Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:41
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2020-06-03 19:41:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1737.76 | 348.79 | 348.79 |
Net Site Energy | 1737.76 | 348.79 | 348.79 |
Total Source Energy | 5276.54 | 1059.08 | 1059.08 |
Net Source Energy | 5276.54 | 1059.08 | 1059.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 31.19 | 35.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 234.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 101.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 806.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 104.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 73.70 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1628.81 | 108.94 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 31.19 | 35.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 234.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 331.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 101.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 164.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 104.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 73.70 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 74.24 | 21.87 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 165.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 326.93 | 21.87 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 74.24 | 21.87 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 165.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 326.93 | 21.87 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1628.812 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1628.812 | 100.00 |
Total On-Site and Utility Electric Sources | 1628.812 | 100.00 |
Total Electricity End Uses | 1628.812 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 254.33 |
Time Setpoint Not Met During Occupied Cooling | 511.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1357.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Meter |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT_COOLC DXCOIL | PACU_VAV_MID_COOLC DXCOIL | PACU_VAV_TOP_COOLC DXCOIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT_HEATC | PACU_VAV_MID_HEATC | PACU_VAV_TOP_HEATC | PACU_VAV_BOT_COOLC DXCOIL | PACU_VAV_MID_COOLC DXCOIL | PACU_VAV_TOP_COOLC DXCOIL |PlantLoopDemandReportMonthly
| SHWSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SHWSYS1 PUMP |CondLoopDemandReportMonthly
| SHWSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 40.8445 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.9438 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.9438 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.9438 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.9438 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.9438 | 18.58 | 14.5400 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.9438 | 18.58 | 14.5400 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-15:00 | 21-JAN-07:10 | - | - | - | 02-JAN-12:20 |
Heating | 0.00 | 48213.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28132.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 51013.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1341.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 172369.45 | 49369.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 48213.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 74291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28132.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 14770.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1341.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 17589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 98.78 | 38.20 | 0.00 | 0.00 | 0.00 |
Cooling | 742.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1049.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 322.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2554.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 59.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 329.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 79.89 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5158.45 | 118.10 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 19.83 | 7.67 | 0.00 | 0.00 | 0.00 |
Cooling | 149.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 210.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 512.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1035.38 | 23.70 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 19.83 | 7.67 | 0.00 | 0.00 | 0.00 |
Cooling | 149.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 210.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 512.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1035.38 | 23.70 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Flow Fraction during Reheat [] | |
CORE_BOTTOM VAV BOX COMPONENT | 4.34 | 0.172740 | 0.300000 | 1.30 | 0.001323 | 0.300000 |
CORE_MID VAV BOX COMPONENT | 2.54 | 0.295577 | 0.308000 | 0.780953 | 0.000794 | 0.308000 |
CORE_TOP VAV BOX COMPONENT | 2.64 | 0.283758 | 0.304000 | 0.802918 | 0.000816 | 0.304000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.762918 | 0.207089 | 0.300000 | 0.228875 | 0.001104 | 0.300000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.849421 | 0.117753 | 0.300000 | 0.254826 | 0.001941 | 0.300000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.822376 | 0.192116 | 0.300000 | 0.246713 | 0.001190 | 0.300000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.946367 | 0.105683 | 0.300000 | 0.283910 | 0.002163 | 0.300000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.635220 | 0.248720 | 0.300000 | 0.190566 | 0.000919 | 0.300000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.720359 | 0.138850 | 0.300000 | 0.216108 | 0.001646 | 0.300000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.694583 | 0.227463 | 0.300000 | 0.208375 | 0.001005 | 0.300000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.770888 | 0.129740 | 0.300000 | 0.231266 | 0.001762 | 0.300000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.668988 | 0.236165 | 0.300000 | 0.200696 | 0.000968 | 0.300000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.851163 | 0.117512 | 0.300000 | 0.255349 | 0.001945 | 0.300000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.728700 | 0.216813 | 0.300000 | 0.218610 | 0.001054 | 0.300000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.886570 | 0.112811 | 0.300000 | 0.265971 | 0.002026 | 0.300000 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 35754.81 |
CORE_MID VAV BOX REHEAT COIL | 21452.88 |
CORE_TOP VAV BOX REHEAT COIL | 29573.56 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12417.38 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8167.39 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12450.46 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8167.24 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9202.69 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6141.04 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9223.43 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6352.92 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9595.82 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7014.47 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 9653.28 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7306.26 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.15 | 2.15 | 7.16 | 2.15 | 6.59 | 6.59 | 0.300000 | 0.325743 | 6.59 |
PACU_VAV_MID | 1.72 | 1.72 | 5.67 | 1.75 | 4.96 | 4.96 | 0.300000 | 0.352941 | 4.96 |
PACU_VAV_TOP | 1.82 | 1.82 | 6.02 | 2.58 | 5.60 | 5.60 | 0.300000 | 0.460317 | 5.60 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.59 |
PACU_VAV_MID_OA_CONTROLLER | 4.96 |
PACU_VAV_TOP_OA_CONTROLLER | 5.60 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT_COOLC DXCOIL | 6.59 | 109151.86 | 0.800655 | 2.20 | 36380.31 | 0.800655 |
PACU_VAV_MID_COOLC DXCOIL | 4.96 | 82161.81 | 0.800655 | 1.65 | 27384.53 | 0.800655 |
PACU_VAV_TOP_COOLC DXCOIL | 5.60 | 92653.06 | 0.800655 | 1.87 | 30881.26 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT_HEATC | 17399.41 |
PACU_VAV_MID_HEATC | 22666.69 |
PACU_VAV_TOP_HEATC | 22203.43 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.59 |
PACU_VAV_MID FAN | 4.96 |
PACU_VAV_TOP FAN | 5.60 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.944 | 40.844 | 0.000 | 0.000 | 0.000 | 0.000 | 48.788 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.944 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.944 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.944 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7812.984 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7812.984 |
2 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 983.54 | 52.9 | 7812.984 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7812.984 |
3 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 983.54 | 52.9 | 7812.984 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7812.984 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1647.046 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1647.046 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1042.716 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1042.716 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1647.046 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1647.046 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1042.648 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1042.648 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1647.046 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1647.046 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1042.716 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1042.716 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1647.046 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1647.046 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1042.648 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1042.648 |
12 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1647.046 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1647.046 |
13 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1042.716 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1042.716 |
14 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1647.046 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1647.046 |
15 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1042.648 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1042.648 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 32109.890 | 32.647 | 606.549 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 22155.824 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 34 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
19 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
20 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
21 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
22 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
23 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
43 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
44 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
45 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
46 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
47 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
48 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
49 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
50 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
51 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
52 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
53 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
54 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
55 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
56 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
57 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
58 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
59 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
60 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
61 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
62 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
63 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
64 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
65 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
66 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
67 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
68 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
69 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
70 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
71 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
72 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
73 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
74 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
75 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
76 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
77 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
78 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
79 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
80 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
81 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
82 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
83 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
84 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
85 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
86 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
87 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
88 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
89 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
90 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.021 | 0.3124 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.790E-002 | 3.757E-004 | 5.690E-004 | 0.493 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.193E-002 | 3.956E-004 | 5.690E-004 | 0.519 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.790E-002 | 3.757E-004 | 5.690E-004 | 0.493 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.193E-002 | 3.957E-004 | 5.690E-004 | 0.519 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 8.012E-002 | 3.864E-004 | 5.690E-004 | 0.507 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.304E-002 | 4.041E-004 | 5.690E-004 | 0.530 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 8.012E-002 | 3.864E-004 | 5.690E-004 | 0.507 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.304E-002 | 4.041E-004 | 5.690E-004 | 0.530 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.790E-002 | 3.757E-004 | 5.690E-004 | 0.493 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.193E-002 | 3.956E-004 | 5.690E-004 | 0.519 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.790E-002 | 3.757E-004 | 5.690E-004 | 0.493 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.193E-002 | 3.957E-004 | 5.690E-004 | 0.519 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.115 | 6.949E-005 | 5.690E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.115 | 6.949E-005 | 5.690E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.115 | 6.949E-005 | 6.193E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 49481.91714 | 49481.91714 | 4.33863 | 4.33863 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.65324E-003 | 983.53657 | 52.93867 | 0.42466 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7189.74613 | 7189.74613 | 0.37549 | 0.42466 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42466 | 0.00000 |
3 | CORE_MID | Cooling | 28957.51119 | 28957.51119 | 2.53556 | 2.53556 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.65324E-003 | 983.53657 | 52.93867 | 0.42466 | 0.00000 |
4 | CORE_MID | Heating | 11360.20428 | 11360.20428 | 0.58412 | 0.58412 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42466 | 0.00000 |
5 | CORE_TOP | Cooling | 29898.46230 | 29898.46230 | 2.64118 | 2.64118 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.65325E-003 | 983.53657 | 52.93867 | 0.42466 | 0.00000 |
6 | CORE_TOP | Heating | 20833.64171 | 20833.64171 | 1.07657 | 1.07657 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42466 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8636.56546 | 8636.56546 | 0.76292 | 0.76292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8723.51032 | 8723.51032 | 0.45203 | 0.45203 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9615.91133 | 9615.91133 | 0.84942 | 0.84942 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.05750 | 5.65325E-003 | 131.26219 | 7.06516 | 5.66755E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5737.15044 | 5737.15044 | 0.29732 | 0.29732 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66755E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 9309.66745 | 9309.66745 | 0.82238 | 0.82238 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8746.68401 | 8746.68401 | 0.45324 | 0.45324 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10713.39653 | 10713.39653 | 0.94637 | 0.94637 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 131.25358 | 7.06470 | 5.66718E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5737.04658 | 5737.04658 | 0.29731 | 0.29731 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66718E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7190.90833 | 7190.90833 | 0.63522 | 0.63522 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.65324E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6471.16332 | 6471.16332 | 0.33501 | 0.33501 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8154.79271 | 8154.79271 | 0.72036 | 0.72036 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.05750 | 5.65325E-003 | 131.26219 | 7.06516 | 5.66755E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4317.39461 | 4317.39461 | 0.22355 | 0.22355 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66755E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 7862.93139 | 7862.93139 | 0.69458 | 0.69458 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.65325E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6485.70161 | 6485.70161 | 0.33576 | 0.33576 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8726.80436 | 8726.80436 | 0.77089 | 0.77089 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.31000 | 5.65325E-003 | 131.25358 | 7.06470 | 5.66718E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4317.36768 | 4317.36768 | 0.22355 | 0.22355 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66718E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7573.20636 | 7573.20636 | 0.66899 | 0.66899 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.65324E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6747.08587 | 6747.08587 | 0.34932 | 0.34932 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9635.61636 | 9635.61636 | 0.85116 | 0.85116 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.65324E-003 | 131.26219 | 7.06516 | 5.66755E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4508.49018 | 4508.49018 | 0.23347 | 0.23347 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66755E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8249.17995 | 8249.17995 | 0.72870 | 0.72870 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.65324E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6787.32892 | 6787.32892 | 0.35141 | 0.35141 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95230E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10036.42589 | 10036.42589 | 0.88657 | 0.88657 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 131.25358 | 7.06470 | 5.66718E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4508.45227 | 4508.45227 | 0.23346 | 0.23346 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66718E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 84166.07 | 6.59386 | 6.59386 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 23086.38 | 1.54254 | 1.54254 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66672.62 | 4.96340 | 4.96340 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24442.17 | 1.75178 | 1.75178 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 74791.71 | 5.59717 | 5.59717 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 24553.59 | 2.57647 | 2.57647 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.33863 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17274 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30159 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32338E-003 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
7 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35754.81458 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53556 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29558 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78095 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.94025E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30800 |
14 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21452.88360 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64118 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28376 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80292 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.16358E-004 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30400 |
21 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29573.55745 |
22 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76292 |
23 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20709 |
24 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22888 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10387E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
28 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12417.38048 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84942 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11775 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25483 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94135E-003 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
35 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8167.38961 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82238 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19212 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24671 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18991E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
42 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12450.45533 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94637 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10568 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28391 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16307E-003 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
49 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8167.24287 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63522 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24872 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19057 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.19107E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
56 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9202.68547 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72036 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13885 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21611 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64638E-003 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6141.04259 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69458 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22746 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20837 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00500E-003 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
70 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9223.42921 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77089 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12974 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23127 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76198E-003 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
77 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6352.91574 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66899 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23617 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20070 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.67966E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9595.82286 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85116 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11751 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25535 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94534E-003 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7014.47124 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72870 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21681 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21861 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05436E-003 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
98 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9653.27525 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88657 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11281 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26597 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02639E-003 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
105 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7306.25802 |
106 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.14790 |
107 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.14790 |
108 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.15968 |
109 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.14790 |
110 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.59386 |
111 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.59386 |
112 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
113 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.32574 |
114 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.72158 |
115 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72158 |
116 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.67098 |
117 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.75178 |
118 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.96340 |
119 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.96340 |
120 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
121 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.35294 |
122 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.81724 |
123 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.81724 |
124 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.02226 |
125 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.57647 |
126 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.59717 |
127 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.59717 |
128 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
129 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.46032 |
130 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.59386 |
131 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.96340 |
132 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.59717 |
133 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.59386 |
134 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.59386 |
135 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 109151.85686 |
136 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
137 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.19773 |
138 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36380.31389 |
139 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
140 | Coil:Heating:Fuel | PACU_VAV_BOT_HEATC | Design Size Nominal Capacity [W] | 17399.41065 |
141 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.59386 |
142 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.96340 |
143 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.96340 |
144 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 82161.81154 |
145 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65430 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27384.53179 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
149 | Coil:Heating:Fuel | PACU_VAV_MID_HEATC | Design Size Nominal Capacity [W] | 22666.69208 |
150 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.96340 |
151 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.59717 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.59717 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92653.05709 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86554 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30881.26393 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
158 | Coil:Heating:Fuel | PACU_VAV_TOP_HEATC | Design Size Nominal Capacity [W] | 22203.43122 |
159 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.59717 |
160 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
161 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
162 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
163 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
164 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | N/A | N/A | 107273.63 | 366032.80 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.06 | 6.2721 | 4.9614 | 3.3261 | 1.4001 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | N/A | N/A | 80748.01 | 275523.65 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.06 | 4.7212 | 3.7346 | 2.5036 | 1.0539 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | N/A | N/A | 91058.73 | 310705.28 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.06 | 5.3240 | 4.2115 | 2.8233 | 1.1885 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 17 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.9409268777E-002 | 0.2014639919 | Pass | Pass | 0.1195060806 | 0.3219058440 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1851383933E-002 | 7.5292013508E-002 | Pass | Pass | 8.5179342964E-002 | 0.2887024553 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.0723981178E-002 | 3.7085554641E-002 | Pass | Pass | 0.3903393813 | 1.8358120923 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.4097992062E-002 | 4.0222061506E-002 | Pass | Pass | 0.2282979582 | 0.9177195922 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.0212012527E-002 | 0.1173035498 | Pass | Pass | 0.1041274044 | 0.3020399052 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.1344427497E-002 | 9.2998606232E-002 | Pass | Pass | 7.6146007976E-002 | 0.2614098987 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.8293145380E-002 | 8.4226334761E-002 | Pass | Pass | 7.5445849743E-002 | 0.2583868878 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1400092770 | 0.1871105798 | Pass | Pass | 7.6242864860E-002 | 0.2611293901 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2002761740 | 0.2270467011 | Pass | Pass | 7.6633728903E-002 | 0.2637210083 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1353855283 | 0.2141188228 | Pass | Pass | 7.4060841316E-002 | 0.2508503876 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.0522839490E-002 | 8.8344484705E-002 | Pass | Pass | 0.1178293669 | 0.3176643982 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1391668301 | 0.1985813250 | Pass | Pass | 0.1190896503 | 0.3210083405 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1798774944 | 0.2742540976 | Pass | Pass | 0.1249237229 | 0.3270935498 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1301977131 | 0.2116236729 | Pass | Pass | 0.1170820870 | 0.3135038745 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.6558915995E-002 | 9.5752301743E-002 | Pass | Pass | 0.1031848988 | 0.2986719079 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1619733941 | 0.2251734912 | Pass | Pass | 0.1055870060 | 0.3040231828 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2118318484 | 0.2988786719 | Pass | Pass | 0.1189759503 | 0.3272920585 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1418299806 | 0.2348941591 | Pass | Pass | 0.1021312892 | 0.2936178731 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | ||
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | ||
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | ||
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 593.29 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 177.99 | 2.159 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 415.31 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 7.9438 | 983.54 | 7812.98 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 49.03 | 0.0000 | Y | 71.91 |
CORE_MID_LIGHTS | CORE_MID | 7.9438 | 983.54 | 7812.98 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 49.03 | 0.0000 | Y | 71.91 |
CORE_TOP_LIGHTS | CORE_TOP | 7.9438 | 983.54 | 7812.98 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 49.03 | 0.0000 | Y | 71.91 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 7.9438 | 207.34 | 1647.05 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.27 | 0.0000 | Y | 11.83 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 7.9438 | 131.26 | 1042.72 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.26 | 0.0000 | Y | 7.49 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 7.9438 | 207.34 | 1647.05 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.15 | 0.0000 | Y | 11.80 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 7.9438 | 131.25 | 1042.65 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.17 | 0.0000 | Y | 7.47 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 7.9438 | 207.34 | 1647.05 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.25 | 0.0000 | Y | 11.83 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 7.9438 | 131.26 | 1042.72 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.24 | 0.0000 | Y | 7.49 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 7.9438 | 207.34 | 1647.05 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.14 | 0.0000 | Y | 11.79 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 7.9438 | 131.25 | 1042.65 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.15 | 0.0000 | Y | 7.47 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 7.9438 | 207.34 | 1647.05 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.27 | 0.0000 | Y | 11.83 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 7.9438 | 131.26 | 1042.72 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.26 | 0.0000 | Y | 7.49 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 7.9438 | 207.34 | 1647.05 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.15 | 0.0000 | Y | 11.80 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 7.9438 | 131.25 | 1042.65 | LightsWired | BLDG_LIGHT_SCH | 50.32 | 168.00 | 38.17 | 0.0000 | Y | 7.47 |
Interior Lighting Total | 7.9438 | 4982.19 | 39577.32 | 331.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1647.05 | 631.64 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1647.05 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1042.72 | 399.88 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1042.72 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1647.05 | 631.64 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1647.05 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1042.65 | 399.86 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1042.65 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1647.05 | 631.64 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1647.05 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1042.72 | 399.88 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1042.72 | 0.00 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1647.05 | 631.64 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1647.05 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1042.65 | 399.86 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1042.65 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1647.05 | 631.64 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1647.05 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1042.72 | 399.88 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1042.72 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1647.05 | 631.64 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1647.05 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.38 | 1042.65 | 399.86 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1042.65 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 390.43 | AstronomicalClock | - | 41.81 | 41.81 | 3.06 | |
EXTERIOR_LIGHTS_B | 7402.35 | AstronomicalClock | - | 83.71 | 71.14 | 98.85 | |
Exterior Lighting Total | 7792.78 | 101.91 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 109151.86 | 87393.01 | 21758.85 | 0.80 | 3.40 | |||
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 82161.81 | 65783.29 | 16378.52 | 0.80 | 3.40 | |||
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 92653.06 | 74183.16 | 18469.90 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT_COOLC DXCOIL | 107273.6 | 2.80 | 9.54 | N/A | 11.20 | |
PACU_VAV_MID_COOLC DXCOIL | 80748.0 | 2.80 | 9.54 | N/A | 11.20 | |
PACU_VAV_TOP_COOLC DXCOIL | 91058.7 | 2.80 | 9.54 | N/A | 11.20 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 35754.81 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21452.88 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 29573.56 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12417.38 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8167.39 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12450.46 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8167.24 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9202.69 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6141.04 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9223.43 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6352.92 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9595.82 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7014.47 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9653.28 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7306.26 | 1.00 | |
PACU_VAV_BOT_HEATC | Coil:Heating:Fuel | 17399.41 | 0.80 | |
PACU_VAV_MID_HEATC | Coil:Heating:Fuel | 22666.69 | 0.80 | |
PACU_VAV_TOP_HEATC | Coil:Heating:Fuel | 22203.43 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.59 | 14340.92 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.96 | 10864.93 | 2189.01 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.60 | 12173.22 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.31 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 107273.63 | 2.80 | 9.54 | 11.20 | 6.2721 | 3.21 | 10.95 | 4.9614 | 3.38 | 11.55 | 3.3261 | 3.53 | 12.06 | 1.4001 |
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 80748.01 | 2.80 | 9.54 | 11.20 | 4.7212 | 3.21 | 10.95 | 3.7346 | 3.38 | 11.55 | 2.5036 | 3.53 | 12.06 | 1.0539 |
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 91058.73 | 2.80 | 9.54 | 11.20 | 5.3240 | 3.21 | 10.95 | 4.2115 | 3.38 | 11.55 | 2.8233 | 3.53 | 12.06 | 1.1885 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 49481.92 | 49481.92 | 50.31 | 4.339 | 4.339 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00874 | 25.11 | 0.00565 | 0.425 | 0.00 |
CORE_MID | 28957.51 | 28957.51 | 29.44 | 2.536 | 2.536 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 25.11 | 0.00565 | 0.425 | 0.00 |
CORE_TOP | 29898.46 | 29898.46 | 30.40 | 2.641 | 2.641 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00890 | 34.97 | 0.00565 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8636.57 | 8636.57 | 41.65 | 0.763 | 0.763 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00876 | 35.10 | 0.00565 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9615.91 | 9615.91 | 73.26 | 0.849 | 0.849 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00865 | 28.06 | 0.00565 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9309.67 | 9309.67 | 44.90 | 0.822 | 0.822 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00874 | 35.10 | 0.00565 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10713.40 | 10713.40 | 81.62 | 0.946 | 0.946 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00863 | 33.21 | 0.00565 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7190.91 | 7190.91 | 34.68 | 0.635 | 0.635 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00883 | 35.10 | 0.00565 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8154.79 | 8154.79 | 62.13 | 0.720 | 0.720 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00868 | 28.06 | 0.00565 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7862.93 | 7862.93 | 37.92 | 0.695 | 0.695 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00880 | 34.97 | 0.00565 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8726.80 | 8726.80 | 66.49 | 0.771 | 0.771 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00867 | 32.31 | 0.00565 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7573.21 | 7573.21 | 36.53 | 0.669 | 0.669 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00880 | 35.10 | 0.00565 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9635.62 | 9635.62 | 73.41 | 0.851 | 0.851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00865 | 27.68 | 0.00565 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8249.18 | 8249.18 | 39.79 | 0.729 | 0.729 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00878 | 35.10 | 0.00565 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10036.43 | 10036.43 | 76.47 | 0.887 | 0.887 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 33.21 | 0.00565 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7189.75 | 7189.75 | 7.31 | 0.375 | 0.425 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
CORE_MID | 11360.20 | 11360.20 | 11.55 | 0.584 | 0.584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
CORE_TOP | 20833.64 | 20833.64 | 21.18 | 1.077 | 1.077 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8723.51 | 8723.51 | 42.07 | 0.452 | 0.452 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5737.15 | 5737.15 | 43.71 | 0.297 | 0.297 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8746.68 | 8746.68 | 42.19 | 0.453 | 0.453 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5737.05 | 5737.05 | 43.71 | 0.297 | 0.297 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6471.16 | 6471.16 | 31.21 | 0.335 | 0.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4317.39 | 4317.39 | 32.89 | 0.224 | 0.224 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6485.70 | 6485.70 | 31.28 | 0.336 | 0.336 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4317.37 | 4317.37 | 32.89 | 0.224 | 0.224 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6747.09 | 6747.09 | 32.54 | 0.349 | 0.349 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4508.49 | 4508.49 | 34.35 | 0.233 | 0.233 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6787.33 | 6787.33 | 32.74 | 0.351 | 0.351 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4508.45 | 4508.45 | 34.35 | 0.233 | 0.233 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -7.90 | 0.00234 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.59 | 6.59 | 1.54 | 1.54 | 6.5939 | 2.1479 | 6.5939 | 0.3257 | 0.3000 |
PACU_VAV_MID | 4.96 | 4.96 | 1.75 | 1.75 | 4.9634 | 1.7518 | 4.9634 | 0.3529 | 0.3000 |
PACU_VAV_TOP | 5.60 | 5.60 | 2.58 | 2.58 | 5.5972 | 2.5765 | 5.5972 | 0.4603 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 35754.815 | 35754.815 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 35754.81 | 11665.59 | 0.424665 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 7189.75 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21452.884 | 21452.884 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21452.88 | 16045.97 | 0.584124 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 11360.20 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 29573.557 | 29573.557 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29573.56 | 29573.56 | 1.076571 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 20833.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 12417.380 | 12417.380 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12417.38 | 12417.38 | 0.452032 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790294 | 42.0282 | 8723.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8167.390 | 8167.390 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8167.39 | 8167.39 | 0.297319 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790453 | 42.0365 | 5737.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 12450.455 | 12450.455 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12450.46 | 12450.46 | 0.453236 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790317 | 42.0294 | 8746.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8167.243 | 8167.243 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8167.24 | 8167.24 | 0.297314 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790453 | 42.0365 | 5737.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9202.685 | 9202.685 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9202.69 | 9202.69 | 0.335007 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00783407 | 41.6672 | 6471.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6141.043 | 6141.043 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6141.04 | 6141.04 | 0.223553 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00785381 | 41.7707 | 4317.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9223.429 | 9223.429 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9223.43 | 9223.43 | 0.335762 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00783549 | 41.6746 | 6485.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6352.916 | 6352.916 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6352.92 | 6141.01 | 0.223552 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00785382 | 41.7708 | 4317.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 9595.823 | 9595.823 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9595.82 | 9595.82 | 0.349318 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00782636 | 41.6267 | 6747.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7014.471 | 7014.471 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7014.47 | 6413.36 | 0.233467 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00784506 | 41.7248 | 4508.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 9653.275 | 9653.275 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9653.28 | 9653.28 | 0.351410 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00782921 | 41.6417 | 6787.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7306.258 | 7306.258 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7306.26 | 6413.31 | 0.233465 | 12.80 | 9.85 | 0.00800000 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00784507 | 41.7249 | 4508.45 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 109151.857 | 87393.008 | 6.593864 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 112826.51 | 112826.51 | 6.593864 | 25.85 | 14.76 | 0.00822918 | 10.65 | 9.21 | 0.00822918 | 34.70 | 0.00565324 | 15.57 | 17.0190 | 24.00 | 0.00874356 | 38.7001 | 73354.25 | 0.00 | 112494.61 | 80977.98 |
PACU_VAV_BOT_HEATC | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 17399.411 | 17399.411 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17399.41 | 17399.41 | 1.978159 | -7.90 | -7.90 | 0.00234317 | 12.80 | 9.85 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 56.7300 | 21.00 | 0.00788578 | 41.9383 | 14974.53 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 82161.812 | 65783.287 | 4.963395 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 84833.54 | 84833.54 | 4.963395 | 26.60 | 14.88 | 0.00806589 | 10.63 | 9.04 | 0.00806589 | 34.56 | 0.00565325 | 15.53 | 24.0783 | 24.00 | 0.00880647 | 38.9746 | 54961.07 | 0.00 | 84678.00 | 60954.50 |
PACU_VAV_MID_HEATC | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 22666.692 | 22666.692 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22666.69 | 22666.69 | 1.489019 | -7.30 | -7.32 | 0.00245853 | 12.80 | 9.85 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 80.2609 | 21.00 | 0.00788982 | 41.9594 | 20965.13 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 92653.057 | 74183.158 | 5.597171 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 95665.93 | 95665.93 | 5.597171 | 26.26 | 14.82 | 0.00813066 | 10.65 | 9.11 | 0.00813066 | 34.56 | 0.00565325 | 15.53 | 21.3519 | 24.00 | 0.00878342 | 38.8740 | 63207.72 | 0.00 | 95490.53 | 68737.79 |
PACU_VAV_TOP_HEATC | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 22203.431 | 22203.431 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22203.43 | 22203.43 | 1.679151 | -7.90 | -7.90 | 0.00234317 | 12.80 | 9.85 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 71.1729 | 21.00 | 0.00794390 | 42.2429 | 23334.89 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 35754.815 | 35754.815 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 35754.81 | 11665.59 | 1.0000 | 0.42059153 | 0.424665 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35754.81 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.03 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 7189.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21452.884 | 21452.884 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21452.88 | 16045.97 | 1.0000 | 0.57852174 | 0.584124 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21452.88 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 11360.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 29573.557 | 29573.557 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29573.56 | 29573.56 | 1.0000 | 1.06624573 | 1.076571 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29573.56 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 20833.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12417.380 | 12417.380 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12417.38 | 12417.38 | 1.0000 | 0.44769653 | 0.452032 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12417.38 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790294 | 21.00 | 0.00790294 | 42.0282 | 8723.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8167.390 | 8167.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8167.39 | 8167.39 | 1.0000 | 0.29446726 | 0.297319 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8167.39 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790453 | 21.00 | 0.00790453 | 42.0365 | 5737.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12450.455 | 12450.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12450.46 | 12450.46 | 1.0000 | 0.44888901 | 0.453236 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12450.46 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790317 | 21.00 | 0.00790317 | 42.0294 | 8746.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8167.243 | 8167.243 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8167.24 | 8167.24 | 1.0000 | 0.29446197 | 0.297314 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8167.24 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790453 | 21.00 | 0.00790453 | 42.0365 | 5737.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9202.685 | 9202.685 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9202.69 | 9202.69 | 1.0000 | 0.33179384 | 0.335007 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9202.69 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00783407 | 21.00 | 0.00783407 | 41.6672 | 6471.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6141.043 | 6141.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6141.04 | 6141.04 | 1.0000 | 0.22140929 | 0.223553 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6141.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785381 | 21.00 | 0.00785381 | 41.7707 | 4317.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9223.429 | 9223.429 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9223.43 | 9223.43 | 1.0000 | 0.33254173 | 0.335762 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9223.43 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00783549 | 21.00 | 0.00783549 | 41.6746 | 6485.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6352.916 | 6352.916 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6352.92 | 6141.01 | 1.0000 | 0.22140796 | 0.223552 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6352.92 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785382 | 21.00 | 0.00785382 | 41.7708 | 4317.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9595.823 | 9595.823 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9595.82 | 9595.82 | 1.0000 | 0.34596802 | 0.349318 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9595.82 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782636 | 21.00 | 0.00782636 | 41.6267 | 6747.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7014.471 | 7014.471 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7014.47 | 6413.36 | 1.0000 | 0.23122747 | 0.233467 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7014.47 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784506 | 21.00 | 0.00784506 | 41.7248 | 4508.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9653.275 | 9653.275 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9653.28 | 9653.28 | 1.0000 | 0.34803941 | 0.351410 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9653.28 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782921 | 21.00 | 0.00782921 | 41.6417 | 6787.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7306.258 | 7306.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7306.26 | 6413.31 | 1.0000 | 0.23122558 | 0.233465 | 12.80 | 9.85 | 0.00800000 | 33059.8 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7306.26 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784507 | 21.00 | 0.00784507 | 41.7249 | 4508.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 109151.857 | 87393.008 | 6.593864 | -999.0 | -999.000 | -999.0000 | 1.07231 | 1.00000 | 1020.1376 | 1004.8586 | 0.9904 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.593864 | 6.53062123 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 112826.51 | 112826.51 | 0.9674 | 6.53062123 | 6.593864 | 25.85 | 14.76 | 0.00822918 | 46952.4 | 10.65 | 9.21 | 0.00822918 | 31442.5 | -999.0 | -999.00 | -999.00 | -999.00 | 14340.917 | 98485.59 | 34.70 | 0.00565324 | 15.57 | 1.12221000 | 17.0190 | 24.00 | 0.00876873 | 24.00 | 0.00874356 | 38.7001 | 73354.25 | 0.00 | 112494.61 | 80977.98 | 6.27206420 | 26.67 | 19.44 | 0.01117891 | 55307.7 | 14.03 | 13.29 | 0.00920875 | 37371.9 | |
PACU_VAV_BOT_HEATC | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17399.411 | 17399.411 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.593864 | 6.53062123 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17399.41 | 17399.41 | 1.0000 | 1.95918637 | 1.978159 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 12.80 | 9.85 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17399.41 | -7.90 | 0.00234317 | -7.90 | 1.12221000 | 56.7300 | 19.51 | 0.00759193 | 21.00 | 0.00788578 | 41.9383 | 14974.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 82161.812 | 65783.287 | 4.963395 | -999.0 | -999.000 | -999.0000 | 1.02475 | 1.00000 | 1019.8341 | 1004.8586 | 0.9904 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.963395 | 4.91579059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 84833.54 | 84833.54 | 0.9685 | 4.91579059 | 4.963395 | 26.60 | 14.88 | 0.00806589 | 47298.3 | 10.63 | 9.04 | 0.00806589 | 31016.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10864.926 | 73968.61 | 34.56 | 0.00565325 | 15.53 | 1.19510000 | 24.0783 | 24.00 | 0.00885370 | 24.00 | 0.00880647 | 38.9746 | 54961.07 | 0.00 | 84678.00 | 60954.50 | 4.72116711 | 26.67 | 19.44 | 0.01117891 | 55307.7 | 14.03 | 13.29 | 0.00920875 | 37371.9 | |
