Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:02
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2020-06-03 20:02:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31087.75 | 671.15 | 671.15 |
Net Site Energy | 31087.75 | 671.15 | 671.15 |
Total Source Energy | 96539.10 | 2084.16 | 2084.16 |
Net Source Energy | 96539.10 | 2084.16 | 2084.16 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 369.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3509.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 884.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2044.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2208.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1398.76 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.89 |
Humidification | 6.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 550.62 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30168.02 | 919.74 | 0.00 | 0.00 | 0.00 | 7061.56 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 369.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1133.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2376.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 4294.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 884.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2208.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 138.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1260.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.89 | |
Humidification | General | 6.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 550.62 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.91 | 19.86 | 0.00 | 0.00 | 0.00 | 0.15 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 651.29 | 19.86 | 0.00 | 0.00 | 0.00 | 0.15 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 111.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.91 | 19.86 | 0.00 | 0.00 | 0.00 | 0.15 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 651.29 | 19.86 | 0.00 | 0.00 | 0.00 | 0.15 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30168.016 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30168.016 | 100.00 |
Total On-Site and Utility Electric Sources | 30168.016 | 100.00 |
Total Electricity End Uses | 30168.016 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7061.56 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7061.56 | 100.00 |
Total Water End Uses | 7061.56 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 164.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 809.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.6875 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.6875 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.6875 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.6875 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.6875 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.6875 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:50 | 22-DEC-07:10 | - | - | - | 16-OCT-11:09 |
Heating | 0.00 | 609378.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 450325.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 92996.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 125524.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55434.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 82332.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1973943.13 | 617524.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 609378.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 304292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 125524.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 55434.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 33083.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 400.12 | 0.00 | 0.00 | 0.00 |
Cooling | 11116.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13600.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2802.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6473.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6993.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1925.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4429.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 596.87 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 95542.11 | 996.99 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.64 | 0.00 | 0.00 | 0.00 |
Cooling | 239.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.89 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2062.64 | 21.52 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.64 | 0.00 | 0.00 | 0.00 |
Cooling | 239.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 139.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.89 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2062.64 | 21.52 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.75 |
DATACENTER BOT DIRECT AIR | 0.470742 |
DATACENTER MID DIRECT AIR | 4.47 |
DATACENTER TOP DIRECT AIR | 0.455019 |
DATACENTER BASEMENT DIRECT AIR | 21.59 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.99 | 0.317643 | 0.300000 | 1.80 | 0.847048 | 0.500000 | 0.001199 | 0.000392 | 1.80 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.40 | 0.337269 | 0.304000 | 17.14 | 0.899384 | 0.500000 | 0.001130 | 0.007170 | 17.14 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.54 | 0.343490 | 0.309000 | 1.71 | 0.915974 | 0.500000 | 0.001109 | 0.001371 | 1.88 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.852895 | 0.280012 | 0.300000 | 0.255868 | 0.746698 | 0.500000 | 0.001361 | 0.000086 | 0.255868 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.944841 | 0.162890 | 0.300000 | 0.283452 | 0.434373 | 0.500000 | 0.002339 | 0.000089 | 0.283452 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.03 | 0.232488 | 0.300000 | 0.308179 | 0.619967 | 0.500000 | 0.001639 | 0.000138 | 0.308179 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.18 | 0.130656 | 0.300000 | 0.353384 | 0.348415 | 0.500000 | 0.002916 | 0.000079 | 0.353384 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.72 | 0.309392 | 0.304000 | 2.35 | 0.825046 | 0.500000 | 0.001231 | 0.002662 | 3.66 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.56 | 0.161023 | 0.304000 | 2.91 | 0.429396 | 0.500000 | 0.002366 | 0.001897 | 2.91 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.48 | 0.251845 | 0.304000 | 2.88 | 0.671587 | 0.500000 | 0.001513 | 0.002700 | 3.71 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 9.78 | 0.157364 | 0.304000 | 2.97 | 0.419637 | 0.500000 | 0.002421 | 0.001731 | 2.97 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.887072 | 0.269223 | 0.309000 | 0.274105 | 0.717929 | 0.500000 | 0.001415 | 0.000380 | 0.522536 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.941412 | 0.163483 | 0.309000 | 0.290896 | 0.435955 | 0.500000 | 0.002331 | 0.000252 | 0.346740 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.05 | 0.226850 | 0.309000 | 0.325312 | 0.604934 | 0.500000 | 0.001680 | 0.000383 | 0.526160 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.05 | 0.146247 | 0.309000 | 0.325181 | 0.389992 | 0.500000 | 0.002605 | 0.000235 | 0.325181 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17751.30 | 0.000392 | 308.97 |
CORE_MID VAV BOX REHEAT COIL | 324531.17 | 0.007170 | 6064.55 |
CORE_TOP VAV BOX REHEAT COIL | 62034.73 | 0.001371 | 1295.76 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3869.88 | 0.000086 | 70.64 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4033.88 | 0.000089 | 73.26 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6232.95 | 0.000138 | 117.50 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3579.21 | 0.000079 | 62.47 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 120471.79 | 0.002662 | 2514.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 85861.29 | 0.001897 | 1738.79 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 122219.25 | 0.002700 | 2550.72 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 78361.94 | 0.001731 | 1545.79 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17204.95 | 0.000380 | 358.98 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11415.88 | 0.000252 | 238.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17323.99 | 0.000383 | 361.46 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10614.80 | 0.000235 | 220.90 |
CAV_BAS_HEATC | 267605.72 | 0.005912 | 5008.98 |
VAV_BOT WITH REHEAT_HEATC | 29735.21 | 0.000657 | 452.41 |
VAV_MID WITH REHEAT_HEATC | 278206.50 | 0.006147 | 4231.53 |
VAV_TOP WITH REHEAT_HEATC | 28748.35 | 0.000635 | 437.26 |
DATACENTER_EXTRAWATERHEATC | 1023912.82 | 0.022622 | 19067.47 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.75 | 5.75 | 5.75 | 5.75 | 5.75 | 5.75 | 1.00 | 1.00 | 5.75 |
VAV_BOT WITH REHEAT | 5.00 | 3.00 | 9.99 | 3.00 | 9.36 | 9.36 | 0.300000 | 0.320148 | 9.36 |
VAV_MID WITH REHEAT | 46.47 | 28.25 | 92.94 | 28.25 | 86.77 | 86.77 | 0.300000 | 0.325607 | 86.77 |
VAV_TOP WITH REHEAT | 4.74 | 2.93 | 9.47 | 3.59 | 8.97 | 8.97 | 0.300000 | 0.400823 | 8.97 |
AIRLOOP DATACENTER BASEMENT | 21.59 | 21.59 | 21.59 | 21.59 | 21.59 | 21.59 | 1.00 | 1.00 | 21.59 |
AIRLOOP DATACENTER BOT | 0.470742 | 0.470742 | 0.470742 | 0.470742 | 0.470742 | 0.470742 | 1.00 | 1.00 | 0.470742 |
AIRLOOP DATACENTER MID | 4.47 | 4.47 | 4.47 | 4.47 | 4.47 | 4.47 | 1.00 | 1.00 | 4.47 |
AIRLOOP DATACENTER TOP | 0.455019 | 0.455019 | 0.455019 | 0.455019 | 0.455019 | 0.455019 | 1.00 | 1.00 | 0.455019 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.75 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.36 | 2.71 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 86.77 | 28.28 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.97 | 2.92 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.59 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.470742 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.47 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.455019 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 95135.58 | 0.004047 | 5.75 | 0.008790 | 24.27 | 6.67 | 11.27 | 0.008436 |
VAV_BOT WITH REHEAT_COOLC | 178129.16 | 0.007578 | 9.36 | 0.008658 | 26.29 | 6.67 | 11.27 | 0.008436 |
VAV_MID WITH REHEAT_COOLC | 1691315.01 | 0.071952 | 86.77 | 0.008648 | 26.70 | 6.67 | 11.27 | 0.008436 |
VAV_TOP WITH REHEAT_COOLC | 171057.06 | 0.007277 | 8.97 | 0.008638 | 26.38 | 6.67 | 11.27 | 0.008436 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.75 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.004047 | 0.000118 |
CAV_BAS_HEATC_CONTROLLER | 0.005912 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007578 | 0.000063 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000657 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.071952 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.006147 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007277 | 0.000065 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000635 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022622 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.36 |
VAV_MID WITH REHEAT FAN | 86.77 |
VAV_TOP WITH REHEAT FAN | 8.97 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.59 | 424273.93 | 302390.63 | 0.010390 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.470742 | 9020.08 | 6510.05 | 0.000221 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.47 | 85621.27 | 61786.01 | 0.002097 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.455019 | 8719.94 | 6292.85 | 0.000214 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.59 | 21.59 | 21.59 | 21.59 | 424273.93 | 424273.93 | 14546.00 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.470742 | 0.470742 | 0.470742 | 0.470742 | 9020.08 | 9020.08 | 671.96 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.47 | 4.47 | 4.47 | 4.47 | 85621.27 | 85621.27 | 6719.65 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.455019 | 0.455019 | 0.455019 | 0.455019 | 8719.94 | 8719.94 | 671.96 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.59 |
DATACENTER BOT SUPPLY FAN | 0.470742 |
DATACENTER MID SUPPLY FAN | 4.47 |
DATACENTER TOP SUPPLY FAN | 0.455019 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.59 | 424273.93 | 0.010390 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.470742 | 9020.08 | 0.000221 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.47 | 85621.27 | 0.002097 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.455019 | 8719.94 | 0.000214 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 14546.00 | |
DATACENTER_EXTRAELECHEATC | 424273.93 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 671.96 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 6719.65 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 671.96 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000085 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.090855 | 21760.53 |
HEATSYS1 PUMP | 0.055537 | 14189.11 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.090855 | 10.90 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.055537 | 6.66 |
COOLSYS1_SUPPLY | 0.090855 | 10.90 |
SINGLE WATER PLANT LOOP | 0.012922 | 1.55 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.090855 | 0.090855 | 381363.72 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 PUMP | 0.090855 | 7253.51 |
PLANT CIRC PUMP | 0.012922 | 3295.69 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2513715.62 | 1256857.81 | 0.055537 |
DUMMY BOILER | 532265.43 | 93894.07 | 0.012922 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.090855 | 0.045685 | 1076504.10 | 1081610.35 | 0.053729 |
COOLSYS1 CHILLER2 | 0.090855 | 0.045685 | 1076504.10 | 1081610.35 | 0.053729 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.012922 | 139666.47 | 60870.65 | 69833.23 | 7879.72 | 21567.81 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.107459 | 12.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.107459 | 27453.15 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 44.36 | 1027324.96 | 8.87 | 128415.62 |
TOWERWATERSYS COOLTOWER 2 | 44.36 | 1027324.96 | 8.87 | 128415.62 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.044476 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.688 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.529 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.758 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.688 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.757 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 9.688 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.987 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 9.688 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 26925.749 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26925.749 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 24181.215 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24181.215 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3036.193 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.193 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3036.259 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3036.259 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1956.638 | 9.688 | 179.982 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1956.638 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 7591.909 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7591.909 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 350.715 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 350.715 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.6890 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.284 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.23694873E-14 | 0.24460372E-16 | -0.16093703E-09 | 0.40693747E-16 |
51 | 8 | 0.23448185E-07 | 0.93803824E-13 | 0.39412945E-03 | -0.26661394E-09 |
52 | 7 | -0.12728387E-01 | 0.47911758E-08 | -0.23786565E-01 | 0.14472641E-03 |
53 | 6 | 0.41857762 | 0.16585077E-05 | 0.48334039 | -0.49036802E-02 |
54 | 5 | -5.3196350 | 0.61661373E-04 | -4.5275917 | 0.64784285E-01 |
55 | 4 | 33.573705 | 0.50245725E-03 | 21.777630 | -0.42970229 |
56 | 3 | -112.44059 | 0.10912898E-02 | -56.290775 | 1.5327395 |
57 | 2 | 198.33458 | 0.61196217E-03 | 78.486619 | -2.9198277 |
58 | 1 | -171.60898 | 0.65143140E-04 | -55.433097 | 2.7533770 |
59 | 0 | 57.057407 | 0.36965150E-06 | 15.529602 | |
60 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
61 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
62 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
63 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
64 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
65 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
66 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
67 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
68 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
69 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
70 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
71 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
72 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
73 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
74 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
75 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
76 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
77 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
78 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
79 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
80 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
81 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
82 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
83 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
84 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
85 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
86 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
87 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
88 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
89 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
90 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
91 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.46_SHGC_0.25 | 29 | 1 | VerySmooth | 2.615 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.53892E-002 | 0.16139 | 0.61607 | 0.61607 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.213 | 6.810E-004 | 1.024E-003 | 0.893 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 0.141 | 6.979E-004 | 1.024E-003 | 0.916 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.213 | 6.810E-004 | 1.024E-003 | 0.893 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 0.141 | 6.979E-004 | 1.024E-003 | 0.916 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.205 | 6.555E-004 | 1.024E-003 | 0.860 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 0.137 | 6.781E-004 | 1.024E-003 | 0.890 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.205 | 6.555E-004 | 1.024E-003 | 0.860 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 0.137 | 6.781E-004 | 1.024E-003 | 0.890 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.205 | 6.555E-004 | 1.024E-003 | 0.860 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 0.137 | 6.781E-004 | 1.024E-003 | 0.890 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.205 | 6.555E-004 | 1.024E-003 | 0.860 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 0.137 | 6.781E-004 | 1.024E-003 | 0.890 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.304 | 8.540E-005 | 1.024E-003 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.304 | 8.540E-005 | 1.024E-003 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.304 | 8.534E-005 | 7.878E-005 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78341.19688 | 78341.19688 | 5.74772 | 5.74772 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 81623.59048 | 81623.59048 | 5.98800 | 5.98800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 768931.12956 | 768931.12956 | 56.39544 | 56.39544 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 155118.85269 | 155118.85269 | 6.60433 | 10.77757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 74796.91855 | 74796.91855 | 5.53741 | 5.53741 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.20219E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 43484.21375 | 43484.21375 | 1.87728 | 1.87728 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11520.71044 | 11520.71044 | 0.85289 | 0.85289 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.20219E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1345.46960 | 1345.46960 | 5.87622E-002 | 0.13532 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12855.68277 | 12855.68277 | 0.94484 | 0.94484 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1242.57747 | 1242.57747 | 5.34516E-002 | 8.72074E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13876.05347 | 13876.05347 | 1.02726 | 1.02726 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 30.73633 | 8.20219E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3195.63186 | 3195.63186 | 0.13712 | 0.13712 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 15911.56458 | 15911.56458 | 1.17795 | 1.17795 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 104.59988 | 104.59988 | 4.56836E-003 | 8.72074E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 105200.84641 | 105200.84641 | 7.71902 | 7.71902 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.20219E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 84386.87537 | 84386.87537 | 3.65566 | 3.65566 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 129107.92576 | 129107.92576 | 9.55793 | 9.55793 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.20219E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 57177.71508 | 57177.71508 | 2.47760 | 2.47760 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 128095.32385 | 128095.32385 | 9.48305 | 9.48305 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.20219E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 85608.15155 | 85608.15155 | 3.70886 | 3.70886 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 132109.80428 | 132109.80428 | 9.78020 | 9.78020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.20219E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 49020.74982 | 49020.74982 | 2.12233 | 2.12233 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11982.42240 | 11982.42240 | 0.88707 | 0.88707 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.20219E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12044.23620 | 12044.23620 | 0.52254 | 0.52254 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 12716.53019 | 12716.53019 | 0.94141 | 0.94141 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 7991.30706 | 7991.30706 | 0.34674 | 0.34674 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14220.94743 | 14220.94743 | 1.05279 | 1.05279 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.20219E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12127.43975 | 12127.43975 | 0.52616 | 0.52616 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 14215.24705 | 14215.24705 | 1.05236 | 1.05236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7403.49846 | 7403.49846 | 0.32114 | 0.32114 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8062.69961 | 8062.69961 | 0.47074 | 0.47074 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 22.45933 | 8.20219E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76517.27766 | 76517.27766 | 4.46747 | 4.46747 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 22.45933 | 8.20219E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7793.40015 | 7793.40015 | 0.45502 | 0.45502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.20219E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369748.64663 | 369748.64663 | 21.58783 | 21.58783 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 22.68183 | 8.20219E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 77909.28 | 5.74772 | 5.74772 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 51589.39 | 1.20008 | 1.20008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 138317.14 | 9.36218 | 9.36218 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 16294.59 | 1.52461 | 1.52461 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1262541.22 | 86.76857 | 86.76857 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 243059.55 | 22.74202 | 22.74202 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 144544.58 | 8.96619 | 8.96619 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 31061.92 | 3.59385 | 3.59385 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365183.93 | 21.58783 | 21.58783 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14546.00 | 0.33837 | 0.33837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7958.47 | 0.47074 | 0.47074 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 671.96 | 1.56314E-002 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75657.15 | 4.46747 | 4.46747 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6719.65 | 0.15631 | 0.15631 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7713.06 | 0.45502 | 0.45502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 671.96 | 1.56314E-002 | 1.56314E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.74772 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.98800 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31764 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79640 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84705 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19946E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.92193E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79640 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17751.29629 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.92193E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 308.96588 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.39544 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33727 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 17.14422 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89938 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12966E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.17012E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 17.14422 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 324531.17173 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.17012E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6064.55240 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.53741 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34349 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.71106 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91597 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10920E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37058E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87728 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 62034.72657 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37058E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1295.75689 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85289 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28001 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25587 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74670 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36066E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.55003E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25587 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3869.88075 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.55003E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 70.63540 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94484 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16289 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28345 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43437 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33900E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.91237E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28345 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4033.88181 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.91237E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 73.25815 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02726 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23249 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30818 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61997 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63880E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37709E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30818 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6232.94632 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37709E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 117.49598 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17795 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13066 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35338 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34841 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91607E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.90783E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35338 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3579.21291 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.90783E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 62.46534 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.71902 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30939 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.34658 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82505 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23145E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.66168E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.65566 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120471.79418 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66168E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2514.28348 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.55793 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16102 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.90561 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42940 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36612E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89700E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.90561 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85861.29369 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89700E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1738.79357 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.48305 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25185 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.88285 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67159 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51284E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70029E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.70886 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122219.25418 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70029E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2550.71793 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.78020 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15736 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.97318 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41964 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42114E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73131E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.97318 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 78361.93911 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73131E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1545.79328 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88707 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26922 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27411 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71793 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41518E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.80122E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52254 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17204.95324 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.80122E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 358.97734 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94141 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16348 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29090 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43596 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33051E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.52220E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34674 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11415.87869 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52220E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.18428 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05279 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22685 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32531 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60493 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67952E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.82752E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52616 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17323.98888 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.82752E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 361.45903 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05236 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14625 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32518 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38999 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60518E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.34521E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32518 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10614.80207 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34521E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.90292 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47074 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.46747 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45502 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.58783 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.74772 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.74772 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74772 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.74772 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.74772 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.74772 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.99547 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.99728 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.99094 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.99728 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.36218 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.36218 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32015 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 46.46782 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.25243 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 92.93564 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.25243 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 86.76857 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 86.76857 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32561 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.73552 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.92655 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.47104 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.59385 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.96619 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.96619 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.40082 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.58783 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.58783 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.58783 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.58783 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.58783 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.58783 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47074 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47074 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47074 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47074 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47074 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47074 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.46747 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.46747 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.46747 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.46747 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.46747 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.46747 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45502 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45502 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45502 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45502 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45502 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45502 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.74772 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.36218 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 86.76857 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.96619 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.58783 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47074 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.46747 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45502 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.74772 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 95135.58355 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.04729E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.74772 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.78974E-003 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.26691 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.26782 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 267605.72319 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.91242E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 5008.98416 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.74772 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.04729E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.17657E-004 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.91242E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.36218 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.70627 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 178129.16230 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.57803E-003 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.36218 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.65779E-003 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.28669 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.26745 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 29735.20756 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.56963E-004 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 452.40907 |
318 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.36218 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.57803E-003 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.28383E-005 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.56963E-004 |
322 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 86.76857 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 28.28001 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 1691315.01486 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.19524E-002 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 86.76857 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.64773E-003 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.69788 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.26742 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 278206.50096 |
333 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.14663E-003 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 4231.53037 |
335 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 86.76857 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.19524E-002 |
337 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.61813E-006 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.14663E-003 |
339 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.96619 |
340 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.92251 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 171057.05604 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.27716E-003 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.96619 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.63782E-003 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.37930 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.26739 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
349 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 28748.35249 |
350 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.35160E-004 |
351 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 437.26342 |
352 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.96619 |
353 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.27716E-003 |
354 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.54363E-005 |
355 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.35160E-004 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.58783 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.58783 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 424273.92807 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 302390.62944 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03904E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.58783 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.58783 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.58783 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.58783 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 424273.92807 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 424273.92807 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14545.99987 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.58783 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.58783 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 424273.92807 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03904E-002 |
374 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 14545.99987 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 8.45802E-005 |
376 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 424273.92807 |
380 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
381 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1023912.81854 |
382 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.26221E-002 |
383 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19067.47301 |
384 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26221E-002 |
385 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.10498E-005 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47074 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.47074 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9020.08498 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6510.05141 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.20901E-004 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47074 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47074 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47074 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47074 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9020.08498 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9020.08498 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 671.96493 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
399 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47074 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.47074 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9020.08498 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.20901E-004 |
403 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 671.96493 |
404 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.46747 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.46747 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 85621.26535 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 61786.01327 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.09686E-003 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.46747 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.46747 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.46747 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.46747 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 85621.26535 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 85621.26535 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6719.64934 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.46747 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.46747 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 85621.26535 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.09686E-003 |
421 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 6719.64934 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45502 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45502 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 8719.94021 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6292.84846 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.13551E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45502 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45502 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45502 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45502 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8719.94021 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8719.94021 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 671.96493 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45502 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45502 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 8719.94021 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.13551E-004 |
439 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 671.96493 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.08549E-002 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 21760.53306 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.08549E-002 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.90259 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.08549E-002 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.08549E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 381363.71728 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
448 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
449 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
450 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
451 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
452 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
453 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.55375E-002 |
454 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.66450 |
455 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.55375E-002 |
456 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 14189.11272 |
457 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2513715.62314 |
458 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1256857.81000 |
459 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.55375E-002 |
460 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.08549E-002 |
461 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.90259 |
462 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.08549E-002 |
463 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 7253.51102 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.08549E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.56848E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1076504.10456 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1081610.35500 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.37295E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.08549E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.56848E-002 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1076504.10456 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1081610.35500 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.37295E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.29218E-002 |
475 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.55061 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.29218E-002 |
477 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3295.69308 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.29218E-002 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60870.65472 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21567.80539 |
484 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 532265.42601 |
485 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
486 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.29218E-002 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10746 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.89507 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10746 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 27453.15111 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 44.36141 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1027324.95674 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.87228 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 128415.61959 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 44.36141 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1027324.95674 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.87228 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 128415.61959 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.44760E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.44760E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16841.09 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 308119.97 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 58859.51 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3675.07 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3831.00 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5917.40 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3395.64 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 114305.76 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 81476.10 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 115963.79 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 74372.34 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16324.38 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10831.60 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16437.32 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10071.60 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 217000.53 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 24998.95 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 233634.36 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 24142.51 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 823292.57 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 141992.09 | 99245.16 | 42746.94 | 0.70 | 18417.94 | 186.80 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 245267.63 | 167651.66 | 77615.97 | 0.68 | 31053.71 | 314.96 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2290025.32 | 1560744.26 | 729281.06 | 0.68 | 287539.36 | 2916.38 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 235030.43 | 160611.15 | 74419.28 | 0.68 | 29712.48 | 301.36 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.89 | 23.50 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.89 | 23.50 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3032207919 | 0.3786913862 | Pass | Pass | 1.1427942558 | 1.5085039881 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.3804274800E-002 | 0.1508184283 | Pass | Pass | 1.3982112979E-002 | 0.1169872118 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.4905257727E-003 | 2.4511659880E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.3368480239E-002 | 8.7709313781E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.5985691595E-002 | 9.9309525025E-002 | Pass | Pass | 1.3957336465E-002 | 0.1166923603 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.9071051368E-002 | 0.1919763045 | Pass | Pass | 1.3889388152E-002 | 0.1167415573 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.9522596562E-002 | 0.1247136124 | Pass | Pass | 1.4042018200E-002 | 0.1169676306 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.3759863167E-002 | 0.2010555686 | Pass | Pass | 1.3892984963E-002 | 0.1149910020 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3468054836E-002 | 2.6265730645E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.2805223664E-002 | 9.2594189824E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.0065293402E-002 | 6.9676649688E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.3370812076E-002 | 3.1207430894E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7016950642E-002 | 2.4846173546E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1679199082E-002 | 8.8114326415E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.1267054511E-002 | 6.8316356085E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7855465612E-002 | 3.0921097004E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1251128345E-002 | 2.1845092244E-002 | Pass | Pass | 1.5829983509E-002 | 0.1270915982 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1211918469E-003 | 1.0666919831E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5867751648E-002 | 3.5680657022E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2032452421E-014 | 3.7127956153E-014 | Pass | Pass | 2.1313317479E-003 | 2.0880012302E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0600805012E-014 | 1.6571820844E-014 | Pass | Pass | 6.4990703236E-003 | 5.1436072890E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2343547564E-002 | 1.7743851992E-002 | Pass | Pass | 4.0788444356E-002 | 0.1074879649 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.4877681818E-014 | 6.1824344761E-014 | Pass | Pass | 2.7384677785E-005 | 2.4165287002E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.46_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.615 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.615 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.615 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.615 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.615 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.615 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.615 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.615 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.615 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.615 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 1043.06 | 2.615 | 0.252 | 0.251 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.615 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 9.6875 | 2779.43 | 26925.75 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 257.68 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
CORE_MID_LIGHTS | CORE_MID | 9.6875 | 24961.20 | 241812.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 2314.14 |
CORE_TOP_LIGHTS | CORE_TOP | 9.6875 | 2496.12 | 24181.22 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 231.41 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 9.6875 | 3134.13 | 30361.93 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 9.6875 | 3134.20 | 30362.59 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 290.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 9.6875 | 2019.75 | 19566.38 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 187.25 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 9.6875 | 313.41 | 3036.19 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 9.6875 | 313.42 | 3036.26 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 29.06 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 9.6875 | 201.98 | 1956.64 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 18.73 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 9.6875 | 783.68 | 7591.91 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 72.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 9.6875 | 362.03 | 3507.15 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 33.56 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 9.6875 | 36.20 | 350.71 | LightsWired | BLDG_LIGHT_SCH | 52.33 | 168.00 | 50.98 | 0.0000 | Y | 3.36 |
Interior Lighting Total | 9.6875 | 46320.38 | 448729.56 | 1321.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 56280.71 | AstronomicalClock | - | 83.75 | 83.75 | 884.83 | |
Exterior Lighting Total | 56280.71 | 884.83 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2130725.48 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1256857.81 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1081610.35 | 6.11 | 6.89 | 23.50 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1081610.35 | 6.11 | 6.89 | 23.50 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1027324.96 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1027324.96 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 95135.58 | 141992.09 | 99245.16 | 42746.94 | 0.70 | - | 18417.94 | 186.80 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 178129.16 | 245267.63 | 167651.66 | 77615.97 | 0.68 | - | 31053.71 | 314.96 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 1691315.01 | 2290025.32 | 1560744.26 | 729281.06 | 0.68 | - | 287539.36 | 2916.38 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 171057.06 | 235030.43 | 160611.15 | 74419.28 | 0.68 | - | 29712.48 | 301.36 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 424273.93 | 302390.63 | 121883.30 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9020.08 | 6510.05 | 2510.03 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 85621.27 | 61786.01 | 23835.25 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8719.94 | 6292.85 | 2427.09 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17751.30 | 16841.09 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 324531.17 | 308119.97 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 62034.73 | 58859.51 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 3869.88 | 3675.07 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4033.88 | 3831.00 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6232.95 | 5917.40 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3579.21 | 3395.64 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 120471.79 | 114305.76 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 85861.29 | 81476.10 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 122219.25 | 115963.79 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 78361.94 | 74372.34 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17204.95 | 16324.38 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11415.88 | 10831.60 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17323.99 | 16437.32 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10614.80 | 10071.60 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 267605.72 | 217000.53 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 29735.21 | 24998.95 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 278206.50 | 233634.36 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 28748.35 | 24142.51 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 424273.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9020.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 85621.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 8719.94 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 14546.00 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1023912.82 | 823292.57 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 671.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 6719.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 671.96 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 5.75 | 10627.82 | 1849.05 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.36 | 21380.67 | 2283.73 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 86.77 | 198155.79 | 2283.73 | 1.00 | 1.07 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.97 | 20476.35 | 2283.73 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.59 | 35792.05 | 1657.97 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 527.28 | 1120.11 | 1.00 | 1.63 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.47 | 5004.05 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 509.67 | 1120.11 | 1.00 | 1.65 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.090855 | 21760.53 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.055537 | 14189.11 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.090855 | 7253.51 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.012922 | 3295.69 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.107459 | 27453.15 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78341.20 | 78341.20 | 28.19 | 5.748 | 5.748 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 24.71 | 0.00820 | 1.200 | 0.00 |
CORE_BOTTOM | 81623.59 | 81623.59 | 32.70 | 5.988 | 5.988 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 24.71 | 0.00820 | 1.078 | 0.00 |
CORE_MID | 768931.13 | 768931.13 | 308.05 | 56.395 | 56.395 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 24.71 | 0.00820 | 10.778 | 0.00 |
CORE_TOP | 74796.92 | 74796.92 | 29.97 | 5.537 | 5.537 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00891 | 31.30 | 0.00820 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11520.71 | 11520.71 | 36.76 | 0.853 | 0.853 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00882 | 31.30 | 0.00820 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12855.68 | 12855.68 | 63.65 | 0.945 | 0.945 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00869 | 24.71 | 0.00820 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13876.05 | 13876.05 | 44.27 | 1.027 | 1.027 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 24.00 | 24.00 | 0.00877 | 30.74 | 0.00820 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 15911.56 | 15911.56 | 78.78 | 1.178 | 1.178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00820 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 105200.85 | 105200.85 | 335.66 | 7.719 | 7.719 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 24.71 | 0.00820 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 129107.93 | 129107.93 | 639.23 | 9.558 | 9.558 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00868 | 25.28 | 0.00820 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 128095.32 | 128095.32 | 408.70 | 9.483 | 9.483 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00878 | 30.86 | 0.00820 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 132109.80 | 132109.80 | 654.09 | 9.780 | 9.780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00868 | 30.29 | 0.00820 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11982.42 | 11982.42 | 38.23 | 0.887 | 0.887 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00880 | 31.30 | 0.00820 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12716.53 | 12716.53 | 62.96 | 0.941 | 0.941 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00868 | 25.28 | 0.00820 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14220.95 | 14220.95 | 45.37 | 1.053 | 1.053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00875 | 31.00 | 0.00820 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14215.25 | 14215.25 | 70.38 | 1.052 | 1.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00866 | 30.41 | 0.00820 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8062.70 | 8062.70 | 222.71 | 0.471 | 0.471 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 22.46 | 0.00820 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76517.28 | 76517.28 | 2113.58 | 4.467 | 4.467 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 22.46 | 0.00820 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7793.40 | 7793.40 | 215.27 | 0.455 | 0.455 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 27.00 | 27.00 | 0.00850 | 29.16 | 0.00820 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369748.65 | 369748.65 | 471.81 | 21.588 | 21.588 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 22.68 | 0.00820 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 155118.85 | 155118.85 | 62.14 | 6.604 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 43484.21 | 43484.21 | 17.42 | 1.877 | 1.877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1345.47 | 1345.47 | 4.29 | 0.059 | 0.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 21.00 | 21.00 | 0.00717 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1242.58 | 1242.58 | 6.15 | 0.053 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00618 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3195.63 | 3195.63 | 10.20 | 0.137 | 0.137 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00666 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 104.60 | 104.60 | 0.52 | 0.005 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | 21.00 | 21.00 | 0.00528 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 84386.88 | 84386.88 | 269.25 | 3.656 | 3.656 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00750 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 57177.72 | 57177.72 | 283.09 | 2.478 | 2.478 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 85608.15 | 85608.15 | 273.14 | 3.709 | 3.709 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00752 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 49020.75 | 49020.75 | 242.71 | 2.122 | 2.122 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00739 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12044.24 | 12044.24 | 38.43 | 0.523 | 0.523 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 7991.31 | 7991.31 | 39.57 | 0.347 | 0.347 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12127.44 | 12127.44 | 38.69 | 0.526 | 0.526 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7403.50 | 7403.50 | 36.66 | 0.321 | 0.321 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.75 | 5.75 | 1.20 | 1.20 | 5.7477 | 5.7477 | 5.7477 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.36 | 9.36 | 1.52 | 1.52 | 9.3622 | 2.9973 | 9.3622 | 0.3201 | 0.3000 |
VAV_MID WITH REHEAT | 86.77 | 86.77 | 22.74 | 22.74 | 86.7686 | 28.2524 | 86.7686 | 0.3256 | 0.3000 |
