Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 20:03:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31617.16 | 682.58 | 682.58 |
Net Site Energy | 31617.16 | 682.58 | 682.58 |
Total Source Energy | 94152.97 | 2032.65 | 2032.65 |
Net Source Energy | 94152.97 | 2032.65 | 2032.65 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2263.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2759.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 882.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2044.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2274.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 364.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 899.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2053.07 |
Humidification | 15.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 606.83 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28746.98 | 2870.18 | 0.00 | 0.00 | 0.00 | 4338.91 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 2263.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 465.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2293.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 882.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2274.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 364.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 854.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2053.07 | |
Humidification | General | 15.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 606.83 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.28 | 61.96 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 620.61 | 61.96 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.28 | 61.96 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 620.61 | 61.96 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28746.981 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28746.981 | 100.00 |
Total On-Site and Utility Electric Sources | 28746.981 | 100.00 |
Total Electricity End Uses | 28746.981 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4338.91 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4338.91 | 100.00 |
Total Water End Uses | 4338.91 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.83 |
Time Setpoint Not Met During Occupied Cooling | 55.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1261.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.6875 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.6875 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 26-DEC-07:10 | - | - | - | 29-AUG-15:30 |
Heating | 0.00 | 1304590.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 428171.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 92996.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147589.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55773.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 82904.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1974765.33 | 1312737.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 1304590.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 258482.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 147589.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 55773.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 33656.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2453.47 | 0.00 | 0.00 | 0.00 |
Cooling | 8739.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13600.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2795.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6473.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7201.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1154.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2847.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 48.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 657.81 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 91041.69 | 3111.28 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 52.97 | 0.00 | 0.00 | 0.00 |
Cooling | 188.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 61.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.20 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1965.48 | 67.17 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 52.97 | 0.00 | 0.00 | 0.00 |
Cooling | 188.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 61.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.20 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1965.48 | 67.17 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.87 |
DATACENTER BOT DIRECT AIR | 0.499253 |
DATACENTER MID DIRECT AIR | 4.77 |
DATACENTER TOP DIRECT AIR | 0.485622 |
DATACENTER BASEMENT DIRECT AIR | 21.57 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.04 | 0.314987 | 0.300000 | 1.81 | 0.839965 | 0.500000 | 0.001210 | 0.000397 | 1.81 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.68 | 0.335586 | 0.300000 | 17.00 | 0.894895 | 0.500000 | 0.001135 | 0.007449 | 17.00 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.53 | 0.344065 | 0.300000 | 1.66 | 0.917505 | 0.500000 | 0.001107 | 0.001552 | 2.12 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.843139 | 0.283252 | 0.300000 | 0.252942 | 0.755338 | 0.500000 | 0.001345 | 0.000114 | 0.252942 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.16 | 0.132351 | 0.300000 | 0.348857 | 0.352935 | 0.500000 | 0.002879 | 0.000122 | 0.348857 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.47 | 0.162469 | 0.300000 | 0.440994 | 0.433250 | 0.500000 | 0.002345 | 0.000197 | 0.440994 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.38 | 0.111344 | 0.300000 | 0.414676 | 0.300000 | 0.500000 | 0.003422 | 0.000107 | 0.414676 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.53 | 0.316959 | 0.300000 | 2.26 | 0.845225 | 0.500000 | 0.001202 | 0.003141 | 4.30 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.87 | 0.129654 | 0.300000 | 3.56 | 0.345743 | 0.500000 | 0.002939 | 0.002255 | 3.56 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.78 | 0.161612 | 0.300000 | 4.43 | 0.430966 | 0.500000 | 0.002357 | 0.003169 | 4.43 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.26 | 0.125544 | 0.300000 | 3.68 | 0.334783 | 0.500000 | 0.003035 | 0.002116 | 3.68 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.871779 | 0.273946 | 0.300000 | 0.261534 | 0.730523 | 0.500000 | 0.001391 | 0.000433 | 0.592562 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.17 | 0.131272 | 0.300000 | 0.351725 | 0.350058 | 0.500000 | 0.002902 | 0.000286 | 0.391824 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.58 | 0.150823 | 0.300000 | 0.475044 | 0.402196 | 0.500000 | 0.002526 | 0.000432 | 0.591198 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.30 | 0.118499 | 0.300000 | 0.389635 | 0.315998 | 0.500000 | 0.003215 | 0.000273 | 0.389635 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17979.93 | 0.000397 | 312.95 |
CORE_MID VAV BOX REHEAT COIL | 337154.16 | 0.007449 | 6334.72 |
CORE_TOP VAV BOX REHEAT COIL | 70263.19 | 0.001552 | 1467.26 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5170.22 | 0.000114 | 97.55 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5503.33 | 0.000122 | 100.79 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8930.93 | 0.000197 | 168.28 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4826.66 | 0.000107 | 85.60 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 142169.39 | 0.003141 | 2966.69 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 102080.39 | 0.002255 | 2049.86 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 143450.04 | 0.003169 | 2973.76 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 95790.67 | 0.002116 | 1883.25 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19590.40 | 0.000433 | 408.71 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12953.13 | 0.000286 | 270.23 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19545.43 | 0.000432 | 407.77 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12377.14 | 0.000273 | 255.23 |
CAV_BAS_HEATC | 285898.40 | 0.006317 | 5283.29 |
VAV_BOT WITH REHEAT_HEATC | 56100.11 | 0.001239 | 809.51 |
VAV_MID WITH REHEAT_HEATC | 540862.46 | 0.011950 | 7761.76 |
VAV_TOP WITH REHEAT_HEATC | 56863.26 | 0.001256 | 816.03 |
DATACENTER_EXTRAWATERHEATC | 1030923.99 | 0.022777 | 19179.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.87 | 5.87 | 5.87 | 5.87 | 5.87 | 5.87 | 1.00 | 1.00 | 5.87 |
VAV_BOT WITH REHEAT | 5.45 | 3.27 | 10.90 | 3.27 | 9.61 | 9.61 | 0.300000 | 0.340336 | 9.61 |
VAV_MID WITH REHEAT | 51.56 | 30.94 | 103.12 | 30.94 | 88.91 | 88.91 | 0.300000 | 0.347937 | 88.91 |
VAV_TOP WITH REHEAT | 5.23 | 3.14 | 10.45 | 4.06 | 9.35 | 9.35 | 0.300000 | 0.434550 | 9.35 |
AIRLOOP DATACENTER BASEMENT | 21.57 | 21.57 | 21.57 | 21.57 | 21.57 | 21.57 | 1.00 | 1.00 | 21.57 |
AIRLOOP DATACENTER BOT | 0.499253 | 0.499253 | 0.499253 | 0.499253 | 0.499253 | 0.499253 | 1.00 | 1.00 | 0.499253 |
AIRLOOP DATACENTER MID | 4.77 | 4.77 | 4.77 | 4.77 | 4.77 | 4.77 | 1.00 | 1.00 | 4.77 |
AIRLOOP DATACENTER TOP | 0.485622 | 0.485622 | 0.485622 | 0.485622 | 0.485622 | 0.485622 | 1.00 | 1.00 | 0.485622 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.87 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.61 | 2.70 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 88.91 | 28.34 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.35 | 2.97 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.57 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.499253 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.77 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.485622 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 104587.08 | 0.004449 | 5.87 | 0.008931 | 24.92 | 6.67 | 11.27 | 0.008398 |
VAV_BOT WITH REHEAT_COOLC | 180852.31 | 0.007694 | 9.61 | 0.008836 | 25.63 | 6.67 | 11.27 | 0.008398 |
VAV_MID WITH REHEAT_COOLC | 1710154.18 | 0.072754 | 88.91 | 0.008858 | 25.90 | 6.67 | 11.27 | 0.008398 |
VAV_TOP WITH REHEAT_COOLC | 176794.17 | 0.007521 | 9.35 | 0.008825 | 25.71 | 6.67 | 11.27 | 0.008398 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.87 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.004449 | 0.000107 |
CAV_BAS_HEATC_CONTROLLER | 0.006317 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007694 | 0.000062 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001239 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.072754 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011950 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007521 | 0.000063 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001256 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022777 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.61 |
VAV_MID WITH REHEAT FAN | 88.91 |
VAV_TOP WITH REHEAT FAN | 9.35 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.57 | 424720.91 | 304452.07 | 0.010401 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.499253 | 9549.20 | 6947.56 | 0.000234 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.77 | 91235.74 | 66379.85 | 0.002234 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.485622 | 9288.34 | 6757.83 | 0.000227 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.57 | 21.57 | 21.57 | 21.57 | 424720.91 | 424720.91 | 17838.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.499253 | 0.499253 | 0.499253 | 0.499253 | 9549.20 | 9549.20 | 824.08 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.77 | 4.77 | 4.77 | 4.77 | 91235.74 | 91235.74 | 8240.84 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.485622 | 0.485622 | 0.485622 | 0.485622 | 9288.34 | 9288.34 | 824.08 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.57 |
DATACENTER BOT SUPPLY FAN | 0.499253 |
DATACENTER MID SUPPLY FAN | 4.77 |
DATACENTER TOP SUPPLY FAN | 0.485622 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.57 | 424720.91 | 0.010401 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.499253 | 9549.20 | 0.000234 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.77 | 91235.74 | 0.002234 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.485622 | 9288.34 | 0.000227 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 17838.92 | |
DATACENTER_EXTRAELECHEATC | 424720.91 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 824.08 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 8240.84 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 824.08 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000143 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.092418 | 22135.00 |
HEATSYS1 PUMP | 0.065584 | 16755.85 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.092418 | 11.09 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.065584 | 7.87 |
COOLSYS1_SUPPLY | 0.092418 | 11.09 |
SINGLE WATER PLANT LOOP | 0.013097 | 1.57 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.092418 | 0.092418 | 387926.38 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 PUMP | 0.092418 | 7378.33 |
PLANT CIRC PUMP | 0.013097 | 3340.41 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2968433.23 | 1484216.61 | 0.065584 |
DUMMY BOILER | 539487.22 | 93894.07 | 0.013097 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.092418 | 0.046475 | 1095134.78 | 1100328.91 | 0.054659 |
COOLSYS1 CHILLER2 | 0.092418 | 0.046475 | 1095134.78 | 1100328.91 | 0.054659 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013097 | 139666.47 | 60092.75 | 69833.23 | 7879.72 | 21494.33 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.109319 | 13.12 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.109319 | 27928.26 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 44.93 | 1045715.94 | 8.99 | 130714.49 |
TOWERWATERSYS COOLTOWER 2 | 44.93 | 1045715.94 | 8.99 | 130714.49 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.045246 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.688 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.529 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 9.688 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 26925.749 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26925.749 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 7591.909 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7591.909 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.4744 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.941 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.31219756E-14 | -0.25237900E-15 | -0.17078023E-09 | -0.40080417E-16 |
51 | 8 | 0.24827770E-07 | 0.64895754E-13 | 0.40814970E-03 | -0.28230026E-09 |
52 | 7 | -0.13145170E-01 | 0.32788080E-08 | -0.24386180E-01 | 0.14946539E-03 |
53 | 6 | 0.42990022 | 0.11289000E-05 | 0.49294528 | -0.50371474E-02 |
54 | 5 | -5.4301032 | 0.41776872E-04 | -4.6011904 | 0.66154067E-01 |
55 | 4 | 34.062169 | 0.33899226E-03 | 22.064921 | -0.43618800 |
56 | 3 | -113.47938 | 0.73347792E-03 | -56.858567 | 1.5477483 |
57 | 2 | 199.36357 | 0.40991987E-03 | 79.008039 | -2.9361691 |
58 | 1 | -171.98885 | 0.43498902E-04 | -55.585984 | 2.7600347 |
59 | 0 | 57.057407 | 0.24596459E-06 | 15.505383 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 80305.69475 | 80305.69475 | 5.86637 | 5.86637 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 82672.34136 | 82672.34136 | 6.03849 | 6.03849 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 776178.79753 | 776178.79753 | 56.67833 | 56.67833 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 168391.30334 | 168391.30334 | 7.14153 | 10.77757 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 75001.39305 | 75001.39305 | 5.52816 | 5.52816 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.79438E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 49234.67245 | 49234.67245 | 2.11870 | 2.11870 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11439.13833 | 11439.13833 | 0.84314 | 0.84314 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.79438E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2672.21600 | 2672.21600 | 0.11388 | 0.13532 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15777.16620 | 15777.16620 | 1.16286 | 1.16286 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2055.68016 | 2055.68016 | 8.77745E-002 | 8.77745E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19943.82757 | 19943.82757 | 1.46998 | 1.46998 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 28.88000 | 8.79438E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4566.88397 | 4566.88397 | 0.19600 | 0.19600 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18753.68969 | 18753.68969 | 1.38225 | 1.38225 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 725.72825 | 725.72825 | 3.15558E-002 | 8.72074E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 103148.16863 | 103148.16863 | 7.53474 | 7.53474 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 99561.48238 | 99561.48238 | 4.29718 | 4.29718 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 161051.93466 | 161051.93466 | 11.87047 | 11.87047 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 66767.60407 | 66767.60407 | 2.88218 | 2.88218 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 200494.88312 | 200494.88312 | 14.77769 | 14.77769 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.79438E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 99492.44049 | 99492.44049 | 4.29418 | 4.29418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 166324.57935 | 166324.57935 | 12.25909 | 12.25909 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 27.59733 | 8.79438E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 59333.05312 | 59333.05312 | 2.56007 | 2.56007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11827.71380 | 11827.71380 | 0.87178 | 0.87178 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.79438E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13712.24288 | 13712.24288 | 0.59256 | 0.59256 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15906.69221 | 15906.69221 | 1.17242 | 1.17242 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9066.24432 | 9066.24432 | 0.39182 | 0.39182 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21483.72368 | 21483.72368 | 1.58348 | 1.58348 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13680.80764 | 13680.80764 | 0.59120 | 0.59120 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17621.19007 | 17621.19007 | 1.29878 | 1.29878 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8512.22744 | 8512.22744 | 0.36780 | 0.36780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8588.73361 | 8588.73361 | 0.49925 | 0.49925 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 82061.46520 | 82061.46520 | 4.77013 | 4.77013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8354.25121 | 8354.25121 | 0.48562 | 0.48562 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371114.91815 | 371114.91815 | 21.57246 | 21.57246 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 19.20800 | 8.79438E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 76618.33 | 5.86637 | 5.86637 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 63268.17 | 1.20008 | 1.20008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 137074.15 | 9.60527 | 9.60527 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 32119.91 | 1.58407 | 1.58407 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1259870.59 | 88.91282 | 88.91282 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 503093.43 | 24.81118 | 24.81118 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 143932.14 | 9.34780 | 9.34780 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 60000.32 | 4.06209 | 4.06209 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:40:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365796.23 | 21.57246 | 21.57246 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17838.92 | 0.33837 | 0.33837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8434.74 | 0.49925 | 0.49925 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.08 | 1.56314E-002 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80580.72 | 4.77013 | 4.77013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8240.84 | 0.15631 | 0.15631 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8203.89 | 0.48562 | 0.48562 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.08 | 1.56314E-002 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.86637 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.03849 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31499 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.81155 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83996 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20957E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.97245E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81155 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17979.93237 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.97245E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 312.94535 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.67833 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33559 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 17.00350 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89490 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13533E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.44901E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 17.00350 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 337154.16278 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.44901E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6334.72286 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.52816 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34406 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.65845 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91751 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10735E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55238E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.11870 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70263.18991 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55238E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1467.26074 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84314 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28325 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25294 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75534 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34509E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14230E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25294 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5170.21849 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14230E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 97.54678 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16286 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13235 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34886 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35294 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87872E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21589E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34886 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5503.32807 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21589E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 100.79179 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46998 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16247 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44099 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43325 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34507E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97318E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44099 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8930.93439 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97318E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 168.28345 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38225 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11134 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41468 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42184E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06639E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41468 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4826.66017 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06639E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.59817 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.53474 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31696 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26042 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84522 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20205E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.14106E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.29718 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 142169.39324 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.14106E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2966.69040 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.87047 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12965 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.56114 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34574 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93860E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25534E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.56114 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 102080.38955 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25534E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2049.86457 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.77769 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16161 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.43331 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43097 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35749E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16935E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.43331 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 143450.04014 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16935E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2973.76036 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.25909 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12554 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.67773 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33478 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03480E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11638E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.67773 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 95790.66932 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11638E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1883.25317 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87178 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27395 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26153 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73052 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39078E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.32826E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59256 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19590.40498 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.32826E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 408.70970 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17242 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13127 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35173 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35006 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90238E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.86184E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39182 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12953.13121 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.86184E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.23311 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58348 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15082 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47504 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40220 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52613E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.31832E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59120 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19545.43228 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.31832E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 407.77213 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29878 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11850 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38964 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31600 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21521E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.73458E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38964 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12377.13547 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73458E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 255.22984 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49925 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.77013 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48562 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.57246 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.86637 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.86637 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.86637 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.86637 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.86637 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.86637 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.44836 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.26902 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.89672 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.26902 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.60527 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.60527 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34034 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 51.56016 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.93609 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 103.12031 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.93609 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 88.91282 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 88.91282 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34794 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.22731 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13639 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.45462 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.06209 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.34780 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.34780 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43455 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.57246 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.57246 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.57246 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.57246 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.57246 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.57246 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49925 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49925 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49925 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49925 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49925 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49925 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.77013 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.77013 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.77013 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.77013 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.77013 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.77013 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48562 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48562 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48562 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48562 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48562 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48562 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.86637 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.60527 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 88.91282 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.34780 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.57246 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49925 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.77013 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48562 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.86637 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 104587.07560 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.44938E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.86637 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.93052E-003 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.91521 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.27494 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 285898.40036 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.31658E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 5283.29060 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.86637 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.44938E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.07024E-004 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.31658E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.60527 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.70194 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 180852.30574 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.69388E-003 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.60527 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.83589E-003 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.62777 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.27467 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 56100.11086 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.23946E-003 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 809.51136 |
318 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.60527 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.69388E-003 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.18922E-005 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23946E-003 |
322 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 88.91282 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 28.33542 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 1710154.18084 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.27539E-002 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 88.91282 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.85833E-003 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.89636 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.27474 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 540862.45508 |
333 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.19497E-002 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 7761.76002 |
335 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 88.91282 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.27539E-002 |
337 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.54522E-006 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.19497E-002 |
339 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.34780 |
340 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.96819 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 176794.17309 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.52123E-003 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.34780 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.82503E-003 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.71455 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.27464 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
349 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 56863.25531 |
350 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.25632E-003 |
351 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 816.02806 |
352 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.34780 |
353 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.52123E-003 |
354 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.33128E-005 |
355 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.25632E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.57246 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.57246 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 424720.91094 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 304452.07368 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04014E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.57246 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.57246 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.57246 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.57246 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 424720.91094 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 424720.91094 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17838.91681 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.57246 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.57246 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 424720.91094 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04014E-002 |
374 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 17838.91681 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.43320E-004 |
376 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 424720.91094 |
380 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
381 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1030923.98667 |
382 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.27770E-002 |
383 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19179.39407 |
384 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27770E-002 |
385 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.09066E-005 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49925 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.49925 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9549.20434 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6947.56414 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.33859E-004 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49925 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49925 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49925 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49925 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9549.20434 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9549.20434 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.08405 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
399 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49925 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.49925 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9549.20434 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.33859E-004 |
403 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 824.08405 |
404 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.77013 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.77013 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 91235.73570 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 66379.84863 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.23436E-003 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.77013 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.77013 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.77013 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.77013 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91235.73570 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91235.73570 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8240.84054 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.77013 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.77013 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 91235.73570 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.23436E-003 |
421 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 8240.84054 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48562 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.48562 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 9288.34005 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6757.82921 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.27471E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48562 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48562 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48562 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48562 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9288.34005 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9288.34005 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.08405 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48562 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.48562 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 9288.34005 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.27471E-004 |
439 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 824.08405 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.24184E-002 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22134.99728 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.24184E-002 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.09021 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.24184E-002 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.24184E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 387926.38130 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
448 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
449 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
450 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
451 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
452 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
453 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.55839E-002 |
454 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 7.87007 |
455 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.55839E-002 |
456 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 16755.84673 |
457 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2968433.23065 |
458 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1484216.61500 |
459 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.55839E-002 |
460 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.24184E-002 |
461 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.09021 |
462 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.24184E-002 |
463 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 7378.33243 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.24184E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.64754E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1095134.78482 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1100328.91000 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.46593E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.24184E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.64754E-002 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1095134.78482 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1100328.91000 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.46593E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.30971E-002 |
475 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.57165 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.30971E-002 |
477 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3340.40916 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.30971E-002 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60092.75050 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21494.33207 |
484 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 539487.22124 |
485 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
486 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.30971E-002 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10932 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.11823 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10932 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 27928.26058 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 44.93126 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1045715.94421 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.98625 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 130714.49303 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 44.93126 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1045715.94421 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.98625 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 130714.49303 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.52460E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.52460E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17057.93 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 320090.78 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 66666.17 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4908.42 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5226.12 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8478.78 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4578.36 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 134891.51 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 96875.57 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 136109.39 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 90914.51 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18587.55 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12290.05 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18544.88 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11743.99 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 227281.39 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 43122.05 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 412469.43 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 43364.73 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 827672.56 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 149369.91 | 103505.90 | 45864.02 | 0.69 | 19022.22 | 192.93 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 252072.44 | 172860.70 | 79211.74 | 0.69 | 32380.93 | 328.43 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2350415.98 | 1607295.11 | 743120.86 | 0.68 | 300131.06 | 3044.10 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 245720.06 | 168399.30 | 77320.76 | 0.69 | 31532.43 | 319.82 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.89 | 23.50 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.89 | 23.50 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.4322960079 | 0.5238721713 | Pass | Pass | 1.8106121893 | 2.5313764497 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.2827495383E-003 | 1.4537831598E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.0299646239E-003 | 1.9413209975E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.5935115593E-002 | 1.3579131941E-002 | Pass | Pass | 0.4216208912 | 0.4844435924 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.5157552511E-002 | 1.2183609629E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.5785558004E-002 | 1.3560153436E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.3521788700E-002 | 1.2917838169E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.5896223837E-002 | 1.2329883945E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.0550399994E-002 | 1.5411447447E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.1231356282E-002 | 1.6563581345E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.1364925011E-002 | 1.6892678453E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.2447180965E-002 | 1.5944715222E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2015753442 | 0.1962636611 | Pass | Pass | 9.3485971553 | 51.2385684024 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2153483180 | 0.2096378227 | Pass | Pass | 7.8915846279 | 43.3696348956 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1969907336 | 0.1950506128 | Pass | Pass | 7.6492140863 | 39.4576729608 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.3012164839E-002 | 0.1186163954 | Pass | Pass | 5.4002668949 | 16.1512455526 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3637921571E-003 | 4.8654298263E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.9703933532E-003 | 6.2857832819E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.0396151090E-002 | 5.5353896020E-002 | Pass | Pass | 0.4273740008 | 0.4814711535 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3528735344E-014 | 2.5394651244E-014 | Pass | Pass | 8.7609517981E-004 | 7.5402921981E-004 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.3858268662E-003 | 4.3566140244E-003 | Pass | Pass | 8.4282434684E-003 | 1.8580117890E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5356531057E-003 | 4.2889643617E-003 | Pass | Pass | 2.1191599061E-003 | 1.8504686772E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0470636703E-013 | 7.0440935221E-014 | Pass | Pass | 2.9757060435E-005 | 2.9913880354E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 1043.06 | 2.159 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 9.6875 | 2779.43 | 26925.75 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 257.68 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
CORE_MID_LIGHTS | CORE_MID | 9.6875 | 24961.20 | 241812.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 2314.14 |
CORE_TOP_LIGHTS | CORE_TOP | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 9.6875 | 3134.13 | 30361.93 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 9.6875 | 3134.20 | 30362.59 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 9.6875 | 783.68 | 7591.91 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 72.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 9.6875 | 362.03 | 3507.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 33.56 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
Interior Lighting Total | 9.6875 | 46320.38 | 448729.56 | 1321.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 56280.71 | AstronomicalClock | - | 83.55 | 83.55 | 882.64 | |
Exterior Lighting Total | 56280.71 | 882.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2167391.88 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1484216.61 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1100328.91 | 6.11 | 6.89 | 23.50 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1100328.91 | 6.11 | 6.89 | 23.50 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1045715.94 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1045715.94 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 104587.08 | 149369.91 | 103505.90 | 45864.02 | 0.69 | - | 19022.22 | 192.93 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 180852.31 | 252072.44 | 172860.70 | 79211.74 | 0.69 | - | 32380.93 | 328.43 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 1710154.18 | 2350415.98 | 1607295.11 | 743120.86 | 0.68 | - | 300131.06 | 3044.10 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 176794.17 | 245720.06 | 168399.30 | 77320.76 | 0.69 | - | 31532.43 | 319.82 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 424720.91 | 304452.07 | 120268.84 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9549.20 | 6947.56 | 2601.64 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91235.74 | 66379.85 | 24855.89 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9288.34 | 6757.83 | 2530.51 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17979.93 | 17057.93 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 337154.16 | 320090.78 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 70263.19 | 66666.17 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5170.22 | 4908.42 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5503.33 | 5226.12 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8930.93 | 8478.78 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4826.66 | 4578.36 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 142169.39 | 134891.51 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 102080.39 | 96875.57 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 143450.04 | 136109.39 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 95790.67 | 90914.51 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19590.40 | 18587.55 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12953.13 | 12290.05 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19545.43 | 18544.88 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12377.14 | 11743.99 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 285898.40 | 227281.39 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 56100.11 | 43122.05 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 540862.46 | 412469.43 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 56863.26 | 43364.73 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 424720.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9549.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 91235.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 9288.34 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 17838.92 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1030923.99 | 827672.56 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 824.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 8240.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 824.08 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 5.87 | 10847.22 | 1849.05 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.61 | 21819.28 | 2271.59 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 88.91 | 203052.67 | 2283.73 | 1.00 | 1.07 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.35 | 21347.82 | 2283.73 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.57 | 35766.56 | 1657.97 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 559.22 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.77 | 5343.06 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 543.95 | 1120.11 | 1.00 | 1.62 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.092418 | 22135.00 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.065584 | 16755.85 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.092418 | 7378.33 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013097 | 3340.41 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.109319 | 27928.26 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 80305.69 | 80305.69 | 28.89 | 5.866 | 5.866 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00879 | 1.200 | 0.00 |
CORE_BOTTOM | 82672.34 | 82672.34 | 33.12 | 6.038 | 6.038 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 21.70 | 0.00879 | 1.078 | 0.00 |
CORE_MID | 776178.80 | 776178.80 | 310.95 | 56.678 | 56.678 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 21.70 | 0.00879 | 10.778 | 0.00 |
CORE_TOP | 75001.39 | 75001.39 | 30.05 | 5.528 | 5.528 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00891 | 29.40 | 0.00879 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11439.14 | 11439.14 | 36.50 | 0.843 | 0.843 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00883 | 29.23 | 0.00879 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15777.17 | 15777.17 | 78.11 | 1.163 | 1.163 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00866 | 22.36 | 0.00879 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19943.83 | 19943.83 | 63.63 | 1.470 | 1.470 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00869 | 28.88 | 0.00879 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18753.69 | 18753.69 | 92.85 | 1.382 | 1.382 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 27.77 | 0.00879 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 103148.17 | 103148.17 | 329.11 | 7.535 | 7.535 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 21.70 | 0.00879 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 161051.93 | 161051.93 | 797.38 | 11.870 | 11.870 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00865 | 23.02 | 0.00879 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 200494.88 | 200494.88 | 639.70 | 14.778 | 14.778 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00869 | 28.97 | 0.00879 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 166324.58 | 166324.58 | 823.49 | 12.259 | 12.259 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00865 | 27.60 | 0.00879 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11827.71 | 11827.71 | 37.74 | 0.872 | 0.872 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00879 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15906.69 | 15906.69 | 78.76 | 1.172 | 1.172 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 23.02 | 0.00879 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21483.72 | 21483.72 | 68.55 | 1.583 | 1.583 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00868 | 29.05 | 0.00879 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17621.19 | 17621.19 | 87.24 | 1.299 | 1.299 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 27.77 | 0.00879 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8588.73 | 8588.73 | 237.24 | 0.499 | 0.499 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 82061.47 | 82061.47 | 2266.72 | 4.770 | 4.770 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8354.25 | 8354.25 | 230.76 | 0.486 | 0.486 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371114.92 | 371114.92 | 473.55 | 21.572 | 21.572 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 27.00 | 27.00 | 0.00850 | 19.21 | 0.00879 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 | |
CORE_MID | 168391.30 | 168391.30 | 67.46 | 7.142 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 49234.67 | 49234.67 | 19.72 | 2.119 | 2.119 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2672.22 | 2672.22 | 8.53 | 0.114 | 0.135 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00542 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2055.68 | 2055.68 | 10.18 | 0.088 | 0.088 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00582 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4566.88 | 4566.88 | 14.57 | 0.196 | 0.196 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00654 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 725.73 | 725.73 | 3.59 | 0.032 | 0.087 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 21.00 | 21.00 | 0.00608 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 99561.48 | 99561.48 | 317.67 | 4.297 | 4.297 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 66767.60 | 66767.60 | 330.57 | 2.882 | 2.882 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00759 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 99492.44 | 99492.44 | 317.44 | 4.294 | 4.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 59333.05 | 59333.05 | 293.76 | 2.560 | 2.560 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13712.24 | 13712.24 | 43.75 | 0.593 | 0.593 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9066.24 | 9066.24 | 44.89 | 0.392 | 0.392 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13680.81 | 13680.81 | 43.65 | 0.591 | 0.591 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8512.23 | 8512.23 | 42.14 | 0.368 | 0.368 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.87 | 5.87 | 1.20 | 1.20 | 5.8664 | 5.8664 | 5.8664 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.61 | 9.61 | 1.58 | 1.58 | 9.6053 | 3.2690 | 9.6053 | 0.3403 | 0.3000 |
VAV_MID WITH REHEAT | 88.91 | 88.91 | 24.81 | 24.81 | 88.9128 | 30.9361 | 88.9128 | 0.3479 | 0.3000 |