PACU_VAV_MID_HEATC | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22666.692 | 22666.692 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.963395 | 4.91579059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22666.69 | 22666.69 | 1.0000 | 1.47473718 | 1.489019 | -7.30 | -7.32 | 0.00245853 | -1219.4 | 12.80 | 9.85 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22666.69 | -7.90 | 0.00234317 | -7.90 | 1.19510000 | 80.2609 | 19.48 | 0.00760196 | 21.00 | 0.00788982 | 41.9594 | 20965.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92653.057 | 74183.158 | 5.597171 | -999.0 | -999.000 | -999.0000 | 1.04681 | 1.00000 | 1019.9545 | 1004.8586 | 0.9904 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.597171 | 5.54348812 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 95665.93 | 95665.93 | 0.9685 | 5.54348812 | 5.597171 | 26.26 | 14.82 | 0.00813066 | 47117.6 | 10.65 | 9.11 | 0.00813066 | 31193.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12173.222 | 83492.71 | 34.56 | 0.00565325 | 15.53 | 1.19510000 | 21.3519 | 24.00 | 0.00880533 | 24.00 | 0.00878342 | 38.8740 | 63207.72 | 0.00 | 95490.53 | 68737.79 | 5.32401316 | 26.67 | 19.44 | 0.01117891 | 55307.7 | 14.03 | 13.29 | 0.00920875 | 37371.9 | |
PACU_VAV_TOP_HEATC | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22203.431 | 22203.431 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.597171 | 5.54348812 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22203.43 | 22203.43 | 1.0000 | 1.66304643 | 1.679151 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 12.80 | 9.85 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22203.43 | -7.90 | 0.00234317 | -7.90 | 1.19510000 | 71.1729 | 17.82 | 0.00562770 | 21.00 | 0.00794390 | 42.2429 | 23334.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.59 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.96 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.60 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1599.17 | 2492.17 | 0.00 |
CORE_MID | 1566.67 | 3246.17 | 3.17 |
CORE_TOP | 1713.33 | 3488.67 | 229.00 |
PERIMETER_TOP_ZN_3 | 2454.67 | 3807.33 | 1054.33 |
PERIMETER_TOP_ZN_2 | 2496.50 | 3574.83 | 822.00 |
PERIMETER_TOP_ZN_1 | 2421.33 | 2845.67 | 530.83 |
PERIMETER_TOP_ZN_4 | 2252.67 | 4035.00 | 968.00 |
PERIMETER_BOT_ZN_3 | 2077.17 | 3838.17 | 657.83 |
PERIMETER_BOT_ZN_2 | 2233.67 | 3235.67 | 340.67 |
PERIMETER_BOT_ZN_1 | 2119.83 | 3168.17 | 343.67 |
PERIMETER_BOT_ZN_4 | 1947.67 | 3611.67 | 400.50 |
PERIMETER_MID_ZN_3 | 2029.00 | 3590.83 | 503.00 |
PERIMETER_MID_ZN_2 | 1760.67 | 3084.50 | 417.67 |
PERIMETER_MID_ZN_1 | 2377.50 | 2485.17 | 235.83 |
PERIMETER_MID_ZN_4 | 1838.00 | 3819.00 | 491.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4099.83 | 4696.50 | 1357.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6.50 | 0.33 | 5.83 | 0.33 |
PERIMETER_TOP_ZN_2 | 0.50 | 19.83 | 0.00 | 19.67 |
PERIMETER_TOP_ZN_1 | 2.17 | 166.67 | 1.83 | 166.67 |
PERIMETER_TOP_ZN_4 | 0.33 | 19.83 | 0.00 | 12.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 10.67 | 0.00 | 10.67 |
PERIMETER_BOT_ZN_1 | 250.67 | 146.00 | 250.67 | 146.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 10.17 | 0.00 | 5.17 |
PERIMETER_MID_ZN_3 | 0.33 | 0.00 | 0.33 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 20.50 | 0.00 | 20.50 |
PERIMETER_MID_ZN_1 | 0.00 | 352.67 | 0.00 | 352.67 |
PERIMETER_MID_ZN_4 | 0.00 | 17.83 | 0.00 | 11.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 255.17 | 523.33 | 254.33 | 511.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 1.314 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.724 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.713 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.897 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.672 | 0.087 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.279 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.711 | 0.087 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.705 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.374 | 0.048 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.934 | 1.317 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.316 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.824 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.615 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.230 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.624 | 0.073 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1628.81 | 13911.62 | 01-JAN-08:40 | 172369.45 | 28-JUN-16:00 |
Electricity:Building | 1138.15 | 13624.74 | 01-JAN-08:30 | 88751.95 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 363.90 | 2727.61 | 01-JAN-06:10 | 35621.92 | 02-JAN-08:10 |
InteriorLights:Electricity | 331.48 | 1562.94 | 01-JAN-08:30 | 31591.01 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.91 | 346.47 | 01-JAN-06:10 | 6236.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 331.48 | 1562.94 | 01-JAN-08:30 | 31591.01 | 13-NOV-17:00 |
Electricity:Zone:CORE_MID | 198.51 | 2727.61 | 01-JAN-06:10 | 13379.84 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.91 | 346.47 | 01-JAN-06:10 | 6236.40 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 198.51 | 2727.61 | 01-JAN-06:10 | 13379.84 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.91 | 346.47 | 01-JAN-06:10 | 6236.40 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 38.52 | 555.40 | 01-JAN-08:30 | 2820.58 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.83 | 53.43 | 01-JAN-08:30 | 1314.69 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.38 | 351.59 | 01-JAN-07:40 | 1785.60 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.49 | 33.83 | 01-JAN-07:40 | 832.31 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 38.48 | 555.39 | 01-JAN-07:40 | 2820.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.80 | 53.43 | 01-JAN-07:40 | 1314.69 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.36 | 351.59 | 01-JAN-08:30 | 1785.54 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.47 | 33.82 | 01-JAN-08:30 | 832.25 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 38.51 | 555.40 | 01-JAN-08:30 | 2820.58 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.83 | 53.43 | 01-JAN-08:30 | 1314.69 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.38 | 351.59 | 01-JAN-07:40 | 1785.60 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.49 | 33.83 | 01-JAN-07:40 | 832.31 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 38.48 | 555.39 | 01-JAN-07:40 | 2820.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.79 | 53.43 | 01-JAN-07:40 | 1314.69 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.36 | 351.59 | 01-JAN-08:30 | 1785.54 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.47 | 33.82 | 01-JAN-08:30 | 832.25 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 38.52 | 555.40 | 01-JAN-08:30 | 2820.58 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.83 | 53.43 | 01-JAN-08:30 | 1314.69 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 24.38 | 351.59 | 01-JAN-07:40 | 1785.60 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.49 | 33.83 | 01-JAN-07:40 | 832.31 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 38.48 | 555.39 | 01-JAN-07:40 | 2820.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.80 | 53.43 | 01-JAN-07:40 | 1314.69 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 24.36 | 351.59 | 01-JAN-08:30 | 1785.54 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.47 | 33.82 | 01-JAN-08:30 | 832.25 | 13-NOV-17:00 |
InteriorEquipment:Electricity | 806.67 | 12061.80 | 01-JAN-00:10 | 58427.47 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 291.99 | 2381.15 | 01-JAN-00:10 | 29385.51 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.28 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 164.75 | 0.00 | 01-JAN-00:10 | 22155.82 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 388.73 | 285.40 | 01-JAN-00:10 | 93222.38 | 28-JUN-16:00 |
ExteriorEquipment:Electricity | 18.87 | 285.40 | 01-JAN-00:10 | 1349.06 | 05-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 18.87 | 285.40 | 01-JAN-00:10 | 1349.06 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 1628.81 | 13911.62 | 20-MAY-17:40 | 172369.45 | 28-JUN-16:00 |
ElectricityPurchased:Plant | 1628.81 | 13911.62 | 20-MAY-17:40 | 172369.45 | 28-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1628.81 | 13911.62 | 20-MAY-17:40 | 172369.45 | 28-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1628.81 | 13911.62 | 20-MAY-17:40 | 172369.45 | 28-JUN-16:00 |
ElectricityNet:Plant | 1628.81 | 13911.62 | 20-MAY-17:40 | 172369.45 | 28-JUN-16:00 |
Cogeneration:ElectricityNet | 1628.81 | 13911.62 | 20-MAY-17:40 | 172369.45 | 28-JUN-16:00 |
Heating:Electricity | 31.19 | 0.00 | 01-JAN-00:10 | 72843.53 | 06-FEB-07:10 |
Fans:Electricity | 104.10 | 0.00 | 01-JAN-00:10 | 17589.28 | 28-JUN-16:00 |
General:Fans:Electricity | 104.10 | 0.00 | 01-JAN-00:10 | 17589.28 | 28-JUN-16:00 |
ExteriorLights:Electricity | 101.91 | 0.00 | 01-JAN-07:20 | 7792.78 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 101.91 | 0.00 | 01-JAN-07:20 | 7792.78 | 01-JAN-06:10 |
Cooling:Electricity | 234.56 | 0.00 | 01-JAN-00:10 | 74291.26 | 28-JUN-16:00 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:20 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:20 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:20 |
WIRED_LTG_ELECTRICITY | 9.31 | 0.00 | 01-JAN-00:10 | 887.71 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 641.93 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 108.94 | 1156.00 | 03-JAN-17:10 | 49369.40 | 21-JAN-07:10 |
Gas:Plant | 73.70 | 1156.00 | 03-JAN-17:10 | 9403.44 | 03-FEB-12:20 |
WaterSystems:Gas | 73.70 | 1156.00 | 03-JAN-17:10 | 9403.44 | 03-FEB-12:20 |
Water Heater:WaterSystems:Gas | 73.70 | 1156.00 | 03-JAN-17:10 | 9403.44 | 03-FEB-12:20 |
Gas:HVAC | 35.24 | 0.00 | 01-JAN-00:10 | 48213.40 | 21-JAN-07:10 |
Heating:Gas | 35.24 | 0.00 | 01-JAN-00:10 | 48213.40 | 21-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 47.80 | 0.00 | 01-JAN-00:10 | 6176.57 | 03-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 47.80 | 0.00 | 01-JAN-00:10 | 6176.57 | 03-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 47.80 | 0.00 | 01-JAN-00:10 | 6176.57 | 03-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2379.46 | 0.00 | 01-JAN-00:10 | 382345.52 | 05-SEP-13:00 |
EnergyTransfer:Building | 1361.87 | 0.00 | 01-JAN-00:10 | 163357.04 | 28-JUN-16:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 326.40 | 0.00 | 01-JAN-00:10 | 31993.14 | 21-JUL-08:00 |
Heating:EnergyTransfer | 23.64 | 0.00 | 01-JAN-00:10 | 62985.75 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1338.23 | 0.00 | 01-JAN-00:10 | 163357.04 | 28-JUN-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 326.40 | 0.00 | 01-JAN-00:10 | 31993.14 | 21-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.00 | 0.00 | 01-JAN-00:10 | 9993.97 | 29-JUN-14:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.50 | 0.00 | 01-JAN-00:10 | 6351.03 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 40.50 | 0.00 | 01-JAN-00:10 | 9993.97 | 29-JUN-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.58 | 0.00 | 01-JAN-00:10 | 3988.36 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 2.85 | 0.00 | 01-JAN-00:10 | 2808.20 | 26-DEC-10:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.73 | 0.00 | 01-JAN-00:10 | 3988.36 | 07-AUG-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.65 | 0.00 | 01-JAN-00:10 | 4456.64 | 21-JUL-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.88 | 0.00 | 01-JAN-00:10 | 3090.92 | 06-FEB-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 31.76 | 0.00 | 01-JAN-00:10 | 4456.64 | 21-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 175.32 | 0.00 | 01-JAN-00:10 | 18034.20 | 24-JUL-10:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1486.93 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 175.32 | 0.00 | 01-JAN-00:10 | 18034.20 | 24-JUL-10:00 |
EnergyTransfer:Zone:CORE_TOP | 170.54 | 0.00 | 01-JAN-00:10 | 21053.25 | 24-JUL-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.29 | 0.00 | 01-JAN-00:10 | 11069.38 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 170.25 | 0.00 | 01-JAN-00:10 | 21053.25 | 24-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.79 | 0.00 | 01-JAN-00:10 | 7213.73 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.76 | 0.00 | 01-JAN-00:10 | 4920.59 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.02 | 0.00 | 01-JAN-00:10 | 7213.73 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.98 | 0.00 | 01-JAN-00:10 | 9125.75 | 05-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.86 | 0.00 | 01-JAN-00:10 | 4488.89 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.12 | 0.00 | 01-JAN-00:10 | 9125.75 | 05-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 64.11 | 0.00 | 01-JAN-00:10 | 10456.13 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.00 | 0.00 | 01-JAN-00:10 | 5182.00 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 63.10 | 0.00 | 01-JAN-00:10 | 10456.13 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.70 | 0.00 | 01-JAN-00:10 | 9964.39 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.10 | 0.00 | 01-JAN-00:10 | 4532.00 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.61 | 0.00 | 01-JAN-00:10 | 9964.39 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.56 | 0.00 | 01-JAN-00:10 | 5664.18 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.35 | 0.00 | 01-JAN-00:10 | 3477.82 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.21 | 0.00 | 01-JAN-00:10 | 5664.18 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 43.59 | 0.00 | 01-JAN-00:10 | 7421.64 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.13 | 0.00 | 01-JAN-00:10 | 1954.11 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 43.47 | 0.00 | 01-JAN-00:10 | 7421.64 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.69 | 0.00 | 01-JAN-00:10 | 10223.92 | 21-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 5.96 | 0.00 | 01-JAN-00:10 | 5662.94 | 22-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 49.73 | 0.00 | 01-JAN-00:10 | 10223.92 | 21-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 41.43 | 0.00 | 01-JAN-00:10 | 8002.58 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.14 | 0.00 | 01-JAN-00:10 | 1980.52 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 41.29 | 0.00 | 01-JAN-00:10 | 8002.58 | 21-JUL-17:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.85 | 0.00 | 01-JAN-00:10 | 6493.57 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.29 | 0.00 | 01-JAN-00:10 | 3646.02 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.56 | 0.00 | 01-JAN-00:10 | 6493.57 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 49.05 | 0.00 | 01-JAN-00:10 | 9032.14 | 05-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.17 | 0.00 | 01-JAN-00:10 | 2942.20 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.88 | 0.00 | 01-JAN-00:10 | 9032.14 | 05-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.87 | 0.00 | 01-JAN-00:10 | 9701.57 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.14 | 0.00 | 01-JAN-00:10 | 3280.11 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.72 | 0.00 | 01-JAN-00:10 | 9701.57 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.75 | 0.00 | 01-JAN-00:10 | 9501.72 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.21 | 0.00 | 01-JAN-00:10 | 2780.82 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.54 | 0.00 | 01-JAN-00:10 | 9501.72 | 28-JUN-16:00 |
EnergyTransfer:Plant | 47.80 | 0.00 | 01-JAN-00:10 | 6176.57 | 03-FEB-12:10 |
WaterSystems:EnergyTransfer | 47.80 | 0.00 | 01-JAN-00:10 | 6176.57 | 03-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 47.80 | 0.00 | 01-JAN-00:10 | 6176.57 | 03-FEB-12:10 |
EnergyTransfer:HVAC | 969.80 | 0.00 | 01-JAN-00:10 | 236878.46 | 05-SEP-13:00 |
HeatingCoils:EnergyTransfer | 59.39 | 0.00 | 01-JAN-00:10 | 107291.43 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 910.41 | 0.00 | 01-JAN-00:10 | 236878.46 | 05-SEP-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -326.399 | 0.000 | 0.000 | 32.828 | 71.912 | 291.987 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -70.329 |
CORE_MID | 0.000 | 0.000 | 0.002 | -175.322 | 0.000 | 0.000 | 33.049 | 71.912 | 126.597 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -56.239 |
CORE_TOP | 0.000 | 0.000 | 0.292 | -170.250 | 0.000 | 0.000 | 33.624 | 71.912 | 126.597 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -62.176 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.765 | -42.024 | 0.000 | 0.000 | 7.370 | 11.832 | 26.688 | 18.037 | 0.000 | 0.261 | 9.426 | 0.000 | -27.846 | 0.000 | -5.508 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.857 | -47.124 | 0.000 | 0.000 | 4.629 | 7.488 | 16.894 | 45.999 | 0.000 | 0.183 | 0.001 | 0.000 | -17.233 | 0.000 | -3.728 | -7.965 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.003 | -63.102 | 0.000 | 0.000 | 7.089 | 11.796 | 26.688 | 76.096 | 0.000 | 0.256 | 0.004 | 0.000 | -26.828 | 0.000 | -5.847 | -27.151 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.097 | -46.607 | 0.000 | 0.000 | 4.762 | 7.470 | 16.894 | 42.542 | 0.000 | 0.178 | 0.001 | 0.000 | -18.367 | 0.000 | -3.730 | -4.240 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.348 | -36.214 | 0.000 | 0.000 | 7.311 | 11.825 | 26.688 | 18.309 | 0.000 | 0.153 | 3.417 | 0.000 | -28.705 | 0.000 | -3.132 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.126 | -43.466 | 0.000 | 0.000 | 4.572 | 7.485 | 16.894 | 46.025 | 0.000 | 0.095 | 0.000 | 0.000 | -18.224 | 0.000 | -2.167 | -11.340 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 5.964 | -49.726 | 0.000 | 0.000 | 7.294 | 11.793 | 26.688 | 76.704 | 0.000 | 4.678 | 0.003 | 0.000 | -28.150 | 0.000 | -36.632 | -18.612 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.142 | -41.291 | 0.000 | 0.000 | 4.672 | 7.467 | 16.894 | 42.614 | 0.000 | 0.094 | 0.001 | 0.000 | -19.375 | 0.000 | -2.162 | -9.055 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.290 | -41.556 | 0.000 | 0.000 | 7.227 | 11.832 | 26.688 | 17.842 | 0.000 | 0.220 | 11.719 | 0.000 | -29.406 | 0.000 | -4.856 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.170 | -48.881 | 0.000 | 0.000 | 3.396 | 7.488 | 16.894 | 45.845 | 0.000 | 0.157 | 0.002 | 0.000 | -17.985 | 0.000 | -3.253 | -3.832 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.145 | -63.723 | 0.000 | 0.000 | 6.954 | 11.796 | 26.688 | 75.737 | 0.000 | 0.215 | 0.004 | 0.000 | -28.151 | 0.000 | -5.130 | -24.531 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.209 | -47.538 | 0.000 | 0.000 | 4.694 | 7.470 | 16.894 | 42.412 | 0.000 | 0.147 | 0.000 | 0.000 | -19.271 | 0.000 | -3.271 | -1.746 |
TOPFLOOR_PLENUM | 7.496 | -40.499 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.264 | 41.368 | 0.000 | 0.000 | 0.000 | -8.629 | -0.001 |
MIDFLOOR_PLENUM | 2.848 | -22.727 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.315 | 28.044 | 0.000 | 0.000 | 0.000 | -8.479 | 0.000 |
FIRSTFLOOR_PLENUM | 0.883 | -31.763 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.256 | 37.381 | 0.000 | 0.000 | 0.000 | -6.756 | 0.000 |
Total Facility | 11.227 | -94.990 | 12.410 | -1243.223 | 0.000 | 0.000 | 169.471 | 331.480 | 806.674 | 548.163 | 0.000 | 7.472 | 131.370 | 0.000 | -279.541 | 0.000 | -103.281 | -297.218 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 21-JUL-04:01 | 0.00 | 0.00 | 0.00 | -51710.69 | 0.00 | 0.00 | 0.00 | 781.30 | 3174.86 | 0.00 | 0.00 | 0.00 | 47754.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-AUG-04:01 | 0.00 | 0.00 | 0.00 | -31833.36 | 0.00 | 0.00 | 0.00 | 781.30 | 3174.86 | 0.00 | 0.00 | 0.00 | 27877.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-AUG-04:01 | 0.00 | 0.00 | 0.00 | -33669.70 | 0.00 | 0.00 | 0.00 | 781.30 | 3174.86 | 0.00 | 0.00 | 0.00 | 29713.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -9311.25 | 0.00 | 0.00 | 0.00 | 60.24 | 501.96 | 2483.70 | 0.00 | 549.58 | 5715.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 20-AUG-08:12 | 0.00 | 0.00 | 0.00 | -12598.51 | 0.00 | 0.00 | 12.81 | 33.83 | 317.77 | 12323.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11.50 | -78.36 |
PERIMETER_TOP_ZN_1 | 01-OCT-11:12 | 0.00 | 0.00 | 0.00 | -12632.39 | 0.00 | 0.00 | 23.88 | 53.43 | 501.96 | 15780.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -41.60 | -3685.38 |
PERIMETER_TOP_ZN_4 | 30-JUL-16:11 | 0.00 | 0.00 | 0.00 | -15219.68 | 0.00 | 0.00 | 12.33 | 33.82 | 317.76 | 11691.79 | 0.00 | 110.64 | 3053.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | -5663.26 | 0.00 | 0.00 | 737.25 | 961.76 | 1505.89 | 4169.58 | 0.00 | 91.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1802.66 |
PERIMETER_BOT_ZN_2 | 20-AUG-08:61 | 0.00 | 0.00 | 0.00 | -11060.95 | 0.00 | 0.00 | 15.16 | 33.83 | 317.77 | 12582.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4.01 | -1884.14 |
PERIMETER_BOT_ZN_1 | 01-OCT-13:01 | 0.00 | 0.00 | 0.00 | -10794.84 | 0.00 | 0.00 | 24.41 | 53.43 | 501.96 | 13942.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5.24 | -3722.31 |
PERIMETER_BOT_ZN_4 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 | -11831.26 | 0.00 | 0.00 | 0.00 | 38.14 | 317.76 | 6073.79 | 0.00 | 46.20 | 5355.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-04:01 | 0.00 | 0.00 | 0.00 | -7581.19 | 0.00 | 0.00 | 0.00 | 164.70 | 669.29 | 0.00 | 0.00 | 0.00 | 7359.31 | 0.00 | -547.40 | 0.00 | -64.71 | 0.00 |
PERIMETER_MID_ZN_2 | 20-AUG-08:61 | 0.00 | 0.00 | 0.00 | -13898.55 | 0.00 | 0.00 | 12.63 | 33.83 | 317.77 | 12488.87 | 0.00 | 0.00 | 1053.46 | 0.00 | -0.00 | 0.00 | -8.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:21 | 0.00 | 0.00 | 0.00 | -11817.84 | 0.00 | 0.00 | 22.26 | 53.43 | 501.96 | 15070.80 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.58 | -3807.04 |
PERIMETER_MID_ZN_4 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 | -14297.69 | 0.00 | 0.00 | 0.00 | 38.14 | 317.76 | 12855.13 | 0.00 | 0.00 | 1095.70 | 0.00 | -0.00 | 0.00 | -9.04 | 0.00 |
TOPFLOOR_PLENUM | 29-JUN-14:30 | 0.00 | -9992.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.48 | 9799.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-16:00 | 0.00 | -3988.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 | 3881.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 21-JUL-16:00 | 0.00 | -4455.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.25 | 4359.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-04:01 | 0.00 | 8996.83 | 0.00 | -185475.91 | 0.00 | 0.00 | 0.00 | 3957.73 | 16082.40 | 0.00 | 0.00 | 0.00 | 162834.19 | 0.00 | -5477.10 | 0.00 | -918.14 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-07:01 | 0.00 | 0.00 | 14869.27 | -0.00 | 0.00 | 0.00 | 886.28 | 2078.80 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21009.22 |
CORE_TOP | 06-FEB-06:01 | 0.00 | 0.00 | 16998.45 | -0.00 | 0.00 | 0.00 | 487.88 | 692.93 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21354.13 |
PERIMETER_TOP_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 5568.10 | -0.00 | 0.00 | 0.00 | 0.00 | 164.70 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2413.13 | 0.00 | -1155.17 | -2833.79 |
PERIMETER_TOP_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 6150.11 | -0.00 | 0.00 | 0.00 | 0.00 | 104.27 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1605.44 | 0.00 | -777.54 | -4295.09 |
PERIMETER_TOP_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 5904.07 | -0.00 | 0.00 | 0.00 | 0.00 | 164.70 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2152.74 | 0.00 | -1253.95 | -3331.36 |
PERIMETER_TOP_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 6801.69 | -0.00 | 0.00 | 0.00 | 0.00 | 104.26 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1614.46 | 0.00 | -784.35 | -4930.83 |
PERIMETER_BOT_ZN_3 | 06-FEB-06:01 | 0.00 | 0.00 | 4108.39 | -0.00 | 0.00 | 0.00 | 104.44 | 146.08 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2685.85 | 0.00 | -146.53 | -2195.80 |
PERIMETER_BOT_ZN_2 | 06-FEB-06:01 | 0.00 | 0.00 | 4536.88 | -0.00 | 0.00 | 0.00 | 65.29 | 92.48 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1815.78 | 0.00 | -99.40 | -3203.15 |
PERIMETER_BOT_ZN_1 | 18-JAN-07:10 | 0.00 | 0.00 | 5988.38 | -0.00 | 0.00 | 0.00 | 193.30 | 438.23 | 669.28 | 0.00 | 0.00 | 0.00 | 11875.85 | 0.00 | -2443.70 | 0.00 | -16721.35 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-06:01 | 0.00 | 0.00 | 4816.31 | -0.00 | 0.00 | 0.00 | 64.95 | 92.47 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1826.33 | 0.00 | -100.11 | -3470.98 |
PERIMETER_MID_ZN_3 | 17-JAN-06:01 | 0.00 | 0.00 | 4390.36 | -0.00 | 0.00 | 0.00 | 105.60 | 146.08 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2484.44 | 0.00 | -286.63 | -2540.24 |
PERIMETER_MID_ZN_2 | 17-JAN-06:01 | 0.00 | 0.00 | 5552.85 | -0.00 | 0.00 | 0.00 | 67.21 | 92.48 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1644.69 | 0.00 | -192.23 | -4299.30 |
PERIMETER_MID_ZN_1 | 17-JAN-06:01 | 0.00 | 0.00 | 4718.38 | -0.00 | 0.00 | 0.00 | 104.58 | 146.08 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2432.97 | 0.00 | -290.52 | -2914.82 |
PERIMETER_MID_ZN_4 | 17-JAN-06:01 | 0.00 | 0.00 | 5755.22 | -0.00 | 0.00 | 0.00 | 67.00 | 92.47 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1599.39 | 0.00 | -193.19 | -4545.80 |
TOPFLOOR_PLENUM | 06-FEB-06:07 | 6814.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -379.29 | -6435.57 |
MIDFLOOR_PLENUM | 22-JAN-14:32 | 4232.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.34 | -4053.39 |
FIRSTFLOOR_PLENUM | 23-OCT-05:02 | 5341.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -99.43 | -5241.67 |
Total Facility | 06-FEB-07:01 | -2101.66 | 8245.48 | 86560.99 | -8245.48 | 0.00 | 0.00 | 4537.29 | 9759.07 | 27364.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20208.97 | 0.00 | -30722.07 | -75189.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.1597 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 6.5939 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6710 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 4.9634 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.0223 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 5.5972 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.1479 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.1479 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 1.7216 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 1.7216 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 1.8172 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 1.8172 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3386 | 4.3386 | 1.3016 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5356 | 2.5356 | 0.7810 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6412 | 2.6412 | 0.8029 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7629 | 0.7629 | 0.2289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8494 | 0.8494 | 0.2548 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8224 | 0.8224 | 0.2467 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9464 | 0.9464 | 0.2839 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6352 | 0.6352 | 0.1906 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7204 | 0.7204 | 0.2161 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6946 | 0.6946 | 0.2084 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7709 | 0.7709 | 0.2313 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6690 | 0.6690 | 0.2007 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8512 | 0.8512 | 0.2553 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7287 | 0.7287 | 0.2186 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8866 | 0.8866 | 0.2660 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.1597 | 6.5939 | 7.1597 | 2.1479 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6710 | 4.9634 | 5.6710 | 1.7216 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.0223 | 5.5972 | 6.0223 | 1.8172 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3016 | 1.3016 | 1.3016 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7810 | 0.7810 | 0.7810 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8029 | 0.8029 | 0.8029 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2289 | 0.2289 | 0.2289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2548 | 0.2548 | 0.2548 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2467 | 0.2467 | 0.2467 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2839 | 0.2839 | 0.2839 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1906 | 0.1906 | 0.1906 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2161 | 0.2161 | 0.2161 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2084 | 0.2084 | 0.2084 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2313 | 0.2313 | 0.2313 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2007 | 0.2007 | 0.2007 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2553 | 0.2553 | 0.2553 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2186 | 0.2186 | 0.2186 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2660 | 0.2660 | 0.2660 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.1479 | 2.1479 | 2.1479 | 2.1479 | 0.0000 | 1.0000 |
PACU_VAV_MID | 1.7216 | 1.7216 | 1.7216 | 1.7216 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 1.8172 | 1.8172 | 1.8172 | 1.8172 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:41:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 254.33 |
Number of hours cooling loads not met | 511.33 |
Number of hours not met | 762.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 31.19 | 72843.53 | 35.24 | 48213.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 234.56 | 74291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 331.48 | 31591.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 101.91 | 7792.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.28 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 164.75 | 22155.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 18.87 | 1349.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 104.10 | 17589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 73.70 | 9403.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 806.67 | 1628.81 |
Natural Gas | 0.00 | 108.94 |
Additional | 0.00 | 0.00 |
Total | 806.67 | 1737.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 66.53 |
Space Heating | 6.26 |
Space Cooling | 47.08 |
Fans (All) | 20.90 |
Service Water Heating | 0.00 |
Receptacle Equipment | 161.91 |
Miscellaneous (All) | 326.93 |
Subtotal | 326.93 |
Natural Gas [MJ/m2] | |
Space Heating | 7.07 |
Service Water Heating | 14.79 |
Miscellaneous (All) | 21.87 |
Subtotal | 21.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.08 |
Space Heating | 3.82 |
Space Cooling | 13.50 |
Fans (All) | 5.99 |
Service Water Heating | 4.24 |
Receptacle Equipment | 46.42 |
Miscellaneous | 6.95 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2624. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 1470. | 4212. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.118279E+11 |
February | 0.000 | 0.675911E+10 |
March | 0.000 | 0.170153E+10 |
April | 0.000 | 0.262727E+09 |
May | 0.000 | 0.146813E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.104677E+10 |
November | 0.000 | 0.238683E+10 |
December | 0.000 | 0.112442E+11 |
Annual Sum or Average | 0.352437E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.118279E+11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205117E+11 | 26698.54 | 26-JAN-08:02 | -5.3 | -7.8 | 0.196644E+10 | 2606.63 | 10-JAN-10:20 | 1.87 | -1.6 |
February | 0.195738E+11 | 27330.80 | 01-FEB-08:03 | -4.0 | -5.7 | 0.178935E+10 | 2606.67 | 15-FEB-10:09 | 11.38 | 5.31 |
March | 0.251342E+11 | 26184.19 | 31-MAR-08:00 | 7.80 | 3.06 | 0.214546E+10 | 2606.65 | 02-MAR-14:09 | 7.88 | 3.37 |
April | 0.258641E+11 | 37786.55 | 14-APR-05:02 | 8.58 | 2.06 | 0.190842E+10 | 2606.66 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.296853E+11 | 43269.10 | 31-MAY-05:02 | 15.28 | 9.15 | 0.206752E+10 | 2606.79 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.323393E+11 | 51111.47 | 29-JUN-04:01 | 24.40 | 15.15 | 0.206160E+10 | 2606.68 | 08-JUN-13:09 | 16.52 | 13.77 |
July | 0.324801E+11 | 51700.63 | 21-JUL-04:01 | 20.92 | 12.26 | 0.191361E+10 | 2606.62 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.349329E+11 | 51529.23 | 18-AUG-04:01 | 20.92 | 13.63 | 0.215115E+10 | 2606.78 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.308570E+11 | 44908.81 | 23-SEP-05:02 | 16.10 | 13.27 | 0.191019E+10 | 2606.68 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.292215E+11 | 38592.13 | 24-OCT-05:02 | 10.60 | 6.21 | 0.198547E+10 | 2606.71 | 24-OCT-13:39 | 10.53 | 5.30 |
November | 0.247776E+11 | 38219.61 | 02-NOV-05:02 | 7.12 | 4.63 | 0.196478E+10 | 2606.62 | 27-NOV-10:20 | 1.47 | -2.8 |
December | 0.210234E+11 | 27518.61 | 07-DEC-08:02 | -2.9 | -4.6 | 0.190173E+10 | 2609.68 | 22-DEC-10:09 | -2.9 | -5.3 |
Annual Sum or Average | 0.326401E+12 | 0.237657E+11 | ||||||||
Minimum of Months | 0.195738E+11 | 26184.19 | -5.3 | -7.8 | 0.178935E+10 | 2606.62 | -2.9 | -5.3 | ||
Maximum of Months | 0.349329E+11 | 51700.63 | 24.40 | 15.15 | 0.215115E+10 | 2609.68 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532976E+09 | 2277.94 | 01-JAN-14:00 | 15.60 | 5.62 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.913392E+09 | 3976.04 | 15-FEB-15:40 | 17.20 | 6.53 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.187133E+10 | 4618.72 | 08-MAR-13:50 | 22.33 | 9.53 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.331185E+10 | 6910.11 | 28-APR-14:20 | 24.60 | 10.30 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.440876E+10 | 8234.91 | 30-MAY-14:30 | 27.20 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.643742E+10 | 9993.97 | 29-JUN-14:30 | 37.25 | 15.76 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.720899E+10 | 9849.56 | 21-JUL-14:50 | 37.80 | 15.26 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.689443E+10 | 9828.69 | 07-AUG-14:10 | 33.22 | 15.83 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.479430E+10 | 8003.59 | 12-SEP-14:30 | 29.15 | 14.67 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.280245E+10 | 6820.89 | 05-OCT-15:00 | 26.70 | 12.34 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.983667E+09 | 3693.41 | 02-NOV-15:10 | 17.12 | 9.37 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.340635E+09 | 2181.78 | 31-DEC-14:38 | 10.73 | 1.99 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.405002E+11 | 0.00 | ||||||||
Minimum of Months | 0.340635E+09 | 2181.78 | 10.73 | 1.99 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.720899E+10 | 9993.97 | 37.80 | 15.83 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363237E+09 | 1364.82 | 28-JAN-06:17 | -2.8 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.460892E+09 | 1526.02 | 11-FEB-06:17 | -3.9 | -4.8 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.884303E+09 | 1602.51 | 18-MAR-05:17 | 0.93 | 0.21 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.166084E+10 | 2357.11 | 28-APR-15:20 | 25.00 | 10.38 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.236117E+10 | 2889.42 | 15-MAY-16:00 | 28.90 | 11.31 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.341412E+10 | 3936.67 | 26-JUN-16:00 | 34.40 | 15.93 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.385411E+10 | 3960.32 | 05-JUL-16:00 | 32.80 | 16.74 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.387600E+10 | 3988.36 | 07-AUG-16:00 | 33.30 | 16.18 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.288301E+10 | 3358.59 | 05-SEP-14:10 | 24.40 | 17.89 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.184262E+10 | 3323.60 | 02-OCT-15:30 | 25.55 | 15.03 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.775518E+09 | 1838.30 | 01-NOV-16:10 | 10.40 | 6.15 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.351879E+09 | 1399.96 | 30-DEC-06:17 | -2.1 | -4.7 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.227277E+11 | 0.00 | ||||||||
Minimum of Months | 0.351879E+09 | 1364.82 | -3.9 | -5.5 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.387600E+10 | 3988.36 | 34.40 | 17.89 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803511E+09 | 2035.90 | 06-JAN-18:01 | 2.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.969365E+09 | 2311.58 | 15-FEB-17:10 | 16.05 | 5.51 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.165463E+10 | 2198.45 | 18-MAR-05:17 | 0.93 | 0.21 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.240804E+10 | 2865.16 | 28-APR-15:50 | 25.00 | 10.38 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.309452E+10 | 3485.98 | 29-MAY-11:44 | 23.72 | 13.38 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.410563E+10 | 4433.41 | 29-JUN-15:10 | 37.43 | 15.86 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.457164E+10 | 4456.64 | 21-JUL-16:00 | 37.20 | 14.96 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.475062E+10 | 4389.64 | 18-AUG-16:00 | 33.30 | 17.37 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.385564E+10 | 3996.23 | 01-SEP-15:50 | 28.40 | 16.07 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.297024E+10 | 3963.79 | 06-OCT-16:00 | 27.80 | 12.26 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.172755E+10 | 3179.98 | 01-NOV-16:09 | 10.40 | 6.15 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.852322E+09 | 2031.60 | 14-DEC-18:01 | -0.7 | -6.0 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.317637E+11 | 0.00 | ||||||||
Minimum of Months | 0.803511E+09 | 2031.60 | -0.7 | -6.0 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.475062E+10 | 4456.64 | 37.43 | 17.37 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.898522E+10 | 11183.32 | 26-JAN-17:00 | 10.00 | 1.18 | 0.188567E+10 | 2606.61 | 06-JAN-10:50 | 1.83 | -1.4 |
February | 0.874499E+10 | 13483.97 | 15-FEB-17:00 | 16.70 | 5.82 | 0.174448E+10 | 2607.44 | 24-FEB-10:39 | 3.87 | 1.08 |
March | 0.121766E+11 | 12674.27 | 31-MAR-16:00 | 15.00 | 4.86 | 0.212555E+10 | 2606.62 | 02-MAR-14:09 | 7.88 | 3.37 |
April | 0.141482E+11 | 24041.36 | 28-APR-05:03 | 11.93 | 4.33 | 0.190353E+10 | 2606.61 | 26-APR-13:20 | 24.80 | 9.87 |
May | 0.169673E+11 | 29252.46 | 22-MAY-04:02 | 17.62 | 11.87 | 0.206708E+10 | 2606.73 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.194760E+11 | 31702.40 | 28-JUN-04:01 | 20.73 | 12.13 | 0.206432E+10 | 2606.64 | 08-JUN-13:09 | 16.52 | 13.77 |
July | 0.201243E+11 | 31789.31 | 06-JUL-04:01 | 20.50 | 13.12 | 0.191911E+10 | 2606.61 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.210927E+11 | 31830.92 | 10-AUG-04:01 | 21.70 | 14.52 | 0.215564E+10 | 2606.71 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.177359E+11 | 30453.47 | 05-SEP-04:02 | 17.52 | 15.19 | 0.191223E+10 | 2606.65 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.154197E+11 | 29442.47 | 02-OCT-04:02 | 17.70 | 12.87 | 0.198035E+10 | 2606.64 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.115164E+11 | 20598.45 | 01-NOV-05:02 | 7.70 | 5.59 | 0.194594E+10 | 2606.62 | 20-NOV-10:20 | 8.87 | 1.86 |
December | 0.893557E+10 | 11399.69 | 01-DEC-16:30 | 12.50 | 4.55 | 0.184099E+10 | 2606.62 | 21-DEC-10:20 | -2.8 | -4.7 |
Annual Sum or Average | 0.175323E+12 | 0.235449E+11 | ||||||||
Minimum of Months | 0.874499E+10 | 11183.32 | 7.70 | 1.18 | 0.174448E+10 | 2606.61 | -2.8 | -4.7 | ||
Maximum of Months | 0.210927E+11 | 31830.92 | 21.70 | 15.19 | 0.215564E+10 | 2607.44 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.760463E+10 | 9145.02 | 26-JAN-16:50 | 10.10 | 1.25 | 0.175168E+10 | 2606.58 | 06-JAN-14:00 | 10.60 | 3.55 |
February | 0.768192E+10 | 13245.12 | 15-FEB-17:00 | 16.70 | 5.82 | 0.164884E+10 | 2606.57 | 09-FEB-14:30 | 12.25 | 4.27 |
March | 0.110441E+11 | 13046.43 | 08-MAR-17:00 | 22.20 | 8.23 | 0.206339E+10 | 2606.61 | 02-MAR-14:09 | 7.88 | 3.37 |
April | 0.137495E+11 | 17502.25 | 28-APR-15:00 | 25.00 | 10.39 | 0.188578E+10 | 2606.61 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.171951E+11 | 29126.31 | 22-MAY-05:02 | 16.78 | 12.19 | 0.205760E+10 | 2606.71 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.205678E+11 | 32984.70 | 29-JUN-04:01 | 24.40 | 15.15 | 0.206093E+10 | 2606.65 | 08-JUN-13:09 | 16.52 | 13.77 |
July | 0.217404E+11 | 33493.77 | 05-JUL-04:01 | 22.20 | 13.91 | 0.191869E+10 | 2606.63 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.222047E+11 | 33665.74 | 21-AUG-04:01 | 21.70 | 15.51 | 0.215386E+10 | 2606.72 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.176248E+11 | 31088.04 | 05-SEP-04:02 | 17.52 | 15.19 | 0.190378E+10 | 2606.63 | 13-SEP-13:39 | 26.67 | 14.53 |
October | 0.138781E+11 | 29412.66 | 02-OCT-05:02 | 17.12 | 12.74 | 0.194786E+10 | 2606.62 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.954201E+10 | 14727.57 | 01-NOV-15:50 | 10.97 | 6.45 | 0.187487E+10 | 2606.61 | 01-NOV-09:09 | 10.47 | 6.67 |
December | 0.741886E+10 | 9165.54 | 01-DEC-16:20 | 12.60 | 4.66 | 0.170274E+10 | 2606.50 | 01-DEC-14:09 | 11.78 | 4.39 |
Annual Sum or Average | 0.170252E+12 | 0.229700E+11 | ||||||||
Minimum of Months | 0.741886E+10 | 9145.02 | 10.10 | 1.25 | 0.164884E+10 | 2606.50 | 7.88 | 3.37 | ||
Maximum of Months | 0.222047E+11 | 33665.74 | 25.00 | 15.51 | 0.215386E+10 | 2606.72 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109556E+10 | 2023.27 | 05-JAN-16:00 | 16.10 | 6.82 | 0.323776E+09 | 492.11 | 27-JAN-14:00 | 11.70 | 2.30 |
February | 0.134295E+10 | 2489.09 | 14-FEB-16:40 | 21.47 | 7.41 | 0.304850E+09 | 539.75 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.241566E+10 | 2782.43 | 16-MAR-15:00 | 20.00 | 8.44 | 0.396047E+09 | 549.48 | 17-MAR-13:00 | 16.10 | 5.39 |
April | 0.331063E+10 | 4940.29 | 28-APR-15:30 | 25.00 | 10.38 | 0.381647E+09 | 549.49 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.438769E+10 | 5540.23 | 31-MAY-15:20 | 27.57 | 10.98 | 0.425828E+09 | 549.50 | 31-MAY-13:30 | 26.95 | 11.56 |
June | 0.596068E+10 | 7213.73 | 29-JUN-15:00 | 37.80 | 15.66 | 0.432293E+09 | 549.50 | 23-JUN-09:30 | 26.10 | 13.89 |
July | 0.654413E+10 | 9310.91 | 04-JUL-17:01 | 35.73 | 14.59 | 0.403790E+09 | 549.49 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.636155E+10 | 6820.89 | 07-AUG-14:40 | 32.97 | 15.68 | 0.452245E+09 | 549.52 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.459384E+10 | 5610.42 | 12-SEP-14:30 | 29.15 | 14.67 | 0.395354E+09 | 549.51 | 13-SEP-13:39 | 26.67 | 14.53 |
October | 0.316437E+10 | 5150.75 | 02-OCT-13:40 | 26.33 | 15.34 | 0.385169E+09 | 549.49 | 06-OCT-13:39 | 26.33 | 12.72 |
November | 0.188790E+10 | 2357.24 | 02-NOV-15:40 | 16.87 | 9.61 | 0.350732E+09 | 548.83 | 03-NOV-13:00 | 12.20 | 2.39 |
December | 0.960020E+09 | 1873.26 | 01-DEC-16:00 | 12.80 | 4.90 | 0.308304E+09 | 500.70 | 01-DEC-14:00 | 12.20 | 4.60 |
Annual Sum or Average | 0.420250E+11 | 0.456003E+10 | ||||||||
Minimum of Months | 0.960020E+09 | 1873.26 | 12.80 | 4.90 | 0.304850E+09 | 492.11 | 11.70 | 2.30 | ||
Maximum of Months | 0.654413E+10 | 9310.91 | 37.80 | 15.68 | 0.452245E+09 | 549.52 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133683E+10 | 2118.66 | 05-JAN-15:50 | 16.10 | 6.82 | 0.208174E+09 | 331.51 | 27-JAN-10:09 | 3.35 | -1.8 |
February | 0.163483E+10 | 3674.04 | 14-FEB-09:20 | 7.80 | 2.16 | 0.198180E+09 | 347.87 | 10-FEB-10:09 | 6.15 | 1.44 |
March | 0.293848E+10 | 4855.81 | 31-MAR-08:30 | 8.60 | 3.36 | 0.257995E+09 | 347.88 | 10-MAR-10:09 | 6.97 | 1.33 |
April | 0.423050E+10 | 11242.72 | 30-APR-08:32 | 15.40 | 4.93 | 0.250082E+09 | 347.88 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.511589E+10 | 12278.69 | 14-MAY-09:12 | 21.67 | 10.02 | 0.270971E+09 | 347.89 | 23-MAY-09:09 | 23.07 | 13.47 |
June | 0.646156E+10 | 12348.34 | 18-JUN-08:32 | 24.67 | 11.79 | 0.273521E+09 | 347.89 | 13-JUN-09:09 | 25.97 | 12.36 |
July | 0.668654E+10 | 12592.75 | 04-JUL-08:22 | 25.55 | 18.33 | 0.255299E+09 | 347.88 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.662183E+10 | 12596.96 | 20-AUG-08:12 | 24.97 | 14.89 | 0.286019E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.503048E+10 | 12348.41 | 03-SEP-09:52 | 27.80 | 16.07 | 0.250819E+09 | 347.89 | 13-SEP-13:39 | 26.67 | 14.53 |
October | 0.363057E+10 | 6380.18 | 02-OCT-08:20 | 19.80 | 13.60 | 0.248552E+09 | 347.88 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.215097E+10 | 4678.85 | 01-NOV-08:50 | 9.63 | 6.29 | 0.226667E+09 | 347.87 | 01-NOV-09:09 | 10.47 | 6.67 |
December | 0.128559E+10 | 2034.23 | 29-DEC-09:20 | 1.67 | -0.8 | 0.198135E+09 | 325.16 | 29-DEC-09:30 | 1.95 | -0.6 |
Annual Sum or Average | 0.471241E+11 | 0.292441E+10 | ||||||||
Minimum of Months | 0.128559E+10 | 2034.23 | 1.67 | -0.8 | 0.198135E+09 | 325.16 | 1.95 | -1.8 | ||
Maximum of Months | 0.668654E+10 | 12596.96 | 27.80 | 18.33 | 0.286019E+09 | 347.89 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377736E+10 | 9671.34 | 15-JAN-14:43 | 12.12 | 3.52 | 0.383871E+09 | 634.29 | 26-JAN-14:09 | 10.10 | 1.47 |
February | 0.378606E+10 | 9980.45 | 12-FEB-12:23 | 13.90 | 4.63 | 0.353242E+09 | 605.73 | 10-FEB-14:09 | 13.90 | 5.02 |
March | 0.411491E+10 | 8540.93 | 08-MAR-13:20 | 20.93 | 9.12 | 0.418417E+09 | 549.83 | 24-MAR-13:20 | 17.57 | 6.05 |
April | 0.422343E+10 | 6834.76 | 27-APR-13:30 | 23.60 | 9.33 | 0.384280E+09 | 549.50 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.474002E+10 | 6127.09 | 31-MAY-14:20 | 27.93 | 11.36 | 0.424358E+09 | 549.50 | 31-MAY-13:30 | 26.95 | 11.56 |
June | 0.612188E+10 | 7731.01 | 29-JUN-14:40 | 37.43 | 15.73 | 0.430765E+09 | 549.49 | 23-JUN-09:30 | 26.10 | 13.89 |
July | 0.684648E+10 | 10832.46 | 30-JUL-16:11 | 33.33 | 17.36 | 0.403189E+09 | 549.49 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.723084E+10 | 9096.45 | 31-AUG-12:40 | 28.87 | 15.83 | 0.451881E+09 | 549.52 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.663954E+10 | 10945.51 | 03-SEP-13:13 | 31.67 | 16.73 | 0.398361E+09 | 621.77 | 28-SEP-13:30 | 29.45 | 15.24 |
October | 0.646879E+10 | 12634.80 | 01-OCT-11:12 | 24.47 | 13.93 | 0.408917E+09 | 627.52 | 31-OCT-13:09 | 20.47 | 8.40 |
November | 0.494499E+10 | 10372.74 | 19-NOV-14:02 | 13.58 | 3.40 | 0.405164E+09 | 655.52 | 01-NOV-13:20 | 12.93 | 7.55 |
December | 0.420937E+10 | 10232.77 | 31-DEC-14:32 | 10.73 | 1.99 | 0.379517E+09 | 629.89 | 29-DEC-14:09 | 10.68 | 3.51 |
Annual Sum or Average | 0.631037E+11 | 0.484196E+10 | ||||||||
Minimum of Months | 0.377736E+10 | 6127.09 | 10.73 | 1.99 | 0.353242E+09 | 549.49 | 10.10 | 1.47 | ||
Maximum of Months | 0.723084E+10 | 12634.80 | 37.43 | 17.36 | 0.451881E+09 | 655.52 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136736E+10 | 4425.57 | 26-JAN-16:30 | 10.30 | 1.37 | 0.207792E+09 | 338.69 | 13-JAN-16:49 | 8.13 | 1.98 |
February | 0.178088E+10 | 6565.99 | 15-FEB-16:30 | 16.95 | 6.15 | 0.193764E+09 | 347.82 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.302233E+10 | 9117.50 | 12-MAR-16:32 | 20.20 | 6.25 | 0.237590E+09 | 347.82 | 10-MAR-14:00 | 13.30 | 3.25 |
April | 0.410821E+10 | 12083.23 | 16-APR-16:32 | 20.20 | 7.99 | 0.227106E+09 | 347.84 | 14-APR-13:00 | 23.30 | 10.23 |
May | 0.502375E+10 | 13433.08 | 20-MAY-17:42 | 26.70 | 10.86 | 0.252208E+09 | 347.85 | 31-MAY-13:39 | 27.40 | 11.57 |
June | 0.608423E+10 | 14487.31 | 25-JUN-16:41 | 33.68 | 14.44 | 0.262432E+09 | 347.85 | 13-JUN-13:09 | 31.38 | 15.22 |
July | 0.633634E+10 | 15219.52 | 30-JUL-16:11 | 33.33 | 17.36 | 0.248140E+09 | 347.84 | 05-JUL-09:00 | 29.40 | 16.78 |
August | 0.635248E+10 | 14286.68 | 20-AUG-17:31 | 34.40 | 15.38 | 0.275806E+09 | 347.87 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.507659E+10 | 12889.78 | 02-SEP-17:04 | 30.92 | 15.51 | 0.236333E+09 | 347.86 | 13-SEP-13:39 | 26.67 | 14.53 |
October | 0.390544E+10 | 12307.82 | 09-OCT-16:12 | 23.53 | 12.53 | 0.230822E+09 | 347.84 | 02-OCT-13:30 | 26.15 | 15.28 |
November | 0.229362E+10 | 5758.95 | 02-NOV-16:00 | 16.70 | 9.77 | 0.217382E+09 | 347.82 | 14-NOV-14:00 | 12.20 | 4.09 |
December | 0.125662E+10 | 3499.50 | 29-DEC-16:10 | 11.42 | 3.72 | 0.201107E+09 | 338.68 | 13-DEC-16:40 | 7.77 | 0.45 |
Annual Sum or Average | 0.466078E+11 | 0.279048E+10 | ||||||||
Minimum of Months | 0.125662E+10 | 3499.50 | 10.30 | 1.37 | 0.193764E+09 | 338.68 | 7.77 | 0.45 | ||
Maximum of Months | 0.635248E+10 | 15219.52 | 34.40 | 17.36 | 0.275806E+09 | 347.87 | 31.38 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120652E+10 | 1642.43 | 05-JAN-16:00 | 16.10 | 6.82 | 0.329067E+09 | 483.58 | 27-JAN-14:00 | 11.70 | 2.30 |
February | 0.121902E+10 | 1931.33 | 14-FEB-16:50 | 21.28 | 7.31 | 0.304824E+09 | 506.75 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.195346E+10 | 1974.64 | 16-MAR-14:40 | 20.20 | 8.57 | 0.387902E+09 | 525.37 | 17-MAR-13:00 | 16.10 | 5.39 |
April | 0.241023E+10 | 3193.05 | 14-APR-14:30 | 23.60 | 10.42 | 0.376267E+09 | 549.47 | 26-APR-13:20 | 24.80 | 9.87 |
May | 0.314712E+10 | 3875.26 | 31-MAY-16:00 | 28.30 | 11.02 | 0.425538E+09 | 549.49 | 01-MAY-13:00 | 10.60 | 5.34 |
June | 0.464714E+10 | 5664.18 | 29-JUN-15:00 | 37.80 | 15.66 | 0.432932E+09 | 549.49 | 08-JUN-09:09 | 17.85 | 14.46 |
July | 0.539471E+10 | 5462.99 | 25-JUL-15:30 | 33.30 | 16.77 | 0.404113E+09 | 549.49 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.555540E+10 | 5576.69 | 07-AUG-14:40 | 32.97 | 15.68 | 0.453750E+09 | 549.52 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.428743E+10 | 4802.12 | 05-SEP-13:40 | 24.23 | 18.03 | 0.401615E+09 | 549.49 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.311240E+10 | 4492.33 | 02-OCT-13:50 | 26.52 | 15.41 | 0.405074E+09 | 549.49 | 12-OCT-09:09 | 5.37 | 2.69 |
November | 0.197238E+10 | 2331.73 | 02-NOV-15:40 | 16.87 | 9.61 | 0.375778E+09 | 549.48 | 03-NOV-13:00 | 12.20 | 2.39 |
December | 0.130872E+10 | 1641.79 | 01-DEC-16:00 | 12.80 | 4.90 | 0.322642E+09 | 523.76 | 01-DEC-14:00 | 12.20 | 4.60 |
Annual Sum or Average | 0.362145E+11 | 0.461950E+10 | ||||||||
Minimum of Months | 0.120652E+10 | 1641.79 | 12.80 | 4.90 | 0.304824E+09 | 483.58 | 5.37 | 2.30 | ||
Maximum of Months | 0.555540E+10 | 5664.18 | 37.80 | 18.03 | 0.453750E+09 | 549.52 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150790E+10 | 1808.27 | 05-JAN-14:10 | 16.10 | 6.82 | 0.213654E+09 | 330.02 | 27-JAN-09:09 | 0.97 | -3.3 |
February | 0.155679E+10 | 2666.57 | 14-FEB-08:30 | 5.00 | 0.50 | 0.199613E+09 | 347.87 | 14-FEB-10:09 | 10.83 | 3.57 |
March | 0.245751E+10 | 3539.40 | 31-MAR-08:70 | 8.07 | 3.17 | 0.257850E+09 | 347.88 | 10-MAR-10:09 | 6.97 | 1.33 |
April | 0.341527E+10 | 9091.47 | 30-APR-07:42 | 14.63 | 5.05 | 0.251111E+09 | 347.87 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.417063E+10 | 9597.25 | 29-MAY-08:42 | 17.93 | 12.71 | 0.273153E+09 | 347.88 | 23-MAY-09:09 | 23.07 | 13.47 |
June | 0.559586E+10 | 8276.23 | 18-JUN-08:32 | 24.67 | 11.79 | 0.274907E+09 | 347.89 | 12-JUN-09:00 | 25.00 | 13.26 |
July | 0.596619E+10 | 10272.88 | 09-JUL-08:52 | 23.90 | 17.54 | 0.256367E+09 | 347.88 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.616947E+10 | 11061.33 | 20-AUG-08:61 | 24.68 | 14.74 | 0.287547E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.489895E+10 | 10740.90 | 03-SEP-08:21 | 24.45 | 14.42 | 0.254135E+09 | 347.88 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.376458E+10 | 9232.52 | 01-OCT-08:22 | 16.70 | 10.68 | 0.259141E+09 | 347.88 | 18-OCT-09:09 | 12.35 | 5.72 |
November | 0.234693E+10 | 4463.35 | 01-NOV-08:70 | 8.17 | 5.62 | 0.244121E+09 | 347.87 | 07-NOV-10:09 | 7.67 | 2.28 |
December | 0.161617E+10 | 1796.84 | 29-DEC-09:00 | 1.10 | -1.1 | 0.209888E+09 | 335.35 | 29-DEC-09:09 | 1.38 | -0.9 |
Annual Sum or Average | 0.434662E+11 | 0.298149E+10 | ||||||||
Minimum of Months | 0.150790E+10 | 1796.84 | 1.10 | -1.1 | 0.199613E+09 | 330.02 | 0.97 | -3.3 | ||
Maximum of Months | 0.616947E+10 | 11061.33 | 24.68 | 17.54 | 0.287547E+09 | 347.89 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214052E+10 | 9055.25 | 01-JAN-14:13 | 15.77 | 5.68 | 0.349741E+09 | 552.81 | 23-JAN-14:20 | 14.80 | 4.42 |
February | 0.190291E+10 | 7890.17 | 14-FEB-14:25 | 21.15 | 7.13 | 0.319600E+09 | 558.54 | 14-FEB-14:09 | 20.78 | 6.99 |
March | 0.205182E+10 | 5772.69 | 08-MAR-13:10 | 20.47 | 8.97 | 0.382331E+09 | 549.50 | 10-MAR-14:39 | 13.13 | 3.19 |
April | 0.249401E+10 | 4858.76 | 13-APR-16:50 | 26.02 | 10.24 | 0.353966E+09 | 549.50 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.324270E+10 | 8127.33 | 19-MAY-16:20 | 30.00 | 12.38 | 0.400210E+09 | 549.51 | 19-MAY-13:00 | 28.90 | 12.69 |
June | 0.565378E+10 | 10222.93 | 28-JUN-16:40 | 38.17 | 14.07 | 0.427716E+09 | 666.55 | 29-JUN-12:09 | 35.37 | 17.05 |
July | 0.683362E+10 | 10223.92 | 21-JUL-17:00 | 37.80 | 14.85 | 0.406131E+09 | 651.63 | 20-JUL-12:09 | 34.60 | 17.11 |
August | 0.720994E+10 | 9401.43 | 01-AUG-16:10 | 34.72 | 16.10 | 0.453327E+09 | 612.66 | 18-AUG-12:09 | 31.20 | 17.27 |
September | 0.655027E+10 | 9931.34 | 03-SEP-13:02 | 31.38 | 16.71 | 0.401701E+09 | 621.08 | 28-SEP-13:39 | 29.63 | 15.07 |
October | 0.575784E+10 | 10794.58 | 01-OCT-13:01 | 27.38 | 14.02 | 0.405079E+09 | 617.06 | 06-OCT-13:50 | 26.52 | 12.64 |
November | 0.356447E+10 | 8834.28 | 19-NOV-13:53 | 13.30 | 3.27 | 0.388778E+09 | 605.32 | 01-NOV-13:39 | 12.57 | 7.40 |
December | 0.232494E+10 | 8656.55 | 31-DEC-14:22 | 10.55 | 1.88 | 0.347983E+09 | 549.51 | 14-DEC-14:20 | 2.40 | -4.2 |
Annual Sum or Average | 0.497268E+11 | 0.463656E+10 | ||||||||
Minimum of Months | 0.190291E+10 | 4858.76 | 10.55 | 1.88 | 0.319600E+09 | 549.50 | 2.40 | -4.2 | ||
Maximum of Months | 0.720994E+10 | 10794.58 | 38.17 | 16.71 | 0.453327E+09 | 666.55 | 35.37 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153798E+10 | 3607.96 | 26-JAN-16:30 | 10.30 | 1.37 | 0.209579E+09 | 338.68 | 09-JAN-16:00 | 11.70 | 3.24 |
February | 0.166256E+10 | 5138.15 | 15-FEB-16:40 | 16.87 | 6.04 | 0.194801E+09 | 338.67 | 02-FEB-16:00 | 5.60 | 0.15 |
March | 0.244050E+10 | 4865.69 | 07-MAR-17:00 | 20.60 | 8.50 | 0.239176E+09 | 338.67 | 29-MAR-15:00 | 13.90 | 4.70 |
April | 0.316668E+10 | 6195.55 | 26-APR-17:00 | 25.60 | 10.21 | 0.231485E+09 | 347.66 | 14-APR-13:00 | 23.30 | 10.23 |
May | 0.388249E+10 | 9591.10 | 20-MAY-17:42 | 26.70 | 10.86 | 0.257566E+09 | 347.84 | 18-MAY-13:00 | 25.60 | 11.93 |
June | 0.502457E+10 | 11480.87 | 18-JUN-18:42 | 28.58 | 10.20 | 0.268426E+09 | 347.85 | 23-JUN-09:20 | 25.53 | 13.74 |
July | 0.534329E+10 | 11471.58 | 04-JUL-17:41 | 34.27 | 13.83 | 0.253447E+09 | 347.85 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.561292E+10 | 11831.34 | 20-AUG-18:01 | 33.67 | 15.12 | 0.284906E+09 | 347.86 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.463579E+10 | 11237.05 | 04-SEP-17:22 | 26.15 | 15.89 | 0.251159E+09 | 347.84 | 19-SEP-13:09 | 25.18 | 14.08 |
October | 0.380997E+10 | 10470.39 | 15-OCT-16:52 | 20.60 | 7.78 | 0.250057E+09 | 347.84 | 04-OCT-13:00 | 25.60 | 13.64 |
November | 0.250144E+10 | 5536.24 | 02-NOV-16:00 | 16.70 | 9.77 | 0.233432E+09 | 347.83 | 14-NOV-14:00 | 12.20 | 4.09 |
December | 0.167389E+10 | 2966.88 | 29-DEC-16:10 | 11.42 | 3.72 | 0.206175E+09 | 338.68 | 13-DEC-16:00 | 7.20 | 0.15 |
Annual Sum or Average | 0.412921E+11 | 0.288021E+10 | ||||||||
Minimum of Months | 0.153798E+10 | 2966.88 | 10.30 | 1.37 | 0.194801E+09 | 338.67 | 5.60 | 0.15 | ||
Maximum of Months | 0.561292E+10 | 11831.34 | 34.27 | 15.89 | 0.284906E+09 | 347.86 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150253E+10 | 1857.30 | 05-JAN-16:00 | 16.10 | 6.82 | 0.341014E+09 | 516.66 | 27-JAN-14:00 | 11.70 | 2.30 |
February | 0.158709E+10 | 2303.10 | 15-FEB-16:20 | 17.03 | 6.25 | 0.322641E+09 | 549.48 | 15-FEB-14:39 | 16.83 | 6.51 |
March | 0.245742E+10 | 2926.40 | 27-MAR-14:40 | 18.13 | 6.96 | 0.417606E+09 | 549.48 | 28-MAR-13:09 | 16.42 | 7.52 |
April | 0.318254E+10 | 4641.49 | 14-APR-14:30 | 23.60 | 10.42 | 0.392395E+09 | 549.49 | 17-APR-13:00 | 24.40 | 9.77 |
May | 0.413987E+10 | 5093.42 | 31-MAY-16:00 | 28.30 | 11.02 | 0.431964E+09 | 549.51 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.557546E+10 | 7447.13 | 29-JUN-05:02 | 24.40 | 16.06 | 0.434370E+09 | 549.50 | 19-JUN-13:09 | 25.10 | 8.99 |
July | 0.602324E+10 | 7581.19 | 24-JUL-04:01 | 22.70 | 14.93 | 0.404680E+09 | 549.49 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.596679E+10 | 6606.65 | 22-AUG-04:01 | 21.70 | 15.46 | 0.453793E+09 | 549.52 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.442300E+10 | 5153.38 | 12-SEP-14:30 | 29.15 | 14.67 | 0.400562E+09 | 549.49 | 27-SEP-09:09 | 18.77 | 10.92 |