VAV_TOP WITH REHEAT | 8.97 | 8.97 | 3.59 | 3.59 | 8.9662 | 3.5939 | 8.9662 | 0.4008 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.59 | 21.59 | 0.34 | 0.34 | 21.5878 | 21.5878 | 21.5878 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4707 | 0.4707 | 0.4707 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.47 | 4.47 | 0.16 | 0.16 | 4.4675 | 4.4675 | 4.4675 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4550 | 0.4550 | 0.4550 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17751.296 | 17751.296 | 1.796399 | 0.00039219 | 308.966 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16841.09 | 17751.30 | 1.796399 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 17822.70 | 17822.70 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 324531.172 | 324531.172 | 17.144215 | 0.00717012 | 6064.552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 308119.97 | 324531.17 | 17.144215 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 155118.85 | 0.00 | 326088.78 | 326088.78 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 62034.727 | 62034.727 | 1.877278 | 0.00137058 | 1295.757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 58859.51 | 62034.73 | 1.877278 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 43484.21 | 0.00 | 62317.99 | 62317.99 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 3869.881 | 3869.881 | 0.255868 | 0.00008550 | 70.635 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 3675.07 | 3869.88 | 0.255868 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00716538 | 45.5221 | 1345.47 | 0.00 | 3888.99 | 3888.99 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4033.882 | 4033.882 | 0.283452 | 0.00008912 | 73.258 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3831.00 | 4033.88 | 0.283452 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00618334 | 39.3463 | 1242.58 | 0.00 | 4053.89 | 4053.89 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6232.946 | 6232.946 | 0.308179 | 0.00013771 | 117.496 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5917.40 | 6232.95 | 0.308179 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00666225 | 42.3624 | 3195.63 | 0.00 | 6262.71 | 6262.71 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3579.213 | 3579.213 | 0.353384 | 0.00007908 | 62.465 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | 3395.64 | 3579.21 | 0.353384 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00527980 | 33.6432 | 104.60 | 0.00 | 3593.60 | 3593.60 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 120471.794 | 120471.794 | 3.655662 | 0.00266168 | 2514.283 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 114305.76 | 120471.79 | 3.655662 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00750398 | 47.6505 | 84386.88 | 0.00 | 121021.82 | 121021.82 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 85861.294 | 85861.294 | 2.905611 | 0.00189700 | 1738.794 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 81476.10 | 85861.29 | 2.905611 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00754553 | 47.9110 | 57177.72 | 0.00 | 86254.13 | 86254.13 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 122219.254 | 122219.254 | 3.708859 | 0.00270029 | 2550.718 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 115963.79 | 122219.25 | 3.708859 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00751866 | 47.7425 | 85608.15 | 0.00 | 122777.26 | 122777.26 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 78361.939 | 78361.939 | 2.973179 | 0.00173131 | 1545.793 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 74372.34 | 78361.94 | 2.973179 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00738603 | 46.9108 | 49020.75 | 0.00 | 78726.25 | 78726.25 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17204.953 | 17204.953 | 0.522536 | 0.00038012 | 358.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16324.38 | 17204.95 | 0.522536 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00776505 | 49.2863 | 12044.24 | 0.00 | 17283.50 | 17283.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11415.879 | 11415.879 | 0.346740 | 0.00025222 | 238.184 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10831.60 | 11415.88 | 0.346740 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777381 | 49.3411 | 7991.31 | 0.00 | 11468.00 | 11468.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17323.989 | 17323.989 | 0.526160 | 0.00038275 | 361.459 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16437.32 | 17323.99 | 0.526160 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00776813 | 49.3056 | 12127.44 | 0.00 | 17403.08 | 17403.08 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10614.802 | 10614.802 | 0.325181 | 0.00023452 | 220.903 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10071.60 | 10614.80 | 0.325181 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00772550 | 49.0387 | 7403.50 | 0.00 | 10663.25 | 10663.25 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 95135.584 | -999.000 | 5.747715 | 0.00404729 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 95135.58 | 89112.01 | 5.747715 | 24.27 | 16.52 | 0.00878974 | 11.27 | 11.27 | 0.00843576 | 25.28 | 0.00820219 | 16.37 | 20.8793 | 24.00 | 0.00894578 | 47.2310 | 77281.52 | 0.00 | 108506.46 | 92938.05 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 267605.723 | 267605.723 | 5.747715 | 0.00591242 | 5008.984 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 217000.53 | 250736.37 | 5.747715 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.8793 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 228999.46 | 228999.46 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 178129.162 | -999.000 | 9.362179 | 0.00757803 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 178129.16 | 171810.71 | 9.362179 | 26.29 | 17.11 | 0.00865779 | 11.27 | 11.93 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 28.9064 | 24.00 | 0.00882055 | 46.5786 | 116656.77 | 0.00 | 200069.41 | 175873.46 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 29735.208 | 29735.208 | 2.808654 | 0.00065696 | 452.409 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24998.95 | 29735.21 | 2.808654 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 96.3547 | 21.00 | 0.00754610 | 47.9113 | 5676.53 | 0.00 | 26442.55 | 26442.55 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1691315.015 | -999.000 | 86.768565 | 0.07195245 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1691315.01 | 1635404.01 | 86.768565 | 26.70 | 17.24 | 0.00864773 | 11.27 | 11.93 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 32.5925 | 24.00 | 0.00884229 | 46.6918 | 1033322.38 | 0.00 | 1894826.80 | 1672297.41 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 278206.501 | 278206.501 | 26.030570 | 0.00614663 | 4231.530 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 233634.36 | 278206.50 | 26.030570 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 108.6415 | 21.00 | 0.00773496 | 49.0972 | 431312.34 | 0.00 | 247130.91 | 247130.91 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 171057.056 | -999.000 | 8.966193 | 0.00727716 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 171057.06 | 165550.04 | 8.966193 | 26.38 | 17.12 | 0.00863782 | 11.27 | 11.93 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 32.5948 | 24.00 | 0.00883051 | 46.6304 | 121077.76 | 0.00 | 192070.90 | 169400.87 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 28748.352 | 28748.352 | 2.689858 | 0.00063516 | 437.263 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24142.51 | 28748.35 | 2.689858 | 3.90 | 3.88 | 0.00507572 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 108.6492 | 21.00 | 0.00788554 | 50.0401 | 67322.48 | 0.00 | 25537.17 | 25537.17 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 424273.928 | 302390.629 | 21.587834 | 0.01039044 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 457260.02 | 457260.01 | -999.0 | 28.49 | 17.71 | 0.00849532 | 12.80 | 11.92 | 0.00849532 | 31.30 | 0.00820219 | 18.40 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 369164.60 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9020.085 | 6510.051 | 0.470742 | 0.00022090 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9763.33 | 9763.33 | -999.0 | 28.04 | 17.56 | 0.00849009 | 12.80 | 11.92 | 0.00849009 | 29.16 | 0.00820219 | 17.70 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 8042.67 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 85621.265 | 61786.013 | 4.467473 | 0.00209686 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 92674.18 | 92674.17 | -999.0 | 28.04 | 17.56 | 0.00848957 | 12.80 | 11.92 | 0.00848957 | 29.16 | 0.00820219 | 17.70 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 76437.43 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8719.940 | 6292.848 | 0.455019 | 0.00021355 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 9438.32 | 9438.32 | -999.0 | 28.04 | 17.56 | 0.00848977 | 12.80 | 11.92 | 0.00848977 | 29.16 | 0.00820219 | 17.70 | -999.0000 | 27.00 | 0.00850000 | 37.5769 | 7793.40 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 424273.928 | 424273.928 | 21.587834 | 0.01039044 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 424273.93 | 424273.93 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5674 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9020.085 | 9020.085 | 0.470742 | 0.00022090 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9020.08 | 9020.08 | 0.470742 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3206 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 85621.265 | 85621.265 | 4.467473 | 0.00209686 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 85621.27 | 85621.27 | 4.467473 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4989 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8719.940 | 8719.940 | 0.455019 | 0.00021355 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8719.94 | 8719.94 | 0.455019 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4353 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14546.000 | 14546.000 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.00 | 14546.00 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5674 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 941740.26 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5674 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1023912.819 | 1023912.819 | 21.587834 | 0.02262210 | 19067.473 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 823292.57 | 941740.26 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5674 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 0.470742 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3206 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6719.649 | 6719.649 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6719.65 | 6719.65 | 4.467473 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4989 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 0.455019 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4353 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17751.296 | 17751.296 | 1.796399 | 0.00039219 | 308.966 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.6568 | 0.706178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16841.09 | 17751.30 | 1.0000 | 2.12294558 | 1.796399 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.39215319 | 60.00 | 49.00 | 11.00 | 0.000 | 16841.09 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 17822.70 | 17822.70 | 2.12294558 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 324531.172 | 324531.172 | 17.144215 | 0.00717012 | 6064.552 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 12.0157 | 12.910417 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 308119.97 | 324531.17 | 1.0000 | 20.26066765 | 17.144215 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 7.16938826 | 60.00 | 49.00 | 11.00 | 0.000 | 308119.97 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 155118.85 | 0.00 | 326088.78 | 326088.78 | 20.26066765 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.58 | 17.54 | 0.00800000 | 49154.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 62034.727 | 62034.727 | 1.877278 | 0.00137058 | 1295.757 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 2.2953 | 2.467850 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 58859.51 | 62034.73 | 1.0000 | 2.21852694 | 1.877278 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 1.37044167 | 60.00 | 49.00 | 11.00 | 0.000 | 58859.51 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 43484.21 | 0.00 | 62317.99 | 62317.99 | 2.21852694 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.35 | 21.25 | 0.00800000 | 61149.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3869.881 | 3869.881 | 0.255868 | 0.00008550 | 70.635 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.1433 | 0.153951 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 3675.07 | 3869.88 | 1.0000 | 0.30237989 | 0.255868 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08549156 | 60.00 | 49.00 | 11.00 | 0.000 | 3675.07 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00716538 | 21.00 | 0.00716538 | 45.5221 | 1345.47 | 0.00 | 3888.99 | 3888.99 | 0.30237989 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 25.41 | 16.44 | 0.00800000 | 45921.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4033.882 | 4033.882 | 0.283452 | 0.00008912 | 73.258 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.1494 | 0.160475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3831.00 | 4033.88 | 1.0000 | 0.33497802 | 0.283452 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08911460 | 60.00 | 49.00 | 11.00 | 0.000 | 3831.00 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.89 | 0.00618334 | 21.00 | 0.00618334 | 39.3463 | 1242.58 | 0.00 | 4053.89 | 4053.89 | 0.33497802 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 24.67 | 16.18 | 0.00800000 | 45161.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6232.946 | 6232.946 | 0.308179 | 0.00013771 | 117.496 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.2308 | 0.247957 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5917.40 | 6232.95 | 1.0000 | 0.36419903 | 0.308179 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.13769528 | 60.00 | 49.00 | 11.00 | 0.000 | 5917.40 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.81 | 0.00666225 | 21.00 | 0.00666225 | 42.3624 | 3195.63 | 0.00 | 6262.71 | 6262.71 | 0.36419903 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.66 | 17.90 | 0.00800000 | 50255.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3579.213 | 3579.213 | 0.353384 | 0.00007908 | 62.465 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.1324 | 0.142387 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | 3395.64 | 3579.21 | 1.0000 | 0.41762124 | 0.353384 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.07907027 | 60.00 | 49.00 | 11.00 | 0.000 | 3395.64 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00527980 | 21.00 | 0.00527980 | 33.6432 | 104.60 | 0.00 | 3593.60 | 3593.60 | 0.41762124 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.24 | 14.93 | 0.00800000 | 41664.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120471.794 | 120471.794 | 3.655662 | 0.00266168 | 2514.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 4.4576 | 4.792578 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 114305.76 | 120471.79 | 1.0000 | 4.32018394 | 3.655662 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 2.66140556 | 60.00 | 49.00 | 11.00 | 0.000 | 114305.76 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00750398 | 21.00 | 0.00750398 | 47.6505 | 84386.88 | 0.00 | 121021.82 | 121021.82 | 4.32018394 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61072.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 85861.294 | 85861.294 | 2.905611 | 0.00189700 | 1738.794 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 3.1773 | 3.415712 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 81476.10 | 85861.29 | 1.0000 | 3.43378874 | 2.905611 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 1.89680685 | 60.00 | 49.00 | 11.00 | 0.000 | 81476.10 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00754553 | 21.00 | 0.00754553 | 47.9110 | 57177.72 | 0.00 | 86254.13 | 86254.13 | 3.43378874 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 37.43 | 20.38 | 0.00800000 | 58179.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122219.254 | 122219.254 | 3.708859 | 0.00270029 | 2550.718 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 4.5222 | 4.862095 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 115963.79 | 122219.25 | 1.0000 | 4.38305101 | 3.708859 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 2.70000962 | 60.00 | 49.00 | 11.00 | 0.000 | 115963.79 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00751866 | 21.00 | 0.00751866 | 47.7425 | 85608.15 | 0.00 | 122777.26 | 122777.26 | 4.38305101 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61071.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 78361.939 | 78361.939 | 2.973179 | 0.00173131 | 1545.793 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 2.9003 | 3.117375 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 74372.34 | 78361.94 | 1.0000 | 3.51363995 | 2.973179 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 1.73113468 | 60.00 | 49.00 | 11.00 | 0.000 | 74372.34 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00738603 | 21.00 | 0.00738603 | 46.9108 | 49020.75 | 0.00 | 78726.25 | 78726.25 | 3.51363995 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 34.77 | 19.56 | 0.00800000 | 55465.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17204.953 | 17204.953 | 0.522536 | 0.00038012 | 358.977 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.6366 | 0.684443 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16324.38 | 17204.95 | 1.0000 | 0.61752140 | 0.522536 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.38008364 | 60.00 | 49.00 | 11.00 | 0.000 | 16324.38 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00776505 | 21.00 | 0.00776505 | 49.2863 | 12044.24 | 0.00 | 17283.50 | 17283.50 | 0.61752140 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61048.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11415.879 | 11415.879 | 0.346740 | 0.00025222 | 238.184 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.4224 | 0.454144 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10831.60 | 11415.88 | 1.0000 | 0.40977014 | 0.346740 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.25219416 | 60.00 | 49.00 | 11.00 | 0.000 | 10831.60 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00777381 | 21.00 | 0.00777381 | 49.3411 | 7991.31 | 0.00 | 11468.00 | 11468.00 | 0.40977014 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61046.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17323.989 | 17323.989 | 0.526160 | 0.00038275 | 361.459 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.6410 | 0.689179 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16437.32 | 17323.99 | 1.0000 | 0.62180504 | 0.526160 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.38271332 | 60.00 | 49.00 | 11.00 | 0.000 | 16437.32 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00776813 | 21.00 | 0.00776813 | 49.3056 | 12127.44 | 0.00 | 17403.08 | 17403.08 | 0.62180504 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61047.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10614.802 | 10614.802 | 0.325181 | 0.00023452 | 220.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.3928 | 0.422275 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10071.60 | 10614.80 | 1.0000 | 0.38429148 | 0.325181 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.23449716 | 60.00 | 49.00 | 11.00 | 0.000 | 10071.60 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00772550 | 21.00 | 0.00772550 | 49.0387 | 7403.50 | 0.00 | 10663.25 | 10663.25 | 0.38429148 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.01 | 21.15 | 0.00800000 | 60807.6 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 95135.584 | -999.000 | 5.747715 | 0.00404729 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1797 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 5.747715 | 6.79252749 | 4197.9300 | 999.8980 | 90.84565900 | 12.27 | 6.67 | 5.60 | 2135636.82 | 4.4547 | 4.454671 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 95135.58 | 89112.01 | 1.0000 | 6.79252749 | 5.747715 | 24.27 | 16.52 | 0.00878974 | 46763.5 | 11.27 | 11.27 | 0.00843576 | 32758.4 | 4.04687478 | 6.67 | 10.65 | 5.60 | 10627.819 | 84507.76 | 25.28 | 0.00820219 | 16.37 | 1.20008137 | 20.8793 | 24.00 | 0.00894569 | 24.00 | 0.00894578 | 47.2310 | 77281.52 | 0.00 | 108506.46 | 92938.05 | 6.79252749 | 24.27 | 16.72 | 0.00878974 | 46763.5 | 10.87 | 10.65 | 0.00788063 | 30789.1 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 267605.723 | 267605.723 | 5.747715 | 0.00591242 | 5008.984 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 5.747715 | 6.79252749 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 8.4624 | 10.645823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 217000.53 | 250736.37 | 1.0000 | 6.79252749 | 5.747715 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 5.91181833 | 60.00 | 49.00 | 11.00 | 0.000 | 217000.53 | 3.80 | 0.00505843 | 3.80 | 1.20008137 | 20.8793 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 228999.46 | 228999.46 | 6.79252749 | 12.80 | 3.41 | 0.00105616 | 15528.5 | 46.29 | 17.71 | 0.00105616 | 49241.9 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 178129.162 | -999.000 | 9.362179 | 0.00757803 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9344 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.362179 | 11.06402334 | 4197.9300 | 999.8980 | 90.84565900 | 12.27 | 6.67 | 5.60 | 2135636.82 | 8.3408 | 8.340798 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 178129.16 | 171810.71 | 1.0000 | 11.06402334 | 9.362179 | 26.29 | 17.11 | 0.00865779 | 48489.6 | 11.27 | 11.93 | 0.00843576 | 34322.2 | 7.57725331 | 6.67 | 10.65 | 5.60 | 21380.668 | 156748.49 | 31.30 | 0.00820219 | 18.40 | 2.70627000 | 28.9064 | 24.00 | 0.00886571 | 24.00 | 0.00882055 | 46.5786 | 116656.77 | 0.00 | 200069.41 | 175873.46 | 11.06402334 | 26.29 | 17.30 | 0.00865779 | 48489.6 | 10.72 | 10.48 | 0.00779027 | 30406.7 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 29735.208 | 29735.208 | 2.808654 | 0.00065696 | 452.409 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.362179 | 11.06402334 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.9749 | 1.182919 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24998.95 | 29735.21 | 1.0000 | 3.31920700 | 2.808654 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.65689606 | 60.00 | 49.00 | 11.00 | 0.000 | 24998.95 | 3.80 | 0.00505843 | 3.80 | 2.70627000 | 96.3547 | 6.13 | 0.00148528 | 21.00 | 0.00754610 | 47.9113 | 5676.53 | 0.00 | 26442.55 | 26442.55 | 3.31920700 | 12.80 | 8.26 | 0.00492818 | 25304.3 | 20.66 | 11.73 | 0.00492818 | 33270.8 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1691315.015 | -999.000 | 86.768565 | 0.07195245 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9157 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.768565 | 102.54123901 | 4197.9300 | 999.8980 | 90.84565900 | 12.27 | 6.67 | 5.60 | 2135636.82 | 79.1949 | 79.194880 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1691315.01 | 1635404.01 | 1.0000 | 102.54123901 | 86.768565 | 26.70 | 17.24 | 0.00864773 | 48883.7 | 11.27 | 11.93 | 0.00843576 | 34322.2 | 71.94511065 | 6.67 | 10.65 | 5.60 | 198155.785 | 1493159.23 | 31.30 | 0.00820219 | 18.40 | 28.28001000 | 32.5925 | 24.00 | 0.00890904 | 24.00 | 0.00884229 | 46.6918 | 1033322.38 | 0.00 | 1894826.80 | 1672297.41 | 102.54123901 | 26.70 | 17.43 | 0.00864773 | 48883.7 | 10.72 | 10.48 | 0.00778686 | 30405.1 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 278206.501 | 278206.501 | 26.030570 | 0.00614663 | 4231.530 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.768565 | 102.54123901 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 9.1110 | 11.067541 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 233634.36 | 278206.50 | 1.0000 | 30.76237170 | 26.030570 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 6.14600567 | 60.00 | 49.00 | 11.00 | 0.000 | 233634.36 | 3.80 | 0.00505843 | 3.80 | 28.28001000 | 108.6415 | 20.76 | 0.00773496 | 21.00 | 0.00773496 | 49.0972 | 431312.34 | 0.00 | 247130.91 | 247130.91 | 30.76237170 | 12.80 | 8.41 | 0.00505843 | 25633.1 | 20.72 | 11.89 | 0.00505843 | 33666.7 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 171057.056 | -999.000 | 8.966193 | 0.00727716 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8973 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.966193 | 10.59605607 | 4197.9300 | 999.8980 | 90.84565900 | 12.27 | 6.67 | 5.60 | 2135636.82 | 8.0097 | 8.009651 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 171057.06 | 165550.04 | 1.0000 | 10.59605607 | 8.966193 | 26.38 | 17.12 | 0.00863782 | 48533.2 | 11.27 | 11.93 | 0.00843576 | 34322.2 | 7.27642025 | 6.67 | 10.65 | 5.60 | 20476.345 | 150580.71 | 31.30 | 0.00820219 | 18.40 | 2.92251000 | 32.5948 | 24.00 | 0.00884856 | 24.00 | 0.00883051 | 46.6304 | 121077.76 | 0.00 | 192070.90 | 169400.87 | 10.59605607 | 26.38 | 17.32 | 0.00863782 | 48533.2 | 10.72 | 10.48 | 0.00778911 | 30406.6 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28748.352 | 28748.352 | 2.689858 | 0.00063516 | 437.263 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.966193 | 10.59605607 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 0.9415 | 1.143660 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24142.51 | 28748.35 | 1.0000 | 3.17881682 | 2.689858 | 3.90 | 3.88 | 0.00507572 | 16653.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.63509493 | 60.00 | 49.00 | 11.00 | 0.000 | 24142.51 | 3.80 | 0.00505843 | 3.80 | 2.92251000 | 108.6492 | 21.00 | 0.00792109 | 21.00 | 0.00788554 | 50.0401 | 67322.48 | 0.00 | 25537.17 | 25537.17 | 3.17881682 | 12.80 | 8.41 | 0.00505843 | 25633.1 | 20.72 | 11.89 | 0.00505843 | 33666.7 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 424273.928 | 302390.629 | 21.587834 | 0.01039044 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6324 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 457260.02 | 457260.01 | 0.9279 | -999.0 | -999.0 | 28.49 | 17.71 | 0.00849532 | 50328.6 | 12.80 | 11.92 | 0.00849532 | 34310.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 457260.02 | 31.30 | 0.00820219 | 18.40 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 369164.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9020.085 | 6510.051 | 0.470742 | 0.00022090 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6226 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9763.33 | 9763.33 | 0.9239 | -999.0 | -999.0 | 28.04 | 17.56 | 0.00849009 | 49847.4 | 12.80 | 11.92 | 0.00849009 | 34297.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9763.33 | 29.16 | 0.00820219 | 17.70 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 8042.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 85621.265 | 61786.013 | 4.467473 | 0.00209686 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6217 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 92674.18 | 92674.17 | 0.9239 | -999.0 | -999.0 | 28.04 | 17.56 | 0.00848957 | 49850.0 | 12.80 | 11.92 | 0.00848957 | 34295.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92674.18 | 29.16 | 0.00820219 | 17.70 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 76437.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8719.940 | 6292.848 | 0.455019 | 0.00021355 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6221 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 9438.32 | 9438.32 | 0.9239 | -999.0 | -999.0 | 28.04 | 17.56 | 0.00848977 | 49849.0 | 12.80 | 11.92 | 0.00848977 | 34296.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9438.32 | 29.16 | 0.00820219 | 17.70 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 7793.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 424273.928 | 424273.928 | 21.587834 | 0.01039044 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 424273.93 | 424273.93 | 1.0000 | 25.51204113 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 424273.93 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5674 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9020.085 | 9020.085 | 0.470742 | 0.00022090 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9020.08 | 9020.08 | 1.0000 | 0.55631285 | 0.470742 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9020.08 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.3206 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 85621.265 | 85621.265 | 4.467473 | 0.00209686 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 85621.27 | 85621.27 | 1.0000 | 5.27956479 | 4.467473 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85621.27 | 3.80 | 0.00505843 | 3.80 | 0.15631366 | 3.4989 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8719.940 | 8719.940 | 0.455019 | 0.00021355 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8719.94 | 8719.94 | 1.0000 | 0.53773164 | 0.455019 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8719.94 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.4353 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14546.000 | 14546.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.587834 | 25.51204113 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.00 | 14546.00 | 1.0000 | 25.51204113 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14546.00 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5674 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.587834 | 25.51204113 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 941740.26 | 1.0000 | 25.51204113 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5674 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1023912.819 | 1023912.819 | 21.587834 | 0.02262210 | 19067.473 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.587834 | 25.51204113 | 4197.9300 | 999.8980 | 55.53180970 | 71.00 | 82.00 | 11.00 | 2564305.15 | 32.1059 | 40.733041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 823292.57 | 941740.26 | 1.0000 | 25.51204113 | 21.587834 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 22.61979488 | 60.00 | 49.00 | 11.00 | 0.000 | 823292.57 | 3.80 | 0.00505843 | 3.80 | 0.33837161 | 1.5674 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51204113 | 16.60 | 4.14 | 0.00007929 | 16881.1 | 16.60 | 4.14 | 0.00007929 | 16881.1 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.470742 | 0.55631285 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 1.0000 | 0.55631285 | 0.470742 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 671.96 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.3206 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6719.649 | 6719.649 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.467473 | 5.27956479 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6719.65 | 6719.65 | 1.0000 | 5.27956479 | 4.467473 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6719.65 | 3.80 | 0.00505843 | 3.80 | 0.15631366 | 3.4989 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 671.965 | 671.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.455019 | 0.53773164 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 671.96 | 671.96 | 1.0000 | 0.53773164 | 0.455019 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 671.96 | 3.80 | 0.00505843 | 3.80 | 0.01563137 | 3.4353 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.1656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.75 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.71 | 9.36 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 28.28 | 86.77 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.92 | 8.97 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4436.00 | 398.33 | 299.17 |
CORE_BOTTOM | 4508.00 | 89.33 | 4.17 |
CORE_MID | 3512.33 | 698.00 | 15.17 |
CORE_TOP | 2408.83 | 2160.50 | 14.00 |
PERIMETER_BOT_ZN_3 | 2847.83 | 1405.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 2341.83 | 2395.83 | 14.83 |
PERIMETER_BOT_ZN_1 | 3343.83 | 1218.00 | 41.83 |
PERIMETER_BOT_ZN_4 | 4420.33 | 656.17 | 146.67 |
PERIMETER_MID_ZN_3 | 1660.67 | 3105.83 | 7.83 |
PERIMETER_MID_ZN_2 | 1258.00 | 3137.50 | 27.50 |
PERIMETER_MID_ZN_1 | 2669.17 | 2139.67 | 47.33 |
PERIMETER_MID_ZN_4 | 1971.00 | 3126.50 | 48.50 |
PERIMETER_TOP_ZN_3 | 1575.67 | 3981.83 | 310.83 |
PERIMETER_TOP_ZN_2 | 1663.83 | 3862.00 | 181.50 |
PERIMETER_TOP_ZN_1 | 2157.33 | 2984.00 | 139.17 |
PERIMETER_TOP_ZN_4 | 1732.33 | 3773.50 | 211.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5303.00 | 4776.50 | 809.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 154.83 | 0.00 | 10.83 |
CORE_BOTTOM | 0.00 | 3.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 1.33 | 0.00 | 1.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 47.17 | 0.00 | 47.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 51.50 | 0.00 | 26.33 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 1.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_1 | 0.00 | 102.17 | 0.00 | 102.17 |
PERIMETER_MID_ZN_4 | 0.00 | 5.17 | 0.00 | 4.50 |
PERIMETER_TOP_ZN_3 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.83 | 14.17 | 0.00 | 14.17 |
PERIMETER_TOP_ZN_4 | 0.83 | 6.17 | 0.00 | 5.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 14.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.83 | 341.67 | 0.00 | 164.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 2.017 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 1.260 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 1.012 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.934 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 1.191 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 1.695 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 1.614 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 2.445 | 0.057 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.928 | 0.125 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 1.549 | 0.134 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 1.427 | 0.125 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 1.757 | 0.130 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 1.011 | 0.155 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 1.628 | 0.161 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 1.437 | 0.155 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 1.870 | 0.161 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
Electricity:Building | 19507.65 | 254949.54 | 01-JAN-06:10 | 1167329.12 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 682.08 | 14702.05 | 01-JAN-06:10 | 35858.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 257.68 | 1244.51 | 01-JAN-06:10 | 22401.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 4294.36 | 20740.28 | 01-JAN-06:10 | 373325.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 552.69 | 7160.52 | 01-JAN-06:10 | 38246.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5526.92 | 71604.96 | 01-JAN-06:10 | 382463.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2314.15 | 11176.56 | 01-JAN-06:10 | 201178.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 552.69 | 7160.50 | 01-JAN-06:10 | 38246.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 231.42 | 1117.66 | 01-JAN-06:10 | 20117.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 693.98 | 8991.05 | 01-JAN-06:10 | 48023.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 290.56 | 1403.33 | 01-JAN-06:10 | 25259.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 447.23 | 5794.18 | 01-JAN-06:10 | 30947.91 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 693.99 | 8991.20 | 01-JAN-06:10 | 48023.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 290.57 | 1403.36 | 01-JAN-06:10 | 25260.46 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 447.22 | 5794.15 | 01-JAN-06:10 | 30947.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 187.25 | 904.36 | 01-JAN-06:10 | 16278.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 69.40 | 899.11 | 01-JAN-06:10 | 4802.31 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.06 | 140.33 | 01-JAN-06:10 | 2525.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 44.72 | 579.42 | 01-JAN-06:10 | 3094.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 69.40 | 899.12 | 01-JAN-06:10 | 4802.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.06 | 140.34 | 01-JAN-06:10 | 2526.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 44.72 | 579.41 | 01-JAN-06:10 | 3094.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.73 | 90.44 | 01-JAN-06:10 | 1627.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7567.51 | 95259.03 | 01-JAN-06:10 | 385948.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 72.65 | 350.90 | 01-JAN-06:10 | 6316.16 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1572.37 | 19648.16 | 01-JAN-06:10 | 80862.03 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 33.56 | 162.10 | 01-JAN-06:10 | 2917.81 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.24 | 1964.82 | 01-JAN-06:10 | 8086.20 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.36 | 16.21 | 01-JAN-06:10 | 291.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4679.12 | 70601.63 | 11-JAN-00:10 | 285351.99 | 18-AUG-15:00 |
ExteriorEquipment:Electricity | 2044.08 | 15778.61 | 01-JAN-00:10 | 129663.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.73 | 1613.62 | 01-JAN-00:10 | 5498.40 | 11-APR-07:20 |
ElectricityPurchased:Facility | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
ElectricityPurchased:Plant | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
Cogeneration:ElectricityPurchased | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
ElectricityNet:Plant | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
Cogeneration:ElectricityNet | 30168.02 | 384445.18 | 29-JAN-10:10 | 1973943.13 | 18-AUG-15:50 |
Fans:Electricity | 2208.11 | 41833.05 | 02-JAN-22:50 | 144957.87 | 16-OCT-14:50 |
General:Fans:Electricity | 2208.11 | 41833.05 | 02-JAN-22:50 | 144957.87 | 16-OCT-14:50 |
ExteriorLights:Electricity | 884.83 | 0.00 | 01-JAN-07:00 | 56280.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 884.83 | 0.00 | 01-JAN-07:00 | 56280.71 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.27 | 1942.80 | 01-JAN-00:10 | 1942.80 | 01-JAN-00:10 |
Cooling:Electricity | 3509.97 | 26823.69 | 11-JAN-00:10 | 450325.57 | 18-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 6.70 | 0.00 | 01-JAN-00:10 | 32206.61 | 28-FEB-22:20 |
Electricity:Plant | 3140.08 | 6047.47 | 03-JAN-01:40 | 448986.63 | 31-JUL-15:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 1133.41 | 0.00 | 01-JAN-00:10 | 311201.99 | 31-JUL-15:50 |
HeatRejection:Electricity | 1398.76 | 2751.78 | 03-JAN-01:40 | 82332.21 | 13-JAN-14:10 |
General:HeatRejection:Electricity | 138.51 | 0.00 | 01-JAN-00:10 | 33083.94 | 13-JAN-14:10 |
Pumps:Electricity | 607.90 | 3295.69 | 01-JAN-01:00 | 56873.89 | 29-SEP-12:30 |
General:Pumps:Electricity | 607.90 | 3295.69 | 01-JAN-01:00 | 56873.89 | 29-SEP-12:30 |
WIRED_LTG_ELECTRICITY | 120.67 | 0.00 | 01-JAN-00:10 | 10490.43 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 919.74 | 8146.58 | 03-JAN-01:10 | 617524.83 | 22-DEC-07:10 |
Gas:Plant | 919.74 | 8146.58 | 03-JAN-01:10 | 617524.83 | 22-DEC-07:10 |
WaterSystems:Gas | 550.62 | 8146.58 | 03-JAN-01:10 | 72191.44 | 02-FEB-12:20 |
Water Heater:WaterSystems:Gas | 550.62 | 8146.58 | 03-JAN-01:10 | 72191.44 | 02-FEB-12:20 |
Heating:Gas | 369.12 | 0.00 | 01-JAN-00:10 | 609378.25 | 22-DEC-07:10 |
Boiler:Heating:Gas | 369.12 | 0.00 | 01-JAN-00:10 | 609378.25 | 22-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 19115.49 | 116662.19 | 03-JAN-01:40 | 2588246.70 | 18-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 19115.49 | 116662.19 | 03-JAN-01:40 | 2588246.70 | 18-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 19115.49 | 116662.19 | 03-JAN-01:40 | 2588246.70 | 18-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7061.56 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
Water:Plant | 7059.06 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 7061.56 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
MainsWater:Plant | 7059.06 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 2.49 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-22:20 |
Humidifier:Water | 2.49 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-22:20 |
MainsWater:HVAC | 2.49 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-22:20 |
Humidifier:MainsWater | 2.49 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-22:20 |
HeatRejection:Water | 4778.89 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 4778.89 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 646.78 | 0.00 | 01-JAN-00:10 | 471921.92 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 379.87 | 0.00 | 01-JAN-00:10 | 43842.98 | 02-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 379.87 | 0.00 | 01-JAN-00:10 | 43842.98 | 02-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 60430.63 | 181170.05 | 03-JAN-01:40 | 10101575.32 | 18-AUG-15:50 |
EnergyTransfer:Building | 20034.22 | 67191.44 | 10-JAN-02:50 | 1464519.02 | 18-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 758.90 | 0.00 | 01-JAN-00:10 | 80574.66 | 03-DEC-18:30 |
Heating:EnergyTransfer | 24.78 | 0.00 | 02-JAN-12:10 | 120429.78 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 8.15 | 0.00 | 01-JAN-00:10 | 60999.23 | 30-JUL-19:50 |
Cooling:EnergyTransfer | 20009.44 | 67162.83 | 10-JAN-02:50 | 1464519.02 | 18-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 750.75 | 0.00 | 01-JAN-00:10 | 79358.91 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 709.24 | 0.00 | 01-JAN-00:10 | 55627.67 | 26-DEC-10:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 709.24 | 0.00 | 01-JAN-00:10 | 55627.67 | 26-DEC-10:20 |
EnergyTransfer:Zone:CORE_MID | 5292.29 | 0.00 | 01-JAN-00:10 | 452347.97 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5292.29 | 0.00 | 01-JAN-00:10 | 452347.97 | 02-OCT-13:10 |
EnergyTransfer:Zone:CORE_TOP | 466.07 | 0.00 | 01-JAN-00:10 | 51623.88 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.08 | 0.00 | 01-JAN-00:10 | 23425.54 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 465.98 | 0.00 | 01-JAN-00:10 | 51623.88 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 83.68 | 0.00 | 01-JAN-00:10 | 9076.65 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 83.68 | 0.00 | 01-JAN-00:10 | 9076.65 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.31 | 0.00 | 01-JAN-00:10 | 9303.19 | 16-OCT-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.31 | 0.00 | 01-JAN-00:10 | 9303.19 | 16-OCT-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 112.83 | 0.00 | 01-JAN-00:10 | 15022.92 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 112.83 | 0.00 | 01-JAN-00:10 | 15022.92 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 112.02 | 0.00 | 01-JAN-00:10 | 13417.68 | 26-APR-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 112.02 | 0.00 | 01-JAN-00:10 | 13417.68 | 26-APR-15:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 583.17 | 0.00 | 01-JAN-00:10 | 79790.34 | 29-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 32260.79 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 583.06 | 0.00 | 01-JAN-00:10 | 79790.34 | 29-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 625.70 | 0.00 | 01-JAN-00:10 | 90508.19 | 14-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 21333.96 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 625.60 | 0.00 | 01-JAN-00:10 | 90508.19 | 14-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 925.71 | 0.00 | 01-JAN-00:10 | 143960.26 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 18061.46 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 925.68 | 0.00 | 01-JAN-00:10 | 143960.26 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 688.19 | 0.00 | 01-JAN-00:10 | 107454.01 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 9206.86 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 688.17 | 0.00 | 01-JAN-00:10 | 107454.01 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 58.07 | 0.00 | 01-JAN-00:10 | 8799.72 | 29-SEP-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.19 | 0.00 | 01-JAN-00:10 | 8121.29 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.88 | 0.00 | 01-JAN-00:10 | 8799.72 | 29-SEP-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.59 | 0.00 | 01-JAN-00:10 | 9000.57 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.57 | 0.00 | 01-JAN-00:10 | 5444.53 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.03 | 0.00 | 01-JAN-00:10 | 9000.57 | 19-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 87.15 | 0.00 | 01-JAN-00:10 | 15598.61 | 16-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.50 | 0.00 | 01-JAN-00:10 | 7995.53 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.65 | 0.00 | 01-JAN-00:10 | 15598.61 | 16-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.75 | 0.00 | 01-JAN-00:10 | 11275.13 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.31 | 0.00 | 01-JAN-00:10 | 5089.43 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.44 | 0.00 | 01-JAN-00:10 | 11275.13 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.94 | 0.00 | 01-JAN-00:10 | 7509.74 | 16-OCT-15:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.84 | 0.00 | 01-JAN-00:10 | 3275.44 | 04-DEC-04:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.09 | 0.00 | 01-JAN-00:10 | 7509.74 | 16-OCT-15:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 498.96 | 0.00 | 01-JAN-00:10 | 55508.23 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.49 | 0.00 | 01-JAN-00:10 | 22660.50 | 27-MAR-05:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 494.47 | 0.00 | 01-JAN-00:10 | 55508.23 | 16-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 76.17 | 0.00 | 01-JAN-00:10 | 17419.54 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.18 | 0.00 | 01-JAN-00:10 | 10039.40 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 67.99 | 0.00 | 01-JAN-00:10 | 17419.54 | 16-OCT-13:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.23 | 1169.41 | 09-JAN-07:40 | 7790.45 | 06-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.23 | 1169.41 | 09-JAN-07:40 | 7790.45 | 06-AUG-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1267.92 | 5541.80 | 08-JAN-07:40 | 72790.86 | 31-AUG-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1267.92 | 5541.80 | 08-JAN-07:40 | 72790.86 | 31-AUG-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.66 | 0.17 | 08-JAN-21:50 | 7405.75 | 20-AUG-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-10:00 | 530.00 | 08-JAN-07:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.54 | 0.00 | 01-JAN-00:10 | 7405.75 | 20-AUG-17:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.67 | 57581.14 | 10-JAN-02:50 | 370762.61 | 16-DEC-03:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 8079.11 | 03-JAN-01:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.60 | 57581.14 | 10-JAN-02:50 | 370762.61 | 16-DEC-03:20 |
EnergyTransfer:Plant | 23265.22 | 0.00 | 01-JAN-00:10 | 6272064.06 | 31-JUL-15:50 |
WaterSystems:EnergyTransfer | 379.87 | 0.00 | 01-JAN-00:10 | 43842.98 | 02-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 379.87 | 0.00 | 01-JAN-00:10 | 43842.98 | 02-FEB-12:30 |
EnergyTransfer:HVAC | 17131.19 | 95990.07 | 03-JAN-01:40 | 2442415.97 | 18-AUG-15:50 |
HeatingCoils:EnergyTransfer | 266.92 | 0.00 | 01-JAN-00:10 | 457066.62 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 266.92 | 0.00 | 01-JAN-00:10 | 457066.62 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 266.92 | 0.00 | 01-JAN-00:10 | 457066.62 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 16864.27 | 95990.07 | 03-JAN-01:40 | 2442415.97 | 18-AUG-15:50 |
LoopToLoop:EnergyTransfer | 7700.22 | 0.00 | 01-JAN-00:10 | 1974650.67 | 31-JUL-15:50 |
Boilers:EnergyTransfer | 263.43 | 0.00 | 01-JAN-00:10 | 484729.39 | 22-DEC-07:10 |
Chillers:EnergyTransfer | 6894.15 | 0.00 | 01-JAN-00:10 | 1977881.72 | 31-JUL-15:50 |
HeatRejection:EnergyTransfer | 8027.55 | 0.00 | 01-JAN-00:10 | 2289083.71 | 31-JUL-15:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 8.151 | -750.758 | 0.000 | 0.000 | 92.669 | 257.680 | 424.397 | 0.000 | 0.000 | 0.000 | 0.008 | 0.000 | 0.000 | 0.000 | 0.000 | -32.140 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -709.244 | 0.000 | 0.000 | 83.392 | 231.415 | 321.278 | 0.000 | 0.000 | 0.000 | 73.158 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5292.308 | 0.000 | 0.000 | 835.740 | 2314.151 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1070.355 |
CORE_TOP | 0.000 | 0.000 | 0.082 | -465.983 | 0.000 | 0.000 | 84.657 | 231.415 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -171.448 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -83.676 | 0.000 | 0.000 | 10.531 | 29.056 | 40.341 | 13.064 | 0.000 | 0.040 | 37.027 | 0.000 | -41.388 | 0.000 | -4.996 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -74.312 | 0.000 | 0.000 | 6.855 | 18.725 | 25.998 | 34.547 | 0.000 | 0.028 | 16.288 | 0.000 | -24.967 | 0.000 | -3.161 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -112.827 | 0.000 | 0.000 | 10.526 | 29.057 | 40.342 | 65.737 | 0.000 | 0.035 | 11.603 | 0.000 | -39.456 | 0.000 | -5.017 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -112.021 | 0.000 | 0.000 | 6.780 | 18.725 | 25.997 | 38.869 | 0.000 | 0.025 | 55.133 | 0.000 | -29.852 | 0.000 | -3.656 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.112 | -583.064 | 0.000 | 0.000 | 107.296 | 290.565 | 403.414 | 140.198 | 0.000 | 0.973 | 119.440 | 0.000 | -378.459 | 0.000 | -100.473 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.103 | -625.603 | 0.000 | 0.000 | 51.748 | 187.251 | 259.975 | 348.424 | 0.000 | 0.641 | 80.540 | 0.000 | -236.091 | 0.000 | -66.989 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.025 | -925.698 | 0.000 | 0.000 | 105.918 | 290.571 | 403.420 | 655.584 | 0.000 | 0.756 | 0.006 | 0.000 | -383.948 | 0.000 | -108.582 | -38.046 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.019 | -688.170 | 0.000 | 0.000 | 70.730 | 187.251 | 259.973 | 401.213 | 0.000 | 0.710 | 96.477 | 0.000 | -257.584 | 0.000 | -70.620 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.193 | -56.876 | 0.000 | 0.000 | 11.078 | 29.056 | 40.341 | 14.765 | 0.000 | 0.136 | 6.071 | 0.000 | -34.550 | 0.000 | -11.216 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.568 | -58.026 | 0.000 | 0.000 | 7.134 | 18.725 | 25.998 | 35.326 | 0.000 | 0.080 | 0.001 | 0.000 | -22.095 | 0.000 | -7.666 | -0.044 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.504 | -86.650 | 0.000 | 0.000 | 10.828 | 29.057 | 40.342 | 66.292 | 0.000 | 0.094 | 0.000 | 0.000 | -35.684 | 0.000 | -12.340 | -12.444 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.307 | -66.445 | 0.000 | 0.000 | 7.262 | 18.725 | 25.997 | 40.409 | 0.000 | 0.093 | 5.807 | 0.000 | -24.037 | 0.000 | -8.119 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.229 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.008 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1267.919 | 0.000 | 0.000 | 0.000 | 33.564 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -304.450 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.125 | -118.538 | 0.000 | 0.000 | 0.000 | 3.356 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -38.825 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.071 | -7152.601 | 0.000 | 0.000 | 0.000 | 72.655 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -414.982 |
GROUNDFLOOR_PLENUM | 0.845 | -76.091 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.059 | 85.620 | 0.000 | 0.000 | 0.000 | -10.433 | 0.000 |
MIDFLOOR_PLENUM | 4.492 | -494.473 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.149 | 666.842 | 0.000 | 0.000 | 0.000 | -178.010 | 0.000 |
TOPFLOOR_PLENUM | 8.182 | -67.988 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.099 | 78.335 | 0.000 | 0.000 | 0.000 | -18.629 | 0.000 |
Total Facility | 13.519 | -638.551 | 11.260 | -19370.947 | 0.000 | 0.000 | 1503.144 | 4294.357 | 15213.288 | 1854.427 | 0.000 | 4.918 | 1332.357 | 0.000 | -1508.111 | 0.000 | -609.905 | -2099.747 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-DEC-08:50 | 0.00 | 0.00 | 0.00 | -123286.91 | 0.00 | 0.00 | 399.54 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 108185.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 04-OCT-03:02 | 0.00 | 0.00 | 0.00 | -95860.54 | 0.00 | 0.00 | 0.00 | 1209.06 | 8057.15 | 0.00 | 0.00 | 0.00 | 86594.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 04-OCT-03:01 | 0.00 | 0.00 | 0.00 | -820113.14 | 0.00 | 0.00 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 727451.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -79839.12 | 0.00 | 0.00 | 864.60 | 2235.31 | 8057.12 | 0.00 | 0.00 | 0.00 | 68682.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-OCT-03:01 | 0.00 | 0.00 | 0.00 | -10672.64 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.70 | 0.00 | 0.00 | 0.00 | 10577.33 | 0.00 | -1068.20 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:42 | 0.00 | 0.00 | 0.00 | -16240.10 | 0.00 | 0.00 | 25.28 | 90.44 | 488.98 | 9652.09 | 0.00 | 190.93 | 5792.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:42 | 0.00 | 0.00 | 0.00 | -19116.78 | 0.00 | 0.00 | 36.14 | 140.34 | 758.78 | 14514.01 | 0.00 | 260.84 | 3406.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-APR-17:02 | 0.00 | 0.00 | 0.00 | -20850.12 | 0.00 | 0.00 | 0.00 | 97.83 | 488.98 | 6016.07 | 0.00 | 0.00 | 14370.35 | 0.00 | -0.00 | 0.00 | -123.11 | 0.00 |
PERIMETER_MID_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -107625.35 | 0.00 | 0.00 | 1089.88 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 101664.94 | 0.00 | -8040.52 | 0.00 | -12.57 | 0.00 |
PERIMETER_MID_ZN_2 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | -109905.83 | 0.00 | 0.00 | 711.78 | 1808.72 | 6519.76 | 0.00 | 0.00 | 0.00 | 106259.81 | 0.00 | -5385.31 | 0.00 | -8.93 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-13:42 | 0.00 | 0.00 | 0.00 | -176433.49 | 0.00 | 0.00 | 359.84 | 1403.36 | 7587.84 | 117134.24 | 0.00 | 3764.26 | 46183.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:31 | 0.00 | 0.00 | 0.00 | -165326.08 | 0.00 | 0.00 | 257.63 | 904.36 | 4889.79 | 86742.40 | 0.00 | 0.00 | 75443.53 | 0.00 | -0.00 | 0.00 | -2911.63 | 0.00 |
PERIMETER_TOP_ZN_3 | 05-OCT-05:01 | 0.00 | 0.00 | 0.00 | -10846.87 | 0.00 | 0.00 | 113.06 | 280.67 | 1011.70 | 0.00 | 0.00 | 0.00 | 10301.74 | 0.00 | -860.30 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 15-OCT-08:52 | 0.00 | 0.00 | 0.00 | -15713.56 | 0.00 | 0.00 | 26.85 | 90.44 | 488.98 | 9258.35 | 0.00 | 656.05 | 5192.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:52 | 0.00 | 0.00 | 0.00 | -20016.08 | 0.00 | 0.00 | 34.52 | 140.34 | 758.78 | 14010.44 | 0.00 | 634.32 | 4437.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:32 | 0.00 | 0.00 | 0.00 | -18541.37 | 0.00 | 0.00 | 23.48 | 90.44 | 488.98 | 10355.11 | 0.00 | 205.98 | 7377.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-17:55 | 0.00 | 0.00 | 0.00 | -7790.45 | 0.00 | 0.00 | 0.00 | 17.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21.50 |
DATACENTER_MID_ZN_6 | 31-AUG-17:00 | 0.00 | 0.00 | 0.00 | -72790.86 | 0.00 | 0.00 | 0.00 | 1621.00 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6774.36 |
DATACENTER_TOP_ZN_6 | 20-AUG-17:28 | 0.00 | 0.00 | 0.00 | -7405.75 | 0.00 | 0.00 | 0.00 | 17.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -406.21 |
DATACENTER_BASEMENT_ZN_6 | 01-MAR-00:22 | 0.00 | 0.00 | 0.00 | -399727.52 | 0.00 | 0.00 | 0.00 | 379.60 | 284724.39 | 0.00 | 0.00 | 0.00 | 114623.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-SEP-05:13 | 0.00 | -9710.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9710.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 16-OCT-05:01 | 0.00 | -73390.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75339.13 | 0.00 | -0.00 | 0.00 | -1948.99 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:10 | 0.00 | -17420.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.25 | 16941.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | 24449.90 | 0.00 | -1797510.27 | 0.00 | 0.00 | 15307.49 | 41480.56 | 623236.89 | 0.00 | 0.00 | 0.00 | 1142973.77 | 0.00 | -47557.65 | 0.00 | -2380.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-AUG-17:00 | 0.00 | 0.00 | 135545.30 | 0.00 | 0.00 | 0.00 | 400.21 | 1244.51 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -150647.56 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 60558.41 | -0.00 | 0.00 | 0.00 | 0.00 | 2418.12 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -71033.65 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JAN-06:01 | 0.00 | 0.00 | 90723.72 | -0.00 | 0.00 | 0.00 | 1468.34 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37425.28 | 0.00 | -4419.64 | -63270.77 |
PERIMETER_MID_ZN_2 | 30-MAR-05:01 | 0.00 | 0.00 | 83635.66 | -0.00 | 0.00 | 0.00 | 950.11 | 1808.72 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21610.38 | 0.00 | -3316.58 | -67987.29 |
PERIMETER_MID_ZN_1 | 30-MAR-05:01 | 0.00 | 0.00 | 109600.77 | -0.00 | 0.00 | 0.00 | 1446.60 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33264.51 | 0.00 | -5094.58 | -85612.13 |
PERIMETER_MID_ZN_4 | 30-MAR-05:01 | 0.00 | 0.00 | 69460.92 | -0.00 | 0.00 | 0.00 | 920.42 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21975.16 | 0.00 | -3455.51 | -53279.11 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:03 | 0.00 | 0.00 | 11939.25 | -0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1546.08 | 0.00 | -1731.33 | -9825.34 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:01 | 0.00 | 0.00 | 11528.28 | -0.00 | 0.00 | 0.00 | 0.00 | 195.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1869.39 | 0.00 | -926.10 | -9580.42 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 13695.87 | -0.00 | 0.00 | 0.00 | 0.00 | 303.63 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1425.27 | 0.00 | -1797.00 | -11788.94 |
PERIMETER_TOP_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 11377.48 | -0.00 | 0.00 | 0.00 | 0.00 | 195.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1915.25 | 0.00 | -944.09 | -9365.78 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 09-JAN-01:12 | 0.00 | 0.00 | 532.10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2498.24 |
DATACENTER_BASEMENT_ZN_6 | 03-JAN-01:19 | 0.00 | 0.00 | 39918.28 | 0.00 | 0.00 | 0.00 | 0.00 | 379.60 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -135206.01 |
GROUNDFLOOR_PLENUM | 18-DEC-03:51 | 12135.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1682.47 | -10452.80 |
MIDFLOOR_PLENUM | 28-MAR-05:01 | 86996.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8290.12 | -78706.38 |
TOPFLOOR_PLENUM | 19-MAY-05:01 | 21530.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -327.59 | -21202.79 |
Total Facility | 30-MAR-05:01 | -1023933.11 | 1086485.72 | 396469.46 | -1086485.72 | 0.00 | 0.00 | 17212.31 | 41480.56 | 504945.49 | 0.00 | 0.00 | 0.00 | 225482.46 | 0.00 | -131305.02 | 0.00 | -30352.14 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.7477 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.7477 | 0.2088 | 1.0000 | 1.2001 | 0.2088 | ||
VAV_BOT WITH REHEAT | 9.9909 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.3622 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 92.9356 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 86.7686 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.4710 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.9662 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5878 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5878 | 0.0157 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4707 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4707 | 0.0332 | 1.0000 | 0.0156 | 0.0332 | ||
AIRLOOP DATACENTER MID | 4.4675 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4675 | 0.0350 | 1.0000 | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4550 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4550 | 0.0344 | 1.0000 | 0.0156 | 0.0344 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.7477 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.7477 | 1.0000 | 1.0000 | 1.2001 | 0.2088 | ||
VAV_BOT WITH REHEAT | 4.9955 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.9973 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 46.4678 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 28.2524 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.7355 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.9266 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5878 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5878 | 1.0000 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4707 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4707 | 1.0000 | 1.0000 | 0.0156 | 0.0332 | ||
AIRLOOP DATACENTER MID | 4.4675 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4675 | 1.0000 | 1.0000 | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4550 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4550 | 1.0000 | 1.0000 | 0.0156 | 0.0344 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.7477 | 5.7477 | 5.7477 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9880 | 5.9880 | 1.7964 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.3954 | 56.3954 | 17.1442 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5374 | 5.5374 | 1.7111 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8529 | 0.8529 | 0.2559 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9448 | 0.9448 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0273 | 1.0273 | 0.3082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1779 | 1.1779 | 0.3534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7190 | 7.7190 | 2.3466 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5579 | 9.5579 | 2.9056 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4830 | 9.4830 | 2.8828 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.7802 | 9.7802 | 2.9732 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8871 | 0.8871 | 0.2741 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9414 | 0.9414 | 0.2909 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0528 | 1.0528 | 0.3253 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0524 | 1.0524 | 0.3252 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4707 | 0.4707 | 0.4707 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4675 | 4.4675 | 4.4675 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4550 | 0.4550 | 0.4550 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5878 | 21.5878 | 21.5878 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.7477 | 5.7477 | 5.7477 | 5.7477 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 9.9909 | 9.3622 | 9.9909 | 2.9973 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 92.9356 | 86.7686 | 92.9356 | 28.2524 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.4710 | 8.9662 | 9.4710 | 2.9266 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5878 | 21.5878 | 21.5878 | 21.5878 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4707 | 0.4707 | 0.4707 | 0.4707 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4675 | 4.4675 | 4.4675 | 4.4675 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4550 | 0.4550 | 0.4550 | 0.4550 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.7477 | 5.7477 | 5.7477 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9940 | 2.9940 | 1.7964 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1977 | 28.1977 | 17.1442 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7687 | 2.7687 | 1.7111 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4264 | 0.4264 | 0.2559 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4724 | 0.4724 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5136 | 0.5136 | 0.3082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5890 | 0.5890 | 0.3534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8595 | 3.8595 | 2.3466 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7790 | 4.7790 | 2.9056 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7415 | 4.7415 | 2.8828 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8901 | 4.8901 | 2.9732 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4435 | 0.4435 | 0.2741 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4707 | 0.4707 | 0.2909 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5264 | 0.5264 | 0.3253 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5262 | 0.5262 | 0.3252 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4707 | 0.4707 | 0.4707 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4675 | 4.4675 | 4.4675 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4550 | 0.4550 | 0.4550 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5878 | 21.5878 | 21.5878 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.7477 | 5.7477 | 5.7477 | 5.7477 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 4.9955 | 2.9973 | 2.9973 | 2.9973 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 46.4678 | 28.2524 | 28.2524 | 28.2524 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.7355 | 2.9266 | 2.9266 | 2.9266 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5878 | 21.5878 | 21.5878 | 21.5878 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4707 | 0.4707 | 0.4707 | 0.4707 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4675 | 4.4675 | 4.4675 | 4.4675 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4550 | 0.4550 | 0.4550 | 0.4550 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 20:02:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 164.67 |
Number of hours not met | 164.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 369.12 | 609378.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1133.41 | 311201.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2376.57 | 139123.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 4294.36 | 373325.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 884.83 | 56280.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.73 | 5498.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.27 | 1942.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2208.11 | 144957.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 607.90 | 56873.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 138.51 | 33083.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 1260.25 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 6.70 | 32206.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 550.62 | 72191.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 30168.02 |
Natural Gas | 0.00 | 919.74 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 31087.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 92.71 |
Space Heating | 0.00 |
Space Cooling | 75.78 |
Fans (All) | 47.67 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 651.29 |
Subtotal | 651.29 |
Natural Gas [MJ/m2] | |
Space Heating | 7.97 |
Service Water Heating | 11.89 |
Miscellaneous (All) | 19.86 |
Subtotal | 19.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.81 |
Space Heating | 1.19 |
Space Cooling | 11.29 |
Fans (All) | 7.10 |
Service Water Heating | 1.77 |
Receptacle Equipment | 48.94 |
Miscellaneous | 15.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2728. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2378. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.803133E+11 |
February | 0.000 | 0.576664E+11 |
March | 0.000 | 0.840401E+11 |
April | 0.000 | 0.224201E+11 |
May | 0.000 | 0.133536E+11 |
June | 0.000 | 0.115473E+10 |
July | 0.000 | 0.156587E+10 |
August | 0.000 | 0.111022E+10 |
September | 0.000 | 0.769785E+09 |
October | 0.000 | 0.649724E+10 |
November | 0.000 | 0.333338E+11 |
December | 0.000 | 0.668921E+11 |
Annual Sum or Average | 0.369117E+12 | |
Minimum of Months | 0.000 | 0.769785E+09 |
Maximum of Months | 0.000 | 0.840401E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.626449E+11 | 120722.22 | 01-JAN-15:02 | 13.00 | 9.26 | 0.567114E+10 | 7499.45 | 10-JAN-14:20 | 16.67 | 11.78 |
February | 0.542373E+11 | 123244.26 | 20-FEB-09:10 | 14.00 | 8.39 | 0.514182E+10 | 7500.26 | 01-FEB-14:20 | 19.00 | 15.51 |
March | 0.636532E+11 | 119605.55 | 20-MAR-00:02 | 10.83 | 10.30 | 0.613574E+10 | 7499.47 | 01-MAR-14:20 | 18.00 | 14.20 |
April | 0.596212E+11 | 122703.85 | 16-APR-22:30 | 10.50 | 9.15 | 0.545247E+10 | 7499.39 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.606241E+11 | 116525.80 | 15-MAY-01:41 | 8.33 | 7.77 | 0.590195E+10 | 7499.47 | 05-MAY-13:00 | 18.00 | 16.13 |
June | 0.612347E+11 | 115502.85 | 05-JUN-00:22 | 13.50 | 12.06 | 0.588243E+10 | 7499.15 | 21-JUN-13:20 | 23.67 | 16.90 |
July | 0.627473E+11 | 114011.74 | 04-JUL-22:57 | 16.00 | 14.12 | 0.547473E+10 | 7499.11 | 13-JUL-09:00 | 22.00 | 18.09 |
August | 0.682882E+11 | 111144.66 | 27-AUG-23:10 | 15.02 | 14.97 | 0.613821E+10 | 7499.10 | 30-AUG-13:20 | 23.67 | 18.22 |
September | 0.608994E+11 | 110260.96 | 20-SEP-03:01 | 11.00 | 9.85 | 0.545339E+10 | 7499.42 | 21-SEP-09:20 | 19.67 | 17.71 |
October | 0.664110E+11 | 118369.45 | 09-OCT-05:42 | 12.17 | 11.06 | 0.567353E+10 | 7499.30 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.653031E+11 | 119757.97 | 05-NOV-23:12 | 10.00 | 8.89 | 0.561787E+10 | 7499.86 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.650853E+11 | 123298.94 | 25-DEC-08:50 | 13.42 | 7.90 | 0.547516E+10 | 7500.07 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.750750E+12 | 0.680184E+11 | ||||||||
Minimum of Months | 0.542373E+11 | 110260.96 | 8.33 | 7.77 | 0.514182E+10 | 7499.10 | 16.67 | 11.68 | ||
Maximum of Months | 0.682882E+11 | 123298.94 | 16.00 | 14.97 | 0.613821E+10 | 7500.26 | 23.67 | 18.22 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516091E+11 | 81331.56 | 17-JAN-04:02 | 14.00 | 12.83 | 0.508046E+10 | 6735.07 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.487099E+11 | 80434.20 | 01-FEB-04:01 | 16.00 | 9.06 | 0.460614E+10 | 6735.30 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.599125E+11 | 80973.58 | 21-MAR-03:02 | 13.00 | 12.44 | 0.550195E+10 | 6735.05 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.622361E+11 | 82753.99 | 14-APR-03:02 | 14.00 | 13.37 | 0.488256E+10 | 6735.13 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.554408E+11 | 80602.61 | 25-MAY-03:01 | 16.00 | 13.58 | 0.528702E+10 | 6735.09 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.594181E+11 | 88055.29 | 27-JUN-03:02 | 17.00 | 15.73 | 0.527196E+10 | 6734.60 | 08-JUN-09:30 | 16.00 | 14.44 |
July | 0.658268E+11 | 87396.56 | 13-JUL-03:02 | 17.00 | 15.07 | 0.489574E+10 | 6734.40 | 03-JUL-13:09 | 22.00 | 16.83 |
August | 0.731774E+11 | 87337.59 | 01-AUG-03:02 | 17.25 | 15.30 | 0.549609E+10 | 6734.47 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.546033E+11 | 87345.35 | 06-SEP-03:02 | 17.00 | 15.06 | 0.488224E+10 | 6734.68 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.600756E+11 | 95868.73 | 04-OCT-03:02 | 20.00 | 18.02 | 0.507716E+10 | 6735.04 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.582033E+11 | 85493.42 | 28-NOV-04:02 | 16.00 | 5.30 | 0.503168E+10 | 6735.54 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.600272E+11 | 89845.32 | 18-DEC-03:51 | 18.00 | 6.95 | 0.490301E+10 | 6735.83 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.709240E+12 | 0.609160E+11 | ||||||||
Minimum of Months | 0.487099E+11 | 80434.20 | 13.00 | 5.30 | 0.460614E+10 | 6734.40 | 16.00 | 11.68 | ||
Maximum of Months | 0.731774E+11 | 95868.73 | 20.00 | 18.02 | 0.550195E+10 | 6735.83 | 23.17 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400247E+11 | 71856.72 | 18-JAN-06:01 | 15.67 | 11.88 | 0.505647E+10 | 6735.04 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.363567E+11 | 68617.67 | 01-FEB-05:03 | 15.33 | 8.86 | 0.458539E+10 | 6735.33 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.428812E+11 | 66577.79 | 16-MAR-05:01 | 12.83 | 11.80 | 0.548304E+10 | 6735.02 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.425831E+11 | 72057.22 | 27-APR-04:02 | 15.00 | 14.40 | 0.486812E+10 | 6735.02 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.451962E+11 | 72223.73 | 08-MAY-04:02 | 14.00 | 12.33 | 0.527656E+10 | 6735.06 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.476768E+11 | 79983.08 | 26-JUN-04:02 | 17.83 | 15.37 | 0.526180E+10 | 6734.59 | 08-JUN-09:30 | 16.00 | 14.44 |
July | 0.480517E+11 | 78805.51 | 20-JUL-05:02 | 17.00 | 17.00 | 0.488754E+10 | 6734.44 | 03-JUL-13:09 | 22.00 | 16.83 |
August | 0.518906E+11 | 79915.79 | 07-AUG-05:02 | 18.00 | 17.98 | 0.548915E+10 | 6734.46 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.453719E+11 | 81637.82 | 30-SEP-05:02 | 23.80 | 13.82 | 0.487262E+10 | 6734.66 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.469563E+11 | 82013.67 | 04-OCT-03:01 | 20.00 | 18.02 | 0.506253E+10 | 6735.02 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.416157E+11 | 69154.15 | 13-NOV-04:03 | 11.83 | 10.73 | 0.501440E+10 | 6735.38 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.406239E+11 | 70744.63 | 19-DEC-06:02 | 16.83 | 5.75 | 0.487689E+10 | 6735.67 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.529229E+12 | 0.607345E+11 | ||||||||
Minimum of Months | 0.363567E+11 | 66577.79 | 11.83 | 5.75 | 0.458539E+10 | 6734.44 | 16.00 | 11.84 | ||
