 | 20-NOV-23:20 | 418112.35 | 0.00 |
December | 0.00 | 0.00 | 0.120439E+13 | 0.104895E+13 | 458965.16 | 01-DEC-00:20 | 401218.54 | 0.00 |
Annual Sum or Average | 0.925369E+13 | 0.821366E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.375311E+12 | 0.333701E+12 | 244889.21 | 218580.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120439E+13 | 0.104895E+13 | 472969.30 | 455893.20 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.501206E+10 | 0.501206E+10 | 2916.74 | 26-JAN-17:00 | 2916.74 | 0.00 |
February | 0.00 | 0.00 | 0.930531E+10 | 0.930531E+10 | 4871.94 | 15-FEB-17:00 | 4871.94 | 0.00 |
March | 0.00 | 0.00 | 0.155328E+11 | 0.155328E+11 | 6736.51 | 24-MAR-17:40 | 6736.51 | 0.00 |
April | 0.00 | 0.00 | 0.199730E+11 | 0.199730E+11 | 8575.17 | 15-APR-17:55 | 8575.17 | 0.00 |
May | 0.00 | 0.00 | 0.595800E+10 | 0.595800E+10 | 2973.99 | 20-MAY-18:11 | 2973.99 | 0.00 |
June | 0.00 | 0.00 | 0.106425E+11 | 0.106425E+11 | 5121.08 | 11-JUN-18:45 | 5121.08 | 0.00 |
July | 0.00 | 0.00 | 0.158553E+11 | 0.158553E+11 | 7016.62 | 04-JUL-18:51 | 7016.62 | 0.00 |
August | 0.00 | 0.00 | 0.202861E+11 | 0.202861E+11 | 7994.23 | 10-AUG-19:00 | 7994.23 | 0.00 |
September | 0.00 | 0.00 | 0.586722E+10 | 0.586722E+10 | 2971.00 | 02-SEP-17:44 | 2971.00 | 0.00 |
October | 0.00 | 0.00 | 0.108386E+11 | 0.108386E+11 | 4946.28 | 15-OCT-17:00 | 4946.28 | 0.00 |
November | 0.00 | 0.00 | 0.150090E+11 | 0.150090E+11 | 6676.13 | 06-NOV-16:40 | 6676.13 | 0.00 |
December | 0.00 | 0.00 | 0.203318E+11 | 0.203318E+11 | 8421.58 | 31-DEC-16:37 | 8421.58 | 0.00 |
Annual Sum or Average | 0.154612E+12 | 0.154612E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.501206E+10 | 0.501206E+10 | 2916.74 | 2916.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203318E+11 | 0.203318E+11 | 8575.17 | 8575.17 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.359701E+11 | 0.359701E+11 | 27332.41 | 26-JAN-17:00 | 27332.41 | 0.00 |
February | 0.00 | 0.00 | 0.791145E+11 | 0.791145E+11 | 45918.81 | 15-FEB-17:05 | 45918.81 | 0.00 |
March | 0.00 | 0.00 | 0.140210E+12 | 0.140210E+12 | 63889.35 | 24-MAR-17:40 | 63889.35 | 0.00 |
April | 0.00 | 0.00 | 0.186257E+12 | 0.186257E+12 | 80128.87 | 07-APR-17:50 | 80128.87 | 0.00 |
May | 0.00 | 0.00 | 0.524979E+11 | 0.524979E+11 | 28365.63 | 20-MAY-18:11 | 28365.63 | 0.00 |
June | 0.00 | 0.00 | 0.993864E+11 | 0.993864E+11 | 47958.30 | 18-JUN-18:28 | 47958.30 | 0.00 |
July | 0.00 | 0.00 | 0.150491E+12 | 0.150491E+12 | 66583.72 | 04-JUL-18:34 | 66583.72 | 0.00 |
August | 0.00 | 0.00 | 0.192240E+12 | 0.192240E+12 | 76128.29 | 10-AUG-18:55 | 76128.29 | 0.00 |
September | 0.00 | 0.00 | 0.519522E+11 | 0.519522E+11 | 28099.94 | 28-SEP-17:00 | 28099.94 | 0.00 |
October | 0.00 | 0.00 | 0.968932E+11 | 0.968932E+11 | 46689.60 | 04-OCT-17:00 | 46689.60 | 0.00 |
November | 0.00 | 0.00 | 0.133848E+12 | 0.133848E+12 | 62892.97 | 02-NOV-16:40 | 62892.97 | 0.00 |
December | 0.00 | 0.00 | 0.179922E+12 | 0.179922E+12 | 78628.66 | 29-DEC-16:50 | 78628.66 | 0.00 |
Annual Sum or Average | 0.139878E+13 | 0.139878E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.359701E+11 | 0.359701E+11 | 27332.41 | 27332.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192240E+12 | 0.192240E+12 | 80128.87 | 80128.87 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.182442E+10 | 0.182442E+10 | 2676.49 | 26-JAN-17:00 | 2676.49 | 0.00 |
February | 0.00 | 0.00 | 0.647521E+10 | 0.647521E+10 | 4625.09 | 15-FEB-17:00 | 4625.09 | 0.00 |
March | 0.00 | 0.00 | 0.130371E+11 | 0.130371E+11 | 6445.90 | 24-MAR-17:40 | 6445.90 | 0.00 |
April | 0.00 | 0.00 | 0.181830E+11 | 0.181830E+11 | 8074.37 | 05-APR-18:00 | 8074.37 | 0.00 |
May | 0.00 | 0.00 | 0.505070E+10 | 0.505070E+10 | 3013.98 | 20-MAY-18:10 | 3013.98 | 0.00 |
June | 0.00 | 0.00 | 0.995625E+10 | 0.995625E+10 | 5095.98 | 18-JUN-18:24 | 5095.98 | 0.00 |
July | 0.00 | 0.00 | 0.151887E+11 | 0.151887E+11 | 6942.91 | 04-JUL-19:12 | 6942.91 | 0.00 |
August | 0.00 | 0.00 | 0.193910E+11 | 0.193910E+11 | 7695.16 | 10-AUG-18:50 | 7695.16 | 0.00 |
September | 0.00 | 0.00 | 0.505795E+10 | 0.505795E+10 | 2931.28 | 02-SEP-17:46 | 2931.28 | 0.00 |
October | 0.00 | 0.00 | 0.899477E+10 | 0.899477E+10 | 4760.96 | 04-OCT-17:00 | 4760.96 | 0.00 |
November | 0.00 | 0.00 | 0.119877E+11 | 0.119877E+11 | 6299.49 | 02-NOV-16:40 | 6299.49 | 0.00 |
December | 0.00 | 0.00 | 0.160266E+11 | 0.160266E+11 | 7799.35 | 29-DEC-16:50 | 7799.35 | 0.00 |
Annual Sum or Average | 0.131173E+12 | 0.131173E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.182442E+10 | 0.182442E+10 | 2676.49 | 2676.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193910E+11 | 0.193910E+11 | 8074.37 | 8074.37 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6939.37 | 37530.54 | 01-JAN-08:10 | 13250.01 | 52454.31 | 31-JAN-12:30 |
February | 6559.86 | 37469.00 | 26-FEB-08:40 | 13431.03 | 52453.29 | 07-FEB-13:00 |
March | 5364.56 | 37588.18 | 26-MAR-07:12 | 14150.19 | 51958.59 | 01-MAR-12:30 |
April | 6512.48 | 37832.50 | 30-APR-07:00 | 12247.52 | 49718.30 | 03-APR-11:40 |
May | 6531.44 | 38057.45 | 29-MAY-06:43 | 11694.58 | 46846.36 | 01-MAY-12:00 |
June | 6060.03 | 38233.64 | 25-JUN-06:35 | 10977.09 | 43467.61 | 01-JUN-12:00 |
July | 7863.74 | 38353.30 | 30-JUL-06:33 | 9218.53 | 40700.27 | 03-JUL-12:00 |
August | 6171.33 | 38358.52 | 06-AUG-06:33 | 10293.95 | 39998.03 | 31-AUG-11:40 |
September | 7092.29 | 38313.79 | 03-SEP-06:35 | 9837.65 | 41924.68 | 29-SEP-12:00 |
October | 7470.21 | 38175.07 | 01-OCT-06:50 | 10680.50 | 45163.14 | 31-OCT-12:00 |
November | 7366.31 | 37919.13 | 05-NOV-06:57 | 11850.07 | 48450.63 | 30-NOV-13:00 |
December | 7097.28 | 37705.13 | 03-DEC-08:20 | 12244.53 | 51011.12 | 29-DEC-12:50 |
Annual Sum or Average | 6753.93 | 11646.41 | ||||
Minimum of Months | 5364.56 | 37469.00 | 9218.53 | 39998.03 | ||
Maximum of Months | 7863.74 | 38358.52 | 14150.19 | 52454.31 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.03 | 73.28 | 11-JAN-15:10 | 90738.10 | 851765.70 | 14-JAN-04:46 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 63563.15 | 854698.62 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 21431.34 | 823375.06 | 03-MAR-04:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4532.26 | 790698.70 | 09-APR-19:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1208.18 | 249721.03 | 14-MAY-19:57 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 221.79 | 224401.79 | 25-JUN-21:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 233.04 | 241912.01 | 23-JUL-14:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 151.13 | 242617.38 | 27-AUG-20:30 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 352.20 | 249225.27 | 10-SEP-13:27 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11431.70 | 482652.45 | 26-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29564.32 | 749795.10 | 27-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 80735.97 | 1218004.26 | 09-DEC-06:01 |
Annual Sum or Average | 0.00 | 25215.61 | ||||
Minimum of Months | 0.00 | 0.00 | 151.13 | 224401.79 | ||
Maximum of Months | 0.03 | 73.28 | 90738.10 | 1218004.26 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7277.64 | 487515.63 | 05-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 27456.20 | 1246347.71 | 13-FEB-16:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 97010.64 | 1247328.62 | 13-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 260873.93 | 1272465.40 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 399724.33 | 1471178.88 | 23-MAY-09:30 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 647747.75 | 1806178.60 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 756530.52 | 1777385.33 | 12-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 736809.37 | 1992159.29 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 541239.72 | 1776588.47 | 05-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 271142.80 | 1420245.28 | 04-OCT-14:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 22747.42 | 941485.30 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1266.11 | 73540.99 | 17-DEC-16:50 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 315916.83 | 0.00 | ||||
Minimum of Months | 1266.11 | 73540.99 | 0.00 | 0.00 | ||
Maximum of Months | 756530.52 | 1992159.29 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3342.99 | 255849.14 | 05-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 17123.66 | 969858.96 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 55593.64 | 992700.72 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 180559.49 | 1273855.45 | 27-APR-14:40 | 0.00 | 0.00 | 01-APR-00:05 |
May | 294010.84 | 1399378.33 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 544548.95 | 1996814.80 | 29-JUN-03:01 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 654393.20 | 2329288.52 | 12-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 631817.28 | 2418248.10 | 15-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 437088.25 | 1775477.47 | 05-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 198467.14 | 1430632.59 | 04-OCT-14:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11419.98 | 536974.44 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.11 | 59587.85 | 17-DEC-16:50 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 253848.11 | 0.00 | ||||
Minimum of Months | 7.11 | 59587.85 | 0.00 | 0.00 | ||
Maximum of Months | 654393.20 | 2418248.10 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 205426.97 | 556131.00 | 13-JAN-23:05 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 369605.78 | 799734.03 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 560850.60 | 1081317.86 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 892521.98 | 1512595.35 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 395824.68 | 1002256.65 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 867405.56 | 1782039.32 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1251795.85 | 2002070.38 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1411024.37 | 2037644.90 | 20-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 477232.68 | 1140896.57 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 494868.64 | 1180156.76 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 525620.42 | 881170.27 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 661742.52 | 769563.33 | 24-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 678520.34 | 0.00 | ||||
Minimum of Months | 205426.97 | 556131.00 | 0.00 | 0.00 | ||
Maximum of Months | 1411024.37 | 2037644.90 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4789.87 | 369470.65 | 05-JAN-16:00 | 781.45 | 90365.71 | 13-JAN-14:00 |
February | 19560.46 | 1031669.93 | 14-FEB-14:35 | 1239.15 | 103656.80 | 24-FEB-06:50 |
March | 71117.17 | 1023490.70 | 13-MAR-15:00 | 735.95 | 77741.45 | 08-MAR-21:10 |
April | 214702.72 | 1797774.33 | 27-APR-14:10 | 989.80 | 87158.36 | 06-APR-11:20 |
May | 347385.42 | 1957531.14 | 19-MAY-16:00 | 196.27 | 78318.06 | 05-MAY-07:50 |
June | 692363.87 | 3180146.41 | 29-JUN-13:00 | 106.26 | 45670.44 | 02-JUN-06:40 |
July | 968026.64 | 4028815.54 | 31-JUL-15:10 | 0.06 | 728.59 | 02-JUL-23:00 |
August | 871045.35 | 4127536.62 | 23-AUG-16:00 | 9.30 | 11346.75 | 25-AUG-04:53 |
September | 545945.99 | 3913652.21 | 05-SEP-13:10 | 60.29 | 36304.60 | 13-SEP-06:00 |
October | 243196.56 | 1953050.43 | 04-OCT-14:40 | 759.33 | 88716.30 | 26-OCT-11:30 |
November | 16394.90 | 670047.12 | 09-NOV-14:10 | 763.17 | 92980.31 | 26-NOV-12:52 |
December | 60.83 | 19618.17 | 06-DEC-11:20 | 2018.48 | 103689.79 | 14-DEC-05:01 |
Annual Sum or Average | 335079.98 | 635.09 | ||||
Minimum of Months | 60.83 | 19618.17 | 0.06 | 728.59 | ||
Maximum of Months | 968026.64 | 4127536.62 | 2018.48 | 103689.79 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.213474E+11 | 1.13 | 12989.81 | 01-JAN-00:11 | 1.84 |
February | 0.191740E+11 | 1.12 | 12989.81 | 01-FEB-04:01 | 1.84 |
March | 0.219291E+11 | 1.16 | 12989.81 | 01-MAR-04:01 | 1.84 |
April | 0.207969E+11 | 1.13 | 12989.81 | 01-APR-03:01 | 1.84 |
May | 0.222554E+11 | 1.17 | 12989.81 | 01-MAY-00:05 | 1.84 |
June | 0.220050E+11 | 1.19 | 12989.81 | 01-JUN-03:01 | 1.82 |
July | 0.224327E+11 | 1.17 | 12989.81 | 01-JUL-03:01 | 1.81 |
August | 0.236981E+11 | 1.23 | 12989.81 | 01-AUG-03:01 | 1.82 |
September | 0.223638E+11 | 1.21 | 12989.81 | 01-SEP-03:01 | 1.82 |
October | 0.231406E+11 | 1.22 | 12989.81 | 01-OCT-08:00 | 1.82 |
November | 0.219921E+11 | 1.20 | 12989.81 | 01-NOV-03:01 | 1.82 |
December | 0.220125E+11 | 1.16 | 12989.81 | 01-DEC-04:01 | 1.84 |
Annual Sum or Average | 0.263148E+12 | 1.17 | |||
Minimum of Months | 0.191740E+11 | 1.12 | 12989.81 | 1.81 | |
Maximum of Months | 0.236981E+11 | 1.23 | 12989.81 | 1.84 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.735063E+10 | 0.47 | 13664.79 | 17-JAN-06:01 | 1.49 |
February | 0.756459E+10 | 0.51 | 13664.79 | 06-FEB-06:01 | 1.50 |