October | 0.320060E+10 | 4853.50 | 02-OCT-13:40 | 26.33 | 15.34 | 0.401817E+09 | 549.49 | 24-OCT-13:50 | 8.87 | 4.53 |
November | 0.206839E+10 | 2607.70 | 02-NOV-15:30 | 16.95 | 9.54 | 0.375965E+09 | 549.48 | 01-NOV-13:00 | 12.20 | 7.25 |
December | 0.142990E+10 | 1768.68 | 01-DEC-16:00 | 12.80 | 4.90 | 0.326540E+09 | 532.59 | 01-DEC-14:00 | 12.20 | 4.60 |
Annual Sum or Average | 0.415568E+11 | 0.470335E+10 | ||||||||
Minimum of Months | 0.142990E+10 | 1768.68 | 12.80 | 4.90 | 0.322641E+09 | 516.66 | 8.87 | 2.30 | ||
Maximum of Months | 0.602324E+10 | 7581.19 | 29.15 | 16.06 | 0.453793E+09 | 549.52 | 30.18 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176262E+10 | 2885.87 | 27-JAN-09:30 | 1.70 | -2.9 | 0.158514E+09 | 338.71 | 26-JAN-09:30 | 0.55 | -4.0 |
February | 0.199405E+10 | 4708.96 | 14-FEB-09:05 | 7.25 | 1.88 | 0.149899E+09 | 338.94 | 10-FEB-09:20 | 4.07 | 0.25 |
March | 0.328335E+10 | 7366.36 | 26-MAR-09:02 | 11.23 | 4.18 | 0.191608E+09 | 338.72 | 31-MAR-07:19 | 5.20 | 1.73 |
April | 0.437889E+10 | 11479.95 | 30-APR-07:42 | 14.63 | 5.05 | 0.184303E+09 | 341.47 | 28-APR-07:00 | 16.70 | 6.95 |
May | 0.509462E+10 | 12379.31 | 29-MAY-08:42 | 17.93 | 12.71 | 0.199786E+09 | 338.75 | 23-MAY-15:09 | 14.32 | 13.26 |
June | 0.628423E+10 | 12405.08 | 18-JUN-07:52 | 22.80 | 11.49 | 0.201532E+09 | 338.74 | 22-JUN-07:10 | 23.68 | 14.41 |
July | 0.639456E+10 | 13023.44 | 02-JUL-08:52 | 23.30 | 17.34 | 0.188699E+09 | 338.74 | 06-JUL-07:10 | 23.68 | 15.33 |
August | 0.641739E+10 | 13900.48 | 20-AUG-08:61 | 24.68 | 14.74 | 0.210706E+09 | 338.73 | 28-AUG-14:09 | 23.40 | 17.49 |
September | 0.504188E+10 | 13319.65 | 03-SEP-08:21 | 24.45 | 14.42 | 0.185268E+09 | 338.73 | 28-SEP-10:09 | 25.68 | 14.14 |
October | 0.393646E+10 | 11714.89 | 01-OCT-09:02 | 18.35 | 11.46 | 0.185051E+09 | 338.73 | 06-OCT-10:09 | 21.57 | 12.31 |
November | 0.257208E+10 | 5435.02 | 01-NOV-08:50 | 9.63 | 6.29 | 0.172895E+09 | 338.98 | 07-NOV-08:39 | 3.87 | 0.35 |
December | 0.172102E+10 | 2705.79 | 29-DEC-08:55 | 1.10 | -1.1 | 0.153391E+09 | 338.71 | 29-DEC-09:20 | 1.67 | -0.8 |
Annual Sum or Average | 0.488811E+11 | 0.218165E+10 | ||||||||
Minimum of Months | 0.172102E+10 | 2705.79 | 1.10 | -2.9 | 0.149899E+09 | 338.71 | 0.55 | -4.0 | ||
Maximum of Months | 0.641739E+10 | 13900.48 | 24.68 | 17.34 | 0.210706E+09 | 341.47 | 25.68 | 17.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431896E+10 | 9734.95 | 01-JAN-14:13 | 15.77 | 5.68 | 0.401931E+09 | 676.99 | 26-JAN-14:09 | 10.10 | 1.47 |
February | 0.421013E+10 | 9702.43 | 19-FEB-14:02 | 16.28 | 6.77 | 0.368320E+09 | 639.76 | 10-FEB-14:09 | 13.90 | 5.02 |
March | 0.439087E+10 | 8283.13 | 08-MAR-13:30 | 21.40 | 9.26 | 0.433003E+09 | 571.31 | 30-MAR-13:20 | 14.80 | 5.77 |
April | 0.414881E+10 | 6455.15 | 27-APR-13:10 | 23.07 | 9.44 | 0.393611E+09 | 549.50 | 26-APR-13:20 | 24.80 | 9.87 |
May | 0.448740E+10 | 5597.77 | 31-MAY-14:20 | 27.93 | 11.36 | 0.430946E+09 | 549.51 | 11-MAY-09:09 | 12.57 | 6.20 |
June | 0.572457E+10 | 7012.77 | 29-JUN-14:40 | 37.43 | 15.73 | 0.433430E+09 | 549.50 | 19-JUN-13:09 | 25.10 | 8.99 |
July | 0.631623E+10 | 8242.66 | 24-JUL-04:01 | 22.70 | 14.93 | 0.404301E+09 | 549.49 | 21-JUL-09:09 | 30.18 | 16.57 |
August | 0.683200E+10 | 8380.77 | 31-AUG-12:40 | 28.87 | 15.83 | 0.453705E+09 | 557.34 | 31-AUG-13:09 | 29.50 | 15.71 |
September | 0.649003E+10 | 10904.17 | 03-SEP-13:02 | 31.38 | 16.71 | 0.404218E+09 | 646.02 | 28-SEP-13:30 | 29.45 | 15.24 |
October | 0.660843E+10 | 11817.01 | 01-OCT-12:21 | 26.40 | 14.32 | 0.425738E+09 | 665.54 | 31-OCT-13:09 | 20.47 | 8.40 |
November | 0.537701E+10 | 9032.58 | 19-NOV-14:23 | 14.15 | 3.66 | 0.426368E+09 | 691.83 | 01-NOV-13:20 | 12.93 | 7.55 |
December | 0.481976E+10 | 9112.75 | 24-DEC-14:13 | 12.57 | 3.50 | 0.400507E+09 | 671.20 | 29-DEC-14:09 | 10.68 | 3.51 |
Annual Sum or Average | 0.637242E+11 | 0.497608E+10 | ||||||||
Minimum of Months | 0.414881E+10 | 5597.77 | 12.57 | 3.50 | 0.368320E+09 | 549.49 | 10.10 | 1.47 | ||
Maximum of Months | 0.683200E+10 | 11817.01 | 37.43 | 16.71 | 0.453705E+09 | 691.83 | 30.18 | 16.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183929E+10 | 4756.18 | 26-JAN-16:30 | 10.30 | 1.37 | 0.213179E+09 | 347.58 | 26-JAN-14:00 | 10.60 | 1.70 |
February | 0.215590E+10 | 6646.06 | 15-FEB-16:30 | 16.95 | 6.15 | 0.199236E+09 | 347.82 | 15-FEB-14:00 | 17.20 | 6.64 |
March | 0.326853E+10 | 9523.93 | 12-MAR-16:42 | 20.40 | 6.29 | 0.246230E+09 | 347.82 | 10-MAR-14:00 | 13.30 | 3.25 |
April | 0.409020E+10 | 11921.69 | 16-APR-16:32 | 20.20 | 7.99 | 0.233431E+09 | 347.84 | 14-APR-13:00 | 23.30 | 10.23 |
May | 0.483241E+10 | 13243.25 | 29-MAY-16:42 | 26.28 | 13.26 | 0.257949E+09 | 347.84 | 15-MAY-13:00 | 27.80 | 10.72 |
June | 0.580479E+10 | 14297.43 | 11-JUN-17:01 | 28.22 | 13.05 | 0.265554E+09 | 347.85 | 13-JUN-13:09 | 31.38 | 15.22 |
July | 0.595754E+10 | 13793.18 | 04-JUL-17:01 | 35.73 | 14.59 | 0.250092E+09 | 347.84 | 21-JUL-09:00 | 31.10 | 16.98 |
August | 0.606547E+10 | 13790.02 | 20-AUG-18:01 | 33.67 | 15.12 | 0.278815E+09 | 347.86 | 28-AUG-13:50 | 23.30 | 17.43 |
September | 0.494678E+10 | 13035.65 | 04-SEP-17:22 | 26.15 | 15.89 | 0.241701E+09 | 347.84 | 29-SEP-13:09 | 28.98 | 15.48 |
October | 0.408005E+10 | 12457.08 | 01-OCT-15:42 | 28.80 | 13.16 | 0.239361E+09 | 347.83 | 02-OCT-13:09 | 25.78 | 15.14 |
November | 0.270961E+10 | 5968.30 | 02-NOV-16:00 | 16.70 | 9.77 | 0.226853E+09 | 347.84 | 15-NOV-14:00 | 8.90 | 2.08 |
December | 0.178878E+10 | 3816.43 | 29-DEC-16:10 | 11.42 | 3.72 | 0.206539E+09 | 347.55 | 20-DEC-14:00 | 7.00 | 0.44 |
Annual Sum or Average | 0.475393E+11 | 0.285894E+10 | ||||||||
Minimum of Months | 0.178878E+10 | 3816.43 | 10.30 | 1.37 | 0.199236E+09 | 347.55 | 7.00 | 0.44 | ||
Maximum of Months | 0.606547E+10 | 14297.43 | 35.73 | 15.89 | 0.278815E+09 | 347.86 | 31.38 | 17.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177817E+10 | 6273.19 | 17-JAN-06:06 | -3.4 |
February | 0.119948E+10 | 6814.80 | 06-FEB-06:07 | -4.6 |
March | 0.783121E+09 | 4501.09 | 04-MAR-06:06 | -1.7 |
April | 0.342814E+09 | 4029.84 | 30-APR-06:35 | 12.60 |
May | 0.160510E+09 | 5929.04 | 30-MAY-05:02 | 14.72 |
June | 54638533.26 | 6380.76 | 19-JUN-05:03 | 12.57 |
July | 25355657.46 | 5214.68 | 13-JUL-05:02 | 17.57 |
August | 23582223.92 | 5132.54 | 28-AUG-05:02 | 16.52 |
September | 72695127.06 | 4960.70 | 14-SEP-05:02 | 14.90 |
October | 0.469855E+09 | 4766.69 | 02-OCT-05:02 | 17.12 |
November | 0.819125E+09 | 5481.48 | 27-NOV-07:05 | -4.2 |
December | 0.176688E+10 | 5537.04 | 15-DEC-06:05 | -7.9 |
Annual Sum or Average | 0.749623E+10 | |||
Minimum of Months | 23582223.92 | 4029.84 | -7.9 | |
Maximum of Months | 0.177817E+10 | 6814.80 | 17.57 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.859382E+09 | 4232.54 | 22-JAN-14:32 | 12.97 |
February | 0.524907E+09 | 3271.77 | 12-FEB-12:23 | 13.90 |
March | 0.114115E+09 | 2821.64 | 12-MAR-11:42 | 15.55 |
April | 13917597.91 | 3048.91 | 16-APR-16:32 | 20.20 |
May | 16892438.75 | 2543.72 | 07-MAY-14:29 | 23.60 |
June | 17784213.10 | 2615.94 | 11-JUN-16:21 | 28.05 |
July | 16164871.93 | 2132.42 | 30-JUL-08:12 | 24.47 |
August | 12922271.74 | 2119.10 | 23-AUG-04:02 | 18.80 |
September | 13472207.00 | 2837.96 | 24-SEP-11:11 | 20.37 |
October | 62252379.12 | 3446.54 | 15-OCT-15:32 | 20.77 |
November | 0.328196E+09 | 3713.30 | 12-NOV-10:02 | 4.18 |
December | 0.867529E+09 | 4110.60 | 24-DEC-12:53 | 10.60 |
Annual Sum or Average | 0.284754E+10 | |||
Minimum of Months | 12922271.74 | 2119.10 | 4.18 | |
Maximum of Months | 0.867529E+09 | 4232.54 | 28.05 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351570E+09 | 4589.04 | 18-JAN-08:07 | -3.2 |
February | 0.158864E+09 | 4440.06 | 06-FEB-08:08 | -4.0 |
March | 19442832.71 | 3452.17 | 06-MAR-08:04 | 1.75 |
April | 8403533.54 | 3456.71 | 14-APR-05:02 | 8.58 |
May | 13409479.27 | 3876.15 | 18-MAY-05:03 | 12.20 |
June | 11784186.10 | 3430.09 | 02-JUN-05:03 | 13.30 |
July | 9554376.63 | 3157.27 | 21-JUL-04:01 | 20.92 |
August | 10756401.61 | 3314.64 | 10-AUG-04:01 | 21.70 |
September | 14760515.58 | 3299.91 | 23-SEP-05:02 | 16.10 |
October | 23497475.25 | 5341.79 | 23-OCT-05:02 | 6.60 |
November | 33527171.45 | 4732.61 | 02-NOV-05:02 | 7.12 |
December | 0.227074E+09 | 4559.61 | 26-DEC-08:14 | -1.3 |
Annual Sum or Average | 0.882644E+09 | |||
Minimum of Months | 8403533.54 | 3157.27 | -4.0 | |
Maximum of Months | 0.351570E+09 | 5341.79 | 21.70 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 704797.32 | 11746.62 | 17-JAN-07:01 | -3.9 |
February | 892155.24 | 14869.25 | 06-FEB-07:01 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 375069.06 | 6251.15 | 26-DEC-07:01 | -1.8 |
Annual Sum or Average | 1972021.62 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 892155.24 | 14869.25 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125562E+09 | 16947.02 | 17-JAN-06:01 | -3.4 |
February | 67092436.26 | 16998.52 | 06-FEB-06:01 | -4.6 |
March | 922177.53 | 15369.63 | 06-MAR-07:01 | -0.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 7516200.84 | 15890.91 | 27-NOV-07:01 | -4.2 |
December | 91312851.98 | 16746.11 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.292406E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.125562E+09 | 16998.52 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634043E+09 | 5547.12 | 17-JAN-05:01 | -3.3 |
February | 0.339769E+09 | 5568.09 | 06-FEB-05:01 | -4.4 |
March | 67502055.43 | 4779.28 | 04-MAR-06:02 | -1.7 |
April | 2994900.02 | 4432.71 | 08-APR-06:03 | 1.78 |
May | 114829.27 | 545.78 | 05-MAY-06:02 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 20113244.79 | 4606.93 | 26-OCT-05:02 | -2.5 |
November | 0.107064E+09 | 5068.06 | 27-NOV-06:01 | -4.4 |
December | 0.593080E+09 | 5110.91 | 04-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.176468E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.634043E+09 | 5568.09 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333266E+09 | 6140.31 | 17-JAN-05:01 | -3.3 |
February | 0.148383E+09 | 6150.08 | 06-FEB-05:01 | -4.4 |
March | 23680997.03 | 5285.13 | 04-MAR-06:02 | -1.7 |
April | 1676997.72 | 4882.45 | 06-APR-06:01 | 1.88 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 12745949.20 | 5006.89 | 26-OCT-06:01 | -1.4 |
November | 36371024.36 | 5575.57 | 27-NOV-06:01 | -4.4 |
December | 0.300597E+09 | 5666.65 | 04-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.856721E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.333266E+09 | 6150.08 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381192E+09 | 5904.05 | 17-JAN-05:01 | -3.3 |
February | 0.203821E+09 | 5887.19 | 06-FEB-05:01 | -4.4 |
March | 47892379.04 | 5120.45 | 04-MAR-06:02 | -1.7 |
April | 2844430.02 | 4767.37 | 08-APR-06:03 | 1.78 |
May | 289049.62 | 1360.07 | 05-MAY-06:02 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 15880710.55 | 4950.49 | 26-OCT-05:02 | -2.5 |
November | 37272421.67 | 5250.11 | 27-NOV-06:01 | -4.4 |
December | 0.313852E+09 | 5479.02 | 04-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.100304E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.381192E+09 | 5904.05 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392460E+09 | 6798.64 | 17-JAN-05:01 | -3.3 |
February | 0.212422E+09 | 6801.66 | 06-FEB-05:01 | -4.4 |
March | 48458623.61 | 5850.43 | 04-MAR-06:02 | -1.7 |
April | 4705809.60 | 5515.87 | 06-APR-06:01 | 1.88 |
May | 1210279.39 | 5416.19 | 05-MAY-06:02 | 6.20 |
June | 97194.21 | 809.95 | 09-JUN-06:02 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 15968081.87 | 5564.21 | 26-OCT-06:01 | -1.4 |
November | 63776254.83 | 6148.38 | 27-NOV-06:01 | -4.4 |
December | 0.358020E+09 | 6293.69 | 04-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.109712E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.392460E+09 | 6801.66 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161507E+09 | 4032.52 | 17-JAN-06:01 | -3.4 |
February | 0.103758E+09 | 4108.40 | 06-FEB-06:01 | -4.6 |
March | 16678232.55 | 3773.27 | 06-MAR-07:01 | -0.3 |
April | 78161.45 | 521.08 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 2740566.00 | 3757.64 | 27-NOV-07:01 | -4.2 |
December | 63177184.77 | 3838.13 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.347939E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.161507E+09 | 4108.40 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67591435.39 | 4468.89 | 17-JAN-06:01 | -3.4 |
February | 27142234.54 | 4536.90 | 06-FEB-06:01 | -4.6 |
March | 4768178.50 | 4238.18 | 23-MAR-06:01 | 2.30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 247085.04 | 4118.08 | 26-OCT-06:01 | -1.4 |
November | 505666.51 | 4186.45 | 27-NOV-07:01 | -4.2 |
December | 26005074.85 | 4253.77 | 26-DEC-07:01 | -1.8 |
Annual Sum or Average | 0.126260E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 67591435.39 | 4536.90 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133158E+10 | 5988.39 | 18-JAN-07:10 | -3.3 |
February | 0.102788E+10 | 5960.57 | 06-FEB-07:10 | -5.4 |
March | 0.804459E+09 | 5425.50 | 30-MAR-06:10 | -1.7 |
April | 0.448132E+09 | 5010.15 | 06-APR-06:10 | 1.88 |
May | 0.293110E+09 | 4686.01 | 05-MAY-06:10 | 6.20 |
June | 39717104.54 | 4344.25 | 09-JUN-06:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 1369715.46 | 2620.19 | 31-AUG-06:07 | 13.63 |
September | 33583571.94 | 4058.49 | 25-SEP-06:05 | 11.75 |
October | 0.358239E+09 | 5382.09 | 26-OCT-07:00 | -2.8 |
November | 0.502690E+09 | 5244.86 | 27-NOV-07:10 | -4.2 |
December | 0.112295E+10 | 5921.34 | 22-DEC-07:10 | -6.1 |
Annual Sum or Average | 0.596371E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 0.133158E+10 | 5988.39 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63931181.98 | 4747.54 | 17-JAN-06:01 | -3.4 |
February | 38693727.76 | 4816.33 | 06-FEB-06:01 | -4.6 |
March | 9218231.64 | 4531.95 | 03-MAR-07:01 | 2.88 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 265142.42 | 4419.04 | 26-OCT-06:01 | -1.4 |
November | 695988.68 | 4480.86 | 27-NOV-07:01 | -4.2 |
December | 29510952.35 | 4543.35 | 26-DEC-07:01 | -1.8 |
Annual Sum or Average | 0.142315E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 63931181.98 | 4816.33 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134211E+09 | 4390.34 | 17-JAN-06:01 | -3.4 |
February | 61004740.96 | 4381.50 | 06-FEB-06:01 | -4.6 |
March | 3764965.93 | 3963.43 | 06-MAR-07:01 | -0.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 503970.75 | 3876.91 | 26-OCT-06:01 | -1.4 |
November | 7149031.20 | 4013.18 | 27-NOV-06:01 | -4.4 |
December | 82991524.07 | 4157.09 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.289625E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.134211E+09 | 4390.34 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81342818.07 | 5552.82 | 17-JAN-06:01 | -3.4 |
February | 29048726.15 | 5519.43 | 06-FEB-06:01 | -4.6 |
March | 4267730.88 | 4963.02 | 22-MAR-06:01 | 2.15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1560969.41 | 4992.91 | 26-OCT-06:01 | -1.4 |
November | 3540749.47 | 4980.65 | 27-NOV-07:01 | -4.2 |
December | 50146115.20 | 5256.61 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.169907E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 81342818.07 | 5552.82 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69146823.19 | 4718.37 | 17-JAN-06:01 | -3.4 |
February | 32588441.58 | 4679.66 | 06-FEB-06:01 | -4.6 |
March | 1956748.84 | 4250.71 | 06-MAR-07:01 | -0.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 421794.96 | 4225.96 | 26-OCT-06:01 | -1.4 |
November | 1275256.50 | 4302.31 | 27-NOV-07:01 | -4.2 |
December | 39326339.49 | 4492.39 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.144715E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 69146823.19 | 4718.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87705163.01 | 5755.19 | 17-JAN-06:01 | -3.4 |
February | 42774774.48 | 5715.71 | 06-FEB-06:01 | -4.6 |
March | 7512365.84 | 5186.45 | 06-MAR-07:01 | -0.3 |
April | 121519.19 | 810.13 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1371713.84 | 5195.22 | 26-OCT-06:01 | -1.4 |
November | 8838494.69 | 5195.84 | 28-NOV-07:01 | -1.9 |
December | 61045338.97 | 5429.07 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.209369E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 87705163.01 | 5755.19 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.600134E+10 | 6236.40 | 02-JAN-08:09 | 0.243995E+11 | 29385.51 | 02-JAN-08:09 |
February | 0.544341E+10 | 6236.40 | 01-FEB-08:09 | 0.221463E+11 | 29385.51 | 01-FEB-08:09 |
March | 0.646374E+10 | 6236.40 | 01-MAR-08:09 | 0.260355E+11 | 29385.51 | 01-MAR-08:09 |
April | 0.577805E+10 | 6236.40 | 03-APR-07:10 | 0.235867E+11 | 29385.51 | 03-APR-07:10 |
May | 0.623254E+10 | 6236.40 | 01-MAY-07:10 | 0.252175E+11 | 29385.51 | 01-MAY-07:10 |
June | 0.620069E+10 | 6236.40 | 01-JUN-07:10 | 0.250118E+11 | 29385.51 | 01-JUN-07:10 |
July | 0.580989E+10 | 6236.40 | 03-JUL-07:10 | 0.237925E+11 | 29385.51 | 03-JUL-07:10 |
August | 0.646374E+10 | 6236.40 | 01-AUG-07:10 | 0.260355E+11 | 29385.51 | 01-AUG-07:10 |
September | 0.577805E+10 | 6236.40 | 01-SEP-07:10 | 0.235867E+11 | 29385.51 | 01-SEP-07:10 |
October | 0.600134E+10 | 6236.40 | 02-OCT-07:10 | 0.243995E+11 | 29385.51 | 02-OCT-07:10 |
November | 0.592974E+10 | 6236.40 | 01-NOV-07:10 | 0.239828E+11 | 29385.51 | 01-NOV-07:10 |
December | 0.580989E+10 | 6236.40 | 01-DEC-08:09 | 0.237925E+11 | 29385.51 | 01-DEC-08:09 |
Annual Sum or Average | 0.719124E+11 | 0.291987E+12 | ||||
Minimum of Months | 0.544341E+10 | 6236.40 | 0.221463E+11 | 29385.51 | ||
Maximum of Months | 0.646374E+10 | 6236.40 | 0.260355E+11 | 29385.51 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.600134E+10 | 6236.40 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.544341E+10 | 6236.40 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.646374E+10 | 6236.40 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.577805E+10 | 6236.40 | 03-APR-07:10 | 0.102937E+11 | 7143.44 | 03-APR-07:10 |
May | 0.623254E+10 | 6236.40 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.620069E+10 | 6236.40 | 01-JUN-07:10 | 0.106523E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.580989E+10 | 6236.40 | 03-JUL-07:10 | 0.104994E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.646374E+10 | 6236.40 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.577805E+10 | 6236.40 | 01-SEP-07:10 | 0.102937E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.600134E+10 | 6236.40 | 02-OCT-07:10 | 0.106609E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.592974E+10 | 6236.40 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.580989E+10 | 6236.40 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.719124E+11 | 0.126597E+12 | ||||
Minimum of Months | 0.544341E+10 | 6236.40 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.646374E+10 | 6236.40 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.600134E+10 | 6236.40 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.544341E+10 | 6236.40 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.646374E+10 | 6236.40 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.577805E+10 | 6236.40 | 03-APR-07:10 | 0.102937E+11 | 7143.44 | 03-APR-07:10 |
May | 0.623254E+10 | 6236.40 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.620069E+10 | 6236.40 | 01-JUN-07:10 | 0.106523E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.580989E+10 | 6236.40 | 03-JUL-07:10 | 0.104994E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.646374E+10 | 6236.40 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.577805E+10 | 6236.40 | 01-SEP-07:10 | 0.102937E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.600134E+10 | 6236.40 | 02-OCT-07:10 | 0.106609E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.592974E+10 | 6236.40 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.580989E+10 | 6236.40 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.719124E+11 | 0.126597E+12 | ||||
Minimum of Months | 0.544341E+10 | 6236.40 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.646374E+10 | 6236.40 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101348E+10 | 1222.09 | 09-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.907587E+09 | 1126.73 | 16-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105839E+10 | 1031.04 | 20-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.935935E+09 | 961.76 | 03-APR-07:10 | 0.216999E+10 | 1505.89 | 03-APR-07:10 |
May | 0.100468E+10 | 961.76 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.993489E+09 | 961.76 | 01-JUN-07:10 | 0.224559E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.935406E+09 | 961.76 | 03-JUL-07:10 | 0.221336E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.104252E+10 | 961.76 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.942551E+09 | 1112.44 | 08-SEP-07:10 | 0.216999E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.993582E+09 | 1112.57 | 25-OCT-07:10 | 0.224739E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.100332E+10 | 1314.69 | 13-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.100072E+10 | 1314.69 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118317E+11 | 0.266877E+11 | ||||
Minimum of Months | 0.907587E+09 | 961.76 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105839E+10 | 1314.69 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.639787E+09 | 772.99 | 09-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.573800E+09 | 704.37 | 16-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.669695E+09 | 620.18 | 14-MAR-15:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.593334E+09 | 608.87 | 03-APR-07:10 | 0.137370E+10 | 953.30 | 03-APR-07:10 |
May | 0.637595E+09 | 608.87 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.630153E+09 | 608.87 | 01-JUN-07:10 | 0.142155E+10 | 953.30 | 01-JUN-07:10 |
July | 0.593055E+09 | 608.87 | 03-JUL-07:10 | 0.140115E+10 | 953.30 | 03-JUL-07:10 |
August | 0.660784E+09 | 608.87 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.596692E+09 | 696.84 | 08-SEP-07:10 | 0.137370E+10 | 953.30 | 01-SEP-07:10 |
October | 0.627201E+09 | 676.70 | 25-OCT-07:10 | 0.142270E+10 | 953.30 | 02-OCT-07:10 |
November | 0.634655E+09 | 832.31 | 13-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.631572E+09 | 832.31 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.748832E+10 | 0.168945E+11 | ||||
Minimum of Months | 0.573800E+09 | 608.87 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.669695E+09 | 832.31 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100410E+10 | 1170.17 | 04-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.902952E+09 | 1119.28 | 16-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105695E+10 | 1016.32 | 20-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.936935E+09 | 961.76 | 03-APR-07:10 | 0.216998E+10 | 1505.88 | 03-APR-07:10 |
May | 0.100699E+10 | 961.76 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.995973E+09 | 961.76 | 01-JUN-07:10 | 0.224557E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.937263E+09 | 961.76 | 03-JUL-07:10 | 0.221335E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.104368E+10 | 961.76 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.942213E+09 | 1110.89 | 08-SEP-07:10 | 0.216998E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.988077E+09 | 1095.42 | 25-OCT-07:10 | 0.224738E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.994830E+09 | 1314.69 | 13-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.986461E+09 | 1314.69 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.117964E+11 | 0.266876E+11 | ||||
Minimum of Months | 0.902952E+09 | 961.76 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105695E+10 | 1314.69 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.637285E+09 | 727.71 | 04-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.572263E+09 | 713.60 | 16-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.669304E+09 | 683.29 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.592087E+09 | 608.83 | 03-APR-07:10 | 0.137369E+10 | 953.29 | 03-APR-07:10 |
May | 0.635960E+09 | 608.83 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.629399E+09 | 621.08 | 08-JUN-07:10 | 0.142154E+10 | 953.29 | 01-JUN-07:10 |
July | 0.592547E+09 | 608.83 | 03-JUL-07:10 | 0.140114E+10 | 953.29 | 03-JUL-07:10 |
August | 0.659895E+09 | 608.83 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.596190E+09 | 705.74 | 08-SEP-07:10 | 0.137369E+10 | 953.29 | 01-SEP-07:10 |
October | 0.627241E+09 | 711.80 | 25-OCT-07:10 | 0.142269E+10 | 953.29 | 02-OCT-07:10 |
November | 0.630164E+09 | 832.25 | 13-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.627459E+09 | 832.25 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.746979E+10 | 0.168944E+11 | ||||
Minimum of Months | 0.572263E+09 | 608.83 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.669304E+09 | 832.25 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101226E+10 | 1215.97 | 09-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.906869E+09 | 1118.60 | 16-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105789E+10 | 1018.39 | 20-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.935792E+09 | 961.76 | 03-APR-07:10 | 0.216999E+10 | 1505.89 | 03-APR-07:10 |
May | 0.100456E+10 | 961.76 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.993313E+09 | 961.76 | 01-JUN-07:10 | 0.224559E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.935233E+09 | 961.76 | 03-JUL-07:10 | 0.221336E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.104253E+10 | 961.76 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.942137E+09 | 1103.68 | 08-SEP-07:10 | 0.216999E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.992821E+09 | 1103.64 | 25-OCT-07:10 | 0.224739E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.100233E+10 | 1314.69 | 13-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.999671E+09 | 1314.69 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118254E+11 | 0.266877E+11 | ||||
Minimum of Months | 0.906869E+09 | 961.76 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105789E+10 | 1314.69 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.639264E+09 | 769.65 | 09-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.573498E+09 | 699.91 | 16-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.669440E+09 | 613.05 | 14-MAR-15:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.593220E+09 | 608.87 | 03-APR-07:10 | 0.137370E+10 | 953.30 | 03-APR-07:10 |
May | 0.637452E+09 | 608.87 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.629990E+09 | 608.87 | 01-JUN-07:10 | 0.142155E+10 | 953.30 | 01-JUN-07:10 |
July | 0.592907E+09 | 608.87 | 03-JUL-07:10 | 0.140115E+10 | 953.30 | 03-JUL-07:10 |
August | 0.660681E+09 | 608.87 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.596516E+09 | 692.12 | 08-SEP-07:10 | 0.137370E+10 | 953.30 | 01-SEP-07:10 |
October | 0.626896E+09 | 670.92 | 25-OCT-07:10 | 0.142270E+10 | 953.30 | 02-OCT-07:10 |
November | 0.634184E+09 | 832.31 | 13-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.631142E+09 | 832.31 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.748519E+10 | 0.168945E+11 | ||||
Minimum of Months | 0.573498E+09 | 608.87 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.669440E+09 | 832.31 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100372E+10 | 1162.98 | 04-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.902623E+09 | 1110.73 | 16-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105661E+10 | 1002.85 | 20-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.936717E+09 | 961.76 | 03-APR-07:10 | 0.216998E+10 | 1505.88 | 03-APR-07:10 |
May | 0.100676E+10 | 961.76 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.995593E+09 | 961.76 | 01-JUN-07:10 | 0.224557E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.936981E+09 | 961.76 | 03-JUL-07:10 | 0.221335E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.104345E+10 | 961.76 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.941848E+09 | 1102.05 | 08-SEP-07:10 | 0.216998E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.987858E+09 | 1085.53 | 25-OCT-07:10 | 0.224738E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.994472E+09 | 1314.69 | 13-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.986062E+09 | 1314.69 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.117927E+11 | 0.266876E+11 | ||||
Minimum of Months | 0.902623E+09 | 961.76 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105661E+10 | 1314.69 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.636955E+09 | 723.35 | 04-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.571968E+09 | 709.60 | 16-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.669114E+09 | 678.16 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.591952E+09 | 608.83 | 03-APR-07:10 | 0.137369E+10 | 953.29 | 03-APR-07:10 |
May | 0.635862E+09 | 608.83 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.629249E+09 | 614.01 | 08-JUN-07:10 | 0.142154E+10 | 953.29 | 01-JUN-07:10 |
July | 0.592438E+09 | 608.83 | 03-JUL-07:10 | 0.140114E+10 | 953.29 | 03-JUL-07:10 |
August | 0.659763E+09 | 608.83 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.595982E+09 | 701.47 | 08-SEP-07:10 | 0.137369E+10 | 953.29 | 01-SEP-07:10 |
October | 0.626924E+09 | 707.71 | 25-OCT-07:10 | 0.142269E+10 | 953.29 | 02-OCT-07:10 |
November | 0.629796E+09 | 832.25 | 13-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.626791E+09 | 832.25 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.746679E+10 | 0.168944E+11 | ||||
Minimum of Months | 0.571968E+09 | 608.83 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.669114E+09 | 832.25 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101348E+10 | 1222.09 | 09-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.907587E+09 | 1126.71 | 16-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105839E+10 | 1031.02 | 20-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.935935E+09 | 961.76 | 03-APR-07:10 | 0.216999E+10 | 1505.89 | 03-APR-07:10 |
May | 0.100468E+10 | 961.76 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.993489E+09 | 961.76 | 01-JUN-07:10 | 0.224559E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.935406E+09 | 961.76 | 03-JUL-07:10 | 0.221336E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.104252E+10 | 961.76 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.942551E+09 | 1112.42 | 08-SEP-07:10 | 0.216999E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.993582E+09 | 1112.55 | 25-OCT-07:10 | 0.224739E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.100332E+10 | 1314.69 | 13-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.100072E+10 | 1314.69 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118317E+11 | 0.266877E+11 | ||||
Minimum of Months | 0.907587E+09 | 961.76 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105839E+10 | 1314.69 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.639787E+09 | 773.00 | 09-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.573800E+09 | 704.36 | 16-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.669695E+09 | 620.17 | 14-MAR-15:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.593334E+09 | 608.87 | 03-APR-07:10 | 0.137370E+10 | 953.30 | 03-APR-07:10 |
May | 0.637595E+09 | 608.87 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.630153E+09 | 608.87 | 01-JUN-07:10 | 0.142155E+10 | 953.30 | 01-JUN-07:10 |
July | 0.593055E+09 | 608.87 | 03-JUL-07:10 | 0.140115E+10 | 953.30 | 03-JUL-07:10 |
August | 0.660784E+09 | 608.87 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.596692E+09 | 696.83 | 08-SEP-07:10 | 0.137370E+10 | 953.30 | 01-SEP-07:10 |
October | 0.627201E+09 | 676.69 | 25-OCT-07:10 | 0.142270E+10 | 953.30 | 02-OCT-07:10 |
November | 0.634655E+09 | 832.31 | 13-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.631572E+09 | 832.31 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.748832E+10 | 0.168945E+11 | ||||
Minimum of Months | 0.573800E+09 | 608.87 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.669695E+09 | 832.31 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100410E+10 | 1170.16 | 04-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.902952E+09 | 1119.26 | 16-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105695E+10 | 1016.30 | 20-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.936935E+09 | 961.76 | 03-APR-07:10 | 0.216998E+10 | 1505.88 | 03-APR-07:10 |
May | 0.100699E+10 | 961.76 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.995973E+09 | 961.76 | 01-JUN-07:10 | 0.224557E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.937263E+09 | 961.76 | 03-JUL-07:10 | 0.221335E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.104368E+10 | 961.76 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.942213E+09 | 1110.88 | 08-SEP-07:10 | 0.216998E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.988077E+09 | 1095.41 | 25-OCT-07:10 | 0.224738E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.994830E+09 | 1314.69 | 13-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.986461E+09 | 1314.69 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.117964E+11 | 0.266876E+11 | ||||
Minimum of Months | 0.902952E+09 | 961.76 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105695E+10 | 1314.69 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.637285E+09 | 727.71 | 04-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.572263E+09 | 713.59 | 16-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.669304E+09 | 683.28 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.592088E+09 | 608.83 | 03-APR-07:10 | 0.137369E+10 | 953.29 | 03-APR-07:10 |
May | 0.635961E+09 | 608.83 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.629399E+09 | 621.07 | 08-JUN-07:10 | 0.142154E+10 | 953.29 | 01-JUN-07:10 |
July | 0.592547E+09 | 608.83 | 03-JUL-07:10 | 0.140114E+10 | 953.29 | 03-JUL-07:10 |
August | 0.659895E+09 | 608.83 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.596190E+09 | 705.73 | 08-SEP-07:10 | 0.137369E+10 | 953.29 | 01-SEP-07:10 |
October | 0.627242E+09 | 711.80 | 25-OCT-07:10 | 0.142269E+10 | 953.29 | 02-OCT-07:10 |
November | 0.630164E+09 | 832.25 | 13-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.627459E+09 | 832.25 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.746980E+10 | 0.168944E+11 | ||||
Minimum of Months | 0.572263E+09 | 608.83 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.669304E+09 | 832.25 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.600134E+10 | 0.243995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544341E+10 | 0.221463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.646374E+10 | 0.260355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577805E+10 | 0.235867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623254E+10 | 0.252175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.620069E+10 | 0.250118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.580989E+10 | 0.237925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.646374E+10 | 0.260355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577805E+10 | 0.235867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.600134E+10 | 0.243995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.592974E+10 | 0.239828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.580989E+10 | 0.237925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719124E+11 | 0.291987E+12 | ||||||
Minimum of Months | 0.427861E+10 | 0.544341E+10 | 0.221463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.646374E+10 | 0.260355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.600134E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544341E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.646374E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577805E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623254E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.620069E+10 | 0.106523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.580989E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.646374E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577805E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.600134E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.592974E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.580989E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719124E+11 | 0.126597E+12 | ||||||
Minimum of Months | 0.427861E+10 | 0.544341E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.646374E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.600134E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544341E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.646374E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577805E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623254E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.620069E+10 | 0.106523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.580989E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.646374E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577805E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.600134E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.592974E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.580989E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719124E+11 | 0.126597E+12 | ||||||
Minimum of Months | 0.427861E+10 | 0.544341E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.646374E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101348E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778136E+09 |
February | 0.901968E+09 | 0.907587E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731914E+09 |
March | 0.107774E+10 | 0.105839E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718924E+09 |
April | 0.956342E+09 | 0.935935E+09 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1815652.13 | 0.520602E+09 |
May | 0.103597E+10 | 0.100468E+10 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15493143.26 | 0.358952E+09 |
June | 0.103308E+10 | 0.993489E+09 | 0.224559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70604271.69 | 0.193568E+09 |
July | 0.959235E+09 | 0.935406E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99602644.11 | 0.110226E+09 |
August | 0.107774E+10 | 0.104252E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50759244.33 | 0.145715E+09 |
September | 0.956342E+09 | 0.942551E+09 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18360883.97 | 0.212928E+09 |
October | 0.994195E+09 | 0.993582E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4562209.96 | 0.393495E+09 |
November | 0.984487E+09 | 0.100332E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629670E+09 |
December | 0.959235E+09 | 0.100072E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714181E+09 |
Annual Sum or Average | 0.119305E+11 | 0.118317E+11 | 0.266877E+11 | 0.261198E+09 | 0.550831E+10 | ||||
Minimum of Months | 0.901968E+09 | 0.907587E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110226E+09 |
Maximum of Months | 0.107774E+10 | 0.105839E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99602644.11 | 0.778136E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.639787E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525318E+09 |
February | 0.571020E+09 | 0.573800E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492141E+09 |
March | 0.682301E+09 | 0.669695E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484316E+09 |
April | 0.605444E+09 | 0.593334E+09 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1677328.20 | 0.360229E+09 |
May | 0.655854E+09 | 0.637595E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11320742.49 | 0.244983E+09 |
June | 0.654023E+09 | 0.630153E+09 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49328268.27 | 0.130122E+09 |
July | 0.607275E+09 | 0.593055E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68182187.90 | 75958803.79 |
August | 0.682301E+09 | 0.660784E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35451492.52 | 98791200.22 |
September | 0.605444E+09 | 0.596692E+09 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13696405.11 | 0.142332E+09 |
October | 0.629407E+09 | 0.627201E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3610265.39 | 0.266875E+09 |
November | 0.623262E+09 | 0.634655E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426261E+09 |
December | 0.607275E+09 | 0.631572E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480519E+09 |
Annual Sum or Average | 0.755301E+10 | 0.748832E+10 | 0.168945E+11 | 0.183267E+09 | 0.372785E+10 | ||||
Minimum of Months | 0.571020E+09 | 0.573800E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75958803.79 |
Maximum of Months | 0.682301E+09 | 0.669695E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68182187.90 | 0.525318E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100410E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844078E+09 |
February | 0.901968E+09 | 0.902952E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786109E+09 |
March | 0.107774E+10 | 0.105695E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751472E+09 |
April | 0.956342E+09 | 0.936935E+09 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1574792.29 | 0.534086E+09 |
May | 0.103597E+10 | 0.100699E+10 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15079153.00 | 0.359226E+09 |
June | 0.103308E+10 | 0.995973E+09 | 0.224557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71703929.75 | 0.191959E+09 |
July | 0.959235E+09 | 0.937263E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99813222.71 | 0.110042E+09 |
August | 0.107774E+10 | 0.104368E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49496296.76 | 0.148026E+09 |
September | 0.956342E+09 | 0.942213E+09 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15436423.57 | 0.224234E+09 |
October | 0.994195E+09 | 0.988077E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3147202.46 | 0.425595E+09 |
November | 0.984487E+09 | 0.994830E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693100E+09 |
December | 0.959235E+09 | 0.986461E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779453E+09 |
Annual Sum or Average | 0.119305E+11 | 0.117964E+11 | 0.266876E+11 | 0.256251E+09 | 0.584738E+10 | ||||
Minimum of Months | 0.901968E+09 | 0.902952E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110042E+09 |
Maximum of Months | 0.107774E+10 | 0.105695E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99813222.71 | 0.844078E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.637285E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527645E+09 |
February | 0.570983E+09 | 0.572263E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496948E+09 |
March | 0.682256E+09 | 0.669304E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485544E+09 |
April | 0.605404E+09 | 0.592087E+09 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1037723.01 | 0.357453E+09 |
May | 0.655811E+09 | 0.635960E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10263161.13 | 0.240029E+09 |
June | 0.653980E+09 | 0.629399E+09 | 0.142154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46566409.52 | 0.130821E+09 |
July | 0.607235E+09 | 0.592547E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68959652.79 | 73593806.27 |
August | 0.682256E+09 | 0.659895E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35147217.83 | 97061209.33 |
September | 0.605404E+09 | 0.596190E+09 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13142816.25 | 0.143225E+09 |
October | 0.629366E+09 | 0.627241E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3330109.99 | 0.265971E+09 |
November | 0.623221E+09 | 0.630164E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427376E+09 |
December | 0.607235E+09 | 0.627459E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484713E+09 |
Annual Sum or Average | 0.755252E+10 | 0.746979E+10 | 0.168944E+11 | 0.178447E+09 | 0.373038E+10 | ||||
Minimum of Months | 0.570983E+09 | 0.572263E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73593806.27 |
Maximum of Months | 0.682256E+09 | 0.669304E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68959652.79 | 0.527645E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101226E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450607E+09 |
February | 0.901968E+09 | 0.906869E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413911E+09 |
March | 0.107774E+10 | 0.105789E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 0.395292E+09 |
April | 0.956342E+09 | 0.935792E+09 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1527026.35 | 0.280808E+09 |
May | 0.103597E+10 | 0.100456E+10 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10025225.48 | 0.192942E+09 |
June | 0.103308E+10 | 0.993313E+09 | 0.224559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41347249.30 | 0.103969E+09 |
July | 0.959235E+09 | 0.935233E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58392325.61 | 57540686.47 |
August | 0.107774E+10 | 0.104253E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29168390.55 | 80410769.90 |
September | 0.956342E+09 | 0.942137E+09 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10173988.85 | 0.123772E+09 |
October | 0.994195E+09 | 0.992821E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413500.95 | 0.233349E+09 |
November | 0.984487E+09 | 0.100233E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378056E+09 |
December | 0.959235E+09 | 0.999671E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421796E+09 |
Annual Sum or Average | 0.119305E+11 | 0.118254E+11 | 0.266877E+11 | 0.153048E+09 | 0.313245E+10 | ||||
Minimum of Months | 0.901968E+09 | 0.906869E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57540686.47 |
Maximum of Months | 0.107774E+10 | 0.105789E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58392325.61 | 0.450607E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.639264E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306041E+09 |
February | 0.571020E+09 | 0.573498E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280948E+09 |
March | 0.682301E+09 | 0.669440E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273005E+09 |
April | 0.605444E+09 | 0.593220E+09 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 888956.31 | 0.203306E+09 |
May | 0.655854E+09 | 0.637452E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5437340.88 | 0.138903E+09 |
June | 0.654023E+09 | 0.629990E+09 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25969328.11 | 73527946.38 |
July | 0.607275E+09 | 0.592907E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35998809.48 | 43468687.32 |
August | 0.682301E+09 | 0.660681E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18339460.62 | 58430688.46 |
September | 0.605444E+09 | 0.596516E+09 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6579768.20 | 86168678.27 |
October | 0.629407E+09 | 0.626896E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1614516.83 | 0.160758E+09 |
November | 0.623262E+09 | 0.634184E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257246E+09 |
December | 0.607275E+09 | 0.631142E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284851E+09 |
Annual Sum or Average | 0.755301E+10 | 0.748519E+10 | 0.168945E+11 | 94828180.42 | 0.216665E+10 | ||||
Minimum of Months | 0.571020E+09 | 0.573498E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43468687.32 |
Maximum of Months | 0.682301E+09 | 0.669440E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35998809.48 | 0.306041E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100372E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616660E+10 |
February | 0.901968E+09 | 0.902623E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503765E+10 |
March | 0.107774E+10 | 0.105661E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426836E+10 |
April | 0.956342E+09 | 0.936717E+09 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32276628.86 | 0.248451E+10 |
May | 0.103597E+10 | 0.100676E+10 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230099E+09 | 0.175406E+10 |
June | 0.103308E+10 | 0.995593E+09 | 0.224557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132052E+10 | 0.670939E+09 |
July | 0.959235E+09 | 0.936981E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145232E+10 | 0.231736E+09 |
August | 0.107774E+10 | 0.104345E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113175E+10 | 0.539956E+09 |
September | 0.956342E+09 | 0.941848E+09 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449171E+09 | 0.972393E+09 |
October | 0.994195E+09 | 0.987858E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61791467.06 | 0.300390E+10 |
November | 0.984487E+09 | 0.994472E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500227E+10 |
December | 0.959235E+09 | 0.986062E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649925E+10 |
Annual Sum or Average | 0.119305E+11 | 0.117927E+11 | 0.266876E+11 | 0.467794E+10 | 0.366316E+11 | ||||
Minimum of Months | 0.901968E+09 | 0.902623E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231736E+09 |
Maximum of Months | 0.107774E+10 | 0.105661E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145232E+10 | 0.649925E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.636955E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306944E+09 |
February | 0.570983E+09 | 0.571968E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283910E+09 |
March | 0.682256E+09 | 0.669114E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.86 | 0.271987E+09 |
April | 0.605404E+09 | 0.591952E+09 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679244.94 | 0.200559E+09 |
May | 0.655811E+09 | 0.635862E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5302136.81 | 0.134922E+09 |
June | 0.653980E+09 | 0.629249E+09 | 0.142154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24801342.07 | 73794161.40 |
July | 0.607235E+09 | 0.592438E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36910017.44 | 41574687.15 |
August | 0.682256E+09 | 0.659763E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18450272.74 | 57448559.48 |
September | 0.605404E+09 | 0.595982E+09 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6487245.33 | 87119231.76 |
October | 0.629366E+09 | 0.626924E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1529056.53 | 0.160840E+09 |
November | 0.623221E+09 | 0.629796E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256523E+09 |
December | 0.607235E+09 | 0.626791E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286486E+09 |
Annual Sum or Average | 0.755252E+10 | 0.746679E+10 | 0.168944E+11 | 94159898.70 | 0.216211E+10 | ||||
Minimum of Months | 0.570983E+09 | 0.571968E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41574687.15 |
Maximum of Months | 0.682256E+09 | 0.669114E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36910017.44 | 0.306944E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101348E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691266E+09 |
February | 0.901968E+09 | 0.907587E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646353E+09 |
March | 0.107774E+10 | 0.105839E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632305E+09 |
April | 0.956342E+09 | 0.935935E+09 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1493002.78 | 0.453012E+09 |
May | 0.103597E+10 | 0.100468E+10 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13016672.12 | 0.311276E+09 |
June | 0.103308E+10 | 0.993489E+09 | 0.224559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59753015.85 | 0.166588E+09 |
July | 0.959235E+09 | 0.935406E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84216008.47 | 93886780.34 |
August | 0.107774E+10 | 0.104252E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42885652.69 | 0.124930E+09 |
September | 0.956342E+09 | 0.942551E+09 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15136985.50 | 0.186565E+09 |
October | 0.994195E+09 | 0.993582E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3610240.05 | 0.348856E+09 |
November | 0.984487E+09 | 0.100332E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563773E+09 |
December | 0.959235E+09 | 0.100072E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637192E+09 |
Annual Sum or Average | 0.119305E+11 | 0.118317E+11 | 0.266877E+11 | 0.220112E+09 | 0.485600E+10 | ||||
Minimum of Months | 0.901968E+09 | 0.907587E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93886780.34 |
Maximum of Months | 0.107774E+10 | 0.105839E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84216008.47 | 0.691266E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.639787E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464108E+09 |
February | 0.421807E+09 | 0.573800E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431831E+09 |
March | 0.502994E+09 | 0.669695E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420776E+09 |
April | 0.447140E+09 | 0.593334E+09 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1580664.47 | 0.308937E+09 |
May | 0.484071E+09 | 0.637595E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9760945.00 | 0.209733E+09 |
June | 0.482240E+09 | 0.630153E+09 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42330116.08 | 0.110399E+09 |
July | 0.448971E+09 | 0.593055E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58172908.98 | 63606930.52 |
August | 0.502994E+09 | 0.660784E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30439715.30 | 83192673.03 |
September | 0.447140E+09 | 0.596692E+09 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11712845.19 | 0.123063E+09 |
October | 0.465148E+09 | 0.627201E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3013211.60 | 0.232791E+09 |
November | 0.460569E+09 | 0.634655E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377468E+09 |
December | 0.448971E+09 | 0.631572E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426646E+09 |
Annual Sum or Average | 0.557719E+10 | 0.748832E+10 | 0.168945E+11 | 0.157010E+09 | 0.325255E+10 | ||||
Minimum of Months | 0.421807E+09 | 0.573800E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63606930.52 |
Maximum of Months | 0.502994E+09 | 0.669695E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58172908.98 | 0.464108E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100410E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746081E+09 |
February | 0.901968E+09 | 0.902952E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690568E+09 |
March | 0.107774E+10 | 0.105695E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656803E+09 |
April | 0.956342E+09 | 0.936935E+09 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1311488.98 | 0.463654E+09 |
May | 0.103597E+10 | 0.100699E+10 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12546043.04 | 0.311460E+09 |
June | 0.103308E+10 | 0.995973E+09 | 0.224557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60463329.20 | 0.165232E+09 |
July | 0.959235E+09 | 0.937263E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83996117.10 | 93718670.90 |
August | 0.107774E+10 | 0.104368E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41594761.39 | 0.126816E+09 |
September | 0.956342E+09 | 0.942213E+09 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12610627.73 | 0.195860E+09 |
October | 0.994195E+09 | 0.988077E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2337845.69 | 0.374375E+09 |
November | 0.984487E+09 | 0.994830E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614048E+09 |
December | 0.959235E+09 | 0.986461E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691539E+09 |
Annual Sum or Average | 0.119305E+11 | 0.117964E+11 | 0.266876E+11 | 0.214860E+09 | 0.513015E+10 | ||||
Minimum of Months | 0.901968E+09 | 0.902952E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93718670.90 |
Maximum of Months | 0.107774E+10 | 0.105695E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83996117.10 | 0.746081E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.637285E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466093E+09 |
February | 0.570983E+09 | 0.572263E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436187E+09 |
March | 0.682256E+09 | 0.669304E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423938E+09 |