Maximum of Months | 0.518906E+11 | 82013.67 | 23.80 | 18.02 | 0.548915E+10 | 6735.67 | 26.83 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295855E+11 | 62245.04 | 25-JAN-06:01 | 16.00 | 11.05 | 0.483016E+10 | 6734.94 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.281682E+11 | 56797.90 | 16-FEB-06:01 | 11.98 | 11.91 | 0.443528E+10 | 6735.30 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.343495E+11 | 60437.74 | 24-MAR-05:02 | 12.00 | 12.00 | 0.534606E+10 | 6734.90 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.388074E+11 | 70655.07 | 27-APR-05:02 | 15.00 | 14.40 | 0.481141E+10 | 6735.01 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.415460E+11 | 68332.61 | 03-MAY-05:02 | 14.17 | 14.07 | 0.522509E+10 | 6735.11 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.466529E+11 | 73768.10 | 26-JUN-04:01 | 17.83 | 15.37 | 0.523760E+10 | 6734.57 | 08-JUN-09:39 | 16.00 | 14.55 |
July | 0.488855E+11 | 76815.99 | 19-JUL-05:02 | 16.20 | 16.13 | 0.487463E+10 | 6734.39 | 28-JUL-13:00 | 23.00 | 19.54 |
August | 0.521201E+11 | 74875.86 | 30-AUG-05:02 | 18.00 | 15.43 | 0.547217E+10 | 6734.42 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.423055E+11 | 79838.33 | 30-SEP-05:02 | 23.80 | 13.82 | 0.484065E+10 | 6734.60 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.416907E+11 | 79802.19 | 02-OCT-03:02 | 19.00 | 17.65 | 0.500459E+10 | 6734.98 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.319923E+11 | 62295.75 | 10-NOV-06:01 | 15.17 | 13.96 | 0.488347E+10 | 6735.26 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.298807E+11 | 56447.49 | 06-DEC-06:01 | 12.33 | 6.16 | 0.469020E+10 | 6735.55 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.465984E+12 | 0.596513E+11 | ||||||||
Minimum of Months | 0.281682E+11 | 56447.49 | 11.98 | 6.16 | 0.443528E+10 | 6734.39 | 16.00 | 11.84 | ||
Maximum of Months | 0.521201E+11 | 79838.33 | 23.80 | 17.65 | 0.547217E+10 | 6735.55 | 26.83 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514578E+10 | 6697.64 | 17-JAN-13:40 | 23.33 | 16.99 | 0.626100E+09 | 845.66 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.500269E+10 | 5924.01 | 01-FEB-12:00 | 26.00 | 14.65 | 0.569983E+09 | 845.70 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.618354E+10 | 6630.64 | 13-MAR-13:50 | 17.83 | 13.80 | 0.683060E+09 | 845.66 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.730720E+10 | 8895.69 | 27-APR-05:01 | 15.00 | 14.40 | 0.609237E+09 | 845.67 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.683377E+10 | 7309.91 | 04-MAY-13:40 | 23.00 | 16.65 | 0.659366E+09 | 845.68 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.789769E+10 | 10031.54 | 26-JUN-05:03 | 17.17 | 15.13 | 0.660331E+09 | 845.61 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.910691E+10 | 10090.99 | 26-JUL-05:01 | 18.00 | 16.69 | 0.613846E+09 | 845.59 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.981024E+10 | 10280.60 | 07-AUG-05:01 | 18.00 | 17.98 | 0.688832E+09 | 845.59 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.692275E+10 | 10515.22 | 30-SEP-05:01 | 23.80 | 13.82 | 0.609694E+09 | 845.62 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.741235E+10 | 10673.24 | 04-OCT-03:01 | 20.00 | 18.02 | 0.633671E+09 | 845.66 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.604876E+10 | 6506.49 | 28-NOV-14:10 | 24.67 | 10.96 | 0.625629E+09 | 845.72 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.600426E+10 | 6952.04 | 05-DEC-15:00 | 25.00 | 13.20 | 0.608131E+09 | 845.75 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.836760E+11 | 0.758788E+10 | ||||||||
Minimum of Months | 0.500269E+10 | 5924.01 | 15.00 | 10.96 | 0.569983E+09 | 845.59 | 16.83 | 11.84 | ||
Maximum of Months | 0.981024E+10 | 10673.24 | 26.00 | 18.02 | 0.688832E+09 | 845.75 | 26.83 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481732E+10 | 6192.40 | 20-JAN-09:00 | 17.00 | 13.94 | 0.397416E+09 | 544.97 | 05-JAN-10:00 | 17.00 | 9.44 |
February | 0.446507E+10 | 7240.89 | 21-FEB-08:50 | 13.67 | 9.74 | 0.360153E+09 | 545.00 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.542301E+10 | 8276.98 | 23-MAR-08:30 | 18.00 | 14.36 | 0.432026E+09 | 544.97 | 08-MAR-10:09 | 15.17 | 11.04 |
April | 0.665727E+10 | 12480.46 | 30-APR-08:62 | 18.67 | 14.17 | 0.388400E+09 | 545.01 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.621160E+10 | 10477.26 | 29-MAY-07:40 | 17.33 | 13.81 | 0.420590E+09 | 544.99 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.682617E+10 | 9577.70 | 25-JUN-06:32 | 17.33 | 14.70 | 0.420408E+09 | 544.95 | 02-JUN-09:50 | 21.50 | 15.57 |
July | 0.817321E+10 | 12465.73 | 23-JUL-08:13 | 23.67 | 19.21 | 0.392157E+09 | 544.93 | 10-JUL-09:00 | 21.00 | 15.41 |
August | 0.874007E+10 | 9565.80 | 20-AUG-08:24 | 21.10 | 18.44 | 0.439834E+09 | 544.94 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.627519E+10 | 12818.65 | 10-SEP-08:32 | 21.00 | 17.13 | 0.388046E+09 | 544.96 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.644777E+10 | 16240.90 | 15-OCT-08:42 | 32.33 | 15.57 | 0.402747E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.513123E+10 | 6698.52 | 20-NOV-08:35 | 12.33 | 11.60 | 0.396792E+09 | 545.00 | 06-NOV-10:00 | 19.00 | 13.18 |
December | 0.514427E+10 | 6562.01 | 05-DEC-09:00 | 24.00 | 11.77 | 0.383264E+09 | 544.98 | 04-DEC-14:09 | 22.33 | 13.55 |
Annual Sum or Average | 0.743122E+11 | 0.482183E+10 | ||||||||
Minimum of Months | 0.446507E+10 | 6192.40 | 12.33 | 9.74 | 0.360153E+09 | 544.93 | 15.17 | 9.44 | ||
Maximum of Months | 0.874007E+10 | 16240.90 | 32.33 | 19.21 | 0.439834E+09 | 545.01 | 23.17 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.988895E+10 | 14934.35 | 29-JAN-12:13 | 15.67 | 12.24 | 0.633402E+09 | 886.45 | 26-JAN-14:20 | 16.67 | 11.94 |
February | 0.788478E+10 | 13886.01 | 21-FEB-13:00 | 21.00 | 13.52 | 0.569717E+09 | 864.30 | 22-FEB-14:09 | 18.80 | 12.71 |
March | 0.831152E+10 | 13083.91 | 01-MAR-13:20 | 18.67 | 13.61 | 0.678576E+09 | 845.71 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.871769E+10 | 10420.40 | 26-APR-13:00 | 27.00 | 17.11 | 0.606511E+09 | 845.70 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.715183E+10 | 8093.04 | 04-MAY-13:10 | 23.00 | 16.65 | 0.653759E+09 | 845.71 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.796122E+10 | 9763.91 | 26-JUN-05:03 | 17.17 | 15.13 | 0.656186E+09 | 845.63 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.953171E+10 | 10449.42 | 24-JUL-05:03 | 16.83 | 16.83 | 0.611083E+09 | 845.61 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.112145E+11 | 11491.13 | 30-AUG-12:40 | 23.67 | 17.82 | 0.686976E+09 | 845.61 | 29-AUG-13:00 | 24.00 | 17.63 |
September | 0.941686E+10 | 14466.08 | 29-SEP-13:20 | 35.33 | 18.07 | 0.609536E+09 | 887.21 | 29-SEP-13:20 | 35.33 | 18.07 |
October | 0.111694E+11 | 19116.53 | 15-OCT-12:42 | 32.00 | 15.98 | 0.637718E+09 | 921.13 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.104388E+11 | 18066.21 | 19-NOV-10:43 | 26.00 | 14.85 | 0.631244E+09 | 884.62 | 27-NOV-14:09 | 22.83 | 9.18 |
December | 0.111384E+11 | 18052.32 | 25-DEC-11:53 | 23.00 | 9.60 | 0.618666E+09 | 902.92 | 19-DEC-14:09 | 22.83 | 9.76 |
Annual Sum or Average | 0.112826E+12 | 0.759337E+10 | ||||||||
Minimum of Months | 0.715183E+10 | 8093.04 | 15.67 | 9.60 | 0.569717E+09 | 845.61 | 16.67 | 9.18 | ||
Maximum of Months | 0.112145E+11 | 19116.53 | 35.33 | 18.07 | 0.686976E+09 | 921.13 | 35.33 | 18.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639258E+10 | 12075.80 | 21-JAN-06:01 | 13.00 | 13.00 | 0.395829E+09 | 544.99 | 10-JAN-14:09 | 16.83 | 11.84 |
February | 0.657431E+10 | 12249.30 | 24-FEB-06:01 | 12.00 | 10.90 | 0.367929E+09 | 545.00 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.869190E+10 | 19646.38 | 19-MAR-15:52 | 18.00 | 14.96 | 0.443361E+09 | 544.99 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.110982E+11 | 20850.29 | 30-APR-17:02 | 21.67 | 15.81 | 0.395859E+09 | 545.00 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.821553E+10 | 16709.00 | 14-MAY-15:32 | 17.33 | 12.56 | 0.422798E+09 | 545.01 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.994190E+10 | 16619.18 | 21-JUN-03:01 | 17.00 | 14.50 | 0.425917E+09 | 544.95 | 08-JUN-13:00 | 17.00 | 14.50 |
July | 0.122981E+11 | 18951.20 | 09-JUL-15:52 | 21.00 | 15.96 | 0.397203E+09 | 544.93 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.140692E+11 | 20750.84 | 06-AUG-17:42 | 21.33 | 19.00 | 0.445700E+09 | 544.94 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.844783E+10 | 18829.18 | 10-SEP-15:42 | 22.00 | 16.92 | 0.391250E+09 | 544.95 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.909644E+10 | 20139.10 | 15-OCT-14:02 | 31.00 | 15.25 | 0.408683E+09 | 544.99 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.832706E+10 | 15674.69 | 10-NOV-04:01 | 15.00 | 14.31 | 0.405966E+09 | 545.07 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.886690E+10 | 15820.04 | 19-DEC-04:01 | 16.00 | 5.12 | 0.396491E+09 | 545.08 | 20-DEC-14:50 | 19.20 | 11.86 |
Annual Sum or Average | 0.112020E+12 | 0.489699E+10 | ||||||||
Minimum of Months | 0.639258E+10 | 12075.80 | 12.00 | 5.12 | 0.367929E+09 | 544.93 | 16.83 | 11.84 | ||
Maximum of Months | 0.140692E+11 | 20850.29 | 31.00 | 19.00 | 0.445700E+09 | 545.08 | 26.83 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360134E+10 | 4968.90 | 18-JAN-14:20 | 24.07 | 14.80 | 0.592736E+09 | 845.62 | 13-JAN-14:09 | 25.67 | 15.32 |
February | 0.332336E+10 | 4436.38 | 03-FEB-15:00 | 23.00 | 8.80 | 0.543649E+09 | 845.69 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.392958E+10 | 5057.74 | 23-MAR-14:50 | 22.17 | 17.38 | 0.651184E+09 | 845.63 | 09-MAR-14:09 | 18.00 | 13.96 |
April | 0.460216E+10 | 6276.72 | 26-APR-14:00 | 26.00 | 16.72 | 0.595892E+09 | 845.66 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.515076E+10 | 6583.47 | 04-MAY-14:00 | 23.00 | 16.65 | 0.650658E+09 | 845.68 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.605362E+10 | 8774.17 | 30-JUN-05:01 | 17.00 | 16.37 | 0.655403E+09 | 845.61 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.645102E+10 | 8674.41 | 20-JUL-05:01 | 17.00 | 17.00 | 0.610377E+09 | 845.59 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.671681E+10 | 8343.74 | 07-AUG-05:01 | 18.00 | 17.98 | 0.684013E+09 | 845.59 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.545916E+10 | 10762.33 | 30-SEP-05:02 | 23.80 | 13.82 | 0.604083E+09 | 845.61 | 29-SEP-13:39 | 34.67 | 17.95 |
October | 0.550345E+10 | 9456.25 | 04-OCT-05:01 | 20.00 | 18.02 | 0.623152E+09 | 845.66 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.385289E+10 | 4491.76 | 10-NOV-14:30 | 19.50 | 15.77 | 0.603684E+09 | 845.68 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.366204E+10 | 4982.96 | 05-DEC-15:00 | 25.00 | 13.20 | 0.574944E+09 | 845.71 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.583062E+11 | 0.738978E+10 | ||||||||
Minimum of Months | 0.332336E+10 | 4436.38 | 17.00 | 8.80 | 0.543649E+09 | 845.59 | 18.00 | 12.36 | ||
Maximum of Months | 0.671681E+10 | 10762.33 | 26.00 | 18.02 | 0.684013E+09 | 845.71 | 34.67 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406078E+10 | 5026.96 | 20-JAN-09:30 | 18.00 | 14.37 | 0.271633E+09 | 521.19 | 27-JAN-09:09 | 12.33 | 9.06 |
February | 0.367611E+10 | 5088.72 | 21-FEB-09:40 | 16.00 | 10.65 | 0.247469E+09 | 521.20 | 22-FEB-09:00 | 15.00 | 11.56 |
March | 0.442504E+10 | 7532.25 | 23-MAR-09:00 | 19.00 | 14.75 | 0.297558E+09 | 521.21 | 21-MAR-10:09 | 18.00 | 14.36 |
April | 0.526370E+10 | 9242.25 | 30-APR-08:53 | 22.00 | 15.38 | 0.279439E+09 | 521.26 | 13-APR-10:09 | 22.83 | 15.57 |
May | 0.541677E+10 | 7769.43 | 18-MAY-08:40 | 19.00 | 14.24 | 0.300305E+09 | 521.29 | 24-MAY-10:50 | 21.00 | 14.87 |
June | 0.608467E+10 | 8297.35 | 30-JUN-08:50 | 21.67 | 17.87 | 0.302569E+09 | 521.21 | 02-JUN-10:09 | 22.00 | 15.75 |
July | 0.682822E+10 | 9752.54 | 02-JUL-08:53 | 22.00 | 16.83 | 0.286970E+09 | 521.21 | 10-JUL-10:20 | 21.33 | 15.74 |
August | 0.722212E+10 | 9532.00 | 06-AUG-07:24 | 20.50 | 17.94 | 0.320480E+09 | 521.20 | 22-AUG-10:20 | 21.33 | 15.74 |
September | 0.560701E+10 | 10990.36 | 30-SEP-05:01 | 23.80 | 13.82 | 0.278650E+09 | 521.21 | 29-SEP-12:20 | 36.00 | 18.18 |
October | 0.559261E+10 | 8829.25 | 16-OCT-08:50 | 30.50 | 14.96 | 0.286569E+09 | 521.26 | 27-OCT-10:30 | 22.00 | 13.02 |
November | 0.424573E+10 | 4880.49 | 13-NOV-09:10 | 17.17 | 13.54 | 0.273325E+09 | 521.21 | 20-NOV-09:00 | 16.00 | 14.12 |
December | 0.413730E+10 | 5015.98 | 05-DEC-09:20 | 24.67 | 12.20 | 0.261914E+09 | 521.19 | 05-DEC-09:39 | 25.33 | 12.63 |
Annual Sum or Average | 0.625601E+11 | 0.340688E+10 | ||||||||
Minimum of Months | 0.367611E+10 | 4880.49 | 16.00 | 10.65 | 0.247469E+09 | 521.19 | 12.33 | 9.06 | ||
Maximum of Months | 0.722212E+10 | 10990.36 | 30.50 | 17.94 | 0.320480E+09 | 521.29 | 36.00 | 18.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.907053E+10 | 15960.30 | 22-JAN-13:53 | 18.00 | 12.35 | 0.633817E+09 | 924.52 | 27-JAN-14:09 | 16.83 | 12.83 |
February | 0.672570E+10 | 14759.34 | 20-FEB-12:41 | 17.00 | 10.16 | 0.561865E+09 | 888.42 | 22-FEB-14:20 | 18.60 | 12.66 |
March | 0.656360E+10 | 12228.93 | 01-MAR-13:20 | 18.67 | 13.61 | 0.662662E+09 | 856.41 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.630551E+10 | 9462.17 | 26-APR-13:10 | 26.83 | 17.05 | 0.596735E+09 | 845.70 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.579418E+10 | 7459.06 | 04-MAY-13:30 | 23.00 | 16.65 | 0.644560E+09 | 845.70 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.639289E+10 | 10033.20 | 30-JUN-05:01 | 17.00 | 16.37 | 0.649976E+09 | 845.63 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.701274E+10 | 10522.04 | 31-JUL-05:01 | 17.00 | 16.37 | 0.606818E+09 | 845.61 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.824520E+10 | 10696.58 | 30-AUG-12:50 | 23.83 | 17.96 | 0.682832E+09 | 845.61 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.832553E+10 | 13933.05 | 29-SEP-13:20 | 35.33 | 18.07 | 0.607463E+09 | 928.29 | 29-SEP-13:30 | 35.00 | 18.01 |
October | 0.982445E+10 | 17643.68 | 15-OCT-13:42 | 31.17 | 15.31 | 0.636978E+09 | 960.04 | 31-OCT-13:20 | 26.67 | 16.68 |
November | 0.892027E+10 | 16813.75 | 19-NOV-11:02 | 26.00 | 15.11 | 0.628462E+09 | 909.09 | 27-NOV-14:09 | 22.83 | 9.18 |
December | 0.938784E+10 | 17154.93 | 25-DEC-13:02 | 22.00 | 9.16 | 0.615830E+09 | 925.38 | 19-DEC-14:09 | 22.83 | 9.76 |
Annual Sum or Average | 0.925684E+11 | 0.752800E+10 | ||||||||
Minimum of Months | 0.579418E+10 | 7459.06 | 17.00 | 9.16 | 0.561865E+09 | 845.61 | 16.83 | 9.18 | ||
Maximum of Months | 0.982445E+10 | 17643.68 | 35.33 | 18.07 | 0.682832E+09 | 960.04 | 35.00 | 18.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432304E+10 | 6588.15 | 18-JAN-15:00 | 23.00 | 14.77 | 0.364733E+09 | 544.95 | 18-JAN-14:00 | 23.00 | 14.77 |
February | 0.408195E+10 | 7482.22 | 22-FEB-16:20 | 15.33 | 12.12 | 0.334220E+09 | 544.98 | 01-FEB-14:20 | 19.00 | 15.51 |
March | 0.491343E+10 | 9494.09 | 23-MAR-16:00 | 21.00 | 17.18 | 0.400869E+09 | 544.96 | 09-MAR-14:39 | 18.00 | 14.20 |
April | 0.583607E+10 | 10385.97 | 26-APR-16:00 | 22.00 | 16.40 | 0.373482E+09 | 544.99 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.594189E+10 | 12273.68 | 29-MAY-15:47 | 18.17 | 14.02 | 0.403961E+09 | 545.00 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.682179E+10 | 12633.65 | 26-JUN-04:01 | 17.83 | 15.37 | 0.411843E+09 | 544.94 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.743006E+10 | 14943.87 | 09-JUL-16:22 | 20.00 | 15.63 | 0.388046E+09 | 544.93 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.784845E+10 | 16534.25 | 13-AUG-16:31 | 23.33 | 19.66 | 0.433868E+09 | 544.93 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.629301E+10 | 11647.80 | 30-SEP-05:01 | 23.80 | 13.82 | 0.377822E+09 | 544.95 | 29-SEP-13:50 | 34.33 | 17.89 |
October | 0.605395E+10 | 12451.91 | 01-OCT-14:42 | 23.17 | 19.60 | 0.386772E+09 | 544.96 | 17-OCT-13:00 | 28.00 | 16.04 |
November | 0.473411E+10 | 7262.74 | 07-NOV-15:30 | 19.00 | 14.50 | 0.372766E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.453895E+10 | 7109.11 | 18-DEC-15:30 | 22.00 | 8.95 | 0.355473E+09 | 545.05 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.688167E+11 | 0.460386E+10 | ||||||||
Minimum of Months | 0.408195E+10 | 6588.15 | 15.33 | 8.95 | 0.334220E+09 | 544.93 | 18.00 | 12.36 | ||
Maximum of Months | 0.784845E+10 | 16534.25 | 23.80 | 19.66 | 0.433868E+09 | 545.05 | 34.33 | 17.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314217E+10 | 4400.89 | 18-JAN-15:00 | 23.00 | 14.77 | 0.539908E+09 | 845.62 | 18-JAN-14:30 | 23.80 | 14.80 |
February | 0.293081E+10 | 4064.75 | 01-FEB-15:00 | 19.00 | 14.75 | 0.500718E+09 | 845.69 | 01-FEB-14:09 | 19.00 | 15.69 |
March | 0.366339E+10 | 5219.32 | 23-MAR-15:20 | 21.67 | 17.33 | 0.603407E+09 | 845.61 | 10-MAR-14:00 | 22.00 | 13.03 |
April | 0.455207E+10 | 6936.55 | 26-APR-14:00 | 26.00 | 16.72 | 0.573083E+09 | 845.66 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.508831E+10 | 7274.03 | 04-MAY-13:50 | 23.00 | 16.65 | 0.629516E+09 | 845.68 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.620257E+10 | 7257.59 | 30-JUN-14:00 | 23.00 | 17.84 | 0.644605E+09 | 845.61 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.682800E+10 | 9215.19 | 19-JUL-05:01 | 16.20 | 16.13 | 0.604253E+09 | 845.59 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.703271E+10 | 7833.45 | 18-AUG-15:00 | 27.00 | 20.84 | 0.675349E+09 | 845.59 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.545324E+10 | 10329.67 | 30-SEP-05:01 | 23.80 | 13.82 | 0.589425E+09 | 845.61 | 29-SEP-13:39 | 34.67 | 17.95 |
October | 0.532866E+10 | 10848.27 | 05-OCT-05:01 | 20.00 | 18.62 | 0.601409E+09 | 845.66 | 31-OCT-13:09 | 26.83 | 16.90 |
November | 0.345921E+10 | 4191.99 | 10-NOV-14:40 | 19.33 | 15.81 | 0.557150E+09 | 845.61 | 28-NOV-14:00 | 23.00 | 10.75 |
December | 0.319493E+10 | 4489.17 | 05-DEC-15:00 | 25.00 | 13.20 | 0.522076E+09 | 845.59 | 05-DEC-14:00 | 25.00 | 13.20 |
Annual Sum or Average | 0.568761E+11 | 0.704090E+10 | ||||||||
Minimum of Months | 0.293081E+10 | 4064.75 | 16.20 | 13.20 | 0.500718E+09 | 845.59 | 19.00 | 10.75 | ||
Maximum of Months | 0.703271E+10 | 10848.27 | 27.00 | 20.84 | 0.675349E+09 | 845.69 | 34.67 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334793E+10 | 3781.39 | 20-JAN-11:00 | 21.00 | 15.42 | 0.349123E+09 | 540.73 | 20-JAN-10:09 | 19.33 | 14.88 |
February | 0.300805E+10 | 3802.72 | 01-FEB-10:10 | 23.83 | 12.68 | 0.323704E+09 | 544.92 | 02-FEB-10:09 | 17.17 | 12.18 |
March | 0.383828E+10 | 6495.94 | 23-MAR-09:30 | 20.50 | 15.61 | 0.392051E+09 | 544.95 | 22-MAR-09:39 | 18.00 | 14.73 |
April | 0.492499E+10 | 7940.05 | 26-APR-09:10 | 23.17 | 16.71 | 0.377726E+09 | 545.00 | 13-APR-09:00 | 23.00 | 15.73 |
May | 0.512732E+10 | 7101.39 | 04-MAY-09:10 | 20.33 | 14.87 | 0.405466E+09 | 545.00 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.604218E+10 | 8178.77 | 19-JUN-08:50 | 21.67 | 16.73 | 0.411014E+09 | 544.95 | 02-JUN-09:00 | 22.00 | 15.82 |
July | 0.690178E+10 | 10769.80 | 23-JUL-09:23 | 25.00 | 19.89 | 0.390499E+09 | 544.93 | 10-JUL-09:00 | 21.00 | 15.41 |
August | 0.725414E+10 | 8895.33 | 14-AUG-09:10 | 25.32 | 20.32 | 0.437470E+09 | 544.93 | 22-AUG-09:09 | 19.33 | 14.88 |
September | 0.538669E+10 | 10063.29 | 30-SEP-05:01 | 23.80 | 13.82 | 0.377671E+09 | 544.95 | 15-SEP-09:09 | 18.17 | 14.34 |
October | 0.517925E+10 | 15715.43 | 15-OCT-08:52 | 33.00 | 15.86 | 0.386729E+09 | 544.98 | 27-OCT-09:00 | 22.00 | 11.68 |
November | 0.363804E+10 | 4064.59 | 19-NOV-10:22 | 26.00 | 14.46 | 0.355052E+09 | 540.22 | 01-NOV-09:39 | 15.33 | 12.78 |
December | 0.337680E+10 | 3834.81 | 05-DEC-15:10 | 24.67 | 13.07 | 0.335809E+09 | 534.10 | 05-DEC-14:00 | 25.00 | 13.20 |
Annual Sum or Average | 0.580254E+11 | 0.454231E+10 | ||||||||
Minimum of Months | 0.300805E+10 | 3781.39 | 20.33 | 12.68 | 0.323704E+09 | 534.10 | 15.33 | 11.68 | ||
Maximum of Months | 0.725414E+10 | 15715.43 | 33.00 | 20.32 | 0.437470E+09 | 545.00 | 25.00 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765246E+10 | 15805.84 | 22-JAN-13:23 | 17.50 | 12.38 | 0.607153E+09 | 876.56 | 26-JAN-14:39 | 16.33 | 11.97 |
February | 0.570647E+10 | 15146.97 | 20-FEB-12:41 | 17.00 | 10.16 | 0.537704E+09 | 846.14 | 22-FEB-14:20 | 18.60 | 12.66 |
March | 0.587226E+10 | 12258.30 | 23-MAR-13:30 | 22.50 | 17.05 | 0.628830E+09 | 845.71 | 01-MAR-14:09 | 18.00 | 14.28 |
April | 0.611304E+10 | 10033.83 | 26-APR-13:10 | 26.83 | 17.05 | 0.577623E+09 | 845.70 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.571314E+10 | 8137.21 | 04-MAY-13:30 | 23.00 | 16.65 | 0.621497E+09 | 845.71 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.657585E+10 | 7388.41 | 30-JUN-13:50 | 23.00 | 17.84 | 0.635348E+09 | 845.63 | 07-JUN-13:00 | 19.00 | 14.24 |
July | 0.738376E+10 | 10457.69 | 19-JUL-05:01 | 16.20 | 16.13 | 0.598494E+09 | 845.61 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.852568E+10 | 11267.74 | 30-AUG-13:00 | 24.00 | 18.11 | 0.673109E+09 | 845.61 | 29-AUG-13:39 | 24.67 | 17.71 |
September | 0.815842E+10 | 15164.07 | 29-SEP-13:20 | 35.33 | 18.07 | 0.595103E+09 | 908.94 | 29-SEP-13:39 | 34.67 | 17.95 |
October | 0.934960E+10 | 20015.69 | 15-OCT-12:52 | 32.00 | 15.81 | 0.620449E+09 | 938.54 | 16-OCT-13:09 | 33.75 | 16.61 |
November | 0.770761E+10 | 17875.41 | 19-NOV-12:52 | 27.00 | 14.94 | 0.607395E+09 | 851.81 | 30-NOV-14:09 | 22.67 | 10.90 |
December | 0.789026E+10 | 14704.13 | 19-DEC-13:20 | 25.00 | 10.98 | 0.589417E+09 | 877.31 | 19-DEC-14:09 | 22.83 | 9.76 |
Annual Sum or Average | 0.866486E+11 | 0.729212E+10 | ||||||||
Minimum of Months | 0.570647E+10 | 7388.41 | 16.20 | 10.16 | 0.537704E+09 | 845.61 | 16.33 | 9.76 | ||
Maximum of Months | 0.934960E+10 | 20015.69 | 35.33 | 18.11 | 0.673109E+09 | 938.54 | 34.67 | 17.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374101E+10 | 6261.17 | 18-JAN-15:10 | 22.83 | 14.88 | 0.343272E+09 | 544.95 | 18-JAN-14:00 | 23.00 | 14.77 |
February | 0.356265E+10 | 7164.41 | 22-FEB-16:20 | 15.33 | 12.12 | 0.315777E+09 | 544.94 | 01-FEB-14:50 | 19.00 | 14.94 |
March | 0.452809E+10 | 9622.78 | 23-MAR-16:00 | 21.00 | 17.18 | 0.378801E+09 | 544.95 | 10-MAR-14:00 | 22.00 | 13.03 |
April | 0.573622E+10 | 11582.24 | 27-APR-05:01 | 15.00 | 14.40 | 0.359090E+09 | 544.98 | 13-APR-13:50 | 20.17 | 15.45 |
May | 0.587532E+10 | 11949.44 | 29-MAY-15:47 | 18.17 | 14.02 | 0.388612E+09 | 545.00 | 03-MAY-13:50 | 23.17 | 16.41 |
June | 0.696305E+10 | 17828.14 | 25-JUN-16:32 | 21.00 | 16.51 | 0.400506E+09 | 544.94 | 06-JUN-13:50 | 18.33 | 14.00 |
July | 0.768375E+10 | 18128.68 | 23-JUL-16:22 | 24.00 | 19.01 | 0.380686E+09 | 544.93 | 05-JUL-13:09 | 22.00 | 16.40 |
August | 0.806165E+10 | 18078.48 | 20-AUG-16:22 | 21.40 | 17.21 | 0.424646E+09 | 544.93 | 01-AUG-13:09 | 22.00 | 16.84 |
September | 0.627473E+10 | 13465.28 | 04-SEP-14:37 | 21.00 | 16.14 | 0.366004E+09 | 544.95 | 29-SEP-13:00 | 34.00 | 17.82 |
October | 0.589934E+10 | 18541.62 | 15-OCT-15:32 | 30.33 | 15.06 | 0.371602E+09 | 544.96 | 17-OCT-13:00 | 28.00 | 16.04 |
November | 0.423235E+10 | 6841.98 | 07-NOV-15:30 | 19.00 | 14.50 | 0.352525E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.06 |
December | 0.388626E+10 | 6759.73 | 19-DEC-15:30 | 21.50 | 8.90 | 0.333747E+09 | 544.98 | 20-DEC-14:00 | 19.00 | 12.36 |
Annual Sum or Average | 0.664444E+11 | 0.441527E+10 | ||||||||
Minimum of Months | 0.356265E+10 | 6261.17 | 15.00 | 8.90 | 0.315777E+09 | 544.93 | 18.33 | 12.36 | ||
Maximum of Months | 0.806165E+10 | 18541.62 | 30.33 | 19.01 | 0.424646E+09 | 545.03 | 34.00 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528547E+10 | 8002.94 | 02-JAN-06:08 | 11.00 | 8.37 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.480171E+10 | 6611.40 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.579399E+10 | 7318.51 | 20-MAR-05:15 | 10.67 | 10.47 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.643197E+10 | 7636.81 | 11-APR-05:13 | 12.00 | 12.00 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.579882E+10 | 7358.75 | 30-MAY-05:15 | 11.00 | 10.47 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.671835E+10 | 9457.11 | 12-JUN-05:13 | 13.47 | 12.38 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.733438E+10 | 8215.78 | 05-JUL-05:13 | 17.00 | 14.31 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.809994E+10 | 8153.81 | 28-AUG-05:13 | 14.00 | 14.00 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.636127E+10 | 9710.30 | 05-SEP-05:13 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.697850E+10 | 9383.43 | 16-OCT-05:01 | 18.67 | 9.53 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.623593E+10 | 8511.83 | 13-NOV-06:15 | 11.33 | 10.62 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.625038E+10 | 8588.94 | 26-DEC-06:04 | 7.00 | 1.07 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.760907E+11 | 0.00 | ||||||||
Minimum of Months | 0.480171E+10 | 6611.40 | 7.00 | 1.07 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.809994E+10 | 9710.30 | 18.67 | 14.76 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310912E+10 | 4348.96 | 21-JAN-06:13 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.283390E+10 | 4177.92 | 04-FEB-06:10 | 5.67 | 0.57 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.317062E+10 | 4864.18 | 23-MAR-05:13 | 10.33 | 9.38 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.387365E+10 | 5535.21 | 28-APR-05:13 | 14.00 | 12.23 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.406534E+10 | 5102.48 | 03-MAY-05:13 | 14.33 | 14.14 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.477251E+10 | 5583.74 | 30-JUN-05:13 | 17.00 | 16.37 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.521006E+10 | 5967.79 | 20-JUL-05:13 | 17.00 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.561112E+10 | 6829.68 | 25-AUG-05:01 | 16.92 | 16.92 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.484504E+10 | 5955.87 | 30-SEP-05:13 | 23.80 | 13.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.492243E+10 | 7339.09 | 16-OCT-05:01 | 18.67 | 9.53 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.364715E+10 | 5069.75 | 13-NOV-06:15 | 11.33 | 10.62 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.338637E+10 | 4455.70 | 11-DEC-06:10 | 7.17 | 6.55 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.494473E+11 | 0.00 | ||||||||
Minimum of Months | 0.283390E+10 | 4177.92 | 5.67 | 0.57 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.561112E+10 | 7339.09 | 23.80 | 17.00 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239050E+10 | 8429.28 | 18-JAN-14:30 | 23.80 | 14.80 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.234238E+10 | 8810.24 | 01-FEB-13:10 | 23.17 | 14.39 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.354948E+10 | 11688.74 | 23-MAR-14:20 | 22.67 | 17.31 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.629769E+10 | 15338.30 | 26-APR-13:40 | 26.33 | 16.85 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.645579E+10 | 14538.29 | 03-MAY-13:10 | 23.83 | 15.33 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.845385E+10 | 14614.69 | 21-JUN-13:30 | 23.50 | 16.84 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.100938E+11 | 16349.20 | 19-JUL-13:10 | 27.00 | 20.28 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.102638E+11 | 15684.17 | 14-AUG-13:10 | 25.83 | 20.41 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.699704E+10 | 17078.76 | 29-SEP-13:40 | 34.67 | 17.95 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.602585E+10 | 17419.54 | 16-OCT-13:10 | 33.75 | 16.61 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.282900E+10 | 8315.81 | 10-NOV-13:10 | 20.83 | 16.37 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.228858E+10 | 7803.03 | 19-DEC-13:10 | 25.50 | 11.27 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.679877E+11 | 0.00 | ||||||||
Minimum of Months | 0.228858E+10 | 7803.03 | 20.83 | 11.27 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.102638E+11 | 17419.54 | 34.67 | 20.41 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400105E+10 | 1955.46 | 30-JAN-16:40 | 14.00 | 11.38 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.829684E+10 | 3933.53 | 22-FEB-17:00 | 14.00 | 12.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.143478E+11 | 5876.85 | 19-MAR-17:27 | 15.50 | 13.70 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.188941E+11 | 7766.63 | 16-APR-17:13 | 16.00 | 11.53 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.424782E+10 | 1985.12 | 01-MAY-00:05 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.918038E+10 | 3824.37 | 25-JUN-17:47 | 19.33 | 15.99 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.145490E+11 | 5820.30 | 04-JUL-17:53 | 18.00 | 14.96 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.195729E+11 | 7790.45 | 06-AUG-17:55 | 21.00 | 18.97 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.423032E+10 | 2001.69 | 01-SEP-00:10 | 16.07 | 14.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.945206E+10 | 4032.00 | 15-OCT-16:38 | 28.00 | 14.53 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.139843E+11 | 5802.06 | 06-NOV-16:20 | 16.67 | 13.32 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.194727E+11 | 7765.26 | 25-DEC-16:04 | 20.17 | 9.82 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.140229E+12 | 0.00 | ||||||||
Minimum of Months | 0.400105E+10 | 1955.46 | 14.00 | 9.82 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.195729E+11 | 7790.45 | 28.00 | 18.97 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288070E+10 | 1771.88 | 30-JAN-16:50 | 14.00 | 11.29 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.707946E+10 | 3672.86 | 22-FEB-17:00 | 14.00 | 12.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.128633E+11 | 5458.94 | 10-MAR-17:00 | 20.00 | 12.29 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.175682E+11 | 7254.40 | 27-APR-17:30 | 16.50 | 14.04 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.352580E+10 | 1772.15 | 29-MAY-18:10 | 15.83 | 12.96 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.838033E+10 | 3570.69 | 25-JUN-17:52 | 19.00 | 15.88 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.136836E+11 | 5455.67 | 04-JUL-18:00 | 18.00 | 14.96 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.185102E+11 | 7279.09 | 31-AUG-17:00 | 20.00 | 17.41 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.360522E+10 | 1883.36 | 29-SEP-16:30 | 31.00 | 16.81 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.846080E+10 | 3735.81 | 17-OCT-16:40 | 24.00 | 18.31 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.125728E+11 | 5472.66 | 12-NOV-16:29 | 16.00 | 13.58 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.176615E+11 | 7228.14 | 18-DEC-16:20 | 20.33 | 7.94 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.126792E+12 | 0.00 | ||||||||
Minimum of Months | 0.288070E+10 | 1771.88 | 14.00 | 7.94 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.185102E+11 | 7279.09 | 31.00 | 18.31 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161470E+10 | 1724.15 | 26-JAN-16:10 | 15.67 | 12.54 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.603110E+10 | 3666.64 | 22-FEB-17:00 | 14.00 | 12.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.118872E+11 | 5493.65 | 10-MAR-17:00 | 20.00 | 12.29 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.170240E+11 | 7312.01 | 26-APR-17:10 | 21.50 | 16.58 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.298512E+10 | 1837.21 | 29-MAY-17:25 | 17.00 | 13.17 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.810046E+10 | 3696.01 | 25-JUN-17:35 | 19.67 | 16.11 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.135415E+11 | 5607.58 | 04-JUL-17:50 | 18.17 | 15.01 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.183276E+11 | 7405.75 | 20-AUG-17:26 | 19.90 | 16.76 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.322573E+10 | 1959.35 | 29-SEP-16:30 | 31.00 | 16.81 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.788612E+10 | 3846.79 | 15-OCT-16:40 | 28.00 | 14.53 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.115457E+11 | 5416.40 | 07-NOV-16:20 | 18.33 | 14.33 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.163686E+11 | 7215.28 | 19-DEC-16:20 | 20.33 | 7.91 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.118538E+12 | 0.00 | ||||||||
Minimum of Months | 0.161470E+10 | 1724.15 | 14.00 | 7.91 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.183276E+11 | 7405.75 | 31.00 | 16.81 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239245E+12 | 320665.02 | 03-JAN-00:25 | 6.50 | 5.07 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.435423E+12 | 379168.44 | 28-FEB-23:08 | 8.03 | 7.00 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.727544E+12 | 399727.13 | 01-MAR-00:22 | 7.50 | 6.49 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.942036E+12 | 365608.95 | 26-APR-16:00 | 22.00 | 16.40 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.238694E+12 | 103135.05 | 01-MAY-00:05 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.467042E+12 | 182052.85 | 28-JUN-16:00 | 22.00 | 18.08 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.728550E+12 | 274081.26 | 06-JUL-16:00 | 21.00 | 16.51 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.974774E+12 | 366044.12 | 15-AUG-16:00 | 23.00 | 19.54 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.232663E+12 | 103903.33 | 01-SEP-00:05 | 16.07 | 14.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.484773E+12 | 183195.36 | 17-OCT-16:00 | 28.00 | 17.86 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.706634E+12 | 381748.10 | 05-NOV-01:37 | 7.33 | 6.01 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.975222E+12 | 391061.10 | 30-DEC-04:03 | 8.17 | 2.30 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.715260E+13 | 0.00 | ||||||||
Minimum of Months | 0.232663E+12 | 103135.05 | 6.50 | 2.30 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.975222E+12 | 399727.13 | 28.00 | 19.54 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.640246E+09 | 114620.55 | 16-JAN-08:00 | 14.00 |
February | 0.560880E+09 | 122167.49 | 20-FEB-14:35 | 17.00 |
March | 0.260854E+09 | 114336.92 | 06-MAR-01:30 | 9.50 |
April | 0.409629E+09 | 124119.83 | 30-APR-18:30 | 19.00 |
May | 0.302299E+09 | 123469.73 | 29-MAY-09:55 | 21.00 |
June | 0.314279E+09 | 123851.96 | 18-JUN-23:00 | 17.00 |
July | 0.942118E+09 | 132050.56 | 30-JUL-16:55 | 21.00 |
August | 0.730837E+09 | 135580.34 | 06-AUG-17:00 | 23.00 |
September | 0.430340E+09 | 126754.46 | 10-SEP-17:40 | 19.00 |
October | 0.123885E+10 | 134252.97 | 01-OCT-14:04 | 23.83 |
November | 0.946080E+09 | 126534.53 | 19-NOV-15:18 | 20.43 |
December | 0.137625E+10 | 123592.49 | 17-DEC-15:20 | 19.67 |
Annual Sum or Average | 0.815266E+10 | |||
Minimum of Months | 0.260854E+09 | 114336.92 | 9.50 | |
Maximum of Months | 0.137625E+10 | 135580.34 | 23.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78920566.22 | 60564.85 | 02-JAN-05:01 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 2664902.02 | 44415.03 | 26-DEC-06:01 | 7.00 |
Annual Sum or Average | 81585468.24 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 78920566.22 | 60564.85 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7226178.98 | 9072.40 | 09-JAN-06:01 | 2.17 |
February | 246062.06 | 4101.03 | 07-FEB-06:01 | 11.83 |
March | 3367683.68 | 9033.64 | 30-MAR-05:01 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 119497.80 | 796.65 | 24-NOV-06:03 | 8.92 |
December | 203694.61 | 3394.91 | 13-DEC-06:01 | 6.17 |
Annual Sum or Average | 11163117.14 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 7226178.98 | 9072.40 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4396445.33 | 8097.89 | 09-JAN-06:01 | 2.17 |
February | 499026.65 | 7549.49 | 07-FEB-06:01 | 11.83 |
March | 4530908.93 | 8363.52 | 30-MAR-05:01 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 71270.75 | 475.14 | 24-NOV-06:03 | 8.92 |
December | 780300.44 | 7828.52 | 13-DEC-06:01 | 6.17 |
Annual Sum or Average | 10277952.12 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 4530908.93 | 8363.52 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2528730.13 | 10960.03 | 30-MAR-05:01 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 2528730.13 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 2528730.13 | 10960.03 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 754477.62 | 5435.73 | 09-JAN-06:01 | 2.17 |
February | 280197.64 | 4669.96 | 07-FEB-06:01 | 11.83 |
March | 850397.41 | 6946.05 | 30-MAR-05:01 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 1885072.66 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 850397.41 | 6946.05 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416574E+09 | 11939.23 | 02-JAN-04:03 | 10.17 |
February | 0.163280E+09 | 11180.93 | 06-FEB-05:02 | 8.17 |
March | 0.225899E+09 | 11414.63 | 30-MAR-04:01 | 4.48 |
April | 19633817.70 | 10558.96 | 01-APR-05:01 | 7.83 |
May | 3945409.72 | 10208.89 | 15-MAY-05:02 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 8212160.82 | 10325.42 | 30-OCT-05:03 | 10.83 |
November | 0.107537E+09 | 11192.64 | 24-NOV-05:02 | 8.17 |
December | 0.247683E+09 | 11173.31 | 13-DEC-05:02 | 6.83 |
Annual Sum or Average | 0.119276E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.416574E+09 | 11939.23 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198633E+09 | 11528.15 | 09-JAN-05:01 | 5.33 |
February | 81822695.73 | 10903.67 | 06-FEB-05:02 | 8.17 |
March | 0.112335E+09 | 11399.36 | 30-MAR-04:01 | 4.48 |
April | 9535916.63 | 10402.11 | 01-APR-05:01 | 7.83 |
May | 1680257.97 | 6216.69 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 4317753.80 | 9331.51 | 28-OCT-05:01 | 9.33 |
November | 47046383.24 | 10952.91 | 24-NOV-05:02 | 8.17 |
December | 0.112522E+09 | 11076.32 | 13-DEC-05:02 | 6.83 |
Annual Sum or Average | 0.567893E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.198633E+09 | 11528.15 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166275E+09 | 13695.42 | 02-JAN-05:01 | 11.00 |
February | 66925879.68 | 12481.12 | 25-FEB-06:01 | 12.00 |
March | 0.164116E+09 | 13424.05 | 30-MAR-04:01 | 4.48 |
April | 14582817.38 | 12413.94 | 01-APR-05:01 | 7.83 |
May | 5808216.52 | 12069.10 | 15-MAY-05:02 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 112051.37 | 1867.52 | 12-OCT-05:01 | 9.00 |
November | 22411692.40 | 12357.99 | 18-NOV-06:01 | 8.17 |
December | 64087125.56 | 13017.42 | 13-DEC-05:02 | 6.83 |
Annual Sum or Average | 0.504318E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.166275E+09 | 13695.42 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134736E+09 | 11377.34 | 09-JAN-05:01 | 5.33 |
February | 31092022.29 | 10147.29 | 04-FEB-06:01 | 5.67 |
March | 64075483.39 | 10859.35 | 30-MAR-04:01 | 4.48 |
April | 5523207.52 | 10173.58 | 01-APR-05:01 | 7.83 |
May | 719449.64 | 4972.10 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 31082.84 | 518.05 | 28-OCT-05:01 | 9.33 |
November | 17985720.35 | 10154.37 | 30-NOV-06:01 | 8.00 |
December | 52735371.79 | 10656.23 | 13-DEC-05:02 | 6.83 |
Annual Sum or Average | 0.306898E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.134736E+09 | 11377.34 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52531325.41 | 9508.53 | 02-JAN-03:31 | 10.33 |
February | 60803702.67 | 10487.34 | 13-FEB-04:02 | 13.83 |
March | 79695038.01 | 12007.62 | 06-MAR-04:01 | 10.92 |
April | 0.100407E+09 | 11141.29 | 18-APR-03:01 | 11.00 |
May | 53035524.01 | 8444.43 | 08-MAY-03:02 | 14.00 |
June | 43263742.45 | 9524.25 | 12-JUN-03:02 | 13.00 |
July | 84669222.72 | 9994.25 | 13-JUL-03:01 | 17.00 |
August | 93766037.66 | 10172.88 | 29-AUG-03:01 | 16.00 |
September | 45075618.31 | 9145.55 | 25-SEP-03:02 | 17.00 |
October | 62422021.50 | 10409.55 | 23-OCT-03:02 | 17.00 |
November | 82046836.91 | 10321.67 | 20-NOV-04:02 | 11.00 |
December | 87123158.66 | 12134.87 | 18-DEC-03:51 | 18.00 |
Annual Sum or Average | 0.844839E+09 | |||
Minimum of Months | 43263742.45 | 8444.43 | 10.33 | |
Maximum of Months | 0.100407E+09 | 12134.87 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36985408.77 | 8446.82 | 02-JAN-06:02 | 11.00 |
February | 33799881.54 | 8363.33 | 28-FEB-06:01 | 10.17 |
March | 37021908.31 | 8699.34 | 28-MAR-05:01 | 11.83 |
April | 40222966.15 | 6870.42 | 03-APR-05:03 | 10.83 |
May | 49930447.99 | 7690.34 | 08-MAY-04:01 | 14.00 |
June | 32922139.48 | 6420.11 | 26-JUN-04:01 | 17.83 |
July | 32655374.85 | 5905.84 | 12-JUL-04:03 | 17.00 |
August | 30523283.06 | 6232.05 | 28-AUG-03:50 | 14.00 |
September | 35169425.67 | 7061.19 | 25-SEP-03:02 | 17.00 |
October | 43433387.51 | 6711.07 | 02-OCT-03:02 | 19.00 |
November | 37536076.42 | 7584.41 | 13-NOV-04:03 | 11.83 |
December | 38981896.52 | 7978.62 | 14-DEC-06:01 | 7.17 |
Annual Sum or Average | 0.449182E+09 | |||
Minimum of Months | 30523283.06 | 5905.84 | 7.17 | |
Maximum of Months | 49930447.99 | 8699.34 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170643E+10 | 14722.13 | 26-JAN-06:01 | 12.00 |
February | 0.108912E+10 | 17989.69 | 17-FEB-06:01 | 11.98 |
March | 0.131859E+10 | 20342.11 | 23-MAR-05:01 | 10.67 |
April | 0.459489E+09 | 20707.99 | 20-APR-05:01 | 9.17 |
May | 0.341456E+09 | 21529.55 | 19-MAY-05:01 | 8.67 |
June | 0.134947E+09 | 19069.02 | 13-JUN-05:01 | 11.33 |
July | 75060040.33 | 17154.77 | 06-JUL-05:01 | 14.33 |
August | 78284541.17 | 16743.30 | 31-AUG-05:01 | 15.17 |
September | 0.152374E+09 | 19770.50 | 20-SEP-05:01 | 12.00 |
October | 0.424504E+09 | 20381.70 | 26-OCT-05:01 | 11.00 |
November | 0.950324E+09 | 16679.26 | 01-NOV-05:01 | 12.83 |
December | 0.145200E+10 | 18026.33 | 06-DEC-06:01 | 12.33 |
Annual Sum or Average | 0.818257E+10 | |||
Minimum of Months | 75060040.33 | 14722.13 | 8.67 | |
Maximum of Months | 0.170643E+10 | 21529.55 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124436E+09 | 532.10 | 09-JAN-01:12 | 5.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 964427.57 | 379.60 | 14-MAY-06:20 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.125401E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.33 | |
Maximum of Months | 0.124436E+09 | 532.10 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66819198.54 | 39918.27 | 03-JAN-01:19 | 5.00 |
February | 3960803.72 | 10524.82 | 28-FEB-23:10 | 8.03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 70780002.26 | |||
Minimum of Months | 0.00 | 0.00 | 5.00 | |
Maximum of Months | 66819198.54 | 39918.27 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.215029E+11 | 22401.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.195042E+11 | 22401.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.231659E+11 | 22401.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.207025E+11 | 22401.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.223344E+11 | 22401.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.222225E+11 | 22401.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.208144E+11 | 22401.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.231659E+11 | 22401.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.207025E+11 | 22401.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.215029E+11 | 22401.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.212480E+11 | 22401.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.208144E+11 | 22401.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.257680E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.195042E+11 | 22401.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.231659E+11 | 22401.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.193111E+11 | 20117.80 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.175161E+11 | 20117.80 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.208046E+11 | 20117.80 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.185923E+11 | 20117.80 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.200579E+11 | 20117.80 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.199573E+11 | 20117.80 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.186928E+11 | 20117.80 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.208046E+11 | 20117.80 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.185923E+11 | 20117.80 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.193111E+11 | 20117.80 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.190822E+11 | 20117.80 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.186928E+11 | 20117.80 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.231415E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.175161E+11 | 20117.80 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.208046E+11 | 20117.80 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242470E+10 | 2525.99 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.219932E+10 | 2525.99 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.261222E+10 | 2525.99 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.233445E+10 | 2525.99 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.251846E+10 | 2525.99 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.250584E+10 | 2525.99 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.234707E+10 | 2525.99 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.261222E+10 | 2525.99 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.233445E+10 | 2525.99 | 01-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.242470E+10 | 2525.99 | 02-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.239596E+10 | 2525.99 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.234707E+10 | 2525.99 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.290565E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.219932E+10 | 2525.99 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.261222E+10 | 2525.99 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242476E+10 | 2526.05 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.219937E+10 | 2526.05 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.261228E+10 | 2526.05 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.233450E+10 | 2526.05 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.251852E+10 | 2526.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.250590E+10 | 2526.05 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.234712E+10 | 2526.05 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.261228E+10 | 2526.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.233450E+10 | 2526.05 | 01-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.242476E+10 | 2526.05 | 02-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.239601E+10 | 2526.05 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.234712E+10 | 2526.05 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.290571E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.219937E+10 | 2526.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.261228E+10 | 2526.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156257E+10 | 1627.84 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.141733E+10 | 1627.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.168342E+10 | 1627.84 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.150441E+10 | 1627.84 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.162299E+10 | 1627.84 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.161486E+10 | 1627.84 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.151254E+10 | 1627.84 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.168342E+10 | 1627.84 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.150441E+10 | 1627.84 | 01-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.156257E+10 | 1627.84 | 02-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.154405E+10 | 1627.84 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.151254E+10 | 1627.84 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.187251E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.141733E+10 | 1627.84 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.168342E+10 | 1627.84 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.606290E+10 | 6316.16 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.549934E+10 | 6316.16 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.653179E+10 | 6316.16 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.583722E+10 | 6316.16 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.629734E+10 | 6316.16 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.626579E+10 | 6316.16 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.586877E+10 | 6316.16 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.653179E+10 | 6316.16 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.583722E+10 | 6316.16 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.606290E+10 | 6316.16 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.599102E+10 | 6316.16 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.586877E+10 | 6316.16 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.549934E+10 | 6316.16 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.653179E+10 | 6316.16 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.280081E+09 | 291.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.254047E+09 | 291.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.301742E+09 | 291.78 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.269655E+09 | 291.78 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.290911E+09 | 291.78 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.289453E+09 | 291.78 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.271113E+09 | 291.78 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.301742E+09 | 291.78 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.269655E+09 | 291.78 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.280081E+09 | 291.78 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.276760E+09 | 291.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.271113E+09 | 291.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.254047E+09 | 291.78 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.301742E+09 | 291.78 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.223344E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.222225E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.207025E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.215029E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.212480E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.208144E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.257680E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.195042E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.231659E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.200579E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.199573E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.185923E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.193111E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.190822E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.186928E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.231415E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.175161E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.208046E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 548277.80 | 0.550524E+09 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84637.18 | 0.642766E+09 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31206.46 | 0.680403E+09 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 633059.02 | 0.390365E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.81 | 0.461695E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52723.84 | 0.245374E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3815368.84 | 0.167401E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4009147.30 | 0.209525E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5988055.56 | 0.214993E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22644110.28 | 0.344950E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1512319.25 | 0.518611E+09 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 373921.19 | 0.568954E+09 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 39692935.53 | 0.499556E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.81 | 0.167401E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22644110.28 | 0.680403E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527138.72 | 0.357403E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58399.81 | 0.411276E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83589.50 | 0.434237E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401296.80 | 0.244293E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 0.298711E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35082.23 | 0.153754E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2740138.88 | 0.100692E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3378900.22 | 0.122937E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4041502.05 | 0.136548E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15166949.48 | 0.215610E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1247797.75 | 0.328952E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375214.40 | 0.356558E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 28056080.01 | 0.316097E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 0.100692E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15166949.48 | 0.434237E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 390381.68 | 0.561053E+09 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84639.35 | 0.646973E+09 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.17 | 0.672106E+09 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 507634.63 | 0.385960E+09 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 | 0.445525E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52728.43 | 0.234336E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4094420.64 | 0.159965E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3963945.47 | 0.205388E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5907515.04 | 0.223896E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19268301.64 | 0.360563E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172866.69 | 0.534367E+09 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243930.78 | 0.586539E+09 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 34686639.54 | 0.501667E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 | 0.159965E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19268301.64 | 0.672106E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 403063.23 | 0.380185E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56155.16 | 0.462261E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10581.36 | 0.493221E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309455.45 | 0.295687E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 | 0.329248E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34811.54 | 0.180212E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2521912.76 | 0.130810E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2504905.99 | 0.165354E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4027677.65 | 0.157362E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14421325.22 | 0.255202E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724227.69 | 0.381186E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226974.38 | 0.425581E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 25241161.40 | 0.365631E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 | 0.130810E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14421325.22 | 0.493221E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1908871.21 | 0.108500E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171883.86 | 0.125148E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 485528.23 | 0.135766E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2747729.72 | 0.796872E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962800E+09 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94864.86 | 0.517246E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8916956.11 | 0.365295E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9148221.41 | 0.455890E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13331572.00 | 0.446434E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52168436.61 | 0.688202E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6027476.35 | 0.102577E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2260428.61 | 0.109462E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 97261968.97 | 0.100473E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365295E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52168436.61 | 0.135766E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1796147.08 | 0.723080E+09 |
February | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162051.56 | 0.829902E+09 |
March | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283434.52 | 0.902272E+09 |
April | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 960994.24 | 0.544218E+09 |
May | 0.744847E+09 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646633E+09 |
June | 0.742030E+09 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98848.19 | 0.340447E+09 |
July | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5592552.21 | 0.249831E+09 |
August | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6091639.00 | 0.309241E+09 |
September | 0.688021E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9212968.50 | 0.298653E+09 |
October | 0.715730E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34084495.05 | 0.452151E+09 |
November | 0.708685E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3693441.40 | 0.678151E+09 |
December | 0.690839E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2126404.06 | 0.724297E+09 |
Annual Sum or Average | 0.858171E+10 | 0.187251E+11 | 0.259975E+11 | 64102975.81 | 0.669888E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249831E+09 |
Maximum of Months | 0.773965E+09 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34084495.05 | 0.902272E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 687437.75 | 0.122374E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165738.85 | 0.137455E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142394E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1605502.31 | 0.836192E+09 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958505E+09 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94867.81 | 0.502972E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9691104.12 | 0.357224E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8481945.35 | 0.469694E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12840283.18 | 0.500238E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41312240.22 | 0.789771E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311615.14 | 0.115905E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 440616.19 | 0.126236E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 75631350.92 | 0.108582E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357224E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41312240.22 | 0.142394E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1512952.29 | 0.740393E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265043.58 | 0.861536E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 437361.81 | 0.928549E+09 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2146328.84 | 0.579707E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.10 | 0.685334E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129540.09 | 0.366907E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7308138.23 | 0.276823E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7372226.41 | 0.341417E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9462242.93 | 0.328226E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35579675.25 | 0.485926E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4151728.94 | 0.709709E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2664923.64 | 0.757442E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 71031797.11 | 0.706197E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.10 | 0.276823E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35579675.25 | 0.928549E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4810900.43 | 0.114690E+10 |
February | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 344917.14 | 0.134062E+10 |
March | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013341.87 | 0.150716E+10 |
April | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4119282.14 | 0.918146E+09 |
May | 0.157338E+10 | 0.251846E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111818E+10 |
June | 0.156900E+10 | 0.250584E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91300.01 | 0.620175E+09 |
July | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11032341.93 | 0.451049E+09 |
August | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11511917.97 | 0.548820E+09 |
September | 0.145243E+10 | 0.233445E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16531077.08 | 0.524999E+09 |
October | 0.150991E+10 | 0.242470E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65667106.21 | 0.766618E+09 |
November | 0.149516E+10 | 0.239596E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10472581.08 | 0.111031E+10 |
December | 0.145680E+10 | 0.234707E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10101440.99 | 0.116260E+10 |
Annual Sum or Average | 0.181194E+11 | 0.290565E+11 | 0.403414E+11 | 0.135696E+09 | 0.112156E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.219932E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451049E+09 |
Maximum of Months | 0.163685E+10 | 0.261222E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65667106.21 | 0.150716E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3113085.54 | 0.781009E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212930.56 | 0.912572E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 458204.93 | 0.102227E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171218.44 | 0.643022E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766588E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66804.80 | 0.417005E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6182554.76 | 0.317114E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6456039.79 | 0.382861E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11192027.56 | 0.362751E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40572437.96 | 0.519616E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5496950.59 | 0.751872E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4929944.11 | 0.789345E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259975E+11 | 79852199.04 | 0.766603E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317114E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40572437.96 | 0.102227E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1227245.16 | 0.133764E+10 |
February | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189514.72 | 0.151488E+10 |
March | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 0.160118E+10 |
April | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1987256.27 | 0.970549E+09 |
May | 0.157341E+10 | 0.251852E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111419E+10 |
June | 0.156904E+10 | 0.250590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103172.48 | 0.602069E+09 |
July | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11853420.85 | 0.441453E+09 |
August | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10336135.76 | 0.566656E+09 |
September | 0.145246E+10 | 0.233450E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15845464.75 | 0.595498E+09 |
October | 0.150994E+10 | 0.242476E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51766623.88 | 0.902694E+09 |
November | 0.149520E+10 | 0.239601E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399260.66 | 0.129901E+10 |
December | 0.145684E+10 | 0.234712E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 678029.06 | 0.139415E+10 |
Annual Sum or Average | 0.181198E+11 | 0.290571E+11 | 0.403420E+11 | 94386135.76 | 0.123400E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.219937E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441453E+09 |
Maximum of Months | 0.163688E+10 | 0.261228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51766623.88 | 0.160118E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2923961.87 | 0.819248E+09 |
February | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 513892.04 | 0.964411E+09 |
March | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 711340.00 | 0.105857E+10 |
April | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2282552.09 | 0.681933E+09 |
May | 0.101394E+10 | 0.162299E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963.80 | 0.809675E+09 |
June | 0.101113E+10 | 0.161486E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 208339.11 | 0.440226E+09 |
July | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8980583.32 | 0.338934E+09 |
August | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9447061.14 | 0.412024E+09 |
September | 0.936002E+09 | 0.150441E+10 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11846691.78 | 0.392856E+09 |
October | 0.973041E+09 | 0.156257E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44805399.52 | 0.558826E+09 |
November | 0.963541E+09 | 0.154405E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6393031.47 | 0.799251E+09 |
December | 0.938820E+09 | 0.151254E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5369958.57 | 0.842635E+09 |
Annual Sum or Average | 0.116768E+11 | 0.187251E+11 | 0.259973E+11 | 93483774.72 | 0.811858E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.141733E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963.80 | 0.338934E+09 |
Maximum of Months | 0.105485E+10 | 0.168342E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44805399.52 | 0.105857E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.606290E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.549934E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.653179E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.583722E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.629734E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.626579E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.586877E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.583722E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.606290E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.599102E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.586877E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726548E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.549934E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.653179E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.280081E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.254047E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.301742E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.269655E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.290911E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.289453E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.271113E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.269655E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.280081E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.276760E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.271113E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335635E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.254047E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.301742E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458474.34 | 0.115045E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76536.28 | 0.133368E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139788E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615630.91 | 0.815921E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947243E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5194.55 | 0.506424E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4504552.17 | 0.362135E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4125139.40 | 0.458696E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10022075.91 | 0.454394E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37614017.83 | 0.728973E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358279.40 | 0.108507E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221571.75 | 0.119215E+10 |
Annual Sum or Average | 59001472.52 | 0.104330E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362135E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37614017.83 | 0.139788E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1306670.09 | 0.194845E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164196.35 | 0.225547E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 0.238351E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2013650.81 | 0.139170E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164351E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8813.55 | 0.875146E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8922270.95 | 0.630959E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7983928.28 | 0.800812E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18093062.15 | 0.785607E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71030680.93 | 0.124073E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4582659.09 | 0.184619E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754055.09 | 0.199887E+10 |
Annual Sum or Average | 0.114860E+09 | 0.178010E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630959E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71030680.93 | 0.238351E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3163516.99 | 0.183144E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21647.76 | 0.219001E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243759E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65487.77 | 0.157130E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186873E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107694E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2243545.86 | 0.845019E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1658400.33 | 0.959003E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17687450.95 | 0.931384E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67460018.47 | 0.125795E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5589637.92 | 0.179472E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1194555.10 | 0.186471E+10 |