March | 0.959268E+10 | 0.57 | 16823.48 | 25-MAR-05:01 | 1.70 |
April | 0.102508E+11 | 0.63 | 19225.06 | 03-APR-05:03 | 1.85 |
May | 0.805646E+10 | 0.53 | 26619.79 | 19-MAY-05:01 | 2.26 |
June | 0.906298E+10 | 0.60 | 26619.79 | 22-JUN-05:01 | 2.25 |
July | 0.969505E+10 | 0.63 | 26619.79 | 06-JUL-05:01 | 2.25 |
August | 0.117146E+11 | 0.72 | 26619.79 | 04-AUG-05:01 | 2.24 |
September | 0.795466E+10 | 0.53 | 26619.79 | 01-SEP-05:01 | 2.25 |
October | 0.927851E+10 | 0.55 | 25133.45 | 11-OCT-05:01 | 2.16 |
November | 0.101026E+11 | 0.58 | 17593.67 | 03-NOV-03:01 | 1.74 |
December | 0.101893E+11 | 0.56 | 16112.45 | 26-DEC-15:50 | 1.65 |
Annual Sum or Average | 0.110813E+12 | 0.57 | |||
Minimum of Months | 0.735063E+10 | 0.47 | 13664.79 | 1.49 | |
Maximum of Months | 0.117146E+11 | 0.72 | 26619.79 | 2.26 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.537103E+11 | 0.42 | 164378.70 | 11-JAN-06:01 | 1.75 |
February | 0.520119E+11 | 0.43 | 164378.70 | 01-FEB-06:01 | 1.75 |
March | 0.622024E+11 | 0.46 | 164378.70 | 04-MAR-06:01 | 1.75 |
April | 0.626169E+11 | 0.47 | 126768.56 | 29-APR-05:01 | 1.49 |
May | 0.654506E+11 | 0.48 | 190401.93 | 19-MAY-05:01 | 1.91 |
June | 0.732224E+11 | 0.53 | 247682.39 | 13-JUN-05:01 | 2.26 |
July | 0.738254E+11 | 0.52 | 247682.39 | 07-JUL-05:01 | 2.24 |
August | 0.783953E+11 | 0.54 | 247682.39 | 02-AUG-05:01 | 2.25 |
September | 0.659949E+11 | 0.49 | 211481.43 | 12-SEP-05:01 | 2.03 |
October | 0.672470E+11 | 0.48 | 166872.93 | 07-OCT-05:01 | 1.75 |
November | 0.633099E+11 | 0.46 | 153905.47 | 25-NOV-06:01 | 1.68 |
December | 0.566842E+11 | 0.43 | 164378.70 | 08-DEC-06:01 | 1.75 |
Annual Sum or Average | 0.774671E+12 | 0.48 | |||
Minimum of Months | 0.520119E+11 | 0.42 | 126768.56 | 1.49 | |
Maximum of Months | 0.783953E+11 | 0.54 | 247682.39 | 2.26 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.441907E+10 | 0.40 | 6270.73 | 26-JAN-16:40 | 0.95 |
February | 0.418207E+10 | 0.40 | 7734.32 | 15-FEB-16:30 | 1.06 |
March | 0.493673E+10 | 0.41 | 6950.03 | 30-MAR-15:50 | 1.00 |
April | 0.553277E+10 | 0.42 | 11841.20 | 11-APR-05:01 | 1.36 |
May | 0.642117E+10 | 0.46 | 21336.46 | 19-MAY-05:01 | 1.95 |
June | 0.811464E+10 | 0.53 | 26939.53 | 22-JUN-05:01 | 2.25 |
July | 0.855663E+10 | 0.53 | 26939.53 | 07-JUL-05:01 | 2.24 |
August | 0.876210E+10 | 0.54 | 26939.53 | 07-AUG-03:01 | 2.24 |
September | 0.666813E+10 | 0.46 | 15989.81 | 12-SEP-05:01 | 1.61 |
October | 0.560548E+10 | 0.41 | 17115.21 | 07-OCT-05:01 | 1.69 |
November | 0.464289E+10 | 0.40 | 11841.20 | 01-NOV-05:01 | 1.35 |
December | 0.437147E+10 | 0.39 | 6029.35 | 29-DEC-16:30 | 0.92 |
Annual Sum or Average | 0.722131E+11 | 0.45 | |||
Minimum of Months | 0.418207E+10 | 0.39 | 6029.35 | 0.92 | |
Maximum of Months | 0.876210E+10 | 0.54 | 26939.53 | 2.25 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114550E+12 | 1.63 | 42768.14 | 01-JAN-00:01 | 1.63 |
February | 0.103465E+12 | 1.63 | 42768.14 | 01-FEB-00:10 | 1.63 |
March | 0.114550E+12 | 1.63 | 42768.14 | 01-MAR-00:03 | 1.63 |
April | 0.110855E+12 | 1.63 | 42768.14 | 01-APR-00:05 | 1.63 |
May | 0.114550E+12 | 1.63 | 42768.14 | 01-MAY-00:03 | 1.63 |
June | 0.110855E+12 | 1.63 | 42768.14 | 01-JUN-00:10 | 1.63 |
July | 0.114550E+12 | 1.63 | 42768.14 | 01-JUL-00:05 | 1.63 |
August | 0.114550E+12 | 1.63 | 42768.14 | 01-AUG-00:01 | 1.63 |
September | 0.110855E+12 | 1.63 | 42768.14 | 01-SEP-00:02 | 1.63 |
October | 0.114550E+12 | 1.63 | 42768.14 | 01-OCT-00:10 | 1.63 |
November | 0.110855E+12 | 1.63 | 42768.14 | 01-NOV-00:10 | 1.63 |
December | 0.114550E+12 | 1.63 | 42768.14 | 01-DEC-00:05 | 1.63 |
Annual Sum or Average | 0.134874E+13 | 1.63 | |||
Minimum of Months | 0.103465E+12 | 1.63 | 42768.14 | 1.63 | |
Maximum of Months | 0.114550E+12 | 1.63 | 42768.14 | 1.63 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173437E+10 | 1.12 | 647.54 | 01-JAN-00:01 | 1.12 |
February | 0.156653E+10 | 1.12 | 647.54 | 01-FEB-00:10 | 1.12 |
March | 0.173437E+10 | 1.12 | 647.54 | 01-MAR-00:03 | 1.12 |
April | 0.167842E+10 | 1.12 | 647.54 | 01-APR-00:05 | 1.12 |
May | 0.173437E+10 | 1.12 | 647.54 | 01-MAY-00:03 | 1.12 |
June | 0.167842E+10 | 1.12 | 647.54 | 01-JUN-00:10 | 1.12 |
July | 0.173437E+10 | 1.12 | 647.54 | 01-JUL-00:05 | 1.12 |
August | 0.173437E+10 | 1.12 | 647.54 | 01-AUG-00:01 | 1.12 |
September | 0.167842E+10 | 1.12 | 647.54 | 01-SEP-00:03 | 1.12 |
October | 0.173437E+10 | 1.12 | 647.54 | 01-OCT-00:10 | 1.12 |
November | 0.167842E+10 | 1.12 | 647.54 | 01-NOV-00:10 | 1.12 |
December | 0.173437E+10 | 1.12 | 647.54 | 01-DEC-00:05 | 1.12 |
Annual Sum or Average | 0.204208E+11 | 1.12 | |||
Minimum of Months | 0.156653E+10 | 1.12 | 647.54 | 1.12 | |
Maximum of Months | 0.173437E+10 | 1.12 | 647.54 | 1.12 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165459E+11 | 1.12 | 6177.52 | 01-JAN-00:01 | 1.12 |
February | 0.149447E+11 | 1.12 | 6177.52 | 01-FEB-00:10 | 1.12 |
March | 0.165459E+11 | 1.12 | 6177.52 | 01-MAR-00:03 | 1.12 |
April | 0.160121E+11 | 1.12 | 6177.52 | 01-APR-00:05 | 1.12 |
May | 0.165459E+11 | 1.12 | 6177.52 | 01-MAY-00:03 | 1.12 |
June | 0.160121E+11 | 1.12 | 6177.52 | 01-JUN-00:10 | 1.12 |
July | 0.165459E+11 | 1.12 | 6177.52 | 01-JUL-00:05 | 1.12 |
August | 0.165459E+11 | 1.12 | 6177.52 | 01-AUG-00:01 | 1.12 |
September | 0.160121E+11 | 1.12 | 6177.52 | 01-SEP-00:02 | 1.12 |
October | 0.165459E+11 | 1.12 | 6177.52 | 01-OCT-00:10 | 1.12 |
November | 0.160121E+11 | 1.12 | 6177.52 | 01-NOV-00:10 | 1.12 |
December | 0.165459E+11 | 1.12 | 6177.52 | 01-DEC-00:05 | 1.12 |
Annual Sum or Average | 0.194814E+12 | 1.12 | |||
Minimum of Months | 0.149447E+11 | 1.12 | 6177.52 | 1.12 | |
Maximum of Months | 0.165459E+11 | 1.12 | 6177.52 | 1.12 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169574E+10 | 1.12 | 633.12 | 01-JAN-00:01 | 1.12 |
February | 0.153163E+10 | 1.12 | 633.12 | 01-FEB-00:10 | 1.12 |
March | 0.169574E+10 | 1.12 | 633.12 | 01-MAR-00:03 | 1.12 |
April | 0.164104E+10 | 1.12 | 633.12 | 01-APR-00:05 | 1.12 |
May | 0.169574E+10 | 1.12 | 633.12 | 01-MAY-00:03 | 1.12 |
June | 0.164104E+10 | 1.12 | 633.12 | 01-JUN-00:10 | 1.12 |
July | 0.169574E+10 | 1.12 | 633.12 | 01-JUL-00:05 | 1.12 |
August | 0.169574E+10 | 1.12 | 633.12 | 01-AUG-00:01 | 1.12 |
September | 0.164104E+10 | 1.12 | 633.12 | 01-SEP-00:02 | 1.12 |
October | 0.169574E+10 | 1.12 | 633.12 | 01-OCT-00:10 | 1.12 |
November | 0.164104E+10 | 1.12 | 633.12 | 01-NOV-00:10 | 1.12 |
December | 0.169574E+10 | 1.12 | 633.12 | 01-DEC-00:05 | 1.12 |
Annual Sum or Average | 0.199659E+11 | 1.12 | |||
Minimum of Months | 0.153163E+10 | 1.12 | 633.12 | 1.12 | |
Maximum of Months | 0.169574E+10 | 1.12 | 633.12 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.324356E+10 | 0.291921E+10 | 9360.27 | 30-JAN-06:01 | 8424.24 | 8424.24 | 73.21 | 16.20 |
February | 0.182409E+10 | 0.164168E+10 | 8762.64 | 06-FEB-06:01 | 7886.38 | 7886.38 | 69.89 | 14.60 |
March | 0.595774E+09 | 0.536197E+09 | 7101.28 | 04-MAR-06:01 | 6391.16 | 6391.16 | 66.82 | 10.80 |
April | 0.106087E+09 | 95477872.26 | 11220.74 | 05-APR-18:30 | 10098.67 | 10098.67 | 75.03 | 22.86 |
May | 0.123876E+09 | 0.111488E+09 | 4711.09 | 29-MAY-20:20 | 4239.98 | 4239.98 | 75.64 | 6.43 |
June | 13926073.62 | 12533466.26 | 4716.69 | 11-JUN-18:22 | 4245.02 | 4245.02 | 77.91 | 6.43 |
July | 12348903.29 | 11114012.96 | 4706.17 | 02-JUL-13:30 | 4235.56 | 4235.56 | 73.59 | 6.43 |
August | 7895269.43 | 7105742.49 | 4705.04 | 20-AUG-13:13 | 4234.53 | 4234.53 | 73.11 | 6.43 |
September | 17550679.65 | 15795611.69 | 4704.96 | 03-SEP-13:16 | 4234.46 | 4234.46 | 73.08 | 6.43 |
October | 0.436582E+09 | 0.392924E+09 | 5039.58 | 26-OCT-06:55 | 4535.62 | 4535.62 | 65.55 | 7.00 |
November | 0.778011E+09 | 0.700210E+09 | 7397.82 | 27-NOV-06:03 | 6658.04 | 6658.04 | 67.66 | 11.42 |
December | 0.193183E+10 | 0.173865E+10 | 7987.14 | 22-DEC-06:01 | 7188.42 | 7188.42 | 59.60 | 12.78 |
Annual Sum or Average | 0.909153E+10 | 0.818238E+10 | ||||||
Minimum of Months | 7895269.43 | 7105742.49 | 4704.96 | 4234.46 | 4234.46 | 59.60 | 6.43 | |
Maximum of Months | 0.324356E+10 | 0.291921E+10 | 11220.74 | 10098.67 | 10098.67 | 77.91 | 22.86 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.185674E+09 | 0.167107E+09 | 4833.96 | 05-JAN-16:00 | 4350.57 | 4350.57 | 7.45 | 6.91 |
February | 0.649355E+09 | 0.584420E+09 | 12373.02 | 14-FEB-16:00 | 11135.72 | 11135.72 | 7.34 | 22.77 |
March | 0.245392E+10 | 0.220853E+10 | 12367.38 | 08-MAR-16:00 | 11130.65 | 11130.65 | 7.35 | 22.76 |
April | 0.650657E+10 | 0.585591E+10 | 14085.33 | 27-APR-16:00 | 12676.80 | 12676.80 | 7.18 | 28.42 |
May | 0.107629E+11 | 0.968663E+10 | 18140.78 | 23-MAY-10:40 | 16326.70 | 16326.70 | 6.79 | 57.37 |
June | 0.182240E+11 | 0.164016E+11 | 19480.41 | 29-JUN-14:20 | 17532.37 | 17532.37 | 6.76 | 74.40 |
July | 0.235291E+11 | 0.211762E+11 | 19348.45 | 12-JUL-05:02 | 17413.61 | 17413.61 | 7.43 | 73.12 |
August | 0.236549E+11 | 0.212894E+11 | 19411.63 | 15-AUG-05:02 | 17470.47 | 17470.47 | 7.46 | 73.74 |
September | 0.166131E+11 | 0.149518E+11 | 18606.52 | 13-SEP-10:20 | 16745.87 | 16745.87 | 6.95 | 64.17 |
October | 0.787671E+10 | 0.708903E+10 | 18266.38 | 04-OCT-15:30 | 16439.75 | 16439.75 | 6.77 | 59.21 |
November | 0.575649E+09 | 0.518084E+09 | 8176.03 | 09-NOV-14:00 | 7358.42 | 7358.42 | 7.94 | 12.82 |
December | 465205.46 | 418684.92 | 1436.43 | 17-DEC-16:50 | 1292.79 | 1292.79 | 7.14 | 1.90 |
Annual Sum or Average | 0.111032E+12 | 0.999292E+11 | ||||||
Minimum of Months | 465205.46 | 418684.92 | 1436.43 | 1292.79 | 1292.79 | 6.76 | 1.90 | |
Maximum of Months | 0.236549E+11 | 0.212894E+11 | 19480.41 | 17532.37 | 17532.37 | 7.94 | 74.40 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 73.95 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 61.40 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 62.12 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 61.48 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 77.92 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 62.53 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 63.79 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 64.57 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 63.18 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 75.96 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 63.05 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 61.70 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 61.40 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 77.92 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.136117E+10 | 0.122505E+10 | 7690.63 | 01-JAN-12:35 | 6921.57 | 6921.57 | 6.76 | 96.32 |
February | 0.207151E+10 | 0.186436E+10 | 7690.63 | 02-FEB-06:01 | 6921.57 | 6921.57 | 6.73 | 96.32 |
March | 0.454304E+10 | 0.408873E+10 | 7690.63 | 01-MAR-14:40 | 6921.57 | 6921.57 | 6.74 | 96.32 |
April | 0.842067E+10 | 0.757861E+10 | 7690.63 | 01-APR-03:01 | 6921.57 | 6921.57 | 6.79 | 96.32 |
May | 0.105454E+11 | 0.949082E+10 | 7690.63 | 01-MAY-00:31 | 6921.57 | 6921.57 | 6.77 | 96.32 |
June | 0.144672E+11 | 0.130205E+11 | 7690.63 | 01-JUN-03:01 | 6921.57 | 6921.57 | 9.08 | 96.32 |
July | 0.168732E+11 | 0.151859E+11 | 7690.63 | 01-JUL-00:05 | 6921.57 | 6921.57 | 6.94 | 96.32 |
August | 0.181372E+11 | 0.163235E+11 | 7690.63 | 01-AUG-00:01 | 6921.57 | 6921.57 | 7.04 | 96.32 |
September | 0.125086E+11 | 0.112577E+11 | 7690.63 | 01-SEP-00:02 | 6921.57 | 6921.57 | 6.94 | 96.32 |
October | 0.854529E+10 | 0.769076E+10 | 7690.63 | 01-OCT-06:51 | 6921.57 | 6921.57 | 8.08 | 96.32 |
November | 0.209920E+10 | 0.188928E+10 | 7690.63 | 01-NOV-03:01 | 6921.57 | 6921.57 | 7.30 | 96.32 |
December | 0.187737E+10 | 0.168963E+10 | 7690.63 | 01-DEC-06:01 | 6921.57 | 6921.57 | 6.73 | 96.32 |
Annual Sum or Average | 0.101450E+12 | 0.913048E+11 | ||||||
Minimum of Months | 0.136117E+10 | 0.122505E+10 | 7690.63 | 6921.57 | 6921.57 | 6.73 | 96.32 | |
Maximum of Months | 0.181372E+11 | 0.163235E+11 | 7690.63 | 6921.57 | 6921.57 | 9.08 | 96.32 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-JAN-00:01 | 3329.13 | 3329.13 | 24.33 | 15.45 |
February | 0.894871E+10 | 0.805384E+10 | 3699.04 | 01-FEB-00:10 | 3329.13 | 3329.13 | 24.39 | 15.45 |
March | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-MAR-00:03 | 3329.13 | 3329.13 | 26.40 | 15.45 |
April | 0.958790E+10 | 0.862911E+10 | 3699.04 | 01-APR-00:05 | 3329.13 | 3329.13 | 30.04 | 15.45 |
May | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-MAY-00:03 | 3329.13 | 3329.13 | 28.35 | 15.45 |
June | 0.958790E+10 | 0.862911E+10 | 3699.04 | 01-JUN-00:10 | 3329.13 | 3329.13 | 27.82 | 15.45 |
July | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-JUL-00:05 | 3329.13 | 3329.13 | 35.59 | 15.45 |
August | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-AUG-00:01 | 3329.13 | 3329.13 | 37.56 | 15.45 |
September | 0.958790E+10 | 0.862911E+10 | 3699.04 | 01-SEP-00:02 | 3329.13 | 3329.13 | 38.51 | 15.45 |
October | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-OCT-00:10 | 3329.13 | 3329.13 | 26.68 | 15.45 |
November | 0.958790E+10 | 0.862911E+10 | 3699.04 | 01-NOV-00:10 | 3329.13 | 3329.13 | 27.49 | 15.45 |
December | 0.990750E+10 | 0.891675E+10 | 3699.04 | 01-DEC-00:05 | 3329.13 | 3329.13 | 30.63 | 15.45 |
Annual Sum or Average | 0.116653E+12 | 0.104988E+12 | ||||||
Minimum of Months | 0.894871E+10 | 0.805384E+10 | 3699.04 | 3329.13 | 3329.13 | 24.33 | 15.45 | |
Maximum of Months | 0.990750E+10 | 0.891675E+10 | 3699.04 | 3329.13 | 3329.13 | 38.51 | 15.45 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.256189E+10 | 0.230570E+10 | 14488.26 | 05-JAN-16:00 | 13039.43 | 13039.43 | 22.66 | 56.84 |
February | 0.395217E+10 | 0.355695E+10 | 28989.55 | 14-FEB-14:35 | 26090.60 | 26090.60 | 23.27 | 113.67 |
March | 0.863540E+10 | 0.777186E+10 | 28989.19 | 13-MAR-15:00 | 26090.28 | 26090.28 | 23.25 | 113.67 |
April | 0.174679E+11 | 0.157211E+11 | 29023.13 | 27-APR-14:10 | 26120.81 | 26120.81 | 24.88 | 113.67 |
May | 0.233102E+11 | 0.209791E+11 | 29030.90 | 19-MAY-16:00 | 26127.81 | 26127.81 | 25.22 | 113.67 |
June | 0.364664E+11 | 0.328198E+11 | 29093.62 | 29-JUN-13:00 | 26184.26 | 26184.26 | 27.79 | 113.67 |
July | 0.438088E+11 | 0.394279E+11 | 29118.41 | 31-JUL-14:30 | 26206.57 | 26206.57 | 28.90 | 113.67 |
August | 0.456277E+11 | 0.410649E+11 | 29118.41 | 23-AUG-15:20 | 26206.57 | 26206.57 | 29.25 | 113.67 |
September | 0.302397E+11 | 0.272157E+11 | 29118.41 | 05-SEP-12:50 | 26206.57 | 26206.57 | 29.00 | 113.67 |
October | 0.184307E+11 | 0.165876E+11 | 29030.67 | 04-OCT-14:40 | 26127.61 | 26127.61 | 25.21 | 113.67 |
November | 0.395201E+10 | 0.355681E+10 | 14501.45 | 09-NOV-14:10 | 13051.31 | 13051.31 | 23.92 | 56.84 |
December | 0.353257E+10 | 0.317931E+10 | 14472.92 | 06-DEC-11:20 | 13025.63 | 13025.63 | 21.18 | 56.84 |
Annual Sum or Average | 0.237985E+12 | 0.214187E+12 | ||||||
Minimum of Months | 0.256189E+10 | 0.230570E+10 | 14472.92 | 13025.63 | 13025.63 | 21.18 | 56.84 | |
Maximum of Months | 0.456277E+11 | 0.410649E+11 | 29118.41 | 26206.57 | 26206.57 | 29.25 | 113.67 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6939.37 | 37530.54 | 01-JAN-08:10 | 80.31 | 82.22 | 13250.01 | 52454.31 | 31-JAN-12:30 |
February | 6559.86 | 37469.00 | 26-FEB-08:40 | 80.28 | 82.22 | 13431.03 | 52453.29 | 07-FEB-13:00 |
March | 5364.56 | 37588.18 | 26-MAR-07:12 | 80.34 | 82.22 | 14150.19 | 51958.59 | 01-MAR-12:30 |
April | 6512.48 | 37832.50 | 30-APR-07:00 | 80.47 | 82.22 | 12247.52 | 49718.30 | 03-APR-11:40 |
May | 6531.44 | 38057.45 | 29-MAY-06:43 | 80.59 | 82.22 | 11694.58 | 46846.36 | 01-MAY-12:00 |
June | 6060.03 | 38233.64 | 25-JUN-06:35 | 80.69 | 82.22 | 10977.09 | 43467.61 | 01-JUN-12:00 |
July | 7863.74 | 38353.30 | 30-JUL-06:33 | 80.75 | 82.22 | 9218.53 | 40700.27 | 03-JUL-12:00 |
August | 6171.33 | 38358.52 | 06-AUG-06:33 | 80.76 | 82.22 | 10293.95 | 39998.03 | 31-AUG-11:40 |
September | 7092.29 | 38313.79 | 03-SEP-06:35 | 80.73 | 82.22 | 9837.65 | 41924.68 | 29-SEP-12:00 |
October | 7470.21 | 38175.07 | 01-OCT-06:50 | 80.66 | 82.22 | 10680.50 | 45163.14 | 31-OCT-12:00 |
November | 7366.31 | 37919.13 | 05-NOV-06:57 | 80.52 | 82.22 | 11850.07 | 48450.63 | 30-NOV-13:00 |
December | 7097.28 | 37705.13 | 03-DEC-08:20 | 80.40 | 82.22 | 12244.53 | 51011.12 | 29-DEC-12:50 |
Annual Sum or Average | 6753.93 | 11646.41 | ||||||
Minimum of Months | 5364.56 | 37469.00 | 80.28 | 82.22 | 9218.53 | 39998.03 | ||
Maximum of Months | 7863.74 | 38358.52 | 80.76 | 82.22 | 14150.19 | 52454.31 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.03 | 73.28 | 11-JAN-15:10 | 82.01 | 82.01 | 90738.10 | 851765.70 | 14-JAN-04:46 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 62.46 | 62.46 | 63563.15 | 854698.62 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 56.53 | 56.53 | 21431.34 | 823375.06 | 03-MAR-04:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 58.37 | 58.37 | 4532.26 | 790698.70 | 09-APR-19:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 73.50 | 73.50 | 1208.18 | 249721.03 | 14-MAY-19:57 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 75.01 | 75.01 | 221.79 | 224401.79 | 25-JUN-21:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 73.62 | 73.62 | 233.04 | 241912.01 | 23-JUL-14:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 73.02 | 73.02 | 151.13 | 242617.38 | 27-AUG-20:30 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 72.97 | 72.97 | 352.20 | 249225.27 | 10-SEP-13:27 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 72.90 | 72.90 | 11431.70 | 482652.45 | 26-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 75.45 | 75.45 | 29564.32 | 749795.10 | 27-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 53.70 | 53.70 | 80735.97 | 1218004.26 | 09-DEC-06:01 |
Annual Sum or Average | 0.00 | 25215.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 53.70 | 53.70 | 151.13 | 224401.79 | ||
Maximum of Months | 0.03 | 73.28 | 82.01 | 82.01 | 90738.10 | 1218004.26 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7277.64 | 487515.63 | 05-JAN-16:00 | 7.91 | 7.30 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 27456.20 | 1246347.71 | 13-FEB-16:20 | 9.79 | 8.12 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 97010.64 | 1247328.62 | 13-MAR-15:00 | 9.79 | 8.12 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 260873.93 | 1272465.40 | 27-APR-16:00 | 9.85 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 399724.33 | 1471178.88 | 23-MAY-09:30 | 10.34 | 8.10 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 647747.75 | 1806178.60 | 28-JUN-16:00 | 11.18 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 756530.52 | 1777385.33 | 12-JUL-05:03 | 11.10 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 736809.37 | 1992159.29 | 14-AUG-05:02 | 11.64 | 6.70 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 541239.72 | 1776588.47 | 05-SEP-13:00 | 11.10 | 6.70 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 271142.80 | 1420245.28 | 04-OCT-14:40 | 10.22 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 22747.42 | 941485.30 | 09-NOV-14:00 | 9.03 | 7.86 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1266.11 | 73540.99 | 17-DEC-16:50 | 6.88 | 6.79 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 315916.83 | 0.00 | ||||||
Minimum of Months | 1266.11 | 73540.99 | 6.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 756530.52 | 1992159.29 | 11.64 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3342.99 | 255849.14 | 05-JAN-16:00 | 15.55 | 7.30 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 17123.66 | 969858.96 | 14-FEB-16:00 | 16.88 | 7.87 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 55593.64 | 992700.72 | 08-MAR-16:00 | 17.13 | 7.90 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 180559.49 | 1273855.45 | 27-APR-14:40 | 17.52 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 294010.84 | 1399378.33 | 19-MAY-16:00 | 18.36 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 544548.95 | 1996814.80 | 29-JUN-03:01 | 14.37 | 7.18 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 654393.20 | 2329288.52 | 12-JUL-05:02 | 14.31 | 7.11 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 631817.28 | 2418248.10 | 15-AUG-05:02 | 14.53 | 7.16 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 437088.25 | 1775477.47 | 05-SEP-13:00 | 15.41 | 6.70 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 198467.14 | 1430632.59 | 04-OCT-14:40 | 12.71 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11419.98 | 536974.44 | 09-NOV-14:00 | 16.71 | 7.82 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.11 | 59587.85 | 17-DEC-16:50 | 14.19 | 6.77 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 253848.11 | 0.00 | ||||||
Minimum of Months | 7.11 | 59587.85 | 12.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 654393.20 | 2418248.10 | 18.36 | 7.90 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 205426.97 | 556131.00 | 13-JAN-23:05 | 28.62 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 369605.78 | 799734.03 | 14-FEB-16:00 | 33.07 | 26.13 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 560850.60 | 1081317.86 | 08-MAR-16:00 | 38.17 | 28.38 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 892521.98 | 1512595.35 | 13-APR-17:00 | 45.87 | 33.33 | 0.00 | 0.00 | 01-APR-00:05 |
May | 395824.68 | 1002256.65 | 19-MAY-16:00 | 36.74 | 32.44 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 867405.56 | 1782039.32 | 28-JUN-16:00 | 50.63 | 43.21 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1251795.85 | 2002070.38 | 22-JUL-15:00 | 54.50 | 44.27 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1411024.37 | 2037644.90 | 20-AUG-16:00 | 55.12 | 42.42 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 477232.68 | 1140896.57 | 03-SEP-14:00 | 39.24 | 35.14 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 494868.64 | 1180156.76 | 01-OCT-16:00 | 39.94 | 32.91 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 525620.42 | 881170.27 | 09-NOV-14:00 | 34.55 | 24.88 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 661742.52 | 769563.33 | 24-DEC-15:00 | 32.52 | 20.24 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 678520.34 | 0.00 | ||||||
Minimum of Months | 205426.97 | 556131.00 | 28.62 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1411024.37 | 2037644.90 | 55.12 | 44.27 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4789.87 | 369470.65 | 05-JAN-16:00 | 22.66 | 21.36 | 781.45 | 90365.71 | 13-JAN-14:00 |
February | 19560.46 | 1031669.93 | 14-FEB-14:35 | 23.27 | 22.37 | 1239.15 | 103656.80 | 24-FEB-06:50 |
March | 71117.17 | 1023490.70 | 13-MAR-15:00 | 23.25 | 22.36 | 735.95 | 77741.45 | 08-MAR-21:10 |
April | 214702.72 | 1797774.33 | 27-APR-14:10 | 24.88 | 21.74 | 989.80 | 87158.36 | 06-APR-11:20 |
May | 347385.42 | 1957531.14 | 19-MAY-16:00 | 25.22 | 21.80 | 196.27 | 78318.06 | 05-MAY-07:50 |
June | 692363.87 | 3180146.41 | 29-JUN-13:00 | 27.79 | 23.86 | 106.26 | 45670.44 | 02-JUN-06:40 |
July | 968026.64 | 4028815.54 | 31-JUL-15:10 | 29.58 | 25.36 | 0.06 | 728.59 | 02-JUL-23:00 |
August | 871045.35 | 4127536.62 | 23-AUG-16:00 | 29.79 | 25.22 | 9.30 | 11346.75 | 25-AUG-04:53 |
September | 545945.99 | 3913652.21 | 05-SEP-13:10 | 29.34 | 24.92 | 60.29 | 36304.60 | 13-SEP-06:00 |
October | 243196.56 | 1953050.43 | 04-OCT-14:40 | 25.21 | 21.79 | 759.33 | 88716.30 | 26-OCT-11:30 |
November | 16394.90 | 670047.12 | 09-NOV-14:10 | 23.92 | 21.58 | 763.17 | 92980.31 | 26-NOV-12:52 |
December | 60.83 | 19618.17 | 06-DEC-11:20 | 21.18 | 20.49 | 2018.48 | 103689.79 | 14-DEC-05:01 |
Annual Sum or Average | 335079.98 | 635.09 | ||||||
Minimum of Months | 60.83 | 19618.17 | 21.18 | 20.49 | 0.06 | 728.59 | ||
Maximum of Months | 968026.64 | 4127536.62 | 29.79 | 25.36 | 2018.48 | 103689.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.29 | 7.48 |
February | 1.26 | 7.48 |
March | 1.36 | 7.48 |
April | 1.24 | 7.48 |
May | 1.71 | 7.48 |
June | 0.88 | 7.48 |
July | 0.58 | 6.77 |
August | 0.71 | 7.48 |
September | 1.25 | 7.48 |
October | 0.94 | 7.48 |
November | 0.22 | 7.48 |
December | 1.69 | 7.48 |
Annual Sum or Average | 13.13 | 7.45 |
Minimum of Months | 0.22 | 6.77 |
Maximum of Months | 1.71 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.27 | 9.61 |
February | 1.61 | 7.45 |
March | 2.18 | 4.74 |
April | 8.51 | 3.06 |
May | 3.03 | 3.62 |
June | 5.91 | 2.06 |
July | 8.63 | 1.69 |
August | 5.40 | 1.91 |
September | 3.28 | 3.63 |
October | 2.17 | 3.82 |
November | 1.50 | 4.73 |
December | 2.56 | 5.76 |
Annual Sum or Average | 46.05 | 3.27 |
Minimum of Months | 1.27 | 1.69 |
Maximum of Months | 8.63 | 9.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.64 | 9.64 |
February | 1.00 | 7.46 |
March | 2.03 | 10.76 |
April | 2.17 | 8.74 |
May | 1.71 | 5.83 |
June | 2.27 | 2.75 |
July | 2.43 | 3.76 |
August | 1.25 | 2.07 |
September | 1.53 | 2.67 |
October | 1.91 | 6.99 |
November | 1.46 | 11.18 |
December | 1.52 | 8.08 |
Annual Sum or Average | 19.92 | 6.45 |
Minimum of Months | 0.64 | 2.07 |
Maximum of Months | 2.43 | 11.18 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.00 |
February | 0.29 | 6.72 |
March | 0.84 | 5.61 |
April | 0.69 | 7.53 |
May | 0.97 | 4.94 |
June | 1.43 | 4.86 |
July | 1.76 | 3.44 |
August | 0.94 | 3.10 |
September | 1.04 | 4.75 |
October | 0.46 | 6.23 |
November | 0.24 | 3.56 |
December | 0.22 | 1.68 |
Annual Sum or Average | 8.93 | 4.65 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 1.76 | 7.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.11 | 0.42 |
February | 0.06 | 0.84 |
March | 0.58 | 0.05 |
April | 2.24 | 0.39 |
May | 1.22 | 0.32 |
June | 3.95 | 0.25 |
July | 6.94 | 0.21 |
August | 3.40 | 0.33 |
September | 1.50 | 0.31 |
October | 0.71 | 0.23 |
November | 0.19 | 0.96 |
December | 0.11 | 0.00 |
Annual Sum or Average | 21.00 | 0.28 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 6.94 | 0.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.22 | 0.53 |