April | 0.605404E+09 | 0.592088E+09 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876235.41 | 0.309864E+09 |
May | 0.655811E+09 | 0.635961E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8039959.89 | 0.208430E+09 |
June | 0.653980E+09 | 0.629399E+09 | 0.142154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38535439.55 | 0.112508E+09 |
July | 0.607235E+09 | 0.592547E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56862455.64 | 62760158.43 |
August | 0.682256E+09 | 0.659895E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29013180.71 | 83049401.21 |
September | 0.605404E+09 | 0.596190E+09 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10631728.33 | 0.125456E+09 |
October | 0.629366E+09 | 0.627242E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2582815.86 | 0.233960E+09 |
November | 0.623221E+09 | 0.630164E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379041E+09 |
December | 0.607235E+09 | 0.627459E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429837E+09 |
Annual Sum or Average | 0.755252E+10 | 0.746980E+10 | 0.168944E+11 | 0.146542E+09 | 0.327112E+10 | ||||
Minimum of Months | 0.570983E+09 | 0.572263E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62760158.43 |
Maximum of Months | 0.682256E+09 | 0.669304E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56862455.64 | 0.466093E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977871E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905835E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874439E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759192.64 | 0.619628E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14184979.24 | 0.420738E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70294804.03 | 0.220681E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103566E+09 | 0.117601E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49059369.37 | 0.164683E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14983104.04 | 0.255275E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779998.87 | 0.491003E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801675E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906924E+09 |
Annual Sum or Average | 0.255628E+09 | 0.675635E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117601E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103566E+09 | 0.977871E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121017E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113138E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110367E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886543.19 | 0.790104E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17521900.63 | 0.541684E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87103780.32 | 0.285785E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127004E+09 | 0.155855E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60393091.35 | 0.213395E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18954363.72 | 0.323222E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3550103.98 | 0.613215E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992152E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111853E+10 |
Annual Sum or Average | 0.315414E+09 | 0.847917E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155855E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127004E+09 | 0.121017E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121561E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114954E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113534E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43736.21 | 0.836399E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8637204.74 | 0.567208E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77240498.17 | 0.291147E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111614E+09 | 0.156917E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51604548.11 | 0.215715E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12765481.62 | 0.329943E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1855990.07 | 0.619193E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997281E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111497E+10 |
Annual Sum or Average | 0.263761E+09 | 0.862926E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156917E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111614E+09 | 0.121561E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6236.40 | 02-JAN-08:09 | 29385.51 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6236.40 | 01-FEB-08:09 | 29385.51 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6236.40 | 01-MAR-08:09 | 29385.51 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6236.40 | 03-APR-07:10 | 29385.51 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6236.40 | 01-MAY-07:10 | 29385.51 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6236.40 | 01-JUN-07:10 | 29385.51 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6236.40 | 03-JUL-07:10 | 29385.51 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6236.40 | 01-AUG-07:10 | 29385.51 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6236.40 | 01-SEP-07:10 | 29385.51 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6236.40 | 02-OCT-07:10 | 29385.51 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6236.40 | 01-NOV-07:10 | 29385.51 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6236.40 | 01-DEC-08:09 | 29385.51 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 6198.29 | 6236.40 | 29385.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6236.40 | 29385.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6236.40 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6236.40 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6236.40 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6236.40 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6236.40 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6236.40 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6236.40 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6236.40 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6236.40 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6236.40 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6236.40 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6236.40 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 6198.29 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6236.40 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6236.40 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6236.40 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6236.40 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6236.40 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6236.40 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6236.40 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6236.40 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6236.40 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6236.40 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6236.40 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6236.40 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 6198.29 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1222.09 | 09-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2082.28 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1126.73 | 16-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1667.14 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1031.04 | 20-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1459.96 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 961.76 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 | 01-APR-17:02 | 1706.49 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 961.76 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.12 | 14-MAY-16:50 | 1055.26 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 961.76 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.25 | 18-JUN-16:00 | 788.51 | 10-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 961.76 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.02 | 04-JUL-14:51 | 445.80 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 961.76 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.51 | 05-AUG-17:02 | 416.47 | 08-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1112.44 | 08-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.05 | 03-SEP-15:00 | 574.97 | 18-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1112.57 | 25-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.08 | 01-OCT-16:03 | 981.43 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1314.69 | 13-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1702.49 | 03-NOV-21:03 |
December | 1306.65 | 01-DEC-10:09 | 1314.69 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2316.70 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.47 | |||||
Maximum of Months | 1306.65 | 1314.69 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 659.02 | 2316.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 772.99 | 09-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1394.34 | 16-JAN-18:00 |
February | 827.22 | 01-FEB-10:09 | 704.37 | 16-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1113.43 | 05-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 620.18 | 14-MAR-15:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 974.78 | 14-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 608.87 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 | 29-APR-17:50 | 1141.64 | 23-APR-08:50 |
May | 827.22 | 01-MAY-09:09 | 608.87 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.06 | 14-MAY-16:50 | 688.96 | 03-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 608.87 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.34 | 18-JUN-16:00 | 529.96 | 04-JUN-17:00 |
July | 827.22 | 03-JUL-09:09 | 608.87 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.57 | 04-JUL-15:10 | 304.25 | 15-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 608.87 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 05-AUG-17:02 | 350.93 | 27-AUG-07:40 |
September | 827.22 | 01-SEP-09:09 | 696.84 | 08-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.69 | 03-SEP-14:40 | 389.85 | 18-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 676.70 | 25-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 01-OCT-16:40 | 648.61 | 11-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 832.31 | 13-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1118.56 | 03-NOV-21:13 |
December | 827.22 | 01-DEC-10:09 | 832.31 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1540.00 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.22 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.25 | |||||
Maximum of Months | 827.22 | 832.31 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 481.57 | 1540.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1170.17 | 04-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2188.64 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1119.28 | 16-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1758.99 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1016.32 | 20-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1500.10 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 961.76 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 01-APR-17:50 | 1726.03 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 961.76 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.25 | 14-MAY-16:50 | 1050.62 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 961.76 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.76 | 18-JUN-16:00 | 782.91 | 10-JUN-01:30 |
July | 1306.65 | 03-JUL-09:09 | 961.76 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 653.17 | 04-JUL-14:51 | 450.95 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 961.76 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.06 | 05-AUG-17:02 | 420.95 | 08-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1110.89 | 08-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.68 | 03-SEP-14:40 | 612.85 | 17-SEP-20:00 |
October | 1306.65 | 02-OCT-09:09 | 1095.42 | 25-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 01-OCT-16:00 | 1007.02 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1314.69 | 13-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1766.20 | 03-NOV-21:03 |
December | 1306.65 | 01-DEC-10:09 | 1314.69 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2404.02 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.95 | |||||
Maximum of Months | 1306.65 | 1314.69 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 653.17 | 2404.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 727.71 | 04-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1412.76 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 713.60 | 16-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1136.95 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 683.29 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 970.14 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 608.83 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 29-APR-14:50 | 1238.36 | 15-APR-17:10 |
May | 827.17 | 01-MAY-09:09 | 608.83 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.08 | 14-MAY-17:30 | 687.71 | 03-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 621.08 | 08-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.49 | 18-JUN-14:02 | 545.68 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 608.83 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.32 | 04-JUL-15:06 | 305.73 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 608.83 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.64 | 20-AUG-16:54 | 290.68 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 705.74 | 08-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.14 | 03-SEP-14:40 | 417.28 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 711.80 | 25-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.14 | 01-OCT-16:00 | 656.21 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 832.25 | 13-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1138.30 | 03-NOV-21:13 |
December | 827.17 | 01-DEC-10:09 | 832.25 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1550.17 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.17 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.68 | |||||
Maximum of Months | 827.17 | 832.25 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 425.32 | 1550.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1215.97 | 09-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1268.36 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1118.60 | 16-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 986.87 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1018.39 | 20-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 08-MAR-14:00 | 819.29 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 961.76 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 | 01-APR-17:02 | 950.77 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 961.76 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.89 | 14-MAY-17:00 | 593.79 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 961.76 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.39 | 18-JUN-16:10 | 452.46 | 10-JUN-01:40 |
July | 1306.65 | 03-JUL-09:09 | 961.76 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.25 | 04-JUL-14:51 | 234.13 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 961.76 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.65 | 05-AUG-17:02 | 238.39 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1103.68 | 08-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.44 | 03-SEP-15:10 | 347.50 | 07-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 1103.64 | 25-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.22 | 01-OCT-16:30 | 574.74 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1314.69 | 13-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1036.06 | 03-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1314.69 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1404.27 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.13 | |||||
Maximum of Months | 1306.65 | 1314.69 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 407.25 | 1404.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 769.65 | 09-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 861.89 | 16-JAN-18:00 |
February | 827.22 | 01-FEB-10:09 | 699.91 | 16-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 669.22 | 05-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 613.05 | 14-MAR-15:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 580.01 | 14-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 608.87 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 29-APR-17:20 | 652.12 | 07-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 608.87 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.25 | 14-MAY-16:40 | 399.10 | 03-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 608.87 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.13 | 18-JUN-16:10 | 308.02 | 10-JUN-01:30 |
July | 827.22 | 03-JUL-09:09 | 608.87 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.65 | 04-JUL-15:10 | 169.04 | 15-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 608.87 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.76 | 05-AUG-17:20 | 172.07 | 27-AUG-07:30 |
September | 827.22 | 01-SEP-09:09 | 692.12 | 08-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.73 | 03-SEP-15:10 | 243.33 | 18-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 670.92 | 25-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 01-OCT-16:30 | 387.00 | 11-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 832.31 | 13-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 690.17 | 03-NOV-24:00 |
December | 827.22 | 01-DEC-10:09 | 832.31 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 944.19 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.22 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.04 | |||||
Maximum of Months | 827.22 | 832.31 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 263.65 | 944.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1162.98 | 04-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 28965.53 | 30-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1110.73 | 16-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 27617.90 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1002.85 | 20-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 23478.78 | 30-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 961.76 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.00 | 13-APR-17:00 | 19332.78 | 06-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 961.76 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5802.50 | 19-MAY-16:10 | 15011.77 | 04-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 961.76 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13878.82 | 28-JUN-16:01 | 12444.30 | 09-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 961.76 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12535.73 | 21-JUL-16:01 | 4274.85 | 28-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 961.76 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10073.85 | 01-AUG-16:02 | 9187.48 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1102.05 | 08-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5757.55 | 20-SEP-16:03 | 11472.61 | 20-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1085.53 | 25-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2851.08 | 06-OCT-16:10 | 23236.27 | 26-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1314.69 | 13-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 26932.22 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1314.69 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31215.67 | 15-DEC-07:01 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4274.85 | |||||
Maximum of Months | 1306.65 | 1314.69 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13878.82 | 31215.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 723.35 | 04-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 871.21 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 709.60 | 16-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 680.44 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 678.16 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 08-MAR-14:00 | 568.78 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 608.83 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 29-APR-15:30 | 665.64 | 07-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 608.83 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.49 | 14-MAY-17:20 | 406.62 | 18-MAY-03:20 |
June | 827.17 | 01-JUN-09:09 | 614.01 | 08-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.32 | 18-JUN-14:12 | 316.99 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 608.83 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.02 | 04-JUL-14:51 | 165.67 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 608.83 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.68 | 05-AUG-17:20 | 172.14 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 701.47 | 08-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.71 | 03-SEP-15:10 | 245.71 | 18-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 707.71 | 25-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 | 01-OCT-16:10 | 393.48 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 832.25 | 13-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 705.40 | 03-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 832.25 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 950.15 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.17 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.67 | |||||
Maximum of Months | 827.17 | 832.25 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 256.02 | 950.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1222.09 | 09-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1895.28 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1126.71 | 16-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1500.00 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1031.02 | 20-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1303.92 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 961.76 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.80 | 01-APR-17:02 | 1482.35 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 961.76 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.24 | 14-MAY-16:50 | 922.93 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 961.76 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.73 | 18-JUN-16:00 | 695.25 | 10-JUN-01:30 |
July | 1306.65 | 03-JUL-09:09 | 961.76 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.09 | 04-JUL-14:51 | 363.48 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 961.76 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.18 | 05-AUG-17:02 | 356.43 | 08-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1112.42 | 08-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.56 | 03-SEP-15:10 | 504.80 | 18-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1112.55 | 25-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.82 | 01-OCT-16:30 | 852.13 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1314.69 | 13-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1508.83 | 03-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1314.69 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2089.95 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.43 | |||||
Maximum of Months | 1306.65 | 1314.69 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 581.09 | 2089.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 773.00 | 09-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1267.91 | 16-JAN-18:00 |
February | 805.43 | 01-FEB-08:09 | 704.36 | 16-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1001.24 | 05-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 620.17 | 14-MAR-15:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 866.31 | 14-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 608.87 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.84 | 29-APR-17:50 | 979.16 | 07-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 608.87 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.77 | 14-MAY-16:50 | 600.03 | 03-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 608.87 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.40 | 18-JUN-16:20 | 456.07 | 10-JUN-01:40 |
July | 805.43 | 03-JUL-07:10 | 608.87 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.17 | 04-JUL-15:10 | 247.75 | 15-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 608.87 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.16 | 05-AUG-17:20 | 299.64 | 27-AUG-07:40 |
September | 805.43 | 01-SEP-07:10 | 696.83 | 08-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.92 | 03-SEP-15:10 | 340.76 | 18-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 676.69 | 25-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.78 | 01-OCT-16:30 | 561.29 | 11-OCT-23:00 |
November | 805.43 | 01-NOV-07:10 | 832.31 | 13-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 994.50 | 03-NOV-24:00 |
December | 805.43 | 01-DEC-08:09 | 832.31 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1386.45 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.75 | |||||
Maximum of Months | 805.43 | 832.31 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 418.17 | 1386.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1170.16 | 04-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1983.39 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1119.26 | 16-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1576.75 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1016.30 | 20-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1335.39 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 961.76 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 01-APR-17:30 | 1496.76 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 961.76 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.09 | 14-MAY-16:50 | 918.90 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 961.76 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.73 | 18-JUN-16:00 | 690.79 | 10-JUN-01:30 |
July | 1306.65 | 03-JUL-09:09 | 961.76 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.05 | 04-JUL-14:51 | 368.32 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 961.76 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.49 | 05-AUG-17:02 | 361.19 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1110.88 | 08-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.52 | 03-SEP-14:30 | 530.45 | 18-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1095.41 | 25-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.74 | 11-OCT-15:00 | 873.69 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1314.69 | 13-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1550.29 | 03-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1314.69 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2167.35 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.19 | |||||
Maximum of Months | 1306.65 | 1314.69 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 575.05 | 2167.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 727.71 | 04-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1283.55 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 713.59 | 16-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1021.31 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 683.28 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 865.40 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 608.83 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 29-APR-14:40 | 1056.74 | 15-APR-17:10 |
May | 827.17 | 01-MAY-09:09 | 608.83 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.32 | 14-MAY-13:00 | 602.99 | 03-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 621.07 | 08-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.17 | 18-JUN-13:52 | 480.09 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 608.83 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.05 | 04-JUL-14:51 | 250.06 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 608.83 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.40 | 05-AUG-17:20 | 249.19 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 705.73 | 08-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.55 | 03-SEP-15:10 | 356.06 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 711.80 | 25-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.47 | 01-OCT-15:47 | 569.73 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 832.25 | 13-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1012.50 | 03-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 832.25 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1394.63 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.17 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.19 | |||||
Maximum of Months | 827.17 | 832.25 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 361.05 | 1394.63 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2747.52 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2177.63 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1848.21 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.81 | 01-APR-17:02 | 2054.27 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.13 | 14-MAY-17:00 | 1258.73 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.38 | 18-JUN-15:52 | 964.48 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.04 | 04-JUL-14:51 | 460.71 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.88 | 05-AUG-17:02 | 469.53 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.62 | 03-SEP-14:50 | 696.16 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 01-OCT-16:10 | 1167.79 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2163.37 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3036.70 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.71 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.04 | 3036.70 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3338.34 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2703.53 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2321.41 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 | 01-APR-17:02 | 2616.82 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.53 | 14-MAY-17:00 | 1599.71 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.51 | 18-JUN-16:00 | 1221.44 | 10-JUN-01:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.69 | 04-JUL-14:51 | 596.10 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.62 | 05-AUG-17:02 | 599.88 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.03 | 03-SEP-14:50 | 877.36 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.92 | 01-OCT-16:00 | 1477.71 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2698.98 | 03-NOV-24:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3765.17 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.10 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.69 | 3765.17 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3338.65 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2573.15 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2240.70 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 29-APR-16:00 | 2647.51 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.87 | 14-MAY-17:00 | 1595.39 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.99 | 18-JUN-16:00 | 1307.53 | 04-JUN-17:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 793.50 | 04-JUL-14:51 | 725.12 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.69 | 20-AUG-17:00 | 597.92 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.13 | 03-SEP-15:00 | 897.04 | 17-SEP-20:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.70 | 01-OCT-16:00 | 1494.66 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2739.15 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3597.40 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 793.50 | 3597.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26698.54 | 26-JAN-08:02 | 60350.08 | 62364.02 | 293855.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27330.80 | 01-FEB-08:03 | 60350.08 | 62364.02 | 293855.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26184.19 | 31-MAR-08:00 | 6035.01 | 6236.40 | 29385.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37786.55 | 14-APR-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43269.10 | 31-MAY-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51111.47 | 29-JUN-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51700.63 | 21-JUL-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 51529.23 | 18-AUG-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44908.81 | 23-SEP-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38592.13 | 24-OCT-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38219.61 | 02-NOV-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27518.61 | 07-DEC-08:02 | 60350.08 | 62364.02 | 293855.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26184.19 | 0.00 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51700.63 | 60350.08 | 62364.02 | 293855.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2277.94 | 01-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.77 |
February | 3976.04 | 15-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.74 |
March | 4618.72 | 08-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.60 |
April | 6910.11 | 28-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 |
May | 8234.91 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 0.00 |
June | 9993.97 | 29-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.48 | 0.00 |
July | 9849.56 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.80 | 0.00 |
August | 9828.69 | 07-AUG-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 0.00 |
September | 8003.59 | 12-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.38 | 0.00 |
October | 6820.89 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3693.41 | 02-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.01 |
December | 2181.78 | 31-DEC-14:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2181.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9993.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.48 | 261.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1364.82 | 28-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 |
February | 1526.02 | 11-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.36 |
March | 1602.51 | 18-MAR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2357.11 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
May | 2889.42 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.66 | 0.00 |
June | 3936.67 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.73 | 0.00 |
July | 3960.32 | 05-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 0.00 |
August | 3988.36 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 | 0.00 |
September | 3358.59 | 05-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
October | 3323.60 | 02-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 0.00 |
November | 1838.30 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.73 |
December | 1399.96 | 30-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1364.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3988.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.73 | 454.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2035.90 | 06-JAN-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.25 |
February | 2311.58 | 15-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.86 |
March | 2198.45 | 18-MAR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2865.16 | 28-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 0.00 |
May | 3485.98 | 29-MAY-11:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 |
June | 4433.41 | 29-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.99 | 0.00 |
July | 4456.64 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.25 | 0.00 |
August | 4389.64 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.69 | 0.00 |
September | 3996.23 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 | 0.00 |
October | 3963.79 | 06-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 0.00 |
November | 3179.98 | 01-NOV-16:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.10 |
December | 2031.60 | 14-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.65 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2031.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4456.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.99 | 352.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11183.32 | 26-JAN-17:00 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13483.97 | 15-FEB-17:00 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12674.27 | 31-MAR-16:00 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24041.36 | 28-APR-05:03 | 2541.06 | 2771.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29252.46 | 22-MAY-04:02 | 0.00 | 4687.79 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31702.40 | 28-JUN-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31789.31 | 06-JUL-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31830.92 | 10-AUG-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30453.47 | 05-SEP-04:02 | 0.00 | 4687.79 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29442.47 | 02-OCT-04:02 | 0.00 | 4687.79 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20598.45 | 01-NOV-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11399.69 | 01-DEC-16:30 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11183.32 | 0.00 | 2771.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31830.92 | 6035.01 | 6236.40 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9145.02 | 26-JAN-16:50 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13245.12 | 15-FEB-17:00 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13046.43 | 08-MAR-17:00 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17502.25 | 28-APR-15:00 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29126.31 | 22-MAY-05:02 | 3176.32 | 3464.67 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32984.70 | 29-JUN-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33493.77 | 05-JUL-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33665.74 | 21-AUG-04:01 | 0.00 | 5469.09 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31088.04 | 05-SEP-04:02 | 0.00 | 4687.79 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29412.66 | 02-OCT-05:02 | 3811.58 | 4157.60 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14727.57 | 01-NOV-15:50 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9165.54 | 01-DEC-16:20 | 6035.01 | 6236.40 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9145.02 | 0.00 | 3464.67 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33665.74 | 6035.01 | 6236.40 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2023.27 | 05-JAN-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 |
February | 2489.09 | 14-FEB-16:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 |
March | 2782.43 | 16-MAR-15:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.56 |
April | 4940.29 | 28-APR-15:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
May | 5540.23 | 31-MAY-15:20 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 55.29 | 0.00 |
June | 7213.73 | 29-JUN-15:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 166.60 | 0.00 |
July | 9310.91 | 04-JUL-17:01 | 0.00 | 481.96 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 549.58 | 0.00 |
August | 6820.89 | 07-AUG-14:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 39.28 | 0.00 |
September | 5610.42 | 12-SEP-14:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 | 0.00 |
October | 5150.75 | 02-OCT-13:40 | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 0.00 |
November | 2357.24 | 02-NOV-15:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 |
December | 1873.26 | 01-DEC-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1873.26 | 0.00 | 481.96 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9310.91 | 1306.65 | 961.76 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 549.58 | 90.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2118.66 | 05-JAN-15:50 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 |
February | 3674.04 | 14-FEB-09:20 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 |
March | 4855.81 | 31-MAR-08:30 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.41 |
April | 11242.72 | 30-APR-08:32 | 211.95 | 169.13 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.69 |
May | 12278.69 | 14-MAY-09:12 | 211.95 | 169.13 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.67 |
June | 12348.34 | 18-JUN-08:32 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 |
July | 12592.75 | 04-JUL-08:22 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 |
August | 12596.96 | 20-AUG-08:12 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 |
September | 12348.41 | 03-SEP-09:52 | 211.95 | 169.13 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
October | 6380.18 | 02-OCT-08:20 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 |
November | 4678.85 | 01-NOV-08:50 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.91 |
December | 2034.23 | 29-DEC-09:20 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2034.23 | 211.95 | 169.13 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12596.96 | 805.43 | 608.87 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 442.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9671.34 | 15-JAN-14:43 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.24 |
February | 9980.45 | 12-FEB-12:23 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.22 |
March | 8540.93 | 08-MAR-13:20 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 |
April | 6834.76 | 27-APR-13:30 | 1306.65 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
May | 6127.09 | 31-MAY-14:20 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 58.36 | 0.00 |
June | 7731.01 | 29-JUN-14:40 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 154.34 | 0.00 |
July | 10832.46 | 30-JUL-16:11 | 535.68 | 427.45 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 256.72 | 0.00 |
August | 9096.45 | 31-AUG-12:40 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | 0.00 |
September | 10945.51 | 03-SEP-13:13 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 126.75 | 0.00 |
October | 12634.80 | 01-OCT-11:12 | 334.80 | 267.16 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.60 |
November | 10372.74 | 19-NOV-14:02 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.38 |
December | 10232.77 | 31-DEC-14:32 | 334.80 | 267.16 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6127.09 | 267.84 | 213.72 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12634.80 | 1306.65 | 961.76 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 256.72 | 405.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4425.57 | 26-JAN-16:30 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 |
February | 6565.99 | 15-FEB-16:30 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 |
March | 9117.50 | 12-MAR-16:32 | 211.94 | 169.12 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.98 |
April | 12083.23 | 16-APR-16:32 | 211.94 | 169.12 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.93 |
May | 13433.08 | 20-MAY-17:42 | 254.33 | 202.94 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 |
June | 14487.31 | 25-JUN-16:41 | 296.72 | 236.77 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 188.37 | 0.00 |
July | 15219.52 | 30-JUL-16:11 | 339.11 | 270.59 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.64 | 0.00 |
August | 14286.68 | 20-AUG-17:31 | 0.00 | 266.96 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 126.25 | 0.00 |
September | 12889.78 | 02-SEP-17:04 | 296.72 | 236.77 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 58.65 | 0.00 |
October | 12307.82 | 09-OCT-16:12 | 254.33 | 202.94 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 |
November | 5758.95 | 02-NOV-16:00 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 |
December | 3499.50 | 29-DEC-16:10 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3499.50 | 0.00 | 169.12 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15219.52 | 805.38 | 608.83 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.37 | 150.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1642.43 | 05-JAN-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 |
February | 1931.33 | 14-FEB-16:50 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 |
March | 1974.64 | 16-MAR-14:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 |
April | 3193.05 | 14-APR-14:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 |
May | 3875.26 | 31-MAY-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 0.00 |
June | 5664.18 | 29-JUN-15:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 91.45 | 0.00 |
July | 5462.99 | 25-JUL-15:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 43.31 | 0.00 |
August | 5576.69 | 07-AUG-14:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 0.00 |
September | 4802.12 | 05-SEP-13:40 | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
October | 4492.33 | 02-OCT-13:50 | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 0.00 |
November | 2331.73 | 02-NOV-15:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 |
December | 1641.79 | 01-DEC-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1641.79 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5664.18 | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 91.45 | 35.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1808.27 | 05-JAN-14:10 | 827.22 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 |
February | 2666.57 | 14-FEB-08:30 | 1610.86 | 1217.75 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 |
March | 3539.40 | 31-MAR-08:70 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.12 |
April | 9091.47 | 30-APR-07:42 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 |
May | 9597.25 | 29-MAY-08:42 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 |
June | 8276.23 | 18-JUN-08:32 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.61 |
July | 10272.88 | 09-JUL-08:52 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 |
August | 11061.33 | 20-AUG-08:61 | 339.13 | 270.61 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
September | 10740.90 | 03-SEP-08:21 | 296.74 | 236.78 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 |
October | 9232.52 | 01-OCT-08:22 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.79 |
November | 4463.35 | 01-NOV-08:70 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.27 |
December | 1796.84 | 29-DEC-09:00 | 1610.86 | 1217.75 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1796.84 | 254.35 | 202.96 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11061.33 | 1610.86 | 1217.75 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9055.25 | 01-JAN-14:13 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.90 |
February | 7890.17 | 14-FEB-14:25 | 2613.31 | 1923.52 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.67 |
March | 5772.69 | 08-MAR-13:10 | 2544.47 | 1923.52 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.94 |
April | 4858.76 | 13-APR-16:50 | 401.76 | 534.31 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.58 | 0.00 |
May | 8127.33 | 19-MAY-16:20 | 401.76 | 534.31 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5650.87 | 0.00 |
June | 10222.93 | 28-JUN-16:40 | 401.76 | 534.31 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 10568.24 | 0.00 |
July | 10223.92 | 21-JUL-17:00 | 401.76 | 534.31 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 10222.47 | 0.00 |
August | 9401.43 | 01-AUG-16:10 | 2008.79 | 2671.56 | 4183.01 | 0.00 | 0.00 | 0.00 | 0.00 | 8513.84 | 0.00 |
September | 9931.34 | 03-SEP-13:02 | 334.80 | 267.16 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 63.37 | 0.00 |
October | 10794.58 | 01-OCT-13:01 | 468.72 | 374.02 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
November | 8834.28 | 19-NOV-13:53 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.06 |
December | 8656.55 | 31-DEC-14:22 | 334.80 | 267.16 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4858.76 | 267.84 | 213.72 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10794.58 | 2613.31 | 2671.56 | 4183.01 | 0.00 | 0.00 | 0.00 | 0.00 | 10568.24 | 536.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3607.96 | 26-JAN-16:30 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 |
February | 5138.15 | 15-FEB-16:40 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 |
March | 4865.69 | 07-MAR-17:00 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 |
April | 6195.55 | 26-APR-17:00 | 254.33 | 338.24 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 0.00 |
May | 9591.10 | 20-MAY-17:42 | 254.33 | 202.94 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
June | 11480.87 | 18-JUN-18:42 | 0.00 | 228.82 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 0.00 |
July | 11471.58 | 04-JUL-17:41 | 0.00 | 266.96 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 124.37 | 0.00 |
August | 11831.34 | 20-AUG-18:01 | 0.00 | 266.96 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 46.20 | 0.00 |
September | 11237.05 | 04-SEP-17:22 | 0.00 | 228.82 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 |
October | 10470.39 | 15-OCT-16:52 | 211.94 | 169.12 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5536.24 | 02-NOV-16:00 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 |
December | 2966.88 | 29-DEC-16:10 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2966.88 | 0.00 | 169.12 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11831.34 | 805.38 | 608.83 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 124.37 | 30.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1857.30 | 05-JAN-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 |
February | 2303.10 | 15-FEB-16:20 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 |
March | 2926.40 | 27-MAR-14:40 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.62 |
April | 4641.49 | 14-APR-14:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
May | 5093.42 | 31-MAY-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 65.12 | 0.00 |
June | 7447.13 | 29-JUN-05:02 | 803.52 | 641.17 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
July | 7581.19 | 24-JUL-04:01 | 0.00 | 1152.93 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 |
August | 6606.65 | 22-AUG-04:01 | 0.00 | 1152.93 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
September | 5153.38 | 12-SEP-14:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 0.00 |
October | 4853.50 | 02-OCT-13:40 | 1306.65 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 0.00 |
November | 2607.70 | 02-NOV-15:30 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 |
December | 1768.68 | 01-DEC-16:00 | 1272.23 | 961.76 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1768.68 | 0.00 | 641.17 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7581.19 | 1306.65 | 1152.93 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.12 | 64.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2885.87 | 27-JAN-09:30 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4708.96 | 14-FEB-09:05 | 1610.86 | 1217.75 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 |
March | 7366.36 | 26-MAR-09:02 | 169.56 | 135.31 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.03 |
April | 11479.95 | 30-APR-07:42 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.75 |
May | 12379.31 | 29-MAY-08:42 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.16 |
June | 12405.08 | 18-JUN-07:52 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13023.44 | 02-JUL-08:52 | 254.35 | 202.96 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 |
August | 13900.48 | 20-AUG-08:61 | 339.13 | 270.61 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
September | 13319.65 | 03-SEP-08:21 | 296.74 | 236.78 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 |
October | 11714.89 | 01-OCT-09:02 | 211.95 | 169.13 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.60 |
November | 5435.02 | 01-NOV-08:50 | 805.43 | 608.87 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
December | 2705.79 | 29-DEC-08:55 | 1610.86 | 1217.75 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2705.79 | 169.56 | 135.31 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13900.48 | 1610.86 | 1217.75 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9734.95 | 01-JAN-14:13 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.01 |
February | 9702.43 | 19-FEB-14:02 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.87 |
March | 8283.13 | 08-MAR-13:30 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 |
April | 6455.15 | 27-APR-13:10 | 1306.65 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
May | 5597.77 | 31-MAY-14:20 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 0.00 |
June | 7012.77 | 29-JUN-14:40 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 128.72 | 0.00 |
July | 8242.66 | 24-JUL-04:01 | 0.00 | 1152.93 | 4684.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.27 |
August | 8380.77 | 31-AUG-12:40 | 1272.23 | 961.76 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.75 | 0.00 |
September | 10904.17 | 03-SEP-13:02 | 334.80 | 267.16 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 81.39 | 0.00 |
October | 11817.01 | 01-OCT-12:21 | 468.72 | 374.02 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
November | 9032.58 | 19-NOV-14:23 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.00 |
December | 9112.75 | 24-DEC-14:13 | 267.84 | 213.72 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5597.77 | 0.00 | 213.72 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11817.01 | 1306.65 | 1152.93 | 4684.97 | 0.00 | 0.00 | 0.00 | 0.00 | 128.72 | 415.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4756.18 | 26-JAN-16:30 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.39 |
February | 6646.06 | 15-FEB-16:30 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 |
March | 9523.93 | 12-MAR-16:42 | 211.94 | 169.12 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.74 |
April | 11921.69 | 16-APR-16:32 | 211.94 | 169.12 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 |
May | 13243.25 | 29-MAY-16:42 | 254.33 | 202.94 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 |
June | 14297.43 | 11-JUN-17:01 | 0.00 | 305.10 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
July | 13793.18 | 04-JUL-17:01 | 0.00 | 305.10 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.84 | 0.00 |
August | 13790.02 | 20-AUG-18:01 | 0.00 | 266.96 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 67.31 | 0.00 |
September | 13035.65 | 04-SEP-17:22 | 0.00 | 228.82 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
October | 12457.08 | 01-OCT-15:42 | 254.33 | 202.94 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 26.86 | 0.00 |
November | 5968.30 | 02-NOV-16:00 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 |
December | 3816.43 | 29-DEC-16:10 | 805.38 | 608.83 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3816.43 | 0.00 | 169.12 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14297.43 | 805.38 | 608.83 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.84 | 137.74 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.124369E+12 | 133187.08 | 17-JAN-08:09 | 0.186716E+11 | 49369.40 | 21-JAN-07:10 |
February | 0.109754E+12 | 128543.64 | 06-FEB-08:09 | 0.130104E+11 | 44507.07 | 04-FEB-07:10 |
March | 0.124478E+12 | 107758.60 | 08-MAR-13:00 | 0.881626E+10 | 26907.33 | 04-MAR-07:10 |
April | 0.120880E+12 | 124074.58 | 13-APR-15:00 | 0.651438E+10 | 14300.68 | 08-APR-06:10 |
May | 0.136575E+12 | 137053.48 | 19-MAY-15:00 | 0.626153E+10 | 9155.83 | 01-MAY-11:39 |