Annual Sum or Average | 99084261.15 | 0.186288E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845019E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67460018.47 | 0.243759E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22401.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22401.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22401.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22401.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22401.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22401.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22401.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22401.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22401.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22401.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22401.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22401.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22401.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20117.80 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20117.80 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20117.80 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20117.80 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20117.80 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20117.80 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20117.80 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20117.80 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20117.80 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20117.80 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20117.80 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20117.80 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20117.80 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 14-JAN-15:00 | 1389.32 | 02-JAN-02:51 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 01-FEB-12:00 | 1217.27 | 12-FEB-19:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 11-MAR-14:00 | 1301.16 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.93 | 30-APR-11:10 | 809.37 | 17-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 03-MAY-12:00 | 710.34 | 20-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 29-JUN-11:00 | 526.18 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.88 | 23-JUL-10:42 | 398.39 | 13-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.90 | 06-AUG-13:10 | 355.77 | 21-AUG-23:42 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.74 | 29-SEP-14:00 | 439.84 | 04-SEP-18:00 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.11 | 15-OCT-13:00 | 864.28 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.40 | 19-NOV-12:50 | 1153.02 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | 05-DEC-10:00 | 1058.13 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 355.77 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 499.11 | 1389.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 15-JAN-14:30 | 913.65 | 02-JAN-02:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 01-FEB-12:00 | 769.85 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 11-MAR-14:00 | 819.37 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 30-APR-11:10 | 514.32 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 452.58 | 29-MAY-13:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 29-JUN-11:00 | 334.74 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 23-JUL-11:10 | 244.67 | 13-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 06-AUG-13:10 | 214.87 | 21-AUG-23:42 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.16 | 29-SEP-14:00 | 335.49 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.25 | 15-OCT-12:52 | 564.01 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.83 | 19-NOV-12:50 | 731.52 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 17-DEC-12:53 | 675.77 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 214.87 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 366.25 | 913.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 14-JAN-11:00 | 1240.49 | 02-JAN-02:51 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 01-FEB-12:00 | 1166.46 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 11-MAR-14:00 | 1268.33 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 30-APR-10:30 | 783.78 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 03-MAY-12:00 | 680.83 | 27-MAY-04:53 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 29-JUN-11:00 | 513.97 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.23 | 23-JUL-10:42 | 387.11 | 13-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.99 | 06-AUG-13:10 | 349.68 | 21-AUG-23:42 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.13 | 29-SEP-14:00 | 470.95 | 04-SEP-18:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.67 | 15-OCT-08:52 | 875.04 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 18-NOV-13:00 | 1149.32 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | 05-DEC-10:00 | 1058.99 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 349.68 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 411.67 | 1268.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 14-JAN-12:40 | 942.70 | 02-JAN-02:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 01-FEB-12:00 | 902.62 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 11-MAR-12:30 | 938.98 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 | 30-APR-11:10 | 623.20 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 593.65 | 20-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 29-JUN-11:00 | 409.19 | 03-JUN-17:08 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.13 | 23-JUL-11:10 | 393.27 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 06-AUG-13:10 | 295.86 | 27-AUG-18:20 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.16 | 29-SEP-14:00 | 378.51 | 03-SEP-16:50 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.02 | 15-OCT-12:12 | 651.80 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.75 | 19-NOV-12:50 | 870.15 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 05-DEC-10:00 | 783.51 | 24-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 295.86 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 357.02 | 942.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.70 | 15-JAN-10:00 | 2274.98 | 02-JAN-02:51 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.89 | 01-FEB-12:00 | 2306.97 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.77 | 11-MAR-14:00 | 2577.71 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.68 | 30-APR-11:10 | 1577.00 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1513.92 | 20-MAY-17:53 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 | 29-JUN-11:00 | 1068.57 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.44 | 23-JUL-10:52 | 829.31 | 02-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.34 | 06-AUG-13:00 | 771.04 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.90 | 29-SEP-14:00 | 870.70 | 04-SEP-17:51 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.09 | 15-OCT-12:50 | 1653.80 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.92 | 19-NOV-12:50 | 2173.26 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.18 | 25-DEC-11:53 | 2109.04 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.04 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.09 | 2577.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 15-JAN-14:50 | 1555.51 | 02-JAN-02:51 |
February | 1239.33 | 01-FEB-08:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 | 01-FEB-12:00 | 1479.68 | 25-FEB-03:00 |
March | 1239.33 | 01-MAR-08:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 11-MAR-14:00 | 1669.79 | 28-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.03 | 30-APR-11:10 | 1043.92 | 17-APR-03:00 |
May | 1239.33 | 01-MAY-07:10 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 982.52 | 27-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 | 29-JUN-11:00 | 716.41 | 04-JUN-13:52 |
July | 1239.33 | 03-JUL-07:10 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 | 31-JUL-13:00 | 588.91 | 04-JUL-13:55 |
August | 1239.33 | 01-AUG-07:10 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.61 | 06-AUG-13:00 | 503.24 | 21-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.26 | 29-SEP-14:00 | 684.01 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 785.51 | 15-OCT-13:10 | 1124.46 | 30-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.43 | 19-NOV-13:10 | 1426.06 | 23-NOV-04:00 |
December | 1239.33 | 01-DEC-08:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.51 | 17-DEC-13:10 | 1392.46 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.24 | |||||
Maximum of Months | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 785.51 | 1669.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 | 14-JAN-11:00 | 2400.20 | 02-JAN-02:51 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 | 01-FEB-12:00 | 2321.93 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2572.28 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.91 | 30-APR-09:52 | 1589.08 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1476.42 | 20-MAY-17:53 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 | 29-JUN-11:00 | 1062.16 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.29 | 23-JUL-10:52 | 819.08 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.62 | 06-AUG-13:00 | 780.77 | 21-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.21 | 29-SEP-14:00 | 1055.28 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 899.27 | 15-OCT-08:52 | 1855.80 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 18-NOV-13:00 | 2319.73 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 05-DEC-10:00 | 2220.38 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.77 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 899.27 | 2572.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.73 | 14-JAN-13:00 | 1566.90 | 02-JAN-02:51 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 01-FEB-12:00 | 1532.72 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.27 | 11-MAR-13:00 | 1702.37 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.79 | 30-APR-10:50 | 1346.22 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 03-MAY-12:00 | 1343.39 | 20-MAY-17:53 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 | 29-JUN-11:00 | 870.11 | 04-JUN-17:18 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.84 | 23-JUL-10:50 | 846.72 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.78 | 06-AUG-13:00 | 650.00 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.27 | 29-SEP-14:00 | 810.59 | 03-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 854.14 | 15-OCT-12:30 | 1175.92 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.32 | 19-NOV-12:30 | 1492.39 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 187.69 | 25-DEC-11:53 | 1440.42 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 650.00 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 854.14 | 1702.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2525.99 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 351.63 | 15-JAN-10:00 | 2534.15 | 27-JAN-04:55 |
February | 2010.79 | 01-FEB-10:09 | 2525.99 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.71 | 01-FEB-12:00 | 2494.09 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 2525.99 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.18 | 11-MAR-14:00 | 3098.41 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2525.99 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.60 | 30-APR-09:52 | 1808.91 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2525.99 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1790.43 | 20-MAY-17:53 |
June | 2010.79 | 01-JUN-09:09 | 2525.99 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 29-JUN-11:00 | 1267.85 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 2525.99 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.89 | 23-JUL-11:10 | 1074.37 | 02-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 2525.99 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.65 | 06-AUG-12:40 | 898.40 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 2525.99 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.69 | 29-SEP-14:00 | 1084.17 | 04-SEP-17:51 |
October | 2010.79 | 02-OCT-09:09 | 2525.99 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432.02 | 15-OCT-09:00 | 1767.94 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2525.99 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 694.39 | 19-NOV-13:00 | 2254.09 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2525.99 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 526.20 | 25-DEC-12:00 | 2355.78 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.40 | |||||
Maximum of Months | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1432.02 | 3098.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.48 | 15-JAN-10:00 | 1684.30 | 27-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.95 | 01-FEB-12:00 | 1629.00 | 04-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 | 11-MAR-14:00 | 2059.58 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.01 | 26-APR-13:00 | 1180.85 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1150.66 | 29-MAY-13:00 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.96 | 29-JUN-11:00 | 940.01 | 04-JUN-13:52 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.20 | 31-JUL-13:00 | 795.28 | 04-JUL-14:06 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 | 17-AUG-14:00 | 616.51 | 27-AUG-18:20 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.79 | 29-SEP-14:00 | 778.89 | 03-SEP-17:45 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 924.32 | 15-OCT-13:00 | 1214.97 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.46 | 19-NOV-13:00 | 1496.53 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 249.77 | 17-DEC-13:00 | 1568.20 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.51 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 924.32 | 2059.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2526.05 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.35 | 15-JAN-10:00 | 2710.77 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 2526.05 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 | 01-FEB-12:00 | 2670.26 | 20-FEB-14:55 |
March | 2010.83 | 01-MAR-10:09 | 2526.05 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 11-MAR-10:10 | 3103.73 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 2526.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.62 | 30-APR-09:52 | 1811.21 | 16-APR-18:00 |
May | 2010.83 | 01-MAY-09:09 | 2526.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1749.20 | 20-MAY-17:53 |
June | 2010.83 | 01-JUN-09:09 | 2526.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 29-JUN-11:00 | 1240.01 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 2526.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.34 | 23-JUL-11:10 | 1061.79 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 2526.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.62 | 06-AUG-12:40 | 928.56 | 27-AUG-18:20 |
September | 2010.83 | 01-SEP-09:09 | 2526.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.00 | 29-SEP-14:00 | 1324.89 | 03-SEP-13:55 |
October | 2010.83 | 02-OCT-09:09 | 2526.05 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.97 | 15-OCT-09:00 | 2031.68 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2526.05 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 | 18-NOV-13:00 | 2452.68 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2526.05 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.71 | 05-DEC-10:00 | 2511.49 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.56 | |||||
Maximum of Months | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.97 | 3103.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1627.84 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.93 | 15-JAN-10:00 | 1729.13 | 27-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 1627.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.32 | 01-FEB-12:00 | 1697.03 | 08-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 1627.84 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.54 | 11-MAR-13:00 | 2074.49 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1627.84 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.21 | 30-APR-09:52 | 1647.15 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 1627.84 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 | 03-MAY-12:00 | 1613.57 | 20-MAY-17:53 |
June | 1295.83 | 01-JUN-09:09 | 1627.84 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 | 25-JUN-12:20 | 1095.22 | 04-JUN-16:53 |
July | 1295.83 | 03-JUL-09:09 | 1627.84 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.22 | 23-JUL-11:10 | 1072.21 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 1627.84 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.77 | 06-AUG-12:40 | 820.27 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 1627.84 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.79 | 29-SEP-14:00 | 1061.32 | 03-SEP-17:00 |
October | 1295.83 | 02-OCT-09:09 | 1627.84 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.78 | 15-OCT-09:00 | 1305.34 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1627.84 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.35 | 19-NOV-13:00 | 1593.63 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1627.84 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 258.90 | 25-DEC-12:00 | 1638.59 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 | 820.27 | |||||
Maximum of Months | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.78 | 2074.49 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 6316.16 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6316.16 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 6316.16 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 6316.16 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 6316.16 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 6316.16 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 6316.16 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 6316.16 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 6316.16 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 6316.16 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 6316.16 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 6316.16 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 6316.16 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 6316.16 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 291.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 291.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 291.78 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 291.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 291.78 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 291.78 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 291.78 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 291.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 291.78 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 291.78 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 291.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 291.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 14-JAN-15:00 | 2938.62 | 02-JAN-02:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.45 | 01-FEB-12:00 | 2528.85 | 12-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2678.46 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.51 | 30-APR-10:53 | 1646.23 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1496.88 | 27-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 29-JUN-11:00 | 1048.63 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.88 | 31-JUL-13:00 | 773.77 | 13-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.76 | 06-AUG-12:52 | 753.52 | 21-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.66 | 29-SEP-13:50 | 892.04 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.90 | 15-OCT-13:00 | 1768.83 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.89 | 19-NOV-13:00 | 2439.84 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 05-DEC-10:00 | 2183.41 | 23-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.90 | 2938.62 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 | 15-JAN-10:00 | 4392.16 | 02-JAN-02:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.34 | 01-FEB-12:00 | 4289.83 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 11-MAR-13:40 | 4592.34 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.47 | 30-APR-11:10 | 2767.45 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 2629.40 | 27-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 29-JUN-11:00 | 1818.75 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.35 | 23-JUL-10:52 | 1342.28 | 13-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.47 | 06-AUG-12:52 | 1301.97 | 21-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.18 | 29-SEP-13:50 | 1508.07 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.60 | 15-OCT-12:52 | 2975.58 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.48 | 19-NOV-12:52 | 4153.27 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 | 05-DEC-10:00 | 3775.31 | 23-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.60 | 4592.34 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.87 | 15-JAN-10:00 | 3909.12 | 27-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 | 01-FEB-12:00 | 4062.61 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4875.61 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.68 | 30-APR-09:52 | 3003.79 | 16-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 3222.17 | 07-MAY-15:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 2615.02 | 04-JUN-13:52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 | 31-JUL-13:00 | 2152.30 | 04-JUL-14:06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.77 | 17-AUG-14:00 | 1559.35 | 20-AUG-13:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.54 | 29-SEP-13:30 | 2113.70 | 03-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.01 | 15-OCT-08:52 | 2837.69 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.50 | 19-NOV-13:00 | 3519.10 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.59 | 04-DEC-10:00 | 3723.69 | 23-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.01 | 4875.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 120722.22 | 01-JAN-15:02 | 4488.06 | 6222.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 123244.26 | 20-FEB-09:10 | 2692.84 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 119605.55 | 20-MAR-00:02 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 122703.85 | 16-APR-22:30 | 0.00 | 4038.86 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 116525.80 | 15-MAY-01:41 | 0.00 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115502.85 | 05-JUN-00:22 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114011.74 | 04-JUL-22:57 | 0.00 | 5385.15 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111144.66 | 27-AUG-23:10 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 110260.96 | 20-SEP-03:01 | 0.00 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 118369.45 | 09-OCT-05:42 | 4488.06 | 6222.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 119757.97 | 05-NOV-23:12 | 0.00 | 6731.44 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 123298.94 | 25-DEC-08:50 | 4488.06 | 6222.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 110260.96 | 0.00 | 3733.52 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 123298.94 | 4488.06 | 13462.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81331.56 | 17-JAN-04:02 | 0.00 | 6045.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80434.20 | 01-FEB-04:01 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80973.58 | 21-MAR-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82753.99 | 14-APR-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80602.61 | 25-MAY-03:01 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88055.29 | 27-JUN-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87396.56 | 13-JUL-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87337.59 | 01-AUG-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87345.35 | 06-SEP-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95868.73 | 04-OCT-03:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85493.42 | 28-NOV-04:02 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89845.32 | 18-DEC-03:51 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 80434.20 | 0.00 | 6045.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95868.73 | 0.00 | 12090.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71856.72 | 18-JAN-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68617.67 | 01-FEB-05:03 | 0.00 | 9672.49 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66577.79 | 16-MAR-05:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72057.22 | 27-APR-04:02 | 0.00 | 12090.61 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72223.73 | 08-MAY-04:02 | 0.00 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79983.08 | 26-JUN-04:02 | 0.00 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78805.51 | 20-JUL-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79915.79 | 07-AUG-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81637.82 | 30-SEP-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82013.67 | 04-OCT-03:01 | 0.00 | 12090.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 69154.15 | 13-NOV-04:03 | 0.00 | 4836.24 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70744.63 | 19-DEC-06:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 66577.79 | 0.00 | 4836.24 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82013.67 | 16122.38 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 62245.04 | 25-JAN-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56797.90 | 16-FEB-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60437.74 | 24-MAR-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70655.07 | 27-APR-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68332.61 | 03-MAY-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73768.10 | 26-JUN-04:01 | 0.00 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76815.99 | 19-JUL-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74875.86 | 30-AUG-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79838.33 | 30-SEP-05:02 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79802.19 | 02-OCT-03:02 | 0.00 | 7254.36 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62295.75 | 10-NOV-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56447.49 | 06-DEC-06:01 | 16122.38 | 22353.12 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 56447.49 | 0.00 | 7254.36 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79838.33 | 16122.38 | 24181.22 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6697.64 | 17-JAN-13:40 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
February | 5924.01 | 01-FEB-12:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 0.00 |
March | 6630.64 | 13-MAR-13:50 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.25 |
April | 8895.69 | 27-APR-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
May | 7309.91 | 04-MAY-13:40 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 |
June | 10031.54 | 26-JUN-05:03 | 809.73 | 1122.66 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
July | 10090.99 | 26-JUL-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10280.60 | 07-AUG-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
September | 10515.22 | 30-SEP-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 10673.24 | 04-OCT-03:01 | 0.00 | 1518.10 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6506.49 | 28-NOV-14:10 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 0.00 |
December | 6952.04 | 05-DEC-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5924.01 | 0.00 | 1122.66 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10673.24 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 115.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6192.40 | 20-JAN-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7240.89 | 21-FEB-08:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.61 |
March | 8276.98 | 23-MAR-08:30 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12480.46 | 30-APR-08:62 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 |
May | 10477.26 | 29-MAY-07:40 | 652.28 | 904.36 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.53 |
June | 9577.70 | 25-JUN-06:32 | 391.37 | 542.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.49 |
July | 12465.73 | 23-JUL-08:13 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 |
August | 9565.80 | 20-AUG-08:24 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 |
September | 12818.65 | 10-SEP-08:32 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.79 |
October | 16240.90 | 15-OCT-08:42 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 190.93 | 0.00 |
November | 6698.52 | 20-NOV-08:35 | 2478.65 | 3255.69 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6562.01 | 05-DEC-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6192.40 | 260.91 | 361.74 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16240.90 | 2478.65 | 3255.69 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 190.93 | 230.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14934.35 | 29-JAN-12:13 | 303.66 | 421.01 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.65 |
February | 13886.01 | 21-FEB-13:00 | 1058.33 | 2526.05 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 |
March | 13083.91 | 01-MAR-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 |
April | 10420.40 | 26-APR-13:00 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 0.00 |
May | 8093.04 | 04-MAY-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 |
June | 9763.91 | 26-JUN-05:03 | 809.75 | 1122.69 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
July | 10449.42 | 24-JUL-05:03 | 809.75 | 1122.69 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11491.13 | 30-AUG-12:40 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
September | 14466.08 | 29-SEP-13:20 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 150.60 | 0.00 |
October | 19116.53 | 15-OCT-12:42 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 260.84 | 0.00 |
November | 18066.21 | 19-NOV-10:43 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 |
December | 18052.32 | 25-DEC-11:53 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8093.04 | 303.66 | 421.01 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19116.53 | 2010.83 | 2526.05 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 260.84 | 664.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12075.80 | 21-JAN-06:01 | 1304.55 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12249.30 | 24-FEB-06:01 | 1304.55 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
March | 19646.38 | 19-MAR-15:52 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.09 |
April | 20850.29 | 30-APR-17:02 | 0.00 | 489.16 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.11 |
May | 16709.00 | 14-MAY-15:32 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.56 |
June | 16619.18 | 21-JUN-03:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18951.20 | 09-JUL-15:52 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20750.84 | 06-AUG-17:42 | 0.00 | 489.16 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.81 |
September | 18829.18 | 10-SEP-15:42 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.13 |
October | 20139.10 | 15-OCT-14:02 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 | 0.00 |
November | 15674.69 | 10-NOV-04:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 |
December | 15820.04 | 19-DEC-04:01 | 0.00 | 978.32 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.98 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12075.80 | 0.00 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20850.29 | 1304.55 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 | 517.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4968.90 | 18-JAN-14:20 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
February | 4436.38 | 03-FEB-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.77 |
March | 5057.74 | 23-MAR-14:50 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 |
April | 6276.72 | 26-APR-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 0.00 |
May | 6583.47 | 04-MAY-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 |
June | 8774.17 | 30-JUN-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8674.41 | 20-JUL-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.07 |
August | 8343.74 | 07-AUG-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 |
September | 10762.33 | 30-SEP-05:02 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
October | 9456.25 | 04-OCT-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 |
November | 4491.76 | 10-NOV-14:30 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.48 |
December | 4982.96 | 05-DEC-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4436.38 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10762.33 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 | 176.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5026.96 | 20-JAN-09:30 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 |
February | 5088.72 | 21-FEB-09:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
March | 7532.25 | 23-MAR-09:00 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9242.25 | 30-APR-08:53 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.04 |
May | 7769.43 | 18-MAY-08:40 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 |
June | 8297.35 | 30-JUN-08:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.51 |
July | 9752.54 | 02-JUL-08:53 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.41 |
August | 9532.00 | 06-AUG-07:24 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.10 |
September | 10990.36 | 30-SEP-05:01 | 1304.55 | 1808.72 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
October | 8829.25 | 16-OCT-08:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 80.09 | 0.00 |
November | 4880.49 | 13-NOV-09:10 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.26 |
December | 5015.98 | 05-DEC-09:20 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4880.49 | 260.91 | 361.74 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10990.36 | 1304.55 | 1808.72 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 80.09 | 296.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15960.30 | 22-JAN-13:53 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.90 |
February | 14759.34 | 20-FEB-12:41 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.37 |
March | 12228.93 | 01-MAR-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.02 |
April | 9462.17 | 26-APR-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 80.03 | 0.00 |
May | 7459.06 | 04-MAY-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 |
June | 10033.20 | 30-JUN-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10522.04 | 31-JUL-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 |
August | 10696.58 | 30-AUG-12:50 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
September | 13933.05 | 29-SEP-13:20 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 320.48 | 0.00 |
October | 17643.68 | 15-OCT-13:42 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 376.43 | 0.00 |
November | 16813.75 | 19-NOV-11:02 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.49 |
December | 17154.93 | 25-DEC-13:02 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.83 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7459.06 | 404.87 | 561.34 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17643.68 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 376.43 | 1634.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6588.15 | 18-JAN-15:00 | 1295.83 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
February | 7482.22 | 22-FEB-16:20 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.50 |
March | 9494.09 | 23-MAR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 |
April | 10385.97 | 26-APR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 |
May | 12273.68 | 29-MAY-15:47 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.22 |
June | 12633.65 | 26-JUN-04:01 | 0.00 | 1956.64 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14943.87 | 09-JUL-16:22 | 391.37 | 542.61 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.55 |
August | 16534.25 | 13-AUG-16:31 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.16 |
September | 11647.80 | 30-SEP-05:01 | 1304.55 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
October | 12451.91 | 01-OCT-14:42 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.37 |
November | 7262.74 | 07-NOV-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.88 |
December | 7109.11 | 18-DEC-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6588.15 | 0.00 | 452.18 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16534.25 | 1304.55 | 1956.64 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4400.89 | 18-JAN-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
February | 4064.75 | 01-FEB-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.93 |
March | 5219.32 | 23-MAR-15:20 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.74 |
April | 6936.55 | 26-APR-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.44 | 0.00 |
May | 7274.03 | 04-MAY-13:50 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
June | 7257.59 | 30-JUN-14:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 |
July | 9215.19 | 19-JUL-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7833.45 | 18-AUG-15:00 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 91.09 | 0.00 |
September | 10329.67 | 30-SEP-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 |
October | 10848.27 | 05-OCT-05:01 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4191.99 | 10-NOV-14:40 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.37 |
December | 4489.17 | 05-DEC-15:00 | 2010.79 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4064.75 | 1923.11 | 2525.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10848.27 | 2024.33 | 2806.66 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 91.09 | 232.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3781.39 | 20-JAN-11:00 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 |
February | 3802.72 | 01-FEB-10:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
March | 6495.94 | 23-MAR-09:30 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 |
April | 7940.05 | 26-APR-09:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 |
May | 7101.39 | 04-MAY-09:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
June | 8178.77 | 19-JUN-08:50 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
July | 10769.80 | 23-JUL-09:23 | 260.91 | 361.74 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.85 |
August | 8895.33 | 14-AUG-09:10 | 1295.83 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 0.00 |
September | 10063.29 | 30-SEP-05:01 | 1304.55 | 1808.72 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
October | 15715.43 | 15-OCT-08:52 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 656.05 | 0.00 |
November | 4064.59 | 19-NOV-10:22 | 326.14 | 452.18 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 92.03 | 0.00 |
December | 3834.81 | 05-DEC-15:10 | 1239.33 | 1627.84 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3781.39 | 260.91 | 361.74 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15715.43 | 1304.55 | 1808.72 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 656.05 | 170.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15805.84 | 22-JAN-13:23 | 404.87 | 561.34 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1100.36 |
February | 15146.97 | 20-FEB-12:41 | 1012.19 | 1403.36 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.07 |
March | 12258.30 | 23-MAR-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 |
April | 10033.83 | 26-APR-13:10 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 95.39 | 0.00 |
May | 8137.21 | 04-MAY-13:30 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
June | 7388.41 | 30-JUN-13:50 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 |
July | 10457.69 | 19-JUL-05:01 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11267.74 | 30-AUG-13:00 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
September | 15164.07 | 29-SEP-13:20 | 2010.83 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 402.88 | 0.00 |
October | 20015.69 | 15-OCT-12:52 | 607.31 | 842.02 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 634.32 | 0.00 |
November | 17875.41 | 19-NOV-12:52 | 506.09 | 701.68 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 |
December | 14704.13 | 19-DEC-13:20 | 1923.15 | 2526.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7388.41 | 404.87 | 561.34 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20015.69 | 2024.37 | 2806.72 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 634.32 | 2022.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6261.17 | 18-JAN-15:10 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 |
February | 7164.41 | 22-FEB-16:20 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.20 |
March | 9622.78 | 23-MAR-16:00 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 |
April | 11582.24 | 27-APR-05:01 | 1304.55 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
May | 11949.44 | 29-MAY-15:47 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.51 |
June | 17828.14 | 25-JUN-16:32 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.79 |
July | 18128.68 | 23-JUL-16:22 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.00 |
August | 18078.48 | 20-AUG-16:22 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.17 |
September | 13465.28 | 04-SEP-14:37 | 652.28 | 904.36 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.86 |
October | 18541.62 | 15-OCT-15:32 | 326.14 | 452.18 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 | 0.00 |
November | 6841.98 | 07-NOV-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.91 |
December | 6759.73 | 19-DEC-15:30 | 1239.33 | 1627.84 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6261.17 | 326.14 | 452.18 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18541.62 | 1304.55 | 1808.72 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 | 1341.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8002.94 | 02-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.86 |
February | 6611.40 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.33 |
March | 7318.51 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.82 |
April | 7636.81 | 11-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7358.75 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.55 |
June | 9457.11 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 |
July | 8215.78 | 05-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8153.81 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.82 |
September | 9710.30 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9383.43 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.86 |
November | 8511.83 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.68 |
December | 8588.94 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6611.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9710.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4348.96 | 21-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4177.92 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.44 |
March | 4864.18 | 23-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.62 |
April | 5535.21 | 28-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.27 |
May | 5102.48 | 03-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 |
June | 5583.74 | 30-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5967.79 | 20-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.60 |
August | 6829.68 | 25-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5955.87 | 30-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
October | 7339.09 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.90 |
November | 5069.75 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.68 |
December | 4455.70 | 11-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4177.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7339.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8429.28 | 18-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.69 |
February | 8810.24 | 01-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.76 |
March | 11688.74 | 23-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.72 |
April | 15338.30 | 26-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 |
May | 14538.29 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 |
June | 14614.69 | 21-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.03 |
July | 16349.20 | 19-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 | 0.00 |
August | 15684.17 | 14-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 |
September | 17078.76 | 29-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.49 | 0.00 |
October | 17419.54 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.25 | 0.00 |
November | 8315.81 | 10-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.44 |
December | 7803.03 | 19-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7803.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17419.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.49 | 336.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1955.46 | 30-JAN-16:40 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3933.53 | 22-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5876.85 | 19-MAR-17:27 | 0.00 | 52.61 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7766.63 | 16-APR-17:13 | 0.00 | 52.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1985.12 | 01-MAY-00:05 | 0.00 | 35.07 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3824.37 | 25-JUN-17:47 | 0.00 | 70.14 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5820.30 | 04-JUL-17:53 | 0.00 | 70.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7790.45 | 06-AUG-17:55 | 0.00 | 70.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2001.69 | 01-SEP-00:10 | 0.00 | 70.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4032.00 | 15-OCT-16:38 | 0.00 | 81.05 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5802.06 | 06-NOV-16:20 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7765.26 | 25-DEC-16:04 | 0.00 | 162.10 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1955.46 | 0.00 | 35.07 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7790.45 | 0.00 | 291.78 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1771.88 | 30-JAN-16:50 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3672.86 | 22-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5458.94 | 10-MAR-17:00 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7254.40 | 27-APR-17:30 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1772.15 | 29-MAY-18:10 | 0.00 | 52.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3570.69 | 25-JUN-17:52 | 0.00 | 87.68 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5455.67 | 04-JUL-18:00 | 0.00 | 70.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7279.09 | 31-AUG-17:00 | 0.00 | 162.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1883.36 | 29-SEP-16:30 | 0.00 | 162.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3735.81 | 17-OCT-16:40 | 0.00 | 162.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5472.66 | 12-NOV-16:29 | 0.00 | 162.10 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7228.14 | 18-DEC-16:20 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1771.88 | 0.00 | 52.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7279.09 | 0.00 | 291.78 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1724.15 | 26-JAN-16:10 | 0.00 | 291.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3666.64 | 22-FEB-17:00 | 0.00 | 291.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5493.65 | 10-MAR-17:00 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7312.01 | 26-APR-17:10 | 0.00 | 97.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1837.21 | 29-MAY-17:25 | 0.00 | 35.07 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3696.01 | 25-JUN-17:35 | 0.00 | 35.07 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5607.58 | 04-JUL-17:50 | 0.00 | 35.07 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7405.75 | 20-AUG-17:26 | 0.00 | 87.68 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1959.35 | 29-SEP-16:30 | 0.00 | 162.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3846.79 | 15-OCT-16:40 | 0.00 | 81.05 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5416.40 | 07-NOV-16:20 | 0.00 | 291.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7215.28 | 19-DEC-16:20 | 0.00 | 291.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1724.15 | 0.00 | 35.07 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7405.75 | 0.00 | 291.78 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 320665.02 | 03-JAN-00:25 | 0.00 | 3795.95 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 379168.44 | 28-FEB-23:08 | 0.00 | 3508.98 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 399727.13 | 01-MAR-00:22 | 0.00 | 3795.95 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365608.95 | 26-APR-16:00 | 0.00 | 6316.16 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103135.05 | 01-MAY-00:05 | 0.00 | 759.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182052.85 | 28-JUN-16:00 | 0.00 | 6316.16 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274081.26 | 06-JUL-16:00 | 0.00 | 6316.16 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366044.12 | 15-AUG-16:00 | 0.00 | 6316.16 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 103903.33 | 01-SEP-00:05 | 0.00 | 1518.38 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183195.36 | 17-OCT-16:00 | 0.00 | 6316.16 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 381748.10 | 05-NOV-01:37 | 0.00 | 3795.95 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 391061.10 | 30-DEC-04:03 | 0.00 | 3795.95 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 103135.05 | 0.00 | 759.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 399727.13 | 0.00 | 6316.16 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.185177E+13 | 1325842.29 | 13-JAN-14:09 | 0.128410E+12 | 524616.87 | 09-JAN-07:30 |
February | 0.202262E+13 | 1439489.44 | 01-FEB-11:00 | 0.101249E+12 | 410961.42 | 20-FEB-03:30 |
March | 0.267078E+13 | 1672455.22 | 23-MAR-15:09 | 0.134195E+12 | 584788.28 | 30-MAR-06:10 |
April | 0.298408E+13 | 1823257.64 | 11-APR-15:39 | 0.676085E+11 | 566226.17 | 01-APR-06:10 |
May | 0.190730E+13 | 1356893.99 | 04-MAY-15:20 | 0.603939E+11 | 316626.80 | 27-MAY-05:10 |
June | 0.236387E+13 | 1569772.40 | 29-JUN-15:00 | 0.464693E+11 | 368973.83 | 05-JUN-00:20 |
July | 0.289188E+13 | 1827809.93 | 31-JUL-15:50 | 0.450845E+11 | 156626.74 | 30-JUL-21:49 |
August | 0.340272E+13 | 1973943.13 | 18-AUG-15:50 | 0.476195E+11 | 156673.38 | 20-AUG-22:40 |
September | 0.197227E+13 | 1474850.87 | 29-SEP-15:09 | 0.439701E+11 | 164069.69 | 24-SEP-16:40 |
October | 0.244919E+13 | 1608444.79 | 16-OCT-10:00 | 0.521749E+11 | 267162.25 | 30-OCT-06:10 |
November | 0.260804E+13 | 1592076.86 | 28-NOV-14:09 | 0.791184E+11 | 384782.24 | 11-NOV-22:30 |
December | 0.304349E+13 | 1786037.97 | 05-DEC-09:50 | 0.113443E+12 | 617524.83 | 22-DEC-07:10 |
Annual Sum or Average | 0.301680E+14 | 0.919736E+12 | ||||
Minimum of Months | 0.185177E+13 | 1325842.29 | 0.439701E+11 | 156626.74 | ||
Maximum of Months | 0.340272E+13 | 1973943.13 | 0.134195E+12 | 617524.83 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.358355E+12 | 0.871901E+11 | 0.811612E+12 | 0.173544E+12 | 0.183447E+12 | 0.367173E+11 | 0.00 | 0.140197E+12 | 0.595375E+11 | 0.117252E+10 | 0.00 | 0.00 | 0.00 |
February | 0.325045E+12 | 0.745269E+11 | 0.102011E+13 | 0.156760E+12 | 0.165219E+12 | 0.294316E+11 | 0.00 | 0.175290E+12 | 0.754610E+11 | 0.773415E+09 | 0.00 | 0.00 | 0.00 |
March | 0.386070E+12 | 0.763842E+11 | 0.146224E+13 | 0.173828E+12 | 0.186671E+12 | 0.309131E+11 | 0.00 | 0.255841E+12 | 0.983976E+11 | 0.434719E+09 | 0.00 | 0.00 | 0.00 |
April | 0.345016E+12 | 0.679083E+11 | 0.170426E+13 | 0.167919E+12 | 0.180226E+12 | 0.435932E+11 | 0.00 | 0.348958E+12 | 0.126093E+12 | 99970356.50 | 0.00 | 0.00 | 0.00 |
May | 0.372213E+12 | 0.648354E+11 | 0.820095E+12 | 0.173686E+12 | 0.184203E+12 | 0.463289E+11 | 0.00 | 0.161908E+12 | 0.840162E+11 | 14662815.11 | 0.00 | 0.00 | 0.00 |
June | 0.370347E+12 | 0.601078E+11 | 0.110647E+13 | 0.168186E+12 | 0.183482E+12 | 0.595045E+11 | 0.00 | 0.281116E+12 | 0.134658E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346881E+12 | 0.632820E+11 | 0.143833E+13 | 0.173418E+12 | 0.188652E+12 | 0.775537E+11 | 0.00 | 0.440974E+12 | 0.162793E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.386070E+12 | 0.677732E+11 | 0.177907E+13 | 0.173828E+12 | 0.196146E+12 | 0.838916E+11 | 0.00 | 0.547788E+12 | 0.168152E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345016E+12 | 0.713527E+11 | 0.784429E+12 | 0.167919E+12 | 0.182514E+12 | 0.608471E+11 | 0.00 | 0.229163E+12 | 0.130994E+12 | 33559054.53 | 0.00 | 0.00 | 0.00 |
October | 0.358355E+12 | 0.799636E+11 | 0.112844E+13 | 0.173544E+12 | 0.189688E+12 | 0.627656E+11 | 0.00 | 0.317414E+12 | 0.138211E+12 | 0.810460E+09 | 0.00 | 0.00 | 0.00 |
November | 0.354107E+12 | 0.828339E+11 | 0.140306E+13 | 0.168027E+12 | 0.182338E+12 | 0.388084E+11 | 0.00 | 0.270162E+12 | 0.107485E+12 | 0.121376E+10 | 0.00 | 0.00 | 0.00 |
December | 0.346881E+12 | 0.886759E+11 | 0.175516E+13 | 0.173418E+12 | 0.185525E+12 | 0.375491E+11 | 0.00 | 0.341164E+12 | 0.112966E+12 | 0.215039E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429436E+13 | 0.884834E+12 | 0.152133E+14 | 0.204408E+13 | 0.220811E+13 | 0.607904E+12 | 0.00 | 0.350997E+13 | 0.139876E+13 | 0.670347E+10 | |||
Minimum of Months | 0.325045E+12 | 0.601078E+11 | 0.784429E+12 | 0.156760E+12 | 0.165219E+12 | 0.294316E+11 | 0.00 | 0.140197E+12 | 0.595375E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386070E+12 | 0.886759E+11 | 0.177907E+13 | 0.173828E+12 | 0.196146E+12 | 0.838916E+11 | 0.00 | 0.547788E+12 | 0.168152E+12 | 0.215039E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.803133E+11 | 0.00 | 0.480968E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.576664E+11 | 0.00 | 0.435831E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.840401E+11 | 0.00 | 0.501550E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224201E+11 | 0.00 | 0.451884E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.133536E+11 | 0.00 | 0.470403E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115473E+10 | 0.00 | 0.453145E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.156587E+10 | 0.00 | 0.435187E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.111022E+10 | 0.00 | 0.465093E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.769785E+09 | 0.00 | 0.432004E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.649724E+10 | 0.00 | 0.456776E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.333338E+11 | 0.00 | 0.457845E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.668921E+11 | 0.00 | 0.465505E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.369117E+12 | 0.550619E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.769785E+09 | 0.00 | 0.432004E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.840401E+11 | 0.00 | 0.501550E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 373325.05 | 02-JAN-08:09 | 56280.71 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 129663.18 | 02-JAN-08:20 | 125030.28 | 26-JAN-15:30 | 55210.75 | 13-JAN-14:09 | 0.00 | 01-JAN-00:10 |
February | 373325.05 | 01-FEB-08:09 | 56280.71 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 129663.18 | 01-FEB-08:20 | 125813.17 | 22-FEB-16:30 | 53201.65 | 21-FEB-12:50 | 0.00 | 01-FEB-00:10 |
March | 373325.05 | 01-MAR-08:09 | 56280.71 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 129663.18 | 01-MAR-08:20 | 124687.44 | 24-MAR-14:00 | 53583.99 | 23-MAR-13:09 | 0.00 | 01-MAR-00:10 |
April | 373325.05 | 03-APR-07:10 | 56280.71 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 129663.18 | 03-APR-07:19 | 128587.24 | 28-APR-15:30 | 54085.50 | 13-APR-09:20 | 0.00 | 01-APR-00:10 |
May | 373325.05 | 01-MAY-07:10 | 56280.71 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 129663.18 | 01-MAY-07:19 | 118403.27 | 19-MAY-15:00 | 54665.87 | 18-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 373325.05 | 01-JUN-07:10 | 56280.71 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 129663.18 | 01-JUN-07:19 | 124423.88 | 26-JUN-05:10 | 54410.63 | 29-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 373325.05 | 03-JUL-07:10 | 56280.71 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 129663.18 | 03-JUL-07:19 | 134241.76 | 24-JUL-05:10 | 55452.43 | 31-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 373325.05 | 01-AUG-07:10 | 56280.71 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 129663.18 | 01-AUG-07:19 | 125980.11 | 18-AUG-15:20 | 55434.94 | 18-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 373325.05 | 01-SEP-07:10 | 56280.71 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 129663.18 | 01-SEP-07:19 | 144209.39 | 29-SEP-15:30 | 56873.89 | 29-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 373325.05 | 02-OCT-07:10 | 56280.71 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 129663.18 | 02-OCT-07:19 | 144957.87 | 16-OCT-14:50 | 55790.27 | 17-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 373325.05 | 01-NOV-07:10 | 56280.71 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 129663.18 | 01-NOV-07:19 | 129746.12 | 13-NOV-14:39 | 51691.37 | 06-NOV-10:50 | 0.00 | 01-NOV-00:10 |
December | 373325.05 | 01-DEC-08:09 | 56280.71 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 129663.18 | 01-DEC-08:20 | 125244.09 | 21-DEC-15:50 | 52005.72 | 05-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 373325.05 | 56280.71 | 439129.89 | 129663.18 | 118403.27 | 51691.37 | 0.00 | |||||||
Maximum of Months | 373325.05 | 56280.71 | 794004.08 | 129663.18 | 144957.87 | 56873.89 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 226367.27 | 13-JAN-14:09 | 82332.21 | 13-JAN-14:09 | 21868.30 | 03-JAN-00:00 | 0.00 | 0.00 | 0.00 |
February | 244264.01 | 01-FEB-11:00 | 63063.28 | 01-FEB-11:00 | 32206.61 | 28-FEB-22:19 | 0.00 | 0.00 | 0.00 |
March | 280367.06 | 22-MAR-12:30 | 82332.21 | 22-MAR-12:09 | 18958.00 | 30-MAR-21:19 | 0.00 | 0.00 | 0.00 |
April | 329078.99 | 26-APR-10:00 | 82332.21 | 04-APR-12:09 | 4268.52 | 01-APR-11:00 | 0.00 | 0.00 | 0.00 |
May | 214841.05 | 04-MAY-13:00 | 82332.21 | 02-MAY-14:20 | 1147.73 | 24-MAY-09:50 | 0.00 | 0.00 | 0.00 |
June | 310922.53 | 29-JUN-12:00 | 82332.21 | 13-JUN-13:00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 423552.21 | 31-JUL-15:50 | 82332.21 | 01-JUL-13:39 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 450325.57 | 18-AUG-15:50 | 82332.21 | 01-AUG-09:39 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 327354.35 | 29-SEP-12:30 | 82332.21 | 01-SEP-12:50 | 1657.49 | 29-SEP-19:00 | 0.00 | 0.00 | 0.00 |
October | 361744.47 | 16-OCT-10:00 | 82332.21 | 01-OCT-11:39 | 4865.24 | 25-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 276912.27 | 28-NOV-13:39 | 65790.24 | 10-NOV-12:39 | 10000.00 | 05-NOV-00:30 | 0.00 | 0.00 | 0.00 |
December | 318155.11 | 05-DEC-14:00 | 60056.67 | 05-DEC-14:00 | 7460.79 | 19-DEC-11:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 214841.05 | 60056.67 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 450325.57 | 82332.21 | 32206.61 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1325842.29 | 13-JAN-14:09 | 373325.05 | 439129.89 | 0.00 | 44107.79 | 105369.33 | 55210.75 | 0.00 | 226367.27 | 82332.21 |
February | 1439489.44 | 01-FEB-11:00 | 373325.05 | 557421.28 | 0.00 | 44107.79 | 105219.54 | 51260.13 | 0.00 | 244264.01 | 63063.28 |
March | 1672455.22 | 23-MAR-15:09 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 117812.53 | 53220.29 | 0.00 | 277055.87 | 82332.21 |
April | 1823257.64 | 11-APR-15:39 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 115078.43 | 53597.68 | 0.00 | 311923.61 | 82332.21 |
May | 1356893.99 | 04-MAY-15:20 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 112686.98 | 52820.83 | 0.00 | 203602.45 | 82332.21 |
June | 1569772.40 | 29-JUN-15:00 | 373325.05 | 557421.28 | 0.00 | 92996.58 | 119383.58 | 54288.48 | 0.00 | 290025.22 | 82332.21 |
July | 1827809.93 | 31-JUL-15:50 | 373325.05 | 675712.68 | 0.00 | 92996.58 | 124438.77 | 55452.43 | 0.00 | 423552.21 | 82332.21 |
August | 1973943.13 | 18-AUG-15:50 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 125524.70 | 55434.94 | 0.00 | 450325.57 | 82332.21 |
September | 1474850.87 | 29-SEP-15:09 | 373325.05 | 439129.89 | 0.00 | 92996.58 | 143716.61 | 55786.70 | 0.00 | 287062.09 | 82332.21 |
October | 1608444.79 | 16-OCT-10:00 | 373325.05 | 557421.28 | 0.00 | 44107.79 | 134352.22 | 53431.57 | 0.00 | 361744.47 | 82332.21 |
November | 1592076.86 | 28-NOV-14:09 | 373325.05 | 675712.68 | 0.00 | 44107.79 | 110992.88 | 51365.65 | 0.00 | 275960.02 | 56162.90 |
December | 1786037.97 | 05-DEC-09:50 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 101279.22 | 50957.47 | 0.00 | 308687.82 | 58702.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1325842.29 | 373325.05 | 439129.89 | 0.00 | 44107.79 | 101279.22 | 50957.47 | 0.00 | 203602.45 | 56162.90 | |
Maximum of Months | 1973943.13 | 373325.05 | 794004.08 | 0.00 | 92996.58 | 143716.61 | 55786.70 | 0.00 | 450325.57 | 82332.21 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 516470.29 | 09-JAN-07:30 | 0.00 | 72190.22 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 402814.84 | 20-FEB-03:30 | 0.00 | 72191.44 | 02-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 576641.70 | 30-MAR-06:10 | 0.00 | 71885.38 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 558079.59 | 01-APR-06:10 | 0.00 | 70847.76 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 308480.22 | 27-MAY-05:10 | 0.00 | 69655.03 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 360827.25 | 05-JUN-00:20 | 0.00 | 68160.71 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 148480.16 | 30-JUL-21:49 | 0.00 | 66851.12 | 06-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 148526.80 | 20-AUG-22:40 | 0.00 | 66679.78 | 28-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 155923.11 | 24-SEP-16:40 | 0.00 | 67636.63 | 27-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 259015.67 | 30-OCT-06:10 | 0.00 | 69253.92 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 376635.66 | 11-NOV-22:30 | 0.00 | 70672.94 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 609378.25 | 22-DEC-07:10 | 0.00 | 71687.03 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 148480.16 | 0.00 | 66679.78 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 609378.25 | 0.00 | 72191.44 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.34 | 1.17 | 28.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.43 | 1.00 | 27.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.96 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.14 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.18 | 0.67 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.08 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 26.50 | 0.50 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.31 | 0.67 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.19 | 0.83 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.68 | 2.17 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.68 | 1.67 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.72 | 2.17 | 27.73 |
Annual Sum or Average | 0.00 | 0.00 | 154.83 | 26.38 | 10.83 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.96 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.72 | 2.17 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.60 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.62 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 25.60 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.62 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 27.43 | 1.33 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.47 | 2.17 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.46 | 1.17 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 25.56 | 14.17 | 25.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.91 | 4.67 | 26.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 25.31 | 24.33 | 25.31 |
Annual Sum or Average | 0.00 | 0.00 | 47.17 | 25.73 | 47.17 | 25.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.47 | 24.33 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.80 | 0.67 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.69 | 4.83 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.37 | 1.83 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.66 | 1.83 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.65 | 5.83 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.30 | 5.67 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 1.33 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.71 | 1.83 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.50 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.45 | 1.83 | 27.45 |
Annual Sum or Average | 0.00 | 0.00 | 51.50 | 27.49 | 26.33 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.80 | 5.83 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.26 | 0.50 | 27.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 27.34 | 1.00 | 27.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 24.87 | 24.83 | 24.87 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.82 | 4.00 | 24.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.50 | 21.33 | 25.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.18 | 15.83 | 25.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 25.06 | 35.83 | 25.06 |
Annual Sum or Average | 0.00 | 0.00 | 102.17 | 25.12 | 102.17 | 25.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 27.29 | 35.83 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.53 | 2.00 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.44 | 1.33 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.84 | 0.50 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 27.50 | 4.50 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.84 | 2.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.11 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.14 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.71 | 2.17 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 25.57 | 11.17 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.10 | 0.00 | 14.17 | 25.56 | 14.17 | 25.56 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.23 | 0.00 | 0.00 | 11.17 | 27.63 | 11.17 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.33 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 2.67 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.54 | 1.50 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.94 | 0.67 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.16 | 0.00 | 6.17 | 27.57 | 5.50 | 27.59 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.39 | 0.00 | 0.00 | 3.00 | 27.94 | 2.67 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.22 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.25 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.88 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.76 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.17 | 27.82 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.25 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.50 | 24.04 | 270.17 | 25.06 | 0.33 | 26.86 |
February | 26.17 | 24.03 | 250.83 | 24.94 | 0.17 | 26.80 |
March | 0.00 | 0.00 | 324.00 | 24.69 | 0.00 | 0.00 |
April | 2.67 | 24.05 | 407.17 | 24.63 | 0.00 | 0.00 |
May | 0.33 | 24.00 | 388.33 | 24.64 | 0.00 | 0.00 |
June | 3.83 | 24.00 | 480.67 | 24.47 | 3.83 | 24.00 |
July | 106.67 | 25.17 | 497.00 | 24.61 | 106.67 | 25.17 |
August | 117.17 | 25.03 | 514.00 | 24.47 | 117.17 | 25.03 |
September | 37.00 | 25.45 | 454.50 | 24.58 | 37.00 | 25.45 |
October | 33.83 | 24.63 | 342.83 | 24.89 | 32.50 | 24.65 |
November | 18.50 | 24.15 | 293.50 | 25.01 | 0.83 | 26.78 |
December | 27.67 | 24.09 | 213.00 | 25.38 | 0.67 | 26.72 |
Annual Sum or Average | 398.33 | 24.82 | 4436.00 | 24.72 | 299.17 | 25.09 |
Minimum of Months | 0.00 | 0.00 | 213.00 | 24.47 | 0.00 | 0.00 |
Maximum of Months | 117.17 | 25.45 | 514.00 | 25.38 | 117.17 | 26.86 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.67 | 24.18 | 267.83 | 24.74 | 2.83 | 27.04 |
February | 17.17 | 23.92 | 271.33 | 24.57 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 346.67 | 24.48 | 0.00 | 0.00 |
April | 5.17 | 23.76 | 441.33 | 24.33 | 0.00 | 0.00 |
May | 2.33 | 23.59 | 403.17 | 24.39 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 475.83 | 24.32 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 492.00 | 24.28 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 513.67 | 24.22 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 434.83 | 24.37 | 0.00 | 0.00 |
October | 2.00 | 23.90 | 336.33 | 24.50 | 0.00 | 0.00 |
November | 13.67 | 24.31 | 296.50 | 24.65 | 1.33 | 27.02 |
December | 20.33 | 24.02 | 228.50 | 24.80 | 0.00 | 0.00 |
Annual Sum or Average | 89.33 | 24.07 | 4508.00 | 24.43 | 4.17 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 228.50 | 24.22 | 0.00 | 0.00 |
Maximum of Months | 28.67 | 24.31 | 513.67 | 24.80 | 2.83 | 27.04 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.67 | 23.79 | 160.50 | 24.47 | 13.33 | 24.59 |
February | 82.83 | 23.64 | 152.67 | 24.38 | 0.00 | 0.00 |
March | 57.50 | 23.60 | 221.83 | 24.36 | 0.00 | 0.00 |
April | 35.17 | 23.28 | 309.33 | 24.31 | 0.00 | 0.00 |
May | 24.17 | 23.28 | 323.83 | 24.36 | 0.00 | 0.00 |
June | 17.17 | 23.21 | 426.83 | 24.25 | 0.00 | 0.00 |
July | 13.83 | 23.26 | 450.17 | 24.25 | 0.00 | 0.00 |