VAV_TOP WITH REHEAT | 9.35 | 9.35 | 4.06 | 4.06 | 9.3478 | 4.0621 | 9.3478 | 0.4346 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.57 | 21.57 | 0.34 | 0.34 | 21.5725 | 21.5725 | 21.5725 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.4993 | 0.4993 | 0.4993 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.77 | 4.77 | 0.16 | 0.16 | 4.7701 | 4.7701 | 4.7701 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4856 | 0.4856 | 0.4856 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17979.932 | 17979.932 | 1.811547 | 0.00039724 | 312.945 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17057.93 | 17979.93 | 1.811547 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18052.26 | 18052.26 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 337154.163 | 337154.163 | 17.003499 | 0.00744901 | 6334.723 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 320090.78 | 337154.16 | 17.003499 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 168391.30 | 0.00 | 338767.08 | 338767.08 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 70263.190 | 70263.190 | 2.118703 | 0.00155238 | 1467.261 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 66666.17 | 70263.19 | 2.118703 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 49234.67 | 0.00 | 70584.01 | 70584.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5170.218 | 5170.218 | 0.252942 | 0.00011423 | 97.547 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4908.42 | 5170.22 | 0.252942 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00541791 | 34.6722 | 2672.22 | 0.00 | 5194.90 | 5194.90 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5503.328 | 5503.328 | 0.348857 | 0.00012159 | 100.792 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5226.12 | 5503.33 | 0.348857 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00581723 | 37.2046 | 2055.68 | 0.00 | 5530.43 | 5530.43 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8930.934 | 8930.934 | 0.440994 | 0.00019732 | 168.283 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8478.78 | 8930.93 | 0.440994 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00653739 | 41.7621 | 4566.88 | 0.00 | 8973.59 | 8973.59 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4826.660 | 4826.660 | 0.414676 | 0.00010664 | 85.598 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 4578.36 | 4826.66 | 0.414676 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00608016 | 38.8659 | 725.73 | 0.00 | 4845.54 | 4845.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 142169.393 | 142169.393 | 4.297177 | 0.00314106 | 2966.690 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 134891.51 | 142169.39 | 4.297177 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00755281 | 48.1685 | 99561.48 | 0.00 | 142818.47 | 142818.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 102080.390 | 102080.390 | 3.561140 | 0.00225534 | 2049.865 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 96875.57 | 102080.39 | 3.561140 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00759185 | 48.4142 | 66767.60 | 0.00 | 102554.41 | 102554.41 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 143450.040 | 143450.040 | 4.433308 | 0.00316935 | 2973.760 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 136109.39 | 143450.04 | 4.433308 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00755179 | 48.1621 | 99492.44 | 0.00 | 144104.59 | 144104.59 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 95790.669 | 95790.669 | 3.677726 | 0.00211638 | 1883.253 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 90914.51 | 95790.67 | 3.677726 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00744481 | 47.4886 | 59333.05 | 0.00 | 96236.35 | 96236.35 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19590.405 | 19590.405 | 0.592562 | 0.00043283 | 408.710 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18587.55 | 19590.40 | 0.592562 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777008 | 49.5354 | 13712.24 | 0.00 | 19679.84 | 19679.84 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12953.131 | 12953.131 | 0.391824 | 0.00028618 | 270.233 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12290.05 | 12953.13 | 0.391824 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777397 | 49.5599 | 9066.24 | 0.00 | 13012.27 | 13012.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19545.432 | 19545.432 | 0.591198 | 0.00043183 | 407.772 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18544.88 | 19545.43 | 0.591198 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776920 | 49.5298 | 13680.81 | 0.00 | 19634.66 | 19634.66 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12377.135 | 12377.135 | 0.389635 | 0.00027346 | 255.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11743.99 | 12377.14 | 0.389635 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00774224 | 49.3604 | 8512.23 | 0.00 | 12433.61 | 12433.61 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 104587.076 | -999.000 | 5.866373 | 0.00444938 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 104587.08 | 95348.24 | 5.866373 | 24.92 | 16.91 | 0.00893052 | 11.27 | 11.27 | 0.00839822 | 28.05 | 0.00879438 | 17.86 | 20.4570 | 24.00 | 0.00893449 | 47.3803 | 71934.47 | 0.00 | 118558.20 | 99995.10 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 285898.400 | 285898.400 | 5.866373 | 0.00631658 | 5283.291 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 227281.39 | 285898.40 | 5.866373 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.4570 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 239769.86 | 239769.86 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 180852.306 | -999.000 | 9.605274 | 0.00769388 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 180852.31 | 168113.79 | 9.605274 | 25.63 | 17.07 | 0.00883589 | 11.27 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 28.1298 | 24.00 | 0.00879465 | 46.6485 | 121546.89 | 0.00 | 203815.66 | 173965.63 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 56100.111 | 56100.111 | 2.881582 | 0.00123946 | 809.511 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43122.05 | 56100.11 | 2.881582 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 93.7658 | 21.00 | 0.00737180 | 47.0253 | 9856.84 | 0.00 | 45597.55 | 45597.55 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1710154.181 | -999.000 | 88.912816 | 0.07275391 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1710154.18 | 1586093.66 | 88.912816 | 25.90 | 17.18 | 0.00885833 | 11.27 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 31.8688 | 24.00 | 0.00881183 | 46.7384 | 1094244.76 | 0.00 | 1922854.13 | 1639621.71 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 540862.455 | 540862.455 | 26.673845 | 0.01194969 | 7761.760 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 412469.43 | 540862.46 | 26.673845 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 106.2292 | 21.00 | 0.00774028 | 49.3475 | 493545.88 | 0.00 | 436141.17 | 436141.17 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 176794.173 | -999.000 | 9.347796 | 0.00752123 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 176794.17 | 164696.19 | 9.347796 | 25.71 | 17.10 | 0.00882503 | 11.27 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 31.7528 | 24.00 | 0.00880361 | 46.6954 | 126770.36 | 0.00 | 199146.02 | 170320.44 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 56863.255 | 56863.255 | 2.804339 | 0.00125632 | 816.028 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43364.73 | 56863.26 | 2.804339 | -4.04 | -4.05 | 0.00272328 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 105.8428 | 21.00 | 0.00788773 | 50.2746 | 68697.58 | 0.00 | 45853.45 | 45853.45 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 424720.911 | 304452.074 | 21.572460 | 0.01040139 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 457212.45 | 456902.85 | -999.0 | 28.46 | 17.76 | 0.00850462 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 370557.65 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9549.204 | 6947.564 | 0.499253 | 0.00023386 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 10329.04 | 10314.67 | -999.0 | 27.92 | 17.58 | 0.00850922 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 8588.73 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91235.736 | 66379.849 | 4.770133 | 0.00223436 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 98687.06 | 98543.31 | -999.0 | 27.92 | 17.58 | 0.00850965 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 82061.47 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9288.340 | 6757.829 | 0.485622 | 0.00022747 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 10046.91 | 10032.53 | -999.0 | 27.92 | 17.58 | 0.00850948 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 8354.25 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 424720.911 | 424720.911 | 21.572460 | 0.01040139 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 424720.91 | 424720.91 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5685 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9549.204 | 9549.204 | 0.499253 | 0.00023386 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9549.20 | 9549.20 | 0.499253 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1310 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91235.736 | 91235.736 | 4.770133 | 0.00223436 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 91235.74 | 91235.74 | 4.770133 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2769 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9288.340 | 9288.340 | 0.485622 | 0.00022747 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9288.34 | 9288.34 | 0.485622 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2188 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17838.917 | 17838.917 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17838.92 | 17838.92 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5685 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1154108.54 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5685 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1030923.987 | 1030923.987 | 21.572460 | 0.02277701 | 19179.394 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 827672.56 | 1030923.99 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5685 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 0.499253 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1310 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8240.841 | 8240.841 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8240.84 | 8240.84 | 4.770133 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2769 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 0.485622 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2188 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17979.932 | 17979.932 | 1.811547 | 0.00039724 | 312.945 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.5633 | 0.605704 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17057.93 | 17979.93 | 1.0000 | 2.15028904 | 1.811547 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.39720411 | 60.00 | 49.00 | 11.00 | 0.000 | 17057.93 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18052.26 | 18052.26 | 2.15028904 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 337154.163 | 337154.163 | 17.003499 | 0.00744901 | 6334.723 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 10.5704 | 11.357984 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 320090.78 | 337154.16 | 1.0000 | 20.18299617 | 17.003499 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 7.44824937 | 60.00 | 49.00 | 11.00 | 0.000 | 320090.78 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 168391.30 | 0.00 | 338767.08 | 338767.08 | 20.18299617 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.26 | 17.77 | 0.00800000 | 49844.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 70263.190 | 70263.190 | 2.118703 | 0.00155238 | 1467.261 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 2.2015 | 2.367013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 66666.17 | 70263.19 | 1.0000 | 2.51488102 | 2.118703 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 1.55222097 | 60.00 | 49.00 | 11.00 | 0.000 | 66666.17 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 49234.67 | 0.00 | 70584.01 | 70584.01 | 2.51488102 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.32 | 21.25 | 0.00800000 | 61126.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5170.218 | 5170.218 | 0.252942 | 0.00011423 | 97.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.1621 | 0.174173 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4908.42 | 5170.22 | 1.0000 | 0.30023953 | 0.252942 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.11421801 | 60.00 | 49.00 | 11.00 | 0.000 | 4908.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.83 | 0.00541791 | 21.00 | 0.00541791 | 34.6722 | 2672.22 | 0.00 | 5194.90 | 5194.90 | 0.30023953 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.77 | 17.94 | 0.00800000 | 50362.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5503.328 | 5503.328 | 0.348857 | 0.00012159 | 100.792 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.1726 | 0.185395 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5226.12 | 5503.33 | 1.0000 | 0.41409063 | 0.348857 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.12157691 | 60.00 | 49.00 | 11.00 | 0.000 | 5226.12 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00581723 | 21.00 | 0.00581723 | 37.2046 | 2055.68 | 0.00 | 5530.43 | 5530.43 | 0.41409063 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 25.90 | 16.61 | 0.00800000 | 46415.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8930.934 | 8930.934 | 0.440994 | 0.00019732 | 168.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.2800 | 0.300864 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8478.78 | 8930.93 | 1.0000 | 0.52345617 | 0.440994 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.19729795 | 60.00 | 49.00 | 11.00 | 0.000 | 8478.78 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00653739 | 21.00 | 0.00653739 | 41.7621 | 4566.88 | 0.00 | 8973.59 | 8973.59 | 0.52345617 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.61 | 17.88 | 0.00800000 | 50202.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4826.660 | 4826.660 | 0.414676 | 0.00010664 | 85.598 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.1512 | 0.162600 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 4578.36 | 4826.66 | 1.0000 | 0.49221643 | 0.414676 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.10662828 | 60.00 | 49.00 | 11.00 | 0.000 | 4578.36 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00608016 | 21.00 | 0.00608016 | 38.8659 | 725.73 | 0.00 | 4845.54 | 4845.54 | 0.49221643 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 22.45 | 15.38 | 0.00800000 | 42904.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 142169.393 | 142169.393 | 4.297177 | 0.00314106 | 2966.690 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 4.4545 | 4.789375 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 134891.51 | 142169.39 | 1.0000 | 5.10070915 | 4.297177 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 3.14073860 | 60.00 | 49.00 | 11.00 | 0.000 | 134891.51 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00755281 | 21.00 | 0.00755281 | 48.1685 | 99561.48 | 0.00 | 142818.47 | 142818.47 | 5.10070915 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61059.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 102080.390 | 102080.390 | 3.561140 | 0.00225534 | 2049.865 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 3.1991 | 3.438864 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 96875.57 | 102080.39 | 1.0000 | 4.22704058 | 3.561140 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 2.25511140 | 60.00 | 49.00 | 11.00 | 0.000 | 96875.57 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00759185 | 21.00 | 0.00759185 | 48.4142 | 66767.60 | 0.00 | 102554.41 | 102554.41 | 4.22704058 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 36.59 | 20.12 | 0.00800000 | 57321.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 143450.040 | 143450.040 | 4.433308 | 0.00316935 | 2973.760 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 4.4948 | 4.832517 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 136109.39 | 143450.04 | 1.0000 | 5.26229530 | 4.433308 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 3.16903004 | 60.00 | 49.00 | 11.00 | 0.000 | 136109.39 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00755179 | 21.00 | 0.00755179 | 48.1621 | 99492.44 | 0.00 | 144104.59 | 144104.59 | 5.26229530 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 39.66 | 21.05 | 0.00800000 | 60444.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 95790.669 | 95790.669 | 3.677726 | 0.00211638 | 1883.253 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 3.0023 | 3.226977 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 90914.51 | 95790.67 | 1.0000 | 4.36542724 | 3.677726 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 2.11616190 | 60.00 | 49.00 | 11.00 | 0.000 | 90914.51 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00744481 | 21.00 | 0.00744481 | 47.4886 | 59333.05 | 0.00 | 96236.35 | 96236.35 | 4.36542724 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 34.42 | 19.45 | 0.00800000 | 55104.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19590.405 | 19590.405 | 0.592562 | 0.00043283 | 408.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.6138 | 0.659958 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18587.55 | 19590.40 | 1.0000 | 0.70336558 | 0.592562 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.43278191 | 60.00 | 49.00 | 11.00 | 0.000 | 18587.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777008 | 21.00 | 0.00777008 | 49.5354 | 13712.24 | 0.00 | 19679.84 | 19679.84 | 0.70336558 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12953.131 | 12953.131 | 0.391824 | 0.00028618 | 270.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.4059 | 0.436363 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12290.05 | 12953.13 | 1.0000 | 0.46509118 | 0.391824 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.28615441 | 60.00 | 49.00 | 11.00 | 0.000 | 12290.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777397 | 21.00 | 0.00777397 | 49.5599 | 9066.24 | 0.00 | 13012.27 | 13012.27 | 0.46509118 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61037.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19545.432 | 19545.432 | 0.591198 | 0.00043183 | 407.772 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.6124 | 0.658443 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18544.88 | 19545.43 | 1.0000 | 0.70174698 | 0.591198 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.43178839 | 60.00 | 49.00 | 11.00 | 0.000 | 18544.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776920 | 21.00 | 0.00776920 | 49.5298 | 13680.81 | 0.00 | 19634.66 | 19634.66 | 0.70174698 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12377.135 | 12377.135 | 0.389635 | 0.00027346 | 255.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 0.3878 | 0.416959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11743.99 | 12377.14 | 1.0000 | 0.46249327 | 0.389635 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.27342979 | 60.00 | 49.00 | 11.00 | 0.000 | 11743.99 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774224 | 21.00 | 0.00774224 | 49.3604 | 8512.23 | 0.00 | 12433.61 | 12433.61 | 0.46249327 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 39.16 | 20.90 | 0.00800000 | 59943.7 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 104587.076 | -999.000 | 5.866373 | 0.00444938 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4414 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.866373 | 6.96333036 | 4197.9300 | 999.8980 | 92.40896854 | 12.27 | 6.67 | 5.60 | 2172387.74 | 4.8144 | 4.814383 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 104587.08 | 95348.24 | 1.0000 | 6.96333036 | 5.866373 | 24.92 | 16.91 | 0.00893052 | 47784.1 | 11.27 | 11.27 | 0.00839822 | 32765.7 | 4.44892209 | 6.67 | 10.65 | 5.60 | 10847.222 | 93739.85 | 28.05 | 0.00879438 | 17.86 | 1.20008137 | 20.4570 | 24.00 | 0.00897035 | 24.00 | 0.00893449 | 47.3803 | 71934.47 | 0.00 | 118558.20 | 99995.10 | 6.96333036 | 24.92 | 17.06 | 0.00893052 | 47784.1 | 10.86 | 10.63 | 0.00787312 | 30758.0 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 285898.400 | 285898.400 | 5.866373 | 0.00631658 | 5283.291 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.866373 | 6.96333036 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 7.5056 | 9.631290 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 227281.39 | 285898.40 | 1.0000 | 6.96333036 | 5.866373 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 6.31593145 | 60.00 | 49.00 | 11.00 | 0.000 | 227281.39 | -4.20 | 0.00269032 | -4.20 | 1.20008137 | 20.4570 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 239769.86 | 239769.86 | 6.96333036 | 12.80 | 2.72 | 0.00055036 | 14251.5 | 47.03 | 17.54 | 0.00055036 | 48684.7 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 180852.306 | -999.000 | 9.605274 | 0.00769388 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2655 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.605274 | 11.40137172 | 4197.9300 | 999.8980 | 92.40896854 | 12.27 | 6.67 | 5.60 | 2172387.74 | 8.3250 | 8.325047 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 180852.31 | 168113.79 | 1.0000 | 11.40137172 | 9.605274 | 25.63 | 17.07 | 0.00883589 | 48270.8 | 11.27 | 11.97 | 0.00839822 | 34322.2 | 7.69309031 | 6.67 | 10.65 | 5.60 | 21819.275 | 159033.03 | 29.40 | 0.00879438 | 18.30 | 2.70194000 | 28.1298 | 24.00 | 0.00885381 | 24.00 | 0.00879465 | 46.6485 | 121546.89 | 0.00 | 203815.66 | 173965.63 | 11.40137172 | 25.63 | 17.23 | 0.00883589 | 48270.8 | 10.69 | 10.48 | 0.00779729 | 30394.4 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 56100.111 | 56100.111 | 2.881582 | 0.00123946 | 809.511 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.605274 | 11.40137172 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 1.4240 | 1.889890 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43122.05 | 56100.11 | 1.0000 | 3.42041152 | 2.881582 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.23933696 | 60.00 | 49.00 | 11.00 | 0.000 | 43122.05 | -4.20 | 0.00269032 | -4.20 | 2.70194000 | 93.7658 | 6.67 | 0.00183449 | 21.00 | 0.00737180 | 47.0253 | 9856.84 | 0.00 | 45597.55 | 45597.55 | 3.42041152 | 12.80 | 5.49 | 0.00263696 | 19519.6 | 26.00 | 11.59 | 0.00263696 | 32850.6 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1710154.181 | -999.000 | 88.912816 | 0.07275391 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3072 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 88.912816 | 105.53869260 | 4197.9300 | 999.8980 | 92.40896854 | 12.27 | 6.67 | 5.60 | 2172387.74 | 78.7223 | 78.722327 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1710154.18 | 1586093.66 | 1.0000 | 105.53869260 | 88.912816 | 25.90 | 17.18 | 0.00885833 | 48602.3 | 11.27 | 11.97 | 0.00839822 | 34322.2 | 72.74649057 | 6.67 | 10.65 | 5.60 | 203052.670 | 1507101.51 | 29.40 | 0.00879438 | 18.30 | 28.33542000 | 31.8688 | 24.00 | 0.00889296 | 24.00 | 0.00881183 | 46.7384 | 1094244.76 | 0.00 | 1922854.13 | 1639621.71 | 105.53869260 | 25.90 | 17.34 | 0.00885833 | 48602.3 | 10.68 | 10.47 | 0.00779371 | 30382.9 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 540862.455 | 540862.455 | 26.673845 | 0.01194969 | 7761.760 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 88.912816 | 105.53869260 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 13.6211 | 18.220469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 412469.43 | 540862.46 | 1.0000 | 31.66160778 | 26.673845 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 11.94847605 | 60.00 | 49.00 | 11.00 | 0.000 | 412469.43 | -4.20 | 0.00269032 | -4.20 | 28.33542000 | 106.2292 | 20.77 | 0.00774028 | 21.00 | 0.00774028 | 49.3475 | 493545.88 | 0.00 | 436141.17 | 436141.17 | 31.66160778 | 12.80 | 5.55 | 0.00269032 | 19654.3 | 26.44 | 11.83 | 0.00269032 | 33429.4 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 176794.173 | -999.000 | 9.347796 | 0.00752123 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2453 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.347796 | 11.09574822 | 4197.9300 | 999.8980 | 92.40896854 | 12.27 | 6.67 | 5.60 | 2172387.74 | 8.1382 | 8.138242 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 176794.17 | 164696.19 | 1.0000 | 11.09574822 | 9.347796 | 25.71 | 17.10 | 0.00882503 | 48331.7 | 11.27 | 11.97 | 0.00839822 | 34322.2 | 7.52046557 | 6.67 | 10.65 | 5.60 | 21347.823 | 155446.35 | 29.40 | 0.00879438 | 18.30 | 2.96819000 | 31.7528 | 24.00 | 0.00883930 | 24.00 | 0.00880361 | 46.6954 | 126770.36 | 0.00 | 199146.02 | 170320.44 | 11.09574822 | 25.71 | 17.25 | 0.00882503 | 48331.7 | 10.68 | 10.48 | 0.00779445 | 30383.8 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 56863.255 | 56863.255 | 2.804339 | 0.00125632 | 816.028 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.347796 | 11.09574822 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 1.4320 | 1.915598 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43364.73 | 56863.26 | 1.0000 | 3.32872447 | 2.804339 | -4.04 | -4.05 | 0.00272328 | 2730.6 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.25619598 | 60.00 | 49.00 | 11.00 | 0.000 | 43364.73 | -4.20 | 0.00269032 | -4.20 | 2.96819000 | 105.8428 | 21.00 | 0.00788697 | 21.00 | 0.00788773 | 50.2746 | 68697.58 | 0.00 | 45853.45 | 45853.45 | 3.32872447 | 12.80 | 5.55 | 0.00269032 | 19654.3 | 26.44 | 11.83 | 0.00269032 | 33429.4 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 424720.911 | 304452.074 | 21.572460 | 0.01040139 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6497 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 457212.45 | 456902.85 | 0.9289 | -999.0 | -999.0 | 28.46 | 17.76 | 0.00850462 | 50315.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 457212.45 | 29.40 | 0.00879438 | 18.30 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 370557.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9549.204 | 6947.564 | 0.499253 | 0.00023386 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6582 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 10329.04 | 10314.67 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850922 | 49781.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10329.04 | 25.86 | 0.00879438 | 17.12 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 8588.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91235.736 | 66379.849 | 4.770133 | 0.00223436 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6590 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 98687.06 | 98543.31 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850965 | 49781.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98687.06 | 25.86 | 0.00879438 | 17.12 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 82061.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9288.340 | 6757.829 | 0.485622 | 0.00022747 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6587 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 10046.91 | 10032.53 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850948 | 49781.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10046.91 | 25.86 | 0.00879438 | 17.12 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 8354.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 424720.911 | 424720.911 | 21.572460 | 0.01040139 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 424720.91 | 424720.91 | 1.0000 | 25.60631159 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 424720.91 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5685 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9549.204 | 9549.204 | 0.499253 | 0.00023386 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9549.20 | 9549.20 | 1.0000 | 0.59260832 | 0.499253 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9549.20 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.1310 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91235.736 | 91235.736 | 4.770133 | 0.00223436 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 91235.74 | 91235.74 | 1.0000 | 5.66210450 | 4.770133 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91235.74 | -4.20 | 0.00269032 | -4.20 | 0.15631366 | 3.2769 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9288.340 | 9288.340 | 0.485622 | 0.00022747 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9288.34 | 9288.34 | 1.0000 | 0.57642943 | 0.485622 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9288.34 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.2188 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17838.917 | 17838.917 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.572460 | 25.60631159 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17838.92 | 17838.92 | 1.0000 | 25.60631159 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17838.92 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5685 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.572460 | 25.60631159 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1154108.54 | 1.0000 | 25.60631159 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5685 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1030923.987 | 1030923.987 | 21.572460 | 0.02277701 | 19179.394 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.572460 | 25.60631159 | 4197.9300 | 999.8980 | 65.57721476 | 71.00 | 82.00 | 11.00 | 3028174.13 | 27.3324 | 34.729566 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 827672.56 | 1030923.99 | 1.0000 | 25.60631159 | 21.572460 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 22.77468227 | 60.00 | 49.00 | 11.00 | 0.000 | 827672.56 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5685 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60631159 | 16.60 | 4.09 | 0.00004220 | 16787.2 | 16.60 | 4.09 | 0.00004220 | 16787.2 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.499253 | 0.59260832 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 1.0000 | 0.59260832 | 0.499253 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.08 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.1310 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8240.841 | 8240.841 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.770133 | 5.66210450 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8240.84 | 8240.84 | 1.0000 | 5.66210450 | 4.770133 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8240.84 | -4.20 | 0.00269032 | -4.20 | 0.15631366 | 3.2769 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.485622 | 0.57642943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 1.0000 | 0.57642943 | 0.485622 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.08 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.2188 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.87 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.70 | 9.61 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 28.34 | 88.91 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.97 | 9.35 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2814.67 | 128.17 | 4.83 |
CORE_BOTTOM | 2858.67 | 235.83 | 12.50 |
CORE_MID | 1609.50 | 1667.50 | 12.00 |
CORE_TOP | 1459.67 | 3269.50 | 264.33 |
PERIMETER_BOT_ZN_3 | 1593.17 | 2378.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 1188.00 | 3862.50 | 24.83 |
PERIMETER_BOT_ZN_1 | 1724.50 | 3098.17 | 33.17 |
PERIMETER_BOT_ZN_4 | 2947.83 | 1729.17 | 63.50 |
PERIMETER_MID_ZN_3 | 1178.00 | 3900.33 | 298.17 |
PERIMETER_MID_ZN_2 | 1028.67 | 3955.50 | 362.67 |
PERIMETER_MID_ZN_1 | 1440.67 | 3861.67 | 188.83 |
PERIMETER_MID_ZN_4 | 1177.50 | 4399.50 | 239.17 |
PERIMETER_TOP_ZN_3 | 1861.00 | 4467.17 | 1096.67 |
PERIMETER_TOP_ZN_2 | 1940.83 | 4598.67 | 1060.17 |
PERIMETER_TOP_ZN_1 | 1843.17 | 4282.67 | 807.67 |
PERIMETER_TOP_ZN_4 | 1663.17 | 4689.00 | 855.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4462.17 | 5275.67 | 1261.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 147.83 | 0.00 | 12.00 |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.33 | 0.00 | 0.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 5.50 | 0.00 | 5.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 5.67 | 0.00 | 5.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 33.33 | 0.00 | 14.33 |
PERIMETER_MID_ZN_3 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.17 | 4.83 | 0.00 | 4.83 |
PERIMETER_MID_ZN_1 | 0.17 | 9.33 | 0.00 | 9.33 |
PERIMETER_MID_ZN_4 | 0.17 | 10.17 | 0.00 | 4.17 |
PERIMETER_TOP_ZN_3 | 25.00 | 0.00 | 5.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 15.83 | 2.83 | 1.67 | 2.83 |
PERIMETER_TOP_ZN_1 | 10.33 | 1.50 | 0.17 | 1.50 |
PERIMETER_TOP_ZN_4 | 8.17 | 9.83 | 0.00 | 4.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 13.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 11.33 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 8.50 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 58.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 27.00 | 276.33 | 5.83 | 55.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.569 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.099 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.885 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.821 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.008 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.648 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.524 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.139 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.806 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.628 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.525 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.786 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.912 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.791 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.656 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.984 | 0.122 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
Electricity:Building | 19507.65 | 254949.54 | 01-JAN-06:10 | 1167329.12 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 682.08 | 14702.05 | 01-JAN-06:10 | 35858.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 257.68 | 1244.51 | 01-JAN-06:10 | 22401.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 552.69 | 7160.52 | 01-JAN-06:10 | 38246.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5526.92 | 71604.96 | 01-JAN-06:10 | 382463.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2314.15 | 11176.56 | 01-JAN-06:10 | 201178.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 552.69 | 7160.50 | 01-JAN-06:10 | 38246.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 693.98 | 8991.05 | 01-JAN-06:10 | 48023.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 290.56 | 1403.33 | 01-JAN-06:10 | 25259.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 447.23 | 5794.18 | 01-JAN-06:10 | 30947.91 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 693.99 | 8991.20 | 01-JAN-06:10 | 48023.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 290.57 | 1403.36 | 01-JAN-06:10 | 25260.46 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 447.22 | 5794.15 | 01-JAN-06:10 | 30947.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7567.51 | 95259.03 | 01-JAN-06:10 | 385948.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 72.65 | 350.90 | 01-JAN-06:10 | 6316.16 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1572.37 | 19648.16 | 01-JAN-06:10 | 80862.03 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 33.56 | 162.10 | 01-JAN-06:10 | 2917.81 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4670.79 | 67343.24 | 20-JAN-23:00 | 323755.69 | 10-AUG-16:00 |
ExteriorEquipment:Electricity | 2044.08 | 15778.61 | 01-JAN-00:10 | 129663.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.73 | 1613.62 | 01-JAN-00:10 | 5498.40 | 06-APR-07:20 |
ElectricityPurchased:Facility | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
ElectricityNet:Plant | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 28746.98 | 375032.89 | 16-JAN-11:20 | 1974765.33 | 29-AUG-15:10 |
Fans:Electricity | 2274.07 | 42212.79 | 01-JAN-17:30 | 150107.36 | 01-MAR-15:30 |
General:Fans:Electricity | 2274.07 | 42212.79 | 01-JAN-17:30 | 150107.36 | 01-MAR-15:30 |
ExteriorLights:Electricity | 882.64 | 0.00 | 01-JAN-08:10 | 56280.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 882.64 | 0.00 | 01-JAN-08:10 | 56280.71 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.27 | 1942.80 | 01-JAN-00:10 | 1942.80 | 01-JAN-00:10 |
Cooling:Electricity | 2759.64 | 23179.18 | 20-JAN-23:00 | 431104.97 | 29-AUG-14:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 15.24 | 0.00 | 01-JAN-00:10 | 34737.15 | 19-FEB-09:30 |
Electricity:Plant | 1729.57 | 5506.12 | 21-JAN-00:40 | 402046.80 | 29-AUG-14:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 465.90 | 0.00 | 01-JAN-00:10 | 263317.79 | 29-AUG-14:30 |
HeatRejection:Electricity | 899.25 | 2165.71 | 21-JAN-00:40 | 82904.98 | 27-APR-13:20 |
General:HeatRejection:Electricity | 45.07 | 0.00 | 01-JAN-00:10 | 33656.71 | 27-APR-13:20 |
Pumps:Electricity | 364.42 | 3340.41 | 19-JAN-01:10 | 56509.30 | 04-MAY-15:00 |
General:Pumps:Electricity | 364.42 | 3340.41 | 19-JAN-01:10 | 56509.30 | 04-MAY-15:00 |
WIRED_LTG_ELECTRICITY | 120.67 | 0.00 | 01-JAN-00:10 | 10490.43 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2870.18 | 8146.58 | 04-JAN-23:10 | 1312737.27 | 26-DEC-07:10 |
Gas:Plant | 2870.18 | 8146.58 | 04-JAN-23:10 | 1312737.27 | 26-DEC-07:10 |
WaterSystems:Gas | 606.83 | 8146.58 | 04-JAN-23:10 | 78871.62 | 13-FEB-12:40 |
Water Heater:WaterSystems:Gas | 606.83 | 8146.58 | 04-JAN-23:10 | 78871.62 | 13-FEB-12:40 |
Heating:Gas | 2263.35 | 0.00 | 01-JAN-00:10 | 1304590.69 | 26-DEC-07:10 |
Boiler:Heating:Gas | 2263.35 | 0.00 | 01-JAN-00:10 | 1304590.69 | 26-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 14538.98 | 90734.99 | 17-MAY-23:50 | 2380233.48 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 14538.98 | 90734.99 | 17-MAY-23:50 | 2380233.48 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 14538.98 | 90734.99 | 17-MAY-23:50 | 2380233.48 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4338.91 | 0.00 | 01-JAN-00:10 | 0.00 | 29-AUG-15:30 |
Water:Plant | 4333.24 | 0.00 | 01-JAN-00:10 | 0.00 | 29-AUG-15:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 4338.91 | 0.00 | 01-JAN-00:10 | 0.00 | 29-AUG-15:30 |
MainsWater:Plant | 4333.24 | 0.00 | 01-JAN-00:10 | 0.00 | 29-AUG-15:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 5.67 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-09:30 |
Humidifier:Water | 5.67 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-09:30 |
MainsWater:HVAC | 5.67 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-09:30 |
Humidifier:MainsWater | 5.67 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-09:30 |
HeatRejection:Water | 2053.07 | 0.00 | 01-JAN-00:10 | 0.00 | 29-AUG-15:30 |
HeatRejection:MainsWater | 2053.07 | 0.00 | 01-JAN-00:10 | 0.00 | 29-AUG-15:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 2151.09 | 0.00 | 01-JAN-00:10 | 884612.78 | 26-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 425.18 | 0.00 | 01-JAN-00:10 | 50360.07 | 13-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 425.18 | 0.00 | 01-JAN-00:10 | 50360.07 | 13-FEB-12:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 44302.49 | 152337.22 | 19-JAN-01:30 | 9357400.89 | 29-AUG-14:40 |
EnergyTransfer:Building | 19031.61 | 65163.14 | 26-JAN-03:00 | 1594919.57 | 10-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 761.35 | 0.00 | 01-JAN-00:10 | 84834.59 | 10-MAR-04:50 |
Heating:EnergyTransfer | 75.05 | 0.00 | 03-JAN-22:10 | 462121.72 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 7.99 | 0.00 | 01-JAN-00:10 | 63737.46 | 18-JAN-04:50 |
Cooling:EnergyTransfer | 18956.57 | 64977.42 | 26-JAN-03:00 | 1594919.57 | 10-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 753.36 | 0.00 | 01-JAN-00:10 | 79425.05 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 670.62 | 0.00 | 01-JAN-00:10 | 53878.91 | 28-AUG-10:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 670.62 | 0.00 | 01-JAN-00:10 | 53878.91 | 28-AUG-10:00 |
EnergyTransfer:Zone:CORE_MID | 4758.45 | 0.00 | 01-JAN-00:10 | 446425.97 | 28-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.06 | 0.00 | 01-JAN-00:10 | 77627.77 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4758.39 | 0.00 | 01-JAN-00:10 | 446425.97 | 28-AUG-13:10 |
EnergyTransfer:Zone:CORE_TOP | 397.87 | 0.00 | 01-JAN-00:10 | 64848.00 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.14 | 0.00 | 01-JAN-00:10 | 64848.00 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 394.73 | 0.00 | 01-JAN-00:10 | 53350.97 | 10-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 74.25 | 0.00 | 01-JAN-00:10 | 9450.25 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 74.25 | 0.00 | 01-JAN-00:10 | 9450.25 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.29 | 0.00 | 01-JAN-00:10 | 12956.21 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 94.13 | 20-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.29 | 0.00 | 01-JAN-00:10 | 12956.21 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.76 | 0.00 | 01-JAN-00:10 | 19952.86 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1690.37 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.76 | 0.00 | 01-JAN-00:10 | 19952.86 | 04-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.32 | 0.00 | 01-JAN-00:10 | 16934.87 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.32 | 0.00 | 01-JAN-00:10 | 16934.87 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 493.07 | 0.00 | 01-JAN-00:10 | 82019.51 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.57 | 0.00 | 01-JAN-00:10 | 76415.54 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 489.50 | 0.00 | 01-JAN-00:10 | 82019.51 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 574.80 | 0.00 | 01-JAN-00:10 | 130978.87 | 10-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.24 | 0.00 | 01-JAN-00:10 | 56876.04 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 571.56 | 0.00 | 01-JAN-00:10 | 130978.87 | 10-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 903.26 | 0.00 | 01-JAN-00:10 | 206907.85 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.75 | 0.00 | 01-JAN-00:10 | 82609.28 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 900.51 | 0.00 | 01-JAN-00:10 | 206907.85 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 626.42 | 0.00 | 01-JAN-00:10 | 143912.24 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.44 | 0.00 | 01-JAN-00:10 | 42453.01 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 624.99 | 0.00 | 01-JAN-00:10 | 143912.24 | 10-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.86 | 0.00 | 01-JAN-00:10 | 11279.86 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.34 | 0.00 | 01-JAN-00:10 | 11279.86 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.52 | 0.00 | 01-JAN-00:10 | 9597.53 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.01 | 0.00 | 01-JAN-00:10 | 13057.58 | 10-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.25 | 0.00 | 01-JAN-00:10 | 10548.73 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.76 | 0.00 | 01-JAN-00:10 | 13057.58 | 10-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.06 | 0.00 | 01-JAN-00:10 | 21443.69 | 04-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.87 | 0.00 | 01-JAN-00:10 | 15867.87 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.19 | 0.00 | 01-JAN-00:10 | 21443.69 | 04-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.84 | 0.00 | 01-JAN-00:10 | 15128.31 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.39 | 0.00 | 01-JAN-00:10 | 9318.08 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.45 | 0.00 | 01-JAN-00:10 | 15128.31 | 10-AUG-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.00 | 0.00 | 01-JAN-00:10 | 7939.20 | 05-SEP-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.85 | 0.00 | 01-JAN-00:10 | 3101.14 | 17-APR-03:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 73.15 | 0.00 | 01-JAN-00:10 | 7939.20 | 05-SEP-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 462.49 | 0.00 | 01-JAN-00:10 | 55725.88 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.67 | 0.00 | 01-JAN-00:10 | 39487.86 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 451.82 | 0.00 | 01-JAN-00:10 | 55725.88 | 10-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 71.44 | 0.00 | 01-JAN-00:10 | 18869.46 | 17-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.76 | 0.00 | 01-JAN-00:10 | 18869.46 | 17-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.68 | 0.00 | 01-JAN-00:10 | 18619.31 | 10-AUG-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.57 | 839.94 | 21-JAN-18:20 | 8117.66 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.57 | 839.94 | 21-JAN-18:20 | 8117.66 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1210.29 | 15.76 | 16-JAN-18:00 | 77050.13 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.72 | 0.00 | 02-JAN-09:10 | 5380.94 | 01-JAN-22:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1209.57 | 0.00 | 01-JAN-00:10 | 77050.13 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.60 | 0.62 | 04-JAN-02:00 | 7845.90 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 02-JAN-13:30 | 595.57 | 08-JAN-17:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.92 | 0.00 | 01-JAN-00:10 | 7845.90 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.99 | 57147.11 | 11-JAN-04:50 | 374230.23 | 04-APR-21:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.34 | 0.00 | 01-JAN-00:10 | 14411.34 | 04-JAN-23:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.65 | 57147.11 | 11-JAN-04:50 | 374230.23 | 04-APR-21:40 |
EnergyTransfer:Plant | 11173.57 | 0.00 | 01-JAN-00:10 | 5561152.25 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 425.18 | 0.00 | 01-JAN-00:10 | 50360.07 | 13-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 425.18 | 0.00 | 01-JAN-00:10 | 50360.07 | 13-FEB-12:50 |
EnergyTransfer:HVAC | 14097.31 | 74197.17 | 17-MAY-23:50 | 2212799.10 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 1725.90 | 0.00 | 01-JAN-00:10 | 867897.96 | 26-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 1725.90 | 0.00 | 01-JAN-00:10 | 867897.96 | 26-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1725.90 | 0.00 | 01-JAN-00:10 | 867897.96 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 12371.40 | 74197.17 | 17-MAY-23:50 | 2212799.10 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 3063.38 | 0.00 | 01-JAN-00:10 | 1755507.75 | 29-AUG-14:30 |
Boilers:EnergyTransfer | 1704.38 | 0.00 | 01-JAN-00:10 | 1050997.27 | 26-DEC-07:10 |
Chillers:EnergyTransfer | 2757.37 | 0.00 | 01-JAN-00:10 | 1758699.46 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 3223.27 | 0.00 | 01-JAN-00:10 | 2022017.25 | 29-AUG-14:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 7.989 | -753.357 | 0.000 | 0.000 | 92.674 | 257.680 | 424.397 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -29.383 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -670.618 | 0.000 | 0.000 | 83.370 | 231.415 | 321.278 | 0.000 | 0.000 | 0.000 | 34.554 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.061 | -4758.370 | 0.000 | 0.000 | 837.449 | 2314.151 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1606.062 |
CORE_TOP | 0.000 | 0.000 | 3.136 | -394.730 | 0.000 | 0.000 | 85.828 | 231.415 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -246.926 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -74.250 | 0.000 | 0.000 | 10.573 | 29.056 | 40.341 | 14.593 | 0.000 | 0.017 | 37.281 | 0.000 | -50.574 | 0.000 | -7.037 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -72.287 | 0.000 | 0.000 | 7.092 | 18.725 | 25.998 | 32.325 | 0.000 | 0.015 | 22.898 | 0.000 | -30.375 | 0.000 | -4.391 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.003 | -108.754 | 0.000 | 0.000 | 10.828 | 29.057 | 40.342 | 66.053 | 0.000 | 0.018 | 14.912 | 0.000 | -45.679 | 0.000 | -6.779 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -103.316 | 0.000 | 0.000 | 6.864 | 18.725 | 25.997 | 34.455 | 0.000 | 0.009 | 57.473 | 0.000 | -35.251 | 0.000 | -4.956 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.570 | -489.500 | 0.000 | 0.000 | 109.893 | 290.565 | 403.414 | 152.070 | 0.000 | 0.427 | 127.795 | 0.000 | -456.218 | 0.000 | -142.015 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.240 | -571.564 | 0.000 | 0.000 | 54.369 | 187.251 | 259.975 | 326.091 | 0.000 | 0.336 | 114.391 | 0.000 | -281.970 | 0.000 | -92.120 | 0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.754 | -900.504 | 0.000 | 0.000 | 111.238 | 290.571 | 403.420 | 662.640 | 0.000 | 0.393 | 12.640 | 0.000 | -438.642 | 0.000 | -144.510 | -0.015 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.436 | -624.983 | 0.000 | 0.000 | 74.107 | 187.251 | 259.973 | 356.188 | 0.000 | 0.255 | 141.891 | 0.000 | -300.209 | 0.000 | -95.910 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 6.335 | -44.520 | 0.000 | 0.000 | 11.402 | 29.056 | 40.341 | 15.691 | 0.000 | 0.049 | 0.000 | 0.000 | -41.416 | 0.000 | -16.113 | -0.826 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.249 | -49.763 | 0.000 | 0.000 | 7.473 | 18.725 | 25.998 | 32.924 | 0.000 | 0.035 | 0.000 | 0.000 | -26.182 | 0.000 | -10.633 | -2.826 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.871 | -80.187 | 0.000 | 0.000 | 11.428 | 29.057 | 40.342 | 67.063 | 0.000 | 0.045 | 0.000 | 0.000 | -40.558 | 0.000 | -16.547 | -15.515 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 2.389 | -56.455 | 0.000 | 0.000 | 7.572 | 18.725 | 25.997 | 35.876 | 0.000 | 0.030 | 5.046 | 0.000 | -28.047 | 0.000 | -11.134 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.569 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.668 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.719 | -1209.571 | 0.000 | 0.000 | 0.000 | 33.564 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -363.518 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.672 | -109.924 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.986 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.339 | -7170.645 | 0.000 | 0.000 | 0.000 | 72.655 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -397.207 |
GROUNDFLOOR_PLENUM | 0.851 | -73.153 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.025 | 86.463 | 0.000 | 0.000 | 0.000 | -14.186 | 0.000 |
MIDFLOOR_PLENUM | 10.674 | -451.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.514 | 682.524 | 0.000 | 0.000 | 0.000 | -241.894 | 0.000 |
TOPFLOOR_PLENUM | 21.756 | -49.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.022 | 52.943 | 0.000 | 0.000 | 0.000 | -25.039 | -0.002 |
Total Facility | 33.281 | -574.653 | 41.764 | -18381.867 | 0.000 | 0.000 | 1522.160 | 4294.357 | 15213.288 | 1795.969 | 0.000 | 2.192 | 1390.814 | 0.000 | -1775.121 | 0.000 | -833.264 | -2728.934 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-NOV-15:30 | 0.00 | 0.00 | 0.00 | -127212.15 | 0.00 | 0.00 | 402.14 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 112107.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 12-JUN-03:03 | 0.00 | 0.00 | 0.00 | -86256.55 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.15 | 0.00 | 0.00 | 0.00 | 76990.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-03:02 | 0.00 | 0.00 | 0.00 | -804565.54 | 0.00 | 0.00 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 711903.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-AUG-04:02 | 0.00 | 0.00 | 0.00 | -75130.43 | 0.00 | 0.00 | 0.00 | 2418.12 | 8057.12 | 0.00 | 0.00 | 0.00 | 64655.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 | -9952.72 | 0.00 | 0.00 | 115.16 | 280.67 | 1011.70 | 0.00 | 0.00 | 0.00 | 10272.02 | 0.00 | -1700.81 | 0.00 | -26.02 | 0.00 |
PERIMETER_BOT_ZN_2 | 13-AUG-09:32 | 0.00 | 0.00 | 0.00 | -20162.32 | 0.00 | 0.00 | 24.32 | 90.44 | 488.98 | 11747.49 | 0.00 | 0.00 | 7912.67 | 0.00 | -0.00 | 0.00 | -101.57 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:22 | 0.00 | 0.00 | 0.00 | -26628.41 | 0.00 | 0.00 | 36.67 | 140.34 | 758.78 | 18843.25 | 0.00 | 0.00 | 6984.68 | 0.00 | -0.00 | 0.00 | -135.31 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-15:41 | 0.00 | 0.00 | 0.00 | -26437.11 | 0.00 | 0.00 | 20.12 | 90.44 | 488.98 | 16320.19 | 0.00 | 0.00 | 9543.74 | 0.00 | -0.00 | 0.00 | -26.36 | 0.00 |
PERIMETER_MID_ZN_3 | 10-AUG-05:01 | 0.00 | 0.00 | 0.00 | -86678.08 | 0.00 | 0.00 | 1132.87 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 76470.56 | 0.00 | -3094.78 | 0.00 | -754.20 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-09:42 | 0.00 | 0.00 | 0.00 | -210875.55 | 0.00 | 0.00 | 230.50 | 904.36 | 4889.82 | 105771.00 | 0.00 | 0.00 | 101314.46 | 0.00 | -0.00 | 0.00 | -2234.60 | 0.00 |
PERIMETER_MID_ZN_1 | 08-OCT-13:42 | 0.00 | 0.00 | 0.00 | -256089.16 | 0.00 | 0.00 | 372.70 | 1403.36 | 7587.84 | 153824.50 | 0.00 | 0.00 | 97635.90 | 0.00 | -0.00 | 0.00 | -4735.15 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-18:31 | 0.00 | 0.00 | 0.00 | -236646.64 | 0.00 | 0.00 | 0.00 | 978.32 | 4889.79 | 120259.67 | 0.00 | 0.00 | 112825.71 | 0.00 | -0.00 | 0.00 | -2306.85 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -9597.46 | 0.00 | 0.00 | 1114.39 | 2525.99 | 2276.32 | 4591.06 | 0.00 | 98.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1009.14 |
PERIMETER_TOP_ZN_2 | 30-JUL-09:12 | 0.00 | 0.00 | 0.00 | -20950.07 | 0.00 | 0.00 | 23.04 | 90.44 | 488.98 | 13051.01 | 0.00 | 0.00 | 7537.19 | 0.00 | -0.00 | 0.00 | -240.59 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:22 | 0.00 | 0.00 | 0.00 | -29053.16 | 0.00 | 0.00 | 35.37 | 140.34 | 758.78 | 18711.75 | 0.00 | 0.00 | 9810.59 | 0.00 | -0.00 | 0.00 | -403.67 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-18:31 | 0.00 | 0.00 | 0.00 | -25265.19 | 0.00 | 0.00 | 0.00 | 97.83 | 488.98 | 11962.50 | 0.00 | 0.00 | 13020.24 | 0.00 | -0.00 | 0.00 | -304.36 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-19:10 | 0.00 | 0.00 | 0.00 | -8120.88 | 0.00 | 0.00 | 0.00 | 17.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 308.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-19:10 | 0.00 | 0.00 | 0.00 | -77066.82 | 0.00 | 0.00 | 0.00 | 175.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1052.76 |
DATACENTER_TOP_ZN_6 | 06-AUG-19:10 | 0.00 | 0.00 | 0.00 | -7848.41 | 0.00 | 0.00 | 0.00 | 17.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 36.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 25-NOV-21:12 | 0.00 | 0.00 | 0.00 | -408724.00 | 0.00 | 0.00 | 0.00 | 379.60 | 284724.39 | 0.00 | 0.00 | 0.00 | 123620.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-SEP-05:13 | 0.00 | -9966.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10045.82 | 0.00 | -0.00 | 0.00 | -78.95 | 0.00 |
MIDFLOOR_PLENUM | 26-AUG-05:13 | 0.00 | -67363.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68593.32 | 0.00 | -0.00 | 0.00 | -1229.99 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:40 | 0.00 | -18618.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 18551.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-05:01 | 0.00 | 10670.03 | 0.00 | -1823526.48 | 0.00 | 0.00 | 15768.56 | 41480.56 | 623236.89 | 0.00 | 0.00 | 0.00 | 1196306.50 | 0.00 | -57859.37 | 0.00 | -6076.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-JUL-17:30 | 0.00 | 0.00 | 147132.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1346.29 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -161935.84 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-06:03 | 0.00 | 0.00 | 251719.30 | -0.00 | 0.00 | 0.00 | 11451.99 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -366095.61 |
CORE_TOP | 02-JAN-04:11 | 0.00 | 0.00 | 75558.54 | -0.00 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84824.72 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 20-DEC-06:01 | 0.00 | 0.00 | 941.33 | -0.00 | 0.00 | 0.00 | 91.10 | 180.87 | 651.98 | 0.00 | 0.00 | 0.00 | 494.23 | 0.00 | -2219.31 | 0.00 | -140.19 | 0.00 |
PERIMETER_BOT_ZN_1 | 17-JAN-06:01 | 0.00 | 0.00 | 6863.10 | -0.00 | 0.00 | 0.00 | 142.53 | 280.67 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3163.42 | 0.00 | -94.43 | -5040.16 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 100003.76 | -0.00 | 0.00 | 0.00 | 0.00 | 3036.19 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19356.61 | 0.00 | -11374.34 | -82425.98 |
PERIMETER_MID_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 110686.27 | -0.00 | 0.00 | 0.00 | 0.00 | 1956.64 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13086.35 | 0.00 | -7656.14 | -98420.18 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 158942.52 | -0.00 | 0.00 | 0.00 | 0.00 | 3036.26 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19853.83 | 0.00 | -11554.74 | -140687.33 |
PERIMETER_MID_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 97278.26 | -0.00 | 0.00 | 0.00 | 0.00 | 1956.64 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13995.17 | 0.00 | -8031.09 | -83728.36 |
PERIMETER_TOP_ZN_3 | 20-FEB-20:11 | 0.00 | 0.00 | 12911.35 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1775.07 | 0.00 | -1293.02 | -10753.84 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:11 | 0.00 | 0.00 | 15497.82 | -0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -986.12 | 0.00 | -902.84 | -14358.67 |
PERIMETER_TOP_ZN_1 | 02-JAN-04:11 | 0.00 | 0.00 | 22130.86 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1486.23 | 0.00 | -1350.42 | -20457.73 |
PERIMETER_TOP_ZN_4 | 02-JAN-04:11 | 0.00 | 0.00 | 15395.81 | -0.00 | 0.00 | 0.00 | 0.00 | 97.83 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1037.58 | 0.00 | -922.84 | -14185.19 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-04:33 | 0.00 | 0.00 | 5384.61 | 0.00 | 0.00 | 0.00 | 0.00 | 175.36 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25046.02 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:20 | 0.00 | 0.00 | 595.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2560.39 |
DATACENTER_BASEMENT_ZN_6 | 04-JAN-23:31 | 0.00 | 0.00 | 67473.07 | 0.00 | 0.00 | 0.00 | 0.00 | 350.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -162732.10 |
GROUNDFLOOR_PLENUM | 04-DEC-04:01 | 13136.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -869.39 | -12267.55 |
MIDFLOOR_PLENUM | 29-DEC-06:01 | 84192.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4020.59 | -80172.24 |
TOPFLOOR_PLENUM | 17-JAN-06:13 | 21421.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -300.03 | -21121.64 |
Total Facility | 02-JAN-06:03 | -218334.52 | 261309.24 | 780930.33 | -261309.24 | 0.00 | 0.00 | 20209.56 | 41480.56 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -88835.86 | 0.00 | -23085.98 | -780726.79 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.8664 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.8664 | 0.2046 | 1.0000 | 1.2001 | 0.2046 | ||
VAV_BOT WITH REHEAT | 10.8967 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.6053 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 103.1203 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 88.9128 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.4546 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.3478 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5725 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5725 | 0.0157 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4993 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4993 | 0.0313 | 1.0000 | 0.0156 | 0.0313 | ||
AIRLOOP DATACENTER MID | 4.7701 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.7701 | 0.0328 | 1.0000 | 0.1563 | 0.0328 | ||
AIRLOOP DATACENTER TOP | 0.4856 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4856 | 0.0322 | 1.0000 | 0.0156 | 0.0322 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.8664 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.8664 | 1.0000 | 1.0000 | 1.2001 | 0.2046 | ||
VAV_BOT WITH REHEAT | 5.4484 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.2690 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 51.5602 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 30.9361 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.2273 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.1364 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5725 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5725 | 1.0000 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4993 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4993 | 1.0000 | 1.0000 | 0.0156 | 0.0313 | ||
AIRLOOP DATACENTER MID | 4.7701 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.7701 | 1.0000 | 1.0000 | 0.1563 | 0.0328 | ||
AIRLOOP DATACENTER TOP | 0.4856 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4856 | 1.0000 | 1.0000 | 0.0156 | 0.0322 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.8664 | 5.8664 | 5.8664 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0385 | 6.0385 | 1.8115 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.6783 | 56.6783 | 17.0035 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5282 | 5.5282 | 1.6584 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8431 | 0.8431 | 0.2529 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1629 | 1.1629 | 0.3489 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4700 | 1.4700 | 0.4410 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3823 | 1.3823 | 0.4147 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5347 | 7.5347 | 2.2604 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.8705 | 11.8705 | 3.5611 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.7777 | 14.7777 | 4.4333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.2591 | 12.2591 | 3.6777 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8718 | 0.8718 | 0.2615 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1724 | 1.1724 | 0.3517 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5835 | 1.5835 | 0.4750 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2988 | 1.2988 | 0.3896 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4993 | 0.4993 | 0.4993 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.7701 | 4.7701 | 4.7701 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4856 | 0.4856 | 0.4856 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5725 | 21.5725 | 21.5725 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.8664 | 5.8664 | 5.8664 | 5.8664 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 10.8967 | 9.6053 | 10.8967 | 3.2690 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 103.1203 | 88.9128 | 103.1203 | 30.9361 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.4546 | 9.3478 | 10.4546 | 3.1364 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5725 | 21.5725 | 21.5725 | 21.5725 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4993 | 0.4993 | 0.4993 | 0.4993 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7701 | 4.7701 | 4.7701 | 4.7701 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4856 | 0.4856 | 0.4856 | 0.4856 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.8664 | 5.8664 | 5.8664 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0192 | 3.0192 | 1.8115 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.3392 | 28.3392 | 17.0035 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7641 | 2.7641 | 1.6584 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4216 | 0.4216 | 0.2529 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5814 | 0.5814 | 0.3489 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7350 | 0.7350 | 0.4410 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6911 | 0.6911 | 0.4147 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7674 | 3.7674 | 2.2604 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9352 | 5.9352 | 3.5611 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3888 | 7.3888 | 4.4333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1295 | 6.1295 | 3.6777 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4359 | 0.4359 | 0.2615 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5862 | 0.5862 | 0.3517 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7917 | 0.7917 | 0.4750 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6494 | 0.6494 | 0.3896 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4993 | 0.4993 | 0.4993 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.7701 | 4.7701 | 4.7701 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4856 | 0.4856 | 0.4856 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5725 | 21.5725 | 21.5725 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.8664 | 5.8664 | 5.8664 | 5.8664 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 5.4484 | 3.2690 | 3.2690 | 3.2690 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 51.5602 | 30.9361 | 30.9361 | 30.9361 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.2273 | 3.1364 | 3.1364 | 3.1364 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5725 | 21.5725 | 21.5725 | 21.5725 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4993 | 0.4993 | 0.4993 | 0.4993 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7701 | 4.7701 | 4.7701 | 4.7701 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4856 | 0.4856 | 0.4856 | 0.4856 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 20:03:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 5.83 |
Number of hours cooling loads not met | 55.83 |
Number of hours not met | 61.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 2263.35 | 1304590.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 465.90 | 263317.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2293.74 | 167787.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 4294.36 | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 882.64 | 56280.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.73 | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.27 | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2274.07 | 150107.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 364.42 | 56509.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 45.07 | 33656.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 854.18 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 15.24 | 34737.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 606.83 | 78871.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 28746.98 |
Natural Gas | 0.00 | 2870.18 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 31617.16 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 92.71 |
Space Heating | 0.00 |
Space Cooling | 59.58 |
Fans (All) | 49.09 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 620.61 |
Subtotal | 620.61 |
Natural Gas [MJ/m2] | |
Space Heating | 48.86 |
Service Water Heating | 13.10 |
Miscellaneous (All) | 61.96 |
Subtotal | 61.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.58 |
Space Heating | 7.16 |
Space Cooling | 8.73 |
Fans (All) | 7.19 |
Service Water Heating | 1.92 |
Receptacle Equipment | 48.12 |
Miscellaneous | 13.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2728. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.592622E+12 |
February | 0.000 | 0.383454E+12 |
March | 0.000 | 0.225003E+12 |
April | 0.000 | 0.123911E+12 |
May | 0.000 | 0.529439E+11 |
June | 0.000 | 0.115638E+11 |
July | 0.000 | 0.187388E+10 |
August | 0.000 | 0.200229E+10 |
September | 0.000 | 0.172921E+11 |
October | 0.000 | 0.973709E+11 |
November | 0.000 | 0.278631E+12 |
December | 0.000 | 0.476678E+12 |
Annual Sum or Average | 0.226335E+13 | |
Minimum of Months | 0.000 | 0.187388E+10 |
Maximum of Months | 0.000 | 0.592622E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.563662E+11 | 123214.30 | 01-JAN-23:42 | 6.10 | 5.29 | 0.566601E+10 | 7499.16 | 05-JAN-10:20 | 2.60 | 2.43 |
February | 0.525405E+11 | 122399.70 | 27-FEB-02:62 | 8.48 | 6.48 | 0.514005E+10 | 7499.20 | 08-FEB-10:20 | 2.77 | 1.67 |
March | 0.645354E+11 | 122634.76 | 07-MAR-04:50 | 6.70 | 5.14 | 0.613533E+10 | 7499.14 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.610566E+11 | 125680.11 | 23-APR-19:30 | 11.70 | 7.77 | 0.545299E+10 | 7499.04 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.629945E+11 | 123679.52 | 29-MAY-13:02 | 14.90 | 11.85 | 0.590326E+10 | 7499.14 | 05-MAY-09:20 | 16.33 | 13.63 |
June | 0.652395E+11 | 124185.02 | 04-JUN-16:30 | 16.40 | 11.21 | 0.588447E+10 | 7499.17 | 09-JUN-13:20 | 21.87 | 13.50 |
July | 0.658581E+11 | 126756.02 | 04-JUL-17:40 | 15.20 | 10.61 | 0.547595E+10 | 7499.12 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.714367E+11 | 121040.55 | 20-AUG-23:08 | 16.27 | 13.26 | 0.613949E+10 | 7499.55 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.636107E+11 | 120393.79 | 04-SEP-12:11 | 17.20 | 12.61 | 0.545398E+10 | 7499.12 | 14-SEP-09:20 | 17.57 | 15.53 |
October | 0.652603E+11 | 122635.92 | 09-OCT-05:32 | 10.93 | 10.05 | 0.567236E+10 | 7499.06 | 16-OCT-09:09 | 9.78 | 7.90 |
November | 0.633046E+11 | 127214.30 | 12-NOV-15:30 | 5.55 | 4.43 | 0.561707E+10 | 7499.03 | 15-NOV-10:30 | 7.50 | 5.82 |
December | 0.611538E+11 | 122866.98 | 25-DEC-18:42 | -0.6 | -1.0 | 0.547262E+10 | 7499.28 | 13-DEC-14:20 | 6.90 | 5.04 |
Annual Sum or Average | 0.753357E+12 | 0.680136E+11 | ||||||||
Minimum of Months | 0.525405E+11 | 120393.79 | -0.6 | -1.0 | 0.514005E+10 | 7499.03 | 2.60 | 1.67 | ||
Maximum of Months | 0.714367E+11 | 127214.30 | 17.20 | 13.26 | 0.613949E+10 | 7499.55 | 26.10 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427838E+11 | 72296.89 | 02-JAN-04:03 | 6.60 | 5.58 | 0.507531E+10 | 6734.79 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.435888E+11 | 77845.64 | 27-FEB-04:02 | 12.70 | 7.47 | 0.460672E+10 | 6734.81 | 08-FEB-10:20 | 2.77 | 1.67 |
March | 0.578127E+11 | 76262.55 | 10-MAR-04:02 | 11.60 | 11.26 | 0.550381E+10 | 6734.80 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.594909E+11 | 77372.40 | 25-APR-03:02 | 7.12 | 5.13 | 0.488571E+10 | 6734.74 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.561010E+11 | 83902.85 | 01-MAY-03:02 | 11.78 | 9.72 | 0.528910E+10 | 6734.81 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.601831E+11 | 86249.71 | 12-JUN-03:03 | 15.00 | 13.35 | 0.527277E+10 | 6734.86 | 05-JUN-09:00 | 14.40 | 11.88 |
July | 0.650903E+11 | 86155.96 | 11-JUL-03:02 | 15.00 | 13.39 | 0.489839E+10 | 6734.70 | 12-JUL-13:09 | 16.05 | 14.01 |
August | 0.734603E+11 | 83319.64 | 02-AUG-03:02 | 13.35 | 13.04 | 0.549713E+10 | 6735.25 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.537573E+11 | 83039.61 | 18-SEP-03:02 | 12.88 | 11.82 | 0.488502E+10 | 6734.77 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.542007E+11 | 82751.79 | 09-OCT-10:09 | 16.38 | 12.62 | 0.508244E+10 | 6734.76 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.523159E+11 | 79825.48 | 13-NOV-04:02 | 1.60 | 1.20 | 0.503508E+10 | 6734.74 | 13-NOV-10:50 | 2.62 | 2.57 |
December | 0.518346E+11 | 78627.04 | 04-DEC-04:02 | 5.73 | 2.00 | 0.490689E+10 | 6734.90 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.670619E+12 | 0.609384E+11 | ||||||||
Minimum of Months | 0.427838E+11 | 72296.89 | 1.60 | 1.20 | 0.460672E+10 | 6734.70 | 2.62 | 1.67 | ||
Maximum of Months | 0.734603E+11 | 86249.71 | 16.38 | 13.39 | 0.550381E+10 | 6735.25 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288274E+11 | 60797.04 | 13-JAN-06:02 | 3.22 | 2.30 | 0.496483E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.296800E+11 | 64613.75 | 28-FEB-06:01 | 10.60 | 9.73 | 0.455771E+10 | 6734.80 | 08-FEB-10:20 | 2.77 | 1.67 |
March | 0.396950E+11 | 65665.14 | 10-MAR-06:01 | 11.20 | 11.10 | 0.547833E+10 | 6734.79 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.389929E+11 | 65782.96 | 28-APR-04:03 | 11.60 | 10.10 | 0.487002E+10 | 6734.70 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.453322E+11 | 68970.42 | 01-MAY-03:01 | 11.78 | 9.72 | 0.527826E+10 | 6734.79 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.471290E+11 | 74825.17 | 12-JUN-03:02 | 15.00 | 13.35 | 0.526379E+10 | 6734.80 | 05-JUN-09:00 | 14.40 | 11.88 |
July | 0.470288E+11 | 76323.81 | 31-JUL-05:02 | 17.30 | 14.52 | 0.488923E+10 | 6734.72 | 12-JUL-13:09 | 16.05 | 14.01 |
August | 0.514282E+11 | 80463.81 | 28-AUG-03:02 | 16.12 | 14.27 | 0.548960E+10 | 6735.10 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.438426E+11 | 73520.84 | 01-SEP-04:02 | 16.02 | 13.74 | 0.487418E+10 | 6734.75 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.393111E+11 | 69656.84 | 10-OCT-04:02 | 12.20 | 10.97 | 0.506017E+10 | 6734.76 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.337347E+11 | 67319.27 | 07-NOV-06:01 | 12.12 | 9.84 | 0.499510E+10 | 6734.73 | 13-NOV-10:50 | 2.62 | 2.57 |
December | 0.308370E+11 | 61215.99 | 07-DEC-06:02 | 4.27 | 2.77 | 0.484236E+10 | 6734.83 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.475839E+12 | 0.605636E+11 | ||||||||
Minimum of Months | 0.288274E+11 | 60797.04 | 3.22 | 2.30 | 0.455771E+10 | 6734.70 | 2.62 | 1.67 | ||
Maximum of Months | 0.514282E+11 | 80463.81 | 17.30 | 14.52 | 0.548960E+10 | 6735.10 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195461E+11 | 25219.84 | 11-JAN-17:00 | 12.20 | 9.26 | 0.449025E+10 | 6734.57 | 27-JAN-14:09 | 9.72 | 8.08 |
February | 0.205788E+11 | 34496.34 | 28-FEB-17:00 | 14.40 | 10.81 | 0.422552E+10 | 6734.66 | 03-FEB-10:50 | 9.72 | 7.14 |
March | 0.289200E+11 | 41025.74 | 10-MAR-06:01 | 11.20 | 11.10 | 0.528442E+10 | 6734.69 | 02-MAR-14:50 | 13.30 | 8.48 |
April | 0.323121E+11 | 62549.28 | 28-APR-05:01 | 11.10 | 9.92 | 0.477908E+10 | 6734.68 | 14-APR-09:09 | 11.78 | 11.15 |
May | 0.408646E+11 | 66177.61 | 05-MAY-05:02 | 12.98 | 10.75 | 0.523603E+10 | 6734.76 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.453693E+11 | 73602.32 | 12-JUN-03:02 | 15.00 | 13.35 | 0.524690E+10 | 6734.76 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.471181E+11 | 71842.14 | 10-JUL-03:01 | 13.80 | 12.22 | 0.487784E+10 | 6734.69 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.505835E+11 | 75129.71 | 25-AUG-04:02 | 18.07 | 15.52 | 0.547354E+10 | 6735.08 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.380056E+11 | 69262.85 | 01-SEP-05:02 | 15.50 | 13.56 | 0.483054E+10 | 6734.70 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.291447E+11 | 57267.17 | 26-OCT-05:01 | 12.20 | 10.86 | 0.492368E+10 | 6734.74 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.225174E+11 | 33475.17 | 02-NOV-15:40 | 13.30 | 10.98 | 0.470840E+10 | 6734.66 | 03-NOV-09:09 | 11.20 | 10.58 |