June | 0.158627E+12 | 172369.45 | 28-JUN-15:00 | 0.581157E+10 | 9023.63 | 01-JUN-11:09 |
July | 0.167903E+12 | 166494.89 | 21-JUL-15:39 | 0.540837E+10 | 8911.84 | 03-JUL-11:20 |
August | 0.173183E+12 | 157071.12 | 18-AUG-15:00 | 0.575070E+10 | 8881.90 | 30-AUG-11:50 |
September | 0.144740E+12 | 147906.65 | 05-SEP-12:00 | 0.544743E+10 | 8959.80 | 29-SEP-11:50 |
October | 0.131422E+12 | 137323.68 | 06-OCT-15:30 | 0.696505E+10 | 29925.80 | 26-OCT-06:00 |
November | 0.115897E+12 | 103830.38 | 27-NOV-08:09 | 0.853745E+10 | 37617.72 | 27-NOV-07:10 |
December | 0.120983E+12 | 114988.63 | 26-DEC-08:09 | 0.177496E+11 | 49033.91 | 15-DEC-07:10 |
Annual Sum or Average | 0.162881E+13 | 0.108944E+12 | ||||
Minimum of Months | 0.109754E+12 | 103830.38 | 0.540837E+10 | 8881.90 | ||
Maximum of Months | 0.173183E+12 | 172369.45 | 0.186716E+11 | 49369.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.278855E+11 | 0.104551E+11 | 0.677417E+11 | 0.158645E+10 | 0.638748E+10 | 1312252.29 | 0.100806E+11 | 0.231340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251984E+11 | 0.881479E+10 | 0.613762E+11 | 0.143569E+10 | 0.597733E+10 | 1186777.96 | 0.597824E+10 | 0.972568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297529E+11 | 0.885132E+10 | 0.709808E+11 | 0.166266E+10 | 0.718412E+10 | 1343620.87 | 0.245098E+10 | 0.359331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265084E+11 | 0.763594E+10 | 0.654362E+11 | 0.152741E+10 | 0.765990E+10 | 1267813.46 | 0.672816E+09 | 0.114384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.285527E+11 | 0.710421E+10 | 0.693613E+11 | 0.162434E+10 | 0.874791E+10 | 1327936.58 | 0.418742E+09 | 0.207643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.283483E+11 | 0.649532E+10 | 0.683191E+11 | 0.159957E+10 | 0.109735E+11 | 1296568.00 | 74869617.92 | 0.428153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.266038E+11 | 0.688287E+10 | 0.664783E+11 | 0.155210E+10 | 0.116270E+11 | 1299182.04 | 0.00 | 0.547578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.296114E+11 | 0.753278E+10 | 0.709808E+11 | 0.166256E+10 | 0.121502E+11 | 1343620.87 | 7257255.37 | 0.512362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265659E+11 | 0.817364E+10 | 0.654362E+11 | 0.152745E+10 | 0.990058E+10 | 1267813.46 | 66546194.94 | 0.330688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277107E+11 | 0.938902E+10 | 0.677417E+11 | 0.158627E+10 | 0.921760E+10 | 1312252.29 | 0.900404E+09 | 0.148751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275759E+11 | 0.989896E+10 | 0.663434E+11 | 0.155757E+10 | 0.770209E+10 | 1278269.66 | 0.201089E+10 | 0.806486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271658E+11 | 0.106795E+11 | 0.664783E+11 | 0.155270E+10 | 0.657565E+10 | 1299182.04 | 0.853009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331480E+12 | 0.101913E+12 | 0.806674E+12 | 0.188748E+11 | 0.104103E+12 | 15535289.52 | 0.311914E+11 | 0.234560E+12 | |||||
Minimum of Months | 0.251984E+11 | 0.649532E+10 | 0.613762E+11 | 0.143569E+10 | 0.597733E+10 | 1186777.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.297529E+11 | 0.106795E+11 | 0.709808E+11 | 0.166266E+10 | 0.121502E+11 | 1343620.87 | 0.100806E+11 | 0.547578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.118279E+11 | 0.00 | 0.684374E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.675911E+10 | 0.00 | 0.625130E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.170153E+10 | 0.00 | 0.711473E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.262727E+09 | 0.00 | 0.625165E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 14681285.05 | 0.00 | 0.624684E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.581157E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.540837E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.575070E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.544743E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104677E+10 | 0.00 | 0.591828E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.238683E+10 | 0.00 | 0.615061E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.112442E+11 | 0.00 | 0.650542E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.352437E+11 | 0.737007E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.540837E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.118279E+11 | 0.00 | 0.711473E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30311.62 | 04-JAN-16:00 | 7792.78 | 01-JAN-06:10 | 58427.47 | 02-JAN-08:09 | 1345.63 | 04-JAN-16:00 | 9594.33 | 26-JAN-16:30 | 0.73 | 02-JAN-08:20 | 70779.27 | 17-JAN-07:10 |
February | 29675.95 | 16-FEB-08:09 | 7792.78 | 01-FEB-06:10 | 58427.47 | 01-FEB-08:09 | 1347.20 | 16-FEB-08:20 | 9567.50 | 15-FEB-16:19 | 0.73 | 01-FEB-06:10 | 72843.53 | 06-FEB-07:10 |
March | 28658.70 | 20-MAR-07:10 | 7792.78 | 01-MAR-06:10 | 58427.47 | 01-MAR-08:09 | 1345.07 | 20-MAR-07:19 | 8430.34 | 10-MAR-16:00 | 0.73 | 01-MAR-17:10 | 32590.69 | 06-MAR-07:10 |
April | 28132.89 | 03-APR-07:10 | 7792.78 | 01-APR-05:10 | 58427.47 | 03-APR-07:10 | 1343.97 | 03-APR-07:19 | 10456.32 | 13-APR-15:00 | 0.73 | 01-APR-17:10 | 11061.19 | 08-APR-06:10 |
May | 28132.89 | 01-MAY-07:10 | 7792.78 | 01-MAY-05:10 | 58427.47 | 01-MAY-07:10 | 1343.97 | 01-MAY-07:19 | 12558.26 | 19-MAY-15:00 | 0.73 | 02-MAY-06:10 | 7824.58 | 05-MAY-06:10 |
June | 28162.55 | 08-JUN-07:10 | 7792.78 | 01-JUN-19:10 | 58427.47 | 01-JUN-07:10 | 1344.03 | 08-JUN-07:19 | 17589.28 | 28-JUN-15:00 | 0.73 | 04-JUN-12:39 | 5793.62 | 09-JUN-06:10 |
July | 28132.89 | 03-JUL-07:10 | 7792.78 | 01-JUL-19:19 | 58427.47 | 03-JUL-07:10 | 1343.97 | 03-JUL-07:19 | 17221.37 | 21-JUL-15:00 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 28132.89 | 01-AUG-07:10 | 7792.78 | 01-AUG-05:10 | 58427.47 | 01-AUG-07:10 | 1343.97 | 01-AUG-07:19 | 16288.22 | 07-AUG-15:30 | 0.73 | 01-AUG-05:10 | 1956.53 | 31-AUG-06:10 |
September | 29560.30 | 08-SEP-07:10 | 7792.78 | 01-SEP-05:10 | 58427.47 | 01-SEP-07:10 | 1346.95 | 08-SEP-07:19 | 14110.26 | 13-SEP-15:09 | 0.73 | 01-SEP-05:10 | 4822.99 | 25-SEP-06:19 |
October | 29469.95 | 25-OCT-07:10 | 7792.78 | 01-OCT-05:10 | 58427.47 | 02-OCT-07:10 | 1346.77 | 25-OCT-07:19 | 14239.12 | 06-OCT-15:30 | 0.73 | 01-OCT-08:20 | 26988.05 | 26-OCT-06:10 |
November | 31591.01 | 13-NOV-16:00 | 7792.78 | 01-NOV-05:10 | 58427.47 | 01-NOV-07:10 | 1348.55 | 29-NOV-16:00 | 14515.01 | 01-NOV-15:39 | 0.73 | 01-NOV-17:10 | 46836.78 | 27-NOV-07:10 |
December | 31591.01 | 01-DEC-16:00 | 7792.78 | 01-DEC-06:10 | 58427.47 | 01-DEC-08:09 | 1349.06 | 05-DEC-16:00 | 8634.49 | 29-DEC-16:10 | 0.73 | 05-DEC-06:10 | 62561.19 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 28132.89 | 7792.78 | 58427.47 | 1343.97 | 8430.34 | 0.73 | 0.00 | |||||||
Maximum of Months | 31591.01 | 7792.78 | 58427.47 | 1349.06 | 17589.28 | 0.73 | 72843.53 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 6345.93 | 05-JAN-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20846.59 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20470.60 | 08-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33129.35 | 13-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44006.32 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74291.26 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69090.69 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 60315.62 | 18-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54536.23 | 05-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42629.55 | 02-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12699.59 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 133187.08 | 17-JAN-08:09 | 28191.22 | 58427.47 | 0.00 | 1305.46 | 3828.66 | 0.73 | 41433.54 | 0.00 | 0.00 |
February | 128543.64 | 06-FEB-08:09 | 28132.89 | 58427.47 | 0.00 | 1305.27 | 3782.20 | 0.73 | 36895.08 | 0.00 | 0.00 |
March | 107758.60 | 08-MAR-13:00 | 28132.89 | 51658.15 | 0.00 | 1342.02 | 6190.55 | 0.73 | 0.00 | 20434.27 | 0.00 |
April | 124074.58 | 13-APR-15:00 | 28132.89 | 51013.45 | 0.00 | 1341.84 | 10456.32 | 0.73 | 0.00 | 33129.35 | 0.00 |
May | 137053.48 | 19-MAY-15:00 | 28132.89 | 51013.45 | 0.00 | 1341.84 | 12558.26 | 0.73 | 0.00 | 44006.32 | 0.00 |
June | 172369.45 | 28-JUN-15:00 | 28132.89 | 51013.45 | 0.00 | 1341.84 | 17589.28 | 0.73 | 0.00 | 74291.26 | 0.00 |
July | 166494.89 | 21-JUL-15:39 | 28132.89 | 51013.45 | 0.00 | 1341.84 | 16974.71 | 0.73 | 0.00 | 69031.28 | 0.00 |
August | 157071.12 | 18-AUG-15:00 | 28132.89 | 51013.45 | 0.00 | 1341.84 | 16266.59 | 0.73 | 0.00 | 60315.62 | 0.00 |
September | 147906.65 | 05-SEP-12:00 | 28132.89 | 51658.15 | 0.00 | 1342.02 | 12236.64 | 0.73 | 0.00 | 54536.23 | 0.00 |
October | 137323.68 | 06-OCT-15:30 | 28132.89 | 51013.45 | 0.00 | 1341.84 | 14239.12 | 0.73 | 0.00 | 42595.66 | 0.00 |
November | 103830.38 | 27-NOV-08:09 | 28132.89 | 58427.47 | 0.00 | 1305.27 | 4786.19 | 0.73 | 11177.83 | 0.00 | 0.00 |
December | 114988.63 | 26-DEC-08:09 | 28222.53 | 58427.47 | 0.00 | 1305.61 | 3895.89 | 0.73 | 23136.40 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 103830.38 | 28132.89 | 51013.45 | 0.00 | 1305.27 | 3782.20 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 172369.45 | 28222.53 | 58427.47 | 0.00 | 1342.02 | 17589.28 | 0.73 | 41433.54 | 74291.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 48213.40 | 21-JAN-07:10 | 0.00 | 9400.92 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 43351.07 | 04-FEB-07:10 | 0.00 | 9403.44 | 03-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 25751.33 | 04-MAR-07:10 | 0.00 | 9388.04 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 13144.68 | 08-APR-06:10 | 0.00 | 9282.00 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 2829.61 | 06-MAY-06:10 | 0.00 | 9155.83 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9023.63 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8911.84 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8881.90 | 30-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8959.80 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 28769.80 | 26-OCT-06:00 | 0.00 | 9088.95 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 36461.72 | 27-NOV-07:10 | 0.00 | 9235.12 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 47877.91 | 15-DEC-07:10 | 0.00 | 9338.71 | 28-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8881.90 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 48213.40 | 0.00 | 9403.44 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.29 | 2.67 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.33 | 19.23 | 2.00 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.21 | 0.17 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.51 | 1.00 | 19.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6.50 | 19.30 | 5.83 | 19.58 | 0.33 | 27.30 | 0.33 | 27.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.51 | 2.67 | 19.63 | 0.33 | 27.30 | 0.33 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 16.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 16.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.03 | 0.83 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.88 | 3.00 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.24 | 3.00 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.19 | 7.33 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.21 | 4.00 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.09 | 1.17 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.82 | 0.33 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 16.86 | 0.00 | 19.83 | 28.14 | 19.67 | 28.14 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.24 | 0.00 | 0.00 | 7.50 | 28.24 | 7.33 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.21 | 0.83 | 19.68 | 27.17 | 25.07 | 27.17 | 25.07 |
February | 0.83 | 19.18 | 0.67 | 19.75 | 18.17 | 24.96 | 18.17 | 24.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.46 | 7.50 | 25.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 25.34 | 34.17 | 25.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 25.20 | 48.50 | 25.20 |
December | 0.33 | 19.34 | 0.33 | 19.34 | 30.33 | 24.98 | 30.33 | 24.98 |
Annual Sum or Average | 2.17 | 19.22 | 1.83 | 19.64 | 166.67 | 25.16 | 166.67 | 25.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.34 | 0.83 | 19.75 | 48.50 | 27.33 | 48.50 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 16.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 16.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.80 | 1.17 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.05 | 1.83 | 28.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.71 | 2.00 | 28.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.44 | 3.17 | 28.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.48 | 1.67 | 28.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 1.67 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.47 | 0.83 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 16.70 | 0.00 | 19.83 | 28.28 | 12.33 | 28.24 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 16.70 | 0.00 | 0.00 | 5.17 | 28.71 | 3.17 | 28.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.63 | 1.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.74 | 4.50 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.75 | 2.83 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.82 | 0.83 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.67 | 27.70 | 10.67 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 4.50 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.83 | 17.12 | 52.83 | 17.12 | 1.33 | 27.45 | 1.33 | 27.45 |
February | 43.33 | 17.65 | 43.33 | 17.65 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35.50 | 18.01 | 35.50 | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21.00 | 18.85 | 21.00 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10.00 | 19.58 | 10.00 | 19.58 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1.00 | 19.77 | 1.00 | 19.77 | 25.33 | 25.47 | 25.33 | 25.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 25.43 | 28.17 | 25.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 25.29 | 22.50 | 25.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 25.08 | 16.00 | 25.08 |
October | 15.00 | 18.36 | 15.00 | 18.36 | 39.67 | 25.21 | 39.67 | 25.21 |
November | 21.83 | 18.19 | 21.83 | 18.19 | 8.67 | 25.63 | 8.67 | 25.63 |
December | 50.17 | 17.47 | 50.17 | 17.47 | 4.33 | 26.34 | 4.33 | 26.34 |
Annual Sum or Average | 250.67 | 17.83 | 250.67 | 17.83 | 146.00 | 25.38 | 146.00 | 25.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.83 | 19.77 | 52.83 | 19.77 | 39.67 | 27.45 | 39.67 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.57 | 0.17 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.74 | 0.33 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.07 | 1.33 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.97 | 1.50 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.89 | 0.83 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.69 | 0.67 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.45 | 0.33 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 27.92 | 5.17 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.07 | 1.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.37 | 0.33 | 19.37 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.08 | 1.00 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.96 | 3.50 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.24 | 3.17 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.41 | 6.00 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.25 | 4.00 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.00 | 1.67 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.64 | 1.00 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.50 | 28.18 | 20.50 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.41 | 6.00 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 25.48 | 59.83 | 25.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 25.25 | 40.67 | 25.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.60 | 10.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 | 25.34 | 73.83 | 25.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 | 25.55 | 89.17 | 25.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 79.00 | 25.36 | 79.00 | 25.36 |
Annual Sum or Average | 0.00 | 0.00 | 352.67 | 25.42 | 352.67 | 25.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 | 27.28 | 89.17 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.80 | 1.17 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.16 | 1.50 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.64 | 2.17 | 28.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.37 | 2.67 | 28.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.36 | 1.50 | 28.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.85 | 1.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 1.17 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 28.24 | 11.67 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.64 | 2.67 | 28.70 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.00 | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 389.67 | 23.78 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 327.67 | 23.83 | 1.17 | 25.11 | 0.00 | 0.00 |
April | 239.67 | 23.78 | 5.33 | 25.56 | 0.00 | 0.00 |
May | 145.00 | 23.72 | 90.17 | 24.65 | 0.00 | 0.00 |
June | 47.00 | 23.50 | 253.00 | 24.35 | 0.00 | 0.00 |
July | 8.67 | 23.59 | 385.17 | 24.18 | 0.00 | 0.00 |
August | 3.33 | 23.56 | 420.33 | 24.20 | 0.00 | 0.00 |
September | 14.33 | 23.58 | 321.17 | 24.34 | 0.00 | 0.00 |
October | 125.50 | 23.76 | 113.33 | 24.57 | 0.00 | 0.00 |
November | 240.00 | 23.84 | 9.50 | 25.15 | 0.00 | 0.00 |
December | 470.33 | 23.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2492.17 | 23.76 | 1599.17 | 24.31 | 0.00 | |
Minimum of Months | 3.33 | 23.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.00 | 23.84 | 420.33 | 25.56 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.07 | 1.17 | 20.96 | 1.17 | 20.96 |
February | 448.67 | 23.36 | 1.83 | 20.99 | 1.83 | 20.99 |
March | 494.33 | 23.68 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 362.33 | 23.87 | 1.50 | 25.36 | 0.00 | 0.00 |
May | 199.17 | 23.85 | 65.33 | 24.48 | 0.00 | 0.00 |
June | 43.83 | 23.70 | 230.00 | 24.36 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 451.17 | 24.25 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 454.83 | 24.25 | 0.00 | 0.00 |
September | 16.17 | 23.61 | 277.17 | 24.38 | 0.00 | 0.00 |
October | 239.67 | 23.80 | 82.50 | 24.39 | 0.00 | 0.00 |
November | 443.00 | 23.71 | 1.00 | 25.26 | 0.00 | 0.00 |
December | 497.00 | 23.19 | 0.17 | 21.05 | 0.17 | 21.05 |
Annual Sum or Average | 3246.17 | 23.51 | 1566.67 | 24.30 | 3.17 | 20.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.87 | 454.83 | 25.36 | 1.83 | 21.05 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.13 | 91.83 | 20.74 | 91.83 | 20.74 |
February | 454.00 | 22.58 | 36.17 | 20.76 | 36.17 | 20.76 |
March | 504.33 | 23.20 | 5.83 | 21.05 | 5.83 | 21.05 |
April | 380.17 | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 226.33 | 23.69 | 55.67 | 24.38 | 0.00 | 0.00 |
June | 56.33 | 23.62 | 237.67 | 24.29 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 453.00 | 24.26 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 447.17 | 24.24 | 0.00 | 0.00 |
September | 72.67 | 23.53 | 230.83 | 24.25 | 0.00 | 0.00 |
October | 328.33 | 23.42 | 60.00 | 24.16 | 0.00 | 0.00 |
November | 467.50 | 23.01 | 6.17 | 20.86 | 6.17 | 20.86 |
December | 497.00 | 22.16 | 89.00 | 20.76 | 89.00 | 20.76 |
Annual Sum or Average | 3488.67 | 22.91 | 1713.33 | 23.79 | 229.00 | 20.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 504.33 | 23.69 | 453.00 | 24.38 | 91.83 | 21.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.80 | 304.67 | 20.27 | 304.67 | 20.27 |
February | 454.00 | 21.22 | 170.83 | 20.31 | 170.83 | 20.31 |
March | 512.33 | 22.08 | 77.17 | 20.48 | 77.17 | 20.48 |
April | 400.67 | 22.92 | 18.00 | 21.08 | 17.17 | 20.86 |
May | 267.00 | 23.18 | 62.00 | 24.36 | 2.00 | 20.98 |
June | 88.67 | 23.23 | 249.67 | 24.30 | 0.00 | 0.00 |
July | 11.67 | 24.17 | 434.17 | 24.32 | 7.67 | 24.75 |
August | 31.00 | 23.30 | 411.67 | 24.24 | 3.17 | 24.26 |
September | 158.33 | 23.15 | 206.50 | 24.16 | 0.00 | 0.00 |
October | 401.83 | 22.51 | 75.17 | 22.85 | 26.83 | 20.72 |
November | 482.83 | 21.61 | 119.50 | 20.36 | 119.50 | 20.36 |
December | 497.00 | 20.73 | 325.33 | 20.32 | 325.33 | 20.32 |
Annual Sum or Average | 3807.33 | 21.87 | 2454.67 | 22.60 | 1054.33 | 20.39 |
Minimum of Months | 11.67 | 20.73 | 18.00 | 20.27 | 0.00 | 0.00 |
Maximum of Months | 512.33 | 24.17 | 434.17 | 24.36 | 325.33 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.02 | 228.33 | 20.37 | 228.33 | 20.37 |
February | 446.67 | 21.39 | 116.33 | 20.18 | 116.33 | 20.18 |
March | 461.50 | 22.09 | 57.00 | 21.12 | 48.50 | 20.33 |
April | 254.83 | 22.70 | 74.17 | 24.49 | 10.50 | 21.62 |
May | 214.50 | 23.00 | 162.83 | 24.61 | 11.67 | 25.93 |
June | 85.00 | 23.35 | 326.33 | 24.36 | 10.50 | 26.89 |
July | 71.67 | 24.69 | 417.00 | 24.46 | 36.33 | 26.48 |
August | 77.17 | 23.80 | 408.50 | 24.31 | 21.67 | 26.39 |
September | 156.67 | 22.82 | 272.50 | 24.21 | 5.83 | 26.56 |
October | 336.00 | 22.35 | 118.83 | 23.84 | 19.50 | 21.03 |
November | 471.83 | 21.77 | 66.17 | 20.44 | 64.33 | 20.34 |
December | 497.00 | 20.90 | 248.50 | 20.33 | 248.50 | 20.33 |
Annual Sum or Average | 3574.83 | 21.92 | 2496.50 | 23.21 | 822.00 | 20.99 |
Minimum of Months | 71.67 | 20.90 | 57.00 | 20.18 | 5.83 | 20.18 |
Maximum of Months | 502.00 | 24.69 | 417.00 | 24.61 | 248.50 | 26.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 362.00 | 21.58 | 199.83 | 22.07 | 131.00 | 20.33 |
February | 308.67 | 21.78 | 143.00 | 22.20 | 88.33 | 20.37 |
March | 380.50 | 22.26 | 81.17 | 21.80 | 58.83 | 20.51 |
April | 330.33 | 22.90 | 27.33 | 23.07 | 15.50 | 20.87 |
May | 268.00 | 23.10 | 71.83 | 24.37 | 2.33 | 20.96 |
June | 110.33 | 23.13 | 241.67 | 24.29 | 0.00 | 0.00 |
July | 25.83 | 23.73 | 419.67 | 24.32 | 8.67 | 24.81 |
August | 40.00 | 23.44 | 413.67 | 24.27 | 6.17 | 25.21 |
September | 129.00 | 23.33 | 284.83 | 24.38 | 9.67 | 26.23 |
October | 242.50 | 22.82 | 191.00 | 24.44 | 28.83 | 23.03 |
November | 305.83 | 22.26 | 145.17 | 23.78 | 49.00 | 20.76 |
December | 342.67 | 21.60 | 202.17 | 21.97 | 132.50 | 20.28 |
Annual Sum or Average | 2845.67 | 22.35 | 2421.33 | 23.69 | 530.83 | 20.79 |
Minimum of Months | 25.83 | 21.58 | 27.33 | 21.80 | 0.00 | 0.00 |
Maximum of Months | 380.50 | 23.73 | 419.67 | 24.44 | 132.50 | 26.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.00 | 20.93 | 263.00 | 20.29 | 263.00 | 20.29 |
February | 414.33 | 21.16 | 154.33 | 20.47 | 150.00 | 20.34 |
March | 454.17 | 21.60 | 103.17 | 21.45 | 79.00 | 20.47 |
April | 367.83 | 22.36 | 72.00 | 23.96 | 16.33 | 21.45 |
May | 335.33 | 22.59 | 103.50 | 24.37 | 8.00 | 24.57 |
June | 183.17 | 22.76 | 235.50 | 24.38 | 9.33 | 26.97 |
July | 110.33 | 23.09 | 336.17 | 24.25 | 17.17 | 26.01 |
August | 127.17 | 22.81 | 326.33 | 24.20 | 9.33 | 26.09 |
September | 237.83 | 22.54 | 176.33 | 24.22 | 6.17 | 26.42 |
October | 381.67 | 22.03 | 96.33 | 23.32 | 29.83 | 21.01 |
November | 444.83 | 21.39 | 110.00 | 20.55 | 103.83 | 20.32 |
December | 489.33 | 20.95 | 276.00 | 20.33 | 276.00 | 20.33 |
Annual Sum or Average | 4035.00 | 21.75 | 2252.67 | 22.70 | 968.00 | 20.66 |
Minimum of Months | 110.33 | 20.93 | 72.00 | 20.29 | 6.17 | 20.29 |
Maximum of Months | 489.33 | 23.09 | 336.17 | 24.38 | 276.00 | 26.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.10 | 241.67 | 20.58 | 241.67 | 20.58 |
February | 454.00 | 21.33 | 141.50 | 20.59 | 141.50 | 20.59 |
March | 514.00 | 21.94 | 55.17 | 20.72 | 55.17 | 20.72 |
April | 477.83 | 22.94 | 0.67 | 20.86 | 0.67 | 20.86 |
May | 383.00 | 23.36 | 29.83 | 24.43 | 0.00 | 0.00 |
June | 110.17 | 23.46 | 194.83 | 24.25 | 0.00 | 0.00 |
July | 3.50 | 24.61 | 439.50 | 24.25 | 3.50 | 24.61 |
August | 4.00 | 24.23 | 442.83 | 24.22 | 2.33 | 24.79 |
September | 55.50 | 23.57 | 261.33 | 24.25 | 0.00 | 0.00 |
October | 359.00 | 23.24 | 56.83 | 24.09 | 0.00 | 0.00 |
November | 478.17 | 22.50 | 7.83 | 20.70 | 7.83 | 20.70 |
December | 497.00 | 21.29 | 205.17 | 20.73 | 205.17 | 20.73 |
Annual Sum or Average | 3838.17 | 22.20 | 2077.17 | 23.11 | 657.83 | 20.68 |
Minimum of Months | 3.50 | 21.10 | 0.67 | 20.58 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 24.61 | 442.83 | 24.43 | 241.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.41 | 112.83 | 20.57 | 112.83 | 20.57 |
February | 451.17 | 21.65 | 70.17 | 20.49 | 70.17 | 20.49 |
March | 474.33 | 22.31 | 20.50 | 21.95 | 15.50 | 20.50 |
April | 268.83 | 23.09 | 35.67 | 25.48 | 0.00 | 0.00 |
May | 194.50 | 23.23 | 142.00 | 24.82 | 1.67 | 26.10 |
June | 48.50 | 23.33 | 342.33 | 24.43 | 2.67 | 26.19 |
July | 24.50 | 26.29 | 460.83 | 24.46 | 24.17 | 26.33 |
August | 22.00 | 25.30 | 469.67 | 24.35 | 14.83 | 26.36 |
September | 54.50 | 23.51 | 347.33 | 24.37 | 4.50 | 26.58 |
October | 245.50 | 23.11 | 132.83 | 24.54 | 1.00 | 23.25 |
November | 452.83 | 22.72 | 8.17 | 23.98 | 2.00 | 20.36 |
December | 497.00 | 21.55 | 91.33 | 20.66 | 91.33 | 20.66 |
Annual Sum or Average | 3235.67 | 22.29 | 2233.67 | 23.96 | 340.67 | 21.39 |
Minimum of Months | 22.00 | 21.41 | 8.17 | 20.49 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 26.29 | 469.67 | 25.48 | 112.83 | 26.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.33 | 21.35 | 127.67 | 20.84 | 91.67 | 18.69 |
February | 368.50 | 21.58 | 78.83 | 20.79 | 55.17 | 18.43 |
March | 468.67 | 21.88 | 62.00 | 20.19 | 51.50 | 18.89 |
April | 447.83 | 22.53 | 21.83 | 19.09 | 21.83 | 19.09 |
May | 417.67 | 22.79 | 24.00 | 23.60 | 5.67 | 19.32 |
June | 167.33 | 23.00 | 160.83 | 24.51 | 0.00 | 0.00 |
July | 16.00 | 23.15 | 428.67 | 24.36 | 4.17 | 24.45 |
August | 29.67 | 22.69 | 444.67 | 24.34 | 8.00 | 23.98 |
September | 51.17 | 22.73 | 357.83 | 24.53 | 7.00 | 24.84 |
October | 161.50 | 22.42 | 229.67 | 24.64 | 20.17 | 21.95 |
November | 280.83 | 22.47 | 93.00 | 24.19 | 18.50 | 18.76 |
December | 367.67 | 21.59 | 90.83 | 21.04 | 60.00 | 18.28 |
Annual Sum or Average | 3168.17 | 22.12 | 2119.83 | 23.75 | 343.67 | 19.16 |
Minimum of Months | 16.00 | 21.35 | 21.83 | 19.09 | 0.00 | 0.00 |
Maximum of Months | 468.67 | 23.15 | 444.67 | 24.64 | 91.67 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.17 | 21.31 | 147.00 | 20.60 | 147.00 | 20.60 |
February | 434.67 | 21.55 | 81.67 | 20.62 | 81.67 | 20.62 |
March | 474.00 | 21.88 | 34.67 | 21.70 | 28.17 | 20.62 |
April | 390.83 | 22.78 | 25.33 | 25.12 | 0.00 | 0.00 |
May | 336.00 | 22.93 | 66.17 | 24.69 | 0.17 | 26.23 |
June | 123.50 | 22.95 | 252.17 | 24.42 | 2.50 | 26.61 |
July | 29.67 | 23.67 | 395.50 | 24.27 | 8.00 | 25.81 |
August | 19.83 | 23.83 | 425.83 | 24.23 | 5.50 | 25.89 |
September | 76.17 | 23.27 | 292.50 | 24.39 | 3.50 | 26.42 |
October | 290.83 | 22.95 | 96.17 | 24.38 | 1.00 | 23.31 |
November | 442.83 | 22.38 | 11.50 | 23.45 | 3.83 | 20.69 |
December | 494.17 | 21.49 | 119.17 | 20.73 | 119.17 | 20.73 |
Annual Sum or Average | 3611.67 | 22.14 | 1947.67 | 23.63 | 400.50 | 20.92 |
Minimum of Months | 19.83 | 21.31 | 11.50 | 20.60 | 0.00 | 0.00 |
Maximum of Months | 499.17 | 23.83 | 425.83 | 25.12 | 147.00 | 26.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.35 | 171.33 | 20.48 | 171.33 | 20.48 |
February | 454.00 | 21.81 | 84.67 | 20.52 | 84.67 | 20.52 |
March | 511.67 | 22.64 | 12.50 | 20.59 | 12.50 | 20.59 |
April | 404.83 | 23.36 | 0.67 | 25.51 | 0.00 | 0.00 |
May | 234.67 | 23.52 | 62.67 | 24.44 | 0.00 | 0.00 |
June | 60.50 | 23.55 | 256.00 | 24.33 | 0.00 | 0.00 |
July | 6.33 | 24.72 | 465.17 | 24.32 | 6.33 | 24.72 |
August | 5.00 | 24.18 | 447.83 | 24.25 | 3.17 | 24.63 |
September | 81.33 | 23.44 | 245.83 | 24.22 | 0.00 | 0.00 |
October | 359.50 | 23.03 | 58.67 | 24.00 | 1.33 | 20.73 |
November | 474.00 | 22.37 | 25.17 | 20.60 | 25.17 | 20.60 |
December | 497.00 | 21.32 | 198.50 | 20.62 | 198.50 | 20.62 |
Annual Sum or Average | 3590.83 | 22.35 | 2029.00 | 23.37 | 503.00 | 20.63 |
Minimum of Months | 5.00 | 21.32 | 0.67 | 20.48 | 0.00 | 0.00 |
Maximum of Months | 511.67 | 24.72 | 465.17 | 25.51 | 198.50 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.00 | 21.35 | 111.33 | 20.47 | 111.33 | 20.47 |
February | 368.83 | 21.62 | 60.17 | 20.64 | 57.33 | 20.36 |
March | 381.50 | 22.21 | 28.83 | 23.23 | 11.83 | 20.42 |
April | 242.00 | 22.87 | 64.17 | 25.13 | 2.67 | 25.79 |
May | 208.17 | 23.13 | 129.33 | 24.85 | 11.33 | 26.73 |
June | 92.17 | 23.39 | 250.83 | 24.49 | 10.67 | 26.90 |
July | 66.83 | 24.68 | 331.83 | 24.56 | 32.00 | 26.61 |
August | 73.50 | 23.78 | 323.83 | 24.40 | 18.33 | 26.61 |
September | 137.67 | 22.92 | 211.67 | 24.33 | 6.83 | 26.64 |
October | 286.17 | 22.54 | 89.33 | 24.44 | 5.00 | 22.70 |
November | 381.67 | 22.05 | 25.67 | 22.29 | 16.67 | 20.43 |
December | 420.00 | 21.31 | 133.67 | 20.55 | 133.67 | 20.55 |
Annual Sum or Average | 3084.50 | 22.18 | 1760.67 | 23.78 | 417.67 | 21.71 |
Minimum of Months | 66.83 | 21.31 | 25.67 | 20.47 | 2.67 | 20.36 |
Maximum of Months | 426.00 | 24.68 | 331.83 | 25.13 | 133.67 | 26.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 339.17 | 22.14 | 167.50 | 23.53 | 74.00 | 20.85 |
February | 286.83 | 22.34 | 109.83 | 24.00 | 32.50 | 20.79 |
March | 359.50 | 22.77 | 38.50 | 24.31 | 7.00 | 20.58 |
April | 316.67 | 23.33 | 11.83 | 26.07 | 0.00 | 0.00 |
May | 231.33 | 23.44 | 70.00 | 24.49 | 0.00 | 0.00 |
June | 80.00 | 23.43 | 245.33 | 24.32 | 0.00 | 0.00 |
July | 6.00 | 24.65 | 448.67 | 24.32 | 6.00 | 24.65 |
August | 6.33 | 23.99 | 443.50 | 24.28 | 3.17 | 24.58 |
September | 70.67 | 23.90 | 318.17 | 24.44 | 12.33 | 26.21 |
October | 201.17 | 23.44 | 208.67 | 25.02 | 19.67 | 26.25 |
November | 270.50 | 22.97 | 141.83 | 25.51 | 15.50 | 24.58 |
December | 317.00 | 22.23 | 173.67 | 23.76 | 65.67 | 20.95 |
Annual Sum or Average | 2485.17 | 22.84 | 2377.50 | 24.36 | 235.83 | 21.99 |
Minimum of Months | 6.00 | 22.14 | 11.83 | 23.53 | 0.00 | 0.00 |
Maximum of Months | 359.50 | 24.65 | 448.67 | 26.07 | 74.00 | 26.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.17 | 21.27 | 151.00 | 20.45 | 151.00 | 20.45 |
February | 407.50 | 21.55 | 81.33 | 20.76 | 76.67 | 20.52 |
March | 450.83 | 22.01 | 43.33 | 22.91 | 19.00 | 20.54 |
April | 358.83 | 22.70 | 57.00 | 24.80 | 1.83 | 26.10 |
May | 314.33 | 22.90 | 99.50 | 24.52 | 4.67 | 26.83 |
June | 162.00 | 22.99 | 235.67 | 24.43 | 8.17 | 27.15 |
July | 87.17 | 23.30 | 342.83 | 24.27 | 14.67 | 26.10 |
August | 95.33 | 23.03 | 340.17 | 24.22 | 8.50 | 26.05 |
September | 197.50 | 22.82 | 201.83 | 24.30 | 6.00 | 26.41 |
October | 357.83 | 22.45 | 81.00 | 24.23 | 5.33 | 22.21 |
November | 431.00 | 21.88 | 38.17 | 21.49 | 29.50 | 20.51 |
December | 475.50 | 21.29 | 166.17 | 20.59 | 166.17 | 20.59 |
Annual Sum or Average | 3819.00 | 22.08 | 1838.00 | 23.42 | 491.50 | 21.07 |
Minimum of Months | 87.17 | 21.27 | 38.17 | 20.45 | 1.83 | 20.45 |
Maximum of Months | 481.17 | 23.30 | 342.83 | 24.80 | 166.17 | 27.15 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.69088 | 15.28175 | 0.09233 | 5.51189 |
February | 454.00000 | 23.85132 | 16.15700 | 0.14510 | 5.68214 |
March | 514.00000 | 23.99683 | 15.73663 | 0.19412 | 5.96873 |
April | 485.00000 | 24.13049 | 13.87507 | 0.23182 | 6.32983 |
May | 508.00000 | 24.11643 | 21.58647 | -0.5781 | 12.52441 |
June | 496.00000 | 24.09937 | 31.38952 | -0.4893 | 10.48757 |
July | 497.00000 | 24.06600 | 40.12487 | -0.4305 | 9.29145 |
August | 514.00000 | 24.10306 | 40.16995 | -0.4137 | 8.95691 |
September | 485.00000 | 24.15828 | 35.57921 | -0.4422 | 9.54096 |
October | 502.00000 | 24.14771 | 22.27218 | 0.31141 | 7.33830 |
November | 489.00000 | 24.11171 | 16.24275 | 0.23520 | 6.35617 |
December | 497.00000 | 23.81438 | 13.26506 | 0.11584 | 5.50744 |
Annual Sum or Average | 5943.00000 | 24.02465 | 23.54388 | -0.0882 | 7.81206 |
Minimum of Months | 454.00000 | 23.69088 | 13.26506 | -0.5781 | 5.50744 |
Maximum of Months | 514.00000 | 24.15828 | 40.16995 | 0.31141 | 12.52441 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.06158 | 17.64507 | -0.0764 | 5.76531 |
February | 454.00000 | 23.36695 | 18.38838 | 0.00805 | 5.55032 |
March | 514.00000 | 23.70380 | 17.46379 | 0.10127 | 5.52915 |
April | 485.00000 | 24.01640 | 14.94071 | 0.18063 | 5.88481 |
May | 508.00000 | 24.09907 | 22.48929 | -0.6234 | 13.62018 |
June | 496.00000 | 24.16439 | 32.20295 | -0.5072 | 10.74901 |
July | 497.00000 | 24.22230 | 40.82991 | -0.4179 | 8.90920 |
August | 514.00000 | 24.21631 | 40.90214 | -0.4196 | 8.93221 |
September | 485.00000 | 24.20253 | 36.43684 | -0.4746 | 10.07818 |
October | 502.00000 | 24.04781 | 23.42332 | 0.25330 | 6.71711 |
November | 489.00000 | 23.76138 | 18.03342 | 0.11899 | 5.60509 |
December | 497.00000 | 23.18867 | 15.73262 | -0.0573 | 5.62427 |
Annual Sum or Average | 5943.00000 | 23.84066 | 24.93858 | -0.1615 | 7.76978 |
Minimum of Months | 454.00000 | 23.06158 | 14.94071 | -0.6234 | 5.52915 |
Maximum of Months | 514.00000 | 24.22230 | 40.90214 | 0.25330 | 13.62018 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.11282 | 18.54430 | -0.3085 | 8.31509 |
February | 454.00000 | 22.56585 | 19.19881 | -0.1869 | 7.04058 |
March | 514.00000 | 23.21024 | 18.06932 | -0.0201 | 5.80543 |
April | 485.00000 | 23.78122 | 15.00438 | 0.12416 | 5.74504 |
May | 508.00000 | 23.97276 | 22.24654 | -0.6617 | 14.87270 |
June | 496.00000 | 24.12543 | 32.11474 | -0.5060 | 10.77011 |
July | 497.00000 | 24.23488 | 40.73499 | -0.3949 | 8.51650 |
August | 514.00000 | 24.19963 | 40.88117 | -0.4110 | 8.77967 |
September | 485.00000 | 24.06270 | 36.27915 | -0.5206 | 11.10208 |
October | 502.00000 | 23.66514 | 23.86740 | 0.15440 | 6.28925 |
November | 489.00000 | 23.04652 | 19.20305 | -0.0604 | 6.05964 |
December | 497.00000 | 22.15355 | 16.61437 | -0.3112 | 8.28691 |
Annual Sum or Average | 5943.00000 | 23.43389 | 25.29077 | -0.2597 | 8.48177 |
Minimum of Months | 454.00000 | 22.11282 | 15.00438 | -0.6617 | 5.74504 |
Maximum of Months | 514.00000 | 24.23488 | 40.88117 | 0.15440 | 14.87270 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78414 | 19.35136 | -0.6282 | 14.83413 |
February | 454.00000 | 21.20571 | 20.45024 | -0.5008 | 11.93132 |
March | 514.00000 | 22.06893 | 19.37713 | -0.2711 | 8.13633 |
April | 485.00000 | 23.11961 | 15.87155 | -0.0134 | 6.31090 |
May | 508.00000 | 23.62455 | 23.17580 | -0.7544 | 18.76452 |
June | 496.00000 | 24.02225 | 32.41048 | -0.5049 | 11.34538 |
July | 497.00000 | 24.22820 | 41.43790 | -0.3522 | 8.22923 |
August | 514.00000 | 24.10247 | 41.56021 | -0.4071 | 9.06939 |
September | 485.00000 | 23.77496 | 37.47347 | -0.5936 | 13.57746 |
October | 502.00000 | 22.79232 | 25.31755 | -0.0390 | 6.96842 |
November | 489.00000 | 21.63061 | 20.22032 | -0.3826 | 9.75506 |
December | 497.00000 | 20.71368 | 17.64749 | -0.6570 | 15.36576 |
Annual Sum or Average | 5943.00000 | 22.68358 | 26.25011 | -0.4253 | 11.19097 |
Minimum of Months | 454.00000 | 20.71368 | 15.87155 | -0.7544 | 6.31090 |
Maximum of Months | 514.00000 | 24.22820 | 41.56021 | -0.0134 | 18.76452 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.00843 | 18.46739 | -0.5477 | 12.66760 |
February | 454.00000 | 21.41844 | 19.57842 | -0.4135 | 10.53817 |
March | 514.00000 | 22.30525 | 18.39739 | -0.1649 | 7.68436 |
April | 485.00000 | 23.45097 | 14.82322 | 0.13897 | 7.35641 |
May | 508.00000 | 23.70208 | 22.37608 | -0.6176 | 16.54283 |
June | 496.00000 | 24.03668 | 32.06588 | -0.3772 | 10.11432 |
July | 497.00000 | 24.24025 | 40.94617 | -0.2344 | 8.50967 |
August | 514.00000 | 24.05621 | 41.18494 | -0.3075 | 8.99256 |
September | 485.00000 | 23.67112 | 37.10130 | -0.5217 | 13.24780 |
October | 502.00000 | 22.95018 | 24.47436 | 0.05454 | 7.66156 |
November | 489.00000 | 21.83610 | 19.33084 | -0.2965 | 8.50347 |
December | 497.00000 | 20.88230 | 16.86857 | -0.5857 | 13.49603 |
Annual Sum or Average | 5943.00000 | 22.80697 | 25.52793 | -0.3226 | 10.44422 |
Minimum of Months | 454.00000 | 20.88230 | 14.82322 | -0.6176 | 7.35641 |
Maximum of Months | 514.00000 | 24.24025 | 41.18494 | 0.13897 | 16.54283 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.43903 | 17.04900 | -0.1772 | 11.23411 |
February | 454.00000 | 22.61822 | 18.15107 | -0.1093 | 10.01238 |
March | 514.00000 | 22.75171 | 18.02935 | -0.0762 | 7.92268 |
April | 485.00000 | 23.29939 | 15.29883 | 0.04821 | 6.62571 |
May | 508.00000 | 23.59363 | 23.07309 | -0.7540 | 18.98736 |
June | 496.00000 | 23.95286 | 32.49205 | -0.5228 | 11.98756 |
July | 497.00000 | 24.19751 | 41.43620 | -0.3535 | 8.41914 |
August | 514.00000 | 24.11703 | 41.33566 | -0.3782 | 8.86735 |
September | 485.00000 | 23.99066 | 36.52398 | -0.4604 | 11.69434 |
October | 502.00000 | 23.65650 | 23.34022 | 0.22941 | 9.46638 |
November | 489.00000 | 23.17558 | 17.72609 | 0.04493 | 9.29740 |
December | 497.00000 | 22.50403 | 15.29357 | -0.1584 | 11.18823 |
Annual Sum or Average | 5943.00000 | 23.36270 | 25.04856 | -0.2241 | 10.48885 |
Minimum of Months | 454.00000 | 22.43903 | 15.29357 | -0.7540 | 6.62571 |
Maximum of Months | 514.00000 | 24.19751 | 41.43620 | 0.22941 | 18.98736 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.99266 | 18.32412 | -0.5548 | 13.87135 |
February | 454.00000 | 21.40381 | 19.42812 | -0.4177 | 11.49319 |
March | 514.00000 | 21.89903 | 18.68994 | -0.2590 | 8.81728 |
April | 485.00000 | 22.81902 | 15.42974 | -0.0122 | 7.44723 |
May | 508.00000 | 23.12369 | 23.32918 | -0.8114 | 22.56937 |
June | 496.00000 | 23.59813 | 33.03056 | -0.5393 | 14.49480 |
July | 497.00000 | 23.78555 | 42.24254 | -0.4003 | 10.81756 |
August | 514.00000 | 23.67721 | 42.25021 | -0.4440 | 11.49012 |
September | 485.00000 | 23.27512 | 38.00242 | -0.6497 | 17.16807 |
October | 502.00000 | 22.52161 | 24.99661 | -0.0364 | 7.83853 |
November | 489.00000 | 21.62533 | 19.37601 | -0.3432 | 9.81391 |
December | 497.00000 | 20.97362 | 16.61150 | -0.5717 | 14.16128 |
Annual Sum or Average | 5943.00000 | 22.48274 | 26.04155 | -0.4206 | 12.51234 |
Minimum of Months | 454.00000 | 20.97362 | 15.42974 | -0.8114 | 7.44723 |
Maximum of Months | 514.00000 | 23.78555 | 42.25021 | -0.0122 | 22.56937 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.09500 | 19.35560 | -0.5443 | 11.89254 |
February | 454.00000 | 21.31948 | 20.54446 | -0.4793 | 10.58057 |
March | 514.00000 | 21.93522 | 19.91534 | -0.3208 | 7.92569 |
April | 485.00000 | 22.94719 | 16.86373 | -0.0815 | 5.89527 |
May | 508.00000 | 23.55370 | 24.26547 | -0.8253 | 20.51508 |
June | 496.00000 | 24.00968 | 32.66974 | -0.5583 | 12.11105 |
July | 497.00000 | 24.20558 | 41.14003 | -0.4039 | 8.64955 |
August | 514.00000 | 24.16863 | 41.21477 | -0.4176 | 8.87194 |
September | 485.00000 | 24.08893 | 37.14006 | -0.5064 | 10.79576 |
October | 502.00000 | 23.47225 | 24.74100 | 0.11580 | 6.21472 |
November | 489.00000 | 22.52817 | 19.57528 | -0.1714 | 6.44805 |
December | 497.00000 | 21.28548 | 17.17304 | -0.5007 | 10.84714 |
Annual Sum or Average | 5943.00000 | 22.89435 | 26.27652 | -0.3915 | 10.07812 |
Minimum of Months | 454.00000 | 21.09500 | 16.86373 | -0.8253 | 5.89527 |
Maximum of Months | 514.00000 | 24.20558 | 41.21477 | 0.11580 | 20.51508 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40230 | 18.17650 | -0.4394 | 9.82050 |
February | 454.00000 | 21.66118 | 19.34011 | -0.3593 | 8.78274 |
March | 514.00000 | 22.47931 | 18.47099 | -0.1454 | 6.79031 |
April | 485.00000 | 23.65705 | 15.10453 | 0.15548 | 6.64986 |
May | 508.00000 | 23.92917 | 22.62740 | -0.5913 | 14.60193 |
June | 496.00000 | 24.20271 | 31.72910 | -0.3690 | 9.09250 |
July | 497.00000 | 24.38729 | 40.08895 | -0.2273 | 7.31543 |
August | 514.00000 | 24.27085 | 40.35837 | -0.2655 | 7.49780 |
September | 485.00000 | 24.13293 | 36.37958 | -0.3848 | 9.27717 |
October | 502.00000 | 23.70130 | 23.58766 | 0.22925 | 7.45039 |
November | 489.00000 | 22.83247 | 18.35508 | -0.0593 | 5.97071 |
December | 497.00000 | 21.54378 | 16.08711 | -0.4076 | 9.17211 |
Annual Sum or Average | 5943.00000 | 23.19322 | 25.08524 | -0.2388 | 8.54244 |
Minimum of Months | 454.00000 | 21.40230 | 15.10453 | -0.5913 | 5.97071 |
Maximum of Months | 514.00000 | 24.38729 | 40.35837 | 0.22925 | 14.60193 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.09140 | 16.42631 | -0.1918 | 10.85796 |
February | 454.00000 | 22.15157 | 17.83724 | -0.1733 | 9.65268 |
March | 514.00000 | 22.11389 | 18.20922 | -0.2036 | 8.32539 |
April | 485.00000 | 22.66242 | 15.59299 | -0.1032 | 6.77755 |
May | 508.00000 | 23.04942 | 23.48884 | -0.9548 | 26.17337 |
June | 496.00000 | 23.84468 | 31.69640 | -0.6127 | 14.32876 |
July | 497.00000 | 24.24240 | 41.11151 | -0.3851 | 8.64573 |
August | 514.00000 | 24.18830 | 41.15966 | -0.3799 | 8.73875 |
September | 485.00000 | 24.23308 | 35.89976 | -0.3778 | 9.67409 |
October | 502.00000 | 23.88979 | 22.52870 | 0.31546 | 10.18490 |
November | 489.00000 | 23.34128 | 16.89727 | 0.13937 | 8.10713 |
December | 497.00000 | 22.35065 | 14.10033 | -0.1239 | 9.87988 |
Annual Sum or Average | 5943.00000 | 23.18521 | 24.65083 | -0.2564 | 10.98277 |
Minimum of Months | 454.00000 | 22.09140 | 14.10033 | -0.9548 | 6.77755 |
Maximum of Months | 514.00000 | 24.24240 | 41.15966 | 0.31546 | 26.17337 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.31943 | 18.11588 | -0.4578 | 10.44632 |
February | 454.00000 | 21.65056 | 19.20882 | -0.3599 | 9.13516 |
March | 514.00000 | 22.07253 | 18.76276 | -0.2408 | 7.58392 |
April | 485.00000 | 23.07698 | 15.68799 | 0.01325 | 6.25102 |
May | 508.00000 | 23.40023 | 23.63030 | -0.7778 | 19.83394 |
June | 496.00000 | 23.88406 | 32.56158 | -0.5007 | 12.07030 |
July | 497.00000 | 24.05733 | 41.14111 | -0.3639 | 8.87157 |
August | 514.00000 | 24.07947 | 41.04414 | -0.3535 | 8.52157 |
September | 485.00000 | 24.01092 | 36.79384 | -0.4385 | 10.24901 |
October | 502.00000 | 23.45025 | 23.90743 | 0.17287 | 7.08175 |
November | 489.00000 | 22.54855 | 18.44676 | -0.1196 | 6.38988 |
December | 497.00000 | 21.49719 | 15.98175 | -0.4182 | 9.73703 |
Annual Sum or Average | 5943.00000 | 22.92851 | 25.50500 | -0.3212 | 9.70265 |
Minimum of Months | 454.00000 | 21.31943 | 15.68799 | -0.7778 | 6.25102 |
Maximum of Months | 514.00000 | 24.07947 | 41.14111 | 0.17287 | 19.83394 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34534 | 19.15586 | -0.4684 | 10.66667 |
February | 454.00000 | 21.79649 | 20.18636 | -0.3451 | 8.72027 |
March | 514.00000 | 22.63736 | 19.09670 | -0.1356 | 6.46253 |
April | 485.00000 | 23.48348 | 15.83702 | 0.06705 | 5.78689 |
May | 508.00000 | 23.85600 | 23.27150 | -0.6881 | 15.98277 |
June | 496.00000 | 24.12779 | 32.28660 | -0.4871 | 10.52959 |
July | 497.00000 | 24.28653 | 41.26068 | -0.3542 | 8.00608 |
August | 514.00000 | 24.18686 | 41.33002 | -0.3966 | 8.61995 |
September | 485.00000 | 24.01119 | 37.37335 | -0.5234 | 11.34406 |
October | 502.00000 | 23.31595 | 24.94804 | 0.08463 | 6.33038 |
November | 489.00000 | 22.41360 | 19.67639 | -0.1916 | 6.92577 |
December | 497.00000 | 21.31588 | 17.45970 | -0.4842 | 10.78283 |
Annual Sum or Average | 5943.00000 | 23.07404 | 26.04964 | -0.3274 | 9.19050 |
Minimum of Months | 454.00000 | 21.31588 | 15.83702 | -0.6881 | 5.78689 |
Maximum of Months | 514.00000 | 24.28653 | 41.33002 | 0.08463 | 15.98277 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.33463 | 17.60013 | -0.4457 | 10.32044 |
February | 385.00000 | 21.71314 | 18.69221 | -0.3284 | 8.86046 |
March | 433.00000 | 22.45212 | 17.67096 | -0.1245 | 7.04595 |
April | 410.00000 | 23.51395 | 14.56754 | 0.14792 | 7.22662 |
May | 430.00000 | 23.74387 | 22.47066 | -0.6164 | 16.60192 |
June | 418.00000 | 24.05019 | 31.54914 | -0.4010 | 10.72991 |
July | 422.00000 | 24.25421 | 40.47353 | -0.2648 | 9.14593 |
August | 433.00000 | 24.05731 | 40.73671 | -0.3384 | 9.60353 |
September | 410.00000 | 23.72859 | 36.84132 | -0.5197 | 13.10681 |
October | 427.00000 | 23.12414 | 23.77846 | 0.09739 | 7.37703 |
November | 417.00000 | 22.23442 | 18.36361 | -0.1892 | 7.21634 |
December | 422.00000 | 21.29928 | 15.99346 | -0.4621 | 10.50308 |
Annual Sum or Average | 5034.00000 | 22.96576 | 24.94436 | -0.2873 | 9.82103 |
Minimum of Months | 385.00000 | 21.29928 | 14.56754 | -0.6164 | 7.04595 |
Maximum of Months | 433.00000 | 24.25421 | 40.73671 | 0.14792 | 16.60192 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.05325 | 16.53770 | -0.0103 | 9.78164 |
February | 454.00000 | 23.18342 | 17.61810 | 0.03909 | 8.71236 |
March | 514.00000 | 23.20830 | 17.56896 | 0.03666 | 6.82587 |
April | 485.00000 | 23.63367 | 15.20457 | 0.12261 | 6.18434 |
May | 508.00000 | 23.82869 | 23.14995 | -0.6866 | 16.11980 |
June | 496.00000 | 24.06999 | 32.34087 | -0.5018 | 11.01147 |
July | 497.00000 | 24.26526 | 41.22405 | -0.3528 | 8.10383 |
August | 514.00000 | 24.20635 | 41.07052 | -0.3661 | 8.34523 |
September | 485.00000 | 24.21708 | 36.39487 | -0.3925 | 9.75718 |
October | 502.00000 | 24.12492 | 22.89754 | 0.34246 | 9.93991 |
November | 489.00000 | 23.86267 | 16.99056 | 0.21600 | 9.28970 |
December | 497.00000 | 23.19847 | 14.74466 | 0.02777 | 9.69755 |
Annual Sum or Average | 5943.00000 | 23.74045 | 24.71607 | -0.1295 | 9.49448 |
Minimum of Months | 454.00000 | 23.05325 | 14.74466 | -0.6866 | 6.18434 |
Maximum of Months | 514.00000 | 24.26526 | 41.22405 | 0.34246 | 16.11980 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37826 | 18.02701 | -0.4294 | 10.59162 |
February | 454.00000 | 21.79364 | 19.10574 | -0.3009 | 9.00088 |
March | 514.00000 | 22.28142 | 18.34988 | -0.1592 | 7.32528 |
April | 485.00000 | 23.12816 | 15.34270 | 0.05819 | 6.83112 |
May | 508.00000 | 23.37916 | 23.36584 | -0.7378 | 19.24528 |
June | 496.00000 | 23.73752 | 32.82804 | -0.5115 | 13.07299 |
July | 497.00000 | 23.87571 | 41.93646 | -0.3929 | 10.14558 |
August | 514.00000 | 23.79722 | 41.91897 | -0.4231 | 10.52859 |
September | 485.00000 | 23.53758 | 37.81726 | -0.5718 | 14.24047 |
October | 502.00000 | 22.92321 | 24.62363 | 0.06412 | 7.17198 |
November | 489.00000 | 22.15061 | 18.80703 | -0.2013 | 7.54729 |
December | 497.00000 | 21.39524 | 16.30368 | -0.4347 | 10.61687 |
Annual Sum or Average | 5943.00000 | 22.78861 | 25.76812 | -0.3376 | 10.54530 |
Minimum of Months | 454.00000 | 21.37826 | 15.34270 | -0.7378 | 6.83112 |
Maximum of Months | 514.00000 | 23.87571 | 41.93646 | 0.06412 | 19.24528 |
Report: DXReportMonthly
For: PACU_VAV_BOT_COOLC DXCOIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.326436E+09 | 92553343.11 | 21.00 | 0.326434E+09 | 2504.43 | 0.00 | 0.31 | 05-JAN-14:00 | 0.00 | 01-JAN-00:10 | 9501.40 | 05-JAN-14:00 | 9501.40 | 05-JAN-14:00 | 3.39 | 01-JAN-13:15 | 2617.63 | 05-JAN-14:00 | 0.00 |
February | 0.147259E+10 | 0.375151E+09 | 31.49 | 0.147209E+10 | 505302.87 | 0.00 | 0.93 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 33999.18 | 14-FEB-16:10 | 33999.18 | 14-FEB-16:10 | 123.36 | 19-FEB-13:16 | 7936.86 | 14-FEB-16:10 | 0.00 |
March | 0.510217E+10 | 0.134402E+10 | 126.00 | 0.509866E+10 | 3508443.13 | 0.00 | 0.92 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 33767.10 | 08-MAR-14:00 | 33767.10 | 08-MAR-14:00 | 309.87 | 07-MAR-18:50 | 7894.10 | 08-MAR-14:00 | 0.00 |
April | 0.171214E+11 | 0.424202E+10 | 233.81 | 0.170979E+11 | 23443268.31 | 0.00 | 1.00 | 11-APR-15:10 | 0.00 | 01-APR-00:10 | 48425.88 | 13-APR-16:00 | 48425.88 | 13-APR-16:00 | 1406.94 | 14-APR-20:00 | 11541.13 | 13-APR-16:00 | 0.00 |
May | 0.306721E+11 | 0.761570E+10 | 326.94 | 0.297083E+11 | 0.963811E+09 | 0.00 | 1.00 | 08-MAY-12:20 | 0.00 | 01-MAY-00:10 | 57479.66 | 19-MAY-16:10 | 57479.66 | 19-MAY-16:10 | 12651.79 | 24-MAY-15:00 | 15394.72 | 19-MAY-16:10 | 0.00 |
June | 0.579659E+11 | 0.156371E+11 | 422.76 | 0.557001E+11 | 0.226578E+10 | 0.00 | 1.00 | 02-JUN-14:10 | 0.00 | 01-JUN-00:10 | 76457.23 | 29-JUN-05:02 | 74106.99 | 28-JUN-16:00 | 13195.93 | 29-JUN-05:02 | 25962.63 | 28-JUN-16:00 | 0.00 |
July | 0.753662E+11 | 0.200505E+11 | 447.64 | 0.650822E+11 | 0.102840E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 76885.43 | 31-JUL-16:50 | 73538.21 | 21-JUL-16:00 | 28794.49 | 31-JUL-16:50 | 24517.70 | 21-JUL-15:30 | 0.00 |
August | 0.749923E+11 | 0.191930E+11 | 465.09 | 0.640802E+11 | 0.109121E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 87052.60 | 23-AUG-16:00 | 70022.32 | 18-AUG-16:00 | 39263.87 | 23-AUG-16:00 | 21832.76 | 18-AUG-16:00 | 0.00 |
September | 0.517273E+11 | 0.127497E+11 | 404.49 | 0.463874E+11 | 0.533992E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 89440.13 | 05-SEP-13:00 | 63908.29 | 28-SEP-16:00 | 37392.15 | 05-SEP-13:00 | 20593.10 | 05-SEP-13:00 | 0.00 |
October | 0.239509E+11 | 0.585768E+10 | 258.10 | 0.225076E+11 | 0.144324E+10 | 0.00 | 1.00 | 01-OCT-15:42 | 0.00 | 01-OCT-00:10 | 63442.89 | 06-OCT-16:00 | 63442.89 | 06-OCT-16:00 | 17329.10 | 02-OCT-17:00 | 15989.44 | 06-OCT-16:00 | 0.00 |
November | 0.125994E+10 | 0.345689E+09 | 51.58 | 0.122505E+10 | 34884917.22 | 0.00 | 0.65 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 21957.55 | 09-NOV-14:00 | 21957.55 | 09-NOV-14:00 | 1335.49 | 02-NOV-17:05 | 5541.65 | 09-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.339957E+12 | 0.875031E+11 | 2788.90 | 0.308686E+12 | 0.312711E+11 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.753662E+11 | 0.200505E+11 | 465.09 | 0.650822E+11 | 0.109121E+11 | 0.00 | 1.00 | 0.00 | 89440.13 | 74106.99 | 39263.87 | 25962.63 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID_COOLC DXCOIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.247495E+09 | 70105477.23 | 20.83 | 0.247495E+09 | 0.00 | 0.00 | 0.31 | 05-JAN-16:00 | 0.00 | 01-JAN-00:10 | 7309.42 | 05-JAN-16:00 | 7309.42 | 05-JAN-16:00 | 0.00 | 05-JAN-13:50 | 2010.65 | 05-JAN-16:00 | 0.00 |
February | 0.117284E+10 | 0.297793E+09 | 32.25 | 0.117281E+10 | 32863.93 | 0.00 | 1.00 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 28290.56 | 14-FEB-16:00 | 28290.56 | 14-FEB-16:00 | 49.81 | 19-FEB-12:48 | 6460.61 | 14-FEB-16:00 | 0.00 |
March | 0.426780E+10 | 0.111921E+10 | 135.27 | 0.426444E+10 | 3360431.27 | 0.00 | 0.96 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 26864.56 | 08-MAR-16:00 | 26864.56 | 08-MAR-16:00 | 289.54 | 20-MAR-12:00 | 6205.97 | 08-MAR-16:00 | 0.00 |
April | 0.141739E+11 | 0.348629E+10 | 239.45 | 0.141594E+11 | 14461399.25 | 0.00 | 1.00 | 11-APR-13:20 | 0.00 | 01-APR-00:10 | 42297.30 | 13-APR-16:00 | 42297.30 | 13-APR-16:00 | 882.51 | 14-APR-20:00 | 10077.20 | 13-APR-16:00 | 0.00 |
May | 0.254012E+11 | 0.626380E+10 | 335.74 | 0.246699E+11 | 0.731296E+09 | 0.00 | 1.00 | 08-MAY-12:10 | 0.00 | 01-MAY-00:10 | 49581.08 | 19-MAY-16:00 | 49581.08 | 19-MAY-16:00 | 9760.23 | 24-MAY-15:00 | 13274.39 | 19-MAY-16:00 | 0.00 |
June | 0.477842E+11 | 0.128402E+11 | 426.99 | 0.460851E+11 | 0.169911E+10 | 0.00 | 1.00 | 01-JUN-12:40 | 0.00 | 01-JUN-00:10 | 67516.45 | 29-JUN-05:02 | 63804.15 | 28-JUN-16:00 | 11764.91 | 29-JUN-05:02 | 22341.96 | 28-JUN-16:00 | 0.00 |
July | 0.617556E+11 | 0.163853E+11 | 448.84 | 0.533832E+11 | 0.837246E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 65053.71 | 31-JUL-15:20 | 61719.55 | 21-JUL-16:00 | 30232.89 | 01-JUL-05:02 | 20516.41 | 21-JUL-15:40 | 0.00 |
August | 0.597846E+11 | 0.152707E+11 | 463.81 | 0.511603E+11 | 0.862432E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 69381.94 | 23-AUG-16:00 | 58067.39 | 07-AUG-15:50 | 31372.20 | 23-AUG-16:00 | 18017.75 | 18-AUG-16:00 | 0.00 |
September | 0.399906E+11 | 0.983347E+10 | 401.81 | 0.358651E+11 | 0.412552E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 71151.22 | 05-SEP-13:00 | 52338.90 | 29-SEP-14:50 | 29850.11 | 05-SEP-13:00 | 16477.08 | 05-SEP-13:50 | 0.00 |
October | 0.181956E+11 | 0.444435E+10 | 253.56 | 0.171261E+11 | 0.106949E+10 | 0.00 | 1.00 | 01-OCT-11:42 | 0.00 | 01-OCT-00:10 | 53111.32 | 02-OCT-15:00 | 50802.75 | 06-OCT-15:30 | 11518.84 | 02-OCT-17:00 | 13170.99 | 02-OCT-15:00 | 0.00 |
November | 0.865680E+09 | 0.238730E+09 | 49.67 | 0.833633E+09 | 32047419.20 | 0.00 | 0.57 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 14238.64 | 02-NOV-15:00 | 14238.64 | 02-NOV-15:00 | 1020.83 | 02-NOV-17:00 | 3668.73 | 02-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.273640E+12 | 0.702500E+11 | 2808.22 | 0.248968E+12 | 0.246721E+11 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.617556E+11 | 0.163853E+11 | 463.81 | 0.533832E+11 | 0.862432E+10 | 0.00 | 1.00 | 0.00 | 71151.22 | 63804.15 | 31372.20 | 22341.96 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP_COOLC DXCOIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.241183E+09 | 68681277.30 | 20.50 | 0.241172E+09 | 10951.49 | 0.00 | 0.26 | 05-JAN-15:40 | 0.00 | 01-JAN-00:10 | 6844.44 | 05-JAN-15:40 | 6844.44 | 05-JAN-15:40 | 6.10 | 05-JAN-12:50 | 1905.79 | 05-JAN-15:40 | 0.00 |
February | 0.116433E+10 | 0.299623E+09 | 30.79 | 0.116387E+10 | 454937.71 | 0.00 | 0.91 | 14-FEB-15:50 | 0.00 | 01-FEB-00:10 | 28413.02 | 14-FEB-15:50 | 28413.02 | 14-FEB-15:50 | 107.52 | 19-FEB-13:12 | 6654.65 | 14-FEB-15:50 | 0.00 |
March | 0.426536E+10 | 0.113007E+10 | 131.86 | 0.425703E+10 | 8327141.03 | 0.00 | 0.90 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 27764.44 | 08-MAR-16:00 | 27764.44 | 08-MAR-16:00 | 461.29 | 20-MAR-12:02 | 6533.96 | 08-MAR-16:00 | 0.00 |
April | 0.149868E+11 | 0.371004E+10 | 239.55 | 0.149659E+11 | 20843579.66 | 0.00 | 1.00 | 11-APR-13:40 | 0.00 | 01-APR-00:10 | 48317.06 | 13-APR-16:00 | 48317.06 | 13-APR-16:00 | 1204.05 | 14-APR-20:00 | 11511.03 | 13-APR-16:00 | 0.00 |
May | 0.277443E+11 | 0.688480E+10 | 337.82 | 0.269158E+11 | 0.828557E+09 | 0.00 | 1.00 | 08-MAY-12:10 | 0.00 | 01-MAY-00:10 | 57553.87 | 19-MAY-16:00 | 57553.87 | 19-MAY-16:00 | 9454.23 | 24-MAY-15:00 | 15407.66 | 19-MAY-16:00 | 0.00 |
June | 0.529429E+11 | 0.143380E+11 | 424.93 | 0.511125E+11 | 0.183048E+10 | 0.00 | 1.00 | 01-JUN-13:30 | 0.00 | 01-JUN-00:10 | 74222.04 | 28-JUN-16:00 | 74222.04 | 28-JUN-16:00 | 10663.06 | 29-JUN-05:02 | 25986.67 | 28-JUN-16:00 | 0.00 |
July | 0.685751E+11 | 0.183220E+11 | 449.24 | 0.598434E+11 | 0.873175E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 73943.85 | 31-JUL-15:30 | 71899.73 | 21-JUL-15:40 | 26728.80 | 01-JUL-05:02 | 24080.95 | 21-JUL-15:20 | 0.00 |
August | 0.651974E+11 | 0.167725E+11 | 460.12 | 0.562856E+11 | 0.891179E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 74285.94 | 23-AUG-16:00 | 67617.66 | 07-AUG-15:30 | 33510.16 | 23-AUG-16:00 | 20925.83 | 01-AUG-15:50 | 0.00 |
September | 0.423338E+11 | 0.104856E+11 | 399.39 | 0.380242E+11 | 0.430962E+10 | 0.00 | 1.00 | 01-SEP-08:70 | 0.00 | 01-SEP-00:10 | 76643.95 | 05-SEP-13:30 | 58895.52 | 29-SEP-14:40 | 31897.69 | 05-SEP-13:00 | 17740.45 | 05-SEP-13:40 | 0.00 |
October | 0.185665E+11 | 0.457309E+10 | 249.43 | 0.174661E+11 | 0.110045E+10 | 0.00 | 1.00 | 01-OCT-11:52 | 0.00 | 01-OCT-00:10 | 58529.82 | 02-OCT-14:50 | 55812.70 | 06-OCT-15:20 | 11908.79 | 02-OCT-17:00 | 14505.61 | 02-OCT-15:00 | 0.00 |
November | 0.797298E+09 | 0.222067E+09 | 48.00 | 0.749802E+09 | 47496374.53 | 0.00 | 0.50 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 13727.72 | 02-NOV-15:00 | 13727.72 | 02-NOV-15:00 | 1272.95 | 09-NOV-11:00 | 3605.12 | 02-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.296815E+12 | 0.768065E+11 | 2791.63 | 0.271025E+12 | 0.257898E+11 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.685751E+11 | 0.183220E+11 | 460.12 | 0.598434E+11 | 0.891179E+10 | 0.00 | 1.00 | 0.00 | 76643.95 | 74222.04 | 33510.16 | 25986.67 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.32 | 0.00 | 469.32 | 69.28 | 1585.88 | 0.00 | 0.00 | 744.00 |
February | 586.57 | 0.00 | 586.57 | 158.86 | 1435.07 | 0.00 | 0.00 | 672.00 |
March | 739.88 | 0.00 | 739.88 | 365.88 | 1121.93 | 0.00 | 0.00 | 744.00 |
April | 938.56 | 7.92 | 930.65 | 603.80 | 755.27 | 0.00 | 0.00 | 720.00 |
May | 1020.10 | 65.53 | 954.57 | 795.73 | 548.74 | 0.00 | 0.00 | 744.00 |
June | 1159.03 | 189.37 | 969.67 | 1193.57 | 355.60 | 0.00 | 0.00 | 720.00 |
July | 1063.88 | 88.31 | 975.58 | 1281.29 | 240.27 | 0.00 | 0.00 | 744.00 |
August | 987.02 | 21.95 | 965.07 | 1128.49 | 275.96 | 0.00 | 0.00 | 744.00 |
September | 789.42 | 0.19 | 789.23 | 777.85 | 485.35 | 0.00 | 0.00 | 720.00 |
October | 589.08 | 0.00 | 589.08 | 339.83 | 880.33 | 0.00 | 0.00 | 744.00 |
November | 500.26 | 0.00 | 500.26 | 102.86 | 1271.01 | 0.00 | 0.00 | 720.00 |