August | 9.67 | 23.25 | 477.33 | 24.20 | 0.00 | 0.00 |
September | 20.00 | 23.29 | 404.17 | 24.29 | 0.00 | 0.00 |
October | 49.67 | 23.57 | 271.83 | 24.40 | 0.00 | 0.00 |
November | 103.00 | 23.81 | 205.83 | 24.48 | 1.83 | 26.45 |
December | 166.33 | 23.73 | 108.00 | 24.58 | 0.00 | 0.00 |
Annual Sum or Average | 698.00 | 23.64 | 3512.33 | 24.32 | 15.17 | 24.82 |
Minimum of Months | 9.67 | 23.21 | 108.00 | 24.20 | 0.00 | 0.00 |
Maximum of Months | 166.33 | 23.81 | 477.33 | 24.58 | 13.33 | 26.45 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 358.17 | 22.82 | 56.50 | 23.21 | 12.17 | 20.31 |
February | 292.00 | 22.93 | 53.67 | 24.00 | 0.00 | 0.00 |
March | 271.67 | 23.08 | 114.17 | 24.06 | 0.00 | 0.00 |
April | 150.50 | 23.10 | 219.00 | 24.16 | 0.00 | 0.00 |
May | 130.33 | 23.14 | 235.50 | 24.20 | 0.00 | 0.00 |
June | 41.33 | 23.24 | 342.83 | 24.22 | 0.00 | 0.00 |
July | 6.50 | 23.30 | 380.67 | 24.28 | 0.00 | 0.00 |
August | 10.33 | 23.32 | 385.50 | 24.21 | 0.00 | 0.00 |
September | 79.67 | 23.28 | 310.00 | 24.23 | 0.00 | 0.00 |
October | 167.67 | 23.25 | 187.33 | 24.20 | 0.00 | 0.00 |
November | 274.50 | 23.09 | 98.83 | 24.15 | 0.17 | 23.37 |
December | 377.83 | 22.93 | 24.83 | 23.79 | 1.67 | 21.00 |
Annual Sum or Average | 2160.50 | 23.02 | 2408.83 | 24.18 | 14.00 | 20.43 |
Minimum of Months | 6.50 | 22.82 | 24.83 | 23.21 | 0.00 | 0.00 |
Maximum of Months | 377.83 | 23.32 | 385.50 | 24.28 | 12.17 | 23.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 282.33 | 23.31 | 57.67 | 24.43 | 0.00 | 0.00 |
February | 229.83 | 23.39 | 68.17 | 24.05 | 0.00 | 0.00 |
March | 176.33 | 23.37 | 155.83 | 24.14 | 0.00 | 0.00 |
April | 59.50 | 23.53 | 254.83 | 24.16 | 0.00 | 0.00 |
May | 91.67 | 23.45 | 240.50 | 24.24 | 0.00 | 0.00 |
June | 1.33 | 23.39 | 402.67 | 24.23 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 470.83 | 24.22 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 475.83 | 24.14 | 0.00 | 0.00 |
September | 23.67 | 23.40 | 318.50 | 24.26 | 0.00 | 0.00 |
October | 82.33 | 23.55 | 241.33 | 24.29 | 0.00 | 0.00 |
November | 196.00 | 23.60 | 123.00 | 24.28 | 0.00 | 0.00 |
December | 262.67 | 23.61 | 38.67 | 24.24 | 0.00 | 0.00 |
Annual Sum or Average | 1405.67 | 23.46 | 2847.83 | 24.21 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 38.67 | 24.05 | 0.00 | 0.00 |
Maximum of Months | 282.33 | 23.61 | 475.83 | 24.43 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.00 | 22.84 | 76.00 | 24.64 | 0.00 | 0.00 |
February | 263.17 | 22.78 | 72.50 | 24.28 | 0.00 | 0.00 |
March | 255.83 | 22.77 | 153.83 | 24.22 | 0.50 | 26.41 |
April | 175.83 | 22.83 | 228.33 | 24.19 | 0.83 | 26.00 |
May | 174.00 | 22.89 | 230.67 | 24.39 | 0.50 | 25.93 |
June | 126.50 | 22.89 | 299.00 | 24.26 | 2.17 | 26.09 |
July | 91.00 | 22.99 | 338.67 | 24.24 | 4.00 | 25.97 |
August | 114.83 | 22.92 | 327.67 | 24.12 | 2.50 | 26.10 |
September | 147.17 | 22.83 | 278.00 | 24.26 | 2.83 | 26.24 |
October | 182.67 | 22.89 | 200.17 | 24.31 | 1.50 | 26.21 |
November | 251.33 | 22.96 | 107.83 | 24.29 | 0.00 | 0.00 |
December | 323.50 | 22.93 | 29.17 | 24.68 | 0.00 | 0.00 |
Annual Sum or Average | 2395.83 | 22.87 | 2341.83 | 24.26 | 14.83 | 26.10 |
Minimum of Months | 91.00 | 22.77 | 29.17 | 24.12 | 0.00 | 0.00 |
Maximum of Months | 323.50 | 22.99 | 338.67 | 24.68 | 4.00 | 26.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 155.50 | 23.29 | 216.50 | 24.54 | 4.17 | 26.78 |
February | 176.00 | 23.15 | 171.50 | 24.42 | 2.33 | 26.49 |
March | 187.33 | 23.12 | 198.00 | 24.22 | 1.00 | 26.42 |
April | 104.50 | 23.22 | 265.83 | 24.19 | 0.00 | 0.00 |
May | 174.00 | 23.14 | 196.50 | 24.17 | 0.00 | 0.00 |
June | 60.33 | 23.23 | 307.83 | 24.19 | 0.00 | 0.00 |
July | 6.00 | 23.23 | 378.33 | 24.18 | 0.00 | 0.00 |
August | 3.33 | 23.27 | 418.33 | 24.14 | 0.00 | 0.00 |
September | 43.00 | 23.51 | 359.67 | 24.34 | 4.17 | 26.47 |
October | 77.50 | 24.02 | 326.17 | 24.54 | 15.67 | 26.78 |
November | 105.67 | 23.65 | 271.17 | 24.54 | 6.33 | 26.75 |
December | 124.83 | 23.62 | 234.00 | 24.67 | 8.17 | 26.75 |
Annual Sum or Average | 1218.00 | 23.34 | 3343.83 | 24.33 | 41.83 | 26.72 |
Minimum of Months | 3.33 | 23.12 | 171.50 | 24.14 | 0.00 | 0.00 |
Maximum of Months | 187.33 | 24.02 | 418.33 | 24.67 | 15.67 | 26.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 225.33 | 22.96 | 148.17 | 24.56 | 0.00 | 0.00 |
February | 93.50 | 23.19 | 224.33 | 24.49 | 1.17 | 25.88 |
March | 35.33 | 23.69 | 370.67 | 24.44 | 4.67 | 26.39 |
April | 24.67 | 26.13 | 473.67 | 24.52 | 20.67 | 26.67 |
May | 74.50 | 23.33 | 347.83 | 24.46 | 7.67 | 26.17 |
June | 16.83 | 26.39 | 478.67 | 24.38 | 16.00 | 26.57 |
July | 37.50 | 26.49 | 497.00 | 24.50 | 37.50 | 26.49 |
August | 29.50 | 26.53 | 514.00 | 24.41 | 29.50 | 26.53 |
September | 22.50 | 24.18 | 375.33 | 24.42 | 8.33 | 26.19 |
October | 41.00 | 24.04 | 363.50 | 24.50 | 9.83 | 26.30 |
November | 31.00 | 24.16 | 319.17 | 24.59 | 6.00 | 26.38 |
December | 24.50 | 24.28 | 308.00 | 24.71 | 5.33 | 26.26 |
Annual Sum or Average | 656.17 | 23.86 | 4420.33 | 24.49 | 146.67 | 26.46 |
Minimum of Months | 16.83 | 22.96 | 148.17 | 24.38 | 0.00 | 0.00 |
Maximum of Months | 225.33 | 26.53 | 514.00 | 24.71 | 37.50 | 26.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.50 | 22.54 | 22.33 | 23.35 | 4.00 | 20.41 |
February | 367.17 | 22.53 | 19.33 | 23.97 | 0.17 | 21.17 |
March | 395.33 | 22.67 | 52.33 | 23.99 | 0.17 | 20.96 |
April | 273.83 | 22.95 | 110.33 | 24.02 | 0.00 | 0.00 |
May | 238.50 | 23.10 | 145.83 | 24.05 | 0.00 | 0.00 |
June | 97.67 | 23.29 | 268.33 | 24.09 | 0.00 | 0.00 |
July | 34.50 | 23.30 | 341.50 | 24.17 | 0.00 | 0.00 |
August | 78.50 | 23.23 | 313.17 | 24.09 | 0.00 | 0.00 |
September | 150.17 | 23.17 | 219.67 | 24.09 | 0.00 | 0.00 |
October | 240.67 | 23.10 | 125.50 | 24.16 | 0.00 | 0.00 |
November | 357.17 | 22.76 | 32.33 | 24.00 | 1.33 | 21.01 |
December | 450.83 | 22.61 | 10.00 | 23.25 | 2.17 | 20.58 |
Annual Sum or Average | 3105.83 | 22.79 | 1660.67 | 24.08 | 7.83 | 20.59 |
Minimum of Months | 34.50 | 22.53 | 10.00 | 23.25 | 0.00 | 0.00 |
Maximum of Months | 450.83 | 23.30 | 341.50 | 24.17 | 4.00 | 21.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.67 | 22.31 | 10.33 | 23.66 | 1.83 | 20.33 |
February | 332.17 | 22.17 | 13.67 | 24.55 | 0.33 | 20.82 |
March | 338.33 | 22.22 | 44.67 | 24.47 | 0.33 | 20.94 |
April | 218.00 | 22.49 | 137.00 | 24.46 | 0.67 | 26.02 |
May | 232.50 | 22.57 | 133.33 | 24.52 | 0.00 | 0.00 |
June | 178.33 | 22.68 | 173.50 | 24.36 | 1.83 | 26.14 |
July | 121.00 | 22.97 | 247.50 | 24.47 | 9.67 | 26.46 |
August | 143.50 | 22.89 | 232.83 | 24.32 | 8.83 | 26.56 |
September | 192.83 | 22.57 | 156.17 | 24.32 | 1.17 | 26.16 |
October | 247.67 | 22.56 | 87.67 | 24.51 | 0.50 | 26.46 |
November | 344.83 | 22.42 | 19.33 | 24.29 | 0.83 | 21.02 |
December | 402.67 | 22.30 | 2.00 | 21.73 | 1.50 | 20.63 |
Annual Sum or Average | 3137.50 | 22.44 | 1258.00 | 24.40 | 27.50 | 25.42 |
Minimum of Months | 121.00 | 22.17 | 2.00 | 21.73 | 0.00 | 0.00 |
Maximum of Months | 402.67 | 22.97 | 247.50 | 24.55 | 9.67 | 26.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 201.17 | 23.07 | 201.33 | 24.60 | 5.67 | 26.83 |
February | 231.33 | 22.71 | 133.00 | 24.49 | 1.50 | 26.41 |
March | 283.67 | 22.68 | 138.83 | 24.24 | 0.83 | 25.45 |
April | 210.00 | 22.88 | 177.67 | 24.20 | 0.00 | 0.00 |
May | 258.83 | 22.92 | 142.67 | 24.08 | 0.00 | 0.00 |
June | 176.83 | 23.08 | 222.50 | 24.08 | 0.00 | 0.00 |
July | 103.17 | 23.13 | 288.17 | 24.17 | 0.00 | 0.00 |
August | 84.67 | 23.11 | 337.33 | 24.14 | 0.00 | 0.00 |
September | 87.83 | 23.39 | 317.83 | 24.32 | 6.83 | 26.81 |
October | 132.33 | 23.68 | 282.50 | 24.62 | 19.17 | 26.85 |
November | 171.33 | 23.25 | 224.00 | 24.61 | 7.17 | 26.88 |
December | 198.50 | 23.17 | 203.33 | 24.79 | 6.17 | 26.78 |
Annual Sum or Average | 2139.67 | 23.02 | 2669.17 | 24.36 | 47.33 | 26.80 |
Minimum of Months | 84.67 | 22.68 | 133.00 | 24.08 | 0.00 | 0.00 |
Maximum of Months | 283.67 | 23.68 | 337.33 | 24.79 | 19.17 | 26.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.33 | 22.25 | 37.83 | 23.95 | 1.67 | 20.39 |
February | 368.00 | 22.28 | 50.67 | 24.24 | 0.00 | 0.00 |
March | 391.33 | 22.39 | 75.17 | 24.18 | 0.83 | 26.22 |
April | 209.83 | 22.67 | 166.67 | 24.34 | 2.83 | 26.03 |
May | 235.00 | 22.76 | 169.67 | 24.37 | 4.00 | 26.29 |
June | 122.67 | 22.86 | 288.00 | 24.24 | 4.83 | 26.36 |
July | 92.67 | 23.41 | 354.33 | 24.38 | 15.17 | 26.43 |
August | 101.67 | 23.16 | 345.83 | 24.24 | 10.67 | 26.40 |
September | 150.17 | 22.78 | 237.33 | 24.32 | 4.00 | 26.16 |
October | 255.00 | 22.74 | 148.17 | 24.37 | 3.67 | 26.52 |
November | 357.00 | 22.49 | 72.50 | 24.29 | 0.83 | 27.06 |
December | 421.83 | 22.35 | 24.83 | 24.14 | 0.00 | 0.00 |
Annual Sum or Average | 3126.50 | 22.53 | 1971.00 | 24.30 | 48.50 | 26.17 |
Minimum of Months | 92.67 | 22.25 | 24.83 | 23.95 | 0.00 | 0.00 |
Maximum of Months | 421.83 | 23.41 | 354.33 | 24.38 | 15.17 | 27.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.83 | 21.59 | 91.33 | 20.25 | 87.00 | 20.06 |
February | 427.50 | 21.74 | 51.67 | 20.64 | 45.33 | 20.17 |
March | 453.00 | 21.90 | 58.17 | 21.75 | 34.17 | 20.19 |
April | 330.83 | 22.36 | 98.00 | 23.78 | 6.33 | 20.43 |
May | 305.67 | 22.52 | 115.33 | 23.92 | 2.50 | 19.99 |
June | 200.00 | 22.96 | 218.17 | 24.06 | 0.00 | 0.00 |
July | 118.50 | 23.06 | 283.67 | 24.13 | 1.17 | 24.37 |
August | 163.50 | 22.97 | 252.33 | 24.07 | 0.67 | 23.83 |
September | 248.17 | 22.80 | 166.17 | 24.05 | 0.00 | 0.00 |
October | 314.67 | 22.50 | 107.83 | 23.93 | 5.83 | 20.07 |
November | 454.17 | 22.03 | 44.00 | 20.72 | 39.50 | 20.35 |
December | 488.00 | 21.63 | 89.00 | 20.30 | 88.33 | 20.27 |
Annual Sum or Average | 3981.83 | 22.15 | 1575.67 | 23.31 | 310.83 | 20.22 |
Minimum of Months | 118.50 | 21.59 | 44.00 | 20.25 | 0.00 | 0.00 |
Maximum of Months | 488.00 | 23.06 | 283.67 | 24.13 | 88.33 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.83 | 21.71 | 53.67 | 20.32 | 52.00 | 20.20 |
February | 415.33 | 21.75 | 25.83 | 20.92 | 20.50 | 20.16 |
March | 425.83 | 21.84 | 58.17 | 23.05 | 16.17 | 20.10 |
April | 253.33 | 22.17 | 169.33 | 24.18 | 2.00 | 20.42 |
May | 278.67 | 22.28 | 153.67 | 24.27 | 0.67 | 19.99 |
June | 220.00 | 22.65 | 216.33 | 24.24 | 4.33 | 26.63 |
July | 132.33 | 23.20 | 316.00 | 24.33 | 17.67 | 26.67 |
August | 158.67 | 22.94 | 307.50 | 24.20 | 12.33 | 26.55 |
September | 241.17 | 22.44 | 202.17 | 24.21 | 1.00 | 26.55 |
October | 294.17 | 22.28 | 108.50 | 24.14 | 2.67 | 20.13 |
November | 467.17 | 22.05 | 16.83 | 20.53 | 16.33 | 20.42 |
December | 491.50 | 21.69 | 35.83 | 20.31 | 35.83 | 20.31 |
Annual Sum or Average | 3862.00 | 22.08 | 1663.83 | 23.90 | 181.50 | 21.48 |
Minimum of Months | 132.33 | 21.69 | 16.83 | 20.31 | 0.67 | 19.99 |
Maximum of Months | 491.50 | 23.20 | 316.00 | 24.33 | 52.00 | 26.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.50 | 22.19 | 164.00 | 23.54 | 32.67 | 20.32 |
February | 291.33 | 21.95 | 116.17 | 23.81 | 17.17 | 20.25 |
March | 360.17 | 22.01 | 125.67 | 23.52 | 23.00 | 20.35 |
April | 275.50 | 22.35 | 153.17 | 24.03 | 5.33 | 20.54 |
May | 320.00 | 22.38 | 114.17 | 23.94 | 2.83 | 19.87 |
June | 246.33 | 22.77 | 177.00 | 24.05 | 0.00 | 0.00 |
July | 154.33 | 22.88 | 241.50 | 24.14 | 1.00 | 24.57 |
August | 150.33 | 22.86 | 272.50 | 24.10 | 0.67 | 24.34 |
September | 170.00 | 22.92 | 243.83 | 24.30 | 7.00 | 26.84 |
October | 207.83 | 22.94 | 228.67 | 24.55 | 14.50 | 26.84 |
November | 252.83 | 22.47 | 170.83 | 24.20 | 12.33 | 21.29 |
December | 273.83 | 22.32 | 149.83 | 23.95 | 22.67 | 20.44 |
Annual Sum or Average | 2984.00 | 22.43 | 2157.33 | 24.06 | 139.17 | 21.48 |
Minimum of Months | 150.33 | 21.95 | 114.17 | 23.52 | 0.00 | 0.00 |
Maximum of Months | 360.17 | 22.94 | 272.50 | 24.55 | 32.67 | 26.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.50 | 21.58 | 77.17 | 21.55 | 52.17 | 20.32 |
February | 393.17 | 21.66 | 55.33 | 22.70 | 21.50 | 20.31 |
March | 426.00 | 21.78 | 76.83 | 23.27 | 18.67 | 20.55 |
April | 294.17 | 22.32 | 138.50 | 24.25 | 6.67 | 23.52 |
May | 309.67 | 22.36 | 140.17 | 24.32 | 4.33 | 25.56 |
June | 193.50 | 22.60 | 224.17 | 24.20 | 5.50 | 26.31 |
July | 136.50 | 23.03 | 314.67 | 24.33 | 16.67 | 26.32 |
August | 156.67 | 22.80 | 289.00 | 24.19 | 11.00 | 26.22 |
September | 229.50 | 22.51 | 174.17 | 24.30 | 4.50 | 26.09 |
October | 324.17 | 22.33 | 117.00 | 24.38 | 4.67 | 26.47 |
November | 403.50 | 21.89 | 69.67 | 22.97 | 22.00 | 20.45 |
December | 453.17 | 21.69 | 55.67 | 21.20 | 44.00 | 20.46 |
Annual Sum or Average | 3773.50 | 22.06 | 1732.33 | 23.91 | 211.67 | 21.78 |
Minimum of Months | 136.50 | 21.58 | 55.33 | 21.20 | 4.33 | 20.31 |
Maximum of Months | 453.50 | 23.03 | 314.67 | 24.38 | 52.17 | 26.47 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.57318 | 34.58738 | 0.48063 | 10.54713 |
February | 454.00000 | 24.52379 | 37.14711 | 0.48219 | 10.47010 |
March | 514.00000 | 24.43457 | 40.29109 | 0.48882 | 10.48161 |
April | 485.00000 | 24.52921 | 44.06125 | 0.53518 | 11.51187 |
May | 508.00000 | 24.48456 | 43.53158 | -0.3344 | 8.24912 |
June | 496.00000 | 24.44723 | 50.37875 | -0.2915 | 7.60400 |
July | 497.00000 | 24.60449 | 57.08949 | -0.1923 | 7.02672 |
August | 514.00000 | 24.46605 | 58.65247 | -0.2146 | 6.94353 |
September | 485.00000 | 24.54091 | 52.21462 | -0.2453 | 7.46168 |
October | 502.00000 | 24.60579 | 41.86262 | 0.54585 | 12.10902 |
November | 489.00000 | 24.61174 | 35.63634 | 0.50435 | 11.19273 |
December | 497.00000 | 24.60608 | 30.71480 | 0.46621 | 10.46988 |
Annual Sum or Average | 5943.00000 | 24.53514 | 43.91053 | 0.18240 | 9.49297 |
Minimum of Months | 454.00000 | 24.43457 | 30.71480 | -0.3344 | 6.94353 |
Maximum of Months | 514.00000 | 24.61174 | 58.65247 | 0.54585 | 12.10902 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39265 | 36.47921 | 0.45739 | 9.91193 |
February | 454.00000 | 24.33693 | 38.71209 | 0.46561 | 9.90910 |
March | 514.00000 | 24.31647 | 41.46194 | 0.48928 | 10.33513 |
April | 485.00000 | 24.30471 | 44.79425 | 0.51877 | 10.87223 |
May | 508.00000 | 24.29587 | 45.13964 | -0.3609 | 8.22490 |
June | 496.00000 | 24.28703 | 49.08971 | -0.3183 | 7.60868 |
July | 497.00000 | 24.27981 | 49.58069 | -0.3092 | 7.34588 |
August | 514.00000 | 24.21908 | 49.77763 | -0.3147 | 7.31004 |
September | 485.00000 | 24.31321 | 48.89911 | -0.3200 | 7.70272 |
October | 502.00000 | 24.33407 | 40.76645 | 0.49479 | 10.53559 |
November | 489.00000 | 24.40419 | 36.79138 | 0.48212 | 10.41152 |
December | 497.00000 | 24.39047 | 31.64479 | 0.44502 | 9.65160 |
Annual Sum or Average | 5943.00000 | 24.32243 | 42.79497 | 0.14093 | 9.14235 |
Minimum of Months | 454.00000 | 24.21908 | 31.64479 | -0.3609 | 7.31004 |
Maximum of Months | 514.00000 | 24.40419 | 49.77763 | 0.51877 | 10.87223 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12411 | 38.84290 | 0.37949 | 8.38801 |
February | 454.00000 | 24.09157 | 40.13540 | 0.38081 | 8.27519 |
March | 514.00000 | 24.12280 | 42.62870 | 0.40934 | 8.69975 |
April | 485.00000 | 24.14529 | 46.06206 | 0.44640 | 9.41536 |
May | 508.00000 | 24.18164 | 45.88450 | -0.4298 | 9.23850 |
June | 496.00000 | 24.17177 | 49.91166 | -0.3903 | 8.52799 |
July | 497.00000 | 24.18729 | 50.42798 | -0.3793 | 8.37790 |
August | 514.00000 | 24.15057 | 50.62613 | -0.3827 | 8.34206 |
September | 485.00000 | 24.19777 | 49.63436 | -0.3859 | 8.54040 |
October | 502.00000 | 24.16110 | 41.80122 | 0.42939 | 9.17946 |
November | 489.00000 | 24.19432 | 38.27226 | 0.40031 | 8.86007 |
December | 497.00000 | 24.07824 | 33.28783 | 0.33451 | 7.67731 |
Annual Sum or Average | 5943.00000 | 24.15078 | 43.99091 | 0.06453 | 8.62845 |
Minimum of Months | 454.00000 | 24.07824 | 33.28783 | -0.4298 | 7.67731 |
Maximum of Months | 514.00000 | 24.19777 | 50.62613 | 0.44640 | 9.41536 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13779 | 41.83191 | 0.12320 | 6.61615 |
February | 454.00000 | 23.30494 | 42.97030 | 0.17854 | 6.67323 |
March | 514.00000 | 23.51444 | 44.68608 | 0.24835 | 7.10404 |
April | 485.00000 | 23.78670 | 47.34265 | 0.35854 | 8.31147 |
May | 508.00000 | 23.86729 | 47.10422 | -0.5391 | 12.02087 |
June | 496.00000 | 24.03407 | 50.44484 | -0.4334 | 9.36208 |
July | 497.00000 | 24.13618 | 50.51439 | -0.3859 | 8.51183 |
August | 514.00000 | 24.06846 | 50.86783 | -0.4031 | 8.70795 |
September | 485.00000 | 23.99410 | 50.58907 | -0.4580 | 9.94785 |
October | 502.00000 | 23.81774 | 43.15822 | 0.34130 | 8.01381 |
November | 489.00000 | 23.51064 | 40.67751 | 0.22056 | 7.01426 |
December | 497.00000 | 23.17223 | 36.61860 | 0.10231 | 6.26602 |
Annual Sum or Average | 5943.00000 | 23.69811 | 45.58828 | -0.0565 | 8.22510 |
Minimum of Months | 454.00000 | 23.13779 | 36.61860 | -0.5391 | 6.26602 |
Maximum of Months | 514.00000 | 24.13618 | 50.86783 | 0.35854 | 12.02087 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.66647 | 36.48080 | 0.24713 | 6.84875 |
February | 454.00000 | 23.69573 | 39.08945 | 0.28082 | 7.03528 |
March | 514.00000 | 23.80723 | 41.81985 | 0.33321 | 7.72586 |
April | 485.00000 | 23.99323 | 44.85796 | 0.41728 | 8.83463 |
May | 508.00000 | 23.97660 | 44.90505 | -0.4913 | 10.54412 |
June | 496.00000 | 24.14002 | 48.65708 | -0.3846 | 8.38018 |
July | 497.00000 | 24.19405 | 49.42916 | -0.3477 | 7.75971 |
August | 514.00000 | 24.10653 | 49.85895 | -0.3701 | 8.03186 |
September | 485.00000 | 24.05544 | 49.10993 | -0.4283 | 9.24987 |
October | 502.00000 | 24.04711 | 40.71934 | 0.40464 | 8.79038 |
November | 489.00000 | 23.89272 | 37.00790 | 0.32295 | 7.62042 |
December | 497.00000 | 23.80962 | 31.58138 | 0.26234 | 6.76239 |
Annual Sum or Average | 5943.00000 | 23.95024 | 42.82403 | 0.01776 | 8.13935 |
Minimum of Months | 454.00000 | 23.66647 | 31.58138 | -0.4913 | 6.76239 |
Maximum of Months | 514.00000 | 24.19405 | 49.85895 | 0.41728 | 10.54412 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39597 | 36.52864 | 0.21972 | 6.94436 |
February | 454.00000 | 23.29833 | 39.67695 | 0.22203 | 6.90135 |
March | 514.00000 | 23.40286 | 42.48494 | 0.27412 | 7.55058 |
April | 485.00000 | 23.61466 | 45.60325 | 0.37409 | 8.74991 |
May | 508.00000 | 23.74091 | 45.24355 | -0.5108 | 12.22576 |
June | 496.00000 | 23.78290 | 49.43455 | -0.4465 | 10.60425 |
July | 497.00000 | 23.86686 | 50.00485 | -0.3897 | 9.54796 |
August | 514.00000 | 23.73416 | 50.53698 | -0.4255 | 10.04923 |
September | 485.00000 | 23.72016 | 49.67324 | -0.4783 | 11.29215 |
October | 502.00000 | 23.66431 | 41.37393 | 0.35331 | 8.39813 |
November | 489.00000 | 23.48455 | 37.61857 | 0.25927 | 7.19527 |
December | 497.00000 | 23.30058 | 32.23742 | 0.17711 | 6.36309 |
Annual Sum or Average | 5943.00000 | 23.58580 | 43.39827 | -0.0336 | 8.83367 |
Minimum of Months | 454.00000 | 23.29833 | 32.23742 | -0.5108 | 6.36309 |
Maximum of Months | 514.00000 | 23.86686 | 50.53698 | 0.37409 | 12.22576 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.97701 | 35.17801 | 0.38621 | 9.28090 |
February | 454.00000 | 23.79996 | 38.50371 | 0.35061 | 8.63866 |
March | 514.00000 | 23.73489 | 41.63070 | 0.34637 | 8.42843 |
April | 485.00000 | 23.89713 | 44.91358 | 0.41500 | 9.07665 |
May | 508.00000 | 23.73769 | 45.49310 | -0.5627 | 12.54677 |
June | 496.00000 | 23.91690 | 49.32517 | -0.4567 | 9.81513 |
July | 497.00000 | 24.03285 | 49.86089 | -0.3946 | 8.61239 |
August | 514.00000 | 24.02699 | 49.90185 | -0.3714 | 8.24523 |
September | 485.00000 | 24.11171 | 48.57748 | -0.3577 | 8.70212 |
October | 502.00000 | 24.24563 | 39.90287 | 0.50229 | 11.28446 |
November | 489.00000 | 24.17245 | 35.94837 | 0.45082 | 10.24124 |
December | 497.00000 | 24.18375 | 30.43288 | 0.42219 | 9.87555 |
Annual Sum or Average | 5943.00000 | 23.98660 | 42.50761 | 0.05752 | 9.57046 |
Minimum of Months | 454.00000 | 23.73489 | 30.43288 | -0.5627 | 8.24523 |
Maximum of Months | 514.00000 | 24.24563 | 49.90185 | 0.50229 | 12.54677 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.66160 | 35.64995 | 0.31191 | 7.91679 |
February | 454.00000 | 23.98359 | 37.71083 | 0.42503 | 9.49648 |
March | 514.00000 | 24.21717 | 40.07586 | 0.52098 | 11.34127 |
April | 485.00000 | 24.48369 | 42.97048 | 0.65476 | 14.75987 |
May | 508.00000 | 24.07560 | 44.09636 | -0.3458 | 9.07366 |
June | 496.00000 | 24.32762 | 47.56094 | -0.1830 | 6.89611 |
July | 497.00000 | 24.49641 | 47.84271 | -0.0833 | 6.48530 |
August | 514.00000 | 24.39776 | 48.12935 | -0.0835 | 6.24488 |
September | 485.00000 | 24.14184 | 48.18188 | -0.2780 | 8.03720 |
October | 502.00000 | 24.24463 | 39.59402 | 0.53678 | 11.87226 |
November | 489.00000 | 24.32994 | 35.29822 | 0.51548 | 11.34065 |
December | 497.00000 | 24.40791 | 29.70077 | 0.50106 | 10.95097 |
Annual Sum or Average | 5943.00000 | 24.23164 | 41.43205 | 0.20525 | 9.52089 |
Minimum of Months | 454.00000 | 23.66160 | 29.70077 | -0.3458 | 6.24488 |
Maximum of Months | 514.00000 | 24.49641 | 48.18188 | 0.65476 | 14.75987 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.75532 | 38.34572 | 0.01786 | 6.33691 |
February | 454.00000 | 22.79554 | 41.38881 | 0.05281 | 6.18827 |
March | 514.00000 | 22.95224 | 44.33587 | 0.11225 | 6.36808 |
April | 485.00000 | 23.38700 | 46.99459 | 0.25003 | 7.03007 |
May | 508.00000 | 23.56708 | 46.28265 | -0.6508 | 14.85867 |
June | 496.00000 | 23.85393 | 50.05600 | -0.5067 | 10.78263 |
July | 497.00000 | 23.98469 | 51.37593 | -0.4456 | 9.50253 |
August | 514.00000 | 23.86083 | 52.32894 | -0.4818 | 10.25523 |
September | 485.00000 | 23.73967 | 50.82502 | -0.5539 | 12.00721 |
October | 502.00000 | 23.58255 | 42.39786 | 0.27633 | 7.33419 |
November | 489.00000 | 23.08137 | 39.19492 | 0.10978 | 6.42602 |
December | 497.00000 | 22.72902 | 33.68840 | -0.0157 | 6.13354 |
Annual Sum or Average | 5943.00000 | 23.36131 | 44.79803 | -0.1553 | 8.62522 |
Minimum of Months | 454.00000 | 22.72902 | 33.68840 | -0.6508 | 6.13354 |
Maximum of Months | 514.00000 | 23.98469 | 52.32894 | 0.27633 | 14.85867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.43829 | 38.19462 | -0.0160 | 6.09727 |
February | 385.00000 | 22.39519 | 41.51892 | -0.0011 | 6.12581 |
March | 433.00000 | 22.60335 | 43.80664 | 0.07033 | 6.62809 |
April | 410.00000 | 23.28746 | 46.46146 | 0.27396 | 8.02882 |
May | 430.00000 | 23.32153 | 46.15266 | -0.6702 | 16.96697 |
June | 418.00000 | 23.49836 | 50.47926 | -0.5607 | 13.83426 |
July | 422.00000 | 23.84466 | 51.01859 | -0.4194 | 11.09630 |
August | 433.00000 | 23.67076 | 51.95892 | -0.4660 | 11.74742 |
September | 410.00000 | 23.37596 | 51.16342 | -0.6110 | 15.01596 |
October | 427.00000 | 23.20538 | 42.94976 | 0.23238 | 7.27930 |
November | 417.00000 | 22.66728 | 39.28918 | 0.05520 | 6.16216 |
December | 422.00000 | 22.34930 | 33.50194 | -0.0619 | 5.98452 |
Annual Sum or Average | 5034.00000 | 23.05868 | 44.72057 | -0.1828 | 9.60100 |
Minimum of Months | 385.00000 | 22.34930 | 33.50194 | -0.6702 | 5.98452 |
Maximum of Months | 433.00000 | 23.84466 | 51.95892 | 0.27396 | 16.96697 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.82126 | 35.28236 | 0.34465 | 9.22970 |
February | 454.00000 | 23.46102 | 39.27734 | 0.26334 | 8.18771 |
March | 514.00000 | 23.30732 | 42.75252 | 0.23344 | 7.73562 |
April | 485.00000 | 23.55617 | 46.12746 | 0.31611 | 8.01735 |
May | 508.00000 | 23.44023 | 46.44626 | -0.6772 | 15.92688 |
June | 496.00000 | 23.65902 | 50.57789 | -0.5623 | 12.31332 |
July | 497.00000 | 23.83941 | 51.63694 | -0.4812 | 10.46188 |
August | 514.00000 | 23.87094 | 51.83676 | -0.4474 | 9.88364 |
September | 485.00000 | 24.00162 | 49.43049 | -0.4065 | 9.80475 |
October | 502.00000 | 24.12227 | 40.51124 | 0.46300 | 10.91033 |
November | 489.00000 | 23.95791 | 36.46692 | 0.38810 | 9.67663 |
December | 497.00000 | 23.93968 | 30.67658 | 0.34901 | 9.35154 |
Annual Sum or Average | 5943.00000 | 23.74865 | 43.45756 | -0.0215 | 10.14722 |
Minimum of Months | 454.00000 | 23.30732 | 30.67658 | -0.6772 | 7.73562 |
Maximum of Months | 514.00000 | 24.12227 | 51.83676 | 0.46300 | 15.92688 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.52007 | 37.87509 | 0.01208 | 6.36058 |
February | 454.00000 | 22.59779 | 40.93682 | 0.05912 | 6.45392 |
March | 514.00000 | 22.75172 | 43.84309 | 0.12103 | 6.73922 |
April | 485.00000 | 23.44390 | 46.07581 | 0.33055 | 8.67836 |
May | 508.00000 | 23.44563 | 45.92439 | -0.6041 | 15.06047 |
June | 496.00000 | 23.73287 | 49.79904 | -0.4520 | 10.93188 |
July | 497.00000 | 23.98812 | 50.50811 | -0.3439 | 9.19109 |
August | 514.00000 | 23.83619 | 51.31959 | -0.3854 | 9.67356 |
September | 485.00000 | 23.63669 | 50.27302 | -0.4947 | 11.95215 |
October | 502.00000 | 23.37584 | 42.07898 | 0.28546 | 8.05459 |
November | 489.00000 | 22.90295 | 38.56383 | 0.12348 | 6.78431 |
December | 497.00000 | 22.59244 | 32.96909 | 0.00626 | 6.22549 |
Annual Sum or Average | 5943.00000 | 23.23934 | 44.21014 | -0.1141 | 8.86101 |
Minimum of Months | 454.00000 | 22.52007 | 32.96909 | -0.6041 | 6.22549 |
Maximum of Months | 514.00000 | 23.98812 | 51.31959 | 0.33055 | 15.06047 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.68946 | 40.40814 | -0.2462 | 8.68480 |
February | 454.00000 | 21.85485 | 43.35199 | -0.1774 | 7.63745 |
March | 514.00000 | 22.11516 | 46.18052 | -0.0901 | 7.10312 |
April | 485.00000 | 22.84784 | 48.36184 | 0.12739 | 6.91825 |
May | 508.00000 | 23.07204 | 47.55641 | -0.8085 | 21.07503 |
June | 496.00000 | 23.56910 | 50.88476 | -0.5906 | 13.48560 |
July | 497.00000 | 23.79408 | 51.98808 | -0.4918 | 10.91196 |
August | 514.00000 | 23.63686 | 53.15458 | -0.5413 | 12.11281 |
September | 485.00000 | 23.36210 | 52.10772 | -0.6717 | 15.96475 |
October | 502.00000 | 23.06092 | 43.65687 | 0.15457 | 7.17097 |
November | 489.00000 | 22.14560 | 40.99978 | -0.1169 | 7.21816 |
December | 497.00000 | 21.65366 | 35.43995 | -0.2808 | 8.54672 |
Annual Sum or Average | 5943.00000 | 22.73982 | 46.19999 | -0.3129 | 10.60035 |
Minimum of Months | 454.00000 | 21.65366 | 35.43995 | -0.8085 | 6.91825 |
Maximum of Months | 514.00000 | 23.79408 | 53.15458 | 0.15457 | 21.07503 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.76169 | 39.64928 | -0.1926 | 7.49412 |
February | 454.00000 | 21.89891 | 42.78289 | -0.1344 | 7.05385 |
March | 514.00000 | 22.17813 | 45.38549 | -0.0376 | 7.08689 |
April | 485.00000 | 23.07423 | 47.23915 | 0.22817 | 8.06055 |
May | 508.00000 | 23.08772 | 47.03599 | -0.7404 | 19.75920 |
June | 496.00000 | 23.41467 | 50.79042 | -0.5740 | 14.53793 |
July | 497.00000 | 23.83402 | 51.05595 | -0.4010 | 10.73912 |
August | 514.00000 | 23.67002 | 52.02007 | -0.4480 | 11.45188 |
September | 485.00000 | 23.25365 | 51.75271 | -0.6425 | 16.44488 |
October | 502.00000 | 22.99581 | 43.42674 | 0.18078 | 7.23174 |
November | 489.00000 | 22.10385 | 40.53464 | -0.0885 | 6.50454 |
December | 497.00000 | 21.70023 | 34.83259 | -0.2328 | 7.36210 |
Annual Sum or Average | 5943.00000 | 22.75398 | 45.56612 | -0.2586 | 10.33727 |
Minimum of Months | 454.00000 | 21.70023 | 34.83259 | -0.7404 | 6.50454 |
Maximum of Months | 514.00000 | 23.83402 | 52.02007 | 0.22817 | 19.75920 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.05425 | 36.94325 | 0.14138 | 8.66193 |
February | 454.00000 | 22.75730 | 40.92627 | 0.08103 | 8.18078 |
March | 514.00000 | 22.62041 | 44.40175 | 0.06181 | 7.87329 |
April | 485.00000 | 23.06918 | 47.41244 | 0.20416 | 7.74083 |
May | 508.00000 | 22.94583 | 47.71237 | -0.8346 | 22.23208 |
June | 496.00000 | 23.35294 | 51.42935 | -0.6521 | 15.41998 |
July | 497.00000 | 23.64440 | 52.25787 | -0.5287 | 12.03882 |
August | 514.00000 | 23.65171 | 52.66121 | -0.5057 | 11.70055 |
September | 485.00000 | 23.67927 | 50.57144 | -0.5093 | 12.87808 |
October | 502.00000 | 23.69905 | 41.60372 | 0.36052 | 9.98572 |
November | 489.00000 | 23.32383 | 37.85166 | 0.22227 | 8.55487 |
December | 497.00000 | 23.20478 | 31.97244 | 0.15231 | 8.39149 |
Annual Sum or Average | 5943.00000 | 23.25219 | 44.68154 | -0.1537 | 11.17545 |
Minimum of Months | 454.00000 | 22.62041 | 31.97244 | -0.8346 | 7.74083 |
Maximum of Months | 514.00000 | 23.69905 | 52.66121 | 0.36052 | 22.23208 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79784 | 39.42214 | -0.1744 | 7.76039 |
February | 454.00000 | 21.96285 | 42.32454 | -0.1034 | 7.25934 |
March | 514.00000 | 22.13511 | 45.31526 | -0.0315 | 7.20045 |
April | 485.00000 | 22.99371 | 47.26440 | 0.22836 | 8.28848 |
May | 508.00000 | 23.00387 | 47.07210 | -0.7433 | 20.36324 |
June | 496.00000 | 23.42346 | 50.66148 | -0.5415 | 13.77949 |
July | 497.00000 | 23.77130 | 51.18899 | -0.3971 | 10.71593 |
August | 514.00000 | 23.59183 | 52.18297 | -0.4502 | 11.54306 |
September | 485.00000 | 23.28718 | 51.45550 | -0.6021 | 15.47687 |
October | 502.00000 | 22.92540 | 43.18369 | 0.18074 | 7.80673 |
November | 489.00000 | 22.24596 | 39.92210 | -0.0413 | 7.12407 |
December | 497.00000 | 21.87819 | 34.24203 | -0.1791 | 7.48100 |
Annual Sum or Average | 5943.00000 | 22.75654 | 45.38088 | -0.2399 | 10.42865 |
Minimum of Months | 454.00000 | 21.79784 | 34.24203 | -0.7433 | 7.12407 |
Maximum of Months | 514.00000 | 23.77130 | 52.18297 | 0.22836 | 20.36324 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.441122E+11 | 89258.26 | 13-JAN-14:10 | 273.14 | 0.238026E+12 | 0.00 | 0.282138E+12 | 1.71 | 7.06 | 13-JAN-14:10 | 0.00 | 0.00 |
February | 0.327237E+11 | 92730.18 | 01-FEB-13:10 | 225.81 | 0.163846E+12 | 0.00 | 0.196570E+12 | 1.44 | 7.11 | 01-FEB-13:10 | 0.00 | 0.00 |
March | 0.330071E+11 | 88944.43 | 22-MAR-12:30 | 223.22 | 0.169844E+12 | 0.00 | 0.202851E+12 | 1.31 | 6.99 | 10-MAR-12:10 | 0.00 | 0.00 |
April | 0.586962E+11 | 90666.22 | 26-APR-10:10 | 336.66 | 0.334475E+12 | 0.00 | 0.393172E+12 | 2.31 | 6.98 | 27-APR-09:10 | 0.00 | 0.00 |
May | 0.648831E+11 | 85555.35 | 04-MAY-14:00 | 366.86 | 0.360156E+12 | 0.00 | 0.425039E+12 | 2.44 | 6.98 | 18-MAY-11:20 | 0.00 | 0.00 |
June | 0.939625E+11 | 116534.04 | 29-JUN-13:00 | 446.98 | 0.557783E+12 | 0.00 | 0.651745E+12 | 3.35 | 7.16 | 30-JUN-05:02 | 0.00 | 0.00 |
July | 0.129954E+12 | 155600.99 | 31-JUL-15:50 | 550.91 | 0.810727E+12 | 0.00 | 0.940681E+12 | 4.13 | 7.24 | 31-JUL-05:02 | 0.00 | 0.00 |
August | 0.143814E+12 | 152146.00 | 18-AUG-15:50 | 584.73 | 0.908413E+12 | 0.00 | 0.105223E+13 | 4.43 | 7.32 | 07-AUG-05:02 | 0.00 | 0.00 |
September | 0.981310E+11 | 136601.78 | 22-SEP-12:30 | 434.71 | 0.602112E+12 | 0.00 | 0.700243E+12 | 3.38 | 7.28 | 30-SEP-05:02 | 0.00 | 0.00 |
October | 0.102308E+12 | 149849.14 | 04-OCT-05:03 | 445.75 | 0.625566E+12 | 0.00 | 0.727875E+12 | 3.35 | 7.30 | 04-OCT-05:02 | 0.00 | 0.00 |
November | 0.505201E+11 | 83908.50 | 18-NOV-12:40 | 307.94 | 0.273879E+12 | 0.00 | 0.324399E+12 | 2.01 | 6.99 | 27-NOV-15:20 | 0.00 | 0.00 |
December | 0.476123E+11 | 85672.13 | 05-DEC-15:00 | 287.52 | 0.263587E+12 | 0.00 | 0.311199E+12 | 1.83 | 7.00 | 05-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.899725E+12 | 4484.22 | 0.530841E+13 | 0.620814E+13 | 2.65 | |||||||
Minimum of Months | 0.327237E+11 | 83908.50 | 223.22 | 0.163846E+12 | 0.00 | 0.196570E+12 | 1.31 | 6.98 | 0.00 | 0.00 | ||
Maximum of Months | 0.143814E+12 | 155600.99 | 584.73 | 0.908413E+12 | 0.00 | 0.105223E+13 | 4.43 | 7.32 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.227991E+10 | 89258.26 | 13-JAN-14:10 | 7.67 | 0.158083E+11 | 0.00 | 0.180882E+11 | 0.07 | 7.06 | 13-JAN-14:10 | 0.00 | 0.00 |
February | 0.144810E+09 | 80954.58 | 01-FEB-12:00 | 0.50 | 0.999398E+09 | 0.00 | 0.114421E+10 | 0.01 | 6.91 | 01-FEB-12:00 | 0.00 | 0.00 |
March | 0.212687E+10 | 88944.43 | 22-MAR-12:30 | 7.00 | 0.146336E+11 | 0.00 | 0.167605E+11 | 0.06 | 6.96 | 23-MAR-13:10 | 0.00 | 0.00 |
April | 0.525760E+10 | 90666.22 | 26-APR-10:10 | 17.50 | 0.361809E+11 | 0.00 | 0.414385E+11 | 0.17 | 6.97 | 11-APR-14:40 | 0.00 | 0.00 |
May | 0.163456E+10 | 85555.35 | 04-MAY-14:00 | 5.50 | 0.112936E+11 | 0.00 | 0.129281E+11 | 0.05 | 6.97 | 03-MAY-12:10 | 0.00 | 0.00 |
June | 0.230514E+11 | 116534.04 | 29-JUN-13:00 | 70.72 | 0.157625E+12 | 0.00 | 0.180676E+12 | 0.67 | 7.16 | 30-JUN-05:02 | 0.00 | 0.00 |
July | 0.571824E+11 | 155600.99 | 31-JUL-15:50 | 158.06 | 0.385517E+12 | 0.00 | 0.442699E+12 | 1.44 | 7.24 | 31-JUL-05:02 | 0.00 | 0.00 |
August | 0.711373E+11 | 152146.00 | 18-AUG-15:50 | 192.26 | 0.479236E+12 | 0.00 | 0.550373E+12 | 1.74 | 7.32 | 07-AUG-05:02 | 0.00 | 0.00 |
September | 0.330704E+11 | 136601.78 | 22-SEP-12:30 | 97.93 | 0.225855E+12 | 0.00 | 0.258926E+12 | 0.93 | 7.28 | 30-SEP-05:02 | 0.00 | 0.00 |
October | 0.361499E+11 | 149849.14 | 04-OCT-05:03 | 105.41 | 0.247198E+12 | 0.00 | 0.283348E+12 | 0.97 | 7.30 | 04-OCT-05:02 | 0.00 | 0.00 |
November | 0.337509E+09 | 81451.42 | 28-NOV-13:40 | 1.17 | 0.232876E+10 | 0.00 | 0.266627E+10 | 0.01 | 6.92 | 28-NOV-13:40 | 0.00 | 0.00 |
December | 0.131052E+10 | 85672.13 | 05-DEC-15:00 | 4.50 | 0.905632E+10 | 0.00 | 0.103668E+11 | 0.04 | 7.00 | 05-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233683E+12 | 668.20 | 0.158573E+13 | 0.181941E+13 | 0.52 | |||||||
Minimum of Months | 0.144810E+09 | 80954.58 | 0.50 | 0.999398E+09 | 0.00 | 0.114421E+10 | 0.01 | 6.91 | 0.00 | 0.00 | ||
Maximum of Months | 0.711373E+11 | 155600.99 | 192.26 | 0.479236E+12 | 0.00 | 0.550373E+12 | 1.74 | 7.32 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.573160E+11 | 744.00 | 49248.27 | 03-JAN-11:40 | 549043.17 | 03-JAN-01:00 | 22.51 | 18.95 | 13.76 |
February | 0.743570E+11 | 672.00 | 49248.27 | 01-FEB-03:50 | 573079.63 | 28-FEB-22:21 | 25.11 | 18.78 | 13.76 |
March | 0.960087E+11 | 744.00 | 49248.27 | 01-MAR-09:00 | 597983.75 | 01-MAR-00:10 | 28.22 | 19.08 | 13.76 |
April | 0.120281E+12 | 720.00 | 49248.27 | 01-APR-07:50 | 637182.90 | 26-APR-13:10 | 32.83 | 20.74 | 13.76 |
May | 0.796777E+11 | 744.00 | 49248.27 | 01-MAY-09:00 | 301182.73 | 01-MAY-00:05 | 22.82 | 19.18 | 13.76 |
June | 0.119514E+12 | 720.00 | 49248.27 | 01-JUN-08:00 | 338384.92 | 29-JUN-11:20 | 27.17 | 20.65 | 13.76 |
July | 0.131740E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 498435.10 | 31-JUL-13:10 | 32.68 | 23.20 | 13.76 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 645616.55 | 18-AUG-15:30 | 37.06 | 24.63 | 13.76 |
September | 0.111721E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 388712.45 | 01-SEP-00:03 | 24.19 | 20.46 | 13.76 |
October | 0.120606E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 376250.35 | 16-OCT-11:20 | 28.56 | 21.98 | 13.76 |
November | 0.105500E+12 | 720.00 | 49248.27 | 01-NOV-09:30 | 559205.57 | 05-NOV-01:28 | 28.90 | 19.67 | 13.76 |
December | 0.111623E+12 | 744.00 | 49248.27 | 01-DEC-10:50 | 636211.57 | 25-DEC-16:01 | 32.35 | 20.30 | 13.76 |
Annual Sum or Average | 0.126025E+13 | 8760.00 | 28.57 | 20.65 | 13.76 | ||||
Minimum of Months | 0.573160E+11 | 672.00 | 49248.27 | 301182.73 | 22.51 | 18.78 | 13.76 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 645616.55 | 37.06 | 24.63 | 13.76 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.192194E+10 | 218.96 | 16541.97 | 13-JAN-14:10 | 751719.37 | 13-JAN-14:20 | 21.85 | 21.26 | 14.72 |
February | 0.109226E+10 | 169.96 | 13264.43 | 11-FEB-14:00 | 669838.11 | 01-FEB-12:00 | 21.61 | 21.15 | 13.37 |
March | 0.197203E+10 | 171.76 | 16541.97 | 22-MAR-11:00 | 734145.50 | 22-MAR-13:30 | 21.61 | 21.18 | 12.20 |
April | 0.477551E+10 | 277.47 | 16541.97 | 04-APR-11:00 | 731656.85 | 11-APR-15:40 | 22.05 | 21.20 | 19.65 |
May | 0.405407E+10 | 327.23 | 16541.97 | 02-MAY-13:30 | 716608.37 | 04-MAY-14:00 | 22.14 | 21.26 | 21.25 |
June | 0.109130E+11 | 423.16 | 16541.97 | 01-JUN-10:40 | 928584.17 | 29-JUN-13:00 | 22.95 | 21.54 | 27.39 |
July | 0.209091E+11 | 519.68 | 16541.97 | 01-JUL-07:40 | 1175459.69 | 31-JUL-16:00 | 23.99 | 22.04 | 32.70 |
August | 0.238557E+11 | 564.57 | 16541.97 | 01-AUG-09:30 | 1162271.32 | 18-AUG-16:00 | 24.39 | 22.21 | 34.62 |
September | 0.133395E+11 | 415.14 | 16541.97 | 01-SEP-11:00 | 1040720.40 | 22-SEP-12:30 | 23.49 | 21.99 | 26.53 |
October | 0.117751E+11 | 422.10 | 16541.97 | 01-OCT-07:32 | 1073179.31 | 03-OCT-13:40 | 23.37 | 21.85 | 26.14 |
November | 0.197145E+10 | 247.24 | 16541.97 | 10-NOV-12:40 | 673877.03 | 10-NOV-13:20 | 21.88 | 21.18 | 17.59 |
December | 0.127483E+10 | 223.74 | 7176.59 | 07-DEC-12:50 | 706300.19 | 05-DEC-14:50 | 21.79 | 21.15 | 15.50 |
Annual Sum or Average | 0.978544E+11 | 3981.01 | 22.60 | 21.50 | 21.86 | ||||
Minimum of Months | 0.109226E+10 | 169.96 | 7176.59 | 669838.11 | 21.61 | 21.15 | 12.20 | ||
Maximum of Months | 0.238557E+11 | 564.57 | 16541.97 | 1175459.69 | 24.39 | 22.21 | 34.62 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.299506E+09 | 7.67 | 16541.97 | 13-JAN-14:10 | 751719.37 | 13-JAN-14:20 | 21.85 | 21.82 | 0.46 |
February | 11752188.33 | 0.50 | 6907.50 | 01-FEB-12:00 | 669838.11 | 01-FEB-12:00 | 21.61 | 21.61 | 0.03 |
March | 0.416858E+09 | 7.00 | 16541.97 | 22-MAR-12:10 | 734145.50 | 22-MAR-13:30 | 21.61 | 21.58 | 0.42 |
April | 0.103572E+10 | 17.50 | 16541.97 | 04-APR-12:10 | 731656.85 | 11-APR-15:40 | 22.05 | 21.96 | 1.08 |
May | 0.284449E+09 | 5.50 | 16541.97 | 02-MAY-14:20 | 716608.37 | 04-MAY-14:00 | 22.14 | 22.11 | 0.33 |
June | 0.423111E+10 | 71.05 | 16541.97 | 13-JUN-14:00 | 928584.17 | 29-JUN-13:00 | 22.95 | 22.56 | 4.39 |
July | 0.101433E+11 | 170.34 | 16541.97 | 01-JUL-13:40 | 1175459.69 | 31-JUL-16:00 | 23.99 | 23.03 | 10.16 |
August | 0.123896E+11 | 208.07 | 16541.97 | 01-AUG-09:40 | 1162271.32 | 18-AUG-16:00 | 24.39 | 23.19 | 12.37 |
September | 0.593322E+10 | 100.25 | 16541.97 | 01-SEP-12:50 | 1040720.40 | 22-SEP-12:30 | 23.49 | 22.93 | 6.19 |
October | 0.582945E+10 | 110.76 | 16541.97 | 01-OCT-10:54 | 1073179.31 | 03-OCT-13:40 | 23.37 | 22.76 | 6.60 |
November | 14079550.83 | 1.17 | 3470.91 | 28-NOV-14:00 | 673835.01 | 28-NOV-13:40 | 21.88 | 21.87 | 0.07 |
December | 68594747.19 | 4.50 | 5404.20 | 05-DEC-15:00 | 706300.19 | 05-DEC-14:50 | 21.79 | 21.77 | 0.27 |
Annual Sum or Average | 0.406577E+11 | 704.31 | 22.60 | 22.27 | 3.57 | ||||
Minimum of Months | 11752188.33 | 0.50 | 3470.91 | 669838.11 | 21.61 | 21.58 | 0.03 | ||
Maximum of Months | 0.123896E+11 | 208.07 | 16541.97 | 1175459.69 | 24.39 | 23.19 | 12.37 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.590468E+11 | 0.00 | 199.06 | 576659.47 | 30-JAN-01:30 | 0.00 | 63.08 | 67.82 | 0.40 | 0.00 | 0.02 | 0.46 | 30-JAN-01:30 |
February | 0.407151E+11 | 0.00 | 192.98 | 645882.53 | 20-FEB-03:30 | 0.00 | 56.92 | 63.92 | 0.21 | 0.00 | 0.01 | 0.51 | 20-FEB-03:30 |
March | 0.602848E+11 | 0.00 | 226.32 | 681973.50 | 19-MAR-24:00 | 0.00 | 58.61 | 65.39 | 0.30 | 0.00 | 0.02 | 0.54 | 19-MAR-24:00 |
April | 0.148776E+11 | 0.00 | 104.23 | 773696.12 | 23-APR-22:56 | 0.00 | 53.09 | 57.23 | 0.05 | 0.00 | 0.00 | 0.62 | 23-APR-22:56 |
May | 0.878852E+10 | 0.00 | 70.42 | 515763.00 | 29-MAY-08:40 | 0.00 | 55.74 | 58.27 | 0.03 | 0.00 | 0.00 | 0.41 | 29-MAY-08:40 |
June | 0.842449E+09 | 0.00 | 10.85 | 578075.93 | 18-JUN-23:00 | 0.00 | 61.81 | 62.16 | 0.00 | 0.00 | 0.00 | 0.46 | 18-JUN-23:00 |
July | 0.120900E+10 | 0.00 | 1.41 | 295838.15 | 02-JUL-22:08 | 0.00 | 72.28 | 72.30 | 0.01 | 0.00 | 0.00 | 0.24 | 02-JUL-22:08 |
August | 0.854050E+09 | 0.00 | 2.04 | 230445.20 | 27-AUG-23:08 | 0.00 | 72.78 | 72.81 | 0.01 | 0.00 | 0.00 | 0.18 | 27-AUG-23:08 |
September | 0.552196E+09 | 0.00 | 12.55 | 496496.74 | 24-SEP-16:40 | 0.00 | 68.59 | 68.81 | 0.00 | 0.00 | 0.00 | 0.40 | 24-SEP-16:40 |
October | 0.455723E+10 | 0.00 | 37.33 | 499858.19 | 15-OCT-13:48 | 0.00 | 65.63 | 66.56 | 0.03 | 0.00 | 0.00 | 0.40 | 15-OCT-13:48 |
November | 0.226801E+11 | 0.00 | 151.70 | 671796.57 | 26-NOV-15:10 | 0.00 | 58.13 | 63.14 | 0.09 | 0.00 | 0.01 | 0.53 | 26-NOV-15:10 |
December | 0.490229E+11 | 0.00 | 199.17 | 625517.64 | 31-DEC-15:25 | 0.00 | 63.64 | 69.00 | 0.26 | 0.00 | 0.01 | 0.50 | 31-DEC-15:25 |
Annual Sum or Average | 0.263431E+12 | 1208.05 | 62.60 | 65.66 | 0.12 | 0.00 | 0.01 | ||||||
Minimum of Months | 0.552196E+09 | 0.00 | 1.41 | 230445.20 | 0.00 | 53.09 | 57.23 | 0.00 | 0.00 | 0.00 | 0.18 | ||
Maximum of Months | 0.602848E+11 | 0.00 | 226.32 | 773696.12 | 0.00 | 72.78 | 72.81 | 0.40 | 0.00 | 0.02 | 0.62 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.51 | 22.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.11 | 25.11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 28.22 | 28.22 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 32.83 | 32.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 22.82 | 22.82 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 27.17 | 27.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 32.68 | 32.68 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 24.19 | 24.19 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 28.56 | 28.56 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.90 | 28.90 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 32.35 | 32.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.57 | 28.57 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 22.51 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.131248E+11 | 0.00 | 158.46 | 0.130089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83638.06 | 16-JAN-15:20 | 70600.68 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.617350E+10 | 0.00 | 100.89 | 0.608130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74946.52 | 13-FEB-05:52 | 58542.93 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.682026E+10 | 0.00 | 101.40 | 0.671548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53449.83 | 24-MAR-03:01 | 49507.89 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.171903E+11 | 0.00 | 197.56 | 0.169294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89145.24 | 30-APR-21:51 | 61117.05 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.168666E+11 | 0.00 | 216.54 | 0.166685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94938.64 | 29-MAY-09:58 | 70858.42 | 29-MAY-09:58 | 0.00 | 0.00 | 0.00 |
June | 0.299349E+11 | 0.00 | 281.95 | 0.286502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95213.19 | 30-JUN-03:01 | 66210.99 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.500557E+11 | 0.00 | 334.14 | 0.430168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118621.86 | 23-JUL-17:42 | 74720.52 | 23-JUL-17:40 | 0.00 | 0.00 | 0.00 |
August | 0.572964E+11 | 0.00 | 371.02 | 0.476424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142769.90 | 06-AUG-14:41 | 81658.25 | 06-AUG-14:41 | 0.00 | 0.00 | 0.00 |
September | 0.349668E+11 | 0.00 | 284.93 | 0.313841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109281.69 | 22-SEP-03:01 | 94368.53 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.461247E+11 | 0.00 | 315.97 | 0.404426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138946.27 | 01-OCT-14:08 | 115928.50 | 15-OCT-13:50 | 0.00 | 0.00 | 0.00 |
November | 0.148675E+11 | 0.00 | 181.98 | 0.145572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87140.85 | 19-NOV-15:18 | 66880.92 | 23-NOV-15:41 | 0.00 | 0.00 | 0.00 |
December | 0.178147E+11 | 0.00 | 166.64 | 0.177461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76464.96 | 25-DEC-15:21 | 76464.96 | 25-DEC-15:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311236E+12 | 2711.48 | 0.282843E+12 | ||||||||||||
Minimum of Months | 0.617350E+10 | 0.00 | 100.89 | 0.608130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53449.83 | 49507.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.572964E+11 | 0.00 | 371.02 | 0.476424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142769.90 | 115928.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.253889E+11 | 0.00 | 245.74 | 0.250809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92952.36 | 17-JAN-13:50 | 90588.08 | 18-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.170168E+11 | 0.00 | 206.15 | 0.163059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88160.98 | 01-FEB-12:00 | 88160.98 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.201379E+11 | 0.00 | 210.59 | 0.184773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111636.28 | 23-MAR-15:00 | 81599.86 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.412176E+11 | 0.00 | 321.11 | 0.381139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113918.07 | 26-APR-11:00 | 101954.38 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.373406E+11 | 0.00 | 352.98 | 0.362859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84371.06 | 04-MAY-14:00 | 76920.87 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.715658E+11 | 0.00 | 434.75 | 0.561433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138072.83 | 29-JUN-13:00 | 84481.72 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.126184E+12 | 0.00 | 529.01 | 0.786914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181310.37 | 31-JUL-15:40 | 107036.67 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.151830E+12 | 0.00 | 568.34 | 0.892678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180903.24 | 18-AUG-15:50 | 108592.07 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.803763E+11 | 0.00 | 421.40 | 0.572875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154983.78 | 22-SEP-11:40 | 132740.67 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.886505E+11 | 0.00 | 423.76 | 0.702723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182547.65 | 04-OCT-05:01 | 144842.92 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.314078E+11 | 0.00 | 286.05 | 0.303660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96863.07 | 28-NOV-14:00 | 96863.07 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.335004E+11 | 0.00 | 267.07 | 0.333950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102540.46 | 05-DEC-15:00 | 102540.46 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724616E+12 | 4266.94 | 0.549687E+12 | ||||||||||||
Minimum of Months | 0.170168E+11 | 0.00 | 206.15 | 0.163059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84371.06 | 76920.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.151830E+12 | 0.00 | 568.34 | 0.892678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182547.65 | 144842.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.212070E+12 | 0.00 | 258.39 | 0.209849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 768884.36 | 18-JAN-13:10 | 768884.36 | 18-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.134597E+12 | 0.00 | 208.66 | 0.129461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 757358.73 | 01-FEB-12:00 | 757358.73 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.151576E+12 | 0.00 | 203.25 | 0.139147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 931281.09 | 23-MAR-15:00 | 674994.78 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.301539E+12 | 0.00 | 289.31 | 0.280861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 943342.35 | 26-APR-11:00 | 844874.80 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.312215E+12 | 0.00 | 341.11 | 0.303379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 759676.04 | 04-MAY-14:00 | 687803.41 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.584103E+12 | 0.00 | 409.14 | 0.459573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1205090.84 | 29-JUN-13:00 | 733064.80 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.970866E+12 | 0.00 | 434.08 | 0.609768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1526903.76 | 31-JUL-15:40 | 907305.32 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.112601E+13 | 0.00 | 456.95 | 0.671722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1534794.98 | 18-AUG-15:50 | 927221.16 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.689112E+12 | 0.00 | 401.92 | 0.493190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1384085.00 | 22-SEP-12:30 | 1268875.81 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.722850E+12 | 0.00 | 401.79 | 0.576312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1610655.60 | 04-OCT-05:01 | 1297783.81 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.234862E+12 | 0.00 | 276.47 | 0.228169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 737921.55 | 28-NOV-14:00 | 737921.55 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.244013E+12 | 0.00 | 255.96 | 0.243444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 785899.36 | 05-DEC-15:00 | 785899.36 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.568381E+13 | 3937.02 | 0.434488E+13 | ||||||||||||
Minimum of Months | 0.134597E+12 | 0.00 | 203.25 | 0.129461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 737921.55 | 674994.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112601E+13 | 0.00 | 456.95 | 0.671722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1610655.60 | 1297783.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.177030E+11 | 0.00 | 223.50 | 0.175532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73448.11 | 18-JAN-13:30 | 73448.11 | 18-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.114480E+11 | 0.00 | 182.00 | 0.109881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69608.88 | 01-FEB-12:00 | 69608.88 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.138614E+11 | 0.00 | 182.54 | 0.126414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99020.56 | 23-MAR-15:00 | 70817.46 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.302137E+11 | 0.00 | 273.32 | 0.280517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103100.47 | 26-APR-13:40 | 99783.17 | 26-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.314069E+11 | 0.00 | 325.60 | 0.304847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88863.56 | 03-MAY-14:00 | 79265.26 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.613774E+11 | 0.00 | 398.94 | 0.479559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137814.94 | 29-JUN-13:00 | 79668.43 | 29-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.104095E+12 | 0.00 | 421.54 | 0.651602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188794.59 | 31-JUL-15:00 | 111031.13 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.119243E+12 | 0.00 | 442.07 | 0.707529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186994.89 | 17-AUG-15:30 | 110605.85 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.686035E+11 | 0.00 | 380.23 | 0.491345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146933.08 | 22-SEP-12:20 | 145453.11 | 29-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.703055E+11 | 0.00 | 381.63 | 0.558158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177055.72 | 05-OCT-05:01 | 144622.56 | 16-OCT-12:10 | 0.00 | 0.00 | 0.00 |
November | 0.197717E+11 | 0.00 | 246.93 | 0.191875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70086.05 | 28-NOV-14:00 | 70086.05 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.202249E+11 | 0.00 | 227.49 | 0.201817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76991.44 | 05-DEC-15:00 | 76991.44 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.568254E+12 | 3685.79 | 0.427907E+12 | ||||||||||||
Minimum of Months | 0.114480E+11 | 0.00 | 182.00 | 0.109881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69608.88 | 69608.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.119243E+12 | 0.00 | 442.07 | 0.707529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188794.59 | 145453.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.317334E+12 | 0.812529E+11 | 742.19 | 0.317068E+12 | 0.265785E+09 | 0.00 | 1.00 | 02-JAN-22:17 | 0.01 | 10-JAN-23:02 | 434971.33 | 03-JAN-01:00 | 434971.33 | 03-JAN-01:00 | 10295.50 | 02-JAN-22:52 | 90975.87 | 03-JAN-01:00 | 0.00 |
February | 0.496957E+12 | 0.119377E+12 | 671.61 | 0.496423E+12 | 0.534209E+09 | 0.00 | 1.00 | 08-FEB-04:42 | 0.01 | 08-FEB-22:15 | 434363.36 | 28-FEB-23:08 | 434363.36 | 28-FEB-23:08 | 24244.21 | 28-FEB-23:21 | 90965.44 | 28-FEB-23:08 | 0.00 |
March | 0.785300E+12 | 0.182554E+12 | 743.84 | 0.784488E+12 | 0.811195E+09 | 0.00 | 1.00 | 01-MAR-00:05 | 0.01 | 01-MAR-04:02 | 429502.89 | 01-MAR-00:10 | 429502.89 | 01-MAR-00:10 | 24986.51 | 01-MAR-02:05 | 90975.67 | 11-MAR-12:00 | 0.00 |
April | 0.989814E+12 | 0.233498E+12 | 720.00 | 0.988923E+12 | 0.891140E+09 | 0.00 | 1.00 | 01-APR-11:50 | 0.91 | 20-APR-06:10 | 385762.26 | 26-APR-14:40 | 384499.50 | 26-APR-13:10 | 4335.56 | 11-APR-18:00 | 125078.82 | 26-APR-13:00 | 0.00 |
May | 0.317356E+12 | 0.808459E+11 | 744.00 | 0.316307E+12 | 0.104890E+10 | 0.00 | 0.36 | 01-MAY-00:05 | 0.31 | 10-MAY-06:10 | 133379.50 | 01-MAY-00:10 | 133379.50 | 01-MAY-00:10 | 3723.18 | 05-MAY-15:10 | 37134.83 | 03-MAY-13:00 | 0.00 |
June | 0.536538E+12 | 0.135545E+12 | 720.00 | 0.533393E+12 | 0.314577E+10 | 0.00 | 0.57 | 29-JUN-11:10 | 0.52 | 01-JUN-06:10 | 212342.75 | 28-JUN-13:00 | 207579.53 | 29-JUN-11:00 | 6036.23 | 29-JUN-19:00 | 65565.52 | 29-JUN-11:00 | 0.00 |
July | 0.793055E+12 | 0.207910E+12 | 744.00 | 0.788400E+12 | 0.465536E+10 | 0.00 | 0.81 | 31-JUL-13:00 | 0.72 | 01-JUL-00:10 | 302599.04 | 19-JUL-16:00 | 296982.19 | 19-JUL-15:00 | 7272.29 | 18-JUL-19:00 | 101014.85 | 31-JUL-13:00 | 0.00 |
August | 0.102902E+13 | 0.271716E+12 | 744.00 | 0.102433E+13 | 0.469103E+10 | 0.00 | 1.00 | 14-AUG-09:50 | 0.91 | 28-AUG-07:00 | 392177.88 | 18-AUG-13:00 | 385298.16 | 18-AUG-15:30 | 7360.26 | 18-AUG-13:00 | 127688.93 | 18-AUG-12:00 | 0.00 |
September | 0.312246E+12 | 0.826446E+11 | 720.00 | 0.308942E+12 | 0.330444E+10 | 0.00 | 0.40 | 29-SEP-13:00 | 0.31 | 20-SEP-06:10 | 135175.98 | 01-SEP-00:08 | 134091.83 | 01-SEP-00:10 | 6399.10 | 22-SEP-13:00 | 55975.38 | 29-SEP-13:00 | 0.00 |
October | 0.556685E+12 | 0.148602E+12 | 744.00 | 0.554736E+12 | 0.194966E+10 | 0.00 | 0.66 | 16-OCT-11:00 | 0.52 | 25-OCT-06:15 | 214156.00 | 03-OCT-15:00 | 213656.71 | 16-OCT-11:00 | 6618.39 | 05-OCT-16:00 | 95796.27 | 16-OCT-11:00 | 0.00 |
November | 0.763553E+12 | 0.181349E+12 | 719.98 | 0.763060E+12 | 0.492895E+09 | 0.00 | 1.00 | 05-NOV-01:27 | 0.11 | 05-NOV-01:29 | 425882.02 | 05-NOV-01:27 | 424424.95 | 05-NOV-01:27 | 15889.49 | 05-NOV-01:28 | 98835.92 | 19-NOV-13:00 | 0.00 |
December | 0.102450E+13 | 0.241002E+12 | 744.00 | 0.102436E+13 | 0.141337E+09 | 0.00 | 1.00 | 04-DEC-09:30 | 0.83 | 16-DEC-03:08 | 422372.08 | 15-DEC-22:25 | 422372.08 | 15-DEC-22:25 | 2788.49 | 08-DEC-17:00 | 122218.35 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.792237E+13 | 0.196630E+13 | 8757.62 | 0.790044E+13 | 0.219317E+11 | ||||||||||||||
Minimum of Months | 0.312246E+12 | 0.808459E+11 | 671.61 | 0.308942E+12 | 0.141337E+09 | 0.00 | 0.36 | 0.01 | 133379.50 | 133379.50 | 2788.49 | 37134.83 | 0.00 | ||||||
Maximum of Months | 0.102902E+13 | 0.271716E+12 | 744.00 | 0.102436E+13 | 0.469103E+10 | 0.00 | 1.00 | 0.91 | 434971.33 | 434971.33 | 24986.51 | 127688.93 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.521444E+10 | 0.132313E+10 | 744.00 | 0.521444E+10 | 0.00 | 0.00 | 0.32 | 18-JAN-16:10 | 0.22 | 09-JAN-07:40 | 2391.53 | 30-JAN-16:40 | 2391.53 | 30-JAN-16:40 | 0.00 | 01-JAN-00:05 | 705.66 | 18-JAN-13:00 | 0.00 |
February | 0.922074E+10 | 0.219140E+10 | 672.00 | 0.922074E+10 | 0.00 | 0.00 | 0.54 | 22-FEB-17:00 | 0.44 | 25-FEB-18:17 | 4296.92 | 22-FEB-17:00 | 4296.92 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1261.76 | 01-FEB-12:00 | 0.00 |
March | 0.151811E+11 | 0.349161E+10 | 744.00 | 0.151811E+11 | 0.00 | 0.00 | 0.76 | 10-MAR-17:00 | 0.65 | 01-MAR-07:40 | 6168.85 | 19-MAR-17:30 | 6168.85 | 19-MAR-17:30 | 0.00 | 01-MAR-00:05 | 1701.62 | 23-MAR-14:00 | 0.00 |
April | 0.195164E+11 | 0.457629E+10 | 720.00 | 0.195164E+11 | 0.00 | 0.00 | 0.98 | 26-APR-13:00 | 0.84 | 01-APR-07:00 | 7989.19 | 16-APR-17:13 | 7989.19 | 16-APR-17:13 | 0.00 | 01-APR-00:10 | 2501.90 | 26-APR-13:00 | 0.00 |
May | 0.545214E+10 | 0.139059E+10 | 744.00 | 0.545214E+10 | 0.00 | 0.00 | 0.32 | 01-MAY-00:05 | 0.23 | 13-MAY-07:00 | 2420.09 | 01-MAY-00:05 | 2420.09 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 676.02 | 03-MAY-13:00 | 0.00 |
June | 0.101596E+11 | 0.256906E+10 | 720.00 | 0.101596E+11 | 0.00 | 0.00 | 0.54 | 29-JUN-16:00 | 0.46 | 01-JUN-06:40 | 4191.77 | 25-JUN-17:42 | 4191.77 | 25-JUN-17:42 | 0.00 | 01-JUN-00:10 | 1249.82 | 29-JUN-11:00 | 0.00 |
July | 0.153749E+11 | 0.404184E+10 | 744.00 | 0.153749E+11 | 0.00 | 0.00 | 0.78 | 19-JUL-15:00 | 0.68 | 07-JUL-21:03 | 6114.37 | 04-JUL-17:57 | 6114.37 | 04-JUL-17:57 | 0.00 | 01-JUL-00:10 | 1979.78 | 31-JUL-13:00 | 0.00 |
August | 0.202141E+11 | 0.535763E+10 | 744.00 | 0.202141E+11 | 0.00 | 0.00 | 0.99 | 17-AUG-14:10 | 0.87 | 28-AUG-07:00 | 8012.14 | 06-AUG-17:57 | 8012.14 | 06-AUG-17:57 | 0.00 | 01-AUG-00:03 | 2586.73 | 17-AUG-14:00 | 0.00 |
September | 0.539140E+10 | 0.143711E+10 | 720.00 | 0.539140E+10 | 0.00 | 0.00 | 0.36 | 29-SEP-16:20 | 0.24 | 16-SEP-07:00 | 2436.06 | 01-SEP-00:08 | 2436.06 | 01-SEP-00:08 | 0.00 | 01-SEP-00:03 | 971.10 | 29-SEP-13:00 | 0.00 |
October | 0.104652E+11 | 0.277213E+10 | 744.00 | 0.104652E+11 | 0.00 | 0.00 | 0.60 | 15-OCT-16:23 | 0.46 | 28-OCT-07:00 | 4391.77 | 15-OCT-16:38 | 4391.77 | 15-OCT-16:38 | 0.00 | 01-OCT-00:10 | 1766.61 | 16-OCT-11:00 | 0.00 |
November | 0.147870E+11 | 0.346753E+10 | 720.00 | 0.147870E+11 | 0.00 | 0.00 | 0.76 | 28-NOV-14:00 | 0.66 | 18-NOV-08:00 | 6096.80 | 06-NOV-16:20 | 6096.80 | 06-NOV-16:20 | 0.00 | 01-NOV-00:10 | 1875.07 | 19-NOV-13:00 | 0.00 |
December | 0.201176E+11 | 0.464875E+10 | 744.00 | 0.201176E+11 | 0.00 | 0.00 | 0.98 | 05-DEC-15:50 | 0.85 | 13-DEC-07:50 | 7987.87 | 25-DEC-16:02 | 7987.87 | 25-DEC-16:02 | 0.00 | 01-DEC-00:10 | 2424.05 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.151095E+12 | 0.372671E+11 | 8760.00 | 0.151095E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.521444E+10 | 0.132313E+10 | 672.00 | 0.521444E+10 | 0.00 | 0.00 | 0.32 | 0.22 | 2391.53 | 2391.53 | 0.00 | 676.02 | 0.00 | ||||||
Maximum of Months | 0.202141E+11 | 0.535763E+10 | 744.00 | 0.202141E+11 | 0.00 | 0.00 | 0.99 | 0.87 | 8012.14 | 8012.14 | 0.00 | 2586.73 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.406590E+11 | 0.104963E+11 | 744.00 | 0.406590E+11 | 0.00 | 0.00 | 0.31 | 18-JAN-16:10 | 0.15 | 08-JAN-07:40 | 21887.99 | 30-JAN-16:50 | 21887.99 | 30-JAN-16:50 | 0.00 | 01-JAN-00:05 | 6375.69 | 24-JAN-16:00 | 0.00 |
February | 0.798546E+11 | 0.191513E+11 | 672.00 | 0.798546E+11 | 0.00 | 0.00 | 0.53 | 22-FEB-17:00 | 0.38 | 25-FEB-18:25 | 40199.36 | 22-FEB-17:00 | 40199.36 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 11607.41 | 01-FEB-12:00 | 0.00 |
March | 0.136817E+12 | 0.316739E+11 | 744.00 | 0.136817E+12 | 0.00 | 0.00 | 0.75 | 10-MAR-17:00 | 0.60 | 30-MAR-06:00 | 57403.94 | 10-MAR-17:00 | 57403.94 | 10-MAR-17:00 | 0.00 | 01-MAR-00:05 | 16060.81 | 23-MAR-14:00 | 0.00 |
April | 0.181721E+12 | 0.427417E+11 | 720.00 | 0.181721E+12 | 0.00 | 0.00 | 0.98 | 26-APR-13:00 | 0.80 | 01-APR-07:00 | 74698.87 | 27-APR-17:30 | 74698.87 | 27-APR-17:30 | 0.00 | 01-APR-00:10 | 23787.79 | 26-APR-13:00 | 0.00 |
May | 0.468730E+11 | 0.120618E+11 | 744.00 | 0.468730E+11 | 0.00 | 0.00 | 0.31 | 03-MAY-16:00 | 0.19 | 13-MAY-07:00 | 21890.62 | 29-MAY-18:07 | 21890.62 | 29-MAY-18:07 | 0.00 | 01-MAY-00:05 | 6212.60 | 03-MAY-13:00 | 0.00 |
June | 0.932183E+11 | 0.236689E+11 | 720.00 | 0.932183E+11 | 0.00 | 0.00 | 0.54 | 29-JUN-16:00 | 0.44 | 01-JUN-06:50 | 39215.18 | 25-JUN-17:58 | 39215.18 | 25-JUN-17:58 | 0.00 | 01-JUN-00:10 | 11762.66 | 29-JUN-11:00 | 0.00 |
July | 0.144719E+12 | 0.380897E+11 | 744.00 | 0.144719E+12 | 0.00 | 0.00 | 0.78 | 19-JUL-15:00 | 0.67 | 06-JUL-07:00 | 57372.48 | 04-JUL-17:55 | 57372.48 | 04-JUL-17:55 | 0.00 | 01-JUL-00:10 | 18841.70 | 31-JUL-13:00 | 0.00 |
August | 0.191211E+12 | 0.507083E+11 | 744.00 | 0.191211E+12 | 0.00 | 0.00 | 1.00 | 17-AUG-14:00 | 0.86 | 28-AUG-07:00 | 74936.69 | 31-AUG-17:00 | 74936.69 | 31-AUG-17:00 | 0.00 | 01-AUG-00:03 | 24602.79 | 17-AUG-14:00 | 0.00 |
September | 0.472216E+11 | 0.126889E+11 | 720.00 | 0.472216E+11 | 0.00 | 0.00 | 0.36 | 29-SEP-16:30 | 0.22 | 02-SEP-07:00 | 22961.86 | 29-SEP-16:30 | 22961.86 | 29-SEP-16:30 | 0.00 | 01-SEP-00:03 | 9048.39 | 29-SEP-13:00 | 0.00 |
October | 0.944099E+11 | 0.251783E+11 | 744.00 | 0.944099E+11 | 0.00 | 0.00 | 0.60 | 16-OCT-11:10 | 0.42 | 28-OCT-07:00 | 40805.76 | 17-OCT-16:40 | 40805.76 | 17-OCT-16:40 | 0.00 | 01-OCT-00:10 | 16675.14 | 16-OCT-11:00 | 0.00 |
November | 0.133603E+12 | 0.315282E+11 | 720.00 | 0.133603E+12 | 0.00 | 0.00 | 0.75 | 28-NOV-14:10 | 0.62 | 05-NOV-07:00 | 57536.13 | 12-NOV-16:24 | 57536.13 | 12-NOV-16:24 | 0.00 | 01-NOV-00:10 | 16889.66 | 28-NOV-14:00 | 0.00 |
December | 0.183036E+12 | 0.425666E+11 | 744.00 | 0.183036E+12 | 0.00 | 0.00 | 0.97 | 05-DEC-15:50 | 0.80 | 31-DEC-07:20 | 74445.98 | 18-DEC-16:20 | 74445.98 | 18-DEC-16:20 | 0.00 | 01-DEC-00:10 | 22695.17 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.137335E+13 | 0.340554E+12 | 8760.00 | 0.137335E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.406590E+11 | 0.104963E+11 | 672.00 | 0.406590E+11 | 0.00 | 0.00 | 0.31 | 0.15 | 21887.99 | 21887.99 | 0.00 | 6212.60 | 0.00 | ||||||
Maximum of Months | 0.191211E+12 | 0.507083E+11 | 744.00 | 0.191211E+12 | 0.00 | 0.00 | 1.00 | 0.86 | 74936.69 | 74936.69 | 0.00 | 24602.79 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.275023E+10 | 0.732418E+09 | 683.00 | 0.275023E+10 | 0.00 | 0.00 | 0.30 | 18-JAN-16:10 | 0.00 | 01-JAN-00:05 | 2151.75 | 26-JAN-16:10 | 2151.75 | 26-JAN-16:10 | 0.00 | 01-JAN-00:05 | 636.78 | 24-JAN-16:00 | 0.00 |
February | 0.699721E+10 | 0.170152E+10 | 672.00 | 0.699721E+10 | 0.00 | 0.00 | 0.52 | 03-FEB-16:40 | 0.26 | 26-FEB-07:40 | 4022.87 | 22-FEB-17:00 | 4022.87 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1136.04 | 01-FEB-12:00 | 0.00 |
March | 0.127654E+11 | 0.298704E+10 | 744.00 | 0.127654E+11 | 0.00 | 0.00 | 0.75 | 10-MAR-17:00 | 0.50 | 05-MAR-07:10 | 5782.75 | 10-MAR-17:00 | 5782.75 | 10-MAR-17:00 | 0.00 | 01-MAR-00:05 | 1621.24 | 23-MAR-14:00 | 0.00 |
April | 0.176711E+11 | 0.418827E+10 | 720.00 | 0.176711E+11 | 0.00 | 0.00 | 0.97 | 26-APR-13:10 | 0.72 | 01-APR-05:15 | 7534.31 | 26-APR-17:10 | 7534.31 | 26-APR-17:10 | 0.00 | 01-APR-00:10 | 2403.36 | 26-APR-13:00 | 0.00 |
May | 0.418950E+10 | 0.109203E+10 | 743.33 | 0.418950E+10 | 0.00 | 0.00 | 0.31 | 03-MAY-16:00 | 0.00 | 14-MAY-05:05 | 2260.66 | 29-MAY-17:25 | 2260.66 | 29-MAY-17:25 | 0.00 | 01-MAY-00:05 | 653.38 | 03-MAY-13:00 | 0.00 |
June | 0.907537E+10 | 0.231897E+10 | 720.00 | 0.907537E+10 | 0.00 | 0.00 | 0.54 | 29-JUN-16:00 | 0.38 | 01-JUN-06:50 | 4051.16 | 25-JUN-17:35 | 4051.16 | 25-JUN-17:35 | 0.00 | 01-JUN-00:10 | 1190.66 | 29-JUN-11:00 | 0.00 |
July | 0.143590E+11 | 0.379591E+10 | 744.00 | 0.143590E+11 | 0.00 | 0.00 | 0.78 | 19-JUL-15:00 | 0.63 | 06-JUL-07:00 | 5892.50 | 04-JUL-17:45 | 5892.50 | 04-JUL-17:45 | 0.00 | 01-JUL-00:10 | 1915.19 | 31-JUL-13:00 | 0.00 |
August | 0.189692E+11 | 0.505374E+10 | 744.00 | 0.189692E+11 | 0.00 | 0.00 | 0.99 | 17-AUG-14:10 | 0.83 | 06-AUG-05:00 | 7624.60 | 20-AUG-17:28 | 7624.60 | 20-AUG-17:28 | 0.00 | 01-AUG-00:03 | 2490.84 | 17-AUG-14:00 | 0.00 |
September | 0.437975E+10 | 0.119098E+10 | 720.00 | 0.437975E+10 | 0.00 | 0.00 | 0.36 | 29-SEP-16:20 | 0.15 | 03-SEP-06:50 | 2378.30 | 29-SEP-16:30 | 2378.30 | 29-SEP-16:30 | 0.00 | 01-SEP-00:03 | 944.18 | 29-SEP-13:00 | 0.00 |
October | 0.891133E+10 | 0.240326E+10 | 744.00 | 0.891133E+10 | 0.00 | 0.00 | 0.60 | 15-OCT-16:23 | 0.32 | 29-OCT-07:15 | 4196.41 | 15-OCT-16:36 | 4196.41 | 15-OCT-16:36 | 0.00 | 01-OCT-00:10 | 1688.04 | 16-OCT-11:10 | 0.00 |
November | 0.123940E+11 | 0.295928E+10 | 720.00 | 0.123940E+11 | 0.00 | 0.00 | 0.73 | 28-NOV-14:30 | 0.49 | 05-NOV-07:20 | 5708.34 | 07-NOV-16:20 | 5708.34 | 07-NOV-16:20 | 0.00 | 01-NOV-00:10 | 1684.63 | 28-NOV-14:00 | 0.00 |
December | 0.170821E+11 | 0.402411E+10 | 744.00 | 0.170821E+11 | 0.00 | 0.00 | 0.96 | 05-DEC-15:50 | 0.67 | 31-DEC-07:50 | 7441.14 | 19-DEC-16:20 | 7441.14 | 19-DEC-16:20 | 0.00 | 01-DEC-00:10 | 2262.14 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.129544E+12 | 0.324475E+11 | 8698.33 | 0.129544E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.275023E+10 | 0.732418E+09 | 672.00 | 0.275023E+10 | 0.00 | 0.00 | 0.30 | 0.00 | 2151.75 | 2151.75 | 0.00 | 636.78 | 0.00 | ||||||
Maximum of Months | 0.189692E+11 | 0.505374E+10 | 744.00 | 0.189692E+11 | 0.00 | 0.00 | 0.99 | 0.83 | 7624.60 | 7624.60 | 0.00 | 2490.84 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.90 | 0.00 | 77.90 | 27.98 | 366.22 | 0.00 | 0.00 | 744.00 |
February | 97.79 | 0.00 | 97.79 | 34.02 | 335.51 | 0.00 | 0.00 | 672.00 |
March | 119.83 | 0.00 | 119.83 | 55.82 | 339.83 | 0.00 | 0.00 | 744.00 |
April | 138.05 | 0.53 | 137.53 | 87.37 | 264.94 | 0.00 | 0.00 | 720.00 |
May | 165.88 | 7.70 | 158.18 | 109.01 | 226.00 | 0.00 | 0.00 | 744.00 |
June | 176.73 | 17.24 | 159.49 | 140.84 | 174.54 | 0.00 | 0.00 | 720.00 |
July | 167.34 | 13.99 | 153.35 | 154.03 | 151.38 | 0.00 | 0.00 | 744.00 |
August | 138.99 | 2.77 | 136.22 | 132.23 | 162.65 | 0.00 | 0.00 | 744.00 |
September | 117.65 | 0.02 | 117.63 | 103.37 | 198.04 | 0.00 | 0.00 | 720.00 |
October | 93.33 | 0.00 | 93.33 | 89.41 | 224.78 | 0.00 | 0.00 | 744.00 |
November | 84.50 | 0.00 | 84.50 | 33.73 | 334.52 | 0.00 | 0.00 | 720.00 |
December | 72.52 | 0.00 | 72.52 | 22.76 | 375.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.97 | 3.54 | 117.44 | 82.85 | 262.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.52 | 0.00 | 72.52 | 22.76 | 151.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 176.73 | 17.24 | 159.49 | 154.03 | 375.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.90 | 0.00 | 77.90 | 27.98 | 366.22 | 0.00 | 0.00 | 744.00 |
February | 97.79 | 0.00 | 97.79 | 34.02 | 335.51 | 0.00 | 0.00 | 672.00 |
March | 119.83 | 0.00 | 119.83 | 55.82 | 339.83 | 0.00 | 0.00 | 744.00 |
April | 138.05 | 0.53 | 137.53 | 87.37 | 264.94 | 0.00 | 0.00 | 720.00 |
May | 165.87 | 7.70 | 158.18 | 109.01 | 226.00 | 0.00 | 0.00 | 744.00 |
June | 176.73 | 17.24 | 159.49 | 140.84 | 174.54 | 0.00 | 0.00 | 720.00 |
July | 167.34 | 13.99 | 153.35 | 154.02 | 151.38 | 0.00 | 0.00 | 744.00 |
August | 138.99 | 2.77 | 136.22 | 132.23 | 162.65 | 0.00 | 0.00 | 744.00 |
September | 117.65 | 0.02 | 117.63 | 103.37 | 198.04 | 0.00 | 0.00 | 720.00 |
October | 93.32 | 0.00 | 93.32 | 89.41 | 224.78 | 0.00 | 0.00 | 744.00 |
November | 84.50 | 0.00 | 84.50 | 33.73 | 334.52 | 0.00 | 0.00 | 720.00 |
December | 72.52 | 0.00 | 72.52 | 22.76 | 375.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.97 | 3.54 | 117.43 | 82.85 | 262.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.52 | 0.00 | 72.52 | 22.76 | 151.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 176.73 | 17.24 | 159.49 | 154.02 | 375.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.90 | 0.00 | 77.90 | 27.98 | 366.22 | 0.00 | 0.00 | 744.00 |
February | 97.79 | 0.00 | 97.79 | 34.02 | 335.51 | 0.00 | 0.00 | 672.00 |
March | 119.83 | 0.00 | 119.83 | 55.82 | 339.83 | 0.00 | 0.00 | 744.00 |
April | 138.05 | 0.53 | 137.53 | 87.37 | 264.94 | 0.00 | 0.00 | 720.00 |
May | 165.87 | 7.70 | 158.18 | 109.01 | 226.00 | 0.00 | 0.00 | 744.00 |
June | 176.73 | 17.24 | 159.49 | 140.84 | 174.54 | 0.00 | 0.00 | 720.00 |
July | 167.34 | 13.99 | 153.35 | 154.03 | 151.38 | 0.00 | 0.00 | 744.00 |
August | 138.99 | 2.77 | 136.22 | 132.23 | 162.65 | 0.00 | 0.00 | 744.00 |
September | 117.65 | 0.02 | 117.63 | 103.37 | 198.04 | 0.00 | 0.00 | 720.00 |
October | 93.33 | 0.00 | 93.33 | 89.41 | 224.78 | 0.00 | 0.00 | 744.00 |
November | 84.50 | 0.00 | 84.50 | 33.73 | 334.52 | 0.00 | 0.00 | 720.00 |
December | 72.52 | 0.00 | 72.52 | 22.76 | 375.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.97 | 3.54 | 117.43 | 82.85 | 262.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.52 | 0.00 | 72.52 | 22.76 | 151.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 176.73 | 17.24 | 159.49 | 154.03 | 375.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.90 | 0.00 | 77.90 | 27.98 | 366.22 | 0.00 | 0.00 | 744.00 |
February | 97.79 | 0.00 | 97.79 | 34.02 | 335.51 | 0.00 | 0.00 | 672.00 |
March | 119.83 | 0.00 | 119.83 | 55.82 | 339.83 | 0.00 | 0.00 | 744.00 |
April | 138.05 | 0.53 | 137.53 | 87.37 | 264.94 | 0.00 | 0.00 | 720.00 |
May | 165.87 | 7.70 | 158.18 | 109.01 | 226.00 | 0.00 | 0.00 | 744.00 |
June | 176.73 | 17.24 | 159.49 | 140.84 | 174.54 | 0.00 | 0.00 | 720.00 |
July | 167.34 | 13.99 | 153.35 | 154.02 | 151.38 | 0.00 | 0.00 | 744.00 |
August | 138.99 | 2.77 | 136.22 | 132.23 | 162.65 | 0.00 | 0.00 | 744.00 |
September | 117.65 | 0.02 | 117.63 | 103.37 | 198.04 | 0.00 | 0.00 | 720.00 |
October | 93.32 | 0.00 | 93.32 | 89.41 | 224.78 | 0.00 | 0.00 | 744.00 |
November | 84.50 | 0.00 | 84.50 | 33.73 | 334.52 | 0.00 | 0.00 | 720.00 |
December | 72.52 | 0.00 | 72.52 | 22.76 | 375.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.97 | 3.54 | 117.43 | 82.85 | 262.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.52 | 0.00 | 72.52 | 22.76 | 151.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 176.73 | 17.24 | 159.49 | 154.02 | 375.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.90 | 0.00 | 77.90 | 27.98 | 366.21 | 0.00 | 0.00 | 744.00 |
February | 97.78 | 0.00 | 97.78 | 34.01 | 335.50 | 0.00 | 0.00 | 672.00 |
March | 119.82 | 0.00 | 119.82 | 55.81 | 339.81 | 0.00 | 0.00 | 744.00 |
April | 138.05 | 0.53 | 137.52 | 87.37 | 264.93 | 0.00 | 0.00 | 720.00 |
May | 165.87 | 7.70 | 158.17 | 109.00 | 225.99 | 0.00 | 0.00 | 744.00 |
June | 176.73 | 17.24 | 159.49 | 140.83 | 174.53 | 0.00 | 0.00 | 720.00 |
July | 167.33 | 13.98 | 153.34 | 154.02 | 151.38 | 0.00 | 0.00 | 744.00 |
August | 138.98 | 2.77 | 136.21 | 132.22 | 162.64 | 0.00 | 0.00 | 744.00 |
September | 117.65 | 0.02 | 117.63 | 103.37 | 198.03 | 0.00 | 0.00 | 720.00 |
October | 93.32 | 0.00 | 93.32 | 89.41 | 224.77 | 0.00 | 0.00 | 744.00 |
November | 84.50 | 0.00 | 84.50 | 33.73 | 334.51 | 0.00 | 0.00 | 720.00 |
December | 72.52 | 0.00 | 72.52 | 22.76 | 375.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.97 | 3.54 | 117.43 | 82.85 | 262.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.52 | 0.00 | 72.52 | 22.76 | 151.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 176.73 | 17.24 | 159.49 | 154.02 | 375.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 233.48 | 124.87 | 108.61 | 231.70 | 363.44 | 0.00 | 0.00 | 744.00 |
February | 246.29 | 112.83 | 133.47 | 233.25 | 333.17 | 0.00 | 0.00 | 672.00 |
March | 299.20 | 133.32 | 165.88 | 305.67 | 335.37 | 0.00 | 0.00 | 744.00 |
April | 382.52 | 191.85 | 190.67 | 459.99 | 263.21 | 0.00 | 0.00 | 720.00 |
May | 360.96 | 150.63 | 210.33 | 413.69 | 241.55 | 0.00 | 0.00 | 744.00 |
June | 358.71 | 155.63 | 203.08 | 444.33 | 190.41 | 0.00 | 0.00 | 720.00 |
July | 406.45 | 201.97 | 204.48 | 553.98 | 161.94 | 0.00 | 0.00 | 744.00 |
August | 401.41 | 213.22 | 188.20 | 557.05 | 163.14 | 0.00 | 0.00 | 744.00 |
September | 292.27 | 133.93 | 158.34 | 373.10 | 204.03 | 0.00 | 0.00 | 720.00 |