February | 2.36 | 0.47 |
March | 3.02 | 0.27 |
April | 8.64 | 0.26 |
May | 6.06 | 0.23 |
June | 13.03 | 0.17 |
July | 14.48 | 0.16 |
August | 8.69 | 0.19 |
September | 6.84 | 0.21 |
October | 4.79 | 0.35 |
November | 2.48 | 0.44 |
December | 2.43 | 0.36 |
Annual Sum or Average | 74.04 | 0.24 |
Minimum of Months | 1.22 | 0.16 |
Maximum of Months | 14.48 | 0.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.27 | 0.67 |
February | 0.51 | 0.84 |
March | 1.06 | 0.22 |
April | 3.18 | 0.33 |
May | 1.33 | 0.28 |
June | 4.99 | 0.27 |
July | 7.49 | 0.22 |
August | 4.55 | 0.30 |
September | 2.36 | 0.27 |
October | 0.88 | 0.24 |
November | 0.55 | 0.58 |
December | 0.47 | 0.35 |
Annual Sum or Average | 27.64 | 0.29 |
Minimum of Months | 0.27 | 0.22 |
Maximum of Months | 7.49 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.14 | 0.46 |
February | 3.36 | 0.43 |
March | 5.21 | 0.26 |
April | 17.01 | 0.24 |
May | 7.09 | 0.23 |
June | 15.31 | 0.18 |
July | 25.45 | 0.19 |
August | 23.30 | 0.15 |
September | 7.28 | 0.24 |
October | 4.64 | 0.29 |
November | 3.18 | 0.32 |
December | 5.69 | 0.37 |
Annual Sum or Average | 118.68 | 0.22 |
Minimum of Months | 1.14 | 0.15 |
Maximum of Months | 25.45 | 0.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.04 | 0.84 |
February | 0.00 | 0.00 |
March | 0.10 | 0.00 |
April | 0.42 | 0.34 |
May | 1.16 | 0.35 |
June | 1.19 | 0.24 |
July | 1.64 | 0.32 |
August | 1.16 | 0.15 |
September | 0.83 | 0.18 |
October | 0.43 | 0.22 |
November | 0.06 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.02 | 0.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.64 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.79 | 0.54 |
February | 1.74 | 0.53 |
March | 1.87 | 0.44 |
April | 3.38 | 0.33 |
May | 5.20 | 0.32 |
June | 5.79 | 0.23 |
July | 7.75 | 0.24 |
August | 5.88 | 0.18 |
September | 5.80 | 0.25 |
October | 3.12 | 0.51 |
November | 1.60 | 0.71 |
December | 0.81 | 0.54 |
Annual Sum or Average | 43.73 | 0.32 |
Minimum of Months | 0.79 | 0.18 |
Maximum of Months | 7.75 | 0.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.84 |
February | 0.52 | 0.84 |
March | 0.51 | 0.39 |
April | 0.96 | 0.28 |
May | 1.46 | 0.30 |
June | 1.40 | 0.25 |
July | 1.94 | 0.34 |
August | 1.41 | 0.18 |
September | 1.76 | 0.32 |
October | 0.91 | 0.30 |
November | 0.34 | 0.55 |
December | 0.15 | 0.84 |
Annual Sum or Average | 11.51 | 0.34 |
Minimum of Months | 0.14 | 0.18 |
Maximum of Months | 1.94 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.40 | 0.54 |
February | 0.95 | 0.51 |
March | 1.72 | 0.41 |
April | 3.20 | 0.31 |
May | 5.58 | 0.35 |
June | 5.33 | 0.23 |
July | 7.83 | 0.27 |
August | 5.58 | 0.16 |
September | 5.49 | 0.24 |
October | 3.03 | 0.28 |
November | 0.96 | 0.21 |
December | 0.67 | 0.54 |
Annual Sum or Average | 40.74 | 0.28 |
Minimum of Months | 0.40 | 0.16 |
Maximum of Months | 7.83 | 0.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.32 | 0.84 |
February | 0.14 | 0.94 |
March | 0.03 | 0.84 |
April | 0.27 | 0.54 |
May | 0.87 | 0.67 |
June | 1.65 | 0.23 |
July | 1.82 | 0.31 |
August | 1.70 | 0.09 |
September | 1.08 | 0.37 |
October | 0.09 | 1.05 |
November | 0.17 | 0.84 |
December | 1.27 | 0.77 |
Annual Sum or Average | 9.41 | 0.41 |
Minimum of Months | 0.03 | 0.09 |
Maximum of Months | 1.82 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.52 | 0.54 |
February | 0.53 | 0.54 |
March | 0.86 | 0.54 |
April | 1.33 | 0.33 |
May | 3.37 | 0.46 |
June | 5.11 | 0.19 |
July | 5.85 | 0.17 |
August | 4.43 | 0.18 |
September | 4.37 | 0.37 |
October | 0.84 | 0.50 |
November | 0.56 | 1.52 |
December | 0.78 | 0.54 |
Annual Sum or Average | 28.55 | 0.32 |
Minimum of Months | 0.52 | 0.17 |
Maximum of Months | 5.85 | 1.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.38 | 0.84 |
February | 0.20 | 0.84 |
March | 0.22 | 0.84 |
April | 0.61 | 0.65 |
May | 1.13 | 0.65 |
June | 1.83 | 0.21 |
July | 2.47 | 0.24 |
August | 2.02 | 0.13 |
September | 1.64 | 0.45 |
October | 0.28 | 0.91 |
November | 0.13 | 0.84 |
December | 0.11 | 0.84 |
Annual Sum or Average | 11.04 | 0.39 |
Minimum of Months | 0.11 | 0.13 |
Maximum of Months | 2.47 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.37 | 0.54 |
February | 0.58 | 0.54 |
March | 0.73 | 0.54 |
April | 1.33 | 0.40 |
May | 3.65 | 0.47 |
June | 5.19 | 0.34 |
July | 6.89 | 0.25 |
August | 4.48 | 0.16 |
September | 4.03 | 0.36 |
October | 1.02 | 0.51 |
November | 0.34 | 0.51 |
December | 0.34 | 0.54 |
Annual Sum or Average | 28.94 | 0.34 |
Minimum of Months | 0.34 | 0.16 |
Maximum of Months | 6.89 | 0.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.10 | 0.00 |
June | 0.03 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.13 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.10 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 14.70 | 0.00 |
February | 0.11 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.81 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.70 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 41.27 | 0.00 |
February | 25.86 | 0.00 |
March | 20.10 | 0.00 |
April | 0.17 | 0.00 |
May | 3.26 | 0.00 |
June | 0.47 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 14.70 | 0.00 |
November | 21.03 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 126.86 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 41.27 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.737762E+09 | 0.00 | 52060397.90 | 0.213474E+11 | 0.00 | 0.00 |
February | 0.399674E+09 | 0.00 | 0.158369E+10 | 0.191740E+11 | 0.00 | 0.00 |
March | 0.252205E+09 | 0.00 | 0.440033E+10 | 0.219291E+11 | 0.00 | 0.00 |
April | 0.304373E+09 | 0.00 | 0.217785E+11 | 0.207969E+11 | 0.00 | 0.00 |
May | 0.187979E+09 | 0.00 | 0.379821E+11 | 0.222554E+11 | 0.00 | 0.00 |
June | 0.413766E+09 | 0.00 | 0.693520E+11 | 0.220050E+11 | 0.00 | 0.00 |
July | 0.646216E+09 | 0.00 | 0.843753E+11 | 0.224327E+11 | 0.00 | 0.00 |
August | 0.413429E+09 | 0.00 | 0.842442E+11 | 0.236981E+11 | 0.00 | 0.00 |
September | 0.927343E+09 | 0.00 | 0.570464E+11 | 0.223638E+11 | 0.00 | 0.00 |
October | 0.683745E+09 | 0.00 | 0.262491E+11 | 0.231406E+11 | 0.00 | 0.00 |
November | 0.765390E+09 | 0.00 | 0.881340E+09 | 0.219921E+11 | 0.00 | 0.00 |
December | 0.851884E+09 | 0.00 | 5225176.89 | 0.220125E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.658377E+10 | 0.00 | 0.387950E+12 | 0.263148E+12 | 0.00 | 0.00 |
Minimum of Months | 0.187979E+09 | 0.00 | 5225176.89 | 0.191740E+11 | 0.00 | 0.00 |
Maximum of Months | 0.927343E+09 | 0.00 | 0.843753E+11 | 0.236981E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.899169E+10 | 0.00 | 0.926173E+09 | 0.735063E+10 | 0.00 | 0.00 |
February | 0.486132E+10 | 0.00 | 0.352250E+10 | 0.756459E+10 | 0.00 | 0.00 |
March | 0.104413E+10 | 0.00 | 0.134655E+11 | 0.959268E+10 | 0.00 | 0.00 |
April | 61104463.72 | 0.00 | 0.423849E+11 | 0.102508E+11 | 0.00 | 0.00 |
May | 19567209.61 | 0.00 | 0.618696E+11 | 0.805646E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.116980E+12 | 0.906298E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.155100E+12 | 0.969505E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.159368E+12 | 0.117146E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.891706E+11 | 0.795466E+10 | 0.00 | 0.00 |
October | 0.622923E+09 | 0.00 | 0.438498E+11 | 0.927851E+10 | 0.00 | 0.00 |
November | 0.121687E+10 | 0.00 | 0.294962E+10 | 0.101026E+11 | 0.00 | 0.00 |
December | 0.499776E+10 | 0.00 | 867.66 | 0.101893E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.218154E+11 | 0.00 | 0.689586E+12 | 0.110813E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 867.66 | 0.735063E+10 | 0.00 | 0.00 |
Maximum of Months | 0.899169E+10 | 0.00 | 0.159368E+12 | 0.117146E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.194886E+12 | 0.00 | 0.687477E+10 | 0.537103E+11 | 0.00 | 0.00 |
February | 0.121097E+12 | 0.00 | 0.292179E+11 | 0.520119E+11 | 0.00 | 0.00 |
March | 0.451567E+11 | 0.00 | 0.105873E+12 | 0.622024E+11 | 0.00 | 0.00 |
April | 0.908189E+10 | 0.00 | 0.320719E+12 | 0.626169E+11 | 0.00 | 0.00 |
May | 0.196284E+10 | 0.00 | 0.545706E+12 | 0.654506E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.100464E+13 | 0.732224E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.124016E+13 | 0.738254E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.117639E+13 | 0.783953E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.785453E+12 | 0.659949E+11 | 0.00 | 0.00 |
October | 0.219307E+11 | 0.00 | 0.368172E+12 | 0.672470E+11 | 0.00 | 0.00 |
November | 0.601016E+11 | 0.00 | 0.215537E+11 | 0.633099E+11 | 0.00 | 0.00 |
December | 0.178147E+12 | 0.00 | 166676.89 | 0.566842E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.632364E+12 | 0.00 | 0.560475E+13 | 0.774671E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 166676.89 | 0.520119E+11 | 0.00 | 0.00 |
Maximum of Months | 0.194886E+12 | 0.00 | 0.124016E+13 | 0.783953E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.349152E+11 | 0.00 | 0.540561E+09 | 0.441907E+10 | 0.00 | 0.00 |
February | 0.227004E+11 | 0.00 | 0.265461E+10 | 0.418207E+10 | 0.00 | 0.00 |
March | 0.969101E+10 | 0.00 | 0.101270E+11 | 0.493673E+10 | 0.00 | 0.00 |
April | 0.210264E+10 | 0.00 | 0.342721E+11 | 0.553277E+10 | 0.00 | 0.00 |
May | 0.466871E+09 | 0.00 | 0.607123E+11 | 0.642117E+10 | 0.00 | 0.00 |
June | 20199978.64 | 0.00 | 0.115226E+12 | 0.811464E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.143330E+12 | 0.855663E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.133814E+12 | 0.876210E+10 | 0.00 | 0.00 |
September | 3929740.60 | 0.00 | 0.856652E+11 | 0.666813E+10 | 0.00 | 0.00 |
October | 0.500343E+10 | 0.00 | 0.380558E+11 | 0.560548E+10 | 0.00 | 0.00 |
November | 0.132664E+11 | 0.00 | 0.180108E+10 | 0.464289E+10 | 0.00 | 0.00 |
December | 0.344677E+11 | 0.00 | 184.13 | 0.437147E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.122638E+12 | 0.00 | 0.626198E+12 | 0.722131E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 184.13 | 0.418207E+10 | 0.00 | 0.00 |
Maximum of Months | 0.349152E+11 | 0.00 | 0.143330E+12 | 0.876210E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.719744E+10 | 0.00 | 0.485874E+12 | 0.286166E+12 | 0.00 | 23.40 |
February | 0.694973E+10 | 0.00 | 0.742631E+12 | 0.344389E+12 | 0.00 | 33.67 |
March | 0.196533E+10 | 0.00 | 0.114238E+13 | 0.467553E+12 | 0.00 | 48.76 |
April | 88717814.87 | 0.00 | 0.143250E+13 | 0.551665E+12 | 0.00 | 56.25 |
May | 0.689416E+09 | 0.00 | 0.482085E+12 | 0.278285E+12 | 0.00 | 19.85 |
June | 0.177249E+09 | 0.00 | 0.801364E+12 | 0.374041E+12 | 0.00 | 23.84 |
July | 0.00 | 0.00 | 0.117821E+13 | 0.490895E+12 | 0.00 | 26.20 |
August | 0.00 | 0.00 | 0.151319E+13 | 0.608370E+12 | 0.00 | 46.93 |
September | 0.00 | 0.00 | 0.473549E+12 | 0.268795E+12 | 0.00 | 17.23 |
October | 0.282092E+10 | 0.00 | 0.821986E+12 | 0.379855E+12 | 0.00 | 33.87 |
November | 0.261222E+10 | 0.00 | 0.111328E+13 | 0.454461E+12 | 0.00 | 48.92 |
December | 0.113291E+09 | 0.00 | 0.147263E+13 | 0.562079E+12 | 0.00 | 66.55 |
Annual Sum or Average | 0.226143E+11 | 0.00 | 0.116597E+14 | 0.506655E+13 | 0.00 | 445.48 |
Minimum of Months | 0.00 | 0.00 | 0.473549E+12 | 0.268795E+12 | 0.00 | 17.23 |