December | 399.46 | 0.00 | 399.46 | 18.58 | 1672.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 770.89 | 31.16 | 739.73 | 571.95 | 883.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 399.46 | 0.00 | 399.46 | 18.58 | 240.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1159.03 | 189.37 | 975.58 | 1281.29 | 1672.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.56 | 484.52 | 382.04 | 581.73 | 960.68 | 0.00 | 0.00 | 744.00 |
February | 1052.74 | 567.53 | 485.21 | 800.92 | 878.43 | 0.00 | 0.00 | 672.00 |
March | 1388.84 | 789.56 | 599.27 | 1263.16 | 689.37 | 0.00 | 0.00 | 744.00 |
April | 1897.50 | 1081.08 | 816.43 | 1925.26 | 476.60 | 0.00 | 0.00 | 720.00 |
May | 1810.18 | 1031.49 | 778.69 | 1934.97 | 361.47 | 0.00 | 0.00 | 744.00 |
June | 1951.35 | 1201.96 | 749.40 | 2330.38 | 232.71 | 0.00 | 0.00 | 720.00 |
July | 1805.76 | 1032.49 | 773.27 | 2235.95 | 158.37 | 0.00 | 0.00 | 744.00 |
August | 1787.12 | 985.24 | 801.88 | 2140.13 | 178.69 | 0.00 | 0.00 | 744.00 |
September | 1487.69 | 832.44 | 655.25 | 1671.26 | 304.52 | 0.00 | 0.00 | 720.00 |
October | 1293.68 | 820.79 | 472.90 | 1259.71 | 538.72 | 0.00 | 0.00 | 744.00 |
November | 1011.13 | 594.45 | 416.68 | 788.49 | 781.32 | 0.00 | 0.00 | 720.00 |
December | 819.44 | 498.77 | 320.67 | 536.11 | 1016.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1432.40 | 827.72 | 604.68 | 1458.61 | 546.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 819.44 | 484.52 | 320.67 | 536.11 | 158.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1951.35 | 1201.96 | 816.43 | 2330.38 | 1016.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3470.94 | 2701.15 | 769.78 | 3599.16 | 1453.81 | 0.00 | 0.00 | 744.00 |
February | 3397.69 | 2482.48 | 915.21 | 3403.71 | 1359.74 | 0.00 | 0.00 | 672.00 |
March | 2502.35 | 1512.90 | 989.45 | 2191.67 | 1108.54 | 0.00 | 0.00 | 744.00 |
April | 1950.90 | 800.53 | 1150.36 | 1417.78 | 781.52 | 0.00 | 0.00 | 720.00 |
May | 1300.80 | 285.68 | 1015.11 | 979.83 | 576.22 | 0.00 | 0.00 | 744.00 |
June | 1099.98 | 134.77 | 965.20 | 1188.56 | 381.76 | 0.00 | 0.00 | 720.00 |
July | 1217.38 | 193.74 | 1023.64 | 1386.88 | 252.41 | 0.00 | 0.00 | 744.00 |
August | 1674.68 | 544.09 | 1130.59 | 1631.20 | 291.04 | 0.00 | 0.00 | 744.00 |
September | 2316.02 | 1291.37 | 1024.65 | 2267.11 | 499.08 | 0.00 | 0.00 | 720.00 |
October | 3170.40 | 2335.37 | 835.03 | 3267.32 | 864.58 | 0.00 | 0.00 | 744.00 |
November | 3531.42 | 2710.78 | 820.64 | 3685.35 | 1187.63 | 0.00 | 0.00 | 720.00 |
December | 3765.41 | 3106.24 | 659.17 | 3997.95 | 1483.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2444.51 | 1503.25 | 941.25 | 2412.99 | 850.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1099.98 | 134.77 | 659.17 | 979.83 | 252.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3765.41 | 3106.24 | 1150.36 | 3997.95 | 1483.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 893.82 | 509.74 | 384.07 | 673.67 | 1023.36 | 0.00 | 0.00 | 744.00 |
February | 1150.50 | 664.59 | 485.91 | 972.93 | 935.33 | 0.00 | 0.00 | 672.00 |
March | 1285.15 | 684.16 | 600.99 | 1186.51 | 738.76 | 0.00 | 0.00 | 744.00 |
April | 1640.19 | 872.96 | 767.23 | 1647.76 | 513.47 | 0.00 | 0.00 | 720.00 |
May | 1554.82 | 801.04 | 753.78 | 1651.04 | 382.84 | 0.00 | 0.00 | 744.00 |
June | 1666.67 | 929.84 | 736.84 | 2009.35 | 263.54 | 0.00 | 0.00 | 720.00 |
July | 1503.42 | 735.67 | 767.75 | 1871.18 | 171.23 | 0.00 | 0.00 | 744.00 |
August | 1536.37 | 710.61 | 825.75 | 1847.79 | 196.07 | 0.00 | 0.00 | 744.00 |
September | 1387.85 | 730.98 | 656.87 | 1575.28 | 328.61 | 0.00 | 0.00 | 720.00 |
October | 1269.57 | 789.08 | 480.49 | 1288.22 | 582.98 | 0.00 | 0.00 | 744.00 |
November | 996.63 | 586.35 | 410.29 | 819.04 | 816.60 | 0.00 | 0.00 | 720.00 |
December | 861.98 | 540.59 | 321.39 | 630.10 | 1057.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1312.36 | 712.63 | 599.73 | 1349.01 | 582.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 861.98 | 509.74 | 321.39 | 630.10 | 171.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1666.67 | 929.84 | 825.75 | 2009.35 | 1057.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.43 | 0.00 | 156.43 | 22.29 | 546.43 | 0.00 | 0.00 | 744.00 |
February | 195.51 | 0.00 | 195.51 | 55.24 | 485.54 | 0.00 | 0.00 | 672.00 |
March | 246.62 | 0.00 | 246.62 | 129.57 | 371.86 | 0.00 | 0.00 | 744.00 |
April | 312.84 | 2.64 | 310.20 | 211.68 | 248.02 | 0.00 | 0.00 | 720.00 |
May | 340.02 | 21.84 | 318.17 | 274.68 | 179.33 | 0.00 | 0.00 | 744.00 |
June | 386.33 | 63.12 | 323.21 | 404.18 | 116.21 | 0.00 | 0.00 | 720.00 |
July | 354.61 | 29.43 | 325.18 | 432.49 | 78.00 | 0.00 | 0.00 | 744.00 |
August | 328.99 | 7.32 | 321.68 | 379.29 | 92.79 | 0.00 | 0.00 | 744.00 |
September | 263.13 | 0.06 | 263.06 | 258.51 | 170.88 | 0.00 | 0.00 | 720.00 |
October | 196.35 | 0.00 | 196.35 | 110.02 | 315.84 | 0.00 | 0.00 | 744.00 |
November | 166.75 | 0.00 | 166.75 | 30.46 | 457.39 | 0.00 | 0.00 | 720.00 |
December | 133.15 | 0.00 | 133.15 | 4.69 | 588.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 256.95 | 10.39 | 246.56 | 193.52 | 303.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 133.15 | 0.00 | 133.15 | 4.69 | 78.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 386.33 | 63.12 | 325.18 | 432.49 | 588.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.44 | 0.00 | 156.44 | 22.29 | 546.47 | 0.00 | 0.00 | 744.00 |
February | 195.53 | 0.00 | 195.53 | 55.24 | 485.57 | 0.00 | 0.00 | 672.00 |
March | 246.63 | 0.00 | 246.63 | 129.58 | 371.88 | 0.00 | 0.00 | 744.00 |
April | 312.86 | 2.64 | 310.22 | 211.69 | 248.04 | 0.00 | 0.00 | 720.00 |
May | 340.04 | 21.84 | 318.20 | 274.69 | 179.35 | 0.00 | 0.00 | 744.00 |
June | 386.35 | 63.12 | 323.23 | 404.20 | 116.22 | 0.00 | 0.00 | 720.00 |
July | 354.63 | 29.44 | 325.20 | 432.52 | 78.00 | 0.00 | 0.00 | 744.00 |
August | 329.01 | 7.32 | 321.70 | 379.31 | 92.80 | 0.00 | 0.00 | 744.00 |
September | 263.15 | 0.06 | 263.08 | 258.53 | 170.89 | 0.00 | 0.00 | 720.00 |
October | 196.36 | 0.00 | 196.36 | 110.02 | 315.86 | 0.00 | 0.00 | 744.00 |
November | 166.76 | 0.00 | 166.76 | 30.46 | 457.41 | 0.00 | 0.00 | 720.00 |
December | 133.16 | 0.00 | 133.16 | 4.69 | 588.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 256.97 | 10.39 | 246.58 | 193.53 | 303.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 133.16 | 0.00 | 133.16 | 4.69 | 78.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 386.35 | 63.12 | 325.20 | 432.52 | 588.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.44 | 0.00 | 156.44 | 22.29 | 546.47 | 0.00 | 0.00 | 744.00 |
February | 195.53 | 0.00 | 195.53 | 55.24 | 485.57 | 0.00 | 0.00 | 672.00 |
March | 246.63 | 0.00 | 246.63 | 129.58 | 371.88 | 0.00 | 0.00 | 744.00 |
April | 312.86 | 2.64 | 310.22 | 211.69 | 248.04 | 0.00 | 0.00 | 720.00 |
May | 340.04 | 21.84 | 318.20 | 274.69 | 179.35 | 0.00 | 0.00 | 744.00 |
June | 386.35 | 63.12 | 323.23 | 404.20 | 116.22 | 0.00 | 0.00 | 720.00 |
July | 354.63 | 29.44 | 325.20 | 432.52 | 78.00 | 0.00 | 0.00 | 744.00 |
August | 329.01 | 7.32 | 321.70 | 379.31 | 92.80 | 0.00 | 0.00 | 744.00 |
September | 263.15 | 0.06 | 263.08 | 258.53 | 170.89 | 0.00 | 0.00 | 720.00 |
October | 196.36 | 0.00 | 196.36 | 110.02 | 315.86 | 0.00 | 0.00 | 744.00 |
November | 166.76 | 0.00 | 166.76 | 30.46 | 457.41 | 0.00 | 0.00 | 720.00 |
December | 133.16 | 0.00 | 133.16 | 4.69 | 588.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 256.97 | 10.39 | 246.58 | 193.53 | 303.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 133.16 | 0.00 | 133.16 | 4.69 | 78.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 386.35 | 63.12 | 325.20 | 432.52 | 588.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 833.59 | 466.08 | 367.51 | 553.24 | 966.40 | 0.00 | 0.00 | 744.00 |
February | 1012.69 | 545.94 | 466.75 | 772.73 | 872.19 | 0.00 | 0.00 | 672.00 |
March | 1336.00 | 759.52 | 576.48 | 1225.24 | 679.85 | 0.00 | 0.00 | 744.00 |
April | 1825.32 | 1039.95 | 785.37 | 1863.92 | 474.19 | 0.00 | 0.00 | 720.00 |
May | 1741.31 | 992.24 | 749.07 | 1872.28 | 360.56 | 0.00 | 0.00 | 744.00 |
June | 1877.12 | 1156.23 | 720.89 | 2249.93 | 233.22 | 0.00 | 0.00 | 720.00 |
July | 1737.06 | 993.21 | 743.86 | 2157.16 | 161.50 | 0.00 | 0.00 | 744.00 |
August | 1719.13 | 947.76 | 771.38 | 2062.32 | 185.97 | 0.00 | 0.00 | 744.00 |
September | 1431.10 | 800.77 | 630.32 | 1603.86 | 321.64 | 0.00 | 0.00 | 720.00 |
October | 1244.47 | 789.56 | 454.91 | 1201.78 | 569.35 | 0.00 | 0.00 | 744.00 |
November | 972.67 | 571.84 | 400.83 | 743.69 | 821.18 | 0.00 | 0.00 | 720.00 |
December | 788.27 | 479.80 | 308.47 | 507.20 | 1043.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1377.91 | 796.23 | 581.68 | 1403.93 | 555.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 788.27 | 466.08 | 308.47 | 507.20 | 161.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1877.12 | 1156.23 | 785.37 | 2249.93 | 1043.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.96 | 18.43 | 14.53 | 21.87 | 38.21 | 0.00 | 0.00 | 744.00 |
February | 40.04 | 21.59 | 18.46 | 30.55 | 34.49 | 0.00 | 0.00 | 672.00 |
March | 52.82 | 30.03 | 22.79 | 48.44 | 26.88 | 0.00 | 0.00 | 744.00 |
April | 72.17 | 41.12 | 31.05 | 73.70 | 18.75 | 0.00 | 0.00 | 720.00 |
May | 68.85 | 39.23 | 29.62 | 74.03 | 14.26 | 0.00 | 0.00 | 744.00 |
June | 74.22 | 45.72 | 28.50 | 88.96 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 68.68 | 39.27 | 29.41 | 85.29 | 6.39 | 0.00 | 0.00 | 744.00 |
August | 67.97 | 37.47 | 30.50 | 81.54 | 7.35 | 0.00 | 0.00 | 744.00 |
September | 56.58 | 31.66 | 24.92 | 63.41 | 12.72 | 0.00 | 0.00 | 720.00 |
October | 49.21 | 31.22 | 17.99 | 47.52 | 22.51 | 0.00 | 0.00 | 744.00 |
November | 38.46 | 22.61 | 15.85 | 29.40 | 32.47 | 0.00 | 0.00 | 720.00 |
December | 31.17 | 18.97 | 12.20 | 20.05 | 41.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.48 | 31.48 | 23.00 | 55.51 | 21.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.17 | 18.43 | 12.20 | 20.05 | 6.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.22 | 45.72 | 31.05 | 88.96 | 41.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1157.02 | 900.41 | 256.60 | 1207.58 | 516.17 | 0.00 | 0.00 | 744.00 |
February | 1132.60 | 827.52 | 305.08 | 1145.91 | 474.73 | 0.00 | 0.00 | 672.00 |
March | 834.14 | 504.32 | 329.82 | 743.22 | 374.12 | 0.00 | 0.00 | 744.00 |
April | 650.32 | 266.85 | 383.46 | 485.90 | 257.20 | 0.00 | 0.00 | 720.00 |
May | 433.61 | 95.23 | 338.38 | 339.41 | 185.21 | 0.00 | 0.00 | 744.00 |
June | 366.67 | 44.93 | 321.74 | 402.22 | 123.39 | 0.00 | 0.00 | 720.00 |
July | 405.81 | 64.58 | 341.22 | 465.72 | 82.52 | 0.00 | 0.00 | 744.00 |
August | 558.24 | 181.37 | 376.87 | 545.32 | 99.75 | 0.00 | 0.00 | 744.00 |
September | 772.03 | 430.47 | 341.56 | 754.47 | 180.59 | 0.00 | 0.00 | 720.00 |
October | 1056.83 | 778.48 | 278.35 | 1089.24 | 316.40 | 0.00 | 0.00 | 744.00 |
November | 1177.18 | 903.62 | 273.55 | 1231.10 | 435.73 | 0.00 | 0.00 | 720.00 |
December | 1255.18 | 1035.45 | 219.73 | 1339.73 | 535.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 814.86 | 501.10 | 313.76 | 810.78 | 297.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 366.67 | 44.93 | 219.73 | 339.41 | 82.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1255.18 | 1035.45 | 383.46 | 1339.73 | 535.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1157.02 | 900.41 | 256.60 | 1207.58 | 516.17 | 0.00 | 0.00 | 744.00 |
February | 1132.60 | 827.52 | 305.08 | 1145.91 | 474.73 | 0.00 | 0.00 | 672.00 |
March | 834.14 | 504.32 | 329.82 | 743.22 | 374.12 | 0.00 | 0.00 | 744.00 |
April | 650.32 | 266.85 | 383.46 | 485.90 | 257.20 | 0.00 | 0.00 | 720.00 |
May | 433.61 | 95.23 | 338.38 | 339.41 | 185.21 | 0.00 | 0.00 | 744.00 |
June | 366.67 | 44.93 | 321.74 | 402.22 | 123.39 | 0.00 | 0.00 | 720.00 |
July | 405.81 | 64.58 | 341.22 | 465.72 | 82.52 | 0.00 | 0.00 | 744.00 |
August | 558.24 | 181.37 | 376.87 | 545.32 | 99.75 | 0.00 | 0.00 | 744.00 |
September | 772.03 | 430.47 | 341.56 | 754.47 | 180.59 | 0.00 | 0.00 | 720.00 |
October | 1056.83 | 778.48 | 278.35 | 1089.24 | 316.40 | 0.00 | 0.00 | 744.00 |
November | 1177.18 | 903.62 | 273.55 | 1231.10 | 435.73 | 0.00 | 0.00 | 720.00 |
December | 1255.18 | 1035.45 | 219.73 | 1339.73 | 535.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 814.86 | 501.10 | 313.76 | 810.78 | 297.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 366.67 | 44.93 | 219.73 | 339.41 | 82.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1255.18 | 1035.45 | 383.46 | 1339.73 | 535.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1156.94 | 900.36 | 256.59 | 1207.50 | 516.13 | 0.00 | 0.00 | 744.00 |
February | 1132.53 | 827.47 | 305.06 | 1145.84 | 474.70 | 0.00 | 0.00 | 672.00 |
March | 834.09 | 504.28 | 329.80 | 743.18 | 374.10 | 0.00 | 0.00 | 744.00 |
April | 650.28 | 266.84 | 383.44 | 485.87 | 257.18 | 0.00 | 0.00 | 720.00 |
May | 433.58 | 95.22 | 338.36 | 339.39 | 185.20 | 0.00 | 0.00 | 744.00 |
June | 366.65 | 44.92 | 321.72 | 402.20 | 123.38 | 0.00 | 0.00 | 720.00 |
July | 405.78 | 64.58 | 341.20 | 465.69 | 82.51 | 0.00 | 0.00 | 744.00 |
August | 558.21 | 181.36 | 376.85 | 545.28 | 99.74 | 0.00 | 0.00 | 744.00 |
September | 771.98 | 430.44 | 341.54 | 754.43 | 180.58 | 0.00 | 0.00 | 720.00 |
October | 1056.77 | 778.43 | 278.33 | 1089.17 | 316.38 | 0.00 | 0.00 | 744.00 |
November | 1177.10 | 903.57 | 273.54 | 1231.02 | 435.71 | 0.00 | 0.00 | 720.00 |
December | 1255.10 | 1035.38 | 219.72 | 1339.64 | 535.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 814.81 | 501.07 | 313.74 | 810.72 | 297.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 366.65 | 44.92 | 219.72 | 339.39 | 82.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1255.10 | 1035.38 | 383.44 | 1339.64 | 535.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 859.81 | 490.35 | 369.46 | 649.61 | 1031.64 | 0.00 | 0.00 | 744.00 |
February | 1106.73 | 639.31 | 467.43 | 943.44 | 932.33 | 0.00 | 0.00 | 672.00 |
March | 1236.26 | 658.14 | 578.13 | 1154.49 | 725.38 | 0.00 | 0.00 | 744.00 |
April | 1577.79 | 839.75 | 738.04 | 1599.05 | 507.67 | 0.00 | 0.00 | 720.00 |
May | 1495.67 | 770.56 | 725.11 | 1599.50 | 376.22 | 0.00 | 0.00 | 744.00 |
June | 1603.27 | 894.46 | 708.81 | 1937.88 | 261.23 | 0.00 | 0.00 | 720.00 |
July | 1446.23 | 707.68 | 738.55 | 1803.18 | 170.67 | 0.00 | 0.00 | 744.00 |
August | 1477.92 | 683.58 | 794.34 | 1776.36 | 201.92 | 0.00 | 0.00 | 744.00 |
September | 1335.05 | 703.17 | 631.88 | 1506.04 | 347.17 | 0.00 | 0.00 | 720.00 |
October | 1221.27 | 759.06 | 462.22 | 1229.86 | 616.23 | 0.00 | 0.00 | 744.00 |
November | 958.72 | 564.04 | 394.68 | 779.86 | 857.68 | 0.00 | 0.00 | 720.00 |
December | 829.19 | 520.02 | 309.16 | 604.89 | 1084.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1262.44 | 685.52 | 576.92 | 1299.88 | 591.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 829.19 | 490.35 | 309.16 | 604.89 | 170.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1603.27 | 894.46 | 794.34 | 1937.88 | 1084.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.00 | 19.39 | 14.61 | 25.68 | 40.79 | 0.00 | 0.00 | 744.00 |
February | 43.76 | 25.28 | 18.48 | 37.30 | 36.86 | 0.00 | 0.00 | 672.00 |
March | 48.88 | 26.02 | 22.86 | 45.65 | 28.68 | 0.00 | 0.00 | 744.00 |
April | 62.38 | 33.20 | 29.18 | 63.22 | 20.07 | 0.00 | 0.00 | 720.00 |
May | 59.14 | 30.47 | 28.67 | 63.24 | 14.88 | 0.00 | 0.00 | 744.00 |
June | 63.39 | 35.37 | 28.03 | 76.62 | 10.33 | 0.00 | 0.00 | 720.00 |
July | 57.18 | 27.98 | 29.20 | 71.30 | 6.75 | 0.00 | 0.00 | 744.00 |
August | 58.44 | 27.03 | 31.41 | 70.24 | 7.98 | 0.00 | 0.00 | 744.00 |
September | 52.79 | 27.80 | 24.98 | 59.55 | 13.73 | 0.00 | 0.00 | 720.00 |
October | 48.29 | 30.01 | 18.28 | 48.63 | 24.36 | 0.00 | 0.00 | 744.00 |
November | 37.91 | 22.30 | 15.61 | 30.83 | 33.91 | 0.00 | 0.00 | 720.00 |
December | 32.79 | 20.56 | 12.22 | 23.92 | 42.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 49.92 | 27.10 | 22.81 | 51.40 | 23.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.79 | 19.39 | 12.22 | 23.92 | 6.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.39 | 35.37 | 31.41 | 76.62 | 42.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.32 | 0.00 | 469.32 | 57.12 | 1679.37 | 0.00 | 0.00 | 744.00 |
February | 586.57 | 0.00 | 586.57 | 144.03 | 1516.64 | 0.00 | 0.00 | 672.00 |
March | 739.88 | 0.00 | 739.88 | 351.42 | 1182.63 | 0.00 | 0.00 | 744.00 |
April | 938.56 | 7.92 | 930.65 | 596.49 | 792.06 | 0.00 | 0.00 | 720.00 |
May | 1020.10 | 65.53 | 954.57 | 792.26 | 570.27 | 0.00 | 0.00 | 744.00 |
June | 1159.03 | 189.37 | 969.67 | 1194.46 | 364.64 | 0.00 | 0.00 | 720.00 |
July | 1063.88 | 88.31 | 975.58 | 1286.64 | 244.45 | 0.00 | 0.00 | 744.00 |
August | 987.02 | 21.95 | 965.07 | 1132.24 | 283.27 | 0.00 | 0.00 | 744.00 |
September | 789.42 | 0.19 | 789.23 | 774.81 | 508.15 | 0.00 | 0.00 | 720.00 |
October | 589.08 | 0.00 | 589.08 | 329.79 | 936.18 | 0.00 | 0.00 | 744.00 |
November | 500.26 | 0.00 | 500.26 | 88.78 | 1364.77 | 0.00 | 0.00 | 720.00 |
December | 399.46 | 0.00 | 399.46 | 13.01 | 1780.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 770.89 | 31.16 | 739.73 | 565.77 | 932.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 399.46 | 0.00 | 399.46 | 13.01 | 244.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1159.03 | 189.37 | 975.58 | 1286.64 | 1780.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.56 | 484.52 | 382.04 | 566.11 | 1008.03 | 0.00 | 0.00 | 744.00 |
February | 1052.74 | 567.53 | 485.21 | 786.89 | 919.59 | 0.00 | 0.00 | 672.00 |
March | 1388.84 | 789.56 | 599.27 | 1254.64 | 717.67 | 0.00 | 0.00 | 744.00 |
April | 1897.50 | 1081.08 | 816.43 | 1922.57 | 492.61 | 0.00 | 0.00 | 720.00 |
May | 1810.18 | 1031.49 | 778.69 | 1935.98 | 371.60 | 0.00 | 0.00 | 744.00 |
June | 1951.35 | 1201.96 | 749.40 | 2334.60 | 236.63 | 0.00 | 0.00 | 720.00 |
July | 1805.76 | 1032.49 | 773.27 | 2242.05 | 159.76 | 0.00 | 0.00 | 744.00 |
August | 1787.12 | 985.24 | 801.88 | 2144.89 | 181.22 | 0.00 | 0.00 | 744.00 |
September | 1487.69 | 832.44 | 655.25 | 1671.01 | 314.74 | 0.00 | 0.00 | 720.00 |
October | 1293.68 | 820.79 | 472.90 | 1252.97 | 563.62 | 0.00 | 0.00 | 744.00 |
November | 1011.13 | 594.45 | 416.68 | 773.76 | 825.31 | 0.00 | 0.00 | 720.00 |
December | 819.44 | 498.77 | 320.67 | 523.30 | 1073.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1432.40 | 827.72 | 604.68 | 1453.72 | 570.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 819.44 | 484.52 | 320.67 | 523.30 | 159.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1951.35 | 1201.96 | 816.43 | 2334.60 | 1073.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3470.94 | 2701.15 | 769.78 | 3573.17 | 1531.23 | 0.00 | 0.00 | 744.00 |
February | 3397.69 | 2482.48 | 915.21 | 3383.65 | 1430.20 | 0.00 | 0.00 | 672.00 |
March | 2502.35 | 1512.90 | 989.45 | 2177.78 | 1161.77 | 0.00 | 0.00 | 744.00 |
April | 1950.90 | 800.53 | 1150.36 | 1408.57 | 815.87 | 0.00 | 0.00 | 720.00 |
May | 1300.80 | 285.68 | 1015.11 | 975.68 | 597.97 | 0.00 | 0.00 | 744.00 |
June | 1099.98 | 134.77 | 965.20 | 1189.74 | 392.42 | 0.00 | 0.00 | 720.00 |
July | 1217.38 | 193.74 | 1023.64 | 1391.23 | 256.78 | 0.00 | 0.00 | 744.00 |
August | 1674.68 | 544.09 | 1130.59 | 1633.55 | 298.31 | 0.00 | 0.00 | 744.00 |
September | 2316.02 | 1291.37 | 1024.65 | 2262.37 | 519.89 | 0.00 | 0.00 | 720.00 |
October | 3170.40 | 2335.37 | 835.03 | 3252.34 | 910.26 | 0.00 | 0.00 | 744.00 |
November | 3531.42 | 2710.78 | 820.64 | 3658.80 | 1259.07 | 0.00 | 0.00 | 720.00 |
December | 3765.41 | 3106.24 | 659.17 | 3972.36 | 1571.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2444.51 | 1503.25 | 941.25 | 2401.61 | 892.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1099.98 | 134.77 | 659.17 | 975.68 | 256.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3765.41 | 3106.24 | 1150.36 | 3972.36 | 1571.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 893.82 | 509.74 | 384.07 | 665.37 | 1077.04 | 0.00 | 0.00 | 744.00 |
February | 1150.50 | 664.59 | 485.91 | 964.84 | 982.12 | 0.00 | 0.00 | 672.00 |
March | 1285.15 | 684.16 | 600.99 | 1179.40 | 773.19 | 0.00 | 0.00 | 744.00 |
April | 1640.19 | 872.96 | 767.23 | 1644.00 | 535.94 | 0.00 | 0.00 | 720.00 |
May | 1554.82 | 801.04 | 753.78 | 1648.80 | 397.57 | 0.00 | 0.00 | 744.00 |
June | 1666.67 | 929.84 | 736.84 | 2010.32 | 270.66 | 0.00 | 0.00 | 720.00 |
July | 1503.42 | 735.67 | 767.75 | 1873.79 | 174.60 | 0.00 | 0.00 | 744.00 |
August | 1536.37 | 710.61 | 825.75 | 1849.27 | 200.98 | 0.00 | 0.00 | 744.00 |
September | 1387.85 | 730.98 | 656.87 | 1572.05 | 342.88 | 0.00 | 0.00 | 720.00 |
October | 1269.57 | 789.08 | 480.49 | 1282.18 | 614.83 | 0.00 | 0.00 | 744.00 |
November | 996.63 | 586.35 | 410.29 | 809.63 | 867.58 | 0.00 | 0.00 | 720.00 |
December | 861.98 | 540.59 | 321.39 | 623.43 | 1117.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1312.36 | 712.63 | 599.73 | 1344.89 | 611.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 861.98 | 509.74 | 321.39 | 623.43 | 174.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1666.67 | 929.84 | 825.75 | 2010.32 | 1117.66 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125702E+10 | 0.00 | 0.125702E+10 | 0.185566E+09 | 0.424763E+10 |
February | 0.141903E+10 | 0.00 | 0.141903E+10 | 0.384318E+09 | 0.347172E+10 |
March | 0.198171E+10 | 0.00 | 0.198171E+10 | 0.979979E+09 | 0.300499E+10 |
April | 0.243275E+10 | 20518880.08 | 0.241223E+10 | 0.156506E+10 | 0.195767E+10 |
May | 0.273224E+10 | 0.175524E+09 | 0.255672E+10 | 0.213128E+10 | 0.146974E+10 |
June | 0.300421E+10 | 0.490836E+09 | 0.251337E+10 | 0.309372E+10 | 0.921709E+09 |
July | 0.284951E+10 | 0.236519E+09 | 0.261299E+10 | 0.343180E+10 | 0.643547E+09 |
August | 0.264364E+10 | 58788316.90 | 0.258485E+10 | 0.302255E+10 | 0.739126E+09 |
September | 0.204619E+10 | 502581.14 | 0.204569E+10 | 0.201620E+10 | 0.125802E+10 |
October | 0.157778E+10 | 0.00 | 0.157778E+10 | 0.910206E+09 | 0.235787E+10 |
November | 0.129669E+10 | 0.00 | 0.129669E+10 | 0.266625E+09 | 0.329445E+10 |
December | 0.106992E+10 | 0.00 | 0.106992E+10 | 49752491.24 | 0.447975E+10 |
Annual Sum or Average | 0.243107E+11 | 0.982688E+09 | 0.233280E+11 | 0.180371E+11 | 0.278462E+11 |
Minimum of Months | 0.106992E+10 | 0.00 | 0.106992E+10 | 49752491.24 | 0.643547E+09 |
Maximum of Months | 0.300421E+10 | 0.490836E+09 | 0.261299E+10 | 0.343180E+10 | 0.447975E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232098E+10 | 0.129773E+10 | 0.102325E+10 | 0.155810E+10 | 0.257308E+10 |
February | 0.254678E+10 | 0.137296E+10 | 0.117382E+10 | 0.193758E+10 | 0.212510E+10 |
March | 0.371986E+10 | 0.211477E+10 | 0.160509E+10 | 0.338324E+10 | 0.184642E+10 |
April | 0.491833E+10 | 0.280215E+10 | 0.211618E+10 | 0.499028E+10 | 0.123534E+10 |
May | 0.484838E+10 | 0.276274E+10 | 0.208564E+10 | 0.518264E+10 | 0.968172E+09 |
June | 0.505791E+10 | 0.311547E+10 | 0.194244E+10 | 0.604034E+10 | 0.603174E+09 |
July | 0.483655E+10 | 0.276541E+10 | 0.207113E+10 | 0.598876E+10 | 0.424175E+09 |
August | 0.478662E+10 | 0.263887E+10 | 0.214776E+10 | 0.573212E+10 | 0.478605E+09 |
September | 0.385610E+10 | 0.215770E+10 | 0.169840E+10 | 0.433189E+10 | 0.789321E+09 |
October | 0.346501E+10 | 0.219839E+10 | 0.126661E+10 | 0.337400E+10 | 0.144292E+10 |
November | 0.262086E+10 | 0.154083E+10 | 0.108003E+10 | 0.204376E+10 | 0.202517E+10 |
December | 0.219479E+10 | 0.133591E+10 | 0.858883E+09 | 0.143593E+10 | 0.272192E+10 |
Annual Sum or Average | 0.451722E+11 | 0.261029E+11 | 0.190692E+11 | 0.459986E+11 | 0.172334E+11 |
Minimum of Months | 0.219479E+10 | 0.129773E+10 | 0.858883E+09 | 0.143593E+10 | 0.424175E+09 |
Maximum of Months | 0.505791E+10 | 0.311547E+10 | 0.214776E+10 | 0.604034E+10 | 0.272192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.929655E+10 | 0.723477E+10 | 0.206179E+10 | 0.963999E+10 | 0.389389E+10 |
February | 0.821968E+10 | 0.600561E+10 | 0.221407E+10 | 0.823425E+10 | 0.328949E+10 |
March | 0.670229E+10 | 0.405215E+10 | 0.265014E+10 | 0.587018E+10 | 0.296912E+10 |
April | 0.505672E+10 | 0.207498E+10 | 0.298174E+10 | 0.367488E+10 | 0.202570E+10 |
May | 0.348405E+10 | 0.765167E+09 | 0.271888E+10 | 0.262437E+10 | 0.154333E+10 |
June | 0.285114E+10 | 0.349336E+09 | 0.250181E+10 | 0.308076E+10 | 0.989518E+09 |
July | 0.326064E+10 | 0.518920E+09 | 0.274172E+10 | 0.371463E+10 | 0.676060E+09 |
August | 0.448547E+10 | 0.145730E+10 | 0.302817E+10 | 0.436901E+10 | 0.779530E+09 |
September | 0.600313E+10 | 0.334724E+10 | 0.265589E+10 | 0.587636E+10 | 0.129362E+10 |
October | 0.849159E+10 | 0.625505E+10 | 0.223654E+10 | 0.875119E+10 | 0.231570E+10 |
November | 0.915344E+10 | 0.702635E+10 | 0.212710E+10 | 0.955243E+10 | 0.307834E+10 |
December | 0.100853E+11 | 0.831974E+10 | 0.176553E+10 | 0.107081E+11 | 0.397346E+10 |
Annual Sum or Average | 0.770900E+11 | 0.474066E+11 | 0.296834E+11 | 0.760961E+11 | 0.268278E+11 |
Minimum of Months | 0.285114E+10 | 0.349336E+09 | 0.176553E+10 | 0.262437E+10 | 0.676060E+09 |
Maximum of Months | 0.100853E+11 | 0.831974E+10 | 0.302817E+10 | 0.107081E+11 | 0.397346E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239400E+10 | 0.136530E+10 | 0.102870E+10 | 0.180436E+10 | 0.274097E+10 |
February | 0.278330E+10 | 0.160777E+10 | 0.117552E+10 | 0.235370E+10 | 0.226274E+10 |
March | 0.344215E+10 | 0.183246E+10 | 0.160968E+10 | 0.317794E+10 | 0.197871E+10 |
April | 0.425137E+10 | 0.226271E+10 | 0.198866E+10 | 0.427099E+10 | 0.133092E+10 |
May | 0.416443E+10 | 0.214551E+10 | 0.201892E+10 | 0.442216E+10 | 0.102541E+10 |
June | 0.432001E+10 | 0.241013E+10 | 0.190988E+10 | 0.520825E+10 | 0.683107E+09 |
July | 0.402676E+10 | 0.197041E+10 | 0.205635E+10 | 0.501178E+10 | 0.458624E+09 |
August | 0.411501E+10 | 0.190331E+10 | 0.221170E+10 | 0.494913E+10 | 0.525151E+09 |
September | 0.359730E+10 | 0.189469E+10 | 0.170261E+10 | 0.408314E+10 | 0.851746E+09 |
October | 0.340042E+10 | 0.211347E+10 | 0.128695E+10 | 0.345037E+10 | 0.156145E+10 |
November | 0.258327E+10 | 0.151981E+10 | 0.106346E+10 | 0.212295E+10 | 0.211662E+10 |
December | 0.230872E+10 | 0.144792E+10 | 0.860803E+09 | 0.168766E+10 | 0.283150E+10 |
Annual Sum or Average | 0.413867E+11 | 0.224735E+11 | 0.189132E+11 | 0.425424E+11 | 0.183669E+11 |
Minimum of Months | 0.230872E+10 | 0.136530E+10 | 0.860803E+09 | 0.168766E+10 | 0.458624E+09 |
Maximum of Months | 0.432001E+10 | 0.241013E+10 | 0.221170E+10 | 0.520825E+10 | 0.283150E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418988E+09 | 0.00 | 0.418988E+09 | 59689131.35 | 0.146356E+10 |
February | 0.472988E+09 | 0.00 | 0.472988E+09 | 0.133635E+09 | 0.117462E+10 |
March | 0.660537E+09 | 0.00 | 0.660537E+09 | 0.347044E+09 | 0.995977E+09 |
April | 0.810879E+09 | 6839303.10 | 0.804040E+09 | 0.548673E+09 | 0.642870E+09 |
May | 0.910705E+09 | 58505297.46 | 0.852200E+09 | 0.735690E+09 | 0.480329E+09 |
June | 0.100136E+10 | 0.163604E+09 | 0.837751E+09 | 0.104763E+10 | 0.301211E+09 |
July | 0.949790E+09 | 78835782.42 | 0.870954E+09 | 0.115839E+10 | 0.208908E+09 |
August | 0.881171E+09 | 19595178.50 | 0.861576E+09 | 0.101589E+10 | 0.248539E+09 |
September | 0.682030E+09 | 167519.12 | 0.681863E+09 | 0.670071E+09 | 0.442928E+09 |
October | 0.525901E+09 | 0.00 | 0.525901E+09 | 0.294664E+09 | 0.845958E+09 |
November | 0.432208E+09 | 0.00 | 0.432208E+09 | 78960033.34 | 0.118554E+10 |
December | 0.356622E+09 | 0.00 | 0.356622E+09 | 12572981.16 | 0.157745E+10 |
Annual Sum or Average | 0.810318E+10 | 0.327547E+09 | 0.777563E+10 | 0.610290E+10 | 0.956790E+10 |
Minimum of Months | 0.356622E+09 | 0.00 | 0.356622E+09 | 12572981.16 | 0.208908E+09 |
Maximum of Months | 0.100136E+10 | 0.163604E+09 | 0.870954E+09 | 0.115839E+10 | 0.157745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419015E+09 | 0.00 | 0.419015E+09 | 59692903.60 | 0.146365E+10 |
February | 0.473017E+09 | 0.00 | 0.473017E+09 | 0.133644E+09 | 0.117470E+10 |
March | 0.660579E+09 | 0.00 | 0.660579E+09 | 0.347066E+09 | 0.996040E+09 |
April | 0.810930E+09 | 6839735.33 | 0.804091E+09 | 0.548707E+09 | 0.642910E+09 |
May | 0.910763E+09 | 58508994.90 | 0.852254E+09 | 0.735737E+09 | 0.480359E+09 |
June | 0.100142E+10 | 0.163614E+09 | 0.837804E+09 | 0.104769E+10 | 0.301230E+09 |
July | 0.949850E+09 | 78840764.71 | 0.871010E+09 | 0.115846E+10 | 0.208921E+09 |
August | 0.881227E+09 | 19596416.89 | 0.861631E+09 | 0.101596E+10 | 0.248555E+09 |
September | 0.682073E+09 | 167529.71 | 0.681906E+09 | 0.670113E+09 | 0.442956E+09 |
October | 0.525935E+09 | 0.00 | 0.525935E+09 | 0.294683E+09 | 0.846011E+09 |
November | 0.432236E+09 | 0.00 | 0.432236E+09 | 78965023.48 | 0.118562E+10 |
December | 0.356645E+09 | 0.00 | 0.356645E+09 | 12573775.76 | 0.157755E+10 |
Annual Sum or Average | 0.810369E+10 | 0.327568E+09 | 0.777612E+10 | 0.610329E+10 | 0.956851E+10 |
Minimum of Months | 0.356645E+09 | 0.00 | 0.356645E+09 | 12573775.76 | 0.208921E+09 |
Maximum of Months | 0.100142E+10 | 0.163614E+09 | 0.871010E+09 | 0.115846E+10 | 0.157755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419015E+09 | 0.00 | 0.419015E+09 | 59692903.60 | 0.146365E+10 |
February | 0.473017E+09 | 0.00 | 0.473017E+09 | 0.133644E+09 | 0.117470E+10 |
March | 0.660579E+09 | 0.00 | 0.660579E+09 | 0.347066E+09 | 0.996040E+09 |
April | 0.810930E+09 | 6839735.33 | 0.804091E+09 | 0.548707E+09 | 0.642910E+09 |
May | 0.910763E+09 | 58508994.90 | 0.852254E+09 | 0.735737E+09 | 0.480359E+09 |
June | 0.100142E+10 | 0.163614E+09 | 0.837804E+09 | 0.104769E+10 | 0.301230E+09 |
July | 0.949850E+09 | 78840764.71 | 0.871010E+09 | 0.115846E+10 | 0.208921E+09 |
August | 0.881227E+09 | 19596416.89 | 0.861631E+09 | 0.101596E+10 | 0.248555E+09 |
September | 0.682073E+09 | 167529.71 | 0.681906E+09 | 0.670113E+09 | 0.442956E+09 |
October | 0.525935E+09 | 0.00 | 0.525935E+09 | 0.294683E+09 | 0.846011E+09 |
November | 0.432236E+09 | 0.00 | 0.432236E+09 | 78965023.48 | 0.118562E+10 |
December | 0.356645E+09 | 0.00 | 0.356645E+09 | 12573775.76 | 0.157755E+10 |
Annual Sum or Average | 0.810369E+10 | 0.327568E+09 | 0.777612E+10 | 0.610329E+10 | 0.956851E+10 |
Minimum of Months | 0.356645E+09 | 0.00 | 0.356645E+09 | 12573775.76 | 0.208921E+09 |
Maximum of Months | 0.100142E+10 | 0.163614E+09 | 0.871010E+09 | 0.115846E+10 | 0.157755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223268E+10 | 0.124836E+10 | 0.984327E+09 | 0.148179E+10 | 0.258840E+10 |
February | 0.244990E+10 | 0.132073E+10 | 0.112917E+10 | 0.186939E+10 | 0.211001E+10 |
March | 0.357834E+10 | 0.203431E+10 | 0.154403E+10 | 0.328169E+10 | 0.182091E+10 |
April | 0.473122E+10 | 0.269554E+10 | 0.203568E+10 | 0.483129E+10 | 0.122911E+10 |
May | 0.466393E+10 | 0.265763E+10 | 0.200630E+10 | 0.501470E+10 | 0.965714E+09 |
June | 0.486549E+10 | 0.299694E+10 | 0.186855E+10 | 0.583182E+10 | 0.604517E+09 |
July | 0.465255E+10 | 0.266020E+10 | 0.199235E+10 | 0.577774E+10 | 0.432554E+09 |
August | 0.460453E+10 | 0.253847E+10 | 0.206606E+10 | 0.552372E+10 | 0.498107E+09 |
September | 0.370940E+10 | 0.207561E+10 | 0.163380E+10 | 0.415719E+10 | 0.833687E+09 |
October | 0.333319E+10 | 0.211476E+10 | 0.121843E+10 | 0.321884E+10 | 0.152495E+10 |
November | 0.252115E+10 | 0.148220E+10 | 0.103895E+10 | 0.192766E+10 | 0.212850E+10 |
December | 0.211130E+10 | 0.128509E+10 | 0.826211E+09 | 0.135849E+10 | 0.279450E+10 |
Annual Sum or Average | 0.434537E+11 | 0.251098E+11 | 0.183439E+11 | 0.442743E+11 | 0.175310E+11 |
Minimum of Months | 0.211130E+10 | 0.124836E+10 | 0.826211E+09 | 0.135849E+10 | 0.432554E+09 |
Maximum of Months | 0.486549E+10 | 0.299694E+10 | 0.206606E+10 | 0.583182E+10 | 0.279450E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88278335.01 | 49358943.34 | 38919391.67 | 58588618.01 | 0.102343E+09 |
February | 96866785.56 | 52220426.03 | 44646359.53 | 73913979.52 | 83427823.55 |
March | 0.141484E+09 | 80434762.35 | 61049736.65 | 0.129755E+09 | 71997323.75 |
April | 0.187068E+09 | 0.106579E+09 | 80488909.54 | 0.191025E+09 | 48597876.94 |
May | 0.184408E+09 | 0.105080E+09 | 79327415.28 | 0.198277E+09 | 38183453.20 |
June | 0.192377E+09 | 0.118496E+09 | 73880921.40 | 0.230585E+09 | 23902050.60 |
July | 0.183958E+09 | 0.105182E+09 | 78775599.00 | 0.228447E+09 | 17102815.43 |
August | 0.182059E+09 | 0.100369E+09 | 81689980.43 | 0.218403E+09 | 19694721.34 |
September | 0.146666E+09 | 82067593.02 | 64598821.65 | 0.164372E+09 | 32963243.51 |
October | 0.131791E+09 | 83615548.40 | 48175663.98 | 0.127270E+09 | 60295111.49 |
November | 99684048.22 | 58605042.65 | 41079005.57 | 76217755.95 | 84158854.63 |
December | 83478785.57 | 50811145.22 | 32667640.35 | 53713507.11 | 0.110492E+09 |
Annual Sum or Average | 0.171812E+10 | 0.992820E+09 | 0.725299E+09 | 0.175057E+10 | 0.693159E+09 |
Minimum of Months | 83478785.57 | 49358943.34 | 32667640.35 | 53713507.11 | 17102815.43 |
Maximum of Months | 0.192377E+09 | 0.118496E+09 | 81689980.43 | 0.230585E+09 | 0.110492E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309895E+10 | 0.241167E+10 | 0.687281E+09 | 0.323439E+10 | 0.138250E+10 |
February | 0.273998E+10 | 0.200194E+10 | 0.738045E+09 | 0.277219E+10 | 0.114848E+10 |
March | 0.223416E+10 | 0.135076E+10 | 0.883403E+09 | 0.199065E+10 | 0.100205E+10 |
April | 0.168562E+10 | 0.691682E+09 | 0.993940E+09 | 0.125946E+10 | 0.666664E+09 |
May | 0.116138E+10 | 0.255064E+09 | 0.906317E+09 | 0.909075E+09 | 0.496078E+09 |
June | 0.950405E+09 | 0.116449E+09 | 0.833956E+09 | 0.104256E+10 | 0.319828E+09 |
July | 0.108691E+10 | 0.172979E+09 | 0.913930E+09 | 0.124737E+10 | 0.221009E+09 |
August | 0.149520E+10 | 0.485783E+09 | 0.100942E+10 | 0.146058E+10 | 0.267168E+09 |
September | 0.200110E+10 | 0.111578E+10 | 0.885320E+09 | 0.195559E+10 | 0.468089E+09 |
October | 0.283062E+10 | 0.208508E+10 | 0.745535E+09 | 0.291741E+10 | 0.847437E+09 |
November | 0.305124E+10 | 0.234219E+10 | 0.709052E+09 | 0.319101E+10 | 0.112942E+10 |
December | 0.336187E+10 | 0.277334E+10 | 0.588528E+09 | 0.358832E+10 | 0.143495E+10 |
Annual Sum or Average | 0.256974E+11 | 0.158027E+11 | 0.989472E+10 | 0.255686E+11 | 0.938367E+10 |
Minimum of Months | 0.950405E+09 | 0.116449E+09 | 0.588528E+09 | 0.909075E+09 | 0.221009E+09 |
Maximum of Months | 0.336187E+10 | 0.277334E+10 | 0.100942E+10 | 0.358832E+10 | 0.143495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309895E+10 | 0.241167E+10 | 0.687281E+09 | 0.323439E+10 | 0.138250E+10 |
February | 0.273998E+10 | 0.200194E+10 | 0.738045E+09 | 0.277219E+10 | 0.114848E+10 |
March | 0.223416E+10 | 0.135076E+10 | 0.883403E+09 | 0.199065E+10 | 0.100205E+10 |
April | 0.168562E+10 | 0.691682E+09 | 0.993940E+09 | 0.125946E+10 | 0.666664E+09 |
May | 0.116138E+10 | 0.255064E+09 | 0.906317E+09 | 0.909075E+09 | 0.496078E+09 |
June | 0.950405E+09 | 0.116449E+09 | 0.833956E+09 | 0.104256E+10 | 0.319828E+09 |
July | 0.108691E+10 | 0.172979E+09 | 0.913930E+09 | 0.124737E+10 | 0.221009E+09 |
August | 0.149520E+10 | 0.485783E+09 | 0.100942E+10 | 0.146058E+10 | 0.267168E+09 |
September | 0.200110E+10 | 0.111578E+10 | 0.885320E+09 | 0.195559E+10 | 0.468089E+09 |
October | 0.283062E+10 | 0.208508E+10 | 0.745535E+09 | 0.291741E+10 | 0.847437E+09 |
November | 0.305124E+10 | 0.234219E+10 | 0.709052E+09 | 0.319101E+10 | 0.112942E+10 |
December | 0.336187E+10 | 0.277334E+10 | 0.588528E+09 | 0.358832E+10 | 0.143495E+10 |
Annual Sum or Average | 0.256974E+11 | 0.158027E+11 | 0.989472E+10 | 0.255686E+11 | 0.938367E+10 |
Minimum of Months | 0.950405E+09 | 0.116449E+09 | 0.588528E+09 | 0.909075E+09 | 0.221009E+09 |
Maximum of Months | 0.336187E+10 | 0.277334E+10 | 0.100942E+10 | 0.358832E+10 | 0.143495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309875E+10 | 0.241152E+10 | 0.687238E+09 | 0.323418E+10 | 0.138241E+10 |
February | 0.273981E+10 | 0.200181E+10 | 0.737998E+09 | 0.277201E+10 | 0.114840E+10 |
March | 0.223402E+10 | 0.135068E+10 | 0.883347E+09 | 0.199053E+10 | 0.100199E+10 |
April | 0.168552E+10 | 0.691639E+09 | 0.993877E+09 | 0.125938E+10 | 0.666622E+09 |
May | 0.116131E+10 | 0.255048E+09 | 0.906260E+09 | 0.909017E+09 | 0.496047E+09 |
June | 0.950345E+09 | 0.116442E+09 | 0.833903E+09 | 0.104249E+10 | 0.319808E+09 |
July | 0.108684E+10 | 0.172968E+09 | 0.913872E+09 | 0.124729E+10 | 0.220995E+09 |
August | 0.149511E+10 | 0.485752E+09 | 0.100935E+10 | 0.146049E+10 | 0.267151E+09 |
September | 0.200098E+10 | 0.111571E+10 | 0.885264E+09 | 0.195547E+10 | 0.468060E+09 |
October | 0.283044E+10 | 0.208495E+10 | 0.745488E+09 | 0.291723E+10 | 0.847384E+09 |
November | 0.305105E+10 | 0.234204E+10 | 0.709007E+09 | 0.319080E+10 | 0.112935E+10 |
December | 0.336165E+10 | 0.277316E+10 | 0.588490E+09 | 0.358810E+10 | 0.143485E+10 |
Annual Sum or Average | 0.256958E+11 | 0.158017E+11 | 0.989410E+10 | 0.255670E+11 | 0.938307E+10 |
Minimum of Months | 0.950345E+09 | 0.116442E+09 | 0.588490E+09 | 0.909017E+09 | 0.220995E+09 |
Maximum of Months | 0.336165E+10 | 0.277316E+10 | 0.100935E+10 | 0.358810E+10 | 0.143485E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230292E+10 | 0.131336E+10 | 0.989567E+09 | 0.173991E+10 | 0.276314E+10 |
February | 0.267741E+10 | 0.154661E+10 | 0.113081E+10 | 0.228237E+10 | 0.225549E+10 |
March | 0.331120E+10 | 0.176275E+10 | 0.154845E+10 | 0.309218E+10 | 0.194286E+10 |
April | 0.408964E+10 | 0.217663E+10 | 0.191301E+10 | 0.414475E+10 | 0.131587E+10 |
May | 0.400600E+10 | 0.206388E+10 | 0.194212E+10 | 0.428411E+10 | 0.100767E+10 |
June | 0.415567E+10 | 0.231844E+10 | 0.183723E+10 | 0.502298E+10 | 0.677107E+09 |
July | 0.387357E+10 | 0.189544E+10 | 0.197813E+10 | 0.482964E+10 | 0.457116E+09 |
August | 0.395846E+10 | 0.183090E+10 | 0.212757E+10 | 0.475779E+10 | 0.540830E+09 |
September | 0.346045E+10 | 0.182261E+10 | 0.163784E+10 | 0.390365E+10 | 0.899856E+09 |
October | 0.327106E+10 | 0.203306E+10 | 0.123800E+10 | 0.329407E+10 | 0.165050E+10 |
November | 0.248500E+10 | 0.146199E+10 | 0.102301E+10 | 0.202140E+10 | 0.222311E+10 |
December | 0.222089E+10 | 0.139283E+10 | 0.828059E+09 | 0.162014E+10 | 0.290494E+10 |
Annual Sum or Average | 0.398123E+11 | 0.216185E+11 | 0.181938E+11 | 0.409930E+11 | 0.186385E+11 |
Minimum of Months | 0.222089E+10 | 0.131336E+10 | 0.828059E+09 | 0.162014E+10 | 0.457116E+09 |
Maximum of Months | 0.415567E+10 | 0.231844E+10 | 0.212757E+10 | 0.502298E+10 | 0.290494E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91055285.65 | 51928774.80 | 39126510.84 | 68794173.03 | 0.109252E+09 |
February | 0.105862E+09 | 61151252.51 | 44710954.67 | 90242543.13 | 89179931.85 |
March | 0.130922E+09 | 69697297.75 | 61224288.10 | 0.122261E+09 | 76818837.70 |
April | 0.161700E+09 | 86061602.28 | 75638497.01 | 0.163879E+09 | 52028227.79 |
May | 0.158393E+09 | 81603702.50 | 76789671.39 | 0.169389E+09 | 39842298.58 |
June | 0.164311E+09 | 91668776.46 | 72642246.56 | 0.198604E+09 | 26772178.13 |
July | 0.153157E+09 | 74943945.03 | 78213264.24 | 0.190959E+09 | 18073929.18 |
August | 0.156514E+09 | 72391785.16 | 84121832.24 | 0.188118E+09 | 21383928.49 |
September | 0.136823E+09 | 72064037.54 | 64758564.76 | 0.154347E+09 | 35579466.64 |
October | 0.129334E+09 | 80385107.17 | 48949181.29 | 0.130244E+09 | 65259202.92 |
November | 98254349.58 | 57805617.15 | 40448732.43 | 79923855.08 | 87899838.46 |
December | 87811771.52 | 55071149.01 | 32740622.51 | 64058572.81 | 0.114859E+09 |
Annual Sum or Average | 0.157414E+10 | 0.854773E+09 | 0.719364E+09 | 0.162082E+10 | 0.736948E+09 |
Minimum of Months | 87811771.52 | 51928774.80 | 32740622.51 | 64058572.81 | 18073929.18 |
Maximum of Months | 0.164311E+09 | 91668776.46 | 84121832.24 | 0.198604E+09 | 0.114859E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125702E+10 | 0.00 | 0.125702E+10 | 0.152996E+09 | 0.449804E+10 |
February | 0.141903E+10 | 0.00 | 0.141903E+10 | 0.348448E+09 | 0.366906E+10 |
March | 0.198171E+10 | 0.00 | 0.198171E+10 | 0.941242E+09 | 0.316755E+10 |
April | 0.243275E+10 | 20518880.08 | 0.241223E+10 | 0.154611E+10 | 0.205301E+10 |
May | 0.273224E+10 | 0.175524E+09 | 0.255672E+10 | 0.212199E+10 | 0.152741E+10 |
June | 0.300421E+10 | 0.490836E+09 | 0.251337E+10 | 0.309604E+10 | 0.945157E+09 |
July | 0.284951E+10 | 0.236519E+09 | 0.261299E+10 | 0.344613E+10 | 0.654729E+09 |
August | 0.264364E+10 | 58788316.90 | 0.258485E+10 | 0.303258E+10 | 0.758721E+09 |
September | 0.204619E+10 | 502581.14 | 0.204569E+10 | 0.200830E+10 | 0.131712E+10 |
October | 0.157778E+10 | 0.00 | 0.157778E+10 | 0.883309E+09 | 0.250747E+10 |
November | 0.129669E+10 | 0.00 | 0.129669E+10 | 0.230106E+09 | 0.353748E+10 |
December | 0.106992E+10 | 0.00 | 0.106992E+10 | 34858003.10 | 0.476985E+10 |
Annual Sum or Average | 0.243107E+11 | 0.982688E+09 | 0.233280E+11 | 0.178421E+11 | 0.294056E+11 |
Minimum of Months | 0.106992E+10 | 0.00 | 0.106992E+10 | 34858003.10 | 0.654729E+09 |
Maximum of Months | 0.300421E+10 | 0.490836E+09 | 0.261299E+10 | 0.344613E+10 | 0.476985E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232098E+10 | 0.129773E+10 | 0.102325E+10 | 0.151626E+10 | 0.269990E+10 |
February | 0.254678E+10 | 0.137296E+10 | 0.117382E+10 | 0.190364E+10 | 0.222468E+10 |
March | 0.371986E+10 | 0.211477E+10 | 0.160509E+10 | 0.336044E+10 | 0.192220E+10 |
April | 0.491833E+10 | 0.280215E+10 | 0.211618E+10 | 0.498331E+10 | 0.127684E+10 |
May | 0.484838E+10 | 0.276274E+10 | 0.208564E+10 | 0.518533E+10 | 0.995305E+09 |
June | 0.505791E+10 | 0.311547E+10 | 0.194244E+10 | 0.605127E+10 | 0.613355E+09 |
July | 0.483655E+10 | 0.276541E+10 | 0.207113E+10 | 0.600510E+10 | 0.427901E+09 |
August | 0.478662E+10 | 0.263887E+10 | 0.214776E+10 | 0.574487E+10 | 0.485380E+09 |
September | 0.385610E+10 | 0.215770E+10 | 0.169840E+10 | 0.433126E+10 | 0.815815E+09 |
October | 0.346501E+10 | 0.219839E+10 | 0.126661E+10 | 0.335596E+10 | 0.150959E+10 |
November | 0.262086E+10 | 0.154083E+10 | 0.108003E+10 | 0.200558E+10 | 0.213921E+10 |
December | 0.219479E+10 | 0.133591E+10 | 0.858883E+09 | 0.140160E+10 | 0.287446E+10 |
Annual Sum or Average | 0.451722E+11 | 0.261029E+11 | 0.190692E+11 | 0.458446E+11 | 0.179846E+11 |
Minimum of Months | 0.219479E+10 | 0.129773E+10 | 0.858883E+09 | 0.140160E+10 | 0.427901E+09 |
Maximum of Months | 0.505791E+10 | 0.311547E+10 | 0.214776E+10 | 0.605127E+10 | 0.287446E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.929655E+10 | 0.723477E+10 | 0.206179E+10 | 0.957037E+10 | 0.410124E+10 |
February | 0.821968E+10 | 0.600561E+10 | 0.221407E+10 | 0.818573E+10 | 0.345994E+10 |
March | 0.670229E+10 | 0.405215E+10 | 0.265014E+10 | 0.583297E+10 | 0.311170E+10 |
April | 0.505672E+10 | 0.207498E+10 | 0.298174E+10 | 0.365102E+10 | 0.211474E+10 |
May | 0.348405E+10 | 0.765167E+09 | 0.271888E+10 | 0.261327E+10 | 0.160160E+10 |
June | 0.285114E+10 | 0.349336E+09 | 0.250181E+10 | 0.308380E+10 | 0.101716E+10 |
July | 0.326064E+10 | 0.518920E+09 | 0.274172E+10 | 0.372628E+10 | 0.687761E+09 |
August | 0.448547E+10 | 0.145730E+10 | 0.302817E+10 | 0.437530E+10 | 0.798988E+09 |
September | 0.600313E+10 | 0.334724E+10 | 0.265589E+10 | 0.586405E+10 | 0.134755E+10 |
October | 0.849159E+10 | 0.625505E+10 | 0.223654E+10 | 0.871107E+10 | 0.243804E+10 |
November | 0.915344E+10 | 0.702635E+10 | 0.212710E+10 | 0.948361E+10 | 0.326352E+10 |
December | 0.100853E+11 | 0.831974E+10 | 0.176553E+10 | 0.106396E+11 | 0.420834E+10 |
Annual Sum or Average | 0.770900E+11 | 0.474066E+11 | 0.296834E+11 | 0.757370E+11 | 0.281506E+11 |
Minimum of Months | 0.285114E+10 | 0.349336E+09 | 0.176553E+10 | 0.261327E+10 | 0.687761E+09 |
Maximum of Months | 0.100853E+11 | 0.831974E+10 | 0.302817E+10 | 0.106396E+11 | 0.420834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239400E+10 | 0.136530E+10 | 0.102870E+10 | 0.178213E+10 | 0.288475E+10 |
February | 0.278330E+10 | 0.160777E+10 | 0.117552E+10 | 0.233415E+10 | 0.237594E+10 |
March | 0.344215E+10 | 0.183246E+10 | 0.160968E+10 | 0.315891E+10 | 0.207092E+10 |
April | 0.425137E+10 | 0.226271E+10 | 0.198866E+10 | 0.426124E+10 | 0.138915E+10 |
May | 0.416443E+10 | 0.214551E+10 | 0.201892E+10 | 0.441615E+10 | 0.106486E+10 |
June | 0.432001E+10 | 0.241013E+10 | 0.190988E+10 | 0.521074E+10 | 0.701547E+09 |
July | 0.402676E+10 | 0.197041E+10 | 0.205635E+10 | 0.501877E+10 | 0.467639E+09 |
August | 0.411501E+10 | 0.190331E+10 | 0.221170E+10 | 0.495310E+10 | 0.538307E+09 |
September | 0.359730E+10 | 0.189469E+10 | 0.170261E+10 | 0.407475E+10 | 0.888748E+09 |
October | 0.340042E+10 | 0.211347E+10 | 0.128695E+10 | 0.343419E+10 | 0.164675E+10 |
November | 0.258327E+10 | 0.151981E+10 | 0.106346E+10 | 0.209855E+10 | 0.224878E+10 |
December | 0.230872E+10 | 0.144792E+10 | 0.860803E+09 | 0.166979E+10 | 0.299354E+10 |
Annual Sum or Average | 0.413867E+11 | 0.224735E+11 | 0.189132E+11 | 0.424125E+11 | 0.192709E+11 |
Minimum of Months | 0.230872E+10 | 0.136530E+10 | 0.860803E+09 | 0.166979E+10 | 0.467639E+09 |
Maximum of Months | 0.432001E+10 | 0.241013E+10 | 0.221170E+10 | 0.521074E+10 | 0.299354E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 69.28 | 1585.88 | 469.32 | 0.00 | 469.32 | 0.00 | 0.00 |
February | 158.86 | 1435.07 | 586.57 | 0.00 | 586.57 | 0.00 | 0.00 |
March | 365.88 | 1121.93 | 739.88 | 0.00 | 739.88 | 0.00 | 0.00 |
April | 603.80 | 755.27 | 938.56 | 7.92 | 930.65 | 0.00 | 0.00 |
May | 795.73 | 548.74 | 1020.10 | 65.53 | 954.57 | 0.00 | 0.00 |
June | 1193.57 | 355.60 | 1159.03 | 189.37 | 969.67 | 0.00 | 0.00 |
July | 1281.29 | 240.27 | 1063.88 | 88.31 | 975.58 | 0.00 | 0.00 |
August | 1128.49 | 275.96 | 987.02 | 21.95 | 965.07 | 0.00 | 0.00 |
September | 777.85 | 485.35 | 789.42 | 0.19 | 789.23 | 0.00 | 0.00 |
October | 339.83 | 880.33 | 589.08 | 0.00 | 589.08 | 0.00 | 0.00 |
November | 102.86 | 1271.01 | 500.26 | 0.00 | 500.26 | 0.00 | 0.00 |
December | 18.58 | 1672.55 | 399.46 | 0.00 | 399.46 | 0.00 | 0.00 |
Annual Sum or Average | 571.95 | 883.00 | 770.89 | 31.16 | 739.73 | 0.00 | 0.00 |
Minimum of Months | 18.58 | 240.27 | 399.46 | 0.00 | 399.46 | 0.00 | 0.00 |
Maximum of Months | 1281.29 | 1672.55 | 1159.03 | 189.37 | 975.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 581.73 | 960.68 | 866.56 | 484.52 | 382.04 | 0.00 | 0.00 |
February | 800.92 | 878.43 | 1052.74 | 567.53 | 485.21 | 0.00 | 0.00 |
March | 1263.16 | 689.37 | 1388.84 | 789.56 | 599.27 | 0.00 | 0.00 |
April | 1925.26 | 476.60 | 1897.50 | 1081.08 | 816.43 | 0.00 | 0.00 |
May | 1934.97 | 361.47 | 1810.18 | 1031.49 | 778.69 | 0.00 | 0.00 |
June | 2330.38 | 232.71 | 1951.35 | 1201.96 | 749.40 | 0.00 | 0.00 |
July | 2235.95 | 158.37 | 1805.76 | 1032.49 | 773.27 | 0.00 | 0.00 |
August | 2140.13 | 178.69 | 1787.12 | 985.24 | 801.88 | 0.00 | 0.00 |
September | 1671.26 | 304.52 | 1487.69 | 832.44 | 655.25 | 0.00 | 0.00 |
October | 1259.71 | 538.72 | 1293.68 | 820.79 | 472.90 | 0.00 | 0.00 |
November | 788.49 | 781.32 | 1011.13 | 594.45 | 416.68 | 0.00 | 0.00 |
December | 536.11 | 1016.25 | 819.44 | 498.77 | 320.67 | 0.00 | 0.00 |
Annual Sum or Average | 1458.61 | 546.47 | 1432.40 | 827.72 | 604.68 | 0.00 | 0.00 |
Minimum of Months | 536.11 | 158.37 | 819.44 | 484.52 | 320.67 | 0.00 | 0.00 |
Maximum of Months | 2330.38 | 1016.25 | 1951.35 | 1201.96 | 816.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3599.16 | 1453.81 | 3470.94 | 2701.15 | 769.78 | 0.00 | 0.00 |
February | 3403.71 | 1359.74 | 3397.69 | 2482.48 | 915.21 | 0.00 | 0.00 |
March | 2191.67 | 1108.54 | 2502.35 | 1512.90 | 989.45 | 0.00 | 0.00 |
April | 1417.78 | 781.52 | 1950.90 | 800.53 | 1150.36 | 0.00 | 0.00 |
May | 979.83 | 576.22 | 1300.80 | 285.68 | 1015.11 | 0.00 | 0.00 |
June | 1188.56 | 381.76 | 1099.98 | 134.77 | 965.20 | 0.00 | 0.00 |
July | 1386.88 | 252.41 | 1217.38 | 193.74 | 1023.64 | 0.00 | 0.00 |
August | 1631.20 | 291.04 | 1674.68 | 544.09 | 1130.59 | 0.00 | 0.00 |
September | 2267.11 | 499.08 | 2316.02 | 1291.37 | 1024.65 | 0.00 | 0.00 |
October | 3267.32 | 864.58 | 3170.40 | 2335.37 | 835.03 | 0.00 | 0.00 |
November | 3685.35 | 1187.63 | 3531.42 | 2710.78 | 820.64 | 0.00 | 0.00 |
December | 3997.95 | 1483.52 | 3765.41 | 3106.24 | 659.17 | 0.00 | 0.00 |
Annual Sum or Average | 2412.99 | 850.70 | 2444.51 | 1503.25 | 941.25 | 0.00 | 0.00 |
Minimum of Months | 979.83 | 252.41 | 1099.98 | 134.77 | 659.17 | 0.00 | 0.00 |
Maximum of Months | 3997.95 | 1483.52 | 3765.41 | 3106.24 | 1150.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 673.67 | 1023.36 | 893.82 | 509.74 | 384.07 | 0.00 | 0.00 |
February | 972.93 | 935.33 | 1150.50 | 664.59 | 485.91 | 0.00 | 0.00 |
March | 1186.51 | 738.76 | 1285.15 | 684.16 | 600.99 | 0.00 | 0.00 |
April | 1647.76 | 513.47 | 1640.19 | 872.96 | 767.23 | 0.00 | 0.00 |
May | 1651.04 | 382.84 | 1554.82 | 801.04 | 753.78 | 0.00 | 0.00 |
June | 2009.35 | 263.54 | 1666.67 | 929.84 | 736.84 | 0.00 | 0.00 |
July | 1871.18 | 171.23 | 1503.42 | 735.67 | 767.75 | 0.00 | 0.00 |
August | 1847.79 | 196.07 | 1536.37 | 710.61 | 825.75 | 0.00 | 0.00 |
September | 1575.28 | 328.61 | 1387.85 | 730.98 | 656.87 | 0.00 | 0.00 |
October | 1288.22 | 582.98 | 1269.57 | 789.08 | 480.49 | 0.00 | 0.00 |
November | 819.04 | 816.60 | 996.63 | 586.35 | 410.29 | 0.00 | 0.00 |
December | 630.10 | 1057.16 | 861.98 | 540.59 | 321.39 | 0.00 | 0.00 |
Annual Sum or Average | 1349.01 | 582.41 | 1312.36 | 712.63 | 599.73 | 0.00 | 0.00 |
Minimum of Months | 630.10 | 171.23 | 861.98 | 509.74 | 321.39 | 0.00 | 0.00 |
Maximum of Months | 2009.35 | 1057.16 | 1666.67 | 929.84 | 825.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 66.86 | 1639.36 | 469.32 | 0.00 | 469.32 | 0.00 | 0.00 |
February | 165.73 | 1456.69 | 586.57 | 0.00 | 586.57 | 0.00 | 0.00 |
March | 388.73 | 1115.61 | 739.88 | 0.00 | 739.88 | 0.00 | 0.00 |
April | 635.06 | 744.09 | 938.56 | 7.92 | 930.64 | 0.00 | 0.00 |
May | 824.06 | 538.03 | 1020.10 | 65.53 | 954.57 | 0.00 | 0.00 |
June | 1212.58 | 348.64 | 1159.03 | 189.36 | 969.66 | 0.00 | 0.00 |
July | 1297.53 | 234.00 | 1063.88 | 88.31 | 975.57 | 0.00 | 0.00 |
August | 1137.92 | 278.39 | 987.02 | 21.95 | 965.07 | 0.00 | 0.00 |
September | 775.58 | 512.67 | 789.42 | 0.19 | 789.23 | 0.00 | 0.00 |
October | 330.06 | 947.57 | 589.07 | 0.00 | 589.07 | 0.00 | 0.00 |
November | 91.39 | 1372.22 | 500.26 | 0.00 | 500.26 | 0.00 | 0.00 |
December | 14.08 | 1766.94 | 399.46 | 0.00 | 399.46 | 0.00 | 0.00 |
Annual Sum or Average | 580.59 | 910.23 | 770.88 | 31.16 | 739.72 | 0.00 | 0.00 |
Minimum of Months | 14.08 | 234.00 | 399.46 | 0.00 | 399.46 | 0.00 | 0.00 |
Maximum of Months | 1297.53 | 1766.94 | 1159.03 | 189.36 | 975.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 575.11 | 1004.61 | 866.55 | 484.51 | 382.04 | 0.00 | 0.00 |
February | 803.28 | 906.68 | 1052.73 | 567.52 | 485.21 | 0.00 | 0.00 |
March | 1273.69 | 706.73 | 1388.82 | 789.56 | 599.27 | 0.00 | 0.00 |
April | 1937.62 | 492.94 | 1897.49 | 1081.07 | 816.42 | 0.00 | 0.00 |
May | 1946.30 | 374.81 | 1810.16 | 1031.48 | 778.69 | 0.00 | 0.00 |
June | 2338.89 | 242.45 | 1951.34 | 1201.94 | 749.40 | 0.00 | 0.00 |
July | 2242.45 | 167.88 | 1805.75 | 1032.48 | 773.27 | 0.00 | 0.00 |
August | 2143.86 | 193.33 | 1787.11 | 985.23 | 801.88 | 0.00 | 0.00 |
September | 1667.27 | 334.36 | 1487.68 | 832.44 | 655.24 | 0.00 | 0.00 |
October | 1249.29 | 591.86 | 1293.67 | 820.78 | 472.90 | 0.00 | 0.00 |
November | 773.10 | 853.65 | 1011.12 | 594.45 | 416.68 | 0.00 | 0.00 |
December | 527.26 | 1084.60 | 819.44 | 498.77 | 320.67 | 0.00 | 0.00 |
Annual Sum or Average | 1459.44 | 577.88 | 1432.39 | 827.71 | 604.68 | 0.00 | 0.00 |
Minimum of Months | 527.26 | 167.88 | 819.44 | 484.51 | 320.67 | 0.00 | 0.00 |
Maximum of Months | 2338.89 | 1084.60 | 1951.34 | 1201.94 | 816.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3622.67 | 1548.46 | 3470.97 | 2701.18 | 769.79 | 0.00 | 0.00 |
February | 3437.66 | 1424.17 | 3397.72 | 2482.51 | 915.21 | 0.00 | 0.00 |
March | 2229.62 | 1122.35 | 2502.37 | 1512.92 | 989.45 | 0.00 | 0.00 |
April | 1457.68 | 771.59 | 1950.91 | 800.54 | 1150.37 | 0.00 | 0.00 |
May | 1018.21 | 555.63 | 1300.80 | 285.68 | 1015.12 | 0.00 | 0.00 |
June | 1206.64 | 370.16 | 1099.98 | 134.78 | 965.21 | 0.00 | 0.00 |
July | 1397.12 | 247.54 | 1217.39 | 193.74 | 1023.65 | 0.00 | 0.00 |
August | 1635.92 | 299.24 | 1674.70 | 544.10 | 1130.60 | 0.00 | 0.00 |
September | 2263.37 | 541.76 | 2316.04 | 1291.39 | 1024.65 | 0.00 | 0.00 |
October | 3267.64 | 949.17 | 3170.43 | 2335.39 | 835.03 | 0.00 | 0.00 |
November | 3693.22 | 1307.18 | 3531.46 | 2710.81 | 820.64 | 0.00 | 0.00 |
December | 4019.09 | 1607.21 | 3765.45 | 3106.27 | 659.18 | 0.00 | 0.00 |
Annual Sum or Average | 2432.27 | 892.64 | 2444.53 | 1503.27 | 941.26 | 0.00 | 0.00 |
Minimum of Months | 1018.21 | 247.54 | 1099.98 | 134.78 | 659.18 | 0.00 | 0.00 |
Maximum of Months | 4019.09 | 1607.21 | 3765.45 | 3106.27 | 1150.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 675.29 | 1072.43 | 893.81 | 509.74 | 384.07 | 0.00 | 0.00 |
February | 980.74 | 969.19 | 1150.49 | 664.58 | 485.91 | 0.00 | 0.00 |
March | 1200.13 | 754.06 | 1285.14 | 684.16 | 600.98 | 0.00 | 0.00 |
April | 1662.28 | 527.74 | 1640.18 | 872.95 | 767.23 | 0.00 | 0.00 |
May | 1662.74 | 391.10 | 1554.81 | 801.03 | 753.78 | 0.00 | 0.00 |
June | 2014.50 | 271.56 | 1666.66 | 929.83 | 736.83 | 0.00 | 0.00 |
July | 1874.48 | 177.42 | 1503.41 | 735.66 | 767.75 | 0.00 | 0.00 |
August | 1846.59 | 209.91 | 1536.36 | 710.61 | 825.75 | 0.00 | 0.00 |
September | 1565.59 | 360.89 | 1387.84 | 730.97 | 656.87 | 0.00 | 0.00 |
October | 1278.49 | 640.59 | 1269.56 | 789.07 | 480.49 | 0.00 | 0.00 |
November | 810.69 | 891.59 | 996.63 | 586.34 | 410.28 | 0.00 | 0.00 |
December | 628.81 | 1127.46 | 861.97 | 540.59 | 321.39 | 0.00 | 0.00 |
Annual Sum or Average | 1351.27 | 614.39 | 1312.35 | 712.62 | 599.73 | 0.00 | 0.00 |
Minimum of Months | 628.81 | 177.42 | 861.97 | 509.74 | 321.39 | 0.00 | 0.00 |
Maximum of Months | 2014.50 | 1127.46 | 1666.66 | 929.83 | 825.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 57.12 | 1679.37 | 469.32 | 0.00 | 469.32 | 0.00 | 0.00 |
February | 144.03 | 1516.64 | 586.57 | 0.00 | 586.57 | 0.00 | 0.00 |
March | 351.42 | 1182.63 | 739.88 | 0.00 | 739.88 | 0.00 | 0.00 |
April | 596.49 | 792.06 | 938.56 | 7.92 | 930.65 | 0.00 | 0.00 |
May | 792.26 | 570.27 | 1020.10 | 65.53 | 954.57 | 0.00 | 0.00 |
June | 1194.46 | 364.64 | 1159.03 | 189.37 | 969.67 | 0.00 | 0.00 |
July | 1286.64 | 244.45 | 1063.88 | 88.31 | 975.58 | 0.00 | 0.00 |
August | 1132.24 | 283.27 | 987.02 | 21.95 | 965.07 | 0.00 | 0.00 |
September | 774.81 | 508.15 | 789.42 | 0.19 | 789.23 | 0.00 | 0.00 |
October | 329.79 | 936.18 | 589.08 | 0.00 | 589.08 | 0.00 | 0.00 |
November | 88.78 | 1364.77 | 500.26 | 0.00 | 500.26 | 0.00 | 0.00 |
December | 13.01 | 1780.86 | 399.46 | 0.00 | 399.46 | 0.00 | 0.00 |
Annual Sum or Average | 565.77 | 932.45 | 770.89 | 31.16 | 739.73 | 0.00 | 0.00 |
Minimum of Months | 13.01 | 244.45 | 399.46 | 0.00 | 399.46 | 0.00 | 0.00 |
Maximum of Months | 1286.64 | 1780.86 | 1159.03 | 189.37 | 975.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 566.11 | 1008.03 | 866.56 | 484.52 | 382.04 | 0.00 | 0.00 |
February | 786.89 | 919.59 | 1052.74 | 567.53 | 485.21 | 0.00 | 0.00 |
March | 1254.64 | 717.67 | 1388.84 | 789.56 | 599.27 | 0.00 | 0.00 |
April | 1922.57 | 492.61 | 1897.50 | 1081.08 | 816.43 | 0.00 | 0.00 |
May | 1935.98 | 371.60 | 1810.18 | 1031.49 | 778.69 | 0.00 | 0.00 |
June | 2334.60 | 236.63 | 1951.35 | 1201.96 | 749.40 | 0.00 | 0.00 |
July | 2242.05 | 159.76 | 1805.76 | 1032.49 | 773.27 | 0.00 | 0.00 |
August | 2144.89 | 181.22 | 1787.12 | 985.24 | 801.88 | 0.00 | 0.00 |
September | 1671.01 | 314.74 | 1487.69 | 832.44 | 655.25 | 0.00 | 0.00 |
October | 1252.97 | 563.62 | 1293.68 | 820.79 | 472.90 | 0.00 | 0.00 |
November | 773.76 | 825.31 | 1011.13 | 594.45 | 416.68 | 0.00 | 0.00 |
December | 523.30 | 1073.20 | 819.44 | 498.77 | 320.67 | 0.00 | 0.00 |
Annual Sum or Average | 1453.72 | 570.29 | 1432.40 | 827.72 | 604.68 | 0.00 | 0.00 |
Minimum of Months | 523.30 | 159.76 | 819.44 | 484.52 | 320.67 | 0.00 | 0.00 |
Maximum of Months | 2334.60 | 1073.20 | 1951.35 | 1201.96 | 816.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3573.17 | 1531.23 | 3470.94 | 2701.15 | 769.78 | 0.00 | 0.00 |
February | 3383.65 | 1430.20 | 3397.69 | 2482.48 | 915.21 | 0.00 | 0.00 |
March | 2177.78 | 1161.77 | 2502.35 | 1512.90 | 989.45 | 0.00 | 0.00 |
April | 1408.57 | 815.87 | 1950.90 | 800.53 | 1150.36 | 0.00 | 0.00 |
May | 975.68 | 597.97 | 1300.80 | 285.68 | 1015.11 | 0.00 | 0.00 |
June | 1189.74 | 392.42 | 1099.98 | 134.77 | 965.20 | 0.00 | 0.00 |
July | 1391.23 | 256.78 | 1217.38 | 193.74 | 1023.64 | 0.00 | 0.00 |
August | 1633.55 | 298.31 | 1674.68 | 544.09 | 1130.59 | 0.00 | 0.00 |