December | 0.197743E+11 | 24641.27 | 29-DEC-17:00 | 9.40 | 7.98 | 0.440419E+10 | 6734.62 | 13-DEC-14:00 | 6.10 | 4.76 |
Annual Sum or Average | 0.394734E+12 | 0.584804E+11 | ||||||||
Minimum of Months | 0.195461E+11 | 24641.27 | 9.40 | 7.98 | 0.422552E+10 | 6734.57 | 6.10 | 4.76 | ||
Maximum of Months | 0.505835E+11 | 75129.71 | 18.07 | 15.52 | 0.547354E+10 | 6735.08 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338382E+10 | 3909.58 | 11-JAN-14:10 | 14.40 | 10.48 | 0.607529E+09 | 845.62 | 27-JAN-14:09 | 9.72 | 8.08 |
February | 0.370309E+10 | 6042.96 | 27-FEB-15:30 | 19.70 | 12.29 | 0.561326E+09 | 845.62 | 23-FEB-10:09 | 11.70 | 10.84 |
March | 0.551246E+10 | 6236.22 | 20-MAR-14:00 | 12.20 | 7.75 | 0.681543E+09 | 845.63 | 31-MAR-13:09 | 8.98 | 7.52 |
April | 0.657913E+10 | 8421.32 | 03-APR-05:03 | 10.60 | 9.99 | 0.609077E+09 | 845.62 | 27-APR-13:30 | 26.10 | 16.53 |
May | 0.706721E+10 | 8772.60 | 01-MAY-05:01 | 12.20 | 10.39 | 0.660358E+09 | 845.63 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.809652E+10 | 9606.34 | 12-JUN-05:03 | 14.40 | 13.42 | 0.660757E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.922066E+10 | 9846.79 | 24-JUL-05:03 | 15.87 | 13.14 | 0.614289E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.102324E+11 | 9952.76 | 28-AUG-05:02 | 14.83 | 13.93 | 0.689387E+09 | 845.71 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.649676E+10 | 9103.50 | 18-SEP-05:01 | 12.20 | 11.62 | 0.609500E+09 | 845.63 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.543876E+10 | 9157.51 | 10-OCT-05:03 | 12.20 | 11.22 | 0.630380E+09 | 845.62 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.450879E+10 | 7740.22 | 06-NOV-06:03 | 11.28 | 8.35 | 0.621463E+09 | 845.62 | 24-NOV-10:09 | 5.68 | 4.12 |
December | 0.401096E+10 | 4580.20 | 04-DEC-14:10 | 8.90 | 5.69 | 0.600359E+09 | 845.64 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.742506E+11 | 0.754597E+10 | ||||||||
Minimum of Months | 0.338382E+10 | 3909.58 | 8.90 | 5.69 | 0.561326E+09 | 845.62 | 5.68 | 4.12 | ||
Maximum of Months | 0.102324E+11 | 9952.76 | 19.70 | 13.93 | 0.689387E+09 | 845.71 | 26.10 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371189E+10 | 3517.45 | 11-JAN-14:20 | 14.40 | 10.48 | 0.347156E+09 | 518.05 | 05-JAN-10:09 | 2.70 | 2.49 |
February | 0.383632E+10 | 4555.21 | 08-FEB-09:35 | 1.67 | 0.56 | 0.328585E+09 | 544.96 | 08-FEB-10:20 | 2.77 | 1.67 |
March | 0.526105E+10 | 8574.45 | 14-MAR-09:00 | 7.80 | 5.89 | 0.413022E+09 | 544.96 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.633321E+10 | 10872.40 | 26-APR-08:20 | 12.03 | 8.46 | 0.380937E+09 | 544.96 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.679903E+10 | 18426.22 | 14-MAY-08:52 | 16.70 | 11.52 | 0.414818E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.780827E+10 | 11308.92 | 19-JUN-08:30 | 14.75 | 10.97 | 0.418482E+09 | 544.96 | 07-JUN-09:00 | 13.30 | 10.26 |
July | 0.867136E+10 | 19912.40 | 23-JUL-08:32 | 18.53 | 13.72 | 0.387573E+09 | 544.96 | 18-JUL-09:09 | 17.07 | 11.94 |
August | 0.960557E+10 | 20164.79 | 13-AUG-09:32 | 22.10 | 16.35 | 0.433908E+09 | 545.04 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.661487E+10 | 18690.55 | 10-SEP-08:42 | 15.82 | 13.36 | 0.378837E+09 | 544.96 | 15-SEP-09:30 | 17.25 | 14.68 |
October | 0.534217E+10 | 9082.11 | 04-OCT-08:50 | 15.32 | 10.36 | 0.382637E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.431613E+10 | 4421.25 | 05-NOV-12:22 | 15.25 | 13.47 | 0.359947E+09 | 541.69 | 15-NOV-10:09 | 7.30 | 5.71 |
December | 0.398684E+10 | 3475.83 | 04-DEC-10:00 | 8.30 | 4.35 | 0.339074E+09 | 540.42 | 04-DEC-10:09 | 8.30 | 4.43 |
Annual Sum or Average | 0.722867E+11 | 0.458497E+10 | ||||||||
Minimum of Months | 0.371189E+10 | 3475.83 | 1.67 | 0.56 | 0.328585E+09 | 518.05 | 2.70 | 1.67 | ||
Maximum of Months | 0.960557E+10 | 20164.79 | 22.10 | 16.35 | 0.433908E+09 | 545.04 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540414E+10 | 15391.74 | 20-JAN-13:20 | 6.70 | 4.71 | 0.561380E+09 | 846.29 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.649451E+10 | 17433.36 | 27-FEB-13:40 | 18.13 | 11.36 | 0.533450E+09 | 871.02 | 07-FEB-14:09 | 7.88 | 4.77 |
March | 0.905788E+10 | 17421.10 | 14-MAR-13:40 | 15.20 | 10.16 | 0.658531E+09 | 890.02 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.965005E+10 | 16819.89 | 27-APR-12:50 | 25.92 | 16.12 | 0.595662E+09 | 845.65 | 27-APR-13:30 | 26.10 | 16.53 |
May | 0.920426E+10 | 12592.32 | 15-MAY-12:40 | 22.60 | 13.48 | 0.646875E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.978319E+10 | 11951.55 | 12-JUN-05:03 | 14.40 | 13.42 | 0.650715E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.117245E+11 | 21995.95 | 30-JUL-13:02 | 26.20 | 17.72 | 0.606296E+09 | 845.66 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.139885E+11 | 18877.97 | 29-AUG-12:30 | 28.65 | 19.73 | 0.681441E+09 | 845.73 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.107834E+11 | 26627.48 | 10-SEP-13:22 | 21.40 | 14.37 | 0.598129E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.943454E+10 | 25101.92 | 08-OCT-13:12 | 18.53 | 13.80 | 0.611813E+09 | 873.09 | 03-OCT-13:09 | 18.30 | 10.43 |
November | 0.670363E+10 | 20553.20 | 11-NOV-12:23 | 5.85 | 4.71 | 0.588168E+09 | 847.72 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.652646E+10 | 15989.68 | 05-DEC-12:10 | 10.10 | 6.08 | 0.559355E+09 | 845.66 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.108755E+12 | 0.729182E+10 | ||||||||
Minimum of Months | 0.540414E+10 | 11951.55 | 5.85 | 4.71 | 0.533450E+09 | 845.65 | 6.78 | 4.75 | ||
Maximum of Months | 0.139885E+11 | 26627.48 | 28.65 | 19.73 | 0.681441E+09 | 890.02 | 26.10 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486091E+10 | 5585.51 | 05-JAN-15:40 | 6.30 | 4.80 | 0.362890E+09 | 544.64 | 05-JAN-14:00 | 6.70 | 5.17 |
February | 0.540898E+10 | 10414.00 | 27-FEB-15:30 | 19.70 | 12.29 | 0.352826E+09 | 544.95 | 22-FEB-14:20 | 10.00 | 8.95 |
March | 0.793079E+10 | 13624.38 | 11-MAR-04:01 | 10.60 | 10.60 | 0.439362E+09 | 544.96 | 31-MAR-13:09 | 8.98 | 7.52 |
April | 0.998820E+10 | 16346.13 | 05-APR-03:01 | 8.90 | 7.75 | 0.394755E+09 | 544.96 | 27-APR-13:30 | 26.10 | 16.53 |
May | 0.873661E+10 | 25869.19 | 14-MAY-16:31 | 22.97 | 11.83 | 0.419899E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.101369E+11 | 24575.20 | 25-JUN-16:42 | 21.70 | 13.37 | 0.424469E+09 | 544.97 | 05-JUN-09:00 | 14.40 | 11.88 |
July | 0.130705E+11 | 26437.07 | 30-JUL-15:41 | 27.70 | 18.28 | 0.396380E+09 | 544.97 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.146508E+11 | 25277.95 | 06-AUG-16:31 | 23.53 | 15.25 | 0.445217E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.841883E+10 | 25106.52 | 10-SEP-16:42 | 22.20 | 14.21 | 0.384946E+09 | 544.96 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.725986E+10 | 12832.19 | 05-OCT-03:01 | 9.90 | 6.21 | 0.401814E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.639048E+10 | 15850.41 | 20-NOV-04:01 | 7.88 | 6.25 | 0.399248E+09 | 544.95 | 03-NOV-13:00 | 13.30 | 12.64 |
December | 0.646372E+10 | 15563.78 | 04-DEC-04:01 | 5.73 | 2.00 | 0.390734E+09 | 544.97 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.103317E+12 | 0.481254E+10 | ||||||||
Minimum of Months | 0.486091E+10 | 5585.51 | 5.73 | 2.00 | 0.352826E+09 | 544.64 | 6.70 | 5.11 | ||
Maximum of Months | 0.146508E+11 | 26437.07 | 27.70 | 18.28 | 0.445217E+09 | 545.03 | 26.10 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185904E+10 | 2464.96 | 11-JAN-16:00 | 14.40 | 10.48 | 0.521745E+09 | 804.42 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.217341E+10 | 3905.03 | 28-FEB-15:00 | 13.90 | 10.80 | 0.498616E+09 | 845.60 | 24-FEB-14:09 | 12.88 | 11.55 |
March | 0.321417E+10 | 4365.88 | 10-MAR-14:30 | 16.40 | 11.75 | 0.641002E+09 | 845.62 | 31-MAR-13:09 | 8.98 | 7.52 |
April | 0.381165E+10 | 6876.50 | 27-APR-15:40 | 27.20 | 17.01 | 0.587199E+09 | 845.62 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.532635E+10 | 7141.48 | 05-MAY-13:30 | 23.85 | 16.50 | 0.651175E+09 | 845.63 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.602991E+10 | 7624.37 | 21-JUN-15:40 | 24.80 | 15.83 | 0.655721E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.651117E+10 | 8201.95 | 24-JUL-15:00 | 30.60 | 18.76 | 0.610505E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.700171E+10 | 8667.79 | 10-AUG-05:01 | 17.33 | 14.37 | 0.685017E+09 | 845.68 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.497824E+10 | 6636.09 | 12-SEP-14:50 | 24.40 | 16.67 | 0.601710E+09 | 845.62 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.344610E+10 | 5015.76 | 04-OCT-15:30 | 21.40 | 11.43 | 0.602787E+09 | 845.61 | 17-OCT-13:00 | 11.70 | 10.43 |
November | 0.253621E+10 | 3165.67 | 02-NOV-14:00 | 14.40 | 11.36 | 0.560961E+09 | 845.61 | 06-NOV-14:20 | 11.50 | 10.17 |
December | 0.206241E+10 | 2218.33 | 14-DEC-12:00 | 13.30 | 8.42 | 0.513647E+09 | 793.93 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.489504E+11 | 0.713008E+10 | ||||||||
Minimum of Months | 0.185904E+10 | 2218.33 | 13.30 | 8.42 | 0.498616E+09 | 793.93 | 8.98 | 7.52 | ||
Maximum of Months | 0.700171E+10 | 8667.79 | 30.60 | 18.76 | 0.685017E+09 | 845.68 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184732E+10 | 3144.54 | 11-JAN-14:00 | 14.40 | 10.48 | 0.225576E+09 | 439.81 | 05-JAN-09:50 | 2.23 | 2.02 |
February | 0.247679E+10 | 4053.53 | 27-FEB-15:30 | 19.70 | 12.29 | 0.215232E+09 | 496.67 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.406291E+10 | 6832.82 | 14-MAR-09:00 | 7.80 | 5.89 | 0.276332E+09 | 521.21 | 14-MAR-10:20 | 10.57 | 8.08 |
April | 0.496892E+10 | 10729.43 | 27-APR-09:00 | 17.80 | 12.19 | 0.265296E+09 | 521.21 | 27-APR-14:20 | 26.47 | 16.96 |
May | 0.610001E+10 | 10803.84 | 15-MAY-08:40 | 16.47 | 11.41 | 0.291071E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.23 |
June | 0.706068E+10 | 18870.30 | 25-JUN-08:32 | 16.33 | 11.86 | 0.298974E+09 | 521.22 | 07-JUN-10:09 | 13.40 | 10.32 |
July | 0.737933E+10 | 20709.71 | 23-JUL-09:32 | 20.37 | 14.47 | 0.279496E+09 | 521.23 | 06-JUL-10:00 | 18.30 | 13.78 |
August | 0.809128E+10 | 21090.44 | 13-AUG-09:42 | 22.40 | 16.46 | 0.311974E+09 | 521.30 | 09-AUG-10:09 | 23.92 | 15.99 |
September | 0.599345E+10 | 10198.74 | 13-SEP-09:00 | 18.30 | 15.24 | 0.266610E+09 | 521.21 | 11-SEP-10:09 | 19.08 | 14.36 |
October | 0.427080E+10 | 8107.83 | 04-OCT-09:00 | 15.60 | 10.48 | 0.259210E+09 | 521.22 | 05-OCT-10:09 | 14.08 | 9.35 |
November | 0.283027E+10 | 4195.03 | 05-NOV-13:32 | 16.83 | 13.70 | 0.234412E+09 | 481.01 | 15-NOV-09:39 | 7.03 | 5.50 |
December | 0.207468E+10 | 2943.26 | 05-DEC-09:50 | 6.42 | 4.92 | 0.220621E+09 | 448.86 | 05-DEC-09:00 | 6.70 | 5.09 |
Annual Sum or Average | 0.571564E+11 | 0.314480E+10 | ||||||||
Minimum of Months | 0.184732E+10 | 2943.26 | 6.42 | 4.92 | 0.215232E+09 | 439.81 | 2.20 | 1.26 | ||
Maximum of Months | 0.809128E+10 | 21090.44 | 22.40 | 16.46 | 0.311974E+09 | 521.30 | 26.47 | 16.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395875E+10 | 15454.74 | 20-JAN-13:20 | 6.70 | 4.71 | 0.525452E+09 | 846.96 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.541746E+10 | 20323.85 | 12-FEB-13:32 | 6.50 | 1.18 | 0.505229E+09 | 896.80 | 08-FEB-14:09 | 6.88 | 3.84 |
March | 0.768981E+10 | 17849.31 | 14-MAR-14:00 | 15.60 | 10.49 | 0.627544E+09 | 912.71 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.753965E+10 | 17060.32 | 27-APR-13:10 | 26.10 | 16.35 | 0.572355E+09 | 845.65 | 27-APR-13:30 | 26.10 | 16.53 |
May | 0.818552E+10 | 12176.69 | 15-MAY-12:50 | 22.70 | 13.63 | 0.629342E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.834042E+10 | 10179.05 | 21-JUN-13:30 | 22.50 | 15.03 | 0.634009E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.937943E+10 | 18385.14 | 30-JUL-13:02 | 26.20 | 17.72 | 0.593441E+09 | 845.66 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.111825E+11 | 19092.34 | 29-AUG-12:30 | 28.65 | 19.73 | 0.668257E+09 | 845.72 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.102392E+11 | 25374.89 | 10-SEP-13:32 | 21.67 | 14.46 | 0.585598E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.839355E+10 | 25608.47 | 08-OCT-13:42 | 19.63 | 14.08 | 0.589586E+09 | 897.85 | 03-OCT-13:20 | 18.30 | 10.43 |
November | 0.517925E+10 | 15522.58 | 15-NOV-13:20 | 9.60 | 6.61 | 0.547184E+09 | 851.31 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.454550E+10 | 15408.34 | 05-DEC-12:40 | 10.40 | 6.14 | 0.518008E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.900510E+11 | 0.699600E+10 | ||||||||
Minimum of Months | 0.395875E+10 | 10179.05 | 6.50 | 1.18 | 0.505229E+09 | 845.65 | 6.78 | 3.84 | ||
Maximum of Months | 0.111825E+11 | 25608.47 | 28.65 | 19.73 | 0.668257E+09 | 912.71 | 26.10 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226688E+10 | 3415.32 | 05-JAN-15:50 | 6.20 | 4.70 | 0.311901E+09 | 487.64 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.287467E+10 | 6856.24 | 27-FEB-15:30 | 19.70 | 12.29 | 0.297534E+09 | 543.38 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.442007E+10 | 9459.81 | 14-MAR-16:00 | 17.20 | 10.93 | 0.375507E+09 | 544.94 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.520621E+10 | 12706.10 | 26-APR-16:00 | 24.40 | 14.46 | 0.351555E+09 | 544.90 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.664143E+10 | 21363.71 | 07-MAY-16:42 | 21.78 | 16.18 | 0.392998E+09 | 544.95 | 22-MAY-13:09 | 16.10 | 10.32 |
June | 0.712346E+10 | 19144.95 | 18-JUN-18:31 | 16.30 | 12.46 | 0.397916E+09 | 544.93 | 28-JUN-13:00 | 25.00 | 15.63 |
July | 0.842264E+10 | 23665.25 | 23-JUL-18:31 | 24.97 | 15.77 | 0.377044E+09 | 544.94 | 05-JUL-13:39 | 17.80 | 11.94 |
August | 0.865164E+10 | 21628.69 | 06-AUG-17:11 | 23.53 | 15.14 | 0.419650E+09 | 544.94 | 15-AUG-13:50 | 25.25 | 16.27 |
September | 0.646224E+10 | 13329.93 | 10-SEP-16:53 | 22.20 | 14.15 | 0.359168E+09 | 544.72 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.459280E+10 | 10468.43 | 04-OCT-16:00 | 21.10 | 11.38 | 0.350858E+09 | 538.09 | 02-OCT-13:00 | 16.70 | 11.41 |
November | 0.323578E+10 | 4586.06 | 04-NOV-15:40 | 20.37 | 15.92 | 0.324771E+09 | 529.63 | 10-NOV-14:00 | 10.00 | 6.83 |
December | 0.260094E+10 | 3613.18 | 05-DEC-15:40 | 7.40 | 5.39 | 0.307181E+09 | 508.58 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.624988E+11 | 0.426608E+10 | ||||||||
Minimum of Months | 0.226688E+10 | 3415.32 | 6.20 | 4.70 | 0.297534E+09 | 487.64 | 6.10 | 4.61 | ||
Maximum of Months | 0.865164E+10 | 23665.25 | 24.97 | 16.18 | 0.419650E+09 | 544.95 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105835E+10 | 2554.74 | 11-JAN-16:00 | 14.40 | 10.48 | 0.477646E+09 | 730.19 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.149560E+10 | 3215.25 | 27-FEB-16:10 | 19.32 | 12.37 | 0.452742E+09 | 838.92 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.273241E+10 | 3779.58 | 10-MAR-14:50 | 16.20 | 11.58 | 0.582705E+09 | 845.58 | 10-MAR-14:09 | 16.60 | 11.92 |
April | 0.346838E+10 | 7688.61 | 27-APR-15:20 | 27.20 | 17.14 | 0.553674E+09 | 845.63 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.514163E+10 | 7817.13 | 31-MAY-15:00 | 22.20 | 15.71 | 0.630919E+09 | 845.62 | 26-MAY-13:09 | 12.48 | 11.47 |
June | 0.608819E+10 | 8506.54 | 21-JUN-15:40 | 24.80 | 15.83 | 0.645097E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.678186E+10 | 9597.53 | 24-JUL-15:00 | 30.60 | 18.76 | 0.604149E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.717831E+10 | 9133.21 | 09-AUG-15:30 | 28.70 | 18.81 | 0.676465E+09 | 845.68 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.473248E+10 | 7189.54 | 14-SEP-15:40 | 24.23 | 17.00 | 0.579953E+09 | 845.62 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.294406E+10 | 4877.01 | 04-OCT-15:30 | 21.40 | 11.43 | 0.552425E+09 | 845.60 | 06-OCT-13:09 | 16.78 | 12.01 |
November | 0.182325E+10 | 2853.67 | 02-NOV-14:00 | 14.40 | 11.36 | 0.499540E+09 | 804.49 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.107599E+10 | 2217.03 | 29-DEC-16:00 | 10.60 | 8.76 | 0.462375E+09 | 724.36 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.445205E+11 | 0.671769E+10 | ||||||||
Minimum of Months | 0.105835E+10 | 2217.03 | 10.60 | 8.76 | 0.452742E+09 | 724.36 | 10.60 | 8.76 | ||
Maximum of Months | 0.717831E+10 | 9597.53 | 30.60 | 18.81 | 0.676465E+09 | 845.68 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.963940E+09 | 2908.14 | 11-JAN-15:00 | 14.40 | 10.48 | 0.300319E+09 | 418.07 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.160060E+10 | 3841.84 | 27-FEB-15:00 | 20.00 | 12.15 | 0.281915E+09 | 470.77 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.319056E+10 | 5173.75 | 14-MAR-09:35 | 9.27 | 7.13 | 0.362233E+09 | 544.95 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.436983E+10 | 10225.81 | 27-APR-09:10 | 17.98 | 12.32 | 0.355712E+09 | 544.96 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.569618E+10 | 14053.55 | 14-MAY-08:52 | 16.70 | 11.52 | 0.393969E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.689847E+10 | 18231.69 | 25-JUN-09:02 | 16.88 | 12.17 | 0.407726E+09 | 544.97 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.734972E+10 | 20953.74 | 30-JUL-09:12 | 21.13 | 15.96 | 0.381070E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.801329E+10 | 20810.63 | 13-AUG-09:22 | 21.80 | 16.24 | 0.425683E+09 | 545.04 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.549709E+10 | 15967.59 | 10-SEP-08:42 | 15.82 | 13.36 | 0.358735E+09 | 544.95 | 15-SEP-09:30 | 17.25 | 14.68 |
October | 0.337673E+10 | 6871.65 | 04-OCT-09:10 | 15.87 | 10.56 | 0.340884E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.177104E+10 | 3388.94 | 02-NOV-14:00 | 14.40 | 11.36 | 0.305202E+09 | 468.69 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.103543E+10 | 2521.52 | 05-DEC-14:00 | 10.60 | 6.37 | 0.290435E+09 | 423.79 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.497629E+11 | 0.420388E+10 | ||||||||
Minimum of Months | 0.963940E+09 | 2521.52 | 9.27 | 6.37 | 0.281915E+09 | 418.07 | 10.00 | 7.00 | ||
Maximum of Months | 0.801329E+10 | 20953.74 | 21.80 | 16.24 | 0.425683E+09 | 545.04 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250568E+10 | 14211.30 | 20-JAN-13:30 | 6.70 | 4.71 | 0.493075E+09 | 845.63 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.395633E+10 | 16119.28 | 27-FEB-14:20 | 18.87 | 11.66 | 0.477080E+09 | 845.80 | 08-FEB-14:09 | 6.88 | 3.84 |
March | 0.635137E+10 | 18047.45 | 14-MAR-13:30 | 15.00 | 9.99 | 0.593616E+09 | 868.14 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.677365E+10 | 17721.03 | 27-APR-13:10 | 26.10 | 16.35 | 0.548854E+09 | 845.66 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.786941E+10 | 13022.72 | 15-MAY-13:10 | 22.88 | 13.74 | 0.607648E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.840584E+10 | 10972.52 | 21-JUN-13:30 | 22.50 | 15.03 | 0.617682E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.961478E+10 | 15721.01 | 31-JUL-13:10 | 27.38 | 18.34 | 0.582464E+09 | 845.66 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.113354E+11 | 22424.64 | 13-AUG-12:42 | 26.43 | 18.33 | 0.654721E+09 | 845.69 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.975447E+10 | 29052.15 | 10-SEP-13:22 | 21.40 | 14.37 | 0.564616E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.709875E+10 | 21443.69 | 04-OCT-13:30 | 20.85 | 11.29 | 0.558844E+09 | 863.19 | 03-OCT-13:20 | 18.30 | 10.43 |
November | 0.363173E+10 | 14572.41 | 15-NOV-13:10 | 9.50 | 6.55 | 0.507474E+09 | 845.64 | 15-NOV-14:30 | 9.45 | 6.67 |
December | 0.289036E+10 | 13306.47 | 05-DEC-12:30 | 10.30 | 6.12 | 0.485569E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.801878E+11 | 0.669164E+10 | ||||||||
Minimum of Months | 0.250568E+10 | 10972.52 | 6.70 | 4.71 | 0.477080E+09 | 845.63 | 6.78 | 3.84 | ||
Maximum of Months | 0.113354E+11 | 29052.15 | 27.38 | 18.34 | 0.654721E+09 | 868.14 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131193E+10 | 3387.16 | 05-JAN-15:50 | 6.20 | 4.70 | 0.302740E+09 | 465.25 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.201021E+10 | 6017.82 | 27-FEB-15:40 | 19.60 | 12.33 | 0.285415E+09 | 521.19 | 27-FEB-16:10 | 19.32 | 12.37 |
March | 0.364892E+10 | 9307.84 | 14-MAR-16:00 | 17.20 | 10.93 | 0.355186E+09 | 543.66 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.476513E+10 | 13089.09 | 26-APR-16:00 | 24.40 | 14.46 | 0.336192E+09 | 544.93 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.645617E+10 | 22662.81 | 07-MAY-16:42 | 21.78 | 16.18 | 0.379291E+09 | 544.94 | 22-MAY-13:50 | 16.10 | 10.48 |
June | 0.716921E+10 | 20820.89 | 18-JUN-17:01 | 17.12 | 12.22 | 0.387706E+09 | 544.92 | 28-JUN-13:50 | 24.90 | 15.64 |
July | 0.857733E+10 | 25268.26 | 23-JUL-18:31 | 24.97 | 15.77 | 0.369865E+09 | 544.95 | 20-JUL-13:30 | 26.40 | 16.67 |
August | 0.876686E+10 | 22686.58 | 06-AUG-17:32 | 23.67 | 15.19 | 0.410018E+09 | 544.93 | 09-AUG-13:09 | 27.58 | 17.58 |
September | 0.619675E+10 | 23114.60 | 10-SEP-16:42 | 22.20 | 14.21 | 0.344975E+09 | 544.45 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.384643E+10 | 10405.13 | 04-OCT-16:00 | 21.10 | 11.38 | 0.331382E+09 | 521.19 | 03-OCT-15:00 | 18.30 | 10.42 |
November | 0.221805E+10 | 4718.48 | 04-NOV-15:40 | 20.37 | 15.92 | 0.307447E+09 | 501.78 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.148795E+10 | 3517.74 | 05-DEC-15:40 | 7.40 | 5.39 | 0.294463E+09 | 477.87 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.564549E+11 | 0.410468E+10 | ||||||||
Minimum of Months | 0.131193E+10 | 3387.16 | 6.20 | 4.70 | 0.285415E+09 | 465.25 | 6.10 | 4.61 | ||
Maximum of Months | 0.876686E+10 | 25268.26 | 24.97 | 16.18 | 0.410018E+09 | 544.95 | 27.58 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365316E+10 | 5488.79 | 05-JAN-06:10 | -0.8 | -0.8 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.396473E+10 | 6740.60 | 28-FEB-06:02 | 10.60 | 9.73 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.590734E+10 | 6824.61 | 20-MAR-05:15 | 5.97 | 4.26 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.647601E+10 | 7381.92 | 28-APR-05:13 | 11.10 | 9.98 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.650828E+10 | 9241.78 | 08-MAY-05:13 | 9.60 | 9.49 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.728215E+10 | 9755.56 | 12-JUN-05:13 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.794858E+10 | 8714.23 | 06-JUL-05:13 | 12.07 | 9.16 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.880586E+10 | 8406.92 | 28-AUG-05:03 | 14.83 | 13.93 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.670403E+10 | 9967.05 | 05-SEP-05:13 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.599606E+10 | 8760.90 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.515856E+10 | 7987.11 | 13-NOV-06:05 | 1.70 | 1.50 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.474885E+10 | 6620.16 | 04-DEC-06:05 | 3.22 | 1.95 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.731536E+11 | 0.00 | ||||||||
Minimum of Months | 0.365316E+10 | 5488.79 | -0.8 | -0.8 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.880586E+10 | 9967.05 | 14.83 | 13.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131684E+10 | 5687.33 | 14-JAN-06:01 | 2.20 | 1.10 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.185085E+10 | 4456.74 | 10-FEB-06:10 | 2.43 | 1.36 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.320928E+10 | 4993.69 | 01-MAR-06:06 | -0.1 | -1.4 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.359157E+10 | 5334.92 | 28-APR-05:13 | 11.10 | 9.98 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.465973E+10 | 5709.51 | 05-MAY-05:13 | 13.17 | 10.88 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.522485E+10 | 6719.12 | 12-JUN-05:13 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.566173E+10 | 6435.00 | 10-JUL-05:04 | 13.22 | 11.64 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.627246E+10 | 6736.24 | 26-AUG-05:13 | 14.77 | 14.11 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.515937E+10 | 6462.37 | 05-SEP-05:13 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.380097E+10 | 5844.04 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.255266E+10 | 4566.37 | 09-NOV-06:07 | 7.12 | 5.84 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.188161E+10 | 3988.12 | 26-DEC-06:02 | -0.8 | -0.8 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.451819E+11 | 0.00 | ||||||||
Minimum of Months | 0.131684E+10 | 3988.12 | -0.8 | -1.4 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.627246E+10 | 6736.24 | 14.77 | 14.11 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18944321.80 | 918.93 | 11-JAN-17:30 | 12.50 | 9.43 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.417887E+09 | 4625.89 | 27-FEB-15:30 | 19.70 | 12.29 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.186683E+10 | 8524.62 | 14-MAR-13:50 | 15.40 | 10.32 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.420626E+10 | 15916.27 | 27-APR-14:20 | 26.47 | 16.96 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.685474E+10 | 16397.49 | 15-MAY-14:30 | 23.30 | 13.04 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.833916E+10 | 16789.99 | 28-JUN-14:40 | 25.73 | 15.57 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.101047E+11 | 18061.48 | 24-JUL-14:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.984834E+10 | 18619.31 | 10-AUG-14:40 | 29.93 | 18.97 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.563460E+10 | 14284.17 | 14-SEP-14:20 | 23.90 | 17.05 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.204288E+10 | 9966.09 | 04-OCT-13:50 | 21.02 | 11.35 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.336359E+09 | 5283.71 | 04-NOV-13:50 | 21.02 | 15.95 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 13079446.71 | 819.00 | 05-DEC-13:10 | 10.60 | 6.21 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.496838E+11 | 0.00 | ||||||||
Minimum of Months | 13079446.71 | 819.00 | 10.60 | 6.21 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.101047E+11 | 18619.31 | 29.93 | 18.97 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332488E+10 | 1901.99 | 05-JAN-16:10 | 5.73 | 4.38 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.797834E+10 | 3983.43 | 07-FEB-16:50 | 7.30 | 3.82 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.142505E+11 | 6042.65 | 14-MAR-17:10 | 16.52 | 10.82 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.188744E+11 | 8057.26 | 25-APR-18:00 | 14.40 | 8.92 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.430890E+10 | 2536.04 | 29-MAY-18:24 | 15.85 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.919808E+10 | 4308.54 | 18-JUN-18:45 | 16.20 | 12.51 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.146647E+11 | 6670.92 | 30-JUL-18:37 | 25.17 | 16.93 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.196320E+11 | 8120.88 | 06-AUG-19:10 | 21.43 | 14.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.420381E+10 | 2411.58 | 10-SEP-17:26 | 21.40 | 13.99 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.923843E+10 | 4306.29 | 03-OCT-16:50 | 17.38 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.137337E+11 | 5816.81 | 12-NOV-15:50 | 5.18 | 4.15 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.191615E+11 | 7704.70 | 05-DEC-15:50 | 6.75 | 4.97 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.138569E+12 | 0.00 | ||||||||
Minimum of Months | 0.332488E+10 | 1901.99 | 5.18 | 3.82 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.196320E+11 | 8120.88 | 25.17 | 16.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145366E+10 | 1580.44 | 05-JAN-16:20 | 5.37 | 4.14 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.624634E+10 | 3656.99 | 08-FEB-16:50 | 6.78 | 3.35 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.124983E+11 | 5661.14 | 14-MAR-17:10 | 16.52 | 10.82 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.172690E+11 | 7640.27 | 26-APR-18:20 | 21.30 | 12.83 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.349528E+10 | 2290.62 | 29-MAY-18:22 | 15.85 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.828604E+10 | 4005.07 | 22-JUN-18:50 | 23.40 | 15.89 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.136865E+11 | 6192.13 | 30-JUL-18:40 | 25.17 | 16.93 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.184668E+11 | 7706.68 | 06-AUG-19:10 | 21.43 | 14.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.344735E+10 | 2196.61 | 08-SEP-17:30 | 21.65 | 14.35 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.780677E+10 | 4035.49 | 03-OCT-16:50 | 17.38 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.117253E+11 | 5274.09 | 10-NOV-16:10 | 8.53 | 6.27 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.165757E+11 | 7099.45 | 05-DEC-16:00 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.120957E+12 | 0.00 | ||||||||
Minimum of Months | 0.145366E+10 | 1580.44 | 5.37 | 3.35 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.184668E+11 | 7706.68 | 25.17 | 16.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477896E+09 | 1425.32 | 05-JAN-16:20 | 5.37 | 4.14 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.458661E+10 | 3550.42 | 08-FEB-16:50 | 6.78 | 3.35 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.112302E+11 | 5670.11 | 14-MAR-17:10 | 16.52 | 10.82 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.164929E+11 | 7754.14 | 26-APR-18:10 | 22.05 | 13.16 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.298472E+10 | 2420.00 | 07-MAY-18:12 | 20.37 | 15.39 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.804459E+10 | 4171.29 | 18-JUN-18:35 | 16.30 | 12.46 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.135364E+11 | 6383.03 | 30-JUL-18:30 | 25.55 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.182720E+11 | 7848.41 | 06-AUG-19:10 | 21.43 | 14.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.291175E+10 | 2258.98 | 08-SEP-17:30 | 21.65 | 14.35 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.667851E+10 | 4055.42 | 04-OCT-16:50 | 20.68 | 11.35 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.101566E+11 | 5159.47 | 10-NOV-16:10 | 8.53 | 6.27 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.145516E+11 | 6926.62 | 05-DEC-16:00 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.109924E+12 | 0.00 | ||||||||
Minimum of Months | 0.477896E+09 | 1425.32 | 5.37 | 3.35 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.182720E+11 | 7848.41 | 25.55 | 17.12 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238023E+12 | 325859.79 | 17-JAN-22:53 | 2.20 | 1.07 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.435991E+12 | 408218.42 | 19-FEB-06:41 | -5.1 | -5.7 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.729284E+12 | 407287.09 | 24-MAR-04:52 | 2.80 | -0.1 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.944285E+12 | 387569.67 | 19-APR-21:12 | 7.93 | 4.18 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.240493E+12 | 322831.24 | 17-MAY-22:54 | 6.10 | 5.06 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.469689E+12 | 183294.94 | 20-JUN-16:00 | 24.40 | 15.00 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.731484E+12 | 275229.52 | 06-JUL-16:00 | 22.80 | 14.65 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.977838E+12 | 367851.39 | 10-AUG-21:02 | 22.92 | 16.73 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.234204E+12 | 105080.05 | 01-SEP-00:08 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.485850E+12 | 379742.02 | 02-OCT-04:14 | 9.40 | 8.23 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.707479E+12 | 408723.96 | 25-NOV-21:12 | 6.10 | 5.29 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.976026E+12 | 390247.07 | 13-DEC-06:03 | 2.80 | 1.40 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.717065E+13 | 0.00 | ||||||||
Minimum of Months | 0.234204E+12 | 105080.05 | -5.1 | -5.7 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.977838E+12 | 408723.96 | 24.40 | 16.73 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.756422E+09 | 127474.91 | 18-JAN-04:50 | 1.70 |
February | 0.251110E+09 | 136999.72 | 24-FEB-04:54 | 13.90 |
March | 0.467603E+09 | 138432.30 | 24-MAR-03:47 | 3.48 |
April | 0.398021E+09 | 131695.10 | 23-APR-17:48 | 15.97 |
May | 0.424171E+09 | 131774.30 | 12-MAY-03:47 | 7.88 |
June | 0.631217E+09 | 134444.27 | 18-JUN-16:18 | 17.93 |
July | 0.101096E+10 | 147151.41 | 23-JUL-17:30 | 26.40 |
August | 0.706728E+09 | 139922.59 | 06-AUG-16:30 | 23.60 |
September | 0.133308E+10 | 140415.29 | 10-SEP-14:38 | 22.60 |
October | 0.606405E+09 | 133715.07 | 08-OCT-15:50 | 19.90 |
November | 0.680051E+09 | 131234.70 | 29-NOV-04:47 | 8.40 |
December | 0.723796E+09 | 132183.91 | 01-DEC-04:47 | 3.48 |
Annual Sum or Average | 0.798957E+10 | |||
Minimum of Months | 0.251110E+09 | 127474.91 | 1.70 | |
Maximum of Months | 0.133308E+10 | 147151.41 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6059568.98 | 25176.56 | 02-JAN-06:03 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 6059568.98 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 6059568.98 | 25176.56 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161913E+10 | 75558.62 | 02-JAN-04:11 | 6.50 |
February | 0.566978E+09 | 72660.85 | 21-FEB-04:01 | 1.70 |
March | 76988322.72 | 65644.86 | 06-MAR-05:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 752273.41 | 5015.16 | 30-OCT-05:03 | 7.20 |
November | 0.198620E+09 | 65655.39 | 13-NOV-05:01 | 1.20 |
December | 0.673150E+09 | 72722.02 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.313562E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.161913E+10 | 75558.62 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 56479.70 | 941.33 | 20-DEC-06:01 | 6.02 |
Annual Sum or Average | 56479.70 | |||
Minimum of Months | 0.00 | 0.00 | 5.92 | |
Maximum of Months | 56479.70 | 941.33 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2567224.82 | 6863.00 | 17-JAN-06:01 | 1.20 |
February | 403504.02 | 6725.07 | 21-FEB-06:01 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 111997.39 | 1306.64 | 18-DEC-06:01 | 3.72 |
Annual Sum or Average | 3082726.23 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 2567224.82 | 6863.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218105E+09 | 9999.87 | 02-JAN-05:01 | 6.10 |
February | 74155701.32 | 9496.41 | 21-FEB-05:01 | 1.70 |
March | 2504806.28 | 8752.94 | 06-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 5981908.91 | 8785.64 | 30-NOV-06:01 | 5.60 |
December | 56257540.41 | 9090.11 | 26-DEC-05:03 | -0.6 |
Annual Sum or Average | 0.357005E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.218105E+09 | 9999.87 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186317E+09 | 11067.50 | 02-JAN-05:01 | 6.10 |
February | 59522110.56 | 10241.56 | 21-FEB-05:01 | 1.70 |
March | 3600697.90 | 9567.10 | 06-MAR-06:01 | 6.70 |
April | 467913.32 | 6215.18 | 11-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 163950.61 | 2732.51 | 28-OCT-05:01 | 8.22 |
November | 10648439.57 | 9838.80 | 30-NOV-06:01 | 5.60 |
December | 63278071.51 | 9959.25 | 20-DEC-06:01 | 6.02 |
Annual Sum or Average | 0.323998E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.186317E+09 | 11067.50 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174661E+09 | 15892.87 | 02-JAN-05:01 | 6.10 |
February | 40379098.92 | 14435.14 | 14-FEB-06:01 | -0.4 |
March | 2365745.96 | 13634.47 | 06-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 5335584.11 | 14277.81 | 30-NOV-06:01 | 5.60 |
December | 52679571.45 | 14425.84 | 27-DEC-06:01 | 4.90 |
Annual Sum or Average | 0.275421E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.4 | |
Maximum of Months | 0.174661E+09 | 15892.87 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 95085163.13 | 9726.81 | 02-JAN-05:01 | 6.10 |
February | 25267759.75 | 8916.23 | 14-FEB-06:01 | -0.4 |
March | 740841.39 | 5151.13 | 06-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 2029475.15 | 8732.74 | 30-NOV-06:01 | 5.60 |
December | 20498097.36 | 8781.27 | 20-DEC-06:01 | 6.02 |
Annual Sum or Average | 0.143621E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.4 | |
Maximum of Months | 95085163.13 | 9726.81 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225539E+10 | 12892.06 | 01-JAN-18:16 | 6.10 |
February | 0.126720E+10 | 12911.47 | 20-FEB-20:11 | 4.80 |
March | 0.416918E+09 | 11953.03 | 06-MAR-04:02 | 6.70 |
April | 0.105481E+09 | 10775.14 | 11-APR-04:02 | 5.10 |
May | 5072836.43 | 10326.78 | 18-MAY-05:01 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.133647E+09 | 11118.35 | 30-OCT-04:02 | 7.20 |
November | 0.639035E+09 | 11962.73 | 13-NOV-04:01 | 1.60 |
December | 0.151243E+10 | 12874.71 | 25-DEC-23:17 | -0.2 |
Annual Sum or Average | 0.633517E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.2 | |
Maximum of Months | 0.225539E+10 | 12911.47 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151263E+10 | 15497.79 | 02-JAN-04:11 | 6.50 |
February | 0.780101E+09 | 15210.74 | 21-FEB-04:01 | 1.70 |
March | 0.271205E+09 | 14125.64 | 06-MAR-04:02 | 6.70 |
April | 76498619.47 | 12706.50 | 11-APR-04:02 | 5.10 |
May | 6492572.24 | 12080.63 | 18-MAY-05:01 | 5.60 |
June | 264100.84 | 3819.58 | 14-JUN-05:01 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 79330.48 | 645.09 | 28-SEP-05:03 | 8.30 |
October | 0.102243E+09 | 12869.06 | 30-OCT-04:02 | 7.20 |
November | 0.450582E+09 | 14267.94 | 13-NOV-04:01 | 1.60 |
December | 0.104844E+10 | 15187.94 | 18-DEC-04:01 | 2.38 |
Annual Sum or Average | 0.424853E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.60 | |
Maximum of Months | 0.151263E+10 | 15497.79 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174679E+10 | 22130.82 | 02-JAN-04:11 | 6.50 |
February | 0.818311E+09 | 21742.58 | 21-FEB-04:01 | 1.70 |
March | 0.322330E+09 | 19740.04 | 06-MAR-04:02 | 6.70 |
April | 95750468.07 | 18165.96 | 11-APR-04:02 | 5.10 |
May | 8672307.40 | 17519.17 | 18-MAY-05:01 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 5383.72 | 89.73 | 27-SEP-05:03 | 7.38 |
October | 99038950.15 | 17549.05 | 31-OCT-05:01 | 8.58 |
November | 0.530651E+09 | 19679.66 | 24-NOV-05:01 | 2.70 |
December | 0.124971E+10 | 21599.34 | 18-DEC-04:01 | 2.38 |
Annual Sum or Average | 0.487126E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.174679E+10 | 22130.82 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.957499E+09 | 15395.78 | 02-JAN-04:11 | 6.50 |
February | 0.430778E+09 | 15157.46 | 21-FEB-04:01 | 1.70 |
March | 0.146090E+09 | 13352.24 | 06-MAR-05:01 | 6.70 |
April | 31634611.32 | 11777.07 | 19-APR-05:01 | 1.78 |
May | 3244791.18 | 11762.45 | 18-MAY-05:01 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 38054181.60 | 11763.27 | 31-OCT-05:01 | 8.58 |
November | 0.235576E+09 | 13340.81 | 13-NOV-05:01 | 1.20 |
December | 0.546375E+09 | 15000.90 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.238925E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.957499E+09 | 15395.78 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46040988.64 | 10513.71 | 30-JAN-05:01 | 6.10 |
February | 54187054.97 | 11539.54 | 21-FEB-04:01 | 1.70 |
March | 75115780.05 | 10993.60 | 09-MAR-04:01 | 11.70 |
April | 91454972.09 | 11974.08 | 14-APR-03:01 | 9.40 |
May | 60509760.03 | 12606.33 | 01-MAY-03:01 | 11.78 |
June | 68535743.07 | 10827.58 | 19-JUN-03:01 | 11.02 |
July | 93795603.48 | 11843.83 | 17-JUL-03:02 | 14.90 |
August | 92822995.44 | 11179.78 | 05-AUG-03:01 | 12.95 |
September | 44769342.57 | 9152.23 | 18-SEP-03:01 | 12.88 |
October | 74245873.84 | 11203.74 | 09-OCT-10:09 | 16.38 |
November | 70947232.66 | 12404.41 | 20-NOV-04:01 | 7.88 |
December | 78379287.35 | 13136.26 | 04-DEC-04:01 | 5.73 |
Annual Sum or Average | 0.850805E+09 | |||
Minimum of Months | 44769342.57 | 9152.23 | 1.70 | |
Maximum of Months | 93795603.48 | 13136.26 | 16.38 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553080E+09 | 7622.66 | 25-JAN-06:01 | 5.50 |
February | 99503158.93 | 7866.76 | 24-FEB-06:03 | 13.90 |
March | 32395418.66 | 7947.58 | 29-MAR-05:01 | 4.40 |
April | 32457285.71 | 7283.58 | 11-APR-05:01 | 5.60 |
May | 47289335.95 | 7516.78 | 01-MAY-03:01 | 11.78 |
June | 45318072.75 | 7355.45 | 12-JUN-03:02 | 15.00 |
July | 45708174.39 | 7886.24 | 17-JUL-03:02 | 14.90 |
August | 31735229.75 | 7695.67 | 28-AUG-03:01 | 16.12 |
September | 36885227.50 | 6446.22 | 05-SEP-03:02 | 11.70 |
October | 33199981.96 | 7466.06 | 23-OCT-05:01 | 10.60 |
November | 27287918.19 | 8037.05 | 21-NOV-06:01 | 11.10 |
December | 82487158.89 | 8419.02 | 29-DEC-06:01 | 9.90 |
Annual Sum or Average | 0.106735E+10 | |||
Minimum of Months | 27287918.19 | 6446.22 | 4.40 | |
Maximum of Months | 0.553080E+09 | 8419.02 | 16.12 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582694E+10 | 21421.65 | 17-JAN-06:13 | 1.30 |
February | 0.347785E+10 | 19986.89 | 21-FEB-05:12 | 1.70 |
March | 0.191910E+10 | 11369.09 | 06-MAR-06:03 | 6.70 |
April | 0.928798E+09 | 18132.94 | 13-APR-05:01 | 7.70 |
May | 0.368360E+09 | 19592.28 | 03-MAY-05:01 | 8.40 |
June | 0.153421E+09 | 19138.06 | 15-JUN-05:01 | 8.98 |
July | 98710980.66 | 17290.97 | 07-JUL-05:01 | 11.47 |
August | 0.121363E+09 | 17249.88 | 21-AUG-05:01 | 11.20 |
September | 0.314187E+09 | 18018.99 | 20-SEP-05:01 | 9.40 |
October | 0.114776E+10 | 19049.49 | 05-OCT-05:01 | 8.30 |
November | 0.261927E+10 | 13755.18 | 13-NOV-06:03 | 1.70 |
December | 0.478017E+10 | 19954.80 | 26-DEC-05:23 | -0.6 |
Annual Sum or Average | 0.217559E+11 | |||
Minimum of Months | 98710980.66 | 11369.09 | -0.6 | |
Maximum of Months | 0.582694E+10 | 21421.65 | 11.47 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71948335.22 | 538.46 | 02-JAN-04:33 | 6.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 71948335.22 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 71948335.22 | 538.46 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.661724E+09 | 595.57 | 08-JAN-17:20 | 2.57 |
February | 10678497.94 | 520.79 | 21-FEB-02:02 | 3.12 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.672402E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.57 | |
Maximum of Months | 0.661724E+09 | 595.57 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263457E+09 | 67442.29 | 04-JAN-23:31 | 3.50 |
February | 21152978.77 | 30770.32 | 03-FEB-04:11 | 7.20 |
March | 165943.11 | 2765.72 | 24-MAR-04:51 | 2.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 46212304.56 | 66939.30 | 17-MAY-22:51 | 6.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 8015224.32 | 10224.99 | 02-OCT-04:16 | 9.40 |
November | 406844.84 | 3813.76 | 25-NOV-21:11 | 6.10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.339411E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.80 | |
Maximum of Months | 0.263457E+09 | 67442.29 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.215029E+11 | 22401.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.195042E+11 | 22401.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.231659E+11 | 22401.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.207025E+11 | 22401.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.223344E+11 | 22401.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.222225E+11 | 22401.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.208144E+11 | 22401.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.231659E+11 | 22401.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.207025E+11 | 22401.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.215029E+11 | 22401.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.212480E+11 | 22401.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.208144E+11 | 22401.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.257680E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.195042E+11 | 22401.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.231659E+11 | 22401.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.606290E+10 | 6316.16 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.549934E+10 | 6316.16 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.653179E+10 | 6316.16 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.583722E+10 | 6316.16 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.629734E+10 | 6316.16 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.626579E+10 | 6316.16 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.586877E+10 | 6316.16 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.653179E+10 | 6316.16 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.583722E+10 | 6316.16 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.606290E+10 | 6316.16 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.599102E+10 | 6316.16 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.586877E+10 | 6316.16 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.549934E+10 | 6316.16 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.653179E+10 | 6316.16 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.223344E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.222225E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.212480E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.257680E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886336E+09 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784531E+09 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744026E+09 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096603.12 | 0.695595E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39927.48 | 0.529468E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401026.05 | 0.437060E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6299580.07 | 0.358161E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9320867.64 | 0.288911E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39776.40 | 0.248366E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596785E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699388E+09 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768625E+09 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 17197780.75 | 0.703725E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248366E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9320867.64 | 0.886336E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563689E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499756E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468401E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1231961.95 | 0.432586E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84113.22 | 0.336130E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398968.62 | 0.273780E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5935072.69 | 0.212633E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7688149.19 | 0.165112E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61454.48 | 0.155275E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372682E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433754E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477469E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 15399720.15 | 0.439127E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155275E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7688149.19 | 0.563689E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840366E+09 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768531E+09 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723946E+09 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1240699.19 | 0.673470E+09 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44080.36 | 0.514485E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 427387.34 | 0.420743E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6765517.68 | 0.338888E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9129068.34 | 0.271232E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39768.70 | 0.245489E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583113E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666707E+09 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731637E+09 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 17646521.61 | 0.677861E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245489E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9129068.34 | 0.840366E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592860E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543866E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526901E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 396710.56 | 0.502347E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54389.81 | 0.368186E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265470.11 | 0.310235E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2826613.83 | 0.263337E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5735105.03 | 0.214146E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26265.91 | 0.173687E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416853E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492756E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551284E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 9304555.26 | 0.495646E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173687E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5735105.03 | 0.592860E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171973E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154486E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150452E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2951277.31 | 0.142102E+10 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64001.70 | 0.111579E+10 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795064.77 | 0.922507E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16832596.15 | 0.766254E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22009774.96 | 0.625192E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67089.66 | 0.520387E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120650E+10 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137611E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147864E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 42719804.56 | 0.142015E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520387E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22009774.96 | 0.171973E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112476E+10 |
February | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101899E+10 |
March | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976398E+09 |
April | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2556067.58 | 0.928668E+09 |
May | 0.744847E+09 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219945.75 | 0.720398E+09 |
June | 0.742030E+09 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 887299.63 | 0.600631E+09 |
July | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12891154.85 | 0.490544E+09 |
August | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16939526.97 | 0.397424E+09 |
September | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139956.48 | 0.331130E+09 |
October | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773471E+09 |
November | 0.708685E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883844E+09 |
December | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965709E+09 |
Annual Sum or Average | 0.858171E+10 | 0.187251E+11 | 0.259975E+11 | 33633951.26 | 0.921196E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331130E+09 |
Maximum of Months | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16939526.97 | 0.112476E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175804E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163384E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154107E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2245803.09 | 0.144154E+10 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77427.56 | 0.110807E+10 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 953273.98 | 0.901856E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15496393.25 | 0.752057E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20472532.25 | 0.619957E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67070.62 | 0.535703E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125234E+10 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139027E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151628E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 39312500.75 | 0.144510E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535703E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20472532.25 | 0.175804E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115197E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104286E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100678E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220763.83 | 0.962925E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 223430.30 | 0.762888E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638940.76 | 0.623881E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8346496.53 | 0.546141E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15035817.98 | 0.436392E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59524.62 | 0.355464E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801146E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907700E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992819E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 25524974.03 | 0.959097E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355464E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15035817.98 | 0.115197E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191267E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170878E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168584E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4098347.49 | 0.162890E+10 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51952.52 | 0.131573E+10 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860760.47 | 0.110938E+10 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18631068.24 | 0.924745E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25689719.76 | 0.747795E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57856.40 | 0.606306E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133752E+10 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151267E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162254E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 49389704.87 | 0.161129E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606306E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25689719.76 | 0.191267E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126764E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114104E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111362E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3213096.37 | 0.108166E+10 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119239.74 | 0.863317E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 748188.12 | 0.733540E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12981612.80 | 0.601994E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18328884.41 | 0.486108E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95991.62 | 0.395035E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879672E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994414E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107542E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 35487013.07 | 0.106335E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395035E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18328884.41 | 0.126764E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196150E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182106E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175297E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2903953.39 | 0.166936E+10 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64582.35 | 0.131232E+10 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963948.08 | 0.108516E+10 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16931305.02 | 0.909576E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23991572.27 | 0.744198E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57838.60 | 0.631064E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142110E+10 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155597E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168224E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 44913199.70 | 0.165465E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631064E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23991572.27 | 0.196150E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130289E+10 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118592E+10 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115994E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509319.93 | 0.112692E+10 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250570.53 | 0.910444E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679193.89 | 0.753079E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9827928.82 | 0.662556E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17931915.04 | 0.525765E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58779.73 | 0.422050E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921605E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103695E+10 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112635E+10 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 30257707.94 | 0.111345E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422050E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17931915.04 | 0.130289E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.606290E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.549934E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.653179E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.583722E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.629734E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.626579E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.586877E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.583722E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.606290E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.599102E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.586877E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.549934E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179908E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158744E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149726E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1461397.42 | 0.139300E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2594.30 | 0.106175E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264337.11 | 0.872658E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9366947.21 | 0.721923E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13712365.99 | 0.594195E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.63 | 0.500462E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120362E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140554E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154862E+10 |
Annual Sum or Average | 24809175.65 | 0.141855E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500462E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13712365.99 | 0.179908E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298849E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268849E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256834E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3368008.80 | 0.239058E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4764.90 | 0.185220E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505286.50 | 0.151481E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20931746.61 | 0.125472E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26543099.05 | 0.103725E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.62 | 0.872306E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206085E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237182E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258953E+10 |
Annual Sum or Average | 51355412.46 | 0.241894E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872306E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26543099.05 | 0.298849E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290216E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265607E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262901E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2403903.19 | 0.254934E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206297E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32604.29 | 0.173612E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4622970.34 | 0.145042E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14977096.58 | 0.115809E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939832E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209823E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234981E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250690E+10 |
Annual Sum or Average | 22036574.41 | 0.250390E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939832E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14977096.58 | 0.290216E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22401.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22401.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22401.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22401.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22401.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22401.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22401.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22401.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22401.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22401.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22401.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22401.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1429.97 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1344.85 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1244.93 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.71 | 01-APR-17:02 | 1276.18 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 05-MAY-16:00 | 907.93 | 17-MAY-23:51 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 28-JUN-16:00 | 1241.27 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.78 | 23-JUL-16:10 | 639.65 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.47 | 13-AUG-15:00 | 798.38 | 04-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 14-SEP-17:00 | 604.63 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1117.10 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1363.83 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1138.93 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.63 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 168.78 | 1429.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 913.91 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 856.48 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 797.56 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.25 | 01-APR-17:02 | 816.03 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 06-MAY-15:00 | 581.08 | 17-MAY-23:51 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:20 | 792.02 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.75 | 23-JUL-16:10 | 400.52 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.03 | 13-AUG-15:00 | 489.84 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.75 | 14-SEP-17:00 | 381.85 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 686.84 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 851.06 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 722.10 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.85 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 168.75 | 913.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1362.83 | 28-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1288.55 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1236.34 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.87 | 01-APR-17:20 | 1257.22 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 05-MAY-16:00 | 882.91 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 28-JUN-16:00 | 1201.42 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.86 | 23-JUL-16:10 | 616.84 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.85 | 13-AUG-17:00 | 784.62 | 04-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 14-SEP-17:00 | 581.14 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1054.36 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1301.24 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1035.80 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.14 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 222.86 | 1362.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 971.43 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 937.32 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 901.85 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 01-APR-16:00 | 937.71 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 06-MAY-13:00 | 623.98 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 28-JUN-15:00 | 887.31 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.93 | 23-JUL-14:10 | 485.40 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 | 13-AUG-13:00 | 622.13 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 14-SEP-17:00 | 417.35 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 754.96 | 31-OCT-21:20 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 961.24 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 835.17 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.35 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 115.93 | 971.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2799.97 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2600.84 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2457.45 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.39 | 01-APR-17:02 | 2556.64 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 05-MAY-16:00 | 1883.48 | 17-MAY-23:51 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 28-JUN-15:00 | 2451.60 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.57 | 23-JUL-16:00 | 1249.63 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.34 | 13-AUG-15:10 | 1703.11 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-SEP-17:00 | 1238.30 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2266.33 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2647.21 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2128.74 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.30 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 472.57 | 2799.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1809.96 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1695.37 | 16-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1618.67 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.76 | 01-APR-17:02 | 1691.00 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 14-MAY-16:10 | 1211.24 | 18-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 28-JUN-16:20 | 1596.60 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.71 | 23-JUL-16:00 | 804.78 | 02-JUL-04:00 |
August | 1239.33 | 01-AUG-07:10 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.20 | 13-AUG-17:50 | 1110.40 | 11-AUG-04:00 |