Maximum of Months | 0.719744E+10 | 0.00 | 0.151319E+13 | 0.608370E+12 | 0.00 | 66.55 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.622100E+10 | 0.315790E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.115657E+11 | 0.406328E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194158E+11 | 0.582827E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.255645E+11 | 0.732739E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.759681E+10 | 0.362982E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142032E+11 | 0.554092E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.218294E+11 | 0.791015E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.277911E+11 | 0.925167E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.756384E+10 | 0.363528E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.137078E+11 | 0.487764E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186568E+11 | 0.553020E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252394E+11 | 0.673608E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199355E+12 | 0.674886E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.622100E+10 | 0.315790E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.277911E+11 | 0.925167E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.446471E+11 | 0.269890E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.983402E+11 | 0.364102E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.175288E+12 | 0.537704E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238501E+12 | 0.689473E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.669880E+11 | 0.334066E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132716E+12 | 0.522344E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207183E+12 | 0.751953E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.263541E+12 | 0.880094E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.670266E+11 | 0.334987E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122613E+12 | 0.448947E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.166388E+12 | 0.506449E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223352E+12 | 0.612661E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180658E+13 | 0.625267E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.446471E+11 | 0.269890E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.263541E+12 | 0.880094E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.226453E+10 | 0.223821E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.805062E+10 | 0.332136E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163066E+11 | 0.520101E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.233047E+11 | 0.686099E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.645834E+10 | 0.333907E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133130E+11 | 0.529419E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.209222E+11 | 0.763641E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266028E+11 | 0.893737E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.653838E+10 | 0.336314E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113981E+11 | 0.436588E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149043E+11 | 0.478967E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.198952E+11 | 0.574901E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169959E+12 | 0.610963E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.226453E+10 | 0.223821E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266028E+11 | 0.893737E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.213474E+11 | 52060397.90 | 0.737762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191740E+11 | 0.158369E+10 | 0.399674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219291E+11 | 0.440033E+10 | 0.252205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207969E+11 | 0.217785E+11 | 0.304373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222554E+11 | 0.379821E+11 | 0.187979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220050E+11 | 0.693520E+11 | 0.413766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224327E+11 | 0.843753E+11 | 0.646216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236981E+11 | 0.842442E+11 | 0.413429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223638E+11 | 0.570464E+11 | 0.927343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231406E+11 | 0.262491E+11 | 0.683745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219921E+11 | 0.881340E+09 | 0.765390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220125E+11 | 5225176.89 | 0.851884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263148E+12 | 0.387950E+12 | 0.658377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191740E+11 | 5225176.89 | 0.187979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.236981E+11 | 0.843753E+11 | 0.927343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.735063E+10 | 0.926173E+09 | 0.899169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756459E+10 | 0.352250E+10 | 0.486132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959268E+10 | 0.134655E+11 | 0.104413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102508E+11 | 0.423849E+11 | 61104463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.805646E+10 | 0.618696E+11 | 19567209.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.906298E+10 | 0.116980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.969505E+10 | 0.155100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117146E+11 | 0.159368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.795466E+10 | 0.891706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.927851E+10 | 0.438498E+11 | 0.622923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101026E+11 | 0.294962E+10 | 0.121687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101893E+11 | 867.66 | 0.499776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110813E+12 | 0.689586E+12 | 0.218154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.735063E+10 | 867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117146E+11 | 0.159368E+12 | 0.899169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.537103E+11 | 0.687477E+10 | 0.194886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520119E+11 | 0.292179E+11 | 0.121097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622024E+11 | 0.105873E+12 | 0.451567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.626169E+11 | 0.320719E+12 | 0.908189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.654506E+11 | 0.545706E+12 | 0.196284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.732224E+11 | 0.100464E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.738254E+11 | 0.124016E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.783953E+11 | 0.117639E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.659949E+11 | 0.785453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672470E+11 | 0.368172E+12 | 0.219307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.633099E+11 | 0.215537E+11 | 0.601016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.566842E+11 | 166676.89 | 0.178147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774671E+12 | 0.560475E+13 | 0.632364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.520119E+11 | 166676.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.783953E+11 | 0.124016E+13 | 0.194886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.441907E+10 | 0.540561E+09 | 0.349152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418207E+10 | 0.265461E+10 | 0.227004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493673E+10 | 0.101270E+11 | 0.969101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553277E+10 | 0.342721E+11 | 0.210264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642117E+10 | 0.607123E+11 | 0.466871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.811464E+10 | 0.115226E+12 | 20199978.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.855663E+10 | 0.143330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876210E+10 | 0.133814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.666813E+10 | 0.856652E+11 | 3929740.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560548E+10 | 0.380558E+11 | 0.500343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464289E+10 | 0.180108E+10 | 0.132664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437147E+10 | 184.13 | 0.344677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722131E+11 | 0.626198E+12 | 0.122638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.418207E+10 | 184.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.876210E+10 | 0.143330E+12 | 0.349152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114550E+12 | 0.413394E+12 | 0.719744E+10 | 0.00 | 0.00 | 0.626336E+11 | 0.00 | 0.00 |
February | 0.103465E+12 | 0.631206E+12 | 0.694973E+10 | 0.00 | 0.00 | 0.901129E+11 | 0.00 | 0.00 |
March | 0.114550E+12 | 0.965602E+12 | 0.196533E+10 | 0.00 | 0.00 | 0.130495E+12 | 0.00 | 0.00 |
April | 0.110855E+12 | 0.119329E+13 | 88717814.87 | 0.00 | 0.00 | 0.150530E+12 | 0.00 | 0.00 |
May | 0.114550E+12 | 0.402073E+12 | 0.689416E+09 | 0.00 | 0.00 | 0.531169E+11 | 0.00 | 0.00 |
June | 0.110855E+12 | 0.642803E+12 | 0.177249E+09 | 0.00 | 0.00 | 0.637871E+11 | 0.00 | 0.00 |
July | 0.114550E+12 | 0.918998E+12 | 0.00 | 0.00 | 0.00 | 0.701172E+11 | 0.00 | 0.00 |
August | 0.114550E+12 | 0.120651E+13 | 0.00 | 0.00 | 0.00 | 0.125584E+12 | 0.00 | 0.00 |
September | 0.110855E+12 | 0.391297E+12 | 0.00 | 0.00 | 0.00 | 0.461222E+11 | 0.00 | 0.00 |
October | 0.114550E+12 | 0.689791E+12 | 0.282092E+10 | 0.00 | 0.00 | 0.906438E+11 | 0.00 | 0.00 |
November | 0.110855E+12 | 0.944282E+12 | 0.261222E+10 | 0.00 | 0.00 | 0.130925E+12 | 0.00 | 0.00 |
December | 0.114550E+12 | 0.125463E+13 | 0.113291E+09 | 0.00 | 0.00 | 0.178099E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.134874E+13 | 0.965387E+13 | 0.226143E+11 | 0.00 | 0.00 | 0.119217E+13 | 0.00 | 0.00 |
Minimum of Months | 0.103465E+12 | 0.391297E+12 | 0.00 | 0.00 | 0.00 | 0.461222E+11 | 0.00 | 0.00 |
Maximum of Months | 0.114550E+12 | 0.125463E+13 | 0.719744E+10 | 0.00 | 0.00 | 0.178099E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173437E+10 | 0.517412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156653E+10 | 0.960619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173437E+10 | 0.160351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167842E+10 | 0.206258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173437E+10 | 0.615065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167842E+10 | 0.109866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173437E+10 | 0.163680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173437E+10 | 0.209991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167842E+10 | 0.605694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173437E+10 | 0.111891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167842E+10 | 0.154943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173437E+10 | 0.209892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204208E+11 | 0.159675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156653E+10 | 0.517412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173437E+10 | 0.209991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165459E+11 | 0.371332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149447E+11 | 0.816726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165459E+11 | 0.144743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160121E+11 | 0.192331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165459E+11 | 0.541953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160121E+11 | 0.102600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165459E+11 | 0.155357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165459E+11 | 0.198901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160121E+11 | 0.536320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165459E+11 | 0.100026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160121E+11 | 0.138176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165459E+11 | 0.185740E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194814E+12 | 0.144451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149447E+11 | 0.371332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165459E+11 | 0.198901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169574E+10 | 0.188353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153163E+10 | 0.668458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169574E+10 | 0.134587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164104E+10 | 0.187746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169574E+10 | 0.521401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164104E+10 | 0.102782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169574E+10 | 0.156798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169574E+10 | 0.200587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164104E+10 | 0.522150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169574E+10 | 0.928561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164104E+10 | 0.123753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169574E+10 | 0.165449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199659E+11 | 0.135459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153163E+10 | 0.188353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169574E+10 | 0.200587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.213474E+11 | 0.737762E+09 | 52060397.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191740E+11 | 0.399674E+09 | 0.158369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219291E+11 | 0.252205E+09 | 0.440033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207969E+11 | 0.304373E+09 | 0.217785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222554E+11 | 0.187979E+09 | 0.379821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220050E+11 | 0.413766E+09 | 0.693520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224327E+11 | 0.646216E+09 | 0.843753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236981E+11 | 0.413429E+09 | 0.842442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223638E+11 | 0.927343E+09 | 0.570464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231406E+11 | 0.683745E+09 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219921E+11 | 0.765390E+09 | 0.881340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220125E+11 | 0.851884E+09 | 5225176.