October | 258.70 | 132.97 | 125.74 | 338.85 | 224.48 | 0.00 | 0.00 | 744.00 |
November | 235.83 | 119.81 | 116.02 | 238.44 | 328.70 | 0.00 | 0.00 | 720.00 |
December | 224.98 | 125.00 | 99.98 | 220.94 | 361.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 308.81 | 149.96 | 158.85 | 365.16 | 263.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.98 | 112.83 | 99.98 | 220.94 | 161.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 406.45 | 213.22 | 210.33 | 557.05 | 363.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 233.48 | 124.87 | 108.61 | 231.70 | 363.44 | 0.00 | 0.00 | 744.00 |
February | 246.29 | 112.83 | 133.47 | 233.25 | 333.17 | 0.00 | 0.00 | 672.00 |
March | 299.20 | 133.32 | 165.88 | 305.67 | 335.37 | 0.00 | 0.00 | 744.00 |
April | 382.52 | 191.85 | 190.67 | 459.99 | 263.21 | 0.00 | 0.00 | 720.00 |
May | 360.96 | 150.63 | 210.33 | 413.69 | 241.55 | 0.00 | 0.00 | 744.00 |
June | 358.71 | 155.63 | 203.08 | 444.33 | 190.41 | 0.00 | 0.00 | 720.00 |
July | 406.45 | 201.97 | 204.48 | 553.98 | 161.94 | 0.00 | 0.00 | 744.00 |
August | 401.41 | 213.22 | 188.20 | 557.05 | 163.14 | 0.00 | 0.00 | 744.00 |
September | 292.27 | 133.93 | 158.34 | 373.10 | 204.03 | 0.00 | 0.00 | 720.00 |
October | 258.70 | 132.97 | 125.74 | 338.85 | 224.48 | 0.00 | 0.00 | 744.00 |
November | 235.83 | 119.81 | 116.02 | 238.44 | 328.70 | 0.00 | 0.00 | 720.00 |
December | 224.98 | 125.00 | 99.98 | 220.94 | 361.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 308.81 | 149.96 | 158.85 | 365.16 | 263.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.98 | 112.83 | 99.98 | 220.94 | 161.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 406.45 | 213.22 | 210.33 | 557.05 | 363.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 233.47 | 124.86 | 108.61 | 231.70 | 363.43 | 0.00 | 0.00 | 744.00 |
February | 246.29 | 112.82 | 133.47 | 233.24 | 333.16 | 0.00 | 0.00 | 672.00 |
March | 299.20 | 133.32 | 165.88 | 305.66 | 335.37 | 0.00 | 0.00 | 744.00 |
April | 382.51 | 191.85 | 190.67 | 459.99 | 263.21 | 0.00 | 0.00 | 720.00 |
May | 360.95 | 150.63 | 210.33 | 413.68 | 241.55 | 0.00 | 0.00 | 744.00 |
June | 358.70 | 155.63 | 203.08 | 444.32 | 190.41 | 0.00 | 0.00 | 720.00 |
July | 406.44 | 201.96 | 204.48 | 553.97 | 161.94 | 0.00 | 0.00 | 744.00 |
August | 401.41 | 213.22 | 188.19 | 557.04 | 163.14 | 0.00 | 0.00 | 744.00 |
September | 292.26 | 133.93 | 158.33 | 373.09 | 204.02 | 0.00 | 0.00 | 720.00 |
October | 258.70 | 132.96 | 125.73 | 338.85 | 224.48 | 0.00 | 0.00 | 744.00 |
November | 235.83 | 119.81 | 116.02 | 238.43 | 328.69 | 0.00 | 0.00 | 720.00 |
December | 224.98 | 125.00 | 99.98 | 220.94 | 361.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 308.81 | 149.96 | 158.85 | 365.16 | 263.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.98 | 112.82 | 99.98 | 220.94 | 161.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 406.44 | 213.22 | 210.33 | 557.04 | 363.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.23 | 377.25 | 136.98 | 711.05 | 327.28 | 0.00 | 0.00 | 744.00 |
February | 404.12 | 248.94 | 155.18 | 501.17 | 305.05 | 0.00 | 0.00 | 672.00 |
March | 322.06 | 155.54 | 166.52 | 361.77 | 322.48 | 0.00 | 0.00 | 744.00 |
April | 269.02 | 102.51 | 166.51 | 274.96 | 261.91 | 0.00 | 0.00 | 720.00 |
May | 191.56 | 23.49 | 168.06 | 152.67 | 234.11 | 0.00 | 0.00 | 744.00 |
June | 168.04 | 10.06 | 157.98 | 141.51 | 183.91 | 0.00 | 0.00 | 720.00 |
July | 177.98 | 19.93 | 158.04 | 172.96 | 157.91 | 0.00 | 0.00 | 744.00 |
August | 228.67 | 72.05 | 156.63 | 256.21 | 164.73 | 0.00 | 0.00 | 744.00 |
September | 318.27 | 161.23 | 157.04 | 411.06 | 197.05 | 0.00 | 0.00 | 720.00 |
October | 404.92 | 270.71 | 134.21 | 584.12 | 216.12 | 0.00 | 0.00 | 744.00 |
November | 492.23 | 347.54 | 144.68 | 670.06 | 303.47 | 0.00 | 0.00 | 720.00 |
December | 549.34 | 418.15 | 131.19 | 767.99 | 332.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 336.42 | 183.73 | 152.69 | 416.90 | 250.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 168.04 | 10.06 | 131.19 | 141.51 | 157.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 549.34 | 418.15 | 168.06 | 767.99 | 332.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.23 | 377.25 | 136.98 | 711.04 | 327.28 | 0.00 | 0.00 | 744.00 |
February | 404.11 | 248.94 | 155.17 | 501.17 | 305.05 | 0.00 | 0.00 | 672.00 |
March | 322.06 | 155.54 | 166.52 | 361.77 | 322.48 | 0.00 | 0.00 | 744.00 |
April | 269.02 | 102.51 | 166.51 | 274.96 | 261.91 | 0.00 | 0.00 | 720.00 |
May | 191.56 | 23.49 | 168.06 | 152.67 | 234.11 | 0.00 | 0.00 | 744.00 |
June | 168.04 | 10.06 | 157.98 | 141.51 | 183.91 | 0.00 | 0.00 | 720.00 |
July | 177.97 | 19.93 | 158.04 | 172.96 | 157.91 | 0.00 | 0.00 | 744.00 |
August | 228.67 | 72.05 | 156.63 | 256.20 | 164.73 | 0.00 | 0.00 | 744.00 |
September | 318.27 | 161.23 | 157.04 | 411.06 | 197.05 | 0.00 | 0.00 | 720.00 |
October | 404.91 | 270.70 | 134.21 | 584.12 | 216.12 | 0.00 | 0.00 | 744.00 |
November | 492.23 | 347.54 | 144.68 | 670.05 | 303.47 | 0.00 | 0.00 | 720.00 |
December | 549.34 | 418.15 | 131.19 | 767.98 | 332.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 336.42 | 183.73 | 152.69 | 416.90 | 250.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 168.04 | 10.06 | 131.19 | 141.51 | 157.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 549.34 | 418.15 | 168.06 | 767.98 | 332.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.23 | 377.25 | 136.98 | 711.05 | 327.28 | 0.00 | 0.00 | 744.00 |
February | 404.12 | 248.94 | 155.18 | 501.17 | 305.05 | 0.00 | 0.00 | 672.00 |
March | 322.06 | 155.54 | 166.52 | 361.77 | 322.48 | 0.00 | 0.00 | 744.00 |
April | 269.02 | 102.51 | 166.51 | 274.96 | 261.91 | 0.00 | 0.00 | 720.00 |
May | 191.56 | 23.49 | 168.06 | 152.67 | 234.11 | 0.00 | 0.00 | 744.00 |
June | 168.04 | 10.06 | 157.98 | 141.51 | 183.91 | 0.00 | 0.00 | 720.00 |
July | 177.98 | 19.93 | 158.04 | 172.96 | 157.91 | 0.00 | 0.00 | 744.00 |
August | 228.67 | 72.05 | 156.63 | 256.21 | 164.73 | 0.00 | 0.00 | 744.00 |
September | 318.27 | 161.23 | 157.04 | 411.06 | 197.05 | 0.00 | 0.00 | 720.00 |
October | 404.92 | 270.71 | 134.21 | 584.12 | 216.12 | 0.00 | 0.00 | 744.00 |
November | 492.23 | 347.54 | 144.68 | 670.06 | 303.47 | 0.00 | 0.00 | 720.00 |
December | 549.34 | 418.15 | 131.19 | 767.99 | 332.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 336.42 | 183.73 | 152.69 | 416.90 | 250.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 168.04 | 10.06 | 131.19 | 141.51 | 157.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 549.34 | 418.15 | 168.06 | 767.99 | 332.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.23 | 377.25 | 136.98 | 711.04 | 327.28 | 0.00 | 0.00 | 744.00 |
February | 404.11 | 248.94 | 155.17 | 501.17 | 305.05 | 0.00 | 0.00 | 672.00 |
March | 322.06 | 155.54 | 166.52 | 361.77 | 322.48 | 0.00 | 0.00 | 744.00 |
April | 269.02 | 102.51 | 166.51 | 274.96 | 261.91 | 0.00 | 0.00 | 720.00 |
May | 191.56 | 23.49 | 168.06 | 152.67 | 234.11 | 0.00 | 0.00 | 744.00 |
June | 168.04 | 10.06 | 157.98 | 141.51 | 183.91 | 0.00 | 0.00 | 720.00 |
July | 177.97 | 19.93 | 158.04 | 172.96 | 157.91 | 0.00 | 0.00 | 744.00 |
August | 228.67 | 72.05 | 156.63 | 256.20 | 164.73 | 0.00 | 0.00 | 744.00 |
September | 318.27 | 161.23 | 157.04 | 411.06 | 197.05 | 0.00 | 0.00 | 720.00 |
October | 404.91 | 270.70 | 134.21 | 584.12 | 216.12 | 0.00 | 0.00 | 744.00 |
November | 492.23 | 347.54 | 144.68 | 670.05 | 303.47 | 0.00 | 0.00 | 720.00 |
December | 549.34 | 418.15 | 131.19 | 767.98 | 332.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 336.42 | 183.73 | 152.69 | 416.90 | 250.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 168.04 | 10.06 | 131.19 | 141.51 | 157.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 549.34 | 418.15 | 168.06 | 767.98 | 332.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.21 | 377.23 | 136.98 | 711.02 | 327.27 | 0.00 | 0.00 | 744.00 |
February | 404.10 | 248.93 | 155.17 | 501.15 | 305.04 | 0.00 | 0.00 | 672.00 |
March | 322.05 | 155.54 | 166.51 | 361.76 | 322.46 | 0.00 | 0.00 | 744.00 |
April | 269.01 | 102.50 | 166.51 | 274.95 | 261.90 | 0.00 | 0.00 | 720.00 |
May | 191.55 | 23.49 | 168.06 | 152.66 | 234.10 | 0.00 | 0.00 | 744.00 |
June | 168.03 | 10.06 | 157.97 | 141.50 | 183.91 | 0.00 | 0.00 | 720.00 |
July | 177.97 | 19.93 | 158.04 | 172.95 | 157.90 | 0.00 | 0.00 | 744.00 |
August | 228.66 | 72.04 | 156.62 | 256.20 | 164.72 | 0.00 | 0.00 | 744.00 |
September | 318.26 | 161.23 | 157.03 | 411.04 | 197.04 | 0.00 | 0.00 | 720.00 |
October | 404.90 | 270.69 | 134.20 | 584.10 | 216.11 | 0.00 | 0.00 | 744.00 |
November | 492.21 | 347.53 | 144.68 | 670.03 | 303.46 | 0.00 | 0.00 | 720.00 |
December | 549.32 | 418.14 | 131.18 | 767.96 | 332.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 336.41 | 183.72 | 152.68 | 416.89 | 250.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 168.03 | 10.06 | 131.18 | 141.50 | 157.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 549.32 | 418.14 | 168.06 | 767.96 | 332.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.23 | 112.08 | 110.15 | 229.81 | 408.66 | 0.00 | 0.00 | 744.00 |
February | 265.12 | 122.39 | 142.73 | 266.19 | 388.93 | 0.00 | 0.00 | 672.00 |
March | 303.92 | 134.47 | 169.45 | 309.22 | 401.32 | 0.00 | 0.00 | 744.00 |
April | 418.96 | 218.16 | 200.80 | 502.24 | 328.82 | 0.00 | 0.00 | 720.00 |
May | 411.53 | 190.08 | 221.45 | 487.13 | 273.83 | 0.00 | 0.00 | 744.00 |
June | 435.96 | 217.96 | 218.00 | 551.01 | 225.65 | 0.00 | 0.00 | 720.00 |
July | 461.50 | 246.94 | 214.57 | 619.22 | 200.77 | 0.00 | 0.00 | 744.00 |
August | 433.00 | 234.67 | 198.33 | 586.72 | 213.17 | 0.00 | 0.00 | 744.00 |
September | 370.75 | 198.40 | 172.36 | 489.97 | 232.74 | 0.00 | 0.00 | 720.00 |
October | 283.40 | 154.73 | 128.68 | 375.43 | 270.11 | 0.00 | 0.00 | 744.00 |
November | 255.99 | 133.90 | 122.09 | 273.36 | 396.17 | 0.00 | 0.00 | 720.00 |
December | 226.09 | 121.26 | 104.83 | 231.39 | 450.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 341.00 | 173.97 | 167.03 | 410.84 | 315.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 222.23 | 112.08 | 104.83 | 229.81 | 200.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 461.50 | 246.94 | 221.45 | 619.22 | 450.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.23 | 112.08 | 110.15 | 229.81 | 408.66 | 0.00 | 0.00 | 744.00 |
February | 265.12 | 122.39 | 142.73 | 266.19 | 388.93 | 0.00 | 0.00 | 672.00 |
March | 303.92 | 134.47 | 169.45 | 309.22 | 401.32 | 0.00 | 0.00 | 744.00 |
April | 418.96 | 218.16 | 200.80 | 502.24 | 328.82 | 0.00 | 0.00 | 720.00 |
May | 411.53 | 190.08 | 221.45 | 487.13 | 273.83 | 0.00 | 0.00 | 744.00 |
June | 435.96 | 217.96 | 218.00 | 551.01 | 225.65 | 0.00 | 0.00 | 720.00 |
July | 461.50 | 246.94 | 214.57 | 619.22 | 200.77 | 0.00 | 0.00 | 744.00 |
August | 433.00 | 234.67 | 198.33 | 586.72 | 213.17 | 0.00 | 0.00 | 744.00 |
September | 370.75 | 198.40 | 172.36 | 489.97 | 232.74 | 0.00 | 0.00 | 720.00 |
October | 283.40 | 154.73 | 128.68 | 375.43 | 270.11 | 0.00 | 0.00 | 744.00 |
November | 255.99 | 133.90 | 122.09 | 273.36 | 396.17 | 0.00 | 0.00 | 720.00 |
December | 226.09 | 121.26 | 104.83 | 231.39 | 450.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 341.00 | 173.97 | 167.03 | 410.84 | 315.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 222.23 | 112.08 | 104.83 | 229.81 | 200.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 461.50 | 246.94 | 221.45 | 619.22 | 450.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.23 | 112.08 | 110.15 | 229.80 | 408.65 | 0.00 | 0.00 | 744.00 |
February | 265.12 | 122.39 | 142.73 | 266.18 | 388.92 | 0.00 | 0.00 | 672.00 |
March | 303.92 | 134.47 | 169.45 | 309.21 | 401.31 | 0.00 | 0.00 | 744.00 |
April | 418.96 | 218.16 | 200.80 | 502.24 | 328.81 | 0.00 | 0.00 | 720.00 |
May | 411.52 | 190.08 | 221.45 | 487.12 | 273.82 | 0.00 | 0.00 | 744.00 |
June | 435.95 | 217.96 | 218.00 | 551.00 | 225.65 | 0.00 | 0.00 | 720.00 |
July | 461.49 | 246.93 | 214.56 | 619.20 | 200.76 | 0.00 | 0.00 | 744.00 |
August | 433.00 | 234.67 | 198.33 | 586.71 | 213.16 | 0.00 | 0.00 | 744.00 |
September | 370.75 | 198.39 | 172.35 | 489.96 | 232.74 | 0.00 | 0.00 | 720.00 |
October | 283.40 | 154.72 | 128.67 | 375.43 | 270.11 | 0.00 | 0.00 | 744.00 |
November | 255.99 | 133.89 | 122.09 | 273.36 | 396.16 | 0.00 | 0.00 | 720.00 |
December | 226.08 | 121.26 | 104.82 | 231.39 | 450.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 340.99 | 173.97 | 167.02 | 410.83 | 315.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 222.23 | 112.08 | 104.82 | 229.80 | 200.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 461.49 | 246.93 | 221.45 | 619.20 | 450.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.51 | 0.00 | 389.51 | 171.55 | 1660.40 | 0.00 | 0.00 | 744.00 |
February | 488.94 | 0.00 | 488.94 | 203.48 | 1504.80 | 0.00 | 0.00 | 672.00 |
March | 599.15 | 0.00 | 599.15 | 316.34 | 1540.07 | 0.00 | 0.00 | 744.00 |
April | 690.26 | 2.63 | 687.64 | 475.58 | 1213.37 | 0.00 | 0.00 | 720.00 |
May | 829.37 | 38.49 | 790.89 | 570.17 | 1062.29 | 0.00 | 0.00 | 744.00 |
June | 883.67 | 86.20 | 797.47 | 725.67 | 820.91 | 0.00 | 0.00 | 720.00 |
July | 836.69 | 69.93 | 766.76 | 795.01 | 723.69 | 0.00 | 0.00 | 744.00 |
August | 694.93 | 13.83 | 681.10 | 686.58 | 768.52 | 0.00 | 0.00 | 744.00 |
September | 588.26 | 0.09 | 588.17 | 535.32 | 927.51 | 0.00 | 0.00 | 720.00 |
October | 466.63 | 0.00 | 466.63 | 477.11 | 1027.77 | 0.00 | 0.00 | 744.00 |
November | 422.50 | 0.00 | 422.50 | 204.29 | 1506.20 | 0.00 | 0.00 | 720.00 |
December | 362.60 | 0.00 | 362.60 | 155.58 | 1664.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 604.87 | 17.69 | 587.18 | 444.56 | 1200.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 362.60 | 0.00 | 362.60 | 155.58 | 723.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 883.67 | 86.20 | 797.47 | 795.01 | 1664.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 700.42 | 374.59 | 325.83 | 720.41 | 1006.45 | 0.00 | 0.00 | 744.00 |
February | 738.87 | 338.47 | 400.40 | 721.16 | 918.99 | 0.00 | 0.00 | 672.00 |
March | 897.60 | 399.96 | 497.64 | 934.93 | 940.87 | 0.00 | 0.00 | 744.00 |
April | 1147.55 | 575.55 | 572.00 | 1380.67 | 762.46 | 0.00 | 0.00 | 720.00 |
May | 1082.87 | 451.88 | 630.98 | 1246.52 | 693.12 | 0.00 | 0.00 | 744.00 |
June | 1076.11 | 466.88 | 609.23 | 1332.68 | 549.72 | 0.00 | 0.00 | 720.00 |
July | 1219.32 | 605.89 | 613.43 | 1650.02 | 489.95 | 0.00 | 0.00 | 744.00 |
August | 1204.23 | 639.65 | 564.58 | 1659.37 | 497.48 | 0.00 | 0.00 | 744.00 |
September | 876.79 | 401.79 | 475.00 | 1123.40 | 583.01 | 0.00 | 0.00 | 720.00 |
October | 776.10 | 398.89 | 377.21 | 1027.11 | 634.30 | 0.00 | 0.00 | 744.00 |
November | 707.49 | 359.42 | 348.07 | 738.43 | 916.63 | 0.00 | 0.00 | 720.00 |
December | 674.93 | 374.99 | 299.94 | 691.33 | 1001.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 926.43 | 449.89 | 476.54 | 1104.84 | 748.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 674.93 | 338.47 | 299.94 | 691.33 | 489.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1219.32 | 639.65 | 630.98 | 1659.37 | 1006.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2571.19 | 1886.28 | 684.91 | 3529.73 | 1619.49 | 0.00 | 0.00 | 744.00 |
February | 2020.62 | 1244.74 | 775.89 | 2488.44 | 1478.13 | 0.00 | 0.00 | 672.00 |
March | 1610.35 | 777.74 | 832.61 | 1806.51 | 1551.31 | 0.00 | 0.00 | 744.00 |
April | 1345.13 | 512.56 | 832.58 | 1381.64 | 1258.89 | 0.00 | 0.00 | 720.00 |
May | 957.79 | 117.47 | 840.32 | 770.37 | 1135.07 | 0.00 | 0.00 | 744.00 |
June | 840.20 | 50.31 | 789.88 | 719.30 | 882.26 | 0.00 | 0.00 | 720.00 |
July | 889.88 | 99.66 | 790.23 | 880.16 | 768.23 | 0.00 | 0.00 | 744.00 |
August | 1143.37 | 360.24 | 783.14 | 1289.56 | 806.68 | 0.00 | 0.00 | 744.00 |
September | 1591.39 | 806.18 | 785.21 | 2042.51 | 967.64 | 0.00 | 0.00 | 720.00 |
October | 2024.62 | 1353.56 | 671.05 | 2902.37 | 1059.10 | 0.00 | 0.00 | 744.00 |
November | 2461.19 | 1737.76 | 723.43 | 3328.02 | 1481.65 | 0.00 | 0.00 | 720.00 |
December | 2746.77 | 2090.81 | 655.96 | 3819.92 | 1617.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1682.13 | 918.67 | 763.46 | 2078.84 | 1217.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 840.20 | 50.31 | 655.96 | 719.30 | 768.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2746.77 | 2090.81 | 840.32 | 3819.92 | 1619.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 666.68 | 336.24 | 330.44 | 723.65 | 1086.88 | 0.00 | 0.00 | 744.00 |
February | 795.36 | 367.17 | 428.19 | 841.67 | 991.21 | 0.00 | 0.00 | 672.00 |
March | 911.76 | 403.40 | 508.35 | 981.70 | 1013.89 | 0.00 | 0.00 | 744.00 |
April | 1256.88 | 654.47 | 602.40 | 1559.80 | 842.48 | 0.00 | 0.00 | 720.00 |
May | 1234.58 | 570.23 | 664.35 | 1483.21 | 755.36 | 0.00 | 0.00 | 744.00 |
June | 1307.87 | 653.88 | 653.99 | 1680.13 | 598.78 | 0.00 | 0.00 | 720.00 |
July | 1384.49 | 740.80 | 643.69 | 1892.76 | 540.49 | 0.00 | 0.00 | 744.00 |
August | 1299.00 | 704.01 | 594.99 | 1802.29 | 556.67 | 0.00 | 0.00 | 744.00 |
September | 1112.25 | 595.19 | 517.06 | 1487.14 | 635.06 | 0.00 | 0.00 | 720.00 |
October | 850.21 | 464.18 | 386.03 | 1164.76 | 697.79 | 0.00 | 0.00 | 744.00 |
November | 767.96 | 401.69 | 366.27 | 870.05 | 993.77 | 0.00 | 0.00 | 720.00 |
December | 678.25 | 363.77 | 314.47 | 754.41 | 1099.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1022.99 | 521.92 | 501.08 | 1272.24 | 816.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 666.68 | 336.24 | 314.47 | 723.65 | 540.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1384.49 | 740.80 | 664.35 | 1892.76 | 1099.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.51 | 0.00 | 389.51 | 219.44 | 1459.72 | 0.00 | 0.00 | 744.00 |
February | 488.94 | 0.00 | 488.94 | 247.11 | 1335.13 | 0.00 | 0.00 | 672.00 |
March | 599.15 | 0.00 | 599.15 | 356.04 | 1398.47 | 0.00 | 0.00 | 744.00 |
April | 690.26 | 2.63 | 687.64 | 496.37 | 1130.92 | 0.00 | 0.00 | 720.00 |
May | 829.37 | 38.49 | 790.89 | 591.22 | 991.49 | 0.00 | 0.00 | 744.00 |
June | 883.67 | 86.20 | 797.47 | 728.53 | 781.87 | 0.00 | 0.00 | 720.00 |
July | 836.69 | 69.93 | 766.76 | 787.16 | 699.49 | 0.00 | 0.00 | 744.00 |
August | 694.93 | 13.83 | 681.10 | 681.87 | 736.56 | 0.00 | 0.00 | 744.00 |
September | 588.26 | 0.09 | 588.17 | 544.09 | 870.41 | 0.00 | 0.00 | 720.00 |
October | 466.63 | 0.00 | 466.63 | 498.68 | 945.71 | 0.00 | 0.00 | 744.00 |
November | 422.50 | 0.00 | 422.50 | 247.81 | 1345.36 | 0.00 | 0.00 | 720.00 |
December | 362.60 | 0.00 | 362.60 | 203.32 | 1466.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 604.87 | 17.69 | 587.18 | 468.20 | 1095.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 362.60 | 0.00 | 362.60 | 203.32 | 699.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 883.67 | 86.20 | 797.47 | 787.16 | 1466.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 700.42 | 374.59 | 325.83 | 761.61 | 907.57 | 0.00 | 0.00 | 744.00 |
February | 738.87 | 338.47 | 400.40 | 751.29 | 836.58 | 0.00 | 0.00 | 672.00 |
March | 897.60 | 399.96 | 497.64 | 962.14 | 875.25 | 0.00 | 0.00 | 744.00 |
April | 1147.55 | 575.55 | 572.00 | 1390.36 | 726.39 | 0.00 | 0.00 | 720.00 |
May | 1082.87 | 451.88 | 630.98 | 1257.28 | 662.34 | 0.00 | 0.00 | 744.00 |
June | 1076.11 | 466.88 | 609.23 | 1330.42 | 533.76 | 0.00 | 0.00 | 720.00 |
July | 1219.32 | 605.89 | 613.43 | 1639.52 | 482.96 | 0.00 | 0.00 | 744.00 |
August | 1204.23 | 639.65 | 564.58 | 1651.39 | 487.54 | 0.00 | 0.00 | 744.00 |
September | 876.79 | 401.79 | 475.00 | 1124.60 | 558.57 | 0.00 | 0.00 | 720.00 |
October | 776.10 | 398.89 | 377.21 | 1038.15 | 598.35 | 0.00 | 0.00 | 744.00 |
November | 707.49 | 359.42 | 348.07 | 772.01 | 839.04 | 0.00 | 0.00 | 720.00 |
December | 674.93 | 374.99 | 299.94 | 732.27 | 907.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 926.43 | 449.89 | 476.54 | 1120.19 | 700.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 674.93 | 338.47 | 299.94 | 732.27 | 482.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1219.32 | 639.65 | 630.98 | 1651.39 | 907.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2571.19 | 1886.28 | 684.91 | 3583.25 | 1465.90 | 0.00 | 0.00 | 744.00 |
February | 2020.62 | 1244.74 | 775.89 | 2529.30 | 1339.81 | 0.00 | 0.00 | 672.00 |
March | 1610.35 | 777.74 | 832.61 | 1842.90 | 1428.07 | 0.00 | 0.00 | 744.00 |
April | 1345.13 | 512.56 | 832.58 | 1400.19 | 1182.66 | 0.00 | 0.00 | 720.00 |
May | 957.79 | 117.47 | 840.32 | 791.89 | 1066.53 | 0.00 | 0.00 | 744.00 |
June | 840.20 | 50.31 | 789.88 | 724.88 | 843.66 | 0.00 | 0.00 | 720.00 |
July | 889.88 | 99.66 | 790.23 | 875.47 | 746.17 | 0.00 | 0.00 | 744.00 |
August | 1143.37 | 360.24 | 783.14 | 1286.67 | 777.94 | 0.00 | 0.00 | 744.00 |
September | 1591.39 | 806.18 | 785.21 | 2046.32 | 916.25 | 0.00 | 0.00 | 720.00 |
October | 2024.62 | 1353.56 | 671.05 | 2919.25 | 990.66 | 0.00 | 0.00 | 744.00 |
November | 2461.19 | 1737.76 | 723.43 | 3366.84 | 1359.77 | 0.00 | 0.00 | 720.00 |
December | 2746.77 | 2090.81 | 655.96 | 3871.70 | 1474.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1682.13 | 918.67 | 763.46 | 2102.12 | 1131.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 840.20 | 50.31 | 655.96 | 724.88 | 746.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2746.77 | 2090.81 | 840.32 | 3871.70 | 1474.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 666.68 | 336.24 | 330.44 | 746.74 | 988.69 | 0.00 | 0.00 | 744.00 |
February | 795.36 | 367.17 | 428.19 | 860.55 | 907.33 | 0.00 | 0.00 | 672.00 |
March | 911.76 | 403.40 | 508.35 | 999.36 | 940.96 | 0.00 | 0.00 | 744.00 |
April | 1256.88 | 654.47 | 602.40 | 1565.93 | 796.73 | 0.00 | 0.00 | 720.00 |
May | 1234.58 | 570.23 | 664.35 | 1490.05 | 715.05 | 0.00 | 0.00 | 744.00 |
June | 1307.87 | 653.88 | 653.99 | 1678.29 | 573.85 | 0.00 | 0.00 | 720.00 |
July | 1384.49 | 740.80 | 643.69 | 1884.64 | 524.07 | 0.00 | 0.00 | 744.00 |
August | 1299.00 | 704.01 | 594.99 | 1796.83 | 537.26 | 0.00 | 0.00 | 744.00 |
September | 1112.25 | 595.19 | 517.06 | 1488.95 | 603.20 | 0.00 | 0.00 | 720.00 |
October | 850.21 | 464.18 | 386.03 | 1174.74 | 653.62 | 0.00 | 0.00 | 744.00 |
November | 767.96 | 401.69 | 366.27 | 889.19 | 912.34 | 0.00 | 0.00 | 720.00 |
December | 678.25 | 363.77 | 314.47 | 776.28 | 1002.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1022.99 | 521.92 | 501.08 | 1281.35 | 762.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 666.68 | 336.24 | 314.47 | 746.74 | 524.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1384.49 | 740.80 | 664.35 | 1884.64 | 1002.28 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208651E+09 | 0.00 | 0.208651E+09 | 74936693.70 | 0.980890E+09 |
February | 0.236567E+09 | 0.00 | 0.236567E+09 | 82293691.47 | 0.811668E+09 |
March | 0.320954E+09 | 0.00 | 0.320954E+09 | 0.149503E+09 | 0.910190E+09 |
April | 0.357833E+09 | 1361199.68 | 0.356472E+09 | 0.226472E+09 | 0.686723E+09 |
May | 0.444280E+09 | 20617380.87 | 0.423662E+09 | 0.291970E+09 | 0.605314E+09 |
June | 0.458096E+09 | 44685426.21 | 0.413411E+09 | 0.365056E+09 | 0.452399E+09 |
July | 0.448197E+09 | 37459470.90 | 0.410737E+09 | 0.412546E+09 | 0.405465E+09 |
August | 0.372262E+09 | 7407782.37 | 0.364854E+09 | 0.354166E+09 | 0.435638E+09 |
September | 0.304955E+09 | 46551.49 | 0.304908E+09 | 0.267943E+09 | 0.513321E+09 |
October | 0.249964E+09 | 0.00 | 0.249964E+09 | 0.239488E+09 | 0.602058E+09 |
November | 0.219024E+09 | 0.00 | 0.219024E+09 | 87438987.46 | 0.867077E+09 |
December | 0.194237E+09 | 0.00 | 0.194237E+09 | 60961946.39 | 0.100687E+10 |
Annual Sum or Average | 0.381502E+10 | 0.111578E+09 | 0.370344E+10 | 0.261278E+10 | 0.827761E+10 |
Minimum of Months | 0.194237E+09 | 0.00 | 0.194237E+09 | 60961946.39 | 0.405465E+09 |
Maximum of Months | 0.458096E+09 | 44685426.21 | 0.423662E+09 | 0.412546E+09 | 0.100687E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208649E+09 | 0.00 | 0.208649E+09 | 74934964.36 | 0.980888E+09 |
February | 0.236563E+09 | 0.00 | 0.236563E+09 | 82291130.62 | 0.811667E+09 |
March | 0.320950E+09 | 0.00 | 0.320950E+09 | 0.149498E+09 | 0.910190E+09 |
April | 0.357829E+09 | 1361169.75 | 0.356468E+09 | 0.226468E+09 | 0.686722E+09 |
May | 0.444274E+09 | 20616927.62 | 0.423657E+09 | 0.291964E+09 | 0.605313E+09 |
June | 0.458090E+09 | 44684443.86 | 0.413406E+09 | 0.365049E+09 | 0.452398E+09 |
July | 0.448191E+09 | 37458647.40 | 0.410732E+09 | 0.412540E+09 | 0.405464E+09 |
August | 0.372258E+09 | 7407619.52 | 0.364850E+09 | 0.354163E+09 | 0.435636E+09 |
September | 0.304951E+09 | 46550.46 | 0.304905E+09 | 0.267940E+09 | 0.513319E+09 |
October | 0.249961E+09 | 0.00 | 0.249961E+09 | 0.239485E+09 | 0.602056E+09 |
November | 0.219021E+09 | 0.00 | 0.219021E+09 | 87436369.56 | 0.867074E+09 |
December | 0.194234E+09 | 0.00 | 0.194234E+09 | 60960797.11 | 0.100686E+10 |
Annual Sum or Average | 0.381497E+10 | 0.111575E+09 | 0.370340E+10 | 0.261273E+10 | 0.827759E+10 |
Minimum of Months | 0.194234E+09 | 0.00 | 0.194234E+09 | 60960797.11 | 0.405464E+09 |
Maximum of Months | 0.458090E+09 | 44684443.86 | 0.423657E+09 | 0.412540E+09 | 0.100686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208650E+09 | 0.00 | 0.208650E+09 | 74935540.80 | 0.980889E+09 |
February | 0.236565E+09 | 0.00 | 0.236565E+09 | 82291984.23 | 0.811667E+09 |
March | 0.320951E+09 | 0.00 | 0.320951E+09 | 0.149500E+09 | 0.910190E+09 |
April | 0.357830E+09 | 1361179.73 | 0.356469E+09 | 0.226469E+09 | 0.686722E+09 |
May | 0.444276E+09 | 20617078.70 | 0.423659E+09 | 0.291966E+09 | 0.605313E+09 |
June | 0.458092E+09 | 44684771.31 | 0.413407E+09 | 0.365052E+09 | 0.452398E+09 |
July | 0.448193E+09 | 37458921.90 | 0.410734E+09 | 0.412542E+09 | 0.405464E+09 |
August | 0.372259E+09 | 7407673.80 | 0.364851E+09 | 0.354164E+09 | 0.435637E+09 |
September | 0.304952E+09 | 46550.80 | 0.304906E+09 | 0.267941E+09 | 0.513320E+09 |
October | 0.249962E+09 | 0.00 | 0.249962E+09 | 0.239486E+09 | 0.602056E+09 |
November | 0.219022E+09 | 0.00 | 0.219022E+09 | 87437551.14 | 0.867075E+09 |
December | 0.194235E+09 | 0.00 | 0.194235E+09 | 60961180.20 | 0.100686E+10 |
Annual Sum or Average | 0.381499E+10 | 0.111576E+09 | 0.370341E+10 | 0.261275E+10 | 0.827760E+10 |
Minimum of Months | 0.194235E+09 | 0.00 | 0.194235E+09 | 60961180.20 | 0.405464E+09 |
Maximum of Months | 0.458092E+09 | 44684771.31 | 0.423659E+09 | 0.412542E+09 | 0.100686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208649E+09 | 0.00 | 0.208649E+09 | 74934964.36 | 0.980888E+09 |
February | 0.236563E+09 | 0.00 | 0.236563E+09 | 82291130.62 | 0.811667E+09 |
March | 0.320950E+09 | 0.00 | 0.320950E+09 | 0.149498E+09 | 0.910190E+09 |
April | 0.357829E+09 | 1361169.75 | 0.356468E+09 | 0.226468E+09 | 0.686722E+09 |
May | 0.444274E+09 | 20616927.62 | 0.423657E+09 | 0.291964E+09 | 0.605313E+09 |
June | 0.458090E+09 | 44684443.86 | 0.413406E+09 | 0.365049E+09 | 0.452398E+09 |
July | 0.448191E+09 | 37458647.40 | 0.410732E+09 | 0.412540E+09 | 0.405464E+09 |
August | 0.372258E+09 | 7407619.52 | 0.364850E+09 | 0.354163E+09 | 0.435636E+09 |
September | 0.304951E+09 | 46550.46 | 0.304905E+09 | 0.267940E+09 | 0.513319E+09 |
October | 0.249961E+09 | 0.00 | 0.249961E+09 | 0.239485E+09 | 0.602056E+09 |
November | 0.219021E+09 | 0.00 | 0.219021E+09 | 87436369.56 | 0.867074E+09 |
December | 0.194234E+09 | 0.00 | 0.194234E+09 | 60960797.11 | 0.100686E+10 |
Annual Sum or Average | 0.381497E+10 | 0.111575E+09 | 0.370340E+10 | 0.261273E+10 | 0.827759E+10 |
Minimum of Months | 0.194234E+09 | 0.00 | 0.194234E+09 | 60960797.11 | 0.405464E+09 |
Maximum of Months | 0.458090E+09 | 44684443.86 | 0.423657E+09 | 0.412540E+09 | 0.100686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208641E+09 | 0.00 | 0.208641E+09 | 74932232.36 | 0.980849E+09 |
February | 0.236554E+09 | 0.00 | 0.236554E+09 | 82288240.71 | 0.811634E+09 |
March | 0.320937E+09 | 0.00 | 0.320937E+09 | 0.149493E+09 | 0.910153E+09 |
April | 0.357815E+09 | 1361119.88 | 0.356454E+09 | 0.226459E+09 | 0.686695E+09 |
May | 0.444257E+09 | 20616172.20 | 0.423641E+09 | 0.291953E+09 | 0.605289E+09 |
June | 0.458073E+09 | 44682806.60 | 0.413390E+09 | 0.365036E+09 | 0.452380E+09 |
July | 0.448174E+09 | 37457274.89 | 0.410717E+09 | 0.412525E+09 | 0.405448E+09 |
August | 0.372243E+09 | 7407348.10 | 0.364836E+09 | 0.354149E+09 | 0.435619E+09 |
September | 0.304939E+09 | 46548.76 | 0.304893E+09 | 0.267930E+09 | 0.513299E+09 |
October | 0.249952E+09 | 0.00 | 0.249952E+09 | 0.239476E+09 | 0.602032E+09 |
November | 0.219013E+09 | 0.00 | 0.219013E+09 | 87433205.77 | 0.867040E+09 |
December | 0.194227E+09 | 0.00 | 0.194227E+09 | 60958531.66 | 0.100682E+10 |
Annual Sum or Average | 0.381483E+10 | 0.111571E+09 | 0.370325E+10 | 0.261263E+10 | 0.827726E+10 |
Minimum of Months | 0.194227E+09 | 0.00 | 0.194227E+09 | 60958531.66 | 0.405448E+09 |
Maximum of Months | 0.458073E+09 | 44682806.60 | 0.423641E+09 | 0.412525E+09 | 0.100682E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.625341E+09 | 0.334440E+09 | 0.290902E+09 | 0.620587E+09 | 0.973439E+09 |
February | 0.595831E+09 | 0.272946E+09 | 0.322885E+09 | 0.564267E+09 | 0.806003E+09 |
March | 0.801388E+09 | 0.357089E+09 | 0.444300E+09 | 0.818695E+09 | 0.898264E+09 |
April | 0.991489E+09 | 0.497277E+09 | 0.494213E+09 | 0.119231E+10 | 0.682252E+09 |
May | 0.966793E+09 | 0.403447E+09 | 0.563346E+09 | 0.110803E+10 | 0.646974E+09 |
June | 0.929772E+09 | 0.403390E+09 | 0.526382E+09 | 0.115169E+10 | 0.493542E+09 |
July | 0.108862E+10 | 0.540946E+09 | 0.547678E+09 | 0.148379E+10 | 0.433748E+09 |
August | 0.107515E+10 | 0.571086E+09 | 0.504064E+09 | 0.149202E+10 | 0.436967E+09 |
September | 0.757555E+09 | 0.347149E+09 | 0.410406E+09 | 0.967064E+09 | 0.528835E+09 |
October | 0.692910E+09 | 0.356136E+09 | 0.336773E+09 | 0.907588E+09 | 0.601253E+09 |
November | 0.611275E+09 | 0.310543E+09 | 0.300732E+09 | 0.618029E+09 | 0.851988E+09 |
December | 0.602587E+09 | 0.334797E+09 | 0.267790E+09 | 0.591778E+09 | 0.969213E+09 |
Annual Sum or Average | 0.973872E+10 | 0.472925E+10 | 0.500947E+10 | 0.115158E+11 | 0.832248E+10 |
Minimum of Months | 0.595831E+09 | 0.272946E+09 | 0.267790E+09 | 0.564267E+09 | 0.433748E+09 |
Maximum of Months | 0.108862E+10 | 0.571086E+09 | 0.563346E+09 | 0.149202E+10 | 0.973439E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.625341E+09 | 0.334440E+09 | 0.290902E+09 | 0.620587E+09 | 0.973439E+09 |
February | 0.595831E+09 | 0.272946E+09 | 0.322885E+09 | 0.564267E+09 | 0.806003E+09 |
March | 0.801388E+09 | 0.357089E+09 | 0.444300E+09 | 0.818695E+09 | 0.898264E+09 |
April | 0.991489E+09 | 0.497277E+09 | 0.494213E+09 | 0.119231E+10 | 0.682252E+09 |
May | 0.966793E+09 | 0.403447E+09 | 0.563346E+09 | 0.110803E+10 | 0.646974E+09 |
June | 0.929772E+09 | 0.403390E+09 | 0.526382E+09 | 0.115169E+10 | 0.493542E+09 |
July | 0.108862E+10 | 0.540946E+09 | 0.547678E+09 | 0.148379E+10 | 0.433748E+09 |
August | 0.107515E+10 | 0.571086E+09 | 0.504064E+09 | 0.149202E+10 | 0.436967E+09 |
September | 0.757555E+09 | 0.347149E+09 | 0.410406E+09 | 0.967064E+09 | 0.528835E+09 |
October | 0.692910E+09 | 0.356136E+09 | 0.336773E+09 | 0.907588E+09 | 0.601253E+09 |
November | 0.611275E+09 | 0.310543E+09 | 0.300732E+09 | 0.618029E+09 | 0.851988E+09 |
December | 0.602587E+09 | 0.334797E+09 | 0.267790E+09 | 0.591778E+09 | 0.969213E+09 |
Annual Sum or Average | 0.973872E+10 | 0.472925E+10 | 0.500947E+10 | 0.115158E+11 | 0.832248E+10 |
Minimum of Months | 0.595831E+09 | 0.272946E+09 | 0.267790E+09 | 0.564267E+09 | 0.433748E+09 |
Maximum of Months | 0.108862E+10 | 0.571086E+09 | 0.563346E+09 | 0.149202E+10 | 0.973439E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.625330E+09 | 0.334433E+09 | 0.290896E+09 | 0.620575E+09 | 0.973422E+09 |
February | 0.595821E+09 | 0.272942E+09 | 0.322879E+09 | 0.564257E+09 | 0.805988E+09 |
March | 0.801374E+09 | 0.357082E+09 | 0.444292E+09 | 0.818680E+09 | 0.898248E+09 |
April | 0.991471E+09 | 0.497267E+09 | 0.494204E+09 | 0.119228E+10 | 0.682239E+09 |
May | 0.966775E+09 | 0.403439E+09 | 0.563336E+09 | 0.110801E+10 | 0.646962E+09 |
June | 0.929755E+09 | 0.403383E+09 | 0.526372E+09 | 0.115167E+10 | 0.493533E+09 |
July | 0.108860E+10 | 0.540937E+09 | 0.547668E+09 | 0.148376E+10 | 0.433740E+09 |
August | 0.107513E+10 | 0.571075E+09 | 0.504054E+09 | 0.149199E+10 | 0.436959E+09 |
September | 0.757541E+09 | 0.347143E+09 | 0.410398E+09 | 0.967046E+09 | 0.528825E+09 |
October | 0.692897E+09 | 0.356130E+09 | 0.336767E+09 | 0.907572E+09 | 0.601242E+09 |
November | 0.611264E+09 | 0.310538E+09 | 0.300726E+09 | 0.618018E+09 | 0.851973E+09 |
December | 0.602576E+09 | 0.334791E+09 | 0.267785E+09 | 0.591767E+09 | 0.969195E+09 |
Annual Sum or Average | 0.973854E+10 | 0.472916E+10 | 0.500938E+10 | 0.115156E+11 | 0.832233E+10 |
Minimum of Months | 0.595821E+09 | 0.272942E+09 | 0.267785E+09 | 0.564257E+09 | 0.433740E+09 |
Maximum of Months | 0.108860E+10 | 0.571075E+09 | 0.563336E+09 | 0.149199E+10 | 0.973422E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137731E+10 | 0.101042E+10 | 0.366890E+09 | 0.190447E+10 | 0.876600E+09 |
February | 0.977640E+09 | 0.602241E+09 | 0.375399E+09 | 0.121244E+10 | 0.737987E+09 |
March | 0.862618E+09 | 0.416610E+09 | 0.446009E+09 | 0.968973E+09 | 0.863723E+09 |
April | 0.697309E+09 | 0.265704E+09 | 0.431605E+09 | 0.712692E+09 | 0.678873E+09 |
May | 0.513066E+09 | 62924922.41 | 0.450141E+09 | 0.408905E+09 | 0.627046E+09 |
June | 0.435554E+09 | 26080839.69 | 0.409473E+09 | 0.366786E+09 | 0.476707E+09 |
July | 0.476689E+09 | 53383169.65 | 0.423306E+09 | 0.463253E+09 | 0.422944E+09 |
August | 0.612476E+09 | 0.192969E+09 | 0.419507E+09 | 0.686222E+09 | 0.441202E+09 |
September | 0.824962E+09 | 0.417915E+09 | 0.407047E+09 | 0.106547E+10 | 0.510743E+09 |
October | 0.108453E+10 | 0.725061E+09 | 0.359466E+09 | 0.156452E+10 | 0.578854E+09 |
November | 0.127586E+10 | 0.900834E+09 | 0.375023E+09 | 0.173679E+10 | 0.786594E+09 |
December | 0.147136E+10 | 0.111998E+10 | 0.351379E+09 | 0.205698E+10 | 0.890040E+09 |
Annual Sum or Average | 0.106094E+11 | 0.579413E+10 | 0.481525E+10 | 0.131475E+11 | 0.789131E+10 |
Minimum of Months | 0.435554E+09 | 26080839.69 | 0.351379E+09 | 0.366786E+09 | 0.422944E+09 |
Maximum of Months | 0.147136E+10 | 0.111998E+10 | 0.450141E+09 | 0.205698E+10 | 0.890040E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137730E+10 | 0.101041E+10 | 0.366888E+09 | 0.190446E+10 | 0.876599E+09 |
February | 0.977634E+09 | 0.602236E+09 | 0.375397E+09 | 0.121243E+10 | 0.737986E+09 |
March | 0.862613E+09 | 0.416607E+09 | 0.446006E+09 | 0.968966E+09 | 0.863723E+09 |
April | 0.697305E+09 | 0.265702E+09 | 0.431603E+09 | 0.712687E+09 | 0.678872E+09 |
May | 0.513063E+09 | 62924461.29 | 0.450139E+09 | 0.408902E+09 | 0.627046E+09 |
June | 0.435552E+09 | 26080648.57 | 0.409471E+09 | 0.366784E+09 | 0.476707E+09 |
July | 0.476687E+09 | 53382778.46 | 0.423304E+09 | 0.463251E+09 | 0.422944E+09 |
August | 0.612473E+09 | 0.192967E+09 | 0.419506E+09 | 0.686219E+09 | 0.441202E+09 |
September | 0.824957E+09 | 0.417912E+09 | 0.407045E+09 | 0.106546E+10 | 0.510743E+09 |
October | 0.108452E+10 | 0.725056E+09 | 0.359464E+09 | 0.156451E+10 | 0.578853E+09 |
November | 0.127585E+10 | 0.900827E+09 | 0.375021E+09 | 0.173677E+10 | 0.786593E+09 |
December | 0.147135E+10 | 0.111998E+10 | 0.351377E+09 | 0.205697E+10 | 0.890039E+09 |
Annual Sum or Average | 0.106093E+11 | 0.579408E+10 | 0.481522E+10 | 0.131474E+11 | 0.789131E+10 |
Minimum of Months | 0.435552E+09 | 26080648.57 | 0.351377E+09 | 0.366784E+09 | 0.422944E+09 |
Maximum of Months | 0.147135E+10 | 0.111998E+10 | 0.450139E+09 | 0.205697E+10 | 0.890039E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137731E+10 | 0.101042E+10 | 0.366890E+09 | 0.190447E+10 | 0.876600E+09 |
February | 0.977640E+09 | 0.602241E+09 | 0.375399E+09 | 0.121244E+10 | 0.737987E+09 |
March | 0.862618E+09 | 0.416610E+09 | 0.446009E+09 | 0.968973E+09 | 0.863723E+09 |
April | 0.697309E+09 | 0.265704E+09 | 0.431605E+09 | 0.712692E+09 | 0.678873E+09 |
May | 0.513066E+09 | 62924922.41 | 0.450141E+09 | 0.408905E+09 | 0.627046E+09 |
June | 0.435554E+09 | 26080839.69 | 0.409473E+09 | 0.366786E+09 | 0.476707E+09 |
July | 0.476689E+09 | 53383169.65 | 0.423306E+09 | 0.463253E+09 | 0.422944E+09 |
August | 0.612476E+09 | 0.192969E+09 | 0.419507E+09 | 0.686222E+09 | 0.441202E+09 |
September | 0.824962E+09 | 0.417915E+09 | 0.407047E+09 | 0.106547E+10 | 0.510743E+09 |
October | 0.108453E+10 | 0.725061E+09 | 0.359466E+09 | 0.156452E+10 | 0.578854E+09 |
November | 0.127586E+10 | 0.900834E+09 | 0.375023E+09 | 0.173679E+10 | 0.786594E+09 |
December | 0.147136E+10 | 0.111998E+10 | 0.351379E+09 | 0.205698E+10 | 0.890040E+09 |
Annual Sum or Average | 0.106094E+11 | 0.579413E+10 | 0.481525E+10 | 0.131475E+11 | 0.789131E+10 |
Minimum of Months | 0.435554E+09 | 26080839.69 | 0.351379E+09 | 0.366786E+09 | 0.422944E+09 |
Maximum of Months | 0.147136E+10 | 0.111998E+10 | 0.450141E+09 | 0.205698E+10 | 0.890040E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137730E+10 | 0.101041E+10 | 0.366888E+09 | 0.190446E+10 | 0.876599E+09 |
February | 0.977634E+09 | 0.602236E+09 | 0.375397E+09 | 0.121243E+10 | 0.737986E+09 |
March | 0.862613E+09 | 0.416607E+09 | 0.446006E+09 | 0.968966E+09 | 0.863723E+09 |
April | 0.697305E+09 | 0.265702E+09 | 0.431603E+09 | 0.712687E+09 | 0.678872E+09 |
May | 0.513063E+09 | 62924461.29 | 0.450139E+09 | 0.408902E+09 | 0.627046E+09 |
June | 0.435552E+09 | 26080648.57 | 0.409471E+09 | 0.366784E+09 | 0.476707E+09 |
July | 0.476687E+09 | 53382778.46 | 0.423304E+09 | 0.463251E+09 | 0.422944E+09 |
August | 0.612473E+09 | 0.192967E+09 | 0.419506E+09 | 0.686219E+09 | 0.441202E+09 |
September | 0.824957E+09 | 0.417912E+09 | 0.407045E+09 | 0.106546E+10 | 0.510743E+09 |
October | 0.108452E+10 | 0.725056E+09 | 0.359464E+09 | 0.156451E+10 | 0.578853E+09 |
November | 0.127585E+10 | 0.900827E+09 | 0.375021E+09 | 0.173677E+10 | 0.786593E+09 |
December | 0.147135E+10 | 0.111998E+10 | 0.351377E+09 | 0.205697E+10 | 0.890039E+09 |
Annual Sum or Average | 0.106093E+11 | 0.579408E+10 | 0.481522E+10 | 0.131474E+11 | 0.789131E+10 |
Minimum of Months | 0.435552E+09 | 26080648.57 | 0.351377E+09 | 0.366784E+09 | 0.422944E+09 |
Maximum of Months | 0.147135E+10 | 0.111998E+10 | 0.450139E+09 | 0.205697E+10 | 0.890039E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137725E+10 | 0.101038E+10 | 0.366874E+09 | 0.190439E+10 | 0.876564E+09 |
February | 0.977597E+09 | 0.602214E+09 | 0.375383E+09 | 0.121239E+10 | 0.737957E+09 |
March | 0.862581E+09 | 0.416591E+09 | 0.445989E+09 | 0.968930E+09 | 0.863688E+09 |
April | 0.697279E+09 | 0.265692E+09 | 0.431586E+09 | 0.712661E+09 | 0.678845E+09 |
May | 0.513044E+09 | 62922155.71 | 0.450121E+09 | 0.408887E+09 | 0.627020E+09 |
June | 0.435536E+09 | 26079692.96 | 0.409456E+09 | 0.366770E+09 | 0.476688E+09 |
July | 0.476669E+09 | 53380822.48 | 0.423288E+09 | 0.463234E+09 | 0.422927E+09 |
August | 0.612450E+09 | 0.192960E+09 | 0.419489E+09 | 0.686193E+09 | 0.441184E+09 |
September | 0.824926E+09 | 0.417897E+09 | 0.407030E+09 | 0.106542E+10 | 0.510722E+09 |
October | 0.108448E+10 | 0.725029E+09 | 0.359451E+09 | 0.156445E+10 | 0.578830E+09 |
November | 0.127580E+10 | 0.900794E+09 | 0.375007E+09 | 0.173671E+10 | 0.786561E+09 |
December | 0.147130E+10 | 0.111993E+10 | 0.351364E+09 | 0.205689E+10 | 0.890003E+09 |
Annual Sum or Average | 0.106089E+11 | 0.579387E+10 | 0.481504E+10 | 0.131469E+11 | 0.789099E+10 |
Minimum of Months | 0.435536E+09 | 26079692.96 | 0.351364E+09 | 0.366770E+09 | 0.422927E+09 |
Maximum of Months | 0.147130E+10 | 0.111993E+10 | 0.450121E+09 | 0.205689E+10 | 0.890003E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.595221E+09 | 0.300198E+09 | 0.295023E+09 | 0.615514E+09 | 0.109456E+10 |
February | 0.641382E+09 | 0.296086E+09 | 0.345296E+09 | 0.643962E+09 | 0.940901E+09 |
March | 0.814025E+09 | 0.360163E+09 | 0.453862E+09 | 0.828210E+09 | 0.107489E+10 |
April | 0.108595E+10 | 0.565472E+09 | 0.520482E+09 | 0.130182E+10 | 0.852300E+09 |
May | 0.110224E+10 | 0.509110E+09 | 0.593134E+09 | 0.130472E+10 | 0.733421E+09 |
June | 0.113001E+10 | 0.564954E+09 | 0.565054E+09 | 0.142821E+10 | 0.584889E+09 |
July | 0.123609E+10 | 0.661395E+09 | 0.574692E+09 | 0.165851E+10 | 0.537734E+09 |
August | 0.115976E+10 | 0.628546E+09 | 0.531209E+09 | 0.157146E+10 | 0.570945E+09 |
September | 0.960992E+09 | 0.514246E+09 | 0.446746E+09 | 0.127001E+10 | 0.603263E+09 |
October | 0.759071E+09 | 0.414423E+09 | 0.344648E+09 | 0.100556E+10 | 0.723471E+09 |
November | 0.663526E+09 | 0.347061E+09 | 0.316465E+09 | 0.708560E+09 | 0.102686E+10 |
December | 0.605546E+09 | 0.324780E+09 | 0.280766E+09 | 0.619753E+09 | 0.120757E+10 |
Annual Sum or Average | 0.107538E+11 | 0.548643E+10 | 0.526738E+10 | 0.129563E+11 | 0.995081E+10 |
Minimum of Months | 0.595221E+09 | 0.296086E+09 | 0.280766E+09 | 0.615514E+09 | 0.537734E+09 |
Maximum of Months | 0.123609E+10 | 0.661395E+09 | 0.593134E+09 | 0.165851E+10 | 0.120757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.595221E+09 | 0.300198E+09 | 0.295023E+09 | 0.615514E+09 | 0.109456E+10 |
February | 0.641382E+09 | 0.296086E+09 | 0.345296E+09 | 0.643962E+09 | 0.940901E+09 |
March | 0.814025E+09 | 0.360163E+09 | 0.453862E+09 | 0.828210E+09 | 0.107489E+10 |
April | 0.108595E+10 | 0.565472E+09 | 0.520482E+09 | 0.130182E+10 | 0.852300E+09 |
May | 0.110224E+10 | 0.509110E+09 | 0.593134E+09 | 0.130472E+10 | 0.733421E+09 |
June | 0.113001E+10 | 0.564954E+09 | 0.565054E+09 | 0.142821E+10 | 0.584889E+09 |
July | 0.123609E+10 | 0.661395E+09 | 0.574692E+09 | 0.165851E+10 | 0.537734E+09 |
August | 0.115976E+10 | 0.628546E+09 | 0.531209E+09 | 0.157146E+10 | 0.570945E+09 |
September | 0.960992E+09 | 0.514246E+09 | 0.446746E+09 | 0.127001E+10 | 0.603263E+09 |
October | 0.759071E+09 | 0.414423E+09 | 0.344648E+09 | 0.100556E+10 | 0.723471E+09 |
November | 0.663526E+09 | 0.347061E+09 | 0.316465E+09 | 0.708560E+09 | 0.102686E+10 |
December | 0.605546E+09 | 0.324780E+09 | 0.280766E+09 | 0.619753E+09 | 0.120757E+10 |
Annual Sum or Average | 0.107538E+11 | 0.548643E+10 | 0.526738E+10 | 0.129563E+11 | 0.995081E+10 |
Minimum of Months | 0.595221E+09 | 0.296086E+09 | 0.280766E+09 | 0.615514E+09 | 0.537734E+09 |
Maximum of Months | 0.123609E+10 | 0.661395E+09 | 0.593134E+09 | 0.165851E+10 | 0.120757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.595210E+09 | 0.300192E+09 | 0.295018E+09 | 0.615502E+09 | 0.109454E+10 |
February | 0.641370E+09 | 0.296080E+09 | 0.345289E+09 | 0.643950E+09 | 0.940883E+09 |
March | 0.814010E+09 | 0.360156E+09 | 0.453854E+09 | 0.828195E+09 | 0.107487E+10 |
April | 0.108593E+10 | 0.565462E+09 | 0.520473E+09 | 0.130180E+10 | 0.852284E+09 |
May | 0.110222E+10 | 0.509101E+09 | 0.593123E+09 | 0.130470E+10 | 0.733408E+09 |
June | 0.112999E+10 | 0.564944E+09 | 0.565044E+09 | 0.142819E+10 | 0.584878E+09 |
July | 0.123606E+10 | 0.661383E+09 | 0.574682E+09 | 0.165848E+10 | 0.537725E+09 |
August | 0.115973E+10 | 0.628534E+09 | 0.531200E+09 | 0.157144E+10 | 0.570934E+09 |
September | 0.960975E+09 | 0.514237E+09 | 0.446738E+09 | 0.126998E+10 | 0.603252E+09 |
October | 0.759057E+09 | 0.414415E+09 | 0.344642E+09 | 0.100554E+10 | 0.723458E+09 |
November | 0.663514E+09 | 0.347055E+09 | 0.316459E+09 | 0.708547E+09 | 0.102684E+10 |
December | 0.605535E+09 | 0.324774E+09 | 0.280761E+09 | 0.619742E+09 | 0.120755E+10 |
Annual Sum or Average | 0.107536E+11 | 0.548633E+10 | 0.526728E+10 | 0.129561E+11 | 0.995062E+10 |
Minimum of Months | 0.595210E+09 | 0.296080E+09 | 0.280761E+09 | 0.615502E+09 | 0.537725E+09 |
Maximum of Months | 0.123606E+10 | 0.661383E+09 | 0.593123E+09 | 0.165848E+10 | 0.120755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104326E+10 | 0.00 | 0.104326E+10 | 0.459470E+09 | 0.444721E+10 |
February | 0.118283E+10 | 0.00 | 0.118283E+10 | 0.492267E+09 | 0.364042E+10 |
March | 0.160477E+10 | 0.00 | 0.160477E+10 | 0.847298E+09 | 0.412492E+10 |
April | 0.178916E+10 | 6806041.76 | 0.178236E+10 | 0.123271E+10 | 0.314506E+10 |
May | 0.222140E+10 | 0.103088E+09 | 0.211831E+10 | 0.152714E+10 | 0.284525E+10 |
June | 0.229048E+10 | 0.223429E+09 | 0.206705E+10 | 0.188093E+10 | 0.212779E+10 |
July | 0.224098E+10 | 0.187299E+09 | 0.205368E+10 | 0.212934E+10 | 0.193832E+10 |
August | 0.186130E+10 | 37039147.87 | 0.182427E+10 | 0.183894E+10 | 0.205840E+10 |
September | 0.152477E+10 | 232758.92 | 0.152454E+10 | 0.138755E+10 | 0.240412E+10 |
October | 0.124982E+10 | 0.00 | 0.124982E+10 | 0.127788E+10 | 0.275277E+10 |
November | 0.109512E+10 | 0.00 | 0.109512E+10 | 0.529509E+09 | 0.390407E+10 |
December | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.416712E+09 | 0.445758E+10 |
Annual Sum or Average | 0.190751E+11 | 0.557893E+09 | 0.185172E+11 | 0.140198E+11 | 0.378459E+11 |
Minimum of Months | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.416712E+09 | 0.193832E+10 |
Maximum of Months | 0.229048E+10 | 0.223429E+09 | 0.211831E+10 | 0.212934E+10 | 0.445758E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187600E+10 | 0.100331E+10 | 0.872696E+09 | 0.192954E+10 | 0.269568E+10 |
February | 0.178748E+10 | 0.818831E+09 | 0.968645E+09 | 0.174464E+10 | 0.222322E+10 |
March | 0.240414E+10 | 0.107126E+10 | 0.133289E+10 | 0.250411E+10 | 0.252004E+10 |
April | 0.297444E+10 | 0.149181E+10 | 0.148262E+10 | 0.357869E+10 | 0.197629E+10 |
May | 0.290035E+10 | 0.121033E+10 | 0.169002E+10 | 0.333869E+10 | 0.185646E+10 |
June | 0.278929E+10 | 0.121016E+10 | 0.157913E+10 | 0.345430E+10 | 0.142487E+10 |
July | 0.326584E+10 | 0.162282E+10 | 0.164302E+10 | 0.441941E+10 | 0.131228E+10 |
August | 0.322542E+10 | 0.171324E+10 | 0.151218E+10 | 0.444447E+10 | 0.133245E+10 |
September | 0.227264E+10 | 0.104144E+10 | 0.123120E+10 | 0.291186E+10 | 0.151115E+10 |
October | 0.207871E+10 | 0.106840E+10 | 0.101031E+10 | 0.275100E+10 | 0.169891E+10 |
November | 0.183381E+10 | 0.931621E+09 | 0.902186E+09 | 0.191401E+10 | 0.237590E+10 |
December | 0.180774E+10 | 0.100438E+10 | 0.803363E+09 | 0.185166E+10 | 0.268182E+10 |
Annual Sum or Average | 0.292159E+11 | 0.141876E+11 | 0.150283E+11 | 0.348424E+11 | 0.236091E+11 |
Minimum of Months | 0.178748E+10 | 0.818831E+09 | 0.803363E+09 | 0.174464E+10 | 0.131228E+10 |
Maximum of Months | 0.326584E+10 | 0.171324E+10 | 0.169002E+10 | 0.444447E+10 | 0.269568E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.688668E+10 | 0.505221E+10 | 0.183448E+10 | 0.945402E+10 | 0.433763E+10 |
February | 0.488829E+10 | 0.301127E+10 | 0.187702E+10 | 0.602004E+10 | 0.357588E+10 |
March | 0.431316E+10 | 0.208309E+10 | 0.223007E+10 | 0.483856E+10 | 0.415502E+10 |
April | 0.348659E+10 | 0.132855E+10 | 0.215804E+10 | 0.358120E+10 | 0.326304E+10 |
May | 0.256535E+10 | 0.314631E+09 | 0.225072E+10 | 0.206335E+10 | 0.304017E+10 |
June | 0.217779E+10 | 0.130407E+09 | 0.204738E+10 | 0.186443E+10 | 0.228681E+10 |
July | 0.238346E+10 | 0.266921E+09 | 0.211654E+10 | 0.235743E+10 | 0.205762E+10 |
August | 0.306241E+10 | 0.964864E+09 | 0.209755E+10 | 0.345396E+10 | 0.216061E+10 |
September | 0.412487E+10 | 0.208962E+10 | 0.203525E+10 | 0.529419E+10 | 0.250813E+10 |
October | 0.542273E+10 | 0.362538E+10 | 0.179735E+10 | 0.777371E+10 | 0.283670E+10 |
November | 0.637941E+10 | 0.450426E+10 | 0.187514E+10 | 0.862623E+10 | 0.384044E+10 |
December | 0.735696E+10 | 0.560004E+10 | 0.175692E+10 | 0.102313E+11 | 0.433276E+10 |
Annual Sum or Average | 0.530477E+11 | 0.289712E+11 | 0.240765E+11 | 0.655584E+11 | 0.383948E+11 |
Minimum of Months | 0.217779E+10 | 0.130407E+09 | 0.175692E+10 | 0.186443E+10 | 0.205762E+10 |
Maximum of Months | 0.735696E+10 | 0.560004E+10 | 0.225072E+10 | 0.102313E+11 | 0.433763E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178565E+10 | 0.900584E+09 | 0.885061E+09 | 0.193822E+10 | 0.291110E+10 |
February | 0.192413E+10 | 0.888248E+09 | 0.103588E+10 | 0.203617E+10 | 0.239795E+10 |
March | 0.244205E+10 | 0.108048E+10 | 0.136157E+10 | 0.262939E+10 | 0.271561E+10 |
April | 0.325783E+10 | 0.169640E+10 | 0.156143E+10 | 0.404301E+10 | 0.218371E+10 |
May | 0.330670E+10 | 0.152731E+10 | 0.177938E+10 | 0.397263E+10 | 0.202314E+10 |
June | 0.338999E+10 | 0.169485E+10 | 0.169515E+10 | 0.435489E+10 | 0.155203E+10 |
July | 0.370822E+10 | 0.198416E+10 | 0.172406E+10 | 0.506958E+10 | 0.144766E+10 |
August | 0.347923E+10 | 0.188562E+10 | 0.159361E+10 | 0.482726E+10 | 0.149099E+10 |
September | 0.288295E+10 | 0.154272E+10 | 0.134023E+10 | 0.385466E+10 | 0.164607E+10 |
October | 0.227719E+10 | 0.124326E+10 | 0.103393E+10 | 0.311970E+10 | 0.186896E+10 |
November | 0.199056E+10 | 0.104117E+10 | 0.949385E+09 | 0.225517E+10 | 0.257586E+10 |
December | 0.181662E+10 | 0.974331E+09 | 0.842289E+09 | 0.202060E+10 | 0.294530E+10 |
Annual Sum or Average | 0.322611E+11 | 0.164591E+11 | 0.158020E+11 | 0.401213E+11 | 0.257584E+11 |
Minimum of Months | 0.178565E+10 | 0.888248E+09 | 0.842289E+09 | 0.193822E+10 | 0.144766E+10 |
Maximum of Months | 0.370822E+10 | 0.198416E+10 | 0.177938E+10 | 0.506958E+10 | 0.294530E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104326E+10 | 0.00 | 0.104326E+10 | 0.587761E+09 | 0.390971E+10 |
February | 0.118283E+10 | 0.00 | 0.118283E+10 | 0.597802E+09 | 0.322996E+10 |
March | 0.160477E+10 | 0.00 | 0.160477E+10 | 0.953615E+09 | 0.374567E+10 |
April | 0.178916E+10 | 6806041.76 | 0.178236E+10 | 0.128660E+10 | 0.293135E+10 |
May | 0.222140E+10 | 0.103088E+09 | 0.211831E+10 | 0.158352E+10 | 0.265562E+10 |
June | 0.229048E+10 | 0.223429E+09 | 0.206705E+10 | 0.188836E+10 | 0.202661E+10 |
July | 0.224098E+10 | 0.187299E+09 | 0.205368E+10 | 0.210832E+10 | 0.187353E+10 |
August | 0.186130E+10 | 37039147.87 | 0.182427E+10 | 0.182633E+10 | 0.197281E+10 |
September | 0.152477E+10 | 232758.92 | 0.152454E+10 | 0.141029E+10 | 0.225610E+10 |
October | 0.124982E+10 | 0.00 | 0.124982E+10 | 0.133567E+10 | 0.253299E+10 |
November | 0.109512E+10 | 0.00 | 0.109512E+10 | 0.642313E+09 | 0.348717E+10 |
December | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.544564E+09 | 0.392811E+10 |
Annual Sum or Average | 0.190751E+11 | 0.557893E+09 | 0.185172E+11 | 0.147651E+11 | 0.345496E+11 |
Minimum of Months | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.544564E+09 | 0.187353E+10 |
Maximum of Months | 0.229048E+10 | 0.223429E+09 | 0.211831E+10 | 0.210832E+10 | 0.392811E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187600E+10 | 0.100331E+10 | 0.872696E+09 | 0.203990E+10 | 0.243084E+10 |
February | 0.178748E+10 | 0.818831E+09 | 0.968645E+09 | 0.181752E+10 | 0.202385E+10 |
March | 0.240414E+10 | 0.107126E+10 | 0.133289E+10 | 0.257699E+10 | 0.234426E+10 |
April | 0.297444E+10 | 0.149181E+10 | 0.148262E+10 | 0.360382E+10 | 0.188280E+10 |
May | 0.290035E+10 | 0.121033E+10 | 0.169002E+10 | 0.336749E+10 | 0.177402E+10 |
June | 0.278929E+10 | 0.121016E+10 | 0.157913E+10 | 0.344845E+10 | 0.138352E+10 |
July | 0.326584E+10 | 0.162282E+10 | 0.164302E+10 | 0.439129E+10 | 0.129357E+10 |
August | 0.322542E+10 | 0.171324E+10 | 0.151218E+10 | 0.442309E+10 | 0.130584E+10 |
September | 0.227264E+10 | 0.104144E+10 | 0.123120E+10 | 0.291495E+10 | 0.144781E+10 |
October | 0.207871E+10 | 0.106840E+10 | 0.101031E+10 | 0.278059E+10 | 0.160261E+10 |
November | 0.183381E+10 | 0.931621E+09 | 0.902186E+09 | 0.200104E+10 | 0.217479E+10 |
December | 0.180774E+10 | 0.100438E+10 | 0.803363E+09 | 0.196132E+10 | 0.243143E+10 |
Annual Sum or Average | 0.292159E+11 | 0.141876E+11 | 0.150283E+11 | 0.353265E+11 | 0.220953E+11 |
Minimum of Months | 0.178748E+10 | 0.818831E+09 | 0.803363E+09 | 0.181752E+10 | 0.129357E+10 |
Maximum of Months | 0.326584E+10 | 0.171324E+10 | 0.169002E+10 | 0.442309E+10 | 0.243143E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.688668E+10 | 0.505221E+10 | 0.183448E+10 | 0.959738E+10 | 0.392626E+10 |
February | 0.488829E+10 | 0.301127E+10 | 0.187702E+10 | 0.611889E+10 | 0.324126E+10 |
March | 0.431316E+10 | 0.208309E+10 | 0.223007E+10 | 0.493602E+10 | 0.382494E+10 |
April | 0.348659E+10 | 0.132855E+10 | 0.215804E+10 | 0.362930E+10 | 0.306546E+10 |
May | 0.256535E+10 | 0.314631E+09 | 0.225072E+10 | 0.212099E+10 | 0.285659E+10 |
June | 0.217779E+10 | 0.130407E+09 | 0.204738E+10 | 0.187888E+10 | 0.218677E+10 |
July | 0.238346E+10 | 0.266921E+09 | 0.211654E+10 | 0.234485E+10 | 0.199855E+10 |
August | 0.306241E+10 | 0.964864E+09 | 0.209755E+10 | 0.344622E+10 | 0.208363E+10 |
September | 0.412487E+10 | 0.208962E+10 | 0.203525E+10 | 0.530405E+10 | 0.237491E+10 |
October | 0.542273E+10 | 0.362538E+10 | 0.179735E+10 | 0.781893E+10 | 0.265339E+10 |
November | 0.637941E+10 | 0.450426E+10 | 0.187514E+10 | 0.872686E+10 | 0.352453E+10 |
December | 0.735696E+10 | 0.560004E+10 | 0.175692E+10 | 0.103700E+11 | 0.394795E+10 |
Annual Sum or Average | 0.530477E+11 | 0.289712E+11 | 0.240765E+11 | 0.662923E+11 | 0.356842E+11 |
Minimum of Months | 0.217779E+10 | 0.130407E+09 | 0.175692E+10 | 0.187888E+10 | 0.199855E+10 |
Maximum of Months | 0.735696E+10 | 0.560004E+10 | 0.225072E+10 | 0.103700E+11 | 0.394795E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178565E+10 | 0.900584E+09 | 0.885061E+09 | 0.200006E+10 | 0.264810E+10 |
February | 0.192413E+10 | 0.888248E+09 | 0.103588E+10 | 0.208183E+10 | 0.219502E+10 |
March | 0.244205E+10 | 0.108048E+10 | 0.136157E+10 | 0.267668E+10 | 0.252027E+10 |
April | 0.325783E+10 | 0.169640E+10 | 0.156143E+10 | 0.405890E+10 | 0.206512E+10 |
May | 0.330670E+10 | 0.152731E+10 | 0.177938E+10 | 0.399096E+10 | 0.191518E+10 |
June | 0.338999E+10 | 0.169485E+10 | 0.169515E+10 | 0.435013E+10 | 0.148742E+10 |
July | 0.370822E+10 | 0.198416E+10 | 0.172406E+10 | 0.504783E+10 | 0.140368E+10 |
August | 0.347923E+10 | 0.188562E+10 | 0.159361E+10 | 0.481262E+10 | 0.143901E+10 |
September | 0.288295E+10 | 0.154272E+10 | 0.134023E+10 | 0.385935E+10 | 0.156349E+10 |
October | 0.227719E+10 | 0.124326E+10 | 0.103393E+10 | 0.314642E+10 | 0.175067E+10 |
November | 0.199056E+10 | 0.104117E+10 | 0.949385E+09 | 0.230477E+10 | 0.236478E+10 |
December | 0.181662E+10 | 0.974331E+09 | 0.842289E+09 | 0.207919E+10 | 0.268450E+10 |
Annual Sum or Average | 0.322611E+11 | 0.164591E+11 | 0.158020E+11 | 0.404087E+11 | 0.240372E+11 |
Minimum of Months | 0.178565E+10 | 0.888248E+09 | 0.842289E+09 | 0.200006E+10 | 0.140368E+10 |
Maximum of Months | 0.370822E+10 | 0.198416E+10 | 0.177938E+10 | 0.504783E+10 | 0.268450E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 139.89 | 1831.09 | 389.50 | 0.00 | 389.50 | 0.00 | 0.00 |
February | 170.08 | 1677.54 | 488.93 | 0.00 | 488.93 | 0.00 | 0.00 |
March | 279.08 | 1699.12 | 599.14 | 0.00 | 599.14 | 0.00 | 0.00 |
April | 436.86 | 1324.69 | 690.25 | 2.63 | 687.63 | 0.00 | 0.00 |
May | 545.03 | 1129.98 | 829.36 | 38.49 | 790.87 | 0.00 | 0.00 |
June | 704.18 | 872.67 | 883.66 | 86.20 | 797.46 | 0.00 | 0.00 |
July | 770.12 | 756.91 | 836.67 | 69.93 | 766.75 | 0.00 | 0.00 |
August | 661.14 | 813.23 | 694.92 | 13.83 | 681.09 | 0.00 | 0.00 |
September | 516.86 | 990.19 | 588.25 | 0.09 | 588.16 | 0.00 | 0.00 |
October | 447.07 | 1123.90 | 466.62 | 0.00 | 466.62 | 0.00 | 0.00 |
November | 168.67 | 1672.59 | 422.49 | 0.00 | 422.49 | 0.00 | 0.00 |
December | 113.80 | 1879.58 | 362.59 | 0.00 | 362.59 | 0.00 | 0.00 |
Annual Sum or Average | 414.24 | 1312.39 | 604.86 | 17.69 | 587.17 | 0.00 | 0.00 |
Minimum of Months | 113.80 | 756.91 | 362.59 | 0.00 | 362.59 | 0.00 | 0.00 |
Maximum of Months | 770.12 | 1879.58 | 883.66 | 86.20 | 797.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.10 | 1090.32 | 700.42 | 374.59 | 325.83 | 0.00 | 0.00 |
February | 699.73 | 999.50 | 738.87 | 338.47 | 400.40 | 0.00 | 0.00 |
March | 916.99 | 1006.11 | 897.61 | 399.96 | 497.64 | 0.00 | 0.00 |
April | 1379.97 | 789.64 | 1147.55 | 575.55 | 572.00 | 0.00 | 0.00 |
May | 1241.06 | 724.65 | 1082.87 | 451.89 | 630.98 | 0.00 | 0.00 |
June | 1332.97 | 571.23 | 1076.12 | 466.88 | 609.23 | 0.00 | 0.00 |
July | 1661.94 | 485.83 | 1219.33 | 605.90 | 613.43 | 0.00 | 0.00 |
August | 1671.15 | 489.43 | 1204.24 | 639.65 | 564.58 | 0.00 | 0.00 |
September | 1119.28 | 612.07 | 876.79 | 401.79 | 475.00 | 0.00 | 0.00 |
October | 1016.56 | 673.44 | 776.10 | 398.90 | 377.21 | 0.00 | 0.00 |
November | 715.31 | 986.09 | 707.49 | 359.42 | 348.07 | 0.00 | 0.00 |
December | 662.83 | 1085.58 | 674.94 | 374.99 | 299.94 | 0.00 | 0.00 |
Annual Sum or Average | 1095.49 | 791.71 | 926.43 | 449.89 | 476.54 | 0.00 | 0.00 |
Minimum of Months | 662.83 | 485.83 | 674.94 | 338.47 | 299.94 | 0.00 | 0.00 |
Maximum of Months | 1671.15 | 1090.32 | 1219.33 | 639.65 | 630.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3555.20 | 1636.41 | 2571.11 | 1886.22 | 684.90 | 0.00 | 0.00 |
February | 2505.84 | 1525.26 | 2020.56 | 1244.70 | 775.87 | 0.00 | 0.00 |
March | 1808.84 | 1612.37 | 1610.31 | 777.71 | 832.59 | 0.00 | 0.00 |
April | 1374.78 | 1309.54 | 1345.10 | 512.54 | 832.56 | 0.00 | 0.00 |
May | 763.33 | 1170.55 | 957.77 | 117.47 | 840.31 | 0.00 | 0.00 |
June | 707.53 | 919.57 | 840.18 | 50.31 | 789.87 | 0.00 | 0.00 |
July | 864.79 | 789.54 | 889.87 | 99.65 | 790.21 | 0.00 | 0.00 |
August | 1281.02 | 823.62 | 1143.35 | 360.23 | 783.12 | 0.00 | 0.00 |
September | 2055.28 | 985.22 | 1591.34 | 806.15 | 785.19 | 0.00 | 0.00 |
October | 2920.59 | 1080.59 | 2024.56 | 1353.52 | 671.04 | 0.00 | 0.00 |
November | 3350.24 | 1517.34 | 2461.12 | 1737.70 | 723.42 | 0.00 | 0.00 |
December | 3839.90 | 1661.50 | 2746.69 | 2090.75 | 655.94 | 0.00 | 0.00 |
Annual Sum or Average | 2084.50 | 1251.15 | 1682.09 | 918.64 | 763.44 | 0.00 | 0.00 |
Minimum of Months | 707.53 | 789.54 | 840.18 | 50.31 | 655.94 | 0.00 | 0.00 |
Maximum of Months | 3839.90 | 1661.50 | 2746.69 | 2090.75 | 840.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 689.42 | 1225.97 | 666.69 | 336.24 | 330.45 | 0.00 | 0.00 |
February | 798.56 | 1166.78 | 795.36 | 367.17 | 428.19 | 0.00 | 0.00 |
March | 927.65 | 1203.95 | 911.76 | 403.41 | 508.36 | 0.00 | 0.00 |
April | 1506.73 | 986.45 | 1256.88 | 654.48 | 602.41 | 0.00 | 0.00 |
May | 1461.38 | 821.48 | 1234.58 | 570.24 | 664.35 | 0.00 | 0.00 |
June | 1653.01 | 676.95 | 1307.87 | 653.88 | 653.99 | 0.00 | 0.00 |
July | 1857.63 | 602.30 | 1384.50 | 740.81 | 643.69 | 0.00 | 0.00 |
August | 1760.14 | 639.50 | 1299.00 | 704.01 | 594.99 | 0.00 | 0.00 |
September | 1469.91 | 698.22 | 1112.25 | 595.19 | 517.06 | 0.00 | 0.00 |
October | 1126.29 | 810.33 | 850.21 | 464.18 | 386.03 | 0.00 | 0.00 |
November | 820.09 | 1188.49 | 767.97 | 401.69 | 366.28 | 0.00 | 0.00 |
December | 694.16 | 1352.56 | 678.25 | 363.78 | 314.48 | 0.00 | 0.00 |
Annual Sum or Average | 1232.52 | 946.61 | 1023.00 | 521.92 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 689.42 | 602.30 | 666.69 | 336.24 | 314.48 | 0.00 | 0.00 |
Maximum of Months | 1857.63 | 1352.56 | 1384.50 | 740.81 | 664.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.55 | 1660.40 | 389.51 | 0.00 | 389.51 | 0.00 | 0.00 |
February | 203.48 | 1504.80 | 488.94 | 0.00 | 488.94 | 0.00 | 0.00 |
March | 316.34 | 1540.07 | 599.15 | 0.00 | 599.15 | 0.00 | 0.00 |
April | 475.58 | 1213.37 | 690.26 | 2.63 | 687.64 | 0.00 | 0.00 |
May | 570.17 | 1062.29 | 829.37 | 38.49 | 790.89 | 0.00 | 0.00 |
June | 725.67 | 820.91 | 883.67 | 86.20 | 797.47 | 0.00 | 0.00 |
July | 795.01 | 723.69 | 836.69 | 69.93 | 766.76 | 0.00 | 0.00 |
August | 686.58 | 768.52 | 694.93 | 13.83 | 681.10 | 0.00 | 0.00 |
September | 535.32 | 927.51 | 588.26 | 0.09 | 588.17 | 0.00 | 0.00 |
October | 477.11 | 1027.77 | 466.63 | 0.00 | 466.63 | 0.00 | 0.00 |
November | 204.29 | 1506.20 | 422.50 | 0.00 | 422.50 | 0.00 | 0.00 |
December | 155.58 | 1664.27 | 362.60 | 0.00 | 362.60 | 0.00 | 0.00 |
Annual Sum or Average | 444.56 | 1200.09 | 604.87 | 17.69 | 587.18 | 0.00 | 0.00 |
Minimum of Months | 155.58 | 723.69 | 362.60 | 0.00 | 362.60 | 0.00 | 0.00 |
Maximum of Months | 795.01 | 1664.27 | 883.67 | 86.20 | 797.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 720.41 | 1006.45 | 700.42 | 374.59 | 325.83 | 0.00 | 0.00 |
February | 721.16 | 918.99 | 738.87 | 338.47 | 400.40 | 0.00 | 0.00 |
March | 934.93 | 940.87 | 897.60 | 399.96 | 497.64 | 0.00 | 0.00 |
April | 1380.67 | 762.46 | 1147.55 | 575.55 | 572.00 | 0.00 | 0.00 |
May | 1246.52 | 693.12 | 1082.87 | 451.88 | 630.98 | 0.00 | 0.00 |
June | 1332.68 | 549.72 | 1076.11 | 466.88 | 609.23 | 0.00 | 0.00 |
July | 1650.02 | 489.95 | 1219.32 | 605.89 | 613.43 | 0.00 | 0.00 |
August | 1659.37 | 497.48 | 1204.23 | 639.65 | 564.58 | 0.00 | 0.00 |
September | 1123.40 | 583.01 | 876.79 | 401.79 | 475.00 | 0.00 | 0.00 |
October | 1027.11 | 634.30 | 776.10 | 398.89 | 377.21 | 0.00 | 0.00 |
November | 738.43 | 916.63 | 707.49 | 359.42 | 348.07 | 0.00 | 0.00 |
December | 691.33 | 1001.28 | 674.93 | 374.99 | 299.94 | 0.00 | 0.00 |
Annual Sum or Average | 1104.84 | 748.64 | 926.43 | 449.89 | 476.54 | 0.00 | 0.00 |
Minimum of Months | 691.33 | 489.95 | 674.93 | 338.47 | 299.94 | 0.00 | 0.00 |
Maximum of Months | 1659.37 | 1006.45 | 1219.32 | 639.65 | 630.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3529.73 | 1619.49 | 2571.19 | 1886.28 | 684.91 | 0.00 | 0.00 |
February | 2488.44 | 1478.13 | 2020.62 | 1244.74 | 775.89 | 0.00 | 0.00 |
March | 1806.51 | 1551.31 | 1610.35 | 777.74 | 832.61 | 0.00 | 0.00 |
April | 1381.64 | 1258.89 | 1345.13 | 512.56 | 832.58 | 0.00 | 0.00 |
May | 770.37 | 1135.07 | 957.79 | 117.47 | 840.32 | 0.00 | 0.00 |
June | 719.30 | 882.26 | 840.20 | 50.31 | 789.88 | 0.00 | 0.00 |
July | 880.16 | 768.23 | 889.88 | 99.66 | 790.23 | 0.00 | 0.00 |
August | 1289.56 | 806.68 | 1143.37 | 360.24 | 783.14 | 0.00 | 0.00 |
September | 2042.51 | 967.64 | 1591.39 | 806.18 | 785.21 | 0.00 | 0.00 |
October | 2902.37 | 1059.10 | 2024.62 | 1353.56 | 671.05 | 0.00 | 0.00 |
November | 3328.02 | 1481.65 | 2461.19 | 1737.76 | 723.43 | 0.00 | 0.00 |
December | 3819.92 | 1617.67 | 2746.77 | 2090.81 | 655.96 | 0.00 | 0.00 |
Annual Sum or Average | 2078.84 | 1217.49 | 1682.13 | 918.67 | 763.46 | 0.00 | 0.00 |
Minimum of Months | 719.30 | 768.23 | 840.20 | 50.31 | 655.96 | 0.00 | 0.00 |
Maximum of Months | 3819.92 | 1619.49 | 2746.77 | 2090.81 | 840.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 723.65 | 1086.88 | 666.68 | 336.24 | 330.44 | 0.00 | 0.00 |
February | 841.67 | 991.21 | 795.36 | 367.17 | 428.19 | 0.00 | 0.00 |
March | 981.70 | 1013.89 | 911.76 | 403.40 | 508.35 | 0.00 | 0.00 |
April | 1559.80 | 842.48 | 1256.88 | 654.47 | 602.40 | 0.00 | 0.00 |
May | 1483.21 | 755.36 | 1234.58 | 570.23 | 664.35 | 0.00 | 0.00 |
June | 1680.13 | 598.78 | 1307.87 | 653.88 | 653.99 | 0.00 | 0.00 |
July | 1892.76 | 540.49 | 1384.49 | 740.80 | 643.69 | 0.00 | 0.00 |
August | 1802.29 | 556.67 | 1299.00 | 704.01 | 594.99 | 0.00 | 0.00 |
September | 1487.14 | 635.06 | 1112.25 | 595.19 | 517.06 | 0.00 | 0.00 |
October | 1164.76 | 697.79 | 850.21 | 464.18 | 386.03 | 0.00 | 0.00 |
November | 870.05 | 993.77 | 767.96 | 401.69 | 366.27 | 0.00 | 0.00 |
December | 754.41 | 1099.65 | 678.25 | 363.77 | 314.47 | 0.00 | 0.00 |
Annual Sum or Average | 1272.24 | 816.79 | 1022.99 | 521.92 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 723.65 | 540.49 | 666.68 | 336.24 | 314.47 | 0.00 | 0.00 |
Maximum of Months | 1892.76 | 1099.65 | 1384.49 | 740.80 | 664.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.44 | 1459.72 | 389.51 | 0.00 | 389.51 | 0.00 | 0.00 |
February | 247.11 | 1335.13 | 488.94 | 0.00 | 488.94 | 0.00 | 0.00 |
March | 356.04 | 1398.47 | 599.15 | 0.00 | 599.15 | 0.00 | 0.00 |
April | 496.37 | 1130.92 | 690.26 | 2.63 | 687.64 | 0.00 | 0.00 |
May | 591.22 | 991.49 | 829.37 | 38.49 | 790.89 | 0.00 | 0.00 |
June | 728.53 | 781.87 | 883.67 | 86.20 | 797.47 | 0.00 | 0.00 |
July | 787.16 | 699.49 | 836.69 | 69.93 | 766.76 | 0.00 | 0.00 |
August | 681.87 | 736.56 | 694.93 | 13.83 | 681.10 | 0.00 | 0.00 |
September | 544.09 | 870.41 | 588.26 | 0.09 | 588.17 | 0.00 | 0.00 |
October | 498.68 | 945.71 | 466.63 | 0.00 | 466.63 | 0.00 | 0.00 |
November | 247.81 | 1345.36 | 422.50 | 0.00 | 422.50 | 0.00 | 0.00 |
December | 203.32 | 1466.59 | 362.60 | 0.00 | 362.60 | 0.00 | 0.00 |
Annual Sum or Average | 468.20 | 1095.56 | 604.87 | 17.69 | 587.18 | 0.00 | 0.00 |
Minimum of Months | 203.32 | 699.49 | 362.60 | 0.00 | 362.60 | 0.00 | 0.00 |
Maximum of Months | 787.16 | 1466.59 | 883.67 | 86.20 | 797.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 761.61 | 907.57 | 700.42 | 374.59 | 325.83 | 0.00 | 0.00 |
February | 751.29 | 836.58 | 738.87 | 338.47 | 400.40 | 0.00 | 0.00 |
March | 962.14 | 875.25 | 897.60 | 399.96 | 497.64 | 0.00 | 0.00 |
April | 1390.36 | 726.39 | 1147.55 | 575.55 | 572.00 | 0.00 | 0.00 |
May | 1257.28 | 662.34 | 1082.87 | 451.88 | 630.98 | 0.00 | 0.00 |
June | 1330.42 | 533.76 | 1076.11 | 466.88 | 609.23 | 0.00 | 0.00 |
July | 1639.52 | 482.96 | 1219.32 | 605.89 | 613.43 | 0.00 | 0.00 |
August | 1651.39 | 487.54 | 1204.23 | 639.65 | 564.58 | 0.00 | 0.00 |
September | 1124.60 | 558.57 | 876.79 | 401.79 | 475.00 | 0.00 | 0.00 |
October | 1038.15 | 598.35 | 776.10 | 398.89 | 377.21 | 0.00 | 0.00 |
November | 772.01 | 839.04 | 707.49 | 359.42 | 348.07 | 0.00 | 0.00 |
December | 732.27 | 907.79 | 674.93 | 374.99 | 299.94 | 0.00 | 0.00 |
Annual Sum or Average | 1120.19 | 700.64 | 926.43 | 449.89 | 476.54 | 0.00 | 0.00 |
Minimum of Months | 732.27 | 482.96 | 674.93 | 338.47 | 299.94 | 0.00 | 0.00 |
Maximum of Months | 1651.39 | 907.79 | 1219.32 | 639.65 | 630.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3583.25 | 1465.90 | 2571.19 | 1886.28 | 684.91 | 0.00 | 0.00 |
February | 2529.30 | 1339.81 | 2020.62 | 1244.74 | 775.89 | 0.00 | 0.00 |
March | 1842.90 | 1428.07 | 1610.35 | 777.74 | 832.61 | 0.00 | 0.00 |
April | 1400.19 | 1182.66 | 1345.13 | 512.56 | 832.58 | 0.00 | 0.00 |
May | 791.89 | 1066.53 | 957.79 | 117.47 | 840.32 | 0.00 | 0.00 |
June | 724.88 | 843.66 | 840.20 | 50.31 | 789.88 | 0.00 | 0.00 |
July | 875.47 | 746.17 | 889.88 | 99.66 | 790.23 | 0.00 | 0.00 |
August | 1286.67 | 777.94 | 1143.37 | 360.24 | 783.14 | 0.00 | 0.00 |
September | 2046.32 | 916.25 | 1591.39 | 806.18 | 785.21 | 0.00 | 0.00 |
October | 2919.25 | 990.66 | 2024.62 | 1353.56 | 671.05 | 0.00 | 0.00 |
November | 3366.84 | 1359.77 | 2461.19 | 1737.76 | 723.43 | 0.00 | 0.00 |
December | 3871.70 | 1474.00 | 2746.77 | 2090.81 | 655.96 | 0.00 | 0.00 |
Annual Sum or Average | 2102.12 | 1131.54 | 1682.13 | 918.67 | 763.46 | 0.00 | 0.00 |
Minimum of Months | 724.88 | 746.17 | 840.20 | 50.31 | 655.96 | 0.00 | 0.00 |
Maximum of Months | 3871.70 | 1474.00 | 2746.77 | 2090.81 | 840.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 746.74 | 988.69 | 666.68 | 336.24 | 330.44 | 0.00 | 0.00 |
February | 860.55 | 907.33 | 795.36 | 367.17 | 428.19 | 0.00 | 0.00 |
March | 999.36 | 940.96 | 911.76 | 403.40 | 508.35 | 0.00 | 0.00 |
April | 1565.93 | 796.73 | 1256.88 | 654.47 | 602.40 | 0.00 | 0.00 |
May | 1490.05 | 715.05 | 1234.58 | 570.23 | 664.35 | 0.00 | 0.00 |
June | 1678.29 | 573.85 | 1307.87 | 653.88 | 653.99 | 0.00 | 0.00 |
July | 1884.64 | 524.07 | 1384.49 | 740.80 | 643.69 | 0.00 | 0.00 |
August | 1796.83 | 537.26 | 1299.00 | 704.01 | 594.99 | 0.00 | 0.00 |
September | 1488.95 | 603.20 | 1112.25 | 595.19 | 517.06 | 0.00 | 0.00 |
October | 1174.74 | 653.62 | 850.21 | 464.18 | 386.03 | 0.00 | 0.00 |
November | 889.19 | 912.34 | 767.96 | 401.69 | 366.27 | 0.00 | 0.00 |
December | 776.28 | 1002.28 | 678.25 | 363.77 | 314.47 | 0.00 | 0.00 |
Annual Sum or Average | 1281.35 | 762.22 | 1022.99 | 521.92 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 746.74 | 524.07 | 666.68 | 336.24 | 314.47 | 0.00 | 0.00 |
Maximum of Months | 1884.64 | 1002.28 | 1384.49 | 740.80 | 664.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.374674E+09 | 0.490440E+10 | 0.104324E+10 | 0.00 | 0.104324E+10 | 0.00 | 0.00 |
February | 0.411456E+09 | 0.405830E+10 | 0.118281E+10 | 0.00 | 0.118281E+10 | 0.00 | 0.00 |
March | 0.747493E+09 | 0.455091E+10 | 0.160474E+10 | 0.00 | 0.160474E+10 | 0.00 | 0.00 |
April | 0.113234E+10 | 0.343358E+10 | 0.178914E+10 | 6805838.79 | 0.178233E+10 | 0.00 | 0.00 |
May | 0.145982E+10 | 0.302654E+10 | 0.222136E+10 | 0.103084E+09 | 0.211828E+10 | 0.00 | 0.00 |
June | 0.182524E+10 | 0.226197E+10 | 0.229044E+10 | 0.223422E+09 | 0.206702E+10 | 0.00 | 0.00 |
July | 0.206269E+10 | 0.202730E+10 | 0.224095E+10 | 0.187293E+09 | 0.205365E+10 | 0.00 | 0.00 |
August | 0.177080E+10 | 0.217817E+10 | 0.186128E+10 | 37038043.29 | 0.182424E+10 | 0.00 | 0.00 |
September | 0.133969E+10 | 0.256658E+10 | 0.152475E+10 | 232751.98 | 0.152452E+10 | 0.00 | 0.00 |
October | 0.119742E+10 | 0.301026E+10 | 0.124980E+10 | 0.00 | 0.124980E+10 | 0.00 | 0.00 |
November | 0.437182E+09 | 0.433534E+10 | 0.109510E+10 | 0.00 | 0.109510E+10 | 0.00 | 0.00 |
December | 0.304803E+09 | 0.503428E+10 | 0.971167E+09 | 0.00 | 0.971167E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.130636E+11 | 0.413876E+11 | 0.190748E+11 | 0.557876E+09 | 0.185169E+11 | 0.00 | 0.00 |
Minimum of Months | 0.304803E+09 | 0.202730E+10 | 0.971167E+09 | 0.00 | 0.971167E+09 | 0.00 | 0.00 |
Maximum of Months | 0.206269E+10 | 0.503428E+10 | 0.229044E+10 | 0.223422E+09 | 0.211828E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186175E+10 | 0.292030E+10 | 0.187601E+10 | 0.100331E+10 | 0.872700E+09 | 0.00 | 0.00 |
February | 0.169279E+10 | 0.241799E+10 | 0.178748E+10 | 0.818834E+09 | 0.968649E+09 | 0.00 | 0.00 |
March | 0.245607E+10 | 0.269478E+10 | 0.240415E+10 | 0.107126E+10 | 0.133289E+10 | 0.00 | 0.00 |
April | 0.357689E+10 | 0.204674E+10 | 0.297445E+10 | 0.149182E+10 | 0.148263E+10 | 0.00 | 0.00 |
May | 0.332406E+10 | 0.194091E+10 | 0.290036E+10 | 0.121033E+10 | 0.169003E+10 | 0.00 | 0.00 |
June | 0.345505E+10 | 0.148062E+10 | 0.278930E+10 | 0.121016E+10 | 0.157914E+10 | 0.00 | 0.00 |
July | 0.445133E+10 | 0.130124E+10 | 0.326585E+10 | 0.162283E+10 | 0.164302E+10 | 0.00 | 0.00 |
August | 0.447602E+10 | 0.131089E+10 | 0.322543E+10 | 0.171325E+10 | 0.151218E+10 | 0.00 | 0.00 |
September | 0.290117E+10 | 0.158649E+10 | 0.227265E+10 | 0.104144E+10 | 0.123121E+10 | 0.00 | 0.00 |
October | 0.272275E+10 | 0.180375E+10 | 0.207872E+10 | 0.106840E+10 | 0.101031E+10 | 0.00 | 0.00 |
November | 0.185408E+10 | 0.255595E+10 | 0.183381E+10 | 0.931625E+09 | 0.902190E+09 | 0.00 | 0.00 |
December | 0.177532E+10 | 0.290762E+10 | 0.180775E+10 | 0.100439E+10 | 0.803366E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345473E+11 | 0.249673E+11 | 0.292160E+11 | 0.141877E+11 | 0.150283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169279E+10 | 0.130124E+10 | 0.178748E+10 | 0.818834E+09 | 0.803366E+09 | 0.00 | 0.00 |
Maximum of Months | 0.447602E+10 | 0.292030E+10 | 0.326585E+10 | 0.171325E+10 | 0.169003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952225E+10 | 0.438296E+10 | 0.688647E+10 | 0.505204E+10 | 0.183443E+10 | 0.00 | 0.00 |