September | 1239.33 | 01-SEP-07:10 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 14-SEP-17:00 | 773.56 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1452.19 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1725.42 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1396.56 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.56 | |||||
Maximum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 372.71 | 1809.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2760.22 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2773.36 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2531.18 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.98 | 01-APR-17:02 | 2565.96 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 05-MAY-16:00 | 1842.63 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 28-JUN-15:00 | 2408.88 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.81 | 23-JUL-16:00 | 1242.66 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.98 | 13-AUG-17:50 | 1710.23 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-SEP-17:00 | 1202.80 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2185.03 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2619.88 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2133.50 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.80 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 540.81 | 2773.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1835.77 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1718.73 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1645.86 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.59 | 01-APR-17:30 | 1690.93 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.58 | 06-MAY-13:00 | 1242.60 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 28-JUN-15:00 | 1605.84 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.96 | 23-JUL-13:40 | 867.25 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.00 | 13-AUG-13:10 | 1193.45 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 790.37 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1457.46 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1752.04 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1421.33 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.37 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 338.96 | 1835.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3170.03 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2909.89 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2819.21 | 29-MAR-04:57 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.56 | 01-APR-17:02 | 2971.11 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2193.43 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 28-JUN-15:00 | 2793.95 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.46 | 23-JUL-16:00 | 1412.82 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.42 | 13-AUG-14:50 | 2084.07 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 14-SEP-17:00 | 1402.16 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2700.22 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3021.72 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2465.33 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.16 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 553.56 | 3170.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2079.27 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1937.60 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1879.46 | 29-MAR-04:53 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.03 | 01-APR-17:02 | 1981.92 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 06-MAY-15:00 | 1429.40 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 | 28-JUN-15:00 | 1824.56 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.19 | 23-JUL-16:00 | 913.89 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.93 | 13-AUG-17:30 | 1393.54 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 14-SEP-17:00 | 882.18 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1794.31 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1994.26 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1633.16 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.18 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 442.03 | 2079.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3159.94 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2910.19 | 16-FEB-22:03 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2883.86 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.20 | 01-APR-17:02 | 2993.67 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2172.48 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 28-JUN-15:00 | 2742.17 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.80 | 23-JUL-16:00 | 1408.30 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.76 | 13-AUG-17:30 | 2125.46 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 14-SEP-17:00 | 1354.01 | 30-SEP-04:53 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2695.96 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3014.33 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2484.21 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1354.01 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 633.80 | 3159.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2124.36 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1942.82 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1879.60 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.39 | 01-APR-17:30 | 1975.06 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 06-MAY-13:00 | 1469.36 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 | 28-JUN-15:00 | 1833.34 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.86 | 23-JUL-14:10 | 994.59 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.27 | 13-AUG-12:10 | 1493.02 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 | 14-SEP-17:00 | 910.55 | 30-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1800.54 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2042.61 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1675.67 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 910.55 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 372.86 | 2124.36 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 6316.16 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6316.16 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 6316.16 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 6316.16 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 6316.16 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 6316.16 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 6316.16 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 6316.16 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 6316.16 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 6316.16 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 6316.16 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 6316.16 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 6316.16 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 6316.16 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2935.65 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2730.65 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2519.77 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.67 | 01-APR-17:02 | 2549.37 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 05-MAY-16:00 | 1890.34 | 18-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 28-JUN-15:30 | 2504.23 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.57 | 23-JUL-15:51 | 1265.33 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.63 | 13-AUG-15:00 | 1601.49 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 14-SEP-17:00 | 1195.75 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2258.86 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2762.10 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2301.31 | 17-DEC-21:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1195.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.57 | 2935.65 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5013.17 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4632.13 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4309.89 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.33 | 01-APR-17:02 | 4390.80 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 05-MAY-16:00 | 3291.76 | 18-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.41 | 28-JUN-15:00 | 4299.15 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.95 | 23-JUL-16:00 | 2149.12 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.11 | 13-AUG-14:51 | 2878.39 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 14-SEP-17:00 | 2061.58 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3883.09 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4679.90 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3722.70 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2061.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.95 | 5013.17 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4989.86 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4573.19 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4331.53 | 29-MAR-04:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.26 | 01-APR-17:02 | 4629.18 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3323.75 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 28-JUN-17:00 | 4325.33 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.67 | 30-JUL-16:00 | 2154.78 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.37 | 08-AUG-17:00 | 3161.78 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 2106.42 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4202.89 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4762.08 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3893.65 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.26 | 4989.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 123214.30 | 01-JAN-23:42 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 122399.70 | 27-FEB-02:62 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 122634.76 | 07-MAR-04:50 | 0.00 | 4038.86 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 125680.11 | 23-APR-19:30 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 123679.52 | 29-MAY-13:02 | 3590.45 | 4978.03 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 124185.02 | 04-JUN-16:30 | 3590.45 | 4978.03 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 126756.02 | 04-JUL-17:40 | 0.00 | 4038.86 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 121040.55 | 20-AUG-23:08 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 120393.79 | 04-SEP-12:11 | 6283.29 | 8711.56 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 122635.92 | 09-OCT-05:32 | 4488.06 | 6222.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 127214.30 | 12-NOV-15:30 | 4488.06 | 6222.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 122866.98 | 25-DEC-18:42 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 120393.79 | 0.00 | 4038.86 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127214.30 | 6283.29 | 8711.56 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 72296.89 | 02-JAN-04:03 | 0.00 | 4836.24 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77845.64 | 27-FEB-04:02 | 0.00 | 7254.36 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76262.55 | 10-MAR-04:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77372.40 | 25-APR-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83902.85 | 01-MAY-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86249.71 | 12-JUN-03:03 | 0.00 | 7254.36 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86155.96 | 11-JUL-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83319.64 | 02-AUG-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83039.61 | 18-SEP-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82751.79 | 09-OCT-10:09 | 8061.19 | 11176.56 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79825.48 | 13-NOV-04:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78627.04 | 04-DEC-04:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 72296.89 | 0.00 | 4836.24 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86249.71 | 8061.19 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 60797.04 | 13-JAN-06:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64613.75 | 28-FEB-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65665.14 | 10-MAR-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65782.96 | 28-APR-04:03 | 0.00 | 9672.49 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68970.42 | 01-MAY-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74825.17 | 12-JUN-03:02 | 0.00 | 7254.36 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76323.81 | 31-JUL-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80463.81 | 28-AUG-03:02 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73520.84 | 01-SEP-04:02 | 0.00 | 12090.61 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69656.84 | 10-OCT-04:02 | 0.00 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67319.27 | 07-NOV-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61215.99 | 07-DEC-06:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 60797.04 | 0.00 | 7254.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80463.81 | 16122.38 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25219.84 | 11-JAN-17:00 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34496.34 | 28-FEB-17:00 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41025.74 | 10-MAR-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62549.28 | 28-APR-05:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66177.61 | 05-MAY-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73602.32 | 12-JUN-03:02 | 0.00 | 7254.36 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71842.14 | 10-JUL-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75129.71 | 25-AUG-04:02 | 0.00 | 14508.73 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69262.85 | 01-SEP-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57267.17 | 26-OCT-05:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33475.17 | 02-NOV-15:40 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24641.27 | 29-DEC-17:00 | 15316.26 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24641.27 | 0.00 | 7254.36 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75129.71 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3909.58 | 11-JAN-14:10 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.02 |
February | 6042.96 | 27-FEB-15:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 |
March | 6236.22 | 20-MAR-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.89 |
April | 8421.32 | 03-APR-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 |
May | 8772.60 | 01-MAY-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.99 |
June | 9606.34 | 12-JUN-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.19 |
July | 9846.79 | 24-JUL-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
August | 9952.76 | 28-AUG-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
September | 9103.50 | 18-SEP-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9157.51 | 10-OCT-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 |
November | 7740.22 | 06-NOV-06:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.26 |
December | 4580.20 | 04-DEC-14:10 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3909.58 | 809.73 | 1122.66 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9952.76 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3517.45 | 11-JAN-14:20 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.02 |
February | 4555.21 | 08-FEB-09:35 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.61 |
March | 8574.45 | 14-MAR-09:00 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 |
April | 10872.40 | 26-APR-08:20 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.52 |
May | 18426.22 | 14-MAY-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.61 |
June | 11308.92 | 19-JUN-08:30 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.42 |
July | 19912.40 | 23-JUL-08:32 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.32 |
August | 20164.79 | 13-AUG-09:32 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.57 |
September | 18690.55 | 10-SEP-08:42 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.01 |
October | 9082.11 | 04-OCT-08:50 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 |
November | 4421.25 | 05-NOV-12:22 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.10 |
December | 3475.83 | 04-DEC-10:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3475.83 | 326.14 | 452.18 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20164.79 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15391.74 | 20-JAN-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 |
February | 17433.36 | 27-FEB-13:40 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 |
March | 17421.10 | 14-MAR-13:40 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 |
April | 16819.89 | 27-APR-12:50 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 0.00 |
May | 12592.32 | 15-MAY-12:40 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 |
June | 11951.55 | 12-JUN-05:03 | 809.75 | 1122.69 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 |
July | 21995.95 | 30-JUL-13:02 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
August | 18877.97 | 29-AUG-12:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 0.00 |
September | 26627.48 | 10-SEP-13:22 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.31 |
October | 25101.92 | 08-OCT-13:12 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.09 |
November | 20553.20 | 11-NOV-12:23 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.78 |
December | 15989.68 | 05-DEC-12:10 | 1058.33 | 2526.05 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11951.55 | 404.87 | 561.34 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26627.48 | 2010.83 | 2526.05 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 392.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5585.51 | 05-JAN-15:40 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
February | 10414.00 | 27-FEB-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
March | 13624.38 | 11-MAR-04:01 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.82 |
April | 16346.13 | 05-APR-03:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.19 |
May | 25869.19 | 14-MAY-16:31 | 456.59 | 633.05 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.73 |
June | 24575.20 | 25-JUN-16:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.03 |
July | 26437.07 | 30-JUL-15:41 | 456.59 | 633.05 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 |
August | 25277.95 | 06-AUG-16:31 | 456.59 | 633.05 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 |
September | 25106.52 | 10-SEP-16:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.86 |
October | 12832.19 | 05-OCT-03:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.41 |
November | 15850.41 | 20-NOV-04:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 |
December | 15563.78 | 04-DEC-04:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5585.51 | 0.00 | 542.61 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | |
Maximum of Months | 26437.07 | 1239.33 | 1627.84 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2464.96 | 11-JAN-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.76 |
February | 3905.03 | 28-FEB-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4365.88 | 10-MAR-14:30 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.18 |
April | 6876.50 | 27-APR-15:40 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 0.00 |
May | 7141.48 | 05-MAY-13:30 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 7624.37 | 21-JUN-15:40 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
July | 8201.95 | 24-JUL-15:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 0.00 |
August | 8667.79 | 10-AUG-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.42 |
September | 6636.09 | 12-SEP-14:50 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
October | 5015.76 | 04-OCT-15:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 |
November | 3165.67 | 02-NOV-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.86 |
December | 2218.33 | 14-DEC-12:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2218.33 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8667.79 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 571.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3144.54 | 11-JAN-14:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.46 |
February | 4053.53 | 27-FEB-15:30 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 |
March | 6832.82 | 14-MAR-09:00 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.07 |
April | 10729.43 | 27-APR-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.03 |
May | 10803.84 | 15-MAY-08:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 |
June | 18870.30 | 25-JUN-08:32 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.48 |
July | 20709.71 | 23-JUL-09:32 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.20 |
August | 21090.44 | 13-AUG-09:42 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.46 |
September | 10198.74 | 13-SEP-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 |
October | 8107.83 | 04-OCT-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.52 |
November | 4195.03 | 05-NOV-13:32 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.09 |
December | 2943.26 | 05-DEC-09:50 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2943.26 | 326.14 | 452.18 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | |
Maximum of Months | 21090.44 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15454.74 | 20-JAN-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 |
February | 20323.85 | 12-FEB-13:32 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2109.56 |
March | 17849.31 | 14-MAR-14:00 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.01 |
April | 17060.32 | 27-APR-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.92 | 0.00 |
May | 12176.69 | 15-MAY-12:50 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 |
June | 10179.05 | 21-JUN-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
July | 18385.14 | 30-JUL-13:02 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 |
August | 19092.34 | 29-AUG-12:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 0.00 |
September | 25374.89 | 10-SEP-13:32 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.24 |
October | 25608.47 | 08-OCT-13:42 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.51 |
November | 15522.58 | 15-NOV-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.26 |
December | 15408.34 | 05-DEC-12:40 | 1058.33 | 2526.05 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10179.05 | 404.87 | 561.34 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25608.47 | 2010.83 | 2526.05 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 2109.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3415.32 | 05-JAN-15:50 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.37 |
February | 6856.24 | 27-FEB-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 |
March | 9459.81 | 14-MAR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
April | 12706.10 | 26-APR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
May | 21363.71 | 07-MAY-16:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.89 |
June | 19144.95 | 18-JUN-18:31 | 0.00 | 978.32 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.42 |
July | 23665.25 | 23-JUL-18:31 | 0.00 | 782.66 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.68 |
August | 21628.69 | 06-AUG-17:11 | 0.00 | 684.82 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.03 |
September | 13329.93 | 10-SEP-16:53 | 260.91 | 361.74 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.50 |
October | 10468.43 | 04-OCT-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
November | 4586.06 | 04-NOV-15:40 | 130.46 | 271.31 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
December | 3613.18 | 05-DEC-15:40 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3415.32 | 0.00 | 271.31 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23665.25 | 1239.33 | 1627.84 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 592.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2554.74 | 11-JAN-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.35 |
February | 3215.25 | 27-FEB-16:10 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.43 |
March | 3779.58 | 10-MAR-14:50 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 |
April | 7688.61 | 27-APR-15:20 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 | 0.00 |
May | 7817.13 | 31-MAY-15:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.35 |
June | 8506.54 | 21-JUN-15:40 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
July | 9597.53 | 24-JUL-15:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 | 0.00 |
August | 9133.21 | 09-AUG-15:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 0.00 |
September | 7189.54 | 14-SEP-15:40 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
October | 4877.01 | 04-OCT-15:30 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
November | 2853.67 | 02-NOV-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.60 |
December | 2217.03 | 29-DEC-16:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2217.03 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9597.53 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 274.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2908.14 | 11-JAN-15:00 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.38 |
February | 3841.84 | 27-FEB-15:00 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 |
March | 5173.75 | 14-MAR-09:35 | 2591.66 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.41 |
April | 10225.81 | 27-APR-09:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.44 |
May | 14053.55 | 14-MAY-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.44 |
June | 18231.69 | 25-JUN-09:02 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.03 |
July | 20953.74 | 30-JUL-09:12 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.59 |
August | 20810.63 | 13-AUG-09:22 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.72 |
September | 15967.59 | 10-SEP-08:42 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.04 |
October | 6871.65 | 04-OCT-09:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 |
November | 3388.94 | 02-NOV-14:00 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.89 |
December | 2521.52 | 05-DEC-14:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2521.52 | 326.14 | 452.18 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | |
Maximum of Months | 20953.74 | 2591.66 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14211.30 | 20-JAN-13:30 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.12 |
February | 16119.28 | 27-FEB-14:20 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 |
March | 18047.45 | 14-MAR-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.73 |
April | 17721.03 | 27-APR-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 0.00 |
May | 13022.72 | 15-MAY-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 |
June | 10972.52 | 21-JUN-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 |
July | 15721.01 | 31-JUL-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 64.61 | 0.00 |
August | 22424.64 | 13-AUG-12:42 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 |
September | 29052.15 | 10-SEP-13:22 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.67 |
October | 21443.69 | 04-OCT-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.58 |
November | 14572.41 | 15-NOV-13:10 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.70 |
December | 13306.47 | 05-DEC-12:30 | 1058.33 | 2526.05 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10972.52 | 506.09 | 701.68 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29052.15 | 2010.83 | 2526.05 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 64.61 | 403.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3387.16 | 05-JAN-15:50 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.86 |
February | 6017.82 | 27-FEB-15:40 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.57 |
March | 9307.84 | 14-MAR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.55 |
April | 13089.09 | 26-APR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
May | 22662.81 | 07-MAY-16:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.04 |
June | 20820.89 | 18-JUN-17:01 | 0.00 | 684.82 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.77 |
July | 25268.26 | 23-JUL-18:31 | 0.00 | 782.66 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.36 |
August | 22686.58 | 06-AUG-17:32 | 0.00 | 586.99 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.60 |
September | 23114.60 | 10-SEP-16:42 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.40 |
October | 10405.13 | 04-OCT-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.43 |
November | 4718.48 | 04-NOV-15:40 | 130.46 | 271.31 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 |
December | 3517.74 | 05-DEC-15:40 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3387.16 | 0.00 | 271.31 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25268.26 | 1239.33 | 1627.84 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 720.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5488.79 | 05-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.07 |
February | 6740.60 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.25 |
March | 6824.61 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.49 |
April | 7381.92 | 28-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.39 |
May | 9241.78 | 08-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.27 |
June | 9755.56 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.06 |
July | 8714.23 | 06-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 |
August | 8406.92 | 28-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 |
September | 9967.05 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.95 |
October | 8760.90 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.87 |
November | 7987.11 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.39 |
December | 6620.16 | 04-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5488.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9967.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5687.33 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.56 |
February | 4456.74 | 10-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.25 |
March | 4993.69 | 01-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.99 |
April | 5334.92 | 28-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.17 |
May | 5709.51 | 05-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6719.12 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.64 |
July | 6435.00 | 10-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.56 |
August | 6736.24 | 26-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.00 |
September | 6462.37 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.65 |
October | 5844.04 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.41 |
November | 4566.37 | 09-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.32 |
December | 3988.12 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3988.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6736.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 918.93 | 11-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.06 |
February | 4625.89 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.76 |
March | 8524.62 | 14-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.62 |
April | 15916.27 | 27-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
May | 16397.49 | 15-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.42 |
June | 16789.99 | 28-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
July | 18061.48 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 0.00 |
August | 18619.31 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 0.00 |
September | 14284.17 | 14-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 |
October | 9966.09 | 04-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.01 |
November | 5283.71 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 819.00 | 05-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 819.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18619.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 464.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1901.99 | 05-JAN-16:10 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3983.43 | 07-FEB-16:50 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6042.65 | 14-MAR-17:10 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8057.26 | 25-APR-18:00 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2536.04 | 29-MAY-18:24 | 0.00 | 175.36 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4308.54 | 18-JUN-18:45 | 0.00 | 35.07 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6670.92 | 30-JUL-18:37 | 0.00 | 105.21 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8120.88 | 06-AUG-19:10 | 0.00 | 175.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2411.58 | 10-SEP-17:26 | 0.00 | 87.68 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4306.29 | 03-OCT-16:50 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5816.81 | 12-NOV-15:50 | 0.00 | 32.42 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7704.70 | 05-DEC-15:50 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1901.99 | 0.00 | 32.42 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8120.88 | 0.00 | 291.78 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1580.44 | 05-JAN-16:20 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3656.99 | 08-FEB-16:50 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5661.14 | 14-MAR-17:10 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7640.27 | 26-APR-18:20 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2290.62 | 29-MAY-18:22 | 0.00 | 175.36 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4005.07 | 22-JUN-18:50 | 0.00 | 97.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6192.13 | 30-JUL-18:40 | 0.00 | 105.21 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7706.68 | 06-AUG-19:10 | 0.00 | 175.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2196.61 | 08-SEP-17:30 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4035.49 | 03-OCT-16:50 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5274.09 | 10-NOV-16:10 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7099.45 | 05-DEC-16:00 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1580.44 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7706.68 | 0.00 | 291.78 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1425.32 | 05-JAN-16:20 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3550.42 | 08-FEB-16:50 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5670.11 | 14-MAR-17:10 | 0.00 | 97.26 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7754.14 | 26-APR-18:10 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2420.00 | 07-MAY-18:12 | 0.00 | 105.21 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4171.29 | 18-JUN-18:35 | 0.00 | 175.36 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6383.03 | 30-JUL-18:30 | 0.00 | 175.36 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7848.41 | 06-AUG-19:10 | 0.00 | 175.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2258.98 | 08-SEP-17:30 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4055.42 | 04-OCT-16:50 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5159.47 | 10-NOV-16:10 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6926.62 | 05-DEC-16:00 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1425.32 | 0.00 | 97.26 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7848.41 | 0.00 | 291.78 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 325859.79 | 17-JAN-22:53 | 0.00 | 7017.96 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 408218.42 | 19-FEB-06:41 | 0.00 | 3508.98 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 407287.09 | 24-MAR-04:52 | 0.00 | 7591.91 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 387569.67 | 19-APR-21:12 | 0.00 | 2807.18 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 322831.24 | 17-MAY-22:54 | 0.00 | 3508.98 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 183294.94 | 20-JUN-16:00 | 0.00 | 6316.16 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 275229.52 | 06-JUL-16:00 | 0.00 | 6316.16 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367851.39 | 10-AUG-21:02 | 0.00 | 4210.78 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105080.05 | 01-SEP-00:08 | 0.00 | 1518.38 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 379742.02 | 02-OCT-04:14 | 0.00 | 7591.91 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 408723.96 | 25-NOV-21:12 | 0.00 | 3795.95 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 390247.07 | 13-DEC-06:03 | 0.00 | 7017.96 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 105080.05 | 0.00 | 1518.38 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 408723.96 | 0.00 | 7591.91 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.173406E+13 | 1131683.53 | 10-JAN-16:00 | 0.646589E+12 | 1055910.61 | 07-JAN-07:00 |
February | 0.193153E+13 | 1361711.12 | 27-FEB-16:10 | 0.432677E+12 | 1048805.77 | 18-FEB-07:10 |
March | 0.259705E+13 | 1502979.99 | 14-MAR-15:00 | 0.281649E+12 | 840747.33 | 01-MAR-07:10 |
April | 0.288751E+13 | 1873335.33 | 27-APR-15:09 | 0.174534E+12 | 796219.12 | 19-APR-06:10 |
May | 0.184747E+13 | 1396992.09 | 04-MAY-15:20 | 0.105077E+12 | 529683.63 | 29-MAY-01:19 |
June | 0.227006E+13 | 1555719.35 | 28-JUN-15:00 | 0.612322E+11 | 350160.43 | 11-JUN-15:00 |
July | 0.276599E+13 | 1780498.18 | 31-JUL-15:00 | 0.487858E+11 | 262227.95 | 02-JUL-14:30 |
August | 0.330167E+13 | 1974765.33 | 29-AUG-15:09 | 0.519478E+11 | 324481.30 | 20-AUG-15:39 |
September | 0.183354E+13 | 1411988.34 | 14-SEP-15:20 | 0.637520E+11 | 339202.49 | 27-SEP-05:10 |
October | 0.219491E+13 | 1413680.06 | 03-OCT-15:30 | 0.146839E+12 | 444347.53 | 16-OCT-06:00 |
November | 0.247963E+13 | 1427718.89 | 06-NOV-16:00 | 0.328806E+12 | 893823.98 | 24-NOV-07:10 |
December | 0.290357E+13 | 1564755.25 | 05-DEC-16:19 | 0.528292E+12 | 1312737.27 | 26-DEC-07:10 |
Annual Sum or Average | 0.287470E+14 | 0.287018E+13 | ||||
Minimum of Months | 0.173406E+13 | 1131683.53 | 0.487858E+11 | 262227.95 | ||
Maximum of Months | 0.330167E+13 | 1974765.33 | 0.646589E+12 | 1312737.27 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.358355E+12 | 0.959699E+11 | 0.811612E+12 | 0.173544E+12 | 0.175765E+12 | 0.151239E+11 | 0.00 | 0.889047E+11 | 0.120247E+11 | 0.275805E+10 | 0.00 | 0.00 | 0.00 |
February | 0.325045E+12 | 0.791194E+11 | 0.102011E+13 | 0.156760E+12 | 0.165349E+12 | 0.137405E+11 | 0.00 | 0.142164E+12 | 0.267812E+11 | 0.245893E+10 | 0.00 | 0.00 | 0.00 |
March | 0.386070E+12 | 0.772284E+11 | 0.146224E+13 | 0.173828E+12 | 0.196625E+12 | 0.142565E+11 | 0.00 | 0.222808E+12 | 0.614080E+11 | 0.258019E+10 | 0.00 | 0.00 | 0.00 |
April | 0.345016E+12 | 0.643288E+11 | 0.170426E+13 | 0.167919E+12 | 0.190327E+12 | 0.221775E+11 | 0.00 | 0.296293E+12 | 0.955084E+11 | 0.167335E+10 | 0.00 | 0.00 | 0.00 |
May | 0.372213E+12 | 0.571362E+11 | 0.820095E+12 | 0.173686E+12 | 0.199023E+12 | 0.332925E+11 | 0.00 | 0.137298E+12 | 0.540650E+11 | 0.665279E+09 | 0.00 | 0.00 | 0.00 |
June | 0.370347E+12 | 0.502812E+11 | 0.110647E+13 | 0.168186E+12 | 0.195595E+12 | 0.456520E+11 | 0.00 | 0.229705E+12 | 0.103646E+12 | 0.174331E+09 | 0.00 | 0.00 | 0.00 |
July | 0.346881E+12 | 0.542659E+11 | 0.143833E+13 | 0.173418E+12 | 0.198447E+12 | 0.616865E+11 | 0.00 | 0.354216E+12 | 0.138701E+12 | 46193608.82 | 0.00 | 0.00 | 0.00 |
August | 0.386070E+12 | 0.623027E+11 | 0.177907E+13 | 0.173828E+12 | 0.206949E+12 | 0.706714E+11 | 0.00 | 0.472941E+12 | 0.149831E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345016E+12 | 0.702046E+11 | 0.784429E+12 | 0.167919E+12 | 0.192640E+12 | 0.413243E+11 | 0.00 | 0.156526E+12 | 0.754668E+11 | 16729366.71 | 0.00 | 0.00 | 0.00 |
October | 0.358355E+12 | 0.833067E+11 | 0.112844E+13 | 0.173544E+12 | 0.193178E+12 | 0.206450E+11 | 0.00 | 0.173525E+12 | 0.631016E+11 | 0.812536E+09 | 0.00 | 0.00 | 0.00 |
November | 0.354107E+12 | 0.900604E+11 | 0.140306E+13 | 0.168027E+12 | 0.179419E+12 | 0.129884E+11 | 0.00 | 0.212218E+12 | 0.583348E+11 | 0.141481E+10 | 0.00 | 0.00 | 0.00 |
December | 0.346881E+12 | 0.984350E+11 | 0.175516E+13 | 0.173418E+12 | 0.180751E+12 | 0.128608E+11 | 0.00 | 0.273041E+12 | 0.603788E+11 | 0.264238E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429436E+13 | 0.882639E+12 | 0.152133E+14 | 0.204408E+13 | 0.227407E+13 | 0.364419E+12 | 0.00 | 0.275964E+13 | 0.899247E+12 | 0.152428E+11 | |||
Minimum of Months | 0.325045E+12 | 0.502812E+11 | 0.784429E+12 | 0.156760E+12 | 0.165349E+12 | 0.128608E+11 | 0.00 | 0.889047E+11 | 0.120247E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386070E+12 | 0.984350E+11 | 0.177907E+13 | 0.173828E+12 | 0.206949E+12 | 0.706714E+11 | 0.00 | 0.472941E+12 | 0.149831E+12 | 0.275805E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.592622E+12 | 0.00 | 0.539672E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.383454E+12 | 0.00 | 0.492227E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.225003E+12 | 0.00 | 0.566458E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.123911E+12 | 0.00 | 0.506234E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.529439E+11 | 0.00 | 0.521327E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115638E+11 | 0.00 | 0.496684E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.187388E+10 | 0.00 | 0.469119E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.200229E+10 | 0.00 | 0.499455E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.172921E+11 | 0.00 | 0.464599E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.973709E+11 | 0.00 | 0.494684E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.278631E+12 | 0.00 | 0.501751E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.476678E+12 | 0.00 | 0.516135E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.226335E+13 | 0.606835E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.187388E+10 | 0.00 | 0.464599E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.592622E+12 | 0.00 | 0.566458E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 373325.05 | 02-JAN-08:09 | 56280.71 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 129663.18 | 02-JAN-08:20 | 127717.22 | 20-JAN-13:50 | 31684.26 | 02-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 373325.05 | 01-FEB-08:09 | 56280.71 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 129663.18 | 01-FEB-08:20 | 143526.52 | 08-FEB-15:20 | 48818.17 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 373325.05 | 01-MAR-08:09 | 56280.71 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 129663.18 | 01-MAR-08:20 | 150107.36 | 01-MAR-15:30 | 33670.36 | 10-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 373325.05 | 03-APR-07:10 | 56280.71 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 129663.18 | 03-APR-07:19 | 137995.09 | 24-APR-15:20 | 55751.85 | 26-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 373325.05 | 01-MAY-07:10 | 56280.71 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 129663.18 | 01-MAY-07:19 | 141904.00 | 25-MAY-15:00 | 56509.30 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 373325.05 | 01-JUN-07:10 | 56280.71 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 129663.18 | 01-JUN-07:19 | 138324.04 | 12-JUN-05:10 | 56225.75 | 27-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 373325.05 | 03-JUL-07:10 | 56280.71 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 129663.18 | 03-JUL-07:19 | 139228.98 | 05-JUL-15:00 | 55937.83 | 19-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 373325.05 | 01-AUG-07:10 | 56280.71 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 129663.18 | 01-AUG-07:19 | 148039.01 | 10-AUG-15:00 | 55887.49 | 21-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 373325.05 | 01-SEP-07:10 | 56280.71 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 129663.18 | 01-SEP-07:19 | 141158.77 | 05-SEP-14:30 | 56409.21 | 08-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 373325.05 | 02-OCT-07:10 | 56280.71 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 129663.18 | 02-OCT-07:19 | 149212.72 | 11-OCT-14:30 | 49382.28 | 04-OCT-11:39 | 0.00 | 01-OCT-00:10 |
November | 373325.05 | 01-NOV-07:10 | 56280.71 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 129663.18 | 01-NOV-07:19 | 140512.93 | 15-NOV-14:09 | 49905.90 | 04-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 373325.05 | 01-DEC-08:09 | 56280.71 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 129663.18 | 01-DEC-08:20 | 134007.68 | 06-DEC-13:09 | 28491.40 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 373325.05 | 56280.71 | 439129.89 | 129663.18 | 127717.22 | 28491.40 | 0.00 | |||||||
Maximum of Months | 373325.05 | 56280.71 | 794004.08 | 129663.18 | 150107.36 | 56509.30 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 94568.39 | 26-JAN-22:00 | 22103.76 | 26-JAN-22:00 | 31237.69 | 14-JAN-18:19 | 0.00 | 0.00 | 0.00 |
February | 149579.22 | 27-FEB-14:50 | 53262.46 | 27-FEB-15:50 | 34737.15 | 19-FEB-09:30 | 0.00 | 0.00 | 0.00 |
March | 162349.88 | 18-MAR-15:00 | 50990.31 | 18-MAR-14:09 | 20560.33 | 07-MAR-22:30 | 0.00 | 0.00 | 0.00 |
April | 343164.64 | 27-APR-14:00 | 82904.98 | 27-APR-13:20 | 7229.34 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 237966.42 | 04-MAY-14:30 | 82904.98 | 05-MAY-12:20 | 19407.24 | 23-MAY-21:19 | 0.00 | 0.00 | 0.00 |
June | 268146.34 | 22-JUN-15:30 | 82904.98 | 28-JUN-15:00 | 2187.66 | 09-JUN-09:00 | 0.00 | 0.00 | 0.00 |
July | 363186.83 | 31-JUL-15:00 | 82904.98 | 07-JUL-12:30 | 1164.05 | 18-JUL-18:00 | 0.00 | 0.00 | 0.00 |
August | 431104.97 | 29-AUG-14:39 | 82904.98 | 07-AUG-10:09 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 248230.79 | 14-SEP-12:00 | 82904.98 | 11-SEP-15:30 | 979.32 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 155326.87 | 04-OCT-16:10 | 52981.78 | 04-OCT-14:00 | 33365.46 | 05-OCT-03:39 | 0.00 | 0.00 | 0.00 |
November | 178768.24 | 04-NOV-13:50 | 61630.17 | 04-NOV-13:09 | 18869.84 | 28-NOV-05:40 | 0.00 | 0.00 | 0.00 |
December | 108081.59 | 03-DEC-00:20 | 48396.71 | 14-DEC-11:00 | 8739.95 | 09-DEC-17:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 94568.39 | 22103.76 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 431104.97 | 82904.98 | 34737.15 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1131683.53 | 10-JAN-16:00 | 373325.05 | 439129.89 | 56280.71 | 92996.58 | 99584.67 | 24758.45 | 0.00 | 36247.73 | 6414.77 |
February | 1361711.12 | 27-FEB-16:10 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 106084.19 | 33921.78 | 0.00 | 144567.22 | 52977.67 |
March | 1502979.99 | 14-MAR-15:00 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 125975.72 | 31858.35 | 0.00 | 150952.74 | 50935.22 |
April | 1873335.33 | 27-APR-15:09 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 134256.95 | 54241.95 | 0.00 | 341605.73 | 82904.98 |
May | 1396992.09 | 04-MAY-15:20 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 126755.29 | 56498.07 | 0.00 | 235225.55 | 73061.65 |
June | 1555719.35 | 28-JUN-15:00 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 133723.04 | 54585.06 | 0.00 | 260763.36 | 82904.98 |
July | 1780498.18 | 31-JUL-15:00 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 136973.23 | 55398.82 | 0.00 | 363186.83 | 82904.98 |
August | 1974765.33 | 29-AUG-15:09 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 147589.03 | 55773.79 | 0.00 | 428171.82 | 82904.98 |
September | 1411988.34 | 14-SEP-15:20 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 137653.34 | 54444.58 | 0.00 | 231533.92 | 82904.98 |
October | 1413680.06 | 03-OCT-15:30 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 139309.48 | 49138.17 | 0.00 | 148631.71 | 50484.79 |
November | 1427718.89 | 06-NOV-16:00 | 373325.05 | 675712.68 | 56280.71 | 92996.58 | 110595.03 | 3396.61 | 0.00 | 81609.43 | 33802.80 |
December | 1564755.25 | 05-DEC-16:19 | 373325.05 | 794004.08 | 56280.71 | 92996.58 | 114048.11 | 3868.26 | 0.00 | 104027.10 | 23962.98 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1131683.53 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 99584.67 | 3396.61 | 0.00 | 36247.73 | 6414.77 | |
Maximum of Months | 1974765.33 | 373325.05 | 794004.08 | 56280.71 | 92996.58 | 147589.03 | 56498.07 | 0.00 | 428171.82 | 82904.98 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 1047764.03 | 07-JAN-07:00 | 0.00 | 78823.74 | 30-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 1040659.19 | 18-FEB-07:10 | 0.00 | 78871.62 | 13-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 832600.75 | 01-MAR-07:10 | 0.00 | 78726.66 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 788072.54 | 19-APR-06:10 | 0.00 | 77705.07 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 521537.05 | 29-MAY-01:19 | 0.00 | 76211.52 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 342013.85 | 11-JUN-15:00 | 0.00 | 74200.63 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 254081.37 | 02-JUL-14:30 | 0.00 | 72342.32 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 316334.72 | 20-AUG-15:39 | 0.00 | 71397.69 | 28-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 331055.91 | 27-SEP-05:10 | 0.00 | 72616.07 | 28-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 436200.95 | 16-OCT-06:00 | 0.00 | 74582.44 | 30-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 885677.40 | 24-NOV-07:10 | 0.00 | 76506.10 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 1304590.69 | 26-DEC-07:10 | 0.00 | 78010.85 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 254081.37 | 0.00 | 71397.69 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1304590.69 | 0.00 | 78871.62 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.67 | 0.83 | 28.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.12 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.24 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.16 | 0.33 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.30 | 1.00 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.50 | 2.33 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.29 | 1.67 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 26.66 | 2.17 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.40 | 1.33 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.44 | 1.00 | 28.13 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.35 | 1.33 | 28.25 |
Annual Sum or Average | 0.00 | 0.00 | 147.83 | 26.36 | 12.00 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 26.67 | 2.33 | 28.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 25.60 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.88 | 0.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 18.92 | 0.17 | 20.34 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.33 | 0.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.54 | 1.00 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.74 | 0.67 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.02 | 1.67 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.07 | 1.33 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.81 | 0.67 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 27.87 | 5.50 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.07 | 1.67 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.97 | 1.33 | 24.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.99 | 1.00 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.74 | 0.83 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.67 | 0.83 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 27.02 | 5.67 | 27.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.99 | 1.33 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.44 | 2.67 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.18 | 2.17 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.88 | 1.00 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.00 | 4.00 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.71 | 3.00 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.70 | 1.00 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.33 | 27.80 | 14.33 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.18 | 4.00 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.22 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.51 | 0.50 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.63 | 0.67 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.10 | 1.67 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.06 | 1.50 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.74 | 0.50 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.01 | 0.00 | 4.83 | 27.93 | 4.83 | 27.93 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.01 | 0.00 | 0.00 | 1.67 | 28.10 | 1.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.30 | 2.83 | 25.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.76 | 2.17 | 24.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.09 | 1.17 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.64 | 2.50 | 25.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.08 | 0.00 | 9.33 | 25.78 | 9.33 | 25.78 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.08 | 0.00 | 0.00 | 2.83 | 28.09 | 2.83 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.03 | 1.50 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.77 | 0.33 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.49 | 1.17 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.00 | 0.83 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.88 | 0.33 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.32 | 0.00 | 10.17 | 28.13 | 4.17 | 28.03 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.32 | 0.00 | 0.00 | 3.33 | 28.49 | 1.50 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 18.16 | 2.83 | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.17 | 17.62 | 1.83 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.00 | 19.03 | 0.83 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.00 | 18.28 | 5.50 | 18.25 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.50 | 19.42 | 2.83 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 17.33 | 1.00 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.17 | 17.31 | 0.67 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.95 | 1.50 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.86 | 1.17 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.33 | 18.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.83 | 17.86 | 1.67 | 14.99 | 2.83 | 27.88 | 2.83 | 27.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 19.43 | 1.00 | 15.00 | 1.50 | 27.95 | 1.50 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 18.14 | 0.17 | 15.03 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.00 | 18.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 18.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.13 | 1.00 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
November | 1.00 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.33 | 18.43 | 0.17 | 15.03 | 1.50 | 27.85 | 1.50 | 27.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 18.93 | 0.17 | 15.03 | 1.00 | 28.13 | 1.00 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.83 | 18.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.18 | 1.33 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.92 | 0.50 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.58 | 1.17 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.04 | 1.00 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.93 | 0.33 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 18.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.17 | 18.49 | 0.00 | 9.83 | 28.24 | 4.33 | 28.12 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.14 | 0.00 | 0.00 | 3.33 | 28.58 | 1.33 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.00 | 27.89 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.89 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.92 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.33 | 27.92 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.92 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.95 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 27.95 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.95 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.24 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 29.03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.04 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.99 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 28.05 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.43 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 58.67 | 28.10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 29.03 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.67 | 24.07 | 104.83 | 26.25 | 0.83 | 26.84 |
February | 34.00 | 24.03 | 121.17 | 25.75 | 0.00 | 0.00 |
March | 27.17 | 24.02 | 113.17 | 25.81 | 0.00 | 0.00 |
April | 2.83 | 24.04 | 162.67 | 25.57 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 240.50 | 25.05 | 0.00 | 0.00 |
June | 0.17 | 26.81 | 283.67 | 24.82 | 0.17 | 26.81 |
July | 0.33 | 26.77 | 410.50 | 24.75 | 0.33 | 26.77 |
August | 0.83 | 26.67 | 473.67 | 24.52 | 0.83 | 26.67 |
September | 0.50 | 26.84 | 379.33 | 24.70 | 0.50 | 26.84 |
October | 0.67 | 26.84 | 205.67 | 25.42 | 0.67 | 26.84 |
November | 1.67 | 25.21 | 207.00 | 25.39 | 0.67 | 26.83 |
December | 12.33 | 24.25 | 112.50 | 26.39 | 0.83 | 26.83 |
Annual Sum or Average | 128.17 | 24.14 | 2814.67 | 25.09 | 4.83 | 26.80 |
Minimum of Months | 0.00 | 0.00 | 104.83 | 24.52 | 0.00 | 0.00 |
Maximum of Months | 47.67 | 26.84 | 473.67 | 26.39 | 0.83 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.50 | 24.20 | 58.33 | 25.61 | 12.50 | 26.36 |
February | 61.33 | 23.99 | 100.67 | 25.24 | 0.00 | 0.00 |
March | 25.33 | 23.98 | 124.83 | 25.35 | 0.00 | 0.00 |
April | 2.83 | 23.84 | 178.00 | 24.95 | 0.00 | 0.00 |
May | 9.67 | 23.70 | 247.33 | 24.67 | 0.00 | 0.00 |
June | 1.17 | 23.80 | 319.83 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 424.50 | 24.38 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 484.33 | 24.25 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 377.17 | 24.48 | 0.00 | 0.00 |
October | 2.17 | 23.80 | 221.83 | 24.95 | 0.00 | 0.00 |
November | 2.83 | 24.04 | 209.17 | 25.06 | 0.00 | 0.00 |
December | 18.00 | 24.03 | 112.67 | 25.92 | 0.00 | 0.00 |
Annual Sum or Average | 235.83 | 24.08 | 2858.67 | 24.70 | 12.50 | 26.36 |
Minimum of Months | 0.00 | 0.00 | 58.33 | 24.25 | 0.00 | 0.00 |
Maximum of Months | 112.50 | 24.20 | 484.33 | 25.92 | 12.50 | 26.36 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.83 | 23.45 | 12.17 | 21.28 | 12.00 | 21.24 |
February | 272.17 | 23.66 | 21.50 | 24.30 | 0.00 | 0.00 |
March | 183.17 | 23.84 | 17.33 | 24.49 | 0.00 | 0.00 |
April | 104.67 | 23.74 | 78.50 | 24.85 | 0.00 | 0.00 |
May | 47.00 | 23.59 | 167.33 | 24.59 | 0.00 | 0.00 |
June | 25.67 | 23.41 | 202.33 | 24.53 | 0.00 | 0.00 |
July | 25.00 | 23.36 | 306.50 | 24.44 | 0.00 | 0.00 |
August | 20.67 | 23.33 | 383.00 | 24.28 | 0.00 | 0.00 |
September | 23.00 | 23.34 | 288.67 | 24.44 | 0.00 | 0.00 |
October | 79.50 | 23.61 | 88.67 | 24.95 | 0.00 | 0.00 |
November | 167.67 | 23.68 | 43.50 | 24.48 | 0.00 | 0.00 |
December | 333.17 | 23.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1667.50 | 23.62 | 1609.50 | 24.45 | 12.00 | 21.24 |
Minimum of Months | 20.67 | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 385.83 | 23.84 | 383.00 | 24.95 | 12.00 | 21.24 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 21.83 | 101.67 | 19.27 | 101.67 | 19.27 |
February | 416.50 | 22.31 | 53.67 | 19.69 | 53.00 | 19.63 |
March | 406.17 | 23.05 | 17.33 | 21.41 | 14.00 | 20.80 |
April | 271.00 | 23.28 | 39.17 | 24.41 | 0.00 | 0.00 |
May | 162.33 | 23.46 | 110.33 | 24.24 | 0.00 | 0.00 |
June | 76.17 | 23.54 | 191.33 | 24.39 | 0.00 | 0.00 |
July | 37.33 | 23.56 | 302.33 | 24.33 | 0.00 | 0.00 |
August | 48.67 | 23.41 | 339.50 | 24.21 | 0.00 | 0.00 |
September | 131.00 | 23.34 | 195.00 | 24.24 | 0.00 | 0.00 |
October | 317.67 | 23.06 | 6.00 | 24.25 | 0.00 | 0.00 |
November | 415.83 | 22.64 | 27.67 | 21.42 | 20.00 | 20.44 |
December | 492.00 | 22.18 | 75.67 | 20.24 | 75.67 | 20.24 |
Annual Sum or Average | 3269.50 | 22.66 | 1459.67 | 23.47 | 264.33 | 19.79 |
Minimum of Months | 37.33 | 21.83 | 6.00 | 19.27 | 0.00 | 0.00 |
Maximum of Months | 494.83 | 23.56 | 339.50 | 24.41 | 101.67 | 20.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 452.83 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 363.83 | 23.19 | 11.33 | 24.27 | 0.00 | 0.00 |
March | 303.83 | 23.54 | 10.33 | 24.16 | 0.00 | 0.00 |
April | 142.67 | 23.66 | 69.50 | 24.40 | 0.00 | 0.00 |
May | 112.67 | 23.61 | 151.67 | 24.40 | 0.00 | 0.00 |
June | 15.67 | 23.66 | 235.00 | 24.39 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 382.83 | 24.30 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 427.33 | 24.20 | 0.00 | 0.00 |
September | 62.00 | 23.47 | 237.00 | 24.36 | 0.00 | 0.00 |
October | 217.00 | 23.48 | 36.83 | 24.98 | 0.00 | 0.00 |
November | 291.17 | 23.45 | 31.33 | 24.57 | 0.00 | 0.00 |
December | 416.67 | 23.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2378.33 | 23.34 | 1593.17 | 24.33 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 452.83 | 23.66 | 427.33 | 24.98 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.00 | 1.67 | 20.55 | 1.67 | 20.55 |
February | 425.17 | 22.28 | 6.17 | 23.84 | 1.83 | 20.76 |
March | 430.17 | 22.68 | 3.67 | 23.99 | 0.00 | 0.00 |
April | 278.33 | 22.81 | 72.50 | 24.16 | 0.00 | 0.00 |
May | 223.50 | 22.81 | 153.17 | 24.40 | 1.67 | 26.48 |
June | 155.00 | 22.86 | 215.17 | 24.31 | 3.00 | 26.47 |
July | 159.00 | 22.92 | 251.00 | 24.19 | 7.17 | 26.73 |
August | 172.00 | 22.82 | 253.33 | 24.06 | 6.00 | 26.73 |
September | 215.83 | 22.63 | 177.17 | 24.36 | 3.33 | 26.51 |
October | 346.00 | 22.60 | 47.67 | 24.61 | 0.17 | 25.70 |
November | 459.50 | 22.44 | 6.50 | 24.64 | 0.00 | 0.00 |
December | 496.00 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3862.50 | 22.48 | 1188.00 | 24.25 | 24.83 | 25.79 |
Minimum of Months | 155.00 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 22.92 | 253.33 | 24.64 | 7.17 | 26.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 455.33 | 22.06 | 26.33 | 22.80 | 13.00 | 20.68 |
February | 344.33 | 22.41 | 68.83 | 24.39 | 6.33 | 21.06 |
March | 338.17 | 22.89 | 61.67 | 24.26 | 0.00 | 0.00 |
April | 231.83 | 23.09 | 114.83 | 24.23 | 0.50 | 26.13 |
May | 211.67 | 23.02 | 148.67 | 24.31 | 0.50 | 26.18 |
June | 143.67 | 23.05 | 206.67 | 24.29 | 0.00 | 0.00 |
July | 98.00 | 23.11 | 289.67 | 24.21 | 0.83 | 25.81 |
August | 88.00 | 23.12 | 331.00 | 24.14 | 2.33 | 25.95 |
September | 148.67 | 22.99 | 251.33 | 24.35 | 4.17 | 26.86 |
October | 259.83 | 22.91 | 133.17 | 24.50 | 3.33 | 26.68 |
November | 361.33 | 22.64 | 56.33 | 24.71 | 1.83 | 26.67 |
December | 417.33 | 22.41 | 36.00 | 24.49 | 0.33 | 26.51 |
Annual Sum or Average | 3098.17 | 22.67 | 1724.50 | 24.27 | 33.17 | 23.18 |
Minimum of Months | 88.00 | 22.06 | 26.33 | 22.80 | 0.00 | 0.00 |
Maximum of Months | 455.33 | 23.12 | 331.00 | 24.71 | 13.00 | 26.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.83 | 22.54 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.50 | 22.94 | 65.00 | 24.87 | 0.00 | 0.00 |
March | 139.33 | 23.21 | 155.00 | 24.91 | 0.00 | 0.00 |
April | 24.33 | 24.00 | 326.50 | 24.68 | 5.67 | 26.07 |
May | 124.83 | 23.20 | 272.33 | 24.57 | 8.67 | 26.61 |
June | 16.17 | 24.13 | 375.33 | 24.46 | 5.00 | 26.16 |
July | 19.17 | 26.48 | 476.33 | 24.47 | 19.17 | 26.48 |
August | 17.33 | 26.36 | 513.50 | 24.36 | 17.33 | 26.36 |
September | 106.83 | 23.01 | 284.50 | 24.55 | 5.17 | 26.12 |
October | 155.67 | 23.01 | 204.17 | 24.80 | 1.17 | 25.91 |
November | 160.33 | 23.13 | 161.00 | 24.94 | 1.33 | 26.01 |
December | 181.83 | 23.21 | 114.17 | 25.48 | 0.00 | 0.00 |
Annual Sum or Average | 1729.17 | 23.02 | 2947.83 | 24.61 | 63.50 | 26.35 |
Minimum of Months | 16.17 | 22.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 479.83 | 26.48 | 513.50 | 25.48 | 19.17 | 26.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.27 | 133.50 | 19.96 | 133.50 | 19.96 |
February | 438.83 | 21.73 | 69.17 | 19.81 | 69.17 | 19.81 |
March | 478.50 | 22.61 | 11.50 | 20.43 | 11.50 | 20.43 |
April | 353.33 | 22.92 | 23.17 | 24.21 | 0.00 | 0.00 |
May | 245.67 | 23.19 | 76.83 | 24.15 | 0.00 | 0.00 |
June | 133.00 | 23.40 | 112.67 | 24.21 | 0.00 | 0.00 |
July | 88.83 | 23.47 | 243.17 | 24.18 | 0.00 | 0.00 |
August | 95.67 | 23.34 | 292.67 | 24.14 | 0.00 | 0.00 |
September | 211.67 | 23.23 | 130.33 | 24.14 | 0.00 | 0.00 |
October | 389.83 | 22.70 | 1.00 | 24.41 | 0.00 | 0.00 |
November | 466.00 | 22.16 | 8.50 | 20.56 | 8.50 | 20.56 |
December | 497.00 | 21.54 | 75.50 | 20.31 | 75.50 | 20.31 |
Annual Sum or Average | 3900.33 | 22.32 | 1178.00 | 23.12 | 298.17 | 20.05 |
Minimum of Months | 88.83 | 21.27 | 1.00 | 19.81 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.47 | 292.67 | 24.41 | 133.50 | 20.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.72 | 148.67 | 20.00 | 148.67 | 20.00 |
February | 385.00 | 21.21 | 69.83 | 20.22 | 69.83 | 20.22 |
March | 422.00 | 21.80 | 11.83 | 20.48 | 11.17 | 20.27 |
April | 316.83 | 22.22 | 38.67 | 24.53 | 0.00 | 0.00 |
May | 293.00 | 22.43 | 71.67 | 24.62 | 1.33 | 26.23 |
June | 216.83 | 22.64 | 127.50 | 24.56 | 2.33 | 26.36 |
July | 196.83 | 22.74 | 168.33 | 24.44 | 7.33 | 26.76 |
August | 199.00 | 22.63 | 179.00 | 24.28 | 7.17 | 26.66 |
September | 274.67 | 22.34 | 87.33 | 24.46 | 2.83 | 26.44 |
October | 386.67 | 21.92 | 13.83 | 24.92 | 0.00 | 0.00 |
November | 415.67 | 21.36 | 21.00 | 20.53 | 21.00 | 20.53 |
December | 422.00 | 20.97 | 91.00 | 20.33 | 91.00 | 20.33 |
Annual Sum or Average | 3955.50 | 21.75 | 1028.67 | 23.03 | 362.67 | 20.55 |
Minimum of Months | 196.83 | 20.72 | 11.83 | 20.00 | 0.00 | 0.00 |
Maximum of Months | 427.00 | 22.74 | 179.00 | 24.92 | 148.67 | 26.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.83 | 21.32 | 93.83 | 20.54 | 84.67 | 20.04 |
February | 369.00 | 21.71 | 87.33 | 22.92 | 35.83 | 20.44 |
March | 386.50 | 22.17 | 60.00 | 23.95 | 6.17 | 20.34 |
April | 307.67 | 22.44 | 90.17 | 24.46 | 0.17 | 26.13 |
May | 296.50 | 22.70 | 107.67 | 24.35 | 0.83 | 26.26 |
June | 254.83 | 22.81 | 116.67 | 24.34 | 0.00 | 0.00 |
July | 189.83 | 22.85 | 203.00 | 24.29 | 0.50 | 25.86 |
August | 183.67 | 22.80 | 255.33 | 24.22 | 1.17 | 26.01 |
September | 209.67 | 22.77 | 200.67 | 24.33 | 4.67 | 26.84 |
October | 331.00 | 22.41 | 112.67 | 24.61 | 3.00 | 26.65 |
November | 424.17 | 21.89 | 41.00 | 24.29 | 6.67 | 21.78 |
December | 441.00 | 21.48 | 72.33 | 21.94 | 45.17 | 20.32 |
Annual Sum or Average | 3861.67 | 22.13 | 1440.67 | 23.87 | 188.83 | 20.61 |
Minimum of Months | 183.67 | 21.32 | 41.00 | 20.54 | 0.00 | 0.00 |
Maximum of Months | 467.83 | 22.85 | 255.33 | 24.61 | 84.67 | 26.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.95 | 108.50 | 20.07 | 108.50 | 20.07 |