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263148E+12 | 0.658377E+10 | 0.387950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.191740E+11 | 0.187979E+09 | 5225176.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.236981E+11 | 0.927343E+09 | 0.843753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.735063E+10 | 0.899169E+10 | 0.926173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756459E+10 | 0.486132E+10 | 0.352250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959268E+10 | 0.104413E+10 | 0.134655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102508E+11 | 61104463.72 | 0.423849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.805646E+10 | 19567209.61 | 0.618696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.906298E+10 | 0.00 | 0.116980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.969505E+10 | 0.00 | 0.155100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117146E+11 | 0.00 | 0.159368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.795466E+10 | 0.00 | 0.891706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.927851E+10 | 0.622923E+09 | 0.438498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101026E+11 | 0.121687E+10 | 0.294962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101893E+11 | 0.499776E+10 | 867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110813E+12 | 0.218154E+11 | 0.689586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.735063E+10 | 0.00 | 867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117146E+11 | 0.899169E+10 | 0.159368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.537103E+11 | 0.194886E+12 | 0.687477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520119E+11 | 0.121097E+12 | 0.292179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622024E+11 | 0.451567E+11 | 0.105873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.626169E+11 | 0.908189E+10 | 0.320719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.654506E+11 | 0.196284E+10 | 0.545706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.732224E+11 | 0.00 | 0.100464E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.738254E+11 | 0.00 | 0.124016E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.783953E+11 | 0.00 | 0.117639E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.659949E+11 | 0.00 | 0.785453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672470E+11 | 0.219307E+11 | 0.368172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.633099E+11 | 0.601016E+11 | 0.215537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.566842E+11 | 0.178147E+12 | 166676.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774671E+12 | 0.632364E+12 | 0.560475E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.520119E+11 | 0.00 | 166676.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.783953E+11 | 0.194886E+12 | 0.124016E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.441907E+10 | 0.349152E+11 | 0.540561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418207E+10 | 0.227004E+11 | 0.265461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493673E+10 | 0.969101E+10 | 0.101270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553277E+10 | 0.210264E+10 | 0.342721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642117E+10 | 0.466871E+09 | 0.607123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.811464E+10 | 20199978.64 | 0.115226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.855663E+10 | 0.00 | 0.143330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876210E+10 | 0.00 | 0.133814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.666813E+10 | 3929740.60 | 0.856652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560548E+10 | 0.500343E+10 | 0.380558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464289E+10 | 0.132664E+11 | 0.180108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437147E+10 | 0.344677E+11 | 184.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722131E+11 | 0.122638E+12 | 0.626198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.418207E+10 | 0.00 | 184.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.876210E+10 | 0.349152E+11 | 0.143330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.114550E+12 | 0.719744E+10 | 0.485874E+12 | 0.00 | 0.108700E+12 | 0.00 | 0.00 | 0.00 | 0.629156E+11 | 0.00 | 0.00 | 0.00 |
February | 0.103465E+12 | 0.694973E+10 | 0.742631E+12 | 0.00 | 0.150405E+12 | 0.00 | 0.00 | 0.00 | 0.905186E+11 | 0.00 | 0.00 | 0.00 |
March | 0.114550E+12 | 0.196533E+10 | 0.114238E+13 | 0.00 | 0.221921E+12 | 0.00 | 0.00 | 0.00 | 0.131082E+12 | 0.00 | 0.00 | 0.00 |
April | 0.110855E+12 | 88717814.87 | 0.143250E+13 | 0.00 | 0.289602E+12 | 0.00 | 0.00 | 0.00 | 0.151208E+12 | 0.00 | 0.00 | 0.00 |
May | 0.114550E+12 | 0.689416E+09 | 0.482085E+12 | 0.00 | 0.110379E+12 | 0.00 | 0.00 | 0.00 | 0.533560E+11 | 0.00 | 0.00 | 0.00 |
June | 0.110855E+12 | 0.177249E+09 | 0.801364E+12 | 0.00 | 0.199112E+12 | 0.00 | 0.00 | 0.00 | 0.640743E+11 | 0.00 | 0.00 | 0.00 |
July | 0.114550E+12 | 0.00 | 0.117821E+13 | 0.00 | 0.305911E+12 | 0.00 | 0.00 | 0.00 | 0.704329E+11 | 0.00 | 0.00 | 0.00 |
August | 0.114550E+12 | 0.00 | 0.151319E+13 | 0.00 | 0.367671E+12 | 0.00 | 0.00 | 0.00 | 0.126149E+12 | 0.00 | 0.00 | 0.00 |
September | 0.110855E+12 | 0.00 | 0.473549E+12 | 0.00 | 0.111611E+12 | 0.00 | 0.00 | 0.00 | 0.463298E+11 | 0.00 | 0.00 | 0.00 |
October | 0.114550E+12 | 0.282092E+10 | 0.821986E+12 | 0.00 | 0.174253E+12 | 0.00 | 0.00 | 0.00 | 0.910518E+11 | 0.00 | 0.00 | 0.00 |
November | 0.110855E+12 | 0.261222E+10 | 0.111328E+13 | 0.00 | 0.212091E+12 | 0.00 | 0.00 | 0.00 | 0.131515E+12 | 0.00 | 0.00 | 0.00 |
December | 0.114550E+12 | 0.113291E+09 | 0.147263E+13 | 0.00 | 0.268628E+12 | 0.00 | 0.00 | 0.00 | 0.178901E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134874E+13 | 0.226143E+11 | 0.116597E+14 | 0.00 | 0.252028E+13 | 0.00 | 0.00 | 0.00 | 0.119753E+13 | 0.00 | 0.00 | |
Minimum of Months | 0.103465E+12 | 0.00 | 0.473549E+12 | 0.00 | 0.108700E+12 | 0.00 | 0.00 | 0.00 | 0.463298E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114550E+12 | 0.719744E+10 | 0.151319E+13 | 0.00 | 0.367671E+12 | 0.00 | 0.00 | 0.00 | 0.178901E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.173437E+10 | 0.00 | 0.622100E+10 | 0.00 | 0.142353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156653E+10 | 0.00 | 0.115657E+11 | 0.00 | 0.249676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173437E+10 | 0.00 | 0.194158E+11 | 0.00 | 0.409390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167842E+10 | 0.00 | 0.255645E+11 | 0.00 | 0.564897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173437E+10 | 0.00 | 0.759681E+10 | 0.00 | 0.189545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167842E+10 | 0.00 | 0.142032E+11 | 0.00 | 0.386250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173437E+10 | 0.00 | 0.218294E+11 | 0.00 | 0.617578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173437E+10 | 0.00 | 0.277911E+11 | 0.00 | 0.751730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167842E+10 | 0.00 | 0.756384E+10 | 0.00 | 0.195686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173437E+10 | 0.00 | 0.137078E+11 | 0.00 | 0.314327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167842E+10 | 0.00 | 0.186568E+11 | 0.00 | 0.385178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173437E+10 | 0.00 | 0.252394E+11 | 0.00 | 0.500171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204208E+11 | 0.00 | 0.199355E+12 | 0.00 | 0.470678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.156653E+10 | 0.00 | 0.622100E+10 | 0.00 | 0.142353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173437E+10 | 0.00 | 0.277911E+11 | 0.00 | 0.751730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.165459E+11 | 0.00 | 0.446471E+11 | 0.00 | 0.104431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149447E+11 | 0.00 | 0.983402E+11 | 0.00 | 0.214655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165459E+11 | 0.00 | 0.175288E+12 | 0.00 | 0.372245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160121E+11 | 0.00 | 0.238501E+12 | 0.00 | 0.529351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165459E+11 | 0.00 | 0.669880E+11 | 0.00 | 0.168608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160121E+11 | 0.00 | 0.132716E+12 | 0.00 | 0.362223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165459E+11 | 0.00 | 0.207183E+12 | 0.00 | 0.586494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165459E+11 | 0.00 | 0.263541E+12 | 0.00 | 0.714635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160121E+11 | 0.00 | 0.670266E+11 | 0.00 | 0.174866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165459E+11 | 0.00 | 0.122613E+12 | 0.00 | 0.283488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160121E+11 | 0.00 | 0.166388E+12 | 0.00 | 0.346328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165459E+11 | 0.00 | 0.223352E+12 | 0.00 | 0.447202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194814E+12 | 0.00 | 0.180658E+13 | 0.00 | 0.430453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.149447E+11 | 0.00 | 0.446471E+11 | 0.00 | 0.104431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165459E+11 | 0.00 | 0.263541E+12 | 0.00 | 0.714635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.169574E+10 | 0.00 | 0.226453E+10 | 0.00 | 0.542472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153163E+10 | 0.00 | 0.805062E+10 | 0.00 | 0.178973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169574E+10 | 0.00 | 0.163066E+11 | 0.00 | 0.350527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164104E+10 | 0.00 | 0.233047E+11 | 0.00 | 0.521996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169574E+10 | 0.00 | 0.645834E+10 | 0.00 | 0.164333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164104E+10 | 0.00 | 0.133130E+11 | 0.00 | 0.365316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169574E+10 | 0.00 | 0.209222E+11 | 0.00 | 0.594068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169574E+10 | 0.00 | 0.266028E+11 | 0.00 | 0.724163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164104E+10 | 0.00 | 0.653838E+10 | 0.00 | 0.172210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169574E+10 | 0.00 | 0.113981E+11 | 0.00 | 0.267014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164104E+10 | 0.00 | 0.149043E+11 | 0.00 | 0.314863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169574E+10 | 0.00 | 0.198952E+11 | 0.00 | 0.405328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199659E+11 | 0.00 | 0.169959E+12 | 0.00 | 0.411304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.153163E+10 | 0.00 | 0.226453E+10 | 0.00 | 0.542472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169574E+10 | 0.00 | 0.266028E+11 | 0.00 | 0.724163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384983E+09 | 0.00 | 0.00 | 0.206338E+09 | 0.00 | 0.00 | 0.862565E+11 | 0.00 | 0.89 |
February | 0.339876E+09 | 0.00 | 0.00 | 0.174219E+09 | 0.00 | 0.00 | 0.762685E+11 | 0.00 | 0.98 |
March | 0.236715E+09 | 0.00 | 0.00 | 0.186663E+09 | 0.00 | 0.00 | 0.869853E+11 | 0.00 | 1.39 |
April | 0.230167E+09 | 12243956.07 | 0.00 | 0.174649E+09 | 128564.76 | 0.00 | 0.654347E+11 | 0.00 | 1.55 |
May | 92305569.44 | 0.149418E+09 | 0.00 | 0.180190E+09 | 9184685.09 | 0.00 | 0.538464E+11 | 0.00 | 1.55 |
June | 63572692.16 | 0.245842E+10 | 0.00 | 0.136979E+09 | 24562253.31 | 0.00 | 0.262704E+11 | 0.00 | 1.20 |
July | 76590539.86 | 0.274462E+10 | 0.00 | 0.143526E+09 | 61476989.86 | 0.00 | 0.129726E+11 | 0.00 | 1.06 |
August | 49893208.47 | 0.153050E+10 | 0.00 | 0.180440E+09 | 40050794.34 | 0.00 | 0.216462E+11 | 0.00 | 1.30 |
September | 0.107707E+09 | 0.278738E+09 | 0.00 | 0.200965E+09 | 10998668.56 | 0.00 | 0.385746E+11 | 0.00 | 1.57 |
October | 0.206330E+09 | 13743889.52 | 0.00 | 0.236570E+09 | 0.00 | 0.00 | 0.730346E+11 | 0.00 | 1.61 |
November | 0.342576E+09 | 0.00 | 0.00 | 0.225683E+09 | 0.00 | 0.00 | 0.941833E+11 | 0.00 | 1.26 |
December | 0.600543E+09 | 0.00 | 0.00 | 0.207585E+09 | 0.00 | 0.00 | 0.919647E+11 | 0.00 | 0.85 |
Annual Sum or Average | 0.273126E+10 | 0.718769E+10 | 0.00 | 0.225381E+10 | 0.146402E+09 | 0.00 | 0.727438E+12 | 0.00 | 1.27 |
Minimum of Months | 49893208.47 | 0.00 | 0.00 | 0.136979E+09 | 0.00 | 0.00 | 0.129726E+11 | 0.00 | 0.85 |
Maximum of Months | 0.600543E+09 | 0.274462E+10 | 0.00 | 0.236570E+09 | 61476989.86 | 0.00 | 0.941833E+11 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338506E+10 | 0.00 | 0.00 | 0.102434E+09 | 0.00 | 0.00 | 0.580000E+11 | 0.00 | 0.63 |
February | 0.285586E+10 | 0.00 | 0.00 | 99538928.31 | 0.00 | 0.00 | 0.541715E+11 | 0.00 | 0.70 |
March | 0.420523E+10 | 0.00 | 0.00 | 0.125545E+09 | 0.00 | 0.00 | 0.625602E+11 | 0.00 | 0.98 |
April | 0.835992E+10 | 1713652.14 | 0.00 | 0.119107E+09 | 0.00 | 0.00 | 0.463408E+11 | 0.00 | 1.13 |