February | 0.606213E+10 | 0.368990E+10 | 0.488814E+10 | 0.301117E+10 | 0.187698E+10 | 0.00 | 0.00 |
March | 0.484481E+10 | 0.431858E+10 | 0.431304E+10 | 0.208302E+10 | 0.223002E+10 | 0.00 | 0.00 |
April | 0.356342E+10 | 0.339434E+10 | 0.348651E+10 | 0.132850E+10 | 0.215800E+10 | 0.00 | 0.00 |
May | 0.204450E+10 | 0.313520E+10 | 0.256530E+10 | 0.314621E+09 | 0.225068E+10 | 0.00 | 0.00 |
June | 0.183391E+10 | 0.238352E+10 | 0.217775E+10 | 0.130403E+09 | 0.204735E+10 | 0.00 | 0.00 |
July | 0.231624E+10 | 0.211470E+10 | 0.238342E+10 | 0.266913E+09 | 0.211651E+10 | 0.00 | 0.00 |
August | 0.343108E+10 | 0.220599E+10 | 0.306235E+10 | 0.964833E+09 | 0.209751E+10 | 0.00 | 0.00 |
September | 0.532728E+10 | 0.255369E+10 | 0.412476E+10 | 0.208955E+10 | 0.203521E+10 | 0.00 | 0.00 |
October | 0.782250E+10 | 0.289424E+10 | 0.542257E+10 | 0.362526E+10 | 0.179731E+10 | 0.00 | 0.00 |
November | 0.868383E+10 | 0.393293E+10 | 0.637921E+10 | 0.450412E+10 | 0.187510E+10 | 0.00 | 0.00 |
December | 0.102848E+11 | 0.445016E+10 | 0.735673E+10 | 0.559985E+10 | 0.175688E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.657367E+11 | 0.394562E+11 | 0.530463E+11 | 0.289703E+11 | 0.240760E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183391E+10 | 0.211470E+10 | 0.217775E+10 | 0.130403E+09 | 0.175688E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102848E+11 | 0.445016E+10 | 0.735673E+10 | 0.559985E+10 | 0.225068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184653E+10 | 0.328365E+10 | 0.178565E+10 | 0.900588E+09 | 0.885065E+09 | 0.00 | 0.00 |
February | 0.193187E+10 | 0.282268E+10 | 0.192413E+10 | 0.888252E+09 | 0.103588E+10 | 0.00 | 0.00 |
March | 0.248462E+10 | 0.322466E+10 | 0.244206E+10 | 0.108048E+10 | 0.136158E+10 | 0.00 | 0.00 |
April | 0.390543E+10 | 0.255688E+10 | 0.325784E+10 | 0.169641E+10 | 0.156144E+10 | 0.00 | 0.00 |
May | 0.391415E+10 | 0.220025E+10 | 0.330671E+10 | 0.152732E+10 | 0.177939E+10 | 0.00 | 0.00 |
June | 0.428461E+10 | 0.175466E+10 | 0.339001E+10 | 0.169485E+10 | 0.169515E+10 | 0.00 | 0.00 |
July | 0.497549E+10 | 0.161319E+10 | 0.370824E+10 | 0.198417E+10 | 0.172407E+10 | 0.00 | 0.00 |
August | 0.471437E+10 | 0.171282E+10 | 0.347924E+10 | 0.188563E+10 | 0.159362E+10 | 0.00 | 0.00 |
September | 0.381000E+10 | 0.180978E+10 | 0.288296E+10 | 0.154273E+10 | 0.134023E+10 | 0.00 | 0.00 |
October | 0.301666E+10 | 0.217040E+10 | 0.227720E+10 | 0.124326E+10 | 0.103394E+10 | 0.00 | 0.00 |
November | 0.212567E+10 | 0.308056E+10 | 0.199057E+10 | 0.104118E+10 | 0.949388E+09 | 0.00 | 0.00 |
December | 0.185925E+10 | 0.362270E+10 | 0.181663E+10 | 0.974335E+09 | 0.842292E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388686E+11 | 0.298522E+11 | 0.322612E+11 | 0.164592E+11 | 0.158020E+11 | 0.00 | 0.00 |
Minimum of Months | 0.184653E+10 | 0.161319E+10 | 0.178565E+10 | 0.888252E+09 | 0.842292E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497549E+10 | 0.362270E+10 | 0.370824E+10 | 0.198417E+10 | 0.177939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.459470E+09 | 0.444721E+10 | 0.104326E+10 | 0.00 | 0.104326E+10 | 0.00 | 0.00 |
February | 0.492267E+09 | 0.364042E+10 | 0.118283E+10 | 0.00 | 0.118283E+10 | 0.00 | 0.00 |
March | 0.847298E+09 | 0.412492E+10 | 0.160477E+10 | 0.00 | 0.160477E+10 | 0.00 | 0.00 |
April | 0.123271E+10 | 0.314506E+10 | 0.178916E+10 | 6806041.76 | 0.178236E+10 | 0.00 | 0.00 |
May | 0.152714E+10 | 0.284525E+10 | 0.222140E+10 | 0.103088E+09 | 0.211831E+10 | 0.00 | 0.00 |
June | 0.188093E+10 | 0.212779E+10 | 0.229048E+10 | 0.223429E+09 | 0.206705E+10 | 0.00 | 0.00 |
July | 0.212934E+10 | 0.193832E+10 | 0.224098E+10 | 0.187299E+09 | 0.205368E+10 | 0.00 | 0.00 |
August | 0.183894E+10 | 0.205840E+10 | 0.186130E+10 | 37039147.87 | 0.182427E+10 | 0.00 | 0.00 |
September | 0.138755E+10 | 0.240412E+10 | 0.152477E+10 | 232758.92 | 0.152454E+10 | 0.00 | 0.00 |
October | 0.127788E+10 | 0.275277E+10 | 0.124982E+10 | 0.00 | 0.124982E+10 | 0.00 | 0.00 |
November | 0.529509E+09 | 0.390407E+10 | 0.109512E+10 | 0.00 | 0.109512E+10 | 0.00 | 0.00 |
December | 0.416712E+09 | 0.445758E+10 | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140198E+11 | 0.378459E+11 | 0.190751E+11 | 0.557893E+09 | 0.185172E+11 | 0.00 | 0.00 |
Minimum of Months | 0.416712E+09 | 0.193832E+10 | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212934E+10 | 0.445758E+10 | 0.229048E+10 | 0.223429E+09 | 0.211831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192954E+10 | 0.269568E+10 | 0.187600E+10 | 0.100331E+10 | 0.872696E+09 | 0.00 | 0.00 |
February | 0.174464E+10 | 0.222322E+10 | 0.178748E+10 | 0.818831E+09 | 0.968645E+09 | 0.00 | 0.00 |
March | 0.250411E+10 | 0.252004E+10 | 0.240414E+10 | 0.107126E+10 | 0.133289E+10 | 0.00 | 0.00 |
April | 0.357869E+10 | 0.197629E+10 | 0.297444E+10 | 0.149181E+10 | 0.148262E+10 | 0.00 | 0.00 |
May | 0.333869E+10 | 0.185646E+10 | 0.290035E+10 | 0.121033E+10 | 0.169002E+10 | 0.00 | 0.00 |
June | 0.345430E+10 | 0.142487E+10 | 0.278929E+10 | 0.121016E+10 | 0.157913E+10 | 0.00 | 0.00 |
July | 0.441941E+10 | 0.131228E+10 | 0.326584E+10 | 0.162282E+10 | 0.164302E+10 | 0.00 | 0.00 |
August | 0.444447E+10 | 0.133245E+10 | 0.322542E+10 | 0.171324E+10 | 0.151218E+10 | 0.00 | 0.00 |
September | 0.291186E+10 | 0.151115E+10 | 0.227264E+10 | 0.104144E+10 | 0.123120E+10 | 0.00 | 0.00 |
October | 0.275100E+10 | 0.169891E+10 | 0.207871E+10 | 0.106840E+10 | 0.101031E+10 | 0.00 | 0.00 |
November | 0.191401E+10 | 0.237590E+10 | 0.183381E+10 | 0.931621E+09 | 0.902186E+09 | 0.00 | 0.00 |
December | 0.185166E+10 | 0.268182E+10 | 0.180774E+10 | 0.100438E+10 | 0.803363E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348424E+11 | 0.236091E+11 | 0.292159E+11 | 0.141876E+11 | 0.150283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174464E+10 | 0.131228E+10 | 0.178748E+10 | 0.818831E+09 | 0.803363E+09 | 0.00 | 0.00 |
Maximum of Months | 0.444447E+10 | 0.269568E+10 | 0.326584E+10 | 0.171324E+10 | 0.169002E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.945402E+10 | 0.433763E+10 | 0.688668E+10 | 0.505221E+10 | 0.183448E+10 | 0.00 | 0.00 |
February | 0.602004E+10 | 0.357588E+10 | 0.488829E+10 | 0.301127E+10 | 0.187702E+10 | 0.00 | 0.00 |
March | 0.483856E+10 | 0.415502E+10 | 0.431316E+10 | 0.208309E+10 | 0.223007E+10 | 0.00 | 0.00 |
April | 0.358120E+10 | 0.326304E+10 | 0.348659E+10 | 0.132855E+10 | 0.215804E+10 | 0.00 | 0.00 |
May | 0.206335E+10 | 0.304017E+10 | 0.256535E+10 | 0.314631E+09 | 0.225072E+10 | 0.00 | 0.00 |
June | 0.186443E+10 | 0.228681E+10 | 0.217779E+10 | 0.130407E+09 | 0.204738E+10 | 0.00 | 0.00 |
July | 0.235743E+10 | 0.205762E+10 | 0.238346E+10 | 0.266921E+09 | 0.211654E+10 | 0.00 | 0.00 |
August | 0.345396E+10 | 0.216061E+10 | 0.306241E+10 | 0.964864E+09 | 0.209755E+10 | 0.00 | 0.00 |
September | 0.529419E+10 | 0.250813E+10 | 0.412487E+10 | 0.208962E+10 | 0.203525E+10 | 0.00 | 0.00 |
October | 0.777371E+10 | 0.283670E+10 | 0.542273E+10 | 0.362538E+10 | 0.179735E+10 | 0.00 | 0.00 |
November | 0.862623E+10 | 0.384044E+10 | 0.637941E+10 | 0.450426E+10 | 0.187514E+10 | 0.00 | 0.00 |
December | 0.102313E+11 | 0.433276E+10 | 0.735696E+10 | 0.560004E+10 | 0.175692E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.655584E+11 | 0.383948E+11 | 0.530477E+11 | 0.289712E+11 | 0.240765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.186443E+10 | 0.205762E+10 | 0.217779E+10 | 0.130407E+09 | 0.175692E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102313E+11 | 0.433763E+10 | 0.735696E+10 | 0.560004E+10 | 0.225072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193822E+10 | 0.291110E+10 | 0.178565E+10 | 0.900584E+09 | 0.885061E+09 | 0.00 | 0.00 |
February | 0.203617E+10 | 0.239795E+10 | 0.192413E+10 | 0.888248E+09 | 0.103588E+10 | 0.00 | 0.00 |
March | 0.262939E+10 | 0.271561E+10 | 0.244205E+10 | 0.108048E+10 | 0.136157E+10 | 0.00 | 0.00 |
April | 0.404301E+10 | 0.218371E+10 | 0.325783E+10 | 0.169640E+10 | 0.156143E+10 | 0.00 | 0.00 |
May | 0.397263E+10 | 0.202314E+10 | 0.330670E+10 | 0.152731E+10 | 0.177938E+10 | 0.00 | 0.00 |
June | 0.435489E+10 | 0.155203E+10 | 0.338999E+10 | 0.169485E+10 | 0.169515E+10 | 0.00 | 0.00 |
July | 0.506958E+10 | 0.144766E+10 | 0.370822E+10 | 0.198416E+10 | 0.172406E+10 | 0.00 | 0.00 |
August | 0.482726E+10 | 0.149099E+10 | 0.347923E+10 | 0.188562E+10 | 0.159361E+10 | 0.00 | 0.00 |
September | 0.385466E+10 | 0.164607E+10 | 0.288295E+10 | 0.154272E+10 | 0.134023E+10 | 0.00 | 0.00 |
October | 0.311970E+10 | 0.186896E+10 | 0.227719E+10 | 0.124326E+10 | 0.103393E+10 | 0.00 | 0.00 |
November | 0.225517E+10 | 0.257586E+10 | 0.199056E+10 | 0.104117E+10 | 0.949385E+09 | 0.00 | 0.00 |
December | 0.202060E+10 | 0.294530E+10 | 0.181662E+10 | 0.974331E+09 | 0.842289E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401213E+11 | 0.257584E+11 | 0.322611E+11 | 0.164591E+11 | 0.158020E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193822E+10 | 0.144766E+10 | 0.178565E+10 | 0.888248E+09 | 0.842289E+09 | 0.00 | 0.00 |
Maximum of Months | 0.506958E+10 | 0.294530E+10 | 0.370822E+10 | 0.198416E+10 | 0.177938E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.587761E+09 | 0.390971E+10 | 0.104326E+10 | 0.00 | 0.104326E+10 | 0.00 | 0.00 |
February | 0.597802E+09 | 0.322996E+10 | 0.118283E+10 | 0.00 | 0.118283E+10 | 0.00 | 0.00 |
March | 0.953615E+09 | 0.374567E+10 | 0.160477E+10 | 0.00 | 0.160477E+10 | 0.00 | 0.00 |
April | 0.128660E+10 | 0.293135E+10 | 0.178916E+10 | 6806041.76 | 0.178236E+10 | 0.00 | 0.00 |
May | 0.158352E+10 | 0.265562E+10 | 0.222140E+10 | 0.103088E+09 | 0.211831E+10 | 0.00 | 0.00 |
June | 0.188836E+10 | 0.202661E+10 | 0.229048E+10 | 0.223429E+09 | 0.206705E+10 | 0.00 | 0.00 |
July | 0.210832E+10 | 0.187353E+10 | 0.224098E+10 | 0.187299E+09 | 0.205368E+10 | 0.00 | 0.00 |
August | 0.182633E+10 | 0.197281E+10 | 0.186130E+10 | 37039147.87 | 0.182427E+10 | 0.00 | 0.00 |
September | 0.141029E+10 | 0.225610E+10 | 0.152477E+10 | 232758.92 | 0.152454E+10 | 0.00 | 0.00 |
October | 0.133567E+10 | 0.253299E+10 | 0.124982E+10 | 0.00 | 0.124982E+10 | 0.00 | 0.00 |
November | 0.642313E+09 | 0.348717E+10 | 0.109512E+10 | 0.00 | 0.109512E+10 | 0.00 | 0.00 |
December | 0.544564E+09 | 0.392811E+10 | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.147651E+11 | 0.345496E+11 | 0.190751E+11 | 0.557893E+09 | 0.185172E+11 | 0.00 | 0.00 |
Minimum of Months | 0.544564E+09 | 0.187353E+10 | 0.971182E+09 | 0.00 | 0.971182E+09 | 0.00 | 0.00 |
Maximum of Months | 0.210832E+10 | 0.392811E+10 | 0.229048E+10 | 0.223429E+09 | 0.211831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.203990E+10 | 0.243084E+10 | 0.187600E+10 | 0.100331E+10 | 0.872696E+09 | 0.00 | 0.00 |
February | 0.181752E+10 | 0.202385E+10 | 0.178748E+10 | 0.818831E+09 | 0.968645E+09 | 0.00 | 0.00 |
March | 0.257699E+10 | 0.234426E+10 | 0.240414E+10 | 0.107126E+10 | 0.133289E+10 | 0.00 | 0.00 |
April | 0.360382E+10 | 0.188280E+10 | 0.297444E+10 | 0.149181E+10 | 0.148262E+10 | 0.00 | 0.00 |
May | 0.336749E+10 | 0.177402E+10 | 0.290035E+10 | 0.121033E+10 | 0.169002E+10 | 0.00 | 0.00 |
June | 0.344845E+10 | 0.138352E+10 | 0.278929E+10 | 0.121016E+10 | 0.157913E+10 | 0.00 | 0.00 |
July | 0.439129E+10 | 0.129357E+10 | 0.326584E+10 | 0.162282E+10 | 0.164302E+10 | 0.00 | 0.00 |
August | 0.442309E+10 | 0.130584E+10 | 0.322542E+10 | 0.171324E+10 | 0.151218E+10 | 0.00 | 0.00 |
September | 0.291495E+10 | 0.144781E+10 | 0.227264E+10 | 0.104144E+10 | 0.123120E+10 | 0.00 | 0.00 |
October | 0.278059E+10 | 0.160261E+10 | 0.207871E+10 | 0.106840E+10 | 0.101031E+10 | 0.00 | 0.00 |
November | 0.200104E+10 | 0.217479E+10 | 0.183381E+10 | 0.931621E+09 | 0.902186E+09 | 0.00 | 0.00 |
December | 0.196132E+10 | 0.243143E+10 | 0.180774E+10 | 0.100438E+10 | 0.803363E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.353265E+11 | 0.220953E+11 | 0.292159E+11 | 0.141876E+11 | 0.150283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181752E+10 | 0.129357E+10 | 0.178748E+10 | 0.818831E+09 | 0.803363E+09 | 0.00 | 0.00 |
Maximum of Months | 0.442309E+10 | 0.243143E+10 | 0.326584E+10 | 0.171324E+10 | 0.169002E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959738E+10 | 0.392626E+10 | 0.688668E+10 | 0.505221E+10 | 0.183448E+10 | 0.00 | 0.00 |
February | 0.611889E+10 | 0.324126E+10 | 0.488829E+10 | 0.301127E+10 | 0.187702E+10 | 0.00 | 0.00 |
March | 0.493602E+10 | 0.382494E+10 | 0.431316E+10 | 0.208309E+10 | 0.223007E+10 | 0.00 | 0.00 |
April | 0.362930E+10 | 0.306546E+10 | 0.348659E+10 | 0.132855E+10 | 0.215804E+10 | 0.00 | 0.00 |
May | 0.212099E+10 | 0.285659E+10 | 0.256535E+10 | 0.314631E+09 | 0.225072E+10 | 0.00 | 0.00 |
June | 0.187888E+10 | 0.218677E+10 | 0.217779E+10 | 0.130407E+09 | 0.204738E+10 | 0.00 | 0.00 |
July | 0.234485E+10 | 0.199855E+10 | 0.238346E+10 | 0.266921E+09 | 0.211654E+10 | 0.00 | 0.00 |
August | 0.344622E+10 | 0.208363E+10 | 0.306241E+10 | 0.964864E+09 | 0.209755E+10 | 0.00 | 0.00 |
September | 0.530405E+10 | 0.237491E+10 | 0.412487E+10 | 0.208962E+10 | 0.203525E+10 | 0.00 | 0.00 |
October | 0.781893E+10 | 0.265339E+10 | 0.542273E+10 | 0.362538E+10 | 0.179735E+10 | 0.00 | 0.00 |
November | 0.872686E+10 | 0.352453E+10 | 0.637941E+10 | 0.450426E+10 | 0.187514E+10 | 0.00 | 0.00 |
December | 0.103700E+11 | 0.394795E+10 | 0.735696E+10 | 0.560004E+10 | 0.175692E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662923E+11 | 0.356842E+11 | 0.530477E+11 | 0.289712E+11 | 0.240765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.187888E+10 | 0.199855E+10 | 0.217779E+10 | 0.130407E+09 | 0.175692E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103700E+11 | 0.394795E+10 | 0.735696E+10 | 0.560004E+10 | 0.225072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200006E+10 | 0.264810E+10 | 0.178565E+10 | 0.900584E+09 | 0.885061E+09 | 0.00 | 0.00 |
February | 0.208183E+10 | 0.219502E+10 | 0.192413E+10 | 0.888248E+09 | 0.103588E+10 | 0.00 | 0.00 |
March | 0.267668E+10 | 0.252027E+10 | 0.244205E+10 | 0.108048E+10 | 0.136157E+10 | 0.00 | 0.00 |
April | 0.405890E+10 | 0.206512E+10 | 0.325783E+10 | 0.169640E+10 | 0.156143E+10 | 0.00 | 0.00 |
May | 0.399096E+10 | 0.191518E+10 | 0.330670E+10 | 0.152731E+10 | 0.177938E+10 | 0.00 | 0.00 |
June | 0.435013E+10 | 0.148742E+10 | 0.338999E+10 | 0.169485E+10 | 0.169515E+10 | 0.00 | 0.00 |
July | 0.504783E+10 | 0.140368E+10 | 0.370822E+10 | 0.198416E+10 | 0.172406E+10 | 0.00 | 0.00 |
August | 0.481262E+10 | 0.143901E+10 | 0.347923E+10 | 0.188562E+10 | 0.159361E+10 | 0.00 | 0.00 |
September | 0.385935E+10 | 0.156349E+10 | 0.288295E+10 | 0.154272E+10 | 0.134023E+10 | 0.00 | 0.00 |
October | 0.314642E+10 | 0.175067E+10 | 0.227719E+10 | 0.124326E+10 | 0.103393E+10 | 0.00 | 0.00 |
November | 0.230477E+10 | 0.236478E+10 | 0.199056E+10 | 0.104117E+10 | 0.949385E+09 | 0.00 | 0.00 |
December | 0.207919E+10 | 0.268450E+10 | 0.181662E+10 | 0.974331E+09 | 0.842289E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.404087E+11 | 0.240372E+11 | 0.322611E+11 | 0.164591E+11 | 0.158020E+11 | 0.00 | 0.00 |
Minimum of Months | 0.200006E+10 | 0.140368E+10 | 0.178565E+10 | 0.888248E+09 | 0.842289E+09 | 0.00 | 0.00 |
Maximum of Months | 0.504783E+10 | 0.268450E+10 | 0.370822E+10 | 0.198416E+10 | 0.177938E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.60 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.19 | 7.03 | 3.12 | 2.95 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.60 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.61 | 10.61 | 2.62 | 4.75 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.64 | 10.56 | 2.92 | 6.16 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.02 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.75 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.61 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.49 | 13.65 | 2.19 | 8.98 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.71 | 9.60 | 2.71 | 7.73 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.42 | 6.22 | 2.47 | 2.40 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.80 | 3.19 | 2.50 | 0.04 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.75 | 10.02 | 2.59 | 5.48 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.80 | 3.19 | 2.19 | 0.04 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.44 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.65 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.80 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.11 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.03 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.58 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.48 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.18 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.88 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.83 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.94 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.06 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.06 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.18 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.2 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.20 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.32 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.55 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.53 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.2 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.02 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.40 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.31 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.58 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.18 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.18 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.84 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.08 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.63 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.63 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.84 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.84 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.33 | 3.77 | 8.01 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.02 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.46 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.91 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.63 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.91 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.186591E+11 | -.332341E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131475E+10 | 68.72 | 0.00 | 0.00 |
February | 0.170750E+11 | -.302366E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.118207E+10 | 68.47 | 0.00 | 0.00 |
March | 0.207004E+11 | -.351778E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128971E+10 | 67.74 | 0.00 | 0.00 |
April | 0.170605E+11 | -.312529E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.126572E+10 | 68.46 | 0.00 | 0.00 |
May | 0.178708E+11 | -.325130E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131063E+10 | 68.48 | 0.00 | 0.00 |
June | 0.173012E+11 | -.314953E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125648E+10 | 68.04 | 0.00 | 0.00 |
July | 0.146974E+11 | -.295311E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132896E+10 | 69.24 | 0.00 | 0.00 |
August | 0.175775E+11 | -.322619E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129997E+10 | 68.13 | 0.00 | 0.00 |
September | 0.153279E+11 | -.296317E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127274E+10 | 68.71 | 0.00 | 0.00 |
October | 0.165401E+11 | -.312522E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132190E+10 | 69.00 | 0.00 | 0.00 |
November | 0.173136E+11 | -.314581E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127806E+10 | 68.96 | 0.00 | 0.00 |
December | 0.173654E+11 | -.320313E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131606E+10 | 68.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.207489E+12 | -.380076E+12 | 8760.00 | -.154370E+11 | 68.57 | |||||
Minimum of Months | 0.146974E+11 | -.351778E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.132896E+10 | 67.74 | 0.00 | 0.00 |
Maximum of Months | 0.207004E+11 | -.295311E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.118207E+10 | 69.24 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | ||||||||||
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.708334E+09 | 484897.16 | 03-JAN-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311828E+09 | 440930.79 | 28-FEB-23:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129047E+09 | 264094.10 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 60303701.64 | 76189.83 | 15-DEC-22:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120951E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.708334E+09 | 484897.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.296562E+09 | 74268.35 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10996442.47 | 3707.86 | 27-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3545943.55 | 1780.95 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38143050.59 | 56708.01 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349248E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296562E+09 | 74268.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460115E+09 | 113000.17 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29059659.61 | 57388.26 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211652E+09 | 113481.73 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6917775.22 | 3261.50 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13612833.25 | 21563.00 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50900583.67 | 48192.39 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.772257E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460115E+09 | 113481.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.689652E+09 | 106281.94 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.557338E+09 | 107702.71 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496204E+09 | 107309.71 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37946913.22 | 15726.00 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 500375.66 | 833.96 | 30-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61109618.79 | 21580.77 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361849E+09 | 106683.78 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220460E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.689652E+09 | 107702.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49226382.46 | 12939.76 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221226E+09 | 134247.38 | 29-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11164557.72 | 4191.85 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18443011.01 | 8669.08 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300060E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221226E+09 | 134247.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660205E+09 | 71209.04 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169233E+09 | 67436.26 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300501E+09 | 96282.61 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56935495.98 | 13320.49 | 01-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7980114.58 | 2631.44 | 30-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155284E+09 | 17591.67 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135014E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.660205E+09 | 96282.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.875336E+09 | 13231.76 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495204E+09 | 13707.90 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519461E+09 | 13307.98 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78756697.67 | 13150.48 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27315030.39 | 12982.83 | 15-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57900634.60 | 13104.76 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354098E+09 | 13059.60 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.634378E+09 | 13816.27 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304245E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.875336E+09 | 13816.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.620408E+09 | 13118.31 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.472801E+09 | 13262.53 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427976E+09 | 13122.00 | 28-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72781204.28 | 13094.64 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17761534.74 | 8129.66 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1084972.27 | 216.99 | 12-JUN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3764841.11 | 1216.60 | 20-SEP-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49260662.43 | 11973.49 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241272E+09 | 13055.42 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472936E+09 | 13219.80 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238005E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.620408E+09 | 13262.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417385E+09 | 15723.67 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334335E+09 | 16294.10 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.448556E+09 | 15728.12 | 28-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79426822.93 | 15426.09 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47025469.39 | 15424.23 | 15-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19455908.34 | 3971.33 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117196E+09 | 15498.93 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253228E+09 | 16045.03 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171661E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.448556E+09 | 16294.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.657716E+09 | 13304.77 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431546E+09 | 13315.39 | 25-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405258E+09 | 13308.50 | 28-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79710205.21 | 13219.39 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44436859.85 | 7110.83 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 278379.55 | 212.62 | 01-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63239873.25 | 2621.80 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280885E+09 | 13230.27 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485347E+09 | 13410.79 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244842E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657716E+09 | 13410.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.709661E+09 | 236913.70 | 16-JAN-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745272E+09 | 236811.37 | 20-FEB-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213205E+09 | 236922.82 | 13-MAR-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458651E+09 | 236922.25 | 23-APR-22:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234007E+09 | 236915.63 | 29-MAY-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294983E+09 | 236917.64 | 05-JUN-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118790E+10 | 236919.20 | 04-JUL-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.870627E+09 | 235956.19 | 27-AUG-23:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.352660E+09 | 236603.76 | 04-SEP-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167846E+10 | 236922.01 | 09-OCT-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127518E+10 | 236925.69 | 12-NOV-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201819E+10 | 236946.97 | 10-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100388E+11 | |||||||
Minimum of Months | 0.213205E+09 | 235956.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201819E+10 | 236946.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198127E+10 | 30096.52 | 28-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752162E+09 | 15640.69 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123660E+10 | 21396.33 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36304196.25 | 15261.67 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75248658.53 | 6089.24 | 10-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7341386.31 | 3841.06 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55414161.70 | 6590.10 | 18-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.724703E+09 | 17975.05 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486905E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198127E+10 | 30096.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.462894E+11 | 284183.23 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326742E+11 | 269869.80 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496652E+11 | 278751.83 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125305E+11 | 249587.08 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774741E+10 | 129009.36 | 10-MAY-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.337437E+09 | 86659.72 | 12-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299535E+09 | 66928.28 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257065E+10 | 177698.96 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182687E+11 | 214874.48 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.391671E+11 | 278968.68 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209550E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.496652E+11 | 284183.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.575555E+10 | 29398.28 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414809E+10 | 27889.97 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686002E+10 | 28836.66 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147728E+10 | 25792.81 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.834942E+09 | 13305.75 | 10-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35960077.48 | 8922.75 | 12-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 399894.01 | 111.08 | 28-AUG-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36209645.00 | 8195.74 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291595E+09 | 18824.50 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225729E+10 | 22201.14 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498901E+10 | 28858.67 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266863E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686002E+10 | 29398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.131248E+11 | 0.130089E+11 | 83638.06 | 16-JAN-15:20 | 56745.82 | 0.12 |
February | 0.00 | 0.00 | 0.617350E+10 | 0.608130E+10 | 74946.52 | 13-FEB-05:52 | 34132.58 | 0.08 |
March | 0.00 | 0.00 | 0.682026E+10 | 0.671548E+10 | 53449.83 | 24-MAR-03:01 | 22543.65 | 0.11 |
April | 0.00 | 0.00 | 0.171903E+11 | 0.169294E+11 | 89145.24 | 30-APR-21:51 | 38834.82 | 0.26 |
May | 0.00 | 0.00 | 0.168666E+11 | 0.166685E+11 | 94938.64 | 29-MAY-09:58 | 70858.42 | 0.26 |
June | 0.00 | 0.00 | 0.299349E+11 | 0.286502E+11 | 95213.19 | 30-JUN-03:01 | 40583.81 | 0.39 |
July | 0.00 | 0.00 | 0.500557E+11 | 0.430168E+11 | 118621.86 | 23-JUL-17:42 | 74491.59 | 0.45 |
August | 0.00 | 0.00 | 0.572964E+11 | 0.476424E+11 | 142769.90 | 06-AUG-14:41 | 81658.25 | 0.50 |
September | 0.00 | 0.00 | 0.349668E+11 | 0.313841E+11 | 109281.69 | 22-SEP-03:01 | 45046.45 | 0.38 |
October | 0.00 | 0.00 | 0.461247E+11 | 0.404426E+11 | 138946.27 | 01-OCT-14:08 | 75307.83 | 0.29 |
November | 0.00 | 0.00 | 0.148675E+11 | 0.145572E+11 | 87140.85 | 19-NOV-15:18 | 64365.69 | 0.14 |
December | 0.00 | 0.00 | 0.178147E+11 | 0.177461E+11 | 76464.96 | 25-DEC-15:21 | 76464.96 | 0.04 |
Annual Sum or Average | 0.311236E+12 | 0.282843E+12 | 0.25 | |||||
Minimum of Months | 0.00 | 0.00 | 0.617350E+10 | 0.608130E+10 | 53449.83 | 22543.65 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.572964E+11 | 0.476424E+11 | 142769.90 | 81658.25 | 0.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.253889E+11 | 0.250809E+11 | 92952.36 | 17-JAN-13:50 | 78831.61 | 0.20 |
February | 0.00 | 0.00 | 0.170168E+11 | 0.163059E+11 | 88160.98 | 01-FEB-12:00 | 88160.98 | 0.19 |
March | 0.00 | 0.00 | 0.201379E+11 | 0.184773E+11 | 111636.28 | 23-MAR-15:00 | 74605.87 | 0.23 |
April | 0.00 | 0.00 | 0.412176E+11 | 0.381139E+11 | 113918.07 | 26-APR-11:00 | 95125.64 | 0.42 |
May | 0.00 | 0.00 | 0.373406E+11 | 0.362859E+11 | 84371.06 | 04-MAY-14:00 | 73038.02 | 0.44 |
June | 0.00 | 0.00 | 0.715658E+11 | 0.561433E+11 | 138072.83 | 29-JUN-13:00 | 79934.32 | 0.60 |
July | 0.00 | 0.00 | 0.126184E+12 | 0.786914E+11 | 181310.37 | 31-JUL-15:40 | 98078.65 | 0.71 |
August | 0.00 | 0.00 | 0.151830E+12 | 0.892678E+11 | 180903.24 | 18-AUG-15:50 | 97048.92 | 0.76 |
September | 0.00 | 0.00 | 0.803763E+11 | 0.572875E+11 | 154983.78 | 22-SEP-11:40 | 72419.87 | 0.56 |
October | 0.00 | 0.00 | 0.886505E+11 | 0.702723E+11 | 182547.65 | 04-OCT-05:01 | 88129.19 | 0.40 |
November | 0.00 | 0.00 | 0.314078E+11 | 0.303660E+11 | 96863.07 | 28-NOV-14:00 | 96863.07 | 0.23 |
December | 0.00 | 0.00 | 0.335004E+11 | 0.333950E+11 | 102540.46 | 05-DEC-15:00 | 102540.46 | 0.11 |
Annual Sum or Average | 0.724616E+12 | 0.549687E+12 | 0.41 | |||||
Minimum of Months | 0.00 | 0.00 | 0.170168E+11 | 0.163059E+11 | 84371.06 | 72419.87 | 0.11 | |
Maximum of Months | 0.00 | 0.00 | 0.151830E+12 | 0.892678E+11 | 182547.65 | 102540.46 | 0.76 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.212070E+12 | 0.209849E+12 | 768884.36 | 18-JAN-13:10 | 768884.36 | 0.20 |
February | 0.00 | 0.00 | 0.134597E+12 | 0.129461E+12 | 757358.73 | 01-FEB-12:00 | 757358.73 | 0.19 |
March | 0.00 | 0.00 | 0.151576E+12 | 0.139147E+12 | 931281.09 | 23-MAR-15:00 | 626925.90 | 0.22 |
April | 0.00 | 0.00 | 0.301539E+12 | 0.280861E+12 | 943342.35 | 26-APR-11:00 | 773212.65 | 0.38 |
May | 0.00 | 0.00 | 0.312215E+12 | 0.303379E+12 | 759676.04 | 04-MAY-14:00 | 659381.35 | 0.42 |
June | 0.00 | 0.00 | 0.584103E+12 | 0.459573E+12 | 1205090.84 | 29-JUN-13:00 | 699054.30 | 0.56 |
July | 0.00 | 0.00 | 0.970866E+12 | 0.609768E+12 | 1526903.76 | 31-JUL-15:40 | 828429.36 | 0.58 |
August | 0.00 | 0.00 | 0.112601E+13 | 0.671722E+12 | 1534794.98 | 18-AUG-15:50 | 825573.41 | 0.61 |
September | 0.00 | 0.00 | 0.689112E+12 | 0.493190E+12 | 1384085.00 | 22-SEP-12:30 | 685680.12 | 0.53 |
October | 0.00 | 0.00 | 0.722850E+12 | 0.576312E+12 | 1610655.60 | 04-OCT-05:01 | 780469.85 | 0.37 |
November | 0.00 | 0.00 | 0.234862E+12 | 0.228169E+12 | 737921.55 | 28-NOV-14:00 | 737921.55 | 0.22 |
December | 0.00 | 0.00 | 0.244013E+12 | 0.243444E+12 | 785899.36 | 05-DEC-15:00 | 785899.36 | 0.10 |
Annual Sum or Average | 0.568381E+13 | 0.434488E+13 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 0.134597E+12 | 0.129461E+12 | 737921.55 | 626925.90 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.112601E+13 | 0.671722E+12 | 1610655.60 | 828429.36 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177030E+11 | 0.175532E+11 | 73448.11 | 18-JAN-13:30 | 73448.11 | 0.19 |
February | 0.00 | 0.00 | 0.114480E+11 | 0.109881E+11 | 69608.88 | 01-FEB-12:00 | 69608.88 | 0.17 |
March | 0.00 | 0.00 | 0.138614E+11 | 0.126414E+11 | 99020.56 | 23-MAR-15:00 | 66542.58 | 0.20 |
April | 0.00 | 0.00 | 0.302137E+11 | 0.280517E+11 | 103100.47 | 26-APR-13:40 | 99783.17 | 0.36 |
May | 0.00 | 0.00 | 0.314069E+11 | 0.304847E+11 | 88863.56 | 03-MAY-14:00 | 76196.57 | 0.40 |
June | 0.00 | 0.00 | 0.613774E+11 | 0.479559E+11 | 137814.94 | 29-JUN-13:00 | 79668.43 | 0.55 |
July | 0.00 | 0.00 | 0.104095E+12 | 0.651602E+11 | 188794.59 | 31-JUL-15:00 | 107057.88 | 0.57 |
August | 0.00 | 0.00 | 0.119243E+12 | 0.707529E+11 | 186994.89 | 17-AUG-15:30 | 104716.33 | 0.59 |
September | 0.00 | 0.00 | 0.686035E+11 | 0.491345E+11 | 146933.08 | 22-SEP-12:20 | 72010.09 | 0.50 |
October | 0.00 | 0.00 | 0.703055E+11 | 0.558158E+11 | 177055.72 | 05-OCT-05:01 | 76964.55 | 0.35 |
November | 0.00 | 0.00 | 0.197717E+11 | 0.191875E+11 | 70086.05 | 28-NOV-14:00 | 70086.05 | 0.19 |
December | 0.00 | 0.00 | 0.202249E+11 | 0.201817E+11 | 76991.44 | 05-DEC-15:00 | 76991.44 | 0.09 |
Annual Sum or Average | 0.568254E+12 | 0.427907E+12 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 0.114480E+11 | 0.109881E+11 | 69608.88 | 66542.58 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.119243E+12 | 0.707529E+11 | 188794.59 | 107057.88 | 0.59 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.317334E+12 | 0.317068E+12 | 434971.33 | 03-JAN-01:00 | 434971.33 | 0.00 |
February | 0.00 | 0.00 | 0.496957E+12 | 0.496423E+12 | 434363.36 | 28-FEB-23:08 | 434363.36 | 0.00 |
March | 0.00 | 0.00 | 0.785300E+12 | 0.784488E+12 | 429502.89 | 01-MAR-00:10 | 429502.89 | 0.00 |
April | 0.00 | 0.00 | 0.989814E+12 | 0.988923E+12 | 385762.26 | 26-APR-14:40 | 383684.10 | 0.00 |
May | 0.00 | 0.00 | 0.317356E+12 | 0.316307E+12 | 133379.50 | 01-MAY-00:10 | 133379.50 | 0.00 |
June | 0.00 | 0.00 | 0.536538E+12 | 0.533393E+12 | 212342.75 | 28-JUN-13:00 | 207061.81 | 0.00 |
July | 0.00 | 0.00 | 0.793055E+12 | 0.788400E+12 | 302599.04 | 19-JUL-16:00 | 296407.14 | 0.00 |
August | 0.00 | 0.00 | 0.102902E+13 | 0.102433E+13 | 392177.88 | 18-AUG-13:00 | 384817.62 | 0.00 |
September | 0.00 | 0.00 | 0.312246E+12 | 0.308942E+12 | 135175.98 | 01-SEP-00:08 | 134091.37 | 0.00 |
October | 0.00 | 0.00 | 0.556685E+12 | 0.554736E+12 | 214156.00 | 03-OCT-15:00 | 207753.21 | 0.00 |
November | 0.00 | 0.00 | 0.763553E+12 | 0.763060E+12 | 425882.02 | 05-NOV-01:27 | 424424.95 | 0.00 |
December | 0.00 | 0.00 | 0.102450E+13 | 0.102436E+13 | 422372.08 | 15-DEC-22:25 | 422372.08 | 0.00 |
Annual Sum or Average | 0.792237E+13 | 0.790044E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.312246E+12 | 0.308942E+12 | 133379.50 | 133379.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102902E+13 | 0.102436E+13 | 434971.33 | 434971.33 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.521444E+10 | 0.521444E+10 | 2391.53 | 30-JAN-16:40 | 2391.53 | 0.00 |
February | 0.00 | 0.00 | 0.922074E+10 | 0.922074E+10 | 4296.92 | 22-FEB-17:00 | 4296.92 | 0.00 |
March | 0.00 | 0.00 | 0.151811E+11 | 0.151811E+11 | 6168.85 | 19-MAR-17:30 | 6168.85 | 0.00 |
April | 0.00 | 0.00 | 0.195164E+11 | 0.195164E+11 | 7989.19 | 16-APR-17:13 | 7989.19 | 0.00 |
May | 0.00 | 0.00 | 0.545214E+10 | 0.545214E+10 | 2420.09 | 01-MAY-00:05 | 2420.09 | 0.00 |
June | 0.00 | 0.00 | 0.101596E+11 | 0.101596E+11 | 4191.77 | 25-JUN-17:42 | 4191.77 | 0.00 |
July | 0.00 | 0.00 | 0.153749E+11 | 0.153749E+11 | 6114.37 | 04-JUL-17:57 | 6114.37 | 0.00 |
August | 0.00 | 0.00 | 0.202141E+11 | 0.202141E+11 | 8012.14 | 06-AUG-17:57 | 8012.14 | 0.00 |
September | 0.00 | 0.00 | 0.539140E+10 | 0.539140E+10 | 2436.06 | 01-SEP-00:08 | 2436.06 | 0.00 |
October | 0.00 | 0.00 | 0.104652E+11 | 0.104652E+11 | 4391.77 | 15-OCT-16:38 | 4391.77 | 0.00 |
November | 0.00 | 0.00 | 0.147870E+11 | 0.147870E+11 | 6096.80 | 06-NOV-16:20 | 6096.80 | 0.00 |
December | 0.00 | 0.00 | 0.201176E+11 | 0.201176E+11 | 7987.87 | 25-DEC-16:02 | 7987.87 | 0.00 |
Annual Sum or Average | 0.151095E+12 | 0.151095E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.521444E+10 | 0.521444E+10 | 2391.53 | 2391.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202141E+11 | 0.202141E+11 | 8012.14 | 8012.14 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.406590E+11 | 0.406590E+11 | 21887.99 | 30-JAN-16:50 | 21887.99 | 0.00 |
February | 0.00 | 0.00 | 0.798546E+11 | 0.798546E+11 | 40199.36 | 22-FEB-17:00 | 40199.36 | 0.00 |
March | 0.00 | 0.00 | 0.136817E+12 | 0.136817E+12 | 57403.94 | 10-MAR-17:00 | 57403.94 | 0.00 |
April | 0.00 | 0.00 | 0.181721E+12 | 0.181721E+12 | 74698.87 | 27-APR-17:30 | 74698.87 | 0.00 |
May | 0.00 | 0.00 | 0.468730E+11 | 0.468730E+11 | 21890.62 | 29-MAY-18:07 | 21890.62 | 0.00 |
June | 0.00 | 0.00 | 0.932183E+11 | 0.932183E+11 | 39215.18 | 25-JUN-17:58 | 39215.18 | 0.00 |
July | 0.00 | 0.00 | 0.144719E+12 | 0.144719E+12 | 57372.48 | 04-JUL-17:55 | 57372.48 | 0.00 |
August | 0.00 | 0.00 | 0.191211E+12 | 0.191211E+12 | 74936.69 | 31-AUG-17:00 | 74936.69 | 0.00 |
September | 0.00 | 0.00 | 0.472216E+11 | 0.472216E+11 | 22961.86 | 29-SEP-16:30 | 22961.86 | 0.00 |
October | 0.00 | 0.00 | 0.944099E+11 | 0.944099E+11 | 40805.76 | 17-OCT-16:40 | 40805.76 | 0.00 |
November | 0.00 | 0.00 | 0.133603E+12 | 0.133603E+12 | 57536.13 | 12-NOV-16:24 | 57536.13 | 0.00 |
December | 0.00 | 0.00 | 0.183036E+12 | 0.183036E+12 | 74445.98 | 18-DEC-16:20 | 74445.98 | 0.00 |
Annual Sum or Average | 0.137335E+13 | 0.137335E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.406590E+11 | 0.406590E+11 | 21887.99 | 21887.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.191211E+12 | 0.191211E+12 | 74936.69 | 74936.69 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.275023E+10 | 0.275023E+10 | 2151.75 | 26-JAN-16:10 | 2151.75 | 0.00 |
February | 0.00 | 0.00 | 0.699721E+10 | 0.699721E+10 | 4022.87 | 22-FEB-17:00 | 4022.87 | 0.00 |
March | 0.00 | 0.00 | 0.127654E+11 | 0.127654E+11 | 5782.75 | 10-MAR-17:00 | 5782.75 | 0.00 |
April | 0.00 | 0.00 | 0.176711E+11 | 0.176711E+11 | 7534.31 | 26-APR-17:10 | 7534.31 | 0.00 |
May | 0.00 | 0.00 | 0.418950E+10 | 0.418950E+10 | 2260.66 | 29-MAY-17:25 | 2260.66 | 0.00 |
June | 0.00 | 0.00 | 0.907537E+10 | 0.907537E+10 | 4051.16 | 25-JUN-17:35 | 4051.16 | 0.00 |
July | 0.00 | 0.00 | 0.143590E+11 | 0.143590E+11 | 5892.50 | 04-JUL-17:45 | 5892.50 | 0.00 |
August | 0.00 | 0.00 | 0.189692E+11 | 0.189692E+11 | 7624.60 | 20-AUG-17:28 | 7624.60 | 0.00 |
September | 0.00 | 0.00 | 0.437975E+10 | 0.437975E+10 | 2378.30 | 29-SEP-16:30 | 2378.30 | 0.00 |
October | 0.00 | 0.00 | 0.891133E+10 | 0.891133E+10 | 4196.41 | 15-OCT-16:36 | 4196.41 | 0.00 |
November | 0.00 | 0.00 | 0.123940E+11 | 0.123940E+11 | 5708.34 | 07-NOV-16:20 | 5708.34 | 0.00 |
December | 0.00 | 0.00 | 0.170821E+11 | 0.170821E+11 | 7441.14 | 19-DEC-16:20 | 7441.14 | 0.00 |
Annual Sum or Average | 0.129544E+12 | 0.129544E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.275023E+10 | 0.275023E+10 | 2151.75 | 2151.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.189692E+11 | 0.189692E+11 | 7624.60 | 7624.60 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7326.56 | 37949.41 | 01-JAN-07:55 | 11258.51 | 45617.98 | 30-JAN-12:50 |
February | 6963.21 | 37939.40 | 26-FEB-08:70 | 11386.60 | 45616.66 | 06-FEB-12:50 |
March | 5719.94 | 37982.61 | 26-MAR-07:10 | 12062.17 | 45397.24 | 01-MAR-12:20 |
April | 6806.52 | 38065.03 | 30-APR-06:48 | 10858.28 | 44597.85 | 03-APR-11:40 |
May | 6683.91 | 38137.77 | 29-MAY-07:00 | 10957.04 | 43633.78 | 01-MAY-12:00 |
June | 6052.59 | 38192.40 | 25-JUN-06:50 | 11024.31 | 42543.90 | 01-JUN-11:50 |
July | 7720.00 | 38225.54 | 30-JUL-06:38 | 9650.47 | 41686.10 | 03-JUL-11:40 |
August | 6012.61 | 38225.93 | 06-AUG-06:38 | 10834.09 | 41601.58 | 31-AUG-11:40 |
September | 6995.39 | 38206.25 | 03-SEP-06:45 | 10151.04 | 42309.57 | 29-SEP-11:20 |
October | 7518.46 | 38157.02 | 01-OCT-07:00 | 10429.31 | 43392.87 | 31-OCT-11:30 |
November | 7555.90 | 38071.48 | 05-NOV-06:50 | 10964.19 | 44453.26 | 30-NOV-12:40 |
December | 7423.34 | 38002.81 | 03-DEC-08:00 | 10727.95 | 45237.63 | 29-DEC-12:20 |
Annual Sum or Average | 6898.17 | 10855.52 | ||||
Minimum of Months | 5719.94 | 37939.40 | 9650.47 | 41601.58 | ||
Maximum of Months | 7720.00 | 38225.93 | 12062.17 | 45617.98 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 22045.56 | 576659.47 | 30-JAN-01:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16829.97 | 645882.53 | 20-FEB-03:30 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22507.78 | 681973.50 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5739.83 | 773696.12 | 23-APR-22:56 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 3281.26 | 515763.00 | 29-MAY-08:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 325.02 | 578075.93 | 18-JUN-23:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 451.39 | 295838.15 | 02-JUL-22:08 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 318.87 | 230445.20 | 27-AUG-23:08 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 213.04 | 496496.74 | 24-SEP-16:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1701.47 | 499858.19 | 15-OCT-13:48 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 8750.04 | 671796.57 | 26-NOV-15:10 |
December | 3.09 | 13779.30 | 05-DEC-16:30 | 18303.05 | 625517.64 | 31-DEC-15:25 |
Annual Sum or Average | 0.26 | 8353.34 | ||||
Minimum of Months | 0.00 | 0.00 | 213.04 | 230445.20 | ||
Maximum of Months | 3.09 | 13779.30 | 22507.78 | 773696.12 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 176832.05 | 1260140.36 | 13-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 134714.04 | 1318850.21 | 01-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 126180.99 | 1235391.73 | 22-MAR-12:30 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 256824.10 | 1260635.76 | 26-APR-10:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 267522.02 | 1185942.71 | 04-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 428694.39 | 1559011.18 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 603743.52 | 1977881.72 | 31-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 676686.48 | 2020609.36 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 463035.71 | 1799518.96 | 22-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 465602.07 | 2151872.46 | 04-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 210188.99 | 1172355.26 | 27-NOV-15:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 195810.48 | 1199822.11 | 05-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 335391.77 | 0.00 | ||||
Minimum of Months | 126180.99 | 1172355.26 | 0.00 | 0.00 | ||
Maximum of Months | 676686.48 | 2151872.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117057.92 | 1260901.91 | 13-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 80469.02 | 1116139.29 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82239.04 | 1236026.51 | 22-MAR-13:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 176864.77 | 1262371.13 | 26-APR-10:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 175313.10 | 1180818.36 | 04-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 325727.06 | 1555421.00 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 506886.50 | 1974650.67 | 31-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 581372.74 | 2409304.88 | 07-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 372140.46 | 2201226.56 | 30-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 380716.87 | 2618011.96 | 04-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 134987.08 | 1173983.30 | 19-NOV-13:43 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 134659.75 | 1196077.38 | 05-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 257179.01 | 0.00 | ||||
Minimum of Months | 80469.02 | 1116139.29 | 0.00 | 0.00 | ||
Maximum of Months | 581372.74 | 2618011.96 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 200305.86 | 630497.93 | 18-JAN-13:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 325273.03 | 829070.31 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 476110.47 | 929040.75 | 11-MAR-12:00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 701495.40 | 1314727.85 | 26-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 214973.62 | 534999.55 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 425378.83 | 790756.01 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 694024.88 | 1168798.74 | 31-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 909138.08 | 1370093.52 | 18-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 281608.14 | 1162346.18 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 493212.48 | 1437681.91 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 509291.25 | 1092218.37 | 19-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 677850.05 | 1248582.11 | 19-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 493903.92 | 0.00 | ||||
Minimum of Months | 200305.86 | 534999.55 | 0.00 | 0.00 | ||
Maximum of Months | 909138.08 | 1437681.91 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 141228.59 | 2057434.48 | 17-JAN-14:00 | 765.30 | 81557.77 | 09-JAN-06:50 |
February | 101077.47 | 1611986.43 | 01-FEB-12:00 | 542.82 | 64076.91 | 07-FEB-07:00 |
March | 106506.50 | 2298761.05 | 22-MAR-12:40 | 376.24 | 61403.15 | 09-MAR-06:40 |
April | 220159.35 | 2614278.04 | 26-APR-11:00 | 305.97 | 45103.52 | 01-APR-05:15 |
May | 207899.77 | 2099818.42 | 04-MAY-14:00 | 180.63 | 48434.40 | 26-MAY-18:10 |
June | 485430.54 | 4020463.04 | 29-JUN-13:00 | 47.24 | 25272.16 | 12-JUN-07:00 |
July | 959279.02 | 5355643.40 | 31-JUL-15:50 | 21.19 | 20538.66 | 08-JUL-23:05 |
August | 1144718.96 | 5266818.60 | 18-AUG-16:00 | 29.59 | 22448.86 | 28-AUG-06:00 |
September | 598602.64 | 4980207.25 | 22-SEP-12:30 | 80.11 | 34446.94 | 19-SEP-05:50 |
October | 599558.21 | 4740278.73 | 04-OCT-11:00 | 137.44 | 58362.57 | 25-OCT-06:00 |
November | 157527.94 | 1621605.11 | 28-NOV-13:40 | 489.20 | 66463.59 | 29-NOV-04:30 |
December | 150394.73 | 1699733.58 | 05-DEC-14:50 | 589.00 | 78790.91 | 28-DEC-06:40 |
Annual Sum or Average | 408983.40 | 295.77 | ||||
Minimum of Months | 101077.47 | 1611986.43 | 21.19 | 20538.66 | ||
Maximum of Months | 1144718.96 | 5355643.40 | 765.30 | 81557.77 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181353E+11 | 0.98 | 10627.82 | 01-JAN-00:20 | 1.54 |
February | 0.157595E+11 | 0.94 | 10627.82 | 01-FEB-04:01 | 1.54 |
March | 0.180492E+11 | 0.97 | 10627.82 | 01-MAR-04:01 | 1.54 |
April | 0.166892E+11 | 0.93 | 10627.82 | 01-APR-03:01 | 1.54 |
May | 0.177505E+11 | 0.96 | 10627.82 | 01-MAY-00:11 | 1.53 |
June | 0.173515E+11 | 0.96 | 10627.82 | 01-JUN-03:01 | 1.54 |
July | 0.173398E+11 | 0.93 | 10627.82 | 01-JUL-03:01 | 1.53 |
August | 0.184996E+11 | 0.99 | 10627.82 | 01-AUG-03:01 | 1.53 |
September | 0.174689E+11 | 0.97 | 10627.82 | 01-SEP-03:01 | 1.53 |
October | 0.183964E+11 | 0.99 | 10627.82 | 01-OCT-14:04 | 1.53 |
November | 0.178912E+11 | 1.00 | 10627.82 | 01-NOV-03:01 | 1.54 |
December | 0.180969E+11 | 0.98 | 10627.82 | 01-DEC-04:01 | 1.54 |
Annual Sum or Average | 0.211428E+12 | 0.97 | |||
Minimum of Months | 0.157595E+11 | 0.93 | 10627.82 | 1.53 | |
Maximum of Months | 0.184996E+11 | 1.00 | 10627.82 | 1.54 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.599360E+10 | 0.40 | 16806.86 | 21-JAN-06:01 | 1.62 |
February | 0.576665E+10 | 0.42 | 13993.51 | 03-FEB-06:01 | 1.46 |
March | 0.730808E+10 | 0.46 | 13993.51 | 03-MAR-04:01 | 1.45 |
April | 0.727473E+10 | 0.49 | 16790.10 | 27-APR-05:01 | 1.62 |
May | 0.575827E+10 | 0.41 | 14519.53 | 20-MAY-05:01 | 1.48 |
June | 0.626606E+10 | 0.44 | 21112.00 | 26-JUN-05:03 | 1.88 |
July | 0.687596E+10 | 0.48 | 21184.65 | 24-JUL-05:03 | 1.88 |
August | 0.797723E+10 | 0.53 | 20511.29 | 07-AUG-05:01 | 1.84 |
September | 0.576510E+10 | 0.41 | 21372.12 | 05-SEP-05:03 | 1.89 |
October | 0.657472E+10 | 0.44 | 21166.18 | 04-OCT-05:01 | 1.88 |
November | 0.716464E+10 | 0.46 | 13993.51 | 02-NOV-03:01 | 1.45 |
December | 0.755607E+10 | 0.46 | 13993.51 | 01-DEC-04:01 | 1.45 |
Annual Sum or Average | 0.802811E+11 | 0.45 | |||
Minimum of Months | 0.575827E+10 | 0.40 | 13993.51 | 1.45 | |
Maximum of Months | 0.797723E+10 | 0.53 | 21372.12 | 1.89 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438835E+11 | 0.35 | 114667.33 | 03-JAN-06:01 | 1.35 |
February | 0.393563E+11 | 0.35 | 100959.01 | 01-FEB-05:03 | 1.25 |
March | 0.455378E+11 | 0.37 | 131548.96 | 30-MAR-05:01 | 1.47 |
April | 0.437479E+11 | 0.36 | 127991.38 | 24-APR-05:01 | 1.44 |
May | 0.444787E+11 | 0.36 | 132008.80 | 03-MAY-05:01 | 1.46 |
June | 0.467187E+11 | 0.38 | 193312.25 | 30-JUN-05:01 | 1.86 |
July | 0.473270E+11 | 0.38 | 198076.52 | 01-JUL-05:01 | 1.89 |
August | 0.521345E+11 | 0.41 | 198076.52 | 07-AUG-05:01 | 1.89 |
September | 0.464287E+11 | 0.37 | 198076.52 | 30-SEP-05:01 | 1.90 |
October | 0.483204E+11 | 0.38 | 182472.00 | 04-OCT-05:01 | 1.79 |
November | 0.453722E+11 | 0.37 | 100959.01 | 01-NOV-04:03 | 1.24 |
December | 0.444664E+11 | 0.36 | 108379.57 | 13-DEC-06:01 | 1.30 |
Annual Sum or Average | 0.547772E+12 | 0.37 | |||
Minimum of Months | 0.393563E+11 | 0.35 | 100959.01 | 1.24 | |
Maximum of Months | 0.521345E+11 | 0.41 | 198076.52 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338937E+10 | 0.31 | 9601.13 | 21-JAN-06:01 | 1.18 |
February | 0.313382E+10 | 0.31 | 9601.13 | 02-FEB-06:01 | 1.18 |
March | 0.373025E+10 | 0.34 | 9601.13 | 03-MAR-06:01 | 1.18 |
April | 0.408332E+10 | 0.34 | 13340.82 | 27-APR-05:01 | 1.44 |
May | 0.416961E+10 | 0.34 | 10982.24 | 03-MAY-05:01 | 1.28 |
June | 0.471471E+10 | 0.37 | 12701.35 | 23-JUN-05:01 | 1.40 |
July | 0.506374E+10 | 0.38 | 20468.15 | 19-JUL-05:01 | 1.89 |
August | 0.548891E+10 | 0.40 | 12519.49 | 04-AUG-05:01 | 1.39 |
September | 0.441965E+10 | 0.35 | 20468.15 | 30-SEP-05:01 | 1.90 |
October | 0.435033E+10 | 0.35 | 17109.09 | 03-OCT-05:01 | 1.69 |
November | 0.347899E+10 | 0.32 | 9601.13 | 01-NOV-05:01 | 1.18 |
December | 0.335991E+10 | 0.31 | 9601.13 | 06-DEC-06:01 | 1.19 |
Annual Sum or Average | 0.493826E+11 | 0.34 | |||
Minimum of Months | 0.313382E+10 | 0.31 | 9601.13 | 1.18 | |
Maximum of Months | 0.548891E+10 | 0.40 | 20468.15 | 1.90 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.958654E+11 | 1.38 | 35792.05 | 01-JAN-00:05 | 1.38 |
February | 0.865881E+11 | 1.38 | 35792.05 | 01-FEB-00:10 | 1.38 |
March | 0.958654E+11 | 1.38 | 35792.05 | 01-MAR-00:05 | 1.38 |
April | 0.927730E+11 | 1.38 | 35792.05 | 01-APR-00:10 | 1.38 |
May | 0.958654E+11 | 1.38 | 35792.05 | 01-MAY-00:11 | 1.38 |
June | 0.927730E+11 | 1.38 | 35792.05 | 01-JUN-00:20 | 1.38 |
July | 0.958654E+11 | 1.38 | 35792.05 | 01-JUL-00:10 | 1.38 |
August | 0.958654E+11 | 1.38 | 35792.05 | 01-AUG-00:03 | 1.38 |
September | 0.927730E+11 | 1.38 | 35792.05 | 01-SEP-00:05 | 1.38 |
October | 0.958654E+11 | 1.38 | 35792.05 | 01-OCT-00:10 | 1.38 |
November | 0.927730E+11 | 1.38 | 35792.05 | 01-NOV-00:10 | 1.38 |
December | 0.958654E+11 | 1.38 | 35792.05 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.112874E+13 | 1.38 | |||
Minimum of Months | 0.865881E+11 | 1.38 | 35792.05 | 1.38 | |
Maximum of Months | 0.958654E+11 | 1.38 | 35792.05 | 1.38 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141227E+10 | 0.93 | 527.28 | 01-JAN-00:05 | 0.93 |
February | 0.127560E+10 | 0.93 | 527.28 | 01-FEB-00:10 | 0.93 |
March | 0.141227E+10 | 0.93 | 527.28 | 01-MAR-00:05 | 0.93 |
April | 0.136671E+10 | 0.93 | 527.28 | 01-APR-00:10 | 0.93 |
May | 0.141227E+10 | 0.93 | 527.28 | 01-MAY-00:05 | 0.93 |
June | 0.136671E+10 | 0.93 | 527.28 | 01-JUN-00:10 | 0.93 |
July | 0.141227E+10 | 0.93 | 527.28 | 01-JUL-00:10 | 0.93 |
August | 0.141227E+10 | 0.93 | 527.28 | 01-AUG-00:03 | 0.93 |
September | 0.136671E+10 | 0.93 | 527.28 | 01-SEP-00:03 | 0.93 |
October | 0.141227E+10 | 0.93 | 527.28 | 01-OCT-00:10 | 0.93 |
November | 0.136671E+10 | 0.93 | 527.28 | 01-NOV-00:10 | 0.93 |
December | 0.141227E+10 | 0.93 | 527.28 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.166284E+11 | 0.93 | |||
Minimum of Months | 0.127560E+10 | 0.93 | 527.28 | 0.93 | |
Maximum of Months | 0.141227E+10 | 0.93 | 527.28 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134029E+11 | 0.93 | 5004.05 | 01-JAN-00:05 | 0.93 |
February | 0.121058E+11 | 0.93 | 5004.05 | 01-FEB-00:10 | 0.93 |
March | 0.134029E+11 | 0.93 | 5004.05 | 01-MAR-00:05 | 0.93 |
April | 0.129705E+11 | 0.93 | 5004.05 | 01-APR-00:10 | 0.93 |
May | 0.134029E+11 | 0.93 | 5004.05 | 01-MAY-00:05 | 0.93 |
June | 0.129705E+11 | 0.93 | 5004.05 | 01-JUN-00:10 | 0.93 |
July | 0.134029E+11 | 0.93 | 5004.05 | 01-JUL-00:10 | 0.93 |
August | 0.134029E+11 | 0.93 | 5004.05 | 01-AUG-00:03 | 0.93 |
September | 0.129705E+11 | 0.93 | 5004.05 | 01-SEP-00:03 | 0.93 |
October | 0.134029E+11 | 0.93 | 5004.05 | 01-OCT-00:10 | 0.93 |
November | 0.129705E+11 | 0.93 | 5004.05 | 01-NOV-00:10 | 0.93 |
December | 0.134029E+11 | 0.93 | 5004.05 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.157808E+12 | 0.93 | |||
Minimum of Months | 0.121058E+11 | 0.93 | 5004.05 | 0.93 | |
Maximum of Months | 0.134029E+11 | 0.93 | 5004.05 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136510E+10 | 0.93 | 509.67 | 01-JAN-00:05 | 0.93 |
February | 0.123299E+10 | 0.93 | 509.67 | 01-FEB-00:10 | 0.93 |
March | 0.136510E+10 | 0.93 | 509.67 | 01-MAR-00:05 | 0.93 |
April | 0.132107E+10 | 0.93 | 509.67 | 01-APR-00:10 | 0.93 |
May | 0.136510E+10 | 0.93 | 509.67 | 01-MAY-00:05 | 0.93 |
June | 0.132107E+10 | 0.93 | 509.67 | 01-JUN-00:10 | 0.93 |
July | 0.136510E+10 | 0.93 | 509.67 | 01-JUL-00:10 | 0.93 |
August | 0.136510E+10 | 0.93 | 509.67 | 01-AUG-00:03 | 0.93 |
September | 0.132107E+10 | 0.93 | 509.67 | 01-SEP-00:03 | 0.93 |
October | 0.136510E+10 | 0.93 | 509.67 | 01-OCT-00:10 | 0.93 |
November | 0.132107E+10 | 0.93 | 509.67 | 01-NOV-00:10 | 0.93 |
December | 0.136510E+10 | 0.93 | 509.67 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.160730E+11 | 0.93 | |||
Minimum of Months | 0.123299E+10 | 0.93 | 509.67 | 0.93 | |
Maximum of Months | 0.136510E+10 | 0.93 | 509.67 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.809119E+09 | 0.728207E+09 | 6442.56 | 09-JAN-06:01 | 5798.31 | 5798.31 | 78.80 | 9.97 |
February | 0.395979E+09 | 0.356381E+09 | 5101.81 | 06-FEB-03:40 | 4591.63 | 4591.63 | 63.27 | 7.39 |
March | 0.631415E+09 | 0.568274E+09 | 6407.43 | 29-MAR-05:01 | 5766.69 | 5766.69 | 72.88 | 9.93 |
April | 0.108625E+09 | 97762876.89 | 4256.27 | 30-APR-23:00 | 3830.64 | 3830.64 | 64.83 | 5.91 |
May | 67469525.68 | 60722573.11 | 4266.08 | 29-MAY-22:00 | 3839.47 | 3839.47 | 69.66 | 5.91 |
June | 7533582.04 | 6780223.84 | 4264.23 | 26-JUN-01:30 | 3837.81 | 3837.81 | 68.75 | 5.91 |
July | 21701029.42 | 19530926.48 | 4272.77 | 30-JUL-19:00 | 3845.49 | 3845.49 | 72.83 | 5.91 |
August | 16024322.31 | 14421890.08 | 4272.86 | 13-AUG-19:27 | 3845.58 | 3845.58 | 72.88 | 5.91 |
September | 8407088.48 | 7566379.63 | 4272.44 | 10-SEP-17:40 | 3845.19 | 3845.19 | 72.67 | 5.91 |
October | 59274159.07 | 53346743.17 | 4272.45 | 09-OCT-20:20 | 3845.20 | 3845.20 | 72.68 | 5.91 |
November | 0.197420E+09 | 0.177678E+09 | 4700.97 | 26-NOV-24:00 | 4230.87 | 4230.87 | 67.63 | 6.66 |
December | 0.529218E+09 | 0.476297E+09 | 10140.97 | 05-DEC-16:30 | 9126.87 | 9126.87 | 82.14 | 22.62 |
Annual Sum or Average | 0.285219E+10 | 0.256697E+10 | ||||||
Minimum of Months | 7533582.04 | 6780223.84 | 4256.27 | 3830.64 | 3830.64 | 63.27 | 5.91 | |
Maximum of Months | 0.809119E+09 | 0.728207E+09 | 10140.97 | 9126.87 | 9126.87 | 82.14 | 22.62 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.587788E+10 | 0.529009E+10 | 17274.48 | 13-JAN-14:10 | 15547.03 | 15547.03 | 6.95 | 56.52 |
February | 0.386285E+10 | 0.347656E+10 | 15445.00 | 21-FEB-13:00 | 13900.50 | 13900.50 | 8.09 | 37.40 |
March | 0.415866E+10 | 0.374280E+10 | 15631.71 | 23-MAR-13:10 | 14068.54 | 14068.54 | 7.08 | 38.68 |
April | 0.843232E+10 | 0.758909E+10 | 16161.79 | 13-APR-09:20 | 14545.61 | 14545.61 | 7.14 | 42.95 |
May | 0.912563E+10 | 0.821307E+10 | 16739.06 | 18-MAY-15:20 | 15065.16 | 15065.16 | 7.11 | 49.10 |
June | 0.134696E+11 | 0.121227E+11 | 16400.02 | 30-JUN-05:02 | 14760.02 | 14760.02 | 7.52 | 45.26 |
July | 0.185292E+11 | 0.166763E+11 | 17432.31 | 31-JUL-15:50 | 15689.08 | 15689.08 | 7.37 | 58.85 |
August | 0.205386E+11 | 0.184847E+11 | 18603.74 | 07-AUG-05:02 | 16743.37 | 16743.37 | 7.50 | 72.20 |
September | 0.142092E+11 | 0.127883E+11 | 18853.76 | 29-SEP-12:30 | 16968.39 | 16968.39 | 6.76 | 74.17 |
October | 0.146155E+11 | 0.131540E+11 | 20462.03 | 04-OCT-05:02 | 18415.83 | 18415.83 | 7.50 | 83.34 |
November | 0.650108E+10 | 0.585097E+10 | 16474.27 | 08-NOV-13:40 | 14826.84 | 14826.84 | 8.16 | 46.04 |
December | 0.590366E+10 | 0.531330E+10 | 15079.12 | 07-DEC-11:30 | 13571.21 | 13571.21 | 8.09 | 35.12 |
Annual Sum or Average | 0.125224E+12 | 0.112702E+12 | ||||||
Minimum of Months | 0.386285E+10 | 0.347656E+10 | 15079.12 | 13571.21 | 13571.21 | 6.76 | 35.12 | |
Maximum of Months | 0.205386E+11 | 0.184847E+11 | 20462.03 | 18415.83 | 18415.83 | 8.16 | 83.34 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 74.93 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 62.01 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 62.50 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 62.99 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 78.23 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 63.73 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 62.95 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 63.90 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 63.20 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 76.16 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 63.04 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 62.06 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 62.01 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 78.23 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.713235E+10 | 0.641911E+10 | 7253.51 | 01-JAN-00:22 | 6528.16 | 6528.16 | 6.79 | 90.85 |
February | 0.589649E+10 | 0.530684E+10 | 7253.51 | 01-FEB-04:01 | 6528.16 | 6528.16 | 6.95 | 90.85 |
March | 0.582885E+10 | 0.524596E+10 | 7253.51 | 01-MAR-06:01 | 6528.16 | 6528.16 | 6.74 | 90.85 |
April | 0.879104E+10 | 0.791193E+10 | 7253.51 | 01-APR-05:01 | 6528.16 | 6528.16 | 6.82 | 90.85 |
May | 0.957964E+10 | 0.862168E+10 | 7253.51 | 01-MAY-00:11 | 6528.16 | 6528.16 | 6.97 | 90.85 |
June | 0.116718E+11 | 0.105047E+11 | 7253.51 | 01-JUN-03:01 | 6528.16 | 6528.16 | 6.95 | 90.85 |
July | 0.143857E+11 | 0.129471E+11 | 7253.51 | 01-JUL-03:01 | 6528.16 | 6528.16 | 7.56 | 90.85 |
August | 0.152687E+11 | 0.137418E+11 | 7253.51 | 01-AUG-00:03 | 6528.16 | 6528.16 | 6.98 | 90.85 |
September | 0.113515E+11 | 0.102164E+11 | 7253.51 | 01-SEP-00:03 | 6528.16 | 6528.16 | 6.82 | 90.85 |
October | 0.116396E+11 | 0.104757E+11 | 7253.51 | 01-OCT-07:32 | 6528.16 | 6528.16 | 8.26 | 90.85 |
November | 0.804117E+10 | 0.723705E+10 | 7253.51 | 01-NOV-03:01 | 6528.16 | 6528.16 | 7.66 | 90.85 |
December | 0.750782E+10 | 0.675704E+10 | 7253.51 | 01-DEC-04:01 | 6528.16 | 6528.16 | 6.78 | 90.85 |
Annual Sum or Average | 0.117095E+12 | 0.105385E+12 | ||||||
Minimum of Months | 0.582885E+10 | 0.524596E+10 | 7253.51 | 6528.16 | 6528.16 | 6.74 | 90.85 | |
Maximum of Months | 0.152687E+11 | 0.137418E+11 | 7253.51 | 6528.16 | 6528.16 | 8.26 | 90.85 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-JAN-00:05 | 2966.12 | 2966.12 | 21.80 | 13.76 |
February | 0.797294E+10 | 0.717565E+10 | 3295.69 | 01-FEB-00:10 | 2966.12 | 2966.12 | 24.29 | 13.76 |
March | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-MAR-00:05 | 2966.12 | 2966.12 | 29.27 | 13.76 |
April | 0.854244E+10 | 0.768819E+10 | 3295.69 | 01-APR-00:10 | 2966.12 | 2966.12 | 29.80 | 13.76 |
May | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-MAY-00:05 | 2966.12 | 2966.12 | 24.61 | 13.76 |
June | 0.854244E+10 | 0.768819E+10 | 3295.69 | 01-JUN-00:10 | 2966.12 | 2966.12 | 24.29 | 13.76 |
July | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-JUL-00:10 | 2966.12 | 2966.12 | 28.39 | 13.76 |
August | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-AUG-00:03 | 2966.12 | 2966.12 | 33.11 | 13.76 |
September | 0.854244E+10 | 0.768819E+10 | 3295.69 | 01-SEP-00:03 | 2966.12 | 2966.12 | 27.33 | 13.76 |
October | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-OCT-00:10 | 2966.12 | 2966.12 | 26.61 | 13.76 |
November | 0.854244E+10 | 0.768819E+10 | 3295.69 | 01-NOV-00:10 | 2966.12 | 2966.12 | 27.11 | 13.76 |
December | 0.882718E+10 | 0.794447E+10 | 3295.69 | 01-DEC-00:10 | 2966.12 | 2966.12 | 29.89 | 13.76 |
Annual Sum or Average | 0.103933E+12 | 0.935397E+11 | ||||||
Minimum of Months | 0.797294E+10 | 0.717565E+10 | 3295.69 | 2966.12 | 2966.12 | 21.80 | 13.76 | |
Maximum of Months | 0.882718E+10 | 0.794447E+10 | 3295.69 | 2966.12 | 2966.12 | 33.11 | 13.76 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.139579E+11 | 0.125621E+11 | 27343.31 | 17-JAN-14:00 | 24608.98 | 24608.98 | 25.70 | 107.02 |
February | 0.112013E+11 | 0.100812E+11 | 27321.47 | 01-FEB-12:00 | 24589.33 | 24589.33 | 24.70 | 107.02 |
March | 0.113541E+11 | 0.102187E+11 | 27355.68 | 22-MAR-12:40 | 24620.11 | 24620.11 | 26.24 | 107.02 |
April | 0.176096E+11 | 0.158486E+11 | 27371.87 | 26-APR-11:00 | 24634.68 | 24634.68 | 26.94 | 107.02 |
May | 0.186160E+11 | 0.167544E+11 | 27345.48 | 04-MAY-14:00 | 24610.94 | 24610.94 | 25.79 | 107.02 |
June | 0.257038E+11 | 0.231335E+11 | 27414.72 | 28-JUN-10:10 | 24673.25 | 24673.25 | 28.87 | 107.02 |
July | 0.356770E+11 | 0.321093E+11 | 27414.72 | 13-JUL-14:30 | 24673.25 | 24673.25 | 28.83 | 107.02 |
August | 0.391282E+11 | 0.352154E+11 | 27414.72 | 07-AUG-08:00 | 24673.25 | 24673.25 | 29.19 | 107.02 |
September | 0.266263E+11 | 0.239636E+11 | 27414.72 | 21-SEP-12:10 | 24673.25 | 24673.25 | 29.40 | 107.02 |
October | 0.275110E+11 | 0.247599E+11 | 27414.72 | 02-OCT-12:10 | 24673.25 | 24673.25 | 29.42 | 107.02 |
November | 0.154170E+11 | 0.138753E+11 | 27321.89 | 28-NOV-13:40 | 24589.71 | 24589.71 | 24.73 | 107.02 |
December | 0.146684E+11 | 0.132015E+11 | 27325.32 | 05-DEC-14:50 | 24592.79 | 24592.79 | 24.90 | 107.02 |
Annual Sum or Average | 0.257471E+12 | 0.231724E+12 | ||||||
Minimum of Months | 0.112013E+11 | 0.100812E+11 | 27321.47 | 24589.33 | 24589.33 | 24.70 | 107.02 | |
Maximum of Months | 0.391282E+11 | 0.352154E+11 | 27414.72 | 24673.25 | 24673.25 | 29.42 | 107.02 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7326.56 | 37949.41 | 01-JAN-07:55 | 80.54 | 82.22 | 11258.51 | 45617.98 | 30-JAN-12:50 |
February | 6963.21 | 37939.40 | 26-FEB-08:70 | 80.53 | 82.22 | 11386.60 | 45616.66 | 06-FEB-12:50 |
March | 5719.94 | 37982.61 | 26-MAR-07:10 | 80.55 | 82.22 | 12062.17 | 45397.24 | 01-MAR-12:20 |
April | 6806.52 | 38065.03 | 30-APR-06:48 | 80.60 | 82.22 | 10858.28 | 44597.85 | 03-APR-11:40 |
May | 6683.91 | 38137.77 | 29-MAY-07:00 | 80.64 | 82.22 | 10957.04 | 43633.78 | 01-MAY-12:00 |
June | 6052.59 | 38192.40 | 25-JUN-06:50 | 80.67 | 82.22 | 11024.31 | 42543.90 | 01-JUN-11:50 |
July | 7720.00 | 38225.54 | 30-JUL-06:38 | 80.68 | 82.22 | 9650.47 | 41686.10 | 03-JUL-11:40 |
August | 6012.61 | 38225.93 | 06-AUG-06:38 | 80.69 | 82.22 | 10834.09 | 41601.58 | 31-AUG-11:40 |
September | 6995.39 | 38206.25 | 03-SEP-06:45 | 80.67 | 82.22 | 10151.04 | 42309.57 | 29-SEP-11:20 |
October | 7518.46 | 38157.02 | 01-OCT-07:00 | 80.65 | 82.22 | 10429.31 | 43392.87 | 31-OCT-11:30 |
November | 7555.90 | 38071.48 | 05-NOV-06:50 | 80.60 | 82.22 | 10964.19 | 44453.26 | 30-NOV-12:40 |
December | 7423.34 | 38002.81 | 03-DEC-08:00 | 80.56 | 82.22 | 10727.95 | 45237.63 | 29-DEC-12:20 |
Annual Sum or Average | 6898.17 | 10855.52 | ||||||
Minimum of Months | 5719.94 | 37939.40 | 80.53 | 82.22 | 9650.47 | 41601.58 | ||
Maximum of Months | 7720.00 | 38225.93 | 80.69 | 82.22 | 12062.17 | 45617.98 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 73.23 | 73.23 | 22045.56 | 576659.47 | 30-JAN-01:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.33 | 57.33 | 16829.97 | 645882.53 | 20-FEB-03:30 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 62.76 | 82.00 | 22507.78 | 681973.50 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.56 | 58.56 | 5739.83 | 773696.12 | 23-APR-22:56 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 66.73 | 66.73 | 3281.26 | 515763.00 | 29-MAY-08:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.66 | 56.66 | 325.02 | 578075.93 | 18-JUN-23:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 69.70 | 69.70 | 451.39 | 295838.15 | 02-JUL-22:08 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 72.76 | 72.76 | 318.87 | 230445.20 | 27-AUG-23:08 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 72.68 | 72.68 | 213.04 | 496496.74 | 24-SEP-16:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 63.31 | 63.31 | 1701.47 | 499858.19 | 15-OCT-13:48 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 55.11 | 55.11 | 8750.04 | 671796.57 | 26-NOV-15:10 |
December | 3.09 | 13779.30 | 05-DEC-16:30 | 82.14 | 82.14 | 18303.05 | 625517.64 | 31-DEC-15:25 |
Annual Sum or Average | 0.26 | 8353.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.11 | 55.11 | 213.04 | 230445.20 | ||
Maximum of Months | 3.09 | 13779.30 | 82.14 | 82.14 | 22507.78 | 773696.12 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 176832.05 | 1260140.36 | 13-JAN-14:10 | 10.01 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 134714.04 | 1318850.21 | 01-FEB-13:10 | 10.16 | 8.04 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 126180.99 | 1235391.73 | 22-MAR-12:30 | 9.94 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 256824.10 | 1260635.76 | 26-APR-10:10 | 10.01 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 267522.02 | 1185942.71 | 04-MAY-14:00 | 9.81 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 428694.39 | 1559011.18 | 29-JUN-13:00 | 10.80 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 603743.52 | 1977881.72 | 31-JUL-15:50 | 11.90 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 676686.48 | 2020609.36 | 07-AUG-05:03 | 12.01 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 463035.71 | 1799518.96 | 22-SEP-05:03 | 11.43 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 465602.07 | 2151872.46 | 04-OCT-05:03 | 12.36 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 210188.99 | 1172355.26 | 27-NOV-15:20 | 9.78 | 8.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 195810.48 | 1199822.11 | 05-DEC-15:00 | 9.85 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 335391.77 | 0.00 | ||||||
Minimum of Months | 126180.99 | 1172355.26 | 9.78 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 676686.48 | 2151872.46 | 12.36 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117057.92 | 1260901.91 | 13-JAN-14:10 | 12.03 | 7.91 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 80469.02 | 1116139.29 | 01-FEB-12:00 | 16.58 | 7.90 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82239.04 | 1236026.51 | 22-MAR-13:10 | 14.49 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 176864.77 | 1262371.13 | 26-APR-10:10 | 14.54 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 175313.10 | 1180818.36 | 04-MAY-14:00 | 14.32 | 7.93 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 325727.06 | 1555421.00 | 29-JUN-13:00 | 14.93 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 506886.50 | 1974650.67 | 31-JUL-15:50 | 14.72 | 7.40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 581372.74 | 2409304.88 | 07-AUG-05:02 | 14.67 | 7.26 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 372140.46 | 2201226.56 | 30-SEP-05:02 | 16.00 | 7.19 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 380716.87 | 2618011.96 | 04-OCT-05:02 | 14.20 | 7.29 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 134987.08 | 1173983.30 | 19-NOV-13:43 | 15.38 | 7.60 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 134659.75 | 1196077.38 | 05-DEC-15:00 | 16.22 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 257179.01 | 0.00 | ||||||