February | 441.00 | 21.34 | 55.17 | 20.28 | 52.17 | 20.04 |
March | 477.33 | 21.93 | 17.67 | 22.60 | 7.33 | 20.33 |
April | 369.17 | 22.31 | 61.83 | 24.53 | 0.00 | 0.00 |
May | 313.00 | 22.62 | 104.17 | 24.49 | 5.17 | 26.60 |
June | 249.17 | 22.67 | 135.33 | 24.37 | 1.33 | 26.12 |
July | 158.50 | 22.86 | 255.17 | 24.46 | 8.00 | 26.70 |
August | 181.83 | 22.62 | 229.00 | 24.29 | 4.83 | 26.45 |
September | 286.67 | 22.48 | 127.67 | 24.43 | 2.33 | 26.22 |
October | 445.33 | 22.08 | 31.50 | 24.50 | 1.17 | 27.09 |
November | 479.17 | 21.54 | 4.67 | 23.20 | 1.50 | 20.34 |
December | 496.33 | 21.21 | 46.83 | 20.43 | 46.83 | 20.43 |
Annual Sum or Average | 4399.50 | 21.87 | 1177.50 | 23.63 | 239.17 | 20.76 |
Minimum of Months | 158.50 | 20.95 | 4.67 | 20.07 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 22.86 | 255.17 | 24.53 | 108.50 | 27.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 293.83 | 19.57 | 293.83 | 19.57 |
February | 451.17 | 20.73 | 203.50 | 19.69 | 203.50 | 19.69 |
March | 509.17 | 21.65 | 102.67 | 20.14 | 102.67 | 20.14 |
April | 406.17 | 22.20 | 43.00 | 21.51 | 29.33 | 20.35 |
May | 304.83 | 22.60 | 65.83 | 24.08 | 0.17 | 20.92 |
June | 204.67 | 23.01 | 113.33 | 24.19 | 0.00 | 0.00 |
July | 151.17 | 23.11 | 229.67 | 24.14 | 0.00 | 0.00 |
August | 168.17 | 22.98 | 255.83 | 24.10 | 0.00 | 0.00 |
September | 305.17 | 22.67 | 86.17 | 24.07 | 0.00 | 0.00 |
October | 478.67 | 21.88 | 43.83 | 20.02 | 43.83 | 20.02 |
November | 489.00 | 21.05 | 146.00 | 19.78 | 146.00 | 19.78 |
December | 497.00 | 20.45 | 277.33 | 19.82 | 277.33 | 19.82 |
Annual Sum or Average | 4467.17 | 21.57 | 1861.00 | 21.56 | 1096.67 | 19.77 |
Minimum of Months | 151.17 | 20.28 | 43.00 | 19.57 | 0.00 | 0.00 |
Maximum of Months | 509.17 | 23.11 | 293.83 | 24.19 | 293.83 | 20.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 293.17 | 19.57 | 293.17 | 19.57 |
February | 454.00 | 20.62 | 196.33 | 19.82 | 196.33 | 19.82 |
March | 510.17 | 21.37 | 83.83 | 20.01 | 83.83 | 20.01 |
April | 372.67 | 21.88 | 58.17 | 22.48 | 25.00 | 20.35 |
May | 324.83 | 22.16 | 91.83 | 24.31 | 0.83 | 22.91 |
June | 233.50 | 22.51 | 182.83 | 24.35 | 0.67 | 25.82 |
July | 208.83 | 22.66 | 236.33 | 24.27 | 7.00 | 26.61 |
August | 217.00 | 22.50 | 239.00 | 24.17 | 5.83 | 26.52 |
September | 319.00 | 22.05 | 109.50 | 24.23 | 0.67 | 25.77 |
October | 470.67 | 21.53 | 42.33 | 20.38 | 39.33 | 20.11 |
November | 489.00 | 20.77 | 139.67 | 19.79 | 139.67 | 19.79 |
December | 497.00 | 20.35 | 267.83 | 19.78 | 267.83 | 19.78 |
Annual Sum or Average | 4598.67 | 21.32 | 1940.83 | 21.84 | 1060.17 | 19.87 |
Minimum of Months | 208.83 | 20.17 | 42.33 | 19.57 | 0.67 | 19.57 |
Maximum of Months | 510.17 | 22.66 | 293.17 | 24.35 | 293.17 | 26.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.17 | 20.57 | 233.33 | 19.62 | 231.00 | 19.57 |
February | 397.17 | 21.00 | 164.17 | 20.68 | 136.33 | 19.95 |
March | 416.33 | 21.48 | 103.33 | 21.33 | 70.83 | 20.09 |
April | 342.17 | 21.89 | 97.50 | 23.24 | 26.00 | 20.35 |
May | 329.50 | 22.22 | 94.67 | 24.27 | 1.67 | 24.74 |
June | 292.33 | 22.51 | 106.67 | 24.33 | 0.33 | 25.35 |
July | 226.33 | 22.61 | 194.50 | 24.24 | 0.67 | 25.87 |
August | 223.17 | 22.49 | 223.50 | 24.19 | 1.83 | 25.83 |
September | 275.83 | 22.32 | 169.50 | 24.26 | 4.50 | 26.81 |
October | 371.83 | 21.71 | 110.83 | 23.60 | 22.50 | 20.33 |
November | 450.83 | 21.13 | 132.17 | 20.88 | 106.33 | 19.96 |
December | 465.00 | 20.69 | 213.00 | 19.95 | 205.67 | 19.79 |
Annual Sum or Average | 4282.67 | 21.55 | 1843.17 | 22.35 | 807.67 | 19.91 |
Minimum of Months | 223.17 | 20.57 | 94.67 | 19.62 | 0.33 | 19.57 |
Maximum of Months | 492.17 | 22.61 | 233.33 | 24.33 | 231.00 | 26.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 248.50 | 19.57 | 248.50 | 19.57 |
February | 448.83 | 20.79 | 159.00 | 19.86 | 158.00 | 19.83 |
March | 491.67 | 21.38 | 70.00 | 20.64 | 62.17 | 20.22 |
April | 391.67 | 21.84 | 68.17 | 23.53 | 14.67 | 20.42 |
May | 353.83 | 22.25 | 89.83 | 24.45 | 5.67 | 26.45 |
June | 289.83 | 22.41 | 128.17 | 24.34 | 1.83 | 26.27 |
July | 189.00 | 22.59 | 229.50 | 24.39 | 8.33 | 26.67 |
August | 237.17 | 22.42 | 198.33 | 24.26 | 5.33 | 26.50 |
September | 336.33 | 22.14 | 103.50 | 24.36 | 2.17 | 25.99 |
October | 465.67 | 21.54 | 40.17 | 22.25 | 20.67 | 20.23 |
November | 486.00 | 20.97 | 106.83 | 20.05 | 106.83 | 20.05 |
December | 497.00 | 20.61 | 221.17 | 20.00 | 221.17 | 20.00 |
Annual Sum or Average | 4689.00 | 21.43 | 1663.17 | 22.11 | 855.33 | 20.05 |
Minimum of Months | 189.00 | 20.32 | 40.17 | 19.57 | 1.83 | 19.57 |
Maximum of Months | 502.00 | 22.59 | 248.50 | 24.45 | 248.50 | 26.67 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50440 | 26.36484 | 0.39366 | 8.69998 |
February | 454.00000 | 24.50010 | 27.70377 | 0.40600 | 8.94676 |
March | 514.00000 | 24.42754 | 27.75269 | 0.39978 | 8.73956 |
April | 485.00000 | 24.53708 | 31.40468 | 0.45069 | 9.86072 |
May | 508.00000 | 24.50172 | 36.15997 | -0.3738 | 8.93651 |
June | 496.00000 | 24.47374 | 38.33763 | -0.3580 | 8.60064 |
July | 497.00000 | 24.61652 | 43.65123 | -0.2757 | 7.85866 |
August | 514.00000 | 24.48001 | 47.69997 | -0.2794 | 7.57722 |
September | 485.00000 | 24.54921 | 43.70517 | -0.2968 | 8.04210 |
October | 502.00000 | 24.58958 | 34.62863 | 0.48918 | 10.69958 |
November | 489.00000 | 24.60006 | 32.51880 | 0.47484 | 10.41758 |
December | 497.00000 | 24.57043 | 26.91213 | 0.42265 | 9.32794 |
Annual Sum or Average | 5943.00000 | 24.52882 | 34.79111 | 0.11809 | 8.97050 |
Minimum of Months | 454.00000 | 24.42754 | 26.36484 | -0.3738 | 7.57722 |
Maximum of Months | 514.00000 | 24.61652 | 47.69997 | 0.48918 | 10.69958 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.31391 | 29.69951 | 0.36718 | 8.42495 |
February | 454.00000 | 24.34596 | 29.04780 | 0.38302 | 8.38744 |
March | 514.00000 | 24.34403 | 28.90834 | 0.40071 | 8.67203 |
April | 485.00000 | 24.35915 | 32.36175 | 0.44005 | 9.39102 |
May | 508.00000 | 24.32480 | 37.50848 | -0.4040 | 9.01630 |
June | 496.00000 | 24.29897 | 39.88418 | -0.3764 | 8.45892 |
July | 497.00000 | 24.32210 | 43.92717 | -0.3335 | 7.76337 |
August | 514.00000 | 24.23743 | 46.88027 | -0.3274 | 7.52904 |
September | 485.00000 | 24.35820 | 44.84368 | -0.3386 | 8.10590 |
October | 502.00000 | 24.41976 | 36.14852 | 0.46640 | 9.97543 |
November | 489.00000 | 24.46175 | 33.90821 | 0.45670 | 9.83171 |
December | 497.00000 | 24.45770 | 28.53075 | 0.41438 | 9.06179 |
Annual Sum or Average | 5943.00000 | 24.35315 | 36.02103 | 0.09269 | 8.71680 |
Minimum of Months | 454.00000 | 24.23743 | 28.53075 | -0.4040 | 7.52904 |
Maximum of Months | 514.00000 | 24.46175 | 46.88027 | 0.46640 | 9.97543 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.58735 | 31.09414 | 0.15639 | 5.96124 |
February | 454.00000 | 23.85458 | 30.46209 | 0.23310 | 6.49309 |
March | 514.00000 | 24.07719 | 30.06594 | 0.30157 | 7.06170 |
April | 485.00000 | 24.17005 | 33.64151 | 0.35485 | 7.87266 |
May | 508.00000 | 24.18385 | 38.20618 | -0.4842 | 10.30804 |
June | 496.00000 | 24.18084 | 40.56923 | -0.4551 | 9.69367 |
July | 497.00000 | 24.21158 | 45.00685 | -0.4148 | 9.07545 |
August | 514.00000 | 24.15112 | 47.69135 | -0.4062 | 8.83556 |
September | 485.00000 | 24.20891 | 45.63789 | -0.4182 | 9.13127 |
October | 502.00000 | 24.15574 | 37.36655 | 0.37405 | 8.15959 |
November | 489.00000 | 24.03169 | 35.55944 | 0.31622 | 7.30930 |
December | 497.00000 | 23.82965 | 30.27786 | 0.22055 | 6.22319 |
Annual Sum or Average | 5943.00000 | 24.05473 | 37.17835 | -0.0212 | 8.02235 |
Minimum of Months | 454.00000 | 23.58735 | 30.06594 | -0.4842 | 5.96124 |
Maximum of Months | 514.00000 | 24.21158 | 47.69135 | 0.37405 | 10.30804 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.84947 | 32.19671 | -0.2947 | 10.68933 |
February | 454.00000 | 22.43614 | 32.84047 | -0.1328 | 8.45700 |
March | 514.00000 | 23.24199 | 32.04366 | 0.07719 | 6.30969 |
April | 485.00000 | 23.64568 | 35.01362 | 0.21654 | 6.70097 |
May | 508.00000 | 23.91183 | 39.04277 | -0.5844 | 12.87621 |
June | 496.00000 | 24.09436 | 40.85168 | -0.4847 | 10.38870 |
July | 497.00000 | 24.15058 | 45.10790 | -0.4285 | 9.27468 |
August | 514.00000 | 24.06002 | 47.94264 | -0.4351 | 9.35591 |
September | 485.00000 | 23.90925 | 46.92152 | -0.5337 | 11.61264 |
October | 502.00000 | 23.41177 | 39.80398 | 0.17574 | 6.49426 |
November | 489.00000 | 22.83454 | 38.74871 | 0.00172 | 6.58433 |
December | 497.00000 | 22.18811 | 33.44195 | -0.2024 | 7.86342 |
Annual Sum or Average | 5943.00000 | 23.31801 | 38.69914 | -0.2201 | 8.88964 |
Minimum of Months | 454.00000 | 21.84947 | 32.04366 | -0.5844 | 6.30969 |
Maximum of Months | 514.00000 | 24.15058 | 47.94264 | 0.21654 | 12.87621 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.04712 | 28.88030 | 0.02118 | 5.83639 |
February | 454.00000 | 23.35386 | 29.37854 | 0.11066 | 6.09606 |
March | 514.00000 | 23.74874 | 29.34926 | 0.22222 | 6.38626 |
April | 485.00000 | 24.00567 | 32.27405 | 0.32633 | 7.50111 |
May | 508.00000 | 24.05076 | 37.05977 | -0.5149 | 11.16138 |
June | 496.00000 | 24.17321 | 39.24044 | -0.4326 | 9.25600 |
July | 497.00000 | 24.23361 | 43.12106 | -0.3697 | 8.13091 |
August | 514.00000 | 24.15385 | 46.26812 | -0.3675 | 8.03837 |
September | 485.00000 | 24.06983 | 44.66918 | -0.4657 | 10.09839 |
October | 502.00000 | 23.87467 | 36.56387 | 0.30294 | 7.26549 |
November | 489.00000 | 23.70614 | 34.60426 | 0.23460 | 6.60126 |
December | 497.00000 | 23.48673 | 29.33935 | 0.13690 | 5.76807 |
Annual Sum or Average | 5943.00000 | 23.82853 | 35.94137 | -0.0684 | 7.68830 |
Minimum of Months | 454.00000 | 23.04712 | 28.88030 | -0.5149 | 5.76807 |
Maximum of Months | 514.00000 | 24.23361 | 46.26812 | 0.32633 | 11.16138 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.99798 | 29.55051 | -0.1849 | 6.34523 |
February | 454.00000 | 22.38584 | 30.25869 | -0.0741 | 6.14934 |
March | 514.00000 | 22.87808 | 30.36355 | 0.06118 | 5.87272 |
April | 485.00000 | 23.29696 | 33.37091 | 0.21215 | 6.84803 |
May | 508.00000 | 23.54458 | 37.83476 | -0.6101 | 14.92444 |
June | 496.00000 | 23.70697 | 40.06942 | -0.5036 | 12.12579 |
July | 497.00000 | 23.63638 | 44.42319 | -0.4874 | 11.82842 |
August | 514.00000 | 23.50877 | 47.82720 | -0.4966 | 12.05347 |
September | 485.00000 | 23.43238 | 45.95859 | -0.5930 | 14.68368 |
October | 502.00000 | 23.05062 | 37.84765 | 0.15565 | 6.50185 |
November | 489.00000 | 22.53920 | 36.25062 | 0.00006 | 5.79768 |
December | 497.00000 | 22.16179 | 30.72047 | -0.1335 | 5.95187 |
Annual Sum or Average | 5943.00000 | 23.01646 | 37.08626 | -0.2230 | 9.11423 |
Minimum of Months | 454.00000 | 21.99798 | 29.55051 | -0.6101 | 5.79768 |
Maximum of Months | 514.00000 | 23.70697 | 47.82720 | 0.21215 | 14.92444 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.25413 | 29.34062 | -0.1327 | 6.87662 |
February | 454.00000 | 22.88701 | 29.48905 | 0.04650 | 7.15994 |
March | 514.00000 | 23.28519 | 29.61115 | 0.16427 | 6.74090 |
April | 485.00000 | 23.60329 | 32.72373 | 0.27715 | 7.54143 |
May | 508.00000 | 23.66474 | 37.61993 | -0.5981 | 14.13946 |
June | 496.00000 | 23.79690 | 40.00648 | -0.5222 | 11.77909 |
July | 497.00000 | 23.88467 | 43.82241 | -0.4413 | 10.03498 |
August | 514.00000 | 23.84515 | 46.91113 | -0.4063 | 9.53366 |
September | 485.00000 | 23.79756 | 44.92661 | -0.4661 | 11.60467 |
October | 502.00000 | 23.54338 | 36.74780 | 0.28273 | 8.03542 |
November | 489.00000 | 23.04892 | 35.33253 | 0.11526 | 6.80332 |
December | 497.00000 | 22.68714 | 29.97126 | -0.0109 | 6.46742 |
Annual Sum or Average | 5943.00000 | 23.36152 | 36.42344 | -0.1432 | 8.90817 |
Minimum of Months | 454.00000 | 22.25413 | 29.34062 | -0.5981 | 6.46742 |
Maximum of Months | 514.00000 | 23.88467 | 46.91113 | 0.28273 | 14.13946 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60715 | 28.40056 | -0.0222 | 5.64660 |
February | 454.00000 | 23.41146 | 28.34066 | 0.19369 | 6.83540 |
March | 514.00000 | 24.02585 | 28.09751 | 0.37163 | 8.54906 |
April | 485.00000 | 24.38371 | 30.98900 | 0.52632 | 11.53952 |
May | 508.00000 | 23.98803 | 36.70855 | -0.4154 | 10.63284 |
June | 496.00000 | 24.20382 | 38.74163 | -0.2832 | 7.97049 |
July | 497.00000 | 24.42888 | 42.15081 | -0.1238 | 6.81163 |
August | 514.00000 | 24.34741 | 45.23325 | -0.1112 | 6.37982 |
September | 485.00000 | 23.94373 | 44.43320 | -0.3772 | 9.99246 |
October | 502.00000 | 23.95090 | 35.70590 | 0.39706 | 9.16076 |
November | 489.00000 | 23.98844 | 33.18125 | 0.37020 | 8.75786 |
December | 497.00000 | 24.04805 | 27.38529 | 0.34260 | 8.18420 |
Annual Sum or Average | 5943.00000 | 23.94717 | 34.99390 | 0.07077 | 8.37008 |
Minimum of Months | 454.00000 | 22.60715 | 27.38529 | -0.4154 | 5.64660 |
Maximum of Months | 514.00000 | 24.42888 | 45.23325 | 0.52632 | 11.53952 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26468 | 31.18557 | -0.4159 | 10.41257 |
February | 454.00000 | 21.79595 | 31.76316 | -0.2684 | 8.76252 |
March | 514.00000 | 22.69701 | 31.77281 | -0.0427 | 6.26581 |
April | 485.00000 | 23.20920 | 34.37686 | 0.11427 | 6.24650 |
May | 508.00000 | 23.62731 | 38.25925 | -0.6794 | 15.86153 |
June | 496.00000 | 23.88714 | 40.24882 | -0.5594 | 12.12341 |
July | 497.00000 | 23.98697 | 44.05216 | -0.4901 | 10.46858 |
August | 514.00000 | 23.92163 | 47.39505 | -0.4868 | 10.48321 |
September | 485.00000 | 23.68027 | 46.04520 | -0.6190 | 13.84924 |
October | 502.00000 | 22.98862 | 39.09444 | 0.07860 | 6.04508 |
November | 489.00000 | 22.23658 | 37.71399 | -0.1261 | 6.64165 |
December | 497.00000 | 21.53895 | 32.48941 | -0.3363 | 8.38157 |
Annual Sum or Average | 5943.00000 | 22.91177 | 37.90685 | -0.3202 | 9.63865 |
Minimum of Months | 454.00000 | 21.26468 | 31.18557 | -0.6794 | 6.04508 |
Maximum of Months | 514.00000 | 23.98697 | 47.39505 | 0.11427 | 15.86153 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.71042 | 30.35496 | -0.5369 | 12.03741 |
February | 385.00000 | 21.19549 | 31.14370 | -0.3857 | 9.21183 |
March | 433.00000 | 21.83919 | 31.71831 | -0.1995 | 6.77867 |
April | 410.00000 | 22.64255 | 34.12651 | 0.03617 | 6.61419 |
May | 430.00000 | 22.98201 | 38.62645 | -0.8153 | 22.07323 |
June | 418.00000 | 23.38692 | 40.63209 | -0.6305 | 16.33412 |
July | 422.00000 | 23.47443 | 44.53501 | -0.5706 | 14.74097 |
August | 433.00000 | 23.35642 | 48.08521 | -0.5739 | 14.77299 |
September | 410.00000 | 22.91462 | 47.09285 | -0.7836 | 21.08989 |
October | 427.00000 | 22.12359 | 39.63200 | -0.0779 | 6.35006 |
November | 417.00000 | 21.35408 | 37.79093 | -0.3069 | 7.64447 |
December | 422.00000 | 20.95587 | 31.73230 | -0.4610 | 9.83869 |
Annual Sum or Average | 5034.00000 | 22.25085 | 37.99500 | -0.4429 | 12.30990 |
Minimum of Months | 385.00000 | 20.71042 | 30.35496 | -0.8153 | 6.35006 |
Maximum of Months | 433.00000 | 23.47443 | 48.08521 | 0.03617 | 22.07323 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.51471 | 29.86758 | -0.3246 | 9.44706 |
February | 454.00000 | 22.21248 | 30.24352 | -0.1179 | 8.25534 |
March | 514.00000 | 22.65466 | 30.74057 | 0.01253 | 7.02823 |
April | 485.00000 | 23.07918 | 33.77739 | 0.14185 | 7.26094 |
May | 508.00000 | 23.28005 | 38.50935 | -0.7320 | 18.72632 |
June | 496.00000 | 23.41756 | 41.02112 | -0.6614 | 15.92524 |
July | 497.00000 | 23.60755 | 44.69823 | -0.5545 | 13.18052 |
August | 514.00000 | 23.60699 | 47.79936 | -0.5068 | 12.34666 |
September | 485.00000 | 23.52907 | 45.69311 | -0.5565 | 14.44141 |
October | 502.00000 | 23.05994 | 37.86173 | 0.16706 | 7.85217 |
November | 489.00000 | 22.22154 | 36.72163 | -0.0876 | 7.35138 |
December | 497.00000 | 21.79983 | 30.97969 | -0.2377 | 8.32450 |
Annual Sum or Average | 5943.00000 | 22.83688 | 37.37530 | -0.2901 | 10.87181 |
Minimum of Months | 454.00000 | 21.51471 | 29.86758 | -0.7320 | 7.02823 |
Maximum of Months | 514.00000 | 23.60755 | 47.79936 | 0.16706 | 18.72632 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94354 | 30.48045 | -0.4641 | 10.32912 |
February | 454.00000 | 21.41101 | 31.34844 | -0.3175 | 8.59867 |
March | 514.00000 | 22.07324 | 31.63559 | -0.1320 | 6.51740 |
April | 485.00000 | 22.75950 | 34.34418 | 0.07638 | 6.80555 |
May | 508.00000 | 23.16395 | 38.64405 | -0.7300 | 19.36923 |
June | 496.00000 | 23.33565 | 41.01899 | -0.6349 | 15.74865 |
July | 497.00000 | 23.72708 | 44.23006 | -0.4474 | 11.83757 |
August | 514.00000 | 23.48393 | 48.07282 | -0.5065 | 12.88862 |
September | 485.00000 | 23.13853 | 46.74120 | -0.6856 | 17.69375 |
October | 502.00000 | 22.31063 | 39.46551 | -0.0217 | 6.23637 |
November | 489.00000 | 21.58956 | 37.81206 | -0.2362 | 6.98354 |
December | 497.00000 | 21.21482 | 31.74305 | -0.3806 | 8.54559 |
Annual Sum or Average | 5943.00000 | 22.43754 | 38.00554 | -0.3743 | 10.98314 |
Minimum of Months | 454.00000 | 20.94354 | 30.48045 | -0.7300 | 6.23637 |
Maximum of Months | 514.00000 | 23.72708 | 48.07282 | 0.07638 | 19.36923 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27876 | 32.19139 | -0.6988 | 18.53678 |
February | 454.00000 | 20.75222 | 33.00159 | -0.5509 | 14.94062 |
March | 514.00000 | 21.66096 | 33.09833 | -0.3020 | 9.06182 |
April | 485.00000 | 22.47731 | 35.65503 | -0.0619 | 7.08339 |
May | 508.00000 | 23.15270 | 39.29269 | -0.8333 | 22.20966 |
June | 496.00000 | 23.62051 | 40.86904 | -0.6389 | 15.01684 |
July | 497.00000 | 23.77329 | 44.50497 | -0.5475 | 12.40233 |
August | 514.00000 | 23.67995 | 48.03875 | -0.5574 | 12.74305 |
September | 485.00000 | 23.15174 | 47.54534 | -0.7939 | 20.25710 |
October | 502.00000 | 21.97027 | 41.23017 | -0.1694 | 7.28574 |
November | 489.00000 | 21.04469 | 39.44292 | -0.4351 | 11.16390 |
December | 497.00000 | 20.45779 | 33.87188 | -0.6401 | 15.71262 |
Annual Sum or Average | 5943.00000 | 22.18019 | 39.09971 | -0.5192 | 13.86117 |
Minimum of Months | 454.00000 | 20.27876 | 32.19139 | -0.8333 | 7.08339 |
Maximum of Months | 514.00000 | 23.77329 | 48.03875 | -0.0619 | 22.20966 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17320 | 31.46224 | -0.7185 | 18.72365 |
February | 454.00000 | 20.62508 | 32.43925 | -0.5617 | 14.11005 |
March | 514.00000 | 21.37813 | 32.71008 | -0.3323 | 9.01779 |
April | 485.00000 | 22.34328 | 35.14867 | -0.0396 | 7.29163 |
May | 508.00000 | 22.82703 | 39.42908 | -0.8617 | 24.34791 |
June | 496.00000 | 23.36809 | 40.89406 | -0.6238 | 16.36951 |
July | 497.00000 | 23.46282 | 44.88758 | -0.5544 | 14.49142 |
August | 514.00000 | 23.34110 | 48.38835 | -0.5637 | 14.75248 |
September | 485.00000 | 22.72019 | 48.00353 | -0.8483 | 23.92922 |
October | 502.00000 | 21.66431 | 40.98468 | -0.2045 | 7.44609 |
November | 489.00000 | 20.76975 | 39.14225 | -0.4854 | 11.47269 |
December | 497.00000 | 20.35143 | 33.16260 | -0.6586 | 15.92287 |
Annual Sum or Average | 5943.00000 | 21.92941 | 38.92884 | -0.5379 | 14.82707 |
Minimum of Months | 454.00000 | 20.17320 | 31.46224 | -0.8617 | 7.29163 |
Maximum of Months | 514.00000 | 23.46282 | 48.38835 | -0.0396 | 24.34791 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.63182 | 30.86133 | -0.5843 | 15.84729 |
February | 454.00000 | 21.38531 | 31.25543 | -0.3557 | 11.79531 |
March | 514.00000 | 21.94876 | 31.72285 | -0.1799 | 8.89059 |
April | 485.00000 | 22.52827 | 34.76922 | 0.00198 | 7.83684 |
May | 508.00000 | 22.84523 | 39.44599 | -0.8745 | 24.76034 |
June | 496.00000 | 23.13046 | 41.64849 | -0.7465 | 19.39371 |
July | 497.00000 | 23.38744 | 45.17007 | -0.6137 | 15.48653 |
August | 514.00000 | 23.35242 | 48.46895 | -0.5812 | 15.03380 |
September | 485.00000 | 23.07751 | 46.96049 | -0.7093 | 20.15107 |
October | 502.00000 | 22.36380 | 39.39071 | -0.0163 | 8.13499 |
November | 489.00000 | 21.38058 | 37.96179 | -0.3259 | 10.12184 |
December | 497.00000 | 20.91368 | 32.28128 | -0.4995 | 13.59550 |
Annual Sum or Average | 5943.00000 | 22.25260 | 38.37571 | -0.4584 | 14.28005 |
Minimum of Months | 454.00000 | 20.63182 | 30.86133 | -0.8745 | 7.83684 |
Maximum of Months | 514.00000 | 23.38744 | 48.46895 | 0.00198 | 24.76034 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32148 | 31.09390 | -0.6615 | 16.82492 |
February | 454.00000 | 20.82023 | 31.98530 | -0.4975 | 12.78968 |
March | 514.00000 | 21.47838 | 32.34230 | -0.2961 | 8.52077 |
April | 485.00000 | 22.26569 | 35.20267 | -0.0480 | 7.40949 |
May | 508.00000 | 22.77167 | 39.47326 | -0.8574 | 24.67253 |
June | 496.00000 | 23.06513 | 41.62262 | -0.7143 | 18.93682 |
July | 497.00000 | 23.50862 | 44.70945 | -0.5060 | 13.89090 |
August | 514.00000 | 23.22968 | 48.74053 | -0.5804 | 15.48501 |
September | 485.00000 | 22.71587 | 47.92097 | -0.8266 | 23.18749 |
October | 502.00000 | 21.71866 | 40.73039 | -0.1789 | 7.13278 |
November | 489.00000 | 20.98626 | 38.55609 | -0.4180 | 9.87346 |
December | 497.00000 | 20.60818 | 32.50774 | -0.5754 | 13.25970 |
Annual Sum or Average | 5943.00000 | 21.96688 | 38.78458 | -0.5139 | 14.34630 |
Minimum of Months | 454.00000 | 20.32148 | 31.09390 | -0.8574 | 7.13278 |
Maximum of Months | 514.00000 | 23.50862 | 48.74053 | -0.0480 | 24.67253 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.179933E+09 | 15620.33 | 11-JAN-16:00 | 11.52 | 0.499200E+09 | 0.00 | 0.679132E+09 | 0.04 | 2.78 | 07-JAN-06:30 | 0.00 | 0.00 |
February | 0.224391E+10 | 80851.48 | 27-FEB-14:50 | 29.07 | 0.115716E+11 | 0.00 | 0.138155E+11 | 0.15 | 6.88 | 27-FEB-14:50 | 0.00 | 0.00 |
March | 0.486037E+10 | 63337.53 | 18-MAR-14:10 | 42.20 | 0.202575E+11 | 0.00 | 0.251179E+11 | 0.21 | 6.32 | 18-MAR-14:10 | 0.00 | 0.00 |
April | 0.185568E+11 | 93173.66 | 27-APR-15:00 | 130.17 | 0.980474E+11 | 0.00 | 0.116604E+12 | 0.77 | 7.06 | 26-APR-14:40 | 0.00 | 0.00 |
May | 0.382684E+11 | 95704.99 | 04-MAY-14:30 | 237.67 | 0.204047E+12 | 0.00 | 0.242316E+12 | 1.45 | 7.12 | 04-MAY-14:30 | 0.00 | 0.00 |
June | 0.617360E+11 | 94709.52 | 22-JUN-15:30 | 350.65 | 0.349502E+12 | 0.00 | 0.411238E+12 | 2.40 | 7.11 | 22-JUN-15:30 | 0.00 | 0.00 |
July | 0.898560E+11 | 117209.45 | 31-JUL-16:00 | 470.17 | 0.536613E+12 | 0.00 | 0.626469E+12 | 3.25 | 7.09 | 19-JUL-14:50 | 0.00 | 0.00 |
August | 0.105502E+12 | 131658.90 | 29-AUG-14:30 | 519.35 | 0.647329E+12 | 0.00 | 0.752831E+12 | 3.66 | 7.10 | 21-AUG-14:40 | 0.00 | 0.00 |
September | 0.544459E+11 | 102116.40 | 14-SEP-13:00 | 302.09 | 0.302963E+12 | 0.00 | 0.357409E+12 | 2.03 | 7.06 | 15-SEP-12:20 | 0.00 | 0.00 |
October | 0.145226E+11 | 80927.31 | 03-OCT-15:30 | 120.70 | 0.675500E+11 | 0.00 | 0.820726E+11 | 0.62 | 6.89 | 03-OCT-15:30 | 0.00 | 0.00 |
November | 0.239556E+10 | 80582.07 | 04-NOV-13:30 | 28.03 | 0.124125E+11 | 0.00 | 0.148080E+11 | 0.14 | 6.87 | 04-NOV-13:10 | 0.00 | 0.00 |
December | 75194410.92 | 10434.26 | 16-DEC-06:02 | 7.93 | 0.208712E+09 | 0.00 | 0.283906E+09 | 0.03 | 2.78 | 26-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.392643E+12 | 2249.54 | 0.225100E+13 | 0.264364E+13 | 1.24 | |||||||
Minimum of Months | 75194410.92 | 10434.26 | 7.93 | 0.208712E+09 | 0.00 | 0.283906E+09 | 0.03 | 2.78 | 0.00 | 0.00 | ||
Maximum of Months | 0.105502E+12 | 131658.90 | 519.35 | 0.647329E+12 | 0.00 | 0.752831E+12 | 3.66 | 7.12 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.251873E+10 | 93173.66 | 27-APR-15:00 | 8.17 | 0.174908E+11 | 0.00 | 0.200096E+11 | 0.08 | 7.06 | 26-APR-14:40 | 0.00 | 0.00 |
May | 0.281181E+10 | 95704.99 | 04-MAY-14:30 | 9.17 | 0.195478E+11 | 0.00 | 0.223596E+11 | 0.09 | 7.12 | 04-MAY-14:30 | 0.00 | 0.00 |
June | 0.520803E+10 | 94709.52 | 22-JUN-15:30 | 17.00 | 0.362642E+11 | 0.00 | 0.414722E+11 | 0.16 | 7.11 | 22-JUN-15:30 | 0.00 | 0.00 |
July | 0.171411E+11 | 117209.45 | 31-JUL-16:00 | 53.38 | 0.118424E+12 | 0.00 | 0.135565E+12 | 0.50 | 7.09 | 19-JUL-14:50 | 0.00 | 0.00 |
August | 0.369677E+11 | 131658.90 | 29-AUG-14:30 | 108.70 | 0.254746E+12 | 0.00 | 0.291714E+12 | 1.01 | 7.10 | 21-AUG-14:40 | 0.00 | 0.00 |
September | 0.860997E+10 | 102116.40 | 14-SEP-13:00 | 27.17 | 0.598939E+11 | 0.00 | 0.685038E+11 | 0.26 | 7.06 | 15-SEP-12:20 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.732573E+11 | 223.58 | 0.506367E+12 | 0.579624E+12 | 0.18 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.369677E+11 | 131658.90 | 108.70 | 0.254746E+12 | 0.00 | 0.291714E+12 | 1.01 | 7.12 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.120247E+11 | 744.00 | 27995.48 | 11-JAN-04:50 | 547466.12 | 26-JAN-23:00 | 21.65 | 18.33 | 13.95 |
February | 0.267218E+11 | 672.00 | 49248.27 | 27-FEB-11:40 | 582798.51 | 28-FEB-22:41 | 24.49 | 18.36 | 13.95 |
March | 0.613431E+11 | 744.00 | 49248.27 | 08-MAR-10:40 | 596299.28 | 25-MAR-18:31 | 27.39 | 18.41 | 13.95 |
April | 0.942676E+11 | 720.00 | 49248.27 | 01-APR-09:00 | 644571.07 | 27-APR-18:30 | 31.05 | 19.19 | 13.95 |
May | 0.515730E+11 | 744.00 | 49248.27 | 02-MAY-13:00 | 552148.67 | 23-MAY-22:00 | 22.49 | 18.89 | 13.95 |
June | 0.996995E+11 | 720.00 | 49248.27 | 01-JUN-11:10 | 345662.69 | 28-JUN-17:10 | 26.28 | 19.85 | 13.95 |
July | 0.126861E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 512445.15 | 30-JUL-18:11 | 31.22 | 21.87 | 13.95 |
August | 0.130739E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 662648.84 | 10-AUG-19:35 | 36.28 | 24.01 | 13.95 |
September | 0.695748E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 393243.31 | 01-SEP-00:03 | 22.73 | 19.10 | 13.95 |
October | 0.628260E+11 | 744.00 | 49248.27 | 01-OCT-08:20 | 579655.61 | 05-OCT-03:41 | 24.78 | 18.50 | 13.95 |
November | 0.581694E+11 | 720.00 | 49248.27 | 03-NOV-19:30 | 593240.75 | 08-NOV-22:23 | 27.35 | 18.40 | 13.95 |
December | 0.603788E+11 | 744.00 | 48396.71 | 14-DEC-12:00 | 614517.80 | 13-DEC-04:52 | 29.98 | 18.33 | 13.95 |
Annual Sum or Average | 0.854179E+12 | 8760.00 | 27.17 | 19.45 | 13.95 | ||||
Minimum of Months | 0.120247E+11 | 672.00 | 27995.48 | 345662.69 | 21.65 | 18.33 | 13.95 | ||
Maximum of Months | 0.130739E+12 | 744.00 | 49248.27 | 662648.84 | 36.28 | 24.01 | 13.95 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 155990.54 | 09-JAN-05:43 | 21.03 | 21.03 | 0.17 |
February | 59330444.10 | 9.67 | 4014.19 | 27-FEB-15:50 | 633459.20 | 27-FEB-15:50 | 21.12 | 21.08 | 1.25 |
March | 64874037.45 | 27.53 | 1742.04 | 18-MAR-14:10 | 474349.92 | 18-MAR-14:20 | 21.14 | 21.09 | 2.12 |
April | 0.874183E+09 | 85.90 | 16828.36 | 27-APR-13:20 | 753057.67 | 27-APR-15:10 | 21.37 | 21.12 | 6.87 |
May | 0.209664E+10 | 184.26 | 16828.36 | 05-MAY-12:20 | 786817.92 | 04-MAY-14:30 | 21.76 | 21.26 | 13.23 |
June | 0.327467E+10 | 290.47 | 16828.36 | 28-JUN-16:00 | 776533.44 | 22-JUN-15:30 | 22.28 | 21.40 | 20.81 |
July | 0.879131E+10 | 390.55 | 16828.36 | 07-JUL-12:30 | 928067.91 | 31-JUL-16:00 | 22.57 | 21.29 | 27.09 |
August | 0.126503E+11 | 438.25 | 16828.36 | 07-AUG-10:10 | 1031336.73 | 29-AUG-14:40 | 22.94 | 21.40 | 30.25 |
September | 0.434133E+10 | 256.48 | 16828.36 | 11-SEP-15:30 | 825681.59 | 14-SEP-13:10 | 22.26 | 21.50 | 17.91 |
October | 0.275620E+09 | 72.66 | 3733.51 | 04-OCT-15:00 | 669550.08 | 04-OCT-15:00 | 21.31 | 21.14 | 6.21 |
November | 0.165337E+09 | 9.79 | 12381.90 | 04-NOV-13:10 | 644447.51 | 04-NOV-14:00 | 21.26 | 21.23 | 1.19 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 156527.17 | 26-DEC-06:30 | 21.03 | 21.03 | 0.08 |
Annual Sum or Average | 0.325936E+11 | 1765.58 | 21.68 | 21.21 | 10.66 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 155990.54 | 21.03 | 21.03 | 0.08 | ||
Maximum of Months | 0.126503E+11 | 438.25 | 16828.36 | 1031336.73 | 22.94 | 21.50 | 30.25 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.03 | 21.03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.12 | 21.12 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.14 | 21.14 | 0.00 |
April | 0.366640E+09 | 8.17 | 16828.36 | 27-APR-13:20 | 753057.67 | 27-APR-15:10 | 21.37 | 21.33 | 0.51 |
May | 0.395305E+09 | 9.17 | 16828.36 | 05-MAY-12:20 | 786817.92 | 04-MAY-14:30 | 21.76 | 21.71 | 0.56 |
June | 0.671867E+09 | 17.00 | 16828.36 | 28-JUN-16:00 | 776533.44 | 22-JUN-15:30 | 22.28 | 22.19 | 1.07 |
July | 0.304831E+10 | 53.73 | 16828.36 | 07-JUL-12:30 | 928067.91 | 31-JUL-16:00 | 22.57 | 22.29 | 3.27 |
August | 0.644121E+10 | 108.84 | 16828.36 | 07-AUG-10:10 | 1031336.73 | 29-AUG-14:40 | 22.94 | 22.34 | 6.62 |
September | 0.155068E+10 | 27.17 | 16828.36 | 11-SEP-15:30 | 825681.59 | 14-SEP-13:10 | 22.26 | 22.12 | 1.71 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.31 | 21.31 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.26 | 21.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.124740E+11 | 224.07 | 21.68 | 21.58 | 1.16 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 21.03 | 0.00 | ||
Maximum of Months | 0.644121E+10 | 108.84 | 16828.36 | 1031336.73 | 22.94 | 22.34 | 6.62 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.458145E+12 | 0.00 | 458.35 | 1074027.61 | 02-JAN-06:03 | 0.00 | 65.89 | 75.45 | 2.61 | 0.00 | 0.12 | 0.72 | 02-JAN-06:03 |
February | 0.293469E+12 | 0.00 | 366.64 | 935008.24 | 27-FEB-02:00 | 0.00 | 62.46 | 72.36 | 1.71 | 0.00 | 0.08 | 0.63 | 27-FEB-02:00 |
March | 0.163252E+12 | 0.00 | 350.79 | 810964.65 | 10-MAR-04:47 | 0.00 | 58.88 | 68.95 | 0.69 | 0.00 | 0.04 | 0.55 | 10-MAR-04:47 |
April | 0.898371E+11 | 0.00 | 230.77 | 837704.34 | 23-APR-17:48 | 0.00 | 55.39 | 63.56 | 0.34 | 0.00 | 0.02 | 0.56 | 23-APR-17:48 |
May | 0.371593E+11 | 0.00 | 127.29 | 837767.38 | 29-MAY-01:20 | 0.00 | 61.90 | 64.78 | 0.23 | 0.00 | 0.01 | 0.56 | 29-MAY-01:20 |
June | 0.779962E+10 | 0.00 | 45.13 | 774923.24 | 04-JUN-15:46 | 0.00 | 58.51 | 60.09 | 0.03 | 0.00 | 0.00 | 0.52 | 04-JUN-15:46 |
July | 0.143673E+10 | 0.00 | 8.39 | 399019.13 | 02-JUL-14:30 | 0.00 | 71.45 | 71.57 | 0.01 | 0.00 | 0.00 | 0.27 | 02-JUL-14:30 |
August | 0.147216E+10 | 0.00 | 13.92 | 564960.33 | 06-AUG-14:10 | 0.00 | 67.22 | 67.53 | 0.01 | 0.00 | 0.00 | 0.38 | 06-AUG-14:10 |
September | 0.116574E+11 | 0.00 | 88.57 | 732854.51 | 24-SEP-14:36 | 0.00 | 61.14 | 63.84 | 0.07 | 0.00 | 0.00 | 0.49 | 24-SEP-14:36 |
October | 0.677077E+11 | 0.00 | 256.45 | 827967.20 | 01-OCT-16:04 | 0.00 | 59.30 | 66.35 | 0.30 | 0.00 | 0.02 | 0.56 | 01-OCT-16:04 |
November | 0.207125E+12 | 0.00 | 365.71 | 901421.44 | 05-NOV-14:26 | 0.00 | 57.51 | 69.63 | 0.88 | 0.00 | 0.05 | 0.61 | 05-NOV-14:26 |
December | 0.365313E+12 | 0.00 | 413.31 | 1050997.27 | 26-DEC-07:10 | 0.00 | 59.74 | 72.60 | 1.59 | 0.00 | 0.09 | 0.71 | 26-DEC-07:10 |
Annual Sum or Average | 0.170438E+13 | 2725.33 | 61.65 | 68.07 | 0.70 | 0.00 | 0.04 | ||||||
Minimum of Months | 0.143673E+10 | 0.00 | 8.39 | 399019.13 | 0.00 | 55.39 | 60.09 | 0.01 | 0.00 | 0.00 | 0.27 | ||
Maximum of Months | 0.458145E+12 | 0.00 | 458.35 | 1074027.61 | 0.00 | 71.45 | 75.45 | 2.61 | 0.00 | 0.12 | 0.72 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.65 | 21.65 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 24.49 | 24.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 27.39 | 27.39 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.05 | 31.05 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.49 | 22.49 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 26.28 | 26.28 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.22 | 31.22 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 36.28 | 36.28 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.78 | 24.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.35 | 27.35 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.98 | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.17 | 27.17 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 21.65 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | 36.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 3984460.85 | 0.00 | 0.12 | 3984460.85 | 0.00 | 0.00 | 0.00 | 0.00 | 10846.93 | 11-JAN-05:31 | 10846.93 | 11-JAN-05:31 | 0.00 | 0.00 | 0.00 |
February | 0.588433E+09 | 0.00 | 7.59 | 0.572271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56367.39 | 24-FEB-04:01 | 36000.65 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.225917E+09 | 0.00 | 9.03 | 0.199267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43620.57 | 10-MAR-04:01 | 22885.17 | 09-MAR-04:52 | 0.00 | 0.00 | 0.00 |
April | 0.448185E+10 | 0.00 | 48.16 | 0.446718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63153.74 | 27-APR-16:00 | 63153.74 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.850880E+10 | 0.00 | 104.48 | 0.847369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62121.67 | 15-MAY-16:00 | 62121.67 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.178197E+11 | 0.00 | 203.79 | 0.177114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91785.21 | 11-JUN-18:10 | 84929.69 | 11-JUN-14:36 | 0.00 | 0.00 | 0.00 |
July | 0.327933E+11 | 0.00 | 286.09 | 0.324019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122933.45 | 30-JUL-15:47 | 114065.61 | 23-JUL-16:39 | 0.00 | 0.00 | 0.00 |
August | 0.448794E+11 | 0.00 | 322.21 | 0.441011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126689.44 | 13-AUG-14:10 | 108206.16 | 13-AUG-14:12 | 0.00 | 0.00 | 0.00 |
September | 0.144469E+11 | 0.00 | 168.33 | 0.140425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84358.94 | 24-SEP-16:55 | 76085.81 | 10-SEP-16:10 | 0.00 | 0.00 | 0.00 |
October | 0.228286E+10 | 0.00 | 42.03 | 0.222410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70369.92 | 01-OCT-16:06 | 68861.44 | 08-OCT-14:20 | 0.00 | 0.00 | 0.00 |
November | 0.396599E+09 | 0.00 | 7.13 | 0.363901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65066.81 | 05-NOV-14:28 | 44378.07 | 05-NOV-14:28 | 0.00 | 0.00 | 0.00 |
December | 9859750.10 | 0.00 | 0.27 | 9303379.80 | 0.00 | 0.00 | 0.00 | 0.00 | 19746.33 | 16-DEC-06:02 | 15106.94 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126438E+12 | 1199.25 | 0.124571E+12 | ||||||||||||
Minimum of Months | 3984460.85 | 0.00 | 0.12 | 3984460.85 | 0.00 | 0.00 | 0.00 | 0.00 | 10846.93 | 10846.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.448794E+11 | 0.00 | 322.21 | 0.441011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126689.44 | 114065.61 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 34310074.65 | 0.00 | 2.57 | 34310074.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4599.66 | 11-JAN-14:00 | 4599.66 | 11-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.117129E+10 | 0.00 | 20.90 | 0.117129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62144.12 | 27-FEB-15:00 | 62144.12 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.198274E+10 | 0.00 | 38.63 | 0.198274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36040.64 | 14-MAR-16:00 | 36040.64 | 14-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.122473E+11 | 0.00 | 121.22 | 0.122360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116003.33 | 27-APR-15:00 | 112754.36 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.207189E+11 | 0.00 | 218.87 | 0.202543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96100.40 | 05-MAY-15:50 | 90776.30 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.377346E+11 | 0.00 | 331.02 | 0.375015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103840.93 | 28-JUN-16:00 | 103840.93 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.676698E+11 | 0.00 | 450.08 | 0.629496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138686.01 | 31-JUL-16:00 | 123522.20 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.925483E+11 | 0.00 | 502.09 | 0.830975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152130.83 | 29-AUG-14:30 | 132338.59 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.329717E+11 | 0.00 | 279.62 | 0.301140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118407.21 | 14-SEP-13:00 | 96134.42 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.687370E+10 | 0.00 | 105.90 | 0.686421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77441.42 | 04-OCT-15:00 | 77441.42 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.109673E+10 | 0.00 | 19.45 | 0.101221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47582.21 | 04-NOV-13:10 | 41712.22 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 2911.09 | 0.00 | 1.66 | 2911.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 26-DEC-06:30 | 0.73 | 26-DEC-06:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275049E+12 | 2092.01 | 0.257217E+12 | ||||||||||||
Minimum of Months | 2911.09 | 0.00 | 1.66 | 2911.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.925483E+11 | 0.00 | 502.09 | 0.830975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152130.83 | 132338.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.244112E+09 | 0.00 | 10.35 | 0.244112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31282.54 | 11-JAN-14:00 | 31282.54 | 11-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.867428E+10 | 0.00 | 25.17 | 0.867428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 471940.03 | 27-FEB-15:00 | 471940.03 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.153008E+11 | 0.00 | 39.05 | 0.153008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 328398.51 | 18-MAR-14:00 | 328398.51 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.919810E+11 | 0.00 | 105.48 | 0.919742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 987527.20 | 27-APR-15:00 | 976315.06 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.181430E+12 | 0.00 | 221.58 | 0.177320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 885337.96 | 05-MAY-16:00 | 826464.00 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.313111E+12 | 0.00 | 318.12 | 0.311622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 934919.74 | 28-JUN-16:00 | 934919.74 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.539568E+12 | 0.00 | 388.50 | 0.502148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1222587.30 | 31-JUL-16:00 | 1057607.39 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.719599E+12 | 0.00 | 416.43 | 0.646265E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1361318.42 | 29-AUG-14:30 | 1183122.26 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.295276E+12 | 0.00 | 280.27 | 0.268997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1123278.40 | 14-SEP-13:00 | 889097.06 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.547954E+11 | 0.00 | 106.90 | 0.547779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 698642.39 | 04-OCT-15:00 | 698642.39 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.940125E+10 | 0.00 | 22.77 | 0.860057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 456183.27 | 04-NOV-13:20 | 399316.64 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 16326.01 | 0.00 | 7.32 | 16326.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 26-DEC-07:00 | 2.10 | 26-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222938E+13 | 1941.93 | 0.208592E+13 | ||||||||||||
Minimum of Months | 16326.01 | 0.00 | 7.32 | 16326.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 2.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.719599E+12 | 0.00 | 416.43 | 0.646265E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1361318.42 | 1183122.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 15751297.84 | 0.00 | 3.60 | 15751297.84 | 0.00 | 0.00 | 0.00 | 0.00 | 2102.76 | 11-JAN-16:00 | 2102.76 | 11-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.704445E+09 | 0.00 | 18.49 | 0.704445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37099.85 | 27-FEB-15:00 | 37099.85 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.140348E+10 | 0.00 | 35.75 | 0.140348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32098.87 | 18-MAR-14:00 | 32098.87 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.954483E+10 | 0.00 | 97.47 | 0.953831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118516.36 | 27-APR-15:00 | 115863.47 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.189956E+11 | 0.00 | 209.82 | 0.185670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95882.58 | 05-MAY-16:00 | 95627.83 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.337042E+11 | 0.00 | 305.42 | 0.335561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114454.77 | 28-JUN-16:00 | 114454.77 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.589091E+11 | 0.00 | 381.85 | 0.547200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149781.52 | 27-JUL-15:50 | 133013.44 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.771155E+11 | 0.00 | 405.00 | 0.693817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155878.10 | 29-AUG-14:40 | 141784.16 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.296646E+11 | 0.00 | 265.38 | 0.269983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120046.67 | 14-SEP-13:00 | 96893.05 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.492514E+10 | 0.00 | 89.67 | 0.492514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69720.97 | 04-OCT-15:00 | 69720.97 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.898293E+09 | 0.00 | 15.52 | 0.821788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44594.61 | 04-NOV-13:30 | 39314.81 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 13.92 | 0.00 | 0.02 | 13.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 04-DEC-04:01 | 0.23 | 04-DEC-04:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235881E+12 | 1827.98 | 0.220632E+12 | ||||||||||||
Minimum of Months | 13.92 | 0.00 | 0.02 | 13.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 0.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.771155E+11 | 0.00 | 405.00 | 0.693817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155878.10 | 141784.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.312706E+12 | 0.798639E+11 | 735.17 | 0.312644E+12 | 61404025.79 | 0.00 | 1.00 | 02-JAN-22:10 | 0.03 | 20-JAN-06:08 | 434407.81 | 26-JAN-23:00 | 434407.81 | 26-JAN-23:00 | 13829.56 | 27-JAN-01:00 | 91054.19 | 26-JAN-23:00 | 0.00 |
February | 0.494935E+12 | 0.118291E+12 | 669.90 | 0.494886E+12 | 49285520.45 | 0.00 | 1.00 | 02-FEB-22:17 | 0.01 | 28-FEB-22:15 | 439317.27 | 19-FEB-10:10 | 439317.27 | 19-FEB-10:10 | 19868.29 | 19-FEB-12:02 | 91138.39 | 19-FEB-10:10 | 0.00 |
March | 0.785281E+12 | 0.179884E+12 | 743.73 | 0.785218E+12 | 63018673.39 | 0.00 | 1.00 | 01-MAR-00:04 | 0.03 | 15-MAR-22:13 | 426812.71 | 25-MAR-22:57 | 426122.78 | 07-MAR-22:30 | 25536.81 | 07-MAR-01:20 | 90923.94 | 25-MAR-22:57 | 0.00 |
April | 0.990033E+12 | 0.224781E+12 | 720.00 | 0.990033E+12 | 154410.29 | 0.00 | 1.00 | 01-APR-13:20 | 0.87 | 19-APR-21:17 | 417899.90 | 13-APR-03:20 | 417899.90 | 13-APR-03:20 | 257.35 | 15-APR-06:10 | 126151.14 | 27-APR-16:00 | 0.00 |
May | 0.317476E+12 | 0.810549E+11 | 742.92 | 0.317304E+12 | 0.172399E+09 | 0.00 | 1.00 | 17-MAY-21:17 | 0.03 | 23-MAY-23:11 | 434241.30 | 17-MAY-22:00 | 434241.30 | 17-MAY-22:00 | 11862.02 | 23-MAY-22:40 | 91051.34 | 17-MAY-22:00 | 0.00 |
June | 0.535600E+12 | 0.133803E+12 | 720.00 | 0.535486E+12 | 0.113676E+09 | 0.00 | 0.59 | 28-JUN-17:00 | 0.51 | 01-JUN-06:20 | 210130.71 | 28-JUN-16:00 | 210130.71 | 28-JUN-16:00 | 3509.29 | 12-JUN-17:00 | 70239.79 | 28-JUN-17:00 | 0.00 |
July | 0.792148E+12 | 0.200929E+12 | 744.00 | 0.790934E+12 | 0.121455E+10 | 0.00 | 0.82 | 24-JUL-15:00 | 0.72 | 01-JUL-06:10 | 300602.63 | 31-JUL-16:00 | 299286.56 | 24-JUL-15:00 | 4890.42 | 27-JUL-19:50 | 108368.17 | 24-JUL-15:00 | 0.00 |
August | 0.102820E+13 | 0.267524E+12 | 744.00 | 0.102700E+13 | 0.120372E+10 | 0.00 | 1.00 | 07-AUG-13:20 | 0.90 | 01-AUG-07:00 | 393021.08 | 29-AUG-19:30 | 389081.26 | 10-AUG-19:40 | 5956.15 | 29-AUG-19:40 | 137916.58 | 10-AUG-17:00 | 0.00 |
September | 0.309725E+12 | 0.785000E+11 | 720.00 | 0.308703E+12 | 0.102212E+10 | 0.00 | 0.37 | 01-SEP-00:03 | 0.31 | 27-SEP-06:10 | 136338.77 | 01-SEP-00:08 | 135207.59 | 01-SEP-00:10 | 3549.44 | 15-SEP-20:40 | 38918.95 | 14-SEP-17:00 | 0.00 |
October | 0.553159E+12 | 0.132552E+12 | 742.31 | 0.553101E+12 | 57506938.23 | 0.00 | 1.00 | 02-OCT-04:13 | 0.02 | 13-OCT-22:00 | 434675.28 | 02-OCT-04:14 | 434675.28 | 02-OCT-04:14 | 15045.80 | 02-OCT-05:03 | 91058.78 | 02-OCT-04:14 | 0.00 |
November | 0.761196E+12 | 0.173913E+12 | 719.95 | 0.761054E+12 | 0.141589E+09 | 0.00 | 1.00 | 08-NOV-22:17 | 0.02 | 29-NOV-00:42 | 425801.03 | 25-NOV-21:16 | 425801.03 | 25-NOV-21:16 | 15471.35 | 08-NOV-23:10 | 90906.59 | 25-NOV-21:16 | 0.00 |
December | 0.102111E+13 | 0.225465E+12 | 744.00 | 0.102111E+13 | 0.00 | 0.00 | 1.00 | 02-DEC-17:17 | 0.77 | 13-DEC-05:28 | 420807.44 | 09-DEC-20:23 | 420807.44 | 09-DEC-20:23 | 0.00 | 01-DEC-00:10 | 90820.95 | 09-DEC-20:23 | 0.00 |
Annual Sum or Average | 0.790157E+13 | 0.189656E+13 | 8745.98 | 0.789747E+13 | 0.409943E+10 | ||||||||||||||
Minimum of Months | 0.309725E+12 | 0.785000E+11 | 669.90 | 0.308703E+12 | 0.00 | 0.00 | 0.37 | 0.01 | 136338.77 | 135207.59 | 0.00 | 38918.95 | 0.00 | ||||||
Maximum of Months | 0.102820E+13 | 0.267524E+12 | 744.00 | 0.102700E+13 | 0.121455E+10 | 0.00 | 1.00 | 0.90 | 439317.27 | 439317.27 | 25536.81 | 137916.58 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.465749E+10 | 0.120869E+10 | 744.00 | 0.465749E+10 | 0.00 | 0.00 | 0.31 | 05-JAN-16:10 | 0.18 | 21-JAN-18:20 | 2376.91 | 05-JAN-16:10 | 2376.91 | 05-JAN-16:10 | 0.00 | 01-JAN-00:05 | 601.56 | 05-JAN-16:10 | 0.00 |
February | 0.901158E+10 | 0.219405E+10 | 672.00 | 0.901158E+10 | 0.00 | 0.00 | 0.54 | 27-FEB-16:20 | 0.42 | 18-FEB-18:20 | 4387.05 | 07-FEB-16:50 | 4387.05 | 07-FEB-16:50 | 0.00 | 01-FEB-00:01 | 1170.21 | 27-FEB-16:10 | 0.00 |
March | 0.152089E+11 | 0.354182E+10 | 744.00 | 0.152089E+11 | 0.00 | 0.00 | 0.76 | 14-MAR-17:00 | 0.64 | 01-MAR-08:00 | 6375.73 | 14-MAR-17:10 | 6375.73 | 14-MAR-17:10 | 0.00 | 01-MAR-00:01 | 1633.97 | 18-MAR-17:00 | 0.00 |
April | 0.196277E+11 | 0.453254E+10 | 720.00 | 0.196277E+11 | 0.00 | 0.00 | 1.00 | 26-APR-17:00 | 0.83 | 01-APR-07:00 | 8342.16 | 26-APR-18:20 | 8342.16 | 26-APR-18:20 | 0.00 | 01-APR-00:10 | 2718.46 | 27-APR-16:00 | 0.00 |
May | 0.560781E+10 | 0.146413E+10 | 744.00 | 0.560781E+10 | 0.00 | 0.00 | 0.38 | 29-MAY-18:23 | 0.23 | 18-MAY-07:00 | 2989.24 | 29-MAY-18:23 | 2989.24 | 29-MAY-18:23 | 0.00 | 01-MAY-00:10 | 844.82 | 14-MAY-18:02 | 0.00 |
June | 0.102829E+11 | 0.262424E+10 | 720.00 | 0.102829E+11 | 0.00 | 0.00 | 0.60 | 22-JUN-18:50 | 0.46 | 14-JUN-06:50 | 4701.02 | 18-JUN-18:50 | 4701.02 | 18-JUN-18:50 | 0.00 | 01-JUN-00:10 | 1439.93 | 28-JUN-17:00 | 0.00 |
July | 0.156089E+11 | 0.409028E+10 | 744.00 | 0.156089E+11 | 0.00 | 0.00 | 0.88 | 30-JUL-18:11 | 0.66 | 01-JUL-07:00 | 6982.48 | 30-JUL-18:37 | 6982.48 | 30-JUL-18:37 | 0.00 | 01-JUL-00:10 | 2301.84 | 30-JUL-18:05 | 0.00 |
August | 0.204040E+11 | 0.552950E+10 | 744.00 | 0.204040E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-17:11 | 0.85 | 19-AUG-06:50 | 8423.63 | 06-AUG-19:33 | 8423.63 | 06-AUG-19:33 | 0.00 | 01-AUG-00:05 | 2969.11 | 10-AUG-17:00 | 0.00 |
September | 0.545966E+10 | 0.143671E+10 | 720.00 | 0.545966E+10 | 0.00 | 0.00 | 0.38 | 10-SEP-17:22 | 0.23 | 28-SEP-07:00 | 2869.04 | 10-SEP-17:30 | 2869.04 | 10-SEP-17:30 | 0.00 | 01-SEP-00:03 | 844.15 | 10-SEP-17:12 | 0.00 |
October | 0.103685E+11 | 0.252667E+10 | 744.00 | 0.103685E+11 | 0.00 | 0.00 | 0.59 | 04-OCT-16:50 | 0.44 | 28-OCT-07:00 | 4698.85 | 03-OCT-16:50 | 4698.85 | 03-OCT-16:50 | 0.00 | 01-OCT-00:10 | 1330.16 | 04-OCT-16:40 | 0.00 |
November | 0.146631E+11 | 0.341388E+10 | 720.00 | 0.146631E+11 | 0.00 | 0.00 | 0.74 | 04-NOV-16:00 | 0.64 | 18-NOV-18:17 | 6157.62 | 12-NOV-15:50 | 6157.62 | 12-NOV-15:50 | 0.00 | 01-NOV-00:10 | 1676.18 | 04-NOV-15:40 | 0.00 |
December | 0.199516E+11 | 0.447249E+10 | 744.00 | 0.199516E+11 | 0.00 | 0.00 | 0.91 | 05-DEC-15:50 | 0.82 | 23-DEC-18:13 | 7980.85 | 05-DEC-15:50 | 7980.85 | 05-DEC-15:50 | 0.00 | 01-DEC-00:10 | 1775.45 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.150852E+12 | 0.370350E+11 | 8760.00 | 0.150852E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.465749E+10 | 0.120869E+10 | 672.00 | 0.465749E+10 | 0.00 | 0.00 | 0.31 | 0.18 | 2376.91 | 2376.91 | 0.00 | 601.56 | 0.00 | ||||||
Maximum of Months | 0.204040E+11 | 0.552950E+10 | 744.00 | 0.204040E+11 | 0.00 | 0.00 | 1.00 | 0.85 | 8423.63 | 8423.63 | 0.00 | 2969.11 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.271649E+11 | 0.731139E+10 | 709.22 | 0.271649E+11 | 0.00 | 0.00 | 0.28 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 20423.07 | 05-JAN-16:20 | 20423.07 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 5214.69 | 05-JAN-16:20 | 0.00 |
February | 0.728070E+11 | 0.180014E+11 | 672.00 | 0.728070E+11 | 0.00 | 0.00 | 0.52 | 27-FEB-16:20 | 0.30 | 19-FEB-08:16 | 40477.33 | 08-FEB-16:50 | 40477.33 | 08-FEB-16:50 | 0.00 | 01-FEB-00:01 | 10792.90 | 27-FEB-16:20 | 0.00 |
March | 0.134523E+12 | 0.316085E+11 | 744.00 | 0.134523E+12 | 0.00 | 0.00 | 0.75 | 14-MAR-17:10 | 0.56 | 05-MAR-07:40 | 59832.26 | 14-MAR-17:10 | 59832.26 | 14-MAR-17:10 | 0.00 | 01-MAR-00:01 | 14951.65 | 18-MAR-17:00 | 0.00 |
April | 0.180149E+12 | 0.418512E+11 | 720.00 | 0.180149E+12 | 0.00 | 0.00 | 1.00 | 26-APR-17:20 | 0.79 | 01-APR-07:00 | 79483.35 | 26-APR-18:20 | 79483.35 | 26-APR-18:20 | 0.00 | 01-APR-00:10 | 25783.55 | 27-APR-16:00 | 0.00 |
May | 0.475763E+11 | 0.125539E+11 | 744.00 | 0.475763E+11 | 0.00 | 0.00 | 0.37 | 07-MAY-18:12 | 0.18 | 18-MAY-06:00 | 27281.63 | 29-MAY-18:24 | 27281.63 | 29-MAY-18:24 | 0.00 | 01-MAY-00:10 | 7807.91 | 14-MAY-18:02 | 0.00 |
June | 0.933970E+11 | 0.239768E+11 | 720.00 | 0.933970E+11 | 0.00 | 0.00 | 0.59 | 22-JUN-18:50 | 0.42 | 14-JUN-07:00 | 43838.91 | 22-JUN-18:50 | 43838.91 | 22-JUN-18:50 | 0.00 | 01-JUN-00:10 | 13674.52 | 28-JUN-17:00 | 0.00 |
July | 0.145997E+12 | 0.383748E+11 | 744.00 | 0.145997E+12 | 0.00 | 0.00 | 0.86 | 30-JUL-18:11 | 0.64 | 01-JUL-11:10 | 64960.28 | 30-JUL-18:37 | 64960.28 | 30-JUL-18:37 | 0.00 | 01-JUL-00:10 | 21628.37 | 24-JUL-15:00 | 0.00 |
August | 0.192146E+12 | 0.522129E+11 | 744.00 | 0.192146E+12 | 0.00 | 0.00 | 1.00 | 06-AUG-17:32 | 0.82 | 19-AUG-07:00 | 79865.20 | 06-AUG-19:14 | 79865.20 | 06-AUG-19:14 | 0.00 | 01-AUG-00:05 | 28367.59 | 10-AUG-17:00 | 0.00 |
September | 0.466675E+11 | 0.124089E+11 | 720.00 | 0.466675E+11 | 0.00 | 0.00 | 0.37 | 08-SEP-17:30 | 0.19 | 28-SEP-07:00 | 26373.75 | 08-SEP-17:30 | 26373.75 | 08-SEP-17:30 | 0.00 | 01-SEP-00:03 | 7965.12 | 08-SEP-17:10 | 0.00 |
October | 0.892143E+11 | 0.219639E+11 | 744.00 | 0.892143E+11 | 0.00 | 0.00 | 0.59 | 04-OCT-16:50 | 0.39 | 29-OCT-07:10 | 44132.61 | 03-OCT-16:50 | 44132.61 | 03-OCT-16:50 | 0.00 | 01-OCT-00:10 | 12515.26 | 04-OCT-16:40 | 0.00 |
November | 0.126611E+12 | 0.298243E+11 | 720.00 | 0.126611E+12 | 0.00 | 0.00 | 0.70 | 04-NOV-16:00 | 0.57 | 26-NOV-05:20 | 56094.36 | 10-NOV-16:10 | 56094.36 | 10-NOV-16:10 | 0.00 | 01-NOV-00:10 | 15234.74 | 04-NOV-15:40 | 0.00 |
December | 0.173900E+12 | 0.394616E+11 | 744.00 | 0.173900E+12 | 0.00 | 0.00 | 0.88 | 05-DEC-16:00 | 0.73 | 26-DEC-04:45 | 73722.69 | 05-DEC-16:00 | 73722.69 | 05-DEC-16:00 | 0.00 | 01-DEC-00:10 | 16479.01 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.133015E+13 | 0.329550E+12 | 8725.22 | 0.133015E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.271649E+11 | 0.731139E+10 | 672.00 | 0.271649E+11 | 0.00 | 0.00 | 0.28 | 0.00 | 20423.07 | 20423.07 | 0.00 | 5214.69 | 0.00 | ||||||
Maximum of Months | 0.192146E+12 | 0.522129E+11 | 744.00 | 0.192146E+12 | 0.00 | 0.00 | 1.00 | 0.82 | 79865.20 | 79865.20 | 0.00 | 28367.59 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.122828E+10 | 0.340871E+09 | 438.49 | 0.122828E+10 | 0.00 | 0.00 | 0.26 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 1901.82 | 05-JAN-16:20 | 1901.82 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 489.19 | 05-JAN-16:20 | 0.00 |
February | 0.568990E+10 | 0.143418E+10 | 666.92 | 0.568990E+10 | 0.00 | 0.00 | 0.51 | 27-FEB-16:20 | 0.00 | 20-FEB-01:15 | 3954.12 | 08-FEB-16:50 | 3954.12 | 08-FEB-16:50 | 0.00 | 01-FEB-00:01 | 1068.56 | 27-FEB-16:20 | 0.00 |
March | 0.122525E+11 | 0.291327E+10 | 744.00 | 0.122525E+11 | 0.00 | 0.00 | 0.74 | 14-MAR-17:10 | 0.39 | 06-MAR-05:01 | 6001.20 | 14-MAR-17:10 | 6001.20 | 14-MAR-17:10 | 0.00 | 01-MAR-00:01 | 1490.01 | 14-MAR-17:00 | 0.00 |
April | 0.172896E+11 | 0.405186E+10 | 720.00 | 0.172896E+11 | 0.00 | 0.00 | 1.00 | 26-APR-17:20 | 0.69 | 09-APR-06:40 | 8046.69 | 26-APR-18:10 | 8046.69 | 26-APR-18:10 | 0.00 | 01-APR-00:10 | 2617.94 | 27-APR-16:00 | 0.00 |
May | 0.428949E+10 | 0.114521E+10 | 744.00 | 0.428949E+10 | 0.00 | 0.00 | 0.38 | 07-MAY-18:12 | 0.10 | 18-MAY-05:30 | 2862.42 | 07-MAY-18:12 | 2862.42 | 07-MAY-18:12 | 0.00 | 01-MAY-00:10 | 822.50 | 14-MAY-18:02 | 0.00 |
June | 0.913066E+10 | 0.235751E+10 | 720.00 | 0.913066E+10 | 0.00 | 0.00 | 0.60 | 22-JUN-18:50 | 0.37 | 14-JUN-06:40 | 4553.73 | 18-JUN-18:34 | 4553.73 | 18-JUN-18:34 | 0.00 | 01-JUN-00:10 | 1403.36 | 28-JUN-17:00 | 0.00 |
July | 0.144797E+11 | 0.382499E+10 | 744.00 | 0.144797E+11 | 0.00 | 0.00 | 0.87 | 30-JUL-18:11 | 0.59 | 02-JUL-05:50 | 6689.71 | 30-JUL-18:29 | 6689.71 | 30-JUL-18:29 | 0.00 | 01-JUL-00:10 | 2214.70 | 24-JUL-15:00 | 0.00 |
August | 0.190516E+11 | 0.520489E+10 | 744.00 | 0.190516E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-17:32 | 0.78 | 19-AUG-07:00 | 8125.42 | 06-AUG-19:12 | 8125.42 | 06-AUG-19:12 | 0.00 | 01-AUG-00:05 | 2887.95 | 10-AUG-17:00 | 0.00 |
September | 0.417364E+10 | 0.112480E+10 | 720.00 | 0.417364E+10 | 0.00 | 0.00 | 0.37 | 08-SEP-17:20 | 0.13 | 27-SEP-06:50 | 2706.92 | 08-SEP-17:30 | 2706.92 | 08-SEP-17:30 | 0.00 | 01-SEP-00:03 | 818.17 | 08-SEP-17:10 | 0.00 |
October | 0.785676E+10 | 0.195976E+10 | 744.00 | 0.785676E+10 | 0.00 | 0.00 | 0.58 | 04-OCT-16:50 | 0.26 | 29-OCT-08:65 | 4441.82 | 04-OCT-16:50 | 4441.82 | 04-OCT-16:50 | 0.00 | 01-OCT-00:10 | 1262.34 | 04-OCT-16:40 | 0.00 |
November | 0.111704E+11 | 0.267114E+10 | 720.00 | 0.111704E+11 | 0.00 | 0.00 | 0.68 | 04-NOV-16:00 | 0.39 | 27-NOV-01:36 | 5508.06 | 10-NOV-16:10 | 5508.06 | 10-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1507.03 | 04-NOV-15:40 | 0.00 |
December | 0.154602E+11 | 0.356611E+10 | 744.00 | 0.154602E+11 | 0.00 | 0.00 | 0.85 | 05-DEC-16:00 | 0.49 | 26-DEC-04:07 | 7214.67 | 05-DEC-16:00 | 7214.67 | 05-DEC-16:00 | 0.00 | 01-DEC-00:10 | 1621.53 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.122073E+12 | 0.305946E+11 | 8449.41 | 0.122073E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.122828E+10 | 0.340871E+09 | 438.49 | 0.122828E+10 | 0.00 | 0.00 | 0.26 | 0.00 | 1901.82 | 1901.82 | 0.00 | 489.19 | 0.00 | ||||||
Maximum of Months | 0.190516E+11 | 0.520489E+10 | 744.00 | 0.190516E+11 | 0.00 | 0.00 | 1.00 | 0.78 | 8125.42 | 8125.42 | 0.00 | 2887.95 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.11 | 527.57 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.02 | 465.30 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 36.82 | 371.54 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.11 | 288.23 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.71 | 180.11 | 221.30 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 206.62 | 167.62 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.14 | 148.92 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.87 | 147.96 | 0.00 | 0.00 | 744.00 |
September | 192.81 | 0.06 | 192.75 | 109.07 | 223.52 | 0.00 | 0.00 | 720.00 |
October | 132.11 | 0.00 | 132.11 | 32.82 | 323.67 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.43 | 433.91 | 0.00 | 0.00 | 720.00 |
December | 62.46 | 0.00 | 62.46 | 0.01 | 537.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.83 | 5.20 | 182.63 | 92.55 | 320.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.46 | 0.00 | 62.46 | 0.01 | 147.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.14 | 537.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.11 | 527.57 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.02 | 465.30 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 36.82 | 371.54 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.11 | 288.23 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.70 | 180.11 | 221.30 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 206.61 | 167.62 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.13 | 148.92 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.87 | 147.96 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.75 | 109.06 | 223.52 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 32.82 | 323.67 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.43 | 433.91 | 0.00 | 0.00 | 720.00 |
December | 62.45 | 0.00 | 62.45 | 0.01 | 537.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.55 | 320.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.45 | 0.00 | 62.45 | 0.01 | 147.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.13 | 537.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.11 | 527.57 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.02 | 465.30 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 36.82 | 371.54 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.11 | 288.23 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.71 | 180.11 | 221.30 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 206.62 | 167.62 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.14 | 148.92 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.87 | 147.96 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.75 | 109.06 | 223.52 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 32.82 | 323.67 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.43 | 433.91 | 0.00 | 0.00 | 720.00 |
December | 62.46 | 0.00 | 62.46 | 0.01 | 537.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.55 | 320.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.46 | 0.00 | 62.46 | 0.01 | 147.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.14 | 537.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.11 | 527.57 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.02 | 465.30 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 36.82 | 371.54 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.11 | 288.23 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.70 | 180.11 | 221.30 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 206.61 | 167.62 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.13 | 148.92 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.87 | 147.96 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.75 | 109.06 | 223.52 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 32.82 | 323.67 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.43 | 433.91 | 0.00 | 0.00 | 720.00 |
December | 62.45 | 0.00 | 62.45 | 0.01 | 537.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.55 | 320.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.45 | 0.00 | 62.45 | 0.01 | 147.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.13 | 537.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.11 | 527.55 | 0.00 | 0.00 | 744.00 |
February | 114.36 | 0.00 | 114.36 | 8.02 | 465.28 | 0.00 | 0.00 | 672.00 |
March | 168.49 | 0.00 | 168.49 | 36.81 | 371.52 | 0.00 | 0.00 | 744.00 |
April | 238.43 | 0.84 | 237.59 | 104.11 | 288.22 | 0.00 | 0.00 | 720.00 |
May | 306.79 | 9.09 | 297.69 | 180.10 | 221.29 | 0.00 | 0.00 | 744.00 |
June | 322.57 | 21.27 | 301.30 | 206.61 | 167.61 | 0.00 | 0.00 | 720.00 |
July | 306.57 | 24.00 | 282.58 | 226.13 | 148.91 | 0.00 | 0.00 | 744.00 |
August | 248.18 | 6.68 | 241.50 | 196.86 | 147.95 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.74 | 109.06 | 223.51 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 32.81 | 323.66 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.43 | 433.90 | 0.00 | 0.00 | 720.00 |
December | 62.45 | 0.00 | 62.45 | 0.01 | 537.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.54 | 320.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.45 | 0.00 | 62.45 | 0.01 | 147.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.57 | 24.00 | 301.30 | 226.13 | 537.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.23 | 33.28 | 97.96 | 24.47 | 535.49 | 0.00 | 0.00 | 744.00 |
February | 240.80 | 85.47 | 155.33 | 102.90 | 455.74 | 0.00 | 0.00 | 672.00 |
March | 359.53 | 130.16 | 229.37 | 224.42 | 368.11 | 0.00 | 0.00 | 744.00 |
April | 557.34 | 231.60 | 325.74 | 459.82 | 284.30 | 0.00 | 0.00 | 720.00 |
May | 592.99 | 206.14 | 386.85 | 512.48 | 232.78 | 0.00 | 0.00 | 744.00 |
June | 710.14 | 308.94 | 401.20 | 676.38 | 178.55 | 0.00 | 0.00 | 720.00 |
July | 661.28 | 296.77 | 364.52 | 659.87 | 149.58 | 0.00 | 0.00 | 744.00 |
August | 650.02 | 325.17 | 324.86 | 686.81 | 142.12 | 0.00 | 0.00 | 744.00 |
September | 480.67 | 221.72 | 258.95 | 439.22 | 224.82 | 0.00 | 0.00 | 720.00 |
October | 313.26 | 133.11 | 180.16 | 217.81 | 322.92 | 0.00 | 0.00 | 744.00 |
November | 153.55 | 43.35 | 110.20 | 48.83 | 431.62 | 0.00 | 0.00 | 720.00 |
December | 125.95 | 40.55 | 85.40 | 32.24 | 534.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 415.49 | 171.73 | 243.76 | 341.67 | 321.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 125.95 | 33.28 | 85.40 | 24.47 | 142.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 710.14 | 325.17 | 401.20 | 686.81 | 535.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.23 | 33.28 | 97.96 | 24.47 | 535.49 | 0.00 | 0.00 | 744.00 |
February | 240.80 | 85.47 | 155.33 | 102.90 | 455.74 | 0.00 | 0.00 | 672.00 |
March | 359.53 | 130.16 | 229.37 | 224.42 | 368.11 | 0.00 | 0.00 | 744.00 |
April | 557.34 | 231.60 | 325.74 | 459.82 | 284.30 | 0.00 | 0.00 | 720.00 |
May | 592.99 | 206.14 | 386.85 | 512.48 | 232.78 | 0.00 | 0.00 | 744.00 |
June | 710.14 | 308.94 | 401.20 | 676.38 | 178.55 | 0.00 | 0.00 | 720.00 |
July | 661.28 | 296.77 | 364.52 | 659.87 | 149.58 | 0.00 | 0.00 | 744.00 |
August | 650.02 | 325.17 | 324.86 | 686.81 | 142.12 | 0.00 | 0.00 | 744.00 |
September | 480.67 | 221.72 | 258.95 | 439.22 | 224.82 | 0.00 | 0.00 | 720.00 |
October | 313.26 | 133.11 | 180.16 | 217.81 | 322.92 | 0.00 | 0.00 | 744.00 |
November | 153.55 | 43.35 | 110.20 | 48.83 | 431.62 | 0.00 | 0.00 | 720.00 |
December | 125.95 | 40.55 | 85.40 | 32.24 | 534.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 415.49 | 171.73 | 243.76 | 341.67 | 321.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 125.95 | 33.28 | 85.40 | 24.47 | 142.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 710.14 | 325.17 | 401.20 | 686.81 | 535.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.23 | 33.28 | 97.96 | 24.47 | 535.48 | 0.00 | 0.00 | 744.00 |
February | 240.79 | 85.47 | 155.33 | 102.89 | 455.73 | 0.00 | 0.00 | 672.00 |
March | 359.52 | 130.15 | 229.36 | 224.41 | 368.11 | 0.00 | 0.00 | 744.00 |
April | 557.33 | 231.60 | 325.74 | 459.81 | 284.30 | 0.00 | 0.00 | 720.00 |
May | 592.98 | 206.14 | 386.84 | 512.47 | 232.77 | 0.00 | 0.00 | 744.00 |
June | 710.12 | 308.93 | 401.19 | 676.37 | 178.55 | 0.00 | 0.00 | 720.00 |
July | 661.27 | 296.76 | 364.51 | 659.86 | 149.58 | 0.00 | 0.00 | 744.00 |
August | 650.01 | 325.16 | 324.85 | 686.80 | 142.12 | 0.00 | 0.00 | 744.00 |
September | 480.66 | 221.71 | 258.95 | 439.22 | 224.81 | 0.00 | 0.00 | 720.00 |
October | 313.26 | 133.10 | 180.15 | 217.81 | 322.91 | 0.00 | 0.00 | 744.00 |
November | 153.55 | 43.35 | 110.20 | 48.83 | 431.61 | 0.00 | 0.00 | 720.00 |
December | 125.95 | 40.55 | 85.40 | 32.24 | 534.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 415.49 | 171.73 | 243.76 | 341.66 | 321.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 125.95 | 33.28 | 85.40 | 24.47 | 142.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 710.12 | 325.16 | 401.19 | 686.80 | 535.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.64 | 192.73 | 131.91 | 254.42 | 432.77 | 0.00 | 0.00 | 744.00 |
February | 499.42 | 309.15 | 190.27 | 438.40 | 389.42 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 469.76 | 341.76 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 469.51 | 279.70 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 391.88 | 225.29 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.33 | 347.10 | 344.74 | 177.20 | 0.00 | 0.00 | 720.00 |
July | 517.37 | 189.43 | 327.94 | 421.19 | 155.87 | 0.00 | 0.00 | 744.00 |
August | 555.90 | 259.20 | 296.70 | 522.41 | 148.93 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.35 | 275.81 | 599.79 | 215.74 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 540.59 | 296.79 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.25 | 368.74 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.23 | 450.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 418.91 | 289.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.64 | 127.33 | 121.79 | 254.42 | 148.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 599.79 | 450.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.63 | 192.73 | 131.91 | 254.42 | 432.77 | 0.00 | 0.00 | 744.00 |
February | 499.41 | 309.15 | 190.26 | 438.39 | 389.42 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 469.76 | 341.76 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 469.50 | 279.70 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 391.88 | 225.29 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.32 | 347.10 | 344.73 | 177.20 | 0.00 | 0.00 | 720.00 |
July | 517.36 | 189.43 | 327.94 | 421.19 | 155.87 | 0.00 | 0.00 | 744.00 |
August | 555.89 | 259.20 | 296.70 | 522.40 | 148.93 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.34 | 275.81 | 599.79 | 215.74 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 540.58 | 296.79 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.24 | 368.74 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.23 | 450.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 418.90 | 289.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.63 | 127.32 | 121.79 | 254.42 | 148.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 599.79 | 450.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.64 | 192.73 | 131.91 | 254.42 | 432.77 | 0.00 | 0.00 | 744.00 |
February | 499.42 | 309.15 | 190.27 | 438.40 | 389.42 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 469.76 | 341.76 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 469.51 | 279.70 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 391.88 | 225.29 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.33 | 347.10 | 344.74 | 177.20 | 0.00 | 0.00 | 720.00 |
July | 517.37 | 189.43 | 327.94 | 421.19 | 155.87 | 0.00 | 0.00 | 744.00 |
August | 555.90 | 259.20 | 296.70 | 522.41 | 148.93 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.35 | 275.81 | 599.79 | 215.74 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 540.59 | 296.79 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.25 | 368.74 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.23 | 450.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 418.91 | 289.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.64 | 127.33 | 121.79 | 254.42 | 148.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 599.79 | 450.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.63 | 192.73 | 131.91 | 254.42 | 432.77 | 0.00 | 0.00 | 744.00 |
February | 499.41 | 309.15 | 190.26 | 438.39 | 389.42 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 469.76 | 341.76 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 469.50 | 279.70 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 391.88 | 225.29 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.32 | 347.10 | 344.73 | 177.20 | 0.00 | 0.00 | 720.00 |
July | 517.36 | 189.43 | 327.94 | 421.19 | 155.87 | 0.00 | 0.00 | 744.00 |
August | 555.89 | 259.20 | 296.70 | 522.40 | 148.93 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.34 | 275.81 | 599.79 | 215.74 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 540.58 | 296.79 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.24 | 368.74 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.23 | 450.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 418.90 | 289.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.63 | 127.32 | 121.79 | 254.42 | 148.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 599.79 | 450.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.62 | 192.72 | 131.90 | 254.41 | 432.75 | 0.00 | 0.00 | 744.00 |