May | 0.333102E+10 | 84700536.09 | 0.00 | 0.109929E+09 | 26084736.15 | 0.00 | 0.332881E+11 | 0.00 | 0.94 |
June | 0.362700E+10 | 0.256331E+10 | 0.00 | 71986806.48 | 0.131233E+09 | 0.00 | 0.137652E+11 | 0.00 | 0.81 |
July | 0.244314E+10 | 0.496844E+10 | 0.00 | 33871245.07 | 0.873971E+09 | 0.00 | 0.231120E+10 | 0.00 | 0.72 |
August | 0.487539E+10 | 0.298959E+10 | 0.00 | 66307963.43 | 0.413430E+09 | 0.00 | 0.779565E+10 | 0.00 | 0.96 |
September | 0.278687E+10 | 0.469068E+09 | 0.00 | 99564967.61 | 41693354.14 | 0.00 | 0.184929E+11 | 0.00 | 0.84 |
October | 0.456643E+10 | 1379280.36 | 0.00 | 0.122600E+09 | 1927174.66 | 0.00 | 0.447672E+11 | 0.00 | 0.95 |
November | 0.520208E+10 | 0.00 | 0.00 | 0.119145E+09 | 0.00 | 0.00 | 0.648111E+11 | 0.00 | 0.90 |
December | 0.408862E+10 | 0.00 | 0.00 | 0.124219E+09 | 0.00 | 0.00 | 0.682973E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.497266E+11 | 0.110782E+11 | 0.00 | 0.119425E+10 | 0.148834E+10 | 0.00 | 0.474601E+12 | 0.00 | 0.85 |
Minimum of Months | 0.244314E+10 | 0.00 | 0.00 | 33871245.07 | 0.00 | 0.00 | 0.231120E+10 | 0.00 | 0.63 |
Maximum of Months | 0.835992E+10 | 0.496844E+10 | 0.00 | 0.125545E+09 | 0.873971E+09 | 0.00 | 0.682973E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105873E+12 | 0.00 | 0.00 | 0.547764E+09 | 0.00 | 0.00 | 0.396562E+12 | 0.00 | 0.52 |
February | 0.678131E+11 | 0.00 | 0.00 | 0.564269E+09 | 0.00 | 0.00 | 0.374108E+12 | 0.00 | 0.55 |
March | 0.324608E+11 | 0.00 | 0.00 | 0.805233E+09 | 0.00 | 0.00 | 0.451908E+12 | 0.00 | 0.73 |
April | 0.273684E+11 | 32780300.16 | 0.00 | 0.823516E+09 | 39375038.71 | 0.00 | 0.335782E+12 | 0.00 | 0.78 |
May | 0.211006E+11 | 0.731626E+09 | 0.00 | 0.883277E+09 | 0.571058E+09 | 0.00 | 0.273421E+12 | 0.00 | 0.79 |
June | 0.153386E+11 | 0.283081E+11 | 0.00 | 0.596660E+09 | 0.811444E+09 | 0.00 | 0.109166E+12 | 0.00 | 0.65 |
July | 0.803277E+10 | 0.496515E+11 | 0.00 | 0.348067E+09 | 0.432027E+10 | 0.00 | 0.185312E+11 | 0.00 | 0.53 |
August | 0.117414E+11 | 0.276058E+11 | 0.00 | 0.603633E+09 | 0.155540E+10 | 0.00 | 0.624812E+11 | 0.00 | 0.66 |
September | 0.162912E+11 | 0.431563E+10 | 0.00 | 0.809750E+09 | 0.596604E+09 | 0.00 | 0.147296E+12 | 0.00 | 0.70 |
October | 0.334912E+11 | 32802979.71 | 0.00 | 0.869672E+09 | 0.168163E+09 | 0.00 | 0.338366E+12 | 0.00 | 0.74 |
November | 0.427744E+11 | 0.00 | 0.00 | 0.742164E+09 | 0.00 | 0.00 | 0.458537E+12 | 0.00 | 0.66 |
December | 0.905327E+11 | 0.00 | 0.00 | 0.579192E+09 | 0.00 | 0.00 | 0.415115E+12 | 0.00 | 0.46 |
Annual Sum or Average | 0.472819E+12 | 0.110678E+12 | 0.00 | 0.817320E+10 | 0.806232E+10 | 0.00 | 0.338127E+13 | 0.00 | 0.65 |
Minimum of Months | 0.803277E+10 | 0.00 | 0.00 | 0.348067E+09 | 0.00 | 0.00 | 0.185312E+11 | 0.00 | 0.46 |
Maximum of Months | 0.105873E+12 | 0.496515E+11 | 0.00 | 0.883277E+09 | 0.432027E+10 | 0.00 | 0.458537E+12 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261692E+11 | 0.00 | 0.00 | 11416788.74 | 0.00 | 0.913086E+09 | 0.109181E+11 | 0.00 | 0.41 |
February | 0.189177E+11 | 0.00 | 0.00 | 17820484.98 | 0.00 | 0.257194E+09 | 0.150940E+11 | 0.00 | 0.45 |
March | 0.124156E+11 | 0.00 | 0.00 | 36920217.66 | 0.00 | 18162395.92 | 0.268812E+11 | 0.00 | 0.61 |
April | 0.622621E+10 | 0.00 | 0.00 | 55745866.96 | 0.00 | 0.00 | 0.264573E+11 | 0.00 | 0.75 |
May | 0.408085E+10 | 30695800.31 | 0.00 | 73034243.71 | 9504484.11 | 0.00 | 0.241828E+11 | 0.00 | 0.81 |
June | 0.174768E+10 | 0.191587E+10 | 0.00 | 60411172.13 | 65001796.92 | 0.00 | 0.100637E+11 | 0.00 | 0.66 |
July | 0.651706E+09 | 0.369748E+10 | 0.00 | 37535130.30 | 0.466259E+09 | 0.00 | 0.161425E+10 | 0.00 | 0.56 |
August | 0.889338E+09 | 0.187540E+10 | 0.00 | 68593000.70 | 0.148935E+09 | 0.00 | 0.635769E+10 | 0.00 | 0.69 |
September | 0.246038E+10 | 0.252335E+09 | 0.00 | 71538483.23 | 21269428.47 | 0.00 | 0.124450E+11 | 0.00 | 0.72 |
October | 0.846346E+10 | 1059027.74 | 0.00 | 50720384.25 | 11839239.09 | 0.00 | 0.210895E+11 | 0.00 | 0.66 |
November | 0.151489E+11 | 0.00 | 0.00 | 27046521.78 | 0.00 | 0.206075E+09 | 0.215953E+11 | 0.00 | 0.51 |
December | 0.258064E+11 | 0.00 | 0.00 | 11479276.82 | 0.00 | 0.613361E+09 | 0.110864E+11 | 0.00 | 0.36 |
Annual Sum or Average | 0.122977E+12 | 0.777285E+10 | 0.00 | 0.522262E+09 | 0.722808E+09 | 0.200788E+10 | 0.187785E+12 | 0.00 | 0.60 |
Minimum of Months | 0.651706E+09 | 0.00 | 0.00 | 11416788.74 | 0.00 | 0.00 | 0.161425E+10 | 0.00 | 0.36 |
Maximum of Months | 0.261692E+11 | 0.369748E+10 | 0.00 | 73034243.71 | 0.466259E+09 | 0.913086E+09 | 0.268812E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.436589E+10 | 0.00 | 0.00 | 1899972.31 | 0.00 | 0.00 | 0.185701E+10 | 0.00 | 0.49 |
February | 0.322302E+10 | 0.00 | 0.00 | 3048086.72 | 0.00 | 0.00 | 0.246171E+10 | 0.00 | 0.56 |
March | 0.262556E+10 | 0.00 | 0.00 | 6766914.92 | 0.00 | 0.00 | 0.464570E+10 | 0.00 | 0.87 |
April | 0.203661E+10 | 341505.66 | 0.00 | 9862699.51 | 0.00 | 0.00 | 0.465451E+10 | 0.00 | 1.18 |
May | 0.112510E+10 | 15130337.67 | 0.00 | 10653968.60 | 4113653.14 | 0.00 | 0.361120E+10 | 0.00 | 1.04 |
June | 0.700204E+09 | 0.508353E+09 | 0.00 | 8213776.28 | 20724797.42 | 0.00 | 0.170441E+10 | 0.00 | 1.01 |
July | 0.404353E+09 | 0.963383E+09 | 0.00 | 3907615.83 | 0.138102E+09 | 0.00 | 0.301733E+09 | 0.00 | 0.95 |
August | 0.797054E+09 | 0.541886E+09 | 0.00 | 8240343.06 | 65199282.47 | 0.00 | 0.101369E+10 | 0.00 | 1.19 |
September | 0.793474E+09 | 77560188.71 | 0.00 | 9756906.63 | 6575186.21 | 0.00 | 0.201103E+10 | 0.00 | 0.95 |
October | 0.204056E+10 | 209996.34 | 0.00 | 7970521.04 | 303922.11 | 0.00 | 0.341181E+10 | 0.00 | 0.90 |
November | 0.295005E+10 | 0.00 | 0.00 | 5041984.09 | 0.00 | 0.00 | 0.394614E+10 | 0.00 | 0.71 |
December | 0.387377E+10 | 0.00 | 0.00 | 2782805.89 | 0.00 | 0.00 | 0.248719E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.249356E+11 | 0.210686E+10 | 0.00 | 78145594.89 | 0.235019E+09 | 0.00 | 0.321061E+11 | 0.00 | 0.86 |
Minimum of Months | 0.404353E+09 | 0.00 | 0.00 | 1899972.31 | 0.00 | 0.00 | 0.301733E+09 | 0.00 | 0.46 |
Maximum of Months | 0.436589E+10 | 0.963383E+09 | 0.00 | 10653968.60 | 0.138102E+09 | 0.00 | 0.465451E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.508939E+10 | 0.00 | 0.00 | 2328897.36 | 0.00 | 617578.58 | 0.224643E+10 | 0.00 | 0.89 |
February | 0.374039E+10 | 0.00 | 0.00 | 3383751.81 | 0.00 | 474998.87 | 0.282611E+10 | 0.00 | 0.98 |
March | 0.330150E+10 | 0.00 | 0.00 | 7334695.08 | 0.00 | 0.00 | 0.484556E+10 | 0.00 | 1.43 |
April | 0.277779E+10 | 314878.65 | 0.00 | 10658324.53 | 0.00 | 0.00 | 0.542463E+10 | 0.00 | 2.06 |
May | 0.149987E+10 | 14829327.29 | 0.00 | 12635401.77 | 4805418.71 | 0.00 | 0.446674E+10 | 0.00 | 1.86 |
June | 0.103333E+10 | 0.404197E+09 | 0.00 | 9430350.21 | 24122973.70 | 0.00 | 0.183347E+10 | 0.00 | 1.73 |
July | 0.605999E+09 | 0.829111E+09 | 0.00 | 3397697.44 | 0.143830E+09 | 0.00 | 0.242169E+09 | 0.00 | 1.55 |
August | 0.120237E+10 | 0.446770E+09 | 0.00 | 6967198.95 | 74361139.92 | 0.00 | 0.882006E+09 | 0.00 | 1.92 |
September | 0.141401E+10 | 56762398.01 | 0.00 | 9577658.62 | 7683207.22 | 0.00 | 0.207173E+10 | 0.00 | 1.70 |
October | 0.283294E+10 | 111030.18 | 0.00 | 8157493.90 | 440729.13 | 0.00 | 0.363424E+10 | 0.00 | 1.57 |
November | 0.371996E+10 | 0.00 | 0.00 | 4687747.51 | 0.00 | 0.00 | 0.371052E+10 | 0.00 | 1.14 |
December | 0.492229E+10 | 0.00 | 0.00 | 2112537.04 | 0.00 | 3991585.92 | 0.226692E+10 | 0.00 | 0.79 |
Annual Sum or Average | 0.321399E+11 | 0.175209E+10 | 0.00 | 80671754.23 | 0.255243E+09 | 5084163.37 | 0.344505E+11 | 0.00 | 1.47 |
Minimum of Months | 0.605999E+09 | 0.00 | 0.00 | 2112537.04 | 0.00 | 0.00 | 0.242169E+09 | 0.00 | 0.79 |
Maximum of Months | 0.508939E+10 | 0.829111E+09 | 0.00 | 12635401.77 | 0.143830E+09 | 3991585.92 | 0.542463E+10 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301039E+10 | 0.00 | 0.00 | 21602726.95 | 0.00 | 26187758.63 | 0.844578E+10 | 0.00 | 1.00 |
February | 0.213548E+10 | 0.00 | 0.00 | 17669905.46 | 0.00 | 12412437.50 | 0.849709E+10 | 0.00 | 1.12 |
March | 0.221585E+10 | 0.00 | 0.00 | 13927992.88 | 0.00 | 0.00 | 0.822791E+10 | 0.00 | 1.32 |
April | 0.230285E+10 | 412548.56 | 0.00 | 11967899.48 | 0.00 | 0.00 | 0.535050E+10 | 0.00 | 1.39 |
May | 0.145725E+10 | 17126726.08 | 0.00 | 10477589.89 | 4419802.16 | 0.00 | 0.342886E+10 | 0.00 | 1.08 |
June | 0.898093E+09 | 0.516413E+09 | 0.00 | 7043304.96 | 22267191.99 | 0.00 | 0.154560E+10 | 0.00 | 1.02 |
July | 0.440051E+09 | 0.100936E+10 | 0.00 | 3371722.26 | 0.148423E+09 | 0.00 | 0.298067E+09 | 0.00 | 0.99 |
August | 0.866700E+09 | 0.614207E+09 | 0.00 | 8736392.66 | 70051586.55 | 0.00 | 0.105603E+10 | 0.00 | 1.30 |
September | 0.833631E+09 | 0.122143E+09 | 0.00 | 14571785.23 | 6687131.69 | 0.00 | 0.243838E+10 | 0.00 | 1.22 |
October | 0.157464E+10 | 918625.32 | 0.00 | 24892122.59 | 48850.13 | 0.00 | 0.729926E+10 | 0.00 | 1.53 |
November | 0.170146E+10 | 0.00 | 0.00 | 26574814.79 | 0.00 | 0.00 | 0.110167E+11 | 0.00 | 1.32 |
December | 0.222865E+10 | 0.00 | 0.00 | 27204599.08 | 0.00 | 221511.78 | 0.105759E+11 | 0.00 | 0.95 |
Annual Sum or Average | 0.196651E+11 | 0.228058E+10 | 0.00 | 0.188041E+09 | 0.251897E+09 | 38821707.90 | 0.681802E+11 | 0.00 | 1.19 |
Minimum of Months | 0.440051E+09 | 0.00 | 0.00 | 3371722.26 | 0.00 | 0.00 | 0.298067E+09 | 0.00 | 0.95 |
Maximum of Months | 0.301039E+10 | 0.100936E+10 | 0.00 | 27204599.08 | 0.148423E+09 | 26187758.63 | 0.110167E+11 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.633782E+10 | 0.00 | 0.00 | 3128348.41 | 0.00 | 0.00 | 0.310211E+10 | 0.00 | 1.18 |
February | 0.367820E+10 | 0.00 | 0.00 | 6255027.38 | 0.00 | 0.00 | 0.524426E+10 | 0.00 | 1.40 |
March | 0.203330E+10 | 0.00 | 0.00 | 13004741.01 | 0.00 | 0.00 | 0.845557E+10 | 0.00 | 2.00 |
April | 0.181776E+10 | 511385.76 | 0.00 | 22270760.73 | 0.00 | 0.00 | 0.805005E+10 | 0.00 | 2.76 |
May | 0.157122E+10 | 28720431.11 | 0.00 | 11889052.38 | 3000148.29 | 0.00 | 0.431051E+10 | 0.00 | 2.03 |
June | 0.941800E+09 | 0.690224E+09 | 0.00 | 8931313.07 | 24224000.61 | 0.00 | 0.200962E+10 | 0.00 | 1.93 |
July | 0.542858E+09 | 0.120263E+10 | 0.00 | 4767298.30 | 0.175531E+09 | 0.00 | 0.431240E+09 | 0.00 | 1.86 |
August | 0.982977E+09 | 0.769687E+09 | 0.00 | 14342944.00 | 78366388.74 | 0.00 | 0.152754E+10 | 0.00 | 2.54 |
September | 0.118675E+10 | 86829152.20 | 0.00 | 10819416.39 | 6002769.47 | 0.00 | 0.238121E+10 | 0.00 | 1.82 |
October | 0.202191E+10 | 472946.42 | 0.00 | 12731018.65 | 311308.44 | 0.00 | 0.557675E+10 | 0.00 | 1.96 |
November | 0.240272E+10 | 0.00 | 0.00 | 9789304.04 | 0.00 | 0.00 | 0.796135E+10 | 0.00 | 1.68 |
December | 0.266003E+10 | 0.00 | 0.00 | 9353595.94 | 0.00 | 0.00 | 0.791495E+10 | 0.00 | 1.20 |
Annual Sum or Average | 0.261773E+11 | 0.277908E+10 | 0.00 | 0.127283E+09 | 0.287436E+09 | 0.00 | 0.569652E+11 | 0.00 | 1.87 |
Minimum of Months | 0.542858E+09 | 0.00 | 0.00 | 3128348.41 | 0.00 | 0.00 | 0.431240E+09 | 0.00 | 1.18 |
Maximum of Months | 0.633782E+10 | 0.120263E+10 | 0.00 | 22270760.73 | 0.175531E+09 | 0.00 | 0.845557E+10 | 0.00 | 2.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.491752E+11 | 0.00 | 0.00 | 126277.63 | 0.00 | 0.100326E+11 | 0.762273E+09 | 0.00 | 0.47 |
February | 0.413082E+11 | 0.00 | 0.00 | 3199739.01 | 0.00 | 0.489067E+10 | 0.391665E+10 | 0.00 | 0.49 |
March | 0.347570E+11 | 0.00 | 0.00 | 22639200.87 | 0.00 | 0.578764E+09 | 0.177901E+11 | 0.00 | 0.64 |
April | 0.193993E+11 | 7637760.17 | 0.00 | 52267680.50 | 3464449.31 | 1722928.26 | 0.228937E+11 | 0.00 | 0.78 |
May | 0.127350E+11 | 0.172100E+09 | 0.00 | 78070533.39 | 38472275.42 | 0.00 | 0.239139E+11 | 0.00 | 0.85 |
June | 0.561273E+10 | 0.594490E+10 | 0.00 | 59127045.32 | 0.116126E+09 | 0.00 | 0.113932E+11 | 0.00 | 0.84 |
July | 0.142512E+10 | 0.100538E+11 | 0.00 | 33767524.44 | 0.655309E+09 | 0.00 | 0.244210E+10 | 0.00 | 0.74 |
August | 0.331019E+10 | 0.521073E+10 | 0.00 | 60312349.29 | 0.243802E+09 | 0.00 | 0.704640E+10 | 0.00 | 0.85 |
September | 0.909254E+10 | 0.726656E+09 | 0.00 | 70238368.96 | 83036907.56 | 0.00 | 0.124986E+11 | 0.00 | 0.78 |
October | 0.258199E+11 | 4864520.13 | 0.00 | 41459762.33 | 25885739.54 | 30110721.16 | 0.152651E+11 | 0.00 | 0.70 |
November | 0.393908E+11 | 0.00 | 0.00 | 9916798.38 | 0.00 | 0.990189E+09 | 0.119227E+11 | 0.00 | 0.53 |
December | 0.492278E+11 | 0.00 | 0.00 | 425251.47 | 0.00 | 0.807749E+10 | 0.581900E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.291254E+12 | 0.221207E+11 | 0.00 | 0.431551E+09 | 0.116610E+10 | 0.246015E+11 | 0.130427E+12 | 0.00 | 0.68 |
Minimum of Months | 0.142512E+10 | 0.00 | 0.00 | 126277.63 | 0.00 | 0.00 | 0.581900E+09 | 0.00 | 0.41 |
Maximum of Months | 0.492278E+11 | 0.100538E+11 | 0.00 | 78070533.39 | 0.655309E+09 | 0.100326E+11 | 0.239139E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.648812E+11 | 0.00 | 0.00 | 3544037.85 | 0.00 | 0.106145E+11 | 0.390979E+10 | 0.00 | 0.97 |
February | 0.524229E+11 | 0.00 | 0.00 | 12839336.48 | 0.00 | 0.317685E+10 | 0.117216E+11 | 0.00 | 1.01 |