Minimum of Months | 80469.02 | 1116139.29 | 12.03 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 581372.74 | 2618011.96 | 16.58 | 7.93 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 200305.86 | 630497.93 | 18-JAN-13:00 | 31.39 | 27.53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 325273.03 | 829070.31 | 01-FEB-12:00 | 35.44 | 28.69 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 476110.47 | 929040.75 | 11-MAR-12:00 | 37.47 | 27.84 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 701495.40 | 1314727.85 | 26-APR-13:00 | 45.22 | 32.25 | 0.00 | 0.00 | 01-APR-00:10 |
May | 214973.62 | 534999.55 | 03-MAY-13:00 | 29.44 | 25.54 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 425378.83 | 790756.01 | 29-JUN-11:00 | 34.67 | 27.75 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 694024.88 | 1168798.74 | 31-JUL-13:00 | 42.30 | 32.10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 909138.08 | 1370093.52 | 18-AUG-12:00 | 46.32 | 33.28 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 281608.14 | 1162346.18 | 29-SEP-13:00 | 42.17 | 37.77 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 493212.48 | 1437681.91 | 16-OCT-11:00 | 47.66 | 40.08 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 509291.25 | 1092218.37 | 19-NOV-13:00 | 40.76 | 30.94 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 677850.05 | 1248582.11 | 19-DEC-13:00 | 43.90 | 31.15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 493903.92 | 0.00 | ||||||
Minimum of Months | 200305.86 | 534999.55 | 29.44 | 25.54 | 0.00 | 0.00 | ||
Maximum of Months | 909138.08 | 1437681.91 | 47.66 | 40.08 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 141228.59 | 2057434.48 | 17-JAN-14:00 | 25.70 | 22.64 | 765.30 | 81557.77 | 09-JAN-06:50 |
February | 101077.47 | 1611986.43 | 01-FEB-12:00 | 24.70 | 21.71 | 542.82 | 64076.91 | 07-FEB-07:00 |
March | 106506.50 | 2298761.05 | 22-MAR-12:40 | 26.24 | 23.03 | 376.24 | 61403.15 | 09-MAR-06:40 |
April | 220159.35 | 2614278.04 | 26-APR-11:00 | 26.94 | 23.79 | 305.97 | 45103.52 | 01-APR-05:15 |
May | 207899.77 | 2099818.42 | 04-MAY-14:00 | 25.79 | 22.59 | 180.63 | 48434.40 | 26-MAY-18:10 |
June | 485430.54 | 4020463.04 | 29-JUN-13:00 | 30.09 | 25.94 | 47.24 | 25272.16 | 12-JUN-07:00 |
July | 959279.02 | 5355643.40 | 31-JUL-15:50 | 33.07 | 27.82 | 21.19 | 20538.66 | 08-JUL-23:05 |
August | 1144718.96 | 5266818.60 | 18-AUG-16:00 | 32.87 | 27.68 | 29.59 | 22448.86 | 28-AUG-06:00 |
September | 598602.64 | 4980207.25 | 22-SEP-12:30 | 32.23 | 27.58 | 80.11 | 34446.94 | 19-SEP-05:50 |
October | 599558.21 | 4740278.73 | 04-OCT-11:00 | 31.70 | 27.03 | 137.44 | 58362.57 | 25-OCT-06:00 |
November | 157527.94 | 1621605.11 | 28-NOV-13:40 | 24.73 | 21.71 | 489.20 | 66463.59 | 29-NOV-04:30 |
December | 150394.73 | 1699733.58 | 05-DEC-14:50 | 24.90 | 21.74 | 589.00 | 78790.91 | 28-DEC-06:40 |
Annual Sum or Average | 408983.40 | 295.77 | ||||||
Minimum of Months | 101077.47 | 1611986.43 | 24.70 | 21.71 | 21.19 | 20538.66 | ||
Maximum of Months | 1144718.96 | 5355643.40 | 33.07 | 27.82 | 765.30 | 81557.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 7.48 |
February | 0.25 | 7.48 |
March | 0.53 | 7.48 |
April | 0.57 | 7.48 |
May | 0.92 | 7.48 |
June | 0.81 | 7.48 |
July | 0.56 | 7.48 |
August | 1.77 | 7.48 |
September | 0.58 | 7.48 |
October | 0.97 | 7.48 |
November | 1.50 | 7.48 |
December | 1.11 | 7.48 |
Annual Sum or Average | 9.87 | 7.48 |
Minimum of Months | 0.25 | 7.48 |
Maximum of Months | 1.77 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.82 | 4.11 |
February | 2.73 | 4.11 |
March | 2.74 | 5.21 |
April | 12.53 | 1.97 |
May | 4.94 | 4.03 |
June | 4.66 | 3.27 |
July | 18.26 | 2.02 |
August | 22.56 | 2.03 |
September | 4.77 | 3.10 |
October | 4.64 | 3.08 |
November | 3.74 | 4.31 |
December | 4.46 | 4.16 |
Annual Sum or Average | 88.84 | 2.74 |
Minimum of Months | 2.73 | 1.97 |
Maximum of Months | 22.56 | 5.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.20 | 12.06 |
February | 2.64 | 11.95 |
March | 3.33 | 11.76 |
April | 2.59 | 7.01 |
May | 3.58 | 11.39 |
June | 1.70 | 6.07 |
July | 2.19 | 3.96 |
August | 1.95 | 2.82 |
September | 1.76 | 6.08 |
October | 2.80 | 7.67 |
November | 3.04 | 11.54 |
December | 3.72 | 10.45 |
Annual Sum or Average | 32.50 | 9.20 |
Minimum of Months | 1.70 | 2.82 |
Maximum of Months | 3.72 | 12.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.38 | 4.73 |
February | 0.22 | 8.40 |
March | 0.75 | 8.96 |
April | 1.12 | 6.72 |
May | 0.81 | 6.72 |
June | 1.09 | 4.83 |
July | 1.97 | 4.44 |
August | 1.38 | 5.13 |
September | 1.24 | 6.12 |
October | 1.35 | 6.79 |
November | 0.58 | 8.66 |
December | 0.40 | 7.64 |
Annual Sum or Average | 11.29 | 6.14 |
Minimum of Months | 0.22 | 4.44 |
Maximum of Months | 1.97 | 8.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.26 | 0.44 |
February | 0.86 | 0.30 |
March | 1.28 | 0.45 |
April | 3.48 | 0.32 |
May | 2.00 | 0.47 |
June | 2.38 | 0.33 |
July | 8.11 | 0.29 |
August | 6.57 | 0.26 |
September | 2.99 | 0.41 |
October | 2.95 | 0.27 |
November | 1.40 | 0.43 |
December | 0.81 | 0.41 |
Annual Sum or Average | 34.10 | 0.33 |
Minimum of Months | 0.81 | 0.26 |
Maximum of Months | 8.11 | 0.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.91 | 0.27 |
February | 2.82 | 0.36 |
March | 3.49 | 0.35 |
April | 9.12 | 0.25 |
May | 4.01 | 0.31 |
June | 5.72 | 0.23 |
July | 14.58 | 0.19 |
August | 15.54 | 0.19 |
September | 6.80 | 0.25 |
October | 5.79 | 0.23 |
November | 4.52 | 0.33 |
December | 4.73 | 0.33 |
Annual Sum or Average | 80.04 | 0.25 |
Minimum of Months | 2.82 | 0.19 |
Maximum of Months | 15.54 | 0.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.74 | 0.37 |
February | 1.47 | 0.46 |
March | 2.52 | 0.53 |
April | 6.23 | 0.36 |
May | 3.02 | 0.48 |
June | 3.89 | 0.36 |
July | 11.46 | 0.29 |
August | 10.06 | 0.32 |
September | 4.84 | 0.39 |
October | 3.97 | 0.30 |
November | 2.73 | 0.43 |
December | 2.32 | 0.38 |
Annual Sum or Average | 54.26 | 0.36 |
Minimum of Months | 1.47 | 0.29 |
Maximum of Months | 11.46 | 0.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.43 | 0.20 |
February | 5.56 | 0.22 |
March | 5.32 | 0.29 |
April | 13.94 | 0.21 |
May | 7.87 | 0.23 |
June | 7.35 | 0.22 |
July | 18.99 | 0.18 |
August | 19.04 | 0.20 |
September | 7.56 | 0.24 |
October | 7.50 | 0.22 |
November | 6.53 | 0.30 |
December | 6.51 | 0.28 |
Annual Sum or Average | 110.60 | 0.22 |
Minimum of Months | 4.43 | 0.18 |
Maximum of Months | 19.04 | 0.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.32 | 0.40 |
February | 0.22 | 0.00 |
March | 0.37 | 0.08 |
April | 0.67 | 0.25 |
May | 0.72 | 0.26 |
June | 1.63 | 0.25 |
July | 1.21 | 0.45 |
August | 1.08 | 0.27 |
September | 1.66 | 0.24 |
October | 1.28 | 0.33 |
November | 0.43 | 0.08 |
December | 0.17 | 0.00 |
Annual Sum or Average | 9.75 | 0.27 |
Minimum of Months | 0.17 | 0.00 |
Maximum of Months | 1.66 | 0.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.03 | 0.42 |
February | 1.34 | 0.39 |
March | 1.74 | 0.36 |
April | 3.76 | 0.39 |
May | 2.55 | 0.40 |
June | 3.89 | 0.26 |
July | 4.73 | 0.30 |
August | 4.44 | 0.26 |
September | 3.90 | 0.27 |
October | 3.72 | 0.37 |
November | 2.08 | 0.24 |
December | 2.35 | 0.35 |
Annual Sum or Average | 35.54 | 0.32 |
Minimum of Months | 1.03 | 0.24 |
Maximum of Months | 4.73 | 0.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.60 | 0.61 |
February | 0.99 | 0.61 |
March | 0.75 | 0.22 |
April | 1.83 | 0.43 |
May | 1.19 | 0.49 |
June | 2.11 | 0.31 |
July | 2.11 | 0.47 |
August | 1.72 | 0.39 |
September | 2.44 | 0.36 |
October | 1.94 | 0.42 |
November | 0.84 | 0.17 |
December | 0.80 | 0.51 |
Annual Sum or Average | 17.31 | 0.41 |
Minimum of Months | 0.60 | 0.17 |
Maximum of Months | 2.44 | 0.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.14 | 0.34 |
February | 1.62 | 0.49 |
March | 2.13 | 0.35 |
April | 3.79 | 0.25 |
May | 2.81 | 0.43 |
June | 4.36 | 0.27 |
July | 5.10 | 0.29 |
August | 4.56 | 0.26 |
September | 3.91 | 0.28 |
October | 3.77 | 0.35 |
November | 2.03 | 0.21 |
December | 1.93 | 0.30 |
Annual Sum or Average | 37.16 | 0.30 |
Minimum of Months | 1.14 | 0.21 |
Maximum of Months | 5.10 | 0.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.04 | 0.84 |
April | 0.28 | 0.72 |
May | 0.31 | 1.00 |
June | 0.69 | 0.79 |
July | 2.34 | 0.68 |
August | 1.66 | 0.60 |
September | 0.89 | 0.91 |
October | 0.89 | 0.58 |
November | 0.06 | 0.84 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.17 | 0.71 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.34 | 1.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.39 | 0.54 |
February | 0.38 | 0.54 |
March | 0.51 | 0.41 |
April | 1.87 | 0.58 |
May | 1.26 | 0.62 |
June | 2.06 | 0.46 |
July | 4.59 | 0.43 |
August | 2.97 | 0.40 |
September | 2.54 | 0.63 |
October | 2.08 | 0.50 |
November | 0.38 | 0.54 |
December | 0.45 | 0.54 |
Annual Sum or Average | 19.47 | 0.50 |
Minimum of Months | 0.38 | 0.40 |
Maximum of Months | 4.59 | 0.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.29 | 0.84 |
February | 0.38 | 0.84 |
March | 0.24 | 0.99 |
April | 1.16 | 0.71 |
May | 0.88 | 1.06 |
June | 1.17 | 0.84 |
July | 2.86 | 0.68 |
August | 2.07 | 0.60 |
September | 1.53 | 0.85 |
October | 1.00 | 0.66 |
November | 0.28 | 0.84 |
December | 0.40 | 0.84 |
Annual Sum or Average | 12.27 | 0.76 |
Minimum of Months | 0.24 | 0.60 |
Maximum of Months | 2.86 | 1.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.37 | 0.54 |
February | 0.42 | 0.54 |
March | 0.78 | 0.57 |
April | 2.04 | 0.52 |
May | 2.05 | 0.61 |
June | 2.18 | 0.42 |
July | 4.56 | 0.43 |
August | 3.61 | 0.41 |
September | 3.11 | 0.65 |
October | 2.46 | 0.55 |
November | 0.63 | 0.54 |
December | 0.80 | 0.54 |
Annual Sum or Average | 23.01 | 0.51 |
Minimum of Months | 0.37 | 0.41 |
Maximum of Months | 4.56 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.06 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 10.52 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 1.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 11.52 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 10.52 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.80 | 0.00 |
February | 0.49 | 0.00 |
March | 1.16 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.03 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.48 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.16 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.709661E+09 | 0.00 | 0.131248E+11 | 0.181353E+11 | 0.00 | 0.00 |
February | 0.745272E+09 | 0.00 | 0.617350E+10 | 0.157595E+11 | 0.00 | 0.00 |
March | 0.213205E+09 | 0.00 | 0.682026E+10 | 0.180492E+11 | 0.00 | 0.00 |
April | 0.458651E+09 | 0.00 | 0.171903E+11 | 0.166892E+11 | 0.00 | 0.00 |
May | 0.234007E+09 | 0.00 | 0.168666E+11 | 0.177505E+11 | 0.00 | 0.00 |
June | 0.294983E+09 | 0.00 | 0.299349E+11 | 0.173515E+11 | 0.00 | 0.00 |
July | 0.118790E+10 | 0.00 | 0.500557E+11 | 0.173398E+11 | 0.00 | 0.00 |
August | 0.870627E+09 | 0.00 | 0.572964E+11 | 0.184996E+11 | 0.00 | 0.00 |
September | 0.352660E+09 | 0.00 | 0.349668E+11 | 0.174689E+11 | 0.00 | 0.00 |
October | 0.167846E+10 | 0.00 | 0.461247E+11 | 0.183964E+11 | 0.00 | 0.00 |
November | 0.127518E+10 | 0.00 | 0.148675E+11 | 0.178912E+11 | 0.00 | 0.00 |
December | 0.201819E+10 | 0.00 | 0.178147E+11 | 0.180969E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.100388E+11 | 0.00 | 0.311236E+12 | 0.211428E+12 | 0.00 | 0.00 |
Minimum of Months | 0.213205E+09 | 0.00 | 0.617350E+10 | 0.157595E+11 | 0.00 | 0.00 |
Maximum of Months | 0.201819E+10 | 0.00 | 0.572964E+11 | 0.184996E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.198127E+10 | 0.00 | 0.253889E+11 | 0.599360E+10 | 0.00 | 0.00 |
February | 0.752162E+09 | 0.00 | 0.170168E+11 | 0.576665E+10 | 0.00 | 0.00 |
March | 0.123660E+10 | 0.00 | 0.201379E+11 | 0.730808E+10 | 0.00 | 0.00 |
April | 36304196.25 | 0.00 | 0.412176E+11 | 0.727473E+10 | 0.00 | 0.00 |
May | 75248658.53 | 0.00 | 0.373406E+11 | 0.575827E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.715658E+11 | 0.626606E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.126184E+12 | 0.687596E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.151830E+12 | 0.797723E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.803763E+11 | 0.576510E+10 | 0.00 | 0.00 |
October | 7341386.31 | 0.00 | 0.886505E+11 | 0.657472E+10 | 0.00 | 0.00 |
November | 55414161.70 | 0.00 | 0.314078E+11 | 0.716464E+10 | 0.00 | 0.00 |
December | 0.724703E+09 | 0.00 | 0.335004E+11 | 0.755607E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.486905E+10 | 0.00 | 0.724616E+12 | 0.802811E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.170168E+11 | 0.575827E+10 | 0.00 | 0.00 |
Maximum of Months | 0.198127E+10 | 0.00 | 0.151830E+12 | 0.797723E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.481486E+11 | 0.00 | 0.212070E+12 | 0.438835E+11 | 0.00 | 0.00 |
February | 0.334298E+11 | 0.00 | 0.134597E+12 | 0.393563E+11 | 0.00 | 0.00 |
March | 0.508948E+11 | 0.00 | 0.151576E+12 | 0.455378E+11 | 0.00 | 0.00 |
April | 0.126434E+11 | 0.00 | 0.301539E+12 | 0.437479E+11 | 0.00 | 0.00 |
May | 0.774741E+10 | 0.00 | 0.312215E+12 | 0.444787E+11 | 0.00 | 0.00 |
June | 0.337437E+09 | 0.00 | 0.584103E+12 | 0.467187E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.970866E+12 | 0.473270E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.112601E+13 | 0.521345E+11 | 0.00 | 0.00 |
September | 0.299535E+09 | 0.00 | 0.689112E+12 | 0.464287E+11 | 0.00 | 0.00 |
October | 0.257115E+10 | 0.00 | 0.722850E+12 | 0.483204E+11 | 0.00 | 0.00 |
November | 0.183514E+11 | 0.00 | 0.234862E+12 | 0.453722E+11 | 0.00 | 0.00 |
December | 0.397535E+11 | 0.00 | 0.244013E+12 | 0.444664E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.214177E+12 | 0.00 | 0.568381E+13 | 0.547772E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.134597E+12 | 0.393563E+11 | 0.00 | 0.00 |
Maximum of Months | 0.508948E+11 | 0.00 | 0.112601E+13 | 0.521345E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.862296E+10 | 0.00 | 0.177030E+11 | 0.338937E+10 | 0.00 | 0.00 |
February | 0.589298E+10 | 0.00 | 0.114480E+11 | 0.313382E+10 | 0.00 | 0.00 |
March | 0.866127E+10 | 0.00 | 0.138614E+11 | 0.373025E+10 | 0.00 | 0.00 |
April | 0.178795E+10 | 0.00 | 0.302137E+11 | 0.408332E+10 | 0.00 | 0.00 |
May | 0.971481E+09 | 0.00 | 0.314069E+11 | 0.416961E+10 | 0.00 | 0.00 |
June | 37323429.31 | 0.00 | 0.613774E+11 | 0.471471E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.104095E+12 | 0.506374E+10 | 0.00 | 0.00 |
August | 399894.01 | 0.00 | 0.119243E+12 | 0.548891E+10 | 0.00 | 0.00 |
September | 39974486.11 | 0.00 | 0.686035E+11 | 0.441965E+10 | 0.00 | 0.00 |
October | 0.481452E+09 | 0.00 | 0.703055E+11 | 0.435033E+10 | 0.00 | 0.00 |
November | 0.325429E+10 | 0.00 | 0.197717E+11 | 0.347899E+10 | 0.00 | 0.00 |
December | 0.687304E+10 | 0.00 | 0.202249E+11 | 0.335991E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.366231E+11 | 0.00 | 0.568254E+12 | 0.493826E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.114480E+11 | 0.313382E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866127E+10 | 0.00 | 0.119243E+12 | 0.548891E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.708334E+09 | 0.00 | 0.387636E+12 | 0.178291E+12 | 0.00 | 0.44 |
February | 0.311828E+09 | 0.00 | 0.605983E+12 | 0.206739E+12 | 0.00 | 0.29 |
March | 0.129047E+09 | 0.00 | 0.959111E+12 | 0.278854E+12 | 0.00 | 0.16 |
April | 0.00 | 0.00 | 0.122046E+13 | 0.326371E+12 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.387513E+12 | 0.176726E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.660555E+12 | 0.228318E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.991762E+12 | 0.303775E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.129853E+13 | 0.367582E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.384111E+12 | 0.175451E+12 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.693106E+12 | 0.245278E+12 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.936492E+12 | 0.275336E+12 | 0.00 | 0.45 |
December | 60303701.64 | 0.00 | 0.126302E+13 | 0.339017E+12 | 0.00 | 0.80 |
Annual Sum or Average | 0.120951E+10 | 0.00 | 0.978829E+13 | 0.310174E+13 | 0.00 | 2.49 |
Minimum of Months | 0.00 | 0.00 | 0.384111E+12 | 0.175451E+12 | 0.00 | 0.00 |
Maximum of Months | 0.708334E+09 | 0.00 | 0.129853E+13 | 0.367582E+12 | 0.00 | 0.80 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.634061E+10 | 0.273540E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111999E+11 | 0.346700E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.184752E+11 | 0.490388E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240063E+11 | 0.594300E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.664031E+10 | 0.280286E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124904E+11 | 0.393578E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192112E+11 | 0.545411E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254976E+11 | 0.676990E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.662297E+10 | 0.280383E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129834E+11 | 0.418440E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180630E+11 | 0.483424E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246742E+11 | 0.606103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186205E+12 | 0.538954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.634061E+10 | 0.273540E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.254976E+11 | 0.676990E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.494558E+11 | 0.238991E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.970022E+11 | 0.312571E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166522E+12 | 0.450768E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223549E+12 | 0.557122E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.570993E+11 | 0.254647E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.114623E+12 | 0.366394E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.180837E+12 | 0.514926E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241195E+12 | 0.641112E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.580271E+11 | 0.256594E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117175E+12 | 0.385812E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.163220E+12 | 0.444987E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224522E+12 | 0.559695E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169323E+13 | 0.498362E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.494558E+11 | 0.238991E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241195E+12 | 0.641112E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.334950E+10 | 0.209752E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.850150E+10 | 0.293451E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155407E+11 | 0.435214E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217458E+11 | 0.550933E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.510719E+10 | 0.245713E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.111644E+11 | 0.364003E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.179481E+11 | 0.516101E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239334E+11 | 0.641884E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.538750E+10 | 0.251205E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.110706E+11 | 0.376836E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.151459E+11 | 0.428034E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.209608E+11 | 0.538921E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159855E+12 | 0.485205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.334950E+10 | 0.209752E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.239334E+11 | 0.641884E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.181353E+11 | 0.131248E+11 | 0.709661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157595E+11 | 0.617350E+10 | 0.745272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180492E+11 | 0.682026E+10 | 0.213205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166892E+11 | 0.171903E+11 | 0.458651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177505E+11 | 0.168666E+11 | 0.234007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173515E+11 | 0.299349E+11 | 0.294983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173398E+11 | 0.500557E+11 | 0.118790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184996E+11 | 0.572964E+11 | 0.870627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174689E+11 | 0.349668E+11 | 0.352660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183964E+11 | 0.461247E+11 | 0.167846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178912E+11 | 0.148675E+11 | 0.127518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180969E+11 | 0.178147E+11 | 0.201819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211428E+12 | 0.311236E+12 | 0.100388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157595E+11 | 0.617350E+10 | 0.213205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184996E+11 | 0.572964E+11 | 0.201819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.599360E+10 | 0.253889E+11 | 0.198127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576665E+10 | 0.170168E+11 | 0.752162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730808E+10 | 0.201379E+11 | 0.123660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.727473E+10 | 0.412176E+11 | 36304196.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.575827E+10 | 0.373406E+11 | 75248658.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.626606E+10 | 0.715658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687596E+10 | 0.126184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.797723E+10 | 0.151830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576510E+10 | 0.803763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657472E+10 | 0.886505E+11 | 7341386.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716464E+10 | 0.314078E+11 | 55414161.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755607E+10 | 0.335004E+11 | 0.724703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802811E+11 | 0.724616E+12 | 0.486905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.575827E+10 | 0.170168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.797723E+10 | 0.151830E+12 | 0.198127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.438835E+11 | 0.212070E+12 | 0.481486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393563E+11 | 0.134597E+12 | 0.334298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455378E+11 | 0.151576E+12 | 0.508948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437479E+11 | 0.301539E+12 | 0.126434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.444787E+11 | 0.312215E+12 | 0.774741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.467187E+11 | 0.584103E+12 | 0.337437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.473270E+11 | 0.970866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.521345E+11 | 0.112601E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.464287E+11 | 0.689112E+12 | 0.299535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483204E+11 | 0.722850E+12 | 0.257115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453722E+11 | 0.234862E+12 | 0.183514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444664E+11 | 0.244013E+12 | 0.397535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547772E+12 | 0.568381E+13 | 0.214177E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.393563E+11 | 0.134597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.521345E+11 | 0.112601E+13 | 0.508948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.338937E+10 | 0.177030E+11 | 0.862296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313382E+10 | 0.114480E+11 | 0.589298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373025E+10 | 0.138614E+11 | 0.866127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408332E+10 | 0.302137E+11 | 0.178795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416961E+10 | 0.314069E+11 | 0.971481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.471471E+10 | 0.613774E+11 | 37323429.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.506374E+10 | 0.104095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.548891E+10 | 0.119243E+12 | 399894.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.441965E+10 | 0.686035E+11 | 39974486.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435033E+10 | 0.703055E+11 | 0.481452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347899E+10 | 0.197717E+11 | 0.325429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335991E+10 | 0.202249E+11 | 0.687304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493826E+11 | 0.568254E+12 | 0.366231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313382E+10 | 0.114480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.548891E+10 | 0.119243E+12 | 0.866127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.958654E+11 | 0.330060E+12 | 0.708334E+09 | 0.00 | 0.00 | 0.116727E+10 | 0.00 | 0.00 |
February | 0.865881E+11 | 0.517061E+12 | 0.311828E+09 | 0.00 | 0.00 | 0.769949E+09 | 0.00 | 0.00 |
March | 0.958654E+11 | 0.817151E+12 | 0.129047E+09 | 0.00 | 0.00 | 0.432770E+09 | 0.00 | 0.00 |
April | 0.927730E+11 | 0.103057E+13 | 0.00 | 0.00 | 0.00 | 99522365.99 | 0.00 | 0.00 |
May | 0.958654E+11 | 0.330375E+12 | 0.00 | 0.00 | 0.00 | 14597107.61 | 0.00 | 0.00 |
June | 0.927730E+11 | 0.558879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.958654E+11 | 0.826285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.958654E+11 | 0.107226E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927730E+11 | 0.325267E+12 | 0.00 | 0.00 | 0.00 | 33408668.57 | 0.00 | 0.00 |
October | 0.958654E+11 | 0.579419E+12 | 0.00 | 0.00 | 0.00 | 0.806828E+09 | 0.00 | 0.00 |
November | 0.927730E+11 | 0.794453E+12 | 0.00 | 0.00 | 0.00 | 0.120832E+10 | 0.00 | 0.00 |
December | 0.958654E+11 | 0.106556E+13 | 60303701.64 | 0.00 | 0.00 | 0.214076E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112874E+13 | 0.824734E+13 | 0.120951E+10 | 0.00 | 0.00 | 0.667343E+10 | 0.00 | 0.00 |
Minimum of Months | 0.865881E+11 | 0.325267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958654E+11 | 0.107226E+13 | 0.708334E+09 | 0.00 | 0.00 | 0.214076E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141227E+10 | 0.541333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127560E+10 | 0.957244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141227E+10 | 0.157601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136671E+10 | 0.202608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141227E+10 | 0.566009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136671E+10 | 0.105471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141227E+10 | 0.159613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141227E+10 | 0.209851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136671E+10 | 0.559704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141227E+10 | 0.108643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136671E+10 | 0.153510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141227E+10 | 0.208849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166284E+11 | 0.156858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127560E+10 | 0.541333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141227E+10 | 0.209851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134029E+11 | 0.422098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121058E+11 | 0.829004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134029E+11 | 0.142036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129705E+11 | 0.188652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134029E+11 | 0.486608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129705E+11 | 0.967738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134029E+11 | 0.150239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134029E+11 | 0.198505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129705E+11 | 0.490227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134029E+11 | 0.980109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129705E+11 | 0.138699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134029E+11 | 0.190018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157808E+12 | 0.142573E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121058E+11 | 0.422098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134029E+11 | 0.198505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136510E+10 | 0.285516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123299E+10 | 0.726409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136510E+10 | 0.132523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132107E+10 | 0.183451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136510E+10 | 0.434930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132107E+10 | 0.942152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136510E+10 | 0.149066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136510E+10 | 0.196927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132107E+10 | 0.454680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136510E+10 | 0.925122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132107E+10 | 0.128667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136510E+10 | 0.177337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160730E+11 | 0.134485E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123299E+10 | 0.285516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136510E+10 | 0.196927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.181353E+11 | 0.709661E+09 | 0.131248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157595E+11 | 0.745272E+09 | 0.617350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180492E+11 | 0.213205E+09 | 0.682026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166892E+11 | 0.458651E+09 | 0.171903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177505E+11 | 0.234007E+09 | 0.168666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173515E+11 | 0.294983E+09 | 0.299349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173398E+11 | 0.118790E+10 | 0.500557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184996E+11 | 0.870627E+09 | 0.572964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174689E+11 | 0.352660E+09 | 0.349668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183964E+11 | 0.167846E+10 | 0.461247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178912E+11 | 0.127518E+10 | 0.148675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180969E+11 | 0.201819E+10 | 0.178147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211428E+12 | 0.100388E+11 | 0.311236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.157595E+11 | 0.213205E+09 | 0.617350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184996E+11 | 0.201819E+10 | 0.572964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.599360E+10 | 0.198127E+10 | 0.253889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576665E+10 | 0.752162E+09 | 0.170168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730808E+10 | 0.123660E+10 | 0.201379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.727473E+10 | 36304196.25 | 0.412176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.575827E+10 | 75248658.53 | 0.373406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.626606E+10 | 0.00 | 0.715658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687596E+10 | 0.00 | 0.126184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.797723E+10 | 0.00 | 0.151830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576510E+10 | 0.00 | 0.803763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657472E+10 | 7341386.31 | 0.886505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716464E+10 | 55414161.70 | 0.314078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755607E+10 | 0.724703E+09 | 0.335004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802811E+11 | 0.486905E+10 | 0.724616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.575827E+10 | 0.00 | 0.170168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.797723E+10 | 0.198127E+10 | 0.151830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.438835E+11 | 0.481486E+11 | 0.212070E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393563E+11 | 0.334298E+11 | 0.134597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455378E+11 | 0.508948E+11 | 0.151576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437479E+11 | 0.126434E+11 | 0.301539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.444787E+11 | 0.774741E+10 | 0.312215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.467187E+11 | 0.337437E+09 | 0.584103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.473270E+11 | 0.00 | 0.970866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.521345E+11 | 0.00 | 0.112601E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.464287E+11 | 0.299535E+09 | 0.689112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483204E+11 | 0.257115E+10 | 0.722850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453722E+11 | 0.183514E+11 | 0.234862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444664E+11 | 0.397535E+11 | 0.244013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547772E+12 | 0.214177E+12 | 0.568381E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.393563E+11 | 0.00 | 0.134597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.521345E+11 | 0.508948E+11 | 0.112601E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.338937E+10 | 0.862296E+10 | 0.177030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313382E+10 | 0.589298E+10 | 0.114480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373025E+10 | 0.866127E+10 | 0.138614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408332E+10 | 0.178795E+10 | 0.302137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416961E+10 | 0.971481E+09 | 0.314069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.471471E+10 | 37323429.31 | 0.613774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.506374E+10 | 0.00 | 0.104095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.548891E+10 | 399894.01 | 0.119243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.441965E+10 | 39974486.11 | 0.686035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435033E+10 | 0.481452E+09 | 0.703055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347899E+10 | 0.325429E+10 | 0.197717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335991E+10 | 0.687304E+10 | 0.202249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493826E+11 | 0.366231E+11 | 0.568254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.313382E+10 | 0.00 | 0.114480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.548891E+10 | 0.866127E+10 | 0.119243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.958654E+11 | 0.708334E+09 | 0.387636E+12 | 0.00 | 0.812529E+11 | 0.00 | 0.00 | 0.00 | 0.117252E+10 | 0.00 | 0.00 | 0.00 |
February | 0.865881E+11 | 0.311828E+09 | 0.605983E+12 | 0.00 | 0.119377E+12 | 0.00 | 0.00 | 0.00 | 0.773415E+09 | 0.00 | 0.00 | 0.00 |
March | 0.958654E+11 | 0.129047E+09 | 0.959111E+12 | 0.00 | 0.182554E+12 | 0.00 | 0.00 | 0.00 | 0.434719E+09 | 0.00 | 0.00 | 0.00 |
April | 0.927730E+11 | 0.00 | 0.122046E+13 | 0.00 | 0.233498E+12 | 0.00 | 0.00 | 0.00 | 99970356.50 | 0.00 | 0.00 | 0.00 |
May | 0.958654E+11 | 0.00 | 0.387513E+12 | 0.00 | 0.808459E+11 | 0.00 | 0.00 | 0.00 | 14662815.11 | 0.00 | 0.00 | 0.00 |
June | 0.927730E+11 | 0.00 | 0.660555E+12 | 0.00 | 0.135545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.958654E+11 | 0.00 | 0.991762E+12 | 0.00 | 0.207910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.958654E+11 | 0.00 | 0.129853E+13 | 0.00 | 0.271716E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927730E+11 | 0.00 | 0.384111E+12 | 0.00 | 0.826446E+11 | 0.00 | 0.00 | 0.00 | 33559054.53 | 0.00 | 0.00 | 0.00 |
October | 0.958654E+11 | 0.00 | 0.693106E+12 | 0.00 | 0.148602E+12 | 0.00 | 0.00 | 0.00 | 0.810460E+09 | 0.00 | 0.00 | 0.00 |
November | 0.927730E+11 | 0.00 | 0.936492E+12 | 0.00 | 0.181349E+12 | 0.00 | 0.00 | 0.00 | 0.121376E+10 | 0.00 | 0.00 | 0.00 |
December | 0.958654E+11 | 60303701.64 | 0.126302E+13 | 0.00 | 0.241002E+12 | 0.00 | 0.00 | 0.00 | 0.215039E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112874E+13 | 0.120951E+10 | 0.978829E+13 | 0.00 | 0.196630E+13 | 0.00 | 0.00 | 0.00 | 0.670347E+10 | 0.00 | 0.00 | |
Minimum of Months | 0.865881E+11 | 0.00 | 0.384111E+12 | 0.00 | 0.808459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958654E+11 | 0.708334E+09 | 0.129853E+13 | 0.00 | 0.271716E+12 | 0.00 | 0.00 | 0.00 | 0.215039E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.141227E+10 | 0.00 | 0.634061E+10 | 0.00 | 0.132313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127560E+10 | 0.00 | 0.111999E+11 | 0.00 | 0.219140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141227E+10 | 0.00 | 0.184752E+11 | 0.00 | 0.349161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136671E+10 | 0.00 | 0.240063E+11 | 0.00 | 0.457629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141227E+10 | 0.00 | 0.664031E+10 | 0.00 | 0.139059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136671E+10 | 0.00 | 0.124904E+11 | 0.00 | 0.256906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141227E+10 | 0.00 | 0.192112E+11 | 0.00 | 0.404184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141227E+10 | 0.00 | 0.254976E+11 | 0.00 | 0.535763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136671E+10 | 0.00 | 0.662297E+10 | 0.00 | 0.143711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141227E+10 | 0.00 | 0.129834E+11 | 0.00 | 0.277213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136671E+10 | 0.00 | 0.180630E+11 | 0.00 | 0.346753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141227E+10 | 0.00 | 0.246742E+11 | 0.00 | 0.464875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166284E+11 | 0.00 | 0.186205E+12 | 0.00 | 0.372671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.127560E+10 | 0.00 | 0.634061E+10 | 0.00 | 0.132313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141227E+10 | 0.00 | 0.254976E+11 | 0.00 | 0.535763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.134029E+11 | 0.00 | 0.494558E+11 | 0.00 | 0.104963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121058E+11 | 0.00 | 0.970022E+11 | 0.00 | 0.191513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134029E+11 | 0.00 | 0.166522E+12 | 0.00 | 0.316739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129705E+11 | 0.00 | 0.223549E+12 | 0.00 | 0.427417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134029E+11 | 0.00 | 0.570993E+11 | 0.00 | 0.120618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129705E+11 | 0.00 | 0.114623E+12 | 0.00 | 0.236689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134029E+11 | 0.00 | 0.180837E+12 | 0.00 | 0.380897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134029E+11 | 0.00 | 0.241195E+12 | 0.00 | 0.507083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129705E+11 | 0.00 | 0.580271E+11 | 0.00 | 0.126889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134029E+11 | 0.00 | 0.117175E+12 | 0.00 | 0.251783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129705E+11 | 0.00 | 0.163220E+12 | 0.00 | 0.315282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134029E+11 | 0.00 | 0.224522E+12 | 0.00 | 0.425666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157808E+12 | 0.00 | 0.169323E+13 | 0.00 | 0.340554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.121058E+11 | 0.00 | 0.494558E+11 | 0.00 | 0.104963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134029E+11 | 0.00 | 0.241195E+12 | 0.00 | 0.507083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.136510E+10 | 0.00 | 0.334950E+10 | 0.00 | 0.732418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123299E+10 | 0.00 | 0.850150E+10 | 0.00 | 0.170152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136510E+10 | 0.00 | 0.155407E+11 | 0.00 | 0.298704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132107E+10 | 0.00 | 0.217458E+11 | 0.00 | 0.418827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136510E+10 | 0.00 | 0.510719E+10 | 0.00 | 0.109203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132107E+10 | 0.00 | 0.111644E+11 | 0.00 | 0.231897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136510E+10 | 0.00 | 0.179481E+11 | 0.00 | 0.379591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136510E+10 | 0.00 | 0.239334E+11 | 0.00 | 0.505374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132107E+10 | 0.00 | 0.538750E+10 | 0.00 | 0.119098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136510E+10 | 0.00 | 0.110706E+11 | 0.00 | 0.240326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132107E+10 | 0.00 | 0.151459E+11 | 0.00 | 0.295928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136510E+10 | 0.00 | 0.209608E+11 | 0.00 | 0.402411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160730E+11 | 0.00 | 0.159855E+12 | 0.00 | 0.324475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123299E+10 | 0.00 | 0.334950E+10 | 0.00 | 0.732418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136510E+10 | 0.00 | 0.239334E+11 | 0.00 | 0.505374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386552E+09 | 94294745.51 | 0.00 | 0.183870E+09 | 0.00 | 0.00 | 0.729852E+11 | 0.00 | 1.31 |
February | 0.275761E+09 | 5417168.17 | 0.00 | 0.152801E+09 | 0.00 | 0.00 | 0.688803E+11 | 0.00 | 1.31 |
March | 0.334891E+09 | 0.00 | 0.00 | 0.170775E+09 | 0.00 | 0.00 | 0.805687E+11 | 0.00 | 1.33 |
April | 0.237765E+09 | 9984555.68 | 0.00 | 0.164634E+09 | 0.00 | 0.00 | 0.642579E+11 | 0.00 | 1.45 |
May | 0.229221E+09 | 4303326.67 | 0.00 | 0.164240E+09 | 0.00 | 0.00 | 0.670653E+11 | 0.00 | 1.53 |
June | 0.190613E+09 | 0.106673E+09 | 0.00 | 0.164309E+09 | 0.00 | 0.00 | 0.542622E+11 | 0.00 | 1.69 |
July | 0.152265E+09 | 0.206702E+10 | 0.00 | 0.167859E+09 | 0.00 | 0.00 | 0.373131E+11 | 0.00 | 1.50 |
August | 0.129133E+09 | 0.260166E+10 | 0.00 | 0.176658E+09 | 421768.79 | 0.00 | 0.377976E+11 | 0.00 | 1.64 |
September | 0.218046E+09 | 0.110368E+10 | 0.00 | 0.171687E+09 | 31392374.13 | 0.00 | 0.495681E+11 | 0.00 | 1.61 |
October | 0.194412E+09 | 0.271276E+10 | 0.00 | 0.180933E+09 | 20838963.22 | 0.00 | 0.470880E+11 | 0.00 | 1.51 |
November | 0.303078E+09 | 11342739.25 | 0.00 | 0.195298E+09 | 0.00 | 0.00 | 0.741294E+11 | 0.00 | 1.45 |
December | 0.419039E+09 | 1198205.86 | 0.00 | 0.197379E+09 | 0.00 | 0.00 | 0.710502E+11 | 0.00 | 1.33 |
Annual Sum or Average | 0.307078E+10 | 0.871833E+10 | 0.00 | 0.209044E+10 | 52653106.14 | 0.00 | 0.724966E+12 | 0.00 | 1.47 |
Minimum of Months | 0.129133E+09 | 0.00 | 0.00 | 0.152801E+09 | 0.00 | 0.00 | 0.373131E+11 | 0.00 | 1.31 |
Maximum of Months | 0.419039E+09 | 0.271276E+10 | 0.00 | 0.197379E+09 | 31392374.13 | 0.00 | 0.805687E+11 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323882E+10 | 78470661.19 | 0.00 | 0.104687E+09 | 12515925.19 | 0.00 | 0.460325E+11 | 0.00 | 0.80 |
February | 0.377670E+10 | 17575645.44 | 0.00 | 96764710.94 | 0.00 | 0.00 | 0.461592E+11 | 0.00 | 0.86 |
March | 0.351899E+10 | 25322062.38 | 0.00 | 0.119868E+09 | 16968595.72 | 0.00 | 0.590640E+11 | 0.00 | 0.94 |
April | 0.757661E+10 | 43121539.38 | 0.00 | 0.113554E+09 | 43351637.54 | 0.00 | 0.427200E+11 | 0.00 | 1.00 |
May | 0.410400E+10 | 26123324.97 | 0.00 | 0.103940E+09 | 0.00 | 0.00 | 0.403561E+11 | 0.00 | 0.88 |
June | 0.327723E+10 | 0.207856E+10 | 0.00 | 0.100324E+09 | 22938366.34 | 0.00 | 0.269562E+11 | 0.00 | 0.96 |
July | 0.492847E+10 | 0.105521E+11 | 0.00 | 59081773.04 | 0.879767E+09 | 0.00 | 0.867709E+10 | 0.00 | 0.96 |
August | 0.355182E+10 | 0.140438E+11 | 0.00 | 53699899.74 | 0.114781E+10 | 0.00 | 0.759904E+10 | 0.00 | 1.07 |
September | 0.257637E+10 | 0.385587E+10 | 0.00 | 82839039.87 | 0.116596E+09 | 0.00 | 0.191342E+11 | 0.00 | 0.86 |
October | 0.281189E+10 | 0.554600E+10 | 0.00 | 80470870.30 | 0.510844E+09 | 0.00 | 0.223248E+11 | 0.00 | 0.84 |
November | 0.383664E+10 | 8517323.02 | 0.00 | 0.117355E+09 | 18929246.55 | 0.00 | 0.488714E+11 | 0.00 | 0.95 |
December | 0.493244E+10 | 1847143.55 | 0.00 | 0.124636E+09 | 0.00 | 0.00 | 0.486084E+11 | 0.00 | 0.91 |
Annual Sum or Average | 0.481300E+11 | 0.362773E+11 | 0.00 | 0.115722E+10 | 0.276972E+10 | 0.00 | 0.416503E+12 | 0.00 | 0.92 |
Minimum of Months | 0.257637E+10 | 1847143.55 | 0.00 | 53699899.74 | 0.00 | 0.00 | 0.759904E+10 | 0.00 | 0.80 |
Maximum of Months | 0.757661E+10 | 0.140438E+11 | 0.00 | 0.124636E+09 | 0.114781E+10 | 0.00 | 0.590640E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339113E+11 | 0.346566E+09 | 0.00 | 0.751430E+09 | 0.578658E+09 | 0.00 | 0.351588E+12 | 0.00 | 0.65 |
February | 0.288457E+11 | 0.195131E+09 | 0.00 | 0.668342E+09 | 0.00 | 0.00 | 0.347702E+12 | 0.00 | 0.68 |
March | 0.238920E+11 | 0.128161E+09 | 0.00 | 0.824407E+09 | 0.255371E+09 | 0.00 | 0.435022E+12 | 0.00 | 0.71 |
April | 0.276990E+11 | 0.262051E+09 | 0.00 | 0.782248E+09 | 0.400510E+09 | 0.00 | 0.309828E+12 | 0.00 | 0.71 |
May | 0.270333E+11 | 0.279498E+09 | 0.00 | 0.861356E+09 | 0.00 | 0.00 | 0.329206E+12 | 0.00 | 0.73 |
June | 0.174635E+11 | 0.165663E+11 | 0.00 | 0.792450E+09 | 60294004.20 | 0.00 | 0.216014E+12 | 0.00 | 0.77 |
July | 0.145745E+11 | 0.830987E+11 | 0.00 | 0.509147E+09 | 0.954497E+10 | 0.00 | 0.716891E+11 | 0.00 | 0.71 |
August | 0.638934E+10 | 0.108066E+12 | 0.00 | 0.465031E+09 | 0.103190E+11 | 0.00 | 0.623671E+11 | 0.00 | 0.76 |
September | 0.152260E+11 | 0.334001E+11 | 0.00 | 0.656008E+09 | 0.299587E+10 | 0.00 | 0.157685E+12 | 0.00 | 0.72 |
October | 0.185050E+11 | 0.465239E+11 | 0.00 | 0.591937E+09 | 0.491810E+10 | 0.00 | 0.166799E+12 | 0.00 | 0.67 |
November | 0.237081E+11 | 33332812.33 | 0.00 | 0.784290E+09 | 0.302941E+09 | 0.00 | 0.352023E+12 | 0.00 | 0.70 |
December | 0.329704E+11 | 47610125.99 | 0.00 | 0.743000E+09 | 46142827.03 | 0.00 | 0.333504E+12 | 0.00 | 0.65 |
Annual Sum or Average | 0.270218E+12 | 0.288947E+12 | 0.00 | 0.842965E+10 | 0.294218E+11 | 0.00 | 0.313343E+13 | 0.00 | 0.71 |
Minimum of Months | 0.638934E+10 | 33332812.33 | 0.00 | 0.465031E+09 | 0.00 | 0.00 | 0.623671E+11 | 0.00 | 0.65 |
Maximum of Months | 0.339113E+11 | 0.108066E+12 | 0.00 | 0.861356E+09 | 0.103190E+11 | 0.00 | 0.435022E+12 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144926E+11 | 2425619.25 | 0.00 | 25841842.06 | 80885528.26 | 0.203143E+09 | 0.143109E+11 | 0.00 | 0.52 |
February | 0.113205E+11 | 6238841.41 | 0.00 | 28360666.46 | 6158805.76 | 0.00 | 0.182633E+11 | 0.00 | 0.56 |
March | 0.120182E+11 | 0.00 | 0.00 | 37659150.34 | 40771.71 | 0.00 | 0.254815E+11 | 0.00 | 0.60 |
April | 0.686310E+10 | 5670957.65 | 0.00 | 53739877.42 | 17216374.90 | 0.00 | 0.241580E+11 | 0.00 | 0.66 |
May | 0.622844E+10 | 9156793.56 | 0.00 | 60132918.74 | 0.00 | 0.00 | 0.266820E+11 | 0.00 | 0.68 |
June | 0.305641E+10 | 0.118634E+10 | 0.00 | 64929865.89 | 0.00 | 0.00 | 0.193207E+11 | 0.00 | 0.76 |
July | 0.143483E+10 | 0.811801E+10 | 0.00 | 40938410.19 | 0.478546E+09 | 0.00 | 0.667623E+10 | 0.00 | 0.73 |
August | 0.724808E+09 | 0.105063E+11 | 0.00 | 36832294.46 | 0.534017E+09 | 0.00 | 0.509977E+10 | 0.00 | 0.79 |
September | 0.310266E+10 | 0.248923E+10 | 0.00 | 48420773.47 | 0.344080E+09 | 0.00 | 0.119825E+11 | 0.00 | 0.67 |
October | 0.505951E+10 | 0.407910E+10 | 0.00 | 35016940.94 | 0.697817E+09 | 0.00 | 0.960387E+10 | 0.00 | 0.61 |
November | 0.991875E+10 | 175796.70 | 0.00 | 34412976.57 | 22337209.85 | 0.00 | 0.187887E+11 | 0.00 | 0.56 |
December | 0.128402E+11 | 2572229.00 | 0.00 | 26490079.96 | 13625401.67 | 728868.30 | 0.140996E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.870601E+11 | 0.264052E+11 | 0.00 | 0.492776E+09 | 0.219472E+10 | 0.203872E+09 | 0.194467E+12 | 0.00 | 0.64 |
Minimum of Months | 0.724808E+09 | 0.00 | 0.00 | 25841842.06 | 0.00 | 0.00 | 0.509977E+10 | 0.00 | 0.52 |
Maximum of Months | 0.144926E+11 | 0.105063E+11 | 0.00 | 64929865.89 | 0.697817E+09 | 0.203143E+09 | 0.266820E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242810E+10 | 8672083.84 | 0.00 | 5085975.26 | 3832757.26 | 0.00 | 0.259722E+10 | 0.00 | 0.66 |
February | 0.215892E+10 | 2187513.23 | 0.00 | 5193876.74 | 0.00 | 0.00 | 0.310419E+10 | 0.00 | 0.73 |
March | 0.193674E+10 | 3331832.36 | 0.00 | 7071895.07 | 2416907.05 | 0.00 | 0.455400E+10 | 0.00 | 0.80 |
April | 0.164631E+10 | 6119957.05 | 0.00 | 8602375.88 | 6174752.47 | 0.00 | 0.415352E+10 | 0.00 | 0.96 |
May | 0.140144E+10 | 3706479.78 | 0.00 | 8478846.88 | 0.00 | 0.00 | 0.401967E+10 | 0.00 | 0.88 |
June | 0.609654E+09 | 0.310282E+09 | 0.00 | 9559121.07 | 3267206.09 | 0.00 | 0.320356E+10 | 0.00 | 1.02 |
July | 0.734313E+09 | 0.160562E+10 | 0.00 | 5319076.06 | 0.125309E+09 | 0.00 | 0.102159E+10 | 0.00 | 1.06 |
August | 0.547441E+09 | 0.205848E+10 | 0.00 | 4028216.90 | 0.164005E+09 | 0.00 | 0.818186E+09 | 0.00 | 1.14 |
September | 0.749344E+09 | 0.565492E+09 | 0.00 | 5631365.15 | 16607305.06 | 0.00 | 0.182364E+10 | 0.00 | 0.87 |
October | 0.963270E+09 | 0.792700E+09 | 0.00 | 5295158.98 | 75033288.67 | 0.00 | 0.185929E+10 | 0.00 | 0.83 |
November | 0.172402E+10 | 1110906.23 | 0.00 | 6974989.75 | 2696170.63 | 0.00 | 0.375374E+10 | 0.00 | 0.80 |
December | 0.205756E+10 | 223940.22 | 0.00 | 6538390.48 | 0.00 | 0.00 | 0.327303E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.169571E+11 | 0.535792E+10 | 0.00 | 77779288.22 | 0.399342E+09 | 0.00 | 0.341816E+11 | 0.00 | 0.88 |
Minimum of Months | 0.547441E+09 | 223940.22 | 0.00 | 4028216.90 | 0.00 | 0.00 | 0.818186E+09 | 0.00 | 0.66 |
Maximum of Months | 0.242810E+10 | 0.205848E+10 | 0.00 | 9559121.07 | 0.164005E+09 | 0.00 | 0.455400E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285690E+10 | 2248056.44 | 0.00 | 3875580.41 | 10897943.39 | 0.00 | 0.230774E+10 | 0.00 | 1.01 |
February | 0.279429E+10 | 1471209.72 | 0.00 | 3645832.64 | 0.00 | 0.00 | 0.232347E+10 | 0.00 | 1.07 |
March | 0.313769E+10 | 2294166.89 | 0.00 | 4764284.49 | 2677462.22 | 0.00 | 0.297090E+10 | 0.00 | 1.14 |
April | 0.302817E+10 | 4902394.30 | 0.00 | 6346597.85 | 6840422.96 | 0.00 | 0.276959E+10 | 0.00 | 1.42 |
May | 0.234415E+10 | 3006536.05 | 0.00 | 6385549.54 | 0.00 | 0.00 | 0.294503E+10 | 0.00 | 1.28 |
June | 0.168341E+10 | 0.228844E+09 | 0.00 | 5879741.32 | 4167690.83 | 0.00 | 0.192516E+10 | 0.00 | 1.42 |
July | 0.119653E+10 | 0.124914E+10 | 0.00 | 3438861.86 | 0.163546E+09 | 0.00 | 0.652107E+09 | 0.00 | 1.55 |
August | 0.102150E+10 | 0.167258E+10 | 0.00 | 2273619.90 | 0.202849E+09 | 0.00 | 0.440545E+09 | 0.00 | 1.66 |
September | 0.151290E+10 | 0.405929E+09 | 0.00 | 3980231.77 | 44688870.22 | 0.00 | 0.111288E+10 | 0.00 | 1.27 |
October | 0.175436E+10 | 0.494960E+09 | 0.00 | 3506493.01 | 0.172449E+09 | 0.00 | 0.115856E+10 | 0.00 | 1.17 |
November | 0.273942E+10 | 295491.31 | 0.00 | 4505955.77 | 3729964.04 | 0.00 | 0.241848E+10 | 0.00 | 1.11 |
December | 0.312793E+10 | 185100.29 | 0.00 | 3870679.44 | 0.00 | 0.00 | 0.203381E+10 | 0.00 | 1.06 |
Annual Sum or Average | 0.271973E+11 | 0.406585E+10 | 0.00 | 52473428.01 | 0.611845E+09 | 0.00 | 0.230583E+11 | 0.00 | 1.27 |
Minimum of Months | 0.102150E+10 | 185100.29 | 0.00 | 2273619.90 | 0.00 | 0.00 | 0.440545E+09 | 0.00 | 1.01 |
Maximum of Months | 0.313769E+10 | 0.167258E+10 | 0.00 | 6385549.54 | 0.202849E+09 | 0.00 | 0.297090E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198941E+10 | 33155349.86 | 0.00 | 14211622.66 | 2147152.49 | 0.00 | 0.679191E+10 | 0.00 | 1.25 |
February | 0.213097E+10 | 4979203.81 | 0.00 | 10309494.70 | 0.00 | 0.00 | 0.559644E+10 | 0.00 | 1.14 |
March | 0.249300E+10 | 6362147.86 | 0.00 | 9892164.68 | 2626983.28 | 0.00 | 0.576417E+10 | 0.00 | 1.08 |
April | 0.253862E+10 | 8443440.97 | 0.00 | 9690881.55 | 7406586.20 | 0.00 | 0.428723E+10 | 0.00 | 1.15 |
May | 0.247681E+10 | 3915112.83 | 0.00 | 7485956.29 | 0.00 | 0.00 | 0.336844E+10 | 0.00 | 0.94 |
June | 0.145291E+10 | 0.311007E+09 | 0.00 | 7276527.88 | 3935160.17 | 0.00 | 0.254280E+10 | 0.00 | 1.04 |
July | 0.102609E+10 | 0.164356E+10 | 0.00 | 3824820.22 | 0.150927E+09 | 0.00 | 0.916875E+09 | 0.00 | 1.13 |
August | 0.752927E+09 | 0.235901E+10 | 0.00 | 3420154.00 | 0.200192E+09 | 0.00 | 0.813131E+09 | 0.00 | 1.31 |
September | 0.102173E+10 | 0.816173E+09 | 0.00 | 7566704.77 | 26443957.50 | 0.00 | 0.216583E+10 | 0.00 | 1.16 |
October | 0.114383E+10 | 0.117108E+10 | 0.00 | 9411969.18 | 71514146.27 | 0.00 | 0.261371E+10 | 0.00 | 1.19 |
November | 0.153833E+10 | 3799174.90 | 0.00 | 15759719.48 | 2784309.34 | 0.00 | 0.708654E+10 | 0.00 | 1.35 |
December | 0.174735E+10 | 489331.33 | 0.00 | 18581089.21 | 0.00 | 0.00 | 0.706203E+10 | 0.00 | 1.36 |
Annual Sum or Average | 0.203120E+11 | 0.636198E+10 | 0.00 | 0.117431E+09 | 0.467978E+09 | 0.00 | 0.490091E+11 | 0.00 | 1.18 |
Minimum of Months | 0.752927E+09 | 489331.33 | 0.00 | 3420154.00 | 0.00 | 0.00 | 0.813131E+09 | 0.00 | 0.94 |
Maximum of Months | 0.253862E+10 | 0.235901E+10 | 0.00 | 18581089.21 | 0.200192E+09 | 0.00 | 0.708654E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311727E+10 | 13411707.72 | 0.00 | 5192163.99 | 3900171.84 | 0.00 | 0.349356E+10 | 0.00 | 1.31 |
February | 0.160302E+10 | 2543836.23 | 0.00 | 7560667.53 | 0.00 | 0.00 | 0.533556E+10 | 0.00 | 1.49 |
March | 0.100458E+10 | 5562138.15 | 0.00 | 12715059.18 | 3234933.41 | 0.00 | 0.793056E+10 | 0.00 | 1.71 |
April | 0.141710E+10 | 11335832.94 | 0.00 | 18755418.02 | 4515979.65 | 0.00 | 0.721632E+10 | 0.00 | 2.20 |
May | 0.163933E+10 | 3388822.10 | 0.00 | 9966340.23 | 0.00 | 0.00 | 0.506388E+10 | 0.00 | 1.65 |
June | 0.718295E+09 | 0.354716E+09 | 0.00 | 13165288.24 | 3327825.72 | 0.00 | 0.414711E+10 | 0.00 | 1.98 |
July | 0.873501E+09 | 0.212883E+10 | 0.00 | 10595821.25 | 0.121394E+09 | 0.00 | 0.153304E+10 | 0.00 | 2.20 |
August | 0.639412E+09 | 0.288090E+10 | 0.00 | 9509245.60 | 0.146633E+09 | 0.00 | 0.130454E+10 | 0.00 | 2.51 |
September | 0.741517E+09 | 0.600136E+09 | 0.00 | 7324866.47 | 24992825.89 | 0.00 | 0.257121E+10 | 0.00 | 1.66 |
October | 0.817839E+09 | 0.851476E+09 | 0.00 | 7609980.35 | 95168472.90 | 0.00 | 0.283716E+10 | 0.00 | 1.58 |
November | 0.102142E+10 | 2177218.71 | 0.00 | 12243912.22 | 3539948.98 | 0.00 | 0.643192E+10 | 0.00 | 1.68 |
December | 0.120780E+10 | 276868.46 | 0.00 | 14010349.80 | 0.00 | 0.00 | 0.650826E+10 | 0.00 | 1.68 |
Annual Sum or Average | 0.148011E+11 | 0.685476E+10 | 0.00 | 0.128649E+09 | 0.406707E+09 | 0.00 | 0.543731E+11 | 0.00 | 1.81 |
Minimum of Months | 0.639412E+09 | 276868.46 | 0.00 | 5192163.99 | 0.00 | 0.00 | 0.130454E+10 | 0.00 | 1.31 |
Maximum of Months | 0.311727E+10 | 0.288090E+10 | 0.00 | 18755418.02 | 0.146633E+09 | 0.00 | 0.793056E+10 | 0.00 | 2.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.309938E+11 | 16638707.65 | 0.00 | 17969571.02 | 0.102235E+09 | 0.303310E+09 | 0.918601E+10 | 0.00 | 0.53 |
February | 0.266542E+11 | 21176344.45 | 0.00 | 19688220.77 | 0.00 | 2314575.30 | 0.126152E+11 | 0.00 | 0.55 |
March | 0.308858E+11 | 15214338.67 | 0.00 | 24773315.10 | 34953481.26 | 93857084.94 | 0.160589E+11 | 0.00 | 0.58 |
April | 0.201465E+11 | 34111340.43 | 0.00 | 42912992.54 | 55071633.04 | 0.00 | 0.177318E+11 | 0.00 | 0.64 |
May | 0.178318E+11 | 36494689.71 | 0.00 | 55486391.36 | 0.00 | 0.00 | 0.236107E+11 | 0.00 | 0.69 |
June | 0.101145E+11 | 0.240260E+10 | 0.00 | 59109123.06 | 8252632.74 | 0.00 | 0.184678E+11 | 0.00 | 0.79 |
July | 0.507361E+10 | 0.128879E+11 | 0.00 | 28865668.00 | 0.666921E+09 | 0.00 | 0.564580E+10 | 0.00 | 0.76 |
August | 0.467066E+10 | 0.155319E+11 | 0.00 | 18529696.76 | 0.100898E+10 | 0.00 | 0.342980E+10 | 0.00 | 0.79 |
September | 0.108832E+11 | 0.480001E+10 | 0.00 | 34130473.65 | 0.311165E+09 | 0.00 | 0.907088E+10 | 0.00 | 0.70 |
October | 0.140242E+11 | 0.641080E+10 | 0.00 | 25967559.23 | 0.699934E+09 | 0.00 | 0.716826E+10 | 0.00 | 0.64 |
November | 0.240738E+11 | 2986856.42 | 0.00 | 28160454.07 | 41464530.08 | 4030317.16 | 0.145889E+11 | 0.00 | 0.56 |
December | 0.291488E+11 | 3025665.58 | 0.00 | 18417276.73 | 8058653.68 | 1683825.31 | 0.900533E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.224501E+12 | 0.421629E+11 | 0.00 | 0.374011E+09 | 0.293704E+10 | 0.405195E+09 | 0.146579E+12 | 0.00 | 0.65 |
Minimum of Months | 0.467066E+10 | 2986856.42 | 0.00 | 17969571.02 | 0.00 | 0.00 | 0.342980E+10 | 0.00 | 0.53 |
Maximum of Months | 0.309938E+11 | 0.155319E+11 | 0.00 | 59109123.06 | 0.100898E+10 | 0.303310E+09 | 0.236107E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.393361E+11 | 15656840.11 | 0.00 | 10145996.62 | 0.129335E+09 | 0.239606E+09 | 0.986118E+10 | 0.00 | 0.98 |
February | 0.352131E+11 | 19000541.83 | 0.00 | 13989378.57 | 0.00 | 6924509.16 | 0.123367E+11 | 0.00 | 1.02 |
March | 0.403898E+11 | 12816477.04 | 0.00 | 21095521.94 | 43280459.67 | 0.171371E+09 | 0.164956E+11 | 0.00 | 1.07 |
April | 0.241353E+11 | 41492463.17 | 0.00 | 48245820.76 | 62924993.28 | 0.00 | 0.218415E+11 | 0.00 | 1.17 |
May | 0.261194E+11 | 34524066.97 | 0.00 | 45609771.15 | 0.00 | 0.00 | 0.213042E+11 | 0.00 | 1.18 |
June | 0.171077E+11 | 0.197524E+10 | 0.00 | 45958411.74 | 27309619.51 | 0.00 | 0.148403E+11 | 0.00 | 1.29 |
July | 0.736129E+10 | 0.116300E+11 | 0.00 | 30166512.23 | 0.145036E+10 | 0.00 | 0.571819E+10 | 0.00 | 1.29 |
August | 0.633004E+10 | 0.154759E+11 | 0.00 | 20688897.91 | 0.160186E+10 | 0.00 | 0.391111E+10 | 0.00 | 1.37 |
September | 0.154237E+11 | 0.379175E+10 | 0.00 | 29366049.40 | 0.709891E+09 | 0.00 | 0.818271E+10 | 0.00 | 1.18 |
October | 0.181657E+11 | 0.477586E+10 | 0.00 | 20377058.11 | 0.156751E+10 | 0.00 | 0.731852E+10 | 0.00 | 1.07 |
November | 0.324054E+11 | 606309.63 | 0.00 | 13260143.22 | 53968189.94 | 4990460.83 | 0.137554E+11 | 0.00 | 1.02 |
December | 0.394818E+11 | 1576888.79 | 0.00 | 8710737.98 | 11902379.51 | 37617467.70 | 0.711297E+10 | 0.00 | 0.99 |
Annual Sum or Average | 0.301469E+12 | 0.377744E+11 | 0.00 | 0.307614E+09 | 0.565834E+10 | 0.460509E+09 | 0.142678E+12 | 0.00 | 1.14 |
Minimum of Months | 0.633004E+10 | 606309.63 | 0.00 | 8710737.98 | 0.00 | 0.00 | 0.391111E+10 | 0.00 | 0.98 |
Maximum of Months | 0.403898E+11 | 0.154759E+11 | 0.00 | 48245820.76 | 0.160186E+10 | 0.239606E+09 | 0.218415E+11 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197912E+11 | 0.427791E+09 | 0.00 | 0.138396E+09 | 0.00 | 0.00 | 0.600361E+11 | 0.00 | 1.17 |
February | 0.230220E+11 | 62006592.90 | 0.00 | 85667324.03 | 0.00 | 0.00 | 0.434338E+11 | 0.00 | 1.02 |
March | 0.300544E+11 | 45118600.38 | 0.00 | 71282508.52 | 36072548.68 | 0.100510E+09 | 0.383870E+11 | 0.00 | 0.91 |
April | 0.228754E+11 | 60704560.67 | 0.00 | 65502520.50 | 60531910.53 | 0.00 | 0.267098E+11 | 0.00 | 0.86 |
May | 0.243304E+11 | 39600199.25 | 0.00 | 54476193.47 | 0.00 | 0.00 | 0.236507E+11 | 0.00 | 0.79 |
June | 0.160650E+11 | 0.245004E+10 | 0.00 | 49936273.36 | 10138599.88 | 0.00 | 0.157654E+11 | 0.00 | 0.85 |
July | 0.784475E+10 | 0.136504E+11 | 0.00 | 24494861.49 | 0.103636E+10 | 0.00 | 0.443247E+10 | 0.00 | 0.84 |
August | 0.561019E+10 | 0.190159E+11 | 0.00 | 21650447.14 | 0.134505E+10 | 0.00 | 0.417896E+10 | 0.00 | 0.98 |
September | 0.102357E+11 | 0.788513E+10 | 0.00 | 63125127.51 | 0.305777E+09 | 0.00 | 0.166447E+11 | 0.00 | 1.04 |
October | 0.114012E+11 | 0.112539E+11 | 0.00 | 81725062.57 | 0.592868E+09 | 0.00 | 0.195088E+11 | 0.00 | 1.07 |
November | 0.170401E+11 | 77813394.20 | 0.00 | 0.133759E+09 | 22057783.21 | 0.00 | 0.555567E+11 | 0.00 | 1.18 |
December | 0.185186E+11 | 36863503.74 | 0.00 | 0.158673E+09 | 0.00 | 0.00 | 0.541829E+11 | 0.00 | 1.18 |
Annual Sum or Average | 0.206789E+12 | 0.550053E+11 | 0.00 | 0.948688E+09 | 0.340885E+10 | 0.100510E+09 | 0.362487E+12 | 0.00 | 0.99 |
Minimum of Months | 0.561019E+10 | 36863503.74 | 0.00 | 21650447.14 | 0.00 | 0.00 | 0.417896E+10 | 0.00 | 0.79 |
Maximum of Months | 0.300544E+11 | 0.190159E+11 | 0.00 | 0.158673E+09 | 0.134505E+10 | 0.100510E+09 | 0.600361E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.417212E+11 | 55838192.05 | 0.00 | 16605493.06 | 92670280.26 | 25645783.50 | 0.102651E+11 | 0.00 | 1.04 |
February | 0.368026E+11 | 20018293.13 | 0.00 | 18810941.08 | 0.00 | 2932624.28 | 0.138068E+11 | 0.00 | 1.10 |
March | 0.422214E+11 | 21956532.19 | 0.00 | 26032094.06 | 44286927.24 | 18765392.12 | 0.187894E+11 | 0.00 | 1.16 |
April | 0.229827E+11 | 36560066.02 | 0.00 | 50652516.31 | 61118398.42 | 0.00 | 0.261786E+11 | 0.00 | 1.28 |
May | 0.234751E+11 | 31500485.02 | 0.00 | 50646719.10 | 0.00 | 0.00 | 0.271007E+11 | 0.00 | 1.27 |
June | 0.129975E+11 | 0.236159E+10 | 0.00 | 57809442.66 | 9054347.67 | 0.00 | 0.209560E+11 | 0.00 | 1.42 |
July | 0.599490E+10 | 0.133400E+11 | 0.00 | 34186041.28 | 0.171976E+10 | 0.00 | 0.725590E+10 | 0.00 | 1.38 |
August | 0.512590E+10 | 0.159313E+11 | 0.00 | 20712725.63 | 0.253592E+10 | 0.00 | 0.481995E+10 | 0.00 | 1.47 |
September | 0.123848E+11 | 0.445631E+10 | 0.00 | 35210862.05 | 0.645437E+09 | 0.00 | 0.125817E+11 | 0.00 | 1.29 |
October | 0.187323E+11 | 0.525321E+10 | 0.00 | 21555769.95 | 0.156176E+10 | 0.00 | 0.726131E+10 | 0.00 | 1.14 |
November | 0.342633E+11 | 10668003.28 | 0.00 | 25223402.62 | 46359599.98 | 0.00 | 0.152181E+11 | 0.00 | 1.11 |
December | 0.388526E+11 | 9445890.31 | 0.00 | 18043750.81 | 5062460.71 | 0.00 | 0.101540E+11 | 0.00 | 1.06 |
Annual Sum or Average | 0.295554E+12 | 0.415284E+11 | 0.00 | 0.375490E+09 | 0.672143E+10 | 47343799.90 | 0.174388E+12 | 0.00 | 1.23 |
Minimum of Months | 0.512590E+10 | 9445890.31 | 0.00 | 16605493.06 | 0.00 | 0.00 | 0.481995E+10 | 0.00 | 1.04 |
Maximum of Months | 0.422214E+11 | 0.159313E+11 | 0.00 | 57809442.66 | 0.253592E+10 | 25645783.50 | 0.271007E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329738E+10 | 133732.50 | 0.00 | 500462.42 | 13106531.02 | 0.574151E+09 | 0.307092E+09 | 0.00 | 0.59 |
February | 0.310269E+10 | 601779.50 | 0.00 | 645478.23 | 986618.12 | 0.287940E+09 | 0.643317E+09 | 0.00 | 0.60 |
March | 0.399857E+10 | 0.00 | 0.00 | 1127442.41 | 6531.48 | 0.310182E+09 | 0.806424E+09 | 0.00 | 0.65 |
April | 0.235663E+10 | 711711.80 | 0.00 | 3415389.86 | 2758000.19 | 38540448.84 | 0.163749E+10 | 0.00 | 0.68 |
May | 0.216582E+10 | 1104915.35 | 0.00 | 4483430.40 | 0.00 | 4640523.76 | 0.216742E+10 | 0.00 | 0.71 |
June | 0.126152E+10 | 0.167668E+09 | 0.00 | 5328942.66 | 0.00 | 0.00 | 0.177993E+10 | 0.00 | 0.83 |
July | 0.575137E+09 | 0.115900E+10 | 0.00 | 2571111.84 | 0.111045E+09 | 0.00 | 0.556018E+09 | 0.00 | 0.82 |
August | 0.447601E+09 | 0.138799E+10 | 0.00 | 1611765.12 | 0.180508E+09 | 0.00 | 0.337225E+09 | 0.00 | 0.87 |
September | 0.119457E+10 | 0.345377E+09 | 0.00 | 2809809.26 | 64663234.51 | 0.00 | 0.821987E+09 | 0.00 | 0.72 |
October | 0.146692E+10 | 0.533621E+09 | 0.00 | 1947439.57 | 0.145683E+09 | 29145517.51 | 0.549252E+09 | 0.00 | 0.66 |
November | 0.295243E+10 | 17774.53 | 0.00 | 800442.03 | 3578339.19 | 0.179868E+09 | 0.718693E+09 | 0.00 | 0.60 |
December | 0.315981E+10 | 34008.62 | 0.00 | 338900.98 | 2539768.57 | 0.426200E+09 | 0.254881E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.259791E+11 | 0.359626E+10 | 0.00 | 25580614.77 | 0.524875E+09 | 0.185067E+10 | 0.105797E+11 | 0.00 | 0.69 |
Minimum of Months | 0.447601E+09 | 0.00 | 0.00 | 338900.98 | 0.00 | 0.00 | 0.254881E+09 | 0.00 | 0.59 |
Maximum of Months | 0.399857E+10 | 0.138799E+10 | 0.00 | 5328942.66 | 0.180508E+09 | 0.574151E+09 | 0.216742E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377408E+10 | 195857.30 | 0.00 | 315966.53 | 13855474.22 | 0.330191E+09 | 0.323144E+09 | 0.00 | 0.97 |
February | 0.325886E+10 | 634955.29 | 0.00 | 717862.70 | 1047056.07 | 0.196270E+09 | 0.813427E+09 | 0.00 | 0.99 |
March | 0.409066E+10 | 6931.58 | 0.00 | 1344168.38 | 0.00 | 0.191121E+09 | 0.113443E+10 | 0.00 | 1.06 |
April | 0.213234E+10 | 825420.12 | 0.00 | 4593608.63 | 2926948.92 | 19171472.80 | 0.217363E+10 | 0.00 | 1.13 |
May | 0.232908E+10 | 1191682.21 | 0.00 | 4411895.27 | 0.00 | 615910.72 | 0.216013E+10 | 0.00 | 1.13 |
June | 0.153524E+10 | 0.139879E+09 | 0.00 | 4819093.12 | 512320.39 | 0.00 | 0.158271E+10 | 0.00 | 1.28 |
July | 0.590477E+09 | 0.108076E+10 | 0.00 | 3094562.66 | 0.114093E+09 | 0.00 | 0.634782E+09 | 0.00 | 1.31 |
August | 0.476983E+09 | 0.147455E+10 | 0.00 | 2007615.13 | 0.117305E+09 | 0.00 | 0.401318E+09 | 0.00 | 1.40 |
September | 0.128200E+10 | 0.292703E+09 | 0.00 | 2997085.68 | 78508481.51 | 0.00 | 0.848183E+09 | 0.00 | 1.14 |
October | 0.149910E+10 | 0.422041E+09 | 0.00 | 1886981.85 | 0.182198E+09 | 20014163.10 | 0.620881E+09 | 0.00 | 1.02 |
November | 0.333996E+10 | 18863.36 | 0.00 | 311782.15 | 3797539.99 | 78037806.74 | 0.662936E+09 | 0.00 | 0.98 |
December | 0.373984E+10 | 378899.91 | 0.00 | 202422.17 | 2352540.92 | 0.195441E+09 | 0.136590E+09 | 0.00 | 0.96 |
Annual Sum or Average | 0.280486E+11 | 0.341319E+10 | 0.00 | 26703044.25 | 0.516596E+09 | 0.103086E+10 | 0.114922E+11 | 0.00 | 1.11 |
Minimum of Months | 0.476983E+09 | 6931.58 | 0.00 | 202422.17 | 0.00 | 0.00 | 0.136590E+09 | 0.00 | 0.96 |
Maximum of Months | 0.409066E+10 | 0.147455E+10 | 0.00 | 4819093.12 | 0.182198E+09 | 0.330191E+09 | 0.217363E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236090E+10 | 35602892.45 | 0.00 | 9435061.08 | 0.00 | 0.246342E+09 | 0.450056E+10 | 0.00 | 1.08 |
February | 0.258364E+10 | 2087685.91 | 0.00 | 6299323.85 | 1170933.58 | 0.188578E+09 | 0.340352E+10 | 0.00 | 0.97 |
March | 0.374092E+10 | 0.00 | 0.00 | 5310536.50 | 7751.66 | 0.306594E+09 | 0.291227E+10 | 0.00 | 0.92 |
April | 0.255062E+10 | 1100476.11 | 0.00 | 5784732.21 | 3273237.09 | 40097440.30 | 0.258736E+10 | 0.00 | 0.88 |
May | 0.279845E+10 | 1162691.82 | 0.00 | 4425992.68 | 0.00 | 11152658.85 | 0.219222E+10 | 0.00 | 0.81 |
June | 0.181101E+10 | 0.169750E+09 | 0.00 | 4457569.27 | 0.00 | 0.00 | 0.158297E+10 | 0.00 | 0.90 |
July | 0.761373E+09 | 0.120228E+10 | 0.00 | 2282027.31 | 0.162344E+09 | 0.00 | 0.516772E+09 | 0.00 | 0.91 |
August | 0.532252E+09 | 0.169058E+10 | 0.00 | 2009762.56 | 0.195795E+09 | 0.00 | 0.412231E+09 | 0.00 | 1.05 |
September | 0.116763E+10 | 0.585347E+09 | 0.00 | 5589216.92 | 42036071.63 | 0.00 | 0.153791E+10 | 0.00 | 1.04 |
October | 0.133236E+10 | 0.978635E+09 | 0.00 | 6776980.65 | 0.114000E+09 | 165966.24 | 0.156277E+10 | 0.00 | 1.06 |
November | 0.210560E+10 | 4880830.43 | 0.00 | 9594811.63 | 2017831.78 | 43128892.22 | 0.434360E+10 | 0.00 | 1.08 |
December | 0.229702E+10 | 6332305.85 | 0.00 | 9917006.24 | 0.00 | 0.129160E+09 | 0.389411E+10 | 0.00 | 1.08 |
Annual Sum or Average | 0.240418E+11 | 0.467776E+10 | 0.00 | 71883020.90 | 0.520645E+09 | 0.965218E+09 | 0.294463E+11 | 0.00 | 0.98 |
Minimum of Months | 0.532252E+09 | 0.00 | 0.00 | 2009762.56 | 0.00 | 0.00 | 0.412231E+09 | 0.00 | 0.81 |
Maximum of Months | 0.374092E+10 | 0.169058E+10 | 0.00 | 9917006.24 | 0.195795E+09 | 0.306594E+09 | 0.450056E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384458E+10 | 2226263.09 | 0.00 | 1112966.43 | 13481121.18 | 0.418933E+09 | 0.749421E+09 | 0.00 | 1.10 |
February | 0.374074E+10 | 709789.44 | 0.00 | 1353262.30 | 1170459.33 | 0.177680E+09 | 0.101981E+10 | 0.00 | 1.14 |
March | 0.459460E+10 | 0.00 | 0.00 | 2159798.51 | 7748.52 | 0.219862E+09 | 0.149124E+10 | 0.00 | 1.24 |
April | 0.271304E+10 | 1304913.01 | 0.00 | 4456795.42 | 2657085.09 | 33940875.37 | 0.235050E+10 | 0.00 | 1.32 |
May | 0.282911E+10 | 987866.28 | 0.00 | 4387987.39 | 0.00 | 1378491.18 | 0.240438E+10 | 0.00 | 1.31 |
June | 0.160852E+10 | 0.162911E+09 | 0.00 | 5392108.39 | 0.00 | 0.00 | 0.198132E+10 | 0.00 | 1.48 |
July | 0.618078E+09 | 0.120905E+10 | 0.00 | 3276931.16 | 0.182574E+09 | 0.00 | 0.738113E+09 | 0.00 | 1.47 |
August | 0.517939E+09 | 0.143857E+10 | 0.00 | 1983098.67 | 0.280519E+09 | 0.00 | 0.419271E+09 | 0.00 | 1.57 |
September | 0.139375E+10 | 0.311110E+09 | 0.00 | 3232624.64 | 0.112036E+09 | 0.00 | 0.107968E+10 | 0.00 | 1.32 |
October | 0.185096E+10 | 0.425073E+09 | 0.00 | 1936343.58 | 0.247345E+09 | 153787.57 | 0.587949E+09 | 0.00 | 1.18 |
November | 0.356909E+10 | 189215.39 | 0.00 | 1815238.83 | 4081128.13 | 66422788.27 | 0.106857E+10 | 0.00 | 1.13 |
December | 0.369952E+10 | 244842.36 | 0.00 | 1180257.58 | 2813467.56 | 0.257223E+09 | 0.652869E+09 | 0.00 | 1.09 |
Annual Sum or Average | 0.309799E+11 | 0.355238E+10 | 0.00 | 32287412.90 | 0.846685E+09 | 0.117559E+10 | 0.145431E+11 | 0.00 | 1.28 |
Minimum of Months | 0.517939E+09 | 0.00 | 0.00 | 1112966.43 | 0.00 | 0.00 | 0.419271E+09 | 0.00 | 1.09 |
Maximum of Months | 0.459460E+10 | 0.143857E+10 | 0.00 | 5392108.39 | 0.280519E+09 | 0.418933E+09 | 0.240438E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:02:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 5356454.10 | 0.00 | 0.204723E+09 | 0.00 | 0.00 | 0.680891E+10 | 0.00 | 0.32 |
February | 0.00 | 70808.73 | 0.00 | 0.372728E+09 | 0.00 | 0.00 | 0.594310E+10 | 0.00 | 0.32 |
March | 0.00 | 3317308.57 | 0.00 | 0.654464E+09 | 0.00 | 0.00 | 0.650617E+10 | 0.00 | 0.34 |
April | 0.00 | 6956283.64 | 0.00 | 0.788520E+09 | 0.00 | 0.00 | 0.366364E+10 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.207210E+09 | 0.00 | 0.00 | 0.443961E+10 | 0.00 | 0.33 |
June | 0.00 | 0.246990E+09 | 0.00 | 0.349990E+09 | 0.00 | 0.00 | 0.210707E+10 | 0.00 | 0.34 |
July | 0.00 | 0.150594E+10 | 0.00 | 0.218609E+09 | 0.00 | 0.00 | 0.384073E+09 | 0.00 | 0.32 |
August | 0.00 | 0.187141E+10 | 0.00 | 0.210446E+09 | 0.00 | 0.00 | 0.269748E+09 | 0.00 | 0.35 |
September | 0.00 | 0.539565E+09 | 0.00 | 0.136599E+09 | 0.00 | 0.00 | 0.156326E+10 | 0.00 | 0.33 |
October | 0.00 | 0.603137E+09 | 0.00 | 0.291311E+09 | 0.00 | 0.00 | 0.289991E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.595819E+09 | 0.00 | 0.00 | 0.581921E+10 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.817227E+09 | 0.00 | 0.00 | 0.691323E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.478274E+10 | 0.00 | 0.484765E+10 | 0.00 | 0.00 | 0.473179E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136599E+09 | 0.00 | 0.00 | 0.269748E+09 | 0.00 | 0.31 |