February | 499.40 | 309.14 | 190.26 | 438.38 | 389.40 | 0.00 | 0.00 | 672.00 |
March | 537.40 | 286.69 | 250.71 | 469.74 | 341.75 | 0.00 | 0.00 | 744.00 |
April | 567.22 | 246.31 | 320.91 | 469.49 | 279.69 | 0.00 | 0.00 | 720.00 |
May | 518.53 | 154.42 | 364.11 | 391.86 | 225.28 | 0.00 | 0.00 | 744.00 |
June | 474.40 | 127.32 | 347.08 | 344.72 | 177.19 | 0.00 | 0.00 | 720.00 |
July | 517.34 | 189.42 | 327.92 | 421.17 | 155.86 | 0.00 | 0.00 | 744.00 |
August | 555.87 | 259.19 | 296.68 | 522.38 | 148.93 | 0.00 | 0.00 | 744.00 |
September | 616.13 | 340.33 | 275.79 | 599.76 | 215.73 | 0.00 | 0.00 | 720.00 |
October | 558.08 | 344.63 | 213.45 | 540.56 | 296.78 | 0.00 | 0.00 | 744.00 |
November | 329.80 | 188.97 | 140.83 | 273.23 | 368.72 | 0.00 | 0.00 | 720.00 |
December | 345.02 | 223.23 | 121.78 | 303.22 | 450.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.77 | 238.09 | 248.68 | 418.89 | 289.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.62 | 127.32 | 121.78 | 254.41 | 148.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.13 | 344.63 | 364.11 | 599.76 | 450.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.42 | 40.83 | 97.60 | 32.60 | 566.87 | 0.00 | 0.00 | 744.00 |
February | 248.18 | 93.28 | 154.90 | 114.30 | 508.35 | 0.00 | 0.00 | 672.00 |
March | 347.75 | 117.38 | 230.37 | 208.99 | 429.83 | 0.00 | 0.00 | 744.00 |
April | 529.07 | 202.30 | 326.78 | 411.94 | 350.34 | 0.00 | 0.00 | 720.00 |
May | 680.69 | 276.48 | 404.21 | 617.63 | 264.47 | 0.00 | 0.00 | 744.00 |
June | 654.62 | 254.11 | 400.51 | 600.63 | 215.07 | 0.00 | 0.00 | 720.00 |
July | 808.67 | 425.01 | 383.66 | 840.23 | 197.39 | 0.00 | 0.00 | 744.00 |
August | 669.05 | 341.62 | 327.43 | 701.43 | 195.48 | 0.00 | 0.00 | 744.00 |
September | 544.89 | 261.46 | 283.42 | 519.62 | 259.25 | 0.00 | 0.00 | 720.00 |
October | 310.19 | 126.39 | 183.80 | 213.36 | 373.12 | 0.00 | 0.00 | 744.00 |
November | 154.48 | 43.58 | 110.91 | 49.96 | 496.38 | 0.00 | 0.00 | 720.00 |
December | 129.88 | 44.51 | 85.36 | 39.44 | 622.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 435.79 | 186.28 | 249.51 | 364.19 | 372.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.88 | 40.83 | 85.36 | 32.60 | 195.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 808.67 | 425.01 | 404.21 | 840.23 | 622.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.42 | 40.83 | 97.60 | 32.60 | 566.87 | 0.00 | 0.00 | 744.00 |
February | 248.18 | 93.28 | 154.90 | 114.30 | 508.35 | 0.00 | 0.00 | 672.00 |
March | 347.75 | 117.38 | 230.37 | 208.99 | 429.83 | 0.00 | 0.00 | 744.00 |
April | 529.07 | 202.30 | 326.78 | 411.94 | 350.34 | 0.00 | 0.00 | 720.00 |
May | 680.69 | 276.48 | 404.21 | 617.63 | 264.47 | 0.00 | 0.00 | 744.00 |
June | 654.62 | 254.11 | 400.51 | 600.63 | 215.07 | 0.00 | 0.00 | 720.00 |
July | 808.67 | 425.01 | 383.66 | 840.23 | 197.39 | 0.00 | 0.00 | 744.00 |
August | 669.05 | 341.62 | 327.43 | 701.43 | 195.48 | 0.00 | 0.00 | 744.00 |
September | 544.89 | 261.46 | 283.42 | 519.62 | 259.25 | 0.00 | 0.00 | 720.00 |
October | 310.19 | 126.39 | 183.80 | 213.36 | 373.12 | 0.00 | 0.00 | 744.00 |
November | 154.48 | 43.58 | 110.91 | 49.96 | 496.38 | 0.00 | 0.00 | 720.00 |
December | 129.88 | 44.51 | 85.36 | 39.44 | 622.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 435.79 | 186.28 | 249.51 | 364.19 | 372.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.88 | 40.83 | 85.36 | 32.60 | 195.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 808.67 | 425.01 | 404.21 | 840.23 | 622.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.42 | 40.82 | 97.60 | 32.60 | 566.86 | 0.00 | 0.00 | 744.00 |
February | 248.17 | 93.28 | 154.89 | 114.30 | 508.35 | 0.00 | 0.00 | 672.00 |
March | 347.74 | 117.38 | 230.37 | 208.98 | 429.82 | 0.00 | 0.00 | 744.00 |
April | 529.06 | 202.30 | 326.77 | 411.93 | 350.34 | 0.00 | 0.00 | 720.00 |
May | 680.67 | 276.47 | 404.20 | 617.62 | 264.46 | 0.00 | 0.00 | 744.00 |
June | 654.60 | 254.10 | 400.50 | 600.62 | 215.06 | 0.00 | 0.00 | 720.00 |
July | 808.65 | 425.00 | 383.65 | 840.22 | 197.38 | 0.00 | 0.00 | 744.00 |
August | 669.04 | 341.62 | 327.42 | 701.41 | 195.48 | 0.00 | 0.00 | 744.00 |
September | 544.88 | 261.46 | 283.42 | 519.61 | 259.24 | 0.00 | 0.00 | 720.00 |
October | 310.18 | 126.38 | 183.80 | 213.36 | 373.11 | 0.00 | 0.00 | 744.00 |
November | 154.48 | 43.58 | 110.90 | 49.96 | 496.38 | 0.00 | 0.00 | 720.00 |
December | 129.87 | 44.51 | 85.36 | 39.44 | 622.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 435.79 | 186.28 | 249.50 | 364.18 | 372.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.87 | 40.82 | 85.36 | 32.60 | 195.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 808.65 | 425.00 | 404.20 | 840.22 | 622.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 367.50 | 0.00 | 367.50 | 1.96 | 2321.76 | 0.00 | 0.00 | 744.00 |
February | 571.84 | 0.00 | 571.84 | 54.97 | 2067.63 | 0.00 | 0.00 | 672.00 |
March | 842.52 | 0.00 | 842.52 | 210.36 | 1684.29 | 0.00 | 0.00 | 744.00 |
April | 1192.20 | 4.19 | 1188.02 | 557.40 | 1315.16 | 0.00 | 0.00 | 720.00 |
May | 1534.01 | 45.47 | 1488.54 | 922.99 | 1043.49 | 0.00 | 0.00 | 744.00 |
June | 1612.92 | 106.35 | 1506.57 | 1057.61 | 789.52 | 0.00 | 0.00 | 720.00 |
July | 1532.95 | 120.00 | 1412.95 | 1159.29 | 703.28 | 0.00 | 0.00 | 744.00 |
August | 1240.96 | 33.41 | 1207.55 | 1012.53 | 697.69 | 0.00 | 0.00 | 744.00 |
September | 964.03 | 0.28 | 963.76 | 563.32 | 1051.78 | 0.00 | 0.00 | 720.00 |
October | 660.53 | 0.00 | 660.53 | 188.07 | 1468.49 | 0.00 | 0.00 | 744.00 |
November | 416.07 | 0.00 | 416.07 | 24.72 | 1913.92 | 0.00 | 0.00 | 720.00 |
December | 312.28 | 0.00 | 312.28 | 0.83 | 2339.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 939.13 | 26.00 | 913.13 | 482.21 | 1446.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 312.28 | 0.00 | 312.28 | 0.83 | 697.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1612.92 | 120.00 | 1506.57 | 1159.29 | 2339.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 393.70 | 99.83 | 293.87 | 81.16 | 1447.61 | 0.00 | 0.00 | 744.00 |
February | 722.38 | 256.40 | 465.98 | 330.60 | 1254.52 | 0.00 | 0.00 | 672.00 |
March | 1078.57 | 390.47 | 688.10 | 692.30 | 1025.38 | 0.00 | 0.00 | 744.00 |
April | 1672.01 | 694.79 | 977.21 | 1389.77 | 809.09 | 0.00 | 0.00 | 720.00 |
May | 1778.95 | 618.42 | 1160.53 | 1547.65 | 662.60 | 0.00 | 0.00 | 744.00 |
June | 2130.39 | 926.80 | 1203.59 | 2027.46 | 514.66 | 0.00 | 0.00 | 720.00 |
July | 1983.83 | 890.29 | 1093.53 | 1977.38 | 441.72 | 0.00 | 0.00 | 744.00 |
August | 1950.04 | 975.49 | 974.56 | 2056.45 | 429.22 | 0.00 | 0.00 | 744.00 |
September | 1441.99 | 665.15 | 776.84 | 1326.39 | 638.08 | 0.00 | 0.00 | 720.00 |
October | 939.78 | 399.32 | 540.46 | 670.94 | 894.22 | 0.00 | 0.00 | 744.00 |
November | 460.64 | 130.05 | 330.59 | 159.54 | 1176.03 | 0.00 | 0.00 | 720.00 |
December | 377.84 | 121.65 | 256.19 | 105.39 | 1457.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1246.47 | 515.19 | 731.28 | 1034.03 | 894.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 377.84 | 99.83 | 256.19 | 81.16 | 429.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2130.39 | 975.49 | 1203.59 | 2056.45 | 1457.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1623.21 | 963.66 | 659.55 | 1277.37 | 2068.71 | 0.00 | 0.00 | 744.00 |
February | 2497.13 | 1545.79 | 951.34 | 2196.80 | 1877.01 | 0.00 | 0.00 | 672.00 |
March | 2687.17 | 1433.54 | 1253.63 | 2349.32 | 1639.19 | 0.00 | 0.00 | 744.00 |
April | 2836.25 | 1231.61 | 1604.63 | 2355.09 | 1342.86 | 0.00 | 0.00 | 720.00 |
May | 2592.81 | 772.17 | 1820.64 | 1966.65 | 1091.16 | 0.00 | 0.00 | 744.00 |
June | 2372.15 | 636.64 | 1735.51 | 1740.83 | 848.91 | 0.00 | 0.00 | 720.00 |
July | 2586.86 | 947.16 | 1639.70 | 2122.29 | 755.97 | 0.00 | 0.00 | 744.00 |
August | 2779.53 | 1296.03 | 1483.50 | 2623.01 | 731.63 | 0.00 | 0.00 | 744.00 |
September | 3080.82 | 1701.77 | 1379.05 | 2995.01 | 1054.57 | 0.00 | 0.00 | 720.00 |
October | 2790.56 | 1723.25 | 1067.31 | 2696.49 | 1432.63 | 0.00 | 0.00 | 744.00 |
November | 1649.10 | 944.93 | 704.17 | 1376.66 | 1749.08 | 0.00 | 0.00 | 720.00 |
December | 1725.20 | 1116.24 | 608.96 | 1526.34 | 2128.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2434.01 | 1190.53 | 1243.48 | 2101.22 | 1390.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1623.21 | 636.64 | 608.96 | 1277.37 | 731.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3080.82 | 1723.25 | 1820.64 | 2995.01 | 2128.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.27 | 122.47 | 292.79 | 107.78 | 1482.23 | 0.00 | 0.00 | 744.00 |
February | 744.52 | 279.83 | 464.69 | 376.31 | 1299.74 | 0.00 | 0.00 | 672.00 |
March | 1043.24 | 352.14 | 691.10 | 675.22 | 1080.35 | 0.00 | 0.00 | 744.00 |
April | 1587.21 | 606.89 | 980.32 | 1301.96 | 882.94 | 0.00 | 0.00 | 720.00 |
May | 2042.04 | 829.43 | 1212.61 | 1882.35 | 727.66 | 0.00 | 0.00 | 744.00 |
June | 1963.83 | 762.31 | 1201.51 | 1847.49 | 569.06 | 0.00 | 0.00 | 720.00 |
July | 2425.98 | 1275.02 | 1150.96 | 2563.31 | 527.03 | 0.00 | 0.00 | 744.00 |
August | 2007.13 | 1024.86 | 982.27 | 2161.43 | 505.40 | 0.00 | 0.00 | 744.00 |
September | 1634.64 | 784.37 | 850.27 | 1586.79 | 705.40 | 0.00 | 0.00 | 720.00 |
October | 930.56 | 379.15 | 551.40 | 680.08 | 950.33 | 0.00 | 0.00 | 744.00 |
November | 463.44 | 130.73 | 332.71 | 173.97 | 1208.26 | 0.00 | 0.00 | 720.00 |
December | 389.63 | 133.54 | 256.09 | 136.65 | 1504.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1307.37 | 558.85 | 748.52 | 1129.46 | 951.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 389.63 | 122.47 | 256.09 | 107.78 | 505.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2425.98 | 1275.02 | 1212.61 | 2563.31 | 1504.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 367.50 | 0.00 | 367.50 | 6.62 | 2070.52 | 0.00 | 0.00 | 744.00 |
February | 571.84 | 0.00 | 571.84 | 74.69 | 1842.04 | 0.00 | 0.00 | 672.00 |
March | 842.52 | 0.00 | 842.52 | 247.56 | 1516.97 | 0.00 | 0.00 | 744.00 |
April | 1192.20 | 4.19 | 1188.02 | 590.98 | 1216.22 | 0.00 | 0.00 | 720.00 |
May | 1534.01 | 45.47 | 1488.54 | 941.11 | 984.53 | 0.00 | 0.00 | 744.00 |
June | 1612.92 | 106.35 | 1506.57 | 1061.97 | 760.93 | 0.00 | 0.00 | 720.00 |
July | 1532.95 | 120.00 | 1412.95 | 1157.71 | 682.84 | 0.00 | 0.00 | 744.00 |
August | 1240.96 | 33.41 | 1207.55 | 1014.53 | 670.15 | 0.00 | 0.00 | 744.00 |
September | 964.03 | 0.28 | 963.76 | 580.42 | 981.22 | 0.00 | 0.00 | 720.00 |
October | 660.53 | 0.00 | 660.53 | 222.79 | 1313.29 | 0.00 | 0.00 | 744.00 |
November | 416.07 | 0.00 | 416.07 | 36.53 | 1678.61 | 0.00 | 0.00 | 720.00 |
December | 312.28 | 0.00 | 312.28 | 3.96 | 2073.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 939.13 | 26.00 | 913.13 | 497.57 | 1313.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 312.28 | 0.00 | 312.28 | 3.96 | 670.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1612.92 | 120.00 | 1506.57 | 1157.71 | 2073.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 393.70 | 99.83 | 293.87 | 90.77 | 1312.73 | 0.00 | 0.00 | 744.00 |
February | 722.38 | 256.40 | 465.98 | 355.91 | 1144.67 | 0.00 | 0.00 | 672.00 |
March | 1078.57 | 390.47 | 688.10 | 716.27 | 946.67 | 0.00 | 0.00 | 744.00 |
April | 1672.01 | 694.79 | 977.21 | 1407.03 | 763.35 | 0.00 | 0.00 | 720.00 |
May | 1778.95 | 618.42 | 1160.53 | 1554.35 | 637.34 | 0.00 | 0.00 | 744.00 |
June | 2130.39 | 926.80 | 1203.59 | 2022.71 | 504.12 | 0.00 | 0.00 | 720.00 |
July | 1983.83 | 890.29 | 1093.53 | 1970.35 | 437.15 | 0.00 | 0.00 | 744.00 |
August | 1950.04 | 975.49 | 974.56 | 2052.35 | 421.58 | 0.00 | 0.00 | 744.00 |
September | 1441.99 | 665.15 | 776.84 | 1333.52 | 609.02 | 0.00 | 0.00 | 720.00 |
October | 939.78 | 399.32 | 540.46 | 693.19 | 823.43 | 0.00 | 0.00 | 744.00 |
November | 460.64 | 130.05 | 330.59 | 173.38 | 1062.86 | 0.00 | 0.00 | 720.00 |
December | 377.84 | 121.65 | 256.19 | 116.39 | 1317.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1246.47 | 515.19 | 731.28 | 1044.02 | 830.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 377.84 | 99.83 | 256.19 | 90.77 | 421.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2130.39 | 975.49 | 1203.59 | 2052.35 | 1317.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1623.21 | 963.66 | 659.55 | 1319.13 | 1866.28 | 0.00 | 0.00 | 744.00 |
February | 2497.13 | 1545.79 | 951.34 | 2248.81 | 1708.48 | 0.00 | 0.00 | 672.00 |
March | 2687.17 | 1433.54 | 1253.63 | 2380.75 | 1505.72 | 0.00 | 0.00 | 744.00 |
April | 2836.25 | 1231.61 | 1604.63 | 2382.97 | 1259.76 | 0.00 | 0.00 | 720.00 |
May | 2592.81 | 772.17 | 1820.64 | 1984.54 | 1038.69 | 0.00 | 0.00 | 744.00 |
June | 2372.15 | 636.64 | 1735.51 | 1746.78 | 821.47 | 0.00 | 0.00 | 720.00 |
July | 2586.86 | 947.16 | 1639.70 | 2123.19 | 738.68 | 0.00 | 0.00 | 744.00 |
August | 2779.53 | 1296.03 | 1483.50 | 2627.29 | 708.29 | 0.00 | 0.00 | 744.00 |
September | 3080.82 | 1701.77 | 1379.05 | 3010.77 | 996.38 | 0.00 | 0.00 | 720.00 |
October | 2790.56 | 1723.25 | 1067.31 | 2728.63 | 1313.12 | 0.00 | 0.00 | 744.00 |
November | 1649.10 | 944.93 | 704.17 | 1414.89 | 1579.35 | 0.00 | 0.00 | 720.00 |
December | 1725.20 | 1116.24 | 608.96 | 1564.43 | 1921.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2434.01 | 1190.53 | 1243.48 | 2126.56 | 1286.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1623.21 | 636.64 | 608.96 | 1319.13 | 708.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3080.82 | 1723.25 | 1820.64 | 3010.77 | 1921.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.27 | 122.47 | 292.79 | 114.37 | 1355.95 | 0.00 | 0.00 | 744.00 |
February | 744.52 | 279.83 | 464.69 | 392.79 | 1200.35 | 0.00 | 0.00 | 672.00 |
March | 1043.24 | 352.14 | 691.10 | 691.69 | 1003.39 | 0.00 | 0.00 | 744.00 |
April | 1587.21 | 606.89 | 980.32 | 1316.16 | 834.18 | 0.00 | 0.00 | 720.00 |
May | 2042.04 | 829.43 | 1212.61 | 1889.25 | 696.24 | 0.00 | 0.00 | 744.00 |
June | 1963.83 | 762.31 | 1201.51 | 1847.43 | 551.19 | 0.00 | 0.00 | 720.00 |
July | 2425.98 | 1275.02 | 1150.96 | 2559.42 | 514.60 | 0.00 | 0.00 | 744.00 |
August | 2007.13 | 1024.86 | 982.27 | 2161.98 | 490.05 | 0.00 | 0.00 | 744.00 |
September | 1634.64 | 784.37 | 850.27 | 1595.07 | 670.75 | 0.00 | 0.00 | 720.00 |
October | 930.56 | 379.15 | 551.40 | 696.29 | 880.59 | 0.00 | 0.00 | 744.00 |
November | 463.44 | 130.73 | 332.71 | 183.93 | 1108.84 | 0.00 | 0.00 | 720.00 |
December | 389.63 | 133.54 | 256.09 | 143.73 | 1383.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1307.37 | 558.85 | 748.52 | 1137.63 | 889.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 389.63 | 122.47 | 256.09 | 114.37 | 490.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2425.98 | 1275.02 | 1212.61 | 2559.42 | 1383.73 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196862E+09 | 0.00 | 0.196862E+09 | 289568.19 | 0.141304E+10 |
February | 0.276679E+09 | 0.00 | 0.276679E+09 | 19410661.95 | 0.112566E+10 |
March | 0.451319E+09 | 0.00 | 0.451319E+09 | 98612617.81 | 0.995129E+09 |
April | 0.618038E+09 | 2170238.44 | 0.615868E+09 | 0.269863E+09 | 0.747092E+09 |
May | 0.821739E+09 | 24355703.09 | 0.797384E+09 | 0.482413E+09 | 0.592719E+09 |
June | 0.836139E+09 | 55132976.26 | 0.781006E+09 | 0.535557E+09 | 0.434473E+09 |
July | 0.821170E+09 | 64281622.84 | 0.756889E+09 | 0.605687E+09 | 0.398864E+09 |
August | 0.664759E+09 | 17898763.80 | 0.646860E+09 | 0.527297E+09 | 0.396289E+09 |
September | 0.499754E+09 | 142594.85 | 0.499612E+09 | 0.282697E+09 | 0.579354E+09 |
October | 0.353832E+09 | 0.00 | 0.353832E+09 | 87895115.11 | 0.866920E+09 |
November | 0.215689E+09 | 0.00 | 0.215689E+09 | 8888387.83 | 0.112471E+10 |
December | 0.167282E+09 | 0.00 | 0.167282E+09 | 19754.89 | 0.144070E+10 |
Annual Sum or Average | 0.592326E+10 | 0.163982E+09 | 0.575928E+10 | 0.291863E+10 | 0.101149E+11 |
Minimum of Months | 0.167282E+09 | 0.00 | 0.167282E+09 | 19754.89 | 0.396289E+09 |
Maximum of Months | 0.836139E+09 | 64281622.84 | 0.797384E+09 | 0.605687E+09 | 0.144070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+09 | 0.00 | 0.196859E+09 | 289478.58 | 0.141304E+10 |
February | 0.276674E+09 | 0.00 | 0.276674E+09 | 19409615.51 | 0.112566E+10 |
March | 0.451312E+09 | 0.00 | 0.451312E+09 | 98608333.22 | 0.995130E+09 |
April | 0.618029E+09 | 2170190.73 | 0.615859E+09 | 0.269856E+09 | 0.747093E+09 |
May | 0.821727E+09 | 24355167.66 | 0.797372E+09 | 0.482402E+09 | 0.592720E+09 |
June | 0.836126E+09 | 55131764.23 | 0.780995E+09 | 0.535546E+09 | 0.434473E+09 |
July | 0.821159E+09 | 64280209.68 | 0.756879E+09 | 0.605677E+09 | 0.398863E+09 |
August | 0.664750E+09 | 17898370.31 | 0.646851E+09 | 0.527289E+09 | 0.396288E+09 |
September | 0.499747E+09 | 142591.72 | 0.499605E+09 | 0.282691E+09 | 0.579353E+09 |
October | 0.353827E+09 | 0.00 | 0.353827E+09 | 87891763.66 | 0.866920E+09 |
November | 0.215686E+09 | 0.00 | 0.215686E+09 | 8887839.15 | 0.112471E+10 |
December | 0.167279E+09 | 0.00 | 0.167279E+09 | 19745.30 | 0.144070E+10 |
Annual Sum or Average | 0.592318E+10 | 0.163978E+09 | 0.575920E+10 | 0.291857E+10 | 0.101149E+11 |
Minimum of Months | 0.167279E+09 | 0.00 | 0.167279E+09 | 19745.30 | 0.396288E+09 |
Maximum of Months | 0.836126E+09 | 64280209.68 | 0.797372E+09 | 0.605677E+09 | 0.144070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196860E+09 | 0.00 | 0.196860E+09 | 289508.45 | 0.141304E+10 |
February | 0.276676E+09 | 0.00 | 0.276676E+09 | 19409964.32 | 0.112566E+10 |
March | 0.451314E+09 | 0.00 | 0.451314E+09 | 98609761.41 | 0.995130E+09 |
April | 0.618032E+09 | 2170206.63 | 0.615862E+09 | 0.269858E+09 | 0.747093E+09 |
May | 0.821731E+09 | 24355346.14 | 0.797376E+09 | 0.482406E+09 | 0.592719E+09 |
June | 0.836130E+09 | 55132168.24 | 0.780998E+09 | 0.535550E+09 | 0.434473E+09 |
July | 0.821163E+09 | 64280680.74 | 0.756882E+09 | 0.605681E+09 | 0.398864E+09 |
August | 0.664753E+09 | 17898501.47 | 0.646854E+09 | 0.527291E+09 | 0.396289E+09 |
September | 0.499750E+09 | 142592.76 | 0.499607E+09 | 0.282693E+09 | 0.579353E+09 |
October | 0.353828E+09 | 0.00 | 0.353828E+09 | 87892880.81 | 0.866920E+09 |
November | 0.215687E+09 | 0.00 | 0.215687E+09 | 8888022.05 | 0.112471E+10 |
December | 0.167280E+09 | 0.00 | 0.167280E+09 | 19748.49 | 0.144070E+10 |
Annual Sum or Average | 0.592321E+10 | 0.163979E+09 | 0.575923E+10 | 0.291859E+10 | 0.101149E+11 |
Minimum of Months | 0.167280E+09 | 0.00 | 0.167280E+09 | 19748.49 | 0.396289E+09 |
Maximum of Months | 0.836130E+09 | 64280680.74 | 0.797376E+09 | 0.605681E+09 | 0.144070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+09 | 0.00 | 0.196859E+09 | 289478.58 | 0.141304E+10 |
February | 0.276674E+09 | 0.00 | 0.276674E+09 | 19409615.51 | 0.112566E+10 |
March | 0.451312E+09 | 0.00 | 0.451312E+09 | 98608333.22 | 0.995130E+09 |
April | 0.618029E+09 | 2170190.73 | 0.615859E+09 | 0.269856E+09 | 0.747093E+09 |
May | 0.821727E+09 | 24355167.66 | 0.797372E+09 | 0.482402E+09 | 0.592720E+09 |
June | 0.836126E+09 | 55131764.23 | 0.780995E+09 | 0.535546E+09 | 0.434473E+09 |
July | 0.821159E+09 | 64280209.68 | 0.756879E+09 | 0.605677E+09 | 0.398863E+09 |
August | 0.664750E+09 | 17898370.31 | 0.646851E+09 | 0.527289E+09 | 0.396288E+09 |
September | 0.499747E+09 | 142591.72 | 0.499605E+09 | 0.282691E+09 | 0.579353E+09 |
October | 0.353827E+09 | 0.00 | 0.353827E+09 | 87891763.66 | 0.866920E+09 |
November | 0.215686E+09 | 0.00 | 0.215686E+09 | 8887839.15 | 0.112471E+10 |
December | 0.167279E+09 | 0.00 | 0.167279E+09 | 19745.30 | 0.144070E+10 |
Annual Sum or Average | 0.592318E+10 | 0.163978E+09 | 0.575920E+10 | 0.291857E+10 | 0.101149E+11 |
Minimum of Months | 0.167279E+09 | 0.00 | 0.167279E+09 | 19745.30 | 0.396288E+09 |
Maximum of Months | 0.836126E+09 | 64280209.68 | 0.797372E+09 | 0.605677E+09 | 0.144070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196852E+09 | 0.00 | 0.196852E+09 | 289481.84 | 0.141298E+10 |
February | 0.276664E+09 | 0.00 | 0.276664E+09 | 19409007.61 | 0.112561E+10 |
March | 0.451295E+09 | 0.00 | 0.451295E+09 | 98605072.94 | 0.995090E+09 |
April | 0.618006E+09 | 2170111.21 | 0.615836E+09 | 0.269846E+09 | 0.747063E+09 |
May | 0.821696E+09 | 24354275.27 | 0.797342E+09 | 0.482384E+09 | 0.592696E+09 |
June | 0.836095E+09 | 55129744.18 | 0.780965E+09 | 0.535526E+09 | 0.434455E+09 |
July | 0.821128E+09 | 64277854.42 | 0.756850E+09 | 0.605654E+09 | 0.398847E+09 |
August | 0.664724E+09 | 17897714.51 | 0.646827E+09 | 0.527269E+09 | 0.396272E+09 |
September | 0.499728E+09 | 142586.49 | 0.499586E+09 | 0.282681E+09 | 0.579330E+09 |
October | 0.353813E+09 | 0.00 | 0.353813E+09 | 87888779.79 | 0.866885E+09 |
November | 0.215678E+09 | 0.00 | 0.215678E+09 | 8887572.38 | 0.112466E+10 |
December | 0.167273E+09 | 0.00 | 0.167273E+09 | 19746.10 | 0.144064E+10 |
Annual Sum or Average | 0.592295E+10 | 0.163972E+09 | 0.575898E+10 | 0.291846E+10 | 0.101145E+11 |
Minimum of Months | 0.167273E+09 | 0.00 | 0.167273E+09 | 19746.10 | 0.396272E+09 |
Maximum of Months | 0.836095E+09 | 64277854.42 | 0.797342E+09 | 0.605654E+09 | 0.144064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351499E+09 | 89130193.07 | 0.262369E+09 | 65529803.71 | 0.143426E+10 |
February | 0.582536E+09 | 0.206765E+09 | 0.375772E+09 | 0.248925E+09 | 0.110253E+10 |
March | 0.962954E+09 | 0.348612E+09 | 0.614342E+09 | 0.601080E+09 | 0.985950E+09 |
April | 0.144463E+10 | 0.600307E+09 | 0.844322E+09 | 0.119186E+10 | 0.736915E+09 |
May | 0.158826E+10 | 0.552131E+09 | 0.103613E+10 | 0.137262E+10 | 0.623471E+09 |
June | 0.184067E+10 | 0.800765E+09 | 0.103991E+10 | 0.175318E+10 | 0.462808E+09 |
July | 0.177118E+10 | 0.794862E+09 | 0.976318E+09 | 0.176740E+10 | 0.400638E+09 |
August | 0.174102E+10 | 0.870925E+09 | 0.870093E+09 | 0.183955E+10 | 0.380658E+09 |
September | 0.124589E+10 | 0.574696E+09 | 0.671199E+09 | 0.113847E+10 | 0.582727E+09 |
October | 0.839042E+09 | 0.356513E+09 | 0.482529E+09 | 0.583381E+09 | 0.864897E+09 |
November | 0.397999E+09 | 0.112368E+09 | 0.285631E+09 | 0.126561E+09 | 0.111877E+10 |
December | 0.337341E+09 | 0.108614E+09 | 0.228727E+09 | 86355892.24 | 0.143128E+10 |
Annual Sum or Average | 0.131030E+11 | 0.541569E+10 | 0.768734E+10 | 0.107749E+11 | 0.101249E+11 |
Minimum of Months | 0.337341E+09 | 89130193.07 | 0.228727E+09 | 65529803.71 | 0.380658E+09 |
Maximum of Months | 0.184067E+10 | 0.870925E+09 | 0.103991E+10 | 0.183955E+10 | 0.143426E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351499E+09 | 89130193.07 | 0.262369E+09 | 65529803.71 | 0.143426E+10 |
February | 0.582536E+09 | 0.206765E+09 | 0.375772E+09 | 0.248925E+09 | 0.110253E+10 |
March | 0.962954E+09 | 0.348612E+09 | 0.614342E+09 | 0.601080E+09 | 0.985950E+09 |
April | 0.144463E+10 | 0.600307E+09 | 0.844322E+09 | 0.119186E+10 | 0.736915E+09 |
May | 0.158826E+10 | 0.552131E+09 | 0.103613E+10 | 0.137262E+10 | 0.623471E+09 |
June | 0.184067E+10 | 0.800765E+09 | 0.103991E+10 | 0.175318E+10 | 0.462808E+09 |
July | 0.177118E+10 | 0.794862E+09 | 0.976318E+09 | 0.176740E+10 | 0.400638E+09 |
August | 0.174102E+10 | 0.870925E+09 | 0.870093E+09 | 0.183955E+10 | 0.380658E+09 |
September | 0.124589E+10 | 0.574696E+09 | 0.671199E+09 | 0.113847E+10 | 0.582727E+09 |
October | 0.839042E+09 | 0.356513E+09 | 0.482529E+09 | 0.583381E+09 | 0.864897E+09 |
November | 0.397999E+09 | 0.112368E+09 | 0.285631E+09 | 0.126561E+09 | 0.111877E+10 |
December | 0.337341E+09 | 0.108614E+09 | 0.228727E+09 | 86355892.24 | 0.143128E+10 |
Annual Sum or Average | 0.131030E+11 | 0.541569E+10 | 0.768734E+10 | 0.107749E+11 | 0.101249E+11 |
Minimum of Months | 0.337341E+09 | 89130193.07 | 0.228727E+09 | 65529803.71 | 0.380658E+09 |
Maximum of Months | 0.184067E+10 | 0.870925E+09 | 0.103991E+10 | 0.183955E+10 | 0.143426E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351493E+09 | 89128564.47 | 0.262364E+09 | 65528606.34 | 0.143423E+10 |
February | 0.582526E+09 | 0.206761E+09 | 0.375765E+09 | 0.248920E+09 | 0.110251E+10 |
March | 0.962937E+09 | 0.348606E+09 | 0.614331E+09 | 0.601069E+09 | 0.985932E+09 |
April | 0.144460E+10 | 0.600296E+09 | 0.844307E+09 | 0.119184E+10 | 0.736901E+09 |
May | 0.158824E+10 | 0.552121E+09 | 0.103611E+10 | 0.137260E+10 | 0.623459E+09 |
June | 0.184064E+10 | 0.800750E+09 | 0.103989E+10 | 0.175315E+10 | 0.462799E+09 |
July | 0.177115E+10 | 0.794847E+09 | 0.976300E+09 | 0.176737E+10 | 0.400631E+09 |
August | 0.174099E+10 | 0.870909E+09 | 0.870077E+09 | 0.183951E+10 | 0.380651E+09 |
September | 0.124587E+10 | 0.574685E+09 | 0.671187E+09 | 0.113845E+10 | 0.582717E+09 |
October | 0.839027E+09 | 0.356507E+09 | 0.482520E+09 | 0.583370E+09 | 0.864882E+09 |
November | 0.397992E+09 | 0.112366E+09 | 0.285626E+09 | 0.126559E+09 | 0.111875E+10 |
December | 0.337335E+09 | 0.108612E+09 | 0.228722E+09 | 86354314.33 | 0.143125E+10 |
Annual Sum or Average | 0.131028E+11 | 0.541559E+10 | 0.768720E+10 | 0.107747E+11 | 0.101247E+11 |
Minimum of Months | 0.337335E+09 | 89128564.47 | 0.228722E+09 | 65528606.34 | 0.380651E+09 |
Maximum of Months | 0.184064E+10 | 0.870909E+09 | 0.103989E+10 | 0.183951E+10 | 0.143423E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869507E+09 | 0.516204E+09 | 0.353303E+09 | 0.681447E+09 | 0.115913E+10 |
February | 0.120819E+10 | 0.747899E+09 | 0.460290E+09 | 0.106057E+10 | 0.942081E+09 |
March | 0.143944E+10 | 0.767901E+09 | 0.671537E+09 | 0.125821E+10 | 0.915370E+09 |
April | 0.147029E+10 | 0.638455E+09 | 0.831831E+09 | 0.121696E+10 | 0.724993E+09 |
May | 0.138890E+10 | 0.413628E+09 | 0.975268E+09 | 0.104961E+10 | 0.603424E+09 |
June | 0.122971E+10 | 0.330027E+09 | 0.899680E+09 | 0.893555E+09 | 0.459304E+09 |
July | 0.138571E+10 | 0.507366E+09 | 0.878347E+09 | 0.112812E+10 | 0.417479E+09 |
August | 0.148892E+10 | 0.694241E+09 | 0.794674E+09 | 0.139921E+10 | 0.398897E+09 |
September | 0.159707E+10 | 0.882177E+09 | 0.714891E+09 | 0.155466E+10 | 0.559195E+09 |
October | 0.149482E+10 | 0.923089E+09 | 0.571728E+09 | 0.144790E+10 | 0.794919E+09 |
November | 0.854877E+09 | 0.489842E+09 | 0.365035E+09 | 0.708256E+09 | 0.955767E+09 |
December | 0.924137E+09 | 0.597936E+09 | 0.326201E+09 | 0.812173E+09 | 0.120541E+10 |
Annual Sum or Average | 0.153516E+11 | 0.750877E+10 | 0.784278E+10 | 0.132107E+11 | 0.913596E+10 |
Minimum of Months | 0.854877E+09 | 0.330027E+09 | 0.326201E+09 | 0.681447E+09 | 0.398897E+09 |
Maximum of Months | 0.159707E+10 | 0.923089E+09 | 0.975268E+09 | 0.155466E+10 | 0.120541E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869501E+09 | 0.516200E+09 | 0.353301E+09 | 0.681440E+09 | 0.115913E+10 |
February | 0.120818E+10 | 0.747894E+09 | 0.460287E+09 | 0.106056E+10 | 0.942082E+09 |
March | 0.143943E+10 | 0.767895E+09 | 0.671533E+09 | 0.125820E+10 | 0.915370E+09 |
April | 0.147028E+10 | 0.638451E+09 | 0.831826E+09 | 0.121695E+10 | 0.724993E+09 |
May | 0.138889E+10 | 0.413625E+09 | 0.975263E+09 | 0.104961E+10 | 0.603424E+09 |
June | 0.122970E+10 | 0.330024E+09 | 0.899676E+09 | 0.893549E+09 | 0.459304E+09 |
July | 0.138570E+10 | 0.507362E+09 | 0.878343E+09 | 0.112811E+10 | 0.417478E+09 |
August | 0.148891E+10 | 0.694236E+09 | 0.794670E+09 | 0.139921E+10 | 0.398897E+09 |
September | 0.159706E+10 | 0.882171E+09 | 0.714887E+09 | 0.155465E+10 | 0.559194E+09 |
October | 0.149481E+10 | 0.923083E+09 | 0.571725E+09 | 0.144789E+10 | 0.794919E+09 |
November | 0.854871E+09 | 0.489839E+09 | 0.365033E+09 | 0.708249E+09 | 0.955767E+09 |
December | 0.924131E+09 | 0.597932E+09 | 0.326199E+09 | 0.812166E+09 | 0.120541E+10 |
Annual Sum or Average | 0.153515E+11 | 0.750871E+10 | 0.784274E+10 | 0.132106E+11 | 0.913596E+10 |
Minimum of Months | 0.854871E+09 | 0.330024E+09 | 0.326199E+09 | 0.681440E+09 | 0.398897E+09 |
Maximum of Months | 0.159706E+10 | 0.923083E+09 | 0.975263E+09 | 0.155465E+10 | 0.120541E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869507E+09 | 0.516204E+09 | 0.353303E+09 | 0.681447E+09 | 0.115913E+10 |
February | 0.120819E+10 | 0.747899E+09 | 0.460290E+09 | 0.106057E+10 | 0.942081E+09 |
March | 0.143944E+10 | 0.767901E+09 | 0.671537E+09 | 0.125821E+10 | 0.915370E+09 |
April | 0.147029E+10 | 0.638455E+09 | 0.831831E+09 | 0.121696E+10 | 0.724993E+09 |
May | 0.138890E+10 | 0.413628E+09 | 0.975268E+09 | 0.104961E+10 | 0.603424E+09 |
June | 0.122971E+10 | 0.330027E+09 | 0.899680E+09 | 0.893555E+09 | 0.459304E+09 |
July | 0.138571E+10 | 0.507366E+09 | 0.878347E+09 | 0.112812E+10 | 0.417479E+09 |
August | 0.148892E+10 | 0.694241E+09 | 0.794674E+09 | 0.139921E+10 | 0.398897E+09 |
September | 0.159707E+10 | 0.882177E+09 | 0.714891E+09 | 0.155466E+10 | 0.559195E+09 |
October | 0.149482E+10 | 0.923089E+09 | 0.571728E+09 | 0.144790E+10 | 0.794919E+09 |
November | 0.854877E+09 | 0.489842E+09 | 0.365035E+09 | 0.708256E+09 | 0.955767E+09 |
December | 0.924137E+09 | 0.597936E+09 | 0.326201E+09 | 0.812173E+09 | 0.120541E+10 |
Annual Sum or Average | 0.153516E+11 | 0.750877E+10 | 0.784278E+10 | 0.132107E+11 | 0.913596E+10 |
Minimum of Months | 0.854877E+09 | 0.330027E+09 | 0.326201E+09 | 0.681447E+09 | 0.398897E+09 |
Maximum of Months | 0.159707E+10 | 0.923089E+09 | 0.975268E+09 | 0.155466E+10 | 0.120541E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869501E+09 | 0.516200E+09 | 0.353301E+09 | 0.681440E+09 | 0.115913E+10 |
February | 0.120818E+10 | 0.747894E+09 | 0.460287E+09 | 0.106056E+10 | 0.942082E+09 |
March | 0.143943E+10 | 0.767895E+09 | 0.671533E+09 | 0.125820E+10 | 0.915370E+09 |
April | 0.147028E+10 | 0.638451E+09 | 0.831826E+09 | 0.121695E+10 | 0.724993E+09 |
May | 0.138889E+10 | 0.413625E+09 | 0.975263E+09 | 0.104961E+10 | 0.603424E+09 |
June | 0.122970E+10 | 0.330024E+09 | 0.899676E+09 | 0.893549E+09 | 0.459304E+09 |
July | 0.138570E+10 | 0.507362E+09 | 0.878343E+09 | 0.112811E+10 | 0.417478E+09 |
August | 0.148891E+10 | 0.694236E+09 | 0.794670E+09 | 0.139921E+10 | 0.398897E+09 |
September | 0.159706E+10 | 0.882171E+09 | 0.714887E+09 | 0.155465E+10 | 0.559194E+09 |
October | 0.149481E+10 | 0.923083E+09 | 0.571725E+09 | 0.144789E+10 | 0.794919E+09 |
November | 0.854871E+09 | 0.489839E+09 | 0.365033E+09 | 0.708249E+09 | 0.955767E+09 |
December | 0.924131E+09 | 0.597932E+09 | 0.326199E+09 | 0.812166E+09 | 0.120541E+10 |
Annual Sum or Average | 0.153515E+11 | 0.750871E+10 | 0.784274E+10 | 0.132106E+11 | 0.913596E+10 |
Minimum of Months | 0.854871E+09 | 0.330024E+09 | 0.326199E+09 | 0.681440E+09 | 0.398897E+09 |
Maximum of Months | 0.159706E+10 | 0.923083E+09 | 0.975263E+09 | 0.155465E+10 | 0.120541E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869469E+09 | 0.516181E+09 | 0.353288E+09 | 0.681416E+09 | 0.115908E+10 |
February | 0.120814E+10 | 0.747867E+09 | 0.460270E+09 | 0.106052E+10 | 0.942044E+09 |
March | 0.143937E+10 | 0.767867E+09 | 0.671508E+09 | 0.125816E+10 | 0.915333E+09 |
April | 0.147022E+10 | 0.638427E+09 | 0.831795E+09 | 0.121691E+10 | 0.724964E+09 |
May | 0.138884E+10 | 0.413610E+09 | 0.975227E+09 | 0.104957E+10 | 0.603400E+09 |
June | 0.122965E+10 | 0.330012E+09 | 0.899642E+09 | 0.893516E+09 | 0.459285E+09 |
July | 0.138565E+10 | 0.507343E+09 | 0.878309E+09 | 0.112807E+10 | 0.417462E+09 |
August | 0.148885E+10 | 0.694211E+09 | 0.794640E+09 | 0.139915E+10 | 0.398881E+09 |
September | 0.159700E+10 | 0.882138E+09 | 0.714860E+09 | 0.155459E+10 | 0.559172E+09 |
October | 0.149475E+10 | 0.923049E+09 | 0.571703E+09 | 0.144784E+10 | 0.794887E+09 |
November | 0.854840E+09 | 0.489821E+09 | 0.365019E+09 | 0.708224E+09 | 0.955728E+09 |
December | 0.924097E+09 | 0.597910E+09 | 0.326187E+09 | 0.812137E+09 | 0.120536E+10 |
Annual Sum or Average | 0.153509E+11 | 0.750844E+10 | 0.784245E+10 | 0.132101E+11 | 0.913559E+10 |
Minimum of Months | 0.854840E+09 | 0.330012E+09 | 0.326187E+09 | 0.681416E+09 | 0.398881E+09 |
Maximum of Months | 0.159700E+10 | 0.923049E+09 | 0.975227E+09 | 0.155459E+10 | 0.120536E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370753E+09 | 0.109347E+09 | 0.261406E+09 | 87314057.70 | 0.151831E+10 |
February | 0.600386E+09 | 0.225658E+09 | 0.374728E+09 | 0.276524E+09 | 0.122981E+10 |
March | 0.931417E+09 | 0.314394E+09 | 0.617023E+09 | 0.559747E+09 | 0.115125E+10 |
April | 0.137136E+10 | 0.524358E+09 | 0.847001E+09 | 0.106775E+10 | 0.908093E+09 |
May | 0.182315E+10 | 0.740520E+09 | 0.108263E+10 | 0.165425E+10 | 0.708348E+09 |
June | 0.169676E+10 | 0.658645E+09 | 0.103812E+10 | 0.155682E+10 | 0.557454E+09 |
July | 0.216593E+10 | 0.113835E+10 | 0.102759E+10 | 0.225048E+10 | 0.528683E+09 |
August | 0.179198E+10 | 0.915004E+09 | 0.876980E+09 | 0.187870E+10 | 0.523573E+09 |
September | 0.141234E+10 | 0.677707E+09 | 0.734637E+09 | 0.134684E+10 | 0.671973E+09 |
October | 0.830811E+09 | 0.338513E+09 | 0.492298E+09 | 0.571473E+09 | 0.999353E+09 |
November | 0.400418E+09 | 0.112951E+09 | 0.287467E+09 | 0.129491E+09 | 0.128663E+10 |
December | 0.347862E+09 | 0.119225E+09 | 0.228637E+09 | 0.105649E+09 | 0.166705E+10 |
Annual Sum or Average | 0.137432E+11 | 0.587467E+10 | 0.786851E+10 | 0.114851E+11 | 0.117505E+11 |
Minimum of Months | 0.347862E+09 | 0.109347E+09 | 0.228637E+09 | 87314057.70 | 0.523573E+09 |
Maximum of Months | 0.216593E+10 | 0.113835E+10 | 0.108263E+10 | 0.225048E+10 | 0.166705E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370753E+09 | 0.109347E+09 | 0.261406E+09 | 87314057.70 | 0.151831E+10 |
February | 0.600386E+09 | 0.225658E+09 | 0.374728E+09 | 0.276524E+09 | 0.122981E+10 |
March | 0.931417E+09 | 0.314394E+09 | 0.617023E+09 | 0.559747E+09 | 0.115125E+10 |
April | 0.137136E+10 | 0.524358E+09 | 0.847001E+09 | 0.106775E+10 | 0.908093E+09 |
May | 0.182315E+10 | 0.740520E+09 | 0.108263E+10 | 0.165425E+10 | 0.708348E+09 |
June | 0.169676E+10 | 0.658645E+09 | 0.103812E+10 | 0.155682E+10 | 0.557454E+09 |
July | 0.216593E+10 | 0.113835E+10 | 0.102759E+10 | 0.225048E+10 | 0.528683E+09 |
August | 0.179198E+10 | 0.915004E+09 | 0.876980E+09 | 0.187870E+10 | 0.523573E+09 |
September | 0.141234E+10 | 0.677707E+09 | 0.734637E+09 | 0.134684E+10 | 0.671973E+09 |
October | 0.830811E+09 | 0.338513E+09 | 0.492298E+09 | 0.571473E+09 | 0.999353E+09 |
November | 0.400418E+09 | 0.112951E+09 | 0.287467E+09 | 0.129491E+09 | 0.128663E+10 |
December | 0.347862E+09 | 0.119225E+09 | 0.228637E+09 | 0.105649E+09 | 0.166705E+10 |
Annual Sum or Average | 0.137432E+11 | 0.587467E+10 | 0.786851E+10 | 0.114851E+11 | 0.117505E+11 |
Minimum of Months | 0.347862E+09 | 0.109347E+09 | 0.228637E+09 | 87314057.70 | 0.523573E+09 |
Maximum of Months | 0.216593E+10 | 0.113835E+10 | 0.108263E+10 | 0.225048E+10 | 0.166705E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370746E+09 | 0.109345E+09 | 0.261402E+09 | 87312462.28 | 0.151829E+10 |
February | 0.600375E+09 | 0.225654E+09 | 0.374721E+09 | 0.276519E+09 | 0.122979E+10 |
March | 0.931400E+09 | 0.314389E+09 | 0.617011E+09 | 0.559737E+09 | 0.115123E+10 |
April | 0.137133E+10 | 0.524349E+09 | 0.846986E+09 | 0.106774E+10 | 0.908077E+09 |
May | 0.182312E+10 | 0.740507E+09 | 0.108261E+10 | 0.165422E+10 | 0.708335E+09 |
June | 0.169673E+10 | 0.658633E+09 | 0.103810E+10 | 0.155679E+10 | 0.557444E+09 |
July | 0.216589E+10 | 0.113833E+10 | 0.102757E+10 | 0.225044E+10 | 0.528673E+09 |
August | 0.179195E+10 | 0.914987E+09 | 0.876964E+09 | 0.187867E+10 | 0.523564E+09 |
September | 0.141232E+10 | 0.677694E+09 | 0.734624E+09 | 0.134682E+10 | 0.671961E+09 |
October | 0.830795E+09 | 0.338506E+09 | 0.492289E+09 | 0.571462E+09 | 0.999335E+09 |
November | 0.400410E+09 | 0.112949E+09 | 0.287461E+09 | 0.129488E+09 | 0.128661E+10 |
December | 0.347856E+09 | 0.119223E+09 | 0.228633E+09 | 0.105647E+09 | 0.166701E+10 |
Annual Sum or Average | 0.137429E+11 | 0.587456E+10 | 0.786837E+10 | 0.114848E+11 | 0.117503E+11 |
Minimum of Months | 0.347856E+09 | 0.109345E+09 | 0.228633E+09 | 87312462.28 | 0.523564E+09 |
Maximum of Months | 0.216589E+10 | 0.113833E+10 | 0.108261E+10 | 0.225044E+10 | 0.166701E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.984313E+09 | 0.00 | 0.984313E+09 | 5243058.81 | 0.621859E+10 |
February | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.132973E+09 | 0.500200E+10 |
March | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.563426E+09 | 0.451120E+10 |
April | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.144477E+10 | 0.340889E+10 |
May | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.247214E+10 | 0.279487E+10 |
June | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.274132E+10 | 0.204644E+10 |
July | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.310505E+10 | 0.188365E+10 |
August | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.271195E+10 | 0.186869E+10 |
September | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.146012E+10 | 0.272621E+10 |
October | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.503731E+09 | 0.393322E+10 |
November | 0.107845E+10 | 0.00 | 0.107845E+10 | 64081001.97 | 0.496088E+10 |
December | 0.836412E+09 | 0.00 | 0.836412E+09 | 2212706.49 | 0.626717E+10 |
Annual Sum or Average | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.152070E+11 | 0.456218E+11 |
Minimum of Months | 0.836412E+09 | 0.00 | 0.836412E+09 | 2212706.49 | 0.186869E+10 |
Maximum of Months | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.310505E+10 | 0.626717E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.217378E+09 | 0.387728E+10 |
February | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.799796E+09 | 0.303492E+10 |
March | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.185424E+10 | 0.274639E+10 |
April | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.360228E+10 | 0.209717E+10 |
May | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.414522E+10 | 0.177470E+10 |
June | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.525517E+10 | 0.133401E+10 |
July | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.529623E+10 | 0.118310E+10 |
August | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.550798E+10 | 0.114962E+10 |
September | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.343800E+10 | 0.165390E+10 |
October | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.179705E+10 | 0.239507E+10 |
November | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.413524E+09 | 0.304826E+10 |
December | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.282265E+09 | 0.390259E+10 |
Annual Sum or Average | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.326091E+11 | 0.281970E+11 |
Minimum of Months | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.217378E+09 | 0.114962E+10 |
Maximum of Months | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.550798E+10 | 0.390259E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.342132E+10 | 0.554084E+10 |
February | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.531449E+10 | 0.454085E+10 |
March | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.629242E+10 | 0.439040E+10 |
April | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.610440E+10 | 0.348068E+10 |
May | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.526747E+10 | 0.292256E+10 |
June | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.451224E+10 | 0.220038E+10 |
July | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.568435E+10 | 0.202479E+10 |
August | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.702548E+10 | 0.195960E+10 |
September | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.776307E+10 | 0.273344E+10 |
October | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.722229E+10 | 0.383717E+10 |
November | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.356831E+10 | 0.453361E+10 |
December | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.408816E+10 | 0.569984E+10 |
Annual Sum or Average | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.662640E+11 | 0.438642E+11 |
Minimum of Months | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.342132E+10 | 0.195960E+10 |
Maximum of Months | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.776307E+10 | 0.569984E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.288668E+09 | 0.396999E+10 |
February | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.910361E+09 | 0.314433E+10 |
March | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.180850E+10 | 0.289362E+10 |
April | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.337469E+10 | 0.228858E+10 |
May | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.504169E+10 | 0.194898E+10 |
June | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.478869E+10 | 0.147501E+10 |
July | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.686556E+10 | 0.141161E+10 |
August | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.578916E+10 | 0.135367E+10 |
September | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.411297E+10 | 0.182840E+10 |
October | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.182153E+10 | 0.254536E+10 |
November | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.450936E+09 | 0.313180E+10 |
December | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.366002E+09 | 0.402950E+10 |
Annual Sum or Average | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.356188E+11 | 0.300209E+11 |
Minimum of Months | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.288668E+09 | 0.135367E+10 |
Maximum of Months | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.686556E+10 | 0.402950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.984313E+09 | 0.00 | 0.984313E+09 | 17735177.20 | 0.554567E+10 |
February | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.180692E+09 | 0.445626E+10 |
March | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.663074E+09 | 0.406306E+10 |
April | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.153181E+10 | 0.315244E+10 |
May | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.252068E+10 | 0.263696E+10 |
June | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.275263E+10 | 0.197233E+10 |
July | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.310082E+10 | 0.182891E+10 |
August | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.271731E+10 | 0.179494E+10 |
September | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.150445E+10 | 0.254331E+10 |
October | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.596731E+09 | 0.351750E+10 |
November | 0.107845E+10 | 0.00 | 0.107845E+10 | 94697873.03 | 0.435097E+10 |
December | 0.836412E+09 | 0.00 | 0.836412E+09 | 10614759.57 | 0.555365E+10 |
Annual Sum or Average | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.156913E+11 | 0.414160E+11 |
Minimum of Months | 0.836412E+09 | 0.00 | 0.836412E+09 | 10614759.57 | 0.179494E+10 |
Maximum of Months | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.310082E+10 | 0.555365E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.243117E+09 | 0.351603E+10 |
February | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.861022E+09 | 0.276919E+10 |
March | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.191846E+10 | 0.253557E+10 |
April | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.364701E+10 | 0.197861E+10 |
May | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.416317E+10 | 0.170704E+10 |
June | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.524287E+10 | 0.130667E+10 |
July | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.527738E+10 | 0.117087E+10 |
August | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.549703E+10 | 0.112915E+10 |
September | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.345650E+10 | 0.157859E+10 |
October | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.185665E+10 | 0.220547E+10 |
November | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.449391E+09 | 0.275493E+10 |
December | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.311735E+09 | 0.352992E+10 |
Annual Sum or Average | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.329243E+11 | 0.261820E+11 |
Minimum of Months | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.243117E+09 | 0.112915E+10 |
Maximum of Months | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.549703E+10 | 0.352992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.353317E+10 | 0.499866E+10 |
February | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.544032E+10 | 0.413314E+10 |
March | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.637660E+10 | 0.403293E+10 |
April | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.617665E+10 | 0.326530E+10 |
May | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.531540E+10 | 0.278202E+10 |
June | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.452765E+10 | 0.212924E+10 |
July | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.568674E+10 | 0.197849E+10 |
August | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.703692E+10 | 0.189709E+10 |
September | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.780390E+10 | 0.258261E+10 |
October | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.730836E+10 | 0.351707E+10 |
November | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.366740E+10 | 0.409366E+10 |
December | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.419017E+10 | 0.514756E+10 |
Annual Sum or Average | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.670633E+11 | 0.405578E+11 |
Minimum of Months | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.353317E+10 | 0.189709E+10 |
Maximum of Months | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.780390E+10 | 0.514756E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.306340E+09 | 0.363179E+10 |
February | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.950234E+09 | 0.290390E+10 |
March | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.185261E+10 | 0.268748E+10 |
April | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.341149E+10 | 0.216218E+10 |
May | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.506016E+10 | 0.186481E+10 |
June | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.478853E+10 | 0.142869E+10 |
July | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.685515E+10 | 0.137831E+10 |
August | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.579065E+10 | 0.131255E+10 |
September | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.413441E+10 | 0.173859E+10 |
October | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.186493E+10 | 0.235856E+10 |
November | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.476751E+09 | 0.287410E+10 |
December | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.384968E+09 | 0.370619E+10 |
Annual Sum or Average | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.358762E+11 | 0.280471E+11 |
Minimum of Months | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.306340E+09 | 0.131255E+10 |
Maximum of Months | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.685515E+10 | 0.370619E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.54 | 2637.82 | 367.49 | 0.00 | 367.49 | 0.00 | 0.00 |
February | 40.12 | 2326.49 | 571.83 | 0.00 | 571.83 | 0.00 | 0.00 |
March | 184.08 | 1857.68 | 842.50 | 0.00 | 842.50 | 0.00 | 0.00 |
April | 520.56 | 1441.14 | 1192.18 | 4.19 | 1188.00 | 0.00 | 0.00 |
May | 900.54 | 1106.47 | 1533.98 | 45.47 | 1488.52 | 0.00 | 0.00 |
June | 1033.07 | 838.10 | 1612.89 | 106.35 | 1506.54 | 0.00 | 0.00 |
July | 1130.67 | 744.59 | 1532.92 | 120.00 | 1412.92 | 0.00 | 0.00 |
August | 984.33 | 739.78 | 1240.94 | 33.41 | 1207.53 | 0.00 | 0.00 |
September | 545.31 | 1117.57 | 964.02 | 0.28 | 963.74 | 0.00 | 0.00 |
October | 164.08 | 1618.34 | 660.52 | 0.00 | 660.52 | 0.00 | 0.00 |
November | 17.14 | 2169.56 | 416.06 | 0.00 | 416.06 | 0.00 | 0.00 |
December | 0.04 | 2689.46 | 312.27 | 0.00 | 312.27 | 0.00 | 0.00 |
Annual Sum or Average | 462.74 | 1603.70 | 939.11 | 26.00 | 913.11 | 0.00 | 0.00 |
Minimum of Months | 0.04 | 739.78 | 312.27 | 0.00 | 312.27 | 0.00 | 0.00 |
Maximum of Months | 1130.67 | 2689.46 | 1612.89 | 120.00 | 1506.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.40 | 1606.47 | 393.70 | 99.83 | 293.87 | 0.00 | 0.00 |
February | 308.68 | 1367.22 | 722.39 | 256.40 | 465.98 | 0.00 | 0.00 |
March | 673.25 | 1104.33 | 1078.57 | 390.47 | 688.10 | 0.00 | 0.00 |
April | 1379.46 | 852.91 | 1672.01 | 694.80 | 977.22 | 0.00 | 0.00 |
May | 1537.43 | 698.33 | 1778.96 | 618.42 | 1160.54 | 0.00 | 0.00 |
June | 2029.13 | 535.65 | 2130.40 | 926.81 | 1203.59 | 0.00 | 0.00 |
July | 1979.61 | 448.74 | 1983.84 | 890.30 | 1093.54 | 0.00 | 0.00 |
August | 2060.41 | 426.36 | 1950.05 | 975.49 | 974.56 | 0.00 | 0.00 |
September | 1317.66 | 674.45 | 1442.00 | 665.15 | 776.85 | 0.00 | 0.00 |
October | 653.42 | 968.74 | 939.78 | 399.32 | 540.46 | 0.00 | 0.00 |
November | 146.48 | 1294.86 | 460.64 | 130.06 | 330.59 | 0.00 | 0.00 |
December | 96.72 | 1603.13 | 377.84 | 121.66 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1025.00 | 963.17 | 1246.48 | 515.19 | 731.29 | 0.00 | 0.00 |
Minimum of Months | 73.40 | 426.36 | 377.84 | 99.83 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 2060.41 | 1606.47 | 2130.40 | 975.49 | 1203.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1272.10 | 2163.82 | 1623.16 | 963.63 | 659.53 | 0.00 | 0.00 |
February | 2191.95 | 1947.08 | 2497.06 | 1545.74 | 951.32 | 0.00 | 0.00 |
March | 2348.78 | 1708.79 | 2687.09 | 1433.49 | 1253.60 | 0.00 | 0.00 |
April | 2347.50 | 1398.51 | 2836.17 | 1231.57 | 1604.59 | 0.00 | 0.00 |
May | 1959.38 | 1126.45 | 2592.74 | 772.15 | 1820.60 | 0.00 | 0.00 |
June | 1723.66 | 886.00 | 2372.09 | 636.62 | 1735.48 | 0.00 | 0.00 |
July | 2105.93 | 779.34 | 2586.80 | 947.13 | 1639.67 | 0.00 | 0.00 |
August | 2612.01 | 744.65 | 2779.46 | 1295.98 | 1483.47 | 0.00 | 0.00 |
September | 2998.92 | 1078.68 | 3080.73 | 1701.71 | 1379.02 | 0.00 | 0.00 |
October | 2702.89 | 1483.93 | 2790.47 | 1723.19 | 1067.28 | 0.00 | 0.00 |
November | 1366.22 | 1843.67 | 1649.05 | 944.90 | 704.15 | 0.00 | 0.00 |
December | 1516.13 | 2250.22 | 1725.15 | 1116.21 | 608.94 | 0.00 | 0.00 |
Annual Sum or Average | 2094.51 | 1448.49 | 2433.95 | 1190.49 | 1243.45 | 0.00 | 0.00 |
Minimum of Months | 1272.10 | 744.65 | 1623.16 | 636.62 | 608.94 | 0.00 | 0.00 |
Maximum of Months | 2998.92 | 2250.22 | 3080.73 | 1723.19 | 1820.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.80 | 1700.61 | 415.27 | 122.48 | 292.79 | 0.00 | 0.00 |
February | 342.91 | 1525.05 | 744.52 | 279.83 | 464.69 | 0.00 | 0.00 |
March | 626.95 | 1289.48 | 1043.25 | 352.14 | 691.11 | 0.00 | 0.00 |
April | 1235.82 | 1051.03 | 1587.21 | 606.89 | 980.32 | 0.00 | 0.00 |
May | 1852.87 | 793.40 | 2042.05 | 829.43 | 1212.62 | 0.00 | 0.00 |
June | 1801.87 | 645.20 | 1963.83 | 762.32 | 1201.52 | 0.00 | 0.00 |
July | 2520.69 | 592.16 | 2425.99 | 1275.02 | 1150.96 | 0.00 | 0.00 |
August | 2104.27 | 586.44 | 2007.14 | 1024.86 | 982.27 | 0.00 | 0.00 |
September | 1558.84 | 777.74 | 1634.65 | 784.38 | 850.27 | 0.00 | 0.00 |
October | 640.09 | 1119.34 | 930.56 | 379.16 | 551.41 | 0.00 | 0.00 |
November | 149.87 | 1489.15 | 463.44 | 130.73 | 332.71 | 0.00 | 0.00 |
December | 118.33 | 1867.20 | 389.63 | 133.54 | 256.09 | 0.00 | 0.00 |
Annual Sum or Average | 1092.56 | 1117.81 | 1307.37 | 558.85 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 97.80 | 586.44 | 389.63 | 122.48 | 256.09 | 0.00 | 0.00 |
Maximum of Months | 2520.69 | 1867.20 | 2425.99 | 1275.02 | 1212.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.96 | 2321.76 | 367.50 | 0.00 | 367.50 | 0.00 | 0.00 |
February | 54.97 | 2067.63 | 571.84 | 0.00 | 571.84 | 0.00 | 0.00 |
March | 210.36 | 1684.29 | 842.52 | 0.00 | 842.52 | 0.00 | 0.00 |
April | 557.40 | 1315.16 | 1192.20 | 4.19 | 1188.02 | 0.00 | 0.00 |
May | 922.99 | 1043.49 | 1534.01 | 45.47 | 1488.54 | 0.00 | 0.00 |
June | 1057.61 | 789.52 | 1612.92 | 106.35 | 1506.57 | 0.00 | 0.00 |
July | 1159.29 | 703.28 | 1532.95 | 120.00 | 1412.95 | 0.00 | 0.00 |
August | 1012.53 | 697.69 | 1240.96 | 33.41 | 1207.55 | 0.00 | 0.00 |
September | 563.32 | 1051.78 | 964.03 | 0.28 | 963.76 | 0.00 | 0.00 |
October | 188.07 | 1468.49 | 660.53 | 0.00 | 660.53 | 0.00 | 0.00 |
November | 24.72 | 1913.92 | 416.07 | 0.00 | 416.07 | 0.00 | 0.00 |
December | 0.83 | 2339.89 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Annual Sum or Average | 482.21 | 1446.66 | 939.13 | 26.00 | 913.13 | 0.00 | 0.00 |
Minimum of Months | 0.83 | 697.69 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Maximum of Months | 1159.29 | 2339.89 | 1612.92 | 120.00 | 1506.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.16 | 1447.61 | 393.70 | 99.83 | 293.87 | 0.00 | 0.00 |
February | 330.60 | 1254.52 | 722.38 | 256.40 | 465.98 | 0.00 | 0.00 |
March | 692.30 | 1025.38 | 1078.57 | 390.47 | 688.10 | 0.00 | 0.00 |
April | 1389.77 | 809.09 | 1672.01 | 694.79 | 977.21 | 0.00 | 0.00 |
May | 1547.65 | 662.60 | 1778.95 | 618.42 | 1160.53 | 0.00 | 0.00 |
June | 2027.46 | 514.66 | 2130.39 | 926.80 | 1203.59 | 0.00 | 0.00 |
July | 1977.38 | 441.72 | 1983.83 | 890.29 | 1093.53 | 0.00 | 0.00 |
August | 2056.45 | 429.22 | 1950.04 | 975.49 | 974.56 | 0.00 | 0.00 |
September | 1326.39 | 638.08 | 1441.99 | 665.15 | 776.84 | 0.00 | 0.00 |
October | 670.94 | 894.22 | 939.78 | 399.32 | 540.46 | 0.00 | 0.00 |
November | 159.54 | 1176.03 | 460.64 | 130.05 | 330.59 | 0.00 | 0.00 |
December | 105.39 | 1457.06 | 377.84 | 121.65 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1034.03 | 894.12 | 1246.47 | 515.19 | 731.28 | 0.00 | 0.00 |
Minimum of Months | 81.16 | 429.22 | 377.84 | 99.83 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 2056.45 | 1457.06 | 2130.39 | 975.49 | 1203.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1277.37 | 2068.71 | 1623.21 | 963.66 | 659.55 | 0.00 | 0.00 |
February | 2196.80 | 1877.01 | 2497.13 | 1545.79 | 951.34 | 0.00 | 0.00 |
March | 2349.32 | 1639.19 | 2687.17 | 1433.54 | 1253.63 | 0.00 | 0.00 |
April | 2355.09 | 1342.86 | 2836.25 | 1231.61 | 1604.63 | 0.00 | 0.00 |
May | 1966.65 | 1091.16 | 2592.81 | 772.17 | 1820.64 | 0.00 | 0.00 |
June | 1740.83 | 848.91 | 2372.15 | 636.64 | 1735.51 | 0.00 | 0.00 |
July | 2122.29 | 755.97 | 2586.86 | 947.16 | 1639.70 | 0.00 | 0.00 |
August | 2623.01 | 731.63 | 2779.53 | 1296.03 | 1483.50 | 0.00 | 0.00 |
September | 2995.01 | 1054.57 | 3080.82 | 1701.77 | 1379.05 | 0.00 | 0.00 |
October | 2696.49 | 1432.63 | 2790.56 | 1723.25 | 1067.31 | 0.00 | 0.00 |
November | 1376.66 | 1749.08 | 1649.10 | 944.93 | 704.17 | 0.00 | 0.00 |
December | 1526.34 | 2128.08 | 1725.20 | 1116.24 | 608.96 | 0.00 | 0.00 |
Annual Sum or Average | 2101.22 | 1390.92 | 2434.01 | 1190.53 | 1243.48 | 0.00 | 0.00 |
Minimum of Months | 1277.37 | 731.63 | 1623.21 | 636.64 | 608.96 | 0.00 | 0.00 |
Maximum of Months | 2995.01 | 2128.08 | 3080.82 | 1723.25 | 1820.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 107.78 | 1482.23 | 415.27 | 122.47 | 292.79 | 0.00 | 0.00 |
February | 376.31 | 1299.74 | 744.52 | 279.83 | 464.69 | 0.00 | 0.00 |
March | 675.22 | 1080.35 | 1043.24 | 352.14 | 691.10 | 0.00 | 0.00 |
April | 1301.96 | 882.94 | 1587.21 | 606.89 | 980.32 | 0.00 | 0.00 |
May | 1882.35 | 727.66 | 2042.04 | 829.43 | 1212.61 | 0.00 | 0.00 |
June | 1847.49 | 569.06 | 1963.83 | 762.31 | 1201.51 | 0.00 | 0.00 |
July | 2563.31 | 527.03 | 2425.98 | 1275.02 | 1150.96 | 0.00 | 0.00 |
August | 2161.43 | 505.40 | 2007.13 | 1024.86 | 982.27 | 0.00 | 0.00 |
September | 1586.79 | 705.40 | 1634.64 | 784.37 | 850.27 | 0.00 | 0.00 |
October | 680.08 | 950.33 | 930.56 | 379.15 | 551.40 | 0.00 | 0.00 |
November | 173.97 | 1208.26 | 463.44 | 130.73 | 332.71 | 0.00 | 0.00 |
December | 136.65 | 1504.44 | 389.63 | 133.54 | 256.09 | 0.00 | 0.00 |
Annual Sum or Average | 1129.46 | 951.96 | 1307.37 | 558.85 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 107.78 | 505.40 | 389.63 | 122.47 | 256.09 | 0.00 | 0.00 |
Maximum of Months | 2563.31 | 1504.44 | 2425.98 | 1275.02 | 1212.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.62 | 2070.52 | 367.50 | 0.00 | 367.50 | 0.00 | 0.00 |
February | 74.69 | 1842.04 | 571.84 | 0.00 | 571.84 | 0.00 | 0.00 |
March | 247.56 | 1516.97 | 842.52 | 0.00 | 842.52 | 0.00 | 0.00 |
April | 590.98 | 1216.22 | 1192.20 | 4.19 | 1188.02 | 0.00 | 0.00 |
May | 941.11 | 984.53 | 1534.01 | 45.47 | 1488.54 | 0.00 | 0.00 |
June | 1061.97 | 760.93 | 1612.92 | 106.35 | 1506.57 | 0.00 | 0.00 |
July | 1157.71 | 682.84 | 1532.95 | 120.00 | 1412.95 | 0.00 | 0.00 |
August | 1014.53 | 670.15 | 1240.96 | 33.41 | 1207.55 | 0.00 | 0.00 |
September | 580.42 | 981.22 | 964.03 | 0.28 | 963.76 | 0.00 | 0.00 |
October | 222.79 | 1313.29 | 660.53 | 0.00 | 660.53 | 0.00 | 0.00 |
November | 36.53 | 1678.61 | 416.07 | 0.00 | 416.07 | 0.00 | 0.00 |
December | 3.96 | 2073.49 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Annual Sum or Average | 497.57 | 1313.29 | 939.13 | 26.00 | 913.13 | 0.00 | 0.00 |
Minimum of Months | 3.96 | 670.15 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Maximum of Months | 1157.71 | 2073.49 | 1612.92 | 120.00 | 1506.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 90.77 | 1312.73 | 393.70 | 99.83 | 293.87 | 0.00 | 0.00 |
February | 355.91 | 1144.67 | 722.38 | 256.40 | 465.98 | 0.00 | 0.00 |
March | 716.27 | 946.67 | 1078.57 | 390.47 | 688.10 | 0.00 | 0.00 |
April | 1407.03 | 763.35 | 1672.01 | 694.79 | 977.21 | 0.00 | 0.00 |
May | 1554.35 | 637.34 | 1778.95 | 618.42 | 1160.53 | 0.00 | 0.00 |
June | 2022.71 | 504.12 | 2130.39 | 926.80 | 1203.59 | 0.00 | 0.00 |
July | 1970.35 | 437.15 | 1983.83 | 890.29 | 1093.53 | 0.00 | 0.00 |
August | 2052.35 | 421.58 | 1950.04 | 975.49 | 974.56 | 0.00 | 0.00 |
September | 1333.52 | 609.02 | 1441.99 | 665.15 | 776.84 | 0.00 | 0.00 |
October | 693.19 | 823.43 | 939.78 | 399.32 | 540.46 | 0.00 | 0.00 |
November | 173.38 | 1062.86 | 460.64 | 130.05 | 330.59 | 0.00 | 0.00 |
December | 116.39 | 1317.92 | 377.84 | 121.65 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1044.02 | 830.23 | 1246.47 | 515.19 | 731.28 | 0.00 | 0.00 |
Minimum of Months | 90.77 | 421.58 | 377.84 | 99.83 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 2052.35 | 1317.92 | 2130.39 | 975.49 | 1203.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1319.13 | 1866.28 | 1623.21 | 963.66 | 659.55 | 0.00 | 0.00 |
February | 2248.81 | 1708.48 | 2497.13 | 1545.79 | 951.34 | 0.00 | 0.00 |
March | 2380.75 | 1505.72 | 2687.17 | 1433.54 | 1253.63 | 0.00 | 0.00 |
April | 2382.97 | 1259.76 | 2836.25 | 1231.61 | 1604.63 | 0.00 | 0.00 |
May | 1984.54 | 1038.69 | 2592.81 | 772.17 | 1820.64 | 0.00 | 0.00 |
June | 1746.78 | 821.47 | 2372.15 | 636.64 | 1735.51 | 0.00 | 0.00 |
July | 2123.19 | 738.68 | 2586.86 | 947.16 | 1639.70 | 0.00 | 0.00 |
August | 2627.29 | 708.29 | 2779.53 | 1296.03 | 1483.50 | 0.00 | 0.00 |
September | 3010.77 | 996.38 | 3080.82 | 1701.77 | 1379.05 | 0.00 | 0.00 |
October | 2728.63 | 1313.12 | 2790.56 | 1723.25 | 1067.31 | 0.00 | 0.00 |
November | 1414.89 | 1579.35 | 1649.10 | 944.93 | 704.17 | 0.00 | 0.00 |
December | 1564.43 | 1921.88 | 1725.20 | 1116.24 | 608.96 | 0.00 | 0.00 |
Annual Sum or Average | 2126.56 | 1286.08 | 2434.01 | 1190.53 | 1243.48 | 0.00 | 0.00 |
Minimum of Months | 1319.13 | 708.29 | 1623.21 | 636.64 | 608.96 | 0.00 | 0.00 |
Maximum of Months | 3010.77 | 1921.88 | 3080.82 | 1723.25 | 1820.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 114.37 | 1355.95 | 415.27 | 122.47 | 292.79 | 0.00 | 0.00 |
February | 392.79 | 1200.35 | 744.52 | 279.83 | 464.69 | 0.00 | 0.00 |
March | 691.69 | 1003.39 | 1043.24 | 352.14 | 691.10 | 0.00 | 0.00 |
April | 1316.16 | 834.18 | 1587.21 | 606.89 | 980.32 | 0.00 | 0.00 |
May | 1889.25 | 696.24 | 2042.04 | 829.43 | 1212.61 | 0.00 | 0.00 |
June | 1847.43 | 551.19 | 1963.83 | 762.31 | 1201.51 | 0.00 | 0.00 |
July | 2559.42 | 514.60 | 2425.98 | 1275.02 | 1150.96 | 0.00 | 0.00 |
August | 2161.98 | 490.05 | 2007.13 | 1024.86 | 982.27 | 0.00 | 0.00 |
September | 1595.07 | 670.75 | 1634.64 | 784.37 | 850.27 | 0.00 | 0.00 |
October | 696.29 | 880.59 | 930.56 | 379.15 | 551.40 | 0.00 | 0.00 |
November | 183.93 | 1108.84 | 463.44 | 130.73 | 332.71 | 0.00 | 0.00 |
December | 143.73 | 1383.73 | 389.63 | 133.54 | 256.09 | 0.00 | 0.00 |
Annual Sum or Average | 1137.63 | 889.37 | 1307.37 | 558.85 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 114.37 | 490.05 | 389.63 | 122.47 | 256.09 | 0.00 | 0.00 |
Maximum of Months | 2559.42 | 1383.73 | 2425.98 | 1275.02 | 1212.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1447515.63 | 0.706515E+10 | 0.984292E+09 | 0.00 | 0.984292E+09 | 0.00 | 0.00 |
February | 97048864.89 | 0.562824E+10 | 0.138337E+10 | 0.00 | 0.138337E+10 | 0.00 | 0.00 |
March | 0.493044E+09 | 0.497561E+10 | 0.225655E+10 | 0.00 | 0.225655E+10 | 0.00 | 0.00 |
April | 0.134928E+10 | 0.373543E+10 | 0.309013E+10 | 10850937.75 | 0.307928E+10 | 0.00 | 0.00 |
May | 0.241201E+10 | 0.296357E+10 | 0.410862E+10 | 0.121776E+09 | 0.398685E+10 | 0.00 | 0.00 |
June | 0.267772E+10 | 0.217235E+10 | 0.418062E+10 | 0.275658E+09 | 0.390496E+10 | 0.00 | 0.00 |
July | 0.302838E+10 | 0.199430E+10 | 0.410578E+10 | 0.321401E+09 | 0.378438E+10 | 0.00 | 0.00 |
August | 0.263643E+10 | 0.198143E+10 | 0.332374E+10 | 89491720.40 | 0.323424E+10 | 0.00 | 0.00 |
September | 0.141345E+10 | 0.289674E+10 | 0.249873E+10 | 712957.55 | 0.249801E+10 | 0.00 | 0.00 |
October | 0.439460E+09 | 0.433457E+10 | 0.176913E+10 | 0.00 | 0.176913E+10 | 0.00 | 0.00 |
November | 44439660.55 | 0.562349E+10 | 0.107843E+10 | 0.00 | 0.107843E+10 | 0.00 | 0.00 |
December | 98740.08 | 0.720344E+10 | 0.836394E+09 | 0.00 | 0.836394E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.145928E+11 | 0.505743E+11 | 0.296158E+11 | 0.819890E+09 | 0.287959E+11 | 0.00 | 0.00 |
Minimum of Months | 98740.08 | 0.198143E+10 | 0.836394E+09 | 0.00 | 0.836394E+09 | 0.00 | 0.00 |
Maximum of Months | 0.302838E+10 | 0.720344E+10 | 0.418062E+10 | 0.321401E+09 | 0.398685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196588E+09 | 0.430276E+10 | 0.105449E+10 | 0.267389E+09 | 0.787102E+09 | 0.00 | 0.00 |
February | 0.746770E+09 | 0.330758E+10 | 0.174760E+10 | 0.620290E+09 | 0.112731E+10 | 0.00 | 0.00 |
March | 0.180323E+10 | 0.295783E+10 | 0.288885E+10 | 0.104583E+10 | 0.184301E+10 | 0.00 | 0.00 |
April | 0.357556E+10 | 0.221073E+10 | 0.433386E+10 | 0.180091E+10 | 0.253295E+10 | 0.00 | 0.00 |
May | 0.411784E+10 | 0.187040E+10 | 0.476476E+10 | 0.165638E+10 | 0.310838E+10 | 0.00 | 0.00 |
June | 0.525951E+10 | 0.138842E+10 | 0.552199E+10 | 0.240228E+10 | 0.311971E+10 | 0.00 | 0.00 |
July | 0.530218E+10 | 0.120191E+10 | 0.531351E+10 | 0.238457E+10 | 0.292894E+10 | 0.00 | 0.00 |
August | 0.551861E+10 | 0.114197E+10 | 0.522302E+10 | 0.261276E+10 | 0.261026E+10 | 0.00 | 0.00 |
September | 0.341539E+10 | 0.174817E+10 | 0.373766E+10 | 0.172408E+10 | 0.201359E+10 | 0.00 | 0.00 |
October | 0.175013E+10 | 0.259468E+10 | 0.251711E+10 | 0.106953E+10 | 0.144758E+10 | 0.00 | 0.00 |
November | 0.379681E+09 | 0.335628E+10 | 0.119399E+10 | 0.337103E+09 | 0.856888E+09 | 0.00 | 0.00 |
December | 0.259066E+09 | 0.429382E+10 | 0.101202E+10 | 0.325841E+09 | 0.686176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.323246E+11 | 0.303745E+11 | 0.393089E+11 | 0.162470E+11 | 0.230619E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196588E+09 | 0.114197E+10 | 0.101202E+10 | 0.267389E+09 | 0.686176E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551861E+10 | 0.430276E+10 | 0.552199E+10 | 0.261276E+10 | 0.311971E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340719E+10 | 0.579559E+10 | 0.434749E+10 | 0.258099E+10 | 0.176650E+10 | 0.00 | 0.00 |
February | 0.530277E+10 | 0.471037E+10 | 0.604088E+10 | 0.373945E+10 | 0.230142E+10 | 0.00 | 0.00 |
March | 0.629098E+10 | 0.457681E+10 | 0.719711E+10 | 0.383946E+10 | 0.335765E+10 | 0.00 | 0.00 |
April | 0.608473E+10 | 0.362494E+10 | 0.735135E+10 | 0.319224E+10 | 0.415911E+10 | 0.00 | 0.00 |
May | 0.524801E+10 | 0.301710E+10 | 0.694441E+10 | 0.206812E+10 | 0.487629E+10 | 0.00 | 0.00 |
June | 0.446773E+10 | 0.229650E+10 | 0.614847E+10 | 0.165011E+10 | 0.449835E+10 | 0.00 | 0.00 |
July | 0.564053E+10 | 0.208738E+10 | 0.692849E+10 | 0.253680E+10 | 0.439169E+10 | 0.00 | 0.00 |
August | 0.699599E+10 | 0.199447E+10 | 0.744449E+10 | 0.347117E+10 | 0.397333E+10 | 0.00 | 0.00 |
September | 0.777320E+10 | 0.279595E+10 | 0.798525E+10 | 0.441083E+10 | 0.357441E+10 | 0.00 | 0.00 |
October | 0.723943E+10 | 0.397456E+10 | 0.747400E+10 | 0.461539E+10 | 0.285861E+10 | 0.00 | 0.00 |
November | 0.354124E+10 | 0.477879E+10 | 0.427434E+10 | 0.244918E+10 | 0.182515E+10 | 0.00 | 0.00 |
December | 0.406082E+10 | 0.602698E+10 | 0.462063E+10 | 0.298965E+10 | 0.163099E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.660526E+11 | 0.456794E+11 | 0.767569E+11 | 0.375434E+11 | 0.392135E+11 | 0.00 | 0.00 |
Minimum of Months | 0.340719E+10 | 0.199447E+10 | 0.427434E+10 | 0.165011E+10 | 0.163099E+10 | 0.00 | 0.00 |
Maximum of Months | 0.777320E+10 | 0.602698E+10 | 0.798525E+10 | 0.461539E+10 | 0.487629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261941E+09 | 0.455492E+10 | 0.111225E+10 | 0.328038E+09 | 0.784214E+09 | 0.00 | 0.00 |
February | 0.829568E+09 | 0.368941E+10 | 0.180115E+10 | 0.676970E+09 | 0.112418E+10 | 0.00 | 0.00 |
March | 0.167923E+10 | 0.345374E+10 | 0.279423E+10 | 0.943177E+09 | 0.185106E+10 | 0.00 | 0.00 |
April | 0.320324E+10 | 0.272426E+10 | 0.411405E+10 | 0.157307E+10 | 0.254099E+10 | 0.00 | 0.00 |
May | 0.496273E+10 | 0.212503E+10 | 0.546942E+10 | 0.222155E+10 | 0.324788E+10 | 0.00 | 0.00 |
June | 0.467044E+10 | 0.167235E+10 | 0.509026E+10 | 0.197592E+10 | 0.311434E+10 | 0.00 | 0.00 |
July | 0.675141E+10 | 0.158604E+10 | 0.649776E+10 | 0.341502E+10 | 0.308274E+10 | 0.00 | 0.00 |
August | 0.563607E+10 | 0.157071E+10 | 0.537592E+10 | 0.274499E+10 | 0.263092E+10 | 0.00 | 0.00 |
September | 0.404050E+10 | 0.201591E+10 | 0.423701E+10 | 0.203311E+10 | 0.220390E+10 | 0.00 | 0.00 |
October | 0.171441E+10 | 0.299804E+10 | 0.249242E+10 | 0.101553E+10 | 0.147689E+10 | 0.00 | 0.00 |
November | 0.388469E+09 | 0.385987E+10 | 0.120125E+10 | 0.338851E+09 | 0.862395E+09 | 0.00 | 0.00 |
December | 0.316945E+09 | 0.500111E+10 | 0.104358E+10 | 0.357672E+09 | 0.685907E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344550E+11 | 0.352514E+11 | 0.412293E+11 | 0.176239E+11 | 0.236054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261941E+09 | 0.157071E+10 | 0.104358E+10 | 0.328038E+09 | 0.685907E+09 | 0.00 | 0.00 |
Maximum of Months | 0.675141E+10 | 0.500111E+10 | 0.649776E+10 | 0.341502E+10 | 0.324788E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5243058.81 | 0.621859E+10 | 0.984313E+09 | 0.00 | 0.984313E+09 | 0.00 | 0.00 |
February | 0.132973E+09 | 0.500200E+10 | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.00 | 0.00 |
March | 0.563426E+09 | 0.451120E+10 | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.00 | 0.00 |
April | 0.144477E+10 | 0.340889E+10 | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.00 | 0.00 |
May | 0.247214E+10 | 0.279487E+10 | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.00 | 0.00 |
June | 0.274132E+10 | 0.204644E+10 | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.00 | 0.00 |
July | 0.310505E+10 | 0.188365E+10 | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.00 | 0.00 |
August | 0.271195E+10 | 0.186869E+10 | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.00 | 0.00 |
September | 0.146012E+10 | 0.272621E+10 | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.00 | 0.00 |
October | 0.503731E+09 | 0.393322E+10 | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.00 | 0.00 |
November | 64081001.97 | 0.496088E+10 | 0.107845E+10 | 0.00 | 0.107845E+10 | 0.00 | 0.00 |
December | 2212706.49 | 0.626717E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152070E+11 | 0.456218E+11 | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.00 | 0.00 |