September | 2262.37 | 519.89 | 2316.02 | 1291.37 | 1024.65 | 0.00 | 0.00 |
October | 3252.34 | 910.26 | 3170.40 | 2335.37 | 835.03 | 0.00 | 0.00 |
November | 3658.80 | 1259.07 | 3531.42 | 2710.78 | 820.64 | 0.00 | 0.00 |
December | 3972.36 | 1571.21 | 3765.41 | 3106.24 | 659.17 | 0.00 | 0.00 |
Annual Sum or Average | 2401.61 | 892.65 | 2444.51 | 1503.25 | 941.25 | 0.00 | 0.00 |
Minimum of Months | 975.68 | 256.78 | 1099.98 | 134.77 | 659.17 | 0.00 | 0.00 |
Maximum of Months | 3972.36 | 1571.21 | 3765.41 | 3106.24 | 1150.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 665.37 | 1077.04 | 893.82 | 509.74 | 384.07 | 0.00 | 0.00 |
February | 964.84 | 982.12 | 1150.50 | 664.59 | 485.91 | 0.00 | 0.00 |
March | 1179.40 | 773.19 | 1285.15 | 684.16 | 600.99 | 0.00 | 0.00 |
April | 1644.00 | 535.94 | 1640.19 | 872.96 | 767.23 | 0.00 | 0.00 |
May | 1648.80 | 397.57 | 1554.82 | 801.04 | 753.78 | 0.00 | 0.00 |
June | 2010.32 | 270.66 | 1666.67 | 929.84 | 736.84 | 0.00 | 0.00 |
July | 1873.79 | 174.60 | 1503.42 | 735.67 | 767.75 | 0.00 | 0.00 |
August | 1849.27 | 200.98 | 1536.37 | 710.61 | 825.75 | 0.00 | 0.00 |
September | 1572.05 | 342.88 | 1387.85 | 730.98 | 656.87 | 0.00 | 0.00 |
October | 1282.18 | 614.83 | 1269.57 | 789.08 | 480.49 | 0.00 | 0.00 |
November | 809.63 | 867.58 | 996.63 | 586.35 | 410.29 | 0.00 | 0.00 |
December | 623.43 | 1117.66 | 861.98 | 540.59 | 321.39 | 0.00 | 0.00 |
Annual Sum or Average | 1344.89 | 611.08 | 1312.36 | 712.63 | 599.73 | 0.00 | 0.00 |
Minimum of Months | 623.43 | 174.60 | 861.98 | 509.74 | 321.39 | 0.00 | 0.00 |
Maximum of Months | 2010.32 | 1117.66 | 1666.67 | 929.84 | 825.75 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.185566E+09 | 0.424763E+10 | 0.125702E+10 | 0.00 | 0.125702E+10 | 0.00 | 0.00 |
February | 0.384318E+09 | 0.347172E+10 | 0.141903E+10 | 0.00 | 0.141903E+10 | 0.00 | 0.00 |
March | 0.979979E+09 | 0.300499E+10 | 0.198171E+10 | 0.00 | 0.198171E+10 | 0.00 | 0.00 |
April | 0.156506E+10 | 0.195767E+10 | 0.243275E+10 | 20518880.08 | 0.241223E+10 | 0.00 | 0.00 |
May | 0.213128E+10 | 0.146974E+10 | 0.273224E+10 | 0.175524E+09 | 0.255672E+10 | 0.00 | 0.00 |
June | 0.309372E+10 | 0.921709E+09 | 0.300421E+10 | 0.490836E+09 | 0.251337E+10 | 0.00 | 0.00 |
July | 0.343180E+10 | 0.643547E+09 | 0.284951E+10 | 0.236519E+09 | 0.261299E+10 | 0.00 | 0.00 |
August | 0.302255E+10 | 0.739126E+09 | 0.264364E+10 | 58788316.90 | 0.258485E+10 | 0.00 | 0.00 |
September | 0.201620E+10 | 0.125802E+10 | 0.204619E+10 | 502581.14 | 0.204569E+10 | 0.00 | 0.00 |
October | 0.910206E+09 | 0.235787E+10 | 0.157778E+10 | 0.00 | 0.157778E+10 | 0.00 | 0.00 |
November | 0.266625E+09 | 0.329445E+10 | 0.129669E+10 | 0.00 | 0.129669E+10 | 0.00 | 0.00 |
December | 49752491.24 | 0.447975E+10 | 0.106992E+10 | 0.00 | 0.106992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.180371E+11 | 0.278462E+11 | 0.243107E+11 | 0.982688E+09 | 0.233280E+11 | 0.00 | 0.00 |
Minimum of Months | 49752491.24 | 0.643547E+09 | 0.106992E+10 | 0.00 | 0.106992E+10 | 0.00 | 0.00 |
Maximum of Months | 0.343180E+10 | 0.447975E+10 | 0.300421E+10 | 0.490836E+09 | 0.261299E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155810E+10 | 0.257308E+10 | 0.232098E+10 | 0.129773E+10 | 0.102325E+10 | 0.00 | 0.00 |
February | 0.193758E+10 | 0.212510E+10 | 0.254678E+10 | 0.137296E+10 | 0.117382E+10 | 0.00 | 0.00 |
March | 0.338324E+10 | 0.184642E+10 | 0.371986E+10 | 0.211477E+10 | 0.160509E+10 | 0.00 | 0.00 |
April | 0.499028E+10 | 0.123534E+10 | 0.491833E+10 | 0.280215E+10 | 0.211618E+10 | 0.00 | 0.00 |
May | 0.518264E+10 | 0.968172E+09 | 0.484838E+10 | 0.276274E+10 | 0.208564E+10 | 0.00 | 0.00 |
June | 0.604034E+10 | 0.603174E+09 | 0.505791E+10 | 0.311547E+10 | 0.194244E+10 | 0.00 | 0.00 |
July | 0.598876E+10 | 0.424175E+09 | 0.483655E+10 | 0.276541E+10 | 0.207113E+10 | 0.00 | 0.00 |
August | 0.573212E+10 | 0.478605E+09 | 0.478662E+10 | 0.263887E+10 | 0.214776E+10 | 0.00 | 0.00 |
September | 0.433189E+10 | 0.789321E+09 | 0.385610E+10 | 0.215770E+10 | 0.169840E+10 | 0.00 | 0.00 |
October | 0.337400E+10 | 0.144292E+10 | 0.346501E+10 | 0.219839E+10 | 0.126661E+10 | 0.00 | 0.00 |
November | 0.204376E+10 | 0.202517E+10 | 0.262086E+10 | 0.154083E+10 | 0.108003E+10 | 0.00 | 0.00 |
December | 0.143593E+10 | 0.272192E+10 | 0.219479E+10 | 0.133591E+10 | 0.858883E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.459986E+11 | 0.172334E+11 | 0.451722E+11 | 0.261029E+11 | 0.190692E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143593E+10 | 0.424175E+09 | 0.219479E+10 | 0.129773E+10 | 0.858883E+09 | 0.00 | 0.00 |
Maximum of Months | 0.604034E+10 | 0.272192E+10 | 0.505791E+10 | 0.311547E+10 | 0.214776E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.963999E+10 | 0.389389E+10 | 0.929655E+10 | 0.723477E+10 | 0.206179E+10 | 0.00 | 0.00 |
February | 0.823425E+10 | 0.328949E+10 | 0.821968E+10 | 0.600561E+10 | 0.221407E+10 | 0.00 | 0.00 |
March | 0.587018E+10 | 0.296912E+10 | 0.670229E+10 | 0.405215E+10 | 0.265014E+10 | 0.00 | 0.00 |
April | 0.367488E+10 | 0.202570E+10 | 0.505672E+10 | 0.207498E+10 | 0.298174E+10 | 0.00 | 0.00 |
May | 0.262437E+10 | 0.154333E+10 | 0.348405E+10 | 0.765167E+09 | 0.271888E+10 | 0.00 | 0.00 |
June | 0.308076E+10 | 0.989518E+09 | 0.285114E+10 | 0.349336E+09 | 0.250181E+10 | 0.00 | 0.00 |
July | 0.371463E+10 | 0.676060E+09 | 0.326064E+10 | 0.518920E+09 | 0.274172E+10 | 0.00 | 0.00 |
August | 0.436901E+10 | 0.779530E+09 | 0.448547E+10 | 0.145730E+10 | 0.302817E+10 | 0.00 | 0.00 |
September | 0.587636E+10 | 0.129362E+10 | 0.600313E+10 | 0.334724E+10 | 0.265589E+10 | 0.00 | 0.00 |
October | 0.875119E+10 | 0.231570E+10 | 0.849159E+10 | 0.625505E+10 | 0.223654E+10 | 0.00 | 0.00 |
November | 0.955243E+10 | 0.307834E+10 | 0.915344E+10 | 0.702635E+10 | 0.212710E+10 | 0.00 | 0.00 |
December | 0.107081E+11 | 0.397346E+10 | 0.100853E+11 | 0.831974E+10 | 0.176553E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.760961E+11 | 0.268278E+11 | 0.770900E+11 | 0.474066E+11 | 0.296834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.262437E+10 | 0.676060E+09 | 0.285114E+10 | 0.349336E+09 | 0.176553E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107081E+11 | 0.397346E+10 | 0.100853E+11 | 0.831974E+10 | 0.302817E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180436E+10 | 0.274097E+10 | 0.239400E+10 | 0.136530E+10 | 0.102870E+10 | 0.00 | 0.00 |
February | 0.235370E+10 | 0.226274E+10 | 0.278330E+10 | 0.160777E+10 | 0.117552E+10 | 0.00 | 0.00 |
March | 0.317794E+10 | 0.197871E+10 | 0.344215E+10 | 0.183246E+10 | 0.160968E+10 | 0.00 | 0.00 |
April | 0.427099E+10 | 0.133092E+10 | 0.425137E+10 | 0.226271E+10 | 0.198866E+10 | 0.00 | 0.00 |
May | 0.442216E+10 | 0.102541E+10 | 0.416443E+10 | 0.214551E+10 | 0.201892E+10 | 0.00 | 0.00 |
June | 0.520825E+10 | 0.683107E+09 | 0.432001E+10 | 0.241013E+10 | 0.190988E+10 | 0.00 | 0.00 |
July | 0.501178E+10 | 0.458624E+09 | 0.402676E+10 | 0.197041E+10 | 0.205635E+10 | 0.00 | 0.00 |
August | 0.494913E+10 | 0.525151E+09 | 0.411501E+10 | 0.190331E+10 | 0.221170E+10 | 0.00 | 0.00 |
September | 0.408314E+10 | 0.851746E+09 | 0.359730E+10 | 0.189469E+10 | 0.170261E+10 | 0.00 | 0.00 |
October | 0.345037E+10 | 0.156145E+10 | 0.340042E+10 | 0.211347E+10 | 0.128695E+10 | 0.00 | 0.00 |
November | 0.212295E+10 | 0.211662E+10 | 0.258327E+10 | 0.151981E+10 | 0.106346E+10 | 0.00 | 0.00 |
December | 0.168766E+10 | 0.283150E+10 | 0.230872E+10 | 0.144792E+10 | 0.860803E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.425424E+11 | 0.183669E+11 | 0.413867E+11 | 0.224735E+11 | 0.189132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168766E+10 | 0.458624E+09 | 0.230872E+10 | 0.136530E+10 | 0.860803E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520825E+10 | 0.283150E+10 | 0.432001E+10 | 0.241013E+10 | 0.221170E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179075E+09 | 0.439087E+10 | 0.125702E+10 | 0.00 | 0.125702E+10 | 0.00 | 0.00 |
February | 0.400923E+09 | 0.352402E+10 | 0.141902E+10 | 0.00 | 0.141902E+10 | 0.00 | 0.00 |
March | 0.104118E+10 | 0.298806E+10 | 0.198170E+10 | 0.00 | 0.198170E+10 | 0.00 | 0.00 |
April | 0.164609E+10 | 0.192869E+10 | 0.243274E+10 | 20518773.75 | 0.241222E+10 | 0.00 | 0.00 |
May | 0.220716E+10 | 0.144105E+10 | 0.273223E+10 | 0.175523E+09 | 0.255671E+10 | 0.00 | 0.00 |
June | 0.314301E+10 | 0.903671E+09 | 0.300419E+10 | 0.490833E+09 | 0.251336E+10 | 0.00 | 0.00 |
July | 0.347530E+10 | 0.626750E+09 | 0.284949E+10 | 0.236517E+09 | 0.261297E+10 | 0.00 | 0.00 |
August | 0.304780E+10 | 0.745648E+09 | 0.264363E+10 | 58788012.27 | 0.258484E+10 | 0.00 | 0.00 |
September | 0.201030E+10 | 0.132884E+10 | 0.204618E+10 | 502578.54 | 0.204567E+10 | 0.00 | 0.00 |
October | 0.884031E+09 | 0.253798E+10 | 0.157777E+10 | 0.00 | 0.157777E+10 | 0.00 | 0.00 |
November | 0.236890E+09 | 0.355678E+10 | 0.129668E+10 | 0.00 | 0.129668E+10 | 0.00 | 0.00 |
December | 37720532.67 | 0.473256E+10 | 0.106991E+10 | 0.00 | 0.106991E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.183095E+11 | 0.287049E+11 | 0.243106E+11 | 0.982683E+09 | 0.233279E+11 | 0.00 | 0.00 |
Minimum of Months | 37720532.67 | 0.626750E+09 | 0.106991E+10 | 0.00 | 0.106991E+10 | 0.00 | 0.00 |
Maximum of Months | 0.347530E+10 | 0.473256E+10 | 0.300419E+10 | 0.490833E+09 | 0.261297E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154038E+10 | 0.269075E+10 | 0.232096E+10 | 0.129772E+10 | 0.102325E+10 | 0.00 | 0.00 |
February | 0.194330E+10 | 0.219344E+10 | 0.254677E+10 | 0.137295E+10 | 0.117382E+10 | 0.00 | 0.00 |
March | 0.341144E+10 | 0.189291E+10 | 0.371983E+10 | 0.211474E+10 | 0.160508E+10 | 0.00 | 0.00 |
April | 0.502231E+10 | 0.127771E+10 | 0.491829E+10 | 0.280212E+10 | 0.211617E+10 | 0.00 | 0.00 |
May | 0.521298E+10 | 0.100390E+10 | 0.484834E+10 | 0.276271E+10 | 0.208563E+10 | 0.00 | 0.00 |
June | 0.606241E+10 | 0.628419E+09 | 0.505787E+10 | 0.311544E+10 | 0.194243E+10 | 0.00 | 0.00 |
July | 0.600618E+10 | 0.449657E+09 | 0.483651E+10 | 0.276539E+10 | 0.207112E+10 | 0.00 | 0.00 |
August | 0.574212E+10 | 0.517802E+09 | 0.478659E+10 | 0.263884E+10 | 0.214775E+10 | 0.00 | 0.00 |
September | 0.432156E+10 | 0.866650E+09 | 0.385607E+10 | 0.215767E+10 | 0.169839E+10 | 0.00 | 0.00 |
October | 0.334611E+10 | 0.158524E+10 | 0.346498E+10 | 0.219837E+10 | 0.126661E+10 | 0.00 | 0.00 |
November | 0.200387E+10 | 0.221266E+10 | 0.262084E+10 | 0.154081E+10 | 0.108003E+10 | 0.00 | 0.00 |
December | 0.141220E+10 | 0.290500E+10 | 0.219478E+10 | 0.133590E+10 | 0.858879E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.460249E+11 | 0.182241E+11 | 0.451718E+11 | 0.261027E+11 | 0.190692E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141220E+10 | 0.449657E+09 | 0.219478E+10 | 0.129772E+10 | 0.858879E+09 | 0.00 | 0.00 |
Maximum of Months | 0.606241E+10 | 0.290500E+10 | 0.505787E+10 | 0.311544E+10 | 0.214775E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.970295E+10 | 0.414740E+10 | 0.929665E+10 | 0.723485E+10 | 0.206180E+10 | 0.00 | 0.00 |
February | 0.831639E+10 | 0.344535E+10 | 0.821977E+10 | 0.600568E+10 | 0.221409E+10 | 0.00 | 0.00 |
March | 0.597183E+10 | 0.300609E+10 | 0.670235E+10 | 0.405220E+10 | 0.265015E+10 | 0.00 | 0.00 |
April | 0.377829E+10 | 0.199995E+10 | 0.505676E+10 | 0.207500E+10 | 0.298176E+10 | 0.00 | 0.00 |
May | 0.272717E+10 | 0.148820E+10 | 0.348407E+10 | 0.765176E+09 | 0.271889E+10 | 0.00 | 0.00 |
June | 0.312761E+10 | 0.959465E+09 | 0.285116E+10 | 0.349340E+09 | 0.250182E+10 | 0.00 | 0.00 |
July | 0.374204E+10 | 0.663014E+09 | 0.326066E+10 | 0.518926E+09 | 0.274173E+10 | 0.00 | 0.00 |
August | 0.438165E+10 | 0.801487E+09 | 0.448551E+10 | 0.145732E+10 | 0.302819E+10 | 0.00 | 0.00 |
September | 0.586666E+10 | 0.140424E+10 | 0.600318E+10 | 0.334728E+10 | 0.265590E+10 | 0.00 | 0.00 |
October | 0.875205E+10 | 0.254226E+10 | 0.849168E+10 | 0.625512E+10 | 0.223656E+10 | 0.00 | 0.00 |
November | 0.957282E+10 | 0.338820E+10 | 0.915354E+10 | 0.702643E+10 | 0.212711E+10 | 0.00 | 0.00 |
December | 0.107647E+11 | 0.430474E+10 | 0.100854E+11 | 0.831984E+10 | 0.176555E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.767042E+11 | 0.281504E+11 | 0.770907E+11 | 0.474072E+11 | 0.296835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.272717E+10 | 0.663014E+09 | 0.285116E+10 | 0.349340E+09 | 0.176555E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107647E+11 | 0.430474E+10 | 0.100854E+11 | 0.831984E+10 | 0.302819E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180870E+10 | 0.287239E+10 | 0.239398E+10 | 0.136529E+10 | 0.102869E+10 | 0.00 | 0.00 |
February | 0.237261E+10 | 0.234467E+10 | 0.278328E+10 | 0.160776E+10 | 0.117552E+10 | 0.00 | 0.00 |
March | 0.321444E+10 | 0.201968E+10 | 0.344212E+10 | 0.183245E+10 | 0.160968E+10 | 0.00 | 0.00 |
April | 0.430863E+10 | 0.136790E+10 | 0.425134E+10 | 0.226269E+10 | 0.198865E+10 | 0.00 | 0.00 |
May | 0.445349E+10 | 0.104751E+10 | 0.416440E+10 | 0.214548E+10 | 0.201891E+10 | 0.00 | 0.00 |
June | 0.522158E+10 | 0.703879E+09 | 0.431998E+10 | 0.241011E+10 | 0.190987E+10 | 0.00 | 0.00 |
July | 0.502060E+10 | 0.475190E+09 | 0.402673E+10 | 0.197039E+10 | 0.205634E+10 | 0.00 | 0.00 |
August | 0.494591E+10 | 0.562214E+09 | 0.411498E+10 | 0.190329E+10 | 0.221169E+10 | 0.00 | 0.00 |
September | 0.405800E+10 | 0.935435E+09 | 0.359727E+10 | 0.189467E+10 | 0.170260E+10 | 0.00 | 0.00 |
October | 0.342431E+10 | 0.171576E+10 | 0.340039E+10 | 0.211345E+10 | 0.128695E+10 | 0.00 | 0.00 |
November | 0.210132E+10 | 0.231101E+10 | 0.258325E+10 | 0.151980E+10 | 0.106346E+10 | 0.00 | 0.00 |
December | 0.168420E+10 | 0.301980E+10 | 0.230870E+10 | 0.144790E+10 | 0.860799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.426138E+11 | 0.193754E+11 | 0.413864E+11 | 0.224733E+11 | 0.189131E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168420E+10 | 0.475190E+09 | 0.230870E+10 | 0.136529E+10 | 0.860799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.522158E+10 | 0.301980E+10 | 0.431998E+10 | 0.241011E+10 | 0.221169E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152996E+09 | 0.449804E+10 | 0.125702E+10 | 0.00 | 0.125702E+10 | 0.00 | 0.00 |
February | 0.348448E+09 | 0.366906E+10 | 0.141903E+10 | 0.00 | 0.141903E+10 | 0.00 | 0.00 |
March | 0.941242E+09 | 0.316755E+10 | 0.198171E+10 | 0.00 | 0.198171E+10 | 0.00 | 0.00 |
April | 0.154611E+10 | 0.205301E+10 | 0.243275E+10 | 20518880.08 | 0.241223E+10 | 0.00 | 0.00 |
May | 0.212199E+10 | 0.152741E+10 | 0.273224E+10 | 0.175524E+09 | 0.255672E+10 | 0.00 | 0.00 |
June | 0.309604E+10 | 0.945157E+09 | 0.300421E+10 | 0.490836E+09 | 0.251337E+10 | 0.00 | 0.00 |
July | 0.344613E+10 | 0.654729E+09 | 0.284951E+10 | 0.236519E+09 | 0.261299E+10 | 0.00 | 0.00 |
August | 0.303258E+10 | 0.758721E+09 | 0.264364E+10 | 58788316.90 | 0.258485E+10 | 0.00 | 0.00 |
September | 0.200830E+10 | 0.131712E+10 | 0.204619E+10 | 502581.14 | 0.204569E+10 | 0.00 | 0.00 |
October | 0.883309E+09 | 0.250747E+10 | 0.157778E+10 | 0.00 | 0.157778E+10 | 0.00 | 0.00 |
November | 0.230106E+09 | 0.353748E+10 | 0.129669E+10 | 0.00 | 0.129669E+10 | 0.00 | 0.00 |
December | 34858003.10 | 0.476985E+10 | 0.106992E+10 | 0.00 | 0.106992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.178421E+11 | 0.294056E+11 | 0.243107E+11 | 0.982688E+09 | 0.233280E+11 | 0.00 | 0.00 |
Minimum of Months | 34858003.10 | 0.654729E+09 | 0.106992E+10 | 0.00 | 0.106992E+10 | 0.00 | 0.00 |
Maximum of Months | 0.344613E+10 | 0.476985E+10 | 0.300421E+10 | 0.490836E+09 | 0.261299E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151626E+10 | 0.269990E+10 | 0.232098E+10 | 0.129773E+10 | 0.102325E+10 | 0.00 | 0.00 |
February | 0.190364E+10 | 0.222468E+10 | 0.254678E+10 | 0.137296E+10 | 0.117382E+10 | 0.00 | 0.00 |
March | 0.336044E+10 | 0.192220E+10 | 0.371986E+10 | 0.211477E+10 | 0.160509E+10 | 0.00 | 0.00 |
April | 0.498331E+10 | 0.127684E+10 | 0.491833E+10 | 0.280215E+10 | 0.211618E+10 | 0.00 | 0.00 |
May | 0.518533E+10 | 0.995305E+09 | 0.484838E+10 | 0.276274E+10 | 0.208564E+10 | 0.00 | 0.00 |
June | 0.605127E+10 | 0.613355E+09 | 0.505791E+10 | 0.311547E+10 | 0.194244E+10 | 0.00 | 0.00 |
July | 0.600510E+10 | 0.427901E+09 | 0.483655E+10 | 0.276541E+10 | 0.207113E+10 | 0.00 | 0.00 |
August | 0.574487E+10 | 0.485380E+09 | 0.478662E+10 | 0.263887E+10 | 0.214776E+10 | 0.00 | 0.00 |
September | 0.433126E+10 | 0.815815E+09 | 0.385610E+10 | 0.215770E+10 | 0.169840E+10 | 0.00 | 0.00 |
October | 0.335596E+10 | 0.150959E+10 | 0.346501E+10 | 0.219839E+10 | 0.126661E+10 | 0.00 | 0.00 |
November | 0.200558E+10 | 0.213921E+10 | 0.262086E+10 | 0.154083E+10 | 0.108003E+10 | 0.00 | 0.00 |
December | 0.140160E+10 | 0.287446E+10 | 0.219479E+10 | 0.133591E+10 | 0.858883E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.458446E+11 | 0.179846E+11 | 0.451722E+11 | 0.261029E+11 | 0.190692E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140160E+10 | 0.427901E+09 | 0.219479E+10 | 0.129773E+10 | 0.858883E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605127E+10 | 0.287446E+10 | 0.505791E+10 | 0.311547E+10 | 0.214776E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.957037E+10 | 0.410124E+10 | 0.929655E+10 | 0.723477E+10 | 0.206179E+10 | 0.00 | 0.00 |
February | 0.818573E+10 | 0.345994E+10 | 0.821968E+10 | 0.600561E+10 | 0.221407E+10 | 0.00 | 0.00 |
March | 0.583297E+10 | 0.311170E+10 | 0.670229E+10 | 0.405215E+10 | 0.265014E+10 | 0.00 | 0.00 |
April | 0.365102E+10 | 0.211474E+10 | 0.505672E+10 | 0.207498E+10 | 0.298174E+10 | 0.00 | 0.00 |
May | 0.261327E+10 | 0.160160E+10 | 0.348405E+10 | 0.765167E+09 | 0.271888E+10 | 0.00 | 0.00 |
June | 0.308380E+10 | 0.101716E+10 | 0.285114E+10 | 0.349336E+09 | 0.250181E+10 | 0.00 | 0.00 |
July | 0.372628E+10 | 0.687761E+09 | 0.326064E+10 | 0.518920E+09 | 0.274172E+10 | 0.00 | 0.00 |
August | 0.437530E+10 | 0.798988E+09 | 0.448547E+10 | 0.145730E+10 | 0.302817E+10 | 0.00 | 0.00 |
September | 0.586405E+10 | 0.134755E+10 | 0.600313E+10 | 0.334724E+10 | 0.265589E+10 | 0.00 | 0.00 |
October | 0.871107E+10 | 0.243804E+10 | 0.849159E+10 | 0.625505E+10 | 0.223654E+10 | 0.00 | 0.00 |
November | 0.948361E+10 | 0.326352E+10 | 0.915344E+10 | 0.702635E+10 | 0.212710E+10 | 0.00 | 0.00 |
December | 0.106396E+11 | 0.420834E+10 | 0.100853E+11 | 0.831974E+10 | 0.176553E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.757370E+11 | 0.281506E+11 | 0.770900E+11 | 0.474066E+11 | 0.296834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261327E+10 | 0.687761E+09 | 0.285114E+10 | 0.349336E+09 | 0.176553E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106396E+11 | 0.420834E+10 | 0.100853E+11 | 0.831974E+10 | 0.302817E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178213E+10 | 0.288475E+10 | 0.239400E+10 | 0.136530E+10 | 0.102870E+10 | 0.00 | 0.00 |
February | 0.233415E+10 | 0.237594E+10 | 0.278330E+10 | 0.160777E+10 | 0.117552E+10 | 0.00 | 0.00 |
March | 0.315891E+10 | 0.207092E+10 | 0.344215E+10 | 0.183246E+10 | 0.160968E+10 | 0.00 | 0.00 |
April | 0.426124E+10 | 0.138915E+10 | 0.425137E+10 | 0.226271E+10 | 0.198866E+10 | 0.00 | 0.00 |
May | 0.441615E+10 | 0.106486E+10 | 0.416443E+10 | 0.214551E+10 | 0.201892E+10 | 0.00 | 0.00 |
June | 0.521074E+10 | 0.701547E+09 | 0.432001E+10 | 0.241013E+10 | 0.190988E+10 | 0.00 | 0.00 |
July | 0.501877E+10 | 0.467639E+09 | 0.402676E+10 | 0.197041E+10 | 0.205635E+10 | 0.00 | 0.00 |
August | 0.495310E+10 | 0.538307E+09 | 0.411501E+10 | 0.190331E+10 | 0.221170E+10 | 0.00 | 0.00 |
September | 0.407475E+10 | 0.888748E+09 | 0.359730E+10 | 0.189469E+10 | 0.170261E+10 | 0.00 | 0.00 |
October | 0.343419E+10 | 0.164675E+10 | 0.340042E+10 | 0.211347E+10 | 0.128695E+10 | 0.00 | 0.00 |
November | 0.209855E+10 | 0.224878E+10 | 0.258327E+10 | 0.151981E+10 | 0.106346E+10 | 0.00 | 0.00 |
December | 0.166979E+10 | 0.299354E+10 | 0.230872E+10 | 0.144792E+10 | 0.860803E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424125E+11 | 0.192709E+11 | 0.413867E+11 | 0.224735E+11 | 0.189132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.166979E+10 | 0.467639E+09 | 0.230872E+10 | 0.136530E+10 | 0.860803E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521074E+10 | 0.299354E+10 | 0.432001E+10 | 0.241013E+10 | 0.221170E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.2 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.20 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.66 | -5.5 | 4.72 | -6.1 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.69 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.40 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.39 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.11 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.38 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.86 | 7.70 | 3.48 | 8.21 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.78 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.53 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.11 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.80 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.83 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.65 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.28 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.68 | -1.5 | 8.93 | 13.33 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.11 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.67 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.27 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.73 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.23 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.79 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 3.99 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 3.99 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.73 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.1 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.6 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.2 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -0.7 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.53 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.76 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.7 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.82 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.83 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.65 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.92 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.05 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.75 | 167.00 | 0.00 |
June | 18.16 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.19 | 01-JUL-00:00 | 21.20 | 13.50 | 3.60 | 17.57 | 0.00 | 0.00 |
August | 19.17 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.18 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.15 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.79 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.90 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.90 | 12.80 | -10.0 | 2.10 | -0.1 | 0.00 | 0.00 | |
Maximum of Months | 19.19 | 31.70 | 15.60 | 13.40 | 19.17 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.71 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.78 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.70 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.04 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.58 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.03 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.37 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.04 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.297116E+10 | -.452588E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -826712695.5 | 64.71 | 0.00 | 0.00 |
February | 0.273316E+10 | -.414329E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -739054233.7 | 64.51 | 0.00 | 0.00 |
March | 0.320696E+10 | -.478365E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -797833175.8 | 63.71 | 0.00 | 0.00 |
April | 0.254880E+10 | -.408126E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -781614517.0 | 64.44 | 0.00 | 0.00 |
May | 0.249415E+10 | -.407488E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -815918601.8 | 64.90 | 0.00 | 0.00 |
June | 0.221461E+10 | -.376033E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -779579413.5 | 64.38 | 0.00 | 0.00 |
July | 0.178458E+10 | -.337128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -831325808.8 | 65.70 | 0.00 | 0.00 |
August | 0.208069E+10 | -.368455E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -805440878.9 | 64.42 | 0.00 | 0.00 |
September | 0.188903E+10 | -.343138E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -792239046.6 | 65.14 | 0.00 | 0.00 |
October | 0.219942E+10 | -.377903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -825417682.6 | 65.41 | 0.00 | 0.00 |
November | 0.247934E+10 | -.400295E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -793047198.3 | 64.97 | 0.00 | 0.00 |
December | 0.266411E+10 | -.422832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -825844567.8 | 64.85 | 0.00 | 0.00 |
Annual Sum or Average | 0.292660E+11 | -.478668E+11 | 8760.00 | -.961403E+10 | 64.76 | |||||
Minimum of Months | 0.178458E+10 | -.478365E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -831325808.8 | 63.71 | 0.00 | 0.00 |
Maximum of Months | 0.320696E+10 | -.337128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -739054233.7 | 65.70 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-07:40 | 10360.17 | 37.32 | 288.67 | 285.67 | 2650.55 | 27.26 | 196.83 | 276.00 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:30 | 12720.60 | 37.44 | 272.00 | 273.67 | 2016.37 | 24.60 | 166.83 | 262.33 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:00 | 2233.71 | 17.61 | 10.83 | 328.50 | 1327.24 | 20.22 | 128.33 | 297.67 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:19 | 1776.00 | 17.85 | 0.00 | 350.00 | 1091.06 | 20.63 | 144.83 | 323.83 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:00 | 1351.44 | 17.19 | 0.00 | 367.00 | 843.82 | 20.02 | 83.83 | 332.17 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:40 | 1070.80 | 16.24 | 0.00 | 366.33 | 674.04 | 19.16 | 65.00 | 317.00 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:19 | 1303.43 | 17.00 | 0.00 | 371.67 | 803.88 | 19.88 | 97.67 | 330.50 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:00 | 1644.70 | 17.60 | 0.00 | 369.83 | 996.12 | 20.41 | 166.83 | 338.50 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:10 | 2191.73 | 18.12 | 16.50 | 326.17 | 1229.22 | 20.21 | 122.33 | 299.17 |
October | 329.00 | 0.74 | 0.73 | 01-OCT-06:40 | 6151.16 | 27.45 | 181.17 | 317.33 | 1685.90 | 20.49 | 91.00 | 302.67 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-06:49 | 11681.04 | 37.82 | 273.17 | 282.67 | 2642.02 | 27.38 | 168.50 | 273.17 |
December | 265.67 | 0.74 | 0.73 | 01-DEC-07:49 | 11849.70 | 39.77 | 263.50 | 269.17 | 3888.98 | 30.65 | 170.33 | 261.00 |
Annual Sum or Average | 4149.83 | 0.74 | 4721.41 | 23.80 | 1305.83 | 3908.00 | 1530.97 | 22.11 | 1602.33 | 3614.00 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 1070.80 | 16.24 | 0.00 | 269.17 | 674.04 | 19.16 | 65.00 | 261.00 | |
Maximum of Months | 412.83 | 0.74 | 0.73 | 12720.60 | 39.77 | 288.67 | 371.67 | 3888.98 | 30.65 | 196.83 | 338.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-07:40 | 2459.69 | 20.23 | 86.33 | 256.67 | 1455.67 | 23.24 | 94.00 | 227.83 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:19 | 3314.59 | 22.16 | 96.83 | 261.67 | 1844.14 | 23.21 | 92.17 | 232.50 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:49 | 3217.79 | 19.61 | 86.17 | 321.33 | 1806.91 | 22.51 | 84.67 | 290.17 |
April | 381.83 | 0.74 | 0.73 | 01-APR-05:00 | 4724.05 | 21.56 | 114.83 | 354.33 | 1823.77 | 21.22 | 54.83 | 334.00 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:49 | 3653.62 | 18.89 | 81.00 | 371.17 | 2116.33 | 21.71 | 66.33 | 343.17 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:10 | 3644.94 | 19.71 | 111.00 | 384.67 | 2067.61 | 21.35 | 82.67 | 350.17 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:10 | 3510.49 | 18.92 | 84.83 | 379.83 | 1930.06 | 21.72 | 73.67 | 349.00 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:40 | 4358.20 | 21.17 | 118.83 | 377.33 | 1779.52 | 22.12 | 75.50 | 354.33 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-05:00 | 3735.22 | 21.05 | 106.67 | 327.50 | 2091.51 | 22.65 | 87.67 | 302.17 |
October | 329.00 | 0.74 | 0.73 | 01-OCT-06:30 | 3251.21 | 19.49 | 82.67 | 295.50 | 1881.88 | 22.64 | 79.00 | 271.17 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-06:49 | 2688.66 | 20.69 | 77.00 | 259.33 | 1450.18 | 22.18 | 71.67 | 233.33 |
December | 265.67 | 0.75 | 0.73 | 01-DEC-07:49 | 2840.19 | 20.56 | 80.33 | 238.83 | 1771.96 | 23.32 | 81.00 | 200.67 |
Annual Sum or Average | 4149.83 | 0.74 | 3517.36 | 20.29 | 1126.50 | 3828.17 | 1852.55 | 22.24 | 943.17 | 3488.50 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 2459.69 | 18.89 | 77.00 | 238.83 | 1450.18 | 21.22 | 54.83 | 200.67 | |
Maximum of Months | 412.83 | 0.75 | 0.73 | 4724.05 | 22.16 | 118.83 | 384.67 | 2116.33 | 23.32 | 94.00 | 354.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.75 | 0.73 | 01-JAN-08:30 | 597.22 | 14.22 | 0.00 | 233.17 | 386.22 | 17.49 | 0.00 | 172.50 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:40 | 699.98 | 15.16 | 0.00 | 246.83 | 466.06 | 18.34 | 0.00 | 194.00 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:00 | 838.40 | 15.97 | 0.00 | 312.33 | 528.21 | 18.90 | 5.50 | 260.17 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:10 | 1052.54 | 17.59 | 0.00 | 359.50 | 675.22 | 20.35 | 60.17 | 337.00 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:00 | 1234.74 | 17.75 | 0.00 | 387.67 | 718.83 | 20.58 | 100.17 | 353.50 |
June | 412.83 | 0.73 | 0.73 | 01-JUN-05:19 | 1274.89 | 18.99 | 49.83 | 400.67 | 701.51 | 21.28 | 116.67 | 378.33 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:19 | 1256.44 | 19.08 | 35.00 | 392.83 | 738.12 | 21.27 | 118.67 | 370.00 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:49 | 1118.01 | 17.65 | 0.00 | 380.83 | 715.34 | 20.44 | 114.00 | 364.00 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:10 | 883.06 | 16.53 | 0.00 | 321.67 | 570.69 | 19.44 | 17.00 | 282.17 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:00 | 636.28 | 14.68 | 0.00 | 276.50 | 439.14 | 17.84 | 0.00 | 221.83 |
November | 284.17 | 0.75 | 0.73 | 01-NOV-07:10 | 629.14 | 14.92 | 0.00 | 246.00 | 423.49 | 18.20 | 0.00 | 192.00 |
December | 265.67 | 0.76 | 0.73 | 01-DEC-07:00 | 520.01 | 13.35 | 0.00 | 219.50 | 363.83 | 16.82 | 0.00 | 150.33 |
Annual Sum or Average | 4149.83 | 0.74 | 931.20 | 16.57 | 84.83 | 3777.50 | 579.16 | 19.44 | 532.17 | 3275.83 | ||
Minimum of Months | 265.67 | 0.73 | 0.73 | 520.01 | 13.35 | 0.00 | 219.50 | 363.83 | 16.82 | 0.00 | 150.33 | |
Maximum of Months | 412.83 | 0.76 | 0.73 | 1274.89 | 19.08 | 49.83 | 400.67 | 738.12 | 21.28 | 118.67 | 378.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-08:30 | 2231.30 | 20.49 | 84.83 | 262.50 | 1118.15 | 21.42 | 67.00 | 227.67 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:49 | 3122.47 | 20.39 | 75.00 | 259.50 | 1805.78 | 23.37 | 84.00 | 230.00 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-07:10 | 3469.98 | 20.84 | 105.17 | 321.83 | 1305.04 | 20.49 | 50.17 | 290.50 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:30 | 4210.28 | 20.92 | 110.33 | 356.17 | 1739.53 | 21.00 | 51.00 | 336.50 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-06:10 | 3015.15 | 16.33 | 46.67 | 381.17 | 1756.89 | 17.84 | 0.00 | 361.00 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:49 | 3332.83 | 12.51 | 0.00 | 378.83 | 1913.93 | 16.85 | 0.00 | 349.67 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:30 | 3194.76 | 13.66 | 3.67 | 380.33 | 1747.85 | 17.64 | 0.00 | 351.83 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-06:10 | 3084.19 | 17.33 | 62.33 | 370.50 | 1654.64 | 18.42 | 5.17 | 348.50 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:30 | 3582.79 | 20.93 | 107.67 | 328.83 | 1386.11 | 20.87 | 59.67 | 303.67 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:00 | 3164.56 | 19.72 | 86.17 | 297.17 | 1666.25 | 21.97 | 68.67 | 269.33 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-07:10 | 3169.12 | 22.91 | 101.67 | 270.67 | 1258.65 | 22.42 | 63.17 | 241.17 |
December | 265.67 | 0.75 | 0.73 | 01-DEC-08:09 | 2757.13 | 21.10 | 85.17 | 245.33 | 1590.89 | 23.96 | 81.83 | 214.67 |
Annual Sum or Average | 4149.83 | 0.74 | 3224.50 | 18.60 | 868.67 | 3852.83 | 1594.60 | 20.23 | 530.67 | 3524.50 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 2231.30 | 12.51 | 0.00 | 245.33 | 1118.15 | 16.85 | 0.00 | 214.67 | |
Maximum of Months | 412.83 | 0.75 | 0.73 | 4210.28 | 22.91 | 110.33 | 381.17 | 1913.93 | 23.96 | 84.00 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-07:40 | 10153.74 | 37.03 | 288.33 | 284.00 | 2485.49 | 25.01 | 127.17 | 274.67 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:30 | 12517.94 | 37.22 | 271.67 | 272.50 | 1858.19 | 22.08 | 79.67 | 261.50 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:00 | 2097.70 | 13.80 | 10.67 | 326.67 | 1225.47 | 17.62 | 9.33 | 292.83 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:19 | 1679.04 | 14.46 | 0.00 | 347.67 | 1024.84 | 18.50 | 5.67 | 320.67 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:00 | 1288.97 | 13.84 | 0.00 | 365.33 | 805.51 | 17.90 | 0.00 | 328.00 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:40 | 1027.00 | 12.75 | 0.00 | 360.67 | 649.10 | 16.92 | 0.00 | 312.17 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:19 | 1246.16 | 13.56 | 0.00 | 368.33 | 770.06 | 17.67 | 1.17 | 327.50 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:00 | 1561.02 | 14.18 | 0.00 | 368.17 | 941.58 | 18.21 | 1.17 | 335.33 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:10 | 2072.01 | 14.56 | 16.50 | 324.67 | 1141.09 | 17.78 | 8.33 | 296.83 |
October | 329.00 | 0.74 | 0.73 | 01-OCT-06:40 | 5982.69 | 25.39 | 181.17 | 316.50 | 1548.10 | 17.81 | 17.83 | 301.00 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-06:49 | 11465.28 | 37.54 | 273.17 | 280.50 | 2469.26 | 25.07 | 112.83 | 272.33 |
December | 265.67 | 0.74 | 0.73 | 01-DEC-07:49 | 11570.28 | 39.14 | 259.67 | 267.83 | 3689.96 | 28.72 | 146.67 | 259.50 |
Annual Sum or Average | 4149.83 | 0.74 | 4592.07 | 21.28 | 1301.17 | 3882.83 | 1435.82 | 19.81 | 509.83 | 3582.33 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 1027.00 | 12.75 | 0.00 | 267.83 | 649.10 | 16.92 | 0.00 | 259.50 | |
Maximum of Months | 412.83 | 0.74 | 0.73 | 12517.94 | 39.14 | 288.33 | 368.33 | 3689.96 | 28.72 | 146.67 | 335.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-07:40 | 2393.54 | 19.74 | 85.83 | 253.50 | 1403.94 | 23.03 | 88.67 | 224.33 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:19 | 3014.39 | 19.66 | 74.33 | 259.00 | 1784.58 | 23.01 | 84.83 | 229.17 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:49 | 3123.40 | 19.11 | 85.17 | 317.83 | 1732.38 | 22.33 | 78.00 | 287.83 |
April | 381.83 | 0.74 | 0.73 | 01-APR-05:00 | 4599.15 | 21.17 | 114.83 | 351.33 | 1726.70 | 21.05 | 54.83 | 330.33 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:49 | 3531.07 | 18.48 | 81.00 | 369.33 | 2027.72 | 21.56 | 66.33 | 339.83 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:19 | 3339.77 | 17.56 | 83.83 | 379.83 | 1985.77 | 21.19 | 82.83 | 347.00 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:10 | 3402.49 | 18.51 | 84.83 | 378.00 | 1837.95 | 21.46 | 70.33 | 346.67 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:40 | 4244.83 | 20.78 | 118.83 | 376.00 | 1635.88 | 20.92 | 59.83 | 350.83 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-05:00 | 3644.94 | 20.64 | 106.67 | 325.33 | 2017.92 | 22.47 | 84.83 | 299.83 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:30 | 3164.34 | 19.07 | 82.67 | 293.50 | 1809.18 | 22.46 | 76.17 | 268.83 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-06:49 | 2605.69 | 20.25 | 77.00 | 257.33 | 1385.11 | 21.96 | 66.50 | 230.83 |
December | 265.67 | 0.75 | 0.73 | 01-DEC-07:49 | 2770.93 | 20.14 | 80.33 | 236.33 | 1716.73 | 23.11 | 77.33 | 198.17 |
Annual Sum or Average | 4149.83 | 0.74 | 3384.87 | 19.55 | 1075.33 | 3797.33 | 1770.23 | 21.95 | 890.50 | 3453.67 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 2393.54 | 17.56 | 74.33 | 236.33 | 1385.11 | 20.92 | 54.83 | 198.17 | |
Maximum of Months | 412.83 | 0.75 | 0.73 | 4599.15 | 21.17 | 118.83 | 379.83 | 2027.72 | 23.11 | 88.67 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.75 | 0.73 | 01-JAN-08:30 | 572.55 | 10.65 | 0.00 | 227.00 | 373.63 | 15.07 | 0.00 | 164.67 |
February | 282.00 | 0.75 | 0.73 | 01-FEB-07:49 | 671.57 | 11.79 | 0.00 | 243.17 | 451.77 | 16.13 | 0.00 | 188.50 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:00 | 805.99 | 12.66 | 0.00 | 308.67 | 511.72 | 16.80 | 0.00 | 255.50 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:10 | 1010.64 | 14.59 | 0.00 | 358.33 | 653.70 | 18.66 | 2.50 | 335.17 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:00 | 1188.74 | 14.44 | 0.00 | 386.83 | 694.02 | 18.59 | 18.17 | 349.83 |
June | 412.83 | 0.73 | 0.73 | 01-JUN-05:19 | 1230.20 | 15.84 | 49.17 | 396.33 | 657.59 | 17.93 | 7.00 | 370.67 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:19 | 1209.83 | 15.98 | 35.00 | 392.00 | 712.41 | 19.25 | 26.17 | 367.33 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:49 | 1092.16 | 14.47 | 0.00 | 381.00 | 691.62 | 18.56 | 3.33 | 361.50 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:10 | 848.43 | 13.39 | 0.00 | 320.00 | 553.19 | 17.52 | 0.00 | 278.83 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:00 | 611.90 | 11.42 | 0.00 | 272.00 | 427.25 | 15.77 | 0.00 | 216.00 |
November | 284.17 | 0.75 | 0.73 | 01-NOV-07:10 | 602.24 | 11.54 | 0.00 | 241.83 | 409.85 | 15.96 | 0.00 | 185.83 |
December | 265.67 | 0.76 | 0.73 | 01-DEC-07:00 | 497.86 | 9.90 | 0.00 | 213.67 | 352.80 | 14.41 | 0.00 | 142.83 |
Annual Sum or Average | 4149.83 | 0.74 | 897.06 | 13.32 | 84.17 | 3740.83 | 558.38 | 17.25 | 57.17 | 3216.67 | ||
Minimum of Months | 265.67 | 0.73 | 0.73 | 497.86 | 9.90 | 0.00 | 213.67 | 352.80 | 14.41 | 0.00 | 142.83 | |
Maximum of Months | 412.83 | 0.76 | 0.73 | 1230.20 | 15.98 | 49.17 | 396.33 | 712.41 | 19.25 | 26.17 | 370.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-08:30 | 2167.17 | 20.14 | 84.83 | 258.50 | 1067.99 | 21.32 | 66.00 | 225.33 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:00 | 3035.29 | 20.03 | 74.83 | 256.00 | 1738.33 | 23.28 | 82.17 | 227.17 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-07:10 | 3388.01 | 20.48 | 105.17 | 320.17 | 1240.37 | 20.37 | 50.00 | 286.83 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:30 | 4109.20 | 20.54 | 110.33 | 354.17 | 1578.48 | 20.85 | 51.00 | 330.50 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-06:10 | 2915.70 | 15.90 | 46.50 | 379.33 | 1685.64 | 17.66 | 0.00 | 357.83 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:49 | 3241.09 | 12.05 | 0.00 | 375.50 | 1842.52 | 16.68 | 0.00 | 346.33 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:30 | 3097.10 | 13.20 | 3.67 | 378.50 | 1677.62 | 17.47 | 0.00 | 348.83 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-06:10 | 2981.73 | 16.91 | 62.33 | 368.83 | 1580.18 | 18.25 | 5.17 | 346.00 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:30 | 3495.43 | 20.56 | 107.67 | 325.83 | 1304.91 | 20.58 | 57.00 | 300.67 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:00 | 3023.55 | 19.00 | 82.17 | 294.67 | 1488.88 | 20.53 | 54.00 | 265.33 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-07:10 | 2851.19 | 20.25 | 78.67 | 266.50 | 1200.06 | 22.32 | 62.83 | 237.50 |
December | 265.67 | 0.75 | 0.73 | 01-DEC-08:09 | 2626.78 | 20.14 | 80.17 | 242.67 | 1537.30 | 23.88 | 81.67 | 212.33 |
Annual Sum or Average | 4149.83 | 0.74 | 3111.24 | 17.98 | 836.33 | 3820.67 | 1509.93 | 19.97 | 509.83 | 3484.67 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 2167.17 | 12.05 | 0.00 | 242.67 | 1067.99 | 16.68 | 0.00 | 212.33 | |
Maximum of Months | 412.83 | 0.75 | 0.73 | 4109.20 | 20.56 | 110.33 | 379.33 | 1842.52 | 23.88 | 82.17 | 357.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-07:40 | 10153.75 | 37.03 | 288.33 | 284.00 | 2485.42 | 25.01 | 127.17 | 274.67 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:30 | 12517.91 | 37.22 | 271.67 | 272.50 | 1858.11 | 22.08 | 79.67 | 261.50 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:00 | 2097.63 | 13.80 | 10.67 | 326.67 | 1225.40 | 17.62 | 9.33 | 292.83 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:19 | 1678.98 | 14.46 | 0.00 | 347.67 | 1024.79 | 18.50 | 5.67 | 320.67 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:00 | 1288.94 | 13.85 | 0.00 | 365.33 | 805.46 | 17.90 | 0.00 | 328.00 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:40 | 1026.98 | 12.75 | 0.00 | 360.67 | 649.07 | 16.92 | 0.00 | 312.17 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:19 | 1246.13 | 13.56 | 0.00 | 368.33 | 770.02 | 17.67 | 1.17 | 327.50 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:00 | 1560.97 | 14.18 | 0.00 | 368.17 | 941.52 | 18.21 | 1.33 | 335.33 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:10 | 2071.95 | 14.56 | 16.50 | 324.67 | 1141.02 | 17.78 | 8.33 | 296.83 |
October | 329.00 | 0.74 | 0.73 | 01-OCT-06:40 | 5982.65 | 25.39 | 181.17 | 316.50 | 1548.04 | 17.81 | 17.83 | 301.00 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-06:49 | 11465.29 | 37.54 | 273.17 | 280.50 | 2469.18 | 25.07 | 112.83 | 272.33 |
December | 265.67 | 0.74 | 0.73 | 01-DEC-07:49 | 11570.33 | 39.14 | 259.67 | 267.83 | 3689.90 | 28.72 | 146.67 | 259.50 |
Annual Sum or Average | 4149.83 | 0.74 | 4592.04 | 21.29 | 1301.17 | 3882.83 | 1435.76 | 19.81 | 510.00 | 3582.33 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 1026.98 | 12.75 | 0.00 | 267.83 | 649.07 | 16.92 | 0.00 | 259.50 | |
Maximum of Months | 412.83 | 0.74 | 0.73 | 12517.91 | 39.14 | 288.33 | 368.33 | 3689.90 | 28.72 | 146.67 | 335.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-07:40 | 2393.54 | 19.74 | 85.83 | 253.50 | 1403.90 | 23.03 | 88.67 | 224.33 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:19 | 3014.40 | 19.66 | 74.33 | 259.00 | 1784.54 | 23.01 | 85.33 | 229.17 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:49 | 3123.38 | 19.11 | 85.17 | 317.83 | 1732.33 | 22.33 | 78.00 | 287.83 |
April | 381.83 | 0.74 | 0.73 | 01-APR-05:00 | 4599.15 | 21.17 | 114.83 | 351.33 | 1726.64 | 21.05 | 54.83 | 330.33 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:49 | 3531.07 | 18.48 | 81.00 | 369.33 | 2027.67 | 21.56 | 66.33 | 339.83 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:19 | 3339.77 | 17.56 | 83.83 | 379.83 | 1985.73 | 21.19 | 82.83 | 347.00 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:10 | 3402.48 | 18.51 | 84.83 | 378.00 | 1837.90 | 21.46 | 70.33 | 346.67 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:40 | 4244.83 | 20.78 | 118.83 | 376.00 | 1635.82 | 20.92 | 59.83 | 350.83 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-05:00 | 3644.94 | 20.64 | 106.67 | 325.33 | 2017.87 | 22.47 | 84.83 | 299.83 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:30 | 3164.34 | 19.07 | 82.67 | 293.50 | 1809.15 | 22.46 | 76.17 | 268.83 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-06:49 | 2605.71 | 20.25 | 77.00 | 257.33 | 1385.07 | 21.96 | 66.50 | 230.83 |
December | 265.67 | 0.75 | 0.73 | 01-DEC-07:49 | 2770.95 | 20.14 | 80.33 | 236.33 | 1716.70 | 23.12 | 77.33 | 198.17 |
Annual Sum or Average | 4149.83 | 0.74 | 3384.87 | 19.55 | 1075.33 | 3797.33 | 1770.19 | 21.95 | 891.00 | 3453.67 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 2393.54 | 17.56 | 74.33 | 236.33 | 1385.07 | 20.92 | 54.83 | 198.17 | |
Maximum of Months | 412.83 | 0.75 | 0.73 | 4599.15 | 21.17 | 118.83 | 379.83 | 2027.67 | 23.12 | 88.67 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.75 | 0.73 | 01-JAN-08:30 | 572.55 | 10.65 | 0.00 | 227.00 | 373.61 | 15.07 | 0.00 | 164.67 |
February | 282.00 | 0.75 | 0.73 | 01-FEB-07:49 | 671.58 | 11.79 | 0.00 | 243.17 | 451.75 | 16.13 | 0.00 | 188.50 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-06:00 | 805.98 | 12.66 | 0.00 | 308.67 | 511.69 | 16.80 | 0.00 | 255.50 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:10 | 1010.64 | 14.60 | 0.00 | 358.33 | 653.67 | 18.66 | 2.50 | 335.17 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-05:00 | 1188.73 | 14.44 | 0.00 | 386.83 | 693.99 | 18.59 | 18.17 | 349.83 |
June | 412.83 | 0.73 | 0.73 | 01-JUN-05:19 | 1230.19 | 15.84 | 49.17 | 396.33 | 657.56 | 17.94 | 7.00 | 370.67 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:19 | 1209.82 | 15.98 | 35.00 | 392.00 | 712.38 | 19.25 | 26.17 | 367.33 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-05:49 | 1092.16 | 14.48 | 0.00 | 381.00 | 691.59 | 18.56 | 3.33 | 361.50 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:10 | 848.42 | 13.39 | 0.00 | 320.00 | 553.16 | 17.52 | 0.00 | 278.67 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:00 | 611.91 | 11.42 | 0.00 | 272.00 | 427.23 | 15.77 | 0.00 | 216.00 |
November | 284.17 | 0.75 | 0.73 | 01-NOV-07:10 | 602.24 | 11.55 | 0.00 | 241.83 | 409.83 | 15.96 | 0.00 | 185.83 |
December | 265.67 | 0.76 | 0.73 | 01-DEC-07:00 | 497.87 | 9.91 | 0.00 | 213.67 | 352.79 | 14.41 | 0.00 | 142.83 |
Annual Sum or Average | 4149.83 | 0.74 | 897.06 | 13.32 | 84.17 | 3740.83 | 558.36 | 17.25 | 57.17 | 3216.50 | ||
Minimum of Months | 265.67 | 0.73 | 0.73 | 497.87 | 9.91 | 0.00 | 213.67 | 352.79 | 14.41 | 0.00 | 142.83 | |
Maximum of Months | 412.83 | 0.76 | 0.73 | 1230.19 | 15.98 | 49.17 | 396.33 | 712.38 | 19.25 | 26.17 | 370.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.74 | 0.73 | 01-JAN-08:30 | 2167.17 | 20.14 | 84.83 | 258.50 | 1067.96 | 21.32 | 66.00 | 225.33 |
February | 282.00 | 0.74 | 0.73 | 01-FEB-07:00 | 3035.30 | 20.03 | 74.83 | 256.00 | 1738.29 | 23.28 | 82.17 | 227.17 |
March | 351.33 | 0.74 | 0.73 | 01-MAR-07:10 | 3388.00 | 20.48 | 105.17 | 320.17 | 1240.32 | 20.37 | 50.00 | 286.83 |
April | 381.83 | 0.74 | 0.73 | 01-APR-06:30 | 4109.19 | 20.54 | 110.33 | 354.17 | 1578.43 | 20.85 | 51.00 | 330.50 |
May | 378.00 | 0.74 | 0.73 | 01-MAY-06:10 | 2915.69 | 15.90 | 46.50 | 379.33 | 1685.59 | 17.66 | 0.00 | 357.83 |
June | 412.83 | 0.74 | 0.73 | 01-JUN-05:49 | 3241.08 | 12.05 | 0.00 | 375.50 | 1842.48 | 16.68 | 0.00 | 346.33 |
July | 395.33 | 0.74 | 0.73 | 01-JUL-06:30 | 3097.09 | 13.21 | 3.67 | 378.50 | 1677.57 | 17.47 | 0.00 | 348.83 |
August | 408.83 | 0.74 | 0.73 | 01-AUG-06:10 | 2981.71 | 16.92 | 62.33 | 368.83 | 1580.12 | 18.25 | 5.17 | 346.00 |
September | 359.33 | 0.74 | 0.73 | 01-SEP-06:30 | 3495.42 | 20.57 | 107.67 | 325.83 | 1304.86 | 20.58 | 57.00 | 300.67 |
October | 329.00 | 0.75 | 0.73 | 01-OCT-06:00 | 3023.56 | 19.00 | 82.17 | 294.67 | 1488.84 | 20.53 | 54.00 | 265.33 |
November | 284.17 | 0.74 | 0.73 | 01-NOV-07:10 | 2851.20 | 20.25 | 78.67 | 266.50 | 1200.02 | 22.32 | 62.83 | 237.50 |
December | 265.67 | 0.75 | 0.73 | 01-DEC-08:09 | 2626.80 | 20.14 | 80.17 | 242.67 | 1537.28 | 23.88 | 81.67 | 212.33 |
Annual Sum or Average | 4149.83 | 0.74 | 3111.23 | 17.98 | 836.33 | 3820.67 | 1509.88 | 19.97 | 509.83 | 3484.67 | ||
Minimum of Months | 265.67 | 0.74 | 0.73 | 2167.17 | 12.05 | 0.00 | 242.67 | 1067.96 | 16.68 | 0.00 | 212.33 | |
Maximum of Months | 412.83 | 0.75 | 0.73 | 4109.19 | 20.57 | 110.33 | 379.33 | 1842.48 | 23.88 | 82.17 | 357.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2569290.71 | 15948.97 | 17-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3766779.54 | 19040.77 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1217061.61 | 10475.05 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7553131.86 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3766779.54 | 19040.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.411288E+09 | 19629.64 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171004E+09 | 19641.54 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6449665.18 | 19586.06 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27999305.47 | 19604.40 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313966E+09 | 19638.74 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.930707E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.411288E+09 | 19641.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141199E+10 | 5600.01 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811221E+09 | 5610.93 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224661E+09 | 5617.54 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16871858.58 | 5599.45 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 786435.09 | 1782.76 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78103312.91 | 5599.32 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320210E+09 | 5610.39 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140799E+10 | 5599.73 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427183E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141199E+10 | 5617.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111188E+10 | 6234.90 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585563E+09 | 6247.13 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173911E+09 | 6254.30 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5053762.25 | 6214.23 | 06-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89245588.09 | 6234.16 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267501E+09 | 6246.74 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101914E+10 | 6234.43 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325230E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111188E+10 | 6254.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.778787E+09 | 6036.42 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.446684E+09 | 6048.19 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175709E+09 | 6055.31 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17808884.84 | 6035.81 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1795714.53 | 2692.78 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60503166.48 | 6035.68 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121191E+09 | 6047.66 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.620066E+09 | 6036.11 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222254E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.778787E+09 | 6055.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141985E+10 | 6946.47 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.877489E+09 | 6960.11 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.387544E+09 | 6968.06 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55974675.39 | 6945.63 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12234500.12 | 6939.27 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1399271.15 | 2349.07 | 09-JUN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 215978.03 | 134.30 | 09-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155013E+09 | 6945.65 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462891E+09 | 6959.71 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139594E+10 | 6945.91 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476855E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141985E+10 | 6968.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550224E+09 | 4662.51 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382787E+09 | 4671.69 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89986513.01 | 4669.83 | 15-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 738451.63 | 1564.75 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11378514.00 | 4651.80 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327229E+09 | 4660.00 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136234E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.550224E+09 | 4671.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417119E+09 | 5287.13 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231821E+09 | 5297.66 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40135519.79 | 5295.48 | 15-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 965080.10 | 5280.27 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2072343.08 | 5275.08 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241689E+09 | 5283.99 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.933801E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.417119E+09 | 5297.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168431E+10 | 5142.18 | 10-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129878E+10 | 5263.28 | 21-FEB-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106987E+10 | 5304.08 | 20-MAR-11:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.572744E+09 | 5312.94 | 19-APR-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.403892E+09 | 5338.64 | 30-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73470346.76 | 5351.19 | 06-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7257255.37 | 3961.72 | 31-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66330216.90 | 5299.70 | 21-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460231E+09 | 5280.99 | 04-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.615517E+09 | 5239.61 | 09-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139399E+10 | 5187.09 | 01-DEC-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764639E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168431E+10 | 5351.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505382E+09 | 5657.95 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311240E+09 | 5669.22 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122313E+09 | 5676.29 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 529684.34 | 652.49 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20887.80 | 208.88 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2812256.74 | 5650.59 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7926084.99 | 5645.07 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313179E+09 | 5654.54 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126340E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505382E+09 | 5676.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405425E+09 | 4910.45 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198463E+09 | 4920.23 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16359216.43 | 4904.85 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4349675.38 | 4904.15 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27148872.00 | 4905.44 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342619E+09 | 4907.40 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994365E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405425E+09 | 4920.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549512E+09 | 6247.37 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235922E+09 | 6259.93 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34756942.96 | 6256.29 | 15-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31027.22 | 206.85 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19117934.31 | 6246.41 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48325391.80 | 6232.70 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468800E+09 | 6243.78 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135647E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.549512E+09 | 6259.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.210849E+09 | 5348.70 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91363055.19 | 5359.35 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10553111.40 | 5334.71 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3468100.72 | 5341.81 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3691484.02 | 5335.99 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129250E+09 | 5345.43 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449175E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210849E+09 | 5359.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.621399E+09 | 6507.22 | 13-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332134E+09 | 6520.32 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98736365.98 | 6516.52 | 15-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3063434.91 | 2242.13 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13189.01 | 131.89 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26594103.92 | 6506.22 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95043114.98 | 6500.87 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555002E+09 | 6503.51 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173199E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.621399E+09 | 6520.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT_HEATC