March | 0.402788E+11 | 0.00 | 0.00 | 44394030.91 | 0.00 | 0.181679E+09 | 0.347720E+11 | 0.00 | 1.37 |
April | 0.191384E+11 | 10068156.91 | 0.00 | 94876217.97 | 4583941.41 | 2279670.30 | 0.481590E+11 | 0.00 | 1.75 |
May | 0.148026E+11 | 0.204887E+09 | 0.00 | 0.116255E+09 | 52477203.90 | 0.00 | 0.403873E+11 | 0.00 | 1.80 |
June | 0.704226E+10 | 0.531105E+10 | 0.00 | 86687255.53 | 0.175375E+09 | 0.00 | 0.168590E+11 | 0.00 | 1.65 |
July | 0.298614E+10 | 0.101194E+11 | 0.00 | 36860877.05 | 0.746664E+09 | 0.00 | 0.245132E+10 | 0.00 | 1.37 |
August | 0.568089E+10 | 0.526396E+10 | 0.00 | 74676782.83 | 0.392271E+09 | 0.00 | 0.874933E+10 | 0.00 | 1.61 |
September | 0.140417E+11 | 0.598807E+09 | 0.00 | 84882179.96 | 0.109813E+09 | 0.00 | 0.170801E+11 | 0.00 | 1.61 |
October | 0.310855E+11 | 2075702.31 | 0.00 | 59798427.62 | 38249767.16 | 0.219561E+09 | 0.275991E+11 | 0.00 | 1.48 |
November | 0.496536E+11 | 0.00 | 0.00 | 17622174.95 | 0.00 | 0.545584E+09 | 0.199304E+11 | 0.00 | 1.10 |
December | 0.666808E+11 | 0.00 | 0.00 | 1753076.31 | 0.00 | 0.758123E+10 | 0.232597E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.368695E+12 | 0.215103E+11 | 0.00 | 0.634190E+09 | 0.151943E+10 | 0.223216E+11 | 0.233945E+12 | 0.00 | 1.38 |
Minimum of Months | 0.298614E+10 | 0.00 | 0.00 | 1753076.31 | 0.00 | 0.00 | 0.232597E+10 | 0.00 | 0.85 |
Maximum of Months | 0.666808E+11 | 0.101194E+11 | 0.00 | 0.116255E+09 | 0.746664E+09 | 0.106145E+11 | 0.481590E+11 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299398E+11 | 0.00 | 0.00 | 0.260615E+09 | 0.00 | 0.245252E+10 | 0.804136E+11 | 0.00 | 1.01 |
February | 0.227143E+11 | 0.00 | 0.00 | 0.197381E+09 | 0.00 | 0.131783E+10 | 0.767560E+11 | 0.00 | 1.08 |
March | 0.238092E+11 | 0.00 | 0.00 | 0.124514E+09 | 0.00 | 0.298916E+09 | 0.657186E+11 | 0.00 | 1.18 |
April | 0.171235E+11 | 13935944.67 | 0.00 | 88694827.38 | 1142320.25 | 0.00 | 0.381532E+11 | 0.00 | 1.05 |
May | 0.142406E+11 | 0.209027E+09 | 0.00 | 84809881.22 | 41888580.66 | 0.00 | 0.258826E+11 | 0.00 | 0.94 |
June | 0.740561E+10 | 0.602494E+10 | 0.00 | 53695897.50 | 0.128394E+09 | 0.00 | 0.104542E+11 | 0.00 | 0.86 |
July | 0.166780E+10 | 0.106436E+11 | 0.00 | 31553343.25 | 0.711949E+09 | 0.00 | 0.244378E+10 | 0.00 | 0.78 |
August | 0.339087E+10 | 0.623711E+10 | 0.00 | 72835981.70 | 0.261335E+09 | 0.00 | 0.811831E+10 | 0.00 | 0.98 |
September | 0.745611E+10 | 0.130099E+10 | 0.00 | 0.137495E+09 | 81838587.92 | 0.00 | 0.197156E+11 | 0.00 | 1.12 |
October | 0.142242E+11 | 34473336.36 | 0.00 | 0.271623E+09 | 11633408.62 | 1978076.75 | 0.645896E+11 | 0.00 | 1.42 |
November | 0.163143E+11 | 0.00 | 0.00 | 0.290769E+09 | 0.00 | 86679603.57 | 0.988783E+11 | 0.00 | 1.22 |
December | 0.239094E+11 | 0.00 | 0.00 | 0.279748E+09 | 0.00 | 0.187354E+10 | 0.937985E+11 | 0.00 | 0.90 |
Annual Sum or Average | 0.182196E+12 | 0.244641E+11 | 0.00 | 0.189373E+10 | 0.123818E+10 | 0.603146E+10 | 0.584922E+12 | 0.00 | 1.04 |
Minimum of Months | 0.166780E+10 | 0.00 | 0.00 | 31553343.25 | 0.00 | 0.00 | 0.244378E+10 | 0.00 | 0.78 |
Maximum of Months | 0.299398E+11 | 0.106436E+11 | 0.00 | 0.290769E+09 | 0.711949E+09 | 0.245252E+10 | 0.988783E+11 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.671189E+11 | 0.00 | 0.00 | 12784731.78 | 0.00 | 0.778676E+10 | 0.106913E+11 | 0.00 | 1.06 |
February | 0.543136E+11 | 0.00 | 0.00 | 23568792.17 | 0.00 | 0.351607E+10 | 0.169662E+11 | 0.00 | 1.16 |
March | 0.535708E+11 | 0.00 | 0.00 | 34962117.86 | 0.00 | 0.446888E+09 | 0.243255E+11 | 0.00 | 1.49 |
April | 0.274942E+11 | 13108421.39 | 0.00 | 73177838.02 | 4295813.00 | 0.00 | 0.317797E+11 | 0.00 | 1.71 |
May | 0.223505E+11 | 0.282721E+09 | 0.00 | 67882098.23 | 74665120.62 | 0.00 | 0.247075E+11 | 0.00 | 1.70 |
June | 0.120553E+11 | 0.757933E+10 | 0.00 | 36854904.16 | 0.139013E+09 | 0.00 | 0.812057E+10 | 0.00 | 1.51 |
July | 0.342042E+10 | 0.108332E+11 | 0.00 | 17189369.88 | 0.137879E+10 | 0.00 | 0.160120E+10 | 0.00 | 1.30 |
August | 0.693371E+10 | 0.591713E+10 | 0.00 | 45414977.96 | 0.602041E+09 | 0.00 | 0.565381E+10 | 0.00 | 1.53 |
September | 0.162866E+11 | 0.784743E+09 | 0.00 | 60923609.58 | 0.101913E+09 | 0.00 | 0.114252E+11 | 0.00 | 1.51 |
October | 0.393782E+11 | 5264931.32 | 0.00 | 53048874.54 | 38627664.73 | 42128750.07 | 0.200112E+11 | 0.00 | 1.56 |
November | 0.565371E+11 | 0.00 | 0.00 | 24329627.51 | 0.00 | 0.722356E+09 | 0.204946E+11 | 0.00 | 1.25 |
December | 0.640981E+11 | 0.00 | 0.00 | 13367757.35 | 0.00 | 0.727187E+10 | 0.117080E+11 | 0.00 | 0.93 |
Annual Sum or Average | 0.423558E+12 | 0.254155E+11 | 0.00 | 0.463505E+09 | 0.233935E+10 | 0.197861E+11 | 0.187485E+12 | 0.00 | 1.39 |
Minimum of Months | 0.342042E+10 | 0.00 | 0.00 | 12784731.78 | 0.00 | 0.00 | 0.160120E+10 | 0.00 | 0.93 |
Maximum of Months | 0.671189E+11 | 0.108332E+11 | 0.00 | 73177838.02 | 0.137879E+10 | 0.778676E+10 | 0.317797E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269282E+10 | 0.00 | 0.00 | 0.55 |
February | 0.386897E+10 | 0.00 | 0.00 | 87586.53 | 0.00 | 0.163939E+10 | 78168743.43 | 0.00 | 0.57 |
March | 0.411364E+10 | 0.00 | 0.00 | 902482.01 | 0.00 | 0.695954E+09 | 0.987385E+09 | 0.00 | 0.71 |
April | 0.238053E+10 | 0.00 | 0.00 | 4452198.28 | 0.00 | 0.109219E+09 | 0.201603E+10 | 0.00 | 0.86 |
May | 0.160164E+10 | 5548543.42 | 0.00 | 7489038.54 | 1677443.51 | 15054775.05 | 0.234014E+10 | 0.00 | 0.95 |
June | 0.713681E+09 | 0.384886E+09 | 0.00 | 6850413.46 | 11430177.10 | 0.00 | 0.107242E+10 | 0.00 | 0.87 |
July | 0.182793E+09 | 0.710557E+09 | 0.00 | 3612857.54 | 91358278.12 | 0.00 | 0.190382E+09 | 0.00 | 0.78 |
August | 0.438189E+09 | 0.337516E+09 | 0.00 | 7887894.61 | 29490351.91 | 0.00 | 0.686912E+09 | 0.00 | 0.91 |
September | 0.109529E+10 | 40818099.74 | 0.00 | 7113028.20 | 3991315.49 | 0.00 | 0.116743E+10 | 0.00 | 0.88 |
October | 0.301974E+10 | 145015.76 | 0.00 | 2956905.21 | 2089503.70 | 0.280686E+09 | 0.981402E+09 | 0.00 | 0.77 |
November | 0.440122E+10 | 0.00 | 0.00 | 175450.49 | 0.00 | 0.945637E+09 | 0.265904E+09 | 0.00 | 0.60 |
December | 0.339310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300478E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.290078E+11 | 0.147947E+10 | 0.00 | 41527854.86 | 0.140037E+09 | 0.938354E+10 | 0.978618E+10 | 0.00 | 0.75 |
Minimum of Months | 0.182793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.440122E+10 | 0.710557E+09 | 0.00 | 7887894.61 | 91358278.12 | 0.300478E+10 | 0.234014E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.534754E+10 | 0.00 | 0.00 | 5635.48 | 0.00 | 0.193869E+10 | 25298981.93 | 0.00 | 0.96 |
February | 0.468177E+10 | 0.00 | 0.00 | 443572.10 | 0.00 | 0.104212E+10 | 0.598560E+09 | 0.00 | 1.00 |
March | 0.384781E+10 | 0.00 | 0.00 | 3159066.74 | 0.00 | 0.414498E+09 | 0.261093E+10 | 0.00 | 1.29 |
April | 0.159501E+10 | 0.00 | 0.00 | 8801148.96 | 0.00 | 29770090.33 | 0.459177E+10 | 0.00 | 1.71 |
May | 0.127924E+10 | 5764688.03 | 0.00 | 11399752.49 | 2076359.78 | 5273983.48 | 0.405578E+10 | 0.00 | 1.84 |
June | 0.578010E+09 | 0.334727E+09 | 0.00 | 10230497.57 | 10793579.06 | 0.00 | 0.167531E+10 | 0.00 | 1.63 |
July | 0.235433E+09 | 0.747110E+09 | 0.00 | 4504288.36 | 71523737.38 | 0.00 | 0.225400E+09 | 0.00 | 1.38 |
August | 0.457360E+09 | 0.355236E+09 | 0.00 | 9829299.72 | 29440114.77 | 0.00 | 0.953800E+09 | 0.00 | 1.64 |
September | 0.113353E+10 | 31648542.94 | 0.00 | 9153254.95 | 4549111.41 | 0.00 | 0.174602E+10 | 0.00 | 1.66 |
October | 0.267189E+10 | 151102.72 | 0.00 | 5066474.95 | 2367469.37 | 0.205861E+09 | 0.231032E+10 | 0.00 | 1.41 |
November | 0.509055E+10 | 0.00 | 0.00 | 494853.87 | 0.00 | 0.611814E+09 | 0.672372E+09 | 0.00 | 1.06 |
December | 0.525700E+10 | 0.00 | 0.00 | 2937.65 | 0.00 | 0.194896E+10 | 12831452.60 | 0.00 | 0.86 |
Annual Sum or Average | 0.321751E+11 | 0.147464E+10 | 0.00 | 63090782.85 | 0.120750E+09 | 0.619698E+10 | 0.194784E+11 | 0.00 | 1.37 |
Minimum of Months | 0.235433E+09 | 0.00 | 0.00 | 2937.65 | 0.00 | 0.00 | 12831452.60 | 0.00 | 0.86 |
Maximum of Months | 0.534754E+10 | 0.747110E+09 | 0.00 | 11399752.49 | 71523737.38 | 0.194896E+10 | 0.459177E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295528E+10 | 0.00 | 0.00 | 14555041.19 | 0.00 | 0.121621E+10 | 0.658948E+10 | 0.00 | 1.00 |
February | 0.236125E+10 | 0.00 | 0.00 | 12946367.87 | 0.00 | 0.763398E+09 | 0.681516E+10 | 0.00 | 1.07 |
March | 0.260859E+10 | 0.00 | 0.00 | 9120159.72 | 0.00 | 0.533548E+09 | 0.575688E+10 | 0.00 | 1.14 |
April | 0.210662E+10 | 0.00 | 0.00 | 8018035.26 | 0.00 | 70097015.55 | 0.358907E+10 | 0.00 | 1.11 |
May | 0.173324E+10 | 6481653.65 | 0.00 | 8227356.31 | 1803982.50 | 5348291.13 | 0.258972E+10 | 0.00 | 1.04 |
June | 0.826993E+09 | 0.386138E+09 | 0.00 | 6528386.93 | 12895995.25 | 0.00 | 0.105223E+10 | 0.00 | 0.90 |
July | 0.214648E+09 | 0.739871E+09 | 0.00 | 3577711.93 | 0.103907E+09 | 0.00 | 0.179650E+09 | 0.00 | 0.82 |
August | 0.461179E+09 | 0.389982E+09 | 0.00 | 9608275.64 | 32885423.41 | 0.00 | 0.808618E+09 | 0.00 | 1.04 |
September | 0.886768E+09 | 68779071.34 | 0.00 | 14374811.59 | 3903857.76 | 0.00 | 0.202909E+10 | 0.00 | 1.24 |
October | 0.163555E+10 | 1290534.23 | 0.00 | 21814820.05 | 1311760.46 | 0.152596E+09 | 0.619113E+10 | 0.00 | 1.48 |
November | 0.209858E+10 | 0.00 | 0.00 | 18107833.25 | 0.00 | 0.366427E+09 | 0.862666E+10 | 0.00 | 1.20 |
December | 0.271073E+10 | 0.00 | 0.00 | 16257277.50 | 0.00 | 0.973258E+09 | 0.792836E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.205994E+11 | 0.159254E+10 | 0.00 | 0.143136E+09 | 0.156708E+09 | 0.408088E+10 | 0.521561E+11 | 0.00 | 1.08 |
Minimum of Months | 0.214648E+09 | 0.00 | 0.00 | 3577711.93 | 0.00 | 0.00 | 0.179650E+09 | 0.00 | 0.82 |
Maximum of Months | 0.295528E+10 | 0.739871E+09 | 0.00 | 21814820.05 | 0.103907E+09 | 0.121621E+10 | 0.862666E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.557020E+10 | 0.00 | 0.00 | 838402.66 | 0.00 | 0.189814E+10 | 0.894416E+09 | 0.00 | 1.11 |
February | 0.487757E+10 | 0.00 | 0.00 | 1903505.93 | 0.00 | 0.115693E+10 | 0.147272E+10 | 0.00 | 1.20 |
March | 0.526533E+10 | 0.00 | 0.00 | 2998211.59 | 0.00 | 0.587102E+09 | 0.213853E+10 | 0.00 | 1.54 |
April | 0.315081E+10 | 0.00 | 0.00 | 6904400.80 | 0.00 | 33788403.31 | 0.292495E+10 | 0.00 | 1.82 |
May | 0.262046E+10 | 8076166.43 | 0.00 | 7311634.80 | 2372370.60 | 3279936.04 | 0.237281E+10 | 0.00 | 1.86 |
June | 0.119422E+10 | 0.474778E+09 | 0.00 | 5184115.79 | 15484919.01 | 0.00 | 0.855694E+09 | 0.00 | 1.54 |
July | 0.324454E+09 | 0.721506E+09 | 0.00 | 2441753.90 | 0.168750E+09 | 0.00 | 0.121336E+09 | 0.00 | 1.33 |
August | 0.695863E+09 | 0.354539E+09 | 0.00 | 6596647.08 | 74311330.79 | 0.00 | 0.606446E+09 | 0.00 | 1.59 |
September | 0.169596E+10 | 41286201.52 | 0.00 | 6950551.10 | 2972065.64 | 0.00 | 0.105765E+10 | 0.00 | 1.64 |
October | 0.392966E+10 | 370006.79 | 0.00 | 4807668.23 | 2514224.26 | 0.179791E+09 | 0.169387E+10 | 0.00 | 1.61 |
November | 0.520493E+10 | 0.00 | 0.00 | 1833286.23 | 0.00 | 0.737326E+09 | 0.159242E+10 | 0.00 | 1.26 |
December | 0.546939E+10 | 0.00 | 0.00 | 832848.93 | 0.00 | 0.189845E+10 | 0.878637E+09 | 0.00 | 0.98 |
Annual Sum or Average | 0.399989E+11 | 0.160055E+10 | 0.00 | 48603027.05 | 0.266405E+09 | 0.649480E+10 | 0.166095E+11 | 0.00 | 1.46 |
Minimum of Months | 0.324454E+09 | 0.00 | 0.00 | 832848.93 | 0.00 | 0.00 | 0.121336E+09 | 0.00 | 0.98 |
Maximum of Months | 0.557020E+10 | 0.721506E+09 | 0.00 | 7311634.80 | 0.168750E+09 | 0.189845E+10 | 0.292495E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15908019.93 | 0.00 | 0.00 | 0.234088E+09 | 0.00 | 0.00 | 0.152506E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.427485E+09 | 0.00 | 0.00 | 0.127706E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.727603E+09 | 0.00 | 0.00 | 0.123852E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.875571E+09 | 0.00 | 0.00 | 0.996209E+10 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.00 | 0.218980E+09 | 0.00 | 0.00 | 0.736802E+10 | 0.00 | 0.33 |
June | 0.00 | 0.309221E+09 | 0.00 | 0.326073E+09 | 0.00 | 0.00 | 0.218948E+10 | 0.00 | 0.34 |
July | 0.00 | 0.244215E+10 | 0.00 | 51730932.53 | 0.00 | 0.00 | 45600468.27 | 0.00 | 0.31 |
August | 0.00 | 0.211478E+09 | 0.00 | 0.692149E+09 | 0.00 | 0.00 | 0.111908E+10 | 0.00 | 0.35 |
September | 0.00 | 0.235319E+09 | 0.00 | 0.168182E+09 | 0.00 | 0.00 | 0.204079E+10 | 0.00 | 0.32 |
October | 0.00 | 25232557.03 | 0.00 | 0.430385E+09 | 0.00 | 0.00 | 0.813952E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.658821E+09 | 0.00 | 0.00 | 0.120545E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.946050E+09 | 0.00 | 0.00 | 0.154562E+11 | 0.00 | 0.31 |
Annual Sum or Average | 15908019.93 | 0.322340E+10 | 0.00 | 0.575712E+10 | 0.00 | 0.00 | 0.987816E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 51730932.53 | 0.00 | 0.00 | 45600468.27 | 0.00 | 0.31 |
Maximum of Months | 15908019.93 | 0.244215E+10 | 0.00 | 0.946050E+09 | 0.00 | 0.00 | 0.154562E+11 | 0.00 | 0.35 |