Minimum of Months | 2212706.49 | 0.186869E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.310505E+10 | 0.626717E+10 | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217378E+09 | 0.387728E+10 | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.00 | 0.00 |
February | 0.799796E+09 | 0.303492E+10 | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.00 | 0.00 |
March | 0.185424E+10 | 0.274639E+10 | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.00 | 0.00 |
April | 0.360228E+10 | 0.209717E+10 | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.00 | 0.00 |
May | 0.414522E+10 | 0.177470E+10 | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.00 | 0.00 |
June | 0.525517E+10 | 0.133401E+10 | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.00 | 0.00 |
July | 0.529623E+10 | 0.118310E+10 | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.00 | 0.00 |
August | 0.550798E+10 | 0.114962E+10 | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.00 | 0.00 |
September | 0.343800E+10 | 0.165390E+10 | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.00 | 0.00 |
October | 0.179705E+10 | 0.239507E+10 | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.00 | 0.00 |
November | 0.413524E+09 | 0.304826E+10 | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.00 | 0.00 |
December | 0.282265E+09 | 0.390259E+10 | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.326091E+11 | 0.281970E+11 | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.217378E+09 | 0.114962E+10 | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550798E+10 | 0.390259E+10 | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.342132E+10 | 0.554084E+10 | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.00 | 0.00 |
February | 0.531449E+10 | 0.454085E+10 | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.00 | 0.00 |
March | 0.629242E+10 | 0.439040E+10 | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.00 | 0.00 |
April | 0.610440E+10 | 0.348068E+10 | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.00 | 0.00 |
May | 0.526747E+10 | 0.292256E+10 | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.00 | 0.00 |
June | 0.451224E+10 | 0.220038E+10 | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.00 | 0.00 |
July | 0.568435E+10 | 0.202479E+10 | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.00 | 0.00 |
August | 0.702548E+10 | 0.195960E+10 | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.00 | 0.00 |
September | 0.776307E+10 | 0.273344E+10 | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.00 | 0.00 |
October | 0.722229E+10 | 0.383717E+10 | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.00 | 0.00 |
November | 0.356831E+10 | 0.453361E+10 | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.00 | 0.00 |
December | 0.408816E+10 | 0.569984E+10 | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662640E+11 | 0.438642E+11 | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.342132E+10 | 0.195960E+10 | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.00 | 0.00 |
Maximum of Months | 0.776307E+10 | 0.569984E+10 | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.288668E+09 | 0.396999E+10 | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.00 | 0.00 |
February | 0.910361E+09 | 0.314433E+10 | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.00 | 0.00 |
March | 0.180850E+10 | 0.289362E+10 | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.00 | 0.00 |
April | 0.337469E+10 | 0.228858E+10 | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.00 | 0.00 |
May | 0.504169E+10 | 0.194898E+10 | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.00 | 0.00 |
June | 0.478869E+10 | 0.147501E+10 | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.00 | 0.00 |
July | 0.686556E+10 | 0.141161E+10 | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.00 | 0.00 |
August | 0.578916E+10 | 0.135367E+10 | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.00 | 0.00 |
September | 0.411297E+10 | 0.182840E+10 | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.00 | 0.00 |
October | 0.182153E+10 | 0.254536E+10 | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.00 | 0.00 |
November | 0.450936E+09 | 0.313180E+10 | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.00 | 0.00 |
December | 0.366002E+09 | 0.402950E+10 | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.356188E+11 | 0.300209E+11 | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288668E+09 | 0.135367E+10 | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.686556E+10 | 0.402950E+10 | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17735177.20 | 0.554567E+10 | 0.984313E+09 | 0.00 | 0.984313E+09 | 0.00 | 0.00 |
February | 0.180692E+09 | 0.445626E+10 | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.00 | 0.00 |
March | 0.663074E+09 | 0.406306E+10 | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.00 | 0.00 |
April | 0.153181E+10 | 0.315244E+10 | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.00 | 0.00 |
May | 0.252068E+10 | 0.263696E+10 | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.00 | 0.00 |
June | 0.275263E+10 | 0.197233E+10 | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.00 | 0.00 |
July | 0.310082E+10 | 0.182891E+10 | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.00 | 0.00 |
August | 0.271731E+10 | 0.179494E+10 | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.00 | 0.00 |
September | 0.150445E+10 | 0.254331E+10 | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.00 | 0.00 |
October | 0.596731E+09 | 0.351750E+10 | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.00 | 0.00 |
November | 94697873.03 | 0.435097E+10 | 0.107845E+10 | 0.00 | 0.107845E+10 | 0.00 | 0.00 |
December | 10614759.57 | 0.555365E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156913E+11 | 0.414160E+11 | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.00 | 0.00 |
Minimum of Months | 10614759.57 | 0.179494E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.310082E+10 | 0.555365E+10 | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243117E+09 | 0.351603E+10 | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.00 | 0.00 |
February | 0.861022E+09 | 0.276919E+10 | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.00 | 0.00 |
March | 0.191846E+10 | 0.253557E+10 | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.00 | 0.00 |
April | 0.364701E+10 | 0.197861E+10 | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.00 | 0.00 |
May | 0.416317E+10 | 0.170704E+10 | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.00 | 0.00 |
June | 0.524287E+10 | 0.130667E+10 | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.00 | 0.00 |
July | 0.527738E+10 | 0.117087E+10 | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.00 | 0.00 |
August | 0.549703E+10 | 0.112915E+10 | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.00 | 0.00 |
September | 0.345650E+10 | 0.157859E+10 | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.00 | 0.00 |
October | 0.185665E+10 | 0.220547E+10 | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.00 | 0.00 |
November | 0.449391E+09 | 0.275493E+10 | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.00 | 0.00 |
December | 0.311735E+09 | 0.352992E+10 | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.329243E+11 | 0.261820E+11 | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243117E+09 | 0.112915E+10 | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.00 | 0.00 |
Maximum of Months | 0.549703E+10 | 0.352992E+10 | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.353317E+10 | 0.499866E+10 | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.00 | 0.00 |
February | 0.544032E+10 | 0.413314E+10 | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.00 | 0.00 |
March | 0.637660E+10 | 0.403293E+10 | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.00 | 0.00 |
April | 0.617665E+10 | 0.326530E+10 | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.00 | 0.00 |
May | 0.531540E+10 | 0.278202E+10 | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.00 | 0.00 |
June | 0.452765E+10 | 0.212924E+10 | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.00 | 0.00 |
July | 0.568674E+10 | 0.197849E+10 | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.00 | 0.00 |
August | 0.703692E+10 | 0.189709E+10 | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.00 | 0.00 |
September | 0.780390E+10 | 0.258261E+10 | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.00 | 0.00 |
October | 0.730836E+10 | 0.351707E+10 | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.00 | 0.00 |
November | 0.366740E+10 | 0.409366E+10 | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.00 | 0.00 |
December | 0.419017E+10 | 0.514756E+10 | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.670633E+11 | 0.405578E+11 | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.353317E+10 | 0.189709E+10 | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.00 | 0.00 |
Maximum of Months | 0.780390E+10 | 0.514756E+10 | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306340E+09 | 0.363179E+10 | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.00 | 0.00 |
February | 0.950234E+09 | 0.290390E+10 | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.00 | 0.00 |
March | 0.185261E+10 | 0.268748E+10 | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.00 | 0.00 |
April | 0.341149E+10 | 0.216218E+10 | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.00 | 0.00 |
May | 0.506016E+10 | 0.186481E+10 | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.00 | 0.00 |
June | 0.478853E+10 | 0.142869E+10 | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.00 | 0.00 |
July | 0.685515E+10 | 0.137831E+10 | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.00 | 0.00 |
August | 0.579065E+10 | 0.131255E+10 | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.00 | 0.00 |
September | 0.413441E+10 | 0.173859E+10 | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.00 | 0.00 |
October | 0.186493E+10 | 0.235856E+10 | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.00 | 0.00 |
November | 0.476751E+09 | 0.287410E+10 | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.00 | 0.00 |
December | 0.384968E+09 | 0.370619E+10 | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358762E+11 | 0.280471E+11 | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.306340E+09 | 0.131255E+10 | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.685515E+10 | 0.370619E+10 | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.237080E+11 | -.379439E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130408E+10 | 68.28 | 0.00 | 0.00 |
February | 0.218746E+11 | -.347109E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.117131E+10 | 68.05 | 0.00 | 0.00 |
March | 0.262665E+11 | -.403759E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127099E+10 | 67.12 | 0.00 | 0.00 |
April | 0.217438E+11 | -.356279E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125012E+10 | 67.94 | 0.00 | 0.00 |
May | 0.222695E+11 | -.366241E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129466E+10 | 67.98 | 0.00 | 0.00 |
June | 0.210070E+11 | -.349534E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.124474E+10 | 67.68 | 0.00 | 0.00 |
July | 0.176898E+11 | -.323348E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131549E+10 | 68.81 | 0.00 | 0.00 |
August | 0.205824E+11 | -.350778E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128424E+10 | 67.63 | 0.00 | 0.00 |
September | 0.181467E+11 | -.322666E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.126247E+10 | 68.37 | 0.00 | 0.00 |
October | 0.198405E+11 | -.343371E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131142E+10 | 68.63 | 0.00 | 0.00 |
November | 0.211254E+11 | -.350192E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.126714E+10 | 68.57 | 0.00 | 0.00 |
December | 0.217682E+11 | -.361457E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130276E+10 | 68.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.256022E+12 | -.425417E+12 | 8760.00 | -.152794E+11 | 68.12 | |||||
Minimum of Months | 0.176898E+11 | -.403759E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.131549E+10 | 67.12 | 0.00 | 0.00 |
Maximum of Months | 0.262665E+11 | -.322666E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117131E+10 | 68.81 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214574E+10 | 475877.12 | 14-JAN-18:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158276E+10 | 442218.14 | 19-FEB-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894336E+09 | 257552.15 | 24-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169593E+09 | 70155.95 | 05-APR-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.456502E+09 | 473482.04 | 17-MAY-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103739E+10 | 444325.83 | 02-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386306E+09 | 258312.46 | 25-NOV-21:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297899E+09 | 76531.57 | 16-DEC-21:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.697053E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214574E+10 | 475877.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513645E+09 | 416488.95 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513645E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513645E+09 | 416488.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285827E+10 | 78743.43 | 02-JAN-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109415E+10 | 78681.55 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220971E+09 | 78678.46 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45416445.38 | 15764.91 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.541673E+09 | 79231.76 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138567E+10 | 78709.80 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.614615E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285827E+10 | 79231.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 69924121.07 | 1661.84 | 06-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20323156.17 | 1347.27 | 18-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 514010.17 | 162.60 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17736367.49 | 2934.03 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108498E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69924121.07 | 2934.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125942E+09 | 11002.54 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31602096.27 | 10981.55 | 21-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20144.77 | 33.57 | 06-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 219753.80 | 196.80 | 24-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17252196.57 | 4030.68 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175036E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125942E+09 | 11002.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.695139E+10 | 111936.97 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267358E+10 | 113330.15 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257588E+09 | 106700.71 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44788823.29 | 9534.75 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.750968E+09 | 107592.15 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331778E+10 | 115213.25 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139961E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.695139E+10 | 115213.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165058E+11 | 128009.77 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.851647E+10 | 128997.70 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266764E+10 | 127190.74 | 24-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680401E+09 | 83925.63 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143569E+09 | 18517.91 | 18-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8439813.57 | 3047.58 | 14-JUN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54635972.05 | 11123.18 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174776E+10 | 48340.87 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.651747E+10 | 126819.52 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127014E+11 | 127761.89 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495435E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165058E+11 | 128997.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115633E+11 | 181273.24 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466789E+10 | 180865.27 | 21-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112813E+10 | 173506.06 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.401980E+09 | 19870.19 | 18-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53819724.55 | 19927.42 | 18-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.438038E+09 | 18816.90 | 28-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316923E+10 | 178850.75 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.839008E+10 | 180903.94 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298125E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115633E+11 | 181273.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130204E+11 | 119429.63 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.619477E+10 | 119238.13 | 21-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170950E+10 | 71293.45 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.490117E+09 | 26082.28 | 18-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75751459.51 | 19306.39 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100579E+10 | 20491.90 | 31-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.429611E+10 | 117912.50 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.889678E+10 | 119251.47 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356892E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130204E+11 | 119429.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376933E+10 | 12938.51 | 02-JAN-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226380E+10 | 12900.39 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.884265E+09 | 12896.00 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321466E+09 | 12841.36 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34385579.33 | 12839.80 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 425030.31 | 224.67 | 14-JUN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8120797.38 | 1024.39 | 27-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424858E+09 | 12978.92 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147054E+10 | 13248.04 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295892E+10 | 12978.91 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121361E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376933E+10 | 13248.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388184E+10 | 15577.96 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237108E+10 | 15570.23 | 21-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114880E+10 | 15577.26 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.401310E+09 | 15532.35 | 11-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138456E+09 | 15529.43 | 18-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22422810.63 | 5850.35 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4034032.33 | 1139.03 | 05-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120840E+09 | 2937.71 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792315E+09 | 15566.36 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202469E+10 | 15693.47 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329179E+10 | 15579.49 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141976E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388184E+10 | 15693.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415547E+10 | 22219.07 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236351E+10 | 22207.06 | 21-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126921E+10 | 22217.98 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587327E+09 | 22153.88 | 11-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172954E+09 | 22150.05 | 18-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26901036.60 | 2322.45 | 15-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70643492.52 | 3387.86 | 18-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.703726E+09 | 22203.32 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210162E+10 | 22384.05 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343793E+10 | 22220.84 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148893E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415547E+10 | 22384.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336303E+10 | 15641.68 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201238E+10 | 15635.01 | 21-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107588E+10 | 15641.08 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.432934E+09 | 15594.40 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137838E+09 | 15592.92 | 18-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19876856.40 | 2420.79 | 14-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73697909.83 | 2795.62 | 19-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.705307E+09 | 15629.25 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174878E+10 | 15757.00 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273477E+10 | 15629.22 | 16-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123045E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336303E+10 | 15757.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111508E+10 | 247916.09 | 01-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227985E+09 | 248162.97 | 24-FEB-04:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.594907E+09 | 248170.81 | 11-MAR-04:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.314828E+09 | 248084.67 | 14-APR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.384421E+09 | 248138.11 | 29-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.689084E+09 | 248157.90 | 18-JUN-20:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123039E+10 | 248145.21 | 09-JUL-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.788330E+09 | 248163.99 | 27-AUG-23:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183770E+10 | 248174.32 | 24-SEP-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.666503E+09 | 248160.29 | 08-OCT-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778487E+09 | 248165.09 | 05-NOV-14:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.916559E+09 | 247837.25 | 18-DEC-01:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954427E+10 | |||||||
Minimum of Months | 0.227985E+09 | 247837.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183770E+10 | 248174.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178835E+11 | 55066.74 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111919E+11 | 49750.42 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398066E+10 | 35555.39 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138063E+10 | 23490.39 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.969101E+09 | 19505.99 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13784154.80 | 3549.35 | 13-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122784E+09 | 10035.04 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109439E+10 | 16389.17 | 31-OCT-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511723E+10 | 26490.33 | 22-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100926E+11 | 37933.07 | 21-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518466E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178835E+11 | 55066.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334042E+12 | 545638.63 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221528E+12 | 537369.06 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127703E+12 | 488988.25 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.736444E+11 | 401417.34 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.302170E+11 | 292645.68 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588505E+10 | 158404.73 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38188375.91 | 25497.28 | 03-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.552904E+09 | 54972.10 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.822796E+10 | 199937.23 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.501016E+11 | 279077.88 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155306E+12 | 466387.78 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272592E+12 | 535317.99 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127984E+13 | |||||||
Minimum of Months | 38188375.91 | 25497.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334042E+12 | 545638.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426602E+11 | 56819.44 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305521E+11 | 55960.59 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216804E+11 | 53007.08 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120676E+11 | 43760.46 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.487900E+10 | 32293.43 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106737E+10 | 18155.82 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69249604.88 | 7903.76 | 03-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153761E+09 | 10504.85 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170424E+10 | 22585.28 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.959741E+10 | 31017.17 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252504E+11 | 50692.58 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.385100E+11 | 56763.55 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188192E+12 | |||||||
Minimum of Months | 69249604.88 | 7903.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.426602E+11 | 56819.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3984460.85 | 3984460.85 | 10846.93 | 11-JAN-05:31 | 10846.93 | 0.00 |
February | 0.00 | 0.00 | 0.588433E+09 | 0.572271E+09 | 56367.39 | 24-FEB-04:01 | 35172.64 | 0.00 |
March | 0.00 | 0.00 | 0.225917E+09 | 0.199267E+09 | 43620.57 | 10-MAR-04:01 | 21424.79 | 0.01 |
April | 0.00 | 0.00 | 0.448185E+10 | 0.446718E+10 | 63153.74 | 27-APR-16:00 | 63153.74 | 0.03 |
May | 0.00 | 0.00 | 0.850880E+10 | 0.847369E+10 | 62121.67 | 15-MAY-16:00 | 62121.67 | 0.10 |
June | 0.00 | 0.00 | 0.178197E+11 | 0.177114E+11 | 91785.21 | 11-JUN-18:10 | 75646.40 | 0.20 |
July | 0.00 | 0.00 | 0.327933E+11 | 0.324019E+11 | 122933.45 | 30-JUL-15:47 | 109837.65 | 0.34 |
August | 0.00 | 0.00 | 0.448794E+11 | 0.441011E+11 | 126689.44 | 13-AUG-14:10 | 104583.12 | 0.43 |
September | 0.00 | 0.00 | 0.144469E+11 | 0.140425E+11 | 84358.94 | 24-SEP-16:55 | 45294.57 | 0.22 |
October | 0.00 | 0.00 | 0.228286E+10 | 0.222410E+10 | 70369.92 | 01-OCT-16:06 | 50302.71 | 0.02 |
November | 0.00 | 0.00 | 0.396599E+09 | 0.363901E+09 | 65066.81 | 05-NOV-14:28 | 44378.07 | 0.01 |
December | 0.00 | 0.00 | 9859750.10 | 9303379.80 | 19746.33 | 16-DEC-06:02 | 15106.94 | 0.00 |
Annual Sum or Average | 0.126438E+12 | 0.124571E+12 | 0.11 | |||||
Minimum of Months | 0.00 | 0.00 | 3984460.85 | 3984460.85 | 10846.93 | 10846.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.448794E+11 | 0.441011E+11 | 126689.44 | 109837.65 | 0.43 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 34310074.65 | 34310074.65 | 4599.66 | 11-JAN-14:00 | 4599.66 | 0.00 |
February | 0.00 | 0.00 | 0.117129E+10 | 0.117129E+10 | 62144.12 | 27-FEB-15:00 | 62144.12 | 0.02 |
March | 0.00 | 0.00 | 0.198274E+10 | 0.198274E+10 | 36040.64 | 14-MAR-16:00 | 36040.64 | 0.02 |
April | 0.00 | 0.00 | 0.122473E+11 | 0.122360E+11 | 116003.33 | 27-APR-15:00 | 112754.36 | 0.06 |
May | 0.00 | 0.00 | 0.207189E+11 | 0.202543E+11 | 96100.40 | 05-MAY-15:50 | 85234.94 | 0.17 |
June | 0.00 | 0.00 | 0.377346E+11 | 0.375015E+11 | 103840.93 | 28-JUN-16:00 | 103840.93 | 0.34 |
July | 0.00 | 0.00 | 0.676698E+11 | 0.629496E+11 | 138686.01 | 31-JUL-16:00 | 119963.71 | 0.54 |
August | 0.00 | 0.00 | 0.925483E+11 | 0.830975E+11 | 152130.83 | 29-AUG-14:30 | 129504.46 | 0.67 |
September | 0.00 | 0.00 | 0.329717E+11 | 0.301140E+11 | 118407.21 | 14-SEP-13:00 | 81348.92 | 0.37 |
October | 0.00 | 0.00 | 0.687370E+10 | 0.686421E+10 | 77441.42 | 04-OCT-15:00 | 77441.42 | 0.06 |
November | 0.00 | 0.00 | 0.109673E+10 | 0.101221E+10 | 47582.21 | 04-NOV-13:10 | 40090.63 | 0.03 |
December | 0.00 | 0.00 | 2911.09 | 2911.09 | 0.73 | 26-DEC-06:30 | 0.73 | 0.00 |
Annual Sum or Average | 0.275049E+12 | 0.257217E+12 | 0.19 | |||||
Minimum of Months | 0.00 | 0.00 | 2911.09 | 2911.09 | 0.73 | 0.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.925483E+11 | 0.830975E+11 | 152130.83 | 129504.46 | 0.67 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.244112E+09 | 0.244112E+09 | 31282.54 | 11-JAN-14:00 | 31282.54 | 0.01 |
February | 0.00 | 0.00 | 0.867428E+10 | 0.867428E+10 | 471940.03 | 27-FEB-15:00 | 471940.03 | 0.02 |
March | 0.00 | 0.00 | 0.153008E+11 | 0.153008E+11 | 328398.51 | 18-MAR-14:00 | 328398.51 | 0.02 |
April | 0.00 | 0.00 | 0.919810E+11 | 0.919742E+11 | 987527.20 | 27-APR-15:00 | 976315.06 | 0.05 |
May | 0.00 | 0.00 | 0.181430E+12 | 0.177320E+12 | 885337.96 | 05-MAY-16:00 | 781465.15 | 0.17 |
June | 0.00 | 0.00 | 0.313111E+12 | 0.311622E+12 | 934919.74 | 28-JUN-16:00 | 934919.74 | 0.33 |
July | 0.00 | 0.00 | 0.539568E+12 | 0.502148E+12 | 1222587.30 | 31-JUL-16:00 | 1043756.67 | 0.47 |
August | 0.00 | 0.00 | 0.719599E+12 | 0.646265E+12 | 1361318.42 | 29-AUG-14:30 | 1144739.13 | 0.56 |
September | 0.00 | 0.00 | 0.295276E+12 | 0.268997E+12 | 1123278.40 | 14-SEP-13:00 | 770191.41 | 0.37 |
October | 0.00 | 0.00 | 0.547954E+11 | 0.547779E+11 | 698642.39 | 04-OCT-15:00 | 698642.39 | 0.06 |
November | 0.00 | 0.00 | 0.940125E+10 | 0.860057E+10 | 456183.27 | 04-NOV-13:20 | 388078.55 | 0.02 |
December | 0.00 | 0.00 | 16326.01 | 16326.01 | 2.10 | 26-DEC-07:00 | 2.10 | 0.00 |
Annual Sum or Average | 0.222938E+13 | 0.208592E+13 | 0.17 | |||||
Minimum of Months | 0.00 | 0.00 | 16326.01 | 16326.01 | 2.10 | 2.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.719599E+12 | 0.646265E+12 | 1361318.42 | 1144739.13 | 0.56 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15751297.84 | 15751297.84 | 2102.76 | 11-JAN-16:00 | 2102.76 | 0.00 |
February | 0.00 | 0.00 | 0.704445E+09 | 0.704445E+09 | 37099.85 | 27-FEB-15:00 | 37099.85 | 0.02 |
March | 0.00 | 0.00 | 0.140348E+10 | 0.140348E+10 | 32098.87 | 18-MAR-14:00 | 32098.87 | 0.02 |
April | 0.00 | 0.00 | 0.954483E+10 | 0.953831E+10 | 118516.36 | 27-APR-15:00 | 115863.47 | 0.05 |
May | 0.00 | 0.00 | 0.189956E+11 | 0.185670E+11 | 95882.58 | 05-MAY-16:00 | 84792.28 | 0.16 |
June | 0.00 | 0.00 | 0.337042E+11 | 0.335561E+11 | 114454.77 | 28-JUN-16:00 | 114454.77 | 0.31 |
July | 0.00 | 0.00 | 0.589091E+11 | 0.547200E+11 | 149781.52 | 27-JUL-15:50 | 111155.70 | 0.46 |
August | 0.00 | 0.00 | 0.771155E+11 | 0.693817E+11 | 155878.10 | 29-AUG-14:40 | 133443.63 | 0.54 |
September | 0.00 | 0.00 | 0.296646E+11 | 0.269983E+11 | 120046.67 | 14-SEP-13:00 | 82230.50 | 0.35 |
October | 0.00 | 0.00 | 0.492514E+10 | 0.492514E+10 | 69720.97 | 04-OCT-15:00 | 69720.97 | 0.05 |
November | 0.00 | 0.00 | 0.898293E+09 | 0.821788E+09 | 44594.61 | 04-NOV-13:30 | 38549.29 | 0.02 |
December | 0.00 | 0.00 | 13.92 | 13.92 | 0.23 | 04-DEC-04:01 | 0.23 | 0.00 |
Annual Sum or Average | 0.235881E+12 | 0.220632E+12 | 0.17 | |||||
Minimum of Months | 0.00 | 0.00 | 13.92 | 13.92 | 0.23 | 0.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.771155E+11 | 0.693817E+11 | 155878.10 | 133443.63 | 0.54 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.312706E+12 | 0.312644E+12 | 434407.81 | 26-JAN-23:00 | 434407.81 | 0.00 |
February | 0.00 | 0.00 | 0.494935E+12 | 0.494886E+12 | 439317.27 | 19-FEB-10:10 | 439317.27 | 0.00 |
March | 0.00 | 0.00 | 0.785281E+12 | 0.785218E+12 | 426812.71 | 25-MAR-22:57 | 425949.21 | 0.00 |
April | 0.00 | 0.00 | 0.990033E+12 | 0.990033E+12 | 417899.90 | 13-APR-03:20 | 417899.90 | 0.00 |
May | 0.00 | 0.00 | 0.317476E+12 | 0.317304E+12 | 434241.30 | 17-MAY-22:00 | 434241.30 | 0.00 |
June | 0.00 | 0.00 | 0.535600E+12 | 0.535486E+12 | 210130.71 | 28-JUN-16:00 | 210130.71 | 0.00 |
July | 0.00 | 0.00 | 0.792148E+12 | 0.790934E+12 | 300602.63 | 31-JUL-16:00 | 298871.74 | 0.00 |
August | 0.00 | 0.00 | 0.102820E+13 | 0.102700E+13 | 393021.08 | 29-AUG-19:30 | 387153.74 | 0.00 |
September | 0.00 | 0.00 | 0.309725E+12 | 0.308703E+12 | 136338.77 | 01-SEP-00:08 | 135207.15 | 0.00 |
October | 0.00 | 0.00 | 0.553159E+12 | 0.553101E+12 | 434675.28 | 02-OCT-04:14 | 434675.28 | 0.00 |
November | 0.00 | 0.00 | 0.761196E+12 | 0.761054E+12 | 425801.03 | 25-NOV-21:16 | 425801.03 | 0.00 |
December | 0.00 | 0.00 | 0.102111E+13 | 0.102111E+13 | 420807.44 | 09-DEC-20:23 | 420807.44 | 0.00 |
Annual Sum or Average | 0.790157E+13 | 0.789747E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.309725E+12 | 0.308703E+12 | 136338.77 | 135207.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102820E+13 | 0.102700E+13 | 439317.27 | 439317.27 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.465749E+10 | 0.465749E+10 | 2376.91 | 05-JAN-16:10 | 2376.91 | 0.00 |
February | 0.00 | 0.00 | 0.901158E+10 | 0.901158E+10 | 4387.05 | 07-FEB-16:50 | 4387.05 | 0.00 |
March | 0.00 | 0.00 | 0.152089E+11 | 0.152089E+11 | 6375.73 | 14-MAR-17:10 | 6375.73 | 0.00 |
April | 0.00 | 0.00 | 0.196277E+11 | 0.196277E+11 | 8342.16 | 26-APR-18:20 | 8342.16 | 0.00 |
May | 0.00 | 0.00 | 0.560781E+10 | 0.560781E+10 | 2989.24 | 29-MAY-18:23 | 2989.24 | 0.00 |
June | 0.00 | 0.00 | 0.102829E+11 | 0.102829E+11 | 4701.02 | 18-JUN-18:50 | 4701.02 | 0.00 |
July | 0.00 | 0.00 | 0.156089E+11 | 0.156089E+11 | 6982.48 | 30-JUL-18:37 | 6982.48 | 0.00 |
August | 0.00 | 0.00 | 0.204040E+11 | 0.204040E+11 | 8423.63 | 06-AUG-19:33 | 8423.63 | 0.00 |
September | 0.00 | 0.00 | 0.545966E+10 | 0.545966E+10 | 2869.04 | 10-SEP-17:30 | 2869.04 | 0.00 |
October | 0.00 | 0.00 | 0.103685E+11 | 0.103685E+11 | 4698.85 | 03-OCT-16:50 | 4698.85 | 0.00 |
November | 0.00 | 0.00 | 0.146631E+11 | 0.146631E+11 | 6157.62 | 12-NOV-15:50 | 6157.62 | 0.00 |
December | 0.00 | 0.00 | 0.199516E+11 | 0.199516E+11 | 7980.85 | 05-DEC-15:50 | 7980.85 | 0.00 |
Annual Sum or Average | 0.150852E+12 | 0.150852E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.465749E+10 | 0.465749E+10 | 2376.91 | 2376.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204040E+11 | 0.204040E+11 | 8423.63 | 8423.63 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.271649E+11 | 0.271649E+11 | 20423.07 | 05-JAN-16:20 | 20423.07 | 0.00 |
February | 0.00 | 0.00 | 0.728070E+11 | 0.728070E+11 | 40477.33 | 08-FEB-16:50 | 40477.33 | 0.00 |
March | 0.00 | 0.00 | 0.134523E+12 | 0.134523E+12 | 59832.26 | 14-MAR-17:10 | 59832.26 | 0.00 |
April | 0.00 | 0.00 | 0.180149E+12 | 0.180149E+12 | 79483.35 | 26-APR-18:20 | 79483.35 | 0.00 |
May | 0.00 | 0.00 | 0.475763E+11 | 0.475763E+11 | 27281.63 | 29-MAY-18:24 | 27281.63 | 0.00 |
June | 0.00 | 0.00 | 0.933970E+11 | 0.933970E+11 | 43838.91 | 22-JUN-18:50 | 43838.91 | 0.00 |
July | 0.00 | 0.00 | 0.145997E+12 | 0.145997E+12 | 64960.28 | 30-JUL-18:37 | 64960.28 | 0.00 |
August | 0.00 | 0.00 | 0.192146E+12 | 0.192146E+12 | 79865.20 | 06-AUG-19:14 | 79865.20 | 0.00 |
September | 0.00 | 0.00 | 0.466675E+11 | 0.466675E+11 | 26373.75 | 08-SEP-17:30 | 26373.75 | 0.00 |
October | 0.00 | 0.00 | 0.892143E+11 | 0.892143E+11 | 44132.61 | 03-OCT-16:50 | 44132.61 | 0.00 |
November | 0.00 | 0.00 | 0.126611E+12 | 0.126611E+12 | 56094.36 | 10-NOV-16:10 | 56094.36 | 0.00 |
December | 0.00 | 0.00 | 0.173900E+12 | 0.173900E+12 | 73722.69 | 05-DEC-16:00 | 73722.69 | 0.00 |
Annual Sum or Average | 0.133015E+13 | 0.133015E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.271649E+11 | 0.271649E+11 | 20423.07 | 20423.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192146E+12 | 0.192146E+12 | 79865.20 | 79865.20 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122828E+10 | 0.122828E+10 | 1901.82 | 05-JAN-16:20 | 1901.82 | 0.00 |
February | 0.00 | 0.00 | 0.568990E+10 | 0.568990E+10 | 3954.12 | 08-FEB-16:50 | 3954.12 | 0.00 |
March | 0.00 | 0.00 | 0.122525E+11 | 0.122525E+11 | 6001.20 | 14-MAR-17:10 | 6001.20 | 0.00 |
April | 0.00 | 0.00 | 0.172896E+11 | 0.172896E+11 | 8046.69 | 26-APR-18:10 | 8046.69 | 0.00 |
May | 0.00 | 0.00 | 0.428949E+10 | 0.428949E+10 | 2862.42 | 07-MAY-18:12 | 2862.42 | 0.00 |
June | 0.00 | 0.00 | 0.913066E+10 | 0.913066E+10 | 4553.73 | 18-JUN-18:34 | 4553.73 | 0.00 |
July | 0.00 | 0.00 | 0.144797E+11 | 0.144797E+11 | 6689.71 | 30-JUL-18:29 | 6689.71 | 0.00 |
August | 0.00 | 0.00 | 0.190516E+11 | 0.190516E+11 | 8125.42 | 06-AUG-19:12 | 8125.42 | 0.00 |
September | 0.00 | 0.00 | 0.417364E+10 | 0.417364E+10 | 2706.92 | 08-SEP-17:30 | 2706.92 | 0.00 |
October | 0.00 | 0.00 | 0.785676E+10 | 0.785676E+10 | 4441.82 | 04-OCT-16:50 | 4441.82 | 0.00 |
November | 0.00 | 0.00 | 0.111704E+11 | 0.111704E+11 | 5508.06 | 10-NOV-16:10 | 5508.06 | 0.00 |
December | 0.00 | 0.00 | 0.154602E+11 | 0.154602E+11 | 7214.67 | 05-DEC-16:00 | 7214.67 | 0.00 |
Annual Sum or Average | 0.122073E+12 | 0.122073E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.122828E+10 | 0.122828E+10 | 1901.82 | 1901.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190516E+11 | 0.190516E+11 | 8125.42 | 8125.42 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6950.14 | 37526.89 | 01-JAN-08:11 | 13188.29 | 52064.82 | 31-JAN-12:30 |
February | 6572.43 | 37475.12 | 26-FEB-08:40 | 13405.13 | 52127.41 | 10-FEB-12:30 |
March | 5340.53 | 37533.81 | 26-MAR-07:30 | 14305.43 | 51930.82 | 01-MAR-12:30 |
April | 6413.32 | 37664.84 | 30-APR-07:12 | 12765.46 | 50811.95 | 03-APR-11:20 |
May | 6331.77 | 37790.97 | 29-MAY-07:00 | 12712.76 | 49257.52 | 01-MAY-11:50 |
June | 5736.37 | 37893.86 | 25-JUN-06:57 | 12479.64 | 47350.50 | 01-JUN-11:50 |
July | 7390.71 | 37970.63 | 30-JUL-06:50 | 10874.80 | 45738.62 | 03-JUL-11:50 |
August | 5714.84 | 37977.34 | 13-AUG-06:50 | 12135.74 | 45093.88 | 31-AUG-12:00 |
September | 6702.31 | 37959.85 | 03-SEP-07:10 | 11302.24 | 46054.12 | 29-SEP-11:40 |
October | 7235.81 | 37889.69 | 01-OCT-07:10 | 11701.82 | 47799.92 | 31-OCT-11:40 |
November | 7251.11 | 37751.04 | 05-NOV-07:20 | 12482.40 | 49639.78 | 30-NOV-12:40 |
December | 7062.26 | 37630.11 | 03-DEC-08:30 | 12464.96 | 51138.69 | 29-DEC-12:50 |
Annual Sum or Average | 6558.71 | 12479.82 | ||||
Minimum of Months | 5340.53 | 37475.12 | 10874.80 | 45093.88 | ||
Maximum of Months | 7390.71 | 37977.34 | 14305.43 | 52127.41 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 171051.93 | 1074027.61 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 121308.45 | 935008.24 | 27-FEB-02:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 60951.46 | 810964.65 | 10-MAR-04:47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34659.37 | 837704.34 | 23-APR-17:48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13873.68 | 837767.38 | 29-MAY-01:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3009.11 | 774923.24 | 04-JUN-15:46 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 536.41 | 399019.13 | 02-JUL-14:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 549.64 | 564960.33 | 06-AUG-14:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 4497.46 | 732854.51 | 24-SEP-14:36 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25279.16 | 827967.20 | 01-OCT-16:04 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 79909.51 | 901421.44 | 05-NOV-14:26 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 136392.19 | 1050997.27 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 54045.39 | ||||
Minimum of Months | 0.00 | 0.00 | 536.41 | 399019.13 | ||
Maximum of Months | 0.00 | 0.00 | 171051.93 | 1074027.61 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 370.62 | 86139.88 | 11-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9513.22 | 1113191.69 | 27-FEB-14:50 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 15039.94 | 796220.06 | 18-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 75307.64 | 1299392.55 | 27-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 151603.56 | 1363553.79 | 04-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 268324.39 | 1347468.10 | 22-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 398992.99 | 1599168.96 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 481766.98 | 1758699.46 | 29-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 232728.73 | 1424482.66 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 50155.94 | 1114380.17 | 03-OCT-15:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9527.08 | 1106574.10 | 04-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 154.96 | 57532.12 | 16-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 142146.96 | 0.00 | ||||
Minimum of Months | 154.96 | 57532.12 | 0.00 | 0.00 | ||
Maximum of Months | 481766.98 | 1758699.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 85.72 | 37827.72 | 11-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5246.47 | 711632.66 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 7829.90 | 444709.90 | 18-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 51361.62 | 1296315.41 | 27-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 99760.15 | 1372065.63 | 04-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 182845.30 | 1347322.22 | 22-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 300826.16 | 1595949.54 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 390172.18 | 1755507.75 | 29-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 164604.13 | 1422308.11 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 29541.14 | 1052575.72 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5242.07 | 676751.56 | 04-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.17 | 34622.27 | 16-DEC-06:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 103954.49 | 0.00 | ||||
Minimum of Months | 7.17 | 34622.27 | 0.00 | 0.00 | ||
Maximum of Months | 390172.18 | 1755507.75 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 160737.84 | 547466.12 | 26-JAN-23:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 299357.24 | 582798.51 | 28-FEB-22:41 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 441717.19 | 759354.16 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 622401.05 | 1346274.31 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 201815.05 | 597329.47 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 387213.69 | 898901.02 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 631171.34 | 1326309.72 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 883173.30 | 1592781.47 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 213796.42 | 605885.88 | 14-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 313787.14 | 631510.14 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 439478.30 | 787541.54 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 568936.27 | 614517.80 | 13-DEC-04:52 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 431534.71 | 0.00 | ||||
Minimum of Months | 160737.84 | 547466.12 | 0.00 | 0.00 | ||
Maximum of Months | 883173.30 | 1592781.47 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25.22 | 31650.98 | 11-JAN-16:10 | 194.06 | 59734.23 | 01-JAN-11:42 |
February | 6647.81 | 967372.06 | 27-FEB-14:50 | 272.62 | 66712.64 | 16-FEB-06:40 |
March | 11333.94 | 570765.32 | 18-MAR-14:20 | 197.28 | 55898.88 | 04-MAR-06:50 |
April | 65814.15 | 2254929.50 | 27-APR-15:00 | 473.97 | 64566.78 | 01-APR-05:30 |
May | 124106.01 | 2111575.96 | 05-MAY-15:10 | 413.64 | 60761.33 | 10-MAY-05:40 |
June | 217558.13 | 1868740.14 | 22-JUN-15:30 | 370.17 | 43658.27 | 13-JUN-16:30 |
July | 388856.90 | 3742803.09 | 31-JUL-16:00 | 265.94 | 50657.67 | 03-JUL-08:30 |
August | 584702.50 | 4442070.85 | 29-AUG-13:10 | 240.11 | 40105.41 | 19-AUG-07:00 |
September | 214025.51 | 2736270.67 | 14-SEP-13:00 | 341.37 | 45387.31 | 11-SEP-05:50 |
October | 36900.05 | 968893.39 | 03-OCT-15:30 | 421.56 | 70952.48 | 11-OCT-06:00 |
November | 6643.17 | 970011.31 | 04-NOV-13:20 | 234.25 | 76576.96 | 21-NOV-04:01 |
December | 8.49 | 17338.30 | 26-DEC-06:30 | 209.84 | 77114.69 | 21-DEC-06:30 |
Annual Sum or Average | 139263.82 | 302.58 | ||||
Minimum of Months | 8.49 | 17338.30 | 194.06 | 40105.41 | ||
Maximum of Months | 584702.50 | 4442070.85 | 473.97 | 77114.69 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171527E+11 | 0.91 | 10847.22 | 01-JAN-00:20 | 1.54 |
February | 0.155970E+11 | 0.91 | 10847.22 | 01-FEB-04:01 | 1.53 |
March | 0.183492E+11 | 0.97 | 10847.22 | 01-MAR-04:01 | 1.54 |
April | 0.172674E+11 | 0.94 | 10847.22 | 01-APR-03:01 | 1.54 |
May | 0.183464E+11 | 0.97 | 10847.22 | 01-MAY-00:10 | 1.53 |
June | 0.182660E+11 | 0.99 | 10847.22 | 01-JUN-03:01 | 1.53 |
July | 0.182357E+11 | 0.96 | 10847.22 | 01-JUL-03:01 | 1.53 |
August | 0.191676E+11 | 1.01 | 10847.22 | 01-AUG-03:01 | 1.53 |
September | 0.182125E+11 | 0.99 | 10847.22 | 01-SEP-03:01 | 1.53 |
October | 0.184159E+11 | 0.97 | 10847.22 | 01-OCT-16:04 | 1.53 |
November | 0.178404E+11 | 0.97 | 10847.22 | 01-NOV-03:01 | 1.53 |
December | 0.176821E+11 | 0.93 | 10847.22 | 01-DEC-04:01 | 1.54 |
Annual Sum or Average | 0.214533E+12 | 0.96 | |||
Minimum of Months | 0.155970E+11 | 0.91 | 10847.22 | 1.53 | |
Maximum of Months | 0.191676E+11 | 1.01 | 10847.22 | 1.54 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.542117E+10 | 0.36 | 12384.96 | 02-JAN-06:03 | 1.31 |
February | 0.587467E+10 | 0.40 | 12611.52 | 28-FEB-04:01 | 1.33 |
March | 0.851694E+10 | 0.48 | 14611.38 | 11-MAR-04:01 | 1.46 |
April | 0.888231E+10 | 0.51 | 18530.47 | 03-APR-05:03 | 1.69 |
May | 0.712797E+10 | 0.44 | 20522.20 | 05-MAY-05:01 | 1.81 |
June | 0.742700E+10 | 0.47 | 21810.55 | 12-JUN-05:03 | 1.87 |
July | 0.777165E+10 | 0.49 | 20787.96 | 24-JUL-05:03 | 1.82 |
August | 0.888197E+10 | 0.55 | 18530.47 | 01-AUG-05:01 | 1.69 |
September | 0.661995E+10 | 0.43 | 18530.47 | 02-SEP-05:01 | 1.69 |
October | 0.737493E+10 | 0.44 | 16468.31 | 10-OCT-05:03 | 1.57 |
November | 0.714099E+10 | 0.43 | 17262.82 | 06-NOV-06:03 | 1.62 |
December | 0.730435E+10 | 0.43 | 15433.54 | 04-DEC-04:01 | 1.52 |
Annual Sum or Average | 0.883439E+11 | 0.45 | |||
Minimum of Months | 0.542117E+10 | 0.36 | 12384.96 | 1.31 | |
Maximum of Months | 0.888231E+10 | 0.55 | 21810.55 | 1.87 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.365748E+11 | 0.32 | 151440.81 | 13-JAN-06:01 | 1.58 |
February | 0.385671E+11 | 0.34 | 151440.81 | 14-FEB-06:01 | 1.58 |
March | 0.527971E+11 | 0.38 | 137047.02 | 06-MAR-06:01 | 1.48 |
April | 0.506551E+11 | 0.38 | 109115.87 | 01-APR-05:01 | 1.28 |
May | 0.555988E+11 | 0.40 | 127479.36 | 15-MAY-05:02 | 1.41 |
June | 0.552477E+11 | 0.41 | 128441.36 | 21-JUN-05:01 | 1.41 |
July | 0.539166E+11 | 0.39 | 180627.19 | 31-JUL-05:01 | 1.75 |
August | 0.598770E+11 | 0.42 | 202971.45 | 14-AUG-05:01 | 1.88 |
September | 0.538242E+11 | 0.39 | 109115.87 | 01-SEP-04:02 | 1.27 |
October | 0.506007E+11 | 0.36 | 109115.87 | 02-OCT-04:03 | 1.28 |
November | 0.418994E+11 | 0.34 | 151440.81 | 30-NOV-06:01 | 1.58 |
December | 0.395189E+11 | 0.32 | 151440.81 | 09-DEC-06:01 | 1.58 |
Annual Sum or Average | 0.589077E+12 | 0.37 | |||
Minimum of Months | 0.365748E+11 | 0.32 | 109115.87 | 1.27 | |
Maximum of Months | 0.598770E+11 | 0.42 | 202971.45 | 1.88 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355375E+10 | 0.35 | 4957.71 | 02-JAN-04:11 | 0.79 |
February | 0.318939E+10 | 0.33 | 4957.71 | 06-FEB-06:02 | 0.79 |
March | 0.389927E+10 | 0.34 | 5735.68 | 17-MAR-15:40 | 0.85 |
April | 0.410713E+10 | 0.33 | 9886.59 | 05-APR-05:01 | 1.17 |
May | 0.488681E+10 | 0.36 | 11124.78 | 05-MAY-05:01 | 1.25 |
June | 0.523824E+10 | 0.38 | 11011.45 | 21-JUN-05:01 | 1.24 |
July | 0.546035E+10 | 0.38 | 14093.57 | 20-JUL-05:01 | 1.45 |
August | 0.595969E+10 | 0.41 | 13972.07 | 14-AUG-05:01 | 1.44 |
September | 0.456762E+10 | 0.35 | 12736.80 | 14-SEP-05:01 | 1.36 |
October | 0.372419E+10 | 0.31 | 9886.59 | 04-OCT-05:01 | 1.17 |
November | 0.312280E+10 | 0.30 | 4957.71 | 13-NOV-05:01 | 0.79 |
December | 0.318324E+10 | 0.31 | 4957.71 | 04-DEC-06:01 | 0.79 |
Annual Sum or Average | 0.508925E+11 | 0.35 | |||
Minimum of Months | 0.312280E+10 | 0.30 | 4957.71 | 0.79 | |
Maximum of Months | 0.595969E+10 | 0.41 | 14093.57 | 1.45 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.957972E+11 | 1.37 | 35766.56 | 01-JAN-00:05 | 1.37 |
February | 0.865265E+11 | 1.37 | 35766.56 | 01-FEB-00:01 | 1.37 |
March | 0.957972E+11 | 1.37 | 35766.56 | 01-MAR-00:01 | 1.37 |
April | 0.927069E+11 | 1.37 | 35766.56 | 01-APR-00:10 | 1.37 |
May | 0.957972E+11 | 1.37 | 35766.56 | 01-MAY-00:10 | 1.37 |
June | 0.927069E+11 | 1.37 | 35766.56 | 01-JUN-00:20 | 1.37 |
July | 0.957972E+11 | 1.37 | 35766.56 | 01-JUL-00:10 | 1.37 |
August | 0.957972E+11 | 1.37 | 35766.56 | 01-AUG-00:05 | 1.37 |
September | 0.927069E+11 | 1.37 | 35766.56 | 01-SEP-00:05 | 1.37 |
October | 0.957972E+11 | 1.37 | 35766.56 | 01-OCT-00:10 | 1.37 |
November | 0.927069E+11 | 1.37 | 35766.56 | 01-NOV-00:10 | 1.37 |
December | 0.957972E+11 | 1.37 | 35766.56 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112793E+13 | 1.37 | |||
Minimum of Months | 0.865265E+11 | 1.37 | 35766.56 | 1.37 | |
Maximum of Months | 0.957972E+11 | 1.37 | 35766.56 | 1.37 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149781E+10 | 0.93 | 559.22 | 01-JAN-00:05 | 0.93 |
February | 0.135286E+10 | 0.93 | 559.22 | 01-FEB-00:01 | 0.93 |
March | 0.149781E+10 | 0.93 | 559.22 | 01-MAR-00:01 | 0.93 |
April | 0.144949E+10 | 0.93 | 559.22 | 01-APR-00:10 | 0.93 |
May | 0.149781E+10 | 0.93 | 559.22 | 01-MAY-00:10 | 0.93 |
June | 0.144949E+10 | 0.93 | 559.22 | 01-JUN-00:10 | 0.93 |
July | 0.149781E+10 | 0.93 | 559.22 | 01-JUL-00:10 | 0.93 |
August | 0.149781E+10 | 0.93 | 559.22 | 01-AUG-00:05 | 0.93 |
September | 0.144949E+10 | 0.93 | 559.22 | 01-SEP-00:03 | 0.93 |
October | 0.149781E+10 | 0.93 | 559.22 | 01-OCT-00:10 | 0.93 |
November | 0.144949E+10 | 0.93 | 559.22 | 01-NOV-00:10 | 0.93 |
December | 0.149781E+10 | 0.93 | 559.22 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.176355E+11 | 0.93 | |||
Minimum of Months | 0.135286E+10 | 0.93 | 559.22 | 0.93 | |
Maximum of Months | 0.149781E+10 | 0.93 | 559.22 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143109E+11 | 0.93 | 5343.06 | 01-JAN-00:05 | 0.93 |
February | 0.129259E+11 | 0.93 | 5343.06 | 01-FEB-00:01 | 0.93 |
March | 0.143109E+11 | 0.93 | 5343.06 | 01-MAR-00:01 | 0.93 |
April | 0.138492E+11 | 0.93 | 5343.06 | 01-APR-00:10 | 0.93 |
May | 0.143109E+11 | 0.93 | 5343.06 | 01-MAY-00:15 | 0.93 |
June | 0.138492E+11 | 0.93 | 5343.06 | 01-JUN-00:10 | 0.93 |
July | 0.143109E+11 | 0.93 | 5343.06 | 01-JUL-00:10 | 0.93 |
August | 0.143109E+11 | 0.93 | 5343.06 | 01-AUG-00:05 | 0.93 |
September | 0.138492E+11 | 0.93 | 5343.06 | 01-SEP-00:03 | 0.93 |
October | 0.143109E+11 | 0.93 | 5343.06 | 01-OCT-00:10 | 0.93 |
November | 0.138492E+11 | 0.93 | 5343.06 | 01-NOV-00:10 | 0.93 |
December | 0.143109E+11 | 0.93 | 5343.06 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.168499E+12 | 0.93 | |||
Minimum of Months | 0.129259E+11 | 0.93 | 5343.06 | 0.93 | |
Maximum of Months | 0.143109E+11 | 0.93 | 5343.06 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145691E+10 | 0.93 | 543.95 | 01-JAN-00:05 | 0.93 |
February | 0.131592E+10 | 0.93 | 543.95 | 01-FEB-00:01 | 0.93 |
March | 0.145691E+10 | 0.93 | 543.95 | 01-MAR-00:01 | 0.93 |
April | 0.140992E+10 | 0.93 | 543.95 | 01-APR-00:10 | 0.93 |
May | 0.145691E+10 | 0.93 | 543.95 | 01-MAY-00:10 | 0.93 |
June | 0.140992E+10 | 0.93 | 543.95 | 01-JUN-00:20 | 0.93 |
July | 0.145691E+10 | 0.93 | 543.95 | 01-JUL-00:10 | 0.93 |
August | 0.145691E+10 | 0.93 | 543.95 | 01-AUG-00:05 | 0.93 |
September | 0.140992E+10 | 0.93 | 543.95 | 01-SEP-00:03 | 0.93 |
October | 0.145691E+10 | 0.93 | 543.95 | 01-OCT-00:10 | 0.93 |
November | 0.140992E+10 | 0.93 | 543.95 | 01-NOV-00:10 | 0.93 |
December | 0.145691E+10 | 0.93 | 543.95 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.171540E+11 | 0.93 | |||
Minimum of Months | 0.131592E+10 | 0.93 | 543.95 | 0.93 | |
Maximum of Months | 0.145691E+10 | 0.93 | 543.95 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.516877E+10 | 0.465189E+10 | 11033.31 | 02-JAN-06:03 | 9929.98 | 9929.98 | 70.36 | 22.01 |
February | 0.308343E+10 | 0.277509E+10 | 9344.48 | 14-FEB-06:01 | 8410.03 | 8410.03 | 75.33 | 16.10 |
March | 0.146007E+10 | 0.131406E+10 | 7556.88 | 06-MAR-06:01 | 6801.19 | 6801.19 | 71.44 | 11.72 |
April | 0.709121E+09 | 0.638209E+09 | 5224.19 | 19-APR-06:10 | 4701.77 | 4701.77 | 62.69 | 7.32 |
May | 0.487174E+09 | 0.438457E+09 | 6022.71 | 29-MAY-01:20 | 5420.44 | 5420.44 | 59.10 | 8.74 |
June | 60724266.42 | 54651839.78 | 4626.01 | 25-JUN-21:45 | 4163.41 | 4163.41 | 67.92 | 6.32 |
July | 23670321.91 | 21303289.72 | 4637.32 | 30-JUL-22:25 | 4173.59 | 4173.59 | 72.83 | 6.32 |
August | 18723359.60 | 16851023.64 | 4636.43 | 27-AUG-23:07 | 4172.79 | 4172.79 | 72.45 | 6.32 |
September | 0.140297E+09 | 0.126268E+09 | 4637.24 | 04-SEP-20:50 | 4173.51 | 4173.51 | 72.79 | 6.32 |
October | 0.656797E+09 | 0.591118E+09 | 4635.69 | 09-OCT-14:10 | 4172.12 | 4172.12 | 72.13 | 6.32 |
November | 0.178408E+10 | 0.160567E+10 | 7500.05 | 24-NOV-06:01 | 6750.04 | 6750.04 | 70.90 | 11.60 |
December | 0.319380E+10 | 0.287442E+10 | 9299.21 | 26-DEC-07:10 | 8369.29 | 8369.29 | 66.37 | 16.06 |
Annual Sum or Average | 0.167867E+11 | 0.151080E+11 | ||||||
Minimum of Months | 18723359.60 | 16851023.64 | 4626.01 | 4163.41 | 4163.41 | 59.10 | 6.32 | |
Maximum of Months | 0.516877E+10 | 0.465189E+10 | 11033.31 | 9929.98 | 9929.98 | 75.33 | 22.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 14283641.98 | 12855277.78 | 1781.05 | 11-JAN-16:00 | 1602.95 | 1602.95 | 6.95 | 2.38 |
February | 0.242025E+09 | 0.217823E+09 | 10741.19 | 27-FEB-15:00 | 9667.07 | 9667.07 | 8.21 | 18.77 |
March | 0.508813E+09 | 0.457932E+09 | 9016.37 | 10-MAR-14:00 | 8114.73 | 8114.73 | 7.55 | 14.72 |
April | 0.227896E+10 | 0.205106E+10 | 17185.84 | 26-APR-16:00 | 15467.26 | 15467.26 | 6.77 | 51.99 |
May | 0.494305E+10 | 0.444874E+10 | 17929.73 | 04-MAY-15:00 | 16136.75 | 16136.75 | 6.76 | 62.67 |
June | 0.896460E+10 | 0.806814E+10 | 17648.82 | 27-JUN-14:10 | 15883.94 | 15883.94 | 6.95 | 58.63 |
July | 0.134586E+11 | 0.121128E+11 | 17366.37 | 19-JUL-14:00 | 15629.73 | 15629.73 | 6.96 | 54.50 |
August | 0.159515E+11 | 0.143564E+11 | 17308.01 | 21-AUG-14:40 | 15577.21 | 15577.21 | 6.99 | 53.67 |
September | 0.773822E+10 | 0.696440E+10 | 17835.20 | 08-SEP-16:00 | 16051.68 | 16051.68 | 6.78 | 61.34 |
October | 0.167032E+10 | 0.150329E+10 | 13874.95 | 04-OCT-15:00 | 12487.45 | 12487.45 | 7.29 | 28.68 |
November | 0.268090E+09 | 0.241281E+09 | 11364.53 | 04-NOV-13:30 | 10228.08 | 10228.08 | 8.17 | 20.41 |
December | 969489.92 | 872540.93 | 1698.17 | 16-DEC-06:01 | 1528.36 | 1528.36 | 6.98 | 2.26 |
Annual Sum or Average | 0.560395E+11 | 0.504355E+11 | ||||||
Minimum of Months | 969489.92 | 872540.93 | 1698.17 | 1528.36 | 1528.36 | 6.76 | 2.26 | |
Maximum of Months | 0.159515E+11 | 0.143564E+11 | 17929.73 | 16136.75 | 16136.75 | 8.21 | 62.67 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 73.94 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 65.98 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 62.13 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 61.25 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 79.51 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 62.56 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 61.61 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 62.24 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 63.12 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 75.19 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 61.72 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 60.94 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 60.94 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 79.51 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.306064E+09 | 0.275457E+09 | 7378.33 | 01-JAN-11:42 | 6640.50 | 6640.50 | 6.74 | 92.41 |
February | 0.772216E+09 | 0.694995E+09 | 7378.33 | 01-FEB-04:01 | 6640.50 | 6640.50 | 6.75 | 92.41 |
March | 0.112084E+10 | 0.100876E+10 | 7378.33 | 01-MAR-05:03 | 6640.50 | 6640.50 | 6.76 | 92.41 |
April | 0.345749E+10 | 0.311174E+10 | 7378.33 | 01-APR-05:01 | 6640.50 | 6640.50 | 6.76 | 92.41 |
May | 0.631290E+10 | 0.568161E+10 | 7378.33 | 01-MAY-02:21 | 6640.50 | 6640.50 | 6.93 | 92.41 |
June | 0.931396E+10 | 0.838257E+10 | 7378.33 | 01-JUN-03:01 | 6640.50 | 6640.50 | 7.31 | 92.41 |
July | 0.124886E+11 | 0.112397E+11 | 7378.33 | 01-JUL-03:01 | 6640.50 | 6640.50 | 7.52 | 92.41 |
August | 0.137950E+11 | 0.124155E+11 | 7378.33 | 01-AUG-00:42 | 6640.50 | 6640.50 | 6.85 | 92.41 |
September | 0.802416E+10 | 0.722174E+10 | 7378.33 | 01-SEP-00:52 | 6640.50 | 6640.50 | 6.79 | 92.41 |
October | 0.320596E+10 | 0.288536E+10 | 7378.33 | 01-OCT-12:42 | 6640.50 | 6640.50 | 7.34 | 92.41 |
November | 0.744442E+09 | 0.669998E+09 | 7378.33 | 01-NOV-03:01 | 6640.50 | 6640.50 | 6.82 | 92.41 |
December | 0.210578E+09 | 0.189520E+09 | 7378.33 | 02-DEC-06:01 | 6640.50 | 6640.50 | 6.74 | 92.41 |
Annual Sum or Average | 0.597522E+11 | 0.537770E+11 | ||||||
Minimum of Months | 0.210578E+09 | 0.189520E+09 | 7378.33 | 6640.50 | 6640.50 | 6.74 | 92.41 | |
Maximum of Months | 0.137950E+11 | 0.124155E+11 | 7378.33 | 6640.50 | 6640.50 | 7.52 | 92.41 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-JAN-00:05 | 3006.37 | 3006.37 | 21.44 | 13.95 |
February | 0.808112E+10 | 0.727301E+10 | 3340.41 | 01-FEB-00:01 | 3006.37 | 3006.37 | 22.75 | 13.95 |
March | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-MAR-00:01 | 3006.37 | 3006.37 | 21.97 | 13.95 |
April | 0.865834E+10 | 0.779251E+10 | 3340.41 | 01-APR-00:10 | 3006.37 | 3006.37 | 29.68 | 13.95 |
May | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-MAY-00:10 | 3006.37 | 3006.37 | 23.13 | 13.95 |
June | 0.865834E+10 | 0.779251E+10 | 3340.41 | 01-JUN-00:10 | 3006.37 | 3006.37 | 24.32 | 13.95 |
July | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-JUL-00:10 | 3006.37 | 3006.37 | 27.64 | 13.95 |
August | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-AUG-00:05 | 3006.37 | 3006.37 | 33.11 | 13.95 |
September | 0.865834E+10 | 0.779251E+10 | 3340.41 | 01-SEP-00:03 | 3006.37 | 3006.37 | 27.77 | 13.95 |
October | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-OCT-00:10 | 3006.37 | 3006.37 | 24.23 | 13.95 |
November | 0.865834E+10 | 0.779251E+10 | 3340.41 | 01-NOV-00:10 | 3006.37 | 3006.37 | 26.87 | 13.95 |
December | 0.894695E+10 | 0.805226E+10 | 3340.41 | 01-DEC-00:10 | 3006.37 | 3006.37 | 29.60 | 13.95 |
Annual Sum or Average | 0.105343E+12 | 0.948088E+11 | ||||||
Minimum of Months | 0.808112E+10 | 0.727301E+10 | 3340.41 | 3006.37 | 3006.37 | 21.44 | 13.95 | |
Maximum of Months | 0.894695E+10 | 0.805226E+10 | 3340.41 | 3006.37 | 3006.37 | 33.11 | 13.95 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.574959E+09 | 0.517463E+09 | 13862.51 | 11-JAN-16:10 | 12476.26 | 12476.26 | 21.24 | 54.44 |
February | 0.145970E+10 | 0.131373E+10 | 27764.84 | 27-FEB-14:50 | 24988.35 | 24988.35 | 23.23 | 108.87 |
March | 0.210695E+10 | 0.189626E+10 | 13886.15 | 18-MAR-14:20 | 12497.53 | 12497.53 | 23.61 | 54.44 |
April | 0.696435E+10 | 0.626791E+10 | 27824.82 | 27-APR-15:00 | 25042.34 | 25042.34 | 26.06 | 108.87 |
May | 0.124896E+11 | 0.112406E+11 | 27817.47 | 05-MAY-15:10 | 25035.72 | 25035.72 | 25.74 | 108.87 |
June | 0.185451E+11 | 0.166906E+11 | 27805.03 | 22-JUN-15:30 | 25024.53 | 25024.53 | 25.21 | 108.87 |
July | 0.266558E+11 | 0.239902E+11 | 27889.16 | 31-JUL-14:40 | 25100.24 | 25100.24 | 28.81 | 108.87 |
August | 0.318462E+11 | 0.286616E+11 | 27889.16 | 09-AUG-15:20 | 25100.24 | 25100.24 | 28.81 | 108.87 |
September | 0.166541E+11 | 0.149887E+11 | 27849.51 | 14-SEP-13:00 | 25064.56 | 25064.56 | 27.11 | 108.87 |
October | 0.605203E+10 | 0.544683E+10 | 27764.90 | 03-OCT-15:30 | 24988.41 | 24988.41 | 23.23 | 108.87 |
November | 0.142421E+10 | 0.128179E+10 | 27764.95 | 04-NOV-13:20 | 24988.46 | 24988.46 | 23.23 | 108.87 |
December | 0.395573E+09 | 0.356016E+09 | 13861.88 | 26-DEC-06:30 | 12475.69 | 12475.69 | 21.18 | 54.44 |
Annual Sum or Average | 0.125169E+12 | 0.112652E+12 | ||||||
Minimum of Months | 0.395573E+09 | 0.356016E+09 | 13861.88 | 12475.69 | 12475.69 | 21.18 | 54.44 | |
Maximum of Months | 0.318462E+11 | 0.286616E+11 | 27889.16 | 25100.24 | 25100.24 | 28.81 | 108.87 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6950.14 | 37526.89 | 01-JAN-08:11 | 80.31 | 82.22 | 13188.29 | 52064.82 | 31-JAN-12:30 |
February | 6572.43 | 37475.12 | 26-FEB-08:40 | 80.28 | 82.22 | 13405.13 | 52127.41 | 10-FEB-12:30 |
March | 5340.53 | 37533.81 | 26-MAR-07:30 | 80.31 | 82.22 | 14305.43 | 51930.82 | 01-MAR-12:30 |
April | 6413.32 | 37664.84 | 30-APR-07:12 | 80.38 | 82.22 | 12765.46 | 50811.95 | 03-APR-11:20 |
May | 6331.77 | 37790.97 | 29-MAY-07:00 | 80.45 | 82.22 | 12712.76 | 49257.52 | 01-MAY-11:50 |
June | 5736.37 | 37893.86 | 25-JUN-06:57 | 80.51 | 82.22 | 12479.64 | 47350.50 | 01-JUN-11:50 |
July | 7390.71 | 37970.63 | 30-JUL-06:50 | 80.55 | 82.22 | 10874.80 | 45738.62 | 03-JUL-11:50 |
August | 5714.84 | 37977.34 | 13-AUG-06:50 | 80.55 | 82.22 | 12135.74 | 45093.88 | 31-AUG-12:00 |
September | 6702.31 | 37959.85 | 03-SEP-07:10 | 80.54 | 82.22 | 11302.24 | 46054.12 | 29-SEP-11:40 |
October | 7235.81 | 37889.69 | 01-OCT-07:10 | 80.50 | 82.22 | 11701.82 | 47799.92 | 31-OCT-11:40 |
November | 7251.11 | 37751.04 | 05-NOV-07:20 | 80.43 | 82.22 | 12482.40 | 49639.78 | 30-NOV-12:40 |
December | 7062.26 | 37630.11 | 03-DEC-08:30 | 80.36 | 82.22 | 12464.96 | 51138.69 | 29-DEC-12:50 |
Annual Sum or Average | 6558.71 | 12479.82 | ||||||
Minimum of Months | 5340.53 | 37475.12 | 80.28 | 82.22 | 10874.80 | 45093.88 | ||
Maximum of Months | 7390.71 | 37977.34 | 80.55 | 82.22 | 14305.43 | 52127.41 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 81.26 | 81.26 | 171051.93 | 1074027.61 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 60.80 | 60.80 | 121308.45 | 935008.24 | 27-FEB-02:00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 56.99 | 56.99 | 60951.46 | 810964.65 | 10-MAR-04:47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.57 | 55.57 | 34659.37 | 837704.34 | 23-APR-17:48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.75 | 52.75 | 13873.68 | 837767.38 | 29-MAY-01:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.07 | 56.07 | 3009.11 | 774923.24 | 04-JUN-15:46 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 65.39 | 65.39 | 536.41 | 399019.13 | 02-JUL-14:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 72.84 | 72.84 | 549.64 | 564960.33 | 06-AUG-14:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 72.48 | 72.48 | 4497.46 | 732854.51 | 24-SEP-14:36 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 48.45 | 48.45 | 25279.16 | 827967.20 | 01-OCT-16:04 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.66 | 57.66 | 79909.51 | 901421.44 | 05-NOV-14:26 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 62.26 | 62.26 | 136392.19 | 1050997.27 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 54045.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.45 | 48.45 | 536.41 | 399019.13 | ||
Maximum of Months | 0.00 | 0.00 | 81.26 | 81.26 | 171051.93 | 1074027.61 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 370.62 | 86139.88 | 11-JAN-16:00 | 6.92 | 6.81 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9513.22 | 1113191.69 | 27-FEB-14:50 | 9.57 | 8.12 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 15039.94 | 796220.06 | 18-MAR-14:10 | 8.76 | 7.72 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 75307.64 | 1299392.55 | 27-APR-15:00 | 10.06 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 151603.56 | 1363553.79 | 04-MAY-14:30 | 10.22 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 268324.39 | 1347468.10 | 22-JUN-15:30 | 10.18 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 398992.99 | 1599168.96 | 31-JUL-16:00 | 10.83 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 481766.98 | 1758699.46 | 29-AUG-14:30 | 11.24 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 232728.73 | 1424482.66 | 14-SEP-13:00 | 10.38 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 50155.94 | 1114380.17 | 03-OCT-15:30 | 9.58 | 8.12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9527.08 | 1106574.10 | 04-NOV-13:30 | 9.56 | 8.11 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 154.96 | 57532.12 | 16-DEC-06:02 | 6.85 | 6.77 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 142146.96 | 0.00 | ||||||
Minimum of Months | 154.96 | 57532.12 | 6.85 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 481766.98 | 1758699.46 | 11.24 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 85.72 | 37827.72 | 11-JAN-16:00 | 10.50 | 6.81 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5246.47 | 711632.66 | 27-FEB-15:00 | 15.76 | 8.12 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 7829.90 | 444709.90 | 18-MAR-14:00 | 16.33 | 7.68 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 51361.62 | 1296315.41 | 27-APR-15:00 | 14.78 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 99760.15 | 1372065.63 | 04-MAY-15:00 | 11.93 | 7.96 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 182845.30 | 1347322.22 | 22-JUN-15:30 | 12.20 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 300826.16 | 1595949.54 | 31-JUL-16:00 | 14.89 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 390172.18 | 1755507.75 | 29-AUG-14:30 | 14.82 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 164604.13 | 1422308.11 | 14-SEP-13:00 | 14.57 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 29541.14 | 1052575.72 | 04-OCT-15:00 | 15.47 | 7.99 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5242.07 | 676751.56 | 04-NOV-13:30 | 14.62 | 8.05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.17 | 34622.27 | 16-DEC-06:01 | 10.35 | 6.75 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 103954.49 | 0.00 | ||||||
Minimum of Months | 7.17 | 34622.27 | 10.35 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 390172.18 | 1755507.75 | 16.33 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 160737.84 | 547466.12 | 26-JAN-23:00 | 29.54 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 299357.24 | 582798.51 | 28-FEB-22:41 | 30.26 | 18.33 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 441717.19 | 759354.16 | 18-MAR-16:00 | 33.82 | 24.48 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 622401.05 | 1346274.31 | 27-APR-16:00 | 45.49 | 32.64 | 0.00 | 0.00 | 01-APR-00:10 |
May | 201815.05 | 597329.47 | 05-MAY-16:00 | 30.55 | 26.62 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 387213.69 | 898901.02 | 28-JUN-17:00 | 36.62 | 29.62 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 631171.34 | 1326309.72 | 24-JUL-15:00 | 45.09 | 34.91 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 883173.30 | 1592781.47 | 10-AUG-17:00 | 50.31 | 37.34 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 213796.42 | 605885.88 | 14-SEP-17:00 | 30.72 | 26.67 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 313787.14 | 631510.14 | 04-OCT-15:00 | 31.24 | 24.49 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 439478.30 | 787541.54 | 04-NOV-15:00 | 34.39 | 25.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 568936.27 | 614517.80 | 13-DEC-04:52 | 30.90 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 431534.71 | 0.00 | ||||||