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104701E+10 | 9920.52 | 21-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.480957E+09 | 8423.38 | 04-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60120263.34 | 3799.47 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 334482.14 | 386.80 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23258190.15 | 3963.16 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54703563.18 | 6444.47 | 27-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.760326E+09 | 9361.74 | 15-DEC-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242671E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104701E+10 | 9920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID_HEATC
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.381122E+10 | 13534.21 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211422E+10 | 12463.75 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470726E+09 | 7363.49 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57729191.25 | 4036.36 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 140339.29 | 236.68 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276359E+09 | 8426.14 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687486E+09 | 10462.12 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364068E+10 | 13288.43 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110586E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381122E+10 | 13534.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP_HEATC
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460406E+10 | 16250.10 | 21-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281211E+10 | 15048.07 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.830377E+09 | 9904.13 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152118E+09 | 6241.78 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11604688.75 | 2048.35 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.537801E+09 | 10651.20 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116728E+10 | 13262.43 | 27-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.459433E+10 | 16426.46 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147097E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460406E+10 | 16426.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT_COOLC DXCOIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.326436E+09 | 0.326434E+09 | 9501.40 | 05-JAN-14:00 | 9501.40 | 0.00 |
February | 0.00 | 0.00 | 0.147259E+10 | 0.147209E+10 | 33999.18 | 14-FEB-16:10 | 33999.18 | 0.00 |
March | 0.00 | 0.00 | 0.510217E+10 | 0.509866E+10 | 33767.10 | 08-MAR-14:00 | 33767.10 | 0.00 |
April | 0.00 | 0.00 | 0.171214E+11 | 0.170979E+11 | 48425.88 | 13-APR-16:00 | 48425.88 | 0.00 |
May | 0.00 | 0.00 | 0.306721E+11 | 0.297083E+11 | 57479.66 | 19-MAY-16:10 | 57479.66 | 0.00 |
June | 0.00 | 0.00 | 0.579659E+11 | 0.557001E+11 | 76457.23 | 29-JUN-05:02 | 63261.30 | 0.00 |
July | 0.00 | 0.00 | 0.753662E+11 | 0.650822E+11 | 76885.43 | 31-JUL-16:50 | 48090.93 | 0.00 |
August | 0.00 | 0.00 | 0.749923E+11 | 0.640802E+11 | 87052.60 | 23-AUG-16:00 | 47788.73 | 0.00 |
September | 0.00 | 0.00 | 0.517273E+11 | 0.463874E+11 | 89440.13 | 05-SEP-13:00 | 52047.99 | 0.00 |
October | 0.00 | 0.00 | 0.239509E+11 | 0.225076E+11 | 63442.89 | 06-OCT-16:00 | 63442.89 | 0.00 |
November | 0.00 | 0.00 | 0.125994E+10 | 0.122505E+10 | 21957.55 | 09-NOV-14:00 | 21957.55 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.339957E+12 | 0.308686E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.753662E+11 | 0.650822E+11 | 89440.13 | 63442.89 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID_COOLC DXCOIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.247495E+09 | 0.247495E+09 | 7309.42 | 05-JAN-16:00 | 7309.42 | 0.00 |
February | 0.00 | 0.00 | 0.117284E+10 | 0.117281E+10 | 28290.56 | 14-FEB-16:00 | 28290.56 | 0.00 |
March | 0.00 | 0.00 | 0.426780E+10 | 0.426444E+10 | 26864.56 | 08-MAR-16:00 | 26864.56 | 0.00 |
April | 0.00 | 0.00 | 0.141739E+11 | 0.141594E+11 | 42297.30 | 13-APR-16:00 | 42297.30 | 0.00 |
May | 0.00 | 0.00 | 0.254012E+11 | 0.246699E+11 | 49581.08 | 19-MAY-16:00 | 49581.08 | 0.00 |
June | 0.00 | 0.00 | 0.477842E+11 | 0.460851E+11 | 67516.45 | 29-JUN-05:02 | 55751.54 | 0.00 |
July | 0.00 | 0.00 | 0.617556E+11 | 0.533832E+11 | 65053.71 | 31-JUL-15:20 | 56128.15 | 0.00 |
August | 0.00 | 0.00 | 0.597846E+11 | 0.511603E+11 | 69381.94 | 23-AUG-16:00 | 38009.74 | 0.00 |
September | 0.00 | 0.00 | 0.399906E+11 | 0.358651E+11 | 71151.22 | 05-SEP-13:00 | 41301.12 | 0.00 |
October | 0.00 | 0.00 | 0.181956E+11 | 0.171261E+11 | 53111.32 | 02-OCT-15:00 | 49977.64 | 0.00 |
November | 0.00 | 0.00 | 0.865680E+09 | 0.833633E+09 | 14238.64 | 02-NOV-15:00 | 14238.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.273640E+12 | 0.248968E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.617556E+11 | 0.533832E+11 | 71151.22 | 56128.15 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP_COOLC DXCOIL
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.241183E+09 | 0.241172E+09 | 6844.44 | 05-JAN-15:40 | 6844.44 | 0.00 |
February | 0.00 | 0.00 | 0.116433E+10 | 0.116387E+10 | 28413.02 | 14-FEB-15:50 | 28413.02 | 0.00 |
March | 0.00 | 0.00 | 0.426536E+10 | 0.425703E+10 | 27764.44 | 08-MAR-16:00 | 27764.44 | 0.00 |
April | 0.00 | 0.00 | 0.149868E+11 | 0.149659E+11 | 48317.06 | 13-APR-16:00 | 48317.06 | 0.00 |
May | 0.00 | 0.00 | 0.277443E+11 | 0.269158E+11 | 57553.87 | 19-MAY-16:00 | 57553.87 | 0.00 |
June | 0.00 | 0.00 | 0.529429E+11 | 0.511125E+11 | 74222.04 | 28-JUN-16:00 | 74222.04 | 0.00 |
July | 0.00 | 0.00 | 0.685751E+11 | 0.598434E+11 | 73943.85 | 31-JUL-15:30 | 64711.42 | 0.00 |
August | 0.00 | 0.00 | 0.651974E+11 | 0.562856E+11 | 74285.94 | 23-AUG-16:00 | 40775.78 | 0.00 |
September | 0.00 | 0.00 | 0.423338E+11 | 0.380242E+11 | 76643.95 | 05-SEP-13:30 | 46084.21 | 0.00 |
October | 0.00 | 0.00 | 0.185665E+11 | 0.174661E+11 | 58529.82 | 02-OCT-14:50 | 55468.78 | 0.00 |
November | 0.00 | 0.00 | 0.797298E+09 | 0.749802E+09 | 13727.72 | 02-NOV-15:00 | 13727.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.296815E+12 | 0.271025E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.685751E+11 | 0.598434E+11 | 76643.95 | 74222.04 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 329.32 | 4565.47 | 16-JAN-10:30 | 1623.69 | 6424.63 | 30-JAN-12:10 |
February | 323.90 | 4563.21 | 20-FEB-10:30 | 1662.59 | 6439.28 | 06-FEB-12:10 |
March | 236.34 | 4161.43 | 27-MAR-05:20 | 1735.68 | 6377.76 | 01-MAR-12:06 |
April | 304.83 | 4202.64 | 17-APR-05:20 | 1507.28 | 6096.63 | 03-APR-11:10 |
May | 347.46 | 4636.55 | 29-MAY-07:36 | 1445.70 | 5730.69 | 01-MAY-11:10 |
June | 300.66 | 4315.44 | 26-JUN-05:30 | 1374.73 | 5315.41 | 01-JUN-11:07 |
July | 408.98 | 4344.89 | 31-JUL-05:30 | 1145.60 | 4972.38 | 03-JUL-11:20 |
August | 310.50 | 4349.48 | 07-AUG-05:30 | 1299.76 | 4893.58 | 31-AUG-11:50 |
September | 378.43 | 4667.33 | 04-SEP-17:00 | 1239.19 | 5126.14 | 29-SEP-11:20 |
October | 400.29 | 4644.43 | 09-OCT-07:30 | 1326.90 | 5529.51 | 31-OCT-11:10 |
November | 349.14 | 4612.97 | 12-NOV-08:30 | 1466.91 | 5947.24 | 30-NOV-12:07 |
December | 346.02 | 4297.82 | 25-DEC-11:00 | 1506.28 | 6248.37 | 27-DEC-12:10 |
Annual Sum or Average | 336.46 | 1443.25 | ||||
Minimum of Months | 236.34 | 4161.43 | 1145.60 | 4893.58 | ||
Maximum of Months | 408.98 | 4667.33 | 1735.68 | 6439.28 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.267824E+10 | 0.37 | 4471.02 | 26-JAN-08:02 | 1.07 |
February | 0.249899E+10 | 0.38 | 4688.22 | 01-FEB-08:03 | 1.09 |
March | 0.301460E+10 | 0.40 | 4370.06 | 31-MAR-08:00 | 1.05 |
April | 0.301471E+10 | 0.40 | 7511.00 | 14-APR-05:02 | 1.45 |
May | 0.336412E+10 | 0.42 | 7511.00 | 12-MAY-05:02 | 1.45 |
June | 0.407984E+10 | 0.48 | 8703.20 | 29-JUN-04:01 | 1.57 |
July | 0.430503E+10 | 0.48 | 8966.32 | 21-JUL-04:01 | 1.60 |
August | 0.465717E+10 | 0.51 | 10576.77 | 22-AUG-04:01 | 1.77 |
September | 0.399036E+10 | 0.47 | 7800.96 | 23-SEP-05:02 | 1.46 |
October | 0.393117E+10 | 0.45 | 7511.00 | 17-OCT-05:02 | 1.45 |
November | 0.345410E+10 | 0.42 | 7511.00 | 01-NOV-05:02 | 1.44 |
December | 0.281294E+10 | 0.38 | 4763.46 | 07-DEC-08:02 | 1.10 |
Annual Sum or Average | 0.418013E+11 | 0.43 | |||
Minimum of Months | 0.249899E+10 | 0.37 | 4370.06 | 1.05 | |
Maximum of Months | 0.465717E+10 | 0.51 | 10576.77 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189123E+10 | 0.37 | 3110.70 | 26-JAN-16:40 | 1.02 |
February | 0.179064E+10 | 0.37 | 3326.69 | 15-FEB-16:20 | 1.06 |
March | 0.217043E+10 | 0.40 | 2724.70 | 10-MAR-15:00 | 0.95 |
April | 0.241087E+10 | 0.42 | 4246.77 | 14-APR-05:02 | 1.22 |
May | 0.274315E+10 | 0.44 | 4246.77 | 01-MAY-05:03 | 1.22 |
June | 0.343254E+10 | 0.51 | 8281.82 | 29-JUN-05:02 | 1.82 |
July | 0.360103E+10 | 0.51 | 10860.58 | 24-JUL-04:01 | 2.16 |
August | 0.374738E+10 | 0.53 | 8675.01 | 22-AUG-04:01 | 1.87 |
September | 0.305434E+10 | 0.47 | 4891.98 | 12-SEP-05:02 | 1.31 |
October | 0.283499E+10 | 0.44 | 4858.24 | 02-OCT-05:02 | 1.31 |
November | 0.229180E+10 | 0.40 | 4601.86 | 01-NOV-15:30 | 1.27 |
December | 0.193698E+10 | 0.37 | 2738.63 | 29-DEC-16:30 | 0.95 |
Annual Sum or Average | 0.319054E+11 | 0.44 | |||
Minimum of Months | 0.179064E+10 | 0.37 | 2724.70 | 0.95 | |
Maximum of Months | 0.374738E+10 | 0.53 | 10860.58 | 2.16 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181801E+10 | 0.35 | 2383.08 | 26-JAN-16:30 | 0.83 |
February | 0.168770E+10 | 0.35 | 2887.27 | 15-FEB-15:50 | 0.91 |
March | 0.199909E+10 | 0.37 | 2351.12 | 10-MAR-15:20 | 0.82 |
April | 0.223432E+10 | 0.38 | 3610.23 | 13-APR-16:00 | 1.03 |
May | 0.264063E+10 | 0.42 | 4343.46 | 19-MAY-16:00 | 1.14 |
June | 0.346117E+10 | 0.48 | 6082.68 | 28-JUN-16:00 | 1.40 |
July | 0.372093E+10 | 0.49 | 10623.24 | 24-JUL-04:01 | 1.97 |
August | 0.374568E+10 | 0.49 | 6121.20 | 22-AUG-04:01 | 1.40 |
September | 0.285588E+10 | 0.43 | 4503.37 | 29-SEP-14:40 | 1.16 |
October | 0.245144E+10 | 0.39 | 4457.68 | 02-OCT-05:02 | 1.15 |
November | 0.195618E+10 | 0.36 | 3767.26 | 01-NOV-15:30 | 1.05 |
December | 0.182573E+10 | 0.34 | 2124.67 | 29-DEC-16:10 | 0.78 |
Annual Sum or Average | 0.303968E+11 | 0.40 | |||
Minimum of Months | 0.168770E+10 | 0.34 | 2124.67 | 0.78 | |
Maximum of Months | 0.374568E+10 | 0.49 | 10623.24 | 1.97 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.29 | 393675.69 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 73.35 | 0.05 |
February | 1186777.96 | 356033.39 | 0.73 | 01-FEB-06:02 | 0.22 | 0.22 | 58.11 | 0.05 |
March | 1343620.87 | 403086.26 | 0.73 | 01-MAR-06:02 | 0.22 | 0.22 | 59.55 | 0.05 |
April | 1267813.46 | 380344.04 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 60.32 | 0.05 |
May | 1327936.58 | 398380.97 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 71.68 | 0.05 |
June | 1296568.00 | 388970.40 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 60.07 | 0.05 |
July | 1299182.04 | 389754.61 | 0.73 | 01-JUL-05:02 | 0.22 | 0.22 | 60.88 | 0.05 |
August | 1343620.87 | 403086.26 | 0.73 | 01-AUG-05:02 | 0.22 | 0.22 | 60.12 | 0.05 |
September | 1267813.46 | 380344.04 | 0.73 | 01-SEP-05:02 | 0.22 | 0.22 | 60.73 | 0.05 |
October | 1312252.29 | 393675.69 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 69.39 | 0.05 |
November | 1278269.66 | 383480.90 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 59.37 | 0.05 |
December | 1299182.04 | 389754.61 | 0.73 | 01-DEC-06:02 | 0.22 | 0.22 | 60.45 | 0.05 |
Annual Sum or Average | 15535289.52 | 4660586.86 | ||||||
Minimum of Months | 1186777.96 | 356033.39 | 0.73 | 0.22 | 0.22 | 58.11 | 0.05 | |
Maximum of Months | 1343620.87 | 403086.26 | 0.73 | 0.22 | 0.22 | 73.35 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 329.32 | 4565.47 | 16-JAN-10:30 | 80.27 | 82.22 | 1623.69 | 6424.63 | 30-JAN-12:10 |
February | 323.90 | 4563.21 | 20-FEB-10:30 | 80.26 | 82.22 | 1662.59 | 6439.28 | 06-FEB-12:10 |
March | 236.34 | 4161.43 | 27-MAR-05:20 | 78.48 | 81.78 | 1735.68 | 6377.76 | 01-MAR-12:06 |
April | 304.83 | 4202.64 | 17-APR-05:20 | 78.67 | 81.82 | 1507.28 | 6096.63 | 03-APR-11:10 |
May | 347.46 | 4636.55 | 29-MAY-07:36 | 80.59 | 82.22 | 1445.70 | 5730.69 | 01-MAY-11:10 |
June | 300.66 | 4315.44 | 26-JUN-05:30 | 79.17 | 81.85 | 1374.73 | 5315.41 | 01-JUN-11:07 |
July | 408.98 | 4344.89 | 31-JUL-05:30 | 79.30 | 81.87 | 1145.60 | 4972.38 | 03-JUL-11:20 |
August | 310.50 | 4349.48 | 07-AUG-05:30 | 79.32 | 81.89 | 1299.76 | 4893.58 | 31-AUG-11:50 |
September | 378.43 | 4667.33 | 04-SEP-17:00 | 80.72 | 82.22 | 1239.19 | 5126.14 | 29-SEP-11:20 |
October | 400.29 | 4644.43 | 09-OCT-07:30 | 80.62 | 82.22 | 1326.90 | 5529.51 | 31-OCT-11:10 |
November | 349.14 | 4612.97 | 12-NOV-08:30 | 80.48 | 82.22 | 1466.91 | 5947.24 | 30-NOV-12:07 |
December | 346.02 | 4297.82 | 25-DEC-11:00 | 79.09 | 80.99 | 1506.28 | 6248.37 | 27-DEC-12:10 |
Annual Sum or Average | 336.46 | 1443.25 | ||||||
Minimum of Months | 236.34 | 4161.43 | 78.48 | 80.99 | 1145.60 | 4893.58 | ||
Maximum of Months | 408.98 | 4667.33 | 80.72 | 82.22 | 1735.68 | 6439.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.72 | 4.17 |
February | 2.61 | 4.68 |
March | 3.03 | 5.04 |
April | 3.44 | 4.09 |
May | 4.44 | 3.33 |
June | 7.78 | 2.70 |
July | 11.12 | 2.52 |
August | 8.17 | 2.42 |
September | 7.06 | 2.64 |
October | 6.72 | 2.51 |
November | 2.74 | 4.15 |
December | 2.33 | 4.76 |
Annual Sum or Average | 63.15 | 3.14 |
Minimum of Months | 2.33 | 2.42 |
Maximum of Months | 11.12 | 5.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.10 | 0.00 |
August | 0.00 | 0.00 |
September | 0.06 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.15 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.10 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.25 | 3.82 |
February | 0.33 | 3.97 |
March | 1.23 | 3.48 |
April | 1.78 | 3.31 |
May | 1.65 | 3.05 |
June | 1.49 | 2.01 |
July | 2.56 | 1.97 |
August | 2.06 | 1.99 |
September | 1.19 | 2.00 |
October | 1.68 | 3.22 |
November | 0.41 | 4.27 |
December | 0.14 | 2.65 |
Annual Sum or Average | 14.77 | 2.67 |
Minimum of Months | 0.14 | 1.97 |
Maximum of Months | 2.56 | 4.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.24 | 2.65 |
March | 0.96 | 3.41 |
April | 1.96 | 3.62 |
May | 2.98 | 3.50 |
June | 1.98 | 3.15 |
July | 2.75 | 1.78 |
August | 2.09 | 1.99 |
September | 1.99 | 3.53 |
October | 1.80 | 3.63 |
November | 0.15 | 4.57 |
December | 0.00 | 0.00 |
Annual Sum or Average | 16.88 | 3.02 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.98 | 4.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.84 |
February | 0.00 | 0.00 |
March | 0.28 | 0.45 |
April | 0.91 | 0.67 |
May | 2.57 | 0.64 |
June | 1.87 | 0.54 |
July | 4.64 | 0.48 |
August | 3.82 | 0.53 |
September | 2.08 | 0.77 |
October | 0.91 | 0.73 |
November | 0.06 | 0.56 |
December | 0.39 | 0.76 |
Annual Sum or Average | 17.69 | 0.59 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.64 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.29 | 0.35 |
February | 0.38 | 0.35 |
March | 1.08 | 0.34 |
April | 3.48 | 0.39 |
May | 5.10 | 0.41 |
June | 4.47 | 0.31 |
July | 9.57 | 0.30 |
August | 7.42 | 0.34 |
September | 4.21 | 0.42 |
October | 3.32 | 0.43 |
November | 0.35 | 0.52 |
December | 0.44 | 0.35 |
Annual Sum or Average | 40.13 | 0.36 |
Minimum of Months | 0.29 | 0.30 |
Maximum of Months | 9.57 | 0.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 0.56 |
February | 0.06 | 0.56 |
March | 0.42 | 0.35 |
April | 1.51 | 0.73 |
May | 2.92 | 0.69 |
June | 3.47 | 0.68 |
July | 5.13 | 0.50 |
August | 4.25 | 0.55 |
September | 2.42 | 0.72 |
October | 1.34 | 0.63 |
November | 0.24 | 0.69 |
December | 0.14 | 0.56 |
Annual Sum or Average | 22.07 | 0.61 |
Minimum of Months | 0.06 | 0.35 |
Maximum of Months | 5.13 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 0.35 |
February | 0.38 | 0.35 |
March | 1.19 | 0.33 |
April | 3.32 | 0.39 |
May | 5.34 | 0.40 |
June | 5.65 | 0.37 |
July | 8.18 | 0.31 |
August | 6.21 | 0.36 |
September | 4.07 | 0.42 |
October | 3.06 | 0.45 |
November | 0.50 | 0.51 |
December | 0.14 | 0.35 |
Annual Sum or Average | 38.24 | 0.37 |
Minimum of Months | 0.14 | 0.31 |
Maximum of Months | 8.18 | 0.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.58 | 0.69 |
May | 1.50 | 0.71 |
June | 1.63 | 0.31 |
July | 3.64 | 0.46 |
August | 3.08 | 0.34 |
September | 2.82 | 0.40 |
October | 1.38 | 0.28 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.63 | 0.43 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.64 | 0.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.06 | 0.35 |
February | 0.58 | 0.49 |
March | 0.38 | 0.56 |
April | 2.06 | 0.49 |
May | 3.88 | 0.43 |
June | 4.93 | 0.28 |
July | 10.03 | 0.30 |
August | 8.11 | 0.30 |
September | 6.19 | 0.34 |
October | 5.22 | 0.33 |
November | 0.92 | 0.46 |
December | 0.17 | 0.35 |
Annual Sum or Average | 43.51 | 0.34 |
Minimum of Months | 0.17 | 0.28 |
Maximum of Months | 10.03 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 5.26 | 2.91 |
February | 2.77 | 3.51 |
March | 4.72 | 4.97 |
April | 4.57 | 4.13 |
May | 5.17 | 4.09 |
June | 4.73 | 2.78 |
July | 6.04 | 2.27 |
August | 6.94 | 2.99 |
September | 6.13 | 3.42 |
October | 4.99 | 2.01 |
November | 4.21 | 2.73 |
December | 3.11 | 3.63 |
Annual Sum or Average | 58.64 | 3.24 |
Minimum of Months | 2.77 | 2.01 |
Maximum of Months | 6.94 | 4.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.71 | 0.35 |
February | 0.38 | 0.40 |
March | 0.41 | 0.52 |
April | 2.64 | 0.46 |
May | 3.93 | 0.45 |
June | 6.20 | 0.36 |
July | 8.70 | 0.31 |
August | 7.87 | 0.30 |
September | 5.86 | 0.35 |
October | 4.41 | 0.32 |
November | 0.96 | 0.46 |
December | 0.19 | 0.35 |
Annual Sum or Average | 42.27 | 0.35 |
Minimum of Months | 0.19 | 0.30 |
Maximum of Months | 8.70 | 0.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.35 | 0.56 |
April | 1.11 | 0.76 |
May | 1.88 | 0.77 |
June | 1.82 | 0.34 |
July | 3.61 | 0.43 |
August | 2.49 | 0.34 |
September | 2.16 | 0.69 |
October | 0.94 | 0.71 |
November | 0.06 | 1.12 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.42 | 0.54 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.61 | 1.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.11 | 0.35 |
February | 0.92 | 0.37 |
March | 1.53 | 0.43 |
April | 3.69 | 0.40 |
May | 4.59 | 0.43 |
June | 4.57 | 0.28 |
July | 10.35 | 0.31 |
August | 8.27 | 0.31 |
September | 4.61 | 0.39 |
October | 4.88 | 0.41 |
November | 1.46 | 0.42 |
December | 1.07 | 0.35 |
Annual Sum or Average | 47.07 | 0.36 |
Minimum of Months | 0.92 | 0.28 |
Maximum of Months | 10.35 | 0.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.56 |
February | 0.08 | 0.56 |
March | 0.59 | 0.56 |
April | 1.66 | 0.73 |
May | 2.25 | 0.79 |
June | 2.91 | 0.52 |
July | 4.68 | 0.48 |
August | 3.98 | 0.41 |
September | 2.58 | 0.65 |
October | 1.43 | 0.64 |
November | 0.28 | 0.67 |
December | 0.00 | 0.00 |
Annual Sum or Average | 20.65 | 0.56 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.68 | 0.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.86 | 0.35 |
February | 0.50 | 0.39 |
March | 1.54 | 0.43 |
April | 3.72 | 0.40 |
May | 4.86 | 0.43 |
June | 6.28 | 0.35 |
July | 8.87 | 0.31 |
August | 7.38 | 0.33 |
September | 4.19 | 0.41 |
October | 3.61 | 0.44 |
November | 0.67 | 0.50 |
December | 0.71 | 0.35 |
Annual Sum or Average | 43.19 | 0.37 |
Minimum of Months | 0.50 | 0.31 |
Maximum of Months | 8.87 | 0.50 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.592783E+10 | 0.130877E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.509878E+10 | 0.601196E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.568093E+10 | 75150329.18 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.783074E+10 | 418102.68 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113837E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.197904E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.243555E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.238574E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168064E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102529E+11 | 29072737.69 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.443669E+10 | 68379453.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.508903E+10 | 0.950408E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140510E+12 | 0.303339E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.443669E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.243555E+11 | 0.130877E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.375109E+10 | 0.476402E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.295008E+10 | 0.264278E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.345005E+10 | 0.588408E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.590026E+10 | 72161489.06 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.900697E+10 | 175424.11 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.162728E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.199864E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.190181E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.128878E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.733287E+10 | 0.345448E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.270474E+10 | 0.859357E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.343387E+10 | 0.455084E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.106695E+12 | 0.138232E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.270474E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.199864E+11 | 0.476402E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.702048E+10 | 0.575508E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.487928E+10 | 0.351514E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.409744E+10 | 0.103797E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.604007E+10 | 0.190148E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.954025E+10 | 14505860.94 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.178005E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.220429E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.205182E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133417E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.740740E+10 | 0.672251E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.337804E+10 | 0.145910E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.658285E+10 | 0.574292E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122649E+12 | 0.183871E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.337804E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.220429E+11 | 0.575508E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.267824E+10 | 0.326436E+09 | 0.420405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249899E+10 | 0.147259E+10 | 0.270559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301460E+10 | 0.510217E+10 | 0.138242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301471E+10 | 0.171214E+11 | 0.574346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336412E+10 | 0.306721E+11 | 0.403913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.407984E+10 | 0.579659E+11 | 73470346.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.430503E+10 | 0.753662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465717E+10 | 0.749923E+11 | 7257255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.399036E+10 | 0.517273E+11 | 66330216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.393117E+10 | 0.239509E+11 | 0.487267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345410E+10 | 0.125994E+10 | 0.691598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281294E+10 | 0.00 | 0.303641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418013E+11 | 0.339957E+12 | 0.136327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.249899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465717E+10 | 0.753662E+11 | 0.420405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189123E+10 | 0.247495E+09 | 0.560097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179064E+10 | 0.117284E+10 | 0.297587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217043E+10 | 0.426780E+10 | 0.631132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241087E+10 | 0.141739E+11 | 60823653.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274315E+10 | 0.254012E+11 | 153528.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.343254E+10 | 0.477842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.360103E+10 | 0.617556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.374738E+10 | 0.597846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305434E+10 | 0.399906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283499E+10 | 0.181956E+11 | 0.329889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229180E+10 | 0.865680E+09 | 0.861695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193698E+10 | 0.00 | 0.513756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319054E+11 | 0.273640E+12 | 0.155981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374738E+10 | 0.617556E+11 | 0.560097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.181801E+10 | 0.241183E+09 | 0.973785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168770E+10 | 0.116433E+10 | 0.570407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199909E+10 | 0.426536E+10 | 0.179865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223432E+10 | 0.149868E+11 | 0.247827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264063E+10 | 0.277443E+11 | 26421338.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346117E+10 | 0.529429E+11 | 1399271.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.372093E+10 | 0.685751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.374568E+10 | 0.651974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285588E+10 | 0.423338E+11 | 215978.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245144E+10 | 0.185665E+11 | 0.920666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195618E+10 | 0.797298E+09 | 0.236707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182573E+10 | 0.00 | 0.935145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303968E+11 | 0.296815E+12 | 0.301556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374568E+10 | 0.685751E+11 | 0.973785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.267824E+10 | 0.00 | 0.00 | 0.00 | 92553343.11 | 0.315704E+10 | 0.130877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249899E+10 | 0.00 | 0.00 | 0.00 | 0.375151E+09 | 0.222463E+10 | 0.601196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301460E+10 | 0.00 | 0.00 | 0.00 | 0.134402E+10 | 0.132230E+10 | 75150329.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301471E+10 | 0.00 | 0.00 | 0.00 | 0.424202E+10 | 0.574012E+09 | 418102.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336412E+10 | 0.00 | 0.00 | 0.00 | 0.761570E+10 | 0.403913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.407984E+10 | 0.00 | 0.00 | 0.00 | 0.156371E+11 | 73470346.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.430503E+10 | 0.00 | 0.00 | 0.00 | 0.200505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465717E+10 | 0.00 | 0.00 | 0.00 | 0.191930E+11 | 7257255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.399036E+10 | 0.00 | 0.00 | 0.00 | 0.127497E+11 | 66330216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.393117E+10 | 0.00 | 0.00 | 0.00 | 0.585768E+10 | 0.464009E+09 | 29072737.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345410E+10 | 0.00 | 0.00 | 0.00 | 0.345689E+09 | 0.636894E+09 | 68379453.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227609E+10 | 0.950408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418013E+11 | 0.00 | 0.00 | 0.00 | 0.875031E+11 | 0.112059E+11 | 0.303339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.249899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465717E+10 | 0.00 | 0.00 | 0.00 | 0.200505E+11 | 0.315704E+10 | 0.130877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.189123E+10 | 0.00 | 0.00 | 0.00 | 70105477.23 | 0.178976E+10 | 0.476402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179064E+10 | 0.00 | 0.00 | 0.00 | 0.297793E+09 | 0.861650E+09 | 0.264278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217043E+10 | 0.00 | 0.00 | 0.00 | 0.111921E+10 | 0.160406E+09 | 0.588408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241087E+10 | 0.00 | 0.00 | 0.00 | 0.348629E+10 | 3094462.12 | 72161489.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274315E+10 | 0.00 | 0.00 | 0.00 | 0.626380E+10 | 13189.01 | 175424.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.343254E+10 | 0.00 | 0.00 | 0.00 | 0.128402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.360103E+10 | 0.00 | 0.00 | 0.00 | 0.163853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.374738E+10 | 0.00 | 0.00 | 0.00 | 0.152707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305434E+10 | 0.00 | 0.00 | 0.00 | 0.983347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283499E+10 | 0.00 | 0.00 | 0.00 | 0.444435E+10 | 53529814.33 | 0.345448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229180E+10 | 0.00 | 0.00 | 0.00 | 0.238730E+09 | 0.174209E+09 | 0.859357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149689E+10 | 0.455084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319054E+11 | 0.00 | 0.00 | 0.00 | 0.702500E+11 | 0.453954E+10 | 0.138232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.179064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374738E+10 | 0.00 | 0.00 | 0.00 | 0.163853E+11 | 0.178976E+10 | 0.476402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.181801E+10 | 0.00 | 0.00 | 0.00 | 68681277.30 | 0.513379E+10 | 0.575508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168770E+10 | 0.00 | 0.00 | 0.00 | 0.299623E+09 | 0.289196E+10 | 0.351514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199909E+10 | 0.00 | 0.00 | 0.00 | 0.113007E+10 | 0.968274E+09 | 0.103797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223432E+10 | 0.00 | 0.00 | 0.00 | 0.371004E+10 | 95709181.06 | 0.190148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264063E+10 | 0.00 | 0.00 | 0.00 | 0.688480E+10 | 14816649.74 | 14505860.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346117E+10 | 0.00 | 0.00 | 0.00 | 0.143380E+11 | 1399271.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.372093E+10 | 0.00 | 0.00 | 0.00 | 0.183220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.374568E+10 | 0.00 | 0.00 | 0.00 | 0.167725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285588E+10 | 0.00 | 0.00 | 0.00 | 0.104856E+11 | 215978.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245144E+10 | 0.00 | 0.00 | 0.00 | 0.457309E+10 | 0.382865E+09 | 0.672251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195618E+10 | 0.00 | 0.00 | 0.00 | 0.222067E+09 | 0.119979E+10 | 0.145910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475711E+10 | 0.574292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303968E+11 | 0.00 | 0.00 | 0.00 | 0.768065E+11 | 0.154459E+11 | 0.183871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.168770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374568E+10 | 0.00 | 0.00 | 0.00 | 0.183220E+11 | 0.513379E+10 | 0.575508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.536356E+10 | 0.00 | 0.00 | 45605010.88 | 0.00 | 0.00 | 0.183154E+11 | 0.00 | 0.66 |
February | 0.350856E+10 | 0.00 | 0.00 | 44292821.72 | 0.00 | 0.00 | 0.184068E+11 | 0.00 | 0.74 |
March | 0.230602E+10 | 0.00 | 0.00 | 53440544.28 | 0.00 | 0.00 | 0.238729E+11 | 0.00 | 1.06 |
April | 0.160672E+10 | 2456492.16 | 0.00 | 48050633.52 | 2002065.23 | 0.00 | 0.184555E+11 | 0.00 | 1.16 |
May | 0.149455E+10 | 34876308.52 | 0.00 | 49765069.19 | 9082674.31 | 0.00 | 0.148732E+11 | 0.00 | 1.17 |
June | 0.110796E+10 | 0.861223E+09 | 0.00 | 29177789.11 | 58156512.55 | 0.00 | 0.477740E+10 | 0.00 | 0.82 |
July | 0.313854E+09 | 0.335772E+10 | 0.00 | 3937177.19 | 0.339057E+09 | 0.00 | 0.109289E+09 | 0.00 | 0.62 |
August | 0.663343E+09 | 0.229936E+10 | 0.00 | 17359968.56 | 0.149019E+09 | 0.00 | 0.147272E+10 | 0.00 | 0.84 |
September | 0.131954E+10 | 0.428345E+09 | 0.00 | 44192619.01 | 99520413.93 | 0.00 | 0.654010E+10 | 0.00 | 1.02 |
October | 0.229352E+10 | 27635171.00 | 0.00 | 56698139.27 | 7327175.32 | 0.00 | 0.194361E+11 | 0.00 | 1.17 |
November | 0.216911E+10 | 0.00 | 0.00 | 59412453.04 | 0.00 | 0.00 | 0.269010E+11 | 0.00 | 1.01 |
December | 0.443130E+10 | 0.00 | 0.00 | 50518775.15 | 0.00 | 0.00 | 0.201091E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.265781E+11 | 0.701162E+10 | 0.00 | 0.502451E+09 | 0.664164E+09 | 0.00 | 0.173270E+12 | 0.00 | 0.90 |
Minimum of Months | 0.313854E+09 | 0.00 | 0.00 | 3937177.19 | 0.00 | 0.00 | 0.109289E+09 | 0.00 | 0.59 |
Maximum of Months | 0.536356E+10 | 0.335772E+10 | 0.00 | 59412453.04 | 0.339057E+09 | 0.00 | 0.269010E+11 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.769983E+10 | 0.00 | 0.00 | 6396487.58 | 0.00 | 549320.64 | 0.447101E+10 | 0.00 | 0.33 |
February | 0.546557E+10 | 0.00 | 0.00 | 8791753.49 | 0.00 | 568161.32 | 0.540045E+10 | 0.00 | 0.36 |
March | 0.429193E+10 | 0.00 | 0.00 | 16191121.63 | 0.00 | 0.00 | 0.886525E+10 | 0.00 | 0.52 |
April | 0.192900E+10 | 1300979.87 | 0.00 | 21766723.05 | 1181950.24 | 0.00 | 0.926729E+10 | 0.00 | 0.64 |
May | 0.112474E+10 | 19930994.27 | 0.00 | 26887650.71 | 6256680.17 | 0.00 | 0.830819E+10 | 0.00 | 0.67 |
June | 0.618095E+09 | 0.552814E+09 | 0.00 | 18894826.28 | 31201844.97 | 0.00 | 0.297869E+10 | 0.00 | 0.52 |
July | 0.235197E+09 | 0.229025E+10 | 0.00 | 4450928.39 | 0.158076E+09 | 0.00 | 0.145240E+09 | 0.00 | 0.42 |
August | 0.360237E+09 | 0.148879E+10 | 0.00 | 12177288.88 | 56173765.83 | 0.00 | 0.988367E+09 | 0.00 | 0.54 |
September | 0.553206E+09 | 0.252440E+09 | 0.00 | 26213955.21 | 57752963.10 | 0.00 | 0.393923E+10 | 0.00 | 0.60 |
October | 0.214660E+10 | 13384735.23 | 0.00 | 25200524.58 | 4697246.19 | 0.00 | 0.906105E+10 | 0.00 | 0.62 |
November | 0.395347E+10 | 0.00 | 0.00 | 17986081.52 | 0.00 | 0.00 | 0.995689E+10 | 0.00 | 0.48 |
December | 0.709942E+10 | 0.00 | 0.00 | 7527840.65 | 0.00 | 495301.84 | 0.500889E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.354773E+11 | 0.461891E+10 | 0.00 | 0.192485E+09 | 0.315340E+09 | 1612783.79 | 0.683905E+11 | 0.00 | 0.50 |
Minimum of Months | 0.235197E+09 | 0.00 | 0.00 | 4450928.39 | 0.00 | 0.00 | 0.145240E+09 | 0.00 | 0.29 |
Maximum of Months | 0.769983E+10 | 0.229025E+10 | 0.00 | 26887650.71 | 0.158076E+09 | 568161.32 | 0.995689E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.883017E+10 | 0.00 | 0.00 | 1792112.31 | 0.00 | 0.246664E+09 | 0.200372E+10 | 0.00 | 0.31 |
February | 0.680871E+10 | 0.00 | 0.00 | 3727998.01 | 0.00 | 70218218.26 | 0.313739E+10 | 0.00 | 0.34 |
March | 0.532207E+10 | 0.00 | 0.00 | 10430576.01 | 0.00 | 380714.24 | 0.678673E+10 | 0.00 | 0.49 |
April | 0.268430E+10 | 0.00 | 0.00 | 18320418.20 | 0.00 | 0.00 | 0.821385E+10 | 0.00 | 0.65 |
May | 0.180913E+10 | 6487195.63 | 0.00 | 24044240.90 | 2358273.47 | 0.00 | 0.758912E+10 | 0.00 | 0.70 |
June | 0.721694E+09 | 0.401753E+09 | 0.00 | 21068910.61 | 32533216.90 | 0.00 | 0.271882E+10 | 0.00 | 0.52 |
July | 0.161255E+09 | 0.210040E+10 | 0.00 | 4185487.02 | 0.217109E+09 | 0.00 | 76671702.46 | 0.00 | 0.42 |
August | 0.301202E+09 | 0.125718E+10 | 0.00 | 12683294.06 | 74670302.42 | 0.00 | 0.791923E+09 | 0.00 | 0.55 |
September | 0.977419E+09 | 0.173803E+09 | 0.00 | 21936186.43 | 48355451.73 | 0.00 | 0.307292E+10 | 0.00 | 0.62 |
October | 0.339892E+10 | 9842598.86 | 0.00 | 16716994.14 | 9583770.76 | 0.00 | 0.616308E+10 | 0.00 | 0.58 |
November | 0.527973E+10 | 0.00 | 0.00 | 9000225.48 | 0.00 | 20389590.51 | 0.632680E+10 | 0.00 | 0.41 |
December | 0.882010E+10 | 0.00 | 0.00 | 1774503.82 | 0.00 | 0.166555E+09 | 0.182031E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.451147E+11 | 0.394947E+10 | 0.00 | 0.145681E+09 | 0.384610E+09 | 0.504207E+09 | 0.487013E+11 | 0.00 | 0.49 |
Minimum of Months | 0.161255E+09 | 0.00 | 0.00 | 1774503.82 | 0.00 | 0.00 | 76671702.46 | 0.00 | 0.27 |
Maximum of Months | 0.883017E+10 | 0.210040E+10 | 0.00 | 24044240.90 | 0.217109E+09 | 0.246664E+09 | 0.821385E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837936E+09 | 0.00 | 0.00 | 0.41 |
February | 0.227482E+10 | 0.00 | 0.00 | 56485.46 | 0.00 | 0.463141E+09 | 55193710.12 | 0.00 | 0.44 |
March | 0.249121E+10 | 0.00 | 0.00 | 558650.39 | 0.00 | 0.130014E+09 | 0.585768E+09 | 0.00 | 0.60 |
April | 0.134248E+10 | 0.00 | 0.00 | 3117460.27 | 0.00 | 5310304.93 | 0.132625E+10 | 0.00 | 0.78 |
May | 0.849627E+09 | 2106392.60 | 0.00 | 5127184.90 | 672236.61 | 474196.57 | 0.145145E+10 | 0.00 | 0.85 |
June | 0.332086E+09 | 0.128562E+09 | 0.00 | 5296975.68 | 9155217.93 | 0.00 | 0.556069E+09 | 0.00 | 0.68 |
July | 51867511.98 | 0.633314E+09 | 0.00 | 752358.13 | 67048763.38 | 0.00 | 12929761.32 | 0.00 | 0.57 |
August | 0.133667E+09 | 0.362219E+09 | 0.00 | 2652501.17 | 23832551.83 | 0.00 | 0.150778E+09 | 0.00 | 0.71 |
September | 0.451788E+09 | 52212181.88 | 0.00 | 4544244.98 | 9781699.58 | 0.00 | 0.588289E+09 | 0.00 | 0.77 |
October | 0.166326E+10 | 3333545.81 | 0.00 | 2099011.84 | 1962170.89 | 39280680.33 | 0.676616E+09 | 0.00 | 0.69 |
November | 0.261384E+10 | 0.00 | 0.00 | 153366.60 | 0.00 | 0.190219E+09 | 0.216095E+09 | 0.00 | 0.50 |
December | 0.207799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983275E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.165806E+11 | 0.118175E+10 | 0.00 | 24358239.41 | 0.112453E+09 | 0.264965E+10 | 0.561944E+10 | 0.00 | 0.61 |
Minimum of Months | 51867511.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.261384E+10 | 0.633314E+09 | 0.00 | 5296975.68 | 67048763.38 | 0.983275E+09 | 0.145145E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279357E+10 | 0.00 | 0.00 | 15691.61 | 0.00 | 0.671651E+09 | 26254246.13 | 0.00 | 0.72 |
February | 0.256567E+10 | 0.00 | 0.00 | 285521.48 | 0.00 | 0.310024E+09 | 0.247173E+09 | 0.00 | 0.78 |
March | 0.230572E+10 | 0.00 | 0.00 | 1702771.88 | 0.00 | 45674159.52 | 0.140374E+10 | 0.00 | 1.11 |
April | 0.955966E+09 | 0.00 | 0.00 | 5671656.66 | 0.00 | 1291168.86 | 0.263268E+10 | 0.00 | 1.54 |
May | 0.739056E+09 | 2055229.56 | 0.00 | 6865162.05 | 748458.24 | 0.00 | 0.229660E+10 | 0.00 | 1.64 |
June | 0.272894E+09 | 0.137428E+09 | 0.00 | 6626064.44 | 5720374.50 | 0.00 | 0.839265E+09 | 0.00 | 1.31 |
July | 53884598.23 | 0.685925E+09 | 0.00 | 827448.24 | 69345988.83 | 0.00 | 17776138.24 | 0.00 | 1.04 |
August | 0.124455E+09 | 0.400813E+09 | 0.00 | 3255776.04 | 30317688.14 | 0.00 | 0.221155E+09 | 0.00 | 1.33 |
September | 0.481589E+09 | 39566470.63 | 0.00 | 5618809.26 | 16777469.97 | 0.00 | 0.844854E+09 | 0.00 | 1.47 |
October | 0.151732E+10 | 1319875.30 | 0.00 | 3213420.95 | 4473260.22 | 35071660.14 | 0.132501E+10 | 0.00 | 1.28 |
November | 0.282392E+10 | 0.00 | 0.00 | 461029.67 | 0.00 | 86506926.68 | 0.477929E+09 | 0.00 | 0.88 |
December | 0.271753E+10 | 0.00 | 0.00 | 6280.29 | 0.00 | 0.676878E+09 | 13951469.14 | 0.00 | 0.62 |
Annual Sum or Average | 0.173516E+11 | 0.126711E+10 | 0.00 | 34549632.57 | 0.127383E+09 | 0.182710E+10 | 0.103464E+11 | 0.00 | 1.14 |
Minimum of Months | 53884598.23 | 0.00 | 0.00 | 6280.29 | 0.00 | 0.00 | 13951469.14 | 0.00 | 0.62 |
Maximum of Months | 0.282392E+10 | 0.685925E+09 | 0.00 | 6865162.05 | 69345988.83 | 0.676878E+09 | 0.263268E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147641E+10 | 0.00 | 0.00 | 9283697.28 | 0.00 | 0.497231E+09 | 0.330227E+10 | 0.00 | 0.75 |
February | 0.123505E+10 | 0.00 | 0.00 | 8503352.47 | 0.00 | 0.248946E+09 | 0.344223E+10 | 0.00 | 0.82 |
March | 0.158180E+10 | 0.00 | 0.00 | 6191355.84 | 0.00 | 0.105963E+09 | 0.310617E+10 | 0.00 | 0.94 |
April | 0.121472E+10 | 0.00 | 0.00 | 5378369.60 | 0.00 | 5404735.84 | 0.213987E+10 | 0.00 | 0.98 |
May | 0.945300E+09 | 2477549.08 | 0.00 | 5473347.73 | 724627.40 | 511153.11 | 0.155712E+10 | 0.00 | 0.92 |
June | 0.388282E+09 | 0.127805E+09 | 0.00 | 5259773.88 | 11563218.67 | 0.00 | 0.548787E+09 | 0.00 | 0.70 |
July | 56772185.07 | 0.650425E+09 | 0.00 | 745504.81 | 84703132.17 | 0.00 | 12821442.63 | 0.00 | 0.60 |
August | 0.148181E+09 | 0.408850E+09 | 0.00 | 3071249.95 | 27913529.40 | 0.00 | 0.167742E+09 | 0.00 | 0.80 |
September | 0.428082E+09 | 82770549.56 | 0.00 | 7685517.01 | 9369942.05 | 0.00 | 0.876957E+09 | 0.00 | 1.04 |
October | 0.959175E+09 | 6292227.01 | 0.00 | 11576371.83 | 443043.45 | 34578359.10 | 0.341326E+10 | 0.00 | 1.28 |
November | 0.123769E+10 | 0.00 | 0.00 | 13061141.71 | 0.00 | 52107508.89 | 0.474128E+10 | 0.00 | 0.99 |
December | 0.140881E+10 | 0.00 | 0.00 | 12518788.38 | 0.00 | 0.356814E+09 | 0.383128E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.110803E+11 | 0.127862E+10 | 0.00 | 88748470.50 | 0.134717E+09 | 0.130156E+10 | 0.271398E+11 | 0.00 | 0.87 |
Minimum of Months | 56772185.07 | 0.00 | 0.00 | 745504.81 | 0.00 | 0.00 | 12821442.63 | 0.00 | 0.60 |
Maximum of Months | 0.158180E+10 | 0.650425E+09 | 0.00 | 13061141.71 | 84703132.17 | 0.497231E+09 | 0.474128E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257407E+10 | 0.00 | 0.00 | 418805.97 | 0.00 | 0.921383E+09 | 0.425144E+09 | 0.00 | 0.81 |
February | 0.239685E+10 | 0.00 | 0.00 | 1211390.74 | 0.00 | 0.499125E+09 | 0.741685E+09 | 0.00 | 0.92 |
March | 0.299514E+10 | 0.00 | 0.00 | 1986333.51 | 0.00 | 0.173941E+09 | 0.110562E+10 | 0.00 | 1.29 |
April | 0.201460E+10 | 0.00 | 0.00 | 3774323.25 | 0.00 | 8461447.86 | 0.144427E+10 | 0.00 | 1.60 |
May | 0.151887E+10 | 3081177.56 | 0.00 | 4236189.26 | 788398.53 | 812046.57 | 0.127211E+10 | 0.00 | 1.61 |
June | 0.568361E+09 | 0.127438E+09 | 0.00 | 3934504.63 | 19543229.82 | 347464.39 | 0.410832E+09 | 0.00 | 1.17 |
July | 67998018.98 | 0.507668E+09 | 0.00 | 664539.51 | 0.182897E+09 | 0.00 | 10803535.16 | 0.00 | 0.94 |
August | 0.210423E+09 | 0.305259E+09 | 0.00 | 2125736.09 | 86935461.84 | 0.00 | 0.114444E+09 | 0.00 | 1.19 |
September | 0.769496E+09 | 42371780.16 | 0.00 | 3787978.63 | 20685210.54 | 0.00 | 0.454735E+09 | 0.00 | 1.39 |
October | 0.214259E+10 | 1527139.36 | 0.00 | 2905512.89 | 4983801.32 | 55168576.27 | 0.923070E+09 | 0.00 | 1.41 |
November | 0.284889E+10 | 0.00 | 0.00 | 1083539.08 | 0.00 | 0.217492E+09 | 0.865634E+09 | 0.00 | 1.03 |
December | 0.243808E+10 | 0.00 | 0.00 | 355979.61 | 0.00 | 0.931439E+09 | 0.443265E+09 | 0.00 | 0.70 |
Annual Sum or Average | 0.205454E+11 | 0.987346E+09 | 0.00 | 26484833.18 | 0.315833E+09 | 0.280817E+10 | 0.821161E+10 | 0.00 | 1.17 |
Minimum of Months | 67998018.98 | 0.00 | 0.00 | 355979.61 | 0.00 | 0.00 | 10803535.16 | 0.00 | 0.70 |
Maximum of Months | 0.299514E+10 | 0.507668E+09 | 0.00 | 4236189.26 | 0.182897E+09 | 0.931439E+09 | 0.144427E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397158E+09 | 0.00 | 0.00 | 0.33 |
February | 0.204965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234548E+09 | 0.00 | 0.00 | 0.36 |
March | 0.254106E+10 | 0.00 | 0.00 | 14706.49 | 0.00 | 33093007.81 | 53877586.43 | 0.00 | 0.50 |
April | 0.146704E+10 | 14319.45 | 0.00 | 1067510.53 | 630453.19 | 232750.30 | 0.502611E+09 | 0.00 | 0.56 |
May | 0.842738E+09 | 4631779.67 | 0.00 | 2875254.64 | 1703732.35 | 0.00 | 0.790443E+09 | 0.00 | 0.59 |
June | 0.340728E+09 | 0.146421E+09 | 0.00 | 2679612.13 | 8635275.42 | 0.00 | 0.344187E+09 | 0.00 | 0.51 |
July | 50156241.18 | 0.559256E+09 | 0.00 | 264606.73 | 49738435.31 | 0.00 | 7941059.45 | 0.00 | 0.44 |
August | 0.119944E+09 | 0.378927E+09 | 0.00 | 1793707.26 | 21874495.22 | 0.00 | 0.150235E+09 | 0.00 | 0.58 |
September | 0.326522E+09 | 70208580.87 | 0.00 | 4736370.58 | 13979182.75 | 0.00 | 0.640554E+09 | 0.00 | 0.64 |
October | 0.122673E+10 | 3674798.06 | 0.00 | 2875531.02 | 1072773.86 | 0.00 | 0.950323E+09 | 0.00 | 0.61 |
November | 0.219006E+10 | 0.00 | 0.00 | 468298.26 | 0.00 | 8844165.10 | 0.507861E+09 | 0.00 | 0.44 |
December | 0.234427E+10 | 0.00 | 0.00 | 3471.18 | 0.00 | 0.172984E+09 | 27451846.49 | 0.00 | 0.29 |
Annual Sum or Average | 0.156817E+11 | 0.116313E+10 | 0.00 | 16779068.82 | 97634348.10 | 0.846859E+09 | 0.397548E+10 | 0.00 | 0.49 |
Minimum of Months | 50156241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.254106E+10 | 0.559256E+09 | 0.00 | 4736370.58 | 49738435.31 | 0.397158E+09 | 0.950323E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264537E+10 | 0.00 | 0.00 | 12819.44 | 0.00 | 0.257718E+09 | 22636122.76 | 0.00 | 0.60 |
February | 0.237559E+10 | 0.00 | 0.00 | 151670.81 | 0.00 | 81495755.23 | 0.137124E+09 | 0.00 | 0.64 |
March | 0.217491E+10 | 0.00 | 0.00 | 955899.04 | 0.00 | 7421429.76 | 0.882231E+09 | 0.00 | 0.91 |
April | 0.808743E+09 | 400016.85 | 0.00 | 4545020.11 | 332410.51 | 0.00 | 0.195269E+10 | 0.00 | 1.20 |
May | 0.582179E+09 | 5673139.79 | 0.00 | 5515284.93 | 1486314.47 | 0.00 | 0.176366E+10 | 0.00 | 1.26 |
June | 0.251326E+09 | 0.158952E+09 | 0.00 | 4526011.00 | 6038849.84 | 0.00 | 0.669451E+09 | 0.00 | 1.04 |
July | 47889932.26 | 0.638885E+09 | 0.00 | 589880.85 | 36818989.67 | 0.00 | 21720091.32 | 0.00 | 0.85 |
August | 0.119446E+09 | 0.427319E+09 | 0.00 | 2640109.05 | 19043053.64 | 0.00 | 0.228508E+09 | 0.00 | 1.12 |
September | 0.295410E+09 | 65683492.22 | 0.00 | 6149275.72 | 15254078.31 | 0.00 | 0.100085E+10 | 0.00 | 1.26 |
October | 0.998000E+09 | 3703176.23 | 0.00 | 4608342.70 | 1216558.81 | 131740.17 | 0.179172E+10 | 0.00 | 1.18 |
November | 0.188575E+10 | 0.00 | 0.00 | 1415329.11 | 0.00 | 393589.60 | 0.124078E+10 | 0.00 | 0.80 |
December | 0.277381E+10 | 0.00 | 0.00 | 16419.85 | 0.00 | 89480717.46 | 22475794.55 | 0.00 | 0.52 |
Annual Sum or Average | 0.149584E+11 | 0.130062E+10 | 0.00 | 31126062.62 | 80190255.24 | 0.436641E+09 | 0.973385E+10 | 0.00 | 0.95 |
Minimum of Months | 47889932.26 | 0.00 | 0.00 | 12819.44 | 0.00 | 0.00 | 21720091.32 | 0.00 | 0.52 |
Maximum of Months | 0.277381E+10 | 0.638885E+09 | 0.00 | 6149275.72 | 36818989.67 | 0.257718E+09 | 0.195269E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133682E+10 | 0.00 | 0.00 | 2465220.39 | 0.00 | 0.824959E+09 | 0.134320E+10 | 0.00 | 0.50 |
February | 0.134529E+10 | 0.00 | 0.00 | 1869285.58 | 0.00 | 0.580395E+09 | 0.966445E+09 | 0.00 | 0.50 |
March | 0.190317E+10 | 0.00 | 0.00 | 1136019.86 | 0.00 | 0.496174E+09 | 0.566826E+09 | 0.00 | 0.58 |
April | 0.167092E+10 | 394669.39 | 0.00 | 1275258.86 | 320516.26 | 0.235347E+09 | 0.262337E+09 | 0.00 | 0.63 |
May | 0.130692E+10 | 5369027.09 | 0.00 | 2065832.18 | 1846232.96 | 0.174572E+09 | 0.269888E+09 | 0.00 | 0.63 |
June | 0.487702E+09 | 0.185485E+09 | 0.00 | 2471422.26 | 11159564.68 | 41483350.05 | 0.169255E+09 | 0.00 | 0.55 |
July | 59482411.47 | 0.668071E+09 | 0.00 | 200904.60 | 69040433.29 | 0.00 | 3981929.07 | 0.00 | 0.51 |
August | 0.178616E+09 | 0.481934E+09 | 0.00 | 1788774.49 | 30871396.69 | 1834356.23 | 99665889.19 | 0.00 | 0.67 |
September | 0.379776E+09 | 0.114762E+09 | 0.00 | 7676873.11 | 14432751.42 | 47132325.15 | 0.721631E+09 | 0.00 | 0.86 |
October | 0.852664E+09 | 7736604.85 | 0.00 | 9738032.10 | 289239.42 | 0.224032E+09 | 0.243483E+10 | 0.00 | 1.10 |
November | 0.119187E+10 | 0.00 | 0.00 | 5704316.33 | 0.00 | 0.255521E+09 | 0.315776E+10 | 0.00 | 0.77 |
December | 0.125809E+10 | 0.00 | 0.00 | 3117369.43 | 0.00 | 0.648118E+09 | 0.166138E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.119713E+11 | 0.146375E+10 | 0.00 | 39509309.20 | 0.127960E+09 | 0.352957E+10 | 0.116572E+11 | 0.00 | 0.64 |
Minimum of Months | 59482411.47 | 0.00 | 0.00 | 200904.60 | 0.00 | 0.00 | 3981929.07 | 0.00 | 0.43 |
Maximum of Months | 0.190317E+10 | 0.668071E+09 | 0.00 | 9738032.10 | 69040433.29 | 0.824959E+09 | 0.315776E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259583E+10 | 0.00 | 0.00 | 243076.55 | 0.00 | 0.295176E+09 | 0.254892E+09 | 0.00 | 0.64 |
February | 0.231279E+10 | 0.00 | 0.00 | 659312.71 | 0.00 | 0.149288E+09 | 0.371940E+09 | 0.00 | 0.71 |
March | 0.277214E+10 | 0.00 | 0.00 | 999311.58 | 0.00 | 26334717.50 | 0.486125E+09 | 0.00 | 1.00 |
April | 0.168213E+10 | 330720.96 | 0.00 | 2226482.63 | 455858.93 | 0.00 | 0.835931E+09 | 0.00 | 1.15 |
May | 0.113678E+10 | 5803321.21 | 0.00 | 2897693.13 | 2867342.63 | 0.00 | 0.896531E+09 | 0.00 | 1.16 |
June | 0.482226E+09 | 0.171473E+09 | 0.00 | 1970707.45 | 11728680.40 | 0.00 | 0.286954E+09 | 0.00 | 0.89 |
July | 61761396.67 | 0.523952E+09 | 0.00 | 242071.47 | 82074679.25 | 0.00 | 8851543.30 | 0.00 | 0.72 |
August | 0.176969E+09 | 0.374221E+09 | 0.00 | 1382440.25 | 25794313.25 | 0.00 | 0.116946E+09 | 0.00 | 0.93 |
September | 0.469830E+09 | 66066470.38 | 0.00 | 4435360.27 | 16757082.63 | 0.00 | 0.596000E+09 | 0.00 | 1.07 |
October | 0.138780E+10 | 4126578.41 | 0.00 | 3595988.87 | 1217849.18 | 140980.89 | 0.131542E+10 | 0.00 | 1.18 |
November | 0.251574E+10 | 0.00 | 0.00 | 1161434.31 | 0.00 | 1417165.60 | 0.934623E+09 | 0.00 | 0.89 |
December | 0.261627E+10 | 0.00 | 0.00 | 332362.42 | 0.00 | 0.149901E+09 | 0.339656E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.182103E+11 | 0.114597E+10 | 0.00 | 20146241.64 | 0.140896E+09 | 0.622258E+09 | 0.644387E+10 | 0.00 | 0.91 |
Minimum of Months | 61761396.67 | 0.00 | 0.00 | 242071.47 | 0.00 | 0.00 | 8851543.30 | 0.00 | 0.56 |
Maximum of Months | 0.277214E+10 | 0.523952E+09 | 0.00 | 4435360.27 | 82074679.25 | 0.295176E+09 | 0.131542E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380711E+09 | 0.00 | 0.00 | 0.38 |
February | 0.233127E+10 | 0.00 | 0.00 | 129611.05 | 0.00 | 0.151948E+09 | 0.121897E+09 | 0.00 | 0.40 |
March | 0.210116E+10 | 0.00 | 0.00 | 1085120.29 | 0.00 | 12114273.17 | 0.843958E+09 | 0.00 | 0.56 |
April | 0.100694E+10 | 340977.53 | 0.00 | 3569490.55 | 303748.19 | 0.00 | 0.144081E+10 | 0.00 | 0.70 |
May | 0.631199E+09 | 5692431.22 | 0.00 | 5438793.67 | 1592434.18 | 0.00 | 0.148821E+10 | 0.00 | 0.76 |
June | 0.286597E+09 | 0.185530E+09 | 0.00 | 4309526.57 | 6607428.93 | 0.00 | 0.568984E+09 | 0.00 | 0.65 |
July | 72368023.44 | 0.716089E+09 | 0.00 | 659801.25 | 41679249.57 | 0.00 | 18182204.49 | 0.00 | 0.56 |
August | 0.131749E+09 | 0.443396E+09 | 0.00 | 2200853.71 | 15499622.27 | 0.00 | 0.181466E+09 | 0.00 | 0.67 |
September | 0.356697E+09 | 72332134.16 | 0.00 | 4709776.66 | 12795998.36 | 0.00 | 0.660914E+09 | 0.00 | 0.68 |
October | 0.132448E+10 | 3063736.12 | 0.00 | 2879731.50 | 1425868.74 | 879348.26 | 0.986862E+09 | 0.00 | 0.64 |
November | 0.219336E+10 | 0.00 | 0.00 | 668536.90 | 0.00 | 22672439.72 | 0.685207E+09 | 0.00 | 0.46 |
December | 0.267988E+10 | 0.00 | 0.00 | 15023.46 | 0.00 | 0.242074E+09 | 30977278.33 | 0.00 | 0.33 |
Annual Sum or Average | 0.157442E+11 | 0.142644E+10 | 0.00 | 25666265.61 | 79904350.23 | 0.810399E+09 | 0.702747E+10 | 0.00 | 0.57 |
Minimum of Months | 72368023.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.267988E+10 | 0.716089E+09 | 0.00 | 5438793.67 | 41679249.57 | 0.380711E+09 | 0.148821E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332727E+10 | 0.00 | 0.00 | 145958.63 | 0.00 | 0.379351E+09 | 0.126628E+09 | 0.00 | 0.76 |
February | 0.286149E+10 | 0.00 | 0.00 | 590944.27 | 0.00 | 94685694.90 | 0.406920E+09 | 0.00 | 0.81 |
March | 0.238810E+10 | 0.00 | 0.00 | 2209302.33 | 0.00 | 6776233.94 | 0.166566E+10 | 0.00 | 1.18 |
April | 0.102763E+10 | 425382.71 | 0.00 | 6055606.70 | 386463.48 | 0.00 | 0.275128E+10 | 0.00 | 1.54 |
May | 0.779976E+09 | 6497955.85 | 0.00 | 6997790.53 | 2026078.39 | 0.00 | 0.232622E+10 | 0.00 | 1.58 |
June | 0.326414E+09 | 0.179517E+09 | 0.00 | 5634479.01 | 6663254.43 | 0.00 | 0.868722E+09 | 0.00 | 1.31 |
July | 89750410.20 | 0.741031E+09 | 0.00 | 880005.82 | 51765972.90 | 0.00 | 29808139.30 | 0.00 | 1.05 |
August | 0.178353E+09 | 0.462852E+09 | 0.00 | 2868417.13 | 25143840.78 | 0.00 | 0.248815E+09 | 0.00 | 1.31 |
September | 0.553758E+09 | 55113465.84 | 0.00 | 5544324.83 | 22884202.51 | 0.00 | 0.915499E+09 | 0.00 | 1.41 |
October | 0.163556E+10 | 2037735.74 | 0.00 | 3749418.53 | 3201267.11 | 5168531.44 | 0.159097E+10 | 0.00 | 1.32 |
November | 0.289163E+10 | 0.00 | 0.00 | 1135474.32 | 0.00 | 10632439.86 | 0.851160E+09 | 0.00 | 0.94 |
December | 0.344710E+10 | 0.00 | 0.00 | 85718.62 | 0.00 | 0.210942E+09 | 0.100490E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.195070E+11 | 0.144747E+10 | 0.00 | 35897440.72 | 0.112071E+09 | 0.707556E+09 | 0.118822E+11 | 0.00 | 1.16 |
Minimum of Months | 89750410.20 | 0.00 | 0.00 | 85718.62 | 0.00 | 0.00 | 29808139.30 | 0.00 | 0.66 |
Maximum of Months | 0.344710E+10 | 0.741031E+09 | 0.00 | 6997790.53 | 51765972.90 | 0.379351E+09 | 0.275128E+10 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159861E+10 | 0.00 | 0.00 | 14236699.57 | 0.00 | 0.180221E+09 | 0.366507E+10 | 0.00 | 0.76 |
February | 0.128069E+10 | 0.00 | 0.00 | 11766172.26 | 0.00 | 68561237.20 | 0.365477E+10 | 0.00 | 0.83 |
March | 0.146760E+10 | 0.00 | 0.00 | 7390001.12 | 0.00 | 6022970.87 | 0.328996E+10 | 0.00 | 0.96 |
April | 0.965468E+09 | 694490.99 | 0.00 | 5730520.29 | 105435.63 | 0.00 | 0.215430E+10 | 0.00 | 0.90 |
May | 0.747551E+09 | 6927864.08 | 0.00 | 5714731.43 | 1734570.09 | 0.00 | 0.155004E+10 | 0.00 | 0.82 |
June | 0.356493E+09 | 0.187083E+09 | 0.00 | 4098154.17 | 8614325.28 | 0.00 | 0.543095E+09 | 0.00 | 0.67 |
July | 80368594.15 | 0.752884E+09 | 0.00 | 598197.59 | 45498591.02 | 0.00 | 17471964.51 | 0.00 | 0.58 |
August | 0.152149E+09 | 0.514314E+09 | 0.00 | 2357497.66 | 17023156.01 | 0.00 | 0.188021E+09 | 0.00 | 0.76 |
September | 0.354916E+09 | 0.122016E+09 | 0.00 | 7553826.24 | 12738510.91 | 0.00 | 0.879230E+09 | 0.00 | 0.91 |
October | 0.797335E+09 | 6714251.67 | 0.00 | 14159014.95 | 523335.18 | 810441.61 | 0.352964E+10 | 0.00 | 1.22 |
November | 0.107504E+10 | 0.00 | 0.00 | 19049858.84 | 0.00 | 2658582.94 | 0.508538E+10 | 0.00 | 1.00 |
December | 0.141573E+10 | 0.00 | 0.00 | 20412568.74 | 0.00 | 0.121270E+09 | 0.436516E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.102920E+11 | 0.159063E+10 | 0.00 | 0.113067E+09 | 86237924.12 | 0.379544E+09 | 0.289221E+11 | 0.00 | 0.84 |
Minimum of Months | 80368594.15 | 0.00 | 0.00 | 598197.59 | 0.00 | 0.00 | 17471964.51 | 0.00 | 0.58 |
Maximum of Months | 0.159861E+10 | 0.752884E+09 | 0.00 | 20412568.74 | 45498591.02 | 0.180221E+09 | 0.508538E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:41:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308738E+10 | 0.00 | 0.00 | 611215.03 | 0.00 | 0.454800E+09 | 0.507168E+09 | 0.00 | 0.81 |
February | 0.269337E+10 | 0.00 | 0.00 | 1434358.33 | 0.00 | 0.180362E+09 | 0.793212E+09 | 0.00 | 0.91 |
March | 0.305450E+10 | 0.00 | 0.00 | 2113940.02 | 0.00 | 22808280.68 | 0.110730E+10 | 0.00 | 1.27 |
April | 0.183013E+10 | 892473.44 | 0.00 | 3766584.90 | 106156.08 | 600740.39 | 0.143721E+10 | 0.00 | 1.47 |
May | 0.125587E+10 | 7777407.55 | 0.00 | 4098826.52 | 3231619.23 | 0.00 | 0.133257E+10 | 0.00 | 1.45 |
June | 0.586511E+09 | 0.199127E+09 | 0.00 | 2648842.37 | 12968375.35 | 0.00 | 0.375305E+09 | 0.00 | 1.12 |
July | 0.110177E+09 | 0.626734E+09 | 0.00 | 396807.05 | 0.117932E+09 | 0.00 | 8270931.68 | 0.00 | 0.92 |
August | 0.259912E+09 | 0.412334E+09 | 0.00 | 1348406.85 | 50083428.97 | 0.00 | 0.107264E+09 | 0.00 | 1.13 |
September | 0.711274E+09 | 64946516.83 | 0.00 | 3646539.55 | 23377890.95 | 0.00 | 0.518620E+09 | 0.00 | 1.23 |
October | 0.211343E+10 | 3336759.39 | 0.00 | 3178728.05 | 2199678.74 | 7721731.50 | 0.104029E+10 | 0.00 | 1.34 |
November | 0.299875E+10 | 0.00 | 0.00 | 1362652.81 | 0.00 | 30038808.54 | 0.104301E+10 | 0.00 | 1.04 |
December | 0.310963E+10 | 0.00 | 0.00 | 581398.39 | 0.00 | 0.326931E+09 | 0.530724E+09 | 0.00 | 0.70 |
Annual Sum or Average | 0.218109E+11 | 0.131515E+10 | 0.00 | 25188299.87 | 0.209899E+09 | 0.102326E+10 | 0.880095E+10 | 0.00 | 1.12 |
Minimum of Months | 0.110177E+09 | 0.00 | 0.00 | 396807.05 | 0.00 | 0.00 | 8270931.68 | 0.00 | 0.70 |
Maximum of Months | 0.310963E+10 | 0.626734E+09 | 0.00 | 4098826.52 | 0.117932E+09 | 0.454800E+09 | 0.143721E+10 | 0.00 | 1.47 |