Minimum of Months | 160737.84 | 547466.12 | 29.54 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 883173.30 | 1592781.47 | 50.31 | 37.34 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25.22 | 31650.98 | 11-JAN-16:10 | 21.24 | 20.86 | 194.06 | 59734.23 | 01-JAN-11:42 |
February | 6647.81 | 967372.06 | 27-FEB-14:50 | 23.23 | 22.34 | 272.62 | 66712.64 | 16-FEB-06:40 |
March | 11333.94 | 570765.32 | 18-MAR-14:20 | 23.61 | 21.52 | 197.28 | 55898.88 | 04-MAR-06:50 |
April | 65814.15 | 2254929.50 | 27-APR-15:00 | 26.06 | 22.75 | 473.97 | 64566.78 | 01-APR-05:30 |
May | 124106.01 | 2111575.96 | 05-MAY-15:10 | 25.74 | 22.51 | 413.64 | 60761.33 | 10-MAY-05:40 |
June | 217558.13 | 1868740.14 | 22-JUN-15:30 | 25.21 | 21.79 | 370.17 | 43658.27 | 13-JUN-16:30 |
July | 388856.90 | 3742803.09 | 31-JUL-16:00 | 29.32 | 25.25 | 265.94 | 50657.67 | 03-JUL-08:30 |
August | 584702.50 | 4442070.85 | 29-AUG-13:10 | 30.86 | 26.40 | 240.11 | 40105.41 | 19-AUG-07:00 |
September | 214025.51 | 2736270.67 | 14-SEP-13:00 | 27.11 | 23.50 | 341.37 | 45387.31 | 11-SEP-05:50 |
October | 36900.05 | 968893.39 | 03-OCT-15:30 | 23.23 | 22.34 | 421.56 | 70952.48 | 11-OCT-06:00 |
November | 6643.17 | 970011.31 | 04-NOV-13:20 | 23.23 | 22.35 | 234.25 | 76576.96 | 21-NOV-04:01 |
December | 8.49 | 17338.30 | 26-DEC-06:30 | 21.18 | 20.49 | 209.84 | 77114.69 | 21-DEC-06:30 |
Annual Sum or Average | 139263.82 | 302.58 | ||||||
Minimum of Months | 8.49 | 17338.30 | 21.18 | 20.49 | 194.06 | 40105.41 | ||
Maximum of Months | 584702.50 | 4442070.85 | 30.86 | 26.40 | 473.97 | 77114.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 7.48 |
February | 0.17 | 7.48 |
March | 0.25 | 6.76 |
April | 0.56 | 7.48 |
May | 0.69 | 7.48 |
June | 1.10 | 7.48 |
July | 1.99 | 7.48 |
August | 0.68 | 7.48 |
September | 0.58 | 7.48 |
October | 0.81 | 7.48 |
November | 1.08 | 7.48 |
December | 0.74 | 7.48 |
Annual Sum or Average | 8.77 | 7.46 |
Minimum of Months | 0.12 | 6.76 |
Maximum of Months | 1.99 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.33 | 12.36 |
February | 1.65 | 9.18 |
March | 1.87 | 3.88 |
April | 5.84 | 3.22 |
May | 3.22 | 4.59 |
June | 4.77 | 3.08 |
July | 11.70 | 3.20 |
August | 12.04 | 1.89 |
September | 3.18 | 2.57 |
October | 2.62 | 3.82 |
November | 1.93 | 3.55 |
December | 1.40 | 3.85 |
Annual Sum or Average | 52.56 | 3.62 |
Minimum of Months | 1.40 | 1.89 |
Maximum of Months | 12.04 | 12.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 13.44 |
February | 0.51 | 9.99 |
March | 2.94 | 13.06 |
April | 2.60 | 12.53 |
May | 2.41 | 10.34 |
June | 1.91 | 10.32 |
July | 1.21 | 5.68 |
August | 1.35 | 3.99 |
September | 1.67 | 8.60 |
October | 2.79 | 12.37 |
November | 0.75 | 11.20 |
December | 0.22 | 6.72 |
Annual Sum or Average | 18.54 | 10.47 |
Minimum of Months | 0.17 | 3.99 |
Maximum of Months | 2.94 | 13.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 5.76 |
February | 0.25 | 7.46 |
March | 0.31 | 0.00 |
April | 0.36 | 5.17 |
May | 0.93 | 6.92 |
June | 0.59 | 5.61 |
July | 0.59 | 4.44 |
August | 0.28 | 9.40 |
September | 0.43 | 5.85 |
October | 0.22 | 10.08 |
November | 0.42 | 2.69 |
December | 0.44 | 0.00 |
Annual Sum or Average | 5.02 | 5.13 |
Minimum of Months | 0.19 | 0.00 |
Maximum of Months | 0.93 | 10.08 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.11 | 0.00 |
February | 0.11 | 0.84 |
March | 0.22 | 0.42 |
April | 0.26 | 0.44 |
May | 1.16 | 0.33 |
June | 1.36 | 0.31 |
July | 3.37 | 0.35 |
August | 4.27 | 0.28 |
September | 1.03 | 0.25 |
October | 0.42 | 0.53 |
November | 0.33 | 0.56 |
December | 0.06 | 0.84 |
Annual Sum or Average | 12.71 | 0.33 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 4.27 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.10 | 0.56 |
February | 1.64 | 0.44 |
March | 2.32 | 0.16 |
April | 7.31 | 0.28 |
May | 5.08 | 0.22 |
June | 7.78 | 0.21 |
July | 13.39 | 0.27 |
August | 13.94 | 0.19 |
September | 5.84 | 0.18 |
October | 5.21 | 0.26 |
November | 3.00 | 0.28 |
December | 1.54 | 0.28 |
Annual Sum or Average | 68.16 | 0.24 |
Minimum of Months | 1.10 | 0.16 |
Maximum of Months | 13.94 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.72 | 0.91 |
February | 1.46 | 0.68 |
March | 2.28 | 0.27 |
April | 6.38 | 0.40 |
May | 4.35 | 0.43 |
June | 6.94 | 0.32 |
July | 12.15 | 0.42 |
August | 13.35 | 0.29 |
September | 4.87 | 0.20 |
October | 4.02 | 0.41 |
November | 2.28 | 0.42 |
December | 1.40 | 0.48 |
Annual Sum or Average | 60.21 | 0.37 |
Minimum of Months | 0.72 | 0.20 |
Maximum of Months | 13.35 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.07 | 0.60 |
February | 3.72 | 0.38 |
March | 5.57 | 0.14 |
April | 9.28 | 0.22 |
May | 7.02 | 0.21 |
June | 7.19 | 0.23 |
July | 14.46 | 0.25 |
August | 16.69 | 0.18 |
September | 6.05 | 0.16 |
October | 7.39 | 0.26 |
November | 6.34 | 0.26 |
December | 4.83 | 0.24 |
Annual Sum or Average | 90.61 | 0.23 |
Minimum of Months | 2.07 | 0.14 |
Maximum of Months | 16.69 | 0.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.04 | 0.00 |
May | 0.63 | 0.17 |
June | 0.89 | 0.21 |
July | 0.39 | 0.31 |
August | 0.24 | 0.15 |
September | 1.23 | 0.11 |
October | 0.06 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 3.48 | 0.17 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.23 | 0.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.54 |
February | 0.51 | 0.54 |
March | 0.21 | 0.11 |
April | 1.80 | 0.28 |
May | 3.69 | 0.29 |
June | 4.79 | 0.24 |
July | 4.63 | 0.33 |
August | 3.32 | 0.16 |
September | 4.06 | 0.29 |
October | 1.48 | 0.26 |
November | 0.29 | 0.54 |
December | 0.19 | 0.54 |
Annual Sum or Average | 25.02 | 0.28 |
Minimum of Months | 0.06 | 0.11 |
Maximum of Months | 4.79 | 0.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.84 |
February | 0.36 | 1.04 |
March | 0.21 | 0.17 |
April | 1.32 | 0.44 |
May | 2.91 | 0.49 |
June | 3.67 | 0.34 |
July | 3.31 | 0.44 |
August | 2.50 | 0.22 |
September | 3.21 | 0.30 |
October | 1.61 | 0.52 |
November | 0.35 | 1.05 |
December | 0.37 | 0.84 |
Annual Sum or Average | 19.96 | 0.41 |
Minimum of Months | 0.14 | 0.17 |
Maximum of Months | 3.67 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 0.54 |
February | 0.44 | 0.65 |
March | 0.44 | 0.34 |
April | 2.11 | 0.29 |
May | 4.08 | 0.31 |
June | 4.80 | 0.26 |
July | 4.67 | 0.33 |
August | 3.97 | 0.19 |
September | 3.75 | 0.27 |
October | 1.63 | 0.31 |
November | 0.40 | 0.66 |
December | 0.23 | 0.54 |
Annual Sum or Average | 26.71 | 0.29 |
Minimum of Months | 0.18 | 0.19 |
Maximum of Months | 4.80 | 0.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.15 | 1.15 |
February | 0.18 | 0.65 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.31 | 0.99 |
June | 0.35 | 0.71 |
July | 0.52 | 0.54 |
August | 0.53 | 0.09 |
September | 0.34 | 1.12 |
October | 0.00 | 0.00 |
November | 0.08 | 0.84 |
December | 0.35 | 0.74 |
Annual Sum or Average | 2.82 | 0.67 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.53 | 1.15 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 0.54 |
February | 0.17 | 0.54 |
March | 0.08 | 0.54 |
April | 0.50 | 0.53 |
May | 2.20 | 0.40 |
June | 2.12 | 0.44 |
July | 4.29 | 0.38 |
August | 1.76 | 0.27 |
September | 2.02 | 0.60 |
October | 0.15 | 0.54 |
November | 0.18 | 0.54 |
December | 0.31 | 0.54 |
Annual Sum or Average | 13.97 | 0.43 |
Minimum of Months | 0.08 | 0.27 |
Maximum of Months | 4.29 | 0.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.10 | 0.84 |
February | 0.08 | 0.84 |
March | 0.04 | 0.84 |
April | 0.49 | 0.82 |
May | 2.22 | 0.71 |
June | 1.88 | 0.65 |
July | 3.76 | 0.58 |
August | 1.53 | 0.36 |
September | 1.66 | 0.95 |
October | 0.38 | 1.03 |
November | 0.37 | 0.84 |
December | 0.17 | 0.84 |
Annual Sum or Average | 12.69 | 0.67 |
Minimum of Months | 0.04 | 0.36 |
Maximum of Months | 3.76 | 1.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.54 |
February | 0.08 | 0.54 |
March | 0.26 | 0.54 |
April | 0.54 | 0.53 |
May | 2.75 | 0.49 |
June | 2.43 | 0.45 |
July | 4.10 | 0.39 |
August | 2.20 | 0.26 |
September | 2.04 | 0.68 |
October | 0.40 | 0.69 |
November | 0.35 | 0.54 |
December | 0.26 | 0.54 |
Annual Sum or Average | 15.47 | 0.46 |
Minimum of Months | 0.06 | 0.26 |
Maximum of Months | 4.10 | 0.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 2.03 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.03 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.03 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 43.62 | 0.00 |
February | 1.25 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 44.87 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 43.62 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 5.47 | 0.00 |
February | 2.50 | 0.00 |
March | 9.38 | 0.00 |
April | 0.00 | 0.00 |
May | 0.42 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 3.05 | 0.00 |
November | 2.37 | 0.00 |
December | 1.07 | 0.00 |
Annual Sum or Average | 24.25 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 9.38 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.111508E+10 | 0.00 | 3984460.85 | 0.171527E+11 | 0.00 | 0.00 |
February | 0.227985E+09 | 0.00 | 0.588433E+09 | 0.155970E+11 | 0.00 | 0.00 |
March | 0.594907E+09 | 0.00 | 0.225917E+09 | 0.183492E+11 | 0.00 | 0.00 |
April | 0.314828E+09 | 0.00 | 0.448185E+10 | 0.172674E+11 | 0.00 | 0.00 |
May | 0.384421E+09 | 0.00 | 0.850880E+10 | 0.183464E+11 | 0.00 | 0.00 |
June | 0.689084E+09 | 0.00 | 0.178197E+11 | 0.182660E+11 | 0.00 | 0.00 |
July | 0.123039E+10 | 0.00 | 0.327933E+11 | 0.182357E+11 | 0.00 | 0.00 |
August | 0.788330E+09 | 0.00 | 0.448794E+11 | 0.191676E+11 | 0.00 | 0.00 |
September | 0.183770E+10 | 0.00 | 0.144469E+11 | 0.182125E+11 | 0.00 | 0.00 |
October | 0.666503E+09 | 0.00 | 0.228286E+10 | 0.184159E+11 | 0.00 | 0.00 |
November | 0.778487E+09 | 0.00 | 0.396599E+09 | 0.178404E+11 | 0.00 | 0.00 |
December | 0.916559E+09 | 0.00 | 9859750.10 | 0.176821E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.954427E+10 | 0.00 | 0.126438E+12 | 0.214533E+12 | 0.00 | 0.00 |
Minimum of Months | 0.227985E+09 | 0.00 | 3984460.85 | 0.155970E+11 | 0.00 | 0.00 |
Maximum of Months | 0.183770E+10 | 0.00 | 0.448794E+11 | 0.191676E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.180793E+11 | 0.00 | 34310074.65 | 0.542117E+10 | 0.00 | 0.00 |
February | 0.112438E+11 | 0.00 | 0.117129E+10 | 0.587467E+10 | 0.00 | 0.00 |
March | 0.398068E+10 | 0.00 | 0.198274E+10 | 0.851694E+10 | 0.00 | 0.00 |
April | 0.138063E+10 | 0.00 | 0.122473E+11 | 0.888231E+10 | 0.00 | 0.00 |
May | 0.969101E+09 | 0.00 | 0.207189E+11 | 0.712797E+10 | 0.00 | 0.00 |
June | 13784154.80 | 0.00 | 0.377346E+11 | 0.742700E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.676698E+11 | 0.777165E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.925483E+11 | 0.888197E+10 | 0.00 | 0.00 |
September | 0.122784E+09 | 0.00 | 0.329717E+11 | 0.661995E+10 | 0.00 | 0.00 |
October | 0.109439E+10 | 0.00 | 0.687370E+10 | 0.737493E+10 | 0.00 | 0.00 |
November | 0.511797E+10 | 0.00 | 0.109673E+10 | 0.714099E+10 | 0.00 | 0.00 |
December | 0.101276E+11 | 0.00 | 2911.09 | 0.730435E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.521301E+11 | 0.00 | 0.275049E+12 | 0.883439E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2911.09 | 0.542117E+10 | 0.00 | 0.00 |
Maximum of Months | 0.180793E+11 | 0.00 | 0.925483E+11 | 0.888231E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.382597E+12 | 0.00 | 0.244112E+09 | 0.365748E+11 | 0.00 | 0.00 |
February | 0.243581E+12 | 0.00 | 0.867428E+10 | 0.385671E+11 | 0.00 | 0.00 |
March | 0.133466E+12 | 0.00 | 0.153008E+11 | 0.527971E+11 | 0.00 | 0.00 |
April | 0.752169E+11 | 0.00 | 0.919810E+11 | 0.506551E+11 | 0.00 | 0.00 |
May | 0.304901E+11 | 0.00 | 0.181430E+12 | 0.555988E+11 | 0.00 | 0.00 |
June | 0.589348E+10 | 0.00 | 0.313111E+12 | 0.552477E+11 | 0.00 | 0.00 |
July | 38188375.91 | 0.00 | 0.539568E+12 | 0.539166E+11 | 0.00 | 0.00 |
August | 0.552904E+09 | 0.00 | 0.719599E+12 | 0.598770E+11 | 0.00 | 0.00 |
September | 0.828259E+10 | 0.00 | 0.295276E+12 | 0.538242E+11 | 0.00 | 0.00 |
October | 0.533379E+11 | 0.00 | 0.547954E+11 | 0.506007E+11 | 0.00 | 0.00 |
November | 0.170040E+12 | 0.00 | 0.940125E+10 | 0.418994E+11 | 0.00 | 0.00 |
December | 0.305898E+12 | 0.00 | 16326.01 | 0.395189E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.140939E+13 | 0.00 | 0.222938E+13 | 0.589077E+12 | 0.00 | 0.00 |
Minimum of Months | 38188375.91 | 0.00 | 16326.01 | 0.365748E+11 | 0.00 | 0.00 |
Maximum of Months | 0.382597E+12 | 0.00 | 0.719599E+12 | 0.598770E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.606882E+11 | 0.00 | 15751297.84 | 0.355375E+10 | 0.00 | 0.00 |
February | 0.406570E+11 | 0.00 | 0.704445E+09 | 0.318939E+10 | 0.00 | 0.00 |
March | 0.262796E+11 | 0.00 | 0.140348E+10 | 0.389927E+10 | 0.00 | 0.00 |
April | 0.138107E+11 | 0.00 | 0.954483E+10 | 0.410713E+10 | 0.00 | 0.00 |
May | 0.536263E+10 | 0.00 | 0.189956E+11 | 0.488681E+10 | 0.00 | 0.00 |
June | 0.113699E+10 | 0.00 | 0.337042E+11 | 0.523824E+10 | 0.00 | 0.00 |
July | 69249604.88 | 0.00 | 0.589091E+11 | 0.546035E+10 | 0.00 | 0.00 |
August | 0.157795E+09 | 0.00 | 0.771155E+11 | 0.595969E+10 | 0.00 | 0.00 |
September | 0.197754E+10 | 0.00 | 0.296646E+11 | 0.456762E+10 | 0.00 | 0.00 |
October | 0.122690E+11 | 0.00 | 0.492514E+10 | 0.372419E+10 | 0.00 | 0.00 |
November | 0.331377E+11 | 0.00 | 0.898293E+09 | 0.312280E+10 | 0.00 | 0.00 |
December | 0.523190E+11 | 0.00 | 13.92 | 0.318324E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.247865E+12 | 0.00 | 0.235881E+12 | 0.508925E+11 | 0.00 | 0.00 |
Minimum of Months | 69249604.88 | 0.00 | 13.92 | 0.312280E+10 | 0.00 | 0.00 |
Maximum of Months | 0.606882E+11 | 0.00 | 0.771155E+11 | 0.595969E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.214574E+10 | 0.00 | 0.380788E+12 | 0.178419E+12 | 0.00 | 1.03 |
February | 0.158276E+10 | 0.00 | 0.602661E+12 | 0.207276E+12 | 0.00 | 0.91 |
March | 0.894336E+09 | 0.00 | 0.956715E+12 | 0.278262E+12 | 0.00 | 0.96 |
April | 0.169593E+09 | 0.00 | 0.121216E+13 | 0.319162E+12 | 0.00 | 0.62 |
May | 0.456502E+09 | 0.00 | 0.387736E+12 | 0.177517E+12 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.658138E+12 | 0.226684E+12 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.984098E+12 | 0.296772E+12 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.129345E+13 | 0.363321E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.377873E+12 | 0.171224E+12 | 0.00 | 0.01 |
October | 0.103739E+10 | 0.00 | 0.674126E+12 | 0.229162E+12 | 0.00 | 0.30 |
November | 0.386306E+09 | 0.00 | 0.926862E+12 | 0.268035E+12 | 0.00 | 0.53 |
December | 0.297899E+09 | 0.00 | 0.124366E+13 | 0.323905E+12 | 0.00 | 0.98 |
Annual Sum or Average | 0.697053E+10 | 0.00 | 0.969827E+13 | 0.303974E+13 | 0.00 | 5.67 |
Minimum of Months | 0.00 | 0.00 | 0.377873E+12 | 0.171224E+12 | 0.00 | 0.00 |
Maximum of Months | 0.214574E+10 | 0.00 | 0.129345E+13 | 0.363321E+12 | 0.00 | 1.03 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.567457E+10 | 0.270649E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.109843E+11 | 0.354691E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185403E+11 | 0.503963E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240576E+11 | 0.598203E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.685954E+10 | 0.296194E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126605E+11 | 0.407373E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.194857E+11 | 0.558809E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.258498E+11 | 0.702731E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.668885E+10 | 0.288620E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126490E+11 | 0.402448E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178726E+11 | 0.486337E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243063E+11 | 0.597029E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185629E+12 | 0.546705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.567457E+10 | 0.270649E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.258498E+11 | 0.702731E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.330967E+11 | 0.216223E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.887468E+11 | 0.309274E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163993E+12 | 0.459194E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220836E+12 | 0.557005E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.582098E+11 | 0.268647E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115018E+12 | 0.378260E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.182281E+12 | 0.526857E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.243473E+12 | 0.665238E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.571920E+11 | 0.262582E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108844E+12 | 0.362747E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.154327E+12 | 0.436736E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211856E+12 | 0.537725E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163787E+13 | 0.498049E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.330967E+11 | 0.216223E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243473E+12 | 0.665238E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.149651E+10 | 0.179779E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.693594E+10 | 0.275010E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149373E+11 | 0.437018E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211998E+11 | 0.546177E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.525159E+10 | 0.260212E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112494E+11 | 0.376743E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.180867E+11 | 0.528190E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241516E+11 | 0.666180E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.511898E+10 | 0.253471E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.958668E+10 | 0.341667E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.136164E+11 | 0.408105E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.188348E+11 | 0.502303E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150466E+12 | 0.477486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.149651E+10 | 0.179779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241516E+11 | 0.666180E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171527E+11 | 3984460.85 | 0.111508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155970E+11 | 0.588433E+09 | 0.227985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183492E+11 | 0.225917E+09 | 0.594907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172674E+11 | 0.448185E+10 | 0.314828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183464E+11 | 0.850880E+10 | 0.384421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182660E+11 | 0.178197E+11 | 0.689084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182357E+11 | 0.327933E+11 | 0.123039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191676E+11 | 0.448794E+11 | 0.788330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182125E+11 | 0.144469E+11 | 0.183770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184159E+11 | 0.228286E+10 | 0.666503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178404E+11 | 0.396599E+09 | 0.778487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176821E+11 | 9859750.10 | 0.916559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214533E+12 | 0.126438E+12 | 0.954427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155970E+11 | 3984460.85 | 0.227985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191676E+11 | 0.448794E+11 | 0.183770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.542117E+10 | 34310074.65 | 0.180793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587467E+10 | 0.117129E+10 | 0.112438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.851694E+10 | 0.198274E+10 | 0.398068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.888231E+10 | 0.122473E+11 | 0.138063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.712797E+10 | 0.207189E+11 | 0.969101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742700E+10 | 0.377346E+11 | 13784154.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.777165E+10 | 0.676698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.888197E+10 | 0.925483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661995E+10 | 0.329717E+11 | 0.122784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737493E+10 | 0.687370E+10 | 0.109439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714099E+10 | 0.109673E+10 | 0.511797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730435E+10 | 2911.09 | 0.101276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883439E+11 | 0.275049E+12 | 0.521301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542117E+10 | 2911.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.888231E+10 | 0.925483E+11 | 0.180793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.365748E+11 | 0.244112E+09 | 0.382597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385671E+11 | 0.867428E+10 | 0.243581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527971E+11 | 0.153008E+11 | 0.133466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.506551E+11 | 0.919810E+11 | 0.752169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555988E+11 | 0.181430E+12 | 0.304901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.552477E+11 | 0.313111E+12 | 0.589348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.539166E+11 | 0.539568E+12 | 38188375.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598770E+11 | 0.719599E+12 | 0.552904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.538242E+11 | 0.295276E+12 | 0.828259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506007E+11 | 0.547954E+11 | 0.533379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418994E+11 | 0.940125E+10 | 0.170040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395189E+11 | 16326.01 | 0.305898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589077E+12 | 0.222938E+13 | 0.140939E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.365748E+11 | 16326.01 | 38188375.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.598770E+11 | 0.719599E+12 | 0.382597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.355375E+10 | 15751297.84 | 0.606882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318939E+10 | 0.704445E+09 | 0.406570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389927E+10 | 0.140348E+10 | 0.262796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.410713E+10 | 0.954483E+10 | 0.138107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.488681E+10 | 0.189956E+11 | 0.536263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.523824E+10 | 0.337042E+11 | 0.113699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.546035E+10 | 0.589091E+11 | 69249604.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.595969E+10 | 0.771155E+11 | 0.157795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.456762E+10 | 0.296646E+11 | 0.197754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.372419E+10 | 0.492514E+10 | 0.122690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312280E+10 | 0.898293E+09 | 0.331377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318324E+10 | 13.92 | 0.523190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.508925E+11 | 0.235881E+12 | 0.247865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312280E+10 | 13.92 | 69249604.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.595969E+10 | 0.771155E+11 | 0.606882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.957972E+11 | 0.324995E+12 | 0.214574E+10 | 0.00 | 0.00 | 0.274569E+10 | 0.00 | 0.00 |
February | 0.865265E+11 | 0.514544E+12 | 0.158276E+10 | 0.00 | 0.00 | 0.244791E+10 | 0.00 | 0.00 |
March | 0.957972E+11 | 0.816071E+12 | 0.894336E+09 | 0.00 | 0.00 | 0.256863E+10 | 0.00 | 0.00 |
April | 0.927069E+11 | 0.102935E+13 | 0.169593E+09 | 0.00 | 0.00 | 0.166585E+10 | 0.00 | 0.00 |
May | 0.957972E+11 | 0.330146E+12 | 0.456502E+09 | 0.00 | 0.00 | 0.662298E+09 | 0.00 | 0.00 |
June | 0.927069E+11 | 0.557079E+12 | 0.00 | 0.00 | 0.00 | 0.173550E+09 | 0.00 | 0.00 |
July | 0.957972E+11 | 0.824714E+12 | 0.00 | 0.00 | 0.00 | 45986604.48 | 0.00 | 0.00 |
August | 0.957972E+11 | 0.107128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927069E+11 | 0.322448E+12 | 0.00 | 0.00 | 0.00 | 16654398.51 | 0.00 | 0.00 |
October | 0.957972E+11 | 0.575120E+12 | 0.103739E+10 | 0.00 | 0.00 | 0.808895E+09 | 0.00 | 0.00 |
November | 0.927069E+11 | 0.791356E+12 | 0.386306E+09 | 0.00 | 0.00 | 0.140847E+10 | 0.00 | 0.00 |
December | 0.957972E+11 | 0.106120E+13 | 0.297899E+09 | 0.00 | 0.00 | 0.263054E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112793E+13 | 0.821830E+13 | 0.697053E+10 | 0.00 | 0.00 | 0.151745E+11 | 0.00 | 0.00 |
Minimum of Months | 0.865265E+11 | 0.322448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957972E+11 | 0.107128E+13 | 0.214574E+10 | 0.00 | 0.00 | 0.274569E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149781E+10 | 0.482269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135286E+10 | 0.933120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149781E+10 | 0.157483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144949E+10 | 0.203239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149781E+10 | 0.580670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144949E+10 | 0.106476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149781E+10 | 0.161625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149781E+10 | 0.211297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144949E+10 | 0.565330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149781E+10 | 0.107362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144949E+10 | 0.151832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149781E+10 | 0.206593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176355E+11 | 0.156204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135286E+10 | 0.482269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149781E+10 | 0.211297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143109E+11 | 0.281285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129259E+11 | 0.753893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143109E+11 | 0.139294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138492E+11 | 0.186540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143109E+11 | 0.492637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138492E+11 | 0.967097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143109E+11 | 0.151176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143109E+11 | 0.198977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138492E+11 | 0.483228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143109E+11 | 0.923786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138492E+11 | 0.131102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143109E+11 | 0.180068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168499E+12 | 0.137735E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129259E+11 | 0.281285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143109E+11 | 0.198977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145691E+10 | 0.127197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131592E+10 | 0.589172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145691E+10 | 0.126871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140992E+10 | 0.179028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145691E+10 | 0.444163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140992E+10 | 0.945451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145691E+10 | 0.149933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145691E+10 | 0.197288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140992E+10 | 0.432167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145691E+10 | 0.813543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140992E+10 | 0.115665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145691E+10 | 0.160085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171540E+11 | 0.126404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131592E+10 | 0.127197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145691E+10 | 0.197288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.171527E+11 | 0.111508E+10 | 3984460.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155970E+11 | 0.227985E+09 | 0.588433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183492E+11 | 0.594907E+09 | 0.225917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172674E+11 | 0.314828E+09 | 0.448185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183464E+11 | 0.384421E+09 | 0.850880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182660E+11 | 0.689084E+09 | 0.178197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182357E+11 | 0.123039E+10 | 0.327933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191676E+11 | 0.788330E+09 | 0.448794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182125E+11 | 0.183770E+10 | 0.144469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184159E+11 | 0.666503E+09 | 0.228286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178404E+11 | 0.778487E+09 | 0.396599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176821E+11 | 0.916559E+09 | 9859750.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214533E+12 | 0.954427E+10 | 0.126438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.155970E+11 | 0.227985E+09 | 3984460.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191676E+11 | 0.183770E+10 | 0.448794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.542117E+10 | 0.180793E+11 | 34310074.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587467E+10 | 0.112438E+11 | 0.117129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.851694E+10 | 0.398068E+10 | 0.198274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.888231E+10 | 0.138063E+10 | 0.122473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.712797E+10 | 0.969101E+09 | 0.207189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742700E+10 | 13784154.80 | 0.377346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.777165E+10 | 0.00 | 0.676698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.888197E+10 | 0.00 | 0.925483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661995E+10 | 0.122784E+09 | 0.329717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737493E+10 | 0.109439E+10 | 0.687370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714099E+10 | 0.511797E+10 | 0.109673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730435E+10 | 0.101276E+11 | 2911.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883439E+11 | 0.521301E+11 | 0.275049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.542117E+10 | 0.00 | 2911.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.888231E+10 | 0.180793E+11 | 0.925483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.365748E+11 | 0.382597E+12 | 0.244112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385671E+11 | 0.243581E+12 | 0.867428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527971E+11 | 0.133466E+12 | 0.153008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.506551E+11 | 0.752169E+11 | 0.919810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555988E+11 | 0.304901E+11 | 0.181430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.552477E+11 | 0.589348E+10 | 0.313111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.539166E+11 | 38188375.91 | 0.539568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598770E+11 | 0.552904E+09 | 0.719599E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.538242E+11 | 0.828259E+10 | 0.295276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506007E+11 | 0.533379E+11 | 0.547954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418994E+11 | 0.170040E+12 | 0.940125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395189E+11 | 0.305898E+12 | 16326.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589077E+12 | 0.140939E+13 | 0.222938E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.365748E+11 | 38188375.91 | 16326.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.598770E+11 | 0.382597E+12 | 0.719599E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.355375E+10 | 0.606882E+11 | 15751297.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318939E+10 | 0.406570E+11 | 0.704445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389927E+10 | 0.262796E+11 | 0.140348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.410713E+10 | 0.138107E+11 | 0.954483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.488681E+10 | 0.536263E+10 | 0.189956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.523824E+10 | 0.113699E+10 | 0.337042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.546035E+10 | 69249604.88 | 0.589091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.595969E+10 | 0.157795E+09 | 0.771155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.456762E+10 | 0.197754E+10 | 0.296646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.372419E+10 | 0.122690E+11 | 0.492514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312280E+10 | 0.331377E+11 | 0.898293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318324E+10 | 0.523190E+11 | 13.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.508925E+11 | 0.247865E+12 | 0.235881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.312280E+10 | 69249604.88 | 13.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.595969E+10 | 0.606882E+11 | 0.771155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.957972E+11 | 0.214574E+10 | 0.380788E+12 | 0.00 | 0.798639E+11 | 0.00 | 0.00 | 0.00 | 0.275805E+10 | 0.00 | 0.00 | 0.00 |
February | 0.865265E+11 | 0.158276E+10 | 0.602661E+12 | 0.00 | 0.118291E+12 | 0.00 | 0.00 | 0.00 | 0.245893E+10 | 0.00 | 0.00 | 0.00 |
March | 0.957972E+11 | 0.894336E+09 | 0.956715E+12 | 0.00 | 0.179884E+12 | 0.00 | 0.00 | 0.00 | 0.258019E+10 | 0.00 | 0.00 | 0.00 |
April | 0.927069E+11 | 0.169593E+09 | 0.121216E+13 | 0.00 | 0.224781E+12 | 0.00 | 0.00 | 0.00 | 0.167335E+10 | 0.00 | 0.00 | 0.00 |
May | 0.957972E+11 | 0.456502E+09 | 0.387736E+12 | 0.00 | 0.810549E+11 | 0.00 | 0.00 | 0.00 | 0.665279E+09 | 0.00 | 0.00 | 0.00 |
June | 0.927069E+11 | 0.00 | 0.658138E+12 | 0.00 | 0.133803E+12 | 0.00 | 0.00 | 0.00 | 0.174331E+09 | 0.00 | 0.00 | 0.00 |
July | 0.957972E+11 | 0.00 | 0.984098E+12 | 0.00 | 0.200929E+12 | 0.00 | 0.00 | 0.00 | 46193608.82 | 0.00 | 0.00 | 0.00 |
August | 0.957972E+11 | 0.00 | 0.129345E+13 | 0.00 | 0.267524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927069E+11 | 0.00 | 0.377873E+12 | 0.00 | 0.785000E+11 | 0.00 | 0.00 | 0.00 | 16729366.71 | 0.00 | 0.00 | 0.00 |
October | 0.957972E+11 | 0.103739E+10 | 0.674126E+12 | 0.00 | 0.132552E+12 | 0.00 | 0.00 | 0.00 | 0.812536E+09 | 0.00 | 0.00 | 0.00 |
November | 0.927069E+11 | 0.386306E+09 | 0.926862E+12 | 0.00 | 0.173913E+12 | 0.00 | 0.00 | 0.00 | 0.141481E+10 | 0.00 | 0.00 | 0.00 |
December | 0.957972E+11 | 0.297899E+09 | 0.124366E+13 | 0.00 | 0.225465E+12 | 0.00 | 0.00 | 0.00 | 0.264238E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112793E+13 | 0.697053E+10 | 0.969827E+13 | 0.00 | 0.189656E+13 | 0.00 | 0.00 | 0.00 | 0.152428E+11 | 0.00 | 0.00 | |
Minimum of Months | 0.865265E+11 | 0.00 | 0.377873E+12 | 0.00 | 0.785000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957972E+11 | 0.214574E+10 | 0.129345E+13 | 0.00 | 0.267524E+12 | 0.00 | 0.00 | 0.00 | 0.275805E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.149781E+10 | 0.00 | 0.567457E+10 | 0.00 | 0.120869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135286E+10 | 0.00 | 0.109843E+11 | 0.00 | 0.219405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149781E+10 | 0.00 | 0.185403E+11 | 0.00 | 0.354182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144949E+10 | 0.00 | 0.240576E+11 | 0.00 | 0.453254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149781E+10 | 0.00 | 0.685954E+10 | 0.00 | 0.146413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144949E+10 | 0.00 | 0.126605E+11 | 0.00 | 0.262424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149781E+10 | 0.00 | 0.194857E+11 | 0.00 | 0.409028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149781E+10 | 0.00 | 0.258498E+11 | 0.00 | 0.552950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144949E+10 | 0.00 | 0.668885E+10 | 0.00 | 0.143671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149781E+10 | 0.00 | 0.126490E+11 | 0.00 | 0.252667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144949E+10 | 0.00 | 0.178726E+11 | 0.00 | 0.341388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149781E+10 | 0.00 | 0.243063E+11 | 0.00 | 0.447249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176355E+11 | 0.00 | 0.185629E+12 | 0.00 | 0.370350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.135286E+10 | 0.00 | 0.567457E+10 | 0.00 | 0.120869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149781E+10 | 0.00 | 0.258498E+11 | 0.00 | 0.552950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143109E+11 | 0.00 | 0.330967E+11 | 0.00 | 0.731139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129259E+11 | 0.00 | 0.887468E+11 | 0.00 | 0.180014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143109E+11 | 0.00 | 0.163993E+12 | 0.00 | 0.316085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138492E+11 | 0.00 | 0.220836E+12 | 0.00 | 0.418512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143109E+11 | 0.00 | 0.582098E+11 | 0.00 | 0.125539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138492E+11 | 0.00 | 0.115018E+12 | 0.00 | 0.239768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143109E+11 | 0.00 | 0.182281E+12 | 0.00 | 0.383748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143109E+11 | 0.00 | 0.243473E+12 | 0.00 | 0.522129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138492E+11 | 0.00 | 0.571920E+11 | 0.00 | 0.124089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143109E+11 | 0.00 | 0.108844E+12 | 0.00 | 0.219639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138492E+11 | 0.00 | 0.154327E+12 | 0.00 | 0.298243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143109E+11 | 0.00 | 0.211856E+12 | 0.00 | 0.394616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168499E+12 | 0.00 | 0.163787E+13 | 0.00 | 0.329550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129259E+11 | 0.00 | 0.330967E+11 | 0.00 | 0.731139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143109E+11 | 0.00 | 0.243473E+12 | 0.00 | 0.522129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.145691E+10 | 0.00 | 0.149651E+10 | 0.00 | 0.340871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131592E+10 | 0.00 | 0.693594E+10 | 0.00 | 0.143418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145691E+10 | 0.00 | 0.149373E+11 | 0.00 | 0.291327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140992E+10 | 0.00 | 0.211998E+11 | 0.00 | 0.405186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145691E+10 | 0.00 | 0.525159E+10 | 0.00 | 0.114521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140992E+10 | 0.00 | 0.112494E+11 | 0.00 | 0.235751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145691E+10 | 0.00 | 0.180867E+11 | 0.00 | 0.382499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145691E+10 | 0.00 | 0.241516E+11 | 0.00 | 0.520489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140992E+10 | 0.00 | 0.511898E+10 | 0.00 | 0.112480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145691E+10 | 0.00 | 0.958668E+10 | 0.00 | 0.195976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140992E+10 | 0.00 | 0.136164E+11 | 0.00 | 0.267114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145691E+10 | 0.00 | 0.188348E+11 | 0.00 | 0.356611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171540E+11 | 0.00 | 0.150466E+12 | 0.00 | 0.305946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131592E+10 | 0.00 | 0.149651E+10 | 0.00 | 0.340871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145691E+10 | 0.00 | 0.241516E+11 | 0.00 | 0.520489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495762E+09 | 0.00 | 0.00 | 0.155271E+09 | 0.00 | 0.00 | 0.789760E+11 | 0.00 | 0.68 |
February | 0.540040E+09 | 0.00 | 0.00 | 0.142920E+09 | 0.00 | 0.00 | 0.720759E+11 | 0.00 | 0.78 |
March | 0.357626E+09 | 0.00 | 0.00 | 0.178671E+09 | 0.00 | 0.00 | 0.885077E+11 | 0.00 | 0.98 |
April | 0.377345E+09 | 22770251.46 | 0.00 | 0.169991E+09 | 0.00 | 0.00 | 0.787695E+11 | 0.00 | 1.07 |
May | 0.283150E+09 | 14260277.38 | 0.00 | 0.175448E+09 | 0.00 | 0.00 | 0.783092E+11 | 0.00 | 1.31 |
June | 0.150350E+09 | 16783013.32 | 0.00 | 0.186559E+09 | 1249789.37 | 0.00 | 0.714029E+11 | 0.00 | 1.56 |
July | 0.176066E+09 | 0.172126E+09 | 0.00 | 0.196710E+09 | 4024321.79 | 0.00 | 0.568785E+11 | 0.00 | 1.52 |
August | 0.102965E+09 | 0.439570E+09 | 0.00 | 0.200013E+09 | 197457.61 | 0.00 | 0.521193E+11 | 0.00 | 1.48 |
September | 0.287264E+09 | 0.00 | 0.00 | 0.197374E+09 | 0.00 | 0.00 | 0.729128E+11 | 0.00 | 1.51 |
October | 0.462865E+09 | 0.00 | 0.00 | 0.195042E+09 | 0.00 | 0.00 | 0.866721E+11 | 0.00 | 1.18 |
November | 0.401392E+09 | 0.00 | 0.00 | 0.188824E+09 | 0.00 | 0.00 | 0.860489E+11 | 0.00 | 0.94 |
December | 0.620950E+09 | 0.00 | 0.00 | 0.178046E+09 | 0.00 | 0.00 | 0.837694E+11 | 0.00 | 0.73 |
Annual Sum or Average | 0.425578E+10 | 0.665509E+09 | 0.00 | 0.216487E+10 | 5471568.77 | 0.00 | 0.906442E+12 | 0.00 | 1.15 |
Minimum of Months | 0.102965E+09 | 0.00 | 0.00 | 0.142920E+09 | 0.00 | 0.00 | 0.521193E+11 | 0.00 | 0.68 |
Maximum of Months | 0.620950E+09 | 0.439570E+09 | 0.00 | 0.200013E+09 | 4024321.79 | 0.00 | 0.885077E+11 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204627E+10 | 0.00 | 0.00 | 84618427.53 | 0.00 | 0.00 | 0.606714E+11 | 0.00 | 0.51 |
February | 0.222625E+10 | 0.00 | 0.00 | 89031324.83 | 0.00 | 0.00 | 0.574384E+11 | 0.00 | 0.61 |
March | 0.297553E+10 | 0.00 | 0.00 | 0.119934E+09 | 0.00 | 0.00 | 0.705510E+11 | 0.00 | 0.76 |
April | 0.527468E+10 | 21604804.97 | 0.00 | 0.120074E+09 | 0.00 | 0.00 | 0.624849E+11 | 0.00 | 0.86 |
May | 0.384169E+10 | 15944438.92 | 0.00 | 0.108436E+09 | 0.00 | 0.00 | 0.543499E+11 | 0.00 | 0.86 |
June | 0.392631E+10 | 15541345.89 | 0.00 | 0.121389E+09 | 4458232.47 | 0.00 | 0.482455E+11 | 0.00 | 0.97 |
July | 0.785698E+10 | 0.777954E+09 | 0.00 | 0.106209E+09 | 41394442.98 | 0.00 | 0.327777E+11 | 0.00 | 0.96 |
August | 0.830690E+10 | 0.218373E+10 | 0.00 | 0.105729E+09 | 17910955.78 | 0.00 | 0.291645E+11 | 0.00 | 1.02 |
September | 0.388772E+10 | 86464682.33 | 0.00 | 0.106238E+09 | 0.00 | 0.00 | 0.438019E+11 | 0.00 | 0.88 |
October | 0.344858E+10 | 0.00 | 0.00 | 0.112301E+09 | 0.00 | 0.00 | 0.607622E+11 | 0.00 | 0.81 |
November | 0.289580E+10 | 0.00 | 0.00 | 0.110877E+09 | 0.00 | 0.00 | 0.648357E+11 | 0.00 | 0.69 |
December | 0.284679E+10 | 0.00 | 0.00 | 0.108824E+09 | 0.00 | 0.00 | 0.672704E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.495335E+11 | 0.310124E+10 | 0.00 | 0.129366E+10 | 63763631.22 | 0.00 | 0.652354E+12 | 0.00 | 0.79 |
Minimum of Months | 0.204627E+10 | 0.00 | 0.00 | 84618427.53 | 0.00 | 0.00 | 0.291645E+11 | 0.00 | 0.51 |
Maximum of Months | 0.830690E+10 | 0.218373E+10 | 0.00 | 0.121389E+09 | 41394442.98 | 0.00 | 0.705510E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189914E+12 | 0.00 | 0.00 | 0.334645E+09 | 0.00 | 0.116027E+09 | 0.337283E+12 | 0.00 | 0.45 |
February | 0.992051E+11 | 0.00 | 0.00 | 0.449679E+09 | 0.00 | 0.00 | 0.375440E+12 | 0.00 | 0.50 |
March | 0.321979E+11 | 0.00 | 0.00 | 0.783876E+09 | 0.00 | 0.00 | 0.515570E+12 | 0.00 | 0.58 |
April | 0.224227E+11 | 0.234233E+09 | 0.00 | 0.751711E+09 | 90973827.04 | 0.00 | 0.445598E+12 | 0.00 | 0.61 |
May | 0.290300E+11 | 50919955.48 | 0.00 | 0.878199E+09 | 0.139261E+09 | 0.00 | 0.441914E+12 | 0.00 | 0.72 |
June | 0.220671E+11 | 0.168738E+09 | 0.00 | 0.925713E+09 | 51720440.42 | 0.00 | 0.380079E+12 | 0.00 | 0.77 |
July | 0.238796E+11 | 0.656847E+10 | 0.00 | 0.805644E+09 | 0.100849E+10 | 0.00 | 0.252564E+12 | 0.00 | 0.70 |
August | 0.212009E+11 | 0.202093E+11 | 0.00 | 0.828788E+09 | 0.221412E+09 | 0.00 | 0.222049E+12 | 0.00 | 0.72 |
September | 0.269931E+11 | 0.564735E+09 | 0.00 | 0.846487E+09 | 0.387136E+09 | 0.00 | 0.352313E+12 | 0.00 | 0.72 |
October | 0.303281E+11 | 0.00 | 0.00 | 0.752836E+09 | 0.00 | 0.00 | 0.447299E+12 | 0.00 | 0.62 |
November | 0.576898E+11 | 0.00 | 0.00 | 0.586846E+09 | 0.00 | 0.00 | 0.432009E+12 | 0.00 | 0.51 |
December | 0.130089E+12 | 0.00 | 0.00 | 0.453631E+09 | 0.00 | 0.00 | 0.390031E+12 | 0.00 | 0.46 |
Annual Sum or Average | 0.685017E+12 | 0.277964E+11 | 0.00 | 0.839806E+10 | 0.189899E+10 | 0.116027E+09 | 0.459215E+13 | 0.00 | 0.61 |
Minimum of Months | 0.212009E+11 | 0.00 | 0.00 | 0.334645E+09 | 0.00 | 0.00 | 0.222049E+12 | 0.00 | 0.45 |
Maximum of Months | 0.189914E+12 | 0.202093E+11 | 0.00 | 0.925713E+09 | 0.100849E+10 | 0.116027E+09 | 0.515570E+12 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341409E+11 | 0.00 | 0.00 | 6183173.63 | 0.00 | 0.103659E+10 | 0.898969E+10 | 0.00 | 0.42 |
February | 0.250970E+11 | 0.00 | 0.00 | 11601270.12 | 0.00 | 0.528629E+09 | 0.132485E+11 | 0.00 | 0.44 |
March | 0.176191E+11 | 0.00 | 0.00 | 28352664.88 | 0.00 | 0.128402E+09 | 0.271902E+11 | 0.00 | 0.50 |
April | 0.102736E+11 | 12519.31 | 0.00 | 40928054.82 | 1179016.12 | 0.00 | 0.306506E+11 | 0.00 | 0.55 |
May | 0.708123E+10 | 3372455.60 | 0.00 | 59071326.06 | 0.00 | 0.00 | 0.362980E+11 | 0.00 | 0.67 |
June | 0.335037E+10 | 4605034.82 | 0.00 | 76395508.21 | 2898149.21 | 0.00 | 0.351951E+11 | 0.00 | 0.75 |
July | 0.252401E+10 | 0.560406E+09 | 0.00 | 74431703.64 | 23563305.19 | 0.00 | 0.244798E+11 | 0.00 | 0.70 |
August | 0.290208E+10 | 0.168334E+10 | 0.00 | 70855385.50 | 40293586.30 | 0.00 | 0.191071E+11 | 0.00 | 0.71 |
September | 0.681737E+10 | 5883658.74 | 0.00 | 54963567.97 | 15279722.18 | 0.00 | 0.247174E+11 | 0.00 | 0.64 |
October | 0.128775E+11 | 0.00 | 0.00 | 31625915.58 | 0.00 | 1359238.52 | 0.241394E+11 | 0.00 | 0.51 |
November | 0.216604E+11 | 0.00 | 0.00 | 15009401.86 | 0.00 | 0.311491E+09 | 0.165378E+11 | 0.00 | 0.44 |
December | 0.311954E+11 | 0.00 | 0.00 | 6749851.91 | 0.00 | 0.761590E+09 | 0.101665E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.175539E+12 | 0.225762E+10 | 0.00 | 0.476168E+09 | 83213779.00 | 0.276806E+10 | 0.270720E+12 | 0.00 | 0.56 |
Minimum of Months | 0.252401E+10 | 0.00 | 0.00 | 6183173.63 | 0.00 | 0.00 | 0.898969E+10 | 0.00 | 0.42 |
Maximum of Months | 0.341409E+11 | 0.168334E+10 | 0.00 | 76395508.21 | 40293586.30 | 0.103659E+10 | 0.362980E+11 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385143E+10 | 0.00 | 0.00 | 1954647.16 | 0.00 | 0.00 | 0.197275E+10 | 0.00 | 0.38 |
February | 0.289316E+10 | 0.00 | 0.00 | 3184022.85 | 0.00 | 0.00 | 0.263433E+10 | 0.00 | 0.46 |
March | 0.221070E+10 | 0.00 | 0.00 | 6303584.68 | 0.00 | 0.00 | 0.506010E+10 | 0.00 | 0.61 |
April | 0.151039E+10 | 3365437.32 | 0.00 | 8352170.39 | 0.00 | 0.00 | 0.595521E+10 | 0.00 | 0.78 |
May | 0.121014E+10 | 2744926.11 | 0.00 | 9575731.69 | 0.00 | 0.00 | 0.597474E+10 | 0.00 | 0.88 |
June | 0.737740E+09 | 2684295.78 | 0.00 | 12287200.28 | 622491.96 | 0.00 | 0.597490E+10 | 0.00 | 1.04 |
July | 0.123346E+10 | 0.131140E+09 | 0.00 | 11608195.77 | 5779803.56 | 0.00 | 0.415982E+10 | 0.00 | 1.07 |
August | 0.126218E+10 | 0.362424E+09 | 0.00 | 10871611.37 | 2500862.40 | 0.00 | 0.354032E+10 | 0.00 | 1.11 |
September | 0.120587E+10 | 12449311.24 | 0.00 | 8093277.45 | 0.00 | 0.00 | 0.437215E+10 | 0.00 | 0.85 |
October | 0.193869E+10 | 0.00 | 0.00 | 6197528.95 | 0.00 | 0.00 | 0.464958E+10 | 0.00 | 0.67 |
November | 0.235055E+10 | 0.00 | 0.00 | 4574798.88 | 0.00 | 0.00 | 0.376443E+10 | 0.00 | 0.51 |
December | 0.310447E+10 | 0.00 | 0.00 | 3387605.94 | 0.00 | 0.00 | 0.280897E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.235088E+11 | 0.514808E+09 | 0.00 | 86390375.41 | 8903157.92 | 0.00 | 0.508673E+11 | 0.00 | 0.73 |
Minimum of Months | 0.737740E+09 | 0.00 | 0.00 | 1954647.16 | 0.00 | 0.00 | 0.197275E+10 | 0.00 | 0.38 |
Maximum of Months | 0.385143E+10 | 0.362424E+09 | 0.00 | 12287200.28 | 5779803.56 | 0.00 | 0.597490E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.781372E+10 | 0.00 | 0.00 | 12733.89 | 0.00 | 0.00 | 37837477.35 | 0.00 | 0.78 |
February | 0.587589E+10 | 0.00 | 0.00 | 666844.77 | 0.00 | 0.00 | 0.101863E+10 | 0.00 | 0.86 |
March | 0.477818E+10 | 0.00 | 0.00 | 2766085.93 | 0.00 | 0.00 | 0.308704E+10 | 0.00 | 1.00 |
April | 0.373672E+10 | 2139064.36 | 0.00 | 5231140.29 | 353855.34 | 0.00 | 0.409297E+10 | 0.00 | 1.25 |
May | 0.302111E+10 | 2380803.49 | 0.00 | 6323545.05 | 544102.16 | 0.00 | 0.438703E+10 | 0.00 | 1.39 |
June | 0.228446E+10 | 2262307.70 | 0.00 | 8364584.92 | 924015.88 | 0.00 | 0.473390E+10 | 0.00 | 1.64 |
July | 0.288432E+10 | 95980844.68 | 0.00 | 7346027.52 | 18655344.02 | 0.00 | 0.288222E+10 | 0.00 | 1.69 |
August | 0.286479E+10 | 0.263419E+09 | 0.00 | 6701568.78 | 14785124.60 | 0.00 | 0.244219E+10 | 0.00 | 1.79 |
September | 0.305479E+10 | 6008593.58 | 0.00 | 5413713.11 | 6480447.18 | 0.00 | 0.321397E+10 | 0.00 | 1.45 |
October | 0.452086E+10 | 0.00 | 0.00 | 3083842.62 | 0.00 | 0.00 | 0.274355E+10 | 0.00 | 1.13 |
November | 0.592310E+10 | 0.00 | 0.00 | 385939.37 | 0.00 | 0.00 | 0.109420E+10 | 0.00 | 0.89 |
December | 0.711165E+10 | 0.00 | 0.00 | 101014.13 | 0.00 | 228998.44 | 0.255715E+09 | 0.00 | 0.77 |
Annual Sum or Average | 0.538696E+11 | 0.372190E+09 | 0.00 | 46397040.37 | 41742889.17 | 228998.44 | 0.299892E+11 | 0.00 | 1.22 |
Minimum of Months | 0.228446E+10 | 0.00 | 0.00 | 12733.89 | 0.00 | 0.00 | 37837477.35 | 0.00 | 0.77 |
Maximum of Months | 0.781372E+10 | 0.263419E+09 | 0.00 | 8364584.92 | 18655344.02 | 228998.44 | 0.473390E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.829840E+10 | 0.00 | 0.00 | 2384375.73 | 0.00 | 13378678.83 | 0.219686E+10 | 0.00 | 0.68 |
February | 0.622887E+10 | 0.00 | 0.00 | 5123015.69 | 0.00 | 548732.01 | 0.406128E+10 | 0.00 | 0.84 |
March | 0.496040E+10 | 0.00 | 0.00 | 9256134.18 | 0.00 | 0.00 | 0.754162E+10 | 0.00 | 1.06 |
April | 0.417861E+10 | 6332124.31 | 0.00 | 9543416.19 | 0.00 | 0.00 | 0.697458E+10 | 0.00 | 1.20 |
May | 0.365067E+10 | 3930124.29 | 0.00 | 9095333.80 | 0.00 | 0.00 | 0.602040E+10 | 0.00 | 1.19 |
June | 0.296119E+10 | 3034578.46 | 0.00 | 10016648.72 | 1085290.97 | 0.00 | 0.540668E+10 | 0.00 | 1.30 |
July | 0.339523E+10 | 0.168601E+09 | 0.00 | 9833453.57 | 10989468.11 | 0.00 | 0.378785E+10 | 0.00 | 1.41 |
August | 0.336377E+10 | 0.534343E+09 | 0.00 | 9525646.18 | 4260878.24 | 0.00 | 0.330493E+10 | 0.00 | 1.55 |
September | 0.328971E+10 | 30492862.04 | 0.00 | 12052951.68 | 0.00 | 0.00 | 0.551738E+10 | 0.00 | 1.44 |
October | 0.418656E+10 | 0.00 | 0.00 | 10190101.52 | 0.00 | 0.00 | 0.736607E+10 | 0.00 | 1.22 |
November | 0.584282E+10 | 0.00 | 0.00 | 4672725.22 | 0.00 | 0.00 | 0.395847E+10 | 0.00 | 0.81 |
December | 0.692328E+10 | 0.00 | 0.00 | 4150619.08 | 0.00 | 538854.63 | 0.367716E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.572795E+11 | 0.746734E+09 | 0.00 | 95844421.56 | 16335637.32 | 14466265.47 | 0.598133E+11 | 0.00 | 1.12 |
Minimum of Months | 0.296119E+10 | 0.00 | 0.00 | 2384375.73 | 0.00 | 0.00 | 0.219686E+10 | 0.00 | 0.68 |
Maximum of Months | 0.829840E+10 | 0.534343E+09 | 0.00 | 12052951.68 | 10989468.11 | 13378678.83 | 0.754162E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.776910E+10 | 0.00 | 0.00 | 546809.29 | 0.00 | 0.00 | 0.157502E+10 | 0.00 | 0.93 |
February | 0.445569E+10 | 0.00 | 0.00 | 3441708.88 | 0.00 | 0.00 | 0.400261E+10 | 0.00 | 1.07 |
March | 0.175301E+10 | 0.00 | 0.00 | 9696800.60 | 0.00 | 0.00 | 0.868086E+10 | 0.00 | 1.36 |
April | 0.145009E+10 | 4930786.03 | 0.00 | 15166862.11 | 0.00 | 0.00 | 0.946120E+10 | 0.00 | 1.81 |
May | 0.220734E+10 | 3496233.65 | 0.00 | 11182150.37 | 0.00 | 0.00 | 0.659984E+10 | 0.00 | 1.71 |
June | 0.111328E+10 | 6408961.15 | 0.00 | 14519088.09 | 924584.48 | 0.00 | 0.703033E+10 | 0.00 | 2.03 |
July | 0.182538E+10 | 0.226573E+09 | 0.00 | 17263661.04 | 1419819.63 | 0.00 | 0.545408E+10 | 0.00 | 2.32 |
August | 0.183193E+10 | 0.538529E+09 | 0.00 | 18718383.00 | 3711520.83 | 0.00 | 0.490221E+10 | 0.00 | 2.42 |
September | 0.247594E+10 | 18501146.50 | 0.00 | 8589920.58 | 0.00 | 0.00 | 0.477168E+10 | 0.00 | 1.76 |
October | 0.268272E+10 | 0.00 | 0.00 | 7245907.85 | 0.00 | 0.00 | 0.620363E+10 | 0.00 | 1.42 |
November | 0.244916E+10 | 0.00 | 0.00 | 6219542.67 | 0.00 | 0.00 | 0.630583E+10 | 0.00 | 1.12 |
December | 0.194450E+10 | 0.00 | 0.00 | 6774196.90 | 0.00 | 0.00 | 0.741262E+10 | 0.00 | 0.99 |
Annual Sum or Average | 0.319581E+11 | 0.798439E+09 | 0.00 | 0.119365E+09 | 6055924.94 | 0.00 | 0.723999E+11 | 0.00 | 1.58 |
Minimum of Months | 0.111328E+10 | 0.00 | 0.00 | 546809.29 | 0.00 | 0.00 | 0.157502E+10 | 0.00 | 0.93 |
Maximum of Months | 0.776910E+10 | 0.538529E+09 | 0.00 | 18718383.00 | 3711520.83 | 0.00 | 0.946120E+10 | 0.00 | 2.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.513863E+11 | 0.00 | 0.00 | 3963.71 | 0.00 | 0.664137E+10 | 0.112466E+09 | 0.00 | 0.40 |
February | 0.436211E+11 | 0.00 | 0.00 | 3366328.20 | 0.00 | 0.207060E+10 | 0.317139E+10 | 0.00 | 0.40 |
March | 0.362562E+11 | 0.00 | 0.00 | 16991347.79 | 0.00 | 68812722.08 | 0.156283E+11 | 0.00 | 0.44 |
April | 0.238082E+11 | 36479136.33 | 0.00 | 33122637.13 | 12093935.03 | 0.00 | 0.243053E+11 | 0.00 | 0.51 |
May | 0.174632E+11 | 29230909.68 | 0.00 | 61288279.48 | 0.00 | 0.00 | 0.373010E+11 | 0.00 | 0.69 |
June | 0.100127E+11 | 30669185.56 | 0.00 | 80225181.45 | 6875643.98 | 0.00 | 0.388622E+11 | 0.00 | 0.79 |
July | 0.858947E+10 | 0.123399E+10 | 0.00 | 74988278.23 | 66561111.25 | 0.00 | 0.264714E+11 | 0.00 | 0.76 |
August | 0.871241E+10 | 0.346589E+10 | 0.00 | 64470994.50 | 17665096.55 | 0.00 | 0.208013E+11 | 0.00 | 0.77 |
September | 0.161408E+11 | 0.118753E+09 | 0.00 | 51477942.96 | 14211745.83 | 0.00 | 0.257063E+11 | 0.00 | 0.67 |
October | 0.275842E+11 | 0.00 | 0.00 | 23444217.81 | 0.00 | 0.00 | 0.186362E+11 | 0.00 | 0.48 |
November | 0.416696E+11 | 0.00 | 0.00 | 4115790.88 | 0.00 | 0.383673E+09 | 0.473407E+10 | 0.00 | 0.39 |
December | 0.519310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193558E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.337175E+12 | 0.491502E+10 | 0.00 | 0.413495E+09 | 0.117408E+09 | 0.111000E+11 | 0.215730E+12 | 0.00 | 0.56 |
Minimum of Months | 0.858947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.519310E+11 | 0.346589E+10 | 0.00 | 80225181.45 | 66561111.25 | 0.664137E+10 | 0.388622E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115527E+11 | 0.00 | 0.00 | 0.96 |
February | 0.714736E+11 | 0.00 | 0.00 | 66413.22 | 0.00 | 0.463788E+10 | 0.361444E+09 | 0.00 | 0.98 |
March | 0.686989E+11 | 0.00 | 0.00 | 9031725.97 | 0.00 | 0.163717E+09 | 0.107494E+11 | 0.00 | 1.04 |
April | 0.435703E+11 | 29967508.14 | 0.00 | 32276763.70 | 19053170.09 | 12312640.01 | 0.269998E+11 | 0.00 | 1.13 |
May | 0.384859E+11 | 21593460.51 | 0.00 | 42991207.33 | 17390424.56 | 0.00 | 0.316437E+11 | 0.00 | 1.34 |
June | 0.250469E+11 | 30285036.92 | 0.00 | 67596814.13 | 12325284.37 | 0.00 | 0.384668E+11 | 0.00 | 1.53 |
July | 0.209138E+11 | 0.102576E+10 | 0.00 | 64262373.97 | 0.310221E+09 | 0.00 | 0.241274E+11 | 0.00 | 1.45 |
August | 0.198894E+11 | 0.302739E+10 | 0.00 | 56314366.75 | 0.186588E+09 | 0.00 | 0.200180E+11 | 0.00 | 1.51 |
September | 0.374266E+11 | 66003163.92 | 0.00 | 38394299.67 | 86388137.76 | 0.00 | 0.205517E+11 | 0.00 | 1.39 |
October | 0.549505E+11 | 0.00 | 0.00 | 13389628.95 | 0.00 | 2395439.55 | 0.140859E+11 | 0.00 | 1.10 |
November | 0.723661E+11 | 0.00 | 0.00 | 10491.21 | 0.00 | 0.103666E+10 | 0.123246E+09 | 0.00 | 0.95 |
December | 0.782569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659317E+10 | 0.00 | 0.00 | 0.92 |
Annual Sum or Average | 0.611078E+12 | 0.420100E+10 | 0.00 | 0.324334E+09 | 0.631966E+09 | 0.239988E+11 | 0.187127E+12 | 0.00 | 1.19 |
Minimum of Months | 0.198894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
Maximum of Months | 0.799991E+11 | 0.302739E+10 | 0.00 | 67596814.13 | 0.310221E+09 | 0.115527E+11 | 0.384668E+11 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.914568E+11 | 0.00 | 0.00 | 15976302.34 | 0.00 | 0.103568E+11 | 0.165982E+11 | 0.00 | 0.80 |
February | 0.756187E+11 | 0.00 | 0.00 | 43866413.20 | 0.00 | 0.301927E+10 | 0.309478E+11 | 0.00 | 0.91 |
March | 0.659008E+11 | 0.00 | 0.00 | 71613384.37 | 0.00 | 0.124407E+09 | 0.555096E+11 | 0.00 | 1.05 |
April | 0.494818E+11 | 0.112572E+09 | 0.00 | 66164759.58 | 0.00 | 0.00 | 0.472747E+11 | 0.00 | 1.04 |
May | 0.441292E+11 | 48839456.72 | 0.00 | 67944084.81 | 0.00 | 0.00 | 0.450808E+11 | 0.00 | 1.12 |
June | 0.345997E+11 | 40032747.68 | 0.00 | 67908057.38 | 13485026.13 | 0.00 | 0.377125E+11 | 0.00 | 1.16 |
July | 0.265805E+11 | 0.182355E+10 | 0.00 | 69922761.84 | 0.177235E+09 | 0.00 | 0.270169E+11 | 0.00 | 1.15 |
August | 0.253935E+11 | 0.593251E+10 | 0.00 | 67989967.10 | 67938233.85 | 0.00 | 0.222793E+11 | 0.00 | 1.25 |
September | 0.364674E+11 | 0.396658E+09 | 0.00 | 0.107510E+09 | 1010842.56 | 0.00 | 0.449389E+11 | 0.00 | 1.40 |
October | 0.519698E+11 | 0.00 | 0.00 | 87510360.42 | 0.00 | 0.00 | 0.567298E+11 | 0.00 | 1.17 |
November | 0.770909E+11 | 0.00 | 0.00 | 27267329.11 | 0.00 | 0.469543E+09 | 0.202378E+11 | 0.00 | 0.83 |
December | 0.889424E+11 | 0.00 | 0.00 | 26423577.32 | 0.00 | 0.321413E+10 | 0.221072E+11 | 0.00 | 0.80 |
Annual Sum or Average | 0.667632E+12 | 0.835416E+10 | 0.00 | 0.720097E+09 | 0.259669E+09 | 0.171841E+11 | 0.426434E+12 | 0.00 | 1.06 |
Minimum of Months | 0.253935E+11 | 0.00 | 0.00 | 15976302.34 | 0.00 | 0.00 | 0.165982E+11 | 0.00 | 0.80 |
Maximum of Months | 0.914568E+11 | 0.593251E+10 | 0.00 | 0.107510E+09 | 0.177235E+09 | 0.103568E+11 | 0.567298E+11 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.857014E+11 | 0.00 | 0.00 | 50455.10 | 0.00 | 0.850007E+10 | 0.322813E+09 | 0.00 | 0.99 |
February | 0.726433E+11 | 0.00 | 0.00 | 3522747.70 | 0.00 | 0.269835E+10 | 0.389738E+10 | 0.00 | 1.01 |
March | 0.707142E+11 | 0.00 | 0.00 | 11549283.92 | 0.00 | 37203354.36 | 0.122480E+11 | 0.00 | 1.09 |
April | 0.485408E+11 | 52720035.55 | 0.00 | 27663128.41 | 6728846.42 | 0.00 | 0.235789E+11 | 0.00 | 1.19 |
May | 0.392636E+11 | 15754194.67 | 0.00 | 57352668.97 | 24607646.40 | 0.00 | 0.326829E+11 | 0.00 | 1.43 |
June | 0.280565E+11 | 75571953.22 | 0.00 | 56781363.62 | 11186734.51 | 0.00 | 0.318078E+11 | 0.00 | 1.53 |
July | 0.194693E+11 | 0.208511E+10 | 0.00 | 67488219.56 | 43307294.86 | 0.00 | 0.255756E+11 | 0.00 | 1.57 |
August | 0.209498E+11 | 0.459372E+10 | 0.00 | 51631699.69 | 41773052.89 | 0.00 | 0.175977E+11 | 0.00 | 1.54 |
September | 0.376810E+11 | 0.141706E+09 | 0.00 | 37785612.37 | 45901800.46 | 0.00 | 0.207388E+11 | 0.00 | 1.46 |
October | 0.604918E+11 | 0.00 | 0.00 | 12601553.68 | 0.00 | 0.00 | 0.110485E+11 | 0.00 | 1.15 |
November | 0.744737E+11 | 0.00 | 0.00 | 782823.34 | 0.00 | 0.152039E+09 | 0.130196E+10 | 0.00 | 0.98 |
December | 0.851625E+11 | 0.00 | 0.00 | 344178.47 | 0.00 | 0.153068E+10 | 0.925784E+09 | 0.00 | 0.95 |
Annual Sum or Average | 0.643148E+12 | 0.696459E+10 | 0.00 | 0.327554E+09 | 0.173505E+09 | 0.129183E+11 | 0.181726E+12 | 0.00 | 1.24 |
Minimum of Months | 0.194693E+11 | 0.00 | 0.00 | 50455.10 | 0.00 | 0.00 | 0.322813E+09 | 0.00 | 0.95 |
Maximum of Months | 0.857014E+11 | 0.459372E+10 | 0.00 | 67488219.56 | 45901800.46 | 0.850007E+10 | 0.326829E+11 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309571E+10 | 0.00 | 0.00 | 0.52 |
February | 0.387723E+10 | 0.00 | 0.00 | 57850.27 | 0.00 | 0.184578E+10 | 0.117486E+09 | 0.00 | 0.52 |
March | 0.493078E+10 | 0.00 | 0.00 | 330010.43 | 0.00 | 0.641742E+09 | 0.516913E+09 | 0.00 | 0.54 |
April | 0.334387E+10 | 1935.91 | 0.00 | 2189953.63 | 185928.40 | 0.233123E+09 | 0.162934E+10 | 0.00 | 0.56 |
May | 0.240477E+10 | 529115.12 | 0.00 | 5086208.95 | 0.00 | 12964481.21 | 0.322070E+10 | 0.00 | 0.71 |
June | 0.143461E+10 | 808790.82 | 0.00 | 7172203.98 | 457032.12 | 0.00 | 0.364123E+10 | 0.00 | 0.82 |
July | 0.102903E+10 | 94664218.12 | 0.00 | 7309861.06 | 3715884.33 | 0.00 | 0.269806E+10 | 0.00 | 0.81 |
August | 0.111664E+10 | 0.279354E+09 | 0.00 | 5972645.24 | 5663816.24 | 0.00 | 0.184124E+10 | 0.00 | 0.80 |
September | 0.221234E+10 | 841384.97 | 0.00 | 3936969.84 | 2409580.48 | 0.00 | 0.185802E+10 | 0.00 | 0.67 |
October | 0.393567E+10 | 0.00 | 0.00 | 806358.14 | 0.00 | 0.223314E+09 | 0.723278E+09 | 0.00 | 0.53 |
November | 0.449370E+10 | 0.00 | 0.00 | 9212.64 | 0.00 | 0.113862E+10 | 34403838.34 | 0.00 | 0.52 |
December | 0.379750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273781E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.363831E+11 | 0.376199E+09 | 0.00 | 32871274.16 | 12432241.56 | 0.992906E+10 | 0.162807E+11 | 0.00 | 0.63 |
Minimum of Months | 0.102903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.493078E+10 | 0.279354E+09 | 0.00 | 7309861.06 | 5663816.24 | 0.309571E+10 | 0.364123E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.503959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418280E+10 | 0.00 | 0.00 | 1.08 |
February | 0.561523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220570E+10 | 0.00 | 0.00 | 1.09 |
March | 0.683342E+10 | 0.00 | 0.00 | 366961.04 | 0.00 | 0.663659E+09 | 0.690912E+09 | 0.00 | 1.13 |
April | 0.423845E+10 | 1554.11 | 0.00 | 2911919.31 | 250046.80 | 0.209143E+09 | 0.252027E+10 | 0.00 | 1.15 |
May | 0.365953E+10 | 330542.53 | 0.00 | 4260526.73 | 351682.45 | 35531175.96 | 0.314767E+10 | 0.00 | 1.31 |
June | 0.232756E+10 | 661584.51 | 0.00 | 6960668.37 | 614642.09 | 338045.03 | 0.391922E+10 | 0.00 | 1.51 |
July | 0.182744E+10 | 79436567.35 | 0.00 | 7063122.42 | 9910557.41 | 0.00 | 0.260520E+10 | 0.00 | 1.44 |
August | 0.178398E+10 | 0.235989E+09 | 0.00 | 6066310.16 | 18418813.51 | 0.00 | 0.194260E+10 | 0.00 | 1.50 |
September | 0.338016E+10 | 699343.31 | 0.00 | 3780705.37 | 3240537.22 | 1315488.12 | 0.192807E+10 | 0.00 | 1.32 |
October | 0.533217E+10 | 0.00 | 0.00 | 788992.44 | 0.00 | 0.371660E+09 | 0.852928E+09 | 0.00 | 1.11 |
November | 0.600573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160484E+10 | 0.00 | 0.00 | 1.08 |
December | 0.522260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352220E+10 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.512659E+11 | 0.317118E+09 | 0.00 | 32199205.84 | 32786279.48 | 0.127972E+11 | 0.176069E+11 | 0.00 | 1.23 |
Minimum of Months | 0.178398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.683342E+10 | 0.235989E+09 | 0.00 | 7063122.42 | 18418813.51 | 0.418280E+10 | 0.391922E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.809855E+10 | 0.00 | 0.00 | 646774.79 | 0.00 | 0.358462E+10 | 0.972232E+09 | 0.00 | 0.96 |
February | 0.681064E+10 | 0.00 | 0.00 | 2917496.71 | 0.00 | 0.210018E+10 | 0.274195E+10 | 0.00 | 1.05 |
March | 0.729312E+10 | 0.00 | 0.00 | 5400908.27 | 0.00 | 0.100072E+10 | 0.450657E+10 | 0.00 | 1.15 |
April | 0.561803E+10 | 348017.56 | 0.00 | 5976783.04 | 0.00 | 0.369967E+09 | 0.416934E+10 | 0.00 | 1.10 |
May | 0.511508E+10 | 921420.46 | 0.00 | 6023961.17 | 0.00 | 44382003.84 | 0.415995E+10 | 0.00 | 1.16 |
June | 0.396583E+10 | 929438.56 | 0.00 | 6278673.07 | 830142.27 | 0.00 | 0.367199E+10 | 0.00 | 1.21 |
July | 0.285933E+10 | 0.129127E+09 | 0.00 | 7123605.04 | 10558898.03 | 0.00 | 0.280661E+10 | 0.00 | 1.21 |
August | 0.261911E+10 | 0.453243E+09 | 0.00 | 6966299.09 | 13972980.28 | 0.00 | 0.220437E+10 | 0.00 | 1.31 |
September | 0.415355E+10 | 10297126.16 | 0.00 | 10291014.31 | 0.00 | 256292.68 | 0.396267E+10 | 0.00 | 1.40 |
October | 0.570865E+10 | 0.00 | 0.00 | 6541805.98 | 0.00 | 0.382949E+09 | 0.456225E+10 | 0.00 | 1.19 |
November | 0.790348E+10 | 0.00 | 0.00 | 1434263.47 | 0.00 | 0.149883E+10 | 0.121161E+10 | 0.00 | 0.98 |
December | 0.721169E+10 | 0.00 | 0.00 | 1457124.24 | 0.00 | 0.336930E+10 | 0.168307E+10 | 0.00 | 0.96 |
Annual Sum or Average | 0.673571E+11 | 0.594865E+09 | 0.00 | 61058709.18 | 25362020.58 | 0.123512E+11 | 0.366526E+11 | 0.00 | 1.14 |
Minimum of Months | 0.261911E+10 | 0.00 | 0.00 | 646774.79 | 0.00 | 0.00 | 0.972232E+09 | 0.00 | 0.96 |
Maximum of Months | 0.809855E+10 | 0.453243E+09 | 0.00 | 10291014.31 | 13972980.28 | 0.358462E+10 | 0.456225E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.700413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320887E+10 | 0.00 | 0.00 | 1.20 |
February | 0.669764E+10 | 0.00 | 0.00 | 184445.58 | 0.00 | 0.169258E+10 | 0.274708E+09 | 0.00 | 1.21 |
March | 0.758016E+10 | 0.00 | 0.00 | 808538.39 | 0.00 | 0.668461E+09 | 0.929653E+09 | 0.00 | 1.27 |
April | 0.553971E+10 | 204043.70 | 0.00 | 2606720.68 | 75621.24 | 0.225677E+09 | 0.194451E+10 | 0.00 | 1.29 |
May | 0.447295E+10 | 414735.23 | 0.00 | 5170832.92 | 341021.98 | 19051150.69 | 0.308438E+10 | 0.00 | 1.48 |
June | 0.330261E+10 | 1655537.91 | 0.00 | 5482477.01 | 680890.03 | 0.00 | 0.300912E+10 | 0.00 | 1.60 |
July | 0.212919E+10 | 0.152334E+09 | 0.00 | 7884306.90 | 1891985.11 | 0.00 | 0.261519E+10 | 0.00 | 1.65 |
August | 0.226931E+10 | 0.353269E+09 | 0.00 | 5323964.69 | 11538484.30 | 0.00 | 0.159638E+10 | 0.00 | 1.60 |
September | 0.420401E+10 | 2136038.94 | 0.00 | 3709505.75 | 2462984.28 | 0.00 | 0.159105E+10 | 0.00 | 1.48 |
October | 0.632944E+10 | 0.00 | 0.00 | 934470.76 | 0.00 | 0.198784E+09 | 0.784008E+09 | 0.00 | 1.24 |
November | 0.738525E+10 | 0.00 | 0.00 | 16427.75 | 0.00 | 0.976571E+09 | 67348731.00 | 0.00 | 1.19 |
December | 0.737583E+10 | 0.00 | 0.00 | 910.03 | 0.00 | 0.229722E+10 | 11733966.61 | 0.00 | 1.18 |
Annual Sum or Average | 0.642902E+11 | 0.510013E+09 | 0.00 | 32122600.47 | 16990986.93 | 0.928722E+10 | 0.159081E+11 | 0.00 | 1.37 |
Minimum of Months | 0.212919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
Maximum of Months | 0.758016E+10 | 0.353269E+09 | 0.00 | 7884306.90 | 11538484.30 | 0.320887E+10 | 0.308438E+10 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:03:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17012254.17 | 0.00 | 0.00 | 0.213025E+09 | 0.00 | 0.00 | 0.140381E+11 | 0.00 | 0.32 |
February | 3657941.85 | 0.00 | 0.00 | 0.390952E+09 | 0.00 | 0.00 | 0.116397E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.680988E+09 | 0.00 | 0.00 | 0.119324E+11 | 0.00 | 0.34 |
April | 0.00 | 3723236.67 | 0.00 | 0.817798E+09 | 0.00 | 0.00 | 0.855879E+10 | 0.00 | 0.32 |
May | 0.00 | 5522109.30 | 0.00 | 0.209069E+09 | 0.00 | 0.00 | 0.722218E+10 | 0.00 | 0.33 |
June | 0.00 | 2437388.82 | 0.00 | 0.422238E+09 | 0.00 | 0.00 | 0.512254E+10 | 0.00 | 0.34 |
July | 0.00 | 0.128749E+09 | 0.00 | 0.514448E+09 | 0.00 | 0.00 | 0.282185E+10 | 0.00 | 0.31 |
August | 0.00 | 0.289947E+09 | 0.00 | 0.672384E+09 | 0.00 | 0.00 | 0.215457E+10 | 0.00 | 0.34 |
September | 0.00 | 9411499.20 | 0.00 | 0.199156E+09 | 0.00 | 0.00 | 0.470867E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.417746E+09 | 0.00 | 0.00 | 0.813726E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.598867E+09 | 0.00 | 0.00 | 0.102143E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.828349E+09 | 0.00 | 0.00 | 0.126874E+11 | 0.00 | 0.31 |
Annual Sum or Average | 20670196.02 | 0.439790E+09 | 0.00 | 0.596502E+10 | 0.00 | 0.00 | 0.992379E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.199156E+09 | 0.00 | 0.00 | 0.215457E+10 | 0.00 | 0.31 |
Maximum of Months | 17012254.17 | 0.289947E+09 | 0.00 | 0.828349E+09 | 0.00 | 0.00 | 0.140381E+11 | 0.00 | 0.34 |